Type ME43
Fieldbus gateway büS to Industrial Ethernet for
PROFIBUS DPV1, PROFINET, EtherNet/IP,
EtherCAT, Modbus TCP, CC-Link,
Operating Instructions
We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous réserve de modifications techniques.
© Bürkert Werke GmbH & Co. KG, 2017 – 2019
Operating Instructions 1905/02_EUen_00810575 / Original DE
Type ME43
Fieldbus gateway type ME43
C ontents
3 english
Type ME43
4
General settings for the Gateway configuration
Fieldbus-specific address mapping
.........................................................20
Declaring inputs and outputs for the Gateway configuration .....................................22
...........................................................................25
Storage and download of the Gateway configuration
................................................30
..........................................................................................31
Setting the Ethernet parameters for EtherNet/IP, PROFINET, Modbus TCP ..............34
9.4.2 Establishing a connection between the device and Bürkert Communicator ..............38
english
Type ME43
12.2.2 Overview of device-specific setting options that can be adjusted using
5 english
6
Type ME43
The operating instructions
1 THE OPERATING INSTRUCTIONS
The operating instructions describe the entire life cycle of the device. Keep these instructions ready to hand at the operation site.
Important safety information!
▶ Carefully read these instructions.
▶ Observe in particular the safety instructions, intended use and operating conditions.
▶ Persons, who work on the device, must read and understand these instructions.
1.1 Symbols
DANGER!
Warns of an immediate danger!
▶ Failure to observe the warning will result in fatal or serious injuries.
WARNING!
Warns of a potentially dangerous situation!
▶ Failure to observe the warning may result in serious injuries or death.
CAUTION!
Warns of a potential danger!
▶ Failure to observe the warning may result in a moderate or minor injury.
NOTE!
Warns of damage!
▶ Failure to observe the warning may result in damage to the device or other equipment.
Indicates important additional information, tips and recommendations.
Refers to information in these operating instructions or in other documentation.
Designates an instruction which you must follow to prevent a hazard.
Designates a procedure which you must carry out.
Indicates a result.
MENUE Representation of software interface text.
english
Type ME43
The operating instructions
1.2
Begriffsdefinitionen
Definition of the terms used in these instructions.
• Device: the term “Device” stands for the following device types: ME43
• Ex area: the term “Ex area” stands for potentially explosive atmosphere
• Ex approval: the term “Ex approval” stands for approval in the potentially explosive atmosphere
• büS (Bürkert system bus): the term “büS” stands for the communication bus developed by Bürkert, based on the CANopen protocol.
2 INTENDED USE
Inappropriate use of the device may be dangerous to people, nearby equipment and the environment.
The fieldbus gateway Type ME43 is used as a fieldbus converter for the process values between büS participants and an industrial Ethernet PLC.
The Type ME43 supports the fieldbus protocols PROFIBUS DPV1, EtherCAT, PROFINET, EtherNet/IP,
Modbus TCP, CC-Link as well as DeviceNet and CANopen.
▶ When using the device, observe the permitted data, operating conditions and application conditions.
This information can be found in the contractual documents, the operating instructions and on the type label.
▶ In areas at risk of explosion, only use devices approved for use in those areas. These devices are labeled with a separate Ex type label. In use, note the information provided on the separate Ex type label and the additional explosion-related information or separate explosion-related operating instructions.
The device
▶ Do not use the device outside.
▶ Do not open the device.
▶ Use the device only in conjunction with third-party devices and components recommended and authorized by Bürkert.
▶ Only operate the device when in perfect condition and always ensure proper storage, transportation, installation and operation.
▶ Use only as intended.
english
7
Type ME43
Basic safety instructions
3 BASIC SAFETY INSTRUCTIONS
These safety instructions do not consider any contingencies or incidents which occur during installation, operation and maintenance. The operator is responsible for observing the location-specific safety regulations, also with reference to the personnel.
General hazardous situations.
To prevent injury, ensure the following:
▶ Operate the device only in perfect condition and in accordance with the operating instructions.
▶ Do not make any changes to the device and do not subject it to mechanical stress.
▶ Secure device or system to prevent unintentional activation.
▶ Only trained technicians may perform installation and maintenance work.
▶ Install the device according to the regulations applicable in the country.
▶ After an interruption in the power supply, ensure that the process is restarted in a controlled manner.
▶ Observe the general rules of technology.
NOTE!
Electrostatic sensitive components and modules.
The device contains electronic components which react sensitively to electrostatic discharge (ESD).
Contact with electrostatically charged persons or objects are hazardous to these components. In the worst case scenario, these components will be destroyed immediately or will fail after starting up.
• To minimize or eliminate the risk of damage resulting from sudden electrostatic discharges, ensure compliance with the requirements of EN 61340-5-1.
• Do not touch electronic components while the supply voltage is switched on!
8 english
Type ME43
General information
4
4.1
GENERAL INFORMATION
Contact address
Germany
Bürkert Fluid Control Systems
Sales Center
Christian-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10-91 111
Fax + 49 (0) 7940 - 10-91 448
Email: [email protected]
International
You can find the contact addresses on the internet at: www.burkert.com
4.2
Warranty
The warranty is only valid if the device is used as intended in accordance with the specified application conditions.
4.3
Information on the Internet
The operating instructions and data sheets for Bürkert products can be found on the Internet at: www.burkert.com english
9
Type ME43
Product description
5 PRODUCT DESCRIPTION
The fieldbus gateway type ME43 is used as a field bus converter between büS and Industrial Ethernet.
Application area:
Switch the process values between the devices of fieldbus 1 and fieldbus 2.
Device type
ME43
ME43
ME43
ME43
ME43
ME43
Table 1: Type ME43 application area
Fieldbus 1 büS büS büS büS büS büS
Fieldbus 2
PROFINET
EtherNet/IP
Modbus TCP
PROFIBUS DPV1
CC-LINK
EtherCAT
The Bürkert Communicator PC software is required to configure the fieldbus gateway.
The Bürkert Communicator PC software can be downloaded free of charge from the Bürkert website. In addition to the PC software, the USB-büS-interface set 1, available as an accessory, is required.
See chapter “15 Accessories”, page 64.
10 english
Type ME43
Technical data
6 TECHNICAL DATA
6.1
Conformity
The device conforms to the EU Directives as per the EU Declaration of Conformity (if applicable).
6.2
Standards
The applied standards, which are used to demonstrate conformity with the EU Directives, are listed in the EU type examination certificate and/or the EU Declaration of Conformity (if applicable).
6.3
Operating conditions
WARNING!
Risk of injury due to malfunction if device used outdoors.
▶ Do not use the device outdoors and avoid heat sources which may cause the permitted temperature range to be exceeded.
Permitted ambient temperature range. -20 °C to +60 °C
Operating altitude: up to 2000 m above sea level
6.4
Mechanical data
Dimensions: Refer to data sheet for Type ME43
Housing material: Polycarbonate
6.5
Electrical data
Supply voltage: 24 V ±10 % - residual ripple 10%
Power consumption < 2 W
Degree of protection: IP 20 according to EN 60529 / IEC 60529
(only if cables, plugs and sockets have been connected correctly) verified by Bürkert, not evaluated by UL
Protection class: 3 according DIN EN 61140 (VDE 0140)
Interfaces 1 spring-type terminal 5-pin for supply voltage and büS connection
PROFIBUS version: 1 plug-in connector D-Sub, 9-pin
CC-LINK version: 1 plug-in connector D-Sub, 9-pin
Industrial Ethernet version: 2 sockets for RJ45 plug-in connector
UL Devices: Limited Energy Circuit (LEC) according to UL/ IEC 61010-1
Limited Power Source (LPS) according to UL/ IEC 60950
SELV/ PELV with UL Recognized Overcurrent Protection dimensioned according to UL/ IEC 61010-1 Table 18
NEC Class 2 power source 11 english
Type ME43
Technical data
6.6
Type label, device labeling
Identification number of the device
QR code (link for further information to the device)
ID: 00307390
Type: ME43
S/N: 001001
W1XXXX
Type
Serial number
Manufacture code
CE mark
Permitted ambient temperature range
T amb
-20 °C...+60 °C
24 V | 2 W | IP20
Made in Germany
74653 Ingelfingen
Supply voltage,
Nominal power,
Degree of protection
12
Figure 1: Description of type label and device labeling
6.7
Industrial Ethernet
PROFINET IO specifications
Topology recognition
Minimum cycle time
IRT
MRP (Media Redundancy)
