Instrukcja obsługi
BasicController i BasicController
plus
CR0401
CR0403
CR0411
PL
BasicController / BasicController plus
Spis treści
3.3 Urządzenia serii produktów Basic (przykłady) � � � � � � � � � � � � � � � � � � � � � � 7
4.1 Ogólne instrukcje dotyczące montażu � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
4.1.2 Powierzchnia montażu � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
4.3 Pokrywa i uszczelnienie kablowe � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
4.3.1 Instalacja uszczelnienia kablowego � � � � � � � � � � � � � � � � � � � � � � � � � 10
4.3.2 Demontaż uszczelnienia kablowego � � � � � � � � � � � � � � � � � � � � � � � � 10
4.3.4 Demontaż pokrywy � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �11
5.1 Ogólne zasady wykonywania podłączeń.
� � � � � � � � � � � � � � � � � � � � � � � � � 12
5.2.1 Przykładowe akcesoria � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
9.2 Czyszczenie powierzchni obudowy � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 33
2
BasicController / BasicController plus
PL
Ten dokument jest instrukcją tłumaczoną.
≥ CR0401AC
≥ CR0403 AD
≥ CR0411 AA
Wszystkie znaki towarowe i nazwy firm podlegają prawom autorskim poszczególnych firm.
3
4
BasicController / BasicController plus
1 Uwaga wstępna
Niniejszy dokument odnosi się do urządzeń typu "BasicController / BasicController plus " (art. nr: CR040x, CR041x).
Oraz est uznawany za część urządzenia.
Dokument jest przeznaczony dla specjalistów. Specjaliści to osoby, które posiadają odpowednie kwalifikacje i doświadczenie pozwalające im przewidywać i zapobiegać możliwym zagrożeniom, mogącym powstać podczas użytkowania urządzenia. Dokument zawiera informację dotyczące prawidłowej obsługi urządzenia.
Należy przeczytać niniejszy dokument przed zastosowaniem urządzenia, aby zapoznać się z warunkami pracy, montażu i działania urządzenia. Proszę zachować ninejszą instrukcje przez cały czas użytkowania urządzenia.
Proszę stosować się do instrukcji bezpieczeństwa.
1.1 Symbole
► Instrukcje
> Reakcja, wynik
[…] Oznaczenie przycisków, klawiszy oraz wskaźników
→ Odsyłacz
Ważna uwaga
Nie stosowanie się do instrukcji obsługi może prowadzić do nieprawidłowego działania lub zakłóceń.
Informacje
Nota uzupełniająca
1.2 Użyte znaki ostrzegawcze
Ostrzeżenie
Ostrzeżenie przed poważnym urazem ciała.
Grozi śmiercią lub trwałym uszkodzeniem ciała.
UWAGA
Ostrzeżenie przed urazem ciała.
Mogą się pojawić niewielkie odwracalne urazy.
UWAGA
Ostrzeżenie przed uszkodzeniem mienia.
BasicController / BasicController plus
2 Instrukcje dotyczące bezpieczeństwa
2.1 Ogólne
Instrukcje te zawierają informacje tekstowe i rysunki dotyczące prawidłowej obsługi urządzenia i muszą zostać przeczytane przed instalacją lub użyciem urządzenia.
Należy postępować zgodnie z zawartymi instrukcjami. Nieprzestrzegania instrukcji, użytkowanie niezgodne z poniższymi zaleceniami, nieprawidłowy montaż lub użytkowanie mogą wpłynąć na bezpieczeństwo ludzi i maszyn.
PL
2.2 Grupa docelowa
Instrukcje te przeznaczona są dla osób upoważnionych zgodnie z wytycznymi dyrektywy EMC i dyrektywy niskonapięciowej. Urządzenie może być montowane, podłączane i uruchamiane wyłącznie przez odpowiednio wykwalifikowanego elektryka.
2.3 Podłączenie elektryczne
Przed wykonaniem podłączeń elektrycznych należy odłączyć zasilanie. Jeśli jest to konieczne, należy odłączyć wszystkie niezależnie zasilane obwody wyjściowe.
Jeśli urządzenie nie jest zasilane przez system zasilania pojazdu (akumulatory
12/24 V), należy zapewnić zewnętrzne napięcie, generowane i dostarczane zgodnie z kryteriami bezpieczeństwa niskiego napięcia (SELV), ponieważ to napięcie jest dostarczane bez dalszych pomiarów do podłączonego sterownika, czujników oraz elementów wykonawczych.
Podłączenie wszystkich sygnałów połączonych z obwodem SELV musi być zgodne z wymaganiami SELV (bezpieczne oddzielenie od innych obwodów).
Jeśli układ zasilania SELV posiada zewnętrzne uziemienie (SELV staje się PELV), odpowiedzialność spoczywa na użytkowniku a zastosowanie mają odpowiednie krajowe przepisy instalacji. Wszystkie stwierdzenia niniejszej instrukcji odnoszą się do urządzenia, którego napięcie SELV nie jest uziemione.
Połączenia mogą być zasilane z tylko według danych podanych w danych technicznych i / lub na etykiecie urządzenia, podłączone tylko za pomocą akcesoriów zatwierdzonych przez ifm electronic.
2.4 Ingerencja w urządzenie
W przypadku usterki lub niepewności związanych z działeniem prosimy o kontakt z producentem. Ingerencja w urządzenie może poważnie wpłynąć na bezpieczeństwo operatorów i maszyn, jest zabroniona i prowadzi do wyłączenia jakiejkolwiek odpowiedzialności producenta czy roszczeń gwarancyjnych.
5
BasicController / BasicController plus
3 Funkcje i własności
Swobodnie programowalne kontrolery z serii "BasicController / BasicController plus " są przystosowane do użytkowania w trudnych warunkach (np. rozszerzony zakres temperatur, silne wibracje, intensywne zakłócenia EMC), oraz nadają się do bezpośredniogo montażu w urządzeniach mobilnych.
Za pomocą środowiska progamistycznego można skonfigurować wejścia oraz wyjścia w celu dostosowania do wymagań danej aplikacji. Kontrolery te mogą być wykorzystane jako kontrolery CAN, CANopen master oraz inteligenty moduł wejść/
Rozszerzenia specyficzne dla aplikacji są możliwe w połączeniu z dodatkowymi produktami serii Basic.
