L-INX ™ Automation Server
User Manual
LOYTEC electronics GmbH
Contact
LOYTEC electronics GmbH
Blumengasse 35
1170 Vienna
AUSTRIA/EUROPE [email protected] http://www.loytec.com
Version 4.0
Document № 88073008
LOYTEC MAKES AND YOU RECEIVE NO WARRANTIES OR CONDITIONS,
EXPRESS, IMPLIED, STATUTORY OR IN ANY COMMUNICATION WITH YOU,
AND
LOYTEC SPECIFICALLY DISCLAIMS ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THIS
PRODUCT IS NOT DESIGNED OR INTENDED FOR USE IN EQUIPMENT
INTENDED FOR SURGICAL IMPLANT INTO THE BODY OR OTHER
APPLICATIONS INTENDED TO SUPPORT OR SUSTAIN LIFE, FOR USE IN
FLIGHT CONTROL OR ENGINE CONTROL EQUIPMENT WITHIN AN
AIRCRAFT, OR FOR ANY OTHER APPLICATION IN WHICH IN THE FAILURE
OF SUCH PRODUCT COULD CREATE A SITUATION IN WHICH PERSONAL
INJURY OR DEATH MAY OCCUR.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of LOYTEC.
LC3020
, L-Chip
, L-Core
, L-DALI
, L-GATE
, L-INX
, L-IOB
, L-IP
,
LPA
, L-Proxy
, L-Switch
, L-Term
, L-VIS
, L-WEB
, and ORION™ stack are trademarks of LOYTEC electronics GmbH.
LonTalk
®
, L ON W ORKS
®
, Neuron
®
, L ON M ARK
®
, LonMaker
®
, i .
LON ®
, and LNS
®
are trademarks of Echelon Corporation registered in the United States and other countries.
L-INX User Manual
Contents
3 LOYTEC
Version 4.0
IP Configuration on the Console .............................................................. 24
IP Configuration via the Web Interface ................................................... 25
IP Configuration via the LCD Display ..................................................... 26
Getting Started with the L-INX Configurator ................................................ 28
Configuration of the L-IOB I/O Modules ....................................................... 29
Connect with an OPC XML-DA Client ........................................................... 36
LOYTEC electronics GmbH
L-INX User Manual 4 LOYTEC
Version 4.0
Resetting Forwarding Tables ................................................................... 46
Terminal Layout and Power Supply ............................................................... 48
Device Information and Account Management ............................................. 53
CEA-709 Configuration .......................................................................... 59
CEA-852 Device Configuration .............................................................. 59
CEA-709 Router Configuration ............................................................... 61
CEA-852 Server Configuration ............................................................... 61
CEA-852 Channel List ............................................................................ 63
BACnet/IP Configuration ........................................................................ 65
LOYTEC electronics GmbH
L-INX User Manual 5 LOYTEC
Version 4.0
BACnet BDT (Broadcast Distribution Table) .......................................... 66
IEC61131 Configuration .......................................................................... 74
Enhanced Communications Test .............................................................. 77
OPC Server Statistics Page ...................................................................... 79
BACnet MS/TP Statistics ......................................................................... 80
Behavior on Value Changes ..................................................................... 86
LOYTEC electronics GmbH
L-INX User Manual 6 LOYTEC
Version 4.0
CEA-709 L-INX Device .......................................................................... 93
Limitations for Local CEA-709 Schedulers............................................. 95
Limitations for CEA-709 Alarm Servers ................................................. 95
Limitations for Local CEA-709 Trends ................................................... 96
BACnet Schedulers and Calendars .......................................................... 97
Registration as an LNS Plug-In ............................................................... 99
CEA-709 Operating Modes ................................................................... 101
Managing Multistate Maps .................................................................... 106
Data Point Naming Rules ...................................................................... 110
Involved Configuration Files ................................................................. 116
LOYTEC electronics GmbH
L-INX User Manual
Version 4.0
7 LOYTEC
Configure without LNS .......................................................................... 117
Configure without LNS Using Bindings ................................................ 118
Adding the L-INX to LNS ..................................................................... 120
Replace a L-INX in LNS........................................................................ 122
Involved Configuration Files ................................................................. 125
Uploading the Configuration .................................................................. 129
Configuration Download ........................................................................ 130
Upload the System Log .......................................................................... 131
Starting as an LNS Plug-In..................................................................... 133
Scanning for Network Variables ............................................................ 134
Importing Network Variables................................................................. 135
Scanning NVs online from the Network ................................................ 136
Select and Use Network Variables ......................................................... 138
Change the NV Allocation ..................................................................... 138
Configuration Download over LNS ....................................................... 142
Enable Legacy NM Mode ...................................................................... 143
Build XIF for Port Interface ................................................................... 144
Upload Dynamic NVs from Device ....................................................... 144
Advanced CEA-709 Configuration ................................................................ 145
Import Devices from XIF Templates ..................................................... 145
Install Unconfigured Devices ................................................................. 145
Using Feedback Data Points .................................................................. 146
Working with Configuration Properties ................................................. 147
Working with UNVTs, UCPTs .............................................................. 148
Scan for BACnet Objects ....................................................................... 149
LOYTEC electronics GmbH
L-INX User Manual
Version 4.0
8 LOYTEC
Use Imported BACnet Objects .............................................................. 151
Export Server Objects to an EDE File ................................................... 153
Map other Properties than Present_Value ............................................. 154
Enable International Character Support ................................................. 155
Create a New Connection ...................................................................... 155
Create Connections from a CSV File .................................................... 157
Connection Overview ............................................................................ 158
Create an E-mail Template .................................................................... 158
Limit E-mail Send Rate ......................................................................... 161
Create a Local Scheduler ....................................................................... 162
Configure Scheduled Data Points .......................................................... 163
Configure Daily Schedules .................................................................... 164
Configure Exception Days ..................................................................... 166
Configure Embedded Exceptions .......................................................... 167
Configure Control Data Points .............................................................. 168
Using the SNVT_tod_event................................................................... 168
Using the Local Scheduler ................................................................ 169
Create an Alarm Server ......................................................................... 169
Create an Alarm Condition .................................................................... 170
Deliver Alarms via E-mail ..................................................................... 172
Configure Trended Data Points ............................................................. 175
Download Trend Data in CSV Format .................................................. 177
Deliver Trend Data via E-mail .............................................................. 177
LOYTEC electronics GmbH
L-INX User Manual 9 LOYTEC
Version 4.0
Remote Scheduler and Calendar ............................................................ 178
Configured Router Mode ....................................................................... 183
Store-and-Forward Repeater .................................................................. 184
Smart Switch Mode with No Subnet Broadcast Flooding ...................... 184
Configuration Server for Managing the IP-852 Channel ....................... 185
Configuration Server Contacts IP-852 Device ....................................... 186
IP-852 Device Contacts Configuration Server ....................................... 186
Using the Built-In Configuration Server ................................................ 186
Firewall and NAT Router Configuration ...................................................... 187
Automatic NAT Configuration .............................................................. 187
Multiple IP-852 Devices behind a NAT: Extended NAT Mode ............ 188
Multiple IP-852 devices behind a NAT: Classic Method ...................... 190
Escrowing Timer (Packet Reorder Timer) ............................................. 193
Dynamic NAT Addresses....................................................................... 194
LOYTEC electronics GmbH
L-INX User Manual 10 LOYTEC
Version 4.0
Create a new L-WEB Project ................................................................ 204
Start a Graphical L-WEB Design .......................................................... 205
Organize L-WEB Projects ..................................................................... 205
Configure the Bridge Locally ................................................................ 207
Export OPC Servers for another PC ...................................................... 207
Import OPC Servers Using the Configurator ......................................... 208
Manually Configure Servers .................................................................. 208
Bridge Timing Parameters ..................................................................... 209
M-Bus Protocol Analyzer ...................................................................... 214
Activating M-Bus Configuration ........................................................... 215
Data Point Manager for M-Bus ............................................................. 215
Scanning the M-Bus Network ................................................................ 219
Network Management Functions ........................................................... 221
Manual Configuration of Data Points .................................................... 225
Importing via Device Templates ........................................................... 227
LOYTEC electronics GmbH
L-INX User Manual 11 LOYTEC
Version 4.0
Creating Device Templates .................................................................... 228
Trending Synchronized Meter Data ....................................................... 232
M-Bus Protocol Analyzer ...................................................................... 233
Modbus Protocol Analyzer .................................................................... 238
Activating Modbus Configuration .......................................................... 238
Data Point Manager for Modbus ............................................................ 239
Using the Configurator for Modbus .............................................................. 242
Modbus Management Functions ............................................................ 242
Manual Configuration of Data Points .................................................... 245
Importing via Device Templates ............................................................ 247
Creating Device Templates .................................................................... 249
Modbus Protocol Analyzer .................................................................... 252
Build and Download the IEC61131 Program ........................................ 260
Usage of NVs, Technology Converters .................................................. 261
IEC61131 Program Cycle Time ............................................................. 262
Based on Network Information .............................................................. 271
LOYTEC electronics GmbH
L-INX User Manual 12 LOYTEC
Version 4.0
Pre-compiled IEC61131 Program ......................................................... 274
Force Update Functionality ................................................................... 274
Using UNVT variables .......................................................................... 275
Create Your Own Data Type ................................................................. 275
Using Persistent Data Points and Markers ............................................. 276
LINX-110 System Registers, System Time ........................................... 276
Schedule and Calendar XML Files ........................................................ 277
Real-Time Keeper Object ...................................................................... 281
Channel Monitor Object ........................................................................ 281
Gateway/PLC Objects ........................................................................... 283
Client Mapping CSV File ...................................................................... 290
EDE Export of BACnet Objects ............................................................ 290
Firmware Update via the Configurator ........................................................ 293
Connecting to the Console ..................................................................... 297
Reset configuration (load factory defaults) ............................................ 298
LOYTEC electronics GmbH
L-INX User Manual 13 LOYTEC
Use of Static, Dynamic, and External NVs on a Device ............................... 301
LINX-10X/11X/20X/21X ...................................................................... 302
LINX-12X/15X/22X .............................................................................. 302
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Abbreviations
14 LOYTEC
Version 4.0
100Base-T .......................... 100 Mbps Ethernet network with RJ-45 plug
Aggregation ........................ Collection of several CEA-709 packets into a single CEA-852 packet
AST .................................... Alarming, Scheduling, Trending
BACnet ............................... Building Automation and Control Network
BOOTP ............................... Bootstrap Protocol, RFC 1497
CEA-709 ............................. Protocol standard for L ON W ORKS networks
CEA-852 ............................. Protocol standard for tunneling CEA-709 packets over IP channels
CN ...................................... Control Network
COV.................................... change-of-value
CR ....................................... Channel Routing
CS ....................................... Configuration Server that manages CEA-852 IP devices
DA ...................................... Data Access (Web service)
DHCP ................................. Dynamic Host Configuration Protocol, RFC 2131, RFC 2132
DIF, DIFE ........................... Data Information Field, Data Information Field Extension
DL ....................................... Data Logger (Web service)
DNS .................................... Domain Name Server, RFC 1034
DST .................................... Daylight Saving Time
GMT ................................... Greenwich Mean Time
IP ........................................ Internet Protocol
IP-852 ................................. logical IP channel that tunnels CEA-709 packets according
CEA-852
LSD Tool ............................ LOYTEC System Diagnostics Tool
MAC ................................... Media Access Control
MD5 ................................... Message Digest 5, a secure hash function, see Internet
RFC 1321
M-Bus ................................. Meter-Bus (Standards EN 13757-2, EN 13757-3)
MS/TP ................................ Master/Slave Token Passing (this is a BACnet data link layer)
NAT .................................... Network Address Translation, see Internet RFC 1631
NV ...................................... Network Variable
OPC .................................... Open Process Control
PLC ..................................... Programmable Logic Controller
RNI ..................................... Remote Network Interface
RTT .................................... Round-Trip Time
RTU .................................... Remote Terminal Unit
SCPT .................................. Standard Configuration Property Type
SL ....................................... Send List
SMTP ................................. Simple Mail Transfer Protocol
SNTP .................................. Simple Network Time Protocol
SSL ..................................... Secure Socket Layer
TLS ..................................... Transport Layer Security
UCPT .................................. User-defined Configuration Property Type
LOYTEC electronics GmbH
L-INX User Manual 15 LOYTEC
UI ........................................ User Interface
UNVT ................................. User-defined Network Variable Type
UTC .................................... Universal Time Coordinated
VIF, VIFE ........................... Value Information Field, Value Information Field Extension
XML .................................... eXtensible Markup Language
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
1 Introduction
17 LOYTEC
1.1 Overview
The L-INX product family consists of high performance, reliable and secure network infrastructure components that implement an embedded automation server. The different models of the L-INX family contain a number of components and network technologies. As protocols on the control network side, the L-INX implements access to BACnet, CEA-709,
Modbus, and M-Bus.
Data from the supported network technologies are available as data points in the automation server. Those data points are freely configurable via configuration software, which provides a fast and easy way to configure the L-INX using online network scans, import/export features or device templates. Data points between different network technologies can be connected to each other for data transfer between those network technologies (gateway).
Data points are also subject to alarming, trending and scheduling (AST) functions of the automation server. The usage of math objects allows basic calculations and the built-in Email client allows the L-INX to transmit E-mails on certain conditions. Generated alarms can be configured to send e-mails to predefined addresses. Alarms can also be stored in a historical alarm log.
Trended data collected by the L-INX is available in CSV format and through a dedicated Web service.
An embedded OPC server exposes a defined set of data points as OPC tags. It implements the OPC XML-DA standard OPC XML-DA 1.01, which lets OPC clients access the data points via Web services. Which native data points are exposed to OPC can also be configured by the configuration software. AST objects such as schedules are exposed as a set of OPC tags. Using the supplied L-WEB designer, users can easily generate a Webbased visualization for the LINX.
The L-INX contains a freely programmable controller that can operate on all L-INX data points. The controller application is developed using the provided IEC-61131 compliant design tool.
The device permanently collects statistical information from the attached network channels
(OPC connections, FT traffic, MS/TP token passing, Ethernet traffic, etc.). Using this data, the device is able to detect problems on these channels (overload, lost tokens, connection
problems, etc.) and warns the system operator via LEDs (see Section 3.4). An intuitive user
interface allows fast and easy network troubleshooting without any additional analysis tools or deep system knowledge.
The built-in Web server allows convenient device configuration through a standard Web browser such as the Internet Explorer or Firefox. The Web interface also provides statistics information for system installation and network troubleshooting. Some L-INX devices also have an LCD display, which provides a quick way to configure basic settings of the device
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 18 LOYTEC via a jog dial. Also available on some L-INX models are ports for SD card memory, USB peripheral bus and a 2-port Ethernet Switch/Hub.
The L-INX is used for:
Exposing data of control network devices from different technologies (CEA-709,
BACnet, Modbus, M-Bus) to data points in the automation server,
Directly connecting I/Os to data points in the automation server,
exposing data points to OPC tags,
visualization of data points with the supplied LOYTEC L-WEB software,
visualization of data points in an OPC XML-DA SCADA package,
running IEC61131 programs to control data points,
automatic meter reading applications via M-Bus and Modbus,
building custom Web pages with active content,
browsing data points on the Web interface or LCD display,
scheduling data points,
trending data points,
generating alarms from data points,
logging alarms,
sending e-mails on alarms, trend logs, or scheduled events.
1.2 CEA-709.1
Version 4.0
L-INX automation server models that have CEA-709 are equipped with an FT port
(CEA-709) and a 100Base-T Ethernet port (CEA-852). CEA-709 L-INX models come with a router option or an RNI option. L-INX models with the router option contain a CEA-709 router between the FT and the IP-852 channel, which can be configured like an L-IP. It includes a configuration server (CS) to manage the IP-852 channel. The L-INX models without the router option contain a remote network interface (RNI) instead of the router for
remote network access. Please refer to Table 1 to learn, which L-INX models have CEA-
709 and the router option.
The CEA-709 L-INX device is fully compliant with ANSI/CEA-709, ANSI/CEA-852-A,
EN 14908. The CEA-709 node, that is going to be commissioned in the network, is always connected to the FT port of the device.
The function of the CEA-709 node is to expose CEA-709 network variables (NVs) and configuration properties (CPs) to data points in the automation server. The configuration software can be run as LNS plug-in or stand-alone. The CEA-709 data points can be bound in the CEA-709 network as NVs or operated as ―external NVs‖. External NVs are polled or explicitly written to without allocating static or dynamic NVs on the device. In this case, address information is supplied by the configuration software by importing e.g., a CSV file.
User-defined network variable types (UNVTs) can be used as dynamic or external NVs.
Configuration properties (CPs) on other devices can be accessed through file transfer. To transfer CPs, the device supports both the L ON M ARK file transfer and the read memory access method. For CPs, the standard SCPTs and user-defined UCPTs are supported. All those CEA-709 data points can be exposed to the automation server.
The CEA-709 L-INX with the router option possesses a router between the CEA-852 interface (IP-852) and the FT interface. The CEA-852 interface can be used to connect the
L-INX to an IP-based high-speed backbone. The L-INX‘s router can be used as a standard
LOYTEC electronics GmbH
L-INX User Manual 19 LOYTEC
CEA-709 configured router or it can be used as a self-learning plug&play router based on the high-performance, well-proven routing core from our L-Switch plug&play multi-port router devices (―smart switch mode‖). The self-learning router doesn‘t need a network management tool for configuration but is a true plug&play and easy to use IP infrastructure component. For a detailed description of the CEA-709 router‘s usage refer to the L-IP User
Manual [1].
The CEA-709 L-INX without the router option can be configured to run either on the
CEA-852 interface (IP-852 mode) or on the FT interface (FT mode). In the FT mode, the device provides a remote network interface (RNI), which appears like a LOYTEC NIC-IP is intended to be used together with the LOYTEC NIC software [3]. The RNI can be utilized for remote access and configuration as well as trouble-shooting with the remote LPA. Please consult our product literature for the LPA-IP to learn more about this IP-based CEA-709 protocol analyzer.
The CEA-709 technology in the L-INX allows for:
Exposing CEA-709 network variables (NVs) and configuration properties (CPs) as data points to the automation server,
supporting standard (SNVT, SCPT) and user-defined (UNVT, UCPT) types,
scheduling CEA-709 network variables,
generating alarms over the L ON M ARK node object,
CEA-709 PC applications (as a CEA-709 network interface),
remote LPA functionality,
communicating on CEA-709 with either FT or IP-852 (IP channel on the
Intranet/Internet),
connecting an FT channel to a high-performance backbone using existing IP infrastructure,
operating as a configuration server for IP-852 devices with the router option.
1.3 BACnet
L-INX automation server models that have BACnet are equipped with an MS/TP port and a
100Base-T Ethernet port (BACnet/IP). BACnet L-INX models with the router option also contain a BACnet router between the MS/TP and the BACnet/IP ports, which can be configured like an LIP-ME201. The router models also include a BACnet broadcast management device (BBMD) to manage BACnet/IP internetworks, which span across IP routers. BACnet models without the router can register as a foreign device (FD) with other
BBMDs. The device is fully compliant with ANSI/ASHRAE 135-2008 (1.5) and ISO
16484-5. Please refer to Table 1 to learn, which L-INX models have BACnet and the router
option.
The BACnet L-INX exposes BACnet server objects and client mappings to data points of the automation server. For client mappings, the BACnet address information is supplied by the configuration software by importing e.g., a CSV file or by performing an online network scan.
The BACnet L-INX models also support the LOYTEC Alarming, Scheduling and Trending
(AST) features in native BACnet objects. The device provides BACnet scheduler/calendar objects, which can directly schedule BACnet server objects, remote BACnet objects or non-
BACnet registers. For alarm conditions the device supports the intrinsic reporting method of
BACnet objects. Trend logs can be uploaded from the device via the native BACnet read range.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 20 LOYTEC
The BACnet L-INX with the router option possesses a BACnet router between the
BACnet/IP port and the MS/TP port. This router can be operated and configured like the
LIP-ME200 from LOYTEC. The BACnet/IP interface can be used to connect the L-INX to an IP-based high-speed backbone. The L-INX also can act as a BBMD for a BACnet/IP network. For a detailed description of the BACnet router‘s usage refer to the LIP-ME201
User Manual [2].
A BACnet L-INX without the router option can be configured to run either on the
BACnet/IP interface or on the MS/TP interface. In BACnet/IP mode, the L-INX can be configured as a foreign device in another BBMD. It does not provide the BBMD functionality itself.
The BACnet technology in the L-INX allows for:
Exposing local BACnet server objects (analog, binary, multi-state) and remote objects
(client mappings) to data points,
scheduling from native BACnet schedule and calendar objects,
trending to native BACnet trend log objects,
generating native BACnet alarms,
communicating with either MS/TP or BACnet/IP,
connecting an MS/TP network to a high-performance backbone using existing IP infrastructure,
operation as a BBMD for a BACnet/IP network with the router option.
1.4 M-Bus
In addition to the basic network technologies the device supports the M-Bus interface according to the standards EN 13757-2 and EN 13757-3. To gain access to the M-Bus network, an external M-Bus interface such as the L-MBUS by LOYTEC must be attached to the device. On devices with a serial port, the M-Bus interface is connected to the serial connector. In this case the user needs to turn M-Bus support on and off via a DIP switch.
On devices without a serial port, the L-MBUS interface must be used and is connected to the extension port (EXT).
Through the M-Bus interface the L-INX can be used to scan the attached M-Bus network for devices, pull M-Bus data points into a configuration, connect those data points to other technologies and expose M-Bus data points to the automation server. All AST functions can be used directly on M-Bus data points. Especially trending data and polling for data on M-
Bus devices has been optimized for automatic meter reading applications.
For debugging purposes a protocol analyzer is included in the firmware and can be operated via the Web-UI and the configuration software. For more information on how to set up the
device for using M-Bus, configuring and using M-Bus data points, refer to Chapter 10.
1.5 Modbus
In addition to the basic network technologies the device supports the Modbus RTU and the
Modbus TCP interface. To gain access to the Modbus network, the appropriate interfaces have to be activated either in the Web UI or in the configuration software. Modbus RTU is operated with 8N1. A Modbus port can either be operated as Modbus master or Modbus slave.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 21 LOYTEC
On some BACnet L-INX models, the Modbus RTU and BACnet MS/TP protocols share the same port. On those models, Modbus RTU can only be used, if BACnet MS/TP is disabled.
Please refer to Table 1 to learn, which BACnet L-INX models have this restriction.
Through the Modbus interface the device can be used to data points to other technologies, and expose Modbus data points to OPC tags. All AST functions can be used directly on
Modbus data points. Especially trending data and polling for data on Modbus devices has been optimized for automatic meter reading applications.
For debugging purposes a protocol analyzer is included in the firmware and can be operated via the Web UI and the configuration software. For more information on how to set up the
device for using Modbus, configuring and using Modbus data points, refer to Chapter 11.
1.6 LIOB
Some L-INX automation server models allow connecting physical I/Os directly to the device via the LIOB I/O modules. Those modules can be stacked up to the L-INX using the
LIOB Connect feature. The connected I/O modules are automatically identified and coupled as data points into the L-INX automation server. LIOB modules are available with digital inputs and outputs, analog inputs and outputs and universal inputs that are configurable.
The I/O modules can be parameterized over the configuration software or the Web UI. All parameterization data is stored on the L-INX and can be reloaded to the LIOB modules when needed. The exchange of modules is detected automatically. For more information on how to setup and use LIOB I/Os please refer to the L-IOB user manual [7].
1.7 L-INX Models
This Section provides an overview of the different L-INX models in Table 1. This table
identifies the different features of the L-INX models. Models that possess a certain feature have a check mark (
) in the respective column. If a feature is not available in the particular model, the column is left blank.
L-INX models with the router option have a CEA-709 router or a BACnet router, respectively. The LINX-151 has both a CEA-709 router between FT and IP and a BACnet router between MS/TP and IP.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 22 LOYTEC
L-INX
Model
Features
CEA-709 Router
CEA-709 RNI
CEA-709 (FT)
CEA-852 (IP)
BACnet Router
BACnet MS/TP
BACnet IP
Modbus RTU
1 1 1 1
1 1 1 1
2 2 2 2
2 2 2 2
3 3 3 3 3 3
Modbus IP
M-Bus
OPC XML-DA Server
PLC (IEC 61131)
LIOB Connect
LIOB FT
LCD Display
Serial Console
SD Card, USB
Ethernet Switch/Hub
1
This model can be configured to have either FT or IP active for CEA-709.
2
This model can be configured to have either MS/TP or IP active for BACnet.
3
Modbus RTU can only be used, if BACnet MS/TP is not active on this model.
Table 1: Available features in different L-INX models
On models without the router option, certain ports can only be used alternatively. On CEA-
709 models this means either as CEA-709 FT or as CEA-852 IP (see note 1 in Table 1). On
BACnet models this means either as BACnet MS/TP or as BACnet IP (see note 2 in Table
1). Some BACnet models have a restriction on Modbus RTU and BACnet MS/TP as they
share the same port. On those models Modbus RTU can only be used, if BACnet MS/TP is
disabled (see note 3 in Table 1).
1.8 Scope
This document covers L-INX devices with firmware version 4.0 and the L-INX
Configurator version 4.0 and higher. The usage of logiCAD itself is beyond the scope of this manual. Please refer to the logiCAD online help in case of additional questions.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 23
2 Quick-Start Guide
LOYTEC
This chapter shows step-by-step instructions on how to configure the LINX-20X for a simple OPC server application.
2.1 Hardware Installation
Connect power (12-35 VDC or 12-24 VAC), the MS/TP network, and the Ethernet cable as
shown in Figure 1. More detailed instructions are shown in Chapter 3.
Important: Do not connect terminal 17 with Earth-ground!
Version 4.0
Power Supply
Ethernet
Figure 1: Basic Hardware Installation.
If the LINX-20X is connected to a BACnet MS/TP network, the MS/TP network segment must be properly terminated with an LT-04 network terminator connected at each of the two ends of the segment media.
LOYTEC electronics GmbH
L-INX User Manual 24 LOYTEC
2.2 Configuration of the LINX
The L-INX can be configured via a console interface, LCD display or via the Web interface.
To configure the device, the following steps have to be performed:
1.
Setup IP configuration (see Sections 2.2.1 and 2.2.2).
2.
Setup BACnet configuration (see Section 2.2.4).
3.
Setup the OPC configuration (see Section 2.3).
Note: This setup procedure assumes the use of the IP interface.
2.2.1 IP Configuration on the Console
Use a PC terminal program with the communication settings set to 38,400 bps / 8 data bits / no parity / 1 stop bit / no handshake. To connect COM1 of the PC to the Console on the device, use a standard null-modem cable with full handshaking. Power up the device or press Return if the device is already running. The following menu should appear on the terminal:
Device Main Menu
================
[1] Show device information
[2] Serial firmware upgrade
[3] System configuration
[5] IP configuration
[7] BACnet configuration
[8] Reset configuration (factory defaults)
[9] Device statistics
[a] Data Points
[0] Reset device
Please choose:
Figure 2: Device Main Menu
Important!
Select ‗5‘ from the device main menu and enter the IP address, netmask, and gateway address. Note that you must use different IP addresses if you are using multiple IP devices in your setup.
IP Configuration Menu
=====================
[1] DHCP : disabled
[2] IP Address : 192.168.24.99
[3] IP Netmask : 255.255.192.0
[4] IP Gateway : 192.168.1.1
[5] Hostname : test-linx200
[6] Domainname : <unset>
[7] DNS Servers : 10.101.17.2
[9] MAC Address : 00:0A:B0:01:0A:4C (factory default)
[0] NTP Servers : <unset> (out-of-sync)
[b] Link Speed & Duplex : Auto Detect
[q] Quit without saving
[x] Exit and save
Please choose:
Figure 3: Enter basic IP settings.
Press ‗x‘ to save the IP settings and reset the device with the main menu item ‗0 ’ in order to let the new IP settings take effect.
The default IP address 192.168.1.254 is only set for configuration access. It must be changed in order to make the device functional.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 25 LOYTEC
You should now be able to connect to the LINX-20X with a Web browser.
2.2.2 IP Configuration via the Web Interface
Optionally to using the console interface one can also use the Web interface to configure the client device. In a Web browser enter the default IP address ‗192.168.1.254‘ of the
LINX-20X. Note that if your PC has an IP address in a subnet other than 192.168.1.xxx, please open a command tool and enter the following route command to add a route to the
LINX-20X.
To Add a Route to the Device
1.
Windows START
Run
2.
Enter ‗cmd‘ and click OK .
3.
In the command window enter the command line route add 192.168.1.254 %COMPUTERNAME%
4.
Then open your Web browser and type in the default IP address 192.168.1.254.
Figure 4: Example Start Screen.
5.
Click on Config in the left menu. You will be asked to enter the administrator password in order to change the IP settings. Enter ‗admin‘ and select Login .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 26 LOYTEC
Figure 5: Enter ‗admin‘ as the default administrator password.
6.
The Config menu opens. Click on IP in the Config menu and enter the IP address, the
IP netmask, and IP gateway for this device as shown in Figure 6.
Figure 6: Enter IP address and gateway.
7.
Press Save Settings and then reset the device by selecting Reset in the highlighted text.
This changes the IP settings of the device.
2.2.3 IP Configuration via the LCD Display
L-INX models with an LCD display can also be configured to their basic settings through jog dial navigation on the LCD UI. Turn the jog dial to navigate between menu items and press to enter a menu or go into selection mode. When in selection mode turn the jog dial to alter the value and press again to quit the selection.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 27
To Set the IP Address on the LCD Display
1.
On the LCD main screen navigate to Device Settings »» .
2.
Then navigate to Device Mgmt »» , TCP/IP Setup »» .
LOYTEC
3.
There navigate to the needed input fields, press and change the value. Press again to set the value. Continue to the next field.
4.
Finally navigate to Save and Reboot and press.
5.
The device reboots with the new IP address.
2.2.4 BACnet Configuration
To configure the BACnet interface, at least the Device ID and the Device Name must be
Version 4.0
Figure 7: BACnet Device Configuration.
The device ID corresponds to the instance number of the BACnet device object. It must be a unique ID on the BACnet internetwork. Also the Device Name must be a unique name on the BACnet internetwork.
By default the BACnet/IP data link layer is used. If the device shall be used with the
BACnet MS/TP data link layer, please refer to Section 4.2.13 for further information.
On devices with an LCD display, the BACnet device ID can also be configured over the
LCD UI.
To Configure the BACnet Device ID over the LCD Display
1.
On the LCD main screen navigate to Device Settings »» .
2.
Then navigate to the menu BACnet »» .
LOYTEC electronics GmbH
L-INX User Manual 28 LOYTEC
3.
In that menu navigate to the ID input for entering the device ID. The field is split into two controls, one for the thousands and one for singles.
4.
After the device ID has been entered the device name is automatically assembled using that device ID, if no other name has been configured on the Web UI.
5.
To let the changes take effect, the device needs to be rebooted. For doing this now you may select the menu item Save and reboot .
2.3 Getting Started with the L-INX Configurator
Before setting up a working IEC61131 program or creating an L-Web visualization, the data points of the L-INX automation server need to be set up. These can be data points of
L-IOB I/Os, network variables, BACnet objects, and other available technologies. Before executing the steps below, install the L-INX Configurator Software from the ‗setup.exe‘.
This file can be downloaded from www.loytec.com
.
To Start a Configurator Project
1.
Start the L-INX Configurator software by selecting Windows Start
Programs
LOYTEC LINX Configurator
LOYTEC LINX Configurator . The application
starts up and displays the data point manager screen as shown in Figure 9.
2.
When the device is online, connect to the device by clicking on the FTP connect speed
button as indicated by the red rectangle in Figure 9.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 29 LOYTEC
Figure 8: L-INX Configurator main screen.
3.
For detailed information on how to create data points out of the network please refer to
Section 6.7 for CEA-709 or 6.9 for BACnet.
2.4 Configuration of the L-IOB I/O Modules
The L-IOB I/O modules can be attached either directly to the LIOB Connect bus or to the
LIOB-FT bus with standard TP/FT-10 wiring rules. Please visit the L-IOB User Manual [7] for detailed hardware installation and terminal configuration instructions.
The L-INX Configurator uses a separate tab to configure the L-IOB devices. The L-IOB device configuration can be done off-line and is shown in the following steps.
To Configure L-IOB I/Os
1.
Add L-IOB devices on the LIOB tab from the supplied L-IOB templates using the Add
Device(s) button
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 30 LOYTEC
Figure 9: Add LIOB devices to the LIOB-Connect bus.
2.
Select a L-IOB device in the tree on the left-hand side and enter names for the terminals by double-clicking into the Name
Figure 10: Change LIOB terminal names for your installation.
3.
Select a terminal and change the object parameters to configure this terminal. You can multi-select terminals and change the parameters for all selected terminals.
Version 4.0
Figure 11: Change LIOB parameters for the selected terminal(s).
4.
On the Datapoints tab the data points for the LIOB terminals have been created. These data points can be used, e.g., in the logiCAD IEC61131 program. For terminal inputs the data point L1_x_UIy_ Input_Read will be used to read an input terminal and for
LOYTEC electronics GmbH
L-INX User Manual 31 LOYTEC terminal outputs the data point L1_x_DOy_ Output_Write will be used to set an output terminal.
5.
After downloading the L-INX configuration into the L-INX device, the L-IOB input and output terminals can be tested with the L-INX Web UI. An example is shown in
Figure 12: Test L-IOB inputs and outputs on the Web UI.
2.5 Getting started with logiCAD
Install the following software components which are available from the website:
Hardlock driver for USB keys. For the logiCAD license, an Aladdin USB key may be used. If no driver for this type of keys is installed on the PC and the software is licensed via the USB key, install this driver first. This driver is not required if a logiCAD softlock license is used.
L-logiCAD setup package. This package installs the logiCAD software, which is needed to design PLC programs for the L-INX device.
L-INX Configurator. This software is required to configure the device to provide the necessary data points to the PLC and integrate the device into the CEA709 network.
A detailed guide how to install the software components described above can be found in
To Start a logiCAD Project
1.
After installing the necessary software components start logiCAD from the L-INX
Configurator by clicking the Start LogiCAD speed button.
2.
The project wizard starts automatically as shown in Figure 13.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 32 LOYTEC
Figure 13: logiCAD project wizard
3.
Select Create new project and press Next .
Version 4.0
Figure 14: Available project templates
4.
Select the project template for the L-INX device (e.g., LINX-11x or LINX-12x).
LOYTEC electronics GmbH
L-INX User Manual 33 LOYTEC
Figure 15: Project name and path
5.
Specify the name of the project and the path where to store the project files, see Figure
Figure 16: Additional information
6.
After specifying additional information the new project is created by pressing the
Finish button.
7.
As shown in Figure 17 below, expand the tree element
Functionplans and double click
Plan_1 in order to start editing the plan.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 34 LOYTEC
Version 4.0
Figure 17: Edit Plan_1
8.
In the new LogiCAD project there are no external variables yet. To expose data points from the L-INX to the logic program, activate the PLC check box of the corresponding data points in the Configurator, e.g., the L-IOB I/Os of the universal input or any other data point such as a network variable, user register or BACnet object.
9.
When you have completed selecting the PLC data points, click the Export variables to
LogiCAD speed button while LogiCAD is running.
10.
The data points now appear as variables in LogiCAD in a folder under the device folder. The folder is named specific to the technology of the data points, e.g. LIOB for
all L-IOB I/Os that are exposed as a PLC variable. An example is shown in Figure 18.
LOYTEC electronics GmbH
L-INX User Manual 35 LOYTEC
Figure 18: Exposed PLC data points appear in LogiCAD
11.
Now the logic can be developed on the function plan.
12.
For later debugging, it is good practice to add online test fields to the drawing, to display the current value of the signals during online test. To do this, right-click on the value output of the left function block and select Create OLT Field from the context
Figure 19: Create online test fields
13.
Place the fields above and below the drawing as shown in Figure 20, then press the
Save button to save your changes.
Version 4.0
Figure 20: Online Test fields
14.
Finally, open the context menu of the LINX-11x device again and select Code
Generation . In the dialog, press the button Start to start the code generation process.
On success, the code generation window reports Errors=0 and Warnings=1.
15.
Close the window by pressing the OK button. Now the compiled IEC61131 program can be downloaded to the device. Right-click the tree element LINX-11x and select
Download from the context menu. A connection dialog will appear and ask for the type of connection and additional information.
LOYTEC electronics GmbH
L-INX User Manual 36 LOYTEC
Figure 21: IEC61131 program download
16.
Select the TCP/IP communication driver and enter the target address as configured in
section 2.2. Start the download process by pressing the
OK button.
2.6 Connect with an OPC XML-DA Client
After the configuration has been downloaded to the L-INX it is ready to serve OPC XML-
DA clients. All data points with the OPC check box activated will be exposed. Connect to the L-INX using the URL http://192.168.24.99/DA , given that 192.168.24.99 is the IP address of the device. Note, that by default, writing to
OPC tags needs basic HTTP authentication using the password for the operator user. This is
‗operator‘ by default.
2.7 Reset to Factory Defaults
In case the password of the device or the PIN code of the LCD UI has been forgotten you may need to reset the device back to factory defaults to gain access again. On the L-INX models 10X, 11X, 20X, 21X press the service button and power-cycle the device. On the
L-INX models with the jog dial press the jog dial and power-cycle the device. Keep the button/jog dial pressed until the port LEDs illuminate orange permanently. Release the button/jog dial within five seconds from that time on to reset the device to factory defaults.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 37
3 Hardware Installation
LOYTEC
3.1 Enclosure
3.1.1 LINX-10X/11X
The LINX-10X/11X enclosure is 107 mm wide for DIN rail mounting, following
Ethernet DIP Switch
1 2 3 4 5 6 7
OPC/PLC
Status
LED
FT, CNIP
Status LEDs
CS/RNI
LED
Ethernet
LEDs
Console
Connector
Power
LED
Status Button and LED
Version 4.0
1 2 3 4 5 6 15 16 17
Figure 22: LINX-10X/11X Enclosure (dimensions in mm).
LOYTEC electronics GmbH
L-INX User Manual 38 LOYTEC
3.1.2 LINX-12X/15X
The LINX-12X/15X enclosure is 159 mm wide for DIN rail mounting, following
Power USB Ethernet
Jog
Dial
OPC, PLC Ethernet
LEDs LEDs
USB,
SD Card
FT
LEDs
Modbus
LED
M-Bus
LED
Figure 23: LINX-12X/15X Enclosure (dimensions in mm).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 39 LOYTEC
3.1.3 LINX-20X/21X
The LINX-20X/21X enclosure is 107 mm wide for DIN rail mounting, following
Ethernet DIP Switch
1 2 3 4 5 6 7
OPC/PLC
Status
LED
MS/TP
LED
BACnet/IP,
BBMD LEDs
Ethernet
LEDs
Console
Connector
Power
LED
Status Button and LED
4 5 6 15 16 17
Figure 24: LINX-20X/21X Enclosure (dimensions in mm).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 40 LOYTEC
3.1.4 LINX-22X
The LINX-22X enclosure is 159 mm wide for DIN rail mounting, following DIN 43 880
Power USB Ethernet
Jog
Dial
OPC, PLC Ethernet
LEDs LEDs
USB,
SD Card
MS/TP
LED
FT
LED
Modbus
LED
M-Bus
LED
Figure 25: LINX-22X Enclosure (dimensions in mm).
3.2 Product Label
3.2.1 LINX-10X/11X
The product label on the side of the LINX-10X/11X contains the following information (see
L-INX order number with bar-code (e.g., LINX-100, LINX-111),
serial number with bar-code (Ser#),
unique node ID and virtual ID of each port (NID1, VID1) with bar-code,
Ethernet MAC ID with bar-code (MAC1).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 41 LOYTEC
Figure 26: LINX-10X/11X product label.
Unless stated otherwise, all bar codes are encoded using ―Code 128‖. An additional label is also supplied with the L-INX for documentation purposes. A virtual ID (VID) is a Node ID on the IP channel.
3.2.2 LINX-12X/15X
The product label on the side of the LINX-12X/15X contains the following information (see
L-INX order number with bar-code (e.g., LINX-120, LINX-151),
serial number with bar-code (Ser#),
unique node ID and virtual ID of each port (NID1, VID1) with bar-code,
Ethernet MAC ID with bar-code (MAC1).
Figure 27: LINX-12X/15X product label.
Unless stated otherwise, all bar codes are encoded using ―Code 128‖. An additional label is also supplied with the L-INX for documentation purposes. A virtual ID (VID) is a Node ID on the IP channel.
3.2.3 LINX-20X/21X
The product label on the side of the LINX-20X/21X contains the following information (see
L-INX order number with bar-code (e.g., LINX-200, LINX-211),
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 42
Date Code, which defines the production week and year,
Serial number with bar-code (Ser#),
MAC address of Ethernet port with bar-code (MAC1).
LOYTEC
Figure 28: LINX-20X/21X product label.
Unless stated otherwise, all bar codes are encoded using ―Code 128‖. An additional label is also supplied with the L-INX for documentation purposes.
3.2.4 LINX-22X
The product label on the side of the LINX-22X contains the following information (see
L-INX order number with bar-code (e.g., LINX-221),
Date Code, which defines the production week and year,
Serial number with bar-code (Ser#),
MAC address of Ethernet port with bar-code (MAC1).
Figure 29: LINX-22X product label.
Unless stated otherwise, all bar codes are encoded using ―Code 128‖. An additional label is also supplied with the L-INX for documentation purposes.
3.3 Mounting
The device comes prepared for mounting on DIN rails following DIN EN 50 022. The device can be mounted in any position. However, an installation place with proper airflow
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 43 LOYTEC must be selected to ensure that the device‘s temperature does not exceed the specified range
3.4 LED signals
3.4.1 Power LED
The power LED lights up green when power is supplied to the power terminals.
3.4.2 Status LED
This LED is available on L-INX models 10X, 11X, 20X, 21X only. The device is equipped
with a red status LED (see Figure 24). This LED is normally off. During boot-up the status
LED is used to signal error conditions (red). If the fall-back image is executed the status
LED flashes red once every second.
3.4.3 OPC LED
The OPC Server LED illuminates green when at least one OPC client is connected to the
OPC server. The LED flickers on OPC XML-DA traffic activity.
3.4.4 PLC LED
The three-color PLC LED indicates the state of the IEC61131 kernel and the IEC61131
program (see Figure 24). Table 2 shows the different LED patterns and their meaning.
Behavior
GREEN permanent
GREEN flashing at 1
Hz
ORANGE
RED
OFF
Description Comment
No IEC61131 program running
Normal condition, IEC61131 program running
IO driver disabled
CPU overload
The IEC61131 kernel is running but either there is no IEC61131 program to execute or the program execution was stopped.
The IEC61131 kernel and program were successfully loaded. The IEC61131 program is executed.
The IO driver is disabled, that is that no updates from or the IEC61131 program were handled.
CPU load exceeded 80%. Modify the
PLC program to reduce CPU load in order to guarantee normal system operation (for example, reduce the cycle time of the program).
IEC61131 kernel not started A problem occurred while starting the
IEC61131 kernel. No IEC61131 features available.
Table 2: PLC LED Patterns
3.4.5 FT Activity LED
The FT port on the device has a three-color LED (green, red, and orange, see Figure 24).
Table 3 shows different LED patterns of the port and their meaning.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 44 LOYTEC
Behavior
GREEN flashing fast
GREEN flashing at 1Hz
RED permanent
RED flashing fast
RED flashing at 1 Hz
(all ports)
ORANGE permanent
ORANGE flashing fast
Description
Traffic
The OPC node or LINX-101‘s router port is unconfigured
Port damaged
Traffic with high amount of errors
Firmware image corrupt
Comment
On the LINX-101 this LED only stops flashing if both, node and router, are commissioned.
Please upload new firmware.
Port disabled
Traffic on port configured as management port
Table 3: CEA-709 Activity LED Patterns. e.g., using LSD Tool e.g., using LSD Tool
3.4.6 MSTP Activity LED
The MS/TP port has a three-color MSTP Activity LED (see Figure 24). Table 4 shows the
different LED patterns of the port and their meaning. A permanent color reflects a state.
Flicker is for 25 ms when there is activity on the MS/TP data link layer.
Behavior
GREEN permanently, flicker off
ORANGE flicker
RED permanent, flicker
GREEN
RED flash fast
Description Comment
Multi-Master, token ok, flicker when traffic
Sole master, flicker when traffic
Token lost state, flicker when transmit attempt
Transmission or receive errors
Table 4: MS/TP Activity LED Patterns.
Normal condition on a multi-master
MS/TP network.
Normal condition on a single-master
MS/TP network.
Cable might be broken.
This indicates bad cabling.
3.4.7 Ethernet Link LED
The Ethernet Link LED lights up green whenever an Ethernet cable is plugged-in and a physical connection with a switch, hub, or PC can be established.
3.4.8 Ethernet Activity LED
The Ethernet Activity LED lights up green for 6 ms whenever a packet is transmitted or received or when a collision is detected on the network cable.
3.4.9 CNIP LED
This LED is available on L-INX models 10X, 11X only. The CNIP LED is a three color
LED that indicates different operating states of the device‘s CEA-852 device.
Green: The CEA-852 device is fully functional and all CEA-852 configuration data
(channel routing info, channel membership list, send list) are up-to-date.
Green flicker: If a valid CEA-709 packet is received or transmitted over the IP channel the
CNIP LED turns off for 50 ms. Only valid CEA-709 IP packets sent to the IP address of the
LINX-10X can be seen. Stale packets or packets not addressed to the device are not seen.
Yellow: Device is functional but some configuration data is not up-to-date (device cannot contact configuration server but has configuration data saved in Flash memory)
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 45 LOYTEC
Red: Device is non-functional because it was rejected from the CEA-852 IP channel or shut-down itself due to an internal error condition.
Off: Device is non-functional because the CEA-852 device has not started. This can be the case if the device uses DHCP and it has not received a valid IP configuration (address) from the DHCP server.
Flashing red at 1 Hz: Device is non-functional because the CEA-852 device is started but has not been configured. Please add the device to a CEA-852 IP channel (register in configuration server).
Flashing green or orange at 1 Hz: The device‘s CEA-709 side of the gateway has not been commissioned yet. The color indicates the CEA-852 IP channel status as described above.
3.4.10 CS/RNI LED
This LED is available on L-INX models 10X, 11X only. On the CEA-709 L-INX with the router option this LED indicates the status of the CEA-852 configuration server. If illuminated green, the configuration server is enabled.
On the CEA-709 L-INX without the router option this LED indicates the remote network interface (RNI) status. The LED is dark, if RNI is not supported by this device or the interface is not enabled. The LED is green, if the RNI is currently in use.
3.4.11 BACnet/IP LED
This LED is available on L-INX models 20X, 21X only. The BACnet/IP LED flashes green for 25 ms when BACnet packets are transmitted or received over the BACnet/IP interface.
3.4.12 BBMD LED
This LED is available on L-INX models 201, 211 only. The BBMD LED is permanent green if BBMD is enabled. Otherwise, it is off.
3.4.13 Wink Action
If the CEA-709 L-INX receives a wink command on any of its network ports, it shows a blink pattern on the CNIP and the CEA-709 activity LEDs. The CEA-709 activity and the
CNIP LED turn green/orange/red (each 0.15 s). This pattern is repeated six times. After that, the CNIP LED flashes orange six times if the wink command was received on the IP channel or the CEA-709 activity LED flashes orange six times if the wink command was received on the CEA-709 channel. After that the device‘s LEDs resume their normal behavior.
3.4.14 Network Diagnostics
The CEA-709 L-INX provides simple network diagnostics via its CEA-709 activity LED:
If the LED does not light up at all, this port is not connected to any network segment or the connected network segment currently shows no traffic.
If the LED is flashing green, the network segment connected to this port is ok.
If the LED is flashing red, a potential problem exists on the network segment connected to this port. This state is referred to as overload condition.
A port overload condition occurs if
the average bandwidth utilization of this port was higher than 70 %, or
the collision rate was higher than 5 %, or
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 46 LOYTEC
more than 15 % CRC errors have occurred on a port with a power-line transceiver, or more than 5 % on a port with a transceiver other than power-line, or
the device was not able to process all available messages.
For a deeper analysis of the reason for the overload condition, it is recommended to use a protocol analyzer (e.g., LOYTEC‘s LPA) or a similar tool. The exact reason of the overload condition can also be determined with the LSD Tool.
3.5 Status Button
The device models 10X, 11X, 20X, and 21X are equipped with a status button (see Figure
24). When pressing the status button shortly during normal operation of the device, it sends
a ―Service Pin Message‖ on the active CEA-709 network port (FT or CEA-852) and a
BACnet ―I Am‖ message on all active BACnet data link layers. As an alternative to pressing
the status button, a service pin message can be sent via the Web interface (see Section 4.1).
The status button can also be used to switch the device back to factory default state. Press the service button and power-cycle the device. Keep the button pressed until the port LEDs illuminate orange permanently. Release the button within five seconds from that time on to reset the device to factory defaults. Alternatively, the device can be switched back to factory
defaults over the console UI (see Section 16.2.2).
3.5.1 Resetting Forwarding Tables
This function is available on CEA-709 L-INX devices with the router option. In order to reset the forwarding tables of the device‘s router, the status button needs to be pressed for at least 20 seconds during normal operation of the device. Resetting forwarding tables means:
Resetting the CEA-709 transceiver to the standard values.
Setting all ports to unconfigured.
Clearing the group forwarding, the subnet/node forwarding and the router domain table when used in smart switch mode.
Clearing the device status and statistic data.
But does not clear the IP address, the CEA-852 configuration settings, and the data point configuration.
All this is done when the button is released. Afterwards a reset is performed to let the changes take effect.
Important:
Important:
If the L-INX is moved from one location to another or if major changes to the configuration of the network are made, it is recommended to reset the configuration to factory defaults.
Wait at least 30 seconds after power-up of the device before pressing the Status Button to ensure that the device has booted properly!
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 47 LOYTEC
3.6 LCD Display and Jog Dial
L-INX models with an LCD display can also be configured to their basic settings through
jog dial navigation on the LCD UI. The main page of the LCD UI is shown in Figure 30. It
displays the device‘s IP address, hostname, CPU load, system temperature and supply voltage.
Below are menu items. Turn the jog dial to navigate between menu items and press to enter a menu or go into selection mode. When in selection mode turn the jog dial to alter the value and press again to quit the selection. The Datapoints »» menu allows browsing through the data points on the L-INX automation server.
Figure 30: Main Screen of the LCD UI.
The Device Settings »» menu allows configuring basic device settings. Navigate to the
Device Mgmt »»
sub-menu, which is displayed in Figure 31.
Version 4.0
Figure 31: Device Management Menu on the LCD UI.
This menu gives you the following options for basic device configuration:
TCP/IP Setup : This menu allows configuring the device‘s IP address.
Send ID messages : When selecting this menu, the device sends out service pin,
BACnet I-Am, and identification broadcasts for finding the device in the L-Config tool on all applicable ports.
Reload config : By choosing this menu, the device performs a quick restart by reloading its configuration only.
Reboot system : By choosing this menu, the device performs a full reboot.
Clear DP config : By choosing this menu, the user can clear the devive‘s entire data point configuration. This is equivalent to the same Web UI function. The IP address as well as other settings needed to reach the device are not deleted.
Factory Defaults : By choosing this menu, the user can reset the entire device to its factory default. Also IP addresses are cleared.
Remote Config : When enabling this option, the LWEB-822 master device manager restores the last saved configuration to the discovered device, if it has no configuration yet. This feature is beneficial when replacing a device.
Change PIN : Alter the default PIN to any 4-digit number to protect certain operations on the LCD UI. The user will be prompted to enter the PIN on protected areas.
LOYTEC electronics GmbH
L-INX User Manual 48 LOYTEC
3.7 DIP Switch Settings
The DIP switch assignment for the device is shown in Table 5. Please leave all switches at
default state. Note, that the L-INX models 12X, 15X, 22X do not have DIP switches.
DIP Switch #
6
7
4
5
1
2
3
Function Factory Default
Must be OFF
Must be OFF
Must be ON
Must be OFF
Must be OFF
Must be OFF
M-Bus enable
Table 5: DIP Switch Settings.
OFF
OFF
ON
OFF
OFF
OFF
OFF
3.8 Terminal Layout and Power Supply
3.8.1 LINX-10X/11X
The LINX-10X/11X provides pluggable screw terminals to connect to the network as well as to the power supply. The screw terminals can be used for wires of a maximum thickness of 2.5 mm
2
/AWG12. The device can either be DC or AC powered.
Terminal
3
4
1
2
5, 6
8
15
16, 17
Function
Modbus RS-485 Ground
Modbus RS-485 Non-Inverting Input
Modbus RS-485 Inverting Input
Earth Ground
CEA-709 A, B of TP/FT-10 Channel Port
Ethernet 100Base-T
Earth Ground
Power Supply 12 – 35 VDC or 12 – 24 VAC ± 10 %
Do not connect terminal 17 to earth ground!
Table 6: LINX-10X/11X Terminals.
