Yaskawa PS5 Drive Manual
Advertisement
Advertisement
VS-616PS5 Series
Installation & Quick-start Manual
Brushless Motor Drive
WARNING
YASKAWA manufactures component parts that can be used in a wide variety of industrial applications.
The selection and application of YASKAWA products remains the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design.
Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All products designed to incorporate a component part manufactured by YASKAWA must be supplied to the end user with appropriate warnings and instructions as to that part’s safe use and operation. Any warnings provided by YASKAWA must be promptly provided to the end user.
YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and specifications published in YASKAWA’s manual. NO OTHER WARRANTY, EXPRESS OR
IMPLIED, IS OFFERED. YASKAWA assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
READ THIS ENTIRE MANUAL BEFORE INSTALLING OR OPERATING THE VS-616PS5!
WARNING!
The PS5 motor uses permanent magnets. HIGH VOLTAGE is generated by the motor whenever the rotor is turning, with or without a power supply. Make sure the motor is not turning before performing ANY service on the motor or on the inverter.
If there is a possibility that the motor can be turned by the load while inverter power is off, install a contactor or a manual disconnect to open the motor leads while servicing the inverter. Interlock the disconnect with the control circuits of the drive.
ONLY PERSONNEL WHO ARE EXPERIENCED IN WORKING WITH HIGH VOLTAGE, HIGH
POWER EQUIPMENT SHOULD INSTALL OR SERVICE THIS EQUIPMENT.
Turn off the supply power to the VS-616PS5 AND make sure the motor is stopped AND the internal capacitors are discharged before connecting or disconnecting wires or touching any internal parts.
The VS-616PS5 internal capacitors remain charged even after the power supply is turned off. Wait at least five minutes after removing power. Make sure all LED’s are off before servicing the inverter.
Do not use a Megger or other type of high withstand voltage tester on the VS-616PS5. Higher voltages can damage the semiconductors used in the inverter.
Do not connect or disconnect the operator or a computer while the VS-616PS5 is running.
FAILURE TO OBSERVE THE WARNINGS AND PRECAUTIONS IN THIS MANUAL CAN EXPOSE THE USER TO HIGH
VOLTAGES, RESULTING IN DAMAGE TO EQUIPMENT, SERIOUS PERSONAL INJURY, OR EVEN DEATH.
POWER SUPPLY LIMITATIONS
The VS-616PS5 is suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes at 480 VAC maximum (for 460 VAC class units) or 240 VAC maximum (for 230 VAC class units).
2
The information contained within this document is the proprietary property of Yaskawa Electric America, Inc.
This information may not be copied, reproduced, or transmitted to other parties without the expressed written authorization of Yaskawa Electric America, Inc.
No patent liability is assumed with respect to the use of the information contained herein.
Yaskawa is constantly improving its high-quality products. The information contained in this manual is subject to change without notice.
Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
General Connection Diagram (3 Wire Control W/Standard Hall Sensor Fdbk)
Supply Power
User Supplied
Disconnect
*
STOP
START
FWD REV
EMER STOP
MAINTAINED
CONTACT
3
4
1
2
5
6
7
8
L1
L2
L3
E
VS-616PS5
Rev.C
T1
T2
T3
2
3
+12VDC
COM
T2
T1
T3
Brushless
Motor
Hall Effect
Encoder
Red
Black
1 2 3 4 5 6 7 8 9 10
HS1
HS2
HS3
HS4
HS5
Brown
Orange
Yellow
Green
Blue
11
* For this configuration, set parameter A1-03 =3330 prior to programming the inverter settings. This action re-initializes the inverter settings and configures the inverter for 3-wire control (as shown above).
If the inverter settings have already been programmed, setting parameter H1-01=0 configures the inverter for 3 -wire control without re-initializing the parameter settings.
The terminal layout shown on the PG-P2 Encoder Feedback Card applies to Revision C boards (Rev CO).
3
4
Example of Quick Start Motor Data Entry (See page 35 for complete explanation)
Parameter
E1-01
E1-02
E1-03
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-13
E1-17
F1-01
F8-01
Name
Input Voltage Setting
Motor Capacity
Rated Motor Voltage
Motor Rated Current
Number of Poles
Motor Maximum Speed
Description
Set equal to the input supply voltage in VAC RMS
Set to 1000 for manual entry of the following “E1” parameters
Set to 230 for motors with 320VDC BUS on the nameplate
Set to 460 for motors with 640VDC BUS on the nameplate
Enter the motor nameplate full load current in AC Amps RMS
Set for the number of poles in motor (even number)
Set to the maximum speed desired being sure not to exceed the
Base Motor Speed
Minimum Motor Speed motor maximum RPM
Set to nameplate base speed of the motor in RPM
Set to the Minimum Motor Speed
Motor Winding Resistance Set to line to line winding resistance in ohms
Motor d-axis Inductance
Motor q-axis Inductance
Set to Stator Inductance in millihenries
Set equal to E1-10
Induced Voltage Constant Set to motor Generated voltage KV in VAC RMS (V/1000 RPM)
Motor Connection Set to 0 = 1D, 1 = 2D, 2 = 1Y, 3 = 2Y
PG Feedback Rate
Speed Feedback Source
Set to number of pulses in one encoder speed channel (PPR)
Set to “1” for Hall Sensors, set to “0” for encoder feedback
Example
230
1000
230
9.6
4
1750
1750
30
0.102
5.45
5.45
176.0
0
30
01
Personnel who are experienced in the use of VS-616PS5 inverters and motors may use this procedure.
NOTE: Do not use this procedure if the inverter has been programmed for a particular application by an Original
Equipment Manufacturer or if the inverter has already been programmed for your application.
1. Remove the Digital Operator and cover from the inverter before installation (section 1.1).
2. Mount the inverter in a clean, dry location with adequate airflow for cooling (sections 2.1 and 2.2).
3. Connect the proper supply power through an approved power disconnect device to the input terminals (see section
3.2). Make sure the disconnecting device is off.
4. Connect the motor leads T1, T2, and T3 to their respective terminals on the drive. Connect a ground wire between the motor frame and the drive (see section 3.3).
5. Connect the proper motor feedback device. Make sure the feedback device is the correct one for the feedback card
(i.e., hall effect device, commutation encoder, or resolver). See section 3.4 and Appendix C. Connect the control circuits according to the drawing generated for the installation. A typical installation with hall sensor feedback to the PG-
P2 feedback card is shown on page 3, but the circuits will vary for each installation. Some installations may use only the digital operator. For guidance, see section 3.5.
6. Check input power connections, motor connections, and feedback wiring for unintentional grounds.
7. Re-install the cover and the Digital Operator.
8. Check the supply power to be sure it is correct for the unit installed.
9. Apply power by turning on the disconnecting device. Watch for lights on the digital operator to turn on. If no lights or indicators turn on within 30 seconds, turn power off and connect a DC voltmeter to the bus terminals (+ and -). Reapply power and watch for DC voltage (340 VDC for 230VAC, or 640 VDC for 460VAC). If no voltage appears, disconnect any braking resistors and check incoming fuses.
10. After the inverter powers up, press the DRIVE/PRGM button on the digital operator to access parameter A1-01. If it is set to “0000” or “0001”, stop using this procedure and consult with your equipment manufacturer for start up procedures. Otherwise, set parameter A1-01 to “0002” (Quick Start Level). If you need help in operating the Digital Operator, read section 4.2 on pages 28 and 29.
11. If the control circuits use momentary START and STOP operators (3-wire operation) connected as shown on page 2, set parameter A1-03 to “3330” and press the “DATA/ENTER” button. This sets the inverter for start/stop control circuit operation and sets all other parameters to the factory defaults. If the inverter is being used in a system with maintained relay contacts or switches, enter “2220” in A1-01. Again, this sets all parameters to factory defaults. If the inverter settings have already been programmed, setting parameter H1-01=0 configures the inverter for 3- Wire control without reinitializing the parameter settings. Setting H1-01 to a value other than “0” configures the inverter for 2- Wire control.
12. Verify that the Emergency Stop button (or some type of emergency shutdown) is installed properly. See page 2 for a typical installation. This is a normally open, maintained contact (push ON / pull OFF) button connected to terminal 8 provided parameter H1-06 is programmed to a value of “8”(Normally open external baseblock). It should be used to shut off the inverter quickly if that action becomes necessary. If the Emergency Stop circuit is activated, press the inverter STOP button before resetting the emergency stop circuit.
13. Set parameters B1-01 and B1-02 to “0”. This enables operation from the digital operator.
14. Set parameter B1-03 to “1”. This causes the motor to coast to a stop (inverter off) on all stops.
15. Defaults for acceleration (C1-01) and deceleration (C1-02) are 10.0 seconds. These may be changed.
16. Preset references D1-01 through D1-04 and Jog reference D1-09 may be set.
17. Set parameter E1-01 to the input line AC RMS voltage (example: 230).
18. Enter the motor data. Enter the number “1000” for E1-02 and manually enter the motor parameters as shown in the table on page 4.
19. Make sure the motor is disconnected from the load and that it is safe to run the motor.
20. Set T1-03 to “1” and then, set T1-02 to 2”. Press the DRIVE/PROG key. The display should show “CAL12”. Press the
RUN button on the digital operator. The motor should turn, and the display should blink, as the pulse generator is oriented to the drive. When the orientation is finished, the display will show “End”. If the display shows “Er-18” or “Zdev”, check the connections to the motor and feedback.
21. Once the drive has finished orienting the feedback, you can run the test run on page 6.
5
Operation Plan for Test Run
1 2 3 4 5 6 7
POWER
ON
FWD JOG
RUN
SET
SPEED
FWD
RUN
SET
SPEED
REV
RUN
STOP
1
2
3
Description
Power ON
Ÿ Displays Frequency
Reference Value
Operation Source
Ÿ Select LOCAL Mode
Set JOG Reference
Ÿ
Set D1-09 to 10.00%
Ÿ
Forward Jog Run
Runs at JOG speed while key is pressed.
Speed Setting
Ÿ
Change Speed Reference
Value
4
5
Ÿ ENTER the new value
Ÿ Select Speed display
Forward RUN
Ÿ Press RUN on operator
Change Speed Reference
Ÿ Select reference display
Ÿ Change Reference value
6
Ÿ ENTER the new value
Ÿ Select Speed display
Reverse RUN
Ÿ Press Reverse
7 Stop
Ÿ Press Stop Button
Key Sequence
LOCAL
REMOTE
JOG
Change value with arrow keys
DATA
ENTER
DISPL
RUN
RUN LED ON
DISPL
Change value with arrow keys
DATA
ENTER
DISPL
FWD
REV
STOP
Digital Operator Display
P 0 0.
0 0
REMOTE LED OFF
FWD LED ON
1 0.
0 0
P 0 0.
0 0
Digit to be changed blinks
P 2 5.
0 0
0 0.
0 0
2 5.
0 0
P 2 5.
0 0
Digit to be changed blinks
P 1 0 0.
0
P 1 0 0.
0
1 0 0.
0
1 0 0.
0
0 0 0.
0
Once this test run is completed, the inverter and motor are ready for service.
6
The Model VS-616PS5 is a series of high quality, general purpose, inverters designed to control the current in a permanent magnet (PM) brushless motor. In the PM motor, current is directly related to torque.
With power outputs ranging from 0.5 to 500 horsepower (HP), the VS-616PS5 series is suitable for any application. The inverters provide full start-up torque, smooth low speed operation, and precise speed control from zero to full speed. The proprietary auto-tuning function allows the inverters to get the best performance from PM motors manufactured worldwide.
Some of Yaskawa’s proprietary features of the VS-616PS5 inverter include torque control, automatic tuning to the motor characteristics, UL recognized electronic thermal motor overload, energy saving operation, PID loop control, and low noise operation. Also standard is a digital operator for simple programming. The design team has used the latest in microprocessor technology to produce the ultimate drive for any application.
This manual details installation, start-up, and diagnostic procedures for the PS5 series. For more details on programming, request the VS-616PS5 Programming manual (publication number YEA-TOA-S616-10.21) from your Yaskawa representative.
QUICK START ...................................................................................................... 4
1.
PREPARATION ..................................................................................................... 9
1.1
1.2
Inspection ................................................................................................ 9
Specifications ........................................................................................ 11
2.
INSTALLATION ................................................................................................... 13
2.1
Mounting Considerations ...................................................................... 13
2.2
2.3
Thermal Considerations ........................................................................ 14
Dimensions ........................................................................................... 15
3.
WIRING .............................................................................................................. 17
3.1
Wiring Considerations ........................................................................... 17
3.2
3.3
Connecting Supply Power ..................................................................... 19
Connecting the Motor ............................................................................ 20
3.4
3.5
Connecting the Feedback ..................................................................... 21
Connecting Control Circuits .................................................................. 24
3.6
Connecting Resistor Braking Units ....................................................... 26
4.
INITIAL OPERATION .......................................................................................... 27
4.1
4.2
4.3
4.4
Operational Concerns .......................................................................... 27
Digital Operator ..................................................................................... 28
Entering Initial Data ............................................................................... 30
Initial Operation by Digital Operator ...................................................... 31
4.5
Initial Operation by Control Circuits....................................................... 32
5.
PROGRAMMING................................................................................................. 33
5.1
5.2
Initializing .............................................................................................. 33
Quick Start Programming ...................................................................... 35
5.3
Basic Programming ............................................................................... 46
6.
DIAGNOSTICS .................................................................................................... 63
6.1
6.2
Precautions ........................................................................................... 63
Maintenance and Inspection ................................................................. 64
6.3
Alarm and Fault Displays ...................................................................... 65
7.
APPENDICES ................................................................................... After page 70
A.
B.
C.
D.
Wiring Tables .......................................................................................A.1
Motor Set-up ........................................................................................B.1
PG Feedback Connection Diagram .................................................... C.1
Parameter List ..................................................................................... D.1
7
This page left intentionally blank.
8
1.1 Inspection ................................................................................................. 9
Receiving ................................................................................................. 9
Checking the Nameplate .......................................................................... 9
Identifying the Parts ............................................................................... 10
Removing the Digital Operator ............................................................... 10
Removing the Cover .............................................................................. 10
1.2 Specifications ......................................................................................... 11
230 VAC Units 0.5 thru 20 HP ............................................................... 11
460 VAC Units 0.5 thru 25 HP ............................................................... 11
460 VAC Units 30 thru 500 HP .............................................................. 11
General Specifications ........................................................................... 12
1.1 Inspection
Receiving
After unpacking the VS-616PS5:
• Verify that the part numbers on the drive nameplate match the part numbers on your packing slip and the parts numbers on your purchase order.
• Check the unit for physical damage that may have occurred during shipping. If any part of the drive is damaged, notify the freight carrier and your Yaskawa representative immediately.
• Inspect the drive to determine if any parts have come loose during shipment. Check the screws, covers, components, etc. for tightness.
• If the drive is to be stored after you receive it, replace the unit in its original packaging and store it in an appropriate environment (see specifications, page 10). Storage instructions are also included in the original packaging or on the shipping container.
Checking the Nameplate
Inverter Model
Input Spec
Output Spec
Lot Number
Serial Number
UL File Number
MODEL:
INPUT:
CIMR - PS5U43P7 SPEC: 43P71A
AC 3PH 380-440V 50 Hz
380-460V 60 Hz
10.2 A
AC 3PH 0-460V 6.1 kVA 8.5 A OUTPUT:
LOT NO:
SER NO:
UL FILE NO: E131457
MASS: 4.5 kg
Mg
Figure 1 Nameplate Example
Inverter Spec
Weight
CIMR
Inverter
VS-616PS5 Series
U = American Series
Voltage Class
2 = 230VAC 3Ø
4 = 460 VAC 3Ø
PS5 U 4 3P7
Figure 2 Nameplate Description
1 A
Model Designation
See specifications
Revision Symbol
Enclosure
0 = Open Chassis
1 = NEMA 1 (IP20)
VS-616PS5 Installation & Quick Start Manual 9
Identifying the Parts
Figure 3 Parts Identification- Model CIMR-PS5U43P7
Removing the Digital Operator
To remove the digital operator from the unit:
• Push the operator retaining lever in the direction shown by arrow 1
• Lift the digital operator in the direction shown by arrow 2
²
Figure 4 Removal of the operator
Removing the Cover
YOU MUST REMOVE THE DIGITAL OPERATOR
BEFORE REMOVING THE COVER.
• Squeeze the cover on both sides in the directions shown by arrows 2
• Lift the cover in the direction shown by arrow 3.
10
²
Figure 5 Removal of the inverter cover
VS-616PS5 Installation & Quick Start Manual
1.2 Specifications
The Rated Current of the inverter must be equal to or greater than the Rated Current of the motor, regardless of the nominal horsepower ratings.
230 VAC Units 0.5 thru 20 HP
Inverter Model
CIMR-PS5U
20P4
Output Characteristics
Motor HP (NEMA)
Capacity (KVA)
Rated Current (AAC)
Maximum Voltage
Rated Frequency
Overload Capacity
Power Supply Characteristics
Input Current (AAC)
Rated Voltage, Tolerance
Rated Frequency, Tolerance
0.5
1.2
3.2
3.9
460 VAC Units 0.5 thru 30 HP
20P7
1
2.3
6
7.2
VS-616PS5
21P5 22P2 23P7 25P5
13.2
21 30
3-phase, 200VAC to 230VAC, +/- 10%
50/60 Hertz +/- 5%
27P5
2 3 5 7.5
10
3.0
8
402
11
6.7
17.5
9.5
25
13
33
200VAC to 230VAC, 3 phase (proportional to input voltage)
200 Hertz maximum
150% rated current for 1 minute
9.6
40
2011
15
19
49
59
2015
20
24
64
77
Inverter Model
CIMR-PS5U
VS-616PS5
40P4 40P7 41P5 42P2 43P7
Output Characteristics
Motor HP (NEMA)
Capacity (KVA)
Rated Current (AAC)
Maximum Voltage
Rated Frequency
Overload Capacity
0.5
1.4
1.9
Power Supply Characteristics
Input Current (AAC)
2.3
Rated Voltage,
Rated Frequency
1
2.6
3.6
4.3
2
3.7
5.1
6.1
3
4.7
6.6
8
5
6.1
8.5
200 Hertz maximum
150% rated current for 1 minute
10.2
44P0
7.5
8.4
11.7
14
45P5
10
11
14.8
17.8
26
3-phase, 380VAC to 460VAC +/- 10%
50/60 Hertz +/- 5%
47P5
15
16
21
4011
20
21
28.6
380VAC to 460VAC, 3 phase (proportional to input voltage)
35
460 VAC Units 40 thru 500 HP
4015
25
26
34
4018
30
31
41
40 46
Inverter Model
CIMR-PS5U
4022
Output Characteristics
Motor HP (NEMA)
Capacity (KVA)
Rated Current (AAC)
Maximum Voltage
Rated Frequency
Overload Capacity
40
40
52
Power Supply Characteristics
Input Current (AAC) 58
Rated Voltage,
Rated Frequency
4030
50
50
65
72
VS-616PS5 Installation & Quick Start Manual
4037
88
4045 4055
VS-616PS5
4075 4110
106 141 182 247 330
3-phase, 380VAC to 460VAC +/- 10%
50/60 Hertz +/- 5%
4160 4185
60
61
75
73
100
98
125
130
150
170
200
230
250
260
80 96 128 165 224 302 340
380VAC to 460VAC, 3 phase (proportional to input voltage)
200 Hertz maximum
150% rated current for 1 minute
408
4220
350
340
450
4300
500
460
605
540 726
11
General Specifications
Control Characteristics
Control Method
Starting Torque
Speed Control Range
Speed Control Accuracy
Torque Limit
Frequency Control Range
Frequency Accuracy
Frequency Setting Resolution
Output Frequency Resolution
Frequency Setting Signals
Accel/Decel Time Setting
Braking Torque
Protection Functions
Motor Overload Protection
Instantaneous Overcurrent
Fuse Protection
Overload
Overvoltage
Undervoltage
Momentary Power Loss
Heatsink Overheat
Ground Fault
Power Charge Indicator
Phase Loss
Sine Wave PWM, Flux Vector
150% at 1% speed
100 : 1 (Constant Power Excluded)
+/- 0.02%
Independent Quadrant Settings 0 - 300%
0.1 to 200 Hertz
Analog Speed Command 0.1% Digital Speed Command 0.01%
Digital Operator: 0.01 Hertz
Analog Reference: 0.03 Hertz @ 60 Hz
0.01 Hertz
0 to +10 VDC (20 Kohm)
0 to +/-10 VDC (20 Kohm)
4 to 20 mA (250 ohm)
0 to 6000.0 seconds, independent ramps
Approximately 100% with optional resistor braking
UL Recognized Electronic Thermal Overload
200% rated current, motor coasts to stop
Motor coasts to stop when fuse blows
Motor shuts off after 150% for 1 minute
410 VDC (230VAC units) 820 VDC (460 VAC units)
User adjustable value
TRIP after 15 ms continuous power loss
Thermistor Protection
Electronic Overcurrent circuit
Charge LED ON above 50 VDC bus voltage
Input/Output selectable power protection
Environmental Specifications
Location
Ambient Temperature
Storage Temperature
Humidity
Vibration
Indoors, clean and dry
Open Chassis: +14 to 113 °F (-10 to 45 °C)
NEMA 1: +14 to 104 °F (-10 to 40 °C)
-4 to 140 °F (-20 to 60 °C)
95% Relative Humidity, non-condensing
9.8 m/sec
2
(1G), less than 20 Hz // 1.96 m/sec
2
(0.2G) @ 20 to 50 Hz
12 VS-616PS5 Installation & Quick Start Manual
2.1
Mounting Considerations .................................................................... 13
Precautions......................................................................................... 13
Choosing a Location ........................................................................... 13
2.2
Thermal Considerations...................................................................... 14
Clearances.......................................................................................... 14
2.3
Dimensions ......................................................................................... 15
Open Chassis Dimensions and Heat Loss ......................................... 15
NEMA 1 Dimensions ........................................................................... 16
2.1 Mounting Considerations
Precautions
Observe these precautions to avoid damage to the equipment:
• Do NOT lift the VS-616PS5 by its cover, which may come loose. Handle the inverter unit only by its base.
• Do not mount the inverter on flammable material.
• Mount the inverter in a vertical orientation (fins vertical) to promote cooling. See the section below on clearances.
• The ambient temperature in an enclosure must be kept below 113 °F (45 °C). Install fans and enclosure cooling as necessary.
Choosing a location
Be sure that the inverter is mounted in a location protected against the following conditions:
• Extreme heat or cold. Refer to the ambient temperature conditions on page 12.
• Direct sunlight. The inverter is not designed for outdoor use.
• Rain or excessive moisture.
• High humidity.
• Oil sprays or splashes.
• Salt spray.
• Dust or metallic particles in the air.
• Corrosive gases or liquids.
• Radioactive substances.
• Combustible solids, liquids, or gases.
• Severe physical shocks or vibrations. Refer to the vibration specs on page 12.
• Magnetic noise (e.g., welding machines and other large magnetic power devices).
VS-616PS5 Installation & Quick Start Manual 13
2.2 Thermal Considerations
Clearances
When mounting the VS-616PS5, allow sufficient clearances for effective cooling as shown below:
1.97in (50mm)
4.72in (120mm)
Air
1.18in (30mm)
1.97in (50mm)
Front View
4.72in (120mm)
Air
Side View
NOTES:
1. Required clearances at the top, bottom, and sides of the inverter apply to both open chassis and
NEMA 1 enclosed models.
2. When inverter models 25 HP or less are mounted in an enclosure, remove the top and bottom covers to convert NEMA 1 units to open chassis.
3. Allowable ambient air temperature around the inverter must be within the “Ambient Temperature” limits in the specifications on page 12.
4. Temperatures in the enclosure may not exceed the ambient temperature ratings.
14 VS-616PS5 Installation & Quick Start Manual
2.3 Dimensions and Heat Loss
Open Chassis Type (IP00)
Note: All units up to model CIMR-PSU4045 are stocked and shipped as NEMA1 units.
Voltage
230V
460V
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
4022
Model
CIMRW
Open Chassis Dimensions in inches (mm)
H D W1 H1 H2
Mass
Lbs (kg)
Heat loss (W)
Heat Inside Total
Sink Unit PSU
20P4
20P7
21P5
2011
2015
40P4
40P7
41P5
5.51 (140) 11.02 (280) 6.30 (160) 4.96 (126) 10.47 (266)
5.51 (140) 11.02 (280 6.30 (160) 4.96 (126) 10.47 (266)
0.28(7)
22P2 5.51 (140) 11.02 (280) 7.09(180) 4.96 (126) 10.47 (266) 0.28 (7)
23P7
25P5 7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8)
27P5
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5)
0.28 (7)
6.5(3)
10 (4.5)
24 (11)
6.5 (3)
8.8 (4)
15
25
40
80
135
50
65
80
60
80
12 (5.5) 210
13 (6) 235
90
110
425 160
525 200
10
20
30
50
65
80
585
725
60
85
110
65
90
120
140
215
300
345
5.51 (140) 11.02 (280) 7.09 (180) 4.96 (126) 10.47 (266) 0.28 (7)
7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.30 (7.5)
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5)
12.80 (325) 24.02 (610) 11.22 (285) 10.83 (275) 17.13 (435) 3.44 (87.5)
10 (4.5)
13 (6)
24 (11)
60 (27)
65
80
120
135
240
305
390
465
620
60
65
80
85
120
150
180
195
260
360
455
570
660
880
125
145
200
220
4030
4037
4045
4010
12.80 (325) 24.61(625) 11.22 (285) 10.83 (275) 24.02 (610) 0.30 (7.5) 97 (44)
705 315 1020
875 370 1245
970 415 1385
1110 710 1820
4055
4075
4160
4185
4220
22.64 (575) 36.42 (925)
14.76 (375)
15.75 (400)
17.52 (445) 35.24 (895) 0.59 (15)
1430 890 2320
298 (135) 1870 1160
3030
320 (145) 2670 1520
4190
17.91 (455) 57.09 (1450) 17.13 (435) 29.53 (750) 55.12(1400) 0.98 (25) 794 (360) 3400
1510
2110
4910
6850
4300 37.80 (960) 62.99 (1600) 17.91 (455) 29.53 (750) 61.02 (1550) 0.98 (25) 926 (420) 6820 2910 9730
VS-616PS5 Installation & Quick Start Manual 15
Enclosed Type NEMA 1 (IP20)
Note: All units up to model CIMR-PSU4045 are stocked and shipped as NEMA1 units.
