Burkert 8045 Insertion magnetic inductive flowmeter User Manual
The Burkert 8045 insertion electromagnetic flowmeter is designed to accurately measure flow rates of conductive liquids in various industrial applications. With its compact design and easy installation, it provides reliable flow measurement in pipes ranging from DN15 to DN2500. The 8045 features a wide flow range, high accuracy, and fast response time, making it suitable for a variety of liquids, including water, chemicals, and slurries. Its robust construction and IP65 protection rating ensure reliable operation even in harsh environments.
Advertisement
Advertisement
Type 8045
Insertion electromagnetic flowmeter
Magnetisch-induktives Durchfluss-Messgerät, Insertion
Débitmètre électromagnétique à insertion
Quickstart
English Deutsch Français
We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous réserve de modifications techniques.
© Bürkert SAS, 2012 - 2019
Quickstart 1904/04_EU-ML 00563855 / Original FR
Type 8045
1. About the QuickstArt.........................................................................4
3. bAsic sAfety informAtion ...............................................................5
4. GenerAl informAtion ...........................................................................7
5. description of the rAtinG plAte ...............................................7
7. instAllAtion And wirinG .................................................................13
9. mAintenAnce And troubleshootinG ..................................32
10. pAckAGinG, trAnsport ...................................................................32
12. disposAl of the device .................................................................32
English 3
Type 8045
AbouttheQuickstart
1. AbouT The QuicksTArT
The Quickstart describes the life cycle of the device. Please keep this
Quickstart in a safe place, accessible to all users and any new owners.
important safety information.
Respect the safety instructions. Study in particular the chapters
entitled 2. Intended use and 3. Basic safety information.
▶ The Quickstart must be read and understood.
▶ When the symbol is marked inside or outside the device, carefully read the Operating Instructions.
The Quickstart explains how to install, set, and start-up the device.
A detailed description of the device can be found in the related
Operating Instructions available on the internet at www.burkert.com
1.1. symbols used
Danger warns against an imminent danger.
▶ Failure to observe this warning can result in death or in serious injury.
Warning warns against a potentially dangerous situation.
▶ Failure to observe this warning can result in serious injury or even death.
Caution warns against a possible risk.
▶ Failure to observe this warning can result in substantial or minor injuries. notiCe warns against material damage.
Indicates additional information, advice or important recommendations.
Refers to information contained in this Quickstart or in other documents.
▶ Indicates an instruction to be carried out to avoid a danger, a warning or a possible risk.
→ Indicates a procedure to be carried out.
1.2. Definition of the word "device"
The word "device" used within this Quickstart refers to the insertion electromagnetic flowmeter type 8045.
4 English
Type 8045
Intendeduse
2. inTenDeD use
use of the device that does not comply with the instructions could present risks to people, nearby installations and the environment.
The insertion electromagnetic flowmeter type 8045 is intended exclusively to measure flow rate in liquids.
▶ This device must be used in compliance with the characteristics and commissioning and use conditions specified in the contractual documents and in these Operating Instructions.
▶ Never use this device for security applications.
▶ This device must be protected against electromagnetic interference, ultraviolet rays and, when installed outdoors, the effects of climatic conditions.
▶ Only operate a device in perfect working order.
▶ Requirements for the safe and proper operation of the device are proper transport, storage and installation, as well as careful operation and maintenance.
▶ Only use the device as intended.
3. bAsic sAfeTy informATion
This safety information does not take into account:
• any contingencies or occurrences that may arise during installation, use and maintenance of the devices.
• the local safety regulations for which the operating company is responsible including the staff in charge of installation and maintenance.
risk of injury due to high pressure in the installation.
▶ Stop the circulation of fluid, cut off the pressure and drain the pipe before loosening the process connections. danger due to electrical voltage.
▶ If a 18...36 V DC powered version is installed either in a wet environment or outdoors, all the electrical voltages must be of max. 35 V DC.
▶ Disconnect the electrical power for all the conductors and isolate it before carrying out work on the system.
▶ Observe all applicable accident protection and safety regulations for electrical equipment. risk of injury due to high fluid temperatures.
▶ Use safety gloves to handle the device.
