V7N Drive with DeviceNet
Installation Guide
YEA Document Number: IG.V7N.01 5/23/07 Software Version: 3005
Data Subject to change without notice.
Yaskawa Electric America, Inc.
Models: CIMR-V7NU Document Number: IG.V7N.01
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 2
WARNINGS, CAUTIONS, INSTRUCTIONS
WARNING
YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application of YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
YASKAWA product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All products designed to incorporate a component part manufactured by YASKAWA must be supplied to the end user with appropriate warnings and instructions as to that part’s safe use and operation. Any warnings provided by YASKAWA must be promptly provided to the end user. YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the
YASKAWA manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
YASKAWA assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
WARNING
• Do not connect or disconnect wiring while the power is on. Do not remove covers or touch circuit boards while the power is on.
• Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned OFF. Status indicator LEDs and Digital Operator display will be extinguished when the DC bus voltage is below
50 VDC. To prevent electric shock, wait at least 5 minutes after all indicators are
OFF.
• Do not perform a withstand voltage test on any part of the unit. This equipment uses sensitive devices and may be damaged by high voltage.
• The drive is not suitable for circuits capable of delivering more than 18,000 RMS symmetrical amperes at 250V maximum or 480V maximum. Install adequate branch short circuit protection. Refer to page 16. Failure to do so may result in equipment damage and/or personal injury.
IMPORTANT
• Wiring should be performed only by qualified personnel.
• Verify that the rated voltage of the Drive matches the voltage of the incoming power.
• Some drawings in this manual are shown with the protective covers and shields removed, in order to describe detail with more clarity. Make sure all covers and shields are replaced before operating this product.
• This manual may be modified when necessary because of product improvement, modification, or changes in specifications.
• YASKAWA is not responsible for any modification of the product made by the user, doing so will void the warranty.
2
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 3
SECTION
1
2
6
7
8
3
4
5
9
10
11
CONTENTS
DESCRIPTION PAGE
Specifications ......................................................................................... 4
Preliminary Inspection ............................................................................ 6
Introduction ............................................................................................. 6
Receiving ............................................................................................... 6
Nameplate Structure .............................................................................. 7
Mounting Precautions ............................................................................ 8
Wiring ...................................................................................................... 9
Main Circuit Input/Output Wiring ............................................................. 9
Control Circuit Wiring ............................................................................. 9
Grounding .............................................................................................. 10
Wire & Terminal Screw Sizes ................................................................ 10
Terminal Functions & Voltages .............................................................. 11
Network Connection DeviceNet ..............................................................12
Switch Settings and LEDs.......................................................................14
Set Drive Parameters..............................................................................15
EDS Files ................................................................................................16
Supported Assemblies ............................................................................17
Peripheral Devices ................................................................................. 20
Conformance to European EMC Directive ............................................ 22
Interconnection Precautions and Diagrams .......................................... 23
2-Wire Control ....................................................................................... 24
3-Wire Control ....................................................................................... 25
Drive Parameter Listing ......................................................................... 26
Monitor Displays .................................................................................... 33
Drive Dimensions .................................................................................. 34
3
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 4
Drive
Specifications Section 1
Standard Specifications
SECTION A. Model No. Related Specifications
230V Class
Model CIMR-V7NU
Max. applicable motor output
HP (kW) (1)
Drive capacity (kVA)
Rated Output Current (A)
Rated Input Current (A)
Max. Output Voltage (V)
Max. Output Frequency (Hz)
Rated Input Voltage and
Frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Cooling Method
(QTY)
20P1
1/8 (0.1) 1/4 (0.2) 1/2 (0.4) 3/4 & 1 (0.7) 2 (1.5)
0.3
0.8
1.1
self
20P2
0.6
1.6
1.8
self
20P4 self
20P7 22P2
3 (2.2)
3-phase. 200 to 230 V, 50/60 Hz fan
21P5
-15% to +10%
±5% fan fan
23P7
5 (3.7)
1.1
3.0
3.9
1.9
5.0
6.4
3.0
8.0
11.0
4.2
11.0
15.1
200 to 230V (proportional to input voltage)
400 Hz (programmable)
6.7
17.5
24.0
fan
460V Class
Model CIMR-V7NU
Max. applicable motor output HP (kW) (1)
Drive capacity (kVA)
Rated Output Current (A)
Rated Input Current (A)
Max. Output Voltage (V)
Max. Output Frequency (Hz)
Rated Input Voltage and
Frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Cooling Method
(QTY)
- -
- -
- -
- -
- -
- -
40P2 40P4 40P7 41P5
1/2 (0.2) 3/4 (0.4) 1 & 2 (0.7) 3 (1.5)
0.9
1.2
1.6
42P2
3 (2.2)
43P7
5 (3.7)
1.4
1.8
2.4
2.6
3.4
4.7
3.7
4.8
7.0
4.2
5.5
8.1
380 to 460V (proportional to input voltage)
400 Hz (programmable)
7
8.6
12.0
3-phase. 380 to 460 V, 50/60 Hz
-15% to +10%
±5% self self self fan fan fan
Control method
Frequency control range
Frequency accuracy
(temperature change)
Speed Regulation
Frequency setting resolution
Output frequency resolution
Overload capacity
Frequency Reference Signal
Accel/Decel Time
Braking Torque
V/f characteristics
25P5 27P5
7.5 (5.5) 10 (7.5)
9.5
25
33.0
13
33
39.6
fan(2) fan(2)
SECTION B. All Drives
Sine wave PWM (V/f Control or Open Loop Vector)
0.1 to 400 Hz
Digital command: ±0.01% (14 to 122°F, -10 to +50°C)
Analog command: ±0.5% (77°F ± 18°F, 25°C ± 10°C)
Open Loop Vector: ±0.2%
V/Hz Mode: ±0.5% – 1% with Slip Compensation
Digital Operator reference: 0.01 Hz (< 100Hz)
0.1 Hz (100Hz or more)
Analog reference: 0.06Hz/60Hz (1/1000)
0.01 Hz
150% of rated output current for 1 minute
0 to 10VDC (20k ), 4 to 20mA (250 ), 0 to 20mA (250 ) pulse train input,
Digital Operator Pot
0.01 to 6000 sec.
(accel/decel time are independently programmed)
Short-term average deceleration torque (2)
0.2kW: 150%
0.75kW: 100%
1.5kW: 50%
2.2kW or more: 20%
Continuous regenerative torque: Approx. 20% (150% with optional braking resistor, braking transistor built-in)
Custom V/f pattern fan(2)
45P5
7.5 &
10 (5.5)
11
14.8
19.6
47P5
10 (7.5)
14
18
23.8
fan(2)
See notes at end of table.
(table continued on next page)
4
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 5
Section 1
Drive
Specifications
Standard Specifications (Continued)
Motor overload protection
Instantaneous overcurrent
Overload
Overvoltage
Undervoltage
Momentary Power Loss
Heatsink overheat
Stall prevention level
Ground fault
Power charge indication
Cooling Fan Fault
Run/stop input
Multi-function input
Multi-function output
Standard functions
Status indicator LEDs
Digital Operator
SECTION B. All Drives (Continued)
Electronic thermal overload relay
Motor coasts to stop at approx. 250% of Drive current
Motor coasts to stop after 1 min. at 150% of
Drive rated current (7)
Motor coasts to stop if DC bus voltage exceeds
410VDC (230V), 820VDC (460V)
Motor coasts to stop when DC bus voltage is
210VDC or less (230V), 400VDC or less (460V)
The following operations are selectable:
• Not provided (stops if power loss is 15 ms or longer)
• Automatic restart at recovery from 0.5 sec. power loss
• Automatic restart
Protected by electronic circuit
Independently programmable during accel and constant-speed running. Selectable during decel.
Protected by electronic circuit (overcurrent level)
ON until the DC bus voltage becomes 50V or less.
RUN lamp says ON or digital operator LED stays ON.
(Charge LED is Provided for 400V)
Protected by electronic circuit
2-Wire or 3-Wire
Seven of the following input signals are selectable: (3)
Forward/reverse run (3-Wire sequence), fault reset, external fault (NO/NC contact input), multi-step speed operation,
Jog command, accel/decel time select, external baseblock (NO/NC contact input), speed search command, accel/decel hold command, LOCAL/REMOTE selection,
DeviceNet communication/control circuit terminal selection, emergency stop fault emergency stop alarm
Following output signals are selectable
(1 NO/NC contact output, 2 photo-coupler outputs): (4)
Fault, running, zero speed, at frequency, frequency detection
(output frequency ≤ or ≥ set value), during overtorque detection, during undervoltage detection, minor error, during baseblock, operation mode, inverter run ready, during fault retry, during UV, during speed search, data output through DeviceNet communication
Open Loop Vector Control, full-range automatic torque boost, auto restart, upper/lower frequency limit, DC injection braking current/time at start/stop, frequency reference gain/bias, prohibited frequencies, analog meter calibrating gain, S-curve accel/decel, slip compensation,
DeviceNet communications, frequency reference from digital operator pot
RUN and ALARM LEDs provided as standard
Monitors frequency reference, output frequency, output current, FWD/REF selection
Screw terminals for both main circuit and control circuit Terminals
Wiring distance between
Drive and motor
Enclosure
Cooling method
Input Power
DeviceNet Specification
DeviceNet Profile
Connector Type
Physical Layer Type
MAC ID Setting
Baud Rate
Supported Message
I/O Assembly Instance
Ambient temperature
Humidity
Storage temperature (6)
Location
Elevation
Vibration
328 ft (100 m) or less (5)
Nema Type 1
Self-cooling/cooling fan
Voltage: 11 to 25VDC
Current: 40mA
Conformance level 16: Passed
AC Drive Device Type 2
5-pin open-style screw connector
Isolated Physical Layer
CAN transceiver + photo coupler
2 Rotary-switches: MAC ID 0 to 63; Parameter setting available
A rotary-switch: 125/250/500 kbaud/Auto Baud; Parameter setting available
Group 2 only server
Explicit and Polled I/O messaging
Input: 5 types (4-8 bytes)
Output: 5 types (4-8 bytes)
14 to 104°F (-10 to 40°C)
95% RH or less (non-condensing)
-4 to 140°F (-20 to 60°C)
Indoor (free from corrosive gases or dust)
3,280 feet (1,000 m) or less
Up to 1G, at less than 20 Hz; up to 0.2G, at 20 to 50 Hz
NOTES:
(1)
(2)
(3)
(4)
(5)
(6)
Based on an N.E.C. standard 4-pole motor for max. applicable motor output.
Shows deceleration torque for an uncoupled motor decelerating from 60 Hz in 0.1 seconds.
Four of these input signals are present on the control terminal, and three are controlled via DeviceNet communications.
Two photo-coupler outputs are present on the control terminal, and one NO contact output is controlled via DeviceNet communications.
Contact Yaskawa for wiring distances greater than 328 ft. (100 m).
Temperature during shipping (for short periods of time).
5
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 6
Preliminary
Inspection Section 2
Introduction
This document pertains to the V7N AC Drive. In this document, the word “Drive”, “AC Drive”, and
“inverter” may be used interchangeably. The V7N is a general purpose sine-coded pulse width modulated AC motor Drive with embedded DeviceNet communications. It generates an adjustable voltage/frequency three phase output for complete speed control of most conventional squirrel cage induction motors. Automatic stall prevention and voltage boost prevent nuisance tripping during load or line side transient conditions. The Drive will not induce any voltage line notching distortion back to the utility line, and it maintains a displacement power factor of not less than 0.98 throughout its speed range.
When properly installed, operated and maintained, the Drive will provide a lifetime of service. It is mandatory that the person who operates, inspects, or maintains this equipment thoroughly read and understand this manual before proceeding.
This installation guide details installation procedures and parameter setting ranges for the V7N
Drive. For programming and DeviceNet Communication protocol requirements, refer to the V7N
Drive with DeviceNet Technical Manual TM.V7N.01.
Receiving
Check nameplate - Be certain your input voltage source, motor and Drive nameplates are all marked either 230V or 460V. Other voltages can be used, but require additional programming; see TM.V7N.01.
6
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 7
Section 2
Nameplate Structure
MODEL NO.
INPUT SPEC
OUTPUT SPEC
LOT NO.
SERIAL NO.
