Yaskawa iQpump 7 Series Manual
Werbung
Werbung
YASKAWA iQpump
Intelligent Pump Controller
Manual Supplement
Software No.VSP130035 and VSP130036
Use this supplement with User Manual TM.iQp.06 and Programming
Manual TM.iQp.07. To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance.
Ensure the end user receives this manual.
MANUAL NO. TM.iQp.10
2 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
Table of Contents
WATER LEVEL/SUCTION PRESSURE CONTROL IN MEMOBUS MULTIPLEX . . . . . . . . . . . . . . . . . . . . 26
.
Use this addendum with User Manual TM.iQp.06 and Programming TM.iQp.07.
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 3
This Page Intentionally Blank
4 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
1 Preface and Safety
1 Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESSED
OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
Applicable Documentation
The following manuals are available for the iQpump Controller:
SUPPLEMENT
Option Supplement
Yaskawa AC Drive - iQpump Controller Manual Supplement
Manual No: TM.iQp.10
Read this manual first.This document is a supplement to the iQpump Controller User Manual and
Technical Manual and Simplex Cheat Sheet. This supplement lists the effect of this custom software on the parameters in the drive and function descriptions in the manual.
Access this web site to obtain a PDF or additional printed copies of this supplement.
U.S.: http://www.yaskawa.com
Yaskawa Drive
Yaskawa AC Drive-iQpump Controller
User Manual TM.iQp.06
Yaskawa AC Drive-iQpump Controller
Programming Manual TM.iQp.07
To obtain instruction manuals for Yaskawa products access these sites:
U.S.: http://www.yaskawa.com
Other areas: contact a Yaskawa representative.
iQpump Controller Simplex Cheat Sheet
TM.iQp.04
For questions, contact the local Yaskawa sales office or the nearest Yaskawa representative.
Terminology Used in this Manual
These terms are used in this manual. iQpump Controller: The iQpump Controller may also be referred to as “drive” in this manual.
Obtaining Support
When seeking support for a drive with custom software, it is imperative to provide the unique part number shown on the drive nameplate. The software is flashed to the control board memory and the operation of parameters, functions, and monitors are different than the standard drive software, as described herein.
Refer to the Yaskawa office location listed on the back cover of this supplement for support inquiries.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 5
2 General Safety
2 General Safety
NOTICE
Abnormal Pump Operation Hazard
Important note when replacing an iQpump Controller.
Verify software ID drive monitor U1-14 when replacing an iQpump Controller in a multiplex network configuration.
Set parameter P9-99 to a value of 0 : "A-version 30034" if (ONE or MORE) iQpump Controllers on the network have software version monitor U1-14=30034 and nameplate PRG: 0034. Otherwise do not change P9-99 setting from factory default. Failure to comply will result abnormal drive operation.
Supplemental Safety Information
Read and understand this manual and the iQpump Controller User Manual before installing, operating, or servicing this option unit. The drive must be installed according to the iQpump Controller User Manual and local codes. Observe all cautions and warnings in this document and the standard drive manuals.
Refer to the iQpump Controller Simplex Cheat Sheet TM.iQp.04 and the iQpump Controller User Manual TM.iQp.06 for safety information and installation and start-up instructions.
This document is a supplement to the standard iQpump Controller Manuals. It describes the enhanced functionality of drive software version U1-14=30035 and nameplate PRG: 0035 or greater.
• Custom software is provided to add functionality to a standard AC drive to enhance or enable use in a specific application.
6 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
3 Product Overview
3 Product Overview
About This Product
Yaskawa has simplified the application of variable frequency drives to pumping applications. Pumps are typically used whenever water must be pumped from deep water wells or open bodies of water such as rivers, lakes, irrigation canals, and water storage facilities. The integrated pump specific software and quick setup parameters, allow the operator easy access to setup control values for a wide range of applications.
Feature Enhancement Summary
The following is a brief summary of features for drive software PRG:0035 that are added or enhanced over previous iQpump Controllers:
Initialization Function: A special initialization function is created to quickly and conveniently configure the drive as a generic speed controller. This initialization re-configures the Pump Quick Setup (Quick Start) menu to show parameters likely to require adjustment in generic applications.
b1-04 (Reverse Operation Selection): Added new parameter B1-04 (Reverse Operation Selection) which allows the motor phases to be exchanged.
FCarrier Frequency Selection (C6-02): Default has been changed to 1 (2.0 kHz).
Remote Drive Disable: This feature prohibits the drive from running when a new multifunction digital input is closed for a set amount of time.
Low City Pressure Alarm Selection: Added a parameter that selects the Low City Pressure alarm text that will show when in a Low City Pressure condition.
Suction Control Support via the Constant Pressure with Well Draw Down Control: Suction control option has been integrated into the Water Level control.
Modified Terminal A1 Loss Detection: Different alarm/fault texts will occur when feedback loss is detected on
Terminal A1 to differentiate from PI feedback loss on Terminal A2.
iQpump Memobus Multiplex: Lag Drive Speed Follower: Lag drives follow the speed of the lead drive.
iQpump Memobus Multiplex: Lag Turn Off: Lag drives can run at a fixed speed for a set time before turning off.
iQpump Memobus Multiplex: Flow Meter: New option to stage or de-stage based on Flow Rate.
iQpump Memobus Multiplex: Stop History: A new lead drive selection (P1-01) option has been added.
Geothermal Mode: The speed of the drive is determined by an analog temperature input and a temperature-speed curve. iQpump Multiplex: Water Level/Suction Pressure Control
• Ability to run the iQpump Controller Memobus network with just 1 drive connected to a Water Level or Suction
Pressure device
• Ability to automatically switch from the Analog Water Level/Suction Pressure Source to the Network Source in case of transducer loss or wire breaks.
• Pump De-stage due to the Water Level being below the Minimum Water Level.
• Pump De-stage due to the Suction Pressure being below the Minimum Suction Pressure.
• Disallow Pump Staging when PI is being influenced by the Water Level/Suction Pressure control
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 7
3 Product Overview
Applicable Models
The iQpump Controller is available in these models in
Table 1 Applicable Models
Drive
(All P7 drive models) CIMR-P7U -107
VSP1300035 or VSP1300036.
Listed on the drive nameplate as PRG:0035 or PRG:0036
<1> See “PRG” on the drive nameplate or drive monitor U1-14 for the software version number.
8 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
4 Drive Change Summary
4 Drive Change Summary
Overview
The following is an overview of changes made the drive with software PRG: 0035 and PRG: 0036.
Drive Software Changes
Table 2 Parameter Enhancements for PRG: 0035
Parameter
A1-01 Language Selection Selection 6:Portuguese is removed.
Description
A1-03 Initialization Mode Added selection 7770:General Purpose.
b1-01 Frequency
Reference Selection
Added selection 5:Geothermal Mode.
b1-03 Stop Method Default changed from: Ramp to Stop (0) to Coast to Stop (1).
C6-02 Carrier Frequency Default value changed to setting 1 (2.0 kHz) for all drive sizes.
P8-01 Water Lev./Suc.
Pres. Selection
Selection 1: Changed from Enabled to Water Level Control.
Added selection 2:Suction Pressure Control.
P8-09 Low Level Behavior Added selection 3:Auto-Restart (time set by P8-12).
P9-01 Lead Drive
Selection
P9-05 Lag Drive Mode
P9-08 Add Pump Mode
Added selection 2:Stop History.
Added selection 3:Follow Lead Speed.
Added selection 3:Flow Meter.
P9-12 Remove Pump
Mode
P9-23 Max Pumps
Running
P9-25 Highest Node
Address
Added selection 3:Flow Meter.
Range changed from 1 - 16 to 1 - 8.
Default changed from 16 to 8.
Range changed from 2 – 16 to 2 - 8.
Function
72 Remote Drive Disable
Table 3 Digital Input H1 Enhancements for PRG: 0035
Description
Digital Input function (normally open or normally closed) that can be used to prevent the drive from running with a programmable delay time.
Table 4 Digital Output H2 Enhancements for PRG: 0035
Function
57 Low Water Level
58 Low Suction Level
Description
Closed: During a “Feedback Loss” alarm.
Closed: During a “FBL – Feedback Loss” fault”.
Closed: During an “A1-LOST Terminal A1 Lost” alarm.
Closed: During an “A1-LOST Terminal A1 Lost” fault.
New
This will energize if P8-01 = 1 and the level in the well drops below the Low Level
Detection Level (P8-07) for more than the Low Level Detection Delay Time
(P8-08), or if there is a LOWWL – Low Water Level Fault.
This will energize if P8-01 = 2 and the suction pressure drops below the Low Suction
Pressure Detection Level (P8-07) for more than the Low Suction Pressure Delay Time
(P8-08), or if there is a LOSUC – Low Suction Pressure Fault.
<1> Modified from previous version.
Function
20 Geothermal Mode
Table 5 Added H3-09 Analog Input Function for PRG: 0035
Description
Temperature input for geothermal mode operation.
Page
Page
Page
Page
–
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 9
4 Drive Change Summary
Fault Code
OPE13
Terminal A1
OPE17
Run/Stp-CoastTmr
OPE18
Net Incompatible
OPE19
Geothermal Set
Temp Lost
Geothermal Input
LOSUC
Low Suction
Table 6 Additional or Modified Fault Codes for PRG: 0035
Description
Displayed when terminal A1 is assigned to more than one function. OPE13 is modified from the previous software version PRG:0034.
Displayed when Run/Stop Control and Coast To Stop w/Timer are both enabled.
Displayed when using features specific to iQpump software version 30035+ and nameplate
PRG: 0035 or greater with parameter P9-99 set to (0: A:Version 30034).
Displayed when a parameter selection is not compatible with the Geothermal Mode
(b1-01 = 5) setting.
Displayed when geothermal input is not present.
Suction pressure is below programmed level.
Table 7 Additional Alarms or Messages for PRG:0035
Alarm
Net FlowMeter
Lost, Chk Source
LOSUC
Low Suction
Low Water in Tank
Temp Lost
Geothermal Input
R-DNE-S
Remote Drv Dis
AnalogA1 Lost
Switched to Net
Net Wtr/Suctn
Lost, Chk Source
Remote drive disable is active.
Description
Displayed when there is no drive on the Memobus Network with an analog Flow Meter.
Displayed when Low City Pressure is active and alarm selection P4-27 = 1.
Displayed when Low City Pressure is active and alarm selection P4-27 = 2.
Displayed when a geothermal input is not present.
Displayed when there is a defective or broken analog input source. Analog Terminal A1 has not been detected, and the Network Water Level or Suction Pressure signal is now used.
Displayed when a valid analog source for Water Level or Suction Control Pressure can not be found on the network.
<1> The character is a place holder for the actual digital input designation, such as S1, S2, or S3.
OPE20
Alarm
Net WL/SP Mode
Low WL/SP
Drive Disabled
Table 8 Additional Alarms or Messages for PRG:0036
Description
Incompatible Network Water Level / Suction Pressure Mode.
Drive is unable to run because the Water Level or Suction Pressure is below the P8-05 setting.
Page
-
-
Page
Page
10 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
5 Feature Details - Remote Drive Disable
5 Feature Details - Remote Drive Disable
Overview
This function allows users to prohibit the iQpump Controller from running by using a multi-function digital input set to
"Remote Drv Disbl" (72) in combination with a programmable on time (P4-25) and off time delay (P4-26).
The "Remote Drive Disable" input logic can be selected with parameter P4-24.
Function Operation
When the Remote Drive Disable (H1-0 = 72) input is active for the amount of time specified in P4-25 the drive will be forced into a sleep-like state. Stopping method used is defined by b1-03 (Stopping Method Selection) setting.
If the iQpump Controller is running as part of a Memobus Network (multiplex system), it will be taken out and considered unavailable to run.
Alarm "R-DNE-S " will be displayed, where S is the Terminal programmed for Remote Drive Disable (H1-0 = 72).
The iQpump Controller will restart and perform a pre-charge if needed when the Remote Drive Disable ( H1-0 = 72) is inactive for the time specified in P4-26.
Note: When the drive run is disabled using this feature, the pre-charge function is reset and will run if necessary.
P4-24 Remote Drive Disable Selection
Selects the type of pressure switch connected to the “Remote Drv Disbl” digital input (H1-0 = 72).
Setting
0
1
Description
Normally Open (factory default)
Closed indicates a "Remote Disable" condition - active
Normally Closed
Open indicates a "Remote Disable" condition - active
Figure 1
P4-25 On-Delay Time
Active
Inactive
Remote
Drive Disable iQpump Drive Enabled iQpump Drive Stopping
Figure 1 Remote Disable: Inactive to Active Operation
Time
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 11
5 Feature Details - Remote Drive Disable
Figure 2
P4-26 Off-Delay Time
Active
Remote
Drive Disable
Inactive iQpump Drive Stopped iQpump Drive Enabled
Time
Figure 2 Remote Disable: Active to Inactive Operation
P4-25 Remote Drive Disable On-Delay Time
Range
1 - 1000 sec
Description
Sets the amount of time a “Remote Drive Disable” condition needs to be present before the drive will stop.
P4-26 Remote Drive Disable Off-Delay Time
Default
0 sec
Range
1 - 1000 sec
Description
Sets the amount of time a "Remote Drive Disable" condition must be absent before the drive will be allowed to run.
Multi-function Input Setting: Remote Drive Disable Function
Default
0 sec
Setting
72 Remote Drv Disbl
Description
Remote Drive Disable: Prevents the iQpump Controller from running when active for the time set in
P4-25. Must be inactive for the time set in P4-26 to allow the drive to run again.
Note: Parameter P4-24 determines if this input is Normally Open or Normally Closed.
Alarm: Remote Drive Disable
Alarm Display
R-DNE-Sx
Remote Drv Dis
Description
Multi-function Input Terminal S (H1-0 = 72) has been closed for the time set in P4-25 when P4-24 = 0.
or
Multi-function Input Terminal S (H1-0 = 72) has been open for the time set in P4-25 when P4-24 = 1.
Note: S or Sx denotes the digital input terminal programmed for this function.
12 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
6 Feature Details - Low City Pressure Alarm
6 Feature Details - Low City Pressure Alarm
Overview
The alarm function is used for stopping the iQpump Controller or preventing the iQpump Controller from running based on an external contact closure.
This function has been enhanced by parameter P4-27 which allows users to select the alarm message that will be displayed when a Low City Pressure condition is detected.
Function Operation
P4-27 Low City Pressure Alarm Text
Selects the alarm message that will be displayed when a Low City Pressure condition is detected.
Setting
0
1
2
Low City Pressure (factory default)
Low Suction Pressure
Low Water in Tank
Alarm: Low Pressure/Low Water in Tank
Description
Alarm Display
Low Suction Pressure
Low Water In Tank
Description
Shown when P4-27 = 1 and when the digital input has been active (closed for P4-21 = 0, or open for
P4-21 = 1) for the time set in P4-22. The drive, if running, coasts-to-stop and does not run until the digital input has been inactive for the time set in P4-22.
Shown when P4-27 = 2 and when the digital input has been active
(closed for P4-21 = 0, or open for P4-21 = 1) for the time set in P4-22. The drive, if running, coasts-to-stop and does not run until the digital input has been inactive for the time set in P4-22.
Related Parameters
P4-21 Low City Pressure Input Select
Setting
0
1
P4-22 Low City Pressure Input Delay Time
Description
Normally Open (closed for the "Low City Pressure" condition)
Normally Closed (open for the "Low City Pressure" condition) (factory default)
Range
1 - 1000 sec
Description
Sets the amount of time a "Low City Pressure" condition must be present before the drives will stop. Also sets the amount of time that the pressure must be adequate before the drive system will restart.
Multi-function Input Setting H1 : Low City Pressure
Setting
73 Low City Pressure
Default
10 sec
Description
Indicates that sufficient/insufficient pressure is present on the inlet to the pump. This setting is used mainly for pressure booster stations.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 13
7 Suction Control via Constant Pressure w/Well Draw Down
7 Suction Control via Constant Pressure w/Well Draw Down
Overview
This function enables the iQpump Controller to monitor suction pressure at the inlet of the pumps.
Note: This function is active when parameter P8-01 is set to 2 for Suction Control.
Packaged Booster Systems have a desired discharge pressure and a given suction pressure from the city water system or from a suction tank. Such systems are often designed to handle a specific pressure and flow rate.
The suction pressure may have a wide range between high and low pressures. The suction pressure typically decreases with increased fluid flow rate. In some instances, pump cavitation may occur if suction pressure falls below a certain pressure level.
In addition low or negative suction pressure can lead to damage such as pipe collapse due to external forces acting on the pipe.
The iQpump Controller will accept an analog suction transducer (Terminal A1) and can be programmed to trigger an alarm or shutdown the system when the suction pressure falls outside of a normal operating range.The iQpump Controller will automatically restart and return to normal operation once the suction pressure returns to a normal level.
When operating in multiplex mode, additional control can be programmed to de-stage any active pumps as a method to try and reduce pump loading to prevent suction pressure from continuing to drop below the shut down level.
Function Description
The iQpump Controller will regulate outlet pressure of the pump system using the standard iQpump Controller features when there is adequate suction pressure available at the inlet of the pumps and offers two options to respond to a drop in suction pressure.
1.
Regulate Outlet Pressure and Suction Pressure: (P8-03 > or = P8-04)
To regulate suction pressure set the suction pressure setpoint (P8-03) to a value greater or equal than the minimum suction pressure (P8-04). In this mode the iQpump Controller will try to regulate the suction pressure based on the programmed suction pressure setpoint (P8-03) level.
As the suction pressure decreases and approaches the suction pressure setpoint level (P8-03), the iQpump Controller will slow down causing the outlet pressure and flow to decrease. When the suction pressure rises above the P8-05 level for more than the P1-05 time, normal operation (outlet pressure regulation) will resume.
When the suction pressure drops below Minimum Suction Pressure (P8-04), for more than the Sleep Delay Time
(P2-03), the iQpump Controller will go to sleep.
Note: The Suction Control Minimum Speed parameter (P8-06) should be set to a high enough value that will ensure flow.
2.
Regulate Outlet Pressure Only: (P8-03 < P8-04)
Set the suction pressure setpoint (P8-03) to a value smaller than the minimum suction pressure (P8-04) to regulate outlet pressure.
This mode allows the iQpump Controller to maintain the outlet pressure setpoint using the standard iQpump Controller features and go to sleep immediately when the suction pressure drops below the Minimum Suction Pressure (P8-04), for more than the Sleep Delay Time (P2-03).
Normal operation (outlet pressure regulation) will resume when the suction pressure returns above the P8-05 level for more than the P1-05 time.
14 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
7 Suction Control via Constant Pressure w/Well Draw Down
Duplex System Example
Example:
A pump system consisting of a duplex domestic pressure booster system using a pressured city supply averaging 40
- 60 psi. If city pressure starts to fall below 40 psi the pump system will start to slow down to reduce the chances of pump cavitation. When suction pressure (city pressure) drops to 30 psi, the pump system will shut down (sleep) and wait until city pressure returns, after which the system will automatically start and operate under normal condition.
Pump System Settings
• All pumps have the same flow rate and will alternate
• Lag Pump will track speed of lead pump
• All drives have individual discharge transducers rated 150 psi. Upon failure, system will look to network for feedback information.
• Suction Transducer is rated 75 psi
• Below 40 psi city pressure the pump system will start to reduce speed until reaching 30 psi
• System Auto setpoint 85 psi, with a 5 psi start level.
Duplex System Example (Related Parameters)
Parameter
P8-02
P8-03
P8-04
P8-05
P9-02
P9-05
P9-25
P9-50
U1-01
H3-02
H3-03
H3-08
H5-01
P1-01
P1-03
P1-04
P8-01
Description
Terminal A1 Gain
Terminal A1 Bias
Terminal A2 Signal
Drive Node Network Address
Pump Mode
FD Device Scaling
Start Level
WtrLvl/SuctionPres Selection
Suction Transducer Scaling
Suction Pressure Setpoint
Minimum Suction Pressure
Wakeup Suction Pressure
Feedback Source
Lag Drive Mode
Highest Node Address
Suction Pressure Source
Auto Setpoint
Booster Pump 1
75 psi
40.0 psi
30.0 psi
40.0 psi
3
2
2
2
85 psi
231.3%
-25.0%
2
1
3
150 psi
-5.0 psi
2
Note:
Booster Pump 2
75 psi
40.0 psi
30.0 psi
40.0 psi
3
2
2
2
85 psi
231.3%
-25.0%
2
2
3
150 psi
-5.0 psi
2
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 15
7 Suction Control via Constant Pressure w/Well Draw Down
Enabling Suction Pressure Control
The suction pressure control selection is added to parameter P8-01 Water Level/Suction Pressure Selection. Follow these steps for basic suction pressure control setup:
1.
Enable suction control by setting parameter P8-01 to 2 (Suction Control).
2.
Set suction transducer scaling (P8-03) in psi, scaling for analog input A1 (20 mA scale).
3.
Set suction pressure setpoint (P8-03) in psi.
4.
Select iQpump operation when a drop in suction pressure occurs: a. Regulate outlet pressure only and go to sleep immediately when suction pressure falls below minimum suction pressure level (P8-04). Set suction pressure setpoint (P8-03) below minimum suction pressure level (P8-04).
b. Regulate suction pressure when pressure is below suction pressure setpoint (P8-03) but above the minimum suction pressure level (P8-04). Set suction pressure setpoint (P8-03) to above the minimum suction pressure level
(P8-04).
5.
Set minimum suction pressure (P8-04) – Sleep Level for Suction Control.
6.
Set suction pressure wake-up level (P8-05) – Wake-up level.
7.
Set suction control minimum speed (P8-06) – Minimum Flow Speed.
P8-01 Water Level/Suction Pressure Selection
Sets the mode of operation for the Water Level / Suction Control function.
Setting
0
1
2
Description
Disabled (factory default)
Water Level Control
(This function is defined as "Enabled" for iQpump software PRG: 0034)
Suction Pressure Control (New)
Note: The iQpump Controller will only perform the outlet pressure and suction pressure control when "normal" PI mode is enabled
(b5-01 > 0, not jogging, not disabled via MFDI, etc.).
P8-02 Suction Transducer Scaling
Terminal A1 is used for the suction pressure analog input. The analog pressure sensor, mounted on the inlet side of the pump(s) will provide the required signal. Set this parameter to the full-scale pressure of the transducer. The suction pressure will then be displayed on the U1-98 monitor.
Default
100 psi
Range
5 - 500 psi
Description
Sets the full scale (20 mA) output of the pressure transducer connected to
Terminal A1.
P8-03 Suction Pressure Setpoint
Range
0.0 - 1200.0 psi
Description
Sets the amount of suction pressure the iQpump Controller will attempt to regulate.
P8-04 Minimum Suction Pressure
Range
0.0 - 1200.0 psi
Description
When the suction pressure drops to below this level for more than the P2-03 time, the drive will go to sleep and turn off all lag pumps.
Default
20.0 psi
Default
10.0 psi
16 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
7 Suction Control via Constant Pressure w/Well Draw Down
P8-05 Wake-Up Suction Pressure
Range
0.0 - 1200.0 psi
Description
If the drive is forced to sleep based upon the minimum suction pressure
(P8-04), the suction pressure must go above this level for more than the P8-13 time in order to wake up.
P8-06 Suction Control Minimum Speed
Range
0.00 - 120.00 Hz
Description
This parameter sets the minimum speed the drive will run when the drive is controlling suction pressure. When the drive is controlling outlet pressure or this parameter is set less than P1-06 and P4-05, P1-06 and P4-05 will be used as the minimum speed.
P8-07 Low Suction Pressure Detection Level <1>
Range
0.0 - 1200.0 psi
Description
When the amount of suction pressure drops below this level for more than the
P8-08 time, the drive will respond depending on the P8-09 setting. A setting of
0.0 disables this detection.
P8-08 Low Suction Pressure Detection Time <1>
Default
30.0 psi
Default
0.00 Hz
Default
0.0 psi
Range
0.0- 300.0 min
Description
Sets the amount of time delay that the suction pressure must drop below the
P8-07 level before the drive will react. *Time units are defined by P8-14.
Default
0.1 min
P8-09 Water Level/Suction Pressure Selection
Sets how the drive will respond when the water level in the well drops below the P8-07 level for more than the P8-08 time.
Setting
0
1
2
3
No Display (Digital Output Only)
Alarm Only (factory default)
Fault
Auto-Restart (time set by P8-12) (New)
P8-10 Suction Control Proportional Gain
Description
Range
0.00 - 25.00
P8-11 Suction Control Integral Time
Description
Sets the proportional gain for the suction pressure control.
Range
0.0 - 360.0 sec
Description
Sets the integral time for the suction pressure control. A setting of zero disables the suction pressure control integrator.
P8-12 Suction Control Auto-Restart Time
Range
0.1 - 6000.0 min
Description
Sets the amount of time the drive will wait before attempting an auto-restart of the "Low Suction" fault. Effective only when P8-09 = 3 and L5-01 > 0.
Default
2.00
Default
5.0 min
Default
5.0 min
<1> Low Level/Low Suction Detection (P8-07/P8-08): This feature is disabled when the drive is in Run-Stop control
(b1-02 = 5, Timed Run).
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 17
7 Suction Control via Constant Pressure w/Well Draw Down
P8-13 Suction Pressure Sleep Wake-Up Time
Range
0 - 3600 sec
Description
If the iQpump Controller has been forced to sleep based upon the minimum suction pressure (P8-04), the pressure must go above the P8-05 level for more than this time in order to wake up.
P8-14 Low Suction Pressure Detection Time Unit
Defines the time unit for P8-08.
Default
1 sec
Setting
0
1
Minutes (factory default)
Seconds
Description
Suction Pressure Transducer Wire-break Detection
Wire-break detection is active on Terminal A1 when PI Feedback Loss Detection is enabled (b5-12 = 1 or 2) , Suction control is enabled (P8-01 = 2) and PI control is NOT disabled via Multi-Function Digital Input.
The iQpump Controller detects a wire-break condition when the suction transducer signal on Terminal A1 falls below -
6.25 % or rises above 106.25 % for more than 1 second and will react according to parameter b5-12 (Feedback Loss
Detection).
Note: Wire-break detection on Terminal A1 detection is checked after the gain/bias parameters (H3-02 and H3-03) are applied.
Fault: Low Suction
Fault Display
LOSUC
Low Suction
Description
Low Suction: Suction pressure is below the P8-07 level for more than the P8-08 time.
Parameters P8-12 to P8-14 are also available for Water Level control P8-01 set to 1. The parameter titles change accordingly.
P8-12 Water Level Auto-Restart Time
Range
0.1 - 6000.0 min
Description
Sets the amount of time the iQpump Controller will wait before attempting an auto-restart of the "Low Water" fault. Effective only when P8-09 = 3 and
L5-01 > 0.
P8-13 Water Level Sleep Wake-Up Time
Range
0 - 3600 sec
Description
If the iQpump Controller is forced to sleep based upon the minimum water level (P8-04), the pressure must go above the P8-05 level for more than this time in order to wake up.
P8-14 Low Water Detection Time Unit
Default
5.0 min
Default
1 sec
Setting
0
1
Minutes (factory default)
Seconds
Multi-function Output Setting H2 : Low Suction (Modified)
Description
Setting
57 Low Water
Description
This output will energize if P8-01 = 1 and the level in the well drops below the Low Level Detection Level
(P8-07) for more than the Low Level Detection Delay Time (P8-08), or if there is a LOWWL - Low Water
Level Fault.
18 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
7 Suction Control via Constant Pressure w/Well Draw Down
Multi-function Output Setting H2 : Low Suction (New)
Setting
58 Low Suction
Description
This output will energize if P8-01 = 2 and the suction pressure drops below the Low Suction Pressure
Detection Level (P8-07) for more than the Low Suction Pressure Delay Time (P8-08), or if there is a
LOSUC - Low Suction Pressure Fault.