Voltage
230V
460V
Model
CIMR-
4045
4055
4075
4110
4160
44P0
45P5
47P5
4011
4015
4018
4022
4030
4037
25P5
27P5
2011
2015
40P4
40P7
41P5
42P2
43P7
PSU
20P4
20P7
21P5
22P2
23P7
W
NEMA 1 Dimensions in inches (mm)
H D W1 H1 H2
5.51 (140) 11.02 (280) 6.30 (160) 4.96 (126) 10.47 (266) 0.28(7)
5.51 (140) 11.02 (280) 7.09(180) 4.96 (126) 10.47 (266) 0.28 (7)
7.87 (200) 1.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8)
5.51 (140) 11.02 (280) 6.30 (160) 4.96 (126) 10.47 (266) 0.28 (7)
5.51 (140) 11.02 (280) 7.09 (180) 4.96 (126) 10.47 (266) 0.28 (7)
7.87 (200) 11.81 (300) 8.07 (205) 7.32 (186) 11.22 (285) 0.31 (8)
12.99 (330)
30.91(785)
33.46 (850)
3.44 (87.5)
11.22 (285) 10.83 (275) 24.02 (610)
6.00 (152.5)
22.83 (580) 50.79 (1290)
14.76 (375)
15.75 (400)
17.52 (445) 35.24 (895) 10.63 (270)
Mass
Lbs (kg)
6.5(3)
10 (4.5)
12 (5.5)
13 (6)
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5) 24 (11)
6.5 (3)
8.8 (4)
10 (4.5)
13 (6)
9.84 (250) 14.96 (380) 8.86 (225) 9.29 (236) 14.37 (365) 0.30 (7.5) 24 (11)
12.99 (330) 24.02 (610) 11.22 (285) 10.83 (275) 17.13 (435) 3.44 (87.5) 68 (31)
106 (48)
320 (145)
342 (155)
16
W1
W
Front View
W4
W6
W5
Model CIMR-
PS5U
4185, 4220
4300
W1 W2 W3 W4 W5 W6
29.53
(750)
29.53
(750)
17.32
(440)
17.32
(440)
12.20
(310)
12.20
(310)
33.46
(850)
34.37
(873)
11.22
(285)
11.73
(298)
22.24
(565)
22.64
(575)
D
W2
W1
W3
Side View Models PS5U4185~4300
Figure 7 VS-616PS5 Dimension Diagram
VS-616PS5 Dimension Diagram
VS-616PS5 Installation & Quick Start Manual
3.1 Wiring Considerations ..........................................................................17
Precautions ..........................................................................................17
Inspection .............................................................................................17
Main Circuit Diagrams ..........................................................................18
3.2
Connecting the Supply Power .............................................................19
Input Circuit Requirements...................................................................19
Grounding.............................................................................................19
3.3
Connecting the Motor ...........................................................................20
Output Circuit Considerations...............................................................20
3.4 Connecting the Feedback.....................................................................21
Types of Feedback Device ...................................................................21
Types of Feedback Card ......................................................................21
PG-H2 Hall Sensor Feedback Card ....................................................22
PG-P2 Encoder Feedback Card with Hall Effect Sensors....................22
PG-P2 Encoder Feedback Card with Commutation Encoder...............23
PG-R2 Resolver Feedback Card..........................................................23
3.5 Connecting the Control Circuits ............................................................24
3.6 Connecting Resistor Braking Units .......................................................26
3.1
Wiring Considerations
Precautions
Observe these guidelines to avoid damage to the equipment and/or injury to personnel:
• The National Electric Code (NEC) governs the installation of electrical equipment. The provisions of the NEC and other national, state and local codes must be observed.
• Do not connect or disconnect wiring while power is on.
• Do not connect or disconnect test equipment while the power is on.
• Connect the main power supply ONLY to L1 (R), L2 (S), and L3 (T). DO NOT connect main power supply wiring to output terminals T1, T2, and T3.
• Connect motor power wires to T1 (U), T2 (V), and T3 (W) ONLY.
• Never touch the output circuit directly or place output wires in contact with the inverter enclosure or any metal surface.
• Do not use power correction capacitors on the output of the drive.
• Motor wiring must be less than 328 feet (100 meters) in length.
• Motor wiring must be run in conduit separately from control and signal wires. If there is sensitive equipment in the vicinity of the drive or motor, the conduit must be metallic, properly grounded.
• Control wiring must be less than 164 feet (50 meters) and in separate conduit or cable. Low voltage wiring shall be wired with Class 1 wiring.
Inspection
After wiring is completed and at regular intervals, check:
• that all wiring is correctly installed
• that there are no loose screws or wire clippings inside the drive or enclosure
• that all screws are securely fastened
• that there are no loose strands in contact with other wires or other terminals.
VS-616PS5 Installation & Quick Start Manual 17
Main Circuit Diagrams
PS5U20P4 thru 21P5, PS5U40P4 thru 41P5
(optional reactor)
⊕ 1
⊕ 2
L1
L2
L3
+
B1 B2
T1
T2
T3
Power Supply Control Circuit
PS5U22P2 thru 27P5, PS5U42P2 thru 4015
(optional reactor)
⊕ 1
⊕ 2
L1
L2
L3
+
B1 B2
T1
T2
T3
Power Supply
Cooling Fan
Control Circuit
PS5U2011 thru 2015
(optional reactor)
⊕ 1
⊕ 2
L1
L2
L3
⊕ 3
+
T1
T2
T3
Power Supply
Cooling Fan
Control Circuit
18
PS5U4018 thru 4045
⊕ 1
⊕ 2
L1
L2
L3 r s
⊕ 3
+
Cooling Fan
Power Supply
Internal
Cooling Fan
Control Circuit
T1
T2
T3
L1
L2
L3 r s
200 s
400
PS5U4055 thru 4160
⊕ 3
+
Power Supply
Internal
Cooling Fan
Control Circuit
T1
T2
T3
PS5U4185 thru 4300
⊕ 3
L1
L2
L3 r s
200 s
400
+
T1
T2
T3
Power Supply
Internal
Cooling Fan
Control Circuit
VS-616PS5 Installation & Quick Start Manual
3.2
Connecting the Power Supply
Input Circuit Requirements
The input power supply phases (L1, L2, and L3) may be connected in any sequence.
1. Circuit Breaker or Disconnect
• The user must supply a circuit breaker or disconnect with properly sized fuses to protect the input wiring to the VS-616PS5 inverter.
• Input currents to the inverters are listed in section 1.2.
• Recommended wire sizes are listed in the Wire Size Tables in Appendix A. Circuit Breakers and fuses must be sized via the NEC standards according to the wire size.
2. Ground Fault Interrupter
• Select a ground fault interrupter not affected by high frequencies for use on the input.
• Example: NV Series by Mitsubishi Electric Company
• Example: EGSG series by Fuji Electric Co., Ltd.
3. Magnetic Contactors
• A magnetic contactor may be used as a disconnecting device on the input side of the inverter. The user must still supply fuses to protect the wiring and a circuit breaker or disconnecting device to remove power from the input side of the contactor.
• The VS-616PS5 may be started/stopped by closing/opening the magnetic contactor on the power input; however, frequent operation may cause an inverter malfunction.
• When a magnetic contactor is opened on the input side, dynamic braking does not function and the motor coasts to a stop.
• When using a braking resistor unit, use an input side contactor to prevent damage to the braking resistors in the event of a braking resistor overload.
4. Reactors and Transformers
• The use of reactors on the power supply side will improve the input side power factor.
• DC reactors may be connected to VS-616PS5 units 15 KW or less between the + 1 and
+2 terminals on the inverter (after removing factory installed shorting bar).
• AC reactors may be used on the input. They should not exceed 5% impedance.
• Transformers or reactors must be used with 15 KW units or smaller to limit instantaneous current of a mains power supply 600 KVA or larger.
• If power factor correction is used on the mains supply, a transformer or reactor must be used to limit peak currents into the converter section of the drive.
5. Surge Suppressors
• A surge suppressor must be used on the coil of an input contactor.
• Magnetic solenoids, valves, etc. must have surge suppressors across their inputs.
Grounding
The PS5 Controller must be grounded properly not only for safety, but also to insure proper operation.
1. Ground Resistance: 230 VAC class = 100 ohms or less 460 VAC class = 10 ohms or less
2. Never ground the VS-616PS5 in common with high current electrical equipment.
3. Do not use metallic conduit as a grounding conductor.
4. Size ground wires according to the “Wire and Terminal Screw Sizes” table in Appendix A.
5. The length of ground wires should be as short as possible.
6. When several units are used, do not loop ground wires.
(a ) Acceptable
VS-616PS5 Installation & Quick Start Manual
(b) Acceptable (c) Not Acceptable
19
Input Fuse Protection
The input diode bridge should be protected from failure, in the event of a short circuit in the inverter, by installing high-speed fuses (Semiconductor Type) on the input. These fuses are for short circuit protection only. They DO
NOT take the place of the protection for the wiring, which is supplied by the approved fused disconnect or circuit breaker discussed previously, and is sized according to national, state, and local electrical codes.
Drive Model
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
Fuse Number FLA
A50P30
A50P30
30
30
A50P30
A50P40
A50QS70
A50QS70
30
40
70
70
A50QS100 100
A50QS125 125
A50QS150 150
Drive Model
40P4
40P7
41P5
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
Fuse Number
A70P20
A70P20
A70P20
A70P25
A70P25
A70P25
A70P30
A70P30
A70P50
A70P60
A70P70
20
25
25
25
FLA
20
20
30
30
50
60
70
Drive Model
4022
4030
4037
4045
4055
4075
4110
4160
4185
4220
4300
Fuse Number FLA
A70P80
A70P100
80
100
A70P125
A70P150
A70P200
A70P225
125
150
200
225
A70P300
A70P350
A70P700
A70P700
A70P1000
300
350
700
700
1000
Fuse numbers given are Gould-Shawmut Amp-Trap
®
part numbers. Substitutes must be equivalent.
3.3
Connecting the Motor
Output Circuit Considerations
The VS-616PS5 is not suitable for running multiple motors on its output.
20
1. Motor Power Connections
• Motor lead T1 must be connected to T1 (U) on the inverter, T2 to T2 (V), and T3 to T3 (W).
This is NOT an induction motor. You cannot reverse rotation by swapping phases.
• Refer to the wire size tables in Appendix A for wire sizes.
• Make sure that the nameplate current of the motor does not exceed the nameplate current of the VS-616PS5.
• The motor leads shall not be run in the same conduit as the feedback signals.
• Around sensitive instrumentation, metallic conduit must be used for motor power leads.
2. Motor Starters
• Opening or closing a magnetic contactor in the output of an inverter while it is running will cause the inverter to malfunction.
• If a magnetic contactor is used on the output of the inverter, it must be interlocked with the inverter in such a way that it is closed before the inverter output is turned on, and opened only after the inverter output is turned off.
3. Thermal Overload Relays
• The VS-616PS5 inverter incorporates a UL Recognized electronic overload function.
• If this overload function is disabled (L1-01 = “0”), an external thermal overload relay must be installed.
4. Wiring Distances
• Excessively long motor wiring and a high carrier frequency may adversely affect the inverter and peripheral devices.
• For distances of up to 328 feet (100 meters), the carrier frequency may be set as high as 8 kilohertz. If the distance is greater than 328 feet, the inverter carrier frequency should be lowered to less than 5 kilohertz. The carrier frequency is set by parameter C6-02. NOTE:
Setting the carrier frequency higher than the default frequency for any model requires derating. Consult the factory for de-rating information.
• For distances greater than 328 feet, increase the wire size by 1 AWG wire gauge for each additional 100 feet.
VS-616PS5 Installation & Quick Start Manual
3.4
Connecting the Feedback
The PS5 operates in a closed loop control method only. A PG feedback option PCB is therefore required.
Refer to the following information to properly select and configure the feedback option. Additional connection diagrams are located in Appendix C.
Types of Feedback Device
1. Hall Effect Sensor Device
• 3 commutation channels, 60° separation, sinking
• 2 speed channels, 30 or 60 PPR, quadrature, sinking
2. Commutation Encoder
• 3 commutation channels, 60° separation, line driver
• 2 speed channels, 500 to 4096 PPR, quadrature, line driver
3. Resolver
• 1 marker channel, 1 PPR, line driver
• 6 kHz or 6.5 kHz reference frequency
• Sine channel, 0.5:1 or 0.333:1, differential output
• Cosine channel, 0.5:1 or 0.333:1, differential output
Types of Feedback Card
Earth Ground
Connection
PG-H2 Hall Sensor
Feedback Card
Part Number
PG-H2
Earth Ground
Connection
PG-P2 Encoder
Feedback Card
Part Number
PG-P2
Earth Ground
Connection
PG-R2 Resolver
Feedback Card
Part Number
PG-R2
CONNECTOR CONNECTOR CONNECTOR
+12VDC isol
12V isol COM
A1+ IN
A1- IN
B1+ IN
B1- IN
C1+ IN
C1- IN
SHIELD
+12VDC isol
HS1
HS2
HS3
HS4
HS5
SHIELD
APM+ OUT
APM- OUT
BPM+ OUT
BPM- OUT
CPM+ OUT
CPM- OUT
SHIELD
12V isol COM
15
16
17
18
19
20
21
22
23
24
8
9
10
11
12
13
14
6
7
4
5
1
2
3
VS-616PS5 Installation & Quick Start Manual
SHIELD
SHIELD
NO CONNECTION
+12VDC isol
12V isol COM
A1+ IN
A1- IN
B1+ IN
B1- IN
C1+ IN
C1- IN
HS1
HS2
HS3
HS4
HS5
Pulse Output
APM+ OUT
APM- OUT
BPM+ OUT
BPM- OUT
CPM+ OUT
CPM- OUT
Pulse Input
12V isol COM
1
2
3
J2A
J2B
J1
A+ OUT
A- OUT
B+ OUT
B- OUT
C+ OUT
C- OUT
0V
M1
M2
0V
CLOCK1
CLOCK2
DATA1
DATA2
LOSS1
LOSS2
R1
R2
0V
S1
S3
0V
S4
S2
0V
19
20
21
22
23
24
25
13
14
15
16
17
18
9
10
11
12
7
8
5
6
1
2
3
4
21
PG-H2 Hall Sensor Feedback Card
The PG-H2 is intended for use with Permanent Magnet motors with integrated Hall-effect sensors. It uses 3 commutation channels with 120 electrical degree separation, and 2 speed channels in quadrature. All outputs of the
Hall-effect feedback device are in a sinking configuration. Three encoder (line driver type) input channels are also standard for the encoder speed feedback option. When using the encoder inputs, a 12 Volt, differential encoder with channels A, A, B, B and C, C is required. When using a PG-H2, make sure the jumper is on the upper 2 pins of header HDRI (as shown below).
HALL
EFFECT
SENSOR
RING
H1
H4 H5
H2
H3
+
-
1 2 3 4 5 6 7 8 9 10
Earth
Ground
Connection
Motor Thermal Switch to control circuits
CONNECTOR
Revision Level
VS-616PS5
INVERTER
Jumper
+12VDC isol
12V isol COM
A1+ IN
A1- IN
B1+ IN
B1- IN
C1+ IN
C1- IN
SHIELD
HDRI
+12VDC isol
HS1
HS2
HS3
HS4
HS5
SHIELD
APM+ OUT
APM- OUT
BPM+ OUT
BPM- OUT
CPM+ OUT
CPM- OUT
SHIELD
12V isol COM
4
5
6
7
8
1
2
3
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
CONTROL CIRCUIT TERMINALS
PG-P2 Encoder Feedback Card and Hall Effect Sensors (PG-P2 Revision C)
The Hall Effect Sensor device can also be used with the PG-P2 encoder card. The PG-P2 card has a pulse input for following applications. There is also a pulse train output. The PG-P2 terminal markings shown apply to revision
C boards. Refer to Appendix C for connection details.
HALL
EFFECT
SENSOR
RING
H1
H4 H5
H2
H3
+
-
1 2 3 4 5 6 7 8 9 10
Earth
Ground
Connection
Motor Thermal Switch to control circuits
Revision Level
VS-616PS5
INVERTER
CONNECTOR
1
2
3
4
SHIELD
SHIELD
J2A
+12VDC isol
12V isol COM
A1+ IN
A1- IN
B1+ IN
B1- IN
C1+ IN
C1- IN
HS1
J2B
HS2
HS3
HS4
HS5
J1
Pulse Output
APM+ OUT
APM- OUT
BPM+ OUT
BPM- OUT
CPM+ OUT
CPM- OUT
Pulse Input
12V isol COM
CONTROL CIRCUIT TERMINALS
22 VS-616PS5 Installation & Quick Start Manual
PG-P2 Encoder Feedback Card with Commutation Encoder (PG-P2 revision C)
The PG-P2 Encoder Feedback card accepts line driver signals from a commutation encoder. The commutation channels S1, S2, and S3 are wired to HS1, HS2, and HS3. The speed and direction channels are wired to the A, B, and Z line driver outputs of the encoder. The PG-P2 terminal markings shown apply to revision C boards. Refer to
Appendix C for connection details.
COMMUTATION ENCODER CONNECTIONS
MS Connector MS3102E20 29P
M
L
K
J
T
H
S
A
N
B
P
C
D
G
R
F
E
Suggested Mating Connector
MS310GF-20-29S
A
S
T
G
H
J
K
L
M
C
D
E
COMMUTATION ENCODER
CONNECTOR PIN
M
N
K
L
H
J
P
R
S
T
F
G
D
E
A
B
C
ENCODER
CASE GROUND
N/C
S1
S2
S3
N/C
A
/A
Z
/Z
B
/B
/S1
/S2
/S3
ENCODER V++
ENCODER VDC COM
Earth
Ground
Connection
Pulse Train
Speed Output
Pulse Train
Follower Input
Revision Level
VS-616PS5
INVERTER
CONNECTOR
1
2
3
SHIELD
SHIELD
J2A
+12VDC isol
12V isol COM
A1+ IN
A1- IN
B1+ IN
B1- IN
C1+ IN
C1- IN
HS1
J2B
HS2
HS3
HS4
HS5
J1
Pulse Output
APM+ OUT
APM- OUT
BPM+ OUT
BPM- OUT
CPM+ OUT
CPM- OUT
Pulse Input
12V isol COM
CONTROL CIRCUIT TERMINALS
PG-R2 Resolver Feedback Card (Future)
The PG-R2 Resolver Feedback Card accepts the Sine and Cosine signals from a resolver mounted on the motor.
Shown below is a typical connection scheme.
RESOLVER
MOTOR
PROTECTION
THERMAL
DEVICES
1 2 3 4 5 6 7 8
NC
9 10
Earth
Ground
Connection
Revision Level
VS-616PS5
INVERTER
CONNECTOR
B+ OUT
B- OUT
C+ OUT
C- OUT
0V
M1
M2
0V
CLOCK1
CLOCK2
DATA1
DATA2
LOSS1
LOSS2
R1
R2
0V
S1
S3
0V
S4
S2
0V
A+ OUT
A- OUT
16
17
18
19
20
21
22
23
24
25
9
10
11
12
13
14
15
6
7
4
5
8
1
2
3
CONTROL CIRCUIT TERMINALS
VS-616PS5 Installation & Quick Start Manual 23
3.5
Connecting the Control Circuits
Control Terminals Layout
11
1
12 (G)
2
13
3
14
4
15
5
16
6
17
7
25
8
26
21
27
22
33
23
18
9
19
10
20
Control Circuit Wiring
The table below outlines the functions of the control circuit terminals.
Classification
Terminal
1
2
3
4 Fault reset input
5
Master/Aux. change
Multi-step speed ref.1)
6 Multi-step speed ref.2
7 Jog reference
8 External base block
11
Sequence control input common terminal
15
33
+15V
Power supply output
-15V
Power supply output
13 Master freq. ref. (voltage)
14
16
17
12
9
10
Signal Function
Forward run/stop
Reverse run/stop
External fault input
Master freq. ref. (current)
Multi-function analog input
During running (NO contact)
Forward run when closed, stop when open
Reverse run when closed, stop when open
Fault when closed, normal state when open
Reset when closed
Aux. freq. ref. when closed
Effective when closed
Jog run when closed
Inv. output stop when closed
--
For analog command +15V power supply
For analog command -15V power supply
Common terminal for control circuit
Connection to shield sheath of signal lead
--
± 10V/ ± 100% 0 to +10V/100%
4 to 20mA/100%.
± 10V/ ± 100%
0 to +10V/100%
Aux. analog input (H3-05)
0V
Closed when running
Description
Multi-function contact inputs
( H1-01 to H1-06 )
Multi-function output
Photo-coupler insulated
Input: +24VDC 8mA
+15V
Signal Level
(Allowable current 20mA max.)
-15V
(Allowable current 20mA max.)
± 10V (20k Ω )
0 to +10V/(20k Ω )
4 to 20mA (250 Ω )
± 10V (20k Ω )
0 to +10V/(20k Ω )
--
--
Dry contact
Contact capacity:
250VAC, 1A or less
30VDC, 1A or less
25 Zero speed detection
26 Speed agree detection
Activates at min. freq. (E1-
09) or less
Activates when freq. reaches ±1Hz of set freq.
Open collector output
48V, 50mA or less
27 Open collector output common
18
19
Fault contact output
(NO/NC contact)
20
21 Frequency meter output
22 Common
23 Current monitor
Fault when closed between terminals 18 and 20
Fault when open between terminals 19 and 20
0 to ±10V/100% frequency
5V/inverter rated current
Multi-function analog monitor 1 (H4-01, H4-02)
Multi-function analog monitor 2 (H4-04, H4-05)
--
Dry contact
Contact capacity:
250VAC 1A or less
30VDC 1A or less
0 to ±11V Max. ±5%
2mA or less
24 VS-616PS5 Installation & Quick Start Manual
VS-616PS5 Standard Connection Diagram
⊕ P3
230V: 0.4 ~ 15kW
460V: 0.4 ~ 300kW
L1
L2
L3
E
N
*
+
T1
T2
T3
PM
Gate Drive
Multi-Function
Inputs
Analog Inputs
-10 to +10V
4 to 20mA
-10 to +10V
4
5
6
1 - Fwd Run when CLOSED
2 - Rev Run when CLOSED
3
7
8
11 (Com)
Fixed
PWM
±9 bit
PG-P2
or
PG-H2
0~±10V 21
22
0~±10V 23
32
12
15
13
14
17
(+15V, 20mA)
(20k Ω )
(250
(0V)
Ω
16 (20k Ω )
) A/D
±11 bit
18
19
20
9
10
25
33 (-15V, 20mA)
Digital
Operator
26
27
Multi-Function
Analog Outputs
Fault Relay
Outputs (fixed)
Multi-Function
Relay Outputs
Multi-Function
PHC Outputs
48V, 50mA or less
Encoder/
Hall
Sensor
VS-616PS5 Installation & Quick Start Manual 25
3.6
Connecting Resistor Braking Units
230V: PS5U20P4 to 27P5
460V: PS5U40P4 to 4015
Overload Relay Trip Contact
1 2
B
Braking Resistor
Unit
L1
L2
L3
P
MCCB
MC
L1
L2
L3
B1 B2 T1
T2
T3
M
THRX OFF
ON
MC
Overload Relay Trip Contact of Braking Resistor Unit
1
MC
2
MC
SA
THRX
SA
TRX
SA
TRX
MC MA
Fault Contact
Braking Unit
230V: PS5U2011 to 2015
460V: PS5U4018 to 4045
Braking Unit
⊕ 3
⊕
P P0
B
P
Braking Resistor
Unit
N
Level
Detection
3
B
1 2
4
Overload Relay Trip Contact
3 & 4 output signal to multi-function fault input.
26 VS-616PS5 Installation & Quick Start Manual
4.1 Operational Concerns ............................................................................27
Before Initial Operation ..........................................................................27
Replacing the Digital Operator ...............................................................27
4.2 Digital Operator .....................................................................................28
Orientation..............................................................................................28
Parameter Entry .....................................................................................29
4.3 Entering the Initial Data ..........................................................................30
4.4 Initial Operation by Digital Operator .......................................................31
4.5 Initial Operation by Control Circuits........................................................32
4.1
Operational Concerns
Before Initial Operation
1. Replace the cover and Digital Operator on the unit before applying power to the inverter.
2. Make sure that the automatic re-start function is disabled (parameter L5-01 = 0).
3. The initial operation of the motor should be performed with the motor disconnected from its mechanical load.
4. Make sure the motor is securely fastened to its base and all personnel are clear before energizing the inverter.
5. Install and check an Emergency Stop button before operation. Install a Normally Closed, momentary,
Emergency Stop push button between control terminals 11 and 4. Set parameter H1-02 to 25.
6. Do not change any parameters unless you are instructed to do so, or unless you have read and understood what the change in the parameter will do.
Replacing the Digital Operator
Digital Operator
Front Cover
2
1
B Claws
A Claws
To replace the digital operator:
• connect the operator to the A claws in the direction shown by arrow 1
• then connect the B claws in the direction shown by arrow 2, locking the digital operator into place.
VS-616PS5 Installation & Quick Start Manual 27
4.2
Digital Operator
Orientation
All functions of the VS-616PS5 are accessed using the digital operator. Below are descriptions of the display and keypad sections.
Mode Indicator LEDs
DRIVE Mode LED
Lights when selecting drive mode (operation is possible).
OFF when selecting any other mode.
Rotation Direction LEDs
FWD : Lights at forward run.
REV : Lights at reverse run.
REMOTE Mode LEDs
Lights when selecting input mode from the control circuit terminal or serial communication.
SEQ : Lights when selecting run command from the control circuit terminal or serial communication.
REF : Lights when selecting frequency reference from the control circuit terminals 13 or 14, or serial communication.
28
Display
Displays set values of each function or monitoring value such as output frequency or current (5 characters).
Operation Mode Selection Key (LOCAL/REMOTE)
The operation mode is alternated with REMOTE and
LOCAL (digital operator) when operational instruction and frequency references are set at the control circuit terminal.
Mode Selection Key (DRIVE/PRGM)
Alternates drive or program mode (even during run). In drive mode, DRIVE LED lights at mode indicator.
Display Selection Key (DSPL)
Selects monitoring items.
Read/Write Key (DATA ENTER)
Selects mode, group, function, or constant name. Displays each constant set value while displaying a constant name. By pressing this key again, the set value is written in.
Menu/Set Value Changing Keys
Selects mode, group, function, parameter or set value.
∧∧ : Increment key
∨∨ : Decrement key
Digit Selection Key (>RESET)
Selects a digit of a set value to be changed. The selected digit blinks. Resets operation at faults.
Run Command Keys
Run command keys for use by the digital operator.
These are enabled only in the drive mode.
STOP :
RUN :
Red LED lights after depressing STOP key.
FWD/REV : Selects forward or reverse run.
JOG :
Red LED lights after depressing RUN key.
Jog run is enabled while depressing this key.
VS-616PS5 Installation & Quick Start Manual
Parameter Entry
When power is applied, the display defaults to the reference setting:
P 00.00
DRIVE
PRGM
Press the key to access the parameters.
A1-01
is displayed.
Press the
DATA
ENTER
key to display the value. The default is:
0 002
The first 0 will be blinking. This is the value for access to the Quick Start parameters.
DISPL
We want to keep this value, so press to go back to:
A1-01
Press the key to go to the next parameter:
A1-03
.