Additional supported features
Transmission speed
Data transport layer
PROFINET IO specification
(AR) Application Relations
LLDP, SNMP V1, MIB2, physical device
10 ms not supported
MRP Client is supported
DCP, VLAN priority tagging, Shared Device
100 Mbit/s
Ethernet II, IEEE 802.3
V2.3
The device can simultaneously process up to 2 IO-ARs,
1 Supervisor AR and 1 Supervisor DA AR.
EtherNet/IP specifications
Predefined standard objects
DHCP
BOOTP
Identity Object (0x01)
Message Router Object (0x02)
Assembly Object (0x04)
Connection Manager (0x06)
DLR Object (0x47)
QoS Object (0x48)
TCP/IP Interface Object (0xF5)
Ethernet Link Object (0xF6) supported supported english
Type ME43
Technical data
Transmission speed
Duplex transmission
MDI modes
10 and 100 Mbit/s
Half Duplex, full Duplex, autonegotiation
MDI, MDI-X, Auto-MDIX
Data transport layer Ethernet II, IEEE 802.3
Address Conflict Detection (ACD) supported
DLR (ring topology)
Integrated switch
CIP Reset services supported supported
Identity Object Reset Service of Type 0 and 1
Modbus TCP specifications
Modbus Function Codes
Mode
Transmission speed
Data transport layer
1, 2, 3, 4, 6, 15, 16, 23
Message Mode: Server
10 and 100 Mbit/s
Ethernet II, IEEE 802.3
EtherCAT SPECIFICATIONS
Maximum number of cyclic input and output data
Maximum number of cyclic input data
Maximum number of cyclic output data
Acyclic communication (CoE)
Type
FMMUs
Sync managers
Transmission speed
Data transport layer
512 bytes in sum
1024 bytes
1024 bytes
SDO,
SDO master-slave
SDO slave-slave (depending on master capability)
Complex slave
8
4
100 Mbit/s
Ethernet II, IEEE 802.3
6.8
PROFIBUS DPV1 specifications
Acyclic communication
Transmission speed
Maximum size of the transmitted data
DP V1 Class 1 Read/Write
DP V1 Class 1 Alarm
DP V1 Class 2 Read/Write/Data Transport
Fixed values from 9.6 kbit/s to 12 Mbit/s
Autodetect mode is supported
Input data: 244 bytes
Output data: 244 bytes english
13
Type ME43
Technical data
6.9
CC-Link specifications
Features
Remote I/O Station
Remote Device Station
Configurable number of occupied stations
Configurable number of extension cycles
Supported protocols only I/O points i/O points and Words
1...4
1, 2, 4, or 8
CC-Link version 2.0
CC-Link version 1.11
CC-Link version 2.0
Number of stations
Maximum number of input data up to 4 occupied stations
368 bytes
Maximum number of output data 368 bytes
Input data 112 bytes (RY) and 256 bytes (RWw)
Output data
Extension cycles
Transmission speed
112 bytes (RX) and 256 bytes (RWr)
1, 2, 4, 8
156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s
CC-Link version 1.1 and 2.0
Number of stations
Maximum number of input data up to 4 occupied stations
48 bytes
Maximum number of output data 48 bytes
Input data 4 bytes (RY) and 8 bytes (RWw) per occupied station
Output data
Transmission speed
4 bytes (RX) and 8 bytes (RWr) per occupied station
156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s
14 english
Type ME43
Installation
7 INSTALLATION
7.1
Safety instructions
WARNING!
Risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
▶ Secure system against unintentional activation.
▶ Following installation, ensure a controlled restart.
7.2
Mounting on standard rail
Electrical connection upwards
1.
Electrical connection downwards
1.
→ Tip device to the right and align with standard rail.
→ Tip device to the left and align with standard rail.
2.
→ Mount device in the lower guide of the standard rail.
2.
→ Mount device in the upper guide of the standard rail.
3.
→ Push device upwards while also swiveling it to the left; lock it into the upper guide of the standard rail.
3.
Figure 2: Mount device on standard rail english
→ Push device downwards while also swiveling it to the left; lock it into the lower guide of the standard rail.
15
16
Type ME43
Installation
7.3
Electrical connection
→ Connect 5-pin spring-type terminal in accordance with configuration.
Configuration of 5-pin spring-type terminal
Connector view Color of terminal Description
Red Supply voltage 24 V
White CAN H (büS connection)
Green
Blue
Black
Shielding
CAN L (büS connection)
GND
Table 2: Configuration of 5-pin spring-type terminal
7.4
Establishing connection to fieldbus
7.4.1
Industrial Ethernet
→ Insert the Ethernet cable into the sockets of the X1 and X2 interfaces.
The X1 and X2 interfaces for RJ45 plug-in connectors are equivalent.
Configuration of X1 and X2 interface
8
7
6
5
4
3
2
1
6
7
8
4
5
2
3
Pin Plug configuration RJ45
1 TX+
TX–
RX+
Not used
Not used
RX–
Not used
Not used
Figure 3: Configuration of X1 and X2 interfaces; connection to fieldbus
NOTE!
To ensure electromagnetic compatibility (EMC)
▶ Only use shielded Ethernet cables.
▶ Connect the Ethernet cables of all fieldbus participants to the standard rail to ground the cable shielding.
→ Apply supply voltage.
english
Type ME43
Installation
7.4.2
PROFIBUS version
Configuration of plug-in connector D-Sub, 9-pin
D-Sub, 9-pin
6
7
8
9
Figure 4:
1
2
3
4
5
3
4
Pin Signal
1 not used
2 not used
5
6
RxD/TxD-P
CNTR-P
DGND
VP
Function
Data line P (B conductor)
Repeater directional control
Ground for data signals and VP
+5 V supply for bus terminating resistor
7
8
9 not used
RxD/TxD-N not unsed
Data line N (A conductor)
PROFIBUS, Configuration of plug-in connector D-Sub, 9-pin
7.4.3
CC-Link version
Configuration of plug-in connector D-Sub, 9-pin
D-Sub, 9-pin
8
9
6
7
Figure 5:
1
2
3
4
5
5
6
7
8
9
2
3
4
Pin Signal
1 not used not used
DA
DG not used not used not used
DB not used
Function
Data line A
Data ground
Data line B
CC-Link, Configuration of plug-in connector D-Sub, 9-pin
Connection
Mandatory
Optional
Mandatory
Optional
Mandatory
Connection
Mandatory
Mandatory
Mandatory english
17
Type ME43
Start-up
8 START-UP
8.1
Safety instructions
WARNING!
Risk of injury from improper operation!
▶ Before start-up, it must be ensured that the operating personnel are aware of and fully understand the contents of the operating instructions.
▶ Note the safety instructions and intended use.
▶ Only trained and qualified personnel may start up the device or system.
18
8.2
Base settings
Sequence of base settings:
1. Select fieldbus protocol (not for PROFIBUS variant and CC-Link variant)
Description see chapter
“8.3 Selecting fieldbus protocol” .
2. Gateway configuration (if not yet available)
Description see chapter
“8.4 Configuration of the fieldbus gateway” .
3. Configuring büS network
Description see chapter “10 Setting up the büS network”.
4. Protocol settings for connecting the device to the PLC network
Description see chapter “8.5 Protocol settings for connecting the device to the PLC network”.
8.3
Selecting fieldbus protocol
Selection of the appropriate fieldbus protocol is a requirement for configuration of the device and connection to the network.
The setting can be made on the display of the device or on the PC using the Bürkert Communicator PC software.
If devices feature a PROFIBUS interface and CC-Link interface, the fieldbus protocol has been preset at the factory.
The menu for setting the fieldbus protocol is located in the Parameter detailed view.
Change to the Parameter detailed view:
To make the setting with the Bürkert Communicator in the navigation area, select Industrial communication .
To make the setting on the display, press menu key 2x.
You are in the detailed view Parameter.
Setting fieldbus protocol:
→ Select the fieldbus protocol in the Protocol menu.
You have selected the fieldbus protocol.
english
Type ME43
Start-up
8.4
Configuration of the fieldbus gateway
The “Bürkert Communicator” PC software and the büS stick, which is available as an accessory, are required for configuration, see chapter
The “Bürkert Communicator” software and a general description of it are available on the Bürkert homepage.
8.4.1
Preparing to configure the fieldbus gateway
1. Establish the connection with the Bürkert Communicator PC software.
See chapter “9.4.2 Establishing a connection between the device and Bürkert Communicator”
2. Open configuration area in the Bürkert Communicator.
→ Select Gateway XXXX in the navigation area.
To open the configuration areas, click on + .
3. Select fieldbus protocol.
→ Select Industrial communication . → Parameter → Protocol → Select fieldbus protocol.
The fieldbus protocol for industrial communication can also be set on the display of the device:
Parameter → Protocol
8.4.2
Methods for generating a Gateway configuration
There are different methods for configuring a fieldbus gateway in the Bürkert Communicator.
1. Downloading the Gateway configuration.
→ Industrial communication . → Parameter . → Gateway configuration
→ Downlading a gateway configuration file → Load gateway configuration to device
→ Specify storage location.
2.
Automatic gateway configuration.
→ Industrial communication . → Parameter . → Gateway configuration
→ Create a gateway configuration → Automatic gateway configuration
→ Specify storage location.
3. Regenerating a Gateway configuration.
Description of the required steps in the following chapters
“8.4.4 General settings for the Gateway configuration”
and
“8.4.5 Declaring inputs and outputs for the Gateway configuration” .
4. Editing the existing Gateway configuration.
Procedure identical to the regeneration of a Gateway configuration.
→ Finally, specify the storage location of the existing configuration.
19 english
Type ME43
Start-up
8.4.3
Maximum number of data values (objects)
Fieldbus protocol Input values
PROFIBUS DPV1 128
Output values
128
PROFINET
EtherNet/IP
Modbus TCP
128
128
128
128
128
128
EtherCAT
(ME43 until
A.03.02.00)
EtherCAT
(ME43 from A.7.5)
Table 3:
128
128
128
128
Maximum number of data values
Total number of values
244
256
256
256
176
Input bytes
244
512
504
512
512
160 512
Output bytes
244
512
504
512
512
512
8.4.4
General settings for the Gateway configuration
Procedure in the Bürkert Communicator:
→ Select Industrial communication . → Parameter .
→ Select Gateway configuration → Create a gateway configuration .
