VM1000 Series
VM1000 AC Drive
User Manual
资料代码:
‐ 0 ‐
Version Code :VM1000-E2016-04-1MB
VM1000 Series
Preface
Thank you for choosing SAJ VM1000 AC drive.
This user manual provides you with technical specification, installation instruction and detailed function parameters of VM 1000.Before installation, operation, maintenance or inspection, please read this manual carefully.
Special warning: Please be sure to read and understand the warnings and precautions in this manual before using VM 1000 and make sure the certificate of relative electrical engineers is line with the provisions of the labor supervision department, and the electrics and environment conditions is in conformity with the country’s standard.
Make sure the wiring is correct before it is power-on; before normally operating and using this product, make sure the motor rotation meets the requirements by debugging it.
When installing, using or maintaining the product, if it needs a consultation for product functions, performance, other technical issues as well as safety precautions, please contact our customer service center according to the hotline in the manual.
China service hotline: 400-159-0088
‐ 1 ‐
VM1000 Series
Content
Preface .............................................................................................. - 1
Precautions ...................................................................................... - 4
Signs, Abbreviation and Brandmark statement ........................... - 8
Chapter 1 Product Information ..................................................... - 9
1.1 Production Introduction ................................................................................. - 9 -
1.2 Technical Specification Table ...................................................................... - 10 -
1.3 Product nameplate........................................................................................ - 13 -
1.4 Model Description ....................................................................................... - 14 -
1.5 Dimension of AC Drive ............................................................................... - 14 -
1.6 Dimension of Keyboard ............................................................................... - 17 -
1.7 Specification of Selecting Products ............................................................. - 18 -
1.8 Maintenance ................................................................................................. - 19 -
Chapter 2 Installation ................................................................... - 22
2.1 Mechanical Installation ................................................................................ - 22 -
2.2 Electrical wiring ........................................................................................... - 28
2.3 Electro Magnetic Compatibility ................................................................... - 43
Chapter 3 Panel Display and Operation ................................... - 46
3.1 Introduction of Operation&Display Interface .............................................. - 46 -
3.2 Function Code Viewing, Modification Instruction ...................................... - 49 -
3.3 Viewing Methods of Status Parameters ....................................................... - 50 -
3.4 Password Setting ........................................................................................ - 50 -
Chapter 4 Quick Debugging Guide ............................................. - 51
4.1 Preparation and Examination Before Commissioning Operation ................ - 51 -
4.2 Panel Operation ............................................................................................ - 53 -
4.3 Start/Stop control of terminal forward rotation ........................................... - 56 -
4.4 Common Control Guideline ......................................................................... - 58 -
4.5 Auto-tuning of Motor Parameters ................................................................ - 62 -
4.6 Faults Query and Reset step ......................................................................... - 64 -
4.7 Parameters Restore as Factory Value ........................................................... - 65
‐ 2 ‐
VM1000 Series
Chapter 5 Function Code Datasheet ......................................... - 66
Chapter 6 VM1000 Communication Application ..................... - 112
6.1 The Content of Protocol ............................................................................. - 112 -
6.2 Application ................................................................................................. - 112 -
6.3 Bus Structure .............................................................................................. - 112 -
6.4 Protocol Instruction .................................................................................... - 113 -
6.5 Communication Frame Description ........................................................... - 113 -
6.6 Register Address ........................................................................................ - 118
Chapter 7 Faults and Solutions ............................................... - 126
7.1 Fault Code Table ........................................................................................ - 126 -
7.2 Troubleshooting and Solution .................................................................... - 138
Appendix A -Selection of External Electrical Components ..... - 140
A.1 VM1000 External Electrical Connection Diagram ................................... - 140 -
A.2 Selection Guide of Braking Components ................................................. - 143
A.3 Selection of Air Switch,Contactor or Cable .............................................. - 145
Appendix B-Manual Revision Record ....................................... - 146
‐ 3 ‐
VM1000 Series
Precautions
The Definition of Manual Warning Signs
In this manual, there are three kinds of warning signs that is respectively corresponding to three kinds of precautions; once violated, it will probably cause person injury to different degree.
DANGER: it indicates that it will probably cause death or severe physical injuries if violate the correct instruction.
WARNING: it indicates that it could cause personal moderate injuries, minor injuries or damage to the equipment if violates the correct instructions..
NOTE: it indicates that it would cause error or using equipment insecurely if violates the correct instruction.
The Definition of Product Warning Signs
The product warning signs are right under the case cover.
It indicates that there is high voltage in the product
+10 minutes time delay, which indicates that it needs to wait for capacitor discharging after power off
Before Installation
Before opening, please confirm that:(1) model and rated values on the nameplates is same as the goods you order; products, certification accessories, user manual and warranty card are complete and have not been damaged;(2) Whether the products are damaged or destroyed with water etc.; If there is damages,losses or other abnormal phenomenon,please contact our company or your suppliers to solve problems
‐ 4 ‐
VM1000 Series
Warning
◎ Do not install or operate the VFD if it is damaged or has missing parts. Otherwise it may result in equipment damage or physical injuries.
Installation
Warning
◎ Please hold the bottom of VFD when installing or moving it. In case that the VFD is broken or damaged; only holding the shell is not allowed.
◎ Keep the VFD away from heat, inflammable and explosive goods; Install VFD on the metal or other nonflammable objects.
◎ If the VFD is mounted in an electric cabinet or other enclosed objects, fans or other cooling device should be installed inside the cabinet; Setting ventilation opening to ensure ambient temperature is below 40 ℃ . Otherwise it may be damaged because of high temperature.
Danger
◎ Wiring must be completed by qualified electrical engineers. Otherwise it can cause an electrical shock or VFD damage.
◎ Before wiring, make sure the power supply is de-energized. Otherwise it will cause an electrical shock or a fire.
◎ Make sure the ground terminal is grounded safely and correctly. Otherwise there will be a risk of electrical shock on the shell of VFD.
◎ Do not touch the main circuit terminal, and the main circuit terminals of the VFD are not allowed to contact the shell. Otherwise it may cause an electrical shock.
◎ Braking resistor of the connection terminal is ( + ) and PB. Do not connect the other terminals;
Otherwise it may cause a fire.
‐ 5 ‐
VM1000 Series
Wiring
Warning
◎ Before connecting, make sure the voltage rating and phase number of VFD is conformed to the input power voltage, phase number; Otherwise it may cause a fire or physical injuries.
◎ Never connect the AC input power supply to the output terminals V, U, W of VFD;
Otherwise it will cause damage to the VFD and you are not guaranteed to enjoy the warranty services.
◎ Never conduct a pressure test on VFD ; Otherwise it will cause damage to the VFD.
◎ The main circuit wiring of the VFD and the control loop wiring should be separated or vertical crossed, otherwise the control signal will be interfered.
◎ The cable connected to the main circuit terminals should be use lugs with isolated casing.
◎ If the length of cable between the VFD and the motor is over 50 meters, an output reactor is recommended so as to protect the VFD and motor.
Operation
Danger
◎ Turn on the input AC power after the wiring of VFD is completed and the front cover is installed. Do not dismantle the front cover when operating; otherwise it will lead to an electric shock.
◎ When VFD is set with the function of fault automatic reset or auto-restart after power failure, protection measures for equipment system should be taken in advance. Otherwise it will cause physical injuries.
◎ The key “RUN/STOP” may be lose efficacy because some function had been set, a separate emergency power switch can be installed in the VFD control system; Otherwise it may cause damage or physical injuries.
◎ Though the VFD terminal is in stop state, the terminal is electrified after power on. Do not touch; otherwise there will be a risk of electric shock.
Warning
◎ Do not use the breaker to control the stop/start of AC drive, or it may damage to the AC drive.
◎ Because the acceleration time is short when AC drive makes motor operates from low to high speed, make sure the motor and mechanical equipment is within the permitted range
‐ 6 ‐
VM1000 Series before operation,or it will damage the equipment.
◎ The temperature of heat sink and braking resistor is high. Please do not touch. Otherwise, it may cause burns.
◎ When leaving factory, the preset parameters of AC drive have met most of the operational requirements of equipment. If not necessary, do not arbitrarily change the parameters. Even some devices have some special requirements; you can only modify the necessary parameters. Otherwise, arbitrary modification may damage the equipment.
Maintenance and Inspection
Danger
◎ When power on, do not touch the connection terminals. Otherwise it may cause an electrical shock.
◎ Only qualified electrical engineering personnel can maintain, replace and inspect the SPD.
◎ Wait at least 10 minutes after the power failure, or make sure that is no residual voltage before carry out maintenance and inspection, otherwise it may cause damage.
Note
◎ PCB board has CMOS integrated circuit, do not touch, otherwise the static electricity may damage PCB board.
Others
Danger
◎ It is strictly forbidden to transform the VFD, otherwise it may cause casualties. After arbitrarily changing VFD, will no longer enjoy the warranty service.
‐ 7 ‐
VM1000 Series
Signs, Abbreviation and Brandmark statement
■ Signs
Protective Earthing: PE
Signal Ground: GND
Shield: SHIELD
■ Name Abbreviation
1. In this user manual, VM1000 AC drive has another name or abbreviation :
Variable frequency drive, VM1000, inverter, speed controller, VFD product and product.
2. VFD parameter is as follows : function parameters, function code, parameters code
3. SAJ, Sanjing Electric 、 SAJ Electric are all the standard abbreviation of
Guangzhou Sanjing Electric Co. Ltd
4. Common Technical Terms,Similar or Equal Name:
Voltage frequency ratio control mode: VF control
Open-loop vector control mode: SVC control
Three-phase induction motor: asynchronous motor, squirrel-cage asynchronous motor
■ Trademark
1. Modbus ○
2. SAJ ○
3. Other trademark that may occur or product names belong to respective owners
‐ 8 ‐
VM1000 Series
Chapter 1 Product Information
1.1 Production Introduction
The Usage of VM1000 AC drive
VM1000 AC drive is the new generation product with high performance and multi usages, which usually apply in the regular three-phase induction motor for speed control. Power range is
11 ~
110kW;It can select V/F control mode or SVC control mode.
Key Design Points
Design Points Instruction
Control performance and function
1.Product adopts: large capacity power module,high accuracy detection hardware and brandnew control platform
2.Function upgrade: mainly includes torque control,S curve,given frequency,vector control, V/F separation, Two groups of PID parameters , input 、 output and auxiliary function , faults protection and user-defined protection action
3. Meanwhile,it maintain the compatibility for previous products
Input/Output and communication interface
Support 5 common inputs, 1 high-speed pulse input, 1 high-speed pulse output( also work as open collector output DO), 2 relay output, 2 analogue output, 2 analogue input, 1 RS485 communication interface
G/P load types
Whole series support heavy load(G) and normal load(P) rating characteristics.
G load type: typical constant torque load, such as conveyor, lift, crane, etc.
P load type: typical variable torque load, such as pump and fan.
Structure design
Structure optimization, dimension decrease, good heat dissipation, industrial protection, simple case
‐ 9 ‐
VM1000 Series
Wiring installation
1. Main circuit adopt increased superior terminal array , large power type and independent terminal,and equipped with dual GND ports.
2. Control terminal is vertical arranged on the left of the control board and print with PCB logo.
New keyboard design
1. Adopt potentionmeter of electrical impulse,standard keyboard adopts 5 bits digital tube to display and match LED lights;
2. Common keyboard supports short distance installation externally, and adopts LCD keyboard to realize long-distance external leading by cables
Faults detection
Faults type and strategy are more refined, user can define faults protection action
EMC Level standard product satisfy IEC61800-3 C3 requirements external filter satisfy IEC61800-3 C2 requirements
Table 1-1 Product Key Design
1.2 Technical Specification Table
Item
High frequency
Carrier frequency
Control mode
Starting torque
Specification
V/F control : ~ 1000Hz ; : ~ 400Hz
0.5kHz ~ 16kHz ; it can adjust load frequency automatically according to the load character
V/F control ; SVC control ; Torque control
G load type : 0.5Hz/150% ( SVC ) P load type :
0.5Hz/100%
Personalized
Function
1 : 100 ( SVC )
Speed adjustable range
Speed-holding precision
Torque control
Accuracy
±0.5% ( SVC )
±5% ( SVC )
Overload capacity
G load type : 60s for150% rated current ; 1s for180% rated current
‐ 10 ‐
VM1000 Series
Torque boost
V/F curve
V/F separation
Acceleration and deceleration Time
DC braking
JOG control
P load type : 60s for120% rated current;1s for 180% rated current
0.0% auto torque boost ; customized torque boost
0.1% ~ 30.0%
Three types: Linear, multipoint square V/F curve
Whole separation,semi separation
Linear mode and S curve acceleration and deceleration time ; Four kinds of acceleration and deceleration time; the range of acceleration and deceleration time is
0.0 ~ 6500.0s
Braking time: 0.0s ~ 100.0s;Braking action current value: 0.0% ~ 100.0%
JOG frequency range : 0.00Hz ~ max frequency ; JOG acceleration and deceleration time 0.0s ~ 6500.0s
Simple
PLC,multi-speed control
Integrated PID
16 section speed(at most) can be realized by integrated
PID and control terminals
AVR
It is convenient to realize closed-loop control system
When grid voltage changes , it keeps output voltage constant automatically.
Control of overvoltage, overcurrent, speed stall
The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage/overcurrent.
Rapid current limit
Torque limit and control
Power peripheral and safety self-checking
MF.K Key
Decrease overcurrent at max, protect VFD to operate regularly
It can limit the torque automatically and prevent frequent over current tripping during the running process.
To realize self checking of peripheral equipment at power on, such as grounding fault, short circuit fault, etc.
Programmable:command channel switch,forward rotation and reverse rotation/JOG function selection
‐ 11 ‐
VM1000 Series
Running frequency control
Timing control Timing control: setting time range: 0h ~ 65535h
Operation command channel
Three channels: operation panel given, control terminal given, and communication given. It can be switched by various methods.
Frequency source
There are 10 frequency sources in total: digital setting, analog voltage setting, analog current setting, pulse setting and serial communication port setting etc. It can be switched by these frequency sources in various methods.
Auxiliary frequency source
There are ten auxiliary frequency sources. It can implement fine tuning of auxiliary frequency and frequency synthesis.
Input terminal
There are 6 digital input terminals. One of them can be used as high speed pulse input, which can reach 100KHz at max. All of them support supports active PNP and NPN input.
2 analog input (AI) terminals, one of which only supports voltage input and the other supports voltage input or current input
Display and keyboard operation
Output terminal
LED display
LCD display
Parameters copy
Key locking and function selection
1.High-speed pulse output terminal (open-collector) that supports 0–100 kHz square wave signal output, which can realize the output of setting frequency and output frequency 2 relay output terminal
2 analog output (AO) terminal that supports 0/4mA–20 mA current output or 0/2V–10 V voltage output, which can realize the output of setting frequency and frequency etc.
Displayed parameters
Optional; operation content indicated.
Iit can be achieved parameters’ fast copy via LCD keypad option
It can lock the keys partially or completely and define the function range of some keys so as to prevent mis-operation.
Protection function
Motor short-circuit detection at power-on, input/output phase loss protection, overcurrent protection, overvoltage protection, undervoltage protection, overheat protection and overload
‐ 12 ‐
VM1000 Series
Environment protection etc.
Accessories selection
LCD operation panel, braking unit etc.
Installation location
Altitude
Indoor, free from direct sunlight, dust, corrosive gas, combustible gas, oil smoke, vapour, drip or salt.
Lower than 1000m,higher than 1000m ,it is used at derating
-10°C to +40°C (de-rated if the ambient temperature is between 40°C and 50°C)
Ambient temperature
Humidity
Vibration
Less than 95%RH, without condensing
Less than 5.9m/s2(0.6g)
Storage temperature - 40 ℃~+ 70 ℃
Table 1-2 Technical Specification
1.3 Product nameplate
Figure 1-1 Product nameplate
‐ 13 ‐
VM1000 Series
1.4 Model Description
VM1000 – 4 T 18R5G/022P
① ② ③ ④ ⑤
Field Sign Sign Instruction
Specification
Product abbreviation
① Product abbreviation
VM1000 : General vector control variable frequency drive, “Vector
Master” series
2 : 220VAC ; 4 : 380VAC Voltage class ② Voltage class input power phase
③ Sign of power phase S : single-phase ; T : three-phase
Rated power 1 ④ Power of G load type
Rated power 2 ⑤ Power of P load type
18R5-18.5kW
, R represents decimal point
G—constant torque load
B—built-in braking unit
022-22kW
P—variable torque load
B—built-in braking unit
Table 1-3 VM1000 Field Annotation
1.5 Dimension of AC Drive
Table 1-2 11kW-15kW Installation Dimension
‐ 14 ‐
VM1000 Series
Table 1-3 18.5kW-22kW Installation Dimension
Table 1-4 30kW-37kW Installation Dimension
‐ 15 ‐
VM1000 Series
Table 1-5 45kW-55kW Installation Dimension
Table 1-6 75kW-110kW Installation Dimension
‐ 16 ‐
VM1000 Series
1.6 Dimension of Keyboard
VM1000 operation keyboard is directly plug in the control board socket and is buttoned on the keyboard tray.There is a keyboard frame for the the front cover.