Press the
DATA
ENTER
key to display the value. The default is:
0 000
We want to enter 3330 for 3-wire operation. The first zero will be blinking.
Press the key three times to change the first number to 3.
Now the display will show:
3000
with the 3 blinking.
Press the key to go to the next digit. Now the second digit is blinking.
Press the key three times to change the second number to 3:
3 3 00
Use the and keys to change the third digit to 3:
33 3 0
DATA
DISPL
A1-03
DRIVE
The display is now ready for a speed reference entry:
P 0 0.00
The digit to be changed is blinking.
DATA
Use the , , , and keys to set the desired reference in percent speed.
DISPL
Press the key to see the speed display.
VS-616PS5 Installation & Quick Start Manual 29
4.3
Entering the Initial Data
Quick Start Parameters
Parameter A1-01 sets the access level for the parameters. Setting it to “ 0000 ” disables access to any other changeable parameters. Setting A1-01 to “ 0002 ”, which is the factory default setting, enables access to the Quick
Start parameters, which are used to initially get the inverter and motor into operation.
The user can scroll through the Quick Start parameters using the increment key on the digital operator.
NOTE: only the settings involved in Quick Start Menu are explained here. See the programming section for other settings for these parameters.
A1-03 Initialization
• Set to “0000” (default) for no initialization
• Set to “2220” for 2-wire initialization (terminal 1 = FWD RUN, terminal 2 = REV RUN)
• Set to “3330” for 3-wire initialization (terminal 1 = RUN, terminal 2 = STOP, terminal 3 = FWD/
REV)
• In the 2-wire and 3-wire case, all other parameters are set to the factory defaults.
A1-04 Password
• Allows entry of a password for access to masked parameters.
B1-01 Frequency Reference Source
• Set to “00” to set the speed reference from the digital operator only.
• Set to “01” (default) to set the speed reference from the inverter terminals 13 (+) and 17 (-)
B1-02 Operation Control Source
• Set to “00” to start/stop/jog the inverter from the digital operator only.
• Set to “01” (default) to start/stop/jog the inverter from the inverter control terminals.
NOTE: B1-01 and B1-02 do not have to be set to the same source; they may be set for different sources.
When B1-01 and B1-02 are set to “01”, the LOCAL/REMOTE key on the operator controls the sources. LOCAL mode allows only digital operator operation; REMOTE allows operation from control terminals or digital operator
(determined by the settings of parameter B1-01 and B1-02).
If you disconnect the digital operator, B1-01 and B1-02 must be set to something other than “00”. When the power to the inverter is cycled, these parameters will control the reference and control sources.
C1-01 Acceleration Time 1
C1-02 Deceleration Time 2
•The default time for these is 10.0 seconds. They may be changed for Quick Start, if desired.
D1-01 Preset Frequency Reference 1
D1-02 Preset Frequency Reference 2
D1-03 Preset Frequency Reference 3
D1-04 Preset Frequency Reference 4
• With the factory default settings, Presets 1 and 2 are not used.
• Preset 3 can be selected by closing input terminal 6 (factory default).
• Preset 4 can be selected by closing terminals 5 and 6 (factory default).
D1-09 Jog Frequency Reference
• The factory default is 10.0%. It may be changed if desired.
E1-01 through F1-01 Motor Parameters
• See the table on page 4 and item 19 of the VS-616PS5 QUICK START PROCEDURE on page 5.
T1-02 and T1-03 Auto Tuning Parameters
• See items 20 through 22 of the VS-616PS5 QUICK START PROCEDURE on page 5.
30 VS-616PS5 Installation & Quick Start Manual
4.4 Initial Operation by Digital Operator
1 2 3 4 5 6 7
POWER
ON
FWD JOG
RUN
SET
SPEED
FWD
RUN
SET
SPEED
REV
RUN
STOP
1
2
3
4
5
Description
Power ON
Ÿ
Displays Frequency
Reference Value
Operation Source
Ÿ Select LOCAL Mode
Set JOG Reference
Ÿ
Ÿ
Set D1-09 to 10.00%
Press Display Key
Forward Jog Run
Ÿ Runs at JOG speed while key is pressed.
Ÿ
Press Display Key
Speed Setting
Ÿ
Change Speed Reference
Value
Ÿ ENTER the new value
Ÿ Select Speed display
Forward RUN
Ÿ Press RUN on operator
Change Speed Reference
Ÿ Select reference display
Ÿ
Change Reference value
6
Ÿ ENTER the new value
Ÿ Select Speed display
Reverse RUN
Ÿ
Press Reverse
7 Stop
Ÿ
Press Stop Button
Key Sequence
LOCAL
REMOTE
DISPL
JOG
DISPL
Change value with arrow keys
DATA
ENTER
DISPL
RUN
RUN LED ON
DISPL
Change value with arrow keys
DATA
ENTER
DISPL
FWD
REV
STOP
Digital Operator Display
P 0 0.
0 0
REMOTE LED OFF
FWD LED ON
0 0 0.
0
0 0.
0 0
1 0.
0 0
P 0 0.
0 0
Digit to be changed blinks
P 2 5.
0 0
0 0.
0 0
2 5.
0 0
P 2 5.
0 0
Digit to be changed blinks
P 1 0 0.
0
P 1 0 0.
0
1 0 0.
0
1 0 0.
0
VS-616PS5 Installation & Quick Start Manual 31
4.5 Initial Operation by Control Circuits
For operation from the control input terminals, B1-01 must be set to 0001 and B1-02 must be set to 0001. Select
REMOTE operation on the digital operator (SEQ and REF LED’s on operator should be ON).
1 2 3 4 5 6 7
POWER
ON
FWD RUN
SLOW
SET
SPEED
FWD
RUN
SET
SPEED
REV
RUN
STOP
1
2
3
Description
Power ON
Ÿ
Displays Reference Value
Operation Source
Ÿ Select REMOTE Mode
Set Speed Reference
Ÿ
Set analog input to 10%
Ÿ Press DISPL button
Forward Run slowly
Ÿ
Start motor for slow run
Ÿ
Stop Motor
Speed Setting
Ÿ Select Reference display
Ÿ Set analog reference to 25%
Control Inputs
LOCAL
REMOTE
Set analog reference voltage at terminals 13
(+) and 17 (-) to 1.0VDC
DISPL
Press operator RUN Button
Press Operator STOP Button
DISPL
Set analog reference voltage at terminals 13 (+) and 17 (-) to 2.5 VDC
Digital Operator Display
Displays Operator Speed
P 1 0. 0 0 0
REMOTE LED OFF
FWD LED ON
Displays input analog reference
P 0 0. 0 0 3
P 1 0. 0 0
0 0. 0 0
1 0. 0 0
0 0. 0 0
P 1 0. 0 0
P 2 5. 0 0
3
0
3
0
3
2
4
5
Ÿ Select Speed display
Forward RUN
Ÿ
Start Motor
Change Speed Reference
Ÿ Select reference display
DISPL
Press operator RUN Button
RUN LED ON
DISPL
0 0. 0 0
2 5. 0 0
P 2 5. 0 0
0
2
2
Ÿ Change Reference value
Ÿ Select Speed display
6 Reverse RUN
Ÿ Set Operator Reverse switch Change operator from FWD to REV
7 Stop
Ÿ Press Stop Button
Set analog reference voltage at terminals 13
(+) and 17 (-) to 10.0 VDC
DISPL
-
-
P 1 0 0. 0
1 0 0. 0
- 1 0 0. 0
- 0 0 0. 0
2
2
1
0
32 VS-616PS5 Installation & Quick Start Manual
5.1 Initializing ...............................................................................................33
Parameter Access..................................................................................33
Operator Status ......................................................................................34
5.2 Quick Start Programming ......................................................................35
Application..............................................................................................35
Tuning ..................................................................................................36
Reference...............................................................................................36
Motor Parameters ..................................................................................38
Automatic Tuning ...................................................................................42
Operation Monitoring..............................................................................44
5.3 Basic Programming ................................................................................46
Note: Changing parameters while in operation may have drastic consequences.
5.1
Initializing
The inverter parameters are arranged in groups to simplify the task of placing the inverter into service. Almost all of the parameters have default values that will serve well in the vast majority of applications. This minimizes the number of parameters that need to be set just to get a motor running.
The parameters are further broken down into access levels. The number of parameters needed to get a motor running is far fewer than the number of parameters to make a drive work in a system, in a complex application, or to do complicated actions.
A1 – 01 Parameter Access Level
When power is applied, and the DRIVE/PRGM button is pushed on the operator, parameter A1-01 is the first parameter to appear. This parameter determines the parameter set available for programming.
Setting Explanation
0000 Allows access to this parameter and monitor (“U”) parameters only
0001 Accesses special OEM parameters (A2-01 through A2-32)
0002 Quick Start parameters – described in section 5.2
0003 Basic Parameters – briefly described in section 5.3
0004 Advanced parameters – described in the VS-616PS5 Programming manual
Default
X
VS-616PS5 Installation & Quick Start Manual 33
A1 – 03 Operator Status
Use this parameter to reset the inverter to the factory defaults before initial operation, after changing the Control
PCB, or when changing the motor to a different type. The selection of this parameter depends on the type of control circuit connections used.
Setting Explanation
0000 No initialization activation
2220 2-wire initialization (terminal 1 = FWD run, terminal 2 = REV run) All other parameters are restored to the factory default settings.
3330 3-wire initialization (terminal 1 = RUN, terminal 2 = STOP, terminal 5 = FWD/
REV) All other parameters are restored to the factory default settings.
Upon executing an initialization, parameter A1-03 reverts back to the default setting.
Default
X
When A1-03 is set to 2220, the control terminals will be set for two wire control.
1
FWD Run/Stop
2
REV Run/Stop
11
2 Wire Control
When A1-03 is set to 3330, the control terminals will be set for three wire control.
1
Run Command (Run on momentary “Close”)
2
Stop Command (Stop on momentary “Open”)
5
11
FWD/REV Run Selection (FWD Run when “Open”
Rev Run when “Closed”)
3 Wire Control
A1 – 04 Password Entry
This parameter allows the entry of a password to view masked parameters. Consult the factory prior to adjusting this parameter.
34 VS-616PS5 Installation & Quick Start Manual
5.2 Quick Start Programming
The Quick Start Program is a set of parameters that are the minimum necessary to get the motor running in the majority of stand-alone applications. This set is activated when “0002” is entered into parameter A1-01. The Quick
Start parameters are scrolled in order when the DRIVE/PRGM key is pressed after power up and the increment key is pressed repeatedly. Refer to Appendix D for a complete parameter list.
Application Parameters
B1 – 01
B1 – 02
Speed Reference Source Selection
Operating Control Source Selection
These two parameters are used to determine the source of the speed command (B1-01) and the source of control inputs (B1-02). They use a common selection table, but they DO NOT need to be set to the same number. The speed and control may come from different sources.
Setting Explanation
00 The source is the Digital Operator
01
02
03
04
06
The source is the control circuit input terminals
The source is serial communications
The source is an option card (2CN or 3CN)
The source is a CP-717 (personal computer interface)
The source is a pulse train input on the feedback card (for B1-01 only)
Default
X
The Digital Operator has a LOCAL/REMOTE function.
LOCAL: The speed and control functions are under control of the digital operator.
REMOTE: The sources of operation are chosen by B1-01 and B1-02.
When power is applied to the inverter, the REMOTE function is activated, so power should be cycled if the operator is disconnected.
B1 – 03 Stopping Method Selection
This parameter selects the method of stopping the motor on a normal stop operation.
Setting Explanation
00 RAMP - deceleration under ramped speed control according to decel rate 1 (C1-
01
02
02)
COAST – power to the motor is shut off and the motor coasts to a stop.
TIMED – power to motor is removed, motor coasts to a stop, timer inhibits restart
Default
X
RAMP: Upon removal of the RUN command, the speed of the motor is decreased under power at a rate determined by the time set in parameter C1-02. If the deceleration time is short, or the inertial load on the motor is large, an overvoltage fault (OV) may occur while ramping. In this case, either the deceleration time must be increased or an optional braking unit must be installed.
COAST: Upon removal of the RUN command, the power to the motor is shut off and the motor and load slow down to a stop in a time determined by the speed before stopping, the inertia of the motor and load, and the amount of friction in the system. If the motor takes too long to stop, it may be necessary to install a mechanical brake on the motor or load. Alternatively, passive resistance dynamic braking may be installed.
TIMED: Upon removal of the RUN command, the motor slows down as in the COAST method. A new RUN command will not be accepted until the deceleration time (C1-02) has elapsed.
VS-616PS5 Installation & Quick Start Manual 35
Tuning Parameters
The only tuning parameters available in the Quick Start Program are Acceleration Rate 1 and Deceleration Rate 1.
C1 – 01
C1 – 02
Acceleration Time 1
Deceleration Time 1
Minimum Maximum Description
0000.0
6000.0
Acceleration/Deceleration Time in Seconds
Default Setting
6000.0
Acceleration Time 1: Sets the amount of time the inverter will take to accelerate from zero speed to the maximum speed (E1-06). The amount of time it takes to go from a lower speed (which may be zero) to a higher speed
(which may be maximum) is proportional to the amount of the actual speed change versus the total range from zero to maximum.
Deceleration Time 1: Sets the amount of time the inverter will take to decelerate from maximum speed (E1-06) to zero speed. The amount of time it takes to go from a higher speed (which may be the maximum) to a lower speed (which may be zero) is proportional to the amount of the actual speed change versus the total range from maximum to zero.
C2 – 13 PG Marker Pulse Offset Angle
Indicates the electrical angle between the rotor magnetic pole position and the marker pulse after auto-tuning has been performed. The offset angle is derived from using the marker pulse (encoder speed feedback method) or calculated marker pulse (hall effect speed feedback method) along with the rotor pole position as detected during auto-tuning.
Minimum Maximum Description
-180.0º +180.0º PG Marker Pulse Offset Angle
Default Setting
--
Reference Parameters
The preset speed references in the Quick Start program are entered into D1-01 through D1-04, and into parameter
D1-09 for the JOG speed reference
D1 – 01
D1 – 02
D1 – 03
D1 – 04
Preset Speed Reference 1
Preset Speed Reference 2
Preset Speed Reference 3
Preset Speed Reference 4
Minimum Maximum Description
000.00
100.00
Reference Parameters
Default Setting
000.00
Multi-function input terminals 6 and 7 control the application of preset speed references in Quick Start mode. The following table shows how they can be used in Quick Start mode:
36 VS-616PS5 Installation & Quick Start Manual
Terminal 5
OPEN
CLOSED
OPEN
CLOSED
Terminal 6
OPEN
OPEN
CLOSED
CLOSED
NOTE: Up to nine presets are available in advanced modes.
Selected Speed Reference
Speed Reference 1 - determined by B1-01
Speed Reference 2 - active only if H3-05 and H3-09 is not equal to 0
Speed Reference 3 – D1-03 supplies speed reference
Speed Reference 4 – D1-04 supplies speed reference
D1 – 09 Preset JOG Speed Reference
The JOG speed reference is set in the same manner as the other presets. This is the speed at which the motor will run when the digital operator is in LOCAL mode and the JOG button is pressed.
To use the JOG speed reference when the digital operator is in REMOTE (or disconnected), close terminal 7 at the same time as the RUN command is applied. The JOG speed command has priority over all other reference commands.
VS-616PS5 Installation & Quick Start Manual 37
Motor Parameters
The motor parameters must be entered before attempting operation of the motor. Motor information is obtained from the nameplate of the motor and from Appendix B of this manual (partial listing only). Older motors do not have all their characteristics listed on their nameplates. It may be necessary to contact the motor manufacturer to obtain the data for programming parameters E1-03 thru E1-17.
E1 – 01 Input Voltage
Enter the nominal power supply voltage supplied to the inverter.
Minimum Maximum Inverter Type
155 255 230V class PS5 inverter
310 510 460V class PS5 inverter
Default Setting
230
460
E1 – 02 Motor Capacity Selection
Enter “1000” for custom motor data. Entering numbers greater than 1000 access stored motor characteristics that load most of the “E” parameters (future addition- reference Appendix B). Used in conjunction with motor connection selection, parameter E1-17, to automatically load parameters, E1-03 thru E1-13. Set E1-17 to the correct winding configuration prior to programming E1-02 to the desired winding code.
Minimum Maximum Description
1000 1999 Winding number - obtained from motor model number
Default Setting
1000
E1 – 03 Rated Motor Voltage
Enter the motor voltage according to the nameplate bus voltage.
Minimum Maximum Inverter Type
0 255 320 VDC bus voltage motors
0 510 640 VDC bus voltage motors
Setting
230
460
E1 – 04 Motor Rated Current
Enter the rated motor current (from nameplate). The maximum value that can be entered for an inverter is equal to inverter rated current (nameplate value).
Minimum Maximum Description
000.00
605.0
Rated Motor Current FLA from nameplate –
7.5 Kw or less resolution 0.01A
11 Kw or more resolution 0.1A
Default Setting
- -
E1 – 05 Number of Motor Poles
Enter the number of motor poles according to the nameplate.
38
Minimum Maximum Description
2 8 Winding number - obtained from motor model number
Default Setting
1000
VS-616PS5 Installation & Quick Start Manual
E1 – 06 Motor Maximum Speed
Enter the maximum speed of the motor.
Minimum Maximum Description
0000 6000 Maximum Speed of motor – set by application
E1 – 07 Motor Base Speed
Enter the base speed of the motor (from nameplate).
Minimum Maximum Description
0000 6000 Base Speed of motor - obtained from motor nameplate
Default Setting
E1-07
Default Setting
- -
E1 – 08 Minimum Motor Speed
Enter the minimum speed of the motor (in RPM).
Minimum Maximum Description
0000 6000 Minimum Speed of motor – set by application
E1 – 09 Motor Resistance
Enter the resistance of the motor (in Ohms).
Minimum Maximum Description
00.000
65.535
Motor Line to line resistance value
Default Setting
30
Default Setting
- -
E1 – 10 Motor d-axis Inductance
Enter the real inductance of the motor (in mH).
Minimum Maximum Description
000.00
600.00
Motor Line to line real axis inductance value
Default Setting
- -
E1 – 11 Motor q-axis Inductance
Enter the real inductance of the motor (in mH). Under most circumstances, the same value will be entered here as is entered in E1-10.
Minimum Maximum Description
000.00
600.00
Motor Line to line quadrature axis inductance value
Default Setting
- -
VS-616PS5 Installation & Quick Start Manual 39
E1 – 13 Induced Voltage Constant
Enter the induced voltage constant (KV or KE) of the motor.
Minimum Maximum Description
0000 6000 Motor Induced Voltage (KV AC RMS/1000 RPM)
Default Setting
- -
E1 – 17 Motor Connection Selection
Enter the winding connection of the motor (used only if E1-02 is not equal to 1000). Used in conjunction with parameter E1-02 to automatically load the motor parameters (See Appendix B).
Minimum Maximum Description
00 03 Connection: 0 = 1-delta, 1 = 2-delta, 2 = 1-wye, 3 = 2-wye
Default Setting
0
40 VS-616PS5 Installation & Quick Start Manual
PG Option Set-up
F1 – 01 PG Pulses Per Revolution
Enter the number of pulses per revolution of the speed feedback device (hall sensor or encoder).
Minimum Maximum Description
0 10000 Speed Feedback device PPR
Default Setting
30
F1 – 05 PG Rotation Selection
Enter the relationship between the motor rotation and the PG polarity (hall sensor 4 & 5 or encoder A & B channels).
Settings
0
1
Description
HS5 leads HS4/Channel B leads A in FWD direction
HS4 leads HS5/Channel A leads B in FWD direction
Default
X
F8 – 01 Speed Feedback Selection
Select between hall sensor and encoder signals as the speed feedback method.
Settings
0
1
Description
Speed feedback from encoder input (A & B)
Speed feedback from hall sensor inputs (HS4 & HS5)
Default
X
VS-616PS5 Installation & Quick Start Manual 41
Automatic Tuning
T1 - 03 Tuning Operation
This parameter sets up the scope of the tuning operation.
Setting Description
00 All parameters are subject to Auto Tuning (Future Enhancement)
Default
01 PG Orientation only ( Pole position tuning) X
T1 - 02 Tuning Mode
The tuning mode is set up in this parameter.
Setting Description
00 Normal Running Mode
02 Auto Tuning Mode
Default
X
Auto Tuning is initiated by setting T1-02 to “02”, exiting the PRGM mode and pressing the RUN button on the digital operator. After the sequence is completed, T1-02 is automatically reset to “00”. Be sure to uncouple the motor from the load prior to performing the Auto-Tuning.
NOTICE: Once the Auto Tuning sequence has been initiated, do not touch the motor or the inverter as long as the display is showing “CAL12” .
When this parameter is set to “02” and the drive is returned to the operation mode (by pressing the DRIVE/PRGM key), the display will read “CAL12” . Press the RUN button. The display will flash on and off and the motor shaft will begin turning. If the Auto Tuning sequence is successful, the display will show “End” after the motor stops turning.
If it is not successful it will display an error code:
Display Error
PGO PG open Circuit dEV Speed Deviation
Explanation
Pulse generator circuit is broken.
The difference between speed command and actual speed is too
ZdEV Phase Z pulse fault
Er-04
Er-11
Er-12 Y-axis Voltage Offset
Er-14
Er-17
Motor Speed
Er-10 Stop Command
Resistance
Induced Voltage
Er-15 d-axis Inductance
Control Axis Comp great.
Incomplete PG origin pulse adjustment.
Motor speed is much higher than commanded speed.
The sequence was interrupted by the operator
Item not completed within tuning time.
Item not completed within tuning time.
Item not completed within tuning time.
Item not completed within tuning time.
Item not completed within tuning time.
Er-18 Phase Comp Amount Tuning not completed within the allotted time.
NOTE: Major faults that may occur during tuning will be displayed and will interrupt the tuning sequence. In this case, other error codes may be displayed. See the Diagnostics section
When “PGO”, “dEV”, or “ZdEV” is displayed, check the hall sensor and/or encoder connections. Also, verify the load is disconnected from the motor shaft.
42 VS-616PS5 Installation & Quick Start Manual
When T1-03 is set to “01”, the most common fault seen will be Er-18. When Er-18 is displayed, shut off power and check the connections to the motor and to the hall sensor and/or encoder.
If two or more attempts to orient the encoder fail (i.e., “End” is not displayed at the end of the sequence), you will need to change parameter F1-05 and re-initiate the auto tuning process as described above. It may be necessary to change A1-03 to “0003” (Basic Parameter Group) to access this parameter (depends on Software version).
VS-616PS5 Installation & Quick Start Manual 43
Operation Monitoring
In the Quick Start program, most of the monitoring parameters are available to peek into what the inverter is doing internally. These parameters, the “U” parameters may be used to monitor normal operation or to troubleshoot abnormal operation. There are three groups:
1. U1 – Monitor
2. U2 – Fault Trace
3. U3 – Fault History
Monitor Parameters
Number Description
U1-01 Speed Reference
U1-02 Output Frequency
U1-03 Output Current
U1-05 Motor Speed
U1-06 Output Voltage
U1-07 DC Bus Voltage
U1-08 Output Power
U1-09 Internal Torque Reference
Units Explanation
% Displays speed reference in percent
Hz Displays fundamental output frequency to motor
AAC Displays current output to motor in RMS Amperes
% Displays motor speed in percent of maximum speed
VAC Displays output voltage to motor in Volts AC RMS
VDC Displays DC Bus Voltage in Volts DC
KW Displays Output power in Kilowatts
% Displays Internal Torque Reference Command
Number Description
U1-10 Input Terminal Status
Units
- -
Explanation
Displays status of input terminals
Parameter U1-10 represents the status of the input terminals with a letter “C” followed by a series of vertical bars.
The bars represent terminals 1 through 8 from right to left.
The first character in the digital operator display is a letter “C”:
If terminals 1, 2, 5, and 8 are ON, the display will look like this:
Number Description
U1-11 Output Terminal Status
Units Explanation
- Displays status of output terminals
Parameter U1-11 represents the status of the output terminals with a letter “o” followed by a series of vertical bars in a manner much like U1-10 displays the input terminals. The display is for the following outputs:
Terminal Contacts
9 - 10
25 - 27
26 - 27
Display
_ _ _ _ _ _ _ 1
_ _ _ _ _ _ 1 _
_ _ _ _ _ 1 _ _
Number Description
U1-12 Internal Control Status
Units Explanation
- Same as U1-10 and U1-11 for internal status
The explanation of these bits is beyond the scope of this manual.
44
Number Description
U1-13 Elapsed Time
U1-14 Flash ID Number
Units Explanation
H Displays inverter operating time in hours
- Displays firmware revision number
VS-616PS5 Installation & Quick Start Manual
Fault Tracing Parameters
Number Description
U2-01 Existing Fault
U2-02 Previous Fault
U2-03 Speed at time of fault
U2-04 Frequency at time of fault
U2-05 Output current at fault
U2-06 Motor speed at fault
U2-07 Output voltage at fault
U2-08 Bus Voltage at Fault
U2-09 Output Power at fault
U2-10 Torque Reference at fault
U2-11 Input status at time of fault
U2-12 Output status at time of fault
U2-13 Drive Status before fault
U2-14 Elapsed time since fault
Units Explanation
- Displays a currently existing fault
- Displays the last fault detected
% Displays the speed percentage when last fault occurred
Hz Displays output fundamental frequency at time of last fault
AAC Displays output current at time of last fault
% Displays the speed at time of last fault
VAC Displays output voltage at time of last fault
VDC Displays bus voltage at time of last fault
KW Displays output power at time of last fault
% Displays internal torque reference at time of last fault
- Displays state of input terminals at time of last fault
- Displays state of output terminals at time of last fault
- Displays state of drive internally before last fault occurred
H Displays elapsed time when last fault was detected
Fault History
Number
U3-01 Most Recent Fault
U3-02
2 nd
Most Recent Fault
U3-03
U3-04
3 rd
Description
Most Recent Fault
4 th
Most Recent Fault
U3-05 Time since Most Recent Fault
U3-06
Time since 2 nd
Most Recent Fault
U3-07
U3-08
Time since 3 rd
Most Recent Fault
Time since 4 th
Most Recent Fault
Fault Tracing and Fault History are retained when power is lost.
Units
- -
- -
- -
- -
H
H
H
H
VS-616PS5 Installation & Quick Start Manual 45
5.3 Basic Programming
When parameter A1-01 is changed to “0003” , additional programming parameters become available. These additional parameters give the user more options to use the features of the inverter without the burden of dealing with all of the options available. Refer to Appendix D for a complete parameter list.
Changing of the programming level from Quick Start to Basic and the setup of these additional parameters should not be attempted until the Quick Start Program has been completed and the motor is in operation at the Quick Start level.