3.8.2 LINX-20X/21X
The LINX-20X/21X provides pluggable screw terminals to connect to the network as well as to the power supply. The screw terminals can be used for wires of a maximum thickness of 2.5 mm
2
/AWG12. The device can either be DC or AC powered.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 49
Terminal
4
5
6
8
15
16, 17
Function
BACnet MS/TP / Modbus RS-485 Ground
BACnet MS/TP / Modbus RS-485 Non-Inverting
Input
BACnet MS/TP / Modbus RS-485 Inverting Input
Ethernet 100Base-T
Earth Ground
Power Supply 12 – 35 VDC or 12 – 24 VAC ± 10 %
Do not connect terminal 17 to earth ground!
Table 7: LINX-20X/21X Terminals.
LOYTEC
3.9 Wiring
3.9.1 LINX-10X/11X
The CEA-709 network segment connected to the LINX-10X/11X needs to be terminated
according to the rules found in the specification of the transceiver (see Section 14.1).
Important:
Important:
When using shielded network cables, only one side of the cable should be connected to earth ground. Thus, the shield must be connected to earth ground either at the
LINX-10X terminals or somewhere else in the network.
Never connect terminal 17 to earth ground!
Power Supply
Ethernet
Figure 32: Connecting the LINX-10X/11X.
3.9.2 LINX-20X/21X
If BACnet over MS/TP is enabled, the MS/TP network segment must be properly terminated with an LT-04 network terminator connected at each of the two ends of the segment media.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Important:
50 LOYTEC
When using 2-wire MS/TP, earth ground must be connected to both terminal 15 and 16
(see Figure 33a). Never connect terminal 17 to earth ground!
Power Supply
2-wire
MS/TP
Power Supply 3-wire
MS/TP
Ethernet Ethernet
(a) (b)
Figure 33: Connecting the LINX-20X/21X: (a) 2-wire MS/TP, (b) 3-wire MS/TP.
3.9.3 LINX-12X/15X
The terminals and wiring information for the LINX-12X/15X can be seen in Figure 34. The
CEA-709 network segment connected to the LINX-10X/11X needs to be terminated
according to the rules found in the specification of the transceiver (see Section 14.1).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 51 LOYTEC
Figure 34: Connecting the LINX-12X/15X.
3.9.4 LINX-22X
The terminals and wiring information for the LINX-22X can be seen in Figure 35. If
BACnet over MS/TP is enabled, the MS/TP network segment must be properly terminated with an LT-04 network terminator connected at each of the two ends of the segment media.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 52 LOYTEC
Figure 35: Connecting the LINX-22X.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
4 Web Interface
53 LOYTEC
The L-INX comes with a built-in Web server and a Web interface to configure the L-INX and extract statistics information. The Web interface allows configuring the IP settings,
CEA-709, BACnet and other configuration settings.
4.1 Device Information and Account Management
In a Web browser, enter the default IP address 192.168.1.254 of the device. Note that if your PC has an IP address in a subnet other than 192.168.1.xxx, you must open a command tool and enter the following route command to add a route to the device.
To Add a Route to the Device
1.
Windows START
Run
2.
Enter ‗cmd‘ and click OK .
3.
In the command window enter the command line route add 192.168.1.254 %COMPUTERNAME%
4.
Then open your Web browser and type in the default IP address ‗192.168.1.254‘.
5.
The device information page should appear as shown in Figure 36.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 54 LOYTEC
Figure 36: Device Information Page.
The device information page shows information about the L-INX and the current firmware version. It also contains operational parameters, such as free memory, system temperature and supply voltage.
Click through the menus on the left hand side to become familiar with the different screens.
If you click on Config in the left menu, you will be asked to enter the administrator
password in order to make changes to the settings as shown in Figure 37. Enter the default
administrator password ‗loytec4u‘ and select Login . Note, that firmware versions previous to 4.0 used ‗admin‘ as the default password.
Version 4.0
Figure 37: Enter ‗admin‘ as the default administrator password.
The Config menu opens. Click on Passwords in the Config menu, which opens the
password configuration page as shown in Figure 38. The device has three user accounts: (1)
guest allows the user to view certain information only, e.g., the device info page. By default the guest user has no password. (2) operator is able to read more sensible information such as calendar data. (3) admin has full access to the device and can make changes to its
LOYTEC electronics GmbH
L-INX User Manual 55 LOYTEC configuration. Note that the user accounts are also used to log on to the FTP and Telnet server.
Figure 38: Password Configuration Screen.
Please change the administrator password in order to protect yourself from unwanted configuration changes by anyone else. To do so, select the admin account in the drop-down box and enter the new password. If the administrator password is left empty, password protection is turned off and everyone can access the device without entering a password.
Click on Change password to activate the change.
4.2 Device Configuration
The device configuration pages allow viewing and changing the device settings of the
LINX. Here are some general rules for setting IP addresses, port numbers, and time values:
An empty IP address field disables the entry.
An empty port number field sets the default port number.
An empty time value field disables the time setting.
4.2.1 System Configuration
The system configuration page is shown in Figure 39. This page allows configuring the
device‘s system time and other system settings. The TCP/IP Configuration link is a shortcut to the Ethernet port configuration. Follow that link to change the IP settings of the device.
The time sync source can be set to auto , manual , NTP , BACnet , or LonMark . In the auto mode, the device switches to the first external time source that is discovered. Possible external time sources are NTP, BACnet, LonMark. The option manual allows setting the time manually in the fields Local Time and Local Date . In manual mode, the device does not switch to an external time source. Note, that if NTP is selected, the NTP servers have to
be configured on the IP Configuration page (see Section 4.2.2).
The time zone offset must be defined independently of the time source. It is specified as the offset to GMT in hours and minutes (e.g., Vienna/Austria is +01:00, New York/USA is
-06:00). For setting the daylight saving time (DST) predefined choices are offered for
Europe and USA/Canada. DST can be switched off completely by choosing none or set manually for other regions. In that case, start and end date of DST must be entered in the fields below.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 56 LOYTEC
Figure 39: System Configuration Page, e.g., for Vienna, Austria.
The next section on the page allows configuring the device‘s earth position. This setting defines the longitude, latitude and elevation of the device. The latitude and longitude are entered as degrees, minutes, and seconds. The altitude is entered in meters height above sea level. This setting is used for an astronomical clock. For fixed locations such as a building, the position can be entered on this page.
For generating CSV files for trend logs, alarm logs, etc., the delimiter for those CSV files can be configured. This setting can be changed between a comma ‗,‘ and a semi-colon ‗;‘.
The change takes effect immediately for all files generated by the device.
4.2.2 Backup and Restore
A configuration backup of the device can be downloaded via the Web interface. Press the
backup link as shown in Figure 40 to start the download. The device assembles a single file
including all required files. A file requestor dialog allows specifying the location where the backup file shall be stored.
To restore the device settings, simply select a previously generated backup file in the
Restore Configuration section of the page by clicking the button next to the Filename field. Then press the Restore button.
The backed up configuration data consists of:
Device settings (Passwords, IP settings, e-mail config, etc.),
Data point configuration,
CEA-709 binding information,
BACnet server objects and client mappings,
LIOB configuration and parameters,
AST settings,
L-WEB configuration and custom Web pages.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 57 LOYTEC
Figure 40: Backup/Restore page.
4.2.3 Port Configuration
This menu allows configuring the device‘s communications ports. For each communication port, which is available on the device and shown on the label (e.g., Port 1, Port 2 Ethernet), a corresponding configuration tab is provided by the Web UI. An example is shown in
Figure 41. Each port tab contains a selection of available communication protocols. By
selecting a checkbox or radio button the various protocols can be enabled or disabled on the communication port. Some ports allow exclusive protocol activation only, other ports (e.g., the Ethernet port) allow multiple protocols bound to that port.
Figure 41: Port Configuration Page.
When selecting a protocol on a communication port, the protocol‘s communication parameters are displayed in a box on the right-hand side. To save the settings of the currently opened protocol, click the Save Settings button. Pressing Get Settings retrieves the current settings from the device.
4.2.4 IP Configuration
The TCP/IP configuration is done under the Ethernet port tab as shown in Figure 42. The
mandatory IP settings, which are needed to operate the device, are marked with a red asterisk (IP address, netmask, gateway). The Enable DHCP checkbox switches between manual entry of the IP address, netmask, and gateway address, and automatic configuration from a DHCP server.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 58 LOYTEC
Hostname and Domainname are optional entries and can be left empty. For some DHCP configurations it may be necessary to enter a hostname. Please contact your system administrator on how to configure DHCP to acquire an IP address. Further, you can configure up to 3 Domain Name Servers.
Version 4.0
Figure 42: IP Configuration Page.
The device comes configured with a unique MAC address. This address can be changed in order to clone the MAC address of another device. Please contact your system administrator to avoid MAC address conflicts.
The device can be configured to synchronize its clock with NTP time. Enter the IP address of a primary and, optionally, a secondary NTP server. The device will use NTP as a time source if the time sync source in the system configuration page is set to NTP (see Section
NTP status below the NTP server settings displays the current NTP synchronization status ( out-of-sync , or in-sync ).
If the device is operated with a 10 Mbit/s-only hub, the link speed should be switched from
Auto Detect to 10Mbps/Half-Duplex . With modern 100/10 Mbit/s switches, this setting can be left at its default.
Other standard protocols that are bound to the Ethernet interface are FTP, Telnet, and
HTTP (Web server). By deselecting the checkbox, those protocols can be individually disabled. The standard UDP/TCP ports can be changed in the respective protocol settings.
An example for the FTP server is shown for FTP in Figure 43. The FTP server is used for
instance to update the firmware (see Section 15.1) or to upload a new data point
configuration. Note that HTTP for the Web server can only be disabled on the console interface or by using the device configuration of the Configurator.
LOYTEC electronics GmbH
L-INX User Manual 59 LOYTEC
Figure 43: FTP server configuration on the Ethernet port.
4.2.5 Ethernet Sniffer
The L-INX models, which provide a built-in Ethernet switch/hub, can configure the switch to operate as a hub. This allows connecting a laptop computer to the second Ethernet port and running a packet sniffer on the device. To activate the sniffer mode, go to the Ethernet port config and select the Ethernet Sniffer
item as shown in Figure 44. In the settings box
select the Ethernet port, on which the traffic shall be forwarded to.
Figure 44: Activating the Ethernet Sniffer.
4.2.6 CEA-709 Configuration
The CEA-709 protocol can be enabled on the device‘s ports Port1, Port2, etc. if available.
To enable it, click the CEA-709
radio button as shown in Figure 45. Note, that depending
on the device model, other protocols on the same port will be disabled in this case. The protocol settings box on the right-hand side displays the current transceiver settings.
Figure 45: CEA-709 Configuration Page.
4.2.7 CEA-852 Device Configuration
The CEA-852 protocol is only available on the Ethernet port. To enable CEA-852 on the device, select the CEA-852 (CEA-709 over IP) checkbox on the Ethernet tab of the port configuration page. Please note that on device models without a router or a proxy, the
CEA-709 protocol on other ports will be disabled (e.g., LINX-100).
The CEA-852 protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 46. Typically, the device is added to an IP channel by entering the relevant
information on a configuration server. The configuration server then contacts the CEA-852 device of the L-INX and sends its configuration.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 60 LOYTEC
Version 4.0
Figure 46: CEA-852 Device Configuration Page.
The field Config server address and Config server port display the IP address and port of the configuration server, which manages the L-INX and the IP channel. The field Config client port represents the IP port of the LINX‘s CEA-852 device. This setting should be left at its default (1628) unless there are more than one CEA-852 devices operating behind a single NAT router. Please refer to the L-IP User Manual [1] to learn more about NAT configuration.
In the field Device name the user can enter a descriptive name for the LINX, which will appear in the IP channel to identify this device. You can enter a device name with up to 15 characters. It is recommended to use unique device names throughout the IP channel.
The Channel mode field reflects the current channel mode of the CEA-852 device. It is configured by the configuration server. If there are any two devices in the channel which use the same IP address but different ports (e.g., multiple devices behind one NAT router) the channel switches to Extended NAT mode . Please refer to the L-IP User Manual [1] to learn more about configuring the Extended NAT mode in the configuration server.
The configuration server sets the SNTP server addresses and the Channel timeout .
The filed Escrow timeout defines how long the CEA-852 device on the L-INX waits for out-of-sequence CEA-852 data packets before they are discarded. Please enter the time in ms or ‗0‘ to disable escrowing. The maximum time is 255 ms.
The field Aggregation timeout defines the time interval in which multiple CEA-709 packets are combined into a single CEA-852 data packet. Please enter the time in ms or ‗0‘ to disable aggregation. The maximum time is 255 ms. Note that disabling aggregation will negatively affect the performance of the CEA-852 device of the LINX.
The field MD5 authentication enables or disables MD5 authentication. Note that MD5 authentication cannot be used together with the Echelon‘s i .
LON 1000 since the i .
LON 1000 is not fully compliant with the CEA-852 authentication method. MD5 can be used with the i .
LON 600. In the following field MD5 secret enter the 16-byte MD5 secret.
Note that for security purposes the active MD5 secret is not displayed. You may enter the
16 bytes as one string or with spaces between each byte, e.g., 00 11 22 33 44 55 66 77 88
99 AA BB CC DD EE FF.
LOYTEC electronics GmbH
L-INX User Manual 61 LOYTEC
Also note that entering the MD5 secret on the Web interface may pose a security risk. Since the information is transmitted over the network it can be subject for eavesdroppers on the line. It is recommended to use a cross-over cable.
In the field Location string the user can enter a descriptive test which identifies the physical location of the LINX. A location string can have a maximum length of 255 characters. This is optional and for informational purposes only.
If the CEA-852 device on the L-INX is used behind a NAT router, the public IP address of the NAT router or firewall must be known. To automatically detect the NAT address leave the Auto-NAT checkmark enabled.
The Multicast Address field allows the user to add the CEA-852 device of the L-INX into a multi-cast group for the CEA-852 IP channel. Enter the channel‘s IP multi-cast address here. Please contact your system administrator on how to obtain a valid multi-cast address.
To learn when it is beneficial to use multi-cast addresses in your channel please refer to the
L-IP User Manual [1].
4.2.8 CEA-709 Router Configuration
This page is only available on L-INX models with the router option (101, 111, 121, 151).
The CEA-709 router configuration page allows configuring the built-in router mode.
Available modes are Configured Router and Smart Switch . The L-INX must be rebooted to let the changes on this page take effect.
The configured router mode is the default setting. Choose this setting if you want to use the
L-INX as a standard configured CEA-709 router that can be configured in a network management tool such as NL-200 or LonMaker.
The Smart Switch mode lets the device act as a self-learning router like the L-Switch. In this configuration the LINX‘s router doesn‘t need to be configured with a network management tool but is completely transparent in the network. Use this operating mode in a plug&play networking environment. The switch mode should only be used in LAN networks. In Smart
Switch mode, this page has two more configuration fields: Subnet/node learning and
Group learning .
Figure 47: CEA-709 Router Configuration Page.
4.2.9 CEA-852 Server Configuration
This page is only available on CEA-709 L-INX models with the router option (101, 111,
121, 151). On this configuration page the configuration server on the LINX-101 can be enabled or disabled. In the drop-down box Config server status select enabled and click
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 62 LOYTEC on Save Settings to activate the configuration server. Then the configuration server settings
page appears as shown in Figure 48. If the configuration server is enabled the green
configuration server LED labeled CS will be on, otherwise it will be off.
The configuration server port can be changed in the Config server port field. It is recommended to keep the default port setting of 1629. The field Channel name is informational only and can consist of up to 15 characters.
The field Channel members displays the current number of members on the IP-852 channel. The field Channel mode reflects the current channel mode. The L-INX configuration server automatically determines this mode. Depending on if there are any two devices in the channel which use the same IP address but different ports (e.g., multiple
CEA-852 devices behind one NAT router). If all IP addresses are unique, the mode is
Standard , if some are not unique the mode is Extended NAT mode . Please refer to
Section 7.3.2 to learn more about the implications of this mode.
Version 4.0
Figure 48: Configuration server settings.
Enter NTP timer server address and ports in the fields Primary SNTP and Secondary
SNTP . The L-INX will synchronize to NTP time if primary or primary and secondary NTP servers are specified. A list of available timeservers can be found at www.ntp.org
.
The Channel timeout is an IP-852 channel property and indicates how old a packet can be before it is discarded. The channel timeout is set in ms. To disable the channel timeout enter
a value of 0. To select the proper value please consult Section 7.5.2. Setting a channel
timeout other than 0 requires a valid SNTP server entry on the configuration server.
The Auto members option allows members to be automatically added to the channel. If turned on, CEA-852 devices can register on the IP-852 channel without the device being explicitly added on the configuration server. This special feature is useful in combination with the LPA-IP since it can add itself to the configuration server during the debug session.
Non-responding auto members are automatically removed from the channel. This feature is turned off by default and must be explicitly turned on. Use this option with care because new CEA-852 devices can add themselves to the channel without knowledge of the system operator. This could cause a potential security hole.
LOYTEC electronics GmbH
L-INX User Manual 63 LOYTEC
The Roaming members option allows tracking CEA-852 devices when their IP address changes. This feature must be turned on if DHCP is used and the DHCP server can assign different IP addresses to the same device (same Neuron-ID). In combination with Auto-
NAT the LINX‘s router can also be operated behind NAT routers, which change their IP address between connection setups. For more information on this topic refer to Section
7.3.1. The roaming member feature is turned on by default. It is recommended to turn off
this feature if DHCP is not used or if the DHCP server always assigns the same IP address to a given MAC address.
Use the drop-down box MD5 authentication to enable and disable MD5 authentication. If
MD5 authentication is enabled, all devices on the IP-852 channel must have MD5 enabled and must use the same MD5 secret. Note that MD5 authentication cannot be used together with the Echelon‘s i .
LON 1000 since the i .
LON 1000 is not fully compliant with the
CEA-852 authentication method. MD5 can be used with the i .
LON 600. The MD5 secret can be entered over the Web interface. You may enter the 16 bytes as one string or with spaces between each byte, e.g., 00 11 22 33 44 55 66 77 88 99 AA BB CC DD EE FF.
It is recommended, however, to enter the secret locally and not over an Internet connection.
It is best to use a cross-over Ethernet cable connected to the PC.
4.2.10 CEA-852 Channel List
This page is only available on CEA-709 L-INX models with the router option (101, 111,
121, 151). If the configuration server is enabled on the LINX, the CEA-852 device list can
be seen in the CEA-852 channel list menu. An example is given in Figure 45.
The Add Device button is used to add another CEA-852 device to the IP-852 channel. The
Reload button updates the Web page and the Recontact button contacts all devices to update their status. The Execute button executes the option selected in the adjacent dropdown box on the checked members. Each member can be selected for that action in an individual check-box in the Sel column. Actions available are: disable , enable , delete , assign to NAT , and remove from NAT . For more information on the actions on NAT
routers refer to Section 7.3.2.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 64 LOYTEC
Figure 49: CEA-852 channel membership list.
The device status information is indicated with descriptive icons of different colors. The
description for the different status indicators is shown in Table 8. The
Flags column indicates with an A that the device is an auto member.
Click on the Edit button to change the device name, IP address, and port number for this device. Click Edit on a NAT router to change the NAT router address. The Stats button retrieves the statistics summary page from the client device.
Icon Status Description registered unregistered not contacted not responding disabled
No extended
NAT
The CEA-852 device has been successfully registered with the IP-852 channel and is fully functional.
The CEA-852 device has never been registered with the IP-852 channel.
The CEA-852 device has not been contacted since the configuration server has started.
The CEA-852 device has been registered but is not responding at the moment.
The CEA-852 device has been disabled on the channel (or rejected).
The CEA-852 device does not support the extended
NAT mode. This device is disabled.
Table 8: Possible Communication Problems in the Configuration Server.
4.2.11 BACnet Configuration
Figure 50 shows the BACnet device configuration page. This configuration page allows
setting the Device ID , which is the instance part of the Object_Identifier property of the
BACnet Device object. The field Device name holds the name of the BACnet device object
(property Object_Name).
Important: The device ID and device name must be unique within the BACnet internetwork.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 65 LOYTEC
Important!
Figure 50: BACnet Device Configuration.
Further, the description and location can be configured. These configuration items correspond to the properties Description, and Location respectively of the BACnet Device object.
Depending on the selected BACnet/IP mode, applicable fields are enabled and others are grayed-out. Note, that on the LINX-200, the BACnet/IP modes are restricted to Device and
Foreign Device , while the LINX-201 also supports Broadcast Management Device .
For operating the LINX-151,201,211,221 as a BACnet router between BACnet/IP and
MS/TP, the BACnet network numbers for the BACnet/IP and MS/TP ports must be set.
On the settings for BACnet/IP refer to Section 4.2.12. For configuring the MS/TP data link
4.2.12 BACnet/IP Configuration
The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the device, select the BACnet/IP checkbox on the Ethernet tab of the port configuration page.
Please note that on device models without a router, the BACnet MS/TP protocol on other ports will be disabled (e.g., LINX-200, L-Gate).
The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 51. On devices with a router (e.g., LINX-201) the
Network Number of the
BACnet/IP port must be configured to operate the build-in router. If the BACnet/IP network uses a non-default UDP port number other than 47808/0xBAC0, enter this port in the
BACnet/IP port field. Enter ‗0‘ in this field for switching back to the default setting.
Version 4.0
Figure 51: BACnet/IP Configuration.
In the field BACnet/IP mode the operation mode of the device is selected:
Device (Default): In this mode the device operates as a regular BACnet/IP device on the local network without other advanced features.
LOYTEC electronics GmbH
L-INX User Manual 66 LOYTEC
Foreign Device (FD): In this mode, the device registers at an existing BBMD in the
BACnet/IP network as a foreign device. It is used, if the device is located as a single
BACnet/IP device on a remote IP subnet or behind a NAT router. If operated as a foreign device behind a NAT router, port forwarding to the BACnet/IP port (UDP, default port 0xBAC0) and optionally to the Web server and FTP server port (TCP, default port 80 and 21) must be setup in the NAT router. If foreign device is selected, the following, additional settings must be made: o FD BBMD IP address and FD BBMD port : IP address and port of the remote BBMD the device registers at as a foreign device. o
FD re-registration : A foreign device must periodically re-register at a
BBMD. Here you can setup the corresponding interval. The default is 1800 seconds. o FD retry timeout and FD retries : Here you can specify the behavior, if registration does not work instantly. These values should be left at default:
30000ms / 3 retries.
Broadcast Management Device (BBMD): This option is available on the LINX-201
only. Same as ‗Device‘ but the BBMD function is enabled (see Section 4.2.14). For
BBMD-only function, MS/TP can also be disabled (see Section 4.2.13).
4.2.13 MS/TP Configuration
The BACnet MS/TP protocol can be enabled on the device‘s port Port2 if available. To enable it, click the BACnet MS/TP
radio button as shown in Figure 52. Note, that
depending on the device model, other protocols on the same port will be disabled in this case. On a BACnet L-INX without a BACnet router BACnet MS/TP port is not enabled by default. On a BACnet L-INX with a BACnet router the MS/TP port is enabled by default.
Figure 52: MS/TP Configuration.
The MS/TP protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 52. Mandatory settings are the
MS/TP node number and the MS/TP baud rate. The MS/TP node number determines the physical address of the device on the
MS/TP channel and must be in the range from ‗0‘ to the number configured with the
MS/TP max master configuration option. It must be unique within the MS/TP channel.
The Baud rate on the MS/TP channel can be set to 9600, 19200, 38400, and 76800 Baud. It is strongly recommended to leave the MS/TP max info frames and the MS/TP max master configuration options at their default settings.
On a L-INX with a BACnet router, the Network Number of the MS/TP port must be configured to operate the build-in router. On the LINX-201 the MS/TP port can be disabled independently of the BACnet/IP port.
4.2.14 BACnet BDT (Broadcast Distribution Table)
The BBMD function is only available on L-INX models with the BACnet router option
(151, 201, 211, 221). The BBMD function is needed when a BACnet/IP network spans over several IP subnets separated by IP routers. If the device is configured as a BBMD, i.e. the
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 67 LOYTEC
BACnet/IP mode is set to Broadcast Management Device,
(Broadcast Distribution Table) specifies all other BBMDs of the BACnet/IP network. The
Figure 53: BACnet Broadcast Distribution Table.
By clicking Add Device new BBMDs (IP address and port) can be added. With Action on
Selected and selecting existing entries, certain BBMDs can be deleted again from the table.
To commit the finished table, device must be rebooted (see Section 4.5).
4.2.15 E-mail Configuration
The Web interface provides the e-mail configuration page to set up an e-mail account, which is used to send e-mails. The content and time when e-mails are sent is configured
through the Configurator software (see Section 6.11). The e-mail configuration page is
In the field for the outgoing e-mail server, enter the SMTP server of your Internet provider.
Typically, the SMTP server port can be left at 25. In the field Source E-mail Address , enter the e-mail address of the device‘s e-mail account. In the field Source E-mail Sender
Name enter a name that the e-mail will display as the source name. Note, that only ASCII characters are allowed in the name. If replies shall be sent to another e-mail address, specify this in the Reply E-mail Address .
If the provider‘s SMTP server requires authentication, enter the required user name and password. Note, that only username/password is supported. SSL/TLS authentication is not supported (e.g., Hotmail, gmail cannot be used).
To verify the e-mail configuration, reboot the device to let the changes take effect and return to the e-mail configuration page. Then press one of the Send Test E-mail buttons.
Note, that a DNS server must be configured in the IP settings (see Section 4.2.4) to resolve
the e-mail server host name. The Web UI displays a warning message at the top of the page, if the DNS configuration is missing.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 68 LOYTEC
Figure 54: E-mail Configuration Page.
4.2.16 Data Points
The device‘s Web interface provides a data point page, which lists all configured data
points on the device. An example is shown in Figure 55. The data point page contains a tree
view. Clicking on a particular tree item fills the right part of the page with a data point list of that tree level and all levels below. Thus, one can get an easy overview of all data points.
The data point list displays the data point name, direction, type, current value, and data point state. Inactive points are displayed in gray. If the data point list does not fit on one page, there are page enumerator links at the bottom. Important data point states and their
implications are listed in Table 9.
Version 4.0
Figure 55: Data point page.
LOYTEC electronics GmbH
L-INX User Manual 69 LOYTEC
Data Point Status Description normal invalid value offline (config) offline unreliable
(offline) unreliable (range) unreliable not configured inactive
The data point is in normal operation state and possesses a value.
The data point has no valid value.
The data point has a value but it is not reflected on the network due to a configuration error (not commissioned, no binding, no client mapping, etc.)
The data point has a value but it is not reflected on the network due to a communication error (e.g., the peer node is not online).
The data point is in normal operation. The value of it, however, is qualified as unreliable because a connected data point is offline. For an output data point it means that the value was fed from a connection, where the source is offline. For an input data point it means that the connected output data point could not send the value to the network.
The data point is in normal operation. The value of it, however, is qualified unreliable because the value is an out-of-range value for the connected data point. The value is limited to the supported range.
The data point is in normal operation. The value of the data point or a connected data point has been tagged as unreliable over the network. This is the case when the BACnet reliability has been written.
The data point is mapped to a port, which is not configured (e.g., the port is disabled).
The data point is inactive and the line is grayed-out. Values can be written but no network communication is triggered. This can be the case, if a data point is not used in the configuration or it is connected to a BACnet server object, which is not present on the device.
Table 9: Data Point States.
The data point names are links. Clicking on such a link opens a detailed page on that data point. If the data point supports it, the user can also enter a new data point value as depicted
Status
field is discussed in Table 9. The
Flags , Poll cycle , Min/Max send time and Max age fields are the common timing parameters for the data point. See
Section 5.1.2 for a closer discussion on timing parameters.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 70 LOYTEC
Figure 56: Data point details page.
Clicking on the Set button writes the new value to the device‘s data server. When setting a value, the Web page displays the status of the action:
Successfully set value : The new value has been successfully set in the data point and the update has been sent on the network, if it is a network data point.
Could not send value update : The new value has been set but it has not been sent out on the network. The reason can be that the peer node is currently offline or there is a configuration error. The data point status reflects this error.
Could not set value (error code ): The new value has not been set because of an internal error. Please contact LOYTEC with the error code.
4.2.17 Trend
The Web interface provides a configuration page to re-configure trend logs at run-time. The changes made to the trend logs take effect immediately without the needs for a reboot of the device. Allocating new trend logs can only be done in the configuration software (see
Section 6.14.1). The trend log main page displays all available trend logs. Click on the trend
log to be edited. This opens the trend log configuration page. An example is shown in
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 71 LOYTEC
Figure 57: Trend log configuration page.
The user can change the Trend Mode , the Fill Mode , the Log Interval and the Fill Level
Notification . Furthermore, data points can be added to the trend log by clicking the Add… button. A data point selector dialog opens. Click on a data point for adding it. For removing a data point from the trend log, click on it in the Logged Data Points list and hit the
Remove button. Save the changes made by clicking the Save button. For more information
on how a trend log can be configured please refer to the Configurator Section 6.14.2.
4.2.18 Scheduler
The Web interface provides the scheduler page to edit its schedules at run-time, i.e., change the times and values that shall be scheduled. Allocating new schedules and attaching data
points to those schedules can only be done in the configuration software (see Section 6.12).
The scheduler main page displays all available schedules. Click on the schedule to be
edited. This opens the scheduler page. An example is shown in Figure 58.
The effective period defines when this schedule shall be in effect. Leave From and To at
‗*.*.*‘ to make this schedule always in-effect. Otherwise enter dates, such as ‗30.1.2000‘.
To entirely disable a scheduler de-select the Enable Schedule check box.
Schedules are defined per day. On the left-hand side, the weekdays Monday through
Sunday can be selected, or exception days from the calendar, e.g., Holidays. Once a day is selected, the times and values can be defined in the daily planner on the right-hand side. In
the example shown in Figure 58, on Monday the value
day is scheduled at 8:00am . The same principle applies to exception days . Exception days override the settings of the normal weekday. Put a check mark on those exception days from the calendar, which shall be used in the schedule. To edit the date ranges of exception days click on the links to the used calendars, e.g., ‗calendar‘ or ‗Scheduler_1‘. The ‗Scheduler_1‘ is a calendar, which is embedded into the schedule and not accessible by other schedulers. For more information
on how to set up schedules and calendars refer to Section 6.12.
To define actual values for the names such as day click on the tab Presets as shown in
Figure 59. To define a new value, click on the button
Add Preset . This adds a new column.
Enter a new preset name (e.g., ‗day‘). Then enter values for the data points in the preset column. The data point description column displays the short-hand name defined in the configuration software. This description can also be changed on the Web UI.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 72 LOYTEC
Figure 58: Schedule Configuration Page.
Version 4.0
Figure 59: Scheduled Presets Configuration Page.
You can switch back and forth between the two tabs. Once the configuration is complete, click on the Save button. This updates the schedule in the device. Any changes made become effective immediately.
On local schedulers the Web UI also allows to reconfigure the scheduled data points. This change takes effect immediately without a reboot of the device. To add and remove data points to the scheduler, go to the Data Points tab. The configuration page is depicted in
Figure 60. To add a new data point, click the
Add…
button. To remove a data point, select the data point in the list Scheduled Data Points by clicking on it and then press the
Remove button. Finally, store the changes by clicking the Save button. After modifying the scheduled data points, go back to the Presets tab and enter descriptive value label names.
For more information on how to configure a scheduler please refer to the Configurator
LOYTEC electronics GmbH
L-INX User Manual 73 LOYTEC
Figure 60: Re-configure scheduled data points on the Web UI.
4.2.19 Calendar
The Web interface provides the calendar page to edit its calendars at run-time, i.e. change the exception days. The calendar main page displays all available calendars. Click on the calendar to be edited. This opens the calendar configuration page. An example is shown in
The effective period defines when this calendar shall be in effect. Leave From and To at
‗*.*.*‘ to make this calendar always in-effect. Otherwise enter dates, such as ‗30.1.2000‘.
Version 4.0
Figure 61: Calendar Configuration Page.
On the remainder of this page, work from left to right. Click on a calendar pattern or create a new calendar pattern by clicking Add new entry . A calendar pattern defines a set of
pattern entries, which defines the actual dates or date ranges. In the example in Figure 61,
the calendar pattern Holidays is selected.
In the Pattern Configuration box, the calendar pattern‘s name can be edited. It also lists the entries. New entries can be added by clicking Add new entry . Existing entries can be
LOYTEC electronics GmbH
L-INX User Manual 74 LOYTEC
selected and edited in the box on the right-hand side. In the example in Figure 61, the date
14.7.* is selected, which means ―The 14.7. of every year‖. Other entry types such as Date
Range and Week-and-Day
can be selected. See Section 5.3.3 for more information about
defining exception dates.
4.2.20 Alarm
The Web interface provides the alarm page to view the currently pending alarms of its alarm data points. The alarm main page displays all available alarm data points. Alarm objects which have active alarms are displayed in red. Click on the alarm object to be viewed. This
opens the alarm summary page. An example is shown in Figure 62.
Figure 62: Alarm Summary Page.
Active alarms are highlighted red. Inactive alarms which have not been acknowledged are rendered in green. Alarms that can be acknowledged have an Ack button. Press on the Ack button to acknowledge the alarm. Depending on the technology, this and older alarm records will be acknowledged. Acknowledged, active alarms are rendered in red. Click on
Reload to refresh your alarm list.
Inactive alarms that have been acknowledged disappear from the list. To record historical
information about those alarms, the alarm log must be used. See Section 4.3.9 for the alarm
log Web interface.
4.2.21 IEC61131 Configuration
On the IEC61131 configuration page the user can download an IEC61131 program as well
as controlling the behavior of the IO driver, see Figure 63.
After downloading the IEC61131 program rebooting the L-INX is necessary in order to load and start the new IEC61131 program. After resetting the device check the PLC LED for a successfully started program.
Important! Downloading a new IEC61131 may result in the need for a new data point configuration.
Hence, take care about the requirements of the downloaded program and in case of a different set of IEC61131 variables use the L-INX configuration tool to adapt the data point configuration.
The data exchange of the IEC61131 program can be disabled by disabling the IO driver. As a result the IEC61131 program is not able to receive or send update from/to the appropriate data points. Hence, for debugging purpose, the data point values can be manipulated regardless of the data set from the IEC61131 program.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 75 LOYTEC
The information about the running program is also displayed. The IEC61131 program can be removed from the device by clicking the Remove button. The device needs to reboot after this action.
Figure 63: IEC61131 Configuration Page.
4.3 Device Statistics
The device statistics pages provide advanced statistics information about the CEA-709 device, the CEA-852 device, the BACnet device, the system log, the scheduler, the alarm log and the Ethernet interface.
4.3.1 System Log
The System Log page prints all messages stored in the system log of the device. An example
is shown in Figure 64. This log data is important for trouble-shooting. It contains log entries
for reboots and abnormal operating conditions. When contacting LOYTEC support, have a copy of this log ready.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 76 LOYTEC
Figure 64: System Log Page.
4.3.2 IP Statistics
Figure 65 shows the IP statistics page. It allows finding possible problems related to the IP
communication. Specifically, any detected IP address conflicts are displayed (if the device‘s
IP address conflicts with a different host on the network).
Version 4.0
Figure 65: IP Statistics Page.
LOYTEC electronics GmbH
L-INX User Manual 77 LOYTEC
4.3.3 CEA-852 Statistics
The CEA-852 statistics page displays the statistics data of the CEA-852 device on the device. It is only displayed if the CEA-852 interface is enabled and supported by the L-INX
model. The upper part of the CEA-852 statistics page is depicted in Figure 66. To update
the statistics data, press the button Update all CEA-852 statistics . To reset all statistics counters to zero, click on the button Clear all CEA-852 statistics . The field Date/Time of clear will reflect the time of the last counter reset.
Figure 66: Part of the CEA-852 Statistics Page.
4.3.4 Enhanced Communications Test
The Enhanced Communications Test allows testing the CEA-852 communication path between the CEA-852 device on the L-INX and other CEA-852 devices as well as the configuration server. The test thoroughly diagnoses the paths between individual members of the IP channel and the configuration server in each direction. Port-forwarding problems are recognized. For older devices or devices by other manufacturers, which do not support the enhanced test features, the test passes as soon as a device is reachable, but adds a
comment, that the return path could not be tested. A typical output is shown in Figure 67.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 78 LOYTEC
Figure 67: Enhanced Communication Test Output.
The Round Trip Time (RTT) is measured as the time a packet sent to the peer device needs to be routed back to the LINX-10X. It is a measure for general network delay. If the test to a specific member fails, a text is displayed to describe the possible source of the problem.
The reasons for failure are summarized in Table 10.
Text displayed (Web icon) Meaning
OK, Return path not tested (green checkmark)
Not reachable/not supported
(red exclamation)
Local NAT config. Error
(red exclamation)
Peer not reachable
(red exclamation)
Displayed for a device which is reachable but which does not support the feature to test the return path (device sending to this CEA-852 device).
Therefore a potential NAT router configuration error cannot be detected. If the tested device is an L-IP, it is recommended to upgrade this L-IP to 3.0 or higher.
This is displayed for the CS if it is not reachable or the CS does not support this test. To remove this uncertainty it is recommended to upgrade the L-IP to
3.0 or higher.
This is displayed if the CEA-852 device of the LINX-10X is located behind a
NAT router or firewall, and the port-forwarding in the NAT-Router (usually
1628) or the filter table of the firewall is incorrect.
Displayed for a device, if it is not reachable. No RTT is displayed. The device is either not online, not connected to the network, has no IP address, or is not reachable behind its NAT router. Execute this test on the suspicious device to determine any NAT configuration problem.
Table 10: Possible Communication Problems.
4.3.5 CEA-709 Statistics
The CEA-709 statistics page displays statistics data of the CEA-709 port on the device as
shown in Figure 68. This data can be used to troubleshoot networking problems. To update
the data, click on the button Update CEA-709 statistics .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 79 LOYTEC
Figure 68: CEA-709 Statistics Page.
4.3.6 OPC Server Statistics Page
The OPC server statistics page shows statistics data, which contains information on currently and previously connected clients. An example list of OPC clients is shown in
Update OPC statistics button retrieves the current statistics.
The Summary table on the top of the page displays the number of currently connected clients. These clients occupy TCP connections. The next line specifies the total number of accepted client connections since the device is running. The figure for rejected connections can be used to detect situations, where too many clients try connecting at the same time.
Version 4.0
Figure 69: OPC Server Statistics Page.
LOYTEC electronics GmbH
L-INX User Manual 80 LOYTEC
The Connection Details list shows more information on the history of client connections.
The green lines at the top denote currently active connections. Active connections have an idle time figure specified in seconds. The following lines in black represent a history of the most recent connections. Inactive connections read ―n/a‖ in the
Idle column.
All lines contain client information, which specifies the client IP address and port of the connected client. The Srvc column specifies the type of Web service (Web, DA, and DL).
The Agent column contains information on the HTTP agent of the client, and the Last
Action column contains information on the last known Web service SOAP action the client has requested.
4.3.7 BACnet MS/TP Statistics
The BACnet MS/TP statistics page is only available, when the MS/TP data link layer is
enabled (see Section 4.2.13) and supported by the L-INX model. An example is shown in
Figure 70. The separated part on the top of the table contains the most important statistics
data.
The MS/TP token status reports the current token passing state. In state OK , the token is circulating between the masters. This is the normal state, when multiple masters are on the
MS/TP network. The state SOLE MASTER is the normal state when the device is the only master on the network. If there are multiple masters on the network, this state is a hint to a broken cable. In state TOKEN LOST , the token is currently not circulating.
The counter MS/TP lost tokens is an indicator for communication problems on the
MST/TP network. If it increases, there is a cabling, ground, or termination problem. The counters Rcv OK and Send OK reflect the number of successfully received or transmitted
MS/TP frames. Check these counters to verify that communication is flowing on the MS/TP segment.
Version 4.0
Figure 70: BACnet MS/TP Statistics Page.
LOYTEC electronics GmbH
L-INX User Manual 81 LOYTEC
4.3.8 Scheduler Statistics Page
The scheduler statistics page provides an overview of what is scheduled at which day and which time. In the Display Schedules list, select a single schedule to view its scheduled values and times. Use the multi-select feature to get the overview of more schedules. An
example is shown in Figure 71.
Figure 71: Scheduler Statistics Page.
4.3.9 Alarm Log Page
The alarm log page provides an overview of all alarm logs on the system. Click on one of the links to view a specific alarm log. Each alarm log contains a historical log of alarm transitions. When an inactive and acknowledged alarm disappears from the alarm summary page (live list), the alarm log contains this last transition and maintains it over a reboot. An
example is shown in Figure 72.
To refresh the alarm log contents click on the Reload button. Currently active alarms cannot be acknowledged in this historical view. Follow the link to the attached alarm objects to get to the respective live lists, where alarms can be acknowledged on the Web
interface (see Section 4.2.20).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 82 LOYTEC
Figure 72: Alarm Log Page.
The alarm log contents can be uploaded from the device in a CSV formatted file. Click on the button Upload Alarm Log to upload the current log. To clear the log, press the button
Clear Alarm Log . Please note, that this permanently purges all historical alarm log data of this alarm log.
4.4 L-WEB
This configuration page provides a download link to the L-WEB application installer and a
listing of L-WEB projects available on the device (see Figure 73). Clicking on
Install will
download the installer for L-WEB and start the installation process. See Section 9.2 for
more information on working with the L-WEB visualization.
Figure 73: L-WEB Page.
4.5 Reset, Contact, Logout
The menu item Reset allows two essential operations:
Rebooting the device from a remote location, or
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 83 LOYTEC
resetting the data point configuration from a remote location. This option clears all data points and the entire port configuration. It leaves the IP settings intact.
The Contact item provides contact information and a link to the latest user manual and the latest firmware version. The Logout item closes the current session.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
5 Concepts
84 LOYTEC
5.1 Data Points
5.1.1 Overview
Data points are part of the fundamental device concept to model process data. A data point is the basic input/output element on the device. Each data point has a value, a data type, a direction, and a set of meta-data describing the value in a semantic context. Each data point also has a name and a description. The entire set of data points is organized in a hierarchy.
At the data point level, the specific technological restrictions are abstracted and hidden from the user. Working with different technologies at this level involves common work-flows for all supported technologies.
The direction of a data point is defined as the ―network view‖ of the data flow. This means, an input data point obtains data from the network. An output data point sends data to the network. This is an important convention to remember as different technologies may define other direction semantics.
The basic classes of data points are:
Analog : An analog data point typically represents a scalar value. The associated data type is a double precision machine variable. Meta-data for analog data points include information such as value range, engineering units, precision, and resolution.
Binary : A binary data point contains a Boolean value. Meta-data for binary data points includes human-readable labels for the Boolean states (i.e., active and inactive texts).
Multi-state : A multi-state data point represents a discrete set of states. The associated data type is a signed integer machine variable. Each state is identified by an integer value, the state ID . State IDs need not be consecutive. Meta-data of a multi-state data point includes human-readable descriptions for the individual states (state texts) and the number of available states.
String : A string data point contains a variable-length string. The associated data type is a character string. International character sets are encoded in UTF-8. A string data point does not include any other meta-data.
User : A user data points contains un-interpreted, user-defined data. The data is stored as a byte array. A user data point does not include any other meta-data. This type of data point also serves as a container for otherwise structured data points and represents the entirety of the structure.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 85 LOYTEC
5.1.2 Timing Parameters
Apart from the meta-data, data points can be configured with a number of timing parameters. The following properties are available to input or output data points, respectively:
Pollcycle (input): The value is given in seconds, which specifies that this data point periodically polls data from the source.
Receive Timeout (input): This is a variation on the poll cycle. When receive timeout is enabled, the data point actively polls the source unless it receives an update. For example, if poll cycle is set to 10 seconds and an update is received every 5 seconds, no extra polls are sent.
Poll-on-startup (input): If this flag is set, the data point polls the value from the source when the system starts up. Once the value has been read, no further polls are sent unless a poll cycle has been defined.
Minimum Send Time (output): This is the minimum time that elapses between two consecutive updates. If updates are requested more often, they are postponed and the last value is eventually transmitted after the minimum send time. Use this setting to limit the update rate.
Maximum Send Time (output): This is the maximum time without sending an update.
If no updates are requested, the last value is transmitted again after the maximum send time. Use this setting to enable a heart-beat feature.
5.1.3 Default Values
Default values can be defined for data points when needed. The value of a data point will be set to the defined default value, if no other value source initializes the data point. Default values are beneficial, if certain input data points are not used by the network and need a predefined value, e.g., for calculations. Default values are overridden by persistent values or values determined by poll-on-startup.
5.1.4 Persistency
Data point values are by default not persistent. This means that their value is lost after a power-on reset. There exist different strategies for initializing data points with an appropriate value after the device has started.
For input data points, the value can be actively polled from the network when starting up.
Use the Poll-on-Startup feature for this behavior. Polling the network values has the advantage that intermediate changes on the network are reflected. An input data point can be made persistent, if the last received value shall be available after a power-on reset before a poll-on-startup completes. This can be beneficial, if the remote device is temporarily offline and the last value is considered usable.
For output data points, the value can be restored after starting up by the application. For example, if the output data point‘s value is determined by an input data point and a math object, or the output data point is in a connection with an input, the input can poll its value on startup. If the output data point has no specific other value source, e.g., it is a configuration parameter set by the user, it can be made persistent .
To make a data point persistent, enable the Persistent property of the respective data point.
The persistency option is only available for the base data point classes analog, binary, multistate, string and user. More complex objects such as calendars, schedules, etc., have their own data persistency rules.
For structured data points, only all or none of the structure members can be made persistent.
The configuration of the top-level data point, which represents the entire structure, serves as
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 86 LOYTEC a master switch. Setting the top-level data point to be persistent enables persistency for all sub-data points. Clearing it disables persistency for all sub-data points.
5.1.5 Parameters
A data point can be qualified as a parameter data point. This is accomplished in the
Configurator software by setting a Parameter check box on the data point. Those parameter data points are automatically persistent and will typically have a default value. Their purpose is to store parameterization values, which can be changed from the default value at run time and influence the behavior of the device or the logic running on the device. This way, a number of devices can have the same basic configuration and be adapted by parameter values. Examples are sunblind run times for control logic or descriptive strings for the LWEB visualization.
The qualified parameter data points are also exported via a parameter file, which contains the entire set of current parameter values including meta-information for external tools to display parameter data in a human-readable way. The LWEB-821 master parameter editor can process such parameter data points and manage them for a large number of devices. For more information on how to manage parameters on your devices please refer to the LWEB-
821 Master Parameter Editor manual.
5.1.6 Behavior on Value Changes
The value of a data point can change, if it is written by the application or over the network.
For all data points (input and output) the application (connection, user control, etc.) can be notified, when the value is written to. The property Only notify on COV defines, whether the notification is done with each write or only if the value changes (change-of-value,
COV). If only notify on COV is disabled, writing the same value multiple times will result in multiple notifications.
When the value of an output data point is updated, an update is usually sent out onto the network. The property Send-On-Delta decides how the update is reflected on the network.
If send-on-delta is inactive, each update of the value is sent. If send-on-delta is active, value changes only are sent. The send-on-delta property is only valid for output data points.
For analog data points, the COV or send-on-delta takes an extra argument, which specifies by what amount the value must change to regard it as a change for action. Both, COV and send-on-delta for analog data points check the Analog Point COV Increment property. A change is detected, if the value increment is bigger or equal to the specified increment. If the property is zero, all updates are considered.
5.1.7 Custom Scaling
Custom scaling is applied to all analog data points when they communicate values to or from the network. This feature can be used, if a network data point has engineering units not suitable for the application (e.g., grams instead of kilograms). The scaling is linear and applied in the direction from the network to the application as:
A = k N + d , where N is the network value, k the custom scaling factor , d the custom scaling offset , and
A the application value. When sending a value to the network, the reverse scaling is applied.
If this property is enabled, the analog values are pre-scaled from the technology to the data point. The custom scaling is in addition to any technology-specific scaling factors and can be applied regardless of the network technology.
5.1.8 System Registers
The device provides a number of built-in system registers. They are present without a data point configuration. The system registers, such as the System time or the CPU load, can be
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 87 LOYTEC exposed to the OPC server. By default, all system registers are checked for being exposed to
OPC. To reduce the number of needed OPC tags, you may deselect certain system registers, which are not useful in a specific project.
System register can also serve as a testing setup for the OPC XML-DA communication without a network data point configuration. The System Time register is updated every second and may serve for testing subscriptions. The Authentication Code register can be used to verify writing to OPC tags.
5.1.9 User Registers
The device can be configured to contain user registers. In contrast to system registers, these are only available as a part of the data point configuration. User registers are data points on the device that do not have a specific technological representation on the control network.
Thus, they are not accessible over a specific control network technology.
A register merely serves as a container for intermediate data (e.g., results of math objects, calculation parameters). The register can have the following, basic data types:
Double : A register of base type double is represented by an analog data point. It can hold any scalar value. No specific scaling factors apply.
Signed Integer : A register of base type signed integer is represented by a multi-state data point. This register can hold a set of discrete states, each identified by a signed stats ID.
Boolean : A register of base type Boolean is represented by a binary data point. This register can hold a Boolean value.
String : A register of base type string is represented by a string data point. This register can hold a variable-length character string in UTF-8 format.
Variant : A register of base type variant is represented by a user data point. This register can hold any user-defined data of up to a specified length of Bytes. This length is defined when creating the register and cannot be changed at run time.
Since a register has no network direction, it can be written and read. Therefore, two data points are generated for each register, one for writing the register (output) and one for reading the register (input). A suffix is added to the register name to identify the respective data point. For example, the register MyValue will have two data points generated for:
MyValue_Read and MyValue_Write .
5.1.10 Math Objects
Math objects are advanced application objects that can execute mathematical operations on data points. A math object takes a number of input data points (variables v
1
, v
2
, …, v n
) and calculates a result value according to a specified formula. The result is written to a set of output data points. The formula is calculated each time one of the input data points updated its value. The formula is only evaluated if all of the input data points have a valid value (i.e., don‘t show the invalid value status).
5.2 Connections
Version 4.0
With the use of connections data points can interact with each other. Connections specify which data points exchange values with each other. Both types of connections - ―1: n ‖ and
― m :1‖ connections – are supported. The single data point is referred to as the hub data point, whereas the other data points are the target data points.
This means, the following connections are possible:
1 input data point is connected to n output data points,
LOYTEC electronics GmbH
L-INX User Manual 88 LOYTEC
m inputs data points are connected to 1 output data point.
The most common connection will be the 1:1 connection. This is the type of connection that is auto-generated by the Configurator software. Other types must be created manually in the
Configurator.
In the 1: n connection the input value is distributed to all n output data points. In the m:1 connection, the most current input value is written to the output data point. When polling the output data point in poll-through mode (maximum cache age is set on the output), the value from the first input data point is polled.
Connections can connect data points of different technologies with each other (also mixed among the target data points) but are restricted to the same class of data points. This means only data points of class analog can exchange values within a connection.
For certain classes of data points, additional restrictions exist:
Analog : The value range is capped on the output data points. This means, if the input value in the hub does not fit into the range of an output data point, the value is capped to the biggest or smallest allowed value.
Binary : No special restrictions exist.
Multi-state : Only multi-state data points of an equal number of states can be placed into a connection. The actual state Ids need not be equal. They are ordered and the n-th state is propagated over a connection. For example, the 2nd state on the hub has the state ID ‗2‘, while on the target the 2nd state has the state ID ‗0‘.
String : No special restrictions exist.
User : Only user data points of the same length can be placed in a connection.
5.3 AST Features
5.3.1 Alarming
The alarming architecture comprises a number of entities. Objects that monitor values of data points and generate alarms depending on an alarm condition are called alarm sources .
The alarms are reported to an alarm server on the same device. The alarm server maintains a list of alarm records, called the alarm summary . The alarm server is the interface to access the local alarms. This can be done over the network or the Web UI.
An alarm record contains the information about the alarm. This includes information about the alarm time, the source of the alarm, an alarm text, an alarm value, an alarm type, an alarm priority, and an alarm state. An alarm record undergoes a number of state changes during its life-cycle. When the alarm occurs, it is active . When the alarm condition subsides, the alarm becomes inactive . Active alarms can be acknowledged by an operator. Then they become active acknowledged . Active alarms can also become inactive, but an acknowledgement is still required. Then they become ack-pending . When an alarm is inactive and was acknowledged it disappears from the alarm summary.
Other devices can access the alarm information of an alarm server. These devices are alarm clients . They register with the alarm server and get notified about changes to the alarm summary. Alarm clients can be used to display the current alarm summary and acknowledge alarms.
Depending on the underlying technology, some restrictions to the available alarm information and acknowledgement behavior may exist.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 89 LOYTEC
5.3.2 Historical Alarm Log
The alarm summary of the alarm objects contains a live list of currently active and acknowledge-pending alarms. As soon as an alarm becomes inactive and has been acknowledged, it disappears from the alarm summary. To store a historical log of alarm transitions an alarm log is utilized. An alarm log can log transitions of one or more alarm objects.