OSTRZEŻENIE
Seria BasicController / BasicController plus nie posiada dopuszczeń do zastosowań związanych z bezpieczeństwem osób.
UWAGA
BasicController / BasicController plus przeznaczony jest do instalacji we wnętrzu pojazdu a nie w silnikach.
3.1 Przegląd głównych danych
● swobodnie programowalne zgodnie z IEC 61131-3
● 2 interfejsy CAN (uwzg. interfejs do BasicDisplay CR0451 lub CR0452)
● konfigurowalne wejścia /wyjścia
● diody statusowe LED
3.2 Przykład zastosowania
Użycie z pokrywą i wyświetlaczem BasicDisplay
6
BasicController / BasicController plus
3.3 Urządzenia serii produktów Basic (przykłady)
● BasicDisplay (art. nr: CR0451) programowalny wyświetlacz kolorowy o przekątnej 2.8 cala
5 swobodnie programowalnych, podświetlanych przycisków
1 przełącznik z funkcjonalnością kursora
● BasicDisplay XL (art. nr: CR0452) programowalny wyświetlacz kolorowy o przekątnej 4.3 cala
6 swobodnie programowalnych, podświetlanych przycisków
1 przełącznik z funkcjonalnością kursora
● BasicRelay (art. nr: CR0421) swobodnie podłączana podstwa do 6 przekaźników i 10 bezpieczników samochodowych
● Pokrywa (art. nr: EC0401)
● Pokrywa z otworem do zabudowania wyświetlacza (art. nr: EC0402) zawiera uszczelniania kablowe, żeby osiągnąć IP 54
Dlasze informacje na temat rodziny produktów Basic: www.ifm.com.pl→ Asortyment produktów → Systemy do maszyn mobilnych →
Mikrosterowniki lub bezpośrednio www.ifm.com.pl → wyszukiwanie kart katalogowych → np. CR0451
PL
7
BasicController / BasicController plus
4 Montaż
4.1 Ogólne instrukcje dotyczące montażu
4.1.1 Stopień ochrony
Osiągalny stopień ochrony urządzenia zależy od zastosowanych akcesoriów i pozycji montażu.
Stopień ochrony
IP 20
IP 54
Akcesoria
– pokrywa z uszczelnieniem kablowym
Pozycja montażu dowolny przyłączenia kablowe od spodu
Art. nr
– np. EC0401
4.1.2 Powierzchnia montażu
UWAGA
Obudowa nie może być narażona na siły skręcające lub naprężenia mechaniczne.
► Należy montować urządzania na płaskich powierzchniach.
► Przy braku płaskiej powerzchni, należy zastowoać elementy kompensacyjne,
Powierzchnia montażu
4.2 Mocowanie
► Należy umieścić załączone tukeje w tylnej częsci modułu w 4 otworach montażowych.
► Następnie zamocować moduł używając 4 podkładek i śrub M4.
Dokręcić śruby, dociągając po przekątnych.
8
BasicController / BasicController plus
Użycie tuleji.
Moment dokręcający: 1,5 Nm
Wymiary otworów montażowych (→ 8 Dane techniczne)
Możliwe do zastosowania śruby (przykłady):
Śruby imbusowe z łbem cylindrycznym
Śruby imbusowe z niskim łbem cylindrycznym
Standard
DIN 912
DIN 7984
PL
9
BasicController / BasicController plus
4.3 Pokrywa i uszczelnienie kablowe
UWAGA
Stopień ochrony IP 54 może zostać osiągnięty jedynie gdy zostanie użyta pokrywa razem z uszczlenieniem kablowym.
UWAGA
Po zainstalowaniu pokrywy może wzrosnąć temperatura modułu.
4.3.1 Instalacja uszczelnienia kablowego
► Należy włożyć uszczelnienie kablowe w lokator od dołu.
> Zamek uszczelnienia kablowego kliknie słyszalnie.
1� Lokator uszczelnienia kablowego.
2� Blokowanie
Zamontowane uszczelnienie kablowe.
Uszczelnienie kablowe nie może być używane do odciążania kabli.
(→ 5.1 Ogólne zasady wykonywania podłączeń.)
4.3.2 Demontaż uszczelnienia kablowego
► Należy nacisnąć blokadę na dole urządzenia i usunąć uszczelnienie kablowe z urządzenia pociągając w dół.
1� Uszczelnienie kablowe
2� Blokada
Spód urządzenia
10
BasicController / BasicController plus
4.3.3 Instalacja pokrywy
Pokrywy serii Basic posiadają pojedynczą dzwignię blokującą. Montażu pokrywy dokonuje się bez użycia narzędzi.
PL
1: dzwignia blokująca
2: zaczepy pokrywy
3: otwory na zaczepy pokrywy
► Należy pociągnąć dzwignię blokującą i obrócić do siebie.
► Następnie umieścić pokrywę pod kątem do urządzenia.
Należy umieścić oba zaczepy na dole pokrywy w odpowiednie otwory w urządzeniu.
► Natępnie zamknąć porywę na dolnej części.
Zaczepy i otwory stanowią oś obrotu.
► Następnie należy zablokować dźwignię w jej początkowym położeniu.
> Pokrywa została zablokowana.
1: BasicController / BasicController plus
2: pokrywa
4.3.4 Demontaż pokrywy
► Należy pociągnąć dzwignię blokującą i obrócić do siebie.
> Pokrywa jest odblokowana i może zostać usunięta.
11
BasicController / BasicController plus
5 Podłączenie elektryczne
5.1 Ogólne zasady wykonywania podłączeń.
Przewody zasilające, interfejsy CAN oraz wyjścia/wejścia powinny by podłączone poprzez
6.3 x 0.8 mm konektory męskie w przedniej części urządzenia.
Schemat połączeń (→ 8 Dane techniczne)
A B C D
N2
E F
P/N1
1: Wejścia
2: Wyjścia
3: Zasilanie i interfejsy CAN
Strefa konektorów
C
D
E
Konektor
A
B
F
P/N1
N2
Podłączenie
Wejścia wyjścia
CR0401
IN0���3
IN4���7
IN8���11
–
OUT0���3
CR0403
IN0���3
IN4���7
IN8���11
OUT0���3
OUT4���7
OUT4���7 interfejs CAN 1 i zasilanie
OUT8���11 interfejs CAN 2 (np. do BasicDisplay CR0451)
CR0411
IN0���3
IN4���7
–
OUT0���3
OUT4���7
–
Liczba złącz
8
6
4
UWAGA
Błędne podłączenie może uszkodzić urządzenie.
