advertisement
A I R C O N D I T I O N I N G
HYDRONIC HIGH WALL
D1 8
Hydronic Highwall
Contents
1. Introduction ......................................................................... 2
2. Nomenclature .............................................................. 2
3. Product Schedule ....................................................... 3
4. External Appearance .................................................. 3
5. Features....................................................................... 4
6. Specifications ............................................................. 5
7. Dimension ................................................................... 7
8. Service Spaces ........................................................... 7
9. Wiring Diagrams ......................................................... 8
10. Capacity Tables ........................................................ 9
11. Sound Levels .......................................................... 13
12. Exploded View ........................................................ 14
13. Installation ............................................................... 16
14. Controller ................................................................ 29
Hydronic Highwall
1. Introduction
Fan coil unit is a kind of compound device which assemble fan and heat-exchang coil together. Fan coil with fresh air supply system is a main type of center air-conditioner system, so it is an important component of AC devices. Fan coil unit has concealed type and exposed type. A cooling (heating) supply system usually consists of fan coil terminals and chilled water system (heated water system).
Maxa
fan coil is designed and manufactured on the base of advanced technology, and utilize qualified galvanized iron as material. Due to its supper-thin design, it has such advantages: beautiful outlook, space saving, easy installation, etc. And the most obvious advantage is that it can decrease the outlet air Tempdifference as low as possible to make room more comfortable, as well as don’t decrease cooling capacity output. For the large air flow volume design, it can increase room ventilation frequency, supply more flesh air, and balance room temperature distribution. Benefiting from adoption of advanced material and technology, it can effectively decrease the running noise and keep running smoothly. With the advantages above, it can be widely applied in market, hospital, office building, hotel, airport, etc.
2. Nomenclature
M I – 26 A
Cooling capacity (2,6 kW)
Chilled Water Fan Coil Unit
Maxa
2 Introduction
Hydronic Highwall
3. Product Schedule
Model
MI35A
MI35A
MI53A
4. External Appearance
Type
Wall mounted
Air volume
(CFM)
250
400
500
Power supply
220~240V-1Ph-50Hz
Product Schedule 3
Hydronic Highwall
5. Features
New panel supplies more choice for customs.
Multi-connection outlet pipe method: left/right/rear, more flexible for installation.
Left piping
Left back piping
Right back piping
Right piping
Wind direction adjustment can be in horizontal and vertical way for auto swing louver
Horizontal air deflector
Vertical air deflector
Built-in 3-way electromagnetic valve.
Easy maintenance has been realized as the front panel can be removed for easy access.
Remote controller with LCD display is standard, wired controller and central controller are optional.
Four-speed motor with super high speed reserved for more choice.
4 Features
Hydronic Highwall
6. Specifications
Model
Air flow
Cooling
Heating
H/M/L m 3 /h
H/M/L CFM
Capacity
Water flow rate
H/M/L kW
H l/h
Water pressure drop
Capacity
H kPa
H/M/L kW
Water pressure drop H kPa
MI26A
425/360/320
250/210/190
2.63/2.41/2.16
452
29.4
3.36/3.1/2.79
27.3
220-240/1/50
MI35A
680/580/510
400/340/300
3.28/2.83/2.41
564
43.5
4.37/3.73/3.17
40.8
Power supply
Power input
Sound pressure level
Fan motor
Type
Quantity
H
V/ph/Hz
W
H/M/L dB(A)
24
30/24/20
40
37/31/26
Low noise 4-speed fan motor
1
Cross-flow fan
1
Fan
Type
Quantity
Coil
Row
Max. Working pressure
Diameter
Mpa mm
2
1.6
Φ7
915×230×290 Dimensions
Net weight
W×H×D mm kg 13 13.3
Body
Packing
Gross weight
W×H×D mm kg
1020×315×390
16.3 16.7
Pipe
Water inlet/outlet pipe connection
Drain pipe
Inch mm
G3/4"
OD
Φ20
Controller R51/E (standard)
Note:
1. H: high speed; M: medium speed; L: low speed
2. Cooling Conditions: entering water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°CWB.
Heating Conditions: entering water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise is tested in semi-anechoic test room.
Specifications 5
Hydronic Highwall
Specifications
Model
Air flow
Cooling
Heating
H/M/L m 3 /h
H/M/L CFM
Capacity
Water flow rate
H/M/L kW
H l/h
Water pressure drop
Capacity
H kPa
H/M/L kW
Water pressure drop H kPa
Power supply
Power input
Sound pressure level
Fan motor
Type
Quantity
Fan
Coil
Body
H
V/ph/Hz
W
H/M/L dB(A)
Type
Quantity
Row
Max. Working pressure
Diameter
Dimensions
Net weight
Mpa mm
W×H×D mm kg
Packing
Gross weight
W×H×D mm kg
MI42A
850/720/640
500/420/380
4.25/3.85/3.32
731
31.8
5.81/5.17/4.43
30.2
220-240/1/50
50
39/33/28
Low noise 4-speed fan motor
1
Cross-flow fan
1
2
1.6
Φ7
1072×230×315
15.8
1180×315×415
19.4
Pipe