After installation, the frame is fixed around operation keyboard. Please refer to 2-1.
If keyboard needs to be extended externally, please cut a rectangle hole on the control panel or the door carbinet for the keyboard installation according to the following dimension.
RESET
■ Dimension Instruction
Table 1-7 Keyboard Dimension
(1) There are four keyboard buckles; the distance between bottom and keyboard surface is 7.6mm
(2)When cutting a rectangle hole for keyboard, it suggests adding 1mm more for the length and width based on the dimension in this picture. Namely is Length 101.1mm is increased to 102.1mm, and width 72.1mm is increased to 73.1mm.
■ Cover of Keyboard Window
It can select one window panel for installing keyboard externally in order to cover the AC drive keyboard window.
‐ 17 ‐
VM1000 Series
1.7 Specification of Selecting Products
VFD Module (G/P load type)
Rated
Power
( kW ) power capacity kVA input current
A
Output current
A
Fitted Motor G/P kW HP
VM1000-4T011GB/015PB 11/15 17/21 26/35 25/32 11/15 15/20
VM1000-4T015GB/18R5PB 15/18.5 21/24 35/38.5 32/37 15/18.5 20/25
VM1000-4T022GB/030PB 22/30 30/40 46.5/62 45/60 22/30 30/40
Table 1-4 Specification of Selecting Products
‐ 18 ‐
VM1000 Series
1.8 Maintenance
1.8.1 Routine Maintenance
The influence of the ambient temperature, humidity, dust and vibration will cause the aging of the devices in the AC drive, which may cause potential faults or reduce the service life of the AC drive. Therefore, it is necessary to carry out routine and periodic maintenance.
(1) Routine maintenance involves checking:
• Whether the motor sounds abnormally during running
• Whether the motor vibrates excessively during running
• Whether the installation environment of the AC drive changes.
• Whether the AC drive's cooling fan works normally
• Whether the AC drive overheats
(2) Routine cleaning involves:
• Keep the AC drive clean all the time.
• Remove the dust, especially metal powder on the surface of the AC drive, to prevent the dust from entering the AC drive.
• Clear the oil stain on the cooling fan of the AC drive.
1.8.2 Periodic Inspection
Perform periodic inspection in places where inspection is difficult.
Periodic inspection involves:
• Check and clean the air duct periodically.
‐ 19 ‐
VM1000 Series
• Check whether the screws become loose.
• Check whether the AC drive is corroded.
• Check whether the wiring terminals show signs of arcing;
1.8.3 The Replacement of Vulnerable Components
The vulnerable components of the AC drive are cooling fan and filter electrolytic capacitor. Their service life is related to the operating environment and maintenance status. Generally, the service life is shown as follows:
Components name Lifetime
Electrolytic capacitor 4 ~ 5 Year
Table 1-5 Lifetime of Wearing Parts
User can decide the replacing time according to its operation
(1) Cooling Fan
Damage causes: bearing wear, leaf aging
Judge standard: whether there is crack on the fan blase; whether there is abnormal vibrating when turn on
(2) Filter Electrolytic Capacitor
Damage causes: the quality of input power is bad; the ambient temperature is relatively high; frequent load jump, electrolyte aging
Judge standard: Whether there is liquid leakage or protrusion of safety valve or not, electrostatic capacitance and insulation resistance measurement.
‐ 20 ‐
VM1000 Series
1.8.4 Storage of the AC Drive
For storage of the AC drive, pay attention to the following two aspects:
(1) Pack the AC drive with the original packing box provided by SAJ
(2) Long-term storage degrades the electrolytic capacitor. Thus, the AC drive must be energized once every 2 years, each time lasting at least 5 hours. The input voltage must be increased slowly to the rated value with the regulator.
‐ 21 ‐
VM1000 Series
Chapter 2 Installation
2.1 Mechanical Installation
2.1.1VM1000 Structure
B: Fan
C: Front cover
E: Keyboard Tray
D: Operation Keyboard
A: VM1000 housing
E: Keyboard frame
G: Cable Inlet
Figure 2-1 VM1000 Structure
‐ 22 ‐
VM1000 Series
2.1.2 Removal Steps
( 1 ) Example of Cover Removal and Installation
Figure2-2 Cover Removal
( 2 ) Keyboard Removal Example
Figure2-3 Keyboard Removal
‐ 23 ‐
VM1000 Series
( 3 ) Fan Removal Example
11-55kW
Figure 2-4 Fan Removal
75-110kW
2.1.3 Environment Requirements
VFD is power electrical equipment. In order to use regularly, make sure the operation and storage environment meets the requirements. The following is the detailed index sheet. If there are other items that involves with electric installation, please refer to relative national or regional standards.
Item Index Instruction
Installation places and
Precaution
Installation place: VM1000’s ingress protection is IP20. With power input and high voltage output, it needs to be installed in indoors or equivalent places. In order to keep away from accidental contact, invasion and prevent rats and insects, it is suggested to install in the distribution box that has sufficient protection effect or control box.
AC drive need to be installed on the surface of incombustible object such as support, panel and solid architectural facade, and fix the AC drive with screws and bolts.
Since a great amount of heat will be generated when VFD is running there needs to have sufficient space around for heat dissipation. If necessary, it also needs to equip with mandatory ventilation and heat dissipation devices.
Because the channel for ventilation and heat dissipation is designed vertically, the VFD needs to be installed horizontally other than horizontally or transversely.
‐ 24 ‐
VM1000 Series
Free from direct sunlight, high humidity and condensation
Free from corrosive, explosive and flammable gas
Free from oil dirt, dust and metal powder
Environmental temperature
When VFD is with normal rated load, the permitted environmental temperature is -10 ℃ +~40 ℃ , service in derated capacity for 40 ℃ ~50 ℃ .
Notes: 1) Derate 4% capacity for every 1 ℃ increased. 2) If the ambient temperature is too low, it needs to take measures to increase the temperature.
Humidity
≤ 95%RH, no water condensation
Notes: If there is condensation may occur due to environmental factors, install electrical heating device in the control cabinet.
Storage temperature
-40 ℃~ 70 ℃。
Altitude
Vibration
Lower than 1000m, use according to the normal load standard
Higher than 1000m, it needs derating. Derate 1% capacity every 100m.
Please install in the place that is not easy to generate vibration. Vibration should not exceed 0.6G. Special Notes: 1. Do not be installed on the punching machine etc; 2. Do not use as VOBC (Vehicle on Board Controller); 3. When it is applied to moving equipment like cranes etc., ensure VFD is installed according to the stability of equipment and make sure VFD won’t occur uncontrollable shaking or other abnormal condition.
Table 2-1 Index List for Environmental Requirements
‐ 25 ‐
VM1000 Series
2.1.4 Installation Guide
(1) Single-drive Installation
It needs to keep space around the VFD in order to have abundant airflow.
Requirements of recommended spatial distance are shown as table 2-2
Figure 2-5 Spatial Distances
Dimension
Power Level
11kW-15kW
18.5kW-37kW
45kW-110kW
B
≥ 100mm
≥ 200mm
≥ 300mm
Table 2-2 Recommended Spatial Distance
A no requirements
≥ 50mm
≥ 50mm
‐ 26 ‐
VM1000 Series
(2) Top/Bottom Installation
Insulation guide plate needs to be installed between two VFDs so as to separate airflow. Refer to the requirements of recommended spatial distance.The picture below is the example of
Insulation guide plate.
Insulation guide plate
Figure 2-6 Diagram of Insulation Guide Plate
When two VFDs or more are installed side by side, increase 50mm at least for every two; increase 100mm at least for the left and right, top and bottom
(3) Installation Method
Wall-mounting ( 11 ~ 110kW )
(4) Protection requirements
① Complete water-proof measures
② Preventing insects invasion,including adopt anti-rats and anti-pests measures
‐ 27 ‐
VM1000 Series
2.2 Electrical wiring
2.2.1 Electrical Operation Condition
VM1000 AC drive is applicable to the low-voltage power electrical system. Make sure that the following conditions meet the requirements when conducting wiring. If necessary, please refer to relative national or regional standards.
Item Instruction
Power distribution system
GND requirements
Three-phase four-wire system, three-phase five-wire system
Voltage and frequency range
380VAC , 50/60Hz
Power range
Voltage : Three phase 380VAC, permitted fluctuation range ±15% ,
Frequency : 50/60Hz, permitted fluctuation range ±5%
The protective earthing,signal ground should be separately wired
Leakage protection
With the VFD installed, power distribution line, it can not use circuit breaker with leakage protection etc.As for the VFD application, please complete equipment grounding measures to ensure the security.
Short-circuit protection
Start/stop control
VFD power supply need to connect with the circuit breaker with short circuit protection or rapid fuse protector
Under normal situation, VFD conduct start /stop control by its panel, control terminals and other methods.
Usually, it is not suggested to adopt contactor as the switch device at VFD power-supply side, nor use it as motor’s start/stop control device at VFD output side. If it is done and contactor is disconnected when operating, it will easily damage VFD.
Notes: Some industries or equipment (such as elevator) is required to use contactor as security isolation device at VFD power-supply side and output side, which is in conformity with the above requirements.
Table 2-3 Electrical Running Condition
‐ 28 ‐
VM1000 Series
2.2.2 Electrical Safety Precautions
When installing, operating or maintaining VFD and other relative equipment, it needs to take measures to prevent static electricity and electricity shock .Please refer to precautions in this manual.
2.2.3 Product Electrical Components
The electrical components are as shown on the picture below
Control terminals
Signal ground
Cable inlet
Operation keyboard
Control board
External keypad socket
Main circuit terminals
& Ground terminals
Figure 2-7 Electrical Components
‐ 29 ‐
VM1000 Series
2.2.4 Main Circuit Wiring
MCCB MC
Figure 2-8 11 ~ 22kW Main Circuit Wiring
The external components
AC reactor Brake unit
P
Earth ground
Figure 2-9 30 ~ 110kW Main Circuit Wiring
Earth ground
GND
Output terminal at variable frequency
‐ 30 ‐
VM1000 Series
( 1 ) 11 ~ 15kW Main Circuit Terminals
Figure 2-10 11 ~ 15kW Main Circuit Terminals
( 2 ) 18.5
~ 22kW Main Circuit Terminals
Figure 2-11 18.5
~ 22kW Main Circuit Terminals
( 3 ) 30 ~ 37kW Main Circuit Terminals
Figure 2-12 30 ~ 37kW Main Circuit Terminals
‐ 31 ‐
VM1000 Series
( 4 ) 45 ~ 55kW Main Circuit Terminals
Figure 2-13 45 ~ 55kW Main Circuit Terminals
( 5 ) 75 ~ 110kW Main Circuit Terminals
Figure 2-14 75 ~ 110kW Main Circuit Terminals
‐ 32 ‐
VM1000 Series
( 6 ) Main circuit terminal and function are as shown on the table below
Terminal sign
Name Instruction
R 、 S 、 T
Three phase power supply input terminals
Connect to three phase AC power supply
(+)
(+)
、
、
(-)
PB
Positive and negative AC bus terminals
Common DC bus input point(connect the external braking unit to AC drive of 30kw or above)
Connecting terminals of brake resistor
Connect to braking resistor for AC drive of 22kw and below
P 、 (+)
Connecting terminals of external reactor
Connect to an external reactor
U 、 V 、 W VFD output terminals Connect to a three-phase motor
Grounding terminal
Ground Terminals
Table 2-4 Main Circuit Terminals and Function
( 7 ) Wiring Precautions
A: Input Power R 、 S 、 T
The cable connection on the input side of the AC drive has no phase sequence requirement.
B: DC bus terminals (+), (-)
Terminals (+) and (-) of DC bus have residual voltage after the AC drive is switched off. Before touching the equipment, wait until power indicator goes off and make sure it is lower than 36V. Otherwise, you may get electric shock.
–– connecting external braking components for the AC drive of 30 kW or above.
‐ 33 ‐
VM1000 Series
Do not reverse poles (+) and (-). Otherwise, it may damage the AC drive and even cause a fire.
–– The cable length of the braking unit shall be no longer than 10 m. Use twisted pair wire or pair wires for parallel connection.
–– Do not connect the braking resistor directly to the DC bus. Otherwise, it may damage the AC drive and even cause fire.
C: Braking resistor connecting terminals (+) 、 PB
The connecting terminals of the braking resistor are effective only for the AC drive of 22kw and configured with the built-in braking unit.
The cable length of the braking resistor shall be less than 5 m. Otherwise, it may damage the AC drive.
D: External reactor connecting terminals P 、( + )
For the AC drive of 33 kW and above, it support external DC reactor. Remove the jumper bar across terminals P and (+) and install the reactor between the two terminals.
E: AC drive output terminals U, V, W
The capacitor or surge absorber cannot be connected to the output side of the AC drive. Otherwise, it may cause frequent AC drive fault or even damage the AC drive.
If the motor cable is too long, electrical resonance will occur due to the existance of distributed capacitance. This will damage the motor insulation or generate higher leakage current, causing the AC drive to trip in overcurrent protection. If the motor cable is greater than 50m, an AC output reactor should be installed close to the AC drive.
‐ 34 ‐
VM1000 Series
F: PE Terminal
This terminal must be reliably connected to the main earthing conductor and resistance range must less than 0.1
Ω . Otherwise, it may cause mal-function or even damage to the AC drive.
Do not connect the earthing terminal to the neutral conductor of the power supply.
Notes: The peripheral circuit includes breakers, braking resistor, braking unit and wiring specification guide such as optional guidance, please see Appendix A.
‐ 35 ‐
VM1000 Series
2.2.5 Control circuit wiring
Figure 2-15 Control Circuit Wiring
‐ 36 ‐
VM1000 Series
( 1 ) Control Terminals Diagram
Figure2-16 Control Terminals
‐ 37 ‐
VM1000 Series
( 2 ) Control terminals and functions
Type Terminal Name Function description
+10 V
+10V-GND power supply for external connection.
Provide +10 V power supply to external unit. Maximum output current: 10 mA.
Generally, it provides power supply to external, potentiometer with resistance range of 1–5 k Ω .
Power supply
+24 V
+24V-COM power supply for external connection
Provide +24 V power supply to external unit. Generally, it is used as power supply for digital input, output terminals and external sensor. The max output current: 200mA
OP
Input terminal of external power supply
Connect with +24 V power supply or COM by choosing lug plate on the control board.
Factory default is connecting to +24 V.
When using external signal to drive DI1 ~
DI6, OP needs to be connected with external power supply after removing the default lug plate among terminals OP-24V.
Analog input
Digital input
AI1-GND analog input 1
1.input voltage range:DC 0V ~ 10V
2.input impedance 22k Ω
AI2-GND analog input 2
1.Input range:DC 0V ~ 10V/4mA ~
20mA,decided by J8 jumper on control board.
2. input impedance 22k Ω ,current input
500 Ω
DI1 Digital input 1
DI2 Digital input 2
DI3 Digital
1.Optical coupling isolation, 2.compatible with dual polarity input
Impedance: 2.4 k Ω
DI4 Digital
‐ 38 ‐
VM1000 Series
DI6
High-speed pulse input
Except for DI1~DI5, it can also work as
High-speed pulse input
Max input frequency : 100kHz analog output
AO1-GND analog output 1 A01 is decided by J5 jumper on the control board, A02 is voltage input
AO2-GND analog output 2 output voltage : 0V ~ 10V output current : 0mA ~ 20mA
Digital output FM-CME
Optical coupling isolation, dual polarity open collector output
Output voltage range: 0–24 V
Digital output 1/
High-speed pulse output
Output current range: 0–50 mA
Note that CME and COM are internally insulated, but they are shorted by jumper externally. In this case DO1 is driven by +24
V by default. If you want to drive DO1 by external power supply, remove the jumper.
Relay output
T1/A-T1/B
Normally closed terminal
T1/A-T1/C
T2/A-T2/B
Normally open terminal
Contact driving capacity :
AC250V , 3A , COS
ø
=0.4
。
DC 30V , 1A
Normally open terminal
Communicati on terminal and socket
RS+
RS-
RJ45 socket
RS485 differential signal+
RS485 differential signal-
External LCD keyboard interface
Table 2-5 Control Terminal and Function
‐ 39 ‐
VM1000 Series
( 3 ) Wiring Standard of Control Terminal
According to the input signal and internal design of terminals, there are A, B, C three conditions as following.
A : Analog input terminal
Weak analog voltage signals are easy to suffer external interference, and therefore the shielded cable must be used and the cable length should be less than 20 m, as shown in following picture 2-17 .