▶ Stop the circulation of fluid and drain the pipe before loosening the process connections. risk of injury due to the nature of the fluid.
▶ Respect the prevailing regulations on accident prevention and safety relating to the use of aggressive fluids.
English 5
6 various dangerous situations
To avoid injury take care:
▶ not to use the device in explosive atmospheres.
▶ not to use the device in an environment incompatible with the materials it is made of.
▶ not to use fluid that is incompatible with the materials the device is made of.
▶ not to subject the device to mechanical loads.
▶ not to make any modifications to the device.
▶ to prevent any unintentional power supply switch-on.
▶ to carry out the installation and maintenance work by qualified and skilled staff with the appropriate tools.
▶ to guarantee a defined or controlled restarting of the process, after a power supply interruption.
▶ to observe the general technical rules when installing and using the device.
Type 8045
Basicsafetyinformation notiCe the device may be damaged by the fluid in contact with.
▶ Systematically check the chemical compatibility of the component materials of the device and the fluids likely to come into contact with it (for example: alcohols, strong or concentrated acids, aldehydes, alkaline compounds, esters, aliphatic compounds, ketones, halogenated aromatics or hydrocarbons, oxidants and chlorinated agents). notiCe elements / components sensitive to electrostatic discharges
▶ This device contains electronic components sensitive to electrostatic discharges. They may be damaged if they are touched by an electrostatically charged person or object. In the worst case scenario, these components are instantly destroyed or go out of order as soon as they are activated.
▶ To minimise or even avoid all damage due to an electrostatic discharge, take all the precautions described in the EN 61340-
5-1 norm.
▶ Also ensure that you do not touch any of the live electrical components.
English
Type 8045
Generalinformation
4. GenerAl informATion
4.1. manufacturer's address and international contacts
To contact the manufacturer of the device, use following address:
Bürkert SAS
Rue du Giessen
BP 21
F-67220 TRIEMBACH-AU-VAL
You may also contact your local Bürkert sales office.
The addresses of our international sales offices are available on the internet at: www.burkert.com
4.2. Warranty conditions
The condition governing the legal warranty is the conforming use of the 8045 in observance of the operating conditions specified in this
Quickstart.
4.3. information on the internet
You can find the Operating Instructions and technical data sheets regarding the type 8045 at: www.burkert.com
5.
1
DescripTion of The rATinG plATe
2 3 4 5
FLOW 8045 SST LONG
DO1: 5-36V– 100mA
DI1: 18-36V– 10mA IP65
S/N 1000
00570481
14 13 12 11 10
SUPPLY: 18-36V– 300 mA
DO2/3: Rel 30V~ or 60V–
Fluid: PN16:-15/110°C
9
W44MU
8 7 6
FLOW
15
English 7
1. Measured value and type of the device
2. Specification of the flow sensor
3. Specification of the DO1 digital output
4. Specifications of the relay outputs DO2 and DO3
5. Electrical power supply and current consumption
6. Manufacturing code
7. Conformity marking
8. Warning: before using the device, take into account the technical specifications described in the Operating Instructions.
9. Certification
10. Fluid temperature range and fluid nominal pressure
11. Protection class of the device
12. Specification of the DI1 digital input
13. Serial number
14. Order code
15. Shows the flow direction
Fig. 1 : Rating plate of the 8045 insertion electromagnetic flowmeter (example)
Type 8045
Technicaldata
6. TechnicAl DATA
6.1. conditions of use
Ambient temperature –10...+60 °C
Air humidity < 85 %, non condensated height above see level max. 2000 m operating conditions Continuous equipment mobility use
Fixed installation category
Indoor and outdoor
(Protect the device against electromagnetic interference, ultraviolet rays and, when installed outdoors, against the effects of climatic conditions)
Category I according to UL/
EN 61010-1 degree of pollution Degree 2 according to UL/
EN 61010-1 protection class according to iec / en 60529
IP65 1) , if the device is wired and if the cable glands are tightened and the cover lid is screwed tight.
1) not evaluated by UL
8 English
Type 8045
Technicaldata
6.2. conformity to standards and directives
The applied standards, which verify conformity with the EU Directives, can be found on the EU Type Examination Certificate and/or the EU Declaration of Conformity (if applicable).