Water inlet/outlet pipe connection
Drain pipe
Inch mm
G3/4"
OD
Φ20
Controller R51/E (standard)
Note:
1. H: high speed; M: medium speed; L: low speed
2. Cooling Conditions: entering water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°CWB.
Heating Conditions: entering water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise is tested in semi-anechoic test room.
6 Specifications
Hydronic Highwall
7. Dimensioni
MI26A MI35A
MI53A
Dimensioni
7
Hydronic Highwall
8. Wiring Diagrams
8 Wiring Diagrams
Hydronic Highwall
10. Capacity Tables
Cooling Capacity:
Remark: EWT:
Enter Water Temp. ( ℃ ); Δ t:
Temperature Difference ( ℃ )
DB:
Dry Bulb Temp. ( ℃ );
WB:
Wet Bulb Temp. ( ℃ );
TC:
Total Cooling Capacity (kW);
SC:
Sensible Cooling Capacity (kW);
WF:
Water Flow (m 3 /h);
WPD:
Water Pressure Drop (kPa)
MI26A
EWT
5
Δ t
Air inlet condition
DB:21 WB:15 DB:26.7 WB:19.4 DB:27 WB:19 DB:29 WB:21 DB:33 WB:25
TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD
3 2.17 1.58 0.62 55.8 3.35 2.02 0.96 132.6 3.28 2.11 0.94 127.2 3.67 1.92 1.05 158.7 4.93 2.39 1.41 287.4
4 2.05 1.49 0.44 27.8 3.22 1.96 0.69 68.9 3.17 2.05 0.68 66.7 3.52 1.86 0.76 82.4 4.78 2.32 1.03 151.9
5 1.89 1.43 0.33 15.2 3.08 1.89 0.53 40.4 3.02 1.98 0.52 38.8 3.39 2.93 0.58 48.7 4.63 2.28 0.80 91.1
6 1.73 1.37 0.25 8.8 2.94 1.84 0.42 25.6 2.89 1.91 0.41 24.6 3.24 1.72 0.46 30.9 4.52 2.20 0.65 60.2
6
7 1.55 1.28 0.19 5.2 2.80 1.75 0.34 17.0 2.74 1.85 0.34 16.2 3.10 1.65 0.38 20.8 4.36 2.13 0.54 41.3
3 1.97 1.49 0.56 45.6 3.16 1.94 0.91 118.0 3.09 2.02 0.89 112.7 3.48 1.84 1.00 143.0 4.74 2.32 1.36 265.7
4 1.83 1.42 0.39 22.1 3.04 1.87 0.65 61.2 2.96 1.95 0.64 58.3 3.34 1.78 0.72 74.1 4.59 2.24 0.99 140.0
5 1.69 1.35 0.29 12.1 2.89 1.80 0.50 35.5 2.83 1.90 0.49 34.1 3.21 1.71 0.55 43.7 4.44 2.16 0.76 83.8
6 1.51 1.29 0.22 6.8 2.75 1.75 0.39 22.3 2.69 1.83 0.39 21.3 3.05 1.63 0.44 27.4 4.33 2.09 0.62 55.2
7 1.33 1.20 0.16 3.8 2.61 1.67 0.32 14.7 2.54 1.78 0.31 14.0 2.91 1.56 0.36 18.4 4.17 2.05 0.51 37.8
3 1.76 1.40 0.50 36.5 2.95 1.84 0.85 102.9 2.89 1.94 0.83 98.5 3.28 1.75 0.94 126.6 4.52 2.20 1.29 240.8
4 1.61 1.34 0.35 17.3 2.83 1.78 0.61 53.2 2.76 1.87 0.59 50.4 3.15 1.69 0.68 65.7 4.40 2.16 0.95 128.7
7
8
9
10
5 1.46 1.28 0.25 9.0 2.69 1.72 0.46 30.7 2.63 1.81 0.45 29.4 2.99 1.62 0.52 38.1 4.25 2.09 0.73 76.8
6 1.28 1.21 0.18 4.9 2.55 1.67 0.36 19.1 2.50 1.75 0.36 18.5 2.86 1.55 0.41 24.1 4.14 2.01 0.59 50.5
7 1.11 1.11 0.14 2.7 2.41 1.59 0.30 12.6 2.33 1.69 0.29 11.8 2.71 1.48 0.33 15.9 3.98 1.94 0.49 34.4
3 1.54 1.32 0.44 28.0 2.75 1.76 0.79 89.4 2.69 1.85 0.77 85.2 3.08 1.65 0.88 111.8 4.33 2.13 1.24 221.0
4 1.39 1.28 0.30 12.8 2.63 1.70 0.57 45.9 2.55 1.81 0.55 43.2 2.93 1.60 0.63 57.0 4.17 2.05 0.90 115.7
5 1.23 1.20 0.21 6.4 2.50 1.63 0.43 26.5 2.42 1.73 0.42 24.9 2.80 1.54 0.48 33.4 4.06 1.97 0.70 70.1
6 1.10 1.10 0.16 3.6 2.33 1.58 0.33 16.1 2.29 1.67 0.33 15.5 2.66 1.46 0.38 21.0 3.91 1.94 0.56 45.1
7 0.96 0.96 0.12 2.0 2.20 1.51 0.27 10.5 2.13 1.61 0.26 9.8 2.49 1.40 0.31 13.5 3.77 1.86 0.46 30.9
3 1.32 1.25 0.38 20.5 2.56 1.69 0.73 77.2 2.49 1.77 0.71 73.0 2.87 1.57 0.82 97.4 4.14 2.05 1.19 202.0
4 1.20 1.20 0.26 9.5 2.41 1.62 0.52 38.7 2.34 1.72 0.50 36.4 2.72 1.51 0.59 49.3 3.98 1.97 0.86 105.5
5 1.10 1.07 0.19 5.2 2.28 1.56 0.39 22.2 2.21 1.66 0.38 20.8 2.59 1.45 0.45 28.6 3.87 1.90 0.67 63.7
6 0.97 0.97 0.14 2.8 2.13 1.50 0.31 13.4 2.06 1.61 0.29 12.5 2.46 1.38 0.35 17.8 3.71 1.86 0.53 40.6
7 0.79 0.79 0.10 1.4 1.97 1.43 0.24 8.4 1.91 1.53 0.23 7.9 2.28 1.32 0.28 11.3 3.58 1.79 0.44 27.8
3 1.16 1.16 0.33 15.9 2.35 1.60 0.67 64.9 2.25 1.70 0.65 59.8 2.67 1.49 0.77 84.3 3.95 1.94 1.13 183.9
4 1.07 1.07 0.23 7.6 2.20 1.54 0.47 32.2 2.13 1.65 0.46 30.0 2.52 1.43 0.54 42.0 3.78 1.90 0.81 95.1
5 0.95 0.95 0.16 3.9 2.06 1.49 0.35 18.0 1.97 1.59 0.34 16.5 2.38 1.37 0.41 24.1 3.67 1.83 0.63 57.1
11
12
13
6 0.82 0.82 0.12 2.0 1.92 1.42 0.27 10.8 1.83 1.53 0.26 9.9 2.23 1.30 0.32 14.6 3.51 1.78 0.50 36.3
7 0.52 0.52 0.06 0.6 1.75 1.36 0.21 6.6 1.67 1.48 0.20 6.0 2.08 1.23 0.26 9.4 3.35 1.71 0.41 24.4
3 1.02 1.02 0.29 12.4 2.12 1.53 0.61 52.9 2.04 1.62 0.59 49.2 2.46 1.41 0.70 71.2 3.72 1.86 1.07 163.7
4 0.94 0.94 0.20 5.8 1.98 1.47 0.43 26.2 1.91 1.56 0.41 24.1 2.32 1.35 0.50 35.7 3.57 1.81 0.77 84.7
5 0.81 0.81 0.14 2.8 1.83 1.42 0.32 14.3 1.75 1.53 0.30 13.0 2.17 1.29 0.37 20.0 3.46 1.75 0.59 50.8
6 0.65 0.65 0.09 1.2 1.67 1.36 0.24 8.2 1.61 1.46 0.23 7.6 2.01 1.22 0.29 11.9 3.30 1.70 0.47 32.1
7 0.44 0.44 0.05 0.4 1.49 1.31 0.18 4.8 1.43 1.43 0.18 4.5 1.85 1.15 0.23 7.4 3.15 1.63 0.39 21.5
3 0.90 0.90 0.26 9.6 1.89 1.45 0.54 42.3 1.80 1.57 0.52 38.4 2.23 1.33 0.64 58.8 3.51 1.79 1.01 145.8
4 0.80 0.80 0.17 4.2 1.75 1.40 0.38 20.4 1.67 1.51 0.36 18.4 2.10 1.27 0.45 29.3 3.37 1.73 0.72 75.3
5 0.69 0.69 0.12 2.0 1.60 1.35 0.28 10.9 1.52 1.46 0.26 9.8 1.95 1.21 0.33 16.1 3.24 1.67 0.56 44.5
6 0.41 0.41 0.06 0.5 1.42 1.31 0.20 6.0 1.41 1.38 0.20 5.9 1.78 1.15 0.26 9.4 3.08 1.62 0.44 28.0
7 0.34 0.34 0.04 0.3 1.26 1.26 0.15 3.4 1.30 1.30 0.16 3.7 1.62 1.08 0.20 5.7 2.93 1.56 0.36 18.6
3 0.78 0.78 0.22 7.1 1.65 1.39 0.47 32.3 1.56 1.51 0.45 28.7 2.01 1.26 0.58 47.8 3.29 1.72 0.94 127.8