Related Parameters
When P1-01 = 3 (Memobus Multiplex), the Water Level or Suction Pressure can be transmitted or read through the network.
Refer to Water Level/Suction Pressure Control in Memobus Multiplex on page 26 .
P9-50 Water Level Source (P8-01 set to 0 or 1, Water Level Control)
Defines which signal to use for Water Level Control (P8 ) when P1-01=3.
Setting has no effect when P1-01 ≠ 3.
Setting
0
1
2
3
Analog Only (factory default)
Analog -> Network, No Alarm
Analog -> Network, Alarm
Network Only
Description
P9-50 Suction Pressure Level Source (P8-01 set to 2 Suction Control)
Defines which signal to use for Suction Pressure Control (P8 ) when P1-01=3.
Setting has no effect when P1-01 ≠ 3.
Setting
2
3
0
1
Analog Only (factory default)
Analog -> Network, No Alarm
Analog -> Network, Alarm
Network Only
Description
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 19
8 Geothermal Mode
8 Geothermal Mode
Overview
A geothermal well facilitates heat transfer between the earth and a known system, such as space heating, dehydration, electric power generation and food processing.
The geothermal function has the ability to regulate the speed of the iQpump Controller based on an external temperature signal following a preset temperature-speed curve.
Figure 3
Warm Cold
Warm
Heat
Exchanger
Geothermal
Heater
Well
Pump
M
Cold iQpump
Pool
Pump
M
Cold
Filter
Cold
Thermostat
Discharge Valve
Warm
Cold
Warm Pool
Discharge
Well
Aquifer
Figure 3 Geothermal Pool Application
Geothermal Mode Setup Procedure
Follow these steps to setup the iQpump Controller in Geothermal Mode:
1. Set iQpump Controller parameters to factory default by setting parameter A1-03 to 2220 for "2 Wire" Initialization.
<1>
2. Disable PI Control by setting parameter b5-01 to 0 "Disabled"
3. Set multi-function analog input function H3-09 to 20 "Geothermal Temp"
4. Enable Geothermal Mode by setting parameter b1-01 to 5 "Geothermal Mode"
5. Set display monitor to selectable mode by setting o1-06 to 1 "3 Mon Selectable"
6. Select monitor display line #1 to display output frequency by setting o2-01 to 2 "Output Freq"
7. Select monitor display line #3 to display temperature by setting o1-08 to 80 "Geothermal Temp"
8. Set the temperature transducer range to properly scale the input. (P4-31 and P4-32)
9. Set the temperature-speed curve to the intended operation (P4-33 ~ P4-38)
<1> "3330" for 3-Wire Initialization or "7770" for General Purpose Initialization can also be used.
20 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
8 Geothermal Mode
Related Parameters
b1-01 Frequency Reference Source Selection
Set the frequency reference source (b1-01) to 5 for Geothermal mode operation.
Setting
0
1
2
3
5
Description
Operator - Digital preset speed d1-01 (factory default)
Terminals - Analog input Terminal A1 (or Terminal A2, see parameter H3-13)
Serial Com - RS-485 terminals R+, R-, S+ and S-
Option PCB - Option board connected at 2CN
Geothermal Mode - Frequency reference is dependent on temperature input
(H3-09 = 20) <0035>
H3-09 Multi-function Analog Input Setting: Geothermal Temperature
Program H3-09 = 20 to use an external temperature sensor in Geothermal mode operation.
Setting
20
Description
Geothermal Temperature
Analog input function for use with an external temperature sensor.
Range scaling: 0V (or 4 mA) = P4-31 ~ 10 V (or 20 mA) = P4-32
Geothermal Mode Frequency/Temperature Characteristic
When the iQpump Controller is set to operate in Geothermal Mode (b1-01 = 5), the drive's frequency reference is determined by the analog input Geothermal Temperature (H3-09 = 20) and the setting of parameters P4-33 ~ P4-38. The
Geothermal characteristic can be programmed in normal or inverse operation.
Normal Operation: P4-33 < P4-34 and P4-35 < P4-36 < P4-37 < P4-38
Inverse Operation: P4-33 > P4-34 and P4-35 < P4-36 < P4-37 < P4-38
P4-31 Minimum Geothermal Temperature Input
Range
-110.0 ~ 440.0 °F
P4-32 Maximum Geothermal Temperature Input
Description
Sets the temperature that corresponds to a 0V (or 4 mA) analog input.
Range
-110.0 ~ 450.0 °F
Description
Sets the temperature that corresponds to a 10V (or 20 mA) analog input.
0.0 °F
Default
150.0 °F
Default
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 21
8 Geothermal Mode
Parameter No.
P4-33
P4-34
P4-35
P4-36
Parameter Name
Minimum Geothermal Speed
Maximum Geothermal Speed
Low Temperature to Run at
Maximum Geothermal Speed
Low Temperature to Run at
Minimum Geothermal Speed
Description Range Default
Sets the frequency reference characteristics based on the set temperature points and the corresponding frequency.
For proper operation, P4-34 > P4-33 and P4-38 > P4-37 > P4-36 >
P4-35.
0.00 ~
120.00 Hz
40.00 Hz
Maximum
Geothermal Speed
㩿㪧㪋㪄㪊㪋㪀 0.00 ~
120.00 Hz
40.00 Hz
Minimum
Geothermal Speed
㩿㪧㪋㪄㪊㪊㪀
-110.0 ~
450.0 °F
55.0 °F
Low Temp
@ Max
㩿㪧㪋㪄㪊㪌㪀
Low Temp
@ Min
㩿㪧㪋㪄㪊㪍㪀
High Temp
@ Min
㩿㪧㪋㪄㪊㪎㪀
High Temp
@ Max
㩿㪧㪋㪄㪊㪏㪀
Temperature (°F)
Geothermal Mode Frequency/Temperature Characteristic|
(Normal Operation)
.
Maximum
Geothermal Speed
㩿㪧㪋㪄㪊㪋㪀
-110.0 ~
450.0 °F
65.0 °F
P4-37
P4-38
High Temperature to Run at
Minimum Geothermal Speed
Minimum
Geothermal Speed
㩿㪧㪋㪄㪊㪊㪀
-110.0 ~
450.0 °F
75.0 °F
High Temperature to Run at
Maximum Geothermal Speed
Low Temp
@ Max
㩿㪧㪋㪄㪊㪌㪀
Low Temp
@ Min
㩿㪧㪋㪄㪊㪍㪀
High Temp
@ Min
㩿㪧㪋㪄㪊㪎㪀
High Temp
@ Max
㩿㪧㪋㪄㪊㪏㪀
Temperature (°F)
Geothermal Mode Frequency/Temperature Characteristic
(Inverse Operation)
-110.0 ~
450.0 °F
85.0 °F
Figure 4
22
Figure 4 Digital Operator Display Showing Geothermal Mode Operation
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
8 Geothermal Mode
Geothermal Mode iQpump Controller Monitors
U1-80 Geothermal Temperature Input
Unit
0.1 °F
Description
Displays Geothermal temperature input after gain and bias are applied. This is the temperature used by the
Geothermal Function to determine what frequency to run the iQpump Controller.
Note: Only shown when b1-05 = 5 (Geothermal Mode)
Geothermal Temperature Loss Detection
P4-39 Geothermal Temperature Loss Detection
Selects iQpump Controller action when the temperature sensor signal from Terminal A2 is below 3 mA or above 21 mA.
Setting
0
1
2
Disabled
Alarm (factory default)
Fault
Description
Note: Only effective when H3-08 = 2 (4-20 mA) and H3-09 = 20 (Geothermal Temp).
Alarm: Temperature Sensor Lost (factory default)
Alarm Display
Temp Lost
Geothermal Input
Description
The geothermal temperature sensor is not present. Alarm occurs when:
1. b1-01 = 5, H3-09 = 20 (Geothermal Temp), H3-08 = 2 (4-20 mA), P4-39 = 1 (Alarm), and the input has either dropped below 3 mA or went above 21 mA.
Check: Ensure the device connected to Terminal A2 is installed and working properly.
2. b1-01 = 5, and H3-09 ≠ 20 (Geothermal Temp), and P4-39 = 1 (Alarm).
Check: Terminal A2 must be assigned to Geothermal Temp (H3-09 = 20).
3. b1-01 = 5, H3-09 = 20 (Geothermal Temp), H3-08 = 2 (4-20 mA), P4-39 = 2 (Fault), the drive is either in HAND mode or has no run command, and the input is below 3 mA or above 21 mA.
Check: Ensure the device connected to Terminal A2 is installed and working properly.
4. b1-01 = 5, and H3-09 ≠ 20 (Geothermal Temp), P4-39 = 2 (Fault), and the drive is either in HAND mode or has no run command.
Check: Terminal A2 needs to be assigned to Geothermal Temp (H3-09=20).
Alarm: Geothermal Parameters Programming Error
Alarm Display Description
The drive is running at the P4-31 level because of an incorrect setting.
Geo Params
Check P4-35~P4-38 The temperature parameter values must be set in the following order:
P4-35 < P4-36 < P4-37 < P4-38
Fault: Temperature Sensor Lost
Fault Display
Temp Lost
Geothermal Input
Description
The geothermal temperature sensor is not present. Fault occurs when:
1.b1-01 = 5, and H3-09 ≠ 20 (Geothermal Temp), and P4-39 = 2 (Fault).
Check: Terminal A2 must be assigned to Geothermal Temp (H3-09 = 20).
2.b1-01 = 5, H3-09 = 20 (Geothermal Temp), H3-08 = 2 (4-20 mA), P4-39 = 2 (Fault), the drive is either in
HAND mode or has no run command, and the input is below 3 mA or above 21 mA.
Check: Ensure the device connected to Terminal A2 is installed and working properly.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 23
8 Geothermal Mode
Fault: Geothermal Frequency Reference/Temperature Curve Error: OPE19
Fault Display
OPE19
Geothermal Set
Description
Parameter selection is not compatible with the Geothermal Mode (b1-01 = 5) setting. Fault occurs when b1-01 = 5 (Geothermal Mode), and one of the following is NOT set:
- b5-01 = 0 (PI Disabled)
- P1-01 = 0 (Simplex)
Check: Confirm parameter settings for b1-01, b5-01, and P1-01.
Example: Geothermal Pump System Transducer Setup
Example:
Geothermal Pump system using a temperature transducer 4 - 20 mA with a temperature range of 0 - 120 °F. The system requires a minimum pump speed of 35 Hz. The system requires increased pump speed when the temperature increases above 75 °F or when temperature falls below 65 °F.
60Hz
㩿㪧㪋㪄㪊㪋㪀
35Hz
㩿㪧㪋㪄㪊㪊㪀
4-20mA
Temperature
Transducer
V+
Output
55°F
㩿㪧㪋㪄㪊㪌㪀
+V iQpump
A2
AC
EG
65°F
㩿㪧㪋㪄㪊㪍㪀
75°F
㩿㪧㪋㪄㪊㪎㪀
Temperature (°F)
0-10V
Temperature
Transducer
V+
Output
Common
85°F
㪧㪋㪄㪊㪏㪀
+V iQpump
A2
AC
EG
Set S1-2 to ON
* Factory Default
O
F
F
1
Set S1-2 to OFF
O
F
F
1
2 2
Set parameter H3-08
Terminal A2 Signal to ‘0’ for 0 – 10V.
Geothermal Mode Setup Procedure:
24 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
8 Geothermal Mode
Related Parameters for Geothermal Mode Operation
Parameter b1-01 b5-01
H3-09 o1-06
o1-08
P1-01
P4-31
P4-32
P4-33
P4-34
P4-35
P4-36
P4-37
P4-38
P4-39
Description
Frequency Reference Source
PI Mode
Terminal A2 Function Selection
User Monitor Selection Mode
User Monitor Selection After Power-Up
Third Line User Monitor Selection
Pump Mode
Minimum Geothermal Temperature Input
Maximum Geothermal Temperature Input
Minimum Geothermal Speed
Maximum Geothermal Speed
Low Temperature to Run at Max. Geothermal speed
Low Temperature to Run at Min. Geothermal speed
High Temperature to Run at Min. Geothermal speed
High Temperature to Run at Max. Geothermal speed
Geothermal Temperature Loss Detection iQpump Controller
120.0 °F
35.00 Hz
60.00 Hz
55.0 °F
65.0 °F
75.0 °F
85.0 °F
1
20
1
5
0
2
80
0
0.0 °F
<1> After programming is completed, cycle power to the drive, as changes to the o1-02 monitor requires a drive power-up cycle to be effective.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 25
9 Water Level/Suction Pressure Control in Memobus Multiplex
9 Water Level/Suction Pressure Control in Memobus Multiplex
Overview
When using Water Level or Suction Pressure Control in a Memobus Multiplex system, (see parameter P8-01). The iQpump Controller can be programmed to receive the Water Level or Suction Pressure information from another drive on the network with a Water Level or Suction Pressure input.
Parameters
Parameter representation for this function depends on the setting of parameter P8-01.
Parameter Settings
P8-01 Water Level/Suction Pressure Selection
Setting
0
1
2
Description
Disabled (factory default)
Water Level Control (Previous version PRG: 0034 functionality for setting is "Enabled")
Suction Pressure Control
P9-50 Water Level Source (P8-01 set to 0 or 1, Water Level Control)
Setting
0
1
2
3
Analog Only (factory default)
Analog -> Network, No Alarm
Analog -> Network, Alarm
Network Only
Description
P9-50 Suction Pressure Level Source (P8-01 set to 2 Suction Pressure Control)
Setting
0
1
2
3
Analog Only (factory default)
Analog -> Network, No Alarm
Analog -> Network, Alarm
Network Only
Description
P9-50 = 0 (Analog Only)
This drive will transmit its Water Level/Suction Pressure signal to the network. If this signal is lost, the drive will not switch to another signal on the network. The detection action in this mode is solely on parameter b5-12.
P9-50 = 1 (Ana->Net, No Alarm)
This drive will transmit its Water Level/Suction Pressure signal to the network when the analog input is healthy. If this signal is lost, the drive will switch to another signal on the network if available. If there are no available network signals, then this drive will act according to the setting of parameter b5-12 (when = 1 or 2).
Note: Setting parameter b5-12 to 0 will disable analog feedback detection and will prevent the iQpump Controller from switching to the
Network Water Level/Suction Pressure.
P9-50 = 2 (Ana->Net, Alarm)
This drive will transmit its Water Level / Suction Pressure signal to the network when the analog input is healthy. If this signal is lost, the drive will switch to another signal on the network if available. An alarm will be displayed indicating that the analog signal has been lost and that the signal is coming from the network. If there are no available network signals, then this drive will act according to the setting of parameter b5-12 (when = 1 or 2).
Note: Setting parameter b5-12 to 0 will disable analog feedback detection and will prevent the iQpump Controller from switching to the
Network Water Level/Suction Pressure.
26 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
9 Water Level/Suction Pressure Control in Memobus Multiplex
P9-50 = 3 (Network Only)
The drive will always use a valid network Water Level / Suction Pressure signal. If there are no available network signals, the drive will act according to the setting of b5-12 with the following differences:
Setting b5-12 to 1: Instead of an alarm, Network P8 Lost message is displayed.
Setting b5-12 to 2: Instead of a fault, Network P8 Lost message is displayed. In this condition the iQpump
Controller no longer accepts iQpump Controller Network run commands and the stopping method is fixed to coast-tostop.
b5-12 PI Feedback Reference Missing Detection Selection
Setting
0
1
2
Disabled
Alarm
Fault (factory default)
Description
Any drive with b5-12 set to 0 (Disabled) and P9-50 ≠ 3 will effectively have no Terminal A1 signal loss detection and will continuously send the Water Level/Suction Pressure to the iQpump Controller Network regardless of a faulty or an invalid signal.
When b5-12 set to 2 (Fault) and P9-02 = 3, iQpump Controller will display a feedback loss alarm instead of a fault when one of the following conditions active:
1. The iQpump Controller is in Hand Mode
2. There is no Lead iQpump Controller on the network
3. The iQpump Controller is not in Auto Mode
Minimum Water Level or Suction Pressure Detection Operation
In case of a minimum water level or suction pressure, the lead iQpump Controller will de-stage when one or more Lag iQpump Controllers are present, otherwise the lead iQpump Controller will go to sleep.
Note: Setting parameter b5-12 to 0 will disable analog feedback detection and will prevent the iQpump Controller from switching to the
Network Water Level/Suction Pressure.
Related Parameters
b5-12 PI Feedback Reference Missing Detection Selection
Setting
0
1
2
Disabled (factory default)
Alarm
Fault
Description
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 27
9 Water Level/Suction Pressure Control in Memobus Multiplex
P2-03 Sleep Delay Time
Sets delay time when water level or suction pressure signal falls below the minimum level programmed (P8-04).
Range Description
Network Multiplex Mode: Water Level Control (P8-01 = 1): Parameter specifies the time delay before the lead drive de-stages when the water level (U1-98) falls below the Minimum Water Level (P8-04).
0 - 3600 sec
Default: 5 sec
Network Multiplex Mode: Suction Control (P8-01 = 2): Parameter specifies the time delay before the lead drive de-stages when the suction pressure (U1-98) falls below the Minimum Suction Pressure (P8-
04).
Contactor Multiplex Mode (P1-01 =1 or 2): There are two contactor multiplex modes, one for Water
Level and another for Suction. Contactors programmed for Multiplex (H2 = 40 and 41) will open one by one when the Water Level (U1-98) is below the Minimum Water Level (P8-04) for the time set in the Sleep Delay Time (P2-03).
IMPORTANT: Staging Restriction when in Water Level/Suction Pressure Control.
• When P1-01 = 3 (Memobus Network) and the iQpump Controller’s PI output is being influenced by the Water Level/
Suction Pressure Control, pump system staging is disabled.
• When P1-01 = 1 or 2 (Multiplex system) and the iQpump Controller’s PI output is being influenced by the Water Level/
Suction Pressure Control, Multi-function output contacts (H2 = 40 and 41) are prohibited from closing.
Alarm: Water Level/Suction Pressure Transducer Lost
Alarm Display Description
Analog Terminal A1 signal is lost and the Network Water Level or Suction Pressure signal is now used.
AnalogA1 Lost
Switched to Net
Cause: Defective or broken analog input source.
Countermeasure: Check to ensure the Water Level or Suction Pressure source is installed and working properly. If no signal is present, set P9-50 = 3 to have it always read from another drive's network Water
Level or Suction Pressure.
Alarm: Network Water or Suction Pressure Signal Lost
Alarm Display Description
Network source for Water Level or Suction Control Pressure is lost.
Net Wtr/Suctn
Lost, Chk Source Cause: Valid analog source for Water Level or Suction Control Pressure can not be found on the network.
Countermeasure: Check the source on drives configured as P9-50 ≠ 3.
Fault: Programming Error: OPE13 Terminal A1
Fault Display
OPE13
Terminal A1
Description
Cause: Terminal A1 is assigned to more than one of the following functions.
• Frequency Reference (b1-01 = 1)
• Dual Zone PI is enabled (b5-01 = 2)
• Flow Meter Enabled (P6-01 > 0)*
• Water Level/Suction Pressure Control Enabled (P8-01>0)*
• Hand Mode Ref Term A1 (P5-01 = 0)
Note: An OPE13 error will not be generated if b1-01 = 1 and P5-01 = 0, and none of the other conditions listed above apply.
*When P1-01 = 3 (Memobus), a setting of P6-01 > 0 and P8-01 > 0 is allowed only if P9-40 = 1 or
P9-50 = 3.
Countermeasure: Reprogram b1-01, b5-01, P6-01, or P8-01.
Note: The OPE13 fault is modified in drive software version PRG:0035. Previous software versions have different functionality.
28 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
10 iQpump MEMOBUS/Network Operation
10 iQpump MEMOBUS/Network Operation
Lag Drive Speed Follower and Lag Turn Off
Certain multiplex pump systems require a common pump speed for all running pumps. To allow for this operation, a new selection "Follow Lead Spd" is added to parameter P9-05.
Function Description
P9-05 Lag Drive Mode
Setting
0
1
2
3
Description
Fixed Speed (factory default)
Runs at the P9-06 setting after the P9-07 time expires.
PI Regulation.
Uses PI to determine speed.
Turn Off
The iQpump Controller stops running when it switches to a lag drive after P9-07 time expires.
Follow Lead Spd
The iQpump Controller follows the speed of the active Lead drive. Use P9-30 gain and P9-31 bias setting to adjust reference signal.
Note: The rate at which the Lag drives follow the Lead drive's output speed is dependent on the communication speed of the iQpump
Controller network (H5-02), the maximum number of iQpump Controllers on the network (P9-25) and the current number of iQpump Controllers online.
Display Message for Follow Lead Speed Operation:
When the iQpump Controller is operating in Auto Mode, Lag operation and the Follow Lead Speed function is active
(P9-05 = 3) then the display will show the actual frequency reference in Hz instead of the selected system units.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 29
10 iQpump MEMOBUS/Network Operation
Related Parameters
P9-06 Lag Fixed Speed
Range
0 - 120.0 Hz
Description
When the drive changes from a lead to a lag and P9-05 = 0, the drive will run at this speed after P9-07 delay time expires.
P9-07 Lag Fixed Speed Delay
Time delay before execution of P9-05 selection when the iQpump Controller changes from lead to lag.
Note: Only active when Lag Mode Selection (P9-05) is set to 0, 2 or 3.
Default
55.0 Hz
Range
0 - 1000 sec
New Parameters
P9-30 Lag Follower Gain
Description
When the drive changes from a lead to a lag and P9-05 ≠ 1, this time specified in parameter P9-07 determines how long the speed is latched before executing one of the following operations:
1. P9-05 = 0: Run at P9-06
2. P9-05 = 2: Turn off
3. P9-05 = 3: Follow the Lead Drive's speed.
5 sec
Default
100.0 %
Default Range
0.0 -300.0%
Description
When P9-05 = 3, the drive will follow the speed of the active lead drive applying this gain and P9-31 bias to the reference signal.
P9-31 Lag Follower Bias
Range
-60.00 - 60.00 Hz
Description
When P9-05 = 3, the drive will follow the speed of the active lead drive applying this bias and P9-30 gain to the reference signal.
0.00 Hz
Default
30 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
10 iQpump MEMOBUS/Network Operation
Flow Meter
Certain multiplex pump systems require staging/de-staging based on the flow rate. The iQpump Controller offers a dedicated set of parameters to operate multiplex pump systems based on flow control.
0-10V
4-20mA
Network iQpump 2 iQpump 3
Flow Meter
Pressure
Transducer
Inlet
iQpump 1
A1
A2
Pump 1 Pump 2 Pump 3
Flow Pressure
Outlet
Multiplex Pump System Operation
Flow Rate Staging: Set P9-08 (Add Pump Mode) to 3: Flow Meter.
This mode monitors the Flow Rate to determine if staging is needed. If the Flow Rate of the lead iQpump Controller rises above the Flow Staging level (no. of pumps running times P9-41) for the time set in P9-11, the drive will issue a network stage request if an iQpump Controller is available to run.
Example:
If P9-41 Add Flow Rate Level set to 80.0 GPM, then the 2nd pump is called to run when the flow rate rises above
80.0 GPM. The 3rd pump is called to run the flow rate rises above 160.0 GPM and the 4th pump is called when the flow rate rises above 240.0 GPM.
De-staging: Set P9-12 (Remove Pump Mode) to 3: Flow Meter.
This mode monitors the Flow Rate to determine if de-staging is needed. If the flow rate of the lead iQpump Controller falls below the Flow De-Staging level ((no. of pumps running - 1) x P9-42) for the time set in P9-15, a de-stage request is issued if two or more iQpump Controllers are running on the network.
Example:
If P9-42 = 60.0 GPM, then the 4th pump is de-staged when flow rate falls below 180.0 GPM. The 3rd pump is destaged when the flow rate falls below 120.0 GPM (gallons per minute ) and the 2nd pump is de-staged when the flow rate falls below
60.0 GPM.
NOTICE: Using Fixed Speed Lag Drive mode P9-05 = 0 in conjunction with Flow Meter Staging (P9-08 = 3) or Flow Meter De-staging
(P9-12 = 3) could result in an unstable system depending on the system and the parameter settings.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 31
10 iQpump MEMOBUS/Network Operation
New Parameters
P9-40 Flow Rate Source
Defines the Flow Meter input source when P1-01=3 (Memobus Network).
Setting
0
1
Analog (factory default)
Network
Uses PI to determine speed.
P9-41 Add Flow Rate Level
Description
Range
0.0 ~ 6000.0
Description
When P9-08=3 and the Flow Rate is above this level times (No. of pumps running) for the time set in P9-11, the lead drive will request for a new lead drive through the iQpump Controller Memobus network.
<1> Displayed units are determined by parameter P6-02.
P9-42 Remove Flow Rate Level
Default
0.0
Range
0.0 ~ 6000.0
Description
When P9-12=3 and the Flow Rate is below this level times (No. of pumps running minus 1) for the time set in P9-15, the lead drive will request to be removed from the system through the iQpump Controller Memobus network.
<1> Displayed units are determined by parameter P6-02.
Related Parameters
P6-01 Flow Meter Scaling
Default
0.0
Range
0.0 ~ 6000.0 GPM
Description
Sets the scaling for the flow meter connected to terminal A1. Enter the gal/min when the flow meter is at its rated output. A setting of 0.0 disables all flow meter functions.
0.0 GPM
P6-02 Water Flow Units
Sets the units displayed for monitor U1-95. Also sets units for parameters P2-02, P6-04, P9-41 and P9-42.
Default
Setting
0
1
2
3
4
U.S. Gallons/min (GPM) (factory default)
U.S. Gallons/Hr (GPH)
U.S. Barrels/min (BPM)
U.S. Barrels/hour (BPH)
U.S. Barrels/day (BPD)
P9-08 Add Pump Mode
Selects the detection method for staging a new pump.
Description
Setting
0
1
2
3
Output Frequency (factory default)
Feedback
Feedback + Fout
Flow Meter (New)
Description
32 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
10 iQpump MEMOBUS/Network Operation
P9-11 Add Delay Time
Range
0 ~ 3600 sec
Description
Delay time before a new lead drive is added to the system.
P9-12 Remove Pump Mode
Selects the detection method for de-staging to the previous lead pump.
Default
10 sec
Setting
0
1
2
3
Output Frequency (factory default)
Feedback
Feedback + Fout
Flow Meter
P9-15 Remove Delay Time
Description
Range
0 ~ 3600 sec
Description
Delay time before the lead drive is removed from the system.
Alarm: Network Water or Suction Pressure Signal Lost
Alarm Display Description
There is no drive on the Memobus Network with an analog Flow Meter.
Net FlowMeter
Lost, Chk Source
Default
10 sec
Cause: With P1-01 = 3, P6-01 > 0 and P9-40 = 1 (Network), the Flow Meter function needs a valid Flow
Rate from the network originating from another drive that is also running the Flow Meter function
(P6-01 > 0) with P9-40 = 0 (Analog).
Countermeasure: If the drive has an operational Flow Meter connected to Terminal A1, set P9-40 = 0. If another drive on the Memobus Network has a Flow meter connected to Terminal A1, confirm that drive is online, with P6-01 > 0 and P9-40 = 0.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 33
10 iQpump MEMOBUS/Network Operation
New Lead Drive Selection: Stop History
Overview
Many irrigation pumping skids consist of a PM pump (Pressure Maintenance) and typically two (2) larger booster pumps to maintain high flow peak demands.
In many cases depending on the number of irrigation zones in combination with the type of sprinkler heads used, the flow demand fluctuates and may not require the use of both larger booster pumps at the same time until higher flow rates are required.
The iQpump Controller "Run Stop" history ensures that both booster pumps alternate each run cycle.
Parameters
P9-01 Lead Drive Selection
Selects the detection method for staging a new pump.
