INVT CHE100-055G/075P-4, CHE100-090G/110P-4 Operation Manuals
Reklāma
Reklāma
CHE Series Sensorless Vector
Control Inverter
Operation Manual
z Thank you very much for your buying CHE series sensorless vector control inverter. z Before use, please read this manual thoroughly to ensure proper usage. Keep this manual at an easily accessible place so that can refer anytime as necessary.
Safety Precautions
Please read this operation manual carefully before installation, operation, maintenance or inspection
In this manual, the safety precautions were sorted to “WARNING” or “CAUTION”.
Indicates a potentially dangerous situation which, if can not
WARNING
avoid will result in death or serious injury.
CAUTION
Indicates a potentially dangerous situation which, if can not avoid will cause minor or moderate injury and damage the device. This
Symbol is also used for warning any un-safety operation.
In some cases, even the contents of “CAUTION” still can cause serious accident.
Please follow these important precautions in any situation
★ NOTE indicate the necessary operation to ensure the device run properly.
Warning Marks are placed on the front cover of the inverter.
Please follow these indications when using the inverter.
WARNING
z May cause injury or electric shock. z Please follow the instructions in the manual before installation or operation. z Disconnect all power line before opening front cover of unit. Wait at least 1 minute until DC Bus capacitors discharge. z Use proper grounding techniques. z Never connect AC power to output UVW terminals
I
TABLE OF CONTENTS
TABLE OF CONTENTS ............................................................................................ II
LIST OF FIGURES ...................................................................................................IV
1. INTRODUCTION................................................................................................. 1
1.1 Technology Features .................................................................................... 1
1.2 Description of Name Plate ........................................................................... 2
1.3 Selection Guide ............................................................................................ 2
1.4 Parts Description .......................................................................................... 4
1.5 External Dimension ...................................................................................... 5
2. INSPECTION ...................................................................................................... 8
3. INSTALLATION................................................................................................... 9
3.1 Environmental Requirement....................................................................... 10
3.2 Installation Space ........................................................................................11
3.3 Dimension of External Keypad ................................................................ 12
3.4 Disassembly ............................................................................................... 12
4. WIRING ............................................................................................................. 14
4.1 Connection of Peripheral Devices.............................................................. 15
4.2 Terminal Configuration ............................................................................... 16
4.2.1 Main Circuit Terminals............................................................................ 16
4.2.2 Control Circuit Terminals ........................................................................ 17
4.3 Typical Wiring Diagram .............................................................................. 18
.4.4 Specifications of Breaker, Cable, Contactor and Reactor......................... 19
4.4.1 Specifications of breaker, cable and contactor....................................... 19
4.4.2 Specifications of AC input reactor, AC output reactor and DC reactor ... 21
4.4.3 Specification of braking resistor ............................................................. 22
4.5 Wiring Main Circuits ................................................................................... 23
4.5.1 Wiring at input side of main circuit ......................................................... 23
4.5.2 Wiring at inverter side of main circuit ..................................................... 24
4.5.3 Wiring at motor side of main circuit........................................................ 25
4.5.4 Wiring of regenerative unit ..................................................................... 25
4.5.5 Wiring of Common DC bus .................................................................... 26
4.5.6 Ground Wiring (PE)................................................................................ 26
4.6 Wiring Control Circuits................................................................................ 26
4.6.1 Precautions ............................................................................................ 26
4.6.2 Control circuit terminals.......................................................................... 27
4.6.3 Jumpers on control board ...................................................................... 27
4.6.4 Wiring description of size A (1AC 0.4~0.75kW) ..................................... 28
4.7 Installation Guidline to EMC Compliance................................................... 28
4.7.1 General description of EMC ................................................................... 28
4.7.2 EMC features of inverter ........................................................................ 29
4.7.3 EMC Installation Guideline..................................................................... 29
5. OPERATION ..................................................................................................... 32
5.1 Keypad Description .................................................................................... 32
5.1.1 Keypad schematic diagram.................................................................... 32
5.1.2 Key function description ......................................................................... 32
5.1.3 Indicator light description ....................................................................... 33
5.2 Operation Process...................................................................................... 34
II
5.2.1 Parameter setting................................................................................... 34
5.2.2 Fault reset .............................................................................................. 35
5.2.3 Motor parameter autotuning................................................................... 35
5.2.4 Password setting.................................................................................... 36
5.3 Running State .............................................................................................36
5.3.1 Power-on initialization ............................................................................ 36
5.3.2 Stand-by ................................................................................................. 36
5.3.3 Motor parameter autotuning................................................................... 36
5.3.4 Operation ............................................................................................... 36
5.3.5 Fault ....................................................................................................... 37
5.4 Quick Testing ..............................................................................................37
6. DETAILED FUNCTION DESCRIPTION............................................................38
6.1 P0 Group--Basic Function ..........................................................................38
6.2 P1 Group--Start and Stop Control...............................................................45
6.3 P2 Group--Motor Parameters .....................................................................47
6.4 P3 Group—Vector Control ..........................................................................49
6.5 P4 Group-- V/F Control...............................................................................50
6.6 P5 Group--Input Terminals..........................................................................52
6.7 P6 Group--Output Terminals.......................................................................57
6.8 P7 Group--Display Interface .......................................................................59
6.9 P8 Group--Enhanced Function...................................................................64
6.10 P9 Group--PID Control .............................................................................68
6.11 PA Group-- Multi-step Speed Control........................................................71
6.12 PB Group-- Protection Function ...............................................................73
6.13 PC Group--Serial Communication ............................................................76
6.14 PD Group—Supplementary Function .......................................................78
6.15 PE Group—Factory Setting ......................................................................81
7. TROUBLE SHOOTING .....................................................................................81
7.1 Fault and Trouble shooting .........................................................................81
7.2 Common Faults and Solutions....................................................................83
8. MAINTENANCE ...................................................................................................84
8.1 Daily Maintenance ......................................................................................85
8.2 Periodic Maintenance .................................................................................85
8.3 Replacement of wearing parts ....................................................................86
8.4 Warranty......................................................................................................86
9. LIST OF FUNCTION PARAMETERS ..................................................................87
Special parameter for CHE150 series high speed inverter: ...........................100
Parameters display on LCD keypad ...............................................................101
10. COMMUNICATION PROTOCOL.....................................................................108
III
LIST OF FIGURES
Figure 1.1 Nameplate of inverter....................................................................................... 2
Figure 1.2 Parts of inverters (15kw and below)................................................................. 4
Figure 1.3 Parts of inverters (18.5kw and above). ............................................................ 5
Figure 1.4 Dimension (0.4~0.75kW 1AC 220V). ............................................................... 5
Figure1.5 Dimension (0.75~15kW). .................................................................................. 6
Figure 1.6 Dimension (18.5~110kW). ............................................................................... 6
Figure 1.7 Dimension (132~315kW). ................................................................................ 6
Figure 1.8 Dimension (350~630kW). ................................................................................ 7
Figure 3.1 Relationship between output current and altitude.......................................... 10
Figure 3.2 Safe space. .................................................................................................... 11
Figure 3.3 Installation of multiple inverters...................................................................... 11
Figure 3.4 Dimension of small keypad. ........................................................................... 12
Figure 3.5 Dimension of big keypad................................................................................ 12
Figure 3.6 Disassembly of plastic cover.......................................................................... 12
Figure 3.7 Disassembly of metal plate cover. ................................................................. 13
Figure 3.8 Open inverter cabinet..................................................................................... 13
Figure 4.1 Connection of peripheral devices................................................................... 15
Figure 4.2 Main circuit terminals (0.4~0.75kW 1AC 220V). ............................................ 16
Figure 4.3 Main circuit terminals (1.5~2.2kW)................................................................. 16
Figure 4.4 Main circuit terminals (4.0~5.5kW) ................................................................ 16
Figure 4.5 Main circuit terminals (7.5~15kW).................................................................. 16
Figure 4.6 Main circuit terminals (18.5~110kW).............................................................. 16
Figure 4.7 Main circuit terminals (132~315kW)............................................................... 16
Figure 4.8 Main circuit terminals (350~630kW)............................................................... 16
Figure 4.9 Control circuit terminals (0.4~0.75kW 1AC 220V). ........................................ 17
Figure 4.10 Control circuit terminals (1.5~2.2kW)........................................................... 17
Figure 4.11 Control terminals (4.0kW and above). ......................................................... 17
Figure4. 12 Wiring diagram. ............................................................................................ 18
Figure 4.13 Wiring at input side of main circuit. .............................................................. 24
Figure 4.14 Wiring at motor side of main circuit.............................................................. 25
Figure 4.15 Wiring of regenerative unit. .......................................................................... 25
Figure 4.16 Wiring of common DC bus. .......................................................................... 26
IV
Figure 4.17 Wiring of size A (0.4~0.75kW 1AC). ............................................................ 28
Figure 5.1 Keypad schematic diagram............................................................................ 32
Figure 5.2 Flow chart of parameter setting...................................................................... 35
Figure 5.3 Quick testing diagram. ................................................................................... 38
Figure 6.1 Acceleration and deceleration time. ............................................................... 42
Figure 6.2 Effect of carrier frequency. ............................................................................. 43
Figure 6.3 Starting diagram............................................................................................. 45
Figure 6.4 DC braking diagram. ...................................................................................... 47
Figure 6.5 FWD/REV dead time diagram........................................................................ 47
Figure 6.6 ASR diagram.................................................................................................. 49
Figure 6.7 PI parameter diagram. ................................................................................... 50
Figure6.8 V/F curve diagram........................................................................................... 51
Figure 6.9 Manual torque boost diagram. ....................................................................... 51
Figure 6.10 2-wire control mode1.................................................................................... 55
Figure 6.11 2-wire control mode 2................................................................................... 55
Figure 6.12 3-wire control mode 1................................................................................... 55
Figure 6.13 3-wire control mode2.................................................................................... 56
Figure 6.14 Relationship between AI and corresponding setting.................................... 57
Figure 6.15 Relationship between AO and corresponding setting. ................................. 59
Figure 6.16 Skip frequency diagram. .............................................................................. 65
Figure 6.17 Traverse operation diagram. ........................................................................ 65
Figure 6.18 FDT level and lag diagram. .......................................................................... 67
Figure 6.19 Frequency arriving signal diagram. .............................................................. 67
Figure 6.20 PID control diagram. .................................................................................... 68
Figure 6.21 Reducing overshooting diagram. ................................................................. 69
Figure 6.22 Rapidly stabilizing diagram. ......................................................................... 70
Figure 6.23 Reducing long-cycle oscillation diagram. ..................................................... 70
Figure 6.24 Reducing short-cycle oscillation diagram..................................................... 70
Figure 6.25 Relationship between bias limit and output frequency................................. 71
Figure 6.26 Multi-steps speed operating diagram. .......................................................... 72
Figure 6.27 Motor overload protection curve................................................................... 73
Figure 6.28 Over-voltage stall function............................................................................ 75
Figure 6.29 Current limiting protection function............................................................... 76
Figure 6.30 Meaning of PC.06...................................................................................... 78
V
1
Introduction
1. INTRODUCTION
1.1 Technology Features
● Input & Output
◆ Input Voltage Range: 380/220V ±15%
◆ Input Frequency Range: 47~63Hz
◆ Output Voltage Range: 0~rated input voltage
◆ Output Frequency Range: 0~400Hz
● I/O features
◆ Programmable Digital Input:
Provide 4 terminals which can accept ON-OFF inputs
◆ Programmable Analog Input:
AI1 can accept input of 0 ~10V; AI2 can accept input of 0~10V or 0~20mA.
◆ Programmable Open Collector Output:
Provide 1 output terminal (open collector output or high-speed pulse output)
◆ Relay Output: Provide 1 output terminal.
◆ Analog Output: Provide 1 analog output terminal, whose output scope can be
0/4~20 mA or 0~10 V, as chosen..
● Main Control Function
◆ Control Mode: Sensorless Vector Control (SVC), V/F Control.
◆ Overload Capacity:
60s with 150% of rated current, 10s with 180% of rated current.
◆ Starting Torque: 150% of rated torque at 0.5Hz (SVC).
◆ Speed Adjusting Range: 1:100 (SVC)
◆ Speed Accuracy: ± 0.5% of maximum speed (SVC)
◆ Carrier Frequency: 0.5kHz ~15.0kHz.
◆ Reference Frequency Source: keypad, analog input, serial communication, multi-step speed, PID and so on. The combination of multi- modes and switching between different modes can be realized.
◆ Torque Control Function: Provide multiple torque setting source.
◆ PID Control Function
◆ Multi-Step Speed Control Function: 8 steps speed can be set.
◆ Traverse Control Function
◆ None-Stop when instantaneous power off.
◆ Speed trace Function: Start the running motor smoothly.
◆ QUICK/JOG Key: User defined shortcut key can be realized.
◆ Automatic Voltage Regulation (AVR) Function:
Automatically keep the output voltage stable when input voltage fluctuating.
◆ Up to 24 fault protections:
Protect from over current, over voltage, under voltage, over heat, phase failure, over load etc.
Introduction
1.2 Description of Name Plate
Figure 1.1 Nameplate of inverter.
1.3 Selection Guide
Model No.
Rated
Output
Power
(kW)
Rated
Input current
(A)
Rated
Output current
(A)
Motor
Power
(KW)
Size
1AC 220V ± 15%
CHE100-0R4G-S2 0.4 5.4 2.3 0.4 A
CHE100-0R7G-S2 0.75 8.2 4.5 0.75 A
CHE100-1R5G-S2 1.5 14.2 7.0 1.5 B
CHE100-2R2G-S2 2.2 23.0 10 2.2 B
3AC 220V ± 15%
CHE100-0R7G-2 0.75 5.0 4.5 0.75 A
CHE100-1R5G-2 1.5 7.7 7 1.5 B
CHE100-2R2G-2 2.2 11.0 10 2.2 B
CHE100-004G-2 4.0 17.0 16 3.7 C
CHE100-5R5G-2 5.5 21.0 20 5.5 C
CHE100-7R5G-2 7.5 31.0 30 7.5 D
CHE100-011G-2 11.0 43.0 42 11.0 E
CHE100-015G-2 15.0 56.0 55 15.0 E
CHE100-018G-2 18.5 71.0 70 18.5 E
CHE100-022G-2 22.0 81.0 80 22.0 F
2
Introduction
3AC 380V ± 15%
CHE100-0R7G-4
CHE100-1R5G-4
CHE100-2R2G-4
CHE100-004G/5R5P-4
CHE100-5R5G/7R5P-4
0.75 3.4 2.5 0.75 B
1.5 5.0 3.7 1.5 B
2.2 5.8 5 2.2 B
4.0/5.5 10/15 9/13 4.0/5.5 C
5.5/7.5 15/20 13/17 5.5/7.5 C
CHE100-7R5G/011P-4
CHE100-011G/015P-4
7.5/11 20/26 17/25 7.5/11 D
11/15 26/35 25/32 11/15 D
CHE100-015G/018P-4 15/ 18.5
35/38 32/37 15/ 18.5
D
CHE100-018G/022P-4 18.5/ 22
CHE100-022G/030P-4
38/46 37/45 18.5/ 22 E
22/30 46/62 45/60 22/30 E
CHE100-030G/037P-4 30/37 62/76 60/75 30/37 E
CHE100-037G/045P-4
CHE100-045G/055P-4
CHE100-055G/075P-4
CHE100-075G/090P-4
CHE100-090G/110P-4
CHE100-110G/132P-4
CHE100-132G/160P-4
CHE100-160G/185P-4
CHE100-185G/200P-4
CHE100-200G/220P-4
37/45 76/90 75/90 37/45 F
45/55 90/105 90/110 45/55 F
55/75 105/ 140 110/ 150 55/75 F
75/90
90/110
110/132
132/160
160/185
185/200
200/220
CHE100-220G/250P-4 220/250
140/ 160 150/ 176
160/ 210 176/ 210
210/ 240 210/ 250
240/ 290 250/ 300
290/ 330 300/ 340
330/ 370
370/ 410 380/ 415 200/220
410/ 460
340/ 380
415/ 470
75/90
90/110
110/132
132/160
160/185
185/200
220/250
G
G
G
H
H
H
I
I
CHE100-250G/280P-4 250/280
CHE100-280G/315P-4 280/315
CHE100-315G/350P-4 315/350
460/ 500
500/ 580
580/ 620
470/ 520
520/ 600
600/ 640
250/280
280/315
315/350
I
I
I
3
Introduction
1.4 Parts Description
Figure 1.2 Parts of inverters (15kw and below).
4
Figure 1.3 Parts of inverters (18.5kw and above).
1.5 External Dimension
Introduction
Figure 1.4 Dimension (0.4~0.75kW 1AC 220V).
5
Introduction
Figure1.5 Dimension (0.75~15kW).
Figure 1.6 Dimension (18.5~110kW).
Figure 1.7 Dimension (132~315kW).
6
Introduction
Figure 1.8 Dimension (350~630kW).
Power
(kW)
Size
A
(mm)
B
(mm)
Installation
Dimension
0.4~0.75
(1AC 220V)
0.75~2.2 B 110.4
170.2
237.5
H
(mm)
W
(mm)
D
(mm)
External Dimension
Installation
Hole
(mm)
132~185
200~315
H(without base)
H(with base)
I(without base)
I(with base)
270 1233
— —
500 1324
— —
1275
1490
1358
1670
490 391 13.0
490 391 —
750 402 12.5
750 402 —
7
Inspection
2. INSPECTION
CAUTION
● Don’t install or use any inverter that is damaged or have fault part, otherwise may cause injury .
Check the following items when unpacking the inverter,
1. Inspect the entire exterior of the Inverter to ensure there are no scratches or other damage caused by the transportation.
2. Ensure there is operation manual and warranty card in the packing box.
3. Inspect the nameplate and ensure it is what you ordered.
4. Ensure the optional parts are what you need if have ordered any optional parts.
Please contact the local agent if there is any damage in the inverter or optional parts.
8
Installation
3. INSTALLATION
WARNING
● The person without passing the training manipulate the device or any rule in the
“Warning” being violated, will cause severe injury or property loss. Only the person, who has passed the training on the design, installation, commissioning and operation of the device and gotten the certification, is permitted to operate this equipment.
● Input power cable must be connected tightly, and the equipment must be grounded securely.
● Even if the inverter is not running, the following terminals still have dangerous voltage:
- Power Terminals: R, S, T
- Motor Connection Terminals: U, V, W.
● When power off, should not install the inverter until 5 minutes after, which can ensure the device discharge completely.
● The section area of grounding conductor must be no less than that of power supply cable.
CAUTION
●
When moving the inverter please lift by its base and don’t lift by the panel.
Otherwise may cause the main unit fall off which may result in personal injury.
● Install the inverter on the fireproofing material (such as metal) to prevent fire.
● When need install two or more inverters in one cabinet, cooling fan should be provided to make sure that the air temperature is lower than 45°C. Otherwise it could cause fire or damage the device.
9
Installation
3.1 Environmental Requirement
3.1.1 Temperature
Environment temperature range: -10°C ~ +40°C. Inverter will be derated if ambient temperature exceeds 40°C.
3.1.2 Humidity
Less than 95% RH, without dewfall.
3.1.3 Altitude
Inverter can output the rated power when installed with altitude of lower than
1000m. It will be derated when the altitude is higher than 1000m. For details, please refer to the following figure:
Figure 3.1 Relationship between output current and altitude.
3.1.4 Impact and Vibration
It is not allowed that the inverter falls down or suffers from fierce impact or the inverter installed at the place that vibration frequently.
3.1.5 Electromagnetic Radiation
Keep away from the electromagnetic radiation source.
3.1.6 Water
Do not install the inverter at the wringing or dewfall place.
