advertisement
![SOLIS Solis-mini-700-4G Installation And Operation Manual | Manualzz SOLIS Solis-mini-700-4G Installation And Operation Manual | Manualzz](http://s2.manualzz.com/store/data/064708527_1-0e9ded562b2eb9d0adb5ee8a4e567588-360x466.png)
PV Grid Tie Inverter
Solis 4G Mini Single Phase Inverter
Installation and Operation Manual
Solis-mini-700-4G, Solis-mini-1000-4G, Solis-mini-1500-4G, Solis-mini-2000-4G,
Solis-mini-2500-4G, Solis-mini-3000-4G, Solis-mini-3600-4G, Solis-mini-1000-4G-LV
Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606
Please adhere to the actual products in case of any discrepancies in this user manual.
If you encounter any problem on the inverter, please find out the inverter S/N and contact us, we will try to respond to your question ASAP.
C
Ginlong Technologies Co., Ltd.
Ver 2.2
Contents
1. Introduction …………………………………………………
1.1 Product Description
1.2 Packaging
2. Safety Instructions
……………………………………
……………………………………………
…………………………………………
2.1 Safety Symbols ………………………………………
2.2 General Safety Instructions
2.3 Notice For Use
…………………………
…………………………………………
3. Overview ……………………………………………………
3.1 Front Panel Display …………………………………
3.2 LED Status Indicator Lights …………………………
3.3 Keypad
3.4 LCD
………………………………………………
……………………………………………………
4. Installation …………………………………………………
4.1 Select Location for the Inverter
4.2 Mounting the Inverter
……………………
…………………………………
4.3 Electrical Connections …………………………………
4.3.1 Connect PV side of inverter
4.3.2 Connect grid side of inverter
…………………
…………………
4.3.3 External ground connection …………………
4.3.4 Max. overcurrent protection device (OCPD) …
4.3.5 Inverter monitoring connection ………………
4.3.6 Electrical connection diagram
4.3.7 Meter Connection (optional)
………………
…………………
4.3.8 CT connections (optional) ……………………
4.3.9
Logic interface connection (For UK and Belgium)
……
5. Start & Stop ………………………………………………
5.1 Start the Inverter
5.2 Stop the Inverter
……………………………………
………………………………………
6. Operation ……………………………………………………
6.1 Main Menu ………………………………………………
6.2 Information
6.2.1
………………………………………………
Lock screen
………………………………………
6.3 Settings …………………………………………………
6.3.1 Set Time ………………………………………
18
19
19
20
20
9
11
13
8
8
9
13
16
6
7
5
5
7
7
4
5
3
3
23
24
25
25
25
26
26
26
28
28
28
Contents
6.3.2 Set Address ……………………………………
6.4 Advanced Info.
………………………………………
6.4.1 Alarm Message ………………………………
6.4.2 Running Message
6.4.3 Version
……………………………
…………………………………………
6.4.4 Daily Energy
6.4.5 Monthly Energy
……………………………………
…………………………………
6.4.6 Yearly Energy
6.4.7 Daily Record
……………………………………
……………………………………
6.4.8 Communication Data
6.4.9 Warning Message
…………………………
…………………………
6.5 Advanced Settings
6.5.1 Select Standard
6.5.2 Grid ON/OFF
…………………………………
………………………………
……………………………………
6.5.3 24H Switch ……………………………………
6.5.4 Clear Energy
6.5.5 Reset Password
………………………………
…………………………………
6.5.6 Power Control
6.5.7 Calibrate Energy
6.5.8 Special Settings
………………………………
…………………………………
……………………………
6.5.9 STD. Mode Settings ………………………
6.5.10 Restore Settings
6.5.11 HMI Update
……………………………
…………………………………
6.5.12 Internal EPM Set ……………………………
6.5.13 External EPM Set ……………………………
6.5.14 Restart HMI …………………………………
6.5.15 Debug Parameter …………………………
6.5.16 DSP Update …………………………………
6.5.17 Power Parameter …………………………
7. Maintenance
8. Troubleshooting
………………………………………………
…………………………………………
9. Specifications ……………………………………………
41
41
42
42
45
36
40
40
40
34
35
35
35
36
34
34
34
31
31
32
32
33
33
29
30
30
30
28
29
29
31
31
1. Introduction
1.1 Product Description
Solis 4G Mini Single Phase Inverter integrate DRM and backflow power control function, thatcould suitable for smart grid requirement.
Mini Single phase 4G series inverter contain 8 models which are listed below:
Solis-mini-700-4G, Solis-mini-1000-4G, Solis-mini-1500-4G, Solis-mini-2000-4G,
Solis-mini-2500-4G, Solis-mini-3000-4G, Solis-mini-3600-4G, Solis-mini-1000-4G-LV
LED lights
LCD display
4 buttons
Figure 1.1 Front side view
CT or Meter input
DC Switch(optional)
DRM
(For UK and Belgium)
Figure 1.2a Bottom side view (0.7~3.0kW)
DC input RS 485 AC output
Figure 1.2b Bottom side view (3.6kW)
.3.
1. Introduction
1.2 Packaging
When you receive the inverter, ensure that all the parts listed below are included:
.4.
1 2 3
PV Grid Tie Inverter
Solis 4G Mini Single Phase Inverter
Installation and Operation Manual
Solis -m ini-7 00-4 G, S olis -m ini-1 000-4 G, Solis -m ini-1 500-4 G, S olis -m in i-2 000-4 G,
Solis -m ini-2 500-4 G, Solis -m ini-3 000-4 G, S olis -m in i-3 600-4 G, S olis -m in i-1 000-4 G-LV
4
Part #
1
2
3
4
5
6
7
8
9
5 6 7
Description
PV grid tie inverter
Wall/pole bracket
Locking screws
DC connector
AC connector
RJ45 connector
(For UK and Belgium)
WiFi / GPRS Stick ( Optional )
Manual
CT with cable ( Optional )
Table 1.1 Parts list
Number
1
1
2
1 pair for 0.7~3.0kW
2 pairs for 3.6kW
1
1
1
1
1
C
Ginlong Technologies Co., Ltd.
Ver 2.2
8
2.Safety Instructions
Improper use may result in potential electric shock hazards or burns. This manual contains important instructions that should be followed during installation and maintenance. Please read these instructions carefully before use and keep them for future reference.
2.1 Safety Symbols
Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed as follows:
WARNING:
WARNING symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death.
