BRAKING UNIT CDBR-
BRAKING RESISTOR UNIT LKEB-
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
安川インバータオプション
制動ユニット,制動抵抗器ユニット
取扱説明書
制動ユニット CDBR-
制動抵抗器ユニット LKEB-
製品を安全にお使い頂くために,本書を必ずお読みください。
また,本書をお手元に保管していただくとともに,最終的に本製品をご使用になる
ユーザー様のお手元に確実に届けられるよう,お取り計らい願います。
MANUAL NO. TOBP C720600 00F
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
PREFACE
Braking resistor unit and braking unit are used to con-sume regenerative energy from motor in the braking resistor unit at deceleration and to improve the transis-tor inverter braking ability.
Before using the braking resistor unit and braking unit, a thorough understanding of this manual is recom-mended. This instruction manual will be of great help for daily maintenance, inspection and troubleshoot-ing.
Inverters to which the braking resistor unit and braking unit can be connected are of the following series:
• YASKAWA AC Drive 1000 Series
• Varispeed Series
Wiring sequence should shut off power to the drive when a braking resistor Overload Relay Trip Contact (Thermal Protector Contact) output is triggered.
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
General Precautions
S Some drawings in this manual are shown with the protective cover or shields removed, in order to describe with more clarity. Make sure all covers and shields are replaced before operating this product.
S Since the drawings in this manual are represented examples, some are subject to differ from delivered products.
S This manual may be modified when necessary because of improvement of the product, modification or changes in specifications. Such modifications are denoted by a revised manual No.
S To order a copy of this manual, if your copy has been damaged or lost, contact your YASKAWA representative.
S YASKAWA is not responsible for any modification of the product made by the user since that will void your guarantee.
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
NOTES FOR SAFE OPERATION
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the braking unit and the braking resistor unit. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” or
“CAUTION.”
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury to personnel and damage to equipment.
It may also be used to alert against unsafe practices.
Even items described in CAUTION CAUTION may result in a vital accident in some situations. In either case, follow these important notes.
: These are steps to be taken to insure proper operation.
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
WIRING
WARNING
(Ref. page)
27
• Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electrical shock or a fire.
• High voltage exists at all terminals of braking unit and braking resistor unit.
Failure to observe this warning can result in an electrical shock.
• Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electrical shock or a fire.
• Wiring sequence should shut off power to the drive when a braking resistor Overload Relay Trip Contact (Thermal
Protector Contact) output is triggered.
Failure to observe this warning can result in a fire.
27
27
27
• When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning can result in personal injury.
27
• Make sure to ground the ground terminal.
(Ground resistance
200V class: 100 Ω . or less, 400V class: 10 Ω . or less)
Failure to observe this warning can result in an electrical shock.
27
• Short Circuit Current Rating (SCCR)
Install adequate branch short circuit protection according to applicable codes. Failure to comply could result in damage to the drive. The device is suitable for circuits capable of delivering 31,000 RMS symmet-rical
Amperes, 240 Vac maximum (200V Class), 480 Vac maximum (400V Class) and 575Vac (600V Class) or the SCCR rating of the drive it is connected to, which ever is greater.
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
CAUTION
S
Verify that the rated voltage of the braking unit and the braking resistor unit coincides with the AC power supply voltage.
Failure to observe this caution can result in personal injury or a fire.
(Ref. page)
27
27 S Do not perform a withstand voltage test of the braking unit and braking resistor unit.
It may cause semi − conductor elements to be damaged.
S Connect braking resistors, braking resistor units, and braking units as shown in the I/O wiring examples. Use properly rated wire in accordance with table 2 on page 31.
Otherwise, a fire can occur.
27
S
Tighten terminal screws to the specified tightening torque.
Failure to observe this caution can result in a fire.
S Be sure to connect braking resistors or braking resistor units to the braking units.
If neither braking resistor nor braking resistor unit is connected to a braking unit, the fault contact may instantaneously turn ON when the power is turned ON, resulting in malfunction of the inverter.
27
27
8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
OPERATION
WARNING
S
Only turn ON the input power supply after replacing the front cover. Do not remove the cover while current is flowing.
Failure to observe this warning can result in an electrical shock.
(Ref. page)
41
CAUTION
S
Never touch the heatsink or discharging resistor since the temperature is very high.
Failure to observe this caution can result in harmful burns to the body.
(Ref. page)
41
41 S Do not check signals during operation.
The machine or the inverter may be damaged.
S
Alltheconstantsofthethebrakingunit andthe brakingresistor unit have been preset at the factory. Do not change the settings unnecessarily.
41
9
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
CAUTION
S The control PC board employs CMOS ICs. Do not touch the
CMOS elements.
They are easily damaged by static electricity.
(Ref. page)
46
S Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury.
46
OTHERS
WARNING
S Never modify the product.
Failure to observe this warning can result in an electrical shock or personal injury and will invalidate the guarantee.
11
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
WARNING INDICATION
A warning label is displayed on the front cover of the braking unit, as shown below. Follow these instructions when handling the braking unit and the braking resistor unit.