3.1.7 Air Pollution
Keep away from air pollution such as dusty, corrosive gas.
3.1.8 Storage
Do not store the inverter in the environment with direct sunlight, vapor, oil fog and vibration.
10
3.2 Installation Space
Figure 3.2 Safe space.
Figure 3.3 Installation of multiple inverters.
Notice: Add the air deflector when apply the up-down installation .
Installation
11
Installation
3.3 Dimension of External Keypad
Figure 3.4 Dimension of small keypad.
Figure 3.5 Dimension of big keypad.
3.4 Disassembly
Figure 3.6 Disassembly of plastic cover.
12
Figure 3.7 Disassembly of metal plate cover.
Installation
Figure 3.8 Open inverter cabinet.
13
Wiring
4. WIRING
WARNING
●
Wiring must be performed by the person certified in electrical work.
● Forbid testing the insulation of cable that connects the inverter with high-voltage insulation testing devices.
● Cannot install the inverter until discharged completely after the power supply is switched off for 5 minutes.
● Be sure to ground the ground terminal.
(200V class: Ground resistance should be 100 Ω or less, 400V class: Ground resistance should be 10 Ω or less, 660V class: Ground resistance should be 5 Ω or less). Otherwise, it might cause electric shock or fire.
● Connect input terminals (R, S, T) and output terminals (U, V, W) correctly.
Otherwise it will cause damage the inside part of inverter.
● Do not wire and operate the inverter with wet hands.
Otherwise there is a risk of electric shock.
CAUTION
●
Check to be sure that the voltage of the main AC power supply satisfies the rated voltage of the Inverter.
Injury or fire can occur if the voltage is not correct.
● Connect power supply cables and motor cables tightly.
14
4.1 Connection of Peripheral Devices
Wiring
Figure 4.1 Connection of peripheral devices.
15
Wiring
4.2 Terminal Configuration
4.2.1 Main Circuit Terminals (380VAC)
Figure 4.2 Main circuit terminals (0.4~0.75kW 1AC 220V).
(+) PB
R S T U V W
POWER MOTOR
Figure 4.3 Main circuit terminals (1.5~2.2kW).
(+) PB (-)
R S T U V W
POWER MOTOR
Figure 4.4 Main circuit terminals (4.0~5.5kW) .
(+) PB (-)
R S T U V W
POWER MOTOR
Figure 4.5 Main circuit terminals (7.5~15kW).
R S T
POWER
P1 (+) (-)
U V
MOTOR
Figure 4.6 Main circuit terminals (18.5~110kW).
W
R S
POWER
T U V
MOTOR
W
P1 (+) (-)
Figure 4.7 Main circuit terminals (132~315kW).
R S
POWER
T U V
MOTOR
W
P1 (+) (-)
Figure 4.8 Main circuit terminals (350~630kW).
16
Wiring
Main circuit terminal functions are summarized according to the terminal symbols in the following table. Wire the terminal correctly for the desired purposes.
Terminal Symbol Function Description
R 、 S 、 T
(+) 、 (-)
Terminals of 3 phase AC input
Spare terminals of external braking unit
(+)
P1
、
、
PB
(+)
(-)
U 、 V 、 W
Spare terminals of external braking resistor
Spare terminals of external DC reactor
Terminal of negative DC bus
Terminals of 3 phase AC output
Terminal of ground
4.2.2 Control Circuit Terminals
485+ 485S1 S2 S3 S4 COM AI2 AO Y +24V ROA ROB ROC
Figure 4.9 Control circuit terminals (0.4~0.75kW 1AC 220V).
485+ 485- +10V AO
AI1 GND AI2 S1
COM Y +24V
S2 S3 S4
ROA ROB ROC
Figure 4.10 Control circuit terminals (1.5~2.2kW).
Figure 4.11 Control terminals (4.0kW and above).
17
Wiring
4.3 Typical Wiring Diagram
Figure4. 12 Wiring diagram.
Notice
1. Inverters between 18.5KW and 90KW have built-in DC reactor which is used to improve power factor. For inverters above 110KW, it is recommended to install DC reactor between P1 and (+).
2. Inverters below 15KW have built-in braking unit. If need braking, only need to install braking resistor between PB and (+).
3. For inverters above 18.5KW, if need braking, should install external braking unit between (+) and (-).
18
Wiring
.4.4 Specifications of Breaker, Cable, Contactor and Reactor
4.4.1 Specifications of breaker, cable and contactor
Model No.
Circuit Breaker
(A)
Input/Output
Cable (mm 2 )
AC Contactor
(A)
1AC 220V ± 15%
CHE100-0R4G-S2 16 2.5 10
CHE100-0R7G-S2 16 2.5 10
CHE100-1R5G-S2 20 4 16
CHE100-2R2G-S2 32 6 20
3 A C 2 2 0 V ± 1 5 %
CHE100-0R4G-2 16 2.5 10
CHE100-0R7G-2 16 2.5 10
CHE100-1R5G-2 20 4 16
CHE100-2R2G-2 32 6 20
CHE100-004G-2 40 6 25
CHE100-5R5G-2 63 6 32
CHE100-7R5G-2 100 10 63
CHE100-011G-2 125 25 95
CHE100-015G-2 160 25 120
CHE100-018G-2 160 25 120
CHE100-022G-2 200 35 170
CHE100-030G-2 200 35 170
CHE100-037G-2 200 35 170
CHE100-045G-2 250 70 230
19
Wiring
3AC 380V ± 15%
CHE100-0R7G-4 10 2.5 10
CHE100-1R5G-4 16 2.5 10
CHE100-2R2G-4 16 2.5 10
CHE100-004G/5R5P-4 25
CHE100-5R5G/7R5P-4 25
CHE100-7R5G/011P-4 40
CHE100-011G/015P-4 63
4
4
6
6
16
16
25
32
CHE100-015G/018P-4 63
CHE100-018G/022P-4 100
CHE100-022G/030P-4 100
CHE100-030G/037P-4 125
CHE100-037G/045P-4 160
CHE100-045G/055P-4 200
CHE100-055G/075P-4 200
CHE100-075G/090P-4 250
6
10
16
25
25
35
35
70
50
63
80
95
120
135
170
230
CHE100-090G/110P-4 315
CHE100-110G/132P-4 400
70 280
95 315
CHE100-132G/160P-4 400 150 380
CHE100-160G/185P-4 630 185 450
CHE100-185G/200P-4 630 185 500
CHE100-220G/250P-4 800 150x2 630
CHE100-250G/280P-4 800 150x2 700
CHE100-280G/315P-4 1000 185x2 780
CHE100-315G/350P-4 1200 240x2 900
20
Wiring
4.4.2 Specifications of AC input reactor, AC output reactor and DC reactor
Model No. Current
( A )
Inductance
( mH )
Current
( A )
Inductance
( mH )
Current
( A )
3AC 380V ± 15%
CHE100-0R7G-4
CHE100-1R5G-4
CHE100-2R2G-4
-
5
7
-
3.8
2.5
-
5
7
-
1.5
1
-
-
-
CHE100-004G/5R5P-4 10 1.5 -
CHE100-5R5G/7R5P-4 15 1.4 15 0.25 -
CHE100-7R5G/011P-4
AC Input reactor AC Output reactor
20 1 20 -
DC reactor
Inductance
( mH
-
-
-
-
-
-
)
CHE100-011G/015P-4
CHE100-015G/018P-4
CHE100-018G/022P-4
CHE100-022G/030P-4
30 0.6 30 0.087
40 0.6 40 0.066
50
60
0.35
0.28
50
60
0.052
0.045
-
-
80
80
-
-
0.4
0.4
CHE100-030G/037P-4 80 0.19 80 0.032
CHE100-037G/045P-4 90 0.19 110 0.25
CHE100-045G/055P-4
CHE100-055G/075P-4
CHE100-075G/090P-4
CHE100-090G/110P-4
120
150
200
200
CHE100-110G/132P-4 250
CHE100-132G/160P-4 290
0.13
0.11
0.08
0.08
0.065
0.065
120
150
200
200
250
290
0.023
0.019
0.014
0.014
0.011
0.011
110
110
180
180
250
0.25
0.25
0.18
0.18
0.2
326 0.215
CHE100-160G/185P-4 330 0.05 494 0.142
CHE100-185G/200P-4 400 0.044 494 0.142
CHE100-200G/220P-4 400 0.044 494 0.142
CHE100-220G/250P-4 490 0.035 494 0.126
CHE100-250G/280P-4 530
CHE100-280G/315P-4 600
0.04
0.04
530
600
0.005
0.005
700 0.1
700 0.1
CHE100-315G/350P-4 660 0.025 800 0.08
21
Wiring
4.4.3 Specification of braking unit and braking resistor
Model No.
Braking unit
Order No.
Quantity
Braking resistor
(100% braking torque)
Specification Quantity
3AC 220V ± 15%
CHE100-0R4G-2
CHE100-0R7G-2
275
275
Ω
Ω
/75W 1
/75W 1
CHE100-1R5G-2 138 Ω /150W 1
CHE100-2R2G-2 Built-in 1 91 Ω /220W 1
CHE100-004G-2
CHE100-5R5G-2
52 Ω
37.5
/400W 1
Ω /550W 1
CHE100-7R5G-2 27.5
Ω /750W 1
CHE100-011G-2 1 19 Ω /1100W 1
1 13.6
Ω /1500W 1
CHE100-015G-2
CHE100-018G-2 DBU-055-2 1 12 Ω /1800W 1
CHE100-022G-2 1 9 Ω /2200W 1
CHE100-030G-2
CHE100-037G-2
1 6.8
Ω /3000W 1
2 11 Ω /2000W 2
DBU-055-2
CHE100-045G-2
3AC 380V ± 15%
2 9 Ω /2400W 2
CHE100-0R7G-4 900 Ω /75W 1
CHE100-1R5G-4 460 Ω /150W 1
CHE100-2R2G-4 315 Ω /220W 1
CHE100-004G/5R5P-4 175 Ω /400W 1
CHE100-5R5G/7R5P-4 120 Ω /550W 1
CHE100-7R5G/011P-4 100 Ω /750W 1
CHE100-011G/015P-4 70 Ω /1100W 1
CHE100-015G/018P-4
CHE100-018G/022P-4 DBU-055-4 1
47 Ω /1500W 1
38 Ω /2000W 1
CHE100-022G/030P-4 32 Ω /2200W 1
CHE100-030G/037P-4 23 Ω /3000W 1
CHE100-037G/045P-4 19 Ω /3700W 1
22
Wiring
CHE100-045G/055P-4
CHE100-055G/075P-4
CHE100-075G/090P-4
CHE100-090G/110P-4
CHE100-110G/132P-4
CHE100-132G/160P-4
DBU-055-4 2
16 Ω /4500W 1
13 Ω /5500W 1
19 Ω /3700W 2
16 Ω /4500W 2
13 Ω /5500W 2
5 Ω /15000W 1
CHE100-160G/185P-4
DBU-160-4
1
1 3.5
Ω /20000W 1
CHE100-185G/200P-4
CHE100-200G/220P-4
CHE100-220G/250P-4
DBU-220-4
1
1
1
3.5
3
Ω
Ω
/20000W 1
/25000W 1
3 Ω /25000W 1
CHE100-250G/280P-4
CHE100-280G/315P-4 DBU-315-4
1
1
2.5
Ω /30000W
2.5
Ω /30000W
1
1
CHE100-315G/350P-4
Notice:
1 2 Ω /35000W 1
1. Above selection is based on following condition: 700V DC braking voltage threshold, 100% braking torque and 10% usage rate.
2. Parallel connection of braking unit is helpful to improve braking capability.
3. Wire between inverter and braking unit should be less than 5m.
4. Wire between braking unit and braking resistor should be less than 10m.
5. Braking unit can be used for braking continuously for 5 minutes. When braking unit is working, temperature of cabinet will be high, user is not allowed to touch to prevent from injure.
For more details, please refer to DBU and RBU user manual.
4.5 Wiring Main Circuits
4.5.1 Wiring at input side of main circuit
4.5.1.1 Circuit breaker
It is necessary to connect a circuit breaker which is compatible with the capacity of inverter between 3ph AC power supply and power input terminals (R, S, T). The capacity of breaker is 1.5~2 times to the rated current of inverter. For details, see
<Specifications of Breaker, Cable, and Contactor>.
4.5.1.2 Contactor
In order to cut off the input power effectively when something is wrong in the system, contactor should be installed at the input side to control the on/off of the main circuit
23
Wiring power supply.
In order to prevent the rectifier damage resulted from the large current, AC reactor should be installed at the input side. It can also prevent rectifier from sudden variation of power voltage or harmonic generated by phase-control load.
4.5.1.4 Input EMC filter
The surrounding device may be disturbed by the cables when the inverter is working.
EMC filter can minimize the interference. Just like the following figure.
Figure 4.13 Wiring at input side of main circuit.
4.5.2 Wiring at inverter side of main circuit
4.5.2.1 DC reactor
Inverter from 18.5kW to 90kW have built-in DC reactor which can improve the power factor.
4.5.2.2 Braking unit and braking resistor
• Inverter of 15KW and below have built-in braking unit. In order to dissipate the regenerative energy generated by dynamic braking, the braking resistor should be installed at (+) and PB terminals. The wire length of the braking resistor should be less than 5m.
• Inverter of 18.5KW and above need connect external braking unit which should be installed at (+) and (-) terminals. The cable between inverter and braking unit should be less than 5m. The cable between braking unit and braking resistor should be less than 10m.
• The temperature of braking resistor will increase because the regenerative energy will be transformed to heat. Safety protection and good ventilation is recommended.
24
Wiring
Notice: Be sure that the electric polarity of (+) (-) terminals is right; it is not allowed to connect (+) with (-) terminals directly, otherwise damage or fire could occur.
4.5.3 Wiring at motor side of main circuit
4.5.3.1 Output Reactor
When the distance between inverter and motor is more than 50m, inverter may be tripped by over-current protection frequently because of the large leakage current resulted from the parasitic capacitance with ground. And the same time to avoid the damage of motor insulation, the output reactor should be installed.
4.5.3.2 Output EMC filter
EMC filter should be installed to minimize the leak current caused by the cable and minimize the radio noise caused by the cables between the inverter and cable.
Just see the following figure.
Figure 4.14 Wiring at motor side of main circuit.
4.5.4 Wiring of regenerative unit
Regenerative unit is used for putting the electricity generated by braking of motor to the grid. Compared with traditional 3 phase inverse parallel bridge type rectifier unit, regenerative unit uses IGBT so that the total harmonic distortion (THD) is less than 4%.
Regenerative unit is widely used for centrifugal and hoisting equipment.
Figure 4.15 Wiring of regenerative unit.
25
Wiring
4.5.5 Wiring of Common DC bus
Common DC bus method is widely used in the paper industry and chemical fiber industry which need multi-motor to coordinate. In these applications, some motors are in driving status while some others are in regenerative braking (generating electricity) status. The regenerated energy is automatically balanced through the common DC bus, which means it can supply to motors in driving status. Therefore the power consumption of whole system will be less compared with the traditional method (one inverter drives one motor).
When two motors are running at the same time (i.e. winding application), one is in driving status and the other is in regenerative status. In this case the DC buses of these two inverters can be connected in parallel so that the regenerated energy can be supplied to motors in driving status whenever it needs. Detailed wiring is shown in the following figure:
Figure 4.16 Wiring of common DC bus.
Notice: Two inverters must be the same model when connected with Common DC bus method. Be sure they are powered on at the same time.
4.5.6 Ground Wiring (PE)
In order to ensure safety and prevent electrical shock and fire, PE must be grounded with ground resistance. The ground wire should be big and short, and it is better to use copper wire (>3.5mm
2 ). When multiple inverters need to be grounded, do not loop the ground wire.
4.6 Wiring Control Circuits
4.6.1 Precautions z Use shielded or twisted-pair cables to connect control terminals. z Connect the ground terminal (PE) with shield wire.
26
Wiring z The cable connected to the control terminal should leave away from the main circuit and heavy current circuits (including power supply cable, motor cable, relay and contactor connecting cable) at least 20cm and parallel wiring should be avoided.
It is suggested to apply perpendicular wiring to prevent inverter malfunction caused by external interference.
4.6.2 Control circuit terminals
Terminal
No.
S1~S4
+24V
GND
+10V
COM
ROA
AI1
AI2
AO
Y
、 ROB
ROC
、
Function
ON-OFF signal input, optical coupling with PW and COM.
Input voltage range: 9~30V
Input impedance: 3.3k
Ω
Provide output power supply of +24V.
Maximum output current: 150mA
Analog input: 0~10V
Input impedance: 10k Ω
Analog input: 0~10V/ 0~20mA, switched by J16.
Input impedance:10k Ω (voltage input) / 250 Ω (current input )
Common ground terminal of analog signal and +10V.
GND must isolated from COM.
Supply +10V to inverter.
Common ground terminal for digital signal and +24V (or external power supply).
Provide voltage or current output which can be switched by J15.
Output range: 0~10V/ 0~20mA
Open collector output terminal, the corresponding common ground terminal is COM.
Relay output: ROA--common; ROB--NC, ROC—NO.
Contact capacity: AC 250V/3A, DC 30V/1A
4.6.3 Jumpers on control board
Jumper
J2, J4
Function
Default setting: J2 and J4 are disconnected. It is prohibited to be connected together, otherwise it will cause inverter malfunction.
J7
Default setting: 2 and 3 connected. Do not change default setting otherwise it will cause communication malfunction.
27
Wiring
J16
J15
Switch between (0~10V) voltage input and (0~20mA) current input.
V connect to GND means voltage input;
I connect to GND means current input.
Switch between (0~10V) voltage output and (0~20mA) current output.
V connect to OUT means voltage output;
I connect to OUT means current output.
4.6.4 Wiring description of size A (1AC 0.4~0.75kW)
AI2 can work in three modes (0~24V/0~10V/0~20mA) depend on the configuration of
J16.
0~24V input 0~10V input 0~20mA input
Figure 4.17 Wiring of size A (0.4~0.75kW 1AC).
To the external potentiometer, resistance should be greater than 3k Ω and power should greater than 1/4W. Its resistance is recommended to be 5~10k Ω .
Notice:
The terminal will use the internal circuit to adjust the input signal. To the first two work mode, the relative internal voltage range is 0~10V. And to the third work mode, the relative internal voltage range is 0~5V.
4.7 Installation Guidline to EMC Compliance
4.7.1 General description of EMC
EMC is the abbreviation of electromagnetic compatibility, which means the device or system has the ability to work normally in the electromagnetic environment and will not generate any electromagnetic interference to other equipments.
EMC includes two subjects: electromagnetic interference and electromagnetic anti-jamming.
According to the transmission mode, Electromagnetic interference can be divided into two
28
Wiring categories: conducted interference and radiated interference.
Conducted interference is the interference transmitted by conductor. Therefore, any conductors (such as wire, transmission line, inductor, capacitor and so on) are the transmission channels of the interference.
Radiated interference is the interference transmitted in electromagnetic wave, and the energy is inverse proportional to the square of distance.
Three necessary conditions or essentials of electromagnetic interference are: interference source, transmission channel and sensitive receiver. For customers, the solution of EMC problem is mainly in transmission channel because of the device attribute of disturbance source and receiver can not be changed
4.7.2 EMC features of inverter
Like other electric or electronic devices, inverter is not only an electromagnetic interference source but also an electromagnetic receiver. The operating principle of inverter determines that it can produce certain electromagnetic interference noise. And the same time inverter should be designed with certain anti-jamming ability to ensure the smooth working in certain electromagnetic environment. The following is its EMC features:
4.7.2.1 Input current is non-sine wave. The input current includes large amount of high-harmonic waves that can cause electromagnetic interference, decrease the grid power factor and increase the line loss.