The alarm log is always local and stored as a file on the device. The size of an alarm log is configurable. The alarm log operates as a ring buffer. As soon as its size limit is reached, the oldest alarm log records are overwritten by newer alarm transitions. The alarm log is available on the Web UI or can be uploaded from the device as a CSV file. The CSV file can also be used as an e-mail attachment.
5.3.3 Scheduling
Schedulers are objects that schedule values of data points on a timely basis. A scheduler object is configured by which data points it shall schedule. This configuration is done by the system engineer once, when the system is designed. The configuration of the times and values that shall be scheduled is not part of that initial configuration and may be changed later. This distinction has to be kept in mind.
A scheduler object sets its data points to predefined values at specified times. The function of the scheduler is state-based. This means, that after a given time, the scheduler maintains this state. It can re-transmit the scheduled values as appropriate (e.g., when rebooting). The predefined values are called value presets . A value preset contains one or more values under a single label (e.g., ―day‖ schedules the values { 20.0, TRUE, 400 } ).
Which value preset is scheduled at what time is defined through a daily schedule . The daily schedule defines the times and value presets in a 24-hour period. A schedule typically
contains daily schedules for the weekdays Monday through Sunday. See Figure 74 for an
example of a daily schedule.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 90 LOYTEC
Figure 74: Example of a Daily Schedule.
For some tasks the daily schedules on weekdays is sufficient. However, on some specific dates, there may be exceptions to the regular week. This can be implemented by defining daily schedules for exception days . For instance, there may be a separate daily schedule for
Holidays . The exception days are defined through a calendar . The calendar contains a number of calendar patterns . Each calendar pattern describes a pattern of dates that define the class of an exception, e.g., Holidays .
When a calendar is defined on a system, the exception days are available in all schedules.
When a schedule wants to define daily schedules for some of the available exception days,
they need to be enabled in the schedule. See Figure 75 for an example where
Holidays is used.
Version 4.0
Figure 75: Example of used Exception Days.
The function of the exception is simple. The daily schedule of a regular weekday is overridden by the daily schedule of the exception, when one of the specified date patterns is in effect (e.g., July 14 th
in Holidays overrides the regular weekday). If more than one exception days are in use, there may be conflicts on specific dates. These conflicts are resolved by defining priorities for the different exceptions. The daily schedule of the exception with the higher priority is eventually in effect. If two exceptions with the same
LOYTEC electronics GmbH
L-INX User Manual 91 LOYTEC priority exist, it is not defined, which one is in effect. Therefore, always use distinct priorities.
Apart from the defined value presets, there exist special events that can be scheduled in a daily schedule. They affect how the scheduler behaves and which exception is active:
Invalid : If this value is scheduled, the scheduler transmits the invalid value. The numeric representation of that invalid value is defined by the underlying data point and is technology-specific.
Withdraw : If this value is scheduled, the scheduler takes the previously value preset out of effect. This means that the daily schedule with the next lower priority becomes effective. If no daily schedule with lower priority applies, the scheduler behaves as if it
was disabled. Figure 76 presents an example of the
Maintenance Day exception day, which schedules the maint value at 6 am and goes out of effect at 10 am. If the maintenance day falls on a Monday, the regular schedule for Monday will be overridden by the Maintenance schedule at 6 am and become effective again at 10 am sending the day value.
Temporary Disable : If this value is scheduled, the entire scheduler is disabled until a new event is scheduled in a daily schedule of the same or higher priority than the one that has the temporary disable event. This type of event can be used to define periods for manual override.
Please also refer to the technology-specific limitations described in Section 6.12 to learn
about special behavior of the respective networking technology.
Version 4.0
Figure 76: Example using withdraw in an exception schedule.
The configuration of exceptions is done by calendar patterns in the calendar. Each calendar pattern contains a number of pattern entries. These entries can define the following:
A single date: This defines a singe date. Wildcards may be used in the year to specify
July 14 th
of every year.
LOYTEC electronics GmbH
L-INX User Manual 92 LOYTEC
5.3.4 Trending
Trending refers to the ability to log values of data points over time. A trend log object is responsible for this task. It is configured, which data points shall be trended. Log records are generated either in fixed time intervals, on change-of-value (COV) conditions, or when a trigger is activated. Trend log objects can trend either local or remote data points.
The trend data is stored in a binary format on the device. The capacity of a given trend log is configured. The trend log can be operated in one of two modes: In linear mode the trend file fills up until it reaches its capacity. It then stops logging. In ring buffer mode the oldest log records are overwritten when the capacity is reached.
A fill-level action can be activated, whenever the trend log has logged a percentage of its log size with new log records. A fill-level condition of 70% on a trend log with 1000 items capacity will activate the fill-level trigger every 700 logged records. This trigger can be used to send E-Mails.
Trended data points can be logged as their actual values at given time instants or as an aggregated value over the defined log interval. Aggregation can be calculated as minimum, maximum, or average. Aggregation can be beneficial, if the trended value changes more frequently than the selected log interval. Using aggregation, the log interval can be chosen to limit the amount of logged data while preserving information of the trended value.
How many data points can be trended in one trend log is limited by the underlying technology. So are some of the log modes. Refer to the technology sections for more information.
5.3.5 E-mail
A date range: This defines a range. Starting with a start date and ending with the end date. No wildcards should be used.
A Week-and-Day definition: This defines dates based on a week, such as every 1st
Friday in a month, every Monday, every last Wednesday of a month.
While exception days of a calendar are accessible to all schedules on a device, specific exceptions can be defined, which are embedded into a specific schedule. These are referred to as an embedded calendar . In contrast to a regular calendar each calendar pattern of an embedded calendar can hold exactly one date entry. This can be a single date or a date range. The embedded exception days are only visible to the schedule they are defined in.
Apart from these restrictions, embedded calendars behave like the regular calendar. Figure
75 shows an example for an embedded exception day named ‗*-12-24‘.
A schedule defines at which time instants certain states of the scheduled data points are maintained. The next-state feature allows looking ahead into the future and predicting when the next scheduled state will occur. There are two data points involved: the time-to-nextstate is a counter in minutes to the next scheduled event, and the next-state data point is the state of the next scheduled event. This information can be used by controllers to optimize their algorithms (e.g., pre-heat a room for the scheduled occupancy state). Use the
SNVT_tod_event in CEA-709 to accomplish this task.
When a scheduler is executing the schedule on the local device, it is called a local scheduler . Such a scheduler is configured to schedule data points and later its daily schedules can be modified. When accessing the daily schedules of a scheduler, which executes on a remote device, the object is called a remote scheduler . A remote scheduler has the same interface to the user to modify daily schedules. A remote scheduler object can be used as a user-interface for schedulers that execute on different devices.
The e-mail function can be combined with the other AST features. The format of an e-mail is defined through e-mail templates . An e-mail template defines the recipients, the e-mail
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 93 LOYTEC text, value parameters inserted into the text and triggers, which invoke the transmission of an e-mail. An e-mail template can also specify one or more files to be sent along as an attachment.
A prerequisite to sending e-mails is the configuration of an e-mail account on the device.
This can be done on the Web UI (see Section 4.2.15). It is recommended to use the e-mail
server of your Internet provider. For public mailers, enable the required authentication.
Please note that the device does currently not support the SS/TLS e-mail authentication mechanism. Therefore, Hotmail and gmail cannot be used.
The amount of generated e-mails can be limited using a rate limit algorithm. The transmission of e-mails can be disabled altogether by using a special data point. That data point can be scheduled or driven over the network.
If an e-mail cannot be sent (e.g. the mail server is not reachable), the mail delivery is retried up to 24 times every 30 minutes.
5.4 CEA-709 Technology
5.4.1 CEA-709 L-INX Device
The CEA-709 L-INX implements a L ON M ARK device which exposes network variables
(NVs) and configuration properties (CPs) from the CEA-709 network to data points in the automation server.
The L-INX has one physical FT port and one IP-852 port, which is accessible over
Ethernet. On the L-INX with the RNI option, the automation server node is internally connected either to the FT port or to the IP-852 port. Which one is used can be configured
in the CEA-709 configuration (see Section 4.2.6). The schematic is shown in Figure 77 (a).
If configured for the FT channel, the L-INX provides an RNI for remote access to the FT channel. The RNI can be used to commission nodes and trouble-shoot communications on the FT channel.
The L-INX with the CEA-709 router connects the FT port and the IP-852 port. On the L-
INX the automation server node is always internally connected to the FT port. The
schematic is shown in Figure 77 (b).
LINX
Server
Node
LINX
Server
Node
LINX
Router
IP-852
Channel
Version 4.0
FT or IP-852 Channel FT Channel
(a) (b)
Figure 77: (a) OPC server node on LINX-100, (b) OPC server node and router on the LINX-101.
If the automation server shall only expose network variables from the local FT channel and there is no IP-852 backbone, then the router is not needed. In this case, the user needs to commission only the L-INX server node. To attach the FT channel to an IP-852 backbone,
LOYTEC electronics GmbH
L-INX User Manual 94 LOYTEC
the CEA-709 router in the L-INX needs to be commissioned. See Chapter 7 for more
information on the built-in router and configuration server.
5.4.2 CEA-709 Data Points
Data points in the CEA-709 network are known as network variables (NVs). They have a direction, a name, and a type, known as the standard network variable type (SNVT) or userdefined network variable type (UNVT). In addition to NVs, also configuration properties
(CPs) in the CEA-709 network can be accessed as data points. Both standard CP types
(SCPTs) and user-defined CP types (UCPTs) are supported.
The typical procedure in configuring the device consists of the following steps:
1.
Select the data points of the network to be used on the device (e.g., select the NVs in the CEA-709 network nodes)
2.
Create necessary registers, math objects
3.
Select those data points on the device, which shall be exposed as OPC tags or the PLC
The CEA-709 NVs on the device can be created in three different ways:
Static NV : For each selected NV on the network there is a static NV created on the device. This NV can be bound to the NV on the network. Note that adding static NVs to the device results in a change to the default XIF file. The device is assigned a new
―model number‖ to reflect this change (see Section 5.4.3). Static NVs are the way to
use NVs in non-LNS systems, where NVs shall be bound instead of using polling.
Dynamic NV : For each selected NV on the network there is a dynamic NV created on the device. Compared to static NVs, dynamic NVs do not change the XIF interface of the device. The dynamic NVs are created by the network management tool. Currently, only LNS-based tools can manage dynamic NVs. As for static NVs, with dynamic NVs it is possible to use bindings instead of polling.
External NV : The selected NVs on the network are treated as external NVs to the device. The device doesn‘t create any NVs on the device, but instead uses polling to read from those NVs and explicit updates to write to the NVs. Therefore, no bindings are necessary for external NVs. For input data points using external NVs however, a poll cycle must be configured. If not configured explicitly, a default poll cycle of 10 sec. is chosen. The default poll cycle can be changed in the project settings menu.
Based on the NV the data point is derived from, the following kinds of data points are created:
Simple NVs that hold only one scalar value, e.g., SNVT_amp: Those kinds on NVs are represented as analog data points. The data points holds the current value, NV scaling factors are applied.
Simple NVs based on an enumeration, e.g., SNVT_date_day: Enumeration types result in multi-state data points. They represent the state of the NV.
Structured NVs that consists of a number of fields, e.g., SNVT_switch: All structured
NVs are represented as user point. That is, the data point is structured similar to the NV it is based on. Beneath the user data point, the individual structure fields are presented as ―sub-data points‖.
For more information on the different types of network variables and their implications
please refer to the application note in Section 17.2. For CPs the allocation type ―File‖ is
used.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 95 LOYTEC
5.4.3 Static Interface Changes
The device can be configured to use static NVs. Unlike dynamic NVs, static NVs cannot be created in the network management tool. They are part of the static interface and are usually compiled into the device. When static NVs are used, the device changes its static interface and boots with a new one.
Each time the static interface of the device changes (i.e., static NVs are added, deleted, or modified), the model number is changed. The model number is the last byte of the program
ID. Thus, a change in the static interface results in a change of the program ID and a new device template needs to be created in the network management tool. A new device template usually means that the device has to be deleted and added again in the database.
All bindings and dynamic NVs have to be created again for the new device.
When the Configurator software is connected via LNS, it supports the process of changing the device template for the new static interface. It automatically upgrades the device template of the L-INX device in the LNS database and restores the previous bindings and dynamic NVs. If the L-INX is not configured with an LNS-based tool, this support is not available. The new static interface is only available in a new XIF file or by uploading the new device template into the database. For more information on the static interface and
device templates please refer to the application note in Section 17.2.
5.4.4 Limitations for Local CEA-709 Schedulers
CEA-709 schedulers and the CEA-709 calendar adhere to the L ON M ARK standard objects.
For CEA-709, certain restrictions exist that need to be kept in mind. Attached data points can either represent an entire NV or individual elements of a structured NV. CEA-709 schedulers may have several different groups of data points attached, i.e., the value preset may consist of more than one element. For example, a CEA-709 scheduler might schedule a
SNVT_temp and a SNVT_switch and have 3 elements in each value preset as depicted in
Figure 78: Example value presets in CEA-709 schedulers.
Priorities of exception days in a CEA-709 scheduler range from 0 (the highest) to 126 (the lowest). The value 127 is reserved as a default for weekdays.
Further, the implementation as L ON M ARK standard objects requires the use of configuration properties. If the number of CEA-709 schedulers or their capacities for daily schedules and value presets is changed, the resource and static interface of the CEA-709 port changes. The resources reserved for L ON M ARK calendar and scheduler objects can be changed in the
project settings (see Section 6.3.4). When downloading a project, the software verifies if
sufficient resources have been configured. If it detects a problem, the user is notified to update the project settings. The Auto-Set feature automatically selects the right amount of resources.
5.4.5 Limitations for CEA-709 Alarm Servers
Local CEA-709 alarming supports only one alarm server object. This alarm server object is represented by the device‘s L
ON M ARK node object and facilitates the SNVT_alarm2 output network variable. Acknowledging alarms in the alarm server is adhering to the L ON M ARK specification and relies on the RQ_CLEAR_ALARM mechanism.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 96 LOYTEC
5.4.6 Limitations for Local CEA-709 Trends
Local CEA-709 trend objects support trending multiple data points in all trend modes, interval, COV, and trigger. The enable data point is also supported. All data points can be
NVs, registers or of any other technology. There is no L ON M ARK object linked to the trend object. Consequently, trend data cannot be accessed over a L ON M ARK mechanism.
5.5 BACnet Technology
5.5.1 BACnet Data Points
Data points in the BACnet technology are known as BACnet objects. They have a specific type (e.g. analog input or binary output) and a set of properties, which describe the data point more closely. The actual value is stored in the ―Present_Value‖.
On the device, there exist two classes of BACnet data points:
BACnet server objects (SO): These BACnet objects configured by the Configurator software to be allocated locally on the device. These objects can be accessed by the
BACnet building control system or operating workstations. They support COV subscriptions to deliver value changes in an event-driven way.
BACnet client mappings (CM): For certain applications, it is necessary that the device acts as a BACnet client. This functionality can be configured by activating a client mapping . Client mappings can be of the type Poll , COV , Write , or Auto . This specifies how the BACnet client accesses other BACnet objects on the BACnet network. The
Auto method determines the best way (poll, COV, or write) to talk with other server objects. Poll is used for objects that need to read data from other BACnet objects in a periodic manner. COV is used to subscribe for COV at other BACnet objects in order to get updates in an event-driven fashion. Write is used to send updates to other
BACnet objects.
The direction of BACnet server objects deserves a closer look. The direction specified for data points in the Configurator software always refers to the network view of the communication. The definition of input and output objects in BACnet, however, refers to the process view, which is opposite to the network. Therefore, a BACnet analog input (AI) object is modeled as an analog output data point. The direction of client mappings naturally refers to the network communication. Therefore, a write client mapping is represented as an analog output data point.
In BACnet commandable objects can be written with values at a certain priority. The value with the highest priority is in effect. When revoking a written value, the NULL value is written. This takes back the value. When all written values are withdrawn, the
Relinquish_Default value is in effect.
The default value feature of a data point is mapped to the Relinquish_Default property for commandable objects. For BACnet objects, which are not commandable, the Present_Value is initialized with the specified default value.
5.5.2 BACnet Alarming
BACnet alarming on the device is based on the intrinsic reporting mechanism. Currently, algorithmic reporting is not supported. Alarm conditions can only be applied to data points, which map to BACnet server objects. If defined, the intrinsic reporting properties of the underlying BACnet objects are enabled. Alarm conditions can be specified for analog input, output, value objects (AI, AO, AV), for binary input, value objects (BI, BV), and for multistate input, value objects (MSI, MSV). Since there is no value source for the
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 97 LOYTEC
Feedback_Value property available, alarm conditions cannot be defined for binary output
(BO) and multi-state output (MSO) objects.
Alarm servers in the BACnet technology are mapped to BACnet Notification Class (NC) objects. Each alarm server is mapped to one NC. The notification class number can be configured in the object instance number property of the alarm server object.
Remote alarms in the BACnet technology refer to a remote NC object. When the device starts up, the remote alarm object reads out the current alarm state of the remote NC and reporting objects. To get notified about alarm transitions during run-time, the device registers in the Recipient_List of the remote NC object.
5.5.3 BACnet Schedulers and Calendars
BACnet schedulers and the BACnet calendar adhere to the standard schedule and calendar object in BACnet. For each scheduler a BACnet Schedule object is created. The calendar deserves a closer look. For each calendar pattern a BACnet Calendar object is created. The visible calendar on the Web UI is therefore a collection of BACnet calendar objects. Each calendar pattern therefore is associated with a BACnet object instance number. The calendar pattern ―Holidays‖ is for example visible as CAL,1 on the BACnet port.
The BACnet schedule object allows only objects of one selected data type to be scheduled.
Therefore, schedulers on BACnet can only schedule one class of data points (e.g., only one group of analog data points). As a consequence, the value preset in BACnet always has only one element. The name of the value preset is not stored in BACnet. It is not accessible over the BACnet network, either. Therefore, a default name is created, such as ‗Value(22)‘ for an
analog value. An example of two scheduled BACnet objects is shown in Figure 79.
Figure 79: Example value presets in BACnet schedulers.
Priorities of exception days in a BACnet scheduler range from 1 (the highest) to 16 (the lowest). Weekdays in BACnet have no priority.
Changing the number of calendar patterns in a BACnet calendar can only be done through the configuration software and not during run-time. The individual calendar pattern entries in the calendar patterns can be changed at run-time. Therefore, it is advisable to reserve a suitable number of calendar patterns in a BACnet calendar and leave them empty if not needed immediately.
5.5.4 BACnet Trend Logs
Trending in the BACnet technology is based on the BACnet TrendLog object. A number of restrictions apply to trend log objects in BACnet. Trend log objects must be created by the
Configurator software. These objects are accessible over the BACnet network for other
BACnet devices and operator workstations (OWS). All configuration properties can be modified by the Configurator software as well as an OWS. The number of trend log objects cannot be changed at run-time. Therefore, if it is intended that an OWS configures the trend logs, a suitable number of empty trend log objects (i.e., without attached data points) must be created in the Configurator software.
In BACnet trend logs, only one data point can be trended per trend log object. The trended data point can be either a local BACnet server object or a remote BACnet object accessed through a client mapping. Data points of other technologies and the min/max/avg algorithms cannot be trended in this firmware version.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 98 LOYTEC
BACnet trend logs are limited to interval and COV logs. The trigger mode is not supported in BACnet. The setting linear and ring-buffer logging is mapped to the Stop_When_Full property of the underlying BACnet trend log object. This setting in the Configurator software is a default and can be overridden by writing to the Stop_When_Full property by the OWS.
If an enable data point is configured by the Configurator software, the Log_Enable property is written with the value of that data point. If no enable data point is configured, the
Log_Enable is TRUE as a default and can be modified over the network.
The fill-level action is mapped to generating a buffer event notification in the BACnet trend log object. The fill-level trigger can still be used for e-mails even if no notification class is configured in the BACnet trend log object. The fill-level percentage maps to the
Notification_Threshold property. The percentage setting in the Configurator software is a default and can be changed by the OWS over the network.
5.6 IEC61131 Variables
IEC61131 variables are used to exchange data with the IEC61131 program. These variables are represented in the data point configuration as register data points and can be connected to other data points, e.g. to CEA-709 NV points, via data point connections.
In contrast to CEA-709 or BACnet variables, IEC61131 variables are always represented as single data point. In case of scalar values (representing CEA-709 scalar or enumeration types) one of the following basic data types might be used:
Double : A register of base type double is represented by an analog data point. It can hold any scalar value. No specific scaling factors apply.
Signed Integer : A register of base type signed integer is represented by a multi-state data point. This register can hold a set of discrete states, each identified by a signed stats ID.
Boolean : A register of base type boolean is represented by a binary data point. This register can hold a Boolean value.
Structured IEC61131 variables, representing for example structured NVs, or customer defined IEC61131 structures, are stored as user type:
User : A user data point contains un-interpreted, user-defined data. The data is stored as a byte array. A user data point does not include any other meta-data. This type of data point also serves as a container for otherwise structured data points and represents the entire data structure. User data points can only be connected to other user data points of the same data length.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 99
6 The L-INX Configurator
LOYTEC
This Chapter gives step-by-step instructions on how to commission the LINX, create a data point configuration with L ON M ARK network variables, BACnet objects, and how to expose those data points to the automation server.
6.1 Installation
6.1.1 Software Installation
The L-INX Configurator must be used to setup the data point configuration of the L-INX automation server. The Configurator is installed as a plug-in tool for all LNS-based network management tools as well as a stand-alone tool (for systems without LNS).
System requirements:
LNS 3.1, Service Pack 8 or LNS TE SP5 or higher (for LNS mode),
Windows XP, Windows 2003 Server, Windows Vista, Windows 7, or Windows 2008
Server.
The L-INX Configurator can be downloaded from the LOYTEC Web site http://www.loytec.com. When asked for the type of installation, there are two options to choose from. Select Typical to install the required program files.
6.1.2 Registration as an LNS Plug-In
If the CEA-709 L-INX shall be configured using LNS-based tools (e.g., NL200 or
LonMaker), the L-INX Configurator needs to be registered as an LNS plug-in. In the following, the process is described for LonMaker TE. Otherwise, please refer to the documentation of your network management tool on how to register an LNS plug-in.
To Register in LonMaker TE
1.
Open LonMaker and create a new network.
2.
Click Next until the plug-in registration tab appears in the Network Wizard. Select the
LOYTEC LINX Configurator (Version X.Y) from the list of Not Registered (see
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 100 LOYTEC
Note:
Figure 80: Select the Plug-in to be registered.
3.
Click Register . The Configurator now appears in the Pending list.
4.
Click Finish to complete the registration. Device templates for the LINX-10X are added automatically and XIF files are copied into the LNS import directory.
If you are using multiple databases (projects) make sure you have registered the plug-in in each project.
5.
Under LonMaker
Network Properties
Plug-In Registration make sure that the
LOYTEC LINX Configurator (Version X.Y) shows up under Already Registered .
Version 4.0
Figure 81: Check that the L-INX Configurator is properly registered.
LOYTEC electronics GmbH
L-INX User Manual 101 LOYTEC
6.1.3 CEA-709 Operating Modes
The Configurator can be used in on-line, off-line, and stand-alone mode. On-line and offline mode refers to the 2 operating modes of your LNS network management software.
On-line Mode : This is the preferred method to use the Configurator. The network management tool is attached to the network and all network changes are directly propagated into the network. This mode must be used to add the device, commission the device, extract the port interface definition, and download the configuration into the device.
Off-line Mode : In off-line mode, the network management software is not attached to the network or the device is not attached to the network, respectively. This mode can be used to add the device using the device templates, create the port interface definition and to make the internal connections.
Stand-alone Mode : The Configurator can also be executed as a stand-alone program.
This mode is useful for the engineer who doesn‘t want to start the configuration software as a plug-in from within network management software (e.g., NL-220,
LonMaker or Alex). Instead the engineer can work directly with the device when online or engineer it offline.
6.2 Data Point Manager
The Configurator uses a central concept to manage data points. The data point manager is located on the Datapoints
tab as shown in Figure 82. It is used to select, create, edit and
delete data points. The dialog is divided into three sections:
The folder list (number 1 in Figure 82),
The data point list (number 2 in Figure 82),
And a property view (number 3 in Figure 82).
2
1 3
Figure 82: Data Point Manager Dialog.
6.2.1 Folder List
At the left is a list of folders which is used to sort the available data objects by their category. There are a number of predefined folders available:
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Version 4.0
102 LOYTEC
Imported : This folder has a number of sub-folders for different import methods: o CEA-709 CSV File: This folder is used to display data points imported from
CSV files. o CEA-709 LNS Scan : This folder is used to hold data retrieved from a network database scan. o CEA-709 Network Scan : This folder holds NVs scanned online from an attached CEA-709 network. o CEA-709 Devices from XIF : This folder holds sub-folders and NVs created from XIF files. o BACnet Network Scan : This folder is used to display data points retrieved by an online scan of the BACnet network. o BACnet EDE File : This folder is used to display data points imported from an EDE file.
Data objects in the import folder are not stored on the device when the project is downloaded. They represent data objects which are available on remote devices and are shown here as templates to create suitable data objects for use on the device by selecting the Use on Device option.
Filter Templates : This folder contains the created data point templates. They contain a set of properties, which are applied to data points, when they are created on the device.
There is a sub-folder for filter templates specific to different technologies, e.g. CEA-
709.
LINX-XXX : This is the device folder of the LINX. It contains all the necessary data points which constitute to the LINX‘s configuration. These data points are created on the device when the configuration is downloaded. The following subfolders may be present depending on the particular model: o Favorites : This folder contains freely configurable symbolic links to data points, which may reside anywhere in the folder structure. This folder represents a way to assemble an alternate view to the data point hierarchy.
This folder is also available on the Web UI or the LCD UI. o System Registers : This folder contains system registers, which provide information on the device itself. o
User Registers : This folder holds user-definable registers. These registers are not visible on the underlying network and are intended for internal usage. o CEA-709 Port : This folder contains data points, schedulers, calendars, trend logs, statistics, and remote data points of the CEA-709 network technology.
o BACnet Port : This folder contains data points, schedulers, calendars, trend logs, statistics, and remote data points of the BACnet network technology. See
Global Objects : This top-level folder contains sub-folders that organize specific application objects that operate on data points. o
E-mail Configuration : This folder contains e-mail templates. An e-mail template defines the destination address and text body of an e-mail, which is triggered by data points and may contain data point values or file attachments.
To create an e-mail template, select the folder and use the context menu. o Math Objects Configuration : This folder contains math objects. Math objects are used to perform a predefined calculation on a number of input data points and write the result to a defined set of output data points. Each math object contains one formula. To create a math object, select the folder and use the context menu.
LOYTEC electronics GmbH
L-INX User Manual 103 LOYTEC o Alarm Log Configuration : This folder contains the alarm log objects. Each alarm log object creates a historical log of alarm transitions of one or more alarm objects (alarm server or client). To create an alarm log, select the folder and use the context menu.
Using the context menu on a folder, sub-folders may be created to organize the available objects. If new objects are created automatically, they are usually placed in the base folder and can then be moved by the user to any of his sub-folders. Note, that the folder structure described above cannot be changed by adding or deleting folders at that level.
6.2.2 Network Port Folders
Each network port folder on the device has the same structure of sub folders. These sub folders are:
Datapoints : This folder holds all data points, which are allocated on the network port.
To create a data point, select the folder and use the context menu.
Calendar : This folder is used to hold a locally available calendar object with its calendar patterns (definitions of day classes like holiday, maintenance day, and so on).
Current devices allow one local calendar object. To create a calendar, select the folder and use the context menu.
Scheduler : This folder is used for local scheduler objects. Each of these objects will map to a local scheduler on the device‘s network port. Configuring schedules through these objects actually transfers schedule configuration data to the underlying scheduler objects on the network port. To create a scheduler, select the folder and use the context menu.
Alarm : This folder is used for local alarm server objects. Each of these alarm server objects represent an alarm class, which other objects can report alarms to. Other devices can use the alarm server object to get notified about alarms. To create an alarm server object, select the folder and use the context menu.
Trend : This folder is used for local trend log objects. Each of these objects will be able to trend data points over time and store a local trend log file. To create a trend log object, select the folder and use the context menu.
Statistics : This folder contains registers, which provide communication statistics specific to the network port.
Remote Devices : This folder is used to collect all remote calendars, schedulers, trend logs, and alarm client objects, which were created from network scan data. For each remote device, a subfolder will be created where the objects referencing this device are collected.
6.2.3 Data Point List
At the top right, a list of all data objects which are available in the selected folder is shown.
From this list, objects may be selected (including multi-select) in order to modify some of their properties. Click on the Include Subfolders button to show all data points of the selected data point folder and all its sub-folders. This can be a convenient way for multiselect across folders. To filter for data point names, enter a search text into the Datapoint
Name Filter text box and hit Enter . A drop-down list holds the previously used filters available.
Version 4.0
The list can be sorted by clicking on one of the column headers. For example, clicking on the Direction column header will sort the list by direction. Other columns display
Datapoint Name , NV name , SNVT , Object Name , object Type and Instance number, allocation ( Alloc ) of server object (SO) and/or client mapping (CM), number of attached
Client Maps , and the data point unique ID . To apply the current sort order as the new data point order on the device, right-click on the column header and select Renumber
Datapoints . Alternatively, select from the menu Tools
Renumber Datapoints.
LOYTEC electronics GmbH
L-INX User Manual 104 LOYTEC
The OPC column provides check boxes for each data point. If checked, the respective data point is exposed to OPC on the device. Deselect the check box, if a data points shall not be exposed to OPC. Note, that deselected data points do not add to the OPC tag limit.
The Param column provides check boxes for each data point. If checkded, the respective data point is exposed to the parameter file. The PLC column provides check-boxes, which define if data points are visible inside the IEC61131 PLC program.
New objects may be created in the selected folder by pressing the New button to the right of the list or via the New command in the context menu. A plus sign in the list indicates that the data point contains sub-points. Clicking on the plus sign expands the view.
For the alarming, scheduling, trending (AST) features, there are columns, which display
icons for data points that are attached to an AST function. See Table 11 for details.
Icon Data Point Usage
Data point is scheduled
Data point has an active alarm condition
Data point has an inactive alarm condition.
Data point is a trigger for e-mails
Data point used for trending
Table 11: Icons for used data points in the data point list view.
6.2.4 Property View
When one or multiple data points are selected, the available properties are displayed in the property view. Properties which are read-only are marked with a lock sign. When applying multi-select, only those properties common to all selected data points are displayed. Depending on the network technology and data point class, different properties may exist.
Data point properties common to all technologies:
Datapoint Name : This is the technology-independent data point name. This name may be longer than and different to the name of the native communication object (i.e., network variable). Data point names must be unique within a given folder. The maximum length is limited to 64 ASCII characters.
Datapoint Path : This informational property specifies the entire path of the data point within the data point hierarchy. The maximum length is limited to 64 ASCII characters.
Datapoint Description : This is a human-readable description of the data point. There are no special restrictions for a description.
OPC Tag : If enabled, the data point will be exposed to OPC. If not enabled, this data point does not contribute to the limit of OPC tags.
Parameter : If enabled, the data point will be exposed to the parameter file. Those data points are visible to the LWEB-821 master parameter editor. A parameter data point is
also persistent. See Section 5.1.5.
PLC IEC61131 Variable : If enabled, the data point will be usable in the IEC61131
PLC program.
Use Pollcycle value as : For input data points, this property defines whether the input
shall use a receive timeout or be constantly polling. See Section 5.1.2.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 105 LOYTEC
Poll on Startup : For input data points this property defines, whether the data point shall be polled once at start-up. Poll-on-startup can be enabled independently of the
poll cycle. See Section 5.1.2.
Pollcycle : For input data points, this property defines the poll cycle in seconds. Set this
property to 0 to disable polling. See Section 5.1.2.
Receive Timeout : For input data points, this property defines the receive timeout in
seconds. Set this property to 0 to disable polling. See Section 5.1.2.
Min Send : For output data points, this property defines the min send time in seconds.
Max Send : For output data points, this property defines the max send time in seconds.
Send-on-delta : For output data points this property defines, if value updates shall be sent only once they meet the COV condition of the data point. For analog data points the analog COV increment is used. If not checked, updates are always transmitted
according to min and max send times. See Section 5.1.7.
Use Linear Scaling : If this property is enabled, the analog values are pre-scaled from the technology to the data point. This scaling is in addition to any technology-specific scaling factors. If enabled, the properties Custom Scaling Factor and Custom Scaling
Offset
accept the scaling factors. See Section 5.1.7.
Custom Scaling Factor, Custom Scaling Offset : These properties only exist, if linear
scaling is enabled. They apply to analog data points only. See Section 5.1.7.
Only notify on COV : This property assists for binary and multi-state input data points.
It defines, if a data point shall trigger an update only when the value changes or on every write. If this is enabled, consecutive writes with the same value do not trigger an update. If you want to convey every write, disable COV on the data point.
Persistent : This property defines, if the last written value shall be stored as a persistent value. Persistent data points restore that value after a restart from the persistent storage.
Default Value
: This property defines a default value (see Section 5.1.3). Enter a
default value to enable this feature in the data point. Delete the value entirely to remove the default value. If no default value is defined, this property reads ―N/A‖. The default is no default value.
Point Type : This is the base data point type, e.g., ―Analog Datapoint‖.
Direction : This is the data point direction. Use input or output as directions.
Unit Text : For analog data points this property contains a human-readable text for the engineering units of the scalar value, e.g., ―kilogram‖.
Analog Datapoint Max Value : For analog data points this property contains the upper limit of the supported value range. Note that this does not define an alarm limit.
Analog Datapoint Min Value : For analog data points this property contains the lower limit of the supported value range. Note that this does not define an alarm limit.
Analog Datapoint Precision : For analog data points this property defines the number of decimals. ‗0‘ specifies an integer value. Display units may use this to format the floating point value accordingly.
Analog Datapoint Resolution : For analog data points this property defines the smallest possible value increment.
Analog Point COV Increment : This property is valid for analog input data points. It specifies by which amount the value needs to change, before an update is generated. If every write shall generate an update even when the value does not change, specify 0 as
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 106 LOYTEC the COV increment. If any value change shall generate an update, delete the value, which results in Any .
Active Text : For binary data points this property defines a human-readable text for the active state (true).
Inactive Text : For binary data points this property defines a human-readable text for the inactive state (false).
State Count : For multi-state data points this property defines the number of discrete states.
State Text : For multi-state data points this property defines a human-readable state label for each state.
6.2.5 Managing Multistate Maps
Multistate data points have a descriptive set of state texts for their state IDs. To manage those state IDs and state texts among many multistate data points, they refer to multistate maps . Some technologies have a fixed set of such multistate maps others have freely configurable multistate maps (e.g, user registers). Editing a multistate map affects all multistate data points, which are using that particular map. It is not necessary to edit each data point individually.
To Edit a Multistate Map
1.
Click on the button in the State Count property of a multistate data point. This
opens the multistate map manager as shown in Figure 83.
Version 4.0
Figure 83: Assign multistate maps in the multistate map manager.
2.
Select an existing state map in the State Map list and click on Assign . Maps that are fixed and cannot be changed are marked with a lock symbol .
3.
If a new multistate map shall be created, change to the Edit tab.
4.
Click on the Create button and enter a new multistate map name. Then hit Enter .
5.
In the Configure States box enter the desired number of states and click Set .
LOYTEC electronics GmbH
L-INX User Manual 107
6.
Edit the state texts as needed.
LOYTEC
7.
Change back to the Assign tab.
8.
Select the newly created multistate map and click the Assign button. The assigned map is now displayed next to the data point.
6.2.6 Organizing Favorites
There is a special Favorites top-level folder in the device data point folder hierarchy. This folder contains freely configurable symbolic links to data points, which may actually reside anywhere in the folder structure. This folder represents a way to assemble an alternate view to the data point hierarchy.
To configure favorites, select any data point from any location in the data point folder hierarchy and drag it onto the favorites folder. This will create a data point link, which is displayed in the data point list:
The link name can be edited to something different that the original data point name. The contents of this folder are also available on the Web UI or the LCD UI. The link names are displayed there. The data point links can also be individually exposed to the OPC server notwithstanding if their original source is exposed or not.
Furthermore, the user can create sub-folders in the favorites folder and beneath to build a hierarchy of data point links.
6.2.7 CEA-709 Properties
Apart from the common data point properties discussed in Section 6.2.4 the data points of
the CEA-709 technology have additional properties. Depending on if a NV is local or external (remote), the properties may vary.
NV Allocation : This property defines how a data point shall be allocated on the device.
Choices are ―Static NV‖, ―Dynamic NV‖, and ―External NV‖. If the allocation type cannot be changed, this property is locked.
SNVT : This property defines the SNVT of the NV, e.g., ―lux (79)‖.
Invalid Value : This property defines the ―invalid value‖ for the NV. If set, this specific value will be interpreted as ―invalid‖ in the data point. If known by the SNVT, the invalid value is filled in. Otherwise, the user can specify an invalid value.
CEA-709 Mapping Information : This information is derived from the SNVT. It defines how the NV contents are mapped to the data point.
NV Scaling A, B, C : These are the scaling factors known from the SNVT table. The scaling factors are applied to translate a raw NV value into the scalar representation of the data point.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 108 LOYTEC
Data Type : This is the basic NV data type. This is usually filled in from the SNVT definition.
Local NV Member Index : This property specifies the NV member index within a given functional block. This must be a unique index in the functional block, which identifies the NV after other NVs have been added or removed from the interface.
Local/Remote NV Index : This property specifies the NV index. For local, static NVs this is the NV index of the static NV. For external NVs, this is the NV index of the NV on the remote device.
Local/Remote NV Name : This property specifies the programmatic name of the NV.
For local, static NVs this is the programmatic name of the static NV. For external NVs, this is the programmatic name of the NV on the remote device.
Local/Remote Functional Block : This property specifies the programmatic name of the NV. For local, static NVs, one of the reserved functional blocks can be selected.
Local/Remote NV Flags : This property specifies the NV flags. For local (static or dynamic) NVs, the flags can be configured. For external NVs, these flags are only informational.
Remove NV Information : For external NVs, this property contains the information on the remote device and the NV selector on that device.
Remote Device ID : For external NVs, this property contains information on the remote device by listing the program ID and location string.
Remote Device Address : For external NVs, this property contains the CEA-709 network addressing information to access the node, i.e., subnet, node, and NID.
Retry Count : For external NVs, this property defines the retry count. The default is 3.
Repeat Timer : For external NVs, this property defines the repeat timer in milliseconds. The default is 96 ms.
Transmit Timer : For external NVs, this property defines the transmit timer in milliseconds. The default is 768 ms.
LNS Network Path : If available from an LNS scan, this property specifies the LNS network path of the device where the given NV exists.
LNS Channel Name : If available from an LNS scan, this property specifies the LNS channel name of the device where the given NV exists.
6.2.8 BACnet Properties
Apart from the common data point properties discussed in Section 6.2.4 the data points of
the BACnet technology have additional properties. Depending on if a NV is local or external (remote), the properties may vary,
Engineering Units : For analog BACnet server objects, this property defines the engineering units from the BACnet standard. One of those units can be chosen from a drop-down box, if this property is not locked.
Server Object Type : This property defines the BACnet object type of the underlying
BACnet server object. It can be changed within the class, i.e., for an analog data point, the server object type analog input, analog output, or analog value can be chosen.
Commandable : This property defines, if the underlying BACnet server object is commandable. For BACnet value objects (AV, BV, MSV) this property can be edited to create commandable or non-commandable BACnet value objects.
Relinquish to invalid value : This property defines whether the data point maintains the Relinquish_Default value, if the priority array is empty or assumes the invalid value. By default, this property is false and the Relinquish_Default value is used.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 109 LOYTEC
Setting this property to true can be beneficial when used in a connection to withdraw a value in another technology.
Server Object Name : This property defines the object name of the underlying BACnet server object. It must be unique among all server objects. It can be up to 64 characters.
Server Object Instance No : This property defines the object instance number of the underlying BACnet server object.
Server Object Description : This property defines the object description of the underlying BACnet server object. It can be left blank.
Server Object Device Type : This property defines the object device type of the underlying BACnet server object. It can be left blank.
Allocate Server Object : This Boolean property defines, if a server object shall be allocated for the data point. This option is useful, when a local server object shall be allocated for a client mapping.
Allocate Client Mapping : This Boolean property defines, if a client mapping shall be allocated for the data point. This option is always set, if at least on client mapping is attached.
Client Map Count : This property defines the number of client mappings attached to a data point. A data point can have one read client map or n write client mappings.
Client Map [n] : This is a list of client mappings. The property shows a summary of the client mapping parameters. To edit a client mapping click on the … button.
Confirmed COV : This Boolean property defines, if a client map subscribes with the confirmed COV service. If not enabled, the unconfirmed COV is used.
6.3 Project Settings
The project settings allow defining certain default behavior and default settings used throughout the project. To access the project settings go to the menu Settings
Project
Settings… . This opens the project settings dialog, which provides several tabs as described in the following sections.
6.3.1 General
The general tab of the project settings as shown in Figure 84 contains settings independent
of the technology port. The settings are:
Project Name : This setting allows entering a descriptive name for the project.
Device Configuration Download Default : This group of settings defines, how the download of device configuration parameters shall proceed. If Download only data point configuration is selected, the configuration download does not download anything else than the data point configuration. If Ask is selected, the download will pop up a dialog in which the user can choose what to download. If Download specific is selected, the project settings of this dialog determine what is downloaded onto the device. As a default, the configuration download includes the schedules and calendar patterns but does not include the device settings as defined in the Device
Configuration
Automatically add downloaded device to the OPC Bridge : This option is only available, if LOPC-BR800, the LOYTEC OPC bridge software, is installed on the same
PC. If enabled, the LINX-20X device, a configuration is downloaded to, is automatically added to the OPC server list in the bridge. For more information on using
LOPC-BR800 refer to Section 9.3.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 110 LOYTEC
Automatically structure imported data points for faster OPC browsing : This option enables the automatic generation of sub-folders when using data points on the device. A sub-folder is created for each scanned or imported device. This allows OPC clients to browse the OPC tags in a hierarchical way.
Figure 84: General Project Settings.
6.3.2 Data Point Naming Rules
The data point naming rules tab (see Figure 85) allows specifying how data point names are
automatically derived from scanned network variables. This function is applicable to the
CEA-709 technology only. The preview shows how names would look like, when the check marks are modified.
Use programmatic name, Use display name : This option decides, how the data point name is extracted from the NV. The programmatic name is the NV name from the XIF file. The display name may be extracted from LNS, which allows to display a different name than the programmatic name.
Figure 85: Data Point Naming Rules Project Settings.
6.3.3 CEA-709 Settings
The CEA-709 configuration tab as shown in Figure 86 allows configuring properties of the
device‘s CEA-709 port. The options are:
Enable Legacy Network Management Mode : This group box contains check boxes for each CEA-709 port of the device. Put a check mark on the port, if this port shall be operated in the legacy network management mode. In that mode, the port does not use the extended command set (ECS) of network management commands. This can be
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 111 LOYTEC necessary to operate the device with some network management tools that do not support the ECS.
Default Pollcycle for External NVs : When using external NVs, this poll cycle is set as a default for input data points. The poll cycle can be edited individually in the properties view of the data point manager.
Use state-member of SNVT_switch as : This setting defines how the state member of the SNVT_switch shall be mapped to a data point. Depending on how the data point shall be used, it can be binary or multi-state. The multi-state setting allows setting the
UNSET state explicitly. As a binary point the UNSET state is implicitly chosen, if the value is invalid.
Omit unused child data points of UNVT/UCPT structures : This setting defines, that if set, also unsued sub-data points of user-defined structure types are not downloaded onto the device. This option can reduce the total amount of data points in the configuration. As a default it is not enabled to allow full structure information after an upload to the PC even if the user does not have the original resource files installed.
Configuration Download : This group box contains self-configuration settings for the
CEA-709 ports. This is necessary if the device shall be used without being commissioned by a network management tool. Set the check mark and enter the
CEA-709 domain and subnet/node information. If operated in self-configured mode,
the CEA-709 network can be scanned using the network scan (see Section 6.7.4) and
external NVs can be used on the device. Note, that the domain must match the nodes‘ domain on the network and the subnet/node address must not be used by another device.
Figure 86: CEA-709 Project Settings.
6.3.4 AST Settings
For CEA-709 devices, the use of alarming, scheduling, and trending (AST) features requires additional resources (functional objects and NVs). This changes the static interface. Since the number of used resources also influences the performance, the CEA-709 AST tab allows configuring those resources for the project. In this tab, the required number of scheduler units that may be instantiated and their capacity may be configured (how many time/value entries, value templates, bytes per value template, etc.). It contains the following options and settings, which are relevant to calendar and scheduler functionality of the device:
Enable Calendar Object: This checkbox enables a L ON M ARK compliant calendar object on the device. It is automatically enabled together with local schedulers, since the two are always used together.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 112 LOYTEC
Enable Scheduler Objects: This checkbox enables local L ON M ARK compliant scheduler objects on the device. Checking this box will automatically enable the calendar as well.
Enable Remote AST Objects: This checkbox enables the functional object for NVs, which are used to access remote AST objects. If this box is checked, the Clients functional block is included in the static interface.
Enable AST v2: This checkbox enables the AST interface version 2 for local CEA-709 schedulers on the device. This interface is not compatible with older devices. The new interface provides access to the value label descriptions in schedule presets for remote schedulers.
Number of calendar patterns: Specifies the maximum number of different exception schedules (day classes like holiday, maintenance day) supported by this calendar object.
Total number of date entries: Specifies the maximum number of date definitions which may be stored by the calendar. This is the sum of all date definitions from all calendar entries. A date definition is for example a single date, a date range, or a week and day pattern.
Number of local schedulers: This is the number of local scheduler objects which should be available on the device. Each local scheduler data point created in the data point manager will connect to one of these scheduler objects. There may be more scheduler objects available on the device than are actually used at a certain time. It is a good idea to have some spare scheduler objects ready, in case another scheduler is needed.
Number of daily schedules: This is the maximum number of schedules supported by each scheduler object. This number must at least be 7, since a scheduler always needs to provide one schedule for each day of the week (default weekly schedule). For each special day defined by the calendar or embedded exception day, an additional daily schedule is required to support it.
Entries in Time/Value table: This is the total number of entries in each scheduler defining a value template that should apply on a specific day starting at a specific time
(the time table).
Number of value templates: This is the maximum number of value templates supported by each scheduler.
Data size per value template: This specifies the buffer size reserved to hold the data for each value template. More data points or bigger data structures require a bigger value buffer.
Max. number of data point maps: Specifies the maximum number of individual data points that this scheduler is able to control.
AST Configuration Size: This number in Bytes is calculated from the scheduler settings above and represents the total size of the L ON M ARK configuration properties file stored on the device. While certain settings can be freely edited within the given limits, the resulting configuration size is also limited.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 113 LOYTEC
Figure 87: CEA-709 AST Project Settings.
As can be seen from the above list, it is not easy to configure a L ON M ARK scheduler object.
There are many technical parameters which need to be set and which require some knowledge of how these scheduler objects work internally. Therefore, the configuration software provides the following mechanisms to help in choosing the right settings:
Resources required by the current project: The absolute minimum settings required by the current project are shown in a table at the left side of the window. This data may be used to fill in the values at the right side, but some additional resources should be planned to allow for configuration changes which need more resources.
Auto-Set: This button may be used to let the configuration software decide on the best settings to use, based on the current project. Since the current projects resource usage is taken as a starting point, all schedulers and calendar patterns in the project should first be configured before this button is used.
Set Defaults: This button will choose standard values for all settings. In most cases, these settings will provide more resources than necessary.
6.3.5 BACnet Settings
The BACnet configuration tab as shown in Figure 88 allows configuring properties of the
device‘s BACnet port. The options are:
Enable Unsolicited COV : Put a check mark on this option to enable COV-U on the
BACnet port. When active, the device sends unsolicited COV broadcast on all BACnet objects, when their value changes in accordance to the respective COV rules.
Use 255.255.255.255 for global broadcast : This setting overrides the standard behavior of BACnet to send broadcasts as global IP broadcasts. This can solve scanning problems with some BACnet devices.
Enable periodic I-Am broadcast : This setting enables the periodic transmission of I-
Am broadcasts. Specify the interval in seconds. If disabled, the device sends an I-Am only when starting up. This is the default behavior of BACnet devices.
String encoding : This setting defines, how strings in BACnet objects are encoded. By default it is ASCII, which is compatible with most BACnet software. To support characters of Western European languages, choose ISO-8859-1. To support Unicode character sets (e.g., Japanese) select UCS-2.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 114 LOYTEC
Default Poll cycle, Default COV Expiry : This setting defines the default values that are used when creating new client mappings. Changing this option does not affect already existing client mappings.
Figure 88: BACnet Project Settings.
6.3.6 Device Configuration
This tab is shown in Figure 89. It is available only with the newest firmware version and can
be used to configure the device through the Configurator. In the configuration tree on the left-hand side the user can select certain groups of settings, e.g. Web server settings. The dialog displays the settings of the selected group in the dialog area. The structure is similar to the menu structure on the Web UI.
Under the port configuration tree, the user can enable or disable communication protocols on the device‘s ports. Enabled protocols are marked with a checkmark. Click on the checkmark and toggle it. Note, that depending on the device model communication protocols on other ports may be disabled.
The IP address settings cannot be changed in this dialog. The FTP server can not be disabled in this dialog, either. This ensures that the Configurator can maintain connection to the device.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 115 LOYTEC
Figure 89: Device Configuration Settings
Important!
The Upload button can be used to get the current device settings from the device and display them in this dialog. The Download button can be used to explicitly transfer the settings from this dialog onto the device. Those changes will be visible immediately on the
Web UI but take effect only after a reboot of the device.
After downloading the device settings from this dialog the changes will be visible immediately on the Web UI but the device needs to be rebooted to let the changes take effect.
6.3.7 LogiCAD
This tab is shown in Figure 90. It is available only with L-INX models that support the
IEC61131 PLC kernel. On this tab, the default path to the LogiCAD project may be specified. This is used by the Configurator software to scan for device resources and compiled IEC61131 programs, which may be attached to the L-INX project on the Project
Files tab in the main window.
Version 4.0
Figure 90: LogiCAD Settings.
LOYTEC electronics GmbH
L-INX User Manual 116 LOYTEC
6.4 Workflows for CEA-709
This section discusses a number of work flows for configuring a CEA-709 L-INX in different use cases in addition to the simple use case in the quick-start scenario (see Chapter
2). The description is intended to be high-level and is depicted in flow diagrams. The
individual steps refer to later sections, which describe each step in more detail. In principle, the L-INX Configurator supports the following use cases:
Network Management Tool based on LNS 3.x (see Section 6.4.2)
Non-LNS 3.x network management tool with polling (see Section 6.4.3)
Non-LNS 3.x network management tool with bindings (see Section 6.4.4)
6.4.1 Involved Configuration Files
In the configuration process, there are a number of files involved:
XIF file: This is the standard file format to exchange the static interface of a device.
This file can be used to create a device in the database without having the L-INX online. There exists a standard XIF file for the FT port (e.g., LINX-10x_FT-10.xif) and one for the IP-852 port (e.g., LINX-10x_IP-10L.xif). For the LINX-15x model use the
LINX-12x XIF files.
L-INX Configurator project file: This file contains all ports, data points, and connections of a project. These files end with ―.linx0‖, ―.linx1‖, or ―.linx2‖. It stores all relevant configuration data and is intended to be saved on a PC to backup the LINX‘s data point configuration.
6.4.2 Configure with LNS
The flow diagram in Figure 91 shows the steps that need to be followed in order to
configure the L-INX in a network with LNS 3.x. In this scenario, the L-INX will use dynamic NVs and bindings.
First, the L-INX device must be added to LNS (see Section 6.4.6). Then the L-INX
Configurator must be started in plug-in mode to configure the L-INX (see Section 6.7.1). In
the Configurator, scan for the data points in the LNS database (see Section 6.7.2). Select the
data points that the L-INX shall expose (see Section 6.7.5). Finally, the configuration needs
to be downloaded to the L-INX via LNS (see Section 6.7.9). It is recommended to backup
the device configuration to a file for being able to replace the device in the network (see
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 117 LOYTEC
START
Add L-INX
Section 6.4.6
Start the Configurator as a plug-in
Section 6.7.1
Scan network variables
Section 6.7.4
Select NVs and use on device
Section 6.7.5
Download configuration to device
Section 6.7.9
DONE
Figure 91: Basic design-flow with LNS.
To add more NVs when all bindings are in place and the L-INX is already being used, simply repeat the steps described above. The Configurator software will back up the bindings, create or delete the dynamic NVs, and re-create the bindings again.
6.4.3 Configure without LNS
The flow diagram in Figure 92 shows the steps that need to be followed in order to
configure the device without LNS 3.x. In this scenario the device will use external NVs and polling. The advantage of this solution is that no bindings in the non-LNS tool (or selfbinding nodes) need to be changed. This comes at the cost of a constant network load caused by polling.
