L-INX User Manual
4 Web Interface
53 LOYTEC
The L-INX comes with a built-in Web server and a Web interface to configure the L-INX and extract statistics information. The Web interface allows configuring the IP settings,
CEA-709, BACnet and other configuration settings.
4.1 Device Information and Account Management
In a Web browser, enter the default IP address 192.168.1.254 of the device. Note that if your PC has an IP address in a subnet other than 192.168.1.xxx, you must open a command tool and enter the following route command to add a route to the device.
To Add a Route to the Device
1.
Windows START
Run
2.
Enter ‗cmd‘ and click OK .
3.
In the command window enter the command line route add 192.168.1.254 %COMPUTERNAME%
4.
Then open your Web browser and type in the default IP address ‗192.168.1.254‘.
5.
The device information page should appear as shown in Figure 36.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 54 LOYTEC
Figure 36: Device Information Page.
The device information page shows information about the L-INX and the current firmware version. It also contains operational parameters, such as free memory, system temperature and supply voltage.
Click through the menus on the left hand side to become familiar with the different screens.
If you click on Config in the left menu, you will be asked to enter the administrator
password in order to make changes to the settings as shown in Figure 37. Enter the default
administrator password ‗loytec4u‘ and select Login . Note, that firmware versions previous to 4.0 used ‗admin‘ as the default password.
Version 4.0
Figure 37: Enter ‗admin‘ as the default administrator password.
The Config menu opens. Click on Passwords in the Config menu, which opens the
password configuration page as shown in Figure 38. The device has three user accounts: (1)
guest allows the user to view certain information only, e.g., the device info page. By default the guest user has no password. (2) operator is able to read more sensible information such as calendar data. (3) admin has full access to the device and can make changes to its
LOYTEC electronics GmbH
L-INX User Manual 55 LOYTEC configuration. Note that the user accounts are also used to log on to the FTP and Telnet server.
Figure 38: Password Configuration Screen.
Please change the administrator password in order to protect yourself from unwanted configuration changes by anyone else. To do so, select the admin account in the drop-down box and enter the new password. If the administrator password is left empty, password protection is turned off and everyone can access the device without entering a password.
Click on Change password to activate the change.
4.2 Device Configuration
The device configuration pages allow viewing and changing the device settings of the
LINX. Here are some general rules for setting IP addresses, port numbers, and time values:
An empty IP address field disables the entry.
An empty port number field sets the default port number.
An empty time value field disables the time setting.
4.2.1 System Configuration
The system configuration page is shown in Figure 39. This page allows configuring the
device‘s system time and other system settings. The TCP/IP Configuration link is a shortcut to the Ethernet port configuration. Follow that link to change the IP settings of the device.
The time sync source can be set to auto , manual , NTP , BACnet , or LonMark . In the auto mode, the device switches to the first external time source that is discovered. Possible external time sources are NTP, BACnet, LonMark. The option manual allows setting the time manually in the fields Local Time and Local Date . In manual mode, the device does not switch to an external time source. Note, that if NTP is selected, the NTP servers have to
be configured on the IP Configuration page (see Section 4.2.2).
The time zone offset must be defined independently of the time source. It is specified as the offset to GMT in hours and minutes (e.g., Vienna/Austria is +01:00, New York/USA is
-06:00). For setting the daylight saving time (DST) predefined choices are offered for
Europe and USA/Canada. DST can be switched off completely by choosing none or set manually for other regions. In that case, start and end date of DST must be entered in the fields below.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 56 LOYTEC
Figure 39: System Configuration Page, e.g., for Vienna, Austria.
The next section on the page allows configuring the device‘s earth position. This setting defines the longitude, latitude and elevation of the device. The latitude and longitude are entered as degrees, minutes, and seconds. The altitude is entered in meters height above sea level. This setting is used for an astronomical clock. For fixed locations such as a building, the position can be entered on this page.
For generating CSV files for trend logs, alarm logs, etc., the delimiter for those CSV files can be configured. This setting can be changed between a comma ‗,‘ and a semi-colon ‗;‘.
The change takes effect immediately for all files generated by the device.
4.2.2 Backup and Restore
A configuration backup of the device can be downloaded via the Web interface. Press the
backup link as shown in Figure 40 to start the download. The device assembles a single file
including all required files. A file requestor dialog allows specifying the location where the backup file shall be stored.
To restore the device settings, simply select a previously generated backup file in the
Restore Configuration section of the page by clicking the button next to the Filename field. Then press the Restore button.
The backed up configuration data consists of:
Device settings (Passwords, IP settings, e-mail config, etc.),
Data point configuration,
CEA-709 binding information,
BACnet server objects and client mappings,
LIOB configuration and parameters,
AST settings,
L-WEB configuration and custom Web pages.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 57 LOYTEC
Figure 40: Backup/Restore page.
4.2.3 Port Configuration
This menu allows configuring the device‘s communications ports. For each communication port, which is available on the device and shown on the label (e.g., Port 1, Port 2 Ethernet), a corresponding configuration tab is provided by the Web UI. An example is shown in
Figure 41. Each port tab contains a selection of available communication protocols. By
selecting a checkbox or radio button the various protocols can be enabled or disabled on the communication port. Some ports allow exclusive protocol activation only, other ports (e.g., the Ethernet port) allow multiple protocols bound to that port.