In applications where the analog signal suffers severe interference, install filter capacitor or ferrite magnetic core at the analog signal source,as shown in following picture 2-18.
+10V
AI1
GND
PE
Figure 2-17 Analog input terminals
Figure 2-18 Analog input terminals handling
‐ 40 ‐
VM1000 Series
B : Digital Input Terminal
Generally, select shielded cable no longer than 20 m. When active driving is adopted, necessary filtering measures shall be taken to prevent the interference to the power supply. It is recommended to use mechanical contact input for control.
SINK Wiring
Figure 2-19 SINK Wiring
Sink wiring is the most commonly used wiring mode. To apply external power supply, remove jumpers between +24 V and OP and connect the positive pole of external power supply to OP and negative pole to COM.
‐ 41 ‐
VM1000 Series
Figure 2-20 Source Wiring
To source wiring, OP must be changed to connect to COM(for example by lug plate), and connect +24v to public terminal of external controller.If using external power, it also needs to connect the negative pole of external power to OP.
C : Digital Output Terminal
When the digital output terminal needs to drive the relay, an absorption diode shall be installed between two sides of the relay coil. Otherwise, it may cause damage to the 24 VDC power supply.
Do not reverse the polarity of the absorption diode during installation, as shown in
Figure2-21. Otherwise, the 24 VDC power supply will be damaged immediately once there is digital output.
‐ 42 ‐
VM1000 Series
Figure 2-21 Wiring of Digital Output Terminal
2.3 Electro Magnetic Compatibility
2.3.1 Eletromagnetic Interference and Installation Precautions
The electromagnetic interference includes two situations: one is electromagnetic noise from the surroundings having interference on VFD; the other interference is the interference to other equipment generating by VFD .
Precautions :
(1)VFD and other electrical product should be well grounded.
(2)Try not to install the power input and output cables of the AC drive and weak-current signal cables (such as control cable) in parallel. Install vertically if it has conditions.
(3) It is recommended to use shield cable in the VFD output power or and the shielding should be grounded completely.For the extension cable of interfered equipment, it is suggested to use twisted shield cable and shielding should be well grounded.
(4) If motor cable is longer than 50m, it requires to install output filter and reactor.
‐ 43 ‐
VM1000 Series
2.3.2 Solutions of Interfering VFD by Electromagnetic Equipment
Generally, the reason that VFD has an influence on electromagnetic is there are a large number of relays, contactors, or electromagnetic brakes around VFD.When VFD is interfered and malfunction, the following methods are recommended:
① Install a surge suppressor for the part that generates interference
② Install a filter at VFD intput side, refer to 2.3.5 for more details
③ Use shield cables in VFD control signal line and detection cable, shielding should be well grounded.
2.3.3 Solutions of interfering peripheral equipments by VFD
Noise in this part is classified into two kinds : One is VFD radiated interference ; The other one is VFD conducted interference. Both kinds of interference generate eletro magnetic and electrostatic induction around the equipment, which result in equipment malfunction. Refer to the following solutions according to various interference situations
(1)Generally the signal of meter, receiver and sensor etc for measuring is relatively weak . If they are closed to VFD or in the same cabinet, it will cause interference and malfunction to them easily.It is suggested to adopt the following solutions:Try to keep away from the interference source;Do not arrange signal cable and power cable in parallel,especially, do not tie together.Signal cable and power cable should use shield cable and ground well;Install ferrite ring on VFD output side(suppressing frequency range from 30 ~ 1000MHz), and coil 2 ~ 3 turns. For bad conditions, it can install an EMC output filter as option.
(2) When the equipment and VFD use same power, it will cause conducted interference. If the solutions above can not eliminate interference, it needs to install EMC filter between VFD and power (For model selection, refer to 2.3.5)
(3) Peripheral equipment ground independently, which can eliminate interference that caused by leakage current of VFD ground cable when it is in common -ground.
‐ 44 ‐
VM1000 Series
2.3.4 Leakage Current and Handling
There are two forms of leakage current while using VFD: one is earth leakage current,the other is leakage current between cable and cable.
(1) Factors that influenced earth leakage current and solutions
There exists distributed capacitance between wire and earth.The bigger the distributed capacitance, the larger the leakage current.It can decrease the carrier frequency in order to decrease leakage current. However, to decrease carrier frequency will increase motor noise.
Please note that the installation of the reactor is also an effective way to solve the leakage current.
Leakage current increases with the loop current. When motor power is high, the corresponding leakage current is high.
(2) The factors that caused leakage current between cable and cable and solutions
There exists distributed capacitance in VFD output circuits. It is likely to cause resonance and bring about leakage current if the current in the circuits contains higher harmonics. If thermal relay is put into use at this time, it will cause malfunction.
Solutions: decrease carrier frequency or install output reactor. When using VFD, it is suggested to use its electronic overload protection, and do not install a thermal relay before the motor.
Precautions of installing EMC input filter at power input side
① Notes : Strictly comply with the ratings when using the EMC filter. The EMC filter is category I electric apparatus, and therefore, the metal housing ground of the filter should be in good contact with the metal ground of the installation cabinet on a large area, and requires good conductive continuity. Otherwise, it will result in electric shock or poor EMC effect.
② As result of EMC test , it founds that the ground of the EMC filter and the PE conductor of the AC drive must be tied to the same common ground. Otherwise, the EMC effect will be affected seriously.
③ The EMC filter should be installed as closely as possible to the power input side of the AC drive.
‐ 45 ‐
VM1000 Series
Chapter 3 Panel Display and Operation
3.1 Introduction of Operation&Display Interface
You can modify the parameters, monitor the working status and start or stop the VFD by operating the operation panel. Its shape and functions are as shown in the following figure.
Figure 3-1 Operation Panel
‐ 46 ‐
VM1000 Series
( 1 ) Indicator Instruction
RUN: ON indicates that the AC drive is in the running state, and OFF indicates that the AC drive is in the stop state.
LOCAL/REMOT: Keyboard operation, terminal operation and remote operation
(communication control) indicators. OFF indicates keyboard operation control; ON indicates terminal operation control, FLICKER indicates remote operation control
FWD/REV : ON indicates reverse rotation, and OFF indicates forward rotation.
TUNE/TC : blinking, it indicates the fault state.
( 2 ) Unit Indicators
Hz: unit of frequency
A: unit of current
V: unit of voltage
RPM ( Hz+A ) : unit of rotational speed
% ( A+V ) : Percentage
( 3 ) Digital Display
The 5-digit LED display is able to display the set frequency, output frequency, monitoring data and alarm codes.
( 4 ) Pulse Electronic Knob
VDF panel has a pulse electronic knob. It can be used as frequency reference. When using this configuration of the drive knob as frequency source, turning it clockwise is the increased setting and counterclockwise is reduced setting. There are icons on the panel to present you operation direction.
‐ 47 ‐
VM1000 Series
( 5 ) Keys and Functions of Operation Panel
Key Name Function
PRG Programming
ENT
》
RUN
Confirm
Increment
Decrement
Shift
RUN
Enter the sub-menu display level by level; confirm the parameter setting.
Increase data or function code.
Decrease data or function code.
Select the displayed parameters in cyclic turn when in the stop or running state, and select the digit to be modified when modifying parameters.
Start the AC drive in the operation panel control mode.
STOP/ RESET
MF.K
Stop/Reset
Stop the AC drive when it is in the running state and perform the reset operation when it is in the fault state. The functions of this key are restricted in F7-02.
Multi-function key
Select function switchover according to the setting of F7.01.
Table 3-1 Keypad Instruction
‐ 48 ‐
VM1000 Series
3.2 Function Code Viewing, Modification Instruction
The operation panel of VM1000 adopts three level menus to conduct parameter setting.
The three-level menu is : function code group (Level I) → function code (Level II)
→ function code setting value (level III), as shown figure 3-2.
Table 3-2 Operation Flowchart of Three-level Menu
Instruction: In Level III, you can return to Level II by pressing PRG or ENTER.
The difference between them is: it will save the parameter setting, return to Level
Two, and then shift to the next function code by pressing ENT. While you press
PRG, the system will directly return to Level Two without saving the parameter setting.
For example: Modify F4.02 from 10.00Hz to 15.00Hz
Table 3-3 Flowchart of Function Code Modification
In Level III: if there is no flicker bit in parameters, it indicates the function code can not be modified. The possible reason is: a. The function code is unchangeable parameters. eg: actual detection parameters, running record parameters. b. Function code can not be modified at running statue. It can be modified after stopping.
‐ 49 ‐
VM1000 Series
3.3 Viewing Methods of Status Parameters
In stop or running status, it can separately demonstrate various status parameters by using “ 》 ”. Whether parameters are displayed is determined by the binary bits of values converted from the values of F7.03(parameter 1 LED displayed at running),
F7.04(parameter 2 LED displayed at running), and F7.05(parameter 3 LED displayed at stop) in the hexadecimal format
In stop status, a total of 12 status parameters can be displayed: setting frequency, bus voltage, DI input status, DO output status, Analog inputAI1 voltage, Analog inputAI2 voltage, actual count value, actual length value, PLC (running steps), load speed, PID setting, PULSE input frequency and three reserved parameters.
Pressing “ 》 ” to select the parameters.
In running status, there are 29 status parameters: running frequency, setting frequency, bus voltage, output voltage,output current are default display.Other display parameters:output power, output torque, DI input status, DO output status, analog input AI1 voltage, analog input AI2 voltage, analog input AI3 voltage,actual count value, actual length value,linear speed, PID setting, PID feedback are displayed by the binary bits of values converted from the values of
F7.03, F7.04. Pressing “ 》 ”and then switch the keys sequencely to display the selected parameter.
When VFD is power-on again, the display parameters are defaulted as the selected parameters before power off.
3.4 Password Setting
VM1000 offer protection function of user password. When FE.00 set as nonzero, namely user password, the password come into effect after exiting the function code editing .
Press PRG again, it will indicate “.....”. User password must be correctly input in order to access common menu. Otherwise, it cannot enter.
If you want to cancel code protection function, it needs to use passwords to enter and set FE.00 as 0.
‐ 50 ‐
VM1000 Series
Chapter 4 Quick Debugging Guide
4.1 Preparation and Examination Before Commissioning
Operation
VM1000 is the electrical appliance that used in motor drive and speed adjustment.
Therefore, it needs to make a preparation for electric and mechanic conditions before operating, and examine the commissioning operation. The following table
4-1 is relevant items
Item Instruction
Stabilization
&
Installation of VM 1000
In case loose wiring caused by moving or damages incurred by equipment drop, VFD should be installed firmly. Please refer to 2.1.3 and 2.1.4 to confirm the installation.
For temporary power-on operation, like product detection test, VFD should be placed on the platform stably and can’t be operated for a long time.
Input connection in main circuit
1. Be sure input voltage and capacity is conform to the requirements of VFD rated value.Please refer to the nameplate in 1.3 and data in 1.6 section
2. Be sure cable connection is correct and firm, meanwhile, the cable specification is complied with the reference data of cable selection in Section 3 of Annex A.
Output connection in main circuit
1. Make sure the rated voltage of motor is corresponding to the output rated value of VFD; make sure the connection is stable and secure.
2. Be sure cable connection is correct, meanwhile, the cable specification is complied with the reference data of cable selection in Section 3 of Annex A.
Motor installation condition
1. Make sure the installation of motor is stable and secure, and is corresponding to the requirements of mechanical design. The motor that is not securely installed will likely cause an accident.
2. For the idle motor or the motor with a load, ensure that the start will not cause damage to persons and equipment. Even if the test running should be in the same case. For those equipment that prohibit reversed rotation, it must remove the coupling between motor and mechanical first.,After confirming rotation is correct by commissioning operation, it can restore the mechanical connection.
3. In the torque control mode of VFD,it needs to ensure that there will be no
‐ 51 ‐
VM1000 Series danger of runaway in motor and equipment, while it needs to set and examine vfd max frequency of torque control rotation correspondingly (F3.12 and
F3.13). NOTE: Runaway refers to a state that is out of control because of a sudden and rapid acceleration with no load.
4. Make sure that the insulation of the motor is normal. When testing motor insulation,
VFD output wiring must be disconnected. Please refer to safety precautions in the manual.
Mechanical safety inspection
1. Make sure there are enough security measures for the drive motor and machine.
2. It is suggested to conduct no-load test in the first operation,
Control circuit connection
1. Adopt the cable selection which is conforming to A.3.
2. For the wiring of control circuit, please refer to 2.2.5 for design and inspection.
VFD parameters
Please check that the drive parameter settings is corresponding to mechanical design or control mode required by product testing.If not, it will likely result in accidents after starting.
For the drives applied in vector control mode, it also need for auto-tuning of motor parameters, Please refer to Section 4.5.
Table 4-1 Examination of Commissioning Operation
After completion of commissioning operation, it can be energized and conduct subsequent tests in accordance with the formal operation of electrical safety standards
‐ 52 ‐
VM1000 Series
4.2 Panel Operation
( 1 ) Application
It usually adopt panel operation for the single-drive VFD which doesn’t need external operating or control devices as well as regular product inspection. At the same time, it can use a knob or digital setting in the frequency setting principal.
( 2 ) Typical Wiring
Only after main circuit wiring, it can be operated by panel, including start/stop.
Figure 4-1 VFD Main Circuit Wiring
( 3 ) VFD Parameter Setting
Function code
Name Setting Instruction
F0.00
Notes
Control
Mode
Selection
1 V/F control
Setting factory value as 1, adopt
V/F control.When debugging, except rated value of motor, the other motor parameters don’t need to be adjust.
2. If it is changed as 0, vector control, please refer to section
4.5 to conduct auto-tuning of motor parameter.
When it is in simple application, keep the factory setting value unchanged
‐ 53 ‐
VM1000 Series
F0.01
F0.03
F0.08
F0.09
Control
Command
Source
0 : Command channel of operation panel
(light off)
The factory value is 0,it can implement start/stop control by panel operation
Remain unchanged
Master
Frequency
Reference
X
Selection
0:Eletronic potentiometer( non-retentive at power off)
When the factory value is set as
0, conduct the frequency given by the EVR of control panel
1: Digital setting
(retentive at power off) ……
It can be changed as 1, namely to modify the F0.08 frequency given value by operation panel
When using eletronic potentiometer, keep the factory value unchanged
Setting
Frequency
0.00Hz ~ max frequency
F0.10
When F0.03 is set as 1, it needs to set this parameters as running given frequency.
Running direction selection
0
1
:
:
Forward
Reverse
When the running direction of motor is not corresponding with the use requirements, the rotate direction can be changed by modifying this parameters
To modify this parameters is equivalent to commutation and wiring of motor
F0.10
Max output frequency
50.00Hz ~
400.00Hz
( V/F at max is1000.0Hz)
In accordance with the motor nameplate, ensure that the VFD output does not exceed the rating of the motor.
NOTE: Under certain circumstances, the motor can be adjusted according to frequency range allowed by motor.
Factory value
50.00Hz
Table 4-2 Common Parameters Setting of Operation Panel
Other parameters that may be adjusted: F0.18 acceleration time 1, F0.19 deceleration time 1 etc.
‐ 54 ‐
VM1000 Series
( 4 ) Steps of Panel Operation
Step Operation Panel display
Start Press “Run” Key
5- digit LED display become non-flicker from flicker when operating
Indicator Note
RUN indicator become lighter
Refer to 3.1
Viewing running status
Press “”key, switch display status in turn there are four items of default display : running frequency,setting frequency,bus voltage,output current
Stop
Turn on the Hz,A,V separately or turn them on in group
Refer to 3.1
Press
“STOP/RESET”
5- digit LED display become flicker from non-flicker
RUN Light off
Table 4-3 Panel Operation Procedure
Refer to 3.1
‐ 55 ‐
VM1000 Series
4.3 Start/Stop control of terminal forward rotation
( 1 ) Application
VFD common control mode is start/stop control. Generally, it is used in conveyor, fan, and pump etc.