NOTE:
NOTE symbol indicates important safety instructions, which if not correctly followed, could result in some damage or the destruction of the inverter.
CAUTION:
CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety instructions, which if not correctly followed, could result in electric shock.
CAUTION:
CAUTION, HOT SURFACE symbol indicates safety instructions, which if not correctly followed, could result in burns.
2.2 General Safety Instructions
WARNING:
Only devices in compliance with SELV (EN 69050) may be connected to the
RS485 and USB interfaces.
WARNING:
Please don’t connect PV array positive(+) or negative(-) to ground, it could cause serious damage to the inverter.
WARNING:
Electrical installations must be done in accordance with the local and national electrical safety standards.
WARNING:
Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input.
.5.
2.Safety Instructions
WARNING:
To reduce the risk of fire, over-current protective devices (OCPD) are required for circuits connected to the Inverter.
The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC
Article 690, Part II. All Solis 4G Mini Single Phase Inverters feature an integrated
DC switch.
CAUTION:
Risk of electric shock. Do not remove cover. There is no user serviceable parts inside. Refer servicing to qualified and accredited service technicians.
CAUTION:
The PV array (Solar panels) supplies a DC voltage when they are exposed to sunlight.
CAUTION:
Risk of electric shock from energy stored in capacitors of the Inverter. Do not remove cover for 5 minutes after disconnecting all power sources(service technician only). Warranty may be voided if the cover is removed without unauthorized .
CAUTION:
The surface temperature of the inverter can reach up to 75 ℃ (167 F).
To avoid risk of burns, do not touch the surface of the inverter while it’s operating.
Inverter must be installed out of the reach of children.
PV module used with inverter must have an IEC 61730 Class A rating.
.6.
2.3 Notice For Use
The inverter has been constructed according to the applicable safety and technical guidelines. Use the inverter in installations that meet the following specifications ONLY:
1. Permanent installation is required.
2. The electrical installation must meet all the applicable regulations and standards.
3. The inverter must be installed according to the instructions stated in this manual.
4. The inverter must be installed according to the correct technical specifications.
5. To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before
the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply
Main Switch (AC) must be switched off before the solar panel's DC isolator shall be
switched off.
3.1 Front Panel Display
3. Overview
Figure 3.1 Front Panel Display
3.2 LED Status Indicator Lights
There are three LED status indicator lights in the front panel of the inverter. Left LED:
POWER LED (red) indicates the power status of the inverter. Middle LED: OPERATION
LED (green) indicates the operation status. Right LED: ALARM LED (yellow) indicates the alarm status. Please see Table 3.1 for details
Light
POWER
OPERATION
ALARM
Status
ON
OFF
ON
OFF
FLASHING
ON
OFF
Description
The inverter can detect DC power
No DC power or low DC power
The inverter is operating properly.
The inverter has stopped to supply power.
The inverter is initializing.
Alarm or fault condition is detected.
The inverter is operating without fault or alarm.
Table 3.1 Status Indicator Lights
.7.
3. Overview
3.3 Keypad
There are four keys in the front panel of the Inverter(from left to right):
ESC, UP, DOWN and ENTER keys. The keypad is used for:
Scrolling through the displayed options (the UP and DOWN keys);
Access to modify the adjustable settings (the ESC and ENTER keys).
3.4 LCD
The two-line Liquid Crystal Display (LCD) is located on the front panel of the Inverter, which shows the following information:
Inverter operation status and data;
Service messages for operator;
Alarm messages and fault indications.
4. Installation
4.1 Select a Location for the Inverter
To select a location for the inverter, the following criteria should be considered:
WARNING: Risk of fire
Despite careful construction, electrical devices can cause fires.
Do not install the inverter in areas containing highly flammable materials or
gases.
Do not install the inverter in potentially explosive atmospheres.
Do not install in small closed spaces where air can not circulate freely. To avoid overheating, always make sure the flow of air around the inverter is not blocked.
Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting. Ginlong recommends inverter installed to avoid direct sunlight or raining.
To avoid over heating ambient air temperature must be considered when choosing the inverter installation location. Ginlong recommends using a sun shade minimizing direct sunlight when the ambient air temperature around the unit exceeds 104°F/40°C.
Figure 4.1 Recommended installation position
.9.
.8.
4. Installation
Install vertically with a maximum incline of +/- 5 °.
If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
When 1 or more inverters are installed in one location, a minimum 12inchs clearance should be kept between each inverter or other object. The bottom of the inverter should be 20inchs clearance to the ground.
4.2 Mounting the Inverter
Dimensions of wall bracket:
4. Installation
.10.
300mm 300mm 300mm
Figure 4.2 Inverter Mounting clearance
Visibility of the LED status indicator lights and the LCD located at the front panel of the inverter should be considered.
Adequate ventilation must be provided if the inverter is to be installed in a confined space.
NOTE:
Nothing should be stored on or placed against the inverter.
Figure 4.3 Inverter wall mounting
Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter.
The inverter shall be mounted vertically. The steps to mount the inverter are listed below:
1. According to the figure 4.2, select the mounting height of the bracket and mark the
mounting holes. For brick walls, the position of the holes should be suitable for the
expansion bolts.
Bracket
Suitable fixing screws
Figure 4.4 Inverter wall mounting
.11.
4. Installation
2.Make
sure the bracket is horizontal and the mounting holes (in Figure 4.4 )
are marked correctly . Drill the holes into the wall or pillar at your marks .
3. Use the suitable screws to fix the bracket to the wall.
WARNING:
The inverter must be mounted vertically.
4. Lift up the inverter (be careful to avoid body strain), and align the back bracket on the
inverter with the convex section of the mounting bracket. Hang the inverter on the
mounting bracket and make sure the inverter is secure (see Figure 4.5).
Locking screws
4. Installation
4.3 Electrical Connections
4.3.1 Connect PV side of inverter
The electrical connection of the inverter must follow the steps listed below:
1. Switch the Grid Supply Main Switch (AC) OFF.
2. Switch the DC Isolator OFF.
3. Assemble PV input connector to the Inverter.
Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter
Maximum 600Voc for
Solis-mini-700-4G, Solis-mini-1000-4G, Solis-mini-1500-4G,
Solis-mini-2000-4G, Solis-mini-2500-4G, Solis-mini-3000-4G,
Solis-mini-3600-4G, Solis-mini-1000-4G-LV
Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter
Before connection, please make sure the polarity of the output voltage of PV array matches the “ DC+ ” and “ DC” symbols.