Figure 41: Port Configuration Page.
When selecting a protocol on a communication port, the protocol‘s communication parameters are displayed in a box on the right-hand side. To save the settings of the currently opened protocol, click the Save Settings button. Pressing Get Settings retrieves the current settings from the device.
4.2.4 IP Configuration
The TCP/IP configuration is done under the Ethernet port tab as shown in Figure 42. The
mandatory IP settings, which are needed to operate the device, are marked with a red asterisk (IP address, netmask, gateway). The Enable DHCP checkbox switches between manual entry of the IP address, netmask, and gateway address, and automatic configuration from a DHCP server.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 58 LOYTEC
Hostname and Domainname are optional entries and can be left empty. For some DHCP configurations it may be necessary to enter a hostname. Please contact your system administrator on how to configure DHCP to acquire an IP address. Further, you can configure up to 3 Domain Name Servers.
Version 4.0
Figure 42: IP Configuration Page.
The device comes configured with a unique MAC address. This address can be changed in order to clone the MAC address of another device. Please contact your system administrator to avoid MAC address conflicts.
The device can be configured to synchronize its clock with NTP time. Enter the IP address of a primary and, optionally, a secondary NTP server. The device will use NTP as a time source if the time sync source in the system configuration page is set to NTP (see Section
NTP status below the NTP server settings displays the current NTP synchronization status ( out-of-sync , or in-sync ).
If the device is operated with a 10 Mbit/s-only hub, the link speed should be switched from
Auto Detect to 10Mbps/Half-Duplex . With modern 100/10 Mbit/s switches, this setting can be left at its default.
Other standard protocols that are bound to the Ethernet interface are FTP, Telnet, and
HTTP (Web server). By deselecting the checkbox, those protocols can be individually disabled. The standard UDP/TCP ports can be changed in the respective protocol settings.
An example for the FTP server is shown for FTP in Figure 43. The FTP server is used for
instance to update the firmware (see Section 15.1) or to upload a new data point
configuration. Note that HTTP for the Web server can only be disabled on the console interface or by using the device configuration of the Configurator.
LOYTEC electronics GmbH
L-INX User Manual 59 LOYTEC
Figure 43: FTP server configuration on the Ethernet port.
4.2.5 Ethernet Sniffer
The L-INX models, which provide a built-in Ethernet switch/hub, can configure the switch to operate as a hub. This allows connecting a laptop computer to the second Ethernet port and running a packet sniffer on the device. To activate the sniffer mode, go to the Ethernet port config and select the Ethernet Sniffer
item as shown in Figure 44. In the settings box
select the Ethernet port, on which the traffic shall be forwarded to.
Figure 44: Activating the Ethernet Sniffer.
4.2.6 CEA-709 Configuration
The CEA-709 protocol can be enabled on the device‘s ports Port1, Port2, etc. if available.
To enable it, click the CEA-709
radio button as shown in Figure 45. Note, that depending
on the device model, other protocols on the same port will be disabled in this case. The protocol settings box on the right-hand side displays the current transceiver settings.
Figure 45: CEA-709 Configuration Page.
4.2.7 CEA-852 Device Configuration
The CEA-852 protocol is only available on the Ethernet port. To enable CEA-852 on the device, select the CEA-852 (CEA-709 over IP) checkbox on the Ethernet tab of the port configuration page. Please note that on device models without a router or a proxy, the
CEA-709 protocol on other ports will be disabled (e.g., LINX-100).
The CEA-852 protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 46. Typically, the device is added to an IP channel by entering the relevant
information on a configuration server. The configuration server then contacts the CEA-852 device of the L-INX and sends its configuration.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 60 LOYTEC
Version 4.0
Figure 46: CEA-852 Device Configuration Page.
The field Config server address and Config server port display the IP address and port of the configuration server, which manages the L-INX and the IP channel. The field Config client port represents the IP port of the LINX‘s CEA-852 device. This setting should be left at its default (1628) unless there are more than one CEA-852 devices operating behind a single NAT router. Please refer to the L-IP User Manual [1] to learn more about NAT configuration.
In the field Device name the user can enter a descriptive name for the LINX, which will appear in the IP channel to identify this device. You can enter a device name with up to 15 characters. It is recommended to use unique device names throughout the IP channel.
The Channel mode field reflects the current channel mode of the CEA-852 device. It is configured by the configuration server. If there are any two devices in the channel which use the same IP address but different ports (e.g., multiple devices behind one NAT router) the channel switches to Extended NAT mode . Please refer to the L-IP User Manual [1] to learn more about configuring the Extended NAT mode in the configuration server.
The configuration server sets the SNTP server addresses and the Channel timeout .
The filed Escrow timeout defines how long the CEA-852 device on the L-INX waits for out-of-sequence CEA-852 data packets before they are discarded. Please enter the time in ms or ‗0‘ to disable escrowing. The maximum time is 255 ms.
