Burkert 8630 Operating Instructions Manual
Anuncio
Anuncio
Operating Instructions
Bedienungsanleitung
Instructions de Service
Type 8630
TOP Control Continuous
We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous resérve de modification techniques.
© 2001 Bürkert Werke GmbH & Co KG.
Operating Instructions 0507/11_EU-EN_00804575
C
ONTENTS
Overall Operating Instructions
TOP Control Continuous 8630
GENERAL NOTES
Symbols
..........................................................................................................................................................................................................................................................
10
Intended use
............................................................................................................................................................................................................................................
10
Safety notes
..............................................................................................................................................................................................................................................
10
Protection from damage by electrostatic charging
.........................................................................................................................
11
Scope of delivery
..............................................................................................................................................................................................................................
11
Warranty conditions
......................................................................................................................................................................................................................
11
Master code
..............................................................................................................................................................................................................................................
12
Transport, storage
............................................................................................................................................................................................................................
12
Disposal
.........................................................................................................................................................................................................................................................
12
SYSTEM DESCRIPTION
Valve types
.................................................................................................................................................................................................................................................
14
Characteristics of the valve types
......................................................................................................................................................................................
15
Construction of TOP Control Continuous
.....................................................................................................................................................
16
Illustrations (cover removed)
...................................................................................................................................................................................................
16
Design features
.....................................................................................................................................................................................................................................
17
Functional diagram as a positioner with single-acting actuator
............................................................................................................
18
Operation as a positioner
.....................................................................................................................................................................................................
19
Schematic representation of positioning control
..................................................................................................................................................
20
Characteristics of the positioner software
..................................................................................................................................................................
21
* Alternative chapters or functions depending on device configuration
8630 - 1
C
ONTENTS
*Operation as a process controller (option)
...............................................................................................................................................
22
Example of process control: TOP Control Continuous with sensor
...................................................................................................
22
Schematic representation of process control
.........................................................................................................................................................
23
Characteristics of the process controller software
.............................................................................................................................................
24
* Operation as a flow rate controller (option)
..........................................................................................................................................
25
Characteristics of the flow rate controller software
.........................................................................................................................................
25
Schematic representation of process control with flow rate controller
.......................................................................................
26
* Interfaces of the TOP Control Continuous in the multipole variant
..................................................................
27
* Interfaces of the TOP Control Continuous in the variants with
cable bushings
..................................................................................................................................................................................................................................
28
Technical data
........................................................................................................................................................................................................................................
29
Safety settings on failure of auxiliary electrical or pneumatic energy
.........................................................................................
29
Factory settings on the TOP Control Continuous
.............................................................................................................................................
30
Data of the TOP Control Continuous
.............................................................................................................................................................................
31
FIRST COMMISSIONING
Fluidic installation
.............................................................................................................................................................................................................................
34
*Electrical installation - multipole connector
............................................................................................................................................
35
*Electrical installation - connection terminals for cable bushings
............................................................................
36
Basic settings of the TOP Control Continuous
.....................................................................................................................................
37
Settings in the menu items
.......................................................................................................................................................................................................
38
Entering the position setpoint in the AUTOMATIC mode
..........................................................................................................................
38
Manual opening and closing of the valve actuator in the MANUAL mode
.............................................................................
39
INSTALLATION
Installation of the valve
............................................................................................................................................................................................................
42
Turning the TOP Control Continuous
..................................................................................................................................................................
42
Procedure
...................................................................................................................................................................................................................................................
42
Fluidic connection of the TOP Control Continuous
.......................................................................................................................
43
* Alternative chapters or functions depending on device configuration
2 - 8630
C
ONTENTS
*Electrical connection - multipole connectors
.......................................................................................................................................
44
Marking of the multipole plugs or sockets and the contacts
...................................................................................................................
44
Output signals for SPS (circular plug M 16)
.............................................................................................................................................................
45
Operating voltage (circular plug M 12)
............................................................................................................................................................................
45
Inductive proximity switches (circular socket M 8)
...........................................................................................................................................
45
Process value (circular plug M 8)
.......................................................................................................................................................................................
46
Process value with the option flow rate controller (2 circular plugs M 8)
Option: with temperature sensor input (3 circular plugs M 8)
..............................................................................................................
46
*Electrical connection - terminals for cable bushing
....................................................................................................................
47
Connection PCB of the TOP Control Continuous with screw terminals and jumpers
................................................
47
Terminal configuration with cable bushings
............................................................................................................................................................
47
Choice of binary outputs or process value input
...............................................................................................................................................
48
*Setting the inductive proximity switches (option)
...........................................................................................................................
50
Opening the housing of the TOP Control Continuous
.................................................................................................................................
50
Positioning the inductive proximity switches
..........................................................................................................................................................
50
OPERATION AND CONTROLLER FUNCTIONS
Operating and display elements
................................................................................................................................................................................
52
Operating levels
..................................................................................................................................................................................................................................
52
Commissioning and set-up as a positioner
...............................................................................................................................................
53
Procedure for specifying the basic settings
............................................................................................................................................................
53
Main menu for the settings on commissioning
....................................................................................................................................................
54
Description of the procedure
..................................................................................................................................................................................................
55
Configuring the supplementary functions
....................................................................................................................................................
59
Keys in the configuration level
..............................................................................................................................................................................................
59
Configuration menu
..........................................................................................................................................................................................................................
59
Supplementary functions
...........................................................................................................................................................................................................
62
Operating the process
...............................................................................................................................................................................................................
86
Changeover between operating modes
......................................................................................................................................................................
86
Operating mode AUTOMATIC
.......................................................................................................................................................................................
87
Meaning of the keys in the AUTOMATIC mode
..................................................................................................................................................
87
Display of the AUTOMATIC mode
.....................................................................................................................................................................................
87
Operating mode MANUAL
..................................................................................................................................................................................................
88
Meaning of the keys in the MANUAL mode
............................................................................................................................................................
88
Display of the MANUAL mode
..............................................................................................................................................................................................
88
* Alternative chapters or functions depending on device configuration
8630 - 3
C
ONTENTS
OPERATING THE PROCESS CONTROLLER
Factory settings on the process controller
...................................................................................................................................................
90
Setting up a process control system
....................................................................................................................................................................
90
Self-parametrization of the positioner - X.TUNE
...............................................................................................................................
91
Supplementary function P.CONTRL
....................................................................................................................................................................
91
Basic settings of the function P.CONTRL
...................................................................................................................................................................
92
P.Q’LIN - Starting the routine for linearization of the process curve
.....................................................................
105
Display during call-up and execution of the routine
..........................................................................................................................................
105
P.CO TUNE - Self-optimization of the process controller (process tune)
.....................................................
106
P.CO LEAK - Leakage characteristic for flow rate control
...................................................................................................
110
Operating the process
...............................................................................................................................................................................................................
112
Changeover between the operating modes
................................................................................................................................................................
112
Operating mode AUTOMATIC
.......................................................................................................................................................................................
113
Meaning of the keys
.........................................................................................................................................................................................................................
113
Displays
........................................................................................................................................................................................................................................................
113
Operating structure and procedures
..................................................................................................................................................................................
113
Manually changing the process setpoint
......................................................................................................................................................
114
Operating mode MANUAL
..................................................................................................................................................................................................
114
Meaning of the keys
.........................................................................................................................................................................................................................
114
Displays
........................................................................................................................................................................................................................................................
115
Operating structure and procedures
..................................................................................................................................................................................
115
PROFIBUS DP
General notes
.........................................................................................................................................................................................................................................
118
Technical data
.......................................................................................................................................................................................................................................
118
Safety settings on bus failure
.........................................................................................................................................................................................
118
Interfaces
.......................................................................................................................................................................................................................................................
119
Electrical connections
...............................................................................................................................................................................................................
119
Connection with one plugged bus connector
...........................................................................................................................................................
119
Connection with 2 plugged bus connectors
..............................................................................................................................................................
120
Operating voltage (circular plug M12)
.............................................................................................................................................................................
120
Bus connection (circular socket M12)
............................................................................................................................................................................
120
4 - 8630
C
ONTENTS
Inductive proximity switches (circular socket M8)
.............................................................................................................................................
121
Process value (circular plug M8)
.........................................................................................................................................................................................
121
Termination connection for PROFIBUS systems
................................................................................................................................................
122
Settings on the TOP Control Continuous
.....................................................................................................................................................
123
Explanation of the menu items
..............................................................................................................................................................................................
124
Functional deviations from the standard version
..............................................................................................................................
124
Configuration in the Profibus DP master
......................................................................................................................................................
125
Configuration of the process values
.................................................................................................................................................................................
125
Bus status display
...........................................................................................................................................................................................................................
127
Example 1 with COM-Profibus V3.3
....................................................................................................................................................................
128
Example for a positioner
...............................................................................................................................................................................................................
128
Example 2 with COM-Profibus V3.3
....................................................................................................................................................................
131
Example for a process controller
.........................................................................................................................................................................................
131
DEVICE NET
General notes
.........................................................................................................................................................................................................................................
134
Explanation of terms
....................................................................................................................................................................................................................
134
Technical data
.......................................................................................................................................................................................................................................
135
Safety settings on bus failure
.........................................................................................................................................................................................
135
Interfaces
.......................................................................................................................................................................................................................................................
136
Electrical connection
...................................................................................................................................................................................................................
136
Operating voltage (4-pole M12 circular plug)
...........................................................................................................................................................
137
Bus connection (4-pole M12 circular plug)
.................................................................................................................................................................
137
Inductive proximity switches (4-pole M8 circular socket)
...........................................................................................................................
137
Process value (circular plug M8)
.........................................................................................................................................................................................
137
Termination connection for DeviceNet systems
...................................................................................................................................................
138
Net topology of a DeviceNet system
...............................................................................................................................................................................
138
Settings on the TOP Control Continuous
.....................................................................................................................................................
139
Explanation of the menu items in the program run-off schematic
......................................................................................................
139
Settings in the main menu
.........................................................................................................................................................................................................
140
Configuring the process data
.........................................................................................................................................................................................
141
Static input assemblies
.................................................................................................................................................................................................................
141
Static output assemblies
.............................................................................................................................................................................................................
143
8630 - 5
C
ONTENTS
Bus status display
...........................................................................................................................................................................................................................
144
Configuration example 1
.......................................................................................................................................................................................................
145
Installation of the EDS file
.........................................................................................................................................................................................................
145
Address allocation
..............................................................................................................................................................................................................................
145
Offline parametrization of the device
...............................................................................................................................................................................
146
Online parametrization of the device
...............................................................................................................................................................................
147
Configuration example 2
.......................................................................................................................................................................................................
148
Setting up the process map (mapping)
..........................................................................................................................................................................
149
MAINTENANCE AND ERROR CORRECTION ON THE POSITIONER
Maintenance
............................................................................................................................................................................................................................................
152
Error messages and malfunctions
..........................................................................................................................................................................
152
Error messages on the LC display
.....................................................................................................................................................................................
152
Other malfunctions
.............................................................................................................................................................................................................................
152
MAINTENANCE AND ERROR CORRETION ON THE
PROCESS CONTROLLER
Maintenance
............................................................................................................................................................................................................................................
154
Error messages and malfunctions
..........................................................................................................................................................................
154
Error messages on the LC display
.....................................................................................................................................................................................
154
Other malfunctions
.............................................................................................................................................................................................................................
156
Appendix
6 - 8630
C
ONTENTS
GENERAL RULES
Selection criteria for continuous valves
..........................................................................................................................................................
158
Characteristics of PID controllers
.............................................................................................................................................................................
160
P component
............................................................................................................................................................................................................................................
160
I component
..............................................................................................................................................................................................................................................
161
D component
............................................................................................................................................................................................................................................
162
Superimposing the P, I and D components
...............................................................................................................................................................
163
Function of a real PID controller
...........................................................................................................................................................................................
164
Rules for setting PID controllers
................................................................................................................................................................................
165
Setting rules of Ziegler and Nichols (oscillation method)
............................................................................................................................
165
Setting rules of Chien, Hrones and Reswick (controller output step method)
........................................................................
166
OPERATING STRUCTURE
Operating structure of the TOP Control Continuous
.....................................................................................................................
170
TABLE FOR POSITIONER
Table for noting your settings on the positioner
..................................................................................................................................
178
TABLE FOR PROCESS CONTROLLER
Tables for noting your settings on the process controller
.....................................................................................................
180
MASTER CODE
Code number
..........................................................................................................................................................................................................................................
182
8630 - 7
C
ONTENTS
8 - 8630
G
ENERAL
N
OTES
GENERAL NOTES
Symbols
..............................................................................................................................................................................................................................................................
10
Intended use
................................................................................................................................................................................................................................................
10
Safety notes
..................................................................................................................................................................................................................................................
10
Protection from damage by electrostatic charging
.............................................................................................................................
11
Scope of delivery
..................................................................................................................................................................................................................................
11
Warranty conditions
..........................................................................................................................................................................................................................
11
Master code
..................................................................................................................................................................................................................................................
12
Transport, storage
................................................................................................................................................................................................................................
12
Disposal
.............................................................................................................................................................................................................................................................
12
8630 - 9
G
ENERAL
N
OTES
Symbols
The following symbols are used in these operating instructions: marks a work step that you must carry out.
ATTENTION!
marks notes on whose non-observance your health or the functioning of the device will be endangered.
NOTE marks important additional information, tips and recommendations.
Intended use
In order for the device to function perfectly and have a long service life, you must observe the information given in these operating instructions and comply with the operating conditions and the permissible data for the TOP Control Continuous, in addition to the information for the respective pneumatically actuated valve, which is specified in the „Technical Data“ chapter of these instructions and in the valve instructions.
Please note that the Top control Continuous may not be used out-of-doors.
In view of the large number of possible applications and categories of use, you should check whether the
Top control Continuous is suitable for your specific application, and carry out tests where necessary.
Safety notes
• Keep to standard engineering rules in planning the use of and operating the device!
• Installation and maintenance work are only allowed by specialist personnel using suitable tools!
• Observe the current regulations on accident prevention and safety during operation and maintenance of the device!
• Switch off the supply voltage in all cases before intervening in the system!
• Note that in systems under pressure, piping and valves may not be loosened!
• Take suitable precautions to prevent inadvertent operation or damage by unauthorized action!
• Make sure that after an interruption to the electrical or pneumatic supply, the process starts up again in a well-defined, controlled manner!
• On non-observance of these notes and unauthorized interference with the device, we will refuse all liability and the warranty on device and accessories will become void!
10 - 8630
G
ENERAL
N
OTES
Protection from damage by electrostatic charging
ATTENTION
EXERCISE CAUTION ON HANDLING!
ELECTROSTATICALLY SENSITITVE
COMPONENTS/MODULES
This device contains electronic components that are sensitive to electrostatic discharge (ESD). Contact to electrostatically charged persons or objects will endanger these components. In the worst case, they will be immediately destroyed or will fail after commissioning.
Observe the requirements of EN 100 015 - 1 in order to minimize the possibility of, or avoid, damage from instantaneous electrostatic discharge. Also take care not to touch components that are under supply voltage.
Scope of delivery
Immediately after receipt of a shipment, make sure that the contents are undamaged and match the scope of delivery stated on the packing slip. In general this consists of:
• Pneumatically actuated valve of type 2652, 2655, 2672, 2700, 2712, 2730, 2731 or 2731K with attached
TOP Control Continuous,
• Operating Instructions for the TOP Control Continuous and for the valve with pneumatic actuation.
If there are discrepancies, please contact immediately our customer service:
Bürkert Fluid Control Systems
Chr.-Bürkert-Str. 13-17
Service Department
D-76453 Ingelfingen
Tel.: (07940) 10-111
Fax: (07940) 10-448
E-Mail: [email protected]
NOTE Suitable cable plugs for the multipole connection are available as accessoires.
Warranty conditions
This document contains no warranty promises. We refer in this connection to our General Conditions of
Sale and Business. The condition for the warranty is use of the unit for the intended purpose under the specified application conditions.
ATTENTION!
The warranty covers only faultless condition of the TOP Control Continuous and the attached valve with pneumatic actuation. No liability will be accepted for consequential damage of any kind that may arise from failure or malfunctioning of the device.
8630 - 11
G
ENERAL
N
OTES
Master Code
Operation of this device can be locked by means of a freely selectable user code. Independent of this, there exists an unchangeable master code with which you can execute all operative actions on the device. This 4-digit code is to found on the last page of these operating instructions.
If required, cut out this code and keep it separate from these operating instructions.
Transport, storage
ATTENTION!
Transport and store the appliance in its original packing only.
Disposal
ATTENTION!
When disponsing of the appliance, observe the national standards for refuse disposal.
12 - 8630
S
YSTEM
D
ESCRIPTION
SYSTEM DESCRIPTION
Valve types
................................................................................................................................................................................................................................................
14
Characteristics of the valve types
..........................................................................................................................................................................
15
Construction of TOP Control Continuous
....................................................................................................................................................
16
Illustrations (cover removed)
........................................................................................................................................................................................
16
Design features
..............................................................................................................................................................................................................................
17
Functional diagram as a positioner with single-acting actuator
.......................................................................................
18
Operation as a positioner
....................................................................................................................................................................................................
19
Schematic representation of positioning control
.................................................................................................................................
20
Characteristics of the positioner software
...................................................................................................................................................
21
* Operation as a process controller (option)
..........................................................................................................................................
22
Example of process control: TOP Control Continuous with sensor
............................................................................
22
Schematic representation of process control
..........................................................................................................................................
23
Characteristics of the process controller software
............................................................................................................................
24
* Operation as a flow rate controller (option)
.........................................................................................................................................
25
Characteristics of the flow rate controller software
..........................................................................................................................
25
Schematic representation of process control with flow rate controller
...................................................................
26
* Interfaces of the TOP Control Continuous in the multipole variant
.................................................................
27
* Interfaces of the TOP Control Continuous in the variants with cable bushings
...........................
28
Technical data
.......................................................................................................................................................................................................................................
29
Safety settings on failure of auxiliary electrical or pneumatic energy
......................................................................
29
Factory settings on the TOP Control Continuous
...............................................................................................................................
30
Data of the TOP Control Continuous
..................................................................................................................................................................
31
* Alternative chapters or functions depending on device configuration
8630 - 13
S
YSTEM
D
ESCRIPTION
By the combination of the TOP Control with pneumatically actuated process valves, the functionality of the Bürkert process valve series is extended. These valves, in connection with the TOP Control, may also be employed in those control applications requiring continuous behaviour of the actuator.
Valve types
The figure below gives an overview of the possible combinations of TOP Control and various pneumatically actuated valves. For each type, various actuator sizes and valve sizes are available (not shown). More detailled information is to be found on the respective data sheets. The product range is being extended continually.
TOP Control
Continuous
Type 8630 with flat-seat valve
Type 2712
(here with flange connection)
TOP Control
Continuous
Type 8630 with Y-valve Type 2700 with butterfly valve
Type 2672 with ball valve
Type 2655 with diaphragm valve
Type 2730
Various process valves from the Bürkert range can be combined with the TOP Control to suit different applications. Y-, diaphragm or ball valves with control cones are suitable.
14 - 8630
S
YSTEM
D
ESCRIPTION
Pneumatically driven piston and rotary actuators may be used to operate them. Both single-acting and doubleacting actuators are offered in combination with TOP Control Continuous.
With single-acting actuators, only one chamber in the actuator is pressurized and vented. The pressure produced works against a spring. The piston moves until an equilibrium is set up between the pressure and the spring force.
With double-acting actuators, the chambers on both sides of the piston are pressurized. When the one chamber is pressurized, the other is vented and vice versa. No spring is installed in this actuator version.
Characteristics of the valve types
Y-valves
Flat seat valves
• 2700
• 2712
Diaphram valves Ball valves Flap valves
Types
Typical media • Water, steam and
gases
• Alcohols, oils, fuels,
hydraulic fluides
• Salt solutions, lyes
(organic)
• Organic solvents
• 2730 (plastic)
• 2731 (metal)
• 2731K (pipe housing)
• 2652 (2-part,VA)
• 2655 (3-part,VA)
• 2658 (plastic)
• Neutral gases and
liquids
• contaminated, ab-
rasive and aggressive
media
• high purity or sterile
media
• high viscosity media
• Neutral gases and
liquids
• pure water
• slightly aggressive
media
• 2672 (metal)
• 2675 (plastic)
Characteristic • Inlet flow under seat
• Non-impact closure
• Medium is hermeti-
cally separated from
actuator and the
ambient
• Straight flow of
medium
• Self-adjusting packed
gland for very tight seal
• Self-draining housing
design without dead
spaces
• Either flow direction
with low turbulence
flow
• May be steam
sterilized
• CIP compatible
• Non-impact closure
• Actuator and dia-
phragm are de-
tachable with the
housing
• Piggable
• Low and dead space
• insensitive to
contamination
• Lower pressure loss
than with other valve
types
• with 3-part ball valve,
seat and seal can be
exchaged while
installed
Note
Only usable as process controller.
• insusceptible to dirt
• less pressure loss
compared to other
valve types
• good value for money
• smaller volume
• Neutral gases and
fluides
• slightly aggressive
media
8630 - 15
S
YSTEM
D
ESCRIPTION
Construction of TOP Control Continuous
Illustrations (cover removed)
Screw for adjusting the lower proximity switch
Screw for adjusting the upper proximity switch
Positioning system with 2, 3 or 4 solenoid valves
Operating module with display and keys
Pressure supply port
(marked: 1)
Control ports
(connected in the factory)
Exhaust air ports
(marked 3)
16 - 8630
Fixing screw for fixing the
TOP Control Continuous on the drive
Max. torque 1.2 Nm
Electrical connection module, here with multipole connectors
S
YSTEM
D
ESCRIPTION
Design features
• Versions for single and double acting valve actuators
• Position sensor very high resolution conductive plastic potentiometer, coupled without play to the piston rod of the pneumatic actuator
• Microprocessor controlled electronics for signal processing, control and driving the valve
• Operating module
The device is operated via 3 keys. 8-digit, 16-segment LC display for showing the setpoint or actual value and for configuration and parametrization via menu functions.
• Positioning system
With single-acting actuators, the positioning system consists of 2 solenoid valves; with double-acting actuators of four solenoid valves. With single-acting actuators, one valve serves to pressurize the pneumatic piston drive and another to exhaust it. Double-acting actuators contain 2 valves for pressurization and 2 for exhausting.The solenoid valves work on the rocker principle and are driven via the controller with a PWM voltage. This enables great flexibility with regard to actuator volumes and floating speed. For larger pneumatic actuators, the solenoid valve are equipped with diaphragm boosters.
As an option, with single-acting actuators, there are fast pressurizing/exhaust variants with an additional pressurizing valve and an additional exhaust valve. These enable the actuator to be completely pressurized and exhausted more rapidly. This is used with the tight-closure function (see section
" CUTOFF") and on activation of a safety position of 0 or 100% (see section "BIN-IN").
• Position repeater (optional)
2 inductive proximity switches (initiators) or mechanical limit switches.
Attainment of an upper or lower position of the valve can be relayed via binary outputs e.g. to a PLC.
The end settings on the initiators can be adjusted by the owner by means of setscrews.
• Pneumatic interfaces
1/4’’- connectors in various threads
(G, NPT, RC)
• Electrical interfaces
Multipole plug connector or cable bushing
• Housing
The housing of the TOP Control is protected by a pressure relief valve from excessive internal pressure, e.g. resulting from leaks.
The cover may be secured against unauthorized opening with a lead seal or with a self-tapping screw.
8630 - 17
S
YSTEM
D
ESCRIPTION
Fuctional diagram as a positioner with single-acting actuator
Actual process value
Process setpoint external position setpoint
Process controller
Actual position
TOP Control Continuous
Position sensor
Setpoint position
Positioner
Positioning system
Positioning system
1: pressurizing valve
2: exhaust valve
Compressed air supply
Exhaust air
Pneumatic actuator
(single-acting)
Valve
(actuator)
Sensor
Actual process value
(flow rate, pressure, level, temperature etc.)