► Należy postępować zgodnie z zawartymi instrukcjami (→ 2.3 Podłączenie elektryczne).
► Zasadniczo wszystkie przewody zasilające i sygnałowe należy układać osobno.
► Należy układać przewody do urządzenia najkrószą możliwą trasą.
► Wyszstkie przewody należy odciążyć przynajmniej 100mm za miejscem podłączenia.
► Gdy nie jest stosowana pokrywa ochronna, należy chronić niezarobionymi wtyczkami nieżywane złącza.
12
BasicController / BasicController plus
5.2 Akcesoria
Więcej informacji o akcesoriach znajdą Państwo pod adresem: www.ifm.com.pl → wyszukiwanie kart katalogowych → np. CR0401 → Akcesoria
5.2.1 Przykładowe akcesoria
PL
BasicDisplay CR0451
Pokrywa EC0402 z otworem na wyświetlacz kabel łączeniowy EC0452
Akcesoria i przykład podłączenia
5.3 Wejścia częstotliwościowe
► Do podłączenia wejść częstotliwościowych należy stosować przewody ekranowane, tak aby zakłócenia nie miały wpływu na sygnały użytkowe.
5.4 Bezpieczniki
► Każdy osobny obwód musi być chroniony osobno, aby zapewnić bezpieczeństwo całego systemu.
Opis
VBB
S
VBB
1
Potencjał
8…32 V DC
8…32 V DC
Złącze: pin
P/N1: 1
P/N1: 2
Bezpiecznik
≤ 2 A T
15 A
VBB
2
Zasilanie czujników/modułu
Zasilanie wyjść
CR0401: OUT0...3
CR0403: OUT0...7
CR0411: OUT0...3
Zasilanie wyjść
CR0401: OUT4...7
CR0403: OUT8...11
CR0411: OUT4...7
8…32 V DC P/N1: 3 15 A
13
BasicController / BasicController plus
6 Wskaźniki
1: diody statusowe LED
Stany pracy (→ 8 Dane techniczne)
2: Dioda led w pokrywie (np. EC0401)
14
BasicController / BasicController plus
7 Uruchomienie
7.1 Programowanie
Użytkownik może w prosty sposób tworzyć oprogramowanie za pomocą aplikacji zgodnej z IEC 61131-3 CODESYS 2.3.
Ostrzeżenie
Użytkownik jest odpowiedzialny za bezpieczne funkcjonowanie programów, stworzonych przez samego siebie. Jeśli to konieczne, użytkownik musi dodatkowo przeprowadzić badania homologacyjne zgodnie z odpowiednimi przepisami krajowymi.
7.2 Dokumentacja
Oprócz aplikacji CODESYS do programowaniasterownik, dostępne są następujące dokumenty do programowania i konfiguracji urządzenia:
● CODESYS V2.3 programming manual
(alternatywnie jako pomoc online)
● BasicController / BasicController plus system manual
(alternatywnie jako pomoc online)
Podręczniki te można ściągnąć z internetu: www.ifm.com.pl → wyszukiwanie kart katalogowych → np. CR0401 → Dodatkowe informacje
CODESYS and BasicController / BasicController plus pomoc online: www.ifm.com → Service → Download → Control systems*
*) ściągnięcie wymaga rejestracji
7.3 Wymagany sprzęt
Interfejs CAN do połączenia z komputerem, jest niezbędny do załadowania oprogramowania do urządzenia.
Przykład:
● CAN/RS232 USB interfejs CANfox (art. nr: EC2112)
● Kabel adaptacyjny CANfox (art. nr: EC2113)
Więcej informacji o akcesoriach znajdą Państwo na: www.ifm.com.pl → wyszukiwanie kart katalogowych → CR0451 → Akcesoria lub bezpośrednio www.ifm.com.pl → wyszukiwanie kart katalogowych → EC2112
PL
15
BasicController / BasicController plus
8 Dane techniczne
Control systems
8.1 CR0401
CR0401
Mobile controller
BasicController
12 inputs
8 outputs
2 CAN interfaces
Programming to IEC 61131-3
8...32 V DC
8,5
12,5
LED
A B C D E
N2
F
P/N1
25,5
18
Technical data
Mechanical data
Housing
Dimensions (H x W x D) without cover with EC0401 cover with EC0402 cover and BasicDisplay
CR0451
Installation
Connection
Inputs
Outputs
Operating voltage , CAN bus
Protection rating
Operating/storage temperature
Weight
Electrical data
Operating voltage
Current consumption
Overvoltage
Undervoltage detection
Undervoltage shutdown
Processor
Memory (total)
Memory allocation
Device monitoring
79,7
112
Modular control system
Usable as CANopen controller or intelligent I/O module plastic housing (black)
163 x 112 x 25.5 mm
163 x 112 x 68 mm
163 x 112 x 73.4 mm
xing by means of 4 M4 screws to DIN 912 or DIN 7984 and 4 tubular rivets to
DIN 7340 (tubular rivets are supplied)
AMP blade male terminals 6.3 mm, to be clipped into place and thus vibrationresistant, protected against reverse polarity contacts AMP timer, CuZn pre-tin-plated core cross-section 0.5...2.5 mm²
3 x 8-pole
2 x 8-pole
1 x 6-pole, 1 x 4-pole
IP 20 (with cover and cable seal IP 54)
-40...85° C / -40...85° C
0.30 kg
8...32 V DC
45 mA (at 24 V DC)
36 V for t ≤ 10 s at U
B
≤ 7.8 V at U
B
≤ 7.0 V
Freescale PowerPC, 50 MHz
208 Kbytes RAM / 1536 Kbytes Flash / 1 Kbyte FRAM see BasicController system manual www.ifm.com → data sheet search → e.g. CR0401 → Additional data undervoltage monitoring watchdog function checksum test for program and system excess temperature monitoring
CR0401 / page 1 24.10.2014
Control systems
CR0401
CAN interfaces 1/2
Baud rate
Communication pro le
Software/programming
Programming system
Inputs
Con gurations
Outputs
Con gurations
Status LED
Operating states (preset)
BasicController / BasicController plus
Technical data
CAN interface 2.0 A/B, ISO 11898
20 kBit/s...1 MBit/s (default CAN1: 250 kBit/s, CAN2: 250 kBit/s)
CANopen, CiA DS 301 version 4, CiA DS 401 version 1.4
or SAE J 1939 or free protocol
CODESYS version 2.3 (IEC 61131-3)
12 (con gurable),
Number Version
4
4