Setting
0
1
2
Description
Next Available
Select next available drive on the network as the new lead drive.
Lowest Runtime (factory default)
Select the iQpump Controller with the lowest runtime as the new lead drive.
Stop History
Select the iQpump that had been stopped the longest time.
Note: This new lead drive selection also applies to Alternation (P9-03 > 0) and will use the Stop History list when finding the alternate drive.
System Example: Triplex Irrigation Booster System-Using Stop History
Overview
A typical pump system operates as described below:
When pressure is dropping, the PM Pump (if installed) will attempt to return the system pressure to the desired setpoint level. If the PM Pump is not able to return the system to the setpoint pressure, typically due to a greater flow demand, the first booster pump (1) will be called to start.
The iQpump Controller will speed up or slow down the pump as needed to maintain the system pressure. When flow decreases and the pump system is no longer required to run, the system will go to sleep waiting for the pressure to drop.
On the next run cycle the PM pump will start up again, and instead of running booster pump #1, booster pump #2 is started, since booster #1 ran during the last cycle.
This method ensures that during normal operation both booster pumps will operate evenly as lead or lag pumps each run cycle.
Detailed Description
Triplex irrigation booster system consisting of one PM Pump (pressure maintenance) and two larger booster pumps of the same horsepower. The customer would like to ensure that the PM Pump is also the lead pump to recharge the system during low flow usage, but during high demands the booster pumps alternate on each run cycle or if required will both run to support very high flow demands.
• Jockey/PM Pump will also be lead to start.
• Jockey/PM Pump will stage booster pump 1 or 2 and stay running for 20 seconds and then shut off.
• Booster pump 1 will run system and if required, call for booster pump 2 or vice versa.
• On sleep mode, the lead drive for starting will swap back to Jockey/PM Pump.
• System setpoint 100 psi.
• Pressure drop of 10 psi will start the Jockey pump.
• All drives have individual transducers rated 200 psi maximum, but if there is a transducer failure, switch to network.
34 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
10 iQpump MEMOBUS/Network Operation
Related Parameters: Triplex Irrigation Booster System
Parameter
H5-01
P1-01
P1-03
P1-04
P9-01
P9-02
P9-07
P9-20
P9-21
P9-24
P9-25
U1-01
Description
Drive Node Network Address
Pump Mode
FD Device Scaling
Start Level
Lead Drive Select
Feedback Source
Lag Fixed Spd Dly
(PM Pump will shut off after 20 sec)
Allow Net Run
(PM Pump will be lead Pump to start)
Run Priority
Lead Swap @ Sleep
Highest Node Address
Auto Setpoint
PM Pump
1
3
200 psi
-10.0 psi
2
2
20 sec
2
7
0 sec
3
100 psi
Network
Booster Pump 1 Booster Pump 2
2
3
200 psi
-10.0 psi
2
2
3
3
200 psi
-10.0 psi
2
2
5 sec 5 sec
0
8
1 sec
3
100 psi
0
8
1 sec
3
100 psi
System
Pressure
Feedback
PM iQpump 1
V+
A2
AC
PM
Pump
System
Pressure
Feedback
Pump 1 i Q p u m p 2
V+
A2
AC
Booster
Pump 1
System
Pressure
Feedback
Pump 2 i Q p u m p 3
V+
A2
AC
Booster
Pump 2
10 HP
50 HP 50 HP
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 35
11 Improved and Miscellaneous Functions
11 Improved and Miscellaneous Functions
Terminal A1 Loss Detection
Feedback loss detection alarm and fault messages are enhanced to differentiate between terminal A1 feedback loss and
Terminal A2 PI feedback loss.
Use parameter b5-12 is select feedback loss detection operation for terminal A1.
Parameters
b5-12 Feedback Loss Detection
Setting
0
1
2
Disabled
Alarm
Fault (factory default)
New Alarm Message: Feedback Loss Terminal A1 (Modified)
Description
Fault Display
A1-LOST
Terminal A1 Lost
New Fault Message: Feedback Loss Terminal A1 (Modified)
Description
Shown when b5-12 = 1 and feedback signal on terminal A1 is lost. Check to ensure the device connected to
Terminal A1 is installed and working properly.
Fault Display
A1-LOST
Terminal A1 Lost
Multi-function Output Setting: Transducer Loss (Modified)
Description
Shown when b5-12 = 2 and feedback signal on terminal A1 is lost. Check to ensure the device connected to
Terminal A1 is installed and working properly.
Setting
4A
Description
Transducer Loss
Closed: During a "Feedback Loss" alarm.
Closed: During a "FBL - Feedback Loss" fault".
Closed: During an "A1-LOST Terminal A1 Lost" alarm (New)
Closed: During an "A1-LOST Terminal A1 Lost" fault (New)
Function Description Feedback Loss Detection
Wire break (feedback loss detection) will be detected on Terminal A1 when all of the following conditions are satisfied:
• PI Feedback Loss Detection is enabled (b5-12 = 1 or 2).
• PI function is enabled (b5-01 > 0).
• Dual Zone PI or Water Level/Suction Pressure Control is enabled (b5-01 = 2 or P8-01 > 0, P1-01 = 0, b5-09 = 0, and
H3-09 = B).
• PI function is NOT disabled via Multi-Function Digital Input.
• Signal on Terminal A1 falls below -6.25 % or rises above 106.25 % for more than 1 second.
Note: Wire-break detection on Terminal A1 is checked after the gain/bias parameters (H3-02 and H3-03) are applied.
36 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
11 Improved and Miscellaneous Functions
Feedback Loss Detection Special Conditions:
Auto Mode Operation and b5-12 is set to 2 (Fault):
• Running: The iQpump Controller will fault on feedback loss detection.
• Stopped: The iQpump Controller will display feedback loss alarm.
Hand Mode Operation and b5-12 is set to 2 (Fault):
• Running: The iQpump Controller will display feedback loss alarm.
• Stopped: The iQpump Controller will display feedback loss alarm.
Both the alarm or fault message display in any of these scenarios is: "A1-LOST Terminal A1 Lost."
Note: To convert terminal A1 to a 4-20 mA signal, connect a 250 ohm precision resistor (1/4 Watt or greater) between iQpump
Controller terminals A1 and AC. Then program H3-02 = 231.3% and H3-03 = -25.0 %.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 37
11 Improved and Miscellaneous Functions
Initialization for Basic Applications (A1-03)
A new initialization mode setting 7770 is available under parameter A1-03 (Initialize Parameters). This setting allows users to easily configure the iQpump Controller for use as a standard drive in simple applications. In this mode the iQpump Controller defaults to start/stop operation from the terminals and speed control using a 0-10 Vdc signal to analog input A1.
A1-03 Initialize Parameters
Setting
0
1111
2220
3330
7770
Description
No Initialize (factory default)
User Initialize
The modified iQpump Controller parameters are returned to the values selected as user settings. User settings are stored when parameter o2-03 = 1: Set Defaults.
2-Wire Initialize
Initializes the iQpump Controller for 2 Wire Control Operation
3-Wire Initialize
Initializes the iQpump Controller for 3 Wire Control Operation
General Purpose
Configures the iQpump Controller for General Purpose Operation
The Table below shows the default parameters settings for the standard iQpump Controller 2-wire initialization (2220) and the General Purpose Initialization (7770).
Parameters Modified for General Purpose Initialization
Parameter No.
Parameter Name Factory Default Setting
H2-01
H2-02
H3-09*
L5-01
L5-03 o1-06*
P1-02
P1-03 b1-01 b1-02 b5-01
C1-01
C1-02
C6-02
H1-04
H1-05
P1-05
P1-06
P4-05
P4-11
P5-02
Frequency Reference Selection 0 (Operator)
Run Command Selection 0 (Operator)
PID Mode Setting
Acceleration Time 1
Deceleration Time 1
Carrier Frequency Selection
Terminal S6 Selection
Terminal S7 Selection
1 (Enabled)
20.0 sec
10.0 sec
1 (2.0 kHz)
80 (Hand Mode)
84 (Disable Pre-Charge)
Terminal M1-M2 Selection
Terminal M3-M4 Selection
40 (Pump 2 Control)
41 (Pump 3 Control)
Terminal A2 Function Selection B (PID Feedback)
Number of Auto Restarts 5
Maximum Restart Time 20.0 sec
User Monitor Selection Mode 1 (3 Mon Selectable)
System Units
Feedback Scaling
1 (psi:lb/SqrInch)
145
Start Level Delay Time
Minimum Pump Frequency
Thrust Frequency
Utility Delay Time
Hand Reference
1 sec
40.0 Hz
30.00 Hz
0.2 minutes
40.00 Hz
Note: After performing a General Purpose initialization (7770), the parameters shown in this table will be visible in the Modified
Constants menu, with the exception of parameters marked by *.
Setting After General
Purpose Initialize
(A1-03 = 7770)
1 (Terminals)
1 (Terminals)
0 (Disabled)
25.0 sec
25.0 sec kVA dependent
4 (Multi-Step SP 2)
F (Term Not Used)
0 (During Run 1)
A (Remote/Auto Oper)
2 (Aux Reference)
0
180.0 sec
0 (3 Mon Sequential)
14 (Hz: Hertz)
26000
0 sec
0.0 Hz
0.00 Hz
0.0 minutes
0.00 Hz
38 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
11 Improved and Miscellaneous Functions
Pump Quick Setup Menu
Initializing the iQpump Controller for General Purpose Operation also re-configures the Pump Quick Setup (Quick Start) menu to show parameters for use in basic applications.
The table below shows the parameters that appear in the quick start menu for standard iQpump Controller 2-Wire
Initialization (2220) and the General Purpose Initialization (7770).
Quick Setup Overview
A1-03 = 2220, 3330 iQpump Quick Setup
E2-01 (Motor Rated FLA)
E2-04 (Number of Poles)
P1-03 (FB Dev. Scaling)
D1-01 (Set-Point 1)
P1-04 (Start Level)
P1-06 (Min. Pump Freq.)
P4-10 (AMO PwDn-Storage)
P5-04 (Oper HAND Key)
-
A1-03 = 7770
General Purpose Quick Setup b1-01 (Reference Source) b1-02 (Run Source)
C1-01 (Accel Time 1)
C1-02 (Decel Time 1)
E2-01 (Motor Rated FLA)
E2-04 (Number of Poles)
L5-01 (Num of Restarts)
L5-03 (Max Restart Time)
P1-06 (Min. Pump Freq.)
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 39
11 Improved and Miscellaneous Functions
General Purpose Initialization: Carrier Frequency Adjustment
Initializing the iQpump Controller for General Purpose Operation adjust the carrier frequency setting as shown in table below for each of the iQpump Controller models.
Carrier Frequency Setting for A1-03 = 7770 "General Purpose" Initialization
208-240 V Drives 480 V Drives
Model
CIMR-
P7 -107
20151
20181
20221
20301
20370
20450
20550
20750
20900
21100
20P41
20P71
21P51
22P21
23P71
25P51
27P51
20111
Parameter C6-02
Setting Value
3
1
2
2
1
1
3
3
3
3
3
3
3
3
3
3
3
3
C6-03
Carrier Frequency
(kHz)
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
5.1 kHz
5.1 kHz
8.0 kHz*
2.0 kHz
2.0 kHz
2.0 kHz
Model
CIMR-
P7 -107
49P01
40111
40151
40181
40221
40241
40301
40371
40P41
40P71
41P51
42P21
43P71
44P01
45P51
47P51
40451
40551
40750
40900
41100-107
41320-107
41600-107
41850-107
42200-107
43000-107
Parameter C6-02
Setting Value
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2
1
2
2
1
1
2
3
3
2
8.0 kHz*
8.0 kHz*
8.0 kHz*
5.1 kHz
5.1 kHz
8.0 kHz*
5.1 kHz
5.1 kHz
5.1 kHz
2.0 kHz
2.0 kHz
2.0 kHz
C6-03
Carrier
Frequency
(kHz)
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
8.0 kHz*
Note: * = when an option card is installed, C6-03 max is 7.0 kHz.
40 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
11 Improved and Miscellaneous Functions
Miscellaneous Changes
This following items are minor changes to existing iQpump Controller parameters and functions.
A1-01 Language Selection
Selection 6:Portuguese is removed.
Stopping Method - Default Value
Parameter b1-03 stopping method selection factory default has been changed from setting 0 (Ramp to Stop) to
1 (Coast to Stop).
b1-03 Stopping Method
Setting
0
1
2
3
Description
Ramp to Stop
Coast to Stop (factory default)
DC Injection to Stop
Coast w/Timer
(A new run command is ignored if input before the time in C1-02 expires)
Output Phase Exchange
Parameter b1-04 allows users to switch the motor phasing in the software without physically switching the motor leads.
When b1-04 is set to 3 (Exchange Phase, Reverse Disabled) "forward operation" is defined as the opposite direction.
NOTICE: It is strongly recommended not to use this function to reverse motor rotation, but to exchange two of the output phases to the motor. Make sure the motor is wired correctly to the iQpump Controller and motor rotation is correct.
b1-04 Reverse Operation
Setting
1
3
Description
Reverse Disabled (factory default)
"Forward operation" is defined as the forward direction. Set when motor direction matches iQpump
Controller forward operation.
Exchange Phase, Reverse Disabled
Reverse motor phases in the software. "Forward operation" is defined as the opposite direction.
Note: b1-04 is not affected by initialization A1-03.
C6-02 Carrier Frequency - Default Value
The default setting for parameter C6-02 Carrier Frequency is changed to 1 (2.0 kHz).
L2-01 Momentary Power Loss Detection Selection
Setting
0
1
2
Disabled
Drive trips on (UV1) fault when power is lost.
Description
PwrL Ride Thru t
Drive will restart if power returns within the time set in L2-02. If a second power loss occurs within one hour, the drive will trip on Uv1.*
CPU Power Active (factory default)
Drive will restart if power returns prior to internal power supply shut down. If a second power loss occurs within one hour, the drive will remain in an undervoltage state for an additional 10-second delay after power returns. With each additional power loss occurrence, the time delay will increase. If the drive operates for one hour with no power loss conditions detected, the time delay is cleared.*
Note: *In order for a restart to occur, the run command must be maintained throughout the ride thru period.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 41
11 Improved and Miscellaneous Functions
P9-23 Max Pumps Running
The Range changed from 1 - 16 to 1 - 8 and the default changed from 16 to 8.
P9-25 Highest Node Address - Range
The range for parameter P9-25 Highest Node Address changes to 2 - 8.
Fault: Programming Error: OPE17 Run/Stop - Coast Time
Fault Display
OPE17
Run/Stp-CoastTmr
Description
Cause: Run/Stop Control and Coast To Stop w/Timer are both enabled.
1. P8-18 > 0 AND
2. P8-19 > 0 AND
3. P8-20 > 0 AND
4. b1-03 = 3 (Coast w/Timer)
Countermeasure: Reprogram b1-03 or P8-18 ~ P8-20.
Compatibility Mode
A compatibility mode is available for using the iQpump Controller software or PRG:0035/U1-14=30036 on a multiplex network that consists of iQpump Controllers with software PRG:0034/U1-14=30034. Compatibility Mode must be enabled by the customer.
Figure 5
6
Figure 5 Example Software ID Check: Check iQpump Controller Monitor U1-14
P9-99 Network Compatibility Selection
Determines the communication compatibility for the iQpump Memobus Network.
Setting
0
1
Description
A-Version PRG:30034
Use this mode if (ONE or MORE) iQpump Controllers on the network have software version monitor
U1-14=30034 and nameplate PRG: 0034.
B-Version PRG:30035+ or greater (factory default)
Use this mode if (NONE) of the iQpump Controllers on the network have software version monitor
U1-14=30034 and nameplate PRG: 0034.
NOTICE
Abnormal Pump Operation Hazard During iQpump Controller Replacement
Verify software ID (U1-14) when replacing an iQpump Controller in a multiplex network configuration. Set parameter
P9-99 to a value of “0 :A-version 30034" if (ONE or MORE) iQpump Controllers on the network have Use this mode if
(ONE or MORE) iQpump Controllers on the network have software version monitor U1-14=30034 and nameplate
PRG: 0034. Failure to comply will result abnormal drive operation
42 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
11 Improved and Miscellaneous Functions
New Fault Message: Net Incompatible
Fault Display
OPE18
Net Incompatible
Description
Parameter selection is not compatible with the selected network, see parameter P9-99.
When P1-01 = 3 (Memobus Networking), P9-99 = 0 (A-Version 30034), and one of the following is set:
1. P9-01 = 2 (Stop History)
2. P9-05 = 3 (Follow Lead Spd)
3. P8-01 = 1 or 2 (Water Level or Suction Control enabled).
4. P6-01 > 0 (Flow Meter Enabled) and P9-40 = 1 (Network)
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 43
12 Speed Follower Deceleration Time Switchover <0036>
12 Speed Follower Deceleration Time Switchover <0036>
Overview
The current iQpump Speed Follower will attempt to match the speed of the Lead Drive after the Lag Drive Fixed Speed
Delay.
Consider a scenario wherein the system needs help from an idle drive to maintain system pressure. When the idle drive is called to run, the difference between the set-point and the feedback may be too small to make the drive accelerate faster.
In the case of a system is configured with these settings:
• Set for Lag Drive Speed Follower
• Add Pump method is Frequency Reference
• Frequency Reference setting close to the maximum frequency
The system will drop the speed after the Lag Drive Fixed Speed Delay expires in order to follow the output frequency of the previously idle drive. This transition may cause unwanted pressure drops. A longer deceleration time will be activated on the lag drives when the system switches the drive that is being followed. The longer deceleration time will be effective for a programmable setting, after which, the regular deceleration time is used.
Note: The Network Compatibility Mode parameter P9-99=1: B-Version 30035+ reflects support for drive software version U1-14=30036 and nameplate PRG: 0036.
Functional Operation
If P9-05 = 3 (Follow Lead Spd), the lag drive will use the network information and the lead drive's output speed as its frequency reference. The lag drive's final speed reference is affected by (Lag Follower Gain P9-30) and then by (Lag
Follower Bias P9-31).
Lag Drive Speed = ( Lead Drive Speed x Lag Follower Gain ) + Lag Follower Bias
When P9-33 > 0.0 sec, an alternate deceleration time (Lag Follower Decel P9-32) is used when the drive switches from the latched speed (Lag Fixed Delay P9-07) to the new Lead drive's output frequency. The deceleration time is active for the duration set in (Lag Followr Dtim P9-33), and will switch back to the regular deceleration rates when it expires.
Note: Parameter functionality stated below only applies when P1-01 = 3 (Memobus Network)
P9-32 Lag Follower Deceleration Time
Default
60.0 sec
Range
0.0 ~ 1000.0 sec
Description
When the P9-33 timer is running, and the drive is running as Lag Drive Speed
Follower (P9-05 = 3), then the deceleration time is set to this value.
P9-33 Lag Follower Deceleration Time Active Time
Range
0.0 ~ 360.0 sec
Description
The P9-32 deceleration time is effective during this time window. The drive will use the standard deceleration rates when it expires.
A setting of 0.0 sec will disable the Lag Follower deceleration time switching.
Related Parameters
Note: Parameter functionality stated below only applies when P1-01 = 3 (Memobus Network)
P9-05 Lag Drive Mode
Determines the function of the lag drive.
Default
0.0 sec
Setting
0
Description
Fixed Speed (factory default)
Runs at the P9-06 setting after the P9-07 time expires.
44 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
12 Speed Follower Deceleration Time Switchover <0036>
Setting
1
2
3
Description
PI Regulation.
Uses PI to determine speed.
Turn Off
The iQpump Controller stops running when it switches to a lag drive after P9-07 time expires.
Follow Lead Spd
The iQpump Controller follows the speed of the active Lead drive. Use P9-30 gain and P9-31 bias setting to adjust reference signal.
P9-07 Lag Fixed Speed Delay
Time delay before execution of P9-05 selection when the iQpump Controller changes from lead to lag.
Range
0 - 1000 sec
Description
When the drive changes from a lead to a lag and P9-05 ≠ 1, this time specified in parameter P9-07 determines how long the speed is latched before executing one of the following operations:
1. P9-05 = 0: Run at P9-06
2. P9-05 = 2: Turn off
3. P9-05 = 3: Follow the Lead Drive's speed.
5 sec
P9-30 Lag Drive Speed Follower Gain
Range
0.0 - 300.0 %
Description
When P9-05 = 3, the drive will follow the speed of the active lead drive applying this gain and P9-31 bias to the reference signal.
P9-31 Lag Drive Speed Follower Bias
Default
100.0 %
Default
Range
-60.00 - 60.00 Hz
Description
When P9-05 = 3, the drive will follow the speed of the active lead drive applying this bias and P9-30 gain to the reference signal.
P9-99 Network Compatibility Selection
Determines the communication compatibility for the iQpump Memobus Network.
0.00 Hz
Default
Setting
0
1
Description
A-Version 30034
Use this mode if (ONE or MORE) iQpump Controllers on the network have software version monitor U1-
14=30034 and nameplate PRG: 0034.
B-Version 30035+ (factory default)
Use this mode if (NONE) of the iQpump Controllers on the network have software version monitor U1-
14=30034 and nameplate PRG: 0034.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 45
12 Speed Follower Deceleration Time Switchover <0036>
Timing Diagrams - Speed Follower Deceleration Time Switchover (Disabled and Enabled)
Figure 6
P9-01 = 1 (Lowest Run-time)
P9-08 = 0 (Output Frequency)
P9-32 = 60.0 sec
P9-05 = 3 (Follow Lead Speed)
P9-12 = 0 (Output Frequency)
P9-33 = 0.0 sec
Start-up…
Drive 1 is the
Lead Pump.
Drive 2 Staged-in.
Drive 1 becomes a Lag
Drive and latches to its current output speed.
Drive 3 Staged-in.
Drive 2 becomes a Lag
Drive and latches to its current output speed.
Drive 1 follows the speed of Drive 2
(Lead)
Drive 3 is no longer needed and gets destaged.
Drive 2 is the Lead again.
Drive 1 follows the speed of Drive 2 again.
Drive 1 and Drive 2 follows the speed of
Drive 3 (Lead)
P9-07
Lag
Fixed
Delay
P9-07
Lag
Fixed
Delay
Figure 6 Lag Follower Deceleration Time Switching (Disabled)
46 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
12 Speed Follower Deceleration Time Switchover <0036>
Figure 7
P9-01 = 1 (Lowest Run-time)
P9-08 = 0 (Output Frequency)
P9-32 = 60.0 sec
P9-05 = 3 (Follow Lead Speed)
P9-12 = 0 (Output Frequency)
P9-33 = 10.0 sec
Start-up…
Drive 1 is the
Lead Pump.
Drive 2 Staged-in.
Drive 1 becomes a Lag
Drive and latches to its current output speed.
Drive 3 Staged-in.
Drive 2 becomes a Lag
Drive and latches to its current output speed.
Drive 1 follows the speed of Drive 2
(Lead)
Drive 3 is no longer needed and gets destaged.
Drive 2 is the Lead again.
Drive 1 follows the speed of Drive 2 again.
Drive 1 and Drive 2 follows the speed of
Drive 3 (Lead)
P9-07
Lag
Fixed
Delay
P9-33
Lag
Followr
Dtim
P9-32
Lag Followr Dcel
P9-07
Lag
Fixed
Delay
P9-33
Lag
Followr
Dtim
P9-32
Lag Followr Dcel
P9-32
Lag Followr Dcel
Figure 7 Lag Follower Deceleration Time Switching (Enabled)
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 47
13 Transducer Wiring using an External Power Supply
13 Transducer Wiring using an External Power Supply
Simplex Pump System - Transducer Connection using Analog Input A2
(4 - 20 mA Mode)
A2 used for pressure transducer.
External
24Vdc Power Supply
+ -
V+
Output
+V
A2 iQpump
S1-2
4-20mA
Transducer
AC
EG
O
F
F
1
2
Set S1-2 to ON Position (4-20mA) for iQpump Drive (Factory Default)
Simplex Pump System - Transducer Connection using Analog Input A1
(0 - 10 Vdc Mode)
A1 used for flow meter, water level or suction pressure transducer.
External
24Vdc Power Supply
+ -
V+
Output
4-20mA
Transducer
*
250Ω iQpump
+V
A1
AC
EG
* Resistor 250 Ohm / 1% 1W
Refer to Page 242 of the
TM.iQp.06 User Manual for gain and bias settings.
48 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
13 Transducer Wiring using an External Power Supply
Duplex System: Single Transducer Connection using Analog Input A2
A2 used for pressure transducer.
External
24Vdc Power Supply
+ iQpump 1 iQpump 2
V+
Output
4-20mA
Outlet
Transducer
A2
AC
EG
A2
AC
EG
O
F
F
S1-2
1
2
Set S1-2 to ON Position (4-20mA) for both iQpump Drives (Factory Default)
Triplex System: Transducer Connection using Analog Input A2
A2 used for water level or suction pressure transducer.
External
24Vdc Power Supply
+ -
External Power Supply only required when connecting 2 or more drives.
V+
Output
4-20mA
Transducer iQpump 1
+V
A2
AC
EG iQpump 2
A2
AC
EG iQpump x
A2
AC
EG
Last drive on network
O
F
F
1
O
F
F
1
O
F
F
1
2 2 2
Set S1-2 to ON Position for the last iQpump Drive on the network . All other iQpump drives should have S1-2 set to OFF.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement 49
13 Transducer Wiring using an External Power Supply
Triplex System: Transducer Connection using Analog Input A1
A2 used for pressure transducer.
External
24Vdc Power Supply
+ -
External Power Supply only required when connecting 2 or more drives.
V+
Output
4-20mA
Transducer
*
Resistor 250 Ohm / 1% 1W
Refer to Page 242 of the
TM.iQp.06 User Manual for gain and bias settings.
*
250 iQpump 1
+V
A1
AC
EG iQpump 2
A1
AC
EG iQpump x
A1
AC
EG
Last drive on network
50 YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
A
Parameters for iQpump Software
PRG:0035 and 0036
This appendix lists all the parameter numbers and names, along with a description of each. Also, below the parameter name in bold type is the abbreviated name as it appears on the digital operator display/keypad.
PARAMETER LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
YASKAWA TM.iQp.10 Technical Manual Supplement 51
Parameter List
Table 1 Parameter List
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
A1-00
A1-01
A1-03
A1-04
A1-05
0100
0101
0103
0104
0105
Language Selection
Select Language
Access Level Selection
Access Level
Initialize Parameters
Init Parameters
Password 1
Enter Password
Password 2
Select Password
Initialization
Language selection for digital operator display.
0: English
2: Deutsch
3: Francais
4: Italiano
5: Espanol
*Not returned to factory setting by initialization
This setting determines which parameters are accessible.
0: Operation Only
2: Advanced Level
Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter default values and then parameter o2-03 must be set to “1” to save them. If the parameter values are changed after o2-03 is set to “1”, the user default values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial
7770: General Purpose <0035>
When the value set into A1-04 does NOT match the value set into A1-05, parameters A1-01 thru A1-03 cannot be changed.
All other parameters as determined by A1-01 can be changed. Parameter
A1-05 can be accessed by pressing the MENU key while holding the
RESET key.
0 ~ 6
0 or 2
0 ~ 7770
0 ~ 9999
0 ~ 9999
0
2
0
0
0
Programming
Programming
Programming
Programming
Programming
Denotes that parameter can be changed when the drive is running. * Menu location is Pump Quick Setup when b5-01=1, and Programming when b5-01=0.
Sequence b1-01 b1-02 b1-03
0180
0181
0182
Frequency Reference
Selection
Reference Source
Run Command Selection
Run Source
Stopping Method
Selection
Stopping Method
Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see parameter
H3-13)
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Geothermal Mode - frequency reference dependent on temperature input
(H3-09=20) <0035>
Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Timed Run <0034>
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if input before the time in C1-02 expires.)