MODEL : CIMR–V7NU40P7 SPEC: 40P71
INPUT : 3PH 380–460VAC 50/60Hz 4.7A
OUTPUT:
O / N
S / N :
:
3PH 0–460VAC MAX 0–400Hz 3.4A
0P1689–003–9
J00199961000009
MASS: 1.7kg
PRG: 0011
INSTALLATION CATEGORY II IP20
V7N Nameplate
MS
Model No. C I M R - V 7 N U 2 0 P 1
Preliminary
Inspection
DRIVE SPEC
MASS
SOFTWARE NO.
INSTALLATION CATEGORY
DRIVE
V7 SERIES
N Embedded DeviceNet Communications
No. Applicable maximum motor output
0P1 0.13 HP
0P2 0.25 HP
0P4 0.5 HP
0P7 1 HP
1P5 2 HP
2P2 3 HP
3P0 4 HP
3P7 5 HP
5P5 7.5 HP
7P5 10 HP
No. Voltage Class
B Single-phase 230VAC
2 Three-phase 230VAC
4 Three-phase 460VAC
No. Specifications
U
UL Specification (U.S.
Specification)
Drive Spec 2 0 P 1 1
B Single-phase 230VAC
2 Three-phase 230VAC
4
Three-phase 460VAC
No. Applicable maximum motor output
0P1 0.13 HP
0P2 0.25 HP
0P4
0P7
1P5
2P2
3P0
3P7
5P5
7P5
0.5 HP
1 HP
2 HP
3 HP
4 HP
5 HP
7.5 HP
10 HP
No. Protective structure
0 Open chassis
(IP20, IP00)
1 Enclosed wall-mounted
(NEMA 1)
7
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 8
Mounting
Precautions Section 3
Location of the Drive is important to achieve proper performance and normal operating life. The unit should be installed in an area where it will be protected from:
• Extreme cold and heat. Use only within the ambient temperature range (for open chassis type): 14 to 122°F (-10 to +50°C) (for enclosed wall mount type): 14 to 104°F (10 to +40°C)
• Rain, moisture
• Oil sprays, splashes
• Salt spray
• Direct sunlight. (Avoid using outdoors)
• Corrosive gases (e.g. sulfurized gas) or liquids
• Dust or metallic particles in the air
• Physical shock, vibration
• Magnetic noise (Example: welding machines, power devices, etc.)
• High humidity
• Radioactive substances
• Combustibles: thinner, solvents, etc.
When preparing to mount the Drive, lift it by its base, never by the front cover. For effective cooling, as well as proper maintenance, the Drive must be installed on a flat, non-flammable vertical surface
(wall or panel) using recommended mounting screws. There MUST be a MINIMUM 3.9 in.
clearance above and below the Drive to allow air flow over the heat sink fins. A minimum 1.2 in.
clearance is required on each side of the Drive.
AIR
3.94 in.
(100mm)
1.2in.
30mm
1.2in.
30mm
3.94 in.
(100mm)
8
Important: To use the CIMR-V7NU25P5, 45P5, and 47P5 Drives as an open chassis, remove top and bottom covers.
AIR
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 9
Section 4
Wiring
Main and Control Circuit
Main Circuit Input /Output Wiring
• Use 600V vinyl-sheathed wire or equivalent. Wire size and type should be determined by local electrical codes.
• Avoid routing power wiring near equipment sensitive to electrical noise.
• Avoid running input and output wiring in the same conduit.
• NEVER connect AC main power to output terminals T1(U), T2(V), and T3(W).
• NEVER allow wire leads to contact metal surfaces. Short-circuit may result.
• NEVER connect power factor correction capacitors to the Drive output. Consult Yaskawa when connecting noise filters to the Drive output.
• WIRE SIZING MUST BE SUITABLE FOR CLASS I CIRCUITS.
• When connecting motor to Drive’s output terminals, include a separate ground wire. Attach ground wire solidly to motor frame and to Drive’s ground terminal .
• When using armored or shielded cable for connection between Drive and motor, solidly connect armor or shield to motor frame, and to Drive’s ground terminal .
• Motor lead length should NOT EXCEED 164 feet (50 meters), and motor wiring should be run in a separate conduit from the power wiring. If lead length must exceed this distance, reduce carrier frequency (see TM.V7N.01, paragraph 5.8) and consult factory for proper installation procedures.
• Use UL listed closed loop connectors or CSA certified ring connectors sized for the selected wire gauge. Install connectors using the correct crimp tool recommended by the connector manufacturer.
Control Circuit
• Interconnections for external two-wire control in combination with the Digital Operator are shown in
Figure 1-5.
• Interconnections for external three-wire control in combination with the Digital Operator are shown in Figure 1-6.
Note: Make wire connections according to Figure 1-5 and Table 1-2; observe the following:
• Signal Leads: Terminals S1-S4 & SC.
• Control Leads: Terminals P1, P2 & PC.
• Use twisted shielded or twisted-pair shielded wire (20-16 AWG [0.5 – 1.25mm2]) for control and signal circuit leads. The shield sheath MUST be connected at the Drive end ONLY (terminal ).
The other end should be dressed neatly and left unconnected (floating). See Figure 1-1.
• DeviceNet Leads: Black, Blue, Shield, White, Red.
• Use DeviceNet thick or thin cable specified by ODVA.
• Signal leads and feedback leads (PG) must be separated from control leads main circuit leads, and any other power cables, to prevent erroneous operation caused by electrical noise.
• Lead length should NOT EXCEED 164 feet (50 meters). Wire sizes should be determined considering the voltage drop.
• All AC relays, contactors and solenoids should have RC surge supressors installed across their coils.
• All DC relays, contactors and solenoids should have diodes installed across their coils.
TO DRIVE
SIGNAL
TERMINALS
TO SHIELD
SHEATH
TERMINAL
(TERM. )
SHIELD SHEATH
OUTER JACKET
WRAP BOTH ENDS
OF SHEATH WITH
INSULATING TAPE
CRIMP
CONNECTION
Figure 1-1. Shielded Sheath Termination
DO NOT
CONNECT
TO
EXTERNAL
CIRCUIT
9
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 10
Wiring
Grounding Section 4
• The Drive must be solidly grounded using the main circuit ground terminal .
• If Drive is installed in a cabinet with other equipment, ground leads for all equipment should be connected to a common low-impedance ground point within the cabinet.
• The supply neutral should be connected to the ground point within the cabinet.
• Select appropriate ground wire size from Table 1-1.
• Make all ground wires as short as practical.
• NEVER ground the Drive in common with welding machines, or other high power electrical equipment.
• Where several Drives are used, ground each directly to the ground point (see Figure 1-2).
DO NOT FORM A LOOP WITH THE GROUND LEADS.
• When connecting a motor to the Drive’s output terminals, include a separate ground wire.
Attach ground wire solidly to motor frame and to Drive’s ground terminal .
• When using armored or shielded cable for connection between Drive and motor, solidly connect armor or shield to motor frame, and to the Drive’s ground terminal .
10
Model
CIMR-V7NU
22P2
23P7
25P5
27P5
40P2
40P4
20P1
20P2
20P4
20P7
21P5
40P7
41P5
42P2
43P7
45P5
47P5
• • •
•
• • • • • •
CORRECT CORRECT NOT
ACCEPTABLE
Figure 1-2. Correct Ground Connection
Table 1-1. Wire and Terminal Screw Sizes
Terminal Symbol
L1(R), L2(S), L3(T)
B1, B2
T1(U), T2(V), T3(W)
-, +1,+2
L1(R), L2(S), L3(T)
B1, B2
T1(U), T2(V), T3(W)
-, +1,+2 x 1
Tightening
Screw Torque lb • in
(N • m)
Applicable size mm 2
Wire
Recommended
AWG mm 2 size Type
AWG
M3.5
M3.5
M3.5
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2 18 to
14
0.75 to 2 18 to
14
0.75 to 2 18 to
10
M3.5
M5
M5
M4
0.75 to 2 18 to
14
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
22.19
(2.5)
22.19
(2.5)
5.5 to 8 10 to 8
5.5 to 8 10 to 8
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
10.65 to 13.31 2 to 5.5 14 to
(1.2 to 1.5) 10
M4
M5
12.43
(1.4)
22.19
(2.5)
3.5 to 5.5 12 to
10
5.5 to 8
12 to
10
2
2
2
2
2
3.5
5.5
8
8
2
2
2
2
2
5.5
5.5
14
14
14
14
14
12
10
8
8
14
14
14
14
14
2 14
3.5 x 1 12 x 1
10
10
600V vinylsheathed wire or equivalent
600V vinylsheathed wire or equivalent
Note: The wire size is set for copper wires at 160°F (75°C)
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 11
Section 4
Wiring
Terminal Functions and Voltages
Table 1-1. Wire and Terminal Screw Sizes - continued
Model Terminal Symbol
Common to all models
DeviceNet
S1 to S4, P1, P2, SC, PC
DeviceNet Connector
Screw
M2
M3
Wire
Tightening
Torque lb • in (N • m)
Applicable size mm 2 AWG
1.94 to 2.21
twisted wire 0.5 to 0.75 20 to 18
(0.22 to 0.25) single
Recommended size mm 2
0.5 to 1.25 20 to 16 0.75
AWG
18
Type
Shielded wire or equivalent
4.44 to 5.33
(0.5 to 0.6) twisted wire 0.2 to 2.5
24 to 12 0.32/.2 22/24
Thin
Cable
TERMINAL
L1 (R)
L2 (S)
L3 (T)
T1 (U)
T2 (V)
T3 (W)
B1
B2
+1
+2
–
S1
S2
S3
S4
SC
P1
P2
FUNCTION
Table 1-2. Terminal Functions and Voltages
Main circuit input power supply
Main circuit output
For connection of braking resistor (option)
VOLTAGE / SIGNAL LEVEL
230V Drive: 200 / 208 / 220 / 230V at 50/60 Hz
460V Drive: 380 / 400 / 440 / 460 / 480V at 50/60 Hz
230V Drive: 0 - 200 / 208 / 220 / 230V
460V Drive: 0 - 400 / 440 / 460 / 480V
DC Reactor terminals
DC Bus terminals (+1 & –)
Ground terminal (100 ohms or less) – – – –
Multi-Function-Input 1
Multi-Function-Input 2
Multi-Function-Input 3
Multi-Function-Input 4
Sequence common for terminals S1-S4.
Multi-Function Open
Collector Output 1
Factory setting is
" Drive Running "
Factory setting is " Forward Run/Stop " (1).
(Forward run when closed, stop when open)
Factory setting is " Reverse Run/Stop " (1).
(Reverse Run when closed, stop when open)
Factory setting is " External Fault (NO contact) input " (1)
Factory setting is " Fault Reset " (1)
Common terminal for sequence inputs
Photocoupler output:
48 VDC; 50 mA or less.
Multi-Function Open
Collector Output 2
Factory setting is
" Speed Agree "
PC Multi-Function Open
Collector Output common
0 V
CN2 V
CN2 I
CN2 C
Frequency reference voltage input
Frequency reference current input
Frequency reference input common
0 to +10 / 100% (20K
4 to 20 mA (250 )
0V
)
NOTES:
1.
These inputs have factory settings based on 2-wire reset. For 3-wire reset definitions, see Figure 1-6.
Table 1-3. Terminal Functions and Signals of DeviceNet
TERMINAL
BLACK
BLUE
GREEN
WHITE
RED
V-
CAN_L
Shield
CAN_H
V+
NAME FUNCTION
DeviceNet power supply ground
DeviceNet data low
Shield wire
DeviceNet data high
DeviceNet power supply +24VDC
11
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 12
Network Connection
DeviceNet Section 5
Remove power and wait for all LEDs to go out before making DeviceNet and control terminal connections. Use standard DeviceNet thin or thick cable when connecting to DeviceNet terminals.
Remove the front cover and connect the
DeviceNet communication wires on the quick-disconnect screw terminal on the
Drive (see page 11, Cable Installation).
SW1 Baud Rate
SW4 LSD Addr.
Control wiring should be sized 16 to 20 AWG.
Control wiring should be shielded, with the shield wire connected to the ground terminal , which is located towards the left side of the aluminum heat sink.
SW3 MSD Addr.
Quick-Disconnect
DeviceNet Terminal
9
8 7
5
0
2
9
8
7
5
9
8 7
R U N
ALARM
PNP/NPN
Switch
S1 S2 S3 S4 SC
P1 P2 PC
E
Control
Terminal Block
Terminal
Color
Black
Blue
-
White
Red
Name
V-
CAN_L
Shield
CAN_H
V+
Wiring
Color
Black
Blue
Bare
White
Red
Content
Communication power supply GND
Communication data low side
Shield wire
Communication data high side
Communication power supply DC+24V
Top View
Black Blue White Red
0.2in
(5.5mm)
DeviceNet
Cable
Side View
V7N Without Front Cover
DeviceNet Thick Cable
Thick cable consists of two shielded pairs twisted on a common axis with a drain wire in the center covered with an overall braid shield and is commonly used as trunk line when length is important.