4 digital for positive / negative sensor signals analogue (0…10/32 V DC, 0..20 mA, ratiometric) frequency ( ≤ 30 kHz) digital for positive sensor signals resistance measurement (0,016...3.6 k Ω ) digital for positive sensor signals positive sensor signals have diagnostic capabilities
8 (con gurable),
Number Version
2
4
2 positive switching (high side)
PWM output (20…250 Hz), 2 A, diagnosis positive switching (high side)
PWM output (20…250 Hz), 1 A positive switching (high side)
PWM output (20…250 Hz), 4 A, diagnosis
B
A
B
L
L
Colour
– orange green red two-colour LED (red/green)
Status Description permanently off no operating voltage
1 x on
5 Hz
2 Hz permanently on application stopped (STOP)
10 Hz
5 Hz initialisation or reset checks no operating system loaded application is running (RUN) application stopped (STOP with error) application stopped due to undervoltage permanently on system fault (fatal error)
/B
FRQ
B
L
H
B
H
PWM
B
H
PWM
B
H
PWM
PL ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0401 / page 2 24.10.2014
17
BasicController / BasicController plus
Control systems
CR0401
Characteristics of the inputs
Analogue inputs (A)
Connection A: 02, 03, 06, 07
IN0...IN3
can be con gured as:
Technical data
● Voltage inputs
Input voltage
Resolution
Accuracy
Input resistance
Input frequency
●
0...10 V or 0...32 V
12 bits
± 1% FS
65.6 k Ω (0...10 V), 50.7 k
≤ 500 Hz
Current inputs, with diagnostic capability
Ω (0...32 V)
Input current
Resolution
Accuracy
Input resistance
0...20 mA
12 bits
± 1% FS
400 Ω
Input frequency ≤ 500 Hz
At a current of > 23 mA the input is switched to the voltage input!
● Voltage inputs, 0...32 V, ratiometric
Function
Value range
Input resistance
(U
IN
÷ U
B
) x 1000 ‰
0...1000 ‰
50.7 k Ω
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
Diagnosis short circuit
> 0.95 U
B
< 1 V
● Binary voltage inputs for negative sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
● Frequency inputs
Input resistance
Input frequency
Switch-on level
Switch-off level
> 0.7 U
B
< 0.3 U
B
3.2 k Ω
50 Hz
> 0.7 UB
< 0.3 UB
3.2 k Ω
50 Hz
3.2 k
≤
Ω
30 kHz
> 0.35...0.48 U
< 0.29 U
B
B
Digital input (B
L
)
Connection B: 02, 03, 06, 07
IN4…IN7 can be con gured as...
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
> 0.7 U
B
< 0.3 U
B
3.2 k
< 1 V
Ω
50 Hz
> 0.95 U
B
Diagnosis short circuit
● Resistor input
Measuring range
Accuracy
16…3.6 k
± 3 %
Ω ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0401 / page 3 24.10.2014
18
BasicController / BasicController plus
Control systems
CR0401
Digital input (B
L
)
Connection C: 02, 03, 06, 07
IN8…IN11 can be con gured as...
Technical data
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
Diagnosis short circuit
> 0.7 U
B
< 0.3 U
B
3.2 kΩ
50 Hz
> 0.95 U
< 1 V
B
Characteristics of the outputs
Digital outputs (B
H
, PWM)
Connection F: 01, 03,
OUT4…OUT5
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected. Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage 8...32 V DC
≤ 2A Switching current
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
20...250 Hz
1…1000 ‰
≤ 2A
If only one output of the output pair is active, the switching current is ≤ 2.5 A.
Max. switch-on current ≤ 11 A
Digital outputs (B
H
, PWM)
Connection E: 01, 03, 05, 07
OUT0…OUT3
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected
Switching voltage
Switching current
8...32 V DC
≤ 1 A
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
20...250 Hz
1…1000 ‰
≤ 1 A
Max. switch-on current ≤ 11 A
Digital outputs (B
Connection F: 05, 07
OUT6…OUT7
H
, PWM)
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected. Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage 8...32 V DC
≤ 4 A Switching current
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
20...250 Hz
1…1000 ‰
≤ 4 A
Max. switch-on current ≤ 30 A
Free wheel diodes
Overload protection
(valid for all outputs)
Short-circuit strength
(valid for all inputs and outputs)
Max. total current of the output supplies
VBB
1
/VBB
2
(Continuous current load) free wheel diodes for the deactivation of inductive loads are integrated
≤ 5 minutes (at 100% overload)
≤ 5 minutes (contact +VBB with GND) permanently ≤ 50 % of the nominal current ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0401 / page 4 24.10.2014
PL
19
BasicController / BasicController plus
Control systems
CR0401
Test standards and regulations
CE marking
E1 marking
Electrical tests
Climatic tests
Mechanical tests
Note
Wiring
Abbreviations
Technical data
EN 61000-6-2
EN 61000-6-4
EN 61010-1
UN/ECE-R10
ISO 7637-2
EN 60068-2-30
EN 60068-2-78
EN 60068-2-52
ISO 16750-3
EN 60068-2-6
ISO 16750-3
Electromagnetic compatibility (EMC)
Noise immunity
Electromagnetic compatibility (EMC)
Emission standard
Safety requirements for electrical equipment for measurement, control and laboratory use
Emission standard
Immunity with 100 V/m
Pulse 1, severity level: IV; function state C
Pulse 2a, severity level: IV; function state A
Pulse 2b, severity level: IV; function state C
Pulse 3a, severity level: IV; function state A
Pulse 3b, severity level: IV; function state A
Pulse 4, severity level: IV; function state A
Pulse 5, severity level: III; function state C
(data valid for the 24 V system)