+
+
+
+
-
File
COMMUNICATOR
Device Edit View Options Tools
Desktop
Help
Industrial communication
Graph
+
büS
FLOWave
Gateway ME43
Parameter Diagnostics
Parameter
Maintenance
Creation of a gateway configuration
Industrial communication
General settings
MFC_01
MFC_02
MFC_03
ProcessValve_01
Protocol selection
PROFINET
EtherNet/IP
ModbusTCP
PROFIBUS
Edit existing configuration
CANopen
EtherCAT
DeviceNet
Start new configuration
Total number of bytes
244
1024
1008
2048
1024
1024
20
Figure 6:
100%
Configuration, select target protocol
→ Select target protocol in the window Protocol Selection . It is possible to select several protocols.
When selecting several, the configuration files will be created for the selected target protocols based on the following IO-value configuration.
→ Select Edit existing configuration or Start new configuration .
english
Type ME43
Start-up
Creation of a gateway configuration
General settings
General device settings
Product code
Product family
Product name
Description
1296380467
Gateway
ME43
Gateway_ME43_bueS
Default network settings
IP address of gateway
Network mask
Default gateway
Advanced
192.168.0.100
255.255.255.0
192.168.0.1
Information for inputting see
“Table 4: Gateway configuration; input fields for “General device settings””, page 21
Cancel
Figure 7: Configuration, general settings
Gateway configuration General settings :
Next
Input field
Product code
Input
Inputting article number of the device or self-defined code.
Importance for the configuration
Unique device code.
Important when using several systems:
Assign a separate code for each system.
Product family
Table 4:
Product family.
Is used for classification in the PLC.
Gateway configuration; input fields for “General device settings”
→ Modify general settings for device description file of target system (PLC) (if necessary).
→ Select Next .
english
21
22
Type ME43
Start-up
8.4.5
Declaring inputs and outputs for the Gateway configuration
Create a gateway configuration
Declare inputs and outputs
– Products
– Electromotive Valves
332x E_Process_Valve
336x E_Process_Valve
328x Motor Control Valve
+ Process and Control Valves
+ Valve Islands
+ Sensors
...
0030739000000001
Inputs and outputs
% EVA_POS
EVA_SP_IO
EVA_PV_IO
– Input values
Generic number %
Binary value
Namur device state
Lenght
Density
...
O
Name
EVA_SPdigital l/min
EVA_SPdigital
– Output values
Generic number %
Binary value
Namur device state
Lenght
Density
...
Value type
Data type
Default value
Groups / Devices
EVA
Mass flow rate [l/min]
Floating point number
0 l/min
CANopen compatible
* Highlighted entries are available in the current network
Unit conversion
Back Cancel
Unité API: Flow rate: Liters per m
Next
Figure 8:
1. Selecting the products (devices) as well as the input values and output values
2. Declaring inputs and outputs
Example: selected output to be declared
(highlighted in grey)
Overview of the selected inputs and outputs
Display of the selected devices / device groups
(to delete, click on the X )
Declare inputs and outputs
1. Selecting the inputs and outputs:
The inputs and outputs to be declared are specified by selecting products or process values.
→ Open the list of products and process values by clicking on
The process values in the büS network are highlighted.
+ . english
Type ME43
Start-up
Adding products:
→ Add products by drag-and-drop or double-clicking.
Values for declaring inputs and outputs have been predefined in the Add device(s) dialogue box.
Add device(s)
Settings
Device name
(prefix for all value names)
Count
Max. possible number of inputs
Max. possible number of outputs
Device configuration
Postition Controller
Process Controller
EVA
1
128
128
^
Values per device
O i i i i i i i i i i i i i i POS
CMD
SP_IO
PV_IO
CMD_IO
XCO_DO1
XCO_DO2
DigitalIn
CMD_GW
SP_GW
PCOinactiv_GW
ExrError_GW
NamurStatus
PV_UserUnit
CMDdigital
Preview
Generated values: 3
EVA_POS
EVA_NamurStatus
EVA_CMDdigital O i i REAL Generic number %
UINT8 Namur device state
REAL Generic number %
Cancel OK
Figure 9: Gateway configuration; add products
Make the following settings in the dialogue box:
→ Accept or change Device name (max. 20 characters)
The name is used for protocol-specific grouping and to improve assignment in the network.
→ Select Count of the devices.
→ Select Device configuration (if selection option available).
→ Accept Values per device or select different values.
(to select, click on the square before the value).
The name of the value can be changed by overwriting it.
Adding process values:
→ Drag-and-drop or double click to add input values and output values.
Adding multiple values from the same unit at the same time:
→ Click on the unit with the right mouse button and then on the window Add multiple .
→ Add all of the required values.
english
23
24
Type ME43
Start-up
Contextualized definition of value:
Input values
Icon: i
Input values are values which come from the büS participant and are read by the PLC (büS device → fieldbus gateway → PLC)
Output values
Icon: O
Output values are values which are written from the PLC to the büS participant/fieldbus gateway.
Output value Continued output data Input value
büS device
Output value Input value Continued input data
Figure 10: Configuration; type of conversion for process values from the PLC to the büS device
2.
Adjusting properties of the values:
The properties for the values only require adjustment if deviations from the standard are requested.
→ In the overview click on the input value or output value to be declared.
The selected value is highlighted in grey.
The default values for the declaration are shown at bottom right.
Meaning of the default values.
The default values are used when the device starts or if the partner device was not found.
For the declaration input or select the following:
→ Accept or adjust Name . These names appear via the device description file in the target control.
→ Value type . Specify physical size or device status for the input or output.
→ Select or do not select Default value .
The standard value is accepted if no signal arrives from the partner device.
→ Select or do not select CANopen compatible .
Is selected when the values are consumed by a CANopen device.
→ Unit conversion .
Specifies in which physical unit the value is received or sent by the PLC.
You have selected and declared the inputs and outputs for the Gateway configuration.
→ Using Next , open the menu for the fieldbus-specific address mapping.
english
Type ME43
Start-up
8.4.6
Fieldbus-specific address mapping
→ Check editable fields and complete if necessary.
The protocol-specific settings are explained in the following screenshots
→ Select Next .
If multiple protocols are selected the corresponding protocol-specific configuration pages then appear (see
“Figure 6: Configuration, select target protocol” ).
Adress mapping for EtherNet/IP:
Create a gateway configuration
EtherNet/IP settings
EthernetIP Data
Major Revision
1
Order number
EtherNet/IP-EDS revision
1.1
EtherNet/IP product code 1.1
Minor Revision 7
EtherNet/IP product type Generic Device,keyable (43)
^
Addressing
Automatic EtherNet/IP addressing
Start Reset device
Cyclic Name
EVA_POS
Index SubIndex Assembly Connection Class (hex) Instance (hex) Attribute (hex)
0x2540 0x01 0x64 1 0x64 0x01 0x03
EVA_NamurStatus
EVA_CMDdigital
0x2541 0x01
0x2500 0x01
Device Status NamurNE107 0x2004 0x01
Control Word 0x3C32 0x01
0x64
0x65
0x66
0x67
1
1
2
2
0x64
0x65
0x66
0x67
0x01
0x01
0x01
0x01
0x03
0x03
0x03
0x03
Back Cancel Next
Overview of EtherNet/IP addressing
Automatic EtherNet/IP addressing
Start: Perform automatic EtherNet/IP addressing again
Reset device : Resets the values of columns 5 to 9 to 0.
Fieldbus-specific device data and access data
Figure 11: Gateway configuration; Adress mapping EtherNet/IP
25 english
26
Type ME43
Start-up
Adress mapping for PROFINET:
Create a gateway configuration
Profinet
Header Info
Main Family
Device ID
Gateway
0x23
^
Information Gateway_ME43_bueS
Advanced
Modul ID
Hardware version
Maximum input lenght
Information
0x100
A.01.01.00
1400
Gateway_ME23_bues
Byte
Addressing
Automatic PROFINET addressing
Minimum cycle time of the gateway
Software version
Maximum output lenght
Compatible DNS name
4
580515
1400
MEX3
Slot and subslot description: These fields are requird in the ............
Start Reset device ms
Byte
Advanced
Load the GSDML file for an advanced tabel restore
Cyclic Name
EVA_POS
EVA_NamurStatus
Control Word
Index SubIndex Slot Subslot Subslotindex
0x2540 0x01
0x2541 0x01
EVA_CMDdigital 0x2500 0x01
Device Status NamurNE107 0x2004 0x01
0x3C32 0x01
1
2
3
4
5
1
1
1
1
1
0
0
0
0
0
Modul ID GSDML slot description
201
202
301
203
302
GSDML subslot description
Back Cancel
Overview of PROFINET addressing
Automatic PROFINET addressing
Start: Perform automatic PROFINET addressing again
Reset device : Resets the values of columns 5 to 8 to 0.
Existing Profinet addressing can be restored by loading the GSDML file.
Next
Fieldbus-specific device data and access data
Figure 12: Gateway configuration; Adress mapping PROFINET english
Type ME43
Start-up
Adress mapping for ModbusTCP:
Create a gateway configuration
Modbus TCP settings
Bus Ident Data
Device Name: MEX3 MajorMinorRev 1.7
Addressing
Automatic Modbus-TCP addressing
Coil/Register addressing
^
Start Reset device
Start address 0
Start address 1
Use Modbus FC03 where possible
Cyclic Name
EVA_POS
EVA_NamurStatus
EVA_CMDdigital
Index SubIndex Size in byte
0x2540 0x01
0x2541 0x01
0x2500 0x01
Device Status NamurNE107 0x2004 0x01
Control Word 0x3C32 0x01
4
1
4
1
4
Address range
3xxxx
1xxxx
4xxxx
1xxxx
4xxxx
8
2
0
0
Start address
0
Functioncode
Read: FC04
Read: FC02
Read: FC03, Write Single: FC06, Write...