6.3. conformity to the pressure equipment Directive
→ Make sure the device materials are compatible with the fluid.
→ Make sure the pipe DN is adapted for the device.
The device conforms to Article 4, Paragraph 1 of the Pressure
Equipment Directive 2014/68/EU under the following conditions:
• Device used on a pipe (PS = maximum admissible pressure;
DN = nominal diameter of the pipe) type of fluid conditions
Fluid group 1, Article 4, Paragraph 1.c.i DN ≤ 25
Fluid group 2, Article 4, Paragraph 1.c.i
Fluid group 1, Article 4, Paragraph 1.c.ii
Fluid group 2, Article 4, Paragraph 1.c.ii
DN ≤ 32 or PSxDN ≤ 1000
DN ≤ 25 or PSxDN ≤ 2000
DN ≤ 200 or PS ≤ 10 or PSxDN ≤ 5000
6.4. ul certification
The devices with variable key PU01 or PU02 are UL-certified devices and comply also with the following standards:
• UL 61010-1
• CAN/CSA-C22.2 n°61010-1 identification on the device certification variable key
UL recognized PU01
®
Measuring
Equipment
EXXXXXX
UL listed PU02
6.5. mechanical data
part
Housing / seal material (8045 with flow sensor in pvdf)
PC / NBR material (8045 with flow sensor in stainless steel)
Black PPA / NBR
Cover with lid / seal
Front foil
M20x1,5 cable glands / seal
PC / silicone PSU / silicone
Polyester
PA / neoprene
English 9
part
Screws material (8045 with flow sensor in pvdf) material (8045 with flow sensor in stainless steel)
Stainless steel
Nut
Flow sensor
(exposed to the fluid)
Seal
PC
PVDF
PPA
Stainless steel 316L
(DIN 1.4404)
FKM
Earth ring of the flow sensor
Stainless steel 316L
(DIN 1.4404) or Alloy
C22
Electrodes holder -
Electrodes
Rating plate
8045 with a G2" nut:
FKM
-
PEEK
Stainless steel 316L (DIN 1.4404) or Alloy
C22
Polyester
Type 8045
Technicaldata
6.6. fluid data
Min. fluid conductivity
Fluid temperature
• 8045 with flow sensor in
PVDF
• 8045 with flow sensor in stainless steel
Fluid pressure
• 8045 with flow sensor in
PVDF
• 8045 with flow sensor in stainless steel
1) not evaluated by UL
20 µS/cm
The fluid temperature may be restricted by the fluid pressure, the material the flow sensor is made of and the material the S020 fitting used is made of.
• 0...+80 °C
• –15...+110 °C
The fluid pressure may be restricted by the fluid temperature, the material the flow sensor is made of, the material the S020 fitting used is made of and the DN of the fitting used.
• PN10 1)
• PN16 1)
10 English
Type 8045
Technicaldata
P (bar)
4
3
6
5
10
9
8
7
2
1
0
PVC + PP
A
PVC (PN10)
0
PVDF (PN10) /
+20 +40 +60 +80
Metal
PP (PN10)
T (°C)
A: range of use
Fig. 2 : Fluid pressure / fluid temperature dependency for a 8045 with PVDF flow sensor and a fitting S020 in metal, PVC,
PVDF or PP
P (bar)
2
1
4
3
0
6
5
8
7
12
11
10
9
16
15
14
13
PVDF
PVC + PP
Metal
(PN16) 1)
A
PVC (PN10)
DN100 for measuring devices with a clamp connection (PN10)
PP (PN10)
PVDF (PN10)
-20 0 +20 +40 +60 +80 +100 +120
T (°C)
1) Except DN100 for measuring devices with a clamp connection
A: range of use
Fig. 3 : Fluid pressure / fluid temperature dependency for a 8045 with stainless steel flow sensor and a fitting S020 in metal, PVC, PVDF or PP
English 11
6.7. electrical data
operating voltage specifications of the power source (not supplied) of the ul devices
• 18...36 V DC,
• filtered and regulated
• oscillation rate: ±5 %
• Connection to main supply: permanent (through external SELV and through LPS power supply)
• Limited power source according to UL / EN 60950-1 standards
• or limited energy circuit according to UL / EN 61010-1,
Paragraph 9.4
300 mA max. (at 18 V DC) current consumption transistor output do1
• type
• function
• frequency
• Electrical data
• duty cycle if f > 2 Hz
• NPN / PNP (wiring dependent), open collector
• pulse output (by default), user configurable
• 0...250 Hz
• 5...36 V DC, 100 mA max.