Warning
Indication
$4#-+0)70+6
ෂ㒾ޓ㨃㧭㧾㧺㧵㧺㧳
ߌ߇ޔᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ᝪ߃ઃߌޔㆇォߩ೨ߦߪᔅߕขᛒ⺑ᦠࠍ⺒ࠎߢޔ
ޓߘߩᜰ␜ߦᓥߞߡߊߛߐޕ
ᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ㅢ㔚ਛ߮㔚Ḯㆤᢿᓟ㧡ಽએౝߪޔ㕙ࠞࡃࠍ㐿ߌ
ޓߥߢߊߛߐޕ
⏕ታߦធࠍⴕߞߡߊߛߐޕ
Ἣἴߩ߅ߘࠇ߇ࠅ߹ߔޕ
േᛶ᛫ེߩࠨࡑ࡞࠻࠶ࡊធὐߢ㔚Ḯࠍ
ޓㆤᢿߔࠆࠪࠤࡦࠬࠍ⚵ࠎߢߊߛߐޕ
㧹㨍㨥ޓ㨏㨍㨡㨟㨑ޓ㨕㨚㨖㨡㨞㨥ޓ㨛㨞㨑㨘㨑㨏㨠㨞㨕㨏ޓ㨟㨔㨛㨏㨗㧚
㧼㨘㨑㨍㨟㨑ޓ㨒㨛㨘㨘㨛㨣ޓ㨠㨔㨑ޓ㨕㨚㨟㨠㨞㨡㨏㨠㨕㨛㨚㨟ޓ㨕㨚ޓ㨠㨔㨑
ޓ㨙㨍㨚㨡㨍㨘ޓ㨎㨑㨒㨛㨞㨑ޓ㨕㨚㨟㨠㨍㨘㨘㨍㨠㨕㨛㨚ޓ㨛㨞ޓ㨛㨜㨑㨞㨍㨠㨕㨛㨚㧚
㧰㨕㨟㨏㨛㨚㨚㨑㨏㨠ޓ㨍㨘㨘ޓ㨜㨛㨣㨑㨞ޓ㨎㨑㨒㨛㨞㨑ޓ㨛㨜㨑㨚㨕㨚㨓
ޓ㨒㨞㨛㨚㨠ޓ㨏㨛㨢㨑㨞ޓ㨛㨒ޓ㨡㨚㨕㨠㧚
㨃㨍㨕㨠ޓ㧡ޓ㨙㨕㨚㨡㨠㨑㨟ޓ㨡㨚㨠㨕㨘ޓ㧰㧯ޓ㧮㨡㨟ޓ㨏㨍㨜㨍㨏㨕㨠㨛㨞㨟
㨐㨕㨟㨏㨔㨍㨞㨓㨑㧚
㨁㨟㨑ޓ㨜㨞㨛㨜㨑㨞ޓ㨓㨞㨛㨡㨚㨐㨕㨚㨓ޓ㨠㨑㨏㨔㨚㨕㨝㨡㨑㨟㧚
㧾㨕㨟㨗ޓ㨛㨒ޓ㨒㨕㨞㨑㧚
㨁㨟㨑ޓ㨟㨑㨝㨡㨑㨚㨏㨑㨞ޓ㨠㨛ޓ㨎㨞㨑㨍㨗ޓ㨜㨛㨣㨑㨞ޓ㨟㨡㨜㨜㨘㨥ޓ㨟㨕㨐㨑
ޓ㨛㨚ޓ㨛㨢㨑㨞㨘㨛㨍㨐ޓ㨞㨑㨘㨍㨥ޓ㨠㨞㨕㨜ޓ㨏㨛㨚㨠㨍㨏㨠ޓ㨛㨒ޓ
ޓ㨎㨞㨍㨗㨕㨚㨓ޓ㨞㨑㨟㨕㨟㨠㨛㨞㧚
㧺㧼㧶㨀㧠㧞㧡㧜㧞㧙㧝㧙㧜
㧹㧻㧰㧱㧸㧦㧯㧰㧮㧾㧙㧠㧜㧠㧡㧮
ޓ ޓޓޓޓޓ㧠㧜㧜㨂ޓ㧯㧸㧭㧿㧿ޓ㧲㧻㧾ޓ㧠㧡㨗㨃
ㅢ㔚೨ߦᧄࠞࡃࠍߪߕߒߡޔ
ࠦࡀࠢ࠲ߩ⸳ቯࠍ߅ߎߥߞߡਅߐޕ
㧔ขᛒ⺑ᦠෳᾖߩߎߣޕ㧕
4GOQXGVJKUEQXGTCPF
UGVVJGEQPPGEVQTU
DGHQTGVWTPKPIVJG
RQYGTQP
5GG+PUVTWEVKQPU
.KIJVU
YJGP
DTCMKPI
Example of Braking Unit Model CDBR−4045B
12
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Warning Indication
ෂ㒾ޓ㨃㧭㧾㧺㧵㧺㧳
ߌ߇ޔᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ᝪ߃ઃߌޔㆇォߩ೨ߦߪᔅߕขᛒ⺑ᦠࠍ⺒ࠎߢޔ
ޓߘߩᜰ␜ߦᓥߞߡߊߛߐޕ
ᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ㅢ㔚ਛ߮㔚Ḯㆤᢿᓟ㧡ಽએౝߪޔ㕙ࠞࡃࠍ
ޓ㐿ߌߥߢߊߛߐޕ
⏕ታߦធࠍⴕߞߡߊߛߐޕ
Ἣἴߩ߅ߘࠇ߇ࠅ߹ߔޕ
േᛶ᛫ེߩࠨࡑ࡞࠻࠶ࡊធὐߢ㔚Ḯࠍ
ޓㆤᢿߔࠆࠪࠤࡦࠬࠍ⚵ࠎߢߊߛߐޕ
㧹㨍㨥ޓ㨏㨍㨡㨟㨑ޓ㨕㨚㨖㨡㨞㨥ޓ㨛㨞㨑㨘㨑㨏㨠㨞㨕㨏ޓ㨟㨔㨛㨏㨗㧚
㧼㨘㨑㨍㨟㨑ޓ㨒㨛㨘㨘㨛㨣ޓ㨠㨔㨑ޓ㨕㨚㨟㨠㨞㨡㨏㨠㨕㨛㨚㨟ޓ㨕㨚ޓ㨠㨔㨑
ޓ㨙㨍㨚㨡㨍㨘ޓ㨎㨑㨒㨛㨞㨑ޓ㨕㨚㨟㨠㨍㨘㨘㨍㨠㨕㨛㨚ޓ㨛㨞ޓ㨛㨜㨑㨞㨍㨠㨕㨛㨚㧚
㧰㨕㨟㨏㨛㨚㨚㨑㨏㨠ޓ㨍㨘㨘ޓ㨜㨛㨣㨑㨞ޓ㨎㨑㨒㨛㨞㨑ޓ㨛㨜㨑㨚㨕㨚㨓
ޓ㨒㨞㨛㨚㨠ޓ㨏㨛㨢㨑㨞ޓ㨛㨒ޓ㨡㨚㨕㨠㧚
㨃㨍㨕㨠ޓ㧡ޓ㨙㨕㨚㨡㨠㨑㨟ޓ㨡㨚㨠㨕㨘ޓ㧰㧯ޓ㧮㨡㨟ޓ㨏㨍㨜㨍㨏㨕㨠㨛㨞㨟
㨐㨕㨟㨏㨔㨍㨞㨓㨑㧚
㨁㨟㨑ޓ㨜㨞㨛㨜㨑㨞ޓ㨓㨞㨛㨡㨚㨐㨕㨚㨓ޓ㨠㨑㨏㨔㨚㨕㨝㨡㨑㨟㧚
㧾㨕㨟㨗ޓ㨛㨒ޓ㨒㨕㨞㨑㧚
㨁㨟㨑ޓ㨟㨑㨝㨡㨑㨚㨏㨑㨞ޓ㨠㨛ޓ㨎㨞㨑㨍㨗ޓ㨜㨛㨣㨑㨞ޓ㨟㨡㨜㨜㨘㨥ޓ㨟㨕㨐㨑
ޓ㨛㨚ޓ㨛㨢㨑㨞㨘㨛㨍㨐ޓ㨞㨑㨘㨍㨥ޓ㨠㨞㨕㨜ޓ㨏㨛㨚㨠㨍㨏㨠ޓ㨛㨒ޓ
ޓ㨎㨞㨍㨗㨕㨚㨓ޓ㨞㨑㨟㨕㨟㨠㨛㨞㧚
㧺㧼㧶㨀㧠㧞㧡㧜㧞㧙㧝㧙㧜
13
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
CONTENTS
NOTES FOR OPERATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5
1 RECEIVING - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
1.1 NAMEPLATE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
2 INSTALLATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16
2.1 LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16
2.2 INSTALLATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16
2.3 REPLACEMENT OF CONVENTIONAL BRAKING UNITS
WITH NEW UNITS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 25
3 WIRING - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 27
3.1 REMOVING AND REPLACING THE COVERS OF
THE BRAKING UNIT (MODELS CDBR-2015B, -2015C,
-2022B, -2022C, -4030B, -4045B) - - - - - - - - - - - - - - - - - - - 27
3.2 SECTION NAMES - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 28
3.3 CIRCUITS AND WIRING SPECIFICATIONS - - - - - - - - - - - 31
3.4 WIRING PRECAUTIONS - - - - - - - - - - - - - - - - - - - - - - - - - 32
3.5 INTERCONNECTION - - - - - - - - - - - - - - - - - - - - - - - - - - - 33
4 OPERATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
4.1 ADJUSTMENT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
4.2 POWER SUPPLY VOLTAGE SELECTION CONNECTOR
SETTING - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
4.3 MASTER/SLAVE SELECTION CONNECTOR SETTING - - 44
4.4 PARALLEL CONNECTION OF BRAKING UNIT - - - - - - - - - 44
4.5 OPERATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
5 TROUBLESHOOTING - - - - - - - - - - - - - - - - - - - - - - - - - - - 46
6 SPECIFICATIONS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
6.1 BRAKING UNIT AND BRAKING RESISTOR UNIT
APPLICATION LIST - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
6.2 BRAKING UNIT FOR 575V CLASS APPLICATION LIST - - 49
6.3 LIST OF APPLICABLE/NOT APPLICABLE COMBINATIONS
WITH CONVENTIONAL MODELS (VS-616HII/H3,
VS-616GII/G3, VS-676) - - - - - - - - - - - - - - - - - - - - - - - - - - 50
6.4 BRAKING UNIT SPECIFICATIONS - - - - - - - - - - - - - - - - - - 51
6.5 BRAKING RESISTOR UNIT SPECIFICATIONS - - - - - - - - - 52
6.6 MODELS AND CODE NOS. OF BRAKING UNIT AND
BRAKING RESISTOR UNIT - - - - - - - - - - - - - - - - - - - - - - - 53
14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
1 RECEIVING
1 RECEIVING
CAUTION
• Do not install and attempt to use a braking resistor or braking resistor unit If there are any damaged or missing components.
Failure to comply can result in personal injury.
The braking resistor unit and braking unit have been put through severe tests at the factory before shipment. After unpacking, however, check and see the following. If any malfunctions are found, contact your YASKAWA representative.
• Their nameplate data meet your requirements.
• They have sustained no damage while in transit.
• Fastening bolts and screws are not loose.
For long term storage, the unit should be kept in a clean area indoors.
1.1 NAMEPLATE
(1) NAMEPLATE INFORMATION (BRAKING UNIT)
Braking Unit
Model Number
(2) NAMEPLATE INFORMATION (BRAKING RESISTER UNIT)
Braking Resistor
Unit Model Number
Design
Revision
Order
15