18 - 8630
S
YSTEM
D
ESCRIPTION
Operating as a positioner
The actual position (POS) of the pneumatic actuator is measured via the position sensing system. The controller compares this actual value of the position with the setpoint (CMD) , which can be specified as a standard signal. If a control difference (Xd1) exists, a pulse-width modulated voltage signal is sent to the positioning system as the correcting variable. With single-acting actuators, if the difference is positive, the pressurizing valve is driven via output B1; if it is negative, the exhaust valve is driven via output
E1. In this way, the position of the actuator is altered until the control difference is zero. Z1 represents a disturbance.
CMD
Position setpoint
Xd1
Positioner
Z1
B1
E1
POS
Positioning system Solenoid
P
K
Continious valve
Valve opening
Position control loop
8630 - 19
S
YSTEM
D
ESCRIPTION
20 - 8630
S
YSTEM
D
ESCRIPTION
Characteristics of the positioner software
Supplementary function
Insensitivity range
Effect
Positioner with supplementary functions
Tight-closing function
Valve closes tight outside control range. A value is given (at %) from which the actuator is completely exhausted (at 0%) or pressurized (at 100 %).
Stroke limitation
Signal range splitting
Correction characteristic to match the operating curve
Mech. valve piston movement only withhin a specified stroke range.
Splitting of the standard signal range over two or more
TOP Control Continuous.
Linearization of the process characteristic can be performed.
The positioner cuts in only above a specified control difference.
Direction of action of the controller setpoint
Safety position
Reversal of the setpoint action direction
Valve moves to a specified safety position.
Hierarchical concept for simple operation with the following levels
Process operation
Configuration
In this level your switch between automatic and manual operation.
In this level you specify on commissioning certain basic functions and configure supplementary functions as needed.
8630 - 21
S
YSTEM
D
ESCRIPTION
* Operation as a process controller (option)
On operation of the TOP Control Continuous as a process controller, the abovementioned position control becomes a subordinate auxiliary control loop; the result is a cascade control. The process controller in the main loop of the TOP Control Continuous has a PID function. The setpoint specified is the process setpoint (SP) and it is compared with the process variable to be controlled. The actual position (XPOS) of the pneumatic actuator is measured via the position sensing system. The controller compares this actual value of the position with the setpoint (CMD) , which can be specified as a standard signal. If a control difference (Xd1) exists, a pulse-width modulated voltage signal is sent to the positioning system as the correcting variable. With single-acting actuators, if the difference is positive, the pressurizing valve is driven via output B1. If it is negative, the exhaust valve is driven via output E1.
In this way, the position of the actuator is altered until the control difference is zero. Z2 represents a disturbance.
Z1
Xd1
B1
P
K
E1
Positioner
XPOS
Positioning system Solenoid valves
Continuous
Valve
Valve opening
Position control loop
Position sensor
Process setpoint
SP
Z2
Xd2 CMD Process control loop
Process controller
Valve opening
Process
Process variable
PV
Transmitter
Example of process control:
TOP Control Continuous with sensor
22 - 8630
S
YSTEM
D
ESCRIPTION
8630 - 23
S
YSTEM
D
ESCRIPTION
Characteristics of the process controller software
Supplementary function Effect
Positioner with supplementary functions
Tight-closing function
Stroke limitation
Signal range splitting
Correction characteristic to match the operating curve
Insensitivity range
Valve closes tight outside control range. A value is given (at %) from which the actuator is completely exhausted (at 0%) or pressurized (at 100%).
Mech. valve piston movement only within a specified stroke range.
Splitting of the standard signal range over two or more
TOP Control Continuous.
Linearization of the process characteristic can be performed.
The positioner cuts in only after a specified control difference.
Direction of action of the controller setpoint
Safety position
Reserval of the setpoint action direction
Analog feedback (option)
Valve moves to a specified safety position
Feedback of the position/process values
Binary outputs
Connectable process controller with the following characteristics (Option)
Controller structure
Parameters that can be set
Scalable input
Method of setpoint setting
PID
Proportional action factor, reset time, rate time and operating point
Decimal point position, upper and lower sacle valures of process value and setpoint
Setting either via standard signal input or via keys
Hierarchical concept for simple operation with the following levels
Process operation
Configuration
In this level your switch between automatic and manual operation.
In this level you specify on commissioning certain basic functions and configure supplementary functions as needed.
24 - 8630
S
YSTEM
D
ESCRIPTION
* Operation as a flow rate controller (option)
The flow rate controller is a special type of process controller. The process value (PV) is not measured directly via an analog input but calculated in the device by the dp method. According to the algorithm, the flow rate is dependent on the parameters pressure before valve (p1), pressure after valve (p2), medium temperature (T) and the kv value. For this reason, the TOP Control Continuous FMR has inputs for 2 pressure transmitters and a temperature transmitter which can be optionally connected.
One pressure transmitter measures the pressure before the valve and a second one after the valve. The temperature is either entered manually in the operating menu or is provided as a standard signal by a temperature transmitter. The kv value is determined internally from the current position of the control valve. For this purpose, a kv characteristic curve is provided in the control valve used.
The density of the medium is entered via the operating menu.
T
Temperature (optional)
Pressure p1
PV
8630
Flow rate controller e.g. valve type 2712 kv value
Pressure p2 p1 p2
In the case of the flow rate controller, the process parameters are either the volumetric flow rate or, for special applications, the transport velocity at the end of a pumping section.
The volumetric flow rate is represented in m 3 /h STP, i.e. referred to 0 °C (medium temperature) and a gas pressure of 1013 mbar (abs).
There are special applications for flow rate controllers in which a pumping section is set up after the valve, in which bulk goods enter via an airlock. These bulk goods are blown through the pumping section by the pumping pressure that builds up behind the valve.
The transport velocity corresponds to the volumetric flow rate of the medium, referred to the piping diameter of the pumping section. However, it is not specified for standard conditions, but reflects the velocity of the gas particles at the existing medium temperature. The diameter is entered in the operating menu.
Characteristics of the flow rate controller software
The flow rate controller offers the same functions as the process controller.
8630 - 25
S
YSTEM
D
ESCRIPTION
26 - 8630
S
YSTEM
D
ESCRIPTION
* Interfaces of the TOP Control Continuous in the multipole variant
Inputs for position or process setpoint
4..20 mA
0..20 mA
0..10 V
0..5 V
Input for process setpoint
4..20 mA
Frequency
Pt 100
* Flow rate controller
Binary input
24 V DC
TOP Control
Continuous
(multipole - variant)
Operating unit
2 binary outputs
Analog position feedback
*Initiators 1 + 2
* Note:
Inputs for process value with flow rate controller (option): p
1
, p
2
, T (optional).
The standard process controller inputs (4 ... 20 mA, frequency, Pt 100) and the initiators cannot be used with this option.
NOTE TOP Control Continuous Type 8630 is a 3-conductor device, i.e. the voltage supply (24 V
DC) is separate from the setpoint signal.
8630 - 27
S
YSTEM
D
ESCRIPTION
* Interface of the TOP Control Continuous in the variants with cable bushings
Inputs for position or process setpoint
4..20 mA
0..20 mA
0..10 V
0..5 V
Input for process setpoint*
4..20 mA
Frequency
Pt 100
(alternative to binary outputs)
Binary input
24 V DC
Sup- ply
TOP Control
Continuous
(PG - variant)
Operating unit
2 binary outputs*
(alternative to input for process setpoint)
Analog position feedback
* Note:
The choice between a process setpoint input and two binary outputs is made by positioning the jumper.
NOTE TOP Control Continuous Type 8630 is a 3-conductor device, i.e. the voltage supply (24 V
DC) is separate from the setpoint signal.
28 - 8630
S
YSTEM
D
ESCRIPTION
Technical data
Safety settings on failure of auxiliary electrical or pneumatic energy
Actuator type Designation
Single-acting
SFA
Safety position after failure of auxiliary energy
Electrical Pneumatic down down
Single-acting
SFB up up
Double-acting
SFI down / up
(depending on connection of control conductors)
undefined
8630 - 29
S
YSTEM
D
ESCRIPTION
Factory settings on the TOP Control Continuous
Function Factory setting Function Factory setting
ACTFUNC
INPUT
CHARACT
FUNCSNGL
INP 4'20 A
CHA LIN
X.CONTRL
X.CO DBND 1 %
X.CO PARA
KX Values calculated by AUTOTUNE
KX Values calculated by AUTOTUNE
After execution of SETFACT: 1
DIR.CMD
CUTOFF
DIR.ACT
SPLTRNG
X.LIMIT
DIR.CRISE
CUT 0 %, CUT
DIR.ARISE
SR
LIM
100 %
0 (%), SR 100 (%)
0 %, LIM 100 %
X.TIME
T.OPN
T.CLS
Values calculated by AUTOTUNE
Values calculated by AUTOTUNE
After execution of SETFACT: 1 s
P.CONTRL
P.CO DBND 1 %
P.CO PARA
KP
TN
TV
X0
1.00
999.9
0.0
0
P.CO SETP SETP INT
P.CO INP INP 4´20 A
P.CO FILT
P.CO SCAL
P.CO TUNE
P.CO KV
0
PV 000.0, PV 100.0
D’ACT
FACT
OUTPUT
OUT ANL:
OUT POS
OUT BIN:
OUT DEV
BIN-IN
B.IN SPOS
OUT 4´20 A
DEV 5.0 NO
SPOS 000 NO
P.CONTRL with flow rate controller
P.CO DBND 1 %
P.CO PARA
KP 1.0
999.9
TN
TV
X0
0.0
0
P.CO SETP SETP INT
P.CO INP INP P1’P2
P.CO FILT
P.CO SCAL
0
PV 000.0, PV 100.0
P.TYP
UNIT
TEMP
DENS
DIAM
P.CO TUNE
P.CO KV
FLOW
M3/H
MAN
1.293
0025
D’ACT
FACT
CODE CODE 0000
NOTE The functions and factory settings shown in grey are valid for the optional flow rate control.
30 - 8630
S
YSTEM
D
ESCRIPTION
Data of the TOP Control Continuous
OPERATING CONDITIONS
Permissible ambient temperature
Protection type cable or
- 10 ... + 50 °C
IP 65 to EN 60529 (only with correctly connected plug and socket)
ATTENTION!
The TOP Control Continuous is not suitable for outdoor use.
CONFORMITY TO THE FOLLOWING STANDARDS
CE conformity wer. EMC Guideline 89/336/EWG
MECHANICAL DATA
Dimensions
Housing material TOP Control
Dichtmaterial see data sheet outer: Noryl (PPE/PA), PSU, inner: PA 6
NBR
ELECTRICAL DATA
Connections
Voltage supply
Power consumption
Housing internal temperature indication
Input resistance for actual value signal
Choice between multipole connector or
3 bushings M 16 x 1.5
with screw terminals 0.14 ... 1.5 mm²
24 V DC ± 10 % residual ripple 10 %
No industrial DC!
< 5 W
- 55 ... + 125 °C, accuracy ± 2 °C
180 Ω at 4 - 20 mA/resolution 12 bit
17 k Ω at frequency, 0 ... 1000 Hz / 1‰ of mean
> 300 V ss
sinus, square-wave, sawtooth
PT-100 - 20 ... + 220 °C, resolution < 0.1 °C
180 Ω at 0/4 - 20 mA/resolution 12 bit
19 k Ω at 0 - 5/10 V /resolution 12 bit
3 to VDE 0580
Input resistance for setpoint signal
Protection class
Analog position feedback: max. current for voltage output 0 ... 5/10 V max. burden for current output 0/4 ... 20 mA
Inductive proximity switch current limitation
10 mA
560 Ω
100 mA
8630 - 31
S
YSTEM
D
ESCRIPTION
Binary outputs current limitation
Binary input
PNEUMATIC DATA
Control medium
Dust content
Water content
Oil content
Temperature range of compressed air
Pressure range
Supply pressure variation
Air flow capacity of control valve
Intrinsic air consumption with zero control output
Connections electrically isolated
100 mA, output is clocked electrically isolated
0 ... 5 V = log "0", 10 ... 30 V = log "1" inverted output reversed accordingly
Qualitiy Classes to DIN ISO 8573-1
Class 5 max. particle size 40 µm, max. particle density 10 mg/m 3
Class 3 max.pressure dew point
- 20 °C or min. 10 deg. below the lowest operating temperature
Class 5 max. 25 mg/m³
-10 ... + 50 °C
3 ... 7 bar max. ± 10 % during operation
100 l
N
(Q
Nn
/ min STP (for pressurizing and exhausting)
- value acc. to definition on pressure drop from 7 to 6 bar abs.)
0.0 l
N
/min STP
G 1/4’’ internal thread G / NPT / RC
32 - 8630
F
IRST
C
OMMISSIONING
FIRST
COMMISSIONING
Fluidic installation
............................................................................................................................................................................................................................
34
* Electrical installation - multipole connector
.........................................................................................................................................
35
* Electrical installation - connection terminals for cable bushings
........................................................................
36
Basic settings of the TOP Control Continuous
...................................................................................................................................
37
Settings in the menu items
..............................................................................................................................................................................................
38
Entering the position setpoint in the AUTOMATIC mode
.........................................................................................................
38
Manual opening and closing of the valve actuator in the MANUAL mode
.........................................................
39
* Alternative chapters or functions depending on device configuration
8630 - 33
F
IRST
C
OMMISSIONING
NOTE This section enable you to put the TOP Control Continuous rapidly into operation for a functional check. Supplementary functions unnecessary for this purpose are not dealt with here.
Fluidic installation
➔ Install the valve according to operating instructions!
➔ Connect supply pressure to connection "1" (3
.. 7 bar; instrument air, free from oil, water and dust)
➔ Attach the exhaust line or silencer to connection "3"!
NOTE Remove the protective caps from the valve and and the TOP Control
Continuous!
34 - 8630
* Electrical installation - multipole connector
F
IRST
C
OMMISSIONING
M16 M12
➔ Apply the setpoint signal to the circular connector M16
Configuration of the circular connector M 16
Pin
B
A
Allocation
Setpoint + (0/4 ... 20 mA
or 0 ... 5/10 V)
Setpoint GND
B
A
External connection/Signal level
+ (0/4 ... 20 mA or 0 ... 5 / 10 V)
GND
➔ Apply the supply voltage to the circular connector M12
Configuration of the circular connector M 12
Pin
1
2
3
4
Allocation
+ 24 V not connected
GND not connected
1
3
External connection
24 V DC ± 10 % max. residual ripple 10 %
NOTE Further installation notes are to be found in the chapter Installation.
After application of the supply voltage, the TOP Control Continuous is in operation. Carry out the necessary basic settings and initiate self-parametrization of the TOP Control.
8630 - 35
F
IRST
C
OMMISSIONING
* Electrical installation - connection terminals for cable bushings
➔ Remove the cover with the cable bushings to gain access to the terminals. This is done by unscrewing the 4 self-tapping screws.
➔
Apply the setpoint signal and the supply voltage to the respective terminals (see
Terminal configuration with cable bushings).
screw terminals
Terminal configuration with cable bushings
Terminal
1
2
5
6
Allocation
Setpoint +
Setpoint GND
Operating voltage +
Operating voltage GND
External connection
1 + + (0/4 ... 20 mA or 0 ... 5/10 V)
2
5
GND
24 V DC ± 10 % max. residual ripple 10 %
6
NOTE Further installation notes are to be found in the chapter Installation.
After application of the supply voltage, the TOP Control Continuous is in operation. Carry out the necessary basic settings and initiate self-parametrization of the TOP Control.
36 - 8630
Basic settings of the TOP Control Continuous
Configuration of the keys
MANUAL/AUTOMATIC-key
Arrow keys
Switch between main and subitems, e.g. ACT FUNC - FUNCSNGL
Switch between equal-ranking menu items, e.g. ACTFUNC - INPUT
AUTOMATIC
MODE
F
IRST
C
OMMISSIONING
MANUAL
MODE
Jump over on first commissioning
8630 - 37
F
IRST
C
OMMISSIONING
Settings in the menu items
ACTFUNC Actuator function
FUNC SNGL - single-acting
FUNC DOUB - double-acting
INPUT Standard signal
INP 4’20A - Current 4 ... 20 mA
INP 0’20A - Current 0 ... 20 mA
INP 0’10V - Voltage 0 ... 10 V
INP 0’5V - Voltage 0 ... 5 V
ADDFUNCT
X.TUNE
Jump over
Initiate self-parametrization
END XX Return to AUTOMATIC mode ;
the display EEPROM appears until the settings have been in the
memory.
Entering the position setpoint in the AUTOMATIC mode
After selection of the basic settings and return to the AUTOMATIC mode, the TOP Control Continuous works as a positioner.
Enter the position setpoint via the signal.
Switching between the display options:
Display:
• Actual position of valve actuator
• Setpoint position of valve actuator
• Input signal for setpoint position
(here identical to setpoint position)
• Temperature inside
TOP Control Continuous housing
POS__XXX (0 ... 100 %)
CMD__XXX (0 ... 100 %)
INP__XXX
(0 ... 5/10 V or 0/4 ... 20 mA)
TEMP_XX.X (in °C)
38 - 8630
Manual opening and closing of the valve actuator in the
MANUAL mode
F
IRST
C
OMMISSIONING
Open valve actuator:
Close valve actuator:
Display: the display set in the AUTOMATIK mode is retained.
NOTE Select the display POS_XXX , in this case the actual position of the valve actuator can be checked.
8630 - 39
F
IRST
C
OMMISSIONING
40 - 8630
I
NSTALLATION
INSTALLATION
Installation of the valve
............................................................................................................................................................................................................
42
Turning the TOP Control Continuous
.................................................................................................................................................................
42
Procedure
...............................................................................................................................................................................................................................................
42
Fluidic connection of the TOP Control Continuous
.......................................................................................................................
43
* Electrical connection - multipole connectors
.....................................................................................................................................
44
Marking of the multipole plugs or sockets and the contacts
..................................................................................................
44
Output signals for SPS (circular plug M 16)
................................................................................................................................................
45
Operating voltage (circular plug M 12)
...............................................................................................................................................................
45
Inductive proximity switches (circular socket M 8)
..............................................................................................................................
45
Process value (circular plug M 8)
.............................................................................................................................................................................
46
Process value with the option flow rate controller (2 circular plugs M 8)
Option: with temperature sensor input (3 circular plugs M 8)
...............................................................................................
46
* Electrical connection - terminals with cable bushing
.............................................................................................................
47
Connection PCB of the TOP Control Continuous with screw terminals and jumpers
...........................
47
Terminal configuration with cable bushings
.................................................................................................................................................
47
Choice of binary outputs or process value input
...................................................................................................................................
48
* Setting the inductive proximity switches (option)
.........................................................................................................................
50
Opening the housing of the TOP Control Continuous
....................................................................................................................
50
Positioning the inductive proximity switches
...............................................................................................................................................
50
* Alternative chapters or functions depending on device configuration
8630 - 41
I
NSTALLATION
NOTE See data sheet for dimensions of TOP Control and the variants of the complete device, consisting of TOP Control Continuous, pneumatic actuator and valve.
Installation of the valve
NOTE The actuator must not be connected.
For dimensions and threads, see data sheet for the process valve.
Turning the TOP Control Continuous
If, after installation of the continuous valve, the display of the TOP Control Continuous is poorly visible or it is difficult to attach the cable or hoses, the TOP Control Continuous may be rotated relative to the pneumatic actuator.
Procedure
➔ Disconnect the fluidic connection between TOP Control Continuous and pneumatic actuator.
➔ Loosen the fixing screws recessed into the side of the housing (hex socket SW3, see chapter System description - Construction of the TOP Control Continuous).
➔ Rotate the TOP Control Continuous clockwise without lifting into the desired position.
➔ Retighten the fixing screw with 1.2 Nm moderate torque.
➔ Remarke the fluidic connection between TOP Control Continuous and pneumatic actuator, using longer hoses if necessary.
ATTENTION!
If theTOP Control Continuous is lifted during rotation (axially displaced), the mechanical coupling to the position sensor mechanism may be damaged. By turning in the wrong direction (anticlockwise), there is a risk of unhooking the position sensor mechanism.
This can be reconnected only with a special tool!
ATTENTION!
To assure leak tightness of the device (IP65), the screw for connecting TOP Control
Continuous and process valve shall be tightened with a torque not exceeding 1.2 Nm!
42 - 8630
Fluidic connection of the TOP Control Continuous
I
NSTALLATION
➔ Apply the supply pressure to connection“1" (3..7 bar, instrument air, free from oil, water and dust)
➔ Attach the exhaust line or silencer to connection „3“
NOTE Maintain the applied supply pressure, without fail , at least 0.5 - 1 bar over that required to bring the pneumatic actuator into the end position. This assures that the control behaviour in the upper region of the stroke will not be significantly affected negatively if the pressure difference is too small.
Keep variations in the supply pressure as low as possible during operation (max. ± 10
%). With larger variations, the controller parameters calibrated with the AUTOTUNE function will not be optimal.
Remove the protective caps from the valve and the TOP Control Continuous.
8630 - 43
I
NSTALLATION
* Electrical connection - multipole connectors
ATTENTION!
For connection to the technical earth (ground) (TE), a threaded stud with nut is provided on the connection module. To assure electromagnetic compatibility (EMC), connect this stud to a suitable earthing (grounding) point using as short a cable as possible (max. 30 cm).
NOTE Use of the 4 - 20 mA setpoint input
If the voltage supply of a TOP Control device fails in a row of such devices connected in series, the input of the failed device will become high-impedance. This will cause the 4 -
20 mA standard signal to fail. If this occurs, please contact Bürkert Service directly.
With Profibus DP or DeviceNet:
The markings of the multipole plugs and sockets, and the contacts are to be found in the respective chapters.
Marking of the multipole plugs or sockets and the contacts
M16
M8
M12
M8
Output signals to
SPC
Operating voltage
Process value
44 - 8630
TE
Initiators (inductive proximity switches)
I
NSTALLATION
Output signals for SPS (circular plug M16)
C
D
E
F
G
H
J
K
L
M
Pin
A
B
Allocation
Setpoint GND
Setpoint + (0/4..20 mA or 0..5/10 V)
Analog position feedback +
Analog position feedback GND
Binary output 1
Binary output 2
Binary output GND
Binary input +
Binary input GND not connected not connected not connected
H
J
E
F
G
B
A
C
D
External connection/signal level
+ (0/4 ... 20 mA or 0..5/10 V)
completely isolated electrically
GND
+ (0/4 ... 20 mA or 0 ... 5/10 V)
completely isolated electrically
GND
24 V / 0 V
24 V / 0 V
GND
+
GND
0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
Operating voltage (circular plug M 12)
External connection Pin
1
2
3
4
Allocation
+ 24 V not connected
GND not connected
24 V DC ± 10 % max. residual ripple 10 %
Inductive proximity switches (circular socket M 8)
Pin
3
4
1
2
Allocation
Proximity switch 1 + (NO)
Proximity switch 1 GND
Proximity switch 2 + (NO)
Proximity switch 2 GND
Signal level
+24 V DC
GND
S1
S2
+24 V DC
GND
1
2
3
4 open / 24 V
GND open / 24 V
GND
8630 - 45
I
NSTALLATION
Process value (circular plug M 8)
Input type *
4 ... 20 mA
- internal
supply
4 ... 20 mA
- external
supply
Frequency
- internal
supply
Frequency
- external
supply
3
4
1
2
3
4
1
2
1
2
3
4
Pin Allocation
3
4
1
2
Jumper** External connection
+ 24 V supply transmitter
Output Transmitter
GND bridge to GND (GND from
3-conductor transmitter) not connected
Process actual + not connected
Process actual -
+ 24 V - supply sensor
Clock input +
Clock input - (GND) not connected not connected
Clock input +
Clock input not connected
1
2
3
2
3
2
4
4 ... 20 mA
GND
+24 V
Clock +
Clock -
Clock +
Clock -
Pt-100
(see
Note below)
3
4
1
2 not connected process actual 1(current supply) process actual 3 (GND) process actual 2 (compensation)
2
3
4
Pt 100
* May be set via software (section Procedure for specifying the basic settings)
** The jumper is situated on the connection board of the TOP Control Continuous (see next page)
NOTE For line compensation reasons, connect sensor Pt-100 via 3 conductors. PIN 3 and PIN 4 must be bridged at the sensor.