4 0.66 0.66 0.14 2.9 1.51 1.34 0.33 15.2 1.46 1.43 0.31 14.2 1.87 1.20 0.40 23.2 3.15 1.65 0.68 65.9
5 0.48 0.48 0.08 1.0 1.35 1.32 0.23 7.8 1.37 1.37 0.23 7.9 1.72 1.14 0.30 12.6 3.01 1.59 0.52 38.5
6 0.32 0.32 0.05 0.3 1.23 1.23 0.18 4.5 1.27 1.27 0.18 4.8 1.55 1.08 0.22 7.1 2.85 1.55 0.41 24.0
7 0.24 0.24 0.03 0.1 1.12 1.12 0.14 2.7 1.17 1.17 0.14 3.0 1.36 1.02 0.17 4.0 2.71 1.48 0.33 15.9
Capacity Tables 9
Hydronic Highwall
Cooling capacity table
EWT
Δ t
MI35A
Air inlet condition
DB:21 WB:15 DB:26.7 WB:19.4 DB:27 WB:19 DB:29 WB:21 DB:33 WB:25
TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD
5
3 2.71 1.97 0.78 82.6 4.18 2.52 1.20 196.2 4.09 2.63 1.17 188.3 4.57 2.40 1.31 234.8 6.15 2.98 1.76 425.2
4 2.55 1.86 0.55 41.1 4.02 2.44 0.86 102.0 3.95 2.55 0.85 98.7 4.39 2.32 0.94 121.9 5.96 2.89 1.28 224.7
5 2.36 1.78 0.41 22.5 3.84 2.36 0.66 59.7 3.77 2.47 0.65 57.4 4.22 3.65 0.73 72.1 5.77 2.84 0.99 134.8
6 2.15 1.70 0.31 13.0 3.67 2.29 0.53 37.9 3.60 2.39 0.52 36.4 4.04 2.15 0.58 45.8 5.63 2.75 0.81 89.1
6
7
8
9
10
11
12
13
7 1.93 1.60 0.24 7.7 3.49 2.18 0.43 25.2 3.41 2.30 0.42 24.0 3.87 2.06 0.48 30.8 5.44 2.65 0.67 61.1
3 2.45 1.86 0.70 67.5 3.94 2.42 1.13 174.6 3.85 2.52 1.10 166.7 4.34 2.29 1.24 211.6 5.92 2.89 1.70 393.1
4 2.28 1.77 0.49 32.7 3.79 2.33 0.81 90.6 3.70 2.44 0.79 86.3 4.17 2.22 0.90 109.6 5.73 2.79 1.23 207.2
5 2.10 1.68 0.36 17.9 3.60 2.25 0.62 52.5 3.53 2.37 0.61 50.4 4.00 2.13 0.69 64.7 5.54 2.70 0.95 124.0
6 1.89 1.61 0.27 10.0 3.43 2.18 0.49 33.1 3.35 2.28 0.48 31.5 3.80 2.04 0.54 40.6 5.40 2.60 0.77 81.7
7 1.66 1.50 0.20 5.7 3.25 2.08 0.40 21.8 3.17 2.22 0.39 20.7 3.63 1.95 0.45 27.2 5.21 2.56 0.64 55.9
3 2.19 1.74 0.63 53.9 3.68 2.30 1.06 152.3 3.60 2.42 1.03 145.7 4.08 2.18 1.17 187.4 5.63 2.75 1.61 356.3
4 2.01 1.68 0.43 25.6 3.53 2.22 0.76 78.8 3.44 2.34 0.74 74.6 3.92 2.11 0.84 97.3 5.49 2.70 1.18 190.4
5 1.82 1.60 0.31 13.4 3.35 2.14 0.58 45.4 3.28 2.26 0.56 43.5 3.73 2.02 0.64 56.4 5.30 2.60 0.91 113.6
6 1.60 1.51 0.23 7.2 3.18 2.08 0.46 28.3 3.12 2.18 0.45 27.3 3.56 1.93 0.51 35.7 5.16 2.51 0.74 74.7
7 1.39 1.39 0.17 4.0 3.01 1.98 0.37 18.6 2.91 2.11 0.36 17.4 3.37 1.85 0.41 23.5 4.97 2.41 0.61 51.0
3 1.92 1.65 0.55 41.5 3.43 2.20 0.98 132.3 3.35 2.30 0.96 126.1 3.84 2.06 1.10 165.5 5.40 2.65 1.55 327.0
4 1.73 1.60 0.37 19.0 3.28 2.13 0.71 68.0 3.18 2.25 0.68 63.9 3.65 2.00 0.79 84.3 5.21 2.56 1.12 171.2
5 1.53 1.50 0.26 9.5 3.11 2.04 0.54 39.2 3.02 2.16 0.52 36.9 3.50 1.92 0.60 49.5 5.06 2.46 0.87 103.7
6 1.38 1.38 0.20 5.3 2.91 1.97 0.42 23.8 2.85 2.08 0.41 22.9 3.32 1.83 0.48 31.0 4.88 2.41 0.70 66.7
7 1.20 1.20 0.15 3.0 2.74 1.88 0.34 15.5 2.66 2.01 0.33 14.5 3.11 1.75 0.38 19.9 4.70 2.32 0.58 45.7
3 1.64 1.56 0.47 30.3 3.19 2.10 0.91 114.3 3.10 2.21 0.89 107.9 3.58 1.96 1.03 144.2 5.16 2.56 1.48 298.9
4 1.49 1.49 0.32 14.0 3.01 2.03 0.65 57.2 2.92 2.14 0.63 53.9 3.40 1.89 0.73 73.0 4.97 2.46 1.07 156.0
5 1.38 1.33 0.24 7.7 2.85 1.94 0.49 32.8 2.76 2.07 0.47 30.8 3.23 1.80 0.56 42.3 4.83 2.37 0.83 94.2
6 1.21 1.21 0.17 4.1 2.66 1.87 0.38 19.9 2.57 2.00 0.37 18.5 3.06 1.72 0.44 26.3 4.62 2.31 0.66 60.0
7 0.98 0.98 0.12 2.0 2.46 1.78 0.30 12.5 2.38 1.91 0.29 11.6 2.85 1.64 0.35 16.7 4.47 2.23 0.55 41.2
3 1.45 1.45 0.42 23.6 2.93 1.99 0.84 96.1 2.81 2.13 0.80 88.5 3.33 1.86 0.96 124.7 4.92 2.41 1.41 272.1
4 1.33 1.33 0.29 11.2 2.75 1.92 0.59 47.6 2.65 2.05 0.57 44.4 3.14 1.78 0.67 62.2 4.72 2.37 1.01 140.7
5 1.19 1.19 0.20 5.7 2.57 1.86 0.44 26.6 2.46 1.99 0.42 24.4 2.97 1.70 0.51 35.7 4.57 2.28 0.79 84.5
6 1.02 1.02 0.15 2.9 2.39 1.77 0.34 16.0 2.28 1.91 0.33 14.6 2.78 1.62 0.40 21.7 4.37 2.22 0.63 53.7
7 0.65 0.65 0.08 0.9 2.18 1.70 0.27 9.8 2.08 1.84 0.26 8.9 2.60 1.54 0.32 13.9 4.18 2.13 0.51 36.0
3 1.28 1.28 0.37 18.3 2.64 1.90 0.76 78.3 2.55 2.03 0.73 72.8 3.06 1.76 0.88 105.3 4.64 2.32 1.33 242.1
4 1.17 1.17 0.25 8.6 2.48 1.84 0.53 38.7 2.38 1.95 0.51 35.7 2.89 1.68 0.62 52.8 4.45 2.26 0.96 125.3
5 1.01 1.01 0.17 4.1 2.29 1.77 0.39 21.1 2.18 1.90 0.38 19.2 2.70 1.60 0.46 29.5 4.31 2.18 0.74 75.2
6 0.80 0.80 0.12 1.8 2.08 1.69 0.30 12.2 2.00 1.82 0.29 11.3 2.51 1.52 0.36 17.7 4.11 2.13 0.59 47.5
7 0.54 0.54 0.07 0.6 1.86 1.63 0.23 7.1 1.79 1.79 0.22 6.6 2.31 1.43 0.28 11.0 3.92 2.04 0.48 31.8
3 1.13 1.13 0.32 14.3 2.36 1.81 0.68 62.7 2.25 1.95 0.64 56.8 2.78 1.66 0.80 87.0 4.38 2.23 1.26 215.7
4 0.99 0.99 0.21 6.2 2.19 1.75 0.47 30.2 2.08 1.89 0.45 27.3 2.62 1.59 0.56 43.3 4.20 2.16 0.90 111.3
5 0.86 0.86 0.15 3.0 2.00 1.69 0.34 16.1 1.89 1.83 0.33 14.5 2.43 1.51 0.42 23.8 4.04 2.08 0.69 65.9
6 0.52 0.52 0.07 0.7 1.77 1.63 0.25 8.8 1.76 1.72 0.25 8.7 2.22 1.43 0.32 13.9 3.84 2.03 0.55 41.5
7 0.43 0.43 0.05 0.4 1.57 1.57 0.19 5.1 1.62 1.62 0.20 5.4 2.02 1.34 0.25 8.4 3.65 1.95 0.45 27.5
3 0.97 0.97 0.28 10.6 2.06 1.73 0.59 47.8 1.95 1.88 0.56 42.5 2.51 1.57 0.72 70.7 4.10 2.14 1.18 189.1
4 0.83 0.83 0.18 4.3 1.89 1.67 0.41 22.5 1.82 1.79 0.39 21.0 2.33 1.49 0.50 34.3 3.93 2.06 0.84 97.5
5 0.60 0.60 0.10 1.4 1.68 1.65 0.29 11.5 1.70 1.70 0.29 11.7 2.14 1.42 0.37 18.6 3.75 1.98 0.65 57.0
6 0.40 0.40 0.06 0.4 1.53 1.53 0.22 6.6 1.59 1.59 0.23 7.1 1.94 1.34 0.28 10.5 3.56 1.93 0.51 35.6
7 0.29 0.29 0.04 0.2 1.40 1.40 0.17 4.0 1.46 1.46 0.18 4.4 1.69 1.27 0.21 5.9 3.37 1.85 0.41 23.5