Start the Configurator in stand-alone mode and connect to the device via the FTP method
(see Section 6.6.1). If changing an existing configuration, upload the current configuration
from the device (see Section 6.6.2). In the Configurator, import data points from a CSV
import file (see Section 6.7.3) or from an XIF file (see Section 6.8.1). If the other devices
are already connected to the network you may also scan them (see Section 6.7.4). Select the
data points that the device shall expose (see Section 6.7.5). Alternatively, you can create
external NVs manually (see Section 6.7.8). Finally, the configuration needs to be
downloaded to the device (see Section 6.6.4). It is recommended to backup the device
configuration to a file for being able to replace the device in the network (see Section
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 118 LOYTEC
Import network variables from XIF
Section 6.8.1
START
Start the Configurator stand-alone
Section 6.6.1
Upload configuration
Section 6.6.2
Import network variables from file
Section 6.7.3
Select NVs and use on device
Section 6.7.5
Create other external NVs manually
Section 6.7.8
Download configuration to the device
Section 6.6.4
Scan online for network variables
Section 6.7.4
DONE
Figure 92: Basic design-flow without LNS.
6.4.4 Configure without LNS Using Bindings
The flow diagram in Figure 93 shows the steps that need to be followed in order to
configure the device without LNS 3.x. In this scenario the device will use static NVs and bindings. The advantage of this solution is that the network load is minimized. However, the non-LNS management tool must create bindings for the device and update an existing network.
Start the Configurator in stand-alone mode and connect to the device via the FTP method
(see Section 6.6.1). In the Configurator import data points from a CSV import file (see
Section 6.7.3) or from an XIF file (see Section 6.8.1). If the other devices are already
connected to the network you may also scan them (see Section 6.7.4). Select the data points
that the device shall expose (see Section 6.7.5). For the NVs used on the device select the
―static NV‖ allocation type (see Section 6.7.6). Alternatively, you can create static NVs
For network management tools, which do not support the ECS (enhanced command set) network management commands, the legacy network management mode must be configured
(see Section 6.7.10). Please contact the tool‘s vendor for information whether ECS is
supported or not.
Download the configuration onto the device (see Section 6.6.4). Finally, export a XIF file
(see Section 6.7.11). It is recommended to backup the device configuration to a file for
being able to replace the device in the network (see Section 6.6.6).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 119 LOYTEC
Import network variables from FIX
Section 6.8.1
START
Start the Configurator stand-alone
Section 6.6.1
Import network variables from file
Section 6.7.3
Select NVs and use on device
Section 6.7.5
Switch NVs to „static“
Section 6.7.6
Create other static NVs manually
Section 6.7.7
Scan online for network variables
Section 6.7.4
Tool supports
ECS ?
no
Enable Legacy NM Mode
Section 6.7.10
yes
Download configuration to device
Section 6.6.4
Export XIF file
Section 6.7.11
DONE
Figure 93: Basic design-flow without LNS using bindings.
To use the device in the non-LNS management tool, commission the device using the exported XIF file and create the bindings.
When changing a running device configuration with existing bindings, it is recommended to
create additional data points as external NVs with polling as described in Section 6.4.3.
Otherwise, depending on the third-party tool, a new XIF file may be required to be exported for replacing the device in the non-LNS tool. In this case the user would need to create all
bindings again from scratch (see Section 5.4.3).
6.4.5 Replace a L-INX
A device can be replaced in the network by another unit. This might be necessary if a hardware defect occurs. First of all, the replacement device needs to be configured with the appropriate IP settings. The remainder of this section focuses on restoring the device
configuration from a backup file. The work flow is depicted in Figure 94.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 120 LOYTEC
START
Start the Configurator stand-alone
Section 6.6.1
Restore a backup file to the device
Section 6.6.6
Replace the device in LNS
Section 6.4.7
DONE
Figure 94: Basic work flow to configure a replacement device.
Start the Configurator software stand-alone and connect via the FTP method (see Section
6.6.1). Then restore the device configuration from the backup file, which has been created
when the original device has been configured or modified (see Section 6.6.6). After the
restore all data points, dynamic NVs and bindings are restored. The device is again configured online and fully functional in the CEA-709 network.
If using an LNS-based tool, the device needs to be replaced in that tool at some later point
in time (see Section 6.4.7) as the NID has changed. If you are not using LNS, then refer to
your network management tool‘s reference manual on how to replace a device.
6.4.6 Adding the L-INX to LNS
To configure a L-INX in your LonMaker drawing, the device needs to be added to the LNS database and commissioned. This Section refers to LonMaker TE and describes how to add a L-INX to your database. The example discusses a LINX-10X but it is general to all CEA-
709 L-INX models
To Add a Device to LonMaker TE
1.
In your LonMaker drawing, drag a device stencil into the drawing. Enter an appropriate
Version 4.0
Figure 95: Create a new device in the drawing.
LOYTEC electronics GmbH
L-INX User Manual 121 LOYTEC
2.
Select Commission Device if the LINX-10X is already connected to the network.
3.
In the Device Template group box select the existing device template of the LINX.
Select ―LINX-xxx_FT-10‖, if the L-INX is configured to use the FT-10 interface, or
―LINX-xxx_IP-10L‖, if the L-INX is configured to be on the IP channel. For
information on how to configure which port to use, refer to Section 4.2.6 for the Web
UI. Note that for the LINX-15x the LINX-12x XIF has to be used.
4.
Select the channel, which the L-INX is connected to and click Next .
5.
The following dialog shown in Figure 96 appears, click
Next .
Figure 96: Leave defaults for Location.
6.
Check Service Pin as the device identification method as shown in Figure 97 and click
Next .
Version 4.0
Figure 97: Use Service Pin.
LOYTEC electronics GmbH
L-INX User Manual 122 LOYTEC
7.
Click Next
in the following screens until you get to the final dialog shown in Figure 98.
8.
If the device is already on-net, select Online .
Figure 98: Final dialog.
9.
Click Finish . A dialog will prompt to press the service pin.
10.
Finally, you should get the device added to your drawing as depicted in Figure 99.
LNS Network Interface linx
Channel FT-10
Figure 99: The L-INX has been added to the drawing.
6.4.7 Replace a L-INX in LNS
This Section describes how to replace a L-INX in your LNS database. The example discusses a LINX-10X but is general to all CEA-709 L-INX models. The description refers to LonMaker TE. Let‘s assume there is a device ‗linx‘ in the LNS database as shown in
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 123 nvi01temp nvi03lux nvi05lev_percent nvi07temp_f nvi09switch nvi11motor_state nvi13amp nvi15fire_test nvi17state nvi19temp
Gateway[0] nvo00temp nvo02lux nvo04lev_percent nvo06temp_f nvo08switch nvo10motor_state nvo12amp nvo14fire_test nvo16state nvo18temp
LOYTEC
Channel FT-10 linx
Figure 100: LonMaker drawing with one LINX.
To Replace a Device in LonMaker TE
1.
Select the device and right-click on the device shape.
2.
Select Commissioning
Replace… . This opens the LonMaker Replace Device
Wizard as shown in Figure 101.
Figure 101: LonMaker replace device wizard.
3.
Choose the existing device template and click Next .
4.
In the following window shown in Figure 102 click
Next .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 124 LOYTEC
Figure 102: Click Next without loading an application image.
5.
Then select Online
as shown in Figure 103 and click
Next .
Figure 103: Select online state.
6.
Select the Service pin method and click on Finish
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 125 LOYTEC
Figure 104: Select Service Pin and click Finish.
7.
Then the service pin requestor opens as shown in Figure 105. Press the service pin on
the replacement L-INX on the correct port. You can also send the service pin using the
Web interface (see Section 4.1).
Figure 105: Wait for the service pin from the device.
8.
After the service pin has been received, LonMaker commissions the replacement device, creates the dynamic NVs again (if any), and installs the bindings.
6.5 Workflows for BACnet
This section discusses a number of work flows for configuring a BACnet L-INX in different
use cases in addition to the simple use case in the quick-start scenario (see Chapter 2). The
description is intended to be high-level and is depicted in flow diagrams. The individual steps refer to later sections, which describe each step in more detail.
6.5.1 Involved Configuration Files
In the configuration process, there are a number of files involved:
L-INX Configurator project file: This file contains all ports, data points, and connections of a project. These files end with ―.linx0‖, ―.linx1‖, or ―.linx2‖. It stores all relevant configuration data and is intended to be saved on a PC to backup the LINX‘s data point configuration.
EDE file: When engineering offline, the Configurator can import remote BACnet data points via an EDE file. Out of this information client mappings are created.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 126 LOYTEC
6.5.2 Engineer On-Line
The flow diagram in Figure 106 shows the steps on how to configure the BACnet port when
being on-line. In this case, the device must be present in the BACnet network and configured with an IP address. The user can connect to the device and scan for existing
BACnet devices and objects on the network.
START
Start the Configurator stand-alone
Section 6.6.1
Upload configuration
Section 6.6.2
Scan BACnet network
Section 6.9.1
Select BACnet objects and use on device
Section 6.9.3
Create client mappings manually
Section 6.9.4
Create other BACnet server objects manually
Section 6.9.5
Download configuration to device
Section 6.6.4
DONE
Figure 106: Basic work flow to engineer on-line.
Start the Configurator in stand-alone mode and connect to the device via the FTP method
(see Section 6.6.1). If changing an existing configuration, upload the current configuration
from the device (see Section 6.6.2). In the Configurator, start an on-line network scan to
discover devices and BACnet objects (see Section 6.9.1). Select the data points that the
device shall expose (see Section 6.9.3). Alternatively, you can create client mappings (see
Section 6.9.4) and local BACnet server objects (see Section 6.9.5) manually. Finally, the
configuration needs to be downloaded to the device (see Section 6.6.4). It is recommended
to backup the device configuration to a file for being able to replace the device in the
6.5.3 Engineer Off-Line
The flow diagram in Figure 107 shows the steps on how to configure the BACnet port when
being off-line. In this case, the device doesn‘t need to be present in the BACnet network.
The systems integrator can engineer the BACnet port and download the configuration at a later point in time.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 127 LOYTEC
START
Start the Configurator and select the LINX model
Import BACnet data points from EDE
Section 6.9.2
Select BACnet objects and use on device
Section 6.9.3
Create client mappings manually
Section 6.9.4
Create other BACnet server objects manually
Section 6.9.5
Store configuration on hard drive
DONE
Figure 107: Basic work flow to engineer off-line.
Start the Configurator in stand-alone mode and select the appropriate L-INX model in the menu Model . In the Configurator, import external BACnet data points from an EDE file
(see Section 6.9.2). Select the data points that the device shall expose (see Section 6.9.3).
Alternatively, you can create client mappings (see Section 6.9.4) and local BACnet server
objects (see Section 6.9.5) manually. When finished store the configuration on the hard
drive and download later to the device (see Section 6.6.4).
6.5.4 Replace a L-INX
A L-INX can be replaced in the network by another unit. This might be necessary if a hardware defect occurs. First of all, the replacement device needs to be configured with the appropriate IP settings. The remainder of this section focuses on restoring the device
configuration from a backup file. The work flow is depicted in Figure 108.
START
Version 4.0
Generate a Backup of the device
Section 4.2.2
Replace the physical unit
Enter the basic IP settings
Section 2.2
Restore a backup file to the device
Section 6.6.6
DONE
Figure 108: Basic work flow to configure a replacement device.
Make a backup of the old device over the Web UI (see Section 4.2.2) and store the backup
file on the hard drive. Replace the unit and enter the IP settings (see Section 2.2). Then
restore the device configuration from the backup file, which has been created when the
original device has been configured or modified (see Section 6.6.6). After the restore all
LOYTEC electronics GmbH
L-INX User Manual 128 LOYTEC data points, BACnet server objects and client mappings. The device is again fully functional in the network.
6.6 Using the L-INX Configurator
6.6.1 Starting Stand-Alone
Go to the Windows Start menu, select Programs , LOYTEC LINX Configurator and then click on LOYTEC LINX Configurator . This starts the Configurator and the main connections screen is displayed.
If the L-INX is not yet connected to the network, go to the Firmware menu and select the firmware version and model of the L-INX to be configured. If the L-INX is already connected to the network it is recommended to connect the Configurator online to the
LINX.
To Connect to a L-INX Stand-Alone
1.
Select the FTP connection method by clicking on the FTP connect button
in the tool bar of the main connections window. The connect dialog as shown in Figure
109 opens containing the managed device connection templates.
Version 4.0
Figure 109: FTP connection dialog.
2.
To add a new device connection, click on New or select an existing connection in the tree on the left-hand side.
3.
Enter the host name or IP address of the device. Enter the admin password. The default password is ‗loytec4u‘ (older firmware versions used ‗admin‘).
4.
Optionally, click on Use secure connection to enable encrypted SSH access to the device.
5.
If your device is located behind a NAT router or firewall, you may change the FTP,
Telnet, SSH, and HTTP ports to your needs for accessing the device.
LOYTEC electronics GmbH
L-INX User Manual 129 LOYTEC
6.
Click on Save to store that connection.
7.
Click on Connect . This establishes the connection to the device.
6.6.2 Uploading the Configuration
To get the current data point configuration of the device, the configuration needs to be uploaded. This will upload the entire configuration from the device, including data points, client mappings, and schedules.
To Upload a Configuration
1.
Click on the upload button
in the tool bar. The configuration upload dialog opens up as shown in Figure 110.
2.
Click on the button Start to start the transfer. This will upload the configuration of all ports.
Figure 110: Configuration upload dialog.
3.
When the project settings of the configuration being uploaded specify to ask, which specific parameters shall be uploaded, check the needed information and proceed.
6.6.3 Create User Registers
User registers are data points on the device that do not have a representation on the network. Thus, they are not accessible over a specific technology. A register merely serves as a container for intermediate data (e.g., results of math objects). Since a register has no network direction, it can be written and read. Therefore, two data points are generated for each register, one for writing the register (output) and one for reading the register (input).
To Create a User Register
1.
Select the User Registers folder under the device folder.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 130 LOYTEC
2.
Right-click in the data point list and select New Datapoint… in the context menu. This
opens the register creation dialog as shown in Figure 111.
Figure 111: Create a user register.
3.
Enter a Datapoint Name for the register. You may leave the Register Name blank to give the underlying register the same name as the data point.
4.
Select a Type . Available are ―Double‖, ―Boolean‖, ―Signed Integer‖, ―String‖, or
―Variant‖.
5.
Click Create Register .
6.
Two data points now appear for the register, one for writing the register and one for
reading the register as shown in Figure 112.
Figure 112: Manually created user register.
6.6.4 Configuration Download
After the data points have been configured, the configuration needs to be downloaded to the device. For doing so, the device must be online. If the device is not yet connected to the network, the configuration can be saved to a project file on the local hard drive.
To Download a Configuration
1.
In the main connections window, click on the Download Configuration speed button in the tool bar of the main connections window. This will open the configuration
download dialog as shown in Figure 113.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 131 LOYTEC
2.
If the project settings specify to ask (see Section 6.3.1), which specific parameters shall
be downloaded, check all that apply and click Ok .
3.
Click Start to start the download. Each of the actions is displayed in the Task List section of the dialog. The current progress is indicated by the progress bar below.
4.
When the download process has finished, a notification window appears, which has to be acknowledged by clicking OK .
Figure 113: Configuration Download Dialog.
6.6.5 Upload the System Log
The system log on the device contains important log messages. Log messages are generated for important operational states (e.g., last boot time, last shutdown reason) or errors at runtime. This file is important for trouble-shooting and is available on the Web UI (see Section
4.3.1). The file can also be uploaded from the device with the Configurator.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 132 LOYTEC
To Upload the System Log
1.
Connect to the device (see Section 6.6.1).
2.
Click on the Upload system log button
in the tool bar. The upload system log dialog as shown in Figure 114 opens showing the
upload progress.
Figure 114: Upload system log dialog.
3.
When the upload is finished, click on Show System Log . The system log window
appears as shown in Figure 115.
Figure 115: System log window.
4.
Click on Save to store the system log into a file on your local hard drive.
6.6.6 Backup and Restore
The Configurator provides a backup and restore function for the connected device. It is highly recommended to create a device backup once the device configuration has been completed. This backup can be used in the case a device needs to be replaced in the network.
To Create a Backup
1.
Connect to the device (see Section 6.6.1).
2.
Choose the menu Tools
Backup Device Configuration … .
3.
A file requestor opens. Choose a location to store the ZIP file of the device backup.
The suggested file name contains device IP address and creation date.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 133
4.
Click on Save . The backup is being uploaded.
LOYTEC
To Restore a Backup
1.
Choose the menu Tools
Restore Device Configuration … .
2.
In the file requestor choose a backup ZIP file and click Open .
3.
The Configurator restores and reboots the device. The process is complete when the device has finished rebooting.
6.7 CEA-709 Configuration
6.7.1 Starting as an LNS Plug-In
In LonMaker the plug-in is started by right-clicking on the L-INX device shape or the
Gateway/PLC functional block and selecting Configure… from the pop-up window.
In NL-220, the Plug-in is started by right clicking on the L-INX node, then selecting the
Option LOYTEC LINX Configurator in the PlugIns sub menu.
In Alex, the Plug-in is started by right clicking on the L-INX device and selecting the
LOYTEC LINX Configurator in the Starte PlugIn sub menu.
A window similar to what is shown in Figure 116 should appear.
Version 4.0
Figure 116: L-INX Configurator main window.
LOYTEC electronics GmbH
L-INX User Manual 134 LOYTEC
6.7.2 Scanning for Network Variables
When the L-INX Configurator is connected to an LNS database, network variables can be scanned from that data base.
To scan network variables from the LNS database
1.
Click on the Datapoints tab.
2.
Click on the button Scan channel . This scans in all NVs on all devices connected to the CEA-709 channel of the LINX-10X.
3.
After the scan has completed, the folder LNS Database Scan is populated with the found NVs. Data point names for those NVs are automatically generated, following the
data point naming rules defined in the project settings (see Section 6.3.2). By default
the name is generated from node name, object name, and NV name. These names are ensured to be unique by adding a counter for multiple occurrences of the same name.
Version 4.0
Figure 117: Scanned NVs in the LNS Database Scan Folder.
Figure 117 shows an example result of the database scan. The list can be sorted by each
column. Selecting a line will display a number of associated properties in the property view below. Multiple items can be selected by using the <Ctrl> key and clicking with the mouse.
All items can be selected by pressing <Ctrl-A>.
LOYTEC electronics GmbH
L-INX User Manual 135 LOYTEC
6.7.3 Importing Network Variables
Without LNS, the tool cannot connect to an LNS database, where it scans for network variables (NVs). Therefore, the list of NVs to be used on the device has to be available in a
CSV file. This file can be produced by external software or created by hand. The CSV
format for importing NVs is defined in Section 13.2.1.
To Import NVs from a File
1.
Click on the Datapoints tab.
2.
Select the import folder CEA709 CSV File
3.
Right-click and select Import File . In the following file selector dialog, choose the
CSV import file and click OK .
Version 4.0
Figure 118: Imported NVs.
4.
Now the CSV File folder is populated with the imported NVs as shown in Figure 118.
LOYTEC electronics GmbH
L-INX User Manual 136 LOYTEC
The list can be sorted by each column. Selecting a line will display a number of associated properties in the property view below. Multiple items can be selected by using the <Ctrl> key and clicking with the mouse. All items can be selected by pressing <Ctrl-A>.
6.7.4 Scanning NVs online from the Network
LOYTEC devices also support an online network scan on the CEA-709 network. In this scan, the device searches for other devices on the CEA-709 network and pulls in NV information of these devices. These NVs can then be used instead of importing them from a
CSV file.
To scan NVs online off the CEA-709 network
1.
Click on the Datapoints tab.
2.
Select the folder CEA709 Network Scan .
3.
Right-click on that folder and select Scan CEA709/852 Network… . This opens the
CEA709 Management
dialog as shown in Figure 119.
Version 4.0
Figure 119: CEA-709 network scan dialog.
LOYTEC electronics GmbH
L-INX User Manual 137 LOYTEC
4.
If the device has not been installed with a network management tool (e.g. LNS-based tool), press the Configure CEA709 Port button. This opens the device install dialog as
Note:
Tip!
Figure 120: Configure CEA-709 port dialog.
5.
Select the Manually set domain check-box and click the Set button. This sets the device configured, online to start the scan. Then click Close .
You need to set the same domain as the devices to be scanned. Click Get Domain from
Network and press a service pin on some other, already installed device to retrieve the domain information before setting the device online.
6.
Click on the button Discover Devices . This starts a network scan. The results are put in the device list box.
7.
Alternatively, click the button Discover on Service Pin . Then press the service pin of a particular device on the network. This device will be added to the device list.
8.
Select a device in the device list. To give the device a usable name, enter the name in the Device Name field and click on the Update Selected button.
9.
Then click the button Scan . This scans the NVs on the selected device and adds them to the CEA709/852 Network Scan folder as a separate sub-folder for the device as
If you are not sure which device you have selected, click on Wink . The selected device will execute its wink sequence.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 138 LOYTEC
Figure 121: CEA-709 network scan results.
10.
Click Close when all devices needed have been scanned.
6.7.5 Select and Use Network Variables
Data points in the CEA709 LNS Scan folder, the CEA709 Network Scan folder or in the
CEA709 CSV File folder can be selected for use on the device. Select those NVs, which shall be used on the device.
To Use NVs on the Device
1.
Go to any of the CEA709 LNS Scan , CEA709 Network Scan or the CEA709 CSV
File folder.
2.
Use the multi-select feature by holding the Shift or Ctrl keys pressed.
Tip!
3.
Click on the button Use on Device in the tool bar.
4.
This creates data points in the CEA709 Port folder of the device. All data points in that folder will actually be created on the device after downloading the configuration.
Data points can be edited by selecting a single point or using multi-select. The available properties to be edited are displayed in the property view below.
6.7.6 Change the NV Allocation
After selecting the Use on device action on scanned or imported NVs, they are assigned a default NV allocation in the CEA709 port folder. This default allocation can be changed, e.g., for imported NVs when they shall be allocated as static NVs on the device.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Tip!
139 LOYTEC
To Change the NV Allocation Type
1.
In the data point view, select the NVs in the CEA709 port folder, for which the NV allocation shall be changed.
By using Ctrl-A all NVs can be selected.
2.
Select the NV allocation
property as indicated by the red rectangle in Figure 122.
3.
To make the data points static NVs on the device, select Static NV .
Figure 122: Change the NV allocation type.
6.7.7 Create Static NVs
The LOYTEC device can be configured to change its static interface and boot with a new one. Apart from creating static NVs from scanned or imported data points, static NVs can also be created manually in the CEA709 port folder.
To Create Static NVs Manually
1.
Select the Datapoints folder under the CEA-709 port folder.
2.
Right-click in the data point list and select New Datapoint… in the context menu. This
opens the NV creation dialog as shown in Figure 123.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 140 LOYTEC
Figure 123: Create a static NV manually.
3.
Enter a data point name and a programmatic name. The programmatic name is the name of the static NV which is being created.
4.
Select a resource file. To create a SNVT, let the STANDARD resource file be selected.
5.
Select a SNVT and a direction. If a non-standard resource file has been selected, choose from one of the UNVTs.
Tip! Recently created SNVTs are available in the Recent NV Types list. Click on one to set the
NV type without scrolling through the drop-down box.
6.
Choose a functional block, where this static NV shall be located in.
7.
Click Create Static NV . The static NV is created and appears in the data point list.
8.
Note, that the static interface of the device will change as soon as static NVs are added or modified in the data point manager. This change is reflected in a new model number,
which the device will receive after the configuration download (see Section 5.4.3). Also
note that the manually created static NVs are not bound automatically by the
Configurator. They simply appear on the device and need to be bound in the network management tool.
9.
Click Close .
6.7.8 Create External NVs
External NVs are not actually allocated NVs on the device as NVs. Instead, the device uses polling to read data from and explicit updates to write data to external NVs. Since external
NVs do not affect the static NV interface of the device, they can be used to extend the interface configuration at run-time, when no LNS with dynamic NVs is available.
To Create an External NV manually
1.
Select the Datapoints folder under the CEA-709 port folder.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 141 LOYTEC
2.
Right-click in the data point list and select New Datapoint… in the context menu. This opens the NV creation dialog.
3.
Click on the tab External
Version 4.0
Figure 124: Create a new external NV.
4.
Select the device in the box Select a Device on the left-hand side.
5.
Enter the properties of the external NV on that device, starting with the local data point name, the remote programmatic NV name, the NV type (SNVT) and direction. Note, that the direction is the direction of the external NV on the device. Therefore, the remote output NV nvo00_switch becomes an input on the device. Also enter the NV selector in hexadecimal and the NV index in decimal notation. Choose the preferred addressing mode, e.g., Subnet/Node.
6.
Click Create External NV to add this NV to the data point list.
7.
The external NV now appears in the data point list as shown in Figure 125. For external
NVs, which are inputs to the device, adapt the poll cycle property to your needs.
LOYTEC electronics GmbH
L-INX User Manual 142 LOYTEC
Figure 125: Manually created external NV in the port interface definition.
6.7.9 Configuration Download over LNS
After the data points have been configured, the configuration needs to be downloaded to the device. For doing so, the device must be online. If the device is not yet connected to the network, the configuration can be saved to a project file on the local hard drive.
If connected via LNS, and the NVs on the device are ―Static NV‖ or ―Dynamic NV‖, the
Configurator can create the bindings automatically. This behavior can be influenced by the download dialog. When connected via LNS, the download procedure also manages the device template upgrade in the LNS database, if the static NV interface has been changed.
To Download a Configuration
1.
In the main connections window, click on the Download Configuration speed button in the tool bar of the main connections window. This will open the configuration
download dialog as shown in Figure 113.
2.
If no bindings shall be generated, deselect the Automatically create bindings
checkbox indicated by the red circle in Figure 126.
3.
If the static NV interface has been changed, a new model number for the device needs to be selected. This is necessary, as the static network interface of the device changes on the CEA-709 network. The Configurator automatically selects a usable value, which can be overridden in the field Model Number
marked by the blue rectangle in Figure
4.
Click Start to start the download. Each of the actions is displayed in the Task List section of the dialog. The current progress is indicated by the progress bar below.
5.
When the download process has finished, a notification window appears, which has to be acknowledged by clicking OK .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 143 LOYTEC
Figure 126: Configuration Download Dialog via LNS.
Note, that after the download is complete, the interface changes become active on the device (i.e., the static NV interface has changed). Refresh the network management tool to synchronize the tool with the changes to the LNS database made by the Configurator (e.g., use the menu ―LonMaker|Refresh‖ in LonMaker or hit
F5 in NL-220).
Normally, the Configurator software optimizes the download process by not executing certain LNS operations, if not necessary. For example, only those bindings and dynamic
NVs are deleted and re-created, which correspond to real changes in the interface. The user can check the Force Full Upgrade option to clean and re-do all steps.
6.7.10 Enable Legacy NM Mode
For network management tools, which do not support the ECS (enhanced command set) network management commands, the legacy network management mode must be configured. Please contact the tool‘s vendor for information whether ECS is supported or not. Note, that changing to legacy network management mode changes the static interface of the device.
To Enable Legacy NM Mode
1.
In the Configurator menu go to Settings
Project settings …
2.
Click on the tab CEA709 .
3.
Put a check mark in Enable Legacy Network Management Mode .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 144 LOYTEC
4.
Click OK.
5.
Download the configuration to activate the change.
6.7.11 Build XIF for Port Interface
When using static NVs on the device, the Configurator can export a new XIF file for the changed static interface.
To Create a XIF File
1.
Select the CEA-709 Port folder
2.
Right-click on that folder and in the context menu select
Build XIF …
.
3.
This opens a file requestor where the XIF file name needs to be entered. Select a useful name to identify the device, e.g., as ―linx-10X_1.xif‖.
6.7.12 Upload Dynamic NVs from Device
In LNS-based tools it is possible to create dynamic NVs on the device manually. This is a possible workflow to engineer the NV interface of the device in the LNS database. To use those manually created dynamic NVs, the Configurator must synchronize its dynamic NV information with the port.
To Upload Dynamic NVs
1.
Select the CEA709 Port folder.
2.
Right-click and select Sync Dynamic NVs in the context menu. The Configurator then loads any new dynamic NVs, which have been created and are not yet part of the port
interface definition. The process completes when the dialog shown in Figure 127
appears.
Version 4.0
Figure 127: Synchronizing dynamic NVs from the device.
LOYTEC electronics GmbH
L-INX User Manual 145 LOYTEC
3.
Click on Finish . The new dynamic NVs now appear in the data point list and can be edited and used on the device.
6.8 Advanced CEA-709 Configuration
6.8.1 Import Devices from XIF Templates
When working entirely without LNS, nodes on the network can be engineered via importing device templates from a XIF file. The Configurator provides a XIF device template import feature. Having devices imported from a XIF file is similar to have devices scanned online from the CEA-709 network, only their actual node IDs are unknown.
To Import from a XIF Template
1.
Select the folder CEA709 Devices from XIF .
2.
Right-click on the folder and select Create device(s) from XIF file… from the context menu.
3.
In the file open dialog select a XIF file to import and click Ok .
4.
The imported data points appear as a device sub-folder of the CEA709 Devices from
XIF folder named after the XIF file name.
5.
In that folder select those data points, which shall be used on the device and use them
on the device as described in Section 6.7.5.
6.
Repeat the import of XIF files for as many nodes as needed. The same XIF can be imported more than one time, resulting in multiple nodes of the same type in the
CEA709 Devices from XIF folder.
6.8.2 Install Unconfigured Devices
CEA-709 devices must be installed by a network management tool (e.g., LNS-based tool) to be available for communication. Devices can be imported from a CEA-709 network scan or from a XIF file. If no network management tool is available, the CEA-709 device manager must be used to install the unconfigured devices. To install a device the following steps need to be done:
The imported devices must be assigned to actual devices on the network. This is done by setting a node ID that corresponds to a node on the network.
The domain information must be written to the device and it must be set configured, online to be ready for data communication.
To Install Devices
1.
Open the CEA-709 management dialog by clicking on the Manage CEA-709 Devices speed button.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 146 LOYTEC
2.
If devices have been imported via a XIF file, they do not have a node ID (all zero). To assign the physical node to the device, select the imported device.
3.
Click the Update NodeID button and press the service button on the network node.
The node ID will be filled in to the selected device. Alternatively the node ID can also be entered manually.
4.
After node IDs have been assigned to all unassigned devices, select the device(s) to install in the Device List of the CEA-709 management dialog. Multi-select of devices is possible.
5.
Click the Install button. This opens the Install Devices
dialog as shown in Figure 128.
Figure 128: Install devices dialog.
6.
Select the device to be installed.
7.
Enter the domain information or click Get Domain from Network and press a service pin.
8.
Enter a subnet and node address and click Install .
9.
Some nodes won‘t be operable on the new settings until they are reset. Click the Reset button to reset the selected node.
10.
Repeat this step for other unconfigured devices on the network.
6.8.3 Using Feedback Data Points
Feedback data points allow reading back the value written out over an output data point. In
L ON M ARK systems getting a feedback value is normally accomplished by creating a dedicated feedback NV on the device, which can be bound back to the devices that are interested in the currently active value on an output.
Version 4.0
Some nodes, however, do not possess such feedback NVs for certain functions. To support getting feedback values on such nodes, the Configurator can create feedback data points based on existing output data points. This is especially interesting for bound output NVs
(static and dynamic alike). The corresponding feedback data point is an input, which uses
LOYTEC electronics GmbH
L-INX User Manual 147 LOYTEC the original output NV for polling the target NV. Once the binding is changed the new target is polled. No additional input NV needs to be created for the feedback value, if the feedback data point feature is used.
To Create a Feedback Data Point
1.
Select an output data point in the data point list of the CEA-709 port folder, e.g.
‗nvoHumid101‘.
2.
Right-click and choose Create Feedback-Point from the context menu.
3.
A new input data point is created, having ‗_fb‘ appended to the original name, e.g.,
‗nvoHumid101_fb‘. Note, that the feedback data point maps to the same NV index as the original output data point.
4.
Choose an appropriate poll cycle in the data point properties for the feedback data point.
6.8.4 Working with Configuration Properties
Configuration properties (CPs) are supported by the LNS network scan and the online network scan. They can be selected and used on the device in a similar way as NVs. There is a notable difference to NVs: CPs are part of files on the remote nodes. Reading and writing CPs on the device results in a file transfer.
The device supports both, the L ON M ARK file transfer and the simpler direct memory read/write method. In both cases however, one has to keep in mind that a file transfer incurs more overhead than a simple NV read/write. Therefore, polling CPs should be done at a much slower rate than polling NVs.
Another aspect is how CPs are handled by network management tools. Formerly, those tools were the only instance that could modify CPs in devices. Therefore, most tools do not automatically read back CPs from the devices when browsing them. This can result in inconsistencies between the actual CP contents on the device and their copy in the network management tool. It is recommended to synchronize the CPs from the device into the LNS database before editing and writing them back.
To Synchronize CPs in NL220
1.
Double-click on the device object in the device tree
2.
Press the Upload
button on the Configuration tab of the device properties (see Figure
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 148 LOYTEC
Figure 129: Configuration Tab for Configuration Properties in NL220.
To Synchronize CPs in LonMaker TE
1.
Right-click on a device object and select Commissioning
Resync CPs… from the context menu.
2.
This opens the dialog shown in Figure 130.
Figure 130: Set Configuration Properties in LonMaker TE.
3.
In this dialog select the radio button Upload values from device in the Operation group box. To use the current settings of the device as default values for new devices, select Set device template defaults from device .
4.
Execute the operation by clicking the OK button.
6.8.5 Working with UNVTs, UCPTs
This device supports user-defined type, including user-defined network variable types
(UNVTs) and user-defined configuration property types (UCPTs). In order to interpret the
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 149 LOYTEC contents of user-defined types, the device resource files supplied by the vendor must be added to the resource catalog on your PC.
Once the resource files are installed, the CEA-709 network scan and the LNS scan will display the user-defined types from the resource files. Those data points can be used on the device like regular, standard-type data points. Also manual creation of UNVTs can be performed.
To Manually Create a Static UNVT
1.
Perform the steps to manually create a static NV as described in Section 6.7.7.
2.
When the Create New NV dialog appears, change the resource file from
‗STANDARD‘ in the Resource File drop-down box to the desired, user-defined resource file
3.
Then select the desired UNVT from the Type drop-down list below. This list will display the types of the selected resource file only.
4.
Click Create Static NV to create the UNVT on the device.
6.9 BACnet Configuration
6.9.1 Scan for BACnet Objects
LOYTEC devices also support an online network scan on the BACnet network. In this scan the device searches for other devices on the BACnet network and pulls in the BACnet object information of these devices. These BACnet objects can then be used on the device as the basis for client mapping.
To Scan for BACnet Objects
1.
Go to the Datapoints tab.
2.
Select the folder BACnet Network Scan
3.
Right-click on that folder and select Scan BACnet Network… . This opens the
BACnet Network Scan dialog as shown in Figure 131.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 150 LOYTEC
Figure 131: BACnet network scan dialog.
4.
Click on the button Discover Devices . This starts a network scan. The results are put in the device list box. A progress bar below indicates how many devices are being scanned.
5.
Select a device in the device list and click the button Scan Objects . This scans the
BACnet objects on the selected device and adds them to the BACnet Network Scan
folder as a separate sub-folder for the device as shown in Figure 132.
Figure 132: BACnet network scan results.
6.
Click Close when all devices needed have been scanned.
6.9.2 Import from EDE File
If the device is engineered offline or some of the required BACnet devices are not yet online in the network, the engineering process can be done by importing a device and object list from a set of EDE files. These objects also appear in the import folder and can be later used on the device.
There are a set of EDE files. Select the main EDE file, e.g. device.csv
. The EDE import will also search for the other components, which must be named device-states.csv
. Which
components are expected, please refer to Section 13.3.3. Example EDE files can be found
in the ‗examples‘ directory of the LOYTEC Configurator software installation directory.
To Import BACnet Objects from an EDE File
1.
Open the data point manager dialog.
2.
Select the folder BACnet EDE File
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 151 LOYTEC
3.
Right-click and select Import File . In the following file selector dialog, choose the
EDE import file and click OK .
4.
Now the BACnet EDE File folder is populated with the imported BACnet objects.
6.9.3 Use Imported BACnet Objects
After BACnet objects have been imported (with a network scan or by importing from an
EDE file) the user can select the BACnet objects that the device shall access. When executing the Use on device the configuration software allocates client mappings on the device. These client mappings will read or write values from the BACnet objects in the network.
In an additional step, there can be also server objects allocated on the device. These server objects can be created automatically from converting a client mapping to a server object.
This is usually done, if the imported BACnet objects shall also be directly modified over the
BACnet network on the device itself.
To Use Imported BACnet Objects on the Device
1.
Open the data point manager dialog and select the desired BACnet objects in one of the import folders.
2.
Use the multi-select feature by holding the Shift or Ctrl keys pressed.
3.
Click on the button Use on Device in the tool bar.
4.
This creates data points in the BACnet Port/Datapoints folder. All data points in that folder will be created as client mappings. No server object is created automatically in this case.
5.
To also create server objects select the data points in question using the multi-select feature. Then edit the property Allocate Server Object and set it to Yes.
6.9.4 Edit a Client Mapping
The client mapping information in BACnet data points can be edited after they have been created. Usually, this is done to correct the remote BACnet object instance number.
To Edit a Client Mapping
1.
Select the BACnet data point that has the client mapping to be edited.
2.
On the Client Map property click the … button
3.
This opens the Modify Client Mapping
dialog as shown in Figure 133.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 152 LOYTEC
Figure 133: Modify Client Mapping Dialog.
4.
Edit the target device by selecting a different device in the list of known devices. Edit the target object instance number. For read client mappings edit the COV expiry or
Pollcycle setting. For write client maps edit the Write Priority . When finished click
Save Changes .
6.9.5 Create Server Object
On the BACnet port server objects can also be created manually. These BACnet objects are visible on the BACnet network and can be modified by other devices. They appear as data points in the BACnet/Datapoints folder.
To Create Server Objects Manually
1.
Select the Datapoints folder under the BACnet Port folder.
2.
Right-click in the data point list and select New Datapoint… in the context menu. This opens the Create New BACnet Point
dialog as shown in Figure 134.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 153 LOYTEC
Figure 134: Create a Server Object manually.
3.
In the Mandatory Properties enter a Datapoint Name and an Object Type .
Optionally, update the Instance No and select the Commandable check box for value objects, if the value object shall be commandable from the network.
4.
In the Optional Properties you may select Engineering Units for analog objects. For all object types you can enter the Description . The Device Type can be left empty.
5.
Click Create Server Object . The BACnet data point is created and appears in the data point list.
6.9.6 Export Server Objects to an EDE File
When engineering offline it can be beneficial to hand out the server object configuration of the device to other parties electronically. For doing so you may export the server object configuration to a set of EDE files. The set of EDE files consist of the main EDE file, e.g. myDevice.csv
. This file refers to state texts that are exported to a second file named myDevice-states.csv
. For which components are exported in an EDE file, please refer to
To Export an EDE File
1.
Select the BACnet Port folder.
2.
Right-click and select Export EDE … in the context menu. This opens the EDE export
dialog to enter the EDE header information as shown in Figure 135.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 154 LOYTEC
Figure 135: EDE Export Dialog.
3.
Click the button to select the EDE file export location.
4.
Specify the Device Name and Device Instance . The device instance will be used by other tools to configure their BACnet clients for accessing the exported device.
5.
Optionally fill in project name, author to document that information in the EDE file.
6.
Click Export .
6.9.7 Map other Properties than Present_Value
When creating a BACnet server object, the Present_Value property is mapped by the created data point. That means writing and reading on the data point reads or writes the
Present_Value. If other properties shall be accessed, they must be added to the BACnet server object‘s data point.
To Add other Properties
1.
Select the BACnet server object for adding properties.
2.
Right-click on the data point and select Add/Remove BACnet properties … . The
dialog appears as shown in Figure 136.
Version 4.0
Figure 136: Dialog for adding/removing BACnet properties.
3.
Check the additional properties. Checking the Read box will add an input data point, checking the Write box will add an output data point.
LOYTEC electronics GmbH
L-INX User Manual 155 LOYTEC
4.
Click Close . The selected data point can now be expanded with the plus icon and show its additional properties as sub-data points.
5.
To remove properties perform the same steps and uncheck the corresponding checkboxes. Alternatively, select the property (or more) and press the Delete key.
6.9.8 Enable International Character Support
By default BACnet objects on the device contain ASCII strings in properties such as object name, description, active/inactive text, state texts. This is the setting most third-party tools are interoperable with. To support international character sets, the device can be configured to expose strings as ISO-8895-1 (for most Western European languages) or UCS-2 (for
Unicode character sets such as Japanese).
To Enable International Character Support
1.
In the Configurator software menu go to Settings
Project settings … . This opens the Project Settings
dialog (see also Section 6.3.5).
2.
Click on the tab BACnet .
3.
Put a check mark either on ASCII (default), UCS-2 (Unicode, e.g., for Japanese), or
ISO-8859-1 (for Western European languages).
4.
Click OK.
5.
Download the configuration to activate the change.
6.10 Connections
6.10.1 Create a New Connection
After having configured the device‘s network ports with data points, internal connections between those data points can be created. Usually, the manual method to create a connection is used to create connections between different named data points.
A connection is an internal mapping in the device between input and output data points. A connection always consists of one hub data point and one or multiple target data points.
Hub data points can be input or output. If the hub data point is an input, then the target data points must be output and vice versa. All data points in the connection must be of a compatible type.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 156
To manually create a new connection
Click on the Connections tab
Note:
LOYTEC in the tool bar of the main connections window and press Add Connection… . A new connection is added to the connection list. Rename the connection if you want to do so.
1.
Click on Select Hub… to select the hub point. This opens a list of all available data points. Select one and press OK .
2.
Then click on Add Target… Similar to 2) select all target data points. You may use multi-select to select more than one data point at a time.
By default only compatible data points are displayed. Sometimes compatible data points are available as member points (e.g., a SNVT structure member). Click on to expand the data point and select the desired member point.
3.
Now the connection dialog contains a hub and two target data point as shown in Figure
Figure 137: Connection dialog with hub and target points.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 157 LOYTEC
6.10.2 Create Connections from a CSV File
A quick way to perform batch edit on connections is to export and import connections from the connections CSV file. Each line in the connections CSV file identifies a connection. The first column is the connection name. The second column specifies the hub data point. The full path to the data point must be specified using the dot ‗.‘ as the folder separator. The third and following columns specify the target data points.
To Create Connection from a CSV File
1.
Select the menu Tools
Export Connections …
2.
Select an appropriate file name and export.
3.
Edit the connections CSV file. An example is shown in Figure 138.
#connection_csv_ver,1
#ConnectionName,HubDPName,TargetDPName
Ai0,LINX-200.BACnet Port.ai0,LINX-200.User Registers.abs_humid1
Ai1,LINX-200.BACnet Port.ai1,LINX-200.User Registers.abs_humid2
Ai2,LINX-200.BACnet Port.ai2,LINX-200.User Registers.abs_humid3
Ai3,LINX-200.BACnet Port.ai3,LINX-200.User Registers.abs_humid4
Figure 138: Example Connection CSV File.
4.
Select the menu Tools
Import Connections …
5.
If connections that are not part of the connection CSV file shall be deleted, click Yes when prompted. Click No if the other connections shall be left as is.
6.
Choose the file to import and click Ok .
7.
When the import has completed, optionally view the log to check, which connections have been added, modified, and deleted.
6.10.3 Modify Connections
Connections can be edited and deleted. This is also done in the Connections tab of the main window. Editing connections does not influence the data point configuration. This means, when deleting a connection or adding/removing data points to/from a connection, the data points are not deleted.
To Edit a Connection
1.
Change to the Connections tab of the main window.
2.
Select the connection to edit. Then follow the steps as applied when creating a connection.
3.
To delete a target, select the target and click on Remove Target(s) .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 158 LOYTEC
To Delete a Connection
1.
Change to the Connections tab of the main window.
2.
Select the connection for removal. Use multi-select to select more than one connection.
3.
Click Remove .
6.10.4 Connection Overview
Select the Connection Summary tab to get a graphical representation of all connections. It represents the two connected data points, their technology they are based on and the
direction of the connection. An example for the overview is shown in Figure 139.
Figure 139: Connections Summary.
6.11 E-mail Templates
6.11.1 Create an E-mail Template
E-mail templates are used to assemble and transmit e-mails when certain trigger conditions occur. The e-mail template contains the destination e-mail address, the subject, and text.
Variable parameters can be added to the text by using data point sources. The transmission of an e-mail is triggered by one or more trigger data points. For setting up e-mails, the e-mail account information has to be configured on the device, e.g., on the Web UI (see
To Create an E-mail Template
1.
Under the Global Objects folder, select the E-mail Configuration sub-folder.
2.
Right-click and select New E-mail Template … from the context menu.
3.
In the Configure E-mail Template
dialog, which is shown in Figure 140 enter the
To address and the Subject . Optionally, Cc and Bcc addresses can be specified.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 159 LOYTEC
Figure 140: Configure E-Mail Template Dialog.
4.
Enter text in the E-mail Text multi-line field.
5.
If the e-mail text shall contain values of data points, add data points to the Data
Sources list by clicking the Add… button.
6.
A data point selector dialog opens. Select one or more data points and click OK . The selected data point appears in the Data Sources list.
7.
Select the data point in the Data Sources list. In the drop-down box underneath select
Selected Data Source Value and click the Paste to Text button.
8.
A place holder %{v1} for the data point value appears now in the e-mail text.
9.
To replace an existing data source select the data point in the Data Sources list and click the Replace… button. This opens a data point selector dialog for choosing the replacement data point.
6.11.2 Trigger E-mails
E-mail templates are used to assemble and transmit e-mails when certain trigger conditions occur. For an e-mail template, one or more trigger conditions can be defined. The e-mail will be sent, when one of the trigger conditions is activated. Depending of the trigger data point type, the trigger conditions can be refined.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Note:
160 LOYTEC
Note, that the behavior of the trigger data point is influenced by the COV properties of the data point. If the Only notify on COV property is checked, the data point triggers only if its value changes to the value of the trigger condition. If that property is not checked, the data point triggers on every write with a value that matches the trigger condition.
The trigger for sending an e-mail can be enabled or disabled altogether by using an enable data point. This data point must be of type binary . If the value of that enable data point is
TRUE, the trigger conditions are evaluated. If the value of the enable is FALSE, no e-mails are be triggered.
To Create an E-mail Trigger
1.
Under the Global Objects folder, select the E-mail Configuration sub-folder.
2.
Right-click and select Configure E-mail Template … from the context menu.
3.
Change to the Mail Triggers tab.
Of course, you can also change directly to the Mail Triggers tab when creating an e-mail template.
4.
Click the Add… button. A data point selection dialog opens.
5.
Select one or more data points and click OK .
6.
The triggers appear now in the E-Mail Triggers list. The data points that serve as e-mail triggers also appear with the e-mail icon in the data point list.
7.
In the Manage Trigger Conditions you can setup the trigger condition depending on the trigger data point class.
8.
If the trigger condition is depending on the value of an enabling data point, you can add an enable data point by clicking on the … button.
9.
To remove such a trigger enable, click the Remove Enable Trigger button.
6.11.3 Attachments
E-mail templates can be configured to have file attachments. Basically, any file of the device can be specified as an attachment.
To Configure Attachments
1.
Under the Global Objects folder, select the E-mail Configuration sub-folder.
Version 4.0
2.
Right-click and select Configure E-mail Template … from the context menu.
LOYTEC electronics GmbH
L-INX User Manual
Note:
161 LOYTEC
3.
Change to the Attachments tab.
Of course, you can also change directly to the Attachments tab when creating an e-mail template.
4.
Select an available file from the Attach File drop-down box.
5.
Click the Add button. The file appears in the Attachments list.
6.
To remove an attachment, select the attachment file in the Attachments list and click the button Remove .
6.11.4 Limit E-mail Send Rate
The transmission of e-mails is triggered by the configured trigger conditions. It is not predictable, how often the trigger condition will cause the transmission of an e-mail. The e-mail template can be configured to limit the number of transmitted e-mails. This is done in the Configure E-mail Template dialog.
To configure an E-mail Rate Limit, configure the settings:
Max. E-mails per day : This setting defines how many e-mails can be sent on average per day. The actual number of transmitted e-mails on a specific day may be slightly higher than this setting, depending on burst rates. The default is 100 e-mails per day.
This results in an average interval of one e-mail per 14 minutes.
Send burst count : This setting defines how many e-mails may be transmitted shortly after each other not limited by the above average interval. After the burst count, the average mails per day limit takes effect. The default is a maximum of 20 e-mails in a row.
6.12 Local Schedule and Calendar
6.12.1 Create a local Calendar
As the first step, the required data points must be created. A calendar must be created, if the schedules shall work with exception days, such as ―Holidays‖. If it suffices for schedules to define daily schedules for normal weekdays only, no calendar needs to be created.
To Create a Local Calendar
1.
Under the port folder, select the Calendar sub-folder to create a calendar.
Version 4.0
2.
Right-click in the data point list view and select New local Calendar … .
3.
In the Create New Calendar dialog box (as shown in Figure 141) enter Name and
Description of the calendar. Note, that a BACnet calendar does not have the Effective
Period settings.
LOYTEC electronics GmbH
L-INX User Manual 162 LOYTEC
Figure 141: Create New Calendar dialog box.
4.
Click Create Calendar . The calendar appears now in the data point list view.
6.12.2 Create Calendar Pattern
When a local calendar is used, it needs to be configured with calendar patterns. A calendar pattern represents a class of days such as ―Holidays‖. The calendar patterns can then be used in a schedule to define daily schedules for exception days. The available calendar patterns should be created when the system configuration is engineered. The actually dates in the calendar patterns can be modified later at run-time.
To Create a Calendar Pattern
1.
Select an existing calendar data point.
2.
Right-click and select Create Calendar Pattern…
3.
Enter a Pattern Name in the Create Calendar Pattern dialog
4.
Click Create Pattern . The dialog closes and the calendar pattern appears beneath the calendar data point.
6.12.3 Create a Local Scheduler
For scheduling data points, a scheduler object must be created. Under each port folder, multiple local scheduler objects can be created. These local schedulers can then be configured to schedule data points.
To Create a Local Scheduler
1.
Under the port folder, select the Scheduler sub-folder to create a scheduler.
Version 4.0
2.
Right-click in the data point list view and select New Local Scheduler … .
LOYTEC electronics GmbH
L-INX User Manual 163 LOYTEC
3.
Enter a name for the schedule and a description. Note, that the schedule automatically detects a calendar, if it has previously been created.
4.
Click Create Schedule . The new schedule appears in the data point list of the
Scheduler sub-folder.
6.12.4 Configure Scheduled Data Points
When a local scheduler has been created, it needs to be configured, which data points it shall schedule. This is done by attaching data points to the scheduler. Note, that there may
be limits, how many and which data points may be attached (see Section 5.5.3).
This configuration must be done as an initial setup. The daily schedules, however, can be changed later in the Web UI or over the network.
To Attach Data Points to a Scheduler
1.
Select the scheduler data point in the Scheduler sub-folder.
2.
Right-click and select Configure Schedule from the context menu. The same dialog which appears when a new scheduler is created is shown and allows configuring the scheduler. Of course, this step can also be done directly when the data point is created.
3.
Select the tab Scheduled Datapoints .
Tip!
4.
Click the button Attach Datapoints . This opens another data point selector window.
5.
Select the data points to attach and click OK . For each of the attached data points, one or more lines appear in the list below the attach button. If the attached point is a structure, there will be one line for each element of the structure.
Data points can also be attached to a scheduler by selecting a data point in the data point manager, drag it onto a scheduler data point and drop it on the scheduler data point.
6.
Enter a short text in the Description field in the second column of each line. This text will serve as a label, which will be shown on the device‘s UI to identify the data point.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 164 LOYTEC
Tip!
7.
Add new value presets by entering a name and pressing the Create button next to the input field.
To generate presets automatically for multi-state data points, click the Auto-Create button.
This button is available, if no other presets have been defined yet.
8.
For each new preset, a new column will appear in the list. In this column, enter the desired value for each of the attached points, which will be set when this value template is scheduled. The user may later edit the values for each preset on the device but cannot add new value presets unless there is only one line (one value) in the list.
9.
If there are multiple output values which belong together, they can be grouped in order to save space on the device. For each group, the entered value is stored only once, even if there are more data points in the same group.
Tip!
10.
When done with the point and value setup, switch back to the Configuration tab or click Save Changes to leave the dialog.
A shortcut to creating a scheduler object and attaching a data point is to select a data point in the data point manager, right-click on it and choose Schedule Datapoint from the context menu. This generates a scheduler and links that data point to it.
6.12.5 Configure Daily Schedules
Once a scheduler is configured with attached data points and value presets, the daily schedules can be defined. This can be done on the device or over the network at run-time, or also in the configuration software. A daily schedule defines the time and value sequences in a 24-hour period starting at 00:00 and ending at 23:59 hours. For each weekday a daily schedule can be configured.