Process value with the option flow rate controller (2 circular plugs M8)
Option: with temperature sensor input (3 circular plugs M8)
Input type No. of plugs
1 internally supplied transmitter*
2
Option: temperature transmitter
3
Pin Configuration
1
2
3 + 4
1
2
3 + 4
+ 24 V - supply to transmitter p1
4 ... 20 mA - output from transmitter p1 n.c.
+ 24 V - supply to transmitter p2
4 ... 20 mA - output from transmitter p2 n.c.
1
2
3 + 4
+ 24 V - supply to transmitter
4 ... 20 mA - output from temperature transmitter n.c.
Jumper ext. connection
* With external supply of the sensors, the mass of the standard signal must be
connected to the mass of the supply voltage.
Circular plug
M12
46 - 8630
I
NSTALLATION
* Electrical connection - terminals for cable bushing
ATTENTION!
For connection to the technical earth (ground) (TE), a threaded stud with nut is provided on the connection module. To assure electromagnetic compatibility
(EMC), connect this stud to a suitable earthing (grounding) point using as short a cable as possible (max. 30 cm).
NOTE Use of the 4 - 20 mA setpoint input
If the voltage supply of a TOP Control Continuous device fails in a row of such devices connected in series, the input of the failed device will become high-impedance. This will cause the 4 - 20 mA standard signal to fail. If this occurs, please contact Bürkert Service directly.
Connection PCB of the TOP Control Continuous with screw terminals and jumpers
➔ Remove the cover with the cable bushings to gain access to the screw terminals. This is done by unscrewing the 4 self-tapping screws.
Terminal configuration with cable bushings
Terminal
1
2
3
4
5
6
Allocation
Setpoint +
Setpoint GND
Analog position feedback +
Analog position feedback GND
Operating voltage +
Operating voltage GND
External connection
1 + + (0/4 ... 20 mA or 0 ... 5/10 V
2
GND
3
4
5
+ (0/4 ... 20 mA or 0 ... 5/10 V)
completely isolated electrically
GND
24 V DC ± 10 % max. residual ripple 10 %
6
8630 - 47
I
NSTALLATION
Choice of binary outputs or process value input
➔
Select using the jumpers:
2 binary outputs (see terminal Allocation when binary outputs selected) or
Process value input (see terminal Allocation when process value input selected).
Terminals 7 to 10 are connected to the corresponding signals.
Jumper Terminal Allocation
7
8
Binary output 1
Binary output 1
9
10
Binary output 2
Binary output 2
9
8
7
External connection
24 V / 0 V NC / NO
GND
24 V / 0 V NC / NO
10 GND
Terminal allocation on selection of process value input:
➔ The input type is set via the configuration menu (see Procedure for specifying the basic settings) .
Input type* Jumper Terminal Allocation
4 ... 20 mA internal supply
7
8
9
10
+ 24 V input transmitter
Output transmitter
Bridge to GND (GND from
3-conductor transmitter)
GND
Frequency internal supply
4 ... 20 mA external supply
Frequency external supply
Pt-100
(see
Note below)
7
8
9
10
7
8
9
10
7
8
9
10
7
8
9
10
External connection
7
8
9
10
+ 24 V supply sensor
Clock input + not connected
Clock input - (GND) not connected
Process actual +
Process actual not connected not connected
Clock input + not connected
Clock input not connected
Process actual 1 (current supply)
Process actual 2 (compensation)
Process actual 3 (GND)
8
10
8
9
8
9
10
7
8
10
+24 V
Clock +
Clock - (GND)
+ (4 ... 20 mA)
GND
Clock +
Clock -
Pt100
NOTE For reasons of line compensation, connect the Pt 100 sensor over 3 conductors. Be sure to bridge terminals 9 and 10 at the sensor.
48 - 8630
I
NSTALLATION
Terminal allocation with binary outputs
Terminal Allocation
11
12
Binary input +
Binary input GND
External connection
11
12
+
GND
0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
8630 - 49
I
NSTALLATION
* Setting the inductive proximity switches (Option)
ATTENTION!
In order to set the inductive proximity switches, the housing of the TOP Control
Continuous must opened. Switch off the operating voltage before making this intervention!
Opening the housing of the TOP Control Continuous
➔
Remove any lead seals or fastenings present between cover and housing.
➔
Turn the cover anticlockwise and lift it off.
Positioning the inductive proximity switches
➔ The inductive proximity switches are positioned vertically with one adjusting screw each:
Turning clockwise causes upward adjustment
Turning anticlockwise causes downward adjustment
ATTENTION!
On adjusting the height of the inductive proximity switches, make sure that adjacent flexes are not pulled (e.g. by getting hooked in the proximity switches). If this is not adhered to, plugged connections may be damaged or loosened).
Screw to adjust the lower proximity switch
Screw to adjust the upper proximity switch
50 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
OPERATION
AND
CONTROLLER FUNCTION
Operating and display elements
...............................................................................................................................................................................
52
Operating levels
.................................................................................................................................................................................................................................
52
Commissioning and set-up as a positioner
..............................................................................................................................................
53
Procedure for specifying the basic settings
...............................................................................................................................................
53
Main menu for the settings on commissioning
......................................................................................................................................
54
Description of the procedure
........................................................................................................................................................................................
55
Configuring the supplementary functions
...................................................................................................................................................
59
Keys in the configuration level
....................................................................................................................................................................................
59
Configuration menu
..................................................................................................................................................................................................................
59
Supplementary functions
..................................................................................................................................................................................................
62
Operating the process
.............................................................................................................................................................................................................
86
Changeover between operating modes
.........................................................................................................................................................
86
Operating mode AUTOMATIC
......................................................................................................................................................................................
87
Meaning of the keys in the AUTOMATIC mode
....................................................................................................................................
87
Display of the AUTOMATIC mode
........................................................................................................................................................................
87
Operating mode MANUAL
.................................................................................................................................................................................................
88
Meaning of the keys in the MANUAL mode
...............................................................................................................................................
88
Display of the MANUAL mode
....................................................................................................................................................................................
88
8630 - 51
O
PERATION AND CONTROLLER FUNCTIONS
Operating and display elements
The TOP Control Continuous is equipped with a 3-key operating and display element with LC display.
The functions of the keys are described in the following sections.
MANUAL/AUTOMATIC KEY
LED (yellow) in the MANUAL/AUTOMATIC-key
(see chapter Operating the process controller)
Arrow key up Arrow key down
Operating levels
Operation of the TOP Control Continuous is done via two operating levels:
• Process operating level:
After the device is switched on, the process operating level is active. In this level, you can switch between the operating modes AUTOMATIC and MANUAL. In the AUTOMATIC mode, position or process control (only for the process controller option) runs. In the MANUAL mode, the valve can be manually opened and closed.
• Configuration level:
In the configuration level, you can specify on first commissioning the basic functions and configure supplementary functions if needed.
Process operating level
MANUAL AUTO-
MATIC
5 sec
Configuration level
Basic funktions
End
Supplementary functions
52 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
Commissioning and set-up as a positioner
➔ Before commissioning, execute the fluidic and electrical installations.
Procedure for specifying the basic settings
➔
On first commissioning of the TOP Control Continuous, carry out the following basic settings:
• Specify the function of the pneumatic actuator used.
• Specify the standard signal input for setpoint setting (4..20 mA, 0..20 mA, 0..10 V or 0..5 V).
• Start the automatic adaptation of the positioner to the current operating conditions (AUTOTUNE).
Configuration of the keys
MANUAL/AUTOMATIC-key
Arrow keys
Switch between main and sub-menu items, e.g.
ACT FUNC - FUNCSNGL
Switch between eual-ranking menu items, e.g.
ACTFUNC - INPUT
Factory setting of the positioner
Function Factory setting
ACTFUNC FUNCSNGL
INPUT INP 4'20A
CHARACT CHA LIN
DIR.CMD DIR.CRISE
CUTOFF CUT = 0 %; CUT = 100 %
DIR.ACT DIR.ARISE
SPLTRNG SR = 0 (%); SR = 100 (%)
X.LIMIT LIM = 0%, LIM = 100%
X.TIME
T.OPN Values determined by AUTOTUNE
T.CLS Values determined by AUTOTUNE
After execution of SETFACT: 1 s
Function
OUTPUT
OUT ANL:
OUT POS
OUT BIN:
OUT DEV
BIN-IN
B.IN SPOS
Factory setting
OUT 4'20 A
DEV 5.0 NO
SPOS 000 NO
X.CONTROL
X.CO DBND 1 %
X.CO PARA
KX Values determined by AUTOTUNE
KX Values determined by AUTOTUNE
After execution of SETFACT: 1
CODE CODE 0000
8630 - 53
O
PERATION AND CONTROLLER FUNCTIONS
Main menu for the settings on commissioning
AUTOMATIC
MODE
5 s
MANUAL
MODE
Jump over on first commissioning
5 s
54 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
Description of the procedure
After the voltage supply has been switched on, the positioner is in the process operating level in the
AUTOMATIC mode. To specify the basic settings, switch to the configuration level. Depress the MANU-
AL/AUTOMATIC key for 5 seconds. The display then shows ACTFUNCT, the first item of the main menu.
To make a setting under the menu item ACTFUNC, press the MANUAL/AUTOMATIC key briefly.
Then one of the sub-menu items appears on the display. The arrow keys are used to switch between these sub-items, enabling the desired settings to be made. The desired setting is confirmed after selection by pressing the MANUAL/AUTOMATIC key. The arrow keys are also used to switch between the items of the main menu ( ACTFUNCT, INPUT, ...).
NOTE At the level of the sub-menu items, the selected function is shown by the three or four characters at the right of the 8-digit display. These characters flash on the display.
ACTFUNC - Function of actuator
➔ Enter under this menu item the function of the pneumatic actuator used in combination with the TOP
Control. This function is marked on the rating plate of the actuator.
- single-acting
- double-acting
INPUT - Selected standard signal
➔ Enter under this menu item the standard signal used for the setpoint.
- Current 4 ... 20 mA
- Current 0 ... 20 mA
- Voltage 0 ... 10 V
- Voltage 0 ... 5 V
8630 - 55
O
PERATION AND CONTROLLER FUNCTIONS
ADDFUNCT
See section Configuring the supplementary functions.
➔
Jump over this menu item on first commissioning.
X.TUNE
- Autotune for positioner
➔ Start the program for automatic parametrization of the TOP Control Continuous via the menu item
X.TUNE.
The following functions are initiated automatically:
• Adaptation of the sensor signal to the (physical) stroke of the valve used
• Determination of parameters of the PWM signals for driving the solenoid valves integrated in the
TOP Control Continuous.
• Setting of the controller parameters of the positioner. Optimization is done according to the criteria: as short a correcting time as possible and simultaneously freedom from overshoot.
➔
Start AUTOTUNE by calling up X.TUNE in the main menu.
➔ Then depress the MANUAL/AUTOMATIC key for 5 seconds.
NOTE To cancel AUTOTUNE, operate both arrow keys at the same time and select X.TUN BRK .
Start the automatic adaptation of the positioner to the current operating conditions
Display
TUNE 5
TUNE 4
:
TUNE 0
¦ X.T INIT
¦ X.T A1-P
¦ X.T TOPN
¦ X.T TCLS
:
TUNE-END
X.ERR X
Description
Countdown from 5 to 0 start of AUTOTUNE
Display of the autotune phase in progress at the moment
(continuation is indicated by a rotating bar to the left of the display)
Flashing display
➞ end of AUTOTUNE
Message on occurrence of an error
(Indication right: Error number, see chapter Maintenance and controller fault rectification)
NOTE The basic settings onthe TOP Control Continuous are made in the factory. On commissioning, nevertheless, execution of X.TUNE is absolutely necessary . TOP Control
Continuous then determines automatically the optimum settings for the current operating conditions.
If the supplementary function X.CONTRL is present in the main menu during execution of
X.TUNE, the positioner dead band X.CO DBND is additionally determined automatically as a function of the frictional behaviour of the positioning mechanism (see chapter
Supplementary Functions - X.CONTROL).
56 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
ATTENTION!
During execution of the AUTOTUNE function, the valve moves on its own away from its current position. For this reason, never execute AUTOTUNE while the process is running!
MANUAL TUNE - FUNCTIONS
Access to the manual TUNE functions is obtained by selection X.TUNE in the main menu and briefly pressing the MANUAL/AUTOMATIC key, or on abortion of countdown, by releasing the MANUAL/
AUTOMATIC key.
AUTOTUNE MANUAL TUNE release
5 s move to max.
position move to min.
position change min. PWM T.V.
for pressurizing valve display of opening time (s) change min. PWM T.V. for venting valve display of closing time (s)
The following parameters, which are automatically determined during X.TUNE, may be manually present or adjusted afterwards.
TUNE-END - Return to main menu
TUNE-POS Present end position
The AUTOTUNE function determines the end positions of the control armature from the physically stops.
Certain armatures (e.g. rotating vanes) have no physically stops, so that the end positions must be manually present using TUNE-POS. When executed immediately afterwards, AUTOTUNE assumes the manual end settings and continues with the setting of the positioning system and optimization of the positioner.
NOTE If manual presetting of the end positions by means of TUNE-POS is necessary, it must be done before execution of AUTOTUNE.
8630 - 57
O
PERATION AND CONTROLLER FUNCTIONS
TUNE-PWM - Readjust minimum PWM pulse-duty factor for driving the solenoid integrated in
the TOP Control Continuous
The AUTOTUNE function determines automatically the minimum PWM pulse-duty factor necessary for driving the solenoid integrated in the TOP Control Continuous. If the frictional characteristics of the positioning mechanism are unfavourable, these values may deviate from the optimum. By using TUNE-
PWM, however, they can be readjusted to obtain the lowest possible speed in both directions.
NOTE
The function TUNE-PWM must be executed after AUTOTUNE!
TUNE-AIR Adapt the opening to the closing time of the process valve
With spring-closing process valves, the opening speed may be varied within certain limits by changing the supply pressure. The closing speed, however, is independent of the supply pressure and given by the spring force and the nominal diameter of the venting valve. By using TUNE-AIR, the opening time may be adapted to the closing time. This results in symmetrical motion, which has a favourable effect on the process control.
NOTE The function TUNE-AIR must be executed after AUTOTUNE!
ATTENTION!
Avoid faulty adaptation of the controller by executing X.TUNE in all cases at the supply pressure (pneumatic auxiliary energy) that will exist in later operation.
The function X.TUNE should preferably be executed without operating medium pressure to avoid disturbing influences from flow forces.
END - Quitting the main menu and display of the software version
➔ To quit the main menu, select the item END with the arrow keys. To the right of the display the software version is shown (END XX).If the MANUAL/AUTOMATIC key is pressed, EEPROM appears on the display until the changes have been saved. After that, the device returns to the mode in which it was before switching over to the main menu (MANUAL or AUTOMATIC).
58 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
Configuring the supplementary functions
NOTE The operating concept for the TOP Control Continuous is based on a strict separation between the basic and supplementary functions. In the delivered state, only the basic functions are activated. These suffice for normal operation. For more demanding control applications, you can select and specify supplementary functions in the configuration level.
Keys in the configuration level
Press key
Press key in Menu
Scroll up
(select)
Scroll down
(select) in a selected and confirmed menu item
Increment (increase) numeric value
Decrement (decrease) numeric value in Menu confirm selected menu item
Confirm set values in menu ADDFUNCT
Confirm selected menu item of supplementary menu to add it to the main menu. The menu item is marked with an asterisk (*) in the supplementary menu.
The menu item appears int he main menu and can be selected and edited there. Confirm the menu item selected and marked with asterisk in the supplementary menu for deletion from the main menu.
Configuration menu
Switching between the process operating level and the configuration level
Process operating level
MANUAL AUTO-
MATIC
5 sec
Configuration level
Basic functions
END
Supplementary menu
8630 - 59
O
PERATION AND CONTROLLER FUNCTIONS
5 s To activate the configuration menu, press (in the process operating level), the MANUAL/
AUTOMATIC key for 5 seconds.
The configuration menu consists of a main and a supplementary menu. The main menu contains initially the basic functions which are specified during first commissioning. The supplementary menu comprises supplementary functions which may be reached via the menu item ADDFUNCT of the main menu.
Specification of device functions and parameters is possible only within the main menu. If needed, the main menu may be augmented by additional functions and parameters from the supplementary menu, which can then be specified.
Addition of supplementary functions to the main menu
➔ Select in the main menu the item ADDFUNCT.
➔ By pressing the MANUAL/AUTOMATIC key, enter the supplementary menu.
➔ With the arrow keys, select the desired supplementary function.
➔ By pressing the MANUAL/AUTOMATIC key, confirm addition of the supplementary function to the main menu. The function is automatically marked with an asterisk (*).
➔ All marked functions are added to the main menu after confirmation of ENDFUNCT.
➔ In the main menu, enter the parameters for the supplementary functions.
Deletion of supplementary functions from the main menu
NOTE By removing a function from the main menu, the settings previously made under this function are again invalidated.
➔ Select in the main menu the item ADDFUNCT.
➔ By pressing the MANUAL/AUTOMATIC key, enter the supplementary menu.
➔ With the arrow keys, select a supplementary function marked with (*).
➔ By pressing the MANUAL/AUTOMATIC key, confirm deletion of the supplementary function (the asterisk (*) marking is deleted).
➔ After confirmation of ENDFUNCT, the supplementary function is deactivated and deleted from the main menu.
Setting of numeric values
Numeric values are set in the menu items provided by pressing the keys „arrow up“ (increment value) or
„arrow down“ (decrement value) one or more times. In the case of 4-digit numbers, only the flashing digit can be set with the arrow keys. By pressing the MANUAL/AUTOMATIC key, you can switch to the next digit.
60 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
Principle of adding supplementary functions to the main menu
8630 - 61
O
PERATION AND CONTROLLER FUNCTIONS
Supplementary Functions
ADDFUNCT
CHARACT
CUTOFF
DIR.CMD
DIR.ACT
SPLTRNG
X.LIMIT
X.TIME
X.CONTRL
P.CONTRL
CODE
SAFEPOS
SIG-ERR
BIN-IN
OUTPUT
CAL USER
SETFACT
SER-I/O
ENDFUNCT
Select the transfer characteristic between input signal ans stroke (correction characteristic)
Tight closure function for positioners or process controllers (if activated)
Sense of action between input signal ans setpoint position
Allocation of state of pressurization of actuator chamber (Port 2
1
) to actual position
Signal range splitting; input signal in % for which the valvetransverses the entire stroke
Limitation of mechanical stroke range
Limitation of correcting speed
Parametrization of positioner
(Parametrization of the PID process controller).
Without function in the version as positioner!
Code protection for settings
Enter safety position
Configure error recognition signal level
Activation of binary input
(Configuration of the outputs, only with supplementary board for analog feedback or binary outputs)
Calibration
Reset to factory settings
Configuration of the serial interface
62 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
CHARACT
Selection of the transfer characteristic between input signal (position setpoint) and stroke (correction curve)
Customized characteristic
Factory setting: CHA LIN
With this function, you can select a transfer characteristic with respect to setpoint position (setpoint position CMD) and valve stroke (POS) to correct the flow or operating curve.
Linear characteristic
Equipercentile characteristic 1:25
Equipercentile characteristic: 1:33
Equipercentile characteristic 1:50
Inverse equipercentile characteristic 25:1
Inverse equipercentile characteristic 33:1
Inverse equipercentile characteristic 50:1
User-defined characteristic, freely programmable via fixed points
The flow characteristic k v
= f(s) describes the flow through a valve, expressed by the k v
value, as a function of the stroke s of the actuator spindle. It is determined by the shape of the valve seat and the seat seal. In general, two types of flow characteristic are realized: the linear and the equipercentile.
With linear characteristics, equal changes in stroke ds are allocated to equal changes in k v
value dk v
(dk
V
= n lin
* ds).
With an equipercentile characteristic, a change in stroke ds corresponds to an equipercentile change in k v
value
(dk
V
/k
V
= n gleichpr
* ds).
The operating characteristic Q = f(s) represents the relationship between the volumetric flow Q passing through a valve installed in a system and the stroke s. This characteristic contains the properties of the piping, pumps and consumers. It hence has a different shape from the flow characteristic.
8630 - 63
O
PERATION AND CONTROLLER FUNCTIONS
Normalized valve stroke [%] (POS)
Normalized position setpoint [%]
(CMD)
For positioning applications of control systems, special requirements are usually made on the shape of the characteristic, e.g. linearity. For this reason it is sometimes necessary to correct its shape in a suitable manner.
For this purpose, a transfer member is provided in the
TOP Control Continuous which realizes different characteristics. These are used to correct the operation characteristic.
The equipercentile characteristics 1:25, 1:33, 25:1,
33:1 and 50:1 and a linear characteristic may be set.
Furthermore, it is possible to freely program a characteristic via fixed points or have it calibrated automatically.
Entering the freely programmable characteristic
The characteristic is defined via 21 fixed points distributed evenly over the 0...100 % range of the position setpoint. They are separated by 5 %. Each fixed point may be allocated to a freely selectable stroke (setting range 0...100 %). The difference between two adjacent values of stroke may not exceed
20 %.
To enter the point on the characteristic (values of the function), first select the menu item CHR FREE.
After pressing the MANUAL/AUTOMATIC key, the first fixed point is displayed (0 %). Next to it is the value of the function (initially 0 %).
With the arrow keys, set a value of the function between 0 and 100 %. After pressing the MANUAL/
AUTOMATIC key, the next fixed point is displayed, etc. Finally, press the MANUAL/AUTOMATIC key to confirm the value of the function belonging to the last fixed point (100 %). The display returns to the menu item CHARACT.
64 - 8630
Example of a programmed characteristic
Valve stroke [%]
(POS)
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
Setpoint signal [%]
(CMD)
Entering the fixed points:
NOTE
Valve stroke [%]
(enter with arrow keys)
Position setpoint [%]
(fixed point)
Return to
CHARACT
The fixed points that were entered should be noted in the table in the Appendix.
8630 - 65
O
PERATION AND CONTROLLER FUNCTIONS
CUTOFF
Tight closure function for positioners or process controllers
Factory setting: CUT = 0 %; CUT = 100 %
This function causes the valve to close tightly outside the control range. Enter here the limits in percent for the position setpoint (CMD) or, with activated PID controller either for the position setpoint or for the process setpoint SP, from which the actuator is to be completely vented or pressurized. In the case of the fast pressurization/venting version, two valves are driven in each case in order to obtain complete venting more rapidly. Opening or resumption of controlled operation is performed with a hysteresis of 1
%.
If the process valve is in the region of tight closure, there appears in the display a flashing MIN or MAX symbol.
Tight-closing threshold exhaust (0 = inactive); setting range: 0..25 %.
Tight-closing threshold pressurize (100 = inactive); setting range: 75 ... 100 %
Menu appears only with activated PID controller
Limits refer to process setpoint (SP)
Limits refer to position setpoint (CMD)
Valve stroke [%]
(POS)
Setting range: 75 ... 100 %
66 - 8630
Setting range: 0 ... 25 %
Setpoint [%]
(CMD)
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
DIR.CMD
Sense of action or direction of the positioner setpoint
Factory setting: DIR.CRISE
With this supplementary function, you can set the sense of action between the input signal (INP) and the setpoint position (CMD) of the actuator.
