Cat. No. I546-E1-02
0675398-6B
SETUP MANUAL
SYSDRIVE 3G3JV
Compact Simplified Inverters
Thank you for choosing this SYSDRIVE 3G3JV-series product. Proper use and handling of the product will ensure proper product performance, will lengthen product life, and may prevent possible accidents.
Please read this manual thoroughly and handle and operate the product with care.
1. To ensure safe and proper use of the OMRON Inverters, please read this SETUP
MANUAL and the USER’S MANUAL (Cat. No. I528-E1) to gain sufficient knowledge of the devices, safety information, and precautions before actual use.
2. The products are illustrated without covers and shieldings for closer look in this SET-
UP MANUAL and the USER’S MANUAL. For actual use of the products, make sure to use the covers and shieldings as specified.
3. This SETUP MANUAL and other related user’s manuals are to be delivered to the actual end users of the products.
4. Please keep this manual close at hand for future reference.
5. If the product has been left unused for a long time, please inquire at our sales representative.
NOTICE
1. This manual describes the functions of the product and relations with other products. You should assume that anything not described in this manual is not possible.
2. Although care has been given in documenting the product, please contact your
OMRON representative if you have any suggestions on improving this manual.
3. The product contains potentially dangerous parts under the cover. Do not attempt to open the cover under any circumstances. Doing so may result in injury or death and may damage the product. Never attempt to repair or disassemble the product.
4. We recommend that you add the following precautions to any instruction manuals you prepare for the system into which the product is being installed.
S
Precautions on the dangers of high-voltage equipment.
S
Precautions on touching the terminals of the product even after power has been turned OFF. (These terminals are live even with the power turned OFF.)
5. Specifications and functions may be changed without notice in order to improve product performance.
Items to Check Before Unpacking
Check the following items before removing the product from the package:
S
Has the correct product been delivered (i.e., the correct model number and specifications)?
S
Has the product been damaged in shipping?
S
Are any screws or bolts loose?
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Additionally, there may be severe property damage.
!
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Additionally, there may be severe property damage.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
OMRON, 2005
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because
OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
WARRANTY
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á a period of one year (or other period if specified) from date of sale by OMRON.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
Á
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
LIMITATIONS OF LIABILITY
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
STRICT LIABILITY.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á which liability is asserted.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
Á
REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Application Considerations
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SUITABILITY FOR USE
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ the combination of products in the customer’s application or use of the products.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
At the customer’s request, OMRON will provide applicable third party certification documents identifying
Á ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á complete determination of the suitability of the products in combination with the end product, machine,
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á system, or other application or use.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
The following are some examples of applications for which particular attention must be given. This is not
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á uses listed may be suitable for the products:
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á or uses not described in this manual.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á •
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á industry or government regulations.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
•
Systems, machines, and equipment that could present a risk to life or property.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
Please know and observe all prohibitions of use applicable to the products.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
Á
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ OMRON shall not be responsible for the user’s programming of a programmable product, or any
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á consequence thereof.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Disclaimers
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
CHANGE IN SPECIFICATIONS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
Product specifications and accessories may be changed at any time based on improvements and other
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ reasons.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á changed without any notice. When in doubt, special model numbers may be assigned to fix or establish
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á key specifications for your application on your request. Please consult with your OMRON representative
Á ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á at any time to confirm actual specifications of purchased products.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
DIMENSIONS AND WEIGHTS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
Á
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PERFORMANCE DATA
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
Performance data given in this manual is provided as a guide for the user in determining suitability and
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
Á
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ERRORS AND OMISSIONS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
The information in this manual has been carefully checked and is believed to be accurate; however, no
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ Á
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
General Precautions
Observe the following precautions when using the SYSDRIVE Inverters and peripheral devices.
This manual may include illustrations of the product with protective covers removed in order to describe the components of the product in detail. Make sure that these protective covers are on the product before use.
Consult your OMRON representative when using the product after a long period of storage.
!
WARNING
Do not touch the inside of the Inverter. Doing so may result in electrical shock.
!
WARNING
Operation, maintenance, or inspection must be performed after turning OFF the power supply, confirming that the CHARGE indicator (or status indicators) are OFF, and after waiting for the time specified on the front cover. Not doing so may result in electrical shock.
!
WARNING
Do not damage, pull on, apply stress to, place heavy objects on, or pinch the cables.
Doing so may result in electrical shock.
!
WARNING
Do not touch the rotating parts of the motor under operation. Doing so may result in injury.
!
WARNING
Do not modify the product. Doing so may result in injury or damage to the product.
!
Caution
!
Caution
Do not store, install, or operate the product in the following places. Doing so may result in electrical shock, fire or damage to the product.
S
Locations subject to direct sunlight.
S Locations subject to temperatures or humidity outside the range specified in the specifications.
S
Locations subject to condensation as the result of severe changes in temperature.
S Locations subject to corrosive or flammable gases.
S
Locations subject to exposure to combustibles.
S
Locations subject to dust (especially iron dust) or salts.
S
Locations subject to exposure to water, oil, or chemicals.
S
Locations subject to shock or vibration.
Do not touch the Inverter radiator, regenerative resistor, or Servomotor while the power is being supplied or soon after the power is turned OFF. Doing so may result in a skin burn due to the hot surface.
!
Caution
!
Caution
Do not conduct a dielectric strength test on any part of the Inverter. Doing so may result in damage to the product or malfunction.
Take appropriate and sufficient countermeasures when installing systems in the following locations. Not doing so may result in equipment damage.
S Locations subject to static electricity or other forms of noise.
S
Locations subject to strong electromagnetic fields and magnetic fields.
S
Locations subject to possible exposure to radioactivity.
S
Locations close to power supplies.
Transportation Precautions
!
Caution Do not hold by front cover or panel, instead, hold by the radiation fin (heat sink) while transporting the product. Doing so may result in injury.
!
Caution
!
Caution
Do not pull on the cables. Doing so may result in damage to the product or malfunction.
Use the eye-bolts only for transporting the Inverter. Using them for transporting the machinery may result in injury or malfunction.
Installation Precautions
!
WARNING
Provide an appropriate stopping device on the machine side to secure safety. (A holding brake is not a stopping device for securing safety.) Not doing so may result in injury.
!
WARNING
Provide an external emergency stopping device that allows an instantaneous stop of operation and power interruption. Not doing so may result in injury.
!
Caution
!
Caution
!
Caution
Be sure to install the product in the correct direction and provide specified clearances between the Inverter and control panel or with other devices. Not doing so may result in fire or malfunction.
Do not allow foreign objects to enter inside the product. Doing so may result in fire or malfunction.
Do not apply any strong impact. Doing so may result in damage to the product or malfunction.
Wiring Precautions
!
WARNING
Wiring must be performed only after confirming that the power supply has been turned OFF. Not doing so may result in electrical shock.
!
WARNING
Wiring must be performed by authorized personnel. Not doing so may result in electrical shock or fire.
!
WARNING
Be sure to confirm operation only after wiring the emergency stop circuit. Not doing so may result in injury.
!
WARNING
Always connect the ground terminals to a ground of 100
Ω
or less. Not connecting to a proper ground may result in electrical shock.
!
Caution
!
Caution
!
Caution
!
Caution
!
Caution
!
Caution
!
Caution
Install external breakers and take other safety measures against short-circuiting in external wiring. Not doing so may result in fire.
Confirm that the rated input voltage of the Inverter is the same as the AC power supply voltage. An incorrect power supply may result in fire, injury, or malfunction.
Connect the Braking Resistor and Braking Resistor Unit as specified in the manual.
Not doing so may result in fire.
Be sure to wire correctly and securely. Not doing so may result in injury or damage to the product.
Be sure to firmly tighten the screws on the terminal block. Not doing so may result in fire, injury, or damage to the product.
Do not connect an AC power to the U, V, or W output. Doing so may result in damage to the product or malfunction.
Set the multi-function contact input parameter for NC contact terminals (e.g., 3-wire sequence) before wiring them. If the parameter’s default setting is used, the motor may start running when the input terminal S2 is turned ON.
Operation and Adjustment Precautions
!
WARNING
Turn ON the input power supply only after mounting the front cover, terminal covers, bottom cover, Operator, and optional items. Not doing so may result in electrical shock.
!
WARNING
Do not remove the front cover, terminal covers, bottom cover, Operator, or optional items while the power is being supplied. Doing so may result in electrical shock or damage to the product.
!
WARNING
Do not operate the Operator or switches with wet hands. Doing so may result in electrical shock.
!
WARNING
Do not touch the inside of the Inverter. Doing so may result in electrical shock.
!
WARNING
Do not come close to the machine when using the error retry function because the machine may abruptly start when stopped by an alarm. Doing so may result in injury.
!
WARNING
Do not come close to the machine immediately after resetting momentary power interruption to avoid an unexpected restart (if operation is set to be continued in the processing selection function after momentary power interruption is reset). Doing so may result in injury.
!
WARNING
Provide a separate emergency stop switch because the STOP Key on the Operator is valid only when function settings are performed. Not doing so may result in injury.
!
WARNING
Be sure to confirm that the RUN signal is turned OFF before turning ON the power supply, resetting the alarm, or switching the LOCAL/REMOTE selector. Doing so while the RUN signal is turned ON may result in injury.
!
Caution
!
Caution
!
Caution
!
Caution
Be sure to confirm permissible ranges of motors and machines before operation because the Inverter speed can be easily changed from low to high. Not doing so may result in damage to the product.
Provide a separate holding brake when necessary. Not doing so may result in injury.
Do not perform a signal check during operation. Doing so may result in injury or damage to the product.
Do not carelessly change settings. Doing so may result in injury or damage to the product.
Maintenance and Inspection Precautions
!
WARNING
Do not touch the Inverter terminals while the power is being supplied.
!
WARNING
Maintenance or inspection must be performed only after turning OFF the power supply, confirming that the CHARGE indicator (or status indicators) is turned OFF, and after waiting for the time specified on the front cover. Not doing so may result in electrical shock.
!
WARNING
Maintenance, inspection, or parts replacement must be performed by authorized personnel. Not doing so may result in electrical shock or injury.
!
WARNING
Do not attempt to take the Unit apart or repair. Doing either of these may result in electrical shock or injury.
!
Caution
!
Caution
Carefully handle the Inverter because it uses semiconductor elements. Careless handling may result in malfunction.
Do not change wiring, disconnect connectors, the Operator, or optional items, or replace fans while power is being supplied. Doing so may result in injury, damage to the product, or malfunction.
Warnings for UL/cUL Marking
• Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
•
The Inverter internal capacitor is still charged even after the power supply is turned OFF. To prevent electrical shock, disconnect all power before servicing the Inverter. Then wait at least one minute after the power supply is disconnected and all indicators are OFF.
•
Do not perform a withstand voltage test on any part of the Inverter. This electronic equipment uses semiconductors and is vulnerable to high voltage.
•
Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF. Never touch the printed control board (PCB) while the power supply is turned ON.