The thick cable specified for DeviceNet network connections consists of:
• One twisted signal pair (#18): blue/white
• One twisted power pair (#15): black/red
• Separate aluminized Mylar shields around power pair and signal pair
• Overall foil/braid shield with drain wire (#18): bare
DeviceNet Thin Cable
Thin Cable is smaller and more flexible than Thick Cable. It is commonly used for drop lines, but can also be used, for shorter distances, as trunk line.
The thin cable specified for DeviceNet network connections consists of:
• One twisted signal pair (#24): blue/white
• One twisted power pair (#22): black/red
• Separate aluminized Mylar shields around power pair and signal pair
• Overall foil/braid shield with drain wire (#22): bare
Cable Vendors
DeviceNet cables are available from various vendors. Two sources are listed below:
Belden Part #
3082A thick
3084A thin
3083A thick
3085A thin
Berk-Tek Part #
210051 thick
210144 thin
Pair
Data
Power
Data
Power
Data
Power
Data
Power
Belden Wire & Cable Company
AWG
18
15
Insulation
Datalene
PVC/Nylon
24
22
18
15
24
22
Datalene
PVC/Nylon
Datalene
PVC/Nylon
Datalene
PVC/Nylon
Pair
Data
Power
Data
Power
AWG
18
15
24
22
Berk-Tek
Insulation
FPE/HDPE
PVC/Nylon
FPE/HDPE
PVC/Nylon
Outer Jacket
Lt. Gray PVC
Lt. Gray PVC
Yellow CPE
Yellow CPE
Outer Jacket
Lt. Gray PVC
Lt. Gray PVC
12
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 13
Section 5
Network Connection
DeviceNet
Cable Installation
Wire the DeviceNet communication cable to the terminal block according to the following procedures:
1) Loosen terminal screws using a slotted screwdriver.
2) Insert the DeviceNet wires into corresponding terminals.
3) Fasten wires by tightening terminal screws.
4) Secure the removable terminal by tightening down the terminal block screws.
(Tightening torque: 0.22~0.25 [N • m])
Note: The shield is daisy chained between devices and should be grounded at the 24 VDC power supply as specified by the Open DeviceNet Vendor Association (ODVA).
Terminating Resistors
Terminating resistors must be mounted on the first and last node in a DeviceNet network, at both furthest ends of the cable. The value of the terminating resistor is specified by the ODVA (Open
DeviceNet Vendors Association) and is a value of 121 Ohms, 1% tolerance, and 1/4 watt.
Terminating resistors can be found in the ODVA product catalogue.
DeviceNet Trunk Line
Up to 64 Physical Devices
Baud Rate and Address Configuration
The board is equipped with one rotary switch S1 for baud rate and two rotary switches S3 and S4 for node address set-up. The rotary switches are located next to the DeviceNet connector.
MAC ID
Tens Place
S3 S4
0
1
9
2 3
4
8 7
6
RATE
S1
1
0
2
9
8
3
4
7
6
1
0
2
9
8
3
4
7
6
BAUD
RATE
MAC ID
Ones Place
MSB LSB
Baud Rate Setting Switch
The Drive’s DeviceNet baud rate can be set in several ways.
The baud rate can be set using the rotary switch RATE (S1). Setting the switch to position 0, 1, or 2 enables the rotary switch to set the Drive’s baud rate for 125kbps, 250kbps, or 500kbps, respectively.
Setting the rotary switch to 3 enables Auto Baud detection. Setting the rotary switch to values 4 ... 9 sets the baud rate to parameter n152 .
S1 Switch Setting 0 1 2 3 4-9
Baud Rate 125 kbps 250 kbps 500 kbps Auto Baud Parameter n152
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Auto Baud
13
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 14
Switch Settings and LEDs
DeviceNet Section 5
MAC ID Setting Switch
The Drive’s MAC ID can be set in two different ways.
The MAC ID can be set using the rotary switches MSD (S3) and LSD (S4).
MAC ID = (MSD x 10) + LSD
Setting range of 0 to 63 on the rotary switches enables the rotary switches to set the Drive’s MAC ID.
Setting range of 64 to 99 on the rotary switches activates parameter n150 to set the Drive’s MAC ID.
Setting the MAC ID to 63 in conjunction with ADR enabled allows for some vendor’s “Faulted Node
Recovery” and the setting of the MAC ID through DeviceNet.
S3 + S4 Switch Setting
MAC ID
0-63
MAC ID = (S3 x 10) + S4 Parameter n150
64-99
Setting Range: 0 to 63
DeviceNet Indication LEDs
The V7N Embedded DeviceNet Drive has two ODVA standard DeviceNet LED’s on the cover to indicate DeviceNet communications status.
MS LED
NS LED
MS
NS
R U N
ALARM
V7N With Front Cover
The table below describes the function of DeviceNet specific LED’s.
LED
Name
MS
NS
Color
Display
Status
Green Lit
Green
Red
Operation Status
During Drive operation
Flashing During Drive initialization
Lit Unrecoverable fault
Description
The Drive is operating normally.
Initial setting status or communication not ready.
An unrecoverable fault occurred in the Drive.
Red Flashing Recoverable fault A recoverable fault occurred, such as switch setting error.
Not lit Power OFF Power not being supplied to the Drive.
Green
Green
Red
Lit DeviceNet communication taking
Flashing DeviceNet communication not taking place
Lit
DeviceNet communicating normally.
place
DeviceNet network normal, but not communicating with the master.
A fault that makes it impossible for the DeviceNet to
Communication fault communicate occurred.
• Duplicate MAC ID
• Bus-off detection
Communication timeout with master occurred.
Red Flashing Communication timeout Data length sent by the PLC matches the data length expected by the Drive.
Not lit
DeviceNet not set to Online.
Offline, Power OFF Power not being supplied to the interface card.
Mismatch of baud rate.
Note: The LED’s will flash red once (100ms) during power up initialization. This is used in the internal testing process to verify that the red LED is working properly.
14
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 15
Section 5
Set the drive parameters to their appropriate values.
Set Drive Parameters
DeviceNet
n003 n004
8
9
6
7
0
3
4
1
2
5
Data
0
1
2
3
0
Text
Digital Operator
Terminal
Serial Communications
Option Card (DeviceNet CM013)
Digital Operator Pot
Digital Operator
Voltage Reference (0 ~ 10vdc)
Current Reference (4 ~ 20ma)
Current reference (0 ~ 20ma)
Pulse Train Reference
Serial Communications
Multi-Function Analog Input (0 ~ 10vdc)
Multi-Function Analog Input (4 ~ 20ma)
Option Card (DeviceNet CM013)
0.01Hz
n035 n148 n152
1
2-39
0.1%
Number of motor poles for RPM (set for DeviceNet)
40-3999 User scaled
DeviceNet PPA 46h (70): Basic Speed Control
(Output Instances)47h (71): Extended Speed Control
96h (150): Modbus I/O Control
97h (151): Standard Drive Control
98h (152): Acc/Dec Time Control
9Bh (155): Expanded I/O Modbus Control
9Ch (156): General Purpose DI/DO Control
DeviceNet PCA14h (20): Basic Speed Control
(Input Instsnces) 15h (21): Extended Speed Control
64h (100): Modbus I/O Control n149 65h (101): Standard Drive Control
66h (102): Acc/Dec Time Conrtrol
69h (105): Expanded I/O Modbus Control
6Ah (106): General Purpose DI/DO Control n150 0 … 63 MAC ID (valid only when rotary switches 3 and 4 are set to 64 … 99)
2
3
0
1
125kb Baud Rate (only valid when rotary switch 1 is set to 4 … 9)
250kb Baud Rate (only valid when rotary switch 1 is set to 4 … 9)
500kb Baud Rate (only valid when rotary switch 1 is set to 4 … 9)
Auto Baud (only valid when rotary switch 1 is set to 4 … 9)
15
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 16
EDS Files
DeviceNet Section 5
The EDS file can be obtained from the CD that was included with the drive or downloaded from www.Yaskawa.com. It is recommended that the EDS file be downloaded from www.Yaskawa.com to be sure that the latest version is used. Install the EDS file into the DeviceNet configuration tool (i.e.
RSNetworx for DeviceNet or DeviceNet Manager). There is a separate EDS file for each drive model. Verify that the correct EDS file has been installed for the drive model configured. Refer to the documentation that came with the DeviceNet master configuration tool for information on installing EDS files and configuring a DeviceNet node.
Note: The EDS files located on the CD or downloaded from www.Yaskawa.com will be in “zip” format and will need to be un-zipped to a temporary directory prior to installation.
Model
CIMR-V7NU
B0P2
B0P4
B0P7
B1P5
B2P2
B3P7
B4P0
40P7
41P5
42P2
43P0
43P7
44P0
45P5
47P5
B0P1
20P1
20P2
20P4
20P7
21P5
22P2
23P7
24P0
25P5
27P5
40P1
40P2
40P4
Drive Description
Drive Capacity
V7N Parameter
EDS File Names
V7NU20P1_DNET_V1_04.EDS
n210 Modbus
Register No. 1D2H
00 (00h) 3 Phase 230V, 0.13HP, 0.8A
3 Phase 230V, 0.25HP, 1.6A
V7NU20P2_DNET_V1_04.EDS
3 Phase 230V, 0.5HP, 3A V7NU20P4_DNET_V1_04.EDS
3 Phase 230V, 0.75&1HP, 5A V7NU20P7_DNET_V1_04.EDS
01 (01h)
02 (02h)
03 (03h)
3 Phase 230V, 2HP, 8A
3 Phase 230V, 3HP, 11A
3 Phase 230V, 5HP, 17.5A
3 Phase 230V, 5HP, 17.5A
3 Phase 230V, 7.5HP, 25A
V7NU21P5_DNET_V1_04.EDS
V7NU22P2_DNET_V1_04.EDS
V7NU23P7_DNET_V1_04.EDS
V7NU24P0_DNET_V1_04.EDS
V7NU25P5_DNET_V1_04.EDS
04 (04h)
05 (05h)
07 (07h)
08 (08h)
09 (09h)
3 Phase 230V, 10HP, 33A
3 Phase 460V, 0.25HP, 1.2A
3 Phase 460V, 0.5HP, 1.2A
3 Phase 460V, .75HP, 1.8A
3 Phase 460V, 1&2HP, 3.4A
3 Phase 460V, 3HP, 4.8A
3 Phase 460V, 3HP, 5.5A
3 Phase 460V, 4HP, 7.2A
3 Phase 460V, 5HP, 8.6A
V7NU27P5_DNET_V1_04.EDS
V7NU40P1_DNET_V1_04.EDS
V7NU40P2_DNET_V1_04.EDS
V7NU40P4_DNET_V1_04.EDS
V7NU40P7_DNET_V1_04.EDS
V7NU41P5_DNET_V1_04.EDS
V7NU42P2_DNET_V1_04.EDS
V7NU43P0_DNET_V1_04.EDS
V7NU43P7_DNET_V1_04.EDS
10 (0Ah)
40 (28h)
41 (29h)
42 (2Ah)
43 (2Bh)
44 (2Ch)
45 (2Dh)
46 (2Eh)
47 (2Fh)
3 Phase 460V, 5.3HP, 9.2A
V7NU44P0_DNET_V1_04.EDS
3 Phase 460V, 7.5&10HP, 14.8A V7NU45P5_DNET_V1_04.EDS
3 Phase 460V, 10HP, 18A
1 Phase 230V, 0.13HP, 0.8A
V7NU47P5_DNET_V1_04.EDS
V7NUB0P1_DNET_V1_04.EDS
1 Phase 230V, 0.25HP, 1.6A
1 Phase 230V, 0.5HP, 3A
1 Phase 230V, 1HP, 5A
V7NUB0P2_DNET_V1_04.EDS
V7NUB0P4_DNET_V1_04.EDS
V7NUB0P7_DNET_V1_04.EDS
1 Phase 230V, 2HP, 8A
1 Phase 230V, 3HP, 11A
1 Phase 230V, 5HP, 17.5A
1 Phase 230V, 5HP, 17.5A
V7NUB1P5_DNET_V1_04.EDS
V7NUB2P2_DNET_V1_04.EDS
V7NUB3P7_DNET_V1_04.EDS
V7NUB4P0_DNET_V1_04.EDS
48 (30h)
49 (31h)
50 (32h)
20 (14h)
21 (15h)
22 (16h)
23 (17h)
24 (18h)
25 (19h)
27 (1Bh)
28 (1Ch)
Product Code
Class 01
Instance 01
Attribute 03
12288 (3000h)
12289 (3001h)
12290 (3002h)
12291 (3003h)
12292 (3004h)
12293 (3005h)
12295 (3007h)
12296 (3008h)
12297 (3009h)
12298 (300Ah)
12329 (3029h)
12230 (302Ah)
12231 (302Bh)
12232(302Ch)
12233 (302Dh)
12234 (302Eh)
12235 (302Fh)
12236 (3030h)
12237 (3031h)
12238 (3032h)
12239 (3033h)
12308 (3014h)
12309 (3015h)
12310 (3016h)
12311 (3017h)
12312 (3018h)
12313 (3019h)
12315 (301Bh)
12316 (301Ch)
Note: All of the EDS files are in one zip file, so you must un-zip the file before installing in the configuration tool.