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
2 INSTALLATION
2.1 LOCATION
If the units are temporarily stored or machine stops for an extended length of time, the following precautions should be taken. Store the units at pollution level
2 or less (UL standard) and under the following conditions.
• Free from rainfall and drops of water.
• Clean and dry.
• Free from corrosive gases and liquids.
• Free from dirt and dust.
• Ambient temperature: 14 to 104 ° F, 10 to 40 ° C.
• Humidity: 90% RH or less (no condensation)
• Free from vibration.
2.2 INSTALLATION
For full use of the braking resistor unit or braking unit functions, install the units at pollution level 2 or less (UL standard) and in a location to satisfy the following conditions:
Figs. 1 to 8 show the external dimensions and the spaces from the periphery.
• Provide the spaces shown in Figs. 1 to 8 between the units and the periphery.
• Since the braking resistor unit generates heat, provide sufficient spaces from devices which are weak against heat.
• Install the units at such locations that all requirements described in
Par. 2.1 “LOCATION” are satisfied.
16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
2 INSTALLATION
• Install the units in the directions shown in Figs. 1 to 8. There will be no problem if they are installed vertically.
4−M4 MTG HOLE 2.83 (72) 2.73 (66.5)
1.18 (30)
OR MORE
1.5 (38) 1.5 (38)
5.04 (128)
5.51 (140)
1.18 (30)
OR MORE
4.51 (114.5)
5.45 (138.5)
Fig. 1
3−LEAD WIRE OUTLET
[0.87 (20) DIA RUBBER BUSH]
Braking Unit Dimensions in inches (mm) CDBR-2015B, -2015C,
-2022B,-2022C,-4030B, -4045B
17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3.94 (100)
4 − M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M4
2.30
(58.5)
3 − LEAD WIRE
OUTLET
1.10 (28) DIA
RUBBER BUSH
1.18 (30)
OR MORE
1.97 (50)
3.94 (100)
5.51 (140)
1.18 (30)
OR MORE
6.57 (167)
Fig. 2 Braking Unit Dimensions in inches (mm) CDBR − 5037B
18
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
2 INSTALLATION
5.51 (140)
4−M6
MTG HOLE
Fig. 3
MAIN CIRCUIT
TERMINAL M5
3.86 (98)
3.94 (100)
2.32
1.97 (50)
(59)
5.51 (140)
7.09 (180)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Braking Unit Dimensions in inches (mm) CDBR-2045B
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2−LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
19
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
5.51 (140)
4 − M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M6 4.09
(104)
3.94 (100)
2.32 1.97 (50)
(59)
5.51 (140)
7.09 (180)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Fig. 4 Braking Unit Dimensions in inches (mm) CDBR − 2110B
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
20
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
2 .
INSTALLATION
7.09 (180)
4 − M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M5
3.86 (98)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
5.45 (138.5)
2.70
1.97 (50)
(68.5) 7.09 (180)
8.66 (220)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Fig. 5 Braking Unit Dimensions in inches (mm) CDBR − 4090B, − 5110B
21
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
8.27 (210)
4 − M6
MTG HOLE
Fig. 6
MAIN CIRCUIT
TERMINAL M6 4.09
(104)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
6.16 (156.5)
4.67 (118.5) 1.97 (50)
8.27 (210)
9.84 (250)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Braking Unit Dimensions in inches (mm) CDBR − 4220B, − 5300B
22
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
2 INSTALLATION b a b
Braking Resistor
Unit Model
(LKEB )
20P7
21P5
22P2
23P7
25P5
27P5
40P7
41P5
42P2
43P7
45P5
47P5
Dimensions in inches (mm)
A B C D E
4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
Fig. 7 Braking Resistor Unit Dimensions in inches (mm) [for 0.5 to 10HP (0.4 to
7.5kW)]
23
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Braking Resistor
Unit Model
(LKEB-
)
2011
2015
2018
2022
4011
4015
4018
4022
4030
4037
4045
Dimensions in inches (mm)
A B C D E
10.48 (266) 21.38 (543) 9.69 (246) 13.39 (340) M8
14.02 (356) 21.38 (543) 13.23 (336) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6
13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
14.02 (356) 37.64 (956) 13.23 (336) 29.13 (740) M8
17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8
17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8
Fig. 8 Braking Resistor Unit Dimensions in inches (mm) [for 15 to 60HP (11 to
45kW)]
24
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
2 INSTALLATION
2.3 REPLACEMENT OF CONVENTIONAL BRAKING
UNITS WITH NEW UNITS
To replace conventional braking units (models CDBR-2015, -2022, -4030, -4045) with new units (CDBR-2015B, -2015C, -2022B, -2022C, -4030B, -4045B), an exclusive-use attachment is required. Contact your YASKAWA representative.