0 ~ 5
0 ~ 3, 5
0 ~ 3
0
0
1
Programming
Programming
Default =0 prior to
PRG:
<0035>
Programming b1-04
<0035>
0183
Reverse Operation
Selection
Reverse Operation
1: Reverse Disabled
3: Exchange Phase, Reverse Disabled
1, 3 1 Programming b1-07 b1-08
0186
0187
Local/Remote Run
Selection
LOC/REM RUN Sel
Run Command Selection
During Program
RUN CMD at PRG
0: Cycle External RUN - If the run command is closed when switching from hand (local) mode to auto (remote) mode, the drive will not run.
1: Accept External RUN - If the run command is closed when switching from hand (local) mode to auto (remote) mode, the drive WILL run.
Note: Used with LCD Operator only.
0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus (except when b1-02 = 0).
After a run command, drive output will start after this delay time.
0 ~ 1
0 ~ 1
0
0
Programming
Programming b1-11 010F
Drive Delay Time Setting
Wait to Run Time
0 ~ 600 sec 0 sec Programming
52 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description b2-01 b2-02 b2-03
0189
018A
018B
DC Injection Braking Start
Frequency
DCInj Start Freq
DC Injection Braking
Current
DCInj Current
DC Injection Braking
Time at Start
DCInj Time @ Start
DC Braking
Sets the frequency at which DC injection braking starts when ramp to stop
(b1-03 = 0) is selected. If b2-01 < E1-09, DC injection braking starts at E1-
09.
Selects the DC injection braking current as a percentage of the drive rated current.
Sets the time length of DC injection braking at start in units of 1 second.
b2-04 b2-09 b3-01
018C
01E1
0191
DC Injection Braking
Time at Stop
DCInj Time @ Stop
Motor Pre-Heat Current
Preheat Current
Speed Search Selection
SpdSrch at Start
When b1-03 = 2 actual DC Injection time is calculated as follows: b2-04 x 10 x Output Frequency/E1-04. When b1-03 = 0, this parameter determines the amount of time DC Injection is applied to the motor at the end of the decel ramp. This should be set to a minimum of 0.50 seconds when using HSB. This will activate DC injection during the final portion of HSB and help ensure that the motor stops completely.
Motor Pre-heat current in % of drive rated current. This is used to keep the motor warm to prevent condensation and is used in conjunction with a digital input (data = 60).
Speed Search
Enables/disables and selects the speed search function at start.
0: SpdsrchF Disable - Speed search at start is disabled (estimated speed method is used at other times)
1: SpdsrchF Enable - Speed search is enabled (estimated speed method)
2: SpdsrchI Disable - Speed search at start is disabled (current detection method is used at other times)
3: SpdscrhI Enable - Speed search is enabled (current detection method)
Estimated Speed Method: Actual motor speed and direction is estimated, then the motor is ramped from that speed to the commanded speed.
Current Detection Method: Current level is monitored while output frequency is ramped down. b3-02 0192 b3-03 b3-05 b3-14
0193
0195
019E
Speed Search Deactivation
Current
SpdSrch Current
Speed Search Deceleration
Time
SpdSrch Dec Time
Speed Search Delay Time
Search Delay
Bidirectional Speed Search
Selection
Bidir Search Sel
Used only when b3-01 = 3. Sets the speed search operation current as a percentage of drive rated current.
Used only when b3-01 = 3. Sets the deceleration time during speed search.
Delays the speed search operation after a momentary power loss to allow time for an external output contactor to re-energize.
0: Disabled
1: Enabled b4-01 b4-02
01A3
01A4
Timer Function ON-Delay
Time
Delay-ON Timer
Timer Function OFF-
Delay Time
Delay-OFF Timer
Delay Timers
Used in conjunction with a multi-function digital input and a multifunction digital output. This sets the amount of time between when the digital input is closed, and the digital output is energized.
Used in conjunction with a multi-function digital input and a multifunction digital output. This sets the amount of time the output stays energized after the digital input is opened.
PI Control b5-01 01A5
PI Mode Setting
PI Mode
This parameter enable /disables the closed loop (PI) controller.
0: Disabled
1: Enabled (commanded speed becomes PI setpoint)
2: Enabled - 2 Zone (dual zone PI enabled) <0034> b5-02
b5-03
01A6
01A7
Proportional Gain Setting
P Gain
Integral Time Setting
PI I Time
Sets the proportional gain of the PI controller.
Sets the integral time for the PI controller. A setting of zero disables integral control.
b5-04
01A8
Integral Limit Setting
PI I Limit
Sets the maximum output possible from the integrator. Set as a % of fmax.
b5-06
01AA
PI Output Limit
PI Limit
Sets the maximum output possible from the entire PI controller. Set as a % of fmax.
Denotes that parameter can be changed when the drive is running.
Setting
Range
0.0 ~
10.0 Hz
0 ~ 100 %
0.00 to
10.00 sec
0.00 ~
10.00 sec
0 ~ 100 %
0 ~ 3
0 ~ 200 %
0.1 ~
10.0 sec
0.0 ~
20.0 sec
0 ~ 1
0.0 ~
3000.0 sec
0.0 ~
3000.0 sec
0 ~ 2
0.00 ~
25.00
0.0 ~
360.0 sec
0.0 ~
100.0 %
0.00 ~
100.00 %
Factory
Setting
Menu
Location
0.5 Hz Programming
50 % Programming
0.00 sec Programming
0.5 sec Programming
0 %
2
120 % Programming
2.0 sec Programming
0.2 sec Programming
1
0.0 sec Programming
0.0 sec Programming
1
2.00
Programming
Programming
Programming
Programming
Programming
3.0 sec Programming
100.0 % Programming
100.00 % Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 53
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description b5-07
01AB
PI Offset Adjustment
PI Offset
Sets the amount of offset of the output of the PI controller. Set as a % of fmax.
The PI Offset Adjustment parameter has two different uses. Parameter b5-
07 serves different functions depending on whether it is used on a standard
PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of the PI function in a non-Differential PI loop. Every time the PI output is updated, the offset is summed with the PI output. This can be used to artificially kick-start a slow starting PI loop.
2: If the drive is configured for Differential PI Regulation
(H3-09 = 16), then the PI Offset is the targeted maintained differential between the signal measured on analog input A1 and the signal measured on analog input A2.
b5-08
01AC
PI Primary Delay Time
Constant
PI Delay Tim e
Sets the amount of time for a filter on the output of the PI controller.
b5-09 01AD
PI Output Level Selection
Output Level Sel
Determines whether the PI controller will be direct or reverse acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting) b5-10 b5-12 b5-13 b5-14
01AE
01B0
01B1
01B2
PI Output Gain Setting
Output Gain
PI Feedback Reference
Missing Detection
Selection
Fb los Det Sel
PI Feedback Loss
Detection Level
Fb los Det Lvl
PI Feedback Loss
Detection Time
Fb los Det Time
Sets the output gain of the PI controller.
0: Disabled
1: Alarm
2: Fault
Sets the PI feedback loss detection level as a percentage of maximum frequency (E1-04).
Sets the PI feedback loss detection delay time in terms of seconds.
b5-17 b5-32
01B5
85F
PI Accel/Decel Time
Acc/Dec Time
Integrator Ramp Limit
Int Ramp Lim
Applies an accel/decel time to the PI setpoint reference.
When set a value greater than zero, the PI Integrator is forced to be within
+/- this amount of the soft starter output
Denotes that parameter can be changed when the drive is running.
Energy Saving b8-01 01CC
Energy Savings function enable/disable selection
0: Disabled
1: Enabled b8-04 b8-05 b8-06
01CF
01D0
01D1
Energy Saving Control
Selection
Energy Save Sel
Energy Saving Coefficient
Value
Energy Save COEF
Power Detection Filter
Time kW Filter Time
Search Operation Voltage
Limit
Search V Limit
Used to fine-tune the energy savings function.
Setting
Range
–100.0 ~
+100.0 %
0.00 ~
10.00 sec
0 ~ 1
0.0 ~ 25.0
0 ~ 2
0 ~ 100 %
0.0 ~
25.5 sec
0.0 ~
25.5 sec
0.0 ~
10.0 Hz
0 ~ 1
0.0 ~ 655.0
0 ~
2000 ms
0 ~ 100 %
Factory
Setting
Menu
Location
0.0 % Programming
0.00 sec Programming
0
1.0
2
0 %
2.0 sec Programming
0.0 sec Programming
0.0 Hz Programming
0 kVA
Dependent
Programming
20 ms Programming
0 %
Programming
Programming
Programming
Programming
Programming
Programming
Accel/Decel
C1-01
C1-02
C1-03
C1-04
0200
0201
0202
0203
Acceleration Time 1
Accel Time 1
Deceleration Time 1
Decel Time 1
Acceleration Time 2
Accel Time 2
Deceleration Time 2
Decel Time 2
Sets the time to accelerate from zero to maximum frequency.
Sets the time to decelerate from maximum frequency to zero.
Sets the time to accelerate from zero to maximum frequency when selected via a multi-function input.
Sets the time to decelerate from maximum frequency to zero when selected via a multi-function input.
C1-05
0204
Acceleration Time 3
Accel Time 3
Sets the time to accelerate from zero to maximum frequency when activated by P3-12. Used for system response stabilization.
C1-06
0205
Deceleration Time 3
Decel Time 3
Sets the time to decelerate from maximum frequency to zero when activated by P3-12. Used for system response stabilization.
Denotes that parameter can be changed when the drive is running.
0.0 ~
6000.0 sec
20.0 sec Programming
10.0 sec Programming
10.0 sec Programming
10.0 sec Programming
50.0 sec Programming
50.0 sec Programming
54 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
C1-09
C1-11
0208
020A
Parameter Name
Digital Operator
Display
Fast Stop Time
Fast Stop Time
Accel/Decel Switch
Frequency
Acc/Dec SW Freq
Description
Setting
Range
Sets the time to decelerate from maximum frequency to zero for the “Fast
Stop” function.
Sets the frequency for automatic switching of accel/decel times.
Fout < C1-11: Accel/Decel Time 2
Fout > = C1-11: Accel/Decel Time 1
Multi-function input “Multi-Acc/Dec 1" has priority over C1-11.
S-Curve Accel/Decel
0.0 ~
6000.0 sec
0.0 ~
200.0 Hz
Factory
Setting
Menu
Location
10.0 sec Programming
0.0 Hz Programming
C2-01 020B
S-Curve Characteristic at
Accel Start
SCrv Acc @ Star t
S-curve is used to further soften the starting ramp.
The longer the S-curve time, the softer the starting ramp.
0.00 ~
2.50 sec
0.20 sec Programming
Run command
ON
Output frequency
C2-02
OFF
C2-02 020C
S-Curve Characteristic at
Accel End
SCrv Acc @ End
0.00 ~
2.50 sec
0.20 sec Programming
C2-01
Time
C6-02 0224
Carrier Frequency
Selection
CarrierFreq Sel
Torque Compensation
C4-01
C4-02
0215
0216
Torque Compensation
Gain
Torq Comp Gain
Torque Compensation
Primary Delay Time
Torq Comp Time
This parameter helps to produce better starting torque. It determines the amount of torque or voltage boost based upon motor current and motor resistance.
This parameter adjusts a filter on the output of the torque compensation function. Increase to add torque stability, decrease to improve torque response.
Denotes that parameter can be changed when the drive is running.
Carrier Frequency
Carrier frequency sets the number of pulses per second of the output voltage waveform.
1: 2.0 kHz
2: 5.1 kHz
3: 8.0 or 7.0* kHz
F: Program (Determined by the setting of C6-03)
* when an option card is installed
Note: In PRG: <0035> C6-02 is default is 2 kHz for all KVA sizes except
when A1-03=7770. Refer to page 40
for setting details.
C6-03 0225
Carrier Frequency Upper
Limit
CarrierFreq Max
Maximum carrier frequency allowed when C6-02 = F.
0.00 ~ 2.50
0 ~
10000 ms
1 ~ F
0.4 ~
15.0 kHz
1.00
Programming
200 ms Programming kVA
Dependent
Programming kVA
Dependent
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 55
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description d1-01
d1-02
d1-03
d1-04
d3-01 d3-02 d3-03
0280
0281
0282
0283
0294
0295
0296
Set-point Reference 1
Set-point 1
Set-point Reference 2
Set-point 2
Set-point Reference 3
Set-point 3
Set-point Reference 4
Set-point 4
Preset Reference
Digital preset setpoint reference 1. Used when b1-01 = 0 and when in
“hand” mode. Setting units are affected by P1-02.
Digital preset setpoint reference 2. Selected via multi-function input terminals. Setting units are affected by P1-02.
Parameter d1-02 is also the Zone 1 PI reference when b5-01 = 2. <0034>
Digital preset setpoint reference 3. Selected via multi-function input terminals. Setting units are affected by P1-02.
Parameter d1-03 is also the Zone 2 PI reference when b5-01 = 2. <0034>
Digital preset setpoint reference 4. Selected via multi-function input terminals. Setting units are affected by P1-02.
Parameter d1-04 is also the Zone 1 and 2 PI reference when b5-01 = 2.
<0034> d1-17
0292
Jog Frequency Reference
Jog Reference
Jog reference used when a jog is selected via the LCD operator keypad.
This parameter is not available with the HOA operator. Setting units are affected by o1-03.
Denotes that parameter can be changed when the drive is running.
Reference Limits d2-01 d2-02
0289
028A
Frequency Reference
Upper Limit
Ref Upper Limit
Frequency Reference
Lower Limit
Ref Lower Limit
Determines maximum speed command, set as a percentage of parameter
E1-04. If speed command is above this value, actual drive speed will be limited to this value. This parameter applies to all speed command sources.
Determines minimum speed command, set as a percentage of parameter
E1-04. If speed command is below this value, actual drive speed will be set to this value. This parameter applies to all speed command sources.
d2-03 0293
Master Speed Reference
Lower Limit
Ref1 Lower Limit
Determines the minimum speed command, set as a percentage of parameter E1-04. If speed command is below this value, actual drive speed will be set to this value. This parameter only applies to analog inputs A1 and A2.
Jump Frequencies
Jump Frequency 1
Jump Freq 1
Jump Frequency 2
Jump Freq 2
Jump Frequency 3
Jump Freq 3
These parameters allow programming of up to three prohibited frequency points for eliminating problems with resonant vibration of the motor/ machine. This feature does not actually eliminate the selected frequency values, but will accelerate and decelerate the motor through the prohibited bandwidth.
d3-04 0297
Jump Frequency Width
Jump Bandwidth
This parameter determines the width of the deadband around each selected prohibited frequency point. A setting of “1.0” will result in a deadband of
+/- 1.0 Hz.
V/f Pattern
Setting
Range
1 ~ P1-03
Value
0.00 to
P1-02
Value
<0034>
0.0 ~
110.0 %
0.0 ~
110.0 %
0.0 ~
110.0 %
0.0 ~
200.0 Hz
0.0 ~
20.0 Hz
E1-01 0300
Input Voltage Setting
Input Voltage
Set to the nominal voltage of the incoming line.
155 ~
255.0
(240V)
310 to
510.0
(480V)
E1-03 0302
V/f Pattern Selection
V/f Selection
0: 50 Hz
1: 60 Hz Saturation
2: 50 Hz Saturation
3: 72 Hz
4: 50 Hz VT1
5: 50 Hz VT2
6: 60 Hz VT1
7: 60 Hz VT2
8: 50 Hz HST1
9: 50 Hz HST2
A: 60 Hz HST1
B: 60 Hz HST2
C: 90 Hz
D: 120 Hz
F: Custom V/F
FF: Custom w/o limit
0 ~ FF
Factory
Setting
0.00
0.00
0.00
0.00
0.00
Menu
Location
Programming
Programming
Programming
Programming
Programming
100.0 % Programming
0.0 % Programming
0.0 % Programming
0.0 Hz Programming
0.0 Hz Programming
0.0 Hz Programming
1.0 Hz Programming
240 V
480 V
F
Programming
Programming
56 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
E2-01
E2-03
E2-04
E2-05
F6-01
F6-02
F6-03
F6-05
0303
0304
0305
0306
0307
0308
0309
030A
030B
030C
030E
030F
0311
0312
03A2
03A3
03A4
03A6
Parameter Name
Digital Operator
Display
Maximum Output
Frequency
Max Frequency
Output voltage (V)
0: Always detected
1: Detected only during run
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Description
Setting
Range
0.0 ~
120.0 Hz
Factory
Setting
Menu
Location
60.0 Hz Programming
Maximum Output Voltage
Max Voltage
Base Frequency
Base Frequency
Mid Output Frequency A
Mid Frequency A
Mid Output Voltage A
Mid Voltage A
Minimum Output
Frequency
Min Frequency
Mid Output Voltage
Min Voltage
Mid Output Frequency B
Mid Frequency B
Mid Output Voltage B
Mid Voltage B
Base Voltage
Base Voltage
Motor Rated Current
Motor Rated FLA
No-Load Current
Number of Motor Poles
Number of Poles
Motor Line-to-Line
Resistance
Term Resistance
VMAX
(E1-05)
VBASE
(E1-13)
VA
(E1-08)
VMIN
(E1-10)
0.0 ~ 255.0
(240V)
0.0 to 510.0
(480V)
0.0 ~
200.0 Hz
0.0 ~
200.0 Hz
0.0 ~ 255.0
(240V)
0.0 to 510.0
(480V)
230.0 V
460.0 V
Programming
60.0 Hz Programming
3.0 Hz Programming
17.2 Vac
34.5 Vac
Programming
FMIN FA FBASE FMAX
(E1-09) (E1-07) (E1-06) (E1-04)
Frequency (Hz)
0.0 ~
200.0 Hz
1.5 Hz Programming
To set V/f characteristics in a straight line, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E1-04 (FMAX) E1-06 (FA) > E1-07 (FB) E1-09 (FMIN)
Set only when V/f is finely adjusted at rated output range.
Adjustment is not normally required.
0.0 ~ 255.0
(240V)
0.0 to 510.0
(480V)
0.0 ~
200.0 Hz
0.0 ~ 255.0
(240V)
0.0 to 510.0
(480V)
0.0 ~ 255.0
(240V)
0.0 to 510.0
(480V)
10.3 Vac
20.7 Vac
Programming
0.0 Hz Programming
0.0 Vac Programming
0.0 Vac Programming
Motor Setup
Set to the motor nameplate full load amps.
Sets the magnetizing current of the motor.
Set to the number of poles. Used for no-flow detection function and for the calculation of rpm related parameters.
10 ~
200 % kVA
Dependent kVA
Dependent kVA
Dependent
Pump Quick
Setup
Programming
2 ~ 48 2
Pump Quick
Setup
Phase to phase motor resistance, normally set by the autotuning routine.
0.000 ~
65.000
kVA
Dependent
Programming
Operation Selection after
Communication Error
Com Bus Flt Sel
Communication Option Setup
Sets the stopping method for option PCB communications error (BUS fault). Active only when a communications option PCB is installed and when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 ~ 3 1 Programming
Input Level of External
Fault from
Communication Option
Card
EF0 Detection
Stopping Method for
External Fault from
Communication Option
Card
EF0 Fault Action
0 ~ 1
0 ~ 3
0
1
Programming
Programming
Current Monitor Display
Unit Selection
Current Unit Sel
0: A Display
1: 100 % /8192 (Drive Rated Current)
0 ~ 1 0 Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 57
Parameter
No.
Addr.
Hex
H1-01
H1-02
Parameter Name
Digital Operator
Display
0400
Terminal S3 Function
Selection
Terminal S3 Sel
0401
Terminal S4 Function
Selection
Terminal S4 Sel
H1-03
(continued on next page)
0402
Terminal S5 Function
Selection
Terminal S5 Sel
Description
Digital Inputs
0: 3-wire control
FWD/REV selection for 3-wire sequence
1: Local/Remote Sel
Hand/Auto Selection - Closed = Hand, Open = Auto
2: Option/Inv Sel
Selects source of speed command and sequence.
Closed = b1-01 & b1-02, Open = Option Card
3: Multi-Step SP1
Closed = speed command from d1-02 or Aux Terminal.
Open = speed command determined by b1-01.
4: Multi-Step SP2
Closed = speed command from d1-03 or d1-04.
Open = speed command determined by b1-01.
7: Multi-Acc/Dec 1
Closed = Accel & Decel Ramps determined by C1-03 & C1-04.
Open = Accel & Decel Ramps determined by C1-01 & C1-02.
8: Ext BaseBlk N.O.
Closed = Output transistors forced off, Open = Normal operation.
9: Ext BaseBlk N.C.
Closed = Normal Operation, Open = Output transistors forced off.
A: Acc/Dec RampHold
Closed = Acceleration suspended and speed held, Open = Normal
Operation.
C: Term A2 Enable
Closed = Terminal A2 is active, Open = Terminal A2 is disabled.
F: Term Not Used
Terminal has no effect.
10: MOP Increase
Closed = Speed Command Increases, Open = Speed Command Held.
Must be set in conjunction with MOP Decrease and b1-02 must be set to 1.
11: MOP Decrease
Closed = Speed Command Decreases, Open = Speed Command Held.
Must be set in conjunction with MOP Increase and b1-02 must be set to 1.
14: Fault Reset
Closed = Resets the drive after the fault and the run command have been removed.
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of run command status.
17: Fast-Stop N.C.
Closed = Normal operation.
Open = Drive decelerates using C1-09, regardless of run command status.
18: Timer Function
Input for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with a multi-function digital output.
19: PI Disable
Turns off the PI controller, and PI setpoint becomes speed command.
1B: Program Lockout
Closed =All parameter settings can be changed.
Open = Only speed command at U1-01 can be changed.
20: External Pump Fault, Normally Open, Always Detected, Ramp To Stop
21: External Pump Fault, Normally Closed, Always Detected, Ramp To
Stop
22: External Pump Fault, Normally Open, During Run, Ramp To Stop
23: External Pump Fault, Normally Closed, During Run, Ramp To Stop
24: External Pump Fault, Normally Open, Always Detected, Coast To Stop
25: External Pump Fault, Normally Closed, Always Detected, Coast To
Stop
Setting
Range
Factory
Setting
Menu
Location
0 ~ 87
0 ~ 87
0 ~ 87
24
14
Programming
Programming
3: 2-wire
0: 3-wire
Programming
58 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
H1-04
(continued on next page)
0403
Parameter Name
Digital Operator
Display
Terminal S6 Function
Selection
Terminal S6 Sel
Description
26: External Pump Fault, Normally Open, During Run, Coast To Stop
27: External Pump Fault, Normally Closed, During Run, Coast To Stop
28: External Pump Fault, Normally Open, Always Detected, Fast-Stop
29: External Pump Fault, Normally Open, Always Detected, Fast-Stop
2A: External Pump Fault, Normally Open, During Run, Fast-Stop
2B: External Pump Fault, Normally Closed, During Run, Fast-Stop
2C: External Pump Fault, Normally Open, Always Detected, Alarm Only
2D: External Pump Fault, Normally Closed, Always Detected, Alarm Only
2E: External Pump Fault, Normally Open, During Run, Alarm Only
2F: External Pump Fault, Normally Closed, During Run, Alarm Only
30: PID Integral Reset
31: PID Integral Hold
34: PI SFS Cancel
36: Option/Inv Sel 2
Selects source of speed command and sequence.
Closed = Option Card, Open = b1-01 & b1-02.
60: Motor Preheat Applies current to create heat to avoid condensation.
Closed = Apply amount of current as set in parameter b2-09.
61: Speed Search 1
When closed as a run command is given, drive does a speed search starting at maximum frequency (E1-04). (Current detection.)
62: Speed Search 2
When closed as a run command is given, drive does a speed search starting at speed command. (Current detection.)
64: Speed Search 3
67: Com Test Mode - Used to test RS-485/422 interface.
Direction determined by fwd/rev input. 3-wire control Only.
6A: Drive Enable - Closed = Drive will accept run command.
Open = Drive will not run. If running, drive will stop per b1-03.
6B: Com/Inv Sel - Selects source of speed command and sequence
Closed = Serial Communication (R+,R-,S+,S-), Open = b1-01 & b1-02
6C: Com/Inv Sel 2
72: Remote Drv Disbl <0035>
Prevents the drive from running when active for the time set in P4-25.
Must be inactive for the time set in P4-26 to allow the drive to run again.
Note : Parameter P4-24 determines if this input is Normally Open or
Normally Closed.
73: Low City Press <0034>
Indicates that sufficient/insufficient pressure is present on the inlet to the pump. Used mainly for pressure booster stations. When P1-01 = 3, an alarm condition (see parameters P4-21 and P4-22) will cause drives in the network to stop running and show a “Net Pump Err” message. 75: Reset
Accum <0034>
Closed: Volume accumulated will be reset to zero (and held at zero if digital input remains closed).
76: High Water Level <0034>
Function will be active whenever the drive is running. Function logic depends on parameter P1-15 (Water DI Config).
P1-15 = 0 or 1 (Normally Open)
Closed: High Water Level Fault
Open: Reservoir/Tank is filled to normal level.
P1-15 = 2 or 3 (Normally Closed)
Closed: Reservoir/Tank is filled to normal level.
Open: High Water Level Fault
80: Hand Mode
Function Active in Stopped and Auto Mode.
Closed: Hand mode operation as defined in P1-14.
Open: Stop Mode when with no incoming run command.
Note: Input not active when b1-02 is set for 0 – Operator.
81: Disable Sleep Mode
Function Active in Auto Mode.
Closed: Disables sleep function, Feedback Drop Detection and Over cycle protection.
Open: Sleep function, Feedback Drop Detection and Over cycle protection enabled.
82: Sleep Activation
Active in Auto Mode.
Closed: Drive will go to sleep (External Digital Input).
Open: No function.
Setting
Range
0 ~ 87
Factory
Setting
80
Menu
Location
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 59
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
H1-05
0404
Terminal S7 Function
Selection
Terminal S7 Sel
83: Thermostat Fault,
Function Active in Auto Mode.
Closed: Drive will trip on “Thermostat Fault”.
Open: Thermostat fault not active.
Open: Low Water Level Fault.
84: Pre-charge
Closed: Disables pre-charge function.
Open: Pre-charge function enabled.
85: Low Water Level <0034>
Function Active in Auto Mode during normal operation, also used with pre-charge function.
Function logic depends on parameter P1-15 (Water DI Config).
P1-15 = 0, or 2 (Normally open).
Closed: Low Water Level Fault.
Open: Reservoir/Tank is filled to normal level.
P1-15 = 1 or 3 (Normally Closed).
Closed: Reservoir/Tank is filled to normal level.
Pre-charge function: Function uses low water level input as “Tank/
Reservoir” feedback to indicate water level reached.
IMPORTANT
Program P1-15 to 0 or 2 when the “Low Water” function is not used. 86:
Fixed Speed Auto
Function Active in Auto Mode Only, Pre-charge and Thrust Bearing function have a higher priority. When fixed speed auto is active (closed) drive disabled Sleep Mode and Lead/Lag operation.
Closed: Drive runs at P3-02 frequency, PI Control disabled
Open: Drive runs normal operation auto mode.
87: Thermostat Fault, Normally Closed <0032>
Function Active in Auto Mode.
Closed: Thermostat fault not active.
Open: Drive will trip on “Thermostat Fault”.
H1-12
<0034>
H1-13
<0034>
H1-14
<0034>
H1-15
<0034>
87A
87B
87C
87D
External Fault 3 Delay
Time
EF3 Delay Time
External Fault 4 Delay
Time
EF4 Delay Time
External Fault 5 Delay
Time
EF5 Delay Time
External Fault 6 Delay
Time
EF6 Delay Time
Sets the amount of time delay applied to the EF3 fault.
(20
Sets the amount of time delay applied to the EF4 fault.
