AMS USB Fieldbus Interface Rev 4 Owner's Manual
AMS USB Fieldbus Interface Rev 4 empowers you with the tools to seamlessly configure, monitor, and troubleshoot FOUNDATION fieldbus (FF) devices. Its capabilities include:
-
Easy Device Interaction: Connect to fieldbus devices directly through your computer's USB port, enabling convenient configuration and diagnostics.
-
Versatile Power Options: Choose between two power modes – external power or interface-supplied power – to suit your specific needs.
-
Comprehensive Device Support: Compatible with all FF devices, allowing you to work with a wide range of field instruments.
-
Convenient Device Setup: Effortlessly set device addresses, modify tags, and perform other essential configuration tasks using the intuitive USB Fieldbus Interface Configuration utility.
Werbung
Werbung
USB Fieldbus Interface
User's Manual
User's Manual
AW7060MNL, Rev 4
February 2022
User's Manual February 2022
Copyright and trademark information
Copyright
© Emerson, 2022. All rights reserved. Printed in the USA.
The contents of this publication are presented for informational purposes only, and while diligent efforts were made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Trademarks
The Emerson logo is a trademark and service mark of Emerson Electric Co.
AMS is a mark of one of the Emerson group of companies.
FOUNDATION ™ is a mark of the FieldComm Group of Austin, Texas, USA.
Microsoft and Windows are registered trademarks of the Microsoft Corporation in the
United States and/or other countries.
PACTware is a trademark of PACTware Consortium e.V.
All other marks are property of their respective owners.
Contents
Introduction...................................................3
USB Fieldbus Interface....................................5
Software installation and device setup........... 9
USB Fieldbus Interface Configuration utility.....
Using with AMS Device Manager..................22
Using with an FDT Frame Application........... 30
Troubleshooting.......................................... 41
Approvals and certifications.........................45
Specifications...............................................47
Waste disposal.............................................49
Remove pre-release driver versions on a
Windows 10 operating system.....................51
2
February 2022
1
User's Manual
Introduction
This manual guides you in using the USB Fieldbus Interface to power and/or configure fieldbus devices. Included here are basic setup, configuration, and troubleshooting information, as well as guidelines on how to use the interface with AMS Device Manager and with a third-party FDT Frame
Application.
This USB Fieldbus Interface User's Manual contains the following information:
• Chapter 1: Introduction – contains safety messages and information about this manual.
• Chapter 2: USB Fieldbus Interface – contains information about the interface, its parts, usage, and features.
• Chapter 3: Software installation and device setup – contains system requirements, software installation instructions, and device setup information.
• Chapter 4: USB Fieldbus Interface Configuration utility – contains information on how to use the utility to power, commission, and/or configure some parameters of fieldbus devices, including device address and tag.
• Chapter 5: Using with AMS Device Manager – contains setup information and instructions in using the interface with AMS Device
Manager to configure fieldbus devices.
• Chapter 6: Using with an FDT Frame Application – contains setup information and instructions in using the interface with an FDT Frame
Application to configure fieldbus devices.
• Chapter 7: Troubleshooting – contains solutions to the most common operating problems.
• Appendix A: Approvals and certifications – contains certifications and approval information.
• Appendix B: Specifications – contains specifications such as operating temperature, software, electrical information, and environmental considerations.
• Appendix C: Waste disposal – contains disposal guidelines.
• Appendix D: Remove pre-release driver versions on a Windows 10 operating system – contains instructions on how to remove previous driver versions.
User's Manual 3
4
User's Manual February 2022
1.1
Safety message
WARNING
Do not connect the USB Fieldbus Interface to a live segment (with an active
DCS Host and power supply attached) if the power indicator light on the interface is amber in color. Doing so can disrupt communications and may compromise automation safety.
February 2022 User's Manual
2 USB Fieldbus Interface
2.1
Overview
The USB Fieldbus Interface enables two-way communication between a computer and fieldbus devices. Its primary function is to allow the setup, configuration, monitoring, and troubleshooting of fieldbus devices at any valid FF address through a computer.
The interface is fully compatible with all FOUNDATION fieldbus (FF) devices and is always configured as a "visitor."