4.7.2.2 Output voltage is high frequency PMW wave, which can increase the temperature rise and shorten the life of motor. And the leakage current will also increase, which can lead to the leakage protection device malfunction and generate strong electromagnetic interference to influence the reliability of other electric devices.
4.7.2.3 As the electromagnetic receiver, too strong interference will damage the inverter and influence the normal using of customers.
4.7.2.4 In the system, EMS and EMI of inverter coexist. Decrease the EMI of inverter can increase its EMS ability.
4.7.3 EMC Installation Guideline
In order to ensure all electric devices in the same system to work smoothly, this section,
29
Wiring based on EMC features of inverter, introduces EMC installation process in several aspects of application (noise control, site wiring, grounding, leakage current and power supply filter). The good effective of EMC will depend on the good effective of all of these five aspects.
All the connections to the control terminals must use shielded wire. And the shield layer of the wire must ground near the wire entrance of inverter. The ground mode is 360 degree annular connection formed by cable clips. It is strictly prohibitive to connect the twisted shielding layer to the ground of inverter, which greatly decreases or loses the shielding effect.
Connect inverter and motor with the shielded wire or the separated cable tray. One side of shield layer of shielded wire or metal cover of separated cable tray should connect to ground, and the other side should connect to the motor cover. Installing an EMC filter can reduce the electromagnetic noise greatly.
Power supply wiring: the power should be separated supplied from electrical transformer.
Normally it is 5 core wires, three of which are fire wires, one of which is the neutral wire, and one of which is the ground wire. It is strictly prohibitive to use the same line to be both the neutral wire and the ground wire
Device categorization: there are different electric devices contained in one control cabinet, such as inverter, filter, PLC and instrument etc, which have different ability of emitting and withstanding electromagnetic noise. Therefore, it needs to categorize these devices into strong noise device and noise sensitive device. The same kinds of device should be placed in the same area, and the distance between devices of different category should be more than 20cm.
Wire Arrangement inside the control cabinet: there are signal wire (light current) and power cable (strong current) in one cabinet. For the inverter, the power cables are categorized into input cable and output cable. Signal wires can be easily disturbed by power cables to make the equipment malfunction. Therefore when wiring, signal cables and power cables should be arranged in different area. It is strictly prohibitive to arrange them in parallel or interlacement at a close distance (less than 20cm) or tie them together.
If the signal wires have to cross the power cables, they should be arranged in 90 angles.
Power input and output cables should not either be arranged in interlacement or tied
30
Wiring together, especially when installed the EMC filter. Otherwise the distributed capacitances of its input and output power cable can be coupling each other to make the EMC filter out of function.
4.7.3.3 Ground
Inverter must be ground safely when in operation. Grounding enjoys priority in all EMC methods because it does not only ensure the safety of equipment and persons, but also is the simplest, most effective and lowest cost solution for EMC problems.
Grounding has three categories: special pole grounding, common pole grounding and series-wound grounding. Different control system should use special pole grounding, and different devices in the same control system should use common pole grounding, and different devices connected by same power cable should use series-wound grounding.
Leakage current includes line-to-line leakage current and over-ground leakage current.
Its value depends on distributed capacitances and carrier frequency of inverter. The over-ground leakage current, which is the current passing through the common ground wire, can not only flow into inverter system but also other devices. It also can make leakage current circuit breaker, relay or other devices malfunction. The value of line-to-line leakage current, which means the leakage current passing through distributed capacitors of input output wire, depends on the carrier frequency of inverter, the length and section areas of motor cables. The higher carrier frequency of inverter, the longer of the motor cable and/or the bigger cable section area, the larger leakage current will occur.
Countermeasure:
Decreasing the carrier frequency can effectively decrease the leakage current. In the case of motor cable is relatively long (longer than 50m), it is necessary to install AC reactor or sinusoidal wave filter at the output side, and when it is even longer, it is necessary to install one reactor at every certain distance.
EMC filter has a great effect of electromagnetic decoupling, so it is preferred for customer to install it.
For inverter, noise filter has following categories: z Noise filter installed at the input side of inverter; z Install noise isolation for other equipment by means of isolation transformer or
31
Wiring power filter.
5. OPERATION
5.1 Keypad Description
5.1.1 Keypad schematic diagram
Figure 5.1 Keypad schematic diagram.
5.1.2 Key function description
Button
Symbol
Name
Programming
Key
Function Description
Entry or escape of first-level menu.
Enter Key Progressively enter menu and confirm parameters.
32
Operation
UP Increment
Key
Progressively increase data or function codes.
DOWN
Decrement Key
Progressive decrease data or function codes.
+
Combination
Key
Shift Key
Cyclically displays parameters by left shift, In the stop or running status. Note that when operation, should firstly press and hold the DATA/ENT key and then press the QUICK/JOG key.
In parameter setting mode, press this button to select the bit to be modified. In other modes, cyclically displays parameters by right shift
Run Key
STOP/RESET
Key
Shortcut
Multifunction
Key
Start to run the inverter in keypad control mode.
In running status, restricted by P7.04, can be used to stop the inverter.
When fault alarm, can be used to reset the inverter without any restriction.
Determined by Function Code P7.03:
0: Jog operation
1: Switch between forward and reverse
2: Clear the UP/DOWN settings.
3: Quick debugging mode1 (by menu)
4: Quick debugging mode2 (by latest order)
5: Quick debugging mode3 (by non-factory setting parameters)
+
Combination
Key
5.1.3 Indicator light description
Pressing the RUN and STOP/REST at the same time can achieve inverter coast to stop.
5.1.3.1 Function Indicator Light Description
Indicator Light
Name
Indicator Light Description
RUN/TUNE
FWD/REV
Extinguished: stop status
Flickering: parameter autotuning status
Light on: operating status
Extinguished: forward operation
33
Operation
LOCAL/REMOT
TRIP
Light on: reverse operation.
Extinguished: keypad control
Flickering: terminal control
Light on: communication control
Extinguished: normal operation status
Flickering: overload pre-warning status
5.1.3.2 Unit Indicator Light Description
Symbol Description
RPM Rotation speed unit
% Percentage
Have 5 digit LED , which can display all kinds of monitoring data and alarm codes such as reference frequency, output frequency and so on.
5.2 Operation Process
5.2.1 Parameter setting
Three levels of menu are: z Function code group (first-level); z Function code (second-level); z Function code value (third-level).
Remarks:
Press both the PRG/ESC and the DATA/ENT can return to the second-class menu from the third-class menu. The difference is: pressing DATA/ENT will save the set parameters into the control panel, and then return to the second-class menu with shifting to the next function code automatically; while pressing PRG/ESC will directly return to the second-class menu without saving the parameters, and keep staying at the current function code
34
Operation
Figure 5.2 Flow chart of parameter setting.
Under the third-class menu, if the parameter has no flickering bit, it means the function code cannot be modified. The possible reasons could be: z This function code is not modifiable parameter, such as actual detected parameter, operation records and so on; z This function code is not modifiable in running status, but modifiable in stop status
5.2.2 Fault reset
If the inverter has fault, it will prompt the related fault information. User can use
STOP/RST or according terminals determined by P5 Group to reset the fault. After fault reset, the inverter is at stand-by state. If user does not reset the inverter when it is at fault state, the inverter will be at operation protection state, and can not run.
5.2.3 Motor parameter autotuning
If “Sensorless Vector Control” mode is chosen, motor nameplate parameters must be input correctly as the autotuning is based on it. The performance of vector control depends on the parameters of motor strongly, so to achieve excellent performance, firstly must obtain the parameter of motor exactly.
The procedure of motor parameter autotuning is as follows:
Firstly, choose the keypad command channel as the operation command channel
(P0.01).
And then input following parameters according to the actual motor parameters:
P2.00: motor rated power.
P2.01: motor rated frequency;
P2.02: motor rated speed;
P2.03: motor rated voltage;
P2.04: motor rated current
Notice: the motor should be uncoupled with its load; otherwise, the motor parameters obtained by autotuning may be not correct.
Set P0.12 to be 1, and for the detail process of motor parameter autotuning, please refer to the description of Function Code P0.12. And then press RUN on the keypad panel, the inverter will automatically calculate following parameter of the motor:
35
Operation
P2.05: motor stator resistance;
P2.06: motor rotor resistance;
P2.07: motor stator and rotor inductance;
P2.08: motor stator and rotor mutual inductance;
P2.09: motor current without load; then motor autotuning is finished.
5.2.4 Password setting
CHE series inverter offers user’s password protection function. When P7.00 is set to be nonzero, it will be the user’s password, and After exiting function code edit mode, it will become effective after 1 minute. If pressing the PRG/ESC again to try to access the function code edit mode, “0.0.0.0.0”will be displayed, and the operator must input correct user’s password, otherwise will be unable to access it.
If it is necessary to cancel the password protection function, just set P7.00 to be zero.
5.3 Running State
5.3.1 Power-on initialization
Firstly the system initializes during the inverter power-on, and LED displays “-CHE-”. After the initialization is completed, the inverter is on stand-by status.
5.3.2 Stand-by
At stop or running status, parameters of multi-status can be displayed. Whether or not to display this parameter can be chosen through Function Code P7.06(Running status display selection ) and P7.07 (Stop status display selection) according to binary bits, the detailed description of each bit please refer the function code description of P7.06 and
P7.07.
In stop status, there are nine parameters which can be chosen to display or not. They are: reference frequency, DC bus voltage, ON-OFF input status, open collector output status,
PID setting, PID feedback, analog input AI1 voltage, analog input AI2 voltage, step number of multi-step speed. Whether or not to display can be decided by setting the corresponding binary bit of P7.07. Press the 》 /SHIFT to scroll through the parameters in right order . Press DATA/ENT + QUICK/JOG to scroll through the parameters in left order.
5.3.3 Motor parameter autotuning
For details, please refer to the description of P0.12.
5.3.4 Operation
In running status, there are fourteen running parameters: output frequency, reference frequency, DC bus voltage, output voltage, output current, output power, output torque,
PID setting, PID feedback, ON-OFF input status, open collector output status, length value, count value, step number of PLC and multi-step speed, voltage of AI1, voltage of
AI2 and step number of multi-step speed. Whether or not to display can be decided by the
36
Operation bit option of Function Code P7.06 (converted into binary system). Press the 》 /SHIFT to scroll through the parameters in right order . Press DATA/ENT + QUICK/JOG to scroll through the parameters in left order.
5.3.5 Fault
CHE series inverter offers a variety of fault information. For details, see inverter faults and their troubleshooting.
5.4 Quick Testing
37
Operation
Figure 5.3 Quick testing.diagram
6. DETAILED FUNCTION DESCRIPTION
6.1 P0 Group--Basic Function
Function
Code
Name
P0.00
Control mode selection
Description
0:Sensorless vector control
1:V/F control
2:Torque control
Setting
Range
Factory
Setting
0~2 0
0: Sensorless vector control: It is widely used for the application which requires high torque at low speed, higher speed accuracy, and quicker dynamic response, such as machine tool, injection molding machine, centrifugal machine and wire-drawing machine, etc.
1: V/F control: It is suitable for general purpose application such as pumps, fans etc.
2: Torque control: It is suitable for the application with low accuracy torque control, such as wired-drawing. In torque control mode, the speed of motor is determined by load, the rate of ACC/DEC has nothing to do with the value of P0.08 and P0.09 (or P8.00 and
P8.01).
Notice: z Inverter can drive only one motor when P0.00 is set to be 0 or 2. When P0.00 is set to be 1, inverter can drive multi motors. z The autotuning of motor parameters must be accomplished properly when
P0.00 is set to be 0 or 2. z In order to achieve better control characteristic, the parameters of speed regulator (P3.00~P3.05) must be adjusted according to actual situation when
P0.00 is set to be 0 or 2.
Function
Code
Name Description
Setting
Range
Factory
Setting
P0.01
Run command source
0: Keypad (LED extinguished)
1: Terminal (LED flickering)
2: Communication (LED lights on)
0~2 0
The control commands of inverter include: start, stop, forward run, reverse run, jog, fault
38
Detailed Function Description reset and so on.
0: Keypad (LED extinguished);
Both RUN and STOP/RST key are used for running command control. If Multifunction key QUICK/JOG is set as FWD/REV switching function (P7.03 is set to be 1), it will be used to change the rotating orientation. In running status, pressing RUN and
STOP/RST in the same time will cause the inverter coast to stop.
1: Terminal (LED flickering)
The operation, including forward run, reverse run, forward jog, reverse jog etc. can be controlled by multifunctional input terminals.
2: Communication (LED lights on)
The operation of inverter can be controlled by the host through communication.
Function
Code
P0.02
Name
UP/DOWN setting
Description
0: Valid, save UP/DOWN value when power off
1: Valid, do not save
UP/DOWN value when power off
2: Invalid
3: Valid during running, clear when stop.
Setting
Range
Factory
Setting
0~3 0
0: User can adjust the reference frequency by UP/DOWN. The value of UP/DOWN can be saved when power off.
1: User can adjust the reference frequency by UP/DOWN, but the value of UP/DOWN will not be saved when power off.
2: User can not adjust the reference frequency by UP/DOWN. The value of UP/DOWN will be cleared if P3.05 is set to 2.
3: User can only adjust the reference frequency by UP/DOWN during the inverter is running. The value of UP/DOWN will be cleared when the inverter stops.
Notice: z UP/DOWN function can be achieved by keypad ( ∧ and ∨ ) and multifunctional terminals. z Reference frequency can be adjusted by UP/DOWN. z UP/DOWN has highest priority which means UP/DOWN is always active no matter which frequency command source is. z When the factory setting is restored (P1.03 is set to be 1), the value of
UP/DOWN will be cleared
Function
Code
Name Description
39
Setting
Range
Factory
Setting
Detailed Function Description
P0.03
Frequency A command source
0: Keypad
1: AI1
2. AI2
3: AI1+AI2
4. Multi-Step speed
5: PID
6: Communication
0: Keypad: Please refer to description of P3.00
1: AI1
2: AI2
0~6 0
3:AI1+AI2
The reference frequency is set by analog input. CHE series inverter provides 2 analog input terminals. AI1 is 0~10V voltage input terminal, while AI2 is 0~10V voltage input or
0~20mA current input. Voltage input or current input of AI2 can be selected by Jumper
J16.
Notice: z When AI2 is set as 0~20mA current input, the corresponding voltage range is
0~5V. For detailed relationship between analogue input voltage and frequency, please refer to description of P5.07~P5.11. z 100% of AI is corresponding to maximum frequency(P0.04)
4: Multi-step speed
The reference frequency is determined by PA group. The selection of steps is determined by combination of multi-step speed terminals.
Notice: z Multi-step speed mode will enjoy priority in setting reference frequency if
P0.03 is not set to be 4. In this case, only step 1 to step 15 are available. z If P0.03 is set to be 4, step 0 to step 15 can be realized.
Jog has highest priority.
5: PID
The reference frequency is the result of PID adjustment. For details, please refer to description of P9 group
6: Communication
The reference frequency is set through RS485. For details, please refer to description of
Chapter 10.
Function
Code
Name Description Setting Range
P0.04
Maximum frequency
P0.05~400.00Hz P0.05~400.00
Notice: z The frequency reference should not exceed maximum frequency.
Factory
Setting
50.00Hz
40
Detailed Function Description z Actual acceleration time and deceleration time are determined by maximum frequency. Please refer to description of P0.08 and P0.09.
Function
Code
Name Description Setting Range
Factory
Setting
P0.05
Upper frequency limit
P0.06~ P0.04 P0.06~P0.04
50.00Hz
Notice: z Upper frequency limit should not be greater than the maximum frequency
(P0.04). z Output frequency should not exceed upper frequency limit.
Function
Code
Name Description Setting Range
Factory
Setting
P0.06
Lower frequency limit
0.00 Hz ~ P0.05 0.00~P0.05 0.00Hz
Notice: z Lower frequency limit should not be greater than upper frequency limit
(P0.05). z If frequency reference is lower than P0.06, the action of inverter is determined by P1.12. Please refer to description of P1.12.
Function
Code
Name Description
Setting
Range
Factory
Setting
P0.07
Keypad reference frequency
0.00 Hz ~
P0.04
0.00~P0.04 50.00Hz
When P0.03 is set to be 0, this parameter is the initial value of inverter reference frequency
Function
Code
P0.08
P0.09
Name
Acceleration time 0
Deceleration time 0
Description
0.0~3600.0s
0.0~3600.0s
Setting Range
0.0~3600.0
0.0~3600.0
Factory
Setting
Depend on model
Depend on model
Acceleration time is the time of accelerating from 0Hz to maximum frequency (P0.04).
Deceleration time is the time of decelerating from maximum frequency (P0.04) to 0Hz.
Please refer to following figure.
41
Detailed Function Description
Figure 6.1 Acceleration and deceleration time.
When the reference frequency is equal to the maximum frequency, the actual acceleration and deceleration time will be equal to the P0.08 and P0.09 respectively.
When the reference frequency is less than the maximum frequency, the actual acceleration and deceleration time will be less than the P0.08 and P0.09 respectively.
The actual acceleration (deceleration) time = P0.08 (P0.09) * reference frequency/P0.04.
CHE series inverter has 2 groups of acceleration and deceleration time.
1st group: P0.07, P0.08
2nd group: P8.00, P8.01
The acceleration and deceleration time can be selected by combination of multifunctional
ON-OFF input terminals determined by P5 Group. The factory setting of acceleration and deceleration time is as follow: z 5.5kW and below: 10.0s z 7.5kW~30kW: 20.0s z 37kW and above: 40.0s
Function
Code
Name
P0.10
Running direction selection
Description
0: Forward
1: Reverse
2: Forbid reverse
Setting
Range
Factory
Setting
0~2 0
Notice: z The rotation direction of motor is corresponding to the wiring of motor. z When the factory setting is restored (P0.13 is set to be 1), the rotation direction of motor may be changed. Please be cautious to use. z If P0.10 is set to 2, user can not change rotation direction of motor by
QUICK/JOG or terminal.
Function
Code
Name Description
Setting
Range
Factory
Setting
Depend on model
42
Detailed Function Description
Figure 6.2 Effect of carrier frequency.
The following table is the relationship between power rating and carrier frequency.
Carrier f
Model
G Model: 0.4kW~11kW
P Model: 0.75kW~15kW
G Model: 15kW~55kW
P Model: 18.5kW~75kW
G Model: 75kW~300kW
P Model: 90kW~315kW
Highest Carrier f
( kHz )
Lowest Carrier f
( kHz )
Factory setting
( kHz )
15 1 8
8 1 4
6 1 2
Carrier frequency will affect the noise of motor and the EMI of inverter.
If the carrier frequency is increased, it will cause better current wave, less harmonic current and lower noise of motor.
Notice: z The factory setting is optimal in most cases. Modification of this parameter is not recommended. z If the carrier frequency exceeds the factory setting, the inverter must be derated because the higher carrier frequency will cause more switching loss, higher temperature rise of inverter and stronger electromagnetic interference.
If the carrier frequency is lower than the factory setting, it is possible to cause less output torque of motor and more harmonic current.
Function
Code
Name Description
Setting
Range
Factory
Setting
P0.12
Motor parameters autotuning
0: No action
1: Rotation autotuning
2: Static autotuning
0~2 0
0: No action: Forbidding autotuning.
1: Rotation autotuning: z Do not connect any load to the motor when performing autotuning and ensure the motor is in static status.