(20
(20
≤
≤
≤
H1-01
H1-02
H1-03
≤
≤
≤
2F
2F
Sets the amount of time delay applied to the EF5 fault.
2F
Sets the amount of time delay applied to the EF6 fault.
(20 ≤ H1-04 ≤ 2F )
)
)
)
H1-16
<0034>
87E
External Fault 7 Delay
Time
EF7 Delay Time
Sets the amount of time delay applied to the EF7 fault.
(20 ≤ H1-05 ≤
Denotes that parameter can be changed when the drive is running.
2F )
0 ~ 87
0.00 ~
300.00 sec
0.00 ~
300.00 sec
0.00 ~
300.00 sec
0.00 ~
300.00 sec
0.00 ~
300.00 sec
84 Programming
0.00 sec Programming
0.00 sec Programming
0.00 sec Programming
0.00 sec Programming
0.00 sec Programming
60 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
H2-01
H2-02
(continued on next page)
040B
040C
Parameter Name
Digital Operator
Display
Description
Terminal M1-M2 Function
Selection
Term M1-M2 Se l
Terminal M3-M4 Function
Selection
Term M3-M4 Sel
Digital Outputs
0: During RUN 1 = Closed when a run command is input or the drive is outputting voltage.
1: Zero Speed = Closed when drive output frequency is less than Fmin (E1-
09).
2: Fref/Fout Agree 1 = Closed when drive output speed equals the speed command within the bandwidth of L4-02.
3: Fref/Set Agree 1 = Closed when the drive output speed and the speed command are equal to the value in L4-01 within the bandwidth of L4-02.
4: Freq Detect 1 = Closed when the drive output speed is less than or equal to the value in L4-01, with hysteresis determined by L4-02.
5: Freq Detect 2 = Closed when the drive output speed is greater than or equal to the value in L4-01, with hysteresis determined by L4-02.
6: Inverter Ready = Closed when the drive is not in a fault state, and not in program mode.
7: DC Bus Undervolt = Closed when the DC bus voltage falls below the
UV trip level (L2-05).
8: Base Blk 1 = Closed when the drive is not outputting voltage.
9: Operator Reference = Closed when the speed command is coming from the digital operator.
A: Remote/Auto Oper = Closed when the run command is coming from the digital operator.
B: Trq Det 1 N.O. - Closes when the output current exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03.
C: Loss of Ref - Closes when the drive has detected a loss of analog speed command.
Speed command is considered lost when it drops 90 % in 0.4 seconds.
Parameter L4-05 determines drive reaction to a loss of speed command.
D: DB Overheat.
E: Fault - Closes when the drive experiences a major fault.
F: Not Used
10: Minor Fault - Closes when drive experiences a minor fault or alarm.
11: Reset Cmd Active - Closes when the drive receives a reset command from terminals or serial comms.
12: Timer Output - Output for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with a multi-function digital input.
17: Trq. Det 1 N.C. - Opens when the output current exceeds the value set in parameter.
L6-02 for more time than is set in parameter L6-03.
1A: Reverse Dir - Closes when the drive is running in the reverse direction.
1E: Restart Enabled - Closes when the drive is performing an automatic restart.
Automatic restart is configured by parameter L5-01.
1F: Overload (OL1) - Closes before a motor overload occurs. (90 % of
OL1 time).
20: OH Prealarm - Closes when the drive’s heatsink temperature exceeds the setting of parameter L8-02.
38: Drive Enable - Closes when the drive enable input is active.
39: Waiting to Run - Closes during the time after a run command is issued, but the drive is not running due to the time set in parameter b1-10.
3A: OH Freq Reduce
3B: Run Src Com/Opt
3D: Cooling Fan Err = Closed during internal cooling fan failure.
40: Pump 2 Control
Open: Shutdown Additional Pump 2.
Closed: Start Additional Pump 2.
Function Active in multiplex mode.
Contactor control for second pump.
41: Pump 3 Control
Open: Shutdown Additional Pump 3.
Closed: Start Additional Pump 3.
Function Active in multiplex mode.
Contactor control for second pump.
Setting
Range
0 ~ 57
0 ~ 57
Factory
Setting
Menu
Location
40
41
Programming
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 61
Parameter
No.
Addr.
Hex
H2-02
(continued)
040C
Parameter Name
Digital Operator
Display
Description
Terminal M3-M4 Function
Selection
Term M3-M4 Sel
42: Pump Fault
Function Active in hand, auto, pre-charge and thrust mode
Open: No Dedicated Pump Faults are active.
Closed: Dedicated pump fault active (Low Feedback Fault, High Feedback
Fault, Over Cycling Fault, Pump Protection Fault,
Thermostat Fault, Low Water Fault, Ext. Pump Fault).
43: Mot 2 Alternate <0034>
Used in conjunction with the 2-motor alternation function.
Open: Motor 1 in use (or 2-motor alternation is disabled).
Closed: Motor 2 in use.
44: Sleep Active <0034>
Closed: Drive is in the sleep mode.
45: Start Lvl Delay <0034>
Closed: During the Start Level Delay Time (P1-05). Feedback has dropped below the P1-04 level and the drive is delaying running.
46: Thrust Bearing <0034>
Closed: The Thrust Bearing feature is active (output frequency is between zero and P4-05).
47: Pre-charge <0034>
Closed: The Pre-charge feature is active (configured by P4-01 ~
P4-03). -OR-
Closed: The Pre-charge 2 feature is active (configured by P4-12 ~
P4-13).
48: High Feedback <0034>
Closed: During a “High FB/Water” Fault. -OR-
Closed: During a “Low Feedback” Alarm.
49: Low Feedback <0034>
Closed: During a “High FB/Water” Fault. -OR-
Closed: During a “Low Feedback” Alarm.
4A: Transducer Loss <0034>
Closed: Feedback Loss has been detected (configured by b5-12 ~ b5-14). -OR-
Closed: Feedback Loss has been detected on A1 (dual-zone PI). <0035>-
OR-
Closed: During a “FBL - Feedback Loss Fault”.
4B: Set-point Not Met <0034>
Closed: During an “NMS - Set-point Not Met” Fault. -OR-
Closed: Feedback level is outside of the P1-11 window. (P1-12 time delay is not applied).
Note: If P1-11 is set to zero, this digital output will always be open.
4C: Loss of Prime <0034>
Closed: During a “LOP - Loss Of Prime” Fault. -OR-
Closed: Output current is below the P1-14 level.
Note : If P1-14 is set to zero, this digital output will always be open.
4D: Thermostat Fault <0034>
Closed: Thermostat Fault is present.
4E: Low Flow <0034>
Closed: During the “Low Flow Fault” condition. -OR-
Closed: During a low flow condition as set by P6-04 ~ P6-06 (includes
“Low Flow Alarm”).
4F: Accum Level <0034>
Closed: Accumulated level has exceeded the P6-09 and P6-10 setting.
-OR-
Closed: During the “Accum Level” Fault.
50: Utility Delay <0034>
Closed: Drive is stopped and is waiting for the utility delay timer to expire
(configured by P4-11).
51: Run/Stop-Stop <0034>
Closed: Drive is stopped due to the run/stop control (P4-18 and
P4-19) -OR-
Closed: Drive is stopped because the number of run/stop cycles has completed. (P4-20)
52: Run/Stop - Finish <0034>
Closed: Drive is stopped because the number of run/stop cycles has completed. (P4-20)
53: Anti-Jam/De-Scale <0034>
Closed: When the Anti-Jam or the De-Scale features are active (configured by P7 ).
54: During Run 2 <0034>
Closed: Whenever the drive is outputting voltage to the motor (not baseblocked).
Setting
Range
0 ~ 57
Factory
Setting
41
Menu
Location
Programming
62 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
H2-02
(continued)
H3-02
H3-03
H3-08
H3-09
H3-10
H3-11
H3-12
040C
0411
0412
0417
0418
0419
041A
041B
Parameter Name
Digital Operator
Display
Description
Terminal M3-M4 Function
Selection
Term M3-M4 Sel
Terminal A1 Gain Setting
Terminal A1 Gain
Terminal A1 Bias Setting
Terminal A1 Bias
Terminal A2 Signal Level
Selection
Term A2 Signal
Aux Terminal Function
Selection
Terminal A2 Sel
55: Lube Pump <0034>
Closed: When the Lube Pump Feature is active.
This will energize for the time set in parameter P4-23 each time the drive is supposed to start. The drive will delay starting for the P4-23 time.
56: High Flow <0034>
Closed: During the “High Flow Fault” condition. -OR-
Closed: During a high flow condition as set by P6-12 ~ P6-14 (included
“High Flow Alarm”)
57: Low Water Level <0034>
Closed: During the “Low Water Level” condition as set by P8-07 and P8-
08. -OR-
Closed: During the LOWWL - Low Water Level Fault”.
This will energize if P8-01 = 1 and the level in the well drops below the
Low Level Detection Level (P8-07) for more than the Low Level
Detection Delay Time (P8-08), or if there is a LOWWL - Low Water Level
Fault.
58: Low Suction <0035>
This will energize if P8-01 = 2 and the suction pressure drops below the
Low Suction Pressure Detection Level (P8-07) for more that the Low
Suction Pressure Delay Time (P8-08), of if there is a LOSUC - Low
Suction Pressure Fault.
Analog Inputs
Sets the speed command when 10 V is input, as a percentage of the maximum output frequency (E1-04).
Sets the speed command when 0 V is input, as a percentage of the maximum output frequency (E1-04).
Selects the signal level of Terminal A2.
0: 0 - 10 Vdc (switch S1-2 must be in the off position)
2: 4 - 20 mA (switch S1-2 must be in the on position)
3: 0- 20 mA
Selects what effect the aux terminal has on the drive.
0: Frequency Bias - 0 - 100 % bias
2: Aux Reference
B: PI Feedback
D: Frequency Bias 2 - 0 - 100 % bias
E: Motor Temperature - See parameters L1-03 & L1-04
16: PI Differential
20: Geothermal Mode <0035>
1F: Not Used
Terminal A2 Gain Setting
Terminal A2 Gain
Terminal A2 Bias Setting
Terminal A2 Bias
Analog Input Filter Time
Constant Filter Avg Time
Analog Input Fil Tim
Sets the percentage when 10 V (20 mA) is input.
Sets the percentage when 0 V (4 mA) is input.
Used to “smooth” out erratic or noisy analog input signals.
Setting
Range
0 ~ 57
0.0 ~
1000.0 %
–100.0 ~
+100.0 %
0 or 2
0 ~ 1F
0.0 ~
1000.0 %
–100.0 ~
+100.0 %
0.00 ~
2.00 sec
Factory
Setting
41
Menu
Location
Programming
100.0 % Programming
0.0 % Programming
2
B
Programming
Programming
100.0 % Programming
0.0 % Programming
0.30 sec Programming
H3-13 041C
Master Frequency
Reference
Terminal Sel TA1/A2
Select
Determines which terminal will be the main reference source.
0: Main Fref TA1 - Terminal TA1 is the main speed command and
Terminal TA2 is the Aux speed command.
1: Main Fref TA2 - Terminal TA2 is the main speed command and
Terminal TA1 is the Aux speed command. Only effective when H3-09 is set to 2 “Aux Reference”.
0 ~ 1 0 Programming
Denotes that parameter can be changed when the drive is running.
YASKAWA TM.iQp.10 Technical Manual Supplement 63
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
H4-01
H4-02
H4-03
H4-04
041D
041E
041F
0420
Terminal FM Monitor
Selection
Terminal FM Sel
Terminal FM Gain Setting
Terminal FM Gain
Terminal FM Bias Setting
Terminal FM Bias
Terminal AM Monitor
Selection
Terminal AM Sel
Analog Outputs
Selects which monitor will be output on Terminals FM and AC.
1: Frequency Ref (100 % = max. output frequency)
2: Output Freq (100 % = max. output frequency)
3: Output Current (100 % = drive rated current)
6: Output Voltage (100 % = 230 V or 100 % = 460 V)
7: DC Bus Voltage (100 % = 400 V or 100 % = 800 V)
8: Output kWatts (100 % = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100 % = Motor rated secondary current)
20: SFS Output (100 % = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Set-point
Note: 100% = 10 V DC output x FM gain setting (H4-02).
Sets Terminal FM output voltage (in percent of 10 V) when selected monitor is at 100 % output.
Sets Terminal FM output voltage (in percent of 10 V) when selected monitor is at 0 % output.
Selects which monitor will be output on Terminals AM and AC.
1: Frequency Ref (100 % = max. output frequency)
2: Output Freq (100 % = max. output frequency)
3: Output Current (100 % = drive rated current)
6: Output Voltage (100 % = 230 V or 100 % = 460 V)
7: DC Bus Voltage (100 % = 400 V or 100% = 800 V)
8: Output kWatts (100 % = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100 % = Motor rated secondary current)
20: SFS Output (100 % = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100 % % = max. output frequency)
38: PI Set-point
Note: 100 % = 10 V DC output x AM gain setting (H4-05).
Sets Terminal AM output voltage (in percent of 10 V) when selected monitor is at 100 % output.
Sets Terminal AM output voltage (in percent of 10 V) when selected monitor is at 0 % output.
1 ~ 38
<0032>
0.0 ~
1000.0 %
–110.0 ~
+110.0 %
1 ~ 38
<0032>
2
100.0 % Programming
0.0 % Programming
8
Programming
Programming
H4-05
H4-06
H4-07
H4-08
0421
0422
0423
0424
Terminal AM Gain Setting
Terminal AM Gain
Terminal AM Bias Setting
Terminal AM Bias
Terminal FM Signal Level
Selection
AO Level Select1
Terminal AM Signal Level
Selection
AO Level Select2
0: 0 - 10 Vdc
2: 4 - 20 mA*
0: 0 - 10 Vdc
2: 4 - 20 mA*
0.0 ~
1000.0 %
–110.0 ~
+110.0 %
0 or 2
0 or 2
50.0 % Programming
0.0 % Programming
0
0
Programming
Programming
Denotes that parameter can be changed when the drive is running. * An analog output of 4 - 20 mA cannot be used with the standard terminal board. Therefore an optional terminal board (with shunt connector CN15) is needed.
Serial Communication Setup
H5-01
H5-02
0425
0426
Drive Node Address
Serial Com Adr
Communication Speed
Selection
Serial Baud Rate
Selects drive station node number (address) for Terminals R+, R-, S+, S-.
Note: An address of “0” disables serial com.
Drive power must be cycled before the changes will take effect.
*Range is dependent on P9-25, if P1-01 = 3. <0034>
Selects the baud rate for Terminals R+, R-, S+ and S-.
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
Note: Drive power must be cycled before the changes will take effect.
<0034>
0 ~ 20*
0 ~ 4
1F
3
Programming
Programming
64 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
H5-03
H5-04
H5-05
H5-06
H5-07
H5-08
H5-09
L1-01
L1-02
L1-03
L1-04
0427
0428
0429
042A
042B
042C
0435
0480
0481
0482
0483
Parameter Name
Digital Operator
Display
Description
Communication Parity
Selection
Serial Com Sel
Stopping Method after
Communication Error
Serial Flt Sel
Communication Error
Detection Selection
Serial Flt Dtct
Drive Transmit Wait Time
Transmit WaitTim
Selects the communication parity for Terminals R+, R-, S+ and S-.
0: No Parity
1: Even Parity
2: Odd Parity
Note: Drive power must be cycled before the changes will take effect.
<0034>
Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a communications fault.
1: Enabled - If communications are lost for more than the time specified in parameter H5-09, a communications fault will occur.
Sets the time from when the drive receives data to when the drive sends data.
Enables or disables “request to send” (RTS) control:
RTS Control Selection
RTS Control Sel
Communication Protocol
Selection
Com Protocol Sel
Communication Error
Detection Time
CE Detect Time
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
0: MEMOBUS/Modbus
1: N2 (Metasys)
2: FLN (APOGEE)
Determines how long communications must be lost before a fault is annunciated. Works in conjunction with parameters H5-05 and H5-04.
Motor Overload
Enables or disables the motor thermal overload protection.
Motor Overload Protection
Selection
MOL Flt Sel
Motor Overload Protection
Time
MOL Time Const
0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor
Determines how much time will elapse prior to a motor overload fault
(OL1), when motor amps exceed the value set in parameter E2-01 by
10 %. Actual (OL1) trip time will vary depending on severity of overload.
Operation selection when the motor temperature analog input
Setting
Range
0 ~ 2
0 ~ 3
0 ~ 1
5 ~ 65 ms
0 ~ 1
0 ~ 2
0.0 ~
10.0 sec
0 ~ 1
0.1 ~
20.0 min
Motor Overheat Alarm
Operation Selection
Mtr OH Alarm Sel
Motor Overheat Fault
Operation Selection
Mtr OH Fault Sel
(H3-09 = E) exceeds the OH3 alarm level (1.17 V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 level (2.34 V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
0 ~ 3
0 ~ 2
Factory
Setting
Menu
Location
0
3
1
5 ms
1
0
Programming
Programming
Programming
Programming
Programming
Programming
2.0 sec Programming
1 Programming
8.0 min Programming
3
1
Programming
Programming
L1-05 0484
Motor Temperature Input
Filter Time
Mtr Temp Filter
Delay Time applied to motor temperature analog input (H3-09 = E) for filtering purposes.
0.00 ~
10.00 sec
0.20 sec Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 65
Parameter
No.
Addr.
Hex
L2-01
L2-02
L2-03
L2-04
L2-05
L3-01
L3-02
L3-04
L3-05
0485
0486
0487
0488
0489
048F
0490
0492
0493
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Momentary Power Loss
Detection Selection
PwrL Selection
Power Loss Ridethru
Enables and disables the momentary power loss function.
0: Disabled - Drive trips on (Uv1) fault when power is lost.
1: PwrL Ride Thru t - Drive will restart if power returns within the time set in L2-02. If a second power loss occurs within one hour, the drive will trip on Uv1.*
2: CPU Power Active - Drive will restart if power returns prior to internal power supply shut down. If a second power loss occurs within one hour, the drive will remain in an undervoltage state for an additional 10-second delay after power returns. With each additional power loss occurrence, the time delay will increase. If the drive operates for one hour with no power loss conditions detected, the time delay is cleared.*
0 ~ 2 2 Programming
* In order for a restart to occur, the run command must be maintained throughout the ride thru period.
Momentary Power Loss
Ride-thru Time
PwrL Ridethru T
Momentary Power Loss
Minimum Base Block
Time
PwrL Baseblock T
Momentary Power Loss
Voltage Recovery Ramp
Time
PwrL V/f Ramp T
Undervoltage Detection
Level
PUV Det Level
Determines the power loss ride-thru time. This value is dependent on the capacity of the drive. Only effective when L2-01 = 1.
Used to allow the residual motor voltage to decay before the drive output turns back on. After a power loss, if L2-03 is greater than L2-02, operation resumes after the time set in L2-03.
The time it takes the output voltage to return to the preset V/f pattern after speed search (current detection mode) is complete.
0.0 ~
25.5 sec kVA
Dependent
Programming
0.1 ~ 5.0 sec kVA
Dependent
Programming
0.0 ~ 5.0 sec kVA
Dependent
Programming
Stall Prevention Selection
During Accel
StallP Accel Sel
Sets the drive's DC Bus undervoltage trip level. If this is set lower than the factory setting, additional AC input reactance or DC bus reactance may be necessary.
Stall Prevention
0: Disabled (Motor accelerates at active acceleration, C1-01 or C1-03. The motor may stall if load is too heavy or accel time is too short.)
1: General Purpose (When output current exceeds L3-02 level, acceleration stops. It starts to accelerate at current value recovery.)
2: Intelligent (The active acceleration rate, C1-01 or C1-02, is ignored.
Acceleration is completed in the shortest amount of time w/o exceeding the current value set in L3-02.
Voltage
Class
Dependent
0 ~ 2
Voltage
Class
Dependent
Programming
1 Programming
Stall Prevention Level
During Accel
StallP Accel Lvl
This function is enabled when L3-01 is “1” or “2”. Drive rated current is
100 %. Decrease the set value if stalling occurs at factory setting.
Stall Prevention Selection
During Decel
StallP Decel Sel
Stall Prevention Level
During Decel
StallP Run Sel
0: Disabled (The drive decelerates at the active deceleration rate,
C1-02 or C1-04. If the load is too large or the deceleration time is too short, an OV fault may occur.)
1: General Purpose (The drive decelerates at the active deceleration rate,
C1-02 or C1-04, but if the main circuit DC bus voltage reaches the stall prevention level the output frequency will clamp. Deceleration will continue once the DC bus level drops below the stall prevention level.)
2: Intelligent (The active deceleration rate is ignored and the drive decelerates as fast as possible w/o hitting OV fault level.)
0: Disabled (drive runs a set frequency.) A heavy load may cause the drive to trip on an OC fault.
1: Decel Time 1 (In order to avoid stalling during heavy loading, the drive will start to decelerate at Decel time 1 (C1-02) if the output current exceeds the level set by L3-06. Once the current level drops below the L3-06 level the drive will accelerate back to its set frequency at the active acceleration rate.)
2: Decel Time 2 (Same as setting 1 except the drive decelerates at Decel
Time 2 (C1-04).) For 6 Hz or less frequency, stall prevention function during run is disabled regardless of L3-05 set.
0 ~ 200 %
0 ~ 3
0 ~ 2
120 % Programming
1
1
Programming
Programming
L3-06 0494
Stall Prevention Level
During Running
StallP Run Level
This function is enabled when L3-05 is “1” or “2”.
Drive rated current is set as 100 %.
Normally, changing the setting is not required.
Decrease the set value if stalling occurs at factory setting.
30 ~ 200 % 120 % Programming
66 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
L4-01
L4-02
L4-05
L4-06
L5-01
L5-02
0499
049A
049D
04C2
049E
049F
Parameter Name
Digital Operator
Display
Description
Auto Restart Operation
Selection
Restart Sel
Reference Detection
Speed Agreement
Detection Level
Spd Agree Level
Speed Agreement
Detection Width
Spd Agree Width
Number of Auto Restart
Attempts
Num of Restarts
L4-01 and L4-02 are used in conjunction with the multi-function outputs,
(H2-01and H2-02) as a setpoint and hysteresis for a contact closure.
Frequency Reference Loss
Detection Selection
Ref Loss Sel
Frequency Reference
Level at Loss Frequency
Fref at Freq loss
Determines how the drive will react when the frequency reference is lost.
0: Stop (Disabled) - Drive will not run at the frequency reference.
1: Enabled @ % of PrevRef - Drive will run at a percentage (L4-06) of the frequency reference level at the time frequency reference was lost.
Note: Only available in the Hand Mode (P5-01 = 0).
If Frequency Reference loss function is enabled (L4-05 = 1) and Frequency
Reference is lost, then the drive will run at reduced frequency reference determined by L4-06. New Fref=Fref at time of loss x L4-06.
Note: Only available in the Hand Mode (P5-01 = 0)
Fault Restart
Determines the number of times the drive will perform an automatic restart.
Determines if the fault contact activates during an automatic restart attempt.
0: No Flt Relay - fault contact will not activate during an automatic restart.
1: Flt Relay Active - fault contact will activate during an automatic restart.
Setting
Range
0.0 ~
200.0 Hz
0.0 ~
20.0 Hz
0 ~ 1
0 ~ 1
0 ~ 10
0 ~ 1
Factory
Setting
Menu
Location
0.0 Hz Programming
2.0 Hz Programming
0
0
5
0
Programming
Programming
Programming
Programming
L5-03 04A0
Maximum Restart Time
After Fault
Max Restart Time
If the restart fails (or is not attempted due to a continuing fault condition, e.g. an OV fault) the drive waits the Maximum Restart Time After Fault
(L5-03) before attempting another restart. This parameter is not applicable to Loss of Prime Fault.
10.0 ~
3600.0 sec
<0032>
20.0 sec Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 67
Parameter
No.
Addr.
Hex
L6-01
L6-02
L6-03
L8-01
L8-02
L8-03
L8-05
<0033>
L8-06
L8-07
<0033>
L8-09
L8-10
L8-11
<0032>
L8-12
04A1
04A2
04A3
04AD
04AE
04AF
04B1
04B2
04B3
04B5
04B6
04B7
04B8
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Torque Detection
Selection 1
Load Detection
Torque Detection Level 1
Load Det Lvl
Torque Detection Time 1
Loss Det Time
Torque Detection
Determines the drive's response to an overtorque/undertorque condition.
Overtorque and Undertorque are determined by the settings in parameters
L6-02 and L6-03.
0: Disabled
1: OL@SpdAgree - Alm (Overtorque Detection only active during Speed
Agree and Operation continues after detection)
2: OL At RUN - Alm (Overtorque Detection is always active and operation continues after detection)
3: OL@SpdAgree - Flt (Overtorque Detection only active during Speed
Agree and drive output will shut down on an OL3 fault.)
4: OL At RUN - Flt (Overtorque Detection is always active and drive output will shut down on an OL3 fault.)
5: LL@SpdAgree - Alm (Undertorque Detection is only active during
Speed Agree and operation continues after detection.)
6: LL at RUN - Alm (Undertorque Detection is always active and operation continues after detection.)
7: LL @ SpdAgree - Flt (Undertorque Detection only active during Speed
Agree and drive output will shut down on an OL3 fault.)
8: LL At RUN - Flt (Undertorque Detection is always active and drive output will shut down on an OL3 fault.)
Sets the overtorque/undertorque detection level as a percentage of drive rated current.
Sets the length of time an overtorque/undertorque condition must exist before being recognized by the drive. OL3 is then displayed.
Hardware Protection
0 ~ 8
0 ~ 300 %
0.0 ~
10.0 sec
0
15 %
Programming
Programming
10.0 sec Programming
Internal Dynamic Braking
Resistor Protection
Selection
DB Resistor Prot
Overheat Pre-Alarm Level
OH Pre-Alarm Lvl
Overheat Pre-Alarm
Operation Selection
OH Pre-Alarm Sel
Input Phase Loss
Protection Selection
Ph Loss In Sel
0: Not Provided
1: Provided
When the cooling fin temperature exceeds the value set in this parameter, an overheat pre-alarm (OH) will occur.
Drive Operation upon OH Pre Alarm Detection.
0: Ramp to Stop (Decel Time C1-02).
1: Coast to Stop
2: Fast-Stop (Decel Time = C1-09).
3: Alarm Only
*0 to 2 is recognized as fault detection, and 3 is recognized as alarm. (For the fault detection, the fault contact operates.)
4: OH Alarm & Reduce (Continue operation and reduce output frequency by L8-19)
Selects the detection of input current phase loss, power supply voltage imbalance, or main circuit electrostatic capacitor deterioration.
0: Disabled
1: Enabled
Input Phase Loss
Detection Level
Ph Loss In Lvl
Monitors the DC Bus current ripple and activates when one of the input phases is lost (PF).
Output Phase Loss
Protection Selection
Ph Loss Out Sel
Output Ground Fault
Detection Selection
Ground Fault Sel
Heatsink Cooling Fan
Operation Selection
Fan On/Off Sel
Selects the detection of output current open-phase.
When applied motor capacity is too small for drive capacity, output phase loss may be detected inadvertently. In this case, set to 0.
0: Disabled
1: Enabled
Enables and disables drive output ground fault detection.
0: Disabled
1: Enabled
Controls the Heatsink Cooling Fan Operation.
0: Fan On-Run Mode (Fan will operate only when drive is running and for
L8-11 seconds after RUN is removed).
1: Fan Always On (Cooling fan operates whenever drive is powered up.)
Heatsink Cooling Fan
Operation Delay Time
Fan Delay Time
Ambient Temperature
Setting
Ambient Temp
When L8-10=0 this parameter sets a delay time for Cooling Fan deenergization after the run command is removed or baseblock enabled.
When the drive is installed in an ambient temperature exceeding its rating, drive overload (OL2) protection level is reduced.