Pulse 4, severity level: III; function state C
(data valid for the 12 V system)
Damp heat, cyclic
Upper temperature 55°C, number of cycles: 6
Damp heat, steady state
Test temperature 40°C / 93% RH,
Test duration: 21 days
Salt spray test
Severity level 3 (motor vehicle) only with installed EC0401 or EC0402 cover
Test VII; Vibration, random
Mounting location: vehicle body
Vibration, sinusoidal
10...500 Hz; 0.72 mm/10 g; 10 cycles/axis
Bumps
30 g/6 ms; 24,000 shocks
The EC declaration of conformity and approvals can be found at: www.ifm.com → data sheet search → CR0401 → More information
A
8 poles
VBB
IN0
IN1
GND
GND
IN2
IN3
VBB
S
S
B
VBB
S
IN4
IN5
GND
GND
IN6
IN7
VBB
S
D = not used
C
VBB
IN8
IN9
GND
GND
IN10
IN11
VBB
S
S
A = analogue
B
H
= binary high side
B
L
= binary low side
FRQ = frequency/pulse inputs
PWM = pulse width modulation
VBB
S
= supply sensors/module
VBB
1
= supply OUT 0...3
VBB
2
= supply OUT 4...7
D E F
OUT0
GND
OUT1
GND
OUT2
GND
OUT3
GND
OUT4
GND
OUT5
GND
OUT6
GND
OUT7
GND
N2
4 poles
VBB
S
GND
CAN2_H
CAN2_L
P/N1
6 poles
VBB
S
VBB
1
VBB
2
GND
CAN1_H
CAN1_L ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0401 / page 5 24.10.2014
20
BasicController / BasicController plus
CR0403
Mobile controller
BasicController
12 inputs
12 outputs
2 CAN interfaces
Programming to IEC 61131-3
8...32 V DC
8,5
12,5
LED
A B C D E
N2
F
P/N1
25,5
18
79,7
112
Technical data
Mechanical data
Housing
Dimensions (H x W x D) without cover with EC0401 cover with EC0402 cover and BasicDisplay
CR0451
Installation
Connection
Inputs
Outputs
Operating voltage, CAN bus
Protection rating
Operating/storage temperature
Weight
Modular control system
Usable as CANopen master or intelligent I/O module plastic housing (black)
163 x 112 x 25.5 mm
163 x 112 x 68 mm
163 x 112 x 73.4 mm
xing by means of 4 M4 screws to DIN 912 or DIN 7984 and 4 tubular rivets to
DIN 7340 (tubular rivets are supplied)
AMP blade male terminals 6.3 mm, to be clipped into place and thus vibrationresistant, protected against reverse polarity contacts AMP timer, CuZn pre-tin-plated core cross-section 0.5...2.5 mm²
3 x 8-pole
3 x 8-pole
1 x 6-pole, 1 x 4-pole
IP 20 (with cover and cable seal IP 54)
-40...85° C / -40...85° C
0.30 kg
Electrical data
Operating voltage
Current consumption
Overvoltage
Undervoltage detection
Undervoltage shutdown
Processor
Memory (total)
Memory allocation
Device monitoring
8...32 V DC
45 mA (at 24 V DC)
36 V for t ≤ 10 s at U
B
≤ 7.8 V at U
B
≤ 7.0 V
Freescale PowerPC, 50 MHz
592 Kbytes RAM / 1536 Kbytes Flash / 1 Kbyte FRAM see BasicController system manual www.ifm.com → data sheet search → e.g. CR0403 → Additional data undervoltage monitoring watchdog function checksum test for program and system excess temperature monitoring ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0403 / page 1 24.10.2014
21
PL
BasicController / BasicController plus
Control systems
CR0403
CAN interfaces 1/2
Baud rate
Communication pro le
Software/programming
Programming system
Inputs
Con gurations
Outputs
Con gurations
Technical data
CAN interface 2.0 A/B, ISO 11898
20 kBit/s...1 MBit/s (Default CAN1: 250 kBit/s, CAN2: 250 kBit/s)
CANopen, CiA DS 301 version 4, CiA DS 401 version 1.4
or SAE J 1939 or free protocol
CODESYS version 2.3 (IEC 61131-3)
12 (con gurable)
Number Version
4
4
4 digital for positive / negative sensor signals analogue (0…10/32 V DC, 0..20 mA, ratiometric) frequency ( ≤ 30 kHz) digital for positive sensor signals resistance measurement (0,016...3.6 k Ω ) digital for positive sensor signals positive sensor signals have diagnostic capabilities
12 (con gurable)
Number Version
2
4
4
2 positive switching (high side)
PWM output (20…250 Hz), 2A, current-controlled 0.02…2 A, diagnosis positive switching (high side)
PWM output (20…250 Hz), 2 A, diagnosis positive switching (high side)
PWM output (20…250 Hz), 1 A positive switching (high side)
PWM output (20…250 Hz), 4 A, diagnosis
B
A
L
/B
FRQ
B
L
H
B
L
B
H
PWM
PWM-I
B
H
PWM
B
H
PWM
B
H
PWM
Status LED
Operating states (preset)
Colour
– orange green red two-colour LED (red/green)
Status Description permanently off no operating voltage
1 x on
5 Hz
2 Hz permanently on application stopped (STOP)
10 Hz
5 Hz initialisation or reset checks no operating system loaded application is running (RUN) application stopped (STOP with error) application stopped due to undervoltage permanently on system fault (fatal error) ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0403 / page 2 24.10.2014
22
Control systems
CR0403
Characteristics of the inputs
Analogue inputs (A)
Connection A: 02, 03, 06, 07
IN0...IN3
can be con gured as:
Digital input (B
L
)
Connection B: 02, 03, 06, 07
IN4…IN7 can be con gured as...
BasicController / BasicController plus
Technical data
● Voltage inputs
Input voltage
Resolution
Accuracy
Input resistance
Input frequency
0...10 V or 0...32 V
12 bits
± 1% FS
65.6 kΩ (0...10 V), 50.7 kΩ (0...32 V)
≤ 500 Hz
● Current inputs, with diagnostic capability
Input current
Resolution
Accuracy
Input resistance
0...20 mA
12 bits
± 1% FS
400 Ω
Input frequency ≤ 500 Hz
At a current of > 23 mA the input is switched to the voltage input!