Figure 4.6 DC+ Connector Figure 4.7 DC- Connector
Please use approved DC cable for PV system.
Figure 4.5 Wall Mount Bracket
5. Use M4*9 screws in accessory to lock the inverter to the mount bracket.
.12.
.13.
4. Installation
Cable type
Cross section
Range
Recommended value
Industry generic PV cable
( model:PV1 F )
4.0~6.0
( 12~10AWG )
4.0
( 12AWG )
Table 4.1 DC cable
The steps to assemble the DC connectors are listed as follows:
I) Strip off the DC wire for about 7mm, Disassemble the connector cap nut.
Figure 4.8 Disassemble the Connector Cap nut
ii) Insert the wire into the connector cap nut and contact pin.
Figure 4.9 Insert the Wire into the Connector Cap nut and contact pin
iii) Crimp the contact pin to the wire using a proper wire crimper.
Crimping plier
Figure 4.10 Crimp the contact pin to the wire
.14.
4. Installation iv) Insert the contact pin to the top part of the connector and screw up the cap nut to the top part of the connector.
Figure 4.11 Connector with Cap nut Screwed on v) Then connect the DC connectors to the inverter. Small click will confirm connection.
Figure 4.12 Connect the DC Connectors to the Inverter
Caution:
If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch as it will damage the inverter and even leads to a fire disaster.
The correct actions are:
*Use a clip-on ammeter to measure the DC string current
*If it is above 0.5A, please wait for the solar irradiance reduces until the
current decreases to below 0.5A.
*Only after the current is below 0.5A, you are allowed to turn off the DC switches and disconnect the PV strings.
Please note that any damages due to wrong operations are not covered in the device warranty.
.15.
4. Installation
4.3.2 Connect grid side of inverter
2
For all AC connections, 2.5- 6mm 105 ℃ cable is required to be used. Please make sure the resistance of cable is lower than 1 ohm. If the wire is longer than 20m, it's recommended
WARNING:
There are symbols marked inside the connector , the Line wire of grid must be connected to “ L ” terminal; the Neutral wireof grid must be connected to “ N ” terminal; the Earth of grid must be connected to “ ” (see Figure 4.13).
Cable type
Industry generic grid cable
Cross section
Range
Recommended value
2.5~6.0mm
²
Table 4.2 Grid cable size
6mm ²
4. Installation
The steps to assemble the AC grid terminal connectors are listed as follows: a) Disassemble the AC connector. Strip the AC wires about 6mm.
Figure 4.15 Stripped AC Wires b) Fix the green and yellow wire to the ground terminal. Fix the red(or brown) wire to L
(line) terminal. Fix the blue wire to N(Neutral). Tight the screws on the connector.
Please try to pull out the wire to make sure the it’s well connected.
Figure 4.13 AC Grid Terminal Connector Inside
Each Solis 4G Mini Single Phase Inverter is supplied with an AC grid terminal connector.
Figure 4.16 Connect Wires to the Terminal
c) Tighten up the cap on the terminal (see Figure 4.17).
Figure 4.14 AC Grid Terminal Connector
Figure 4.17 Tighten up the Cap on the Terminal
.17.
.16.
4. Installation
d) Connect the AC grid terminal connector to the inverter. Small click will confirm connection.
Figure 4.18 Connect the AC Connector to the Inverter
Note: Connection for Split phase grid.
When connect to 208/220/240V split phase, please connect L1 to “L” terminal,
L2 to “N” terminal. Also connect earth to ground terminal.
4.3.3 External ground connection
An external ground connection is provided at the right side of inverter.
Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal.
.18.
Figure4.19
Connect the external grounding conductor
4. Installation
4.3.4 Max. over current protection device (OCPD)
To protect the inverter's AC grid connection conductors, Solis recommends installing breakers that will protect against overcurrent. The following table defines OCPD ratings for the Solis Mini Single PhaseInverters.
Inverter
Rated output
voltage(V)
Rated output
current (A)
Current for protection device (A)
Solis-mini-700-4G
Solis-mini-1000-4G
Solis-mini-1500-4G
Solis-mini-2000-4G
220/230
220/230
220/230
220/230
3.2/3.0
4.5/4.3
6.8/6.5
9.1/8.7
10
10
10
15
Solis-mini-2500-4G
Solis-mini-3000-4G
Solis-mini-3600-4G
Solis-mini-1000-4G-LV
220/230
220/230
220/230
101/120/127
11.4/10.9
13.6/13
16
8.3
15
20
20
15
Table 4.3 Rating of grid OCPD
4.3.5 Inverter monitoring connection
The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are optional (Figure 4.20). For connection instructions, please refer to the Solis Monitoring
Device installation manuals.
Smart phone monitoring
GPRS monitoring
Internet
Wi-Fi monitoring
Router
Wi-Fi monitoring
PC monitoring
Wi-Fi box
Figure 4.20 Communication function
Web server
.19.
4. Installation
4.3.6 Electrical connection diagram
Refer to figure 4.21, which is a simple guidance for installing a solar system with PV inverter.
A DC isolator is required to be installed in the system between PV panels with inverter.
Isolation device
Consumers mains
(to grid)
Main switch
1
MAIN SWITCHBOARD
Solar supply main switch
1 Inverter with integral grid
Protection device
Solar
(PV) array
2
Isolation switch
Circuits not protected by
RCDs
Circuits Protected by RCDs
Figure 4.21 Guidance for a Simple Installation of an Inverter Solar Energy System
1. The RCD should be in parallel connection between the consumers mains and the solar supply.
2. More than one RCD may be used. Each RCD can protect one or more circuits.
4.3.7 Meter Connection(optional)
The inverter can work with a single phase smart meter to achieve Export Power Management function and/or 24hour consumption monitoring function.
Note:
Inverters are classified as "Meter Model" and "CT Model" due to hardware difference.
Meter Model can only connect a smart meter.
CT Model can only connect a smart sensor.
Please consult Solis Sales Rep before placing the order.
Note:
To achieve Export Power Management function, the smart meter can be installed on either grid side or load side. To achieve 24hour consumption monitoring function, the smart meter can only be installed on grid side.
