Cat. No. W235-E1-05
SYSMAC
Programmable Controllers
C200HS
C200HS Programmable Controllers
Operation Manual
Revised February 2002
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1994
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience
2 General Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 The Origins of PC Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 PC Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 OMRON Product Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 Overview of PC Operation
1-6 Peripheral Devices
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7 Available Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8 New C200HS Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Hardware Considerations . . . . . . . . . . . . . . . . . . . . . . . . .
2-1 CPU Components
2-2 PC Configuration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 CPU Capabilities
2-4 Memory Cassettes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Installing Memory Cassettes
2-6 CPU DIP Switch
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Memory Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Data Area Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 IR (Internal Relay) Area
3-4 SR (Special Relay) Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 AR (Auxiliary Relay) Area
3-6 DM (Data Memory) Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 HR (Holding Relay) Area
3-8 TC (Timer/Counter) Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9 LR (Link Relay) Area
3-10 UM Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-11 TR (Temporary Relay) Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Writing and Inputting the Program . . . . . . . . . . . . . . . . .
4-1 Basic Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Instruction Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Program Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Basic Ladder Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 The Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Preparation for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7 Inputting, Modifying, and Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8 Controlling Bit Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9 Work Bits (Internal Relays) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10 Programming Precautions
4-11 Program Execution
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii xiv xiv xiv xiv xv xvi
1
5
6
4
5
3
3
2
2
15
16
18
19
20
21
23
63
78
80
92
108
110
112
114
64
64
65
65
25
48
55
60
60
26
27
31
33
61
61
61 vii
viii
TABLE OF CONTENTS
SECTION 5
Instruction Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 Notation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Instruction Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Data Areas, Definer Values, and Flags
5-4 Differentiated Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Expansion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Coding Right-hand Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7 Instruction Set Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8 Ladder Diagram Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9 Bit Control Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03) . . . . . . . . . . . . . . . . . . .
5-11 JUMP and JUMP END – JMP(04) and JME(05) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-12 END – END(01) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-13 NO OPERATION – NOP(00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-14 Timer and Counter Instructions
5-15 Data Shifting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16 Data Movement
5-17 Data Comparison
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18 Data Conversion
5-19 BCD Calculations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20 Binary Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21 Special Math Instructions
5-22 Logic Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-23 Subroutines and Interrupt Control
5-24 Step Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25 Special Instructions
5-26 Network Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-27 Serial Communications Instructions
5-28 Advanced I/O Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Program Execution Timing . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Calculating Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Instruction Execution Times
6-4 I/O Response Time
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 7
Program Monitoring and Execution
7-1 Monitoring Operation and Modifying Data
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 8
Communications
8-1 Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Parameters for Host Link and RS-232C Communications . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 9
Memory Cassette Operations
9-1 Memory Cassettes
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2 Memory Cassette Settings and Flags
9-3 UM Area Data
9-4 IOM Area Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
317
318
322
324
333
345
346
373
374
374
385
386
386
387
388
115
158
169
181
205
220
234
250
254
267
276
292
298
302
130
135
137
138
138
138
150
118
118
118
119
120
122
125
129
TABLE OF CONTENTS
SECTION 10
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-1 Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-2 Programmed Alarms and Error Messages
10-3 Reading and Clearing Errors and Messages
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-4 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-5 Error Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-6 Host Link Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 11
Host Link Commands
11-1 Communications Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-2 Command and Response Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3 Host Link Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4 Host Link Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A Standard Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B Programming Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Error and Arithmetic Flag Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Memory Areas
E PC Setup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F Word Assignment Recording Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G Program Coding Sheet
H Data Conversion Tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I Extended ASCII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
391
392
392
392
392
397
399
401
402
404
407
431
433
443
449
453
461
465
471
473
475
477
493
499 ix
About this Manual:
This manual describes the operation of the C200HS C-series Programmable Controllers, and it includes the sections described below. Installation information is provided in the C200HS Programmable Control-
ler Installation Guide. A table of other manuals that can be used in conjunction with this manual is provided in Section 1 Introduction. Provided in Section 2 Hardware Considerations is a description of the differences between the older CPUs and the new CPUs described in this manual.
Please read this manual completely and be sure you understand the information provided before attempting to operate the C200HS. Be sure to read the precautions in the following section.
Section 1 Introduction explains the background and some of the basic terms used in ladder-diagram programming. It also provides an overview of the process of programming and operating a PC and explains basic terminology used with OMRON PCs. Descriptions of Peripheral Devices used with the
C200HS PCs and a table of other manuals available to use with this manual for special PC applications are also provided.
Section 2 Hardware Considerations explains basic aspects of the overall PC configuration and describes the indicators that are referred to in other sections of this manual.
Section 3 Memory Areas takes a look at the way memory is divided and allocated and explains the information provided there to aid in programming. It explains how I/O is managed in memory and how bits in memory correspond to specific I/O points. It also provides information on System DM, a special area in
C200HS PCs that provides the user with flexible control of PC operating parameters.
Section 4 Writing and Entering Programs explains the basics of ladder-diagram programming, looking at the elements that make up the parts of a ladder-diagram program and explaining how execution of this program is controlled. It also explains how to convert ladder diagrams into mnemonic code so that the programs can be entered using a Programming Console.
Section 5 Instruction Set describes all of the instructions used in programming.
Section 6 Program Execution Timing explains the cycling process used to execute the program and tells how to coordinate inputs and outputs so that they occur at the proper times.
Section 7 Program Debugging and Execution explains the Programming Console procedures used to input and debug the program and to monitor and control operation.
Section 8 Communications provides an overview of the communications features provided by the
C200HS.
Section 9 Memory Cassette Operations describes how to manage both UM Area and IOM data via
Memory Cassettes. mounted in the CPU.
Section 10 Troubleshooting provides information on error indications and other means of reducing downtime. Information in this section is also useful when debugging programs.
Section 11 Host Link Commands explains the methods and procedures for using host link commands, which can be used for host link communications via the C200HS ports.
The Appendices provide tables of standard OMRON products available for the C200HS PCs, reference tables of instructions and Programming Console operations, coding sheet to help in programming and parameter input, and other information helpful in PC operation.
!
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
xi
PRECAUTIONS
This section provides general precautions for using the Programmable Controller (PC) and related devices.
The information contained in this section is important for the safe and reliable application of the PC. You must read this section and understand the information contained before attempting to set up or operate a PC system.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv xiv xiv xiv xv xvi xiii
Operating Environment Precautions
1
2
4
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
•
Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating OMRON PCs.
Be sure to read this manual before attempting to use the software and keep this manual close at hand for reference during operation.
!
WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the abovementioned applications.
3 Safety Precautions
!
WARNING Never attempt to disassemble any Units while power is being supplied. Doing so may result in serious electrical shock or electrocution.
4
!
WARNING Never touch any of the terminals while power is being supplied. Doing so may result in serious electrical shock or electrocution.
Operating Environment Precautions
Do not operate the control system in the following places.
• Where the PC is exposed to direct sunlight.
•
Where the ambient temperature is below 0
°
C or over 55
°
C.
• Where the PC may be affected by condensation due to radical temperature changes.
• Where the ambient humidity is below 10% or over 90%.
•
Where there is any corrosive or inflammable gas.
• Where there is excessive dust, saline air, or metal powder.
• Where the PC is affected by vibration or shock.
•
Where any water, oil, or chemical may splash on the PC.
xiv
Application Precautions
5
5
!
Caution The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
Application Precautions
Observe the following precautions when using the PC.
!
WARNING Failure to abide by the following precautions could lead to serious or possibly fatal injury. Always heed these precautions.
• Always ground the system to 100 Ω or less when installing the system to protect against electrical shock.
• Always turn off the power supply to the PC before attempting any of the following. Performing any of the following with the power supply turned on may lead to electrical shock:
•
Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Memory Units, or any other Units.
•
Assembling any devices or racks.
• Connecting or disconnecting any cables or wiring.
!
Caution Failure to abide by the following precautions could lead to faulty operation or the
PC or the system or could damage the PC or PC Units. Always heed these precautions.
• Use the Units only with the power supplies and voltages specified in the operation manuals. Other power supplies and voltages may damage the Units.
•
Take measures to stabilize the power supply to conform to the rated supply if it is not stable.
•
Provide circuit breakers and other safety measures to provide protection against shorts in external wiring.
• Do not apply voltages exceeding the rated input voltage to Input Units. The
Input Units may be destroyed.
• Do not apply voltages exceeding the maximum switching capacity to Output
Units. The Output Units may be destroyed.
•
Always disconnect the LG terminal when performing withstand voltage tests.
• Install all Units according to instructions in the operation manuals. Improper installation may cause faulty operation.
• Provide proper shielding when installing in the following locations:
•
Locations subject to static electricity or other sources of noise.
• Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radiation.
•
Locations near to power supply lines.
• Be sure to tighten Backplane screws, terminal screws, and cable connector screws securely.
•
Do not attempt to take any Units apart, to repair any Units, or to modify any
Units in any way.
!
Caution The following precautions are necessary to ensure the general safety of the system. Always heed these precautions.
•
Provide double safety mechanisms to handle incorrect signals that can be generated by broken signal lines or momentary power interruptions.
•
Provide external interlock circuits, limit circuits, and other safety circuits in addition to any provided within the PC to ensure safety.
xv
Conformance to EC Directives
6
Section 6
Conformance to EC Directives
Observe the following precautions when installing the C200HS-CPU01-EC and
C200HS-CPU21-EC that conform to the EC Directives.
Provide reinforced insulation or double insulation for the DC power source connected to the DC I/O Unit and for the Power Supply Unit.
Use a separate power source for the DC I/O Unit from the external power supply for the Relay Output Unit.
xvi
SECTION 1
Introduction
This section gives a brief overview of the history of Programmable Controllers and explains terms commonly used in ladderdiagram programming. It also provides an overview of the process of programming and operating a PC and explains basic terminology used with OMRON PCs. Descriptions of peripheral devices used with the C200HS, a table of other manuals available to use with this manual for special PC applications, and a description of the new features of the C200HS are also provided.
1-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 The Origins of PC Logic
1-3 PC Terminology
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 OMRON Product Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 Overview of PC Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-6 Peripheral Devices
1-7 Available Manuals
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8 New C200HS Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-1 Improved Memory Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-2 Faster Execution Times
1-8-3 Larger Instruction Set
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-4 Wide Selection of Special I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-5 Improved Interrupt Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-6 SYSMAC NET Link and SYSMAC LINK Capabilities . . . . . . . . . . . . . . . . . . . .
1-8-7 Built-in RS-232C Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-8 More Flexible PC Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-9 Debugging and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-10 New Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-11 Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8-12 Using C200H Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
9
7
7
5
6
4
5
2
2
3
3
10
10
10
10
9
9
10
11
1
The Origins of PC Logic Section 1-2
1-1 Overview
A PC (Programmable Controller) is basically a CPU (Central Processing Unit) containing a program and connected to input and output (I/O) devices. The program controls the PC so that when an input signal from an input device turns ON, the appropriate response is made. The response normally involves turning ON an output signal to some sort of output device. The input devices could be photoelectric sensors, pushbuttons on control panels, limit switches, or any other device that can produce a signal that can be input into the PC. The output devices could be solenoids, switches activating indicator lamps, relays turning on motors, or any other devices that can be activated by signals output from the PC.
For example, a sensor detecting a passing product turns ON an input to the PC.
The PC responds by turning ON an output that activates a pusher that pushes the product onto another conveyor for further processing. Another sensor, positioned higher than the first, turns ON a different input to indicate that the product is too tall. The PC responds by turning on another pusher positioned before the pusher mentioned above to push the too-tall product into a rejection box.
Although this example involves only two inputs and two outputs, it is typical of the type of control operation that PCs can achieve. Actually even this example is much more complex than it may at first appear because of the timing that would be required, i.e., “How does the PC know when to activate each pusher?” Much more complicated operations, however, are also possible. The problem is how to get the desired control signals from available inputs at appropriate times.
To achieve proper control, the C200HS uses a form of PC logic called ladder-diagram programming. This manual is written to explain ladder-diagram programming and to prepare the reader to program and operate the C200HS.
1-2 The Origins of PC Logic
PCs historically originate in relay-based control systems. And although the integrated circuits and internal logic of the PC have taken the place of the discrete relays, timers, counters, and other such devices, actual PC operation proceeds as if those discrete devices were still in place. PC control, however, also provides computer capabilities and accuracy to achieve a great deal more flexibility and reliability than is possible with relays.
The symbols and other control concepts used to describe PC operation also come from relay-based control and form the basis of the ladder-diagram programming method. Most of the terms used to describe these symbols and concepts, however, have come in from computer terminology.
Relay vs. PC Terminology The terminology used throughout this manual is somewhat different from relay terminology, but the concepts are the same.
The following table shows the relationship between relay terms and the PC terms used for OMRON PCs.
Relay term contact coil
NO relay
NC relay
PC equivalent input or condition output or work bit normally open condition normally closed condition
Actually there is not a total equivalence between these terms. The term condition is only used to describe ladder diagram programs in general and is specifically equivalent to one of certain set of basic instructions. The terms input and output are not used in programming per se, except in reference to I/O bits that are assigned to input and output signals coming into and leaving the PC. Normally open conditions and normally closed conditions are explained in 4-4 Basic
Ladder Diagrams.
2
OMRON Product Terminology Section 1-4
1-3 PC Terminology
Although also provided in the Glossary at the back of this manual, the following terms are crucial to understanding PC operation and are thus explained here.
PC
Inputs and Outputs
Because the C200HS is a Rack PC, there is no one product that is a C200HS
PC. That is why we talk about the configuration of the PC, because a PC is a configuration of smaller Units.
To have a functional PC, you would need to have a CPU Rack with at least one
Unit mounted to it that provides I/O points. When we refer to the PC, however, we are generally talking about the CPU and all of the Units directly controlled by it through the program. This does not include the I/O devices connected to PC inputs and outputs.
If you are not familiar with the terms used above to describe a PC, refer to Sec-
tion 2 Hardware Considerations for explanations.
A device connected to the PC that sends a signal to the PC is called an input
device; the signal it sends is called an input signal. A signal enters the PC through terminals or through pins on a connector on a Unit. The place where a signal enters the PC is called an input point. This input point is allocated a location in memory that reflects its status, i.e., either ON or OFF. This memory location is called an input bit. The CPU, in its normal processing cycle, monitors the status of all input points and turns ON or OFF corresponding input bits accordingly.
There are also output bits in memory that are allocated to output points on
Units through which output signals are sent to output devices, i.e., an output bit is turned ON to send a signal to an output device through an output point. The
CPU periodically turns output points ON or OFF according to the status of the output bits.
These terms are used when describing different aspects of PC operation. When programming, one is concerned with what information is held in memory, and so
I/O bits are referred to. When talking about the Units that connect the PC to the controlled system and the places on these Units where signals enter and leave the PC, I/O points are referred to. When wiring these I/O points, the physical counterparts of the I/O points, either terminals or connector pins, are referred to.
When talking about the signals that enter or leave the PC, one refers to input signals and output signals, or sometimes just inputs and outputs. It all depends on what aspect of PC operation is being talked about.
Controlled System and
Control System
The Control System includes the PC and all I/O devices it uses to control an external system. A sensor that provides information to achieve control is an input device that is clearly part of the Control System. The controlled system is the external system that is being controlled by the PC program through these I/O devices. I/O devices can sometimes be considered part of the controlled system, e.g., a motor used to drive a conveyor belt.
1-4 OMRON Product Terminology
OMRON products are divided into several functional groups that have generic names. Appendix A Standard Models list products according to these groups.
The term Unit is used to refer to all of the OMRON PC products. Although a Unit is any one of the building blocks that goes together to form a C200HS PC, its meaning is generally, but not always, limited in context to refer to the Units that are mounted to a Rack. Most, but not all, of these products have names that end with the word Unit.
The largest group of OMRON products is the I/O Units. These include all of the
Rack-mounting Units that provide non-dedicated input or output points for general use. I/O Units come with a variety of point connections and specifications.
3
Overview of PC Operation Section 1-5
High-density I/O Units are designed to provide high-density I/O capability and include Group 2 High-density I/O Units and Special I/O High-density I/O Units.
Special I/O Units are dedicated Units that are designed to meet specific needs.
These include some of the High-density I/O Units, Position Control Units, Highspeed Counter Units, and Analog I/O Units.
Link Units are used to create Link Systems that link more than one PC or link a single PC to remote I/O points. Link Units include Remote I/O Units, PC Link
Units, Host Link Units, SYSMAC NET Link Units, and SYSMAC LINK Units.
SYSMAC NET Link and SYSMAC LINK Units can be used with the CPU11 only.
Other product groups include Programming Devices, Peripheral Devices, and DIN Rail Products.
1-5 Overview of PC Operation
The following are the basic steps involved in programming and operating a
C200HS. Assuming you have already purchased one or more of these PCs, you must have a reasonable idea of the required information for steps one and two, which are discussed briefly below. This manual is written to explain steps three through six, eight, and nine. The relevant sections of this manual that provide more information are listed with each of these steps.
1, 2, 3...
1. Determine what the controlled system must do, in what order, and at what times.
2. Determine what Racks and what Units will be required. Refer to the C200HS
Installation Guide. If a Link System is required, refer to the appropriate Sys-
tem Manual.
3. On paper, assign all input and output devices to I/O points on Units and determine which I/O bits will be allocated to each. If the PC includes Special I/O
Units or Link Systems, refer to the individual Operation Manuals or System
Manuals for details on I/O bit allocation. (Section 3 Memory Areas)
4. Using relay ladder symbols, write a program that represents the sequence of required operations and their inter-relationships. Be sure to also program appropriate responses for all possible emergency situations. (Section 4
Writing and Inputting the Program, Section 5 Instruction Set, Section 6 Program Execution Timing)
5. Input the program and all required operating parameters into the PC. (Sec-
tion 4-7 Inputting, Modifying, and Checking the Program.)
6. Debug the program, first to eliminate any syntax errors, and then to find execution errors. (Section 4-7 Inputting, Modifying, and Checking the Pro-
gram, Section 7 Program Monitoring and Execution, and Section 10
Troubleshooting)
7. Wire the PC to the controlled system. This step can actually be started as soon as step 3 has been completed. Refer to the C200HS Installation Guide and to Operation Manuals and System Manuals for details on individual
Units.
8. Test the program in an actual control situation and carry out fine tuning as required. (Section 7 Program Monitoring and Execution and Section 10
Troubleshooting)
9. Record two copies of the finished program on masters and store them safely in different locations. (Section 4-7 Inputting, Modifying, and Checking the
Program)
Control System Design Designing the Control System is the first step in automating any process. A PC can be programmed and operated only after the overall Control System is fully understood. Designing the Control System requires, first of all, a thorough understanding of the system that is to be controlled. The first step in designing a
Control System is thus determining the requirements of the controlled system.
4
Available Manuals Section 1-7
Input/Output Requirements The first thing that must be assessed is the number of input and output points that the controlled system will require. This is done by identifying each device that is to send an input signal to the PC or which is to receive an output signal from the PC. Keep in mind that the number of I/O points available depends on the configuration of the PC. Refer to 3-3 IR Area for details on I/O capacity and the allocation of I/O bits to I/O points.
Sequence, Timing, and
Relationships
Next, determine the sequence in which control operations are to occur and the relative timing of the operations. Identify the physical relationships between the
I/O devices as well as the kinds of responses that should occur between them.
For instance, a photoelectric switch might be functionally tied to a motor by way of a counter within the PC. When the PC receives an input from a start switch, it could start the motor. The PC could then stop the motor when the counter has received a specified number of input signals from the photoelectric switch.
Each of the related tasks must be similarly determined, from the beginning of the control operation to the end.
Unit Requirements The actual Units that will be mounted or connected to PC Racks must be determined according to the requirements of the I/O devices. Actual hardware specifications, such as voltage and current levels, as well as functional considerations, such as those that require Special I/O Units or Link Systems will need to be considered. In many cases, Special I/O Units, Intelligent I/O Units, or Link Systems can greatly reduce the programming burden. Details on these Units and Link
Systems are available in appropriate Operation Manuals and System Manuals.
Once the entire Control System has been designed, the task of programming, debugging, and operation as described in the remaining sections of this manual can begin.
1-6 Peripheral Devices
The following peripheral devices can be used in programming, either to input/ debug/monitor the PC program or to interface the PC to external devices to output the program or memory area data. Model numbers for all devices listed below are provided in Appendix A Standard Models. OMRON product names have been placed in bold when introduced in the following descriptions.
Programming Console
Ladder Support Software:
LSS
A Programming Console is the simplest form of programming device for OM-
RON PCs. All Programming Consoles are connected directly to the CPU without requiring a separate interface.
LSS is designed to run on IBM AT/XT compatibles and allows you to perform all the operations of the Programming Console as well as many additional ones. PC programs can be written on-screen in ladder-diagram form as well as in mnemonic form. As the program is written, it is displayed on a display, making confirmation and modification quick and easy. Syntax checks may also be performed on the programs before they are downloaded to the PC.
The LSS is available on either 5” or 3.5” disks.
A computer running the LSS is connected to the C200HS via the Peripheral Port on the CPU using the CQM1-CIF02 cable.
1-7 Available Manuals
The following table lists other manuals that may be required to program and/or operate the C200HS. Operation Manuals and/or Operation Guides are also provided with individual Units and are required for wiring and other specifications.
Name
GPC Operation Manual
FIT Operation Manual
Cat. No.
W84
W150
Contents
Programming procedures for the GPC
(Graphics Programming Console)
Programming procedures for using the FIT
(Factory Intelligent Terminal
5
New C200HS Features Section 1-8
Name
SYSMAC Support Software Operation Manuals
Data Access Console Operation Guide
Printer Interface Unit Operation Guide
PROM Writer Operation Guide
Floppy Disk Interface Unit Operation Guide
Wired Remote I/O System Manual
(SYSMAC BUS)
Optical Remote I/O System Manual
(SYSMAC BUS)
PC Link System Manual
Host Link System Manual
(SYSMAC WAY)
SYSMAC NET Link Unit Operation Manual
SYSMAC LINK System Manual
High-speed Counter Unit Operation Manual
Position Control Unit Operation Manuals
Analog I/O Units Operation Guide
Analog Input Unit Operation Manual
Temperature Sensor Unit Operation Guide
ASCII Unit Operation Manual
ID Sensor Unit Operation Guide
Voice Unit Operation Manual
Fuzzy Logic Unit Operation Manual
Fuzzy Support Software Operation Manual
Temperature Control Unit Operation Manual
Heat/Cool Temperature Control Unit Operation
Manual
PID Control Unit Operation Manual
Cam Positioner Unit Operation Manual
W229
W124
W165
W153
W172
W208
W210
Cat. No.
Contents
W247/W248 Programming procedures for using the SSS
W173
W107
Data area monitoring and data modification procedures for the Data Access Console
Procedures for interfacing a PC to a printer
W155
W119
W120
W136
Procedures for writing programs to EPROM chips
Procedures for interfacing PCs to floppy disk drives
Information on building a Wired Remote I/O System to enable remote I/O capability
Information on building an Optical Remote I/O
System to enable remote I/O capability
W135
W143
W114
W174
W141
NC111: W137
NC112: W128
NC211: W166
W127
Information on building a PC Link System to automatically transfer data between PCs
Information on building a Host Link System to manage PCs from a ‘host’ computer
Information on building a SYSMAC NET Link
System and thus create an optical LAN integrating
PCs with computers and other peripheral devices
Information on building a SYSMAC LINK System to enable automatic data transfer, programming, and programmed data transfer between the PCs in the
System
Information on High-speed Counter Unit
Information on Position Control Unit
Information on the C200H-AD001, C200H-DA001
Analog I/O Units
Information on the C200H-AD002 Analog Input Unit
Information on Temperature Sensor Unit
Information on ASCII Unit
Information on ID Sensor Unit
Information on Voice Unit
Information on Fuzzy Logic Unit
Information on the Fuzzy Support Software which supports the Fuzzy Logic Units
W225
W240
W241
W224
Information on Temperature Control Unit
Information on Heating and Cooling Temperature
Control Unit
Information on PID Control Unit
Information on Cam Positioner Unit
1-8 New C200HS Features
The C200HS CPUs (C200HS-CPU01-E, C200HS-CPU03-E, C200HS-
CPU21-E, C200HS-CPU23-E, C200HS-CPU31-E, and C200HS-CPU33-E) have a number of new features that the C200H CPUs lacked. The new C200HS features are described briefly in this section. The C200HS-CPU01-E, C200HS-
CPU21-E, C200HS-CPU31-E use an AC power supply and the C200HS-
CPU03-E, C200HS-CPU23-E, and C200HS-CPU33-E use DC.
In addition, the C200HS-CPU21-E, C200HS-CPU23-E, C200HS-CPU31-E, and C200HS-CPU33-E CPUs have an RS-232C connector. The C200HS-
CPU31-E and C200HS-CPU33-E CPUs support the SYSMAC NET Link Unit and SYSMAC LINK Unit.
6
New C200HS Features Section 1-8
1-8-1 Improved Memory Capabilities
Internal Memory (UM)
Memory Cassettes
The C200HS CPUs come equipped with 16 KW of RAM in the PC itself, so a very large memory capacity is available without purchasing a separate Memory Unit.
Furthermore, the Ladder Program Area has been increased to 15.2 KW.
Two types of Memory Cassettes are available for storage of data such as the program. The PC can be set to transfer data from the Memory Cassette to UM automatically when the PC is turned on.
Specifications Model
C200HS-ME16K
C200HS-MP16K
16-K Word EEPROM
16-K Word EPROM
Note C200H Memory Cassettes cannot be used in the C200HS.
Clock Function
Increased SR Area
Increased DM Area
Fixed DM and Expansion
DM Areas
The C200HS CPUs have a built-in clock. It is not necessary to purchase a
Memory Unit equipped with a clock, as it was with the C200H-CPU21-E.
In addition to the conventional areas of the C200H, the following areas have been added for the internal auxiliary relays and special auxiliary relays of the
C200H. The SR area has been increased substantially to provide more work words and words dedicated to new instructions. The SR area now ranges from
SR 236 to SR 299. (The SR area ends at SR 255 in C200H CPUs.) By using additional areas, the user can use Special I/O Units and Remote I/O Units without worrying the empty areas.
Conventional areas IR Area 1 (without I/O area): IR 030 to 235
SR Area 1: SR 236 to 255
Additional areas IR Area 2:
SR Area 2:
IR 300 to 511
SR 256 to 299
The number of operands and instruction execution time will be increased when
SR 256 to SR 511 are used in basic instructions.
The Read/Write DM area has been increased substantially, too. It now ranges from DM 0000 to DM 6143, compared to DM 0000 to DM 0999 in C200H CPUs.
The 6000 words from DM 0000 to DM 5999 are available for use in the program.
(DM 6000 to DM 6143 are used for the History Log and other functions.)
The Fixed DM Area, used to store initializing data for Special I/O Units, has been decreased in size. It now contains the 512 words from DM 6144 to DM 6655, compared to 1000 words (DM 1000 to DM 1999) in C200H CPUs.
On the other hand, up to 3000 words of UM can be allocated as expansion DM.
Expansion DM is allocated in 1000-word units in DM 7000 to DM 9999.
C200H data stored in words DM 1000 to DM 1999 can be used in C200HS PCs by converting these 1000 words to ROM in the C200HS’s DM area (DM 7000 to
DM 7999) and then automatically transferring them to DM 1000 to DM 1999 when the C200HS is turned on.
1-8-2 Faster Execution Times
Instruction Execution Time Basic instructions in the C200HS are executed in !
2 of the time required in the
C200H. Other instructions are executed in just !
4 of the time.
END Processing Time The time required for the cycle’s overhead processes depend on the system configuration, but these processes are executed in about
!
4
of the time required in the C200H.
7
New C200HS Features Section 1-8
I/O Refreshing Time
New Instructions
The I/O refreshing time has been reduced for all units, as shown in the following table.
I/O Unit
Standard I/O Units
Group-2 High-density I/O Units
Special I/O Units
Time Required for Refreshing
!
3 of the C200H I/O refreshing time
!
3 of the C200H I/O refreshing time
$ 5 of the C200H I/O refreshing time
1-8-3 Larger Instruction Set
Advanced programming is facilitated by the 225 application instructions available with the C200HS-CPU01-E, C200HS-CPU03-E, C200HS-CPU21-E, and
C200HS-CPU23-E, or the 229 application instructions available with the
C200HS-CPU31-E and C200HS-CPU33-E. In addition, programming has been simplified by the addition of convenient instructions and macro functions. The new instructions and functions are covered in detail in Section 5 Instruction Set.
Improved Instructions Additional functions have been added to the 7 instructions in the following table.
Instruction
DIST(80)
COLL(81)
MLPX(76)
DMPX(77)
ADB(50)
SBB(51)
INT(89)
Additional Function(s)
Stack operation. The stack can contain up to 999 words.
FIFO/LIFO stack operation. The stack can contain up to 999 words.
4-to-256 decoder capability.
256-to-8 encoder capability.
Signed binary data can be added.
Signed binary data can be subtracted.
Can be used to set scheduled interrupts in 1 ms units and control input interrupts.
Expansion Instructions A group of 47 instructions have been designated as expansion instructions. An expansion instruction does not have a fixed function code; one of the 18 expansion instruction function codes must be assigned to it before it can be used in a program. An instructions tables, which allocates functions codes to expansion instructions, must be transferred to the C200HS before the expansion instructions can be used.
A total of 36 new instructions have been added to the C200HS. These instructions are listed below. (Instructions with (--) for function codes are expansion instructions, which do not have fixed function codes. Some expansion instruction do have default function codes. The SET and RESET instructions are basic instructions, MACRO and TRACE MEMORY SAMPLE instructions are applied instructions, and the other instructions are expansion applied instructions. A default function number is assigned to the TOTALIZING TIMER, TRANSFER
BITS, AREA RANGE COMPARE, MACRO, AND TRACE MEMORY SAMPLE instructions.
8
New C200HS Features
TRSM(45) TRACE MEMORY SAMPLE
MCRO(99) MACRO
MAX(--) FIND MAXIMUM
MIN(--) FIND MINIMUM
SUM(--) SUM
SRCH(--) DATA SEARCH
FPD(--)
PID(--)
FAILURE POINT DETECTION
PID CONTROL
HEX(--) ASCII TO HEX
XDMR(--) EXPANSION DM READ
DSW(--) DIGITAL SWITCH INPUT
TKY(--) TEN-KEY INPUT
MTR(--) MATRIX INPUT
HKY(--) 16-KEY INPUT
ADBL(--) DOUBLE BINARY ADD
SBBL(--) DOUBLE BINARY SUBTRACT
MBSL(--) DOUBLE SIGNED BINARY MULTIPLY
DBSL(--) DOUBLE SIGNED BINARY DIVIDE
Section 1-8
MBS(--) SIGNED BINARY MULTIPLY
DBS(--) SIGNED BINARY DIVIDE
FCS(--) FRAME CHECKSUM
7SEG(--) 7-SEGMENT DISPLAY OUTPUT
RXD(--) RECEIVE
TXD(--) TRANSMIT
CPS(--) SIGNED BINARY COMPARE
CPSL(--) SIGNED DOUBLE BINARY COMPARE
NEG(--) 2’S COMPLEMENT
NEGL(--) DOUBLE 2’S COMPLEMENT
ZCPL(--) DOUBLE AREA RANGE COMPARE
AVG(--) AVERAGE VALUE
SCL(--)
SET
SCALE
SET
RSET RESET
TTIM(87) TOTALIZING TIMER
XFRB(62) TRANSFER BITS
ZCP(88) AREA RANGE COMPARE
1-8-4 Wide Selection of Special I/O Units
C200HS Systems can be configured in a variety of ways, using High-density I/O
Units, High-speed Counters, Position Control Units, Analog I/O Units, Temperature Sensor Units, ASCII Units, Voice Units, ID Sensor Units, Fuzzy Logic Units,
Cam Positioner Units, and so on.
1-8-5 Improved Interrupt Functions
Scheduled Interrupts
Input Interrupts
The C200HS’s scheduled interrupt function has been improved so that the interrupt interval can be set in 1 ms units rather than the 10 ms units in the C200H.
When the interrupt mode is set to C200HS mode, the interrupt response time is only 1 ms max. (excluding the input ON/OFF delays). When a Communications
Unit is used with the C200HS-CPU31-E/CPU33-E CPU, the interrupt response time is 10 ms max.
Up to 8 interrupt subroutines can be executed by inputs to a C200HS-INT01 Interrupt Input Unit mounted to the C200HS. When the interrupt mode is set to
C200HS mode, the interrupt response time is only 1 ms max. (excluding the input ON/OFF delays). When a Communications Unit is used with the C200HS-
CPU31-E/CPU33-E CPU, the interrupt response time is 10 ms max.
1-8-6 SYSMAC NET Link and SYSMAC LINK Capabilities
The SYSMAC NET Link and SYSMAC LINK Systems are high-speed FA networks which can be used with the C200HS-CPU31-E and C200HS-CPU33-E
CPUs and the following Units:
SYSMAC NET Link Unit:
SYSMAC LINK Units:
C200HS-SNT32
C200HS-SLK12 (optical fiber cable)
C200HS-SLK22 (coaxial cable)
Data can be exchanged with the PCs in a SYSMAC NET Link or SYSMAC LINK
System using the SEND and RECV instructions.
9
New C200HS Features Section 1-8
1-8-7 Built-in RS-232C Connector
Host link communications are possible using the RS-232C connector built into the C200HS-CPU21-E/CPU23-E/CPU31-E/CPU33-E CPU. By using the TXD and RXD instructions, RS-232C communications is possible without using timeconsuming procedures. A 1-to-1 link using the LR Area or an NT link with the
Programmable Terminal (PT) allows high-speed communications.
1-8-8 More Flexible PC Settings
With its default settings, the C200HS can be used like a C200H PC, but the
C200HS’s new settings provide more flexibility and allow it to be adjusted to fit particular applications. These new settings are described below.
DIP Switch Settings The 6 pins on the C200HS’s DIP switch are used to write-protect part of UM, set the CPU to automatically transfer Memory Card data to UM, and other functions.
UM Area Allocation
PC Setup
Portions of the UM area can be allocated for use as the Expansion DM Area and
I/O Comment Area. (Most of the UM area is used to store the ladder program.)
DM 6600 to DM 6655 is set aside for PC Setup data. The PC Setup determines many operating parameters, including the startup mode and initial Special I/O
Unit area.
1-8-9 Debugging and Maintenance
Data Trace
Differential Monitor
Error Log Area
A data trace function has been added, allowing bit status or word content to be traced in real time.
The C200HS supports differential monitoring from either the Programming Console or LSS. The operator can detect OFF-to-ON or ON-to-OFF transition in a specified bit.
The C200HS supports all of the C200H-CPU31-E error history area functions and also records the time and date of power interruptions. The C200HS’s error log area is DM 6000 to DM 6030 (not DM 0969 to DM 0999 as in the C200H-
CPU31-E).
1-8-10 New Programming Console Operations
The following Programming Console operations are supported by the C200HS in addition to those supported by the C200H.
• Constants can be input in decimal form.
•
Monitor displays can be switched between hexadecimal and normal or long decimal form.
• OFF to ON and ON to OFF transitions in bit status can be monitored (differential monitoring).
•
Function codes can be allocated to expansion instructions and current function code allocations can be read.
• UM area allocations can be set.
•
The clock in the C200HS can be read and set.
• In addition to the TERMINAL mode supported in the C200H, the C200HS has an EXTENDED TERMINAL mode in which all of the Programming Console’s keys can be used to the status of Key Bits.
• The memory clear operation has been separated into an operation to clear the user program excluding I/O comments and UM area allocation information, and one to clear the user program, I/O comments , and UM area allocation information.
1-8-11 Peripheral Devices
Peripheral Device
Connection
With the C200H a Peripheral Device had to be connected through a Peripheral
Interface Unit or Host Link Unit, but with the C200HS Peripheral Devices can be connected to the PC through a CQM1-CIF02 Connecting Cable.
10
New C200HS Features Section 1-8
I/O Comments Stored in PC By allocating a part of UM as the I/O Comment area, it is no longer necessary to read I/O Comments from a Peripheral Device’s floppy disk. If the Peripheral Device is connected to the C200HS online, the ladder diagram can be viewed with
I/O comments.
Online Editing A “CYCLE TIME OVER” error will no longer be generated when the program in the PC itself is being edited online.
1-8-12 Using C200H Programs
Programs developed for the C200H can be very easily transferred for use in the
C200HS. This section provides the steps necessary to achieve this. Two procedures are provided: one for transferring using only internal CPU memory and one for transferring via Memory Cassettes.
Detailed procedures for the individual steps involved in transferring programs can be found in the Version-3 LSS Operation Manuals. You will also require a
CQM1-CIF02 Connecting Cable to connect the computer running LSS to the
C200HS.
Precautions
Using Internal Memory
Observe the following precautions when transferring C200H programs to the
C200HS.
• If a C200H program including the SET SYSTEM instruction (SYS(49)) is transferred to the C200HS, the operating parameters set by this instruction will be transferred to the C200HS’s PC Setup area (DM 6600, DM 6601, and
DM 6655) and overwrite any current settings. Be sure to confirm that the settings in these words are correct before using the C200HS after program transfer.
• If the C200H program accesses the C200H’s error log in DM 0969 to DM 0999, the addresses of the words being accessed must be changed to DM 6000 to
DM 6030, which is the error log area for the C200HS.
•
Any programs that rely on the execution cycle time (i.e., on the time require to execute any one part of all of the program) must be adjusted when used on the
C200HS, which provides a much faster cycle time.
The following procedure outlines the steps to transfer C200H programs to the user memory inside the C200HS.
1, 2, 3...
1. Transfer the program and any other required data to the LSS work area. This data can be transferred from a C200H CPU, from floppy disk, or from a
C200HS Memory Unit.
To transfer from a C200H CPU, set the PC for the LSS to the C200H, connect the LSS to the C200H, go online, and transfer the program and any other require data to the LSS work area. You will probably want to transfer DM data and the I/O table, if you have created an I/O table for the C200H.
or To transfer from floppy disk, set the PC for the LSS to the C200H in the offline mode and load the program and any other require data to the LSS work area. You will probably want to load DM data and the I/O table, if you have created an I/O table for the C200H.
or To transfer from a C200H-MP831, set the PC for the LSS to the C200H in the offline mode and read data from the Memory Unit into the LSS work area.
2. Go offline if the LSS is not already offline.
3. Change the PC setting for the LSS to the C200HS.
4. If you want to transfer I/O comments together with the program to the
C200HS, allocate UM area for I/O comments.
5. Connect the LSS to the C200HS and go online.
6. Make sure that pin 1 on the C200HS’s CPU is OFF to enable writing to the
UM area.
11
New C200HS Features Section 1-8
Using Memory Cassettes
7. Transfer the program and and any other require data to the C200HS. You will probably want to transfer DM data and the I/O table, if you have created an I/O table for the C200H.
8. Turn the C200HS off and then back on to reset it.
9. Test program execution before attempting actual operation.
The following procedure outlines the steps to transfer C200H programs to the
C200HS via EEPROM or EPROM Memory Cassettes. This will allow you to read the program data from the Memory Cassette automatically at C200HS startup.
The first four steps of this procedure is the same as those used for transferring directly to the C200HS’s internal memory (UM area).
1, 2, 3...
1. Transfer the program and any other required data to the LSS work area. This data can be transferred from a C200H CPU, from floppy disk, or from a
C200HS Memory Unit.
To transfer from a C200H CPU, set the PC for the LSS to the C200H, connect the LSS to the C200H, go online, and transfer the program and any other require data to the LSS work area. You will probably want to transfer DM data and the I/O table, if you have created an I/O table for the C200H.
or To transfer from floppy disk, set the PC for the LSS to the C200H in the offline mode and load the program and any other require data to the LSS work area. You will probably want to load DM data and the I/O table, if you have created an I/O table for the C200H.
or To transfer from a C200H-MP831, set the PC for the LSS to the C200H in the offline mode and read data from the Memory Unit into the LSS work area.
2. Go offline if the LSS is not already offline.
3. Change the PC setting for the LSS to the C200HS.
4. If you want to transfer I/O comments together with the program to the
C200HS, allocate UM area for I/O comments.
5. Allocate expansion DM words DM 7000 to DM 7999 in the UM area using the
UM allocation operation from the LSS.
6. Copy DM 1000 through DM 1999 to DM 7000 through DM 7999.
7. Write “0100” to DM 6602 to automatically transfer the contents of DM 7000 through DM 7999 to DM 1000 through DM 1999 at startup.
8. To transfer to an EEPROM Memory Cassette, use the following procedure.
a) Connect the LSS to the C200HS and go online.
b) Make sure that pin 1 on the C200HS’s CPU is OFF to enable writing to the UM area.
c) Transfer the program and any other require data to the C200HS. You will probably want to transfer DM data and the I/O table, if you have created an I/O table for the C200H. Make sure you specify transfer of the Expansion DM Area and, if desired, the I/O Comment Area.
d) Turn ON SR 27000 from the LSS to transfer UM data to the Memory Cassette and continue from step 9.
or To transfer to an EPROM Memory Cassette, use the following procedure.
a) Connect an PROM Writer to the LSS and write the data to the EPROM chip using the LSS EPROM writing operation.
e) Set the ROM type selector on the Memory Cassette to the correct capacity.
f) Mount the ROM chip to the Memory Cassette.
g) Mount a EPROM Memory Cassette to the C200HS.
9. Turn ON pin 2 on the C200HS’s DIP switch to enable automatic transfer of
Memory Cassette data to the CPU at startup.
12
New C200HS Features Section 1-8
10. Turn the C200HS off and then back on to reset it and transfer data from the
Memory Cassette to the CPU.
11. Test program execution before attempting actual operation.
13
SECTION 2
Hardware Considerations
This section provides information on hardware aspects of the C200HS that are relevant to programming and software operation. These include CPU Components, basic PC configuration, CPU capabilities, and Memory Cassettes. This information is covered in detail in the C200HS Installation Guide.
2-1 CPU Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 CPU Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Peripheral Device Connection
2-2 PC Configuration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 CPU Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Memory Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Installing Memory Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 CPU DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
17
18
18
19
20
21
23
15
CPU Components Section 2-1
2-1 CPU Components
There are two groups of CPUs available, one that uses an AC power supply, and one that uses a DC power supply. Select one of the models shown below according to requirements of your control system.
CPU model Power supply voltage
C200HS-CPU01-E/CPU21-E/CPU31-E 100 to 120 VAC or 200 to 240 VAC
(voltage selector)
C200HS-CPU03-E/CPU23-E/CPU33-E 24 VDC
The CPU21-E, CPU23-E, CPU31-E, and CPU33-E CPUs have an RS-232C connector. The CPU31-E and CPU33-E CPUs support the SYSMAC NET Link
Unit and SYSMAC LINK Unit.
!
Caution Be sure to check the power supply used by the CPU. Absolutely do not provide an AC power supply to a DC-type CPU.
The following diagram shows the main CPU components.
Indicators
Power fuse (MF51NR, 5.2 dia. x 20 mm)
C200HS-CPU01-E: 2 A, 250 V
C200HS-CPU03-E: 5 A, 125 V
Removable terminal block
Battery/switch compartment
The backup lithium battery (C200H-BAT09) and the DIP switch for setting C200HS operations are contained. An optional Memory Cassette can also be mounted.
Cable connector for Peripheral Devices
(Peripheral port)
16
CPU Components
C200HS-CPU21-E/CPU23-E/CPU31-E/CPU33-E
Section 2-1
Indicators
Power fuse (MF51NR, 5.2 dia. x 20 mm):
C200HS-CPU21-E/CPU31-E: 2 A, 250 V
C200HS-CPU23-E/CPU33-E: 5 A, 125 V
Memory Casette compartment
Bus connector:
Available only with the CPU31-E and CPU33-E. Use this connector when SYSMAC NET Link Unit or
SYSMAC LINK Unit is used.
Removable terminal block
RS-232C connector
Cable connector for peripheral devices
Battery/Switch compartment
2-1-1 CPU Indicators
CPU indicators provide visual information on the general operation of the PC.
Although not substitutes for proper error programming using the flags and other error indicators provided in the data areas of memory, these indicators provide ready confirmation of proper operation.
CPU Indicators CPU indicators are shown and described below. (CPU01-E/03-E shown below.)
RUN indicator (green)
Lights when the PC is operating normally.
COMM/COMM1 (orange):
Lights when a peripheral device is in operation.
COMM2 (orange):
Available only with the CPU21-E, CPU23-E, CPU31-E, and CPU33-E. Lights when the CPU is communicating via the RS-232C connector.
POWER (green)
Lights when power is supplied to the CPU.
COMM
ALM (blinking red)
Blinks if an error occurs that does not stop the CPU.
ERR (solid red)
Lights if an error occurs that stops the
CPU, at which time the RUN indicator turns OFF and the outputs are turned
OFF.
OUT INHIBIT (red)
Lights when the Load OFF flag (SR bit 25215) turns ON, at which time all the outputs are turned OFF.
17
PC Configuration Section 2-2
2-1-2 Peripheral Device Connection
A Programming Console or IBM PC/AT running LSS can be used to program and monitor the C200HS PCs.
Programming Console A C200H-PR027-E or CQM1-PRO01-E Programming Console can be connected as shown in the following diagram. The C200H-PR027-E is connected via the C200H-CN222 or C200H-CN422 Programming Console Connecting
Cable, which must be purchased separately. A Connecting Cable is provided with the CQM1-PRO01-E.
Connecting Cable
Programming Console
IBM PC/AT with LSS An IBM PC/AT or compatible computer can be connected as shown in the following diagram. The LSS is available on either 3.5” disks (C500-SF312-EV3) or
5.25” disks (C500-SF711-EV3). Only version 3 or later of the LSS supports
C200HS functionality.
Connecting Cable
(CQM1-CIF02)
IBM PC/AT
2-2 PC Configuration
The basic PC configuration consists of two types of Rack: a CPU Rack and Expansion I/O Racks. The Expansion I/O Racks are not a required part of the basic system. They are used to increase the number of I/O points. An illustration of these Racks is provided in 3-3 IR Area. A third type of Rack, called a Slave Rack, can be used when the PC is provided with a Remote I/O System.
CPU Racks A C200HS CPU Rack consists of three components: (1) The CPU Backplane, to which the CPU and other Units are mounted. (2) The CPU, which executes the program and controls the PC. (3) Other Units, such as I/O Units, Special I/O
Units, and Link Units, which provide the physical I/O terminals corresponding to
I/O points.
A C200HS CPU Rack can be used alone or it can be connected to other Racks to provide additional I/O points. The CPU Rack provides three, five, eight, or ten slots to which these other Units can be mounted depending on the backplane used.
18
CPU Capabilities Section 2-3
Expansion I/O Racks
Unit Mounting Position
An Expansion I/O Rack can be thought of as an extension of the PC because it provides additional slots to which other Units can be mounted. It is built onto an
Expansion I/O Backplane to which a Power Supply and up to ten other Units are mounted.
An Expansion I/O Rack is always connected to the CPU via the connectors on the Backplanes, allowing communication between the two Racks. Up to two Expansion I/O Racks can be connected in series to the CPU Rack.
Only I/O Units and Special I/O Units can be mounted to Slave Racks. All I/O
Units, Special I/O Units, Group-2 High-density I/O Units, Remote I/O Master
Units, PC and Host Link Units, can be mounted to any slot on all other Racks.
Interrupt Input Units must be mounted to C200H-BC jj
1-V2 Backplanes.
Refer to the C200HS Installation Guide for details about which slots can be used for which Units and other details about PC configuration. The way in which I/O points on Units are allocated in memory is described in 3-3 IR Area.
2-3 CPU Capabilities
The following tables compare the capabilities of C200H and C200HS CPUs.
C200H
Function
Built-in clock/calendar
Error log
Data Trace
Differential Monitor
Expansion DM
General-use DM
Ladder Program capacity
SR Area
New instructions:
(See 1-8-3 Larger Instruction Set for a list of the
36 new instructions.)
Network Instructions:
NETWORK SEND - SEND(90)
NETWORK RECEIVE - RECV(98)
Power Supply
CPU21-E
No (see note)
No
No
No
No
1000 words
6974 words (in Memory Unit)
SR 236 to SR 255
No No
C200H
CPU23-E
No (see note)
No
No
No
No
No No
CPU31-E
Yes
Yes
No
No
No
970 words
No
Yes
AC DC AC
Note The C200H-CPU21-E/CPU23-E can use the C200H-MR433/MR833/
ME432/ME832 Memory Units’ clock.
19
Memory Cassettes
C200HS-ME j 16K
(EEPROM)
Section 2-4
C200HS
Function
Built-in clock/calendar
Error log
Data Trace
Differential Monitor
Expansion DM
General-use DM
Ladder Program capacity
SR Area
New instructions:
(See 1-8-3 Larger Instruction Set for a list of the
36 new instructions.)
Network Instructions:
NETWORK SEND - SEND(90)
NETWORK RECEIVE - RECV(98)
Power Supply
C200HS
CPU01-E CPU21-E CPU31-E CPU03-E CPU23-E CPU33-E
Yes
Yes 1
Yes
Yes
3K words max.
2
6K words
15.2K words max 2
SR 236 to SR 255 and SR 256 to SR 299
Yes
No No Yes No No Yes
AC DC
Note 1. The C200HS CPUs record the time and date of power interruptions.
2. Part of the 16K-word UM can be allocated to Expansion DM and I/O comments.
2-4 Memory Cassettes
The C200HS comes equipped with a built-in RAM for the user’s program, so a normal program be created even without installing a Memory Cassette. An optional Memory Cassette, however, can be used. There are two types of Memory
Cassette available, each with a capacity of 16K words. For instructions on installing Memory Cassettes, refer to 2-5 Installing Memory Cassettes.
The following table shows the Memory Cassettes which can be used with the
C200HS PCs. These Memory Cassettes cannot be used in C200H PCs.
Memory Capacity Model number Comments
EEPROM 16K words C200HS-ME16K ---
EPROM 16K words C200HS-MP16K The EPROM chip is not included with the Memory Cassette; it must be purchased separately.
Note Memory Cassettes for the C200HS cannot be used with the C200H, and
Memory Units for the C200H cannot be used with the C200HS.
When a Memory Cassette is installed in the CPU, reading and writing of the user memory (UM) and I/O data is made possible. There is no need for a backup power supply. The Memory Cassette can be removed from the CPU and used for storing data.
20
Installing Memory Cassettes Section 2-5
C200HS-MP j 16K (EPROM) The program is written using a PROM Writer. The ROM is mounted to the
Memory Casette and then installed in the CPU. I/O data cannot be stored.
Notch
2-5 Installing Memory Cassettes
An optional Memory Cassette can be installed in the C200HS. (The C200H
Memory Unit cannot be used with the C200HS.) The two types of Memory Cassettes are described in 2-4 Memory Cassettes. To install a Memory Cassette, follow the procedure outlined below.
!
Caution Be careful to always turn the power off before inserting or removing a Memory Cassette. If a
Memory Cassette is inserted into or removed from the CPU with the power on, it may cause the
CPU to malfunction or cause damage to the memory.
1, 2, 3...
1. Set the DIP switch. For an EEPROM Memory Cassette, set pin no. 1 (write protect) to either ON or OFF. Setting it to ON will protect the program in the memory from being overwritten. Setting it to OFF will allow the program to be overwritten. (The factory setting is OFF.)
For an EPROM Memory Cassette, set pin no. 1 (ROM Type Selector) according to the type of ROM that is to be mounted.
Pin no. 1
OFF
ON
ROM type
27256
27512
Model
ROM-JD-B
ROM-KD-B
Capacity
16K words
32K words*
Access speed
150 ns
150 ns
Note *Only 16K words accessible.
2. Write to EPROM (if using an EPROM Memory Cassette). Using a PROM
Writer, write the program to EPROM. Then mount the EPROM chip to the
Memory Cassette, with the notched end facing upwards as shown in the illustration below.
Notch
21
Installing Memory Cassettes Section 2-5
3. Remove the bracket from the Memory Cassette, as shown in the illustration below.
Metal bracket
4. Check that the connector side goes in first and that the Cassette’s circuit components face right and then insert the Cassette into the CPU. The Cassette slides in along a track in the CPU.
5. Replace the Memory Cassette bracket over the Cassette and tighten the screw that holds the bracket.
22
CPU DIP Switch Section 2-6
2-6 CPU DIP Switch
The DIP switch on C200HS CPUs is located between the Memory Cassette compartment and battery.
The 6 pins on the DIP switch control 6 of the CPU’s operating parameters.
Pin no.
1
Item
Memory protect
2
3
4
5
6
Automatic transfer of Memory
Cassette contents
Expansion instruction setting
Communications parameters h AR 0709 i ON
Setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Function
Program Memory and read-only DM (DM 6144 to DM 6655) data cannot be overwritten from a Peripheral Device.
Program Memory and read-only DM (DM 6144 to DM 6655) data can be overwritten from a Peripheral Device.
The contents of the Memory Cassette will be automatically transferred to the internal RAM at start-up.
The contents will not be automatically transferred.
Programming Console messages will be displayed in English.
Programming Console messages will be displayed in the language stored in system ROM. (Messages will be displayed in Japanese with the Japanese version of system ROM.)
Expansion instructions set by user. Normally ON when using a host computer for programming/monitoring.
Expansion instructions set to defaults.
Standard communications parameters (see note) will be set for the following serial communications ports.
• Built-in RS-232C port
• Peripheral port (only when a CQM1-CIF01/-CIF02 Cable is connected. Does not apply to Programming Console.)
Note 1. Standard communications parameters are as follows:
Serial communications mode: Host Link or peripheral bus; start bits: 1; data length: 7 bits; parity: even; stop bits: 2; baud rate: 9,600 bps
2. The CX-Programmer running on a personal computer can be connected to the peripheral port via the peripheral bus using the above standard communications parameters.
The communications parameters for the following serial communications ports will be set in PC Setup as follows:
• Built-in RS-232C port: DM 6645 and DM 6646
• Peripheral port: DM 6650 and DM 6651
Note When the CX-Programmer is connected to the peripheral port with the peripheral bus, either set bits 00 to 03 of DM
6650 to 0 Hex (for standard parameters), or set bits 12 to
15 of DM 6650 to 0 Hex and bits 00 to 03 of DM 6650 to 1
Hex (for Host Link or peripheral bus) separately.
Expansion TERMINAL mode; AR 0712 ON.
Normal mode; AR 0712: OFF
Note The above settings apply to CPUs manufactured from July 1995 (lot number **75 for July 1995). For CPUs manufactured before July 1995 (lot number **65 for June 1995), only 1 stop bit will be set and the baud rate will be 2,400 bps.
23
SECTION 3
Memory Areas
Various types of data are required to achieve effective and correct control. To facilitate managing this data, the PC is provided with various memory areas for data, each of which performs a different function. The areas generally accessible by the user for use in programming are classified as data areas. The other memory area is the UM Area, where the user’s program is actually stored. This section describes these areas individually and provides information that will be necessary to use them. As a matter of convention, the TR area is described in this section, even though it is not strictly a memory area.
3-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Data Area Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 IR (Internal Relay) Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 SR (Special Relay) Area
3-4-1
3-4-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYSMAC NET/SYSMAC LINK System
Remote I/O Systems
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-3
3-4-4
Link System Flags and Control Bits
Forced Status Hold Bit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-5
3-4-6
3-4-7
I/O Status Hold Bit
Output OFF Bit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FAL (Failure Alarm) Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-8
3-4-9
Low Battery Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cycle Time Error Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-10 I/O Verification Error Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-11 First Cycle Flag
3-4-12 Clock Pulse Bits
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-13 Step Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-14 Group-2 Error Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-15 Special Unit Error Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-16 Instruction Execution Error Flag, ER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-17 Arithmetic Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-18 Interrupt Subroutine Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-19 RS-232C Port Communications Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-20 Peripheral Port Communications Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-21 Memory Cassette Areas
3-4-22 Data Transfer Error Bits
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-23 Ladder Diagram Memory Areas
3-4-24 Memory Error Flags
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-25 Data Save Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-26 Transfer Error Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-27 PC Setup Error Flags
3-5 AR (Auxiliary Relay) Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-1
3-5-2
3-5-3
3-5-4
Restarting Special I/O Units
Slave Rack Error Flags
Group-2 Error Flags
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optical I/O Unit and I/O Terminal Error Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-5
3-5-6
3-5-7
SYSMAC LINK System Data Link Settings
Error History Bits
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Active Node Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-8
3-5-9
SYSMAC LINK/SYSMAC NET Link System Service Time
Calendar/Clock Area and Bits
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-10 TERMINAL Mode Key Bits
3-5-11 Power OFF Counter
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-12 Cycle Time Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-13 Link Unit Mounted Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-14 CPU-mounting Device Mounted Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-15 FPD Trigger Bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-16 Data Tracing Flags and Control Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-17 Cycle Time Indicators
3-6 DM (Data Memory) Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6-1
3-6-2
3-6-3
Expansion DM Area
Special I/O Unit Data
Error History Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6-4 PC Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 HR (Holding Relay) Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8 TC (Timer/Counter) Area
3-9 LR (Link Relay) Area
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-10 UM Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-11 TR (Temporary Relay) Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
51
51
52
52
52
53
54
54
54
54
48
48
50
50
50
50
56
56
57
58
60
54
54
54
55
44
44
44
45
45
46
46
47
47
47
47
48
42
42
42
42
43
43
43
43
44
44
27
31
33
37
39
39
41
60
61
61
61
25
Introduction
3-1 Introduction
Section 3-1
Details, including the name, size, and range of each area are summarized in the following table. Data and memory areas are normally referred to by their acronyms, e.g., the IR Area, the SR Area, etc.
I/O Area
Area
Group-2 High-density
I/O Unit and B7A
Interface Unit Area
SYSMAC BUS Area
Special I/O Unit Area
Optical I/O Unit and I/O
Terminal Area
Work Area 1
Special Relay Area 1
Special Relay Area 2
Macro Area
Work Area 2
1,600 bits
512 bits
64 bits
312 bits
704 bits
64 bits
64 bits
3,392 bits
Temporary Relay Area 8 bits
Holding Relay Area
Auxiliary Relay Area
Link Relay Area
Timer/Counter Area
Fixed DM Area
Expansion DM Area
480 bits
320 bits
800 bits
Size
1,600 bits
Range
IR 000 to IR 029
IR 030 to IR 049
IR 050 to IR 099
IR 100 to IR 199
IR 200 to IR 231
IR 232 to IR 235
SR 23600 to SR
25507
SR 256 to SR 299
(298 to 299 reserved by system)
SR 290 to SR 293
SR 294 to SR 297
IR 300 to IR 511
TR 00 to TR 07
HR 00 to HR 99
Comments
I/O words are allocated to the CPU Rack and
Expansion I/O Racks by slot position.
1
Allocated to Group-2 High-density I/O Units and to Group-2 B7A Interface Units 0 to 9
1
Allocated to Remote I/O Slave Racks 0 to 4.
1
Allocated to Special I/O Units 0 to 9.
1
Allocated to Optical I/O Units and I/O
Terminals.
1
For use as work bits in the program.
Contains system clocks, flags, control bits, and status information.
Contains flags, control bits, and status information.
Inputs
Outputs
For use as work bits in the program.
Used to temporarily store and retrieve execution conditions when programming certain types of branching ladder diagrams.
Used to store data and to retain the data values when the power to the PC is turned off.
448 buts
1,024 bits
512 counters/ timers
AR 00 to AR 27
LR 00 to LR 63
TC 000 to TC 511
Contains flags and bits for special functions. Retains status during power failure.
Used for data links in the PC Link System.
1
Used to define timers and counters, and to access completion flags, PV, and SV.
Interval timers 0 through 2 and high-speed counters 0 through 2 provided in separate area.
TIM 000 through TIM 015 can be refreshed via interrupt processing as high-speed timers.
DM 0000 to DM 6143 Read/Write 6,144 words
1,000 words DM 0000 to DM 0999 Normal DM.
1,000 words DM 1000 to DM 1999 Special I/O Unit Area
2
4,000 words DM 2000 to DM 5999 Normal DM.
31 words DM 6000 to DM 6030 History Log
(44 words)
512 words
DM 6100 to DM 6143
DM 6144 to DM 6599
Link test area (reserved)
Fixed DM Area (read only)
56 words DM 6600 to DM 6655 PC Setup
3,000 words max.
DM 7000 to DM 9999 Read only
Note 1. These can be used as work words and bits when not used for their allocated purposes.
2. The PC Setup can be set to use DM 7000 through DM 7999 as the Special
I/O Area.
26
Data Area Structure Section 3-2
Work Bits and Words
Flags and Control Bits
When some bits and words in certain data areas are not being used for their intended purpose, they can be used in programming as required to control other bits. Words and bits available for use in this fashion are called work words and work bits. Most, but not all, unused bits can be used as work bits. Those that can be used are described area-by-area in the remainder of this section. Actual application of work bits and work words is described in Section 4 Writing and Input-
ting the Program.
Some data areas contain flags and/or control bits. Flags are bits that are automatically turned ON and OFF to indicate particular operation status. Although some flags can be turned ON and OFF by the user, most flags are read only; they cannot be controlled directly.
Control bits are bits turned ON and OFF by the user to control specific aspects of operation. Any bit given a name using the word bit rather than the word flag is a control bit, e.g., Restart bits are control bits.
3-2 Data Area Structure
When designating a data area, the acronym for the area is always required for any but the IR and SR areas. Although the acronyms for the IR and SR areas are often given for clarity in text explanations, they are not required, and not entered, when programming. Any data area designation without an acronym is assumed to be in either the IR or SR area. Because IR and SR addresses run consecutively, the word or bit addresses are sufficient to differentiate these two areas.
An actual data location within any data area but the TC area is designated by its address. The address designates the bit or word within the area where the desired data is located. The TC area consists of TC numbers, each of which is used for a specific timer or counter defined in the program. Refer to 3-8 TC Area for more details on TC numbers and to 5-14 Timer and Counter Instructions for information on their application.
The rest of the data areas (i.e., the IR, SR, HR, DM, AR, and LR areas) consist of words, each of which consists of 16 bits numbered 00 through 15 from right to left. IR words 000 and 001 are shown below with bit numbers. Here, the content of each word is shown as all zeros. Bit 00 is called the rightmost bit; bit 15, the leftmost bit.
The term least significant bit is often used for rightmost bit; the term most significant bit, for leftmost bit. These terms are not used in this manual because a single data word is often split into two or more parts, with each part used for different parameters or operands. When this is done, the rightmost bits of a word may actually become the most significant bits, i.e., the leftmost bits in another word,when combined with other bits to form a new word.
Bit number
IR word 000
IR word 001
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
The DM area is accessible by word only; you cannot designate an individual bit within a DM word. Data in the IR, SR, HR, AR, and LR areas is accessible either by word or by bit, depending on the instruction in which the data is being used.
To designate one of these areas by word, all that is necessary is the acronym (if required) and the two-, three-, or four-digit word address. To designate an area by bit, the word address is combined with the bit number as a single four- or fivedigit address. The following table show examples of this. The two rightmost digits of a bit designation must indicate a bit between 00 and 15, i.e., the rightmost digit must be 5 or less the next digit to the left, either 0 or 1.
27
Data Area Structure Section 3-2
Data Structure
Digit number
Bit number
Contents
The same TC number can be used to designate either the present value (PV) of the timer or counter, or a bit that functions as the Completion Flag for the timer or counter. This is explained in more detail in 3-8 TC Area.
Area
IR
SR
DM
TC
LR
Word designation
000
252
DM 1250
TC 215 (designates PV)
LR 12
Bit designation
00015 (leftmost bit in word 000)
25200 (rightmost bit in word 252)
Not possible
TC 215 (designates completion flag)
LR 1200
Word data input as decimal values is stored in binary-coded decimal (BCD); word data entered as hexadecimal is stored in binary form. Each four bits of a word represents one digit, either a hexadecimal or decimal digit, numerically equivalent to the value of the binary bits. One word of data thus contains four digits, which are numbered from right to left. These digit numbers and the corresponding bit numbers for one word are shown below.
3 2 1 0
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Converting Different Forms of Data
When referring to the entire word, the digit numbered 0 is called the rightmost digit; the one numbered 3, the leftmost digit.
When inputting data into data areas, it must be input in the proper form for the intended purpose. This is no problem when designating individual bits, which are merely turned ON (equivalent to a binary value of 1) or OFF (a binary value of
0). When inputting word data, however, it is important to input it either as decimal or as hexadecimal, depending on what is called for by the instruction it is to be used for. Section 5 Instruction Set specifies when a particular form of data is required for an instruction.
Binary and hexadecimal can be easily converted back and forth because each four bits of a binary number is numerically equivalent to one digit of a hexadecimal number. The binary number 0101111101011111 is converted to hexadecimal by considering each set of four bits in order from the right. Binary 1111 is hexadecimal F; binary 0101 is hexadecimal 5. The hexadecimal equivalent would thus be 5F5F, or 24,415 in decimal (16 3 x 5 + 16 2 x 15 + 16 x 5 + 15).
Decimal and BCD are easily converted back and forth. In this case, each BCD digit (i.e., each group of four BCD bits) is numerically equivalent of the corresponding decimal digit. The BCD bits 0101011101010111 are converted to decimal by considering each four bits from the right. Binary 0101 is decimal 5; binary
0111 is decimal 7. The decimal equivalent would thus be 5,757. Note that this is not the same numeric value as the hexadecimal equivalent of
0101011101010111, which would be 5,757 hexadecimal, or 22,359 in decimal
(16
3
x 5 + 16
2
x 7 + 16 x 5 + 7).
Because the numeric equivalent of each four BCD binary bits must be numerically equivalent to a decimal value, any four bit combination numerically greater then 9 cannot be used, e.g., 1011 is not allowed because it is numerically equivalent to 11, which cannot be expressed as a single digit in decimal notation. The binary bits 1011 are of course allowed in hexadecimal are a equivalent to the hexadecimal digit C.
There are instructions provided to convert data either direction between BCD and hexadecimal. Refer to 5-18 Data Conversion for details. Tables of binary equivalents to hexadecimal and BCD digits are provided in the appendices for reference.
28
Data Area Structure Section 3-2
Decimal Points Decimal points are used in timers only. The least significant digit represents tenths of a second. All arithmetic instructions operate on integers only.
Signed and Unsigned Binary Data
This section explains signed and unsigned binary data formats. Many instructions can use either signed or unsigned data and a few (CPS(––), CPSL(––),
DBS(––), DBSL(––), MBS(––), and MBSL(––)) use signed data exclusively.
Unsigned binary Unsigned binary is the standard format used in OMRON PCs. Data in this manual are unsigned unless otherwise stated. Unsigned binary values are always positive and range from 0 ($0000) to 65,535 ($FFFF). Eight-digit values range from 0 ($0000 0000) to 4,294,967,295 ($FFFF FFFF).
Digit value 16 3 16 2 16 1 16 0
Bit number
Contents
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Signed Binary Signed binary data can have either a positive and negative value. The sign is indicated by the status of bit 15. If bit 15 is OFF, the number is positive and if bit 15 is ON, the number is negative. Positive signed binary values range from 0
($0000) to 32,767 ($7FFF), and negative signed binary values range from
–32,768 ($8000) to –1 ($FFFF).
Sign indicator
Digit value
Bit number
Contents
16 3 16 2 16 1 16 0
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Eight-digit positive values range from 0 ($0000 0000) to 2,147,483,647 ($7FFF
FFFF), and eight-digit negative values range from –2,147,483,648 ($8000
0000) to –1 ($FFFF FFFF).
29
Data Area Structure
Converting Decimal to
Signed Binary
Section 3-2
The following table shows the corresponding decimal, 16-bit hexadecimal, and
32-bit hexadecimal values.
Decimal
2147483647
2147483646
.
32768
.
.
32767
32766
2
.
.
.
1
0
–1
–32767
–32768
–32769
.
.
.
–2
.
.
.
–2147483647
–2147483648
16-bit Hex
–––
–––
.
–––
.
.
7FFF
7FFE
0002
.
.
.
0001
0000
FFFF
FFFE
.
.
.
8001
8000
–––
.
.
.
–––
–––
32-bit Hex
7FFFFFFF
7FFFFFFE
00008000
.
.
.
00007FFF
00007FFE
00000002
.
.
.
00000001
00000000
FFFFFFFF
FFFFFFFE
.
.
.
FFFF8001
FFFF8000
FFFF7FFF
.
.
.
80000001
80000000
Positive signed binary data is identical to unsigned binary data (up to 32,767) and can be converted using BIN(100). The following procedure converts negative decimal values between –32,768 and –1 to signed binary. In this example
–12345 is converted to CFC7.
Bit number
Contents
Bit number
Contents
Bit number
Contents
1. First take the absolute value (12345) and convert to unsigned binary:
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 1 1 0 0 0 0 0 0 1 1 1 0 0 1
2. Next take the complement:
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
1 1 0 0 1 1 1 1 1 1 0 0 0 1 1 0
3. Finally add one:
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
1 1 0 0 1 1 1 1 1 1 0 0 0 1 1 1
Reverse the procedure to convert negative signed binary data to decimal.
30
IR Area Section 3-3
3-3 IR (Internal Relay) Area
The IR area is used both as data to control I/O points, and as work bits to manipulate and store data internally. It is accessible both by bit and by word. In the
C200HS PC, the IR area is comprised of words 000 to 235 and 298 to 511.
Words in the IR area that are used to control I/O points are called I/O words. Bits in I/O words are called I/O bits. Bits in the IR area which are not assigned as I/O bits can be used as work bits. IR area work bits are reset when power is interrupted or PC operation is stopped.
I/O Words
Input Bit Usage
If a Unit brings inputs into the PC, the bit assigned to it is an input bit; if the Unit sends an output from the PC, the bit is an output bit. To turn on an output, the output bit assigned to it must be turned ON. When an input turns on, the input bit assigned to it also turns ON. These facts can be used in the program to access input status and control output status through I/O bits.
Input bits can be used to directly input external signals to the PC and can be used in any order in programming. Each input bit can also be used in as many instructions as required to achieve effective and proper control. They cannot be used in instructions that control bit status, e.g., the OUTPUT, DIFFERENTIATION UP, and KEEP instructions.
Output Bit Usage Output bits are used to output program execution results and can be used in any order in programming. Because outputs are refreshed only once during each cycle (i.e., once each time the program is executed), any output bit can be used in only one instruction that controls its status, including OUT, KEEP(11),
DIFU(13), DIFD(14) and SFT(10). If an output bit is used in more than one such instruction, only the status determined by the last instruction will actually be output from the PC.
See 5-15-1 Shift Register – SFT(10) for an example that uses an output bit in two
‘bit-control’ instructions.
Word Allocation for Racks I/O words are allocated to the CPU Rack and Expansion I/O Racks by slot position. One I/O word is allocated to each slot, as shown in the following table. Since each slot is allocated only one I/O word, a 3-slot rack uses only the first 3 words, a 5-slot rack uses only the first 5 words, and an 8-slot rack uses only the first 8 words. Words that are allocated to unused or nonexistent slots are available as work words.
←
Left side of rack Right side of a 10-slot rack
→
Rack
CPU
1 st Expansion
2 nd Expansion
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Slot 9 Slot 10
IR 000 IR 001 IR 002 IR 003 IR 004 IR 005 IR 006 IR 007 IR 008 IR 009
IR 010 IR 011 IR 012 IR 013 IR 014 IR 015 IR 016 IR 017 IR 018 IR 019
IR 020 IR 021 IR 022 IR 023 IR 024 IR 025 IR 026 IR 027 IR 028 IR 029
Unused Words Any words allocated to a Unit that does not use them can be used in programming as work words and bits. Units that do not used the words assigned to the slot they are mounted to include Link Units (e.g., Host Link Units, PC Link Units,
SYSMAC NET Link Units, etc.), Remote I/O Master Units, Special I/O Units,
Group-2 High-density I/O Units, Group-2 B7A Interface Units, and Auxiliary
Power Supply Units.