0 ~ 1
50 ~
130 °C
0 ~ 4
0 ~ 1
0.0 ~ 25.0
0 ~ 1
0 ~ 1
0 ~ 1
0 ~ 300 sec
45 ~ 60 °C
0
95 °C
4
1 kVA
Dependent
1
1
0
300 sec
45 °C
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
68 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
L8-15
L8-18
L8-19 04BF n1-01 n1-02 n3-01 n3-02 n3-03 n3-04 o1-01
o1-02
04BB
04BE
0580
0581
0588
0589
058A
058B
0500
0501
Parameter Name
Digital Operator
Display
Description
Setting
Range
OL2 Characteristic
Selection at Low Speeds
OL2 Sel @ L-Spd
Soft CLA Selection
Soft CLA Sel
This parameter assists in protecting the output transistor junctions from overheating when output current is high and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)
Enables and disables current limit “A”.
0: Disabled
1: Enabled
0 ~ 1
0 ~ 1
OH Frequency Reference
Reduction Level
Fref During OH
Sets the amount of frequency reference reduction when an Overheat Prealarm (OH) is detected.
0.0 ~
100.0 %
Hunting Prevention
Selection
Hunt Prev Select
Hunting Prevention Gain
Setting
Hunt Prev Gain
High-Slip Braking
Deceleration Frequency
Width
HSB Decel Width
High-Slip Braking Current
Limit
HSB Current Ref
High-Slip Braking Dwell
Time at Stop
HSB DwelTim@ Stp
High-Slip Braking
Overload Time
HSB OL Time
User Monitor Selection
User Monitor Sel
User Monitor Selection
After Power-Up
Power-On Monitor
Hunting Prevention
0: Disabled (Hunting prevention function disabled.)
1: Enabled (Hunting prevention function enabled.)
If the motor vibrates while lightly loaded, hunting prevention may reduce the vibration. There is a loss of responsiveness if hunting prevention is enabled.
Gain setting for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases. If the motor stalls while n1-01 = 1 decrease the gain by 0.1 until the stalling ceases.
High-Slip Braking
Sets how aggressively the drive decreases the output frequency as it stops the motor. If overvoltage (OV) faults occur during HSB, this parameter may need to be increased.
Note: Function Deactivated
Sets the maximum current to be drawn during a HSB stop. Higher n3-02 settings will shorten motor stopping times but cause increased motor current and therefore, increased motor heating.
Note: Function Deactivated
Sets the amount of time the drive will dwell at E1-09 (Minimum
Frequency). If this time is set too low, the machine inertia can cause the motor to rotate slightly after the HSB stop is complete and drive output is shut off.
Note: Function Deactivated
Sets the time required for a HSB Overload Fault to occur when the drive output frequency does not change for some reason during a HSB stop.
Normally this does not need to be adjusted.
Note: Function Deactivated
Monitor Select
Selects which monitor will be displayed upon power-up when o1-02 = 4.
Selects which monitor will be displayed upon power-up.
1: Auto: Set-point
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)
0 ~ 1
0.00 ~ 2.50
1.0 ~
20.0 %
100.0 ~
200.0 %
0.00 ~
10.0 sec
30.0 ~
1200.0 sec
6 ~ 94
1 ~ 4
Factory
Setting
1
1
Menu
Location
20.0 % Programming
1
1.00
5 %
Programming
Programming
Programming
150 % Programming
1.0 sec Programming
40 sec Programming
6
1
Programming
Programming
Programming
Programming o1-05 0504
LCD Brightness
Adjustment
LCD Contrast
Set Value
5
3
1
Description
LCD display becomes dark
Standard setting
LCD display becomes light
0 ~ 5 3 Programming o1-06 0517
User Monitor Selection
Mode
Monitor Mode Sel
Selects the “U1” monitors displayed on the 4th and 5th lines of the digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1 monitors.)
1: 3 Mon Selectable (Displays U1 monitors set by o1-07 and o1-08.)
0 ~ 1
Denotes that parameter can be changed when the drive is running.
1** Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 69
Parameter
No.
Addr.
Hex o1-07 o1-08 o2-01 o2-02 0506 o2-03 o2-04 o2-05 o2-06 o2-07 o2-08 o2-10 o2-12 o2-14 o3-01 o3-02
0518
0519
0505
0507
0508
0509
050A
050B
050C
050E
0510
0512
0515
0516
Parameter Name
Digital Operator
Display
Second Line User Monitor
Selection
2nd Monitor Sel
Third Line User Monitor
Selection
3rd Monitor Sel
Description
Sets the “U1” monitor always displayed on the 4th line of the digital operator display. Effective only when o1-06 = 1.
Sets the “U1” monitor always displayed on the 5th line of the digital operator display. Effective only when o1-06 = 1.
Local/Remote Key
Function Selection
Local/Remote Key
OFF Key Function During
Auto Run
Oper OFF Key
User Parameter Default
Value
User Defaults
Drive/kVA Selection
Inverter Model #
Frequency Reference
Setting
Method Selection
Operator M.O.P.
Key Selections
Has no function when HOA operator is connected.
0: Disabled
1: Enabled
Determines if the off key on the digital operator will stop the drive when drive is operating from external terminals or serial communications.
0: Disabled
1: Enabled
Allows storing of current parameter values as a User Initialization
Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user initialization. A1-
03 now allows selecting <1110> for user initialization.
2: Clear All (Clears the currently saved user initialization. A1-03 no longer allows selecting <1110>.
Sets the kVA of the drive. Enter the number based on drive model #. Use the portion of the CIMR-P7 -107 Model Number.
Determines if the Data/Enter key must be used to input a frequency reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a frequency reference.
1: Enabled: -Data/Enter key is not required. The frequency reference is adjusted by the up and down arrow keys on the digital operator without having to press the data/enter key.
Determines if the drive will stop when the digital operator is removed.
0: Disabled - The drive will not stop when the digital operator is removed.
1: Enabled - The drive will fault (OPR) and coast to stop when the operator is removed.
Operation Selection when
Digital Operator is
Disconnected
Oper Detection
Cumulative Operation
Time Setting
Elapsed Time Set
Cumulative Operation
Time Selection
Elapsed Time Run
Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Se t
Fault Trace/Fault History
Clear Function
FLT Trace Ini t kWh User Monitor (U1-
29) Initialization kWh MonitorClear
Copy Function Selection
Copy Function Sel
Sets the initial value of the elapsed operation timer.
Sets how time is accumulated for the elapsed timer (o2-07).
0: Power-On Time (Time accumulates whenever drive is powered).
1: Running Time (Time accumulates only when drive is running)
Sets the initial value of the heatsink fan operation time.
Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled (no effect).
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.
Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to zero.
Copy Function
This parameter controls the copying of parameters to and from the digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from the drive to the digital operator.
2: OP -> INV WRITE - All parameters are copied from the digital operator into the drive.
3: OP <--> INV VERIFY - Parameter settings in the drive are compared to those in the digital operator.
Note: When using the copy function, the drive model number and software number (U1-14) must match or an error will occur.
Setting
Range
1 ~ 94
1 ~ 94
0 ~ 1
0 ~ 1
0 ~ 2
0 ~ FF
0 ~ 1
0 ~ 1
0 ~
65535 hr
0 ~ 1
0 ~
65535 hr
0 ~ 1
0 ~ 1
0 ~ 3
Factory
Setting
2
91
1
1
0
Menu
Location
Programming
Programming
Programming
Programming
Programming kVA
Dependent
Programming
0
1
0 hr
1
0 hr
0
0
0
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Read Allowed Selection
Read Allowable
Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are allowed.
1: Enabled - Copying allowed
0 ~ 1 0 Programming
70 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Pump Basic
P1-01
P1-02
P1-03
P1-04
0600
0601
0602
0603
Pump Mode
Pump Mode
System Units
System Units
Feedback Device Scaling
Fb Dev Scaling
Start Level
Start Level
Select type of control operation.
0: Drive Only (Simplex)
1: Drive + 1 Pump
2: Drive + 2 Pumps
3: Memobus network <0034>
0: WC:InchOfWater
1: psi:lb/SqrInch
2: GPM:Gallons/min
3: F:DegFarenheit
4: CFM:Cubic ft/min
5: CMH:Cubic m/hr
6: LPH:Liters/hr
7: LPS:Liters/s
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Ft: Feet <0032>
12:%: Percent
13: rpm: Revs/min (Note 1) <0034>
14: Hz: Hertz (Note 1) <0034>
Scaling of feedback device in user units (P1-02=1, e.g. 150 psi).
Digits 1 through 4 set the maximum feedback number. Digit 5 determines the number of decimal places.
Digit 5 = 0: Number format is XXXX
Digit 5 = 1: Number format is XXX.X
Digit 5 = 2: Number format is XX.XX
Digit 5 = 3: Number format is X.XXX
Examples:
01000 = 1000
13000 = 300.0
25000 = 50.00
32000 = 2.000
Drive starts when the feedback level drops below the start level for a time specified in P1-05. This level also specifies the wake up level when the drive is in Sleep Mode.
If set to a negative value, the feedback level must drop by this amount below the setpoint. <0034>
Note: When PID operates in the reverse mode, the feedback value has to rise above the start level for the time programmed in P1-05 for the system to start. A value of 0 disables this function.
If P1-01 = 3, the function is active only on the first drive in the network.
<0034>
0 ~ 3
0 ~ 14
1 ~ 36000
(system units
P1-02)
- 999.9 ~
999.9
(system units
P1-02)
0
1
00145
0.0 (system units
P1-02)
Programming
Programming
Programming
Pump Quick
Setup
P1-05
P1-06
0604
0605
Start Level Delay Time
S-Lvl Delay Time
Minimum Pump
Frequency
Min. Pump Freq
Drive starts when the feedback level drops below the start level for a time specified in P1-05.
Minimum drive frequency when operated in the auto mode. Programmed value will limit minimum PID output. Minimum value must be programmed to a value smaller than P3-09 and P3-10 when drive is operating in the multiplex mode (P1-01).
0 ~ 3600 sec
0.0 ~
120.0 Hz
1 sec
40.0 Hz
Programming
Pump Quick
Setup
P1-07
P1-08
0606
0607
Low Feedback Level
Low FB Level
Low Feedback Level Fault
Delay Time
Low Lvl Flt Tim e
The drive will display a “Low Feedback (LFB)” alarm when the feedback level falls below the programmed level. The alarm will turn off when the feedback level rises above the programmed Low Feedback Level plus the
Hysteresis Level (P1-13). A value of 0 disables this function. This function is only active during running while operating in the auto mode.
The drive will display a “Low Feedback/Water (LFB/LW)” alarm when the feedback level falls below the programmed level for a time specified in P1-
08. The drive will coast to a stop when a fault occurs. A value of 0 disables this function. This function is only active during running while operating in the auto mode.
If P1-01 = 3, the function will stop all drives running on the network when the system fault occurs. <0034>
0.0 ~
6000.0
(system units
P1-02)
0 ~ 3600 sec
0.0 (system units
P1-02)
5 sec
Programming
Programming
Denotes that parameter can be changed when the drive is running.
Note 1: When P1-02 = 3, parameter P1-03 must be set to (120 x E1-04/E2-04) for proper display. When P1-02 = 14, parameter P1-03 must be set to the same value as E1-
04 for proper display.
YASKAWA TM.iQp.10 Technical Manual Supplement 71
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
P1-09
P1-10
P1-11
<0032>
P1-12
<0032>
0608
0609
0106
0107
High Feedback Level
High FB Level
High Feedback Level Fault
Delay Time
Hgh Lvl Flt Time
Maximum SetPoint
Difference
Max Set-point Diff
Not Maintaining Set-point
Time
Not Maint SP Tm
The drive will display a “High Feedback Level (HFB)” alarm when the feedback level rises above the programmed level. The alarm will turn off when the feedback level falls below the programmed High Feedback Level minus the Hysteresis Level (P1-13). This function is active during running in the hand mode, auto mode, pre-charge and thrust-bearing mode.
If P1-01 = 3, parameter P9-18 uses this value to calculate the quick destage feedback level. <0034>
The drive will initiate a “High Feedback Fault (HFB)” when the feedback level rises above the programmed level for a time specified in P1-10. The drive will coast to a stop when a fault occurs. This function is active during running in all operation modes.
If P1-01 = 3, the function will stop all drives running on the network when the system fault occurs. <0034>
When the drive is running and the difference between the setpoint and the feedback exceeds the level in P1-11 for the time specified in P1-12, the drive will trip on a “Not Maintaining Set-point (NMS)”. The drive will coast to a stop when a fault occurs. A value of 0 disables this function. This function is only active during running while operating in auto mode.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives running on the network when the system fault occurs. <0034>
Delay time before a Not Maintaining Set-point fault occurs. Pump protection criteria specified in P1-11 must be met for the drive to fault. The drive will coast to a stop when a fault occurs. A value of 0 disables Not
Maintaining Set-point fault.
0.0 ~
6000.0
(system units
P1-02)
0 ~ 3600 sec
0.0 ~
6000.0
(system units
P1-02)
0 ~ 3600 sec
155.0
(system units
P1-02)
2 sec
Programming
Programming
0.0 (system units
P1-02)
Programming
60 sec Programming
P1-13
0108
Hysteresis Level
Hysteresis Level
Hysteresis Level used for low and high feedback alarm detection. See function P1-07 and P1-09.
0.0 ~ 100.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
P1-14
P1-15
0109
010A
Prime Loss Level
Prime Loss Level
Low/Hi Water Digital
Input Configuration
Water DI Config
<0034>
Used to detect loss of prime in the pump. If output current drops below this level for the time specified in P1-12 and the output frequency is at fmax, a
“Loss Of Prime” fault occurs. The drive will coast to a stop when a fault occurs.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives running on the network when the system fault occurs. <0034>
Sets the type of control operation
0: Low N.O. - Hi N.O. (Low Water Normally Open, High Water Normally
Open) <0034>
1: Low N.C. - Hi N.O. (Low Water Normally Closed, High Water
Normally Open) <0034>
2: Low N.O. - Hi N.C. (Low Water Normally Open, High Water Normally
Closed) <0034>
3: Low N.C. - Hi N.C.(Low Water Normally Closed, High Water Normally
Closed) <0034>
To use the low water function one of the digital inputs (H1 =85) must be programmed. The low water input can be used for a low water condition or in combination with the pre-charge function to indicate the reservoir is filled. The low water input fault is only active during running while operating in auto mode.
P1-16
<0034>
87F
Loss of Prime Time
Prime Loss Time
Delay time before a Loss of Prime fault occurs. Pump protection criteria specified P1-14 must be met for the drive to fault. On fault the drive will coast to a stop.
Denotes that parameter can be changed when the drive is running.
Pump Protection
P2-01 060A
Sleep Level Type
Sleep Lvl Type
Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
3: Output Speed (rpm) <0034>
4: Low Flow (Terminal A1 - Flow meter required) <0034>
0.0 ~
1000.0 A
0 ~ 3
1 ~ 600 sec 20 sec Programming
0 ~ 4
0.0 A Programming
0
0
Programming
Programming
Note: Feedback depends on PID direction operation.
Displays a “Sleep” Alarm when active.
72 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
P2-02
060B
Sleep Level
Sleep Level
Sleep activates when selected level (P2-01) reaches programmed sleep level for time specified in P2-03. The level type is determined by
P2-01. A value of 0 disables this function. This function is only active during running while operating in auto mode.
If P1-01 = 3, the function is active when there is only one drive running on the network. <0034>
Display Units for Sleep Level P2-02 when P2-01 is programmed for the following:
P2-01=0: Display based on “Hz”
P2-01=1: Display based on “A”
P2-01=2: Display based on P1-02 Selection
P2-01=3: Display based on “rpm” <0034>
P2-01=4: Display based on P6-02 Selection <0034>
0.0 ~
6000.0
0.0
Programming
P2-03
P2-04
P2-05
P2-06
P2-07
P2-08
060C
060D
060E
060F
0610
0611
Sleep Delay Time
Sleep Delay Time
Delta Sleep Feedback
Drop Level
D Fb Drop Level
Feedback detection drop time.
FB Drop DetTime
Sleep Mode: Cycling
Protection
Cycle Protection
Sleep Mode: Maximum
Cycling Protection Time
Max. Cycle Time
Over Cycling Mode
Over Cycle Mode
Note: When P2-01 is set for a value of 2, display units will be dependent on P1-02 setting. If P2-02 = 0, pump will sleep at minimum speed.
Delay time before drive enters sleep mode when criteria is met as defined by parameter P2-02.
When the drive enters sleep mode, the software monitors the feedback to detect a flow-no flow condition. If the PID Error (setpoint minus feedback) exceeds the programmed level P2-04 within the programmed time (P2-05) and the output frequency is greater than the minimum frequency (P1-06), the sleep operation deactivates and the drive returns to normal operation. A value of 0 disables this function.
Defines the time window in which the software monitors the feedback to detect a flow-no flow condition. Works in conjunction with parameter P2-
04.
Maximum number of cycles allowed within the time specified in P2-07 before the drive initiates a “Pump Cycle Fault (PCF)”. One Cycle is defined when the drive transfers from normal operation in auto mode to sleep mode. A value of 0 disables this function.
If P1-01 = 3, the function is active when there is only one drive running on the network. <0034>
Maximum time allowed between cycles. When no cycling occurs within the programmed time, the drive will reset the internal cycle register. Works in conjunction with P2-06.
Sets the Over Cycle Mode:
0: Disabled
1: Alarm
2: Pump Over Cycle Fault (POC)
3: Auto Compensation
0 ~ 3600 sec
0.0 ~
6000.0
(system units
P1-02)
0 ~ 3600 sec
0 ~ 10
0 ~ 3600 sec
0 ~ 3
P2-09
P2-10
0612
0613
Set-point Compensation
Set-point Comp
Maximum Set-point
Compensation
Max. SP Comp
Allows for the software to automatically compensate the setpoint in case of excessive cycling.
Maximum allowable setpoint compensation for the over-cycling function.
0.0 ~
6000.0
(system units
P1-02)
0.0 ~
6000.0
(system units
P1-02)
P2-11
P2-12
P2-13
010B
010C
010D
No-Flow Activation Level
NF Act. Level
No-Flow Detection
Bandwidth
NF Det.Bandwidth
No-Flow Detection Time
NF Detect Time
When the motor rpm falls below the programmed level in P2-12, the noflow detection will activate. A value of 0 disables this function.
If P1-01 = 3, the function is active on the lead drive. <0034>
Sets the motor rpm fluctuation bandwidth. No-flow activates when the motor rpm remains within the programmed bandwidth in P2-12 for a time specified in parameter P2-13.
No-flow activates when the motor rpm remains within the programmed bandwidth (P2-12) for a time specified in parameter
P2-13.
P2-14 010E
No-Flow Stabilization
Time
NF StabilizeTime
Time delay when setpoint returns to the original setting after being changed for no-flow detection.
Denotes that parameter can be changed when the drive is running.
0 ~
24000 rpm
0 ~
1000 rpm
0.0 ~
1000.0 sec
0.0 ~
1000.0 sec
5 sec Programming
0.0 (system units
P1-02)
Programming
10 sec
0
300 sec
0
Programming
Programming
Programming
Programming
0.0 (system units
P1-02)
Programming
0.0 (system units
P1-02)
Pump Quick
Setup
0 rpm
15 rpm
5.0 sec
5.0 sec
Programming
Programming
Programming
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 73
Parameter
No.
Addr.
Hex
P2-15
P2-16
P2-17
P2-18
P2-19
P2-20
010F
011F
0120
0121
0122
0123
Parameter Name
Digital Operator
Level
Display
No-Flow Delta Feedback
NF FB Level
No-Flow Set-point
Compensation
NF SP Comp
No-Flow Feedback Delay
Time
NF Fdbk Delay Time
Description
Setting
Range
Factory
Setting
Menu
Location
No-flow feedback (PID-Error: setpoint minus feedback) level used to detect no-flow condition based on feedback value.
Delta feedback (setpoint minus feedback) has to exceed the programmed level for the time programmed in P2-17 to detect a no-flow condition.
0.0 ~
6000.0
(system units
P1-02)
Set-point compensation used in the no-flow detection function.
0.0 ~
6000.0
(system units
P1-02)
Delay timer used in combination with the no-flow feedback (PID-Error: setpoint minus feedback) level (P2-15) used to detect the no-flow condition based on the feedback value.
Delta feedback (Set-point minus feedback) has to exceed the programmed level (P2-15) for the time programmed to detect a no-flow condition.
0.0 ~
1000.0 sec
1.0 (system units
P1-02)
Programming
1.5 (system units
P1-02)
Programming
2.0 sec Programming
No-Flow Motor RPM
Sample Time
NF RPM Sample Tm
No-Flow Feedback
Detection Direction
NF Fdbk Det Direct
No-flow detection motor rpm sample rate.
Direction of feedback detection upon return of no-flow detection.
0: Outside Bandwidth (P2-15)
1: Inside Bandwidth (P2-15)
When P2-01 Sleep Level Type is set for 0 (Output Frequency) or 3 (Output
Speed), the sleep function becomes active when the output frequency is greater or equal to the level in P2-20. When programmed to 0, the sleep function will become active above the P2-02 Sleep.
0.1 ~
1000.0 sec
0 ~ 1
2.0 sec
0
Programming
Programming
Alternative Sleep Activate
Level
SLP Act Level
Level.Display Units for Sleep Activate Level P2-20 when P2-01 is programmed for the following: <0034>
P2-01=0: Display based on “Hz”
P2-01=1: Display based on “Hz”
P2-01=2: Display based on “Hz”
P2-01=3: Display based on “rpm”
P2-01=4: Display based on “Hz”
0.0 ~
6000.0
0.0
Programming
A value of 0 disables this function.
P2-21
<0034>
820
Sleep Boost Level
Sleep Boost Lvl
Sets the amount of boost applied to the setpoint just before going to sleep.
A setting of 0.0 disables the sleep boost function. (Internally limited to 25
% of P1-03.)
0.0 ~
6000.0
(system units
P1-02)
P2-22
<0034>
821
Sleep Boost Maximum
Time
Sleep Boost Time
Sets the amount of time the system (feedback) has to reach the “boosted” setpoint. If more than this time elapses, the drive will go to sleep
P2-23
<0034>
822
Anti-No-Flow Bandwidth
ANF Bandwidth
Sets the amount of PI “Error” bandwidth used to detect the no-flow condition.
Operation can become less stable if this value is set too high. A setting of
0.00 % disables this feature.
P2-24
<0034>
P2-25
<0034>
823
824
Anti-No-Flow Detection
Time
ANF Det Time
Anti-No-Flow Release
Level
ANF Release Lvl
Sets the time delay after no-flow is detected before the drive starts its increased deceleration rate.
Once the Anti-No-Flow activates (after the P2-24 time), the feedback must drop this amount below the setpoint for the Anti-No-Flow to disengage and return to normal PI operation.
Denotes that parameter can be changed when the drive is running.
Pump Multiplex
Selects lead-lag detection operation.
1.0 ~
160.0 sec
0.00 ~
2.00 %
1.0 ~
60.0 sec
0.0 ~
100.0 psi
P3-01 0614
Lead-Lag Control
Lead-Lag Control
0: Output Frequency (Output Frequency). 0: Uses P3-02, P3-04, P3-06,
P3-09, P3-10.
1: Feedback (Feedback Level). 1: Uses P3-03, P3-04, P3-05, P3-06.
2: Feedback + Fout (Feedback Level and Output Frequency). 2: Uses P3-
02, P3-03, P3-05, P3-06, P3-07, P3-08, P3-10.
Works in conjunction with parameters P2-11 to P2-19.
0 ~ 2
0.0
5.0 sec Programming
0.40 % Programming
10.0 sec Programming
3.0 psi Programming
0
Programming
Programming
74 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
P3-02
P3-03
P3-04
Addr.
Hex
0615
0616
0617
Parameter Name
Digital Operator
Display
Drive Multi/Maximum
Level
Max-Multi Level
Add Pump Delta Level
Add Pump D-Lvl
Add Pump Delay Time
Add Pump Dly Tm
Description
Setting
Range
Sets the maximum level used for multiplex pumping operation. Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01 = 0: When the output frequency rises above the level programmed in P3-02 for a time specified in P3-04, the next available pump will be added to the system by means of a multi-function digital output closure
(H2 = 40, 41).
P3-01 = 1: Not Used.
0.0 ~
120.00 Hz
P3-01 = 2: When the output frequency rises above level programmed in
P3-02 and the delta feedback (setpoint minus feedback) has exceeded the level programmed in P3-03 for a time specified in P3-04, the next available pump will be added to the system by means of a multi-function digital output closure (H2 = 40, 41).
Sets the level used for multiplex pumping operation. The parameter is active when P3-01 =1 or P3-01 = 2 is selected.
Factory
Setting
59.0 Hz
Menu
Location
Programming
P3-01 = 0: Not Used
P3-01 = 1: When the delta feedback (setpoint minus feedback) has exceeded the level programmed in P3-03 for a time specified in P3-04, the next available pump will be added to the system by means of a multifunction digital output closure. (H2 = 40, 41).
0.0 ~
6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
P3-01 = 2: When the output frequency rises above level programmed in
P3-02 and the delta feedback (Set-point minus feedback) has exceeded the level programmed in P3-03 for a time specified in P3-04, the next available pump will be added to the system by means of a multi-function digital output closure. (H2 = 40, 41).
Note: Do not program this level too close to the system setpoint or excessive cycling of the pump system may occur.
Sets the delay time before a pump is added to the system. Works in conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.
Sets the level used for multiplex pumping operation. Parameter is active when P3-01 = 1 or P3-01 = 2 is selected.
P3-01 = 0: Not Used
0 ~ 3600 sec
2 sec Programming
P3-05
0618
Shutdown Pump Delta
Level
Shdn Pump D-Lvl
P3-01 =1 : When the delta feedback (feedback minus setpoint) has exceeded the level programmed in P3-05 for a time specified in
P3-06,the last pump that was brought online will be shutdown by means of a multi-function digital output opening. (H2 = 40, 41).
P3-01 = 2: When the output frequency drops below level programmed in
P3-09 or P3-10 (depends on last pump running) and the delta feedback
(feedback minus setpoint) has exceeded the level programmed in P3-05 for a time specified in P3-06, the last pump that was brought online will be shutdown by means of a multi-function digital output opening. (H2 =
40, 41).
0.0 ~
6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
Note: Do not program this level too close to the system setpoint or excessive cycling of the pump system may occur.
P3-06
0619
Shutdown Pump Delay
Time
Shdn Pump Dly Tm
Sets the delay time before one of the additional across the line pumps is shutdown.Works in conjunction with parameters P3-02 and P3-03.
P3-07
P3-08
061A
061B
Multi Pump Set-point
Increase
MP Set-point Incr
Multi Pump Set-point
Decrease
MP Set-point Decr
Sets the amount the drive’s setpoint will decrease for each time a new pump is brought offline.
Pump 1: Set-point
Pump 1+2: Set-point + P3-07
Pump 1+2+3: Set-point + (2 x P3-07)
Sets the amount the drive’s setpoint will increase for each time a new pump is brought online.
Pump 1: Set-point
Pump 1+2: Set-point - P3-08
Pump 1+2+3: Set-point - (2 x P3-08)
Denotes that parameter can be changed when the drive is running.
0 ~ 3600 sec
0.0 ~
6000.0
(system units
P1-02)
0.0 ~
6000.0
(system units
P1-02)
5 sec Programming
0.0 (system units
P1-02)
Programming
0.0 (system units
P1-02)
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 75
Parameter
No.
Addr.
Hex
P3-09
P3-10
P3-11
P3-12
061C
061D
0110
0111
Parameter Name
Digital Operator
Display
Pump 2 Frequency
Shutdown Level
P2 Freq Shd Lvl
Pump 3 Frequency
Shutdown Level
P3 Freq Shd Lvl
Multiplex Stabilization
Time
M-Stabilize Time
Description
Setting
Range
Sets the level used for multiplex pumping operation. Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-0 1= 0: When the output frequency falls below the level programmed in
P3-09 for a time specified in P3-06 and a total of 2 pumps are running, the last pump (Pump 2) that was brought online will be shutdown by means of a multi-function digital output opening (H2 = 40, 41).