Two types of meters are supported:
Direct Insert Type Meter - Max input current 60A (Model:DDSD1352-C)
External CT Type Meter - 120A/40mA CT is supplied (Model: ACR10RD16TE)
Customer can place the order for a suitable meter from Solis Sales Reps.
Below are the connection diagrams of different meters connecting to different locations.
Detailed settings please refer to Section 6.5.12.
.20.
4. Installation
Pre-made Cable in Meter Package
A B
5 6 7 8
Load
L N PE
L L' N N'
2-Pin Connector
INV L
INV N
INV PE
Figure 4.22 Direct Insert Type Meter - “Meter in Grid”
Grid L
Grid N
Grid PE
2-Pin Connector
INV L
INV N
INV PE
Grid L
Grid N
Grid PE
Pre-made Cable in Meter Package
A B
5 6 7 8
L L' N N'
Load
L N PE
Figure 4.23 Direct Insert Type Meter - “Meter in Load”
.21.
4. Installation
1 2 3 4 13 12
Pre-made Cable in Meter Package RJ45 Connector
5 6 7 8 9 10 21 22 23
2-Pin Connector
INV L
INV N
INV PE
Load
L N PE
White Black
+ -
CT Arrow Grid
Grid L
Grid N
Grid PE
Figure 4.24 External CT Type Meter - “Meter in Grid”
INV L
INV N
INV PE
Grid L
Grid N
Grid PE
2-Pin Connector
Pre-made Cable in Meter Package
1 2 3 4 13 12
.22.
RJ45 Connector
5 6 7 8 9 10 21 22 23
White Black
+ -
Load
L N PE
Figure 4.25 External CT Type Meter - “Meter in Load”
4. Installation
4.3.8 CT connections(optional)
The inverter can work with a smart sensor to achieve Export Power Management function.
NOTE:
Inverters are classified as "Meter Model" and "CT Model" due to hardware difference.
Meter Model can only connect a smart meter.
CT Model can only connect a smart sensor.
Please consult Solis Sales Rep before placing the order.
NOTE:
To achieve Export Power Management function, the smart sensor must be installed on the grid side.
Below is the connection diagram of the smart sensor.
Detailed settings please refer to Section 6.5.12.
Pre-made Cable in CT Package
2-Pin Connector
CT Arrow Grid
INV L
INV N
INV PE
Grid L
Grid N
Grid PE
Load
L N PE
Figure 4.26 Smart Sensor
.23.
4. Installation
4.3.9 Logic interface connection (For UK and Belgium)
Logic interface is required by Logic interface is required by local regulations in UK and
Belgium that can be operated by a simple switch or contactor.
When the switch is closed the inverter can operated normally.
When the switch is opened, the inverter will reduce it’s output power to zero within 5s.
Pin5 and Pin6 of RJ45 terminal is used for the logic interface connection.
Please follow below steps to assemble RJ45 connector.
1. Insert the network cable into the communication connection terminal of RJ45.
Figure 4.27 RJ45 communication connection terminals
2. Use the network wire stripper to strip the insulation layer of the communication cable.
According to the standard line sequence of figure 4.28 connect the wire to the plug of
RJ45, and then use a network cable crimping tool to make it tight.
Rj45 plug 1--8
Rj45 terminal
1 2 3 4 5 6 7 8
Correspondence between the cables and the stitches of plug, Pin5 and Pin6 of RJ45 terminal is used for the logic interface, other Pins are reserved.
Pin 1: Reserved; Pin 2: Reserved
1 2 3 4 5 6 7 8
Switch _ input1 Switch _ input2
DRM(logic interface)
Pin 3: Reserved; Pin 4: Reserved
Pin 5: Switch_input1; Pin 6: Switch_input2
Pin 7: Reserved; Pin 8: Reserved
Figure 4.28 Strip the insulation layer and connect to RJ45 plug
3. Connect RJ45 to DRM (l ogic interface ) .
After wire connection, please refer chapter 6.5.8.1 to enable the logic interface function.
5. Start & Stop
5.1 Start the Inverter
To start up the Inverter, it is important that the following steps are strictly followed:
1. Switch the grid supply main Switch (AC) ON first.
2. Switch the DC switch ON. If the voltage of PV arrays are higher than start up voltage,
the inverter will turn on. The red LED power will light.
3. When both the DC and the AC sides supply to the inverter, it will be ready to generate
power. Initially, the inverter will check both its internal parameters and the parameters
of the AC grid, to ensure that they are within the acceptable limits. At the same time,
the green LED will flash and the LCD displays the information of INITIALIZING.
4. After 30-300 seconds (depending on local requirement), the inverter will start to
generate power. The green LED will be on continually and the LCD displays
GENERATING.
WARNING:
Do not touch the surface when the inverter is operating. It may be hot and cause burns.
5.1.1 Inverter working status
When inverter working normally,there would be 5 status :
Generating:Inverter is working normally
LimByTemp: Inverter power limited by over ambient temperature.
LimByFreq: Inverter power limited by over grid frequency
LimByVg: Inverter power limited by over grid voltage
LimByVar: Inverter power limited by generating reactive power.
5.2 Stop the Inverter
To stop the Inverter, the following steps must be strictly followed:
1. Switch the Supply Main Switch (AC) OFF.
2. Wait 30 seconds. Switch the DC Switch OFF. All the LEDs of the inverter will be off in one
minute.
.24.
.25.
6. Operation
During normal operation, the display alternately shows the power and the operation status with each screen lasting for 10 seconds (see Figure 6.1). Screens can also be scrolled manually by pressing the UP and DOWN keys. Press the ENTER key to access to the Main Menu.
Pressing the
ESC key calls back the previous menu.
Power 3424W
01-01-2020 00:00
Main Menu
Information
UP/DOWN
Settings
5 sec
Start
UP/DOWN or auto-scroll
(10 sec)
UP/DOWN
Advanced Info.
Status: Generating
01-01-2020 00:00 UP/DOWN
Advanced settings
Pressing the
ENTER key gives access to the main menu.
Figure 6.1 Operation Overview
6.1 Main Menu
There are four submenus in the Main Menu (see Figure 6.1):
1. Information
2. Settings
3. Advanced Info.
4. Advanced Settings
6.2 Information
The Solis 4G Mini Single Phase Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
.26.
6. Operation
Display
V_DC1 350.8V
I_DC1 5.1A
V_DC2 350.8V
I_DC2 5.1A
V_Grid 230.4V
I_Grid 8.1A
Status: Generating
Power: 1488W
Duration
10 sec
10 sec
10 sec
10 sec
Description
V_DC1: Shows input 01 voltage value.