The field Aggregation timeout defines the time interval in which multiple CEA-709 packets are combined into a single CEA-852 data packet. Please enter the time in ms or ‗0‘ to disable aggregation. The maximum time is 255 ms. Note that disabling aggregation will negatively affect the performance of the CEA-852 device of the LINX.
The field MD5 authentication enables or disables MD5 authentication. Note that MD5 authentication cannot be used together with the Echelon‘s i .
LON 1000 since the i .
LON 1000 is not fully compliant with the CEA-852 authentication method. MD5 can be used with the i .
LON 600. In the following field MD5 secret enter the 16-byte MD5 secret.
Note that for security purposes the active MD5 secret is not displayed. You may enter the
16 bytes as one string or with spaces between each byte, e.g., 00 11 22 33 44 55 66 77 88
99 AA BB CC DD EE FF.
LOYTEC electronics GmbH
L-INX User Manual 61 LOYTEC
Also note that entering the MD5 secret on the Web interface may pose a security risk. Since the information is transmitted over the network it can be subject for eavesdroppers on the line. It is recommended to use a cross-over cable.
In the field Location string the user can enter a descriptive test which identifies the physical location of the LINX. A location string can have a maximum length of 255 characters. This is optional and for informational purposes only.
If the CEA-852 device on the L-INX is used behind a NAT router, the public IP address of the NAT router or firewall must be known. To automatically detect the NAT address leave the Auto-NAT checkmark enabled.
The Multicast Address field allows the user to add the CEA-852 device of the L-INX into a multi-cast group for the CEA-852 IP channel. Enter the channel‘s IP multi-cast address here. Please contact your system administrator on how to obtain a valid multi-cast address.
To learn when it is beneficial to use multi-cast addresses in your channel please refer to the
L-IP User Manual [1].
4.2.8 CEA-709 Router Configuration
This page is only available on L-INX models with the router option (101, 111, 121, 151).
The CEA-709 router configuration page allows configuring the built-in router mode.
Available modes are Configured Router and Smart Switch . The L-INX must be rebooted to let the changes on this page take effect.
The configured router mode is the default setting. Choose this setting if you want to use the
L-INX as a standard configured CEA-709 router that can be configured in a network management tool such as NL-200 or LonMaker.
The Smart Switch mode lets the device act as a self-learning router like the L-Switch. In this configuration the LINX‘s router doesn‘t need to be configured with a network management tool but is completely transparent in the network. Use this operating mode in a plug&play networking environment. The switch mode should only be used in LAN networks. In Smart
Switch mode, this page has two more configuration fields: Subnet/node learning and
Group learning .
Figure 47: CEA-709 Router Configuration Page.
4.2.9 CEA-852 Server Configuration
This page is only available on CEA-709 L-INX models with the router option (101, 111,
121, 151). On this configuration page the configuration server on the LINX-101 can be enabled or disabled. In the drop-down box Config server status select enabled and click
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 62 LOYTEC on Save Settings to activate the configuration server. Then the configuration server settings
page appears as shown in Figure 48. If the configuration server is enabled the green
configuration server LED labeled CS will be on, otherwise it will be off.
The configuration server port can be changed in the Config server port field. It is recommended to keep the default port setting of 1629. The field Channel name is informational only and can consist of up to 15 characters.
The field Channel members displays the current number of members on the IP-852 channel. The field Channel mode reflects the current channel mode. The L-INX configuration server automatically determines this mode. Depending on if there are any two devices in the channel which use the same IP address but different ports (e.g., multiple
CEA-852 devices behind one NAT router). If all IP addresses are unique, the mode is
Standard , if some are not unique the mode is Extended NAT mode . Please refer to
Section 7.3.2 to learn more about the implications of this mode.
Version 4.0
Figure 48: Configuration server settings.
Enter NTP timer server address and ports in the fields Primary SNTP and Secondary
SNTP . The L-INX will synchronize to NTP time if primary or primary and secondary NTP servers are specified. A list of available timeservers can be found at www.ntp.org
.
The Channel timeout is an IP-852 channel property and indicates how old a packet can be before it is discarded. The channel timeout is set in ms. To disable the channel timeout enter
a value of 0. To select the proper value please consult Section 7.5.2. Setting a channel
timeout other than 0 requires a valid SNTP server entry on the configuration server.
The Auto members option allows members to be automatically added to the channel. If turned on, CEA-852 devices can register on the IP-852 channel without the device being explicitly added on the configuration server. This special feature is useful in combination with the LPA-IP since it can add itself to the configuration server during the debug session.
Non-responding auto members are automatically removed from the channel. This feature is turned off by default and must be explicitly turned on. Use this option with care because new CEA-852 devices can add themselves to the channel without knowledge of the system operator. This could cause a potential security hole.
LOYTEC electronics GmbH
L-INX User Manual 63 LOYTEC
The Roaming members option allows tracking CEA-852 devices when their IP address changes. This feature must be turned on if DHCP is used and the DHCP server can assign different IP addresses to the same device (same Neuron-ID). In combination with Auto-
NAT the LINX‘s router can also be operated behind NAT routers, which change their IP address between connection setups. For more information on this topic refer to Section
7.3.1. The roaming member feature is turned on by default. It is recommended to turn off
this feature if DHCP is not used or if the DHCP server always assigns the same IP address to a given MAC address.