Read: FC02
Read: FC03, Write Single: FC06, Write...
Back Cancel Next
Overview of Modbus TCP addressing
Automatic Modbus TCP addressing
Start: Perform automatic Modbus TCP addressing again
Reset device : Resets the values of columns 5 to 8 to 0.
Settings:
Coil/Register addressing Register addressing :
Coil addressing :
Use Modbus FC03 where possible :
Fieldbus-specific device data and access data
Figure 13: Gateway configuration; Adress mapping ModbusTCP english
27
Type ME43
Start-up
Adress mapping for EtherCAT:
Create a gateway configuration
EtherCAT
EtherCAT data
EtherCAT product code
EtherCAT revision
#xFDF9
#x00010002
Product code of the EtherCAT device, has to be a number, e.g. 12345678
EtherCAT revision of the device. Has to be a 8-digit hex-number and start with #x,...
Addressing
Automatic EtherCAT addressing
Start Reset device
Cyclic Name
EVA_POS
EVA_NamurStatus
Index
0x2540
0x2541
EVA_CMDdigital 0x2500
Device Status NamurNE107 0x2004
Control Word 0x3C32
SubIndex
0x01
0x01
0x01
0x01
0x01
Back Cancel
Overview of EtherCAT addressing
Automatic EtherCAT addressing
Start: Perform automatic EtherCAT addressing again
Reset device : Resets the values
Fieldbus-specific device data and access data
Figure 14: Gateway configuration; Adress mapping EtherCAT
Next
28 english
Type ME43
Start-up
Adress mapping for CC-Link
Create a gateway configuration
CC-Link
gui.gateway.CC-Linkdata gui.gateway.cclinkstationcycles
2 Station & Estension Cycle: SINGLE
^
Addressing
Automatic CC-Link addressing
Start Reset device
Cyclic Name
EVA_POS
EVA_NamurStatus
EVA_CMDdigital
Index
0x2540
0x2541
0x2500
Device Status NamurNE107 0x2004
Control Word 0x3C32
SubIndex
0x01
0x01
0x01
0x01
0x01
Startadresse
0x000
0x00C
0x000
0x00D
0x008
Back Annuler
Overview of CC-Link addressing
Automatic CC-Link addressing
Start: Perform automatic CC-Link addressing again
Reset device : Resets the values
Fieldbus-specific data
Figure 15: Gateway configuration; Adress mapping CC-Link
Next english
29
Type ME43
Start-up
8.4.7
Storage and download of the Gateway configuration
Creation of a gateway configuration
Final settings
Select output directory
Output directory
Create new major version
C:\User\Joe.Bloggs\AppData\Comuni Browse
30
Back Cancel Next
Figure 16: Selection of output list
→ In the dialogue box Final settings Select output directory.
→ Select Next .
The Gateway configuration is saved.
The download onto the device runs in the background.
The existing device description file is also located on the specified path in the subfolder.
→ Select Finish .
The configuration of the device is completed. The connection between the PLC and fieldbus gateway is established. The folder, in which the description files are located, opens automatically.
The following overview shows which files are generated during the Gateway configuration.
Gateway configuration file
Protocol-independent files
Buerkert-Gateway-date-.bgc
Buerkert-Gateway-Mapping-date-.xml
Folder no folder
BGC
Description
Buerkert-Gateway-date-.eds
EDS
Gateway configuration container.
Gateway mapping file.
The file is automatically downloaded to the device.
Gateway extension file.
The file is automatically downloaded to the device.
Files for CC-Link
0x1640_GatewayME43_4_V2.0_E4.cspp help_cclink.csv
PLC_CCLink
PLC_CCLink
Device description file. Import into the
PLC.
Overview of the cyclical and acyclical device values.
english
Type ME43
Start-up
Gateway configuration file Folder Description
Files for EtherCAT
EtherCAT-Buerkert-Gateway-date-.xml
help_ethercat.csv
PLC_EtherCAT
PLC_EtherCAT
Device description file.
Optional: Import into the PLC.
Overview of the cyclical and acyclical device values.
Files for EtherNet/IP
EthernetIP-Buerkert-Gateway-date-.eds help_ethernetip.csv/txt
Connection-X-In/Out_Importdata.L5X
PLC_EtherNetIP Device description file. Import into the
PLC.
PLC_EtherNetIP Overview of the cyclical and acyclical device values.
PLC_EtherNetIP Data type for Rockwell users. Used for each assembly.
Files for Modbus TCP
ModbusTCP-Buerkert-Gateway-date-.txt
help_modbusTcp.csv/txt
PLC_ModbusTCP Device description file.
PLC_ModbusTCP Overview of the cyclical and acyclical device values.
Files for PROFIBUS DPV1
BUER1234.gsd help_profibus.csv/txt
PLC_Profibus
PLC_Profibus
Device description file. Import into the
PLC.
Overview of the cyclical and acyclical device values.
Files for PROFINET
GSDML-V2.32-Buerkert-Gateway-date-.xml
GSDML-0078-0023-icon.bmp
help_profinet.csv/txt
Table 5:
PLC_Profinet
PLC_Profinet
PLC_Profinet
Device description file. Import into the
PLC.
Icon used together with the device description file.
Overview of the cyclical and acyclical device values.
Overview of the files which are generated during the Gateway configuration
8.4.8
büs network configuration
A büS network configuration is required to connect other büS devices successfully to the system and to connect to Type ME43.
Description see chapter “10 Setting up the büS network”
english
31
32
Type ME43
Start-up
8.5
Protocol settings for connecting the device to the
PLC network
The required settings depend on the fieldbus protocol.
To ensure that the settings can be made, the fieldbus protocol must be selected in the parameter detailed view:
Parameter → Protocol → Select protocol.
If devices feature a PROFIBUS interface and CC-Link interface, the fieldbus protocol has been preset at the factory.
8.5.1
Setting the PROFIBUS address
PROFIBUS address pre-configured at the factory: 126
The PROFIBUS address can be set on the display of the device or on the PC using the Bürkert Communicator PC software.
The menu for setting the PROFIBUS address is located in the Parameter detailed view.
Change to the Parameter detailed view:
For the setting using the Bürkert Communicator in the navigation area, select Industrial communication .
To make the setting on the display, press the menu key twice.
You are in the detailed view Parameter.
The PROFIBUS address can only be set when the fieldbus protocol PROFIBUS DPV1 has been selected. If devices feature a PROFIBUS interface, the fieldbus protocol has been preset at the factory.
Setting the PROFIBUS address:
→ On the display select PROFIBUS address and input PROFIBUS address.
→ In the Bürkert Communicator select address.
Protocol settings → PROFIBUS address and input PROFIBUS
→ Enter the address. Valid addresses: 0 to 126
If an address is set outside of the valid range, the device will display an error message.
You have set the PROFIBUS address to connect the device to the PLC network.
english
Type ME43
Start-up
8.5.2
Setting the CC-Link address
CC-Link address pre-configured at the factory: 64
The CC-Link address can be set on the display of the device or on the PC using the Bürkert Communicator
PC software.
The menu for setting the CC-Link address is located in the Parameter detailed view.
Change to the Parameter detailed view:
For the setting using the Bürkert Communicator in the navigation area, select Industrial communication .
To make the setting on the display, press the menu key twice.
You are in the detailed view Parameter.
The CC-Link address can only be set when the fieldbus protocol CCLink has been selected. If devices feature a CC-Link interface, the fieldbus protocol has been preset at the factory.
Setting the CCLink address: :
→ the display select CCLink address and input CC-Link address.
→ In the Bürkert Communicator select Protocol settings → CCLink address and input CC-Link address.
.
→ Enter the address. Valid addresses: 0 to 64
If an address is set outside of the valid range, the device will display an error message.
You have set the CC-Link address to connect the device to the PLC network.
8.5.3
Setting the EtherCAT address (Station Alias)
The Alias station (network node addressing) can be set using the Bürkert Communicator PC software.
The Alias station can only be set when the fieldbus protocol EtherCAT has been selected.
For the setting using the Bürkert Communicator in the navigation area, select Industrial communication .
You are in the detailed view Parameter.
Setting Station Alias:
→ Select Protocol settings → Station Alias or Assistant .
→ Enter the address. Valid addresses: 0 to 65536.
If an address is set outside of the valid range, the device will display an error message.
You have set the Alias station to connect the device to the PLC network.
33 english
Type ME43
Start-up
8.5.4
Setting the Ethernet parameters for EtherNet/IP, PROFINET,
Modbus TCP
With Modbus TCP the setting of the Ethernet parameters is mandatory.
The EtherNet parameters can be set on the display of the device or on the PC using the Bürkert Communicator
PC software or the Webserver.
The menu for setting the EtherNet parameters is located in the Parameter detailed view.
Change to the Parameter detailed view:
For the setting using the Bürkert Communicator in the navigation area, select Industrial communication .
To make the setting on the display, press the menu key twice.
You are in the detailed view Parameter.
The Ethernet parameters can only be set when the corresponding fieldbus protocol has been selected. Parameter → Protocol → Select protocol.