•
The Inverter is not suitable for use on a circuit capable of delivering more than 5,000 RMS symmetrical amperes, 250 volts maximum (100-V-class Units).
•
Take measures against overcurrent, overload, and overheating by using the Motor Protection Settings.
CAUTION
Use 75
°
C copper wires or equivalent.
Low voltage wires shall be wired with Class I Wiring.
H
Motor Protection Settings
Rated Motor Current (n32)
•
Set the rated motor current (n32) in order to prevent the motor from burning due to overloading.
•
Check the rated current on the motor nameplate and set the parameter.
•
This parameter is used for the electronic thermal function for motor overload detection (OL1). By setting the correct parameter, the overloaded motor will be protected from burning.
n32 Rated Motor Current No
Setting range
0.0% to 120% (A) of rated output current of Inverter
Unit of setting
0.1 A
Changes during operation
Default setting (see note 1)
Note 1.
The standard rated current of the maximum applicable motor is the default rated motor current.
Note 2.
Motor overload detection (OL1) is disabled by setting the parameter to 0.0.
Motor Protection Characteristics (n33 and n34)
•
This parameters setting is for motor overload detection (OL1).
n33 Motor Protection Characteristic Selection
Setting range
0 to 2 Unit of setting
1
Changes during operation
Default setting
No
0
0
1
2
D
Set Values
Value Description
Protection characteristics for general-purpose induction motors
Protection characteristics for Inverter-dedicated motors
No protection
•
This parameter is used to set the electric thermal characteristics of the motor to be connected.
•
Set the parameter according to the motor.
•
If a single Inverter is connected to more than one motor, set the parameter to 2 for no protection. The parameter is also disabled by setting n32 for rated motor current to 0.0. Provide thermal relays or other methods separately for each motor to protect equipment from overloads.
n34 Motor Protection Time No
Setting range
1 to 60 (min) Unit of setting
1 min
Changes during operation
Default setting 8
D
Set Values
•
This parameter is used to set the electronic thermal protection constant of motor overload detection
OL1.
•
The default setting does not need any changes in normal operation.
•
To set the parameter according to the characteristics of the motor, confirm the thermal time constant with the motor manufacturer and set the parameter with some margin. In other words, set the value a little shorter than the thermal time constant.
•
To detect motor overloading more quickly, reduce the set value, provided that it does not cause any application problems.
Checking Before Unpacking
H
Checking the Product
On delivery, always check that the delivered product is the SYSDRIVE 3G3JV Inverter that you ordered.
Should you find any problems with the product, immediately contact your nearest local sales representative.
D
Checking the Nameplate
Inverter model
Input specifications
Output specifications
3G3JV-A1001
AC3PH 100-115V 3.2A
D
Checking the Model
3G3JV-A1001
Maximum applicable motor capacity
Voltage class
Installation type
Series name: 3G3JV Series
Maximum Applicable Motor Capacity
001 0.1 (0.1) kW
002 0.25/0.37 (0.2) kW
Note
The figures in parentheses indicate capacities for motors used outside Japan.
Voltage Class
1 Single-phase 100-V AC input (100-V class)
Note
The output is 3-phase 200 V AC.
Installation Type
A Panel-mounting models (IP10 min.) or
Closed wall mounting
D
Checking for Damage
Check the overall appearance and check for damage or scratches resulting from transportation.
H
Checking the Accessories
This manual is the only accessory provided with the 3G3JV. Set screws and other necessary parts must be provided by the user.
Table of Contents
Chapter 1. Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-2 Removing and Mounting the Covers
1-2 Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-1 Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 Standard Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-6
1-10
1-2-3 Wiring around the Main Circuit
1-2-4 Optional Accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-11
1-12
1-2
1-2
1-4
1-6
1-3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Chapter 2. Preparing for Operation and Monitoring . . . . . . . . . . . . . 2-1
2-1 Using the Digital Operator
2-1-1 Nomenclature
2-1-2 Accepting Operation Commands While Changing Parameters
2-1-3 Outline of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Copying and Verifying Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Parameters Used to Copy and Verify Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Outline of Copying Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-3 Procedures
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-4 Error Messages for Copying and Verifying Parameters . . . . . . . . . . . . . . . . . . . . . . . .
2-2
2-2
2-4
2-5
2-7
2-7
2-9
2-10
2-12
Chapter 3. List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Chapter 4. Maintenance Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4-1 Protective and Diagnostic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Fault Detection (Fatal Error) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
4-2
4-1-2 Warning Detection (Nonfatal Error) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
4-10
Design
1-1 Installation
1-2 Wiring
1-3 Specifications
1
Chapter 1
Design
1-1 Installation
1-1-1 Dimensions
D
3G3JV-A1001, -A1002 (0.1 to 0.2 kW) Single-phase 100-V AC Input
Chapter 1 t
Model 3G3JV-
A1001
A1002
80
112
Dimensions (mm)
D t
3
5
Approx. 0.5
Approx. 0.8
H
Installation Direction and Dimensions
•
Install the Inverter under the following conditions.
Ambient temperature for operation (panel-mounting): –10
°
C to 50
°
C
Humidity: 95% or less (no condensation)
•
Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it in a totally enclosed panel that is completely protected from floating dust.
•
When installing or operating the Inverter, always take special care so that metal powder, oil, water, or other foreign matter does not get into the Inverter.
• Do not install the Inverter on inflammable material such as wood.
H
Direction
•
Install the Inverter on a vertical surface so that the characters on the nameplate are oriented upward.
1-2
Design Chapter 1
H
Dimensions
•
When installing the Inverter, always provide the following clearances to allow normal heat dissipation from the Inverter.
W = 30 mm min.
100 mm min.
Air
Inverter Inverter Inverter Side
100 mm min.
Air
H
Ambient Temperature Control
•
To enhance operation reliability, the Inverter should be installed in an environment free from extreme temperature changes.
•
If the Inverter is installed in an enclosed environment such as a box, use a cooling fan or air conditioner to maintain the internal air temperature below 50
°
C.
The life of the built-in electrolytic capacitors of the Inverter is prolonged by maintaining the internal air temperature as low as possible.
•
The surface temperature of the Inverter may rise approximately 30
°
C higher than the ambient temperature. Be sure to keep away equipment and wires from the Inverter as far as possible if the equipment and wires are easily influenced by heat.
H
Protecting Inverter from Foreign Matter during Installation
•
Place a cover over the Inverter during installation to shield it from metal power produced by drilling.
Upon completion of installation, always remove the cover from the Inverter. Otherwise, ventilation will be affected, causing the Inverter to overheat.
1-3
Design
1-1-2 Removing and Mounting the Covers
Chapter 1
It is necessary to remove the front cover, optional cover, top protection cover, and the bottom protection cover from the Inverter to wire the terminal block.
Follow the instructions below to remove the covers from the Inverter.
To mount the covers, take the opposite steps.
H
Removing the Front Cover
• Loosen the front cover mounting screws with a screwdriver.
• Press the left and right sides of the front cover in the arrow 1 directions and lift the bottom of the cover in the arrow 2 direction to remove the front cover as shown in the following illustration.
H
Removing the Top and Bottom Protection Covers and Optional Cover
D
Removing the Top and Bottom Protection Covers
•
After removing the front cover, pull the top and bottom protection covers in the arrow 1 directions.
1-4
Design Chapter 1
D
Removing the Optional Cover
•
After removing the front cover, lift the optional cover in the arrow 2 direction based on position A as a fulcrum.
Note The front cover functions as a terminal cover. The Digital Operator cannot be removed.
1-5
Design
1-2 Wiring
Chapter 1
1-2-1 Terminal Block
Before wiring the terminal block, be sure to remove the front cover, top protection cover, and the bottom protection cover.
H
Position of Terminal Block
Ground terminal
Main circuit input terminals
Control circuit terminals
Main circuit output terminals
H
Arrangement of Control Circuit Terminals
Ground terminal
1-6
Design
H
Arrangement of Main Circuit Terminals
D
3G3JV-A1001, -A1002
Main Circuit Input Terminals
(Upper Side)
Chapter 1
Main Circuit Output Terminals
(Lower Side)
H
Main Circuit Terminals
Symbol
R/L1
Name
S/L2 t i l
U/T1
V/T2
W/T3
Ground terminal
Description
3G3JV-A1 j : Single-phase 100 to 115 V AC
Note Connect single-phase input to terminals R/L1 and S/L2.
3G3JV-A1 j : 3-phase 200 to 230 V AC
Be sure to ground the terminal under the following conditions.
3G3JV-A1 j
: Ground at a resistance of 100
Ω
or less, and connect to the power supply’s neutral phase to conform to EC Directives.
Note Be sure to connect the ground terminal directly to the motor frame ground.
Note The maximum output voltage corresponds to the power supply input voltage of the Inverter.
1-7
Design Chapter 1
H
Control Circuit Terminals
Input
Symbol
S1
Output
S2
S3
S4
S5
SC
FS
FR
FC
MA
MB
MC
AM
AC
Multi-function input 1
(S2)
Multi-function input 2
(S3)
Multi-function input 3
(S4)
Name
Forward/Stop
Function
Forward at ON. Stops at
OFF.
Set by parameter n36
(Reverse/Stop)
Set by parameter n37
(Fault reset)
Set by parameter n38
(External fault: Normally open)
Multi-function input 4
(S5)
Sequence input common
Set by parameter n39
(Multi-step reference 1)
Common for S1 through
S5
Frequency reference power supply
Frequency reference input
Frequency reference common
Multi-function contact output (Normally open)
Multi-function contact output (Normally closed)
(
DC power supply for frequency reference use
Input terminal for frequency reference use
Common for frequency reference use
Set by parameter n40 g g)
Multi-function contact output common
Common for MA and
MB use
Analog monitor output Set by parameter n44
(Output frequency)
Analog monitor output common
Common for AM use
Signal level
Photocoupler
8 mA at 24 V DC
Note NPN is the default setting for these terminals. Wire th b idi common ground. No required. To provide an external power supply and i i li however, set the SW7 to the power supply is at
24 V DC ± 10%.
20 mA at 12 V DC
0 to 10 V DC
( p p 0
Ω
)
Relay output
1 A max. at 250 V AC
2 mA max. at 0 to 10 V DC
Note 1.
Depending on the parameter settings, various functions can be selected for multi-function inputs and multi-function contacts outputs.
Note 2.
Functions in parentheses are default settings.
H
Selecting Input Method
•
Switches SW7 and SW8, both of which are located above the control circuit terminals, are used for input method selection.
Remove the front cover and optional cover to use these switches.
Selector
Control circuit terminal block
1-8
Design
D
Selecting Sequence Input Method
•
By using SW7, NPN or PNP input can be selected as shown below.