Use the drop-down box MD5 authentication to enable and disable MD5 authentication. If
MD5 authentication is enabled, all devices on the IP-852 channel must have MD5 enabled and must use the same MD5 secret. Note that MD5 authentication cannot be used together with the Echelon‘s i .
LON 1000 since the i .
LON 1000 is not fully compliant with the
CEA-852 authentication method. MD5 can be used with the i .
LON 600. The MD5 secret can be entered over the Web interface. You may enter the 16 bytes as one string or with spaces between each byte, e.g., 00 11 22 33 44 55 66 77 88 99 AA BB CC DD EE FF.
It is recommended, however, to enter the secret locally and not over an Internet connection.
It is best to use a cross-over Ethernet cable connected to the PC.
4.2.10 CEA-852 Channel List
This page is only available on CEA-709 L-INX models with the router option (101, 111,
121, 151). If the configuration server is enabled on the LINX, the CEA-852 device list can
be seen in the CEA-852 channel list menu. An example is given in Figure 45.
The Add Device button is used to add another CEA-852 device to the IP-852 channel. The
Reload button updates the Web page and the Recontact button contacts all devices to update their status. The Execute button executes the option selected in the adjacent dropdown box on the checked members. Each member can be selected for that action in an individual check-box in the Sel column. Actions available are: disable , enable , delete , assign to NAT , and remove from NAT . For more information on the actions on NAT
routers refer to Section 7.3.2.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 64 LOYTEC
Figure 49: CEA-852 channel membership list.
The device status information is indicated with descriptive icons of different colors. The
description for the different status indicators is shown in Table 8. The
Flags column indicates with an A that the device is an auto member.
Click on the Edit button to change the device name, IP address, and port number for this device. Click Edit on a NAT router to change the NAT router address. The Stats button retrieves the statistics summary page from the client device.
Icon Status Description registered unregistered not contacted not responding disabled
No extended
NAT
The CEA-852 device has been successfully registered with the IP-852 channel and is fully functional.
The CEA-852 device has never been registered with the IP-852 channel.
The CEA-852 device has not been contacted since the configuration server has started.
The CEA-852 device has been registered but is not responding at the moment.
The CEA-852 device has been disabled on the channel (or rejected).
The CEA-852 device does not support the extended
NAT mode. This device is disabled.
Table 8: Possible Communication Problems in the Configuration Server.
4.2.11 BACnet Configuration
Figure 50 shows the BACnet device configuration page. This configuration page allows
setting the Device ID , which is the instance part of the Object_Identifier property of the
BACnet Device object. The field Device name holds the name of the BACnet device object
(property Object_Name).
Important: The device ID and device name must be unique within the BACnet internetwork.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 65 LOYTEC
Important!
Figure 50: BACnet Device Configuration.
Further, the description and location can be configured. These configuration items correspond to the properties Description, and Location respectively of the BACnet Device object.
Depending on the selected BACnet/IP mode, applicable fields are enabled and others are grayed-out. Note, that on the LINX-200, the BACnet/IP modes are restricted to Device and
Foreign Device , while the LINX-201 also supports Broadcast Management Device .
For operating the LINX-151,201,211,221 as a BACnet router between BACnet/IP and
MS/TP, the BACnet network numbers for the BACnet/IP and MS/TP ports must be set.
On the settings for BACnet/IP refer to Section 4.2.12. For configuring the MS/TP data link
4.2.12 BACnet/IP Configuration
The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the device, select the BACnet/IP checkbox on the Ethernet tab of the port configuration page.
Please note that on device models without a router, the BACnet MS/TP protocol on other ports will be disabled (e.g., LINX-200, L-Gate).
The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 51. On devices with a router (e.g., LINX-201) the
Network Number of the
BACnet/IP port must be configured to operate the build-in router. If the BACnet/IP network uses a non-default UDP port number other than 47808/0xBAC0, enter this port in the
BACnet/IP port field. Enter ‗0‘ in this field for switching back to the default setting.
Version 4.0
Figure 51: BACnet/IP Configuration.
In the field BACnet/IP mode the operation mode of the device is selected:
Device (Default): In this mode the device operates as a regular BACnet/IP device on the local network without other advanced features.
LOYTEC electronics GmbH
L-INX User Manual 66 LOYTEC
Foreign Device (FD): In this mode, the device registers at an existing BBMD in the
BACnet/IP network as a foreign device. It is used, if the device is located as a single
BACnet/IP device on a remote IP subnet or behind a NAT router. If operated as a foreign device behind a NAT router, port forwarding to the BACnet/IP port (UDP, default port 0xBAC0) and optionally to the Web server and FTP server port (TCP, default port 80 and 21) must be setup in the NAT router. If foreign device is selected, the following, additional settings must be made: o FD BBMD IP address and FD BBMD port : IP address and port of the remote BBMD the device registers at as a foreign device. o
FD re-registration : A foreign device must periodically re-register at a
BBMD. Here you can setup the corresponding interval. The default is 1800 seconds. o FD retry timeout and FD retries : Here you can specify the behavior, if registration does not work instantly. These values should be left at default:
30000ms / 3 retries.