10 Capacity Tables
Hydronic Highwall
Cooling capacity table
EWT
Δ t
MI53A
Air inlet condition
DB:21 WB:15 DB:26.7 WB:19.4 DB:27 WB:19 DB:29 WB:21 DB:33 WB:25
TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD
5
3 3.51 2.55 1.01 60.4 5.42 3.26 1.55 143.4 5.30 3.40 1.52 137.6 5.92 3.11 1.70 171.6 7.97 3.86 2.29 310.8
4 3.31 2.41 0.71 30.1 5.21 3.16 1.12 74.6 5.12 3.31 1.10 72.1 5.69 3.01 1.22 89.1 7.73 3.74 1.66 164.3
5 3.05 2.31 0.53 16.4 4.98 3.05 0.86 43.7 4.88 3.20 0.84 42.0 5.47 4.73 0.94 52.7 7.48 3.68 1.29 98.6
6 2.79 2.21 0.40 9.5 4.76 2.97 0.68 27.7 4.67 3.09 0.67 26.6 5.23 2.78 0.75 33.5 7.30 3.56 1.05 65.1
6
7
8
9
10
11
12
13
7 2.50 2.07 0.31 5.6 4.53 2.83 0.56 18.4 4.42 2.99 0.54 17.6 5.01 2.67 0.62 22.6 7.05 3.43 0.87 44.7
3 3.18 2.40 0.91 49.4 5.11 3.13 1.46 127.6 4.99 3.27 1.43 121.9 5.62 2.97 1.61 154.7 7.67 3.74 2.20 287.4
4 2.95 2.29 0.63 23.9 4.91 3.02 1.05 66.2 4.79 3.16 1.03 63.1 5.40 2.87 1.16 80.1 7.42 3.62 1.60 151.5
5 2.72 2.18 0.47 13.1 4.67 2.91 0.80 38.3 4.58 3.07 0.79 36.9 5.18 2.76 0.89 47.3 7.18 3.50 1.23 90.6
6 2.45 2.09 0.35 7.3 4.45 2.83 0.64 24.2 4.34 2.95 0.62 23.0 4.92 2.64 0.71 29.7 6.99 3.37 1.00 59.8
7 2.15 1.94 0.26 4.2 4.21 2.70 0.52 15.9 4.11 2.87 0.50 15.2 4.70 2.53 0.58 19.9 6.75 3.31 0.83 40.9
3 2.84 2.26 0.81 39.4 4.77 2.98 1.37 111.3 4.67 3.13 1.34 106.5 5.29 2.82 1.52 137.0 7.30 3.56 2.09 260.5
4 2.61 2.17 0.56 18.7 4.58 2.88 0.98 57.6 4.45 3.03 0.96 54.5 5.08 2.73 1.09 71.1 7.11 3.50 1.53 139.2
5 2.35 2.07 0.41 9.8 4.34 2.77 0.75 33.2 4.25 2.93 0.73 31.8 4.84 2.62 0.83 41.2 6.87 3.37 1.18 83.1
6 2.07 1.96 0.30 5.3 4.12 2.69 0.59 20.7 4.04 2.82 0.58 20.0 4.62 2.50 0.66 26.1 6.68 3.25 0.96 54.6
7 1.80 1.80 0.22 2.9 3.89 2.57 0.48 13.6 3.77 2.74 0.46 12.7 4.37 2.40 0.54 17.2 6.44 3.13 0.79 37.2
3 2.49 2.14 0.71 30.3 4.45 2.85 1.27 96.7 4.34 2.99 1.24 92.2 4.97 2.67 1.43 121.0 6.99 3.43 2.00 239.0
4 2.24 2.07 0.48 13.9 4.25 2.75 0.91 49.7 4.12 2.92 0.89 46.7 4.73 2.59 1.02 61.7 6.75 3.31 1.45 125.2
5 1.99 1.94 0.34 7.0 4.04 2.64 0.69 28.7 3.91 2.80 0.67 27.0 4.53 2.48 0.78 36.2 6.56 3.19 1.13 75.8
6 1.78 1.78 0.26 3.9 3.77 2.56 0.54 17.4 3.70 2.70 0.53 16.7 4.31 2.37 0.62 22.7 6.32 3.13 0.91 48.8
7 1.56 1.56 0.19 2.2 3.55 2.44 0.44 11.3 3.44 2.61 0.42 10.6 4.03 2.27 0.50 14.6 6.10 3.01 0.75 33.4
3 2.13 2.02 0.61 22.1 4.13 2.72 1.18 83.6 4.02 2.86 1.15 78.9 4.64 2.54 1.33 105.4 6.68 3.31 1.92 218.5
4 1.93 1.93 0.42 10.3 3.90 2.62 0.84 41.8 3.78 2.77 0.81 39.4 4.40 2.45 0.95 53.3 6.44 3.19 1.38 114.1
5 1.78 1.73 0.31 5.6 3.69 2.51 0.64 24.0 3.58 2.68 0.61 22.5 4.19 2.34 0.72 30.9 6.26 3.07 1.08 68.9
6 1.56 1.56 0.22 3.0 3.45 2.42 0.49 14.5 3.32 2.59 0.48 13.5 3.97 2.23 0.57 19.2 5.99 3.00 0.86 43.9
7 1.28 1.28 0.16 1.5 3.19 2.31 0.39 9.1 3.08 2.48 0.38 8.5 3.69 2.13 0.45 12.2 5.79 2.89 0.71 30.1
3 1.88 1.88 0.54 17.2 3.79 2.58 1.09 70.2 3.64 2.75 1.04 64.7 4.32 2.40 1.24 91.2 6.38 3.13 1.83 198.9
4 1.72 1.72 0.37 8.2 3.56 2.48 0.76 34.8 3.43 2.66 0.74 32.4 4.07 2.31 0.87 45.5 6.11 3.07 1.31 102.8
5 1.54 1.54 0.26 4.2 3.32 2.40 0.57 19.5 3.18 2.58 0.55 17.8 3.85 2.21 0.66 26.1 5.92 2.96 1.02 61.8
6 1.32 1.32 0.19 2.1 3.10 2.30 0.44 11.7 2.96 2.48 0.42 10.7 3.60 2.10 0.52 15.8 5.67 2.88 0.81 39.3
7 0.84 0.84 0.10 0.6 2.83 2.20 0.35 7.2 2.69 2.39 0.33 6.5 3.37 1.99 0.41 10.2 5.42 2.76 0.67 26.3
3 1.66 1.66 0.47 13.4 3.42 2.47 0.98 57.3 3.30 2.62 0.95 53.2 3.97 2.28 1.14 77.0 6.02 3.01 1.72 177.0
4 1.51 1.51 0.33 6.3 3.21 2.38 0.69 28.3 3.08 2.53 0.66 26.1 3.75 2.18 0.81 38.6 5.77 2.93 1.24 91.6
5 1.31 1.31 0.23 3.0 2.96 2.29 0.51 15.4 2.83 2.47 0.49 14.1 3.50 2.08 0.60 21.6 5.59 2.83 0.96 55.0
6 1.04 1.04 0.15 1.3 2.70 2.20 0.39 8.9 2.59 2.35 0.37 8.2 3.25 1.97 0.47 12.9 5.33 2.75 0.76 34.7
7 0.71 0.71 0.09 0.4 2.40 2.12 0.30 5.2 2.32 2.32 0.28 4.8 2.99 1.86 0.37 8.0 5.08 2.64 0.62 23.2
3 1.46 1.46 0.42 10.4 3.06 2.35 0.88 45.8 2.91 2.53 0.84 41.5 3.61 2.15 1.03 63.6 5.68 2.89 1.63 157.7
4 1.29 1.29 0.28 4.6 2.83 2.27 0.61 22.1 2.69 2.45 0.58 19.9 3.39 2.05 0.73 31.6 5.44 2.80 1.17 81.4
5 1.11 1.11 0.19 2.2 2.59 2.19 0.45 11.8 2.45 2.37 0.42 10.6 3.15 1.96 0.54 17.4 5.23 2.70 0.90 48.2
6 0.67 0.67 0.10 0.5 2.30 2.12 0.33 6.5 2.28 2.23 0.33 6.3 2.88 1.85 0.41 10.2 4.98 2.62 0.71 30.3
7 0.55 0.55 0.07 0.3 2.04 2.04 0.25 3.7 2.10 2.10 0.26 4.0 2.62 1.74 0.32 6.2 4.73 2.52 0.58 20.1
3 1.26 1.26 0.36 7.7 2.67 2.24 0.77 35.0 2.52 2.43 0.72 31.1 3.25 2.03 0.93 51.7 5.32 2.78 1.52 138.3
4 1.07 1.07 0.23 3.2 2.45 2.16 0.53 16.5 2.36 2.32 0.51 15.3 3.02 1.93 0.65 25.0 5.09 2.67 1.09 71.3
5 0.77 0.77 0.13 1.1 2.18 2.13 0.38 8.4 2.21 2.21 0.38 8.6 2.78 1.84 0.48 13.6 4.86 2.57 0.84 41.6
6 0.52 0.52 0.07 0.3 1.99 1.99 0.28 4.8 2.05 2.05 0.29 5.2 2.51 1.74 0.36 7.7 4.61 2.50 0.66 26.0
7 0.38 0.38 0.05 0.1 1.82 1.82 0.22 3.0 1.89 1.89 0.23 3.2 2.20 1.64 0.27 4.3 4.37 2.40 0.54 17.2
Capacity Tables 11
Hydronic Highwall
Cooling capacity modification coefficient table
:
MI26A
Speed
TC SC
High
Mid
1
0.92
1
0.9
TC
1
0.86
MI35A
SC
1
0.83
TC
1
0.91
Low 0.82
Heating Capacity:
Remark:
0.8 0.73 0.7 0.78
Δ t:
Temperature Difference ( ℃ ) ;
TH:
Total Heating Capacity (kW);
WF:
Water Flow (m 3 /h);
WPD:
Water Pressure Drop (kPa)
MI26A
MI42A
SC
1
0.86
0.75
Air inlet temp. (20 ℃ DB)
Water inlet temp. ( ℃ )
Δ t
35 40 45 50 55 60 65 70
TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD
10 1.15 0.10 1.2 1.80 0.15 2.8 2.49 0.21 5.4 3.14 0.27 8.7 3.80 0.33 12.6 4.46 0.38 17.5 5.11 0.44 22.9 5.75 0.49 29.0
8 1.27 0.14 2.2 1.98 0.21 5.4 2.65 0.28 9.6 3.31 0.36 15.0 3.94 0.42 21.3 4.58 0.49 28.8 5.23 0.56 37.4 5.87 0.63 47.2
6 1.47 0.21 5.3 2.14 0.31 11.2 2.78 0.40 18.8 3.45 0.49 29.0 4.10 0.59 41.0 4.74 0.68 54.9 5.35 0.77 69.7 6.03 0.86 88.6
MI35A
Air inlet temp. (20 ℃ DB)
Water inlet temp. ( ℃ )
Δ t
35 40 45 50 55 60 65 70
TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD
10 1.49 0.13 2.1 2.34 0.20 5.1 3.25 0.28 9.7 4.10 0.35 15.5 4.95 0.43 22.7 5.82 0.50 31.3 6.66 0.57 41.0 7.50 0.65 52.0
8 1.66 0.18 4.0 2.58 0.28 9.6 3.46 0.37 17.3 4.31 0.46 26.8 5.14 0.55 38.2 5.98 0.64 51.6 6.82 0.73 67.1 7.66 0.82 84.7
6 1.92 0.28 9.5 2.80 0.40 20.1 3.62 0.52 33.7 4.50 0.65 52.0 5.35 0.77 73.5 6.19 0.89 98.4 6.98 1.00 124.9 7.87 1.13 158.9
MI42A
Air inlet temp. (20 ℃ DB)
Water inlet temp. ( ℃ )
Δ t
35 40 45 50 55 60 65 70
TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD
10 1.99 0.17 1.6 3.13 0.27 3.9 4.33 0.37 7.5 5.46 0.47 11.9 6.60 0.57 17.4 7.76 0.67 24.1 8.88 0.76 31.5 10.00 0.86 40.0
8 2.21 0.24 3.1 3.44 0.37 7.4 4.61 0.50 13.3 5.75 0.62 20.7 6.85 0.74 29.4 7.97 0.86 39.7 9.09 0.98 51.7 10.21 1.10 65.1
6 2.56 0.37 7.3 3.73 0.53 15.4 4.83 0.69 25.9 6.00 0.86 40.0 7.13 1.02 56.5 8.25 1.18 75.7 9.30 1.33 96.1 10.49 1.50 122.3
Heating capacity modification coefficient table
:
MI26A MI35A
Speed
TH TH
High
Mid
Low
1
0.92
0.83
1
0.85
0.73
MI42A
TH
1
0.89
0.76
12 Capacity Tables
Hydronic Highwall
Altitude modification coefficient table:
Altitude (m) TC
500
1000
1500
2000
2500
0.98
0.97
0.95
0.94
0.93
0.91 3000
11. Sound Levels
Test condition
SC
0.95
0.91
0.86
0.82
0.78
0.74
TH
0.95
0.91
0.86
0.82
0.78
0.7
Unit Number
1
3
4
Model
MI26A
MI35A
MI53A
Sound pressure level under three speeds of fan (dB(A))
H
30
37
39
M
24
31
33
L
20
26
28
Sound Levels 13
Hydronic Highwall
12. Exploded View
MI26A MI35A
No.
1
2
3
4
5
6
7
Filter
Evaporator I
Evaporator II
Evaporator Ⅲ
Part Name
Coil temp sensor
Evaporate connect board
Display board ass'y
8
9
Motor
Base pan assembly
10 Motor spud
11 E-part box ass'y
11.1 Dial code switch box cover
11.2 Electric control box seat
11.3 E-Part box cover
11.4 Electric control box soleplate
11.5 Electric control box side board ass'y
11.6 Dial code switch board ass'y
11.7 Main controller ass'y
11.8 Transformer
11.9 Wire joint
11.10 Wire joint, 3p
11.11 Motor capacitor
12 Air outlet frame mount ass'y
13 Louver board
1
1
2
1
1
1
1
Quantity
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
No.
14 Louver
15 Panel dalle
Part Name
16 Panel
17 Panel frame ass'y
18 Stepper motor
19 Screw cover
20 Pipe clamp
21 Drainage pan
22 Bearing base
23 Evaporator left clapboard
24 Water inlet pipe ass'y
25 Water outlet pipe ass'y
26 Three-way valve
27 Control wire for 3-Ways valve
28 Outlet screw pipe ass'y
29 Inlet screw pipe ass'y
30 Discharge valve
31 Cross fan
32 Base pan holder
33 Formaldehyde killer
34 Room Temperature Sensor Ass'y
35 Network matching wire
36 Remote controller
37 Remote controller holder ass'y
Quantity
1
1
1
1
1
1
1
1
1
1
1
2
3
1
1
1
1
1
1
1
1
1
1
1
14 Exploded View
Hydronic Highwall
MI53A
No.
1
2
3
4
5
6
7
Part Name
Filter
Evaporator I
Evaporator II
Evaporator Ⅲ
Coil temp sensor
Evaporate connect board
Cross fan
8
9
10
11
Display board ass'y
Motor
Base pan assembly
Motor spud
12
13
Panel frame ass'y
E-part box ass'y
13.1 Dial code switch box cover
13.2 Electric control box seat
13.3 E-Part box cover
13.4 Electric control box soleplate
13.5 Electric control box side board ass'y
13.6 Dial code switch board ass'y
13.7 Main controller ass'y
13.8 Transformer
13.9 Motor capacitor
13.10 Wire joint, 3p
13.11 Wire joint
1
1
1
2
1
1
1
Quantity
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
21
22
23
24
25
26
27
No.
14
15
16
17
18
19
20
32
33
34
35
36
37
28
29
30
31
Part Name
Air outlet frame mount ass'y
Louver board
Louver
Panel dalle
Panel
Stepper motor
Screw cover
Pipe clamp
Drainage pan
Bearing base
Water inlet pipe ass'y
Water outlet pipe ass'y
Three-way valve
Control wire for 3-Ways valve
Outlet screw pipe ass'y
Inlet screw pipe ass'y
Discharge valve
Evaporator left clapboard
Base pan holder
Formaldehyde killer
Room Temperature Sensor Ass'y
Network matching wire
Remote controller
Remote controller holder ass'y
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
3
Exploded View 15
Hydronic Highwall
13. Installation
13.1 Precautions
Be sure to be in conformity with the local, national and international laws and regulations.
Read "PRECAUTIONS" carefully before installation.
The following precautions include important safty items. Observe them and never forget.
Keep the installation manual in a handy place for future reference.
Before out from factory, FAN COIL UNIT (AIR UNITS) has passed Fan Coil Overpressure Resistant Test,
Statically and Dynamically Balanced Adjustment, Noise Test, Air (cool) Volume Test, Electric Property
Test, Outline Quality Detection.