• 0,5
• min. pulse duration if f < 2 Hz
• protections
• 250 ms
• galvanically isolated, and protected against overvoltages, polarity reversals and short-circuits
12 English
Type 8045
Technicaldata relay outputs (do2 and do3)
• operating
• electrical data of the load
(non UL recognized devices)
• electrical data of the load
(UL recognized devices)
• max. breaking capacity
• life span current output Ao1
• hysteresis (by default), configurable, normally open
• 250 V AC / 3 A or
40 V DC / 3 A (resistive load)
• max. 30 V AC and
42 V peak / 3 A or max. 60 V DC / 1 A
• 750 VA (resistive load)
• min. 100000 cycles
• specification
• max. loop impedance
To use the relay outputs in a wet location, observe the following safety instruction.
• 4...20 mA, sink or source (wiring dependent), 22 mA to indicate a fault
• 1300 W at 36 V DC, 1000 W at
30 V DC, 700 W at 24 V DC,
450 W at 18 V DC digital input (di1)
• supply voltage
• input impedance
• min. pulse duration
• protections
• 18...36 V DC
• 15 k W
• 200 ms
• galvanically isolated, and protected against polarity reversals and voltage spikes
Type 8045
Installationandwiring
Danger danger due to the operation of the relay outputs of a ul device in a wet location.
▶ If a UL device is used in a wet location:
energize the relay outputs with an alternating voltage of max.
16 Vrms and 22.6 Vpeak.
or energize the relay outputs with a direct voltage of max. 35 V DC.
6.8. electrical connection
Type of connection Through two M20x1,5 cable glands
Cable specifications
• cable type
• Cross section
• Diameter of each cable:
- if only one cable is used per cable gland
- if two cables are used per cable gland
• shielded
• 0,5...1,5 mm 2
- 6...12 mm
- 4 mm, with the supplied multi-way seal
7. insTAllATion AnD WirinG
7.1. safety instructions
Danger risk of injury due to high pressure in the installation. risk of injury due to electrical voltage. risk of injury due to high fluid temperatures. risk of injury due to the nature of the fluid.
Warning risk of injury due to non-conforming installation.
▶ The electrical and fluid installation can only be carried out by qualified and skilled staff with the appropriate tools.
▶ Install appropriate safety devices (correctly rated fuse and/or circuit-breaker).
▶ Respect standard NF C 15-100 / IEC 60364.
▶ Observe mounting instructions of the fitting or sensor-fitting. risk of injury due to unintentional switch on of power supply or uncontrolled restarting of the installation.
▶ Take appropriate measures to avoid unintentional activation of the installation.
▶ Guarantee a set or controlled restarting of the process subsequent to any intervention on the device.
English 13
Protect this device against electromagnetic interference, ultraviolet rays and, when installed outdoors, the effects of the climatic conditions.
7.2. recommandations for installing the 8045 on the pipe
→ Choose an S020 fitting appropriate to the velocity of the fluid inside the pipe.
→ Install the device on the pipe in such a way that the upstream and downstream distances are respected according to the design of
the pipes, refer to standard EN ISO 5167-1 and Fig. 4:
flow direction
Type 8045
Installationandwiring
50 x DN 5 x DN
With control valve
40 x DN 5 x DN
Pipe with 2 elbows at 90° in 3 dimensions
25 x DN 5 x DN
Pipe with 2 elbows at 90°
20 x DN 5 x DN
Pipe with 1 elbow at 90° or 1
T-piece
18 x DN 5 x DN
With pipe expansion
15 x DN 5 x DN
With pipe reduction
Fig. 4 : Upstream and downstream distances depending on the design of the pipes.
→ Respect the following additional mounting conditions to ensure that the measuring device operates correctly:
14 English
Type 8045
Installationandwiring
- Preferably install the device at a 45° angle to the horizontal centre of the pipe to avoid having deposits on the electrodes and false meas-
urements due to air bubbles (see Fig. 5).