It is particularly useful in these plant scenarios:
• Workbench setup and troubleshooting of fieldbus devices
• With a laptop in the field to configure, commission, decommission, set device address, or troubleshoot fieldbus devices
The USB Fieldbus Interface comes with a USB cable, lead set, user's manual*, and installation CD/DVD*. The user's manual and installation CD/DVD are not included in the illustration.
Figure 2-1: Box Contents
User's Manual 5
User's Manual
2.2
Parts and function
Figure 2-2: USB Fieldbus Interface
February 2022
6
1
4
Field connection indicator
2 Power indicator light
3 USB port
Fieldbus device connection socket
Indicates the fieldbus device connection status
Indicates the power mode of the interface
Enables USB connection
Enables fieldbus device or segment connection
* See the Indicator light scenarios table.
February 2022 User's Manual
Table 2-1: Indicator light scenarios
Power indicator light
Field connection indicator light
Green
Amber
Off
Green
Off
Amber
Amber
Amber
Green
Green
Off
Off
Green
Red
Off
Amber
Scenarios
Normal scenarios
The USB Fieldbus Interface is connected to an externally powered segment and is able to communicate.
The USB Fieldbus Interface is providing power to a fieldbus segment and is able to communicate.
Other scenarios
The USB Fieldbus Interface is not connected to a powered computer.
-OR-
The USB Fieldbus Interface is connected to a computer but the computer power is off.
-OR-
The USB FF HSE Server is not running on the connected computer.
The USB Fieldbus Interface is not connected to a powered segment.
-OR-
The USB Fieldbus Interface is connected to a powered segment with the wrong polarity.
The USB Fieldbus Interface is connected normally to a powered segment but the USB FF HSE Server is not running.
The USB Fieldbus Interface is providing power but a short circuit has been detected on the field connection.
The USB Fieldbus Interface is providing power and connected to an already powered fieldbus segment with reverse polarity.
The USB Fieldbus Interface is providing power to a fieldbus segment and the load on that segment has exceeded its limit.
User's Manual 7
8
User's Manual February 2022
2.3
Power modes
The USB Fieldbus Interface has two power modes:
• Mode 1 - The interface does not supply power to the connected fieldbus device or segment. The fieldbus device or segment is powered by an external source.
Mode 1 is the default.
• Mode 2 - The interface powers the connected fieldbus device or segment and no external power is needed.
In Mode 2, it can provide current of up to 85 mA (typically sufficient for three or four fieldbus devices on the same segment).
You can configure Mode 2 using the USB Fieldbus Interface
WARNING
Choose only one power mode. Never attempt to use two power sources at the same time. Doing so can disrupt communications and may compromise automation safety.
February 2022 User's Manual
3 Software installation and device setup
Perform software installation and device setup in the following order:
1.
Install the USB Fieldbus Interface Configuration utility.
This allows you to configure the USB Fieldbus Interface and connected fieldbus devices.
2.
Install the Emerson DTM Library.
This allows you to use DTMs associated with Emerson devices through an FDT Frame Application.
Note
Device DTMs are usually acquired from device suppliers. Contact your device supplier if you have a non-Emerson device and install the appropriate third-party DTM library.
3.
Set up and configure connected fieldbus devices.
3.1
System requirements
Supported operating systems
Windows 10
Hard disk space
500MB or more
Hardware
USB 1.1, 2.0, or 3.x port
3.2
Install the USB Fieldbus Interface Configuration utility
Notes
• Do not connect the USB Fieldbus Interface to the computer or to a fieldbus device or segment until software installation is complete.
• You may be prompted to determine the operating system and the
Windows version (32-bit or 64-bit) running on your computer. Keep this information handy.
• For installation purposes, the user must use the Administrator account.
Procedure
1. Insert the USB Fieldbus Interface installation CD/DVD.
Software and driver installation should start automatically.
User's Manual 9
User's Manual February 2022
If AutoRun is not enabled, double-click setup.exe
.
2. Follow the prompts on the installation window.
3. Click Finish .
3.3
Install the Emerson DTM Library
Procedure
1. Insert the USB Fieldbus Interface installation CD/DVD.
2. Navigate to the Emerson DTM Library folder.
The DTM library folder is typically named "Emerson Process
Management FF Device DTM Library v1.x.x".
3. Double-click Setup → Setup.exe
.
