EAGLE Free g
Installation – Commissioning – Maintenance
20210126
Installation
The air diffuser is normally suspended from the ceiling.
An M8 pop nut, i.e. a threaded grommet that facilitates installation, is in the centre of the top of the air diffuser.
On the size 315 and 400 air diffusers, there are two M8 pop nuts for more stable mounting, see figure 1 and 3.
Commissioning
Commissioning should be carried out with the diffuser face mounted. Pull the measuring tubes and the damper adjustment cords out of the air diffuser through one nozzle in the diffuser face. Then connect the manometer to the correct measuring tube(s): two blue tubes for supply air and one transparent tube for extract air. The rated coefficient of performance of the air register can be used in a calculation to determine the required commissioning pressure. Conclude commissioning by adjusting the damper to the correct blade position, tie a commissioning knot in the damper cords to indicate the damper position.
See Figure 1.
The K-factor is specified on the product’s identification label and last in these instructions.
Maintenance
• Clean the air diffuser if needed with lukewarm water and dishwashing detergent added.
• The duct system can be accessed and lightly pulling the spring-loaded diffuser front downwards and then tilting, see figure 2.
• Dismantle the perforated air distribution plate located on the inlet as shown in figure 4.
• Loosen the damper in the inlet from its bayonet fastening by rotating to the side.
Length of straight duct
Type of obstruction upstream of
EAGLE Free
One 90° bend
Two 90°bends in the same plane
Two 90° bends in alignment at right angles to one another.
One 45° damper
Length of straight duct upstream of the EAGLE
Free m
2
= 5%
3 ·Ød m
2
= 10%
2 ·Ød
4 ·Ød
4 ·Ød
2 ·Ød
2 ·Ød
6 ·Ød 3 ·Ød
One T-piece 4 ·Ød 3 ·Ød m 2 = accuracy of the method according to NVG’s report T32:1982
Tomelilla
Sweden k-factor
EAGLE Free x
XXX k = XX q = k ⋅ p p = q k
Figure 2. Spring-loaded diffuser front.
FRÅ
NLU
FT /
EXTR
ACT AI
R p q = flow reading l/s p = current pressure reading (Pa) k = commissioning factor q
Figure 1. Installation. Commissioning. Maintenance.
TILLUFT / SUPPLY AIR
TILLUFT / SUPPLY AIR
EAGLE Free
Figure 3a. Alternative installation.
Figure 3b. Extra M8 pop nut, size 315 and 400.
Applies only for size 315 & 400
Figure 4. Dismantling of the perforated air distribution plate.
We recommend wearing gloves as there is a risk of cut injuries to the hands/fingers.
2
Swegon reserves the right to alter specifications. 20210126
EAGLE Free
The number holes in the damper must correspond with the number of holes in the sleeve plate
Figure 5. Damper installation and dismantling.
The number holes in the damper must correspond with the number of holes in the sleeve plate
The damper is turned anticlockwise and pulled out.
We recommend wearing gloves as there is a risk of cut injuries to the hands/fingers.
20210126 Swegon reserves the right to alter specifications.
3
EAGLE Free
Dimensions and weights
Size
100
125
160
200
250
315
400
A B C D E
304 192 118 99 96
380 217 210 124 108
456 252 220 159 126
568 288 230 199 144
568 338 275 249 169
700 388 330 314 194
700 488 350 399 244
Number of nozzles
19
31
42
64
72
98
115
Weight, kg
2,7
3,9
5,5
7,8
8,8
13
15,5
Figure 6. EAGLE Free.
K-factor (COP)
EAGLE F – supply air
Size
100
125 k-factor
4,9
8,3
160
200
250
315
14,6
24,1
36,3
59,7
400 101,0
Number of measuring tubes: 2
EAGLE F – extract air
Size
100
125
160
200
250
315
400 68,4
Number of measuring tubes 1 k-factor
5,7
9,0
15,2
24,3
32,9
49,4
Tube colour
Blue + Blue
Blue + Blue
Blue + Blue
Blue + Blue
Blue + Blue
Blue + Blue
Blue + Blue
Tube colour
Transparent
Transparent
Transparent
Transparent
Transparent
Transparent
Transparent
Nozzle settings – examples
Figure 7. Nozzle settings.
NOTE: Air direction in the figure.
1. Clockwise swirling air discharge (standard)
2. 1-way
3. 2-way
4. 3-way
5. 4-way
6. VK Vertical Concentrated
7. VD Vertical Diffused
!
4
Swegon reserves the right to alter specifications. 20210126