31
IR Area Section 3-3
Allocation for Special I/O
Units and Slave Racks
Up to ten Special I/O Units may be mounted in any slot of the CPU Rack or Expansion I/O Racks. Up to five Slave Racks may be used, whether one or two
Masters are used. IR area words are allocated to Special I/O Units and Slave
Racks by the unit number on the Unit, as shown in the following tables.
4
5
6
1
2
3
7
8
9
Special I/O Units Slave Racks
Unit number IR address Unit number IR address
0 100 to 109 0 050 to 059
110 to 119 1
120 to 129 2
130 to 139 3
140 to 149 4
150 to 159
160 to 169
170 to 179
180 to 189
190 to 199
060 to 069
070 to 079
080 to 089
090 to 099
Allocation for Optical I/O
Units and I/O Terminals
The C500-RT001/002-(P)V1 Remote I/O Slave Rack may be used, but it requires 20 I/O words, not 10, and therefore occupies the I/O words allocated to 2
C200H Slave Racks, both the words allocated to the unit number set on the rack and the words allocated to the following unit number. When using a C200HS
CPU, do not set the unit number on a C500 Slave Rack to 4, because there is no unit number 5. I/O words are allocated only to installed Units, from left to right, and not to slots as in the C200HS system.
I/O words between IR 200 and IR 231 are allocated to Optical I/O Units and I/O
Terminals by unit number. The I/O word allocated to each Unit is IR 200+n, where n is the unit number set on the Unit.
Allocation for Remote I/O
Master and Link Units
Remote Master I/O Units and Host Link Units do not use I/O words, and the PC
Link Units use the LR area, so words allocated to the slots in which these Units are mounted are available as work words.
Bit Allocation for I/O Units An I/O Unit may require anywhere from 8 to 16 bits, depending on the model.
With most I/O Units, any bits not used for input or output are available as work bits. Transistor Output Units C200H-OD213 and C200H-OD411, as well as Triac
Output Unit C200H-OA221, however, uses bit 08 for the Blown Fuse Flag. Transistor Output Unit C200H-OD214 uses bits 08 to 11 for the Alarm Flag. Bits 08 to
15 of any word allocated to these Units, therefore, cannot be used as work bits.
Bit Allocation for Interrupt
Input Units
The Interrupt Input Unit uses the 8 bits of the first I/O word allocated to its slot in the CPU Rack. (An Interrupt Input Unit will operate as a normal Input Unit when installed in an Expansion I/O Rack.) The other 24 bits allocated to its slot in the
CPU Rack can be used as work bits.
32
SR Area Section 3-4
Allocation for Group-2
High-density I/O Units and
B7 Interface Units
Group-2 High-density I/O Units and B7A Interface Units are allocated words between IR 030 and IR 049 according to I/O number settings made on them and do not use the words allocated to the slots in which they are mounted. For 32-point
Units, each Unit is allocated two words; for 64-point Units, each Unit is allocated four words. The words allocated for each I/O number are in the following tables.
Any words or part of words not used for I/O can be used as work words or bits in programming.
7
8
5
6
9
3
4
1
2
32-point Units
I/O number
0
Words
IR 30 to IR 31
IR 32 to IR 33
IR 34 to IR 35
IR 36 to IR 37
IR 38 to IR 39
IR 40 to IR 41
IR 42 to IR 43
IR 44 to IR 45
IR 46 to IR 47
IR 48 to IR 49
7
8
5
6
9
3
4
1
2
64-point Units
I/O number
0
Words
IR 30 to IR 33
IR 32 to IR 35
IR 34 to IR 37
IR 36 to IR 39
IR 38 to IR 41
IR 40 to IR 43
IR 42 to IR 45
IR 44 to IR 47
IR 46 to IR 49
Cannot be used.
When setting I/O numbers on the High-density I/O Units and B7A Interface
Units, be sure that the settings will not cause the same words to be allocated to more than one Unit. For example, if I/O number 0 is allocated to a 64-point Unit,
I/O number 1 cannot be used for any Unit in the system.
Group-2 High-density I/O Units and B7A Interface Units are not considered Special I/O Units and do not affect the limit to the number of Special I/O Units allowed in the System, regardless of the number used.
The words allocated to Group-2 High-density I/O Units correspond to the connectors on the Units as shown in the following table.
Unit
First
Second
First
Second
Third
Fourth
Word Connector/row
Row A
Row B
CN1, row A
CN1, row B
CN2, row A
CN2, row B
Note Group-2 High-density I/O Units and B7A Interface Units cannot be mounted to
Slave Racks.
3-4 SR (Special Relay) Area
The SR area contains flags and control bits used for monitoring PC operation, accessing clock pulses, and signalling errors. SR area word addresses range from 236 through 511; bit addresses, from 23600 through 51115.
The following table lists the functions of SR area flags and control bits. Most of these bits are described in more detail following the table. Descriptions are in order by bit number except that Link System bits are grouped together.
Unless otherwise stated, flags are OFF until the specified condition arises, when they are turned ON. Restart bits are usually OFF, but when the user turns one
ON then OFF, the specified Link Unit will be restarted. Other control bits are OFF until set by the user.
33
SR Area Section 3-4
Note all SR words and bits are writeable by the user. Be sure to check the function of a bit or word before attempting to use it in programming.
Word(s)
236
237
238 and 241
242 and 245
Bit(s)
00 to 07
08 to 15
00 to 07
08 to 15
00 to 15
00 to 15
Function
Node loop status output area for operating level 0 of SYSMAC NET Link System
Node loop status output area for operating level 1 of SYSMAC NET Link System
Completion code output area for operating level 0 following execution of
SEND(90)/RECV(98) SYSMAC LINK/SYSMAC NET Link System
Completion code output area for operating level 1 following execution of
SEND(90)/RECV(98) SYSMAC LINK/SYSMAC NET Link System
Data link status output area for operating level 0 of SYSMAC LINK or SYSMAC NET Link
System
Data link status output area for operating level 1 of SYSMAC LINK or SYSMAC NET Link
System
246 00 to 15
247 and 248 00 to 07
08 to 15
249 and 250 00 to 07
251
08 to 15
00
Reserved by system
PC Link Unit Run Flags for Units 16 through 31 or data link status for operating level 1
PC Link Unit Error Flags for Units 16 through 31 or data link status for operating level 1
PC Link Unit Run Flags for Units 00 through 15 or data link status for operating level 0
PC Link Unit Error Flags for Units 00 through 15 or data link status for operating level 0
Remote I/O Error Read Bit
01 and 02 Not used
03 Remote I/O Error Flag
04 to 06
07
08 to 15
Unit number of Remote I/O Unit, Optical I/O Unit, or I/O Terminal with error
Not used
Word allocated to Remote I/O Unit, Optical I/O Unit, or I/O Terminal with error (BCD)
252 00
253
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
00 to 07
08
09
10
11
12
13
14
15
SEND(90)/RECV(98) Error Flag for operating level 0 of SYSMAC LINK or SYSMAC NET
Link System
SEND(90)/RECV(98) Enable Flag for operating level 0 of SYSMAC LINK or SYSMAC NET
Link System
Operating Level 0 Data Link Operating Flag
SEND(90)/RECV(98) Error Flag for operating level 1 of SYSMAC LINK or SYSMAC NET
Link System
SEND(90)/RECV(98) Enable Flag for operating level 1 of SYSMAC LINK or SYSMAC NET
Link System
Operating Level 1 Data Link Operating Flag
Rack-mounting Host Link Unit Level 1 Communications Error Flag
Rack-mounting Host Link Unit Level 1 Restart Bit
Peripheral Port Restart Bit
RS-232C Port Restart Bit
PC Setup Clear Bit
Forced Status Hold Bit
Data Retention Control Bit
Rack-mounting Host Link Unit Level 0 Restart Bit
Not used.
Output OFF Bit
FAL number output area (see error information provided elsewhere)
Low Battery Flag
Cycle Time Error Flag
I/O Verification Error Flag
Rack-mounting Host Link Unit Level 0 Communications Error Flag
Remote I/O Error Flag
Always ON Flag
Always OFF Flag
First Cycle Flag
34
SR Area Section 3-4
Word(s)
254
255
256 to 261
262
263
264
265
266
00 to 03
04
05
06
07
08 to 11
12
13
14
00
01
02
03
13
14
15
04
05
06
07
08 to 15
00 to 15
00 to 15
00 to 15
09
10
11
12
05
06
07
08
00
01
Bit(s) Function
1-minute clock pulse bit
0.02-second clock pulse bit
02 and 03 Reserved for function expansion. Do not use.
04 Overflow Flag (for signed binary calculations)
Underflow Flag (for signed binary calculations)
Differential Monitor End Flag
Step Flag
MTR Execution Flag
7SEG Execution Flag
DSW Execution Flag
Interrupt Input Unit Error Flag
Reserved by system
Interrupt Programming Error Flag
Group-2 Error Flag
Special Unit Error Flag (includes Special I/O, PC Link, Host Link, Remote I/O Master Units)
0.1-second clock pulse bit
0.2-second clock pulse bit
1.0-second clock pulse bit
Instruction Execution Error (ER) Flag
Carry (CY) Flag
Greater Than (GR) Flag
Equals (EQ) Flag
Less Than (LE) Flag
Reserved by system (used for TR bits)
Reserved by system
Longest interrupt subroutine (action) execution time (0.1 ms)
Number of interrupt subroutine (action) with longest execution time.
15
00 to 15
00 to 15
(8000 to 8512) 8000 to 8007, 8099
Bit 15: Interrupt Flag
RS-232C Port Error Code
0: No error 1: Parity error
2: Framing error
RS-232C Port Communications Error
RS-232C Port Send Ready Flag
3: Overrun error
RS-232C Port Reception Completed Flag
RS-232C Port Reception Overflow Flag
Peripheral Port Error Code in General I/O Mode
0: No error 1: Parity error
2: Framing error
F: When in Peripheral Bus Mode
3: Overrun error
Peripheral Port Communications Error in General I/O Mode
Peripheral Port Send Ready Flag in General I/O Mode
Peripheral Port Reception Completed Flag in General I/O Mode
Peripheral Port Reception Overflow Flag in General I/O Mode
RS-232C Port Reception Counter in General I/O Mode
Peripheral Reception Counter in General I/O Mode (BCD)
35
271
272
SR Area
Word(s)
267
268
269
270
36
Section 3-4
SR Area Section 3-4
Word(s)
273
274
275
276
277 to 279
280 to 289
290 to 293
294 to 297
298 to 299
00
Bit(s)
01
02 to 11
12
13
14
15
00
01
02
03
04
05
06
07
08
09
10 to 15
00
01
02
03 to 15
00 to 07
08 to 15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 15
Save IOM to Cassette Bit
Function
Data transferred to Memory Cassette when Bit is turned
Load IOM from Cassette Bit An error will be produced if turned ON in any other mode.
Reserved by system (not accessible by user)
Transfer Error Flag: Not
PROGRAM mode
Data will not be transferred from IOM to the Memory
Transfer Error Flag: Read Only
Transfer Error Flag: Insufficient
Capacity or No IOM
Transfer Error Flag: Checksum
Error
Special I/O Unit #0 Restart Flag g
Special I/O Unit #1 Restart Flag fl ill ON f U i
Special I/O Unit #2 Restart Flag
Special I/O Unit #3 Restart Flag
Special I/O Unit #4 Restart Flag
Special I/O Unit #5 Restart Flag
Special I/O Unit #6 Restart Flag
Special I/O Unit #7 Restart Flag p
Special I/O Unit #8 Restart Flag
Special I/O Unit #9 Restart Flag
Reserved by system (not accessible by user)
PC Setup Startup Error (DM 6600 to DM 6614)
PC Setup RUN Error (DM 6615 to DM 6644)
PC Setup Communications/Error Setting/Misc. Error (DM 6645 to DM 6655)
Reserved by system (not accessible by user)
Sl
Minutes (00 to 59)
Hours (00 to 23)
Used for time increments.
Used for keyboard mapping. See page 368.
Reserved by system (not accessible by user)
Macro Area inputs.
Macro Area outputs.
Reserved by system (not accessible by user) g
R k
3-4-1 SYSMAC NET/SYSMAC LINK System
Loop Status
–––
Level 0
Level 1
Status/
Meaning
SR 236 provides the local node loop status for SYSMAC NET Systems, as shown below.
07 06
15 14
1 1
05
13
Central Power Supply
0: Connected
1: Not connected
04
12
1
Bit in SR 236
03
11
Loop Status
11: Normal loop
10: Downstream backloop
01: Upstream backloop
00: Loop error
02
10
01
09
Reception Status
0: Reception enabled
1: Reception disabled
00
08
1
Completion Codes SR 23700 to SR23707 provide the SEND/RECV completion code for operating level 0 and SR 23708 to SR 23215 provide the SEND/RECV completion code for operating level 1. The completion codes are as given in the following tables.
37
SR Area
Data Link Status
Section 3-4
SYSMAC LINK
Code
00
01
02
03
04
05
06
07
08
09
Item
Normal end
Parameter error
Meaning
Processing ended normally.
Parameters for network communication instruction is not within acceptable ranges.
Unable to send
Destination not in network
Busy error
Communications controller error
Setting error
PC error
Unit reset during command processing or local node in not in network.
Destination node is not in network.
The destination node is processing data and cannot receive the command.
Response timeout The response monitoring time was exceeded.
Response error There was an error in the response received from the destination node.
An error occurred in the communications controller.
There is an error in the node address settings.
An error occurred in the CPU of the destination node.
03
04
05
06
07
SYSMAC NET
Code
00
01
Item
Normal end
Parameter error
02 Routing error
Busy error
Send error (token lost)
Loop error
No response
Response error
Meaning
Processing ended normally.
Parameters for network communication instruction is not within acceptable ranges.
There is a mistake in the routing tables for connection to a remote network.
The destination node is processing data and cannot receive the command.
The token was not received from the Line Server.
An error occurred in the communications loop.
The destination node does not exist or the response monitoring time was exceeded.
There is an error in the response format.
SR 238 to SR 245 contain the data link status for SYSMAC LINK/SYSMAC NET
Systems. The data structure depends on the system used to create the data link.
SYSMAC LINK l l 0
SR 238
SR 239
SR 240
SR 241 l l 1
SR 242
SR 243
SR 244
SR 245
12 to 15
Node 4
Node 8
Node 12
Node 16
11 to 08
Node 3
Node 7
Node 11
Node 15
Bit
04 to 07
Node 2
Node 6
Node 10
Node 14
00 to 03
Node 1
Node 5
Node 9
Node 13
Leftmost bit
1: PC RUN status 1: PC CPU error 1: Communications error
Rightmost bit
1: Data link operating
38
SR Area Section 3-4 l l 0
SR 238
SR 239
SR 240
SR 241 l l 1
SR 242
SR 243
SR 244
SR 245
SYSMAC NET
Bit (Node numbers below)
8
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
16 15 14 13 12 11 10 9 16 15 14 13 12 11 10 9
24 23 22 21 20 19 18 17 24 23 22 21 20 19 18 17
32 31 30 29 28 27 26 25 32 31 30 29 28 27 26 25
1: PC CPU error 1: PC RUN status
3-4-2 Remote I/O Systems
SR 25312 turns ON to indicate an error has occurred in Remote I/O Systems.
The ALM/ERR indicator will flash, but PC operation will continue. SR 251, as well as AR 0014 and AR 0015, contain information on the source and type of error. The function of each bit is described below. Refer to Optical and Wired Re-
mote I/O System Manuals for details.
Bit 00 – Error Check Bit
Bits 01 and 02
Bit 03
Bits 04 to 15
If there are errors in more than one Remote I/O Unit, word 251 will contain error information for only the first one. Data for the remaining Units will be stored in memory and can be accessed by turning the Error Check bit ON and OFF. Be sure to record data for the first error, which will be cleared when data for the next error is displayed.
Not used.
Remote I/O Error Flag: Bit 03 turns ON when an error has occurred in a Remote
I/O Unit.
The content of bits 04 to 06 is a 3-digit binary number (04: 2 0 , 05: 2 1 , 06: 2 2 ) and the content of bits 08 to 15 is a 2-digit BCD number (08 to 11: 10 0 , 12 to 15: 10 1 ).
If the content of bits 12 through 15 is B, an error has occurred in a Remote I/O
Master or Slave Unit, and the content of bits 08 through 11 will indicate the unit number, either 0 or 1, of the Master involved. In this case, bits 04 to 06 contain the unit number of the Slave Rack involved.
If the content of bits 12 through 15 is a number from 0 to 31, an error has occurred in an Optical I/O Unit or I/O Terminal. The number is the unit number of the
Optical I/O Unit or I/O Terminal involved, and bit 04 will be ON if the Unit is assigned leftmost word bits (08 through 15), and OFF if it is assigned rightmost word bits (00 through 07).
3-4-3 Link System Flags and Control Bits
Use of the following SR bits depends on the configuration of any Link Systems to which your PC belongs. These flags and control bits are used when Link Units, such as PC Link Units, Remote I/O Units, or Host Link Units, are mounted to the
PC Racks or to the CPU. For additional information, consult the System Manual for the particular Units involved.
The following bits can be employed as work bits when the PC does not belong to the Link System associated with them.
39
SR Area Section 3-4
Host Link Systems
Both Error flags and Restart bits are provided for Host Link Systems. Error flags turn ON to indicate errors in Host Link Units. Restart bits are turned ON and then
OFF to restart a Host Link Unit. SR bits used with Host Link Systems are summarized in the following table. Rack-mounting Host Link Unit Restart bits are
not effective for the Multilevel Rack-mounting Host Link Units. Refer to the
Host Link System Manual for details.
25206
25207
25213
25311
Bit Flag
Rack-mounting Host Link Unit Level 1 Error Flag
Rack-mounting Host Link Unit Level 1 Restart Bit
Rack-mounting Host Link Unit Level 0 Restart Bit
Rack-mounting Host Link Unit Level 0 Error Flag
PC Link Systems
PC Link Unit Error and Run
Flags
Single-level PC Link
Systems
When the PC belongs to a PC Link System, words 247 through 250 are used to monitor the operating status of all PC Link Units connected to the PC Link System. This includes a maximum of 32 PC Link Units. If the PC is in a Multilevel PC
Link System, half of the PC Link Units will be in a PC Link Subsystem in operating level 0; the other half, in a Subsystem in operating level 1. The actual bit assignments depend on whether the PC is in a Single-level PC Link System or a Multilevel PC Link System. Refer to the PC Link System Manual for details. Error and
Run Flag bit assignments are described below.
Bits 00 through 07 of each word are the Run flags, which are ON when the PC
Link Unit is in RUN mode. Bits 08 through 15 are the Error flags, which are ON when an error has occurred in the PC Link Unit. The following table shows bit assignments for Single-level and Multi-level PC Link Systems.
Flag type
Run flags
06
07
Error flags 08
09
10
11
12
13
14
15
02
03
04
05
00
01
Bit no.
SR 247
Unit #24
Unit #25
Unit #26
Unit #27
Unit #28
Unit #29
Unit #30
Unit #31
Unit #24
Unit #25
Unit #26
Unit #27
Unit #28
Unit #29
Unit #30
Unit #31
SR 248
Unit #16
Unit #17
Unit #18
Unit #19
Unit #20
Unit #21
Unit #22
Unit #23
Unit #16
Unit #17
Unit #18
Unit #19
Unit #20
Unit #21
Unit #22
Unit #23
SR 249
Unit #8
Unit #9
Unit #10
Unit #11
Unit #12
Unit #13
Unit #14
Unit #15
Unit #8
Unit #9
Unit #10
Unit #11
Unit #12
Unit #13
Unit #14
Unit #15
SR 250
Unit #0
Unit #1
Unit #2
Unit #3
Unit #4
Unit #5
Unit #6
Unit #7
Unit #0
Unit #1
Unit #2
Unit #3
Unit #4
Unit #5
Unit #6
Unit #7
40
SR Area Section 3-4
Multilevel PC Link Systems
Application Example
Flag type
Run flags 00
Bit no.
01
02
03
04
05
06
07
Error flags 08
09
10
11
12
13
14
15
Unit #14, level 1
Unit #15, level 1
Unit #8, level 1
Unit #9, level 1
Unit #10, level 1
Unit #11, level 1
SR 247
Unit #8, level 1
Unit #9, level 1
Unit #10, level 1
Unit #11, level 1
Unit #12, level 1
Unit #13, level 1
Unit #12, level 1
Unit #13, level 1
Unit #14, level 1
Unit #15, level 1
Unit #6, level 1
Unit #7, level 1
Unit #0, level 1
Unit #1, level 1
Unit #2, level 1
Unit #3, level 1
SR 248
Unit #0, level 1
Unit #1, level 1
Unit #2, level 1
Unit #3, level 1
Unit #4, level 1
Unit #5, level 1
Unit #4, level 1
Unit #5, level 1
Unit #6, level 1
Unit #7, level 1
Unit #14, level 0
Unit #15, level 0
Unit #8, level 0
Unit #9, level 0
Unit #10, level 0
Unit #11, level 0
SR 249
Unit #8, level 0
Unit #9, level 0
Unit #10, level 0
Unit #11, level 0
Unit #12, level 0
Unit #13, level 0
Unit #12, level 0
Unit #13, level 0
Unit #14, level 0
Unit #15, level 0
Unit #6, level 0
Unit #7, level 0
Unit #0, level 0
Unit #1, level 0
Unit #2, level 0
Unit #3, level 0
SR 250
Unit #0, level 0
Unit #1, level 0
Unit #2, level 0
Unit #3, level 0
Unit #4, level 0
Unit #5, level 0
Unit #4, level 0
Unit #5, level 0
Unit #6, level 0
Unit #7, level 0
If the PC is in a Multilevel PC Link System and the content of word 248 is 02FF, then PC Link Units #0 through #7 of in the PC Link Subsystem assigned operating level 1 would be in RUN mode, and PC Link Unit #1 in the same Subsystem would have an error. The hexadecimal digits and corresponding binary bits of word 248 would be as shown below.
Bit no.
Binary
Hex
15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 00
0 0 0 0 0 0 1 0 1 1 1 1 1 1 1 1
0 2 F F
3-4-4 Forced Status Hold Bit
SR 25211 determines whether or not the status of bits that have been force-set or force-reset is maintained when switching between PROGRAM and MONI-
TOR mode to start or stop operation. If SR 25211 is ON, bit status will be maintained; if SR 25211 is OFF, all bits will return to default status when operation is started or stopped. The Forced Status Hold Bit is only effective when enabled in the PC Setup.
The status of SR 25211 in not affected by a power interruption unless the I/O table is registered; in that case, SR 25211 will go OFF.
SR 25211 is not effective when switching to RUN mode.
SR 25211 should be manipulated from a Peripheral Device, e.g., a Programming Console or LSS.
41
SR Area Section 3-4
Maintaining Status during
Startup
The status of SR 25211 and thus the status of force-set and force-reset bits can be maintained when power is turned off and on by enabling the Forced Status
Hold Bit in the PC Setup. If the Forced Status Hold Bit is enabled, the status of
SR 25211 will be preserved when power is turned off and on. If this is done and
SR 25211 is ON, then the status of force-set and force-reset bits will also be preserved, as shown in the following table.
ON
OFF
Status before shutdown
SR 25211
Status at next startup
ON
SR 25211
OFF
Force-set/reset bits
Status maintained
Reset
Note Refer to 3-6-4 PC Setup for details on enabling the Forced Status Hold Bit.
3-4-5 I/O Status Hold Bit
SR 25212 determines whether or not the status of IR and LR area bits is maintained when operation is started or stopped, when operation begins by switching from PROGRAM mode to MONITOR or RUN modes. If SR 25212 is ON, bit status will be maintained; if SR 25212 is OFF, all IR and LR area bits will be reset.
The I/O Status Hold Bit is effective only if enabled in the PC Setup.
The status of SR 25212 in not affected by a power interruption unless the I/O table is registered; in that case, SR 25212 will go OFF.
SR 25212 should be manipulated from a Peripheral Device, e.g., a Programming Console or LSS.
Maintaining Status during
Startup
The status of SR 25212 and thus the status of IR and LR area bits can be maintained when power is turned off and on by enabling the I/O Status Hold Bit in the
PC Setup. If the I/O Status Hold Bit is enabled, the status of SR 25212 will be preserved when power is turned off and on. If this is done and SR 25212 is ON, then the status of IR and LR area bits will also be preserved, as shown in the following table.
ON
OFF
Status before shutdown
SR 25212
Status at next startup
ON
SR 25212
OFF
IR and LR bits
Status maintained
Reset
Note Refer to 3-6-4 PC Setup for details on enabling the I/O Status Hold Bit.
3-4-6 Output OFF Bit
SR bit 25215 is turned ON to turn OFF all outputs from the PC. The OUT INHIBIT indicator on the front panel of the CPU will light. When the Output OFF Bit is OFF, all output bits will be refreshed in the usual way.
The status of the Output OFF Bit is maintained for power interruptions or when
PC operation is stopped, unless the I/O table has been registered, or the I/O table has been registered and either the Forced Status Hold Bit or the I/O Status
Hold Bit has not been enabled in the PC Setup.
3-4-7 FAL (Failure Alarm) Area
A 2-digit BCD FAL code is output to bits 25300 to 25307 when the FAL or FALS instruction is executed. These codes are user defined for use in error diagnosis, although the PC also outputs FAL codes to these bits, such as one caused by battery voltage drop.
This area can be reset by executing the FAL instruction with an operand of 00 or by performing a Failure Read Operation from the Programming Console.
3-4-8 Low Battery Flag
SR bit 25308 turns ON if the voltage of the CPU’s backup battery drops. The
ALM/ERR indicator on the front of the CPU will also flash.
42
SR Area Section 3-4
This bit can be programmed to activate an external warning for a low battery voltage.
The operation of the battery alarm can be disabled in the PC Setup if desired.
Refer to 3-6-4 PC Setup for details.
3-4-9 Cycle Time Error Flag
SR bit 25309 turns ON if the cycle time exceeds 100 ms. The ALM/ERR indicator on the front of the CPU will also flash. Program execution will not stop, however, unless the maximum time limit set for the watchdog timer is exceeded. Timing may become inaccurate after the cycle time exceeds 100 ms.
3-4-10 I/O Verification Error Flag
SR bit 25310 turns ON when the Units mounted in the system disagree with the
I/O table registered in the CPU. The ALM/ERR indicator on the front of the CPU will also flash, but PC operation will continue.
To ensure proper operation, PC operation should be stopped, Units checked, and the I/O table corrected whenever this flag goes ON.
3-4-11 First Cycle Flag
SR bit 25315 turns ON when PC operation begins and then turns OFF after one cycle of the program. The First Cycle Flag is useful in initializing counter values and other operations. An example of this is provided in 5-14 Timer and Counter
Instructions.
3-4-12 Clock Pulse Bits
Five clock pulses are available to control program timing. Each clock pulse bit is
ON for the first half of the rated pulse time, then OFF for the second half. In other words, each clock pulse has a duty factor of 50%.
These clock pulse bits are often used with counter instructions to create timers.
Refer to 5-14 Timer and Counter Instructions for an example of this.
Pulse width
Bit
1 min
25400
0.02 s
25401
0.1 s
25500
0.2 s
25501
1.0 s
25502
Bit 25400
1-min clock pulse
Bit 25401
0.02-s clock pulse
30 s 30 s
1 min.
Bit 25500
0.1-s clock pulse
.01 s .01 s
.02 s
Bit 25501
0.2-s clock pulse
.05 s .05 s
0.1 s
Bit 25502
1.0-s clock pulse
0.5 s
1.0 s
0.5 s
0.1 s 0.1 s
0.2 s
Caution:
Because the 0.1-second and
0.02-second clock pulse bits have
ON times of 50 and 10 ms, respectively, the CPU may not be able to accurately read the pulses if program execution time is too long.
43
SR Area Section 3-4
3-4-13 Step Flag
SR bit 25407 turns ON for one cycle when step execution is started with the
STEP(08) instruction.
3-4-14 Group-2 Error Flag
SR bit 25414 turns ON for any of the following errors for Group-2 High-density
I/O Units and B7A Interface Units: the same I/O number set twice, the same words allocated to more than one Unit, refresh errors. If one of these errors occurs, the Unit will stop operation and the ALARM indicator will flash, but the overall PC will continue operation.
When the Group-2 Error Flag is ON, the number of the Unit with the error will be provided in AR 0205 to AR 0214. If the Unit cannot be started properly even though the I/O number is set correctly and the Unit is installed properly, a fuse may be blown or the Unit may contain a hardware failure. If this should occur, replace the Unit with a spare and try to start the system again.
There is also an error flag for High-density I/O Units and B7A Interface Units in the AR area, AR 0215.
3-4-15 Special Unit Error Flag
SR bit 25415 turns ON to indicate errors in the following Units: Special I/O, PC
Link, Host Link, and Remote I/O Master Units. SR bit 25415 will turn ON for any of the following errors.
•
When more than one Special I/O Unit is set to the same unit number.
• When an error occurs in refreshing data between a Special I/O Unit and the
PC’s CPU.
•
When an error occurs between a Host Link Unit and the PC’s CPU.
•
When an error occurs in a Remote I/O Master Unit.
Although the PC will continue operation if SR 25415 turns ON, the Units causing the error will stop operation and the ALM indicator will flash. Check the status of
AR 0000 to AR 0015 to obtain the unit numbers of the Units for which the error occurred and investigate the cause of the error.
Unit operation can be restarted by using the Restart Bits (AR 0100 to AR 0115,
SR 25207, and SR 25213), but will not be effective if the same unit number is set for more than one Special I/O Unit. Turn off the power supply, correct the unit number settings, and turn of the power supply again to restart.
SR 25415 will not turn OFF even if AR 0100 to AR 0115 (Restart Bits) are turned
ON. It can be turned OFF by reading errors from a Programming Device or by executing FAL(06) 00 from the ladder program.
3-4-16 Instruction Execution Error Flag, ER
SR bit 25503 turns ON if an attempt is made to execute an instruction with incorrect operand data. Common causes of an instruction error are non-BCD operand data when BCD data is required, or an indirectly addressed DM word that is non-existent. When the ER Flag is ON, the current instruction will not be executed.
3-4-17 Arithmetic Flags
The following flags are used in data shifting, arithmetic calculation, and comparison instructions. They are generally referred to only by their two-letter abbreviations.
!
Caution These flags are all reset when the END(01) instruction is executed, and therefore cannot be monitored from a programming device.
Refer to 5-15 Data Shifting, 5-17 Data Comparison, 5-19 BCD Calculations, and
5-20 Binary Calculations for details.
44
SR Area Section 3-4
Overflow Flag, OF
Underflow Flag, UF
Carry Flag, CY
Greater Than Flag, GR
Equal Flag, EQ
Less Than Flag, LE
SR bit 25404 turns ON when the result of a binary addition or subtraction exceeds 7FFF or 7FFFFFFF.
SR bit 25405 turns ON when the result of a signed binary addition or subtraction exceeds 8000 or 80000000.
SR bit 25504 turns ON when there is a carry in the result of an arithmetic operation or when a rotate or shift instruction moves a “1” into CY. The content of CY is also used in some arithmetic operations, e.g., it is added or subtracted along with other operands. This flag can be set and cleared from the program using the
Set Carry and Clear Carry instructions.
SR bit 25505 turns ON when the result of a comparison shows the first of two operands to be greater than the second.
SR bit 25506 turns ON when the result of a comparison shows two operands to be equal or when the result of an arithmetic operation is zero.
SR bit 25507 turns ON when the result of a comparison shows the first of two operands to be less than the second.
Note The four arithmetic flags are turned OFF when END(01) is executed.
3-4-18 Interrupt Subroutine Areas
The following areas are used in subroutine interrupt processing.
Interrupt Subroutine
Maximum Processing Time
Area
SR bits 26200 to 26215 are used to set the maximum processing time of the interrupt subroutine. Processing times are determined to within 0.1 ms increments.
Maximum Processing Time
Interrupt Subroutine
Number Area
SR bits 26300 to 26315 contain the maximum processing time interrupt subroutine number. Bit 15 will be ON if there is an interruption.
3-4-19 RS-232C Port Communications Areas
RS-232C Port Error Code SR bits 26400 to 26403 set when there is a RS-232C port error.
Setting Error type
0
1
2
3
No error
Parity error
Framing error
Overrun error
RS-232C Port
Communication Error Bit
RS-232C Port Send Ready
Flag
SR bit 26404 turns ON when there is a RS-232C port communication error.
SR bit 26405 turns ON when the C200HS is ready to transmit data.
RS-232C Port Reception
Completed Flag
RS-232C Port Reception
Overflow Flag
RS-232C Reception Counter
Host Link Level 0 Send
Ready Flag
SR bit 26406 turns ON when the C200HS has completed reading data from a
RS-232C device.
SR bit 26407 turns ON when data overflow occurs following the reception of data.
SR areas 26500 to 26515 contains the number of RS-232C port receptions in
General I/O Mode.
SR bit 26705 turns ON when the C200HS is ready to transmit to the Host Link
Unit.
Host Link Level 1 Send
Ready Flag
SR bit 26713 turns ON when the C200HS is ready to transmit to the Host Link.
45
SR Area Section 3-4
3-4-20 Peripheral Port Communications Areas
Peripheral Port Error Code SR bits 26408 to 26411 are set when there is a peripheral port error in the General I/O Mode.
Setting
2
3
0
1
F
Error type
No error
Parity error
Framing error
Overrun error
Connected in Peripheral Mode
Peripheral Port
Communication Error Bit
Peripheral Port Send Ready
Flag
Peripheral Port Reception
Completed Flag
Peripheral Port Reception
Overflow Flag
Peripheral Reception
Counter
Host Link Level 0 Send
Ready Flag
SR bit 26412 turns ON when there is a peripheral port communication error (effective in General I/O Mode).
SR bit 26413 turns ON when the C200HS is ready to transmit data in General I/O
Mode.
SR bit 26414 turns ON when the C200HS has completed reading data from a peripheral device. Effective in General I/O Mode.
SR bit 26415 turns ON when data overflow occurs following the reception of data. Effective in General I/O Mode.
SR areas 26600 to 26615 contains the number of peripheral port receptions in
General I/O Mode (BCD).
SR bit 26705 turns ON when the C200HS is ready to transmit to the Host Link
Unit.
Host Link Level 1 Receive
Ready Flag
SR bit 26713 turns ON when the C200HS is ready to receive data from the Host
Link.
3-4-21 Memory Cassette Areas
Memory Cassette Contents SR areas 26900 to 26907 indicate memory type contained on the Memory Cassette.
Memory Type Code
Nothing
UM
IOM
00
01
02
Memory Cassette Capacity SR areas 26908 to 26910 indicate memory capacity of the Memory Cassette.
Code Capacity
0 KW (no board mounted)
16 KW
0
3
EEPROM/EPROM Memory
Cassette Mounted Flag
Memory Cassette Flag
Save UM to Cassette Flag
Load UM from Cassette
Flag
SR bit 26914 turns ON when EEPROM Memory Cassette is protected or
EPROM Memory Cassette is mounted.
SR bit 26915 turns ON when a Memory Cassette is mounted.
SR bit 27000 turns ON when UM data is read to a Memory Cassette in Program
Mode. Bit will automatically turn OFF. An error will be produced if turned ON in any other mode.
SR bit 27001 turns ON when data is loaded into UM from a Memory Cassette in
Program Mode. Bit will automatically turn OFF. An error will be produced if turned ON in any other mode.
46
SR Area Section 3-4
Collation (Between DM and
Memory Cassette)
SR bit 27002 turns ON when data is verified between DM and a Memory Cassette. SR bit 27003 turns OFF when the contents of the verification coincide and turns ON when the contents of the verification do not coincide.
3-4-22 Data Transfer Error Bits
Data will not be transferred from UM to the Memory Cassette if an error occurs
(except for Board Checksum Error). Detailed information on checksum errors occurring in the Memory Cassette will not be output to SR 272 because the information is not needed. Repeat the transmission if SR 27015 is ON
Transfer Error Flag: Not
PROGRAM Mode
Transfer Error Flag: Read
Only
SR bit 27012 turns ON when the C200HS is not in Program Mode and data transfer is attempted.
SR bit 27013 turns ON when the C200HS is in Read-only Mode and data transfer is attempted.
Transfer Error Flag:
Insufficient Capacity or No
UM
SR bit 27014 turns ON when data transfer is attempted and available UM is insufficient.
Transfer Error Flag: Board
Checksum Error
SR bit 27015 turns ON when data transfer is attempted and a Board Checksum error occurs.
3-4-23 Ladder Diagram Memory Areas
Memory Cassette Ladder
Diagram Size Area
CPU Ladder Diagram Size and Type
SR areas 27100 to 27107 indicate the amount of ladder program stored in a
Memory Cassette.
Ladder-only File: 04: 4 KW; 08: 8 KW; 12: 12 KW; ... (64: 64 KW)
(Ladder File (Bit 07 will be ON): 84: 4 KW; 88: 8 KW; 92: 12 KW;
... (E4: 64 KW))
00: No ladder program or no file
Data updated at data transfer from CPU at startup. The file must begin in segment 0.
SR areas 27108 to 27115 indicate the CPU’s ladder program size and type.
Specifications are the same as for bits 00 to 07.
3-4-24 Memory Error Flags
Memory Error Flag: PC
Setup Error
Memory Error Flag: Ladder
Checksum Error
Memory Error Flag:
Instruction Change Error
SR bit 27211 turns ON when a PC Setup Checksum error occurs.
SR bit 27212 turns ON when a Ladder Checksum error occurs.
SR bit 27213 turns ON when an instruction change vector area error occurs.
Memory Error Flag: Memory
Cassette Disconnect Error
SR bit 27214 turns ON when a Memory Cassette is connected or disconnected during operations.
Memory Error Flag:
Autoboot Error
SR bit 27215 turns ON when an autoboot error occurs.
3-4-25 Data Save Flags
Data transferred to Memory Cassette when Bit is turned ON in PROGRAM mode. Bit will automatically turn OFF. An error will be produced if turned ON in any other mode.
47
AR Area Section 3-5
Save IOM to Cassette Bit SR bit 27300 turns ON when IOM is saved to a Memory Cassette.
Load IOM from Cassette Bit SR bit 27301 turns ON when loading to IOM from a Memory Cassette.
3-4-26 Transfer Error Flags
Data will not be transferred from IOM to the Memory Cassette if an error occurs
(except for Read Only Error).
Transfer Error Flag: Not
PROGRAM mode
Transfer Error Flag
Transfer Error Flag
SR bit 27312 turns ON when attempting to transfer data in other than Program
Mode.
SR bit 27313 turns ON when attempting to transfer data in Read-only Mode.
SR bit 27314 turns ON when attempting to transfer data and IOM capacity is insufficient.
3-4-27 PC Setup Error Flags
PC Setup Startup Error
PC Setup RUN Error
SR bit 27500 turns ON when a PC Setup Startup error occurs (DM6600 to
DM6614).
SR bit 27501 turns ON when a PC Setup Run error occurs (DM6615 to
DM6644).
SR bit 27501 turns ON when a PC Setup Communications, Error setting or Miscellaneous error occurs (DM6645 to DM6655).
PC Setup
Communications/Error
Setting/Misc. Error
Minutes (00 to 59)
Hours (00 to 23)
Keyboard Map
SR bits 27600 to 27607 set the PC Clock to minutes (00 to 59).
SR bits 27608 to 27615 set the PC Clock to hours (0 to 23).
Used for keyboard mapping.
3-5 AR (Auxiliary Relay) Area
AR word addresses extend from AR 00 to AR 27; AR bit addresses extend from
AR 0000 to AR 2715. Most AR area words and bits are dedicated to specific uses, such as transmission counters, flags, and control bits, and words AR 00 through AR 07 and AR 23 through AR 27 cannot be used for any other purpose.
Words and bits from AR 08 to AR 22 are available as work words and work bits if not used for the following assigned purposes.
Word
AR 0713 to AR 0715
AR 07 to 15
AR 16, AR 17
AR 18 to AR 21
AR 0708, AR 0709, and AR 22
Use
Error History Area
SYSMAC LINK Units
SYSMAC LINK and SYSMAC NET Link Units
Calendar/clock Area
TERMINAL Mode Key Bits
The AR area retains status during power interruptions, when switching from
MONITOR or RUN mode to PROGRAM mode, or when PC operation is stopped. Bit allocations are shown in the following table and described in the following pages in order of bit number.
AR Area Flags and Control Bits
00
Word(s) Bit(s)
00 to 09
10
Function
Error Flags for Special I/O Units 0 to 9 (also function as Error Flags for PC Link Units)
Error Flag for operating level 1 of SYSMAC LINK or SYSMAC NET Link System
11
12
13
14
15
Error Flag for operating level 0 of SYSMAC LINK or SYSMAC NET Link System
Host Computer to Rack-mounting Host Link Unit Level 1 Error Flag
Host Computer to Rack-mounting Host Link Unit Level 0 Error Flag
Remote I/O Master Unit 1 Error Flag
Remote I/O Master Unit 0 Error Flag
48
AR Area Section 3-5
03
04
05
06
07
08 to 11
12 to 15
16
17
18
Writeable
19
Writeable
20
Writeable
21
01
Word(s)
02
22
23
Bit(s)
00 to 09
10
11
12, 13
14
15
00 to 04
05 to 14
15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 03
Function
Restart Bits for Special I/O Units 0 to 9 (also function as Restart Bits for PC Link Units)
Restart Bit for operating level 1 of SYSMAC LINK or SYSMAC NET Link System
Restart Bit for operating level 0 of SYSMAC LINK or SYSMAC NET Link System
Not used.
Remote I/O Master Unit 1 Restart Flag.
Remote I/O Master Unit 0 Restart Flag.
Slave Rack Error Flags (#0 to #4)
Group-2 Error Flags
Group-2 Error Flag
Error Flags for Optical I/O Units and I/O Terminals 0 to 7
Error Flags for Optical I/O Units and I/O Terminals 8 to 15
Error Flags for Optical I/O Units and I/O Terminals 16 to 23
Error Flags for Optical I/O Units and I/O Terminals 24 to 31
Data Link setting for operating level 0 of SYSMAC LINK System
04 to 07
08
Data Link setting for operating level 1 of SYSMAC LINK System
Normal TERMINAL Mode/Expansion TERMINAL Mode Input Cancel Bit
09 Expansion TERMINAL Mode Changeover Flag
10 and 11 Reserved by system.
12 Terminal Mode Flag
ON: Expansion; OFF: Normal (Same as status of pin 6 on CPU’s DIP switch)
13
14
15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 07
Error History Overwrite Bit
Error History Reset Bit
Error History Enable Bit
Active Node Flags for SYSMAC LINK System nodes of operating level 0
Active Node Flags for SYSMAC LINK System nodes of operating level 1
SYSMAC LINK/SYSMAC NET Link System operating level 0 service time per cycle
SYSMAC LINK/SYSMAC NET Link System operating level 1 service time per cycle
Seconds: 00 to 99
08 to 15
00 to 07
08 to 15
Minutes: 00 to 59
Hours: 00 to 23 (24-hour system)
Day of Month: 01 to 31 (adjusted by month and for leap year)
00 to 07
08 to 15
00 to 07
08 to 12
13
14
15
00 to 15
00 to 15
Month: 1 to 12
Year: 00 to 99 (Rightmost two digits of year)
Day of Week: 00 to 06 (00: Sunday; 01: Monday; 02: Tuesday; 03: Wednesday; 04:
Thursday; 05: Friday; 06: Saturday)
Not used.
30-second Compensation Bit
Clock Stop Bit
Clock Set Bit
Keyboard Mapping
Power Off Counter (BCD)
49
AR Area
24
Word(s)
25
26
27
14
15
00 to 11
12
13
14
15
00 to 15
00 to 15
06
07
08
Bit(s)
00 to 04
05
Reserved by system.
Cycle Time Flag
Function
SYSMAC LINK System Network Parameter Flag for operating level 1
SYSMAC LINK System Network Parameter Flag for operating level 0
SYSMAC/SYSMAC NET Link Unit Level 1 Mounted Flag
09
10
SYSMAC/SYSMAC NET Link Unit Level 0 Mounted Flag
Reserved by system.
11 and 12 PC Link Level
13 Rack-mounting Host Link Unit Level 1 Mounted Flag
Rack-mounting Host Link Unit Level 0 Mounted Flag
CPU-mounting Device Mounted Flag
Reserved by system.
Trace End Flag
Tracing Flag
Trace Trigger Bit (writeable)
Trace Start Bit (writeable)
Maximum Cycle Time (0.1 ms)
Present Cycle Time (0.1 ms)
Section 3-5
3-5-1 Restarting Special I/O Units
To restart Special I/O Units (including PC Link Units) turn the corresponding bit
ON and OFF (or turn power ON and OFF). Do not access data refreshed for Special I/O Units during restart processing (see SR 27400 to SR 27409 on page 37).
3-5-2 Slave Rack Error Flags
AR bits 0200 to AR 0204 correspond to the unit numbers of Remote I/O Slave
Units #0 to #4 and AR bits 0710 to AR 0712 correspond to the unit numbers of
Remote I/O Slave Units #5 to #7. These flags will turn ON if the same number is allocated to more then one Slave or if a transmission error occurs when starting the System. Refer to SR 251 for errors that occur after the System has started normally.
3-5-3 Group-2 Error Flags
AR bits 0205 to AR 0215 correspond to Group-2 High-density I/O Units and B7A
Interface Units 0 to 9 (I/O numbers) and will turn ON when the same number is set for more than one Unit, when the same word is allocated to more than one
Unit, when I/O number 9 is set for a 64-point Unit, or when the fuse burns out in a
Transistor High-density I/O Unit. AR bit 0215 will turn ON when a Unit is not recognized as a Group-2 High-density I/O Unit.
3-5-4 Optical I/O Unit and I/O Terminal Error Flags
AR 03 through AR 06 contain the Error Flags for Optical I/O Units and I/O Terminals. An error indicates a duplication of a unit number. Up to 64 Optical I/O Units and I/O Terminals can be connected to the PC. Units are distinguished by unit
50
AR Area
Optical I/O Unit and I/O
Terminal Error Flags
Section 3-5
13
14
15
08
09
10
11
12
04
05
06
07
00
01
02
03 number, 0 through 31, and a letter, L or H. Bits are allocated as shown in the following table.
Bits AR03 allocation
4 L
4 H
5 L
5 H
6 L
6 H
7 L
7 H
2 L
2 H
3 L
3 H
0 L
0 H
1 L
1 H
AR04 allocation
12 L
12 H
13 L
13 H
14 L
14 H
15 L
15 H
8 L
8 H
9 L
9 H
10 L
10 H
11 L
11 H
AR05 allocation
20 L
20 H
21 L
21 H
22 L
22 H
23 L
23 H
16 L
16 H
17 L
17 H
18 L
18 H
19 L
19 H
AR06 allocation
28 L
28 H
29 L
29 H
30 L
30 H
31 L
31 H
24 L
24 H
25 L
25 H
26 L
26 H
27 L
27 H
3-5-5 SYSMAC LINK System Data Link Settings
AR 0700 to AR 0703 and AR 0704 to AR 0707 are used to designate word allocations for operating levels 0 and 1 of the SYSMAC LINK System. Allocation can be set to occur either according to settings from an FIT or automatically in the LR and/or DM areas. If automatic allocation is designated, the number of words to be allocated to each node is also designated. These settings are shown below.
External/Automatic
Allocation
Operating level 0 Operating level 1 Setting
AR 0700 AR 0701 AR 0704 AR 0705
0
1
0
1
1
1
0
0
0
1
0
1
1
1
0
0
Words set externally (FIT)
Automatic LR area only allocation DM area only
LR and DM areas
Words per Node The following setting is necessary if automatic allocation is designated above.
0
1
0
1
Operating level 0 Operating level 1 Words per node Max. no.
AR 0702 AR 0703 AR 0706 AR 0707 LR area DM area of nodes
0
0
1
1
0
1
0
1
0
0
1
1
4
8
16
32
8
16
32
64
16
8
4
2
The above settings are read every cycle while the SYSMAC LINK System is in operation.
3-5-6 Error History Bits
AR 0713 (Error History Overwrite Bit) is turned ON or OFF by the user to control overwriting of records in the Error History Area in the DM area. Turn AR 0713 ON to overwrite the oldest error record each time an error occurs after 10 have been recorded. Turn OFF AR 0713 to store only the first 10 records that occur each time after the history area is cleared.
51
AR Area Section 3-5
AR 0714 (Error History Reset Bit) is turned ON and then OFF by the user to reset the Error Record Pointer (DM 0969) and thus restart recording error records at the beginning of the history area.
AR 0715 (Error History Enable Bit) is turned ON by the user to enable error history storage and turned OFF to disable error history storage.
Refer to 3-6 DM Area for details on the Error History Area.
Error history bits are refreshed each cycle.
3-5-7 Active Node Flags
AR 08 through AR 11 and AR 12 through AR 15 provide flags that indicate which nodes are active in the SYSMAC LINK System at the current time. These flags are refreshed every cycle while the SYSMAC LINK System is operating.
The body of the following table show the node number assigned to each bit. If the bit is ON, the node is currently active.
Level 0
AR 08
AR 09
AR 10
AR 11
Level 1
AR 12
AR 13
AR 14
AR 15
1
Bit (body of table shows node numbers)
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
17
33
49
2
18
34
50
*Communication Controller Error Flag
**EEPROM Error Flag
3
19
35
51
4
20
36
52
5
21
37
53
6
22
38
54
7
23
39
55
8
24
40
56
9
25
41
57
10 11 12 13 14 15 16
26
42
58
27
43
59
28
44
60
29
45
61
30
46
62
31
47
*
32
48
**
3-5-8 SYSMAC LINK/SYSMAC NET Link System Service Time
AR 16 provides the time allocated to servicing operating level 0 of the SYSMAC
LINK System and/or SYSMAC NET Link System during each cycle when a SYS-
MAC LINK Unit and/or SYSMAC NET Link Unit is mounted to a Rack.
AR 17 provides the time allocated to servicing operating level 1 of the SYSMAC
LINK System and/or SYSMAC NET Link System during each cycle when a SYS-
MAC LINK Unit and/or SYSMAC NET Link Unit is mounted to a Rack.
These times are recorded in 4-digit BCD to tenths of a millisecond (000.0 ms to
999.9 ms) and are refreshed every cycle.
Bits
15 to 12 11 to 08 07 to 04 03 to 00
10 2 10 1 10 0 10 –1
3-5-9 Calendar/Clock Area and Bits
Calendar/Clock Area
Calendar/Clock Bits
Bits Contents
AR 1800 to AR 1807 Seconds
AR 1808 to AR 1815 Minutes
AR 1900 to AR 1907 Hours
AR 1908 to AR 1915 Day of month
AR 2000 to AR 2007 Month
AR 2008 to AR 2015 Year
AR 2100 to AR 2107 Day of week
A clock is built into the C200HS CPUs. If AR 2114 (Clock Stop Bit) is OFF, then the date, day, and time will be available in BCD in AR 18 to AR 20 and AR 2100 to
AR 2108 as shown below. This area can also be controlled with AR 2113 (30-second Compensation Bit) and AR 2115 (Clock Set Bit).
Possible values
00 to 59
00 to 59
00 to 23 (24-hour system)
01 to 31 (adjusted by month and for leap year)
1 to 12
00 to 99 (Rightmost two digits of year)
00 to 06 (00: Sunday; 01: Monday; 02: Tuesday; 03: Wednesday; 04:
Thursday; 05: Friday; 06: Saturday)
52
AR Area Section 3-5
30-second Compensation Bit AR 2113 is turned ON to round the seconds of the Calendar/clock Area to zero, i.e., if the seconds is 29 or less, it is merely set to 00; if the seconds is 30 or greater, the minutes is incremented by 1 and the seconds is set to 00.
Clock Stop Bit AR 2114 is turned OFF to enable the operation of the Calendar/clock Area and
ON to stop the operation.
Clock Set Bit AR 2115 is used to set the Calendar/clock Area as described below. This data must be in BCD and must be set within the limits for the Calendar/clock Area given above.
1, 2, 3...
1. Turn ON AR 2114 (Stop Bit).
2. Set the desired date, day, and time, being careful not to turn OFF AR 2114
(Clock Stop Bit) when setting the day of the week (they’re in the same word).
(On the Programming Console, the Bit/Digit Monitor and Force Set/Reset
Operations are the easiest ways to set this data.)
3. Turn ON AR 2115 (Clock Set Bit). The Calendar/clock will automatically start operating with the designated settings and AR 2114 and AR 2115 will both be turned OFF.
The Calendar/clock Area and Bits are refreshed each cycle while operational.
Clock Accuracy Clock accuracy is affected by the ambient temperature as shown in the following table.
Ambient temperature
55 ° C
25 ° C
0 ° C
Accuracy (loss or gain per month)
–3 to 0 minutes
± 1 minute
–2 to 0 minutes
3-5-10 TERMINAL Mode Key Bits
If the Programming Console is mounted to the PC and is in TERMINAL mode, any inputs on keys 0 through 9 (including characters A through F, i.e, keys 0 through 5 with SHIFT) will turn on a corresponding bit in AR 22. TERMINAL mode is entered by a Programming Console operation.
The bits in AR 22 correspond to Programming Console inputs as follows:
Bit
AR 2200
AR 2201
AR 2202
AR 2203
AR 2204
AR 2205
AR 2206
AR 2207
AR 2208
AR 2209
AR 2210
AR 2211
AR 2212
AR 2213
AR 2214
AR 2215
8
9
6
7
A
B
E
F
C
D
0
3
4
1
2
5
Programming Console input
Refer to Section 7 Program Monitoring and Execution for details on the TERMI-
NAL mode.
53
AR Area Section 3-5
3-5-11 Power OFF Counter
AR 23 provides in 4-digit BCD the number of times that the PC power has been turned off. This counter can be reset as necessary using the PV Change 1 operation from the Programming Console. (Refer to 7-1-4 Hexadecimal/BCD Data
Modification for details.) The Power OFF Counter is refreshed every time power is turned on.
3-5-12 Cycle Time Flag
AR 2405 turns ON when the cycle time set with SCAN(18) is shorter than the actual cycle time.
AR 2405 is refreshed every cycle while the PC is in RUN or MONITOR mode.
3-5-13 Link Unit Mounted Flags
The following flags indicate when the specified Link Units are mounted to the
Racks. (Refer to 3-5-14 CPU-mounting Device Mounted Flag for CPU-mounting
Host Link Units.) These flags are refreshed every cycle.
Name
PC Link Unit Level 1
PC Link Unit Level 0
Rack-mounting Host Link Unit Level 1
Rack-mounting Host Link Unit Level 0
Bit
AR 2411
AR 2412
AR 2413
AR 2414
Link Unit
PC Link Unit in operating level 1
PC Link Unit in operating level 0
Rack-mounting Host Link Unit in operating level 1
Rack-mounting Host Link Unit in operating level 0
3-5-14 CPU-mounting Device Mounted Flag
AR 2415 turns ON when any device is mounted directly to the CPU. This includes CPU-mounting Host Link Units, Programming Consoles, and Interface
Units. This flag is refreshed every cycle.
3-5-15 FPD Trigger Bit
AR 2508 is used to adjust the monitoring time of FPD(––) automatically. Refer to
5-25-12 FAILURE POINT DETECT – FPD(––) for details.
3-5-16 Data Tracing Flags and Control Bits
The following control bits and flags are used during data tracing with TRSM(45).
The Tracing Flag will be ON during tracing operations. The Trace Completed
Flag will turn ON when enough data has been traced to fill Trace Memory.
Bit
AR 2512
AR 2513
AR 2514
AR 2515
Trace Completed Flag
Tracing Flag
Trace Trigger Bit (writeable)
Sampling Start Bit (writeable)
Name
Note Refer to 5-25-3 TRACE MEMORY SAMPLING – TRSM(45) for details.
3-5-17 Cycle Time Indicators
AR 26 contains the maximum cycle time that has occurred since program execution was begun. AR 27 contains the present cycle time.
Both times are to tenths of a millisecond in 4-digit BCD (000.0 ms to 999.9 ms), and are refreshed every cycle.
54
DM Area Section 3-6
3-6 DM (Data Memory) Area
The DM area is divided into various parts as described in the following table. A portion of UM (up to 3,000 words in 1,000-word increments) can be allocated as
Expansion DM.
Addresses User read/write
Usage
DM 0000 to DM 0999 Read/Write Normal DM.
DM 1000 to DM 1999 Special I/O Unit Area
1
DM 2000 to DM 5999
DM 6000 to DM 6030
Normal DM.
History Log
DM 6100 to DM 6143
DM 6144 to DM 6599 Read only
DM 6600 to DM 6655
DM 7000 to DM 9999
Link test area (reserved)
System Settings
PC Setup
Expansion DM
2
Indirect Addressing
Note 1. The PC Setup can be set to use DM 7000 through DM 7999 as the Special
I/O Area instead of DM 1000 to DM 1999. Refer to 3-6-4 PC Setup for details.
2. The UM ALLOCATION Programming Console operation can be used to allocate up to 3000 words of UM as Expansion DM.
Although composed of 16-bit words like any other data area, data in the DM area cannot be specified by bit for use in instructions with bit operands. DM 0000 to
DM 6143 can be written to by the program, but DM 6144 to DM 6655 can be overwritten only from a Peripheral Device, such as a Programming Console or host computer with LSS.
The DM area retains status during power interruptions.
Normally, when the content of a data area word is specified for an instruction, the instruction is performed directly on the content of that word. For example, suppose MOV(21) is performed with DM 0100 as the first operand and LR 20 as the second operand. When this instruction is executed, the content of DM 0100 is moved to LR 20.
Note Expansion DM cannot be used for indirect addressing.
It is possible, however, to use indirect DM addresses as the operands for many instructions. To indicate an indirect DM address, : DM is input with the address of the operand. With an indirect address, with content of this operand does not contain the actual data to be used. Instead, it’s contents is assumed to hold the address of another DM word, the content of which will actually be used in the instruction. If
:
DM 0100 was used in our example above and the content of DM
0100 is 0324, then
:
DM 0100 actually means that the content of DM 0324 is to be used as the operand in the instruction, and the content of DM 0324 will be moved to LR 20.
MOV(21)
: DM 0100
LR 00
Indirect address
Word
DM 0099
DM 0100
DM 0101
Content
4C59
0324
F35A
Indicates
DM 0324
DM 0324
DM 0325
DM 0326
5555
2506
D541
5555 moved to LR 00.
55
DM Area Section 3-6
3-6-1 Expansion DM Area
The expansion DM area is designed to provide memory space for storing operating parameters and other operating data for Link Units and Special I/O Units.
Up to 3,000 words of UM can be allocated as Expansion DM (in 1K-word increments) using the UM ALLOCATION operation in the Programming Console or
LSS. Expansion DM area addresses run from DM 7000 to DM 9999.
The data in the expansion DM area can be transferred to the Special I/O Unit
Default Area (DM 1000 to DM 1999) when starting the PC or via programming instruction to easily change operating parameters, enabling rapid switching between control processes. The expansion DM area can also be used to store parameters for other devices connected in the PC system, e.g., Programmable
Terminal character string or numeral tables.
The expansion DM area is used to store operating parameters and cannot be used in programming like the normal DM area. Expansion DM can only be overwritten from a Peripheral Device, retains status during power interruptions, and cannot be used for indirect addressing.
The UM area can be allocated as expansion DM area in increments of 1K words.
Once expansion DM area has been created, it is saved and transferred as part of the program, i.e., no special procedures are required when saving or transferring the program.
UM ALLOCATION Operation The procedure for the Programming Console’s UM ALLOCATION operation is shown below. Refer to 1-8-10 New Programming Console Operations for details on the DATA CLEAR and UM ALLOCATION instructions.
1, 2, 3...
1. Clear memory.
CLR SET NOT RESET EXT MONTR
Note UM allocation is not possible unless memory is cleared first.
2. The expansion DM area can be set to 0, 1, 2, or 3 K words. The following key sequence creates a 2-KW expansion DM area (DM 7000 to DM 8999).
CLR FUN VER CHG 2 SET 9 7 1 3 WRITE
Press the 0 Key to eliminate the expansion DM area (0 KW).
or Press the 1 Key to allocate DM 7000 to DM 7999 (1 KW).
or Press the 2 Key to allocate DM 7000 to DM 8999 (2 KW).
or Press the 3 Key to allocate DM 7000 to DM 9999 (3 KW).
3-6-2 Special I/O Unit Data
Special I/O Units are allocated 1000 words in the DM Area as shown in the following table. The value set in the PC Setup (DM 6602 bits 08 to 15) determines
56
DM Area Section 3-6 whether DM 1000 to DM 1999 or DM 7000 to 7999 will be used. Refer to 3-6-4
PC Setup for details.
5
6
3
4
7
8
1
2
0
Unit
9
Addresses
DM 1000 to DM 1099 or DM 7000 to DM 7099
DM 1100 to DM 1199 or DM 7100 to DM 7199
DM 1200 to DM 1299 or DM 7200 to DM 7299
DM 1300 to DM 1399 or DM 7300 to DM 7399
DM 1400 to DM 1499 or DM 7400 to DM 7499
DM 1500 to DM 1599 or DM 7500 to DM 7599
DM 1600 to DM 1699 or DM 7600 to DM 7699
DM 1700 to DM 1799 or DM 7700 to DM 7799
DM 1800 to DM 1899 or DM 7800 to DM 7899
DM 1900 to DM 1999 or DM 7900 to DM 7999
Note These DM words can be used for other purposes when not allocated to Special
I/O Units.
3-6-3 Error History Area
DM 6000 to DM 6030 are used to store up to 10 records that show the nature, time, and date of errors that have occurred in the PC.
The Error History Area will store system-generated or FAL(06)/FALS(07)-generated error codes whenever AR 0715 (Error History Enable Bit) is ON. Refer to
Section 10 Troubleshooting for details on error codes.
Area Structure Error records occupy three words each stored between DM 6001 and DM 6030.
The last record that was stored can be obtained via the content of DM 6000 (Error Record Pointer). The record number, DM words, and pointer value for each of the ten records are as follows:
8
9
6
7
10
3
4
1
2
5
Record
None
Addresses
N.A.
DM 6001 to DM 6003
DM 6004 to DM 6006
DM 6007 to DM 6009
DM 6010 to DM 6012
DM 6013 to DM 6015
DM 6016 to DM 6018
DM 6019 to DM 6021
DM 6022 to DM 6024
DM 6025 to DM 6027
DM 6028 to DM 6030
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
000A
Pointer value
Although each of them contains a different record, the structure of each record is the same: the first word contains the error code; the second and third words, the day and time. The error code will be either one generated by the system or by
FAL(06)/FALS(07); the time and date will be the date and time from AR 18 and
AR 19 (Calender/date Area). Also recorded with the error code is an indication of whether the error is fatal (08) or non-fatal (00). This structure is shown below.
First
Second
Third
Word
00 to 07
08 to 15
00 to 07
08 to 15
00 to 07
08 to 15
Bit Content
Error code
00 (non-fatal) or 80 (fatal)
Seconds
Minutes
Hours
Day of month
57
DM Area
Operation
3-6-4 PC Setup
Section 3-6
The following table lists the possible error codes and corresponding errors.
Error severity
Fatal errors
Non-fatal errors
00
Error code
01 to 99
9F
C0 to C2
E0
8A
8B
9A
9B
E1
F0
F1
01 to 99
9D
B0 to B1
D0
E7
F7
F8
Error
Power Interruption
System error (FALS)
Cycle time error
I/O bus error
Input-output I/O table error
Too many Units
No END(01) instruction
Memory error
System error (FAL)
Interrupt Input error
Interrupt program error
Group 2 High-density I/O error
PC Setup error
UM Memory Cassette transfer error
Remote I/O error
Special I/O error
I/O table verification error
Battery error
Cycle time overrun
When the first error code is generated with AR 0715 (Error History Enable Bit) turned ON, the relevant data will be placed in the error record after the one indicated by the History Record Pointer (initially this will be record 1) and the Pointer will be incremented. Any other error codes generated thereafter will be placed in consecutive records until the last one is used. Processing of further error records is based on the status of AR 0713 (Error History Overwrite Bit).
If AR 0713 is ON and the Pointer contains 000A, the next error will be written into record 10, the contents of record 10 will be moved to record 9, and so on until the contents of record 1 is moved off the end and lost, i.e., the area functions like a shift register. The Record Pointer will remain set to 000A.
If AR 0713 is OFF and the Pointer reaches 000A, the contents of the Error History Error will remain as it is and any error codes generate thereafter will not be recorded until AR 0713 is turned OFF or until the Error History Area is reset.
The Error History Area can be reset by turning ON and then OFF
AR 0714 (Error History Reset Bit). When this is done, the Record Pointer will be reset to 0000, the Error History Area will be reset (i.e., cleared), and any further error codes will be recorded from the beginning of the Error History Area.
AR 0715 (Error History Enable Bit) must be ON to reset the Error History Area.
The PC Setup contains settings that determine C200HS operation. Data in the
PC Setup can be changed with a Programming Console or LSS if UM is not write-protected by pin 1 of the CPU’s DIP switch. Refer to page 23 for details on changing DIP switch pin settings.
The PC can be operated with the default PC Setup, which requires changing only when customizing the PC’s operating environment to application needs.
The PC Setup parameters are described in the following table. Refer to Appen-
dix E PC Setup for more details on these parameters.
58
DM Area Section 3-6
The PC Setup is allocated to DM 6600 through DM 6655.
Parameter
STARTUP MODE
STARTUP
MODE
FORCED
STATUS
IOM HOLD BIT
STATUS
CYCLE TIME
Default
Don’t hold
Variable
Settings
Programming
Console mode selector
Don’t hold
Programming Console mode selector, previous mode (i.e., the mode in use last time power was interrupted), PROGRAM,
MONITOR, or RUN
Hold or don’t hold
Hold or don’t hold
Variable or minimum
Minimum setting: 1 to
9,999 ms
Remarks
Determines the operating mode the PC will start in when power is turned ON.
This setting is required for restart continuation.
Setting is effective from next time power is turned on to the PC.
Determines whether or not the status of the Forced
Status Hold Bit is maintained after power interruptions.
If the status of the Forced Status Hold Bit is not set to be held, it will be turned OFF the next time the PC is started and forced status will be cleared.
Setting is effective from next time power is turned on to the PC.
Determines whether or not the status of the IOM Hold
Bit is maintained after power interruptions. If the status of the IOM Hold Bit is not set to be held, it will be turned OFF the next time the PC is started and I/O status will be cleared.
This setting is required for restart continuation.
Setting is effective from next time power is turned on to the PC.
Determines whether or not a minimum cycle time is to be used for user program execution. If a minimum time is set, the PC will wait until the minimum time has expired before starting program execution again. The entire program will be executed even if the minimum time is exceeded.
This setting can be used to reduce variations in I/O response times.
An error of approximately 3 to 4 ms, plus the execution time required for any interrupt programs, can occur.
Setting is effective immediately.
Detect Long
Cycles
120 ms 0 to 99,000 ms If the set time is exceeded, the Cycle Time Exceeded
Flag will turn ON and a fatal error will occur.
An error of approximately 3 to 4 ms can occur.
Setting is effective immediately.
RS-232C SETUP
METHOD Host link
NODE NO
DELAY
0
0
START CODE None
END CODE None
DATA LINK
AREAS
BAUD RATE
PC SETUP, HEX
INPUT
None
9,600 bps
STOP BITS
PARITY
2 bits
Even parity
DATA LENGTH 7 bits
Host Link, RS-232C with no protocol, 1:1 link master, or 1:1 link slave
00 to 31
0 to 9,999 ms
00 to FF
00 to FF or CR, LF
LR 00 to LR 63, LR 00 to
LR 31, or LR 00 to LR 15
1200, 2400, 4800, 9600, or 19200
1 or 2 bits
Even, odd, or none
7 or 8 bits
Determines the settings used when a device, such as a Programmable Terminal or bar code reader is
Do not set the node number to a number already used communicated with.
Used to set the above parameters on a binary display.
ff ti i di t l
59
TC Area Section 3-8
3-7 HR (Holding Relay) Area
The HR area is used to store/manipulate various kinds of data and can be accessed either by word or by bit. Word addresses range from HR 00 through HR
99; bit addresses, from HR 0000 through HR 9915. HR bits can be used in any order required and can be programmed as often as required.
The HR area retains status when the system operating mode is changed, when power is interrupted, or when PC operation is stopped.
HR area bits and words can be used to preserve data whenever PC operation is stopped. HR bits also have various special applications, such as creating latching relays with the Keep instruction and forming self-holding outputs. These are discussed in Section 4 Writing and Inputting the Program and Section 5 Instruc-
tion Set.
Note The required number of words is allocated between HR 00 and HR 42 for routing tables and to monitor timers when using SYSMAC NET Systems.
3-8 TC (Timer/Counter) Area
The TC area is used to create and program timers and counters and holds the
Completion flags, set values (SV), and present values (PV) for all timers and counters. All of these are accessed through TC numbers ranging from TC 000 through TC 511. Each TC number is defined as either a timer or counter using one of the following instructions: TIM, TIMH, CNT, CNTR(12), and TTIM(87). No prefix is required when using a TC number in a timer or counter instruction.
Once a TC number has been defined using one of these instructions, it cannot be redefined elsewhere in the program either using the same or a different instruction. If the same TC number is defined in more than one of these instructions or in the same instruction twice, an error will be generated during the program check. There are no restrictions on the order in which TC numbers can be used.
Once defined, a TC number can be designated as an operand in one or more of certain set of instructions other than those listed above. When defined as a timer, a TC number designated as an operand takes a TIM prefix. The TIM prefix is used regardless of the timer instruction that was used to define the timer. Once defined as a counter, the TC number designated as an operand takes a CNT prefix. The CNT is also used regardless of the counter instruction that was used to define the counter.
TC numbers can be designated for operands that require bit data or for operands that require word data. When designated as an operand that requires bit data, the TC number accesses the completion flag of the timer or counter. When designated as an operand that requires word data, the TC number accesses a memory location that holds the PV of the timer or counter.
TC numbers are also used to access the SV of timers and counters from a Programming Device. The procedures for doing so using the Programming Console are provided in 7-1 Monitoring Operation and Modifying Data.
The TC area retains the SVs of both timers and counters during power interruptions. The PVs of timers are reset when PC operation is begun and when reset in interlocked program sections. Refer to 5-10 INTERLOCK and INTERLOCK
CLEAR – IL(02) and ILC(03) for details on timer and counter operation in interlocked program sections. The PVs of counters are not reset at these times.
Note that in programming “TIM 000” is used to designate three things: the Timer instruction defined with TC number 000, the completion flag for this timer, and the PV of this timer. The meaning in context should be clear, i.e., the first is always an instruction, the second is always a bit, and the third is always a word.
The same is true of all other TC numbers prefixed with TIM or CNT.
60
TR Area Section 3-11
3-9 LR (Link Relay) Area
The LR area is used as a common data area to transfer information between
PCs. This data transfer is achieved through a PC Link System.
Certain words will be allocated as the write words of each PC. These words are written by the PC and automatically transferred to the same LR words in the other PCs in the System. The write words of the other PCs are transferred in as read words so that each PC can access the data written by the other PCs in the
PC Link System. Only the write words allocated to the particular PC will be available for writing; all other words may be read only. Refer to the PC Link System
Manual for details.
The LR area is accessible either by bit or by word. LR area word addresses range from LR 00 to LR 63; LR area bit addresses, from LR 0000 to LR 6315. Any part of the LR area that is not used by the PC Link System can be used as work words or work bits.
LR area data is not retained when the power is interrupted, when the PC is changed to PROGRAM mode, or when it is reset in an interlocked program section. Refer to 5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03) for details on interlocks.