Direct sense of action
(e.g. 4 mA or 0 V ➔ 0 %,
20 mA or 5/10 V ➔ 100%)
Inverse sense of action
(e.g. 4 mA or 0 V ➔ 100%,
20 mA or 5/10 V ➔ 0%)
Setpoint position
(CMD)
Inputsignal
(INP)
8630 - 67
O
PERATION AND CONTROLLER FUNCTIONS
DIR.ACT
Sense of action or direction of the actuator
Factory setting: DIR.ARISE
With this supplementary function, you can set the sense of action between the state of pressurization of the actuator and the actual position (POS).
Direct sense of action
(exhausted ➔ 0 %; pressurized ➔ 100 %)
Inverse Wirkungsrichtung
(entlüftet ➔ 100 %; belüftet ➔ 0 %)
Actual position
(POS)
Exhausted Pressurized State of pressurization
68 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
SPLTRNG
Split range
Split range; min. and max. values of the input signal in % for which the valve traverses the entire stroke
Factory setting: SR = 0 (%); SR = 100 (%)
NOTE This function is only effective when operating as a positioner.
This supplementary function limits the Position setpoint range of the TOP Control Continuous by specifying a minimum and maximum values. In this way it is possible to distribute the standard signal range used (4..20 mA, 0..20 mA, 0..10 V or 0..5 V) over several TOP Control Continuous (with or without overlap). Several valves can thus be used as final control elements either alternating or, if the setpoint ranges overlap, simultaneously.
XX
XXX
Entering the minimum value of the input signal in %
(0 ... 75 (%) of the standard signal range)
Entering the maximum value of the input signal in %
(25 ... 100 (%) of the standard signal rage)
Splitting the standard signal range into tow setpoint ranges
Valve stroke
[%]
(POS)
Setpoint range
TOP Control
Continuous 1
Setpoint range
TOP Control
Continuous 2
Setpoint range [mA]
(INP)
8630 - 69
O
PERATION AND CONTROLLER FUNCTIONS
X.LIMIT
Limitation of the mechanical stroke range
Factory setting: LIM = 0%, LIM = 100%
This supplementary function limits the (physical) stroke to preset % values (minimum and maximum).
The range of the limited stroke is thereby set to 100 %.If the limited stroke range is left during operation, negative or positive POS values greater than 100 % are displayed.
XX
Entering the start value of the stroke range in %,
0 ... 50 % of the overall stroke
XXX
Entering the end value of the stroke rage in %,
50 ... 100 % of the overall stroke
The minimum separation between LIM is 50 %.
and LIM
Limited stroke [%]
(POS)
Physical stroke
[%] (POS) unlimited stroke limited stroke
Setpoint [mA]
(INP)
70 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
X.TIME
Limitation of the correcting speed
Factory setting: 1 s
NOTE When executing the function X.TUNE, the minimum opening and closing time for T.OPN
and T.CLS is automatically entered for the full stroke. In this way it is possible to traverse at maximum speed.
If the correcting speed is to be limited, values can be entered for T:OPN and T.CLS that lie between the minimum values determined by X:TUNE and 60 s.
XX
Opening time for full stroke (in seconds)
XX
Closing time for full stroke (in seconds)
Effect of limitation of the opening speed after a step in the setpoint
Valve stroke [%]
(POS, CMD)
Setpoint
Actual value t
T.OPN
NOTE If positioning times < 1 s are determined from the AUTOTUNE, X.TIME is automatically copied to the main menu and the relevant value is set to 1 s.
8630 - 71
O
PERATION AND CONTROLLER FUNCTIONS
X.CONTRL
Parametrization of the positioner
XXXX
XXXX
Insensitivity range (dead band) of the positioner
Entry of the dead band in %, referred to the scaled stroke range; i.e. LIM minus LIM (see function X.LIMIT). This function assures that the positioner cuts in only above a certain control difference. The function reduces wear on the solenoid valves in the TOP Control Continuous and the pneumatic actuator.
NOTE If, during execution of X.TUNE (AUTOTUNE of the positioner), the supplementary function
X.CONTRL is in the main menu, the dead band X.CO DBND is automatically determined in dependence on the frictional behaviour of the positioning mechanism. The value resulting is a guide value. It can be readjusted manually.
Xd1'
Position setpoint
(CMD)
Control difference
Xd1
Position actual value
(POS)
Dead band
Xd1
Parameters of the positioner
Gain factor of the positioner (to close the valve)
Gain factor of the positioner (to open the valve)
72 - 8630
End of parametrization of positioner. Jump back to X.CONTRL.
to controller
Xd1'
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
CODE
Code protection for the settings
Factory setting: CODE 0000
Locking of all functions that cloud change the operating status of the device. (The display on the display unit can be switched over).
Locking of the entry into the configuration level.
Locking of all actions (including bus parameterd and binary input) that change the operating status of the device. (The display on the display unit can be switched over.)
Entry of the 4-digit code.
If the code protection is activated, entry of the code will be demanded on every protected operative manipulation:
Change the flasching digit
Confirm the digit and switch to next digit
8630 - 73
O
PERATION AND CONTROLLER FUNCTIONS
SAFEPOS
Entering the safety position
Factory setting: 0 %
SAFEPOS SPOS XXX
Enter safety position (0 ... 100 %) *
* When the safety position is 0 % or 100 %, the actuator will be fully vented or pressurized as soon as the safety position is
activated int he supplementary function SIG-ERR or BIN-IN.
ATTENTION!
The safety position set is only moved to when a corresponding signal is present at the binary input (for configuration see BIN-IN), or on occurrence of a signal error (for configuration see SIG-ERR).
This function is executed only in the AUTOMATIC mode.
With the fast pressurize / fast vent variant, two valves are driven in each case to obtain faster pressurizing and venting.
74 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
SIG-ERR
Configuration of error recognition signal level
Activate signal error recognition
SIG-ERR
ERR INP INP ON
ERR P.INP
INP OFF
P.INP ON
P.INP OFF
Activate move to safety position
Configure error recognition of setpoint signal
SPOS ON
SPOS OFF
SPOS ON
Move to safety position if signal in error
Configure error recognition of process value signal
SPOS OFF
Move to safety position if signal error
ERR END
When signal error recognition is activated, the error is displayed (see chapter: Maintenance and Error
Correction).
NOTE Error recognition
Error recognition can be selected only with 4 ... 20 mA, Pt100 and P1’P2 signals.
4 ... 20 mA
Error in input signal
≤
3.5 mA (± 0.5 % of end value, hysteresis 0.5 % of end value)
Pt100
Error in input signal ≥ 225 °C (± 0.5 % of end value, hysteresis 0.5 % of end value)
P1’P2
Error in input signal ≤ 3.5 mA (± 0.5 % of end value, hysteresis 0.5 % of end value)
If other types of signal are selected or if the process controller is unactivated, the respective branch of menu will be faded out. If because of this configuration neither of the error recognition modes is possible, the message NOT.AVAIL
is displayed in the selection menu.
Safety position SPOS ON
If SPOS ON is set, the following configurations may occur:
Activated menu item SAFEPOS
On error recognition the actuatur moves to the position set under SAFEPOS.
Deactivated menu item SAFEPOS
On error recognition the actuator moves to the end position which it would assume in the zero-voltage state.
8630 - 75
O
PERATION AND CONTROLLER FUNCTIONS
BIN-IN
Activating the binary input
BIN-IN
Select the function of the binary input
B.IN SPOS
Safety position
B.IN M / A
Operating mode changeover
Type of binary input
NORM OPN
NORM CLS
NORM OPN
NORM CLS
Type of binary input normally closed
(0 ... 5 V = 1; 10 ... 30 V = 0) normally open
(0 ... 5 V = 0; 10 ... 30 V = 1)
Safety position B.IN SPOS
Moving to a safety position.
Activated menu item SAFEPOS
The actuator moves to the position set under SAFEPOS.
Deactivated menu item SAFEPOS
The actuator moves to the end position which it would assume in the zero-voltage state.
Switching over the operating mode B.IN M / A
Switching over the operating mode into MANUAL or AUTOMATIC.
Binary input = 0
Binary input = 1
Operating mode AUTOMATIC
Operating mode MANUAL
If the operating mode switchover has been selected, you can then no longer switch over the operating mode using the MANUAL/AUTOMATIC key.
76 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
OUTPUT (Option)
Configuration of the outputs
Configure the analog output
Configure binary output 1
Configure binary output 2
End of configuration of the outputs
OUT ANL - Standard signal for the analog position output
Selection of the desired output Selection of the desired standard signal
Actual position
Setpoint position
Actual value of process
Actual value of process
Current 4..20 mA
Current 0..20 mA
Voltage 0..10 V
Voltage 0..5 V
NOTE The signal types shown in gray are only selectable with active process controller.
8630 - 77
O
PERATION AND CONTROLLER FUNCTIONS
OUT BIN1 - Configuring binary output 1
Permissible actuating signal *
Limit position
NOTE NORM CLS (NC) "Normally Closed" output, in switched state low (
≅
0 V)
NORM OPN (NO) "Normally Open" output, in switched state high ( ≅
24 V)
78 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
BIN1 DEV.X
Selection: alarm output for too great an actuation signal from the positioner
* The permissible actuating signal DEV.X XXX shall not be smaller than dead band.
BIN1 LIM.X
Selection: binary position output
LIM.X XXX - limit position
OUT BIN1
POS > LIM
POS < LIM
NORM OPN
0 V
24 V
NORM CLS
24 V
0 V
BIN1 SPOS
Selection: actuator in safety position
BIN1 SIG
Selection: error message setpoint signal
BIN1 SIG.P
Selection: error message process value signal
BIN1 RMOT
Selection: operating mode AUTOMATIC and EXTERNAL Setpoint activated
OUT BIN1
Operating mode
AUTO +
External set-value
Operating mode
MANUAL or internal set-value
NORM OPN
0 V
24 V
NORM CLS
24 V
0 V
8630 - 79
O
PERATION AND CONTROLLER FUNCTIONS
OUT BIN2 - Configuring binary output 2
Permissible actuating signal *
Limit position
NOTE NORM CLS (NC) "Normally Closed" output, in switched state low ( ≅
0 V)
NORM OPN (NO) "Normally Open" output, in switched state high ( ≅
24 V)
80 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
BIN2 DEV.X
Selection: alarm output for too great an actuation signal from the positioner
* The permissible actuating signal DEV.X XXX shall not be smaller than dead band.
BIN2 LIM.X
Selection: binary position output
LIM.X XXX - limit position
OUT BIN2
POS > LIM
POS < LIM
NORM OPN
0 V
24 V
NORM CLS
24 V
0 V
BIN2 SPOS
Selection: actuator in safety position
BIN2 SIG
Selection: error message setpoint signal
BIN2 SIG.P
Selection: error message process value signal
BIN2 RMOT
Selection: operating mode AUTOMATIC and EXTERNAL Setpoint activated
OUT BIN2
Operating mode
AUTO + external set-value
Operating mode
MANUAL or internal set-value
NORM OPN
0 V
24 V
NORM CLS
24 V
0 V
8630 - 81
O
PERATION AND CONTROLLER FUNCTIONS
CAL.USER
Calibration of the actual value display, the inputs for position setpoint, process setpoint, process actual value and of the K factor for the valve
NOTE
82 - 8630
With the removal of the additional function CALUSER, the factory calibration will be re-established.
NOTE
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
The signal types shown in grey can be selected only with the process controller activated.
The signal surrounded by a dotted line can be selected only with the process controller deactivated.
The signal types in brackets are only shown in this menu; they cannot be changed here. The type of signal shown is that which you have selected in the associated menus:
CAL INP (CAL SP) Display of the selection in the menu INPUT
CAL PV Display of the selection in the menu P.CONTROL / P.CO INP
The signal types over a grey background can be selected only with the option flow rate controller.
CAL.POS
Calibration of the position display (0 - 100 %)
Storage of the minimum position:
Move to minimum position via arrow keys and confirm by pressing the MANUAL / AUTOMATIC key.
Storage of the maximum position:
Move to maximum position via arrow keys and confirm by pressing the MANUAL / AUTOMATIC key.
CAL INP
Calibration of the position setpoint (4 ... 20 mA; 0 ... 20 mA; 0 ... 5 V; 0 ... 10 V)
CAL SP
Calibration of the process setpoint (4 ... 20 mA; 0 ... 20 mA; 0 ... 5 V; 0 ... 10 V)
Menu point does not appear with selection of actual value frequency!
Storage of the minimum input signal (0 mA; 4 mA; 0 V):
Apply the minimum value of the standard signal to the input and confirm ist by pressing the MANUAL/
AUTOMATIC key.
Storage of the maximum input signal (20 mA; 5 V; 10 V):
Apply the maximum value of the standard signal to the input and confirm it by pressing the MANUAL/
AUTOMATIC key.
CAL PV
Calibration of the process setpoint (4 ... 20 mA; Pt-100)
This menu item does not appear on selection of frequency setpoint
Select 4 ... 20 mA:
Apply the minimum value of the process setpoint signal to the input and confirm the value by pressing the MANUAL/AUTOMATIC key.
Apply the maximum value of the process setpoint signal to the input and confirm the value by pressing the MANUAL/AUTOMATIC key.
Select Pt-100:
Alter the value displayed using the arrow keys until thedisplay on the SIDE Control S/HART agrees with that on the reference measuring instrument. Then confirm the value by pressing the MANUAL/
AUTOMATIC key.
8630 - 83
O
PERATION AND CONTROLLER FUNCTIONS
+ +
CAL P1, CAL P2, CAL TEMP
Calibrating the transmitter inputs at the flow rate controller (4 ... 20 mA)
Apply 4 mA to the input to be calibrated (p1/p2/temperature) and confirm the value by pressing the MANU-
AL/AUTOMATIC key.
Apply 20 mA to the input to be calibrated (p1/p2/temperature) and confirm the value by pressing the
MANUAL/AUTOMATIC key.
At the inputs p1/p2, 4 mA corresponds to a pressure of 0.0 bar (rel).
20 mA corresponds to a pressure of 10.0 bar (rel) or the end value set under CAL PLIM .
At the temperature input, 4 mA correspond to a temperature of 0°C.
20 mA correspond to a temperature of 150°C or the end value set under CAL TLIM .
+
CAL PLIM, CAL TLIM
Setting up the sensor measurement range
First, enter the lower pressure/temperature value that corresponds to the 4 mA transmitter signal. Then enter the upper pressure/temperature value that corresponds to the 20 mA transmitter signal.
PMIN must be within the range -1.01 ... 15.0 bar (rel), PMAX in the range 0.0 ... 16.0 bar (rel).
TMIN and TMAX must be within the 0 ... 150 °C range.
CAL P1P2
Balancing the pressure transmitters
The pressure transmitters p1 and p2 can be balanced in order to increase the measurement accuracy at small pressure differences. To do this, the feed line behind process valve must be closed, and a constant pressure must be applied to the controller unit.
With a pressure < 10 % of the sensor measurement range, the zero-point can be balanced, with a pressure > 55 % of the sensor measurement range, the upper calibration value.
Change the display between p1 and p2 using the arrow keys.
If you press the MANUAL/AUTOMATIC key, the displayed value will be confirmed and the other value will be matched to ist.
The process will be cancelled with the message P1P2 ERR if the pressure lies between 10 % and 55 % of the des sensor measurement range or if the difference between p1 and p2 > 1.5 %.
CAL FACT
Reset the settings under CAL.USER to the factory settings
Hold down the MANUAL/AUTOMATIC key until the countdown has expired.
84 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
SETFACT
Resetting to the factory settings
Using this function, all settings made by the user can be reset to the status existing on delivery.
All EEPROM parameters, with the exception of the calibration values, are reset to the default values.
Following this a hardware reset is executed.
5 s
To initiate the function, hold the MANU-
AL/AUTOMATIC key depressed for ca.
5 s until the countdown has finished.
8630 - 85
O
PERATION AND CONTROLLER FUNCTIONS
Operating the process
Each time after switching on the voltage supply, the TOP Control Continuous is automatically in the process operating level. To get there from the configuration level, confirm the menu item END by pressing the MANUAL/AUTOMATIC key.
In the process operating level, the normal controlled operation is executed and monitored (in the
AUTOMATIC mode), and the valve opened or closed by hand (MANUAL mode).
Changeover between operating modes
5 sec
Operate the MANUAL/AUTOMATIC key to switch between the MANUAL and AUTOMATIC modes.
Both in the MANUAL and the AUTOMATIC modes, you can change to the configuration level by pressing the MANUAL/AUTOMATIC key for longer than 5 seconds. On switching back to the process operating level, the operating mode is resumed that was set before switching over.
Operating mode
AUTOMATIC
MANUAL yellow LED in the
MANUAL/AUTOMATIC key flashes
Display off -
An apostrophe (') runs continuously from left to right.
86 - 8630
O
PERATION AND
C
ONTROLLER
F
UNCTIONS
Operating mode AUTOMATIC
(yellow LED flashes)
In the AUTOMATIC mode, normal controlled operation is executed and monitored.
Meaning of the keys in the AUTOMATIC mode:
or Switch over the display or
> 3 s
Change the process setpoint: with configured supplementary functions P.CONTRL / P.CO SETP / SETP INT and display set to SP
Display of the AUTOMATIC mode
With regard to the positioner, the following parameters can be displayed:
• Actual position of valve actuator POS__XXX (0 ... 100 %)
• Setpoint position of valve actuator after rescaling through optionally activated split-range function or correction characteristic:
• Input signal for setpoint position:
• Temperature inside housing of TOP Control Continuous
CMD__XXX (0 ... 100 %)
INP__XXX
(0 ... 5/10 V or 0/4 ... 20 mA)
TEMP_XX.X (in °C)
By pressing the arrow keys, you can switch between these 4 display options.
AUTOMATIC mode
Configuration
Menu item
END
Switch over display or
(> 5 sec.)
No operating action
Release key
MANUAL mode
NOTE If the device is in the safety position (for the relevant configuration, see menu item BIN-IN or SIG-ERR), SAFE XXX appears in the display.
If the menu item CUTOFF is activated and the process vave is in the tight-closing range, a flashing MIN or MAX symbol appears in the display.
8630 - 87
O
PERATION AND CONTROLLER FUNCTIONS
Operating mode MANUAL
(yellow LED off)
In the manual mode, the valve can be opened and closed by hand.
Meaning of the keys in the MANUAL mode:
+
+
Press the key in the MANUAL mode:
Pressurization of the actuator
SFA: valve opens
SFB: valve closes
SFI: port 2.1 pressurized
Press the key in the MANUAL mode:
Venting of the actuator
SFA: valve closes
SFB: valve opens
SFI: port 2.2 pressurized
Hold down the key and simultaneously press the :
Fast pressurization
Hold down the key and simultaneously press the :
Fast venting
NOTE SFA: actuator closing by spring force
SFA: actuator opening by spring force
SFI: actuator with double action
Displays of the MANUAL mode:
The last display set in the AUTOMATIC mode is shown.
By selecting POS_XXX, the actual position of the valve actuator can be checked.
AUTOMATIC mode
88 - 8630
MANUAL mode
Valve closes at normal speed
Release key release
Valve closes fast
No operating action
(> 5 sec.)
Menu item
END
Configuration
Release key
Valve opens at normal speed release
Valve opens fast
O
PERATING THE PROCESS CONTROLLER
OPERATING THE PROCESS
CONTROLLER
Factory settings on the process controller
................................................................................................................................................
90
Setting up a process control system
..................................................................................................................................................................
90
Self-parametrization for positioner - X.TUNE
.......................................................................................................................................
91
Supplementary function P.CONTRL
.................................................................................................................................................................
91
Basic settings of the function P.CONTRL
.....................................................................................................................................................
92
P.Q’LIN - Starting the routine for linearization of the process curve
................................................................
105
Display during call-up and execution of the routine
......................................................................................................................
105
P.CO TUNE - Self-optimization of the process controller (process tune)
................................................
106
P.CO LEAK - Leakage characteristic for flow rate control
..............................................................................................
110
Operating the process
..........................................................................................................................................................................................................
112
Changeover between the operating modes
...........................................................................................................................................
112
Operating mode AUTOMATIC
..................................................................................................................................................................................
113
Meaning of the keys
.............................................................................................................................................................................................................
113
Displays
...............................................................................................................................................................................................................................................
113
Operating structure and procedures
...............................................................................................................................................................
113
Manually changing the process setpoint
.................................................................................................................................................
114
Operating mode MANUAL
.............................................................................................................................................................................................
114
Meaning of the keys
.............................................................................................................................................................................................................
114
Displays
...............................................................................................................................................................................................................................................
115
Operating structure and procedures
...............................................................................................................................................................
115
8630 - 89
O
PERATING THE PROCESS CONTROLLER
Factory settings on the process controller
Factory setting Function
P.CONTRL
P.CO DBND
P.CO PARA
KP
TN
TV
X0
P.CO SETP
P.CO INP
P.CO FILT
P.CO SCAL
P.CO TUNE
P.CO KV
1 %
1.00
999.9
0.0
0
SETP INT
INP 4´20 A
0
PV 000.0,
PV 100.0
D’ACT
FACT
Function Factory setting
P.CONTRL with flow rate controller
P.CO DBND 1 %
P.CO PARA
KP 1.0
999.9, TN
TV
X0
0.0
0
P.CO SETP
P.CO INP
P.CO FILT
P.CO SCAL
SETP INT
INP P1’P2
0
PV 000.0, PV 100.0,
P.TYP
UNIT
TEMP
DENS
DIAM
P.CO TUNE
FLOW
M3/H,
MAN
1.293,
0025
D’ACT
P.CO KV FACT
NOTE The functions and factory settings shown in grey are valid for the optional flow rate control.
Setting up a process control system
In order to be able to operate the TOP Control Continuous as a process controller, you must execute the following steps:
➔ In all cases, carry out the self-parametrization for positioners ( X.TUNE).
➔
Via the configuration menu, add the supplementary function P.CONTRL to the main menu.
With the function P.CONTRL, the function P.Q'LIN is also inserted into the main menu.
➔ Call up the basic settings for the process controller under P.CONTRL.
Linearization of the process characteristic:
If you are dealing with a flow control system, the process characteristic can be linearized automatically:
➔ Initiate the function P.Q’LIN.
Self-optimization of the process controller
➔
Activate the function P.CO TUNE and initiate self-optimization of the PID parameters of the process controller.
Activate valve characteristic curve
➔ Initiate the function P.CO KV to activate the valve characteristic.
Read in leakage characteristic
➔ Initiate automatic determination of the leakage characteristic using the functions
P.CO LEAK ➔ P.CO MEAS .
ATTENTION!
In all cases, keep to the following sequence! X.TUNE
➔ P.Q’LIN ➔ P.CO TUNE
90 - 8630
O
PERATING THE PROCESS CONTROLLER
Self-parametrization of the positioner - X.TUNE
The description of the self-optimization of controllers is to be found in the chapter Operating and
Controller Functions / Commissioning and Setting Up as a Positioner / Main Menu for the Settings on
Commissioning / X.TUNE.