( 2 ) Typical Wiring
In the control circuit, it can adopt 2 wiring or 3 wiring. The following is 2 wiring scheme
Figure 4-2 Start/Stop Control of Forward
( 3 ) VM 1000 Parameter Setting
In F0 group, except F0.01, other parameter can refer to Table 4-2
Function code
Name Setting Instruction
F0.01
Control
Command
Source
0: Keypad(with
LOCAL/REMOTE light off)
1: Terminals(with
LOCAL/REMOTE light on)
1. Modify the setting as 1, namely conduct the start and stop control by terminal input signal
2: Communication(with
LOCAL/REMOTE LED
2. Terminals(with
LOCAL/REMOTE
Note
‐ 56 ‐
VM1000 Series
F5.00
DI1 terminal function
Setting range : 0 ~ 50
1 indicates: forward rotation(FWD)
Factory value has been set as 0, namely adopt two wiring control mode 1
Factory value remain unchanged
F5.16
Terminal control mode
Setting range : 0 ~ 3
0 indicates: 2 wiring scheme
1
Factory value has been set as 0, namely adopt two wiring control mode 1
Factory value remain unchanged
Table 4-4 Common Parameters Setting of FWD Start/Stop
( 4 ) Operation Procedure
Steps Operation Panel display Indicator Note
Start
Viewing running status
Connect DI1 and COM
Usually, it adopts one manual switch or PLC output
5- digit LED display become non-flicker from flicker when operating
RUN Lights on
Press “”key, switch display status in turn
Refer to
3.1
There are four items of default display : frequency,setting frequency,bus voltage,output current
Turn on the
Hz,A,V separately or turn them on in group
Refer to
3.1
Stop
Disconnect DI1 and
COM
5- digit LED display become flicker from non-flicker
RUN Light off
Table 4-5 Running Procedures of FWD Start/Stop
Refer to
3.1
‐ 57 ‐
VM1000 Series
4.4 Common Control Guideline
4.4.1 Multi- step Speed Control
(1) Multi-step Speed
It indicates the selection of VFD preset out frequency is completed by the DI input terminals. It supports a maximum of 16 preset value.Usually, this mode is used for switching multiple operation speed in turn. It often applied in escalator,conveyor and large washing equipment etc.
(2) Typical wiring
The following is the wiring diagram of multi- step speed mode that adopt DI2 and
DI3
Figure 4-3 VM1000 FWD Multi-step Speed Control
(3) Parameter setting
This application is the control terminal control; start/stop can be 2-wire or 3-wire.
Control parameters can be found in the above Table 4-4. Table 4-6 is the parameter example of Figure 4-3 that adopts two DI terminals at 4- step speed
‐ 58 ‐
VM1000 Series
Function code
Name Setting Instruction Note
F5.01
DI2 terminal function
Setting range:0 ~ 50
12 ~ 15 indicates multi-step speed
1 ~ 4
Modify the setting as 12, namely DI2 is Multi-step speed 1
F5.02
FD.00
DI3 terminal function
Setting range:0 ~ 50
12 ~ 15 indicates multi-step speed 1 ~ 4
Modify the setting as 13, namely DI3 is Multi-step speed 2
Multi-step speed 0
-100.0%~100.0% (100.0% refers to maximum frequency F0.10)
Setting according to the applied requirements
FD.01
FD.02
Multi-step speed 1
-100.0% ~ 100.0%
Multi-step speed 2
-100.0% ~ 100.0%
Setting according to the applied requirements
Setting according to the applied requirements
FD.03
Multi-step speed 3
-100.0% ~ 100.0%
Setting according to the applied requirements
Table 4-6 FWD Control Parameter at Multi-step Speed
4.4.2 PID control
(1) PID control
It refers to PID algorithm- a control mode that is used for conducting process adjustment on controlled objects. In this mode, the VFD output is used to adjust some physical quantities such as speed, temperature, pressure, flow, etc., and the corresponding target values can be set via digital, analog given, and other communications given. It is often used in variable frequency air compressor, draw-bench, constant-pressure water supply, HVAC, and so on.
‐ 59 ‐
VM1000 Series
(2)Typical wiring
The following the water supply system wiring diagram that adopts given digital and analog feedback
M
Figure 4-4 VM1000 PID Control
(3) Parameters setting
This control application is terminal control, which start and stop is 2-wire or 3-wire.
The master frequency needs to be modified as PID. Part of the control parameters can be found in the above Table 4-4. The following Table 4-7 is the PID para example in Figure 4-4 that adopts AI2 analog feedback.
Function code
Name Setting Instruction Notes
F0.03
Master
Frequency
Reference X
Selection
0: Eletronic potentiometer
(non-retentive at power off)……
8 : PID
9:Communication given
Modify the setting as 8; adopt PID output as master frequency reference
F5.23
AI2 lower
0.00V ~ F5.20 Setting according to the Used for checking
‐ 60 ‐
VM1000 Series limit
F5.24
AI2 setting value correspondin g to AI2 lower limit
-100.0% ~
+100.0% applied requirements
Setting according to the applied requirements analog signal
Used for checking analog signal
F5.25
AI2 upper limit
F5.18 ~
+10.00V
F5.26
AI2setting value correspondin g to AI2 upper limit
-100.0% ~
+100.0%
F9.00
PID given source
Setting according to the applied requirements
Setting according to the applied requirements
Used for checking analog signal
Used for checking analog signal setting range : ~
6
0 indicates function code
F9.01 given
Factory value has been set as 0, namely set
F9.01 as digital setting
Keep the factory value unchanged
F9.01
~
F9.32 other parameters in
PID group
-100.0% ~
100.0%
Set and adjust according to the applied requirements
Some parameters need to be adjusted in order to get the proper value
Table 4-7 VM1000 PID Control Parameters
‐ 61 ‐
VM1000 Series
4.5 Auto-tuning of Motor Parameters
Selection of vector control mode : Before the drive operates ,you must input the exact nameplate parameters of motor, the standard motor parameters is equipped with 8000H inverter according to parameters on the nameplate; vector control has a high dependence on motor parameters.In order to get good control performance,it must receive the correct parameters of controlled motor.
Procedures of motor auto tuning are as follows:
First, the control command source (F0.02) is selected as keypad.
Then input the following parameters according to the actual motor parameters
(according to the current motor selection):
F2.00: GP Type Display Selection
F2.01: motor rated power
F2.02: motor rated voltage
F2.03: motor rated current
F2.04: motor rated frequency
F2.05: motor rated speed
If the motor is completely disconnected from the load, select 2 in F2.11 (auto-tuning completely), and then press the “RUN ”on the keypad , the VFD will automatically calculate following parameter of the motor:
F2.06: asynchronous motor stator resistance
F2.07: asynchronous motor rotor resistance
F2.08: asynchronous motor leakage inductance
F2.09: asynchronous mutual inductance
F2.10: Motor no load current
The motor parameter automatic tuning above is completed
If the motor can not be completely disconnected with load, select 1 in the F2.11
(static auto tuning), and then press the RUN key on the keyboard.
‐ 62 ‐
VM1000 Series
If VFD will measure the stator resistance, rotor resistance and leakage inductance instead of the mutual inductive reactance and load current,the user can calculate these two parameters on their own according to the motor nameplate. The parameters that used for calculating motor nameplate are: rated voltage U, rated current I, rated frequency and power factor η :
The calculation methods of motor no-load current and motor mutual inductance is as follows: L σ indicates motor leakage inductance. no-load current : I o
= calculation of mutual inductance: L m
=
I
o
: no-load current
L
m
: mutual inductance
L σ : leakage inductance
‐ 63 ‐
VM1000 Series
4.6 Faults Query and Reset step
( 1 ) Faults Status and Reset
In start/stop and running status, the VFD will access to fault status subject to various internal and external constraints or internal abnormalities. When security conditions and the devices permit, you need to reset the fault manually so as to return to normal standby status. Also, automatic fault reset function can be set on the VFD.
( 2 ) Faults Query and Reset Steps
Steps Operation Panel display Indicator Note
Viewing fault status
Viewing fault code
Failure panel displays fault codes beginning with an E, and flashes to remind
TUNE/TC
Lights flash
Indicator refer to 3.1
Fault code refer to
8.1
Viewing fault record
1. Viewing E0 parameters for
In fault status, it can not only the latest fault check fault information but information also enter and view various
2. E1 ~ E4 are historical fault information parameters, modify parameter values.
——
Reset
Deal with the the influence of failure, confirm the cause of the malfunction and eliminate it.
Under the qualified conditions, the error code is no longer displayed and return to the stop/standby status.
TUNE/TC
Lights off
2. Press the
"STOP /
RESET" button and reset 1
Indicator refer to 3.1
Table 4-8 Faults Query and Reset Step
‐ 64 ‐
VM1000 Series
4.7 Parameters Restore as Factory Value
Before restoring the parameters as factory value, please confirm the recovery does not pose a safety hazard to the equipment (such as control failure), nor lost some parameters after the commissioning. If necessary, it should make records. Note:
You can copy the parameters by LCD keypad.
Steps:
(1) Turn on F0 group; enter F0.20 (parameter initialization).
(2) Select 1 is factory parameters restoring (not including the motor parameters and record values)
(3) Select 2 is recorded value clearance, including a variety of accumulated data such as running time.
‐ 65 ‐
VM1000 Series
Chapter 5 Function Code Datasheet
(1)Parameter Protection
When FE-00 is set to a non-zero number, parameter protection code is enabled. You must use the correct user password to enter the menu.If you cancel the code, it needs to set FE.00 as 0.The parameters in shortcut menu is not included in the code protection.
(2)Symbol and Legend
The modification method of parameters in function code are marked with graphic symbols. The descriptions are as follows:
" ☆ ": The parameter can be modified when the AC drive is in either stop or running state.
" ★ ": The parameter cannot be modified when the AC drive is in the running state.
" ● ": The parameter is the actually measured value and cannot be modified.
" ◎ ": The parameter is factory parameter and can be set only by the manufacturer.
Function code
Description Set range Unit Default
Modifi
-cation level
F0.00
Control Mode
Selection
F0 Group: Basic Parameters
0: Sensorless Vector
Control(SVC)
1: V/F Control
1 1 ★
F0.01
Control Command
Source
0: Keypad(with
LOCAL/REMOTE light off)
1: Terminals(with
LOCAL/REMOTE light on)
2: Communication(with
LOCAL/REMOTE flashing)
1 0 ☆
‐ 66 ‐
VM1000 Series
Function code
Description Set range
F0.02
Base frequency for
UP/
DOWN modification during running
0 : Running Frequency
1 : Preset Frequency
F0.03
Master Frequency
Reference X
Selection
0 : Digital setting of F0.08 Preset
Frequency(Adjustable by pulse knob & Up/Down keys, non-retentive at power off)
1 : Digital setting of F0.08 Preset
Frequency(Adjustable by pulse knob & Up/Down keys modification, retentive at power off)
2 : AI1
3 : AI2
4 : Reserved
5 : PULSE Input ( DI6 )
6 : Multi-Step Speed Input
Frequency References
7 : Simple PLC
8 : PID
9 : Communication
Unit Default
Modifi
-cation level
1
1
1
0
★
★
F0.04
Auxiliary
Frequency
Reference Y
Selection
As the same as F0.03
F0.05
Auxiliary
Frequency
Reference Y's
Range Reference while in superposition of X and Y.
0 : Refer to Maximium Frequency
1 : Refer to Frequency Reference
X.
1
1
0
0
★
☆
‐ 67 ‐
VM1000 Series
Function code
Description
F0.06
Auxiliary
Frequency
Reference Y's
Scope Setting while in superposition of X and Y
0%~150%
Set range Unit
1%
Default
100%
F0.07
Frequency
References
Superposition
Selection
Units: Frequency Reference
Selection
0: Master Frequency Reference X
1: Calculation of Master with
Auxiliary Frequency
Reference(Calculation defined by setting of tens)
2: Switching between Master and
Auxiliary Frequency Reference.
3: Switching between Master and
Calculation of Master with
Auxiliary Frequency Reference
4: Switching between Auxiliary and Calculation of Master with
Auxiliary Frequency Reference
Tens: Calculation Definision of
Master and Auxiliary
0: Master+Auxiliary
1: Master-Auxiliary
2: Maximium Value between the
Two
3: Minimium Value between the
Two
11
F0.08 Preset Frequency
0.00Hz~Maximium Frequency
F0.10
0
0.01Hz 50.00Hz
Modifi
-cation level
☆
☆
☆
F0.09
Running Direction
Selection
0 : Forward
1 : Reverse
1 0 ☆
‐ 68 ‐
VM1000 Series
Function code
Description Set range Unit Default
Modifi
-cation level
F0.10
Maximium Output
Frequency
50.00Hz~400.00Hz
(Maximium 1000.0Hz Under V/F
Control Mode)
0.01Hz 50.00Hz ★
F0.11
Upper Limit
Frequency
Reference
Selection
0 : F0.12 Setting
1 : AI1
2 : AI2
3 : Reserved
4 : PULSE Input
5 : Communication
1 0 ★
F0.12
Upper Limit of
Running
Frequency
Minimium Running
FrequencyF0.14~Maximium
Output FrequencyF0.10
F0.13
Bias of Upper
Limit of Running
Frequency
0.00Hz~Maximium Output
Frequency F0.10
0.01Hz 50.00Hz
0.01Hz 0.00Hz
☆
☆
F0.14
Lower Limit of
Running
Frequency
0.00Hz~Upper Limit of Running
Frequency F0.12
0.01Hz 0.00Hz
F0.15
The function of lower limit frequency
When the frequency reference is lower than the Lower Limit of
Running Frequency,
0 : Running at lower limit frequency
1: Stop
2: Sleep
0
F0.16 Carrier Frequency 0.5kHz~16.0kHz
F0.17 Reserved
☆
☆
0.01 kHz
Rated
Model
Dependent
☆
‐ 69 ‐
VM1000 Series
Function code
F0.18
Description
Acceleration Time
1
Set range
0.0s~6500.0s
Unit Default
Modifi
-cation level
0.1s
Rated
Model
Dependent
☆
F0.19
Deceleration Time
1
0.0s~6500.0s 0.1s
Rated
Model
Dependent
☆
F0.20
Restore Default
Setting
F0.21
Parameter lock option
0:No operation
1: Restore to factory setting
2:Fault record clearing
0: Unlock parameter
1: Lock parameter
F0.22
Retentive option of digital setting frequency upon power off
0: Non-retentive
1: Retentive
F0.23
Acceleration/Decel eration Time Unit
0 : 1s
1 : 0.1s
2 : 0.01s
F0.24
Base Frequency
Reference of
Acceleration/Decel eration Time
0 : Maximium Running
Frequency ( F0.10
)
1 : Setting Frequency Source
2 : 100Hz
F0.25
Cooling fan
Control
0: Keep running during main output is on.
1: Keep running when the drive is power on.