● Voltage inputs, 0...32 V, ratiometric
Function
Value range
Input resistance
(U
IN
÷ U
B
) x 1000 ‰
0...1000 ‰
50.7 kΩ
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
Diagnosis short circuit
> 0.95 U
B
< 1 V
● Binary voltage inputs for negative sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
● Frequency inputs
Input resistance
Input frequency
Switch-on level
Switch-off level
> 0.7 U
B
< 0.3 U
B
3.2 kΩ
50 Hz
> 0.7 UB
< 0.3 UB
3.2 kΩ
50 Hz
3.2 kΩ
< 30 kHz
> 0.35...0.48 U
< 0.29 U
B
B
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
> 0.7 U
B
< 0.3 U
B
3.2 kΩ
50 Hz
> 0.95 U
< 1 V
B
Diagnosis short circuit
● Resistor input
Measuring range
Accuracy
16…3.6 kΩ
± 3 %
PL ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0403 / page 3 24.10.2014
23
BasicController / BasicController plus
Control systems
CR0403
Digital input (B
L
)
Connection C: 02, 03, 06, 07
IN8…IN11 can be con gured as...
Technical data
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
Diagnosis short circuit
> 0.7 U
B
< 0.3 U
B
3.2 k
< 1 V
Ω
50 Hz
> 0.95 U
B
Characteristics of the outputs
Digital outputs (B
Connection D: 01, 03
OUT0…OUT1
H
, PWM, PWM-I)
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected
Diagnosis via current feedback (wire break / overload)
Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage
Switching current
Load resistance
8...32 V DC
≤
≥
2A
6 Ω (at 12 V DC)
≥ 12 Ω (at 24 V DC)
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
● Current-controlled output
Output frequency
Control range
Setting resolution
Control resolution
20...250 Hz
1…1000 ‰
≤ 2A
20...250 Hz
0.02…2 A
1 mA
2 mA
If only one output is active, the switching current is ≤ 2.5 A.
Max. switch-on current ≤ 11 A
Digital outputs (B
H
, PWM)
Connection D: 05, 07
OUT2…OUT3
Connection F: 01, 03,
OUT8…OUT9
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected
Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage
Switching current
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
8...32 V DC
≤ 2A
20...250 Hz
1…1000 ‰
≤ 2 A
If only one output of the output pair is active, the switching current is ≤ 2.5 A.
Max. switch-on current ≤ 11 A ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0403 / page 4 24.10.2014
24
BasicController / BasicController plus
Control systems
CR0403
Digital outputs (B
Connection E: 01, 03, 05, 07
OUT4…OUT7
H
)
Digital outputs (B
H
, PWM)
Connection F: 05, 07
OUT10…OUT11
Free wheel diodes
Overload protection
(valid for all outputs)
Short-circuit strength
(valid for all inputs and outputs)
Max. total current of the output supplies
VBB
1
/VBB
2
(continuous current load)
Technical data
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected
Switching voltage
Switching current
8...32 V DC
≤ 1 A
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
20...250 Hz
1…1000 ‰
≤ 1 A
Max. switch-on current ≤ 11 A
● Semiconductor outputs, positive switching (high side), short-circuit and overload protected
Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage
Switching current
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
8...32 V DC
≤ 4 A
20...250 Hz
1…1000 ‰
≤ 4 A
Max. switch-on current ≤ 30 A free wheel diodes for the deactivation of inductive loads are integrated
≤ 5 minutes (at 100% overload)
≤ 5 minutes (contact +VBB with GND) permanently ≤ 50 % of the nominal current
PL ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0403 / page 5 24.10.2014
25
BasicController / BasicController plus
Control systems
CR0403
Test standards and regulations
CE marking
E1 marking
Electrical tests
Climatic tests
Mechanical tests
Note
Wiring
Technical data
EN 61000-6-2
EN 61000-6-4
EN 61010-1
UN/ECE-R10
ISO 7637-2
EN 60068-2-30
EN 60068-2-78
Electromagnetic compatibility (EMC)
Noise immunity
Electromagnetic compatibility (EMC)
Emission standard
Safety requirements for electrical equipment for measurement, control and laboratory use
Emission standard
Immunity with 100 V/m
Pulse 1, severity level: IV; function state C
Pulse 2a, severity level: IV; function state A
Pulse 2b, severity level: IV; function state C
Pulse 3a, severity level: IV; function state A
Pulse 3b, severity level: IV; function state A
Pulse 4, severity level: IV; function state A
Pulse 5, severity level: III; function state C
(data valid for the 24 V system)
Pulse 4, severity level: III; function state C
(data valid for the 12 V system)
Damp heat, cyclic
Upper temperature 55°C, number of cycles: 6
Damp heat, steady state
Test temperature 40°C / 93% RH,
Test duration: 21 days
EN 60068-2-52
ISO 16750-3
EN 60068-2-6
Salt spray test
Severity level 3 (motor vehicle) only with installed EC0401 or EC0402 cover
Test VII; vibration, random
Mounting location: vehicle body
Vibration, sinusoidal
10...500 Hz; 0.72 mm/10 g; 10 cycles/axis
ISO 16750-3 Bumps
30 g/6 ms; 24,000 shocks
The EC declaration of conformity and approvals can be found at: www.ifm.com → data sheet search → CR0403 → More information
A
8 poles
VBB
S
IN0
IN1
GND
GND
IN2
IN3
VBB
S
B
VBB
S
IN4
IN5
GND
GND
IN6
IN7
VBB
S
C
VBB
S
IN8
IN9
GND
GND
IN10
IN11
VBB
S
D E
OUT0
GND
OUT1
GND
OUT2
GND
OUT3
GND
OUT4
GND
OUT5
GND
OUT6
GND
OUT7
GND
F
OUT8
GND
OUT9
GND
OUT10
GND
OUT11
GND
N2
4 poles
VBB
S
GND
CAN2_H
CAN2_L
P/N1
6 poles
VBB
S
VBB
1
VBB
2
GND
CAN1_H
CAN1_L
Abbreviations A = analogue
B
H
= binary high side
B
L
= binary low side
FRQ = frequency/pulse inputs
PWM = pulse width modulation
VBB
S
= supply sensors/module
VBB
1
= supply OUT 0...7
VBB
2
= supply OUT 8...11