4−M6 MTG HOLE
ATTACHMENT
0.28(7)
0.79
(20)
3.94 (100)
0.79
(20)
3.94 (100)
5.51 (140)
0.28(7)
5.45 (138.5)
Fig. 9
Code No.: DACT32732−AD
Mounting Dimensions of Attachment in inches (mm)
0.39 (10)
25
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
The main circuit terminal symbols are different between conventional models and new models. Refer to the following table.
Table 1 Main Circuit Terminal Symbols
Conventional Models
Example: CDBR-2015
N
P
P
0
B
New Models
Example: CDBR-2015B,
-2015C
0
0
26
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
3 WIRING
3.1 REMOVING AND REPLACING THE COVERS OF
THE BRAKING UNIT (MODELS CDBR-2015B,
-2015C, -2022B, -2022C,-4030B, -4045B)
(1) Romoving and Replacing the Terminal Cover
For removing, grasp the terminal cover at c on borh sides and then lift in the direciton of d . For replacing, reverse the method.
Terminal
Cover
(2) Removing and Replacing the lndicating Cover
Remove the terminal cover first. Push down on the lever in the direction of c and lift the cover in the direction of d . For replacing, reverse the method.
Indicating Cover
Lever
27
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3.2 SECTION NAMES
Figs. 10, 11 and 12 show appearance and each section name of braking unit and braking resistor unit respectively.
Thermal overload relay protects the braking resistor unit for models LKEB-20P7 to -27P5 and -40P7 to -4015. Thermal protector protects the braking resistor unit for models LKEB-2011 to -2022 and -4018 to -4045.
/1&'.%&$4$
8%.#55(14M9
$4#-+0)70+6
ෂ㒾ޓ㨃㧭㧾㧺㧵㧺㧳
ߌ߇ޔᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ᝪ߃ઃߌޔㆇォߩ೨ߦߪᔅߕขᛒ⺑ᦠࠍ⺒ࠎߢޔߘߩᜰ␜
ޓߦᓥߞߡߊߛߐޕ
ᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ㅢ㔚ਛ߮㔚Ḯㆤᢿᓟ㧡ಽએౝߪޔ㕙ࠞࡃࠍ㐿ߌߥߢ
ޓߊߛߐޕ
⏕ታߦធࠍⴕߞߡߊߛߐޕ
Ἣἴߩ߅ߘࠇ߇ࠅ߹ߔޕ
േᛶ᛫ེߩࠨࡑ࡞࠻࠶ࡊធὐߢ㔚Ḯࠍ
ޓㆤᢿߔࠆࠪࠤࡦࠬࠍ⚵ࠎߢߊߛߐޕ
㧹㨍㨥ޓ㨏㨍㨡㨟㨑ޓ㨕㨚㨖㨡㨞㨥ޓ㨛㨞
㨑㨘㨑㨏㨠㨞㨕㨏ޓ㨟㨔㨛㨏㨗㧚
㧼㨘㨑㨍㨟㨑ޓ㨒㨛㨘㨘㨛㨣ޓ㨠㨔㨑ޓ㨕㨚㨟㨠㨞㨡㨏㨠㨕㨛㨚㨟ޓ㨕㨚ޓ㨠㨔㨑
ޓ㨙㨍㨚㨡㨍㨘ޓ㨎㨑㨒㨛㨞㨑ޓ㨕㨚㨟㨠㨍㨘㨘㨍㨠㨕㨛㨚ޓ㨛㨞ޓ㨛㨜㨑㨞㨍㨠㨕㨛㨚㧚
㧰㨕㨟㨏㨛㨚㨚㨑㨏㨠ޓ㨍㨘㨘ޓ㨜㨛㨣㨑㨞ޓ㨎㨑㨒㨛㨞㨑ޓ㨛㨜㨑㨚㨕㨚㨓
ޓ㨒㨞㨛㨚㨠ޓ㨏㨛㨢㨑㨞ޓ㨛㨒ޓ㨡㨚㨕㨠㧚
㨃㨍㨕㨠ޓ㧡ޓ㨙㨕㨚㨡㨠㨑㨟ޓ㨡㨚㨠㨕㨘ޓ㧰㧯ޓ㧮㨡㨟ޓ㨏㨍㨜㨍㨏㨕㨠㨛㨞㨟
ޓ㨐㨕㨟㨏㨔㨍㨞㨓㨑㧚
㨁㨟㨑ޓ㨜㨞㨛㨜㨑㨞ޓ㨓㨞㨛㨡㨚㨐㨕㨚㨓ޓ㨠㨑㨏㨔㨚㨕㨝㨡㨑㨟㧚
㧾㨕㨟㨗ޓ㨛㨒ޓ㨒㨕㨞㨑㧚
㨁㨟㨑ޓ㨟㨑㨝㨡㨑㨚㨏㨑㨞ޓ㨠㨛ޓ㨎㨞㨑㨍㨗ޓ㨜㨛㨣㨑㨞ޓ㨟㨡㨜㨜㨘㨥ޓ㨟㨕㨐㨑
ޓ㨛㨚ޓ㨛㨢㨑㨞㨘㨛㨍㨐ޓ㨞㨑㨘㨍㨥ޓ㨠㨞㨕㨜ޓ㨏㨛㨚㨠㨍㨏㨠ޓ㨛㨒ޓ
ޓ㨎㨞㨍㨗㨕㨚㨓ޓ㨞㨑㨟㨕㨟㨠㨛㨞㧚
㧺㧼㧶㨀㧠㧞㧡㧜㧞㧙㧝㧙㧜
/#56'4
5.#8'
Power Supply Selection
Connector
Master/Slave
Selection Connector
Calibration Resistor
(Adjusted Prior to
Shipment)
Operation Indicator
(Lights when Discharging.)
7UGq%EQRRGTYKTGUQPN[4GHGTVQOCPWCNHQTEQPPGEVKQPU
Control Circuit
Terminals 1 to 6
Charge Indicator
(Charge Lamp)
Control Circuit Terminals
0 0
Fig. 10 Braking Resistor Unit Model CDBR-2015B (Terminal Cover and Indicating Cover Removed)
Remove the label on the terminal block before using the braking unit.