1
1
1
1
1
1
0
0
1
1
0
0
★
☆
★
★
★
☆
‐ 70 ‐
VM1000 Series
Function code
Description
F0.26
Resolution of
Frequency
Command
1 : 0.1Hz
2 : 0.01Hz
Set range Unit Default
Modifi
-cation level
1 2
F1.00 Start Mode
F1 Group: Start and Stop Parameters
0: Direct start
1: Rotator speed tracking and start
2: Asynchronous motor pre-excite and start
1
F1.01
Rotator speed tracking method
0: From the frequency at power off
1: From zero speed
2: From maximum frequency
1
F1.02
Rotator tracking speed
1~100
F1.03 Start frequency 0.00~10.00Hz
F1.04
Holding time of start frequency
0.0s~100.0s
F1.05
DC braking/pre-excitin g current before start
0%~100%
F1.06
DC braking/pre-excitin g time before start
0.0s~100.0s
F1.07
Acceleration/Decel eration mode
0: Linear
1: S-curve A
2: S-curve B
F1.08
S-curve beginning segment time ratio
0.0%~(100.0%.F1.09)
1
0.01Hz
0.1s
1%
0.1s
1
0.10%
0
0
20
0.00Hz
0.0s
0%
0.0s
0
30.00%
‐ 71 ‐
★
☆
★
☆
☆
★
★
★
★
★
VM1000 Series
Function code
Description Set range
F1.09
S-curve ending segment time ratio
0.0%~(100.0%.F1.08)
F1.10 Stop mode
0: Decelerate to stop
1: Coast to stop
F1.11
Trigging frequency of DC braking at stop
0.00Hz~Maximum Frequency
F1.12
Waiting time before DC braking at stop
0.0s~100.0s
Unit
0.10%
1
0.01Hz
0.1s
Default
30.00%
0
0.00Hz
0.0s
F1.13
DC braking current at stop
0%~100%
F1.14
DC braking time at stop
0.0s~100.0s
F2.01 Motor rated power 0.1kW~400.0kW
1%
0.1s
0%
0.0s
F1.15
Applying ratio of braking unit
0%~100%
F2.00 Drive model
F2 Group: Motor Parameters
0:General model (Constant torque style‘s loads)
1:Pump model (Fan & Pump style's loads)
1%
1
100%
Rated
Model
Dependent
0.1kW
Rated
Model
Dependent
Modifi
-cation level
★
☆
☆
☆
☆
☆
☆
●
★
F2.01
Motor rated
Voltage
1V~440V 1V
Rated
Model
Dependent
★
‐ 72 ‐
VM1000 Series
Function code
Description
F2.03 Motor rated current
F2.04
Motor rated frequency
Set range
0.01A~655.35A
0.1A~6553.5A
(
(
<=55kW
>55kW )
)
0.00Hz~Maximum Frequency
Unit Default
Modifi
-cation level
0.01A/
0.1A
Rated
Model
Dependent
★
0.01Hz
Rated
Model
Dependent
★
F2.05
F2.06
F2.07
F2.08
F2.09
Motor rated rotation speed
Asynchronous motor stator resistance
Asynchronous motor rotator resistance
Asynchronous motor leakage inductance
Asynchronous motor mutual inductance
F2.10
Motor no-load current
1rpm~36000rpm 1rpm
Rated
Model
Dependent
★
0.001
Ω ~65.535
Ω ( <=55kW )
0.0001
Ω ~6.5535
Ω ( >55kW )
0.001
Ω
/
0.0001
Ω
Rated
Model
Dependent
0.001
Ω ~65.535
Ω ( <=55kW )
0.0001
Ω ~6.5535
Ω ( >55kW )
0.001
Ω
/
0.0001
Ω
Rated
Model
Dependent
0.01mH~655.35mH ( <=55kW )
0.001mH~65.535mH ( >55kW )
0.01m
H/
0.001m
H
Rated
Model
Dependent
★
★
★
0.01mH~6553.5mH ( <=55kW )
0.01mH~655.35mH ( >55kW )
0.1mH/
0.01m
H
Rated
Model
Dependent
★
0.01A~F2.03
0.1A~F2.03
(
(
<=55kW
>55kW )
) 0.01A/
0.1A
Rated
Model
Dependent
★
‐ 73 ‐
VM1000 Series
Function code
Description Set range
F2.11
Motor parameters autotuning
0: No autotuning
1: Static autotuning(with load)
2: Autotuning completely(no load)
F2.12-
F2.37
Reserved
Unit
1
Default
0
Modifi
-cation level
★
F3 Group: Vector Control Parameters
F3.00
Proportional gain 1 of speed loop
1~100 1 30 ☆
F3.01
Integral time 1 of speed loop
0.01s~10.00s
F3.02 Switch frequency 1 0.00~F3.05
F3.03
Proportional gain 2 of speed loop
1~100
F3.04
Integral time 2 of speed loop
0.01s~10.00s
F3.05 Switch frequency 2 F3.02~Maximum frequency
F3.06
Coefficient of slip compensation in vector control mode
50%~200%
0.01s
0.01Hz
1
0.01s
0.50s
5.00Hz
20
1.00s
0.01Hz 10.00Hz
1% 100%
☆
☆
☆
☆
☆
☆
F3.07
Filter time constant of speed loop
0.000s ~ 0.100s
F3.08
Torque upper limit for speed control mode
0.0%~200.0%
‐ 74 ‐
0.001s 0.000s ☆
0.10% 150.00% ☆
VM1000 Series
Function code
Description
F3.09
Speed/torque control mode selection
0: Speed control mode
1: Torque control mode
F3.10
Torque upper limit reference source in torque control mode
0 : Digital setting
1 : AI1
2 : AI2
3 : Reserved
4 : PULSE setting
5 : Communication setting
6 : MIN(AI1,AI2)
7 : MAX(AI1,AI2)
F3.11
Torque upper limit for torque control mode
-200.0%~200.0%
F3.12
Max. forward frequency for torque control mode
F3.13
Max. reverse frequency for torque control mode
Set range
0.00Hz~Maximum Frequency
0.00Hz~Maximum Frequency
F3.14
Acceleration time for torque control
0.00s~650.00s
F3.15
Deceleration time for torque control
0.00s~650.00s
F3.16
Torque stiffness coefficient
10.0%~120.0%
F3.17
Proportional gain of M axis current loop
0~60000
‐ 75 ‐
Unit Default
Modifi
-cation level
100.00
%
0.00% ★
100.00
%
0.00% ★
0.10% 150.00% ☆
0.01Hz 50.00Hz ☆
0.01Hz 50.00Hz ☆
0.01s
0.01s
0.001
1
0.00s
0.00s
1
2000
☆
☆
☆
☆
VM1000 Series
Function code
Description
F3.18
Integral gain of M axis current loop
0~60000
Set range Unit
1
F3.19
Proportional gain of T axis current loop
0~60000
F3.20
Integral gain of T axis current loop
0~60000
1
1
F3.21
Speed loop integral seperation
0: Invalid
1: Valid
F4 Group: V/F Control Parameters
1
Default
1300
2000
1300
0
Modifi
-cation level
☆
☆
☆
☆
F4.00
V/F curve & mode selection
0: Linear V/F curve
1: Multi-point V/F curve
2: Square V/F curve
3~9: Reserved
10: V/F complete seperation mode
11: V/F half seperation mode
1 0 ★
F4.01 Torque boost
0.0% : Automatic torque boost
0.1%~30.0% (Invalid when in V/F seperation mode
0.10%
Rated
Model
Dependent
☆
F4.02
Torque boost cut-off frequency
0.00Hz~Maximum Frequency
F4.03
Multi-point V/F curve's frequency point 1
0.00Hz~F4.05
F4.04
Multi-point V/F curve's voltage point 1
0.0%~100.0%
0.01Hz 50.00Hz
0.01Hz
0.10%
0.00Hz
0.00%
★
★
★
‐ 76 ‐
VM1000 Series
Function code
Description Set range
F4.05
Multi-point V/F curve's frequency point 2
F4.03~F4.07
F4.06
Multi-point V/F curve's voltage point 2
0.0%~100.0%
F4.07
Multi-point V/F curve's frequency point 3
F4.05~Motor rated freqency(F2.04)
F4.08
Multi-point V/F curve's voltage point 3
0.0%~100.0%
F4.09
Coefficient of slip compensation in
V/F control mode
0.0%~200.0%
F4.10
V/F over-excitation gain
0 ~ 200
F4.11
Oscillation suppression gain
0 ~ 100
Unit
0.01Hz
0.10%
0.01Hz
0.10%
0.10%
1
1
F4.12
Voltage reference in V/F seperation mode
0: Digital Setting (F4.13)
1: AI1
2: AI2
3: Reserved
4: PULSE input ( DI6 )
5: Multi-step speed input
6 : Simple PLC
7 : PID
8 : Communication, 100.0% refers to motor rated voltage.
1
Default
0.00Hz
0.00%
0.00Hz
0.00%
0.00%
64
Rated
Model
Dependent
0
Modifi
-cation level
★
★
★
★
☆
☆
☆
☆
‐ 77 ‐
VM1000 Series
Function code
Description Set range
F4.13
Digital setting for voltage reference in
V/F seperation
0V~Motor rated voltage mode
Unit
1V
F4.14
Voltage rising time for V/F seperation mode
0.0s~1000.0s
(Time from 0V to motor rated voltage.)
0.1s
F5 Group: Input Terminals Parameters
Default
0V
0.0s
Modifi
-cation level
☆
☆
F5.00
F5.01
F5.02
DI1 terminal function
DI2 terminal function
DI3 terminal function
0: No function
1: Run forward(FWD)
2: Run reverse(REV)
3: 3-wire control
4: Jog forward (FJOG)
5: Jog reverse (RJOG)
6: UP command
7: DOWN command
8: Coast to stop
9: Fault reset (RESET)
10: Pause running
11: External fault input N. O.
12: Multi-step speed terminal 1
13: Multi-step speed terminal 2
14: Multi-step speed terminal 3
15: Multi-step speed terminal 4
16: Acceleration/Deceleration
Time Selection Terminal 1
17: Acceleration/Deceleration
Time Selection Terminal 2
18: : Frequency Reference
Switching Terminal
19: Reset UP/DOWN Frequency
Setting(Both keypad and terminals)
1
1
1
1
2
9
★
★
★
‐ 78 ‐
VM1000 Series
Function code
Description
F5.03
F5.04
F5.05
DI4 terminal function
DI5 terminal function
DI6 terminal function
Set range Unit Default
Modifi
-cation level
20: Control Command Switching
Terminal 1
21: Acceleration/deceleration prohibited
22: PID Control Pause
23 : Simple PLC Running Status
Reset
24 : Swing Frequency Pause
25: Counter Input
26: Counter Reset
27: Length Counting Input
28: Length Counting Reset
29: Torque Control Prohibit
30 :
Input, DI6 terminal only)
31: Reserved
32: DC Brake Instantly
33: External Fault Input N.C.
34: Frequency Setting Taking
Effect ( If no terminal is set to this value, the function is in effect defaultly)
35: PID Control Output Reverse
36: External Stop terminal 1
37: Control Command Switching terminal 2
38: PID Integration Pause
39: Switching terminal, between
Frequency Reference X and Preset
Frequency
40: Switching terminal, between
Frequency Reference Y and Preset
Frequency
41~42: Reserved
43: PID Parameter Switching
Terminal
44: User Defined Fault 1
44: User Defined Fault 2
1
1
1
0
0
0
★
★
★
‐ 79 ‐
VM1000 Series
Function code
Description
F5.06
-F0.09
Reserved
F5.10
VDI terminal function
Set range Unit Default
Modifi
-cation level
46: Speed/Torque Control Mode
Switching
47: Emergency Stop
48: External Stop Terminal 2
49: Decelerating and DC Braking
50: Time Clearing of Present
Running
51~59: Reserved
1 0 ★
F5.11~
F5.14
Reserved
F5.15 DI filter time 0.000s~1.000s
F5.16
Terminal control mode
0: 2-wire control mode 1
2: 2-wire control mode 2
3: 3-wire control mode 1
4: 3-wire control mode 2
0.001s
1
0.010s
0
☆
★
F5.17
Frequency changing rate through UP/
DOWN terminal adjusting
0.01Hz~ 6553.5Hz
F5.18 AI1 lower limit 0.00V~F5.20
F5.19
Setting value corresponding to
AI1 lower limit
-100.0% ~ +100.0%
F5.20 AI1 upper limit F5.18 ~ +10.00V
0.01Hz
0.01V
0.10%
0.01V
0.10Hz
0.00V
0.00%
10.00V
☆
☆
☆
☆
F5.21
Setting value corresponding to
AI1 upper limit
-100.0% ~ +100.0%
F5.22 AI1 filter time 0.00s ~ 10.00s
0.10% 100.00%
0.01s 0.10s
☆
☆
‐ 80 ‐
Function code
VM1000 Series
Description
F5.23 AI2 lower limit
F5.24
Setting value corresponding to
AI2 lower limit
-100.0% ~ +100.0%
F5.25 AI2 upper limit
F5.26
Setting value corresponding to
AI2 upper limit
-100.0% ~ +100.0%
F5.27 AI2 filter time 0.00s ~ 10.00s
F5.28
PULSE input lower limit
0.00kHz ~ F5.30
F5.29
Setting value corresponding to
PULSE input lower
-100.0% ~ 100.0% limit
F5.30
PULSE input upper limit
F5.28 ~ 100.00kHz
F5.31
Setting value corresponding to
PULSE input upper
-100.0% ~ 100.0% limit
F5.32 PULSE filter time 0.00s ~ 10.00s
F5.33 DI1 ON delay 0.0s ~ 3600.0s
F5.34 DI2 ON delay 0.0s ~ 3600.0s
F5.35 DI1 OFF delay
Set range
0.00V ~ F5.25
F5.23 ~ +10.00V
0.0s ~ 3600.0s
Unit Default
0.01V 0.00V
Modifi
-cation level
☆
0.10% 0.00% ☆
0.01V 10.00V ☆
0.10% 100.00% ☆
0.01s 0.10s
0.01kH
z
0.00kHz
☆
☆
0.10%
0.01kH
z
0.10% 100.00%
0.01s
0.1s
0.1s
0.1s
0.00%
50.00kHz
0.10s
0.0s
0.0s
0.0s
☆
☆
☆
☆
★
★
★
‐ 81 ‐
VM1000 Series
Function code
Description
F5.36 DI2 OFF delay
Set range
F5.37
DI input ON status setting 1
0.0s ~ 3600.0s
0: High level
1: Low level
Unit: DI1
Tens: DI2
Hundreds: DI3
Thousands: DI4
Tens thousands: DI5
F5.38
DI input ON status setting 2
0: High level
1: Low level
Unit: DI6
Tens: Reserved
Hundreds: Reserved
Thousands: Reserved
Tens thousands: Reserved
Unit
0.1s
11111
11111
F6 Group: Output Terminals Parameters
F6.00
FM terminal output selection
0: Pulse output(FMP)
1: Open collector discrete output(FMR)
1
Default
0.0s
0
0
0
Modifi
-cation level
★
★
★
☆
F6.01
FMR open collector output function
F6.02
Relay 1 output function
0: No output
1: AC drive running
2: Fault output (stop)
3: Frequency-level detection
FDT1 output
4: Frequency reached
5: Zero-speed running (no output at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
9: Designated count value reached
10: Length reached
1
1
0
2
☆
☆
‐ 82 ‐
VM1000 Series
Function code
Description
F6.03
F6.04
~F6.05
F6.06
F6.07~
F6.10
Relay 2 output function
Reserved
VDO output function
Reserved
Set range Unit Default
Modifi
-cation level
11: PLC cycle complete
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for Run
16: AI1>AI2
17: Frequency upper limit reached
18: Frequency lower limit reached
(no output at stop)
19: Undervoltage state output
20: Communication setting
21: Reserved
22: Reserved
23: Zero-speed running 2 (having output at stop)
24: Accumulative power-on time reached
25: Frequency level detection
FDT2 output
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing reached
31: AI1 input limit exceeded
32: Load loss
33: Reverse running
34: Zero current state
35: Module temperature reached
36: Software current limit exceeded
37: Frequency lower limit reached
(having output at stop)
38: Alarm output(Keep running)
39: Motor overheat warning
40: Current running time reached
41: User defined output 1
42: User defined output 2
1
1
1
0
☆
☆
‐ 83 ‐
VM1000 Series
Function code
Description Set range
F6.11
FMP output options
0: Running frequency
1: Target frequency
2: Output current
3: Output torque
F6.12 AO1 output options
4: Output power
5: Output voltage
6: Pulse input( 100% correspond to 100.0kHz)
7: AI1
8: AI2
9: Reserved
10: Length counting value
11: Couter value
F6.13 AO2 output options
12: Communication frequency reference
13: Motor rotating speed
14: Output current( 100% correspond to rated current)
15: Output voltage( 100% correspond to rated voltage)
16: Reserved
F6.14
FMP output maximum frequency
F6.15
AO1 zero offset coefficient
0.01kHz~100.00kHz
-100.0%~100.0%
F6.16 AO1 gain -10.00~10.00
F6.17 AO2 zero offset -100.0%~100.0%
Unit
1
1
1
0
0
1
☆
☆
☆
0.01kH
z
50.00kHz ☆
0.10%
0.01
0.10%
Default
0.00%
1
0.00%
Modifi
-cation level
☆
☆
☆
‐ 84 ‐
‐ 85 ‐
VM1000 Series
Function code
Description Set range
F6.28
0: Running frequency
1: Target frequency
2: DC bus voltage
3: Output voltage
4: Output current
Test value selection 5: Output Power for user defined output (EX) 1
6: Output torque
7~8: Reserved
9: AI1 input value
10: AI2 input value
11: Reserved
12: Couter value
13: Length counting value
F6.29
Comparison method of user defined output 1
Units: comparison test method
0: Equal(EX==X1)
1: Equal or greater than
2: Equal or less than
3: Interval comparison(X1 ≤
EX ≤ X2)
4: Bits test(EX & X1 = X2
Tens: Output method
0: False value output
1: True value output
F6.30
User defined dead interval 1
0 ~ 65535
F6.31
User defined output
1 comparison value 0 ~ 65535
X1
F6.32
User defined output
1 comparison value 0 ~ 65535
X2
Unit Default
Modifi
-cation level
0
0
0
0
0
☆
☆
☆
☆
☆
‐ 86 ‐
VM1000 Series
Function code
Description Set range
F6.33
0: Running frequency
1: Target frequency
2: DC bus voltage
3: Output voltage
4: Output current
Test value selection 5: Output Power for user defined output (EX) 2
6: Output torque
7~8: Reserved
9: AI1 input value
10: AI2 input value
11: Reserved
12: Couter value
13: Length counting value
Unit Default
Modifi
-cation level
F6.34
Comparison method of user defined output 2
Units: comparison test method
0: Equal(EX==X3)
1: Equal or greater than
2: Equal or less than
3: Interval comparison(X3 ≤
EX ≤ X4)
4: Bits test(EX & X3 = X4
Tens: Output method
0: False value output
1: True value output
F6.35
User defined dead interval 2
0 ~ 65535
F6.36
User defined output
2 comparison value 0 ~ 65535
X3
F6.37
User defined output
2 comparison value 0 ~ 65535
X4
‐ 87 ‐
0
0
0
0
0
☆
☆
☆
☆
☆
VM1000 Series
Function code
Description Set range Unit Default
Modifi
-cation level
F7 Group: Keypad & Display Interface Parameters
F7.00
LCD yeypad parameter copy
0: No operation
1: Local parameters will be copied to LCD keypad
2: LCD keypad will download parameters to local drive.
1
F7.01 MF.K key function
0: No function
1: Switching control command source between keypad and remote control(Remote control include communication and terminals command).