16
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 17
Section 5
Supported Input Instances
Instance
20 (14h)
Basic Speed
Control
Byte
0
1
2
3
Instance
21 (15h)
Extended
Speed Control
Supported Input Instances
Instance Byte
70 (46h)
Basic Speed
Control
1
2
3
Byte
0
1
2
3
Instance
71 (47h)
Extended
Speed Control
Byte
0
1
2
3
Bit 7
Bit 7
Supported Assemblies
DeviceNet
Bit 6
Bit 6
Net Ref
Bit 5 Bit 4 Bit 3 Bit 2
Fault Reset
Speed Reference Scaled by Parameter n035)
Bit 1
Bit 5
Net Ctrl
Bit 4 Bit 3
Speed Reference (Scaled by Parameter n035)
Bit 2
Fault Reset
Bit 1
Run REV
Bit 0
Run FWD
Bit 0
Run FWD
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
@Fault
Speed Actual (Scaled by Parameter n035)
Bit 7
@ Speed
Bit 6
@Ref from Net*
Bit 5
@Ctrl from Net*
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
@FWD @Fault
Speed Actual (Scaled by Parameter n035)
17
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 18
Supported Assemblies
DeviceNet Section 5
Yaskawa Supported Input Instances
Instance
100 (64h)
MODBUS
Message
Note:
Byte
0
1
2
3
4
Bit 7 Bit 6 Bit 5 Bit 4
Data
Bit 3
Register Number
Bit 2 Bit 1
Function Code ( Only MODBUS functions register read (03h) and register write (10h) are supported)
Refer to output assembly instance 150 (96h) for response
Bit 0
Instance
101 (65h)
Standard
Control
Note
Instance
102(66h)
Acc/Dec Time
Control
*
5
6
3
4
7
Byte
0
1
2
Bit 7
Terminal P2
Bit 6
Terminal S7
Terminal P1
Bit 5
Terminal S6
Terminal MA
Bit 4
Terminal S5
Bit 3
Terminal S4
Bit 2
Terminal S3
Bit 1
Run REV
Bit 0
Run FWD
Reset
Speed Reference (Scaled by Parameter n035)
Terminals S5, S6, S7 and MA are only available through DeviceNet
Reserved
Reserved
*
6
7
4
5
Byte
0
1
2
3
Bit 7
Terminal P2
Bit 6
Terminal S7
Terminal P1
Bit 5
Terminal S6
Bit 4
Terminal S5
Bit 3
Terminal S4
Bit 2
Terminal S3
Speed Reference (Scaled by Parameter n035)
Terminals S5, S6, S7 and MA are only available through DeviceNet
Acc Time 1
Dec Time 1
Bit 1
Run REV
Fault Reset
Bit 0
Run FWD
External Fault
Note
Instance
0105(69h)
Standard
DI/DO Control
3
4
5
6
Byte
0
1
2
7
Code 1 Code 2
Bit 7
Terminal P2
Func Code
Bit 6
Terminal S7
Terminal P1
Bit 5
Terminal S6
Terminal MA
Bit 4
Terminal S5
Bit 3
Terminal S4
Function Code 2
Bit 2
Terminal S3
Function Code 1
Speed Reference (Scaled by Parameter n035)
Bit 1
Run REV
Fault Reset
Register Address
Register Data
Description
Bit 0
Run FWD
External Fault
Note
Instance
106 (6Ah)
Standard
Control
Note
Refer to output assembly instance 155 (9Bh) for response
* Terminals S5, S6, S7 and MA are only available through DeviceNet
*
Byte
0
1
4
5
2
3
6
7
Bit 7
Terminal P2
Bit 6
Terminal S7
Terminal P1
Bit 5
Terminal S6
Terminal MA
Bit 4
Terminal S5
Bit 3
Terminal S4
Bit 2
Terminal S3
Bit 1
Run REV
Bit 0
Run FWD
External
Speed Reference (Scaled by Parameter n035)
Terminals S5, S6, S7 and MA are only available through DeviceNet
Reserved
Reserved
18
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 19
Section 5
Supported Assemblies
DeviceNet
Yaskawa Supported Output Instances
Instance
150(96h)
MODBUS
Message
Note:
Byte
0
1
2
Bit 7 Bit 6 Bit 5 Bit 4
Function Code*
Register Number
3
4
Data
Refer to Input Instance 100 (64Refer to Input Instance 100 (64h)
* A Modbus message error is returned if the function code has the MSB (bit 80h) set
Bit 3 Bit 2 Bit 1 Bit 0
Instance
151(97h)
Standard
Control
Note *
Byte
0
1
2
3
4
5
6
7
Bit 7 Bit 6
Terminal MA is only available through DeviceNet
Bit 5 Bit 4
@ @Fault Reset @REV Run
@Terminal P2 @Terminal P1 @Terminal MA @Local Mode
Output Frequency (Scaled by Parameter n035)
Reserved
Bit 3 Bit 2
Output Current (0.01A or 0.1A Based on Drive Capacity)
Bit 1 Bit 0
@ Zero Speed @FWD Run
@ UV @OPE
/Instance
152(98h)
Enhanced
Control/
MODBUS
Message
Note *
5
6
3
4
7
Byte
0
1
2
Bit 7
@Fault
Bit 6
@Alarm
Bit 5
@Ready
Bit 4
@ Speed Agree
Bit 3
@Fault Reset
Output Frequency (Scaled by Parameter n035)
Speed Reference (Scaled by Parameter n035)
Output Current
Bit 2
@REV Run
@Terminal P2 @Terminal P1 @Terminal MA @Local Mode
Terminal MA is only available through DeviceNet
Bit 1 Bit 0
@ Zero Speed @FWD Run
@ UV @OPE
Instance Byte
0
1
2
3
155(9Bh)
Standard DI/DO
Control
6
7
4
5
Code 1 Code 2
Bit 7
@Fault
Bit 6
@Alarm
Bit 5
@Ready
Bit 4
@ Speed Agree
Bit 3
@Fault Reset
Bit 2
@REV Run
@Terminal P2 @Terminal P1 @Terminal MA @Local Mode Function Bit 2 Function Bit 1
Speed Actual (Scaled by Parameter n035)
Register Address
Register Data
Description
Bit 1 Bit 0
@ Zero Speed @FWD Run
@UV @OPE
Func Code
Note
Refer to input assembly instance 105 (69h)
* Terminal MA is only available through DeviceNet
Instance
156(9Ch)
Standard DI/DO
Control
Note *
Byte
0
1
2
3
6
7
4
5
Bit 7
@Fault
Bit 6
@Alarm
Bit 5
Terminal MA is only available through DeviceNet
Bit 4
Reserved
Bit 3
Output Current
Bit 2
@Ready @ Speed Agree @Fault Reset @REV Run
@Terminal P2 @Terminal P1 @Terminal MA @Local Mode
Speed Actual Frequency (Scaled by Parameter n035)
Bit 1 Bit 0
@ Zero Speed @FWD Run
@ UV @OPE
19
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 20
Peripheral
Devices Section 6
The following peripheral devices may be required to be mounted between the AC main circuit power supply and the Drive input terminals L1 (R), L2 (S) and L3 (T).
CAUTION
Never connect a general LC/RC noise filter to the Drive output circuit.
Never connect a phase-advancing capacitor to the input/output sides or a surge suppressor to the output side of the Drive.
When a magnetic contactor is installed between the Drive and the motor, never turn it on or off during operation.
Note: For more details on peripheral devices, contact your manufacturer.
Recommended Branch Short Circuit Protection Peripheral Devices
All models have UL evaluated motor overload protection built in. Motor overload protection is also provided in accordance with the NEC and CEC. Additional branch circuit overload protection is not required.
230V 3-Phase
Model CIMR-V7NU
Capacity (kVA)
Rated output current (A)
Rated input current (A)
Max. Time Delay Fuse Rating (A) (1)
Max. Non-Time Delay Fuse Rating (A) (2)
Max. MCCB Rating (A)
20P1
0.3
0.8
1.1
1.8
3.0
15.0
20P2
0.6
1.6
1.8
3.2
5.0
15.0
20P4
1.1
3.0
3.9
6.25
10.0
15.0
20P7
1.9
5.0
6.4
10.0
20.0
15.0
21P5
3.0
8.0
11.0
17.5
30.0
20.0
22P2
4.2
11.0
15.1
20.0
45.0
30.0
23P7
6.7
17.5
24.0
25.0
45.0
40.0
25P5
9.5
25.0
33.0
45.0
70.0
50.0
460V 3-Phase
Model CIMR-V7NU
Capacity (kVA)
Rated output current (A)
Rated input current (A)
Max. Time Delay Fuse Rating (A) (1)
Max. Non-Time Delay Fuse Rating (A) (2)
Max. MCCB Rating (A)
40P2
0.9
1.2
1.6
2.8
5.0
15.0
40P4
1.4
1.8
2.4
4.0
7.0
15.0
40P7
2.6
3.4
4.7
8.0
12.0
15.0
41P5
3.7
4.8
7.0
12.0
20.0
15.0
42P2
4.2
5.5
8.1
12.0
20.0
15.0
Notes:
(1) Apply UL designated Class RK5 fuses.
(2) Apply UL designated Class CC or T non-time delay fuses.
Input fuse sizes are determined by NEC guidelines, and should not exceed the ratings shown in the table.
Fuse Ratings are based upon 250V fuses for 230V Drives, and 600V for 460V Drives
Fuse Manufacturer’s Designators: Class CC: KTK, FNQ or equivalent
Class RK5: FRN, FRS or equivalent
Class T: JJS, JJN or equivalent
43P7
7.0
9.2
12.0
20.0
35.0
20.0
45P5
11.0
14.8
19.6
35.0
60.0
30.0
47P5
14.0
18
23.8
45.0
70.0
40.0
Magnetic Contactor
Mount a surge protector on the coil. When using a magnetic contactor to start and stop the Drive, do not exceed one start per hour.
Ground Fault Interrupter
Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the current should be 200mA or more and the operating time 0.1 second or more.
AC and DC Reactor
Install a reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to improve the power factor on the power supply side.
Noise Filter
Use a noise filter exclusively for the Drive if radio noise generated from the Drive causes other control devices to malfunction.
27P5
13.0
33.0
39.6
60.0
80.0
60.0
20
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 21
Section 6
Peripheral
Devices
Auxiliary Input and Output Power Option Devices
A disconnect device (circuit breaker, contactor, disconnect switch, etc.) should NOT be used as a means of starting and stopping the Drive or motor.
A disconnect device can be installed for emergency stop purposes, but when that disconnect device is opened, there may be loss of electrical braking.
Figure 1-3 is a factory guideline for proper wiring practices and relative locations within the electrical path from the line to the load. It does not imply what devices are needed for a particular application, nor does it show what devices were shipped with a particular order. Therefore, disregard those items in the diagram which are not being used in your installation. However, it is recommended that an input or DC reactor be used with all Drive ratings when wired to a source of 600 kVA or greater.
Mount all optional power devices close to the Drive, and keep electrical connections as short as possible.
Note: DO NOT run input and output wiring in the same conduit.
CUSTOMER’S
3fl A.C. LINE
POWER
SUPPLY
L3
L2
L1
NOTES
1.