28
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
Top Side
Thermal Overload Relay
(Automatically Reset)
Control Circuit Terminals
B 㧘 P 㧘 1 㧘 2
Bottom Side
Lead Wire Outlet
(Rubber Bush)
Fig. 11 Braking Resistor Unit Model LKEB-20P7 SPEC: B (Front Cover
Removed)
Note: 1. External terminals for SPEC: B models LKEB-
20P7 and 40P7 are located up to 20 mm further inside the unit when compared to the same models for SPEC: A.
2. External terminals for SPEC:B models LKEB-
21P5 to 27P5 and LKEB-41P5 to 47P5 are located up to 15 mm higher on the unit when compared to the same models for SPEC: A.
29
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Resistor
Thermal
Overload
Protector
Lead Wire Outlet
(Rubber Bush)
Control Circuit Terminals
B, P, 1, 2
Fig. 12 Braking Resistor Unit Model LKEB − 2022 (Front Cover Removed)
30
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
3.3 CIRCUITS AND WIRING SPECIFICATIONS
Table 2 Circuits and Wiring Specifications
Name
Braking Unit
(Models CDBR-
2015B, -2015C
-2022B, -2022C
-4030B, -4045B
-5037B)
Circuit
Main
Control
Terminals
1 2 3
4 5 6
0
0
Wire
Size
AWG
(mm
2
)
12-10
(3.5-5.5)
18-14
(0.75-2)
Wire Type
Terminal
Screw
Max.
Torque lb.in (N·m)
M4 13.3 (1.50)
Braking Unit
(Model CDBR-
2045B, -4090B,
-5110B)
Braking Unit
(Model
CDBR-2110B,
-4220B, -5300B)
Braking Resistor
Unit
(Model LKEB )
Main
Control
Main
Control
Main
Control
1 2 3
4 5 6
0
0
1 2 3
4 5 6
0
0
B P
1 2
10-8
(5.5-8)
18-14
(0.75-2)
4 (22)
8-6
(8-14)
*1
18-14
(0.75-2)
12-10
(3.5-5.5)
18-14
(0.75-2)
600V
(High
Voltage)
*3 vinyl sheathed wire or equivalent
M5
M4
M6
M4
M4
(M5)
M4
*2
21.7 (2.45)
15.6 (1.76)
43.4 (4.90)
15.6 (1.76)
15.6 (1.76)
(21.7(2.45))
15.6 (1.76)
* 1. For wire size of 8-6(8-14), use UL Listed copper wires (rated at 75 ° C).
* 2. M4 for Models LKEB-20P7 to -27P5 or -40P7 to -4015.
M5 for Models LKEB-2011 to -2022 or -4018 to -4045.
* 3. Models-5037B, -5100B, and -5300B can reach an operating voltage of 1040 VDC.
Please select wire which is suitable for the operating voltage.
31
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3.4 WIRING PRECAUTIONS
(1) Wiring Leading-in Method
Lead in the wire through the knockout hole on the unit bottom. Since the knockout hole is provided with a rubber bush, cut the rubber bush central crosswise with a blade and lead the wire through.
(2) Separation from Signal Lines
Since strong noise component is superimposed on the braking resistor unit and braking unit wiring, separate the units from signal lines which are weak against noise.
(3) Wiring Distance
• Wiring distance between the braking resistor unit and braking unit or braking unit and inverter must be provided as shown in Fig. 13. Make sure to bundle the wires between the units.
• When connecting two or more braking units in parallel, refer to 4.4,
“Parallel Connection of Braking Unit” for details.
Braking Resistor
Unit
Braking Unit Inverter
Fig. 13 Wiring Distance
32.8ft
(10 m) or less
16.4ft
(5 m) or less
32
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
(4) Grounding Method
• Mount the braking resistor unit on a grounded metallic plate. When it cannot be mounted on a grounded metallic plate, pull out the lead wire from the mounting screw section to ground.
• Braking unit grounding terminal must be provided with the ground resistance of 100 Ω or less in 200V class ,or 10 Ω or less in 400V class.
• Use the sizes specified in “INTERNAL CONNECTION SPECIFICA-
TIONS” for grounding cables.
3.5 INTERCONNECTION
Figs. 14 to 20 show the interconnecting diagrams of the braking unit or braking resistor unit and VS-616G5.
Refer to Par. 3.3, “Wiring Precautions” for proper wiring in actual wiring design and work.
Be sure to connect braking resistors or braking resistor units to the braking units.
Connect only braking resistors or Braking Resistor Units (LKEB-XXXX) to
Braking Units.
1. If using another braking resistor instead of YASKAWA braking resistor unit, wiring sequence should shut off power to the drive when a braking resistor Overload Relay Trip Contact (Thermal
Protector Contact) output is triggered.
2. Faulty wiring can result in fire. Make sure the interconnecting diagrams are followed correctly.
33
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
34
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
35
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
36
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
37
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
38
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3 WIRING
39
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
40
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
4 .
OPERATION
4. OPERATION
4.1 ADJUSTMENT
The braking resistor unit and braking unit do not have to be adjusted.
Especially, do not readjust the braking unit except in the case described in Par. 4.2,
“Power Supply Voltage Selection Connector Setting.”
4.2 POWER SUPPLY VOLTAGE SELECTION CON-
NECTOR SETTING
It may be necessary to select power supply voltage selection connector for braking unit according to main circuit power supply type. Table 3 shows the relationship between the power supply voltage selection connector and braking start voltage.
The following is the setting prior to shipment:
S 200V class : 220V
S 400V class : 440V
S 575V class : 575V
For removing the terminal cover and the indicating cover, refer to Par. 3.1.