2: Switching rotation between
FWD & REV
3: Jog Forward
4: Jog Reverse
F7.02
STOP/RESET key stop function
0: Only valid in keypad control command mode
1: Always valid in any control command mode
F7.03
Running status
LED display selection 1
0000~FFFF
Bit00: Running frequency(Hz)
Bit01: Target frequency(Hz)
Bit02: DC bus voltage(V)
Bit03: Output voltage(V)
Bit04: Output current(A)
Bit05: Output Power(kW)
Bit06: Output torque(%)
Bit07: DI input status
Bit08: DO output status
Bit09: AI1 input value(V)
Bit10: AI2 input value(V)
Bit11: Reserved
Bit12: Counter value
‐ 88 ‐
1
1
1111
0
0
1
17
●
★
☆
☆
VM1000 Series
Function code
Description
F7.04
Running status
LED display selection 2
Set range Unit Default
Modifi
-cation level
Bit13: Length counting value
Bit14: Load speed display
Bit15: PID setting value
0000~FFFF
Bit0: PID feedback
Bit1: Current step of PLC running
Bit2: Feedback speed, unit 0.1Hz
Bit3: Feedback speed
Bit4: Running time left
Bit5: AI1 voltage before correction
Bit6: AI2 voltage before correction
Bit7: Reserved
Bit8: Line speed
Bit9: Time since current power on
Bit10: Time of current running
Bit11: PULSE input frequency,
Unit 1Hz
Bit12: Setting of communication
Bit13: Reserved
Bit14: Master frequency reference
X display
Bit15: Auxiliary frequency reference Y display
1111 0 ☆
F7.05
Stop status LED display selection
0000~FFFF
Bit00: Target frequency(Hz)
Bit01: DC bus voltage(V)
Bit02: DI input status
Bit03: DO output status
Bit04: AI1 input value(V)
Bit05: AI2 input value(V)
Bit06: Reserved
Bit07: Counter value
Bit08: Length counting value
‐ 89 ‐
1111 33 ☆
VM1000 Series
Function code
Description Set range
Bit09: Current step of PLC running
Bit10: Load speed display
Bit11: PID setting value
Bit12: PULSE input frequency,
Unit 0.01kHz?
F7.06
Load speed display ratio
0.0001 ~ 6.5000
F7.07
Heat sink temperature of inverter Power module
F7.08
Heat sink temperature of rectifier bridge
F7.09
Accumulative running time
0.0
0.0
0h
F7.10 Product number -
F7.11 Firmware version -
℃~
℃~
~
100
100
65535h
F7.12
Number of decimal places for load speed display
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
F7.13
Accumulative power-on time
0h~65535h
Unit
0.0001
0.1
0.1
℃
℃
1h
1
1h
Default
0.3
.
.
.
.
.
0
.
Modifi
-cation level
☆
●
●
●
●
●
☆
●
F7.14
Accumulative consumed electric energy(kWh)
0~65535 kWh 1kWh . ●
‐ 90 ‐
VM1000 Series
Function code
Description Set range Unit Default
Modifi
-cation level
F8 Group: Auxiliary Function Parameters
0.01Hz 2.00Hz ☆ F8.00 Jog frequency
F8.01
Jog acceleration time
0.00Hz~Maximum Frequency
0.0s ~ 6500.0s
F8.02
Jog deceleration time
0.0s ~ 6500.0s
0.1s
0.1s
20.0s
20.0s
☆
☆
F8.03 Acceleration time 2 0.0s
F8.04 Deceleration time 2 0.0s
F8.05 Acceleration time 3 0.0s
F8.06 Deceleration time 3 0.0s
F8.07 Acceleration time 4 0.0s
~
~
~
~
~
6500.0s
6500.0s
6500.0s
6500.0s
6500.0s
0.1s
Rated
Model
Dependent
0.1s
Rated
Model
Dependent
0.1s
Rated
Model
Dependent
0.1s
Rated
Model
Dependent
0.1s
Rated
Model
Dependent
☆
☆
☆
☆
☆
F8.08 Deceleration time 3 0.0s ~ 6500.0s 0.1s
Rated
Model
Dependent
☆
F8.09 Jump frequency 1 0.00Hz~Maximum Frequency
F8.10 Jump frequency 2 0.00Hz~Maximum Frequency
0.01Hz 0.00Hz
0.01Hz 0.00Hz
☆
☆
‐ 91 ‐
VM1000 Series
Function code
Description
F8.11
Jump frequency width
Set range
0.00Hz~Maximum Frequency
F8.12
FWD/REV switchover dead zone time
0.0s~3000.0s
F8.13 Reverse option
0: Reverse allowed
1: Reverse Prohibited
F8.14
Carrier Frequency adjusting by temperature
0: Disable
1: Enable
0.00Hz~10.00Hz F8.15 Droop control
F8.16
Accumulative power-on time threshold
0h ~ 65000h
F8.17
Accumulative running time threshold
F8.18
Drive startup protection
0h ~ 65000h
0: Disable
1: Enable
F8.19
Frequency detection value
(FDT1)
0.00Hz~Maximum Frequency
F8.20
Frequency detection hysteresis (FDT 1)
0.0%~100.0% (FDT1 Level)
F8.21
Detection width of frequency reached
0.0% ~ 100.0% (Maximum frequency)
Unit Default
Modifi
-cation level
0.01Hz 0.00Hz ☆
0.1s
1
1
1h
1h
1
0.10%
0.10%
0.0s
0
1
0.01Hz 0.00Hz
0h
65000h
0
0.01Hz 50.00Hz
5.00%
0.00%
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
‐ 92 ‐
VM1000 Series
Function code
Description
F8.22
Jump frequency validity during acceleration/decele ration
0: Invalid
1: Valid
F8.23
Option as accumulative running time reached
Set range
0: operation continue
1: Error code alarm
F8.24
Acting option as accumulative power-on time reached
0: operation continue
1: Error code alarm
F8.25
Frequency point for switchover between acceleration time 1
0.00Hz~Maximum Frequency and acceleration time 2
F8.26
Frequency point for switchover between deceleration time 1
0.00Hz~Maximum Frequency and deceleration time 2
F8.27
Terminal jogging priority
0: Disable
1: Enable
F8.28
Frequency detection value
(FDT2)
0.00Hz~Maximum Frequency
F8.29
Frequency detection hysteresis (FDT 2)
0.0%~100.0% (FDT2 Level)
‐ 93 ‐
Unit Default
Modifi
-cation level
1
1
1
0.01Hz 0.00Hz
0.01Hz 0.00Hz
1
0
0
0
1
0.01Hz 50.00Hz ☆
0.10% 5.00%
☆
★
★
☆
☆
☆
☆
VM1000 Series
Function code
Description Set range
F8.30
Given frequency reached 1
0.00Hz~Maximum Frequency
F8.31
Given frequency reached detection width 1
0.0%~100.0% (Maximum frequency)
Unit Default
0.01Hz 50.00Hz
0.10% 0.00%
F8.32
Given frequency reached 2
0.00Hz~Maximum Frequency 0.01Hz 50.00Hz
F8.33
Given frequency reached detection width 2
0.0%~100.0% (Maximum frequency)
F8.34
Zero current detection level
0.10% 0.00%
0.0%~300.0%, 100.0% is corresponding to motor rated current, No output in stop status.
0.10% 5.00%
Modifi
-cation level
☆
☆
☆
☆
☆
F8.35
Zero current detection time
F8.36
Programm over current setting
0.01s ~ 600.00s 0.01s 0.10s
0.0%: No detection
0.1%~300.0% Motor rated current
0.10% 200.00%
F8.37
Programm over current detection time
0.00s ~ 600.00s
F8.38
Given current reached 1
0.0% ~ 300.0% Motor rated current
0.01s 0.00s
0.10% 100.00%
F8.39
Given current reached detection width 1
0.0% ~ 300.0% Motor rated current
F8.40
Given current reached 2
0.0% ~ 300.0% Motor rated current
0.10% 100.00%
0.10% 100.00%
☆
☆
☆
☆
☆
☆
‐ 94 ‐
VM1000 Series
Function code
Description Set range
F8.41
Given current reached detection width 2
0.0% ~ 300.0% Motor rated current
F8.42 Timing operation
0: Disable
1: Enable
F8.43 Timing reference
0: F8.44 Timing setting
1: AI1
2: AI2
3: reserved
Unit
0.10% 100.00%
1
1
Default
0
0
F8.44 Timing setting 0.0Min ~ 6500.0min
F8.45
AI1 input voltage lower limit
0.00V~F8.46
F8.46
AI1 input voltage upper limit
F8.45~10.00V
F8.47 inverter Power module temperature reached
0 ~100
F8.48
Rapid current limiting function
0: Disable
1: Enable
F9.00
PID reference source
F9 Group: PID parameters
0: Preset value(F9.01)
1: Analog terminal AVI
2 Analog terminal ACI
3: Communication interface
4: Muli-function digital input terminals
F9.01 PID preset value 0.0%~100.0%
0.1min 0.0min
0.01V
0.01V
1 ℃
1
1
0.10%
3.10V
6.80V
75 ℃
1
0
50.0%
Modifi
-cation level
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
‐ 95 ‐
VM1000 Series
Function code
Description Set range
F9.02
PID feedback selection
F9.03
PID control characteristic
0: AI1
1: AI2
2: Reserved
3: AI1-AI2
4: PULSE input ( DI6 )
5: Communication
6: AI1+AI2
7: MAX(|AI1|, |AI2|)
8: MIN(|AI1|, |AI2|)
0: Positive
1: Negative
F9.04
PID reference & feedback range
0 ~ 65535
F9.05
Proportional gain
P1
0.0~100.0
F9.06 Integral time I1 0.01s~10.00s
F9.07
Differential time
D1
0.000s~10.000s
F9.08
PID reverse output frequency limit
0.00~Maximum frequency
F9.09
PID control deviation limit
F9.10
PID differential limit
0.0%~100.0%
0.00%~100.00%
F9.11
PID reference gradual effect time
0.00~650.00s
F9.12
PID feedback filter time
0.00~60.00s
‐ 96 ‐
Unit Default
Modifi
-cation level
1 0 ☆
1
1
0
1000
0.1
0.01s
20
2.00s
0.001s 0.000s
☆
☆
☆
☆
☆
0.01Hz 2.00Hz ☆
0.10% 0.00% ☆
0.01% 0.10% ☆
0.01s 0.00s ☆
0.01s 0.00s ☆
VM1000 Series
Function code
Description Set range
F9.13
PID output filter time
0.00~60.00s
F9.14
Proportional gain
P2
0.0~100.0
F9.15 Integral time I2 0.01s~10.00s
F9.16
Differential time
D2
0.000s~10.000s
F9.17
PID control parameter switching function
0: No switching
1: Switching by DI terminal
2: Switching by deviation
F9.18
PID control parameter switching deviation
0.0%~F9.19
1
F9.19
PID control parameter switching deviation
F9.18~100.0%
2
F9.20
PID initial output value
0.0%~100.0%
F9.21
PID initial output time
0.00~650.00s
F9.22
Maximum positive deviation limit of output interval
0.00% ~ 100.00%
F9.23
Maximum positive deviation limit of output interval
0.00%~100.00%
‐ 97 ‐
Unit Default
Modifi
-cation level
0.01s 0.00s ☆
0.1
0.01s
20
2.00s
0.001s 0.000s
☆
☆
☆
1 0 ☆
0.10% 20.00% ☆
0.10% 80.00% ☆
0.10% 0.00% ☆
0.01s 0.00s ☆
0.01% 1.00% ☆
0.01% 1.00% ☆
VM1000 Series
Function code
Description Set range
F9.24 PID integral option
Units: Seperated Integral calculation
0: Disable
1: Enable
Tens: Output reaching limit and stopping integral
0: Continue integral
1: Stop integral
F9.25
PID feedback loss detection
0.0%: No detection
0.1% ~ 100.0
%
F9.26
PID feedback loss detection time
0.0s~20.0s
Unit
11
0.10%
0.1s
Default
0
0.00%
0.0s
F9.27 PID option at stop
0: No calculation cotinue at stop
1: Calculation continue at stop
F9.28
PID auxiliary function
0: Normal PID
1: PID with sleeping function
F9.29
PID sleeping threshold
0.0%~100.0%
F9.30 PID sleeping delay 0.0~3600.0s
1
1
0.10% 60.00%
0.1s
0
0
3.0s
F9.31
PID wakeup threshold
0.0%~100.0% 0.10% 20.00%
F9.32 PID wakeup delay 0.0~3600.0s 0.1s
FA Group: Protection Parameters and Fault Record
3.0s
FA.00
Motor overload protection
FA.01
Motor overload protection gain
0: Disable
1: Enable
0.20~10.00
1
0.01
1
1
Modifi
-cation level
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
‐ 98 ‐
Function code
FA.02
Motor overload warning coefficient
50%~100%
FA.03
FA.04
FA.05
VM1000 Series
Description
Over-voltage stall gain
0~100
Over-voltage stall protection voltage
120%~150%
Over-current stall gain
0~100
Set range
FA.06
Over-current stall
Protection currnet
100%~200%
FA.07
Protecton against short-circuit to ground at power on
0: Disable
1: Enable
FA.08
Fault auto reset times
0~20
FA.09
Options for fault output DO during fault auto reset
0: Disable
1: Enable
FA.10
Fault auto reset interval
0.1s~100.0s
FA.11
Input phase-loss protection
0: Disable
1: Enable
FA.12
Output phase-loss protection
0: Disable
1: Enable
Unit Default
Modifi
-cation level
1% 80% ☆
1 0 ☆
1% 130% ☆
1 20 ☆
1% 150% ☆
1
1
1
0.1s
1
1
1
0
0
1.0s
1
1
☆
☆
☆
☆
☆
☆
‐ 99 ‐
VM1000 Series
Function code
Description
FA.13
Fault protection action option 1
FA.14
Fault protection action option 2
FA.15
Fault protection action option 3
Set range Unit Default
Modifi
-cation level
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: Motor overload(Err11)
Tens: Input phase-loss(Err12)
Hundreds: Output phase-loss(Err13)
Thousands: External fault(Err15)
Tens of Thousand:
Communication Error(Err16)
11111 0 ☆
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: Reserved
Tens: Parameter Re-write failure(Err21)
Hundreds: Reserved
Thousands: Reserved
Tens of Thousand: accumulative running time reached(Err16)
11111
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: User defined fault 1 (Err27)
Tens: User defined fault 2 (Err28)
Hundreds: Reserved
Thousands: Load loss(Err30)
Tens of Thousand: PID feedback loss during operation(Err31)
11111
0
0
☆
☆
‐ 100 ‐
VM1000 Series
Function code
FA.16
Description
Fault protection action option 4
Set range Unit Default
Modifi
-cation level
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: Motor speed deviation too large (Err42)
Tens: Motor over speed (Err43)
Hundreds: Initial position error(E51)
Thousands: Reserved)
Tens of Thousand: Reserved
11111 0 ☆
FA.17 Reserved
FA.18
Under-voltage setting
60.0%~140.0%
FA.19
Over-voltage setting
200.0V~2500.0V
FA.20
Frequency option for continuing to run upon fault
0: Current running frequency
1: Selected frequency reference
2: Upper limit frequency
3: Lower limit frequency
4: Preset backup freqency in abnormal condition
0.10% 100.00%
0.1V
1
810
0
☆
☆
☆
FA.21
Preset backup freqency in abnormal condition
0.0%~100.0%(Current target frequency)
FA.22
Action at instantaneous power failure
0: No action
1: Deceleration
2: Deceleration and stop
FA.23
Action pause voltage at instantaneous power failure
80.0%~100.0%
0.10% 100.00%
1
0.10%
0
90.00%
☆
☆
☆
‐ 101 ‐
VM1000 Series
Function code
Description Set range
FA.24
Voltage recoverring time at instantaneous power failure
0.00s~100.00s
Unit
0.01s
Default
0.50s
FA.25
Action start voltage at instantaneous power failure
60.0%~100.0%(Standard DC bus voltage)
0.10% 80.00%
FA.26
Load loss protection
0: Disable
1: Enable
FA.27
Load loss detection level
0.0~100.0
%
1
0.10%
0
10.00%
Modifi
-cation level
☆
☆
☆
☆
FA.28
Load loss detection time
0.0~60.0s
FA.29
Decimal place of frequency at fault
1: 1 decimal place
2: 2 decimal place
Units: Frequency decimal place of the last fault
Tens: Fequency decimal place of the fault before last
Hundreds: Fequency decimal place of the second fault before last
0.1s
1
1.0s
222
FB Group: Swing frequency, length control and counter control
FB.00
Swing frequency setting mode
0: Relative to center frequency
1: Relative to Maximum frequency
FB.01
Swing frequency range
0.0%~100.0%
1
0.10%
0
0.00%
☆
●
☆
☆
FB.02
Skip frequency range
0.0%~50.0% 0.10% 0.00% ☆
‐ 102 ‐
VM1000 Series
Function code
Description Set range
FB.03
Swing frequency cycle
0.1s~3000.0s
FB.04
Triangle wave rising time coefficient of swing frequency
0.1%~100.0%
FB.05 Length setting
FB.06 Actual length
0m~65535m
0m~65535m
FB.07
Pulse per meter, unit: 0.1
0.1~6553.5
Unit
0.1s
0.10%
1m
1m
0.1
FB.08 Counter setting 1~65535
FB.09
Designated counter value
1~65535
1
1
FC Group: RS485 Communication Parameters
FC.00 Local address
1~247, 0 refers to the broadcast address
1
FC.01 Baud rate selection
0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
8: 57600BPS
9: 115200BPS
1
Default
10.0s
50.00%
1000m
0m
100
1000
1000
1
5
Modifi
-cation level
☆
☆
☆
☆
☆
☆
☆
☆
☆
‐ 103 ‐
VM1000 Series
Function code
Description Set range
FC.02 Data bit check
0: No check (8, N, 2)
1: Even parity check (8, E, 1)
2: Odd parity check (8, O, 1)
3: No check (8, N, 1)
FC.03
Communication response delay time
0ms~20ms
Unit
1
1ms
Default
0
2
FC.04