3-10 UM Area
With the C200HS, the UM area is defined as the part of memory that can be converted and transferred to ROM. The UM area is 16 KW of RAM which is backed up by the CPU’s battery. Some of the UM area is reserved to system use, so
15,488 words can be used by the operator. The structure of the C200HS DM and
UM areas is shown in the following illustration.
DM 0000
Special I/O Unit Default Area
DM 1000 to DM 1999
Normal DM Area
DM 6144 DM 6600 DM 6655 DM 7000
PC Setup Reserved Expansion
DM Area
DM 9999
I/O Comment
Area
Ladder program
Fixed DM Area
Variable size
Ladder Program Area (15.1 KW)
UM Area (16.0 KW)
Note Allocating UM area for an expansion DM and/or I/O Comment Area will reduce program capacity. Check program capacity requirements before allocating the
UM area.
3-11 TR (Temporary Relay) Area
The TR area provides eight bits that are used only with the LD and OUT instructions to enable certain types of branching ladder diagram programming. The use of TR bits is described in Section 4 Writing and Inputting the Program.
TR addresses range from TR 0 though TR 7. Each of these bits can be used as many times as required and in any order required as long as the same LR bit is not used twice in the same instruction block.
61
SECTION 4
Writing and Inputting the Program
This section explains the basic steps and concepts involved in writing a basic ladder diagram program, inputting the program into memory, and executing it. It introduces the instructions that are used to build the basic structure of the ladder diagram and control its execution. The entire set of instructions used in programming is described in Section 5 Instruction Set.
4-1 Basic Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Instruction Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Program Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Basic Ladder Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-1 Basic Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-2 Mnemonic Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-3 Ladder Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-4 OUTPUT and OUTPUT NOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-5 The END Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-6 Logic Block Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-7 Coding Multiple Right-hand Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 The Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-1 The Keyboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-2 PC Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-3 The Display Message Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Preparation for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-1 Entering the Password
4-6-2 Buzzer
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-3 Clearing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-4 Registering the I/O Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-5 Clearing Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-6 Verifying the I/O Table
4-6-7 Reading the I/O Table
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-8 Clearing the I/O Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-9 SYSMAC NET Link Table Transfer (CPU31/33-E Only) . . . . . . . . . . . . . . . . . .
4-7 Inputting, Modifying, and Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-1 Setting and Reading from Program Memory Address . . . . . . . . . . . . . . . . . . . . .
4-7-2 Entering and Editing Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-3 Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-4 Displaying the Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-5 Program Searches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-6 Inserting and Deleting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-7 Branching Instruction Lines
4-7-8 Jumps
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8 Controlling Bit Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8-1 DIFFERENTIATE UP and DIFFERENTIATE DOWN . . . . . . . . . . . . . . . . . . . .
4-8-2 KEEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8-3 Self-maintaining Bits (Seal)
4-9 Work Bits (Internal Relays)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10 Programming Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11 Program Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
96
98
99
100
92
92
93
86
87
89
90
81
81
82
84
85
103
107
108
109
109
109
110
112
114
78
80
80
80
71
78
78
66
67
70
70
64
64
65
65
66
63
Instruction Terminology Section 4-2
4-1 Basic Procedure
There are several basic steps involved in writing a program. Sheets that can be copied to aid in programming are provided in Appendix F Word Assignment Re-
cording Sheets and Appendix G Program Coding Sheet.
1, 2, 3...
1. Obtain a list of all I/O devices and the I/O points that have been assigned to them and prepare a table that shows the I/O bit allocated to each I/O device.
2. If the PC has any Units that are allocated words in data areas other than the
IR area or are allocated IR words in which the function of each bit is specified by the Unit, prepare similar tables to show what words are used for which
Units and what function is served by each bit within the words. These Units include Special I/O Units and Link Units.
3. Determine what words are available for work bits and prepare a table in which you can allocate these as you use them.
4. Also prepare tables of TC numbers and jump numbers so that you can allocate these as you use them. Remember, the function of a TC number can be defined only once within the program; jump numbers 01 through 99 can be used only once each. (TC number are described in 5-14 Timer and Counter
Instructions; jump numbers are described later in this section.)
5. Draw the ladder diagram.
6. Input the program into the CPU. When using the Programming Console, this will involve converting the program to mnemonic form.
7. Check the program for syntax errors and correct these.
8. Execute the program to check for execution errors and correct these.
9. After the entire Control System has been installed and is ready for use, execute the program and fine tune it if required.
10. Make a backup copy of the program.
The basics of ladder-diagram programming and conversion to mnemonic code are described in 4-4 Basic Ladder Diagrams. Preparing for and inputting the program via the Programming Console are described in 4-5 The Programming
Console through 4-7 Inputting, Modifying, and Checking the Program. The rest of Section 4 covers more advanced programming, programming precautions, and program execution. All special application instructions are covered in Sec-
tion 5 Instruction Set. Debugging is described in Section 7 Program Monitoring
and Execution. Section 10 Troubleshooting also provides information required for debugging.
4-2 Instruction Terminology
There are basically two types of instructions used in ladder-diagram programming: instructions that correspond to the conditions on the ladder diagram and are used in instruction form only when converting a program to mnemonic code and instructions that are used on the right side of the ladder diagram and are executed according to the conditions on the instruction lines leading to them.
Most instructions have at least one or more operands associated with them. Operands indicate or provide the data on which an instruction is to be performed.
These are sometimes input as the actual numeric values, but are usually the addresses of data area words or bits that contain the data to be used. For instance, a MOVE instruction that has IR 000 designated as the source operand will move the contents of IR 000 to some other location. The other location is also designated as an operand. A bit whose address is designated as an operand is called an operand bit; a word whose address is designated as an operand is called an operand word. If the actual value is entered as a constant, it is preceded by # to indicate that it is not an address.
Other terms used in describing instructions are introduced in Section 5 Instruc-
tion Set.
64
Basic Ladder Diagrams Section 4-4
4-3 Program Capacity
The maximum user program size varies with the amount of UM allocated to expansion DM and the I/O Comment Area. Approximately 10.1 KW are available for the ladder program when 3 KW are allocated to expansion DM and 2 KW are allocated to I/O comments as shown below. Refer to the 3-10 UM Area for further information on UM allocation.
DM
6144
DM
6600
DM
6655
DM
7000
DM
9999
PC
Setup
Reserved Expansion
DM Area
I/O Comment
Area
Ladder program
Fixed DM Area
Variable size
Ladder Program Area (15.1 KW)
4-4 Basic Ladder Diagrams
A ladder diagram consists of one line running down the left side with lines branching off to the right. The line on the left is called the bus bar; the branching lines, instruction lines or rungs. Along the instruction lines are placed conditions that lead to other instructions on the right side. The logical combinations of these conditions determine when and how the instructions at the right are executed. A ladder diagram is shown below.
00000 06315 25208 24401 HR 0109 LR 2503 24400
Instruction
00001 00501 00502 00503 00504
00100 00002
00010
00011
00003 HR 0050 00007 TIM 001 LR 0515
21001
21005
21002
21007
00403 00405
Instruction
As shown in the diagram above, instruction lines can branch apart and they can join back together. The vertical pairs of lines are called conditions. Conditions without diagonal lines through them are called normally open conditions and correspond to a LOAD, AND, or OR instruction. The conditions with diagonal lines through them are called normally closed conditions and correspond to a
LOAD NOT, AND NOT, or OR NOT instruction. The number above each condition indicates the operand bit for the instruction. It is the status of the bit associated with each condition that determines the execution condition for following instructions. The way the operation of each of the instructions corresponds to a condition is described below. Before we consider these, however, there are some basic terms that must be explained.
Note When displaying ladder diagrams with LSS, a second bus bar will be shown on the right side of the ladder diagram and will be connected to all instructions on the right side. This does not change the ladder-diagram program in any functional sense. No conditions can be placed between the instructions on the right side and the right bus bar, i.e., all instructions on the right must be connected directly to the right bus bar. Refer to the LSS Operation Manual for details.
65
Basic Ladder Diagrams Section 4-4
4-4-1 Basic Terms
Normally Open and
Normally Closed
Conditions
Each condition in a ladder diagram is either ON or OFF depending on the status of the operand bit that has been assigned to it. A normally open condition is ON if the operand bit is ON; OFF if the operand bit is OFF. A normally closed condition is ON if the operand bit is OFF; OFF if the operand bit is ON. Generally speaking, you use a normally open condition when you want something to happen when a bit is ON, and a normally closed condition when you want something to happen when a bit is OFF.
00000
Instruction
Instruction is executed when IR bit 00000 is ON.
Normally open condition
00000
Instruction
Instruction is executed when IR bit 00000 is OFF.
Normally closed condition
Execution Conditions
Operand Bits
Logic Blocks
In ladder diagram programming, the logical combination of ON and OFF conditions before an instruction determines the compound condition under which the instruction is executed. This condition, which is either ON or OFF, is called the execution condition for the instruction. All instructions other than LOAD instructions have execution conditions.
The operands designated for any of the ladder instructions can be any bit in the
IR, SR, HR, AR, LR, or TC areas. This means that the conditions in a ladder diagram can be determined by I/O bits, flags, work bits, timers/counters, etc. LOAD and OUTPUT instructions can also use TR area bits, but they do so only in special applications. Refer to 4-7-7 Branching Instruction Lines for details.
The way that conditions correspond to what instructions is determined by the relationship between the conditions within the instruction lines that connect them. Any group of conditions that go together to create a logic result is called a logic block. Although ladder diagrams can be written without actually analyzing individual logic blocks, understanding logic blocks is necessary for efficient programming and is essential when programs are to be input in mnemonic code.
4-4-2 Mnemonic Code
The ladder diagram cannot be directly input into the PC via a Programming Console; LSS is required. To input from a Programming Console, it is necessary to convert the ladder diagram to mnemonic code. The mnemonic code provides exactly the same information as the ladder diagram, but in a form that can be typed directly into the PC. Actually you can program directly in mnemonic code, although it in not recommended for beginners or for complex programs. Also, regardless of the Programming Device used, the program is stored in memory in mnemonic form, making it important to understand mnemonic code.
Because of the importance of the Programming Console as a peripheral device and because of the importance of mnemonic code in complete understanding of a program, we will introduce and describe the mnemonic code along with the ladder diagram. Remember, you will not need to use the mnemonic code if you are inputting via LSS (although you can use it with LSS too, if you prefer).
Program Memory Structure The program is input into addresses in Program Memory. Addresses in Program
Memory are slightly different to those in other memory areas because each address does not necessarily hold the same amount of data. Rather, each address holds one instruction and all of the definers and operands (described in more detail later) required for that instruction. Because some instructions require no operands, while others require up to three operands, Program Memory addresses can be from one to four words long.
66
Basic Ladder Diagrams Section 4-4
Program Memory addresses start at 00000 and run until the capacity of Program
Memory has been exhausted. The first word at each address defines the instruction. Any definers used by the instruction are also contained in the first word.
Also, if an instruction requires only a single bit operand (with no definer), the bit operand is also programmed on the same line as the instruction. The rest of the words required by an instruction contain the operands that specify what data is to be used. When converting to mnemonic code, all but ladder diagram instructions are written in the same form, one word to a line, just as they appear in the ladder diagram symbols. An example of mnemonic code is shown below. The instructions used in it are described later in the manual.
Address Instruction
00000
00001
00002
00003
00004
00005
00006
LD
AND
OR
LD NOT
AND
AND LD
MOV(21)
00007
00008
00009
00010
00011
00012
00013
CMP(20)
LD
OUT
MOV(21)
DIFU(13)
AND
OUT
Operands
HR 0001
00001
00002
00100
00101
00102
DM
DM
HR
DM
DM
000
0000
0000
00
25505
00501
0000
0500
00502
00005
00503
The address and instruction columns of the mnemonic code table are filled in for the instruction word only. For all other lines, the left two columns are left blank. If the instruction requires no definer or bit operand, the operand column is left blank for first line. It is a good idea to cross through any blank data column spaces (for all instruction words that do not require data) so that the data column can be quickly scanned to see if any addresses have been left out.
When programming, addresses are automatically displayed and do not have to be input unless for some reason a different location is desired for the instruction.
When converting to mnemonic code, it is best to start at Program Memory address 00000 unless there is a specific reason for starting elsewhere.
4-4-3 Ladder Instructions
The ladder instructions are those instructions that correspond to the conditions on the ladder diagram. Ladder instructions, either independently or in combination with the logic block instructions described next, form the execution conditions upon which the execution of all other instructions are based.
67
Basic Ladder Diagrams
LOAD and LOAD NOT
Section 4-4
The first condition that starts any logic block within a ladder diagram corresponds to a LOAD or LOAD NOT instruction. Each of these instruction requires one line of mnemonic code. “Instruction” is used as a dummy instruction in the following examples and could be any of the right-hand instructions described later in this manual.
00000
A LOAD instruction.
00000
A LOAD NOT instruction.
Address Instruction
00000
00001
00002
00003
LD
Instruction
LD NOT
Instruction
Operands
00000
00000
AND and AND NOT
When this is the only condition on the instruction line, the execution condition for the instruction at the right is ON when the condition is ON. For the LOAD instruction (i.e., a normally open condition), the execution condition will be ON when IR
00000 is ON; for the LOAD NOT instruction (i.e., a normally closed condition), it will be ON when 00000 is OFF.
When two or more conditions lie in series on the same instruction line, the first one corresponds to a LOAD or LOAD NOT instruction; and the rest of the conditions correspond to AND or AND NOT instructions. The following example shows three conditions which correspond in order from the left to a LOAD, an
AND NOT, and an AND instruction. Again, each of these instructions requires one line of mnemonic code.
00000 00100 LR 0000
Instruction
Address Instruction
00000
00001
00002
00003
LD
AND NOT
AND
Instruction
LR
Operands
00000
00100
0000
The instruction will have an ON execution condition only when all three conditions are ON, i.e., when IR 00000 is ON, IR 00100 is OFF, and LR 0000 is ON.
AND instructions in series can be considered individually, with each taking the logical AND of the execution condition (i.e., the total of all conditions up to that point) and the status of the AND instruction’s operand bit. If both of these are ON, an ON execution condition will be produced for the next instruction. If either is
OFF, the result will also be OFF. The execution condition for the first AND instruction in a series is the first condition on the instruction line.
Each AND NOT instruction in series takes the logical AND of its execution condition and the inverse of its operand bit.
68
Basic Ladder Diagrams
OR and OR NOT
Section 4-4
When two or more conditions lie on separate instruction lines which run in parallel and then join together, the first condition corresponds to a LOAD or LOAD
NOT instruction; the other conditions correspond to OR or OR NOT instructions.
The following example shows three conditions which correspond (in order from the top) to a LOAD NOT, an OR NOT, and an OR instruction. Again, each of these instructions requires one line of mnemonic code.
00000
Instruction
00100
LR 0000
Combining AND and OR
Instructions
Address Instruction
00000
00001
00002
00003
LD
OR NOT
OR
Instruction
LR
Operands
00000
00100
0000
The instruction will have an ON execution condition when any one of the three conditions is ON, i.e., when IR 00000 is OFF, when IR 00100 is OFF, or when LR
0000 is ON.
OR and OR NOT instructions can be considered individually, each taking the logical OR between its execution condition and the status of the OR instruction’s operand bit. If either one of these were ON, an ON execution condition will be produced for the next instruction.
When AND and OR instructions are combined in more complicated diagrams, they can sometimes be considered individually, with each instruction performing a logic operation on the execution condition and the status of the operand bit.
The following is one example. Study this example until you are convinced that the mnemonic code follows the same logic flow as the ladder diagram.
00000 00001 00002 00003
Instruction
00200
Address Instruction
00000
00001
00002
00003
00004
00005
LD
AND
OR
AND
AND NOT
Instruction
Operands
00000
00001
00200
00002
00003
Here, an AND is taken between the status of IR 00000 and that of IR 00001 to determine the execution condition for an OR with the status of IR 00200. The result of this operation determines the execution condition for an AND with the status of IR 00002, which in turn determines the execution condition for an AND with the inverse (i.e., and AND NOT) of the status of IR 00003.
In more complicated diagrams, however, it is necessary to consider logic blocks before an execution condition can be determined for the final instruction, and that’s where AND LOAD and OR LOAD instructions are used. Before we consider more complicated diagrams, however, we’ll look at the instructions required to complete a simple “input-output” program.
69
Basic Ladder Diagrams Section 4-4
4-4-4 OUTPUT and OUTPUT NOT
The simplest way to output the results of combining execution conditions is to output it directly with the OUTPUT and OUTPUT NOT. These instructions are used to control the status of the designated operand bit according to the execution condition. With the OUTPUT instruction, the operand bit will be turned ON as long as the execution condition is ON and will be turned OFF as long as the execution condition is OFF. With the OUTPUT NOT instruction, the operand bit will be turned ON as long as the execution condition is OFF and turned OFF as long as the execution condition is ON. These appear as shown below. In mnemonic code, each of these instructions requires one line.
00000
00001
00200
00201
Address Instruction
00000
00001
LD
OUT
Address Instruction
00000
00001
LD
OUT NOT
Operands
00000
00200
Operands
00001
00201
In the above examples, IR 00200 will be ON as long as IR 00000 is ON and IR
00201 will be OFF as long as IR 00001 is ON. Here, IR 00000 and IR 00001 will be input bits and IR 00200 and IR 00201 output bits assigned to the Units controlled by the PC, i.e., the signals coming in through the input points assigned IR
00000 and IR 00001 are controlling the output points assigned IR 00200 and IR
00201, respectively.
The length of time that a bit is ON or OFF can be controlled by combining the
OUTPUT or OUTPUT NOT instruction with TIMER instructions. Refer to Examples under 5-14-1 TIMER – TIM for details.
4-4-5 The END Instruction
The last instruction required to complete a simple program is the END instruction. When the CPU cycles the program, it executes all instruction up to the first
END instruction before returning to the beginning of the program and beginning execution again. Although an END instruction can be placed at any point in a program, which is sometimes done when debugging, no instructions past the first END instruction will be executed until it is removed. The number following the END instruction in the mnemonic code is its function code, which is used when inputted most instruction into the PC. These are described later. The END instruction requires no operands and no conditions can be placed on the same instruction line with it.
00000 00001
Instruction
END(01)
Program execution ends here.
Address Instruction
00000
00001
00002
00003
LD
AND NOT
Instruction
END(01)
Operands
00000
00001
---
If there is no END instruction anywhere in the program, the program will not be executed at all.
70
Basic Ladder Diagrams Section 4-4
Now you have all of the instructions required to write simple input-output programs. Before we finish with ladder diagram basic and go onto inputting the program into the PC, let’s look at logic block instruction (AND LOAD and OR LOAD), which are sometimes necessary even with simple diagrams.
4-4-6 Logic Block Instructions
Logic block instructions do not correspond to specific conditions on the ladder diagram; rather, they describe relationships between logic blocks. The AND
LOAD instruction logically ANDs the execution conditions produced by two logic blocks. The OR LOAD instruction logically ORs the execution conditions produced by two logic blocks.
AND LOAD Although simple in appearance, the diagram below requires an AND LOAD instruction.
00000
00001
00002
00003
Address Instruction
00000
00001
00002
00003
00004
LD
OR
LD
OR NOT
AND LD
Operands
00000
00001
00002
00003
---
Instruction
The two logic blocks are indicated by dotted lines. Studying this example shows that an ON execution condition will be produced when: either of the conditions in the left logic block is ON (i.e., when either IR 00000 or IR 00001 is ON), and when either of the conditions in the right logic block is ON (i.e., when either IR
00002 is ON or IR 00003 is OFF).
The above ladder diagram cannot, however, be converted to mnemonic code using AND and OR instructions alone. If an AND between IR 00002 and the results of an OR between IR 00000 and IR 00001 is attempted, the OR NOT between IR 00002 and IR 00003 is lost and the OR NOT ends up being an OR NOT between just IR 00003 and the result of an AND between IR 00002 and the first
OR. What we need is a way to do the OR (NOT)’s independently and then combine the results.
To do this, we can use the LOAD or LOAD NOT instruction in the middle of an instruction line. When LOAD or LOAD NOT is executed in this way, the current execution condition is saved in a special buffer and the logic process is restarted. To combine the results of the current execution condition with that of a previous “unused” execution condition, an AND LOAD or an OR LOAD instruction is used. Here “LOAD” refers to loading the last unused execution condition.
An unused execution condition is produced by using the LOAD or LOAD NOT instruction for any but the first condition on an instruction line.
71
Basic Ladder Diagrams
OR LOAD
Section 4-4
Analyzing the above ladder diagram in terms of mnemonic instructions, the condition for IR 00000 is a LOAD instruction and the condition below it is an OR instruction between the status of IR 00000 and that of IR 00001. The condition at
IR 00002 is another LOAD instruction and the condition below is an OR NOT instruction, i.e., an OR between the status of IR 00002 and the inverse of the status of IR 00003. To arrive at the execution condition for the instruction at the right, the logical AND of the execution conditions resulting from these two blocks will have to be taken. AND LOAD does this. The mnemonic code for the ladder diagram is shown below. The AND LOAD instruction requires no operands of its own, because it operates on previously determined execution conditions. Here too, dashes are used to indicate that no operands needs designated or input.
The following diagram requires an OR LOAD instruction between the top logic block and the bottom logic block. An ON execution condition will be produced for the instruction at the right either when IR 00000 is ON and IR 00001 is OFF, or when IR 00002 and IR 00003 are both ON. The operation of the OR LOAD instruction and its mnemonic code is exactly the same as that for an AND LOAD instruction, except that the current execution condition is ORed with the last unused execution condition.
00000
00002
00001
00003
Address Instruction
00000
00001
00002
00003
00004
LD
AND NOT
LD
AND
OR LD
Operands
00000
00001
00002
00003
---
Instruction
Naturally, some diagrams will require both AND LOAD and OR LOAD instructions.
Logic Block Instructions in
Series
To code diagrams with logic block instructions in series, the diagram must be divided into logic blocks. Each block is coded using a LOAD instruction to code the first condition, and then AND LOAD or OR LOAD is used to logically combine the blocks. With both AND LOAD and OR LOAD there are two ways to achieve this. One is to code the logic block instruction after the first two blocks and then after each additional block. The other is to code all of the blocks to be combined, starting each block with LOAD or LOAD NOT, and then to code the logic block instructions which combine them. In this case, the instructions for the last pair of blocks should be combined first, and then each preceding block should be combined, working progressively back to the first block. Although either of these methods will produce exactly the same result, the second method, that of coding all logic block instructions together, can be used only if eight or fewer blocks are being combined, i.e., if seven or fewer logic block instructions are required.
72
Basic Ladder Diagrams Section 4-4
00000
00001
The following diagram requires AND LOAD to be converted to mnemonic code because three pairs of parallel conditions lie in series. The two options for coding the programs are also shown.
00002 00004
00500
00003 00005
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
OR NOT
LD NOT
OR
AND LD
LD
OR
AND LD
OUT
Operands
00000
00001
00002
00003
—
00004
00005
—
00500
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
OR NOT
LD NOT
OR
LD
OR
AND LD
AND LD
OUT
Operands
00000
00001
00002
00003
00004
00005
—
—
00500
Again, with the method on the right, a maximum of eight blocks can be combined. There is no limit to the number of blocks that can be combined with the first method.
The following diagram requires OR LOAD instructions to be converted to mnemonic code because three pairs of series conditions lie in parallel to each other.
00000 00001
00501
00002 00003
00040 00005
The first of each pair of conditions is converted to LOAD with the assigned bit operand and then ANDed with the other condition. The first two blocks can be coded first, followed by OR LOAD, the last block, and another OR LOAD; or the three blocks can be coded first followed by two OR LOADs. The mnemonic codes for both methods are shown below.
Combining AND LOAD and
OR LOAD
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
AND NOT
LD NOT
AND NOT
OR LD
LD
AND
OR LD
OUT
Operands
00000
00001
00002
00003
—
00004
00005
—
00501
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
AND NOT
LD NOT
AND NOT
LD
AND
OR LD
OR LD
OUT
Operands
00000
00001
00002
00003
00004
00005
—
—
00501
Again, with the method on the right, a maximum of eight blocks can be combined. There is no limit to the number of blocks that can be combined with the first method.
Both of the coding methods described above can also be used when using AND
LOAD and OR LOAD, as long as the number of blocks being combined does not exceed eight.
73
Basic Ladder Diagrams Section 4-4
The following diagram contains only two logic blocks as shown. It is not necessary to further separate block b components, because it can be coded directly using only AND and OR.
00000 00001 00002 00003
00501
00201
Block a
00004
Block b
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
LD
AND NOT
LD
AND
OR
OR
AND LD
OUT
Operands
00000
00001
00002
00003
00201
00004
—
00501
Although the following diagram is similar to the one above, block b in the diagram below cannot be coded without separating it into two blocks combined with OR
LOAD. In this example, the three blocks have been coded first and then OR
LOAD has been used to combine the last two blocks, followed by AND LOAD to combine the execution condition produced by the OR LOAD with the execution condition of block a.
When coding the logic block instructions together at the end of the logic blocks they are combining, they must, as shown below, be coded in reverse order, i.e., the logic block instruction for the last two blocks is coded first, followed by the one to combine the execution condition resulting from the first logic block instruction and the execution condition of the logic block third from the end, and on back to the first logic block that is being combined.
00000 00001
Block a
Block b1
00002 00003
00004 00202
Block b2
Block b
Complicated Diagrams
00502
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD NOT
AND
LD
AND NOT
LD NOT
AND
OR LD
AND LD
OUT
Operands
00000
00001
00002
00003
00004
00202
—
—
00502
When determining what logic block instructions will be required to code a diagram, it is sometimes necessary to break the diagram into large blocks and then continue breaking the large blocks down until logic blocks that can be coded without logic block instructions have been formed. These blocks are then coded, combining the small blocks first, and then combining the larger blocks. Either
AND LOAD or OR LOAD is used to combine the blocks, i.e., AND LOAD or OR
LOAD always combines the last two execution conditions that existed, regardless of whether the execution conditions resulted from a single condition, from logic blocks, or from previous logic block instructions.
74
Basic Ladder Diagrams
Block a1
00000 00001
00002 00003
Block a2
Block a
Block b1
00004 00005
00006 00007
Block b2
Block b
Section 4-4
When working with complicated diagrams, blocks will ultimately be coded starting at the top left and moving down before moving across. This will generally mean that, when there might be a choice, OR LOAD will be coded before AND
LOAD.
The following diagram must be broken down into two blocks and each of these then broken into two blocks before it can be coded. As shown below, blocks a and b require an AND LOAD. Before AND LOAD can be used, however, OR
LOAD must be used to combine the top and bottom blocks on both sides, i.e., to combine a1 and a2; b1 and b2.
00503
Blocks a1 and a2
Blocks b1 and b2
Blocks a and b
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
LD
AND NOT
LD NOT
AND
OR LD
LD
AND
LD
AND
OR LD
AND LD
OUT
Operands
00000
00001
00002
00003
—
00004
00005
00006
00007
—
—
00503
The following type of diagram can be coded easily if each block is coded in order: first top to bottom and then left to right. In the following diagram, blocks a and b would be combined using AND LOAD as shown above, and then block c would be coded and a second AND LOAD would be used to combined it with the execution condition from the first AND LOAD. Then block d would be coded, a third AND
LOAD would be used to combine the execution condition from block d with the execution condition from the second AND LOAD, and so on through to block n.
00500
Block a
Block b
Block c
Block n
75
Basic Ladder Diagrams
00000
00004
00006
00001
00002 00003
00005
00007
Section 4-4
The following diagram requires an OR LOAD followed by an AND LOAD to code the top of the three blocks, and then two more OR LOADs to complete the mnemonic code.
LR 0000
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
LD
LD
LD
AND NOT
OR LD
AND LD
LD NOT
AND
OR LD
LD NOT
AND
OR LD
OUT LR
Operands
00000
00001
00002
00003
––
––
00004
00005
––
00006
00007
––
0000
00002 00003
00001
00004
00006
00000
Block a
00000
00005
00007
00001 00002
Block b
00003
Block c
00004
Although the program will execute as written, this diagram could be drawn as shown below to eliminate the need for the first OR LOAD and the AND LOAD, simplifying the program and saving memory space.
LR 0000
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
LD
AND NOT
OR
AND
LD NOT
AND
OR LD
LD NOT
AND
OR LD
OUT LR
Operands
00002
00003
00001
00000
00004
00005
––
00006
00007
––
0000
The following diagram requires five blocks, which here are coded in order before using OR LOAD and AND LOAD to combine them starting from the last two blocks and working backward. The OR LOAD at program address 00008 combines blocks blocks d and e, the following AND LOAD combines the resulting execution condition with that of block c, etc.
Block d
00005
00006 00007
Block e
LR 0000
Blocks d and e
Block c with result of above
Block b with result of above
Block a with result of above
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
LD
LD
AND
LD
AND
LD
LD
AND
OR LD
AND LD
OR LD
AND LD
OUT LR
Operands
00000
00001
00002
00003
00004
00005
00006
00007
––
––
––
––
0000
76
Basic Ladder Diagrams Section 4-4
Again, this diagram can be redrawn as follows to simplify program structure and coding and to save memory space.
00006 00007
00005
00001
Block a
00000 00001
LD
AND
00000
00001
00003 00004
00002
OR LD
00500
OR 00500
00002 00003
AND 00002
AND NOT 00003
00000
The next and final example may at first appear very complicated but can be coded using only two logic block instructions. The diagram appears as follows:
00000 00001
Block a
00002 00003
01000 01001
00500
Block b
00004 00005
00006
Block c
00500
The first logic block instruction is used to combine the execution conditions resulting from blocks a and b, and the second one is to combine the execution condition of block c with the execution condition resulting from the normally closed condition assigned IR 00003. The rest of the diagram can be coded with OR,
AND, and AND NOT instructions. The logical flow for this and the resulting code are shown below.
Block b
01000 01001
LD
AND
01000
01001
LR 0000
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
LD
AND
OR
AND
AND
LD
AND
OR LD
AND
OUT LR
Operands
00006
00007
00005
00003
00004
00001
00002
––
00000
0000
AND LD
Block c
00004 00005
LD
AND
00006
00004
00005
LD 00006
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
LD
AND
LD
AND
OR LD
OR
AND
AND NOT
LD
AND
OR
AND LD
OUT
Operands
00000
00001
01000
01001
––
00500
00002
00003
00004
00005
00006
––
00500
00500
77
The Programming Console Section 4-5
4-4-7 Coding Multiple Right-hand Instructions
If there is more than one right-hand instruction executed with the same execution condition, they are coded consecutively following the last condition on the instruction line. In the following example, the last instruction line contains one more condition that corresponds to an AND with IR 00004.
00000 00003
00001
00002
HR 0000
00004
HR
0001
00500
00506
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
OR
OR
OR
AND
OUT
OUT
AND
OUT
Operands
HR
HR
00000
00001
00002
0000
00003
0001
00500
00004
00506
4-5 The Programming Console
This and the next section describe the Programming Console and the operations necessary to prepare for program input. 4-7 Inputting, Modifying, and
Checking the Program describes actual procedures for inputting the program into memory.
Although the Programming Console can be used to write ladder programs, it is primarily used to support LSS operations and is very useful for on-site editing and maintenance. The main Programming Console functions are listed below.
1, 2, 3...
1. Displaying operating messages and the results of diagnostic checks.
2. Writing and reading ladder programs, inserting and deleting instructions, searching for data or instructions, and monitoring I/O bit status.
3. Monitoring I/O status, force-setting/resetting bits.
4. The Programming Console can be connected to or disconnected from the
PC with the power on.
5. The Programming Console can be used with C-series PCs.
6. Supports TERMINAL mode, which allows the display of a 32-character message, as well as operation of the keyboard mapping function. Refer to
5-25-6 TERMINAL MODE – TERM(––) for details.
Note The Programming Console does not support all of the LSS operations, only those required for on-site editing and maintenance.
4-5-1 The Keyboard
White: Numeric Keys
Red: CLR Key
Yellow: Operation Keys
The keyboard of the Programming Console is functionally divided by key color into the following four areas:
The ten white keys are used to input numeric program data such as program addresses, data area addresses, and operand values. The numeric keys are also used in combination with the function key (FUN) to enter instructions with function codes.
The CLR key clears the display and cancels current Programming Console operations. It is also used when you key in the password at the beginning of programming operations. Any Programming Console operation can be cancelled by pressing the CLR key, although the CLR key may have to be pressed two or three times to cancel the operation and clear the display.
The yellow keys are used for writing and correcting programs. Detailed explanations of their functions are given later in this section.
78
The Programming Console
Gray: Instruction and Data
Area Keys
Section 4-5
Except for the SHIFT key on the upper right, the gray keys are used to input instructions and designate data area prefixes when inputting or changing a program. The SHIFT key is similar to the shift key of a typewriter, and is used to alter the function of the next key pressed. (It is not necessary to hold the SHIFT key down; just press it once and then press the key to be used with it.)
The gray keys other than the SHIFT key have either the mnemonic name of the instruction or the abbreviation of the data area written on them. The functions of these keys are described below.
Pressed before the function code when inputting an instruction via its function code.
Pressed to enter SFT (the Shift Register instruction).
Input either after a function code to designate the differentiated form of an instruction or after a ladder instruction to designate an inverse condition.
Pressed to enter AND (the AND instruction) or used with NOT to enter AND NOT.
Pressed to enter OR (the OR instruction) or used with NOT to enter OR NOT.
Pressed to enter CNT (the Counter instruction) or to designate a TC number that has already been defined as a counter.
Pressed to enter LD (the Load instruction) or used with NOT to enter LD NOT. Also pressed to indicate an input bit.
Pressed to enter OUT (the Output instruction) or used with
NOT to enter OUT NOT. Also pressed to indicate an output bit.
Pressed to enter TIM (the Timer instruction) or to designate a
TC number that has already been defined as a timer.
Pressed before designating an address in the TR area.
Pressed before designating an address in the LR area.
Pressed before designating an address in the HR area.
Pressed before designating an address in the AR area.
Pressed before designating an address in the DM area.
Pressed before designating an indirect DM address.
Pressed before designating a word address.
Pressed before designating an operand as a constant.
Pressed before designating a bit address.
Pressed before function codes for block programming instructions, i.e., those placed between pointed parentheses <>.
79
Preparation for Operation Section 4-6
4-5-2 PC Modes
The Programming Console is equipped with a switch to control the PC mode. To select one of the three operating modes—RUN, MONITOR, or PROGRAM— use the mode switch. The mode that you select will determine PC operation as well as the procedures that are possible from the Programming Console.
RUN mode is the mode used for normal program execution. When the switch is set to RUN and the START input on the CPU Power Supply Unit is ON, the CPU will begin executing the program according to the program written in its Program
Memory. Although monitoring PC operation from the Programming Console is possible in RUN mode, no data in any of the memory areas can be input or changed.
MONITOR mode allows you to visually monitor in-progress program execution while controlling I/O status, changing PV (present values) or SV (set values), etc. In MONITOR mode, I/O processing is handled in the same way as in RUN mode. MONITOR mode is generally used for trial system operation and final program adjustments.
In PROGRAM mode, the PC does not execute the program. PROGRAM mode is for creating and changing programs, clearing memory areas, and registering and changing the I/O table. A special Debug operation is also available within
PROGRAM mode that enables checking a program for correct execution before trial operation of the system.
!
DANGER Do not leave the Programming Console connected to the PC by an extension cable when in
RUN mode. Noise picked up by the extension cable can enter the PC, affecting the program and thus the controlled system.
4-5-3 The Display Message Switch
Pin 3 of the CPU’s DIP switch determines whether Japanese or English language messages will be displayed on the Programming Console. It is factory set to ON, which causes English language messages to be displayed.
4-6 Preparation for Operation
This section describes the procedures required to begin Programming Console operation. These include password entry, clearing memory, error message clearing, and I/O table operations. I/O table operations are also necessary at other times, e.g., when changes are to be made in Units used in the PC configuration.
!
DANGER Always confirm that the Programming Console is in PROGRAM mode when turning on the
PC with a Programming Console connected unless another mode is desired for a specific purpose. If the Programming Console is in RUN mode when PC power is turned on, any program in Program Memory will be executed, possibly causing a PC-controlled system to begin operation.
The following sequence of operations must be performed before beginning initial program input.
1, 2, 3...
1. Insert the mode key into the Programming Console.
2. Set the mode switch to PROGRAM mode. (The mode key cannot be removed while set to PROGRAM mode.)
3. Turn on PC power.
Note When I/O Units are installed, turn on those Units also. The Programming Console will not operate if these Units are not turned on.
80
Preparation for Operation Section 4-6
4. Confirm that the CPU’s POWER LED is lit and the following display appears on the Programming Console screen. (If the ALM/ERR LED is lit or flashing or an error message is displayed, clear the error that has occurred.)
<PROGRAM>
PASSWORD!
5. Enter the password. See 4-6-1 Entering the Password for details.
6. Clear memory. Skip this step if the program does not need to be cleared.
See 4-6-3 Clearing Memory for details.
4-6-1 Entering the Password
To gain access to the PC’s programming functions, you must first enter the password. The password prevents unauthorized access to the program.
The PC prompts you for a password when PC power is turned on or, if PC power is already on, after the Programming Console has been connected to the PC. To gain access to the system when the “Password!” message appears, press CLR and then MONTR. Then press CLR to clear the display.
If the Programming Console is connected to the PC when PC power is already on, the first display below will indicate the mode the PC was in before the Programming Console was connected. Ensure that the PC is in PROGRAM mode
before you enter the password. When the password is entered, the PC will shift to the mode set on the mode switch, causing PC operation to begin if the mode is set to RUN or MONITOR. The mode can be changed to RUN or MONI-
TOR with the mode switch after entering the password.
<PROGRAM>
PASSWORD!
<PROGRAM> BZ
Indicates the mode set by the mode selector switch.
4-6-2 Buzzer
Immediately after the password is input or anytime immediately after the mode has been changed, SHIFT and then the 1 key can be pressed to turn on and off the buzzer that sounds when Programming Console keys are pressed. If BZ is displayed in the upper right corner, the buzzer is operative. If BZ is not displayed, the buzzer is not operative.
This buzzer also will also sound whenever an error occurs during PC operation.
Buzzer operation for errors is not affected by the above setting.
81
Preparation for Operation Section 4-6
4-6-3 Clearing Memory
Using the Memory Clear operation it is possible to clear all or part of the UM area
(RAM or EEPROM), and the IR, HR, AR, DM and TC areas. Unless otherwise specified, the clear operation will clear all of the above memory areas. The UM area will not be cleared if the write-protect switch (pin 1 of the CPU’s DIP switch) is set to ON.
Before beginning to programming for the first time or when installing a new program, all areas should normally be cleared. Before clearing memory, check to see if a program is already loaded that you need. If you need the program, clear only the memory areas that you do not need, and be sure to check the existing program with the program check key sequence before using it. The check sequence is provided later in this section. Further debugging methods are provided in Section 7 Program Monitoring and Execution. To clear all memory areas press CLR until all zeros are displayed, and then input the keystrokes given in the top line of the following key sequence. The branch lines shown in the sequence are used only when performing a partial memory clear, which is described below.
Memory can be cleared in PROGRAM mode only. The following table shows which memory areas will be cleared for the 3 memory clearing operations (all clear, partial clear, memory clear).
Memory Area
I/O words
Work words
HR, AR, TC, DM, fixed DM
Expansion DM
I/O comments
Ladder program
UM Allocation information
All clear
Cleared
Cleared
Cleared
Cleared
Cleared
Cleared
Cleared
Partial clear
Cleared
---
Cleared
---
---
Cleared
---
Memory clear
Cleared
Cleared
Cleared
Cleared
---
Cleared
---
All Clear
Note 1. The error history area (DM 6000 to DM 6030) will not be cleared when the
DM area is cleared.
2. When the PC Setup area (DM 6600 to DM 6655 in fixed DM) is cleared, the settings will be returned to their factory-set defaults.
3. When the All Clear operation is executed, the ladder program area will be allocated entirely to the ladder program. (The expansion DM and I/O comment areas will be set to 0 KW.)
The key sequence for all clear is shown below.
82
Preparation for Operation
The following procedure is used to clear memory completely.
Section 4-6
MEMORY ERR
I/O VER ERR
Continue pressing the CLR key once for each error message until “00000” appears on the display
00000
00000
00000MEMORY CLR?
HR CNT DM
00000MEM ALLCLR?
00000MEM ALLCLR
END
All clear
Partial Clear It is possible to retain the data in specified areas or part of the ladder program. To retain the data in the HR and AR, TC, and/or DM areas, press the appropriate key after entering REC/RESET. HR is pressed to designate both the HR and AR areas. In other words, specifying that HR is to be retained will ensure that AR is retained also. If not specified for retention, both areas will be cleared. CNT is used for the entire TC area. The display will show those areas that will be cleared.
It is also possible to retain a portion of the ladder program from the beginning to a specified address. After designating the data areas to be retained, specify the first program address to be cleared. For example, to leave addresses 00000 to
00122 untouched, but to clear addresses from 00123 to the end of Program
Memory, input 00123.
The key sequence for a partial memory clear is shown below.
Both AR and HR areas
TC area
DM area
Program Memory cleared from designated address.
Retained if pressed
83
Preparation for Operation Section 4-6
To leave the TC area uncleared and retain Program Memory addresses 00000 through 00122, input as follows:
00000
Memory Clear
00000
00000
00000MEMORY CLR?
HR CNT DM
00000MEMORY CLR?
HR DM
00123MEMORY CLR?
HR DM
00000MEMORY CLR
END HR DM
The memory clear operation clears all memory areas except the I/O comments and UM Allocation information.
The key sequence for a partial memory clear is shown below.
The Programming Console will display the following screens:
00000
00000
00000
00000MEMORY CLR?
HR CNT DM
00000MEMORY CLR
END HR CNT DM
Note When the write-protect switch (pin 1 of the CPU’s DIP switch) is set to ON the UM area (from DM 6144 through the ladder program) will not be cleared. Other data areas, such as HR, AR, CNT, and DM from DM 0000 to DM 6143 will be cleared.
4-6-4 Registering the I/O Table
The I/O Table Registration operation records the types of I/O Units controlled by the PC and the Rack locations of the I/O Units. It also clears all I/O bits.
It is not absolutely necessary to register the I/O table with the C200HS. When the
I/O table has not been registered, the PC will operate according to the I/O Units mounted when power is applied. The I/O verification/setting error will not occur.
84
Preparation for Operation Section 4-6
It is necessary to register the I/O table if I/O Units are changed, otherwise an I/O verification error message, “I/O VER ERR” or “I/O SET ERROR”, will appear when starting programming operations.
I/O Table Registration can be performed only in PROGRAM mode with the writeprotection switch (pin 1 of the CPU’s DIP switch) set to OFF (OFF=“WRITE”).
Group-2 HIgh-density I/O Units will not be displayed in the I/O table when it is displayed using a host computer. Four asterisks ( ∗∗∗∗ ), indicating no Unit, will be displayed instead.
Key Sequence
Initial I/O Table Registration
00000
00000
FUN (??)
00000IOTBL ?
?-?U=
00000IOTBL WRIT
????
00000IOTBL WRIT
9713
00000IOTBL WRIT
OK
Register I/O table
4-6-5 Clearing Error Messages
After the I/O table has been registered, any error messages recorded in memory should be cleared. It is assumed here that the causes of any of the errors for which error messages appear have already been taken care of. If the beeper sounds when an attempt is made to clear an error message, eliminate the cause of the error, and then clear the error message (refer to Section 10 Troubleshoot-
ing).
To display any recorded error messages, press CLR, FUN, and then MONTR.
The first message will appear. Pressing MONTR again will clear the present message and display the next error message. Continue pressing MONTR until all messages have been cleared.
Although error messages can be accessed in any mode, they can be cleared only in PROGRAM mode.
Key Sequence
85
Preparation for Operation Section 4-6
4-6-6 Verifying the I/O Table
The I/O Table Verification operation is used to check the I/O table registered in memory to see if it matches the actual sequence of I/O Units mounted. The first inconsistency discovered will be displayed as shown below. Every subsequent pressing of VER displays the next inconsistency.
Note This operation can be executed only when the I/O table has been registered.
Key Sequence
Example
Meaning of Displays
00000
00000
FUN (??)
00000IOTBL ?
?-?U=
00000IOTBL CHK
OK
00000IOTBL CHK
0-1U=O*** I***
(No errors)
(An error occurred)
Actual I/O words
Registered I/O table words
I/O slot number
Rack number
The following display indicates a C500, C1000H, or C2000H and C200H or
C200HS have the same unit number on a Remote I/O Slave Rack.
00000I/OTBL CHK
*-*U=----
The following display indicates a duplication in Optical I/O Unit unit numbers.
00000I/OTBL CHK
2**HU=R*-I R*-W
Indicates duplication
86
Preparation for Operation Section 4-6
4-6-7 Reading the I/O Table
The I/O Table Read operation is used to access the I/O table that is currently registered in the CPU memory. This operation can be performed in any PC mode.
Key Sequence
[0 to 2]
Rack number
[0 to 9]
Unit number
Press the EXT key to select Remote
I/O Slave Racks or Optical I/O Units.
Example 00000
00000
FUN (??)
00000IOTBL ?
?-?U=
(Slave Rack Units)
00000IOTBL ?
R??-?U=
(Optical I/O Unit)
00000IOTBL ?
2??LU=
00000IOTBL ?
?-?U=
00000IOTBL ?
0-?U=
00000IOTBL ?
0-5U=
00000IOTBL READ
0-5U=i*** 005
00000IOTBL READ
0-4U=o*** 004
00000IOTBL READ
0-5U=i*** 005
(Main Rack)
(Main Rack)
87
Preparation for Operation
Meaning of Displays
I/O Unit Designations for Displays
(see I/O Units Mounted in Remote Slave Racks, page 89)
Section 4-6
C500, 1000H/C2000H I/O Units
No. of points
16
32
64
Input Unit
I * * *
I I * *
I I I I
Output Unit
0 * * *
0 0 * *
0 0 0 0
C200H I/O Units
No. of points
8
16
Input Unit Output Unit i(*)* * o * * * i i * * o o * *
Note: ( ∗ ) is i for non-fatal errors or F_
I/O Units
Interrupt Input Units
00000IOTBL READ
*-*U=**** ***
I/O word number
I/O type: i: (input), o: (output)
Unit number (0 to 9)
Rack number (0 to 2)
00000IOTBL READ
*-*U=****
INT0: Mounted to CPU Rack.
IN**: Mounted to Expansion I/O Rack.
(Treated as an 8-point Input Unit.)
Special I/O Units 00000IOTBL READ
*-*U=$***
Blank: Unit 1 exclusively
W: Unit 2 exclusively
Special I/O
Unit type:
C: High-speed Counter
N: Position Control Unit
A: Other
Unit number (0 to 9)
Indicates Special I/O Unit
Remote I/O Master Units 00000IOTBL READ
*-*U=RMT*
Remote I/O
Master no. (0 or 1)
88
Preparation for Operation
Remote I/O Slave Racks 00000IOTBL READ
R**-*U=**** ***
Section 4-6
I/O word number
I/O type: I, O i, o (see tables on previous page)
Unit number (0 to 9)
Remote I/O Slave Unit number (0 to 4)
Remote I/O Master Unit number (0 or 1)
Indicates a Remote I/O Rack
Group-2 HIgh-density I/O
Units
00000IOTBL READ
*-*U=#***
2:
4:
2 words (32 pts)
4 words (64 pts)
I:
O:
Input Unit
Output Unit
Unit number (0 to 9)
Indicates Group-2 HIgh-density I/O Unit
Optical I/O Units and
Remote Terminals
Note Group-2 HIgh-density I/O Units will not be displayed in the I/O table when it is displayed using LSS (host computer). Four asterisks (
∗∗∗∗
), indicating no Unit, will be displayed instead.
00000IOTBL READ
2**HU=R*-*
I/O type: I (input), O (output), or
W (input/output)
Remote I/O Master Unit number (0 to 1)
Word (H: leftmost 8 bits; L: rightmost 8 bits)
I/O word number (200 to 231)
4-6-8 Clearing the I/O Table
The I/O Table Clear operation is used to delete the contents of the I/O table that is currently registered in the CPU memory. The PC will be set for operation based on the I/O Units mounted when the I/O Table Clear operation is performed.
The I/O Table Clear operation will reset all Special I/O Units and Link Units mounted at the time. Do not perform the I/O Table Clear operation when a Host or PC Link Unit, Remote I/O Master Unit, High-speed Counter Unit, Position
Control Unit, or other Special I/O Unit is in operation.
Note This operation can be performed only in PROGRAM mode with the write-protection switch (pin 1 of the CPU’s DIP switch) set to OFF (OFF=“WRITE”).
89
Preparation for Operation
Key Sequence
Section 4-6
Example 00000
00000
FUN (??)
00000IOTBL
?-?U=
00000IOTBL WRIT
????
00000IOTBL CANC
????
00000IOTBL CANC
9713
00000IOTBL CANC
OK
4-6-9 SYSMAC NET Link Table Transfer (CPU31/33-E Only)
The SYSMAC NET Link Table Transfer operation transfers a copy of the SYS-
MAC NET Link Data Link table to RAM or EEPROM program memory.This allows the user program and SYSMAC NET Link table to be written into EPROM together. This operation is applicable to the CPU31-E and CPU33-E only.
Note When power is applied to a PC which has a copy of a SYSMAC NET Link table stored in its program memory, the SYSMAC NET Link table of the CPU will be overwritten. Changes made in the SYSMAC NET Link table do not affect the copy of the SYSMAC NET Link table in program memory; SYSMAC NET Link
Table Transfer must be repeated to change the copy in program memory.
The SYSMAC NET Link Table Transfer operation will not work if:
• The Memory Unit is not RAM or EEPROM, or the write protect switch is not set to write.
•
There isn’t an END(01) instruction.
• The contents of program memory exceeds 14.7K words. (To find the size of the contents of program memory, do an instruction search for END(01).)
SYSMAC NET Link table transfer can only be done in PROGRAM mode.
90
Preparation for Operation
Key Sequence
Example
Section 4-6
00000
00000
FUN(??)
00000LINK TBL~UM
(SYSMAC-NET)????
00000LINK TBL~UM
(SYSMAC-NET)9713
00000LINK TBL~UM
OK
The following indicates that the
I/O table cannot be transferred.
00000LINK TBL~UM
DISABLED
91
Inputting, Modifying, and Checking the Program Section 4-7
4-7 Inputting, Modifying, and Checking the Program
Once a program is written in mnemonic code, it can be input directly into the PC from a Programming Console. Mnemonic code is keyed into Program Memory addresses from the Programming Console. Checking the program involves a syntax check to see that the program has been written according to syntax rules.
Once syntax errors are corrected, a trial execution can begin and, finally, correction under actual operating conditions can be made.
The operations required to input a program are explained below. Operations to modify programs that already exist in memory are also provided in this section, as well as the procedure to obtain the current cycle time.
Before starting to input a program, check to see whether there is a program already loaded. If there is a program loaded that you do not need, clear it first using the program memory clear key sequence, then input the new program. If you need the previous program, be sure to check it with the program check key sequence and correct it as required. Further debugging methods are provided in
Section 7 Program Monitoring and Execution.
4-7-1 Setting and Reading from Program Memory Address
When inputting a program for the first time, it is generally written to Program
Memory starting from address 00000. Because this address appears when the display is cleared, it is not necessary to specify it.
When inputting a program starting from other than 00000 or to read or modify a program that already exists in memory, the desired address must be designated.
To designate an address, press CLR and then input the desired address. Leading zeros of the address need not be input, i.e., when specifying an address such as 00053 you need to enter only 53. The contents of the designated address will not be displayed until the down key is pressed.
Once the down key has been pressed to display the contents of the designated address, the up and down keys can be used to scroll through Program Memory.
Each time one of these keys is pressed, the next or previous word in Program
Memory will be displayed.
If Program Memory is read in RUN or MONITOR mode, the ON/OFF status of any displayed bit will also be shown.
Key Sequence
92
Inputting, Modifying, and Checking the Program
Example
Section 4-7
If the following mnemonic code has already been input into Program Memory, the key inputs below would produce the displays shown.
00000
00200
00200READ OFF
LD 00000
00201READ ON
AND 00001
00202READ OFF
TIM 000
00202
TIM #0123
00203READ ON
LD 00100
Address Instruction
00200
00201
00202
LD
AND
TIM
00203 LD
#
Operands
00000
00001
000
0123
00100
4-7-2 Entering and Editing Programs
Programs can be entered and edited only in PROGRAM mode with the writeprotect switch (pin 1 of the CPU’s DIP switch) set to OFF (OFF=“WRITE”).
The same procedure is used to either input a program for the first time or to edit a program that already exists. In either case, the current contents of Program
Memory is overwritten, i.e., if there is no previous program, the NOP(00) instruction, which will be written at every address, will be overwritten.
To enter a program, input the mnemonic code that was produced from the ladder diagram step-by-step, ensuring that the correct address is set before starting.
Once the correct address is displayed, enter the first instruction word and press
WRITE. Next, enter the required operands, pressing WRITE after each, i.e.,
WRITE is pressed at the end of each line of the mnemonic code. When WRITE is pressed at the end of each line, the designated instruction or operand is entered and the next display will appear. If the instruction requires two or more words, the next display will indicate the next operand required and provide a default value for it. If the instruction requires only one word, the next address will be displayed.
Continue inputting each line of the mnemonic code until the entire program has been entered.
When inputting numeric values for operands, it is not necessary to input leading zeros. Leading zeros are required only when inputting function codes (see below). When designating operands, be sure to designate the data area for all but
IR and SR addresses by pressing the corresponding data area key, and to designate each constant by pressing CONT/#. CONT/# is not required for counter or timer SVs (see below). The AR area is designated by pressing SHIFT and then
HR. TC numbers as bit operands (i.e., completion flags) are designated by pressing either TIM or CNT before the address, depending on whether the TC number has been used to define a timer or a counter. To designate an indirect
DM address, press CH/
∗
before the address (pressing DM is not necessary for an indirect DM address).
93
Inputting, Modifying, and Checking the Program Section 4-7
Inputting SV for Counters and Timers
Designating Instructions
The SV (set value) for a timer or counter is generally entered as a constant, although inputting the address of a word that holds the SV is also possible. When inputting an SV as a constant, CONT/# is not required; just input the numeric value and press WRITE. To designate a word, press CLR and then input the word address as described above.
The most basic instructions are input using the Programming Console keys provided for them. All other instructions are entered using function codes. These function codes are always written after the instruction’s mnemonic. If no function code is given, there should be a Programming Console key for that instruction.
To designate the differentiated form of an instruction, press NOT after the function code.
To input an instruction using a function code, set the address, press FUN, input the function code including any leading zeros, press NOT if the differentiated form of the instruction is desired, input any bit operands or definers required for the instruction, and then press WRITE.
!
Caution Enter function codes with care and be sure to press SHIFT when required.
Key Sequence
[Address displayed] [Instruction word] [Operand]
94
Inputting, Modifying, and Checking the Program
Example
Section 4-7
The following program can be entered using the key inputs shown below. Displays will appear as indicated.
00000
Address Instruction
00200
00201
LD
TIM
00200
00202 TIMH(15)
#
#
Operands
00002
000
0123
001
0500
00200
LD 00002
00201READ
NOP (00)
00201
TIM 000
00201 TIM DATA
#0000
00201 TIM
#0123
00202READ
NOP (00)
00202
FUN (??)
00202
TIMH (15) 001
00202 TIMH DATA
#0000
00202 TIMH
#0500
00203READ
NOP (00)
95
Inputting, Modifying, and Checking the Program
Error Messages
Message
****REPL ROM
****PROG OVER
****ADDR OVER
****SETDATA ERR
****I/O NO. ERR
Section 4-7
The following error messages may appear when inputting a program. Correct the error as indicated and continue with the input operation. The asterisks in the displays shown below will be replaced with numeric data, normally an address, in the actual display.
Cause and correction
An attempt was made to write to write-protected RAM or EEPROM. Ensure that the write-protect switch is set to OFF.
The instruction at the last address in memory is not NOP(00). Erase all unnecessary instructions at the end of the program.
An address was set that is larger than the highest memory address in the UM area.
Input a smaller address
Data has been input in the wrong format or beyond defined limits, e.g., a hexadecimal value has been input for BCD. Re-enter the data. This error will generate a FALS 00 error.
A data area address has been designated that exceeds the limit of the data area, e.g., an address is too large. Confirm the requirements for the instruction and re-enter the address.
4-7-3 Checking the Program
Once a program has been entered, the syntax should be checked to verify that no programming rules have been violated. This check should also be performed if the program has been changed in any way that might create a syntax error.
To check the program, input the key sequence shown below. The numbers indicate the desired check level (see below). When the check level is entered, the program check will start. If an error is discovered, the check will stop and a display indicating the error will appear. Press SRCH to continue the check. If an error is not found, the program will be checked through to the first END(01), with a display indicating when each 64 instructions have been checked (e.g., display
#1 of the example after the following table).
CLR can be pressed to cancel the check after it has been started, and a display like display #2, in the example, will appear. When the check has reached the first
END, a display like display #3 will appear.
A syntax check can be performed on a program only in PROGRAM mode.
Key Sequence
To check up to END(01)
To abort
Check Levels and Error
Messages
(0, 1, 2, Check levels)
Three levels of program checking are available. The desired level must be designated to indicate the type of errors that are to be detected. The following table provides the error types, displays, and explanations of all syntax errors. Check level 0 checks for type A, B, and C errors; check level 1, for type A and B errors; and check level 2, for type A errors only.
The address where the error was generated will also be displayed.
96
Inputting, Modifying, and Checking the Program
Type Message
Type A ?????
NO END INSTR
CIRCUIT ERR
LOCN ERR
DUPL
SBN UNDEFD
JME UNDEFD
OPERAND ERR
STEP ERR
Type B IL-ILC ERR
JMP-JME ERR
SBN-RET ERR
Type C JMP UNDEFD
SBS UNDEFD
COIL DUPL
Section 4-7
Many of the following errors are for instructions that have not yet been described yet. Refer to 4-8 Controlling Bit Status or to Section 5 Instruction Set for details on these.
Meaning and appropriate response
The program has been lost. Re-enter the program.
There is no END(01) in the program. Write END(01) at the final address in the program.
The number of logic blocks and logic block instructions does not agree, i.e., either
LD or LD NOT has been used to start a logic block whose execution condition has not been used by another instruction, or a logic block instruction has been used that does not have the required number of logic blocks. Check your program.
An instruction is in the wrong place in the program. Check instruction requirements and correct the program.
The same jump number or subroutine number has been used twice. Correct the program so that the same number is only used once for each. (Jump number 00 may be used as often as required.)
SBS(91) has been programmed for a subroutine number that does not exist.
Correct the subroutine number or program the required subroutine.
A JME(04) is missing for a JMP(05). Correct the jump number or insert the proper
JME(04).
A constant entered for the instruction is not within defined values. Change the constant so that it lies within the proper range.
STEP(08) with a section number and STEP(08) without a section number have been used correctly. Check STEP(08) programming requirements and correct the program.
IL(02) and ILC(03) are not used in pairs. Correct the program so that each IL(02) has a unique ILC(03). Although this error message will appear if more than one
IL(02) is used with the same ILC(03), the program will executed as written. Make sure your program is written as desired before proceeding.
JMP(04) 00 and JME(05) 00 are not used in pairs. Although this error message will appear if more than one JMP(04) 00 is used with the same JME(05) 00, the program will be executed as written. Make sure your program is written as desired before proceeding.
If the displayed address is that of SBN(92), two different subroutines have been defined with the same subroutine number. Change one of the subroutine numbers or delete one of the subroutines. If the displayed address is that of RET(93),
RET(93) has not been used properly. Check requirements for RET(93) and correct the program.
JME(05) has been used with no JMP(04) with the same jump number. Add a
JMP(04) with the same number or delete the JME(05) that is not being used.
A subroutine exists that is not called by SBS(91). Program a subroutine call in the proper place, or delete the subroutine if it is not required.
The same bit is being controlled (i.e., turned ON and/or OFF) by more than one instruction (e.g., OUT, OUT NOT, DIFU(13), DIFD(14), KEEP(11), SFT(10)).
Although this is allowed for certain instructions, check instruction requirements to confirm that the program is correct or rewrite the program so that each bit is controlled by only one instruction.
97
Inputting, Modifying, and Checking the Program
Example
Section 4-7
The following example shows some of the displays that can appear as a result of a program check.
00000
00000PROG CHK
CHKLVL (0-2)?
00064PROG CHK
Display #1
Halts program check
00699CHK ABORTD
Display #2
Check continues until END(01)
02000PROG CHK
END (01)(02.7KW)
When errors are found
00178CIRCUIT ERR
OUT 00200
00200IL-ILC ERR
ILC (03)
02000NO END INST
END
Display #3
4-7-4 Displaying the Cycle Time
Once the program has been cleared of syntax errors, the cycle time should be checked. This is possible only in RUN or MONITOR mode while the program is being executed. See Section 6 Program Execution Timing for details on the cycle time.
To display the current average cycle time, press CLR then MONTR. The time displayed by this operation is a typical cycle time. The differences in displayed values depend on the execution conditions that exist when MONTR is pressed.
Example
00000
00000SCAN TIME
054.1MS
00000SCAN TIME
053.9MS
98
Inputting, Modifying, and Checking the Program Section 4-7
4-7-5 Program Searches
The program can be searched for occurrences of any designated instruction or data area address used in an instruction. Searches can be performed from any currently displayed address or from a cleared display.
To designate a bit address, press SHIFT, press CONT/#, then input the address, including any data area designation required, and press SRCH. To designate an instruction, input the instruction just as when inputting the program and press
SRCH. Once an occurrence of an instruction or bit address has been found, any additional occurrences of the same instruction or bit can be found by pressing
SRCH again. SRCH’G will be displayed while a search is in progress.
When the first word of a multiword instruction is displayed for a search operation, the other words of the instruction can be displayed by pressing the down key before continuing the search.
If Program Memory is read in RUN or MONITOR mode, the ON/OFF status of any bit displayed will also be shown.
Key Sequence
99
Inputting, Modifying, and Checking the Program
Example:
Instruction Search
00000
00000
LD 00000
00200SRCH
LD 00000
00202
LD 00000
02000SRCH
END (01)(02.7KW)
Section 4-7
00000
00100
00100
TIM 001
00203SRCH
TIM 001
00203 TIM DATA
#0123
Example:
Bit Search
00000
00000CONT SRCH
CONT 00005
00200CONT SRCH
LD 00005
00203CONT SRCH
AND 00005
02000
END (01)(02.7K)
4-7-6 Inserting and Deleting Instructions
In PROGRAM mode, any instruction that is currently displayed can be deleted or another instruction can be inserted before it. These operations are possible only in PROGRAM mode with the write-protect switch (pin 1 of the CPU’s DIP switch) set to OFF (OFF=“WRITE”).
To insert an instruction, display the instruction before which you want the new instruction to be placed, input the instruction word in the same way as when inputting a program initially, and then press INS and the down key. If other words are required for the instruction, input these in the same way as when inputting the program initially.
100
Inputting, Modifying, and Checking the Program Section 4-7
To delete an instruction, display the instruction word of the instruction to be deleted and then press DEL and the up key. All the words for the designated instruction will be deleted.
!
Caution Be careful not to inadvertently delete instructions; there is no way to recover them without reinputting them completely.
Key Sequences
Example
When an instruction is inserted or deleted, all addresses in Program Memory following the operation are adjusted automatically so that there are no blank addresses or no unaddressed instructions.
The following mnemonic code shows the changes that are achieved in a program through the key sequences and displays shown below.
Original Program
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
AND
LD
AND NOT
OR LD
AND
AND NOT
OUT
END(01)
Operands
00100
00101
00201
00102
––
00103
00104
00201
––
Before Insertion:
00100 00101
00201 00102
00103 00104
00105
00201
Before Deletion:
00100 00101
00201 00102
00103 00105 00104
Delete
00201
END(01)
END(01)
The following key inputs and displays show the procedure for achieving the program changes shown above.
101
Inputting, Modifying, and Checking the Program
Inserting an Instruction
00000
00000
OUT 00000
00000
OUT 00201
00207SRCH
OUT 00201
00206READ
AND NOT 00104
00206
AND 00000
00206
AND 00105
00206INSERT?
AND 00105
00207INSERT END
AND NOT 00104
00206READ
AND 00105
Deleting an Instruction
00000
00000
OUT 00000
00000
OUT 00201
00208SRCH
OUT 00201
00207READ
AND NOT 00104
00207 DELETE?
AND NOT 00104
00207DELETE END
OUT 00201
00206READ
AND 00105
102
Section 4-7
Find the address prior to the insertion point
Program After Insertion
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
LD
AND
LD
AND NOT
OR LD
AND
AND
AND NOT
OUT
END(01)
Operands
00100
00101
00201
00102
––
00103
00105
00104
00201
––
Insert the instruction
Find the instruction that requires deletion.
Program After Deletion
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
LD
AND NOT
LD
AND NOT
OR LD
AND
AND
AND NOT
OUT
Operands
00100
00101
00201
00102
––
00103
00105
00104
00201
Confirm that this is the instruction to be deleted.
Inputting, Modifying, and Checking the Program Section 4-7
4-7-7 Branching Instruction Lines
When an instruction line branches into two or more lines, it is sometimes necessary to use either interlocks or TR bits to maintain the execution condition that existed at a branching point. This is because instruction lines are executed across to a right-hand instruction before returning to the branching point to execute instructions on a branch line. If a condition exists on any of the instruction lines after the branching point, the execution condition could change during this time making proper execution impossible. The following diagrams illustrate this.
In both diagrams, instruction 1 is executed before returning to the branching point and moving on to the branch line leading to instruction 2.
00000
Branching point
00002
Instruction 1
Instruction 2
Address Instruction
00000
00001
00002
00003
LD
Instruction 1
AND
Instruction 2
Operands
00000
00002
Diagram A: Correct Operation
00000
Branching point
00001
Instruction 1
00002
Diagram B: Incorrect Operation
Instruction 2
Address Instruction
00000
00001
00002
00003
00004
LD
AND
Instruction 1
AND
Instruction 2
Operands
00000
00001
00002
TR Bits
If, as shown in diagram A, the execution condition that existed at the branching point cannot be changed before returning to the branch line (instructions at the far right do not change the execution condition), then the branch line will be executed correctly and no special programming measure is required.
If, as shown in diagram B, a condition exists between the branching point and the last instruction on the top instruction line, the execution condition at the branching point and the execution condition after completing the top instruction line will sometimes be different, making it impossible to ensure correct execution of the branch line.
There are two means of programming branching programs to preserve the execution condition. One is to use TR bits; the other, to use interlocks
(IL(02)/IL(03)).
The TR area provides eight bits, TR 0 through TR 7, that can be used to temporarily preserve execution conditions. If a TR bit is placed at a branching point, the current execution condition will be stored at the designated TR bit. When returning to the branching point, the TR bit restores the execution status that was saved when the branching point was first reached in program execution.
103
Inputting, Modifying, and Checking the Program Section 4-7
The previous diagram B can be written as shown below to ensure correct execution. In mnemonic code, the execution condition is stored at the branching point using the TR bit as the operand of the OUTPUT instruction. This execution condition is then restored after executing the right-hand instruction by using the same TR bit as the operand of a LOAD instruction
00000
TR 0
00001
00002
Diagram B: Corrected Using a TR bit
Instruction 1
Instruction 2
Address Instruction
00000
00001
00002
00003
00004
00005
00006
LD
OUT
AND
Instruction 1
LD
AND
Instruction 2
Operands
TR
00000
0
00001
TR 0
00002
In terms of actual instructions the above diagram would be as follows: The status of IR 00000 is loaded (a LOAD instruction) to establish the initial execution condition. This execution condition is then output using an OUTPUT instruction to
TR 0 to store the execution condition at the branching point. The execution condition is then ANDed with the status of IR 00001 and instruction 1 is executed accordingly. The execution condition that was stored at the branching point is then re-loaded (a LOAD instruction with TR 0 as the operand), this is ANDed with the status of IR 00002, and instruction 2 is executed accordingly.
The following example shows an application using two TR bits.
00000
TR 0
00001
TR 1
00004
00005
00002
00003
Instruction 1
Instruction 2
Instruction 3
Instruction 4
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
LD
AND
OUT
LD
AND
OUT
LD
OUT
AND
OUT
AND
OUT
LD
AND NOT
OUT
Operands
TR
TR
TR
TR
TR
00000
0
00001
1
00002
00500
1
00003
00501
0
00004
00502
0
00005
00503
In this example, TR 0 and TR 1 are used to store the execution conditions at the branching points. After executing instruction 1, the execution condition stored in
TR 1 is loaded for an AND with the status IR 00003. The execution condition stored in TR 0 is loaded twice, the first time for an AND with the status of IR
00004 and the second time for an AND with the inverse of the status of IR 00005.
TR bits can be used as many times as required as long as the same TR bit is not used more than once in the same instruction block. Here, a new instruction block is begun each time execution returns to the bus bar. If, in a single instruction block, it is necessary to have more than eight branching points that require the execution condition be saved, interlocks (which are described next) must be used.
104
Inputting, Modifying, and Checking the Program Section 4-7
When drawing a ladder diagram, be careful not to use TR bits unless necessary.
Often the number of instructions required for a program can be reduced and ease of understanding a program increased by redrawing a diagram that would otherwise required TR bits. In both of the following pairs of diagrams, the bottom versions require fewer instructions and do not require TR bits. In the first example, this is achieved by reorganizing the parts of the instruction block: the bottom one, by separating the second OUTPUT instruction and using another LOAD instruction to create the proper execution condition for it.
Note Although simplifying programs is always a concern, the order of execution of instructions is sometimes important. For example, a MOVE instruction may be required before the execution of a BINARY ADD instruction to place the proper data in the required operand word. Be sure that you have considered execution order before reorganizing a program to simplify it.
00000
TR 0
00001
Instruction 1
Instruction 2
00000
00000
00001
TR 0
00002
00004
00001
Instruction 2
Instruction 1
00003
Instruction 1
Instruction 2
Interlocks
00001
00000
00002 00003
Instruction 1
00001 00004
Instruction 2
Note TR bits are only used when programming using mnemonic code. They are not necessary when inputting ladder diagrams directly. The above limitations on the number of branching points requiring TR bits, and considerations on methods to reduce the number of programming instructions, still hold.
The problem of storing execution conditions at branching points can also be handled by using the INTERLOCK (IL(02)) and INTERLOCK CLEAR (ILC(03)) instructions to eliminate the branching point completely while allowing a specific execution condition to control a group of instructions. The INTERLOCK and IN-
TERLOCK CLEAR instructions are always used together.
105
Inputting, Modifying, and Checking the Program Section 4-7
When an INTERLOCK instruction is placed before a section of a ladder program, the execution condition for the INTERLOCK instruction will control the execution of all instruction up to the next INTERLOCK CLEAR instruction. If the execution condition for the INTERLOCK instruction is OFF, all right-hand instructions through the next INTERLOCK CLEAR instruction will be executed with OFF execution conditions to reset the entire section of the ladder diagram.
The effect that this has on particular instructions is described in 5-10 INTER-
LOCK and INTERLOCK CLEAR – IL(02) and ILC(03).
Diagram B can also be corrected with an interlock. Here, the conditions leading up to the branching point are placed on an instruction line for the INTERLOCK instruction, all of lines leading from the branching point are written as separate instruction lines, and another instruction line is added for the INTERLOCK
CLEAR instruction. No conditions are allowed on the instruction line for INTER-
LOCK CLEAR. Note that neither INTERLOCK nor INTERLOCK CLEAR requires an operand.