43
Detailed Function Description z Input the nameplate parameters of motor (P2.01~P2.05) correctly before performing autotuning. Otherwise the parameters detected by autotuning will be incorrect; it may influence the performance of inverter. z Set the proper acceleration and deceleration time (P0.08 and P0.09) according to the motor inertia before performing autotuning. Otherwise it may cause over-current and over-voltage fault during autotuning. z The operation process is as follow: a. Set P0.12 to be 1 then press the DATA/ENT, LED will display “-TUN-” and flickers. During “-TUN-” is flickering, press the PRG/ESC to exit autotuning. b. Press the RUN to start the autotuning. LED will display “TUN-0”. c. After a few seconds the motor will start to run. LED will display “TUN-1” and
“RUN/TUNE” light will flicker. d. After a few minutes, LED will display “-END-”. That means the autotuning is finished and return to the stop status. e. During the autotuning, press the STOP/RST will stop the autotuning.
Notice: Only keypad can control the autotuning. P0.12 will restore to 0 automatically when the autotuning is finished or cancelled.
2: Static autotuning: z If it is difficult to disconnect the load, static autotuning is recommended. z The operation process is the same as rotation autotuning except step c.
Notice: The Mutual inductance and current without load will not be detected by static autotuning, if needed user should input suitable value according to experience.
Function
Code
Name Description
Setting
Range
Factory
Setting
P0.13
Restore parameters
0: No action
1: Restore factory setting
2: Clear fault records
0~2 0
0: No action
1: Inverter restores all parameters to factory setting except P2 group.
2: Inverter clear all fault records.
This function code will restore to 0 automatically when complete the function operation.
Function
Code
Name Description
Setting
Range
Factory
Setting
0~2 1
44
Detailed Function Description
2: Disabled during deceleration
AVR ( Auto Voltage Regulation) function ensure the output voltage of inverter stable no matter how the DC bus voltage changes. During deceleration, if AVR function is disabled, the deceleration time will be short but the current will be big. If AVR function is enabled all the time, the deceleration time will be long but the current will be small.
6.2 P1 Group--Start and Stop Control
Function
Code
Name Description
P1.00
Start
Mode
0: Start directly
1: DC braking and start
Setting
Range
Factory
Setting
0~1 0
0: Start directly: Start the motor at the starting frequency determined by P1.01.
1: DC braking and start: Inverter will output DC current firstly and then start the motor at the starting frequency. Please refer to description of P1.03 and P1.04. It is suitable for the motor which have small inertia load and may reverse rotation when start.
Function
Code
Name Description
Setting
Range
Factory
Setting
P1.02
Hold time of starting frequency
0.0~50.0s 0.0~50.0 0.0s z Set proper starting frequency can increase the starting torque. z If the reference frequency is less than starting frequency, inverter will be at stand-by status. The indicator of RUN/TUNE lights on, inverter has no output. z The starting frequency could be less than the lower frequency limit (P0.06). z P1.01 and P1.02 take no effect during FWD/REV switching.
Function
Code
P1.03
Name
Figure 6.3 Starting diagram.
DC Braking
current before start
Description
Setting
Range
Factory
Setting
0.0~150.0% 0.0~150.0 0.0%
45
Detailed Function Description
P1.04
DC Braking time before start
0.0~50.0s 0.0~50.0 0.0s
When inverter starts, it performs DC braking according to P1.03 firstly, then start to accelerate after P1.04.
Notice:
DC braking will take effect only when P1.00 is set to be 1.
DC braking is invalid when P1.04 is set to be 0.
The value of P1.03 is the percentage of rated current of inverter. The bigger the DC braking current, the greater the braking torque.
Function
Code
Name Description
Setting
Range
Factory
Setting
0~1 0
0: Deceleration to stop
When the stop command takes effect, the inverter decreases the output frequency according to the selected acceleration/deceleration time till stop.
1: Coast to stop
When the stop command takes effect, the inverter blocks the output immediately. The motor coasts to stop by its mechanical inertia.
Function
Code
Name Description
Setting
Range
Factory
Setting
P1.06
P1.07
P1.08
Starting frequency of DC braking
Waiting time before DC braking
DC braking current
0.00~P0.04 0.00~50.00
0.0~50.0s 0.0~50.0 0.0s
0.0~150.0% 0.0~150.0
0.00Hz
0.0%
P1.09 DC braking time 0.0~50.0s 0.0~50.0 0.0s
Starting frequency of DC braking: Start the DC braking when output frequency reaches starting frequency determined by P1.06.
Waiting time before DC braking: Inverter blocks the output before starting the DC braking.
After this waiting time, the DC braking will be started. It is used to prevent over-current fault caused by DC braking at high speed.
DC braking current: The value of P1.08 is the percentage of rated current of inverter. The bigger the DC braking current, the greater the braking torque.
DC braking time: The time used to perform DC braking. If the time is 0, the DC braking will be invalid.
46
Detailed Function Description
Figure 6.4 DC braking diagram.
Function
Code
Name Description Setting Range
Factory
Setting
P1.10
Dead time of
FWD/REV
0.0~3600.0s 0.0~3600.0 0.0s
Set the hold time at zero frequency in the transition between forward and reverse running.
It is shown as following figure:
Figure 6.5 FWD/REV dead time diagram.
Function
Code
Name Description
Setting
Range
Factory
Setting
P1.11
FWD/REV enable option when power on
0: Disabled
1: Enabled
0~1 0
Notice:
This function only takes effect if run command source is terminal control.
If P1.11 is set to be 0, when power on, inverter will not start even if FWD/REV terminal is active, until FWD/REV terminal disabled and enabled again.
If P1.11 is set to be 1, when power on and FWD/REV terminal is active, inverter will start automatically.
This function may cause the inverter restart automatically, please be cautious.
6.3 P2 Group--Motor Parameters
Function
Code
Name Description
47
Setting
Range
Factory
Setting
Detailed Function Description
0: G model
1: P model
0~1 0
0: Applicable to constant torque load
1: Applicable to variable torque load (i.e. fans, pumps)
CHE series inverters provide the G/P integration function. The adaptive motor power used for constant torque load (G model) should be one grade less than that used for variable torque load (P model).
To change from G model to P model, procedures are as follow:
Set P2.00 to be 1;
Input motor parameters in P2 group again..
Function
Code
Name Description Setting Range
Factory
Setting
P2.01
P2.02
P2.03
P2.04
P2.05
Motor rated power
Motor rated frequency
Motor rated speed
Motor rated voltage
Motor rated current model
0.01Hz~P0.04 0.01~P0.04 50.00Hz model model
Notice:
In order to achieve superior performance, please set these parameters according to motor nameplate, then perform autotuning.
The power rating of inverter should match the motor. If the bias is too big, the control performances of inverter will be deteriorated distinctly.
Reset P2.01 can initialize P2.02~P2.10 automatically.
Function
Code
Name Description Setting Range
Factory
Setting
P2.06
P2.07
P2.08
P2.09
P2.10
Motor stator resistance
Motor rotor resistance
Motor leakage inductance
Motor mutual inductance
Current without load
0.001~65.535
Ω 0.001~65.535 model
0.001~65.535
Ω 0.001~65.535 model model model
0.01~655.35A 0.01~655.35 model
After autotuning, the value of P2.06~P2.10 will be automatically updated.
48
Detailed Function Description
Notice: Do not change these parameters, otherwise it may deteriorate the control performance of inverter.
6.4 P3 Group—Vector Control
Function
Code
Name
P3.00
P3.01
ASR proportional gain K p
1
ASR integral time
K i
1
P3.02
P3.03
P3.04
P3.05
ASR switching point 1
ASR proportional gain K p
2
ASR integral time
K i
2
ASR switching point 2
Description Setting Range
Factory
Setting
0.01~10.00s 0.01~10.00 0.50s
0.00Hz~P3.05 0.00~P3.05 5.00Hz
0.01~10.00s 0.01~10.00 1.00s
P3.00
~ P3.05 are only valid for vector control and torque control and invalid for V/F control. Through P3.00
~ P3.05, user can set the proportional gain K p
and integral time K i of speed regulator (ASR), so as to change the speed response characteristic. ASR's structure is shown in following figure.
Figure 6.6 ASR diagram.
P3.00 and P3.01 only take effect when output frequency is less than P3.02. P3.03 and
P3.04 only take effect when output frequency is greater than P3.05. When output frequency is between P3.02 and P3.05, K p
and K
I
are proportional to the bias between
P3.02 and P3.05. For details, please refer to following figure.
49
Detailed Function Description
Figure 6.7 PI parameter diagram.
The system's dynamic response can be faster if the proportion gain K p
is increased;
However, if K p
is too large, the system tends to oscillate.
The system dynamic response can be faster if the integral time K i
is decreased;
However, if K i
is too small, the system becomes overshoot and tends to oscillate.
P3.00 and P3.01 are corresponding to K p
and K i
at low frequency, while P3.03 and P3.04 are corresponding to K p
and K i
at high frequency. Please adjust these parameters according to actual situation. The adjustment procedure is as follow:
Increase the proportional gain (K p
) as far as possible without creating oscillation.
Reduce the integral time (K i
) as far as possible without creating oscillation.
For more details about fine adjustment, please refer to description of P9 group.
Function
Code
Name Description
Setting
Range
Factory
Setting
P3.06
Slip compensation rate of VC
Name
50.0~200.0% 50.0~200.0
Description Setting Range
100%
The parameter is used to adjust the slip frequency of vector control and improve the precision of speed control. Properly adjusting this parameter can effectively restrain the static speed bias.
Function
Code
Factory
Setting
This parameter is used to limit the torque current output by speed regulator. Torque limit value 0.0-200% is the inverter's rated current percentage.
6.5 P4 Group-- V/F Control
Function
Code
Name
V/F curve selection
Description
Setting
Range
Factory
Setting
P4.00
0:Linear curve
1: Torque_stepdown curve
(2.0 order)
0~1 0
0: Linear curve. It is applicable for normal constant torque load.
1: Torque_stepdown curve. It is applicable for variable torque load, such as blower, pump and so on. Please refer to following figure.
50
Detailed Function Description
Figure6.8 V/F curve diagram.
Function
Code
Name Description
Setting
Range
Factory
Setting
P4.02
Torque boost cut-off
0.0%: (auto)
0.1
% ~10.0
%
0.0%~50.0% (motor rated frequency)
0.0~10.0 0.0
%
0.0~50.0 20.0%
Torque boost will take effect when output frequency is less than cut-off frequency of torque boost (P4.02). Torque boost can improve the torque performance of V/F control at low speed.
The value of torque boost should be determined by the load. The heavier the load, the larger the value.
Notice: P4.01 should not be too large, otherwise the motor would be over-heat or the inverter would be tripped by over-current or over-load.
If P4.01 is set to be 0, the inverter will boost the output torque according to the load automatically.
Please refer to following diagram.
Figure 6.9 Manual torque boost diagram.
Function
Code
Name Description
Setting
Range
Factory
Setting
P4.03
V/F Slip compensation limit
0.00~200.0% 0.00~200.00
0.0%
The slip compensation function calculates the torque of motor according to the output current and compensates for output frequency. This function is used to improve speed accuracy when operating with a load. P4.03 sets the slip compensation limit as a percentage of motor rated slip, with the motor rated slip taken as 100%.
Function Name Description Setting Factory
51
Detailed Function Description
Code Range Setting
P4.04
When P4.04 is set to be 1, while there is a light load, it will reduce the inverter output voltage and saves energy.
6.6 P5 Group--Input Terminals
Function
Code
Name Description
Setting
Range
Factory
Setting
P5.00
P5.01
P5.02
S1 Terminal function
S2 Terminal function
S3 Terminal function
Programmable multifunctional terminal
Programmable multifunctional terminal
Programmable multifunctional terminal
0~25 1
0~25 4
0~25 7
P5.03
Auto energy saving selection
S4 Terminal function
0: Disabled
1: Enabled
Programmable multifunctional terminal
0~1 0
0~25 0
The meaning of each setting is shown in following table.
Setting value
Function Description
2 Reverse
3 3-wire control Please refer to description of P5.05.
6 forward
Please refer to description of P8.02~P8.04. reverse
Coast to stop
The inverter blocks the output immediately. The motor coasts to stop by its mechanical inertia.
8
9
External fault input
Up command
Stop the inverter and output a alarm when a fault occurs in a peripheral device.
The reference frequency of inverter can be adjusted by UP command and DOWN command.
52
10
11
12
13
14
15
17
18
19
Detailed Function Description
DOWN command
Clear
UP/DOWN
Use this terminal to clear UP/DOWN setting. Please refer to description of P0.02.
Multi-step speed reference1
Multi-step speed reference
2
Multi-step speed reference 3
8 steps speed control can be realized by the combination of these four terminals. For details, please refer to: Multi-step speed reference terminal status and according step value table:
2 groups of ACC/DEC time can be selected by the combination of these two terminals.
ACC/DEC time selection
Terminal ACC/DEC time
Corresponding
Parameter
OFF
ON
Acceleration Time
0
Acceleration Time
1
P0.08
P8.00
、
、
P0.09
P8.01
PID adjustment will be paused and inverter keeps output
PID frequency unchanged.
Pause traverse operation
Inverter keeps output frequency unchanged. If this terminal is disabled, inverter will continue traverse operation from current frequency.
Reset traverse operation
Reference frequency of inverter will be forced as center frequency of traverse operation.
ACC/DEC ramp hold
Pauses acceleration or deceleration and maintains output frequency. When this terminal is disabled, acceleration/deceleration is restarted.
53
Detailed Function Description
20
21
Disable torque control
UP/DOWN invalid temporarily
Torque control is disabled. Inverter will work in speed control mode.
UP/DOWN setting is invalid and will not be cleared. When this terminal is disabled, UP/DOWN setting before will be valid again.
Multi-step speed reference terminal status and according step value table:
Terminal
Step
Multi-step speed reference1
Multi-step speed reference2
Multi-step speed reference3
0 OFF OFF OFF
2 OFF ON OFF
6 OFF ON ON
7 ON ON ON
Function
Code
P5.04
Name
ON/OFF filter times
Description
1~10
Setting
Range
1~10
Factory
Setting
5
This parameter is used to set filter strength of terminals (S1~S4). When interference is heavy, user should increase this value to prevent malfunction.
Function
Code
Name Description
Setting
Range
Factory
Setting
P5.05
FWD/REV control mode
0: 2-wire control mode 1
1: 2-wire control mode 2
2: 3-wire control mode 1
3: 3-wire control mode 2
0~3 0
This parameter defines four different control modes that control the inverter operation through external terminals.
0: 2-wire control mode 1: Integrate START/STOP command with run direction.
K1 K2 Run
54
Detailed Function Description
OFF OFF Stop
ON OFF FWD
OFF ON REV
ON ON Stop
Figure 6.10 2-wire control mode1.
1: 2-wire control mode 2: START/STOP command is determined by FWD terminal. Run direction is determined by REV terminal.
K1 K2 Run
OFF OFF Stop
ON OFF FWD
OFF ON Stop
ON ON REV
Figure 6.11 2-wire control mode 2.
2: 3-wire control mode 1:
SB1: Start button
SB2: Stop button (NC)
K: Run direction button
Terminal SIn is the multifunctional input terminal of S1~S4. The terminal function should be set to be 3 (3-wire control).
OFF Stop
ON FWD
Figure 6.12 3-wire control mode 1.
3: 3-wire control mode 2:
SB1: Forward run button
SB2: Stop button (NC)
SB3: Reverse run button
Terminal SIn is the multifunctional input terminal of S1~S4. The terminal function should be set to be 3 (3-wire control)
55
Detailed Function Description
Figure 6.13 3-wire control mode2.
Notice: When 2-wire control mode is active, the inverter will not run in following situation even if FWD/REV terminal is enabled: z Coast to stop (press RUN and STOP/RST at the same time). z Stop command from serial communication.
FWD/REV terminal is enabled before power on. Please refer to description of P1.11.
Function
Code
Name Description
Setting
Range
Factory
Setting
P5.06
UP/DOWN setting change rate
0.01~50.00Hz/s 0.01~50.00 0.50Hz/s
Terminal UP/DOWN regulates the incremental rate of setting frequency.
Function
Code
Name Description Setting Range
Factory
Setting
P5.07 0.00V~10.00V 0.00~10.00 0.00V
P5.08
AI1 lower limit
AI1 lower limit corresponding setting
-100.0%~100.0% -100.0~100.0
0.0%
P5.09
P5.10
P5.11
AI1 upper limit
AI1 upper limit corresponding setting
AI1 filter time constant
0.00V~10.00V 0.00~10.00
-100.0%~100.0% -100.0~100.0
10.00V
100.0%
0.00s~10.00s 0.00~10.00 0.10s
These parameters determine the relationship between analog input voltage and the corresponding setting value. When the analog input voltage exceeds the range between lower limit and upper limit, it will be regarded as the upper limit or lower limit.
The analog input AI1 can only provide voltage input, and the range is 0V~10V.
For different applications, the corresponding value of 100.0% analog setting is different.
For details, please refer to description of each application.
Notice: AI1 lower limit must be less or equal to AI1 upper limit.
56
Detailed Function Description
Figure 6.14 Relationship between AI and corresponding setting.
AI1 filter time constant is effective when there are sudden changes or noise in the analog input signal. Responsiveness decreases as the setting increases.
Function
Code
P5.12
Name Description
0.00V~10.00V
Setting Range
0.00~10.00
Factory
Setting
0.00V
P5.13
P5.14
P5.15
P5.16
AI2 lower limit
AI2 lower limit corresponding setting
AI2 upper limit
AI2 upper limit corresponding setting
AI2 filter time constant
-100.0%~100.0% -100.0~100.0 0.0%
0.00V~10.00V 0.00~10.00 10.00V
-100.0%~100.0% -100.0~100.0 100.0%
Please refer to description of AI1. When AI2 is set as 0~20mA current input, the corresponding voltage range is 0~5V.
6.7 P6 Group--Output Terminals
Function Code Name Description
P6.00
P6.01
Y output selection
Relay output selection
Open-collector output
Relay output
OC/Relay output functions are indicated in the following table.
Setting
Value
Function Description
Setting
Range
0~10
0~10
0 No output Output terminal has no function
Factory
Setting
1
3
1
2
Run forward
Run reverse
ON: During forward run.
ON: During reverse run.
57
Detailed Function Description
6
7
3
4
5
8
Fault output
FDT reached
Frequency reached
Zero speed running
Upper frequency limit reached
Lower frequency limit reached
ON: Inverter is in fault status.
Please refer to description of P8.13 and P8.14.
Please refer to description of P8.15.
ON: The running frequency of inverter is zero.
ON: Running frequency reaches the value of P0.05.
ON: Running frequency reaches the value of P0.06.
Function
Code
Name Description
Setting
Range
Factory
Setting output
0~10 0
Current (0~20mA) or voltage (0~10V) output can be selected by Jumper J15.
AO functions are indicated in the following table:
Setting
Value
0
1
2
3
4
5
6
Function
Running frequency
Reference frequency
Motor speed
Output current
Output voltage
Output power
Output torque
9~10 Reserved
Function
Code
P6.03
Name Description
0.0%~100.0%
P6.04
AO lower limit
AO lower limit corresponding output
0.00V ~10.00V
Range
0~maximum frequency (P0.04)
0~ maximum frequency (P0.04)
0~2* rated synchronous speed of motor
0~2* inverter rated current
0~1.5* inverter rated voltage
0~2* rated power
0~2*rated current
0~10V
0~10V/0~20mA
Reserved
Setting
Range
0.0~100.0
0.00~10.00
Factory
Setting
0.0%
0.00V
58
Detailed Function Description
P6.05
P6.06
AO upper limit
AO upper limit corresponding output
0.0%~100.0%
0.00V ~10.00V
0.0~100.0
0.00~10.00
100.0%
10.00V
These parameters determine the relationship between analog output voltage/current and the corresponding output value. When the analog output value exceeds the range between lower limit and upper limit, it will output the upper limit or lower limit.