Broadcast Management Device (BBMD): This option is available on the LINX-201
only. Same as ‗Device‘ but the BBMD function is enabled (see Section 4.2.14). For
BBMD-only function, MS/TP can also be disabled (see Section 4.2.13).
4.2.13 MS/TP Configuration
The BACnet MS/TP protocol can be enabled on the device‘s port Port2 if available. To enable it, click the BACnet MS/TP
radio button as shown in Figure 52. Note, that
depending on the device model, other protocols on the same port will be disabled in this case. On a BACnet L-INX without a BACnet router BACnet MS/TP port is not enabled by default. On a BACnet L-INX with a BACnet router the MS/TP port is enabled by default.
Figure 52: MS/TP Configuration.
The MS/TP protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 52. Mandatory settings are the
MS/TP node number and the MS/TP baud rate. The MS/TP node number determines the physical address of the device on the
MS/TP channel and must be in the range from ‗0‘ to the number configured with the
MS/TP max master configuration option. It must be unique within the MS/TP channel.
The Baud rate on the MS/TP channel can be set to 9600, 19200, 38400, and 76800 Baud. It is strongly recommended to leave the MS/TP max info frames and the MS/TP max master configuration options at their default settings.
On a L-INX with a BACnet router, the Network Number of the MS/TP port must be configured to operate the build-in router. On the LINX-201 the MS/TP port can be disabled independently of the BACnet/IP port.
4.2.14 BACnet BDT (Broadcast Distribution Table)
The BBMD function is only available on L-INX models with the BACnet router option
(151, 201, 211, 221). The BBMD function is needed when a BACnet/IP network spans over several IP subnets separated by IP routers. If the device is configured as a BBMD, i.e. the
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 67 LOYTEC
BACnet/IP mode is set to Broadcast Management Device,
(Broadcast Distribution Table) specifies all other BBMDs of the BACnet/IP network. The
Figure 53: BACnet Broadcast Distribution Table.
By clicking Add Device new BBMDs (IP address and port) can be added. With Action on
Selected and selecting existing entries, certain BBMDs can be deleted again from the table.
To commit the finished table, device must be rebooted (see Section 4.5).
4.2.15 E-mail Configuration
The Web interface provides the e-mail configuration page to set up an e-mail account, which is used to send e-mails. The content and time when e-mails are sent is configured
through the Configurator software (see Section 6.11). The e-mail configuration page is
In the field for the outgoing e-mail server, enter the SMTP server of your Internet provider.
Typically, the SMTP server port can be left at 25. In the field Source E-mail Address , enter the e-mail address of the device‘s e-mail account. In the field Source E-mail Sender
Name enter a name that the e-mail will display as the source name. Note, that only ASCII characters are allowed in the name. If replies shall be sent to another e-mail address, specify this in the Reply E-mail Address .
If the provider‘s SMTP server requires authentication, enter the required user name and password. Note, that only username/password is supported. SSL/TLS authentication is not supported (e.g., Hotmail, gmail cannot be used).
To verify the e-mail configuration, reboot the device to let the changes take effect and return to the e-mail configuration page. Then press one of the Send Test E-mail buttons.
Note, that a DNS server must be configured in the IP settings (see Section 4.2.4) to resolve
the e-mail server host name. The Web UI displays a warning message at the top of the page, if the DNS configuration is missing.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 68 LOYTEC
Figure 54: E-mail Configuration Page.
4.2.16 Data Points
The device‘s Web interface provides a data point page, which lists all configured data
points on the device. An example is shown in Figure 55. The data point page contains a tree
view. Clicking on a particular tree item fills the right part of the page with a data point list of that tree level and all levels below. Thus, one can get an easy overview of all data points.
The data point list displays the data point name, direction, type, current value, and data point state. Inactive points are displayed in gray. If the data point list does not fit on one page, there are page enumerator links at the bottom. Important data point states and their
implications are listed in Table 9.
Version 4.0
Figure 55: Data point page.
LOYTEC electronics GmbH
L-INX User Manual 69 LOYTEC
Data Point Status Description normal invalid value offline (config) offline unreliable
(offline) unreliable (range) unreliable not configured inactive
The data point is in normal operation state and possesses a value.
The data point has no valid value.
The data point has a value but it is not reflected on the network due to a configuration error (not commissioned, no binding, no client mapping, etc.)
The data point has a value but it is not reflected on the network due to a communication error (e.g., the peer node is not online).
The data point is in normal operation. The value of it, however, is qualified as unreliable because a connected data point is offline. For an output data point it means that the value was fed from a connection, where the source is offline. For an input data point it means that the connected output data point could not send the value to the network.
The data point is in normal operation. The value of it, however, is qualified unreliable because the value is an out-of-range value for the connected data point. The value is limited to the supported range.
The data point is in normal operation. The value of the data point or a connected data point has been tagged as unreliable over the network. This is the case when the BACnet reliability has been written.
The data point is mapped to a port, which is not configured (e.g., the port is disabled).