00000
00001
00002
IL(02)
Instruction 1
Instruction 2
ILC(03)
Address Instruction
00000
00001
00002
00003
00004
00005
00006
LD
IL(02)
LD
Instruction 1
LD
Instruction 2
ILC(03)
Operands
00000
---
00001
00002
---
If IR 00000 is ON in the revised version of diagram B, above, the status of IR
00001 and that of IR 00002 would determine the execution conditions for instructions 1 and 2, respectively. Because IR 00000 is ON, this would produce the same results as ANDing the status of each of these bits. If IR 00000 is OFF, the
INTERLOCK instruction would produce an OFF execution condition for instructions 1 and 2 and then execution would continue with the instruction line following the INTERLOCK CLEAR instruction.
As shown in the following diagram, more than one INTERLOCK instruction can be used within one instruction block; each is effective through the next INTER-
LOCK CLEAR instruction.
00000
00001
00002
00003
00005
00006
00004
IL(02)
Instruction 1
IL(02)
Instruction 2
Instruction 3
Instruction 4
ILC(03)
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
LD
IL(02)
LD
Instruction 1
LD
IL(02)
LD
AND NOT
Instruction 2
LD
Instruction 3
LD
Instruction 4
ILC(03)
Operands
00000
---
00001
00002
---
00003
00004
00005
00006
---
106
Inputting, Modifying, and Checking the Program Section 4-7
If IR 00000 in the above diagram is OFF (i.e., if the execution condition for the first INTERLOCK instruction is OFF), instructions 1 through 4 would be executed with OFF execution conditions and execution would move to the instruction following the INTERLOCK CLEAR instruction. If IR 00000 is ON, the status of IR 00001 would be loaded as the execution condition for instruction 1 and then the status of IR 00002 would be loaded to form the execution condition for the second INTERLOCK instruction. If IR 00002 is OFF, instructions 2 through 4 will be executed with OFF execution conditions. If IR 00002 is ON, IR 00003, IR
00005, and IR 00006 will determine the first execution condition in new instruction lines.
4-7-8 Jumps
A specific section of a program can be skipped according to a designated execution condition. Although this is similar to what happens when the execution condition for an INTERLOCK instruction is OFF, with jumps, the operands for all instructions maintain status. Jumps can therefore be used to control devices that require a sustained output, e.g., pneumatics and hydraulics, whereas interlocks can be used to control devices that do not required a sustained output, e.g., electronic instruments.
Jumps are created using the JUMP (JMP(04)) and JUMP END (JME(05)) instructions. If the execution condition for a JUMP instruction is ON, the program is executed normally as if the jump did not exist. If the execution condition for the
JUMP instruction is OFF, program execution moves immediately to a JUMP
END instruction without changing the status of anything between the JUMP and
JUMP END instruction.
All JUMP and JUMP END instructions are assigned jump numbers ranging between 00 and 99. There are two types of jumps. The jump number used determines the type of jump.
A jump can be defined using jump numbers 01 through 99 only once, i.e., each of these numbers can be used once in a JUMP instruction and once in a JUMP
END instruction. When a JUMP instruction assigned one of these numbers is executed, execution moves immediately to the JUMP END instruction that has the same number as if all of the instruction between them did not exist. Diagram
B from the TR bit and interlock example could be redrawn as shown below using a jump. Although 01 has been used as the jump number, any number between
01 and 99 could be used as long as it has not already been used in a different part of the program. JUMP and JUMP END require no other operand and JUMP END never has conditions on the instruction line leading to it.
00000
00001
00002
Diagram B: Corrected with a Jump
JMP(04) 01
Instruction 1
Instruction 2
JME(05) 01
Address Instruction
00000
00001
00002
00003
00004
00005
00006
LD
JMP(04)
LD
Instruction 1
LD
Instruction 2
JME(05)
Operands
00000
01
00001
00002
015
This version of diagram B would have a shorter execution time when 00000 was
OFF than any of the other versions.
107
Controlling Bit Status Section 4-8
The other type of jump is created with a jump number of 00. As many jumps as desired can be created using jump number 00 and JUMP instructions using 00 can be used consecutively without a JUMP END using 00 between them. It is even possible for all JUMP 00 instructions to move program execution to the same JUMP END 00, i.e., only one JUMP END 00 instruction is required for all
JUMP 00 instruction in the program. When 00 is used as the jump number for a
JUMP instruction, program execution moves to the instruction following the next
JUMP END instruction with a jump number of 00. Although, as in all jumps, no status is changed and no instructions are executed between the JUMP 00 and
JUMP END 00 instructions, the program must search for the next JUMP END 00 instruction, producing a slightly longer execution time.
Execution of programs containing multiple JUMP 00 instructions for one JUMP
END 00 instruction is similar to that of interlocked sections. The following diagram is the same as that used for the interlock example above, except redrawn with jumps. The execution of this diagram would differ from that of the diagram described above (e.g., in the previous diagram interlocks would reset certain parts of the interlocked section, however, jumps do not affect the status of any bit between the JUMP and JUMP END instructions).
00000
00001
00002
00003
00005
00006
00004
JMP(04) 00
Instruction 1
JMP(04) 00
Instruction 2
Instruction 3
Instruction 4
JME(05) 00
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
LD
JMP(04)
LD
Instruction 1
LD
JMP(04)
LD
AND NOT
Instruction 2
LD
Instruction 3
LD
Instruction 4
JME(05)
Operands
00000
00
00001
00002
00
00003
00004
00005
00006
00
4-8 Controlling Bit Status
There are five instructions that can be used generally to control individual bit status. These are the OUTPUT, OUTPUT NOT, DIFFERENTIATE UP,
DIFFERENTIATE DOWN, and KEEP instructions. All of these instructions appear as the last instruction in an instruction line and take a bit address for an operand. Although details are provided in 5-9 Bit Control Instructions, these instructions (except for OUTPUT and OUTPUT NOT, which have already been introduced) are described here because of their importance in most programs. Although these instructions are used to turn ON and OFF output bits in the IR area
(i.e., to send or stop output signals to external devices), they are also used to control the status of other bits in the IR area or in other data areas.
108
Controlling Bit Status Section 4-8
4-8-1 DIFFERENTIATE UP and DIFFERENTIATE DOWN
DIFFERENTIATE UP and DIFFERENTIATE DOWN instructions are used to turn the operand bit ON for one cycle at a time. The DIFFERENTIATE UP instruction turns ON the operand bit for one cycle after the execution condition for it goes from OFF to ON; the DIFFERENTIATE DOWN instruction turns ON the operand bit for one cycle after the execution condition for it goes from ON to OFF.
Both of these instructions require only one line of mnemonic code.
00000
00001
DIFU(13) 00200
DIFD(14) 00201
Address Instruction
00000
00001
LD
DIFU(13)
Address Instruction
00000
00001
LD
DIFD(14)
Operands
00000
00200
Operands
00001
00201
Here, IR 00200 will be turned ON for one cycle after IR 00000 goes ON. The next time DIFU(13) 00200 is executed, IR 00200 will be turned OFF, regardless of the status of IR 00000. With the DIFFERENTIATE DOWN instruction, IR 00201 will be turned ON for one cycle after IR 00001 goes OFF (IR 00201 will be kept OFF until then), and will be turned OFF the next time DIFD(14) 00201 is executed.
4-8-2 KEEP
00002
00004
00005
00003
The KEEP instruction is used to maintain the status of the operand bit based on two execution conditions. To do this, the KEEP instruction is connected to two instruction lines. When the execution condition at the end of the first instruction line is ON, the operand bit of the KEEP instruction is turned ON. When the execution condition at the end of the second instruction line is ON, the operand bit of the KEEP instruction is turned OFF. The operand bit for the KEEP instruction will maintain its ON or OFF status even if it is located in an interlocked section of the diagram.
In the following example, HR 0000 will be turned ON when IR 00002 is ON and IR
00003 is OFF. HR 0000 will then remain ON until either IR 00004 or IR 00005 turns ON. With KEEP, as with all instructions requiring more than one instruction line, the instruction lines are coded first before the instruction that they control.
S: set input
R: reset input
KEEP(11)
HR 0000
Address Instruction
00000
00001
00002
00003
00004
LD
AND NOT
LD
OR
KEEP(11)
Operands
HR
00002
00003
00004
00005
0000
4-8-3 Self-maintaining Bits (Seal)
Although the KEEP instruction can be used to create self-maintaining bits, it is sometimes necessary to create self-maintaining bits in another way so that they can be turned OFF when in an interlocked section of a program.
109
Work Bits
00002 00003
HR 0000
Section 4-9
To create a self-maintaining bit, the operand bit of an OUTPUT instruction is used as a condition for the same OUTPUT instruction in an OR setup so that the operand bit of the OUTPUT instruction will remain ON or OFF until changes occur in other bits. At least one other condition is used just before the OUTPUT instruction to function as a reset. Without this reset, there would be no way to control the operand bit of the OUTPUT instruction.
The above diagram for the KEEP instruction can be rewritten as shown below.
The only difference in these diagrams would be their operation in an interlocked program section when the execution condition for the INTERLOCK instruction was ON. Here, just as in the same diagram using the KEEP instruction, two reset bits are used, i.e., HR 0000 can be turned OFF by turning ON either IR 00004 or
IR 00005.
00004 00005
HR 0000
Address Instruction
00000
00001
00002
00003
00004
00005
LD
AND NOT
OR
AND NOT
AND NOT
OUT
Operands
HR
HR
00002
00003
0000
00004
00005
0000
4-9 Work Bits (Internal Relays)
In programming, combining conditions to directly produce execution conditions is often extremely difficult. These difficulties are easily overcome, however, by using certain bits to trigger other instructions indirectly. Such programming is achieved by using work bits. Sometimes entire words are required for these purposes. These words are referred to as work words.
Work bits are not transferred to or from the PC. They are bits selected by the programmer to facilitate programming as described above. I/O bits and other dedicated bits cannot be used as works bits. All bits in the IR area that are not allocated as I/O bits, and certain unused bits in the AR area, are available for use as work bits. Be careful to keep an accurate record of how and where you use work bits. This helps in program planning and writing, and also aids in debugging operations.
Work Bit Applications Examples given later in this subsection show two of the most common ways to employ work bits. These should act as a guide to the almost limitless number of ways in which the work bits can be used. Whenever difficulties arise in programming a control action, consideration should be given to work bits and how they might be used to simplify programming.
Work bits are often used with the OUTPUT, OUTPUT NOT, DIFFERENTIATE
UP, DIFFERENTIATE DOWN, and KEEP instructions. The work bit is used first as the operand for one of these instructions so that later it can be used as a condition that will determine how other instructions will be executed. Work bits can also be used with other instructions, e.g., with the SHIFT REGISTER instruction
(SFT(10)). An example of the use of work words and bits with the SHIFT REGIS-
TER instruction is provided in 5-15-1 SHIFT REGISTER – SFT(10).
Although they are not always specifically referred to as work bits, many of the bits used in the examples in Section 5 Instruction Set use work bits. Understanding the use of these bits is essential to effective programming.
110
Work Bits
Reducing Complex
Conditions
00000
00002
00003
24600
00004
24600
00001
24600 00004
Section 4-9
Work bits can be used to simplify programming when a certain combination of conditions is repeatedly used in combination with other conditions. In the following example, IR 00000, IR 00001, IR 00002, and IR 00003 are combined in a logic block that stores the resulting execution condition as the status of IR
24600. IR 24600 is then combined with various other conditions to determine output conditions for IR 00100, IR 00101, and IR 00102, i.e., to turn the outputs allocated to these bits ON or OFF.
00005
00005
24600
00100
00101
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
LD
AND NOT
OR
OR NOT
OUT
LD
AND
AND NOT
OUT
LD
OR NOT
AND
OUT
LD NOT
OR
OR
OUT
Operands
00000
00001
00002
00003
24600
24600
00004
00005
00100
24600
00004
00005
00101
24600
00006
00007
00102
00102
00006
00007
Differentiated Conditions Work bits can also be used if differential treatment is necessary for some, but not all, of the conditions required for execution of an instruction. In this example, IR
00100 must be left ON continuously as long as IR 00001 is ON and both IR
00002 and IR 00003 are OFF, or as long as IR 00004 is ON and IR 00005 is OFF.
It must be turned ON for only one cycle each time IR 00000 turns ON (unless one of the preceding conditions is keeping it ON continuously).
111
Programming Precautions Section 4-10
This action is easily programmed by using IR 22500 as a work bit as the operand of the DIFFERENTIATE UP instruction (DIFU(13)). When IR 00000 turns ON, IR
22500 will be turned ON for one cycle and then be turned OFF the next cycle by
DIFU(13). Assuming the other conditions controlling IR 00100 are not keeping it
ON, the work bit IR 22500 will turn IR 00100 ON for one cycle only.
00000
22500
00001 00002 00003
00004 00005
DIFU(13) 22500
00100
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
LD
DIFU(13)
LD
LD
AND NOT
AND NOT
OR LD
LD
AND NOT
OR LD
OUT
Operands
00000
22500
22500
00001
00002
00003
---
00004
00005
---
00100
4-10 Programming Precautions
The number of conditions that can be used in series or parallel is unlimited as long as the memory capacity of the PC is not exceeded. Therefore, use as many conditions as required to draw a clear diagram. Although very complicated diagrams can be drawn with instruction lines, there must not be any conditions on lines running vertically between two other instruction lines. Diagram A shown below, for example, is not possible, and should be drawn as diagram B. Mnemonic code is provided for diagram B only; coding diagram A would be impossible.
00002 00000
00004
00001 00003
Instruction 1
Instruction 2
Diagram A
00001
00000
00000
00001
00004
00004
Diagram B
00002
00003
Instruction 1
Instruction 2
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
LD
AND
OR
AND
Instruction 1
LD
AND
OR
AND NOT
Instruction 2
Operands
00001
00004
00000
00002
00000
00004
00001
00003
The number of times any particular bit can be assigned to conditions is not limited, so use them as many times as required to simplify your program. Often, complicated programs are the result of attempts to reduce the number of times a bit is used.
112
Programming Precautions Section 4-10
Except for instructions for which conditions are not allowed (e.g., INTERLOCK
CLEAR and JUMP END, see below), every instruction line must also have at least one condition on it to determine the execution condition for the instruction at the right. Again, diagram A , below, must be drawn as diagram B. If an instruction must be continuously executed (e.g., if an output must always be kept ON while the program is being executed), the Always ON Flag (SR 25313) in the SR area can be used.
00000
00001 00207
00001 00207
00000
Instruction
25313
Diagram A: Incorrect
Diagram B
Instruction
Address Instruction
00000
00001
LD
Instruction
Operands
25313
There are a few exceptions to this rule, including the INTERLOCK CLEAR,
JUMP END, and step instructions. Each of these instructions is used as the second of a pair of instructions and is controlled by the execution condition of the first of the pair. Conditions should not be placed on the instruction lines leading to these instructions. Refer to Section 5 Instruction Set for details.
When drawing ladder diagrams, it is important to keep in mind the number of instructions that will be required to input it. In diagram A, below, an OR LOAD instruction will be required to combine the top and bottom instruction lines. This can be avoided by redrawing as shown in diagram B so that no AND LOAD or OR
LOAD instructions are required. Refer to 5-8-2 AND LOAD and OR LOAD for more details and Section 7 Program Monitoring and Execution for further examples.
Diagram A
00207
00207
Address Instruction
00000
00001
00002
00003
00004
LD
LD
AND
OR LD
OUT
Operands
00000
00001
00207
---
00207
Address Instruction
00000
00001
00002
00003
LD
AND
OR
OUT
Operands
00001
00207
00000
002
Diagram B
113
Program Execution Section 4-11
4-11 Program Execution
When program execution is started, the CPU cycles the program from top to bottom, checking all conditions and executing all instructions accordingly as it moves down the bus bar. It is important that instructions be placed in the proper order so that, for example, the desired data is moved to a word before that word is used as the operand for an instruction. Remember that an instruction line is completed to the terminal instruction at the right before executing an instruction lines branching from the first instruction line to other terminal instructions at the right.
Program execution is only one of the tasks carried out by the CPU as part of the cycle time. Refer to Section 6 Program Execution Timing for details.
114
SECTION 5
Instruction Set
The C200HS PC has a large programming instruction set that allows for easy programming of complicated control processes.
This section explains instructions individually and provides the ladder diagram symbol, data areas, and flags used with each.
The C200HS can process more than 100 instructions that require function codes, but only 100 function codes (00 to 99) are available. Some instructions, called expansion instructions, do not have fixed function codes and must be assigned function codes from the 18 function codes set aside for expansion instructions before they can be used.
The many instructions provided by the C200HS are organized in the following subsections by instruction group. These groups include Ladder Diagram Instructions, Bit Control Instructions, Timer and Counter Instructions, Data Shifting Instructions,
Data Movement Instructions, Data Comparison Instructions, Data Conversion Instructions, BCD Calculation Instructions,
Binary Calculation Instructions, Logic Instructions, Subroutines, Special Instructions, and Network Instructions.
Some instructions, such as Timer and Counter instructions, are used to control execution of other instructions, e.g., a TIM
Completion Flag might be used to turn ON a bit when the time period set for the timer has expired. Although these other instructions are often used to control output bits through the Output instruction, they can be used to control execution of other instructions as well. The Output instructions used in examples in this manual can therefore generally be replaced by other instructions to modify the program for specific applications other than controlling output bits directly.
5-1 Notation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Instruction Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Data Areas, Definer Values, and Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Differentiated Instructions
5-5 Expansion Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Coding Right-hand Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7 Instruction Set Lists
5-7-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7-2 Alphabetic List by Mnemonic
5-8 Ladder Diagram Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8-1 LOAD, LOAD NOT, AND, AND NOT, OR, and OR NOT . . . . . . . . . . . . . . . . . . . . . . .
5-8-2 AND LOAD and OR LOAD
5-9 Bit Control Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9-1 OUTPUT and OUTPUT NOT – OUT and OUT NOT . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9-2
5-9-3
DIFFERENTIATE UP and DOWN – DIFU(13) and DIFD(14)
SET and RESET – SET and RSET
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9-4 KEEP – KEEP(11) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03) . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-11 JUMP and JUMP END – JMP(04) and JME(05) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-12 END – END(01) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-13 NO OPERATION – NOP(00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-14 Timer and Counter Instructions
5-14-1 TIMER – TIM
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-14-2 HIGH-SPEED TIMER – TIMH(15) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-14-3 TOTALIZING TIMER – TTIM(87) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-14-4 COUNTER – CNT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-14-5 REVERSIBLE COUNTER – CNTR(12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15 Data Shifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-1 SHIFT REGISTER – SFT(10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-2 REVERSIBLE SHIFT REGISTER – SFTR(84) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-3 ARITHMETIC SHIFT LEFT – ASL(25) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-4 ARITHMETIC SHIFT RIGHT – ASR(26)
5-15-5 ROTATE LEFT – ROL(27)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-6 ROTATE RIGHT – ROR(28) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-7 ONE DIGIT SHIFT LEFT – SLD(74)
5-15-8 ONE DIGIT SHIFT RIGHT – SRD(75)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-9 WORD SHIFT – WSFT(16) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15-10 ASYNCHRONOUS SHIFT REGISTER – ASFT(17) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16 Data Movement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-1 MOVE – MOV(21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
152
154
154
155
155
144
145
148
150
150
138
138
138
139
143
131
133
133
135
137
156
156
157
157
158
159
125
125
125
129
129
130
130
130
118
118
118
119
120
122
115
116
5-16-2 MOVE NOT – MVN(22) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-3 BLOCK SET – BSET(71) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-4 BLOCK TRANSFER – XFER(70) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-5 DATA EXCHANGE – XCHG(73) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-6 SINGLE WORD DISTRIBUTE – DIST(80) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-7 DATA COLLECT – COLL(81) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-8 MOVE BIT – MOVB(82) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-9 MOVE DIGIT – MOVD(83) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16-10 TRANSFER BITS – XFRB(62) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17 Data Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-1 MULTI-WORD COMPARE – MCMP(19)
5-17-2 COMPARE – CMP(20)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-3 DOUBLE COMPARE – CMPL(60) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-4 BLOCK COMPARE – BCMP(68) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-5 TABLE COMPARE – TCMP(85) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-6 AREA RANGE COMPARE – ZCP(88) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-7 DOUBLE AREA RANGE COMPARE – ZCPL(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-8 SIGNED BINARY COMPARE – CPS(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-17-9 DOUBLE SIGNED BINARY COMPARE – CPSL(––) . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18 Data Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-1 BCD-TO-BINARY – BIN(23) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-2 DOUBLE BCD-TO-DOUBLE BINARY – BINL(58) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-3 BINARY-TO-BCD – BCD(24) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-4 DOUBLE BINARY-TO-DOUBLE BCD – BCDL(59) . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-5 HOURS-TO-SECONDS – SEC(65) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-6 SECONDS-TO-HOURS – HMS(66) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-7 4-TO-16 DECODER – MLPX(76)
5-18-8 16-TO-4 ENCODER – DMPX(77)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-9 7-SEGMENT DECODER – SDEC(78) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-10 ASCII CONVERT – ASC(86) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-11 ASCII-TO-HEXADECIMAL – HEX(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-12 SCALING – SCL(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-13 COLUMN TO LINE – LINE(63) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-14 LINE TO COLUMN – COLM(64)
5-18-15 2’S COMPLEMENT – NEG(––)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-18-16 DOUBLE 2’S COMPLEMENT – NEGL(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19 BCD Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-1 INCREMENT – INC(38) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-2 DECREMENT – DEC(39) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-3 SET CARRY – STC(40) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-4 CLEAR CARRY – CLC(41) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-5 BCD ADD – ADD(30) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-6 DOUBLE BCD ADD – ADDL(54) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-7 BCD SUBTRACT – SUB(31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-8 DOUBLE BCD SUBTRACT – SUBL(55)
5-19-9 BCD MULTIPLY – MUL(32)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-10 DOUBLE BCD MULTIPLY – MULL(56)
5-19-11 BCD DIVIDE – DIV(33)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-12 DOUBLE BCD DIVIDE – DIVL(57) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-13 FLOATING POINT DIVIDE – FDIV(79) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-19-14 SQUARE ROOT – ROOT(72) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20 Binary Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-1 BINARY ADD – ADB(50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-2 BINARY SUBTRACT – SBB(51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-3 BINARY MULTIPLY – MLB(52) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-4 BINARY DIVIDE – DVB(53) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-5 DOUBLE BINARY ADD – ADBL(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-6 DOUBLE BINARY SUBTRACT – SBBL(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
184
185
186
189
192
195
196
199
181
181
182
182
183
201
202
203
204
205
205
205
206
206
213
213
214
215
218
220
220
222
206
207
208
210
212
225
225
226
228
169
170
173
174
176
177
178
179
180
159
160
161
162
162
164
166
167
168
169
5-20-7 SIGNED BINARY MULTIPLY – MBS(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-8 DOUBLE SIGNED BINARY MULTIPLY – MBSL(––) . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-9 SIGNED BINARY DIVIDE – DBS(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-20-10 DOUBLE SIGNED BINARY DIVIDE – DBSL(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21 Special Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21-1 FIND MAXIMUM – MAX(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21-2 FIND MINIMUM – MIN(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21-3 AVERAGE VALUE – AVG(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21-4 SUM – SUM(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21-5 ARITHMETIC PROCESS – APR(69) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21-6 PID CONTROL – PID(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-22 Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-22-1 COMPLEMENT – COM(29) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-22-2 LOGICAL AND – ANDW(34) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-22-3 LOGICAL OR – ORW(35) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-22-4 EXCLUSIVE OR – XORW(36) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-22-5 EXCLUSIVE NOR – XNRW(37)
5-23 Subroutines and Interrupt Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-23-1 Subroutines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-23-2 Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-23-3 SUBROUTINE ENTER – SBS(91) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-23-4 SUBROUTINE DEFINE and RETURN – SBN(92)/RET(93) . . . . . . . . . . . . . . . . . . . . .
5-23-5 MACRO – MCRO(99) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-23-6 INTERRUPT CONTROL – INT(89) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-24 Step Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-24-1 STEP DEFINE and STEP START–STEP(08)/SNXT(09) . . . . . . . . . . . . . . . . . . . . . . . . .
5-25 Special Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-1 FAILURE ALARM – FAL(06) and
SEVERE FAILURE ALARM – FALS(07) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-2 CYCLE TIME – SCAN(18) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-3 TRACE MEMORY SAMPLING – TRSM(45) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-4 MESSAGE DISPLAY – MSG(46) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-5 LONG MESSAGE – LMSG(47) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-6 TERMINAL MODE – TERM(48) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-7 WATCHDOG TIMER REFRESH – WDT(94)
5-25-8 I/O REFRESH – IORF(97)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-9 GROUP-2 HIGH-DENSITY I/O REFRESH – MPRF(61)
5-25-10 BIT COUNTER – BCNT(67)
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-11 FRAME CHECKSUM – FCS(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-12 FAILURE POINT DETECTION – FPD(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-13 DATA SEARCH – SRCH(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-25-14 EXPANSION DM READ – XDMR(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-26 Network Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-26-1 NETWORK SEND – SEND(90) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-26-2 NETWORK RECEIVE – RECV(98) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-26-3 About Network Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-27 Serial Communications Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-27-1 RECEIVE – RXD(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-27-2 TRANSMIT – TXD(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-28 Advanced I/O Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-28-1 7-SEGMENT DISPLAY OUTPUT – 7SEG(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-28-2 DIGITAL SWITCH INPUT – DSW(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-28-3 HEXADECIMAL KEY INPUT – HKY(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-28-4 TEN KEY INPUT – TKY(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-28-5 MATRIX INPUT – MTR(––) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
292
292
294
296
284
286
290
291
298
298
300
282
282
283
284
276
277
278
279
280
281
302
302
305
309
312
314
254
254
254
255
258
260
261
263
267
267
276
250
251
252
253
238
240
243
250
234
234
235
236
230
231
232
233
117
Data Areas, Definer Values, and Flags
5-1 Notation
Section 5-3
In the remainder of this manual, all instructions will be referred to by their mnemonics. For example, the Output instruction will be called OUT; the AND Load instruction, AND LD. If you’re not sure of the instruction a mnemonic is used for, refer to Appendix B Programming Instructions.
If an instruction is assigned a function code, it will be given in parentheses after the mnemonic. These function codes, which are 2-digit decimal numbers, are used to input most instructions into the CPU and are described briefly below and in more detail in 4-7 Inputting, Modifying, and Checking the Program. A table of instructions listed in order of function codes, is also provided in Appendix B.
An @ before a mnemonic indicates the differentiated version of that instruction.
Differentiated instructions are explained in Section 5-4.
5-2 Instruction Format
Most instructions have at least one or more operands associated with them. Operands indicate or provide the data on which an instruction is to be performed.
These are sometimes input as the actual numeric values (i.e., as constants), but are usually the addresses of data area words or bits that contain the data to be used. A bit whose address is designated as an operand is called an operand bit; a word whose address is designated as an operand is called an operand word. In some instructions, the word address designated in an instruction indicates the first of multiple words containing the desired data.
Each instruction requires one or more words in Program Memory. The first word is the instruction word, which specifies the instruction and contains any definers
(described below) or operand bits required by the instruction. Other operands required by the instruction are contained in following words, one operand per word. Some instructions require up to four words.
A definer is an operand associated with an instruction and contained in the same word as the instruction itself. These operands define the instruction rather than telling what data it is to use. Examples of definers are TC numbers, which are used in timer and counter instructions to create timers and counters, as well as jump numbers (which define which Jump instruction is paired with which Jump
End instruction). Bit operands are also contained in the same word as the instruction itself, although these are not considered definers.
5-3 Data Areas, Definer Values, and Flags
In this section, each instruction description includes its ladder diagram symbol, the data areas that can be used by its operands, and the values that can be used as definers. Details for the data areas are also specified by the operand names and the type of data required for each operand (i.e., word or bit and, for words, hexadecimal or BCD).
Not all addresses in the specified data areas are necessarily allowed for an operand, e.g., if an operand requires two words, the last word in a data area cannot be designated as the first word of the operand because all words for a single operand must be within the same data area. Also, not all words in the SR and DM areas are writeable as operands (see Section 3 Memory Areas for details.) Other specific limitations are given in a Limitations subsection. Refer to Section 3
Memory Areas for addressing conventions and the addresses of flags and control bits.
118
Differentiated Instructions Section 5-4
!
Caution The IR and SR areas are considered as separate data areas. If an operand has access to one area, it doesn’t necessarily mean that the same operand will have access to the other area. The border between the IR and SR areas can, however, be crossed for a single operand, i.e., the last bit in the IR area may be specified for an operand that requires more than one word as long as the
SR area is also allowed for that operand.
Indirect Addressing
The Flags subsection lists flags that are affected by execution of an instruction.
These flags include the following SR area flags.
EQ
LE
OF
UF
Abbreviation
ER
CY
GR
Name
Instruction Execution Error Flag
Carry Flag
Greater Than Flag
Equals Flag
Less Than Flag
Overflow Flag
Underflow Flag
25503
25504
25505
Bit
25506
25507
25404
25405
ER is the flag most commonly used for monitoring an instruction’s execution.
When ER goes ON, it indicates that an error has occurred in attempting to execute the current instruction. The Flags subsection of each instruction lists possible reasons for ER being ON. ER will turn ON if operands are not entered correctly. Instructions are not executed when ER is ON. A table of instructions and the flags they affect is provided in Appendix C Error and Arithmetic Flag Opera-
tion.
When the DM area is specified for an operand, an indirect address can be used.
Indirect DM addressing is specified by placing an asterisk before the DM: ∗ DM.
When an indirect DM address is specified, the designated DM word will contain the address of the DM word that contains the data that will be used as the operand of the instruction. If, for example, ∗ DM 0001 was designated as the first operand and LR 00 as the second operand of MOV(21), the contents of DM 0001 was
1111, and DM 1111 contained 5555, the value 5555 would be moved to LR 00.
MOV(21)
∗ DM 0001
LR 00
Indirect address
Word
DM 0000
DM 0001
DM 0002
Content
4C59
1111
F35A
Indicates
DM 1111.
DM 1111
DM 1113
DM 1114
5555
2506
D541
5555 moved to LR 00.
Designating Constants
When using indirect addressing, the address of the desired word must be in BCD and it must specify a word within the DM area. In the above example, the content of
∗
DM 0000 would have to be in BCD between 0000 and 1999.
Although data area addresses are most often given as operands, many operands and all definers are input as constants. The available value range for a given definer or operand depends on the particular instruction that uses it. Constants must also be entered in the form required by the instruction, i.e., in BCD or in hexadecimal.
5-4 Differentiated Instructions
Most instructions are provided in both differentiated and non-differentiated forms. Differentiated instructions are distinguished by an @ in front of the instruction mnemonic.
119
Expansion Instructions Section 5-5
00000
A non-differentiated instruction is executed each time it is cycled as long as its execution condition is ON. A differentiated instruction is executed only once after its execution condition goes from OFF to ON. If the execution condition has not changed or has changed from ON to OFF since the last time the instruction was cycled, the instruction will not be executed. The following two examples show how this works with MOV(21) and @MOV(21), which are used to move the data in the address designated by the first operand to the address designated by the second operand.
Address Instruction
00000 LD
00001 MOV(21)
Operands
00000
Diagram A
MOV(21)
HR 10
DM 0000
HR
DM
10
0000
00000
@MOV(21)
HR 10
Address Instruction
00000 LD
00001 @MOV(21)
Operands
00000
Diagram B DM 0000
HR
DM
10
0000
In diagram A, the non-differentiated MOV(21) will move the content of HR 10 to
DM 0000 whenever it is cycled with 00000. If the cycle time is 80 ms and 00000 remains ON for 2.0 seconds, this move operation will be performed 25 times and only the last value moved to DM 0000 will be preserved there.
In diagram B, the differentiated @MOV(21) will move the content of HR 10 to DM
0000 only once after 00000 goes ON. Even if 00000 remains ON for 2.0 seconds with the same 80 ms cycle time, the move operation will be executed only once during the first cycle in which 00000 has changed from OFF to ON. Because the content of HR 10 could very well change during the 2 seconds while 00000 is
ON, the final content of DM 0000 after the 2 seconds could be different depending on whether MOV(21) or @MOV(21) was used.
All operands, ladder diagram symbols, and other specifications for instructions are the same regardless of whether the differentiated or non-differentiated form of an instruction is used. When inputting, the same function codes are also used, but NOT is input after the function code to designate the differentiated form of an instruction. Most, but not all, instructions have differentiated forms.
Refer to 5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and IL(03) for the effects of interlocks on differentiated instructions.
The C200HS also provides differentiation instructions: DIFU(13) and DIFD(14).
DIFU(13) operates the same as a differentiated instruction, but is used to turn
ON a bit for one cycle. DIFD(14) also turns ON a bit for one cycle, but does it when the execution condition has changed from ON to OFF. Refer to 5-9-2 DIF-
FERENTIATE UP and DOWN - DIFU(13) and DIFD(14) for details.
!
Caution Do not use SR 25313 and SR25315 for differentiated instructions. These bits never change status and will not trigger differentiated instructions
5-5 Expansion Instructions
The C200HS has more instructions that require function codes (121) than function codes (100), so some instructions do not have fixed function codes. These instructions, called expansion instructions, are listed in the following table. Default function codes are given for the instructions that have them.
An expansion instruction can be assigned one of 18 function codes using the
Programming Console’s Expansion Instruction Function Code Assignments operation. The 18 function codes are: 17, 18, 19, 47, 48, 60 to 69, 87, 88, and 89.
Refer to 7-1-14 Expansion Instruction Function Code Assignments for details on assigning function codes.
120
Expansion Instructions
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
88
89
---
---
---
66
67
68
69
87
48
60
61
62
63
64
65
17
18
19
47
Code Mnemonic Name
(@)ASFT ASYNCHRONOUS SHIFT REGISTER
(@)SCAN CYCLE TIME
(@)MCMP MULTI-WORD COMPARE
(@)LMSG 32-CHARACTER MESSAGE
(@)TERM TERMINAL MODE
CMPL DOUBLE COMPARE
(@)MPRF GROUP-2 HIGH-DENSITY I/O REFRESH
(@)XFRB TRANSFER BITS
(@)LINE COLUMN TO LINE
(@)COLM LINE TO COLUMN
(@)SEC HOURS TO SECONDS
(@)HMS SECONDS TO HOURS
(@)BCNT BIT COUNTER
(@)BCMP BLOCK COMPARE
(@)APR
TTIM
ARITHMETIC PROCESS
TOTALIZING TIMER
ZCP
(@)INT
7SEG
AREA RANGE COMPARE
INTERRUPT CONTROL
7-SEGMENT DISPLAY OUTPUT
(@)ADBL DOUBLE BINARY ADD
AVG AVERAGE VALUE
CPS
CPSL
(@)DBS
SIGNED BINARY COMPARE
DOUBLE SIGNED BINARY COMPARE
SIGNED BINARY DIVIDE
(@)DBSL DOUBLE SIGNED BINARY DIVIDE
DSW DIGITAL SWITCH INPUT
(@)FCS
FPD
(@)HEX
HKY
(@)MAX
FCS CALCULATE
FAILURE POINT DETECT
ASCII-TO-HEXADECIMAL
HEXADECIMAL KEY INPUT
FIND MAXIMUM
(@)MBS SIGNED BINARY MULTIPLY
(@)MBSL DOUBLE SIGNED BINARY MULTIPLY
(@)MIN FIND MINIMUM
MTR
(@)NEG
MATRIX INPUT
2’S COMPLEMENT
(@)NEGL DOUBLE 2’S COMPLEMENT
PID PID CONTROL
(@)RXD RECEIVE
(@)SBBL DOUBLE BINARY SUBTRACT
(@)SCL SCALING
(@)SRCH DATA SEARCH
(@)SUM SUM CALCULATE
(@)TKY
(@)TXD
TEN KEY INPUT
TRANSMIT
(@)XDMR EXPANSION DM READ
ZCPL DOUBLE AREA RANGE COMPARE
Section 5-5
229
230
234
313
202
283
285
195
308
233
178
179
231
232
304
176
262
301
225
235
203
242
297
227
198
289
237
311
299
290
177
184
283
174
239
144
282
168
200
201
183
Page
157
276
169
279
280
172
121
Coding Right-hand Instructions Section 5-6
5-6 Coding Right-hand Instructions
Writing mnemonic code for ladder instructions is described in Section 4 Writing
and Inputting the Program. Converting the information in the ladder diagram symbol for all other instructions follows the same pattern, as described below, and is not specified for each instruction individually.
The first word of any instruction defines the instruction and provides any definers. If the instruction requires only a signal bit operand with no definer, the bit operand is also placed on the same line as the mnemonic. All other operands are placed on lines after the instruction line, one operand per line and in the same order as they appear in the ladder symbol for the instruction.
The address and instruction columns of the mnemonic code table are filled in for the instruction word only. For all other lines, the left two columns are left blank. If the instruction requires no definer or bit operand, the data column is left blank for first line. It is a good idea to cross through any blank data column spaces (for all instruction words that do not require data) so that the data column can be quickly scanned to see if any addresses have been left out.
If an IR or SR address is used in the data column, the left side of the column is left blank. If any other data area is used, the data area abbreviation is placed on the left side and the address is place on the right side. If a constant to be input, the number symbol (#) is placed on the left side of the data column and the number to be input is placed on the right side. Any numbers input as definers in the instruction word do not require the number symbol on the right side. TC bits, once defined as a timer or counter, take a TIM (timer) or CNT (counter) prefix.
When coding an instruction that has a function code, be sure to write in the function code, which will be necessary when inputting the instruction via the Programming Console. Also be sure to designate the differentiated instruction with the @ symbol.
122
Coding Right-hand Instructions
00000
00002
00100 00200
01001 01002 LR 6300
00005
TIM 000
HR 0015
00001
Section 5-6
22500
The following diagram and corresponding mnemonic code illustrates the points described above.
DIFU(13) 22500
BCNT(67)
#0001
004
HR 00
TIM 000
#0150
MOV(21)
HR 00
LR 00
00500
Address Instruction Data
00000 LD
00001 AND
00000
00001
00002 OR
00003 DIFU(13)
00004 LD
00005 AND NOT
00006 LD
00007 AND NOT
00008 AND NOT LR
00009 OR LD
00010 AND
00011 BCNT(67)
#
00012 LD
00013 TIM
HR
00002
22500
00100
00200
01001
01002
6300
––
22500
––
0001
004
00
00005
00014
00015
00016
00017
LD
MOV(21)
LD
OUT NOT
#
TIM
HR
LR
HR
000
0150
000
––
00
00
0015
00500
123
Coding Right-hand Instructions Section 5-6
Multiple Instruction Lines
00000 00001
00002
00100 00200
01001 01002 LR 6300
HR 0015
22500
If a right-hand instruction requires multiple instruction lines (such as KEEP(11)), all of the lines for the instruction are entered before the right-hand instruction.
Each of the lines for the instruction is coded, starting with LD or LD NOT, to form
‘logic blocks’ that are combined by the right-hand instruction. An example of this for SFT(10) is shown below.
I
P
R
SFT(10)
HR 00
HR 00
00500
Address Instruction Data
00000 LD 00000
00001 AND 00001
00002 LD
00003 LD
00004 AND NOT
00005 LD
00002
00100
00200
01001
00006 AND NOT
00007 AND NOT LR
00008 OR LD
00009 AND
00010 SFT(10)
00011 LD
00012 OUT NOT
HR
HR
HR
01002
6300
––
22500
––
00
00
0015
00500
END(01) When you have finished coding the program, make sure you have placed
END(01) at the last address.
124
Instruction Set Lists Section 5-7
5-7 Instruction Set Lists
This section provides tables of the instructions available in the C200HS. The first table can be used to find instructions by function code. The second table can be used to find instruction by mnemonic. In both tables, the @ symbol indicates instructions with differentiated variations.
Note Refer to 5-5 Expansion Instructions for a list of the expansion instructions.
5-7-1 Function Codes
The following table lists the instructions that have fixed function codes. Each instruction is listed by mnemonic and by instruction name. Use the numbers in the leftmost column as the left digit and the number in the column heading as the right digit of the function code.
Left
0
1
2
3
4
5
6
7
8
9
0
NOP
NO
OPERATION
SFT
SHIFT
REGISTER
CMP
COMPARE
(@) ADD
BCD ADD
(@) STC
SET CARRY
(@) ADB
BINARY ADD
CMPL
DOUBLE
COMPARE
(@) XFER
BLOCK
TRANSFER
(@) DIST
SINGLE
WORD
DISTRIBUTE
(@) SEND
NETWORK
SEND
END
END
KEEP
KEEP
1
(@) MOV
MOVE
(@) SUB
BCD
SUBTRACT
(@) CLC
CLEAR
CARRY
(@) SBB
BINARY
SUBTRACT
(@) MPRF
TRANSFER
BITS
(@) BSET
BLOCK SET
(@) COLL
DATA
COLLECT
(@) SBS
SUBROU-
TINE
ENTRY
2
IL
INTERLOCK
CNTR
REVERS-
IBLE
COUNTER
(@) MVN
MOVE NOT
(@) MUL
BCD
MULTIPLY
---
(@) MLB
BINARY
MULTIPLY
(@) XFRB
TRANSFER
BITS
(@) ROOT
SQUARE
ROOT
(@) MOVB
MOVE BIT
SBN
SUBROU-
TINE
DEFINE
3
ILC
INTERLOCK
CLEAR
DIFU
DIFFEREN-
TIATE UP
(@) BIN
BCD TO
BINARY
(@) DIV
BCD
DIVIDE
---
(@) DVB
BINARY
DIVIDE
(@) LINE
COLUMN TO
LINE
(@) XCHG
DATA
EXCHANGE
(@) MOVD
MOVE DIGIT
RET
SUBROU-
TINE
RETURN
JMP
JUMP
4
Right digit
5
JME
JUMP END
DIFD
DIFFEREN-
TIATE DOWN
(@) BCD
BINARY TO
BCD
(@) ANDW
LOGICAL
AND
---
(@) ADDL
DOUBLE
BCD ADD
(@) COLM
LINE TO
COLUMN
(@) SLD
ONE DIGIT
SHIFT LEFT
(@) SFTR
REVERS-
IBLE SHIFT
REGISTER
(@) WDT
WATCHDOG
TIMER
REFRESH
TIMH
HIGH-
SPEED
TIMER
(@) ASL
SHIFT LEFT
(@) ORW
LOGICAL OR
TRSM
TRACE
MEMORY
SAMPLE
(@) SUBL
DOUBLE
BCD
SUBTRACT
(@) SEC
HOURS-TO-
SECONDS
(@) SRD
ONE DIGIT
SHIFT
RIGHT
(@) TCMP
TABLE
COMPARE
---
6
(@) FAL
FAILURE
ALARM AND
RESET
(@) WSFT
WORD
SHIFT
(@) ASR
SHIFT
RIGHT
(@) XORW
EXCLUSIVE
OR
(@) MSG
MESSAGE
DISPLAY
(@) MULL
DOUBLE
BCD
MULTIPLY
(@) HMS
SECONDS-
TO-HOURS
(@) MLPX
4-TO-16
DECODER
(@) ASC
ASCII
CONVERT
---
7
FALS
SEVERE
FAILURE
ALARM
(@) ASFT
ASYNCHRO-
NOUS SHIFT
REGISTER
(@) ROL
ROTATE
LEFT
(@) XNRW
EXCLUSIVE
NOR
(@) LMSG
LONG MES-
SAGE
(@) DIVL
DOUBLE
BCD
DIVIDE
(@) BCNT
BIT
COUNTER
(@) DMPX
16-TO-4
ENCODER
TTIM
TOTALIZING
COUNTER
(@) IORF
I/O
REFRESH
8
STEP
STEP
DEFINE
(@) SCAN
CYCLE TIME
(@) ROR
ROTATE
RIGHT
(@) INC
INCREMENT
(@) TERM
TERMINAL
MODE
(@) BINL
DOUBLE
BCD-TO-
DOUBLE
BINARY
(@) BCMP
BLOCK
COMPARE
(@) SDEC
7-SEGMENT
DECODER
ZCP
AREA
RANGE
COMPARE
(@) RECV
NETWORK
RECEIVE
9
SNXT
STEP START
(@) MCMP
MULTI-
WORD
COMPARE
(@) COM
COMPLE-
MENT
(@) DEC
DECRE-
MENT
---
(@) BCDL
DOUBLE
BINARY-TO-
DOUBLE
BCD
(@) APR
ARITHMETIC
PROCESS
(@) FDIV
FLOATING
POINT
DIVIDE
(@) INT
INTERRUPT
CONTROL
(@) MCRO
MACRO
5-7-2 Alphabetic List by Mnemonic
Mnemonic
7SEG
ADB (@)
ADBL (@)
ADD (@)
ADDL (@)
AND
AND LD
AND NOT
ANDW (@)
APR (@)
ASC (@)
ASFT(@)
Code Words
––
50
––
4
4
4
30
54
None
None
4
4
1
1
None
34
69
86
17
4
4
1
4
4
Name
7-SEGMENT DISPLAY OUTPUT
BINARY ADD
DOUBLE BINARY ADD
BCD ADD
DOUBLE BCD ADD
AND
AND LOAD
AND NOT
LOGICAL AND
ARITHMETIC PROCESS
ASCII CONVERT
ASYNCHRONOUS SHIFT REGISTER
301
219
225
205
206
129
130
129
250
239
194
157
Page
125
Instruction Set Lists
CNT
CNTR
COLL (@)
COLM(@)
COM (@)
CPS
CPSL
DBS (@)
DBSL (@)
DEC (@)
DIFD
DIFU
DIST (@)
DIV (@)
DIVL (@)
DMPX (@)
DSW
Mnemonic
ASL (@)
ASR (@)
AVG (@)
BCD (@)
BCDL (@)
BCMP (@)
BCNT (@)
BIN (@)
BINL (@)
BSET (@)
CLC (@)
CMP
CMPL
DVB (@)
END
FAL (@)
FALS
FCS (@)
FDIV (@)
FPD
HEX (@)
HKY
HMS (@)
IL
ILC
INC (@)
INT (@)
IORF (@)
JME
JMP
KEEP
LD
33
57
77
––
39
14
13
80
29
––
––
––
––
None
12
81
64
71
41
20
60
68
67
23
58
––
24
59
Code
25
26
03
38
89
97
––
––
66
02
––
79
––
53
01
06
07
05
04
11
None
Name
ARITHMETIC SHIFT LEFT
ARITHMETIC SHIFT RIGHT
AVERAGE VALUE
BINARY TO BCD
DOUBLE BINARY-TO-DOUBLE BCD
BLOCK COMPARE
BIT COUNTER
BCD-TO-BINARY
DOUBLE BCD-TO-DOUBLE BINARY
BLOCK SET
CLEAR CARRY
COMPARE
DOUBLE COMPARE
COUNTER
REVERSIBLE COUNTER
DATA COLLECT
LINE TO COLUMN
COMPLEMENT
SIGNED BINARY COMPARE
DOUBLE SIGNED BINARY COMPARE
SIGNED BINARY DIVIDE
DOUBLE SIGNED BINARY DIVIDE
BCD DECREMENT
DIFFERENTIATE DOWN
DIFFERENTIATE UP
SINGLE WORD DISTRIBUTE
BCD DIVIDE
DOUBLE BCD DIVIDE
16-TO-4 ENCODER
DIGITAL SWITCH
BINARY DIVIDE
END
FAILURE ALARM AND RESET
SEVERE FAILURE ALARM
FCS CALCULATE
FLOATING POINT DIVIDE
FAILURE POINT DETECT
ASCII-TO-HEXADECIMAL
HEXADECIMAL KEY INPUT
SECONDS TO HOURS
INTERLOCK
INTERLOCK CLEAR
INCREMENT
INTERRUPT CONTROL
I/O REFRESH
JUMP END
JUMP
KEEP
LOAD
4
4
4
4
2
4
2
2
4
4
2
4
4
4
4
2
3
3
4
4
1
3
3
4
4
4
3
3
2
2
Words
4
3
1
2
4
1
4
4
2
1
2
2
4
4
4
2
2
4
1
126
Section 5-7
212
213
188
304
224
138
275
275
249
178
179
231
232
204
131
131
162
160
205
170
172
145
148
164
201
154
154
235
181
182
174
283
180
181
135
204
262
281
137
137
133
129
283
214
285
195
308
184
135
Page
Instruction Set Lists
MOVD (@)
MPRF (@)
MSG (@)
MTR
MUL (@)
MULL (@)
MVN (@)
NEG (@)
NEGL (@)
NOP
OR
OR LD
OR NOT
ORW (@)
OUT
OUT NOT
PID (@)
Mnemonic
LD NOT
LINE (@)
LMSG (@)
MAX (@)
MBS (@)
MBSL (@)
MCMP (@)
MCRO (@)
MIN (@)
MLB (@)
MLPX (@)
MOV (@)
MOVB (@)
RECV (@)
RET
ROL (@)
ROOT (@)
ROR (@)
RSET
RXD(@)
SBB (@)
SBBL (@)
SBN
SBS (@)
SCAN (@)
SCL (@)
SDEC (@)
SEC (@)
SEND (@)
SET
SFT
SFTR (@)
00
None
None
None
35
None
None
––
32
56
22
––
––
83
61
46
––
52
76
21
82
––
19
99
––
47
––
––
Code
None
63
18
––
78
65
51
––
92
91
98
93
27
72
28
None
––
90
None
10
84
2
4
4
2
1
1
1
1
3
4
4
4
4
2
4
4
4
3
4
4
4
4
4
4
4
4
4
4
1
4
Words
4
4
4
4
2
2
4
4
3
4
4
2
2
2
4
2
3
4
1
Name
LOAD NOT
COLUMN TO LINE
32-CHARACTER MESSAGE
FIND MAXIMUM
SIGNED BINARY MULTIPLY
DOUBLE SIGNED BINARY MULTIPLY
MULTI-WORD COMPARE
MACRO
FIND MINIMUM
BINARY MULTIPLY
4-TO-16 DECODER
MOVE
MOVE BIT
MOVE DIGIT
GROUP-2 HIGH-DENSITY I/O REFRESH
MESSAGE
MATRIX INPUT
BCD MULTIPLY
DOUBLE BCD MULTIPLY
MOVE NOT
2’S COMPLEMENT
DOUBLE 2’S COMPLEMENT
NO OPERATION
OR
OR LOAD
OR NOT
LOGICAL OR
OUTPUT
OUTPUT NOT
PID CONTROL
NETWORK RECEIVE (CPU31-E/33-E only)
SUBROUTINE RETURN
ROTATE LEFT
SQUARE ROOT
ROTATE RIGHT
RESET
RECEIVE
BINARY SUBTRACT
DOUBLE BINARY SUBTRACT
SUBROUTINE DEFINE
SUBROUTINE ENTRY
CYCLE TIME
SCALING
7-SEGMENT DECODER
HOURS TO SECONDS
NETWORK SEND (CPU31-E/33-E only)
SET
SHIFT REGISTER
REVERSIBLE SHIFT REGISTER
Section 5-7
251
130
130
242
293
259
155
217
211
212
159
202
203
138
129
130
129
224
185
159
166
167
282
278
313
129
200
279
233
229
230
169
260
234
276
198
191
183
291
133
150
152
155
133
297
221
227
259
257
Page
127
Instruction Set Lists
TKY (@)
TRSM
TTIM
TXD (@)
WDT (@)
WSFT (@)
XCHG (@)
XDMR (@)
XFER (@)
XFRB (@)
XNRW (@)
XORW (@)
ZCP
ZCPL
Mnemonic
SLD (@)
SNXT
SRCH (@)
SRD (@)
STC (@)
STEP
SUB (@)
SUBL (@)
SUM (@)
TCMP (@)
TERM (@)
TIM
TIMH
94
16
73
––
70
––
45
87
––
62
37
36
88
––
08
31
55
––
85
48
None
15
––
75
40
Code
74
09
3
4
2
3
4
4
4
4
1
4
4
4
4
4
2
3
4
4
4
4
2
4
4
3
1
3
2
Words Name
ONE DIGIT SHIFT LEFT
STEP START
DATA SEARCH
ONE DIGIT SHIFT RIGHT
SET CARRY
STEP DEFINE
BCD SUBTRACT
DOUBLE BCD SUBTRACT
SUM CALCULATION
TABLE COMPARE
TERMINAL MODE
TIMER
HIGH-SPEED TIMER
TEN KEY INPUT
TRACE MEMORY SAMPLE
TOTALIZING TIMER
TRANSMIT
WATCHDOG TIMER REFRESH
WORD SHIFT
DATA EXCHANGE
EXPANSION DM READ
BLOCK TRANSFER
TRANSFER BITS
EXCLUSIVE NOR
EXCLUSIVE OR
AREA RANGE COMPARE
DOUBLE AREA RANGE COMPARE
Section 5-7
175
280
139
143
311
277
144
299
156
266
289
156
205
266
207
209
237
168
253
252
176
177
281
157
162
290
161
Page
128
Ladder Diagram Instructions Section 5-8
5-8 Ladder Diagram Instructions
Ladder Diagram instructions include Ladder instructions and Logic Block instructions and correspond to the conditions on the ladder diagram. Logic block instructions are used to relate more complex parts.
5-8-1 LOAD, LOAD NOT, AND, AND NOT, OR, and OR NOT
Ladder Symbols Operand Data Areas
LOAD – LD
B B: Bit
IR, SR, AR, HR, TC, LR, TR
LOAD NOT – LD NOT
AND – AND
AND NOT – AND NOT
OR – OR B
B
B
B
B: Bit
IR, SR, AR, HR, TC, LR
B: Bit
IR, SR, AR, HR, TC, LR
B: Bit
IR, SR, AR, HR, TC, LR
B: Bit
IR, SR, AR, HR, TC, LR
OR NOT – OR NOT B
B: Bit
IR, SR, AR, HR, TC, LR
Limitations
Description
Flags
There is no limit to the number of any of these instructions, or restrictions in the order in which they must be used, as long as the memory capacity of the PC is not exceeded.
These six basic instructions correspond to the conditions on a ladder diagram.
As described in Section 4 Writing and Inputting the Program, the status of the bits assigned to each instruction determines the execution conditions for all other instructions. Each of these instructions and each bit address can be used as many times as required. Each can be used in as many of these instructions as required.
The status of the bit operand (B) assigned to LD or LD NOT determines the first execution condition. AND takes the logical AND between the execution condition and the status of its bit operand; AND NOT, the logical AND between the execution condition and the inverse of the status of its bit operand. OR takes the logical OR between the execution condition and the status of its bit operand; OR
NOT, the logical OR between the execution condition and the inverse of the status of its bit operand. The ladder symbol for loading TR bits is different from that shown above. Refer to 4-4-3 Ladder Instructions for details.
There are no flags affected by these instructions.
129
Bit Control Instructions
5-8-2 AND LOAD and OR LOAD
AND LOAD – AND LD
Ladder Symbol
00000
00001
00002
00003
Section 5-9
OR LOAD – OR LD
Ladder Symbol
00000
00002
00001
00003
Description When instructions are combined into blocks that cannot be logically combined using only OR and AND operations, AND LD and OR LD are used. Whereas
AND and OR operations logically combine a bit status and an execution condition, AND LD and OR LD logically combine two execution conditions, the current one and the last unused one.
In order to draw ladder diagrams, it is not necessary to use AND LD and OR LD instructions, nor are they necessary when inputting ladder diagrams directly, as is possible from LSS. They are required, however, to convert the program to and input it in mnemonic form. The procedures for these, limitations for different procedures, and examples are provided in 4-7 Inputting, Modifying, and Checking
the Program.
In order to reduce the number of programming instructions required, a basic understanding of logic block instructions is required. For an introduction to logic blocks, refer to 4-4-6 Logic Block Instructions.
There are no flags affected by these instructions.
Flags
5-9 Bit Control Instructions
There are five instructions that can be used generally to control individual bit status. These are OUT, OUT NOT, DIFU(13), DIFD(14), and KEEP(11). These instructions are used to turn bits ON and OFF in different ways.
5-9-1 OUTPUT and OUTPUT NOT – OUT and OUT NOT
OUTPUT – OUT
Ladder Symbol Operand Data Areas
B
B: Bit
IR, SR, AR, HR, TC, LR, TR
OUTPUT NOT – OUT NOT
Ladder Symbol
B
Operand Data Areas
B: Bit
IR, SR, AR, HR, TC, LR
Limitations
Description
Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.
OUT and OUT NOT are used to control the status of the designated bit according to the execution condition.
130
Bit Control Instructions Section 5-9
OUT turns ON the designated bit for an ON execution condition, and turns OFF the designated bit for an OFF execution condition. With a TR bit, OUT appears at a branching point rather than at the end of an instruction line. Refer to 4-7-7
Branching Instruction Lines for details.
OUT NOT turns ON the designated bit for a OFF execution condition, and turns
OFF the designated bit for an ON execution condition.
OUT and OUT NOT can be used to control execution by turning ON and OFF bits that are assigned to conditions on the ladder diagram, thus determining execution conditions for other instructions. This is particularly helpful and allows a complex set of conditions to be used to control the status of a single work bit, and then that work bit can be used to control other instructions.
The length of time that a bit is ON or OFF can be controlled by combining the
OUT or OUT NOT with TIM. Refer to Examples under 5-14-1 TIMER – TIM for details.
Flags There are no flags affected by these instructions.
5-9-2 DIFFERENTIATE UP and DOWN – DIFU(13) and DIFD(14)
Ladder Symbols
DIFU(13) B
Operand Data Areas
B: Bit
IR, AR, HR, LR
Limitations
Description
Flags
DIFD(14) B
B: Bit
IR, AR, HR, LR
Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.
DIFU(13) and DIFD(14) are used to turn the designated bit ON for one cycle only.
Whenever executed, DIFU(13) compares its current execution with the previous execution condition. If the previous execution condition was OFF and the current one is ON, DIFU(13) will turn ON the designated bit. If the previous execution condition was ON and the current execution condition is either ON or OFF,
DIFU(13) will either turn the designated bit OFF or leave it OFF (i.e., if the designated bit is already OFF). The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below).
Whenever executed, DIFD(14) compares its current execution with the previous execution condition. If the previous execution condition was ON and the current one is OFF, DIFD(14) will turn ON the designated bit. If the previous execution condition was OFF and the current execution condition is either ON or OFF,
DIFD(14) will either turn the designated bit OFF or leave it OFF. The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below).
These instructions are used when differentiated instructions (i.e., those prefixed with an @) are not available and single-cycle execution of a particular instruction is desired. They can also be used with non-differentiated forms of instructions that have differentiated forms when their use will simplify programming. Examples of these are shown below.
There are no flags affected by these instructions.
131
Bit Control Instructions
Precautions
Example 1:
When There is No
Differentiated Instruction
Section 5-9
DIFU(13) and DIFD(14) operation can be uncertain when the instructions are programmed between IL and ILC, between JMP and JME, or in subroutines. Refer to 5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03), 5-11
JUMP and JUMP END – JMP(04) and JME(05), and 5-23 Subroutines and Inter-
rupt Control for details.
In diagram A, below, whenever CMP(20) is executed with an ON execution condition it will compare the contents of the two operand words (HR 10 and DM
0000) and set the arithmetic flags (GR, EQ, and LE) accordingly. If the execution condition remains ON, flag status may be changed each cycle if the content of one or both operands change. Diagram B, however, is an example of how
DIFU(13) can be used to ensure that CMP(20) is executed only once each time the desired execution condition goes ON.
00000
00000
22500
Diagram A
Diagram B
CMP(20)
HR 10
DM 0000
DIFU(13) 22500
CMP(20)
HR 10
DM 0000
Address Instruction
00000 LD
00001 CMP(20)
HR
DM
Operands
00000
10
0000
Address Instruction
00000 LD
00001 DIFU(13)
00002 LD
00003 CMP(20)
HR
DM
Operands
00000
22500
22500
10
0000
Example 2:
Simplifying Programming
Although a differentiated form of MOV(21) is available, the following diagram would be very complicated to draw using it because only one of the conditions determining the execution condition for MOV(21) requires differentiated treatment.
00000
22500
00001 00002 00003
00004 00005
DIFU(13) 22500
MOV(21)
HR 10
DM 0000
Address Instruction
00000 LD
00001 DIFU(13)
00002 LD
00003 LD
00004 AND NOT
00005 AND NOT
00006 OR LD
00007 LD
00008 AND NOT
00009 OR LD
00010 MOV(21)
HR
DM
Operands
00000
22500
22500
00001
00002
00003
---
00004
00005
---
10
0000
132
Bit Control Instructions
5-9-3 SET and RESET – SET and RSET
Ladder Symbols
Description
Precautions
Flags
Examples
00000
SET B
Section 5-9
Operand Data Areas
B: Bit
IR, SR, AR, HR, LR
RSET B
B: Bit
IR, SR, AR, HR, LR
SET turns the operand bit ON when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. RSET turns the operand bit OFF when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF.
The operation of SET differs from that of OUT because the OUT instruction turns the operand bit OFF when its execution condition is OFF. Likewise, RSET differs from OUT NOT because OUT NOT turns the operand bit ON when its execution condition is OFF.
The status of operand bits for SET and RSET programmed between IL(02) and
ILC(03) or JMP(04) and JME(05) will not change when the interlock or jump condition is met (i.e., when IL(02) or JMP(04) is executed with an OFF execution condition).
There are no flags affected by these instructions.
The following examples demonstrate the difference between OUT and SET/
RSET. In the first example (Diagram A), IR 10000 will be turned ON or OFF whenever IR 00000 goes ON or OFF.
In the second example (Diagram B), IR 10000 will be turned ON when IR 00001 goes ON and will remain ON (even if IR 00001 goes OFF) until IR 00002 goes
ON.
Diagram A
10000
Address Instruction
00000 LD
00001 OUT
Operands
00000
10000
00001
00002
SET 10000
RSET 10000
Diagram B
5-9-4 KEEP – KEEP(11)
Ladder Symbol
S
R
KEEP(11)
B
Address Instruction
00000 LD
00001 SET
00002 LD
00003 RSET
Operands
00001
10000
00002
10000
Operand Data Areas
B: Bit
IR, AR, HR, LR
Limitations Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.
133
Bit Control Instructions
Description
Section 5-9
KEEP(11) is used to maintain the status of the designated bit based on two execution conditions. These execution conditions are labeled S and R. S is the set input; R, the reset input. KEEP(11) operates like a latching relay that is set by S and reset by R.
When S turns ON, the designated bit will go ON and stay ON until reset, regardless of whether S stays ON or goes OFF. When R turns ON, the designated bit will go OFF and stay OFF until reset, regardless of whether R stays ON or goes
OFF. The relationship between execution conditions and KEEP(11) bit status is shown below.
S execution condition
R execution condition
00002 00003
00500
Status of B
KEEP(11) operates like the self-maintaining bit described in 4-8-3 Self-maintain-
ing Bits. The following two diagrams would function identically, though the one using KEEP(11) requires one less instruction to program and would maintain status even in an interlocked program section.
00500
Address Instruction
00000 LD
00001 OR
00002 AND NOT
00003 OUT
Operands
00002
00500
00003
00500
00002
00003
S
R
KEEP(11)
B
Address Instruction
00000 LD
00001 LD
00002 KEEP(11)
Operands
00002
00003
00500
Flags
Precautions
There are no flags affected by this instruction.
Exercise caution when using a KEEP reset line that is controlled by an external normally closed device. Never use an input bit in an inverse condition on the reset (R) for KEEP(11) when the input device uses an AC power supply. The delay in shutting down the PC’s DC power supply (relative to the AC power supply to the input device) can cause the designated bit of KEEP(11) to be reset. This situation is shown below.
A
Input Unit
NEVER
A
S
R
KEEP(11)
B
Bits used in KEEP are not reset in interlocks. Refer to the 5-10 INTERLOCK –
and INTERLOCK CLEAR IL(02) and ILC(03) for details.
134
INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03)
Example
00002
00003
00004
Reset input
00005
Indicates emergency situation
Section 5-10
If a HR bit or an AR bit is used, bit status will be retained even during a power interruption. KEEP(11) can thus be used to program bits that will maintain status after restarting the PC following a power interruption. An example of this that can be used to produce a warning display following a system shutdown for an emergency situation is shown below. Bits 00002, 00003, and 00004 would be turned
ON to indicate some type of error. Bit 00005 would be turned ON to reset the warning display. HR 0000, which is turned ON when any one of the three bits indicates an emergency situation, is used to turn ON the warning indicator through 00500.
S
KEEP(11)
B
R
Address Instruction
00000 LD
00001 OR
00002 OR
00003 LD
00004 KEEP(11)
00005 LD
00006 OUT
HR
HR
Operands
00002
00003
00004
00005
0000
0000
00500
HR 0000
00500
Activates warning display
KEEP(11) can also be combined with TIM to produce delays in turning bits ON and OFF. Refer to 5-14-1 TIMER – TIM for details.
5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03)
Ladder Symbol
IL(02)
Description
Ladder Symbol
ILC(03)
IL(02) is always used in conjunction with ILC(03) to create interlocks. Interlocks are used to enable branching in the same way as can be achieved with TR bits, but treatment of instructions between IL(02) and ILC(03) differs from that with
TR bits when the execution condition for IL(02) is OFF. If the execution condition of IL(02) is ON, the program will be executed as written, with an ON execution condition used to start each instruction line from the point where IL(02) is located through the next ILC(03). Refer to 4-7-7 Branching Instruction Lines for basic descriptions of both methods.
If the execution condition for IL(02) is OFF, the interlocked section between
IL(02) and ILC(03) will be treated as shown in the following table:
Instruction
OUT and OUT NOT
SET and RSET
TIM and TIMH(15)
TTIM(87)
CNT, CNTR(12)
KEEP(11)
DIFU(13) and DIFD(14)
All others
Treatment
Designated bit turned OFF.
Bit status maintained.
Reset.
PV maintained.
PV maintained.
Bit status maintained.
Not executed (see below).
Not executed.
135
INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03)
DIFU(13) and DIFD(14) in
Interlocks
00000
00001
Section 5-10
IL(02) and ILC(03) do not necessarily have to be used in pairs. IL(02) can be used several times in a row, with each IL(02) creating an interlocked section through the next ILC(03). ILC(03) cannot be used unless there is at least one
IL(02) between it and any previous ILC(03).
Changes in the execution condition for a DIFU(13) or DIFD(14) are not recorded if the DIFU(13) or DIFD(14) is in an interlocked section and the execution condition for the IL(02) is OFF. When DIFU(13) or DIFD(14) is execution in an interlocked section immediately after the execution condition for the IL(02) has gone
ON, the execution condition for the DIFU(13) or DIFD(14) will be compared to the execution condition that existed before the interlock became effective (i.e., before the interlock condition for IL(02) went OFF). The ladder diagram and bit status changes for this are shown below. The interlock is in effect while 00000 is
OFF. Notice that 01000 is not turned ON at the point labeled A even though
00001 has turned OFF and then back ON.
A
IL(02)
DIFU(13) 01000
ILC(03)
Address Instruction
00000 LD
00001 IL(02)
00002 LD
00003 DIFU(13)
00004 ILC(03)
Operands
00000
00001
01000
00000
00001
01000
ON
OFF
ON
OFF
ON
OFF
Precautions
Flags
There must be an ILC(03) following any one or more IL(02).
Although as many IL(02) instructions as are necessary can be used with one
ILC(03), ILC(03) instructions cannot be used consecutively without at least one
IL(02) in between, i.e., nesting is not possible. Whenever a ILC(03) is executed, all interlocks between the active ILC(03) and the preceding ILC(03) are cleared.
When more than one IL(02) is used with a single ILC(03), an error message will appear when the program check is performed, but execution will proceed normally.
There are no flags affected by these instructions.
136
JUMP and JUMP END – JMP(04) and JME(05)
Example
00000
00001
00002
00003
00100
00005
00004
Section 5-11
The following diagram shows IL(02) being used twice with one ILC(03).
IL(02)
#0015 001.5 s
IL(02)
CP
R
CNT
001
IR 010
00502
Address Instruction
00000 LD
00001 IL(02)
00002 LD
00003 TIM
00004 LD
00005 IL(02)
00006 LD
00007 AND NOT
00008 CNT
00009 LD
00010 OUT
00011 ILC(03)
#
Operands
00000
00001
511
0015
00002
00003
00004
001
010
00005
00502
ILC(03)
When the execution condition for the first IL(02) is OFF, TIM 511 will be reset to
1.5 s, CNT 001 will not be changed, and 00502 will be turned OFF. When the execution condition for the first IL(02) is ON and the execution condition for the second IL(02) is OFF, TIM 511 will be executed according to the status of 00001,
CNT 001 will not be changed, and 00502 will be turned OFF. When the execution conditions for both the IL(02) are ON, the program will execute as written.
5-11 JUMP and JUMP END – JMP(04) and JME(05)
Ladder Symbols
JMP(04) N
Definer Values
N: Jump number
# (00 to 99)
Limitations
Description
JME(05) N
N: Jump number
# (00 to 99)
Jump numbers 01 through 99 may be used only once in JMP(04) and once in
JME(05), i.e., each can be used to define one jump only. Jump number 00 can be used as many times as desired.
JMP(04) is always used in conjunction with JME(05) to create jumps, i.e., to skip from one point in a ladder diagram to another point. JMP(04) defines the point from which the jump will be made; JME(05) defines the destination of the jump.
When the execution condition for JMP(04) in ON, no jump is made and the program is executed consecutively as written. When the execution condition for
JMP(04) is OFF, a jump is made to the JME(05) with the same jump number and the instruction following JME(05) is executed next.
If the jump number for JMP(04) is between 01 and 99, jumps, when made, will go immediately to JME(05) with the same jump number without executing any instructions in between. The status of timers, counters, bits used in OUT, bits used in OUT NOT, and all other status bits controlled by the instructions between
JMP(04) and JMP(05) will not be changed. Each of these jump numbers can be used to define only one jump. Because all of instructions between JMP(04) and
JME(05) are skipped, jump numbers 01 through 99 can be used to reduce cycle time.
137
Timer and Counter Instructions Section 5-14
DIFU(13) and DIFD(14) in
Jumps
Precautions
Flags
Examples
If the jump number for JMP(04) is 00, the CPU will look for the next JME(05) with a jump number of 00. To do so, it must search through the program, causing a longer cycle time (when the execution condition is OFF) than for other jumps.
The status of timers, counters, bits used in OUT, bits used in OUT NOT, and all other status controlled by the instructions between JMP(04) 00 and JMP(05) 00 will not be changed. jump number 00 can be used as many times as desired. A jump from JMP(04) 00 will always go to the next JME(05) 00 in the program. It is thus possible to use JMP(04) 00 consecutively and match them all with the same
JME(05) 00. It makes no sense, however, to use JME(05) 00 consecutively, because all jumps made to them will end at the first JME(05) 00.
Although DIFU(13) and DIFD(14) are designed to turn ON the designated bit for one cycle, they will not necessarily do so when written between JMP(04) and
JMP (05). Once either DIFU(13) or DIFD(14) has turned ON a bit, it will remain
ON until the next time DIFU(13) or DIFD(14) is executed again. In normal programming, this means the next cycle. In a jump, this means the next time the jump from JMP(04) to JME(05) is not made, i.e., if a bit is turned ON by DIFU(13) or DIFD(14) and then a jump is made in the next cycle so that DIFU(13) or
DIFD(14) are skipped, the designated bit will remain ON until the next time the execution condition for the JMP(04) controlling the jump is ON.
When JMP(04) and JME(05) are not used in pairs, an error message will appear when the program check is performed. Although this message also appears if
JMP(04) 00 and JME(05) 00 are not used in pairs, the program will execute properly as written.
There are no flags affected by these instructions.
Examples of jump programs are provided in 4-7-8 Jumps.
5-12 END – END(01)
Ladder Symbol
END(01)
Description
Flags
END(01) is required as the last instruction in any program. If there are subroutines, END(01) is placed after the last subroutine. No instruction written after
END(01) will be executed. END(01) can be placed anywhere in the program to execute all instructions up to that point, as is sometimes done to debug a program, but it must be removed to execute the remainder of the program.