When AO is current output, 1mA is corresponding to 0.5V.
For different applications, the corresponding value of 100.0% analog output is different.
For details, please refer to description of each application.
Figure 6.15 Relationship between AO and corresponding setting.
6.8 P7 Group--Display Interface
Function
Code
Name
P7.00 User password
Description
0~65535
Setting Range
0~65535
Factory
Setting
0
The password protection function will be valid when set to be any nonzero data. When
P7.00 is set to be 00000, user’s password set before will be cleared and the password protection function will be disabled.
After the password has been set and becomes valid, the user can not access menu if the user’s password is not correct. Only when a correct user’s password is input, the user can see and modify the parameters. Please keep user’s password in mind.
Function
Code
Name Description
Setting
Range
Factory
Setting
P7.01 LCD language selection
P7.02 Parameter copy
0: Chinese
1: English
0: Invalid
1: Upload from inverter
2: Download to inverter
59
0~1 0
0~2 0
Detailed Function Description
P7.02 will take effect when LCD keypad is used.
1: All value of parameters will be uploaded from inverter to LCD.
2: All value of parameters will be downloaded from LCD to inverter.
Notice: When upload or download operation completes, P7.02 will be set to 0 automatically.
Function
Code
P7.03
Name
QUICK/JOG function selection
Description
0: Jog
1: FDW/REV switching
2: Clear UP/DOWN setting
Setting
Range
Factory
Setting
0~2 0
QUICK/JOG is a multifunctional key, whose function can be defined by the value of
P7.03.
0: Jog: Press QUICK/JOG , the inverter will jog.
1: FWD/REV switching: Press QUICK/JOG, the running direction of inverter will reverse.
It is only valid if P0.03 is set to be 0.
2: Clear UP/DOWN setting: Press QUICK/JOG, the UP/DOWN setting will be cleared.
Function
Code
Name Description
Setting
Range
Factory
Setting
P7.04
STOP/RST function option
0: Valid when keypad control
(P0.01=0)
1: Valid when keypad or terminal control (P0.01=0 or
1)
2: Valid when keypad or communication control
(P0.01=0 or 2)
3: Always valid
0~3 0
Notice:
The value of P7.04 only determines the STOP function of STOP/RST.
The RESET function of STOP/RST is always valid.
Function
Code
Name Description
Setting
Range
Factory
Setting
P7.05
Keypad display selection
0: Preferential to external keypad
1: Both display, only external key valid.
2: Both display, only local key valid.
3: Both display and key valid.
0~3 0
0: When external keypad exists, local keypad will be invalid.
60
Detailed Function Description
1: Local and external keypad display simultaneously, only the key of external keypad is valid.
2: Local and external keypad display simultaneously, only the key of local keypad is valid.
3: Local and external keypad display simultaneously, both keys of local and external keypad are valid. Notice: This function should be used cautiously, otherwise it may cause malfunction.
Notice:
When P7.05 is set to be 1, local keypad is valid if external keypad is not connected.
When LCD keypad is connected, P7.05 must be set to be 0.
Function
Code
Name Description Setting Range
P7.06
Running status display selection
Factory
Setting
0~0x7FFF 0~0x7FFF 0xFF
P7.06 defines the parameters that can be displayed by LED in running status. If Bit is 0, the parameter will not be displayed; If Bit is 1, the parameter will be displayed. Press 》
/SHIFT to scroll through these parameters in right order . Press DATA/ENT +
QUICK/JOG to scroll through these parameters in left order.
The display content corresponding to each bit of P7.06 is described in the following table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
Output torque
Output power
Rotation speed
Output current
Output voltage
DC bus voltage
Reference frequency
Output frequency
BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8
Reserved
Step No. of multi-step
Output
AI2 AI1 status
Input terminal status
PID feedback
PID preset
For example, if user wants to display output voltage, DC bus voltage, Reference frequency, Output frequency, Output terminal status, the value of each bit is as the following table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 0 0 0 1 1 1 1
BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8
61
Detailed Function Description
0 0 1 0 0 0 0
The value of P7.06 is 100Fh.
Notice: I/O terminal status is displayed in decimal.
For details, please refer to description of P7.18 and P7.19.
Function
Code
Name Description
Setting
Range
Factory
Setting
P7.07
Stop status display selection
0~0x1FF 0~0x1FF 0xFF
P7.07 determines the display parameters in stop status. The setting method is similar with P7.06.
The display content corresponding to each bit of P7.07 is described in the following table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
AI2 AI1
PID feedback
PID preset
Output terminal status
Input terminal status
DC bus voltage
Reference frequency
BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8
Reserved Reserved Reserved Reserved Reserved Reserved Reserved
Step No. of multi-step
Function
Code
Name Description
Setting
Range
Factory
Setting
P7.08
P7.09
Rectifier module temperature
IGBT module temperature
0~100.0
0~100.0
℃
℃
P7.11
Accumulated running time
0~65535h
Rectify module temperature: Indicates the temperature of rectify module. Overheat protection point of different inverter may be different.
IGBT module temperature: Indicates the temperature of IGBT module. Overheat protection point of different inverter may be different.
Software version: Indicates current software version of DSP.
62
Detailed Function Description
Accumulated running time: Displays accumulated running time of inverter.
Notice: Above parameters are read only.
Function
Code
P7.12
P7.13
P7.14
Name
Third latest fault type
Second latest fault type
Latest fault type
Description
0~24
0~24
0~24
Setting
Range
Factory Setting
These parameters record three recent fault types. For details, please refer to description of chapter 7.
Function
Code
P7.15
P7.16
P7.17
P7.18
Name Description
Output frequency at current fault
Output current at current fault
DC bus voltage at current fault
Output frequency at current fault.
Output current at current fault.
DC bus voltage at current fault.
This value records ON-OFF input terminal status at current fault.
The meaning of each bit is as below:
Input terminal status at current fault
BIT3 BIT2 BIT1 BIT0
S4 S3 S2 S1
1 indicates corresponding input terminal is ON, while 0 indicates
OFF. Notice: This value is displayed as decimal.
Setting
Range
Factory
Setting
63
Detailed Function Description
P7.19
This value records output terminal status at current fault. The meaning of each bit is as below:
Output terminal status at current fault
BIT3 BIT2 BIT1 BIT0
RO Y
1 indicates corresponding output terminal is ON, while 0 indicates
OFF. Notice: This value is displayed as decimal.
6.9 P8 Group--Enhanced Function
Function
Code
Name
P8.00 Acceleration time 1
P8.01 Deceleration time 1
Description
1.0~3600.0s
Setting Range
Factory
Setting
1.0~3600.0 20.0s
1.0~3600.0 20.0s 1.0~3600.0s
For details, please refer to description of P0.08 and P0.09.
Function
Code
P8.02
P8.03
P8.04
Name
Jog reference
Jog acceleration time
Description
0.00~P0.04
0.1~3600.0s
Setting Range
0.00~ P0.04
0.1~3600.0
Factory
Setting
5.00Hz
Depend on model
The meaning and factory setting of P8.03 and P8.04 is the same as P0.08 and P0.09. No matter what the value of P1.00 and P1.05 are, jog will start as start directly mode and stop as deceleration to stop mode.
Function
Code
Name Description Setting Range
Factory
Setting
P8.06
Skip frequency bandwidth
0.00~P0.04 0.00~P0.04 0.00Hz
By means of setting skip frequency, the inverter can keep away from the mechanical resonance with the load. P8.05 is centre value of frequency to be skipped.
Notice:
If P8.06 is 0, the skip function is invalid.
If P8.05 is 0, the skip function is invalid no matter what P8.06 is.
Operation is prohibited within the skip frequency bandwidth, but changes
64
Detailed Function Description during acceleration and deceleration are smooth without skip.
The relation between output frequency and reference frequency is shown in following figure.
Figure 6.16 Skip frequency diagram.
Function
Code
Name Description
Setting
Range
Factory
Setting
P8.07
Traverse amplitude
P8.08 Jitter 0.0~50.0 0.0%
P8.09
P8.10
Rise time of traverse
Fall time of traverse
0.1~3600.0s 0.1~3600.0
0.1~3600.0s 0.1~3600.0
5.0s
5.0s
Traverse operation is widely used in textile and chemical fiber industry. The typical application is shown in following figure.
Figure 6.17 Traverse operation diagram.
Center frequency (CF) is reference frequency.
Traverse amplitude (AW) =center frequency (CF) * P8.08%
Jitter frequency = traverse amplitude (AW) * P8.08%
Rise time of traverse: Indicates the time rising from the lowest traverse frequency to the
65
Detailed Function Description highest traverse frequency.
Fall time of traverse: Indicates the time falling from the highest traverse frequency to the lowest traverse frequency.
Notice:
P8.07 determines the output frequency range which is as below:
(1-P8.07%) * reference frequency ≤ output frequency ≤ (1+P8.07%) * reference frequency
The output frequency of traverse is limited by upper frequency limit (P0.05) and lower frequency limit (P0.06).
Function
Code
Name Description
Setting
Range
Factory
Setting
P8.11 Auto reset times
1.0s
Auto reset function can reset the fault in preset times and interval. When P8.11 is set to be 0, it means “auto reset” is disabled and the protective device will be activated in case of fault.
Notice: The fault such as OUT 1, OUT 2, OUT 3, OH1 and OH2 cannot be reset automatically.
Function
Code
P8.13
Name
FDT level
Description
0.00~ P0.04
Setting
Range
0.00~ P0.04
Factory
Setting
50.00Hz when the output frequency reaches a certain preset frequency (FDT level), output terminal will output an ON-OFF signal until output frequency drops below a certain frequency of FDT level (FDT level - FDT lag), as shown in following figure.
66
Detailed Function Description
Figure 6.18 FDT level and lag diagram.
Function
Code
Name Description
Setting
Range
Factory
Setting
P8.15
Frequency arrive detecting range
0.0~100.0%
( maximum frequency )
0.0~100.0 0.0%
When output frequency is within the detecting range of reference frequency, an ON-OFF signal will be output.
Figure 6.19 Frequency arriving signal diagram.
Function
Code
P8.16
Name
Brake threshold voltage
Description Setting Range
115.0~140.0% 115.0~140.0
Factory
Setting
Depend on model
When the DC bus voltage is greater than the value of P8.16, the inverter will start dynamic braking.
Notice:
Factory setting is 120% if rated voltage of inverter is 220V.
Factory setting is 130% if rated voltage of inverter is 380V.
The value of P8.16 is corresponding to the DC bus voltage at rated input voltage.
Function
Code
Name Description
Setting
Range
Default
Value
P8.17
Coefficient of rotation speed
0.1~999.9% 0.1~999.9% 100.0%
67
Detailed Function Description
This parameter is used to calibrate the bias between actual mechanical speed and rotation speed. The formula is as below:
Actual mechanical speed = 120 * output frequency *P8.17 / Number of poles of motor
6.10 P9 Group--PID Control
PID control is a common used method in process control, such as flow, pressure and temperature control. The principle is firstly detect the bias between preset value and feedback value, then calculate output frequency of inverter according to proportional gain, integral and differential time. Please refer to following figure.
Figure 6.20 PID control diagram.
Function
Code
Name Description
Setting
Range
Factory
Setting
P9.00
PID preset source selection
0: Keypad
1: AI1
2: AI2
3: Communication
4: Multi-step
0~4 0
P9.01
P9.02
Keypad
PID preset
PID feedback source selection
0.0%~100.0% 0.0~100.0
0: AI1
1: AI2
2: AI1+AI2
3: Communication
0.0%
0~3 0
These parameters are used to select PID preset and feedback source.
Notice:
Preset value and feedback value of PID are percentage value.
100% of preset value is corresponding to 100% of feedback value.
Preset source and feedback source must not be same, otherwise PID will be malfunction.
68
Detailed Function Description
Function
Code
P9.03
Name
PID output characteristics
Description
0: Positive
1: Negative
Setting
Range
Factory
Setting
0~1 0
0 : Positive. When the feedback value is greater than the preset value, output frequency will be decreased, such as tension control in winding application.
1: Negative. When the feedback value is greater than the preset value, output frequency will be increased, such as tension control in unwinding application.
Function
Code
Name
P9.04 Proportional (Kp)
P9.05 Integral time (Ti)
Description Setting Range
Factory
Setting
0.00~100.00 0.00~100.00 0.10
0.01~10.00s 0.01~10.00 0.10s
P9.06 Differential time (Td) 0.00~10.00s 0.00~10.00 0.00s
Optimize the responsiveness by adjusting these parameters while driving an actual load.
Use the following procedure to activate PID control and then adjust it while monitoring the response.
1. Enabled PID control (P0.03=5)
2. Increase the proportional gain (Kp) as far as possible without creating oscillation.
3. Reduce the integral time (Ti) as far as possible without creating oscillation.
4. Increase the differential time (Td) as far as possible without creating oscillation.
Making fine adjustments:
First set the individual PID control constants, and then make fine adjustments. z Reducing
If overshooting occurs, shorten the differential time and lengthen the integral time.
Figure 6.21 Reducing overshooting diagram. z Rapidly stabilizing control status
To rapidly stabilize the control conditions even when overshooting occurs, shorten the integral time and lengthen the differential time.
69
Detailed Function Description
Figure 6.22 Rapidly stabilizing diagram. z Reducing long-cycle oscillation
If oscillation occurs with a longer cycle than the integral time setting, it means that integral operation is strong. The oscillation will be reduced as the integral time is lengthened.
Figure 6.23 Reducing long-cycle oscillation diagram. z Reducing short-cycle oscillation
If the oscillation cycle is short and oscillation occurs with a cycle approximately the same as the differential time setting, it means that the differential operation is strong. The oscillation will be reduced as the differential time is shortened.
Figure 6.24 Reducing short-cycle oscillation diagram.
If oscillation cannot be reduced even by setting the differential time to 0, then either lower the proportional gain or raise the PID primary delay time constant.
Function
Code
Name Description Setting Range
Factory
Setting
P9.07 Sampling cycle (T) 0.01~100.00s 0.01~100.00 0.10s
70
Detailed Function Description
Sampling cycle T refers to the sampling cycle of feedback value. The PI regulator calculates once in each sampling cycle. The bigger the sampling cycle, the slower the response is.
Bias limit defines the maximum bias between the feedback and the preset. PID stops operation when the bias is within this range. Setting this parameter correctly is helpful to improve the system output accuracy and stability.
Figure 6.25 Relationship between bias limit and output frequency.
Function
Code
Name Description
Setting
Range
Factory
Setting
P9.09
P9.10
Feedback lost detecting value
Feedback lost detecting time
0.0~100.0% 0.0~100.0 0.0%
0.0~3600.0s 0.0~3600.0 1.0s
When feedback value is less than P9.09 continuously for the period determined by P9.10, the inverter will alarm feedback lost failure (PIDE).
Notice: 100% of P9.09 is the same as 100% of P9.01.
6.11 PA Group-- Multi-step Speed Control
Function
Code
Name Description Setting Range
Factory
Setting
PA.00 Multi-step speed 0 -100.0~100.0% -100.0~100.0 0.0%
Multi-step speed 1 -100.0~100.0% -100.0~100.0 0.0% PA.01
71
Detailed Function Description
PA.02
PA.03
PA.04
PA.05
PA.06
PA.07
Multi-step speed 2
Multi-step speed 3
Multi-step speed 4
Multi-step speed 5
Multi-step speed 6
Multi-step speed 7
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0
-100.0~100.0
-100.0~100.0
-100.0~100.0
-100.0~100.0
-100.0~100.0
Notice:
100% of multi-step speed x corresponds to the maximum frequency (P0.04).
If the value of multi-step speed x is negative, the direction of this step will be reverse, otherwise it will be forward.
Multi-step speed function has highest priority
Selection of step is determined by combination of multi-step terminals. Please refer to following figure and table.
Figure 6.26 Multi-steps speed operating diagram.
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
72
Detailed Function Description
Terminal
Step
Multi-step speed reference1
Multi-step speed reference2
Multi-step speed reference3
0 OFF OFF OFF
2 OFF ON OFF
3 ON ON OFF
4 OFF OFF ON
5 ON OFF ON
6 OFF ON ON
7 ON ON ON
6.12 PB Group-- Protection Function
Function
Code
Name
PB.00
Motor overload protection
Description
0: Disabled
1: Normal motor
2: Variable frequency motor
Name Description
Setting
Range
Factory
Setting
0~2 2
1: For normal motor, the lower the speed, the poorer the cooling effect. Based on this reason, if output frequency is lower than 30Hz, inverter will reduce the motor overload protection threshold to prevent normal motor from overheat.
2: As the cooling effect of variable frequency motor has nothing to do with running speed, it is not required to adjust the motor overload protection threshold.
Function
Code
Setting
Range
Factory
Setting
PB.01
Motor overload protection current
20.0%~120.0% 20.0~120.0 100.0%
Figure 6.27 Motor overload protection curve.
The value can be determined by the following formula:
Motor overload protection current = (motor rated current / inverter rated current) * 100%
Notice:
73
Detailed Function Description
This parameter is normally used when rated power of inverter is greater than rated power of motor.
Motor overload protection time: 60s with 200% of rated current. For details, please refer to above figure.
Function
Code
Name
PB.02
PB.03
Threshold of trip-free
Decrease rate of trip-free
Description Setting Range
Factory
Setting
70.0~110.0% 70.0~110.0 80.0%
0.00Hz~P0.04 0.00Hz~P0.04 0.00Hz
If PB.03 is set to be 0, the trip-free function is invalid.
Trip-free function enables the inverter to perform low-voltage compensation when DC bus voltage drops below PB.02. The inverter can continue to run without tripping by reducing its output frequency and feedback energy via motor.
Notice: If PB.03 is too big, the feedback energy of motor will be too large and may cause over-voltage fault. If PB.03 is too small, the feedback energy of motor will be too small to achieve voltage compensation effect. So please set PB.03 according to load inertia and the actual load.
Function
Code
Name Description
Setting
Range
Factory
Setting
PB.04
PB.05
Over-voltage stall protection
Over-voltage stall protection point
0: Disabled
1: Enabled
0~1 1
110~150% 110~150
380V:130%
220V:120%
During deceleration, the motor’s decelerating rate may be lower than that of inverter’s output frequency due to the load inertia. At this time, the motor will feed the energy back to the inverter, resulting in DC bus voltage rise. If no measures taken, the inverter will trip due to over voltage.
During deceleration, the inverter detects DC bus voltage and compares it with over-voltage stall protection point. If DC bus voltage exceeds PB.05, the inverter will stop reducing its output frequency. When DC bus voltage become lower than PB.05, the deceleration continues, as shown in following figure.
74
Detailed Function Description
Figure 6.28 Over-voltage stall function.
Function
Code
PB.06
PB.07
Name
Auto current limiting threshold
Frequency decrease rate when current limiting
Description
0.00~100.00Hz/s
Setting Range Factory Setting
0.00~100.00 10.00Hz/s
Auto current limiting is used to limit the current of inverter smaller than the value determined by PB.06 in real time. Therefore the inverter will not trip due to surge over-current. This function is especially useful for the applications with big load inertia or step change of load.
PB.06 is a percentage of the inverter’s rated current.
PB.07 defines the decrease rate of output frequency when this function is active. If PB.06 is too small, overload fault may occur. If it is too big, the frequency will change too sharply and therefore, the feedback energy of motor will be too large and may cause over-voltage fault. This function is always enabled during acceleration or deceleration.
Notice:
During auto current limiting process, the inverter’s output frequency may change; therefore, it is recommended not to enable the function when requires the inverter’s output frequency stable.