Communication timeout fault time
0.0 (invalid), 0.1~60.0s
FC.05
Current resolution of communication
0: 0.01A
1: 0.1A
0.1s
1
0
0
FD Group:Multi-step Speed and Simple PLC Parameters
FD.00 Multi-step speed 0
-100.0%~100.0% (100.0% refers to maximum frequency F0.10)
0.10% 0.00%
FD.01 Multi-step speed 1 -100.0%~100.0%
FD.02 Multi-step speed 2 -100.0%~100.0%
0.10% 0.00%
0.10% 0.00%
Modifi
-cation level
☆
☆
☆
☆
☆
☆
☆
FD.03 Multi-step speed 3 -100.0%~100.0%
FD.04 Multi-step speed 4 -100.0%~100.0%
FD.05 Multi-step speed 5 -100.0%~100.0%
FD.06 Multi-step speed 6 -100.0%~100.0%
FD.07 Multi-step speed 7 -100.0%~100.0%
FD.08 Multi-step speed 8 -100.0%~100.0%
FD.09 Multi-step speed 9 -100.0%~100.0%
FD.10 Multi-step speed 10 -100.0%~100.0%
0.10%
0.10%
0.10%
0.10%
0.10%
0.00%
0.00%
0.00%
0.10% 0.00%
0.10% 0.00%
0.10% 0.00%
0.00%
0.00%
☆
☆
☆
☆
☆
☆
☆
☆
‐ 104 ‐
VM1000 Series
Function code
Description Set range
FD.11 Multi-step speed 11 -100.0%~100.0%
FD.12 Multi-step speed 12 -100.0%~100.0%
FD.13 Multi-step speed 13 -100.0%~100.0%
FD.14 Multi-step speed 14 -100.0%~100.0%
FD.15 Multi-step speed 15 -100.0%~100.0%
Unit
0.10%
Default
0.00%
0.10% 0.00%
0.10% 0.00%
0.10% 0.00%
0.10% 0.00%
FD.16
Simple PLC operation method
0:Stop after sigle operation
1:Keep the f inal value af ter single operation
2:Operation in cycles
FD.17
Memory option of simple PLC
Units:
0: Non-retentive at power-off
1: Retentive at power-off
T ens:
0: Non-retentive at stop
1: Retentive at stop
1
11
FD.18
0th step running time
0.0s(h)~6553.5s(h) 0.1s(h)
0
0
0.0s(h)
FD.19
Acceleration time of 0th step
0~3
FD.20
1st step running time
0.0s(h)~6553.5s(h)
FD.21
Acceleration time of 1st step
0~3
FD.22
2nd step running time
0.0s(h)~6553.5s(h)
1
0.1s(h)
1
0.1s(h)
0
0.0s(h)
0
0.0s(h)
Modifi
-cation level
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
‐ 105 ‐
Function code
Description
FD.23
Acceleration time of 2nd step
0~3
Set range
FD.24
3rd step running time
0.0s(h)~6553.5s(h)
FD.25
Acceleration time of 3rd step
0~3
FD.26
4th step running time
0.0s(h)~6553.5s(h)
FD.27
Acceleration time of 4th step
0~3
FD.28
5th step running time
0.0s(h)~6553.5s(h)
FD.29
Acceleration time of 5th step
0~3
FD.30
6th step running time
0.0s(h)~6553.5s(h)
FD.31
Acceleration time of 6th step
0~3
FD.32
7th step running time
0.0s(h)~6553.5s(h)
FD.33
Acceleration time of 7th step
0~3
FD.34
8th step running time
0.0s(h)~6553.5s(h)
FD.35
Acceleration time of 8th step
0~3
‐ 106 ‐
VM1000 Series
Unit Default
Modifi
-cation level
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
Function code
Description
FD.36
9th step running time
Set range
0.0s(h)~6553.5s(h)
FD.37
Acceleration time of 9th step
0~3
FD.38
10th step running time
0.0s(h)~6553.5s(h)
FD.39
Acceleration time of 10th step
0~3
FD.40
11th step running time
0.0s(h)~6553.5s(h)
FD.41
Acceleration time of 11th step
0~3
FD.42
12th step running time
0.0s(h)~6553.5s(h)
FD.43
Acceleration time of 12th step
0~3
FD.44
13th step running time
0.0s(h)~6553.5s(h)
FD.45
Acceleration time of 13th step
0~3
FD.46
14th step running time
0.0s(h)~6553.5s(h)
FD.47
Acceleration time of 14th step
0~3
FD.48
15th step running time
0.0s(h)~6553.5s(h)
‐ 107 ‐
VM1000 Series
Unit Default
Modifi
-cation level
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
1 0 ☆
0.1s(h) 0.0s(h) ☆
VM1000 Series
Function code
Description
FD.49
Acceleration time of 15th step
0~3
Set range
FD.50
PLC operation time unit
0: s
1: h
2: min
FD.51
Multi-step speed 0 frequency reference
0: Function parameter FD.00 setting
1: AI1
2: AI2
3: Reserved
4: Pulse Input
5: PID
6: Digital setting of F0.08 Preset
Frequency(Adjustable Up/Down keys)
Unit
1
1
1
FE.00 User Password
FE Group: Parameter Management
0~65535 1
FE.01
Fault Record times display
0~15 1
Default
0
0
0
0
5
Modifi
-cation level
☆
☆
☆
☆
☆
E0.00
Code of the last fault
FF Group: Reserved ◎
E0 Group: Record of the last fault
0: No faults
1: Reserved
2: Overcurrent at acceleration(Err02)
3: Overcurrent at deceleration(Err03)
4: Overcurrent at constant speed(Err04)
- - ●
‐ 108 ‐
VM1000 Series
Function code
Description
E0.00
Code of the last fault
Set range Unit Default
Modifi
-cation level
5: Overvoltage at acceleration(Err05)
6: Overvoltage at deceleration(Err06)
7: Overvoltage at constant speed(Err07)
8: Buffer resistance overload(Err08)
9: Undervoltage fault(Err09)
10: Ac drive overload(Err10)
11: Motor overload(Err11)
12: Phase loss at input(Err12)
13: Phase loss at output(Err13)
14: Module overheat(Err14)
15: External fault(Err15)
16: Abnormal communication(Err16)
17: Contactor abnormal(Err17)
18: Current detection fault(Err18)
19: Motor tuning fault(Err19)
21: Abnormal para reading and writing(Err21)
22: Drive hardware fault(Err22)
23: Motor short circuit to ground(Err23)
24: Reserved(Err24)
25: Reserved(Err25)
26: Running time reached(Err26)
27: User-defined fault 1(Err27)
28: User-define fault 2(Err28)
- - ●
‐ 109 ‐
VM1000 Series
Function code
Description Set range Unit Default
Modifi
-cation level
E0.01
Running frequency at the last fault
-
E0.02
Current at the last fault
-
E0.03
DC bus voltage at the last fault
-
E0.04
Digital input status at the last fault
-
E0.05
Digital output status at the last fault
E0.06
Drive Status at the last fault
-
E0.07
Timing result at the power on)
E0.08
Timing result at the
Starting)
E0.09 Reserved -
29: Power-on time reached(Err29)
30: Load loss(Err30)
31: PID feedback loss at running time(Err31)
40: Time-out fault of rapid current limit(Err40)
41: Reserved
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
●
●
●
●
●
●
●
●
●
‐ 110 ‐
VM1000 Series
Function code
Description
E0.10 Reserved
Set range Unit Default
- -
Modifi
-cation level
● -
E1 ~ E4 Group: Record of the four faults before the last
‐ 111 ‐
VM1000 Series
Chapter 6 VM1000 Communication Application
VM1000 series provides RS485 communication interface and supports MODBUS communication protocol. Through computer or PLC, users can achieve centralized control, set VFD operation command, modify or read function code parameters, read the working status and fault information etc.
6.1 The Content of Protocol
The serial communication protocol defines the information content and use format of transmitting the serial communication, which includes: host “polling” (or broadcasting) format; The encoding method of host includes: function code of requiring action, data transmission, and error checking etc.If error occurred in the slave drive while receiving the information or can not complete the requested action form the host, it will organize a fault message as a response to the host.
6.2 Application
VFD is connectted to the "Single-host and multi-slave" PC / PLC control network with RS485.
6.3 Bus Structure
(1) Interface: RS485 hardware interface
(2) Transmission mode: asynchronous serial, half-duplex transmission mode. At the same moment, there is only one can transmit data while the other receive data in master and slave. During the asynchronous serial communication, data is sent frame by frame based on the packets.
(3) Topology: In single-host and multi-slave system, slave address range from 1 to
31, 0 is broadcast communication address. Network slave address must be unique.
‐ 112 ‐
VM1000 Series
6.4 Protocol Instruction
VM1000 series inverter communication protocol is an asynchronous serial master-slave ModBus communication protocol. Only one device (the host) can build a protocol (referred to as "Inquire / Command") in the network. Other devices
(slaves) can only respond to the host by providing the data "inquiry / command", or make the appropriate action based on the host "inquiry / command." The host refers to the personal computer (PC), industrial control equipment or programmable logic controller (PLC) The slave means VM1000. Master can not only communicate with a slave individually, but also broadcast information to the entire lower auxiliary. For the master that access "inquiry / command" solely, slaves will feedback a message
(called a response). For broadcast information provided by master, slave needs not feedback and response to the host.
6.5 Communication Frame Description
In RTU mode, information is sent with 3.5 character of interval of times at least. In diverse character time of network baud rate, it is much easier to realize it. The first transmission domain is the device address. The transmission characters that can be used is hexadecimal 0 ...
9, A ... F. Network devices monitor the network- bus constantly, including the pause at time interval. When the first field (the address field) is received, each device decodes it and judges whether it is sent to its own. After the last transmitted character, a times pause of 3.5 character
( at least ) marks the end of the message. After this pause, a new message can begin.
The entire message frame must be used as a continuous flow of output. If it exceed times pause of 1.5 characters, the receiving device will keep renewing the incomplete message and assumes that the next byte is the address field of a new message. Likewise, if a new message start within 3.5 character and continue in the previous information, the receiving device will consider it as a continuation of the previous message. Because the final CRC field value is not correct, this will cause an error.
RTU format is as follows :
START Time of 3.5 character
CMD
03 : Read auxiliary parameters ; 06 : Write auxiliary
‐ 113 ‐
VM1000 Series parameters
DATA ( N-1 )
DATA ( N-2 )
……
DATA0
CRCCHK High Bit
CRCCHK Low Bit
END
Data content :
Para address of function code , parameter bit of function code , parameter value of function code
Detection value : CRC
Time of 3.5 character
Table 6-1 RTU Format
Reading the Data from Auxiliary Register:
Example 1: The slave address is the start address of 01VFD, F002 continuously read two consecutive values.
Command Information of the Host:
ADR 01H
CMD 03H
High bit of starting address
Low bit of starting address
F0H
02H
High bit of register number
Low bit of register number
CRCCHK low bit
CRCCHK high bit
00H
02H
The CPCCHK is still need to be calculated
Table 6-2 The Host Reading Command Frame Format
‐ 114 ‐
VM1000 Series
Responding Information of Auxiliary:
ADR 01H
CMD 03H
Byte number
F002H high bit
F002H low bit
04H
00H
00H
F003H high bit
F003H high bit
CRCCHK low bit
CRCCHK high bit
00H
01H
The CPCCHK is still need to be calculated
Table 6-3 The Auxiliary Reading the Frame Format of Responding Information
Register Data that is Written in the Auxiliary :
Example 2: Write the 5000(1388H) in the auxiliary address from F00AH of 02H
VFD.
Command information of host :
ADR 02H
CMD 06H
High bit of data address
Low bit of data address
F0H
0AH
High bit of data content
Low bit of data content
CRCCHK low bit
CRCCHK high bit
13H
88H
The CPCCHK is still need to be calculated
Table 6-4 The Host Written into Command Frame Format
‐ 115 ‐
VM1000 Series
Responding Information of Auxiliary:
ADR 02H
CMD 06H
High bit of data address
Low bit of data address
High bit of data content
Low bit of data content
CRCCHK LOW BIT
F0H
0AH
13H
88H
The CPCCHK is still need to be calculated
Table 6-5 The Auxiliary Written into Responding Information Frame Format
Checking Mode -CRC:
When using RTU frame format, the message contains error detection domain that based on CRC. CRC field checks the contents of the whole message. CRC field is two bytes and includes a 16-bit binary value. After calculated by the transmission equipment, it is added to the message. The receiving device recalculates the CRC that received message, and compares it with the value that received in the CRC field.
If the two CRC values are not equal, it means that the transmission is not correct.
CRC is first stored in 0xFFFF, then invoke a continuous procedure to process the message with 8-bit byte and the current value of register. Only each character 8Bit data is valid for CRC, while start/ stop bits and the parity check bits are invalid. In
CRC, each 8-bit character is different from the register contents or (XOR). The result moves to the least significant bit and most significant bit is filled with 0. If
LSB is 1, the register is independently different from preset value. If LSB is 0, it will not implement. The whole procedure is repeated eight times. After completing the last bit (the 8th bit), the next 8-bit byte is different from the current value of register again. The final value of the register is the CRC value of all bytes in the message after the execution. When CRC is added to the message, the low byte will be added first and followed by the high byte.
‐ 116 ‐
VM1000 Series
When CRC is added to the message, the low byte will be added first and followed by the high byte.The simple function of CRC is as follows : unsigned int crc_chk_value(unsigned char *data_value,unsigned char length)
{ unsigned int crc_value = 0xFFFF; int i; while(length--)
{ crc_value ^= *data_value++; for(i=0;i<8;i++)
{ if(crc_value&0x0001)
{ crc_value = (crc_ value>>1) ^ 0xa001;
} else
{ crc_value = crc_ value >> 1;
}
}
} return(crc_value);
}
Address definition of communication parameters: this part is the content of the communication, which is used to control the VFD operation, VFD status and related parameters setting (some function code can not be changed, only for factory use).
The rule of function code’s parameters address: high byte (F0 ~ FF), the low byte
(00 ~ FF); Like F3.12, the address is expressed as F30C.
Note: FF Group: Neither it can be readable parameters, nor modified parameters;
Therefore, some parameters can not be modified when VFD is at running status; No matter in what status, some parameters can not be changed; When changing the function code parameters, it still need to pay attention to the parameter range, unit and related instructions.
‐ 117 ‐
VM1000 Series
In addition, the life of the EEPROM is shortening since the EEPROM is stored frequently. Therefore, you have only to change the value of RAM under communication mode. It is no need to store some function code. (it can be achieved as long as the high bit F of the function code address is changed into 0.The address can only represent the writing RAM, can not act as the reading action. When reading, it is invalid address).