I_DC1: Shows input 01 current value.
V_DC2: Shows input 02 voltage value.
I_DC2: Shows input 02 current value.
V_Grid: Shows the grid's voltage value
I_Grid: Shows the grid's current value.
Status: Shows instant status of the Inverter.
Power: Shows instant output power value.
Grid Frequency
F_Grid 60.06Hz
10 sec F_Grid: Shows the grid's frequency value.
Total Energy
0258458 kwh
This Month: 0123kwh
Last Month: 0123kwh
Today: 15.1kwh
Yesterday: 13.5kwh
Inverter SN
00000000000000
Export_P: +0000W
Export_I: 00.0A
Work Mode: NULL
DRM Number: 08
Meter EnergyP
0000000 .
00k Wh
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
Total generated energy value.
This Month: Total energy generated this month.
Last Month: Total energy generated last month.
Today: Total energy generated today.
Yesterday: Total energy generated yesterday.
Display series number of the inverter.
Power of ERM.
Current of EPM.
Work Mode : The work mode of inverter .
DRM Number : Show the number 01 08 .
Meter EnergyP : The active power .
Table 6.1 Information list
.27.
6. Operation
6.2.1 Lock screen
Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks
(Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen.
5.2 Stop the Inverter
(a) (b)
Figure 6.2 Locks and Unlocks the Screen of LCD
6.3 Settings
The following submenus are displayed when the Settings menu is selected:
1. Set Time 2. Set Address
6.3.1 Set Time
This function allows time and date setting. When this function is selected, the LCD will display a screen as shown in Figure 6.3.
NEXT=<ENT> OK=<ESC>
01-01-2020 00:00
Figure 6.3 Set Time
Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one digit to the next (from left to right).
Press the ESC key to save the settings and return to the previous menu.
6.3.2 Set Address
This function is used to set the address when muti inverters are connected to single monitor.
The address number can be assigned from “01”to “99”.
The default address number of Solis 4G Mini Single Phase Inverter is “01”.
YES=<ENT> NO=<ESC>
Set Address: 01
Figure 6.4 Set Address
Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.
Press the ESC key to cancel the change and return to the previous menu.
.28.
6. Operation
6.4 Advanced Info - Technicians Only
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Enter menu “Advanced Info.” and “Advanced settings” ( need password ) .
Select “Advanced Info.” from the Main Menu. The screen will require the password as below
YES=<ENT> NO=<ESC>
Password:0000
Figure 6.5 Enter password
The default password is “0010".
Please press “down” to move the cursor, press “up” to select the number.
After enter the correct password the Main Menu will display a screen and be able to access to the following information.
1. Alarm Message 2. Running Message 3.Version 4. Daily Energy 5. Monthly Energy
6. Yearly Energy 7. Daily Record 8. Communication Data 9 .
Warning Message
The screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTER key gives access to a submenu. Press the ESC key to return to the Main Menu.
6.4.1 Alarm Message
The display shows the 100 latest alarm messages.
Screens can be scrolled manually by pressing the UP/ DOWN keys.
Press the ESC key to return to the previous menu.
Alarm001: OV-G-V
Time: 00-00 Data: 0000
Figure 6.6 Alarm Message
6.4.2 Running Message
This function is for maintaince person to get running message such as internal temperature,
Standard NO. etc.
Screens can be scrolled manually by pressing the UP/DOWN keys.
.29.
6. Operation
6.4.3 Version
The screen shows the model version and the software version of the Inverter .
Model: 08
Software Version: D20001
Figure 6.7 Model Version and Software Version
6.4.4 Daily Energy
The function is for checking the energy generation for selected day.
YES=<ENT> NO=<ESC>
Select: 2020-0101
Figure 6.8 Select date for daily energy
Press DOWN key to move the cursor to day, month and year, press UP key to change the digit. Press Enter after the date is fixed.
2020-01-01: 051.3kWh
2020-01-02: 061.5kWh
Figure 6.9 Daily energy
Press UP/DOWN key to move one date from another.
6.4.5 Monthly Energy
The function is for checking the energy generation for selected month.
YES=<ENT> NO=<ESC>
Select: 202001
Figure 6.10 Select month for monthly energy
Press DOWN key to move the cursor, press UP key to change the digit.
Press Enter after the month is fixed.
2020-02: 0510kWh
2020-01: 0610kWh
Figure 6.11 Month energy
Press UP/DOWN key to move one date from another.
.30.
6. Operation
6.4.6 Yearly Energy
The function is for checking the energy generation for selected year.
YES=<ENT> NO=<ESC>
Select: 20 20
Figure 6.12 Select year for yearly energy
Press DOWN key to move the cursor, press UP key to change the digit.
Press Enter after the year is fixed.
2020: 0017513kWh
2019: 0165879kWh
Figure 6.13 Yearly energy
Press UP/DOWN key to move one date from another.
6.4.7 Daily record
The screen shows history of changing settings. Only for maintance personel.
6.4.8 Communication Data
The screen shows the internal data of the Inverter (see Figure 6.14), which is for service technicians only.
01-05: 01 25 E4 9D AA
06-10: C2 B5 E4 9D 55
Figure 6.14 Communication Data
6.4.9 Warning Message
The display shows the 100 latest warn messages (see Figure 6.15). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.
Msg000:
T: 00 00 00 : 00 D : 0000
Figure 6.15 Warning Message
.31.
6. Operation
6.5 Advanced Settings - Technicians Only
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 6.4 to enter password to access this menu.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard 2. Grid ON/OFF 3. 24H Switch 4. Clear Energy 5. Reset Password
6. Power Control 7. Calibrate Energy 8. Special Settings 9. STD. Mode Settings
10. Restore Settings 11. HMI Update 12. Internal EPM Set 13. External EPM Set
14. Restart HMI 15. Debug Parameter 16. DSP Update 17. Power Parameter
6.5.1 Selecting Standard
This function is used to select the grid's reference standard (see Figure 6.16).
YES=<ENT> NO=<ESC>
Standard:AS4777-02
Figure 6.16
Press the UP/DOWN keys to select the standard (AS4777-02,AS4777-15, VDE4105, VDE0126,
UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3
(for 4-5kW models), C10/11, EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function).
NOTE:
This function is for technicians use only.