SW7
Chapter 1
SW7
D
Selecting Frequency Reference Input Method
Frequency reference input method
Voltage input
Current input
V (OFF)
I (ON)
SW8 setting Frequency reference selection
(parameter n03)
Set value 2
Set value 3 or 4
1-9
Design
1-2-2 Standard Connections
DC reactor
(optional)
Noise Filter
Chapter 1
3-phase 200 V AC
Single-phase 100 V AC
Forward/Stop
Multi-function input 1 (Reserve/Stop)
Multi-function input 2 (S3) (Fault Reset)
Multi-function input 3 (S4) (External fault
Normally open)
Multi-function input 4 (S5) (Multi-step speed reference 1)
Sequence input common
FREQ adjuster
Frequency reference power supply 20 mA at +12 V
Frequency reference input
Frequency reference common
(2 k Ω , 1/4 W min.)
Multi-function contact output
NO
NC
Common
Analog monitor output
Analog monitor output common
Note 1.
The braking resistor cannot be connected because no braking transistor is incorporated.
Note 2.
A DC Reactor can be connected in series between the R input and L1 terminal or between the
S input and L2 terminal to use it as an AC reactor.
D
DC Reactor Wiring Example
Noise Filter
DC Reactor
Single-phase 100 V AC
Applicable Noise Filters
3G3JV-A1001
Inverter
3G3JV-A1002
Applicable DC Reactors
3G3JV-A1001
Inverter
3G3JV-A1002
1-10
Applicable Filter
3G3JV-PRS1010J
(f i h 0 1 kW 0 2 kW)
Applicable Reactor
3G3HV-PUZDAB5.4A8MH
3G3HV-PUZDAB18A3MH
Specifications
Specifications
5.4 A, 8 mH
18 A, 3 mH
Design Chapter 1
D
Example of 3-wire Sequence Connections
Stop switch
(NC)
RUN switch
(NO)
RUN input (Operates with the stop switch and RUN switch closed.)
Direction switch
Stop input (Stops with the stop switch opened.)
Forward/Stop reference (Forward with the direction switch opened and reverse with the direction switch closed.)
Sequence input common
Note Set parameter n37 for 3-wire sequence input.
1-2-3 Wiring around the Main Circuit
H
Wire Size, Terminal Screw, Screw Tightening Torque, and Molded-case
Circuit Breaker Capacities
•
For the main circuit and ground, always use 600-V polyvinyl chloride (PVC) cables.
•
If any cable is long and may cause voltage drops, increase the wire size according to the cable length.
D
Single-phase 100-V AC Model
Model
3G3JV-
A1001
Terminal symbol
R/L1, S/L2, U/T1, V/T2, W/T3
Terminal screw
M3.5
Screw tightening torque
(N
S m)
Wire size
(mm
0.8 to 1.0
0.75 to 2
2 )
2
Recommended wire size (mm 2 )
A1002 R/L1, S/L2, U/T1, V/T2, W/T3 M3.5
0.8 to 1.0
0.75 to 2 2
H
Wiring
Control Circuit
Terminal symbol
MA, MB, MC M3
Terminal screw
S1 to S5, SC, FS,
FR, FC, AM, AC
M2
Screw tightening torque N
S m (lb
S in)
Wire size mm 2 (AWG)
0.5 to 0.6 (4.4 to 5.3) Stranded wire:
0.5 to 1.25 (20 to 16)
Single wire:
0.5 to 1.25 (20 to 16)
0.22 to 0.25 (2 to 2.2) Stranded wire:
0.5 to 0.75 (20 to 18)
Single wire:
0.5 to 1.25 (20 to 16)
Recommended wire size mm 2 (AWG)
0.75 (18)
0.75 (18)
1-11
Design
1-2-4 Optional Accessories
Option Specifications
N i Fil
For A1001
For A1002
For A1001 DC Reactor
For A1002
DIN Track Mounting Bracket ---
Standard installation
Removable
1 m
3 m
Without adjuster (with case)
Main Unit
Case
Chapter 1
Model
3G3JV-PRS1010J
3G3HV-PUZDAB5, 4A8MH
3G3HV-PUZDAB18A3MH
3G3IV-PEZZ08122A
3G3JV-PSI232J
3G3JV-PSI232JC
3G3IV-PCN126
3G3IV-PCN326
3G3IV-PJVOP146
3G3IV-PJVOP140
3G3IV-PEZZ08386
1-12
Design
1-3 Specifications
Chapter 1
Power
Allowable voltage fluctuation
Allowable frequency fluctuation
–15 to 10%
± 5%
Input current (for rated output) (A) 3.2
Heating radiation (W) 14.6
Weight (kg)
Cooling method
100-V AC Models
0.5
3G3JV-A1001
Natural cooling
6.2
21.1
0.8
3G3JV-A1002
Rated voltage and power supply Single-phase 100 to 115 V AC at 50/60 Hz
Maximum motor capacity (kW)
Rated output capacity (kVA)
0.1
0.3
0.2
0.6
Control characteristics
Rated output current (A)
Rated output voltage (V)
Maximum output frequency
Power supply harmonics countermeasures
Control method
Carrier frequency
Frequency control range i i )
Frequency setting resolution
0.8
1.6
Three-phase 200 to 230 V (Handles twice the input voltage.)
400 Hz (Set in a parameter.)
DC Reactor (optional) can be connected.
Sine wave PWM (V/f control)
2.5 to 10.0 kHz (Switched in steps.)
0.1 to 400 Hz
Digital reference:
±
0.01% (–10 to 50
°
C)
Analog reference:
±
0.5% (25
°
C
±
10
°
C)
Digital reference: 0.1 Hz (less than 100 Hz), 1 Hz (100 Hz or greater)
Analog reference: 0.06 Hz/60 Hz (equivalent to 1/1000)
0.01 Hz (data processing resolution) Output frequency resolution
Overload capacity
External frequency set signal
150% of rated output current for 1 min
Switchable: 0 to 10 V DC (20 k Ω ), 4 to 20 mA (250 Ω ), 0 to
20 mA (250 Ω ), or frequency adjustment
Acceleration/deceleration times 0.0 to 999 s (Acceleration and deceleration times set separately: Switches between 2 settings.)
Braking torque Approx. 20%
Note: A Braking Resistor or Braking Resistor Unit cannot be connected.
Voltage/frequency characteristics User-set V/f pattern
1-13
Design Chapter 1 f
Protective i
100-V AC Models
Motor protection
Instantaneous overcurrent protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power interruption compensation (selection)
Radiation fin overheated
Grounding protection
Charge indicator
EnvironLocation ment
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Insulation resistance
Vibration resistance
Degree of protection
3G3JV-A1001
Protection by electronic thermal
3G3JV-A1002
Stops at approx. 250% of rated output current.
Stops in 1 min at approximately 150% of rated output current.
Stops when main-circuit DC voltage is approximately 410 V.
Stops when main-circuit DC voltage is approximately 160 V.
None (Stops at 15 ms or longer.)
Select between continuing operation if power is restored within approx. 0.5 s or continuing operation regardless of length of interruption.
Detected at 110 ° C ± 10 ° C
Rated output current level protection
CHARGE indicator lights until the main circuit DC voltage reaches 50 V or less.
Indoors (with no corrosive gas, dust, etc.)
–10 to 50 ° C
95% max. (with no condensation)
–20 to 60
°
C
1,000 m max.
5 M
Ω
min. (Do not carry out any insulation resistance or withstand voltage tests.)
9.8 m/s 2 max. between 10 and 20 Hz, 2.0 m/s 2 max. between 20 and 50 Hz
Mounted in a panel (equivalent to IP20)
1-14
Preparing for
Operation and
Monitoring
2-1 Using the Digital Operator
2-2 Copying and Verifying Parameters
2
Chapter 2
Preparing for Operation and Monitoring
2-1 Using the Digital Operator
2-1-1 Nomenclature
Chapter 2
Data display
Keys
Indicators
Setting/Monitor item indicators
Appearance Name
Data display
FREQ adjuster
FREF indicator
FOUT indicator
IOUT indicator
MNTR indicator
F/R indicator
LO/RE indicator
PRGM indicator
Mode Key
Increment Key
FREQ adjuster
Function
Displays relevant data items, such as frequency reference, output frequency, and parameter set values.
Sets the frequency reference within a range between 0 Hz and the maximum frequency.
The frequency reference can be monitored or set while this indicator is lit.
The output frequency of the Inverter can be monitored while this indicator is lit.
The output current of the Inverter can be monitored while this indicator is lit.
The values set in U01 through U10 are monitored while this indicator is lit.
The direction of rotation can be selected while this indicator is lit, when operating the Inverter with the RUN
Key.
The operation of the Inverter through the Digital Operator or according to the parameters set is selectable while this indicator is lit.
Note This status of this indicator can be only monitored while the Inverter is in operation. Any RUN command input is ignored while this indicator is lit.
The parameters in n01 through n79 can be set or monitored while this indicator is lit.
Note While the Inverter is in operation, the parameters can be only monitored and only some parameters can be changed. The RUN command input is ignored while this indicator is lit.
Switches the setting and monitor item indicators in sequence.
Parameter setting being made is canceled if this key is pressed before entering the setting.
Increases multi-function monitor numbers, parameter numbers, and parameter set values.
2-2
Preparing for Operation and Monitoring Chapter 2
Appearance Name
Decrement Key
Enter Key
RUN Key
STOP/RESET Key
Function
Decreases multi-function monitor numbers, parameter numbers, and parameter set values.
Enters multi-function monitor numbers, parameter numbers, and internal data values after they are set or changed.
Starts the Inverter running when the 3G3FV is in operation with the Digital Operator.
Stops the Inverter unless n06 is set to disable the STOP
Key. Functions as a Reset Key when an Inverter error occurs. (See note.)
Note For safety’s reasons, the reset will not work while a RUN command (forward or reverse) is in effect. Wait until the RUN command is OFF before resetting the Inverter.
2-3
Preparing for Operation and Monitoring Chapter 2
2-1-2 Accepting Operation Commands While Changing
Parameters
With the default settings, the Inverter will not accept operation commands when parameter settings are being changed. This functions as a safety measure to prevent the motor from rotating if the operation command is mistakenly set to ON when changing parameters.
Depending on the operating conditions, however, the user may want to have operation commands accepted even while parameters are being changed. In that case, change the following settings.
H
Using the Indicators to Determine When Operation Commands Can Be
Accepted
The indicators on the Digital Operator can be used to determine if operation commands will be accepted or not while changing parameters.
Green: Operation commands will be accepted if the indicator lights green.
Red: Operation commands will not be accepted after the Inverter stops if an indicator lights red.
Therefore, if the indicator lights red when changing parameters or when switching between local and remote operation, operation will continue, but once the Inverter stops, the Inverter will not operate even if the operation command is set to ON again.
The FREF indicator will light when the power supply is turned ON.