4. Click Next and follow the prompts on the installation window.
Figure 3-1: Emerson DTM Library installation
10
5. Click Close .
February 2022 User's Manual
3.4
Setup and connection
Note
Install the USB Fieldbus Interface Configuration utility first before setting up and connecting the USB Fieldbus Interface. For more information, see
Install the USB Fieldbus Interface Configuration utility
Procedure
1. Connect the USB Fieldbus Interface to the computer using the USB cable provided.
USB driver installation should start automatically.
2. Connect the interface to a fieldbus device or to a fieldbus segment using the field leads.
WARNING
Do not proceed to the next step if you are connecting to a live
(powered) segment. Providing additional power source to an already powered segment can disrupt communications and may compromise automation safety.
3. Power the connected fieldbus device or segment.
Connect the fieldbus device or the unpowered segment to an external power source (Mode 1), or provide power using the USB
Fieldbus Interface Configuration utility (Mode 2). For more
information on the power modes, see Power modes
.
User's Manual 11
User's Manual
Figure 3-2: Sample benchtop connection
February 2022
3.5
Connect to a live fieldbus segment
Warning
Do not use the Supply Power option on the USB Fieldbus Interface
Configuration utility when connecting to a live segment. Doing so can disrupt communications and may compromise automation safety.
Procedure
1. Make sure the USB Fieldbus Interface is connected to the computer and that all software and drivers are installed.
2. Plug one end of the field lead to the fieldbus device connection socket of the interface and connect the other end to the live fieldbus segment.
Notes
• The USB Fieldbus Interface draws current of 10 mA from the segment. Make sure the segment has enough power and has the capacity to provide this additional current.
• Make sure the lead set is connected to the live fieldbus segment with the correct polarity.
• Changing the device tag/address is only allowed when the USB fieldbus Interface is acting as Link Active Scheduler (LAS).
12
February 2022 User's Manual
• When a fieldbus device is acting as a LAS, you can cycle power to the device, or remove and replace the fieldbus device from the segment to make the USB Fieldbus interface act as the LAS. You can check the LAS address next to the segment info to find out which device is the LAS.
User's Manual 13
User's Manual February 2022
4 USB Fieldbus Interface Configuration utility
4.1
Launch the USB Fieldbus Interface Configuration utility
Procedure
Click Start → All Programs → Emerson Process Management → USB
Fieldbus Interface .
Note
If no fieldbus device is detected after 35 seconds, this dialog is displayed.
Click OK to continue.
Figure 4-1: No device detected dialog
A connected fieldbus device or segment has to be powered by an external power source or by the USB Fieldbus Interface Configuration utility for it to
be detected. For more information, see Fieldbus device not detected in USB
Fieldbus Interface Configuration utility
.
4.2
Start or stop the USB FF HSE Server manually
The USB FF HSE Server automatically starts when you launch the USB
Fieldbus Interface Configuration utility. It is typically not necessary to start or stop the USB FF HSE Server manually.
Procedure
1. Launch the USB Fieldbus Interface Configuration utility.
2. Click Start Server or Stop Server .
14
February 2022
Figure 4-2: Start Server/Stop Server
User's Manual
Note
The USB FF HSE Server should be running to use the USB Fieldbus
Interface Configuration utility to power or configure a fieldbus device or segment.
User's Manual 15
User's Manual February 2022
4.3
Power fieldbus device with the USB Fieldbus Interface
Configuration utility
You can power a fieldbus device or segment by connecting it to an external power source or by using the USB Fieldbus Interface Configuration utility.
Note
You can also power a fieldbus device or segment by connecting it to an external power source.
Procedure
1. Launch the USB Fieldbus Interface Configuration utility.
2. Select the Supply Power check box.
Note
The USB Fieldbus Interface is only capable of providing an output current of up to 85 mA. Typically, you should not attempt to connect more than three or four fieldbus devices on the same segment when using the Supply Power option.
Figure 4-3: Supply Power option
16
WARNING
Do not use the Supply Power option on a live (already powered) segment. Doing so can disrupt communications and may compromise automation safety.
February 2022 User's Manual
3. Select Yes to acknowledge the warning and restart the USB FF HSE
Server.
4.4
Set Fieldbus Device Permanent Address/Tag
Device Address can be set to permanent, which commissions the device.
Device Tag can be set and cleared.
Notes
• You need to commission fieldbus devices first before you can use them with AMS Device Manager or with an FDT Frame Application.
• The USB Fieldbus Interface must be acting as the Link Master to commission or decommission.