During auto current limiting process, if PB.06 is too low, the overload capacity will be impacted.
Please refer to following figure.
75
Detailed Function Description
Figure 6.29 Current limiting protection function.
6.13 PC Group--Serial Communication
Function
Code
Name Description
Setting
Range
Factory
Setting
PC.00 Local 1~247 0~247 1
This parameter determines the slave address used for communication with master. The value “0” is the broadcast address.
Function
Code
Name selection
Description
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
Setting
Range
Factory
Setting
0~5 3
This parameter can set the data transmission rate during serial communication.
Notice: The baud rate of master and slave must be the same.
Function
Code
Name Description
PC.02
Data format
Setting
Range
Factory
Setting
This parameter defines the data format used in serial communication protocol.
0: RTU, 1 start bit, 8 data bits, no parity check, 1 stop bit.
1: RTU, 1 start bit, 8 data bits, even parity check, 1 stop bit.
2: RTU, 1 start bit, 8 data bits, odd parity check, 1 stop bit.
3: RTU, 1 start bit, 8 data bits, no parity check, 2 stop bits.
4: RTU, 1 start bit, 8 data bits, even parity check, 2 stop bits.
5: RTU, 1 start bit, 8 data bits, odd parity check, 2 stop bits.
6: ASCII, 1 start bit, 7 data bits, no parity check, 1 stop bit.
7: ASCII, 1 start bit, 7 data bits, even parity check, 1 stop bit.
8: ASCII, 1 start bit, 7 data bits, odd parity check, 1 stop bit.
9: ASCII, 1 start bit, 7 data bits, no parity check, 2 stop bits.
76
Detailed Function Description
10: ASCII, 1 start bit, 7 data bits, even parity check, 2 stop bits.
11: ASCII, 1 start bit, 7 data bits, odd parity check, 2 stop bits.
12: ASCII, 1 start bit, 8 data bits, no parity check, 1 stop bit.
13: ASCII, 1 start bit, 8 data bits, even parity check, 1 stop bit.
14: ASCII, 1 start bit, 8 data bits, odd parity check, 1 stop bit.
15: ASCII, 1 start bit, 8 data bits, no parity check, 2 stop bits.
16: ASCII, 1 start bit, 8 data bits, even parity check, 2 stop bits.
17: ASCII, 1 start bit, 8 data bits, odd parity check, 2 stop bits.
Function
Code
Name Description
Setting range
PC.03
Communication delay time
Factory
Setting
0~200ms 0~200 5ms
This parameter can be used to set the response delay in communication in order to adapt to the MODBUS master. In RTU mode, the actual communication delay should be no less than 3.5 characters’ interval; in ASCII mode, 1ms.
Function
Code
Name Description
Setting
Range
PC.04
Communication timeout delay
0.0: Disabled
0.1~100.0s
Factory
Setting
0~100.0 0.0s
When the value is zero, this function will be disabled. When communication interruption is longer than the non-zero value of PC.04, the inverter will alarm communication error
(CE).
Function
Code
Name Description
Setting
Range
Factory
Setting
PC.05
Communication error action
0: Alarm and coast to stop
1: No alarm and continue to run
2: No alarm but stop according to P1.05 (if
P0.01=2)
3: No alarm but stop according to P1.05
0~3 1
0: When communication error occurs, inverter will alarm (CE) and coast to stop.
1: When communication error occurs, inverter will omit the error and continue to run.
2: When communication error occurs, if P0.01=2, inverter will not alarm but stop according to stop mode determined by P1.05. Otherwise it will omit the error.
3: When communication error occurs, inverter will not alarm but stop according to stop
77
Detailed Function Description mode determined by P1.05.
Function
Code
Name
PC.06
Response action
Description
Unit’s place of LED
0: Response to writing
1: No response to writing
Ten’s place of LED
0: Reference not saved when power off
1: Reference saved when power off
Setting
Range
Factory
Setting
0~1 0~1
Figure 6.30 Meaning of PC.06.
A stands for: Unit’s place of LED.
B stands for: Ten’s place of LED
6.14 PD Group—Supplementary Function
Function
Code
Name
PD.00
PD.01
Low-frequency threshold of restraining oscillation
High-frequency threshold of restraining oscillation
Description
Setting
Range
Factory
Setting
0~500 0~500 5
0~500 0~500 100
This function is valid only when PD.04 is set to be 0. The smaller the value of PD.00 and
PD.01, the stronger the restraining effect.
Notice: Most motor may have current oscillation at some frequency point. Please be cautious to adjust these parameters to weaken oscillation.
Function
Code
Name Description
Setting
Range
Factory
Setting
PD.02
Amplitude of restraining oscillation
0~10000 0~10000 5000
This parameter is used to limit the strength of restraining oscillation. If the value of PD.02
78
Detailed Function Description is too big, it may cause inverter over current. It should be set a little bit smaller for large power motor, vice versa.
Function
Code
Name Description Setting Range
Factory
Setting
PD.03
Boundary of restraining oscillation
0.0~P0.04 0.0HZ~P0.04
12.5HZ
If output frequency is greater than PD.03, PD.00 takes effect, otherwise PD.01 takes effect.
Function
Code
Name Description
Setting
Range
Factory
Setting oscillation
0: Enabled
1: Disabled
0~1 0
Motor always has current oscillation when its load is light. This will cause abnormal operation even over-current. For details, please refer to description of PD.00~PD.03.
Function
Code
Name Description
Setting
Range
Factory
Setting
0: PWM mode 1 mode 1: PWM mode 2
2: PWM mode 3
0~2 0
The features of each mode, please refer the following table:
Mode
PWM mode 1
Noise in lower frequency
Low
Noise in higher frequency high
PWM mode 2
PWM mode 3 low high
Others
Need to be derated, because of higher temperature rise.
Can more effectively restrain the oscillation
Function
Code
Name
Setting
Range
Factory
Setting
PD.06
Torque setting source
Description
0: Keypad
1: AI1
2: AI2
3: AI1+AI2
4: Multi-step setting
5: Communication
0~5 0
PD.07
Keypad torque setting
-100.0%~100.0% -100.0%~100.0% 50.0% z When torque control takes effect, if Tset > Tload, output frequency will increase continuously until it reaches upper
79
Detailed Function Description frequency limit.
If Tset < Tload, output frequency will decrease continuously until it reaches lower frequency limit.
Inverter can run at any frequency between upper and lower frequency limit only when Tset = Tload. z Torque control can be switched to speed control, vice versa.
Switching by multifunctional terminal: For example, if torque control is enabled (P0.00=2), torque setting source is AI1, the value of multifunction terminal S5 is set to 20 (Disable torque control). When S5 is valid, control mode will switch from torque control to speed control, vice versa.
When running at torque control mode, press STOP/RST, it will switch to speed control automatically. z If torque setting is positive, inverter will run forward; otherwise it will run reverse.
Notice:
When running at torque control mode, the acceleration time has nothing to do with P0.08.
The 100% of torque setting is corresponding to 100% of P3.07 (Torque limit).
For example, if torque setting source is keypad (PD.06=0), PD.07=80% and
P3.07=90%, then
Actual torque setting = 80% (PD.07) * 90% (P3.07) = 72%.
Function
Code
Name Description
Setting
Range
Factory
Setting
PD.08
Upper frequency limit selection
0: Keypad
1: AI1
2: AI2
3: Multi-step setting
4: Communication
0~4 0
The 100% of this parameter is corresponding to 100% of P0.04 (maximum frequency).
When running at torque control mode, output frequency can be adjusted by changing upper frequency limit.
Function
Code
Name Description
Setting
Range
Factory
Setting
PD.09
Auto current limiting selection
0: Enabled
1: Disabled when constant speed
0~1 0
Auto current limiting function is used to prevent inverter trip over-current from surge current. It is especially useful for the applications with big load inertia or step change of
80
Detailed Function Description load. This function is always enabled during acceleration or deceleration period.
Notice: During auto current limiting process, the inverter’s output frequency may change; therefore, it is recommended not to enable the function when output frequency need to be stable.
6.15 PE Group—Factory Setting
This group is the factory-set parameter group. The user DO NOT try to open these group parameters, otherwise it will cause the inverter abnormal operation or damage.
7. TROUBLE SHOOTING
7.1 Fault and Trouble shooting
Fault
Code
Fault Type
OUT1 IGBT Ph-U fault
OUT2
OUT3
IGBT Ph-V fault
IGBT Ph-W fault
Reason
1. Acc/Dec time is too short.
2. IGBT module fault.
3. Malfunction caused by interference.
4. Grounding is not properly.
OC1
OC2
OC3
Over-current when acceleration
Over-current when deceleration
Over-current when constant speed running
1. Short-circuit or ground fault occurred at inverter output.
2. Load is too heavy or
Acc/Dec time is too short.
3. V/F curve is not suitable.
4. Sudden change of load.
81
Solution
1. Increase Acc/Dec time.
2. Ask for support.
3. Inspect external equipment and eliminate interference.
1. Inspect whether motor damaged, insulation worn or cable damaged.
2. Increase Acc/Dec time or select bigger capacity inverter.
3. Check and adjust V/F curve.
Check the load.
Trouble Shooting
OV1
OV2
OV3
UV
SPI
SPO
Over-voltage when acceleration
Over-voltage when deceleration
Over-voltage when constant speed running
1. Dec time is too short and regenerative energy from the motor is too large.
2. Input voltage is too high.
1. Increase Dec time or connect braking resistor
2. Decrease input voltage within specification.
DC bus
Under-voltage
Input phase failure
Output phase failure
1. Open phase occurred with power supply.
2. Momentary power loss occurred
3. Wiring terminals for input power supply are loose.
4. Voltage fluctuations in power supply are too large.
Inspect the input power supply or wiring.
1. Motor drive heavy load at low speed for a long time. protection threshold (PB.01)
4. Sudden change of load.
1. Load is too heavy or
Acc/Dec time is too short.
2. Improper V/F curve
3. Capacity of inverter is too small.
1. Select variable frequency motor.
2. Check and adjust V/F curve.
3. Check and adjust
PB.01
4. Check the load.
1. Increase Acc/Dec time or select bigger capacity inverter.
2. Check and adjust V/F curve.
3. Select bigger capacity inverter.
1. Open-phase occurred in power supply.
2. Momentary power loss occurred.
3. Wiring terminals for input power supply are loose.
4. Voltage fluctuations in power supply are too large.
5. Voltage balance between phase is bad.
1. There is a broken wire in the output cable
2. There is a broken wire in the motor winding.
3. Output terminals are loose.
Check the wiring, installation and power supply.
Check the wiring and installation.
Inspect external equipment.
82
Trouble Shooting
CE
ITE
PIDE
BCE
1.Ambient temperature is too high. overheat
3. Cooling fans of inverter stop or damaged.
4. Obstruction of ventilation channel
5. Carrier frequency is too
Communication fault
Current detection fault high.
1. Improper baud rate setting.
2. Receive wrong data.
3. Communication is interrupted for Long time
1. Wires or connectors of control board are loose
2. Hall sensor is damaged.
3. Amplifying circuit is abnormal.
PID feedback fault
Brake unit fault
1. Install cooling unit.
2. Remove heat source.
3. Replace cooling fan
4. Clear the ventilation channel.
5. Decrease carrier frequency.
1. Set proper baud rate.
2. Check communication devices and signals.
1. Check the wiring.
2. Ask for support.
1. Improper setting of motor
2. Overtime of autotuning.
1. PID feedback disconnected.
2. PID feedback source disappears.
1. Braking circuit failure or brake tube damaged.
2. Too low resistance of externally connected braking resistor.
1. Set rated parameters according to motor nameplate.
2. Check motor’s wiring.
Press STOP/RESET to reset
Ask for support
1. Inspect PID feedback signal wire.
2. Inspect PID feedback source.
1. Inspect braking unit, replace braking tube.
2. Increase braking resistance.
Factory
7.2 Common Faults and Solutions
Inverter may have following faults or malfunctions during operation, please refer to the following solutions.
7.2.1 No display after power on: z Inspect whether the voltage of power supply is the same as the inverter rated voltage or not with multi-meter. If the power supply has problem, inspect and solve it. z Inspect whether the three-phase rectify bridge is in good condition or not. If the rectification bridge is burst out, ask for support. z Check the CHARGE light. If the light is off, the fault is mainly in the rectify bridge or
83
Trouble Shooting the buffer resistor. If the light is on, the fault may be lies in the switching power supply. Please ask for support.
7.2.2 Power supply air switch trips off when power on: z Inspect whether the input power supply is grounded or short circuit. Please solve the problem. z Inspect whether the rectify bridge has been burnt or not. If it is damaged, ask for support.
7.2.3 Motor doesn’t move after inverter running: z Inspect if there is balanced three-phase output among U, V, W. If yes, then motor could be damaged, or mechanically locked. Please solve it. z If the output is unbalanced or lost, the inverter drive board or the output module may be damaged, ask for support..
7.2.4 Inverter displays normally when power on, but switch at the input side trips when running: z Inspect whether the output side of inverter is short circuit. If yes, ask for support. z Inspect whether ground fault exists. If yes, solve it. z If trip happens occasionally and the distance between motor and inverter is too far, it is recommended to install output AC reactor.
8. MAINTENANCE
WARNING
● Maintenance must be performed according to designated maintenance methods.
● Maintenance, inspection and replacement of parts must be performed only by authorized personnel.
● After turning off the main circuit power supply, waiting for 10 minutes before performance maintenance or inspection.
● DO NOT directly touch components or devices of PCB board. Otherwise inverter can be damaged by electrostatic.
● After maintenance, all screws must be tightened.
84
Maintenance
8.1 Daily Maintenance
In order to prevent the fault of inverter to make it operate smoothly in high-performance for a long time, user must inspect the inverter periodically (within half year). The following table indicates the inspection content.
Items to be checked
Main inspections
Inspection content
Criteria
Frequency Means/methods
1. ambient temperature shall
Operation environment
Inverter
1. temperature
2. humidity
3. dust
4. vapor
5. gases
1. vibration
2. cooling and heating
3. noise
1. point thermometer, hygrometer
2. observation
3. visual examination and smelling
1. point thermometer
2. comprehensive observation
3. listening the rated values should be decreased. Humidity shall meet the requirement
2. no dust accumulation, no traces of water leakage and no condensate.
3. no abnormal color and smell.
1. smooth operation without vibration.
2. fan is working in good condition. Speed and air flow are normal. No abnormal heat.
3. No abnormal noise
Motor
1. vibration
2. heat
3. noise
1. comprehensive observation
2. point thermometer
3. listening
1. No abnormal vibration and no abnormal noise.
2. No abnormal heat.
3. No abnormal noise.
Operation status parameters
1. power input voltage
2. inverter output voltage
3. inverter output current
4. internal temperature
1. voltmeter
2. rectifying voltmeter
3. ammeter
4. point thermometer
1. satisfying the specification
2. satisfying the specification
3. satisfying the specification
4. temperature rise is lower than 40
8.2 Periodic Maintenance
Customer should check the drive every 3 months or 6 months according to the actual
85
Maintenance environment
8.2.1 Check whether the screws of control terminals are loose. If so, tighten them with a screwdriver;
8.2.2 Check whether the main circuit terminals are properly connected; whether the mains cables are over heated;
8.2.3 Check whether the power cables and control cables are damaged, check especially for any wear on the cable tube;
8.2.4 Check whether the insulating tapes around the cable lugs are stripped;
8.2.5 Clean the dust on PCBs and air ducts with a vacuum cleaner;
8.2.6 For drives that have been stored for a long time, it must be powered on every 2 years. When supplying AC power to the drive, use a voltage regulator to raise the input voltage to rated input voltage gradually. The drive should be powered for 5 hours without load.
8.2.7 Before performing insulation tests, all main circuit input/output terminals should be short-circuited with conductors. Then proceed insulation test to the ground. Insulation test of single main circuit terminal to ground is forbidden; otherwise the drive might be damaged. Please use a 500V Mega-Ohm-Meter.
8.2.8 Before the insulation test of the motor, disconnect the motor from the drive to avoid damaging it.
8.3 Replacement of wearing parts
Fans and electrolytic capacitors are wearing part, please make periodic replacement to ensure long term, safety and failure-free operation. The replacement periods are as follows:
◆ Fan: Must be replaced when using up to 20,000 hours;
◆ Electrolytic Capacitor: Must be replaced when using up to 30,000~40, 000 hours.
8.4 Warranty
The manufacturer warrants its products for a period of 12 months from the date of purchase.
86
Maintenance
9. LIST OF FUNCTION PARAMETERS
Notice:
PE group is factory reserved, users are forbidden to access these parameters.
The column “Modify” determines the parameter can be modified or not.
“
○
” indicates that this parameter can be modified all the time.
“ ◎ ”indicates that this parameter cannot be modified during the inverter is running.
“
●
” indicates that this parameter is read only.
“Factory Setting” indicates the value of each parameter while restoring the factory parameters, but those detected parameters or record values cannot be restored.
Function
Code
Name Description
Factory
Setting
Modify
Serial
No.
87
List of Function Parameters
Function
Code
Name
P0 Group: Basic Function
Description
Factory
Setting
P0.00
P0.01
Control mode selection
Run command source
0:Sensorless vector control
1:V/F control
2:Torque control
0: Keypad (LED extinguishes)
1: Terminal (LED flickers)
2: Communication (LED lights up)
0
0
P0.02
P0.03
UP/DOWN setting
Frequency A command source
0: Valid, save UP/DOWN value when power off
1: Valid, do not save UP/DOWN value when power off
2: Invalid
3: Valid during running, clear when stop.
0: Keypad
1: AI1
2. AI2
3: AI1+AI2
4. Multi-Step speed
5: PID
6: Communication
P0.04 Maximum frequency 10.00~400.00Hz
P0.05 Upper frequency limit P0.06~ P0.04
P0.06 Lower frequency limit 0.00 Hz ~ P0.05
0
0
50.00Hz
50.00Hz
0.00Hz
P0.07
Keypad reference frequency
0.00 Hz ~ P0.04 50.00Hz
P0.08
P0.09
Acceleration time 0 0.0~3600.0s
Deceleration time 0 0.0~3600.0s
Depend on model
Depend on model
P0.10
Running direction selection
0: Forward
1: Reverse
2: Forbid reverse
0
P0.11 Carrier frequency 1.0~15.0kHz
Depend on model
P0.12
Motor parameters autotuning
0: No action
1: Rotation autotuning
2: Static autotuning
0
Modify
Serial
No.
O
O
O
O
O
O
O
O
0
1
2
3
4
5
6
7
8
9
10
11
12
88
Function
Code
Name Description
P0.13
P0.14
Restore parameters
0: No action
1: Restore factory setting
2: Clear fault records
AVR function
0: Disabled
1: Enabled all the time
2: Disabled during deceleration
P1 Group: Start and Stop Control
P1.00 Start Mode
0: Start directly
1: DC braking and start
P1.01
P1.02
P1.03
P1.04
P1.05
P1.06
P1.07
P1.08
P1.09
P1.10
Starting frequency 0.00~10.00Hz
Hold time of starting frequency
0.0~50.0s
DC Braking
current before start
0.0~150.0%
DC Braking time before start
0.0~50.0s
Stop mode
0: Deceleration to stop
1: Coast to stop
Starting frequency of
DC braking
0.00~P0.04
Waiting time before
DC braking
0.0~50.0s
DC braking current 0.0~150.0%
DC braking time
Dead time of
FWD/REV
0.0~50.0s
0.0~3600.0s
P1.11
FWD/REV enable when power on
0: Disabled
1: Enabled
P1.12 Reserved
P2 Group: Motor Parameters
P2.00 G/P option
0: G model
1: P model
P2.01 Motor rated power 0.4~900.0kW
89
List of Function Parameters
Factory
Setting
Modify
Serial
No.