Setting Ethernet parameter:
→ On the display select IP settings and input IP address.
→ In the Bürkert Communicator select input the parameters:
Protocol settings → Assistant or select Protocol settings and
• IP mode can be set for EtherNet/IP only. Setting in the menu IP settings.
Pre-configured at the factory: Static IP address .
• DNS compatible name can be set for PROFINET only.
• Static IP address Pre-configured at the factory: 192.168.0.100
• Network mask Pre-configured at the factory: 255.255.255.0
• Default gateway Pre-configured at the factory: 192.168.0.1.
You have set the Ethernet parameters to connect the device to the PLC network.
34 english
Type ME43
Operation
9 OPERATION
9.1
Safety instructions for operation
WARNING!
Danger due to improper operation.
▶ The operating personnel must be aware of and have understood the contents of the operating instructions.
▶ Note the safety instructions and intended use.
▶ Only adequately trained personnel may operate the system or device.
9.2
Operating elements of Type ME43
Arrow key, up arrow
Arrow key, down arrow
Menu key
Cover
Card holder for Micro SD card
Figure 17: Overview of the operating elements
9.3
Operation of Type ME43 using the display
Operation using the display is achieved by means of the two arrow keys and the round menu key.
Opening the main menu:
→ Press the menu key twice.
First the start screen appears, then the main menus with the detailed views Parameter , Diagnostics and Maintenance .
Returning from a menu:
→ Using the arrow keys, select Exit or Abort or Save and confirm using the menu key .
Effect of the selection:
Exit Returns to the next menu level up.
Abort Rejects any unsaved settings and returns to the next menu level up.
Save Saves any changed settings and returns to the next menu level up.
35 english
Type ME43
Operation
9.3.1
Description of the keys
Element
Down arrow key
Description
Page down through menu
Decrease numerical values. Hold down arrow key to run through quickly.
Up arrow key Page up through menu
Increase numerical values. Hold down arrow key to run through quickly.
Menu key
Open main menu (press the menu key twice)
Confirm selection
Confirm input
Table 6: Description of the keys
36 english
Type ME43
Operation
9.4
Operation of Type ME43 using the “Bürkert
Communicator” software
The device can be configured on the PC using the “Bürkert Communicator” software.
The PC software “Bürkert Communicator” can be downloaded free of charge from the Bürkert website.
In addition to the software, the USB büS interface set 1, available as an accessory, is required.
This chapter only describes the fundamental handling of Bürkert Communicator. A detailed description of the operation and configuration of the PC software “Bürkert Communicator” can be found on the website www.
burkert.com → Type 8920.
9.4.1
Bürkert Communicator user interface
Navigation area
Menu bar
File
Add interface
(Connect with
USB-büS-Interface)
COMMUNICATOR
Device Edit View Options
1
Tools Help
General settings
Start page
Desktop Parameter Diagnostics Maintenance
Graph büS
Alarm limits büS on COM3
Gateway ME43
Industrial communication
Diagnostics
PDO Configuration
Configuration provider
General settings
Display
1
Zoom 100%
Configuration areas of the device
Device
Figure 18: Bürkert Communicator user interface
Menus
Detailed views Parameter Diagnostics Maintenance
37 english
Type ME43
Operation
9.4.2
Establishing a connection between the device and Bürkert
Communicator
The Bürkert Communicator can be connected to the device via a büs network or with the büS stick.
→ Install the Bürkert Communicator software on the PC.
→ Use the büS stick to establish the connection between the device and the PC.
Not required for devices within a büS network.
→ Open Bürkert Communicator.
→ Select New project → büS-Project on the start page.
→ Select büS stick or büS over network and follow the further instructions in the dialogue boxes .
→ Finish .
You have established the connection between the device or the network and Bürkert Communicator.
The device or devices in the network are displayed in the navigation area.
Alternatively on the home page the device can be connected to the Bürkert Communicator also via the menu bar.
→ In the menu bar, click on the icon for Add interface .
38 english
Type ME43
Operation
9.5
Importing and saving data using the Micro SD card
The Micro SD card can be used to save and transfer device-specific values and user settings to a different device.
The Micro SD card is not suitable for backups. If the Micro SD card of the device is re-inserted at a later date, the most recently saved data is not restored. The function of the Micro SD card is limited to exchanging data.
Note!
By resetting the device to the factory settings, the data saved on the SD card is also reset.
A Micro SD card which has just been inserted is checked for existing data during device restart. If applicable, this data is accepted or overwritten:
• The Micro SD card does not contain any data.
The existing device-specific values and user settings are saved on the Micro SD card.
• The Micro SD card contains data which is compatible with the device.
The Micro SD card data is imported by the device. The existing device-specific values and user settings are overwritten.
• The Micro SD card contains data which is not compatible with the device.
The device overwrites the data on the Micro SD card with its own device-specific values and user settings.
NOTE!
Do not use conventional retail Micro SD cards for the device.
The inserted Micro SD card is a special industrial-grade version which is particularly durable and tem perature-resistant.
Purchase the Micro SD card for the fieldbus gateway ME43 via your Bürkert sales branch only.
The Micro SD card is available as an accessory, see “15 Accessories”.
english
39
Type ME43
Operation
Replacing the Micro SD card
Card holder for Micro SD card
Cover
Figure 19: Replacing the Micro SD card; fieldbus gateway ME43
NOTE!
Do not remove the SD card while the supply voltage is applied.
If the SD card is removed while the supply voltage is applied, data may be lost and the SD card may be damaged.
The SD card can be inserted while the supply voltage is applied.
A restart is required to ensure that the device detects the SD card.
Removing the Micro SD card:
→ 1. Carefully pull the cover out of the recess.
→ 2. Rotate the cover upwards to the left.
→ 3. Press on the edge of the engaged Micro SD card to unlock it.
→ 4. Remove the Micro SD card.
Inserting the Micro SD card in replacement device:
Insert the memory card the right way around.
→ Insert the Micro SD card into the card holder.
Ensure that the Micro SD card clicks into place.
→ Close the card holder using the cover.
40 english
Type ME43
Operation
9.6
Display elements of the Type ME43
Display
Status LED for indicating device status
LEDs for network connection to the Industrial Ethernet
(not present with
PROFIBUS version and
CC-Link version)
RJ45
Link LED
(yellow)
Link/Act LED
(green)
Figure 20: Overview of the display elements
9.7
LEDs for indicating the network connection to the
Industrial Ethernet
The PROFIBUS version and CC-Link version has no status indicator for the network connection.
The network connection is established via a D-Sub, 9-pin plug-in connector.
Description:
LED status
Link LED
(yellow)
Link/Act
LED
(green)
Active
Not active
Active
Description and cause of error
Connection to the network established.
No connection to the network available.
Rapid flashing: Connection to the higher-level protocol layer
(PROFINET, EtherNet/IP or Modbus TCP) has been established.
Data being transmitted.
Slow flashing, around 20 seconds after restart.
No connection established to protocol layer.
Procedure
-
Check cables.
Table 7:
Not active
No connection to the network available.
Description: LEDs for network connection
Check cables.
41 english
Type ME43
Operation
9.8
LED for indicating device status
The LED that indicates the device status changes color and status in accordance with NAMUR NE 107.
If several device statuses exist simultaneously, the device status with the highest priority is displayed. The priority is determined by the severity of the deviation from standard operation (red = failure = highest priority).
Displays in NAMUR mode:
Display in accor dance with NE 107
Color Color code
5 red
Description Meaning
4
3
2
1 orange yellow blue green
Failure, error or malfunction
Malfunction. The functionality of the device is not guaranteed.
Function check The device is searching for a büS device, this status is terminated after a few seconds.
Out of specification
Ambient conditions or process conditions for the device are outside the specified area.
Internal device diagnostics point to problems in the device or the process properties.
Data sheet values cannot be complied with.
Maintenance required
Based on a running diagnostic, the device has detected and corrected a deviation. Device functionality restricted.
The device is in controlled operation, although a function is briefly restricted.
→ Service device.
Diagnostics active
Device is operating perfectly. Status changes are indicated in different colors.
Messages are transmitted via a possibly connected fieldbus.
0
Table 8: white Diagnostics inactive
Device is switched on. Statuses are not displayed. Messages are not listed in the message list or transmitted via any connected fieldbus.
Device is running within its specifications.
Display of device status in NAMUR mode
42 english
Type ME43
Setting up the büS network
10 SETTING UP THE büS NETWORK
10.1
Conversion Industrial Ethernet to büS
The function of the fieldbus gateway is to convert the process values between an Industrial-Ethernet PLC and büS devices. For this, the fieldbus gateway ME43 must be configured and parameterized.
10.2
Theoretical principles for the selection of büS devices and process values
Select the büS devices that are to communicate with the PLC via the fieldbus gateway ME43:
Fieldbus gateway büS device 1 büS device 2
Figure 21: Configuration; selection of the büS devices that are to communicate with the PLC
Select which process values are to be converted from “Industrial Ethernet” to “büS”:
Fieldbus gateway
Set-point value 1 büS device 1
Actual value 1
Set-point value 2 büS device 2
Actual value 2
Figure 22: Configuration; selection of the process values that are to be converted from “Industrial Ethernet” to “büS”
43 english
44
Type ME43
Setting up the büS network
Define the direction for transmission of the process values (from/to PLC, from/to büS device):
The direction is assigned from the perspective of the fieldbus gateway ME43 in the fieldbus büS.