Procedure
1. Launch the USB Fieldbus Interface Configuration utility.
2. Double-click the Fieldbus device icon you want to configure. A device screen is displayed.
Note
A connected fieldbus device or segment should be powered by an external power source or by the USB Fieldbus Interface Configuration utility for it to be detected.
3. Optionally, select a permanent device address from 17 to 40 or from
223 to 247. Otherwise, the first available address is assigned.
Note
The utility only accepts device addresses in the range of 17 through
40 and the range of 223 through 247.
4. Optionally, enter a device tag or clear a device tag.
5. Click Apply to accept the new tag. Or, click Set Permanent Address and Tag to accept both the permanent device address and the tag.
User's Manual 17
User's Manual
Figure 4-4: Set Permanent Address and Tag
February 2022
Note
The set permanent address and tag process takes about 1 to 2 minutes to complete.
6. Repeat steps 2 through 5 for each device on which you want to set a permanent address.
4.5
Set Fieldbus Device Default Address
Device address can be set to a default address, which decommissions the device.
Note
Fieldbus devices on a live segment cannot be decommissioned.
Procedure
1. Launch the USB Fieldbus Interface Configuration utility.
2. Double-click the Fieldbus device icon you want to configure. A device screen is displayed.
Note
A connected fieldbus device or segment should be powered by an external power source or by the USB Fieldbus Interface Configuration utility for it to be detected.
3. Click Set Default Address .
18
February 2022
Figure 4-5: Set Default Address
User's Manual
4. If the device was set to a permanent address by a different host, it is not recommended that you set the device to a Default Address. If you click the Set Default Address button, you will be asked to confirm if you really want to set the device to a default address.
• If you select Yes , the device will be set to a default address.
• If you select No , the operation will be canceled.
5. Repeat steps 2 through 4 for each device you want to set to a default address.
4.6
Change the device class
A connected fieldbus device can be assigned as a Link Master (LM) or as a basic device. A Link Master contains the LAS functionality that controls communications on a fieldbus link or segment.
Procedure
1. Launch the USB Fieldbus Interface Configuration utility.
2. Double-click the Fieldbus device icon you want to configure. A device screen is displayed.
Note
A connected fieldbus device or segment should be powered by an external power source or by the USB Fieldbus Interface Configuration utility for it to be detected.
User's Manual 19
User's Manual February 2022
3. If Device Class is not displayed, click Read to identify if the fieldbus device is a Link Master or a basic device.
Note
Only the device class of a fieldbus device at a permanent address can be identified. For more information on setting a permanent device
address, see Set Fieldbus Device Permanent Address/Tag
.
Figure 4-6: Identify the device class
4. Switch to Basic or Link Master from the drop-down menu and click
Apply .
20
February 2022
Figure 4-7: Change the device class
User's Manual
5. Click Yes to acknowledge the restart of the device.
6. Click OK to continue. The operation is complete when the Apply button is grayed out.
Note
Changing the device class takes about 1 minute to complete.
User's Manual 21
User's Manual February 2022
5 Using with AMS Device Manager
AMS Device Manager provides a single application for predictive diagnostics, documentation, calibration management, and device configuration. Using
AMS Device Manager gives you better visibility into the assets in your plant, resulting in faster startup and increased availability through more costeffective maintenance and improved asset performance.
Contact your Emerson Sales/Support representative for more information on AMS Device Manager.
5.1
Add a network component in AMS Device Manager
An FF HSE network component is required to use the USB Fieldbus Interface with AMS Device Manager.
Notes
• If there is an existing FF HSE network configured for another fieldbus device, you do not need to add a new FF HSE network component.
• You must have an updated license file that includes an HSE license. The
HSE license enables you to add an FF HSE network component in AMS
Device Manager.
If you do not yet have an HSE license, contact your Emerson sales representative and place an order for part number AW7060HSE.
Procedure
1. Click Start → All Programs → AMS Device Manager → Network
Configuration to open the AMS Device Manager Network
Configuration utility.
2. Click Add .
22
February 2022
Figure 5-1: Add a network component
User's Manual
User's Manual
3. Select the FF HSE Network component, and click Install .
23
User's Manual
Figure 5-2: Install an FF HSE network component
February 2022
4. Click Next .
5. Enter a name for the FF HSE network, and click Next .
24
February 2022
Figure 5-3: Enter a network name
User's Manual
User's Manual
6. Choose to automatically discover FF HSE linking devices or manually configure IP addresses for FF HSE linking devices.