NOTE:
For different countries, the grid standard needs to be set as different according to local requirements. If there is any doubt, please consult
Solis service technicians for details.
Selecting the “User-Def” menu will access to the following submenu (see Figure 6.17),
OV-G-V1: 260V
OV-G-V1-T: 1S
Figure 6.17
NOTE:
The " User-Def" function can be only used by the service engineer and must be allowed by the local energy supplier.
.32.
6. Operation
Below is the setting range for “User-Def”.
Using this function, the limits can be changed manually.
OV-G-V1: 240---270V OV-G-F1: 50.2-53Hz(60.2-64Hz)
OV-G-V1-T: 0.1---9S OV-G-F1-T: 0.1---9S
OV-G-V2: 240---300V OV-G-F2: 50.2-53Hz(60.2-64Hz)
OV-G-V2-T: 0.1---1S OV-G-F2-T: 0.1---9S
UN-G-V1: 170---210V UN-G-F1: 47-49.5Hz(56-59.8Hz)
UN-G-V1-T: 0.1---9S UN-G-F1-T: 0.1---9S
UN-G-V2: 110---210V UN-G-F2: 47-49Hz(56-59.8Hz)
UN-G-V2-T: 0.1---1S UN-G-F2-T: 0.1---9S
Startup-T : 10-600S Restore-T: 10-600S
6.5.2 Grid ON/OFF
This function is used to start up or stop the power generation of Solis Single Phase Inverter.
Grid ON
Grid OFF
Figure 6.18 Set Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key to save the setting. Press the ESC key to return to the previous menu.
6.5.3 24H Switch
This function controls the 24H hours consumption function enable or disable.
Enable
Disable
Figure 6.19 Set 24H ON/OFF
When this is enabled, the inverter LCD will still be alive at night with the power
LED light on.
If the grid is in malfunction at night, the system can’t recover even after the grid is back to normal but the consumption data will still be recorded in the meter.
Until the sunrise, the system will start to work again while the meter data can be uploaded to the Solis monitoring system to calibrate the load consumption data.
.33.
6. Operation
6.5.4 Clear Energy
Clear Energy can reset the history yield of inverter
These two functions are applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.
6.5.5 Reset Password
This function is used to set the new password for menu “Advanced info.” and “Advanced information” (see Figure 6.20).
YES=<ENT> NO=<ESC>
Password: 0000
Figure 6.20 Reset password
Enter the right password before set new password. Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting.
Press the ESC key to return to the previous menu.
6.5.6 Power Control
Active and reactive power can be set through power setting button.
There are 5 item for this sub menu:
1. Set output power 2. Set Reactive Power 3. Out_P With Restore
4. Rea_P With Restore 5. Select PF Curve
This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
6.5.7 Calibrate Energy
Maintenance or replacement could clear or cause a different value of total energy. Use this function could allow user to revise the value of total energy to the same value as before. If the monitoring website is used the data will be synchronous with this setting automatically.
YES=<ENT> NO=<ESC>
Energy:0000000kWh
Figure 6.21 Calibrate energy
Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the
ENTER key to execute the setting. Press the ESC key to return to the previous menu.
.34.
6. Operation
6.5.8 Special Settings
This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.
6.5.9 STD. Mode Settings
There are 5 setting under STD. Mode settings.
1. Working mode 2. Power Rate limit 3. Freq. Derate set 4. 10mins OV-G-V set.
5.Initial Settings
This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.
6.5.9.1 Enable logic interface settings
When select G98 or G99 standard to use the logic interface function, please follow below settings to enable the DRM . DRM default setting is “OFF” , if DRM set “ON”, but the logic interface un-connected to the switch or the switch is open, the inverter HMI will display “Limit by DRM” and the inverter output power will be limited to zero.
1. Select Initial Settings
2. Select DRM and set it “ ON ”
6.5.10 Restore Settings
Restore setting could set all item in 6.5.8 special setting to default.
The screen shows as below :
Are you sure?
YES=<ENT> NO=<ESC>
Figure 6.22 Restore Settings
Press the Enter key to save the setting after setting grid off .
Press the ESC key to return the previous mean .
6.5.11 HMI Update
This function is used for update the LCD program.
This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
.35.
6. Operation
6.5.12 Internal EPM Set
This section includes two functions related to the smart meter or smart sensor.
Please refer to section 4.3.7 or 4.3.8 for detailed connection diagrams.
Function 1: Internal Export Power Management Function
Inverters can work with a smart meter OR a smart sensor to dynamically limit the export power of the system. Zero injection can be achieved.
Smart meter can be installed either on the grid side OR the load side.
Smart sensor can only be installed on the grid side.
Function 2: 24 Hour Consumption Monitoring Function
Only applicable if Solis monitoring system is used.
Inverters can work with a smart meter to monitor the load consumption data for the whole day and the data will be displayed on the Solis monitoring system.
Smart meter can only be installed on the grid side.
Please refer to below instructions for different user scenarios.
Scenario 1. Only Function 1 is required
Using a Smart Meter:
Step 1: Refer to Section 4.3.7 to connect the smart meter on the grid side or
load side.
Step 2: Select the corresponding meter model in Section 6.5.12.4
Step 3: Select the Section 6.5.12.1 Mode Select as Option 2(Meter in Load)
or Option 3 (Meter in Grid) accordingly.
Step 4: Configure the Section 6.5.12.2 to set the allowed backflow power.
Step 5: Configure the Section 6.5.12.3 to enable the failsafe function (If necessary).
Using a Smart Sensor:
Step 1: Refer to Section 4.3.8 to connect the smart sensor on the grid side.
Step 2: Select the Section 6.5.12.1 Mode Select as Option 5(Current Sensor).
Step 3: Configure the "CT Sampling Ratio" and "CT Link Test" if necessary.
Step 4: Configure the Section 6.5.12.2 to set the allowed backflow power.
Step 5: Configure the Section 6.5.12.3 to enable the failsafe function (If necessary).
.36.
6. Operation
Scenario 2. Both Function 1 and 2 are required
Using a Smart Meter:
Step 1: Refer to Section 4.3.7 to connect the smart meter on the grid side.
Step 2: Select the corresponding meter model in Section 6.5.12.4
Step 3: Select the Section 6.5.11.1 Mode Select as Option 3(Meter in Grid).
Step 4: Select the Section 6.5.3 24H Switch as "Enable".