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0403 / page 6 24.10.2014
26
BasicController / BasicController plus
CR0411
Mobile controller
BasicController plus
8 inputs
8 outputs
2 CAN interfaces
Programming to IEC 61131-3
8...32 V DC
8,5
12,5
LED
A B C D E
N2
F
P/N1
25,5
18
79,7
112
Technical data
Mechanical data
Housing
Dimensions (H x W x D) without cover with EC0401 cover with EC0402 cover and BasicDisplay
CR0451
Installation
Connection
Inputs
Outputs
Operating voltage , CAN bus
Protection
Operating/storage temperature
Weight
Modular control system
Usable as CANopen master or intelligent I/O module plastic housing (black)
163 x 112 x 25.5 mm
163 x 112 x 68 mm
163 x 112 x 73.4 mm
xing by means of 4 M4 screws to DIN 912 or DIN 7984 and 4 tubular rivets to
DIN 7340 (tubular rivets are supplied)
AMP blade male terminals 6.3 mm, to be clipped into place and thus vibrationresistant, protected against reverse polarity contacts AMP timer, CuZn pre-tin-plated core cross-section 0.5...2.5 mm²
2 x 8-pole
2 x 8-pole
1 x 6-pole, 1 x 4-pole
IP 20 (with cover and cable seal IP 54)
-40...85° C / -40...85° C
0.30 kg
Electrical data
Operating voltage
Current consumption
Overvoltage
Undervoltage detection
Undervoltage shutdown
Processor
Memory (total)
Memory allocation
Device monitoring
8...32 V DC
45 mA (at 24 V DC)
36 V for t ≤ 10 s if U
B
≤ 7.8 V if U
B
≤ 7.0 V
Freescale PowerPC, 50 MHz
592 Kbytes RAM / 1536 Kbytes Flash / 1 Kbyte FRAM see BasicController plus system manual www.ifm.com → Data sheet search → e.g. CR0411 → Additional data
Undervoltage monitoring
Watchdog function
Checksum test for program and system
Excess temperature monitoring ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0411 / page 1 24.10.2014
27
PL
BasicController / BasicController plus
Control systems
CR0411
CAN interfaces 1/2
Baud rate
Communication pro le
Software/programming
Programming system
Inputs
Con gurations
Outputs
Con gurations
Technical data
CAN interface 2.0 A/B, ISO 11898
20 Kbits/s...1 Mbit/s (default CAN1: 250 Kbits/s, CAN2: 250 Kbits/s)
CANopen, CiA DS 301 version 4, CiA DS 401 version 1.4
or SAE J 1939 or free protocol
CODESYS version 2.3 (IEC 61131-3)
8 (con gurable)
Number Description
4
4 digital for positive/negative sensor signals analogue (0...10/32 V DC, 0...20 mA, ratiometric) frequency (≤ 30 kHz) digital for positive sensor signals resistance measurement (0.016...30 kΩ) positive sensor signals have diagnostic capabilities
8 (con gurable)
Number Description
4
4 positive switching (high side)
PWM output (20…250 Hz), 2.5 A, current-controlled, 0.02…2.5 A, diagnosis positive switching (high side) negative switching (low side), 4 A
PWM output (20…250 Hz), 4 A, diagnosis current-controlled, 0.02…4 A, diagnosis
H-bridge function
B
A
FRQ
B
R
L
L
/B
H
B
H
PWM
PWM-I
B
H
B
L
PWM
PWM-I
H bridge
Status LED
Operating states (preset)
Abbreviations two-colour LED (red/green)
Colour
– orange green
Red
Status Description permanently off no operating voltage
1 x on
5 Hz
2 Hz permanently on application stopped (STOP)
10 Hz
5 Hz initialisation or reset checks no operating system loaded application running (RUN) application stopped (STOP with error) application stopped due to undervoltage permanently on system error (fatal error)
A
B
H
B
L
FRQ
H
PWM
PWM-I
R
VBB
S
VBB
1
VBB
2
Analogue
Binary high side
Binary low side
Frequency/pulse inputs
H-bridge function
Pulse width modulation
Pulse width modulation, current-controlled
Resistor input
Supply sensors/module supply OUT 0...3
supply OUT 4...7
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0411 / page 2 24.10.2014
28
BasicController / BasicController plus
Control systems
CR0411
Input characteristics
Analogue inputs (A, B
L
/B
H
, FRQ)
Connection A: 02, 03, 06, 07
IN0...IN3
can be con gured as...
Technical data
● Voltage inputs
Input voltage
Resolution
Accuracy
Input resistance
Input frequency
●
0...10 V or 0...32 V
12 bits
± 1% FS
65.6 k Ω current inputs, with diagnostic capability
(0...10 V), 50.7 k
≤ 500 Hz
Ω (0...32 V)
Input current
Resolution
Accuracy
Input resistance
0...20 mA
12 bits
± 1% FS
400 Ω
Input frequency ≤ 500 Hz
At a current of > 23 mA the input is switched to the voltage input!
● Voltage inputs, 0...32 V, ratiometric
Function
Value range
Input resistance
(U
IN
÷ U
B
) x 1000 ‰
0...1000 ‰
50.7 k Ω
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
Diagnosis short circuit
> 0.95 U
B
< 1 V
● Binary voltage inputs for negative sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
● Frequency inputs
Input resistance
Input frequency
Switch-on level
Switch-off level
> 0.7 U
B
< 0.3 U
B
3.2 k Ω
50 Hz
> 0.7 UB
< 0.3 UB
3.2 k Ω
50 Hz
3.2 k
≤
Ω
30 kHz
> 0.35...0.48 U
< 0.29 U
B
B
Digital/resistor inputs (B
L
, R)
Connection B: 02, 03, 06, 07
IN4…IN7 can be con gured as…
● Binary voltage inputs for positive sensor signals
Switch-on level
Switch-off level
Input resistance
Input frequency
Diagnosis wire break
> 0.7 U
B
< 0.3 U
B
3.2 k
< 1 V
Ω
50 Hz
> 0.95 U
B
Diagnosis short circuit
● Resistor input
Measuring current
Input frequency
Measuring range
Accuracy
Diagnosis
Diagnosis short circuit
< 2.0 mA
50 Hz
0.016…30 k Ω
± 2 % FS: 16 Ω ...3 k Ω
± 5 % FS: 3...15 k Ω
± 10 % FS: 15...30 k Ω
> 31 k Ω to VBB ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0411 / page 3 24.10.2014
PL
29
BasicController / BasicController plus
Control systems
CR0411
Output characteristics
Digital outputs
(B
H
, PWM, PWM-I)
Connection D: 01, 03, 05, 07
OUT0…OUT3
Technical data