25
User's Manual
Figure 5-4: Configure the network connection
February 2022
26
Notes
• Choosing the PC NIC address in the Primary HSE NIC Address field displays the USB Fieldbus Interface and any local FF HSE interfaces on the network in the AMS Device Manager hierarchy.
• Choosing the localhost address (127.0.0.1) in the Primary HSE
NIC Address field displays only the USB Fieldbus Interface in the
AMS Device Manager hierarchy.
• Manually entering IP addresses displays manually entered FF HSE networks and the USB Fieldbus Interface in the AMS Device
Manager hierarchy.
February 2022 User's Manual
• The USB Fieldbus Interface does not support FF device alerts.
7. Click Finish .
5.2
Configure fieldbus devices in AMS Device Manager
Note
Commission fieldbus devices first in the USB Fieldbus Interface
Configuration utility before configuring them in AMS Device Manager. For more information, see
Set Fieldbus Device Permanent Address/Tag .
Procedure
1. Click Start → All Programs → AMS Device Manager → AMS Device
Manager to open AMS Device Manager.
2. From the Device Connection or Device Explorer view, right-click the
FF HSE network icon and select Rebuild Hierarchy .
The USB Fieldbus Interface icon then appears under the FF HSE network.
Figure 5-5: USB Fieldbus Interface icon in AMS Device Manager
User's Manual
3. If you are using the Device Connection View, click the sign next to the USB Fieldbus Interface icon to display a list of connected fieldbus devices.
27
User's Manual February 2022
4. If necessary, right-click the USB Fieldbus Interface icon and then scan new devices.
Scanning synchronizes the AMS Device Manager database with connected live devices.
5. Right-click the fieldbus device you want to configure and select from the context menus.
Figure 5-6: Fieldbus device context menus
28
Configure
Compare
Service Tools or
Device Diagnostics
Overview or
Process Variables
Displays configuration parameters that define the physical attributes and operating characteristics of the device.
Lets you compare two configurations of the device.
Displays alert conditions. These include hardware and software malfunctions or parameters with values beyond the device specifications.
Displays the current output from the device.
February 2022 User's Manual
For more information about the context menus and other AMS
Device Manager functions, refer to AMS Device Manager Books Online .
User's Manual 29
User's Manual February 2022
6 Using with an FDT Frame Application
You can also configure fieldbus devices using third-party FDT Frame
Applications. For the purpose of this document, PACTware is used as an example. PACTware can be downloaded from multiple sites on the Internet.
6.1
Install an FDT Frame Application
Note
Install the Communication DTM software (provided separately) and the
Emerson DTM Library first before installing an FDT Frame application. For instructions, see
Install the Emerson DTM Library
.
To be able to view DTMs associated with a device, an FDT Frame Application should be installed. Follow the manufacturer's recommended software installation instructions.
For the purpose of this document, PACTware is used.
6.2
Update the DTM library
Note
You only need to update the DTM library when a new DTM is recently added.
Procedure
1. Launch PACTware.
2. Press F3 to show the Device catalog and click Update device catalog .
Figure 6-1: Update device catalog
30
February 2022 User's Manual
3. Click Yes when prompted to create a new PACTware device catalog.
4. Close the device catalog when done.
6.3
Configure fieldbus devices in an FDT Frame Application
Notes
• Install the Communication DTM software (provided separately) and the
DTM Library first before configuring fieldbus devices in an FDT Frame
Application. For more information, see
Install the Emerson DTM Library .
• If necessary, update the DTM library. For more information, see
• Make sure the USB Fieldbus Interface and fieldbus devices are correctly set up and that the USB Fieldbus Interface Configuration utility is
installed and running. For more information, see Setup and connection
and USB Fieldbus Interface Configuration utility .
Procedure
1. Launch PACTware.
2. From the Project pane, right-click HOST PC and click Add device .
Figure 6-2: Project pane
User's Manual
Press F2 to display the Project pane if it is not already displayed.