Supplementary function P.CONTRL
(see also the section „Operating the positioner - configuring the supplementary functions“)
Parametrization of the PID controller
8630 - 91
O
PERATING THE PROCESS CONTROLLER
Basic settings of the function
P.CONTRL
Parametrization of the process controller
Insensitivity range (dead band) of the PID process controller
Parameters of the PID process controller
Type of setpoint setting
Specification of the signal type for process actual value
Filtering of the process actual value input
Scaling of the process controller
Self-optimization of the process controller
(process tune) kv characteristic curve of process valve
Leakage characteristic for flow rate control
Storage of the new parameters
End of the parametrization
92 - 8630
O
PERATING THE PROCESS CONTROLLER
P.CO - DBND
Insensitivity range (dead band) of the process controller
Factory setting: 1% (refers to the span of the process actual value scaled by means of SCAL PV and PV )
This function assures that the process controller cuts in only above a certain control difference . The function reduces wear on the solenoid valves in the TOP Control Continuous and the pneumatic actuator.
Entering the dead band in %
Insensitivity range with process control
Process setpoint
(SP)
Control difference
Xd2
Process actual value
(PV)
Xd2'
Dead band
Xd2 to controller
Xd2'
8630 - 93
O
PERATING THE PROCESS CONTROLLER
P.CO - PARA
Parameters of the PID process controller
Gain factor of the process controller
0 ... 99.99 (factory setting 1.00)
Reset time
0.5 s ... 999.9 s (factory setting 999.9 s)
Rate time
0 s ... 999.9 s (factory setting 0 s)
Operating point
0.0 ... 100 % (factory setting 0 %)
NOTE For self-optimization of the PID parameters, see Step
The parameters entered should be noted in the table in the Appendix Tables for process controller.
For definition of the parameters of a PID controllers, see Appendix General rules.
P.CO - SETP
Type of setpoint setting (internal/external)
Setpoint setting internally via the keys on the TOP
Control Continuous.
Setpoint setting externally via the standard signal input.
94 - 8630
O
PERATING THE PROCESS CONTROLLER
P.CO - INP
Specification of the signal type for process actual value
Frequency signal (flow rate) 0 ... 1000 Hz
Connection with Pt100 (temperature)
- 20 °C ... + 220 °C
Configuration for flow rate controller - option standard signal current 4 ... 20 mA (flow rate, pressure, level)
P.CO - FILT
Filtering of the process actual value input
Factory setting: 0
Valid for all types of process actual value.
Filter has low-pass behavior (PT1).
Range: 0 ... 9
FILT XX
Setting in 10 steps: 0 ... 9
Setting in 10 steps
Setting
6
7
4
5
8
9
0
1
2
3
Corresponds to limiting frequency (Hz)
10
5
2
1
0.5
0.2
0.1
0.07
0.05
0.03
Effect minimum filtering maximum filtering
8630 - 95
O
PERATING THE PROCESS CONTROLLER
P.CO SCAL
Scaling the process controller on selection of analog input 4 ... 20 mA (P.CO INP 4 - 20 A)
XX.XX
XX.XX
XX.XX
XX.XX
Position of the decimal point for process actual value and setpoint (Setting range: 0..3)
Lower scaling value for process actual value (process value); the value is assigned to 4 mA. (*)
Upper scaling value for process actual value (process value); the value is assigned to 20 mA. (*)
Lower scaling value for process setpoint; the value is assigned to the smallest current or voltage value of the standard signal. (**)
Upper scaling value for process setpoint; the value is assigned to the largest current or voltage value of the standard signal.
(**)
(*) This setting determines the reference span for the dead-band of the process controller and the analog feedback of the process actual value (option).
(**) This setting is only active when P.CO SETP / SETP EXT is selected.
96 - 8630
O
PERATING THE PROCESS CONTROLLER
Example of scaling for 4 ... 20 mA input:
Process actual value from transmitter :
Process setpoint from SPS:
4 ... 20 mA corresponds 0 ... 10 l/min
4 ... 20 mA corresponds 0 ... 8 l/min
Scaling value
[l/min]
Process actual value
Process setpoint
Example for entering scaling values
PV
PV
SP
SP
Variant 1 Variant 2 Variant 3
0
1.0
0
0.8
0
10.0
0
8.0
0
100.0
0
80.0
Input signal
[mA]
NOTE
On entering small scaling values, decimal places are automatically added to increase the precision of display, such that the maximum possible digit range is given between the lower and upper scaling values in each case. The amplification factor KP of the process controller refers to the scaling values set.
With P.CO SETP / SETP INT (setpoint entry via the arrow keys), scaling of the setpoint via
SP and SP is not possible. The setpoint may be entered directly corresponding to the scaled process variable (PV , PV ).
8630 - 97
O
PERATING THE PROCESS CONTROLLER
P.CO SCAL
Scaling the process controller on selection of the frequency input
(P.CO INP FREQ)
NOTE On entry into this menu the valve is closed in order to have a well-defined starting conditions for execution of the teach-in function.
Unit l/s
Unit l/min
Unit m³/min
Unit m³/h
Unit gal(US)/s
Unit gal(US)/min
Unit gal(US)/h
Unit gal(Imperial)/s
Unit gal(Imperial)/min
Unit gal(Imperial)/h
98 - 8630
O
PERATING THE PROCESS CONTROLLER
Position of the decimal point for process actual value and setpoint
(Setting range: 0 ... 3).
Lower scaling value for process actual value; the value is entered in the unit that subsequently selected for the flow rate. This setting determines the reference span for the dead-band of the process controller and the analog feedback of the process actual value (option).
Upper scaling value for process actual value; the value is entered in the unit that is subsequently selected for the flow rate. This setting determines the reference span for the dead-band of the process controller and the analog feedback of the process actual value (option).
Lower scaling value for process setpoint; the value is assigned to the minimum current or voltage value of the standard signal. This setting is active only when P.CO SETP / SETP EXT has been selected.
Upper scaling value for process setpoint; the value is assigned to the maximum current or voltage value of the standard signal. This setting is active only when P.CO SETP / SETP EXT has been selected.
Setting the desired unit of the flow rate
Manual entry of the K factor for the flow rate sensor
(e.g. from the data sheet for the flow rate sensor)
Position of the decimal point for the K factor (setting range: 0 ... 2)
K factor (setting range: 0 ... 9999)
8630 - 99
O
PERATING THE PROCESS CONTROLLER
Teach-In funktion:
Calibration of the k factor by measurement of a certain quantity of fluid.
Start of measurement
Open the valve. Close the valve when the tank is filled.
Use the arrow keys for opening and closing the valve. For this the valve must not be fully open.
End of measurement
Position of the decimal point for entry of the volume measured
(setting range: 0..3).
Enter the volume measured (setting range: 0..9999).
Unit as selected before under UNITXXXX.
Display of the calculated K factor.
100 - 8630
O
PERATING THE PROCESS CONTROLLER
P.CO SCAL
Scaling the process controller on selection of Pt 100 input
(P.CO INP PT100)
Position of the decimal point
(Setting range: 0... 3)
Lower scaling value for process actual value the value is entered in the unit that is subeequently selected for the flow rate. (*)
Upper scaling value for process actual value
the value is entered in the unit that is subsequently selected for the flow rate. (*)
Lower scaling value for external process setpoint the value is assigned to the minimum current or voltage value of the standard signal. (**)
Upper scaling value for process setpoint the value is assigned to the maximum current or voltage value of the standard signal. (**)
Setting the desired unit of temperature
Unit °C
Unit °F
(*) This setting determines the reference span for the dead-band of the process controller and the analog feedback of the process actual value (option).
(**) This setting is only active when P.CO SETP / SETP EXT is selected.
8630 - 101
O
PERATING THE PROCESS CONTROLLER
P.CO SCAL
Scaling the process controller on selection of the p
1
(P.CO INP P1’P2)
/p
2
input
Position of the decimal point
(Setting range: 0 ... 3)
Lower scaling value for process value -
The value is entered in the unit that is subsequently selected for the flow rate. (*)
Upper scaling value for process value -
The value is entered in the unit that is subsequently selected for the flow rate. (*)
Lower scaling value for external process setpoint The value is assigned to the minimum current or voltage value of the standard signal.
(**)
Upper scaling value for process setpoint The value is assigned to the maximum current or voltage value of the standard signal. (**)
Display of the flow rate As a transport velocity in m/s
(e.g. with bulk goods) or as a volumetric flow rate in m³
N
/h
Temperature of the medium – Activate the temperature transmitter (optional) or enter the temperature value.
Temperature default value from the Master as process data output (for PROFIBUS DP or DeviceNet).
Medium density (kg/m³) under standard conditions
Diameter of piping in the pumping section (mm)
A dialog appears only when transport velocity (Velocity) has been selected as a process parameter.
(*) This setting specifies the reference range for the deadband of the process controller and for the analog display of the process value (option).
(**) This setting is active only when P.CO SETP/SETP EXT has been selected.
102 - 8630
O
PERATING THE PROCESS CONTROLLER
P.CO TUNE
Activating the self-optimization of the process controller (process tune)
Activate process tune
Select controlled member
NOTE Process tune is started in the operating mode AUTOMATIC.
Controlled member unknown
Flow rate control
Temperature control
Pressure control
Filling level control
P.CO KV
Display or enter kv characteristic curve of the process valve
(option flow rate controller)
Enter user-defined kv curve
Display factoryset kv curve
No. of places after the decimal point for entry of kv curve.
Display/enter kvs value in m 3 /h
Display/enter kv curve in %, referred to the kvs value
8630 - 103
O
PERATING THE PROCESS CONTROLLER
P.CO LEAK
Reading-in of the leakage characteristic (Flow rate control option)
Deactivate leakage characteristic
Activate leakage characteristic
Release
Start automatic determination of the leakage characteristic
*Show the leakage characteristic display
Reference points are displayed alternately as conveyance pressure in mbar and air flow or conveyance speed in m 3 /h or m/s respectively.
NOTE To interrupt the leakage determination, press both arrow buttons simultaneously and select
LEAK BRK.
104 - 8630
O
PERATING THE PROCESS CONTROLLER
P.Q’LIN
Starting the routine for linearization of the process curve
This function makes sense only when flow control is to be carried out.
➔ You start the routine for linearization of the process characteristic by calling up the menu item P.Q’LIN in the main menu and pressing the MANUAL/AUTOMATIC key for 5 seconds.
NOTE The function P.Q’LIN can only be started when the menu item P.CONTRL / P.COINP /
INP FREQ or item P.CONTRL / P.COINP / INP420 has been selected.
With the activation of the function P.CONTRL, the functions P.Q’LIN, which are required for process control, are copied into the main menu. Via these functions, the program is started for autonomous determination of the fixed points for a correction characteristic.
The program increases in 20 steps the valve stroke from 0 to 100 % and measures the associated process variables. The pairs of values of the correction characteristic are stored as a freely programmable characteristic under the menu item CHARACT/CHAFREE and may be viewed under this menu item.
If the menu item CHARACT was not transferred under the menu item ADDFUNCT to the main menu, this is done automatically on execution of the function P.Q’LIN. At the same time, the menu item
CHARACT/CHAFREE is activated.
Display during call-up and execution of the routine
Display
P.Q’LIN 5
P.Q’LIN 4
:
P.Q’LIN 0
¦ P.Q’LIN 0
¦ P.Q’LIN 1
¦ P.Q’LIN 2
¦ P.Q’LIN 3
:
P.Q’LIN.END
Q.ERR X.X
Description
Countdown from 5 to 0 for starting der Routine
Display of the fixed point that is being approached at the moment
(der Fortgang wird durch einen sich drehenden Balken am linken
Rand des Displays angezeigt)
(flashing) End of routine
Message on occurrence of an error
(shown on the right is the error number - see chapter Maintenance process controller)
8630 - 105
O
PERATING THE PROCESS CONTROLLER
P.CO TUNE
Self-optimization of the process controller (process tune)
The control system TOP Control Continuous is equipped with a positioner which if required can be supplemented by a superimposed process controller (see chapter: Operation as a Process Controller).
The positioner controls the position of the process valve to the desired setpoint and is automatically parametrized and optimized by the X.TUNE function.
The superimposed process controller, which together with a sensor forms a process control loop, can control any process parameter. It has a PID structure whose components may be combined in various ways (P, PI, PD, PID), and freely parametrized (KP, TN, TV).
In order to obtain good control behaviour, the structure of the controller must be adapted to the characteristics of the process (controlled member). The parameters must be chosen to obtain a short setting time, a small overshoot width and good damping.
Parametrization demands experience in control tecnique, measuring equipment and is time consuming.
For this reason, TOP Control Continuous has a self-optimization function P.TUNE. This function provides an unique, direct determination of the parameters. The results may be read out as needed and modified in any way desired.
METHOD OF OPERATION
During commissioning of the control system, the process is excited by a step in the setpoint in a closed control loop. This step is carried out within the future working range of the process control system and serves to determine characteristic variables of the process. Calculation of the PID controller parameters is carried out on the basis of these characteristic variables by use of a modified Ziegler-Nichols procedure.
SETPOINT MODULATOR
In addition to optimization of the PID parameters, a setpoint modulator (filter) is calculated for the reduction of unwanted non-linear effects. Such effects may arise because of physical limitation of the correcting variables and the floating time of the control valve.
The setpoint modulator further improves the control behaviour. It is activated as long as the P.TUNE
function is activated in the operating menu of the TOP Control Continuous ( P.TUN ACT ). When the function P.TUNE is deactivated in the operating menu ( P.TUN D’ACT ) after completion of selfoptimization, the process is controlled with the optimized PID parameters and the setpoint modulator is deactivated.
ATTENTION!
Be sure to comply with the sequence ... on setting up the process control system!
106 - 8630
O
PERATING THE PROCESS CONTROLLER
Operation
To carry out self-optimization (process tune) on the process controller, proceed as follows with the steps
... described.
NOTE All operating steps for the execution of process tune are performed on the spot using the operating elements (keypad and display) of the TOP Control Continuous.
Step - Activate process tune
You are in the menu item P.CONTROL in the configuration level of the TOP Control Continuous.
Activate process tune on the process controller P.TUN ACT and select the process type corresponding to your control job.
If the process is unknown, enter P.TYP N.DEF (not defined).
Activate process tune
Select the controlled member
Controlled member unknown
Flow rate control
Temperature control
Pressure control
Filling level control
Change to the process operation level by leaving the configuration level via the menu item END X.XX
and switching the device to the operating mode AUTOMATIC (yellow LED in the MANUAL/AUTOMATIC key flashes).
8630 - 107
O
PERATING THE PROCESS CONTROLLER
Step - Process tune ready to start
You are in the process operating level in the AUTOMATIC mode (yellow LED in the MANUAL/
AUTOMATIC key flashes).
Make ready process tune by the following operating procedure:
Make ready P.TUNE
(process tune) process tune ready process tune not ready
The next setpoint step entered via the keypad (see Step ) is now used for parameter optimization. The setpoint SP is set equal to the actual sensor value PV and is the starting value for the optimization step.
Adaptation/modification of this starting value is described in Step .
Readiness of process tune is symbolized int he display by three horizontal bars behind the flashing setpoint symbol SP.
Step - Adaptation of the starting value for the optimization step (optional)
If required you can carry out an adaptation of the starting value for the optimization step. Switch the device to the MANUAL mode (LED in the MANUAL/AUTOMATIC key is off). By pressing the arrow keys, open or close the process valve, which causes a corresponding change in the process value PV. As soon as the desired starting value is set, switch the device back to the AUTOMATIC mode.
Step - Initiate process tune
You are in the process operating level in the AUTOMATIC mode (yellow LED in the MANUAL/
AUTOMATIC key flashes).
Process tune is now initiated by entering via the keypad a setpoint step. This step should take place in the future working range of the process control system.
The procedure is as follows: or
> 3 s or
With the display SP (setpoint) set, press one of the arrow keys for longer than 3 seconds to activate the mode for changing the process setpoint. After release of the key, the first digit of the process setpoint flashes.
Set the value of the flashing digit of the process setpoint SP.
Confirm the value set and move to the next digit. After confirmation of the fourth digit, the process setpoint set is stored as the end value of the process setpoint step.
108 - 8630
O
PERATING THE PROCESS CONTROLLER
NOTE
The setpoint step for parameter optimization must always be entered via the operating keypad. This also applies when, on configuration, the function P.CONTRL / P.CO SETP /
SETP EXT (setpoint setting via analog input) is specified. In this case, the external setpoint setting is reactivated only after completion of process tune.
Self-optimization of the process controller now runs automatically. The display shows a rotating bar and the message P.TUNE. After completion of process tune, the device is in the AUTO mode. The process controller works from this point on with the optimized PID parameters and controls to the current, internal or external setpoint SP.
To execute a new optimization cycle, repeat Steps ... .
NOTE The Process Tune in the conrol menu of the TOP Control Continuous remains active, so that the process control takes place with the Set-value-Modulation (Filer) for the reduction of unwanted, non-linear effects. If the control will be carried out without the Set-value-Modulator, the process tune in the control menu must be deactivated: P.CONTRL / P.CO TUNE / P. TUN
D´ACT
To stop the self-optimization, press both arrow keys at the same time and select
P.TUN BRK.
8630 - 109
O
PERATING THE PROCESS CONTROLLER
P.CO LEAK Leakage characteristic for flow rate control (Flow rate control option)
The program function P.CO LEAK enables air leakage compensation, which increases the accuracy of the flow rate control.
Background: during transport of pourable solids, there arises at a cellular wheel sliuce an air leakage dependent on the pressure. The air flow through the controller unit is the sum of this leakage and the air flow of the conveying pipe.
QFMR = Q air leak
+ Q conv. pipe
To achieve an air leakage compensation, an air leakage characteristic must be read-in once with the conveying pipe closed.
Reading-in of the leakage characteristic
Boundary conditions
For exact measurement of the leakage, the system should be started up in the normal mode.
However, the following exceptions apply:
•
The conveying pipe must be closed off behind the components causing the leak.
•
The material to be transported is omitted.
ATTENTION!
•
In the case of pneumatic conveying of pourable solids with a rotary valve, the following must be observed:
•
The conveying pipe must be closed off behind the rotary valve.
•
The rotary valve must be empty and run at the nominal rpm..
•
Measures for sealing the system (e. g. blocking air that enters from above into the rotary valve) must be connected.
•
The compressor must be switched on.
Measurement and reading-in of the leakage characteristic
Select program to initiate automatic recording of leakage characteristic using
P.CONTRL
P.CO LEAK P.CO MEAS menu
Press and hold the button for 5 seconds.
The leakage characteristic is now automatically captured and read-in.
Display
TUNE 5
TUNE 4
:
TUNE 0
LEAK IN
LEAK PO
LEAK OPN
LEAK PAR
LEAK END
L.ERR X
Description
Countdown from 5 to 0 to the start of leakage determination
Display of the momentarily running phase of leakage determination
(progress is indicated by a rotating beam at the left hand edge of the display)
Display flashes. Leakage determination successfully completed
Display on occurrence of an error (display on the right: error number, see chapter Maintenance and Troubleshooting in the controller manual)
NOTE Press both buttons simultaneously to interrupt the determination of the characteristic and select LEAK BRK .
110 - 8630
O
PERATING THE PROCESS CONTROLLER
Program sequence
•
The control valve is closed.
•
After 10 sec settling time, the admission pressure at the controller unit (FMR) is registered.
NOTE Scaling of the x-axis of the leakage characteristic is based upon this pressure value. The upper limit is this value times a factor of 0.85
Up to 21 reference points are determined.
Example: at an admission pressure of 2.0 bar, the characteristic curve is obtained from 0 to
1.7 bar in 85 mbar steps.
•
The control valve is slowly opened in a ramp time of 60 sec.
•
Parallel to this, the conveyance pressure (pressure at the outlet side of the FMR) is monitored.
For each reference point of the characteristic, the conveyance pressure and the air flow are registered.
•
Reading in is complete when after 60 sec the contol valve is fully open, or the conveyance pressure previously reaches the uper limit of the scaling.
•
Air leakage compensation is now activated. The process value is now obtained from the difference between the measured air flow and the air leak rate calculated from the characteristic:
Q conv. pipe
= Q
FMR
- Q air leak
Deactivate leakage characteristic
Activate leakage characteristic
Release
Start automatic determination of the leakage characteristic
*Show the leakage charateristic display.
* Reference points are displayed alternately as conveyance pressure in mbar and air flow or conveyance speed in m 3 /h or m/s respectively.
Deactivation of the characteristic curve
The leakage characteristic that has been read-in can be deactivated using the function LEAK D'ACT in the
P.CO LEAK menu.
8630 - 111
O
PERATING THE PROCESS CONTROLLER
Operating the process
Each time after switching on the voltage supply, the TOP Control Continuous is automatically in the process operating level. To change to the process operating level from the configuration level, confirm the menu item END by pressing the MANUAL/AUTOMATIC key.
In the process operating level, normal controlled operation is executed and monitored (in the
AUTOMATIC mode), and the valve opened or closed by hand (MANUAL mode).
Switching between the operating modes
5 sec
Operate the MANUAL/AUTOMATIC key to switch between the MANUAL and
AUTOMATIC modes.
Both in the MANUAL and the AUTOMATIC modes, you can change to the configuration level by pressing the MANUAL/AUTOMATIC key for longer than 5 seconds. On switching back to the process operating level, the operating mode is resumed that was set before switching over.
Operating mode
AUTOMATIC
MANUAL
Yellow LED in the
MANUAL/AUTOMATIC key flashes
Display off -
An apostrophe (') runs continuously from left to right.
112 - 8630
O
PERATING THE PROCESS CONTROLLER
Operating mode AUTOMATIC
In the AUTOMATIC mode, normal controlled operation is executed and monitored.
Meaning of the keys
or Switch over the display or
> 3 sec and
Change the process setpoint
With configured supplementary functions P.CONTRL/P.CO SETP/SETP INT and SP display set.
Make P.TUNE (process tune) ready for start.
With PID self-optimization activated, P.CONTRL/P.CO TUNE/ P.TUN ACT
Displays
With the process controller activated, the following parameters can be displayed:
• Actual value of process variable (process value) PV_____ (- 999 ... 9999)
• Setpoint of process variable (process setpoint) SP_____ (- 999 ... 9999)
• Setpoint position of valve actuator after rescaling through optionally activated split-range function or correction curve
• Temperature inside housing of the TOP Control Continuous
CMD __XXX (0 ...100 %)
TEMP__XX.X (in °C)
By pressing the arrow keys, you can switch between these display options.
Operating structure and procedures
PV_____
SP_____
POS__XXX
CMD __XXX
TEMP__XX.X
AUTOMATIC mode
Switch over display
Configuration
Menu item
END and
P.TUNE
(process tune) ready for start or
Release key
(> 5 s)
No operating action
SP active or
(> 3 s)
Set the process setpoint
Release key
P.TUNE
(process tune)
MANUAL mode
NOTE If the device is in the safety position (for the relevant configuration, see menu item BIN-IN or SIG-ERR), SAFE XXX appears in the display.
If the menu item CUTOFF is activated and the process vave is in the tight-closing range, a flashing MIN or MAX symbol appears in the display.
If the process value ( PV) is above or below the measurement range, a flashing bar appears in the display.
8630 - 113
O
PERATING THE PROCESS CONTROLLER
Manually changing the process setpoint
or
> 3 sec or
If the supplementary function P.CONTRL / P.CO SETP / SETP INT (setting of the setpoint via keys) was specified on configuration, then with the display
SP set (setpoint) and on pressing one of the arrow keys for longer than 3 seconds, the mode for changing the process setpoint can be activated. After release of the key, the first digit of the process setpoint flashes.
The first digit of the process setpoint can be set.
After confirmation with the MANUAL/AUTOMATIC key, the set value is stored.
In the same manner, the other digits are set. After confirmation of the last digit, the display returns to the previous mode.
Operating mode MANUAL
(yellow LED off)
In the manual mode, the valve can be opened and closed by hand.