Connect Drive ground terminal or panel to earth ground. Always use low impedance paths and connections.
2.
Mount input and output RFI filters physically as close to the Drive as possible (on the same panel, if possible). Filters should have a solid connection from filter case or ground terminal to Drive panel or ground terminal
(conduit with good bare metal to bare metal connections may serve as the path). If multiple input or output RFI filters are used, they must be wired in parallel.
3.
Shield conductors with metallic conduit.
4.
Connect output conduit in a manner that allows it to act as an unbroken shield from the
Drive panel to the motor casing.
5.
RF noise filter (different from RFI filter) part no. 05P00325-0023 is a delta wye capacitor network which is wired in parallel with the
Drive input terminals. On the smaller Drives with die cast chassis, it must be mounted externally. On the larger Drives with sheet metal chassis, it may be mounted inside the area where the input power wiring enters the
Drive. On units equipped with bypass, it may be wired to the primary side of the circuit breaker and mounted to the bypass panel or sidewall.
6.
Connection points:
Input
Output
Drive w/o Bypass Drive w/ Bypass
L1, L2, L3
T1, T2, T3
Ckt Brkr L1, L2, L3
Unwired side of
Overload relay
ISOLATION
TRANSFORMER
H3 X3
H2 X2
H1 X1
INPUT
RFI FILTER
C1(L3)
L
B1(L2)
I
N
A1(L1)
E
L
(L3)C2
O
(L2)B2
A
D
(L1)A2
(G)
RF NOISE
FILTER
EARTH GROUND
SEE NOTE 2
INPUT
REACTOR
C1 C2
B1 B2
A1 A2
SEE NOTE 5
EARTH GROUND
SEE NOTE 2
EARTH GROUND
SEE NOTE 1
OUTPUT
RFI FILTER
OUTPUT
REACTOR
SEE NOTE 3
L1 L2 L3 L11 L21 L31
INPUT
AC DRIVE
+ 1
SEE NOTE 6
+ 2
OUTPUT
T1 T2 T3
1
4
IN
2
OUT
5
3
SEE NOTES 3, 4
TO CASE
6
EARTH
GROUND
SEE NOTE 2
A1 B1 C1
SEE NOTES 3, 4
A2 B2 C2
T1 T2 T3
DC
REACTOR
SEE NOTES 3, 4
A.C. MOTOR
Figure 1-3. Customer Connection Diagram For Isolation Transformers, Input Reactors,
Input RFI Filters, DC Reactors, Output Reactors and Output RFI Filters
21
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 22
Conformance to
European EMC Directive Section 7
In order to conform to EMC standards, the following methods are required for line filter application, cable shielding and Drive installation.
The line filter and Drive must be mounted on the same metal plate. The filter should be mounted as close to the Drive as practical. The cable must be kept as short as possible and the metal plate should be securely grounded. The ground of the line filter and the Drive must be bonded to the metal plate with as much bare-metal contact as possible.
For main circuit input cables, a screened cable is recommended within the panel and is also suggested for external connections. The screen of the cable should be connected to a solid ground.
For the motor cables, a screened cable (max. 20 m) must be used and the screen of the motor cable should be connected to ground at both ends by a short connection, again using as much baremetal contact as practical.
For a more detailed explanation, refer to the manufacturer document EZZ006543, “Installation
Guidelines For EMC Directive using AC Drive Products.”
Table 1-4 and Figure 1-4 show the line filter list for EMC standards and the installation/wiring of the
Drive and line filter.
Model
CIMR-V7NU
20P1
20P2
20P4
20P7
21P5
22P2
23P7
25P5
27P5
40P2
40P4
40P7
41P5
42P2
43P7
45P5
47P5
Table 1-4. Line Filters for EMC Standards
Part Number
FIL00
Line Filter
Rated Weight
Current (A) lbs. (kg)
Dimensions in in. (mm)
H x W x D (1)
1083
1084
1085
1100
1086
1087
10
16
26
50
5
10
1.8 (0.8) 7.6 x 3.2 x 2.0 (194 x 82 x 50)
2.2 (1.0) 6.7 x 4.4 x 2.0 (169 x 111 x 50) 6.1 x 3.6 (156 x 91) M5
2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120) M5
5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150) M6
2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)
2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)
Mounting Dim. in in. (mm)
H1 x W1
7.1 x 2.4 (181 x 62)
6.1 x 3.6 (156 x 91)
6.1 x 3.6 (156 x 91)
Screw
Size
M5
M5
M5
1088
1101
15
30
2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120)
5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)
(1) D is the distance the filter will extend outward from the surface of the metal plate.
M5
M6
4-d L1 L2 L3 PE
Ground Bands (remove any paint)
D
H1 H
MAINS
FILTER
LOAD
Cable Length max. 40cm
Metal Plate
V7N
DRIVE
L1 L2 L3 L1 L2 L3
Ground Bands (remove any paint)
W1
W
Figure 1-4. Installation of Line Filter and V7N Drive
IM
3~
Motor Cable max. 20m
22
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 23
Section 8
Interconnection Precautions and Diagrams
Notes for Figure 1-5 (2-Wire Control) and Figure 1-6 (3-Wire Control)
Q
– Indicates components not supplied.
– Main circuit terminal.
– Indicates control circuit terminal.
( ) – Indicates alternate terminal marking, i.e., (R) and L1.
s
– Function labels shown for these terminals are determined by factory settings of n050 through n056 . (see TM.V7N.01) l
– Function labels shown for these terminals are determined by factory settings of n057 through n059 .
(see TM.V7N.01)
1.
Insulated twisted shielded wire is required.
2-conductor #18 GA. (Belden #8760 or equivalent).
3-conductor #18 GA. (Belden #8770 of equivalent).
Connect shield ONLY AT the Drive END (ground terminal ). Stub and isolate other end.
2.
The Drive’s Electronic Thermal Overload function ( n036 , n037 ) meets standards set by UL and CUL for motor thermal overload protection. If local code requires a separate mechanical overload protection, an overload relay should be installed, interlocked with the Drive as shown. It should be the manual reset type to prevent automatic restart following a motor fault and subsequent contact reclosure after cool down.
3.
Customer to connect terminal to earth ground.
4.
For installation of Braking Resistor or Braking Resistor unit, refer to Appendix 6, “Dynamic Braking Option.”
See TM.V7N.01.
5.
An optional DC reactor may be added for harmonic attenuation, if needed. See separate instruction sheet for wiring.
6.
If application does not allow reverse operation, parameter n006 , Reverse Run Prohibit Selection, should be set to
“ 1 ” (Reverse Run Disabled), and the Reverse Run/Stop input can be eliminated.
7.
Terminals S5-S7, MA and MC are not physical terminals, but they are multi-function inputs and outputs that are controlled via DeviceNet communications.
WARNING
8.
Input fuses are required for proper branch short circuit protection for all Drives. Failure to use recommended fuses (see page 16) may result in damage to the Drive and/or personal injury.
CAUTION
The Drive leaves the factory with parameters initialized for 2-Wire control (when using external Run/Stop signals). Before using the initialization function of constant n001 , know your control wiring configuration:
10 = Factory 2-Wire Control Initialization (Maintained RUN Contact)
11 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)
Entering either Initialization code resets all parameters to factory settings, and automatically returns parameter n001 setting to “ 1 ”. If the Drive is connected for 3-Wire control and this parameter is set to “ 10 ” (2-Wire
Control Initialization), the motor may run in reverse direction WITHOUT A RUN COMMAND APPLIED.
Equipment damage or personal injury may result.
Parameter n012 must be set to proper motor voltage.
Always ground the Drive using the ground terminal provided.
Never connect main circuit output terminals T1 (U), T2 (V) & T3 (W) to AC main circuit power supply.
When programmed for auto-restart ( n082 = “ 1 ” thru “ 10 ”), the motor may restart unexpectedly — personal injury may result
For Enclosed wall-mounted type (NEMA type 1)
When mounting units in an enclosure, remove the top, bottom and terminal covers. Install a cooling fan or some other means to maintain the air entering the enclosure below 113°F (45°C).
23
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 24
Interconnection Diagram
2-Wire Control Section 8
FOR DC REACTOR
(See Note 5)
3-PHASE
POWER SUPPLY
(Use L1 (R) and
L2 (S) for single-phase input)
(Note that drive must be derated by 50% on 3-Phase Models)
L1
L2
L3
MCCB
*
1-3 FU
*
(See Note 8)
*
1OL
(See
Note 3)
FORWARD
RUN/STOP
REVERSE
RUN/STOP
(See Note 6)
EXTERNAL
FAULT
FAULT
RESET
MULTI-STEP
SPEED REF 1
MULTI-STEP
SPEED REF 2
JOG REFERENCE
+1 +2
L1 ( R )
L2 ( S )
L3 ( T )
–
S1
(See Note 5)
S2
V7N
S3
S4
MULTI-FUNCTION
CONTACT INPUT
S5
S6
S7
SC
MULTI-FUNCTION
DEVICENET INPUT
(See Note 7)
LOGIC
COMMON
TERMINAL
(See Note 1)
FOR DYNAMIC BRAKING
(See Note 4)
B1 B2
T1 ( U )
T2 ( V )
T3 ( W )
MA
MC
*
1OL (See Note 2)
FAULT
AC
MOTOR
(See Note 3)
*
MULTI-FUNCTION
DEVICENET OUTPUT
(See Note 7)
P1
PC
RUNNING
MULTI-FUNCTION
PHOTOCOUPLER
OUTPUT
48V, 50mA OR LESS
SHIELD
CONNECTION
BLACK V-
BLUE CAN_L
GREEN SHIELD
DEVICENET
TERMINALS
WHITE CAN_H
RED V+
BAUD RATE
1
2
0
9
8
3
4
7
5
6
1
2
0
9
8
3
4
7
5
6
1
2
0
9
8
3
4
7
5
6
SW1
FREQUENCY
SETTING
POT
MIN
PNP
NPN
MSD LSD
ADDRESS
MAX
CN2 V
I
C
P2
SPEED
COINCIDENCE
0 ~ 10V
4 ~ 20 mA
Common
MULTI-FUNCTION
ANALOG INPUT
Figure 1-5. Standard Connections (2-Wire Control)
(Parameter n001 set to “10”)
FIG. 1-9
CAUTION
• After wiring is complete, verify that all wiring is correctly installed, excess screws and wire clippings are removed from inside of unit, screws are securely tightened, and exposed wire does not contact other wiring or terminals.
• The Drive leaves the factory with all parameters set for 2-wire external control/ reference control. To use the Drive in a 3-wire application, Drive parameters n001, n003 and n004 must be reprogrammed and Figure 1-6 used for all external connections.
• If a FWD or REV run command is given from the control circuit terminal when the operation method selection function ( n003 ) is set to “ 1 ” and the “LO/RE” selection is set to “RE”, the motor will start automatically as soon as power is applied to the main circuit.
24
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 25
Section 8
Interconnection Diagram
3-Wire Control
FOR DC REACTOR
(See Note 5)
FOR DYNAMIC BRAKING
(See Note 4)
3-PHASE
POWER SUPPLY
(Use L1 (R) and
L2 (S) for single-phase input)
(Note that drive must be derated by 50% on 3-Phase Models)
L1
L2
L3
RUN
STOP
MCCB
*
1-3 FU
(See Note 8)
+1 +2
L1 ( R )
L2 ( S )
L3 ( T )
–
(See Note 6)
*
1OL
(See
Note 3)
REVERSE
FAULT
RESET
MULTI-STEP
SPEED REF 1
MULTI-STEP
SPEED REF 2
JOG REFERENCE
(See Note 1)
B1 B2
T1 ( U )
T2 ( V )
T3 ( W )
*
1OL (See Note 2)
V7N AC
MOTOR
*
(See Note 3)
S1
(See Note 5)
S2
S3
S4
MULTI-FUNCTION
CONTACT INPUT
S5
S6
S7
SC
MULTI-FUNCTION
DEVICENET INPUT
(See Note 7)
LOGIC
COMMON
TERMINAL
SHIELD
CONNECTION
BLACK V-
BLUE CAN_L
GREEN SHIELD
DEVICENET
TERMINALS
WHITE CAN_H
RED V+
BAUD RATE
1
0
9
2 3
8 7
4
5
6
1
0
9
2 3
8 7
4
5
6
1
0
9
2 3
8 7
4
5
6
SW1
FREQUENCY
SETTING
POT
MIN
PNP
NPN
MSD LSD
ADDRESS
MAX
CN2 V
I
C
MA
MC
P2
FAULT
P1
PC
RUNNING
MULTI-FUNCTION
PHOTOCOUPLER
OUTPUT
48V, 50mA OR LESS
SPEED
COINCIDENCE
0 ~ 10V
4 ~ 20 mA
Common
MULTI-FUNCTION
DEVICENET OUTPUT
(See Note 7)
MULTI-FUNCTION
ANALOG INPUT
Figure 1-6. Standard Connections (3-Wire Control)
(Parameter n001 set to “11”)
FIG. 1-10
CAUTION
• After wiring is complete, verify that all wiring is correctly installed, excess screws and wire clippings are removed from inside of unit, screws are securely tightened, and exposed wire does not contact other wiring or terminals.