The safety precautions listed here are divided into two categories. In either case, important safety information is listed which must be read carefully.
Warning:
Failure to observe a warning may result in death.
Caution:
Failure to observe a caution may result in injury or damage to the equipment.
After completing the installation, make sure that the unit operates properly during the start-up operation.
Please instruct the customer on how to operate the unit and keep it maintained.
Warning:
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
Install according to the installation instructions strictly.
If installation is defective, it will cause water leakage, electrical shock and fire.
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
Use the attached accessories parts and specified parts for installation.
Otherwise, it will cause the set to fall, water leakage, electrical shock and fire.
The appliance must be installed 2.3m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation the installation instructions. An independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock fire.
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.
If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
16 Installation
Hydronic Highwall
When carrying out piping connection, take care not to let air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle.
Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances.
Otherwise, it will cause fire or electrical shock.
If the water leaks during installation, ventilate the area immediately.
After completing the installation work, check that the water does not leak.
The cool water in the unit is not lower than 3
℃
, hot water is not higher than 70
℃
. Water in the unit must clean, air quality must meet to the standard of PH=6.5~7.5.
Caution:
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes, lightning rod or telephone ground wire.Incomplete grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires, and then connect the indoor unit wires.
You are not allowed to connect the air conditioner with the power source until wiring and piping the air conditioner is done.
While following the installation instructions, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
This appliance is not intended for use by persons (including children) with reduced physical,sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Don't install the air conditioner in the following locations:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
Installation 17
Hydronic Highwall
13.2 Accessory
Name
1. Screw ST3.9x25 for installation board
2. Plastic expanded tube
Shape Quantity
3
3
Function
Secure the installation board
3. Wrapping tape 1
4. Drain pipe 1
5. Wall conduit cover 1
6. Remote controller
(including operation manual)
1
7. Frame 1 Hold the remote controller
8. Mounting screw (ST2.9 x 10-C-H) 2 Insulation the holder of remote controller
9. Alkaline dry batteries (AM4)
10. Owner's manual
11. Installation manual
2
1
1
12. seel gasket 4 For connecting water pipe
13.3 Remote controller installation
Never throw or beat the controller.
Before installation, operate the remote controller to determine its location in a reception range.
Keep the remote controller at least 1m apart from the nearest TV set or stereoequipment. (it is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
Note that the positive and negative poles are right positions when loading batteries.
This information is subject to changes due to technological improvement without further notices.
18 Installation
Hydronic Highwall
AUTO
COOL
DRY
HEAT
SET TEMPERATURE(°C)
FAN
HIGH
MED
LOW
T E M P
MODE
ON/OFF
FAN
SPEED
SWING
E C O N O M IC
R U N N IN G
TIMER
VENT
RESET
LOCK
CANCEL
Mounting screw B
ST2.9x10-C-H
Remote controller holder
Remote controller
13.4 Indoor unit installation
13.4.1 Installation place
Installation in the following places may cause trouble. If it is unavoidable, please consult with the local dealer.
A place full of machine oil.
A saline place such as coast.
A place full of sulfide gas such as hot-spring resort.
Places where there are high frequency machines such as wireless equipment, welding machine, and medical facility.
A place there is no combustive gases and volatile matter.
A place of special environmental conditions.
Indoor unit installation place
A place where is no obstacle near the inlet and outlet area.
A place which can bear the indoor unit.
A place which is convenient to maintenance.
A place which provides the space around the indoor unit as required right in the diagram.
There is strong electromagnetic wave existing.
A place which is far from heat, steam and inflammable gas.
13.4.2 Drilling a hole and mounting installation board
Installation Board and Its Direction (unit: mm)
MI26A/MI35A type mounting board of indoor unit
MI42A type mounting board of indoor unit
460 730
1070
915 the shape of indoor unit the shape of indoor unit
Fix the installation board.
Install the installation board horizontally on structural parts on the wall with the spaces provided around the plate.
In case of brick, concrete or similar type walls, make 5mm dia. holes on the wall. Insert clip anchors for
Installation 19
Hydronic Highwall appropriate mounting screws.
Fix the installation board on the wall.
Right installation
Tow Screw Tow Screw mounting board of indoor unit horizontal line
False installation mounting board of indoor unit mounting board of indoor unit horizontal line horizontal line
Drilling a hole
Determine the pipe hole position using the installation board, and drill the pipe hole (N95mm) so it slants slightly downward.
Always use a wall hole conduit when piercing metal lath, ply wood or metal plate.
13.4.3 Connective and drain pipe installation
Drain pipe installation
Run the drain hose sloping downward. Do not install the drain hose as illustrated below.
Do not form a rise
Do not put the hose end into water
When connection extended drain hose, insulate the connecting part of extended drain hose with a shield pipe.
Wall
Shield pipe
Extended drain hose
Drain hose
Connection pipe installation
20 Installation
Hydronic Highwall
Left piping
Left back piping
Right piping
Right back piping
For the left-hand and rear-left-hand piping, install the piping as shown. Bend the connective pipe to be laid at 43mm height or less from the wall.
Indoor unit outline
Connective pipe
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. .
..
.
. ..
.
. . .
.
.
.
.
.
.
.
.
.
.
.
.
Fix the end of the connective pipe. (Refer to Tightening Connection in WATER PIPING INSTALLATION)
Cautions:
Connect the indoor unit first, then the outdoor unit. Bend and arrange the pipe carefully.
Do not allow the piping to let out from the back of the indoor unit.
Be careful not to let the drain hose slack.
Insulate both of the auxiliary piping.
Banding the drain hose under the auxiliary pipe.
Piping and bandaging
Wind the connective cable, drain hose and wiring with tape securely, evenly as shown below.
Because the condensed water from rear of the indoor unit is gathered in Pond Box and is piped out of room. Do not put anything else in the box.
Indoor unit
Pond box
Connective cable
.
.
.
.
.
..
..
.
.
..
..
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
Pipe room
Connective pipe
Wrapping belt
Drain hose
13.4.4 Indoor unit installation
Pass the piping through the hole in the wall.
Put the claw at the back of the indoor unit on the hook of the installation board, move the Indoor Unit from side to side to see that it is securely hooked.
Piping can easily lift the indoor unit by the cushioning material between the indoor unit and the wall. Get
Installation 21
Hydronic Highwall it out after finish piping.
Push the lower part of the Indoor Unit up to the wall, and then move the Indoor Unit from side to side, up and down to check if it is hooked securely. hook
Cushioning material
13.5 Water pipe installation
Connection of the water pipe should be done by professionals. Double-span should be used when connecting pipes of Indoor Unit.
At the first debugging, completely expel air from coils via expelling valve.
3-way valve
(4.ports) discharge valve conector
13.6 Wiring chart
The wiring diagram please refers to chapter 8.
Cautions:
The reserved function is indicated in broken line table, users can select it when necessary.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
Take out the faceplate, and then dismantle the display cover faceplate display cover plate
Individual connect the power cord and signal line, adjust the dial switch.
22 Installation
Hydronic Highwall the wire holder of power cord(three-position) the wire holder of signal line
(five-position) display cover plate dial switch
13.6.1 Terminal Board Diagram
Note:
The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system address and network address of indoor units.
Single phase indoor unit
Power supply 220-240V/1 ph/50Hz
Circuit breaker/fuse (A)
Indoor unit power wiring
Ground wiring (mm 2 )
Below 20m
Below 50m
15/15
Twisted pairwire 2.5 mm 2
Twisted pairwire 6 mm 2
2.5
Y/G
XT1
L N
X Y E 1 2
XT3
INDOOR UNIT POWER
220-240V ~ 50Hz
To Central Control Monitor
(CCM)COMM. BUS
Please adopt the shielded twisted-pair wire, and connect the shielded layer to E
TO Timer
DISPLAY BOARD
WIRE CONTROLLER
To wire controller
The reserved wire control function is indicated in broken line table, users can purchase the wire controller when necessary.
13.6.2 Network address setting
Installation 23
Hydronic Highwall
Every air-conditioner in network has only one network address to distinguish each other. Address code of airconditioner in LAN is set by code switch on Network Interface Module (NIM), and the set range is 0-63.