Example:
- The set-point values of a büS device are the output values of the fieldbus gateway ME43.
- The actual values of a büS device are the input values of the fieldbus gateway ME43.
Process output values of the PLC are received by the fieldbus gateway ME43 as process input values via
Industrial Ethernet. These process input values are converted and provided as process output values via büS.
Conversely, process output values of the büS device are received as büS input values. These process input values are converted and output as process output values via Industrial Ethernet .
Fieldbus gateway
Output value Input value Output value Input value
büS device
Input value Output value Input value Output value
Conversion of the process values
Industrial Ethernet
Figure 23: Configuration; principle of direction allocation for process values
büS
Based on the type of conversion, büS devices can be addressed directly using their process values and the direction of conversion.
Output value Continued output data Input value
büS device
Output value Input value Continued input data
Figure 24: Configuration; type of conversion for process values from the PLC to the büS device english
Type ME43
Setting up the büS network
10.3
Configuration of the büS network
→ Establish the connection with the Bürkert Communicator PC software.
See chapter “9.4.2 Establishing a connection between the device and Bürkert Communicator”
Procedure in Bürkert Communicator:
→ Select büS in the navigation area.
→ Select detailed view büS-Map .
–
+
+
File
COMMUNICATOR
Communication Edit View Options Tools
büS
Help
Overview büS-Map
Start page
Desktop
Graph büS
FLOWave
Gateway ME43
Gateway_01
Other
Actual Flow PR...
Actual Flow 02 01
Actual Flow PR...
Actual Flow 02 02
Setpoint PRO 01
Setpoint 02 01
Setpoint PRO 02
Setpoint 02 02
Flow_Gesamt
ActFlowGas 1
ActFlowGas 2
Anteil_Propan
SetpointGas 1
SetpointGas 2
NamurStatus
MFC_02
Sensor
Actual Flow
Medium Temp.
Current Totalizer
Controller
Current Setpoint
Setpoint
Manual Setpoint
Actuator
Current Dutycycle
Dutycycle
Other
NamurStatus
+ -
100%
Figure 25: büS-Map
→ Using drag and drop, parameterize the inputs and outputs.
(Dashed line connections represent as yet inactive connections between devices.
Compatible connection points are highlighted in blue.)
→ Select Apply changes .
All configured devices are restarted.
You have configured the büS network.
english
45
46
Type ME43
Setting up the büS network
10.4
Download gateway configuration file for device configuration
If, for instance, a configuration file exists from a previous project, the device can be directly configured with it.
→ Establish the connection with the Bürkert Communicator PC software.
See chapter
“9.4.2 Establishing a connection between the device and Bürkert Communicator”
Procedure in Bürkert Communicator:
→ Select Gateway ME43 in the navigation area.
To open the configuration areas, click on + .
→ Select Industrial communication .
→ Select Gateway configuration .
→ Select Downloading a gateway configuration file .
-
File
COMMUNICATOR
Device Edit View Options Tools Help
Industrial communication
Start page
Gateway_01
Desktop
Graph Parameter Diagnostics Maintenance büS Parameter Downloading a gateway configuration file
+
-
FLOWave
Gateway ME43
Gateway configuration
General gateway settings
Industrial Communication
Load configuration to device
General settings Load gateway configuration from device
+
+
+
MFC_01
MFC_02
ProcessValve_01 Advanced view
Restart
100%
Figure 26: Downloading a gateway configuration file
→ Select Load configuration to the device .
→ Specify the name and location of the file.
→ Use Restart to perform a device restart.
You have configured the device with the gateway configuration file.ndus
english
Type ME43
Web server
11 WEB SERVER
The configuration of the Ethernet participant, required to connect to the network, can be run with a Webserver, the Bürkert Communicator or on the display.
11.4.1
Connection to the web server
→ Setting IP address in the network card of the PC.
IP address: 192.168.0.xxx
For xxx enter any numerical value except 100
(Ethernet device is delivered with 100 occupied by IP address).
→ Connect the PC to the Ethernet device with a network cable.
11.4.2
Access to the web server
Bürkert ME43 Gateway
Industrial Communication
Protocol
Communication status
PROFINET
Waiting to establish communication
DNS compatible name
MAC address DC:B0:58:99:00:99
Static IP address
192.168.0.100
Network mask
255.255.255.0
Default gateway
192.168.0.1
Temporary IP address
IP settings
192.168.0.100
None
Figure 27: Access to the web server via the Default IP
S/N: 99
47 english
48
Type ME43
Web server
With EtherNet/IP, it is also possible to set DHCP or BOOTP (NOT standard).
The IP address is acquired from a DHCP server.
→ Open an Internet browser.
→ Input Default IP 192.168.0.100
.
(For Ethernet/IP devices the IP address is assigned via a DHCP server. If no assignment occurs within
1 minute via DHCP, the device uses the Default IP 192.168.0.100.)
The software for configuration of the Ethernet device is now available on the PC.
Configuration of several devices:
All devices are delivered with the same IP address (192.168.0.100). To ensure that the device can be identified for the configuration, the network may contain only 1 device which has not yet been configured.
▶ Connect the devices (Ethernet device) in succession, individually to the network and configure.
11.4.3
Configuring Ethernet device
Logging into the system:
→ Input user name and password. User name: admin
Password: admin
Bürkert ME43 Gateway
User login
User name
User password admin admin
Login
Figure 28: Logging into the system
S/N: 99
x
english
Type ME43
Web server
Configuration:
→ Input device name and IP address for the Ethernet device.
The device name (DNS-compatible name) will be used later for project planning (e.g. in STEP 7).
→ Activate with Commit changes .
To accept the changed PROFINET parameters, the voltage must be reset in the Ethernet device.
→ Restart device with Restart device .
Bürkert ME43 Gateway
Network configuration
Protocol
DNS compatible name
PROFINET
Static IP address
192.168.0.100
Network mask
255.255.255.0
Default gateway
IP settings
192.168.0.1
None
Commit changes
Figure 29: Configuring Ethernet device
S/N: 99
Restart device
english
49
Type ME43
Other setting options
12 OTHER SETTING OPTIONS
12.1
Settings on the display of the fieldbus gateway ME43
Settings adjusted on the display can also be adjusted using the PC software “Bürkert
Communicator”.
Overview:
Detailed view on display
Setting
Parameter Adress Set PROFIBUS address 1)
Adress Set CC-Link address 2)
Set IP mode 3)
IP set Set IP address 4)
Choice: Static IP , BOOTP , DHCP
Diagnosis
Protocol Set field bus protocol 5)
BueS
Display
Baudrate Set baud rate
NodeID Set node ID
Contrast Set contrast of the display
Brightness Set brightness of the display
Mounting Set mounting position of the device
Off Activate configuration provider CfgProvid.
On Deactivate configuration provider
Display of errors by error code.
Error description see chapter “14.1 Description of the error codes”.
Maintena..
Restart of the device
Ident. no Identification number of the device is displayed
Serial no.
Serial number is displayed
SW version Software version is displayed
HW version Hardware version is displayed büS vers.
büS version is displayed
IComm vers.
IComm version is displayed
DEVReplace can be used in conjunction with configuration provider.
Table 9: Setting options on the display of the fieldbus gateway ME43
50
1) Only for PROFIBUS DPV1.
2) Only for CC-Link.
3) Only for EtherNet/IP.
4) Only for PROFINET, EtherNet/IP and Modbus TCP.
5) Only for PROFINET, EtherNet/IP, EtherCAT and Modbus TCP english
Type ME43
Other setting options
12.2
Settings using the PC software
“Bürkert Communicator”
The device can be configured on the PC using the “Bürkert Communicator” software.
The PC software “Bürkert Communicator” can be downloaded free of charge from the Bürkert website.
In addition to the software, the USB büS interface set 1, available as an accessory, is required.
12.2.1
f(x) configuration
The configuration area f(x) configuration includes the menu for the configuration of other device functions.
The f(x) configuration enables functions to be extended using free programming based on a graphical pro gramming interface.
Examples of functions are e.g. a timer, a graphical program or a controller.
Information and the instructions for the software of the f(x) configuration can be found on the
Bürkert website under Type 8922.
12.2.2
Overview of device-specific setting options that can be adjusted using Bürkert Communicator
The list of setting options shown below only includes the device-specific options for the fieldbus gateway
ME43 and does not include the description of the PC software Bürkert Communicator.
A detailed description of the operation and configuration of the PC software “Bürkert Communi cator” can be found on the website www.burkert.com → Type 8920.
Bürkert Communicator: Industrial Communication configuration area
Detailed view Menu
Maintenance Version numbers
Table 10:
Web server
Reset device
Stack Name
Stack Version
Stack Build
In these menus the current values are displayed, not set.
Stack Revision
Stack Date
ICom Version
Activate web server Activate or deactivate web server
Set admin password assign password for administrator
Restart
Hardware reset of industrial communication
Restore SML data
Setting options in Bürkert Communicator, Industrial Communication configuration area – maintenance detailed view
51 english
Type ME43
Other setting options
52
Bürkert Communicator: Industrial Communication configuration area
Detailed view Setting
Parameter Select Protocol
For a description see chapter “Setting up the büS network”.
Table 11:
Protocol settings for PROFIBUS DPV1
Protocol settings for EtherCAT
Protocol settings for PROFINET
Protocol settings for EtherNet IP
Set PROFIBUS address .