• The Drive leaves the factory with all parameters set for 2-wire external control/ reference control. To use the Drive in a 3-wire application, Drive parameters n001, n003 and n004 must be reprogrammed and Figure 1-6 used for all external connections.
• If a FWD or REV run command is given from the control circuit terminal when the operation method selection function ( n003 ) is set to “ 1 ” and the “LO/RE” selection is set to “RE”, the motor will start automatically as soon as power is applied to the main circuit.
25
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 26
Drive Parameter Listing
(n001-n017) Section 9
The Drive control circuits use various parameters to select functions and characteristics of the Drive.
Changing of parameter settings must be done in the Program mode, or by use of the Function
LEDs, if available (see TM.V7N.01, Section 4).
Drive Parameters
PARA-
METER
ADDR
CLASS 100
INST. 01 n001 n002 n003 n004 n005 n006 n007 n008 n009 n010 n011 n012 n013 n014 n015 10Fh n016 110h n017
101h
102h
103h
104h
105h
106h
107h
108h
109h
10Ah
10Bh
10Ch
10Dh
10Eh
111h
01h
02h
03h
04h
05h
06h
07h
08h
09h
0Ah
0Bh
0Ch
0Dh
0Eh
0Fh
10h
11h
Parameter Selection /
Initialization
Control Method Selection
Operation Method Selection
Reference Selection
Stop Method
Reverse Prohibit
STOP
NAME
Key Function
Reference Selection -
Digital Operator
0
1
0
Frequency Reference Setting
Method From Digital Operator 1
Operation Selection
When Digital Operator is
Disconnected
Frequency - Max.
Voltage - Max.
Frequency - Max.
Voltage Point
Frequency - Midpoint
Voltage - Midpoint
Frequency - Min.
Voltage - Min.
DATA
0
6
7
4
5
8
9
2
3
0
1
0
1
0
1
0
2
3
0
1
0
1
9
10
11
6
7
8
3
4
1
2
5
1
0
1
-
-
-
-
-
-
-
SETTING RANGE
(AND UNITS)
0: n001 can be read and set; n002 - n179 read only
1: n001 - n039 can be read and set
2: n001 - n079 can be read and set
3: n001 - n119 can be read and set
4: n001 - n179 can be read and set
5: n001 - n179 can be read and set
RUN command accepted during Program mode
6: Clear Fault History Only
7: Not Used
8: 2-wire Initialization (Japan Spec.)
9: 3-wire Initialization (Japan Spec.)
10:2 wire initialization (USA Spec)
11:3 wire initialization (USA Spec.)
0: V/f Control
1: Open Loop Vector
0: Digital Operator
1: Terminal
2: Not Used
3: DeviceNet
0: Digital Operator Pot
1: Frequency Reference 1 (n024)
2: Not Used
3: Not Used
4: Not Used
5: Not Used
6: Not Used
7: Multi-Function Analog Input (0 to 10V) (CN2)
8: Multi-Function Analog Input (4 to 20 mA) (CN2)
9: DeviceNet
0: Ramp to stop
1: Coast to stop
0: Reverse Run enabled
1: Reverse Run disabled
0: STOP key is effective regardless of programming of n003
1: STOP key is effective only when sequence command (per n003) is from Digital Operator
0: Frequency Reference from digital operator pot
1: Frequency Reference from n024
0: ENTER key must be pressed to write-in new value
1: ENTER key does not have to be pressed to write-in new value
0: Disabled (operation continues)
1: Enabled (motor coasts to a stop and fault is displayed)
50.0 to 400.0
0.1 to 255.0 (230V Drive)
0.2 to 510.0 (460V Drive)
0.2 to 400.0
SETTING FACTORY
INCREMENT SETTING
1
1
1
1
1
1
1
1
1
1
0.1 (Hz)
0.1 (V)
1
0
3
9
0
0
0
0
0
0
60.0
230.0
460.0
0.1 (Hz)
0.1 (Hz)
60.0
(Note 2) 0.1 to 399.9
0.1 to 255.0 (230V Drive)
0.2 to 510.0 (460V Drive)
0.1 to 10.0
0.1 to 50.0 (230V Drive)
0.2 to 100.0 (460V Drive)
0.1 (V)
0.1 (Hz)
0.1 (V)
(Note 2)
(Note 2)
(Note 2)
26
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 27
Section 9
Drive Parameter Listing
(n018-n052)
Drive Parameters - Continued
PARA- ADDR CLASS 100
METER INST. 01 n018 n019 n020 n021 n022
112h
113h
114h
115h
116h
NAME DATA
12h
Accel/Decel Time
Setting Unit
13h Acceleration Time 1 (Note 4)
14h Deceleration Time 1 (Note 4) -
0
1
15h
16h
Acceleration Time 2 (Note 4)
Deceleration Time 2 (Note 4) n023 117h 17h S-curve Selection
2
3
0
1 n024 118h n025 119h n026 11Ah n027 11Bh n028 11Ch n029 11Dh n030 11Eh n031 11Fh n032 120h n033 n034
121h
122h
18h
19h
1Ah
1Bh
1Ch
1Dh
1Eh
1Fh
20h
21h
22h
Freq. Reference 1 (Note 4)
Freq. Reference 2 (Note 4)
Freq. Reference 3 (Note 4)
Freq. Reference 4 (Note 4)
Freq. Reference 5 (Note 4)
Freq. Reference 6 (Note 4)
Freq. Reference 7 (Note 4)
Freq. Reference 8 (Note 4)
Jog Freq. Reference (Note 4)
Frequency Reference Upper
Limit
Frequency Reference Lower
Limit
-
-
-
0:
1:
SETTING RANGE
(AND UNITS)
0.1
0.01
0.00 to 600.0
or
0:
1:
2:
3:
0.0 to 6000
(Dependent on n018 setting)
No S-curve
0.2 second
0.5 second
1.0 second
0.00 to 400.00
0. to 110
0. to 110 n035 123h 23h
Digital Operator
Display Mode
0: 0.01 Hz (less than 100 Hz) / 0.1 Hz
1: 0.1%
2 - 39: rpm
40 - 3999: custom n036 124h n037 125h n038 126h n039 127h n040 128h n041 129h n042 12Ah n043 12Bh n044 12Ch n050 132h n051 133h n052 134h
24h
25h
26h
27h
28h
29h
2Ah
2Bh
2Ch
32h
33h
34h
Motor Rated Current
Electronic Thermal Overload
Protection (for OL1 fault)
Electronic Thermal Overload
Protection Time Constant
-
-
0
0
1
2
Cooling Fan Operation
Selection
1
0
1
Motor Rotation
Acceleration Time 3
(Note 4)
Deceleration Time 3
(Note 4)
Acceleration Time 4
(Note 4)
Deceleration Time 4
(Note 4)
-
0
Multi-function Input
Selection 1 (Terminal S1)
Multi-function Input
Selection 2 (Terminal S2)
Multi-function Input
Selection 3 (Terminal S3)
7
8
5
6
3
4
1
2
0.1 to 49.5 Amps
(Up to 150% of Drive rated current)
0: Short term rating
1: Standard rating
2: Disabled
1 to 60
0: Operates only when Drive is running
(continues operation for 1 minute after
Drive is stopped)
1: Operates with power applied to Drive
0: Rotate C.C.W.
1: Rotate C.W. (or opposite direction)
0.00 to 600.00
or
0.0 to 6000.0
(Dependent on n018 setting)
0: Fwd / Rev command (3 wire control)
[can only be set in n052]
1: Forward run (2 wire control)
2: Reverse run (2 wire control)
3: External Fault (N.O.)
4: External Fault (N.C.)
5: Fault Reset
6: Multi-step speed ref. cmd. A
7: Multi-step speed ref. cmd. B
8: Multi-step speed ref. cmd. C
SETTING FACTORY
INCREMENT SETTING
1 (sec) 0
0.01 (sec) or
0.1 (sec)
10.0
1 0
0.01 (Hz)
(< 100 Hz) or
0.1 (Hz)
(>= 100 Hz)
1(%)
1(%)
6.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
6.00
100
0
1
0.1 (A) (Note 1)
1
1 (min)
0
8
1
1
0.01 (sec) or
0.1 (sec)
10.0
1
1
1
0
0
0
1
(1)
2
(2)
3
(0)
27
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 28
Drive Parameter Listing
(n053-n069) Section 9
Drive Parameters - Continued
PARA- ADDR CLASS 100
METER INST. 01 n053 n054 n055 n056 n057 n058 n059 n064 n068 n069
135h
136h
137h
138h
139h
13Ah
13Bh
140h
144h
145h
NAME DATA SETTING RANGE
(AND UNITS)
35h
36h
37h
38h
39h
3Ah
3Bh
40h
44h
45h
Multi-function Input Selection 4
(Terminal S4)
Multi-function Input Selection 5
(DeviceNet Input S5)
Multi-function Input Selection 6
(DeviceNet Input S6)
Multi-function Input Selection 7
(DeviceNet Input S7)
9 9: Multi-step speed ref. cmd. D
Ah 10: JOG Selection
Bh 11: Accel/Decel time change cmd.
Ch 12: External Base Block (N.O.)
Dh 13: External Base Block (N.C.)
Eh 14: Speed search from max. freq.
Fh 15: Speed search from set freq.
10h 16: Accel/Decel hold command
11h 17: Remote/Local selection
12h 18: Communication / control circuit terminal selection
13h 19: Fast Stop - Fault (N.O.)
14h 20: Fast Stop - Alarm (N.O.)
15h 21: Fast Stop - Fault (N.C.)
16h 22: Fast Stop - Alarm (N.C.)
17h 23: PID control off
18h 24: I value reset (PID)
19h 25: I value hold (PID)
1Ah 26: Over Heat Pre-alarm OH3
1Bh 27: Accel/Decel Time Select 2
1Ch 28: Data input from DeviceNet communications
22 34: Up/Down Function
Multi-Function Output
Selection 1 (DeviceNet
Output MA)
Multi-Function Output
Selection 2
(Terminals P1 & PC)
Multi-Function Output
Selection 3
(Terminals P2 & PC)
Frequency Reference Loss
Detection
Analog Frequency Reference
Gain (CN2, Voltage Ref Input)
Analog Frequency Reference
Bias (CN2, Voltage Ref Input)
7
8
5
6
9
3
4
0
1
2
0: Fault
1: During running
2: Speed Agree
3: Zero Speed
4: Frequency detection 1
5: Frequency detection 2
6: Overtorque detection (N.O.)
7: Overtorque detection (N.C.)
8: Undertorque Detection (N.O.)
9: Undertorque Detection (N.C.)
Ah 10: Minor Fault
Bh 11: During Base Block
Ch 12: Local / Remote
Dh 13: Ready
Eh 14: During auto restart
Fh 15: During undervoltage
10h 16: During reverse run
11h 17: During speed search
12h 18: Comm. Controlled
13h 19: PID feedback loss
14h 20: Frequency Reference Loss Detect (N.O.)
15h 21: Overheat Pre-alarm OH3 (N.O.)