Indicator Color Name Acceptance of operation commands
Stopped
Yes
During operation
Yes FREF
FOUT
IOUT
MNTR
F/R
LO/RE
PRGM
Green
Green
Green
Green
Green
Red
Red
Frequency Reference/Monitor
Output Frequency Monitor
Output Current Monitor
Multi–function Monitor
Operator RUN command forward/reverse operation selection
Local/Remote Selection
Parameter Number/Setting
Yes
Note Perform the settings given in the following description to have operation commands accepted while the red indicator is lit (i.e., while changing parameters or switching between local and remote.)
Set n01 (Parameter write–prohibit selection/parameter initialization) to 5.
S
The default value for n01 is 1.
S
Operation commands will not be accepted when n01 itself is being changed.
S
Some parameters cannot be changed during operation. Those parameters cannot be changed during operation even if the setting for n01 is changed.
S
When n01 is changed to 5, an operation command will be accepted even when changing parameters, such as during trial operation. Thoroughly check safety before changing any setting.
2-4
Preparing for Operation and Monitoring
2-1-3 Outline of Operation
Chapter 2
H
Selecting Indicators
Whenever the Mode Key is pressed, an indicator is lit in sequence beginning with the
FREF indicator. The data display indicates the item corresponding to the indicator selected.
The FOUT or IOUT indicator will be lit by turning the Inverter on again if the Inverter is turned off while the FOUT or IOUT indicator is lit. The FREF indicator will be lit by turning the Inverter on again if the Inverter is turned off while an indicator other than the FOUR or
IOUT indicator is lit.
Power On
FREF (Frequency Reference)
Monitors and sets the frequency reference.
FOUT (Output Frequency)
Monitors the output frequency.
Note This indicator will be lit by turning the Inverter on again if the Inverter is turned off while this indicator is lit.
IOUT (Output Current)
Monitors the output current.
Note This indicator will be lit by turning the Inverter on again if the Inverter is turned off while this indicator is lit.
MNTR (Multi-function Monitor)
Monitors the values set in U01 through U10.
F/R (Forward/Reverse Rotation)
Selects the direction of rotation.
LO/RE (Local/Remote)
Selects the operation of the Inverter through the Digital Operator or according to the parameters.
PRGM (Parameter Setting)
Monitors or sets the values in n01 through n79.
The FREF indicator is lit again.
2-5
Preparing for Operation and Monitoring
H
Example of Multi-function Display
Chapter 2
Key sequence Indicator Display Explanation
Power On
Press the Mode Key repeatedly until the MNTR indicator is lit.
U01 will be displayed.
Use the Increment or Decrement Key to select the monitor item to be displayed.
Press the Enter Key so that the data of the selected monitor item will be displayed.
The monitor number display will appear again by pressing the Mode Key.
D
Status Monitor
Item
U01
U02
Display Display unit
Hz Frequency reference
Output frequency Hz
U03
U04
Output current
Output voltage
A
V
U05
U06
DC bus voltage V
---
Function
Monitors the frequency reference. (Same as FREF)
Monitors the output frequency. (Same as FOUT)
Monitors the output current. (Same as IOUT)
Monitors the internal output voltage reference value of the
Inverter.
Monitors the DC voltage of the internal main circuit of the
Inverter.
Shows the ON/OFF status of inputs.
status
U07 ---
: Input ON : No input
Terminal S1: Forward/Stop
Terminal S2: Multi-function input 1 (S2)
Terminal S3: Multi-function input 2 (S3)
Terminal S4: Multi-function input 3 (S4)
Terminal S5: Multi-function input 4 (S5) Not used
Shows the ON/OFF status of outputs.
status
U09 ---
: Closed : Open
Not used
Terminal MA: Multi-function contact output
Displays the latest error.
recent one) )
U10
U15
Software No.
---
Receive data error ---
Error
OMRON use only.
The cause of the receive data error during MEMOBUS communications can be checked. (Same as the contents of communications register number 003DM.)
2-6
Preparing for Operation and Monitoring
2-2 Copying and Verifying Parameters
Chapter 2
The 3G3IV-PJVOP140 and 3G3IV-PJOP146 Digital Operators contain an EEPROM.
All Inverter parameter settings, the Inverter capacity, and the software number are recorded in this EEPROM. The EEPROM can be used to copy parameter settings to other
Inverters.
Parameter settings can be copied between Inverters with the same power supply specifications, but some of the parameter settings are not copied.
2-2-1 Parameters Used to Copy and Verify Parameters
•
The following parameters are used to read, copy (write), and verify parameter settings.
Parameter
No.
(Register No.
(Hex)) n76
(014C)
Name
Parameter copy and verify function n77
(014D)
Parameter read prohibit selection
Description
Selects the function for copying parameters.
rdy: Ready to accept the next command.
rED: Reads the Inverter parameters.
Cpy: Copies the parameter to the Inverter.
vFY: Verifies the Inverter parameters.
vA: Checks the Inverter capacity display.
Sno: Checks the software number.
Selects the copy-prohibit function.
Use this parameter to protect the data in the
EEPROM of the Digital Operator.
0: Read prohibited for Inverter parameters.
(Data cannot be written to EEPROM.)
1: Read possible for Inverter parameters.
(Data can be written to EEPROM.)
Setting range
Setting unit
Default setting
Changes during operation rdy to
Sno
0, 1
---
--rdy
0
No
No
2-7
Preparing for Operation and Monitoring
H
Display Transitions
Reading
Writing
Verifying
Reading finished
Writing finished
Verification finished
OR
OR
OR
Inverter capacity
OR
Software number
OR
Chapter 2
Note The following display is an example of the capacity displayed. The values in parentheses indicate the capacities for European motors.
10.1
Voltage Class
1: Single-phase 100 V
Max. applicable motor capacity
0.1: 0.1 kW (0.1 kW)
0.2: 0.25 kW/0.37 kW (0.2 kW)
Note The values in parentheses indicate Japanese motor capacities.
2-8
Preparing for Operation and Monitoring
2-2-2 Outline of Copying Parameters
(1) Check setting of n01
0: Writing from Digital Operator prohibited.
1: Parameters can be changed (default setting).
(2) Clear prohibition of reading the copy function: n77
This function protects parameters stored in the Digital
Operator.
0: Reading copy function (rEd) prohibited (default setting).
1: Reading copy function (rEd) enabled.
(3) Perform the read operation for the copy function: n76
Read (rEd) the current parameter settings from the Inverter to the EEPROM in the Digital Operator.
(4) Disconnect the Digital Operator and connect it to a different Inverter. Always turn OFF the power supply before connecting or disconnecting the Digital Operator to protect against electric shock and product failure.
(5) Perform the write operation for the copy function: n76
Write (CPy) the current parameter settings from the EE-
PROM in the Digital Operator to the Inverter.
(6) Perform the verify operation for the copy function: n76
Verify (vFy) the current parameter settings between the
EEPROM in the Digital Operator and the Inverter.
Set n01 to 1.
See operation on next page.
Set n77 to 1.
Same basic operation as for n01.
Set n76 to rEd.
Change Inverter connection.
Turn ON power after checking wiring.
Set n76 to CPy.
Set n76 to vFy.
Chapter 2
H
Parameters That Cannot Be Copied
1. Copying is not possible between Inverters with different power supply specifications (e.g., from a
100-V Inverter to a 400-V Inverter).
2. The recorded hold output frequency and the following parameters cannot be copied: n76: Parameter copy and verify function n77: Parameter read prohibit selection n78: Error log n79: Software number
3. The following parameters cannot be copied if the Inverters have different capacities.
n09 to n15: V/f settings n32: Rated motor current n46: Carrier frequency selection
2-9
Preparing for Operation and Monitoring n64: Motor rated slip n65: Motor no-load current
Chapter 2
2-2-3 Procedures
Changing Parameters
The setting of n01 is changed so that n76 and n77 can be displayed.
D
Setting n01 (Parameter Write-prohibit Selection/Parameter Initialization Parameter)
---
Key Indicator Display Description
(Display after the power supply is turned ON.)
Press the Mode Key until the PRGM indicator lights.
Confirm that n01 is displayed on the data display.
Press the Enter Key.
The setting of the specified parameter number will be displayed.
Press the Increment Key until 4 is displayed. (The display will flash.)
After about 1 s
Press the Enter Key to confirm the setting. (The display will stop flashing.)
The display of the parameter number will return in about 1 s.
2-10
Preparing for Operation and Monitoring Chapter 2
Example of Copy Function
H
Verifying Parameters (vFy)
•
The Parameter Copy and Verify Function (n76) can be set to “vFy” to compare the parameter settings in the Digital Operator with those in the Inverter.
D
Verifying Parameters
Key Indicator
---
Display
(After comparison is finished.) or
Description
(Display after the power supply is turned ON.)
Press the Mode Key until the PRGM indicator lights.
Confirm that n01 is displayed on the data display.
Press the Increment/Decrement Key until “n76” is displayed.
Press the Enter Key.
“rdy” will be displayed.
Press the Increment Key until “vFy” is displayed
Press the Enter Key. The parameter settings will be compared and the display will flash.
The parameter number of any parameter that has different settings will be displayed.
Press the Enter Key.
The setting of the parameter in the Inverter will be displayed
(flashing) first.
Press the Enter Key again.
The setting of the parameter in the Digital Operator will be displayed (flashing) next.
Press the Increment Key.
The comparison will be continued.
“End” will be displayed when the comparison has been finished.
Press the Mode Key or Enter Key.
The display of the parameter number will return.
2-11
Preparing for Operation and Monitoring Chapter 2
2-2-4 Error Messages for Copying and Verifying Parameters
The errors that can be displayed when reading, writing, or verifying parameter settings are described in the following table along with corrective actions. All of these error displays will flash on the display.
Display pre rde cse ndt cpe
Name
Protect error
Read error
Description
An attempt was made to read parameter settings when the
Parameter Read Prohibit Selection parameter (n77) was set to 0
(prohibiting reading).
The parameter settings could not be read normally or a low main circuit voltage was detected while reading parameter settings.
Checksum error A checksum error occurred for the parameters recorded in the Digital
Operator.
No data error
Copy source error
No parameters are recorded in the
Digital Operator.
Copying or verifying parameter settings was attempted between
Inverters with different voltage classes.
cye
Ure
Voltage error while copying
Capacity error
A low main circuit voltage was detected while reading parameter settings.
Verification was attempted between
Inverters of different capacities.
ife Communications error
A communications error occurred between the Inverter and Digital
Operator.
Corrective action
Confirm that it is necessary to read the parameter settings. If it is, change the Parameter Read Prohibit
Selection parameter (n77) to 1
(enabling reading).
Check the main circuit voltage and then attempt reading again.
Read the parameter settings again to record them in the Digital Parameter.
Read the parameter settings to record them in the Digital Parameter.
Check the voltage classes. (They must both be the same to copy parameter settings.)
Check the main circuit voltage and then attempt copying again.
Press the Enter Key to continue the comparison.
Press the STOP/RESET Key to cancel the comparison.
Check the connection between the
Inverter and the Digital Operator.
Correct any problems and then repeat the operation.