3. Select Emerson FF HSE Server and click OK .
31
User's Manual
Figure 6-3: Add the Emerson FF HSE Server
February 2022
4. Right-click FF HSE Server on the Project pane and click Add device .
32
February 2022
Figure 6-4: FF HSE Server - Add device
User's Manual
User's Manual
5. Select Emerson USB Fieldbus Interface and click OK .
33
User's Manual
Figure 6-5: Add the Emerson USB Fieldbus Interface
February 2022
6. Right-click USB Fieldbus Interface on the Project pane and click Add device .
34
February 2022
Figure 6-6: USB Fieldbus Interface - Add device
User's Manual
User's Manual
7. Select the device you want to add then click OK .
35
User's Manual
Figure 6-7: Add device
February 2022
Only devices with DTMs available and installed appear on the list. For more information on DTM library installation, see
Repeat steps 6 and 7 if you want to add more devices to the list.
8. Right-click USB Fieldbus Interface and select Additional functions →
Edit DTM Address .
36
February 2022
Figure 6-8: Edit DTM Address
User's Manual
9. On the right pane, select the fieldbus device from the list, enter the device address in the Node ID field, and click Apply .
Figure 6-9: Enter Node ID
User's Manual
Note
The device address and Node ID should match. The device address is set and can be found in the USB Fieldbus Interface Configuration
37
User's Manual February 2022 utility. For more information on setting the device address, see
Fieldbus Device Permanent Address/Tag .
10. Right-click HOST PC and click Connect .
Figure 6-10: Connect devices
This connects all devices under the host PC. You can also opt to select each device you want connected and click Connect .
Connected devices appear in bold face type in the menu tree.
11. Right-click the fieldbus device you want to configure and click
Parameter .
38
February 2022
Figure 6-11: Parameter
User's Manual
User's Manual
This displays the various parameters you can edit for the device.
12. Configure the parameters of the device.
Note
The parameter display varies and is dependent on the device manufacturer.
39
User's Manual
Figure 6-12: Edit device parameters
February 2022
40
February 2022 User's Manual
7 Troubleshooting
7.1
Fieldbus device not responding in AMS Device Manager
To configure a fieldbus device in AMS Device Manager, you must first commission the device in the USB Fieldbus Interface Configuration utility.
For more information on commissioning a device, see
.
Uncommissioned devices are marked in AMS Device Manager with the
(non-responding device) icon and are characterized by an empty device tag or by the device default address.
Figure 7-1: Uncommissioned device in AMS Device Manager
Commissioned fieldbus devices appear with their own icons in AMS Device
Manager and are characterized by a valid permanent address or by a valid device string.
User's Manual 41
User's Manual
Figure 7-2: Commissioned device in AMS Device Manager
February 2022
7.2
Fieldbus device not detected in USB Fieldbus Interface
Configuration utility
The USB Fieldbus Interface Configuration utility immediately detects connected fieldbus devices. If 35 seconds have elapsed and no device is detected, the following dialog is displayed.
Figure 7-3: No device detected dialog
42
February 2022 User's Manual
Procedure
Click OK and check for the following:
• Make sure the fieldbus device or segment is powered either by an external source or by the USB Fieldbus Interface. For more information, see
• Make sure drivers are installed and that the hardware is ready for use.
• Check that there are no loose connections and that the USB cable does not exceed 2 meters in length.
• Make sure the USB FF HSE Server is running.
7.3
Cannot edit device parameters in FDT Frame Application
Figure 7-4: Cannot edit device parameters in PACTware
• Check the Node ID in PACTware and the Device Address in the USB
Fieldbus Interface Configuration utility. The Node ID and Device Address should match. You may need to manually enter the Node ID in
PACTware. For more information on entering the Node ID, see
Configure fieldbus devices in an FDT Frame Application
.
• Update the DTM library. If a new DTM is added, you may need to update the DTM library. For more information, see
User's Manual 43
User's Manual February 2022
• Check physical connections. Make sure all devices are properly connected and have access to a power source. For more information, see
.
•
Commission the fieldbus device. For more information, see Set Fieldbus
.
44
February 2022 User's Manual
A Approvals and certifications
Fieldbus Foundation Communication
FF Physical Layer Specification (IEC 61158-2)
FF Physical Layer Conformance Test (FF830)
CE
EN 61326-1-2006, Radiated Emissions Class B, Basic Immunity Test
Requirements.
ETL (US and Canada)
Conforms to ANSI/UL STD 60950-1; Certified to CAN/CSA STD C22.2 NO.
60950-1.