Meaning of the keys in the MANUAL mode:
+
+
Press the key in the MANUAL mode:
Pressurization of the actuator
SFA: valve opens
SFB: valve closes
SFI: port 2.1 pressurized
Press the key in the MANUAL mode:
Venting of the actuator
SFA: valve closes
SFB: valve opens
SFI: port 2.2 pressurized
Hold down the key and simultaneously press the :
Fast pressurization
Hold down the key and simultaneously press the :
Fast venting
NOTE SFA: actuator closing by spring force
SFA: actuator opening by spring force
SFI: actuator with double action
114 - 8630
O
PERATING THE PROCESS CONTROLLER
Displays
The last display set in the AUTOMATIC mode is shown.
By selecting PV_XXX, the actual value of the process variable can be checked.
To display the actual position of the valve actuator during MANUAL operation, change to the display
POS_XXX in advance in the AUTOMATIC mode.
Operating structure and procedures
AUTOMATIC mode
MANUAL mode
Valve closed at normal speed
Release key
No operating action
Release key
Valve opens at normal speed
Valve closes fast release (> 5 sec.)
Menu item
END
Configuration
Valve opens fast release
8630 - 115
O
PERATING THE PROCESS CONTROLLER
116 - 8630
P
ROFIBUS
DP
PROFIBUS DP
General notes
...................................................................................................................................................................................................................................
118
Technical data
..................................................................................................................................................................................................................................
118
Safety settings on bus failure
....................................................................................................................................................................................
118
Interfaces
..................................................................................................................................................................................................................................................
119
Electrical connections
..........................................................................................................................................................................................................
119
Connection with one plugged bus connector
.......................................................................................................................................
119
Connection with 2 plugged bus connectors
...........................................................................................................................................
120
Operating voltage (circular plug M12)
...........................................................................................................................................................
120
Bus connection (circular socket M12)
..........................................................................................................................................................
120
Inductive proximity switches (circular socket M8)
........................................................................................................................
121
Process value (circular plug M8)
.........................................................................................................................................................................
121
Termination connection for Profibus systems
.....................................................................................................................................
122
Settings on the TOP Control Continuous
................................................................................................................................................
123
Explanation of the menu items
................................................................................................................................................................................
124
Functional deviations from the standard version
.........................................................................................................................
124
Configuration in the PROFIBUS DP master
......................................................................................................................................
125
Configuration of the process values
................................................................................................................................................................
125
Bus status display
......................................................................................................................................................................................................................
127
Example 1 with COM-Profibus V3.3
...............................................................................................................................................................
128
Example for a positioner
.................................................................................................................................................................................................
128
Example 2 with COM-Profibus V3.3
...............................................................................................................................................................
131
Example for a process controller
.........................................................................................................................................................................
131
8630 - 117
P
ROFIBUS
DP
General notes
he following functions are invalid for the TOP Control Continuous with PROFIBUS DP:
• INPUT
• CAL.USER / CAL INP
• CAL.USER / CAL OUT
• CAL.USER / CAL SP
Technical data
The protocol sequence corresponds to DIN 19245 Part 3.
GSD file
Bitmap files
PNO-ID
Baud rate
Sync and freeze mode
Diagnosis telegram
Parameter telegram
BUERC630.GSD
BUEC630.DIB
BUEC630N.BMP (for Siemens COM-PROFIBUS)
BUEC630D.BMP (for Siemens COM-PROFIBUS)
C630 Hex max. 1.5 Mbaud
(automatically set by TOP Control Continuous) not supported no device-specific diagnosis no user parameters
Configuration of the process data is performed in the TOP Control and in the PROFIBUS Master.
A maximum of 10 process values (sum of input and output) can be transferred.
Safety settings on bus failure
The actuator moves to the position corresponding to the setpoint last transmitted (default setting).
For other setting options (see the chapter Settings on the TOP Control Continuous)
118 - 8630
P
ROFIBUS
DP
Interfaces
Bus
Inputs for process actual value
4 ... 20 mA
Frequency
Pt 100
Bus
Initiators 1-2
24 V DC
Operating unit
Electrical connections
For operating the device it is imperative to connect the 5-pole, inverse-coded M12 circular socket connector and the 4-pole M12 circular plug connector (voltage supply).
Connection with one plugged bus connector
M8 plug,
4-pole
(process value)
M12 plug
4-pole
(operating voltage)
M12 socket
5-pole inverse coded
(Profibus DP)
M8 socket,
4-pole
(initiators)
8630 - 119
P
ROFIBUS
DP
Connection with 2 plugged bus connectors
M12 plug,
5-pole inverse coded
(Profibus DP)
M12 socket,
5-pole inverse coded
(Profibus DP)
M12 plug,
4-pole
(operating voltage)
Operating voltage (circular plug M12, 4-pole)
External connection Pin
1
2
3
4
Allocation
+ 24 V not connected
GND not connected
Bus connection (circular socket/plug M12, 5-pole)
Pin Signal
1 VP+5
Meaning
Supply for terminating resistors
2 RxD/TxD-N Received/transmitted data (minus)
3 DGND Data transmission potential (mass to 5 V)
4 RxD/TxD-P Received/transmitted data (plus)
5 Screen Screen/protective earth (ground)
120 - 8630
P
ROFIBUS
DP
Inductive proximity switches (circular socket M 8)
Signal level Pin
1
2
3
4
Allocation
Proximity switch 1 + (NO)
Proximity switch 1 GND
Proximity switch 2 + (NO)
Proximity switch 2 GND
Process value (circular plug M 8)
Input type *
4 ... 20 mA
- internally
supplied
4 ... 20 mA
- externally
supplied
Frequency
- internally
supplied
Frequenz
- externally
supplied
Pt-100
(see
Note below)
3
4
1
2
3
4
1
2
Pin Assignment
3
4
1
2
3
4
1
2
3
4
1
2
+ 24 V input transmitter output transmitter
GND bridge after GND not assigned process actual + not assigned process actual -
+ 24 V - sensor supply clock input + clock input - (GND) not assigned
Jumper** external circuit
1
2
3
2
4
+(4..20 mA)
GND
+24 V clock + clock not assigned clock input + clock input not assigned not assigned process actual 1 (current supply) process actual 3 (GND) process actual 2 (compensation)
2
3
2
3
4 clock + clock -
Pt 100
* Adjustable via software (see chapter Procedure for determining the basic settings)
** The jumper is located on the connector board of the TOP Control Continuous.
NOTE For line compensation reasons, connect sensor Pt-100 via 3 conductors, PIN 3 and PIN 4 must be bridged at the sensor.
8630 - 121
P
ROFIBUS
DP
Termination connection for PROFIBUS systems
On installation of a PROFIBUS system, care must be taken to terminate the data lines correctly. The termination generates a well-defined potential state and avoids the occurrence of disturbances by signal reflections on the data lines. For this purpose, the data lines must be terminated at both ends by resistors as shown.
122 - 8630
P
ROFIBUS
DP
Settings on the TOP Control Continuous
In deviation from the details in the enclosed operating instructions, the following settings must be made in the main menu of the device:
On activation, moves to,
safety position
8630 - 123
P
ROFIBUS
DP
Explanation of the menu items
BUS ADDR
ADDR xxx
Entry of the device address (default: 3)
Values from 0 to 126 can be set with the arrow keys; confirmation is done with the MANUAL/AUTOMATIC key.
BUS PDI
* PDI. POS
:
* PDI. ERR
Selection of the process values that are to be transferred from the TOP Control
Continuous to the control (master).
with the MANUAL/AUTOMATIC key, each process value can be either activated (* appears) or deactivated (no * )
For significance of the process values, see table PDI: Process Data Input
BUS PDO
* PDO. INP
:
* PDO. ERR
Selection of the process values that are to be transferred from the control
(master) to the TOP Control Continuous.
With the MANUAL/AUTOMATIC key, each process value can be either activated (* appears) or deactivated (no * ).
For significance of the process values, see table PDO: Process Data Output
BUS FAIL
SPOS OFF
SPOS ON
Activation for movement to saftey position on bus communication failure
The actuator moves to the position corresponding to the setpoint last transmitted
(default setting).
With SPOS ON set, the following configurations can occur:
Activated menu item SAFEPOS
On error in bus communication, the actuator moves to the position set under
SAFEPOS.
Deactivated menu item SAFEPOS
On error in bus communication, the actuator moves to the end position it would occupy in the zero voltage condition.
Functional deviations from the standard version
The operating mode can be switched between MANUAL and AUTOMATIC in the process operating level either with the keypad on the TOP Control Continuous or over the bus.
MANUAL/AUTOMATIC switchover on the keypad is no longer possible when an operating mode (under
“PDO MODE”) is transmitted to the TOP Control Continuous over the bus.
124 - 8630
P
ROFIBUS
DP
Configuration in the PROFIBUS DP master
User parameters (hex paramaters) are not required.
Configuration of the process values
First the process data input are entered (from the TOP Control Continuous to the control).
NOTE In the same order as in the selection in the TOP Control Continuous and only process data ( PDI) activated in the configuration menu may be entered.
PDI : Process Data Input
(from the TOP Control Continuous to the control)
Name
PDI:POS
PDI:CMD
PDI:PV
PDI:SP
Description
Actual position (Position)
Actual value of positioner in ‰.
Range of values 0 ... 1000.
Values < 0 or > 1000 are possible when e.g.
AUTOTUNE was not run throug properly.
Setpoint position (Command)
Positioner setpoint in ‰. Range of values 0 ... 1000.
Identifiers
GSD file: PDI:POS
Identifiers (HEX): 41, 40, 00
GSD file: PDI:CMD
Process actual value (Process Value)
Actual value of process controller in physical units
(as set in menu P.CO INP or P.CO SCAL ), max.
range of values -999 ... 9999, depending on internal scaling
Process setpoint (Setpoint)
Setpoint of value of process controller in physical units
(as set in menu P.CO INP or P.CO SCAL ), max. range of values -999 ... 9999, depending on internal scaling
Identifiers (HEX): 41, 40, 01
GSD file: PDI:PV
Identifiers (HEX): 41, 40, 02
GSD file: PDI:SP
Identifiers (HEX): 41, 40, 03
PDI:TEMP
PDI:MODE
PDI:ERR
Device temperature (Temperature)
Temperature in 0.1 °C is measured on the CPU board with a sensor, range of values -550 (-55 °C) ... +1250 (+125 °C)
GSD file: PDI:TEMP
Identifiers (HEX): 41, 40, 04
Operation mode (Operation Mode)
Operation mode:
0: AUTO 10: P.TUNE
1: HAND 12: BUSSAFEPOS
2: XTUNE
3: MENUE
9: P.QLIN
GSD file: PDI:Mode
Identifiers (HEX): 41, 00, 05
Error (Error)
States the number of the process value (output) that was not written. The value is retained until deleted with
PD-O:ERR .
HEX
14 PD-O:CMD
15 PD-O:SP
16 PD-O:MODE
GSD file: PDI:ERR
Identifiers (HEX): 41, 00, 06
8630 - 125
P
ROFIBUS
DP
PDI : Process Data Input (continued)
(from the TOP Control Continuous to the controller)
Name
PDI:P1
PDI:P2
PDI:MTMP
Description
Forward pressure p1
Pressure in mbar (rel) that is present in front of the process valve.
The value will be determined using a pressure transmitter.
Value range -1013 ... +16000
Back pressure p2
Pressure in mbar (rel) that is present behind the process valve.
The value will be determined using a pressure transmitter.
Value range -1013 ... +16000
Medium temperature
Temperature of the medium in °C. The value will be predefined from the menu, the bus, or using a temperature transmitter.
Value range -20 ... +150
NOTE
Identifiers
GSD file: PDI:P1
Identifiers (HEX): 41, 40, 07
GSD file: PDI:P2
Identifiers (HEX): 41, 40, 08
GSD file: PDI:MTMP
Identifiers (HEX): 41, 40, 09
PDI. PV and PDI. SP can only be selected if the process controller has been activated.
PDI.P1/P2/MTMP can only be selected if the fluid flow controller option is active.
Finally, the process data output (from the controller to the TOP Control Continuous) is entered.
NOTE In the same order as in the selection in the TOP Control Continuous and only process data
( PDI) activated in the configuration menu may be entered.
The updating of the process data output only takes place in the MANUAL and
AUTOMATIC modes.
126 - 8630
P
ROFIBUS
DP
PDO : Process Data Output
(from the control to TOP Control Continuous)
Name
PDO:INP
Description
Set position (Input)
Set-value positioner in ‰, value range 0 ... 1000.
In the "pure" positioner operation (PCONTRL inanctive), the transmission of the set position INP is required, as process controller ( PCONTRL active), the transmission of
INP is not possible.
If the value is too small or too large, the last valid value will be used and will be displayed in ERR with HEX 14.
PDO:SP Process-set-value (Set-point)
Set-value process controller in physical unit (as set up in the P.CO INP or P.CO SCAL menu), max. value range
-999 ... 9999, depending on the internal scaling.
If the value is too small or too large, the last valid value will be used and will be displayed i n ERR with HEX 15.
PDO:MODE Operation Mode
Value range 0 ( AUTO ) ... 1 ( MANUAL ) ...
12 ( BUSSAFEPOS )
Operation mode:
0: AUTO 12: BUSSAFEPOS
1: HAND
If the value is too small or too large, the last valid value will be used and will be displayed in ERR with HEX 16.
PDO:ERR Reset of error message
If the value > 0, ERR is reset.
Identifiers
GSD file: PDO:INP
Identifiers (HEX): 81, 40, 14
GSD file: PDO:SP
Identifiers (HEX): 81, 40, 15
GSD file: PDO:MODE
Identifiers (HEX): 81, 00, 16
GSD file: PDO:ERR
Identifiers (HEX): 81, 00, 17
GSD file: PDO:MTMP PDO:MTMP Medium temperature
Temperature of the medium in °C. The value will be predefined from the menu, the bus, or using a temperature transmitter.
Value range -20 ... +150
If the value is too small or too large, the last valid value will be used and will be displayed in ERR with HEX 18.
Identifiers (HEX): 81, 40, 18
NOTE PDO. INP is always active with the positioner, not present with process conroller.
PDO. SP can only be selected if the process controller is activated.
PDO. MTMP can only be selected if the fluid flow controller option is active.
Bus status display
The bus standard is indicated on the display.
Display message
BUS OFFL alternates with the display value set
Device status offline
Explanation/problem elimination
Device is no connection to the bus
- bus connection incl. plug configuration correct?
- voltage supple and bus connection of the other
subscribers correct?
Device is engaged in cyclic data exchange 4 dots to the left beneath the display value set online, active connection
8630 - 127
P
ROFIBUS
DP
Example 1 with COM Profibus V3.3
Example for a positioner
Settings in the configuration menu of the TOP Control Continuous:
ADDR: 3 PDI:
• PDI:POS
• PDI:MODE
PDO:
• PDO:INP
• PDO:MODE
After starting COM Profibus and the setting of master and SPS information, one gets the following screen:
• Select CONTROLLER
• Set an element under the control
• Set the 3rd address in the menu address (without image)
• Confirm with OK
The following screen appears:
• Select CONTROLLER family
• Select Type 8630
• Select Configuration ...
128 - 8630
The following screen appears:
• Select Order no. ...
The following screen appears:
P
ROFIBUS
DP
Here the process values are entered corresponding to the selection in the configuration menu of the TOP
Control Continuous.
Important: 1. Observe sequence of process values
2. Input before output
• Select process value PDI:POS
• Select process value PDI:MODE
• Select process value PDO:INP
• Select process value PDO:MODE
- Enter inputs and outputs in the process diagram.
8630 - 129
P
ROFIBUS
DP
Final configuration screen:
130 - 8630
Example 2 with COM Profibus V3.3
Example for a process controller
Settings in the configuration menu of the TOP Control Continuous:
ADDR: 3 PDI:
• PDI:PV
PDO:
• PDO:SP
Procedure as in Example 1.
Final configuration screen:
P
ROFIBUS
DP
8630 - 131
P
ROFIBUS
DP
132 - 8630
D
EVICE
N
ET
DEVICE-NET
General notes
...................................................................................................................................................................................................................................
134
Explanation of terms
...............................................................................................................................................................................................................
134
Technical data
..................................................................................................................................................................................................................................
135
Safety settings on bus failure
....................................................................................................................................................................................
135
Interfaces
..................................................................................................................................................................................................................................................
136
Electrical connection
..............................................................................................................................................................................................................
136
Operating voltage (4-pole M12 circular plug)
.......................................................................................................................................
137
Bus connection (4-pole M12 circular plug)
..............................................................................................................................................
137
Inductive proximity switches (4-pole M8 circular socket)
....................................................................................................
137
Process value (circular plug M8)
.........................................................................................................................................................................
137
Termination connection for DeviceNet systems
...............................................................................................................................
138
Net topology of a DeviceNet system
..............................................................................................................................................................
138
Settings on the TOP Control Continuous
................................................................................................................................................
139
Explanation of the menu items in the program run-off schematic
..............................................................................
139
Setting in the main menu
.................................................................................................................................................................................................
140
Configuring the process data
....................................................................................................................................................................................
141
Static input assemblies
.....................................................................................................................................................................................................
141
Static output assemblies
.................................................................................................................................................................................................
143
Bus status display
......................................................................................................................................................................................................................
144
Configuration example 1
..................................................................................................................................................................................................
145
Installation of the EDS file
.............................................................................................................................................................................................
145
Address allocation
..................................................................................................................................................................................................................
145
Offline parametrization of the device
..............................................................................................................................................................
146
Online parametrization of the device
..............................................................................................................................................................
147
Configuration example 2
..................................................................................................................................................................................................
148
Setting up the process map (mapping)
........................................................................................................................................................
149
8630 - 133
D
EVICE
N
ET
General notes
The following sections of the complete operating instructions are not applicable to the DeviceNet variant of the TOP Control Continuous 8630:
• Variants of the TOP Control Continuous
• First commissioning
• Electrical connection
• Defining the basic settings
Function INPUT
Function SPLTRNG
Function BIN-IN
Function OUTPUT
Function CAL.USER / CAL INP
Function CAL.USER / CAL OUT
Function CAL.USER / CAL SP
Explanation of terms
DeviceNet
• DeviceNet is a field bus system based on the CAN protocol (Controller Area Network). It permits the networking of actuators and sensors (slaves) with higher ranking control devices (masters).
• In the DeviceNet the TOP Control Continuous is a slave device according to the Predefined Master/
Slave Connection Set defined in the DeviceNet specification. Polled I/0, Bit Strobed I/O and Change of
State (COS) are supported as I/O connection variants.
• With the DeviceNet a distinction is made between cyclic or event-controlled transferred process messages of high priority (I/O Messages) and acyclic management messages of low priority (Explicit
Messages).
• The protocol sequence corresponds to DeviceNet Specification Release 2.0.
134 - 8630
D
EVICE
N
ET
Technical data
EDS file
Icons
Baud rate
Adress
Process data
BUER8630.EDS
BUER8630.ICO
125 kBit/s, 250 kBit/s, 500 kBit/s (adjustable via keys at the device or via network);
Factory setting 125 kBit/s
0 ... 63; (adjustable via keys at the device or via network);
Factory setting 63
7 static Input Assemblies
(Input: from TOP Control Continuous to DeviceNet Master/Scanner)
4 static Output Assemblies
Total line length according to DeviceNet specification
(Total line length = sum of all mein and drop lines)
Baud rate
125 kBaud
250 kBaud
500 kBaud
Thick Cable
500 m
250 m
100 m
Maximum total line length
Thin Cable
100 m for all baud rates
Drop line length (Drop Lines)
Baud rate
Maximum length
6 m for all baud rates 125 kBaud
250 kBaud
500 kBaud
Length of drop lines
Maximum total length of drop lines in network
156 m
78 m
39 m
Safety settings on bus failure
The actuator moves to the position corresponding to the setpoint last transmitted (default setting).
For other setting options (see the chapter Settings on the TOP Control Continuous)
8630 - 135
D
EVICE
N
ET
Interfaces
Bus
Inputs for process value
4 .. 20 mA
Frequency
Pt 100
24 V DC
TOP Control
Continuous
DeviceNet
Bus
Initiators 1 + 2
Operating unit
Electrical connection
For operation of the device, it is absolutely necessary to connect the 5-pole (bus) and the 4-pole circular plugs M12 (voltage supply).
NOTE Voltage supply to the device is not from the DeviceNet voltage V+ and V-m but from the electrically isolated operating voltage.
136 - 8630
Operating voltage (4-pole M12 circular plug)
Pin
1
2
3
4
Assignment
+24 V not assigned
GND not assigned external circuit
Bus connection (4-pole M12 circular plug)
Pin
1
2
3
4
5
Signal screen
V+
V-
CAN H
CAN L
Color not assigned red black white blue
Inductive proximity switches (4-pole M8 circular socket)
Pin
3
4
1
2
Assignment proximity switch 1 + (NO) proximity switch 1 GND proximity switch 2 + (NO) proximity switch 2 GND
Signal level
Process value (circular plug M8)
Input type *
4...20 mA internally supplied
4...20 mA externally supplied
Pin Assignment
3
4
1
2
+ 24 V input transmitter output transmitter
GND bridge after GND
3
4
1
2 not assigned process actual + not assigned process actual -
* adjustable via software
Jumper external circuit
D
EVICE
N
ET
8630 - 137
D
EVICE
N
ET
Process value (circular plug M8, continuation)
Input type * Pin Assignment
Frequency internally supplied
3
4
1
2
+ 24 V supply sensor clock input + not assigned clock input - / GND
Frequency externally supplied
Pt-100 (see
Note) 3
4
1
2
3
4
1
2 not assigned clock input + not assigned clock input not assigned process actual 1 (current supply) process actual 2 (GND) process actual 3 (compensation)
Jumper
* adjustable via software external circuit
2
3
4
Pt100
NOTE For line compensation reasons, connect sensor Pt-100 via three conductors. PIN3 and 4 must be bridged at the sensor.
Actual process value for the fluid flow controller option (2 M8 round plugs), or optionally: with temperature sensor input (3 M8 round plugs)
Input type internally supplied transmitter * option: temperature transmitter*
Plug
1
2
3
Pin Assignment
1
2
3 + 4
+ 24 V transmitter supply p1
4 ... 20 mA - transmitter output p1 not assigned
1
2
3 + 4
+ 24 V - transmitter supply p2
4 ... 20 mA - transmitter output p2 not assigned
1
3
2 + 4
+ 24 V transmitter supply
4 ... 20 mA - output transmitter temperature not assigned
* With external supply of the sensors the mass of the standard signal must be connected with the mass of supply voltage.
Jumper external circuit
Termination connection for DeviceNet systems
On installing a DeviceNet system, it is important to have the correct termination circuit for the data lines.
The circuit avoids the occurrence of faults through signal reflections on the data lines. For this purpose the main line is to be terminated at both ends with resistors of respectively 120 Ω and 1 / 4 W power loss.
138 - 8630
Net topology of a DeviceNet system
Comprises a trunk line and several drop lines.
Trunk and drop lines are composed of identical material (see drawing).
D
EVICE
N
ET
Settings on the TOP Control Continuous
Explanations of the menu items in the program run-off schematic
BUS ADDR
ADDR XXX
Input of the device address (factory setting: 63)
The address can be changed via the keys at the device or via the bus. After each change, all Connection Objects are deleted followed by the execution of the normal
Start-Up procedure for network access by a subscriber (as after a Reset or Power-
Up).
Values from 0 .. 63 can be set via the arrow keys; confirmation takes place with the
MANUAL/AUTOMATIC key.
BUS RATE
KBD XXX
The baud rate can be changed via the keys at the device or via the bus. In each case a change has no effect until a Reset (transmission of a Reset message to the
Identity Object) or a Power-Up is performed. That is to say, if the changed attribute baud rate is accessed before a Reset or Power-Up, the entered (changed) value does not agree with the still current (to be changed) baud rate of the network.
Selection of 125kbit/s, 250 kbit/s or 500kbit/s.