If there is no END(01) in the program, no instructions will be executed and the error message “NO END INST” will appear.
END(01) turns OFF the ER, CY, GR, EQ, and LE Flags.
5-13 NO OPERATION – NOP(00)
Description NOP(00) is not generally required in programming and there is no ladder symbol for it. When NOP(00) is found in a program, nothing is executed and the program execution moves to the next instruction. When memory is cleared prior to programming, NOP(00) is written at all addresses. NOP(00) can be input through the 00 function code.
Flags There are no flags affected by NOP(00).
5-14 Timer and Counter Instructions
TIM and TIMH are decrementing ON-delay timer instructions which require a TC number and a set value (SV).
CNT is a decrementing counter instruction and CNTR is a reversible counter instruction. Both require a TC number and a SV. Both are also connected to multiple instruction lines which serve as an input signal(s) and a reset.
138
Timer and Counter Instructions Section 5-14
Any one TC number cannot be defined twice, i.e., once it has been used as the definer in any of the timer or counter instructions, it cannot be used again. Once defined, TC numbers can be used as many times as required as operands in instructions other than timer and counter instructions.
TC numbers run from 000 through 511. No prefix is required when using a TC number as a definer in a timer or counter instruction. Once defined as a timer, a
TC number can be prefixed with TIM for use as an operand in certain instructions. The TIM prefix is used regardless of the timer instruction that was used to define the timer. Once defined as a counter, a TC number can be prefixed with
CNT for use as an operand in certain instructions. The CNT is also used regardless of the counter instruction that was used to define the counter.
TC numbers can be designated as operands that require either bit or word data.
When designated as an operand that requires bit data, the TC number accesses a bit that functions as a ‘Completion Flag’ that indicates when the time/count has expired, i.e., the bit, which is normally OFF, will turn ON when the designated SV has expired. When designated as an operand that requires word data, the TC number accesses a memory location that holds the present value (PV) of the timer or counter. The PV of a timer or counter can thus be used as an operand in
CMP(20), or any other instruction for which the TC area is allowed. This is done by designating the TC number used to define that timer or counter to access the memory location that holds the PV.
Note that “TIM 000” is used to designate the TIMER instruction defined with TC number 000, to designate the Completion Flag for this timer, and to designate the PV of this timer. The meaning of the term in context should be clear, i.e., the first is always an instruction, the second is always a bit operand, and the third is always a word operand. The same is true of all other TC numbers prefixed with
TIM or CNT.
An SV can be input as a constant or as a word address in a data area. If an IR area word assigned to an Input Unit is designated as the word address, the Input
Unit can be wired so that the SV can be set externally through thumbwheel switches or similar devices. Timers and counters wired in this way can only be set externally during RUN or MONITOR mode. All SVs, including those set externally, must be in BCD.
5-14-1 TIMER – TIM
Ladder Symbol
Definer Values
N: TC number
# (000 through 511)
TIM N
SV Operand Data Areas
SV: Set value (word, BCD)
IR, AR, DM, HR, LR, #
Limitations
Description
SV is between 000.0 and 999.9. The decimal point is not entered.
Each TC number can be used as the definer in only one TIMER or COUNTER instruction.
TC 000 through TC 015 should not be used in TIM if they are required for
TIMH(15). Refer to 5-14-2 HIGH-SPEED TIMER – TIMH(15) for details.
A timer is activated when its execution condition goes ON and is reset (to SV) when the execution condition goes OFF. Once activated, TIM measures in units of 0.1 second from the SV.
139
Timer and Counter Instructions Section 5-14
If the execution condition remains ON long enough for TIM to time down to zero, the Completion Flag for the TC number used will turn ON and will remain ON until TIM is reset (i.e., until its execution condition is goes OFF).
The following figure illustrates the relationship between the execution condition for TIM and the Completion Flag assigned to it.
Execution condition
Completion Flag
ON
OFF
ON
OFF
SV SV
Precautions
Flags
Examples
Example 1:
Basic Application
00000
TIM 000
00001
TIM 001
Timers in interlocked program sections are reset when the execution condition for IL(02) is OFF. Power interruptions also reset timers. If a timer that is not reset under these conditions is desired, SR area clock pulse bits can be counted to produce timers using CNT. Refer to 5-14-4 COUNTER – CNT for details.
Program execution will continue even if a non-BCD SV is used, but timing will not be accurate.
The SV of the timers can be set in the range #0000 to #9999 (BCD). If the SV for a timer is set to #0000 or #0001, it will operate in the following way. If the SV is set to #0000, when the timer input goes from OFF to ON, the Completion Flag will turn ON. If the SV is set to #0001, because the timer accuracy is 0 to –0.1 s, the actual time will be a value between 0 and 0.1 s, and the Completion Flag may turn ON as soon as the timer input goes from OFF to ON. With other values also, allow for a timer accuracy of 0 to –0.1 s when setting the SV.
ER: SV is not in BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
All of the following examples use OUT in diagrams that would generally be used to control output bits in the IR area. There is no reason, however, why these diagrams cannot be modified to control execution of other instructions.
The following example shows two timers, one set with a constant and one set via input word 005. Here, 00200 will be turned ON after 00000 goes ON and stays
ON for at least 15 seconds. When 00000 goes OFF, the timer will be reset and
00200 will be turned OFF. When 00001 goes ON, TIM 001 is started from the SV provided through IR word 005. Bit 00201 is also turned ON when 00001 goes
ON. When the SV in 005 has expired, 00201 is turned OFF. This bit will also be turned OFF when TIM 001 is reset, regardless of whether or not SV has expired.
TIM 000
#0150 015.0 s
00200
TIM 001
IR 005 IR 005
00201
Address Instruction
00000 LD
00001 TIM
00002 LD
00003 OUT
00004 LD
00005 TIM
00006 AND NOT
00007 OUT
#
Operands
TIM
TIM
00000
000
0150
000
00200
00001
001
005
001
00200
140
Timer and Counter Instructions
Example 2:
Extended Timers
Section 5-14
There are two ways to achieve timers that operate for longer than 999.9 seconds. One method is to program consecutive timers, with the Completion Flag of each timer used to activate the next timer. A simple example with two 900.0-second (15-minute) timers combined to functionally form a 30-minute timer.
00000
TIM 001
TIM 002
TIM 001
#9000 900.0 s
TIM 002
#9000 900.0 s
00200
Address Instruction
00000 LD
00001 TIM
00002 LD
00003 TIM
00004 LD
00005 OUT
#
TIM
#
Operands
TIM
00000
001
9000
001
002
9000
002
00200
Example 3:
ON/OFF Delays
In this example, 00200 will be turned ON 30 minutes after 00000 goes ON.
TIM can also be combined with CNT or CNT can be used to count SR area clock pulse bits to produce longer timers. An example is provided in 5-14-4 COUNTER
– CNT.
TIM can be combined with KEEP(11) to delay turning a bit ON and OFF in reference to a desired execution condition. KEEP(11) is described in 5-9-4 KEEP –
KEEP(11).
To create delays, the Completion Flags for two TIM are used to determine the execution conditions for setting and reset the bit designated for KEEP(11). The bit whose manipulation is to be delayed is used in KEEP(11). Turning ON and
OFF the bit designated for KEEP(11) is thus delayed by the SV for the two TIM.
The two SV could naturally be the same if desired.
In the following example, 00500 would be turned ON 5.0 seconds after 00000 goes ON and then turned OFF 3.0 seconds after 00000 goes OFF. It is necessary to use both 00500 and 00000 to determine the execution condition for TIM
002; 00000 in an inverse condition is necessary to reset TIM 002 when 00000 goes ON and 00500 is necessary to activate TIM 002 (when 00000 is OFF).
00000
00500 00000
TIM 001
TIM 002
TIM 001
#0050 005.0 s
Address Instruction
00000 LD
00001 TIM
TIM 002
#0030
003.0 s
S
R
KEEP(11)
00500
00002
00003
00004
LD
AND NOT
TIM
00005 LD
00006 LD
00007 KEEP(11)
#
#
TIM
TIM
Operands
00000
001
0050
00500
00000
002
0030
001
002
00500
00000
00500
5.0 s 3.0 s
141
Timer and Counter Instructions
Example 4:
One-Shot Bits
01000 TIM 001
00000
01000
01000 TIM 001
Section 5-14
The length of time that a bit is kept ON or OFF can be controlled by combining
TIM with OUT or OUT NO. The following diagram demonstrates how this is possible. In this example, 00204 would remain ON for 1.5 seconds after 00000 goes
ON regardless of the time 00000 stays ON. This is achieved by using 01000 as a self-maintaining bit activated by 00000 and turning ON 00204 through it. When
TIM 001 comes ON (i.e., when the SV of TIM 001 has expired), 00204 will be turned OFF through TIM 001 (i.e., TIM 001 will turn ON which, as an inverse condition, creates an OFF execution condition for OUT 00204).
01000
TIM 001
#0015 001.5 s
00204
Address Instruction
00000 LD
00001 AND NOT
00002 OR
00003 OUT
00004 LD
00005 TIM
00006 LD
00007 AND NOT
00008 OUT
TIM
#
Operands
TIM
01000
001
00000
01000
01000
001
0015
01000
001
00204
00000
00204
00000
00100
1.5 s
TIM 001
1.5 s
The following one-shot timer may be used to save memory.
TIM 001
#0015 001.5 s
00100
Address Instruction
00000 LD
00001 OR
00002 TIM
00003 AND NOT
00004 OUT
#
Operands
TIM
00000
00100
001
0015
001
00100
142
Timer and Counter Instructions
Example 5:
Flicker Bits
00000 TIM 002
TIM 001
TIM 001
Section 5-14
Bits can be programmed to turn ON and OFF at regular intervals while a designated execution condition is ON by using TIM twice. One TIM functions to turn
ON and OFF a specified bit, i.e., the Completion Flag of this TIM turns the specified bit ON and OFF. The other TIM functions to control the operation of the first
TIM, i.e., when the first TIM’s Completion Flag goes ON, the second TIM is started and when the second TIM’s Completion Flag goes ON, the first TIM is started.
TIM 001
#0010
1.0 s
TIM 002
#0015 1.5 s
00205
Address Instruction
00000 LD
00001 AND
00002 TIM
00003 LD
00004 TIM
00005 LD
00006 OUT
Operands
TIM
#
TIM
#
TIM
00000
002
001
0010
001
002
0015
001
00205
00000
00205
00000 25502
1.0 s 1.5 s 1.0 s 1.5 s
A simpler but less flexible method of creating a flicker bit is to AND one of the SR area clock pulse bits with the execution condition that is to be ON when the flicker bit is operating. Although this method does not use TIM, it is included here for comparison. This method is more limited because the ON and OFF times must be the same and they depend on the clock pulse bits available in the SR area.
In the following example the 1-second clock pulse is used (25502) so that 00206 would be turned ON and OFF every second, i.e., it would be ON for 0.5 seconds and OFF for 0.5 seconds. Precise timing and the initial status of 00206 would depend on the status of the clock pulse when 00000 goes ON.
00206
Address Instruction
00000 LD
00001 LD
00002 OUT
Operands
00000
25502
00206
5-14-2 HIGH-SPEED TIMER – TIMH(15)
Limitations
Ladder Symbol
Definer Values
N: TC number
# (000 through 015 preferred)
TIMH(15) N
SV Operand Data Areas
SV: Set value (word, BCD)
IR, AR, DM, HR, LR, #
SV is between 00.00 and 99.99. (Although 00.00 and 00.01 may be set, 00.00
will disable the timer, i.e., turn ON the Completion Flag immediately, and 00.01 is not reliably cycled.) The decimal point is not entered.
143
Timer and Counter Instructions Section 5-14
Description
Precautions
Flags
Each TC number can be used as the definer in only one TIMER or COUNTER instruction.
If the cycle time is greater than 10 ms, use TC 000 through TC 015.
TIMH(15) operates in the same way as TIM except that TIMH measures in units of 0.01 second.
The cycle time affects TIMH(15) accuracy if TC 016 through TC 511 are used. If the cycle time is greater than 10 ms, use TC 000 through TC 015.
Refer to 5-14-1 TIMER – TIM for operational details and examples. Except for the above, and all aspects of operation are the same.
Timers in interlocked program sections are reset when the execution condition for IL(02) is OFF. Power interruptions also reset timers. If a timer that is not reset under these conditions is desired, SR area clock pulse bits can be counted to produce timers using CNT. Refer to 5-14-4 COUNTER – CNT for details.
Program execution will continue even if a non-BCD SV is used, but timing will not be accurate.
The SV of the timers can be set in the range #0000 to #9999 (BCD). If the SV for a timer is set to #0000 or #0001, it will operate in the following way. If the SV is set to #0000, when the timer input goes from OFF to ON, the Completion Flag will turn ON. There may be a time delay if TC 000 to TC 003 are used. If the SV is set to #0001, because the timer accuracy is 0 to –0.1 s, the actual time will be a value between 0 and 0.1 s, and the Completion Flag may turn ON as soon as the timer input goes from OFF to ON. With other values also, allow for a timer accuracy of
0 to –0.1 s when setting the SV.
ER: SV is not in BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-14-3 TOTALIZING TIMER – TTIM(87)
Ladder Symbol
TTIM(87)
N
SV
RB
Definer Values
N: TC number
# (000 through 511)
Operand Data Areas
SV: Set value (word, BCD)
IR, AR, DM, HR, LR
RB: Reset bit
IR, SR, AR, HR, LR
Limitations
Description
SV is between 0000 and 9999 (000.0 and 999.9 s) and must be in BCD. The decimal point is not entered.
Each TC number can be used as the definer in only one TIMER or COUNTER instruction.
TTIM(87) is used to create a timer that increments the PV every 0.1 s to time between 0.1 and 999.9 s. TTIM(87) increments in units of 0.1 second from zero.
TTIM(87) accuracy is +0.0/–0.1 second. A TTIM(87) timer will time as long as its execute condition is ON until it reaches the SV or until RB turns ON to reset the timer. TIMM(87) timers will time only as long as they are executed every cycle, i.e., they do not time, but maintain the current PV, in interlocked program sections or when they are jumped in the program.
144
Timer and Counter Instructions
Precautions
Flags
Example
00000
Section 5-14
The PVs of totalizing timers in interlocked program sections are maintained when the execution condition for IL(02) is OFF. Unlike timers and high-speed timers, totalizing timers in jumped program sections do not continue timing, but maintain the PV.
Power interruptions will reset timers.
Totalizing timers will not restart after timing out unless the PV is changed to a value below the SV or the reset input is turned ON.
A delay of one cycle is sometimes required for a Completion Flag to be turned
ON after the timer times out.
The SV of the timers can be set in the range #0000 to #9999 (BCD). If the SV for a timer is set to #0000 or #0001, it will operate in the following way. If the SV is set to #0000, when the timer input goes from OFF to ON, the Completion Flag will turn ON. If the SV is set to #0001, because the timer accuracy is 0 to –0.1 s, the actual time will be a value between 0 and 0.1 s, and the Completion Flag may turn ON as soon as the timer input goes from OFF to ON. With other values also, allow for a timer accuracy of 0 to –0.1 s when setting the SV.
ER (SR 25503): Content of
∗
DM word is not BCD when set for BCD.
SV is not BCD.
The following figure illustrates the relationship between the execution conditions for a totalizing timer with a set value of 2 s, its PV, and the Completion Flag.
TTIM(87)
TIM 000
#0020
LR 2100
Address Instruction
00000 LD
00001 TTIM(87)
Operands
00000
TIM
#
LR
000
0020
2100
Timer input
(I: IR 00000)
Reset bit
(RB: LR 2100)
Completion Flag
(TIM 000)
Present value: 0020
0000
5-14-4 COUNTER – CNT
Ladder Symbol
CP
R
CNT N
SV
Definer Values
N: TC number
# (000 through 511)
Operand Data Areas
SV: Set value (word, BCD)
IR, AR, DM, HR, LR, #
145
Timer and Counter Instructions
Limitations
Description
Section 5-14
Each TC number can be used as the definer in only one TIMER or COUNTER instruction.
CNT is used to count down from SV when the execution condition on the count pulse, CP, goes from OFF to ON, i.e., the present value (PV) will be decremented by one whenever CNT is executed with an ON execution condition for
CP and the execution condition was OFF for the last execution. If the execution condition has not changed or has changed from ON to OFF, the PV of CNT will not be changed. The Completion Flag for a counter is turned ON when the PV reaches zero and will remain ON until the counter is reset.
CNT is reset with a reset input, R. When R goes from OFF to ON, the PV is reset to SV. The PV will not be decremented while R is ON. Counting down from SV will begin again when R goes OFF. The PV for CNT will not be reset in interlocked program sections or by power interruptions.
Changes in execution conditions, the Completion Flag, and the PV are illustrated below. PV line height is meant only to indicate changes in the PV.
Execution condition on count pulse (CP)
Execution condition on reset (R)
Completion Flag
ON
OFF
ON
OFF
ON
OFF
SV
PV
SV
SV – 1
SV – 2
0002
0001
0000
Precautions
Flags
Example 1:
Basic Application
00000
00002
CNT 004
Program execution will continue even if a non-BCD SV is used, but the SV will not be correct.
ER: SV is not in BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
In the following example, the PV will be decremented whenever both 00000 and
00001 are ON provided that 00002 is OFF and either 00000 or 00001 was OFF the last time CNT 004 was executed. When 150 pulses have been counted down
(i.e., when PV reaches zero), 00205 will be turned ON.
00001
CP
CNT 004
R
#0150
00205
Address Instruction
00000 LD
00001 AND
00002 LD
00003 CNT
00004 LD
00005 OUT
#
Operands
CNT
00000
00001
00002
0004
0150
004
00205
Here, 00000 can be used to control when CNT is operative and 00001 can be used as the bit whose OFF to ON changes are being counted.
146
Timer and Counter Instructions
00000
00002
25315
00001
CNT 004
Section 5-14
The above CNT can be modified to restart from SV each time power is turned ON to the PC. This is done by using the First Cycle Flag in the SR area (25315) to reset CNT as shown below.
CP
R
CNT 004
#0150
00205
Address Instruction
00000 LD
00001 AND
00002 LD
00003 OR
00004 CNT
00005 LD
00006 OUT
#
Operands
CNT
00000
00001
00002
25315
004
0150
004
00205
Example 2:
Extended Counter
00000 00001
00002
CNT 001
CNT 002
CNT 001
00002
CNT 002
Counters that can count past 9,999 can be programmed by using one CNT to count the number of times another CNT has counted to zero from SV.
In the following example, 00000 is used to control when CNT 001 operates. CNT
001, when 00000 is ON, counts down the number of OFF to ON changes in
00001. CNT 001 is reset by its Completion Flag, i.e., it starts counting again as soon as its PV reaches zero. CNT 002 counts the number of times the Completion Flag for CNT 001 goes ON. Bit 00002 serves as a reset for the entire extended counter, resetting both CNT 001 and CNT 002 when it is OFF. The Completion Flag for CNT 002 is also used to reset CNT 001 to inhibit CNT 001 operation, once SV for CNT 002 has been reached, until the entire extended counter is reset via 00002.
Because in this example the SV for CNT 001 is 100 and the SV for CNT 002 is
200, the Completion Flag for CNT 002 turns ON when 100 x 200 or 20,000 OFF to ON changes have been counted in 00001. This would result in 00203 being turned ON.
CP
R
CP
R
CNT 001
#0100
CNT 002
#0200
Address Instruction
00000 LD
00001 AND
00002 LD NOT
00003 OR
00004 OR
00005 CNT
00006 LD
00007 LD NOT
00008 CNT
00009 LD
00010 OUT
CNT
CNT
#
CNT
#
Operands
CNT
00000
00001
00002
001
002
001
0100
001
00002
002
0200
002
00203
00203
Example 3:
Extended Timers
CNT can be used in sequence as many times as required to produce counters capable of counting any desired values.
CNT can be used to create extended timers in two ways: by combining TIM with
CNT and by counting SR area clock pulse bits.
In the following example, CNT 002 counts the number of times TIM 001 reaches zero from its SV. The Completion Flag for TIM 001 is used to reset TIM 001 so that it runs continuously and CNT 002 counts the number of times the Completion Flag for TIM 001 goes ON (CNT 002 would be executed once each time be-
147
Timer and Counter Instructions
00000 TIM 001 CNT 002
TIM 001
00001
CNT 002
00000 25502
00001
CNT 001
Section 5-14 tween when the Completion Flag for TIM 001 goes ON and TIM 001 is reset by its Completion Flag). TIM 001 is also reset by the Completion Flag for CNT 002 so that the extended timer would not start again until CNT 002 was reset by
00001, which serves as the reset for the entire extended timer.
Because in this example the SV for TIM 001 is 5.0 seconds and the SV for CNT
002 is 100, the Completion Flag for CNT 002 turns ON when 5 seconds x 100 times, i.e., 500 seconds (or 8 minutes and 20 seconds) have expired. This would result in 00201 being turned ON.
CP
R
TIM 001
#0050 005.0 s
CNT
002
#0100
00201
Address Instruction
00000 LD
00001 AND NOT
00002 AND NOT
00003 TIM
00004 LD
00005 LD
00006 CNT
00007 LD
00008 OUT
TIM
CNT
#
TIM
#
Operands
CNT
00000
001
002
001
0050
001
00001
002
0100
002
00201
In the following example, CNT 001 counts the number of times the 1-second clock pulse bit (25502) goes from OFF to ON. Here again, 00000 is used to control the times when CNT is operating.
Because in this example the SV for CNT 001 is 700, the Completion Flag for
CNT 002 turns ON when 1 second x 700 times, or 11 minutes and 40 seconds have expired. This would result in 00202 being turned ON.
CP
R
CNT
001
#0700
0202
Address Instruction
00000 LD
00001 AND
00002 LD NOT
00003 CNT
00004 LD
00005 OUT
#
Operands
CNT
00000
25502
00001
001
0700
001
00202
!
Caution The shorter clock pulses will not necessarily produce accurate timers because their short ON times might not be read accurately during longer cycles. In particular, the 0.02-second and
0.1-second clock pulses should not be used to create timers with CNT instructions.
5-14-5 REVERSIBLE COUNTER – CNTR(12)
Ladder Symbol
II
DI
R
CNTR(12)
N
SV
Definer Values
N: TC number
# (000 through 511)
Operand Data Areas
SV: Set value (word, BCD)
IR, AR, DM, HR, LR, #
148
Timer and Counter Instructions
Limitations
Description
Precautions
Flags
Section 5-14
Each TC number can be used as the definer in only one TIMER or COUNTER instruction.
The CNTR(12) is a reversible, up/down circular counter, i.e., it is used to count between zero and SV according to changes in two execution conditions, those in the increment input (II) and those in the decrement input (DI).
The present value (PV) will be incremented by one whenever CNTR(12) is executed with an ON execution condition for II and the last execution condition for II was OFF. The present value (PV) will be decremented by one whenever
CNTR(12) is executed with an ON execution condition for DI and the last execution condition for DI was OFF. If OFF to ON changes have occurred in both II and
DI since the last execution, the PV will not be changed.
If the execution conditions have not changed or have changed from ON to OFF for both II and DI, the PV of CNT will not be changed.
When decremented from 0000, the present value is set to SV and the Completion Flag is turned ON until the PV is decremented again. When incremented past the SV, the PV is set to 0000 and the Completion Flag is turned ON until the
PV is incremented again.
CNTR(12) is reset with a reset input, R. When R goes from OFF to ON, the PV is reset to zero. The PV will not be incremented or decremented while R is ON.
Counting will begin again when R goes OFF. The PV for CNTR(12) will not be reset in interlocked program sections or by the effects of power interruptions.
Changes in II and DI execution conditions, the Completion Flag, and the PV are illustrated below starting from part way through CNTR(12) operation (i.e., when reset, counting begins from zero). PV line height is meant to indicate changes in the PV only.
Execution condition on increment (II)
Execution condition on decrement (DI)
Completion Flag
ON
OFF
ON
OFF
ON
OFF
PV
SV – 2
SV – 1
SV
0000
0001
0000
SV
SV – 1
SV – 2
Program execution will continue even if a non-BCD SV is used, but the SV will not be correct.
ER: SV is not in BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
149
Data Shifting Section 5-15
5-15 Data Shifting
All of the instructions described in this section are used to shift data, but in differing amounts and directions. The first shift instruction, SFT(10), shifts an execution condition into a shift register; the rest of the instructions shift data that is already in memory.
5-15-1 SHIFT REGISTER – SFT(10)
Ladder Symbol
I
P
R
SFT(10)
St
E
Operand Data Areas
St: Starting word
IR, SR, AR, HR, LR
E: End word
IR, SR, AR, HR, LR
Limitations
Description
E
St must be less than or equal to E, and St and E must be in the same data area.
If a bit address in one of the words used in a shift register is also used in an instruction that controls individual bit status (e.g., OUT, KEEP(11)), an error
(“COIL DUPL”) will be generated when program syntax is checked on the Programming Console or another Programming Device. The program, however, will be executed as written. See Example 2: Controlling Bits in Shift Registers for a programming example that does this.
SFT(10) is controlled by three execution conditions, I, P, and R. If SFT(10) is executed and 1) execution condition P is ON and was OFF the last execution, and 2) R is OFF, then execution condition I is shifted into the rightmost bit of a shift register defined between St and E, i.e., if I is ON, a 1 is shifted into the register; if I is OFF, a 0 is shifted in. When I is shifted into the register, all bits previously in the register are shifted to the left and the leftmost bit of the register is lost.
St+1, St+2, ...
St
Lost data
The execution condition on P functions like a differentiated instruction, i.e., I will be shifted into the register only when P is ON and was OFF the last time SFT(10) was executed. If execution condition P has not changed or has gone from ON to
OFF, the shift register will remain unaffected.
St designates the rightmost word of the shift register; E designates the leftmost.
The shift register includes both of these words and all words between them. The same word may be designated for St and E to create a 16-bit (i.e., 1-word) shift register.
When execution condition R goes ON, all bits in the shift register will be turned
OFF (i.e., set to 0) and the shift register will not operate until R goes OFF again.
There are no flags affected by SFT(10).
Execution condition I
Flags
150
Data Shifting
Example 1:
Basic Application
00005
25502
00006
Section 5-15
The following example uses the 1-second clock pulse bit (25502) so that the execution condition produced by 00005 is shifted into a 3-word register between
IR 010 and IR 012 every second.
I
P
R
SFT(10)
010
012
Address Instruction
00000 LD
00001 LD
00002 LD
00003 SFT(10)
Operands
00005
25502
00006
010
012
Example 2:
Controlling Bits in Shift
Registers
The following program is used to control the status of the 17th bit of a shift register running from AR 00 through AR 01. When the 17th bit is to be set, 00004 is turned ON. This causes the jump for JMP(04) 00 not to be made for that one cycle, and AR 0100 (the 17th bit) will be turned ON. When 12800 is OFF (i.e., at all times except during the first cycle after 00004 has changed from OFF to ON), the jump is executed and the status of AR 0100 will not be changed.
00004
12800
12800
00200 00201
00202
00203
I
P
SFT(10)
AR 00
AR 01
R
DIFU(13) 12800
JMP(04) 00
AR 0100
Address Instruction
00000 LD
00001 AND
00002 LD
00003 LD
00004 SFT(10)
00005 LD
00006 DIFU(13)
00007 LD
00008 JMP(04)
00009 LD
00010 OUT
00011 JME(05)
AR
AR
Operands
00200
00201
00202
00203
AR
00
01
00004
12800
12800
00
12800
0100
00
JME(05) 00
Example 3:
Control Action
When a bit that is part of a shift register is used in OUT (or any other instruction that controls bit status), a syntax error will be generated during the program check, but the program will executed properly (i.e., as written).
The following program controls the conveyor line shown below so that faulty products detected at the sensor are pushed down a shoot. To do this, the execution condition determined by inputs from the first sensor (00001) are stored in a shift register: ON for good products; OFF for faulty ones. Conveyor speed has been adjusted so that HR 0003 of the shift register can be used to activate a pusher (00500) when a faulty product reaches it, i.e., when HR 0003 turns ON,
00500 is turned ON to activate the pusher.
151
Data Shifting Section 5-15
The program is set up so that a rotary encoder (00000) controls execution of
SFT(10) through a DIFU(13), the rotary encoder is set up to turn ON and OFF each time a product passes the first sensor. Another sensor (00002) is used to detect faulty products in the shoot so that the pusher output and HR 0003 of the shift register can be reset as required.
Sensor
(00001)
Pusher
(00500)
00001
00000
00003
HR 0003
00002
Rotary Encoder
(00000)
Sensor
(00002)
Chute
I
P
R
SFT(10)
HR 00
HR 01
00500
00500
Address Instruction
00000 LD
00001 LD
00002 LD
00003 SFT(10)
00004
00008
LD
00005 OUT
00006 LD
00007 OUT NOT
OUT NOT
HR
HR
HR
Operands
00001
00000
00003
HR
00
01
0003
00500
00002
00500
0003
HR 0003
5-15-2 REVERSIBLE SHIFT REGISTER – SFTR(84)
Ladder Symbols
SFTR(84)
C
St
E
@SFTR(84)
C
St
E
Operand Data Areas
C: Control word
IR, AR, DM, HR, LR
St: Starting word
IR, SR, AR, DM, HR, LR
E: End word
IR, SR, AR, DM, HR LR
St and E must be in the same data area and St must be less than or equal to E.
Limitations
152
Data Shifting
Description
Flags
Example
00005
00006
00007
00008
00009
Section 5-15
SFTR(84) is used to create a single- or multiple-word shift register that can shift data to either the right or the left. To create a single-word register, designate the same word for St and E. The control word provides the shift direction, the status to be put into the register, the shift pulse, and the reset input. The control word is allocated as follows:
15 14 13 12 Not used.
Shift direction
1 (ON): Left (LSB to MSB)
0 (OFF): Right (MSB to LSB)
Status to input into register
Shift pulse bit
Reset
The data in the shift register will be shifted one bit in the direction indicated by bit
12, shifting one bit out to CY and the status of bit 13 into the other end whenever
SFTR(84) is executed with an ON execution condition as long as the reset bit is
OFF and as long as bit 14 is ON. If SFTR(84) is executed with an OFF execution condition or if SFTR(84) is executed with bit 14 OFF, the shift register will remain unchanged. If SFTR(84) is executed with an ON execution condition and the reset bit (bit 15) is OFF, the entire shift register and CY will be set to zero.
ER: St and E are not in the same data area or ST is greater than E.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: Receives the status of bit 00 of St or bit 15 of E, depending on the shift direction.
In the following example, IR 00005, IR 00006, IR 00007, and IR 00008 are used to control the bits of C used in @SHIFT(84). The shift register is between LR 20 and LR 21, and it is controlled through IR 00009.
05012
05013
05014
05015
@SFTR(84)
050
LR 20
LR 21
Direction
Status to input
Shift pulse
Address Instruction
00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
LD
OUT
LD
OUT
LD
OUT
LD
OUT
LD
@SFT(10)
Reset
LR
LR
Operands
00005
05012
00006
05013
00007
00514
00008
05015
00009
050
20
21
153
Data Shifting
5-15-3 ARITHMETIC SHIFT LEFT – ASL(25)
ASL(25)
Wd
Ladder Symbols
@ASL(25)
Wd
Section 5-15
Operand Data Areas
Wd: Shift word
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, ASL(25) is not executed. When the execution condition is ON, ASL(25) shifts a 0 into bit 00 of Wd, shifts the bits of Wd one bit to the left, and shifts the status of bit 15 into CY.
CY
Bit
15
Bit
00
1 0 0 1 1 1 0 0 0 1 0 1 0 0 1 1
0
Flags ER: Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: Receives the status of bit 15.
EQ: ON when the content of Wd is zero; otherwise OFF.
5-15-4 ARITHMETIC SHIFT RIGHT – ASR(26)
ASR(26)
Wd
Ladder Symbols
@ASR(26)
Wd
Operand Data Areas
Wd: Shift word
IR, SR, AR, DM, HR, LR
Description
Flags
When the execution condition is OFF, ASR(25) is not executed. When the execution condition is ON, ASR(25) shifts a 0 into bit 15 of Wd, shifts the bits of Wd one bit to the right, and shifts the status of bit 00 into CY.
0
Bit
15
1
Bit
00
1 0 0 1 0 1 1 0 0 1 1 0 0 1 0
CY
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
CY: Receives the data of bit 00.
EQ: ON when the content of Wd is zero; otherwise OFF.
154
Data Shifting
5-15-5 ROTATE LEFT – ROL(27)
ROL(27)
Wd
Ladder Symbols
@ROL(27)
Wd
Section 5-15
Operand Data Areas
Wd: Rotate word
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, ROL(27) is not executed. When the execution condition is ON, ROL(27) shifts all Wd bits one bit to the left, shifting CY into bit 00 of Wd and shifting bit 15 of Wd into CY.
CY
0
Bit
15
Bit
00
1 0 1 1 0 0 1 1 1 0 0 0 1 1 0 1
Precautions
Flags
Use STC(41) to set the status of CY or CLC(41) to clear the status of CY before doing a rotate operation to ensure that CY contains the proper status before execution ROL(27).
The status of CY is cleared at the end of each cycle (when END(01) is executed).
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
CY: Receives the data of bit 15.
EQ: ON when the content of Wd is zero; otherwise OFF.
5-15-6 ROTATE RIGHT – ROR(28)
Ladder Symbols
ROR(28)
Wd
@ROR(28)
Wd
Operand Data Areas
Wd: Rotate word
IR, SR, AR, DM, HR, LR
Description
Precautions
Flags
When the execution condition is OFF, ROR(28) is not executed. When the execution condition is ON, ROR(28) shifts all Wd bits one bit to the right, shifting CY into bit 15 of Wd and shifting bit 00 of Wd into CY.
CY
0
Bit
15
Bit
00
0 1 0 1 0 1 0 0 0 1 1 1 0 0 0 1
Use STC(41) to set the status of CY or CLC(41) to clear the status of CY before doing a rotate operation to ensure that CY contains the proper status before execution ROR(28).
The status of CY is cleared at the end of each cycle (when END(01) is executed).
ER: Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: Receives the data of bit 15.
EQ: ON when the content of Wd is zero; otherwise OFF.
155
Data Shifting
5-15-7 ONE DIGIT SHIFT LEFT – SLD(74)
SLD(74)
St
E
Ladder Symbols
@SLD(74)
St
E
Section 5-15
Limitations
Description
St and E must be in the same data area, and St must be less than or equal to E.
When the execution condition is OFF, SLD(74) is not executed. When the execution condition is ON, SLD(74) shifts data between St and E (inclusive) by one digit (four bits) to the left. 0 is written into the rightmost digit of the St, and the content of the leftmost digit of E is lost.
E
8 F C 5
...
St
D 7 9 1
Lost data 0
Precautions
Flags
If a power failure occurs during a shift operation across more than 50 words, the shift operation might not be completed.
ER: The St and E words are in different areas, or St is greater than E.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-15-8 ONE DIGIT SHIFT RIGHT – SRD(75)
Ladder Symbols
SRD(75)
E
St
@SRD(75)
E
St
Operand Data Areas
E: End word
IR, SR, AR, DM, HR, LR
St: Starting word
IR, SR, AR, DM, HR, LR
Limitations
Description
Operand Data Areas
St: Starting word
IR, SR, AR, DM, HR, LR
E: End word
IR, SR, AR, DM, HR, LR
St and E must be in the same data area, and St must be less than or equal to E.
When the execution condition is OFF, SRD(75) is not executed. When the execution condition is ON, SRD(75) shifts data between St and E (inclusive) by one digit (four bits) to the right. 0 is written into the leftmost digit of St and the rightmost digit of E is lost.
St
3 4 5 2
...
E
F 8 C 1
0 Lost data
156
Data Shifting Section 5-15
Precautions If a power failure occurs during a shift operation across more than 50 words, the shift operation might not be completed. Set the range between E and St to a maximum of 50 words.
Flags ER: The St and E words are in different areas, or St is less than E.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
5-15-9 WORD SHIFT – WSFT(16)
Ladder Symbols
WSFT(16)
St
E
@WSFT(16)
St
E
Operand Data Areas
St: Starting word
IR, SR, AR, DM, HR, LR
E: End word
IR, SR, AR, DM, HR, LR
Limitations
Description
St and E must be in the same data area, and St must be less than or equal to E.
When the execution condition is OFF, WSFT(16) is not executed. When the execution condition is ON, WSFT(16) shifts data between St and E in word units.
Zeros are written into St and the content of E is lost.
E St + 1 St
F 0 C 2 3 4 5 2 1 0 2 9
Lost
0000
E St + 1 St
3 4 5 2 1 0 2 9 0 0 0 0
Flags ER: The St and E words are in different areas, or St is greater than E.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-15-10 ASYNCHRONOUS SHIFT REGISTER – ASFT(17)
Ladder Symbols
Operand Data Areas
C: Control word
IR, SR, AR, DM, HR, LR
ASFT(17)
C
St
E
ASFT(17)
C
St
E
St: Starting word
IR, SR, AR, DM, HR, LR
E: End word
IR, SR, AR, DM, HR, LR
Limitations St and E must be in the same data area, and St must be less than or equal to E.
157
Data Movement
Description
Control Word
Flags
Example
Section 5-16
When the execution condition is OFF, ASFT(17) does nothing and the program moves to the next instruction. When the execution condition is ON, ASFT(17) is used to create and control a reversible asynchronous word shift register between St and E. This register only shifts words when the next word in the register is zero, e.g., if no words in the register contain zero, nothing is shifted. Also, only one word is shifted for each word in the register that contains zero. When the contents of a word are shifted to the next word, the original word’s contents are set to zero. In essence, when the register is shifted, each zero word in the register trades places with the next word. (See Example below.)
The shift direction (i.e. whether the “next word” is the next higher or the next lower word) is designated in C. C is also used to reset the register. All of any portion of the register can be reset by designating the desired portion with St and E.
Bits 00 through 12 of C are not used. Bit 13 is the shift direction: turn bit 13 ON to shift down (toward lower addressed words) and OFF to shift up (toward higher addressed words). Bit 14 is the Shift Enable Bit: turn bit 14 ON to enable shift register operation according to bit 13 and OFF to disable the register. Bit 15 is the
Reset bit: the register will be reset (set to zero) between St and E when
ASFT(17) is executed with bit 15 ON. Turn bit 15 OFF for normal operation.
ER: The St and E words are in different areas, or St is greater than E.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
The following example shows instruction ASFT(17) used to shift words in an
11-word shift register created between DM 0100 and DM 0110 with a control word value of #6000 (bits 13 and 14 ON). The data changes that would occur for the given register and control word contents are also shown.
00000
Address Instruction Operands
ASFT(17)
#6000
00100 LD 00000
DM 0100
00101 ASFT(17)
# 6000
DM 0110
DM 0100
DM 0110
DM 0100
DM 0101
DM 0102
DM 0103
DM 0104
DM 0105
DM 0106
DM 0107
DM 0108
DM 0109
DM 0110
Before execution
1234
0000
0000
2345
3456
0000
4567
5678
6789
0000
789A
After 1 execution
1234
0000
2345
0000
3456
4567
0000
5678
6789
789A
0000
After 7 executions
1234
2345
3456
4567
5678
6789
789A
0000
0000
0000
0000
5-16 Data Movement
This section describes the instructions used for moving data between different addresses in data areas. These movements can be programmed to be within the same data area or between different data areas. Data movement is essential for utilizing all of the data areas of the PC. Effective communications in Link Systems also requires data movement. All of these instructions change only the content of the words to which data is being moved, i.e., the content of source words is the same before and after execution of any of the data movement instructions.
158
Data Movement
5-16-1 MOVE – MOV(21)
Ladder Symbols
MOV(21)
S
D
@MOV(21)
S
D
Section 5-16
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR, #
D: Destination word
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, MOV(21) is not executed. When the execution condition is ON, MOV(21) copies the content of S to D.
Source word Destination word
Bit status not changed.
Precautions
Flags
TC numbers cannot be designated as D to change the PV of the timer or counter.
You can, however, easily change the PV of a timer or a counter by using
BSET(71).
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when all zeros are transferred to D.
5-16-2 MOVE NOT – MVN(22)
Ladder Symbols
MVN(22)
S
D
@MVN(22)
S
D
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR, #
D: Destination word
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, MVN(22) is not executed. When the execution condition is ON, MVN(22) transfers the inverted content of S (specified word or four-digit hexadecimal constant) to D, i.e., for each ON bit in S, the corresponding bit in D is turned OFF, and for each OFF bit in S, the corresponding bit in D is turned ON.
Source word Destination word
Bit status inverted.
Precautions
Flags
TC numbers cannot be designated as D to change the PV of the timer or counter.
However, these can be easily changed using BSET(71).
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when all zeros are transferred to D.
159
Data Movement Section 5-16
5-16-3 BLOCK SET – BSET(71)
Limitations
Description
Ladder Symbols
BSET(71)
S
St
E
@BSET(71)
S
St
E
Operand Data Areas
S: Source data
IR, SR, AR, DM, HR, TC, LR, #
St: Starting word
IR, SR, AR, DM, HR, TC, LR
E: End Word
IR, SR, AR, DM, HR, TC, LR
St must be less than or equal to E, and St and E must be in the same data area.
When the execution condition is OFF, BSET(71) is not executed. When the execution condition is ON, BSET(71) copies the content of S to all words from St through E.
S
3 4 5 2
St
3 4 5 2
St+1
3 4 5 2
St+2
3 4 5 2
Flags
E
3 4 5 2
BSET(71) can be used to change timer/counter PV. (This cannot be done with
MOV(21) or MVN(22).) BSET(71) can also be used to clear sections of a data area, i.e., the DM area, to prepare for executing other instructions.
ER: St and E are not in the same data area or St is greater than E.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
160
Data Movement
Example
00003 00004
00004 00003
00003
00004
Section 5-16
The following example shows how to use BSET(71) to change the PV of a timer depending on the status of IR 00003 and IR 00004. When IR 00003 is ON, TIM
010 will operate as a 50-second timer; when IR 00004 is ON, TIM 010 will operate as a 30-second timer.
@BSET(71)
#0500
TIM 010
TIM 010
@BSET(71)
#0300
TIM 010
TIM 010
TIM 010
#9999
Address Instruction
00000 LD
00001 AND NOT
00002 @BSET(71)
00003 LD
00004 AND NOT
00005 @BSET(71)
00006
00007
00008
LD
OR
TIM
#
TIM
TIM
Operands
00003
00004
#
TIM
TIM
#
0500
010
010
00004
00003
0300
010
010
00003
00004
010
9999
5-16-4 BLOCK TRANSFER – XFER(70)
Limitations
Description
Ladder Symbols
XFER(70)
N
S
D
@XFER(70)
N
S
D
Operand Data Areas
N: Number of words (BCD)
IR, SR, AR, DM, HR, TC, LR, #
S: Starting source word
IR, SR, AR, DM, HR, TC, LR
D: Starting destination word
IR, SR, AR, DM, HR, TC, LR
Both S and D may be in the same data area, but their respective block areas must not overlap. S and S+N must be in the same data area, as must D and D+N.
N must be BCD between 0000 and 6144.
When the execution condition is OFF, XFER(70) is not executed. When the execution condition is ON, XFER(70) copies the contents of S, S+1, ..., S+N to D,
D+1, ..., D+N.
S
3 4 5 2
S+1
3 4 5 1
S+2
3 4 2 2
D
3 4 5 2
D+1
3 4 5 1
D+2
3 4 2 2
S+N
6 4 5 2
D+N
6 4 5 2
161
Data Movement Section 5-16
Flags ER: N is not BCD between 0000 and 2000.
S and S+N or D and D+N are not in the same data area.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
5-16-5 DATA EXCHANGE – XCHG(73)
Ladder Symbols
XCHG(73)
E1
E2
@XCHG(73)
E1
E2
Operand Data Areas
E1: Exchange word 1
IR, SR, AR, DM, HR, TC, LR
E2: Exchange word 2
IR, SR, AR, DM, HR, TC, LR
Description When the execution condition is OFF, XCHG(73) is not executed. When the execution condition is ON, XCHG(73) exchanges the content of E1 and E2.
E1 E2
Flags
If you want to exchange content of blocks whose size is greater than 1 word, use work words as an intermediate buffer to hold one of the blocks using XFER(70) three times.
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-16-6 SINGLE WORD DISTRIBUTE – DIST(80)
Ladder Symbols
DIST(80)
S
DBs
C
@DIST(80)
S
DBs
C
Operand Data Areas
S: Source data
IR, SR, AR, DM, HR, TC, LR, #
DBs: Destination base word
IR, SR, AR, DM, HR, TC, LR
C: Control word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Limitations
Description
Precautions
Data Distribution Operation
(C=0000 to 6655)
C must be a BCD. If C ≤ 6655, DBs must be in the same data area as DBs+C. If
C ≥ 9000, DBs must be in the same data area as DBs+C–9000.
Depending on the value of C, DIST(80) will operate as a data distribution instruction or stack instruction. If C is between 0000 and 6655, DIST(80) will operate as a data distribution instruction and copy the content of S to DBs+C. If the leftmost digit of C is 9, DIST(80) will operate as a stack instruction and create a stack with the number of words specified in the rightmost 3 digits of C.
Stack operation will be unreliable if the specified stack length is different from the length specified in the last execution of DIST(80) or COLL(81).
When the execution condition is OFF, DIST(80) is not executed. When the execution condition is ON, DIST(80) copies the content of S to DBs+C, i.e.,C is added to DBs to determine the destination word.
S
3 4 5 2
DBs + C
3 4 5 2
162
Data Movement
Stack Operation
(C=9000 to 9999)
Section 5-16
When the execution condition is OFF, DIST(80) is not executed. When the execution condition is ON, DIST(80) operates a stack from DBs to DBs+C–9000.
DBs is the stack pointer, so S is copied to the word indicated by DBs and DBs is incremented by 1.
Digits of C: 3 2 1 0
Specifies the stack length (000 to 999).
A value of 9 indicates stack operation.
Data can be added to the stack until it is full. DIST(80) is normally used together with COLL(81), which can be set to read from the stack on a FIFO or LIFO basis.
Refer to 5-16-7 DATA COLLECT – COLL(81) for details.
Example of Stack Operation In the following example, the content of C (LR 10) is 9010, and DIST(80) is used to write the numerical data #00FF to the 10-word stack from HR 20 to HR 29.
During the first cycle when IR 00001 is ON, the data is written to DBs+1 (HR 21) and the stack pointer is incremented by 1. In the second cycle the data is written to DBs+2 (HR 22) and the stack pointer is incremented, and so on.
00001
Stack pointer
Stack area
DIST(80)
# 00FF
HR 20
LR 10
Address Instruction
00000 LD
00001 DIST(80)
#
HR
LR
Operands
00001
00FF
20
10
After one execution
HR 20
0 0 0 1
HR 21
0 0 F F
HR 22
Stack pointer incremented
After two executions
HR 20
0 0 0 2
HR 21
0 0 F F
HR 22
0 0 F F
HR 29 HR 29
Flags ER: The content of C is not BCD or 6655<C<9000.
When C
≤
6655, DBs and DBs+C are not in the same data area.
When C
≥
9000, DBs and DBs+C–9000 are not in the same data area.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of S is zero; otherwise OFF.
163
Data Movement
5-16-7 DATA COLLECT – COLL(81)
Section 5-16
Ladder Symbols
COLL(81)
SBs
C
D
@COLL(81)
SBs
C
D
Operand Data Areas
SBs: Source base word
IR, SR, AR, DM, HR, TC, LR
C: Offset data (BCD)
IR, SR, AR, DM, HR, TC, LR, #
D: Destination word
IR, SR, AR, DM, HR, TC, LR
Limitations
Description
Precautions
Data Collection Operation
(C=0000 to 6655)
C must be a BCD. If C ≤ 6655, SBs must be in the same data area as SBs+C. If the leftmost digit of C is 8 or 9, DBs must be in the same data area as SBs+N (N=the
3 rightmost digits of C).
Depending on the value of C, COLL(81) will operate as a data collection instruction, FIFO stack instruction, or LIFO stack instruction. If C is between 0000 and
6655, COLL(81) will operate as a data collection instruction and copy the content of SBs+C to D.
If the leftmost digit of C is 9 , COLL(81) will operate as a FIFO stack instruction. If the leftmost digit of C is 8, COLL(81) will operate as a LIFO stack instruction.
Both stack operations use a stack beginning at SBs with a length specified in the rightmost 3 digits of C.
Stack operation will be unreliable if the specified stack length is different from the length specified in the last execution of DIST(80) or COLL(81).
When the execution condition is OFF, COLL(81) is not executed. When the execution condition is ON, COLL(81) copies the content of SBs + C to D, i.e., C is added to SBs to determine the source word.
SBs + C
3 4 5 2
D
3 4 5 2
FIFO Stack Operation
(C=9000 to 9999)
When the execution condition is OFF, COLL(81) is not executed. When the execution condition is ON, COLL(81) copies the data from the oldest word recorded in the stack to D. The stack pointer, SBs, is then decremented by 1.
Digits of C: 3 2 1 0
Specifies the stack length (000 to 999).
A value of 9 indicates FIFO stack operation.
COLL(81) can be used together with DIST(80). Refer to 5-16-6 SINGLE WORD
DISTRIBUTE – DIST(80) for details.
Note FIFO stands for First-In-First-Out.
164
Data Movement
Example
00001
Section 5-16
In the following example, the content of C (HR 00) is 9010, and COLL(81) is used to copy the oldest entries from a10-word stack (IR 001 to IR 010) to LR 20.
DIST(80)
001
HR 00
LR 20
Address Instruction
00000 LD
00001 COLL(81)
HR
LR
Operands
00001
001
00
20
Stack pointer
Before execution
IR 001
0 0 0 2
IR 002
1 2 3 4
IR 003
A B C D
Stack pointer decremented
After one execution
IR 001
0 0 0 1
IR 002
A B C D
IR 003
Stack pointer decremented
After two executions
IR 001
0 0 0 0
IR 002
IR 003
Stack area
IR 010 IR 010 IR 010
LIFO Stack Operation
(C=8000 to 8999)
Output
LR 20
1 2 3 4
Output
LR 20
A B C D
When the execution condition is OFF, COLL(81) is not executed. When the execution condition is ON, COLL(81) copies the data most recently recorded in the stack to D. The stack pointer, SBs, is then decremented by 1.
Digits of C: 3 2 1 0
Specifies the stack length (000 to 999).
A value of 8 indicates LIFO stack operation.
Data can be added to the stack until it is full. DIST(80)’s stack operation can be used together with COLL(81)’s read stack operation. COLL(81) can be set to read on a FIFO or LIFO basis. Refer to 5-16-6 SINGLE WORD DISTRIBUTE
(80) for details.
Note LIFO stands for Last-In-First-Out.
165
Data Movement
Example
00001
Stack pointer
Section 5-16
In the following example, the content of C (HR 00) is 8010, and COLL(81) is used to copy the most recent entries from a 10-word stack (IR 001 to IR 010) to LR 20.
COLL(81)
001
HR 00
LR 20
Address Instruction
00000 LD
00001 COLL(81)
HR
LR
Operands
00001
001
00
20
Before execution
IR 001
0 0 0 2
IR 002
1 2 3 4
IR 003
A B C D
Stack pointer decremented
After one execution
IR 001
0 0 0 1
IR 002
1 2 3 4
IR 003
Stack pointer decremented
After two executions
IR 001
0 0 0 0
IR 002
IR 003
Stack area
IR 010 IR 010 IR 010
Output
LR 20
A B C D
Output
LR 20
1 2 3 4
Flags ER: The content of C is not BCD or 6655<C<8000.
When C ≤ 6655, DBs and DBs+C are not in the same data area.
When C ≥ 8000, the beginning and end of the stack are not in the same data area or the value of the stack pointer exceeds the length of the stack.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the transferred data is zero; otherwise OFF.
5-16-8 MOVE BIT – MOVB(82)
Ladder Symbols
MOVB(82)
S
Bi
D
@MOVB(82)
S
Bi
D
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, LR, #
Bi: Bit designator (BCD)
IR, SR, AR, DM, HR, TC, LR, #
D: Destination word
IR, SR, AR, DM, HR, LR
Limitations The rightmost two digits and the leftmost two digits of Bi must each be between
00 and 15.
166
Data Movement
Description
Section 5-16
Bi
MSB
1 2 0 1
When the execution condition is OFF, MOVB(82) is not executed. When the execution condition is ON, MOVB(82) copies the specified bit of S to the specified bit in D. The bits in S and D are specified by Bi. The rightmost two digits of Bi designate the source bit; the leftmost two bits designate the destination bit.
Bi
Bit
15
0 0 0 1 0 0 1 0 0 0 0 0 0 0 0 1
Bit
00
LSB
S
Bit
15
1 2 0 1 Bit
00
0 1 0 1 0 1 0 0 0 1 1 1 0 0 0 1
Source bit (00 to 15)
Destination bit (00 to 15)
D
Bit
15
0 1 0 0 0 1 0 0 0 1 1 1 0 0 0 1
Bit
00
Flags ER: C is not BCD, or it is specifying a non-existent bit (i.e., bit specification must be between 00 and 15).
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-16-9 MOVE DIGIT – MOVD(83)
Ladder Symbols
MOVD(83)
S
Di
D
@MOVD(83)
S
Di
D
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR, #
Di: Digit designator (BCD)
IR, SR, AR, DM, HR, TC, LR, #
D: Destination word
IR, SR, AR, DM, HR, TC, LR
Limitations
Description
The rightmost three digits of Di must each be between 0 and 3.
When the execution condition is OFF, MOVD(83) is not executed. When the execution condition is ON, MOVD(83) copies the content of the specified digit(s) in S to the specified digit(s) in D. Up to four digits can be transferred at one time. The first digit to be copied, the number of digits to be copied, and the first digit to receive the copy are designated in Di as shown below. Digits from S will be copied to consecutive digits in D starting from the designated first digit and continued for the designated number of digits. If the last digit is reached in either S or D, further digits are used starting back at digit 0.
Digit number: 3 2 1 0
First digit in S (0 to 3)
Number of digits (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
First digit in D (0 to 3)
Not used.
167
Data Movement
Digit Designator
Section 5-16
The following show examples of the data movements for various values of Di.
0
1
2
3
S
Di: 0010
S
Di: 0031
2
3
0
1
D
2
3
0
1
D
0
1
2
3
0
1
2
3
S
Di: 0030
2
3
0
1
S
Di: 0023
D
0
1
2
3
D
0
1
2
3
Flags ER: At least one of the rightmost three digits of Di is not between 0 and 3.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-16-10 TRANSFER BITS – XFRB(62)
Ladder Symbols
XFRB(62)
C
S
D
@XFRB(62)
C
S
D
Operand Data Areas
C: Control word
IR, SR, AR, DM, TC, HR, LR, #
S: First source word
IR, SR, AR, DM, HR, TC, LR
D: First destination word
IR, SR, AR, DM, HR, LR
Limitations
Description
The specified source bits must be in the same data area.
The specified destination bits must be in the same data area.
When the execution condition is OFF, XFRB(62) is not executed. When the execution condition is ON, XFRB(62) copies the specified source bits to the specified destination bits. The two rightmost digits of C specify the starting bits in S and D and the leftmost two digits indicate the number of bits that will be copied.
C
MSB LSB
First bit of S (0 to F)
First bit of D (0 to F)
Number of bits (01 to FF)
Note 255 (FF) bits or more can not be copied at one time.
168
Data Comparison
Example
Section 5-17
In the following example, XFRB(62) is used to transfer 5 bits from IR 020 to
LR 21 when IR 00001 is ON. The starting bit in IR 020 is 0, and the starting bit in
LR 21 is 4, so IR 02000 to IR 02004 are copied to LR 2104 to LR 2108.
00001
XFRB(62)
#0540
IR 020
LR 21
Address Instruction
00000 LD
00001 XFRB(62)
#
Operands
00001
LR
0540
020
21
S (IR 020)
Bit
15
Bit
00
0 1 0 1 0 1 0 0 0 0 0 1 0 1 1 1
D (LR 21)
Bit
15
0 1 0 0 0 1 0
Bit
00
1 0 1 1 1 0 0 0 1
Flags ER: The specified source bits are not all in the same data area.
The specified destination bits are not all in the same data area.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-17 Data Comparison
5-17-1 MULTI-WORD COMPARE – MCMP(19)
Ladder Symbols
MCMP(19)
TB1
TB2
R
@MCMP(19)
TB1
TB2
R
Operand Data Areas
TB1: First word of table 1
IR, SR, AR, DM, HR, TC, LR
TB2: First word of table 2
IR, SR, AR, DM, HR, TC, LR
R: Result word
IR, AR, DM, HR, TC, LR
Limitations
Description
Flags
TB1 and TB1+15 must be in the same data area, as must TB2 and TB2+15.
When the execution condition is OFF, MCMP(19) is not executed. When the execution condition is ON, MCMP(19) compares the content of TB1 to TB2,
TB1+1 to TB2+1, TB1+2 to TB2+2, ..., and TB1+15 to TB2+15. If the first pair is equal, the first bit in R is turned OFF, etc., i.e., if the content of TB1 equals the content of TB2, bit 00 is turned OFF, if the content of TB1+1 equals the content of
TB2+1, bit 01 is turned OFF, etc. The rest of the bits in R will be turned ON.
ER: One of the tables (i.e., TB1 through TB1+15, or TB2 through TB2+15) exceeds the data area.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
169
Data Comparison
Example
00000
TB1: IR 100
IR 100
IR 101
IR 102
IR 103
IR 104
IR 105
IR 106
IR 107
IR 108
IR 109
IR 110
IR 111
IR 112
IR 113
IR 114
IR 115
0100
0200
0210
ABCD
ABCD
ABCD
ABCD
0800
0900
1000
ABCD
ABCD
ABCD
1400
0210
1212
Section 5-17
The following example shows the comparisons made and the results provided for MCMP(19). Here, the comparison is made during each cycle when 00000 is
ON.
MCMP(19)
100
DM 0200
DM 0300
TB2: DM 0200
DM 0200
DM 0201
DM 0202
DM 0203
DM 0204
DM 0205
DM 0206
DM 0207
DM 0208
DM 0209
DM 0210
DM 0211
DM 0212
DM 0213
DM 0214
DM 0215
0100
0200
0210
0400
0500
0600
0210
0800
0900
1000
0210
1200
1300
1400
0210
1600
Address Instruction
00000 LD
00001 MCMP(19)
R: DM 0300
DM 030000
DM 030001
DM 030002
DM 030003
DM 030004
DM 030005
DM 030006
DM 030007
DM 030008
DM 030009
DM 030010
DM 030011
DM 030012
DM 030013
DM 030014
DM 030015
0
0
1
1
0
1
1
0
1
1
0
0
1
1
0
0
DM
DM
Operands
00000
100
0200
0300
5-17-2 COMPARE – CMP(20)
Limitations
Description
Precautions
Ladder Symbols
CMP(20)
Cp1
Cp2
Operand Data Areas
Cp1: First compare word
IR, SR, AR, DM, HR, TC, LR, #
Cp2: Second compare word
IR, SR, AR, DM, HR, TC, LR, #
When comparing a value to the PV of a timer or counter, the value must be in
BCD.
When the execution condition is OFF, CMP(20) is not executed. When the execution condition is ON, CMP(20) compares Cp1 and Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area.
Placing other instructions between CMP(20) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
CMP(20) cannot be used to compare signed binary data. Use CPS(––) instead.
Refer to 5-17-8 SIGNED BINARY COMPARE – CPS(––) for details.
170
Data Comparison
Flags
Section 5-17
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON if Cp1 equals Cp2.
LE: ON if Cp1 is less than Cp2.
GR: ON if Cp1 is greater than Cp2.
GR
EQ
LE
Flag Address
25505
25506
25507
C1 < C2
OFF
OFF
ON
C1 = C2
OFF
ON
OFF
C1 > C2
ON
OFF
OFF
Example 1:
Saving CMP(20) Results
The following example shows how to save the comparison result immediately. If the content of HR 09 is greater than that of 010, 00200 is turned ON; if the two contents are equal, 00201 is turned ON; if content of HR 09 is less than that of
010, 00202 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary. With this type of programming, 00200, 00201, and 00202 are changed only when CMP(20) is executed.
00000
TR
0
CMP(20)
HR 09
010
25505
25506
25507
Address Instruction
00000
00001
00002
LD
OUT
CMP(20)
00003
00004
LD
AND
Operands
TR
00000
0
HR
TR
010
09
0
25505
00200
Greater Than
00201
Equal
00202
Less Than
Address Instruction
00005
00006
00007
00008
00009
00010
00011
OUT
LD
AND
OUT
LD
AND
OUT
Operands
TR
TR
00200
0
25506
00201
0
25507
00202
Example 2:
Obtaining Indications during Timer Operation
The following example uses TIM, CMP(20), and the LE flag (25507) to produce outputs at particular times in the timer’s countdown. The timer is started by turning ON 00000. When 00000 is OFF, TIM 010 is reset and the second two
CMP(20)s are not executed (i.e., executed with OFF execution conditions). Output 00200 is produced after 100 seconds; output 00201, after 200 seconds; output 00202, after 300 seconds; and output 00204, after 500 seconds.
171
Data Comparison
00000
00200
00201
TIM 010
25507
25507
25507
Section 5-17
The branching structure of this diagram is important in order to ensure that
00200, 00201, and 00202 are controlled properly as the timer counts down. Because all of the comparisons here use to the timer’s PV as reference, the other operand for each CMP(20) must be in 4-digit BCD.
TIM 010
#5000 500.0 s
CMP(20)
TIM 010
#4000
00200
Output at
100 s.
CMP(20)
TIM 010
#3000
00201
Output at
200 s.
CMP(20)
TIM 010
#2000
00202
Output at
300 s.
00204
Output at
500 s.
Address Instruction
00000
00001
LD
TIM
00002 CMP(20)
00003
00004
00005
00006
AND
OUT
LD
CMP(20)
#
Operands
00000
010
5000
TIM
#
TIM
#
010
4000
25507
00200
00200
010
3000
5-17-3 DOUBLE COMPARE – CMPL(60)
Ladder Symbols
Address Instruction
00007
00008
00009
00010
AND
OUT
LD
CMP(20)
00011
00012
00013
00014
AND
OUT
LD
OUT
CMPL(60)
Cp1
Cp2
___
Operands
25507
00201
00201
TIM
#
TIM
010
2000
25507
00202
010
00204
Operand Data Areas
Cp1: First word of first compare word pair
IR, SR, AR, DM, HR, TC, TR
Cp2: First word of second compare word pair
IR, SR, AR, DM, HR, TC, LR
172
Data Comparison
Limitations
Description
Precautions
Flags
Example:
Saving CMPL(60) Results
Section 5-17
Cp1 and Cp1+1 must be in the same data area, as must Cp2 and Cp2+1.
When the execution condition is OFF, CMPL(60) is not executed. When the execution condition is ON, CMPL(60) joins the 4-digit hexadecimal content of
Cp1+1 with that of Cp1, and that of Cp2+1 with that of Cp2 to create two 8-digit hexadecimal numbers, Cp+1,Cp1 and Cp2+1,Cp2. The two 8-digit numbers are then compared and the result is output to the GR, EQ, and LE flags in the SR area.
Placing other instructions between CMPL(60) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
CMPL(60) cannot be used to compare signed binary data. Use CPSL(––) instead. Refer to 5-17-9 DOUBLE SIGNED BINARY COMPARE – CPSL(––) for details.
ER: Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
GR: ON if Cp1+1,Cp1 is greater than Cp2+1,Cp2.
EQ: ON if Cp1+1,Cp1 equals Cp2+1,Cp2.
LE: ON if Cp1+1,Cp1 is less than Cp2+1,Cp2.
The following example shows how to save the comparison result immediately. If the content of HR 10, HR 09 is greater than that of 011, 010, then 00200 is turned
ON; if the two contents are equal, 00201 is turned ON; if content of HR 10, HR 09 is less than that of 011, 010, then 00202 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary.
With this type of programming, 00200, 00201, and 00202 are changed only when CMPL(60) is executed.
00000
TR
0
25505
CMPL(60)
HR 09
010
–––
00200
Greater Than
25506
00201
Equal
25507
Address Instruction
00000
00001
00002
LD
OUT
CMPL(60)
00003 AND
Operands
TR
00000
0
HR 09
010
25505
00202
Less Than
Address Instruction
00004
00005
00006
00007
00008
00009
00010
OUT
LD
AND
OUT
LD
AND
OUT
Operands
TR
TR
00200
0
25506
00201
0
25507
00202
173
Data Comparison
5-17-4 BLOCK COMPARE – BCMP(68)
Section 5-17
Ladder Symbols
BCMP(68)
CD
CB
R
@BCMP(68)
CD
CB
R
Operand Data Areas
CD: Compare data
IR, SR, AR, DM, HR, TC, LR, #
CB: First comparison block word
IR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, TC, LR
Limitations
Description
Flags
174
Each lower limit word in the comparison block must be less than or equal to the upper limit.
When the execution condition is OFF, BCMP(68) is not executed. When the execution condition is ON, BCMP(68) compares CD to the ranges defined by a block consisting of of CB, CB+1, CB+2, ..., CB+31. Each range is defined by two words, the first one providing the lower limit and the second word providing the upper limit. If CD is found to be within any of these ranges (inclusive of the upper and lower limits), the corresponding bit in R is set. The comparisons that are made and the corresponding bit in R that is set for each true comparison are shown below. The rest of the bits in R will be turned OFF.
CB ≤ CD ≤ CB+1
CB+2
≤
CD
≤
CB+3
CB+4
≤
CD
≤
CB+5
CB+6 ≤ CD ≤ CB+7
CB+8
≤
CD
≤
CB+9
CB+10
≤
CD
≤
CB+11
CB+12 ≤ CD ≤ CB+13
CB+14
≤
CD
≤
CB+15
CB+16
≤
CD
≤
CB+17
CB+18 ≤ CD ≤ CB+19
CB+20 ≤ CD ≤ CB+21
CB+22
≤
CD
≤
CB+23
CB+24 ≤ CD ≤ CB+25
CB+26 ≤ CD ≤ CB+27
CB+28
≤
CD
≤
CB+29
CB+30 ≤ CD ≤ CB+31
Bit 00
Bit 01
Bit 02
Bit 03
Bit 04
Bit 05
Bit 06
Bit 07
Bit 08
Bit 09
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
ER: The comparison block (i.e., CB through CB+31) exceeds the data area.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
Data Comparison
Example
00000
CD 001
001 0210
Compare data in IR 001
(which contains 0210) with the given ranges.
Section 5-17
The following example shows the comparisons made and the results provided for BCMP(68). Here, the comparison is made during each cycle when 00000 is
ON.
BCMP(68)
001
HR 10
HR 05
Address Instruction
00000 LD
00001 BCMP(68)
HR
HR
Operands
00000
001
10
05
Lower limits
HR 24
HR 26
HR 28
HR 30
HR 32
HR 34
HR 36
HR 38
HR 40
HR 10
HR 12
HR 14
HR 16
HR 18
HR 20
HR 22
0701
0801
0901
1001
1101
1201
1301
1401
1501
0000
0101
0201
0301
0401
0501
0601
Upper limits
HR 25
HR 27
HR 29
HR 31
HR 33
HR 35
HR 37
HR 39
HR 41
HR 11
HR 13
HR 15
HR 17
HR 19
HR 21
HR 23
0800
0900
1000
1100
1200
1300
1400
1500
1600
0100
0200
0300
0400
0500
0600
0700
R: HR 05
HR 0500
HR 0501
HR 0502
HR 0503
HR 0504
HR 0505
HR 0506
HR 0507
HR 0508
HR 0509
HR 0510
HR 0511
HR 0512
HR 0513
HR 0514
HR 0515
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
5-17-5 TABLE COMPARE – TCMP(85)
Limitations
Description
Flags
Ladder Symbols
TCMP(85)
CD
TB
R
@TCMP(85)
CD
TB
R
Operand Data Areas
CD: Compare data
IR, SR, AR, DM, HR, TC, LR, #
TB: First comparison table word
IR, AR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, TC, LR
TB and TB+15 must be in the same data area.
When the execution condition is OFF, TCMP(85) is not executed. When the execution condition is ON, TCMP(85) compares CD to the content of TB, TB+1,
TB+2, ..., and TB+15. If CD is equal to the content of any of these words, the corresponding bit in R is set, e.g., if the CD equals the content of TB, bit 00 is turned ON, if it equals that of TB+1, bit 01 is turned ON, etc. The rest of the bits in
R will be turned OFF.
ER: The comparison table (i.e., TB through TB+15) exceeds the data area.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
175
Data Comparison
Example
00000
CD: 001
001 0210
Compare the data in IR 001 with the given ranges.
Section 5-17
The following example shows the comparisons made and the results provided for TCMP(85). Here, the comparison is made during each cycle when 00000 is
ON.
TCMP(85)
001
HR 10
HR 05
Address Instruction
00000 LD
00001 TCMP(85)
HR
HR
Operands
00000
001
10
05
Upper limits
HR 10
HR 11
HR 12
HR 13
HR 14
HR 15
HR 16
HR 17
HR 18
HR 19
HR 20
HR 21
HR 22
HR 23
HR 24
HR 25
0100
0200
0210
0400
0500
0600
0210
0800
0900
1000
0210
1200
1300
1400
0210
1600
R: HR 05
HR 0500
HR 0501
HR 0502
HR 0503
HR 0504
HR 0505
HR 0506
HR 0507
HR 0508
HR 0509
HR 0510
HR 0511
HR 0512
HR 0513
HR 0514
HR 0515
1
0
0
0
0
0
1
0
0
1
0
0
0
1
0
0
5-17-6 AREA RANGE COMPARE – ZCP(88)
Limitations
Description
Ladder Symbols
ZCP(88)
CD
LL
UL
Operand Data Areas
CD: Compare data
IR, SR, AR, DM, HR, TC, LR, #
LL: Lower limit of range
IR, SR, AR, DM, HR, TC, LR, #
UL: Upper limit of range
IR, SR, AR, DM, HR, TC, LR, #
LL must be less than or equal to UL.
When the execution condition is OFF, ZCP(88) is not executed. When the execution condition is ON, ZCP(88) compares CD to the range defined by lower limit
LL and upper limit UL and outputs the result to the GR, EQ, and LE flags in the
SR area. The resulting flag status is shown in the following table.
CD < LL
LL ≤ CD ≤ UL
UL < CD
Flag status
GR (SR 25505) EQ (SR 25506) LE (SR 25507)
0 0 1
0 1 0
1 0 0
176
Data Comparison
Precautions
Flags
Example:
Saving ZCP(88) Results
Section 5-17
Placing other instructions between ZCP(88) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
LL is greater than UL.
EQ: ON if LL ≤ CD ≤ UL
LE: ON if CD < LL.
GR: ON if CD > UL.
The following example shows how to save the comparison result immediately. If
IR 100 > AB1F, IR 00200 is turned ON; if #0010 ≤ IR 100 ≤ AB1F, IR 00201 is turned ON; if IR 100 < 0010, IR 00202 is turned ON.
00000
TR
0
ZCP(88)
IR 100
#0010
#AB1F
25505
25506
25507
Address Instruction
00000
00001
00002
LD
OUT
ZCP(88)
00003
00004
LD
AND
IR
#
#
Operands
TR
00000
0
100
0010
AB1F
25505
00200
Greater Than
(above range)
00201
Equal
(within range)
00202
Less Than
(below range)
Address Instruction
00005
00006
00007
00008
00009
00010
00011
OUT
LD
AND
OUT
LD
AND
OUT
Operands
TR
TR
00200
0
25506
00201
0
25507
00202
5-17-7 DOUBLE AREA RANGE COMPARE – ZCPL(––)
Ladder Symbols
ZCPL(––)
CD
LL
UL
Operand Data Areas
CD: Compare data
IR, SR, AR, DM, HR, LR
LL: Lower limit of range
IR, SR, AR, DM, HR, LR
UL: Upper limit of range
IR, SR, AR, DM, HR, LR
Limitations The 8-digit value in LL+1,LL must be less than or equal to UL+1,UL.