Step 5: Configure the Section 6.5.11.2 to set the allowed backflow power.
Step 6: Configure the Section 6.5.11.3 to enable the failsafe function (If necessary).
Step 7: Configure the Solis monitoring system (Please refer to the manual of
monitoring device)
If customer does not want to enable the export power control function, please change the "backflow power" to the max output power of the inverter in Step 5
OR simply select the mode as "consumption monitor" in Step 3 and skip Step 5-6.
Select EPM Settings from the Main Menu to access the following options:
1. Mode Select 2. Set Backflow Power 3. Fail safe ON/OFF 4. Meter Select
6.5.12.1 Mode Select
There are 5 options in this section:
1. EPM OFF 2. Meter in Load 3. Meter in Grid 4.Consumption Monitor 5. Current sensor
EPM OFF: Functions are disabled
Meter in Load: Solis Smart Meter is connected in the load branch circuit.
Meter in Grid: Solis Smart Meter is connected in the grid connection point (The backflow power is default as 0W).
Consumption Monitor: Solis Smart Meter is connected in the grid connection point (The backflow power setting is not applicable).
Current sensor: Solis Smart Sensor is connected in the grid connection point.
.37.
6. Operation
.38.
For option 5 (Current sensor), there are several sub-settings available when "Current sensor" is selected.
· CT Sampling Ratio
This setting is used to define the CT sampling ratio if customer didn't use the default CT supplied by Solis.
The default CT is 100A:33.33mA (Default ratio is 3000:1)
-> CT Sampling Ratio YES=<ENT> NO=<ESC>
Ratio:3000:1
· CT Link Test
This setting is used to check the direction of the CT (Not complusory)
The result is only valid if the following conditions are met.
1. Load power is over 500W.
2. Inverter is set as "Grid OFF" in the LCD.
3. CT is connected to the inverter CT port and the CT is placed at the grid side.
CT Link State
Correct
There are 3 states in the CT Link Test
"Error" means the CT is installed in the wrong direction, please change it.
"Can not judge" means the load power is too small and the result is not credible.
"Correct" means the CT is installed correctly.
Inverter
CT Input L N
CT
×
×
CT
L N
Load
CT
√
L
N
Grid
6. Operation
6.5.12.2 Backflow Power
The setting is used to define the allowed export power into the grid.
->Set Backflow Power YES=<ENT> NO=<ESC>
Power:-00000W
Figure 6.
23 Set the backflow p o wer
NOTE:
Positive values indicate the amount of power is allowed to export to the grid.
Negative values indicate a more strict control to limit the export power in advance thus ensuring exact no power is feeding into the grid.
6.5.12.3 Fail safe ON/OFF
This setting is used to give out an alarm (stop inverter generation as well) when the CT/Meter connection is lost during operation.
It can prevent potential backflow power into the grid when the system loses control.
YES=<ENT> NO=<ESC>
Fail Safe Set:ON
Figure 6.24 Set the Fail Safe ON/OFF
It is only mandatory to turn on this function when the inverter is installed in UK due to the
G100 regulation.
For other regions,customers can enable or disable the function as they desire.
NOTE:
When the failsafe function is ON and CT/Meter is disconnected somehow, the inverter will stop generation and give "Failsafe" alarm on the LCD.
When the failsafe function is OFF and CT/Meter is disconnected somehow, the inverter will keep the output power as the last moment when the CT/Meter is still connected. After a restart, the inverter will output at full power without limit.
.39.
6. Operation
6.5.12.4 Meter Select
The setting is used to define the correct meter that is connected to the inverter.
->1PH Meter
3PH Meter
->DDSD1352-C
ACR10RD16TE
Figure 6.
25 Meter Select
For Solis single phase inverters, please select "1PH Meter" and then select the corresponding meter model.
6.5.13 External EPM Set
This setting should only be turned on when Solis external EPM device is used.
Two options are available : 5G-EPM and Others-EPM.
->5G-EPM
Others-EPM
Figure 6.26
5G-EPM Failsafe Option should be turned ON when 5G series EPM device is used
Others-EPM Failsafe Option should be turned ON when 2G series EPM device is used
Only one option can be activated each time.
6.5.14 Restart HMI
The function is used for restart the HMI .
This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
6.5.15 Debug Parameter
This function is used for manufacturer maintenance personnel only.
6. Operation
6.5.16 DSP Update
The function is used for update the DSP .
This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
6.5.17 Power Parameter
This function is used for calibrate inverter output energy. It will not impact the energy count for inverter with RGM.
The screen shows :
YES=<ENT> NO=<ESC>
Power para : 1 .
000
Figure 6.27 Power Rate Limit
Press the Down key to move the cursor .
Press the Up key to change the digit .
Please press the Enter to save the setting and press the ESC key to return to the previous menu .
This setting is used for grid operator, don't change setting under this manual.
.40.
.41.
7. Maintenance
7.Maintenance
Solis 4G Mini Single Phase Inverter does not require any regular maintenance.
However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. The dust can be removed with a soft brush.
CAUTION:
Do not touch the inverter's surface when it is operating. Some parts of the inverter may be hot and cause burns. Turn off the inverter (refer to Section 5.2) and wait for a cool-down period before before any maintenance or cleaning operation.
The LCD and the LED status indicator lights can be cleaned with a damp cloth if they are too dirty to be read.
NOTE:
Never use any solvents, abrasives or corrosive materials to clean the inverter.
8. Troubleshooting
The inverter is designed in accordance with the most important international grid-tied standards and safety and electromagnetic compatibility requirements. Before delivering to the customer, the inverter has been subjected to several tests to ensure its optimal operation and reliability.
In case of failure, the LCD screen will display an alarm message. In this case, the inverter may stop feeding into the grid. The failure descriptions and their corresponding alarm messages are listed in Table 8.1:
8. Trouble Shooting
Alarm Message
No power
Failure description
Inverter no power on LCD
LCD show initializing all the time can not start-up
OV-G-V01/02/03/04 Over grid voltage
UN-G-V01/02
OV-G-F01/02
UN-G-F01/02
Reverse-GRID
Reverse-DC
NO-GRID
OV-DC01/02/03/04
OV-BUS
UN-BUS01/02
GRID-INTF01/02
OV-G-I
IGBT-OV-I
DC-INTF
OV-DCA-I
IGFOL-F
IG-AD
Under grid voltage
Over grid frequency
Under grid frequency
Wrong AC polarity
Reverse DC polarity
No grid voltage
Over DC voltage
Over DC bus voltage
Under DC bus voltage
Grid interference
Over grid current
Over IGBT current
DC input overcurrent
Grid current tracking fail
Grid current sampling fail
OV-TEM
INI-FAULT
DSP-B-FAULT
12Power-FAULT
PV ISO-PRO
01/02
Solution
1.Check PV input connections
2.Check DC input voltage
(single phase >120V, three phase >350V)
3.Check if PV+/ is reversed
1.Check if the connector on main
board or power board are fixed.