Additional Monitor Options
Number Description
U1-15 Terminal 13 input voltage
U1-16 Terminal 14 input voltage
U1-17 Terminal 15 input voltage
U1-18 Motor Torque Current
U1-19 Motor Excitation Current
Units Explanation
% Displays speed reference in percent at terminal 13
% Displays speed reference in percent at terminal 14
% Displays speed reference in percent at terminal 15
% Displays the motor torque producing current (I q
) in percent
% Displays the motor excitation current (I d
) in percent
Additional Fault Tracing Options
Number Description
U2-15 Motor Torque Current
U2-16 Motor Excitation Current
Units Explanation
% Displays the motor torque producing current (I q
) at fault
% Displays the motor excitation current (I d
) at fault
Additional Application Options
B1 - 04 Prohibition of Reverse Motor Operation
This parameter allows the user to prevent the motor from operating in the reverse direction.
Setting Explanation
00 Reverse operation enabled
01 Reverse operation prohibited
Default
X
B2 – 01 Zero Speed Level
This parameter allows the user to set the speed at which the drive senses zero speed. This affects terminal outputs and shutoff after decelerating.
Minimum
00.00
Maximum
020.00
Description
Zero speed detection level
Default Setting
00.50
46 VS-616PS5 Installation & Quick Start Manual
VS-616PS5 Parameter Tree
U Monitor
A Initialize
B Application
C Tuning
D Reference
E Motor
F Option
H Terminal
L Protection
O Operator
T Tuning
Grou p
F5
F6
F9
F1
F2
F3
F4
H1
H2
H3
H4
D1
D2
D3
D4
D5
C1
C2
C3
C5
C6
E1
U1
U2
U3
A1
B5
B6
B7
B1
B2
B3
B4
Function
Monitor
Fault Trace
Fault History
Initialize
Sequence
Zero Speed Level
Magnetic Pull-in
Delay Timers
Pid Control
Reference Hold
Droop Control
Accel/decel
PG Origin Pulse Comp.
Voltage Limit Control
Asr Tuning
Carrier Frequency
Preset Reference
Reference Limit
Jump Speed
Hold Reference Memory
Torque Control
Motor Constant
PG Option Set-up
AI-14 Set-up
DI-08, 16 Set-up
AO-08, 12 Set-up
DO-02 Set-up
DO-08 Set-up
CP-916 Set-up
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Quick-start
01-03, 05-14
01-14
01-08
01, 03, 04
01-03
Parameter No.
Basic Advanced
15-19
15,16
20-22,27-33,41-47, 49,50,53,54,55
17-22
04
01
01, 02
01-04, 09
03, 04, 09
01-04
05-08
01, 02
01-04
05-06
02, 04, 05
01, 02
01-08
01-04
01, 02
05-08, 10, 11
13
05
05-07
02
01,02,04,09-11,13
01
01
01-06
03, 05-08, 15-17
08-11, 13 02-05
01
01
01-06
01, 02
01
01-06
01-06
01-03
01-07
01-07
08-12
VS-616PS5 Installation & Quick Start Manual 47
Additional Tuning Options
C1 – 03
C1 – 04
Acceleration Time 2
Deceleration Time 2
These parameters are set to provide different ramp times when one of the input terminals (3 through 8) is programmed to “Multi-accel/decel 1” (setting “7”). See parameters H1-01 through H1-06. This allows the user to program different acceleration and deceleration rates for various conditions.
Minimum Maximum Description
0000.0
6000.0
Acceleration/Deceleration Time 2 Setting
Default Setting
0010.0
C1 – 09 Fast Stop Time
This parameter is set to provide a ramp time when one of the input terminals (3 through 8) is programmed to “Fast
Stop Command” (setting “15”). See parameters H1-01 through H1-06. This allows the user to program a rapid deceleration rates for a quicker than normal stop.
Minimum Maximum Description
0000.0
6000.0
Fast Stop Time
Default Setting
0010.0
NOTE: Attempting to stop the motor faster than it will coast to a stop by itself (with power off) may require the addition of a resistor-braking unit.
ASR Tuning Options
The Automatic Speed Regulator (ASR) allows the user to adjust for optimum performance during changes in motor speed or load.
Torque Limit
Speed Reference
Speed Feedback
+
-
C5-01, C5-03
P
I
C5-02, C5-04
+
+
1
1+ST
C5-05
L7-01, L7-04
Secondary Current Reference
C5 – 01
C5 – 03
ASR Proportional Gain 1
ASR Proportional Gain 2
The Proportional Gain adjusts the speed in response to a speed deviation, and softens the effects of load changes.
Response becomes more noticeable as the gain is increased. High levels may cause instability.
ASR Proportional Gain 2 is activated by programming one of the input terminals (3 through 8) to “ASR Gain Switch
(setting “77”) and closing a contact to it.
Minimum Maximum Description
000.00
300.00
Automatic Speed Regulator Gain
Default Setting
020.00
48 VS-616PS5 Installation & Quick Start Manual
C5 – 02
C5 – 04
ASR Integral Gain 1
ASR Integral Gain 2
The Integral Gain adjusts the speed of response to a load change. Response become more noticeable as the gain is decreased. Low levels may cause instability.
ASR Integral Gain 2 is an additional integral gain adjustment.
Minimum Maximum Description
00.000
10.000
Automatic Speed Regulator Integral Time
Default Setting
00.500
Additional Reference Parameters
D1 – 05
D1 – 06
D1 – 07
D1 – 08
Preset Speed Reference 5
Preset Speed Reference 6
Preset Speed Reference 7
Preset Speed Reference 8
Minimum Maximum Description
000.00
100.00
Preset Speed References
Default Setting
000.00
There are now eight preset speed references available, which can be controlled by the input terminals.
Terminal 5
Set H1-03 = 3
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
Terminal 6
Set H1-04 = 6
OPEN
OPEN
CLOSED
CLOSED
OPEN
OPEN
CLOSED
CLOSED
Terminal 7 Selected Speed Reference
Set H1-05 = 7
OPEN
OPEN
OPEN
OPEN
Speed Reference 1 - D1-01 supplies speed reference
Speed Reference 2 - D1-02 supplies speed reference
Speed Reference 3 - D1-03 supplies speed reference
Speed Reference 4 - D1-04 supplies speed reference
CLOSED Speed Reference 5 - D1-05 supplies speed reference
CLOSED Speed Reference 6 - D1-06 supplies speed reference
CLOSED Speed Reference 7 - D1-07 supplies speed reference
CLOSED Speed Reference 8 - D1-08 supplies speed reference
VS-616PS5 Installation & Quick Start Manual 49
Reference Limits
D2 – 01 Reference Upper Limit
Sets the maximum reference as a percent of maximum speed, E7-06.
Minimum Maximum Description
000.0
110.0
Speed Reference Upper Limit
Default Setting
100.0
D2 – 02 Reference Lower Limit
Sets the minimum reference as a percent of maximum speed as entered in E1-06.
Minimum Maximum Description
000.0
100.0
Speed Reference Upper Limit
PG Option Set-up
F1 – 02 Disconnection Detection Stopping Method
Selects the stopping method when a disconnected PG is detected.
Setting Description
0 Ramp to stop - according to C1-02. (Declaration time 1)
1
2
3
Coast to stop (factory default).
Fast - stop - according to C1-09.
Alarm flashes, operation continues.
Default Setting
100.0
F1 – 03 Overspeed Detection Stopping Method
Selects the stopping method when an overspeed condition is detected.
Setting Description
0 Ramp to stop - according to C1-02 (Declaration time 1).
1
2
3
Coast to stop (factory default) .
Fast-stop - according to C1-09.
Alarm flashes, operation continues. (
F1 – 04 Deviation Detection Stopping Method
Selects the stopping method when excessive speed deviation is detected.
50
Setting Description
0
1
Ramp to stop - according to C1-02 (Declaration time 1).
Coast to stop.
2
3
Fast-stop - according to C1-09.
Alarm flashes, operation continues (factory default).
VS-616PS5 Installation & Quick Start Manual
PG-P2 Setup
F8 – 02 Pulse Input Moving Average Value
Sets the number of scans the pulse input reference signal is averaged over. A larger number will provide a more stable reference (internal). However, the inverter response to a rapid change in the pulse train frequency may be slow. A setting of “0” or “1”means no moving average will be used, and the pulse input reference will be updated every scan.
Minimum Maximum Description
0 50 Pulse Input moving Scan width.
Default Setting
0
VS-616PS5 Installation & Quick Start Manual 51
Terminal Designation Options
When the inverter is initialized (A1-03) to “2220” (2-wire operation), terminal 1 is FWD RUN, and terminal 2 is REV
RUN. Connecting either input with a contact to terminal 11 causes the inverter to run in that direction as long as the contact is closed, and to stop running when the contact is opened.
When the inverter is initialized (A1-03) to “3330” (3-wire operation), terminal 1 is the START input and terminal 2 is the STOP input. The inverter runs after START is connected momentarily to terminal 11 provided STOP is already connected to terminal 11. The inverter will continue to run until the STOP input is opened. Terminal (5) will be set to
“00” to act as a FORWARD/REVERSE input.
H1 – 01 to H1 - 06 Multifunction Input Terminals Selection
Default assignments are as follows (all contact closures are to terminal 11):
Input
Terminal
3
4
5
6
7
8
Parameter
H1-01
H1-02
H1-03
H1-04
H1-05
H1-06
Default
Setting
24
14
3
4
6
8
Default Function
External Fault – close contact to trip inverter off
Fault Reset – close contact to reset faults in inverter
Preset Reference Selector 1 – close contact to select preset speeds
Preset Reference Selector 2 – close contact to select preset speeds
Jog Reference – close contact to select preset jog speed reference
External Baseblock (N.O.) – close contact to disable inverter output
The following settings are available for the terminals. Unless otherwise indicated, closing a normally open contact to terminal 11 activates the input terminal function.
15
1A
1B
1E
1F
24
71
77
F
10
11
12
13
14
9
A
B
C
E
6
7
8
Setting
0
1
2
3
4
5
Function
3-wire control
Local/Remote
Internal/Option
Preset Reference 1
Preset Reference 2
Preset Reference 3
JOG Reference
Accel/Decel Select 1
External Baseblock NO
External Baseblock NC
Accel/Decel Ramp Hold
Inverter OH2 Alarm
Terminal 16 Enable
ASR Integral Reset
No Operation
MOP Increase
MOP Decrease
Forward JOG
Reverse JOG
Fault Reset
Fast Stop
Accel/Decel Select 2
Program Lockout
Reference Sample Hold
Terminal 13/14 Switch
External Fault
Speed/Torque Control
ASR Gain Switch
The terminal set to “0” becomes the Forward/Reverse input
Selects the operation mode (open = Local). Inverter must be stopped.
Selects Reference source (open = internal, closed = option card)
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
Selects Jog Preset Reference when closed. RUN input must be active
Selects alternate Accel/Decel rates when closed (see C1-03 and C1-04)
Disables output of inverter when contact closes
Disables output of inverter when contact opens
Stops ramping when closed, resumes ramping when opened
External temperature alarm input, causes display to blink “OH2”
Enables the analog input at terminal 16 when closed
Resets Integral control values of inverter when closed
Terminal is not being used
Accelerate while closed with MOP decrease open, otherwise no effect
Decelerate while closed with MOP increase open, otherwise no effect
Run forward at Jog preset speed reference D1-09 while closed
Run reverse at Jog preset speed reference D1-09 while closed
Resets Inverter faults while closed; must be opened to run again
Causes inverter to stop at Fast Stop decel rate (C1-09)
Selects alternate Accel/Decel rates when closed
Prohibits changing of PS5 parameters while open
Samples frequency reference if closed for 100 ms or longer
Selects terminal 13 input (open) or terminal 14 input(closed)
Shuts off inverter when closed, displays “oPE_” on operator
Selects Speed control (open) or torque control (closed)
Switches Gain values in ASR (see C5-01 / C5-02)
Consult the VS-616PS5 Programming Manual for more comprehensive discussions of the parameters.
52 VS-616PS5 Installation & Quick Start Manual
H2 – 01 to H2 – 03 Digital Outputs
Default assignments are as follows:
Output
Terminals
9 – 10
25 – 27
26 - 27
Parameter
H2-01
H2-02
H2-03
Default
Setting
0
1
2
Default Function
RUN output – closes while inverter is running
Zero Speed output – closes while output speed is less than E1-09
Up to Speed – closes when set speed is attained within tolerance (L4-02)
Listed below are other settings for the digital outputs:
Setting
C
D
E
8
9
A
B
F
3
4
5
6
7
Function
Speed Match
Speed Low
Speed High
Inverter Ready
DC Bus Undervoltage
Baseblock 1
Speed from Operator
Control from Operator
Over Torque Detection
Reference Loss
DBR Overheat
Fault
No Operation
Speed Matches Setting – closes when output speed = L4-01 +/- L4-02
Speed Below setting – closes while output speed < L4-01
Speed Above Setting – closes while output speed > L4-01
Ready to Run – closes when inverter has no faults or alarms
Closes when DC Bus level or power supply is below trip level
Closes when inverter output is disabled by a Baseblock command
Closes while the speed reference is supplied from the digital operator
Closes when the RUN command comes from the digital operator
Closes when torque output exceeds setting
Closes when speed reference drops 90% in less than 400 ms
Closes while Dynamic Braking resistor is overheated or on DB fault
Closes when a fault occurs
Output is not being used
Consult the VS-616PS5 Programming Manual for more settings and more comprehensive descriptions.
H3 – 01 to H3 – 03 Analog Input 1
These parameters set up Analog input 1 (Terminal 13), with terminal 17 common
Parameter
H3-01
H3-02
H3-03
Function
Terminal 13 Signal 0: 0 to 10 VDC 1: +/-10 VDC
Terminal 13 Reference % Gain
Terminal 13 Reference +/- Bias
Units
- -
%
%
Range
0/1
0.0 – 1000.0
+/-100.0
Consult the VS-616PS5 Programming Manual for the setup of Analog Input 2 and Analog Input 3.
Default
0
100.0
0.0
H4 – 01 to H4 – 07 Analog Outputs
These parameters set up Analog input 1, with terminal 17 common
Parameter
H4-01
H4-02
H4-03
H4-04
H4-05
H4-06
H4-07
Description
Terminal 21 Analog Output Signal
Terminal 21 Output Gain
Terminal 21 Output Bias
Terminal 23 Analog Output Signal
Terminal 23 Output Gain
Terminal 23 Output Bias
Output Signal Selection (both)
Units
- -
- -
%
- -
- -
%
- -
Range
0…53
0.00 – 2.50
0.0 – 10.0
0…53
0.0 – 1000.0
0.0 – 10.0
0/1
Default
5
1.00
0.0
3
1.00
0.0
0
Consult the VS-616PS5 Programming Manual for further information on the Analog Outputs.
VS-616PS5 Installation & Quick Start Manual
Default Function
Motor Speed
Gain = 1
Bias = 0
Output Current
Gain = 1
Bias = 0
0 – 10 VDC
53
L2 Power Loss Ride-through
When momentary power loss occurs, Power Loss Ride-through function is disabled.
L2-01 Momentary Power Loss Ride-through
Selects whether the inverter stops when power loss is detected or “rides through” a momentary power loss. When ride-through operation is selected, speed search starts from the current output frequency.
Setting Explanation
0 Momentary Power Loss Disabled
1 Momentary Power Loss Enabled
Default
X
Momentary power loss ride-through is disabled (factory default) . When momentary power loss is detected, a fault contact trips, stopping the inverter.
L2-02 Momentary Power Loss Ride-through Time
Minimum Maximum Description
0.0
2.0
Momentary Power Loss Ride through Time (Sec).
Default Setting
Model Dependant
Sets the ride-through time allowed before the inverter trips, after momentary power loss. This setting is activated when L2-01 is set to “1.” If power is restored within this time, operation restarts automatically. If power is not restored within this time, a fault contact trips, stopping the inverter.
54 VS-616PS5 Installation & Quick Start Manual
L3 Stall Prevention/Current Limit
This function automatically adjusts the deceleration rates in order to continue operation without tripping the inverter.
L3-01 Over-voltage Protection (Stall Prevention During Deceleration)
If deceleration times are set too short for load conditions, the inverter automatically extends the deceleration time according to the main circuit DC bus voltage level. When using an optional braking resistor for the VS-616PS5, set parameter L3-01 to”0”.
Setting Explanation
0
Stall prevention during deceleration is disabled. An excessively short deceleration time will generate an overvoltage fault (OV), and the motor will coast.
1
Stall prevention during deceleration is enabled (factory default) .
The DC bus voltage level is monitored, and the deceleration rate is automatically extended to prevent an overvoltage condition. This deceleration time may be longer than the set value (C1-02).
Default
X
Frequency
Adjusts the deceleration time to prevent overvoltage fault (OV).
Time
Set Deceleration Time
VS-616PS5 Installation & Quick Start Manual 55
L4 Reference Detection
Used in conjunction with the multi-function digital outputs to indicate speed agree conditions.
Refer to section H2 , Digital Outputs , for more detailed information on setting these functions.
L4-01 Speed Agree Detection Level (without sign)
Sets the detection level for the desired frequency agree 1 and frequency detection 1 & 2 functions. The set detection level is effective during both FWD and REV operation.
Minimum Maximum Description
0.0
100.0
Speed agree Detection Level (without sign).
Default Setting
0.0
L4-02 Speed Agree Detection Width
Sets the detection width for frequency and desired frequency agree 1 and frequency detection 1 & 2 functions.
Minimum Maximum Description
0.0
100.0
Speed agree Detection Width.
Default Setting
2.0
56 VS-616PS5 Installation & Quick Start Manual
L5 Fault Restart
After a fault occurs, the inverter and its fault detection circuit can be reset. The automatic restart function allows the inverter to continue operation after certain faults.
L5-01 Number of Automatic Restart Attempts
Sets the number of automatic restart attempts. Setting to “0” disables this function.
Minimum Maximum Description
0.0
10 Number of Automatic Restart Attempts.
The inverter can be set to automatically restart after the following faults occur:
Overcurrent (OC)
Overvoltage (OV)
Undervoltage PUV (UV1)
Ground fault (GF)
Regenerative transistor fault (rr)
Default Setting
0
L5-02 Automatic Restart Operation Selection
Selects whether a fault contact output is activated during automatic restart.
Setting Explanation
0
No fault relay (factory default)
1
Fault relay is active
Default
X
VS-616PS5 Installation & Quick Start Manual 57
L6 Torque Detection
The overtorque detection circuit activates when the motor load causes the motor current (or torque) to exceed the overtorque detection level (L6-02) .
L6-01 Overtorque Detection 1 Selection
Activates overtorque detection, and selects whether detection generates an alarm or a fault.
Setting Explanation
0
Overtorque detection is disabled .
1
Overtorque detection is enabled whenever at the speed agree level (when inverter is not accelerating or decelerating). Continue running after detection (OL3 alarm).
2
3
Overtorque detection is enabled always. Continue running after detection (OL3 alarm).
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after detection (OL3 fault).
Default
X
4
Overtorque detection is enabled always. Coast to a stop after detection (OL3 fault).
Notes:
1.To detect torque during acceleration or deceleration, set to “2” or “4.”
2.To continue operation after overtorque detection, set to “1” or “2.” During detection, the digital operator dis plays an “ OL3 ” alarm (blinking).
3.To stop the inverter after an overtorque detection fault, set to “3” or “4.” During detection, the digital opera tor displays an “ OL3 ” fault.
L6-02 Overtorque Detection 1 Level
Sets the overtorque detection level as a percentage of motor rated torque.
Minimum Maximum Description
0 300 Overtorque Detection 1 Level.
Default Setting
150
L6-03 Overtorque Detection 1 Time
The overtorque detection delay time inserts a delay, between the time motor current (or torque) exceeds the overtorque detection level (L6-02) and when the overtorque detection function is enabled. The digital operator then displays “ OL3 .”
Minimum Maximum Description
0.0
10.0
Overtorque Detection 1 Time.
Default Setting
0.1
58 VS-616PS5 Installation & Quick Start Manual
L7 Torque Limit
The torque limit function limits the amount of motor torque in all four quadrants of vector control operation:
• Forward Motoring • Forward Regenerating
• Reverse Motoring • Reverse Regenerating
Torque limit is activated in both the speed and torque control modes.
L7-01 Forward Torque Limit
Sets the motoring side torque limit value during FWD run.
Default Setting
150
Minimum Maximum Description
0 300 Forward Torque Limitl.
L7-02 Reverse Torque Limit
Sets the motoring side torque limit value during REV run.
Minimum Maximum Description
0 300 Reverse Torque Limit.
Default Setting
150
L7-03 Regenerative Forward Torque Limit
Sets the regenerating side torque limit value during FWD run.
Minimum Maximum Description
0 300 Regenerative Forward Torque Limit.
Default Setting
150
L7-04 Regenerative Reverse Torque Limit
Sets the regenerating side torque limit value during REV run
.
Minimum Maximum Description
0 300 Regenerative Reverse Torque Limit.
Default Setting
150
REV Run Regeneration
Torque Limit (L7-04)
REV Motor Rotation
Positive Torque Reference
0
REV Run Motor
Torque Limit (L7-02)
FWD Run Motor
Torque Limit (L7-04)
FWD Motor Rotation
FWD Run Regeneration
Torque Limit (L7-03)
Negative Torque Reference
VS-616PS5 Installation & Quick Start Manual 59
O Operator Parameters
O1-01 Monitor Selection
T
he operation menu allows the viewing of four monitor variables. These are N ref
, N out
, I out
, and a user-selected monitor. Using the table below, set this parameter to the setting corresponding to the monitor item desired for the user monitor.
48
49
50
51
52
44
45
46
47
33
41
42
43
29
30
31
32
21
22
27
28
17
18
19
20
Setting
5
6
7
15
16
8
9
Description
Motor speed
Output voltage (factory default)
DC bus voltage
Output power
Torque reference (internal)
Terminal 13 input voltage level
Terminal 14 input voltage or current level
Terminal 16 input voltage level
Motor secondary current (Iq)
Motor excitation current (Id)
SFS output frequency
ASR input
ASR output
Voltage reference (Vd output)
CPU ID number
Voltage limit control output qAxis current control output dAxis current control output
Output voltage reference (Vq)
Output voltage reference (Vd)
LED check
Internal control status 2
Command 1 from option
Command 2 from option
External torque reference
Torque compensation value
DO-08H output status
Momentary power loss decrease capacity
Control section software number
Speed detection PG counter value
PID feedback
DI-16H input status
60 VS-616PS5 Installation & Quick Start Manual
O1-02 Monitor Selection After Power-up
Selects the monitor to be displayed on the digital operator immediately after the power supply is turned ON.
Setting
1
2
3
4
Description
Displays frequency reference (factory default) .
Displays output frequency.
Displays output current.
Displays the monitor item set in O1-01 .
O1-03 Reverse Torque Limit
Units for parameters and monitors related to frequency can be scaled as shown below.
Setting
1
2 ~ 39
40 ~ 3999
Description
Unit: 0.01%. Speed reference is displayed as P ¨¨
.
¨¨
• Unit: rpm (Enter the # of poles in the motor).
• The speed reference is displayed as n ¨¨¨¨
Digits: 5th 4th 3rd 2nd 1st
0 0 0 0 0
The 1st through 4th digits determine the set value at 100% output frequency.
The decimal point position is set with the 5th digit of O1-03, as follows:
5th digit = 0: displayed as ¨¨¨¨
5th digit = 1: displayed as ¨¨¨ .
¨
5th digit = 2: displayed as ¨¨ .
¨¨
5th digit = 3: displayed as ¨ .
¨¨¨
(Example 1)
If 100% output speed is equal to 200.0 units:
Set O1-03 = “12000”
100% of this reference is displayed as 200.0 and 60% of this reference is displayed as 120.0.
Example 2
If 100% output speed is equal to 65.00:
Set O1-03 = “26500”
60% of this reference is displayed as 39.00.
VS-616PS5 Installation & Quick Start Manual 61
O2 Key Selection
O2-01 Local/Remote Key
Enables/disables the digital operator LOCAL/REMOTE key.
Setting Explanation
0
Local/Remote key is disabled.
1
Local/Remote key is enabled (factory default) .
Depressing the Local/Remote key switches operation commands between the digital operator and the settings of B1-01 & B1-02 .
Default
X
O2-02 STOP Key During External Terminal Operation
Enables/disables the digital operator STOP key, during operation from the external terminals and during serial communication.
Setting Explanation
0
The digital operator STOP key is disabled when Run command does not come from the digital operator
1
The digital operator STOP key is always enabled.
The STOP key is enabled even during external terminal operation and serial communication.
Default
X
O2-04 Inverter Model Selection
Sets the inverter capacity, according to the model number. Control parameters with defaults specific to the inverter’s capacity are set automatically (i.e. carrier frequency, motor data, etc.). This parameter does not need changing, unless the control board is replaced.
Minimum Maximum Description
00 FF Inverter Model Selection.
Default Setting
--
62 VS-616PS5 Installation & Quick Start Manual
6.1 Precautions ............................................................................................63
6.2 Maintenance and Inspection .................................................................64
Periodic Inspection .................................................................................64
Parts Replacement Schedule.................................................................64
6.3 Alarm and Fault Displays .......................................................................65
Fault Classes .........................................................................................65
Fault Diagnosis and Corrective Actions .................................................66
Motor Faults ...........................................................................................70
6.1
Precautions
T
HE
VS-616PS5 I
NVERTER USES AND GENERATES HIGH VOLTAGES WHICH MAY BE LETHAL
.
M
AINTENANCE AND
S
ERVICE MUST BE PERFORMED BY EXPERIENCED PERSONNEL
.
1. Turn OFF power to the inverter and wait until all LED’s are off before removing any covers.
2. Before touching any power terminals, test for voltage:
• between terminals you might touch
• between terminals and ground
3. Replace all covers and guards before turning on power to the inverter.
T
HE
VS-616PS5 I
NVERTER EMPLOYS STATIC SENSITIVE COMPONENTS
.
M
AINTENANCE AND
S
ERVICE MUST BE PERFORMED BY EXPERIENCED PERSONNEL
.
1. DO NOT touch any printed circuit boards while power is on.
2. DO NOT connect or disconnect any wires or connectors while power is on.
3. Use static safe procedures when changing boards
Failure to observe safety precautions will expose the user to high voltages, which may result in equipment damage, serious personal injury, or death!
VS-616PS5 Installation & Quick Start Manual 63
6.2 Maintenance and Inspection
Periodic Inspection
The VS-616PS5 will supply extended, reliable, service if it is kept clean, cool, and dry, and if it is well maintained.
Periodic inspections should be made to ensure that all of the guidelines and precautions in this manual have been followed.
To prevent electrical shock, turn off power and wait five minutes before servicing the inverter. Inspect the inverter according to the following table:
Component
External Terminals
Connectors
Mounting Screws
Heatsink
Printed Circuit Boards
Cooling Fan
Power Components
Smoothing Capacitors
Check for
Loose screws or connectors
Build up of dust and dirt
Accumulation of conductive residue
Abnormal noise or vibration
Accumulation of dust and dirt
Discoloration, deformation, or odor
Corrective Action
Securely Tighten all screws and connectors.