P3-01 = 1: Not Used
0.0 ~
120.0 Hz
P3-01 = 2: When the output frequency falls below the level programmed in
P3-09 and a total of 2 pumps are running and the delta feedback (feedback minus setpoint) has exceeded the level programmed in P3-05 for a time specified in P3-06, the last pump (Pump 2) that was brought online will be shutdown by means of a multi-function digital output opening (H2 =
40, 41).
Sets the level used for multiplex pumping operation. Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01 = 0: When the output frequency falls below the level programmed in
P3-10 for a time specified in P3-06 and a total of 3 pumps are running, the last pump (Pump 3) that was brought online will be shutdown by means of a multi-function digital output opening (H2 = 40, 41).
P3-01 = 1: Not Used
0.0 ~
120.0 Hz
P3-01 = 2: When the output frequency falls below the level programmed in
P3-10 and a total of 3pumps are running and the delta feedback (feedback minus setpoint) has exceeded the level programmed in P3-05 for a time specified in P3-06, the last pump (Pump 3) that was brought online will be shutdown by means of a multi-function digital output opening (H2 =
40, 41).
Factory
Setting
40.0 Hz
40.0 Hz
Menu
Location
Programming
Programming
Sets the time used to stabilize system when a pump is added (brought online) or shutdown during multiplex operation. When a pump is added, the stabilize timer temporarily disables the lead/lag functionality for the programmed time to prevent pump cycling.
Note: This function only active in the multiplex mode when P1-01 is greater than 0.
During the stabilization time, the pump protection and lead-lag control is suspended.
0 ~ 3600 sec
2 sec Programming
Delta Set-point Feedback
Acc/Dec Changeover
SP ACC/DEC Hyst.
Sets the level when the acceleration and deceleration times change over to the values programmed in C1-05 and C1-06 respectively. This function will activate when the difference between the delta setpoint and feedback are within the level programmed in P3-12. This function is used to improve the pump regulation.A value of 0 disables this function.
0.0 ~
6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
P3-13
0112
Friction Compensation start Frequency
Fric. Comp Lvl
Sets the level when the setpoint will be adjusted to compensate for the friction losses. This function will activate when the output frequency rises above the level programmed in P3-13. The maximum compensation at maximum output frequency (E1-04) is specified by maximum setpoint frequency (P2-10).
0.0 ~
120.0 Hz
Note: This function is only active in simplex mode when P1-01 = 0.
0.0 Hz Programming
P3-14
0113
Maximum Friction
Increase at Maximum
Frequency
Friction Inc
Sets the maximum setpoint friction compensation at maximum output frequency (E1-04). This function is a linear calculation with P3-13 as its starting frequency.
Example: P3-13 = 30.0 Hz, P3-14 = 10.0 psi, output frequency = 45.0 Hz and maximum frequency = 60.0 Hz
Set-point Increase = (45-30 Hz) x 10 psi/(60 Hz – 30 Hz) ≥ 5.0 psi
Note: This function is only active in simplex mode when P1-01 = 0.
0.0 ~
6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
Denotes that parameter can be changed when the drive is running.
76 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
P4-01
P4-02
P4-03
0115
0116
0117
Parameter Name
Digital Operator
Display
Pre-charge Level
Pre-charge Level
Pre-charge Frequency
Pre-charge Freq
Pre-charge Time
Pre-charge Time
Description
Setting
Range
Factory
Setting
Menu
Location
Pump Advanced
Sets the level when the drive will run at the pre-charge frequency
(P4-02). The drive will stop when one of the following conditions occurs:
Feedback signal rises above P4-01 level, pre-charge timer
P4-03 expires, or low water digital input is deactivated (H1 = 85).
The pre-charge function can only be activated while in a stop condition.
The function is enabled by setting P4-03 to a value greater than 0. When the function is activated, the drive’s operator display indicates a “Precharge” alarm.
0.0 ~
6000.0
(system units
P1-02)
Note: This function is only active in the stopped mode.
If P1-01 = 3, the function is active when there is only one drive running on the network.
<0034>
Thrust Mode: The pre-charge level is used when the thrust mode is active for the feedback check. The thrust mode is deactivated when the feedback exceeds the programmed level in P4-01. A value of 0 disables the thrust mode feedback check function.
Sets the frequency reference used when the pre-charge function is active.
0.00 ~
120.00 Hz
Sets the maximum allowed pre-charge time.
A value of 0 disables this function. If P1-01 = 3, the function is active when there is only one drive running on the network.
<0034>
Sets the thrust bearing acceleration time. When enabled (P4-05 > 0), the drive output frequency will ramp up to the specified thrust bearing frequency reference in P4-05 using an acceleration time as specified in P4-
04. The PI mode is automatically disabled.
Once the output frequency reaches the programmed thrust bearing frequency, the drive automatically switches to PI control and the original acceleration time (C1-01), and will continue in the normal operation (auto) mode, unless Pre-charge is enabled, in which case Pre-charge mode occurs.
This function active in the Hand Mode and Auto Mode.
0.0 ~
3600.0 min
0.0 ~
600.0 sec
0.0 (system units
P1-02)
Programming
0.00 Hz Programming
0.0 min Programming
1.0 sec Programming
P4-04
P4-05
P4-06
<0032>
P4-07
<0032>
0118
0119
011A
011B
Thrust Bearing
Acceleration Time
Thrust Acce Time
Thrust Bearing Frequency
Thrust Freq
Thrust Bearing
Deceleration Time
Thrust Dec Time
Feedback Fault Auto
Restart Enable
Fdback Flt Rstrt
Note: In Auto Mode , the Minimum Pump Frequency will become the thrust bearing frequency if smaller than the thrust bearing frequency in P4-
05.
In Hand Mode , the minimum frequency is P4-05 when the thrust mode is enabled. The Pre-charge level is not active in the hand mode.
Sets the frequency reference used when the thrust bearing function is active. A value of 0 disables this function.
This deceleration time will be used to bring the drive from Thrust
Frequency (P4-05) to stop when Thrust Mode is active. Any time the Run
Command is removed while the drive is operating in the Thrust Mode above the Thrust Frequency, this deceleration time will be used once the frequency reference is at or below the Thrust Frequency.
0.0 ~
120.0 Hz
Note: In Auto Mode , the Minimum Pump Frequency (P1-06) will become the thrust bearing frequency if smaller than the thrust bearing frequency in
P4-05.
In Hand Mode , the minimum frequency is P4-05 when the thrust mode is enabled. The Pre-charge level is not active in the hand mode.
Setting to enable/disable Auto Restart for the following iQpump transducer/feedback faults (N = disable/Y = enable):
LL: Low Level Feedback (P1-07)
HL: High Level Feedback (P1-09)
TL: Transducer Loss (b5-12)
0: TL = N HL = N LL = N
1: TL = N HL = N LL = Y
2: TL = N HL = Y LL = N
3: TL = N HL = Y LL = Y
4: TL = Y HL = N LL = N
5: TL = Y HL = N LL = Y
6: TL = Y HL = Y LL = N
7: TL = Y HL = Y LL = Y
0.0 ~
600.0 sec
0 ~ 7
Note: Parameter L5-01 must be set to “1” and program L5-03 must be set to the applicable time.
Denotes that parameter can be changed when the drive is running.
30.0 Hz Programming
1.0 sec Programming
0 Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 77
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
P4-08
<0032>
011C
Protection Fault Auto
Restart Enable
Prot Flt Restrt
Setting to enable/disable Auto Restart for the following iQpump protection faults (N = disable/Y = enable):
SP: Not Maintaining SetPoint (P1-11)
LOP: Loss of Prime (P1-16)
POC: Pump Over Cycling (P2-08))
0: POC = N LOP = N SP = N
1: POC = N LOP = N SP = Y
2: POC = N LOP = Y SP = N
3: POC = N LOP = Y SP = Y
4: POC = Y LOP = N SP = N
5: POC = Y LOP = N SP = Y
6: POC = Y LOP = Y SP = N
7: POC = Y LOP = Y SP = Y
0 ~ 7
P4-09
<0032>
011D
Loss of Prime Maximum
Restart Time After Fault
LOP Max Rstrt T
Note: Parameter L5-01 must be set to “1” and program L5-03 must be set to the applicable time.
If the restart fails (or is not attempted due to a continuing fault condition) the drive waits this many minutes before attempting another restart.
0.2 ~
6000.0 min
Note: This parameter will take the place of L5-03 during a Loss of Prime
Fault restart attempt.
Stores the run status in the Auto mode when operating from digital operator (b1-02 = 0).
0: Disabled.
1: Enabled.
0 ~ 1
P4-10
011E
Auto Mode Operator Run
Power Down Storage.
AMO PwDn-Storage
WARNING
P4-11
<0034>
82A
Utility Start Delay
Utility Delay
When the drive is powered down while running, then upon power-up it will automatically initiate an internal run command.
Sets the amount of time the drive will delay starting if a run command is present at power up.
A setting of 0.0 disables this function.
If P1-01 = 3, the drive is unavailable to the network (Pump Off Network) when the function is active. <0034>
0.0 ~
1000.0 min
P4-12
<0034>
P4-13
<0034>
P4-14
<0034>
82B
82C
82D
Pre-charge Frequency 2
Pre-charge Freq2
Pre-charge Time 2
Pre-charge Time2
Two Motor Alternation
Selection
Mot 2 Alternate
Frequency reference used when Pre-charge 2 function is active.
A value of 0.00 disables this function.
Time at which the drive will spend at the Pre-charge Frequency 2
(P4-12) speed during pre-charge.
A value of 0.0 disables this function.
Selects if the alternation feature is enabled.
0: Disabled
1: Enabled
2: Motor 1 Only
3: Motor 2 Only
0.00 ~
120.00 Hz
0 ~
3600.0 min
0 ~ 3
P4-15
<0034>
P4-16
<0034>
P4-17
<0034>
82E
82F
830
Alternation Operation
Selection
Alternation Oper
Alternation Time
Alternation Time
Dual Zone PID Feedback
Bandwidth Range
Dual Zone Range
Selects the drive behavior when the internal alternation timer expires.
0: Wait For Stop
1: Immediate
Selects the amount of time each motor will run before the drive switches to the other motor.
Determines the detection bandwidth for the dual zone PI control.
0 ~ 1
1.0 ~
100.0 hr
0 ~ 6000.0
(system units
P1-02)
This parameter sets the amount of time the drive will run for when the runstop control is enabled. It will also set the “timed” run time when enabled
(b1-02 = 5).
0.0 ~
6000.0 min
P4-18
<0034>
P4-19
<0034>
831
832
Run-Stop Control Run
Time
R-S Run Time
Run-Stop Control Stop
Time
R-S Stop Time
This parameter sets the amount of time the drive will stop for when the run-stop control is enabled.
P4-20
<0034>
833
Run-Stop Control Cycles
R-S Cycle Count
This parameter determines how many run-stop cycles the drive will execute before staying stopped.
Denotes that parameter can be changed when the drive is running.
0.0 ~
6000.0 min
0 ~ 1000
0
0.2 min Programming
0
0
0
Pump Quick
Setup
0.2 min Programming
0.00 Hz Programming
0.0 min Programming
24.0 hr Programming
10.0
(system units
P1-02)
Programming
0.0 min Programming
0.0 min Programming
0
Programming
Programming
Programming
Programming
78 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
P4-21
<0034>
P4-22
<0034>
P4-23
<0034>
P4-24
<0035>
P4-25
<0035>
P4-26
<0035>
P4-27
<0035>
P4-31
<0035>
P4-32
<0035>
P4-33
<0035>
P4-34
<0035>
P4-35
<0035>
P4-36
<0035>
P4-37
<0035>
P4-38
<0035>
P4-39
<0035>
834
835
836
837
838
839
83
83B
83C
83D
83E
83F
85B
85C
85D
85E
Minimum Geothermal
Temperature Inpu
MinGeothrm Scale
Maximum Geothermal
Temperature Inpu
MaxGeothrm Scale
Minimum Geothermal
Speed
MinGeothrm Speed
Maximum Geothermal
Speed
MaxGeothrm Speed
Low Temperature to
Run at Maximum
Geothermal Speed
Low Temp @ Max
Low Temperature to
Run at Minimum
Geothermal Speed
Low Temp @ Min
Low Temperature to
Run at Minimum
Geothermal Speed
Low Temp @ Min
High Temperature to
Run at Maximum
Geothermal Speed
High Temp @ Max
Parameter Name
Digital Operator
Display
Description
Low City Pressure Input
Select
Low City In Sel
Low City Pressure Input
Delay
Low City Delay
Lube Pump Delay Timer
Lube Pump Time
Remote Drive Disable
Selection
Rem Drv Dis Sel
Selects the type of pressure switch connected to the “Low City Pressure” digital input (H1-0x = 73).
0: Normally Open (closed indicates the “Low City Pressure” condition)
1: Normally Closed (open indicates the “Low City Pressure” condition)
Sets the amount of time a “Low City Pressure” condition must be present before the drives will stop. Also sets the amount of time that the pressure must be adequate before the drive system will re-start.
Sets the amount of time the drive’s output will be delayed and the Lube
Pump digital output (H2-0x = 55) will be energized.
A setting of zero will disable this feature.
Selects the type of pressure switch connected to the “Remote Drv Disbl” digital input (H1-0 =72).
0: Normally Open (closed indicates the “Remote Drive Disable” condition).
1: Normally Closed (open indicates the “Remote Drive Disable” condition).
Remote Drive Disable
On-Delay
Drv Dis On-Delay
Remote Drive Disable
Off-Delay
Drv Dis Off-Delay
Sets the amount of time a “Remote Drive Disable” condition must be present before the drive will stop.
Sets the amount of time a “Remote Drive Disable” condition must be absent before the drive will be allowed to run.
Low City Alarm Text
Low Cty Alrm Txt
Selects the alarm message that will be displayed when a Low City condition is detected.
0: Low City Pressure
1: Low Suction Pressure
2: Low Water in Tank
Parameter functionality stated below only applies when b1-01 = 5 (Geothermal Mode)
Sets the temperature that corresponds to a 0V (or 4 mA) analog input.
Sets the temperature that corresponds to a 10V (or 20 mA) analog input.
Frequency Reference (Hz)
P4-34
P4-33
P4-35 P4-36
Temperature (
P4-36 P4-38
° F)
Sets the frequency reference characteristics based on the set temperature points and the corresponding frequency.
For proper operation, P4-34>P4-33 and P4-38>P4-37>P4-36>P4-35.
See Function Description for more information.
Geothermal Temperature
Loss Detection
Geotherm Loss Det
Selects the drive action when the signal from Terminal A2 has gone below
3 mA or above 21 mA. Only effective when H3-08 = 2
(4-20 mA) and H3-09 = 20 (Geothermal Temp).
0: Disabled
1: Alarm
2: Fault
Setting
Range
0 ~ 1
1 ~ 1000 sec
0.0 ~
300.0 sec
0.0 ~ 1
0 ~ 1000 sec
0 ~ 1000 sec
0 ~ 2
-110.0 ~
440.0 °F
-110.0 ~
450.0 °F
0.00 ~
120.00Hz
0.00 ~
120.00Hz
-110.0 ~
450.0 °F
-110.0 ~
450.0 °F
-110.0 ~
450.0 °F
-110.0 ~
450.0 °F
0 ~ 2
Factory
Setting
1
10 sec
0.0 sec
0.0 sec
0 sec
0 sec
0 sec
0.0
150.0
Menu
Location
40.00 Hz Programming
60.00 Hz Programming
55.0
65.0
75.0
85.0
1
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 79
Parameter
No.
Addr.
Hex
P5-01
P5-02
P5-03
<0032>
P5-04
<0032>
P6-01
<0034>
0124
0125
0114
0513
840
Parameter Name
Digital Operator
Display
Hand Mode Reference
Source
Hand Mode Ref
Hand Reference
Hand Reference
HAND/AUTO During
Run Selection
HAND/AUTO @Run
Hand Key Function
Selection
Oper HAND Key
Flow Meter Scaling
Flow Meter Scale
Description
Setting
Range
Hand Mode
Sets the hand mode reference source.
0: Analog Input A1 (0-10 V)
1: Hand reference (P5-02)
Sets the frequency reference used when the hand mode is active and P5-01 is programmed to 1.
Selects if the drive will permit switching between HAND and AUTO modes while running.
0: Disabled
1: Enabled
Switching from HAND to AUTO is not permitted when the drive output frequency is less than the PID minimum speed.
Switching from AUTO to HAND is not permitted when the drive is running in the multiplex mode with auxiliary drives enabled.
Enables or disables the “HAND” key on the digital operator.
0: Disabled
1: Enabled
Flow Meter Setup
Sets the scaling for the flow meter connected to Terminal A1. Enter the gal/ min when the flow meter is at it’s rated output.
A setting of 0.0 disables all flow meter functions.
Sets the units displayed for monitor U1-95. Also sets units for parameters
P2-02 and P6-04, P9-41 and P9-42.
0 ~ 1
0.00 ~
120.00 Hz
0 ~ 1
0 ~ 1
0.0 ~
6000.0
Gpm
Factory
Setting
1
0
1
Menu
Location
Programming
40.00 Hz Programming
Programming
Pump Quick
Setup
0.0 Gpm Programming
P6-02
<0034>
841
Water Flow Units
Water Flow Units
Flow Accumulation Reset
Flow Accum Reset
0: U.S. Gallons/min (GPM)
1: U.S. Gallons/hr (GPH)
2: U.S. Barrels/min (BPM)
3: U.S. Barrels/hr (BPH)
4: U.S. Barrels/Day (BPD)
Resets the accumulated flow and returns the monitors U1-96 and
U1-97 to zero.
0: No Reset
7770: Reset Accum
All other settings will have no effect.
0 ~ 4
P6-03
<0034>
842 0 ~ 65535
P6-04
<0034>
843
Low Flow Level
Low Flow Level
Note: After this parameter is changed it will automatically return to a “0”.
If the drive is running and the flow goes below this level for more than the
P6-05 time, a Low Flow fault or alarm will occur.
A setting of 0 disables the low flow detection.
0.0 ~
6000.0
(*n1)
P6-05
<0034>
P6-06
<0034>
844
845
Low Flow Detection Delay
Time When Already
Running
Low Flow Tim Run
Low Flow Detection Wait
Time At Start
Low Flow Time St
Sets the amount of time the flow rate must be below the P6-04 level before a Low Flow condition is detected.
Sets the time the drive will wait after coming out of a zero speed condition before activating Low Flow detection.
(*n1) Displayed units are determined by parameter P6-02.
Denotes that parameter can be changed when the drive is running.
0 ~ 6000 sec
0.0 ~
3600.0 min
P6-07
<0034>
846
Low Flow Select
Low Flow Sel
If P1-03 = 3, a LOWFL fault will stop all drives running on the network.
Sets the behavior of the drive when a “Low Flow” condition is detected.
0: No Display
1: Alarm Only
2: Fault
3: Auto-Restart (time set by P6-08)
0 ~ 3
P6-08
<0034>
847
Low Flow Auto-Restart
Time
Low Flow Rstrt
Sets the amount of time the drive will wait before attempting an autorestart of the “Low Flow” fault. Effective only when P6-07 = 3.
0.1 ~
6000.0 min
P6-09
<0034>
848
Accumulation Level Fine
Accum Lvl Fine
Sets the accumulated volume that will trigger the Accum Level alarm.
Accum Level fault, or Accum Level digital output. Total Accum Level can be calculated as follows:
Total Accum Level = P6-10 x 1000 + P6-09.
If P1-01 = 3, an ACCUM fault will stop all drives running on the network.
0.0 ~
999.0 gal
0
0
0.0
10 sec
Programming
Programming
Programming
Programming
0.0 min Programming
1
3.0 min Programming
0.0 gal
Programming
Programming
80 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
P6-10
<0034>
P6-11
<0034>
P6-12
<0034>
849
84A
84B
Accumulation Level
Course
Accum Lvl Course
Accumulation Behavior
Accum Behavior
High Flow Level
High Flow Level
Sets the accumulated volume that will trigger the Accum Level alarm.
Accum Level fault, or Accum Level digital output. Total Accum Level can be calculated as follows:
Total Accum Level = P6-10 x 1000 + P6-09.
If P1-01 = 3, an ACCUM fault will stop all drives running on the network.
Sets how the drive will respond when the accumulated volume reaches the
P6-09 and P6-10 level.
0: No Display
1: Alarm Only
2: Fault
3: Fault - Auto Flow Accum Reset
If the drive is running and the flow goes above this level for more than the
P6-13 time, a High Flow fault or alarm will occur.
A setting of 0 disables the High Flow detection.
If P1-01 = 3, a HIFLO fault will stop all drives running on the network.
P6-13
<0034>
84C
High Flow Detection
Delay Time
High Flow Time
Sets the amount of time the flow rate must be above the P6-12 level before a High Flow condition is detected.
P6-14
<0034>
84D
High Flow Select
High Flow Sel
Sets the behavior of the drive when a “High Flow” condition is detected.
0: No Display
1: Alarm Only
2: Fault
3: Auto-Restart (time set by L5-03)
(*n1) Displayed units are determined by parameter P6-02.
Anti-Jam/De-Scale
0 ~
61036 kgl
0 ~ 3
0.0 ~
6000.0
(*n1)
1 ~ 6000 sec
0 ~ 3
0 kgl
1
0.0
10 sec Programming
1
Programming
Programming
Programming
Programming
P7-01
<0034>
P7-02
<0034>
P7-03
<0034>
P7-04
<0034>
P7-05
<0034>
P7-06
<0034>
852
853
854
Anti-Jam Detection Time
A-J Det. Time
Anti-Jam/De-Scale
Frequency Reference
AJ/De-Scale Freq
De-Scale Forward Run
Time
De-Scale Fwd Run
Sets the amount of time the current must be above the P7-03 level to trigger the Anti-Jam function.
Sets the speed during the De-Scale operation and during reverse operation of the Anti-Jam function.
Sets the amount of time the drive will run in the forward time each cycle during the De-Scale function.
P7-07
<0034>
855
De-Scale Reverse Run
Time
De-Scale Rev Run
Sets the amount of time the drive will run in the reverse time each cycle during the De-Scale function.
Denotes that parameter can be changed when the drive is running.
P7-08
<0034>
P7-09
<0034>
P7-10
<0034>
84F
850
851
856
857
858
Anti-Jam/De-Scale
Operation Selection
Anti-Jam/De-Scale
Anti-Jam/De-Scale Cycle
Count
A-J Cycle Count
Anti-Jam Detection
Current Level
A-J Detection Level
De-Scale Acceleration
Time
De-Scale Accel
De-Scale Deceleration
Time
De-Scale Decel
De-Scale Pump Run Time
De-Scale Time
Selects if the Anti-Jam or De-Scale functions are enabled.
0: Disabled
1: Anti-Jam Enabled
2: De-Scale Enabled.
3: Force De-Scale
This parameter sets the maximum number of cycles attempted before the
Anti-Jam fault occurs and also sets the number of fwd/rev cycles for the
De-Scale function.
Sets the current level (at start) that will trigger the Anti-Jam function. Set as a percentage of motor rated current.
Sets the amount of time it will take the drive to accelerate from zero to the
De-Scale frequency reference P7-05 (internally limited 0.1 ~ 6000.0 sec).
Sets the amount of time it will take the drive to decelerate from the
De-Scale frequency reference P7-05 to zero (internally limited 0.1 ~
6000.0 sec).
Sets the number of pump operating hours (pump speed > 0) before a
De-Scale routine will run.
0 ~ 3
1 ~ 100
0.1 ~ 2.0 sec
0.00 ~
120.00 Hz
1 ~ 6000 sec
1 ~ 6000 sec
0.0 ~
600.0 sec
0.0 ~
600.0 sec
1.0 ~
2000.0 hr
0
1
50 ~ 200 % 120 % Programming
0.3 sec
25.00 Hz Programming
10 sec
10 sec
2.0 sec
2.0 sec
168.0 hr
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
P7-11
<0034>
859
Anti-Jam Release Time
Anti-Jam Release
Sets the amount of time that the current must be below the P7-03 level in order to resume normal operation.
0.5 ~
10.0 sec
2.0 sec Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 81
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Pressure and Level Control z Applies when P8-01 = 0 or 1
Applies when P8-01 = 2
P8-01
<0034> z P8-02
<0034>
P8-02
<0035> z P8-03
<0034>
P8-03
<0035> z P8-04
<0034>
P8-04
<0035> z P8-05
<0034>
P8-05
<0035> z P8-06
<0034>
P8-06
<0035> z P8-07
<0034>
P8-07
<0035> z P8-08
<0034>
P8-08
<0035> z P8-09
<0034>
P8-09
<0035>
860
861
861
862
862
863
863
864
864
865
865
866
866
867
867
868
868
Water Level/Suction
Pressure Selection
WtrLvl/SuctnPres
Water Level Scaling
Water Lvl Scale
Suction Transducer
Scaling
Suction Scaling
Sets the mode of operation for the Water Level/Suction Control function:
0: Disabled
1: Water Level Control
2: Suction Control <0035>
Sets the full scale (20 mA) output of the pressure transducer connected to
Terminal A1.
Sets the full scale (20 mA) output of the pressure transducer connected to
Terminal A1.
0 ~ 2
5 ~
500 psi
5 ~
500 psi
Water Level Set-point
Water Lvl Setpnt
Suction Pressure
Set-point
Suction Setpoint
Sets the amount of water above the sensor that the drive will attempt to regulate to.
Sets the amount of suction pressure that the drive will attempt to regulate to.
0.0 ~
1200.0 ft
0.0 ~
1200.0 psi
Minimum Water Level
Min Water Level
When the amount of water above the sensor drops below this level for more than the P2-03 time, the drive will go to sleep.
0.0 ~
1200.0 ft
Minimum Suction
Pressure
Min Suction Pres
When the suction pressure drops to below this level for more than the P2-
03 time, the drive will go to sleep and turn off all lag pumps.
0.0 ~
1200.0 psi
Wake-Up Water Level
Wake-Up Level
Wake-Up Suction Pressure
Wake-Up Pres
Level Control Minimum
Speed
Level Min Spd
Suction Control Minimum
Speed
Suction Min Spd
Low Level Detection
Level
Low Level Detection
Low Suction Pressure
Detection Level
Low Pres Detection
Low Level Detection Time
Delay
Low Lvl Det Tm
Low Suction Pressure
Time Delay
Low Pres Det Tm
Low Level Behavior
Low Lvl Behavior
Low Suction Pressure
Behavior Select
Low Pressure Sel
If the drive has been forced to sleep based upon the minimum water level
(P8-04), the water must go above this level for more than the P8-13 time in order to wake up.
If the drive has been forced to sleep based upon the minimum suction pressure (P8-04), the suction pressure must go above this level for more than the P8-13 time in order to wake up.
This parameter sets the minimum speed the drive will be allowed to run at when the drive is controlling the water level. When the drive is controlling pressure or this parameter is set less than P1-06 and P4-05, P1-06 and P4-
05 will be used as the minimum speed.
This parameter sets the minimum speed the drive will be allowed to run at when the drive is controlling suction pressure. When the drive is controlling outlet pressure or this parameter is set less than P1-06 and P4-
05, P1-06 and P4-05 will be used as the minimum speed.
When the amount of water above the sensor drops below the level for more than the P8-08 time, the drive will respond depending on the
P8-09 setting.
A setting of 0.0 disables this detection.
When the amount of suction pressure drops below this level for more than the P8-08 time, the drive will respond depending on the P8-09 setting. A setting of 0.0 disables this detection.
