Swegon EXP Free b Circular extract air diff Instructions
Swegon EXP Free b is a diffuser that can be installed on a ceiling. Its threaded grommet enables quick and easy installation. After mounting the device, you can connect your manometer to its measuring tube to determine the required commissioning pressure. To indicate the damper position, you can adjust the damper to the correct blade position and tie a knot in the damper cords during commissioning.
The EXP Free b comes with a perforated air distribution plate that can be easily dismantled. Should you need to clean the device, you can use lukewarm water and dishwashing detergent. To access the duct system, just pull the spring-loaded diffuser face downwards and then tilt it.
Anuncio
Anuncio
EXP
Free b
Installation – Commissioning – Maintenance
20201008
Installation
The air diffuser is normally suspended from the ceiling.
An M8 pop nut, i.e. a threaded grommet that facilitates installation, is provided at the top and in the centre of the air diffuser. On sizes 315 and 400, there are two M8 pop nuts for more stable mounting, see figure 1 and 3.
Commissioning
Commissioning should be carried out with the wall diffuser face mounted. Pull the measuring tubes and damper adjustment cords out of the air diffuser through the hole in the front. Then connect the manometer to the correct measuring tube(s); A transparent measuring tube for extract air. The rated coefficient of performance of the air diffuser can be used in a calculation to determine the required commissioning pressure. Conclude commissioning by adjusting the damper to the correct blade position, tie a commissioning knot in the damper cords to indicate the damper position. See Figure 1.
The K-factor is specified on the product’s identification label and last in these instructions.
Maintenance
• Clean the air diffuser if needed with lukewarm water and dishwashing detergent added.
• The duct system can be accessed and lightly pulling the spring-loaded diffuser face downwards and then tilting, see figure 4.
• Dismantle the perforated air distribution plate located on the inlet as shown in figure 5.
• Loosen the damper in the inlet from its bayonet fastening by rotating to the side.
k-factor
Tomelilla
Sweden
EXP Free x
XXX k = XX q p k p q p q q = measured flow l/s p = current pressure reading (Pa) k = commissioning factor
Figure 1. Installation. Commissioning. Maintenance.
0xD / ±5% k
0xD / ±5%
Figure 2. Length of straight section of duct
FRÅ
NLU
FT /
EXTR
ACT AI
R
2xD / ±10%
EXP Free
Applies only for size 315 & 400.
Figure 3a. Extra M8 pop nut, size 315 and 400. Figure 3b. Alternative Installation.
Figure 4. Spring-loaded front.
Figure 5. Dismantling the distribution plate.
2
Swegon reserves the right to alter specifications. 20201008
We recommend wearing gloves as there is a risk of cut injuries to the hands/fingers.
EXP Free
The number holes in the damper must correspond with the number of holes in the sleeve plate
The number holes in the damper must correspond with the number of holes in the sleeve plate
The damper is turned anticlockwise and pulled out.
Figure 6. Damper installation and dismantling.
We recommend wearing gloves as there is a risk of cut injuries to the hands/fingers.
20201008 Swegon reserves the right to alter specifications.
3
EXP Free
Dimensions and weight
Size
100
125
160
200
250
315
400
A
304
380
456
568
568
700
700
B
192
217
252
288
338
388
488
C
118
210
220
230
275
330
350
D
99
124
159
199
249
314
399
E
96
108
126
144
169
194
244
Weight, kg
2,8
3,7
5,0
7,5
8,5
12,4
15,4
K-factor (COP)
EXP F extract air
Size
100
125
160
200
250
EXP F extract air Colour of the tube
5,3 Transparent
8,6
14,5
Transparent
Transparent
24,1
36,3
Transparent
Transparent
315
400
57,5
82,4
Transparent
Transparent
Number of measuring tubes: 1
NOTE! The blue tubes can be used if the product is converted for supply air with the distributor being replaced with nozzles for COLIBRI Fb and EAGLE Fg.
Figure 7. EXP Free.
4
Swegon reserves the right to alter specifications. 20201008