Clean off any foreign material
Clean off board or replace board.
Replace Fan
Clean off any foreign material
Replace capacitor
When cleaning the components, use clean, dry compressed air at the least pressure necessary, but in no case greater than 90 PSI (6 kg/cm
2
).
Parts Replacement Schedule
To extend the operating life of the VS-616PS5 inverter, replace parts according to the following schedule. Doing so may help to avoid an unexpected shutdown.
Part
Cooling Fan
Smoothing Capacitor(s)
Breakers or Relays
Fuses
Aluminum Electrolytic
Capacitors on Printed Circuit
Boards
Approximate Interval
2 to 3 years
5 years
As Needed
10 years
5 years
Remarks
Replace with new fan
Replace with new capacitors
If inspection warrants replacement
Replace with new ones
Replace with new capacitors or replace PCB
Optimum Operating Conditions
• Ambient Temperature:86°F yearly average
• Load Factor: 80% or below
• Operation time: 12 hours per day or less
Consult the motor manufacturer’s manual for inspection and maintenance instructions of the motor.
64 VS-616PS5 Installation & Quick Start Manual
6. 3 Alarms and Fault Displays
Fault Classes
A: MAJOR Fault
• Motor coasts to a stop.
• Operation Indicator lights.
• Fault Output (terminals 18 and 19) is activated
B: FAULT
• Operation continues
• Operation indicator lights
• Multi-function output (if selected) activates
• Fault Output (terminals 18 and 19) is NOT activated
C: ALARM (warning)
• Operation cannot be performed
• Operation Indicator lights
• No fault outputs
When the VS-616PS5 detects a major fault, the fault is displayed on the digital operator and activates a fault contact output, after which the motor coasts to a stop. Check the causes listed by the fault code in the following tables and take the corrective actions necessary.
To restart the inverter, remove any RUN commands present, and reset the inverter with the digital operator or an input, if selected. Cycling the power will also reset the inverter. If the corrective actions suggested do not clear the problem, contact your representative.
Alarms do not activate fault contact outputs. Once the cause of the alarm is removed, the inverter clears the alarm status.
Fault Display
UV1
DC Bus
Undervoltage
UV2
CTL PS
Undervoltage
UV3
MC Answerback
UV
Under Voltage
OC
Overcurrent
Name
Main circuit undervoltage (PUV)
Description
Undervoltage in the DC main circuit during running.
Detection level:
230V class: Approx. 190V or less
460V class: Approx. 380V or less
Undervoltage in the control circuit during running.
Corrective Action
• Check the power supply wiring.
• Correct the line voltage
Control circuit undervoltage (CUV)
MC fault The pre-charge contactor opened during running.
Momentary power loss • The main circuit DC voltage fell below the PUV level.
• The control power source fell below the CUV level.
• The pre-charge contactor opened.
Overcurrent (OC) The inverter output current exceeded the OC level. ( ~ 200% Inverter rating)
−
• Check the motor coil resistance.
• Extend the accel/decel time.
• Check the motor insulation.
• Multi-meter check.
Class
A
A
A
C
A
VS-616PS5 Installation & Quick Start Manual 65
Fault Diagnosis and Corrective Actions (continued)
Fault Display
GF
Ground Fault
Name
Ground fault (GF)
Description
Inverter output grounding current exceeded
50% of inverter rated current.
Corrective Action
Check that motor insulation has not deteriorated.
Check that connection between inverter and motor is not damaged.
OV
Overvoltage
SC
Short Circuit
PUF
DC Bus Fuse
Open
OH
Heatsink Over temp
OL1
Motor Overloaded
OL2
Inv Overloaded
OL3
Overtorque 1
OL4
Overtorque 2
PF
Input Phase
Loss
LF
Output Phase
Loss
RR
Dyn Brk Transistor
RH
Dyn Brk Resistor
OS
Over Speed
PGO
PG open
Overvoltage (OV)
The main circuit direct current voltage exceeded the OV level.
Detection level:
230 V class: Approx. 400 V
460 V class: Approx. 800 V
Load short-circuit (SC) Inverter output (load) is short-circuited.
Fuse blown (FU)
Heatsink overheat
(OH1)
Motor overload (OL1)
Inverter overload
(OL2)
Overtorque
Input open-phase
Output open-phase
Braking transistor failure
Braking resistor unit overheat
Overspeed (OS)
The DC bus fuse is blown.
The output transistors were damaged.
The transistor heatsink temperature exceeded the allowable value.
Inverter output exceeded the motor overload level.
Inverter output exceeded the inverter overload level (thermo switch).
The torque reference exceeded the detection level for longer than the specified time.
Inverter input power supply has open phase.
Large unbalance in input voltage.
Inverter output has open-phase.
The braking transistor has failed.
The braking resistor unit temperature has exceeded the allowable value.
(Protects only inverter built-in type)
The motor speed exceeded the overspeed level. (F1-08)
PG open circuit (PGO) The PG line is broken.
Extend the deceleration time, add braking circuit.
Check the motor coil resistance.
Check the motor installation.
Check for damaged transistor, load side short circuit, grounding, etc.
Check the fan and ambient temperature.
Reduce the load.
Reduce the load, extend the acceleration time.
Verify the parameter setting, reduce the load at the motor.
Check the line voltage.
Re-tighten the input terminal screws.
Check the output wiring.
Check the motor impedance.
Re-tighten the output terminal screws.
The inverter requires repair.
Reduce the regenerative load.
-
Check the PG line.
Check the condition of the motor lock or excessive load.
Class
A
A
A
A
A
A
A
A
B
A
A
A
A
A
A
66 VS-616PS5 Installation & Quick Start Manual
EF4
External Fault 4
EF5
External Fault 5
EF6
External Fault 6
EF7
External Fault 7
EF8
External Fault 8
OPE01 kVA Selection
OPE02
Limit
OPE03
Terminal
Fault Display
DEV
Speed Deviation
STO
Step Out
Zdev
Phase Z Pulse
Fault
EF
External Fault
BB
Base Block
EF3
External Fault 3
Name
Speed deviation
(DEV)
Stepout
Phase Z pulse fault
(Marker Pulse)
Simultaneous forward/ reverse run commands
External base block
External fault at terminal 3
Description
The deviation of the speed reference and speed feedback exceeded the regulation level. (F1-10)
Corrective Action
Check the load.
Motor has pulled out of synchronization with the applied stator field.
An uncontrolled motor state results from an incomplete PG origin pulse adjustment or from a failed initial magnetic pole estimation.
• Check the motor constants.
• Check the motor temperature.
• Reduce the ASL gain (C5-
01).
• Reduce the acceleration (C1-
01).
• Check the PG cable connection.
• Repeat auto-tuning (set T1-
03 = 1, then T1-02 = 2, and press the digital operator
RUN key).
Both FWD and REV run commands are simultaneously input for 500ms or longer.
External base block command is input from control circuit terminal.
Fault occurred in the external control circuit.
Check sequence circuit.
Check sequence circuit.
Check the condition of the input terminal. If the LED lights when the input is not activated, then the inverter requires repair.
Class
B
A
A
B
B
A
External fault at terminal 4
External fault at terminal 5
External fault at terminal 6
External fault at terminal 7
External fault at terminal 8 kVA setting error
(OPE01)
Parameter setting range error (OPE02)
Multi-function input setting error (OPE03)
Fault occurred in the external control circuit.
Check the condition of the input terminal. If the LED lights when terminal is not connected, then the inverter requires repair.
Inverter kVA setting error.
Parameter data is out of range.
Multi-function input settings in H1-01 to H1-06 are not in ascending order. Or, set values other than “F” are overlapping
Check and set the parameter data (O2-04) .
Check the parameter data settings.
Check the function selection.
B
C
C
C
OPE05
Option reference selection fault
(OPE05)
• C-option is not connected although run command from C-option is selected
• C-option is not connected although frequency reference from C-option is selected
• Check and set the contstant data.
• Connect the C-option.
OPE06
Control method selection fault (OPE06)
PG control card is not connected during flux vector control.
VS-616PS5 Installation & Quick Start Manual
Connect PG control card.
D
D
67
Fault Display
OPE07
Name
Multi-function analog input selection fault
(OPE07)
Description
C-option is A1-14B and option/inverter change is selected.
Corrective Action
Check and set the constant data.
OPE08
OPE0 10
OPE0 12
OPR
ERR
EEPROM R/W
Err
CPF00
COM-ERR
(OP&INV)
CPF01
COM-ERR
(OP&INV)
CPF02
BB Circuit Err
CPF03
EEPROM Error
CPF04
Internal A/D Err
CPF05
External A/D Err
Multi-function input/ output selection fault
(OPE08)
R/min setting fault
(OPE10)
Energy-saving control constants setting fault
Digital operator fault
(OPr)
EEPROM writing fault
(ERR)
Control circuit fault 1
(CPF00)
Digital operator transmission fault
Control circuit fault 2
(CPF01)
Digital operator transmission fault
Base block circuit fault
(CPF02)
EEPROM fault
(CPF03)
CPU internal A/D converter fault (CPF04)
CPU external A/D converter fault (CPF05)
Any of the following setting faults has occurred:
• The setting unused in the control method is selected for F4-01 and F4-04.
• The setting unused in the control method is selected for F5-01 and F4-02.
• The setting unused in the control method is selected for H1-01 and H1-06.
• The setting unused in the control method is selected for H2-01 and H2-03.
• The setting unused in the control method is selected for H3-05 and H3-09.
• The setting unused in the control method is selected for H4-01 and H4-04.
• The setting unused in the control method is selected for o1-01.
The settings of E1-06 to E1-08 do not satisfy the following conditions:
E1-06 E1-07 E1-08
Energy-saving control constant values are out of range.
The digital operator was disconnected during operation by run command from the digital operator.
EEPROM internal data did not match when initializing the parameter.
Transmission between the inverter and digital operator cannot be established 5 seconds after supplying power.
MPU peripheral element check fault (on-line)
Transmission between the inverter and digital operator is established once after supplying power, but later transmission is interrupted for more than 2 seconds.
MPU peripheral element check fault (on-line).
Inverter PCB control board fault.
Check and set the constant data.
Check and set the constant data.
Check and set the constant data.
• Check the wiring cable and the digital operator connection.
• Replace the control card.
Replace the control board.
Insert the operator connector again.
Check the wiring of control circuit.
Replace the control board.
Insert the digital operator connector again.
Check the digital control circuit wiring.
Replace the control board.
Replace the control board.
Class
D
D
D
D
A
B
A
A
A
68 VS-616PS5 Installation & Quick Start Manual
Fault Display
CPF06
Option Error
CPF20
Option A/D Error
CPF23
BUS
Name
Option connection fault (CPF06)
A/D converter fault in analog speed reference card (CPF20)
Cross-diagnose fault between transmission option and control card (CPF23)
Transmission fault with transmission option (bUS)
EF0
External fault from transmission option
(EFO)
Description
The option card is not installed correctly.
Option card (AI-14B) A/D converter fault
Corrective Action
Install the option card again.
Replace the option card.
Diagnosis data has not been updated for more than 0.2 seconds between the transmission option and the control card.
Transmission fault with transmission option
(detected when the fault continued for 2.5 seconds).
• Check the transmission option contact part.
• Replace the transmission option.
Check the transmission devices and the transmission signals.
External fault was input from the transmission option.
External fault, defined by user specification, was input from the transmission option. Find the external fault items from the I/O list and correct it.
Class
A
A
A
A
B
VS-616PS5 Installation & Quick Start Manual 69
Motor Faults
If a motor fault occurs, follow the checkpoints listed in the table below and take the corresponding corrective actions. If taking the corrective actions described does not solve the problem, contact your Yaskawa representative immediately.
Motor Faults and Corrective Actions
Fault
Motor does not rotate
Motor rotation reverses
Motor rotates, but variable speed not available.
Check Point
Power supply voltage applied to power supply terminals L1, L2, L3? Charge LED is ON?
Use rectifier type voltmeter to test. Voltage output to output terminals T1, T2, T3 correct?
Motor locks due to excessive load?
Fault displayed in operator display?
FWD or REV run command entered?
Frequency setting voltage entered (when using terminals 13 or 14)?
Are reference and run source settings correct?
Wiring of terminals T1, T2, T3 correct?
FWD and REV wiring run signals entered?
Wiring of frequency setting circuit correct?
Are reference and run source settings correct?
Load excessively large?
Corrective Action
• Turn ON power supply.
• Turn OFF power supply, and then ON again.
• Check power supply voltage.
• Make sure terminal screws are tight.
Turn OFF power supply, then turn ON again.
Reduce the load and release the lock.
Check troubleshooting table on page 52.
Check the wiring.
• Check the wiring.
• Check frequency setting voltage.
Check reference and run source selections
(B1-01, B1-02) .
Match wiring to the phase order of the motor leads T1, T2, T3.
Correct the wiring.
Correct the wiring.
Check reference and run source selections
(B1-01, B1-02) .
Reduce the load.
70 VS-616PS5 Installation & Quick Start Manual
A.1
A.2
A.3
Terminal Functions ....................................................................................................................A-1
230V Class Terminal Functions.................................................................................................A-1
460V Class Terminal Functions.................................................................................................A-1
Wire Sizes and Terminal Screw Sizes.......................................................................................A-2
230V Class Wire Size................................................................................................................A-2
460V Class Wire Size................................................................................................................A-3
JST Closed Loop Connectors ...................................................................................................A-4
A.1
Terminal Functions
230V Class Terminal Functions
Model CIMR-PS5U
Nominal Motor Output
L1, L2, L3
T1, T2, T3
B1, B2
-
+ 1
+ 2
+ 3
GND
20P4 to 27P5
0.5 to 10 HP
Main power supply input: 200 to 230 VAC, 3 Ø, 50/60 Hz
Inverter output: 200 to 230 VAC, 3 Ø, 200 Hz max
Braking Resistor Unit
2011 to 2015
15 to 20 HP
DC Power Supply +1 to -
DC Reactor +1 to +2
DC Power Supply +1 to -
DC Reactor +1 to +2
Braking Unit +3 to -
- -
Earth Ground Terminal (Resistance to earth = 100 ohms or less)
460V Class Terminal Functions
Model CIMR-PS5U
Nominal Motor Output
L1, L2, L3
T1, T2, T3
B1, B2
-
+ 1
+ 2
+ 3
S
R
40P4 to 4015
0.5 to 25 HP
4018 to 4045
30 to 75 HP
4055 to 4160
100 to 200 HP
Main power supply input: 380 to 460 VAC, 3 Ø, 50/60 Hz
Inverter output: 380 to 460 VAC, 3 Ø, 200 Hz max
Braking Resistor Unit
DC Power Supply +1 to -
DC Reactor +1 to +2
DC Power Supply +1 to -
Braking Unit +3 to -
Braking Unit +3 to –
- -
- -
Cooling Fan Power
Supply
_ _
4185 to 4300
250 to 500 HP
Braking Unit +3 to -
(No +1 or +2 terminals provided)
- -
Control power Supply
R to S200: 200 to 230 VAC 1
Ø
R to S400: 380 to 460 VAC 1Ø
S200
S400
GND Earth Ground Terminal (Resistance to earth = 10 ohms or less)
VS-616PS5 Installation & Quick Start Manual Page A-1
A.2
Wire Sizes and Terminal Screw Sizes
230V Class Wire Size
Circuit
Model
CIMR-
PS5U20P4
Terminal Symbol
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
Terminal
Screw
M4
PS5U20P7
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS5U21P5
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
M4
M4
PS5U22P2
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS5U23P7
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS5U25P5
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS5U27P5
L1, L2, L3, , ⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS5U2011
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
PS5U2015
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
M4
M4
M5
M5
M6
M8
M6
Common to all models
1-33
G
M3.5
M3.5
Wire Size *
AWG mm 2
14 - 10 2 - 5.5
10 5.5
3
8
4
8
8
10 - 8
8
10 - 8
8
5.5 - 8
8
5.5 - 8
22
8
30
8
Stranded
0.5 - 1.25
20 - 16
Solid
0.5 - 1.25
20 - 14 0.5 - 2
Max. Torque lb-in (N·m)
12.4 (1.4)
14 - 10 2 - 5.5
12.4 (1.4)
14 - 10 2 - 5.5
12 - 10 3.5 - 5.5
12.4 (1.4)
12 - 10 3.5 - 5.5
12.4 (1.4)
12.4 (1.4)
22.1 (2.5)
22.1 (2.5)
45.1 (5.1)
90.3 (10.2)
45.1 (5.1)
-
8.9 (1.0)
Wire Type
Power cable:
600V vinyl sheathed wire or equivalent
* Wire sizes are based on 75°C copper wire.
Page A-2 VS-616PS5 Installation & Quick Start Manual
460V Class Wire Size
Circuit Model
CIMR-
Terminal Symbol
PS55U40P4 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U40P7 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U41P5 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U42P2 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U43P7 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U44P0 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U45P5 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U47P5 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U4011 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
PS55U4015 L1, L2, L3, ,
⊕ 1, ⊕ 2, B1, B2, T1, T2, T3
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
PS55U4018 r, s
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
PS55U4022 r, s
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
PS55U4030 r, s
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
PS55U4037 r, s
L1, L2, L3, , ⊕ 1, ⊕ 2, ⊕ 3, T1, T2, T3
PS55U4045
PS55U4055
PS55U4075
PS55U4110
PS55U4160 r,
L1, L2, L3, T1, T2, T3 r, r,
, , s s
⊕
200,
, , ⊕ 3 s s
400
L1, L2, L3, T1, T2, T3 r,
L1, L2, L3, T1, T2, T3 r, s
, , s
, , ⊕ 3
L1, L2, L3, T1, T2, T3 s
⊕
200,
200,
200,
3
3 s s
400
400
400
L1, L2, L3, , ⊕ 1, ⊕ 3, T1, T2, T3
PS55U4185 r, s
2
00, s
400
L1, L2, L3, , ⊕ 1, ⊕ 3, T1, T2, T3
PS55U4220 r, s
200, s
400
L1, L2, L3, , ⊕ 1, ⊕ 3, T1, T2, T3
PS55U4300 r, s
200, s
400
Common to all models
1-33
G
VS-616PS5 Installation & Quick Start Manual
M4
M4
M4
M4
M4
M4
M4
M8
M4
M8
M8
M4
M12
M8
M4
M16
M8
M4
M4
M10
M8
M4
M10
M8
M4
M10
M16
M8
M4
M16
M8
M4
M5
M6
M8
M4
M6
M5
M6
M5
M6
M8
M4
M8
Terminal
Screw
M4
M3.5
M3.5
Wire Size *
AWG mm
2
14 - 10
14 - 10
12 - 10
14 - 10
12 - 10
14 - 10
12 - 10
14 - 10
12 - 10
12 - 10
2 - 5.5
2 - 5.5
3.5 - 5.5
2 - 5.5
3.5 - 5.5
2 - 5.5
3.5 - 5.5
2 - 5.5
3.5 - 5.5
3.5 - 5.5
Max. Torque lb-in (N·m)
12.4 (1.4)
12.4 (1.4)
12.4 (1.4)
12.4 (1.4)
12.4 (1.4)
12 - 10 3.5 - 5.5
12.4 (1.4)
12.4 (1.4)
8 - 6 8 - 14 22.1 (2.5)
8
20 - 10
4
8
20 - 10
3
6
20 - 10
8 - 6
8
8 - 6
8
6
8
20 - 10
4
1
6
20 - 10
4/0
4
20 - 10
1/0 x 2P
4
20 - 10
1/0 x 2P
3
20 - 10
4/0 x 2P
1
20 - 10
8
0.5 - 5
22
8
0.5 - 5
30
14
0.5 - 5
8 - 14
8
8 - 14
8
14
8
0.5 - 5
22
50
14
0.5 - 5
100
22
0.5 - 5
60 x 2P
22
0.5 - 5
60 x 2P
30
0.5 - 5
100 x 2P 349.6 (39.5)
50
0.5 - 5
22.1 (2.5)
45.1 (5.1)
22.1 (2.5)
45.1 (5.1)
45.1 (5.1)
90.3 (10.2)
12.4 (1.4)
45.1 (5.1)
90.3 (10.2)
12.4 (1.4)
90.3 (10.2)
12.4 (1.4)
90.3 (10.2)
12.4 (1.4)
90.3 (10.2)
12.4 (1.4)
203.6 (23.0)
90.3 (10.2)
12.4 (1.4)
203.6 (23.0)
90.3 (10.2)
12.4 (1.4)
203.6 (23.0)
90.3 (10.2)
12.4 (1.4)
90.3 (10.2)
12.4 (1.4)
650MCM x 2P 325 x 2P 867.4 (98.0)
1
20 - 10
1/0
50
0.5 - 5.5
90.3 (10.2)
12.4 (1.4)
650MCM x 2P 325 x 2P 867.4 (98.0)
90.3 (10.2)
12.4 (1.4) 20 - 10
60
0.5 - 5.5
650MCM x 2P 325 x 2P 867.4 (98.0)
1/0
20 - 10
60
0.5 - 5.5
Stranded
0.5 - 1.25
90.3 (10.2)
12.4 (1.4)
20 - 16 -
20 - 14
Solid
0.5 - 1.25
0.5 - 2 8.9 (1.0)
Wire Type
Power cable:
600V vinyl sheathed wire or equivalent
Twisted shielded wire with
Class 1 wiring
Page A-3
A.3
JST Closed Loop Connectors
JST Closed Loop Connectors
Wire Size *
AWG mm
2
20
18
16
14
12 - 10
8
6
4
3 - 2
1 - 1/0
3/0
4/0
4/0
300MCM
400MCM
650MCM
0.5
0.75
1.25
2
3.5 - 5.5
8
14
22
30 - 38
50 - 60
80
100
100
150
200
325
Terminal
Screw
M5
M6
M8
M5
M5
M6
M8
M4
M3.5
M4
M3.5
M4
M3.5
M4
M3.5
M4
M6
M8
M8
M8
M10
M6
M8
M6
M8
M10
M12
M12 x 2
M16
JST Closed-Loop Connectors (Lugs)
60 - 10
80 - 10
100 - 10
100 - 12
150 - 12
200 - 12
325 - 12
325 - 16
8 - 6
8 - 8
14 - 6
14 - 8
22 - 6
22 - 8
38 - 8
60 - 8
2 - 5
2 - 6
2 - 8
5.5 - 4
5.5 - 5
5.5 - 6
5.5 - 8
8 - 5
1.25 - 3.5
1.25 - 4
1.25 - 3.5
1.25 - 4
1.25 - 3.5
1.25 - 4
2 - 3.5
2 - 4
Max. Torque lb-in (N·m)
45.1 (5.1)
90.3 (10.2)
45.1 (5.1)
90.3 (10.2)
45.1 (5.1)
90.3 (10.2)
90.3 (10.2)
90.3 (10.2)
203.6 (23.0)
203.6 (23.0)
203.6 (23.0)
349.6 (39.5)
349.6 (39.5)
349.6 (39.5)
349.6 (39.5)
867.4 (98.0)
8.9 (1.0)
12.4 (1.4)
8.9 (1.0)
12.4 (1.4)
8.9 (1.0)
12.4 (1.4)
8.9 (1.0)
12.4 (1.4)
22.1 (2.5)
45.1 (5.1)
90.3 (10.2)
12.4 (1.4)
22.1 (2.5)
45.1 (5.1)
90.3 (10.2)
22.1 (2.5)
Note 1:
The use of a JST closed-loop connector (lug) is recommended to maintain proper clearances. Please contact your
Yaskawa representative for more information.
Note 2:
Voltage drop should be considered when determining wire size. Voltage drop can be calculated using the following equation:
Phase-to phase voltage drop (V)
=
3 wire resistance ( Ω /km) x wiring distance (m) x current (A) x 10
-3
Select a wire size so that voltage drop will be less than 2% of the normal rated voltage.
Page A-4 VS-616PS5 Installation & Quick Start Manual
B.1
B.2
B.3
POWERTEC Motors Winding Determination ............................................................................B-1
E and F Series Motors...............................................................................................................B-1
A, B, C, D, and L Series Motors ................................................................................................B-2
Primary feedback Device...........................................................................................................B-2
Secondary Feedback Device.....................................................................................................B-2
POWERTEC Motors Frame Size and Winding Code Table......................................................B-3
POWERTEC Windings Data .....................................................................................................B-4
POWERTEC Motors Resolver Information .............................................................................B-13
POWERTEC Industrial Motors of Rock Hill, South Carolina manufactures Brushless DC motors from fractional to 300 HP. These motors are the motors for which the PS5 was originally designed. For information on the Brushless DC motors, call POWERTEC at 803-328-1888, or fax to 803-328-1870.
B.1
POWERTEC Motors Winding Determination
E and F Series Motors
POWERTEC motor model numbers beginning with “E” or “F” give the motor frame size in the second and third positions. The stack length is given in the fourth position. Refer to the attached charts of Ferrite motors and PAC-
TORQ (rare earth) motors.
Once the frame size has been determined, the letter in the fifth position of the model number gives the winding letter. Using the frame size and the winding letter, you can obtain the motor winding data to be entered into the “E” parameters with the “POWERTEC Frame Size and Winding Code Table”. This will give you the four-digit code designating the winding data.
Enter the four digit number in the E1-02 parameter. If the number is rejected (indicating the number is not in the drive database), Enter “1000” (CUSTOM) into the E1-02 parameter, and enter the table data into the “E” parameters as shown in the POWERTEC Winding Data Tables.
VS-616PS5 Installation & Quick Start Manual Page B- 1
A, B, C, D, and L Series Motors
POWERTEC motor model numbers beginning with “A”, “B”, “C”, “D”, or “L” give the motor frame size in the second and third positions. The stack length is given in the fifth position. The following table, with reference to the number in the second and third positions, finds the stack length:
S (small) M (medium) L (large) X (extra large) Y (really large)
143
182
213
254
287
145
184
215
256
288
L145
1810
219
259
2810
328
2512
2812
3211 3213
Once the frame size has been determined, the letter in the fourth position of the model number gives the winding letter. Using the frame size and the winding letter, you can obtain the motor winding data to be entered into the “E” parameters with the “POWERTEC Frame Size and Winding Code Table”. This will give you the four-digit code designating the winding data.
Enter the four digit number in the E1-02 parameter. If the number is rejected (indicating the number is not in the drive database), Enter “1000” (CUSTOM) into the E1-02 parameter, and enter the table data into the “E” parameters as shown in the POWERTEC Winding Data Tables.
Page B-2 VS-616PS5 Installation & Quick Start Manual
Primary Feedback Device
The primary feedback PPR is given on the nameplate on “E” and “F” series motors.
The primary feedback device is designated in the 11 th
position of the model number on “E” and “F” series motors.
Refer to the charts attached.
The primary feedback device is designated in the 10 th
position of the earlier series motors. A “0” indicates that the primary feedback is the hall effect switches. Other designations may require a consultation with POWERTEC.