41
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
$4#-+0)70+6
ෂ㒾ޓ㨃㧭㧾㧺㧵㧺㧳
ߌ߇ޔᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ᝪ߃ઃߌޔㆇォߩ೨ߦߪᔅߕขᛒ⺑ᦠࠍ⺒ࠎߢޔߘߩᜰ␜
ޓߦᓥߞߡߊߛߐޕ
ᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ㅢ㔚ਛ߮㔚Ḯㆤᢿᓟ㧡ಽએౝߪޔ㕙ࠞࡃࠍ㐿ߌߥߢ
ޓߊߛߐޕ
⏕ታߦធࠍⴕߞߡߊߛߐޕ
Ἣἴߩ߅ߘࠇ߇ࠅ߹ߔޕ
േᛶ᛫ེߩࠨࡑ࡞࠻࠶ࡊធὐߢ㔚Ḯࠍ
ޓㆤᢿߔࠆࠪࠤࡦࠬࠍ⚵ࠎߢߊߛߐޕ
㧹㨍㨥ޓ㨏㨍㨡㨟㨑ޓ㨕㨚㨖㨡㨞㨥ޓ㨛㨞
㨑㨘㨑㨏㨠㨞㨕㨏ޓ㨟㨔㨛㨏㨗㧚
㧼㨘㨑㨍㨟㨑ޓ㨒㨛㨘㨘㨛㨣ޓ㨠㨔㨑ޓ㨕㨚㨟㨠㨞㨡㨏㨠㨕㨛㨚㨟ޓ㨕㨚ޓ㨠㨔㨑
ޓ㨙㨍㨚㨡㨍㨘ޓ㨎㨑㨒㨛㨞㨑ޓ㨕㨚㨟㨠㨍㨘㨘㨍㨠㨕㨛㨚ޓ㨛㨞ޓ㨛㨜㨑㨞㨍㨠㨕㨛㨚㧚
㧰㨕㨟㨏㨛㨚㨚㨑㨏㨠ޓ㨍㨘㨘ޓ㨜㨛㨣㨑㨞ޓ㨎㨑㨒㨛㨞㨑ޓ㨛㨜㨑㨚㨕㨚㨓
ޓ㨒㨞㨛㨚㨠ޓ㨏㨛㨢㨑㨞ޓ㨛㨒ޓ㨡㨚㨕㨠㧚
㨃㨍㨕㨠ޓ㧡ޓ㨙㨕㨚㨡㨠㨑㨟ޓ㨡㨚㨠㨕㨘ޓ㧰㧯ޓ㧮㨡㨟ޓ㨏㨍㨜㨍㨏㨕㨠㨛㨞㨟
㨐㨕㨟㨏㨔㨍㨞㨓㨑㧚
㨁㨟㨑ޓ㨜㨞㨛㨜㨑㨞ޓ㨓㨞㨛㨡㨚㨐㨕㨚㨓ޓ㨠㨑㨏㨔㨚㨕㨝㨡㨑㨟㧚
㧾㨕㨟㨗ޓ㨛㨒ޓ㨒㨕㨞㨑㧚
㨁㨟㨑ޓ㨟㨑㨝㨡㨑㨚㨏㨑㨞ޓ㨠㨛ޓ㨎㨞㨑㨍㨗ޓ㨜㨛㨣㨑㨞ޓ㨟㨡㨜㨜㨘㨥ޓ㨟㨕㨐㨑
ޓ㨛㨚ޓ㨛㨢㨑㨞㨘㨛㨍㨐ޓ㨞㨑㨘㨍㨥ޓ㨠㨞㨕㨜ޓ㨏㨛㨚㨠㨍㨏㨠ޓ㨛㨒ޓ
ޓ㨎㨞㨍㨗㨕㨚㨓ޓ㨞㨑㨟㨕㨟㨠㨛㨞㧚
㧺㧼㧶㨀㧠㧞㧡㧜㧞㧙㧝㧙㧜
/1&'.%&$4$
8%.#55(14M9
200 V class
200 V
208 V
220 V
230 V
7UGq%EQRRGTYKTGUQPN[4GHGTVQOCPWCNHQTEQPPGEVKQPU
400 V class
380 V
400 V
415 V
440 V
460 V
Fig. 21 Braking Unit Power Supply Voltage Selection
(Models CDBR-2015B, -2015C, -2022B, -2022C, -4030B, -4045B,
Terminal Cover and Indicating Cover Removed)
42
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
4 OPERATION
200 V class
200 V
208 V
220 V
230 V
575 V class
500 V
400 V class
380 V
400 V
415 V
440 V
460 V
575 V
Fig. 22 Braking Unit Power Supply Voltage Selection
(Models CDBR-2045B, -2110B, -4090B, -5037B, -5110B, -5300B,
Indicating Cover Removed)
Table 3 Power Supply Voltage Selection Connector and Braking Start Voltage
200 V
Class*
Power
Supply
Voltage
230 V
220 V
208 V
200 V
–
Braking Start
Voltage
(PN Bus-bar
Voltage)
400 V
Class*
Power
Supply
Voltage
380 V (TYP) 460 V
365 V (TYP) 440 V
345 V (TYP) 415 V
330 V(TYP) 400 V
– 380 V
* Allowable voltage fluctuation is ± 10%
Braking Start
Voltage
(PN Bus-bar
Voltage)
760 V (TYP)
730 V (TYP)
690 V (TYP)
660 V (TYP)
630 V(TYP)
575 V
Class*
Power
Supply
Voltage
575 V
–
–
500 V
–
Braking Start
Voltage
(PN Bus-bar
Voltage)
950 V (TYP)
–
–
825 V (TYP)
–
43
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
4.3 MASTER/SLAVE SELECTION CONNECTOR
SETTING
Selection Connector Setting MASTER side is selected prior to shipment. Use the units without changing the setting.
SLAVE side is selected when more than one braking unit is combined to use and braking start levels must coincide. Refer to Par. 4.4, “Parallel Connection of Braking Unit” for details.
4.4 PARALLEL CONNECTION OF BRAKING UNIT
For using more than one parallel-connected braking unit, connect and select the connectors as follows. (See Fig. 23.)
• Braking units have a MASTER/SLAVE selection connector. (See
Fig. 10.) Select MASTER side only for braking unit 1 and select
SLAVE side for braking units 2 and 3.
• Properly connect the MASTER output to the SLAVE input. Refer to Fig. 23 for details.
• Use properly rated wire in accordance with table 2 on page 31.
• Use twisted-pair wires of 1mm or less for connection between 5, 6 and 1, 2 of the braking units.
• Parallel connection of braking unit is possible up to a maximum of
10 units.
Failure to use the wiring and connectors specified above can damage the braking resistor, braking resistor unit, and the drive itself.
44
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
4 OPERATION
+ 3 −
Drive
(Inverter)
(Thermal Relay Trip Contact)
1
P
Braking Resistor
Overheat Contact
2
B
Braking
Resistor
Unit
1
P
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
2
B
Braking
Resistor
Unit
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1
P
− + + 0 − 0
MASTER
− + + 0
MASTER
− 0 − + + 0
MASTER
− 0
1
2
SLAVE
Braking Unit 1
3 4
+15
5
6
Twisted pair cable
1
2
Max. 1 m
SLAVE
Braking Unit 2
3 4
5
6
Twisted pair cable
1
2
Max. 1 m
SLAVE
Braking Unit 3
3 4
5
6
2
B
Braking
Resistor
Unit
Cooling Fin Overheat Contact
(Thermoswitch Contact)
Master Unit
Cooling Fin Overheat Contact
(Thermoswitch Contact)
Slave Unit 1
Cooling Fin Overheat Contact
(Thermoswitch Contact)
Slave Unit 2
Fig. 23 Example of Parallel Connection of Three Braking Units
4.5 OPERATION
Check that required deceleration characteristics can be obtained. While the braking unit is operating, BRAKE lamp lights for easy check of operation.
High voltage is applied to the braking unit. At normal operation, do not operate the unit without cover.
45
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
5 TROUBLESHOOTING
Only authorized personnel should be permitted to perform maintenance and inspections or replace parts.