● Semiconductor outputs, positive-switching (high side)
Short-circuit proof and overload protected
Diagnosis via current feedback (wire break / overload)
Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage
Switching current
Load resistance
5.5...32 V DC
≤ 2.5 A
≥ 4.8 Ω (at 12 V DC)
≥ 9.6 Ω (at 24 V DC)
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
● Current-controlled output
Output frequency
Control range
Setting resolution
Control resolution
20...250 Hz
1…1000 ‰
≤ 2.5 A
20...250 Hz
0.02…2.5 A
1 mA
2 mA
Max. ambient temperature in PWM mode: ≤ 70 °C
Max. switch-on current ≤ 24 A
Digital outputs
(B
H/L
, PWM, PWM-I, H)
Connection E: 01, 03, 05, 07
OUT4…OUT7
Free wheel diodes
Overload protection
(valid for all outputs)
Short-circuit strength
(valid for all inputs and outputs)
Total current per output supply VBB
1
or
VBB
2
● Semiconductor outputs, positive-switching (high side), negative switching (low side), short-circuit and overload protection
Diagnosis via current feedback (wire break / overload)
Diagnosis via voltage feedback, pullup resistance can be deactivated (wire break/ short circuit)
Switching voltage
Switching current
Max. clamp energy
Load resistance
5.5...32 V DC
≤ 4 A
< 3 J (at 25°C)
≥ 3 Ω (at 12 V DC)
≥ 6 Ω (at 24 V DC)
● PWM outputs
Output frequency
Pulse/pause ratio
Switching current
● current-controlled output
Output frequency
Control range
Setting resolution
Control resolution
20...250 Hz
1…1000 ‰
≤ 4 A
20...250 Hz
0.02…4 A
1 mA
2 mA
Max. ambient temperature in PWM mode: ≤ 70 °C
Max. switch-on current ≤ 24 A (high side)
≤ 16 A (low side)
Free wheel diodes for the deactivation of inductive loads are integrated
≤ 5 minutes (at 100% overload)
≤ 5 minutes (contacts +VBB/GND)
≤ 8 A ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0411 / page 4 24.10.2014
30
Control systems
CR0411
Total summation current of the output supply VBB
1
and VBB
2
(continuous current load)
Test standards and regulations
CE marking
E1 marking
Electrical tests
Climatic tests
Mechanical tests
Tests for railway applications
Note
BasicController / BasicController plus
Technical data
≤ 12 A
EN 61000-6-2
EN 61000-6-4
UN/ECE-R10
ISO 7637-2
EN 60068-2-30
EN 60068-2-78
EN 60068-2-52
ISO 16750-3
EN 60068-2-6
ISO 16750-3
EN 50121-3-2
EN 50155 clause 12.2
Electromagnetic compatibility (EMC)
Noise immunity
Electromagnetic compatibility (EMC)
Emission standard
Emission standard
Immunity with 100 V/m
Pulse 1, severity level: IV; function state C
Pulse 2a, severity level: IV; function state A
Pulse 2b, severity level: IV; function state C
Pulse 3a, severity level: IV; function state A
Pulse 3b, severity level: IV; function state A
Pulse 4, severity level: IV; function state B
Pulse 5, severity level: III; function state C
(data valid for the 24 V system)
Pulse 4, severity level: III; function state C
(data valid for the 12 V system)
Damp heat, cyclic
Upper temperature 55°C, number of cycles: 6
Damp heat, steady state
Test temperature 40°C / 93% RH,
Test duration: 21 days
Salt spray test
Severity level 3 (vehicle)
Only with installed EC0401 or EC0402 cover
Test VII; Vibration, random
Mounting location: vehicle body
Vibration, sinusoidal
10...500 Hz; 0.72 mm/10 g; 10 cycles/axis
Bumps
30 g/6 ms; 24,000 shocks
Electromagnetic compatibility (EMC)
Electronic equipment used on rolling stock
The EC declaration of conformity and approvals can be found at: www.ifm.com → Data sheet search → CR0411 → More information
PL ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0411 / page 5 24.10.2014
31
BasicController / BasicController plus
Control systems
CR0411
Wiring
A
8 poles
VBB
IN0
IN1
GND
GND
IN2
IN3
VBB
S
S
B
VBB
S
IN4
IN5
GND
GND
IN6
IN7
VBB
S
C/F = not used
C
Abbreviations
Technical data
D E
OUT0
GND
OUT1
GND
OUT2
GND
OUT3
GND
OUT4
GND
OUT5
GND
OUT6
GND
OUT7
GND
F
A
B
H
B
L
FRQ
H
PWM
PWM-I
R
VBB
S
VBB
1
VBB
2
Analogue
Binary high side
Binary low side
Frequency/pulse inputs
H-bridge function
Pulse width modulation
Pulse width modulation, current-controlled
Resistor input
Supply sensors/module
Supply OUT 0...3
Supply OUT 4...7
N2
4 poles
VBB
S
GND
CAN2_H
CAN2_L
P/N1
6 poles
VBB
S
VBB
1
VBB
2
GND
CAN1_H
CAN1_L ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen We reserve the right to make technical alterations without prior notice!
CR0411 / page 6 24.10.2014
32
BasicController / BasicController plus
9 Konserwacja, naprawa i utylizacja
9.1 Konserwacja
Urządzenie nie zawiera żadnych elementów, które muszą być konserwowane przez użytkownika.
9.2 Czyszczenie powierzchni obudowy
► Należy rozłączyć urządzenie.
► Z kurzu i lekkich zabrudzeń, czyść urządzenie przy użyciu miękkiej, chemicznie nieprzetworzonej, suchej szmatki.
► W przypadku silnych zabrudzeń użyć wilgotnej miękkiej szmatki.
Następujące środki nie nadają się do czyszczenia urządzenia: chemiczne rozpuszczalniki tworzyw sztucznych takie jak denaturat, benzyna, rozcieńczalnik, alkohol, aceton lub amoniak.
Zalecane jest stosowanie ściereczek z mikrofibry, bez dodatków środkó chemicznych.
PL
9.3 Naprawy
► Wadliwe urządzenia mogą być naprawione jedynie przez producenta.
Należy postępować zgodnie z zawartymi instrukcjami (→ 2.4 Ingerencja w urządzenie)
9.4 Utylizacja
► Urządzenie usuwać zgodnie z krajowymi regulacjami środowiskowymi.
10 Dopuszczenia/standardy
Normy i przepisy dotyczące badań i testów (→ 8 Dane techniczne)
Deklaracja zgodności CE i dopuszczenia można odnaleźć pod adresem: www.ifm.com.pl → wyszukiwanie kart katalogowych → np. CR0401 →