Standard POWERTEC Ferrite motors have a Hall effect sensor installed with three feedback channels for commutation (HS1, HS2, and HS3), and two channels for Speed and Direction (HS4 and HS5). The Hall sensor PPR is given in the attached POWERTEC Winding Data tables as “PG Constant”.
Secondary Feedback Device
The commutation encoder PPR is given in the 13 th
position of the model number of “E” series and “F” series motors. The PPR is given on the nameplate. Otherwise, refer to the following table for the PPR:
D
E
F
0
A
B
C
LTR PPR
NONE
100
120
200
250
256
300
L
M
N
J
K
G
H
LTR PPR
360
400
500
600
1000
1024
1200
T
X
P
Q
R
S
LTR PPR
1500
2000
2048
2500
5000
Special
VS-616PS5 Installation & Quick Start Manual Page B- 3
B.2
POWERTEC Motors Frame Size and Winding Code Table
POWERTEC Motors Frame Size and Winding Code Table
FRAME
CUSTOM
213
213
213
213
213
213
184
184
184
184
184
184
184
213
L145
L145
182
182
182
182
182
182
B42
B42
C42
C42
143
143
145
145
LTR CODE FRAME LTR CODE FRAME LTR CODE FRAME LTR CODE
1000
1017
1018
1019
1020
1132
1242
1189
1047
1047
1048
1048
1049
1050
1193
1108
1109
1013
1014
1015
1016
1244
1185
1140
1141
1142
1143
1104
1105
1106
1107
259
259
259
259
259
259
256
256
256
256
256
256
256
259
219
254
254
254
254
254
254
256
215
215
215
215
215
215
215
215
A
B
B
C
D
H
E
H
Y
A
A
B
C
D
C
D
V
Y
A
B
A
B
A b
A
B
A
B
A
B
A
B
C
D
H k
M
V
E
A
B
C
D
V
Y
A
B
C
D
H
V
Y
Z
A
B
C
D
F
Y
Z
1051
1052
1053
1054
1198
1029
1027
1250
1176
1001
1002
1003
1004
1248
1201
1063
1006
1064
1008
1203
1239
1205
1206
1065
1010
1066
1012
1133
1209
1210
287
287
287
287
287
287
287
288
288
288
288
288
288
288
328
328
328
328
504
508
2512
2810
2810
2810
2810
2810
2812
2812
2812
2812
2812
2812
A
B
C
D
W
Y
Z
A
B
C
D
V
Y
Z
C
D
Y
Z
F
F
F
B
C
D
Y
Z
C
D
F
V
Y
Z
1094
1074
1055
1056
1211
1213
1214
1115
1078
1057
1058
1237
1217
1218
1097
1098
1223
1224
1165
1154
1161
1075
1059
1060
1219
1220
1067
1068
1136
1251
1221
1222
3211
3211
3211
3211
3213
3213
3213
E182
E184
E184
E184
E213
E213
E215
E218
E218
E254
E256
E2810
E2810
E2812
E2812
E3211
E3213
E3213
E328
EL259
ES184
ES259
ES259
M
E
E
E
E
E
E
Z
E
E
E
E
E
H
F
E
E
F
E
F
Z
E
G
Y
Y
E
C
D
Y
Z
1268
1259
1262
1272
1263
1273
1265
1241
1292
1264
1281
1254
1260
1261
1240
1277
1271
1255
1285
1256
1257
1279
1099
1100
1225
1226
1162
1227
1228
1253
Page B-4 VS-616PS5 Installation & Quick Start Manual
POWERTEC Windings Data
In order to use the following winding data tables, first set E1-17 to the appropriate winding connection configuration. Then set E1-02 to the desired winding type. Performing this sequence automatically loads parameters, E1-03 thru E1-13 along with F1-01 to the values specified in the following tables. One must manually program E1-06 and E1-07 to the maximum and base speed, respectively before operation is allowed.
Frame
254
254
254
254
256
256
259
259
182
182
182
182
184
184
184
184
Letter
A
B
C
D
B
D
B
D
A
B
C
D
A
B
C
D
Type
E1-02
1001
1002
1003
1004
1006
1008
1010
1012
1013
1014
1015
1016
1017
1018
1019
1020
230.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
230.0
230.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
460.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
Voltage Rated AMP
E1-03 E1-04
230.0
230.0
0
0
230.0
230.0
230.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Poles
E1-05
4
4
4
4
4
4
4
4
4
4
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08 E1-09 E1-10,11 E1-13 E-17
1
1
30
30
0.115
0.029
3.40
0.85
77.0
38.5
0
1
1
1
1
30
30
30
0.345
0.086
0.260
10.20
2.55
7.67
133.4
66.7
57.7
2
3
0
30
30
30
30
30
30
30
0.065
0.780
0.195
0.460
0.115
1.380
0.345
1.92
23.01
5.75
13.60
3.40
40.80
10.20
28.9
99.9
50.0
154.6
77.3
267.8
133.9
1
2
3
0
1
2
3
30
30
30
30
30
30
30
30
30
1.033
0.258
3.099
0.775
0.145
0.036
0.435
0.109
0.580
30.67
7.67
92.01
23.00
5.00
1.25
15.00
3.75
20.10
230.9
115.5
399.9
200.0
118.0
59.0
204.4
102.2
236.0
2
3
0
0
1
0
1
2
3
0.145
1.740
0.435
0.100
0.025
0.300
0.075
0.400
0.100
1.200
0.300
1.210
0.303
3.630
0.908
3.370
0.843
10.110
2.528
4.850
1.213
14.550
3.638
14.200
3.550
42.600
10.650
0.410
0.103
1.230
5.03
60.30
15.08
3.75
0.94
11.25
2.81
15.00
3.75
45.00
11.25
13.30
3.33
39.90
9.98
36.50
9.13
109.50
27.38
53.30
13.33
159.90
39.98
145.90
36.48
437.70
109.43
6.00
1.50
18.00
252.9
126.4
241.0
120.5
417.4
208.7
75.0
37.5
129.9
126.8
63.4
120.0
60.0
207.8
103.9
146.0
73.0
118.0
408.8
204.4
120.0
60.0
207.8
73.2
36.6
126.8
63.4
120.0
73.2
36.6
0
1
2
2
3
3
0
1
2
2
3
0
1
2
3
0
1
1
2
3
0
1
2
3
0
3
0
1
1
2
30
30
30
30
30
30
30
30
30
30
30
30
30
0.308
1.000
0.250
3.000
0.750
1.630
0.408
4.890
1.223
4.013
1.003
12.039
3.010
4.50
14.30
3.58
42.90
10.73
24.00
6.00
72.00
18.00
57.07
14.27
171.21
42.80
65.0
115.5
57.8
200.1
100.0
150.0
75.0
259.8
129.9
254.0
127.0
439.9
220.0
3
1
2
3
1
2
3
0
2
3
0
0
1
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=1D
=2D
=1Y
=2Y
=1D
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y 30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
PG Const.
F1-01
30
30
30
30
30
30
30
30
30
30
30
30
30
30
VS-616PS5 Installation & Quick Start Manual Page B- 5
POWERTEC Windings Data (continued)
Frame
215
215
213
213
213
213
215
215
215
215
287
287
288
288
2810
2810
Letter
M
K
A
B
C
D
A
B
C
D
C
D
C
D
C
D
Type
E1-02
1027
1029
1047
1048
1049
1050
1051
1052
1053
1054
1055
1056
1057
1058
1059
1060
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
8
8
8
8
8
8
8
8
8
8
8
8
8
4
8
4
4
Poles
E1-05
4
4
4
4
4
8
8
8
8
8
8
8
8
8
8
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
Voltage Rated AMP
E1-03 E1-04
230.0
230.0
0
0
230.0
230.0
230.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
0.108
1.290
0.323
0.973
0.243
2.919
0.730
1.736
0.680
8.160
2.040
0.243
0.061
0.729
0.182
0.430
0.170
2.040
0.510
1.372
0.343
4.116
1.029
2.720
0.033
0.400
0.100
0.343
0.086
1.029
0.257
0.680
0.070
0.840
0.210
0.089
0.022
0.267
0.067
0.201
0.050
0.434
5.208
1.302
0.145
0.036
0.435
0.109
0.280
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08 E1-09 E1-10,11 E1-13 E-17
1
1
30
30
0.770
0.192
18.40
4.60
134.4
67.2
0
1
1
1
1
30
30
30
2.310
0.577
0.133
55.20
13.80
3.37
232.7
116.4
69.3
2
3
0
30
30
30
30
30
30
30
30
30
30
0.603
0.151
0.048
0.012
0.144
0.036
0.109
0.027
0.327
0.082
14.58
3.65
1.27
0.32
3.81
0.95
2.85
0.71
8.55
2.14
469.7
234.9
161.7
80.9
280.1
140.0
243.0
121.5
420.9
210.4
2.50
30.00
7.50
22.50
5.63
67.50
16.88
40.00
13.50
162.00
40.50
5.63
1.41
16.89
4.22
10.00
3.38
40.50
10.13
26.80
6.70
80.40
20.10
54.00
0.84
10.11
2.53
6.70
1.68
20.10
5.30
13.50
1.47
17.58
4.40
2.16
0.54
6.48
1.62
4.86
1.22
10.00
120.00
30.00
2.94
0.74
8.82
2.21
5.86
59.5
206.1
103.1
178.2
89.1
308.7
154.3
237.8
114.3
395.9
198.0
89.1
44.6
154.3
77.2
119.0
57.2
198.0
99.0
161.3
80.7
279.4
139.7
228.6
34.7
120.0
60.0
80.7
40.3
139.7
69.9
114.3
118.0
408.8
204.4
180.8
90.4
313.2
156.6
271.2
135.6
118.9
411.9
205.9
167.0
83.5
289.3
144.6
236.0
0
1
2
3
2
3
0
1
2
3
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
1
2
3
0
1
2
3
0
1
3
0
1
2
3
0
1
2
3
0
1
2
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
60
60
60
60
60
60
60
60
60
60
60
60
60
30
30
30
60
PG Const.
F1-01
30
30
30
30
30
60
60
60
60
60
60
60
60
60
60
Page B-6 VS-616PS5 Installation & Quick Start Manual
POWERTEC Windings Data (continued)
Frame
256
256
259
259
2812
2812
287
2810
288
287
328
328
3211
3211
143
143
Letter
A
C
A
C
C
D
B
B
B
A
C
D
C
D
A
B
Type
E1-02
1063
1064
1065
1066
1067
1068
1074
1075
1078
1094
1097
1098
1099
1100
1104
1105
Voltage Rated AMP
E1-03 E1-04
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
230.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
230.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Poles
E1-05
4
4
4
4
4
4
4
4
8
8
8
4
4
4
4
4
4
4
4
8
8
8
8
8
8
8
4
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4
4
4
4
4
4
4
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08 E1-09 E1-10,11 E1-13 E-17
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
0.043
0.011
0.129
0.032
0.173
0.043
0.519
0.130
0.071
0.018
0.213
0.053
0.284
0.071
0.852
0.213
0.044
0.011
0.132
0.033
0.091
0.023
0.273
0.068
0.070
0.007
0.087
0.022
0.050
0.013
0.150
0.038
5.020
0.010
0.120
0.030
0.076
0.019
0.228
0.057
0.029
1.255
15.060
3.765
10.000
2.500
30.000
7.500
0.013
0.150
0.038
0.037
0.009
0.111
0.028
0.040
0.018
0.210
0.053
0.270
0.068
0.810
0.203
0.050
1.67
0.42
5.01
1.25
6.67
1.67
20.01
5.00
2.38
0.60
7.14
1.79
9.52
2.38
28.56
7.14
1.20
0.30
3.60
0.90
2.45
0.61
7.35
1.84
1.46
0.20
2.43
0.61
1.44
0.36
4.32
1.08
40.40
0.27
3.24
0.81
2.05
0.51
6.15
1.54
0.81
10.10
121.20
30.30
80.80
20.20
242.40
60.60
0.30
3.63
0.91
0.74
0.19
2.22
0.56
1.08
0.37
4.38
1.10
0.71
0.18
2.13
0.53
1.21
79.7
39.9
138.0
69.0
159.4
79.7
276.1
138.0
80.8
40.4
139.9
70.0
161.8
80.9
280.2
140.1
178.0
89.0
308.3
154.2
254.0
127.0
439.9
220.0
118.0
93.7
324.4
162.2
250.0
125.0
433.0
216.5
86.3
92.2
319.4
159.7
253.0
126.5
438.2
219.1
187.3
43.2
149.5
74.7
122.0
61.0
211.3
105.7
67.6
234.0
117.0
83.7
41.9
145.0
72.5
184.4
59.0
204.4
102.2
121.2
60.6
209.9
105.0
135.1
2
3
0
1
2
3
0
1
0
1
2
2
3
0
1
2
3
0
1
2
3
0
3
0
1
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
1
2
3
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
PG Const.
F1-01
30
30
30
30
30
30
30
30
60
60
60
30
30
30
30
30
30
30
30
60
60
60
60
60
60
60
60
60
30
60
60
60
60
60
60
60
60
60
60
60
60
30
30
30
30
30
30
30
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
VS-616PS5 Installation & Quick Start Manual Page B- 7
POWERTEC Windings Data (continued)
Frame
145
145
L145
L145
288
184
259
2812
B42
B42
C42
C42
508
2512
3213
504
Letter
A
B
A
B
A
E
F
F
A
B
A
B
F
F
G
F
Type
E1-02
1106
1107
1108
1109
1115
1132
1133
1136
1140
1141
1142
1143
1154
1161
1162
1165
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
460.0
460.0
460.0
460.0
460.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
Voltage Rated AMP
E1-03 E1-04
230.0
230.0
0
0
230.0
230.0
230.0
230.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
8
8
8
4
8
4
4
8
8
8
8
4
8
8
4
8
4
4
4
4
4
4
4
4
4
4
4
4
4
4
8
4
8
8
4
4
8
4
4
4
4
4
4
8
8
8
8
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Poles
E1-05
4
4
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08 E1-09 E1-10,11 E1-13 E-17
1
1
30
30
1.940
0.485
20.30
5.08
86.6
43.3
0
1
1
1
1
1
30
30
30
30
5.820
1.455
3.860
0.965
60.90
15.23
40.70
10.18
150.0
75.0
123.3
61.7
2
3
0
1
30
30
30
30
30
30
30
30
11.580
2.895
0.840
0.210
2.520
0.630
1.940
0.485
122.10
30.53
11.55
2.89
34.65
8.66
24.40
6.10
213.6
106.8
88.1
44.1
152.6
76.3
128.0
64.0
0
1
2
3
0
1
2
3
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
5.820
1.455
0.023
0.006
0.069
0.017
0.227
0.057
0.682
0.170
0.050
0.012
0.149
0.037
0.069
73.20
18.30
0.54
0.14
1.62
0.41
4.00
1.00
12.00
3.00
1.86
0.46
5.57
1.39
1.96
221.7
110.9
90.1
45.1
156.1
78.0
67.2
33.6
116.4
58.2
90.1
45.1
156.1
78.0
228.7
2
3
0
0
1
2
3
0
1
2
3
0
1
2
3
0.017
0.206
0.052
14.400
3.600
43.200
10.800
25.800
6.450
77.400
19.350
7.180
1.795
21.540
5.385
12.900
3.225
38.700
9.675
0.045
0.011
0.135
0.034
0.049
0.012
0.147
0.037
0.041
0.010
0.123
0.031
0.058
0.014
0.173
0.043
0.49
5.88
1.47
75.30
18.83
225.90
56.48
150.00
37.50
450.00
112.50
45.70
11.43
137.10
34.28
92.30
23.08
276.90
69.23
2.36
0.59
7.08
1.77
1.99
0.50
5.96
1.49
1.41
0.35
4.23
1.06
2.60
0.65
7.80
1.95
48.5
168.0
84.0
259.9
130.0
450.1
225.0
424.1
61.0
211.3
105.7
537.1
268.6
930.3
465.0
97.0
212.0
734.5
367.2
61.0
211.3
105.7
86.0
43.0
149.0
74.5
122.0
114.3
396.1
198.0
86.0
43.0
149.0
74.5
122.0
3
0
1
2
3
0
1
2
1
2
3
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
60
60
60
60
30
30
30
60
60
60
60
30
30
30
30
60
60
60
60
30
30
30
30
30
30
30
30
30
30
30
30
60
60
60
30
30
30
30
30
30
30
60
60
60
30
30
30
30
60
60
30
30
30
30
30
30
30
30
PG Const.
F1-01
30
30
30
30
30
30
Page B-8 VS-616PS5 Installation & Quick Start Manual
POWERTEC Windings Data (continued)
Frame
219
182
184
213
215
254
256
256
256
259
259
287
287
287
288
288
Letter
E
Y
Y
H
H
Y
H
Y
Z
Y
Z
W
Y
Z
Y
Z
Type
E1-02
1176
1185
1189
1193
1198
1201
1203
1205
1206
1209
1210
1211
1213
1214
1217
1218
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
Voltage Rated AMP
E1-03 E1-04
460.0
0
460.0
0
460.0
460.0
460.0
0
0
0
460.0
460.0
460.0
460.0
460.0
460.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
460.0
460.0
460.0
460.0
460.0
0
0
0
0
0
8
8
8
8
8
8
8
8
8
8
8
8
4
4
8
4
4
4
4
4
4
4
4
4
8
8
8
8
8
8
8
8
8
8
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Poles
E1-05
4
4
4
4
4
8
8
8
8
8
1
1
1
1
1
1
1
1
1
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08 E1-09 E1-10,11 E1-13 E-17
1 30 0.058
1.47
57.3
0
1 30 0.015
0.37
28.6
1
1
1
1
30
30
30
0.173
0.043
9.314
4.41
1.10
98.73
99.2
49.6
231.5
2
3
0
1
1
1
1
1
1
30
30
30
30
30
30
2.328
27.943
6.986
2.695
0.674
8.085
24.68
296.20
74.05
47.43
11.86
142.29
115.8
401.0
200.4
231.5
115.8
401.0
1
2
3
0
1
2
30
30
30
30
30
30
30
30
30
30
30
30
30
30
2.021
3.153
0.789
9.460
2.365
3.556
0.889
10.669
2.667
1.199
0.300
3.597
0.899
0.162
35.57
63.70
15.93
191.10
47.78
85.00
21.25
255.00
63.75
35.97
8.99
107.90
26.98
5.69
200.4
248.7
124.3
430.7
215.4
346.4
173.2
600.0
300.0
250.6
125.3
434.0
217.0
125.7
2
3
0
1
0
1
2
3
2
3
0
3
0
1
30
30
30
30
30
30
30
30
30
30
0.040
0.486
0.122
0.649
0.162
1.946
0.487
1.403
0.351
4.208
1.052
0.402
0.100
1.205
0.301
0.904
0.226
2.712
0.678
0.077
0.019
0.231
0.058
0.286
0.071
0.857
0.214
0.497
0.124
1.492
0.373
0.165
0.041
0.496
1.42
17.07
4.27
22.77
5.69
68.32
17.08
49.23
12.31
147.70
36.93
15.00
3.75
45.00
11.25
33.75
8.44
101.25
25.31
1.72
0.43
5.16
1.29
6.37
1.59
19.10
4.78
11.09
2.77
33.27
8.32
4.33
1.08
13.00
62.8
217.7
108.9
250.6
125.3
434.0
217.0
369.7
184.9
640.4
320.2
239.6
119.8
415.0
207.5
359.1
179.6
622.0
311.0
127.6
63.8
221.0
110.5
245.4
122.7
425.0
212.5
323.0
161.5
559.4
279.7
255.2
127.6
442.0
0
1
2
1
2
3
1
2
3
0
2
3
0
3
0
1
0
1
2
1
2
3
2
3
0
3
0
1
0
1
2
1
2
3
1
1
1
1
1
30
30
30
30
30
0.124
0.277
0.069
0.831
0.208
3.25
7.26
1.82
21.78
5.45
221.0
331.4
165.7
574.0
287.0
3
0
1
2
3
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
60
60
60
60
60
60
60
60
60
60
60
60
30
30
30
30
30
60
30
30
30
30
30
30
60
60
60
60
60
60
60
60
60
60
30
30
30
30
30
30
30
30
30
30
30
30
30
30
PG Const.
F1-01
30
30
30
30
30
30
30
30
30
30
30
60
60
60
60
60
VS-616PS5 Installation & Quick Start Manual Page B- 9
POWERTEC Windings Data (continued)
Frame
Frame
2810
254
2810
215
2812
2812
2812
E182
328
ES184
328
E213
3211
E215
3211
E218
3213
E256
3213
ES259
288
ES259
256
E2810
E184
E2812
E3213
E328
184
E3211
182
E254
Letter
Letter
Y
V
Z
V
Z
E
Y
E
Z
E
Y
V
Y
E
Z
E
Y
E
Y
E
V
E
V
E
E
E
E
E
H
E
V
E
Type
E1-02
1248
1220
1250
1221
1251
1222
1253
1223
1254
1224
1255
1225
1256
1226
1257
1227
1259
1228
1260
1237
1261
1239
1262
1240
1263
1241
1264
1242
1265
1244
1268
Poles
E1-05
8 8
8 8
8 8
4 8
4 8
4 8
4 8
4 8
8
8
8
8
8
8
8
8
4
8
4
8
4
8
4
8
4
8
4
8
4
8
4
8
4 8
4
8
4 8
8 4
8 4
8
4
8
4
8
4
8
4
8
4
8
4
8
4
8
6
8
6
8
6
8
4
8
4
8
8
8
8
8
8
8
8
8
8
4
8
4
8
4
8
4
8
6
8
6
8
6
8
6
8
6
8
4
8
6
8
6
8 6
8 6
8 8
8 8
8 8
8 8
8 8
8 8
8 8
8
8
460.0
460.0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 0
0
0
0 0
Voltage Rated AMP
E1-03
Rated AMP
0
0 0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
0 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
0
1 1
1 1
1 1
1 1
1 1
1 1
1
1
1 1
1 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08
30
E1-09
0.118
E1-10,11
3.34
E1-13
263.2
E-17
0
1 1 1 0
1 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
30
30
30
30
30
30
30
0.680
0.223
0.170
2.669
0.078
0.086
0.233
19.24
5.32
4.81
63.80
2.21
2.45
6.63
626.0
86.6
313.0
300.0
241.3
254.0
417.9
3
0
1
2
3
0
0
1
2
3
0
1
1
2
3
0
0
1
2
3
3
0
2
3
1
1
2
2
0
3
0
1
2
1
3
0
1
2
3
2
0
1
2
3
0
3
1
2
3
0
1
2
3
2
0
1
2
3
0
1
2
1 3 1 1
1 1
1 1
2
3
0
1
1 1
1 1
1 1
1 1
1 1
0
1
3
0
2
2
3
0
1
2
1 1
1 1
1
2
3
0
30
30
1.062
0.266
23.26
5.82
601.5
300.8
3
0
1
2
1 3
2
3
0
1
0
1
2
2
3
0
3
0
1
2
1
2
0
1
3
0
1
1
3
2
3
2
0
1
2
3
2
0
3
1
3
0
2
3
=2D
=2Y
=2D
=1Y
=2D
=2Y
=1Y
=1Y
=2Y
=1Y
=1Y
=2Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=1Y
=2Y
PG Const.
F1-01
60 60
60 60
60 60
30 60
30 60
30 60
30 60
30 60
30
60
30 60
30 60
60
60
60
60
60
60
60
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
60 30
60 30
60
30
60
30
60
60
30
30
60
30
60
60
30
60
60
60
60
60
60
60
60
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60
30
60 30
60 30
60 60
60 60
60 60
60 60
60 60
60 60
60 60
60
60
Page B-10 VS-616PS5 Installation & Quick Start Manual
POWERTEC Windings Data (continued)
Frame Letter
E184
E2810
E2812
E184
E218
EL259
E213
E3213
Z
H
Z
F
F
E
F
M
Type
E1-02
1271
1272
1273
1277
1279
1281
1285
1292
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
460.0
Voltage
E1-03
460.0
460.0
460.0
460.0
460.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Rated AMP
E1-04
0
0
0
0
0
8
8
8
8
6
6
6
6
6
6
8
8
8
8
6
6
6
8
8
6
6
6
8
8
8
8
8
Poles
E1-05
6
6
8
6
6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Base Speed Min Speed Stator Res Stator Ind KV VAC/rpm Connection
E1-06,07 E1-08 E1-09 E1-10,11 E1-13 E-17
1 30 0.391
6.10
167.4
0
1
1
1
1
30
30
30
30
0.098
1.173
0.294
0.066
1.53
18.30
4.58
1.68
83.7
290.0
145.0
254.0
1
2
3
0
30
30
30
30
30
30
30
30
30
30
0.017
0.198
0.050
0.082
0.021
0.246
0.061
0.192
0.048
0.575
0.42
5.04
1.26
2.23
0.56
6.68
1.67
2.99
0.75
8.97
127.0
440.0
220.0
337.2
168.6
584.0
292.0
117.5
58.7
203.5
2
3
0
1
2
1
2
3
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
0.144
0.133
0.033
0.399
0.100
0.161
0.040
0.482
0.120
0.901
0.225
2.703
0.676
0.057
0.014
0.170
0.043
2.24
3.05
0.76
9.14
2.29
4.27
1.07
12.81
3.20
17.84
4.46
53.52
13.38
2.12
0.53
6.35
1.59
101.8
178.2
89.1
308.6
154.3
358.0
179.0
620.0
310.0
330.0
165.0
571.6
285.8
444.6
222.3
770.0
385.0
0
1
2
3
0
3
0
1
2
3
2
3
0
1
1
2
3
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
=2D
=1Y
=2Y
60
60
60
60
30
30
30
30
30
30
30
30
30
60
60
60
60
60
60
30
30
30
60
60
60
60
60
PG Const.
F1-01
30
30
30
30
60
CUSTOM 1000 0.0
0.0
0.0
0.0
0
0
0
0
4
4
4
4
1
1
1
1
30
30
30
30
0.000
0.000
0.000
0.000
0.00
0.00
0.00
0.00
0.0
0.0
0.0
0.0
0
1
2
3
=2D
=1Y
=2Y
30
30
30
30
VS-616PS5 Installation & Quick Start Manual Page B- 11
B.3
POWERTEC Motors Resolver Information
RESOLVER MOTORS - CONNECTIONS AND TERMINAL MARKINGS
MOTOR / RESOLVER LEADS
Motors are shipped with nameplate connections (i.e., 1-Y, 1-D, 2Y, or 2-D)
Check Motor nameplate for correct connections.
See page 5 for standard connection diagrams.
Consult drive manual for motor/drive interconnections.
Check shipping documentation for special connections.
SPACE HEATERS
When supplied, will have leads tagged H1 and H2. Check nameplate for voltage and current ratings.
OTHER ACCESSORIES
Check motor nameplate and accessories nameplates for connections and ratings.