CD and CD+1 must be in the same data area, as must LL and LL+1, and UL and
UL+1.
177
Data Comparison
Description
Section 5-17
When the execution condition is OFF, ZCPL(––) is not executed. When the execution condition is ON, ZCPL(––) compares the 8-digit value in CD, CD+1 to the range defined by lower limit LL+1,LL and upper limit UL+1,UL and outputs the result to the GR, EQ, and LE flags in the SR area. The resulting flag status is shown in the following table.
CD , CD+1< LL+1,LL 0
LL+1,LL ≤ CD, CD+1 ≤ UL+1,UL 0
UL+1,UL < CD, CD+1 1
GR
(SR 25505)
0
1
0
Flag status
EQ
(SR 25506)
1
0
0
LE
(SR 25507)
Precautions Placing other instructions between ZCPL(––) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
Flags
Example
ER: Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
LL+1,LL is greater than UL+1,UL.
EQ: ON if LL+1,LL ≤ CD, CD+1 ≤ UL+1,UL
LE: ON if CD, CD+1 < LL+1,LL.
GR: ON if CD, CD+1 > UL+1,UL.
Refer to 5-17-6 AREA RANGE COMPARE – ZCP(88) for an example. The only difference between ZCP(88) and ZCPL(––) is the number of digits in the comparison data.
5-17-8 SIGNED BINARY COMPARE – CPS(––)
Ladder Symbols
CPS(––)
Cp1
Cp2
Operand Data Areas
Cp1: First compare word
IR, SR, AR, DM, HR, TC, LR, #
Cp2: Second compare word
IR, SR, AR, DM, HR, TC, LR, #
Description
Precautions
When the execution condition is OFF, CPS(––) is not executed. When the execution condition is ON, CPS(––) compares the 16-bit (4-digit) signed binary contents in Cp1 and Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area.
Note 1. Refer to page 29 for details on 16-bit signed binary data.
2. Refer to 5-17-2 Compare – CMP(20) for details on saving comparison results.
Placing other instructions between CPS(––) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
178
Data Comparison
Flags
Section 5-17
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON if Cp1 equals Cp2.
LE: ON if Cp1 is less than Cp2.
GR: ON if Cp1 is greater than Cp2.
Cp1 < Cp2
Cp1 = Cp2
Cp1 > Cp2
0
0
1
Flag status
GR (SR 25505) EQ (SR 25506) LE (SR 25505)
0
1
0
1
0
0
5-17-9 DOUBLE SIGNED BINARY COMPARE – CPSL(––)
Ladder Symbols
CPSL(––)
Cp1
Cp2
Operand Data Areas
Cp1: First compare word
IR, SR, AR, DM, HR, TC, LR
Cp2: Second compare word
IR, SR, AR, DM, HR, TC, LR
Limitations
Description
Precautions
Flags
Cp1 and Cp1+1 must be in the same data area, as must Cp2 and Cp2+1.
When the execution condition is OFF, CPSL(––) is not executed. When the execution condition is ON, CPSL(––) compares the 32-bit (8-digit) signed binary contents in Cp1+1, Cp1 and Cp2+1, Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area.
Note 1. Refer to page 29 for details on 32-bit signed binary data.
2. Refer to 5-17-2 Compare – CMP(20) for details on saving comparison results.
Placing other instructions between CPSL(––) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON if Cp1+1, Cp1 equals Cp2+1, Cp2.
LE: ON if Cp1+1, Cp1 is less than Cp2+1, Cp2.
GR: ON if Cp1+1, Cp1 is greater than Cp2+1, Cp2.
Cp1+1, Cp1 < Cp2+1, Cp2
Cp1+1, Cp1 = Cp2+1, Cp2
Cp1+1, Cp1 > Cp2+1, Cp2
Flag status
GR (SR 25505) EQ (SR 25506) LE (SR 25507)
0 0 1
0 1 0
1 0 0
179
Data Conversion Section 5-18
5-18 Data Conversion
The conversion instructions convert word data that is in one format into another format and output the converted data to specified result word(s). Conversions are available to convert between binary (hexadecimal) and BCD, to 7-segment display data, to ASCII, and between multiplexed and non-multiplexed data. All of these instructions change only the content of the words to which converted data is being moved, i.e., the content of source words is the same before and after execution of any of the conversion instructions.
5-18-1 BCD-TO-BINARY – BIN(23)
BIN(23)
S
R
Ladder Symbols
@BIN(23)
S
R
Operand Data Areas
S: Source word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, BIN(23) is not executed. When the execution condition is ON, BIN(23) converts the BCD content of S into the numerically equivalent binary bits, and outputs the binary value to R. Only the content of R is changed; the content of S is left unchanged.
BCD S
Flags
Binary R
BIN(23) can be used to convert BCD to binary so that displays on the Programming Console or any other programming device will appear in hexadecimal rather than decimal. It can also be used to convert to binary to perform binary arithmetic operations rather than BCD arithmetic operations, e.g., when BCD and binary values must be added.
ER: The content of S is not BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is zero.
180
Data Conversion Section 5-18
5-18-2 DOUBLE BCD-TO-DOUBLE BINARY – BINL(58)
Ladder Symbols Operand Data Areas
S: First source word (BCD)
BINL(58) @BINL(58)
S S
IR, SR, AR, DM, HR, TC, LR
R: First result word
R R
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, BINL(58) is not executed. When the execution condition is ON, BINL(58) converts an eight-digit number in S and S+1 into 32-bit binary data, and outputs the converted data to R and R+1.
BCD
S + 1 S
Binary R + 1 R
Flags ER: The contents of S and/or S+1 words are not BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is zero.
5-18-3 BINARY-TO-BCD – BCD(24)
Ladder Symbols
BCD(24)
S
R
@BCD(24)
S
R
Operand Data Areas
S: Source word (binary)
IR, SR, AR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, LR
Description BCD(24) converts the binary (hexadecimal) content of S into the numerically equivalent BCD bits, and outputs the BCD bits to R. Only the content of R is changed; the content of S is left unchanged.
Binary S
BCD
R
BCD(24) can be used to convert binary to BCD so that displays on the Programming Console or any other programming device will appear in decimal rather than hexadecimal. It can also be used to convert to BCD to perform BCD arithmetic operations rather than binary arithmetic operations, e.g., when BCD and binary values must be added.
Note If the content of S exceeds 270F, the converted result would exceed 9999 and
BCD(24) will not be executed. When the instruction is not executed, the content of R remains unchanged.
181
Data Conversion
Signed Binary Data
Section 5-18
BCD(24) cannot be used to convert signed binary data directly to BCD. To convert signed binary data, first determine whether the data is positive or negative. If it is positive, BCD(24) can be used to convert the data to BCD. If it is negative, use the 2’s COMPLEMENT – NEG(––) instruction to convert the data to unsigned binary before executing BCD(24). Refer to page 29 for details on signed binary data.
Flags ER: S is greater than 270F.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is zero.
5-18-4 DOUBLE BINARY-TO-DOUBLE BCD – BCDL(59)
Ladder Symbols
BCDL(59)
S
R
@BCDL(59)
S
R
Operand Data Areas
S: First source word (binary)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Limitations
Description
If the content of S exceeds 05F5E0FF, the converted result would exceed
99999999 and BCDL(59) will not be executed. When the instruction is not executed, the content of R and R+1 remain unchanged.
S and S+1 must be in the same data area as must R and R+1.
BCDL(59) converts the 32-bit binary content of S and S+1 into eight digits of
BCD data, and outputs the converted data to R and R+1.
Binary S + 1 S
Signed Binary Data
Flags
BCD
R + 1 R
BCD(24) cannot be used to convert signed binary data directly to BCD. To convert signed binary data, first determine whether the data is positive or negative. If it is positive, BCD(24) can be used to convert the data to BCD. If it is negative, use the DOUBLE 2’s COMPLEMENT – NEGL(––) instruction to convert the data to unsigned binary before executing BCD(24). Refer to page 29 for details on signed binary data.
ER: Content of R and R+1 exceeds 99999999.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is zero.
182
Data Conversion
5-18-5 HOURS-TO-SECONDS – SEC(65)
SEC(65)
S
R
---
Ladder Symbols
@SEC(65)
S
R
---
Section 5-18
Operand Data Areas
S: Beginning source word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: Beginning result word (BCD)
IR, SR, AR, DM, HR, TC, LR
---: Not used.
Limitations
Description
Flags
Example
S and S+1 must be within the same data area. R and R+1 must be within the same data area. S and S+1 must be BCD and must be in the proper hours/minutes/seconds format.
SEC(65) is used to convert time notation in hours/minutes/seconds to an equivalent in just seconds.
For the source data, the seconds is designated in bits 00 through 07 and the minutes is designated in bits 08 through 15 of S. The hours is designated in S+1. The maximum is thus 9,999 hours, 59 minutes, and 59 seconds.
The result is output to R and R+1. The maximum obtainable value is 35,999,999 seconds.
ER: S and S+1 or R and R+1 are not in the same data area.
S and/or S+1 do not contain BCD.
Number of seconds and/or minutes exceeds 59.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: Turns ON when the result is zero.
When 00000 is OFF (i.e., when the execution condition is ON), the following instruction would convert the hours, minutes, and seconds given in HR 12 and HR
13 to seconds and store the results in DM 0100 and DM 0101 as shown.
00000
HR 12
HR 13
3
2
2
8
0
1
7
5
2,815 hrs, 32 min, 07 s
SEC(65)
HR 12
DM 0100
000
Address Instruction
00000 LD NOT
00001 SEC(65)
HR
DM
Operands
00000
12
0100
000
DM 0100
DM 0101
5
1
9
0
2
1
7
3
10,135,927 s
183
Data Conversion
5-18-6 SECONDS-TO-HOURS – HMS(66)
Ladder Symbols
HMS(66)
S
R
---
@HMS(66)
S
R
---
Section 5-18
Operand Data Areas
S: Beginning source word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: Beginning result word (BCD)
IR, SR, AR, DM, HR, TC, LR
---: Not used.
Limitations
Description
Flags
Example
S and S+1 must be within the same data area. R and R+1 must be within the same data area. S and S+1 must be BCD and must be between 0 and
35,999,999 seconds.
HMS(66) is used to convert time notation in seconds to an equivalent in hours/ minutes/seconds.
The number of seconds designated in S and S+1 is converted to hours/minutes/ seconds and placed in R and R+1.
For the results, the seconds is placed in bits 00 through 07 and the minutes is placed in bits 08 through 15 of R. The hours is placed in R+1. The maximum will be 9,999 hours, 59 minutes, and 59 seconds.
ER: S and S+1 or R and R+1 are not in the same data area.
S and/or S+1 do not contain BCD or exceed 36,000,000 seconds.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: Turns ON when the result is zero.
When 00000 is OFF (i.e., when the execution condition is ON), the following instruction would convert the seconds given in HR 12 and HR 13 to hours, minutes, and seconds and store the results in DM 0100 and DM 0101 as shown.
00000
HR 12
HR 13
5
1
9
0
2
1
7
3
10,135,927 s
DM 0100
DM 0101
3
2
2
8
0
1
7
5
2,815 hrs, 32 min, 07 s
HMS(66)
HR 12
DM 0100
000
Address Instruction
00000 LD NOT
00001 HMS(66)
HR
DM
Operands
00000
12
0100
000
184
Data Conversion
5-18-7 4-TO-16 DECODER – MLPX(76)
Section 5-18
Limitations
Description
4-bit to 16-bit Decoder
Control Word
Ladder Symbols
MLPX(76)
S
C
R
@MLPX(76)
S
C
R
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR
C: Control word
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR, LR
When the leftmost digit of C is 0, the rightmost two digits of C must each be between 0 and 3.
When the leftmost digit of C is 1, the rightmost two digits of C must each be between 0 and 1.
All result words must be in the same data area.
Depending on the value of C, MLPX(76) operates as a 4-bit to 16-bit decoder or an 8-bit to 256-bit decoder.
MLPX(76) operates as a 4-bit to 16-bit decoder when the leftmost digit of C is 0.
The hexadecimal value of the digits in S are used to specify bits in up to 4 result words. The specified bit in each result word is turned on, and the other 15 bits in each word are turned off.
When the execution condition is OFF, MLPX(76) is not executed. When the execution condition is ON, MLPX(76) converts up to four, four-bit hexadecimal digits from S into decimal values from 0 to 15, each of which is used to indicate a bit position. The bit whose number corresponds to each converted value is then turned ON in a result word. If more than one digit is specified, then one bit will be turned ON in each of consecutive words beginning with R. (See examples, below.)
The digits of C are set as shown below. Set the leftmost digit of C to 0 to specify
4-bit to 16-bit decoding.
Digit number: 3 2 1 0
Specifies the first digit to be converted (0 to 3)
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
Not used. Set to 0.
A value of 0 specifies 4-bit to 16-bit decoding.
185
Data Conversion
8-bit to 256-bit Decoder
Control Word
Section 5-18
Some example C values and the digit-to-word conversions that they produce are shown below.
2
3
0
1
S
C: 0010
R
R + 1
2
3
0
1
S
C: 0030
R
R + 1
R + 2
R + 3
S
C: 0031
0
1
2
3
R
R + 1
R + 2
R + 3
0
1
2
3
S
C: 0023
R
R + 1
R + 2
The following is an example of a one-digit decode operation from digit number 1 of S, i.e., here C would be 0001.
Source word
C
Bit C (i.e., bit number 12) turned ON.
First result word
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
The first digit and the number of digits to be converted are designated in C. If more digits are designated than remain in S (counting from the designated first digit), the remaining digits will be taken starting back at the beginning of S. The final word required to store the converted result (R plus the number of digits to be converted) must be in the same data area as R, e.g., if two digits are converted, the last word address in a data area cannot be designated; if three digits are converted, the last two words in a data area cannot be designated.
MLPX(76) operates as an 8-bit to 256-bit decoder when the leftmost digit of C is set to 1. The hexadecimal value of the two bytes in S are used to specify a bit in one or two groups of 16 consecutive result words (256 bits). The specified bit in each group is turned on, and the other 255 bits in the group are turned off.
The digits of C are set as shown below. Set the leftmost digit of C to 1 to specify
8-bit to 256-bit decoding.
Digit number: 3 2 1 0
Specifies the first byte to be converted (0 or 1).
0: Rightmost byte
1: Leftmost byte
Number of bytes to be converted (0 or 1).
0: 1 byte
1: 2 bytes
Not used. Set to 0.
A value of 1 specifies 8-bit to 256-bit decoding.
186
Data Conversion Section 5-18
The 4 possible C values and the conversions that they produce are shown below. (In S, 0 indicates the rightmost byte and 1 indicates the leftmost byte.)
C: 1000 C: 1001
S
0
1
R to R+15
R+16 to R+31
S
0
1
R to R+15
R+16 to R+31
C: 1010 C: 1011
S
0
1
R to R+15
R+16 to R+31
S
0
1
R to R+15
R+16 to R+31
The following is an example of a one-byte decode operation from the rightmost byte of S (C would be 1000 in this case).
Source word
2 C Bit 2C (i.e., bit number 12 in the third word) turned ON.
Bit
15
0 0 0
. . .
Bit
00
0 0 0
. . .
Bit
15
0 0 0 1 0 0 0 0 0 0 0 0 0
Bit
00
Bit
15
0 0 0 0 0 0
. . .
Bit
00
Bit
15
0 0 0 0 0 0
. . .
Bit
00
0 0 0
R+15 R+2 R+1 R
Flags ER: Undefined control word.
The result words are not all in the same data area.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
187
Data Conversion
Example:
4-bit to 16-bit Decoding
00000
Section 5-18
The following program converts three digits of data from LR 20 to bit positions and turns ON the corresponding bits in three consecutive words starting with
HR 10.
MLPX(76)
DM 0020
#0021
HR 10
Address Instruction
00000 LD
00001 MLPX(76)
LR
#
HR
Operands
00000
20
0021
10
S: LR 20
DM 00
DM 01
DM 02
DM 03
DM 04
DM 05
DM 06
DM 07
DM 08
DM 09
DM 10
DM 11
DM 12
DM 13
DM 14
DM 15
1
1
1
1
0
1
1
0
0
0
0
0
R: HR 10
2 2
2 3
2 0
2 1
2 2
2 0
2 1
2 2
2 3
2 0
2 1
2 3
2 0
2 1
2 2
2 3
1
2
3
Not
Converted
15
6
0
HR 1000
HR 1001
HR 1002
HR 1003
HR 1004
HR 1005
HR 1006
HR 1007
HR 1008
HR 1009
HR 1010
HR 1011
HR 1012
HR 1013
HR 1014
HR 1015
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
R+1: HR 11
HR 1100
HR 1101
HR 1102
HR 1103
HR 1104
HR 1105
HR 1106
HR 1107
HR 1108
HR 1109
HR 1110
HR 1111
HR 1112
HR 1113
HR 1114
HR 1115
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
R+2: HR 12
HR 1200
HR 1201
HR 1202
HR 1203
HR 1204
HR 1205
HR 1206
HR 1207
HR 1208
HR 1209
HR 1210
HR 1211
HR 1212
HR 1213
HR 1214
HR 1215
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
5-18-8 16-TO-4 ENCODER – DMPX(77)
Limitations
Description
Ladder Symbols
DMPX(77)
S
R
C
@DMPX(77)
S
R
C
Operand Data Areas
S: First source word
IR, SR, AR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, LR
C: Control Word
IR, SR, AR, DM, HR, TC, LR, #
When the leftmost digit of C is 0, the rightmost two digits of C must each be between 0 and 3.
When the leftmost digit of C is 1, the rightmost two digits of C must each be between 0 and 1.
All source words must be in the same data area.
Depending on the value of C, MLPX(76) operates as a 16-bit to 4-bit encoder or an 256-bit to 8-bit encoder.
188
Data Conversion
16-bit to 4-bit encoder
Control Word
Section 5-18
DMPX(77) operates as a 16-bit to 4-bit encoder when the leftmost digit of C is 0.
When the execution condition is OFF, DMPX(77) is not executed. When the execution condition is ON, DMPX(77) determines the position of the highest ON bit in S, encodes it into single-digit hexadecimal value corresponding to the bit number, then transfers the hexadecimal value to the specified digit in R. The digits to receive the results are specified in C, which also specifies the number of digits to be encoded.
The digits of C are set as shown below. Set the leftmost digit of C to 0 to specify
16-bit to 4-bit encoding.
Digit number: 3 2 1 0
Specifies the first digit in R to receive converted data (0 to 3).
Number of words to be converted (0 to 3).
0: 1 word
1: 2 words
2: 3 words
3: 4 words
Not used. Set to 0.
A value of 0 specifies 16-bit to 4-bit encoding.
Some example C values and the word-to-digit conversions that they produce are shown below.
C: 0011 C: 0030
S
S + 1
R
2
3
0
1
S
S + 1
S + 2
S + 3
R
2
3
0
1
C: 0013 C: 0032
S
S + 1
R
2
3
0
1
S
S + 1
S + 2
S + 3
2
3
R
0
1
The following is an example of a one-digit encode operation to digit number 1 of
R, i.e., here C would be 0001.
First source word
0 0 0 1 0 0 0 1 0 0 0 1 0 1 1 0
C transferred to indicate bit number 12 as the highest ON bit.
Result word
C
Up to four digits from four consecutive source words starting with S may be encoded and the digits written to R in order from the designated first digit. If more digits are designated than remain in R (counting from the designated first digit), the remaining digits will be placed at digits starting back at the beginning of R.
The final word to be converted (S plus the number of digits to be converted) must be in the same data area as SB.
189
Data Conversion
256-bit to 8-bit Encoder
Control Word
Section 5-18
DMPX(77) operates as a 256-bit to 8-bit encoder when the leftmost digit of C is set to 1.
When the execution condition is OFF, DMPX(77) is not executed. When the execution condition is ON, DMPX(77) determines the position of the highest (leftmost) ON bit in the group of 16 source words from S to S+15 or S+16 to S+31, encodes it into a two-digit hexadecimal value corresponding to the location of the bit among the 256 bits in the group, then transfers the hexadecimal value to the specified byte in R. The byte to receive the result is specified in C, which also specifies the number of bytes to be encoded.
The digits of C are set as shown below. Set the leftmost digit of C to 1 to specify
256-bit to 8-bit decoding.
Digit number: 3 2 1 0
Specifies the first byte in R to receive converted data (0 or 1).
0: Rightmost byte
1: Leftmost byte
Number of bytes to be encoded (0 or 1).
0: 1 byte
1: 2 bytes
Not used. Set to 0.
A value of 1 specifies 256-bit to 8-bit encoding.
C: 1000
S to S+15
S+16 to S+31
R
0
1
Three possible C values and the conversions that they produce are shown below. (In R, 0 indicates the rightmost byte and 1 indicates the leftmost byte.)
C: 1010
S to S+15
S+16 to S+31
R
0
1
C: 1011
S to S+15
S+16 to S+31
R
0
1
The following is an example of a one-byte encode operation to the rightmost byte of R (C would be 1000 in this case).
Bit
15
0 0 0 0 1 1 1 1 1 1 1 0 1 1
Bit
00
Bit
15
0 0 0 1 1
. . .
Bit
00
0 1 0
. . .
Bit
15
1 1 1
. . .
Bit
00
0 0 0
S+15 S+14 S
Result word
F B Bit FB (bit 251 of 0 to 255) is the highest ON bit of the
16-word group, so FB is written to the rightmost bit of R.
Flags ER: Undefined control word.
The source words are not all in the same data area.
Content of a source word is zero. (There isn’t an ON bit in the source words.)
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
190
Data Conversion
Example:
16-bit to 4-bit Encoding
00000
IR 010
01000
:
01011 1
01012 0
: : :
01015 0
LR 10
LR 1000
LR 1001 1
LR 1002 0
: :
: :
LR 1015 0
:
:
Section 5-18
When 00000 is ON, the following diagram encodes IR words 010 and 011 to the first two digits of HR 20 and then encodes LR 10 and 11 to the last two digits of
HR 20. Although the status of each source word bit is not shown, it is assumed that the bit with status 1 (ON) shown is the highest bit that is ON in the word.
DMPX(77)
010
HR 20
#0010
DMPX(77)
LR 10
HR 20
#0012
Address Instruction
00000 LD
00001 DMPX(77)
00002 DMPX(77)
HR
#
LR
HR
#
Operands
00000
010
20
0010
10
20
0012
IR 011
01100
:
01109 1
01110 0
: : :
01115 0
HR 20
Digit 0
Digit 1
Digit 2
Digit 3
1
8
B
9
LR 11
LR 1100
:
LR 1108 1
LR 1109 0
: : :
LR 1115 0
5-18-9 7-SEGMENT DECODER – SDEC(78)
Limitations
Description
Ladder Symbols
SDEC(78)
S
Di
D
@SDEC(78)
S
Di
D
Operand Data Areas
S: Source word (binary)
IR, SR, AR, DM, HR, TC, LR
Di: Digit designator
IR, SR, AR, DM, HR, TC, LR, #
D: First destination word
IR, SR, AR, DM, HR, LR
Di must be within the values given below
All destination words must be in the same data area.
When the execution condition is OFF, SDEC(78) is not executed. When the execution condition is ON, SDEC(78) converts the designated digit(s) of S into the equivalent 8-bit, 7-segment display code and places it into the destination word(s) beginning with D.
191
Data Conversion
Digit Designator
Section 5-18
Any or all of the digits in S may be converted in sequence from the designated first digit. The first digit, the number of digits to be converted, and the half of D to receive the first 7-segment display code (rightmost or leftmost 8 bits) are designated in Di. If multiple digits are designated, they will be placed in order starting from the designated half of D, each requiring two digits. If more digits are designated than remain in S (counting from the designated first digit), further digits will be used starting back at the beginning of S.
The digits of Di are set as shown below.
Digit number: 3 2 1 0
Specifies the first digit to receive converted data (0 to 3).
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
First half of D to be used.
0: Rightmost 8 bits (1st half)
1: Leftmost 8 bits (2nd half)
Not used; set to 0.
Some example Di values and the 4-bit binary to 7-segment display conversions that they produce are shown below.
S digits
Di: 0011
0
1
2
3
D
1st half
2nd half
S digits
Di: 0112
0
1
2
3
D
1st half
2nd half
D+1
1st half
2nd half
Di: 0030
S digits
0
1
2
3
D
1st half
2nd half
D+1
1st half
2nd half
S digits
0
Di: 0130
1
2
3
D
1st half
2nd half
D+1
1st half
2nd half
D+2
1st half
2nd half
192
Di
1
0
1 x10 2
1
1
1
0 x10 3
1
1
0
1
0 x10 0
0
0
0 x10 1
0
Data Conversion
Example
1: Second digit
0: One digit
Not used.
Section 5-18
The following example shows the data to produce an 8. The lower case letters show which bits correspond to which segments of the 7-segment display. The table underneath shows the original data and converted code for all hexadecimal digits.
0 or 1: bits 00 through 07 or
08 through 15.
S
0
1
2
3
1
1
1
0
1
1
0
1
0
1
0
0
0
0
0
1
2 2
2 3
2 0
2 1
2 2
2 3
2 0
2 1
2 2
2 3
2 0
2 1
2 2
2 3
2 0
2 1
8
D
Bit 00 or bit 08
1
1
1
Bit 07 or bit 15
0
1
1
1
1 f e c d g a b f e a g b c d
Flags
A
B
8
9
C
D
E
F
5
6
7
0
1
2
3
4
Digit
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
Original data
Bits
0
0
0
0
1
1
1
1
1
1
1
0
0
0
0
1
1
1
0
0
0
0
1
1
0
1
1
0
0
1
1
0
0
1
0
1
0
1
0
1
1
0
1
0
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
–
1
1
1
1
1
0
1
1
1
1
1
1
0
0
0
1
1
1
1
0
1
1
1
1
0
1
0
1
0
1
0
0
1
1
1
1
0
1
1
1
1
1
0
0
0
1
1
1 g
Converted code (segments) f e d c b
0
1
1
1
1
1
1
0
1
1
0
1
0
1
1
0
1
1
1
1
0
1
0
0
1
1
1
1
1
0
1
1
1
0
1
1
0
1
0
0
0
0
1
1
1
1
1
1
1
0
1
1
1
0
1
1
1
1
1
1
0
1
1
0 a
Display
ER: Incorrect digit designator, or data area for destination exceeded
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
193
Data Conversion
5-18-10 ASCII CONVERT – ASC(86)
Limitations
Description
Digit Designator
Section 5-18
ASC(86)
S
Di
D
Ladder Symbols
@ASC(86)
S
Di
D
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR
Di: Digit designator
IR, SR, AR, DM, HR, TC, LR, #
D: First destination word
IR, SR, AR, DM, HR, LR
Di must be within the values given below
All destination words must be in the same data area.
When the execution condition is OFF, ASC(86) is not executed. When the execution condition is ON, ASC(86) converts the designated digit(s) of S into the equivalent 8-bit ASCII code and places it into the destination word(s) beginning with D.
Any or all of the digits in S may be converted in order from the designated first digit. The first digit, the number of digits to be converted, and the half of D to receive the first ASCII code (rightmost or leftmost 8 bits) are designated in Di. If multiple digits are designated, they will be placed in order starting from the designated half of D, each requiring two digits. If more digits are designated than remain in S (counting from the designated first digit), further digits will be used starting back at the beginning of S.
Refer to Appendix I for a table of extended ASCII characters.
The digits of Di are set as shown below.
Digit number: 3 2 1 0
Specifies the first digit to be converted (0 to 3).
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
First half of D to be used.
0: Rightmost 8 bits (1st half)
1: Leftmost 8 bits (2nd half)
Parity 0: none,
1: even,
2: odd
194
Data Conversion Section 5-18
Some examples of Di values and the 4-bit binary to 8-bit ASCII conversions that they produce are shown below.
S
0
1
2
3
Di: 0011
D
1st half
2nd half
S
2
3
0
1
Di: 0112
D
1st half
2nd half
D+1
1st half
2nd half
S
0
1
2
3
Di: 0030
D
1st half
2nd half
D+1
1st half
2nd half
S
0
1
2
3
Di: 0130
D
1st half
2nd half
D+1
1st half
2nd half
D+2
1st half
2nd half
Parity The leftmost bit of each ASCII character (2 digits) can be automatically adjusted for either even or odd parity. If no parity is designated, the leftmost bit will always be zero.
When even parity is designated, the leftmost bit will be adjusted so that the total number of ON bits is even, e.g., when adjusted for even parity, ASCII “31”
(00110001) will be “B1” (10110001: parity bit turned ON to create an even number of ON bits); ASCII “36” (00110110) will be “36” (00110110: parity bit turned
OFF because the number of ON bits is already even). The status of the parity bit does not affect the meaning of the ASCII code.
When odd parity is designated, the leftmost bit of each ASCII character will be adjusted so that there is an odd number of ON bits.
Flags ER: Incorrect digit designator, or data area for destination exceeded.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
5-18-11 ASCII-TO-HEXADECIMAL – HEX(––)
HEX(––)
S
Di
D
Ladder Symbols
@HEX(––)
S
Di
D
Operand Data Areas
S: First source word
IR, SR, AR, DM, HR, TC, LR
Di: Digit designator
IR, SR, AR, DM, HR, TC, LR
D: Destination word
IR, SR, AR, DM, HR, LR
195
Data Conversion
Limitations
Description
Digit Designator
Section 5-18
Di must be within the values given below.
All source words must be in the same data area.
Bytes in the source words must contain the ASCII code equivalent of hexadecimal values, i.e., 30 to 39 (0 to 9), 41 to 46 (A to F), or 61 to 66 (a to f).
When the execution condition is OFF, HEX(––) is not executed. When the execution condition is ON, HEX(––) converts the designated byte(s) of ASCII code from the source word(s) into the hexadecimal equivalent and places it into D.
Up to 4 ASCII codes may be converted beginning with the designated first byte of S. The converted hexadecimal values are then placed in D in order from the designated digit. The first byte (rightmost or leftmost 8 bits), the number of bytes to be converted, and the digit of D to receive the first hexadecimal value are designated in Di. If multiple bytes are designated, they will be converted in order starting from the designated half of S and continuing to S+1 and S+2, if necessary.
If more digits are designated than remain in D (counting from the designated first digit), further digits will be used starting back at the beginning of D. Digits in D that do not receive converted data will not be changed.
The digits of Di are set as shown below.
Digit number: 3 2 1 0
Specifies the first digit of D to be used (0 to 3).
Number of bytes to be converted (0 to 3)
0: 1 byte (2-digit ASCII code)
1: 2 bytes
2: 3 bytes
3: 4 bytes
First byte of S to be used.
0: Rightmost 8 bits (1 st byte)
1: Leftmost 8 bits (2 nd byte)
Parity 0: none
1: even
2: odd
196
Data Conversion
ASCII Code Table
Parity
Section 5-18
Some examples of Di values and the 8-bit ASCII to 4-bit hexadecimal conversions that they produce are shown below.
S
1 st byte
2 nd byte
Di: 0011
D
0
1
2
3
S
1 st byte
2 nd byte
Di: 0030
S+1
1 st byte
2 nd byte
D
0
1
2
3
S
1 st byte
2 nd byte
Di: 0023
S+1
1 st byte
2 nd byte
D
0
1
2
3
S
1 st byte
2 nd byte
Di: 0133
S+1
1 st byte
2 nd byte
S+2
1 st byte
2 nd byte
D
2
3
0
1
The following table shows the ASCII codes before conversion and the hexadecimal values after conversion. Refer to Appendix I for a table of ASCII characters.
36
37
38
39
41
42
43
44
45
46
32
33
34
35
ASCII Code
30
31
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
1
1
0
1
1
0
0
0
0
0
0
0
1
0
0
1
1
1
1
1
0
0
0
0
0
0
Original data
Bit status (See note.)
1
1
1
1
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
0
0
1
0
0
0
1
1
1
1
0
0
0
0
0
0
1
1
1
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Note The leftmost bit of each ASCII code is adjusted for parity.
8
9
A
6
7
B
C
D
E
F
2
3
4
5
0
1
Digit
1
1
1
0
0
1
1
1
1
1
0
0
0
0
Converted data
Bits
0
0
0
0
0
0
0
0
1
1
1
1
0
0
0
0
0
1
1
1
1
0
1
1
0
0
1
1
1
0
1
1
0
1
0
1
0
0
1
0
1
0
1
0
1
1
0
1
0
1
The leftmost bit of each ASCII character (2 digits) is automatically adjusted for either even or odd parity.
With no parity, the leftmost bit should always be zero. With odd or even parity, the leftmost bit of each ASCII character should be adjusted so that there is an odd or even number of ON bits.
If the parity of the ASCII code in S does not agree with the parity specified in Di, the ER Flag (SR 25503) will be turned ON and the instruction will not be executed.
197
Data Conversion
Flags
Example
00000
Section 5-18
ER: Incorrect digit designator, or data area for destination exceeded.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
In the following example, the 2 nd byte of LR 10 and the 1 st byte of LR 11 are converted to hexadecimal values and those values are written to the first and second bytes of IR 010.
@HEX(––)
LR 10
HR 10
010
Address Instruction
00000 LD
00001 @HEX(––)
LR
HR
Operands
00000
10
10
010
HR 10 0 1 1 0
LR 12 3 5 3 4 LR 11 4 2 3 2 LR 10 3 1 3 0
Conversion to hexadecimal
010 0 0 2 1
5-18-12 SCALING – SCL(––)
Limitations
Description
SCL(––)
S
P1
R
Ladder Symbols
@SCL(––)
S
P1
R
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR, #
P1: First parameter word
IR, SR, AR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, LR
P1 and P1+2 must be BCD.
P1 through P1+3 must be in the same data area.
P1+1 and P1+3 must not be set to the same value.
SCL(––) is used to linearly convert a 4-digit hexadecimal value to a 4-digit BCD value. Unlike BCD(24), which converts a 4-digit hexadecimal value to its 4-digit
BCD equivalent (S hex
→ S
BCD
), SCL(––) can convert the hexadecimal value according to a specified linear relationship. The conversion line is defined by two points specified in the parameter words P1 to P1+3.
When the execution condition is OFF, SCL(––) is not executed. When the execution condition is ON, SCL(––) converts the 4-digit hexadecimal value in S to the
4-digit BCD value on the line defined by points (P1, P1+1) and (P1+2, P1+3) and places the result in R. The result is rounded off to the nearest integer. If the result is less than 0000, then 0000 is written to R, and if the result is greater than 9999, then 9999 is written to R.
198
Data Conversion
Flags
Example
00000
Section 5-18
The following table shows the functions and ranges of the parameter words:
Parameter
P1
P1+1
P1+2
P1+3
Function Range
BCD point #1 (A
Y
) 0000 to 9999
Hex. point #1 (A
X
) 0000 to FFFF
BCD point #2 (B
Y
) 0000 to 9999
Hex. point #2 (B
X
) 0000 to FFFF
Comments
---
Do not set P1+1=P1+3.
---
Do not set P1+3=P1+1.
The following diagram shows the source word, S, converted to D according to the line defined by points (A
Y
, A
X
) and (B
Y
, B
X
).
Value after conversion
(BCD)
B
Y
R
A
Y
Value before conversion
(Hexadecimal)
A
X
S B
X
The results can be calculated by first converting all values to BCD and then using the following formula.
Results = B
Y
– [(B
Y
– A
Y
)/(B
X
– A
X
) X (B
X
– S)]
ER: The value in P1+1 equals that in P1+3.
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
P1 and P1+3 are not in the same data area, or other setting error.
EQ: ON when the result, R, is 0000.
When 00000 is turned ON in the following example, the BCD source data in DM
0100 (#0100) is converted to hexadecimal according to the parameters in DM
0150 to DM 0153. The result (#0512) is then written to DM 0200.
@SCL(––)
DM 0100
DM 0150
DM 0200
Address Instruction
00000 LD
00001 @SCL(––)
DM
DM
DM
Operands
00000
0100
0150
0200
DM 0150 0010
DM 0151 0005
DM 0152 0050
DM 0153 0019
DM 0100 0100
DM 0200 0512
199
Data Conversion
5-18-13 COLUMN TO LINE – LINE(63)
Limitations
Description
Section 5-18
Ladder Symbols
LINE(63)
S
C
D
@LINE(63)
S
C
D
Operand Data Areas
S: First word of 16 word source set
IR, SR, AR, DM, HR, TC, LR
C: Column bit designator (BCD)
IR, SR, AR, DM, HR, TC, LR, #
D: Destination word
IR, SR, AR, DM, HR, TC, LR
S and S+15 must be in the same data area.
C must be between #0000 and #0015.
When the execution condition is OFF, LINE(63) is not executed. When the execution condition is ON, LINE(63) copies bit column C from the 16-word set (S to
S+15) to the 16 bits of word D (00 to 15).
S
S+1
S+2
S+3
.
.
.
Bit
15
C
Bit
00
0 0 0 0 1 1 1 0 0 0 1 0 0 0 0 1
1 1 0 1 0 0 1 0 0 1 1 1 0 0 0 1
0 0 0 1 1 0 1 1 0 0 1 0 0 1 1 1
1 0 0 0 0 0 1 1 0 0 0 0 0 1 1 1
.
.
.
.
.
.
.
.
.
S+15 0 1 1 1 0 0 0 1 1 0 0 0 1 0 1 0
D
Bit
15
0
. . .
0 1 1 1
Bit
00
Flags
Example
00000
ER: The column bit designator C is not BCD, or it is specifying a non-existent bit (i.e., bit specification must be between 00 and 15).
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of D is zero; otherwise OFF.
The following example shows how to use LINE(63) to move bit column 07 from the set (IR 100 to IR 115) to DM 0100.
LINE(63)
100
#0007
DM 0100
Address Instruction
00000 LD
00001 LINE(63)
#
DM
Operands
00000
100
0007
0100
200
Data Conversion
5-18-14 LINE TO COLUMN – COLM(64)
Limitations
Description
Section 5-18
Ladder Symbols
COLM(64)
S
D
C
@COLM(64)
S
D
C
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR
D: First word of the destination set
IR, AR, DM, HR, TC, LR
C: Column bit designator (BCD)
IR, SR, AR, DM, HR, TC, LR, #
D and D+15 must be in the same data area.
C must be between #0000 and #0015.
When the execution condition is OFF, COLM(64) is not executed. When the execution condition is ON, COLM(64) copies the 16 bits of word S (00 to 15) to the column of bits, C, of the 16-word set (D to D+15).
S
Bit
15
0
.
.
.
.
.
.
.
Bit
00
0 1 1 1
D
D+1
D+2
D+3
.
.
.
Bit
15
C
0 0 0 0 1 1 1 0 0 0 1 0 0 0 0 1
1 1 0 1 0 0 1 0 0 1 1 1 0 0 0 1
0 0 0 1 1 0 1 1 0 0 1 0 0 1 1 1
1 0 0 0 0 0 1 1 0 0 0 0 0 1 1 1
.
.
.
.
.
.
.
.
.
Bit
00
D+15 0 1 1 1 0 0 0 1 1 0 0 0 1 0 1 0
Flags
Example
00000
ER: The bit designator C is not BCD, or it is specifying a non-existent bit (i.e., bit specification must be between 00 and 15).
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of S is zero; otherwise OFF.
The following example shows how to use COLM(64) to move the contents of word DM 0100 (00 to 15) to bit column 15 of the set (DM 0200 to DM 0215).
COLM(64)
DM 0100
DM 0200
#0015
Address Instruction
00000 LD
00001 COLM(64)
DM
DM
#
Operands
00000
0100
0200
0015
201
Data Conversion
5-18-15 2’S COMPLEMENT – NEG(––)
NEG(––)
S
R
---
Ladder Symbols
@NEG(––)
S
R
---
Description
Flags
Example
Section 5-18
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
Converts the four-digit hexadecimal content of the source word (S) to its 2’s complement and outputs the result to the result word (R). This operation is effectively the same as subtracting S from 0000 and outputting the result to R.
If the content of S is 0000, the content of R will also be 0000 after execution, and
EQ (SR 25506) will be turned on.
If the content of S is 8000, the content of R will also be 8000 after execution, and
UF (SR 25405) will be turned on.
Note Refer to page 29 for details on 16-bit signed binary data.
ER: Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of S is 0000; otherwise OFF.
UF: ON when the content of S is 8000; otherwise OFF.
The following example shows how to use NEG(––) to find the 2’s complement of the hexadecimal value 001F and output the result to DM 0020.
00000
NEG(––)
#001F
DM 0020
---
Address Instruction
00000 LD
00001 NEG(––)
#
DM
Operands
00000
001F
0020
–
#0000
#001F
#FFE1 Output to DM 0020.
202
Data Conversion
5-18-16 DOUBLE 2’S COMPLEMENT – NEGL(––)
Ladder Symbols
NEGL(––)
S
R
---
@NEGL(––)
S
R
---
Section 5-18
Operand Data Areas
S: First source word
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Limitations
Description
Flags
Example
S and S+1 must be in the same data area, as must R and R+1.
Converts the eight-digit hexadecimal content of the source words (S and S+1) to its 2’s complement and outputs the result to the result words (R and R+1). This operation is effectively the same as subtracting the eight-digit content S and S+1 from $0000 0000 and outputting the result to R and R+1.
If the content of S is 0000 0000, the content of R will also be 0000 0000 after execution and EQ (SR 25506) will be turned on.
If the content of S is 8000 0000, the content of R will also be 8000 0000 after execution and UF (SR 25405) will be turned on.
Note Refer to page 29 for details on 32-bit signed binary data.
ER: Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of S+1, S is 0000 0000; otherwise OFF.
UF: ON when the content of S+1, S is 8000 0000; otherwise OFF.
The following example shows how to use NEGL(––) to find the 2’s complement of the hexadecimal value in LR 21, LR 20 (001F FFFF) and output the result to
DM 0021, DM 0020.
00000
NEG(––)
LR20
DM 0020
---
Address Instruction
00000 LD
00001 NEGL(––)
LR
DM
Operands
00000
20
0020
0000 0000
S: LR 20
–
S+1: LR 21
001F FFFF
R+1: DM 0021 R: DM 0020
FFE0 0001
203
BCD Calculations
5-19 BCD Calculations
The BCD calculation instructions – INC(38), DEC(39), ADD(30), ADDL(54),
SUB(31), SUBL(55), MUL(32), MULL(56), DIV(33), DIVL(57), FDIV(79), and
ROOT(72) – all perform arithmetic operations on BCD data.
For INC(38) and DEC(39) the source and result words are the same. That is, the content of the source word is overwritten with the instruction result. All other instructions change only the content of the words in which results are placed, i.e., the contents of source words are the same before and after execution of any of the other BCD calculation instructions.
STC(40) and CLC(41), which set and clear the carry flag, are included in this group because most of the BCD operations make use of the Carry Flag (CY) in their results. Binary calculations and shift operations also use CY.
The addition and subtraction instructions include CY in the calculation as well as in the result. Be sure to clear CY if its previous status is not required in the calculation, and to use the result placed in CY, if required, before it is changed by execution of any other instruction.
5-19-1 INCREMENT – INC(38)
Ladder Symbols
Section 5-19
INC(38)
Wd
@INC(38)
Wd
Operand Data Areas
Wd: Increment word (BCD)
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, INC(38) is not executed. When the execution condition is ON, INC(38) increments Wd, without affecting Carry (CY).
Flags ER: Wd is not BCD
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the incremented result is 0.
5-19-2 DECREMENT – DEC(39)
Ladder Symbols
DEC(39)
Wd
@DEC(39)
Wd
Operand Data Areas
Wd: Decrement word (BCD)
IR, SR, AR, DM, HR, LR
Description
Flags
When the execution condition is OFF, DEC(39) is not executed. When the execution condition is ON, DEC(39) decrements Wd, without affecting CY. DEC(39) works the same way as INC(38) except that it decrements the value instead of incrementing it.
ER: Wd is not BCD
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the decremented result is 0.
204
BCD Calculations
5-19-3 SET CARRY – STC(40)
Section 5-19
STC(40)
Ladder Symbols
@STC(40)
When the execution condition is OFF, STC(40) is not executed.When the execution condition is ON, STC(40) turns ON CY (SR 25504).
Note Refer to Appendix C Error and Arithmetic Flag Operation for a table listing the instructions that affect CY.
5-19-4 CLEAR CARRY – CLC(41)
Ladder Symbols
CLC(41) @CLC(41)
When the execution condition is OFF, CLC(41) is not executed.When the execution condition is ON, CLC(41) turns OFF CY (SR 25504).
CLEAR CARRY is used to reset (turn OFF) CY (SR 25504) to “0”.
CY is automatically reset to “0” when END(01) is executed at the end of each cycle.
Note Refer to Appendix C Error and Arithmetic Flag Operation for a table listing the instructions that affect CY.
5-19-5 BCD ADD – ADD(30)
Ladder Symbols
ADD(30)
Au
Ad
R
@ADD(30)
Au
Ad
R
Operand Data Areas
Au: Augend word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Ad: Addend word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
Description When the execution condition is OFF, ADD(30) is not executed. When the execution condition is ON, ADD(30) adds the contents of Au, Ad, and CY, and places the result in R. CY will be set if the result is greater than 9999.
Au + Ad + CY CY R
Flags ER: Au and/or Ad is not BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when there is a carry in the result.
EQ: ON when the result is 0.
205
BCD Calculations
Example
Section 5-19
If 00002 is ON, the program represented by the following diagram clears CY with
CLC(41), adds the content of LR 25 to a constant (6103), places the result in DM
0100, and then moves either all zeros or 0001 into DM 0101 depending on the status of CY (25504). This ensures that any carry from the last digit is preserved in R+1 so that the entire result can be later handled as eight-digit data.
00002
TR 0
CLC(41)
Address Instruction
00000 LR
00001 OUT
00002 CLC(41)
00003 AND(30)
Operands
TR
00002
0
25504
25504
ADD(30)
LR 25
#6103
DM 0100
MOV(21)
#0001
DM 0101
MOV(21)
#0000
DM 0101
00004 AND
00005 MOV(21)
00006 LD
00007 AND NOT
00008 MOV(21)
LR
#
DM
#
DM
TR
25
6103
0100
25504
0001
0101
0
25504
0000
0101
#
DM
Although two ADD(30) can be used together to perform eight-digit BCD addition,
ADDL(54) is designed specifically for this purpose.
5-19-6 DOUBLE BCD ADD – ADDL(54)
Ladder Symbols
ADDL(54)
Au
Ad
R
@ADDL(54)
Au
Ad
R
Operand Data Areas
Au: First augend word (BCD)
IR, SR, AR, DM, HR, TC, LR
Ad: First addend word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Limitations
Description
Each of the following pairs must be in the same data area: Au and Au+1, Ad and
Ad+1, and R and R+1.
When the execution condition is OFF, ADDL(54) is not executed. When the execution condition is ON, ADDL(54) adds the contents of CY to the 8-digit value in
Au and Au+1 to the 8-digit value in Ad and Ad+1, and places the result in R and
R+1. CY will be set if the result is greater than 99999999.
Au + 1
Ad + 1
Au
Ad
CY
CY
+
R + 1 R
206
BCD Calculations
Flags
Example
00000
Section 5-19
ER: Au and/or Ad is not BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when there is a carry in the result.
EQ: ON when the result is 0.
When 00000 is ON, the following program adds two 12-digit numbers, the first contained in LR 20 through LR 22 and the second in DM 0012. The result is placed in LR 10 through HR 13. In the second addition (using ADD(30)), any carry from the first addition is included. The carry from the second addition is placed in HR 13 by using @ADB(50) (see 5-20-1 BINARY ADD – ADB(50)) with two all-zero constants to indirectly place the content of CY into HR 13.
CLC(41)
@ADDL(54)
LR 20
DM 0010
HR 10
@ADD(30)
LR 22
DM 0012
HR 12
@ADB(50)
#0000
#0000
HR 13
Address Instruction
00000 LD
00001 CLC(41)
00002 @ADDL(54)
00003
00004
@ADD(30)
@ADB(50)
LR
DM
HR
LR
DM
HR
#
#
HR
Operands
00000
20
0010
10
22
0012
12
0000
0000
13
5-19-7 BCD SUBTRACT – SUB(31)
Description
SUB(31)
Mi
Su
R
Ladder Symbols
@SUB(31)
Mi
Su
R
Operand Data Areas
Mi: Minuend word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Su: Subtrahend word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, SUB(31) is not executed. When the execution condition is ON, SUB(31) subtracts the contents of Su and CY from Mi, and places the result in R. If the result is negative, CY is set and the 10’s complement of the actual result is placed in R. To convert the 10’s complement to the true result, subtract the content of R from zero (see example below).
Mi – Su – CY CY R
Note The 2’s COMPLEMENT – NEG(––) instruction can be used to convert binary data only, it cannot be used with BCD data.
207
BCD Calculations
Flags
Section 5-19
ER: Mi and/or Su is not BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the result is negative, i.e., when Mi is less than Su plus CY.
EQ: ON when the result is 0.
!
Caution Be sure to clear the carry flag with CLC(41) before executing SUB(31) if its previous status is not required, and check the status of CY after doing a subtraction with SUB(31). If CY is ON as a result of executing SUB(31) (i.e., if the result is negative), the result is output as the 10’s complement of the true answer. To convert the output result to the true value, subtract the value in R from 0.
Example When 00002 is ON, the following ladder program clears CY, subtracts the contents of DM 0100 and CY from the content of 010 and places the result in HR 20.
If CY is set by executing SUB(31), the result in HR 20 is subtracted from zero
(note that CLC(41) is again required to obtain an accurate result), the result is placed back in HR 20, and HR 2100 is turned ON to indicate a negative result.
If CY is not set by executing SUB(31), the result is positive, the second subtraction is not performed, and HR 2100 is not turned ON. HR 2100 is programmed as a self-maintaining bit so that a change in the status of CY will not turn it OFF when the program is recycled.
In this example, differentiated forms of SUB(31) are used so that the subtraction operation is performed only once each time 00002 is turned ON. When another subtraction operation is to be performed, 00002 will need to be turned OFF for at least one cycle (resetting HR 2100) and then turned back ON.
00002
TR 0
25504
25504
HR 2100
CLC(41)
@SUB(31)
010
DM 0100
HR 20
CLC(41)
First subtraction
@SUB(31)
#0000
HR 20
HR 21
HR 2100
Turned ON to indicate negative result.
Second subtraction
Address Instruction
00000 LD
00001 OUT
00002 CLC(41)
00003 @SUB(31)
Operands
TR
00002
0
DM
HR
010
0100
20
25504 00004 AND
00005 CLC(41)
00006 @SUB(31)
00007 LD
00008 AND
00009 OR
00010 OUT
#
HR
HR
TR
HR
HR
0000
20
20
0
25504
2100
2100
The first and second subtractions for this diagram are shown below using example data for 010 and DM 0100.
208
BCD Calculations Section 5-19
Note The actual SUB(31) operation involves subtracting Su and CY from 10,000 plus
Mi. For positive results the leftmost digit is truncated. For negative results the
10s complement is obtained. The procedure for establishing the correct answer is given below.
First Subtraction
IR 010 1029
DM 0100
CY – 0
– 3452
HR 20 7577 (1029 + (10000 – 3452))
CY
Second Subtraction
0000
HR 20 –7577
CY –0
HR 20 2423 (0000 + (10000 – 7577))
CY 1 (negative result)
In the above case, the program would turn ON HR 2100 to indicate that the value held in HR 20 is negative.
5-19-8 DOUBLE BCD SUBTRACT – SUBL(55)
Ladder Symbols
SUBL(55)
Mi
Su
R
@SUBL(55)
Mi
Su
R
Operand Data Areas
Mi: First minuend word (BCD)
IR, SR, AR, DM, HR, TC, LR
Su: First subtrahend word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Limitations
Description
Each of the following pairs must be in the same data area: Mi and Mi+1, Su and
Su+1, and R and R+1.
When the execution condition is OFF, SUBL(55) is not executed. When the execution condition is ON, SUBL(55) subtracts CY and the 8-digit contents of Su and Su+1 from the 8-digit value in Mi and Mi+1, and places the result in R and
R+1. If the result is negative, CY is set and the 10’s complement of the actual result is placed in R. To convert the 10’s complement to the true result, subtract the content of R from zero. Since an 8-digit constant cannot be directly entered, use the BSET(71) instruction (see 5-16-3 BLOCK SET – BSET(71)) to create an
8-digit constant.
Mi + 1 Mi
Su + 1 Su
CY
–
R + 1
CY
R
Note The DOUBLE 2’s COMPLEMENT – NEGL(––) instruction can be used to convert binary data only, it cannot be used with BCD data.
209
BCD Calculations
Flags
Section 5-19
ER: Mi, M+1,Su, or Su+1 are not BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the result is negative, i.e., when Mi is less than Su.
EQ: ON when the result is 0.
The following example works much like that for single-word subtraction. In this example, however, BSET(71) is required to clear the content of DM 0000 and
DM 0001 so that a negative result can be subtracted from 0 (inputting an 8-digit constant is not possible).
Example
00003
TR 0
25504
25504
HR 2100
CLC(41)
@SUBL(55)
HR 20
120
DM 0100
@BSET(71)
#0000
DM 0000
DM 0001
CLC(41)
First subtraction
@SUBL(55)
DM 0000
DM 0100
DM 0100
HR 2100
Turned ON to indicate negative result.
Second subtraction
Address Instruction
00000
00001
00002
00003
LD
OUT
CLC(41)
@SUBL(55)
TR
Operands
00003
0
00004
00005
AND
@BSET(71)
HR
DM
20
120
0100
25504
#
DM
DM
0000
0000
0001
Address Instruction
00006
00007
CLC(41)
@SUBL(55)
Operands
DM
DM
DM
TR 00008
00009
00010
00011
LD
AND
OR
OUT
HR
HR
0000
0100
0100
0
25504
2100
2100
210
BCD Calculations
5-19-9 BCD MULTIPLY – MUL(32)
Limitations
Description
Section 5-19
Ladder Symbols
MUL(32)
Md
Mr
R
@MUL(32)
Md
Mr
R
Operand Data Areas
Md: Multiplicand (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Mr: Multiplier (BCD)
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR LR
R and R+1 must be in the same data area.
When the execution condition is OFF, MUL(32) is not executed. When the execution condition is ON, MUL(32) multiplies Md by the content of Mr, and places the result In R and R+1.
Md
X
Mr
R +1 R
Example When IR 00000 is ON with the following program, the contents of IR 013 and DM
0005 are multiplied and the result is placed in HR 07 and HR 08. Example data and calculations are shown below the program.
00000
MUL(32)
013
DM 0005
HR 07
Address Instruction
00000 LD
00001 MUL(32)
DM
HR
Operands
00000
013
00005
07
Flags
Md: IR 013
3 3 5 6
X
Mr: DM 0005
0 0 2 5
R+1: HR 08 R: HR 07
0 0 0 8 3 9 0 0
ER: Md and/or Mr is not BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when there is a carry in the result.
EQ: ON when the result is 0.
211
BCD Calculations
5-19-10 DOUBLE BCD MULTIPLY – MULL(56)
Limitations
Description
Section 5-19
Ladder Symbols
MULL(56)
Md
Mr
R
@MULL(56)
Md
Mr
R
Operand Data Areas
Md: First multiplicand word (BCD)
IR, SR, AR, DM, HR, TC, LR
Mr: First multiplier word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR LR
Md and Md+1 must be in the same data area, as must Mr and Mr+1.
R and R+3 must be in the same data area.
When the execution condition is OFF, MULL(56) is not executed. When the execution condition is ON, MULL(56) multiplies the eight-digit content of Md and
Md+1 by the content of Mr and Mr+1, and places the result in R to R+3.
Md + 1
Mr + 1
Md
Mr x
R + 3 R + 2 R + 1 R
Flags ER: Md, Md+1,Mr, or Mr+1 is not BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when there is a carry in the result.
EQ: ON when the result is 0.
5-19-11 BCD DIVIDE – DIV(33)
Ladder Symbol
DIV(33)
Dd
Dr
R
Operand Data Areas
Dd: Dividend word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Dr: Divisor word (BCD)
IR, SR, AR, DM, HR, TC, LR, #
R: First result word (BCD)
IR, SR, AR, DM, HR, LR
Limitations
212
R and R+1 must be in the same data area.
BCD Calculations
Description
Section 5-19
When the execution condition is OFF, DIV(33) is not executed and the program moves to the next instruction. When the execution condition is ON, Dd is divided by Dr and the result is placed in R and R + 1: the quotient in R and the remainder in R + 1.
Remainder
R+1
Quotient
R
Dr Dd
Flags
Example
00000
Dd: HR 09
0 0 0 3
ER: Dd or Dr is not in BCD.
Indirectly addressed DM word is non-existent. (Content of
∗
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
When IR 00000 is ON with the following program, the content of IR 020 is divided by the content of HR 09 and the result is placed in DM 0017 and DM 0018. Example data and calculations are shown below the program.
DIV(33)
020
HR 09
DM 0017
Remainder Quotient
R: DM 0017 R + 1: DM 0018
1 1 5 0 0 0 0 2
Dd: IR 020
3 4 5 2
Address Instruction
00000 LD
00001 DIV(33)
HR
DM
Operands
00000
020
09
0017
5-19-12 DOUBLE BCD DIVIDE – DIVL(57)
Limitations
Ladder Symbols
DIVL(57)
Dd
Dr
R
@DIVL(57)
Dd
Dr
R
Operand Data Areas
Dd: First dividend word (BCD)
IR, SR, AR, DM, HR, TC, LR
Dr: First divisor word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Dd and Dd+1 must be in the same data area, as must Dr and Dr+1.
R and R+3 must be in the same data area.
213
BCD Calculations
Description
Section 5-19
When the execution condition is OFF, DIVL(57) is not executed. When the execution condition is ON, DIVL(57) the eight-digit content of Dd and D+1 is divided by the content of Dr and Dr+1 and the result is placed in R to R+3: the quotient in
R and R+1, the remainder in R+2 and R+3.
Dr+1
R+3
Remainder
R+2
Dr
R+1
Quotient
R
Dd+1 Dd
Flags ER: Dr and Dr+1 contain 0.
Dd, Dd+1, Dr, or Dr+1 is not BCD.
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
5-19-13 FLOATING POINT DIVIDE – FDIV(79)
Ladder Symbols
FDIV(79)
Dd
Dr
R
@FDIV(79)
Dd
Dr
R
Operand Data Areas
Dd: First dividend word (BCD)
IR, SR, AR, DM, HR, TC, LR
Dr: First divisor word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Limitations
Description
Dr and Dr+1 cannot contain zero. Dr and Dr+1 must be in the same data area, as must Dd and Dd+1; R and R+1.
The dividend and divisor must be between 0.0000001 x 10 –7 and
0.9999999 x 10 7 . The results must be between 0.1 x 10 –7 and 0.9999999 x 10 7 .
When the execution condition is OFF, FDIV(79) is not executed. When the execution condition is ON, FDIV(79) divides the floating-point value in Dd and Dd+1 by that in Dr and Dr+1 and places the result in R and R+1.
Dr+1 Dr
R+1
Quotient
R
Dd+1 Dd
214
BCD Calculations Section 5-19
To represent the floating point values, the rightmost seven digits are used for the mantissa and the leftmost digit is used for the exponent, as shown below. The mantissa is expressed as a value less than one, i.e., to seven decimal places.
First word
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
1 0 1 0 0 0 0 1 0 0 0 1 0 0 0 1 exponent (0 to 7) sign of exponent 0: +
1: – mantissa (leftmost 3 digits)
Second word
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1 mantissa (leftmost 4 digits)
= 0.1111111 x 10 –2
Flags
Example
ER: Dr and Dr+1 contain 0.
Dd, Dd+1, Dr, or Dr+1 is not BCD.
The result is not between 0.1 x 10 –7 and 0.999999 x 10 7 .
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
The following example shows how to divide two whole four-digit numbers (i.e., numbers without fractions) so that a floating-point value can be obtained.
First the original numbers must be placed in floating-point form. Because the numbers are originally without decimal points, the exponent will be 4 (e.g., 3452 would equal 0.3452 x 10 4 ). All of the moves are to place the proper data into consecutive words for the final division, including the exponent and zeros. Data movements for Dd and Dd+1 are shown at the right below. Movements for Dr and Dr+1 are basically the same.The original values to be divided are in DM
0000 and DM 0001. The final division is also shown.
215
BCD Calculations
00000
Address Instruction
00000 LD
00001 @MOV(21)
00002 @MOV(21)
00003 @MOV(21)
00004 @MOV(21)
#
HR
#
HR
00005 @MOVD(83)
DM
#
HR
#
HR
#
HR
Operands
00000
0000
00
0000
02
4000
01
4000
03
0000
0021
01
@MOVD(83)
DM 0001
#0021
HR 03
@MOVD(83)
DM 0001
#0300
HR 02
@FDIV(79)
HR 00
HR 02
DM 0002
@MOV(21)
#0000
HR 00
@MOV(21)
#0000
HR 02
@MOV(21)
#4000
HR 01
@MOV(21)
#4000
HR 03
@MOVD(83)
DM 0000
#0021
HR 01
@MOVD(83)
DM 0000
#0300
HR 00
HR 01 HR 00
0 0 0 0
0000
HR 01 HR 00
4 0 0 0 0 0 0 0
4000
DM 0000
3 4 5 2
HR 01 HR 00
4 3 4 5 0 0 0 0
DM 0000
3 4 5 2
HR 01 HR 00
4 3 4 5 2 0 0 0
÷
HR 01 HR 00
4 3 4 5 2 0 0 0
HR 03 HR 02
4 0 0 7 9 0 0 0
DM 0003 DM 0002
2 4 3 6 9 6 2 0
0.4369620 x 10 2
Address Instruction
00006 @MOVD(83)
Operands
DM
#
HR
0000
0300
00
00007 @MOVD(83)
DM
#
HR
0001
0021
03
00008 @MOVD(83)
DM
#
HR
0001
0300
02
00009 @FDIV(79)
HR
HR
DM
00
02
0002
Section 5-19
216
BCD Calculations
5-19-14 SQUARE ROOT – ROOT(72)
Ladder Symbols
Limitations
Description
Section 5-19
ROOT(72)
Sq
R
@ROOT(72)
Sq
R
Operand Data Areas
Sq: First source word (BCD)
IR, SR, AR, DM, HR, TC, LR
R: Result word
IR, SR, AR, DM, HR, LR,
Sq and Sq+1 must be in the same data area.
When the execution condition is OFF, ROOT(72) is not executed. When the execution condition is ON, ROOT(72) computes the square root of the eight-digit content of Sq and Sq+1 and places the result in R. The fractional portion is truncated.
R
Sq+1 Sq
Flags
Example
ER: Sq is not BCD.
Indirectly addressed DM word is non-existent. (Content of ∗ DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
The following example shows how to take the square root of a four-digit number and then round the result.
First the words to be used are cleared to all zeros and then the value whose square root is to be taken is moved to Sq+1. The result, which has twice the number of digits required for the answer (because the number of digits in the original value was doubled), is placed in DM 0102, and the digits are split into two different words, the leftmost two digits to IR 011 for the answer and the rightmost two digits to DM 0103 so that the answer in IR 011 can be rounded up if required. The last step is to compare the value in DM 0103 so that IR 011 can be incremented using the Greater Than flag.
217
BCD Calculations Section 5-19
In this example, √ 6017 = 77.56, and 77.56 is rounded off to 78.
00000
Address
00002
25505
Instruction
00000 LD
00001 @BSET(71)
@MOV(21)
00003 @ROOT(72)
00004 @MOV(21)
DM
DM
DM
#
00005 @MOV(21)
#
DM
#
DM
DM
@MOVD(83)
DM 0102
#0210
DM 0103
@CMP(20)
DM 0103
#4900
@INC(38)
011
Operands
00000
0000
0100
0101
010
0101
0100
0102
0000
011
0000
0103
@BSET(71)
#0000
DM 0100
DM 0101
@MOV(21)
010
DM 0101
@ROOT(72)
DM 0100
DM 0102
@MOV(21)
#0000
011
@MOV(21)
#0000
DM 0103
@MOVD(83)
DM 0102
#0012
011
DM 0101 DM 0100
0 0 0 0 0 0 0 0
0000 0000
010
6 0 1 7
DM 0101 DM 0100
6 0 1 7 0 0 0 0
60170000= 7756.932
DM 0103 IR 011
0 0 0 0 0 0 0 0
0000 0000
DM 0102
7 7 5 6
IR 011 DM 0103
0 0 7 7 5 6 0 0
5600 > 4900
Address
IR 011
0 0 7 8
Instruction
00006 @MOVD(83)
Operands
DM
#
0102
0012
011
00007 @MOVD(83)
DM
#
DM
0102
0210
0103
00008 @CMP(20)
00009 LD
00010 @INC(38)
DM
#
25505
0103
4900
011
218
Binary Calculations Section 5-20
5-20 Binary Calculations
Binary calculation instructions — ADB(50), SBB(51), MLB(52), DVB(53),
ADBL(––), SBBL(––), MBS(––), MBSL(––), DBS(––), and DBSL(––) — perform arithmetic operations on hexadecimal data.
Four of these instructions (ADB(50), SBB(51), ADBL(––), and SBBL(––)) can act on both normal and signed data, two (MLB(52) and DVB(53)) act only on normal data, and four (MBS(––), MBSL(––), DBS(––), and DBSL(––)) act only on signed binary data.
The addition and subtraction instructions include CY in the calculation as well as in the result. Be sure to clear CY if its previous status is not required in the calculation, and to use the result placed in CY, if required, before it is changed by the execution of any other instruction. STC(40) and CLC(41) can be used to control
CY. Refer to 5-19 BCD Calculations.
Signed binary addition and subtraction instructions use the underflow and overflow flags (UF and OF) to indicate whether the result exceeds the acceptable range for 16-bit or 32-bit signed binary data. Refer to page 29 for details on signed binary data.
5-20-1 BINARY ADD – ADB(50)
ADB(50)
Au
Ad
R
Ladder Symbols
@ADB(50)
Au
Ad
R
Operand Data Areas
Au: Augend word (binary)
IR, SR, AR, DM, HR, TC, LR, #
Ad: Addend word (binary)
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
Description
Flags
When the execution condition is OFF, ADB(50) is not executed. When the execution condition is ON, ADB(50) adds the contents of Au, Ad, and CY, and places the result in R. CY will be set if the result is greater than FFFF.
Au + Ad + CY CY R
ADB(50) can also be used to add signed binary data. The underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Refer to page 29 for details on signed binary data.
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the result is greater than FFFF.
EQ: ON when the result is 0.
OF: ON when the result exceeds +32,767 (7FFF).
UF: ON when the result is below –32,768 (8000).
219
Binary Calculations
Example 1:
Adding Normal Data
00000
TR 0
25504
25504
Section 5-20
The following example shows a four-digit addition with CY used to place either
#0000 or #0001 into R+1 to ensure that any carry is preserved.
CLC(41)
ADB(50)
010
DM 0100
HR 10
MOV(21)
#0000
HR 11
MOV(21)
#0001
HR 11
= R
= R+1
= R+1
Address Instruction
00000 LD
00001 OUT
00002 CLC(41)
00003 ADB(50)
Operands
TR
00000
0
00004
00005
AND NOT
MOV(21)
00006 LD
00007 AND
00008 MOV(21)
DM
HR
#
HR
TR
#
HR
010
0100
10
25504
0000
11
0
25504
00001
11
In the case below, A6E2 + 80C5 = 127A7. The result is a 5-digit number, so CY
(SR 25504) = 1, and the content of R + 1 becomes #0001.
Au: IR 010
A 6 E 2
+
Ad: DM 0100
8 0 C 5
R+1: HR 11 R: HR 10
0 0 0 1 2 7 A 7
Note The UF and OF flags would also be turned ON during this addition, but they can be ignored since they are relevant only in the addition of signed binary data.
Example 2:
Adding Signed Binary Data
In the following example, ADB(50) is used to add two 16-bit signed binary values. (The 2’s complement is used to express negative values.)
The effective range for 16-bit signed binary values is –32,767 (8000) to +32,768
(7FFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds
+32,768 (7FFF) and the underflow flag (UF: SR 25405) is turned ON if the result falls below –32,767 (8000).
00000
CLC(41)
ADB(50)
LR 20
DM 0010
DM 0020
Address Instruction
00000 LD
00001 CLC(41)
00002 ADB(50)
LR
DM
DM
Operands
00000
20
0010
0020
220
Binary Calculations Section 5-20
In the case below, 25,321 +(–13,253) = 12,068 (62E9 + CC3B = 2F24). Neither
OF nor UF are turned ON.
+
Au: LR 20
6 2 E 9
Ad: DM 0010
C C 3 B
Ad: DM 0010
2 F 2 4
Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.
5-20-2 BINARY SUBTRACT – SBB(51)
SBB(51)
Mi
Su
R
Ladder Symbols
@SBB(51)
Mi
Su
R
Operand Data Areas
Mi: Minuend word (binary)
IR, SR, AR, DM, HR, TC, LR, #
Su: Subtrahend word (binary)
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
Description
Flags
When the execution condition is OFF, SBB(51) is not executed. When the execution condition is ON, SBB(51) subtracts the contents of Su and CY from Mi and places the result in R. If the result is negative, CY is set and the 2’s complement of the actual result is placed in R.
Mi – Su – CY CY R
SBB(51) can also be used to subtract signed binary data. The overflow and underflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Refer to page
29 for details on signed binary data.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the result is negative, i.e., when Mi is less than Su plus CY.
EQ: ON when the result is 0.
OF: ON when the result exceeds +32,767 (7FFF).
UF: ON when the result is below –32,768 (8000).
221
Binary Calculations
Example 1: Normal Data
00001
TR 1
25504
25504
Section 5-20
The following example shows a four-digit subtraction with CY used to place either #0000 or #0001 into R+1 to ensure that any carry is preserved.
CLC(41)
Address Instruction
00000 LD
00001 OUT
00002 CLC(41)
00003 SBB(51)
Operands
TR
00001
1
SBB(51)
001
LR20
HR 21
MOV(21)
#0000
HR 22
MOV(21)
#0001
HR 22
= R
= R+1
00004 AND NOT
00005 MOV(21)
00006 LD
00007 AND
00008 MOV(21)
LR
HR
#
HR
TR
001
20
21
25504
0000
22
1
25504
= R+1
NEG(––)
HR21
HR 21
00009 NEG(––)
#
HR
0001
22
HR
HR
21
21
In the case below, the content of LR 20 (#7A03) and CY are subtracted from
IR 001 (#F8C5). The result is stored in HR 21 and the content of HR 22 (#0000) indicates that the result is positive.
If the result had been negative, CY would have been set, #0001 would have been placed in HR 22, and the result would have been converted to its 2’s compliment.
–
–
Mi: IR 001
F 8 C 5
Su: LR 20
7 A 0 3
0 0 0 0
CY = 0
(from CLC(41))
R+1: HR 22
0 0 0 0
R: HR 21
7 E C 2
Note The status of the UF and OF flags can be ignored since they are relevant only in the subtraction of signed binary data.
222
Binary Calculations
Example 2:
Signed Binary Data
00000
Section 5-20
In the following example, SBB(51) is used to subtract one 16-bit signed binary value from another. (The 2’s complement is used to express negative values).
The effective range for 16-bit signed binary values is –32,768 (8000) to +32,767
(7FFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds
+32,767 (7FFF) and the underflow flag (UF: SR 25405) is turned ON if the result falls below –32,768 (8000).