In addition, daily schedules can be configured for exception days from a calendar, such as
―Holidays‖. An exception day always overrides a normal weekday. If more than one exception day is used, a priority must be assigned. This is necessary so that the system knows which schedule to follow on a day which matches more than one calendar pattern.
To Configure a Daily Schedule
1.
Open the Configure Schedule dialog and click on the Configuration tab (see Section
2.
Select the day for which to configure a daily schedule.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 165 LOYTEC
3.
Select a value preset in the Available Data Presets box on the upper right-hand side.
4.
Drag and drop the preset from this list into the time table area to define the desired output values on the day schedule.
5.
Completed daily schedules may be copied to other days using the Copy to button. For example, the Monday may serve as the template for a regular work day and be copied to Tuesday till Friday. Then click OK .
Version 4.0
To Use Exception Days
1.
Select a calendar pattern, which shall be used as an exception day and place a checkmark on it.
2.
Edit the daily schedule.
LOYTEC electronics GmbH
L-INX User Manual 166 LOYTEC
Important!
3.
If more than one calendar pattern is used, edit the priorities. For example, if a given calendar day falls in both categories, ―Holidays‖ and ―Maintenance‖, the exception day with the higher priority becomes effective on that day. The highest available priority is marked highest . Note that the actual priority values depend on the technology (see
Choose different priorities for different exceptions. If two exceptions are valid for a given day and their priorities are equal, it is not determined, which exception is in effect.
6.12.6 Configure Exception Days
When a local calendar is used, its calendar patterns need to be configured with exception days (pattern entries). The calendar patterns can be configured in the LINX-100/200
Configurator software or be modified at run-time over the Web UI or over the network.
When configuring in the software, the current exception days should be uploaded from the device, to work on the current configuration.
To Configure Exception Days in a Calendar Pattern
1.
Click on the Upload calendar/scheduler configuration button in the tool bar of the main connections window. Click OK when the upload is finished.
2.
Select the Calendar sub-folder and select the calendar pattern, which shall be configured
3.
Right-click and select Configure Pattern … in the context menu.
4.
The Configure Pattern
dialog appears as shown in Figure 142. Add dates to the
calendar pattern by entering a Date Configuration. Then click Add Entry . The date appears in the Pattern Entries list on the right-hand side.
5.
Edit an exception by selecting the pattern entry in the Pattern Entries list. Then modify the date configuration in the Date Configuration group box.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 167 LOYTEC
Tip!
Figure 142: Configure Calendar Pattern Dialog.
6.
Click Save Changes when all exception days have been entered.
If not sure, how a date configuration affects the calendar days, click on a pattern in the
Pattern Entries list and the affected days will be highlighted in the Preview .
6.12.7 Configure Embedded Exceptions
Besides exception days of the calendar, special exception days can be embedded into the scheduler. These embedded exception days are not visible or accessible in other scheduler objects.
To Configure an Embedded Exception
1.
Open the Configure Schedule dialog to configure daily schedules as described in
2.
Click on the Create button below the Weekly/Exception Schedule Configuration list
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 168 LOYTEC
3.
The Create Pattern dialog opens. You can enter exactly one pattern entry for the embedded exception. It is recommended to choose a descriptive name for the day, e.g.
‗24_12‘xx‘ for every 24 th
of December.
4.
Click Create Pattern . The embedded exception is now available.
6.12.8 Configure Control Data Points
A scheduler object can be configured to use special control data points. These data points can control the scheduler and expose additional state information of the scheduler on the network. The following control data points are available:
Scheduler Enable/Disable Datapoint : This data point can be configured, which enables or disables the scheduler depending on its Boolean value.
Enable/Disable Feedback Datapoint : This data point is updated with the current enabled state of the scheduler. This also reflects and an enable from the network.
Scheduled Preset Name : This data point can be attached to be updated with the name of the currently active preset. Only string data points can be attached.
To Configure Control Data Points
1.
Open the Configure Schedule dialog to configure daily schedules as described in
2.
Go to the Scheduled Datapoints tab.
3.
In the Control Datapoints group box, click the button to add the desired control data point. A data point selection dialog opens.
4.
Select a matching data point and click OK . For the preset name a string data point must be selected.
5.
To remove an undesired control data point, click on the Remove button.
6.12.9 Using the SNVT_tod_event
On LOYTEC devices with the CEA-709 technology the SNVT_tod_event can be used in a schedule for implementing the next-state feature. The parts of this network variable contain:
Current state: This is the currently scheduled occupancy state.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 169 LOYTEC
Next state: This is the next, future occupancy state in the schedule.
Time to next state: This part reflects the time in minutes until the next state becomes active.
To Use a SNVT_tod_event
1.
Create a SNVT_tod_event in the data point configuration.
2.
Add the SNVT_tod_event to the scheduled data points of a scheduler as described in
3.
All three parts of the SNVT_tod_event are scheduled.
6.12.10 Using the Local Scheduler
Once the setup of the local scheduler is done, it is basically operational. It will immediately start working based on the configuration data downloaded through the configuration software. You can verify the daily schedules and values of scheduled data points on the
Web UI (see Section 4.2.18). The local schedule can be altered over the Web UI or over the
network using the underlying networking protocol.
6.13 Local Alarming
6.13.1 Create an Alarm Server
To generate local alarms, an alarm server needs to be created at first. The local alarm sources will report alarms to that alarm server. The alarm server is the interface to access local alarms. This can be done over the network or the Web UI.
To Create an Alarm Server
1.
Under the port folder, select the Alarm sub-folder to create an alarm server.
2.
Right-click in the data point list view and select New Alarm Server … .
3.
In the Create New Alarm Server
dialog box (as shown in Figure 143) enter
Name and
Description of the alarm server.
Version 4.0
Figure 143: Create New Alarm Server dialog box.
LOYTEC electronics GmbH
L-INX User Manual 170 LOYTEC
4.
Click Create . The alarm server appears now in the data point list view.
5.
For a BACnet alarm server, select the created object and edit the properties for transition priorities (To-Normal, To-Fault, To-Offnormal) and the corresponding check boxes, which define whether acknowledgements are required. These are the standard
BACnet settings in a Notification Class object.
6.13.2 Create an Alarm Condition
To generate alarms from data points, intrinsic reporting is used. For each data point an alarm condition must be defined. This condition employs an intrinsic algorithm to generate alarms based on the data point‘s value. Depending on the data point type (analog, binary, multi-state), different conditions are defined. The alarm is reported to the attached alarm server.
To Create an Intrinsic Alarm Condition
1.
Select a data point.
2.
Right-click and select Create Alarm Condition… from the context menu.
3.
For an analog data point, the dialog as shown in Figure 144 appears. Select the
Alarm
Server . Optionally, enter an Alarm Description . If left empty, the description of the data point is used. Enter a Time Delay , after which the condition is evaluated. Select
Low Limit and High Limit and put check marks, if they shall be employed. Enter a
Deadband to account for hysteresis.
Version 4.0
Figure 144: Alarm Condition for an Analog Data Point.
LOYTEC electronics GmbH
L-INX User Manual 171 LOYTEC
4.
For enable, deadband, low limit and high limit data points can be attached by clicking the button. Those data points are used by the device to determine the actual values at run-time.
5.
For a binary data point, the dialog as shown in Figure 145 appears. Select the
Alarm
Server . Optionally, enter an Alarm Description . If left empty, the description of the data point is used. Enter a Time Delay , after which the condition is evaluated. Select the Alarm Value which triggers the alarm.
Figure 145: Alarm Condition for a Binary Data Point.
6.
For enable, a data point can be attached by clicking the button. This data point is used by the device to determine the actual values at run-time.
7.
For a multi-state data point, the dialog as shown in Figure 146 appears. Select the
Alarm Server. Optionally, enter an Alarm Description . If left empty, the description of the data point is used. Enter a Time Delay , after which the condition is evaluated.
Select the Alarm States , which triggers the alarm, by clicking the arrow buttons.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 172 LOYTEC
Figure 146: Alarm Condition for a Multi-State Data Point.
8.
For enable, a data point can be attached by clicking the button. This data point is used by the device to determine the actual values at run-time.
9.
Click on Create . In the alarm column, the alarm sign will be added for those data points that have an alarm condition.
6.13.3 Deliver Alarms via E-mail
Updates in the alarm summary of an alarm object can be used as a trigger to send e-mail.
For setting up e-mails, the account information has to be configured on the device, e.g., on
the Web UI (see Section 4.2.15). Then an e-mail template can be created and the alarm
point attached as a trigger.
To Create an E-mail Template for Alarms
1.
Create or configure an e-mail template as described in Section 6.11.1.
2.
Change to the Mail Triggers tab.
3.
Click the Add… button and select an alarm data point.
4.
In the Mail Triggers list select the added trigger data point.
5.
In the Manage Trigger Conditions list put a check mark on alarm conditions that shall invoke the transmission of the e-mail.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 173 LOYTEC
6.
Change to the Common E-Mail Properties tab.
7.
Add the alarm data point as a data source and insert the place holder into the e-mail text
as described in Section 6.11.1.
6.13.4 Create an Alarm Log
The alarm objects on the device contain an alarm summary (live list) of currently active and acknowledge-pending alarms. As soon as an alarm becomes inactive and has been acknowledged, it disappears from the alarm summary. To store a historical log of alarm transitions an alarm log needs to be created.
An alarm log can log transitions of one or more alarm objects. Its size is configurable. The alarm log is a ring buffer. As soon as its size limit is reached, the oldest alarm log records are overwritten by new alarm transitions.
To Create an Alarm Log
1.
Under the Global Objects folder, select the Alarm Log Object Configuration subfolder.
2.
In the data point list right-click and select New Alarm Log … from the context menu.
Version 4.0
3.
In the Create New Alarm Log dialog enter a Name for the alarm log. Optionally enter a Description .
4.
Enter a Log Size , which defines how many transitions are resident in the alarm log.
5.
Define a percentage for Fill Level Notification , which can be used to trigger the ransmission of E-Mails.
LOYTEC electronics GmbH
L-INX User Manual 174
6.
Click on the button Add… on top of the Logged Alarm Objects list.
LOYTEC
7.
A data point selector dialog opens. Select one or more alarm objects that shall be logged and click OK . The alarm objects appear in the list.
8.
Click Create to create the alarm log object.
6.14 Local Trending
6.14.1 Create a Local Trend
The value of a data point can be logged over time. This is referred to as trend data. To generate trend data a trend object has to be created. The trend data is stored in a data logger
file. This file can be downloaded via FTP in binary or CSV format (see Section 13.1.2).
Trend objects can generate trend logs for single and multiple data points and can be operated in one of the following basic modes:
Interval Mode : In this mode a snapshot of all trended data points is logged into the data logger file.
COV Mode : In this mode, each of the trended data points is logged separately, if and only if its value changes. For analog data points, a specific COV increment can be configured in the data point configuration properties of the trended data point.
Trigger Mode : In this mode a snapshot of all trended data points is logged each time a trigger condition fires. The trigger condition is applied to a trigger data point.
To Create a Trend Object
1.
Under the port folder, select the Trend sub-folder to create a trend log object.
2.
Right-click and select New Trend … from the context menu.
3.
In the Create New Trend Object
dialog (shown in Figure 147) enter a name and
optionally a description for the trend log object.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 175 LOYTEC
Figure 147: Basic Trend Object Configuration.
4.
Select the desired Trend Mode .
5.
Select the Log Size . The display in the dialog will adapt the estimations for needed data logger file size in KB and duration of the trend log. Alternatively, for interval trends, the estimated log duration and log interval can be edited.
6.
Select a Fill Level Notification percentage. This will decide at which fill-level trigger will fire. A fill-level trigger can be used to trigger the transmission of an e-mail (see
7.
Click Save changes to store the basic configuration of the trend object. The new trend log object appears in the data point list of the Trend folder.
6.14.2 Configure Trended Data Points
When a local trend object has been created, it needs to be configured, which data points it shall log. This is done by attaching data points to the trend object. Only simple data points can be attached for trending, i.e., of class analog, binary, or multi-state. For trend log objects in the BACnet technology, single data points can be attached only.
The trending can be enabled/disabled on behalf of an enable data point. This data point should be of type binary . If the value of that enable data point is TRUE, the trend object logs data as defined by the trend mode. If the value of the enable is FALSE, trending is disabled. If no enable data point is configured, the trend log is always enabled.
To Attach Data Points for Trending
1.
Select the trend object in the Trend sub-folder.
2.
Right-click and select Configure Trend from the context menu. The same dialog which appears when a new trend object is created is shown and allows configuring the trend object. Of course, this step can also be done directly when the object is created.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 176 LOYTEC
3.
Add data points to be trended. Click on Add … which opens a data point selector window.
Tip!
Tip!
4.
Select the data points and click OK . For each of the attached data points, a line appears in the list below the add button. The trended data points will also appear with the trend icon in the data point manager.
Data points can also be attached to a trend by selecting a data point in the data point manager, drag it onto a trend object and drop it on the trend object.
5.
Data points can be removed from the trend by clicking Remove .
6.
If COV mode was selected, the COV increment is displayed in the COV delta column.
This value can be increased to produce less trend data. Note, that it cannot be lowered under the trended data point‘s own COV increment. Go to the data point configuration to change the COV increment in this case.
7.
If the trended value of the data point shall be aggregated over the log interval, select the desired aggregation in the Type column. Available options are Min , Max , Avg .
For creating multiple curves with min, average, and maximum values, add the same data point three times and select the different aggregation types.
8.
In addition, a special Trend Enable data point can be selected. If configured, the trend log will only log data, if the value of this data point evaluates true , i.e., is not zero.
Click the … button to select a data point.
Tip!
9.
To remove the enable data point, click the Remove button.
10.
When done with the data point setup, click Save Changes to leave the dialog.
A shortcut to creating a trend log object and attaching a data point is to select a data point in the data point manager, right-click on it and choose Trend Datapoint from the context menu. This generates a trend log and links that data point to it.
6.14.3 Trend Triggers
Local trend objects in CEA-709 can be operated in trigger mode . In this mode, one or more trigger data points cause the generation of a snapshot containing the values of the trended data points at the time instant the trigger is activated. For a trend object, one or more trigger conditions can be defined. Depending on the trigger data point type, the trigger conditions can be refined.
Note, that the behavior of the trigger data point is influenced by the COV properties of the data point. If the Only notify on COV property is checked, the data point triggers only if its value changes to the value of the trigger condition. If that property is not checked, the data point triggers on every write with a value that matches the trigger condition.
Version 4.0
To Configure Trigger Data Points for Trending
1.
Select the trend object in the Trend sub-folder.
LOYTEC electronics GmbH
L-INX User Manual
Note:
177 LOYTEC
2.
Right-click and select Configure Trend from the context menu.
3.
Change to the Triggers tab.
Of course, you can also change directly to the Triggers tab when creating a trend object.
4.
Click the Add… button. A data point selection dialog opens.
5.
Select one or more data points and click OK .
6.
The triggers appear now in the Trend Triggers list.
7.
In the Manage Trigger Conditions you can refine the trigger condition depending on the trigger data point class.
8.
When done with the data point setup, click Save Changes to leave the dialog.
6.14.4 Download Trend Data in CSV Format
Trend logs can be downloaded from the device via FTP in CSV format (see Section 13.1.2).
The CSV contents are generated on-the-fly from the internal binary storage when accessing the file. Each trend log point has one CSV file. The files are located in
/data/trend/ TrendLogName _ UID .csv
Where TrendLogName is the data point name of the trend (Trend Name). The UID is the unique ID of the trend log object. The UID can be obtained from the ID column in the data
point list of trend log data points as shown in Figure 148. This would result in the trend
CSV file ‗ /data/trend/out_temp_107C.csv
‘.
Figure 148: UID of data points.
Because the contents are generated on-the-fly, the file size in the FTP client will appear as 0
Bytes. The decimal point and CSV column separator can be configured in the system
configuration of the Web UI (see Section 4.2.1). Note, that for a comma ―,‖ as the
separator, the decimal point is a point. This is useful for English/U.S. applications. For countries that use the comma as the decimal point, select the semicolon as the CSV separator.
6.14.5 Deliver Trend Data via E-mail
Trend logs can be downloaded from the device via FTP. This requires an active action by the user. Alternatively, trend data can be sent as an e-mail attachment. For doing that, an e-mail template has to be setup for the trend log to be transmitted. The fill-level condition in the trend object can be used as a trigger to send an e-mail with the trend‘s data logger CSV file as an attachment.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 178 LOYTEC
For setting up e-mails, the account information has to be configured on the device, e.g., on
the Web UI (see Section 4.2.15). Then an e-mail template can be created and the trend
object attached as a trigger.
To Create an E-mail Template for Trends
1.
Create or configure an e-mail template as described in Section 6.11.1.
2.
Change to the Mail Triggers tab.
3.
Click the
Add…
button and select a trend object.
4.
In the Mail Triggers list, the added trigger data point appears with the Fill Level condition.
Note:
5.
Change to the Attachments tab.
6.
Select the trend log CSV file of the trend object in the Attach File drop-down box and click Add .
ZIP versions of the CSV files are also available. Select those to save transmission bandwidth and mailbox space.
7.
Click OK to complete the e-mail template configuration.
6.15 Remote AST Objects
6.15.1 Remote Scheduler and Calendar
Adding remote access to the configuration of a scheduler and calendar, which is located on another device, is done by creating remote scheduler and calendar objects. These objects can be created from data obtained by a network scan.
To Create a Remote Scheduler
1.
Execute a network scan, as described earlier in this document. The scan folder is filled with available schedulers.
Version 4.0
2.
From the data points in the import folder, select the scheduler objects you are interested in and click the Use on Device speed button. This creates suitable remote schedulers and the corresponding calendar objects in the Remote Devices folder.
LOYTEC electronics GmbH
L-INX User Manual 179 LOYTEC
Note:
Note:
3.
Adjust the basic settings for the newly created objects, such as the object name and description. The object name will be used as the name for the scheduler, as seen on the
Web UI.
4.
In the CEA-709 technology a static NV is created to receive information from the remote device about changes to the scheduler configuration, so that the local device does not need to poll the remote device. Set a name for this NV (default is nviSchedLink<number>) and assign it to a suitable function block.
Due to the static input NV, which is required for a remote CEA-709 scheduler object, adding remote scheduler points will change the static interface of the device.
The new static input NV representing the remote calendar on the local device (this NV is normally called nviCalLink ) needs to be bound to the output NV called nvoCalLink located in the Calendar functional block of the remote device and the new static nviSchedLink NVs which were created for each remote scheduler point need to be bound to the respective nvoSchedLink variable located in the Scheduler functional block of the remote device. The binding between the nvoSchedLink variable on the remote device to the nviSchedLink variable on the local device defines which of the scheduler data points on the local device connect to which scheduler unit on the remote device. All required information is transmitted over the link NVs, so it is possible to later change the binding to any other remote scheduler without rescanning the network.
If connected via LNS, the bindings to the nvoCalLink and nvoSchedLink NVs are made automatically by the configuration software in the download process.
6.15.2 Alarm Clients
Accessing alarm server objects on remote devices is done by creating remote alarm data points. These points may be created from data obtained by a network scan. The local device is configured as an alarm client and subscribes to alarm updates from the remote alarm server. The alarm client can also be used to acknowledge alarms on the remote alarm server.
Any updates are synchronized back to the alarm client.
To Create an Alarm Client
1.
Execute a network scan, as described earlier in this document. The scan folder is filled with available remote alarm servers.
2.
From the points in the import folder, select the alarm server points you are interested in and click the Use on Device speed button. This creates the corresponding alarm client points in your project.
Version 4.0
3.
In the CEA-709 technology select the new alarm client point and adjust the name of the local NV (default name is nviAlarm_2 ). This NV is located in the Clients functional block.
LOYTEC electronics GmbH
L-INX User Manual
Note:
Note:
180 LOYTEC
Due to the static input NV which is required for a CEA-709 alarm client point, adding alarm clients will change the static interface of the device.
The new static input NVs representing the alarm clients on the local device need to be bound to the alarm outputs of the remote device. A CEA-709 device normally delivers alarms through an output NV of type SNVT_alarm_2 located in the node object of the device, therefore the new input NV on the local device must be bound to the alarm output
NV of the remote devices node object. All required information is transmitted over the alarm input NV, so it is possible to later bind the alarm client to any other alarm server without rescanning the network.
If connected via LNS, the binding to the nvoAlarm2 NV is made automatically by the configuration software in the download process.
6.16 Math Objects
6.16.1 Create a Math Object
Math objects are advanced application objects that can execute mathematical operations on data points. A math object takes a number of input data points (variables v
1
, v
2
, …, v n
) and calculates a result value according to a specified formula. When configuring a math object, the input data points, output data points and the formula must be configured by the user.
Input data points can be configured with a change-of-value condition, to trigger the math calculation only if the value changes more than a certain delta.
To Create a Math Object
1.
Under the Global Objects folder, select the Math Object sub-folder.
2.
Right-click and select New Math Object … from the context menu.
3.
In the Create New Math Object dialog, enter a name and optionally a description for the math object.
4.
Attach input data points by clicking the Add Input DP button.
Version 4.0
5.
In the data point selector dialog, select the input data points and click OK . The data points appear as v1, v2, etc.
6.
If the data point shall trigger the math calculation only after a certain change-of-value, enter a value into the COV delta column.
7.
Select the input data point and click Add Variable to push the variable on the evaluation stack.
LOYTEC electronics GmbH
L-INX User Manual 181 LOYTEC
8.
Select a function to be applied on the variables and click the Add Function button.
9.
Te resulting formula is displayed at the bottom of the dialog. Alternatively, the formula can be entered there.
10.
Add output data points by clicking the Add Output DP button .
11.
In the data point selector dialog select the output data points and click OK .
12.
To create the math object click Create .
6.16.2 Editing a Math Object
Math objects can be edited once created. The formula can be changed, new variables added, or additional output data points added.
To Edit a Math Object
1.
Under the Global Objects folder, select the Math Object sub-folder.
2.
Select the math object in the data point list.
Version 4.0
3.
Right-click and select Configure Math Object … from the context menu.
4.
Edit the math object as described in Section 6.16.1.
5.
To replace an input data point by another input data point without re-writing the entire formula, click the Replace Input DP … button. This opens a data point selector dialog. Select the replacement data point there.
6.
To detach an input data point, click the Detach Input DP button. This leaves the respective variable slot empty.
7.
To finalize the edit click on Save Changes .
LOYTEC electronics GmbH
L-INX User Manual 182
7 The CEA-709 Router
LOYTEC
LOYTEC devices, which are equipped with a standard CEA-709 router (i.e., an embedded
L-IP), connect the FT port and the CEA-852 port. Depending on the use case, the CEA-709 router supports different operating modes how packets are routed between the CEA-709 side and the IP-852 side. LOYTEC devices with the router option also contain a configuration server (CS) to manage members on an IP-852 channel.
7.1 CEA-709 Router
135.23.2.51
135.23.2.52
IP Channel
NV Binding
Version 4.0
Figure 149: The L-INX supports different methods to route packets between the CEA-709 and IP-852 channel.
Depending on the CEA-709 router configuration (see Section 4.2.8) the CEA-709 router
supports 4 different methods to route packets between the CEA-709 and the IP-852 channel.
Those operating modes are listed below and described in more detail in the subsequent sections.
Configured Router: The device acts like a standard CEA-709 configured router ( i .
LON
1000/600 alike)
Smart Switch: The device acts as a self-learning plug&play router (―smart switch mode‖)
Store-and-Forward Repeater: To freeze a learned configuration and operate the switch based on the existing forwarding tables, disable group learning and Subnet/Node learning.
Smart switch with no broadcast flooding: Set Subnet/Node Learning to ―subnet‖. In this mode the router learns the network topology but doesn‘t flood subnet broadcasts.
LOYTEC electronics GmbH
L-INX User Manual 183 LOYTEC
7.1.1 Configured Router Mode
In this operating mode, the router acts like a standard configured router, which can be configured with standard network management tools like LonMaker or NL-220. This operating mode is compatible with the i .
LON 1000 and the i .
LON 600.
This operating mode uses the ―channel routing‖ routing strategy on the IP channel. In this mode the device is fully compatible with i .
LON 1000/600 devices. This operating mode should also be used in networks with more than 10 IP devices on one IP channel and heavy network traffic on the IP channel (more than 500 packets/s) since channel routing sends the
IP packet only to the IP-852 device(s) that connect to the CEA-709 node(s) addressed in this IP packet and not to all IP-852 devices on the IP channel. This is the standard operating mode.
7.1.2 Smart Switch Mode
The router can be configured to act as a learning switch in a CEA-709 network. This operating mode is called smart switch mode. In this operating mode, the router decides if the message has to be forwarded or not, based on the destination address of a message.
Thus, it isolates local network traffic (e.g., in case of heavily loaded networks).
Important:
Important:
Note:
Note:
Note:
Note:
This operating mode doesn’t support network loops!
Whenever a network is reconfigured, it is recommended to clear the forwarding tables in
the device by pressing the status button for at least 20 seconds (see Section 3.5.1).
The router supports learning of up to 4 Domains.
All messages, which are received on an unknown domain, are forwarded to all ports!
The subnet/node learning algorithm supports segmentation of the network traffic on a subnet/node basis. Thus, the user does NOT need to take care of any subnets spanning multiple physical channels. Even when a node is moved from one channel to another, the router keeps track and modifies its forwarding tables accordingly.
All messages with a destination subnet/node address not yet learned are forwarded!
The router supports group learning. Groups can span multiple router ports.
Group learning only works for messages using acknowledged or request/response service.
All messages with a destination group address not yet learned are forwarded!
The router has no learning strategy for broadcast addresses. As a result, all subnet or domain wide broadcasts are always forwarded. If subnet wide broadcasts shall not be forwarded, please use the smart switch operating mode without subnet broadcast forwarding
The router has no learning strategy for unique node ID addresses. Node ID addressed messages are always forwarded.
This operating mode uses the ―channel routing‖ strategy on the IP channel to distribute IP packets. It uses flooding to send all packets on the IP channel to all IP devices on this IP channel. The advantage of this operating mode is that it is fully plug&play and no router configuration is required. The disadvantage is that this operating mode doesn‘t scale very well with larger networks. We do not recommend this operating mode for IP channels with
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 184 LOYTEC more than 10 IP-852 devices and packet rates of more than 500 packets/s. Please use the
configured router mode from Section 7.1.1 for larger IP channel configurations.
Further, it is recommended to configure a multi-cast group for routers in the smart switch
mode to reduce the traffic burden and improve scalability. Refer to Section 7.4 on how to
configure the device to use multi-cast.
7.1.3 Store-and-Forward Repeater
The router can be configured to operate in a repeater mode, where all messages are forwarded regardless of the address format.
This operating mode uses the ―channel routing‖ strategy on the IP channel to distribute IP packets. It uses flooding to send all packets on the IP channel to all IP devices on this IP channel. The advantage of this operating mode is that it is fully plug&play and no router configuration is required. The disadvantage is that this operating mode doesn‘t scale very well with larger networks. We do not recommend this operating mode for IP channels with more than 10 router devices and packet rates of more than 500 packets/s.
Further, it is recommended to configure a multi-cast group for routers in repeater mode to
reduce the traffic burden and improve scalability. Refer to Section 7.4 on how to configure
the device to use multi-cast.
7.1.4 Smart Switch Mode with No Subnet Broadcast Flooding
This operating mode is the same as the smart switch mode from Section 7.1.2 with the only
difference that subnet wide broadcasts are not flooded in this mode. This operating mode can be used in large network installations where the network management tool uses group overloading to replace group addresses with subnet wide broadcasts. In this operating mode, the network installer must ensure that one subnet address may only exist behind one and no more than one network port. This condition is met if nodes are installed using an LNS based tool, on different channels that are separated with a router shape.
This operating mode uses the ―channel routing‖ strategy on the IP channel to distribute IP packets. It uses flooding to send all packets on the IP channel to all IP devices on this IP channel. The advantage of this operating mode is that it is fully plug&play and no router configuration is required. The disadvantage is that this operating mode doesn‘t scale very well with larger networks. We do not recommend this operating mode for IP channels with more than 10 devices and packet rates of more than 500 packets/s.
Further, it is recommended to configure a multi-cast group for the router in the smart switch
mode to reduce the traffic burden and improve scalability. Refer to Section 7.4 on how to
configure the device to use multi-cast.
7.2 CEA-852 Device of the Router
Every L-INX acts as a device on the IP channel. It either needs to contact a configuration server or a configuration server needs to contact the device in order to set up the proper routing tables. Before a device can become a member of the IP-852 channel it needs to have
proper IP settings (see Section 4.2.4):
IP address/netmask/gateway (either via DHCP or manual entry), see Section 4.2.4
Auto-NAT or manual NAT address if used behind a firewall/NAT router, see Section
MD5 secret if authentication is required, see Section 4.2.7
Please consult Sections 4.2.4 and 4.2.7 on how to setup a CEA-852 device.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 185 LOYTEC
The CEA-852 device can be used together with the PC-based i .
LON Configuration Server utility or with any LOYTEC configuration server. If multiple CEA-852 devices behind one
NAT router are added, the Auto-NAT setting in the CEA-852 devices is recommended to be used with the LINX-101 configuration server or an L-IP configuration server. Please refer to the following sections on how to setup the device and the configuration server.
If the ―Auto member‖ feature is enabled in the configuration server, the CEA-852 device can add itself to the IP-852 channel without explicitly adding the device at the configuration server. Note, that enabling auto member is a potential security hole since any device can add itself to the IP-852 channel.
7.2.1 Configuration Server for Managing the IP-852 Channel
7.2.2 Overview
Every logical IP-852 channel requires one configuration server that manages all CEA-852 devices (LINX-121, L-IP, LOYTEC NIC852, i .
LON 1000, i .
LON 600, LonMaker, etc.) on
this channel. A simple example is shown in Figure 150. A configuration server keeps a list
of all devices on a logical IP-852 channel and distributes the routing information between those devices. If a device wants to join an IP-852 channel, it needs to register itself at the configuration server. Traditionally, a dedicated Windows PC is used to act as the configuration server. The L-INX contains an embedded configuration server and can therefore replace the PC.
The configuration server can be enabled in the L-INX in the CEA-852 server configuration
menu in Section 4.2.9. This configuration server can manage one IP-852 channel and up to
256 devices on this IP-852 channel. In order to setup the configuration server, one must specify the following parameters:
IP address/netmask/gateway (either via DHCP or manual entry), see Section 4.2.4
NAT address if used behind a firewall/NAT router, see Section 4.2.7
MD5 secret if authentication is required, see Section 4.2.7
Enable the configuration server, see Section 4.2.9 (server LED lights up green)
A list of IP-852 channel members, see Section 4.2.10.
Note: If the LINX-101 is used as a configuration server it needs a fixed IP address.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 186 LOYTEC
IP-852 Channel
IP: 192.168.1.100
Configuration
Server for
IP-852 Channel
IP: 192.168.1.101
IP: 192.168.1.102
Ethernet
IP: 192.168.1.1xx
CEA-852
Device
CEA-852
Device
CEA-852
Device
Figure 150: The configuration server manages the devices on an IP-852 channel.
7.2.3 Configuration Server Contacts IP-852 Device
In this scenario, the IP-852 device needs the following parameters set in order for the configuration server to contact the device. The remaining parameters are retrieved from the configuration server.
IP address/netmask/gateway (either via DHCP or manual entry), see Section 4.2.4
Auto-NAT or manual NAT address if used behind a firewall/NAT router, see Section
MD5 secret if authentication is required, see Section 4.2.7
If multiple CEA-852 devices behind one NAT router are added, the Auto-NAT setting in the L-INX is recommended to be used with the L-INX configuration server.
7.2.4 IP-852 Device Contacts Configuration Server
In this scenario, the IP-852 device needs the following parameters set in order to contact the configuration server. The remaining parameters are retrieved from the configuration server.
IP address/netmask/gateway (either via DHCP or manual entry), see Section 4.2.4
Auto-NAT or manual NAT address if used behind a firewall/NAT router, see Section
MD5 secret if authentication is required, see Section 4.2.7
Configuration server IP address and port number, see Section 4.2.7
If the ―Auto member‖ feature is enabled in the configuration server, the CEA-852 device can add itself to the IP-852 channel without explicitly adding the device at the configuration server. Note, that enabling auto member is a potential security hole since any device can add itself to the IP-852 channel.
7.2.5 Using the Built-In Configuration Server
For security purposes, the configuration server contacts each CEA-852 device on the IP-852 channel. Therefore, one must enter a list of all channel members in the CEA-852
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 187 LOYTEC
Configuration Server menu (see Section 4.2.10). This ensures that no unwanted device can
join the IP-852 channel. A properly configured IP-852 channel list can look like Figure 151.
List of channel members
=======================
No Name IP Address Status Flags
---------------------------------------------------------------------------
000 local 128.168.1.253:1628 registered
---------------------------------------------------------------------------
NAT Router 128.168.1.250
+ 001 lip-n1 10.0.2.2:1628 registered
+ 002 lip-n2 10.0.2.3:1631 registered
---------------------------------------------------------------------------
003 pc37 128.168.1.37:1628 not responding
---------------------------------------------------------------------------
Press <RETURN> to continue
Figure 151: Properly configured IP-852 channel with 4 channel members.
Note that also i .
LON 1000/600, VNI and LOYTEC NIC852 based network nodes (e.g.,
LonMaker or NL-220 applications) can join the IP-852 channel managed by the configuration server.
Note that the built-in configuration server should be used if LOYTEC CEA-852 devices are communicating across firewalls/NAT routers.
For adding multiple devices behind a NAT router, the configuration server supports the
extended NAT mode (see Section 7.3.2). The configuration server automatically switches
the channel mode to extended NAT if needed. Note that the i .
LON 600 must be configured with the i .
LON CS to extended NAT mode before adding the i .
LON 600 to the configuration server, because the i .
LON 600 does not switch to that mode automatically.
7.3 Firewall and NAT Router Configuration
The CEA-709 router can be used behind a firewall and/or NAT (Network Address
Translation) router as shown in Figure 152. Note, that in general, only one CEA-852 device
can be used behind the NAT router. This mode of operation is referred to as ―Standard‖ channel mode. It is fully compliant with CEA-852.
LOYTEC‘s newer devices such as the L-IP and the L-INX family support more than one
CEA-852 channel member behind a NAT router. This mode of operation is referred to as
―Extended NAT‖ channel mode. This mode introduces extensions to the standard mode which need to be supported by all members. Other devices supporting the extended NAT mode are the i .
LON
600. See Section 7.2.5 on compatibility with the
i .
LON 600.
7.3.1 Automatic NAT Configuration
In order to use the L-INX behind a firewall, the public NAT address and the local IP
address must be set in the IP configuration menu (see Section 4.2.4). By default, the NAT
address is determined automatically when adding the L-INX to the channel in the configuration server. Alternatively, the NAT address can be configured manually.
Furthermore, the NAT router must be configured to forward ports 1628 and 1629 for UDP
and TCP packets to the private IP address of the L-INX (192.168.1.100 in Figure 152). In
summary we can say, the following parameters must be set in order to operate a L-INX behind a NAT router.
Specify the IP address (private IP address: 192.168.1.100),
Specify the gateway address (e.g., 192.168.1.1),
Specify the NAT address (public IP address: 135.23.2.1) or use automatic NAT router discovery,
Enable port forwarding for ports 1628 and 1629 in the NAT router for TCP and UDP,
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 188
Enable the SNTP port 123 in the firewall if SNTP is used.
IP: 192.168.1.100
NAT: 135.23.2.1
LOYTEC
Firewall + NAT Router
135.23.2.1
IP Channel
192.168.1.1
Forward UDP and TCP ports 1628 and
1629 to IP address 192.168.1.100
Internet
Figure 152: Operating a L-INX behind a NAT router and firewall.
Note that a L-INX must be used as configuration server when the device is installed behind a firewall or NAT router. The L-INX with the configuration server can also be located behind a firewall.
7.3.2 Multiple IP-852 Devices behind a NAT: Extended NAT Mode
When using more than one IP-852 device behind a single NAT router, the recommended method in the L-INX configuration server is to use the extended NAT mode. This mode requires that all devices support this feature. Currently these are LINX-101, L-IP 3.0, i .
LON
600, the NIC852 PC software and other CEA-852 capable devices from LOYTEC. If there are other devices in the channel, this method does not work. Incompatible devices are
disabled from the channel in this case. Please refer to the classic method in Section 7.3.3 to
setup this network.
When using multiple devices behind a NAT router, each device needs a separate portforwarding rule in the NAT router. This implies that each device must use a unique client port (e.g., 1628, 1630, 1631, etc). The port-forwarding rules must be setup so that each port points to one of the IP-852 devices. In the LINX, change the client port in the CEA-852
device configuration menu. Figure 153 shows an example configuration for three L-INX
devices behind the NAT router 135.23.2.1.
It is recommended that both ports 1628 and 1629 are forwarded to the same private address.
It is then also possible to turn on the configuration server behind a NAT router. In this case, activate the CS on the L-INX which has port-forwarding to 1628 and 1629. In the example
in Figure 153, the L-INX with private address 192.168.1.100 also acts as a configuration
server.
If the CS is activated on a L-INX behind a NAT router, the NAT router must have a fixed public IP address. The L-INX with the CS also cannot use automatic NAT discovery. In this case, enter the NAT address of the NAT router manually in the IP configuration menu
(Auto-NAT can no longer be enabled on a L-INX with a CS). To diagnose possible problems in the NAT configuration with port forwarding, use the enhanced communications
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Internet
189 LOYTEC
IP: 192.168.1.100 : 1628
NAT: 135.23.2.1
Firewall + NAT Router
IP Channel
Optional: CS of the channel
IP: 192.168.1.102 : 1630
Auto-NAT (135.23.2.1) 135.23.2.1
192.168.1.1
Forward ports 1628 and 1629 to IP address 192.168.1.100, forward 1630 to IP address
192.168.1.102, forward 1631 to IP address
192.168.1.103
FT-10
IP: 192.168.1.103 : 1631
Auto-NAT (135.23.2.1)
FT-10
Figure 153: Multiple L-INX devices behind a NAT: Extended NAT Mode.
After the NAT router has been configured with the port-forwarding settings and the CS has been turned on, the channel members can be added. This can be done either on the console
UI or through the Web interface of the CS.
In the Web UI, add the members with their private IP addresses and the client ports as defined by the port-forwarding. Then select the added member by checking the check box and select the action Assign to NAT . Enter the public NAT address of the NAT router. An
example to add the two IP-852 devices in Figure 153 through the Web UI is depicted in
Figure 154. To remove a device from a NAT router but not delete it, select it and choose
Remove from NAT as the action.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 190 LOYTEC
Figure 154: Adding a member with extended NAT Mode on the Web UI.
7.3.3 Multiple IP-852 devices behind a NAT: Classic Method
If more than one CEA-852 device must be used behind the NAT router and there are
devices which do not support the extended NAT mode, we propose the setup from Figure
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Internet
191 LOYTEC
Firewall + NAT Router
IP Channel 1
IP: 192.168.1.100
NAT: 135.23.2.1
Configuration
Server for
IP Channel 1
135.23.2.1
192.168.1.1
Forward ports 1628 and 1629 to IP address 192.168.1.100
IP: 192.168.1.101
Configuration
Server for
IP Channel 2
TP-1250
High speed back-bone mode
IP: 192.168.1.102
FT-10
IP: 192.168.1.103
FT-10
Figure 155: Application that uses multiple L-INX devices behind a NAT router firewall.
The L-INX with IP address 192.168.1.100 is member of IP Channel 1 and can be accessed through the Internet. The L-INX devices with IP addresses 192.168.101 to 192.168.1.110 form another logical IP Channel 2 that communicates with the devices on the IP Channel 1 over the TP-1250 channel, which is used in high-speed backbone mode for optimum networking performance. Note that devices on both IP Channels 1 and 2 can of course connect to the same physical network wiring. Furthermore, both IP Channels 1 and 2 must have a separate configuration server that manages the L-INX devices on the different
channels. In the example in Figure 155, the L-INX with address 192.168.1.100 acts as the
configuration server for IP Channel 1 and the L-INX with IP address 192.168.1.101 acts as the configuration server for IP Channel 2.
7.4 Multi-Cast Configuration
IP multi-casting is a feature of the IP protocol that allows one packet to be delivered to a group of IP hosts. To receive such multi-cast packets, each IP host must be member of a multi-cast group. This group is identified by a multi-cast address (e.g., 225.0.0.37) and a
UDP port number.
The L-INX supports both unicast and multi-cast delivery of CEA-852 data packets. Using multi-cast is recommended when using the router in the Smart Switch Mode. For those devices, configure a multi-cast address in the IP configuration menu. Please contact your system administrator to obtain a valid multi-cast address for your network. Note, that all
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 192 LOYTEC channel members must be configured with the same multi-cast address and use the same client port (1628 is recommended). Also note, that multi-cast addresses cannot be routed on the Internet. They can only be used in a LAN or VPN environment.
If you configure multi-cast, there may be some devices, which do not support this feature. In this case, the device uses a hybrid scheme and sends unicast to those devices, which are not configured for multi-cast. Note, that the device determines automatically, when to switch to the multi-cast mode depending on what types of devices are in the channel and on the traffic burden for those devices. As a rule of thumb, multi-cast is used when there are only switches/repeaters in the channel and it is not used when there are only configured routers.
To detect if the device utilizes the multi-cast feature, contact the Extended CEA-852 device
statistics in the statistics menu (Section 4.2.15). The entry ―Channel Routing Mode‖ reads
SL (send list) if packets are routed to the multi-cast group. It reads CR (channel routing) if the normal unicast method is employed. Also the entry ―Multi-cast packets sent‖ in the
CEA-852 device statistics menu (Section 4.2.15) counts the number of multicast packets
transmitted to the group. If this item remains zero, no multi-cast is used by the device.
7.5 Remote LPA Operation
The L-INX supports remote LPA access. This means that a CEA-709 protocol analyzer connected to the Ethernet network can connect to the L-INX and record all packets on the
CEA-709 channel (FT-10). Our LPA-IP supports this sophisticated feature. The
functionality is shown in Figure 156.
The LPA-IP runs on a Windows PC that is connected to the Ethernet network. In a
LINX-101 device selection window, one can e.g. select the L-INX with IP address
192.168.1.210 and display all packets on the FT-10 channel connected to the L-INX with IP address 192.168.1.210. For this operation, the LPA-IP does not need to be a member of the
IP-852 channel. Note that this functionality is only available with L-INX Internet routers.
IP: 192.168.1.10
IP: 192.168.1.208
Configuration
Server for
IP-852 Channel
LPA-IP
Ethernet
IP: 192.168.1.209
IP: 192.168.1.210
Figure 156: Remote LPA principle.
7.5.1 Internet Timing Aspects
If the CEA-709 router is used over the Internet or in a large Intranet with unpredictable network delays, the user should become familiar with the following advanced timing aspects. Channel Timeout is set in the configuration server whereas escrowing and aggregation are set in the CEA-852 client device. The Channel Delay is a channel property of LNS and can be set in NL-220, LonMaker or other network management tools.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 193 LOYTEC
Table 12 summarizes the timing values that must be set when operating the device under
WAN conditions.
Timing Parameter Value
Channel Timeout
Escrowing (Packet
Reorder Timer)
Aggregation Timeout
(Packet Bunching)
Channel Delay in
LonMaker
Average ping delay + Aggregation Timeout
The smaller value of: 0.25*Channel Timeout or 64ms
Typically 16 ms
Average ping delay +10% + 2* Aggregation Timeout
Table 12: Advanced IP-852 timing parameters.
Please use a PC to determine the average ping delay between the different CEA-852 devices in the network. If multiple devices are communicating with each other always use the largest
measured average ping delay for the input value for the calculations in Table 12.
Escrowing should be disabled in a LAN (0 ms). The Channel Delay in LonMaker should be set to 2*Aggregation Timeout in a LAN if MD5 is disabled.
In LANs, Channel Timeout is only required if MD5 authentication is enabled. Set Channel
Timeout to 200 ms and Channel Delay to 20 ms.
7.5.2 Channel Timeout
The Channel Timeout is a property of the IP-852 channel. If a packet travels across this
IP-852 channel for longer than what is specified in Channel Timeout in ms, the packet is discarded. The device always needs to synchronize with an SNTP timeserver when a
Channel Timeout is set other than 0 ms.
Channel Timeout is highly recommended if MD5 authentication is enabled in order to prevent replay attacks. Set Channel Timeout to 200 ms and Channel Delay to 20 ms in a
LAN environment. Please refer to Section 4.2.9 on how to enable or disable the Channel
Timeout.
If an LNS based network management tool like LonMaker or NL220 is used on a network that has channel timeout enabled, please install an NTP client program (e.g., achron4.exe) on this PC that synchronizes the PC clock to the NTP time. Otherwise the PC clock and the clock inside the CEA-852 device will drift apart and communication between the PC and the device will terminate.
7.5.3 Channel Delay
Channel Delay is an LNS channel property that specifies the expected round-trip time of a message and its response. This value is used by LNS to adjust the protocol timers in the
CEA-709 nodes. Please consult the documentation for your network management tool about the Channel Delay details.
7.5.4 Escrowing Timer (Packet Reorder Timer)
The Escrowing Timer or Packet Reorder Timer is an IP-852 channel property that specifies the amount of time the device will wait for an out-of-sequence IP packet to arrive. This parameter is important in WANs like the Internet, where packets pass many routers that can change the order in which packets arrive at the destination node. The default value is 64 ms.
Do not use the Escrowing Timer in LANs since the packet order is always guaranteed in a
LAN. This will add unnecessary delays, which negatively impacts the performance of your
CEA-852 devices if a packet is lost or destroyed.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 194 LOYTEC
Whether enabled or disabled, out-of-sequence packets are never sent to the CEA-709
channel. Please refer to Section 4.2.7 on how to enable or disable escrowing.
7.5.5 SNTP Time Server
Small IP networks like LANs have a small propagation delay for packets traveling in these networks. In this case it is not necessary to specify an SNTP server.
In larger IP-852 networks like the Internet with possibly long packet delays, one must specify an SNTP server to synchronize the local clocks of the CEA-852 devices. The local clocks must be synchronized to a common notion of time in order to make CEA-852 protocol features like Escrowing (Channel Timeout) work properly.
The SNTP timeserver can be specified on the IP-852 channel level in the configuration server, which distributes the timeserver address to all CEA-852 devices on the IP-852 channel.
A primary and a secondary SNTP server can be defined please refer to Section 4.2.7 and
Section 4.2.9 on how to enable the SNTP server.
7.6 Advanced Topics
7.6.1 Aggregation
Aggregation (or packet bunching) is a technique that collects multiple CEA-709 packets into a single larger IP packet. Aggregation improves overall system performance since one
IP-852 packets, now carries multiple CEA-709 packets und with the same number of IP-852 transactions, more CEA-709 packets can be exchanged between CEA-852 devices thus reducing protocol overhead. The Aggregation Timeout defines the time period in ms in which the transmitting device collects the CEA-709 packets before it transmits the CEA-852
packet over the IP-852 channel. Please refer to Section 4.2.7 on how to enable aggregation.
Note, that aggregation adds a delay to the transactions but dramatically improves the throughput of your IP-852 channel. Use aggregation if you have a high channel load but can tolerate some additional propagation delay given by the aggregation time value.
7.6.2 MD5 Authentication
MD5 authentication is a method of verifying the authenticity of the sending device. Only devices that have MD5 enabled and use the same MD5 secret can share information with each other. If the configuration server has MD5 enabled, only devices that have MD5 enabled and use the same MD5 secret as the configuration server can join the logical IP-852
channel. Please refer to Section 4.2.7 and 4.2.9 for details.
7.6.3 Dynamic NAT Addresses
A common practice for Internet providers is to assign addresses on a per-session basis to a client. Each time a connection is established (e.g., an ADSL link is set up), the Internet provider may choose an IP address from a pool. Since this address will be the public address of a NAT router, the NAT address configured in the device would need to be updated. The Auto-NAT feature in the device permanently monitors the current NAT address. When the device detects a change in the NAT address it re-registers with the configuration server using this new address. This feature requires a LOYTEC configuration server (e.g., LINX-101, L-IP) and ―Roaming Members‖ enabled on that CS.
Version 4.0
A consequence of this monitoring process is that the device contacts the CS every 45 seconds to probe for the NAT address. This causes a small amount of additional traffic on the Internet link. The Auto-NAT feature also causes any shut-down connection to be reestablished. The NAT monitoring functions as a keep-alive for the connection. If neither the additional traffic nor the automatic initiation of a new connection is tolerable, the Auto-
LOYTEC electronics GmbH
L-INX User Manual 195 LOYTEC
NAT feature must be disabled and the NAT address configured manually. In this case, the
Internet service provider needs to assign a fixed public IP address to the NAT router.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 196
8 The LINX-100 RNI
LOYTEC
8.1 RNI Function
The CEA-709 L-INX devices without the router provide a remote network interface (RNI) function, if the device is configured to use the FT interface (FT mode). In this mode the device provides a remote network interface, which appears like a LOYTEC NIC-IP it is intended to be used together with the LOYTEC NIC software. The RNI can be utilized for remote access and configuration as well as trouble-shooting with the remote LPA.
In particular, the RNI appears as a regular LOYTEC network interface on the PC. The
LOYTEC NIC software needs to be installed to utilize this interface also in LNS-based applications such as NL-220 or LonMaker. Using this software, the L-INX can act as a direct interface to its local FT channel to be managed by LNS or similar tools. For more information on how to configure the LOYTEC NIC software on the PC, please refer to the
LOYTEC NIC User Manual [3].
8.2 Remote LPA Operation
The L-INX supports remote LPA access through its RNI. This means that a CEA-709 protocol analyzer connected to the Ethernet network can connect to the L-INX and record all packets on the CEA-709 channel (FT-10). The LOYTEC LPA-IP supports this advanced
feature. The functionality is shown in Figure 157.
The LPA-IP runs on a Windows PC that is connected to the Ethernet network. In the
NIC-IP/RNI device selection window, one can for example select the L-INX with IP address 192.168.1.210 and display all packets on the FT-10 channel connected to the L-
INX with IP address 192.168.1.210. Please consult our product literature for the LPA-IP to learn more about this IP-based CEA-709 protocol analyzer.
IP: 192.168.1.210
IP: 192.168.1.10
Version 4.0
LPA-IP
Ethernet
Figure 157: Remote LPA on the L-INX.
LOYTEC electronics GmbH
L-INX User Manual
9 OPC Server
197 LOYTEC
9.1 XML-DA OPC Server
9.1.1 Access Methods
LOYTEC devices with the built-in OPC server can expose data points over a Web service.
The OPC tag namespace is built from the data point hierarchy, which has been configured by the Configurator software. The OPC server on the device implements the data access standard via the Web service interface XML-DA. The OPC XML-DA Web service is accessible via the URI http://192.168.24.100/DA where the IP address has to be replaced with the actual IP address of the device. The Web service is accessible over the same TCP port as the Web server. The default TCP port is 80.
The Web server port can only be changed via the device configuration tab in the
Configurator (see Section 6.3.6) or in the L-Config tool (see NIC User Manual [3]).
Since the Web service is easily routable on the Internet, the embedded OPC server implements the basic authentication method to protect the system from unauthorized access.
The basic authentication involves the operator user and the password configured for this
user. On how to configure the operator‘s password, please refer to Section 4.1. To disable
the basic authentication, clear the operator‘s password.
On the LINX-12x, 15x, 22x models, the anonymous OPC access must be enabled. For doing so, change to the port configuration on the Web UI, select the OPC protocol on the
Ethernet tab and check the anonymous OPC box.
Note: It is highly recommended to use basic authentication when exposing crucial data points over the Web service.
To use the exposed OPC data points, there exist several possibilities:
Use LOYTEC‘s L-WEB visualization tool that comes free with the device,
use a standard OPC client or SCADA package, or
create your own Web service client with custom Web Pages.
The easiest way to visualize the network‘s data points over a Web-based interface using the device is the L-WEB software. This software is fully integrated into the Configurator and allows designing graphical page content. The tool is intuitive to use like the L-VIS graphical page designer. The resulting L-WEB application is stored on the device and can be directly
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 198 LOYTEC accessed in your Web browser or other Internet appliances, such as PDAs. For more
information on the L-WEB refer to Section 9.2.
Standard OPC clients and SCADA packages, which shall visualize the device‘s data points, must conform to the OPC XML-DA standard. This means they must support the OPC Web service and not only the COM/DCOM protocol. If your SCADA package does not support
OPC XML-DA, a PC-based bridge from XML-DA to the COM-based protocol can be used.
The bridge software is running on a PC and translates from COM/DCOM requests into
XML-DA Web service requests. The system is depicted in Figure 158.
Figure 158: Using a XML-DA/DCOM bridge.
With the bridge is configured to access a number of devices, the COM-based SCADA application can access a COM-based OPC server for each of those devices. The bridge software OPCBR-800 can be purchased and installed on any PC. This is discussed in
If L-WEB is not used, customers can create their own XML-DA clients based on the WSDL
for OPC XML-DA. Refer to Section 9.4 for more information.
9.1.2 Data Points
The data point hierarchy as configured by the Configurator software is exposed to the OPC tag namespace by the device. This is done internally for all data points, which are marked for OPC exposure (i.e., have the OPC check-mark set).