The data point is inactive and the line is grayed-out. Values can be written but no network communication is triggered. This can be the case, if a data point is not used in the configuration or it is connected to a BACnet server object, which is not present on the device.
Table 9: Data Point States.
The data point names are links. Clicking on such a link opens a detailed page on that data point. If the data point supports it, the user can also enter a new data point value as depicted
Status
field is discussed in Table 9. The
Flags , Poll cycle , Min/Max send time and Max age fields are the common timing parameters for the data point. See
Section 5.1.2 for a closer discussion on timing parameters.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 70 LOYTEC
Figure 56: Data point details page.
Clicking on the Set button writes the new value to the device‘s data server. When setting a value, the Web page displays the status of the action:
Successfully set value : The new value has been successfully set in the data point and the update has been sent on the network, if it is a network data point.
Could not send value update : The new value has been set but it has not been sent out on the network. The reason can be that the peer node is currently offline or there is a configuration error. The data point status reflects this error.
Could not set value (error code ): The new value has not been set because of an internal error. Please contact LOYTEC with the error code.
4.2.17 Trend
The Web interface provides a configuration page to re-configure trend logs at run-time. The changes made to the trend logs take effect immediately without the needs for a reboot of the device. Allocating new trend logs can only be done in the configuration software (see
Section 6.14.1). The trend log main page displays all available trend logs. Click on the trend
log to be edited. This opens the trend log configuration page. An example is shown in
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 71 LOYTEC
Figure 57: Trend log configuration page.
The user can change the Trend Mode , the Fill Mode , the Log Interval and the Fill Level
Notification . Furthermore, data points can be added to the trend log by clicking the Add… button. A data point selector dialog opens. Click on a data point for adding it. For removing a data point from the trend log, click on it in the Logged Data Points list and hit the
Remove button. Save the changes made by clicking the Save button. For more information
on how a trend log can be configured please refer to the Configurator Section 6.14.2.
4.2.18 Scheduler
The Web interface provides the scheduler page to edit its schedules at run-time, i.e., change the times and values that shall be scheduled. Allocating new schedules and attaching data
points to those schedules can only be done in the configuration software (see Section 6.12).
The scheduler main page displays all available schedules. Click on the schedule to be
edited. This opens the scheduler page. An example is shown in Figure 58.
The effective period defines when this schedule shall be in effect. Leave From and To at
‗*.*.*‘ to make this schedule always in-effect. Otherwise enter dates, such as ‗30.1.2000‘.
To entirely disable a scheduler de-select the Enable Schedule check box.
Schedules are defined per day. On the left-hand side, the weekdays Monday through
Sunday can be selected, or exception days from the calendar, e.g., Holidays. Once a day is selected, the times and values can be defined in the daily planner on the right-hand side. In
the example shown in Figure 58, on Monday the value
day is scheduled at 8:00am . The same principle applies to exception days . Exception days override the settings of the normal weekday. Put a check mark on those exception days from the calendar, which shall be used in the schedule. To edit the date ranges of exception days click on the links to the used calendars, e.g., ‗calendar‘ or ‗Scheduler_1‘. The ‗Scheduler_1‘ is a calendar, which is embedded into the schedule and not accessible by other schedulers. For more information
on how to set up schedules and calendars refer to Section 6.12.
To define actual values for the names such as day click on the tab Presets as shown in
Figure 59. To define a new value, click on the button
Add Preset . This adds a new column.
Enter a new preset name (e.g., ‗day‘). Then enter values for the data points in the preset column. The data point description column displays the short-hand name defined in the configuration software. This description can also be changed on the Web UI.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 72 LOYTEC
Figure 58: Schedule Configuration Page.
Version 4.0
Figure 59: Scheduled Presets Configuration Page.
You can switch back and forth between the two tabs. Once the configuration is complete, click on the Save button. This updates the schedule in the device. Any changes made become effective immediately.
On local schedulers the Web UI also allows to reconfigure the scheduled data points. This change takes effect immediately without a reboot of the device. To add and remove data points to the scheduler, go to the Data Points tab. The configuration page is depicted in
Figure 60. To add a new data point, click the
Add…
button. To remove a data point, select the data point in the list Scheduled Data Points by clicking on it and then press the
Remove button. Finally, store the changes by clicking the Save button. After modifying the scheduled data points, go back to the Presets tab and enter descriptive value label names.
For more information on how to configure a scheduler please refer to the Configurator
LOYTEC electronics GmbH
L-INX User Manual 73 LOYTEC
Figure 60: Re-configure scheduled data points on the Web UI.
4.2.19 Calendar
The Web interface provides the calendar page to edit its calendars at run-time, i.e. change the exception days. The calendar main page displays all available calendars. Click on the calendar to be edited. This opens the calendar configuration page. An example is shown in
The effective period defines when this calendar shall be in effect. Leave From and To at
‗*.*.*‘ to make this calendar always in-effect. Otherwise enter dates, such as ‗30.1.2000‘.
Version 4.0
Figure 61: Calendar Configuration Page.