CLC(41)
SBB(51)
LR 20
DM 0010
DM 0020
Address Instruction
00000 LD
00001 CLC(41)
00002 SBB(51)
LR
DM
DM
Operands
00000
20
0010
0020
In the case shown below, 30,020 – (–15,238) = 45,258 (7544 – C47A =
60CA).The OF flag would be turned ON to indicate that this result exceeds the upper limit of the 16-bit signed binary data range. (In other words, the result is a positive value that exceeds 32,767 (7FFF), not a negative number expressed as signed binary data.)
–
Mi: LR 20
7 5 4 4
Su: DM 0010
C 4 7 A
R: DM 0020
B 0 C A
In the case shown below, –30,000 – 3,000 = –33,000 (8AD0 – 0BB8 = 7F18).The
UF flag would be turned ON to indicate that this result is below the lower limit of
16-bit signed binary data range. (In other words, the result is a negative number below –32,768 (8000), not a positive number expressed as signed binary data.)
–
Mi: LR 20
8 A D 0
Su: DM 0010
0 B B 8
R: DM 0020
7 F 1 8
The absolute value of the true result (80E8=33,000) can be obtained by taking the 2’s complement of 7F18 using NEG(––).
Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.
223
Binary Calculations
5-20-3 BINARY MULTIPLY – MLB(52)
Limitations
Description
Section 5-20
MLB(52)
Md
Mr
R
Ladder Symbols
@MLB(52)
Md
Mr
R
Operand Data Areas
Md: Multiplicand word (binary)
IR, SR, AR, DM, HR, TC, LR, #
Mr: Multiplier word (binary)
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR LR
R and R+1 must be in the same data area.
When the execution condition is OFF, MLB(52) is not executed. When the execution condition is ON, MLB(52) multiplies the content of Md by the contents of
Mr, places the rightmost four digits of the result in R, and places the leftmost four digits in R+1.
Md
X
Mr
R +1 R
Precautions
Flags
MLB(52) cannot be used to multiply signed binary data. Use MBS(––) instead.
Refer to 5-20-7 SIGNED BINARY MULTIPLY – MBS(––) for details.
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
5-20-4 BINARY DIVIDE – DVB(53)
DVB(53)
Dd
Dr
R
Ladder Symbols
@DVB(53)
Dd
Dr
R
Operand Data Areas
Dd: Dividend word (binary)
IR, SR, AR, DM, HR, TC, LR, #
Dr: Divisor word (binary)
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR LR
Description When the execution condition is OFF, DVB(53) is not executed. When the execution condition is ON, DVB(53) divides the content of Dd by the content of Dr and the result is placed in R and R+1: the quotient in R, the remainder in R+1.
Quotient Remainder
R R + 1
Dr Dd
224
Binary Calculations
Precautions
Flags
Section 5-20
DVB(53) cannot be used to divide signed binary data. Use DBS(––) instead. Refer to 5-20-9 SIGNED BINARY DIVIDE – DBS(––) for details.
ER: Dr contains 0.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
Example
00000
DVB(53)
001
LR 20
HR 05
Address Instruction
00000 LD
00001 DVB(53)
LR
HR
Operands
00000
001
0020
05
Dd: IR 001
1 0 F 7
Dr: LR 20
0 0 0 3
R+1: HR 06
0 0 0 2
Remainder (2)
R: HR 05
0 5 A 7
Quotient (1447)
5-20-5 DOUBLE BINARY ADD – ADBL(––)
Limitations
Description
Ladder Symbols
ADBL(––)
Au
Ad
R
@ADBL(––)
Au
Ad
R
Au and Au+1 must be in the same data area, as must Ad and Ad+1, and R and
R+1.
When the execution condition is OFF, ADBL(––) is not executed. When the execution condition is ON, ADBL(––)) adds the eight-digit contents of Au+1 and
Au, the eight-digit contents of Ad+1 and Ad, and CY, and places the result in R.
CY will be set if the result is greater than FFFF FFFF.
Au + 1 Au
Ad + 1 Ad
Operand Data Areas
Au: First augend word (binary)
IR, SR, AR, DM, HR, LR
Ad: First addend word (binary)
IR, SR, AR, DM, HR, LR
R: First result word
IR, SR, AR, DM, HR, LR
CY
+
R + 1
CY
R
225
Binary Calculations
Flags
Example 1: Normal Data
00000
Section 5-20
ADBL(––) can also be used to add signed binary data. The underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 32-bit signed binary data range. Refer to page 29 for details on signed binary data.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the result is greater than FFFF FFFF.
EQ: ON when the result is 0.
OF: ON when the result exceeds +2,147,483,647 (7FFF FFFF).
UF: ON when the result is below –2,147,483,648 (8000 0000).
The following example shows an eight-digit addition with CY (SR 25504) used to represent the status of the 9 th
digit.
CLC(41)
ADBL(––)
000
DM 0020
LR 21
Address Instruction
00000 LD
00001 CLC(41)
00002 ADBL(––)
DM
LR
Operands
00000
000
0020
21
Example 2:
Signed Binary Data
00000
+
14020187 + 00A3F8C5 = 14A5FA4C
Au + 1 : 001
1 4 0 2
Ad + 1 : DM 0021
0 0 A 3
Au : 000
0 1 8 7
Ad : DM 0020
F 8 C 5
0
R + 1 : LR 22
1 4 A 5
R : LR 21
F A 4 C
0
CY (Cleared with CLC(41))
CY (No carry)
Note The status of the UF and OF flags can be ignored since they are relevant only in the addition of signed binary data.
In the following example, ADBL(––) is used to add two 32-bit signed binary values and output the 32-bit signed binary result to R and R+1. (The 2’s complement is used to express negative values).
The effective range for 32-bit signed binary values is –2,147,483,648
(8000 0000) to +2,147,483,647 (7FFF FFFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds +2,147,483,647 (7FFF FFFF) and the underflow flag (UF: SR 25405) is turned ON if the result falls below –2,147,483,648
(8000 0000).
CLC(41)
ADBL(––)
LR 20
DM 0010
DM 0020
Address Instruction
00000 LD
00001 CLC(41)
00002 ADBL(––)
LR
DM
DM
Operands
00000
20
0010
0020
226
Binary Calculations Section 5-20
+
Au + 1 : LR 21
6 B 3 C
Ad + 1 : DM 0011
E F 2 5
R + 1 : DM 0021
5 A 6 1
In the case below, 1,799,100,099 + (–282,751,929) = 1,516,348,100
(6B3C167D + EF258C47 = 5A61A2C4). Neither OF nor UF are turned ON.
Au : LR 20
1 6 7 D
Ad : DM 0010
8 C 4 7
0 CY (Cleared with CLC(41))
R : DM 0020
A 2 C 4
0
0
UF (SR 25405)
OF (SR 25404)
Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.
5-20-6 DOUBLE BINARY SUBTRACT – SBBL(––)
Ladder Symbols
SBBL(––)
Mi
Su
R
@SBBL(––)
Mi
Su
R
Operand Data Areas
Mi: First minuend word (binary)
IR, SR, AR, DM, HR, TC, LR
Su: First subtrahend word (binary)
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR, LR
Limitations
Description
Mi and Mi+1 must be in the same data area, as must Su and Su+1, and R and
R+1.
When the execution condition is OFF, SBBL(––) is not executed. When the execution condition is ON, SBBL(––) subtracts CY and the eight-digit value in Su and Su+1 from the eight-digit value in Mi and Mi+1, and places the result in R and
R+1. If the result is negative, CY is set and the 2’s complement of the actual result is placed in R+1 and R. Use the DOUBLE 2’s COMPLEMENT instructions to convert the 2’s complement to the true result.
Mi + 1
Su + 1
Mi
Su
CY
–
R + 1
CY
R
SBBL(––) can also be used to subtract signed binary data. The underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 32-bit signed binary data range. Refer to page 29 for details on signed binary data.
227
Binary Calculations
Flags
Example 1: Normal Data
00000
Section 5-20
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the result is negative, i.e., when Mi is less than Su plus CY.
EQ: ON when the result is 0.
OF: ON when the result exceeds +2,147,483,647 (7FFF FFFF).
UF: ON when the result is below –2,147,483,648 (8000 0000).
In this example, the eight-digit number in IR 002 and IR 001 is subtracted from the eight-digit number in DM 0021 and DM 0020, and the result is output to LR 22 and LR 21. If the result is negative, CY (SR 25504) is turned ON.
CLC(41)
SBBL(––)
001
DM 0020
LR 21
Address Instruction
00000 LD
00001 CLC(41)
00002 SBBL(––)
DM
LR
Operands
00000
001
0020
21
14020187 + 00A3F8C5 = 14A5FA4C
Au + 1 : 002
1 4 0 2
Ad + 1 : DM 0021
0 0 A 3
–
R + 1 : LR 22
1 3 5 E
Au : 001
0 1 8 7
Ad : DM 0020
F 8 C 5
0
R : LR 21
0 8 C 2
0
CY (Cleared with CLC(41))
CY (No carry)
Example 2:
Signed Binary Data
Note The status of the UF and OF flags can be ignored since they are relevant only in the subtraction of signed binary data.
In the following example, SBBL(––) is used to subtract one 32-bit signed binary value from another and output the 32-bit signed binary result to R and R+1.
The effective range for 32-bit signed binary values is –2,147,483,648
(8000 0000) to +2,147,483,647 (7FFF FFFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds +2,147,483,647 (7FFF FFFF) and the underflow flag (UF: SR 25405) is turned ON is the result falls below –2,147,483,648
(8000 0000).
00000
CLC(41)
SBBL(––)
001
DM 0020
LR 21
Address Instruction
00000 LD
00001 CLC(41)
00002 SBBL(––)
DM
LR
Operands
00000
001
0020
21
228
Binary Calculations
Au + 1 : 001
6 B 3 C
–
–
Ad + 1 : DM 0021
E F 2 5
R + 1 : LR 22
7 C 1 6
Section 5-20
In the case below, 1,799,100,099 – (–282,751,929) = 2,081,851,958
(6B3C 167D – {EF25 8C47 – 1 0000 0000} = 7C16 8A36). Neither OF nor UF are turned ON.
Au : 000
1 6 7 D
Ad : DM 0020
8 C 4 7
0
R : LR 21
8 A 3 6
0
0
CY (Cleared with CLC(41))
UF (SR 25405)
OF (SR 25404)
Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.
5-20-7 SIGNED BINARY MULTIPLY – MBS(––)
MBS(––)
Md
Mr
R
Ladder Symbols
@MBS(––)
Md
Mr
R
Operand Data Areas
Md: Multiplicand word
IR, SR, AR, DM, HR, TC, LR, #
Mr: Multiplier word
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR LR
Limitations
Description
R and R+1 must be in the same data area.
MBS(––) multiplies the signed binary content of two words and outputs the
8-digit signed binary result to R+1 and R. The rightmost four digits of the result are placed in R, and the leftmost four digits are placed in R+1. Refer to page 29 for details on signed binary data.
X
R +1
Md
Mr
R
Flags ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0000 0000, otherwise OFF.
229
Binary Calculations
Example
00000
Flags
Section 5-20
In the following example, MBS(––) is used to multiply the signed binary contents of IR 001 with the signed binary contents of DM 0020 and output the result to
LR 21 and LR 22.
MBS(––)
001
DM 0020
LR 21
Address Instruction
00000 LD
00001 MBS(––)
DM
LR
Operands
00000
001
0020
21
Md: IR 100
1 5 B 1
Mr: DM 0020
F C 1 3
X
R+1: LR 22
F F A A
R: LR 21
D 8 2 3
(5,553)
(–1,005)
(–5,580,765)
5-20-8 DOUBLE SIGNED BINARY MULTIPLY – MBSL(––)
Ladder Symbols
MBSL(––)
Md
Mr
R
@MBSL(––)
Md
Mr
R
Operand Data Areas
Md: First multiplicand word
IR, SR, AR, DM, HR, TC, LR
Mr: First multiplier word
IR, SR, AR, DM, HR, TC, LR
R: First result word
IR, SR, AR, DM, HR LR
Limitations
Description
Md and Md+1 must be in the same data area, as must Mr and Mr+1, and R and
R+3.
MBSL(––) multiplies the 32-bit (8-digit) signed binary data in Md+1 and Md with the 32-bit signed binary data in Mr+1 and Mr, and outputs the 16-digit signed binary result to R+3 through R. Refer to page 29 for details on signed binary data.
Md + 1
Mr + 1
Md
Mr x
R + 3 R + 2 R + 1 R
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is zero (content of R+3 through R all zeroes), otherwise OFF.
230
Binary Calculations
Example
00000
Section 5-20
In the following example, MBSL(––) is used to multiply the signed binary contents of IR 101 and IR 100 with the signed binary contents of DM 0021 and
DM 0020 and output the result to LR 24 through LR 21.
MBSL(––)
100
DM 0020
LR 21
Address Instruction
00000 LD
00001 MBSL(––)
DM
LR
Operands
00000
100
0020
21
Md+1: IR 101
0 0 0 8
Md: IR 100
7 9 3 8
Mr+1: DM 0021
F F F 0
Mr: DM 0020
A 8 1 2
X
R+3: LR 24
F F F F
R+2: LR 23
F F 7 D
R+1: LR 22
F C A 5
R: LR 21
4 5 F 0
(555,320)
(–1,005,550)
(–558,402,026,000)
5-20-9 SIGNED BINARY DIVIDE – DBS(––)
Limitations
Description
DBS(––)
Dd
Dr
R
Ladder Symbols
@DBS(––)
Dd
Dr
R
Operand Data Areas
Dd: Dividend word
IR, SR, AR, DM, HR, TC, LR, #
Dr: Divisor word
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR LR
R and R+1 must be in the same data area.
DBS(––) divides the signed binary content of Dd by the signed binary content of
Dr, and outputs the 8-digit signed binary result to R+1 and R. The quotient is placed in R, and the remainder is placed in R+1. Refer to page 29 for details on signed binary data.
Quotient
R
Remainder
R + 1
Dr Dd
Flags ER: Dr contains 0.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of R (the quotient) is 0000, otherwise OFF.
231
Binary Calculations
Example
00000
Section 5-20
In the following example, DBS(––) is used to divide the signed binary contents of
IR 001 with the signed binary contents of DM 0020 and output the result to LR 21 and LR 22.
DBS(––)
001
DM 0020
LR 21
Address Instruction
00000 LD
00001 DBS(––)
DM
LR
Operands
00000
001
0020
21
÷
R+1: LR 22
F F F A
Remainder (–6)
Dd: IR 001
D D D A
Dr: DM 0020
0 0 1 A
R: LR 21
F E B 0
Quotient (–336)
(–8,742)
(26)
(–336 and –6)
5-20-10 DOUBLE SIGNED BINARY DIVIDE – DBSL(––)
Ladder Symbols
DBSL(––)
Dd
Dr
R
@DBSL(––)
Dd
Dr
R
Operand Data Areas
Dd: Dividend word (binary)
IR, SR, AR, DM, HR, TC, LR, #
Dr: Divisor word (binary)
IR, SR, AR, DM, HR, TC, LR, #
R: First result word
IR, SR, AR, DM, HR LR
Limitations
Description
Dd and Dd+1 must be in the same data area, as must Dr and Dr+1, and R and
R+3.
DBS(––) divides the 32-bit (8-digit) signed binary data in Dd+1 and Dd by the
32-bit signed binary data in Dr+1 and Dr, and outputs the 16-digit signed binary result to R+3 through R. The quotient is placed in R+1 and R, and the remainder is placed in R+3 and R+2. Refer to page 29 for details on signed binary data.
Quotient
R+3
Remainder
R+2 R+1 R
Dr+1 Dr Dd+1 Dd
Flags ER: Dr+1 and Dr contain 0.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of R+1 and R (the quotient) is 0, otherwise OFF.
232
Special Math Instructions
Example
00000
Section 5-21
In the following example, DBSL(––) is used to divide the signed binary contents of IR 002 and IR 001 with the signed binary contents of DM 0021 and DM 0020 and output the result to LR 24 through LR 21.
DBSL(––)
001
DM 0020
LR 21
Address Instruction
00000 LD
00001 DBSL(––)
DM
LR
Operands
00000
001
0020
21
Dd+1: IR 002
F F 7 A
Dr+1: DM 0021
0 0 0 0
Dd: IR 001
B 1 5 C
Dr: DM 0020
0 0 1 A
F
R+3: LR 24
F F F
R+2: LR 23
F F F C
Remainder (–4)
F
R+1: LR 22
F F A
R: LR 21
D F 7 0
Quotient (–336,016)
(–8,736,420)
(26)
(–336,016 and –4/26)
5-21 Special Math Instructions
5-21-1 FIND MAXIMUM – MAX(––)
Ladder Symbols
Limitations
Description
MAX(––)
C
R
1
D
@MAX(––)
C
R
1
D
Operand Data Areas
C: Control data
IR, SR, AR, DM, HR, LR
R
1
: First word in range
IR, SR, AR, DM, HR, TC, LR
D: Destination word
IR, SR, AR, DM, HR, LR
N in C must be BCD between 001 to 999.
R
1
and R
1
+N–1 must be in the same data area.
When the execution condition is OFF, MAX(––) is not executed. When the execution condition is ON, MAX(––) searches the range of memory from R
1
to
R
1
+N–1 for the address that contains the maximum value and outputs the maximum value to the destination word (D).
If bit 14 of C is ON, MAX(––) identifies the address of the word containing the maximum value in D+1. The address is identified differently for the DM area:
1, 2, 3...
1. For an address in the DM area, the word address is written to D+1. For example, if the address containing the maximum value is DM 0114, then #0114 is written in D+1.
2. For an address in another data area, the number of addresses from the beginning of the search is written to D+1. For example, if the address containing the maximum value is IR 114 and the first word in the search range is
IR 014, then #0100 is written in D+1.
233
Special Math Instructions Section 5-21
If bit 15 of C is ON and more than one address contains the same maximum value, the position of the lowest of the addresses will be output to D+1.
The number of words within the range (N) is contained in the 3 rightmost digits of
C, which must be BCD between 001 and 999.
When bit 15 of C is OFF, data within the range is treated as normal binary and when it is ON the data is treated as signed binary.
C:
15 14 13 12 11
Data type
1 (ON): Signed binary
0 (OFF): Normal binary
00
Number of words in range (N)
Not used – set to zero.
Output address to D+1?
1 (ON): Yes.
0 (OFF): No.
!
Caution If bit 14 of C is ON, values above #8000 are treated as negative numbers, so the results will differ depending on the specified data type. Be sure that the correct data type is specified.
Flags ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
The number of words specified in C is not BCD (000 to 999).
R
1
and R
1
+N–1 are not in the same data area.
EQ: ON when the maximum value is #0000.
5-21-2 FIND MINIMUM – MIN(––)
Ladder Symbols Operand Data Areas
C: Control data
MIN(––) @MIN(––)
C
R
1
D
C
R
1
D
IR, SR, AR, DM, HR, TC, LR
R
1
: First word in range
IR, SR, AR, DM, HR, TC, LR
D: Destination word
IR, SR, AR, DM, HR, LR
Limitations
Description
N in C must be BCD between 001 to 999.
R
1
and R
1
+N–1 must be in the same data area.
When the execution condition is OFF, MIN(––) is not executed. When the execution condition is ON, MIN(––) searches the range of memory from R
1
to R
1
+N–1 for the address that contains the minimum value and outputs the minimum value to the destination word (D).
If bit 14 of C is ON, MIN(––) identifies the address of the word containing the minimum value in D+1. The address is identified differently for the DM area:
1, 2, 3...
1. For an address in the DM area, the word address is written to D+1. For example, if the address containing the minimum value is DM 0114, then #0114 is written in D+1.
2. For an address in another data area, the number of addresses from the beginning of the search is written to D+1. For example, if the address containing the minimum value is IR 114 and the first word in the search range is
IR 014, then #0100 is written in D+1.
234
Special Math Instructions Section 5-21
If bit 14 of C is ON and more than one address contains the same minimum value, the position of the lowest of the addresses will be output to D+1.
The number of words within the range (N) is contained in the 3 rightmost digits of
C, which must be BCD between 001 and 999.
When bit 15 of C is OFF, data within the range is treated as unsigned binary and when it is ON the data is treated as signed binary. Refer to page 29 for details on signed binary data.
C: 15 14 13 12 11
Data type
1 (ON): Signed binary
0 (OFF): Unsigned binary
00
Number of words in range (N)
Not used – set to zero.
Output address to D+1?
1 (ON): Yes.
0 (OFF): No.
!
Caution If bit 14 of C is ON, values above #8000 are treated as negative numbers, so the results will differ depending on the specified data type. Be sure that the correct data type is specified.
Flags ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
The number of words specified in C is not BCD (000 to 999).
R
1
and R
1
+N–1 are not in the same data area.
EQ: ON when the minimum value is #0000.
5-21-3 AVERAGE VALUE – AVG(––)
Ladder Symbols
AVG(––)
S
N
D
@AVG(––)
S
N
D
Operand Data Areas
S: Source word
IR, SR, AR, DM, HR, TC, LR
N: Number of cycles
IR, SR, AR, DM, HR, TC, LR, #
D: First destination word
IR, SR, AR, DM, HR, LR
Limitations
Description
Data of S must be hexadecimal.
N must be BCD from #0001 to #0064.
D and D+N+1 must be in the same data area.
AVG(––) is used to calculate the average value of S over N cycles.
When the execution condition is OFF, AVG(––) is not executed.
For the first N–1 cycles when the execution condition is ON, AVG(––) writes the value of S to D. Each time that AVG(––) is executed, the previous value of S is stored in words D+2 to D+N+1. The first 2 digits of D+1 are incremented with each execution and act as a pointer to indicate where the previous value is stored. Bit 15 of D+1 remains OFF for the first N–1 cycles.
235
Special Math Instructions Section 5-21
On the N th cycle, the previous value of S is written to last word in the range D+2 to
D+N+1. The average value of the previous values stored in D+2 to D+N+1 is calculated and written to D, bit 15 of D+1 is turned ON, and the previous value pointer (the first 2 digits of D+1) is reset to zero. Each time that AVG(––) is executed, the previous value of S overwrites the content of the word indicated by the pointer and the new average value is calculated and written to D. The pointer will be reset again after reaching N–1.
The following diagram shows the function of words D to D+N+1.
D
D+1
D+2
D+3
Average value (after N or more cycles)
Previous value pointer and cycle indicator
Previous value #1
Previous value #2
Previous Value Pointer
Cycle Indicator
Flags
D+N+1 Previous value #N
The function of bits in D+1 are shown in the following diagram and explained in more detail below.
D+1: 15 14 08 07 00
Not used. Set to zero.
Previous value pointer
(2-digit hexadecimal from 0 to N–1.)
Cycle indicator
0 (OFF): cycles since execution of AVG(––) < N.
1 (ON): cycles since execution of AVG(––)
≥
N.
The previous value pointer indicates the location where the most recent value of
S was stored relative to D+2, i.e., a pointer value of 0 indicates D+2, a value of 1 indicates D+3, etc.
The cycle indicator is turned ON after AVG(––) has been executed N times. At this point, D will contain the average value of the contents of words D+2 through
D+N+1. The average value is 4-digit hexadecimal and is rounded off to the nearest integer value.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
One or more operands have been set incorrectly.
236
Special Math Instructions
Example
Section 5-21
In the following example, the content of IR 040 is set to #0000 and then incremented by 1 each cycle. For the first two cycles, AVG(––) moves the content of
IR 040 to DM 1002 and DM 1003. The contents of DM 1001 will also change
(which can be used to confirm that the results of AVG(––) has changed). On the third and later cycles AVG(––) calculates the average value of the contents of
DM 1002 to DM 1004 and writes that average value to DM 1000.
00001
@MOV(21)
#0000
040
AVG(––)
040
#0003
DM 1000
CLC(41)
ADB(50)
040
#0001
040
Address Instruction
00000 LD
00001 @MOV(21)
00002 AVG(––)
#
#
DM
Operands
00001
0000
040
040
0003
1000
00003 CLC(41)
00004 ADB(50)
#
040
0001
040
IR 40
1 st cycle 2 nd cycle 3 rd cycle 4 th cycle
0000 0001 0002 0003
1 st cycle 2 nd cycle 3 rd cycle 4 th cycle
DM 1000 0000
DM 1001 0001
DM 1002 0000
0001
0002
0000
0001
8000
0000
0002
8000
0003
DM 1003 ---
DM 1004 ---
0001
---
0001
0002
0001
0002
Average
Pointer
Previous values of
IR 40
5-21-4 SUM – SUM(––)
Ladder Symbols
SUM(––)
C
R
1
D
@SUM(––)
C
R
1
D
Operand Data Areas
C: Control data
IR, SR, AR, DM, HR, LR
R
1
: First word in range
IR, SR, AR, DM, HR, TC, LR
D: First destination word
IR, SR, AR, DM, HR, LR
Limitations The 3 rightmost digits of C must be BCD between 001 and 999.
If bit 14 of C is OFF (setting for BCD data), all data within the range R
1
to R
1
+N–1 must be BCD.
237
Special Math Instructions
Description
Section 5-21
When the execution condition is OFF, SUM(––) is not executed. When the execution condition is ON, SUM(––) adds either the contents of words R
1
to
R
1
+N–1 or the bytes in words R
1
to R
1
+N/2–1 and outputs that value to the destination words (D and D+1). The data can be summed as binary or BCD and will be output in the same form. Binary data can be either signed or unsigned.
The function of bits in C are shown in the following diagram and explained in more detail below.
C:
15 14 13 12 11 00
Number of items in range (N, BCD)
Number of words or number of bytes
001 to 999
Starting byte in R1 (when bit 13 is ON)
1 (ON): Rightmost
0 (OFF): Leftmost
Addition units
1 (ON): Bytes
0 (OFF): Words
Data type
1 (ON): Binary
0 (OFF): BCD
Data type (when bit 14 is ON)
1 (ON): Signed binary
0 (OFF): Unsigned binary
Number of Items in Range
Addition Units
The number of items within the range (N) is contained in the 3 rightmost digits of
C, which must be BCD between 001 and 999. This number will indicate the number of words or the number of bytes depending the items being summed.
Words will be added if bit 13 is OFF and bytes will be added if bit 13 is ON.
If bytes are specified, the range can begin with the leftmost or rightmost byte of
R
1
. The leftmost byte of R
1
will not be added if bit 12 is ON.
R
1
R
1
+1
R
1
+2
R
1
+3
5
7
MSB LSB
1
3
2
4
6
8
Data Type
Flags
The bytes will be added in this order when bit 12 is OFF: 1+2+3+4....
The bytes will be added in this order when bit 12 is ON: 2+3+4....
Data within the range is treated as unsigned binary when bit 14 of C is ON and bit
15 is OFF, and it is treated as signed binary when both bits 14 and 15 are ON.
Refer to page 29 for details on signed binary data.
Data within the range is treated as BCD when bit 14 of C is OFF, regardless of the status of bit 15.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
R
1
and R
1
+N–1 are not in the same data area.
The number of items in C is not BCD between 001 and 999.
The data being summed is not BCD when BCD was designated.
EQ: ON when the result is zero.
238
Special Math Instructions
Example
Section 5-21
In the following example, the BCD contents of the 8 words from DM 0000 to
DM 0007 are added when IR 00001 is ON and the result is written to DM 0010 and DM 0011.
00001
@SUM(––)
#4008
DM 0000
DM 0010
Address Instruction
00000 LD
00001 @SUM(––)
#
DM
DM
Operands
00001
4008
0000
0010
DM 0000 0001
DM 0001 0002
DM 0002 0003
DM 0003 0004
DM 0004 0005
DM 0005 0006
DM 0006 0007
DM 0007 0008
DM 0010 0036
DM 0011 0000
5-21-5 ARITHMETIC PROCESS – APR(69)
Limitations
Description
Flags
APR(69)
C
S
D
Ladder Symbols
@APR(69)
C
S
D
Operand Data Areas
C: Control word
IR, SR, AR, DM, HR, TC, LR, #
S: Input data source word
IR, SR, AR, DM, HR, TC, LR
D: Result destination word
IR, SR, AR, DM, HR,TC, LR
For trigonometric functions S must be BCD from 0000 to 0900 (0 °≤ q ≤ 90 ° ).
When the execution condition is OFF, APR(69) is not executed. When the execution condition is ON, the operation of APR(69) depends on the control word C.
If C is #0000 or #0001, APR(69) computes sin( q
) or cos( q
)*. The BCD value of S specifies q
in tenths of degrees.
If C is an address, APR(69) computes f(x) of the function entered in advance beginning at word C. The function is a series of line segments (which can approximate a curve) determined by the operator. The BCD or hexadecimal value of S specifies x.
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
For trigonometric functions, x > 0900. (x is the content of S.)
A constant other than #0000 or #0001 was designated for C.
The linear approximation data is not readable.
EQ: The result is 0000.
239
Special Math Instructions
Examples
Sine Function
00000
Section 5-21
The following example demonstrates the use of the APR(69) sine function to calculate the sine of 30 ° . The sine function is specified when C is #0000.
APR(69)
#0000
DM 0000
DM 0100
Address Instruction
00000 LD
00001 APR(69)
#
DM
DM
Operands
00000
0000
0000
0100
0
0
Input data, x
S: DM 0000
10 1 10 0
3 0
Enter input data not exceeding #0900 in BCD.
10 –1
0
10 –1
5
Result data
D: DM 0100
10 –2 10 –3
0 0
10
0
–4
Result data has four significant digits, fifth and higher digits are ignored. The result for sin(90) will be 0.9999, not 1.
Cosine Function
00000
0
0
Input data, x
S: DM 0010
10 1 10 0
3 0
Enter input data not exceeding #0900 in BCD.
10 –1
0
The following example demonstrates the use of the APR(69) cosine function to calculate the cosine of 30
°
. The cosine function is specified when C is #0001.
APR(69)
#0001
DM 0010
DM 0110
Address Instruction
00000 LD
00001 APR(69)
#
DM
DM
Operands
00000
0001
0010
0110
10 –1
8
Result data
D: DM 0110
10 –2 10 –3
6 6
10 –4
0
Result data has four significant digits, fifth and higher digits are ignored. The result for cos(0) will be 0.9999, not 1.
Linear Approximation APR(69) linear approximation is specified when C is a memory address. Word C is the first word of the continuous block of memory containing the linear approximation data.
The content of word C specifies the number of line segments in the approximation, and whether the input and output are in BCD or BIN form. Bits 00 to 07 contain the number of line segments less 1, m–1, as binary data. Bits 14 and 15 determine, respectively, the output and input forms: 0 specifies BCD and 1 specifies BIN.
C: 15 14 13 Not used.
07 06 05 04 03 02 01 00
Source data form
1 (ON): f(x)=f(X m
0 (OFF): f(x)=f(S)
–S)
Output form
Input form
Number of coordinates minus one (m–1)
240
Special Math Instructions Section 5-21
Y
4
Y
3
Y
1
Y
Y m
Y
2
Y
0
X
0
Enter the coordinates of the m+1 end-points, which define the m line segments, as shown in the following table. Enter all coordinates in BIN form. Always enter the coordinates from the lowest X value (X
1
) to the highest (X does not have to be entered.
m
). X
0
is 0000, and
X
Word Coordinate
C+1
C+2
C+3
C+4
C+5
C+6
↓
X
2
Y
2
↓
C+(2m+1) X m
C+(2m+2) Y m
X m
(max. X value)
Y
0
X
1
Y
1
X
1
X
2
X
3
X
4
X m
If bit 13 of C is set to 1, the graph will be reflected from left to right, as shown in the following diagram.
Y Y
00000
X X
X
0
X m
X m
X
0
The following example demonstrates the construction of a linear approximation with 12 line segments. The block of data is continuous, as it must be, from DM
0000 to DM 0026 (C to C + (2
×
12 + 2)). The input data is taken from IR 010, and the result is output to IR 011.
Content Coordinate
DM 0000 $C00B
DM 0001 $05F0
DM 0002 $0000
DM 0003 $0005
DM 0004 $0F00
DM 0005 $001A
DM 0006 $0402
↓ ↓
DM 0025 $05F0
DM 0026 $1F20
X
2
Y
2
↓
X
12
X
12
Y
0
X
1
Y
1
Y
12
APR(69)
DM 0000
010
011
Address Instruction
00000 LD
00001 APR(69)
Operands
00000
DM 0000
010
011
Bit
15
Bit
00
1 1 0 0 0 0 0 0 0 0 0 0 1 0 1 1
(Output and
input both BIN)
(m–1 = 11: 12 line segments)
241
Special Math Instructions Section 5-21
In this case, the input data word, IR 010, contains #0014, and f(0014) = #0726 is output to R, IR 011.
Y
$1F20
$0F00
(x,y)
$0726
$0402
(0,0)
5-21-6 PID CONTROL – PID(––)
Limitations
Description
$0005
Ladder Symbol
PID(––)
S
C
D
$0014 $001A $05F0
X
Operand Data Areas
S: Input word
IR, SR, AR, DM, HR, LR,
C: First parameter word
IR, SR, DM, HR, LR
D: Output word
IR, SR, AR, DM, HR, LR
C and C+32 must be within the same data area.
!
Caution Do not program PID(––) in the following situations. Doing so may produce unexpected behavior: In interrupt programs, in subroutines, between IL(02) and
ILC(03), between JMP(04) and JME(05), and in step programming (when using
STEP(08) and SNXT(09)).
PID(––) carries out PID control according to the designated parameters. It takes the specified input range of binary data from the contents of input word S and carries out the PID operation according to the parameters that are set. The results are then stored as the operation output amount in output word D.
PID parameter words range from C through C+32. The PID parameters are configured as shown below.
Word
C
C+1
C+2
C+3
C+4
C+5
15 to 12 11 to 8 7 to 4 3 to 0
Set value (SV)
Proportional band (P)
Tik = Integral time T
1
/sampling period γ (See note 1.)
Tdk = Derivative time Td/sampling period
γ
(See note 1.)
Sampling period γ
2-PID parameter (
α
) (See note 2.) PID forward/ reverse designation
C+6 0 Input range 0 Output range
C+7 to C+32 Work area (Cannot be accessed directly from program.)
Note 1. What is set in words 2 and 3 is not the actual integral and derivative times, but rather their values divided by the value of the sampling period
γ
.
2. Setting the 2-PID parameter (
α
) to 000 yields 0.65, the normal value.
242
Special Math Instructions Section 5-21
Parameter Settings
Item
Set value (SV)
Proportional band This is the parameter for P control expressing the proportional control range/total control range.
Tik This is a constant expressing the strength of the integral operation. As this value increases, the integral strength decreases.
Tdk
Sampling period
This is a constant expressing the strength of the derivative operation. As this value increases, the derivative strength increases.
This sets the period for executing the PID operation.
PID forward/reverse designation
2-PID parameter
( α )
Input range
Output range
Contents
This is the target value of the process being controlled.
This is the parameter that determines the direction of the proportional operation.
Setting range
Binary data (of the same number of bits as specified for the input range)
0001 to 9999 (4 digits BCD);
(0.1% to 999.9%, in units of
0.1%)
0001 to 8191 (4 digits BCD);
(9999 = Integral operation not executed)
0000 to 8191 (4 digits BCD)
0001 to 1023 (4 digits BCD);
(0.1 to 102.3 s, in units of
0.1 s)
0: Reverse operation
1: Forward operation
This is the input filter coefficient. Normally use
0.65 (i.e., a setting of 000). The filter efficiency decreases as the coefficient approaches 0.
This is the number of input data bits.
000: α = 0.65
Setting from 100 to 199 means that the value of the rightmost two digits is set from α = 0.00
to α = 0.99.
0: 8 bits 5: 13 bits
This is the number of output data bits. {The number of output bits is automatically the same as the number of input bits.)
2: 10 bits
3: 11 bits
4: 12 bits
7: 15 bits
8: 16 bits
PID CONTROL Operation
PID Control Method
Execution Condition OFF
All data that has been set is retained. Then the execution condition is OFF, the operation amount can be written to the output word (D) to achieve manual control.
Rising Edge of the Execution Condition
The work area is initialized based on the PID parameters that have been set and the PID control operation is begin. Sudden and radical changes in the operation output amount are not made when starting operation to avoid adverse affect on the controlled system (bumpless operation).
When PID parameters are changed, they first become valid when the execution condition changes from OFF to ON.
Execution Condition ON
The PID operation is executed at the intervals based on the sampling period, according to the PID parameters that have been set.
Sampling Period and PID Execution Timing
The sampling period is the time interval to retrieve the measurement data for carrying out a PID operation. PID(––), however, is executed according to
C200HS cycle time, so there may be cases where the sampling period is exceeded. In such cases, the time interval until the next sampling is reduced.
C200HS PID control operations are executed by means of PID control with feedforward control (two degrees of freedom).
243
Special Math Instructions Section 5-21
When overshooting is prevented with simple PID control, stabilization of disturbances is slowed (1). If stabilization of disturbances is speeded up, on the other hand, overshooting occurs and response toward the target value is slowed (2).
With feed-forward PID control, there is no overshooting, and response toward the target value and stabilization of disturbances can both be speeded up (3).
Simple PID Control Feed-forward PID control
(1)
As the target response is slowed, the disturbance response worsens.
Target response Disturbance response
(2)
Overshoot
As the disturbance response is slowed, the target response worsens.
Control Operations Proportional Operation (P)
Proportional operation is an operation in which a proportional band is established with respect to the set value (SV), and within that band the operation amount (the control output amount) is made proportional to the deviation. If the present value (PV) is smaller than the proportional band, the operation amount will be 100%. If within the proportional band the operation amount is made proportional to the deviation and gradually decreased until the SV and PV match
(i.e., until the deviation is 0), the operation amount will return to the previous value (forward operation).
The proportional band is expressed as a percentage with respect to the total input range. With proportional operation an offset (residual deviation) occurs, and the offset is reduced by making the proportional band smaller. If it is made too small, however, hunting will occur.
Adjusting the Proportional Band
Operation amount
100%
Proportional Operation
(Forward Operation)
Proportional band
Proportional band too narrow (hunting occurring)
Offset
0%
SV
Proportional band just right
Proportional band too wide (large offset)
Integral Operation (I)
Combining integral operation with proportional operation reduces the offset according to the time that has passed. The strength of the integral operation is indicated by the integral time, which is the time required for the integral operation amount to reach the same level as the proportional operation amount with respect to the step deviation, as shown in the following illustration. The shorter the integral time, the stronger the correction by the integral operation will be. If the
244
Special Math Instructions Section 5-21 integral time is too short, the correction will be too strong and will cause hunting to occur.
Deviation
0
Integral Operation
Step response
Operation amount
0
PI Operation and Integral Time
Deviation
0
Step response
PI operation
I operation
P operation
Operation amount
0
Ti: Integral time
Derivative Operation (D)
Proportional operation and integral operation both make corrections with respect to the control results, so there is inevitably a response delay. Derivative operation compensates for that drawback. In response to a sudden disturbance it delivers a large operation amount and rapidly restores the original status. A correction is executed with the operation amount made proportional to the incline (derivative coefficient) caused by the deviation.
The strength of the derivative operation is indicated by the derivative time, which is the time required for the derivative operation amount to reach the same level as the proportional operation amount with respect to the step deviation, as shown in the following illustration. The longer the derivative time, the stronger the correction by the derivative operation will be.
Deviation 0
Derivative Operation
Step response
Operation amount
0
Deviation 0
PD Operation and Derivative Time
Ramp response
PD operation
P operation
D operation
Operation amount
0
Td: Derivative time
PID Operation
PID operation combines proportional operation (P), integral operation (I), and derivative operation (D). It produces superior control results even for control objects with dead time. It employs proportional operation to provide smooth control
245
Special Math Instructions Section 5-21 without hunting, integral operation to automatically correct any offset, and derivative operation to speed up the response to disturbances.
Deviation 0
PID Operation Output Step Response
Ramp response
Operation amount
0
Deviation 0
PID Operation Output Lamp Response
Step response
PID operation
I operation
P operation
D operation
PID operation
I operation
P operation
D operation
Operation amount
0
Direction of Operation
Adjusting PID Parameters
When using PID operation, select either of the following two control directions. In either direction, the operation amount increases as the difference between the
SV and the PV increases.
• Forward operation: Control amount is increased when the PV is larger than the
SV.
• Reverse operation: Control amount is increased when the PV is smaller than the SV.
The general relationship between PID parameters and control status is shown below.
• When it is not a problem if a certain amount of time is required for stabilization
(settlement time), but it is important not to cause overshooting, then enlarge the proportional band.
Control by measured PID
SV
When P is enlarged
•
When overshooting is not a problem but it is desirable to quickly stabilize control, then narrow the proportional band. If the proportional band is narrowed too much, however, then hunting may occur.
When P is narrowed
SV
Control by measured PID
•
When there is broad hunting, or when operation is tied up by overshooting and undershooting, it is probably because integral operation is too strong. The
246
Special Math Instructions Section 5-21 hunting will be reduced if the integral time is increased or the proportional band is enlarged.
Control by measured PID
(when loose hunting occurs)
SV
Enlarge I or P.
•
If the period is short and hunting occurs, it may be that the control system response is quick and the derivative operation is too strong. In that case, set the derivative operation lower.
Control by measured PID
(when hunting occurs in a short period)
Flags
Example
SV
Lower D.
ER: Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.
A PID parameter SV is out of range.
The PID operation was executed but the cycle time was two times the sampling period. PID(––) will be executed for this error only even when
ER (SR25503) is ON.
CY: The PID operation is being executed.
This example shows a PID control program using PID(––).
C200HS
CPU
AD001 DA001
#0 #1
Amplifier (See note below.)
Fan (Output word IR 111)
Temperature sensing element
(Output word IR 100)
Amplifier (See note below.)
Heater (Output word IR110)
Note Motors and heaters cannot be directly connected from a Analog Output Unit. An amplifier (i.e., a current amplification circuit) is required.
247
Special Math Instructions Section 5-21
Creating the Program Follow the procedure outlined below in creating the program.
1, 2, 3...
1. Set the target value (binary 0000 to 0FFF) in DM 0000.
2. Input the PV of the temperature sensing element (binary 000 to 0FFF) in bits
0 to 11 of word 101.
3. Output the operation amount of the heater to bits 0 to 11 of word 110 by means of the first PID(––) instruction in the following program.
4. Output the operation amount of the fan to bits 0 to 11 of word 111 by means of the second PID(––) instruction in the following program.
5. Convert the PV of the temperature sensing element (binary 000 to FFF) to temperature data (0000
°
C to 0200
°
C) by means of SCL(––), and output it to
DM 0200.
Program
00000 25315
@MOV(21)
#0F00
DM0000
Target value
@MOV(21)
DM0000
HR00
@MOV(21)
DM0000
HR40
Parameter leading word for first
PID(––) instruction
Parameter leading word for second
PID(––) instruction
PID(––)
101
HR00
110
PV of temperature sensing element
Heater operation amount
PID(––)
101
HR40
111
SCL
101
DM0100
DM0200
END
Fan operation amount
PV of temperature sensing element (binary)
Leading word of converted parameter
Present temperature of temperature sensing element (
°
C)
248
Logic Instructions Section 5-22
Note When using PID(––) or SCL(––), make the data settings in advance with a Peripheral Device such as the Programming Console or LSS.
HR 00
HR 01
HR 02
HR 03
HR 04
HR 05
HR 06
Heater
(DM0000)
0080
0200
0100
0001
0000
0404
Target value HR
Proportional band
Integral time/sampling period
Derivative time/sampling period
Sampling period
Forward/reverse designation/
PID parameters
I/O range
DM 0100
DM 0101
DM 0102
DM 0103
SCL Parameters
0000
0000
0200
0FFF
HR 40
HR 41
HR 42
HR 43
HR 44
HR 45
HR 46
Fan
(DM0000)
0060
0150
0100
0001
0001
0404
5-22 Logic Instructions
The logic instructions – COM(29), ANDW(34), ORW(35), XORW(36), and
XNRW(37) – perform logic operations on word data.
5-22-1 COMPLEMENT – COM(29)
Ladder Symbols Operand Data Areas
COM(29)
Wd
@COM(29)
Wd
Wd: Complement word
IR, SR, AR, DM, HR, LR
Description
Example
When the execution condition is OFF, COM(29) is not executed. When the execution condition is ON, COM(29) clears all ON bits and sets all OFF bits in Wd.
Original
15 00
1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
Flags
15 00
Complement 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
249
Logic Instructions
5-22-2 LOGICAL AND – ANDW(34)
Description
Example
Section 5-22
Ladder Symbols
ANDW(34)
I1
I2
R
@ANDW(34)
I1
I2
R
Operand Data Areas
I1: Input 1
IR, SR, AR, DM, HR, TC, LR, #
I2: Input 2
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, ANDW(34) is not executed. When the execution condition is ON, ANDW(34) logically AND’s the contents of I1 and I2 bit-by-bit and places the result in R.
I1
15 00
1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
I2
15 00
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Flags
15 00
0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1 R
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
250
Logic Instructions
5-22-3 LOGICAL OR – ORW(35)
Description
Example
Section 5-22
Ladder Symbols
ORW(35)
I1
I2
R
@ORW(35)
I1
I2
R
Operand Data Areas
I1: Input 1
IR, SR, AR, DM, HR, TC, LR, #
I2: Input 2
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, ORW(35) is not executed. When the execution condition is ON, ORW(35) logically OR’s the contents of I1 and I2 bit-by-bit and places the result in R.
I1
15 00
1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
I2
15 00
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Flags
R
15 00
1 1 0 1 1 1 0 1 1 1 0 1 1 1 0 1
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
251
Logic Instructions
5-22-4 EXCLUSIVE OR – XORW(36)
Description
Example
Section 5-22
Ladder Symbols
XORW(36)
I1
I2
R
@XORW(36)
I1
I2
R
Operand Data Areas
I1: Input 1
IR, SR, AR, DM, HR, TC, LR, #
I2: Input 2
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, XORW(36) is not executed. When the execution condition is ON, XORW(36) exclusively OR’s the contents of I1 and I2 bit-by-bit and places the result in R.
I1
15 00
1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
I2
15 00
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Flags
15 00
1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 R
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
252
Subroutines and Interrupt Control Section 5-23
5-22-5 EXCLUSIVE NOR – XNRW(37)
Description
Ladder Symbols
XNRW(37)
I1
I2
R
@XNRW(37)
I1
I2
R
Operand Data Areas
I1: Input 1
IR, SR, AR, DM, HR, TC, LR, #
I2: Input 2
IR, SR, AR, DM, HR, TC, LR, #
R: Result word
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, XNRW(37) is not executed. When the execution condition is ON, XNRW(37) exclusively NOR’s the contents of I1 and I2 bit-by-bit and places the result in R.
I1
15 00
1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
I2
15 00
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
15 00
0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 R
Flags ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
5-23 Subroutines and Interrupt Control
5-23-1 Subroutines
Interrupts
Subroutines break large control tasks into smaller ones and enable you to reuse a given set of instructions. When the main program calls a subroutine, control is transferred to the subroutine and the subroutine instructions are executed. The instructions within a subroutine are written in the same way as main program code. When all the subroutine instructions have been executed, control returns to the main program to the point just after the point from which the subroutine was entered (unless otherwise specified in the subroutine).
Subroutines may also be activated by interrupts or the MCRO(99) instruction.
Like subroutine calls, interrupts cause a break in the flow of the main program execution such that the flow can be resumed from that point after completion of the subroutine. An interrupt is caused either by an external source, such as an input signal from an Interrupt Input Unit, or a scheduled interrupt. In the case of the scheduled interrupt, the interrupt signal is repeated at regular intervals.
Whereas subroutine calls are controlled from within the main program, subroutines activated by interrupts are triggered when the interrupt signal is received.
In the case of the scheduled interrupt, the time interval between interrupts is set by the user and is unrelated to the cycle timing of the PC. This capability is useful for periodic supervisory or executive program execution.
253
Subroutines and Interrupt Control Section 5-23
MCRO(99)
INT(89) is used to control the interrupt signals received from the Interrupt Input
Unit, and also to control the scheduling of the scheduled interrupt. INT(89) provides such functions as masking of interrupts (so that they are recorded but ignored) and clearing of interrupts.
Refer to 5-23-2 Interrupts for more details on interrupts.
The MACRO instruction allows a single subroutine (programming pattern) to replace several subroutines that have identical structure but different operands.
Since a number of similar program sections can be managed with just one subroutine, the number of program steps can be greatly reduced. Refer to 5-23-5
MACRO – MCRO(99) for more details on this instruction.
5-23-2 Interrupts
Interrupts Input interrupts
The C200HS supports both input interrupts and scheduled interrupts. The operating modes for these interrupts are shown in the following illustration.
Scheduled interrupts
Normal mode (C200H compatible)
High-speed mode (C200HS only)
Normal mode (C200H compatible)
High-speed mode (C200HS only)
Interrupts at n x 10 ms
Interrupts at n x 1 ms
Interrupts at n x 10 ms
Interrupts at n x 1 ms
Input Interrupts
Scheduled Interrupts
Input interrupts are executed when external inputs are received via a C200HS-
INT01 Interrupt Input Unit. The Interrupt Input Unit provides at total of 8 inputs numbered IN 0 through IN7 that can be used to generate interrupts #00 to #07.
Generally speaking, subroutines #00 to #07 are executed when interrupts #00 to
#07 are generated.
Only one Interrupt Input Unit can be mounted to each C200HS PC. When any of the 8 inputs on the Interrupt Input Unit goes ON, an interrupt is generated and the corresponding bit in the word allocated to the slot to which the Unit is mounted is turned ON.
Note 1. Subroutines #00 to #07 can be used as normal subroutines when they are not used for input interrupts.
2. Inputs on the Interrupt Input Unit not used for interrupts can be used for normal inputs.
Scheduled interrupts can be executed at intervals set either in increments of
10 ms or in increments or 1 ms. Interrupt #99 is used and subroutine #99 is executed.
The unit used to set the scheduled interrupt interval is set in the PC Setup at
DM 6622.
Bit
DM 6622
15 00
Schedule Interrupt Setting Interval Setting Enable
00: Setting disabled (interval fixed at 10 ms)
01: Setting in bits 00 to 07 enabled
Schedule Interrupt Setting Interval Setting
00: 10 ms
01: 1 ms
Note Subroutine #99 can be used as a normal subroutine when it is not used for a scheduled interrupt.
254
Subroutines and Interrupt Control Section 5-23
Normal Interrupt Mode
(C200H Compatible)
The following setting is used for normal interrupt mode.
DM 6620 0 0 0 0
In normal interrupt mode, the following processing will be completed once started even if an interrupt occurs The interrupt will be processed as soon as the current process is completed.
• Host Link servicing
•
Remote I/O servicing
• Special I/O Unit servicing
•
Individual instruction execution
• SYSMAC LINK/SYSMAC NET servicing (CPU31-E/33-E only)
Use this mode whenever using C200H interrupt subroutines without modification or whenever possible considering the response time required for interrupts.
Note The C200HS is set to normal interrupt mode by default.
High-speed Interrupt Mode
(C200HS)
The following setting is used for high-speed interrupt mode.
DM 6620 1 – – –
Interrupt mode
(1 = high-speed)
Interrupt Priority
Special I/O in Interrupt
Subroutines
In high-speed interrupt mode, the following processing will be interrupted and the interrupt subroutine executed as soon as an interrupt is generated.
• Host Link servicing
•
Remote I/O servicing
• Special I/O Unit servicing
•
Individual instruction execution
Use this mode whenever interrupt response time must be accurate to 1.0 ms.
Note 1. With the CPU31-E/33-E, SYSMAC LINK/SYSMAC NET servicing will be completed before processing interrupts, meaning up to 10 ms may be required to respond to and interrupt even in the High-speed mode.
2. Data will not necessarily be concurrent if the high-speed interrupt mode is used because Host Link servicing, remote I/O servicing, Special I/O Unit servicing, and individual instruction execution will not necessarily be completed when started. The program must be designed to allow for this when required by the application. (See the section on data concurrence for further details.)
The specified subroutine will be executed when an interrupt is generated. If further interrupts are generated during execution of an interrupt subroutine, they will not be processed until execution of the current interrupt subroutine has been completed. If more than one interrupt is generated or is awaiting execution at the same time, the corresponding subroutines will be executed in the following order of priority.
Input interrupt 1 > input interrupt 2 > ... > input interrupt 7 > scheduled interrupt
I/O for Special I/O Units can be refreshed from within interrupt subroutines by using the I/O REFRESH (IORF) instruction. If the high-speed interrupt mode is used, refreshing in the normal cycle (END refreshing and IORF refreshing in the main program) must be disabled for the Special I/O Unit that is to be refreshed in the interrupt subroutine. An interrupt programming error (system FAL error 8B) will occur if the same special I/O is refreshed both within an interrupt program and within the normal cycle, and the special I/O will not be refreshed within the interrupt subroutine.
255
Subroutines and Interrupt Control Section 5-23
The PC Setup for the C200HS contains settings in DM 6620 that disable refreshing in the normal cycle for specific Special I/O Units. This settings are as shown below.
Bit 15
1
DM6620
12
0 0 * * * * * * * * * *
00
Interrupt mode
(1 = high-speed)
Unit #0
Unit #1
.
.
.
Unit #9
Note Disabling special I/O refreshing in the normal cycle to refresh special I/O in an interrupt subroutine is necessary only in the high-speed mode. Disabling normal cycle refreshing of special I/O during normal interrupt mode will be ignored and the special I/O will be refreshed both in the normal cycle and in the interrupt subroutine.
The execution time of interrupt subroutines must be kept to less than10 ms if the high-speed interrupt mode is used and Special I/O Units, Host Link Units, or Remote I/O Units are programmed. An interrupt programming error (system FAL error 8B) will occur if the execution time is 10 ms or greater.
The execution time of interrupt subroutine with the longest execution time is output to SR 262 and the number of the subroutine with the longest execution time is output to SR 263.
SR 262
Example: 12.3 ms for subroutine #80
0 1 2 3 Maximum interrupt subroutine execution time (in 0.1 ms)
SR 263 8 0 * *
No. of interrupt subroutine with maximum execution time
Data Concurrence
Note The above 10-ms limit does not apply when the normal interrupt mode is used or when the above Units are not mounted.
Although data concurrence is not a problem for execution of normal arithmetic instructions or comparison instructions, it can be a problem when executing longer instructions that handle multiple words, such as block transfer instructions, when the high-speed interrupt mode is used and the same data is handled both in the main program and in an interrupt subroutine.
Data may not be concurrent in two different situations: 1) if a data write operation in the main program is interrupted and the same data is read in an interrupt subroutine and 2) if a data read operation in the main program is interrupted and the same data is written in an interrupt subroutine.
256
Subroutines and Interrupt Control Section 5-23
If you must handle the same data both in the main program and in an interrupt subroutine, use programming such as that shown below to be sure that data concurrence is preserved, i.e., mask interrupts while read/writing data that is also handled in an interrupt subroutine.
(@)INT(89)
100
000
000
Masks all interrupts.
Reading and writing common data words
(@)INT(89)
200
000
000
Unmasks all interrupts.
Data concurrence can also be a problem if interrupts occur during data transfers occurring in servicing for Special I/O Units, remote I/O, or Host Link Systems.
For any of these, data can be non-concurrent down to byte units.
Use one of the following methods to preserve data concurrence in the above situations. The second methods applies to Special I/O Units only.
• Mask interrupts in the main program while moving data transferred to/from
Units to different words and use these alternate words in the interrupt subroutine.
• Use the I/O REFRESH instruction in interrupt subroutines to refresh required
I/O from Special I/O Units and mask interrupts in the main program while reading/writing Special I/O Unit words.
5-23-3 SUBROUTINE ENTER – SBS(91)
Ladder Symbol
SBS(91) N
Definer Data Areas
N: Subroutine number
00 to 99
Limitations Subroutine numbers 00 through 07 are used with input interrupts and subroutine number 99 is used for the scheduled interrupt.
257
Subroutines and Interrupt Control
Description
Section 5-23
A subroutine can be executed by placing SBS(91) in the main program at the point where the subroutine is desired. The subroutine number used in SBS(91) indicates the desired subroutine. When SBS(91) is executed (i.e., when the execution condition for it is ON), the instructions between the SBN(92) with the same subroutine number and the first RET(93) after it are executed before execution returns to the instruction following the SBS(91) that made the call.
Main program
SBS(91) 00
Main program
SBN(92) 00
Subroutine
RET(93)
END(01)
SBS(91) may be used as many times as desired in the program, i.e., the same subroutine may be called from different places in the program).
SBS(91) may also be placed into a subroutine to shift program execution from one subroutine to another, i.e., subroutines may be nested. When the second subroutine has been completed (i.e., RET(93) has been reached), program execution returns to the original subroutine which is then completed before returning to the main program. Nesting is possible to up to sixteen levels. A subroutine cannot call itself (e.g., SBS(91) 00 cannot be programmed within the subroutine defined with SBN(92) 00). The following diagram illustrates two levels of nesting.
SBN(92) 10 SBN(92) 11 SBN(92) 12
SBS(91) 10 SBS(91) 11 SBS(91) 12
RET(93) RET(93) RET(93)
258
Subroutines and Interrupt Control Section 5-23
The following diagram illustrates program execution flow for various execution conditions for two SBS(91).
Main program
A
SBS(91)
B
SBS(91)
00
01
OFF execution conditions for subroutines 00 and 01
A B C
ON execution condition for subroutine 00 only
A D B C
C
Flags
SBN(92)
D
RET(93)
SBN(92)
00
ON execution condition for subroutine 01 only
A B E C
Subroutines
01
ON execution conditions for subroutines 00 and 01
A D B E C
E
RET(93)
END(01)
Note A non-fatal error (error code 8B) will be generated if a subroutine’s execution time exceeds 10 ms.
ER: A subroutine does not exist for the specified subroutine number.
A subroutine has called itself.
An active subroutine has been called.
!
Caution SBS(91) will not be executed and the subroutine will not be called when ER is
ON.
5-23-4 SUBROUTINE DEFINE and RETURN – SBN(92)/RET(93)
Ladder Symbols Definer Data Areas
SBN(92) N
N: Subroutine number
00 to 99
RET(93)
Limitations
Description
Each subroutine number can be used in SBN(92) once only.
SBN(92) is used to mark the beginning of a subroutine program; RET(93) is used to mark the end. Each subroutine is identified with a subroutine number, N, that is programmed as a definer for SBN(92). This same subroutine number is used in any SBS(91) that calls the subroutine (see 5-23-3 SUBROUTINE EN-
TER – SBS(91)). No subroutine number is required with RET(93).
259
Subroutines and Interrupt Control Section 5-23
Precautions
All subroutines must be programmed at the end of the main program. When one or more subroutines have been programmed, the main program will be executed up to the first SBN(92) before returning to address 00000 for the next cycle. Subroutines will not be executed unless called by SBS(91).
END(01) must be placed at the end of the last subroutine program, i.e., after the last RET(93). It is not required at any other point in the program.
If SBN(92) is mistakenly placed in the main program, it will inhibit program execution past that point, i.e., program execution will return to the beginning when
SBN(92) is encountered.
If either DIFU(13) or DIFU(14) is placed within a subroutine, the operand bit will not be turned OFF until the next time the subroutine is executed, i.e., the operand bit may stay ON longer than one cycle.
Flags There are no flags directly affected by these instructions.
5-23-5 MACRO – MCRO(99)
Ladder Symbols
MCRO(99)
N
I1
O1
@MCRO(99)
N
I1
O1
Operand Data Areas
N: Subroutine number
00 to 99
I1: First input word
IR, SR, AR, DM, HR, TC, LR
O1: First output word
IR, SR, AR, DM, HR, LR
Limitations
Description
I1 and I1+3 must be in the same data area, as must O1 and O1+3.
The MACRO instruction allows a single subroutine to replace several subroutines that have identical structure but different operands. There are 4 input words, SR 290 to SR 293, and 4 output words, SR 294 to SR 297, allocated to
MCRO(99). These 8 words are used in the subroutine and take their contents from I1 to I1+3 and O1 to O1+3 when the subroutine is executed.
When the execution condition is OFF, MCRO(99) is not executed. When the execution condition is ON, MCRO(99) copies the contents of I1 to I1+3 to SR 290 to SR 293, copies the contents of O1 to O1+3 to SR 294 to SR 297, and then calls and executes the subroutine specified in N. When the subroutine is completed, the contents of SR 294 through SR 297 are then transferred back to O1 to O1+3 before MCRO(99) is completed.
260
Subroutines and Interrupt Control Section 5-23
In the following example, the contents of DM 0010 through DM 0013 are copied to SR 290 through SR 293, the contents of DM 0020 through DM 0023 are copied to SR 294 through SR 297, and subroutine 10 is called and executed.
When the subroutine is completed, the contents of SR 294 through SR 297 are copied back to DM 0020 to DM 0023.
Main program
MCRO(99) 10
DM 0010
DM 0020
Main program
Precautions
Flags
SBN(92)
Subroutine
RET(93)
END(01)
10
Note 1. Subroutines for macros are programmed just like other subroutines, except that SR 290 to SR 297 contents are transferred in from the designated input and output words.
2. Not only external I/O words, but internal I/O words can be used for I1 and O1.
3. SR 290 to SR 297 can be used as work bits when not used for macro programs.
MCRO(99) can be used only for program sections that can be written using four or fewer consecutive input words and/or four or fewer consecutive output words.
It is thus generally necessary to consider system and program design together to take full advantage of macro programming.
Be careful that the input and output words properly correspond to the macro input and output words.
ER: A subroutine does not exist for the specified subroutine number.
An operand has exceeded a data area boundary.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
A subroutine has called itself.
An active subroutine has been called.
261
Subroutines and Interrupt Control
Example
Section 5-23
The following examples shows the use of four MCRO(99) instructions that access the same subroutine. The program section on the left shows the same program without the use of MCRO(99).
00000
10000
00001 00002
10001
00200
10500
00201 00202
10501
00500
12000
00501 00502
12001
01000
15000
01001 01002
15001
10000
25313
Always ON Flag
10001
10500
10501
12000
12001
15000
29000
29400
29001 29002
29401
15001
MCRO(99)
MCRO(99)
090
002
105
MCRO(99)
090
000
100
090
005
120
MCRO(99)
090
010
150
29400
29401
RET(93)
5-23-6 INTERRUPT CONTROL – INT(89)
Limitations
INT(89)
C
N
D
Ladder Symbols
@INT(89)
C
N
D
Operand Data Areas
C: Control code
# (000, 001, 002, 100, or 200)
N: Interrupt type
# (000 or 004)
D: Control data
IR, AR, DM, HR, TC, LR, #
D must be between 0000 and 00FF when N=000 and C=000 or 001.
D must be BCD between 0001 and 9999 when N=004 and C=000 or 001.
262
Subroutines and Interrupt Control
Description
Mask/unmask Input
Interrupts (N=000, C=000)
Clear Input Interrupts
(N=000, C=001)
Read Current Mask Status
(N=000, C=002)
Set Interrupt Interval
(N=004, C=000)
Set Time to First Interrupt
(N=004, C=001)
Read Interrupt Interval
(N=004, C=002)
Mask/Unmasking All
Interrupts (C=100/200)
Section 5-23
INT(89) is used to control interrupts and performs one of 8 functions depending on the values of C and N. As shown in the following tables, three of the functions act on input interrupts, three act on the scheduled interrupt, and the other two mask or unmask all interrupts.
Interrupt Value of C
000
001
Scheduled
002
000
001
002
INT(89) Function Comments
Mask/unmask input interrupts Bits 00 to 07 of D indi-
Clear input interrupts
00 0
Status written to D.
Read current mask status
Set interrupt interval
Set time to first interrupt
Read interrupt interval
The following 2 functions depend on the value of C only.
Value of C
100
200
INT(89) Function
Mask all interrupts
Unmask all interrupts
This function is used to mask and unmask input interrupts 00 to 07. Masked inputs are recorded, but ignored. When an input is masked, the interrupt program for it will be run as soon as the bit is unmasked (unless it is cleared beforehand by executing INT(89) with C=001 and N=000).
Set the corresponding bit in D to 0 to unmask or to 1 to mask an I/O interrupt input. Bits 00 to 07 correspond to 00 to 07.
This function is used to clear I/O interrupt inputs 00 to 07. Since interrupt inputs are recorded, masked interrupts will be serviced after the mask is removed unless they are cleared first.
Set the corresponding bit in D to 1 to clear an interrupt input. Bits 00 to 07 correspond to 00 to 07.
This function is used to write the current mask status for input interrupts 00 to 07 to word D. The corresponding bit will be ON if the input is masked. (Bits 00 to 07 correspond to 00 to 07.)
This function is used to set the interval between scheduled interrupts. The content of D (BCD: 0001 to 9999) is multiplied by the scheduled interrupt time unit
(1 ms or 10 ms) to obtain the scheduled interrupt interval.
The scheduled interrupt time unit is set in DM 6622 of the PC Setup. Refer to
3-6-4 PC Setup for details on setting this time unit.
This function is used to set the time to the first scheduled interrupt. The content of D (BCD: 0001 to 9999) is multiplied by the scheduled interrupt time unit (1 ms or 10 ms) to obtain the time to the first scheduled interrupt. The scheduled interrupt time unit is set in DM 6622 of the PC Setup. Refer to 3-6-4 PC Setup for details on setting this time unit.
Be sure to set the time to the first interrupt. If this setting is not made, the interval to the first interrupt (set with N=004, C=000) will be uncertain.
Use the First Cycle Flag (SR 25315) for the execution condition to INT(89) when setting the time to the first interrupt (C=001). The scheduled interrupt might never occur if the C=001 setting is made continuously.
This function is used to write the current setting for the scheduled interrupt interval to word D.
This function is used to mask or unmask all interrupt processing. Masked inputs are recorded, but ignored. The masked inputs will be serviced as soon as they are unmasked. This function masks or unmask all interrupts at the same time and is independent of the masks created with other functions.
The control data, D, is not used for this function. Set D to #0000.
263
Subroutines and Interrupt Control
Flags
Example 1: Input Interrupt
Section 5-23
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
C, and/or N are not within specified values.
This example shows how to unmask a particular interrupt input. Input interrupt subroutines will be executed when the CPU receives the corresponding interrupt input, regardless of the location in the CPU’s cycle. These interrupts are useful when using program sections of uncertain length, such as event programs.
All input interrupts are masked at the start of operation, and the desired interrupt input is unmasked using INT(89) with N=000 and C=000. As shown in the following diagram, the subroutine would be executed if there were an input from input interrupt 00 when that interrupt input was unmasked.
First Cycle Flag
Only interrupt input
00 is unmasked.
Main program
LD
INT(89)
25315
000
000
#00FE
Main program
Interrupt from interrupt input 00
SBN(92)
Subroutine
00
RET(93)
END(01)
Example 2: Scheduled
Interrupt
Note Depending on the setting of DM 6621 in the PC Setup, Host Link servicing, Remote I/O servicing, Special I/O Unit servicing, and individual instruction execution will be completed before the subroutine is executed. Refer to page 255 for details.
This example shows how to set the interval between scheduled interrupts.
Scheduled interrupt subroutines will be executed at fixed intervals, regardless of the location in the CPU’s cycle. This interrupt is useful for program sections such as regular monitoring programs.
264
Subroutines and Interrupt Control Section 5-23
The scheduled interrupt is disabled at the start of operation (the scheduled interrupt interval is 0), so the time to the first interrupt and scheduled interrupt interval must be set using INT(89) with N=004 and C=001/000. In the following diagram, the subroutine would be executed every 20 ms if the scheduled interrupt time unit is set to 10 ms in DM 6622 of the PC Setup.
First Cycle Flag
Sets the time to first interrupt to 20 ms.
Main program
LD
INT(89)
INT(89)
25315
001
004
#0002
000
004
#0002
Sets the scheduled interrupt interval to 20 ms.
Main program
SBN(92)
Subroutine
00
Scheduled interrupt every 20 ms.
RET(93)
END(01)
Return to program address before interrupt.
Note Depending on the setting of DM 6621 in the PC Setup, Host Link servicing, Remote I/O servicing, Special I/O Unit servicing, and individual instruction execution will be completed before the subroutine is executed. Refer to page 255 for details.
265
Step Instructions Section 5-24
5-24 Step Instructions
The step instructions STEP(08) and SNXT(09) are used in conjunction to set up breakpoints between sections in a large program so that the sections can be executed as units and reset upon completion. A section of program will usually be defined to correspond to an actual process in the application. (Refer to the application examples later in this section.) A step is like a normal programming code, except that certain instructions (e.g., IL(02)/ILC(03), JMP(04)/JME(05)) may not be included.
5-24-1 STEP DEFINE and STEP START–STEP(08)/SNXT(09)
Ladder Symbols
STEP(08) B STEP(08)
Definer Data Areas
B: Control bit
IR, SR, AR, HR, LR
Limitations
Description
SNXT(09) B B: Control bit
IR, SR, AR, HR, LR
All control bits must be in the same word and must be consecutive.
IR 29800 to IR 29915 cannot be used for B.
STEP(08) uses a control bit in the IR or HR areas to define the beginning of a section of the program called a step. STEP(08) does not require an execution condition, i.e., its execution is controlled through the control bit. To start execution of the step, SNXT(09) is used with the same control bit as used for
STEP(08). If SNXT(09) is executed with an ON execution condition, the step with the same control bit is executed. If the execution condition is OFF, the step is not executed. The SNXT(09) instruction must be written into the program so that it is executed before the program reaches the step it starts. It can be used at different locations before the step to control the step according to two different execution conditions (see example 2, below). Any step in the program that has not been started with SNXT(09) will not be executed.
Once SNXT(09) is used in the program, step execution will continue until
STEP(08) is executed without a control bit. STEP(08) without a control bit must be preceded by SNXT(09) with a dummy control bit. The dummy control bit may be any unused IR or HR bit. It cannot be a control bit used in a STEP(08).
266
Step Instructions Section 5-24
Execution of a step is completed either by execution of the next SNXT(09) or by turning OFF the control bit for the step (see example 3 below). When the step is completed, all of the IR and HR bits in the step are turned OFF. All timers in the step except TTIM(––) are reset to their SVs. TTIM(––), counters, shift registers, bits set or reset with SET or RSET, and bits used in KEEP(11) maintain status.
Two simple steps are shown below.
00000
Step controlled by LR 2000
SNXT(09) LR 2000
Starts step execution
STEP(08) LR 2000
1st step
00001
SNXT(09) LR 2001
STEP(08) LR 2001
Step controlled by LR 2001
2nd step
00002
SNXT(09) 2002
STEP(08) Ends step execution
Address Instruction
00000 LD
00001 SNXT(09)
00002 STEP(08)
LR
LR
Operands
00000
2000
2000
Step controlled by 20200.
00100 LD
00101 SNXT(09) LR
00001
2001
Address Instruction
00102 STEP(08)
Operands
LR 2001
Step controlled by 20201.
00200 LD
00201 SNXT(09)
00202 STEP(08)
LR
---
00002
2002
Precautions
Steps can be programmed in consecutively. Each step must start with STEP(08) and generally ends with SNXT(09) (see example 3, below, for an exception).
When steps are programmed in series, three types of execution are possible: sequential, branching, or parallel. The execution conditions for, and the positioning of, SNXT(09) determine how the steps are executed. The three examples given below demonstrate these three types of step execution.
Interlocks, jumps, SBN(92), and END(01) cannot be used within step programs.
Bits used as control bits must not be used anywhere else in the program unless they are being used to control the operation of the step (see example 3, below).
All control bits must be in the same word and must be consecutive.
If IR or LR bits are used for control bits, their status will be lost during any power interruption. If it is necessary to maintain status to resume execution at the same step, HR bits must be used.
267
Step Instructions
Flags
Section 5-24
25407: Step Start Flag; turns ON for one cycle when STEP(08) is executed and can be used to reset counters in steps as shown below if necessary.