BUS FAIL
SPOS OFF
SPOS ON
Activation for movement to saftey position on bus communication failure
The actuator moves to the position corresponding to the setpoint last transmitted
(default setting).
With SPOS ON set, the following configurations can occur:
Activated menu item SAFEPOS
On error in bus communication, the actuator moves to the position set under
SAFEPOS.
Deactivated menu item SAFEPOS
On error in bus communication, the actuator moves to the end position it would occupy in the zero voltage condition.
8630 - 139
D
EVICE
N
ET
Settings in the main menu
The following settings are to be made in the main menu of the device, at variance with the statements in these operating instructions:
Operating status
AUTOMATIC or
MANUAL
5 sec.
On activation, moves to,
safety position
140 - 8630
5 sec.
D
EVICE
N
ET
Configuration the process data
5 static input and 2 static output assemblies are available for the transmission of process data via an
I/O connection. Select attributes for transmission jointly as process data via an I/O connection are combiened in an object in these Assemblies.
Selection of the process data takes place by setting the device parameters Active Input Assembly and
Active Output Assembly, or where supported by the DevicNet Master/Scanner, by setting the Produced
Connection Path and Consumed Connection Path on initializing an I/O connection corresponding to the
DeviceNet specification.
Static input assemblies
Name
Pos+ERR (factory setting)
POS+CMD+ERR
PV+ERR
PV+SP+ERR
PV+SP+CMD+ERR
PV+P1+P2+MTMP+ERR
PV+SP+CMD+P1+P2+MTMP+ERR
Adress Data Attribute of ther Assemblies for Read access, Class, Instance, Attribute
Format of the Data
Attribute
4, 1, 3 Byte 0: POS low
Byte 1: POS high
Byte 2: ERR
4, 2, 3
4, 3, 3
4, 4, 3
4, 5, 3
4, 6 , 3
Byte 0: POS low
Byte 1: POS high
Byte 2: CMD low
Byte 3: CMD high
Byte 4: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: CMD low
Byte 5: CMD high
Byte 6: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: P1 low
Byte 3: P1 high
Byte 4: P2 low
Byte 5: P2 high
Byte 6: MTMP low
Byte 7: MTMP high
Byte 8: ERR
4, 7, 3 Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: CMD low
Byte 5: CMD high
Byte 6: P1 low
Byte 7: P1 high
Byte 8: P2 low
Byte 9: P2 high
Byte 10: MTMP low
Byte 11: MTMP high
Byte 12: ERR
8630 - 141
D
EVICE
N
ET
The adresses given in the table Static Input Assemblies can be used as path statement for the attribute
Produced Connection Path of an I/O connection, whereby the attributes described in more detail in the following table can be transferred as Input Process Data via this I/O connection. Independently from thsi however, it is also possible to acyclically access the attributes combined in the Assemblies via Explicit
Messages.
Name
POS
CMD
MTMP
P2
P1
PV
SP
ERR
Description of the Data Attributes Attribute address
Class, Instance,
Attribute; data type, length
111, 1, 59; Actual Position (Actual Position)
Actual value of position controller in ‰. Value range 0...1000.
However values <0 respectively >1000 are also possible if e.g. AUTOTUNE has not run correctly.
Position Setpoint (Position Setpoint)
Setpoint value of position controller in ‰.
Value range 0...1000.
INT, 2 Byte
111, 1, 58;
UINT, 2 Byte
Media temperature value range -20 ... 150
Temperature of the medium in °C. The value will be predefined from the menu, the bus, or using a temperature transmitter.
Back pressure P2
Pressure in mbar (rel) that is present behind the process valve. The value will be determined using a pressure transmitter.
Value range -1013 ... 16000
120, 1, 9;
INT, 2 Byte
120, 1, 8;
INT, 2 Byte
Forward pressure P1
Pressure in mbar (rel) that is present in front of the process valve. The value will be determined using a pressure transmitter.
Value range -1013 ... 16000
Process actual value (Process Value)
Actual value of process controller in physical unit (as set in the menu P.CO INP respectively P.CO SCAL), max. value range –999...9999, depending on the internal scaling.
120, 1, 7;
INT, 2 Byte
120, 1, 3;
INT, 2 Byte
Process Setpoint (Process Setpoint)
Setpoint value of process controller in physical unit (as set in the menu P.CO INP respectively P.CO SCAL), max. value range –999...9999, depending on the internal scaling.
120, 1, 2;
INT, 2 Byte
Error (Error)
Gives the number of the process value (output) which has not been entered. The value is retained until deleted by the acyclic writing of the attribute „Error“ with „0“(access via
Explicit Message – Set Attribut Single).
HEX
0X14 INP
0X15 SP
0X18 MTMP
100, 1, 1;
USINT, 1Byte
142 - 8630
D
EVICE
N
ET
Static Output Assemblies
Name
INP (factory setting)
SP
MTMP
SP+MTMP
Address Data Attribute of the assemblies for
Write/Read access Class, Instance, Attribute
4, 21, 3
4, 22, 3
4, 23, 3
4, 24, 3
Format of the Data
Attribute
Byte 0: INP low
Byte 1: INP high
Byte 0: SP low
Byte 1: SP high
Byte 0: MTMP low
Byte 1: MTMP high
Byte 0: SP low
Byte 1: SP high
Byte 2: MTMP low
Byte 3: MTMP high
The addresses given in the table Static Output Assemblies can be used as path statement for the attribute Consumed Connection Path of an I/O connection, whereby the attributes described in more detail in the following table can be transferred as Output Process Data via this I/O connection.
Independently from this however, it is also possible to acyclically access the attributes combined in the
Assemblies via Explicit Messages.
Name
INP
SP
MTMP
Description of the Output Data Attributes Attribute address,
Class, Instance,
Attribute; data type, length
111, 1, 58; Position setpoint
Setpoint of position controller in ‰.
Value range 0...1000.
In "purely" position controller operation ( PCONTRL inactiv) transmission of the setpoint position INP is necessary; as process controller ( PCONTRL activ) the transmission of INP is not possible. In the case of too small or too large a value, the last valid is used and indicated in ERR with HEX 14.
UINT, 2 Byte
Process-set-value (Process Setpoint)
Set-value process controller in physical unit (as set up in the P.CO INP or P.CO SCAL menu), max. value range –999...9999, depending on the internal scaling.
If the value is too small or too large, the last valid value will be used and will be displayed in ERR with
HEX 15.
120, 1, 2;
INT, 2 Byte
Medium temperature
Temperature of the medium in °C.
Value range -20 ... 150.
If the value is too small or too large, the last valid value will be used and will be displayed in ERR with
HEX 18.
120, 1, 9;
INT, 2 Byte
8630 - 143
D
EVICE
N
ET
Bus status display
The bus standard is indicated on the display.
Display message
BUS OFFL alternates with the display value set
Device status offline
BUS NOCO alternates with the set indication value online, no connection to
Master
2 dots left, under the set indication value online,
Explicit Messaging only
4 dots left, under the set indication value
BUS TIME alternates with the set indication value online, active I/O connection
I/O connection
Timeout
BUS CRIT alternates with the set indication value critical bus error
Explanation/problem elimination
Device is not connected to the bus; the network access procedure (Duplicate MAC-ID-Test, duration 2 s) has not yet ended or the device is the sole active network subscriber.
- Is the baud rate correctly set throughout the network?
- Is the bus connection incl. plug in assignment correct?
- Is the voltage supply and bus connection of the other
subscribers correct?
Device is correctly connected to the bus, the network access procedure has been completed without error, but no connection is established with the Master.
Messaging connection with Master is established. No I/O connection is in the Established state (no I/O data exchange).
An I/O connection is in the Established state (I/O data exchange).
An I/O connection is in the TIME OUT state.
- new establishmend of connection by Master; ensure the
I/O data are transferred cyclically, or with confirmed COS,
the corresponding Acknowledge Messages are sent by the
Master.
Different device with same address in the network, or BUS
OFF due to communication problems:
- change address of device and restart device.
- error analysis in network with a bus monitor.
144 - 8630
D
EVICE
N
ET
Configuration example 1
The example describes the basic procedure on configuring the device when using the software
RSNetworx for DeviceNet (Rev. 2.11.51.0).
Installation of the EDS file
The installation of the EDS file on the supplied floppy takes place with the aid of the tool EDS Installation Wizard belonging to RSNetworx.
The Icon, also supplied on floppy can also be assigned in the course of the installation procedure
(where this does not take place automatically).
Address allocation
There are two possibilities for the assignment of addresses to the devices.
Firstly an address can be set to the desired value over the range 0 … 63 via the keys at the device (see chapter Settings at TOP Control Continuous); secondly a change of address of connected devices can be carried out via the bus with the aid of the tool Node Commissioning belonging to RSNetworx.
Therefore, the sequential addition in an existing network of devices with the default address 63 is a simple matter.
The figure shows how the new address 2 is assigned to a device with the address 63.
8630 - 145
D
EVICE
N
ET
Offline parametrization of the device
After the addition of a device in the DeviceNet configuration of RSNetworx, the device can be parametrized offline.
The figures shows by way of example, how an Input Assembly (Input Process data transferable via I/O connection) at variance with the factory setting can be selected. Note however that the length of the process data must be appropriately adapted with a following configuration of the DeviceNet Masters/
Scanners (see chapter Configuration, Example 2).
All parameter changes carried out offline must be rendered effective for the real device by a Download
Procedure.
146 - 8630
D
EVICE
N
ET
Online parametrization of the device
Devices can also be parameterized online. Here it can be selected whether only a single parameter or all parameters of a group are to be uploaded from the device or downloaded to the device.
The facility also exists for cyclically transferring single parameters or all the parameters of a group in monitor mode. This can be useful, especially for commissioning purposes.
Shown in the figure is the group of process values, respectively Diagnostic information. If the button
Start Monitor is pressed, these values are cyclically updated. However, Explicit Messages are also used for this cyclic access (no I/O connections).
8630 - 147
D
EVICE
N
ET
Configuration example 2
This example describes the basic procedure for setting-up the process mapping of a DeviceNet Master /
Scanner, using the software RSNetworx for DeviceNet (Rev. 2.11.51.0).
Setting-up the Scanlist and setting the I/O parameters
First of all the Scanlist of the DeviceNet Master / Scanner is set-up. For this the devices listed in the left hand part of the associated window are transferred to the right hand part of the window. Then a change of the I/O parameters can be carried out for each device transferred to the Scanlist. This is necessary when, on configuring the relevant TOP Control Continuous, Assemblies have been selected which differ from the default settings.
Shown in the figure is the setting of the I/O parameters with selected
Input-Assembly
Output-Assembly
POS+CMD+ERR (5 bytes long) and selected
INP (2 bytes long; default-Assembly - no change required).
148 - 8630
D
EVICE
N
ET
Setting up the process mapp (mapping)
Using the function AUTOMAP it is possible to assign the input data of the devices listed in the Scanlist to the process mapping of the DeviceNet Master / Scanner.
In our example this resulted in the assignment shown in the figure .
For example, the Input Process values of the TOP Control Continuous with the address 4 are assigned to the internal addresses of the scanner in the following manner:
Actual position:
Setpoint position:
Error:
I:1.6
I:1.7
I:1.8
Therefore if the actual position of the TOP Control Continuous with the address 4 is to be read from a control program, this takes place via an access to 1:1.6.
8630 - 149
D
EVICE
N
ET
150 - 8630
M
AINTENANCE AND ERROR CORRECTION ON THE POSITIONER
MAINTENANCE AND ERROR
CORRECTION ON THE
POSITIONER
Maintenance
........................................................................................................................................................................................................................................
152
Error messages and malfunctions
......................................................................................................................................................................
152
Error messages on the LC display
.....................................................................................................................................................................
152
Other malfunctions
..................................................................................................................................................................................................................
152
8630 - 151
M
AINTENANCE AND ERROR CORRECTION ON THE POSITIONER
Maintenance
When operated according to these Operating Instructions, the TOP Control Continuous is maintenance free.
Error messages and malfunctions
Error messages on the LC display
Error message on switching on
Display
CMD FAUL
EE FAULT
Causes of error signal error set-value positioner
EEPROM faulty
Remedy check signal none, device faulty
Error message on execution of the function X.TUNE
Display
X.ERR 1
X.ERR 2
X.ERR 3
X.ERR 4
X.ERR 6
X.ERR 7
Causes of error
No compressed air connected
Remedy
Connect compressed air
Compressed air failure during
AUTOTUNE
Actuator or positioning system leaky on exhaust side
Check compressed air supply
None, device faulty
Actuator system leaky on pressurized side
The end positions for
POS-MAX
POS-MIN and
are too near to each other
None, device faulty
Check whether the allocation of the end positions to POS-MIN and POS-MAX via the function TUNE-POS is correct.
If incorrect:
Execution TUNE-POS again.
If correct:
TUNE-POS with this arrangement of the end positions is not possible since they are too close together.
False allocation of POS-MIN and POS-
MAX
To determine POS-MIN and POS-MAX , move the actuator in each case in the direction shown on the display.
Other malfunctions
Problem Possible causes
POS = 0 (with CMD > 0 %) or Tight-closing function
POS = 100 %, (by CMD < 100 %) (CUTOFF) has been inadvertently activated
Remedy
Deactivate tight-closing function
152 - 8630
M
AINTENANCE AND ERROR CORRECTION ON THE PROCESS CONTROLLER
MAINTENANCE AND ERROR
CORRECTION ON THE
PROCESS CONTROLLER
Maintenance
........................................................................................................................................................................................................................................
154
Error messages and malfunctions
......................................................................................................................................................................
154
Error messages on the LC display
.........................................................................................................................................................................
154
Other malfunctions
....................................................................................................................................................................................................................
156
8630 - 153
M
AINTENANCE AND ERROR CORRECTION ON THE PROCESS CONTROLLER
Maintenance
When operated according to these Operating Instructions, the TOP Control Continuous is maintenance free.
Error messages and malfunctions
Error messages on the LC display
General error messages
Display
CMD FAUL
SP FAULT
PV FAULT
PT FAULT
P1 FAULT
P2 FAULT
TMP FAUL
EE FAULT
MFI FAUL
Causes of error signal error set-value, positioner signal error set-value, process controller signal error actual value, process controller signal error actual value, Pt-100 signal error actual value, P1 fluid flow controller signal error actual value, P2 fluid flow controller signal error actual value, temperature, fluid flow controller
EEPROM faulty
Fieldbus board faulty
Remedy check signal check signal check signal check signal check signal check signal check signal none, device faulty
Error messages on execution of the function X.TUNE
Display
X.ERR 1
X.ERR 2
X.ERR 3
X.ERR 4
X.ERR 6
X.ERR 7
Causes of error
No compressed air connected
Compressed air failure during
AUTOTUNE
Actuator or positioning system leaky on exhaust side
Actuator system leaky on pressurized side
Remedy
Connect compressed air
Check compressed air supply
None, device faulty
None, device faulty
The end positions for
POS-MAX
POS-MIN and
are too near to each other
Check whether the allocation of the end positions to POS-MIN and POS-MAX via the function TUNE-POS is correct.
If incorrect:
Execution TUNE-POS again.
If correct:
TUNE-POS with this arrangement of the end positions is not possible since they are too close together.
False allocation of POS-MIN and POS-
MAX
To determine POS-MIN and POS-MAX , move the actuator in each case in the direction shown on the display.
154 - 8630
M
AINTENANCE AND ERROR CORRECTION ON THE PROCESS CONTROLLER
Error messages on execution of the function P.Q'LIN
Display
Q.ERR 1
Causes of error
No compressed air connected
No change in process value
Remedy
Connect compressed air
Check process, switch on pump or open shut-off valve if necessary
Q.ERR 2 Current fixed point of the valve stroke was not reached because
• Pressure supply failre
during P.Q’LIN
• No AUTOTUNE was executed
• Check pressure supply
• execute AUTOTUNE
Error message on execution of the function LEAK MEAS
Display
L.ERR 1
L.ERR 2
L.ERR 3
Cause of error
No admission pressure at the controller unit (> 50 mbar).
Control does not fully close.
No leakage detectable: the difference between admission pressure and conveying pressure is so low, even at slight valve opening, that no air leak can be measured.
Whilst the valve is open the delivery pressure is not increased, which means that no restart points for the characteristic can be recorded.
Remedy
Switch on compressor before start of leakage measurement.
Execute AUTOTUNE.
The leakage characteristic must be deactivated since the precision of air flow control cannot be raised.
Make sure that the conveying pipe is closed and the blocking air is open.
8630 - 155
M
AINTENANCE AND ERROR CORRECTION ON THE PROCESS CONTROLLER
Other malfunctions
Problem Possible causes
POS = 0 (with CMD > 0%) or Tight-closing function
POS = 100%,(with CMD < 100%) (CUTOFF) has
PV = 0 (with SP > 0) or
PV = PV (with SP > SP ) been inadvertently activated
Only with devices with analog
repeat: red LED does light
Binary output does not switch
Only with devices with process controller:
Device does not work as a controller despite correctly executed settings.
Binary output:
Current > 100 mA short circuit
Menu item P.CONTRL stands in main menu. The device thus works as a process controller and expects a process value at the corresponding input.
Remedy
Deactivate tight-closing function
Check connection of binary output
Remove the menu item
P.CONTRL from the main menu.
156 - 8630
G
ENERAL
R
ULES
(A
PPENDIX
)
GENERAL RULES
(APPENDIX)
Selection criteria for continuous valves
.................................................................................................................................................................
158
Characteristics of PID controllers
...................................................................................................................................................................................
160
P component
.............................................................................................................................................................................................................................................
160
I component
................................................................................................................................................................................................................................................
161
D component
.............................................................................................................................................................................................................................................
162
Superimposing the P, I and D components
........................................................................................................................................................
163
Function of a real PID controller
.......................................................................................................................................................................................
164
Rules for setting PID controllers
.......................................................................................................................................................................................
165
Setting rules of Ziegler and Nichols (oscillation method)
.................................................................................................................
165
Setting rules of Chien, Hrones and Reswick (controller output step method)
......................................................
166
8630 - 157
G
ENERAL
R
ULES
(A
PPENDIX
)
Selection criteria for continuous valves
The following criteria are of decisive importance for optimal control behaviour and attainment of the maximum flow rate through the valve:
• Correct choice of flow coefficient, which is defined essential by the size of the valve;
• Good matching of the valve size to the pressure conditions, taking into consideration the other flow resistances in the system.
Dimensioning guidelines can be given on the basis of the flow coefficient (k v
). The k v
value refers to the standardized conditions with respect to pressure, temperature and media properties.
The k v
value is defined as the flow rate in m 3 /h of wasser through a component at a pressure difference
Dp of 1 bar and a temperature of 20°C.
With continuous valves the “ k vs continuous valve is fully open.
value” is additionally used. This specifies the k v
value when the
Depending on the specified data, the following cases must be distinguished on selection of a valve: a) The pressures before and after the valve p
1
Q max
is to be attained:
and p
2
are known at which the desired maximum flow rate
The required k vs value is obtained from: k
VS
= Q max
⋅
∆ p
0
∆ p
⋅
ρ
ρ
0
(1)
where: k
VS
Q max
∆ p
0 r
0
∆ p r is the flow coefficient of the continuous valve when fully open [m³/h] is the maximum volumetric flow rate [m³/h]
= 1 bar; the pressure drop over the valve as in the definintion of k
V
= 1000 kg/m³; the density of water as in the definition of k
V is the pressure drop over the valve [bar] and is the density of the medium [kg/m³] b) The pressures at the inlet and outlet of the overall system (p
1 desired maximum flow rate Q max
is to be attained:
and p
2
), are known at which the
Step 1:
Step 2:
Step 3:
Step 4:
Calculate the flow coefficient of the overall system k
Vges
from equation (1).
Measure the flow rate through the system without the continuous valve
(e.g. by short-circuiting the piping where the vale is installed).
Calculate the flow coefficient of the system without the continuous valve (k
Va equation (1).
) from
Calculate the required k
VS
value of the continuous valve ( k
VS
) from equation (2).
k
VS
=
1 k
Vges
2
1
−
1 k
Va
2
(2)
158 - 8630
G
ENERAL
R
ULES
(A
PPENDIX
)
NOTE The k
VS
of the continuous valve should have at least the value valculated from the equation
(1 or 2) relevant to the application, but under no circumstances be very much greater.
The rule of thumb often used with switching valves, "somewhat larger never hurts", can be strongly detrimental to the control behaviour of continuous valves!
Determination in practice of the upper limit to the k
VS
value of the continuous valve is possible by means of the so-called "valve authority"
Ψ:
Ψ =
( )
( )
V
0
0 = k
Va
2 k
Va
2
+ k
VS
2
(3)
(
∆ p)
V0
( ∆ p)
0 is the pressure drop over the fully opened valve and is the pressure drop over the entire system.
NOTE With a valve authority Y < 0.3 the continuous valve is overdimensioned.
With the valve fully open, in this case the flow resistance is significantly smaller than that of the other fluidic components in the system. This means that only in the lower opening range is the valve position dominant in the operating characteristic. For this reason, the operating characteristic is strongly deformed.
By selection of a progressive (equiprocentile) characteristic between position setpoint and valve stroke, this can be partially compensated and the operating characteristic linearized within certain limits. However, the valve authority Y should be > 0.1, even when using a corrected characteristic.
The control behaviour (control performance, settling time) when using a corrected characteristic is strongly dependent on the operating point.
8630 - 159
G
ENERAL
R
ULES
(A
PPENDIX
)
Characteristics of PID controllers
A PID controller has a proportional, an integral and a differential component (P, I and D components).
P component
Function: Y = Kp · Xd
Where Kp is the proportional action factor (amplification factor). It is given by the ratio of the correcting range ∆ Y to the proportional range ∆ Xd.
Characteristic and step response of the P component of a PID controller
Proportional range
Characteristic line Step response
Characteristics
A pure P controller works theoretically undamped, i.e. it is fast and dynamically favourable. It has a residual control difference, i.e. it does not completely eliminate the effects of disturbances and is thus relatively unfavourable from a static viewpoint.
160 - 8630
G
ENERAL
R
ULES
(A
PPENDIX
)
I component
1
Function: Y = ∫ Xd dt
Ti is the integration or floating time. It is the time that expires until the controller output has run through the entire correcting range.
Characteristic and step response of the I component of a PID controller
Control range ∆ Xc
Characteristic line
Floating time
Step response
Correcting range
Characteristics
A purely I controller completely eliminates the effects of disturbances. It thus has a favourable static behaviour. Because of its finite correcting speed, it works more slowly than a P controller and tends to oscillation. It is hence dynamically relatively unfavourable.
8630 - 161
G
ENERAL
R
ULES
(A
PPENDIX
)
D component
Function: Y = Kd d Xd/dt
The higher Kd is, the stronger the D influence is.
Characteristics and step response of the D component of a PID controller
Step response Rise response
Characteristic
A controller with a D component reacts to changes in the controlled variable and can thus reduce more quidckly any control differences that occur.
162 - 8630
G
ENERAL
R
ULES
(A
PPENDIX
)
Superimposing the P, I and D components
Function: Y = Kp Xd +
Ti
∫∫∫∫∫ Xd dt + d Xd/dt
Substituting Kp · Ti = Tn and Kd/Kp = Tv we obtain for the function on the PID controller:
Y = Kp (Xd +
Tn
∫∫∫∫∫ Xd dt + Tv dXd/dt)
Kp is the proportional action factor/amplification factor
Tn is the reset time
(the time required to obtain the same change in correcting variable as was caused by the P component) and
Tv is the rate time
(the time by which a certain change in correcting variable is obtained earlier with the D component than t would have been with a pure P controller).
Step response and rise response of the PID controller
X
Xd
X
Y t
Y t
Kp•Xd
Step response of the PID controller t t
Rise response of the PID controller
8630 - 163
G
ENERAL
R
ULES
(A
PPENDIX
)
Function of a real PID controller
D component with delay
In the process controller of the positioner, the D component is realized with a delay T.