IC
This Class B digital apparatus complies with Canadian ICES-003, Issue
4:2004.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du
Canada.
FCC
This device complies with Part 15 Subpart B of the FCC Rules. Operation is subject to the following conditions:
47 CFR, Part 15:2009, §15.107, §15.109, Class B
Any modifications made to this device that are not approved by Emerson may void the authority granted to the user by the FCC to operate this equipment.
User's Manual 45
User's Manual February 2022
46
February 2022
B Specifications
Software
Supported operating systems
USB 1.1 and USB 2.0 interface
Application software
AMS Device Manager
License
AMS Device Manager HSE license
Electrical
Windows 10
Drivers included
Version 11.5 or later
Part number AW7060HSE
Power consumption (Mode 1)
Power consumption (Mode 2)
≤ 0.2 W at 85 mA output current ≤ 2.5 W at 50 mA output current ≤ 1.7 W
Power supply to a fieldbus segment
(in Mode 2)
Environmental
85 mA at 10V
Operating temperature
Storage temperature
Storage humidity
-20 °C to 60 °C (-4 °F to 140 °F)
-40 °C to 85 °C (-40 °F to 185 °F)
0 to 95% relative humidity
User's Manual
User's Manual 47
User's Manual February 2022
48
February 2022
C
User's Manual
Waste disposal
Products with the following label comply with the Waste Electrical and
Electronic Equipment (WEEE) directive, 2002/96/EC, which applies to
European Union (EU) member states only.
The label indicates this product should be recycled and not treated as household waste. Customers in EU member states should contact their
Emerson sales representative for information on discarding any part of the
USB Fieldbus Interface.
For customers in all other world areas, if it is necessary to discard any part of the USB Fieldbus Interface, follow the waste disposal regulations applicable in your location.
User's Manual 49
User's Manual February 2022
50
February 2022 User's Manual
D Remove pre-release driver versions on a
Windows 10 operating system
Uninstall the USB drivers using Windows Device Manager:
Procedure
1. Launch Windows Device Manager ( Start → Run , type devmgmt.msc
, or device manager, and click on the found item).
2. Expand Ports (COM & LPT) .
3. Connect the USB Fieldbus Interface to the computer through the USB port and wait a few seconds to see if 770 Fieldbus Interface
(COMxx) appears on the list.
4. Right-click 770 Fieldbus Interface (COMxx) , and select Uninstall .
5. Click OK to confirm the driver removal.
6. Expand Universal Serial Bus controllers , right-click 770 Fieldbus
Interface , and select Uninstall .
7. Click OK to confirm the driver removal.
User's Manual 51
User's Manual February 2022
52
February 2022
Index
User's Manual
A
AMS Device Manager adding network component
using to configure fieldbus devices
C change the device class
commission fieldbus devices
configure fieldbus devices using AMS Device Manager
using PACTware
connect to live fieldbus segment
contents of box
D decommission fieldbus devices
device class, changing
drivers automatic installation
DTM library, installation
F features
FF HSE network component adding
field connection indicator light status
fieldbus device basic device
cannot edit device parameters
changing device class
commissioning
configuring, using AMS Device
Manager
configuring, using PACTware
decommissioning
Link Master
fieldbus device (continued) live segment connection and setup
not detected in utility, troubleshooting
not responding in AMS Device
Manager, troubleshooting
providing power
set default address
setting device address
setting device tag
setup and connection
setup and connection, live segment
H hard disk space requirement
I indicator light status
install Emerson DTM Library
install FDT Frame Application
install USB Fieldbus Interface
Configuration utility
L launch the utility
Link Active Scheduler (LAS)
Link Master
live segment connection
O operating systems, supported
overview
P
PACTware
User's Manual 53
User's Manual
PACTware (continued) update device catalog
usage
parts and function
power indicator light status
power modes
Provide Power
R remove pre-release driver versions
S set fieldbus device default address
setup and connection benchtop/segment connection
live segment connection
system requirements
T troubleshooting cannot edit device parameters,
PACTware
fieldbus device not detected in utility
fieldbus device not responding in
AMS Device Manager
U update device catalog
USB FF HSE Server starting, stopping
USB Fieldbus Interface Configuration utility installing
launching
starting/stopping HSE server manually
54
February 2022
February 2022 User's Manual
User's Manual 55
User's Manual
AW7060MNL, Rev. 4
February 2022