0.0 ~
1200.0 ft
0.0 ~
1200.0 psi
0.00 ~
120.00 Hz
0.00 ~
120.00 Hz
0.0 ~
1200.0 ft
0.0 ~
1200.0 psi
Sets the amount of time delay that the water level must drop below the P8-
07 level before the drive will react.
Sets the amount of time delay that the suction pressure must drop below the P8-07 level before the drive will react. Time unit is defined by P8-14.
0.0 ~
300.0
(P8-14 units)
0.0 ~
300.0
(P8-14 units)
Sets how the drive will respond when the water level in the well drops below the P8-07 level for more than the P8-08 time.
0: No Display (Digital Output Only)
1: Alarm Only
2: Fault
3: Auto-Restart (time set by P8-12)
Sets how the drive will respond when the suction pressure drops below the
P8-07 level for more than the P8-08 time.
0: No Display (Digital Output Only)
1: Alarm Only
2: Fault
3: Auto-Restrart (time set by P8-12)
0 ~ 3
0 ~ 3
Factory
Setting
0
Menu
Location
100 psi Programming
100 psi Programming
20.0 ft Programming
20.0 ft Programming
10.0 ft Programming
10.0 ft Programming
30.0 ft Programming
30.0 ft Programming
0.00 Hz Programming
0.00 Hz Programming
0.0 ft
0.0 ft
Programming
Programming
0.1 min Programming
0.1 min Programming
1
1
Programming
Programming
Programming
82 YASKAWA TM.iQp.10 Technical Manual Supplement
z P8-10
<0034>
P8-10
<0035> z P8-11
<0034>
P8-11
<0035>
Parameter
No.
z P8-12
<0034>
P8-12
<0035 only> z P8-13
<0034>
P8-13
<0035 only> z P8-14
<0034>
P8-14
<0035 only>
Addr.
Hex
869
869
86A
86A
86B
86B
86C
86C
86D
86D
Parameter Name
Digital Operator
Display
Level Control Proportional
Gain
Lvl Ctrl P Gain
Suction Control
Proportional Gain
Suction P Gain
Level Control Integral
Time
Lvl Ctrl I Time
Suction Control
Integral Time
Suction I Time
Water Level Control
Auto-Restart Time
WtrLvl Restart
Suction Pressure Auto-
Restart Time
Suction Restart
Water Level Control
Sleep Wake-up Time
WL Wake-up Time
Suction Pressure
Sleep Wake-up Time
SP Wake-up Time
Low Water Level
Detection Time Unit
Low Lvl Det Unit
Low Suction Pressure
Detection Time Unit
Low Pres Det Unit
Description
Sets the proportional gain for the water level control.
Sets the proportional gain for the suction pressure control.
Sets the integral time for the water level control. A setting of zero disables the water level control integrator.
Sets the integral time for the suction pressure control. A setting of zero disables the suction pressure control integrator.
Sets the amount of time the drive will wait before attempting to auto-restart of the “Low Water Level” fault. Effective only when P8-09 = 3 & L5-
01>0.
0.1 ~
6000.0 min
Sets the amount of time the drive will wait before attempting to auto-restart of the “Low Suction” fault. Effective only when P8-09 = 3 & L5-01>0.
0.1 ~
6000.0 min
If the drive has been forced to sleep based upon the minimum water level
(P8-04), the water must go above the P8-05 level for more than this time in order to wake up.
If the drive has been forced to sleep based upon the minimum suction pressure (P8-04), the pressure must go above the P8-05 level for more than this time in order to wake up.
Defines the time unit for P8-08.
0: Minutes (min)
1: Seconds (sec)
Defines the time unit for P8-08.
0: Minutes (min)
1: Seconds (sec)
Network Options
P9-01
<0034>
P9-02
<0034>
P9-06
<0034>
0880
0881
0885
Parameter functionality stated below only applies when P1-01 = 3 (Memobus Network)
Lead Drive Selection
Lead Drive Sel
Specifies how the next Lead Drive is selected.
0: Next Available
1: Lowest Runtime
2: Stop History <0035>
Feedback Source
Feedback Source
Defines which signal to use for PI Feedback when P1-01 = 3.
0: Analog Only
1: Ana->Net, No Alarm.
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01 = 3.
P9-03
<0034>
0882
Alternation Time
Alternation Time
Specifies the time for a drive to request alternation, influenced by the
Alternation Mode P9-04.
The alternation feature is disabled when this parameter is set to 0.
Denotes that parameter can be changed when the drive is running.
P9-04
<0034>
P9-05
<0034>
0883
0884
Alternation Mode
Alternation Mode
Lag Drive Mode
Lag Drive Mode
Determines how alternation is performed:
0: FIFO Auto
1: FIFO Forced
2: LIFO
Determines how the lag drives function.
0: Fixed Speed - Runs at the P9-06 setting.
1: PI Regulation - Uses PI to determine speed.
2: Turn Off: Drive stops running when it switches to a lag drive after the
P9-07 time expires.
3: Follow Lead Spd: The drive will follow the speed of the current Lead drive applying P9-30 gain and P9-31 bias. <0035>
Lag Fixed Speed
Lag Fixed Speed
When the drive changes from a lead to a lag and P9-05 = 0, the drive will run at this speed after P9-07 delay time expires.
P9-07
<0034>
0886
Lag Fixed Speed Delay
Lag Fixed Spd Dly
When the drive changes from a lead to a lag and P9-05 ≠ 1, this time specifies how long the speed is latched before doing one of the following:
<0035>
(1) P9-05 = 0: Run at P9-06
(2) P9-05 = 2: Turn off
(3) P9-05 = 3: Follow the Lead Drive’s speed.
Setting
Range
0.00 ~
25.00
0.00 ~
25.00
0.0 ~
360.0 sec
0.0 ~
360.0 sec
0.0 ~
3600 sec
0.0 ~
3600 sec
0 ~ 1
0 ~ 1
0 ~ 2
0 ~ 3
0 ~ 1000 hr
0 ~ 2
0 ~ 3
0.0 ~
120.0 Hz
0 ~ 1000 sec
Factory
Setting
2.00
2.00
Menu
Location
5.0 sec Programming
5.0 sec Programming
5.0 min Programming
5.0 min Programming
1 sec
1 sec
0
0
1
0
24 hr
0
0
55.0 Hz Programming
5 sec
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 83
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
P9-08
<0034>
0887
Add Pump Mode
Add Pump Mode
Selects the detection method for staging a new pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
3: Flow Meter <0035>
When P9-08 = 0 and the output frequency rises above this level for the time set in P9-11, the lead drive will request for a new lead drive through the iQpump Memobus Network.
P9-09
<0034>
0888
Add Freq Level
Add Freq Lvl When P9-08 = 2 and the output frequency rises above this level the delta feedback (setpoint - feedback) has exceeded the level set in
P9-10 for the time set in P9-11, the lead drive will request for a new lead drive through the iQpump Memobus network.
When P9-08 = 1 and the delta feedback (setpoint - feedback) has exceeded this level for the time set in P9-11, the lead drive will request for a new lead drive through the iQpump Memobus Network.
P9-10
<0034>
088A
Add Delta Level
Add Delta Lvl When P9-08 = 2 and the delta feedback (setpoint - feedback) has exceeded this level and the output frequency is above P9-09 for the time set in P9-11, the lead drive will request for a new lead drive through the iQpump
Memobus network.
P9-11
<0034>
088A
Add Delay Time
Add Dly Time
Delay time before a new lead drive is added to the system.
P9-12
<0034>
088B
Remove Pump Mode
Remove Pump Mode
Selects the detection method for de-staging to the previous lead pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
3: Flow Meter <0035>
When P9-12 = 0 and the output frequency drops below this level for the time set in P9-15, the lead drive will request to be removed from the system through the iQpump Memobus network.
P9-13
<0034>
088C
Remove Freq Level
Remove Freq Lvl When P9-12 = 2 and the output frequency drops below this level and the delta feedback (feedback - setpoint) has exceeded the level set in P9-14 for the time set in P9-15, the lead drive will request to be removed from the system through the iQpump Memobus network.
When P9-12 = 1 and the delta feedback (feedback - setpoint) has exceeded this level for the time set in P9-15, the lead drive will request to be removed from the system through the iQpump Memobus network.
P9-14
<0034><0034
>
088D
Remove Delta Level
Remove Delta Lvl When P9-12 = 2 and the delta feedback (feedback - setpoint) has exceeded this level and the output frequency is below P9-13 for the time set in P9-
15, the lead drive will request to be removed from the system through the iQpump Memobus network.
P9-15
<0034>
P9-16
<0034>
088E
088F
Remove Delay Time
Remove Dly Time
Stabilization Time
Stabilization Time
Delay time before the lead drive is removed from the system.
Time used to stabilize the system when a pump is staged or de-staged.
Lead-lag control and pump protection is suspended during this time.
Denotes that parameter can be changed when the drive is running.
Setting
Range
0 ~ 3
0.0 ~
120.0 Hz
0 ~ 3600 sec
0.0 ~
120.0 Hz
0 ~ 3600 sec
0 ~ 3600 sec
Factory
Setting
0
56.0 Hz
Menu
Location
0 ~ 6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
0 ~ 3
10 sec
0
40.0 Hz
Programming
Programming
Programming
0 ~ 6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
10 sec
3 sec
Programming
Programming
Programming
Programming
P9-17
<0034>
0890
Setpoint Modifier
Set-pt Modifier
System Set-point is incremented with this value depending on the number of pumps running.
Pump 1: Set-point
Pump X: Set-point + {(X-1) (P9-17)}
-6000.0 ~
6000.0
(system units
P1-02)
0.0 (system units
P1-02)
Programming
P9-18
<0034>
0891
High Feedback Quick De-
Stage
High FB De-stage
Determines the feedback level to trigger a quick de-stage, set as a percentage of parameter P1-09. The quick de-stage ignores parameters P9-
12 to P9-15 and only uses an internal 2 second delay.
Selects the unit for P9-03
0.0 ~
100.0 %
90.0 % Programming
P9-19
0892
Alternation Unit
Alternation Unit
0: Hours (hr)
1: Minutes (min)
0 ~ 1 0 Programming
84 YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
P9-20
P9-21
P9-22
<0034>
0893
0894
0895
Allow Network Run
Allow Net Run
Run Priority
Run Priority
System Fault Retry
System Flt Retry
Specifies when a network run command is allowed:
0: Always
1: First/Alternation
2: First Only
3: Alternation Only
Sets the Lead Drive selection priority overriding the P9-01 selection. If multiple drives have the lowest P9-21 value, then P9-01 determines which drive becomes the Lead.
Determines the number of times the iQpump Memobus Network will allow automatic restarts of system faults. The drive uses parameter
L5-03 in determining when to attempt a system fault restart.
For proper operation, this parameter should be set the same for all network drives.
0 ~ 3
1 ~ 16
0 ~ 10
P9-23
<0034>
0896
Max Number of Running
Pumps
MaxPumps Running
Limits the maximum number of pumps that can run on the system.
1 ~ 8
P9-24
<0034>
P9-25
<0034>
P9-26
<0034>
P9-27
<0034>
0897
0898
0899
089A
Lead Swap @ Sleep
Lead Swap @ Sleep
Highest Node Address
Highest Node Adr
Master Time-Out
Master Time-0ut
Network Recovery
Network Recovery
When the Lead DRive has been in Sleep for this amount of time and there is another drive available with a lower P9-21, then this drive will request for a swap.
A setting of 0 disables this function.
Defines the highest possible node address in the Memobus network. To yield optimal network performance, it is recommended to set the serial communication address H5-01 starting from 01h and then consecutively up to the last drive and then setting this parameter to that H5-01 address.
Sets the minimum amount of time that the slave drives will wait for a message from the master before performing the action set in P9-27.
When no messages are received from the master for the time set in
P9-26, the slave drive will act according to this setting:
0: Automatic - drive will attempt to assume master functionality.
1: Slave/Resume - drive will continue running when the master is lost and will wait for a master to come on-line.
2: Slave/Stop - drive will stop running when the master is lost and will wait for a master to come on-line.
3: Fault MSL - fault the drive with an MSL (Master Lost).
Sets the amount of time that the slave drives will wait for a message from the master before displaying a NETSCAN alarm.
After the first drive on the network has been put on Auto mode, the network will wait this amount of time before selecting and starting the
Lead Drive.
0 ~ 7200 sec
02h ~ 8h
3.0 ~
10.0 sec
0 ~ 3
P9-28
<0034>
P9-29
<0034>
P9-30
<0035>
P9-31
<0035>
P9-32
<0036>
089B
089C
NETSCAN Alarm Time
NETSCAN Alrm Time
Net Start Delay
Net Start Delay
1.0 ~
10.0 sec
0.0 ~
60.0 sec
P9-33
<0036>
P9-40
<0035>
P9-41
<0035>
P9-42
<0035>
0876
0877
0871
0872
089D
089E
089F
Lag Drive Speed
Follower Gain
Lag Follower Gain
Lag Drive Speed
Follower Bias
Lag Follower Bias
Lag Follower
Deceleration Time
Lag Follower Dcel
Lag Follower
Deceleration Time Active
Time
Lag Follower Dtim
Flow Rate Source
Flow Rate Source
Add Flow Rate Level
Add Flow Lvl
Remove Flow Rate Level
Remove Flow Lvl
When P9-05 = 3, the drive will follow the speed of the current lead drive applying this gain and the P9-31 bias.
When P9-05 = 3, the drive will follow the speed of the current lead drive applying the P9-30 gain and this bias.
When the P9-33 timer is running, and the drive is running as Lag Drive
Speed Follower (P9-05 = 3), then the deceleration time is set to this value.
The P9-32 deceleration time is effective during this time window. The drive will use the standard deceleration rates when it expires.
A setting of 0.0 sec will disable the Lag Follower deceleration time switching.
Defines the Flow Meter input source when P1-01=3:
0: Analog
1: Network
When P9-08=3 and the Flow Rate is above this level x no. of pumps running for the time set in P9-11, the lead drive will request for a new lead drive through the iQpump Memobus network.
Note: (*n1) Displayed units are determined by parameter P6-02.
When P9-12=3 and the Flow Rate is above this level x (no. of pumps running -1) for the time set in P5-15, the lead drive will request to be removed from the system through the iQpump Memobus network.
Note: (*n1) Displayed units are determined by parameter P6-02.
0.0 ~
300.0%
-60.0 ~
60.0Hz
0.0 ~
1000.0 sec
0.0 ~
360.0 sec
0 ~ 1
0.0 ~
6000.0
(*n1)
0.0 ~
6000.0
(*n1) z Applies when P8-01 = 0 or 1
Applies when P8-01 = 2
Factory
Setting
0
8
5
8
0 sec
08 h
Menu
Location
Programming
Programming
Programming
Programming
Programming
Programming
4.0 sec Programming
0
2.0 sec Programming
2.0 sec Programming
100.0% Programming
0.00Hz
Programming
60.0 sec Programming
0.0 sec Programming
0
0
0
Programming
Programming
Programming
Programming
YASKAWA TM.iQp.10 Technical Manual Supplement 85
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description z P9-50
<0034>
P9-50
<0035>
P9-99
<0036>
0878
0878
0875
Water Level Source
Water Lvl Source
Suction Pressure Source
Suction Pres Src
Network Compatibility
Selection
Network Comp Sel
Defines which signal to use for Water Level Control (P8 ) when P1-01
= 3.
0: Analog Only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01 ≠ 3
Defines which signal to use for Suction Pressure Control (P8 ) when
P1-01 = 3.
0: Analog Only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01 ≠ 3
Determines the communication compatibility for the iQpump Memobus
Network
0: A-Version 30034
Use this mode if (ONE or MORE) iQpump Controllers on the network have software version monitor U1-14=30034 and nameplate PRG: 0034.
1: B-Version 30035+
Use this mode if (NONE) of the iQpump Controllers on the network have software version monitor U1-14=30034 and nameplate PRG: 0034.
Auto-Tuning
T1-02 0702
Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kW.
Note: T1-02 should be left at the default value (last 3 digits of the drive model number).
T1-04 0704
Motor Rated Current
Rated Current
Sets the motor rated current. (Used only during an auto-tune.)
Denotes that parameter can be changed when the drive is running.
Setting
Range
0 ~ 3
0 ~ 3
0 ~ 1
0.00 ~
650.0
kVA
Dependent
Factory
Setting
0
0
1
Menu
Location
Programming
Programming
Programming kVA
Dependent
Auto-Tuning kVA
Dependent
Auto-Tuning
86 YASKAWA TM.iQp.10 Technical Manual Supplement
Monitor List
Parameter No.
U1-01
U1-02
U1-03
U1-06
U1-07
U1-08
U1-10
U1-11
0040
0041
0042
0045
0046
0047
Addr.
Hex
0049
004A
Table 2 Monitor List
Parameter Name Digital
Operator Display
Description
Monitor
Auto Set-point Reference (speed command) monitor when in auto mode, frequency reference
(speed command) setting location when in hand mode. Units changeable via P1-02.
Auto Set-point Reference
Auto: Set-point
Output Frequency
Output Freq
Output Current
Output Current
Output Voltage
Output Voltage
DC Bus Voltage
DC Bus Voltage
Output Power
Output kWatts
Output frequency monitor in Hz.
Output current monitor.
Displays drive output voltage.
Displays DC bus voltage.
Displays drive output power.
Input Terminal Status
Input Term Sts
Output Terminal Status
Output Term Sts
Displays drive input terminal status.
0 0 0 0 0 0 0 0
1: FWD. run
(Terminal S1) is ON.
1: REV. run
(Terminal S2) is ON.
1: Multi-function input 1
(Terminal S3) is ON.
1: Multi-function input 2
(Terminal S4) is ON.
1: Multi-function input 3
(Terminal S5) is ON.
1: Multi-function input 4
(Terminal S6) is ON.
1: Multi-function input 5
(Terminal S7) is ON.
Output terminal ON/OFF check.
0 0 0 0 0 0 0 0
1: Multi-function Contact 1 output 1 (Terminal M1-M2) is
ON.
1:Multi-function Contact 2 output 1 (Terminal M3-M4) is
ON.
Not used
Not used
1:Fault output
(Terminal MA/MB-MC) is
ON.
U1-12
U1-13
U1-14
U1-15
004B
004C
004D
004E
Drive Operation Status
Int Ctl Sts 1
Cumulative Operation Time
Elapsed Time
Software Number
FLASH ID
Terminal A1 Input Voltage
Term A1 Leve l
0 0 0 0 0 0 0 0
1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Drive operation ready
1: During fault detection
(Minor fault)
1: During fault detection
(Major fault)
Displays total operating or power-on time of the drive.
Displays drive's software number.
Displays the input voltage on Terminal A1, as a percentage of 10 Vdc.
YASKAWA TM.iQp.10 Technical Manual Supplement 87
88
U1-16
U1-18
U1-20
U1-34
U1-36
U1-37
U1-38
U1-24
U1-28
U1-29
U1-30
Parameter No.
U1-39
U1-40
U1-62
U1-67
U1-68
U1-80
<0035>
U1-90
0061
0063
0064
0065
0057
005B
005C
005D
Addr.
Hex
004F
0051
0053
Parameter Name Digital
Operator Display
Description
Monitor
Terminal A2 Input Voltage
Term A2 level
Motor Secondary Current (Iq)
Mot SEC Current
Output Frequency After Soft
Start
SFS Output
PI Feedback Value
PI Feedback
CPU Number
CPU ID kWh kWh Lo 4 Digits
MWh kWh Hi 5 Digits
First Parameter Causing an OPE
OPE Detected
PI Input
PI Input
PI Output
PI Output
PI Set-point
PI Set-point
Displays the input current (or voltage) on Terminal A2, as a percentage of 20 mA (or 10 Vdc).
Displays the amount of current being used by the motor to produce torque (Iq).
Displays the frequency reference (speed command) after the accel and decel ramps.
Displays the feedback signal when PI control is used.
Displays control board hardware revision.
Displays the accumulated kWh.
Displays the accumulated MWh.
Displays the parameter number causing an “OPE” fault.
Displays the “error” in the PI regulator. (U1-36 = PI Set-point - PI Feedback).
Displays the output of the PI as a percentage of maximum frequency (E1-04).
Displays the setpoint of the PI regulator (U1-38 = PI reference + PI bias).
0066
0067
007D
009B
0009C
009Dh
0720
Memobus Communication Error
Code
Transmit Err
0 0 0 0 0 0 0 0
1: CRC error
1: Data length error
Not used. Always 0.
1: Parity error
1: Overrun error
1: Framing error
1: Timeover
Not used. Always 0 .
Heatsink Cooling Fan Operation
Time
FAN Elapsed Time
Running Queue No
Running Queue No
Displays total operating time of the heatsink cooling fan.
Position in the iQpump Memobus Multiplex Running Queue
Network Activity
Network Activity
Shows network traffic. A fluctuating number from 0 to 1000 denotes activity, while a relatively constant 0 denotes no activity.
Unit changes based on network status:
<->: Drive can not communicate to other drives
<+>: Drive is a Node on a network
<M>: Drive is a Master on an iQpump Network
Time to Alternate
Time to Alternate
Time remaining before a drive requests alternation which is dependent on P9-04.
Geothermal Temperature Input
Geothermal Temp
Geothermal temperature input after the gain and bias has been applied. This is the temperature used by the Geothermal Function to determine what frequency to run the drive.
Internally limited to -999.9°F and 999.9°F.
Only shown when B1-05 = 5
Units 0.1°F
Pump Set-point
Pump Set-point
Displays drive setpoint.
Resolution 0.1
Note: Does not include setpoint compensation (U1-93).
YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter No.
U1-91
U1-92
Addr.
Hex
Parameter Name Digital
Operator Display
0721
0722
Pump Feedback
Pump Feedback
Pump Status
Pump Status
Description
Monitor
Displays scaled feedback.
Resolution 0.1
Display pump running status.
0 0 0 0 0 0 0 0
1: Drive (Pump 1)
1: Pump 2 on
1: Pump 3 on
Not used. Always 0.
U1-93
U1-94
U1-95 z U1-98
723
Total Set-point Compensation
Total SP Comp.
Displays total absolute setpoint compensation.
Resolution 1.
724
Motor Speed
Motor Speed
Displays motor speed (rpm).
Used for no-flow detection (P2 Group).
725
Flow Rate
Flow Rate
U1-96 72A
Volume Accumulated
(fine)
Volume (fine)
U1-97 72B
Volume Accumulated
(course)
Volume (course) z Applies when P8-01 = 0 or 1
Applies when P8-01 = 2
72C
Water Level
Water Level
Displays the flow rate, based upon the voltage present on Terminal A1 and parameters P6-01 and P6-02. A two second 1st order filter will be applied to this monitor.
Displays the volume that has been measured by Terminal A1. Total volume can be calculated as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.
Displays the volume that has been measured by Terminal A1. Total volume can be calculated as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.
Displays the amount of water above the water level sensor.
U1-98
<0035>
U1-99
72C
Water Level
Suction Pressure
72D
Anti-No-Flow Timer
ANF Timer
Displays the amount of suction pressure.
When this value reaches the P2-24 setting, the Anti-No-Flow feature begins to reduce the output frequency.
YASKAWA TM.iQp.10 Technical Manual Supplement 89
Fault Trace List
Table 3 Fault Trace List
Parameter No.
Addr.
Hex
Fault Trace
U2-01
U2-02
U2-03
U2-04
U2-05
U2-07
U2-08
U2-09
0080
0081
0082
0083
0084
0086
0087
0088
Current Fault
Current Fault
Previous Fault
Last Fault
Frequency Reference at Most Recent Fault
Frequency Ref
Output Frequency at Most Recent Fault
Output Freq
Output Current at Most Recent Fault
Output Current
Output Voltage at Most Recent Fault
Output Voltage
DC Bus Voltage at Most Recent Fault
DC Bus Voltage
Output Power at Most Recent Fault
Output kWatts
U2-11
U2-12
008A
008B
Input Terminal Status at Most Recent Fault. The format is the same as for U1-10.
Input Term Sts
Output Terminal Status at Most Recent Fault. The format is the same as for U1-11.
Output Term Sts
U2-13 008C
Drive Operation Status at Most Recent Fault. The format is the same as for U1-12.
Inverter Status
U2-14 008D
Cumulative Operation Time at Most Recent Fault
Elapsed time
Note: Fault trace is not executed at CPF00, CPF01, CPF03, UVI and UV2.
90 YASKAWA TM.iQp.10 Technical Manual Supplement
Fault History List
Table 4 Fault History List
Parameter No.
Addr.
Hex
Fault History
U3-01
U3-02
U3-03
U3-04
U3-05
U3-06
U3-07
U3-08
U3-09
U3-10
U3-11
U3-12
U3-13
U3-14
U3-15
U3-16
0090
0091
0092
0093
0094
0095
009B
0097
0804
0805
0806
0807
0808
0809
080E
080F
Most Recent Fault
Last Fault
2nd Most Recent Fault
Fault Message 2
3rd Most Recent Fault
Fault Message 3
4th Most Recent Fault
Fault Message 4
Cumulative Operation Time at Most Recent Fault
Elapsed Time 1
Cumulative Operation Time at 2nd Most Recent Fault
Elapsed Time 2
Cumulative Operation Time at 3rd Most Recent Fault
Elapsed Time 3
Cumulative Operation Time at 4th Most Recent Fault
Elapsed Time 4
5th Most Recent Fault
Fault Message 5
6th Most Recent Fault
Fault Message 6
7th Most Recent Fault
Fault Message 7
8th Most Recent Fault
Fault Message 8
9th Most Recent Fault
Fault Message 9
10th Most Recent Fault
Fault Message 10
Cumulative Operation Time at 5th Most Recent Fault
Elapsed Time 5
Cumulative Operation Time at 6th Most Recent Fault
Elapsed Time 6
U3-17
U3-18
0810
0811
Cumulative Operation Time at 7th Most Recent Fault
Elapsed Time 7
Cumulative Operation Time at 8th Most Recent Fault
Elapsed Time 8
U3-19 0812
Cumulative Operation Time at 9th Most Recent Fault
Elapsed Time 9
U3-20 0813
Cumulative Operation Time at 10th Most Recent Fault
Elapsed Time 10
Note: Faults such as CPF00, CPF01, CPF02, CPF03, UV1, and UV02 are not stored in fault history.
YASKAWA TM.iQp.10 Technical Manual Supplement 91
92
47
48
49
50
44
45
46
38
39
40
41
42
43
32
33
34
35
36
37
26
27
28
29
30
31
20
21
22
23
24
25
14
15
16
17
18
19
8
9
10
11
12
13
Decimal
1
2
3
6
7
4
5
Table 5 Decimal to Hex Conversion
2F
30
31
32
2C
2D
2E
29
2A
2B
26
27
28
20
21
22
23
24
25
1A
1B
1C
1D
1E
1F
14
15
16
17
18
19
E
F
10
11
12
13
8
9
A
B
C
D
6
7
4
5
Hex
1
2
3
97
98
99
100
94
95
96
88
89
90
91
92
93
82
83
84
85
86
87
76
77
78
79
80
81
70
71
72
73
74
75
64
65
66
67
68
69
58
59
60
61
62
63
Decimal
51
52
53
54
55
56
57
61
62
63
64
5E
5F
60
58
59
5A
5B
5C
5D
52
53
54
55
56
57
4C
4D
4E
4F
50
51
49
4A
4B
46
47
48
40
41
42
43
44
45
3A
3B
3C
3D
3E
3F
36
37
38
39
Hex
33
34
35
YASKAWA TM.iQp.10 Technical Manual Supplement
YASKAWA TM.iQp.10 Technical Manual Supplement 93
YASKAWA iQpump
Intelligent Pump Controller
Manual Supplement
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: (800) YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310 http://www.yaskawa.com
YASKAWA AMERICA, INC
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.