The Overtemperature threshold for totally enclosed motors is
145º C (104.2 Ohms). The threshold for drip proof and blower ventilated motors is 130ºC (150.5 ohms)
Since the potential exists for a thermistor to open up, Motor
Overtemperature Warnings should be set no higher than 80% of Fault Temperature on totally enclosed motors, and no higher than 80% for drip proof and blower ventilated motors.
Page B-12
CAUTION:
Connect cable shields to designated points only. DO NOT connect shields to ground.
THERMISTORS AND THERMAL SWITCHES
Motors with R3 Resolvers have two thermal switches connected in series embedded in the windings.
Motors equipped with R1 and R2 Resolvers have two
Negative Temperature Coefficient (NTC) thermister probes.
They are 10,000 ohms each @25ºC, connected in parallel to terminals 8 and 9 in the motor junction box. Thermistor leads are labeled P1 and P2. At room temperature (25º C) the resistance between P1 and P2 should be 5000 ohms.
NTS Thermistor Resistance Table
Nominal Resistance between P1 and P2 in ohms
Resistance tolerance is +1-5%
Winding
Temp.
20
30
40
50
60
70
80
ºC
-30
-20
-10
0
10
R
P1-P2 ohms
88500
48535
27665
16325
9950
6250
4028
2663
1801
1244
876
629
Winding
Temp.
ºC
90
100
110
120
130
140
150
160
170
180
190
200
R
P1-P2
VS-616PS5 Installation & Quick Start Manual ohms
459
340
255.5
194.5
150.5
117.5
92.5
74
59.5
48.5
39.7
32.8
RESOLVER EQUIPPED MOTORS
The resolver supplied with POWERTEC motors is a frameless, single speed, transmitter type, mounted on the back of the motor. The rotor element is mounted on the shaft.
See the table at the right for resolver specifications
Resolver Wiring Configuration
Positive resolver rotation is CW facing the resolver end of the motor
Phasing Voltage for 8 Pole Motor for clockwise rotation at drive end
V
T1-T2
V
T2-T3
V
T3-T4
1 Mechanical Revolution
Resolver Output
S1-S3
(SINE)
S2-S4
(COSINE)
Primary Feedback Devices - Technical Data
Frameless Resolvers typical output@25ºC
Parameter Units R1 R2 R3
Frame Size
Type
Primary
Speeds
Input Voltage
Frequency
Vms kHz
Input Current, max mA
Input Power, nom mW
Transformation
Ratio
Phase Shift
Impendances
ZRO
ZRS
ZSO
ZSS
Deg ohms ohms
37
Transmitte r
Rotor
1
8
6.5
68
404
0.5:1
-3
87+j82
82+j79
49 37
Transmitter Transmitter
Rotor
1
8
6.5
85
510
0.5:1
-5
84+j59
87+j82
Rotor
1
6
6
70
250
0.333:1
-5
82+j72
79+j70 ohms 298+j519 905+j1860 147+j247 ohms 278+j497 885+j850 139+j278
DC Resistances
Stator
Rotor
Null Voltage
Max Electrical
Error
Output Voltage
Weight ohms ohms mV minutes
Vms lb.
42
57
+45
20
4.0
1
195
62
+30
20
4.0
2.43
28
56
+60
20
2.0
1
NOTES:
R1 resolvers are used in standard motors except as follows:
R2 resolvers are used in all double shaft and TEFC 280 and
320 frames.
R3 resolvers are used with Control Techniques drives.
Data is for estimation purposes only. For certified data, consult the factory.
PHASING DIAGRAM OF MOTOR STATOR
Phase T1 (U)
VS-616PS5 Installation & Quick Start Manual
Phase T3 (W) Phase T2 (V)
Page B- 13
C.1
C.2
C.3
PG-H2 Connection Diagram for PS5 - POWERTEC motor /w aux. encoder ...............................................................................C-1
PG-P2 Rev C Connection Diagram for PS5 - POWERTEC motor basic .....................................................................................C-2
PG-P2 Rev C Connection Diagram for PS5 - POWERTEC motor /w aux. encoder ....................................................................C-2
PG-P2 Rev C Connection Diagram for PS5 - POWERTEC motor /w com encoder ....................................................................C-3
PG-P2 Rev C Connection Diagram for PS5 - POWERTEC motor and Digimax controller ..........................................................C-3
PG-P2 Rev C Connection Diagram for PS5 - POWERTEC motor /w aux. encoder and
Digimax controller........................................................................................................................................................................C-4
PG-P2 Rev C Connection Diagram for PS5 - POWERTEC motor w/ com encoder and
Digimax controller.........................................................................................................................................................................C-4
PG-P2 Rev D Connection Diagram for PS5 - POWERTEC motor basic .....................................................................................C-5
PG-P2 Rev D Connection Diagram for PS5 - POWERTEC motor /w aux. encoder ....................................................................C-5
PG-P2 Rev D Connection Diagram for PS5 - POWERTEC motor /w com encoder ...................................................................C-6
PG-P2 Rev D Connection Diagram for PS5 - POWERTEC motor and Digimax controller ..........................................................C-6
PG-P2 Rev D Connection Diagram for PS5 - POWERTEC motor /w aux. encoder and
Digimax controller........................................................................................................................................................................C-7
PG-P2 Rev D Connection Diagram for PS5 - POWERTEC motor w/ com encoder and
Digimax controller.........................................................................................................................................................................C-7
C.1
PG-H2 Connection Diagram
POWERTECH
MOTOR
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Hall-effect
Feedback Sensor
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
6
7
4
5
1
2
3
8
9
10
H2-12
H2-11
H2-10
H2-15
H2-13
H2-24
H2-14
Motor mounted
Encoder
V+
V-
Chnl A+
Chnl A -
Chnl B+
Chnl B -
Chnl C+
Chnl C-
Shield
H2-1
H2-2
H2-3
H2-4
H2-5
H2-6
H2-7
H2-8
NOTE: Wiring for HS4 and
HS5 is optional, not required
PS5
PG-H2
18
19
20
21
15
16
17
22
23
24
11
12
13
14
8
9
10
6
7
4
5
1
2
3
+12VDC PWR ouput
12VDC Common
ENC A+ input
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
Shield
+12VDC PWR output
HS1 input
HS2 input
HS3 input
HS4 input
HS5 input
Shield
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
Shield
12VDC Common
Terminal 12
NOTE:
Set Parameter F8 - 01= 0
PG-H2 Connection Diagram for PS5
POWERTEC motor/w aux. encoder
VS-616PS5 Installation & Quick Start Manual Page C-1
C.2 PG-P2 Rev C Connection Diagrams
POWERTECH
MOTOR
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Hall-effect
Feedback Sensor
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
6
7
8
9
10
3
4
5
1
2
P2-J2B-7
P2-J2B-6
P2-J2A-4
P2-J1-3
P2-J1-1
P2-J2A-5
P2-J1-2
5
6
3
4
1
2
PS5
PG-P2
REV C
J2A
Shield
Shield
NC
+12VDC PWR ouput
12VDC Common
ENC A+ input
3
4
5
1
2
6
7
J2B
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
HS1 input
HS2 input
7
8
9
10
11
12
4
5
6
1
2
3
J1
HS3 input
HS4 input
HS5 input
FREQ Output
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
12VDC Common
PG-P2 Rev C Connection Diagram for PS5
POWERTEC motor basic
Terminal 12
NOTE:
Set Parameter F8 - 01= 1
Page C-2
POWERTECH
MOTOR
Hall-effect
Feedback Sensor
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
7
8
5
6
9
10
1
2
3
4
P2-J2B-7
P2-J2B-6
P2-J2A-4
P2-J1-1
P2-J2A-5
Motor mounted
Encoder
V+
V-
Chnl A+
Chnl A -
Chnl B+
Chnl B -
Chnl C+
Chnl C-
Shield
P2-J2A-4
P2-J2A-5
P2-J2A-6
P2-J2B-1
P2-J2B-2
P2-J2B-3
P2-J2B-4
P2-J2B-5
PG-P2 Rev C Connection Diagram for PS5
POWERTEC motor/w aux. encoder
5
6
3
4
1
2
PS5
PG-P2
REV C
J2A
Shield
Shield
NC
+12VDC PWR ouput
12VDC Common
ENC A+ input
1
2
3
4
5
6
7
J2B
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
HS1 input
HS2 input
10
11
12
7
8
9
4
5
6
1
2
3
J1
HS3 input
HS4 input
HS5 input
FREQ Output
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
12VDC Common
Terminal 12
NOTE:
Set Parameter F8 - 01= 0
VS-616PS5 Installation & Quick Start Manual
C.2 PG-P2 Rev C Connection Diagrams
(continued)
MS Connector MS3102E20-29P
M
L
K
J
T
S
H
G
A
N
B
R
P
F
C
E
D
Suggested Mating
Connector
MS310GF-20-29S
COMMUTATION ENCODER
CONNECTOR PIN
R
S
T
N
P
L
M
J
K
G
H
E
F
A
B
C
D
ENCODER
Case Ground
N/C
S1
S2
S3
N/C
A
/A
B
/B
Z
/Z
/S1
/S2
/S3
Encoder V++
Encoder VDC COM
Pulse Train Output
Pulse Train Input
Pulse Train I/O Common
H
J
K
L
M
C
D
E
S
T
G
PG-P2 Rev C Connection Diagram for PS5
POWERTEC motor w/com encoder
4
5
6
1
2
3
PS5
PG-P2
REV C
J2A shield shield
NC
+12 VDC PWR output
12 VDC Common
ENC A + input
4
5
6
7
1
2
3
J2B
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
HS1 input
HS2 input
7
8
9
10
3
4
5
6
1
2
11
12
J1
HS3 input
HS4 input
HS5 input
FREQ Output
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
12VDC Common
NOTE:
Terminal 12
POWERTECH
MOTOR
Hall-effect
Feedback Sensor
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
5
6
7
8
1
2
3
4
9
10
P2-J2B-7
P2-J2B-6
P2-J2A-4
P2-J1-3
P2-J1-1
P2-J2A-5
P2-J1-2
PS5
1
2
3
4
5
6
PG-P2
REV C
J2A
Shield
Shield
NC
+12VDC PWR ouput
12VDC Common
ENC A+ input
5
6
7
1
2
3
4
J2B
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
HS1 input
HS2 input
4
5
6
7
1
2
3
10
11
12
8
9
J1
HS3 input
HS4 input
HS5 input
FREQ Output
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
12VDC Common
Digimax
Controller
TB 2
Tach -
Tach +
Com
11
12
4
TB1
Com
+24V
Com
Out
P2-J1-4
10
11
4
7
P2-J1-12
P2-J1-11
PG-P2 Rev C Connection Diagram for PS5
POWERTEC motor and Digimax controller
Terminal 12
NOTE:
Set Parameter F8 - 01= 1
Set Parameter B1 - 01= 6
VS-616PS5 Installation & Quick Start Manual Page C-3
C.2 PG-P2 Rev C Connection Diagrams
(continued)
POWERTECH
MOTOR
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Hall-effect
Feedback Sensor
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
4
5
6
7
1
2
3
8
9
10
P2-J2B-7
P2-J2B-6
P2-J2A-4
P2-J1-1
P2-J2A-5
Motor mounted
Encoder
V+
V-
Chnl A+
Chnl A -
Chnl B+
Chnl B -
Chnl C+
Chnl C-
Shield
P2-J2A-4
P2-J2A-5
P2-J2A-6
P2-J2B-1
P2-J2B-2
P2-J2B-3
P2-J2B-4
P2-J2B-5
Digimax
Controller
TB 2
Tach -
Tach +
Com
11
12
4
TB1
Com
+24V
Com
Out
P2-J1-4
10
11
4
7
P2-J1-12
P2-J1-11
PG-P2 Rev C Connection Diagram for PS5
POWERTEC motor/w aux. encoder and Digimax controller
PS5
4
5
6
1
2
3
PG-P2
REV C
J2A
Shield
Shield
NC
+12VDC PWR ouput
12VDC Common
ENC A+ input
4
5
6
7
1
2
3
J2B
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
HS1 input
HS2 input
9
10
7
8
11
12
3
4
5
6
1
2
J1
HS3 input
HS4 input
HS5 input
FREQ Output
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
FREQ Input
12VDC Common
Terminal 12
NOTE:
Set Parameter F8 - 01= 0
Set Parameter B1 - 01= 6
Page C-4
MS Connector MS3102E20-29P
M
L
K
J
T
S
H
G
A
N
B
R
P
F
C
E
D
Suggested Mating
Connector
MS310GF-20-29S
COMMUTATION ENCODER
CONNECTOR PIN ENCODER
M
N
P
R
H
J
K
L
S
T
D
E
F
G
A
B
C
Case Ground
N/C
S1
S2
S3
N/C
A
/Z
/S1
/S2
/S3
/A
B
/B
Z
Encoder V++
Encoder VDC COM
H
J
K
L
M
C
D
E
S
T
G
1
2
3
4
5
6
PS5
PG-P2
REV C
J2A shield shield
NC
+12 VDC PWR output
12 VDC Common
ENC A + input
5
6
7
1
2
3
4
J2B
ENC A - input
ENC B+ input
ENC B - input
ENC C+ input
ENC C - input
HS1 input
HS2 input
4
5
6
7
1
2
3
8
9
10
11
12
J1
HS3 input
HS4 input
HS5 input
FREQ Output
ENC A+ output
ENC A - ouput
ENC B + ouput
ENC B - output
ENC C + output
ENC C - output
FREQ Input
12VDC Common
Digimax
Controller
TB 2
Tach -
Tach +
Com
11
12
4
TB1
Com
+24V
Com
Out
P2-10
4
7
10
11
P2-24
P2- 9
Terminal 12
NOTE:
Set Parameter F8 - 01= 1 0
PG-P2 Rev C Connection Diagram for PS5
POWERTEC motor/w com encoder and Digimax controller
VS-616PS5 Installation & Quick Start Manual
C.3 PG-P2 Rev D Connection Diagrams
POWERTEC
MOTOR
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Hall-effect
Feedback Sensor
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
4
5
6
7
1
2
3
8
9
10
TB1-15
TB1-13
TB1- 5
TB1-20
TB1-17
TB1- 6
TB1-19
PS5
TB1
PG-P2
REV D
Shield
Shield
Shield
No Connection
+12/+5 VDC
Common
ENC A+ input
ENC A- input
ENC B+ input
ENC B- input
ENC C+ input
ENC C- input
HS1+ input
HS1 - input
HS2+ input
HS2 - input
HS3+ input
HS3 - input
HS4 input
HS5 input
FREQ Ref Output
Common
ENC A+ output
ENC A - output
ENC B+ output
ENC B - output
ENC C+ output
ENC C- output
FREQ Ref + Input
FREQ Ref - Input
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5 *
6
21
22
23
24
25
26
27
28
29
30
NOTE: Terminal description and jumper settings
Pin 5: For encoder supply voltage adjustment,
JP1 Installed=+5VDC, Removed=+12VDC
-------------------------------------------------------------------------------------
Turn off all switches SW1,2,3.
NOTE: All signal cables must be routed separately or with other circuits of
50VDC or less only
NOTE: All shielded cable must be minimum
18AWG /w overall shield
Terminal 12
NOTE:
Set Parameter F8 - 01= 1
PG-P2 Rev D Connection Diagram for PS5
POWERTEC motor basic
POWERTEC
MOTOR
Hall-effect
Feedback Sensor
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
5
6
7
8
1
2
3
4
9
10
TB1-15
TB1-13
TB1- 5
TB1-17
TB1- 6
Motor mounted
Encoder
V+
V-
Chnl A+
Chnl A -
Chnl B+
Chnl B -
Chnl C+
Chnl C-
Shield
TB1- 5
TB1- 6
TB1- 7
TB1- 8
TB1- 9
TB1- 10
TB1- 11
TB1- 12
NOTE : Terminal description and jumper settings
Pin 5: For encoder supply voltage adjustment,
JP1 Installed=+5VDC, Removed=+12VDC
-----------------------------------------------------------------
Turn off all switches SW1,2,3.
PS5
PG-P2
REV D
Shield
Shield
Shield
No Connection
+12/+5 VDC
Common
ENC A+ input
ENC A- input
ENC B+ input
ENC B- input
ENC C+ input
ENC C- input
HS1+ input
HS1 - input
HS2+ input
HS2 - input
HS3+ input
HS3 - input
HS4 input
HS5 input
FREQ Ref Output
Common
ENC A+ output
ENC A - output
ENC B+ output
ENC B - output
ENC C+ output
ENC C- output
FREQ Ref + Input
FREQ Ref - Input
TB1
10
11
12
13
6
7
8
9
14
15
16
17
18
19
20
21
1
2
3
4
5 *
22
23
24
25
26
27
28
29
30
Terminal 12
NOTE:
Set Parameter F8 - 01= 0
NOTE: All signal cables must be routed separately or with other circuits of
50VDC or less only
NOTE: All shielded cable must be minimum
18AWG /w overall shield
PG-P2 Rev D Connection Diagram for PS5
POWERTEC motor/w aux. encoder
VS-616PS5 Installation & Quick Start Manual Page C-5
C.3 PG-P2 Rev D Connection Diagrams
(continued)
MS Connector MS3102E20-29P
M
K
L
J
T
S
H
G
A
N
B
R
P
F
C
D
E
Suggested Mating
Connector
MS310GF-20-29S
D
P
E
R
C
N
L
M
S
T
G
H
J
K
COMMUTATION ENCODER
CONNECTOR PIN
R
S
T
N
P
J
K
L
M
E
F
G
H
A
B
C
D
ENCODER
Case Ground
N/C
S1
S2
S3
N/C
A
/A
B
/B
Z
/Z
/S1
/S2
/S3
Encoder V++
Encoder VDC COM
NOTE: All signal cables must be routed separately or with other circuits of
50VDC or less only
NOTE: All shielded cable must be minimum
18AWG /w overall shield
NOTE: Terminal description and jumper settings
Pin 5: For encoder supply voltage adjustment;
JP1 Installed=+5VDC, Removed=+12VDC
-------------------------------------------------------------------------------
Turn on all switches SW1,2,3.
23
24
25
26
17
18
19
20
21
22
27
28
29
30
11
12
13
14
15
16
1
2
3
7
8
4
5
*
6
9
10
PS5
TB1
PG-P2
REV D
Shield
Shield
Shield
No Connection
+12/+5 VDC
Common
ENC A+ input
ENC A- input
ENC B+ input
ENC B- input
ENC C+ input
ENC C- input
HS1+ input
HS1 - input
HS2+ input
HS2 - input
HS3+ input
HS3 - input
HS4 input
HS5 input
FREQ Ref Output
Common
ENC A+ output
ENC A - output
ENC B+ output
ENC B - output
ENC C+ output
ENC C- output
FREQ Ref + Input
FREQ Ref - Input
Terminal 12
NOTE:
Set Parameter F8 - 01=0
PG-P2 Rev D Connection Diagram for PS5
POWERTEC motor w/com encoder
POWERTEC
MOTOR
Hall-effect
Feedback Sensor
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
7
8
9
10
3
4
1
2
5
6
TB1-15
TB1-13
TB1- 5
TB1-20
TB1-17
TB1- 6
TB1-19
NOTE: Terminal description and jumper settings
Pin 5: For encoder supply voltage adjustment,
JP1 Installed=+5VDC, Removed=+12VDC
----------------------------------------------------------------------------------------
Turn off all switches SW1,2,3.
PS5
TB1
PG-P2
REV D
Shield
Shield
Shield
No Connection
+12/+5 VDC
Common
ENC A+ input
ENC A- input
ENC B+ input
ENC B- input
ENC C+ input
ENC C- input
HS1+ input
HS1 - input
HS2+ input
HS2 - input
HS3+ input
HS3 - input
HS4 input
HS5 input
FREQ Ref Output
Common
ENC A+ output
ENC A - output
ENC B+ output
ENC B - output
ENC C+ output
ENC C- output
FREQ Ref + Input
FREQ Ref - Input
24
25
26
27
18
19
20
21
22
23
28
29
30
12
13
14
15
10
11
8
9
6
7
16
17
1
2
3
4
5 *
Digimax
Controller
TB 2
Tach -
Tach +
Com
11
12
4
TB1
Com
+24V
Com
Out
TB1-21
4
7
10
11
TB1-22&30
TB1-29
Terminal 12
NOTE:
Set Parameter F8 - 01= 1
Set Parameter B1 - 01= 6
NOTE: All signal cables must be routed separately or with other circuits of
50VDC or less only
NOTE: All shielded cable must be minimum
18AWG /w overall shield
PG-P2 Rev D Connection Diagram for PS5
POWERTEC motor and Digimax controller
Page C-6 VS-616PS5 Installation & Quick Start Manual
C.3 PG-P2 Rev D Connection Diagrams
(continued)
POWERTEC
MOTOR
HS 2
HS1
+V
HS5
HS3
- V
HS4
P1
P2
SHLD
Hall-effect
Feedback Sensor
Orange
Brown
Red
Blue
Yellow
Black
Green
Shield
3
4
5
1
2
6
7
8
9
10
TB1-15
TB1-13
TB1- 5
TB1-17
TB1- 6
Motor mounted
Encoder
V+
V-
Chnl A+
Chnl A -
Chnl B+
Chnl B -
Chnl C+
Chnl C-
Shield
TB1- 5
TB1- 6
TB1- 7
TB1- 8
TB1- 9
TB1- 10
TB1- 11
TB1- 12
Digimax
Controller
TB 2
Tach -
Tach +
Com
11
12
4
TB1
Com
+24V
Com
Out
TB1-21
4
7
10
11
TB1-22&30
TB1-29
NOTE: Terminal description and jumper settings
Pin 5: For encoder supply voltage adjustment,
JP1 Installed=+5VDC, Removed=+12VDC
--------------------------------------------------------------------------------
Turn off all switches SW1,2,3.
23
24
25
26
17
18
19
20
21
22
27
28
29
30
11
12
13
14
9
10
7
8
5 *
6
15
16
3
4
1
2
PS5
TB1
PG-P2
REV D
Shield
Shield
Shield
No Connection
+12/+5 VDC
Common
ENC A+ input
ENC A- input
ENC B+ input
ENC B- input
ENC C+ input
ENC C- input
HS1+ input
HS1 - input
HS2+ input
HS2 - input
HS3+ input
HS3 - input
HS4 input
HS5 input
FREQ Ref Output
Common
ENC A+ output
ENC A - output
ENC B+ output
ENC B - output
ENC C+ output
ENC C- output
FREQ Ref + Input
FREQ Ref - Input
NOTE: All signal cables must be routed separately or with other circuits of
50VDC or less only
NOTE: All shielded cable must be minimum
18AWG /w overall shield
Terminal 12
NOTE:
Set Parameter F8 - 01= 0
Set Parameter B1 - 01= 6
PG-P2 Rev D Connection Diagram for PS5
POWERTEC motor/w aux. encoder and Digimax controller
MS Connector MS3102E20-29P
M
L
K
J
T
S
H
A
N
B
R
P
F
C
E
D
G
Suggested Mating
Connector
MS310GF-20-29S
COMMUTATION ENCODER
CONNECTOR PIN ENCODER
R
S
T
N
P
L
M
J
K
G
H
C
D
A
B
E
F
Case Ground
N/C
S1
S2
S3
N/C
A
/A
B
/B
Z
/Z
/S1
/S2
/S3
Encoder V++
Encoder VDC COM
NOTE: Terminal description and jumper settings
Pin 5: For encoder supply voltage adjustment,
JP1 Installed=+5VDC, Removed=+12VDC
-------------------------------------------------------------------------------
Turn on all switches SW1,2,3.
Digimax
Controller
TB 2
Tach -
Tach +
Com
11
12
4
TB1
Com
+24V
Com
Out
TB1-21
4
7
10
11
TB1-22&30
TB1-29
C
N
J
K
L
M
S
T
G
H
E
R
D
P
PS5
TB1
PG-P2
REV D
Shield
Shield
Shield
No Connection
+12/+5 VDC
Common
ENC A+ input
ENC A- input
ENC B+ input
ENC B- input
ENC C+ input
ENC C- input
HS1+ input
HS1 - input
HS2+ input
HS2 - input
HS3+ input
HS3 - input
HS4 input
HS5 input
FREQ Ref Output
Common
ENC A+ output
ENC A - output
ENC B+ output
ENC B - output
ENC C+ output
ENC C- output
FREQ Ref + Input
FREQ Ref - Input
24
25
26
27
18
19
20
21
22
23
28
29
30
12
13
14
15
10
11
8
9
16
17
1
2
3
6
7
4
5
*
Terminal 12
NOTE:
Set Parameter F8 - 01= 0
NOTE: All signal cables must be routed separately or with other circuits of
50VDC or less only
NOTE: All shielded cable must be minimum
18AWG /w overall shield
PG-P2 Rev D Connection Diagram for PS5
POWERTEC motor/w com encoder and Digimax controller
VS-616PS5 Installation & Quick Start Manual Page C-7
This page left intentionally blank.
Page C-8 VS-616PS5 Installation & Quick Start Manual
D.1
VS-616PS5 Parameter List....................................................................................................... D-1
D.1
Parameter List
No.
Parameter Description
Operation
U Operation
U1 Monitor
U1-01 Speed reference
U1-02 Output frequency
U1-03 Inverter output current
U1-05 Motor speed
U1-06 Output voltage
U1-07 DC bus voltage
U1-08 Output power
U1-09 Torque reference (internal)
U1-10 Input terminal status
U1-11 Output terminal status
U1-12 Internal control status 1
U1-13 Elapsed time
U1-14 Flash ID number
U1-15 External terminal 13 input voltage
U1-16 External terminal 14 input voltage
U1-17 External terminal 16 input voltage
U1-18 Motor torque current (I q
)
U1-19 Motor excitation current (I d)
U1-20 Primary frequency after SFS
U1-21 Speed controller ASR input
U1-22 Speed controller ASR output
U1-27 q Axis current control reference
U1-28 d Axis current control reference
U1-29 Voltage limit control output
U1-30 q Axis current control output
U1-31 d Axis current control output)
U1-32 Output voltage reference (V q
)
U1-33 Output voltage reference (V d
U1-41 LED check
)
U1-42 Internal control status 2
U1-43 Command 1 from option
U1-44 Command 2 from option
U1-45 External torque reference
U1-46 Torque compensation value
U1-47 DO-08H output status
VS-616PS5 Installation & Quick Start Manual
Unit Setting Range
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Access
Level
User
Setting
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
B
B
B
B
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.0~100.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
%
%
%
%
%
V
%
%
%
%
V
-
%
%
-
-
-
-
%
%
H
-
-
-
%
-
%
%
%
Hz
A
%
V ac
V dc kW
Default
Page D-1
No.