Set baud rate Change baud rate.
Advanced settings
Set Internal cycle time .
Set Control mode settings .
Protocol firmware update
Specify Assistant for checking input and start conditions for büS communication.
Set Station Alias .
MAC address is displayed.
Advanced settings
Set Internal cycle time .
Set Control mode settings .
Protocol firmware update
Specify Assistant for checking input and start conditions for büS communication.
Set DNS compatible name .
Set Static IP address .
Set Network mask .
Set Default gateway .
Specify Temporary IP address .
MAC address is displayed.
Advanced settings
Set Alarm settings whether or when an alarm is output (may be overwritten by the controller).
Set Internal cycle time .
Set Control mode settings .
Protocol firmware update
Specify Assistant for checking input and start conditions for büS communication.
IP settings Set BOOTP or DHCP.
Set Static IP address .
Set Network mask .
Set Default gateway .
Specify Temporary IP address .
MAC address is displayed.
Advanced settings
Set Internal cycle time .
Set Control mode settings .
Protocol firmware update
Setting options in Bürkert Communicator, Industrial Communication configuration area – parameter detailed view – view 1 english
Type ME43
Other setting options
Bürkert Communicator: Industrial Communication configuration area
Detailed view Setting
Parameter Protocol settings for Modbus TCP
Protocol settings for CC-Link
Specify Assistant for checking input and start conditions for büS communication.
Set Static IP address .
Set Network mask .
Set Default gateway .
MAC address is displayed.
Advanced settings Set Internal cycle time .
Activate Communication Timeout .
Set Control mode settings .
Protocol firmware update
Set CCLink address .
Change Set baud rate CCLink .
Advanced settings Set Internal cycle time .
Set Control mode settings .
Protocol firmware update
Table 12:
Gateway configuration
Unit conversion
Hide process values
Downloading a gateway configuration file
Load configuration to device
Load gateway configuration from device
Restart Restart of the device: The restart is required to apply the configuration.
Create a gateway configuration
For a description see chapter
“8.4 Configuration of the fieldbus gateway”.
Specify physical unit for the input data and output data of the
PLC.
Edit hide objects
Reset hide objects
Setting options in Bürkert Communicator, Industrial Communication configuration area – parameter detailed view – view 2
Bürkert Communicator: Industrial Communication configuration area
Detailed view Menu
Diagnostics Protocol
Communication status
Control mode settings
Connection to PLC
Used internal cycle time
Advanced Last status code
Table 13:
In these menus the current values are displayed, not set.
Setting options in Bürkert Communicator, Industrial Communication configuration area – diagnostics detailed view
53 english
54
Type ME43
Other setting options
Bürkert Communicator: General settings configuration area
Detailed view Menu
Parameter büS
Alarm limits
Diagnostics
PDO
Configuration
Configuration provider
Display
Configuration of the büS interface.
Displayed name Assign for display and Bürkert Communicator.
Location Specify location displayed for the device.
Description Enter description text for tooltips.
Advanced Unique device name For partner allocation.
Specify Baud rate .
Specify CANopen address .
Bus mode Setting büS interface mode.
Set Show errors from büS partners to indicate whether or not and from which consumer the errors are displayed.
Deallocation delay Time from loss of a partner to deletion of its configuration.
Set limits from which the device outputs a warning or error.
Supply voltage Set alarm limit for supply voltage.
Device temperature Set alarm limit for device temperature.
Warning battery voltage low Value is displayed.
Activate or deactivate diagnostic.
Configure process data objects.
PDO 1
Reset to default values
Status Activate or deactivate configuration provider
Remove all client configurations Set behaviour after device restart.
Force reconfiguration of all clients Set behaviour after device restart.
Ignore offline clients Activation or deactivation
Set display of device.
Brightness Set brightness of the display.
Contrast Set contrast of the display.
Mounting position Set mounting position of the device.
Language Set language.
Screen saver Set Wait time .
Set Brightness .
Table 14: Setting options in Bürkert Communicator, General Settings configuration area – parameters detailed view english
Type ME43
Other setting options
Bürkert Communicator: General settings configuration area
Detailed view Menu
Diagnostics Device status Operating duration
Device temperature
Supply voltage
Voltage drops Number of voltage drops since restart.
Min./Max. values Max. temperature
Min. temperature
Max. supply voltage
Min. supply voltage
Device boot counter
Transferable memory status
In these menus the current values are displayed, not set. büS status
Current system time
Battery voltage
Receive errors Number of received errors since restart.
Receive error max.
The most severe reception error that was produced relative to the device status is displayed.
The indicator can be reset to 0.
Transmit errors Number of transmit errors since restart.
Transmit errors max.
The most severe send error that was produced relative to the device status is displayed.
The indicator can be reset to 0.
Reset error counter
CANopen status operational or preoperational
Logbook The logbook lists all warnings and error messages, specifying the type, time and signature.
The messages listed in the logbook can be updated, saved and deleted.
Table 15:
Configuration provider
Status
Number of managed clients
- Thereof number of offline configurtions
- Thereof number of forced reconfigurations
Number of reconfigured clients since restart.
´Number of loaded client configurations since restart.
Number of missing clients since restart.
Number of failed configuration loads since restart.
Number of failed reconfigurations since restart.
In these menus the current values are displayed, not set.
Setting options in Bürkert Communicator, General Settings configuration area – diagnostics detailed view
55 english
Type ME43
Other setting options
Bürkert Communicator: General settings configuration area
Detailed view Menu
Maintenance Device information Displayed name Is only displayed if a name has been input in the menu of the same name in the parameters detailed view.
Ident. number Identification number of the device.
Serial number of the device.
Software ident. number
Software version büS version
Hardware version
Product type number
Manufacture date eds version f(x) version
Device driver Driver version
Firmware group
DLL version
Origin
In these menus the current values are displayed, not set.
Reset device Restart Restart of the device.
Reset to factory settings Reset device to factory setting.
Table 16: Setting options in Bürkert Communicator, General Settings configuration area – maintenance detailed view
56 english
Type ME43
Maintenance
13 MAINTENANCE
13.1
Safety instructions for maintenance
WARNING!
Risk of injury from improper maintenance work.
▶ Maintenance may be carried out only by trained technicians and with the appropriate tools.
▶ Secure system against unintentional activation.
▶ Following maintenance, ensure a controlled restart.
13.2
Replacement of the fieldbus gateway ME43
Procedure:
1. Switch off supply voltage.
2. Remove 5-pin spring-type terminal.
Figure 30: Remove 5-pin spring-type terminal
3. Remove Ethernet cable from the X2 and X2 interfaces.
For the PROFIBUS version and CC-Link version: Remove plug-in connector D-Sub, 9-pin.
4. Remove the device from the standard rail.
Figure 31: Remove the device from the standard rail
→ Push the device upwards and detach it from the upper guide of the standard rail.
english
57
Type ME43
Maintenance
5. Remove the Micro SD card
Card holder for Micro SD card
Cover
Figure 32: Replacing the Micro SD card; fieldbus gateway ME43
→ Carefully pull the cover out of the recess.
→ Rotate the cover upwards to the left.
→ Press on the edge of the engaged Micro SD card to unlock it.
→ Remove the Micro SD card.
6. Insert Micro SD card in replacement device:
Insert the memory card the right way around.
→ Insert the Micro SD card into the card holder. Ensure that the Micro SD card clicks into place.
→ Close the card holder using the cover.
7. Attach the replacement device to the standard rail
58
Figure 33: Attach the device to the standard rail
→ Tip device to the right and align with standard rail.
→ Mount device in the lower guide of the standard rail.
→ Push device upwards while also swiveling it to the left; lock it into the upper guide of the standard rail.
8. Connect the replacement device electrically
→ Attach the 5-pin spring-type terminal to the device.
→ Insert the Ethernet cables in the sockets X1 and X2 (for plug-in connector RJ45).
For the PROFIBUS version and CC-Link version: Insert plug-in connector D-Sub, 9-pin.
→ Apply supply voltage.
english
Type ME43
Troubleshooting
14 TROUBLESHOOTING
Problem
The NAMUR-LED goes out periodically.
No process values are transferred between Industrial
Ethernet and büS.
The process values cannot be allocated to the büS devices.
An incorrect value is transmitted or value is zero.
Replacement device fails to take over values from Micro
SD card from the defective device.
Replacement device fails to take over all values from
Micro SD card from the defective device.
Possible cause Procedure
The power supply collapses periodically – the device performs a reset each time.
The voltage drop in the connection cable is too great.
No cable connection.
Reading and writing of the values has not been allowed by the PLC in the control object of the device.
The process values have been configured incorrectly.
The process values have been allocated incorrectly.
The process values have not been configured.
The import of the configuration must be completed by restarting the device.
The process values have been allocated to different classes.
Use power supply with adequate power.
Increase cable cross-section.
Reduce cable length.
Check Ethernet and büS cable connection.
Allow reading and writing of the values in the control object of the device.
Check configuration of the process values.
Check allocation of the process values to the büS devices.
Check configuration of the process values.
Restart the device after configuration.
Observe input and output direction as allocation.
The process values have not been allocated or have been allocated to the wrong devices.
The device ID numbers of the replacement device and the defective device differ.
The Micro SD card is defective.
The device was unable to write any values on the Micro SD card.
The EDS device description between the replacement device and the defective device differs.
Check allocation to ensure that büS devices are working with process values of the same class.
Verify that direction of input and output is correct.
Check allocation of the process values.