45°
- Prevent the formation of air bubbles in the pipe in the section
around the device (see Fig. 7).
- Always mount the device upstream a possible injection point in the pipe of a high-conductivity fluid (for example: acid, base, saline,...).
45°
Fig. 5 : Mounting angle on the pipe
- Ensure that the pipe is always filled in the section around the
- When mounting vertically ensure that the flow direction is in an
upward direction (see Fig. 6).
Horizontal mounting
Correct Incorrect flow direction
Correct Incorrect
Fig. 7 : Air bubbles within the pipe
→ If necessary, use a flow conditioner to improve measurement precision.
Correct
Vertical mounting
Incorrect flow direction
Correct
Fig. 6 : Filling of the pipe
Incorrect
English 15
Type 8045
Installationandwiring
7.3. installation into the pipe of a
8045 with a G2'' nut
In order to ensure a high accuracy of the measurements and good stability of the „flow zero“ point, install the device into the processed medium at least 24 hours before calibration.
→ Install the S020 fitting into the pipe taking into account the rec-
→ Check that there is a seal on the fitting and that it is not damaged.
Replace the seal if necessary.
→
Check that there is a seal (see mark 6, Fig. 8) on the flow sensor.
→
Insert the nut (see mark 3, Fig. 8) on the fitting.
→
Insert the snap ring (mark 2 Fig. 8) into the groove (mark 5
→ Position the arrow on the side of the device in the direction of the flow: the totalizers will increment.
→
Insert the device (mark 1 Fig. 8) into the fitting.
→
Tighten the nut (mark 3, Fig. 8) by hand on the device.
6
1
4
2
3
5
Electrodes
FLOW flow direction
Fig. 8 : Installation into the pipe of a 8045 with a G2'' nut
7.4. installation into the pipe of a
8045 with a clamp connection
In order to ensure a high accuracy of the measurements and good stability of the „flow zero“ point, install the device into the processed medium at least 24 hours before calibration.
→ Install the S020 fitting into the pipe taking into account the rec-
→
Install the seal (mark 3 Fig. 9) on the S020 fitting.
16 English
Type 8045
Installationandwiring
→
Make sure that the polarizing pin (mark 4 Fig. 9) is on the fitting.
→
Insert the device (mark 1 Fig. 9) into the fitting. Position the
arrow on the side of the device in the direction of the flow: the totalizers will increment.
→
Tighten by hand the clamp collar (mark 2 Fig. 9).
→ Charge the pipe to make sure the installation is tight.
1
4
3
2
7.5. Wiring
Danger risk of injury due to electrical voltage.
▶ If a 18...36 V DC powered version is installed either in a wet environment or outdoors, all the electrical voltages must be of max. 35 V DC.
▶ Disconnect the electrical power for all the conductors and isolate it before carrying out work on the system.
▶ Observe all applicable accident protection and safety regulations for electrical equipment.
Danger danger due to the operation of the relay outputs of a ul device in a wet location.
▶ If a UL device is used in a wet location:
energize the relay outputs with an alternating voltage of max.
16 Vrms and 22.6 Vpeak.
or energize the relay outputs with a direct voltage of max. 35 V DC. flow direction
Fig. 9 : Installation into the pipe of a 8045 with a clamp connection
English 17
• Use a high quality electrical power supply (filtered and regulated).
• Make sure the installation is equipotential. See chap. 7.5.1.
• Use shielded cables with a temperature limit of 80 °C minimum.
• Do not install the cables near high voltage or high frequency cables; If this cannot be avoided, observe a min. distance of 30 cm.
• Protect the power supply by means of a 300 mA fuse and a switch.
• Protect the relays by means of a max. 3 A fuse and a circuit breaker (depending on the process).
• Do not apply both a dangerous voltage and a safety extralow voltage to the relays.
Insert the supplied stopper gasket into the unused cable gland to ensure the tightness of the device.
If two cables are used in the same cable gland, first insert the supplied multi-way seal.
To wire the device:
→ Loosen the screw from the lid.
→ Flip the lid.
→ Loosen the 4 screws from the cover of the housing.
→ Remove the cover.