0 13
2 O 14
0
1.5Hz
0.0s
O
O
15
16
17
0.0% O 18
0.0s
0
0.00Hz
O
0.0s
0.0%
0.0s
0.0s
O
O
O
O
O
O
21
22
23
24
25
19
20
0~1
0
O
26
27
Depend on model
Depend on model
28
29
List of Function Parameters
Function
Code
P2.02
P2.03
Name
Motor rated frequency
0.01Hz~P0.04
Motor rated speed 0~36000rpm
Description
P2.04 Motor rated voltage 0~2000V
P2.05 Motor rated current 0.8~2000.0A
P2.06
P2.07
Motor stator resistance
Motor rotor resistance
0.001~65.535
0.001~65.535
Ω
Ω
P2.08
P2.09
Motor leakage inductance
Motor mutual inductance
0.1~6553.5mH
0.1~6553.5mH
P2.10 Current without load 0.01~655.35A
P3 Group: Vector Control
P3.00
ASR proportional gain K p
1
0~100
P3.01 ASR integral time K i
1 0.01~10.00s
P3.02
P3.03
ASR switching point
1
0.00Hz~P3.05
ASR proportional gain K p
2
0~100
P3.04 ASR integral time K i
2 0.01~10.00s
P3.05
ASR switching point
2
P3.02~P0.04
P3.06
P3.07
Slip compensation rate of VC
Torque limit
50.0~200.0%
0.0~200.0%
90
Factory
Setting
Modify
Serial
No.
30 50.00Hz
Depend on model
Depend on model
Depend on model
Depend on model
Depend on model l
Depend on model
Depend on model
Depend on model
O
O
O
O
O
31
32
33
34
35
36
37
38
20
0.50s
○
○
39
40
5.00Hz
○ 41
15
1.00s
○
○
42
43
10.00Hz
○ 44
100%
150.0%
O
O
45
46
List of Function Parameters
Function
Code
Name
P4 Group: V/F Control
P4.00
P4.01
Description
V/F curve selection
0:Linear curve
1: Torque_stepdown curve (2.0 order)
Torque boost
0.0%: (auto)
0.1
% ~10.0
%
P4.02
P4.03
P4.04
Torque boost cut-off 0.0%~50.0% (motor rated frequency)
V/F Slip compensation limit
0.00~200.0%
Auto energy saving selection
0: Disabled
1: Enabled
P4.05 Reserved
P5 Group: Input Terminals
P5.00
P5.01
P5.02
P5.03
S1 terminal function
S2 terminal function
S3 terminal function
S4 terminal function
0: Invalid
1: Forward
2: Reverse
3: 3-wire control
4: JOG forward
5: JOG reverse
6: Coast to stop
7: Reset fault
8: External fault input
9: UP command
10: DOWN command
11: Clear UP/DOWN
12: Multi-step speed reference 1
13: Multi-step speed reference 2
14: Multi-step speed reference 3
15: ACC/DEC time selection
16: Pause PID
17: Pause traverse operation
18: Reset traverse operation
19: ACC/DEC ramp hold
20: Disable torque control
21: UP/DOWN invalid temporarily
22-25: reserved
P5.04 ON/OFF filter times 1~10
Factory
Setting
Modify
Serial
No.
0
0.0%
20.0%
0.0%
O
O
0
●
47
48
49
50
51
52
1
4
7
0
5
53
54
55
56
O 57
91
List of Function Parameters
Function
Code
Name Description
P5.05
P5.06
P5.07
P5.08
FWD/REV control mode
0: 2-wire control mode 1
1: 2-wire control mode 2
2: 3-wire control mode 1
3: 3-wire control mode 2
UP/DOWN setting change rate
0.01~50.00Hz/s
0.00V~10.00V AI1 lower limit
AI1 lower limit corresponding setting
-100.0%~100.0%
P5.09
P5.10
P5.11
P5.12
AI1 upper limit
AI1 upper limit corresponding setting
AI1 filter time constant
AI2 lower limit
P5.13
P5.14
P5.15
AI2 lower limit corresponding setting
AI2 upper limit
AI2 upper limit corresponding setting
P5.16
AI2 filter time constant
P6 Group: Output Terminals
0.00V~10.00V
-100.0%~100.0%
0.00s~10.00s
0.00V~10.00V
-100.0%~100.0%
0.00V~10.00V
-100.0%~100.0%
0.00s~10.00s
P6.00
P6.01
Y output selection
Relay output selection
0: No output
1: Run forward
2: Run reverse
3: Fault output
4: FDT reached
5: Frequency reached
6: Zero speed running
7: Upper frequency limit reached
8: Lower frequency limit reached
9~10: reserved
92
Factory
Setting
Modify
Serial
No.
0 58
0.50
Hz/s
0.00V
O
O
0.0% O
59
60
61
10.00V
O
100.0% O
62
63
0.10s
0.00V
O
O
0.0%
10.00V
O
O
100.0% O
64
65
66
67
68
0.10s
O 69
1 O 70
3 O 71
List of Function Parameters
Function
Code
Name Description
P6.02
P6.03
P6.04
P6.05
AO selection
0: Running frequency
1: Reference frequency
2: Motor speed
3: Output current
4: Output voltage
5: Output power
6: Output torque
7: AI1 voltage
8: AI2 voltage/current
9~10: reserved
AO lower limit 0.0%~100.0%
AO lower limit corresponding output
0.00V ~10.00V
AO upper limit 0.0%~100.0%
P6.06
AO upper limit corresponding output
0.00V ~10.00V
P7 Group: Display Interface
P7.00 User password 0~65535
P7.01
LCD language selection
0: Chinese
1: English
P7.02
P7.03
P7.04
P7.05
Parameter copy
0: Invalid
1: Upload from inverter
2: Download to inverter
QUICK/JOG function selection
0: Jog
1: FDW/REV switching
2: Clear UP/DOWN setting
STOP/RST function option
0: Valid when keypad control (P0.01=0)
1: Valid when keypad or terminal control
(P0.01=0 or 1)
2: Valid when keypad or communication control (P0.01=0 or 2)
3: Always valid
Keypad display selection
0: Preferential to external keypad
1: Both display, only external key valid.
2: Both display, only local key valid.
3: Both display and key valid.
Factory
Setting
Modify
Serial
No.
0
0.0%
0.00V
100.0%
10.00V
0
0
0
0
0
0
O
O
O
O
O
O
O
O
O
72
73
74
75
76
77
78
79
80
81
82
93
List of Function Parameters
Function
Code
Name Description
P7.06
P7.07
P7.08
P7.09
P7.10
P7.11
Running status display selection
0~0X7FFF
BIT0: Output frequency
BIT1: Reference frequency
BIT2: DC bus voltage
BIT3: Output voltage
BIT4: Output current
BIT5: Rotation speed
BIT6: Output power
BIT7: Output torque
BIT8: PID preset
BIT9: PID feedback
BIT10: Input terminal status
BIT11: Output terminal status
BIT12: AI1
BIT13: AI2
BIT14: Step No. of multi-step
BIT15: Reserved
Stop status display selection
0~0X1FF
BIT0: Reference frequency
BIT1: DC bus voltage
BIT2: Input terminal status
BIT3: Output terminal status
BIT4: PID preset
BIT5: PID feedback
BIT6: AI1
BIT7: AI2
BIT8: Step No. of multi-step
BIT9~15: Reserved
Rectifier module temperature
0~100.0
℃
IGBT module temperature
Software version
0~100.0
℃
Accumulated running time
0~65535h
Factory
Setting
Modify
Serial
No.
0XFF O 83
0xFF O 84
● 85
●
●
●
86
87
88
94
List of Function Parameters
Function
Code
Name Description
P7.12 Third latest fault type
P7.13
P7.14
Second latest fault type
Current fault type
0: Not fault
1: IGBT Ph-U fault(OUT1)
2: IGBT Ph-V fault(OUT2)
3: IGBT Ph-W fault(OUT3)
4: Over-current when
acceleration(OC1)
5: Over-current when
deceleration(OC2)
6: Over-current when constant speed running (OC3)
7: Over-voltage when
acceleration(OV1)
8: Over-voltage when
deceleration(OV2)
9: Over-voltage when constant speed running(OV3)
10: DC bus Under-voltage(UV)
11: Motor overload (OL1)
12: Inverter overload (OL2)
13: Input phase failure (SPI)
14: Output phase failure (SPO)
15: Rectify overheat (OH1)
16: IGBT overheat (OH2)
17: External fault (EF)
18: Communication fault (CE)
19: Current detection fault (ITE)
20: Autotuning fault (TE)
21: EEPROM fault (EEP)
22: PID feedback fault (PIDE)
23: Brake unit fault (BCE)
24: Reserved
P7.15
P7.16
P7.17
P7.18
Output frequency at current fault
Output frequency at current fault.
Output current at current fault
DC bus voltage at current fault
Output current at current fault.
DC bus voltage at current fault.
Input terminal status at current fault
BIT3 BIT2 BIT1
S4 S3 S2 S1
BIT0
Factory
Setting
Modify
Serial
No.
● 89
● 90
● 91
● 92
● 93
● 94
● 95
95
List of Function Parameters
Function
Code
Name Description
P7.19
Output terminal status at current fault
BIT3 BIT2 BIT1
R0 Y
BIT0
P8 Group: Enhanced Function
P8.00 Acceleration time 1 0.1~3600.0s
P8.01 Deceleration time 1 0.1~3600.0s
P8.02 Jog reference 0.00~P0.04
P8.03 Jog acceleration time 0.1~3600.0s
P8.04 Jog deceleration time 0.1~3600.0s
P8.05
P8.06
Skip frequency
Skip frequency bandwidth
P8.07
P8.10
Traverse amplitude 0.0~100.0%
P8.08 Jitter frequency 0.0~50.0%
P8.09 Rise time of traverse 0.1~3600.0s
Fall time of traverse 0.1~3600.0s
P8.11 Auto reset times
0.00~P0.04
0.00~P0.04
0~3
P8.12 Reset interval 0.1~100.0s
P8.13
P8.14
P8.15
P8.16
P8.17
FDT level
FDT lag
Frequency arrive detecting range
Brake threshold voltage
0.00~ P0.04
0.0~100.0%
0.0~100.0%
115.0~140.0%
Coefficient of rotation speed
0.1~999.9%
( maximum frequency )
P9 Group: PID Control
Factory
Setting
Modify
Serial
No.
● 96
0.00Hz
0.0%
0.0%
5.0s
5.0s
0
1.0s
50.00Hz
5.0%
Depend on model
Depend on model
5.00Hz
Depend on model
Depend on model
0.00Hz
O
O
O
O
O
O
○
O
O
O
O
O
O
O
O
0.0% O
Depend on model
100.0%
O
O
113
114
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
96
Function
Code
Name Description
P9.00
PID preset source selection
0: Keypad
1: AI1
2: AI2
3: Communication
4: Multi-step
P9.01 Keypad PID preset 0.0%~100.0%
P9.02
P9.03
PID feedback source selection
0: AI1
1: AI2
2: AI1+AI2
3: Communication
PID output characteristics
0: Positive
1: Negative
P9.04
Proportional gain
(Kp)
0.00~100.00
P9.05 Integral time (Ti) 0.01~10.00s
P9.06 Differential time (Td) 0.00~10.00s
P9.07 Sampling cycle (T) 0.01~100.00s
P9.08 0.0~100.0%
P9.09
Bias limit
Feedback lost detecting value
0.0~100.0%
P9.10
Feedback lost detecting time
0.0~3600.0s
PA Group: Multi-step Speed Control
PA.00
PA.01
PA.02
PA.03
PA.04
Multi-step speed 0 -100.0~100.0%
Multi-step speed 1 -100.0~100.0%
Multi-step speed 2 -100.0~100.0%
Multi-step speed 3 -100.0~100.0%
Multi-step speed 4 -100.0~100.0%
PA.05
PA.06
Multi-step speed 5 -100.0~100.0%
Multi-step speed 6 -100.0~100.0%
PA.07 Multi-step speed 7 -100.0~100.0%
PB Group: Protection Function
List of Function Parameters
Factory
Setting
Modify
Serial
No.
0 O 115
0.0% O 116
0 O 117
0
1.00
0.10s
0.00s
0.10s
0.0%
0.0%
1.0s
O 118
O
O
O
O
O
O
O
119
120
121
122
123
124
125
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
O
O
O
O
O
O
O
O
130
131
132
133
126
127
128
129
97
List of Function Parameters
Function
Code
Name Description
PB.00
Motor overload protection
0: Disabled
1: Normal motor
2: Variable frequency motor
PB.01
Motor overload protection current
20.0%~120.0%
PB.02 Threshold of trip-free 70.0~110.0%
PB.03
PB.04
PB.05
Decrease rate of trip-free
Over-voltage stall protection
Over-voltage stall protection point
0.00Hz~P0.04
0: Disabled
1: Enabled
110~150%
PB.06
PC.01
Auto current limiting threshold
50~200%
PB.07
Frequency decrease rate when current limiting
0.00~100.00Hz/s
PC Group: Serial Communication
PC.00 Local address 0~247
Baud rate selection
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
PC.02 Data format
0: RTU, 1 start bit, 8 data bits, no parity check, 1 stop bit.
1: RTU, 1 start bit, 8 data bits, even parity check, 1 stop bit.
2: RTU, 1 start bit, 8 data bits, odd parity check, 1 stop bit.
3: RTU, 1 start bit, 8 data bits, no parity check, 2 stop bits.
4: RTU, 1 start bit, 8 data bits, even parity check, 2 stop bits.
5: RTU, 1 start bit, 8 data bits, odd parity check, 2 stop bits.
6: ASCII, 1 start bit, 7 data bits, no parity check, 1 stop bit.
7: ASCII, 1 start bit, 7 data bits, even parity check, 1 stop bit.
98
Factory
Setting
Modify
Serial
No.
2
100.0%
80.0%
0.00Hz
0
Depend on model
G:160%
P:120%
10.00
Hz/s
1
4
0
O
O
O
O
O
O
O
O
O
O
134
135
136
137
138
139
140
141
142
143
144
List of Function Parameters
Function
Code
Name Description
Factory
Setting
Modify
Serial
No.
PC.03
PC.04
PC.05
PC.06
8: ASCII, 1 start bit, 7 data bits, odd parity check, 1 stop bit.
9: ASCII, 1 start bit, 7 data bits, no parity check, 2 stop bits.
10: ASCII, 1 start bit, 7 data bits, even parity check, 2 stop bits.
11: ASCII, 1 start bit, 7 data bits, odd parity check, 2 stop bits.
12: ASCII, 1 start bit, 8 data bits, no parity check, 1 stop bit.
13: ASCII, 1 start bit, 8 data bits, even parity check, 1 stop bit.
14: ASCII, 1 start bit, 8 data bits, odd parity check, 1 stop bit.
15: ASCII, 1 start bit, 8 data bits, no parity check, 2 stop bits.
16: ASCII, 1 start bit, 8 data bits, even parity check, 2 stop bits.
17: ASCII, 1 start bit, 8 data bits, odd parity check, 2 stop bits.
Communication delay time
0~200ms
Communication timeout delay
Response action
0.0: Disabled
0.1~100.0s
Communication error action
0: Alarm and coast to stop
1: No alarm and continue to run
2: No alarm but stop according to P1.05 (if
P0.01=2)
3: No alarm but stop according to P1.05
Unit’s place of LED
0: Response to writing
1: No response to writing
Ten’s place of LED
0: Reference not saved when power off
1: Reference saved when power off
PD Group: Supplementary Function
PD.00
PD.01
Low-frequency threshold of restraining oscillation
0~500
High-frequency threshold of restraining oscillation
0~500
5
0.0s
1
0
5
100
O
O
O
O
O
O
145
146
147
148
149
150
99
List of Function Parameters
Function
Code
Name Description
PD.02
PD.03
PD.04
PD.05
PD.06
Amplitude of restraining oscillation
0~10000
Boundary of restraining oscillation
0.0~P0.04
Restrain oscillation
0: Enabled
1: Disabled
PWM mode
Torque setting source
0: PWM mode 1
1: PWM mode 2
2: PWM mode 3
0: Keypad
1: AI1
2: AI2
3: AI1+AI2
4: Multi-step setting
5: Communication
PD.07
PD.08
Keypad torque setting
-100.0%~100.0%
Upper frequency limit selection
0: Keypad (P0.05)
1: AI1
2: AI2
3: Multi-step setting
4: Communication
PD.09
Auto current limiting selection
0: Enabled
1: Disabled when constant speed
PE Group: Factory Setting
PE.00 Factory password 0~65535
Factory
Setting
Modify
Serial
No.