2.Check if the DSP connector to
power board are fixed.
1.Resistant of AC cable is too high.
Change bigger size grid cable
2.Adjust the protection limit if it’s
allowed by electrical company.
1.Use user define function to adjust the
protection limit if it’s allowed by
electrical company.
1. Check the polarity of AC connector.
1. Check the polarity of DC connector.
1.Check connections and grid switch.
2.Check the grid voltage inside inverter
terminal.
1.Reduce the module number in series
1.Check inverter inductor connection
2.Check driver connection
1.Restart inverter
2.Change power board
1.Restart inverter
2.Identify and remove the string to the fault MPPT
2.Change power board
1.Restart inverter or contact installer.
Over Temperature
1.Check inverter surrounding ventilation.
2.Check if there’s sunshine direct on
inverter in hot weather.
Initialization system fault
Comm. failure between main and slave DSP
12V power supply fault
1.Restart inverter or contact installer.
PV isolation protection
1.Remove all DC input, reconnect and
restart inverter one by one.
2.Identify which string cause the fault and
check the isolation of the string.
.43.
.42.
8. Trouble Shooting
Alarm Message
ILeak-PRO
01/02/03/04
RelayChk-FAIL
DCinj-FAULT
Screen OFF with DC applied
Failure description
Leakage current protection
Relay check fail
High DC injection current
Inverter internally damaged
Solution
1.Check AC and DC connection
2.Check inverter inside cable connection.
1.Restart inverter or contact installer.
1.Restart inverter or contact installer.
1.Do not turn off the DC switches as it will
damage the inverter.
2.Please wait for the solar irradiance reduces
and confirm the string current is less than
0.5A with a clip-on ammeter and then turn
off the DC switches.
3.Please note that any damages due to wrong
operations are not covered in the device
warranty.
Table 8.1 Fault message and description
NOTE:
If the inverter displays any alarm message as listed in Table 8.1; please turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5 minutes before restarting it (refer to Section 5.1 to start your inverter). If the failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Solis 4G Mini Single Phase Inverter;
2. The distributor/dealer of Solis 4G Mini Single Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings
, etc.);
6. Your contact details.
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
9. Specifications
Solis-mini-700-4G
600
200
60
50...500
11
17.2
1/1
700
800
800
1/N/PE, 220/230
3.2/3.0
0.8leading~0.8lagging [1]
<3%
50/60
45...55 or 55...65
97.2%
96.5%
310W*373H*160D (mm)
7.4kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
.45.
.44.
.46.
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
Solis-mini-1000-4G
600
200
60
50...500
11
17.2
1/1
1000
1100
1100
1/N/PE, 220/230
4.5/4.3
0.8leading~0.8lagging [1]
<3%
50/60
45...55 or 55...65
97.2%
96.5%
310W*373H*160D (mm)
7.4kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
Solis-mini-1500-4G
600
200
60
50...500
11
17.2
1/1
1500
1700
1700
1/N/PE, 220/230
6.8/6.5
0.8leading~0.8lagging [1]
<3%
50/60
45...55 or 55...65
97.2%
96.5%
310W*373H*160D (mm)
7.4kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
.47.
.48.
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
Solis-mini-2000-4G
600
330
90
80...500
11
17.2
1/1
2000
2200
2200
1/N/PE, 220/230
9.1/8.7
0.8leading~0.8lagging [1]
<3%
50/60
45...55 or 55...65
97.2%
96.5%
310W*373H*160D (mm)
7.4kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
Solis-mini-2500-4G
600
330
90
80...500
11
17.2
1/1
2500
2800
2800
1/N/PE, 220/230
11.4/10.9
0.8leading~0.8lagging [1]
<3%
50/60
45...55 or 55...65
97.5%
96.8%
310W*373H*160D (mm)
7.7kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
.49.
.50.
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
Solis-mini-3000-4G
600
330
90
80...500
11
17.2
1/1
3000
3300
3300
1/N/PE, 220/230
13.6/13
0.8leading~0.8lagging [1]
<3%
50/60
45...55 or 55...65
97.5%
96.8%
310W*373H*160D (mm)
7.7kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
Communication connections
Warranty Terms
Solis-mini-3600-4G
600
330
90
80...500
19
30
1/2
3600
3600
3600
1/N/PE, 220/230
16
0.8leading~0.8lagging
<3%
50/60
45...55 or 55...65
97.5%
96.8%
310W*373H*160D (mm)
7.7kg
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
.51.
.52.
Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
Solis-mini-1000-4G-LV
600
200
90
50...500
11
17.2
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
1/1
1000
1100
1100
1/N/PE, 101/120/127
8.3
0.8leading~0.8lagging
THDi (at rated output power)
Rated grid frequency (Hertz)
Operating frequency range (Hertz)
Max.efficiency
EU efficiency
Dimensions
Weight
Topology
<3%
50/60
45...55 or 55...65
97.2%
96.5%
310W*373H*160D (mm)
7.7kg
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission (typical)
Cooling concept
Max.operation altitude
Transformerless
< 1 W(Night)
25 ℃ ...
+60 ℃
0~100%
IP65
<20 dBA
Natural convection
Grid connection standard
Safety/EMC standard
DC connection
AC connection
Display
4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1,
UTE C15-712-1, NRS 097-1-2, G98, G99,
EN 50549-1/-2, RD 1699, UNE 206006,
UNE 206007-1, IEC 61727
IEC 62109-1/-2, IEC 62116 ,EN 61000-6-1/-2/-3/-4
MC4 connector
Quick connection plug
LCD, 2×20 Z.
Communication connections
Warranty Terms
RS485, Optional: Wi-Fi, GPRS
5 Years (Extend to 20 Years)
[1]: For Brazil products, the certificated PF range is 0.9 leading~0.9 lagging, but the actual range is 0.8 leading~0.8lagging.
advertisement