Type 8045
Installationandwiring
→ Loosen the nuts of the cable glands.
→ Insert the cable through the nut then through the cable gland.
→ Make sure the earth cable coming from the housing and, on a version with stainless steel sensor, the cable coming from the
flow sensor, are connected as shown in Fig. 15, chap. 7.5.2.
→
Wire acc. to chap. 7.5.1 to 7.5.3.
7.5.1. equipotentiality of the installation
To ensure the equipotentiality of the installation (power supply - device - fluid):
→ Connect together the various earth spots in the installation to eliminate the potential differences that may occur between different earthes.
→ Observe faultless earthing of the shield of the power supply cable, at both ends.
→ Connect the negative power supply terminal to the earth to suppress the effects of common mode currents. If this connection cannot be made directly, a 100 nF / 50 V capacitor can be fitted between the negative power supply terminal and the earth.
→ Special attention has to be paid if the device is installed on plastic pipes because there is no direct earthing possible.
Proper earthing is performed by earthing together the metallic instruments such as pumps or valves, that are as close as possible to the device. If no such instrument is near the device, insert metallic earth rings inside the plastic pipes upstream and downstream the device and connect these parts to the same earth. The earth rings must be in contact with the fluid.
18 English
Type 8045
Installationandwiring
Power cable shield
Pipes in plastic
Power supply
18-36VDC
+
-
1)
Power cable shield
Metal pipe
Power supply
18-36VDC
+
-
1)
Valve, pump,... (or earthing rings, not provided, inserted into the pipe)
1) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth.
Fig. 10 : Equipotentiality skeleton diagram with pipes in plastic
1) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth.
Fig. 11 : Equipotentiality skeleton diagram with pipes in metal
English 19
Type 8045
Installationandwiring
7.5.2. Terminal assignment and use of the selectors
1
A
2
4 pin ribbon cable coming from the flow sensor
B
SINK
CURRENT
SOURCE
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
DI1
-
+
OFF ON
DO2
PE
3
4
DO3
5
Selector A : see Fig. 13
Selector B : see Fig. 14
terminal block 1
Iout: 4...20 mA output (AO1)
L+: V+ (positive voltage)
L–: 0 V (power supply ground)
PE: functional earth, wired in the factory (see Fig. 15)
P+: positive transistor output (DO1)
P–: negative transistor output (DO1) terminal block 2
PE: shieldings of both the power supply cable and the AO1 and DO1 output cables terminal block 3
PE: functional earth of the DI1 digital input
–: negative signal of the DI1 input
+: positive signal of the DI1 input terminal block 4: wiring the DO2 relay output terminal block 5: wiring the DO3 relay output
Fig. 12 : Terminal assignment
20 English
Type 8045
Installationandwiring
Use switch A to configure the wiring of the 4...20 mA current output in sinking or sourcing mode.
A
SINK
CURRENT
SOURCE
Wire the current output in sourcing mode.
Fig. 13 : Sink/source switch
SINK
CURRENT
SOURCE
Wire the current output in sinking mode.
ENTER
Use the switch B to lock/unlock the key to prevent unauthorized access to the configuration of the device.
B
OFF ON OFF ON
The
ENTER
key is unlocked (default position).
ENTER
The locked.
key is
Fig. 14 : Switch to lock/unlock the ENTER key
1 2 3 4 5 6
Earth cable coming from the housing.
On a version with stainless steel flow sensor, a second cable is coming from the sensor.
Fig. 15 : Connection of the earth wire coming from the housing
(made in the factory)
7.5.3. Wiring the Do2 and Do3 relay outputs
Danger danger due to the operation of the relay outputs of a ul device in a wet location.
▶ If a UL device is used in a wet location:
energize the relay outputs with an alternating voltage of max.
16 Vrms and 22.6 Vpeak.
or energize the relay outputs with a direct voltage of max. 35 V DC.
English 21
230 VAC
230 VAC m
3 A
3 A
DO2
DO3
Fig. 16 : Wiring of the DO2 and DO3 relay outputs
7.5.4. Wiring the Ao1 current output
For safety reasons, secure the cables using a non-conducting cable clamp.
The 4...20 mA output can be wired in either sourcing or sinking mode.