5000 O 151
12.5Hz
0
0
0
0
0
0
*****
O
O
O
O
O
O
●
152
153
154
155
156
157
158
159
Special parameter for CHE150 series high speed inverter is as follow:
Function
Code
Name Description
Factory
Setting
P0 Group: Basic Function
Modify
P0.04 Maximum frequency
P0.05
P0.07
Upper frequency limit
Keypad reference frequency
P4 Group: V/F Control
10.00~1500.0Hz
P0.06~ P0.04
0.00 Hz ~ P0.04
1000.0Hz
1000.0Hz
1000.0Hz
O
O
100
List of Function Parameters
Function
Code
Name Description
Factory
Setting
Modify
P4.00
P4.03
V/F curve selection
0:Linear curve
1: User-defined curve
2: Torque_stepdown curve (1.3 order)
3: Torque_stepdown curve (1.7 order)
4: Torque_stepdown curve (2.0 order)
V/F frequency 1 0.0Hz ~ P4.05
0
100.0Hz
O
P4.04
P4.05
P4.06
P4.07
V/F voltage 1
V/F frequency 2
V/F voltage 2
V/F frequency 3
0.0% ~ 100.0% (motor rated voltage)
P4.03 ~ P4.07
0.0% ~ 100.0% (motor rated voltage)
P4.05 ~ P2.02 (motor rated frequency)
10.0%
600.0Hz
60.0%
1000.0Hz
100.0% P4.08 V/F voltage 3 0.0% ~ 100.0% (motor rated voltage)
P4.09
P4.10
V/F Slip compensation limit
Auto energy saving selection
0: Disabled
1: Enabled
0.00~200.0%
Parameters display on LCD keypad
Function Code Name
P0.00
P0.01
P0.02
P0.03
P0.04
P0.05
P0.06
P0.07
P0.08
P0.09
P0.10
P0.11
Control mode selection
Run command source
UP/DOWN setting
Frequency A command source
Maximum frequency
Upper frequency limit
Lower frequency limit
Keypad reference frequency
Acceleration time 0
Deceleration time 0
Running direction selection
Carrier frequency
101
0.0%
0
LCD Display
CONTROL MODE
RUN COMMAND
UP/DOWN SETTING
FREQ SOURCE A
MAX FREQ
UP FREQ LIMIT
LOW FREQ LIMIT
KEYPAD REF FREQ
ACC TIME 0
DEC TIME 0
RUN DIRECTION
CARRIER FREQ
O
O
O
Function Code
P2.01
P2.02
P2.03
P2.04
P2.05
P2.06
P2.07
P2.08
P2.09
P2.10
P3.00
P3.01
P1.06
P1.07
P1.08
P1.09
P1.10
P1.11
P1.12
P2.00
P0.12
P0.13
P0.14
P1.00
P1.01
P1.02
P1.03
P1.04
P1.05
List of Function Parameters
Name
Motor parameters autotuning
Restore parameters
AVR function
Start Mode
Starting frequency
Hold time of starting frequency
DC Braking current before start
DC Braking time before start
Stop mode
Starting frequency of DC braking
Waiting time before DC braking
DC braking current
DC braking time
Dead time of FWD/REV
FWD/REV enable when power on
Reserved
G/P option
Motor rated power
Motor rated frequency
Motor rated speed
Motor rated voltage
Motor rated current
Motor stator resistance
Motor rotor resistance
Motor leakage inductance
Motor mutual inductance
Current without load
ASR proportional gain Kp1
ASR integral time Ki1
102
LCD Display
AUTOTUNING
RESTORE PARA
AVR
START MODE
START FREQ
HOLD TIME
START BRAK CURR
START BRAK TIME
STOP MODE
STOP BRAK FREQ
STOP BRAK DELAY
STOP BRAK CURR
STOP BRAK TIME
FWD/REV DEADTIME
FWD/REV ENABLE
RESERVED
G/P OPTION
MOTOR RATE POWER
MOTOR RATE FREQ
MOTOR RATE SPEED
MOTOR RATE VOLT
MOTOR RATE CURR
STATOR RESISTOR
ROTOR RESISTOR
LEAK INDUCTOR
MUTUAL INDUCTOR
NO LOAD CURR
ASR Kp1
ASR Ki1
Function Code
P4.02
P4.03
P4.04
P4.05
P5.00
P5.01
P5.02
P5.03
P3.02
P3.03
P3.04
P3.05
P3.06
P3.07
P4.00
P4.01
P5.04
P5.05
P5.06
P5.07
P5.08
P5.09
P5.10
P5.11
P5.12
P5.13
P5.14
P5.15
P5.16
Name
ASR switching point 1
ASR proportional gain Kp2
ASR integral time Ki2
ASR switching point 2
Slip compensation rate of VC
Torque limit
V/F curve selection
Torque boost
Torque boost cut-off
V/F Slip compensation limit
Auto energy saving selection
Reserved
S1 terminal function
S2 terminal function
S3 terminal function
S4 terminal function
ON/OFF filter times
FWD/REV control mode
UP/DOWN setting change rate
AI1 lower limit
AI1 lower limit corresponding setting
AI1 upper limit
AI1 upper limit corresponding setting
AI1 filter time constant
AI2 lower limit
AI2 lower limit corresponding setting
AI2 upper limit
AI2 upper limit corresponding setting
AI2 filter time constant
103
List of Function Parameters
LCD Display
ASR SWITCHPOINT1
ASR Kp2
ASR Ki2
ASR SWITCHPOINT2
VC SLIP COMP
TORQUE LIMIT
V/F CURVE
TORQUE BOOST
BOOST CUT-OFF
SLIP COMP LIMIT
ENERGY SAVING
RESERVED
S1 FUNCTION
S2 FUNCTION
S3 FUNCTION
S4 FUNCTION
Sx FILTER TIMES
FWD/REV CONTROL
UP/DOWN RATE
AI1 LOW LIMIT
AI1 LOW SETTING
AI1 UP LIMIT
AI1 UP SETTING
AI1 FILTER TIME
AI2 LOW LIMIT
AI2 LOW SETTING
AI2 UP LIMIT
AI2 UP SETTING
AI2 FILTER TIME
List of Function Parameters
Function Code
P7.07
P7.08
P7.09
P7.10
P7.11
P7.02
P7.03
P7.04
P7.05
P7.06
P6.00
P6.01
P6.02
P6.03
P6.04
P6.05
P6.06
P7.00
P7.01
P7.17
P7.18
P7.19
P8.00
P8.01
P7.12
P7.13
P7.14
P7.15
P7.16
Name
Y output selection
Relay output selection
AO selection
AO lower limit
AO lower limit corresponding output
AO upper limit
AO upper limit corresponding output
User password
LCD language selection
Parameter copy
QUICK/JOG function selection
STOP/RST function option
Keypad display selection
Running status display selection
Stop status display selection
Rectifier module temperature
IGBT module temperature
Software version
Accumulated running time
Third latest fault type
Second latest fault type
Current fault type
Output frequency at current fault
Output current at current fault
DC bus voltage at current fault
Input terminal status at current fault
Output terminal status at current fault
Acceleration time 1
Deceleration time 1
104
LCD Display
Y SELECTION
RO SELECTION
AO SELECTION
AO LOW LIMIT
AO LOW OUTPUT
AO UP LIMIT
AO UP OUTPUT
USER PASSWORD
LANGUAGE SELECT
PARA COPY
QUICK/JOG FUNC
STOP/RST FUNC
KEYPAD DISPLAY
RUNNING DISPLAY
STOP DISPLAY
RECTIFIER TEMP
IGBT TEMP
SOFTWARE VERSION
TOTAL RUN TIME
3rd LATEST FAULT
2nd LATEST FAULT
CURRENT FAULT
FAULT FREQ
FAULT CURR
FAULT DC VOLT
FAULT Sx STATUS
FAULT DO STATUS
ACC TIME 1
DEC TIME 1
Function Code
P8.11
P8.12
P8.13
P8.14
P8.15
P8.16
P8.17
P9.00
P8.02
P8.03
P8.04
P8.05
P8.06
P8.07
P8.08
P8.09
P8.10
P9.01
P9.02
P9.03
P9.04
P9.05
P9.06
P9.07
P9.08
P9.09
P9.10
PA.00
List of Function Parameters
Name
Jog reference
Jog acceleration time
Jog deceleration time
Skip frequency
Skip frequency bandwidth
Traverse amplitude
Jitter frequency
Rise time of traverse
Fall time of traverse
Auto reset times
Reset interval
FDT level
FDT lag
Frequency arrive detecting range
Brake threshold voltage
Coefficient of rotation speed
PID preset source selection
Keypad PID preset
PID feedback source selection
PID output characteristics
Proportional gain (Kp)
Integral time (Ti)
Differential time (Td)
Sampling cycle (T)
Bias limit
Feedback lost detecting value
Feedback lost detecting time
Multi-step speed 0
LCD Display
JOG REF
JOG ACC TIME
JOG DEC TIME
SKIP FREQ
SKIP FREQ RANGE
TRAV AMPLITUDE
JITTER FREQ
TRAV RISE TIME
TRAV FALL TIME
AUTO RESET TIMES
RESET INTERVAL
FDT LEVEL
FDT LAG
FAR RANGE
BRAK VOLT
SPEED RATIO
PID PRESET
KEYPAD PID SET
PID FEEDBACK
PID OUTPUT
PROPORTION GAIN
INTEGRAL TIME
DIFFERENTIA TIME
SAMPLING CYCLE
BIAS LIMIT
FEEDBACK LOST
FEEDBACK LOST(t)
MULTI-SPEED 0
105
List of Function Parameters
PC.02
PC.03
PC.04
PC.05
PC.06
PB.04
PB.05
PB.06
PB.07
PC.00
PC.01
Function Code
PA.01
PA.07
PB.00
PB.01
PB.02
PB.03
PA.02
PA.03
PA.04
PA.05
PA.06
PD.00
PD.01
PD.02
PD.03
Name
Multi-step speed 1
Multi-step speed 2
Multi-step speed 3
Multi-step speed 4
Multi-step speed 5
Multi-step speed 6
Multi-step speed 7
Motor overload protection
Motor overload protection current
Threshold of trip-free
Decrease rate of trip-free
Over-voltage stall protection
Over-voltage stall protection point
Auto current limiting threshold
Frequency decrease rate when current limiting
Local address
Baud rate selection
Data format
Communication delay time
Communication timeout delay
Communication error action
Response action
Low-frequency threshold of restraining oscillation
High-frequency threshold of restraining oscillation
Amplitude of restraining oscillation
Boundary of restraining oscillation
LCD Display
MULTI-SPEED 1
MULTI-SPEED 2
MULTI-SPEED 3
MULTI-SPEED 4
MULTI-SPEED 5
MULTI-SPEED 6
MULTI-SPEED 7
MOTOR OVERLOAD
OVERLOAD CURR
TRIPFREE POINT
TRIPFREE DECRATE
OVER VOLT STALL
OV PROTECT POINT
CURR LIMIT POINT
FREQ DEC RATE
LOCAL ADDRESS
BAUD RATE
DATA FORMAT
COM DELAY TIME
COM TIMEOUT
COM ERR ACTION
RESPONSE ACTION
RES OSC L POINT
RES OSC H POINT
RES OSC AMP
RES OSC BOUND
106
Function Code
PD.04
PD.05
PD.06
PD.07
PD.08
PD.09
PE.00
List of Function Parameters
Name
Restrain oscillation
PWM mode
Torque setting source
Keypad torque setting
Upper frequency limit selection
Auto current limiting selection
Factory password
LCD Display
RES OSC ENABLE
PWM MODE
TORQ SOURCE
KEYPAD TORQ SET
UP FREQ SOURCE
CURR LIMIT SEL
FACTORY PASSWORD
107
Communication Protocol
10. COMMUNICATION PROTOCOL
10.1 Interfaces
RS485: asynchronous, half-duplex.
Default: 8-E-1, 19200bps. See Group PC parameter settings.
10.2 Communication Modes
10.2.1 The protocol is Modbus protocol. Besides the common register Read/Write operation, it is supplemented with commands of follows: parameters management.
10.2.2 The drive is a slave in the network. It communicates in ‘point to point’ master-slave mode. It will not respond to the command sent by the master via broadcast address.
10.2.3 In the case of multi-drive communication or long-distance transmission, connecting a 100~120 Ω resistor in parallel with the master signal line will help to enhance the immunity to interference.
10.3 Protocol Format
Modbus protocol supports both RTU and ASCII mode. The frame format is illustrated as
Modbus adopts “Big Endian” representation for data frame. This means that when a numerical quantity larger than a byte is transmitted, the most significant byte is sent first.
RTU mode
In RTU mode, the Modbus minimum idle time between frames should be no less than 3.5 bytes. The checksum adopts CRC-16 method. All data except checksum itself sent will be counted into the calculation. Please refer to section: CRC Check for more information.
Note that at least 3.5 bytes of Modbus idle time should be kept and the start and end idle time need not be summed up to it.
The table below shows the data frame of reading parameter 002 from slave node address
1.
108
Communication Protocol
Read No. CRC Node addr. Command Data addr.
The table below shows the reply frame from slave node address 1
Node addr. Command Bytes No.
Data CRC
0x44
ASCII mode
In ASCII mode, the frame head is “0x3A”, and default frame tail is “0x0D” or “0x0A”. The frame tail can also be configured by users. Except frame head and tail, other bytes will be sent as two ASCII characters, first sending higher nibble and then lower nibble. The data have 7/8 bits. “A”~“F” corresponds to the ASCII code of respective capital letter. LRC check is used. LRC is calculated by adding all the successive bytes of the message except the head and tail, discarding any carriers, and then two’s complementing the result.
Example of Modbus data frame in ASCII mode:
The command frame of writing 0x0003 into address “0x1000” of slave node address 1 is shown in the table below:
LRC checksum = the complement of (01+06+10+00+0x00+0x03) = 0xE5
Frame head
Node addr. Command Data addr.
Data to write LRC Frame tail
0 0 0 3 E 5 CR
30 30 30 33 45 35 0D
LF
0A
10.4 Protocol function
Different respond delay can be set through drive’s parameters to adapt to different needs.
For RTU mode, the respond delay should be no less than 3.5 bytes interval, and for
ASCII mode, no less than 1ms.
The main function of Modbus is to read and write parameters. The Modbus protocol supports the following commands:
0x03 Read inverter’s function parameter and status parameters
0x06 Write single function parameter or command parameter to inverter
All drive’s function parameters, control and status parameters are mapped to Modbus
R/W data address.
The data addresses of each function parameters please refer the sixth column of chapter
9.
109
Communication Protocol
The data address of control and status parameters please refer to the following table.
Parameter
Description
Address Meaning of value
R/W
Feature
Control command
Inverter status
Communication setting
1000H
1001H
2000H
0001H: Forward
0002H: Reverse
0003H: JOG forward
0004H: JOG reverse
0005H: Stop
0006H: Coast to stop
0007H: Reset fault
0008H: JOG stop
0001H: Forward running
0002H: Reverse running
0003H: Standby
0004H: Fault
Communication Setting Range
(-10000~10000)
Note: the communication setting is the percentage of the relative value
(-100.00%~100.00%). If it is set as frequency source, the value is the percentage of the maximum frequency
(P0.04). If it is set as PID (preset value or feedback value), the value is the percentage of the PID.
W/R
R
W/R
Status parameters
3002H
3008H
3009H
300AH
300BH
300CH
300DH
DC Bus voltage
PID preset value
PID feedback value
Input terminal status
Output terminal status.
Input of AI1
Input of AI2
300EH Reserved
300FH Reserved
3011H Reserved
3012H Step No. of PLC or multi-step
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
110
Communication Protocol
3015H Reserved
R
R
R
R
Fault info address
ModBus communication fault info address
5000H
5001H
This address stores the fault type of inverter. The meaning of each value is same as P7.15.
0000H: No fault
0001H: Wrong password
0002H: Command code error
0003H: CRC error
0004H: Invalid address
0005H: Invalid data
0006H: Parameter change invalid
0007H: System locked
0008H: Busy (EEPROM is storing)
R
R
The above shows the format of the frame. Now we will introduce the Modbus command and data structure in details, which is called protocol data unit for simplicity. Also MSB stands for the most significant byte and LSB stands for the least significant byte for the same reason. The description below is data format in RTU mode. The length of data unit in ASCII mode should be doubled.
Protocol data unit format of reading parameters:
Request format:
Protocol data unit Data length(bytes)
Command 1
Data Address 2
Read number 2
Range
0x03
0~0xFFFF
0x0001~0x0010
Reply format (success):
Protocol data unit Data length(bytes)
Command 1
Range
0x03
Returned byte number 2 2* Read number
Content 2* Read number
If the command is reading the type of inverter (data address 0x3016), the content value in reply message is the device code:
The high 8 bit of device code is the type of the inverter, and the low 8 bit of device code is the sub type of inverter.
111
Communication Protocol
For details, please refer to the following table:
High byte Meaning Low byte Meaning
00 CHV 03
04
Middle frequency
1500HZ
Middle frequency
3000HZ
01 CHE
02
Middle frequency
1500HZ
02 CHF 01
If the operation fails, the inverter will reply a message formed by failure command and error code. The failure command is (Command + 0x80). The error code indicates the reason of the error; see the table below.
Value Name
01H
02H
Illegal command
Illegal data address.
Mean
The command from master can not be executed. The reason maybe:
1. This command is only for new version and this version can not realize.
2. Slave is in fault status and can not execute it.
Some of the operation addresses are invalid or not allowed to access.
When there are invalid data in the message framed received by slave.
06H
10H write exceed the range, but indicate the message frame is a illegal frame.
Slave busy Inverter is busy(EEPROM is storing)
Password error
The password written to the password check address is not same as the password set by P7.00.
12H
13H
Written not allowed.
System locked
It only happen in write command, the reason maybe:
1. the data to write exceed the range of according parameter
2. The parameter should not be modified now.
3. The terminal has already been used.
When password protection take effect and user does not unlock it, write/read the function parameter will return this error.
Protocol data unit format of writing single parameter:
112
Communication Protocol
Request format:
Protocol data unit Data length(bytes)
Command 1
Data Address
Write Content
2
2
Reply format (success):
Protocol data unit Data length(bytes)
Command 1
Data Address
Write Content
2
2
Range
0x06
0~0xFFFF
0~0xFFFF
Range
0x06
0~0xFFFF
0~0xFFFF
If the operation fails, the inverter will reply a message formed by failure command and error code. The failure command is (Command + 0x80). The error code indicates the reason of the error; see table 1.
10.5 Note:
10.5.1 Between frames, the span should not less than 3.5 bytes interval, otherwise, the message will be discarded.
10.5.2 Be cautious to modify the parameters of PC group through communication, otherwise may cause the communication interrupted.
10.5.3 In the same frame, if the span between two .near bytes more than 1.5 bytes interval, the behind bytes will be assumed as the start of next message so that communication will failure.
10.6 CRC Check
For higher speed, CRC-16 uses tables. The following are C language source code for
CRC-16. unsigned int crc_cal_value(unsigned char *data_value,unsigned char data_length)
{ int i; unsigned int crc_value=0xffff; while(data_length--)
{ crc_value^=*data_value++; for(i=0;i<8;i++)
{ if(crc_value&0x0001)crc_value=(crc_value>>1)^0xa001;
} else crc_value=crc_value>>1;
} return(crc_value);
}
113
Communication Protocol
10.7 Example
10.7.1 RTU mode, read 2 data from 0004H
The request command is:
START T1-T2-T3-T4 (transmission time of 3.5 bytes)
Node address 01H
Command 03H
High byte of start address 00H
Low byte of start address
High byte of data number
Low byte of data number
04H
00H
02H
Low byte of CRC
High byte of CRC
END
85H
CAH
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The reply is :
START
Node address
T1-T2-T3-T4 (transmission time of 3.5 bytes)
01H
Command 03H
Returned byte number 04H
Higher byte of 0004H
Low byte of 0004H
High byte of 0005H
00H
00H
00H
Low byte of 0005H
Low byte of CRC
High byte of CRC
END
00H
43H
07H
T1-T2-T3-T4 (transmission time of 3.5 bytes)
114
Communication Protocol
10.7.2 ASCII mode, read 2 data from 0004H:
The request command is:
START ‘:’
Node address
‘0’
‘1’
Command
‘0’
‘3’
High byte of start address
Low byte of start address
‘0’
‘0’
‘0’
High byte of data number
Low byte of data number
‘4’
‘0’
‘0’
‘0’
LRC CHK Hi
LRC CHK Lo
END Lo
END Hi
‘2’
‘F’
‘6’
CR
LF
The reply is
START ‘:’
Node address
Command
‘0’
‘1’
‘0’
Returned byte number
‘3’
‘0’
‘4’
Higher byte of 0004H
Low byte of 0004H
‘0’
‘0’
‘0’
High byte of 0005H
Low byte of 0005H
‘0’
‘0’
‘0’
‘0’
‘0’
LRC CHK Lo
LRC CHK Hi
END Lo
END Hi
‘F’
‘8’
CR
LF
115
Communication Protocol
10.7.3 RTU mode, write 5000(1388H) into address 0008H, slave node address 02.
The request command is:
START
Node address
T1-T2-T3-T4 (transmission time of 3.5 bytes)
02H
Command 06H
High byte of data address
Low byte of data address
High byte of write content
00H
08H
13H
Low byte of write content
Low byte of CRC
High byte of CRC
END
The reply command is:
START
Node address
88H
05H
6DH
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 (transmission time of 3.5 bytes)
02H
Command 06H
High byte of data address 00H
Low byte of data address
High byte of write content
Low byte of write content
Low byte of CRC
High byte of CRC
END
08H
13H
88H
05H
6DH
T1-T2-T3-T4 (transmission time of 3.5 bytes)
116
Communication Protocol
10.7.4 ASCII mode, write 5000(1388H) into address 0008H, slave node address 02.
The request command is:
START
Node address
Command
High byte of data address
Low byte of data address
High byte of write content
Low byte of write content
LRC CHK Hi
LRC CHK Lo
END Lo
END Hi
‘8’
‘5’
‘5’
‘1’
‘3’
‘8’
CR
LF
‘6’
‘0’
‘0’
‘0’
‘8’
‘:’
‘0’
‘2’
‘0’
The reply command is:
START
Node address
Command
High byte of data address
Low byte of data address
High byte of write content
Low byte of write content
LRC CHK Hi
LRC CHK Lo
END Lo
END Hi
‘8’
‘5’
‘5’
‘1’
‘3’
‘8’
CR
LF
‘6’
‘0’
‘0’
‘0’
‘8’
‘:’
‘0’
‘2’
‘0’
117