No.
1
2
3
4
5
Fault Status
Braking resistor unit overload relay
(or thermal overload protector) trips when not decelerating.
Inverter trips at overvoltage (ov).
Cause
• Without braking unit
Inverter built-in main circuit discharging transistor short circuited
• With braking unit
Braking unit main circuit discharging transistor short circuited
Improper braking unit power supply voltage selection connector setting
(Power supply voltage > power supply voltage selection position)
Insufficient braking resistor unit capacity
Improper wiring
Braking unit fault
Corrective Action
Replace the inverter.
Replace the unit.
Set it again.
Examine the braking conditions again.
Check and repair.
Replace the unit.
Braking resistor unit overload relay
(or thermal protector) sometimes trips.
Insufficient braking resistor unit capacity
Examine the braking conditions again.
Braking unit trips by heat sink overheat.
Excessive start/stop switching frequency
Excessive load inertia
Examine the operating conditions again.
Improper combination of braking unit and braking resistor unit
Reset.
Ambient temperature 104 ° F (40 ° C) Reduce it.
Braking unit fault Replace the unit.
The fault contact of a braking unit instantaneously turned ON when the power was turned ON.
Neither a braking resistor nor a braking resistor unit is connected to the braking unit.
Connect a braking resistor or braking resistor unit to the braking unit.
46
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6 SPECIFICATIONS
6 SPECIFICATIONS
6.1 BRAKING UNIT AND BRAKING RESISTOR UNIT
APPLICATION LIST
The applicable braking unit and braking resistor unit models differ depending on the inverter model. Refer to the catalog of the relevant inverter.
Example: 200-V Class Inverter Model CIMR-G5
Inverter
Max. Applicable
Motor Capacity
HP(kW)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
Braking Unit
Model
(CDBR
)
–
–
2015B,
2015C
2015B,
2015C
2022B,
2022C
2022B,
2022C
–
–
–
–
–
Unit
Q’ty
2015B,
2015C
2015B,
2015C
2022B,
2022C
2
2
2
2022B,
2022C
2
2110B 1
2110B 1
2110B 1
–
–
–
–
–
–
–
1
1
1
1
Model
(LKEB
)
20P7
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2015
2015
2022
Braking Resistor Unit
Resistor Spec.
(per unit)
70W 200 Ω
70W 200 Ω
260W 100 Ω
260W 70 Ω
390W 40 Ω
520W 30 Ω
780W 20 Ω
2400W 13.6
3000W 10
4800W 8 Ω
4800W 6.8
3000W 10
3000W 10
4800W 6.8
Ω
Ω
Ω
Ω
Ω
Ω
Unit
Q’ty
1
1
1
1
1
1
1
1
1
1
Approx.
Braking
Torque
(10%ED)
%
220
125
125
120
125
115
125
1 125
2
2
2
125
125
125
125
100
120
75 (55)
100 (75)
120 (90)
150 (110)
2022
2022
2022
2022
4800W 6.8
Ω
4800W 6.8
Ω
4800W 6.8
Ω
4800W 6.8
Ω
2
3
4
5
100
110
120
100
Note: The above table lists the applicable braking unit and braking resistor unit models for the 200-V class inverter model CIMR-G5 . For other inverter models, refer to the catalog of the relevant inverter.
47
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Example: 400 − V Class Inverter Model CIMR − G5 j
Inverter
Max Applicable
Motor Capacity
HP(kW)
Braking Unit
Model
(CDBR
− j
)
Unit
Q’ty
Braking Resistor Unit
Model
(LKEB
− j
)
Resistor Spec.
(per unit)
Unit
Q’ty
Approx.
Braking
Torque
(10%ED)
%
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
150 (110)
200 (160)
300 (220)
400 (300)
800 (600)
−
−
−
−
−
−
−
−
−
4030B
4030B
4030B
4045B
4045B
4030B
4045B
4030B
4220B
4220B
4220B
4220B
−
−
−
−
−
−
−
−
−
1
1
1
1
1
2
2
3
1
1
2
4
40P7
40P7
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4030
4045
4030
4045
4037
4045
4045
70W 750 Ω
70W 750 Ω
260W 400 Ω
260W 250 Ω
1
1
390W 150 Ω
520W 100 Ω
780W 75 Ω
1040W 50 Ω
1560W 40 Ω
1
4800W 32 Ω
4800W 27.2
Ω
6000W 20 Ω
9600W 1 6 Ω
1
1
9600W 13.6
Ω 1
6000W 20 Ω
9600W 13.6
Ω
2
2
6000W 20 Ω 3
9600W 13.6
Ω
9600W 16 Ω
4
5
9600W 13.6
Ω 6
9600W 13.6
Ω 12
1
1
1
1
1
1
1
1
Note: The above table lists the applicable braking unit and braking resistor unit models for the 400 − V class inverter model CIMR − G5 j . For other inverter models, refer to the catalog of the relevant inverter.
135
125
125
125
125
125
230
130
125
135
135
135
130
125
135
145
100
140
110
110
110
48
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6 SPECIFICATIONS
6.2 BRAKING UNIT FOR 575V CLASS APPLICATION
LIST
Example: 575-V Class Inverter Model CIMR-G5
Inverter
Max Applicable
Motor Capacity
HP(kW)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
120 (90)
150 (110)
200 (160)
Braking Unit
Model
(CDBR-
–
–
–
–
–
–
5037B
5037B
5037B
5037B
5037B
5110B
5110B
5110B
5300B
)
Unit Q’ty
–
–
–
–
–
–
1
1
1
2
2
1
1
1
1
Braking Resistor Unit Approx.
Braking
Torque
Resistor Spec.
(10%ED)
%
560W 150 Ω
560W 150 Ω
750W 100 Ω
1100W 75 Ω
1500W 50 Ω
2300W 40 Ω
2800W 38 Ω
3900W 33 Ω
4900W 27 Ω
5900W 22 Ω
7200W 18 Ω
9800W 13.6
Ω
12000W 11 Ω
15000W 9 Ω
21000W 6.8
Ω
180
125
140
125
140
140
125
110
110
110
110
105
110
110
100
Note: The above table lists the applicable braking unit and braking resistor unit models for the 575-V class inverter model CIMR-G5 . For other inverter models, refer to the catalog of the relevant inverter.
49
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6.3
LIST OF APPLICABLE/NOT APPLICABLE COMBINA-
TIONS WITH CONVENTIONAL MODELS (VS
−
616HII/
H3, VS
−
616GII/G3, VS
−
676)
Conventional
Model
VS − 616HII/H3
VS − 616GII/G3
VS − 676
VS − 616HII/H3
VS − 616GII/G3
VS − 676
VS − 616HII/H3
VS − 616GII/G3
VS − 676
VS − 616HII/H3
VS − 616GII/G3
VS − 676
Braking
Unit
−
Model
CDBR − 15H etc.
Models
CDBR
−
−
2015,
2015B etc.