0
1
0: No Detection
1: Continue to run at 80% of max. frequency
-
-
-255 to 255
-100 to 100
SETTING FACTORY
INCREMENT SETTING
1
1
1
1
1
1
1
1
1%
1%
5
(5)
6
(6)
7
(7)
10
(10)
0
1
2
0
100
0
28
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 29
Section 9
Drive Parameter Listing
(n070-n095)
Drive Parameters - Continued
PARA- ADDR CLASS 100
METER INST. 01 n070 n071 n072 n073
146h
147h
148h
149h
46h
47h
48h
49h
NAME
Analog Frequency Reference
Filter Time Constant
(CN2, Voltage Ref Input)
Analog Frequency Reference
Gain (CN2, Current Ref Input)
Analog Frequency Reference
Bias (CN2, Current Ref Input)
Analog Frequency Reference
Filter Time Constant
(CN2, Current Ref Input)
DATA
-
-
-
n077 n078 n079 n080
14Dh
14Eh
14Fh
150h
4Dh
4Eh
4Fh
50h
Multi-Function Analog
Input CN2 Selection
Multi-Function Analog Input
Signal Selection
Multi-Function Digital Input
Scan Rate Selection
Carrier Frequency
0
1
0
1
0
1
2
3
4
n081 151h 51h
Momentary Power Loss
Ride-through Method
0
1
2
SETTING RANGE
(AND UNITS)
0.00 to 2.00
-255 to 255
-100 to 100
0.00 to 2.00
0: Multi-Function analog input disabled
1: Aux. Frequency reference
2: Frequency gain
3: Frequency bias
4: Voltage bias
0: 0 - 10V
1: 4 - 20 mA
0: Scans twice with 8 msec scan rate
1: Scans twice with 2 msec scan rate
1 to 4 (x 2.5 kHz)
7 to 9 (synchronous)
0: Not Provided
1: Continuous operation after power recovery within 2 sec.
2: Continuous operation after power recovery within control logic time
(no fault output) n082 n083
152h
153h
52h
53h
Number of auto restarts attempts
Prohibit Frequency 1
-
-
0 to 10
0.00 to 400.0
n084 154h 54h Prohibit Frequency 2 n085 155h 55h n086 156h 56h n087 157h 57h n088 158h 58h n089 159h 59h n090 15Ah 5Ah n091 15Bh 5Bh n092 15Ch 5Ch n093 15Dh 5Dh n094 n095
15Eh
15Fh
5Eh
5Fh
Prohibit Frequency 3 -
Prohibit Frequency Deadband -
Elapsed Time Function
Selection (5)
0
1
Elapsed Operation Time
(Initial Value) (5)
DC Injection Current
DC Injection Time at stop
DC Injection Time at start
Stall Prevention During
Deceleration
Stall Prevention During
Acceleration
Stall Prevention Level During
Running
Frequency Detection Level
-
-
-
-
-
0
1
-
-
0.00 to 400.0
0.00 to 400.0
0.00 to 25.50
0: Time elapses when power is On
1: Time elapses when Drive is running
0 to 9999 hours
0 to 100
0.0 to 25.5
0.0 to 25.5
0: Enabled
1: Disabled
30 to 200
30 to 200
0.00 to 400.0
SETTING FACTORY
INCREMENT SETTING
0.01 s 0.10
1%
1%
100
0
0.01 s 0.10
1
1
1
1
1
0
1
0.01 (Hz) or 0.1 (Hz)
0.01 (Hz) or 0.1 (Hz)
0.01 (Hz) or 0.1 (Hz)
0.01 (Hz)
0
0
1 (%)
0.1 (sec)
0.1 (sec)
1
1 (%)
1 (%)
0.01 (Hz) or 0.1 (Hz)
50
0.0
0.0
0
170
160
0.00
0
0.00
0.00
0.00
0.00
0
0
3
0
29
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 30
Drive Parameter Listing
(n096-n127) Section 9
Drive Parameters - Continued
PARA- ADDR CLASS 100
METER INST. 01 n096 n097 n098 n099 n100 n101 n102 n103 n104 n105 n106 n107 n108 n109 n110 n111
160h
161h
162h
163h
164h
165h
166h
167h
168h
169h
16Ah
16Bh
16Ch
16Dh
16Eh
16Fh
60h
61h
62h
63h
64h
65h
66h
67h
68h
69h
6Ah
6Bh
6Ch
6Dh
6Eh
6Fh
NAME
Overtorque Detection (OL3)
DATA SETTING RANGE
(AND UNITS)
0 0: Detection Disabled
1 1: Detect only at set frequency; operation continues
2 2: Detect only at set frequency; coast to stop
3 3: Detect during all frequency conditions; operation continues
4 4: Detect during all frequency conditions; coast to stop
Overtorque Detection
Selection (OL3)
(Note 5)
Overtorque Detection
Level (OL3)
Overtorque Detection
Delay Time (OL3)
Up/Down Hold
Memory
Speed Search
Deceleration Time
Speed Search Operation
Level
Torque Compensation Gain
(Note 4)
Torque Compensation
Time Constant
Torque Compensation
Iron Loss
Motor Rated Slip (Note 4)
Motor Line-to-line
Resistance
Motor Leakage
Inductance (Note 1)
Torque Compensation
Limit (Note 1)
0
1
-
-
0
1
-
-
-
-
-
-
-
-
-
0:
1:
30 to 200
0.1 to 10.0
0:
1:
Detected by output torque
Detected by output current
Disabled
Enabled
0.0 to 10.0
0 to 200%
0.0 to 2.5
0.0 to 25.5
0.0 to 6550
0.0 to 20.0
0.000 to 65.50
0.00 to 655.0
0 to 250
Motor No-load Current 0 to 99
Slip Compensation Gain (Note 4) 0.0 to 2.5
n112 n113 n115 n116 n117 n118 n119 n120 n121 n122 n123 n124 n125 n126 n127
170h
171h
173h
174h
175h
176h
177h
178h
179h
17Ah
17Bh
17Ch
17Dh
17Eh
17Fh
70h
71h
73h
74h
75h
76h
77h
78h
79h
7Ah
7Bh
7Ch
7Dh
7Eh
7Fh
Slip Compensation Primary
Delay Time
0.0 to 25.5
Slip Compensation Selection 0 0: Disabled
During Regeneration (Note 1) 1 1: Enabled
Stall Prevention Above Base
Speed During Run
0 0: Disabled
(level is based on setting of n094 )
1 1: Enabled
(level at Fmax is n094 x 0.4)
Stall Prevention During Run,
Accel/Decel Time Select
Undertorque Detection
Select (UL3)
Undertorque Detection
Level (detection by torque);
0 0: Follows acc/dec #1 ( n019, n020 ) or acc/dec #2 ( n021, n022 )
Note: Multi-Function input selectable
1 1: Follows acc/dec #2 ( n021, n022 ) always
0 0: Undertorque detection disabled
1 1: Detected during constant speed running.
Operation continues after detection
2 2: Detected during constant speed running.
Operation stops during detection
3 3: Detected during all frequency conditions.
Operation continues
4 4: Detected during all frequency conditions.
coast to stop
-
0 to 200%
Inverter rated current = 100%; if n097 = 0 motor rated torque becomes 100%
Undertorque Detection
Time
Frequency Reference 9 (Note 4)
Frequency Reference 10 (Note 4)
Frequency Reference 11 (Note 4)
Frequency Reference 12 (Note 4)
Frequency Reference 13 (Note 4)
Frequency Reference 14 (Note 4)
Frequency Reference 15 (Note 4)
Frequency Reference 16 (Note 4)
-
-
0.1 to 10.0
0.00 to 400.00
SETTING FACTORY
INCREMENT SETTING
1
1
1
1
1(%)
0.1 (sec)
0
0
0
0
10
0.1
0.01 (Hz)
(< 100 Hz) or
0.1 (Hz)
(>= 100 Hz)
0.00
1 0
1 (%)
0.1 (sec)
1
0.1 (sec)
1 (%)
0.1
1.0
0.1 (sec) (Note 2)
0.1 (W) or
1 (W)
0.1 (Hz)
(Note 1)
(Note 1)
0.001 (ohm)
(Note 1)
0.01 (mH) or 0.1 (mH)
(Note 1)
1 (%) 150
1 (%)
0.1
(Note 1)
(Note 2)
0.1 (sec) (Note 2)
1 0
160
0.1
0
2
150
30
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 31
Section 9
Drive Parameter Listing
(n128-n157)
Drive Parameters - Continued
PARA- ADDR CLASS 100
METER INST. 01 n128 n129 n130 n131 n132 n133 n134 n135 n136 n137 n138 n139 n140 n141 n142 n143 n144 n145 n146 n148 n149 n150 n151 n152 n153 n154 n155 n156
180h
181h
182h
183h
184h
185h
186h
187h
188h
189h
18Ah
18Bh
18Ch
18Dh
18Eh
18Fh
190h
191h
192h
194h
195h
196h
197h
198h
199h
19Ah
19Bh
19Ch
D3h
D4h
82h
83h
84h
85h
86h
87h
88h
89h
8Ah
8Bh
8Ch
8Dh
8Eh
8Fh
90h
91h
92h
94h
95h
96h
97h
98h
99h
9Ah
9Bh
9Ch
NAME
PID Control Selection
DATA SETTING RANGE
(AND UNITS)
0 0: PID control disabled
1 1: D = Feed Forward
2 2: D = Feedback
3 3: Reference + PID (D = Feed Forward)
4 4: Reference + PID (D = Feedback)
5 5: Inverse PID - D = Feed Forward
6 6: Inverse PID - D = Feedback
7 7: Inverse PID - Reference + PID
(D = Feed Forward)
8 8: Inverse PID - Reference + PID
(D = Feedback)
PID Feedback Gain (Note 4) 0.00 to 10.00
PID Proportional Gain (Note 4) 0.00 to 25.00
PID Integral Time (Note 4)
PID Derivative Time (Note 4)
-
-
0.00 to 360.00
0.00 to 2.50
PID Offset Adjustment (Note 4) -100 to 100
Integral Value Limit (Note 4) -100 to 100
PID Output Lag Filter Time (Note 4) 0.0 to 10.0
Feedback Loss
Detection Selection
0 0: Disabled
1 1: Enabled - Alarm (operation continues)
2 2: Enabled Fault (coast to stop)
Feedback Loss Detection Level 0 to 100
Feedback Loss Detection Time 0.0 to 25.5
Energy Saving Selection
(Note 5)
(Energy Saving)
0: Energy saving disabled
0 1: Energy saving enabled
1 Note: Energy saving becomes enabled by
V/f control mode
Energy Saving Gain
K2 (Energy Saving)
Energy Saving Voltage Lower
Limit at 60 Hz (Energy Saving)
Energy Saving Voltage Lower
Limit at 6 Hz (Energy Saving)
Time of Average kW
(Energy Saving)
-
-
-
-
0.00 to 6550
0 to 120
0 to 25
1 to 200
Voltage Limit of Tuning
(Energy Saving)
Step Voltage of Tuning to
100% Output Voltage
(Energy Saving)
Step Voltage of Tuning to
5% Output Voltage
(Energy Saving)
-
-
-
1 to 100
0.1 to 10.0
0.1 to 10.0
DeviceNet I/O Polled
Producing Attribute
DeviceNet I/O Polled
Consuming Attribute
DeviceNet MAC ID
DeviceNet Timeover Detection
Selection
DeviceNet Baud Rate
Selection
DeviceNet Speed Scale
DeviceNet Current Scale
DeviceNet Electric Power
Scale
46h 70: Basic Speed Control Output Instance
47h 71: Extended Speed Control Output Instance
96h 150: V7N Modbus I/O Control Output Instance
97h 151: V7N Standard Drive Control Output
Instance
98h 152: V7N Accel/Decel Time Control Output
Instance
9Bh 155: Expanded I/O Modbus Output Instance
9Ch 156: V7N General Purpose DI/DO Output Instance
14h 20: Basic Speed Control Input Instance
15h 21: Extended Speed Control Input Instance
64h 100: V7N Modbus I/O Control Input
Instance
65h 101: V7N Standard Drive Control Input
Instance
66h 102: V7N Accel/Decel Time Control Input
Instance
69h 105: Expanded I/O Modbus Input Instance
6Ah 106: V7N General Purpose DI/DO Input Instance
0 to 63
0 0: Coast to stop
1 1: Decel to stop using Decel Time 1 (n020)
2 2: Decel to stop using Decel Time 2 (n022)
3 3: Operation continues with Alarm
4 4: Disabled
0 0: 125 kbps
1 1: 250 kbps
2 2: 500 kbps
3 3: Auto Baud
-15 to 15
-15 to 15
-15 to 15
DeviceNet Voltage Scale -15 to 15
SETTING FACTORY
INCREMENT SETTING
1
0.01
0.1
0.1 s
0.01
1%
1%
0.1 s
1
1%
0.1 s
1
0.1 or 1
1%
1%
1
(x 24 ms)
1%
0.1%
0.1%
70, 71,
150, 151,
152, 155,
156
20, 21,
100, 101,
102, 105,
106
1
1
1
1
1
1
1
0
1.00
1.0
1.0
0.00
0
100
0.0
0
0
1.0
0
(Note 1)
50
12
1
(24 ms)
0
0.5
0.2
71
21
0
0
2
0
0
0
0 n157 19Dh 9Dh DeviceNet Time Scale -15 to 15 1 0
31
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 32
Drive Parameter Listing
(n158-n179)
Drive Parameters - Continued
PARA- ADDR CLASS 100
METER INST. 01 n158 19Eh 9Eh n159 n160 n161 n162 n163
19Fh
1A0h
1A1h
1A2h
1A3h
9Fh
A0h
A1h
A2h
A3h
NAME
Motor Code (Energy Saving)
Energy Saving Voltage
Upper Limit At 60 Hz
(Energy Saving)
Energy Saving Voltage
Upper Limit At 6 Hz
(Energy Saving)
Power Supply Detection
Hold Width (Energy Saving)
Power Supply Detection
Filter Time Constant
PID Output Gain
DATA
-
-
-
n164 1A4h A4h PID Feedback Selection
-
-
0
1
2
3 n166 n167 n168 n169
1A6h
1A7h
1A8h
1A9h
A6h
A7h
A8h
A9h
Input Phase Loss
Detection Level
Input Phase Loss
Detection Time
Output Phase Loss
Detection Level
Output Phase Loss
Detection Time
4
5
-
-
-
0 to 70
0 to 120
0 to 25
0 to 100
SETTING RANGE
(AND UNITS)
0 to 255
0.0 to 25.0
0: Not Used
1: Not Used
3: Multi-Function Analog Input
(Voltage 0 - 10V) (CN2)
4: Multi-Function Analog Input
(Current 4 - 20mA) (CN2)
5: Not Used
0 to 100 (%)
0 to 255 (sec)
0 to 100 (%) n170 n173
1AAh
1ADh
AAh
ADh n174 1AEh AEh n175 n176 n177 n178 n179
1B0h
1B1h
1B2h
1B3h
1B4h
B0h
B1h
B2h
B3h
B4h
Modbus Frequency
Unit Selection
DC Injection P Gain
DC Injection I Time
Reduce Carrier at low speed selection
Digital Operator Parameter
Copy Function Selection
Digital Operator
Parameter copy
Access Selection
Fault History
Software Number
-
2
3
0
1
-
-
-
0.0 to 2.0 (sec)
0: 0.1 Hz
1: 0.01 Hz
2: 30,000/100%
3: 0.1%
1 to 999
1 to 250
0
1
0: Disabled
1: Carrier Frequency reduced to 2.5kHz
when Fout <= 5Hz & Iout >= 110%
Rdy rdy: READY status rEd rEd: READ executes
CPy Cpy: COPY executes vFy vFy: VERIFY executes vA vA: Inverter capacity display
Sno Sno: Software No. display
0
1
0: Read prohibited
1: Read allowed
(Note 3)
(Note 3)
(Note 6)
Note 1: Factory setting differs depending on V7N capacity.