2-12
List of Parameters
3
Chapter 3
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n01
(0101) n02
(0102)
Name Description Setting range
Parameter writeprohibit selection/ parameter initialization
Operation command selection
Used to prohibit parameters to be written, sets parameters, or change the monitor range of parameters.
Used to initialize parameters to default values.
0: Sets or monitors parameter n01.
Parameters n02 through n79 can be monitored only.
1: Sets or monitors parameters n01 through n79.
5: Operation commands can be accepted at any time (n01 to n79 can be set or referenced). (See note.)
6: Clears the error log.
8: Initializes parameters to default values in 2-wire sequence.
9: Initializes parameters to default values in 3-wire sequence.
Note Operation commands will be ignored in Program Mode (refer to 2-1-2) when n01 is set to 0 or
1. Normally set n01 to 0 or 1.
Used to select the input method for the RUN and STOP commands in remote mode.
0: The RUN and STOP/RESET Keys on the Digital Operator are enabled.
1: Multi-function inputs through the control circuit terminals in 2- or
3-wire sequence.
2: Operation commands via
RS-422A/485 communications are enabled.
Note The RUN command only through key sequences on the
Digital Operator is acceptable in local mode.
0, 1, 6, 8,
9
0 to 2 0
1
Default setting
Changes during operation
No
Memo
No
3-2
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n03
(0103)
Name
Frequency reference selection n04
(0104)
Description Setting range
Used to set the input method for the frequency reference in remote mode.
0: Digital Operator
1: Frequency reference 1 (n21)
2: Frequency reference control circuit terminal (0 to 10 V)
3: Frequency reference control circuit terminal (4 to 20 mA)
4: Frequency reference control circuit terminal (0 to 20 mA)
6: Frequency reference via
RS-422A/485 communications
0 to 4, 6
Interruption mode selection
Used to set the stopping method for use when the STOP command is input.
0: Decelerates to stop in preset time.
1: Coasts to stop (with output shut off by the STOP command)
0, 1 n05
(0105) n06
(0106) n07
(0107)
Reverse rotationprohibit selection
Used to select the operation with the reverse command input.
0: Reverse enabled.
1: Reverse disabled.
0, 1
STOP/
RESET
Key function selection
Used to select the stop method in remote mode with n02 for operation mode selection set to 1.
0: STOP/RESET Key of the Digital
Operator enabled.
1: STOP/RESET Key of the Digital
Operator enabled only when the
Digital Operator is selected for the
RUN command.
0, 1
Frequency selection in local mode
Used to set the input method for the frequency reference in local mode.
0: The FREQ adjuster of the Digital
Operator enabled.
1: Key sequences on the Digital Operator enabled.
0, 1 n08
(0108)
Key sequential frequency setting
Used to enable the Enter Key for setting the frequency reference with the
Increment and Decrement Keys.
0: The value is entered with the Enter Key pressed.
1: The value is enabled when the value is input.
0, 1
0
0
0
0
0
0
Default setting
Changes during operation
No
Memo
No
No
No
No
No
3-3
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n09
(0109) n10
(010A) n11
(010B) n12
(010C) n13
(010D) n14
(010E) n15
(010F) n16
(0110)
Name Description
Maximum frequency
(FMAX)
Used to set the V/f pattern as the basic characteristic of the Inverter with output voltage per frequency set.
Maximum voltage
(VMAX)
Maximum voltage frequency (FA)
Middle output frequency (FB)
Middle output frequency voltage
(VC)
Minimum output frequency
(FMIN)
Minimum output frequency voltage
(VMIN)
Acceleration time 3
Output voltage n10
(VMAX)
(VC) n15
(VMIN)
0 n14 n12
( (FMIN) ( (FB) )
Note
Note satisfied.
14 x 12 n11
11 x
Frequency
(Hz) n09
( (FMAX) )
Set the parameters so that the following condition will be
09
The value set in n13 will be ignored if parameters n14 and n12 are the same in value.
Acceleration time: The time required to go from 0% to 100% of the maximum frequency.
Setting range
50.0 to
400
1 to 255
Default setting
0.2 to 400 60.0
0.1 to 399 1.5
1 to 255
1 to 50
(see note
2)
60.0
200
12
0.1 to 10.0
1.5
12.0
0.0 to 999 10.0
n17
(0111) n18
(0112) n19
(0113)
Deceleration time 3
Acceleration time 4
Deceleration time 4 to go from 100% to 0% of the maximum frequency.
Note The actual acceleration or deceleration time is obtained from the following formula.
Acceleration/Deceleration time time set value) quency)
× reference value)
(Frequency
÷
(Max. fre-
10.0
10.0
10.0
Changes during operation
No
Memo
No
No
No
No
No
No
Yes
Yes
Yes
Yes
3-4
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n20
(0114)
Name
S-shape acceleration/ deceleration characteristic
Description Setting range
Used to set S-shape acceleration/deceleration characteristics.
0: No S-shape acceleration/deceleration (trapezoidal acceleration/deceleration)
1: S-shape acceleration/deceleration characteristic time 0.2 s
2: S-shape acceleration/deceleration characteristic time 0.5 s
3: S-shape acceleration/deceleration characteristic time 1.0 s
Note When the S-shape acceleration/deceleration characteristic time is set, the acceleration and deceleration times will be lengthened according to the
S-shape at the beginning and end of acceleration/deceleration.
0 to 3 0
Default setting
Changes during operation
No
Memo
3-5
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n21
(0115) n22
(0116) n23
(0117) n24
(0118) n25
(0119) n26
(011A) n27
(011B) n28
(011C) n29
(011D)
Name Description
Frequency reference 1
Frequency reference 2
Frequency reference 3
Frequency reference 4
Frequency reference 5
Frequency reference 6
Frequency reference 7
Frequency reference 8
Inching frequency command
Used to set internal frequency references.
Note Frequency reference 1 is enn03 for frequency reference selection set to 1.
Note These frequency references speed references (multi-function input).
Used to set the inching frequency command.
Note The inching frequency command is selected with the inching command (multi-function input). The inching frequency command takes precedence over the multi-step speed reference.
Setting range
Default setting
0.0 to max.
frequency
6.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
6.0
Changes during operation
Yes
Memo
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
3-6
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n30
(011E) n31
(011F) n32
(0120)
Name
Frequency reference upper limit
Frequency reference lower limit
Rated motor current n33
(0121)
Description
Used to set the upper and lower frequency reference limits in percentage based on the maximum frequency as 100%.
Note If n31 is set to a value less
Setting range
0 to 110
Default setting
100
Motor protection characteristics quency (n14), the Inverter will have no output when a frequency reference less than the minimum output frequency input is input.
0 to 110
Used to set the rated motor current for motor overload detection (OL1) based on the rated motor current.
Note Motor overload detection
(OL1) is disabled by setting the parameter to 0.0.
Note The rated motor current is default to the standard rated current of the maximum applicable motor.
Used to set the motor overload detection (OL1) for the electronic thermal characteristics of the motor.
0: Protection characteristics for general-purpose induction motors
1: Protection characteristics for inverter-dedicated motors
2: No protection
Note If a single Inverter is connected to more than one motor, set the parameter to 2 for no protection. The parameter is also disabled by setting n32 for rated motor to 0.0.
0.0 to
120% of rated output current of the Inverter.
0 to 2
0
0
No
Varies with the capacity.
No
No
Changes during operation
No
Memo
3-7
List of Parameters Chapter 3
Parameter
No. (Register No.
(Hex)) n34
(0122)
Name
Motor protective time setting n35
(0123)
Cooling fan operation function
Description Setting range
Used to set the electric thermal characteristics of the motor to be connected in 1-minute increments.
Note The default setting does not require any changes in normal operation.
Note To set the parameter according to the characteristics of the motor, check with the motor manufacturer the thermal time constant and set the parameter with some margin. In other words, set the value slightly shorter than the thermal time constant.
Note To detect motor overloading quicker, reduce the set value, provided that it does not cause any application problems.
Used to operate the Cooling Fan of the Inverter while the Inverter is turned on or only while the Inverter is in operation.
0: Rotates only while RUN command is input and for 1 minute after Inverter stops operating
1: Rotates while Inverter is turned on
Note This parameter is available only if the Inverter incorporates a Cooling Fan.
Note If the operation frequency of the Inverter is low, the life of the fan can be prolonged by setting the parameter to 0.
1 to 60
0, 1
8
0
Default setting
Changes during operation
No
Memo
No
3-8
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n36
Name Description
Multi-func-
(Input terminal S2)
Used to select the functions of multi-function input terminals S2 through S5.
Function Description Set value n37
(0125)
Multi-function input 2
(Input terminal S3)
0 n38
(0126) n39
Multi-function input 3
(Input terminal S4)
Multi-func-
(Input terminal S5)
2
3
4
5
6
7
8
10
11
Setting range
2 to 8,
22
2
Forward/
Reverse rotation command
3-wire sequence (to be set in n37 only)
By setting n37 to 0, the set value in n36 is ignored and the following
0, 2 to
8, 10 to 22
5
2 to 8,
10 to
22
3
Reverse/
Stop
External fault (NO)
External fault (NC)
S1: RUN input (RUN when ON)
S2: STOP input (STOP when OFF)
S3: Forward/Reverse d (OFF
Forward; ON: Reverse)
Reverse rotation command in 2-wire sequence
(Reversed with the terminal turned ON)
ON: External fault (FP j detection: j
is a terminal number)
OFF: External fault (EF j detection: j is a terminal number)
Fault reset ON: Fault reset (disabled while RUN command is input)
Multi-step speed reference 1
Signals to select frequency references 1 through
8.
Multi-step speed reference 2
Multi-step speed reference 3
Inching frequency command
Acceleration/Deceleration time changeover
ON: Inching frequency command (taking precedence over the multi-step speed reference)
ON: Acceleration time 2 and deceleration time 2 are selected.
2 to 8,
22,
34, 35
6
Default setting
Changes during operation
No
No
No
No
Memo
3-9
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n39
(0127)
Name
Multi-function input 4
(Input terminal S5) )
12
13
14
15
16
17
18
Description Setting range
External base block command
(NO)
External base block command
(NC)
Search command
(Searching starts from maximum frequency)
Search command
(Searching starts from preset frequency)
Acceleration/Deceleration-prohibit command
Local or remote selection
Communications or remote selection
ON: Output shut off
(while motor coasting to a stop and “bb” flashing)
OFF: Output shut off
(with motor free running and “bb” flashing)
ON: Speed search
(Searching starts from n09)
ON: Speed search
ON: Acceleration/Deceleration is on hold (running at parameter frequency)
ON: Local mode (operated with the Digital Operator)
ON: RS-422A/485 communications input is enabled.
OFF: The settings of n02 and n03 are enabled.