Function T + Y = Kd dXd dt
Superimposing the P, I and DT components
X
Xd t
Y
Xd
T t
T
Function of the real PID controller
T + Y = Kp (Xd + dt Tn
∫∫∫∫∫ Xd dt + Tv ) dt
Step response of the real PID controller
X
Xd t
Y
Kp Xd t
Tn
164 - 8630
G
ENERAL
R
ULES
(A
PPENDIX
)
Rules for setting PID controllers
The literature on control technology contains a number of rules by which a favourable setting of the controller parameters can be determined experimentally. In order to avoid incorrect settings, the conditions under which the rules were set up in each case must be kept in mind. Apart from the characteristics of the controlled member and the controller itself, it makes a difference whether a change in disturbance or a command variable is to be compensated.
Setting rules of Ziegler and Nichols (oscillation method)
With this method, the controller parameters are set on the basis of the behaviour of the control loop at the limit of stability. These parameters are initially set such that the control loop begins to oscillate.
Critical characteristic values occurring allow one to deduce a favourable setting of the control parameters. A prerequisite for using this method is naturally that the control loop is permitted to oscillate.
Procedure
• Set the controller to P control (i.e. Tn = 999, Tv = 0), Kp initially small.
• Set the desired set point.
• Increase Kp until the controlled variable executes continuous, undamped oscillation.
The proportional action factor (amplifucatuib factor) set at the limit of stability is designated K crit resulting oscillation period is designated T krit
.
. The
Curve of controller output at the limit of stability
X
Actual value
Istwert
From K crit
and T crit
the controller parameters can then be calculated using the following table.
Parameter setting according to Ziegler and Nichols
Contr. type Einstellung der Parameter
P
PI
PID
Kp = 0.5 K crit
Kp = 0.45 K crit
Kp = 0.6 K crit
-
Tn = 0.85 T
Tn = 0.5 T crit crit
-
-
Tv = 0.12 T crit
The adjustment rules of Ziegler and Nichols have been determined for P members with first order time increase and dead time. However, they apply only for controllers with disturbance behaviour and not for those with command behaviour.
8630 - 165
G
ENERAL
R
ULES
(A
PPENDIX
)
Setting rules of Chien, Hrones and Reswick
(controller output step method)
With this method the controller parameters are set on the basis of the transient behaviour of the controlled member. A step in the controller output of 100 % is delivered. The times Tu and Tg are derived from the curve of the actual value of the controlled variable.
Curve of the controlled variable after a step in controller output
∆∆∆∆∆
Y
Controller output Y t
Actual value
Ks * ∆ Y
Controlled variable t
Tu Tg
Procedure
• Switch controller to MANUAL.
• Deliver a step in controller output and register the controlled variable with a chart recorder.
• With critical runs (e.g. on risk of overheating), switch off in good time.
NOTE It should be observed that with thermally sluggish systems, the axtual value of the controlled variable may continue to rise after switching off.
In the following table, the setting values are given for the controller parameters as a function of Tu, Tg and Ks for command and disturbance behaviour, as well as for an aperiodic control event and a control event with 20% overswing. They apply for members with P behaviour, with dead time and with first-order delay.
166 - 8630
G
ENERAL
R
ULES
(A
PPENDIX
)
Parameter setting according to Chien, Hrones and Reswick
Controlle type
Parameter setting with aperiodic control event
(0 % overswing) with control event
(with 20 % overswing)
Command
Kp = 0,3
Tg
Tu*Ks
Disturbance
Kp = 0,3
Tg
Tu*Ks
Command
Kp = 0,7
Tg
Tu*Ks
Disturbance
Kp = 0,7
Tg
Tu*Ks
P
PI
PID
Kp = 0,35
Tg
Tu*Ks
Tn = 1,2 Tg
Kp = 0,6
Tg
Tu*Ks
Tn = 4 · Tu
Kp = 0,6
Tg
Tu*Ks
Tn = Tg
Tv = 0,5 · Tu
Kp = 0,95
Tg
Tu*Ks
Tn = 2,4 · Tu
Tv = 0,42 · Tu
Kp = 0,6
Tg
Tu*Ks
Tn = Tg
Kp = 0,7
Tg
Tu*Ks
Tn = 2,3 · Tu
Kp = 0,95
Tg
Tu*Ks
Tn = 1,35 ·Tg
Tv = 0,47 · Tu
Kp = 1,2
Tg
Tu*Ks
Tn = 2 · Tu
Tv = 0,42 · Tu
The proportional action factor Ks of the controlled member is obtained according from:
Ks =
∆
X
∆ Y
8630 - 167
G
ENERAL
R
ULES
(A
PPENDIX
)
168 - 8630
O
PERATING STRUCTURE
(A
PPENDIX
)
OPERATING STRUCTURE
(APPENDIX)
8630 - 169
O
PERATING STRUCTURE
(A
PPENDIX
)
Operating structure of the TOP Control Continuous
170 - 8630
On activation, moves to, safety position
O
PERATING STRUCTURE
(A
PPENDIX
)
Menu appears only with activated PID controller
8630 - 171
O
PERATING STRUCTURE
(A
PPENDIX
)
172 - 8630 with PCO INP = 4´20A with PCO INP = FREQ
SP: only with external setpoint
(selected via PCO SETP / SETPEXT) with PCO INP = P´100 with PCO INP = P1´P2
DIAM can be entered only if,
P.TYP VELO has been selected!
O
PERATING STRUCTURE
(A
PPENDIX
)
If SAFEPOS is deactivated, then SPOS = 000
If SAFEPOS is deactivated, then SPOS = 000
8630 - 173
O
PERATING STRUCTURE
(A
PPENDIX
)
174 - 8630
Controller activated
Process controller activated
Process controller activated
O
PERATING STRUCTURE
(A
PPENDIX
)
8630 - 175
O
PERATING STRUCTURE
(A
PPENDIX
)
176 - 8630
T
ABLES FOR
P
OSITIONER
(A
PPENDIX
)
TABLES FOR
POSITIONER
(APPENDIX)
8630 - 177
T
ABLES FOR
P
OSITIONER
(A
PPENDIX
)
Tables for noting your setting on the positioner
Settings of the freely programmable characteristic
Ref. point
(Set point of position in %)
40
45
50
55
25
30
35
0
5
10
15
20
60
65
70
75
80
85
90
95
100
Date: Date:
Valve stroke [%]
Date: Date:
178 - 8630
T
ABLES FOR
P
ROCESS
C
ONTROLLER
(A
PPENDIX
)
TABLES FOR
PROCESS CONTROLLER
(APPENDIX)
8630 - 179
T
ABLES FOR
P
ROCESS
C
ONTROLLER
(A
PPENDIX
)
Tables for noting your settings on the process controller
Settings of the freely programmable characteristic
Ref. point
(Set point of position in %)
60
65
70
75
35
40
45
50
55
80
85
90
95
100
15
20
25
30
0
5
10
Date: Date:
Valve stroke [%]
Date: Date:
Parameters set on the process controller
Date: Date: Date:
KP
TN
TV
X0
DBND
DP
PV
PV
SP
SP
UNIT
KFAC
FILT
INP
Date:
180 - 8630
M
ASTERCODE
(A
PPENDIX
)
MASTERCODE
(APPENDIX)
8630 - 181
M
ASTERCODE
(A
PPENDIX
)
182 - 8630
MASTERCODE
7175
Addresses of BC offices/Adressliste BC Länder Europe/Europa
BC-A Austria, Österreich
Bürkert-Contromatic G.m.b.H.
Diefenbachgasse 1-3
A-1150 Wien
Phone: Int. (+43 1)894 13 33, Nat. (01)894 13 33
Fax: Int. (+43 1)894 13 00, Nat. (01)894 13 00
E-mail: [email protected]
BC-B Belgium, Belgien
Bürkert Contromatic NV/SA
Bijkhoevelaan 3
B-2110 Wijnegem
Phone: Int. (+32 3)325 89 00, Nat. (03)325 89 00
Fax: Int. (+32 3)325 61 61, Nat. (03)325 61 61
E-mail: [email protected]
BC-CZ Czech Rep., Tschechische Rep.
Bürkert-Contromatic G.m.b.H. organizacni slozka
Krenova 35
CZ-602 00 Brno
Phone: Int. (+420 543)25 25 05, Nat. (543)25 25 05
Fax: Int. (+420 543)25 25 06, Nat. (543)25 25 06
E-mail: [email protected]
BC-DK Denmark, Dänemark
Bürkert-Contromatic A/S
Hørkær 24
DK-2730 Herlev
Phone: Int. (+45 44)50 75 00, Nat. 44-50 75 00
Fax: Int. (+45 44)50 75 75, Nat. 44-50 75 75
E-mail: [email protected]
BC-EST
Bürkert Oy Eesti
Laki 11 E
EE-12915 Tallin
Estonia, Estland
Phone: Int. (+3 72)6440 698, Nat. (372)6440 698
Fax: Int. (+3 72)6313 759, Nat. (372)6313 759
E-mail: [email protected]
BC-SF
Bürkert Oy
Finland, Finnland
Atomitie 5
FI-00370 Helsinki
Phone: Int. (+358 9)549 706 00, Nat. (09)549 706 00
Fax: Int. (+358 9)503 12 75, Nat. (09)503 12 75
E-mail: [email protected]
BC-F France, Frankreich
Burkert Contromatic SARL
Rue du Giessen
FR-67220 Triembach au Val
Phone: Int. (+33 388)58 91 11, Nat. (0388)58 91 11
Fax: Int. (+33 388)57 20 08, Nat. (0388)57 20 08
E-mail: [email protected]
BC-I Italy, Italien
Burkert Contromatic Italiana S.p.A.
Centro Direzionale „Colombirolo“
Via Roma, 74
IT-20060 Cassina De’ Pecchi (Mi)
Phone: Int. (+39 02)959 071, Nat. (02)959 071
Fax: Int. (+39 02)959 072 51, Nat. (02)959 072 51
E-mail: [email protected]
BC-N Norway, Norwegen
Bürkert-Contromatic A/S
Hvamstubben 17
NO-2013 Skjetten
Phone: Int. (+47 63)84 44 10, Nat. (63)84 44 10
Fax: Int. (+47 63)84 44 55, Nat. (63)84 44 55
E-mail: [email protected]
BC-NL Netherlands, Niederlande
Bürkert Contromatic BV
Computerweg 9
NL-3542 DP Utrecht
Phone: Int. (+31 346)58 10 10, Nat. (0346)58 10 10
Fax: Int. (+31 346)56 37 17, Nat. (0346)56 37 17
E-mail: [email protected]
BC-P Portugal, Portugal
Phone: Int. (+351 21)21 28 490, Nat. (21)21 28 490
Fax: Int. (+351 21)21 28 491, Nat. (21)21 28 491
E-mail: [email protected]
BC-PL Poland, Polen
Burkert-Contromatic GmbH
Oddzial w Polsce
Bernardynska street 14 a
PL-02-904 Warszawa
Phone: Int. (+48 22)840 60 10, Nat. (022)840 60 10
Fax: Int. (+48 22)840 60 11, Nat. (022)840 60 11
E-mail: [email protected]
BC-E Spain, Spanien
Bürkert Contromatic S.A.
Avda. Barcelona, 40
ES-08970 Sant Joan Despi, Barcelona
Phone: Int. (+34 93)477 79 80, Nat. (93)477 79 80
Fax: Int. (+34 93)477 79 81, Nat. (93)477 79 81
E-mail: [email protected]
BC-S Sweden, Schweden
Bürkert-Contromatic AB
Skeppsbron 13 B
SE-211 20 Malmö
Phone: Int. (+46 40)664 51 00, Nat. (040)664 51 00
Fax: Int. (+46 40)664 51 01, Nat. (040)664 51 01
E-mail: [email protected]
BC-CH Switzerland, Schweiz
Bürkert-Contromatic AG Schweiz
Bösch 71
CH-6331 Hünenberg ZG
Phone: Int. (+41 41)785 66 66, Nat. (041)785 66 66
Fax: Int. (+41 41)785 66 33, Nat. (041)785 66 33
E-mail: [email protected]
BC-TR Turkey, Türkei
Burkert Contromatic Akiskan
Kontrol Sistemleri Ticaret A.S.
1203/8 Sok. No2-E
TR-Yenisehir, Izmir
Phone: Int. (+90 232)459 53 95, Nat. (0232)459 53 95
Fax: Int. (+90 232)459 76 94, Nat. (0232)459 76 94
E-mail: [email protected]
BC-UK United Kingdom,
Vereinigtes Königreich
Burkert Contromatic Limited
Brimscombe Port Business Park
Brimscombe, Stroud
Glos, GL5 2QF / UNITED KINGDOM
Phone: Int. (+44 1453)73 13 53, Nat. (01453)73 13 53
Fax: Int. (+44 1453)73 13 43, Nat. (01453)73 13 43
E-mail: [email protected]
Addresses of BC offices/Adressliste BC Länder APAC
BC-AUS Australia, Australien
BURKERT CONTROMATIC AUSTRALIA PTY, LIMITED
2 Welder Road
Seven Hills, NSW 2147
AUSTRALIA
Phone: Int. (+61 2)1300 888 868, Nat.(02)1300 888 868
Fax: Int. (+61 2)1300 888 076, Nat.(02)1300 888 076
E-mail: [email protected]
Victoria
BURKERT CONTROMATIC AUSTRALIA PTY, LIMITED
Unit 11/26-30 Howleys Road
Notting Hill Victoria 2168
Phone: Int. (+61 3)85459700, Nat. (03)85459700
Fax: Int. (+61 3)95626599, Nat. (03)95626599
Queensland
BURKERT CONTROMATIC AUSTRALIA PTY, LIMITED
Unit 4/43 Sandgate Road
Albion Queensland 4010
Phone: Int. (+61 7)33269600, Nat. (07)33269600
Fax: Int. (+61 7)32628801, Nat. (07)32628801
Western Australia
BURKERT CONTROMATIC AUSTRALIA PTY. LIMITED
104 Westpoint, 396 Scarborough Beach Road
Osborn Park Western Australia 6017
Phone: Int. (+61 8)94443980, Nat. (08)94443980
Fax: Int. (+61 8)94449353, Nat. (08)94449353
BC-CN China, China
Burkert Contromatic (Shanghai), Co.,Ltd.
Room J1, 3rd floor
207 Tai Gu Road
Wai Gao Qiao Free Trade Zone
Shanghai 200131
P. R. China
Phone: Int. (+86 21)5868 21 19, Nat. (21)5868 21 19
Fax: Int. (+86 21)5868 21 20, Nat. (21)5868 21 20
E-mail: [email protected]
Beijing
Burkert Contromatic (Shanghai), Co., Ltd.
Room 808, Jingtai Building
No. 24, Jian Guo Men Wai Da Jie
Beijing P. R. China, 100022
Phone: Int. (+8610)6515 6508, Nat. (10)6515 6508
Fax: Int. (+8610)6515 6507, Nat. (10)6515 6507
Chengdu
Burkert Contromatic (Shanghai), Co., Ltd.
Room 603-604, Fuji Building
26 Dongfeng Road, Shudu Dadao
Chengdu P. R. China, 610061
Phone: Int. (+8628)84439064, Nat. (28)84439064
Fax: Int. (+8628)84451341, Nat. (28)84451341
Guangzhou
Burkert Contromatic (Shanghai), Co., Ltd.
Room 1502, Tower 4, Dong Jun Plaza
828 - 836 Dong Feng Road East
Guangzhou P. R. China, 510080
Phone: Int. (+8620)87698379, Nat. (20)87698379
Fax: Int. (+8620)87671131, Nat. (20)87671131
Shanghai
Burkert Contromatic (Shanghai), Co., Ltd.
Room 27E, Shanghai Industry Building
No. 18 Caoxi Bai Road
Shanghai P. R. China, 200030
Phone: Int. (+8621)64865110, Nat. (21)64865110
Fax: Int. (+8621)64874815, Nat. (21)64874815
Suzhou
Burkert Contromatic (Shanghai), Co., Ltd.
Room 5, #06-06
Block A, No. 5 Xinghan Street
SIP Suzhou P. R. China, 215021
Phone: Int. (+86512)67611916, Nat. (512)67611916
Fax: Int. (+86512)67611120, Nat. (512)67611120
BC-HKG (China) Hong Kong, Hongkong
Burkert Contromatic (China/HK) Ltd.
Unit 708 Prosperity Centre,
77 - 81, Container Port Road
Kwai Chung, N.T., HONG KONG
Phone: Int. (+852)248 012 02, Nat. 248 012 02
Fax: Int. (+852)241 819 45, Nat. 241 819 45
E-mail: [email protected]
BC-IND India, Indien
Burkert Contromatic PVT Ltd.
Apex Towers
1st Floor, No. 54 II Main Rd
RA Puram
Chennai 600 028
INDIA
Phone: Int. (+91 044)52303456, Nat. (044)52303456
Fax: Int. (+91 044)52303232, Nat. (044)52303232
E-mail: [email protected]
BC-J
Burkert Ltd.
Japan, Japan
1-8-5 Asagaya Minami
Suginami-ku
Tokyo 166-0004
JAPAN
Phone: Int. (+81 3)5305 3610, Nat. (03)5305 3610
Fax: Int. (+81 3)5305 3611, Nat. (03)5305 3611
E-mail: [email protected]
BC-KOR Korea, Korea
Burkert Contromatic Korea Co., Ltd.
C-401, Micro Office Bldg. 554-2
Gasan-Dong, Keumcheon-Gu
Seoul 153-803
KOREA
Phone: Int. (+82 2)3462 5592, Nat. (02)3462 5592
Fax: Int. (+82 2)3462 5594, Nat. (02)3462 5594
E-mail: [email protected]
BC-TT Malaysia, Malaysia
BURKERT CONTROMATIC SINGAPORE PTE. LTD.
2F-1, Tingkat Kenari 6
Sungai Ara
11960 Penang
MALAYSIA
Phone: Int. (+60 4)643 5008, Nat. (04)643 5008
Fax: Int. (+60 4)643 7010, Nat. (04)643 7010
E-mail: [email protected]
BC-NZ New Zealand, Neuseeland
BURKERT CONTROMATIC NEW ZEALAND LIMITED
2A, Unit L, Edinburgh Street
Penrose, Auckland
NEW ZEALAND
Phone: Int. (+64 9)622 28 40, Nat. (09)622 28 40
Fax: Int. (+64 9)622 28 47, Nat. (09)622 28 47
E-mail: [email protected]
Addresses of BC offices/Adressliste BC Länder APAC
BC-RP Philippines, Philippinen
BURKERT CONTROMATIC PHILIPPINES, INC.
8467, West Service Road Km 14
South Superhighway, Sunvalley
Paranaque City, Metro Manila
PHILIPPINES
Phone: Int. (+63 2)776 43 84, Nat. (02)776 43 84
Fax: Int. (+63 2)776 43 82, Nat. (02)776 43 82
E-mail: [email protected]
BC-SIN Singapore, Singapur
BURKERT CONTROMATIC SINGAPORE PTE. LTD.
51 Ubi Avenue 1, #03-14
Paya Ubi Industrial Park
Singapore 408933
SINGAPORE
Phone: Int. (+65)6844 2233, Nat. 6844 2233
Fax: Int. (+65)6844 3532, Nat. 6844 3532
E-mail: [email protected]
BC-RC Taiwan, Taiwan
Burkert Contromatic Taiwan Ltd.
9F, No. 32, Chenggong Road, Sec. 1,
Nangang District
Taipei
TAIWAN 115, R.O.C
Phone: Int. (+886 2)2653 7868, Nat. (02)2653 7868
Fax: Int. (+886 2)2653 7968, Nat. (02)2653 7968
E-mail: [email protected]
Addresses of BC offices/Adressliste BC Länder NAFTA
BC-BRA Brazil, Brasilien
Bürkert-Contromatic Brasil Ltda.
Rua Américo Brasiliense, 2171 cj.1007
04715-005 São Paulo - SP
BRAZIL
Phone: Int. (+55 11)5182 0011, Nat. (011)5182 0011
Fax: Int. (+55 11)5182 8899, Nat. (011)5182 8899
E-mail: [email protected]
BC-CDN
Bürkert Contromatic Inc.
760 Pacific Road, Unit 3
Oakville, Ontario L6L 6M5
Canada, Kanada
CANADA
Phone: Int. (+1 905)847 55 66, Nat. (905)847 55 66
Fax: Int. (+1 905)847 90 06, Nat. (905)847 90 06
E-mail: [email protected]
BC-USA
BURKERT CONTROMATIC CORP.
2602 McGaw Avenue
USA, USA
Irvine, CA 92614
USA
Phone: Int. (+1 949)223 31 00, Nat. (949)223 31 00
Fax: Int. (+1 949)223 31 98, Nat. (949)223 31 98
E-mail: [email protected]
Addresses of BC offices/Adressliste BC Länder AFRICA/AFRIKA
BC-SA South Africa, Südafrika
Bürkert Contromatic Pty. Ltd.
P.O. Box 26260
East Rand
1462
Phone: Int. (+27 11)574 60 00, Nat. (011)574 60 00
Fax: Int. (+27 11)454 14 77, Nat. (011)454 14 77
E-mail: [email protected]
Adressliste Bürkert Fluid Control Systems Deutschland
Headquarter and Service Center,
Stammsitz und Service-Center
Ingelfingen
Bürkert GmbH & Co. KG
Christian-Bürkert-Straße 13 - 17
74653 Ingelfingen
Telefon: Int. (+497940)10-111, Nat. (07940)10-111
Fax: Int. (+497940)10-448, Nat. (07940)10-448
E-mail: [email protected]
Distribution Center, Vertriebs-Center
Berlin
Bürkert GmbH & Co. KG
Paradiesstraße 206 b
DE-12526 Berlin
Telefon: Int. (+4930)6797170, Nat. (030)6797170
Fax: Int. (+4930)67971766, Nat. (030)67971766
Hannover
Bürkert GmbH & Co. KG
Rendsburger Straße 12
DE-30659 Hannover
Telefon: Int. (+49511)902760, Nat. (0511)902760
Fax: Int. (+49511)9027666, Nat. (0511)9027666
Dortmund
Bürkert GmbH & Co. KG
Holzener Straße 70
DE-58708 Menden
Telefon: Int. (+492373)96810, Nat. (02373)96810
Fax: Int. (+492373)968150, Nat. (02373)968150
Frankfurt
Bürkert GmbH & Co. KG
Am Flugplatz 27
DE-63329 Egelsbach
Telefon: Int. (+496103)94140, Nat. (06103)94140
Fax: Int. (+496103)941466, Nat. (06103)941466
Stuttgart
Bürkert GmbH & Co. KG
Karl-Benz-Straße 19
DE-70794 Filderstadt-Bernhausen
Telefon: Int. (+49711)451100, Nat. (0711)451100
Fax: Int. (+49711)4511066, Nat. (0711)4511066
München
Bürkert GmbH & Co. KG
Paul-Gerhardt-Allee 24
DE-81245 München
Telefon: Int. (+4989)8292280, Nat. (089)8292280
Fax: Int. (+4989)82922850, Nat. (089)82922850
Service Center, Dienstleistungs-Center
Dortmund
Bürkert GmbH & Co. KG
Holzener Straße 70
DE-58708 Menden
Telefon: Int. (+492373)968134, Nat. (02373)968134
Fax: Int. (+492373)968132, Nat. (02373)968132
Dresden
Bürkert GmbH & Co. KG
Christian-Bürkert-Straße 2
DE-01900 Großröhrsdorf
Telefon: Int. (+4935952)36-300, Nat. (035952)36-300
Fax: Int. (+4935952)36-551, Nat. (035952)36-551
www.buerkert.com