On the remainder of this page, work from left to right. Click on a calendar pattern or create a new calendar pattern by clicking Add new entry . A calendar pattern defines a set of
pattern entries, which defines the actual dates or date ranges. In the example in Figure 61,
the calendar pattern Holidays is selected.
In the Pattern Configuration box, the calendar pattern‘s name can be edited. It also lists the entries. New entries can be added by clicking Add new entry . Existing entries can be
LOYTEC electronics GmbH
L-INX User Manual 74 LOYTEC
selected and edited in the box on the right-hand side. In the example in Figure 61, the date
14.7.* is selected, which means ―The 14.7. of every year‖. Other entry types such as Date
Range and Week-and-Day
can be selected. See Section 5.3.3 for more information about
defining exception dates.
4.2.20 Alarm
The Web interface provides the alarm page to view the currently pending alarms of its alarm data points. The alarm main page displays all available alarm data points. Alarm objects which have active alarms are displayed in red. Click on the alarm object to be viewed. This
opens the alarm summary page. An example is shown in Figure 62.
Figure 62: Alarm Summary Page.
Active alarms are highlighted red. Inactive alarms which have not been acknowledged are rendered in green. Alarms that can be acknowledged have an Ack button. Press on the Ack button to acknowledge the alarm. Depending on the technology, this and older alarm records will be acknowledged. Acknowledged, active alarms are rendered in red. Click on
Reload to refresh your alarm list.
Inactive alarms that have been acknowledged disappear from the list. To record historical
information about those alarms, the alarm log must be used. See Section 4.3.9 for the alarm
log Web interface.
4.2.21 IEC61131 Configuration
On the IEC61131 configuration page the user can download an IEC61131 program as well
as controlling the behavior of the IO driver, see Figure 63.
After downloading the IEC61131 program rebooting the L-INX is necessary in order to load and start the new IEC61131 program. After resetting the device check the PLC LED for a successfully started program.
Important! Downloading a new IEC61131 may result in the need for a new data point configuration.
Hence, take care about the requirements of the downloaded program and in case of a different set of IEC61131 variables use the L-INX configuration tool to adapt the data point configuration.
The data exchange of the IEC61131 program can be disabled by disabling the IO driver. As a result the IEC61131 program is not able to receive or send update from/to the appropriate data points. Hence, for debugging purpose, the data point values can be manipulated regardless of the data set from the IEC61131 program.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 75 LOYTEC
The information about the running program is also displayed. The IEC61131 program can be removed from the device by clicking the Remove button. The device needs to reboot after this action.
Figure 63: IEC61131 Configuration Page.
4.3 Device Statistics
The device statistics pages provide advanced statistics information about the CEA-709 device, the CEA-852 device, the BACnet device, the system log, the scheduler, the alarm log and the Ethernet interface.
4.3.1 System Log
The System Log page prints all messages stored in the system log of the device. An example
is shown in Figure 64. This log data is important for trouble-shooting. It contains log entries
for reboots and abnormal operating conditions. When contacting LOYTEC support, have a copy of this log ready.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 76 LOYTEC
Figure 64: System Log Page.
4.3.2 IP Statistics
Figure 65 shows the IP statistics page. It allows finding possible problems related to the IP
communication. Specifically, any detected IP address conflicts are displayed (if the device‘s
IP address conflicts with a different host on the network).
Version 4.0
Figure 65: IP Statistics Page.
LOYTEC electronics GmbH
L-INX User Manual 77 LOYTEC
4.3.3 CEA-852 Statistics
The CEA-852 statistics page displays the statistics data of the CEA-852 device on the device. It is only displayed if the CEA-852 interface is enabled and supported by the L-INX
model. The upper part of the CEA-852 statistics page is depicted in Figure 66. To update
the statistics data, press the button Update all CEA-852 statistics . To reset all statistics counters to zero, click on the button Clear all CEA-852 statistics . The field Date/Time of clear will reflect the time of the last counter reset.
Figure 66: Part of the CEA-852 Statistics Page.
4.3.4 Enhanced Communications Test
The Enhanced Communications Test allows testing the CEA-852 communication path between the CEA-852 device on the L-INX and other CEA-852 devices as well as the configuration server. The test thoroughly diagnoses the paths between individual members of the IP channel and the configuration server in each direction. Port-forwarding problems are recognized. For older devices or devices by other manufacturers, which do not support the enhanced test features, the test passes as soon as a device is reachable, but adds a
comment, that the return path could not be tested. A typical output is shown in Figure 67.
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 78 LOYTEC
Figure 67: Enhanced Communication Test Output.
The Round Trip Time (RTT) is measured as the time a packet sent to the peer device needs to be routed back to the LINX-10X. It is a measure for general network delay. If the test to a specific member fails, a text is displayed to describe the possible source of the problem.
The reasons for failure are summarized in Table 10.
Text displayed (Web icon) Meaning
OK, Return path not tested (green checkmark)
Not reachable/not supported
(red exclamation)
Local NAT config. Error
(red exclamation)
Peer not reachable
(red exclamation)
Displayed for a device which is reachable but which does not support the feature to test the return path (device sending to this CEA-852 device).
Therefore a potential NAT router configuration error cannot be detected. If the tested device is an L-IP, it is recommended to upgrade this L-IP to 3.0 or higher.