Toggle switch set
Network address code
1 2
ON
1 2
ON
1 2
SW1
ON
1 2
ON
D
E
F 0
1 23
AB 89
67
B
D
E F
A
0 1 2
3
89
7
6
B
D
E
F 0 1
2
3
9A
78
D
E
B
9A
F 0 1 2
3
78
ENC2
~
~
~
~
D
E
F
0 1 2
3
AB
9
678
D
E
F
0 1 2
3
AB
9
678
D
E
F
0 1 2
3
AB
9
678
D
E
F
0 1 2
3
AB
9
678
00~15
16~31
32~47
48-63
Functions of anti-cold wind and anti-hot wind
Toggle switch set
Function selection
SW2
ON
Anti-cold wind OFF,
Anti-hot wind OFF
1 2
ON
1 2
Anti-cold wind OFF,
Anti-hot wind ON
ON
1 2
ON
1 2
Anti-cold wind ON,
Anti-hot wind OFF
Anti-cold wind ON,
Anti-hot wind ON
13.7 Troubleshooting
24 Installation
Hydronic Highwall
Malfunction code
EE
E2
E3
Malfunction
Water-level alarm malfunction
T2 evaporator sensor malfunction
T1 evaporator sensor malfunction
EE: Water-level alarm malfunction
Water-level switch connecting wire between switch and main board gets loose
Exist
Reconnect and ensure that the connection is reliable.
OK
There is something wrong with the water-level switch
OK
Exist
Replace switch
Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment)
Error
Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip.
OK
Mainboard error:
For example, getting wet
OK
Replace mainboard
Installation 25
Hydronic Highwall
E2: T2 evaporator sensor malfunction
T2 Connecting wire between sensor and mainboard gets loose
Exist
Reconnect and ensure that the connection is reliable.
OK
Temperature sensor is shortcircuited or punctured
OK
Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment)
Exist
Error
Replace sensor
Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip.
OK OK
Mainboard error:
For example, getting wet
Replace mainboard
E3: T1 evaporator sensor malfunction
T1 Connecting wire between sensor and mainboard gets loose
Exist
Reconnect and ensure that the connection is reliable.
OK
Temperature sensor is shortcircuited or punctured
OK
Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment)
OK
Exist
Error
Replace sensor
Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip.
Mainboard error:
For example, getting wet
OK
Replace mainboard
26 Installation
Hydronic Highwall
13.7.1 Troubles and causes of air conditioner
If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer.
The operation lamp is flashing rapidly (twice every second)
This lamp is still flashing rapidly after turn off the power and turn on again.
Remote controller receives malfunction or the button does not work well.
A safety device such as a fuse, a breaker frequently actuates.
Water leaks from indoor unit.
Other malfunctions.
Symptoms
Unit does not start
Causes
Power failure.
Power switch is off.
Fuse of power switch may have burned.
Batteries of remote controller exhausted or other problem of controller.
Solution
Wait for the comeback of power.
Switch on the power.
Replace the fuse.
Replace the batteries or check the controller.
Air flowing normally but completely can't cooling
Temperature is not set correctly.
Set the temperature properly.
Low cooling effect
Indoor unit heat exchanger is dirty.
The air filter is dirty.
Inlet of indoor units is blocked.
Doors and windows are open
Sunlight directly shine.
Too much heat resource.
Outdoor temp. is too high.
Clean the heat exchanger.
Clean the air filter.
Eliminate all dirties and make air smooth.
Close doors and windows.
Make curtains in order to shelter from sunshine.
Reduce heat source.
AC cooling capacity reduces (normal).
Low heating effect
Outdoor temperature is lower than 7 C .
Doors and windows not completely closed.
Use heating device.
Close doors and windows.
Installation 27
Hydronic Highwall
13.7.2 Troubles and causes of remote controller
Before asking for serving or repairing, check the following points.
Symptoms Causes
Check whether the MODE indicated on the display is
"AUTO"
The fan speed can not be changed.
Protection against hot wind in cooling mode.
Protection against cold wind in heating mode.
The remote controller signal is not transmitted even when the ON/OFF button is pushed.
Check whether the batteries in the remote controller are exhausted.
The TEMP. indicator does not come on.
Check whether the MODE indicated on the display is
FAN ONLY
The indication on the display disappears after a lapse of time.
Check whether the timer operation has come to an end when the TIMER OFF is indicated on the display.
The TIMER ON indicator goes off after a lapse of certain time.
Check whether the timer operation is started when the TIMER ON is indicated on the display.
Solution
When the automatic mode is selected, the air conditioner will automatically change the fan speed.
Reduce the temperature of inlet in cooling mode rise the temperature of inlet in heating mode.
The power supply is off.
The temperature cannot be set during
FAN mode.
The air conditioner operation will stop up to the set time
No receiving tone sounds from the indoor unit even when the ON/OFF button is pressed.
Check whether the signal transmitter of the remote controller is properly directed to the infrared signal receiver of the indoor unit when the
ON/OFF button is pressed.
Up to the set time, the air conditioner will automatically start and the appropriate indicator will go off.
Directly transmit the signal transmitter of the remote controller to the infrared signal receiver of the indoor unit, and then repeatly push the ON/OFF button twice.
28 Installation
Hydronic Highwall
14. Controller
14.1 Standard Controller : Remote Controller R51/E
14.1.1 Specifications
Model
Rated Voltage
R51/E
3.0V
2.0V Lowest Voltage of CPU Emitting Signal
Reaching Distance
Environment Temperature Range
14.1.2 Performance Features
1. Operating Mode: COOL 、 HEAT 、 DRY 、 FAN and AUTO.
2. Timer Setting Function in 24 hours.
3. Indoor Temperature Setting Range : 17 ℃ ~30 ℃ .
4. LCD display for all functions.
5. Compatible with the former R11.
14.1.3 Function Buttons Introduction
8m (when using 3.0 voltage, it can get 11m)
-5 ℃ ~ 60 ℃
1. TEMP DOWN Button:
Push the TEMP DOWN button to decrease the indoor temperature setting or to adjust the timer in a counter-clockwise direction.
2. MODLE SELECT Button:
Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, HEAT and FAN as the following figure indicates:
3. SWING Button:
Push this switch button to change the louver angle.
Controller 29
Hydronic Highwall
4. RESET Button:
When the RESET button is pushed, all of the current settings are cancelled and the control will return to the initial settings.
5. ECONOMIC RUNNING Button:
Push this button to go into the Energy-Saving operation mode.
6. LOCK Button:
Push this button to lock in all the current settings. To release settings, push again.
7. CANCEL Button:
Push this button to cancel the TIMER settings.
8. TIMER Button:
This button is used to preset the time ON (start to operate) and the time OFF (turn off the operation)
9. ON/OFF Button:
Push this button to start the unit operation. Push the button again to stop the unit operation.
10. FAN SPEED Button:
This button is used for setting fan speed in the sequence that goes from AUTO,
LOW, MED to HIGH, and then back to Auto.
11. TEMP UP Button:
Push this button to increase the indoor temperature setting or to adjust the timer in a counter-clockwise direction.
12. VENT Button:
Push this button to set the ventilating mode. The ventilating mode will operate in the following sequence:
14.1.4 Indicators Introduction
1
2
AUTO
COOL
DRY
HEAT
Display Panel
FAN
HIGH
MED
LOW
6
5
3 4
1.
TRANSMISSION Indicator:
This indicator lights when remote controller transmits signals to indoor unit.
2.
MODE Display:
Shows the current operation mode - AUTO, COOL, DRY or HEAT. HEAT only available for heat pump model.
3.
HEAT PUMP ONLY- LOCK display
is displayed by pushing the LOCK button. Push the LOCK button again to clear display.
4.
TIMER Display:
This display area shows the settings of TIMER. That is, if only the starting time of operation is set, it will display the TIMER ON. If only the turning off time of operation is set, it will display the TIMER OFF. If both operations are set, it will show TIMER ON OFF which indicates you have chosen to set both the starting time and off time.
5.
FAN Display:
When the FAN button is pushed, this signal indicator lights.
6.
Digital Display Area:
This area will show the temperature, and if in the TIMER mode, it will show the ON and OFF settings of the TIMER.
NOTE:
All items are shown in the Fig for the purpose of clear presentation, But during the actual operation only the relative functional items are shown on the display panel.
14.1.5 Operational Guidelines
14.1.5.1 Operating the Remote Controller
30 Controller
Hydronic Highwall
Install / Replace Batteries:
The Remote Controller uses two alkaline dry batteries(R03/Ir03X2).