2 to 8,
10 to
22,
34, 35
6
Default setting
Changes during operation
No
Memo
3-10
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n39
(0127)
Name
Multi-function input 4
(Input terminal S5)
19
20
21
22
34
35
Description Setting range
Emergency stop fault
(NO)
The Inverter stops according to the setting in n04 for interruption mode selection with the emer-
2 to 8,
10 to
22,
34, 35
6
Emergency stop alarm
(NO)
ON.
NO: Emergency stop with the contact closed.
Emergency stop fault
(NC) the contact opened.
Fault: Fault output is ON and reset with RESET input. Alarm output is ON
Emergency stop alarm
(NC)
Up or down command
Self-diagnostic test
“STP” is displayed (lit with fault input ON and flashes with alarm input
ON)
Up or down command
(set in n39 only)
By setting n39 to 34, the set value in n38 is ignored and the following setting are forcibly made.
S4: Up command
S5: Down command
ON: RS-422A/485 communications self-diagnostic test (set in n39 only)
Default setting
Changes during operation
No
Memo
3-11
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n40
Name
Multi-func-
(MA/MB and MC output ter-
Description Setting range
8
9
10
Used to select the functions of multi-function output terminals.
Function Description Set value
0 Fault output ON: Fault output (with protective function working)
1
2
3
4
5
6
Operation in progress
Frequency detection
Idling
Frequency detection 1
Frequency detection 2
Overtorque being monitored (NOcontact output)
ON: Operation in progress
ON: Frequency detection
(with frequency reference coinciding with output frequency)
ON: Idling (at less than min. output frequency)
ON: Output frequency y frequency detection level
(n58)
ON: Output frequency x frequency detection level
(n58)
Output if any of the following parameter conditions is satisfied.
n59: Overtorque detection function selection
7 Overture being monitored (NCcontact output)
Not used n60: Overtorque detection level d tion time
NO contact: ON with overtorque being detected
NC contact: OFF with overtorque being detected
---
11
12
Alarm output
ON: Alarm being detected (Nonfatal error being detected)
Base block in progress
Base block in progress
(in operation with output shutoff)
RUN mode ON: Local mode (with the
Digital Operator)
0 to 7,
18
1
Default setting
Changes during operation
No
Memo
3-12
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n40
(0128) n41
(0129)
(
Name
Multi-function output
(MA/MB minals)
Frequency reference gain
Description
13 Inverter ready
ON: Inverter ready to operate (with no fault detected)
14
15
16
17
Fault retry ON: Fault retry
UV in progress
ON: Undervoltage being monitored
Rotating in reverse direction
Speed search in progress
ON: Rotating in reverse direction
ON: Speed search in progress
18 Data output via communications
The inverter operates multi-function output terminals independently.
Used to the input characteristics of analog frequency references.
Gain: The frequency of maximum analog input
Setting range
0 to 7,
10 to
18
0 to
255
Default setting
1
100
Changes during operation
No
Yes
Memo n42
(012A) n43
(012B) n44
(012C) n45
(012D)
Frequency reference bias
Analog frequency reference time
Analog monitor output
Analog monitor output gain maximum frequency as 100%.
Bias: The frequency of minimum analog input
(0 V or 0 or 4 mA) in percentage based on the maximum frequency as 100%.
Used to set the digital filter with a first-order lag for analog frequency references to be input.
Used to set the output frequency or current as a monitored item.
0: Output frequency (10-V output at max. frequency with n45 set to 1.00).
1: Output current (10-V output with Inverter rated output current with n45 set to 1.00)
Used to set the output characteristics of analog monitor output.
–99 to
99
0
0.00
to
2.00
0.00
to
2.00
0.10
0, 1 0
1.00
Yes
No
No
Yes
3-13
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n46
(012E)
Name Description
Carrier frequency selection
Used to set the carrier frequency according to the set values, as follows:
1 to 4: Carrier frequency = Set value x 2.5 kHz
(fixed)
7 to 9: Carrier frequency = Output frequency ratio for 1 kHz to 2.5 kHz maximum, as follows:
7: 1.0 to 2.5 kHz (12 times): Output frequency x12
8: 1.0 to 2.5 kHz (24 times): Output frequency x24
9: 1.0 to 2.5 kHz (36 times): Output frequency x36 n47
(012F)
Momentary power interruption compensation
Used to specify the processing that is performed when a momentary power interruption occurs.
0: Inverter stops operating
1: Inverter continues operating if power interruption is 0.5 s or less.
2: Inverter restarts when power is restored.
Setting range
1 to 4,
7 to 9
4
0 to 2
Default setting
Changes during operation
0
No
No n48
(0130) n49
(0131)
Fault retry Used to set the number of times the Inverter is reset and restarted automatically in the case the Inverter has an overvoltage fault, overcurrent fault, or ground fault.
Jump frequency 1
Used to set the frequency jump function.
Output frequency
0 to
10
0.0 to
400
0
0.0
No
No
Memo n50
(0132)
Jump frequency 2 n51
(0133) n52
(0134) n53
(0135) n54
(0136)
0.0 to
400
0.0
Frequency
Jump width
DC control current n50 n49
Note These values must satisfy the following condition: n49 y
n50
Used to impose DC on the induction motor for braking control.
0.0 to
25.5
0 to
100
0.0
50
Interruption DC control time
Startup DC control time based on the rated current of the Inverter as
100%.
Output frequency
Minimum output frequency
(n14) n54
Time n53
0.0 to
25.5
0.0 to
25.5
0.5
0.0
3-14
No
No
No
No
No
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n55
(0137) n56
(0138) n57
(0139) n58
(013A) n59
(013B) n60
(013C) n61
(013D)
Name
Stall prevention during deceleration
Stall prevention level during acceleration
Stall prevention level during operation
Frequency detection level
Overtorque detection function selection
Overtorque detection level
Overtorque detection time
Description Setting range
Default setting
Used to select a function to change the deceleration time of the motor automatically so that there will be no overvoltage imposed on the motor during deceleration.
0: Stall prevention during deceleration enabled
1: Stall prevention during deceleration disabled
Used to select a function to stop the acceleration of the motor automatically for stall prevention during acceleration.
Set the level in percentage based on the rated current of the Inverter as 100%.
Used to select a function to reduce the output frequency of the Inverter automatically for stall prevention during operation.
Set the level in percentage based on the rated current of the Inverter as 100%.
Used to set the frequency to be detected.
Note The parameter n40 for multi-function output must be set for the output of frequency detection levels 1 and 2.
0, 1
30 to
200
30 to
200
0.0 to
400
0
170
160
0.0
Used to enable or disable overtorque detection and select the processing method after overtorque detection.
0: Overtorque detection disabled
0 to 4
1: Overtorque detection only when speed coincides and operation continues (issues alarm)
2: Overtorque detection only when speed coincides and output shut off (for protection)
3: Overtorque always detected and operation continues (issues alarm)
4: Overtorque always detected and output shut off (for protection)
Used to set overtorque detection level.
30 to
200
Set the level in percentage based on the rated current of the Inverter as 100%.
Used to set the detection time of overtorque.
0.1 to
10.0
0
160
0.1
Changes during operation
No
No
No
No
No
No
No
Memo
3-15
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n62
(013E) n63
(013F) n64
(0140) n65
(0141) n66
(0142) n67
(0143)
Name Description
UP/DOWN command frequency memory
Torque compensation gain
Motor rated slip
Motor noload current
Slip compensation gain
Slip compensation time constant
Used to store the adjusted frequency reference with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to store the adjusted frequency reference with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to store the adjusted frequency reference with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to set the gain of the torque compensation function.
The default setting does not need any changes in normal operation.
Used to set the rated slip value of the motor in use.
Note Used as the constant of the slip compensation function.
Used to set the no-load current of the motor in use based on the rated motor current as
100%.
Note Used as the constant of the slip compensation function.
Used to set the gain of the slip compensation function.
Note The slip compensation function is disabled with n66 set to 0.0.
Used for the response speed of the slip compensation function.
Note The default setting does not need any changes in normal operation.
Setting range
Default setting
Changes during operation
0, 1 0
0.0 to
2.5
0.0 to
20.0
0 to
99
0.0 to
2.5
0.0 to
25.5
1.0
Varies with the capacity.
Varies with the capacity.
Yes
No
0.0
2.0
No
Yes
Yes
No
Memo
3-16
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n68
(0144)
(See note 1.) n69
(0145)
(See note 1.) n70
(0146)
(See note 1.) n71
(0147)
(See note 1.) n72
(0148)
(See note 1.) n73
(0149)
(See note 1.)
Name
RS-422A/4
85 communications timeover detection selection
RS-422A/4
85 communications frequency reference/ display unit selection
RS-422A/4
85 communications Slave address
RS-422A/4
85 baud rate selection
RS-422A/4
85 parity selection
RS-422A/4
85 send wait time
Description
Used to set whether a communications timeover (CE) is detected if there is an interval of more than 2 s, and to select the method of processing the detected communications timeover.
0: Detects a time-over and fatal error and coasts to a stop.
1: Detects a time-over and fatal error and decelerates to a stop in deceleration time 1.
2: Detects a time-over and fatal error and decelerates to a stop in deceleration time 2.
3: Detects a time-over and nonfatal error warning and continues operating.
4: No time-over is detected.
Used to the set the unit of frequency reference and frequency-related values to be set or monitored through communications.
0: 0.1 Hz
1: 0.01 Hz
2: Converted value based on 30,000 as max.
frequency
3: 0.1% (Max. frequency: 100%)
Used to set the Slave address (Slave unit number) for communications.
0: Only receives broadcast messages from the Master.
01 to 32: Slave address
Used to set the baud rate for communications.
0: 2,400 bps
1: 4,800 bps
2: 9,600 bps
3: 19,200 bps
Used to set the parity for communications.
0: Even parity
1: Odd parity
2: No parity
Used to set the waiting period for returning a response after the DSR (data-send-request) message is received from the Master.
Setting range
0 to 4 0
0 to 3 0
00 to
32
10 to
65
00
0 to 3 2
0 to 2 0
10
Default setting
Changes during operation
No
No
No
No
No
No
Memo
3-17
List of Parameters Chapter 3
Parameter
No.
(Register No.
(Hex)) n74
(014A)
(See note 1.)
Name Description
RS-422A/4
85 RTS control selection
Select whether or not to enable the RTS
(request-to-send) communications control function.
n75
(014B) n76
(014C)
(See note 1.)
Low-speed carrier frequency reduction selection
Used to select a function to reduce the carrier frequency when Inverter is at low speed.
0: Function disabled
1: Function enabled
Note Normally set n75 to 0.
Parameter copy and verify function
Selects the function to read, copy, and verify the parameters between the memory of the
Inverter and that of the Digital Operator.
rdy: Ready to accept the next command.
rED: Reads the Inverter parameters.
Cpy: Copies the parameter to the Inverter.
vFY: Verifies the Inverter parameters.
vA: Checks the Inverter capacity display.
Sno: Checks the software number.
n77
(014D)
(See note 1.)
Parameter read prohibit selection n78
(014E)
Error log
Selects the copy-prohibit function.