Values can only be transmitted between devices having the same
Ident number.
Replace the Micro SD card (refer to
chapter “15 Accessories”) and try
again to transmit the parameters of the defective device to the Micro
SD card (see chapter “9.5 Importing and saving data using the Micro SD card”).
Only the existing values of the defective device can be transferred to the replacement device. New values of the replacement device must be parameterized using the “Bürkert
Communicator” software.
Table 17: Troubleshooting
59 english
Type ME43
Troubleshooting
60
14.1
Description of the error codes
18/16
18/17
18/18
18/19
18/20
18/21
32/1
32/130
33/1
33/2
33/3
33/4
33/5
33/6
33/7
33/8
33/9
33/11
33/12
18/9
18/10
18/11
18/12
18/13
18/14
18/15
2/4
2/5
2/6
3/1
3/2
3/3
3/4
18/4
18/7
18/8
Error code Description
1/3
2/1
Overload detected.
Overvoltage detected.
2/2
2/3
Undervoltage detected.
Voltage is above the warning limit.
Voltage is below the warning limit.
Battery voltage is below the warning limit.
Voltage drop detected.
Overtemperature detected.
Undertemperature detected.
Temperature is above the warning limit.
Temperature is below the warning limit.
SD card is defective.
Transferable memory is available.
Transferable memory is not accessible.
Configuration is successfully managed by another device.
Configuration isn´t successfully managed by another device.
Configuration of the device could not be loaded by the configuration provider.
At least 1 device is missing.
Bürkert Communicator is required.
Device replacement necessary.
Replacement can not be performed because there are too many options. Reduce suitable clients.
Problems during device replacement.
Problems during device replacement. At least 1 object could not be written.
Device replacement failed.
Device replacement successful.
Configuration provider is not active because no memory card is available.
More than 1 configuration provider is active! Switch off the other provider functions.
The capacity of the internal message memory has been exceeded.
Initialization of the device.
Switch to state „operation“.
Switch to state „diagnostics active“.
Switch to state „maintenance“.
Switch to state „out of specification“.
Switch to state „check function“.
Switch to state „error“.
Switch to AUTOMATIC operating state.
Switch to MANUAL operating state.
Switch to special mode: LED flashing.
Switch to state „off“.
Input value simulation for at least 1 value active.
english
Type ME43
Troubleshooting
45/1796
45/1797
45/1798
45/1799
45/2048
45/2049
45/2304
45/2560
45/2561
45/2562
45/2816
45/3072
45/3584
45/4096
45/4097
51/1
51/2
51/10
51/101
51/102
51/103
51/104
51/105
51/201
51/202
51/203
51/204
Error code Description
33/13 Output value simulation for at least one value active.
33/14 Demo mode activated.
33/32768 1 Status message is pending.
35/1
35/2
40/996
45/256
45/257
EERPROM error has been detected.
At least 1 persistent memory cannot be used.
Error on 1 or more partner device(s).
büS event: büS is NOT operational.
büS event: initialize communication.
45/512
45/768
45/1024
45/1792
45/1793
45/1794
45/1795 büS event: localization.
büS event: a device uses the same NodeID.
büS event: bus connection lost / not available.
büS event: partner allocation active.
büS event: producer(s) not found.
büS event: manual set device without NodeID. Search can take up to 1 minute.
büS event: allocation of producer failed.
büS event: deallocation of producer failed.
büS event: invalid mapping for CANopen device.
büS event: GCV value is mapped on both büS interfaces.
büS event: cyclic communication of producer not active.
büS event: save persistent büS data (don‘t turn off the device).
büS event: delete persistent büS data (don‘t turn off the device).
büS event: router for acyclic data active.
büS event: invalid serial number.
büS event: invalid receive value configuration (not enough filter).
büS event: invalid configuration of cyclic values.
büS event: manager active.
büS event: observed device failed.
Waiting for addressing.
Error during device parameter initialization.
Configured address already in use.
No proper connection to the process control system.
Cyclic data transfer has been slower than configured timeout.
Initialization of industrial communication.
Error while NetX configuration e.g. downloading firmware to NetX.
Industrial communication is powered Off.
No or incorrect mapping file available.
No protocol firmware available.
Please select a protocol and restart the device.
Protocol stack initialization error.
Protocol stack configuration error.
Error while sending MAC-address.
Error while register objects.
english
61
62
Type ME43
Troubleshooting
Error code Description
51/205 Error while config connections, more than 5 connections.
51/206
51/207
51/208
51/300
51/303
Wrong PROFIBUS address valid addresses are 1 - 126.
Wrong CC-Link address valid addresses are 1 - 64.
Wrong CC-Link baud rate.
Fieldbus master is running in stop mode.
Cyclic data exchange failed.
51/400
52/2
52/3
52/4
52/5
52/6
52/7
52/10
52/11
52/12
52/13
Master tried to plug wrong module or submodule.
EDS extension entries for the f(x) function, reconfiguration required.
Function‘s payload CRC error, reconfiguration required.
Functionality couldn‘t be created (unknown functionality?).
Functionality couldn‘t be initialized.
f(x) configuration faulty, reconfiguration required.
Function number invalid, reconfiguration required.
f(x)‘s payload cache is full, reduce the function count or the program size.
Function processing error.
User message.
52/15
52/16
52/17
52/18
52/19
52/20
52/21
52/22
52/23
52/24
52/25
52/26
Function hasn‘t finished processing within its cycle time and has been disabled! Increase the cycle time if possible.
The cycle times of the graphical program f(x) do not match the associated function cycle time, redownload the program to the device.
f(x) mapping is invalid (mapping table invalid), reconfiguration required.
f(x) function is waiting for producers (are all inputs linked?).
Graphical program editor: no program loaded, please download a program to the device.
Any f(x) function has an pending error! (Fix the other pending error).
The cycle time of an f(x) function is too long! The cycle time must be reduced to avoid irreparable damage to the device.
Graphical program editor: License not matching the program requirements! To unlock the full functionality please contact the Bürkert sales and distribution.
Graphical program editor: Invalid persistent data! Default values are used.
Graphical program editor: Program data and configuration does not match, reconfiguration required.
Graphical program editor: No License. The program will be deactivated after 1 hour.
Graphical program editor: No License. The program was deactivated! To unlock the full functionality please contact the Bürkert sales and distribution.
Initialize f(x)
Table 18: Description of the error codes english
Type ME43
Troubleshooting
14.2
Status indicators and action to be taken
Status LED indicators based on NAMUR NE 107
No color
Flashing rapidly
(applies to all colors)
Red
Description Procedure
No power is supplied to the device.
Connect device to power supply.
The device was selected using the
“Bürkert Communicator” software.
Device defective.
De-select the device using the
“Bürkert Communicator” software.
Device requires maintenance –
Contact the manufacturer.
Communication with other büS devices not possible.
Bus error (e. g. short circuit).
The device is not connected to the
PLC.
Integrate device into a network with other büS devices.
Check wiring.
Check wiring.
Device cannot find the allocated büS device.
Check device description for connecting the device to the PLC.
Check whether the büS device is allocated to the device.
Orange Search for büS devices active. Status is terminated after a few seconds.
If the device status persists for more than 4 minutes, perform a restart of the network.
Yellow
Blue
Table 19:
Device temperature out of specifi cation, destruction of the device is a possibility.
Operate the device inside the specification.
Internal device diagnostics point to problems in the device or the process properties.
Maintenance required
Take action based on logbook messages.
Service device.
Action to be taken based on device status indicators
LED status
Link LED (yellow)
Link/Act LED
(green)
Table 20:
Not active
Not active
Description and cause of error
No connection to the network established
No connection to the network available.
LEDs for network connection and action to be taken
Procedure
Check cables.
Check cables.
63 english
Type ME43
Accessories
15 ACCESSORIES
CAUTION!
Risk of injury and/or damage due to the use of incorrect parts!
Incorrect accessories and unsuitable spare parts may cause injuries and damage the device and its environment.
▶ Use original accessories and original spare parts from Bürkert only.
Accessories
USB-büS-Interface set 1 (including power supply unit) and “Bürkert Communicator” software
Micro SD card
Order number
00772426
774087
64 english
Type ME43
Disassembly
16 DISASSEMBLY
WARNING!
Risk of injury from improper disassembly.
▶ Disassembly may be carried out by authorized technicians only.
1. Switch off supply voltage
2. Remove 5-pin spring-type terminal.
Figure 34: Remove 5-pin spring-type terminal
3. Remove Ethernet cable from the X2 and X2 interfaces.
For the PROFIBUS version and CC-Link version: Remove plug-in connector D-Sub, 9-pin.
4. Remove the device from the standard rail
Figure 35: Remove the device from the standard rail
→ Push the device upwards and detach it from the upper guide of the standard rail english
65
66
Type ME43
Packaging, transport
17 PACKAGING, TRANSPORT
NOTE!
Damage in transit due to inadequately protected devices.
• Protect the device against moisture and dirt in shock-resistant packaging during transportation.
• Observe permitted storage temperature.
18 STORAGE
NOTE!
Incorrect storage may damage the device.
• Store the device in a dry and dust-free location.
• Storage temperature: -30 °C to +80 °C.
19 DISPOSAL
NOTE!
Damage to the environment caused by device components contaminated with media.
• Dispose of the device and packaging in an environmentally friendly manner.
• Observe applicable disposal and environmental regulations.
Observe national regulations on the disposal of waste.
english