1. To install batteries, slide back the cover of the battery compartment and install the batteries according to the directions (+and -) shown on the Remote Controller.
2. To replace the old batteries , use the same method as mentioned above.
Note :
1. When replacing batteries, do not use old batteries or a different type battery. This may cause the remote controller to malfunction.
2. If you do not use the remote controller for several weeks remove the batteries. Otherwise battery leakage may damage the remote controller.
3. The average battery life under normal use is about 6 months.
4. Replace the batteries when there is no answering beep from the indoor unit or if the Transmission Indicator light fails to appear.
14.1.5.2 Automatic Operation
When the Air Conditioner is ready for use, switch on the power and the OPERATION indicator lamp on the display panel of the indoor unit starts flashing.
1. Use the MODE select button to select AUTO.
2. Push the TEMP button to set the desired room temperature. The most comfortable temperature settings are between 21 ℃ to 28 ℃ .
3. Push the ON/OFF button to start the air conditioner. The OPERATION lamp on the display panel of the indoor unit lights. The operating mode of AUTO FAN SPEED is automatically set and there are no indicators shown on the display panel of the remote controller.
4. Push the ON/OFF button again to stop the unit.
Note :
1. In the AUTO mode, the air conditioner can logically choose the mode of COOL, FAN, HEAT and DRY by sensing the difference between the actual ambient room temperature and the set temperature on the remote controller..
2. If the AUTO mode is not comfortable for you , the desired mode can be selected manually.
14.1.5.3 COOL, HEAT, and FAN ONLY Operation
1. If the AUTO mode is not comfortable, you may manually override the settings by using COOL, DRY,
HEAT(HEAT PUMP units only), or FAN ONLY modes.
2. Push the TEMP button to set the desired room temperature. When in COOLING mode, the most comfortable settings are 21 ℃ or above. When in HEATING mode, the most comfortable settings are 28 ℃ or below.
3. Push the FAN SPEED to select the FAN mode of AUTO, HIGH, MED or LOW.
4. Push the ON/OFF button. The operation lamp lights and the air conditioner starts to run according to your settings.
5. Push the ON/OFF button again to stop.
Note :
The FAN ONLY mode cannot be used to control the temperature. While in this mode, only steps 1 、 3 and 4 may be performed.
14.1.5.4 Dry Operation
1. Push the MODE button to select DRY.
2. Push the TEMP button to set the desired temperature from 21 ℃ to 28 ℃ .
3. Push the ON/OFF button. The operation lamp lights and the air conditioner starts to run in the DRY mode.
4. Push the ON/OFF button again to stop the unit.
Note :
Due to the difference of the set temperature of the unit and the actual indoor temperature, the Air Conditioner
Controller 31
Hydronic Highwall when in DRY mode will automatically operate many times without running the COOL and FAN mode.
14.1.5.5 Time Operation
PUSH TIMER button to set the on and off times of the unit.
1. To set the STARTING time.
1.1 Please push the CANCEL button to cancel any former settings.
1.2 Push the TIMER button. The remote controller will show the TIMER and the signal "h" is shown on the display panel. The control is now ready to reset the TIMER ON to start the operation.
1.3 Push the TEMP button ( or ) to set desired unit START time .
1.4 After setting the TIMER there will be a one-half second delay before the remote controller transmits the signal to the Air Conditioner. Then, after approximately another 2 seconds, the set temperature will reappear on the digital display.
2. To set the STOPPING time.
2.1 Please press the CANCEL button to cancel any former settings.
2.2 Push the TIMER button and the remote controller will show the last set time for the START operation and the signal "h" will be shown on the display panel. You are now ready to re-adjust the TIMER OFF to stop the operation.
2.3 Push the TEMP button to cancel the TIMER ON setting. The digital area will show "00".
2.4 Push the TIMER button and the remote controller will show the last set time for the STOP operation and the signal "h" will be shown on the display panel. You are now ready to reset the time of the STOP operation.
2.5 Push the TEMP button ( or ) to set the time you want to stop the operation.
2.6 After setting the TIMER there will be a one-half second delay before the remote controller transmits the signals to the Air Conditioner. Then after approximately another 2 seconds, the set temperature will reappear on the digital display.
3. Set the STARTING & STOPPING time
3.1 Please press the CANCEL button to cancel any former settings.
3.2 Push the TIMER button and the remote controller will show the last setting time for START operation and the signal "h" will be shown on the display panel. You are now ready to readjust the TIMER ON to start the operation.
3.3 Push the TEMP button ( or ) to set the time you want to start the operation.
3.4 Push the TIMER button and the remote controller will show the last set time for STOP operation and the signal "h" will be shown on the display panel. You are now ready to reset the time of the STOP operation.
3.5 Push the TEMP button ( or ) to set the time you want to stop the operation.
3.6 After setting the TIMER there will be a one-half second delay before the remote controller transmits the signal to the Air Conditioner. Then, after approximately another 2 seconds ,the set temperature will reappear on the digital display.
Note :
1. Please reset the TIMER after cancelling the former time settings.
2. The setting time is relative time. That is the time set is based on the delay of the current time.
14.2 Optional Controller
32 Controller
Hydronic Highwall
14.2.1 Central Controller: WGC3
Controller 33
Hydronic Highwall
34 Controller
Hydronic Highwall
Liquid crystal matrix display description:
1. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different sizes (as shown in the above figure).
2. The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+,
32+ and 48+ on the left
Side, which indicate the address of the indoor unit. The sum of the horizontal coordinate and the vertical coordinate of the grid is the address of the grid. Each grid corresponds to an indoor unit of this address.
3. One grid is composed of two blocks of different sizes. The status
Indication table is as follows:
Status
Object
Big black block
Small black block
Constantly on
In-service
Power on
Slow blink
Selected
Fast blink
Out of service
Fault of indoor unit Power off
LCD display description
1. Description of the standby page
1) The LCD displays the standby page, 60 air conditioners are in service, of which 28 are powered on and 32 off.
2) In the matrix, the big dots of (00, 16+) and (15,32+) are luminous, and the small dots are not luminous.
It indicates the 32 air conditioners with the addresses from 16 to 47 are powered off.
3) In the matrix, the big and small dots of (09, 48+) and (12, 48+) are not luminous. It indicates the four air conditioners with the addresses from 57 to 60 are outside the network.
4) All other big and small dots in the matrix are luminous. It indicates all other air conditioners are in the network and powered on.
5) The address of the air conditioner is sum of the coordinates. For example, the address of (09, 48+) is
09+48=57.
6) The centralized controller keypad is locked, and the centralized controller communicates with the computer normally.
Controller 35
Hydronic Highwall
Query page description
1) The LCD displays the query page, and the air conditioner with the address of 08 is being queried.
Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor temperature
22°C, set temperature 20°C, cooling mode “lock”.
2) In the matrix, only the big and small black dots at (00, 00+) and (01, 00+) are luminous. It indicates the in-service and power-on status of the air conditioners with the addresses of 00 and 01.
3) The centralized controller communicates with the computer normally.
Setting page description
1) The LCD displays the setting page, and queries the air conditioner with the address of 08. The mode of the air conditioner with the address 08 is: Cooling, strong air, swing on, indoor temperature 28°C, set temperature 22°C, cooling.
2) In the matrix, only the big black dots from (08, 00+) to (16, 00+) are luminous. It indicates the air conditioners with the addresses from 08 to 16 are in service.
3) The centralized controller communicates with the computer normally.
Fault page display description
1) Query the air conditioner with the address of 08 in the query page. The air conditioner with the address of 08 is faulty, and the fault code is 08. The big black dot below (08, 0+) blinks.
2) In the matrix, only the big and small black dots from (00, 00+) to (16, 15+) illuminate. It indicates the inservice status of the air conditioners with the addresses of 00 and 01.
3) The centralized controller communicates with the computer normally.
36 Controller
A I R C O N D I T I O N I N G
Via S. G. LAvoratore 24 (Loc. La Macia)
37040 Arcole
Verona - Italy
Tel. +39 - 045.76.36.585
Fax +39 - 045.76.36.551 www.maxa.it
e-mail: [email protected]
I dati riportati nella presente documentazione sono solamente indicativi. Il costruttore si riserva la facoltà di apportare in qualsiasi momento tutte le modifiche ritenute necessarie.
The data indicated in this manual are purely indicative. The manufacturer reserves the right to modify the data whenever it is considered necessary.
advertisement
Related manuals
advertisement