This is displayed for the CS if it is not reachable or the CS does not support this test. To remove this uncertainty it is recommended to upgrade the L-IP to
3.0 or higher.
This is displayed if the CEA-852 device of the LINX-10X is located behind a
NAT router or firewall, and the port-forwarding in the NAT-Router (usually
1628) or the filter table of the firewall is incorrect.
Displayed for a device, if it is not reachable. No RTT is displayed. The device is either not online, not connected to the network, has no IP address, or is not reachable behind its NAT router. Execute this test on the suspicious device to determine any NAT configuration problem.
Table 10: Possible Communication Problems.
4.3.5 CEA-709 Statistics
The CEA-709 statistics page displays statistics data of the CEA-709 port on the device as
shown in Figure 68. This data can be used to troubleshoot networking problems. To update
the data, click on the button Update CEA-709 statistics .
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 79 LOYTEC
Figure 68: CEA-709 Statistics Page.
4.3.6 OPC Server Statistics Page
The OPC server statistics page shows statistics data, which contains information on currently and previously connected clients. An example list of OPC clients is shown in
Update OPC statistics button retrieves the current statistics.
The Summary table on the top of the page displays the number of currently connected clients. These clients occupy TCP connections. The next line specifies the total number of accepted client connections since the device is running. The figure for rejected connections can be used to detect situations, where too many clients try connecting at the same time.
Version 4.0
Figure 69: OPC Server Statistics Page.
LOYTEC electronics GmbH
L-INX User Manual 80 LOYTEC
The Connection Details list shows more information on the history of client connections.
The green lines at the top denote currently active connections. Active connections have an idle time figure specified in seconds. The following lines in black represent a history of the most recent connections. Inactive connections read ―n/a‖ in the
Idle column.
All lines contain client information, which specifies the client IP address and port of the connected client. The Srvc column specifies the type of Web service (Web, DA, and DL).
The Agent column contains information on the HTTP agent of the client, and the Last
Action column contains information on the last known Web service SOAP action the client has requested.
4.3.7 BACnet MS/TP Statistics
The BACnet MS/TP statistics page is only available, when the MS/TP data link layer is
enabled (see Section 4.2.13) and supported by the L-INX model. An example is shown in
Figure 70. The separated part on the top of the table contains the most important statistics
data.
The MS/TP token status reports the current token passing state. In state OK , the token is circulating between the masters. This is the normal state, when multiple masters are on the
MS/TP network. The state SOLE MASTER is the normal state when the device is the only master on the network. If there are multiple masters on the network, this state is a hint to a broken cable. In state TOKEN LOST , the token is currently not circulating.
The counter MS/TP lost tokens is an indicator for communication problems on the
MST/TP network. If it increases, there is a cabling, ground, or termination problem. The counters Rcv OK and Send OK reflect the number of successfully received or transmitted
MS/TP frames. Check these counters to verify that communication is flowing on the MS/TP segment.
Version 4.0
Figure 70: BACnet MS/TP Statistics Page.
LOYTEC electronics GmbH
L-INX User Manual 81 LOYTEC
4.3.8 Scheduler Statistics Page
The scheduler statistics page provides an overview of what is scheduled at which day and which time. In the Display Schedules list, select a single schedule to view its scheduled values and times. Use the multi-select feature to get the overview of more schedules. An
example is shown in Figure 71.
Figure 71: Scheduler Statistics Page.
4.3.9 Alarm Log Page
The alarm log page provides an overview of all alarm logs on the system. Click on one of the links to view a specific alarm log. Each alarm log contains a historical log of alarm transitions. When an inactive and acknowledged alarm disappears from the alarm summary page (live list), the alarm log contains this last transition and maintains it over a reboot. An
example is shown in Figure 72.
To refresh the alarm log contents click on the Reload button. Currently active alarms cannot be acknowledged in this historical view. Follow the link to the attached alarm objects to get to the respective live lists, where alarms can be acknowledged on the Web
interface (see Section 4.2.20).
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 82 LOYTEC
Figure 72: Alarm Log Page.
The alarm log contents can be uploaded from the device in a CSV formatted file. Click on the button Upload Alarm Log to upload the current log. To clear the log, press the button
Clear Alarm Log . Please note, that this permanently purges all historical alarm log data of this alarm log.
4.4 L-WEB
This configuration page provides a download link to the L-WEB application installer and a
listing of L-WEB projects available on the device (see Figure 73). Clicking on
Install will
download the installer for L-WEB and start the installation process. See Section 9.2 for
more information on working with the L-WEB visualization.
Figure 73: L-WEB Page.
4.5 Reset, Contact, Logout
The menu item Reset allows two essential operations:
Rebooting the device from a remote location, or
Version 4.0 LOYTEC electronics GmbH
L-INX User Manual 83 LOYTEC
resetting the data point configuration from a remote location. This option clears all data points and the entire port configuration. It leaves the IP settings intact.
The Contact item provides contact information and a link to the latest user manual and the latest firmware version. The Logout item closes the current session.
Version 4.0 LOYTEC electronics GmbH