Note 2: Factory setting differs depending on control method selected ( n002 ).
Note 3: n178 and n179 are display only parameters
Note 4: Parameter can be changed while V7N is operating.
Note 5: Available only in CIMR-V7NU25P5, 27P5, 45P5, and 47P5 Drives.
Note 6: Software number should be 3005 or higher for ADR functionality
Section 9
SETTING FACTORY
INCREMENT SETTING
1 Note 1
1% 120
1% 16
1%
1
(x 4 ms)
0.1
10
5
(20 ms)
1.0
1 0
1%
1 sec
1%
0.1 sec
1 0
1 (0.001) 83 (0.083)
1 (4ms)
25
(100ms)
0 1 rdy rEd
Cpy vFy vA
Sno
1 rdy
0
N/A
N/A
N/A
N/A
0
0
0
0
32
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 33
Section 10 Monitor Displays
When using the Monitor Function, a variety of information will appear on the Digital Operator display when each of the U-XX (display only) parameters is selected.
Monitor
U-01
U-02
U-03
U-04
U-05
U-06
U-07
U-08
U-09
U-10
U-11
U-12
U-13 (2)
U-14
U-15
U-16
U-17
U-18
U-19
U-60
U-61
U-62
U-63
U-64
U-65
U-66
Contents
Frequency reference (Hz)
Output frequency (Hz)
Output current (A)
AC output voltage (V)
DC Bus voltage (VPN)
Multi-function input terminal and
DeviceNet input status
Multi-function output terminal and
DeviceNet output status
Motor torque (%)
(Open loop vector only)
Fault history
(last 4 faults)(1)
Software number
XXXX
Output power (KW)
Reserve (Not displayed)
Elapse time
(0-6550 (x 10hour))
Reserve (N/A)
Reserve (N/A)
PID feedback (%)
PID input (%)
PID output (%)
Reserve (Not displayed)
DeviceNet Polled Producing
Attribute (PPA)
DeviceNet Polled Consuming
Attribute (PCA)
DeviceNet MAC ID switch setting
(S3 x 10 + S4)
DeviceNet MAC ID set
Display Example
60.0
60.0
12.5
230
325
72
1.bUS
0010
99.9
-
1234
32
1B2
-
-
35.0
100
75.5
-
-
-
38
39
3A
-
70: Basic speed control
71: Extended Speed Control
150: V7N Memobus I/O Control
151: V7N Standard Drive Control
152: V7N Accel/Decel Time Control
155: V7N Extended I/O MEMOBUS
Instance
156: V7N General Purpose DI/DO
Instance
-
(Readable via DeviceNet Object Class
5, Instance 2, Attribute 10)
20: Basic speed control
21: Extended Speed Control
100: V7N Memobus I/O Control
101: V7N Standard Drive Control
102: V7N Accel/Decel Time Control
105: V7N Extended I/O MEMOBUS
Instance
106: V7N General Purpose DI/DO
Instance
17
-
(Readable via DeviceNet Object Class
5, Instance 2, Attribute 10)
-
17
DeviceNet Baud Rate switch setting
(S1)
DeviceNet Baud Rate set
(when in Auto Baud)
125: 125 kbps
250: 250 kbps
500: 500 kbps
1
DeviceNet connection status
(1)
(1)
(1)
MEMOBUS Address (hex)
23
24
3B
28
31
2B
2D
1B3
37
-
35
-
(Readable via DeviceNet Object Class
3, Instance 1, Attribute 1)
-
-
(Readable via DeviceNet Object Class
3, Instance 1, Attribute 2)
-
(Readable via DeviceNet Object Class
5, Instance 1 and 2, Attribute 1)
(1) Refer to TM.V7N.01 for Monitor details
(2) Available only in CIMR-V7NU25P5, 27P5, 45P5, and 47P5 Drives
33
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 34
Drive Dimensions
Fig. 1
2-d
0.06
(1.5)
H1 H3 H
W2
Fig. 2
W1
W
H2
H4
0.16
(4.0)
0.33
(8.5)
4-d
0.06
(1.5)
H1 H3 H
H2 H4
W1
W
V7N Enclosed wall mounted type
W2
0.16
(4.0)
0.33
(8.5)
D
D
Section 11
34
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 35
Section 11 Drive Dimensions
V7N Enclosed wall mounted type
Voltage
Class
230V
3-phase
230V
3-phase
460V
3-phase
Model
CIMR-
V7NU
20P1
20P2
20P4
20P7
21P5
22P2
23P7
40P2
40P4
40P7
41P5
42P2
43P7
Size
HP
1/8
1/4
1/2
3/4 & 1
2
3
5
1/2
3/4
1 & 2
3
3
5
W H D
Dimensions in inches (mm)
W1 H1 H2 W2 H3 H4 d
2.68
5.83
3.58
2.20
4.65
0.20
0.24
5.04
0.79
M4
(68) (148) (91) (56) (118) (5) (6) (128) (20)
2.68
5.83
3.58
2.20
4.65
0.20
0.24
5.04
0.79
M4
(68) (148) (91) (56) (118) (5) (6) (128) (20)
2.68
5.83
4.84
2.20
4.65
0.20
0.24
5.04
0.79
M4
(68) (148) (123) (56) (118) (5) (6) (128) (20)
2.68
5.83
5.63
2.20
4.65
0.20
0.24
5.04
0.79
M4
(68) (148) (143) (56) (118) (5) (6) (128) (20)
4.25
5.83
5.75
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (146) (96) (118) (5) (6) (128) (20)
4.25
5.83
6.10
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (155) (96) (118) (5) (6) (128) (20)
5.51
5.83
6.22
5.04
4.65
0.20
0.24
5.04
0.79
M4
(140) (148) (158) (128) (118) (5) (6) (128) (20)
4.25
5.83
4.21
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (107) (96) (118) (5) (6) (128) (20)
4.25
5.83
4.92
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (125) (96) (118) (5) (6) (128) (20)
4.25
5.83
6.10
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (155) (96) (118) (5) (6) (128) (20)
4.25
5.83
6.73
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (171) (96) (118) (5) (6) (128) (20)
4.25
5.83
6.73
3.78
4.65
0.20
0.24
5.04
0.79
M4
(108) (148) (171) (96) (118) (5) (6) (128) (20)
5.51
5.83
6.22
5.04
4.65
0.20
0.24
5.04
0.79
M4
(140) (148) (158) (128) (118) (5) (6) (128) (20)
Weight
(kg)
1.55
1.55
2.20
2.65
3.53
(1.6)
3.75
(1.7)
5.30
(2.4)
2.65
(1.2)
2.65
(1.2)
3.75
(1.7)
3.75
(1.7)
3.75
(1.7)
5.30
(2.4)
Heat Loss (W)
Heat-
Internal Total sink
Fig.
9.3
13.0
1 3.7
(0.7)
7.7
(0.7)
10.3
18.0
1
15.8
12.3
28.1
1
(1.0)
28.4
16.7
45.1
1
(1.2)
53.7
19.1
72.8
2
60.4
96.7
9.4
15.1
30.3
45.8
50.5
73.4
34.4
52.4
13.7
15.0
24.6
29.9
32.5
44.5
94.8
149.1
23.1
30.1
54.9
75.7
83.0
117.9
2
2
2
2
2
2
2
2
V7N Enclosed wall mounted type
Drives represented in Fig. 3 can be used as "IP00" type enclosures if the top and bottom covers are removed.
Voltage
Class
230V
3-phase
460V
3-phase
Model
CIMR-
V7NU
25P5
27P5
45P5
47P5
Size
HP W H D
Dimensions in inches (mm)
W1 H1 H2 W2
7.5
10
7.09
10.24
7.28
6.46
9.61
0.31
0.31
(180) (260) (185) (164) (244) (8) (8)
7.09
10.24
7.28
6.46
9.61
0.31
0.31
(180) (260) (185) (164) (244) (8) (8)
7.5 & 10 7.09
10.24
7.28
6.46
9.61
0.31
0.31
(180) (260) (185) (164) (244) (8) (8)
10 7.09
10.24
7.28
6.46
9.61
0.31
(180) (260) (185) (164) (244) (8)
0.31
(8)
H3
–
–
–
–
H4
–
–
–
– d
Weight
(kg)
Heat Loss (W)
Heat- Internal Total sink
Fig.
M5 11.45
(5.2)
M5 11.89
(5.4)
170.4
219.2
79.4
98.9
249.8
318.1
3
3
M5 10.14
168.8
87.7
256.5
3
(4.6)
M5 10.58
209.6
99.3
308.9
3
(4.8)
Fig. 3
4-d
0.06
(1.5)
MS
NS
H1 H
W1
W
W2
H2
0.09
(2.20)
D
35
V7N with DeviceNet
YASKAWA ELECTRIC AMERICA, INC.
Drives Division
16555 W. Ryerson Rd., New Berlin, WI 53151, U.S.A.
Phone: (800) YASKAWA (800-927-5292) Fax: (262)
782-3418
Internet: http://www.drives.com
YASKAWA ELECTRIC AMERICA, INC.
Chicago-Corporate Headquarters
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: (800) YASKAWA (800-927-5292) Fax: (847)
887-7310
Internet: http://www.yaskawa.com
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan,
Minatoku, Tokyo, 105-0022, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580
Internet: http://www.yaskawa.co.jp
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone: 49-6196-569-300 Fax: 49-6196-888-301
V7N Drive with DeviceNet
Installation Guide
YEA Document Number: IG.V7N.01 5/23/07 Software Version: 3005
Data Subject to change without notice.