Yaskawa G5 GPD515 Drive Installation Guide
Publicitate
Publicitate
For GPD 515 Adjustable Frequency Drives
1000 Hz Output Frequency
FLASH Memory Software Option
Part Number: GPD515C-XXXX-CS004
(1)
With this factory-installed FLASH software, the
GPD 515 has the ability to provide an output frequency of up to 1000 Hz (depending on Drive rating) for applications which require high speed operation.
Specifications:
• Maximum Output Frequency:
1000 Hz: 1 to 40 Hp
800 Hz: 50 to 200 HP
400 Hz: 250 to 400 HP
• Control Mode: V/f only
• Serial Communications: Modbus RTU
(RS-232)
STOP
RUN
GPD
515
This document is an addendum to Technical
Manual TM 4515, listing the effect of this software on the parameters in the drive and function descriptions in the manual.
AC Motor
Speed
Reference
1000 Hz
| Change | 0 | 4/18/97 | Page 1 of 4
(1) XXXX refers to the base Model Number of the drive in which the software is installed.
Doc. No. 02Y00025-0420
Added Parameters:
This software does not add any new parameters to the drive.
Changed Parameters:
Refer to Appendix 1 ot the GPD 515 Technical Manual, TM 4515. The following changes result from the installation of this software in the drive.
Parameter Function Name Changed
A1-02 Control Method Selection Max. Value
Factory Setting
Min. Value b3-03 b6-01 b6-03 b8-02
C6-01
C6-02 d1-09
Speed Search Deceleration
Time
Dwell Frequency at Start
Dwell Frequency at Stop
Energy Saving Frequency
Carrier Frequency Upper Limit
Carrier Frequency Lower Limit d1-01 thru Frequency References d1-08
Jog Frequency Reference
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Increment
Max. Value
Increment
Factory Setting
Max. Value
Max. Value d2-02 Reference Lower Limit d3-01 thru Critical Frequency Rejection d3-03
E1-04
E1-06
E1-07
E1-09
E1-11
Max Frequency
Base Frequency
Mid Frequency A
Min Frequency
Mid Frequency B
H1-01 thru Multi-Function Input Terminal
H1-06 Selection
L2-04
L4-01
L4-03
Power Loss V/F Ramp Time
Speed Coincidence Level
Speed Coincidence Level + –
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Max. Value
Min. Value
Increment
(1) Setting will differ depending on drive capacity
Standard
Software
3
2
0.0
400.0
400.0
400.0
15.0 (1)
15.0 (1)
400.0
0.01
400.0
0.01
6.00
100.0
400.0
400.0
400.0
400.0
400.0
400.0
77
2.0
400.0
400.0
–400.0
0.1
1000 Hz
Software
0
0
1.0
1000.0
1000.0
1000.0
10.0 (1)
10.0 (1)
1000.0
0.1
1000.0
0.1
60.0
109.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
66
5.0
1000.0
1000
–1000
1
Doc. No. 02Y00025-0420 Page 2 of 4 This Page: | Change | 0 | 4/18/97 |
Deleted Parameters:
The following parameters are no longer present, and their function descriptions in Section 5 of the
Technical Manual are not applicable: b1-05 b7-01 & b7-02 b9-01 & b9-02
C3-05
C5-01 thru C5-07
C8-08
C8-30 d5-01 thru d5-06
E2-04, E2-06 thru E2-09
F1-01 thru F1-14
L7-01 thru L7-04 o1-03 o1-04
Zero-Speed Operation
Droop Control Setup
Zero Servo Setup
Slip Compensation V/f
Automatic Speed Regulator
AFR Gain
Carrier in tune
Torque Control Parameters
Open Loop Vector Parameters
Pulse Generator / Encoder Setup Parameters
Torque Limits
Display Scaling
Display Units
Startup Procedure:
1.
Set the Parameter Access Level to "Advanced" (Section 2.2C) (2) .
2.
Set the V/f pattern. This pattern can be a standard (preset) V/f pattern or a custom V/f pattern. Preset V/f patterns can be found in Table 5-4 (Section 5.48) (2) . A preset V/f pattern is selected by the setting of E1-03. When one of these preset V/f patterns is employed, parameter E1-01 (Input Voltage Setting) needs to be set at the motor’s nameplate value. If a custom V/f pattern is desired, set E1-03 = F (User Defined V/f) and use
Figure 1 and parameters E1-04 thru E1-13 to set it up (Section 5.48) (2) .
Vmax
( E1-05 )
V
B
( E1-12 )
OUTPUT
VOLTAGE
Vbase
( E1-13 )
V
A
( E1-08 )
Vmin
( E1-10 )
Fmin
( E1-09 )
F
A
Fbase
( E1-07 ) ( E1-06 )
OUTPUT FREQUENCY
F
B
( E1-11 )
Figure 1. V/f Characteristics Set by E1-04 thru E1-13
Fmax
( E1-04 )
This Page: | Change | 0 | 4/18/97 | Page 3 of 4 Doc. No. 02Y00025-0420
3.
Set the motor’s full load current into parameter E2-01 (Motor Rated Current).
4.
Set the JOG frequency (d1-09) to a safe, slow speed (Section 2.2C) (2) .
5.
Check the motor rotation using the JOG function (Section 2.2C) (2) .
6.
Further operational tests can be performed by following Section 2.5 (2) .
(2) Refer to GPD 515 Technical Manual TM 4515.
Verifying Installed Software Number:
For the 1000 Hz software option, the software number is 9990, 5112, or 5114. The software version installed in the drive can be verified by either reading it off of the control board, the FLASH label, or calling it up on the Digital Operator.
In order to read the software number off of the control board, take the cover off of the drive and look for the white sticker on the main control board. This sticker is just to the right of connector 2CN. On it is the version of the control board, then a dash, then the software number (see Figure 2). The "S" before the number can be disregarded.
In order to view the software number from the Digital
Operator, bring up drive parameter U1-14 (FLASH ID).
This is done by powering up the drive and using the following key sequence:
Press
MENU
, then
DATA
ENTER
, then , then
DATA
ENTER
, then 13 times.
Figure 2. Software Number Location on Control Board
NOTICE TO USER:
Be sure to keep this document with your GPD 515 Technical Manual.