6.6 Register Address
stop/running parameters:
Parameter Address
1000
Parameter Description communication setting value(decimal system)
1008
1009
DI input symbol
DO output symbol
100C reserved
100D count value input
‐ 118 ‐
VM1000 Series
1013
1014
PLUSE input frequency , Units 0.01KHz feedback speed, Units 0.1Hz
1015
1016
1017
The rest of running time
AI1 voltage before correcting
AI2voltage before correcting
1018 reserved
101C
101D
PLUSE input frequency , Units 1Hz communication setting value
101F
1020 main frequency x display auxiliary frequency display
Table 6-6 Stop/Running Parameter Address
Note: The communication seting value is the percentage of relative value, 10000 corresponds to 100.00%, - 10000 corresponds to -100.00%. For the data on the frequency dimension, this percentage is a relative maximum frequency (F0-10) percentage; torque data dimension, which is the percentage of F2-10 (Digital torque limit setting)
‐ 119 ‐
VM1000 Series
Control Command Input into VFD(writing only) :
The address of command word
2000
Command function
0001 : Forward rotation
0002 : Reversed rotation
0003 : Forward JOG
0004 : Reversed JOG
0005 : Stop by deceleration
0006 : Stop automatically
0007 : fault rest
Table 6-7 Control Command Function
Reading VM1000 Status (reading only) :
The address of command word
3000
Command function
0001 : forward rotation
0002 : reversed rotation
0003 : stop
Table 6-8 Information Sheet of Reading VM1000 Status
Parameter Lock Password Checking:
If it is 8888H after returning , namely it means the password checking has passed
Code address The content of input code
1F00 *****
Table 6-9 Password Checking Address and Format
‐ 120 ‐
VM1000 Series
Terminal Control of Digital Input:
The address of command word
2001
The content of command
BIT0~BIT1 : reserved
BIT2 : RELAY1 output control
BIT3 : RELAY2 output control
BIT4 : FMR output control
BIT5 : VDO
BIT6~BIT9 : reserved
Table 6-10 Digital Output Control
A01 Analog Output Control ( writing only ) :
Command address Command content
2002 0 100 %
Table 6-11 A01 Analog Output Control
A02 Analog output Control ( writing only ) :
Command address Command content
2003 0 100 %
Table 6-12 A02 Analog output Control
Pulse Output Control ( writing only ) : command address command content
2004 0 100 %
Table 6-13 Pulse Output Control
‐ 121 ‐
VM1000 Series
Fault Description of VM1000 :
Fault address
8000
Fault information
0000 : no faults
0001 : reserved
0002 : overcurrent at acceleration
0003 : overcurrent at deceleration
0004 : overcurren at constant speed
0005 : overvoltage at acceleration
0006 : overvoltage at deceleration
0007 : overvoltage at constant speed
0008 : buffer resistance overload
0009 : undervoltage fault
000A : ac drive overload
000B : motor overload
000C : phase loss at input
000D : phase loss at output
000E : module overheat
000F : external fault
0010 : abnormal communication
0011 : contactor abnormal
0012 : current detection fault
0013 : motor tuning fault
0015 : abnormal para reading and writing
0016 : reserved
0017 : Short circuit to ground
001A : running time reached
001B: user-defined fault 1
001C: user-define fault 2
001D: power-on time reached
001E : reserved
‐ 122 ‐
VM1000 Series
001F : PID feedback loss at running time
0028 : time-out fault of rapid current limit
0029 : reserved
Table 6-14 VM1000 Fault Information
Data Description of Communication Fault(Fault Code) : communication fault address description of fault function
8001
0000 : no fault
0001 : password error
0002 : command code error
0003 : CRC checking error
0004 : invalid address
0005 : invalid parameters
0006 : invalid parameters modification
0007 : 0008 : EEPROM under operation
Table 6-15 Datasheet of Communication Faults
Instruction of F Group Communication Parameters :
FC-00 address of AC drive setting range factory value
00~31
1
When the local address is set as 0, namely broadcast address,realize the broadcast function of the upper machine ( except broadcast address). This is the basis for realizing point to point communication between upper machine and VFD.
FC-01
Baud rate
Setting range
Factory value 5
0 300BPS
1 600BPS
‐ 123 ‐
VM1000 Series
2 1200BPS
3 2400BPS
4 4800BPS
5 9600BPS
6 19200BPS
7 38400BPS
This parameter is used to set the data transfer rate between the host computer and the drive. Note: the baud rate of host computer and the drive must be the same.
Otherwise, communication can not be conducted.The bigger the Baud, the faster the communication.
FC-02
Baud rate
Setting range
Factory value
0
1
2
0 no checking :data format <8,N,2> even checking: data format <8,E,1> odd check: data format <8,O,1>
3 no check: data format<8-N-1>
The baud rate of host computer and the drive must be the same. Otherwise, communication can not be conducted.
Response delay Factory value 10ms
FC-03
Setting range 0~20ms
Response delay: it refers to the time interval that AC drive sent the data to host after receiving data.If the response delay is less than the system processing time, the response delay will be subject to the system processing time.If the response delay time longer than the system processing, it needs wait until the response delay time send the data to host machine after data has been processed.
‐ 124 ‐
VM1000 Series
communication overtime Factory value 0.0 s
FC-04
Setting range 0.0 s ( invalid ), 0.1~60.0s
When the function code is set to 0.0 s, the communication timeout parameter is invalid.
When the function code is set to a valid value, if the time interval between the communication and the next communication exceeds the communication time-out, the system will alarm communication error (Err16). Typically, it is set as invalid.
In the continuous communication system, you can monitor the communication status if the second parameter is set.
Communication Read Current
Resolution
Factory value 0
FC-05
Setting range
0 0.01A
1 0.1A
It is used to determine the output unit of current value when communication reads output current.
‐ 125 ‐
VM1000 Series
Chapter 7 Faults and Solutions
7.1 Fault Code Table
In VM1000, there are a lot of warning information and protection functions. Once the abnormal failure occurred, the protection function is activated and the VFD output is stopped.
The fault code is displayed on AC drive display panel. Before seeking for service, users can conduct a detection on your own , analyze problems and find out the solutions according to this chapter. If it belongs to the reasons mentioned in the dashed box, please seek services, or contact the agent or SAJ-electric.
Overcurrent at acceleration
Whether the output circuit is grounded or short circuited
No
Whether the motor parameter calculation is performed
Yes
Whether the acceleration time is too short
No
Whether the manual torque boost or V/F curve is appropriate
Yes
Whether the voltage is too low
No
Yes
No
Yes
No
Yes
Eliminate external faults
Perform motor parameter calculation
Increase the acceleration time
Adjust the manual torque boost or V/F curve
Adjust the voltage to a normal range
Whether the startup operation is performed on the rotating motor.
No
Whether a sudden load is added during acceleration
No
Yes
Yes
Select rotational speed tracking restart or start the motor after it stops.
Cancel the sudden added load
The model selection of VFD is too small
Figure 7-1 Overcurrent at acceleration (Err02)
‐ 126 ‐
VM1000 Series
Overcurrent at deceleration
Whether the output circuit is grounded or short circuited.
No
Whether the motor parameter calculation is performed or not
Yes
Whether the deceleration time is too short
No
Whether the voltage is low
No
Whether a sudden load is added during deceleratio
No
Whether the braking unit and braking resistor are installed.
Yes
Seek for technical support
Yes
No
Yes
Yes
Yes
No
Eliminate external faults
Perform the motor parameter calculation
Increase the acceleration time
Adjust the voltage to a normal range
Cancel the sudden added load
Install the braking unit and braking resistor.
Figure 7-2 Overcurrent deceleration (Err03)
‐ 127 ‐
VM1000 Series
Figure 7-3 Overcurrent at constant speed (Err04)
Overvoltage at acceleration
Whether the input voltage is too high
No
Whether there exists a external force that drives the motor during acceleration
No
Whether the acceleration time is short
No
The braking unit and braking resistor are not installed
Yes
Yes
Yes
Yes
Adjust the voltage to normal range
Cancel the external force or install a braking resistor
Increase the acceleration time
Install the braking unit and braking resistor.
seek for technical support
Figure 7-4 Overvoltage at acceleration (Err05)
‐ 128 ‐
VM1000 Series
Figure 7-5 Overvoltage at deceleration (Err06)
Figure 7-6 Overvoltage at constant speed (Err07)
‐ 129 ‐
VM1000 Series
Figure 7-7 Control power supply fault (Err08)
Figure 7-8 Undervoltage (Err09)
‐ 130 ‐
VM1000 Series
Figure 7-9 AC drive overload / Motor overload (Err10/Err11)
Figure 7-10 Phase loss at input side (Err12)
‐ 131 ‐
VM1000 Series
Figure 7-11 Phase loss at output side (Err13)
Figure 7-12 Module overheat (Err14)
‐ 132 ‐
VM1000 Series
Figure 7-13 External cquipment fault (Err15)
Figure 7-14 Communication fault (Err16)
‐ 133 ‐
VM1000 Series
Figure 7-15 Current detection fault (Err18)
Figure 7-16 Motor tuning fault (Err19)
Figure 7-17 Data overflow (Err21)
‐ 134 ‐
VM1000 Series
Figure 7-18 Short-circuit to ground (Err23)
Figure 7-19 Accumulative running time reached (Err26)
Figure 7-20 User-defined fault 1 (Err26)
‐ 135 ‐
VM1000 Series
Figure 7-21 User-defined fault 2 (Err28)
Figure 7-22 Accumulative running time reached (Err29)
‐ 136 ‐
VM1000 Series
Figure 7-23 PID feedback lost during running (Err31)
Figure 7-24 Pulse-by-pulse current limit fault (Err31)
‐ 137 ‐
VM1000 Series
7.2 Troubleshooting and Solution
The following faults may occur when using VFD, please conduct the simple fault analysis by referring to the following method:
No. Fault Phenomenon Solutions
1
2
No display at power-on
Display HC at power on
Possible reasons
The input power of VFD is not connected.
The connection between
8-core wires on control board and the drive board is poor.
Internal components in the
VFD are damaged
The connection between
4-core wire between control board and the drive board is poor.
Other components in the
VFD are damaged
Check input power.
Pull and plug 8-core cable again.
Seek for manufacturers services.
Pull and plug the 4-core wire again
Seek for manufacturers services
3
Display Err23 alarm at power on
The motor or the output line is short-circuited to ground.
The AC drive is damaged.
Use tramegger to measure the insulation between the motor and output wire.
Seek for manufacturers services
4
AC drive display normally at power-on ; display
HC and stop immediately after running
Fan is damaged or stalled Replace the fan
5
Report ERR14 frequently(module overheat)
The setting of carrier frequency is too high.
Fan is damaged and the air duct is blocked.
The internal components of
Reduce the carrier frequency (F0.16).
Replace the fan, clean up the air duct.
Seek for manufacturers
‐ 138 ‐
VM1000 Series
No. Fault Phenomenon
6
7
8
9
Motor stop rotating after VFD operates
DI terminal is invalid
When it is closed-loop vector control, the motor speed can not be improved.
The VFD frequently reports the fault of overcurrent and overvoltage
Possible reasons Solutions
VFD is damaged (thermal coupling or other)
Motor damage or stalling.
Incorrect parameter setting
(primarily is motor parameters in F2 group )
Parameter setting error.
short-circuit sheet between OP and + 24V is loose.
Control board fault. services
Replace motor or clear mechanical failure.
Check and reset F2 parameters
Check and re-set the related parameters of F5 group .
Rewiring.
Manufacturers seek services.
Code disk is damaged or wrong connections.
The internal components of
VFD is damaged.
Motor parameter setting wrong.
The acceleration and deceleration time is inappropriate.
Load fluctuations.
Replace the code disk, reconfirmed wiring.
Seek for service.
Reset parameters of F2 group or conduct motor tuning.
Set the appropriate acceleration and deceleration time.
Seek for manufacturers services.
‐ 139 ‐
VM1000 Series
Appendix A -Selection of External Electrical Components
A.1 VM1000 External Electrical Connection Diagram
Table A-1 is the lists and instruction of various external electrical components.
Componen ts Name
Installation Instruction
Air switch
Contactor
Front-end of input circuit
The power is disconnected when the downstream equipment is overcurrent.
Between the open space and the input side of the
AC drive
In VFD power-on or power-off operation, it should be avoided operating ON/OFF frequently (less than twice per minute) or starting operations through direct contact.
AC input reactor
EMC input filter
Input side of AC drive
Input side of AC drive
Improving the power factor at input side;effectively eliminating high harmonics at the input side; preventing from damaging other equipment incurred by voltage waveform distortion ; eliminating the imbalance of input current caused by the imbalance of power phase.
Reducing the external conduction and radiation interference incurred by VFD; Reducing the the drive conductive interference from power supply side to VFD and improving anti-interference capability of the AC drive.
DC reactor
DC reactor is external option,which is connected between “+ “and
“P”(applicable for 30~110kw)
Improving the power factor at input side; improve the overall efficiency and thermal stability of AC drive. Effectively eliminate the influence caused by higher harmonic at input side and reduce the external conduction and radiation interference.
‐ 140 ‐
VM1000 Series
AC output reactor
Between the output side and the AC drive. To install close to the AC drive.
The output side of AC drive generally has more higher harmonics. When the distance between the motor and the drive is relative far, the line has a larger distributed capacitance. If harmonic resonance may occur in the loop,it will cause two influences: damage motor insulationand damage the motor if it last for a long time, it will damage the motor; generate a greater leakage current and cause frequent protection. Usually the distance between VFD and the motor is more than 100m. It is recommended to install output AC reactor.
Table A-1 VM1000 External Electrical Components
‐ 141 ‐
VM1000 Series
Figure A-1 VM1000 External Electrical Connection Diagram
‐ 142 ‐
VM1000 Series
A.2 Selection Guide of Braking Components
Table A-2 is the guide data. Users can select different resistance and power according to the actual situation, (but resistance must not be less than the value recommended in the table, while the power can be greater than the value recommended in the table.) The selection of braking resistor needs to be determined according to the the power of the motor in the actual application system. Also,this selection is related to the system inertia,the deceleration time, potential energy load. Users need to decide according to the real situation.The bigger the system inertia, the shorter the deceleration time. If the brake is more frequently,users need to select the higher power and smaller resistance.
The Selection of Resistance
When it is under braking, the braking resistor will consume almost all the regenerative energy of the motor .
According to the formula: U * U / R = Pb
Formula U ---- braking voltage of systematic stable brake
(Different systems adopt different brake voltage. For 380VAC,the systems typically adopt 700V)
Pb ---- braking power
Power Selection of Brake Resistor
Theoretically, the braking resistor power is consistent with braking power.
Considering it derate to 70%.
According to the formula: 0.7 * Pr = Pb * D
Pr ---- resistor power
D ---- braking frequency (regeneration process accounts for the proportion of total working process)
Elevator ----- 20% to 30%
‐ 143 ‐
VM1000 Series
Uncoil and Coil ----20% to 30%
Centrifuge ------- 50% to 60%
Accidental braking load 5%
Generally adopt 10%
Model NO.
Recommended
Power of Brake
Resistor
VM1000-4T011GB 800W
VM1000-4T015GB 1000W
VM1000-4T18R5G 1300W
VM1000-4T030G 2500W
VM1000-4T037G 4kW
VM1000-4T045G 4.5kW
VM1000-4T055G 5.5kW
VM1000-4T075G 7.5kW
VM1000-4T090G 4.5kW×2
VM1000-4T110G 5.5kW×2
Recommended
Resistance of Brake
Resistor
VM1000-4T022G 1500W
Brake
Unit
≥
≥
≥
≥
43
32
25
22
Ω
Ω
Ω
Ω standard built-in standard built-in standard built-in standard built-in
≥ 16 Ω external
≥ 12.6
Ω external
≥ 9.4
Ω external
≥ 9.4
Ω external
≥ 6.3
Ω external
≥ 9.4
Ω ×2 external
≥ 9.4
Ω ×2 external
Table A-2 Configuration Advice of Braking Components
Note : ×2 indicates two brake units with brake resistors are used in parallel , ×3 and other number can be concluded by analogy.
‐ 144 ‐
VM1000 Series
A.3 Selection of Air Switch,Contactor or Cable
Model NO.
Air Switch
( MCCB )
( A )
Recommended contactor ( A )
Main
Circuit
Wire at input side
Main
Circuit
Wire at output side
Control
Circuit
Wire mm2
VM1000-4T011GB 63
VM1000-4T015GB 63
40
40
4 4 1
6 6 1
VM1000-4T18R5GB 100
VM1000-4T022GB 100
63
63
6 6 1.5
10 10 1.5
VM1000-4T030G 125 100 16 10 1.5
VM1000-4T037G 160 100 16 16 1.5
VM1000-4T045G 200 125 25 25 1.5
VM1000-4T055G 200 125 35 25 1.5
VM1000-4T075G 250 160 50 35 1.5
VM1000-4T090G 250 160 70 35 1.5
VM1000-4T110G 350 350 120 120 1.5
Table A-3 Distribution Supply and Cable selection
‐ 145 ‐
VM1000 Series
Appendix B-Manual Revision Record
Date of Issue
( 1 )
Document Code
Item
Number
April 8th,2016 VM1000-C201602-4MB
Manual edition
Revision
Content
V1.0 version
Documentation
Note(1): The date of issue will be subject to the time of archiving electronic documents or lauch date.
‐ 146 ‐
VM1000 Series
Guangzhou Sanjing Electric CO., LTD.
TEL: 400-159-0088 www.saj-electric.com
ADD: SAJ Innovation Park, No.9, Lizhishan Road, Science City,
Guangzhou High-tech Zone, Guangdong, P.R.China
‐ 147 ‐