Folders are translated into OPC nodes. Any of the data point classes, analog, binary, multistate, string, and user, are exposed as OPC tags. Each OPC tag contains the value of the data point and some of its meta-data. An example of browsing the OPC tags on the LINX-
The OPC quality property of a given OPC tag is coupled to the data point status. If a data point is offline or unreliable, the OPC quality property changes to uncertain .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 199 LOYTEC
Figure 159: Client browsing the OPC tag namespace on a LINX-101.
9.1.2.1 Analog
Analog data points are exposed as a one-to-one mapping to OPC tags. For each analog data point, an OPC tag is created. The OPC tag contains a number of OPC properties, which are derived from the data point‘s properties:
Item Canonical Data Type (SmallInt): This property indicates the data type ‗5‘
(Double).
Item Value (Double): The present data point value.
Item Quality (SmallInt): The value quality. It is ―good‖ if the data point is in normal state, or ―uncertain‖ if the data point has an off-normal state, e.g., offline or unreliable.
Item Timestamp (Date): This property contains the timestamp of the last value update.
Item Access Rights (Integer): This property defines whether the tag is read-only or read/write.
Item Description (String): This is the description of the data point.
Item EU Type (Integer): This property is ‗1‘.
High EU (Double): This is the analog maximum value of the data point.
Low EU (Double): This is the analog minimum value of the data point.
EU Units (String): This is the human-readable engineering units text of the data point.
9.1.2.2 Binary
Binary data points are exposed as a one-to-one mapping to OPC tags. For each binary data point, an OPC tag is created. The OPC tag contains a number of OPC properties, which are derived from the data point‘s properties:
Item Canonical Data Type (SmallInt): This property indicates the data type ‗11‘
(Boolean).
Item Value (Boolean): The present data point value.
Item Quality (SmallInt): The value quality. It is ―good‖ if the data point is in normal state, or ―uncertain‖ if the data point has an off-normal state, e.g., offline or unreliable.
Item Timestamp (Date): This property contains the timestamp of the last value update.
Item Access Rights (Integer): This property defines whether the tag is read-only or read/write.
Item Description (String): This is the description of the data point.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 200 LOYTEC
Contact Close Label (String): This property contains the active text of the binary data point.
Contact Close Label (String): This property contains the inactive text of the binary data point.
9.1.2.3 Multi-state
Multi-state data points are exposed as a one-to-one mapping to OPC tags. For each multistate data point an OPC tag is created. The OPC tag contains a number of OPC properties, which are derived from the data point‘s properties:
Item Canonical Data Type (SmallInt): This property indicates the data type ‗3‘
(Integer).
Item Value (Integer): The present data point value.
Item Quality (SmallInt): The value quality. It is ―good‖ if the data point is in normal state, or ―uncertain‖ if the data point has an off-normal state, e.g., offline or unreliable.
Item Timestamp (Date): This property contains the timestamp of the last value update.
Item Access Rights (Integer): This property defines whether the tag is read-only or read/write.
Item Description (String): This is the description of the data point.
Item EU Type (Integer): This property is ‗2‘ for multi-state.
Enumerated EU (Array of String): This property contains the state texts of the data point.
9.1.2.4 User Type
User-type data points contain a byte array of user-defined data. Data points of user-type are also exposed as a one-to-one mapping to OPC tags. For each such data point, an OPC tag is created. The item value of the user-defined data is a hex string without whitespace representing the byte array, e.g., ―B034‖. The OPC tag contains a number of OPC properties, which are derived from the data point‘s properties:
Item Canonical Data Type (SmallInt): This property indicates the data type ‗8‘ (String).
Item Value (String): A hex string without whitespace representing the byte array.
Item Quality (SmallInt): The value quality. It is ―good‖ if the data point is in normal state, or ―uncertain‖ if the data point has an off-normal state, e.g., offline or unreliable.
Item Timestamp (Date): This property contains the timestamp of the last value update.
Item Access Rights (Integer): This property defines whether the tag is read-only or read/write.
Item Description (String): This is the description of the data point.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 201 LOYTEC
9.1.2.5 Structured Data Points
Structured data points are modeled as one user-type data point, which contains the entire structure value as a byte array. The respective structure fields are created as sub-data points of appropriate class. For example, a SNVT_switch in CEA-709 would be modeled as one user-type data point of 2 bytes length, and two sub-data points, one an analog (value member) and one a multi-state (state member).
The relation between user-type data point and sub-data points is also exposed to OPC. In this case, an OPC node is created for the user-type data point. In that node, the sub-data points are exposed as OPC tags. The entire structure is also exposed as a user-type OPC tag under the same OPC node.
Important! Deselect any un-used structure members from OPC exposure to reduce the number of total OPC tags.
It is important to note, that when using structured data points the top-level and all its structure members are exposed as OPC tags by default. Using many structured data points may lead to exceeding the OPC tag limit. Please observe this limit in the Configurator‘s statistics tab and deselect the OPC Tag check box for unwanted structure members. This helps to keep your configuration lean and improves the performance of the OPC server when browsing and subscribing.
9.1.3 AST Objects
The alarming, scheduling, and trending (AST) objects are more complex than regular data points. The OPC XML-DA standard does not have appropriate tags for those objects.
Therefore, the device exposes AST objects as a set of OPC tags describing the object. All tags for one AST object are collected under an OPC node representing the AST object.
9.1.3.1 Scheduler Object
The device exposes the scheduler objects to OPC XML-DA tags. Each scheduler object is represented by a node in the OPC name space. The content of the schedule XML document referred to in this section must be compliant to the scheduleCfg schema. This schema can be found at the LOYTEC Web site. The XML documents can refer to the target namespace
‗http://www.loytec.com/xsd/scheduleCfg/1.0/‘.
In that node, the following OPC tags are available:
ServiceType (string, Read-only, const): This is a constant tag of type string, which contains ―schedule‖. It identifies this folder as a schedule folder. This can be used as an additional identification to the vendor-specific property of the folder tag.
Schedule (string, read/write): This tag configures the schedule. The data type is string and the format is in XML. The XML document contains the scheduleCfg element as the root element.
Caps (string, read-only): This tag contains the schedule capabilities. The data type is string and the format is in XML. The XML document contains the scheduleCapabilities element as the root element.
CalItemPath (string, Read-only, const): This is an optional tag. If present, it contains the item path to the calendar object, that the schedule references. To read the calendar referenced by the schedule, use this item path and the ―Calendar‖ item name to read the calendar XML document.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 202 LOYTEC
EmbeddedCal (node): This is an optional OPC node. If present, it contains the OPC tags for the embedded calendar. The embedded calendar structure is as defined for
calendar objects in Section 9.1.3.2.
9.1.3.2 Calendar Object
The device exposes the calendar objects to OPC XML-DA tags. Each calendar object is represented by a folder in the OPC name space. In that folder, the following OPC tags shall be available:
ServiceType (string, Read-only, const): This is a constant tag of type string, which contains ―calendar‖. It identifies this folder as a calendar folder. This can be used as an additional identification to the vendor-specific property of the folder tag.
Calendar (string, read/write): This tag configures the calendar. The data type is string and the format is in XML. This document contains the calendarCfg element as the root element.
Caps (string, read-only): This tag contains the calendar capabilities. The data type is string and the format is in XML. The XML document contains the calendarCapabilities element as the root element.
9.1.3.3 Alarm Objects
The alarm objects on the device provide the alarm summary and can be used to acknowledge alarms. The alarm objects are exposed to XML-DA tags. Each alarm is uniquely identified by an XML alarm ID (XAID). The XAID must identify the alarm object and the alarm ID in that object. The XAID is used in the acknowledge service to identify the alarm. The XAID can also be transmitted in e-mail notifications.
Each alarm object is represented by a folder in the OPC name space. In that folder, the following OPC tags shall be available:
ServiceType (string, Read-only, const): This is a constant tag of type string, which contains ―alarm‖. It identifies this folder as an alarm folder. This can be used as an additional identification to the vendor-specific property of the folder tag.
Summary (string, Read-only): Reading from this tag, the current alarm summary can be obtained. The data type is string and the tag contains an XML document. This tag should not be subscribed to as it contains a large document. Subscribe to NotifyCnt instead, to get notified about new alarms. The root element of the XML document is the alarmSummary element.
NotifyCnt (unsigned, Read-only): This tag is updated with an incremented notify count for each alarm update notification. This is the case for new or cleared alarm conditions, and for acknowledged alarms. Clients can subscribe to this tag in order to be notified about changes in the alarm summary. The client has then to read the complete alarm summary when notifications occur.
NotifyNewCnt (unsigned, Read-only): This tag is updated with an incremented notify count each time a new alarm appears. This tag does not update when alarms are acknowledged or go inactive.
Ack (string, Write): Writing to this tag acknowledges an alarm. The data type is string.
The written data is an XML document, which contains the alarmAck element. The write must specify the XAID.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 203 LOYTEC
9.1.3.4 Trend Log Objects
Each trend log object on the device is represented by a folder in the OPC name space. This folder contains a number of tags describing and controlling the trend log. To retrieve log records, however, the XML-DA tag interface cannot be used. There are two options: retrieve the complete log as a CSV file, or use the LOYTEC proprietary Data Log Web service (XML-DL). That Web service uses the logHandle provided by a tag. The CSV file location can be obtained from a tag also.
ServiceType (string, Read-only, const): This is a constant tag of type string, which contains ―trendLog‖, or ―alarmLog‖. It identifies this folder as a trend log, data log or alarm log folder. This can be used as an additional identification to the vendor-specific property of the node tag.
Purge (Boolean, read/write): When writing TRUE to this tag, the log is purged.
TotalCnt (unsignedInt, read-only): This tag contains the total number of logged records. This number can be larger than the BufferSize.
BufferSize (unsignedInt, read/write): The size in records of the log buffer. Writing to this tag can resize the log buffer, if it is disabled.
LogHandle (string, read-only, const): This handle specifies the data log. The logHandle must be used with the proprietary Data Log Web service.
CsvFile (string, read-only, const): This tag specifies the file path and file name of the
CSV data log file.
CentralDL0, CentralDL1 (string, read/write): These tags serve as placeholders for the central data logger to store its URI. The tag CentralDL0 is intended for the primary,
CentralDL1 for the secondary central data logger. The tags are stores in non-volatile memory and retain their values over a power-on reset. For more information on the central data logger refer to the LWEB-801 User Manual [5].
9.1.3.5 E-mail Templates
E-mail templates can be configured in the Configurator software. When an e-mail template is triggered, the corresponding e-mail is transmitted. The e-mail template can also be triggered over the OPC interface. Therefore, a node is added to the OPC name space for each e-mail template under the ―E_Mail‖ node.
Each e-mail node is named after the e-mail template and contains the following OPC tags:
ServiceType (string, Read-only, const): This is a constant tag of type string, which contains ―email‖. It identifies this folder as an e-mail template folder.
Send (Boolean, read/write): When writing TRUE to this tag, the e-mail transmission is triggered.
9.2 Using L-WEB
Version 4.0
The L-WEB is a Web-based visualization software that comes free with the device. It uses the standard Web technologies to visualize and control data provided by one or more
L-INX Automation Servers on a Windows PC.
The L-WEB software uses the standardized OPC XML-DA Web service to communicate between L-WEB and remote L-INX Automation Servers, which makes it extremely firewall-friendly and easy to setup.
LOYTEC electronics GmbH
L-INX User Manual 204 LOYTEC
The graphical design of the L-WEB user interface consists of pages, which can simply be created by using the L-VIS/L-WEB Configurator software without any know-how in
HTML, Java, etc. Dynamic information is shown in the form of numeric values, text, changing icons, bar graphs, trend logs, alarm and event lists, or schedule controls.
The complete set of automation functions of the L-INX Automation Server is fully supported by L-WEB. The automation services are residing in the embedded devices and are distributed over the network to build up a dependable system with L-WEB only accessing these services. Furthermore, any kind of calculations, data point connections, etc., are implemented on the embedded Automation Server, which makes the application on the
Automation Server completely independent from the connection to the L-WEB application.
Starting from the data point configuration, the user can create an L-WEB project. The
L-WEB project contains the data point configuration of the Web service interface and a graphical design for the L-WEB user interface. For more information on creating graphical designs using the L-VIS/L-WEB Configurator software refer to the L-VIS User Manual [5].
9.2.1 Create a new L-WEB Project
The Configurator provides the data point configuration, which is downloaded to the device.
On top of that configuration, an L-WEB design can be created for visualization.
To Create an L-WEB Project
1.
Start the Configurator software and change to the L-WEB Projects tab.
2.
The L-WEB project tab appears as in Figure 160.
Version 4.0
Figure 160: L-WEB Projects Tab.
LOYTEC electronics GmbH
L-INX User Manual
3.
Click on Add New …
4.
Enter a new Project Name .
205 LOYTEC
5.
Click on Create . The new project appears in the projects list.
9.2.2 Start a Graphical L-WEB Design
The L-WEB graphical design tool is started from within the L-WEB projects tab. The graphical design for the L-WEB project is created in the L-VIS design tool (L-VIS/L-WEB
Configurator). The data point configuration created in the Configurator project is available for the L-WEB project and its graphical design.
To Start a Graphical Design
1.
Select the L-WEB Projects tab.
2.
Select an L-WEB project.
3.
Click Edit .
4.
This opens the L-VIS graphical design tool. Complete the graphical design in the tool and click the Write Project to Device speed button
5.
The graphical design is now part of the project.
Note: If the Configurator had been connected to the device, the graphical design would have been added to the device in the same step.
9.2.3 Organize L-WEB Projects
L-WEB projects can be organized within the L-INX configuration project. L-WEB projects can be part of the configuration project and/or stored on the device. For instance, the configuration project may contain a number of L-WEB projects, but for saving space on the device, only one of them is downloaded on the device. The L-WEB projects tab provides a number of tools to organize a set of L-WEB projects.
To Organize L-WEB Projects
1.
Connect to the device as described in Section 6.6.1.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 206 LOYTEC
2.
Select the L-WEB Projects tab.
3.
Click Detect Projects on Device . This scans for all projects found on the device.
Projects marked as a green Yes in the In LINX Project column are L-WEB projects, which are part of the current L-INX configuration project. Projects marked as a green
Yes in the On Device column are L-WEB projects, which are also stored on the device.
A red No identifies the L-WEB project to be missing in the project or on the device, respectively.
4.
If you want to download an L-WEB project to the device, which is missing there, select the project and click Download . After the download the project appears with a green
Yes in On Device .
5.
If you want to remove a project from the device, click Remove in the LINX Device box .
6.
If you want to remove the project from the current L-INX project file, click Remove in the L-WEB Projects on PC box.
7.
If you want to export the L-WEB project into a separate L-WEB project file, click
Export… and select a file name in the file requestor dialog.
If you want to import an L-WEB project from a separate L-WEB project file, click
Import… and select the file in the file requestor dialog. The L-WEB project appears in the project but not on the device.
9.3 Using the OPC Bridge
9.3.1 Software Installation
The LOYTEC OPC Bridge software LOPC-BR800 is installed as a separate application on a PC. A license for the LOYTEC OPC Bridge software must be purchased separately. With one software license for the OPC Bridge, multiple L-INX devices can be accessed. With the
OPC Bridge software installed, each configured LOYTEC L-INX device appears as a separate COM/DCOM server. The OPC Bridge software can be used with LOYTEC L-INX
OPC servers only. The bridge won‘t connect to third-party OPC servers.
System requirements:
Windows XP, Windows 2003 Server, Windows Vista, Windows 7, or Windows 2008
Server.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 207 LOYTEC
The OPC Bridge software is available on the LOYTEC Software CD or via download from the LOYTEC Web site www.loytec.com. For installing the software, a registration code must be purchased.
To Install the OPC Bridge
1.
Double click on ‗lopc-br800_1_0_setup.exe‘ and follow the installation steps.
2.
When asked, type in the bridge‘s registration code. Click Next .
3.
Finalize all remaining installation steps by clicking Next and Finish .
When the installation is complete, the OPC Bridge software is available under Programs
LOYTEC OPC Bridge .
9.3.2 Configure the Bridge Locally
If the bridge software is installed on the same PC where the Configurator software is used to configure the L-INX OPC server, the server information can be automatically made available as a COM OPC server. This is done when the L-INX configuration is downloaded into the device.
To Configure the Bridge Locally
1.
Open the Configurator software and configure the device as described in Section 6.6.
2.
In the Configurator menu go to Settings
Project settings … . This opens the project settings dialog on the tab General
Figure 161: Enable bridge export in the project settings.
3.
Put a check mark on Automatically add downloaded device to the OPC bridge .
4.
Click OK.
5.
Downloading the configuration also makes the OPC server on the device available as a
COM OPC server through the local bridge.
9.3.3 Export OPC Servers for another PC
If the bridge software is not installed locally on the same PC where the L-INX configuration is created, it must be exported to make the OPC server information available. The exported file can then be transferred to the OPC bridge.
To Export the Bridge Configuration
1.
Open the Configurator.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 208 LOYTEC
2.
Connect to the device, which shall be available in the bridge.
3.
Select the menu File
Export to OPC Bridge Configuration...
.
4.
In the OPC Bridge Device Properties
dialog as shown in Figure 162, add information
which is not default, i.e., Min update rate, Wait time and Hold Time (see Section
9.3.6). If the operator user has a non-default password, enter the password.
5.
Click Export to File .
Figure 162: Bridge Export dialog.
9.3.4 Import OPC Servers Using the Configurator
When using OPC server information exported by the Configurator, the exported server definition must be imported to the OPC bridge. This can also be done using the
Configurator software. The Configurator software must be installed on the same PC as the
OPC bridge for doing so.
To Import a Server Definition
1.
Open the Configurator software.
2.
Select the menu File
Import OPC Bridge Configuration...
.
3.
In the file requestor select the bridge configuration XML file, which has previously been exported and click OK .
4.
The OPC Bridge Device Properties dialog displays the imported bridge information.
5.
Click Export to Bridge to add the respective COM server to the bridge.
6.
Click Save .
9.3.5 Manually Configure Servers
The OPC bridge configuration can also be edited manually. The same procedure is also applicable to verify imported OPC server definitions in the bridge software. After adding a server definition in the bridge software, the device‘s OPC server will be available as a COM
OPC server through the bridge.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 209 LOYTEC
To Configure a Server in the Bridge
1.
Start the OPC bridge from the Windows Start menu under Programs
LOYTEC OPC
Bridge
OPC Bridge manual Setup.
2.
In the system tray, right-click on the bridge icon .
3.
In the context menu select Register new Server .
4.
In the Register Server dialog click Add .
5.
A new server entry is added. Enter the information on Server caption (this is displayed), Server name (this is the COM object name), and the Server URL (the
URL of the LOYTEC device) as shown in Figure 163.
Figure 163: Register Server dialog in the bridge software.
6.
Additionally, enter the ―operator‖ as the User name and its Password on the device.
Enter the default timing parameters (min update rate 3 sec, wait time 10 sec, hold time
0). For information on the timing parameters refer to Section 9.3.6.
7.
To test the connection to the device, press the button .
8.
Click OK .
9.3.6 Bridge Timing Parameters
The OPC bridge uses three timing parameters to operate on the OPC XML-DA side. The defaults for those parameters are good for most cases. For specific use cases, however, they might need to be adapted.
Minimum Update Rate : This parameter defines the rate at which the LOYTEC OPC server will update its value caches. In general value changes could occur much more frequently than the value caches are updated. Therefore, the minimum update rate determines the granularity at which updates may be notified to the OPC client. If an
OPC client specifies an update rate less than this value for a group of subscribed data
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 210 LOYTEC points, the group will not be updated faster. If the group specifies a slower update rate, however, the device will be polled less often. Lowering this parameter gives better responsiveness to data changes but also increases the XML-DA traffic and impacts overall performance. The recommended default is 3 seconds.
Wait Time : This parameter specifies how long the OPC bridge shall wait for value updates before issuing the next polled refresh to the LINX. This time can be higher than the update rate because changes are notified within the wait time as soon as they occur on the device. The recommended default is 10 seconds.
Hold Time : This parameter specifies that changes will be held back by the OPC server for the given amount of time before they are notified to the client. Normally, changes in the server are notified at the update rate‘s granularity. In rare cases this can be used to hold back changes beyond the update rate. The recommended default is 0.
9.4 Using Custom Web Pages
Custom Web pages can also be developed for the LINX. For doing so, the applications engineer must implement an OPC XML-DA Web service client, which adheres to the
WSDL interface. This can be done in C++ or script languages such as Perl. The WSDL must be obtained from the OPC Foundation‘s Web site following the OPC XML-DA namespace http://opcfoundation.org/webservices/xmlda/1.0/ .
Any Web content, including scripts, applications or static Web pages can be stored directly on the LINX-20X‘s file system. Use the admin account to upload the content via FTP into the directory
/var/www
For example, a page named ‗my_page.html‘ put directly into ‗/var/www‘ can be accessed via ‗http://192.168.24.100/my_page.html‘, given that the IP address is correct.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
10 M-Bus
211 LOYTEC
10.1 Introduction
The M-Bus (Meter-Bus) is a European standard (EN 13757-2, EN 13757-3) designed for remote reading of meters. With its standardization as a galvanic interface for remote readout of heat, water, and energy meters, this bus has become an important interface for automatic meter reading applications with different vendor‘s meters on the same cable.
The M-Bus is a serial bus, which is controlled by a single bus master. This master can request data from several slave devices connected to the network. The data transmission from master to slave is done by a modulation of the output voltage (36 V means a logical
‗1‘, 24 V means logical ‗0‘). During data transmission from slave to master the current is modulated (1.5 mA represent the logical ‗1‘, 11-20 mA represent a logical ‗0‘). M-bus devices can be powered over the bus. The number of devices which can be powered depends on the M-Bus transceiver used.
10.2 Hardware Installation
For using the M-Bus with the device an external M-bus interface with an RS-232 connector is required. The external interface must be connected to the LOYTEC device either via the serial connector or the extension port EXT. The M-Bus functionality must be enabled on the device itself.
10.2.1 Console Connector
When using the serial console connector, the M-Bus interface is enabled on the device by setting DIP-switch 7 to ON. This disables the console of the device and activates M-Bus over the console connector. After the device is rebooted, the M-Bus is active on the device.
When rebooting the device with M-Bus activated and the console connected, a couple of boot messages are displayed in the console, before the console is turned off.
If the console is needed again, set the DIP switch 7 to OFF and reboot the device. This is required, if the firmware shall be updated over the serial port using the LSU tool.
When using the L-MBUS coupler, connect the L-MBUS to the device‘s console connector
via a Null modem cable (female to female sub-D connector) as shown in Figure 164. On the
L-MBUS remove the jumper as indicated on the front label.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 212 LOYTEC
Figure 164: Connecting L-MBUS over console connector.
10.2.2 Extension Port
Devices that do not have a serial console connector provide an extension port marked EXT
on the device as shown in Figure 165. Those devices need to use the L-MBUS converter.
On the L-MBUS set the jumper as indicated on the front label. Follow the cabling
instructions of Figure 165 between the
EXT port of the L-INX and the PORT1 on the
L-MBUS.
Figure 165: Connecting L-MBUS over the extension port.
10.3 M-Bus Network
The M-Bus network utilizes a two-wire connection. Several M-Bus slave devices are connected in parallel to the transmission medium. Each M-bus device has a primary address in the range from 0 to 250. This primary address must be unique for each device. Also a secondary address can be used for the slave devices. The secondary addressing mode is
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 213 LOYTEC currently not supported by the LOYTEC device. The M-Bus network also supports two kinds of broadcast messages. A broadcast to address 255 does not force the slaves to give a response. A broadcast to address 254 forces an answer from the slave. This broadcast message is mainly used for peer-to-peer connections.
The M-Bus allows the use of devices with different Baud rates of up to 9600 Baud. M-Bus devices are not always able to fulfill the complete functional specification of the M-Bus standard. For readout two different modes are known (some slave devices implement both):
A default read usually reads all the data of a device.
A selective read selects the data points, which are to be read.
Some devices also support writing special data points.
Some M-Bus devices support a synchronized action. This means that when a device receives such a synchronize command, it stores specific data points for later readout. This way, specific information of even a larger number of devices can be read out in a synchronized manner.
M-Bus supports network management functions such as changing the primary address of a device, changing the Baud rate of a device, reading all data from a device as well as pinging a device. It is therefore possible to scan M-Bus devices in an M-Bus network.
M-Bus data points are specified by a DIF/DIFE and VIF/VIFE combination. The DIF/DIFE
(data information field and data information field extension) specify storage number, tariff, subunit as well as the data coding (BCD, int, etc.) and the function (min, max, etc.) of the data point. The DIF/DIFE can be up to 11 bytes long (1 byte for the DIF and up to 10 extensions). The VIF/VIFE combination (value information field and value information field extension) specifies the type of the data point (e.g. energy count value) and how it is presented (e.g., the value is given in ―Wh‖). Like the DIF/DIFE, the VIF/VIFE can consist of one VIF and up to 10 VIF extensions. The Configurator allows the configuration by either entering the DIF/DIFE combination or by specifying the appropriate numbers.
10.4 Web Interface
This section describes the Web interface for the M-Bus port.
10.4.1 Configuration
A configuration of the M-Bus port is not necessary, as no parameters are required for the
M-Bus.
10.4.2 Data Points
M-Bus data points can be accessed through the Web UI as described in Section 4.2.15.
10.4.3 Statistics
Figure 166 shows a typical output of the statistics information which can be displayed for
the M-Bus port.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 214 LOYTEC
Figure 166: Statistics of the M-Bus port.
The following information is available:
Rx bytes: number of bytes received
Tx bytes: number of bytes sent
Tx total: total number of transmissions
Tx errors: number of errors during a transmission
Tx no response: number of transmissions without a response
Tx dropped: number of dropped transmissions (in case of an error, device responses or transmissions can be dropped)
Tx repetitions: number repeated messages
Tx successful: number of successful transmissions
Devices online: number of devices which are currently online
10.4.4 M-Bus Protocol Analyzer
By activating the link Protocol Analyzer (available in the M-Bus statistics tab), the protocol
analyzer page is shown as displayed in Figure 167.
Version 4.0
Figure 167: M-Bus protocol analyzer.
LOYTEC electronics GmbH
L-INX User Manual 215 LOYTEC
Next to the button the status of the protocol analyzer is shown. If the analyzer is started, an automatic refresh is performed every 60 seconds. By pressing the button Start Protocol
Analyzer / Stop Protocol Analyzer the protocol analyzer can be started / stopped.
For every frame sent or received a line is presented using comma separated values.
10.5 Configurator
This section describes how to use the Configurator software for the management of M-Bus
data points. For further information on the Configurator software refer to Chapter 6.
10.5.1 Activating M-Bus Configuration
Before a new M-Bus configuration can be managed, the M-Bus option must be enabled.
The project settings are described in detail in Section 6.3.
To Activate the M-Bus Configuration
1.
Open the project settings dialog.
2.
In the Device Configuration tab enable the M-Bus check box.
3.
Press the OK button.
Important: If the M-Bus Port is deactivated via the checkbox or a firmware or model version is chosen, which does not support M-Bus, the complete M-Bus configuration is deleted. In this case a dialog is displayed, which has to be confirmed.
10.5.2 Data Point Manager for M-Bus
The Configurator uses a central concept to manage data points. The data point manager is used to select, create, edit and delete data points. The dialog is divided into three sections:
The data point list (Figure 169),
And a property view.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 216 LOYTEC
Figure 168: Data Point Manager Dialog with M-Bus folder list
Figure 169: Datapoint Manager Dialog with M-Bus Data Point List.
10.5.3 Folder List
At the left is a list of folders which is used to sort the available data objects by their category. There are a number of predefined M-Bus folders available. All other folders are
Imported : This folder has a number of sub-folders for different import methods: o M-Bus Network Scan : This folder holds data points scanned online from an attached M-Bus network. When scanning an M-Bus device, a subfolder is created under M-Bus Network Scan. The name of this subfolder is generated automatically from the information of the scanned device. Additionally under the device sub-folder a data point folder is created.
Device Templates : This folder contains created data point templates for the different technologies. o
M-Bus Device Templates: This folder contains a sub-folder for each device, which is imported from an M-Bus device template. This device folder also contains a sub-folder with the data points specified in the template. Data points can be added to the folder. Additionally suitable data objects can be created for the use on the device by selecting the Use on Device option.
Filter templates : This folder contains filter templates for scanned M-Bus devices o M-Bus : This folder contains a folder with data points for each created filter template.
LINX-XXX
: This is the device folder (see Section 6.2.1). For M-Bus an additional
port folder exists:
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 217 LOYTEC o M-Bus Port : This folder contains the remote M-Bus data points, which are used on the device.
10.5.4 Network Port Folders
The M-Bus network port folder on the device has the same structure of sub-folders as the
other network port folders in Section 6.2.2. Currently only the
Datapoints folder exists for the M-Bus network port.
10.5.5 M-Bus Properties
Apart from the common data point properties discussed in Section 6.2.4 the data points of
the M-Bus technology have additional properties:
Storage Number : This property defines the M-Bus storage number of the data point.
This number can also be specified by the manufacturer using a DIF/DIFE combination.
Tariff : This property defines the tariff of the M-Bus data point. This number can also be specified by the manufacturer using a DIF/DIFE combination.
Subunit : This property defines the subunit of the M-Bus data point. This number can also be specified by the manufacturer using a DIF/DIFE combination.
Function Field : This property defines the function field of the M-Bus data point.
Possible values for this property are instantaneous value, maximum value, minimum value and value during error state. This number can also be specified by the manufacturer using a DIF/DIFE combination.
Data Coding : This property defines how the value for this data point is coded. The information is not relevant for input data points but it is mandatory for output data points. Possible values for this property are instantaneous value, maximum value, minimum value and value during error state. This number can also be specified by the manufacturer using a DIF/DIFE combination.
VIF/VIFE : The VIF and VIFE (Value Information Field and VIF Extension) specify the counter type and its scaling. When the most significant bit of a VIF or VIFE is set, another VIFE follows. Up to ten VIFEs can be specified. When this combination is entered, also the M-Bus counter type and the unit are updated according to the
VIF/VIFE combination.
M-Bus Counter type: This information is derived from VIF/VIFE. It informs about the type of the data point value (e.g. Energy counter value or operating time).
M-Bus Device Name : This property shows the name of the M-Bus device the remote data point is connected to.
M-Bus Device Address : This property shows the address name of the M-Bus device the remote data point is connected to.
M-Bus Pollgroup : Each M-Bus input data point is attached to a poll group. If more than one poll group is available, the poll group can be selected. This property is not shown for output data points.
10.6 M-Bus Workflow
This section discusses the workflows for setting up an M-Bus environment. The network can either be set up online using the network scan function or also offline by either setting up the devices and data points manually or by using M-Bus device templates. The change of primary addresses and Baud rates can only be done online.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 218 LOYTEC
10.6.1 Offline Engineering
This section describes how an M-Bus network can be set up without using the M-Bus
network. Figure 170 shows the workflow. First, the M-Bus devices, address and Baud rates
of the M-Bus devices must be configured for example by following the device manu-
facturer‘s guidelines (see Section 10.7.3). Afterwards the devices and data points are
configured in the Configurator either configured manually (see Section 10.7.4) or by using
M-Bus device templates (see Section 10.7.5). Also mixing the two methods is possible.
When using the device templates also data points can be added manually. The configuration
is then downloaded to the device and the device is rebooted (see Section 6.6.4).
START
Configure addresses and Baud rates of the M-Bus devices
Section 10.7.3
M-Bus Data Points
Section 10.7.4
Import M-Bus Device Templates
Download Configuration to device
Section 6.6.4
Section 10.7.5
DONE
Figure 170: Workflow for offline engineering.
10.6.2 Online Engineering
This section describes how the M-Bus network is set up when the network can be accessed.
Figure 171 shows the workflow. If necessary the addresses and Baud rates the M-Bus
devices are using can be configured using the Configurator (see Section 10.7.3). The
devices and data points can then be configured by scanning the connected devices (see
Section 10.7.2), manual configuration (see Section 10.7.4) or also by using the M-Bus
device templates (see Section 10.7.5). The configuration is then downloaded to the device
and the device is rebooted (see Section 6.6.4).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 219
START
M-Bus devices already configured in the network?
yes
LOYTEC no
Configure M-Bus devices (change baudrate, change address)
Section 10.7.3
Manually Configure M-Bus devices and data points
Section 10.7.4
Scan M-Bus devices and data points
Section 10.7.2
Download Configuration to device
Section 6.6.4
Import M-Bus device templates
Section 10.7.5
DONE
Figure 171: Workflow for online engineering.
10.7 Using the Configurator for M-Bus
10.7.1 Automatic Naming
Operations which automatically generate M-Bus data points or allocate M-Bus devices use auto naming. Automatic naming is also used, when a device is applied and no device name is specified.
The automatic device name is concatenated from the device medium (e.g. Electricity), the 3 character M-Bus manufacturer code and the address. For example the device could be automatically named ―Electricity_LOY_7‖. If a name is specified, the device name of the applied device is concatenated the address, e.g., ―Device_7‖.
The automatic data point name is concatenated from the device name the data point is related with and the type of the data point. For example if a data point is an energy counter value in the device ―Electricity_LOY_7‖, the name ―Electricity_LOY_7_Energy‖ is created.
10.7.2 Scanning the M-Bus Network
The Configurator software can connect to the device and perform an M-Bus network scan.
The network scan searches for connected M-Bus devices and data points on those devices.
The device scan goes through each address on the M-Bus network using the specified Baud rates. When scanning for a device the M-Bus scanner starts with the highest specified Baud rate. If the device is found, it is added to the device list, if not, the scan tries to find the device address with the next lower Baud rate and so on.
The M-Bus scan can only scan for input data points. Output data points can be created manually or imported via a device template.
To Scan for Devices
1.
Connect to the device via FTP as described in section 6.6.1.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 220 LOYTEC
2.
Right click on the Folder M-Bus Network Scan and select Scan M-Bus Network .
This opens the M-Bus Network Scan
Important:
Figure 172 M-Bus Network Scan dialog.
3.
In M-Bus Transmission Settings choose the address scanning mode. The default is secondary address scanning. This prevents problems with duplicate primary addresses of previously uninstalled M-Bus devices.
4.
Select all applicable Baud rates for the device scan.
Selecting 300 Baud results in a very slow scan. Aborting the scan is possible using the
Abort Device Scan button
5.
Start the scan by pressing the Start Device Scan button. The progress bar shows the progress of the scan. Under the progress bar, a text displays, which device is currently scanned. When a device is found, it is displayed in the device list. The name of the
device is automatically created as described in section 10.7.1.
6.
The scan can be aborted by selecting the Abort Device Scan button.
7.
When the device scan is finished (either aborted or ended), the devices can be selected for a data scan. Also multi-select is possible.
8.
Select the devices which have to be scanned for data points and press the Scan Device
Data button. This scans all data points of the selected devices. For every device a folder with the name of the device is created under the M-Bus Network Scan folder.
The data points found are placed in the Datapoints folder of the appropriate devices.
To Use Datapoints from a Scan
1.
Go to the Datapoints folder of the device of the M-Bus scan.
2.
Select the desired data points, also multi-select is possible.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 221 LOYTEC
3.
Either press on the Use on Device button or right-click and select Use on Device .
The selected data points are now available in the Datapoints subfolder of the M-Bus
Port folder.
To Create Filter Templates from a Network Scan
1.
Go to the Datapoints folder of the device of the M-Bus scan.
2.
Select the desired data points, you wish to create a template from, also multi-select is possible.
3.
Right click on one of the selected data points and select Use as Template . This creates a folder, containing the selected data points.
To Use data points from a Scan using Filter Templates
1.
Right click on the folder M-Bus Network Scan and select either Use on device and apply single M-Bus filter templates or select Use on device an apply all M-Bus filter templates . When all filter templates are applied, all matching data points from the scan are used on the M-Bus port of the device.
2.
When Use on device and apply single M-Bus filter templates is selected, the following dialog is opened:
3.
The drop down box shows all available M-Bus filter templates. As additional information, when a filter template is chosen, the number of data points is displayed, which match the template.
4.
Select OK to use the data points on the device.
10.7.3 Network Management Functions
This section describes how the M-Bus network management functions can be used. It describes adding and removing M-Bus devices as well as changing the Baud rate or the primary address. The tasks can be performed offline as well as online.
Version 4.0
The Network Management
dialog shown in Figure 173 shows a list of devices. Devices
which have been scanned using a network scan have the status online, devices which have been created manually or using device templates have the status offline. If a device which is online also has been scanned for device data, a green checkmark is displayed in the Data column.
To Start the M-Bus Network Management Dialog
1.
Connect to the device via FTP as described in section 6.6.1.
2.
Select the M-Bus dialog by clicking on the M-Bus button in the tool bar of the Datapoints tab. The M-Bus Management dialog opens, showing the Network Management
LOYTEC electronics GmbH
L-INX User Manual 222 LOYTEC
Version 4.0
Figure 173: M-Bus network management dialog.
To Add an M-Bus Device Manually Without Scanning
1.
Fill in the Device Address and select a Device Baudrate from the drop down box.
2.
A Device Name can be specified. If more devices with the same properties have to be created using subsequent addresses, the end address can be specified in the input field on the right hand side of the Device Address field.
3.
The device capabilities specify, what kind of M-Bus read requests the device is able to process. If nothing is specified here, Default Read is used. Default read usually means that the M-Bus device transfers all its data during a read. Selective read means that the data point which is to be read can be selected during the read request. If the device is able to perform such a request, Selective Read should be checked.
4.
The optional device information just represents manufacturer details and model details.
This information is used in two cases: a.
The device name is not specified – in this case a device name is automatically created from the optional device information. The name is concatenated to
MAN_Medium_address, where MAN is the 3 character manufacturer code,
Medium is the M-Bus medium (e.g. ―Heat‖) and address is the specified address. b.
Device templates can be created from the M-Bus devices. The device templates store the device information in order to identify a device.
LOYTEC electronics GmbH
L-INX User Manual 223 LOYTEC
5.
Click on the Create Device button. This creates the M-Bus device and adds it to the device list on the left hand side of the dialog.
6.
When a device is selected the device information is displayed in the appropriate fields on the right hand side of the dialog. The information can be changed in the fields. Press the Update Device button to store the changes.
7.
If a device has to be deleted select the device and press the Remove Device button.
To Add an M-Bus Device Manually Using the Scan Device Information
1.
Enter the address of the device which has to be scanned.
2.
Press the Scan Device Information button. If the device is found in the network, the device properties are filled.
3.
Enter a name for the M-Bus device in the Device Name field. If no name is specified
the name is created automatically as described in section 10.7.1 from the M-Bus data
the device sends back.
4.
Enter a device address in the Device Address field. If more devices with the same properties have to be created using subsequent addresses, the end address can be specified in the input field on the right hand side of the Device Address field.
5.
Select a device Baud rate from the combo box.
6.
Press the Create Device Button to add the number of devices.
To Add an M-Bus Device Manually Using a Template
1.
Enter a name for the M-Bus device in the Device Name field. If no name is specified
the name is created automatically as described in section 10.7.1 from the M-Bus data
the device sends back.
2.
Enter a device address in the Device Address field. If more devices with the same properties have to be created using subsequent addresses the end address can be specified in the input field on the right hand side of the Device Address field.
3.
Click on the Create From Template button. This opens the Import M-Bus Device
Template
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 224 LOYTEC
Tip:
Figure 174 Import M-Bus Device dialog.
4.
Press the button and select a template file from the Open dialog.
5.
After selecting the file, the device information is displayed.
6.
Press Import for importing the template or Cancel for closing the dialog without any changes.
7.
When a template is imported, a folder with the name of the device is created. Under this folder a Datapoints folder containing the data points from the template file is created.
Data points can be added to the data points of the template by right-clicking in the data point list and selecting New Datapoint.
When you want to create one or more device instance together with its data points, use the button Create with DP instead of the button Create From Template. This creates the device instance, all the data points from the template can be found in the M-Bus Port’s data points folder.
To Remove an M-Bus Device
1.
Select the device which has to be removed, also multi-select is possible.
2.
Press the Remove Device button. If the device already has data points, these data points have to be deleted before the remove can be performed.
To Change the Properties of an M-Bus Device
1.
Select the device. This shows the device properties.
Version 4.0
2.
Update the field Device Address or select another Baud rate in the combo box.
3.
Press the button Update Device .
4.
If a device address is specified, which already exists, a failure message is displayed.
LOYTEC electronics GmbH
L-INX User Manual 225 LOYTEC
Important:
To Scan Devices Using the M-Bus Network Management Dialog
1.
Select the Baud rate for the device scan. For more information on scanning the M-Bus
network refer to Section 10.7.2.
2.
Start the scan by pressing the Scan for Devices button .
3.
When the device scan is finished, the devices can be selected for a data scan. Also multi-select is possible.
4.
Select the devices which have to be scanned for data points and press the Scan Device
Data button. This scans all data points of the selected devices. For every device a folder with the name of the device is created under the M-Bus Network Scan folder.
The data points found are placed in the Datapoints folder of the appropriate devices.
If a device, which is scanned, is already in the device list, the existing device can either be overwritten; deleting all previously scanned data points of the existing device or the scanned device can be discarded. A dialog is displayed for this decision.
10.7.4 Manual Configuration of Data Points
It is possible to manually configure M-Bus data points. Manual configuration is done by specifying all information, the M-Bus device manufacturer provides.
To Manually Create an M-Bus Data Point
1.
Click on the M-Bus port Datapoints folder.
2.
Right click in the data point list view and select New Datapoint in the context menu.
3.
This opens the Create New M-Bus Datapoint
Version 4.0
Figure 175 Create M-Bus Object dialog.
4.
If the M-Bus device which provides the data point is not in the list, it has to be created.
In this case open the Network Management dialog by clicking the Edit M-Bus Devices button.
5.
Create the device in the Network Management dialog and close the dialog.
LOYTEC electronics GmbH
L-INX User Manual 226 LOYTEC
6.
Select the device which provides the M-Bus data point.
7.
The data point properties are entered in the presented section of the dialog.
Version 4.0
8.
Enter a data point name. If no name is entered, the data point is named as described in
9.
At the moment only analog M-Bus data points are supported. Select if the data point is an analog input or output. For analog inputs no M-Bus data coding can be specified.
10.
Select if the data point shall be specified by providing the numbers for Storage number, tariff, subunit, function field and data coding or if the information configured using the
DIF/DIFE list.
For reference, if one piece of information is entered, the other one is derived from the specified data. Enter the data point information.
If the DIF list is entered, the dialog expects hexadecimal numbers. As soon as the information is entered the other fields are updated.
11.
Enter the VIF/VIFE list. This list specifies the M-Bus counter type, and unit of the data point. Also this field has to be specified using hexadecimal numbers.
LOYTEC electronics GmbH
L-INX User Manual 227 LOYTEC
Tip:
12.
Usually data points are added to a default poll group. If the data point has to be member of another poll group than default, the poll group can be selected using the drop down box.
In the drop down box the previously specified poll groups are shown. If no poll group
is configured only the default poll group is displayed. Refer to section 10.7.7 for more
information on poll groups.
13.
Press the Create button to create the M-Bus data point
After creating a data point, the poll group can be changed in the data points property view. Also multi-select can be used.
10.7.5 Importing via Device Templates
For some M-Bus devices special templates are available which specify all available data points of an M-Bus device as well as the device properties. Such templates can be imported into the configuration.
To import an M-Bus Device Template
1.
Right click on the Folder M-Bus Device Templates and select Import device template from the context menu.
2.
This opens the Import M-Bus Device Template
Version 4.0
Figure 176: Import M-Bus Device Template dialog.
3.
Press the button and select a template file from the Open dialog.
4.
After selecting the file, the device information is displayed.
5.
Press Import for importing the template or Cancel for closing the dialog without any changes.
6.
When a template is imported, a folder with the name of the device is created. Under this folder a Datapoints folder containing the data points from the template file is created.
LOYTEC electronics GmbH
L-INX User Manual
Tip:
228 LOYTEC
Data points can be added to the data points of the template by right clicking in the data point list and selecting New Datapoint.
Importing a device template from the folder list does not create a device instance. Device instances can only be created using the import in the Network Management Dialog.
To Use Imported Data Points
Using imported data points is a little different to the use of scanned data points. For a scanned device a device instance already exists – the important information address and
Baud rate – devices imported from templates do not have an address or Baud rate.
1.
Go to the Datapoints folder of the device of the M-Bus Templates.
2.
Select the desired data points, also multi-select is possible.
3.
Either press on the Use on Device button or right-click and select Use on Device .
This opens the M-Bus Configure Device For Use
Figure 177 Use on Device dialog.
4.
The device list displays all devices which have the same Manufacturer ID, version number and Medium. If no device instance matches the device template, create one by entering the network management dialog. The dialog can be entered by pressing the
Edit M-Bus Devices button. In the management dialog, the device instance can be either created manually (take care of entering the correct Manufacturer ID, Version and
Medium) or by simply importing the template again.
5.
Select one or more device instances from the list and press the Use On Device button.
This creates for each selected data point and each selected device one data point in the
M-Bus Port‘s data point list.
10.7.6 Creating Device Templates
M-Bus device templates can be created from a data point configuration. In fact, it is only possible to create a device template using an existing device or an existing device template with data points. This device and its data points can either be configured manually, by a scan or also imported from a device template itself.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 229 LOYTEC
To Create an M-Bus Device Template Using Devices
1.
Select the M-Bus dialog by clicking on the M-Bus button in the tool bar of the Datapoints tab. This opens the Network Management dialog as
Figure 178 M-Bus Network Management dialog.
2.
The device list shows all devices of the current configuration. Select a device.
3.
Press the Export Device Template button. This opens the M-Bus Export Template dialog.
Version 4.0
4.
Press the button and select a template file from the Save dialog.
5.
Enter the Creator , Company Name and Version for the template. This information is stored in the template file, when importing the template file the information is displayed after selecting the file.
LOYTEC electronics GmbH
L-INX User Manual 230 LOYTEC
6.
Press the Export button.
To Create an M-Bus Device Template File Using a Device Template
1.
Right-click on the folder of the device template that has to be exported or its data point folder and select Export Device Template… from the context menu.
2.
Proceed as described above to export the template in the Export M-Bus Device
Template dialog.
10.7.7 Poll Groups
In an M-Bus network, the master has to poll the slave devices. Input data points are therefore attached to a poll group. If nothing else is specified, the default poll group is used for input data points. The default poll group has a poll cycle of 60 seconds.
Three different types of poll groups can be specified:
Time-based: The poll group is triggered on a time base. This means that after a specific time – the poll cycle – the poll group is processed.
Trigger-based: The poll group is triggered on a special trigger data point. As soon as the trigger condition is met, the poll group is processed.
Trigger-based with synchronization: This type is similar to the trigger-based. The difference is that when the trigger condition is met, a broadcast synchronization message is sent over the M-Bus. This causes the devices which are able to perform a sync operation to store special data points for later reading. After the broadcast is sent, the poll group is processed.
Tip: If an M-Bus device is only able to process default read requests, it is advisable to attach all data points of this device to the same poll group (this increases the performance).
The poll group a data point is attached to can be changed in the properties view of the data points. The poll group can also be changed for multiple data points using multi-select.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 231 LOYTEC
To Create a Time-Based M-Bus Poll Group
1.
Select the M-Bus dialog by clicking on the M-Bus button in the tool bar of the Datapoints tab. The M-Bus Management dialog opens.
2.
Open the Pollgroups
tab. This shows the dialog displayed in Figure 179.
Version 4.0
Figure 179: Pollgroup Management dialog.
3.
The default poll group is selected and its properties are displayed. Enter the name of the new poll group and enter the poll cycle in seconds. Make sure that under Pollgroup
Mode Time-based is selected.
4.
Press the Save button to store the poll group and continue editing.
5.
If a poll group needs to be updated or deleted, select the poll group edit the data and press the Update Selected or Delete Selected button.
6.
Press the Close button to finish editing. When the poll groups have not been saved, a dialog asks whether the changes have to be saved or not.
To Create a Trigger-Based M-Bus Poll Group
1.
Select the M-Bus dialog by clicking on the M-Bus button
LOYTEC electronics GmbH
L-INX User Manual 232 LOYTEC in the tool bar of the Datapoints tab.
2.
In the M-Bus Management dialog, open the Pollgroups tab. This displays the poll
groups management tab displayed in Figure 179.
3.
Enter a new poll group name and select Trigger-based or Trigger-based with synchronization .
4.
Create the poll group by pressing the Create New button.
5.
Select the new poll group. This enables the Add… and Remove buttons from the triggers.
6.
Press the Add… button and select a trigger data point. This can for example be a binary user register.
7.
The selected trigger data point appears in the trigger list as shown:
8.
Select the trigger from the list and check the desired trigger conditions.
9.
The trigger conditions are then displayed in the trigger list.
10.
Press the Close button to leave the dialog.
10.7.8 Trending Synchronized Meter Data
The use of trigger-based poll groups with synchronization allows trending synchronized meter data. A trigger data point triggers a synchronization message over the M-Bus network. The M-Bus meters which are able to perform the synchronization action store the meter values. These values are read out afterwards.
To Trend Synchronized Meter Data
1.
Create a binary trigger data point.
2.
Create a trigger-based poll group with synchronization.
3.
Create a trend log as described in Section 6.14. Set the
Trend Mode to Change of
Value (COV) and add all required data points.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 233 LOYTEC
10.7.9 M-Bus Protocol Analyzer
When connected to a device a protocol analyzer is available for the M-Bus port. The
protocol analyzer can be found in the M-Bus Management dialog. Figure 180 shows the
dialog for the M-bus protocol analyzer.
The status on the right hand side of the dialog shows, if the device is connected or if the protocol analyzer is stopped or started. When connected to a device, the protocol analyzer can be started by pressing the Start Protocol button. This starts the protocol analyzer in the device. Every time a transmission is made on the M-Bus port, the transmission is displayed in the list. Additionally the protocol data is stored in the device in a rotating log file. The protocol log can hold up to 40 kB of protocol data. So also when the Configurator was not running for an interesting time, the protocol data can be loaded from the device using the
Load From Device button. The protocol data can be stored as CSV file using the Save button, with the Clear button, the shown protocol is deleted.
Version 4.0
Figure 180 M-Bus protocol analyzer.
Figure 181 shows a typical protocol analyzer output for the M-Bus port. It shows the
following information:
Seq.
: sequence number, which is automatically created in the device. This number is unique for one port.
Timestamp: transmission time.
Frame Type: M-Bus frame type (Short Frame, Control Frame Long Frame, E5 – in this case, no other data follows).
Dir.
: direction. Either SND (send) or RCV (receive)
Start1, Start2: Start byte (must be equal)
Length1, Length2: Frame length according to the M-Bus standard (must be equal)
C Field: Control field
Address: M-Bus address
CI Field: Control information field
Checksum: Checksum of the frame
Stop: Stop byte
Payload: Payload in hexadecimal numbers (this column cannot be used for sorting)
Some frame types do not contain the full set of fields. Please refer to the M-Bus standard for additional information.
LOYTEC electronics GmbH
L-INX User Manual 234 LOYTEC
Figure 181 Typical protocol analyzer output for M-Bus port.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
11 Modbus
235 LOYTEC
11.1 Introduction
The Modbus is a de facto industrial standard which was initially intended for the communication between PLCs. In the meantime the Modbus has become an important interface for automatic meter reading applications and industrial applications. As the
Modbus is an open protocol a large number of automation devices providing Modbus communication is available.
Two communication methods are available for Modbus. Modbus TCP utilizes Ethernet for the Modbus communication. Modbus RTU uses a RS485 bus for Modbus data transfer.
Modbus RTU uses a serial bus, which is controlled by a single master. This master can request data from several slave devices connected to the network.
11.2 Modbus Network
Modbus TCP utilizes the Ethernet for the communication. Several Modbus slave devices can be connected. In Modbus TCP a unit identifier is used instead of the slave address.
Modbus slaves may have the same unit identifier. This unifier is usually used to communicate with bridges, routers and gateways.
The Modbus RTU network utilizes an RS485 connection. Several Modbus slave devices are connected in parallel to the transmission medium. Each Modbus device has a unique slave address in the range from 1 to 255. The Baud rate of the RS485 can be configured to use
1200, 2400, 4800, 9600, 19200, and 38400 Baud. The parity is always none. The LOYTEC
Modbus interface supports 8N1 only. Parity and stop bits are not configurable.
Modbus devices use function codes for the specification of the desired data. The following function codes for read/write actions are supported by the LOYTEC device:
02: Read discrete inputs.
01: Read coils.
05: Write coil.
04: Read input register
03: Read holding registers
06: Write holding registers
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 236 LOYTEC
For optimizing the communication adjacent holding registers are usually read using a single read request. This behavior can be turned of for devices which do not support reading a random number of holding registers.
Modbus data points are specified by the function code, the address and the length.
Furthermore, a data type has to be specified together with the information how the order of the bytes look like.
11.3 Web Interface
This section describes the Web interface for the Modbus port.