Use this parameter to protect the data in the
EEPROM of the Digital Operator.
0: Read prohibited for Inverter parameters.
(Data cannot be written to EEPROM.)
1: Read possible for Inverter parameters.
(Data can be written to EEPROM.)
Used to display the latest error recorded.
Display
Note “– – –” will be displayed if no error has been recorded.
Setting range
Default setting
Changes during operation
Memo
0, 1 0
0.1
rdy to
Sno rdy
0, 1 0
---
0
---
No
No
No
No
--n79
(014F)
Software number
Note This parameter is monitored only.
Used to display the software number of the
Inverter for OMRON’s control reference use.
Note This parameter is monitored only.
-------
Note 1.
The n68 to n74, n76, and n77 parameters cannot be written via RS422/485 communications.
They are read-only.
Note 2.
Motor parameters depend on the Inverter capacity as shown in the following table.
3-18
List of Parameters
100-V Class, Single-phase Power Supply n32 n64 n65
Parameter No.
Name
Inverter capacity kW
Rated motor current A
Unit
Motor rated slip Hz
Motor no-load current %
0.1
0.6
2.5
72
Chapter 3
Default constant
0.2
1.1
2.6
73
3-19
Maintenance
Operations
4-1 Protective and Diagnostic Functions
4-2 Inspection and Maintenance
4
Chapter 4
Maintenance Operations
4-1 Protective and Diagnostic Functions
Chapter 4
4-1-1 Fault Detection (Fatal Error)
The Inverter will detect the following faults if the Inverter or motor burns or the internal circuitry of the Inverter malfunctions. When the Inverter detects a fault, the fault code will be displayed on the Digital Operator, the fault contact output will operate, and the
Inverter output will be shut off causing the motor to coast to a stop. The stopping method can be selected for some faults, and the selected stopping method will be used with these faults. If a fault has occurred, refer to the following table to identify and correct the cause of the fault. Use one of the following methods to reset the fault after restarting the
Inverter. If the operation command is being input, however, the reset signal will be ignored. Therefore, be sure to reset the fault with the operation command turned off.
S
Turn on the fault reset signal. A multi-function input (n36 to n39) must be set to 5 (Fault
Reset).
S
Press the STOP/RESET Key on the Digital Operator.
S Turn the main circuit power supply off and then on again.
H
Fault Displays and Processing
Fault name and meaning Fault display
%c
%U
Overcurrent (OC)
The Inverter output current is as high as or higher than
200% of the rated output current.
Overvoltage (OV)
The main circuit DC voltage has reached the overvoltage detection level (100-V models:
410 V DC min.).
Probable cause and remedy
•
A short-circuit or ground fault has occurred and at the
Inverter output.
→
Check and correct the motor power cable.
•
The V/f setting is incorrect.
→
Reduce the V/f set voltage.
•
The motor capacity is too large for the Inverter.
→
Reduce the motor capacity to the maximum permissible motor capacity.
• The magnetic contactor on the output side of the Inverter has been opened and closed.
→ Rearrange the sequence so that the magnetic contactor will not open or close while the Inverter has current output.
• The output circuit of the Inverter is damaged.
→ Replace the Inverter.
•
The deceleration time is too short.
→
Increase the deceleration time.
•
The power supply voltage is too high.
→
Decrease the voltage so it will be within specifications.
•
There is excessive regenerative energy due to overshooting at the time of acceleration.
→ Suppress the overshooting as much as possible.
4-2
Maintenance Operations Chapter 4
Fault display uU1
%h
Fault name and meaning Probable cause and remedy
Main circuit undervoltage
(UV1)
The main circuit DC voltage has reached the undervoltage detection level (160 V DC for the 3G3JV-A1 j ).
Radiation fin overheated
(OH)
The temperature of the radiation fins of the Inverter has reached 110 _ C ± 10 _ C.
• Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power cable is disconnected.
→ Check the above and take necessary countermeasures.
• Incorrect power supply voltage
→
Make sure that the power supply voltage is within specifications.
• Momentary power interruption has occurred.
→ Use the momentary power interruption compensation
(Set n47 so that the Inverter restarts after power is restored)
→
Improve the power supply.
•
The internal circuitry of the Inverter is damaged.
→
Change the Inverter.
•
The ambient temperature is too high.
→
Ventilate the Inverter or install a cooling unit.
•
The load is excessive.
→
Reduce the load.
→
Decrease the Inverter capacity.
•
The V/f setting is incorrect.
→
Reduce the V/f set voltage.
•
The acceleration/deceleration time is too short.
→
Increase the acceleration/deceleration time.
•
The ventilation is obstructed.
→
Change the location of the Inverter to meet the installation conditions.
•
The cooling fan of the Inverter does not work.
→
Replace the cooling fan.
4-3
Maintenance Operations Chapter 4
Fault display
%l1
%l2
%l3
gf
Fault name and meaning Probable cause and remedy
Motor overload (OL1)
The electric thermal relay actuated the motor overload protective function.
Inverter overload (OL2)
The electronic thermal relay has actuated the Inverter overload protective function.
Overtorque detection (OL3)
There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time. A fault has been detected with n59 for overtorque detection function selection set to 2 or 4.
Ground fault (GF)
The ground fault current at the output of the Inverter has exceeded the rated output current of the Inverter.
• The load is excessive.
→ Reduce the load.
→ Decrease the Inverter capacity.
• The V/f setting is incorrect.
→ Reduce the V/f set voltage.
• The value in n11 for maximum voltage frequency is low.
→ Check the motor nameplate and set n11 to the rated frequency.
•
The acceleration/deceleration time is too short.
→
Increase the acceleration/deceleration time.
•
The value in n32 for rated motor current is incorrect.
→
Check the motor nameplate and set n32 to the rated current.
•
The Inverter is driving more than one motor.
→
Disable the motor overload detection function and install an electronic thermal relay for each of the motors.
The motor overload detection function is disabled by setting n32 to 0.0 or n33 to 2.
•
The motor protective time setting in n34 is short.
→
Set n34 to 8 (the default value).
• The load is excessive.
→
Reduce the load.
• The V/f setting is incorrect.
→ Reduce the V/f set voltage.
• The acceleration/deceleration time is too short.
→ Increase the acceleration/deceleration time.
• The Inverter capacity is insufficient.
→ Use an Inverter model with a higher capacity.
• The mechanical system is locked or has a failure.
→ Check the mechanical system and correct the cause of overtorque.
•
The parameter settings were incorrect.
→
Adjust the n60 and n61 parameters according to the mechanical system.
Increase the set values in n60 and n61.
• A ground fault has occurred at the Inverter output.
→ Check the connections between the Inverter and motor and reset the fault after correcting its cause.
4-4
Maintenance Operations Chapter 4
Fault display ef j f00 f01 f04 f05 f07 ce
Fault name and meaning Probable cause and remedy
External fault j (EF j )
An external fault has been input from a multi-function input.
A multi-function input 1, 2, 3, or 4 set to 3 or 4 has operated. The EF number indicates the number of the corresponding input (S2 to
S5).
Digital Operator transmission fault 1 (F00)
An initial memory fault has been detected
•
• The sequence is incorrect.
•
An external fault was input from a multi-function input.
→ Remove the cause of the external fault.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
The internal circuitry of the Inverter has a fault.
→ Turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
Digital Operator transmission fault 2 (F01)
A ROM fault has been detected.
•
The internal circuitry of the Inverter has a fault.
→
Turn the Inverter off and on.
→
Replace the Inverter if the same fault occurs again.
Initial memory fault (F04)
An error in the built-in
EEPROM of the Inverter has been detected.
Analog-to-digital converter fault (F05)
An analog-to-digital converter fault has been detected.
• The internal circuitry of the Inverter has a fault.
→ Initialize the Inverter with n01 set to 8 or 9 and turn the
Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
•
The internal circuitry of the Inverter has a fault.
→
Turn the Inverter off and on.
→
Replace the Inverter if the same fault occurs again.
Digital Operator fault (F07)
An error in the built-in control circuit of the Digital Operator has been detected.
Communications time-over
(CE)
Normal RS-422A/485 communications were not established within 2 s. The
Inverter will detect this error if n68 (RS-422A/485 communications time-over detection selection) is set to 0,
1, or 2.
•
The internal circuitry of the Digital Operator has a fault.
→
Turn the Digital Operator off and on.
→
Replace the Digital Operator if the same fault occurs again.
•
A short-circuit, ground fault, or disconnection has occurred on the communications line.
→
Check and correct the line.
•
The termination resistance setting is incorrect.
→
Set the termination resistance of only the Inverter located at each end of the network to ON.
• Noise influence.
→ Do not wire the communications line along with power lines in the same conduit.
→ Use the twisted-pair shielded wire for the communications line, and ground it at the Master.
•
Master’s program error.
→
Check and correct the program so that communications will be performed more than once every 2-s period.
• Communications circuit damage.
→ If the same error is detected as a result of a self-diagnostic test, change the Inverter.
4-5
Maintenance Operations Chapter 4
Fault display
OFF
Fault name and meaning
Emergency stop (STP)
An emergency stop alarm is input to a multi-function input.
(A multi-function input 1, 2, 3, or 4 set to 19 or 21 has operated.)
Power supply error
• Insufficient power supply voltage
•
Control power supply fault
•
Hardware fault
Probable cause and remedy
• An emergency stop alarm is input to a multi-function input.
→ Remove the cause of the fault.
• The sequence is incorrect.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
• No power supply is provided.
→
Check and correct the power supply wire and voltage.
• Terminal screws are loosened.
→ Check and tighten the terminal screws.
• The Inverter is damaged.
→ Replace the Inverter.
4-6
Maintenance Operations
4-1-2 Warning Detection (Nonfatal Error)
Chapter 4
The warning detection is a type of Inverter protective function that does not operate the fault contact output and returns the Inverter to its original status once the cause of the error has been removed. The Digital Operator flashes and display the detail of the error.
If a warning occurs, take appropriate countermeasures according to the table below.
Note Some warnings or some cases stop the operation of the Inverter as described in the table.
H
Warning Displays and Processing
Fault display
uU
(flashing)
%U
(flashing)
%h
(flashing)
cal
(flashing)
%l3
(flashing)
Warning name and Meaning
Main Circuit Undervoltage (UV)
The main circuit DC voltage has reached the undervoltage detection level (160 V DC for the 3G3JV-A1 j
).
Probable cause and remedy
• Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power line is disconnected.
→
Check the above and take necessary countermeasures.
• Incorrect power supply voltage
→ Make sure that the power supply voltage is within specifications.
• The power supply voltage is too high.
→ Decrease the voltage so it will be within specifications.
Main Circuit Overvoltage
The main circuit DC voltage has reached the overvoltage detection level (100-V models: 410 V DC min.).
Radiation fin overheated (OH)
The temperature of the radiation fins of the Inverter has reached 110
_
C
±
10
_
C.
Communications standby (CAL)
No normal DSR message has been received during RS-422A/4895 communications.