Type 8045
Installationandwiring
Position the
A
switch to "SOURCE".
4...20mA input at external device
I
A
-
+ 300 mA
18-36 V DC
+
-
(*)
Power supply
SINK
CURRENT
SOURCE
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
Fig. 17 : Wiring of the 4...20 mA output (AO1) in sourcing mode
*) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth
22 English
Type 8045
Installationandwiring
Position the
-
+
4...20mA input at external device
I
A
A
switch to "SINK".
300 mA
18-36 V DC
+
-
(*)
Power supply
7.5.5. Wiring the Do1 transistor output
18-36 V DC
+
-
300 mA +
- 5-36 VDC
Power supply (*) +
-
PLC
SINK
CURRENT
SOURCE
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
Fig. 18 : Wiring of the 4...20 mA output (AO1) in sinking mode
*) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
Fig. 19 : NPN wiring of the DO1 transistor output
*) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth
English 23
18-36 V DC
+
-
300 mA
Power supply (*)
+
- 5-36 VDC
+
-
PLC
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
Fig. 20 : PNP wiring of the DO1 transistor output
*) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth
Type 8045
Installationandwiring
7.5.6. Wiring the Di1 digital input
18-36 V DC
+
-
(*)
Power supply
SINK
CURRENT
SOURCE
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
DI1
-
+
DO2
PE
Switch
DO3
24 English
Type 8045
Adjustment,commissioning
SINK
CURRENT
SOURCE
Iout L+ L- PE P+ P-
AO1
Supply
18...36 Vdc
PULSE
DO1
PE
DI1
-
+
DO2
PE
(*)
Power supply
18-36 V DC
+
-
Switch
DO3
Fig. 21 : Possible wirings of the DI1 digital input
*) If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and the earth
8. ADjusTmenT, commissioninG
8.1. safety instructions
Warning risk of injury due to non-conforming operating.
Non-conforming operating could lead to injuries and damage the device and its surroundings.
▶ The operators in charge of operating must have read and understood the contents of this quickstart.
▶ In particular, observe the safety recommendations and intended use.
▶ The device/installation must only be operated by suitably trained staff.
Warning danger due to non-conforming commissioning.
Non-conforming commissioning could lead to injuries and damage the device and its surroundings.
▶ Before commissioning, make sure that the staff in charge have read and fully understood the contents of the quickstart.
▶ In particular, observe the safety recommendations and intended use.
▶ The device / the installation must only be commissioned by suitably trained staff.
▶ Before commissioning the device, enter the K-factor of the fit-
English 25
8.2. operating levels of the device
The device has two operating levels: the Process level and the Configuration level.
Table 1 : Default settings of the device
Function Default value
LANGUAGE English
UNIT of the flow rate
UNIT of the totalizers l/min. litre
K-FACTOR 1.000
OUTPUT
AO1
OUTPUT
DO1
OUTPUT
DO2
4 mA= 0.000
20 mA= 0.000 pulse
PU= 0.00 litre
Hysteresis
2–= 0.000
Function
OUTPUT
DO3
2+= 0.000
Not inverted time delay = 0
Default value
Hysteresis
3–= 0.000
3+= 0.000
Not inverted time delay = 0
INPUT DI1 disable
FILTER 5, slow
FREQUENC. 50 Hz
CUT-OFF 0.000
BACKLIT level 9, activated for 30 s
K-SENSOR Kw= 1.000
FLOW-W. W–= 0.000
W+= 0.000
26 English
Type 8045
Adjustment,commissioning
Type 8045
Adjustment,commissioning
Process level
12.6 L/s
0......9
0......9
16.45 mA
87654 L
231 L.
ENTER
> 5 s
+
0......9
> 2 s
To reset the daily totalizer (identified by a dot after the volume units).
0......9
Parameters menu
LANGUAGE
UNit
K-FACtOR
OUtPUt iNPUt
FiLtER tOtAL
FREqUENC.
CUt-OFF
BACKLit
> 5 s
ENTER
Configuration level
END
0......9
> 2 s
Test Menu
CAL AO1
CALiB 0
FLOw
K-sENsOR
FLOw-w.
END sAVE N/Y
1) Accessible when the device status LED is orange or red.
2) If the ENTER key is unlocked.