U1-49 Control section software number
U1-50 Speed detection PG counter value
U1-53 PID feedback
U1-54 DI-16H input status
U1-55 Hall Sensor Status
U2 Fault Trace
U2-01 Existing detected fault
U2-02 Previous detected fault
U2-03 Frequency reference when fault was detected
U2-04 Output frequency when fault was detected
U2-05 Output current when fault was detected
U2-06 Motor speed reference
U2-07 Output voltage when fault was detected
U2-08 DC bus voltage
U2-09 Output power
U2-10 Torque reference at fault
U2-11 Input terminal status
U2-12 Output terminal status
U2-13 Drive status before fault was detected
U2-14 Elapsed time since fault was detected
U2-15 Motor magnetizing current (I q
) at fault
U2-16 Motor magnetizing current (I d
) at fault
U2-17 Internal control status 2 at fault
U2-18 Command 1 from option at fault
U2-19 Command 2 from option at fault
U2-20 External torque reference at fault
U2-21 Torque compensation at fault
U2-22 Speed controller ASR output at fault
U3 Fault History
U3-01 Most recent fault code
U3-02 2nd most recent fault code
U3-03 3rd most recent fault code
U3-04 4th most recent fault code
U3-05 Elapsed time since most recent fault
U3-06 Elapsed time since 2nd most recent fault
U3-07 Elapsed time since 3rd most recent fault
U3-08 Elapsed time since 4th most recent fault
Initialization
A
A1
Initialization
Initialization Set-up
A1-01 Parameter access level
0: Operation only
1: User program
2: Quick start level
A1-03 Operator status
0: No initialization
2220: 2-Wire initialization
3: Basic level
4: Advanced level
3330: 3-Wire initialization
A1-04 Password entry
Page D-2
Parameter Description
-
-
%
%
%
-
-
-
-
Hz
A
%
V ac
V dc kW
%
-
-
%
-
H
-
-
%
H
H
H
H
-
-
-
-
Unit Setting Range
-
-
%
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Default
-
-
-
-
-
Access
Level
A
A
A
A
User
Setting
Q
Q
Q
B
Q
Q
Q
Q
B
A
A
A
A
A
A
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
0~4 2 Q
0~9999 0 Q
0000~9999 Q
VS-616PS5 Installation & Quick Start Manual
No.
Parameter Description
Programming
B Application
B1 Sequence
B1-01 Frequency reference selection
0: Operator
1: Terminals
2: Serial communication
3: Option PCB
4: CP-717
B1-02 Operation method selection
0: Operator
1: Terminals
2: Serial communication
3: Option PCB
4: CP-717
B1-03 Stopping method selection
0: Ramp to stop
1: Coast to stop
3: Coast with timer
B1-04 Prohibition of reverse operation
0: Reverse enabled 1: Reverse disabled
B1-05 Operation selection at zero speed
0: RUN at freq. ref
1: Stop
2: RUN at min freq.
3: RUN at zero rpm
B1-06 Local/Remote run select
0: Cycle extra RUN 1: Accept extra RUN
B2 Servo Speed Level
B2-01 Zero speed level (BB starting speed)
B3 Magnetic Pull-in
B3-02 Magnetic pull-in current
B3-04 Current ramp-up time
B3-05 Magnetic pull-in time
B4 Delay Timers
B4-01 On-delay timer
B4-02 Off-delay timer
B5 PID Control
B5-01 PID control mode selection
0: Disabled
1: Enabled D = feedback
2: Enabled D = feedfwd
B5-02 PID control proportional gain
B5-03 PID control integral time
B5-04 PID control integral limit
B5-05 PID control derivative time
B5-06 PID control limit
B5-07 PID control offset
B5-08 PID control output primary delay time
B6 Reference Hold
B6-01 Dwell reference at start (dwell level)
B6-02 Dwell time at start (dwell time)
B6-03 Dwell reference at stop (dwell level)
B6-04 Dwell time at stop (dwell time)
B7 Droop Control
B7-01 Droop capacity
B7-02 Droop delay time
VS-616PS5 Installation & Quick Start Manual
Unit Setting Range Default
Access
Level
User
Setting
-
0~4
0~4
1
1
Q
Q
-
-
-
-
%
% s s s s
0~3
0/1
0~3
0/1
0.0~20.0
0~150
0.0~5.0
0.0~5.0
0.0~300.0
0.0~300.0
-
% s
% s
% s
%
% s
% s s
-
0~2
0.00~25.00
0.00~360.0
0.0~100.0
0.00~10.00
0.0~100.0
±100.0
0.00~10.00
0.0~100.00
0.0~10.0
0.0~100.00
0.0~10.0
0.0~100.0
0.00~1.00
0
0
1
1
0.5
50
1.0
1.0
0.0
0.0
0
0.00
0.0
0.00
0.0
0.0
0.10
1.00
1.00
100.0
0.00
100.0
0.0
0.00
Q
B
A
A
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Page D-3
No.
Parameter Description
C
C1
Tuning Parameters
Accel/Decel
C1-01 Acceleration time 1
C1-02 Deceleration time 1
C1-03 Acceleration time 2
C1-04 Deceleration time 2
C1-05 Acceleration time 3
C1-06 Deceleration time 3
C1-07 Acceleration time 4
C1-08 Deceleration time 4
C1-09 Fast-stop time
C1-10 Accel/decel time setting units
0: 0.01 seconds 1: 0.1 seconds
C1-11 Accel/decel time switching speed level
C2 PG Origin Pulse Compensation
C2-13 PG origin pulse compensation value
C3 Voltage Limit Control
C3-05 Voltage limit control selection
C5 ASR Tuning
C5-01 ASR proportional gain 1
C5-02 ASR integral time 1
C5-03 ASR proportional gain 2
C5-04 ASR integral time 2
C5-05 ASR output primary delay time
C5-06 ASR switching speed level
C5-07 ASR p gain at start
C6 Carrier Frequency
C6-02 Carrier frequency
C6-13 Pulse Reference Ratio Denominator Value
C6-14 Pulse Reference Ratio Numerator Value
C7 S-Curve Accel/Decel Characteristics
C7-01 S-Curve characteristic time at start of acceleration
C7-02 S-Curve characteristic time at end of acceleration
C7-03 S-Curve characteristic time at start of deceleration
C7-04 S-Curve characteristic time at end of deceleration
D
D1
Reference Parameters
Preset References
D1-01 Preset reference 1
D1-02 Preset reference 2
D1-03 Preset reference 3
D1-04 Preset reference 4
D1-05 Preset reference 5
D1-06 Preset reference 6
D1-07 Preset reference 7
D1-08 Preset reference 8
D1-09 Jog frequency reference
*
KVA dependant parameter
Page D-4 kHz
-
s s s s
s
%
s
s
-
-
% s s s s s s s s s degrees
0.00~6000.0
0.00~6000.0
0.00~6000.0
0.00~6000.0
0.00~6000.0
0.00~6000.0
0.00~6000.0
0.00~6000.0
0.00~6000.0
0/1
0.0~100.0
±180
°
0/1
0.00~300.00
0.000~10.000
0.00~300.00
0.000~10.000
0.000~0.500
0.00~100.00
0.00~300.00
2,4,6,8,12
0~1000
0~1000
0.00~250.0
0.00~250.0
0.00~250.0
0.00~250.0
Unit Setting Range Default
Access
Level
User
Setting
A
A
A
A
A
A
A
A
A
A
A
B
B
B
B
A
A
A
A
B
A
A
B
Q
Q
B
Q
0
5.00
0.500
5.00
0.500
0.004
0.00
5.00
*
0
0
0.00
0.00
0.00
0.00
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
1
0.0
-
%
%
%
%
%
%
%
%
%
0.00~100.00
0.00~100.00
0.00~100.00
0.00~100.00
0.00~100.00
0.00~100.00
0.00~100.00
0.00~100.00
0.00~100.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
10.00
B
B
B
B
Q
Q
Q
Q
Q
VS-616PS5 Installation & Quick Start Manual
No.
Parameter Description
D2 Reference Limits
D2-01 Reference upper limit
D2-02 Reference lower limit
D3 Jump Frequencies
D3-01 Jump frequency reference 1
D3-02 Jump frequency reference 2
D3-03 Jump frequency reference 3
D3-04 Jump frequency reference bandwidth
D4 Hold reference memory
D4-01 Hold reference memory selection - Up/Down
0: Disabled 1: Enabled
D5 Torque Control
D5-01 Torque control selection
0: Speed control 1: Torque control
D5-02 Torque limit primary delay time
D5-03 Speed limit input selection
1: Analog Input
D5-04 Speed limit value
D5-05 Speed limit bias
D5-06 Reference delay time
E
E1
Motor Parameters
Motor Constant
E1-01 Input voltage setting
2: Program Setting
E1-02 Motor capacity selection
E1-03 Motor rated voltage
E1-04 Motor rated current
E1-05 Number of motor poles
E1-06 Maximum motor speed
E1-07 Base motor speed
E1-08 Minimum motor speed
E1-09 Motor armature resistance
E1-10 Motor d axis inductance
E1-11 Motor q axis inductance
E1-13 Induced voltage constant
E1-15 Motor mechanical loss
E1-16 Motor feeder resistance
E1-17 Motor connection selection
0: 1D
1: 2D
F
F1
Option Parameters
PG Option Setup
2: 1Y
3: 2Y
F1-01 PG pulses per revolution
F1-02 PG disconnection detection stopping method
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
F1-03 Overspeed detection stopping method
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
VS-616PS5 Installation & Quick Start Manual
-
-
-
ms
-
%
% ms
Unit Setting Range
%
%
%
%
%
%
-
0.0~110.0
0.0~100.0
0.0~200.0
0.0~200.0
0.0~200.0
0.0~200.0
0/1
Default
100.0
0.0
0.0
0.0
0.0
1.0
0
Access
Level
User
Setting
A
A
A
A
B
B
A
0/1
0~1000
1/2
±120
0~120
0~1000
1
0
5
50
0
0
A
A
A
A
A
A
A
rpm rpm rpm
Ω mH mH
V
-
V
180~230
1000~1239
0.0~255.0
0.0~200.0
2, 4, 6, 8
0~6000
0~6000
0~6000
0.000~65.535
0.00~600.00
0.00~600.00
mV/rpm 20.0~500.0
% 0.0~10.0
% 0.0~10.0
0~3
*
*
*
*
*
*
*
230
1000
*
*
*
*
*
0
Q
A
A
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
0~10000
0~3
0~3
30
1
1
Q
B
B
Page D-5
No.
Parameter Description
F1-04 PG deviation detection stopping method
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
F1-05 PG rotation selection
0: CCW 1: CW
F1-08 Overspeed detection level
F1-09 Overspeed detection time
F1-10 PG deviation detection level
F1-11 PG deviation detection time
F1-13 PG open phase detection delay time
F2 A1-14B Setup
F2-01 Bipolar or unipolar input selection
0: 3-channel individual 1: 3-channel additional
F3 D1-08/DI-16H Setup
F3-01 Digital input option
0: BCD 1%
1: BCD 0.1%
F4 AO-08/AO-12 Setup
2: BCD 0.01%
7: Binary
F4-01 Analog output Channel 1 selection
1: Speed reference
2: Output frequency
3: Inverter output current
5: Motor speed
6: Output voltage
7: DC bus voltage
8: Output power
9: Torque reference (internal)
15: External terminal 13 input voltage
16: External terminal 14 input voltage
17: External terminal 16 input voltage
18: Motor secondary current (I q
)
)
19: Motor excitation current (I d
20: Primary frequency after SFS
21: Speed controller ASR input
22: Speed controller ASR output
27: q Axis current control reference
28: d Axis current control reference
29: Voltage limit control output
30: q Axis current control output
31: d Axis current control output
32: Output voltage reference (V q
33: Output voltage reference (V d
45: External torque reference
46: Torque compensation value
)
)
49: Control section software number
50: Speed detection PG counter value
53: PID feedback
F4-02 Analog output channel 1 gain
F4-03 Analog output channel 1 bias
F4-04 Analog output channel 2 selection
(same as F4-01)
F4-05 Analog output channel 2 gain
Page D-6
-
% s
% s s
Unit Setting Range
0~3
0/1
0~120
0~2.0
0~50
0~10.0
0.0~10.0
0/1
Default
3
1
115
0.0
10
0.5
3.0
0
Access
Level
User
Setting
B
Q
A
A
A
A
A
A
0~7 0 A
-
-
%
-
-
1~60
±300.0
±109.2
1~60
±300.0
5
1.0
0.0
3
1.0
A
A
A
A
A
VS-616PS5 Installation & Quick Start Manual
No.
Parameter Description
F4-06 Analog output channel 2 bias
F5 DO-02 Setup
F5-01 DO-02C digital output channel 1 selection
0: During RUN 1
1: Zero speed
2: Fref/Fout agree 1
3: Fref/Set agree 1
4: Frequency detection 1
5: Frequency detection 2
6: Inverter Ready
7: DC bus undervoltage
8: Baseblock 1
9: Option reference
A: Remote operation
B: Torque detection 1 (N.O.)
C: Loss of reference
D: DB overheat
E. Fault
F: Not used
10: Minor fault
11: Reset command active
12: Timer output
13: Fref/Fout agree 2
14: Fref/Set agree 2
15: Frequency detection 3
16: Frequency detection 4
17: Torque detection 1 (N.C.)
18: Torque detection 2 (N.O.)
19: Torque detection 2 (N.C.)
1A: Reverse direction
1B: Baseblock 2
1D: Regenerating
1E: Restart enabled
1F: Overload (OL1)
20: OH prealarm
30: Current/Torque limit
31: Speed limit
37: During RUN 2
F5-02 DO-02C digital output Channel 2 selection
(same as F5-01)
F6 DO-08 Set-up
F6-01 DO-08 digital output selection
0: 8-channel Individual 1: Binary Output
F8 PG-P2/H2 Set-up
F8-01 Speed feedback method selection
0: Encoder inputs 1: Hall sensor input
F8-02 Pulse train moving average value
0=1 Scan (5msec)
F9 CP-916 Set-up
F9-01 External fault input level from communication option
F9-02 External fault from communication level
F9-03 Operation at external fault input from communication option
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
VS-616PS5 Installation & Quick Start Manual
Unit Setting Range
±109.2
-
-
-
-
-
-
-
0~FF
0~3F
0/1
0/1
0-50
0/1
0/1
0~3
Default
0.0
Access
Level
A
User
Setting
0
1
0
1
0
0
0
1
A
A
A
Q
B
A
A
A
Page D-7
No.
Parameter Description
F9-04 Trace sampling of option
F9-05 Torque reference selection from communication option
0: Torque reference/limit from terminal
1: Torque reference/limit from option
F9-06 Operation at bus error detection
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
H
H1
Control Circuit Terminal Parameters
Digital Inputs
H1-01 Multi-function input terminal 3 selection
0: 3-Wire control
1: Local/Remote selection
2: Option/Inverter selection
3: Multi-step reference 1
4: Multi-step reference 2
5: Multi-step reference 3
6: Jog frequency reference
7: Multi-accel/decel 1
8: External baseblock N.O.
9: External baseblock N.C.
A: Accel/Decel ramp hold
B: OH2 alarm signal
C: Terminal 16 enable
E: ASR integral reset
F: Terminal not used
10: MOP increase
11: MOP decrease
12: Forward jog
13: Reverse jog
14: Fault reset
15: Fast-stop
18: Timer function
19: PID disable
1A: Multi-accel/decel 2
1B: Program lockout
1E: Reference sample hold
1F: Terminal 13/14 switch
24: external Fault
71: Speed/Torque control change
77: ASR gain switch
H1-02 Multi-function input terminal 4 selection
(same as H1-01)
H1-03 Multi-function input terminal 5 selection
(same as H1-01)
H1-04 Multi-function input terminal 6 selection
(same as H1-01)
H1-05 Multi-function input terminal 7 selection
(same as H1-01)
H1-06 Multi-function input terminal 8 selection
(same as H1-01)
H2 Digital Outputs
H2-01 Multi-function output 1 selection (terminal 9, 10) (same as
F5-01)
Page D-8
Unit Setting Range
-
0~60000
0/1
-
-
-
-
-
-
-
0~3
0~FF
0~FF
0~FF
0~FF
0~FF
0~FF
0~FF
Default
0
0
1
24
14
3
4
6
8
0
Access
Level
A
A
A
B
B
B
B
B
B
B
User
Setting
VS-616PS5 Installation & Quick Start Manual
No.
Parameter Description
H2-02 Multi-function output 2 selection (terminal 25, 27)
(same as F5-01)
H2-03 Multi-function output 3 (terminal 26, 27)
(same as F5-01)
H3 Analog Inputs
H3-01 Terminal 13 signal selection
0: 0 to 10V dc
1: ±10V dc
H3-02 Terminal 13 reference % gain
H3-03 Terminal 13 reference ±% bias
H3-04 Terminal 16 signal selection
0: 0 to 10V dc
1: ±10V dc
H3-05 Terminal 16 multi-function selection
0: Auxiliary reference
1: Frequency gain
2: Frequency bias
7: Overtorque level
9: Reference lower limit
A: Jump frequency
B: PID feedback
10: Forward torque limit
11: Reverse torque limit
12: Regenerative torque limit
13: Torque reference
14: Torque compensation
15: Forward/reverse torque limit
H3-06 Terminal 16 reference % gain)
H3-07 Terminal 16 reference ±% bias
H3-08 Terminal 14 signal selection
0: 0 to 10V
1: ±10V
2: 4 to 20mA
H3-09 Terminal 14 multi-function selection
(same as H3-05)
H3-10 Terminal 14 reference % gain
H3-11 Terminal 14 reference ±% bias
H3-12 Analog input filter time constant
(terminals 13, 14 & 16)
H4 Analog Outputs
H4-01 Terminal 21 analog output selection
(same as F4-01)
H4-02 Terminal 21 analog output gain
H4-03 Terminal 21 analog output bias
H4-04 Terminal 23 analog output selection
(same as F4-01)
H4-05 Terminal 23 analog output gain
H4-06 Terminal 23 analog output bias
H4-07 Analog output signal selection
0: 0 to 10V dc
1: ±10V dc
H5 Serial Communications
H5-01 Serial communication station address
H5-02 Serial communication speed selection
0: 1200 bps, 1: 2400 bps, 2: 4800 bps, 3: 9600 bps
VS-616PS5 Installation & Quick Start Manual
-
%
%
-
Unit Setting Range
-
0~FF
0~3F
Default
1
2
Access
Level
User
Setting
B
B
0/1
0.0~1000.0
±100.0
0/1
0
100.0
0.0
0
B
B
B
A
-
%
%
-
-
%
% s
-
-
%
-
-
%
-
1
1
0~1F
0.0~1000.0
±100.0
0~2
0~1F
0.0~1000.0
±100.0
0.00~2.00
1~60
±300.0
±109.2
1~60
±300.0
±109.2
0/1
0-20
0-3
0
100.0
0.0
2
1F
100.0
0.0
0.00
3
1.0
0.0
5
1.0
0.0
0
1F
3
A
B
B
B
B
B
B
B
A
A
A
A
A
A
A
A
A
Page D-9
No.
Parameter Description
H5-03 Serial communication speed selection
0: No parity, 1: Even parity, 2: Odd parity
H5-04 Stopping method after communication error
0: Ramp to stop, 1: Coast to stop, 2: Fast stop, 3: Alarm only
H5-05 Serial communication timeover detection
0: Disabled , 1: Enabled
L
L2
Protection Parameters
Power Loss Ride through
L2-01 Momentary power loss ride through
0: Disabled
L2-02* Momentary power loss ride through time
L2-05 Undervoltage detection level
L3 Stall Prevention/Current Limit
L3-01 Overvoltage protection (stall prevention during decel)
0: Disabled 1: Enabled
L4 Reference Detection
L4-01 Speed agree detection level (without sign)
L4-02 Speed agree detection width
L4-03 Speed agree detection level (with sign)
L4-04 Speed agree detection width
L4-05 Operation when frequency reference is missing
0: Stop 1: Run at 80% of previous reference
L5 Fault Restart
L5-01 Number of automatic restart attempts
L5-02 Automatic restart operation selection
0: No fault relay 1: Fault relay active
L6 Torque Detection
L6-01 Overtorque detection 1 selection
0: Disabled
1: Alarm at speed agree
2: Alarm at run
3: Fault at speed agree
4: Fault at run
L6-02 Overtorque detection 1 level
L6-03 Overtorque detection 1 time
L6-04 Overtorque detection 2 selection
0: Disabled
2: Alarm at run
3: Fault at speed agree
1: Alarm at speed agree 4: Fault at run
L6-05 Overtorque detection 2 level
L6-06 Overtorque detection 2 time
L7 Torque Limit
L7-01 Forward torque limit
L7-02 Reverse torque limit
L7-03 Regenerative forward torque limit
L7-04 Regenerative reverse torque limit
L8 Hardware Protection
L8-01 Protection selection for internal DB resistor
0: Not Provided 1: Provided
L8-02 OH pre-alarm level
Unit Setting Range
-
-
-
-
-
-
-
1
1
1
s
V
%
%
%
%
% s
% s
%
%
%
%
ºC
0-2
0-3
0,1
0
0.0~2.0
150~210
0~1
0.0~100.0
0.0~100.0
0~±100.0
0.0~100.0
0/1
0~10
0/1
0~4
0~300
0.0~10.0
0~4
0~300
0.0~10.0
0~300
0~300
0~300
0~300
0/1
50~110
Default
0
3
1
0
0.7
190
1
150
150
150
150
0.0
2.0
0.0
2.0
0
0
0
0
150
0.1
0
150
0.1
0
95
*
Default for Parameter L2-02 is model dependant. For clarification, please refer to Parameter 02-04: Inverter Model Selection
Access
Level
User
Setting
A
A
A
B
B
A
A
A
B
B
B
B
A
B
B
B
B
B
B
A
A
B
B
A
A
A
Page D-10 VS-616PS5 Installation & Quick Start Manual
No.
Parameter Description
L8-03 Stopping method selection after OH pre-alarm
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
L8-05 Input phase loss protection
0: Disabled
L8-07 Output phase loss protection
0: Disabled
1: Enabled
1: Enabled
L8-10 Ground fault protection selection
0: Disabled 1: Enabled
O
O1
Operator Parameters
Monitor Selection
O1-01 Analog output Channel 1 selection
5: Motor speed
6: Output voltage
7: DC bus voltage
8: Output power
9: Torque reference (internal)
15: External terminal 13 input voltage
16: External terminal 14 input voltage
17: External terminal 16 input voltage
18: Motor secondary current (I
19: Motor excitation current (I d q
)
)
20: Primary speed after SFS
21: Speed controller ASR input
22: Speed controller ASR output
27: q Axis current control reference
28: d Axis current control reference
29: Voltage limit control output
30: q Axis current control output
31: d Axis current control output
32: Output voltage reference (V q
33: Output voltage reference (V d
45: External torque reference
46: Torque compensation value
)
)
49: Control section software number
50: Speed detection PG counter value
53: PID feedback
54: DI-16H input status
O1-02 Monitor selection after power-up
1: Speed reference
2: Output speed
3: Output current
4: User monitor
O1-03 Scale for setting and monitoring frequency
O2 Key Selection
O2-01 Local/remote key
0: Disabled 1: Enabled
O2-02 STOP key during external terminal operation
0: Disabled 1: Enabled
O2-04 Inverter model selection
O2-05 Digital operator M.O.P. mode selection
0: Disabled 1: Enabled
O2-06 Digital operator disconnection detection
0: Disabled 1: Enabled
O2-07 Operation time setting
VS-616PS5 Installation & Quick Start Manual
-
-
-
Unit Setting Range
0~3
0/1
0/1
0/1
Default
3
0
0
1
Access
Level
User
Setting
A
A
A
A
-
-
-
-
-
-
-
1
H
5~53
1~4
0~39999
0/1
0/1
00~FF
0/1
0/1
0~65535
6
1
1
B
B
B
1 B
0 B kVA dependent B
0 A
0
0
A
A
Page D-11
No.
Parameter Description
O2-08 Cumulative 0peration time selection
0: Power-ON time 1: Running time
T
T1
Tuning
Auto-tuning
T1-02 Tuning mode
0: Normal running mode
2: Auto-tuning mode
T1-03 Tuning operation selection
0: Auto-tuning procedures are performed for all parameters
1: Only PG origin pulse adjustment is performed
Unit Setting Range
0/1
-
0/2
0/1
Default
0
Access
Level
User
Setting
A
0
1
Q
Q
Page D-12 VS-616PS5 Installation & Quick Start Manual
YASKAWA ELECTRIC AMERICA, INC.
Chicago-Corporate Headquarters 2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: (847) 887-7000 Fax: (847) 887-7310 Internet: http://www.yaskawa.com
MOTOMAN INC.
805 Liberty Lane, West Carrollton, OH 45449, U.S.A.
Phone: (937) 847-6200 Fax: (937) 847-6277 Internet: http://www.motoman.com
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580 Internet: http://www.yaskawa.co.jp
YASKAWA ELETRICO DO BRASIL COMERCIO LTDA.
Avenida Fagundes Filho, 620 Bairro Saude Sao Paolo-SP, Brasil CEP: 04304-000
Phone: 55-11-5071-2552 Fax: 55-11-5581-8795 Internet: http://www.yaskawa.com.br
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone: 49-6196-569-300 Fax: 49-6196-888-301 Internet: http://www.yaskawa.de
MOTOMAN ROBOTICS AB
Box 504 S38525, Torsas, Sweden
Phone: 46-486-48800 Fax: 46-486-41410
MOTOMAN ROBOTEC GmbH
Kammerfeldstra β e 1, 85391 Allershausen, Germany
Phone: 49-8166-900 Fax: 49-8166-9039
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, Scotland, United Kingdom
Phone: 44-12-3673-5000 Fax: 44-12-3645-8182
YASKAWA ELECTRIC KOREA CORPORATION
Paik Nam Bldg. 901 188-3, 1-Ga Euljiro, Joong-Gu, Seoul, Korea
Phone: 82-2-776-7844 Fax: 82-2-753-2639
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
Head Office: 151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, SINGAPORE
Phone: 65-282-3003 Fax: 65-289-3003
TAIPEI OFFICE (AND YATEC ENGINEERING CORPORATION)
10F 146 Sung Chiang Road, Taipei, Taiwan
Phone: 886-2-2563-0010 Fax: 886-2-2567-4677
YASKAWA JASON (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone: 852-2803-2385 Fax: 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club,
21 Jianguomanwai Avenue, Beijing 100020, China
Phone: 86-10-6532-1850 Fax: 86-10-6532-1851
SHANGHAI OFFICE
27 Hui He Road Shanghai 200437 China
Phone: 86-21-6553-6600 Fax: 86-21-6531-4242
SHANGHAI YASKAWA-TONJI M & E CO., LTD.
27 Hui He Road Shanghai 200437 China
Phone: 86-21-6533-2828 Fax: 86-21-6553-6677
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing 100083 China
Phone: 86-10-6232-9943 Fax: 86-10-6234-5002
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic & Technological Development Area,
Beijing 100076 China
Phone: 86-10-6788-0551 Fax: 86-10-6788-2878
Yaskawa Electric America, Inc., November 1999 YEA-TOA-S606-12B Printed In U.S.A.