11.3.1 Port Configuration
The Modbus ports can be configured under the port configuration tabs of the Web UI (see
Section 4.2.3). If available on a given port, the Modbus protocol can be enabled. If enabled,
the Modbus communication settings on that port are displayed on the right-hand side. The
RS485 port configuration tab is.
Figure 182 Modbus RS485 port configuration.
The settings for Modbus RS485 are displayed in Figure 182. For
Modbus port mode , the following selections are available: MASTER can be selected, if the device shall operate as
Modbus master. SLAVE can be selected, if the device shall operate as a Modbus slave on this port.
Under Baud rate the Baud rate for the Modbus communication can be configured. The available Baud rates are 1200, 2400, 4800, 9600, 19200, 38400 (default) . Under Paritiy currently only NONE can be selected, using 1 stop bit. Parity and stop bits are not configurable. The Mode specifies if the communication shall use the Modbus RTU mode or the Modbus ASCII mode.
If operated as Modbus master, an additional Transmission delay can be defined in milliseconds. This can improve communications on Modbus RS485 with slow devices that operate outside the timing specifications. Normally, leave this setting at ‗0‘. As a Modbus slave, the user needs to define a unique slave address that this port will have on the
Modbus channel.
Press the button Save Settings for storing the parameter configuration into the device or press Get Settings for overwriting the changes with the original configuration.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 237 LOYTEC
Figure 183 Modbus TCP port configuration.
On an Ethernet port, Modbus TCP can be enabled by selecting the check box. The Modbus
TCP communication settings are displayed on the right-hand side as shown in Figure 183.
For Modbus port mode , the following selections are available: MASTER can be selected, if the device shall operate as Modbus master. SLAVE can be selected, if the device shall operate as a Modbus slave on this port. Configure the desired TCP port, which is used by
Modbus TCP devices on that channel. The default Modbus port number is 502.
11.3.2 Data Points
Modbus data points can be accessed through the Web UI as described in Section 4.2.15.
11.3.3 Statistics
Figure 184 shows a typical output of the statistics information which can be displayed for
the Modbus ports. For each port available one statistics tab is displayed. The statistics can be cleared for each Modbus port separately by pressing the Clear Modbus statistics button. A refresh of the statistics can be done by pressing Update Modbus statistics .
Version 4.0
Figure 184: Statistics of the Modbus port.
The following information is available:
Statistics cleared: last time of statistics reset
Rx packets: number of Modbus packets received
Rx bytes: number of bytes received
Tx packets: number of Modbus packets sent
Tx bytes: number of bytes sent
Timeout errors: number of communication errors (timeout)
LOYTEC electronics GmbH
L-INX User Manual 238 LOYTEC
Checksum errors: number of communication errors (wrong checksum)
11.3.4 Modbus Protocol Analyzer
By activating the link Protocol Analyzer (available in all Modbus statistics tabs), the
protocol analyzer page is shown as displayed in Figure 185.
Figure 185 Modbus protocol analyzer.
Next to the button the status of the protocol analyzer is shown. If the analyzer is started, an automatic refresh is performed every 60 seconds. By pressing the button Start Protocol
Analyzer / Stop Protocol Analyzer the protocol analyzer can be started / stopped.
For every frame sent or received a line is presented using comma separated values.
11.4 Configurator
This section describes how to use the Configurator software for the management of Modbus
data points. For further information on the Configurator software refer to Chapter 6.
11.4.1 Activating Modbus Configuration
Before a new Modbus configuration can be managed, the Modbus option must be enabled
for the appropriate port. The project settings are described in detail in Section 6.3.
To Activate the Modbus Configuration
1.
Open the project settings dialog.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 239 LOYTEC
2.
In the Device Config tab enable the Modbus check boxes on the desired ports as shown
in Figure 186. Setting the check box enables Modbus on that port. Edit the Modbus
communication settings.
3.
If slave mode is enabled, you may change the default Modbus register layout in the
Modbus Slave Register Configuration box.
4.
Click the Download button to activate the changes in the configuration.
Figure 186: Project settings for Modbus.
Important: If the Modbus port is deactivated via the checkbox or a firmware or model version is chosen, which does not support Modbus, the entire Modbus configuration is deleted. In this case a dialog is displayed, which has to be confirmed.
11.4.2 Data Point Manager for Modbus
The Configurator uses a central concept to manage data points. The data point manager is used to select, create, edit and delete data points. The dialog is divided into three sections:
The data point list (Figure 188),
And a property view.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 240 LOYTEC
Figure 187: Data Point Manager Dialog with Modbus folder list.
Figure 188: Datapoint Manager Dialog with Modbus Data Point List.
11.4.3 Folder List
At the left is a list of folders which is used to sort the available data objects by their category. There are a number of predefined Modbus folders available. All other folders are
Device Templates : This folder contains created data point templates for the different technologies. o Modbus Device Templates: This folder contains a sub-folder for each device, which is imported from an Modbus device template. This device folder also contains a sub-folder with the data points specified in the template. Data points can be added to the folder. Additionally suitable data objects can be created for the use on the device by selecting the Use on Device option.
LINX-XXX
: This is the device folder (see Section 6.2.1). For Modbus additional port
sub-folders exist: o Modbus Port RS-485 : This folder contains the remote Modbus data points of the Modbus RS-485 port, which are used on the device. o Modbus Port TCP : This folder contains the remote Modbus data points of the Modbus TCP port, which are used on the device.
11.4.4 Network Port Folders
The Modbus network port folder on the device has the same structure of sub-folders as the
other network port folders in Section 6.2.2. Currently only the
Datapoints folder exists for the Modbus network ports.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 241 LOYTEC
11.4.5 Modbus Properties
Apart from the common data point properties discussed in Section 6.2.4 the data points of
the Modbus technology have additional properties:
Modbus Device Name : This property defines the name of the Modbus slave device which contains the data point.
Modbus Device Address : This property defines the address of the Modbus slave device which contains the Modbus data point.
Modbus Register Start Address : This property defines the address of the Modbus register.
Modbus Register Type : This property defines the register type of the data point. Also the function code, which specifies the register, is displayed. When the Modbus register type is changed from a read to a write register, also the direction of the data point is changed.
Modbus Data Type : This property defines the representation of data in the slave. This is the data type the Modbus slave uses for the data point internally. This can for example be float, double, int16 or uint32.
Modbus Multiplier, Exponent and Offset : This property defines scaling parameters for the data point. The value of the data point in the LOYTEC device is calculated as follows:
Value = (ModbusValue + Offset) ∙ Multiplier ∙ 10 Exponent
.
Modbus Swap 16 bit, Swap 32 bit and Swap 64 bit: This information specifies, if the order of received Modbus data has to be changed. When Swap 16 bit is set, the two bytes of a 16 bit word are swapped, if Swap 32 is set, the two words of 32 bit are swapped, and if Swap 64 bit is set, the two 32 bit words of 64 bit long data are swapped. Also combinations are possible. This configuration is necessary because the
Modbus slaves can store information in any byte order (the Modbus protocol only specifies, how 16 bit data is transferred).
Pollgroup : This property is only available for input data points. It shows the poll group, the data point is connected to.
11.4.6 Modbus Workflow
This section discusses the workflows for setting up a Modbus environment. Modbus does not provide a scan function and therefore the network has to be setup offline. This can be eased by the use of templates. If no templates are available, the data points have to be set up manually.
Figure 189 describes the workflow for setting up a Modbus network. For using Modbus the
Modbus ports of the LOYTEC device and the Modbus devices have to be configured. The
RS-485 Modbus port must get a Baud rate, the parity is fixed at none and the stop bits are configured to 2. The Modbus TCP port must get the TCP port number of the slave devices
(see Section 11.3.1). The Modbus devices have to be configured according to the LOYTEC
device‘s port configuration (see Section 11.5.1). When no device template is available for a
Modbus device, it can simply be created by configuring Modbus data points for the device
manually (see Section 11.5.2) and exporting the device template. The exported device
template can then be used to easily add additional Modbus devices with the same data point
configuration (see Section 11.5.3). Also mixing the two methods is possible. When using
the device templates also data points can be added manually. The configuration is then downloaded to the device and the device is rebooted.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 242
START
Configure Modbus Port
Section 11.3.1
Configure Modbus devices/addresses
Section 11.5.1
Configure Modbus Data Points
Section 11.5.2
Import Modbus Device Templates
Download Configuration to LINX
Section 6.6.4
Section 11.5.3
DONE
Figure 189: Workflow for offline engineering.
LOYTEC
11.5 Using the Configurator for Modbus
11.5.1 Modbus Management Functions
This section describes how the Modbus network management functions can be used. It describes adding and removing Modbus.
The Modbus Management
dialog shown in Figure 190 shows the list of devices. Devices
which have been imported from a template show the template name in the last column. For each device the address, the IP address (if available), the port and the number of data points available on that device is shown.
The Modbus Management dialog can also be used for the configuration of poll groups and for accessing the LOYTEC devices protocol analyzer.
To Start the Modbus Network Management Dialog
1.
Connect to the device via FTP as described in section 6.6.1.
2.
Select the Modbus dialog by clicking on the Modbus button in the tool bar of the Datapoints tab. The Modbus Management dialog opens, showing the Modbus Device Management
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 243 LOYTEC
Version 4.0
Figure 190: Modbus management dialog.
To Add a Modbus Device Manually
1.
Fill in the Device Address and select the Type (either RS485 or TCP) from the drop down box.
2.
A Device Name can be specified. If no device name is specified, the device name is created automatically. If more devices with the same properties have to be created using subsequent addresses, the number of devices can be specified in the input field under the Device IP Address field. If a number of TCP devices has to be created, subsequent IP addresses are configured. If the checkbox Increase Device Address is checked, also the Device Addresses (unit IDs) of the TCP devices are increased.
3.
The Device Address specifies the address of the Modbus device ranging from 1 to 255.
In case of a TCP device the device address specifies the unit ID. For a RS-485 device the device address has to be unique, TCP devices can have equal device addresses.
4.
For TCP devices the Device IP Address has to be specified.
5.
If the device is not able to read adjacent registers with one read command, activate the checkbox Read Single Registers .
6.
The optional manufacturer details just represent Manufacturer name and Model name. This information is used to identify device templates.
7.
Click on the Create Device button. This creates the Modbus device and adds it to the device list on the left hand side of the dialog.
8.
When a device is selected the device information is displayed in the appropriate fields on the right hand side of the dialog. The information can be changed in the fields. Press the Update Device button to store the changes.
9.
If a device has to be deleted select the device and press the Remove Device button.
LOYTEC electronics GmbH
L-INX User Manual 244 LOYTEC
To Add a Modbus Device Manually Using a Template without Creating Data
Points
1.
Enter a name for the Modbus device in the Device Name field. If no name is specified the name is created automatically from the name in the template file.
2.
Fill in the Device Address and select the Type (either RS485 or TCP) from the drop down box. If TCP is selected also enter the Device IP Address . If more devices with the same properties have to be created using subsequent addresses, the number of devices can be specified in the input field under the Device IP Address field.
3.
Click on the Create From Template button. This opens the Import Modbus Device
Template
Tip:
Version 4.0
Figure 191 Import Modbus Device Template dialog.
4.
Press the button and select a template file from the Open dialog.
5.
After selecting the file, the device information is displayed.
6.
Press Import for importing the template or Cancel for closing the dialog without any changes.
7.
When a template is imported, a folder with the name of the device is created. Under this folder a Datapoints folder containing the data points from the template file is created.
Data points can be added to the data points of the template by right-clicking in the data point list and selecting New Datapoint.
To Add a Modbus Device Manually Using a Template Creating Data Points
1.
Enter a name for the Modbus device in the Device Name field. If no name is specified the name is created automatically from the name in the template file.
2.
Fill in the Device Address and select the Type (either RS485 or TCP) from the drop down box. If TCP is selected also enter the Device IP Address . If more devices with the same properties have to be created using subsequent addresses, the number of devices can be specified in the input field under the Device IP Address field.
LOYTEC electronics GmbH
L-INX User Manual 245 LOYTEC
3.
Click on the Create with DP button. This opens the Import Modbus Device
Template
4.
Press the button and select a template file from the Open dialog.
5.
After selecting the file, the device information is displayed.
6.
Press Import for importing the template or Cancel for closing the dialog without any changes.
7.
When a template is imported, a folder with the name of the device is created. Under this folder a Datapoints folder containing the data points from the template file is created.
8.
The created device is shown in the list together with the number of data points.
To Remove a Modbus Device
1.
Select the device which has to be removed, also multi-select is possible.
2.
Press the Remove Device button. If the device already has data points, these data points have to be deleted before the remove can be performed.
To Change the Properties of a Modbus Device
1.
Select the device. This shows the device properties.
2.
Update the properties which have to be changed.
3.
Press the button Update Device .
4.
When the device type is changed, it is verified that no device with the address exists on the appropriate port – on RS485 the device address has to be unique, on TCP the device IP address has to be unique.
11.5.2 Manual Configuration of Data Points
It is possible to manually configure Modbus data points. Manual configuration is done by specifying all information, the Modbus device manufacturer provides.
To Manually Create an Modbus Data Point
1.
Click on the Modbus port Datapoints folder.
2.
Right-click in the data point list view and select New Datapoint… in the context menu.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 246 LOYTEC
3.
This opens the Create New Modbus Datapoint dialog showing only the devices
which are available on the appropriate port. This dialog is shown in Figure 192.
Figure 192 Create Modbus Datapoint dialog.
4.
If the Modbus device which provides the data point is not in the list, it has to be created. In this case open the Modbus Management dialog by clicking the Edit Modbus
Devices button.
5.
Create the device in the Modbus Management dialog and close the dialog.
6.
Select the device which provides the Modbus data point.
7.
Enter the General Data Point Properties. These are the data point name , which is automatically created when not specified, and the Register Type . The register type of the data point is provided in the Modbus device documentation. The drop down menu shows the Modbus register type, the direction (read and write) and the function code.
The data point properties are entered in the presented section of the dialog.
Version 4.0
8.
Enter the properties of the data point. The register address is specified by the manufacturer. Select the Modbus Data Type . This type specifies how the manufacturer stores data in the Modbus device. The Modbus Data Length is automatically updated according to the data type. Offset, Multiplier and Exponent can be used for mapping purposes. The Value of the data point is calculated as follows:
Value = (ModbusValue + Offset) ∙ Multiplier ∙ 10 Exponent
.
Modbus does not specify any byte orders of the data stored in devices. For some devices it may be necessary to change the byte order. This is done by the check boxes
LOYTEC electronics GmbH
L-INX User Manual 247 LOYTEC
Swap 16 bit , Swap 32 bit and Swap 64 bit . When Swap 16 bit is activated, the 2 byte of a word are swapped, when Swap 32 bit is activated, the 2 words of a 32 bit value are swapped and if Swap 64 bit is activated, the two 32 bit words of a 64 bit value are swapped. A preview of the byte order is shown under the check boxes.
Select the Data Point Type of the data point (analog value, multi-state or binary) – only the types which are available for the register type-data type combination are shown.
Tip:
9.
Select a poll group for read data points from the Pollgroup drop down box. The drop down box is grayed out for write registers. Additional poll groups can be configured in the Modbus Management dialog.
10.
Press the Create button to create the Modbus data point.
11.
After the point is created the dialog is not closed, so additional data points can be created.
After creating a data point, the poll group can be changed in the data points property view. Also multi-select can be used in the data point property view.
11.5.3 Importing via Device Templates
For some Modbus devices special templates are available which specify all available data points of a Modbus device as well as the device properties. Such templates can be imported into the configuration.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 248 LOYTEC
To import a Modbus Device Template
1.
Right click on the Folder Modbus Device Templates and select Import device template from the context menu.
2.
This opens the Import Modbus Device Template
Tip:
Figure 193 Import Device Template dialog.
3.
Press the button and select a template file from the Open dialog.
4.
After selecting the file, the device information is displayed.
5.
Press Import for importing the template or Cancel for closing the dialog without any changes.
6.
When a template is imported, a folder with the name of the device is created. Under this folder a Datapoints folder containing the data points from the template file is created.
Data points can be added to the data points of the template by right clicking in the data point list and selecting New Datapoint.
Importing a device template from the folder list does not create a device instance. Device instances can only be created using the import in the Network Management Dialog. In this dialog also the device instances can also be created with their data points.
To Use Imported Data Points using Use On Device
1.
Go to the Datapoints folder of the device of the Modbus Templates.
2.
Select the desired data points, also multi-select is possible.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 249 LOYTEC
3.
Either press on the Use on Device button or right-click and select Use on Device .
This opens the Choose Modbus Device Instance dialog.
Figure 194: Choose Modbus Device Instance dialog.
4.
The device list displays all devices which have the same Manufacturer, and the same
Model Name as the template. If no device instance matches the device template, create one by entering the Modbus management dialog. The dialog can be entered by pressing the Edit Modbus Devices button. In the management dialog, the device instance can be either created manually (take care of entering the correct manufacturer and model) or by simply importing the template again.
5.
Select one or more device instances from the list and press the Use On Device button.
This creates for each selected data point and each selected device one data point in the
Modbus Port‘s data point list.
11.5.4 Creating Device Templates
Modbus device templates can be created from a data point configuration. In fact, it is only possible to create a device template using an existing device or an existing device template with data points. This device and its data points can either be configured manually or also imported from a device template itself.
To Create a Modbus Device Template Using Devices
1.
Select the Modbus dialog by clicking on the Modbus button in the tool bar of the Datapoints tab. This opens the Network Management dialog
opens as described in Section 11.5.1.
2.
The device list shows all devices of the current configuration. Select the device you want to export.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 250 LOYTEC
3.
Press the Export Device Templ. button. This opens the Export Modbus Device
Template
dialog shown in Figure 195. The list on the left side of the dialog shows the
names of the data points which are exported to the template.
Figure 195 Export Modbus Device Template dialog.
4.
Press the button and select a template file from the Save dialog.
5.
Enter the Creator , Company Name and Version for the template. This information is stored in the template file, when importing the template file the information is displayed after selecting the file.
6.
Press the Export button.
To Create a Modbus Device Template File Using a Device Template
1.
Right-click on the folder of the device template that has to be exported or its data point folder and select Export Device Template… from the context menu.
2.
This opens the Export Modbus Device Template
dialog as shown in Figure 195.
Proceed as described above.
11.5.5 Poll Groups
In a Modbus network, the master has to poll the slave devices. Input data points are therefore attached to a poll group. If nothing else is specified, the default poll group is used for input data points. The default poll group has a poll cycle of 60 seconds.
Two different types of poll groups can be specified:
Time-based: The poll group is triggered on a time base. This means that after a specific time – the poll cycle – the poll group is processed.
Trigger-based: The poll group is triggered on a special trigger data point. As soon as the trigger condition is met, the poll group is processed.
Tip: The poll group a data point is attached to can be changed in the properties view of the data points. The poll group can also be changed for multiple data points using multiselect.
To Create a Time-Based Poll Group
1.
Select the Modbus dialog by clicking on the Modbus button
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 251 LOYTEC in the tool bar of the Datapoints tab. This opens the Modbus Management dialog.
2.
Open the Pollgroups
tab. This shows the dialog displayed in Figure 196.
Figure 196: Pollgroup Management dialog.
3.
The default poll group is selected and its properties are displayed. Enter the name of the new poll group and enter the poll cycle in seconds. Make sure that under Pollgroup
Mode Time-based is selected.
4.
Press the Save button to store the poll group and continue editing.
5.
If a poll group needs to be updated or deleted, select the poll group edit the data and press the Update Selected or Delete Selected button.
6.
Press the Close button to finish editing. When the poll groups have not been saved, a dialog asks whether the changes have to be saved or not.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 252 LOYTEC
To Create a Trigger-Based Modbus Poll Group
1.
Select the Modbus dialog by clicking on the Modbus button in the tool bar of the Datapoints tab. This opens the Modbus Management dialog.
2.
In the Modbus Management dialog, open the Pollgroups tab. This displays the poll
groups management tab displayed in Figure 196.
3.
Enter a new poll group name and select Trigger-based .
4.
Create the poll group by pressing the Create New button.
5.
Select the new poll group. This enables the Add… and Remove buttons from the triggers.
6.
Press the Add… button and select a trigger data point. This can for example be a binary user register.
7.
The selected trigger data point appears in the trigger list as shown:
8.
Select the trigger from the list and check the desired trigger conditions.
9.
The trigger conditions are then displayed in the trigger list.
10.
Press the Save button to store the changes in the poll groups.
11.5.6 Modbus Protocol Analyzer
When connected to a device a protocol analyzer is available for each Modbus port. The protocol analyzer can be found in the Modbus Management dialog. On every Modbus port a
protocol analyzer tab is available. Figure 197 shows the Modbus protocol analyzer
Version 4.0
The status on the right hand side of the dialog shows, if the device is connected or if the protocol analyzer is stopped or started. When connected to a device, the protocol analyzer can be started by pressing the Start Protocol button. This starts the protocol analyzer in the device. Every time a transmission is made on the Modbus port, the transmission is displayed in the list. Additionally the protocol data is stored in the device in a rotating log file. The protocol log can hold up to 40 kB of protocol data. So also when the Configurator was not
LOYTEC electronics GmbH
L-INX User Manual 253 LOYTEC running for an interesting time, the protocol data can be loaded from the device using the
Load From Device button. The protocol data can be stored as CSV file using the Save button, with the Clear button, the shown protocol is deleted.
Figure 197: Modbus protocol analyzer.
Figure 198 shows a typical protocol analyzer output for the Modbus TCP port. It shows the
following information for TCP:
Seq.
: sequence number, which is automatically created in the device. This number is unique for one port.
Timestamp: transmission time.
Frame Type: ‗TCP‘ or ‗Damaged‘ when something happened with the frame.
Dir.
: direction. Either SND (send) or RCV (receive)
Trans ID: Transaction ID
Prot ID: Protocol ID
Unit ID: Unit ID
Length: Payload length of the data frame
Payload: Payload in hexadecimal numbers (this column cannot be used for sorting).
Version 4.0
Figure 198: Typical protocol analyzer output for Modbus TCP port.
Figure 199 shows a typical protocol analyzer output for the Modbus RS-485 port. It shows
the following information for RS-485:
Seq.
: sequence number, which is automatically created in the device. This number is unique for one port.
LOYTEC electronics GmbH
L-INX User Manual 254 LOYTEC
Timestamp: transmission time.
Frame Type: RTU, ASCII or Damaged when something happened with the frame.
Dir.
: direction. Either SND (send) or RCV (receive)
Addr.: Slave address
CRC: CRC of the transmission
Length: Payload length of the data frame
Payload: Payload in hexadecimal numbers (this column cannot be used for sorting)
Figure 199: Typical protocol analyzer output for Modbus RS-485 port.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
12 IEC 61131
255 LOYTEC
To design the IEC61131 program which should run on the L-INX device, the graphical programming tool logiCAD is required. The tool allows creating IEC61131 programs using various IEC61131 programming languages. It offers additional features downloading and debugging of the created program.
In addition to logiCAD, the L-INX Configurator necessary to create an appropriate data point configuration in the automation server. The usage of logiCAD itself is beyond the scope of this manual. Please refer to the logiCAD online help in case of additional questions.
12.1 Overview
The PLC in the L-INX device is intended to perform IEC61131 programs operating on
IEC61131 data points. The operating principle is to connect IEC61131 data points to data
points derived from CEA-709, BACnet or LIOB network. Figure 200 depicts the usage of
data points for IEC61131 programs at the example of using CEA-709 network variables.
Input NVs DP DP Output NVs
CEA-709 variables
IEC61131 variables
IEC61131 program
IEC61131 variables
CEA-709 variables
Figure 200 Usage of data points.
12.2 Installing logiCAD
For developing IEC61131 programs with logiCAD the following components must be installed:
1.
Hardlock driver for USB keys. For the logiCAD license, an Aladdin USB key may be used. If no driver for this type of keys is installed on the PC and the software is licensed via the USB key, install this driver first. This driver is not required if a logiCAD softlock license is used.
2.
L-logiCAD setup package. This package installs the logiCAD software, which is needed to design PLC programs for the L-INX device.
3.
L-INX Configurator. This software is required to configure the L-INX device to provide the necessary data points to the PLC and integrate the device into the network.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 256 LOYTEC
The L-logiCAD installer installs the IEC61131 programming environment logiCAD and all
L-INX related software packages. These packages include the template project for the
LINX, the required software to build IEC61131 programs for the L-INX device, and required extensions to interface to CEA709 networks. Follow the instructions of the installer to install logiCAD for the LINX-110.
The language for the logiCAD user interfaces can be set to German or English using the administration folder of the logiCAD control center. The logiCAD control center can be started from the Windows start menu.
The license to run a copy of logiCAD on any PC can be stored on a USB hardlock of type
‗Aladdin‘. If no driver for this type of hardlock is already installed on the PC, install the driver provided on the LOYTEC website. If the driver installation failed, or the USB key
was not detected or connected, the window shown in Figure 201 will be shown when
logiCAD is started. The USB key was correctly detected if it is listened in the Microsoft
Windows device manager as shown in Figure 202.
If a softlock license should be used instead of the USB key, press the button Download
Softlock License , enter the license data provided with the product into the web site form, download the license file (.lic file) and install it using the Install Softlock License button.
Figure 201: logiCAD Product Activation
Note:
Figure 202: USB key driver logiCAD checks frequently if the USB key is present. When unplugging the USB key, even if logiCAD was successfully started, all major features are automatically disabled. But there is no additional message for the user!
12.3 IEC61131 Project Files
In the L-INX Configurator select the Project Files tab to attach an IEC61131 program and
a logiCAD project to the L-INX project. The tab is shown in Figure 203.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 257 LOYTEC
If there is an IEC61131 program attached to the project, every time a new configuration is downloaded to the device, the L-INX Configurator asks, if the attached program should be downloaded as well. This way, no logiCAD is required to download a suitable IEC61131 program in a separate step. The project designed in the L-INX Configurator can hold all necessary information to set up a running device:
IEC61131 data point configuration,
Data point configuration in the LINX,
Required connections,
IEC61131 program.
The logiCAD project directory can also be attached to the L-INX configuration file, in order to include the logiCAD project sources from which the program was compiled.
Figure 203: IEC61131 Project Files.
To attach an IEC61131 program or a logiCAD project select the file/folder to attach. The selected data will be attached automatically the project. It can be restored to disk by pressing the Restore to Disk button. During the development process the attached data may change several times. To update the attached data, located on the before provided path, press the Refresh button.
Every time a logiCAD project is successfully compiled, the file MBRTCode.so, the compiled IEC61131 program, is copied to the public directory of the device resource for which the program was compiled. Select this file to attach it to the project of the
Configurator. Note that the time and date of the file indicates the time of the last code generation. If logiCAD is not able to build a new program, the old file will not be deleted.
To help you find the correct program file, set the path to the logiCAD project in the project settings dialog (on the tab called logiCAD). The project will be scanned for device resources and the available devices will be listed in the dropdown box called Device
Config . Select the desired device and press the button Attach Program to automatically attach the correct MBRTCode.so file.
12.4 Working with logiCAD
A short, straight forward introduction in logiCAD was already provided in the Quick Start
Section (Section 2.5). This section provides all necessary background information how to
use the L-INX with logiCAD.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 258 LOYTEC
To be able to use the L-INX with logiCAD, a predefined project template for the L-INX must be used. Hence, when creating a new project, select the project template ―Project for
LINX-110‖, see Figure 14. For additional information how to create, delete and manage
projects please refer to the logiCAD online help.
Version 4.0
Figure 204: L-INX specific extensions
Figure 204 shows the standard project for the L-INX including all LINX-specific extensions
for logiCAD. It shows the structure window showing the project structure on the left, an empty working area top right and the Error-state viewer on the bottom right side.
The structure window offers interfaces to the following features:
1.
The folder Functionplans holds all the program types created within logiCAD.
‗Plan_1‘ is the default plan to start with.
2.
The folder LOYTEC/LINX-110 represents the LINX-110 device. The folder
LOYTEC represents a configuration containing one LINX-110 resource; please refer to the logiCAD online help for details. To run a program, located in the folder
Functionplans , a program instance of the corresponding function plan must be created.
In the standard LINX-110 template a program instance of the ‗Plan_1‘ is already defined. To be able to transfer IEC61131 variables from the L-INX device to the
IEC61131 program a global variables object within the LINX-110 folder is required,
see Section 12.4.1 for details.
3.
LogiCAD operates on variable types standardized in the IEC61131 standard. Look for
―Elementary and Generic Data Types‖ within the logiCAD online help to get information about the available data types. For those L-INX devices, which are intended to operate on structured NVs, appropriate type definitions for the NVs are required. These definitions are inside the folder CEA-709_Types . Additional NVs must be converted to data types that can be processed by logiCAD. Therefore
Technology Converters are supplied with the L-INX project, which perform this
conversion. See Section 12.4.3 for details.
LOYTEC electronics GmbH
L-INX User Manual 259 LOYTEC
4.
For designing programs that support the force update functionality (see Section 12.6.1),
or designing user-defined Technology Mapper
(see Section 12.6.2) additional function
blocks are required. These blocks are located within the Loytec_Support directory.
All LINX-specific add-ons are provided using function blocks. Hence, in the following, all samples are based on designs using function blocks.
12.4.1 Managing Variables
On a function plan, three basic types of variables may be created using the tabs shown below the function plan sheet:
VAR: Variables created on this tab will be visible only to the logic designed on this group of sheets. It will not be accessible to any other programs or to any function blocks which are used in this program. It is similar to a ‗static‘ variable declaration in a
C code function.
VAR GLOBAL: Variables declared here will be accessible to the entire program, including any function blocks which are called by the program. Function blocks which need to reference this variable need to have a suitable declaration of an external variable (see next point). This declaration is similar to a ‗static‘ declaration of a C variable outside a function, which will be visible to all functions inside the C code module, but not visible to other modules.
VAR EXTERNAL: Variables declared in this list will be treated as open references to a global variable which exists somewhere in the scope of the device on which the program will be executed. This means that a global variable needs to be declared on the device resource, which will be available to all programs running on the device. If the physical address parameter of the variable is set to %I, %O, or %M, the variable will be handed down to the I/O driver of the LINX-110 for processing. If a suitable IEC61131 variable exists in the data point configuration of the device, its value will be forwarded by the I/O driver between the PLC variable and the data point. If no physical address is set, the variable will only be visible to the PLC programs but not to the I/O driver, which may be used to exchange data between PLC tasks.
The basic data flow between the CEA709 network and the PLC program is as follows:
Input NVs DP
IEC61131 variables
IEC61131 program
DP
IEC61131 variables
Output NVs
Figure 205: Connecting IEC61131 variables
The place where global variables are created on the device is shown below.
Version 4.0
Figure 206: Global Variables Object
LOYTEC electronics GmbH
L-INX User Manual 260 LOYTEC
When starting a new project, no global variables object is available; it must be created before compiling the IEC61131 application. The global variables object can be created automatically or manually, depending on the different workflows, please refer to Section
Figure 207: Variables defined in global variables object
Figure 207 shows the contents of a sample global variables object. As shown a global
variable is defined by the fields name , declaration and phys.addr.
.
Name:
The name of a global variable must be unique. The name is used from the IO driver to identify the global variable and from the LINX Configurator to generate the corresponding IEC61131 data points.
Declaration:
Here the type of the global variable is defined.
Phys.Addr.:
The IO driver needs to know the data flow direction to be able to update variables.
The direction is defined by adding %I for an input variable, %O for an output variable and %M for a marker (input and output). If the address is empty, the I/O driver will not handle the variable, but it may still be used by the tasks running on the device.
Only ASCII characters can be used for naming the global variables. Important:
12.4.2 Build and Download the IEC61131 Program
IEC61131 programs, designed using logiCAD, must be cross compiled in order to run on the LINX-110 device. The prerequisite to compile an IEC61131 program are as follows:
A program instance with associated program type
A corresponding global variables object
Right click on the LINX-110 resource, see Figure 206, and select Code Generation. Please
refer to the logiCAD online help for the meaning of the options. Take care about the option
breakpoint support, see section 12.4.5 for details.
Version 4.0
After successfully finished code generation, the IEC61131 application can be downloaded to the LINX-110. Right click on the LINX-110 resource and select download.
The IEC61131 program can be downloaded to the LINX-110 device via TCP/IP, CEA-709 and RS232.
TCP/IP:
Enter the IP address of the LINX-110 device. Do not change the default communication port (2048). This is the easiest and fastest way to connect to the device.
CEA-709:
Select the network interface to use and fill out all other fields, see Figure 208. Alternatively,
select the network interface and press Auto-detect via Service-Pin. Then press the service
LOYTEC electronics GmbH
L-INX User Manual 261 LOYTEC pin on the LINX-110 device. Note that this connection method requires an installed
LOYTEC network interface.
Figure 208: Connect via CEA-709
Important: To be able to communicate with the LINX-110 device via CEA709 the LINX-110 must be commissioned.
RS232:
To connect via RS232 select LOYTEC RS232 as Driver and LOYTEC as transmission protocol. All other values are set correctly per default.
12.4.3 Usage of NVs, Technology Converters
To used CEA-709 variables the content of the NVs must be converted to IEC61131 compliant data types. Look for ―Elementary and Generic Data Types‖ within the logiCAD online help to get information about the available data types. Technology Converters are used to perform the transformation from CEA-709 data types to IEC61131 data types. All
Technology Converters are summarized in the subfolder CEA709_Conv located in the
StandardLibs folder.
Version 4.0
Depending on the type of the NV there are three different ways to use the NV within
IEC61131 programs:
Simple NVs that hold only one scalar value, e.g. SNVT_amp:
Those kinds on NVs are represented as IEC61131 REAL values within logiCAD.
There is no additional conversion necessary. Figure 216 shows an example
program for scalar data types.
Simple NVs based on an enumeration, e.g. SNVT_date_day:
The active identifier of the enumeration is represented as Boolean value. When using NVs based on enumerations, Enumeration Converters are used to identify the current state. There are two kinds of Enumeration Converters. First, the
Enumeration Converters that convert the enumeration types to Boolean types, grouped in the folder Convert from CEA709_Enums. Second, the Enumeration
Converters that converts several Boolean inputs to an enumeration type, grouped in the folder Convert to CEA709_Enums.
Structured NVs that consists of a number of fields, e.g. SNVT_switch:
LOYTEC electronics GmbH
L-INX User Manual 262 LOYTEC
On structured NVs two tasks must be performed by the Technology Converters.
First the structure of the NV is mapped to IEC61131 conform data types. Second, if necessary scaling factors are applied. Similar to the Enumeration Converters, the
Technology Converters are split up into two subfolders. The first one, which converts the NV into IEC61131 compliant data types, is located in the folder
From_CEA709_Types. Technology Converters to set up NVs based on IEC61131 data types are grouped in the folder To_CEA709_Types.
Figure 209 shows the three possibilities how to use NVs within an IEC61131 program.
Figure 209: Usage of NVs
If a structured NV comprises enumerations types, these enumerations are not split up by the
Technology Converter. To get the value of the enumeration, connect an Enumeration
Converter to the corresponding output of the Technology Converter.
For every Technology Converter and Enumeration Converter an online help window, displaying the interface description is available. Select the Technology Converter and press
F1 to get the interface description.
12.4.4 IEC61131 Program Cycle Time
IEC61131 programs are performed in a periodical manner. IEC61131 tasks are used do
control the execution of an IEC61131 program. As shown in Figure 206 several default
tasks are defined within the template project. Right click on the clock symbol and select properties to change the cycle time of the task.
As described in section 12.4 a program instance is required to execute the IEC61131
program. The cycle time of the IEC61131 program is controlled by the task assigned to the program instance. In order to change the cycle time right click on the program instance and select properties. In the upcoming window the task assignment for the selected program
type can be changed, see Figure 210.
Version 4.0
Figure 210: Task assignment
Please take care when defining names for the tasks. The names displayed in the project view are symbolic names, they do not correspond to the settings for the cycle time, even if the
LINX-110 template project use the configured cycle time as task name.
LOYTEC electronics GmbH
L-INX User Manual 263 LOYTEC
12.4.5 CPU Overload
Several conditions affect the CPU utilization of the IEC61131 program. As a result it is not possible to predict the system load caused by the IEC61131 program. E.g. the following parameters are of particular importance when designing IEC61131 programs:
Number of inputs and outputs handled by the I/O driver
Complexity of the running IEC61131 program
Number of simultaneously running program instances on one LINX-110 device
Cycle time of IEC61131 programs
logiCAD breakpoint support and force-able code enabled or disabled
The developer of the IEC61131 program is able to check the current system load within the
Web UI, see section 4.2.16. To get a rough estimate of the CPU load investigate the PLC-
LED. Every time, the system load increases 80% for a certain period of time, the PLC-LED switches to red until the system load goes below 80%.
In case of CPU overload, the IEC61131 program may not be able to finish its work within the defined cycle time. Adapt the program in order to reduce the total system load below
80%. Here are a few tips to keep the CPU load down:
Increase the cycle time, so that the task may finish in time before the next cycle start is scheduled. The PLC kernel will always schedule the next run at an absolute time, no matter how long the previous run took, in order to compensate for irregular execution times and keep a steady cycle time if possible.
Reduce the number of I/O variables, to reduce the load caused by exchanging data between the PLC program and the data point system.
Reduce the number of independent tasks and try to place as much functionality as possible into one task. Every running task will call the I/O driver for new inputs and outputs independently, therefore two tasks running at a 1s cycle time each will cause twice the I/O load of one task running at 2s cycle time.
Take special care about the complexity of function blocks which are used a lot.
Bad performance of one such block may dramatically increase CPU load if it needs to be calculated several hundred times in one cycle.
Try to disable breakpoint support and force-able code when generating code for the target, to get the most efficient PLC code out of your logic.
For complex designs, it may be possible to add a state machine using SFC elements and enable/disable large parts of the logic based on the current state of operation.
Whenever a function does not need to calculate new output values under certain conditions, use the built-in EN input of the block to disable execution and thus reduce the required CPU time, instead of adding your own ‗Enable‘ input which causes the logic to ‗behave‘ as if it would be disabled, while it is actually calculated every cycle. This is similar to power saving methods used in modern electronic devices. Parts which are not required are put into a low power mode instead of keeping them running in an unproductive state.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 264 LOYTEC
12.5 Workflows for the LINX
For designing programs with the L-INX two standard workflows are suggested. In the first
workflow, described in Section 6.4.2, all processes are based on logiCAD. The second
workflow, described in Section 6.4.3, is based on information gathered from the L-INX
Configurator. Both workflows assist the user to set up a running IEC61131 program using a network connection.
12.5.1 Starting with logiCAD
This section introduces how to develop a new IEC61131 program starting up from scratch
using logiCAD. Figure 211 shows the necessary steps to perform.
START
Create IEC61131 program with logiCAD
Generate and export IEC61131 variables
Start LINX-110 Configuration Utility
Import IEC61131 variables
Select Generate and Connect NVs <->
IEC61131 Variables
Download configuration to device
Section 6.6.4
DONE
Figure 211: Starting with logiCAD
After creating a new project for the L-INX and opening the Functionplan Plan_1 an empty
input area is shown, similar to Figure 212.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 265 LOYTEC
Figure 212: Start new function plan
The dark grey areas on the left and right side are intended to place the input and output variables, the light grey area is used to place the functional blocks.
As described above, global variables are used to interface IEC61131 data points on the
LINX-110 device. As assumed for the current workflow, the IEC61131 data points are created on information based on the global variables exported from logiCAD. Hence, for designing the program, external variables are used during the design phase. To create a new variable select the VAR_EXTERNAL tab, right click in the declaration area and select
―New‖, as shown in Figure 213.
Version 4.0
Figure 213: New external variable
In the upcoming dialog the name and the type declaration of the variable must be specified.
The type declaration can be done directly by prompting the type into the declaration field,
LOYTEC electronics GmbH
L-INX User Manual 266 LOYTEC by selecting the type from the pull-down menu or by drag&drop of a specific type from the
project tree, see Figure 214. Finally, the new variable is added by pressing the Add button.
Figure 214: External variable type declaration
The created variable is added to the declaration area and placed to the drawing area by drag&drop. At this time the direction of the external variable is not defined, it can be used as input as well as output variable.
Version 4.0
Figure 215: Drag&drop external variable to drawing area
Please take care to use an external variable only as input OR output. After adding the external variables to the drawing area, function blocks to perform the desired actions, see
Figure 216 for a sample configuration.
LOYTEC electronics GmbH
L-INX User Manual 267 LOYTEC
Figure 216: Use external variables
The Functionplan Plan_1 represents now a simple program. It adds a defined value to the value of the input variable and sends the result to the output variable.
Add all expected functionality to the Plan_1 or use different Functionplans to split up the expected functionality into smaller pieces. But take care about the name and type declaration of external variables when using more than one Functionplan. All external variables with the same name refer to the same global variable.
After adding all functionality, global variables matching the requirements of the defined external variables, must be generated. A tool automatically performs the process of generating the global variables object and the required global variables.
Version 4.0
Figure 217: Auto-create global variables
To start the creation of global variables, based on external variables, right click the LINX-
110 device and select Global Variables
Generate. Then the selected LINX-110 resource
there are more Functionplans than the predefined Plan_1 appropriate program instances for these plans must be added to the resource before creating the global variables. Anyway, only Functionplans referred from program instances are executed.
LOYTEC electronics GmbH
L-INX User Manual 268 LOYTEC
Figure 218: Created global variables object
Now there is a global variables object called IEC61131 Variables available, containing all global representations of the external variables defined before. The error-state viewer
reports all processed program instances and added variables, see Figure 218 for details.
The global variables are crated based on the following rules:
The direction of the variable is determined based on the graphical representation,
Version 4.0
Figure 219: Direction of global variables
Every external variable connected on the right terminal results in a global input variable. External variables connected on the left terminal or on both sides results in a global output variable. Variables connected on both sides can either be used
for the force update feature (see section 12.6.1) or as marker (see section 12.6.4).
As the tool can not distinguish between these two possibilities, per default a global output variable is created.
If there is already a global variables object, only new variables are added. In case of external variables using the same name as an already existing global variable, the new definition is used and a warning is printed in the error-state viewer.
In case of two Functionplans, each referring to a global variable with the same name but a different type, the creation process is stopped and an error is printed in the error-state viewer.
Now the IEC61131 program is ready to compile and download, refer to section 12.4.2 for
details.
Based on the above created global variables corresponding IEC61131 data points are created on the LINX-110. All defined global variables can be exported to a CSV-file. To export all global variables associated with the selected LINX-110 resource, right click on
the LINX-110 resource and select Global Variables -> Export, see Figure 220. All exported
variables are placed in one CSV-file, the name of the file is generated based on the
LOYTEC electronics GmbH
L-INX User Manual 269 LOYTEC configuration and resource name. The export file is located in the base directory of the currently opened project. The result of the export process is displayed in the Error-state viewer and the generated file is added to the project view.
Figure 220: Export global variables
Open the LINX Configurator to import the created CSV-file. Right click on the IEC61131 folder, select Import IEC61131 CSV, navigate to the project directory and select the file
LOYTEC_LINX-110.csv, see Figure 221.
Version 4.0
Figure 221: Import IEC61131 variables
LOYTEC electronics GmbH
L-INX User Manual 270 LOYTEC
The tool starts importing the CSV file and finally reports the results of the import process.
For the import process the following rules are applied:
New variables are added
Variables with same name and type are ignored
If there are variables with the same name but different type or direction, the variable to import is ignored and a warning is added to the import log.
The name of the folder to import the new variables corresponds to the name of the global
variables object. Figure 222 shows the result of the import process.
Figure 222: Connect IEC61131 variables
To create the appropriate CEA709 data points for all imported IEC61131 variables select the IEC61131 Variables folder and press the button Generate and Connect NV <->
IEC61131 variable from folder. Check the log output for errors and finally download the
configuration to the LINX-110 device. See chapter 6 for more information about the LINX
Configurator.
After rebooting the LINX-110 device the IEC61131 program is up and running. Check the
PLC LED.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
12.5.2 Based on Network Information
271
START
Start the Configurator
Scan network variables
Section 6.7.2
Select NVs and use on device
Section 6.7.5
Select Generate and Connect NVs
Download configuration to device
Section 6.7.9
Export IEC61131 variables
LOYTEC
Start logiCAD
Import global Variables
Use (Drag&Drop) global variables in IEC61131 program
DONE
Figure 223: Start with network based information
In opposite to the workflow presented before, the data points used for the IEC61131
program are not derived form logiCAD but from the network side, refer to Figure 223.
Refer to section 6.7.2 about additional information how to gather information from the
network.
It is assumed that there are already CEA-709 data points available. The corresponding
IEC61131 Variables are created by selecting the CEA709->Datapoints folder and pressing
the Generate and Connect NV <-> IEC61131 variable from folder button, see Figure 224.
Check the log output for errors and verify that all required IEC61131 variables were created. Finally download the new configuration into the LINX-110 device.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 272 LOYTEC
Figure 224: Create IEC61131 variables
In order to use the IEC61131 data points within logiCAD corresponding global variables
must be created in logiCAD. Thus, see Figure 225, right click on the IEC61131 folder and
select Export IEC61131 CSV … . Store the select name and location for the export file and press Save to start the export process.
Figure 225: Export IEC61131 variables
Start logiCAD and create a new project for the LINX-110. First of all the global variables object is created is created. To import the global variables right click the LINX-110
resource and select Global Variables -> Import, see Figure 226. Use the upcoming open file
dialog to select the file exported from the LINX Configurator. The result of the import process is summarized in the error-state viewer.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 273 LOYTEC
Version 4.0
Figure 226: Import IEC61131 variables
For the import process the following rules are applied:
The name of the global variables object is supplied by the import file. If there is no global variables object it is created. If there is already a suitable global variables object, the existing variables are saved.
There is already a suitable global variables object: If there is an old and new variable with identical name, the type of the variable is checked. In case of a type mismatch of the old and new variable, the old one is discarded and the new one is imported. Additional a warning is printed on the Error-state viewer.
The name of the global variables object represents the folder name in the LINX
Configurator.
After importing the global variables the Functionplan Plan_1 and the global variables object
IEC61131 Variables are opened. To use the imported variables simply drag&drop the
required global variable on to the Functionplan, see Figure 227. The external variables
described in the previous section are automatically created when adding the global variable to the Funtionplan.
LOYTEC electronics GmbH
L-INX User Manual 274 LOYTEC
Figure 227: Adding global variables to Functionplans
After adding function blocks that perform the expected work, the IEC61131 program is
ready to compile and download, refer to section 12.4.2 for details.
12.5.3 Pre-compiled IEC61131 Program
In opposite to the last two chapters it is assumed that there are already some components finished, hence starting up from scratch is not suitable. Second, there is the possibility to have an already defined IEC61131 program or an already fixed network interface.
Starting with an already precompiled IEC61131 program results in a similar workflow as
presented in section 6.4.2. The difference is that all logiCAD related tasks are missing. As
the IEC61131 program is compiled, the name of the IEC61131 data points is already fixed.
The definitions for the data points must be available either in form of a CSV-file to import to the LINX Configurator or as prepared project for the LINX-110 configuration tool. If the network interface for the LINX-110 was not already defined the LINX Configurator can be used to generate and connect the CEA-709 data points.
Additional, there is the possibility that also the CEA-709 data points are already fixed or a user defined interface is necessary. Then the developer has to connect the IEC61131 data
points to the corresponding CEA709 data points by himself, see section 6.10 for details.
Finally, after downloading the configuration and rebooting the LINX-110, the IEC61131 program can be downloaded to the LINX-110 via the WEB UI or the LINX Configurator.
After a final reboot the LINX-110 loads and executes the IEC61131 program.
12.6 Additional features
12.6.1 Force Update Functionality
Per default the IEC61131 program only sends updates on changed output values. Every program cycle the input values are fetched, the IEC61131 program is executed and the calculated values are sent to the output driver. If the old values are identically with the new one no updates are sent to the IEC61131 data points. As a result no update is sent to the network.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 275 LOYTEC
For some applications, e.g. for a scene controller, it is necessary to send an update on request. E.g. every time the input value is updated, the output value is forwarded to the network, regardless if the value of the output value was changed or not.
For implementing this feature, special vendor blocks are available. First it is necessary to check if there was an update on a selected input within the last execution cycle of the running IEC61131 program. That functionality is offered by the function block Update
Notify located in the StandardLibs->Loytec_Support folder. Second, an output must be forced to send an update even if the value was not changed. The function block Force
Update is used for that functionality, it is located in the StandardLibs->Loytec_Support..
Important:
Figure 228: Force update
Figure 228 depicts how to use the force updated functionality. Beside the part of the
IEC61131 program that defines the tasks to perform, lower half of Figure 228, additional
logic for the force update functionality is required. The global input variable that is monitored for changes is connected to the Update Notification function block. As a result, the Boolean output Updated goes to TRUE for one program cycle if the value of the connected variable was updated since the last cycle start. To force the IO driver do send an update, connect the global output variable to update to the Force Update block. Hence, every time the Update input of the Force Update block is TRUE, an update of the connected global output variable is sent at the end of the program cycle.
Every global variable connected to the update notification or force update block, must be connected via the right terminal.
12.6.2 Using UNVT variables
Similar to the predefined CEA709 data types and the technology converter functions, user defined network variable data types can be used. The LINX Configurator supports the developer to generate the type definitions needed for UNVTs and enumerations based on
L ON M ARK resources files.
Start the L-INX Configurator tool, select the menu Tools, and the command Export NV resource file. Select the resource file to export, structured text as format and export the file to a location of your choice.
To import the created type definition file into logiCAD, add a new library to the project.
Right click on the created library, select Export/Import and Start ST-Import. Select the file to import and check the error-state viewer for the results of the import process.
Using the newly created data types, suitable technology converter function blocks can be created. For each UNVT type, create a normal function block to convert an input of the
UNVT type to a number of standard IEC61131 data types and vice versa. You may look at the technology converter blocks for SNVT types which are provided by LOYTEC, to get ideas how to implement your own converter functions.
12.6.3 Create Your Own Data Type
For special applications, custom IEC61131 compliant data types may be created by the user, which do not correspond to any CEA709 network type but should still be available as a data point on the LINX-110 device, in order to access the data point from the web interface or
XML interface and as a possibility to make variables of such custom data types persistent.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 276 LOYTEC
Most of the IEC61131 data types may be used as global variables on the device and the L-
INX Configurator will be able to create a suitable register data point for the IEC61131 data type. Supported data types include custom enumeration types (a multi-state register with the required states will be created automatically), strings (a string data point with a maximum length of 128 characters will be built), and simple arrays.
While the software will be able to automatically determine the required data point size for simple arrays (like ARRAY [1..16] OF INT) and create a suitable register data point during the IEC61131 variable import, the data size of custom structures cannot be determined automatically at the moment, so the L-INX Configurator does not know how to create a suitable user data point. As a workaround, the type name must contain the desired size of the data point in bytes, for example: MyStructuredType(UT16) will tell the L-INX
Configurator to create an IEC61131 register of type ‗user‘ with a length of 16 bytes, to hold the data for the IEC61131 structure defined in the logiCAD program.
12.6.4 Using Persistent Data Points and Markers
Persistent data points are data points on the LINX-110 device that hold their value even on power loss. There is no difference in handling global variables connected to persistent data points or to non-persistent data points. Global variables connected to persistent data points are marked with retain attribute in logiCAD and with the persistent flag in the LINX-110 configuration tool.
Global input variables marked as persistent, supply the IEC61131 program every time with the last received, valid data, even after a power failure. To set an input variable as persistent in logiCAD, open the global variables object containing the appropriate variable, double click the variable, set the retain check and press the update button. Now export the global variables and import them to the LINX-110 configuration tool. After downloading the new
IEC61131 point configuration to the LINX-110 the data point is set to persistent. Setting the data point persistent in the LINX-110 configuration tool, export the data points and import them to logiCAD is also possible.
Global variables declared as marker can be used as input and output variable in IEC61131 programs. LogiCAD is not able to distinguish markers from global output variables used in
combination with the force update feature, see Figure 228. As a result it is not possible to
create a global variables object holding markers automatically. The procedure as described
in section 6.4.2 is not able to decide when to create an output variable or a marker. Markers
must be created manually by adding them to the global variables object and setting the physical address to %M.
12.6.5 LINX-110 System Registers, System Time
LINX-110 System registers, such as the System time or the CPU load, can be used within
IEC61131 programs. Therefore, for each system input variable, a global input variable of type UDINT may be created within the IEC61131 program. Then, connections to the appropriate system registers are created manually with the LINX-110 Configurator (see
To use the system time within the IEC61131 program, connect the AtoDT converter
(located in the StandardLibs->IEC61131-3_ (EXT) folder) to the global input variable that receives the system time.
12.6.6 Code Protection
There are 4 data points used for code protection. These data points, in combination with an adapted IEC61131 program, can be used to protect your 61131-Program Intellectual
Property. Please contact LOYTEC sales for further information.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 277
13 Operating Interfaces
LOYTEC
13.1 Common Interface
13.1.1 Schedule and Calendar XML Files
The daily schedule and calendar pattern configuration can be changed at run-time over the
Web UI or the network. An alternative way to change that configuration is to download a schedule and calendar XML file via FTP onto the device. After the file has been downloaded, the new configuration becomes effective immediately. The device does not need to be rebooted. The files are located in
/tmp/uid/sched/ UID .xml
/tmp/uid/cal/ UID .xml
The UID is the unique ID of the data point. The UID can be obtained from the ID column in
the data point list as shown in Figure 148. A schedule data point with UID 107C would
result in the schedule XML file ‗ /tmp/uid/sched/107C.xml
‘. The UID remains constant for the life time of the data point even when the name or description is changed.