The Inverter detects this warning only when RUN command selection (n02) is set to 2 or frequency reference selection (n03) is set to 6. Until the warning is reset, no input other than communications input will be ignored.
Overtorque detection (OL3)
There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time. A fault has been detected with n59 for overtorque detection function selection set to 1 or 3.
•
The ambient temperature is too high.
→
Ventilate the Inverter or install a cooling unit.
•
A short-circuit, ground fault, or disconnection has occurred on the communications line.
→ Check and correct the line.
• The termination resistance setting is incorrect.
→ Set the termination resistance of only the
Inverter located at each end of the network to
ON.
•
Master’s program error.
→
Check the start of communications and correct the program.
• Communications circuit damage.
→ If a CAL or CE error is detected as a result of a self-diagnostic test, change the Inverter.
• The mechanical system is locked or has a failure.
→ Check the mechanical system and correct the cause of overtorque.
•
The parameter settings were incorrect.
→
Adjust the n60 and n61 parameters according to the mechanical system.
Increase the set values in n60 and n61.
4-7
Maintenance Operations Chapter 4
Fault display ser
(flashing)
bb
(flashing)
ef
(flashing)
(flashing) fRn
(flashing)
Warning name and Meaning
Sequence error (SER)
A sequence change has been input while the Inverter is in operation.
Local or remote selection is input while the Inverter is in operation.
Note The Inverter coasts to a stop.
External base block (bb)
The external base block command has been input.
Note The Inverter coasts to a stop.
Probable cause and remedy
• A sequence error has occurred.
→ Check and adjust the local or remote selection sequence as multi-function input.
• The external base block command has been input as multi-function input.
→ Remove the cause of external base block input.
•
The sequence is incorrect.
→
Check and change the external fault input sequence including the input timing and NO or NC contact.
•
A sequence error has occurred.
→
Check and adjust the local or remote selection sequence.
Forward- and reverse-rotation input
(EF)
The forward and reverse commands are input to the control circuit terminals simultaneously for 0.5 s or more.
Note The Inverter stops according to the method set in n04.
Emergency stop (STP)
The Digital Operator stops operating.
The STOP/RESET Key on the Digital
Operator is pressed while the Inverter is operating according to the forward or reverse command through the control circuit terminals.
Note The Inverter stops according to the method set in n04.
The emergency stop alarm signal is input as multi-function input.
A multi-function input 1, 2, 3, or 4 set to 20 or 22 has been used.
Note The Inverter stops according to the method set in n04.
Cooling fan fault (FAN)
The cooling fan has been locked.
•
•
The parameter setting was incorrect.
→ Turn off the forward or reverse command once, check that the n06 parameter setting for
STOP/RESET Key function selection, and restart the Inverter.
An emergency stop alarm is input to a multi-function input.
→ Remove the cause of the fault.
• The sequence is incorrect.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
• The cooling fan wiring has a fault.
→ Turn off the Inverter, dismount the fan, and check and repair the wiring.
• The cooling fan in not in good condition.
→ Check and remove the foreign material or dust on the fan.
•
The cooling fan is beyond repair.
→
Replace the fan.
4-8
Maintenance Operations Chapter 4
Fault display ce
Warning name and Meaning
Communications time-over (CE)
Normal RS-422A/485 communications were not established within 2 s. The
Inverter will detect this error if n68
(RS-422A/485 communications time-over detection selection) is set to
0, 1, or 2.
%p1
(flashing)
%p2
(flashing)
%p3
(flashing)
%p4
(flashing)
%p5
(flashing)
Operation error (OP j
)
(Parameter setting error)
Probable cause and remedy
• A short-circuit, ground fault, or disconnection has occurred on the communications line.
→
Check and correct the line.
•
The termination resistance setting is incorrect.
→ Set the termination resistance of only the
Inverter located at each end of the network to
ON.
• Noise influence.
→ Do not wire the communications line along with power lines in the same conduit.
→ Use the twisted-pair shielded wire for the communications line, and ground it at the
Master.
• Master’s program error.
→ Check and correct the program so that communications will be performed more than once every 2-s period.
•
Communications circuit damage.
→
If the same error is detected as a result of a self-diagnostic test, change the Inverter.
•
The values in n36 through n39 for multi-function inputs 1 through 4 have been duplicated.
→
Check and correct the values.
• The V/f pattern settings do not satisfy the following condition.
n14 x n12 t n11 x n09
→ Check and correct the set value.
• The rated motor current set in n32 exceeds
150% of the rated output current of the Inverter.
→ Check and correct the value.
•
The frequency reference upper limit set in n30 and the frequency reference lower limit set in n31 do not satisfy the following condition.
n30 y n31
→ Check and correct the set values.
•
The jump frequencies set n49, n50 do not satisfy the following condition.
n49 y n50
→ Check and correct the set values.
4-9
Maintenance Operations
4-2 Inspection and Maintenance
Chapter 4
H
Daily Inspection
Check the following items while the system is operating.
•
No abnormal noise or vibration in the motor
•
No abnormal heat generation
•
Output current monitor display is not a higher value than normal
• Cooling fan installed in Inverter is operating normally (models with fans only)
H
Periodic Inspection
Check the following items when performing periodic maintenance.
Always wait at least one minute after the power supply has been turned OFF and all the LED indicators have turned OFF before performing maintenance. Touching the terminals immediately after the power is turned OFF may result in electric shock.
•
No looseness in terminal screws
•
No electroconductive dust or oil mist attached to terminal block or the Inverter’s internal parts
• No looseness in Inverter mounting screws
•
No accumulation of dirt or dust on cooling fin (heat sink)
•
No dust accumulated in the ventilation holes
•
No abnormality in external appearance
•
Cooling fan in control panel is operating normally
(Check that there is no abnormal noise or vibration, and that the total ON time has not exceeded the specified value.)
H
Periodic Maintenance of Components
The Inverter is constructed from many components, the normal operation of which is required for the essential functionality of the Inverter. Maintenance is required for some of the electronic components depending on the operating conditions. To enable the Inverter to operate normally for a long time, periodic inspection and component replacement must be performed to suit the service life of these components.
(Source: “Instructions for Periodic Inspection of General Purpose Inverter” (JEMA))
The guidelines for periodic inspection depend on the Inverter’s installation environment and operating conditions.
The maintenance periods for the Inverter are listed below. Use this to determine when periodic maintenance is required.
The guidelines for periodic maintenance are as follows:
•
Cooling fan: 2 to 3 years
•
Electrolytic capacitor: 10 years
•
Fuse: 10 years
These guidelines are applicable for an operating environment in which the ambient temperature is
40
°
C, the load rate is 80%, the operating time is 8 hours per day, and the product is installed according to the instructions in the manual.
4-10
Maintenance Operations Chapter 4
To extend the maintenance period, it is recommended to lower the ambient temperature and shorten the ON time as much as possible.
Note Contact your OMRON sales representative for details on maintenance methods.
4-11
Terms and Conditions of Sale
1.
Offer; Acceptance. These terms and conditions (these "Terms") are deemed part of all quotes, agreements, purchase orders, acknowledgments, price lists, catalogs, manuals, brochures and other documents, whether electronic or in writing, relating to the sale of products or services (collectively, the "Products") by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron objects to any terms or conditions proposed in Buyer’s purchase order or other documents which are inconsistent with, or in addition to, these Terms.
2.
Prices; Payment Terms. All prices stated are current, subject to change without notice by Omron. Omron reserves the right to increase or decrease prices on any unshipped portions of outstanding orders. Payments for Products are due net 30 days unless otherwise stated in the invoice.
3.
Discounts. Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (i) the invoice is paid according to Omron’s payment terms and (ii) Buyer has no past due amounts.
4.
Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms.
5.
Orders. Omron will accept no order less than $200 net billing.
6.
Governmental Approvals. Buyer shall be responsible for, and shall bear all costs involved in, obtaining any government approvals required for the importation or sale of the Products.
7.
Taxes. All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Omron or required to be collected directly or indirectly by Omron for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Omron.
8.
Financial. If the financial position of Buyer at any time becomes unsatisfactory to Omron, Omron reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Omron may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts.
9.
Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron: a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship except in “break down” situations.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall constitute delivery to Buyer; c. All sales and shipments of Products shall be FOB shipping point (unless otherwise stated in writing by Omron), at which point title and risk of loss shall pass from Omron to Buyer; provided that Omron shall retain a security interest in the Products until the full purchase price is paid; d. Delivery and shipping dates are estimates only; and e. Omron will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions.
12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writing to Omron within 30 days of receipt of shipment and include the original transportation bill signed by the carrier noting that the carrier received the Products from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty.
See http://oeweb.omron.com or contact your Omron representative for published information.
14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and their employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Omron is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. Without limiting the foregoing, Buyer (at its own expense) shall indemnify and hold harmless Omron and defend or settle any action brought against such Companies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party.
16. Property; Confidentiality. Any intellectual property in the Products is the exclusive property of Omron Companies and Buyer shall not attempt to duplicate it in any way without the written permission of Omron. Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Omron. All information and materials supplied by Omron to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party.
17. Export Controls. Buyer shall comply with all applicable laws, regulations and licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of regulated technology or information.
18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right and no course of dealing between Buyer and Omron shall operate as a waiver of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder without Omron's written consent. (c) Law. These Terms are governed by the law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law principles). (d) Amendment. These Terms constitute the entire agreement between
Buyer and Omron relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. (e) Severability. If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. (f) Setoff. Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. (g) Definitions. As used herein, “including” means “including without limitation”; and “Omron Companies” (or similar words) mean Omron Corporation and any direct or indirect subsidiary or affiliate thereof.
Certain Precautions on Specifications and Use
1.
Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the
Product in the Buyer’s application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this Product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-
ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
2.
Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
3.
Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
4.
Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product.
5.
Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
OMRON ELECTRONICS LLC
1
Commerce Drive
Schaumburg, IL
60173
847.843.7900
For US technical support or other inquiries: 800.556.6766
OMRON CANADA, INC.
885
Milner Avenue
Toronto, Ontario M
1
B
5
V
8
416.286.6465
OMRON ON-LINE
Global - www.omron.com
USA - www.omron247.com
Canada - www.omron.ca
Brazil - www.omron.com.br
Latin America - www.espanol.omron.com
UNITED STATES
To locate a Regional Sales Office, local Distributor or to obtain product information, call: 847.843.7900
MEXICO SALES OFFICES
Mexico, D.F.
Ciudad Juárez
555.660.3144
656.623.7083
Monterrey, N.L 818.377.4281
Querétaro 442.135.4510
BRAZIL SALES OFFICE
Sao Paulo 55.11.2101.6310
ARGENTINA SALES OFFICE
Cono Sur 54.114.787.1129
OTHER LATIN AMERICAN SALES
I546-E1-02 ©200
7
OMRON ELECTRONICS LLC
Printed in the U.S.A.
Specifications subject to change without notice.