Models
CDBR
− 2015,
− 2015B etc.
Braking Resistor Unit
Model
LKEB − 20P7 etc.
Applicable/
Not Applicable
Applicable
Model
LKEB etc.
Model
LKEB etc.
Model
LKEB etc.
−
−
−
2015
4.8K
2015
Applicable
Not applicable
Applicable
Remarks
See connection examples of Fig 14.
Use sequencer to break power supply side on thermal protector of the braking resistor unit side.
No thermal protective function of braking resistor unit.
See connection examples of Figs. 15 to 18.
50
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6 SPECIFICATIONS
6.4 BRAKING UNIT SPECIFICATIONS
Braking Unit Model
CDBR-
2015
B,
2015
C
20
(15)
200V to 300V
2022
B,
2022
C
30
(22)
2045
B
60
(45)
2110
B
150
(110)
4030
B
380V to 460V
4045
B
4090
B
4220
B
500V to 575V
5037
B
5110
B
5300
B
Applicable Motor Output HP
(kW)
Output charac-teristics
Max. Discharge
Current(A) (peak value) *
Rated Discharge
Current (A)
Braking Start
Voltage
Max. Hysteresis
Error
Power
Supply
VDC
Protective
Functions
Fin Overheat
Power Charge
Indication
Envionmental
Conditions
Location
Altitude
Ambient
Temperature
Storage Transportation Temperature
Humidity
Vibration
Protective Configuration
Heat Loss (W)
40
15
32
60
20
38
100
30
330/345/365/380V
Approx. 8V
243 (1.35
× 200 × 0.9) to
400V peak
60
(45)
60
18
120
(90)
100
30
F (-20 to +60 °
300
(220)
630/660/690/730/760V
Approx. 16V
460 (1.35
×
800V peak
380 ×
Thermostat
0.9) to
C)
250
80
± 6V
57
(37)
40
15
Indoor (protected from corrosive gases and dust)
31
±
250
80
3V
+14 to 104 °
40
(30)
40
15
1000m max.
F (-10 to +40
-4 to 140 °
° C) (not frozen)
90%RH (non-condensing)
1G at 10 to less than 20Hz, up to 0.2G at 20 to 50 Hz
64
Wall-mounted enclosed type
54 59 35 71 22
150
(110)
100
30
825V/ 950V ±
400
(300)
250
Approx. 20V
607 (1.35
to 1000V
Charge lamp stays ON until bus voltage drops below 50V.
×
53
500 ×
80
8V
0.9)
116
* Loading time rate can be used below 10% ED (max. 10 sec.)
51
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6.5 BRAKING RESISTOR UNIT SPECIFICATIONS
Model
(LKEB
)
42P2B
43P7B
45P5B
47P5B
4011B
4015B
4018
2011
2015
2018
2022
40P7B
41P5B
20P7B
21P5B
22P2B
23P7B
25P5B
27P5B
4022
4030
4037
4045
Specifications
200 to
230V
380 to
460V
70W 200 Ω
260W 100 Ω
260W 70 Ω
390W 40 Ω
520W 30 Ω
780W 20 Ω
2400W 13.6
Ω
3000W 10 Ω
4800W 8 Ω
4800W 6.8
Ω
70W 750 Ω
260W 400 Ω
260W 250 Ω
390W 150 Ω
520W 100 Ω
780W 75 Ω
1040W 50 Ω
1560W 40 Ω
4800W 32 Ω
4800W 27.2
Ω
6000W 20 Ω
9600W 16 Ω
9600W 13.6
Ω
89
150
220
300
440
600
740
880
30
60
440
600
740
Allowable
Average
Dissipated
Power
(W)
30
60
89
150
220
300
880
1200
1500
1800
0.60
1.0
1.5
2.0
5.7
7.7
9.6
11.4
0.20
0.39
3.0
3.9
4.8
Allowable
Average
Current
(Effective Value)
(A)
0.39
0.77
1.1
1.9
2.7
3.9
5.7
7.7
9.7
11.5
Allowable
Ambient
Temperature
+14 to 122 ° F
(-10 to +50 ° C)
52
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6 SPECIFICATIONS
6.6 MODELS AND CODE NOS. OF BRAKING UNIT
AND BRAKING RESISTOR UNIT
(1) Braking Unit
Inverter
200 to
230 V
380 to
460 V
500 to
575 V
Model
Voltage HP (kW)
20 (15)
CDBR-2015B
CDBR-2015C
CDBR-2022B
30 (22)
CDBR-2022C
60 (45) CDBR-2045B
150 (110) CDBR-2110B
40 (30) CDBR-4030B
60 (45) CDBR-4045B
120 (90) CDBR-4090B
300 (220) CDBR-4220B
50 (37) CDBR-5037B
150 (110) CDBR-5110B
400 (300) CDBR.5300B
Code No.
72600-R2150B
72600-R2150C
72600-R2220B
72600-R2220C
72600-R2450B
72600-R21100B
72600-R4300B
72600-R4450B
72600-R4900B
72600-R42200B
72600-R5370B
72600-R51100B
72600-R53000B
53
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
(2) Braking Resistor Unit
Inverter
Voltage
200 to
230V
380 to
460V
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
20 (15)
25 (18.5)
30 (22)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
HP(kW)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
Resistor Spec.
(per unit)
Model
70W 200 Ω
260W 100 Ω
260W 70 Ω
390W 40 Ω
LKEB-20P7
LKEB-21P5
LKEB-22P2
LKEB-23P7
520W 30 Ω
780W 20 Ω
LKEB-25P5
LKEB-27P5
2400W 13.6
Ω LKEB-2011
3000W 10 Ω LKEB-2015
4800W 8 Ω
4800W 6.8
Ω
70W 750 Ω
260W 400 Ω
260W 250 Ω
390W 150 Ω
520W 100 Ω
780W 75 Ω
LKEB-2018
LKEB-2022
LKEB-40P7
LKEB-41P5
LKEB-42P2
LKEB-43P7
LKEB-45P5
LKEB-47P5
1040W 50 Ω
1560W 40 Ω
LKEB-4011
LKEB-4015
4800W 32 Ω LKEB-4018
4800W 27.2
Ω LKEB-4022
6000W 20 Ω
9600W 16 Ω
LKEB-4030
LKEB-4037
9600W 13.6
Ω LKEB-4045
Code No.
72600-K2P70B
72600-K2010B
72600-K2020B
72600-K2030B
72600-K2050B
72600-K2070B
72600-K2110
72600-K2150
72600-K2180
72600-K2220
72600-K4P70B
72600-K4010B
72600-K4020B
72600-K4030B
72600-K4050B
72600-K4070B
72600-K4110B
72600-K4150B
72600-K4180
72600-K4220
72600-K4300
72600-K4370
72600-K4450
54
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
YASKAWA AC Drive Option
Braking unit,
Braking resistor unit
Installation Manual
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2005-2013 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. TOBP C720600 00F