The content of the XML file must be compliant to the scheduleCfg schema. This schema can be found at the LOYTEC Web site. The XML documents can refer to the target namespace http://www.loytec.com/xsd/scheduleCfg/1.0/
13.1.2 Trend Log CSV File
The CSV file format for a trend log and the location of those files are defined in this section. The trend log CSV files are accessible either via their UID only, or in combination with contents of the trend log object name. The files are located in
/tmp/uid/trend/ UID .csv
/data/trend/ Datapointname _ UID .csv
The UID is the unique ID of the data point. The UID can be obtained from the ID column in
the data point list as shown in Figure 148. For a more user-friendly listing of the files, the
Datapointname contains the trend log‘s object name. It is truncated after 23 ASCII characters to fit the requirements of the file system. A trend CSV file for the trend object
‗trend0‘ and the UID ‗107C‘ would result in the CSV file
‗ /data/trend/trend0_107C.csv
‘. The UID remains constant for the life time of the object even when the name is changed.
Version 4.0
The CSV file format for a trend log is defined in this section. The CSV file starts with a header, containing at least the first line, which specifies the CSV format (log_csv_ver). The current version is 2. The next line contains the field log_device. It has trailing fields that specify the vendor, product code, firmware version and device ID string. The Device ID
String can be one of the following: (IP) 192.168.24.100, (BACnet Device) 224100, (CEA-
709 NID) NID.
LOYTEC electronics GmbH
L-INX User Manual 278 LOYTEC
F
G
…
…
Column Field
A Sequence Number
B
C
D
E
Source
Error/Time
Change/Log
Status
Date/Time
The log_info line specifies the fields UID and name of the trend log object. The line log_create has two fields specifying the date and time when this CSV log was generated.
The line log_capacity has two fields: the current number of log entries in the file and the log capacity.
Following are one or more lines of log_item. Each line specifies a trended data point. The first field is the index, the second the ID of the logged data point, the third the data point name. The data point name can be augmented by engineering units in square brackets. Log entries in the CSV refer to the item index to identify the data point, for which the entry was logged.
#log_csv_ver,2
#log_device;LOYTEC; Product Code ; Firmware Version ; Device ID String;Serial No
#log_info; Log-ID ; Log Name
#log_create; YYY-MM-DD ; HH:MM:SS
#log_capacity; filled ; capacity
#log_item; index ; UID ; data point name [ units ]
After those lines any number of comment lines starting with a hash character ‗#‘ are allowed. One line contains the column headings. Lines that are not comments specify one log record per line, using the column information as described below. The columns are separated by commas ‗,‘ or semi-colons ‗;‘. If commas are used as a separator, the decimal point must be a point ‗.‘. If semi-colons are used, the decimal point must be a comma ‗,‘.
Record Type
Example
50
0
2
1
Description
The log record sequence number. This is the monotonously increasing sequence number, which is unique for each log record.
Data point source identifier. Indexes into logger_entry header. For value lines in a multi-column CSV, this field indexes the first column, which has a value. For the
ERROR record type, the field indexes the data source that caused the error. For LOGSTATE, TIMECHANGE records this field is not applicable and set to 255.
The record type: LOGSTATE (0), BOOL (1), REAL
(2), ENUM (3), UNSIGNED (4), SIGNED (5), NULL
(7), ERROR (8), TIMECHANGE (9)
This field is valid for records of type ERROR,
TIMECHANGE, and LOGSTATUS.
Value 0
Value 1
…
Value n – 1
2007-11-02 15:34:22
24,5
200
5000
The date/time of the log record. This is in the format
YYYY-MM-DD HH:MM:SS.
Logged value from source 0 or empty
Logged value from source 1 or empty
Logged value from source
Table 13: Columns of the Trend Log CSV File. n – 1 or empty
There are as many value columns as value sources specified in the header. If at a given date/time more values are logged, all of them appear in the same line. If at that given time some sources did not log values, those columns are left empty. The ―Source‖ column in a multi-value CSV refers to the first data source that supplied a value in a given line.
13.1.3 Alarm Log CSV File
The historical alarm logs are also accessible as CSV-formatted files. The alarm log CSV files are accessible either via their UID only, or in combination with contents of the alarm log object name. The files are located in
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 279 LOYTEC
/tmp/uid/allog/ UID .csv
/data/allog/ Alarmlogname _ UID .csv
The UID is the unique ID of the alarm log object. The UID can be obtained from the ID column in the data point list of the alarm log folder, similar to obtaining the UID of trend log objects. For a more user-friendly listing of the files, the Alarmlogname contains the alarm log‘s object name. It is truncated after 23 ASCII characters to fit the requirements of the file system. A trend CSV file for the alarm log object ‗alarmlog0‘ and the UID ‗100C‘ would result in the CSV file ‗ /data/allog/alarmlog0_100C.csv
‘. The UID remains constant for the life time of the object even when the name is changed.
The CSV format of the alarm log CSV file is identical to the trend log CSV format as
13.2 CEA-709 Interface
13.2.1 NV Import File
Network variables can be imported to the Configurator software in a CSV file. The format of this file is described in this section.
The first line of the file must contain a comment, starting with a hash character ‗#‘ specifying the format version and import technology:
#dpal_csv_config;Version=1;Technology=CEA709
After that line any number of comment lines starting with the hash character ‗#‘ are allowed.
Lines that are not comments specify one NV per line, using the column information as
described in Table 14. The columns are separated by commas ‗,‘ or semi-colons ‗;‘. Which
separator is used can be configured in the Web UI (see Section 4.2.1).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 280 LOYTEC
Column Field
A SNVT
B
C
F
I
J
G
H
R
S
T
U
D
E
O
P
Q
K
L
M
N
V
W
X
NV index
NV selector
NV name is output flag auth cfg flag auth flag priority cfg flag priority flag service type cfg flag service ack flag polled flag sync
Deviceref programID neuronID
Subnet
Node location str
Device name node self-doc
NV length
NV self-doc
Allocation
Example Description
39
0
1 nvoTemp
1
1
0
1
1
0
0
1
0
1
9000A44850060402
80000000C8C8
2
3
0
DDC
&3.2@0,2
2
@0|4
1
A numeric value of the SNVT (as defined in the SNVT master list). The example value 39 represents a
SNVT_temp.
The NV index in decimal notation of the NV on the network node. Index starts at 0.
The NV selector in decimal notation of the NV on the network node.
The NV programmatic name of the NV on the network node.
Defines if this NV is an output on the network node. ‗1‘ means the NV is an output on the network node.
‗1‘ defines that authentication can be configured for this
NV on the network node.
‗1‘ defines that the NV is authenticated.
‗1‘ defines that the priority can be configured for this
NV on the network node.
‗1‘ defines that the NV is using priority.
‗1‘ defines that the service type can be configured for this NV on the network node.
‗1‘ defines that the NV is using acknowledged service.
‗1‘ defines that the NV is using the polled attribute
‗1‘ defines that the NV is a synchronous NV.
This field is a numeric reference to a device description.
If it is the first occurrence of this reference in the file, the columns defined below must be filled in. Otherwise, they can be left out.
The program ID string of the network device.
The NID of the network device.
The subnet address of the network device. Use ‗0‘ if the device has no subnet address information.
The node address of the network device. Use ‗0‘ if the device has no node address information.
The location string of the network device. Use ‗0‘ if no information is available.
The device name of the network device. Leave this field blank if this information is not available.
Self-documentation string of the device (special characters are escaped)
NV length in bytes
NV self-documentation string (special characters are escaped)
Define, how this NV shall be allocated: external=1
(default) / static=2 / file=3
Table 14: CSV Columns of the NV Import File.
13.2.2 Node Object
The L-INX provides a node object conforming to the L ON M ARK guidelines.
The Node Object accepts the following commands via nviRequest : RQ_NORMAL,
RQ_UPDATE_STATUS, RQ_REPORT_MASK, RQ_ENABLE, RQ_DISABLE,
RQ_UPDATE_ALARM, RQ_CLEAR_ALARM, RQ_RESET, RQ_CLEAR_RESET
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 281 LOYTEC
L ON M ARK alarming is supported via nvoAlarm (SNVT_alarm) and nvoAlarm_2
(SNVT_alarm_2). This allows devices supporting the L ON M ARK alarm notifier profile to receive alarms generated by the device and react with a defined action (e.g., send an email). By supporting both alarm SNVTs, SNVT_alarm and SNVT_alarm_2, legacy and state-of-the-art alarm handling is supported.
nviDateEvent ( SNVT_date_event ), nvoDateResync ( SNVT_switch ): These NVs are part of the standard L ON M ARK node object, if schedulers are used. If not bound, the local calendar is used. If a global calendar shall be used, both of these NVs must be bound to the respective NVs of the global calendar object.
nviTimeSet ( SNVT_time_stamp ): When writing to this NV, the system is set, if the
configure time-source is ―LonMark‖ or ―Auto‖ (see Section 4.2.1). The time value is
interpreted as local time
nvoSystemTemp ( SNVT_temp ): This NV can be used to poll the system temperature of the device. It does not send updates and must be polled.
nvoSupplyVolt ( SNVT_volt ): This NV can be used to poll the supply voltage of the device. It does not send updates and must be polled.
nvoIpAddress ( SNVT_str_asc ): This NV can be used to poll the IP address of the device. It does not send updates.
nciEarthPos ( SNVT_earth_pos ): This configuration property can be used to set the earth position of the device. It has been implemented as an NV to make other devices send that configuration to the device over the network (e.g., from a GPS device).
nviClearStat ( SNVT_switch ): When writing {100.0 1} to this NV, the channel monitor objects‘ statistics data are cleared.
nvoUpTime ( SNVT_elapsed_tm ): This NV contains the elapsed time since the last reboot.
13.2.3 Real-Time Keeper Object
When the scheduler objects are enabled in the project settings, the device includes the standard L ON M ARK real-time keeper object. The Real-Time Keeper Object is used to synchronize the system time of multiple L ON M ARK compliant devices.
The object has the following network variables:
nvoTimeDate ( SNVT_time_stamp ): Propagates the devices current system time and date (local time). It is typically bound to the nviTimeSet input network variable of the node objects of the L ON M ARK compliant devices, which are synchronized with the system time of the device. The update rate of the nvoTimeDate can be configured using the configuration property SCPTupdateRate (default every 60 seconds).
13.2.4 Channel Monitor Object
The Channel Monitor Object functional block is responsible for network monitoring. There is one object for each channel, the device is attached to: The channel monitor object with index 0 corresponds to the FT port of the device, while the object with index 1 corresponds to the IP-852 port of the device. If a port is not available in the current system configuration, the nvoElapsedTime is set to the invalid value and nvoPort is set to 255.
Each object has the following network variables:
nvoPort ( SNVT_count ): Index of port associated with this Channel Monitor Object instance. Port 1 corresponds to the FT port of the device, while port 2 corresponds to the IP-852 port of the device. If the monitored port is not available in a system configuration, the value is 255. This NV is polled only.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 282 LOYTEC
nvoElapsedTime ( SNVT_elapsed_tm ): Time since device powered up or since the statistics for this port where reset. The statistics can be reset with the network variable nviClearStat
in the node object (see Section 13.2.2) or if the node is reset with a
network management command (e.g., while the device is commissioned). If the monitored port is not available in a system configuration, the value is set to the invalid value. The NV is polled only.
nvoAvgPkts (SNVT_count_32): The average number of packets per second received or transmitted via the associated channel since power-up or since the statistics for this port where reset.
nvoIvalBandUtl ( SNVT_lev_cont ): Bandwidth utilization of associated channel during the last interval. For a smooth operation of the CEA-709 segment, the average bandwidth utilization must remain below 50 %.
nvoIvalCrcErr ( SNVT_lev_cont ): Percentage of packets with CRC error received on the associated channel during the last interval.
nvoIvalMissed ( SNVT_lev_cont ): Percentage of packets from the associated channel which could not be processed during the last interval.
nvoIvalPkts ( SNVT_count_32 ): Number of packets received or transmitted via the associated channel during the last interval.
nvoTotalCrcErr ( SNVT_count_32 ): Total number of packets with CRC error received via the associated channel since power-up or since the statistics for this port where reset.
nvoTotalMissed ( SNVT_count_32 ): Total number of packets from the associated channel which could not be processed since power-up or since the statistics for this port where reset.
nvoTotalPkts ( SNVT_count_32 ): Total number of packets received or transmitted via the associated channel since power-up or since the statistics for this port where reset.
nvoMaxBandUtl ( SNVT_lev_cont ): Maximum value of nvoIvalBandUtl since power-up or since the statistics for this port where reset. For a smooth operation of the CEA-709 segment the average bandwidth utilization must remain below 50 %.
nvoMaxCrcErr ( SNVT_lev_cont ): Maximum value of nvoIvalCrcErr since power-up or since the statistics for this port where reset.
nvoMaxMissed ( SNVT_lev_cont ): Maximum value of nvoIvalMissed since power-up or since the statistics for this port where reset.
nvoMaxPkts ( SNVT_count_32 ): Maximum value of nvoIvalPkts since power-up or since the statistics for this port where reset.
nvoIvalMisPre ( SNVT_count_32 ): Number of missed preambles per second on the associated channel measured during the last interval. A missed preamble is detected whenever the link layer receives a preamble which is shorter then the defined preamble length. A large number in this counter is usually due to noise on the channel.
nvoTotalMisPre ( SNVT_count_32 ): Total number of missed preambles per second on the associated channel measured since power-up or since the statistics for this port where reset.
nvoMaxMisPre ( SNVT_count_32 ): Maximum value of nvoIvalMisPre since power-up or since the statistics for this port where reset.
nvoChnlAlarm ( SNVT_switch ): Signals an overload alarm condition of the channel during the last statistic interval. A channel can be overloaded due to one of the following conditions: o
The bandwidth utilization during the last statistic interval ( nvoIvalBandUtl ) exceeded the limit defined by the SCPThighLimit1 (default 70 %) OR
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 283 LOYTEC o The CRC Error Rate during the last statistic interval ( nvoIvalCrcErr ) exceeded the limit defined by the SCPThighLimit1 (default 5 %) OR o
The Missed Packets Rate during the last statistic interval ( nvoIvalMissed ) was not zero OR o The Missed Preamble Rate during the last statistic interval ( nvoIvalMisPre ) exceeded the limit defined by the SCPThighLimit1 (default switched off).
If an overload is detected, the network variable is set to {100, ON}. If no error occurred, it is set to {0, OFF}.
nvoChnlAlarmRat ( SNVT_lev_cont ): Ratio between statistic intervals during which the channel was in overload alarm condition and intervals during which the channel was not in overload alarm condition since power-up or since the statistics for this port where reset.
In addition, each channel monitor object has the following SCPTs:
SCPTifaceDesc: This configuration property contains a human-readable name of the monitored port. Possible values on the device are ―CEA-709‖, ―IP‖, or ―inactive‖.
SCPTmaxSndT: Defines how often output NVs are transmitted. Exceptions are nvoPort, and nvoElapsedTime, which are polled-only.
13.2.5 Calendar Object
When the scheduler objects are enabled in the project settings, the device includes the standard L ON M ARK calendar object.
13.2.6 Scheduler Object
When the scheduler objects are enabled in the project settings, the device includes the configured number of standard L ON M ARK scheduler objects.
13.2.7 Clients Object
When the remote AST object feature is enabled in the project settings, the device includes a proprietary object, which is a container for network variables required to implement the remote object features.
For remote schedulers and calendars, nviSchedLink and nviCalLink NVs are created. For alarm clients, nviAlarm_2 NVs are created.
13.2.8 Gateway/PLC Objects
The device contains eight proprietary Gateway objects. These are containers for all NVs which are configured on the device‘s CEA-709 port. They are intended for grouping NVs.
When static NVs are created, they can be assigned to any of the eight gateway blocks.
When creating dynamic NVs in the LNS-based tool, the NVs should be added to the gateway blocks.
13.3 BACnet Interface
13.3.1 Device Object
The BACnet interface provides one device object as shown in Table 15.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 284 LOYTEC
Version 4.0
Property Identifier
Object_Identifier
Object_Name
Object_Type
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_Version
Location
Description
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Database_Revision
Max_APDU_Length_Accepted
Segmentation_Supported
Max_Segments_Accepted
APDU_Segment_Timeout
APDU_Timeout
Number_Of_APDU_Retries
Max_Master
Max_Info_Frames
System_Status
Device_Address_Binding
Active_COV_Subscriptions
UTC_Offset
Daylight_Savings_Status
Local_Date
Local_Time
Time_Synchronization_Recipients
UTC_Time_Synchronization_Recipiens
Time_Synchronization_Interval
Align_Interval
Interval_Offset
Configuration_Files
Last_Restore_Time
Slave_Proxy_Enable 1
Auto_Slave_Discovery 1
Slave_Address_Binding
Manual_Slave_Address_Binding
1
1
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
CharacterString
Unsigned16
CharacterString
CharacterString
CharacterString
CharacterString
CharacterString
Unsigned
Unsigned
BACnetServicesSupported
BACnetObjectTypesSupported
BACnetARRAY[N] of
BACnetObjectIdentifier
Unsigned
Unsigned
BACnetSegmentation
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned(1..127)
Unsigned
BACnetDeviceStatus
List of BACnetAddressBinding
List of BACnetCOVSubscription
Integer
Boolean
Date
Time
List of BACnetRecipient
List of BACnetRecipient
Unsigned
Boolean
Unsigned
BACnetARRAY[N] of
BACnetObjectIdentifier
BACnetTimeStamp
BACnetARRAY[N] of Boolean
BACnetARRAY[N] of Boolean
List of BACnetAddressBinding
List of BACnetAddressBinding
LOYTEC electronics GmbH
W
R
R
R
R
R
R
R
W
W
W
W
W
W
W
W
R
R
R
R
R
R
R
W
W
W
R
Conformance Code
R
R
R
R
R
R
R
R
W
W
R
R
R
R
R
L-INX User Manual 285 LOYTEC
Table 15: Properties of the Device Object.
1
Only available if the device is a BACnet/IP-BACnet MS/TP router.
13.3.1.1 Device Name and ID
The following properties of the Device object, which are part of every BACnet object, identify the device uniquely.
Object_Identifier (Read-Only). This property, of type BACnetObjectIdentifier , is a numeric code that is used to identify the object. For the Device object, the object identifier must be unique internetwork-wide.
The Object_Type part of the Object_Identifier of the Device object is 8 (= DEVICE). The instance part of the Object_Identifier of the Device object is configurable via the
configuration UI (see Section 4.2.11). The default value is 17800.
Object_Name (Read-Only). The name of the object. The value of Object_Name of the
Device object is configurable via the configuration UI (see Section 4.2.11). For the Device
object, this name shall be unique within the BACnet internetwork.
Object_Type (Read-Only). The object‘s type. For the Device object, the value of this property is 8 (= DEVICE).
13.3.1.2 Device Information
A whole set of properties provides general purpose information about the device.
Vendor_Name (Read-Only). The value of this property is ―LOYTEC electronics GmbH‖.
Vendor_Identifier (Read-Only). A numerical value identifying the BACnet vendor. The value of this property is 178.
Model_Name (Read-Only). The value of this property is equal to the product code of the device. Examples are ―LINX-200‖ or ―LINX-221‖.
Firmware_Revision (Read-Only). The value of this property gives the current firmware version of the device.
Application_Software_Version (Read-Only). The value of this property gives the build date and the version of the current firmware.
Location (Read-Writable). A string intended to be used to describe the physical location of the device, e.g., ―1st floor‖. This property can be set via the configuration UI (see
Section 4.2.11). The default value is ―unknown‖.
Description (Read-Only). A string intended to be used to describe the device‘s purpose.
This property can be changed via the configuration UI (see Section and 4.2.11).
Protocol_Version (Read-Only). The BACnet protocol version supported by the device.
The value of this property is 1.
Protocol_Revision (Read-Only).
The BACnet protocol revision of the BACnet version supported by the device. The value of this property is 5.
Protocol_Services_Supported (Read-Only). A string of bits marking which BACnet services can be executed by the device. For a detailed list of the BACnet services supported, please refer to the product‘s PICS document.
Protocol_Object_Types_Supported (Read-Only). A string of bits identifying which
BACnet object types are supported by the device. For a detailed list of supported object types, please refer to the product‘s PICS document.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 286 LOYTEC
13.3.1.3 Object Database
The following properties provide information about the BACnet objects contained in the device.
Object_List (Read-Only).
This property holds a BACnetARRAY of object IDs (object type, object instance pairs), one object ID for each object within the device that is accessible through BACnet services.
Database_Revision (Read-Only). This property, of type Unsigned , is a logical revision number for the device's object database. It is incremented when an object is created, an object is deleted, an object's name is changed, an object's Object_Identifier property is changed, or a restore is performed.
13.3.1.4 Protocol Parameters
BACnet protocol parameters are accessible via the properties listed below.
Max_APDU_Length_Accepted (Read-Only). The maximal size of an APDU
(Application Protocol Data Unit) accepted by the device. The value of this property is 487 if BACnet MS/TP is used and 1476 if BACnet/IP is used. When the device can act as a router between BACnet/IP and BACnet MS/TP, the value of this property is 1476.
Segmentation_Supported (Read-Only). The value of this property indicates whether and which kind of segmentation is supported by a device. The value of this property is
SEGMENTED_BOTH.
Max_Segments_Accepted (Read-Only). The maximum numbers of segments accepted by a device. The value of this property is 16.
APDU_Segment_Timeout (Read-Writable). Timeout in milliseconds allowed between segments. The value of this property is 2000 milliseconds by default.
APDU_Timeout (Read-Writable).
Time in milliseconds the device waits for an answer before retrying or giving up on a request; also see Number_Of_APDU_Retries . The value of this property is 3000 milliseconds.
Number_Of_APDU_Retries (Read-Writable). The number of times the device will try to re-send a packet before giving up on a request; also see APDU_Timeout . The value of this property is 3 by default.
Max_Master (Read-Writable).
This property is only present if BACnet MS/TP is enabled.
It defines maximal MS/TP MAC number at which the device expects an MS/TP master.
The value of this property is configurable via the configuration UI (see Section 4.2.11) and
must be in the range 1-127.. The default value of this property is 127.
Max_Info_Frames (Read-Writable).
This property is only present if BACnet MS/TP is enabled. It defines the maximal number of MS/TP packets the device can send when it holds the MS/TP token. Increasing this value will increase latency on the MS/TP network.
The value of this property is configurable via the configuration UI (see Section 4.2.11).
The default value of this property is 1.
13.3.1.5 Diagnostics
Several properties provide run-time information about the device.
System_Status (Read-Only).
The value of this property is always OPERATIONAL.
Device_Address_Binding (Read-Only). This property contains a list of bindings between
BACnet device instance numbers (the instance number part of the Device object ID) and
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 287 LOYTEC
Important!
Important!
BACnet addresses. This property tells a user which BACnet address the device will actually use when trying to communicate with another device known only by its device instance number. This information can be helpful when diagnosing network configuration problems.
A BACnet address consists of the BACnet network number, which is 0 for the local network, and the BACnet MAC address of the device.
In particular, if two or more devices in the network have been wrongly assigned the same device instance number, two BACnetAddressBinding entries with the same instance number but different BACnet addresses will be listed—provided the ambiguous instance number is in some way required by the device (e.g., by a client mapping).
Bindings between device instance numbers and BACnet addresses are only listed in
Device_Address_Binding if they are actually required by a given configuration, and are currently known or ambiguous.
Slave_Address_Binding (Read-Only).
This property is only present if the device is a
BACnet/IP-BACnet MS/TP router. It lists bindings between BACnet MS/TP slave instance numbers (the instance number part of the slave‘s Device object ID) and BACnet addresses of slaves on the MS/TP network for which the device serves as a slave proxy, see Section
Active_COV_Subscriptions (Read-Only). This property lists currently active COV subscriptions.. Each entry of type BACnetCOVSubscription provides information about the recipient address, the monitored property ID, whether notification are confirmed or unconfirmed, the remaining time of the subscription, and optionally the COV increment.
Whenever the device receives a COV subscription via one of the services SubscribeCOV or
SubscribeCOVProperty, a new entry is added to Active_COV_Subscriptions. An entry is removed from Active_COV_Subscriptions when a subscription terminates, either because it times out or because it is actively unsubscribed by the subscriber.
13.3.1.6 Date & Time
The device‘s time and date are exposed to the network via the following set of properties.
UTC_Offset (Read-Writable). This Integer value specifies the time difference between local time and UTC in minutes. The value of this property is configurable via the
configuration UI (see Section 4.2.1).
Important! Note that UTC_Offset is relative to local time and not relative to UTC, i.e., a time zone offset of +1 (hour) corresponds to UTC_Offset being set to -60 (minutes).
Daylight_Savings_Status (Read-Only). This Boolean value indicates whether (TRUE) or not (FALSE) daylight saving correction of the local time is currently active. The daylight
saving scheme is configurable via the configuration UI (see Section 4.2.1).
Local_Date (Read-Only). The current date according to the device‘s clock. The value of
this property can be changed via the configuration UI (see Section 4.2.1).
Local_Time (Read-Only).
The current time according to the device‘s clock. The value of
this property can be changed via the configuration UI (see Section 4.2.1).
13.3.1.7 Time Master
The device can serve as a BACnet time master, i.e., it can issue TimeSynchronization and
UTCTimeSynchronization request on time synchronization events. A time synchronization event occurs after rebooting, when the device‘s clock changes, or, if so configured, periodically. The following properties are used to configure the time master.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 288 LOYTEC
Time_Synchronization_Recipients (Read-Writable).
This list of recipients will receive
TimeSynchronization requests on time synchronization events. A recipients is either specified by its device ID (the object ID of its Device object), or its BACnet address. By default, this list is empty.
UTC_Time_Synchronization_Recipients (Read-Writable).
This list of recipients will receive UTCTimeSynchronization requests on time synchronization events. A recipients is either specified by its device ID (the object ID of its Device object), or its BACnet address.
By default, this list is empty.
Time_Synchronization_Interval (Read-Writable).
The Unsigned value of this property specified the time interval in minutes in which periodic time synchronization events are created. If set to zero, no periodic time synchronization events are generated.
The actual clock time at which periodic time synchronization events are generated is determined by the properties Time_Synchronization_Interval , Align_Interval , and
Interval_Offset
; Table 16 outlines how these properties interact..
Time_Synchronization_Interval Align_Intervals Periodc Time Synchronization Event At…
Multiple of 1440 (minutes), i.e., multiple of one day
Multiple of 60 (minutes) but not multiple of 1440 (minutes), i.e., multiple of one hour
Multiple of 1440 (minutes), i.e., multiple of one day
Multiple of 60 (minutes), but multiple of 1440 (minutes), i.e., multiple of one hour
Neither multiple of 60 or 1440, but greater than zero
Zero not
TRUE
TRUE
FALSE
FALSE
TRUE or
FALSE
Interval_Offset minutes after midnight, every
( Time_Synchronization_Interval /1440) days
Interval_Offset minutes from the current * hour, every ( Time_Synchronization_Interval /60) hours
Interval_Offset minutes from the current
* minute, every
( Time_Synchronization_Interval /1440) days
Interval_Offset minutes from the current
* minute, every
( Time_Synchronization_Interval /60) hours
Interval_Offset minutes from the current
* minute, every Time_Synchronization_Interval minutes
Never TRUE or
FALSE
Table 16: Periodic time synchronization events are parameterized by the properties
Time_Synchronization_Interval , Align_Interval , and Interval_Offset .
*
Current hour or minute refers to the hour or minute at which one of the properties
Time_Synchronization_Interval , Align_Interval , and Interval_Offset is set, e.g., the hour or minute the device completes the boot process or one of these properties is modified via BACnet services.
By default, the value of Time_Synchronization_Interval is 1440 (minutes), i.e., one day.
Align_Intervals (Read-Writable).
The Boolean value of this property determines whether or not periodic time synchronization events shall be anchored at the start of a day or hour
(TRUE) or not (FALSE), provided Time_Synchronization_Interval is a multiple of a day
(1440 minutes) or hour (60 minutes). Table 16 details on how this property influences
generating periodic time synchronization events. The default value of this property is
TRUE.
Interval_Offset (Read-Writable).
While Time_Synchronization_Interval specifies the period in which time synchronization events are generated, the Unsigned value of this property determines the point of time in minutes within this interval at which the time synchronization event is actually triggered. If the value of Interval_Offset is larger than the value of Time_Synchronization_Interval , the remainder of Interval_Offset divided by
Time_Synchronization_Interval is used. The default value of this property is 0.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 289 LOYTEC
13.3.1.8 Backup & Restore
The following properties are related to backup & restore procedures.
Configuration_Files (Read-Only).
The contents of this property is an array of object IDs of File objects that can backed-up or restored during a BACnet backup or restore procedure.
Outside a BACnet backup or restore procedure, this property is empty. After a BACnet backup or restore procedure has been initiated, it contains the object ID (File, 0) , i.e., the
File object whose instance number is 0.
Last_Restore_Time (Read-Only).
The BACnetTimeStamp of the last restore procedure.
13.3.1.9 Slave Proxy
A device configured as BACnet/IP-BACnet MS/TP router, can serve as a slave proxy i.e., the device can answer Who-Is broadcast requests with I-Am responses for BACnet MS/TP slaves which, by definition, cannot initiate any communication and, thus, cannot answer broadcasts. The following properties allow configuring and monitoring the slave proxy.
Slave_Proxy_Enable (Read-Writable).
For each BACnet MS/TP port, this property contains a Boolean that allows a user to enable (TRUE) or disable (FALSE) the slave proxy for the given port. By default, the slave proxy is enabled on all MS/TP ports.
Auto_Slave_Discovery (Read-Writable).
For each BACnet MS/TP port, the slave proxy is capable of auto-detecting slaves on the MS/TP network attached to the port. This autodetection mechanism can be disabled (FALSE) or enabled (TRUE) by changing the
Boolean values stored in this property. Aside from auto-detecting slaves, the presence of slaves can also be manually configured in the property Manual_Slave_Address_Binding . By default, slave auto-detection is enabled on all MS/TP ports.
Important!
Important!
Due to bandwidth and latency limitations on MS/TP networks, the auto-discovery process may initially take up to 10min. However, once, slaves have been discovered, slaves will be quickly re-discovered after reboots or power-outs since the slave proxy caches information about slaves found on the MS/TP networks.
To speed up auto-detection of slaves newly added to an existing MS/TP network for which auto-detection is enabled, simply disable and then re-enable auto-detection on given MS/TP port, i.e., set Auto_Slave_Discovery for the port to FALSE and then back to
TRUE.
Manual_Slave_Address_Binding (Read-Writable).
Aside from auto-detecting slaves, see Auto_Slave_Discovery, slave bindings can also be manually configured via this property. Each entry of this list is a BACnetAddressBinding, i.e., a pair consisting of a slave device‘s instance number and its BACnet address. Note, that bindings in this list may not necessarily appear in the property Slave_Address_Binding , e.g., if for a given binding no physical slave is present at the given MS/TP MAC address. By default, this list is empty.
Only use Manual_Slave_Address_Binding if the slave is not auto-detected. Note, that bindings in Manual_Slave_Address_Binding must contain the correct network number of the MS/TP network to which the slave is attached.
Slave_Address_Binding (Read-Only).
This property lists bindings of instance numbers and BACnet addresses of all slaves for which the slave proxy answers Who-Is requests.
Thus, this property can be used to check if slaves have been auto-discovered or manually bound successfully. The property is also helpful in discovering network configuration issues involving slaves: If two or more slaves on the attached MS/TP networks have been erroneously assigned the same device instance number (the instance number of the slave‘s
Device object), the given instance number will be listed accordingly often in this property.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 290 LOYTEC
The following clauses describe the Device object‘s properties in detail, subsuming related properties in a single section in order to provide a coherent overview.
13.3.2 Client Mapping CSV File
Client functionality for the BACnet server objects can be defined by so-called client mappings . These mappings basically specify whether present value properties shall be written to or polled from the BACnet network, and what the destination address and objects are. These definitions can be downloaded as a CSV file onto the device using FTP.
The CSV file must be named ‗bacclnt.csv‘ and stored in the directory ‗/var/lib/bacnet‘ on the device. The file is read when the device boots. If any errors occur they are reported in
‗/tmp/bacclnt.err‘.
Room 302‖, which writes (mapping type 2) the present value of the local object AI,4 to the remote object AO,1 on the device with the instance number 17801.
Column Field
A
B
C
D
E
F
G
H
Example Description
Description
Local Object-Type
Local Object
Instance Number
Remote Device
Instance
Remote Object-
Type
Remote Object
Instance Number
Map Type
Interval/
Priority
Lamp Room 302
AI
4
17801
AO
1
User-defined description of this client mapping. Can be left empty. Don‘t use commas or semi-colons in the text!
The BACnet object type of the local server object (AI,
AO, AV, BI, BO, BV, MI, MO, MV)
The object instance number of the above object.
The device object instance number of the remote
BACnet device
The BACnet object type of the remote server object (AI,
AO, AV, BI, BO, BV, MI, MO, MV)
The object instance number of the above object.
2
8
Defines the type of the mapping: 0=Poll, 1=COV,
2=Write
Defines the poll interval in seconds for poll mappings and the COV lifetime in seconds for COV mappings.
For write mappings this defines the write priority
(1..16). Omit this field or set it to ‗-1‘ to write w/o priority.
Table 17: CSV Columns of the BACnet Client Mappings File.
13.3.3 EDE Export of BACnet Objects
The BACnet server object configuration of the device is accessible as a set of CSV files following the EDE format convention. They can be downloaded via FTP from the directory
‗/data/ede‘ on the device. The files are
lgate.csv: This is the main EDE sheet with the list of BACnet objects.
lgate-states.csv: This is the state text sheet. For each state text reference in the main sheet, a line contains the state texts for this multi-state object.
lgate-types.csv: This is the object types text sheet. The file contains a line for each object type number. Note, that lines for standard object types can be omitted.
lgate-units.csv: This is the unit text sheet. The file contains a line for each engineering unit enumerator value. Note that lines for standard units can be omitted.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 291
14 Network Media
LOYTEC
14.1 FT
The device‘s FT port is fully compatible to the parameters specified by L ON M ARK for this channel. FT ports can also be used on Link Power (LP-10) channels. However, the device does not provide the power supply for Link Power channels.
When using the Free Topology Segment feature of the FT, only one termination (Figure
229) is required and can be placed anywhere on the free topology segment. Instead of
building the termination, one can order the L-Term module (LT-33) from LOYTEC, which can be used to properly terminate the bus.
100 µF, 50V
+
52,3
105
100 µF, 50V
+
100 µF, 50V
+
+
100 µF, 50V
Figure 229: FT Free Topology Termination.
In a proper bus topology, two terminations are required (Figure 230). These terminations
need to be placed at each end of the bus. Here, also L-Term modules can be used at either end.
100 µF, 50V
+
+
100 µF, 50V
105
Figure 230: Termination in an FT Bus Topology.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 292 LOYTEC
14.2 M-Bus
The device uses the RS-232 console interface for the connection to an external M-Bus transceiver (repeater). The M-Bus specifies no special topology requirement, though it is not advised to use a ring topology. A maximum of 250 M-Bus slave devices can be connected to the bus, in fact, the external bus transceiver can have a lower limit of connected devices. Please refer to the datasheet of the transceiver used for more detailed information. The usual cabling is a standard telephone wire (JYStY N*2*0.8 mm). The maximum distance between a slave and the repeater is 350 meters at Baud rates from 300-
9600 Baud; by limiting the lower Baud rates and using fewer slaves, this limit can be increased. Additionally, it must be ensured that the bus voltage does not fall below 12 V.
The maximum cable length of the system must not exceed 1000 m (maximum cable capacitance of 180 nF).
14.3 Modbus RS-485
The LINX-20X Modbus RS-485 port is an electrical interface in accordance to EIA-485.
The topology of the Modbus RS-485 consists of a trunk cable, along which the devices are connected either directly or via short derivation cables. Without repeater a maximum of 32 slave devices can be connected to the bus. Each Modbus RS-485 network segment must be properly terminated with an LT-04 network terminator connected at each of the two ends of the segment media. Some Modbus slave devices might require the use of external pull-up and pull-down resistors. Please refer to the data sheet or user manual of the external device.
Figure 231 shows the Modbus RS-485 network including pull-up and pull-down resistor
and the network termination.
The maximum length of the cabling depends on the Baud rate used. Without repeater a maximum length of 1000 meters is possible at 9600 Baud. According to the Modbus standard the derivation cabling must never exceed 20 m.
D
Master
R
+ 5V
Pull-Up
LT-04
D1 (B)
D0 (A)
LT-04
Common
Pull-Down
D
R R
Slave 1
D
Slave n
Figure 231: Modbus RS-485 network
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 293
15 Firmware Update
LOYTEC
The L-INX firmware supports remote upgrade over the network and the serial console.
To guarantee that the L-INX is not destroyed due to a failed firmware update, the firmware consists of two images:
1.
The fallback image,
2.
the primary image.
The fallback image cannot be changed. Thus, if the update of the primary image fails or the image is destroyed by some other means, the fallback image is booted and allows reinstalling a valid primary image. When the device boots up with the fallback image, the all port LEDs are flashing red.
The following firmware images are available for the different L-INX automation server models:
LINX-10X: linx10x_x_y_z.dl
LINX-20X: linx20x_x_y_z.dl
LINX-11X: linx_11x_x_y_z.dl
LINX-21X: linx_21x_x_y_z.dl
LINX-12X/15X/22X: linx_12x_15x_22x_x_y_z.dl.
15.1 Firmware Update via the Configurator
The primary image can be updated using the Configurator. For this purpose, it is recommended to have the device connected to the Ethernet and to have a valid IP
configuration (see Section 4.2.2). The Configurator must be installed (see Section 6.1).
To Update the Firmware using the Configurator
1.
Start the Configurator from the Windows Start menu: Start
Programs
LOYTEC
LINX Configurator
LOYTEC LINX Configurator .
2.
Select the menu: Connection
Connect via FTP . This opens the FTP connection
dialog as shown in Figure 232.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 294 LOYTEC
Figure 232: FTP connection dialog.
3.
In the FTP connection dialog, enter the IP address of the device as well as the admin user‘s password. The default password is ‗loytec4u‘ (older firmware versions used
‗admin‘). This can be changed via the Web interface (see Section 4.1) and reset via the
console UI (see Section 16.2.2).
4.
Click on Connect .
5.
Select the menu: Firmware
Update …
6.
This opens the Firmware Update dialog as shown in Figure 233. Click on the button
― … ‖ and select the firmware image.
Version 4.0
Figure 233: Firmware Update dialog of the Configurator.
7.
Click on Start .
8.
Observe the download progress. When the download is complete, the dialog shown in
Figure 234: FTP download success dialog.
LOYTEC electronics GmbH
L-INX User Manual 295
9.
Click OK .
10.
In the Firmware Update dialog, click Close .
11.
The device‘s firmware has now been successfully upgraded.
LOYTEC
15.2 Firmware Update via the Console
On L-INX models with the console connector it is possible to upgrade the device over this interface. To download the firmware via the console interface, the device must be connected to the RS-232 port (EIA-232) of a PC via its console interface as described in
Section 16.2.1. You will need the LOYTEC serial upgrade tool (LSU Tool), which can be
downloaded from our homepage at www.loytec.com.
Please make sure that the console shows the main menu. Otherwise navigate to the main menu or simply reset the device.
To Upgrade via the Console
1.
Double click on the *.dlc file that comes with the new firmware package. This should start the LSU Tool and load the firmware image referenced in the dlc file. Please note that the dlc file and the dl file must be stored in the same folder. The start window of
the LSU tool is shown in Figure 235.
Version 4.0
Figure 235: LSU Serial Upgrade Tool in Idle Mode.
2.
If the device is not connected to COM1 you can change the port to COM2, COM3, or
COM4. Make sure that the product shown under ―Product‖ matches the device you are upgrading. Press Download
to start the download. A progress bar as shown in Figure
LOYTEC electronics GmbH
L-INX User Manual 296 LOYTEC
Figure 236: Progress Bar during Firmware Download.
3.
If the upgrade is successful, the following window appears (Figure 237).
Figure 237: Successful Firmware Upgrade.
4.
Double check that the new firmware is executed by selecting ‗1‘ and pressing Enter in the console window. This will bring up the device information which shows the current firmware version.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 297
16 Troubleshooting
LOYTEC
16.1 Technical Support
LOYTEC offers free telephone and e-mail support for the L-INX product series. If none of the above descriptions solves your specific problem please contact us at the following address:
LOYTEC electronics GmbH
Blumengasse 35
A-1170 Vienna
Austria / Europe e-mail : [email protected]
Web : http://www.loytec.com
tel : fax :
+43/1/4020805-100
+43/1/4020805-99 or
LOYTEC Americas Inc.
11258 Goodnight Lane
Suite 101
Dallas, Texas 75229
USA e-mail: [email protected]
Web: http://www.loytec-americas.com
tel: +1/512/402 5319 fax: +1/972/243 6886
16.2 Statistics on the Console
16.2.1 Connecting to the Console
Use a PC terminal program with the communication settings set to 38,400 bps / 8 data bits / no parity / 1 stop bit / no handshake. To connect COM1 of the PC to the Console on the device, use a standard null-modem cable with full handshaking. Power up the device or press Return
if the device is already running. The menu shown in Figure 238 should appear
on the terminal.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 298 LOYTEC
Device Main Menu
================
[1] Show device information
[2] Serial firmware upgrade
[3] System configuration
[4] CEA-709 configuration
[5] IP configuration
[6] CEA-852 device configuration
[7] CEA-852 server configuration
[8] Reset configuration (factory defaults)
[9] Device statistics
[c] Modbus cofiguration
[a] Data Points
[0] Reset device
Please choose:
Figure 238: Console Main Menu.
16.2.2 Reset configuration (load factory defaults)
Select item ‗8‘ in the console main menu. This menu item allows resetting the device into its
factory default state. The menu appears as shown in Figure 239.
Reset Configuration Menu
========================
[1] Reset everything to factory defaults
[3] Reset all passwords
[4] Clear data point configuration
[q] Quit
Please choose:
Figure 239: Reset to Factory Defaults Menu.
Note:
Select option ‗1‘ to reset the entire device to factory defaults (including error log, configuration files, passwords etc.). Select option ‗3‘ to reset all passwords (Web interface,
FTP server etc.) to factory defaults.
Select option ‗4‘ to clear all configured data points, such as CEA-709 network variables or user registers. This effectively clears the entire port configuration. The device must be rebooted to let the changes take effect.
This option does not reset the configuration of the built-in CEA-709 router. The nodes connected by the router are still reachable after clearing the data point configuration.
16.2.3 Device Statistics Menu
Select ‗9‘ from the device main menu to get to the device statistics menu. This menu holds relevant information regarding the device statistics of the device. This section describes those statistics, which are not available on the Web UI. The device statistics menu is shown
in Figure 240. Use this menu only for debugging purposes. There is no need to access this
menu if the network is running smoothly.
Statistics Menu
===============
[4] Show IP statistics
[8] Show DPAL statistics
[9] Show Reg DPAL statistics
[q] Quit
Please choose:
Figure 240: Device Statistics Menu on the Console.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 299 LOYTEC
16.2.3.1 IP statistics
A sample console output is shown in Figure 241.
*********** INTERFACE STATISTICS ************
***** lo0 *****
Address:127.0.0.1
Flags: Up Loopback Running Multicast
Send queue limit:50 length:0 Dropped:0
***** eth0 *****
Address:192.168.0.2 Broadcast Address:192.168.0.255
Flags: Up Broadcast Running Simplex Multicast
Send queue limit:50 length:0 Dropped:0
Network Driver Stats for CS8900 :
rx ready len - 50 rx loaded len - 0
rx packets - 931 tx packets - 165
rx bytes - 78480 tx bytes - 13627
rx interrupts - 931 tx interrupts - 165
rx dropped - 0 rx no mbuf - 0
rx no custers - 0 rx oversize errors - 0
rx crc errors - 0 rx runt errors - 0
rx missed errors - 0 tx ok - 165
tx collisions - 0 tx bid errors - 0
tx wait for rdy4tx - 0 tx rdy4tx - 0
tx underrun errors - 0 tx dropped - 2
tx resends - 0 int swint req - 2094
int swint res - 2094 int lockup - 0
interrupts - 3189
************ MBUF STATISTICS ************ mbufs: 512 clusters: 64 free: 14 drops: 0 waits: 0 drains: 0
free:461 data:51 header:0 socket:0
pcb:0 rtable:0 htable:0 atable:0
soname:0 soopts:0 ftable:0 rights:0
ifaddr:0 control:0 oobdata:0
************ IP Statistics ************
total packets received 922
datagrams delivered to upper level 922
total ip packets generated here 158
Destination Gateway/Mask/Hw Flags Refs Use Expire
Interface default 192.168.0.1 UGS 6 0 0 eth0
62.178.55.77 192.168.0.1 UGH 0 1 3606 eth0
62.178.95.96 192.168.0.1 UGH 0 1 3606 eth0
81.109.145.243 192.168.0.1 UGH 0 1 3606 eth0
81.109.251.36 192.168.0.1 UGH 0 1 3606 eth0
127.0.0.1 127.0.0.1 UH 0 0 0 lo0
130.140.10.21 192.168.0.1 UGH 1 6 0 eth0
192.168.0.0 255.255.255.0 U 0 0 3 eth0
192.168.0.1 00:04:5A:26:96:1F UHL 7 0 1722 eth0
213.18.80.166 192.168.0.1 UGH 1 148 0 eth0
************ TCP Statistics ************
************ UDP Statistics ************
total input packets 924
total output packets 158
************ ICMP Statistics ************
Figure 241: IP Statistics.
The IP statistics menu has the additional feature of displaying any IP address conflicts. If the device‘s IP address conflicts with another host on the network, the banner shown in
WARNING: Conflicting IP address detected!
IP address 10.125.123.95 also used by device with MAC address
00 04 5A CC 10 41!
Clear IP conflict history (y/n):
Figure 242: IP Address Conflict.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 300 LOYTEC
As useful information, the MAC address of the conflicting host is shown. If the information about this conflict shall be cleared, enter ‗y‘. If ‗n‘ is selected, the conflict will show up again the next time this menu is entered.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 301
17 Application Notes
LOYTEC
17.1 The LSD Tool
Please refer to application note ―AN002E LSD Tool‖ for further information about the
LOYTEC system diagnostics tool for the LINX-10X.
17.2 Use of Static, Dynamic, and External NVs on a Device
Please refer to application note ―AN009E Changing Device Interface in LNS‖ for more information on the static NV interface, XIF files, device templates and the use of static, dynamic, and external NVs on LOYTEC gateway products.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 302
18 Specifications
LOYTEC
18.1 Physical Specifications
18.1.1 LINX-10X/11X/20X/21X
Operating Voltage 12 – 35 VDC or 12 – 24 VAC ±10 % typ. 3 W Power Consumption
In rush current up to 950 mA @ 24 VAC
Operating Temperature (ambient) 0
C to +50
C
-10
C to +85
C Storage Temperature
Humidity (non condensing) operating 10 to 90 % RH @ 50
C
Humidity (non condensing) storage 10 to 90 % RH @ 50
C
Enclosure Installation enclosure 6 TE, DIN 43 880
Environmental Protection
Installation
IP 40 (enclosure); IP 20 (screw terminals)
DIN rail mounting (EN 50 022) or wall mounting
18.1.2 LINX-12X/15X/22X
Operating Voltage
Power Consumption
24 VDC or 24 VAC ±10 % typ. 2.5 W
In rush current
Operating Temperature (ambient) up to 950 mA @ 24 VAC
0
C to +50
C
Storage Temperature -10
C to +85
C
Humidity (non condensing) operating 10 to 90 % RH @ 50
C
Humidity (non condensing) storage 10 to 90 % RH @ 50
C
Enclosure Installation enclosure 9 TE, DIN 43 880
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
Environmental Protection
Installation
303 LOYTEC
IP 40 (enclosure); IP 20 (screw terminals)
DIN rail mounting (EN 50 022) or wall mounting
18.2 Resource Limits
Table 18 specifies the resource limits of the different L-INX models.
L-INX
Model
Limits
Total number of data points
OPC Tags
User Registers
NVs (static, dynamic)
External NVs
Alias NVs (ECS and legacy mode)
Address table entries/legacy
10,000 10,000 30,000 30,000 10,000 10,000 30,000
2,000
1,000
1,000
1,000
1,000 n/a
1,000
1,000
1,000
1,000
5,000
1,000
1,000
1,000
1,000
5,000
1,000
1,000
1,000
1,000
2,000
1,000 n/a n/a n/a
L
ON
M
ARK
Calendar objects
L ON M ARK Scheduler objects
L
ON
M
ARK
Alarm Servers
BACnet objects (analog, binary, multi-state)
BACnet client mappings
BACnet scheduler objects
BACnet calendar objects
BACnet notification classes
Trend Logs
Total trended data points
Total aggregated size
E-mail templates
Math objects
Alarm Logs
Modbus data points
M-Bus data points
Connections
512/
15
1,000/
15
1,000/
15
1 (25 calendar patterns)
1,000/
15
100 (max. AST configuration size 384KB,
1 n/a
64 data points per scheduler)
1 n/a
1 n/a
1
1,000 n/a n/a n/a n/a
750 n/a n/a n/a n/a
100
256
6MB
100
100
10
2,000
1,000 n/a n/a n/a n/a
100
256
6MB
100
100
10
2,000
1,000 n/a n/a n/a n/a
100
256
60MB
100
100
10
2,000
1,000
1,000
100
25
32
100
256
60MB
100
100
10
2,000
1,000
750
100
25
32
100
100
6MB
100
100
10
2,000
1,000
1,000 1,000 2,000 2,000 1,000
Table 18: Resource limits of different L-INX models n/a
1,000 n/a n/a n/a n/a n/a n/a n/a
750
750
100
25
32
100
100
6MB
100
100
10
2,000
1,000
1,000
5,000
1,000 n/a n/a n/a n/a n/a n/a n/a
1,000
1,000
100
25
32
100
100
60MB
100
100
10
2,000
1,000
2,000
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual
19 References
304
[1] L-IP User Manual, LOYTEC electronics GmbH,
Document № 88065909, June 2006.
[2] LIP-ME201 User Manual, LOYTEC electronics GmbH,
Document № 88073501, October 2008.
[3] NIC User Manual, LOYTEC electronics GmbH,
Document № 88067212, September 2008.
[4] LWEB-800 User Manual, LOYTEC electronics GmbH,
Document № 88074203, April 2009.
[5] LWEB-801 User Manual, LOYTEC electronics GmbH,
Document № 88074703, April 2009.
[6] L-VIS User Manual, LOYTEC electronics GmbH,
Document № 88068512, August 2008.
[7] L-IOB User Manual, LOYTEC electronics GmbH,
Document № 88078501, October 2010.
LOYTEC
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 305
20 Revision History
Date
2008-12-23
2009-02-20
2009-05-14
Version
3.0
3.2
3.3
2009-11-16
2010-04-30
2010-10-18
3.4
3.5
4.0
Author Description
STS
PP
PP
STS
STS
STS
Initial revision V3.0 for LINX-20X 3.0
Added Section 5.2 Connections, Chapter 10 M-Bus
Updated for LINX-20X firmware release 3.3, added
Chapter 11 Modbus, added Section 6.1.5. Behavior on
Value Changes, added Section 6.1.6 Custom Scaling, added Section 7.7.2. Create Connections from a CSV File
Updated for LINX-20X firmware release 3.4. Section
6.3.3 Withdraw and embedded exceptions. Section 7.3.2 renumber, filter, include subfolders. Updated Section
7.3.3 BACnet project settings, updated Section 7.6.1 Scan for BACnet objects. Section 7.8.2 Replace data points in e-mail template. Added Section 7.9.7 Configure embedded exceptions. Section 7.13 added COV delta to math objects, replace data points. Added Section 12.1 M-
Bus cabling, added Section 12.2 Modbus cabling.
Updated for LINX-20X firmware release 3.5. Removed
Section on Console UI and added console statistics as
Section 13.2. Added Section 4.2.3 port configuration
Web UI. Added Section 6.2.5: Managing Multistate
Maps. Section 6.3 Project settings: added device configuration tab. Section 6.11.4 Added alarm log fill level notification. Section 7.2: New L-WEB project manager. Section 9.5.1 M-Bus secondary address scanning, new activation in project settings. Section
10.3.1 Modbus speeds 1200, 2400, 4800. Section 10.4.1
Modbus slave, device config in project settings. Section
16.1.2 Resource Limits: 2000 OPC tags.
Merged manuals for LINX-10X, 20X, 11X, 21X.
Updated for firmware version 4.0.