English
Information menu 1)
mEAs. OVF
0......9
CAL. FAiL
NEG. FLOw
ENTER
2) or
END
Process level
27
Type 8045
Adjustment,commissioning
8.3. Description of the navigation keys and the state leDs
• Scrolling up the parameters
• Incrementing the figure selected
Device state LED: see following table.
• Selecting the displayed parameter
• Confirming the settings
Status LED of relay DO3 (LED ON = contact closed)
Status LED of relay DO2 (LED ON = contact closed)
• Reading the messages
• Scrolling through the parameters
• Selecting the figure on the left
28 English
Type 8045
Adjustment,commissioning
8.4. using the navigation keys
you want to... move between parameters within a level or a menu. access the Parameters menu. access the Test menu. access the Information menu. press...
• to go to the next parameter.
•
0......9
to go to the previous parameter.
ENTER
+ simultaneously for 5 s, in the Process level
0......9
+ +
ENTER
simultaneously for 5 s, in the Process level
for 2 s, in the Process level, when the device status LED is orange or red. reset the daily totalizer. select the displayed parameter. confirm the displayed value. modify a numerical value.
0......9
+ simultaneously for 2 s, when the daily totalizer is displayed in the
Process level
ENTER
ENTER
•
0......9
to increase the blinking digit.
• to select the digit at the left of the blinking digit.
• 0......9
+ to move the decimal point.
English 29
Type 8045
Adjustment,commissioning
8.5. choosing the display language
When the device is energized for the first time, the display language is English.
LANGUAGE
0......9
ENGLish
DEUtsCh
FRANçAis itALiANO
EsPANOL
→ Confirm the displayed language: The selected language is immediately active.
UNit
Fig. 22 : Diagram of the "LANGUAGE" parameter of the Parameters menu
→ If you do not want to adjust another parameter, go to the "END"
ENTER parameter of the Parameters menu and press to save the settings or not and go back to the Process level.
8.6. entering the k-factor of the fitting used
The device determines the flow rate in the pipe using the fitting
K-factor.
The K-factor of the fitting used can be entered here.
The device will use the new K-factor as soon as "SAVE
YES" is confirmed when leaving the Parameters menu.
30 English
Type 8045
Adjustment,commissioning
K-FACtOR
OUtPUt
K=10.000
The display shows the K-factor of the fitting, may it have been entered or determined by a teach-in procedure; this K-factor is currently used by the device
→ Edit the parameter.
REtURN
K=2.8500
→ Enter the K-factor (value between 0,0001 and
9999,9) of the fitting used.
→ Confirm the displayed value.
VALiD N/Y
Is only displayed if the K-factor has been changed.
→ Confirm the entered K-factor or not.
Fig. 23 : Entering the K-factor of the fitting used
→ If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press not and go back to the Process level.
ENTER
to save the settings or
English 31
9. mAinTenAnce AnD
TroubleshooTinG
9.1. safety instructions
Danger risk of injury due to high pressure in the installation. risk of injury due to electrical voltage. risk of injury due to high fluid temperatures. risk of injury due to the nature of the fluid.
Warning risk of injury due to non-conforming maintenance.
▶ Maintenance must only be carried out by qualified and skilled staff with the appropriate tools.
▶ Ensure that the restart of the installation is controlled after any interventions.
→ If a problem occurs, refer to the complete Operating Instructions available on the internet at www.burkert.com
Type 8045
Maintenanceandtroubleshooting
10. pAckAGinG, TrAnsporT
notiCe damage due to transport
Transport may damage an insufficiently protected device.
▶ Transport the device in shock-resistant packaging and away from humidity and dirt.
▶ Do not expose the device to temperatures that may exceed the admissible storage temperature range.
▶ Protect the electrical interfaces using protective plugs.
11. sTorAGe
notiCe poor storage can damage the device.
▶ Store the device in a dry place away from dust.
▶ Storage temperature of the device: –20...+60 °C.
12. DisposAl of The Device
→ Dispose of the device and its packaging in an environmentallyfriendly way. notiCe damage to the environment caused by parts contaminated by the fluid.
▶ Comply with the national and/or local regulations which concern the area of waste disposal.
32 English
www.burkert.com