00000
00100
25407
SNXT(09) 01000
STEP(08) 01000
01000
Start
CP
R
CNT 01
#0003
25407
1 cycle
Address Instruction
00000 LD
00001 SNXT(09)
00002 STEP(08)
00003 LD
Operands
00000
01000
01000
00100
Address Instruction
00004 LD
00005 CNT
#
Operands
25407
01
0003
Examples
Example 1:
Sequential Execution
The following three examples demonstrate the three types of execution control possible with step programming. Example 1 demonstrates sequential execution; example 2, branching execution; and example 3, parallel execution.
The following process requires that three processes, loading, part installation, and inspection/discharge, be executed in sequence with each process being reset before continuing on the the next process. Various sensors (SW1, SW2,
SW3, and SW4) are positioned to signal when processes are to start and end.
SW 1
SW 2
SW 3
SW 4
268
Loading Part installation Inspection/discharge
Step Instructions Section 5-24
The following diagram demonstrates the flow of processing and the switches that are used for execution control.
Process A
SW1
Process B
SW2
SW3
Process C
SW4
Loading
Part Installation
Inspection/discharge
269
Step Instructions Section 5-24
The program for this process, shown below, utilizes the most basic type of step programming: each step is completed by a unique SNXT(09) that starts the next step. Each step starts when the switch that indicates the previous step has been completed turns ON.
00001 (SW1)
00002 (SW2)
Process A
00003 (SW3)
Process B
00004 (SW4)
Process C
SNXT(09) 12800
Process A started.
STEP(08) 12800
SNXT(09) 12801
Process A reset.
Process B started.
STEP(08) 12801
SNXT(09) 12802
Process B reset.
Process C started.
STEP(08) 12802
SNXT(09) 12803
Process C reset.
STEP(08)
Address Instruction
00000 LD
00001 SNXT(09)
00002 STEP(08)
Process A
00100 LD
00101 SNXT(09)
00102 STEP(08)
Operands
00001
12800
12800
00002
12801
12801
Address Instruction
Process B
00100 LD
00101 SNXT(09)
00102 STEP(08)
Process C
00200 LD
00201 SNXT(09)
00202 STEP(08)
Operands
00003
12802
12802
00004
12803
---
270
Step Instructions
Example 2:
Branching Execution
Weight scale
Section 5-24
The following process requires that a product is processed in one of two ways, depending on its weight, before it is printed. The printing process is the same regardless of which of the first processes is used. Various sensors are positioned to signal when processes are to start and end.
SW A1
SW A2
Printer
SW D
Process A
Process B
SW B1
SW B2
Process C
The following diagram demonstrates the flow of processing and the switches that are used for execution control. Here, either process A or process B is used depending on the status of SW A1 and SW B1.
Process A
SW A1
SW A2
Process C
SW D
End
Process B
SW B1
SW B2
271
Step Instructions Section 5-24
The program for this process, shown below, starts with two SNXT(09) instructions that start processes A and B. Because of the way 00001 (SW A1) and
00002 (SB B1) are programmed, only one of these will be executed to start either process A or process B. Both of the steps for these processes end with a
SNXT(09) that starts the step for process C.
00001 (SW A1) 00002 (SW B2)
00001 (SW A1) 00002 (SW B2)
00003 (SW A2)
Process A
00004 (SW B2)
Process B
00005 (SW D)
Process C
SNXT(09) HR 0000
SNXT(09) HR 0001
STEP(08) HR 0000
Process A started.
SNXT(09) HR 0002
Process A reset.
Process C started.
STEP(08) HR 0001
SNXT(09) HR 0002
Process B reset.
Process C started.
STEP(08) HR 0002
SNXT(09) HR 0003
Process C reset.
STEP(08)
Address Instruction
00000 LD
00001 AND NOT
00002 SNXT(09)
00003 LD NOT
00004 AND
00005 SNXT(09)
00006 STEP(08)
Process A
00100 LD
00101 SNXT(09)
00102 STEP(08)
Operands
HR
HR
HR
00001
00002
0000
00001
00002
0001
0000
HR
HR
00003
0002
0001
Address Instruction
Process B
00100 LD
00101 SNXT(09)
00102 STEP(08)
Process C
00200 LD
00201 SNXT(09)
00202 STEP(08)
Operands
HR
HR
HR
---
00004
0002
0002
00005
0003
272
Step Instructions
Example 3:
Parallel Execution
SW1
Section 5-24
The following process requires that two parts of a product pass simultaneously through two processes each before they are joined together in a fifth process.
Various sensors are positioned to signal when processes are to start and end.
Process A
SW3 SW5 SW7
Process B
Process D
Process E
SW2
Process C
SW4
SW6
The following diagram demonstrates the flow of processing and the switches that are used for execution control. Here, process A and process C are started together. When process A finishes, process B starts; when process C finishes, process D starts. When both processes B and D have finished, process E starts.
Process A
Process B
SW3
SW 1 and SW2 both ON
SW5 and SW6 both ON
Process E
SW7
End
Process C
Process D
SW4
The program for this operation, shown below, starts with two SNXT(09) instructions that start processes A and C. These instructions branch from the same instruction line and are always executed together, starting steps for both A and C.
When the steps for both A and C have finished, the steps for process B and D begin immediately.
When both process B and process D have finished (i.e., when the status for both of them is “ON”, but SW5 and SW6 have turned ON), processes B and D are reset together by the SNXT(09) at the end of the programming for process B.
Although there is no SNXT(09) at the end of process D, the control bit for it is turned OFF by executing SNXT(09) LR 0004. This is because the OUT for LR
0003 is in the step reset by SNXT(09) LR 0004, i.e., LR 003 is turned OFF when
SNXT(09) LR 0004 is executed Process B is thus reset directly and process D is reset indirectly before executing the step for process E.
273
Step Instructions
00001 (SW1 and SW2))
SNXT(09) LR 0000
Process A started.
Process C started.
SNXT(09) LR 0002
STEP(08) LR 0000
Section 5-24
Process A
00002 (SW3)
SNXT(09) LR 0001
Process A reset.
Process B started.
STEP(08) LR 0001
Process B
01101
00003 (SW4)
00004 (SW5 and SW6)
LR 0003
Used to turn off process D.
SNXT(09) LR 0004
Process E started.
STEP(08) LR 0002
Process C
SNXT(09) LR 0003
Process C reset.
Process D started.
STEP(08) LR 0003
Process D
STEP(08) LR 0004
Process E
00005 (SW7)
SNXT(09) LR 0005
Process E reset.
STEP(08)
274
Special Instructions
Address Instruction
00000 LD
00001 SNXT(09)
00002 SNXT(09)
00003 STEP(08)
Process A
00100 LD
00101 SNXT(09)
00102 STEP(08)
Process B
00100 LD
00101 OUT
0003
00101 AND
00101 SNXT(09)
LR
LR
LR
Operands
00001
0000
0002
0000
LR
LR
LR
00002
0001
0001
01101
LR
00004
0004
Address Instruction
00102 STEP(08)
Process C
00200 LD
00201 SNXT(09)
00202 STEP(08)
Process D
00300 STEP(08)
Process E
00400 LD
00401 SNXT(09)
00402 STEP(08)
Operands
LR 0002
LR
LR
LR
LR
00003
0003
0003
0004
00005
0005
---
Section 5-25
5-25 Special Instructions
The instructions in this section are used for various operations, including programming user error codes and messages, counting ON bits, setting the watchdog timer, and refreshing I/O during program execution.
5-25-1 FAILURE ALARM – FAL(06) and
SEVERE FAILURE ALARM – FALS(07)
Ladder Symbols
FAL(06) N @FAL(06) N
Definer Data Areas
N: FAL number
# (00 to 99)
Limitations
Description
FALS(07) N
N: FAL number
# (01 to 99)
FAL(06) and FALS(07) share the same FAL numbers. Be sure to use a number in either FAL(06) or FALS(07), not both.
FAL(06) and FALS(07) are provided so that the programmer can output error numbers for use in operation, maintenance, and debugging. When executed with an ON execution condition, either of these instructions will output a FAL number to bits 00 to 07 of SR 253. The FAL number that is output can be between 01 and 99 and is input as the definer for FAL(06) or FALS(07). FAL(06) with a definer of 00 is used to reset this area (see below).
FAL Area
25307 25300
X10 1 X10 0
275
Special Instructions
Resetting Errors
Clearing Messages
Section 5-25
FAL(06) produces a non-fatal error and FAL(07) produces a fatal error. When
FAL(06) is executed with an ON execution condition, the ALARM/ERROR indicator on the front of the CPU will flash, but PC operation will continue. When
FALS(07) is executed with an ON execution condition, the ALARM/ERROR indicator will light and PC operation will stop.
The system also generates error codes to the FAL area.
All FAL error codes will be retained in memory, although only one of these is available in the FAL area. To access the other FAL codes, reset the FAL area by executing FAL(06) 00. Each time FAL(06) 00 is executed, another FAL error will be moved to the FAL area, clearing the one that is already there. FAL error codes are recorded and will be recalled in the following order: First code generated, 9A,
9B, 9D, 8A, 8B, and then 01 to 99.
FAL(06) 00 is also used to clear message programmed with the instruction,
MSG(46).
If the FAL area cannot be cleared, as is generally the case when FALS(07) is executed, first remove the cause of the error and then clear the FAL area through the Programming Console (see 4-6-5 Clearing Error Messages).
5-25-2 CYCLE TIME – SCAN(18)
Ladder Symbols
SCAN(18)
Mi
000
000
@SCAN(18)
Mi
000
000
Operand Data Areas
Mi: Multiplier (BCD)
IR, SR, AR, DM, HR, TC, LR, #
000: Not used.
000: Not used.
Limitations
Description
Flags
276
Mi must be BCD. Only the rightmost three digits of Mi are used.
SCAN(18) is used to set a minimum cycle time. Mi is the minimum cycle time that will be set in tenths of milliseconds, e.g., if Mi is 1200, the minimum cycle time will be 120.0 ms. The possible setting range is from 000.0 to 999.9 seconds.
If the actual cycle time is less than the cycle time set with SCAN(18) the CPU will wait until the designated time has elapsed before starting the next cycle. If the actual cycle time is greater than the set time, the set time will be ignored and the program will be executed to completion.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
Mi is not BCD.
Special Instructions Section 5-25
5-25-3 TRACE MEMORY SAMPLING – TRSM(45)
Data tracing can be used to facilitate debugging programs. To set up and use data tracing it is necessary to have a host computer running LSS; no data tracing is possible from a Programming Console. Data tracing is described in detail in the LSS Operation Manual. This section shows the ladder symbol for
TRSM(45) and gives an example program.
Ladder Symbol
TRSM(45)
Description
AR Control Bits and Flags
Precautions
Example
TRSM(45) is used in the program to mark locations where specified data is to be stored in Trace Memory. Up to 12 bits and up to 3 words may be designated for tracing (refer to the LSS Operation Manual for details).
TRSM(45) is not controlled by an execution condition, but rather by two bits in the AR area: AR 2515 and AR 2514. AR 2515 is the Sampling Start bit.
This bit is turned ON to start the sampling processes for tracing. The Sampling Start bit must not be turned ON from the program, i.e., it must be turned
ON only from the peripheral device. AR 2514 is the Trace Start bit. When it is set, the specified data is recorded in Trace Memory. The Trace Start bit can be set either from the program or from the Programming Device. A positive or negative delay can also be set to alter the actual point from which tracing will begin.
Data can be recorded in any of three ways. TRSM(45) can be placed at one or more locations in the program to indicate where the specified data is to be traced. If TRSM(45) is not used, the specified data will be traced when
END(01) is executed. The third method involves setting a timer interval from the peripheral devices so that the specified data will be tracing at a regular interval independent of the cycle time (refer to the LSS Operation Manual).
TRSM(45) can be incorporated anywhere in a program, any number of times.
The data in the trace memory can then be monitored via a Programming
Console, host computer, etc.
The following control bits and flags are used during data tracing. The Tracing
Flag will be ON during tracing operations. The Trace Completed Flag will turn
ON when enough data has been traced to fill Trace Memory.
Flag
AR 2515
AR 2514
AR 2513
AR 2512
Function
Sampling Start Bit
Trace Start Bit
Tracing Flag
Trace Completed Flag
If TRSM(45) occurs TRSM(45) will not be executed within a JMP(08) – JME(09) block when the jump condition is OFF.
The following example shows the basic program and operation for data tracing.
Force set the Sampling Start Bit (AR 2515) to begin sampling. The Sampling
Start Bit must not be turned ON from the program. The data is read and stored into trace memory.
When IR 00000 is ON, the Trace Start Bit (AR 2514) is also turned ON, and the
CPU looks at the delay and marks the trace memory accordingly. This can mean that some of the samples already made will be recorded as the trace memory
(negative delay), or that more samples will be made before they are recorded
(positive delay).
277
Special Instructions
00000
Section 5-25
The sampled data is written to trace memory, jumping to the beginning of the memory area once the end has been reached and continuing up to the start marker. This might mean that previously recorded data (i.e., data from this sample that falls before the start marker) is overwritten (this is especially true if the delay is positive). The negative delay cannot be such that the required data was executed before sampling was started.
AR
2514
Starts data tracing.
AR 2513 ON when tracing
TRSM(45)
Designates point for tracing.
00200
Indicates that tracing is in progress.
AR 2512 ON when trace is complete
00201
Indicates that tracing has been completed.
Address Instruction
00000 LD
00001 OUT
00002 TRSM(45)
00003 LD
Operands
AR
0000
2514
AR 2513
Address Instruction
00004 OUT
00005 LD
00006 OUT
5-25-4 MESSAGE DISPLAY – MSG(46)
Operands
AR
00200
2512
00201
Ladder Symbols
MSG(46)
FM
@MSG(46)
FM
Operand Data Areas
FM: First message word
IR, AR, DM, HR, LR
Limitations
Description
Message Buffering and
Priority
FM and FM+7 must be in the same data area.
When executed with an ON execution condition, MSG(46) reads eight words of extended ASCII code from FM to FM+7 and displays the message on the Programming Console. The displayed message can be up to 16 characters long, i.e., each ASCII character code requires eight bits (two digits). Refer to Appendix
I for the extended ASCII codes. Japanese katakana characters are included in this code.
If not all eight words are required for the message, it can be stopped at any point by inputting “OD”. When OD is encountered in a message, no more words will be read and the words that normally would be used for the message can be used for other purposes.
Up to three messages can be buffered in memory. Once stored in the buffer, they are displayed on a first in, first out basis. Since it is possible that more than three
MSG(46)s may be executed within a single cycle, there is a priority scheme, based on the area where the messages are stored, for the selection of those messages to be buffered.
The priority of the data areas is as follows for message display:
LR > IR (I/O) > IR (not I/O) > HR > AR > TC > DM
In handling messages from the same area, those with the lowest address values have higher priority.
278
Special Instructions
Clearing Messages
Flags
Example
00000
00001
Section 5-25
In handling indirectly addressed messages (i.e. : DM), those with the lowest DM address values have higher priority.
To clear a message, execute FAL(06) 00 or clear it via a Programming Console using the procedure in 4-6-5 Clearing Error Messages.
If the message data changes while the message is being displayed, the display will also change.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
The following example shows the display that would be produced for the instruction and data given when 00000 was ON. If 00001 goes ON, a message will be cleared.
MSG(46)
DM 0010
FAL(06) 00
Address Instruction
00000 LD
00001 MSG(46)
00002 LD
00003 FAL(06)
Operands
00000
DM 0010
00001
00
DM 0010 4
DM 0011 4
DM 0012 4
DM 0013 4
DM 0014 4
DM 0015 4
DM 0016 4
DM 0017 4
DM contents
9
B
D
F
5
7
1
3
4
5
4
4
4
4
4
4
E
0
A
C
6
8
2
4
I
K
M
O
A
C
E
G
ASCII equivalent
J
L
N
P
B
D
F
H
5-25-5 LONG MESSAGE – LMSG(47)
MSG
ABCDEFGHIJKLMNOP
Ladder Symbols
LMSG(47)
S
---
---
@LMSG(47)
S
---
---
Operand Data Areas
S: First source word (ASCII)
IR, SR, AR, DM, HR, TC, LR
---: Not used.
Set to 000
---: Not used.
Set to 000
Limitations S through S+15 must be in the same data area and must be in ASCII. The message will be truncated if a null character (00) is contained between S and S+15.
IR 298 and IR 299 cannot be used for S.
279
Special Instructions
Description
Section 5-25
LMSG(47) is used to output a 32-character message to a Programming Console. The message to be output must be in ASCII beginning in word S and ending in S+15, unless a shorter message is desired. A shorter message can be produced by placing a null character (00) into the string; no characters from the null character on will be output.
To output to the Programming Console, it must be set in TERMINAL mode. Although LMSG(47) will be executed as normal, the message will not appear correctly on the Programming Console unless TERMINAL mode is set. Refer to
5-25-6 TERMINAL MODE – TERM(48) for details on switching to TERMINAL mode.
When pin 6 of the CPU’s DIP switch is OFF, the Programming Console can be switched to TERMINAL mode by pressing the CHG Key or by executing
TERM(48) in the program. When pin 6 of the CPU’s DIP switch is ON, the Programming Console can be switched to Expansion TERMINAL mode by turning on bit AR 0709.
Flags
Example
ER: S and S+15 are not in the same data area.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
Although the display is longer and there is a choice of output devices, the coding for LMSG(47) is the same as that for MSG(46). Refer to Example under the previous section for an example using MSG(46).
5-25-6 TERMINAL MODE – TERM(48)
Ladder Symbols
TERM(48)
000
000
000
@TERM(48)
000
000
000
Description When the execution condition is OFF, TERM(48) is not executed. When the execution condition is ON, TERM(48) switches the Programming Console to TER-
MINAL mode. (Instructions MSG(46), LMSG(47), and the keyboard mapping function are executed in TERMINAL mode.)
The Programming Console will return to CONSOLE mode when the CHG key is pressed again. There is no instruction that returns the Programming Console to
CONSOLE mode from the program.
The Programming Console can also be switched to TERMINAL mode by pressing the CHG key on the Programming Console before inputting the password or when the mode is being displayed provided that pin 6 of the CPU’s DIP switch is
OFF. The Programming Console will return to CONSOLE mode when the CHG key is pressed again.
When pin 6 of the CPU’s DIP switch is ON, the Programming Console can be switched to Expansion TERMINAL mode by turning on bit AR 0709.
280
Special Instructions
Example
00000
Section 5-25
In the following example, TERM(48) is used to switch the Programming Console to TERMINAL mode when 00000 is ON. Be sure that pin 6 of the CPU’s DIP switch is OFF.
TERM(48)
000
000
000
Address Instruction
00000 LD
00001 TERM(48)
Operands
00000
000
000
000
5-25-7 WATCHDOG TIMER REFRESH – WDT(94)
Ladder Symbols
WDT(94) T @WDT(94) T
Definer Data Areas
T: Watchdog timer value
# (00 to 63)
Description
Precautions
When the execution condition is OFF, WDT(94) is not executed. When the execution condition is ON, WDT(94) extends the setting of the watchdog timer (normally set by the system to 130 ms) by 100 ms times T.
Timer extension = 100 ms x T.
If the cycle time is longer than the time set for the watchdog timer, 9F will be output to the FAL area and the CPU will stop.
If the cycle time exceeds 6,500 ms, a FALS 9F will be generated and the system will stop.
Timers might not function properly when the cycle time exceeds 100 ms. When using WDT(94), the same timer should be repeated in the program at intervals that are less than 100 ms apart. TIMH(15) should be used only in a scheduled interrupt routine executed at intervals of 10 ms or less.
Flags There are no flags affected by this instruction.
5-25-8 I/O REFRESH – IORF(97)
Ladder Symbol
IORF(97)
St
E
Operand Data Areas
St: Starting word
IR 000 to IR 049
E: End word
IR 000 to IR 049
Limitations
Description
IORF(97) can be used to refresh I/O words allocated to only I/O Units (IR 000 to
IR 039) and Special I/O Units (IR 100 to IR 199) mounted to the CPU or Expansion I/O Racks. It cannot be used for other I/O words, such as I/O Units on Slaves
Racks or Group-2 High-density I/O Units.
St must be less than or equal to E.
To refresh I/O words allocated to CPU or Expansion I/O Racks (IR 000 to
IR 030), simply indicate the first (St) and last (E) I/O words to be refreshed.
When the execution condition for IORF(97) is ON, all words between St and E will be refreshed. This will be in addition to the normal I/O refresh performed during the CPU’s cycle.
281
Special Instructions Section 5-25
Execution Time
To refresh I/O words allocated to Special I/O Units (IR 100 to IR 199), indicate the unit numbers of the Units by designating IR 040 to IR 049 (see note). IR 040 to
IR 049 correspond to Special I/O Units 0 to 9. For example, set St to IR 043 and E to IR 045 to refresh the I/O words allocated to Special I/O Units 3, 4, and 5. The
I/O words allocated to those Units (IR 130 to IR 159) will be refreshed when
IORF(97) is executed.This will be in addition to the normal I/O refresh performed during the CPU’s cycle.
Note I/O will not be refreshed if IORF(97) is executed for any of the following Units:
• Group-2 High-density I/O Units
• I/O Units or Special I/O Units mounted to Slave Racks (in Remote I/O Systems)
•
Optical I/O Units (in Remote I/O Systems)
Refer to 5-25-9 GROUP-2 HIGH-DENSITY I/O REFRESH – MPRF(61) for details on refreshing words allocated to Group-2 High-density I/O Units.
When Basic I/O Units are specified, the execution time for IORF(97) is computed as follows:
T
IORF
= instruction execution time + Input Unit I/O refresh time
+ Output Unit I/O refresh time
= 0.13 ms + 0.02 ms
×
(no. of 8-pt Units + no. of 16-pt Units
×
2)
+ 0.02 ms
×
(no. of 5- and 8-pt Units + no. of 12-/16-pt Units
×
2)
When Special I/O Units are specified, the execution time for IORF(97) is computed as follows:
T
IORF
= instruction execution time + ∑ (Special I/O Unit I/O refresh times)
The instruction execution time is 0.1 ms. Refer to 6-1 Cycle Time for I/O refresh times for Special I/O Units.
Flags There are no flags affected by this instruction.
5-25-9 GROUP-2 HIGH-DENSITY I/O REFRESH – MPRF(61)
Ladder Symbol
MPRF(61)
St
E
---
Operand Data Areas
St: Starting Unit
#0000 to #0009
E: End Unit
#0000 to #0009
Limitations
Description
Execution Time
MPRF(61) can be used to refresh I/O words allocated to Group-2 High-density
I/O Units (IR 030 to IR 049) only. It cannot be used for other I/O words.
St and E must be between #0000 and #0009. St must be less than or equal to E.
When the execution condition is OFF, MPRF(61) is not executed. When the execution condition is ON, the I/O words allocated to Group-2 High-density I/O
Units with I/O numbers St through E will be refreshed.This will be in addition to the normal I/O refresh performed during the CPU’s cycle.
It is not possible to specify the I/O words by address, only by the I/O number of the Unit to which they are allocated.
The execution time for MPRF(61) is computed as follows:
T
MPRF
= Instruction execution time
+
∑
(Group-2 High-density I/O Unit I/O refresh times)
282
Special Instructions Section 5-25
Refer to 6-1 Cycle Time for a table showing I/O refresh times for Group-2
High-density I/O Units.
Flags ER: St or E is not BCD between #0000 and #0009.
St is greater than E.
5-25-10 BIT COUNTER – BCNT(67)
Ladder Symbols
BCNT(67)
N
SB
D
@BCNT(67)
N
SB
D
Operand Data Areas
N: Number of words (BCD)
IR, SR, AR, DM, HR, TC, LR, #
SB: Source beginning word
IR, SR, AR, DM, HR, TC, LR
D: Destination word
IR, SR, AR, DM, HR, TC, LR
Limitations
Description
N must be BCD between 0000 and 6656.
When the execution condition is OFF, BCNT(67) is not executed. When the execution condition is ON, BCNT(67) counts the total number of bits that are ON in all words between SB and SB+(N–1) and places the result in D.
Flags ER: N is not BCD, or N is 0; SB and SB+(N–1) are not in the same area.
The resulting count value exceeds 9999.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
5-25-11 FRAME CHECKSUM – FCS(––)
FCS(––)
C
R
1
D
Ladder Symbols
@FCS(––)
C
R
1
D
Operand Data Areas
C: Control data
IR, SR, AR, DM, HR, LR
R
1
: First word in range
IR, SR, AR, DM, HR, TC, LR
D: First destination word
IR, SR, AR, DM, HR, LR
Description FCS(––) can be used to check for errors when transferring data through communications ports.
When the execution condition is OFF, FCS(––) is not executed. When the execution condition is ON, FCS(––) calculates the frame checksum of the specified range by exclusively ORing either the contents of words R
1
to R
1
+N–1 or the bytes in words R
1
to R
1
+N–1. The frame checksum value (hexadecimal) is then converted to ASCII and output to the destination words (D and D+1).
283
Special Instructions Section 5-25
The function of bits in C are shown in the following diagram and explained in more detail below.
C: 15 14 13 12 11
Not used. Set to zero.
00
Number of items in range (N, BCD)
001 to 999 words or bytes
First byte (when bit 13 is ON)
1 (ON): Rightmost
0 (OFF): Leftmost
Calculation units
1 (ON): Bytes
0 (OFF): Words
Number of Items in Range
Calculation Units
The number of items within the range (N) is contained in the 3 rightmost digits of
C, which must be BCD between 001 and 999.
The frame checksum of words will be calculated if bit 13 is OFF and the frame checksum of bytes will be calculated if bit 13 is ON.
If bytes are specified, the range can begin with the leftmost or rightmost byte of
R
1
. The leftmost byte of R
1
will not be included if bit 12 is ON.
R
1
R
1
+1
R
1
+2
R
1
+3
5
7
MSB LSB
1
3
2
4
6
8
Conversion to ASCII
Flags
When bit 12 is OFF the bytes will be ORed in this order: 1, 2, 3, 4, ....
When bit 12 is ON the bytes will be ORed in this order: 2, 3, 4, 5, ....
The byte frame checksum calculation yields a 2-digit hexadecimal value which is converted to its 4-digit ASCII equivalent. The word frame checksum calculation yields a 4-digit hexadecimal value which is converted to its 8-digit ASCII equivalent, as shown below.
Byte frame checksum value
4A
Word frame checksum value
F10B
D 3 4 4 1 D+1 4 6 3 1 D 3 0 4 2
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
The number of items is not 001 to 999 BCD.
284
Special Instructions
Example
00000
Section 5-25
When IR 00000 is ON in the following example, the frame checksum (0008) is calculated for the 8 words from DM 0000 to DM 0007 and the ASCII equivalent
(30 30 30 38) is written to DM 0011 and DM 0010.
@FCS(––)
#0008
DM 0000
DM 0010
Address Instruction
00000 LD
00001 @FCS(––)
#
DM
DM
Operands
00000
0008
0000
0010
DM 0000 0001
DM 0001 0002
DM 0002 0003
DM 0003 0004
DM 0004 0005
DM 0005 0006
DM 0006 0007
DM 0007 0008
FCS calculation
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0 0 0 8
ASCII code conversion
DM 0011 3 0 3 0 DM 0010 3 0 3 8
5-25-12 FAILURE POINT DETECTION – FPD(––)
Ladder Symbols
FPD(––)
C
T
D
Operand Data Areas
C: Control data
#
T: Monitoring time (BCD)
IR, SR, AR, DM, HR, TC. LR, #
D: First register word
IR, AR, DM, HR, LR
Limitations
Description
D and D+8 must be in the same data area when bit 15 of C is ON.
C must be input as a constant.
FPD(––) can be used in the program as many times as desired, but each must use a different D. It is used to monitor the time between the execution of FPD(––) and the execution of a diagnostic output. If the time exceeds T, an FAL(06) nonfatal error will be generated with the FAL number specified in C.
The program sections marked by dashed lines in the following diagram can be written according to the needs of the particular program application. The processing programming section triggered by CY is optional and can used any instructions but LD and LD NOT. The logic diagnostic instructions and execution condition can consist of any combination of NC or NO conditions desired.
Branch
Execution condition
FPD(––)
C
T
D
SR 25504
(CY Flag)
Processing after error detection.
Logic diagnostic instructions
Diagnostic output
285
Special Instructions
Control Data
Section 5-25
When the execution condition is OFF, FPD(––) is not executed. When the execution condition is ON, FPD(––) monitors the time until the logic diagnostics condition goes ON, turning ON the diagnostic output. If this time exceeds T, the following will occur:
1, 2, 3...
1.
An FAL(06) error is generated with the FAL number specified in the first two digits of C. If 00 is specified, however, an error will not be generated.
2.
The logic diagnostic instructions are searched for the first OFF input condition and this condition’s bit address is output to the destination words beginning at D.
3.
The CY Flag (SR 25504) is turned ON. An error processing program section can be executed using the CY Flag if desired.
4.
If bit 15 of C is ON, a preset message with up to 8 ASCII characters will be displayed on the Peripheral Device along with the bit address mentioned in step 2.
The function of the control data bits in C are shown in the following diagram.
C: 15 14 08 07 00
Not used. Set to zero.
FAL number
(2-digit BCD, 00 to 99)
Diagnostics output
0 (OFF): Bit address output (binary)
1 (ON): Bit address and message output (ASCII)
Logic Diagnostic Instructions If the time until the logic diagnostics condition goes ON exceeds T, the logic diagnostic instructions are searched for the OFF input condition. If more than one input condition is OFF, the input condition on the highest instruction line and nearest the left bus bar is selected.
00000 00002
Diagnostic output
00001 00003
Diagnostics Output
When IR 00000 to IR 00003 are ON, the normally closed condition IR 00002 would be found as the cause of the diagnostic output not turning ON.
There are two ways to output the bit address of the OFF condition detected in the logic diagnostics condition.
1, 2, 3...
1.
Bit address output (used when bit 15 of C is OFF).
Bit 15 of D indicates whether or not bit address information is stored in D+1.
If there is, bit 14 of D indicates whether the input condition is normally open or closed.
D: 15 14 13 00
Not used.
Input condition
0 (OFF): Normally open
1 (ON): Normally closed
Bit address information
0 (OFF): Not recorded in D+1.
1 (ON): Recorded in D+1.
286
Special Instructions Section 5-25
D+1 contains the bit address code of the input condition, as shown below.
The word addresses, bit numbers, and TC numbers are in binary.
Data
IR, SR
D+1 bit status
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
1 0 0 0 Word address Bit number note c)
HR
LR
TC*
1 0 1 0 Word address Bit number
1 0 0 1 1 Word address
1 0 0 1 0 0 Word address
1 0 0 1 0 1 * Timer or counter number
Bit number
Bit number
Note a) *For the TC area, bit 09 of D+1 indicates whether the number is a timer or counter. A 0 indicates a timer, and a 1 indicates a counter.
b) The status of the leftmost bit of the bit number (bit 03) is reversed.
c) Although the same word address designations are used for both ranges, bit 13 is turned OFF to indicate IR 00000 through SR
25515 and turned ON to indicate SR 25600 through IR 51115
Example: If D + 1 contains 1000 0110 0100 1000, IR 10000 would be indicated as follows:
1000 0110 0100 1000
IR $64 = 100 Bit 00 (inverting status of bit 03)
2.
Bit address and message output (used when bit 15 of C is ON).
Bit 15 of D indicates whether or not there is bit address information stored in
D+1 to D+3. If there is, bit 14 of D indicates whether the input condition is normally open or closed. Refer to the following table.
Words D+5 to D+8 contain information in ASCII that are displayed on a Peripheral Device along with the bit address when FPD(––) is executed.
Words D+5 to D+8 contain the message preset by the user as shown in the following table.
Word
D+1
D+2
D+3
D+4
D+5
D+6
D+7
D+8
20 = space
Bits 15 to 08 Bits 07 to 00
First ASCII character of bit address
Second ASCII character of bit address Third ASCII character of bit address
Fourth ASCII character of bit address Fifth ASCII character of bit address
2D = “–” “0”=normally open,
“1”=normally closed
First ASCII character of message
Third ASCII character of message
Second ASCII character of message
Fourth ASCII character of message
Fifth ASCII character of message Sixth ASCII character of message
Seventh ASCII character of message Eighth ASCII character of message
Note If 8 characters are not needed in the message, input “0D” after the last character.
Determining Monitoring Time The procedure below can be used to automatically set the monitoring time, T, under actual operating conditions when specifying a word operand for T. This operation cannot be used if a constant is set for T.
1, 2, 3...
1.
Switch the C200HS to MONITOR Mode operation.
2.
Connect a Peripheral Device, such as a Programming Console.
3.
Use the Peripheral Device to turn ON control bit AR 2508.
4.
Execute the program with AR 2508 turned ON. If the monitoring time currently in T is exceeded, 1.5 times the actual monitoring time will be stored in
T. FAL(06) errors will not occur while AR 2508 is ON.
5.
Turn OFF AR 2508 when an acceptable value has been stored in T.
287
Special Instructions
Example
Section 5-25
In the following example, the FPD(––) is set to display the bit address and message (“ABC”) when a monitoring time of 123.4 s is exceeded.
SR 25315
SR 25315
LR 0000
10000
10001
HR 10
HR 11
HR 12
HR 13
HR 14
HR 15
HR 16
HR 17
HR 18
0000
0000
0000
0000
0000
4142
430D
0000
0000
SR 25504
(CY Flag)
10002
10003
MOV(21)
#4142
HR 15
MOV(21)
#430D
HR 16
FPD(––)
#8010
#1234
HR 10
INC(38)
DM 0100
LR 0015
Address Instruction
00000 LD
00001 MOV(21)
00002
00003
00004
00005
00006
00007
LD
MOV(21)
LD
FPD(––)
AND
INC(38)
00008 LD
00009 OR
00010 LD NOT
00011 OR NOT
00012 AND LD
00013 OUT
#
HR
LR
#
#
HR
#
HR
Operands
25315
4142
15
25315
430D
16
0000
DM
LR
8010
1234
10
25504
0100
10000
10001
10002
10003
0015
FPD(––) is executed and begins monitoring when LR 0000 goes ON. If LR 0015 does not turn ON within 123.4 s and IR 10000 through IR 10003 are all ON,
IR 10002 will be selected as the cause of the error, an FAL(06) error will be generated with an FAL number of 10, and the bit address and preset message
(“10002–1ABC”) will be displayed on the Peripheral Device.
HR 10
HR 11
HR 12
HR 13
HR 14
HR 15
HR 16
HR 17
HR 18
C000
2031
3030
3032
2D31
4142
430D
0000
0000
Indicates information, normally closed condition
“1”
“00”
“02”
“–1”
“AB”
“C”, and CR code
The last two words are ignored.
(Displayed as spaces.)
Flags ER: T is not BCD.
C is not a constant or the rightmost two digits of C are not BCD 00 to 99.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
CY: ON when the time between the execution of FPD(––) and the execution of a diagnostic output exceeds T.
288
Special Instructions
5-25-13 DATA SEARCH – SRCH(––)
Ladder Symbols
Limitations
Description
Flags
Section 5-25
SRCH(––)
N
R
1
C
@SRCH(––)
N
R
1
C
Operand Data Areas
N: Number of words
IR, SR, AR, DM, HR, TC, LR, #
R
1
: First word in range
IR, SR, AR, DM, HR, TC, LR
C: Comparison data, result word
IR, SR, AR, DM, HR, LR
N must be BCD between 0001 to 6656.
R
1
and R
1
+N–1 must be in the same data area.
When the execution condition is OFF, SRCH(––) is not executed. When the execution condition is ON, SRCH(––) searches the range of memory from R
1
to
R
1
+N–1 for addresses that contain the comparison data in C. If one or more addresses contain the comparison data, the EQ Flag (SR 25506) is turned ON and the lowest address containing the comparison data is identified in C+1. The address is identified differently for the DM area:
1, 2, 3...
1.
For an address in the DM area, the word address is written to C+1. For example, if the lowest address containing the comparison data is DM 0114, then #0114 is written in C+1.
2.
For an address in another data area, the number of addresses from the beginning of the search is written to C+1. For example, if the lowest address containing the comparison data is IR 114 and the first word in the search range is IR 014, then #0100 is written in C+1.
If none of addresses in the range contain the comparison data, the EQ Flag (SR
25506) is turned OFF and C+1 is left unchanged.
ER: Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
N is not BCD between 0001 and 6655.
EQ: ON when the comparison data has been matched in the search range.
289
Special Instructions
Example
00001
Section 5-25
In the following example, the 10 word range from DM 0010 to DM 0019 is searched for addresses that contain the same data as DM 0000 (#FFFF). Since
DM 0012 contains the same data, the EQ Flag (SR 25506) is turned ON and
#0012 is written to DM 0001.
@SRCH(––)
#0010
DM 0010
DM 0000
Address Instruction
00000 LD
00001 @SRCH(––)
#
DM
DM
Operands
00001
0010
0010
0000
DM 0010 0000
DM 0011 9898
DM 0012 FFFF
DM 0013 9797
DM 0014 AAAA
DM 0015 9595
DM 0016 1414
DM 0017 0000
DM 0018 0000
DM 0019 FFFF
5-25-14 EXPANSION DM READ – XDMR(––)
Ladder Symbols
Limitations
Description
Precautions
Flags
XDMR(––)
N
S
D
DM 0000 FFFF
DM 0001 0012
@XDMR(––)
N
S
D
Operand Data Areas
N: Number of words
IR, SR, AR, DM, HR, TC, LR, #
S: First expansion DM word
IR, SR, AR, DM, HR, TC, LR, #
D: First destination word
IR, SR, AR, DM, HR, LR
N must be BCD between 0001 and 3000.
S must be BCD between 7000 and 9999.
S and S+N–1 must be in the same data area, as must D and D+N–1.
When the execution condition is OFF, XDMR(––) is not executed. When the execution condition is ON, XDMR(––) copies the contents of expansion DM words S through S+N–1 to the destination words D through D+N–1.
The Expansion DM area must be set in the PC Setup before it can be used in programming. Do not exceed the set range of the Expansion DM area.
Execution of XDMR(––) is given priority whenever a power interruption occurs.
ER: The specified expansion DM words are non-existent. Make sure that the specified words have been allocated to expansion DM. Refer to
7-1-15 UM Area Allocation for details.
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
N is not BCD between 0001 and 3000.
S is not BCD between 7000 and 9999.
290
Network Instructions
Example
00001
Section 5-26
In the following example, the 100 word range from DM 7000 through DM 7099 is copied to DM 0010 through DM 0109 when IR 00001 is ON.
@XDMR(––)
#0100
#7000
DM 0010
Address Instruction
00000 LD
00001 @XDMR(––)
#
#
DM
Operands
00001
0100
7000
0010
DM 7000 to DM 7099
DM 7000 DM 9999
DM 0010 to DM 0109
DM 0000 DM 6143
5-26 Network Instructions
The SYSMAC NET Link/SYSMAC LINK instructions are used for communicating with other PCs linked through the SYSMAC NET Link System or SYSMAC
LINK System. These instructions are applicable to the C200H-CPU31-E and
CPU33-E only.
5-26-1 NETWORK SEND – SEND(90)
Ladder Symbols
SEND(90)
S
D
C
@SEND(90)
S
D
C
Operand Data Areas
S: Source beginning word
IR, SR, AR, DM, HR, TC, LR
D: Destination beginning word
IR, AR, DM, HR, TC, LR
C: First control data word
IR, AR, DM, HR, TC, LR
Limitations
Description
Can be performed with the CPU31-E/33-E only. C through C+2 must be within the same data area and must be within the values specified below. To be able to use SEND(90), the system must have a SYSMAC NET Link or SYSMAC LINK
Unit mounted.
When the execution condition is OFF, SEND(90) is not executed. When the execution condition is ON, SEND(90) transfers data beginning at word S, to addresses specified by D in the designated node on the SYSMAC NET Link/SYS-
MAC LINK System. The control words, beginning with C, specify the number of words to be sent, the destination node, and other parameters. The contents of the control data depends on whether a transmission is being sent in a SYSMAC
NET Link System or a SYSMAC LINK System.
291
Network Instructions Section 5-26
The status of bit 15 of C+1 determines whether the instruction is for a SYSMAC
NET Link System or a SYSMAC LINK System.
Control Data
SYSMAC NET Link Systems The destination port number is always set to 0. Set the destination node number to 0 to send the data to all nodes. Set the network number to 0 to send data to a node on the same Subsystem (i.e., network). Refer to the SYSMAC NET Link
System Manual for details.
Word
C
C+1
C+2
Bits 00 to 07 Bits 08 to 15
Number of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000 hex
to 03E8 hex
)
Network number (0 to 127 in 2-digit hexadecimal, i.e., 00 hex
to 7F hex
)
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bits 08 to 13 and 15: Set to 0.
Destination node (0 to 126 in 2-digit hexadecimal, i.e., 00 hex
to 7E hex
)*
Destination port
NSB: 00
NSU: 01/02
*The node number of the PC executing the send may be set.
SYSMAC LINK Systems
Examples
Set the destination node number to 0 to send the data to all nodes. Refer to the
SYSMAC LINK System Manual for details.
Word
C
C+1
C+2
Bits 00 to 07
Destination node (0 to 62 in 2-digit hexadecimal, i.e., 00 hex
to 3E hex
)*
Bits 08 to 15
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000 hex
to 0100 hex
)
Response time limit (0.1 and 25.4
seconds in 2-digit hexadecimal without decimal point, i.e., 00 hex
FF hex
)
to
Note: The response time will be
2 seconds if the limit is set to 0 hex
There will be no time limit if the time limit is set to FF hex
.
.
Bits 08 to 11:
No. of retries (0 to 15 in hexadecimal, i.e., 0 hex
to F hex
Bit 12: Set to 0.
)
Bit 13 ON: Response not returned.
OFF: Response returned.
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bit 15: Set to 1.
Set to 0.
*The node number of the PC executing the send cannot be set.
This example is for a SYSMAC NET Link System. When 00000 is ON, the following program transfers the content of IR 001 through IR 005 to LR 20 through LR
24 on node 10.
00000
DM 0010
DM 0011
DM 0012
15
0
0
0
0
0
0
0
0
0
5
0
A
0
IR 001
IR 002
IR 003
IR 004
IR 005
SEND(90)
001
LR 20
DM 0010
Node 10
LR 20
LR 21
LR 22
LR 23
LR 24
Address Instruction
00000 LD
00001 SEND(90)
LR
DM
Operands
00000
001
20
0010
292
Network Instructions
Flags
Section 5-26
ER: The specified node number is greater than 126 in a SYSMAC NET Link
System or greater than 62 in a SYSMAC LINK System.
The sent data overruns the data area boundaries.
Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
There is no SYSMAC NET Link/SYSMAC LINK Unit.
5-26-2 NETWORK RECEIVE – RECV(98)
Ladder Symbols
RECV(98)
S
D
C
@RECV(98)
S
D
C
Operand Data Areas
S: Source beginning word
IR, SR, AR, DM, HR, TC, LR
D: Destination beginning word
IR, AR, DM, HR, TC, LR
C: First control data word
IR, AR, DM, HR, TC, LR
Limitations
Description
Can be performed with the CPU31-E/33-E only. C through C+2 must be within the same data area and must be within the values specified below. To be able to use RECV(98), the system must have a SYSMAC NET Link or SYSMAC LINK
Unit mounted.
When the execution condition is OFF, RECV(98) is not executed. When the execution condition is ON, RECV(98) transfers data beginning at S from a node on the SYSMAC NET Link/SYSMAC LINK System to words beginning at D. The control words, beginning with C, provide the number of words to be received, the source node, and other transfer parameters.
The status of bit 15 of C+1 determines whether the instruction is for a SYSMAC
NET Link System or a SYSMAC LINK System.
Control Data
SYSMAC NET Link Systems The source port number is always set to 0. Set the network number to 0 to receive data to a node on the same Subsystem (i.e., network). Refer to the SYS-
MAC NET Link System Manual for details.
Word
C
C+1
C+2
Bits 00 to 07 Bits 08 to 15
Number of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000 hex
to 03E8 hex
)
Network number (0 to 127 in 2-digit hexadecimal, i.e., 00 hex
to 7F hex
)
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bits 08 to 13 and 15:
Set to 0.
Source node (1 to 126 in 2-digit hexadecimal, i.e., 01 hex
to 7E hex
)
Source port
NSB: 00
NSU: 01/02
293
Network Instructions Section 5-26
SYSMAC LINK Systems
Examples
00000
DM 0010
DM 0011
DM 0012
15
0
0
0
0
0
0
0
0
0
5
0
A
0
Refer to the SYSMAC LINK System Manual for details.
Word
C
C+1
C+2
Bits 00 to 07
Source node (0 to 62 in 2-digit hexadecimal, i.e., 00 hex
to 3E hex
)
Bits 08 to 15
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000 hex
to 0100 hex
)
Response time limit (0.1 and 25.4
seconds in 2-digit hexadecimal without decimal point, i.e., 00 hex
to
FF hex
)
Note: The response time will be
2 seconds if the limit is set to 0 hex
There will be no time limit if the time limit is set to FF hex
.
.
Bits 08 to 11:
No. of retries (0 to 15 in hexadecimal, i.e., 0 hex
to F hex
)
Bit 12: Set to 0.
Bit 13: Set to 0.
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bit 15: Set to 1.
Set to 0.
This example is for a SYSMAC NET Link System. When 00000 is ON, the following program transfers the content of IR 001 through IR 005 to LR 20 through LR
24 on node 10.
RECV(98)
001
LR 20
DM 0010
Address Instruction
00000 LD
00001 RECV(98)
LR
DM
Operands
00000
001
20
0010
Node 10
IR 001
IR 002
IR 003
IR 004
IR 005
LR 20
LR 21
LR 22
LR 23
LR 24
Flags ER: The specified node number is greater than 126 in a SYSMAC NET Link
System or greater than 62 in a SYSMAC LINK System.
The received data overflows the data area boundaries.
Indirectly addressed DM word is non-existent. (Content of
:
DM word is not BCD, or the DM area boundary has been exceeded.)
There is no SYSMAC NET Link/SYSMAC LINK Unit.
294
Network Instructions Section 5-26
5-26-3 About Network Communications
SEND(90) and RECV(98) are based on command/response processing. That is, the transmission is not complete until the sending node receives and acknowledges a response from the destination node. Note that the
SEND(90)/RECV(98) Enable Flag is not turned ON until the first END(01) after the transmission is completed. Refer to the SYSMAC NET Link System Manual or SYSMAC LINK System Manual for details about command/response operations.
If multiple SEND(90)/RECV(98) operations are used, the following flags must be used to ensure that any previous operation has completed before attempting further send/receive SEND(90)/RECV(98) operations
SR Flag
SEND(90)/RECV(98)
Enable Flags
(SR 25201, SR 25204)
SEND(90)/RECV(98)
Error Flags
(SR 25200, SR 25203)
Functions
OFF during SEND(90)/RECV(98) execution (including command response processing). Do not start a
SEND(90)/RECV(98) operation unless this flag is ON.
OFF following normal completion of SEND/RECV (i.e., after reception of response signal)
ON after an unsuccessful SEND(90)/RECV(98) attempt.
Error status is maintained until the next
SEND(90)/RECV(98) operation.
Error types:
Time-out error (command/response time greater than 1 second)
Transmission data errors
Timing
Successful send/receive execution
Send/receive error
Instruction received
Transmission completes normally
Instruction received
Transmission error
Instruction received
Data Processing for
SEND(90)/RECV(98)
Programming Example:
Multiple
SEND(90)/RECV(98)
Data is transmitted for SEND(90) and RECV(98) for all PCs when
SEND(90)/RECV(98) is executed. Final processing for transmissions/receptions is performed during servicing of peripheral devices and Link Units.
To ensure successful SEND(90)/RECV(98) operations, your program must use the SEND(90)/RECV(98) Enable Flags and SEND(90)/RECV(98) Error Flags to confirm that execution is possible. The following program shows one example of how to do this for a SYSMAC NET Link System.
295
Network Instructions
00000
SEND(90)/RECV(98) Enable Flag
25204 12802
12801
12800
296
12800
SEND(90)/RECV(98) Error Flag
25203
12800 25204
00001 25204 12800
12803
12802 25204 25203
12802
12802
SEND(90)/RECV(98) Error Flag
25203
12802 25204
Section 5-26
S
R
KEEP(11)
12800
@MOV(21)
#000A
DM 0000
@MOV(21)
#0000
DM 0001
@MOV(21)
#0003
DM 0002
XFER(70)
#0010
000
DM 0010
@SEND(90)
DM 0010
DM 0020
DM 0000
12800 prevents execution of SEND(90) until
RECV(98) (below) has completed. IR 00000 is turned ON to start transmission.
Data is placed into control data words to specify the 10 words to be transmitted to node 3 in operating level 1 of network 00
(NSB).
Turns ON to indicate transmission error.
00200
DIFU(13) 12801
S
R
KEEP(11)
12802
XFER(70)
#0016
000
DM 0030
@MOV(21)
#0010
DM 0003
@MOV(21)
#0000
DM 0004
@MOV(21)
#007E
DM 0005
@RECV(98)
HR 10
LR 10
DM 0003
00201
Resets 12800, above.
12802 prevents execution of RECV(98) when SEND(90) above has not completed.
IR 00001 is turned ON to start transmission.
Transmitted data moved into words beginning at DM 0030 for storage.
Data moved into control data words to specify the 16 words to be transmitted from node 126 in operating level 1 of network 00
(NSB).
Turns ON to indicate reception error.
DIFU(13) 12803 Resets 12802, above.
Serial Communications Instructions
Address Instruction
00000 LD
00001 AND
00002 AND NOT
00003 LD
00004 KEEP(11)
00005 LD
00006 @MOV(21)
00007 @MOV(21)
00008 @MOV(21)
00009 @XFER(70)
00010 @SEND(90)
#
DM
#
DM
DM
DM
DM
00011 LD
00012 AND
00013 OUT
00014 LD
00015 AND
00016 DIFU(13)
00017 LD
00018 AND
#
DM
#
DM
Operands
00000
25204
12802
12801
12800
12800
000A
0000
0000
0001
0003
00002
0010
000
0002
0010
0020
0000
12800
25203
00200
12800
25204
12801
00001
25204
Address Instruction
00019 AND NOT
00020 LD
00021 KEEP(11)
00022 LD
00023 AND
00024 AND NOT
00025 XFER(70)
00026 LD
00027 @MOV(21)
00028
00029
@MOV(21)
@MOV(21)
00030 @RECV(98)
#
DM
HR
LR
DM
#
DM
#
DM
00031 LD
00032 AND
00033 OUT
00034 LD
00035 AND
00036 DIFU(13)
#
DM
Operands
12800
12803
12802
12802
25204
25203
0016
000
0030
12802
0010
0003
0000
0004
007E
0005
10
10
0003
12802
25203
00201
12802
25204
12803
Section 5-27
5-27 Serial Communications Instructions
5-27-1 RECEIVE – RXD(––)
Ladder Symbols
Limitations
Description
RXD(––)
D
C
N
@RXD(––)
D
C
N
Operand Data Areas
D: First destination word
IR, SR, AR, DM, HR, TC, LR
C: Control word
IR, SR, AR, DM, HR, TC, LR, #
N: Number of bytes
IR, SR, AR, DM, HR, TC, LR, #
D and D+(N ÷ 2)–1 must be in the same data area.
N must be BCD from #0000 to #0256. (#0000 to #0061 in host link mode)
When the execution condition is OFF, RXD(––) is not executed. When the execution condition is ON, RXD(––) reads N bytes of data received at the peripheral port, and then writes that data in words D to D+(N
÷
2)–1. Up to 256 bytes of data can be read at one time.
If fewer than N bytes are received, the amount received will be read.
297
Serial Communications Instructions Section 5-27
Note RXD(––) is required to receive data via the peripheral port or RS-232C port only.
Transmission sent from a host computer to a Host Link Unit are processed automatically and do not need to be programmed.
!
Caution The PC will be incapable of receiving more data once 256 bytes have been received if received data is not read using RXD(––). Read data as soon as possible after the Reception Completed
Flag is turned ON (SR 26414 for peripheral port).
Control Word
Digit number: 3 2 1 0
The value of the control word determines the port from which data will be read and the order in which data will be written to memory.
Byte order 0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 00.)
Port 0: RS-232C port (C200HS-CPU21-E/23-E/31-E/CPU33-E)
1: Peripheral port
The order in which data is written to memory depends on the value of digit 0 of C.
Eight bytes of data 12345678... will be written in the following manner:
D
D+1
D+2
D+3
Digit 0 = 0
3
5
7
MSB LSB
1 2
4
6
8
D
D+1
D+2
D+3
Digit 0 = 1
4
6
8
MSB LSB
2 1
3
5
7
Flags ER: The CPU is not equipped with an RS-232C port.
Another device is not connected to the specified port.
There is an error in the communications settings (PC Setup) or the operand settings.
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
The destination words (D to D+(N ÷ 2)–1) exceed the data area.
Peripheral Port
26414: SR 26414 will be turned ON when data has been received normally at the peripheral port and will be reset when the data is read using
RXD(––) is executed.
266: SR 266 contains the number of bytes received at the peripheral port and is reset to 0000 when RXD(––) is executed.
RS-232C Port
26406: SR 26406 will be turned ON when data has been received normally at the peripheral port and will be reset when the data is read using
RXD(––) is executed.
265: SR 265 contains the number of bytes received at the RS-232C port and is reset to 0000 when RXD(––) is executed.
Note Communications flags and counters can be cleared either by specifying 0000 for
N or using the Port Reset Bit (SR 25208 for peripheral port and SR 25209 for
RS-232C port).
298
Serial Communications Instructions
5-27-2 TRANSMIT – TXD(––)
Limitations
Description
Host Link Mode
TXD(––)
S
C
N
Ladder Symbols
@TXD(––)
S
C
N
Section 5-27
Operand Data Areas
S: First source word
IR, SR, AR, DM, HR, TC, LR
C: Control word
IR, SR, AR, DM, HR, TC, LR, #
N: Number of bytes
IR, SR, AR, DM, HR, TC, LR, #
S and S+(N ÷ 2)–1 must be in the same data area.
N must be BCD from #0000 to #0256. (#0000 to #0061 in host link mode)
When the execution condition is OFF, TXD(––) is not executed. When the execution condition is ON, TXD(––) reads N bytes of data from words S to
S+(N ÷ 2)–1, converts it to ASCII, and outputs the data from the specified port.
TXD(––) operates differently in host link mode and RS-232C mode, so these modes are described separately.
Note The following flags will be ON to indicate that communications are possible through the various ports. Be sure the corresponding flag is ON before executing
TXD(––).
SR 26405:
SR 26413:
SR 26705:
SR 26713:
RS-232C port
Peripheral port
Host Link Unit #0
Host Link Unit #1
N must be BCD from #0000 to #0061 (i.e., up to 122 bytes of ASCII). The value of the control word determines the port from which data will be output, as shown below.
Digit number: 3 2 1 0
Byte order 0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 00.)
Port 0: Specifies RS-232C port
(C200HS-CPU21-E/23-E/31-E/CPU33-E).
1: Specifies peripheral port.
2: Specifies Host Link Unit #0
3: Specifies Host Link Unit #1
The specified number of bytes will be read from S through S+(N/2)–1, converted to ASCII, and transmitted through the specified port. The bytes of source data shown below will be transmitted in this order: 12345678...
S
S+1
S+2
S+3
3
5
7
MSB LSB
1 2
4
6
8
299
Serial Communications Instructions Section 5-27
The following diagram shows the format for host link command (TXD) sent from the C200HS. The C200HS automatically attaches the prefixes and suffixes, such as the node number, header, and FCS.
@ X X X X X X .........
X X X ∗
CR
RS-232C Mode
Control Word
Node number
Header code (EX)
Data (122 ASCII characters max.) FCS Terminator
N must be BCD from #0000 to #0256. The value of the control word determines the port from which data will be output and the order in which data will be written to memory.
The value of the control word determines the port from which data will be read and the order in which data will be written to memory.
Digit number: 3 2 1 0
Byte order 0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 00.)
Port 0: Specifies RS-232C port
(C200HS-CPU21-E/23-E/31-E/CPU33-E).
1: Specifies peripheral port.
The specified number of bytes will be read from S through S+(NP2)–1 and transmitted through the specified port.
S
S+1
S+2
S+3
5
7
MSB LSB
1
3
2
4
6
8
Flags
When digit 0 of C is 0, the bytes of source data shown above will be transmitted in this order: 12345678...
When digit 0 of C is 1, the bytes of source data shown above will be transmitted in this order: 21436587...
Note When start and end codes are specified the total data length should be 256 bytes max., including the start and end codes.
ER: Another device is not connected to the peripheral port.
There is an error in the communications settings (PC Setup) or the operand settings.
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
The source words (S to S+(N ÷ 2)–1) exceed the data area.
26405: RS-232C Port Communications Enabled Flag
26413: Peripheral Port Communications Enabled Flag
26705: Host Link Unit #0 Communications Enabled Flag
26713: Host Link Unit #1 Communications Enabled Flag
300
Advanced I/O Instructions
5-28 Advanced I/O Instructions
Advanced I/O instructions enable control, with a single instruction, of previously complex operations involving external I/O devices (digital switches, 7-segment displays, etc.).
There are five advanced I/O instructions, as shown in the following table. All of these are expansion instructions and must be assigned to function codes before they can be used.
Name Mnemonic
7-SEGMENT DISPLAY OUTPUT 7SEG(––)
DIGITAL SWITCH INPUT
HEXADECIMAL KEY INPUT
TEN-KEY INPUT
MATRIX INPUT
DSW(––)
HKY(––)
TKY(––)
MTR(––)
Function
BCD output to 7-segment display
Data input from a digital switch
Hexadecimal input from 16-key keypad
BCD input from 10-key keypad
Data input from an 8 x 8 matrix
Although TKY(––) is used only to simplify programming, the other advanced I/O instructions can be used to shorten cycle time, reduce the need for Special I/O
Units, and reduce system cost. With the exception of TKY(––), however, the advanced I/O instructions can only be used once each in the program and cannot be used for I/O Units mounted to Slave Racks, where Special I/O Units must be used.
5-28-1 7-SEGMENT DISPLAY OUTPUT – 7SEG(––)
Ladder Symbols
7SEG(––)
S
Operand Data Areas
S: First source word
IR, SR, AR, DM, HR, TC, LR
O: Output word
O
C
IR, SR, AR, HR, LR
C: Control data
000 to 007
Limitations
Overview
Section 5-28
S and S+1 must be in the same data area.
Do not set C to values other than 000 to 007.
When the execution condition is OFF, 7SEG(––) is not executed. When the execution condition is ON, 7SEG(––) reads the source data (either 4 or 8-digit), converts it to 7-segment display data, and outputs that data to the 7-segment display connected to the output indicated by O.
The value of C indicates the number of digits of source data and the logic for the
Input and Output Units, as shown in the following table.
Source data Display’s data input logic Display’s latch input logic
Same as Output Unit
Different from Output Unit
Same as Output Unit
Different from Output Unit
Same as Output Unit
Different from Output Unit
Same as Output Unit
Different from Output Unit
C
0000
0001
0002
0003
0004
0005
0006
0007
301
Advanced I/O Instructions Section 5-28
Precautions
Hardware
D
0
D
1
D
2
D
3
LE3
If there are 8 digits of source data, they are placed in S and S+1, with the most significant digits placed in S+1. If there are 4 digits of source data, they are placed in S.
7SEG(––) displays the 4 or 8-digit data in 12 cycles, and then starts over and continues displaying the data.
The 7-segment display must provide four data lines and one latch signal line for each display digit.
Note 1. Consider the cycle time and the characteristics of the 7-segment display when designing the system.
2. Output bits not used here can be used as ordinary output bits.
I/O refreshing must be performed for all I/O points used by 7SEG(––) each time it is executed to ensure effective operation. The I/O REFRESH instruction must thus be used with 7SEG(––) whenever 7SEG(––) is used in a subroutine to ensure that the I/O points are refreshed each execution. Refer to page 315 for an example of this type of programming.
7SEG(––) will be executed from the first cycle whenever program execution is started, including restarts made after power interruptions.
Do not use 7SEG(––) more than once in the program.
7SEG(––) cannot be used for I/O Units mounted to Slave Racks.
This instruction outputs word data to a 7-segment display. It utilizes either 8 output bits for 4 digits or 12 output bits for 8 digits. The 7-segment display is connected to an Output Unit as shown in the diagram below. For 4-digit display, the data outputs (D0 to D3) are connected to output points 0 through 3 (allocated word O), and latch outputs (CS0 to CS3) are connected to output points 4 through 7. Output point 12 (for 8-digit display) or output point 8 (for 4-digit display) will be turned ON when one round of data is displayed, but there is no need to connect them unless required by the application.
LE2 LE1
V
DD
(+)
V
SS
(0)
LE0
V
DD
(+)
V
SS
(0)
LE3 LE2 LE1
D
0
D
1
D
2
D
3
LE0
OD212
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
DC
The outputs must be connected from an Output Unit with 8 or more output points for four digits or 16 or more output points for eight digits. Basic Output, Special
I/O, or High-density Output Units can be used.
Note 1. Output Unit outputs normally employ negative logic. (Only the PNP output type employs positive logic.)
302
Advanced I/O Instructions
Using the Instruction
Section 5-28
2. The 7-segment display may require either positive or negative logic, depending on the model.
3. The 7-segment display must have 4 data signal lines and 1 latch signal line for each digit.
If the first word holding the data to be displayed is specified at S, and the output word is specified at O, and the SV taken from the table below is specified at C, then operation will proceed as shown below when the program is executed. If only four digits are displayed, then only word S will be used.
Data Storage Format
Leftmost 4 digits
S+1
Rightmost 4 digits
S
Timing
Function
Data output
Latch output 0
Latch output 1
Latch output 2
Latch output 3
The timing of data output is shown in the following table. “O” is the first word holding display data and “C” is the output word.
Bit(s) in O
(4 digits,
1 block)
(4 digits,
2 blocks)
00 to 03
04
05
06
07
00 to 03
04 to 07
08
09
10
11
10 0 10 1 10 2 10 3 Note 0 to 3: Data output for word S
4 to 7: Data output for word S+1
One Round Flag
Application Example
Flags
08 12
0 1 2 3 4 5 6 7 8 9 10 11 12
12 cycles required to complete one round
This example shows a program for displaying 8-digit BCD numbers at a 7-segment LED display. Assume that the 7-segment display is connected to output word IR 100. Also assume that the Output Unit is using negative logic, and that the 7-segment display logic is also negative for data signals and latch signals.
25313 (Always ON)
7SEG(––)
DM0120
100
004
The 8-digit BCD data in DM 0120 (rightmost 4 digits) and DM 0121 (leftmost 4 digits) are always displayed by means of 7SEG(––). When the contents of
DM 0120 and DM 0121 change, the display will also change.
ER: S and S+1 are not in the same data area. (When set to display 8-digit data.)
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
There is an error in operand settings.
25409: SR 25409 will be ON while 7SEG(––) is being executed.
303
Advanced I/O Instructions Section 5-28
5-28-2 DIGITAL SWITCH INPUT – DSW(––)
Ladder Symbols
Overview
Precautions
DSW(––)
IW
OW
R
Operand Data Areas
IW: Input word
IR, SR, AR, HR, LR
OW: Output word
IR, SR, AR, HR, LR
R: First result word
IR, SR, AR, DM, HR, LR
DSW(––) is used to read the value set on a digital switch connected to I/O Units.
When the execution condition is OFF, DSW(––) is not executed. When the execution condition is ON, DSW(––) reads the 8-digit value set on the digital switch from IW and places the result in R.
The 8-digit value it is placed in R and R+1, with the most significant digits placed in R+1.
DSW(––) reads the 8-digit value in 20 executions, and then starts over and continues reading the data.
The digital switch must provide four data lines and one latch signal line and read signal line for each digit being input.
I/O refreshing must be performed for all I/O points used by DSW(––) each time it is executed to ensure effective operation. The I/O REFRESH instruction must thus be used with DSW(––) whenever DSW(––) is used in a subroutine to ensure that the I/O points are refreshed each execution. Refer to page 315 for an example of this type of programming.
DSW(––) will be executed from the first cycle whenever program execution is started, including restarts made after power interruptions.
Do not use DSW(––) more than once in the program.
DSW(––) cannot be used for I/O Units mounted to Slave Racks.
Note Input and output bits not used here can be used as ordinary input and output bits.
304
Advanced I/O Instructions Section 5-28
Hardware With this instruction, 8-digit BCD set values are read from a digital switch.
DSW(––) utilizes 5 output bits and 8 input bits. Connect the digital switch and the
Input and Output Units as shown in the diagram below. Output point 5 will be turned ON when one round of data is read, but there is no need to connect output point 5 unless required for the application.
ID212
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
COM
Input Unit
D
0
D
1
D
2
D
3
D
0
D
1
D
2
D
3
CS
CS
0
CS
1
CS
2
RD
3
Interface D
0
D
1
D
2
D
3
D
0
D
1
D
2
D
3
CS
CS
0
CS
1
CS
2
RD
3
A7E data line rightmost digits
A7E data line leftmost digits
Leftmost digits
To A7E chip selection
To A7E RD terminal
A7E
Rightmost digits
OD212
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
COM
Output Unit
Note An interface to convert signals from 5 V to 24 V is required to connect an A7E digital switch.
305
Advanced I/O Instructions Section 5-28
The following example illustrates connections for an A7B Thumbwheel Switch.
ID212
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
COM
Input Unit
Switch no. 8 7 6 5 4 3 2
8 4 2 1
A7B
Thumbwheel
Switch
1 C
Output Unit
OD212
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
DC
Note The data read signal is not required in the example.
The inputs must be connected to a DC Input Unit with 8 or more input points and the outputs must be connected from a Transistor Output Unit with 8 or more output points.
306
Advanced I/O Instructions
Using the Instruction
Section 5-28
If the input word for connecting the digital switch is specified at for word A, and the output word is specified for word B, then operation will proceed as shown below when the program is executed.
IW
Four digits: 00 to 03
Eight digits: 00 to 03, 04 to 07
Wd 0
00
01
02
03
04
05
10 0 10 1 10 2 10 3 Input data
Leftmost
4 digits
D+1
Rightmost
4 digits
D
When only 4 digits are read, only word D is used.
CS signal
RD (read) signal
1 Round Flag
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 cycles to complete one round of execution
Application Example This example shows a program for reading 8 digits in BCD from the digital switch. Assume that the digital switch is connected to IR 000 (input) and IR 100
(output).
00015
05000
10005
05000
Flags
05000
10005
DSW
000
100
HR51
@MOV(21)
HR51
DM0000
When IR 00015 turns ON, the IR 05000 will hold itself ON until the One Round
Flag (IR 10005) turns ON upon completion of one round of reading by DSW(––).
The data set from the digital switch by DSW(––) is stored in HR 51.
When the One Round Flag (10005) turns ON after reading has been completed, the number stored in HR 51 is transferred to DM 0000.
ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
R and R+1 are not in the same data area.
25410: ON while DSW(––) is being executed.
307
Advanced I/O Instructions
5-28-3 HEXADECIMAL KEY INPUT – HKY(––)
Ladder Symbols
HKY(––)
IW
OW
D
Section 5-28
Operand Data Areas
IW: Input word
IR, SR, AR, HR, LR
OW: Control signal output word
IR, SR, AR, HR, LR
D: First register word
IR, SR, AR, DM, HR, LR
Limitations
Overview
Precautions
D and D+2 must be in the same data area.
When the execution condition is OFF, HKY(––) is not executed. When the execution condition is ON, HKY(––) inputs data from a hexadecimal keypad connected to the input indicated by IW. The data is input in two ways:
1, 2, 3...
1.
An 8-digit shift register is created in D and D+1. When a key is pressed on the hexadecimal keypad, the corresponding hexadecimal digit is shifted into the least significant digit of D. The other digits of D, D+1 are shifted left and the most significant digit of D+1 is lost.
2.
The bits of D+2 and bit 4 of OW indicate key input. When one of the keys on the keypad (0 to F) is being pressed, the corresponding bit in D+2 (00 to 15) and bit 4 of OW are turned ON.
Note 1. When one of the keypad keys is being pressed, input from the other keys is disabled.
2. Input and output bits not used here can be used as ordinary input and output bits.
With this instruction, one key input is read in 4 to 13 cycles. More than one cycle is required because the ON keys can only be determined as the outputs are turned ON to test them.
The hexadecimal key input device must be connectable in a 4 x 4 matrix.
I/O refreshing must be performed for all I/O points used by HKY(––) each time it is executed to ensure effective operation. The I/O REFRESH instruction must thus be used with HKY(––) whenever HKY(––) is used in a subroutine to ensure that the I/O points are refreshed each execution. Refer to page 315 for an example of this type of programming.
HKY(––) will be executed from the first cycle whenever program execution is started, including restarts made after power interruptions.
Do not use HKY(––) more than once in the program.
HKY(––) cannot be used for I/O Units mounted to Slave Racks.
308
Advanced I/O Instructions
Hardware
Section 5-28
This instruction inputs 8 digits in hexadecimal from a hexadecimal keyboard. It utilizes 5 output bits and 4 input bits. Prepare the hexadecimal keyboard, and connect the 0 to F numeric key switches, as shown below, to input points 0 through 3 and output points 0 through 3. Output point 4 will be turned ON while any key is being pressed, but there is no need to connect it unless required by the application.
1
ID212
0
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
COM
4
0
C
8
5
1
D
9
6
2
E
A
F
B
7
3
1
OD212
0
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
COM
Output Unit
Input Unit
The inputs connected to the input terminals must be on a DC Input Unit with 8 or more input points and the outputs connected to the output terminals must be from a Transistor Output Unit with 8 points or more.
309
Advanced I/O Instructions
Using the Instruction
Section 5-28
If the input word for connecting the hexadecimal keyboard is specified at word A, and the output word is specified at word B, then operation will proceed as shown below when the program is executed.
IW
16-key
0 to
9 to
F
00
01
02
03
D+2
00 to
09 to
15
OW
04
0 1 2 3 4 5 6 7 8 9 10 1112
0000
D+1
Once per 12 cycles
0000
D
0000
D+1
000F
D
0000
D+1
00F9
D
16-key selection control signals
Status of 16 keys
Turn ON flags corresponding to input keys (The flags remain ON until the next input.)
ON for a 12-cycle period if a key is pressed.
Flags
Example
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
D and D+2 are not in the same data area.
SR 25408: ON while HKY(––) is being executed.
This example shows a program for inputting numbers from a hexadecimal keyboard. Assume that the hexadecimal keyboard is connected to IR 000 (input) and IR 100 (output).
25313 (Always ON)
00015
HKY(––)
000
100
DM1000
@XFER(70)
#0002
DM1000
DM0000
The hexadecimal key information that is input to IR 000 by HKY(––) is converted to hexadecimal and stored in words DM1000 and DM1001.
IR 00015 is used as an “ENTER key”, and when IR 00015 turns ON, the numbers stored in DM 1000 and DM 1001 are transferred to DM 0000 and DM 0001.
310
Advanced I/O Instructions
5-28-4 TEN KEY INPUT – TKY(––)
Ladder Symbols
Limitations
Overview
Hardware
TKY(––)
IW
D
1
D
2
Section 5-28
Operand Data Areas
IW: Input word
IR, SR, AR, HR, LR
D
1
: First register word
IR, SR, AR, DM, HR, LR
D
2
: Key input word
IR, SR, AR, DM, HR, LR
D
1
and D
1
+1 must be in the same data area.
When the execution condition is OFF, TKY(––) is not executed. When the execution condition is ON, TKY(––) inputs data from a ten-key keypad connected to the input indicated by IW. The data is input in two ways:
TKY(––) can be used in several locations in the program by changing the input word, IW.
1, 2, 3...
1.
An 8-digit shift register is created in D
1
and D
1
+1. When a key is pressed on the ten-key keypad, the corresponding BCD digit is shifted into the least significant digit of D
1
. The other digits of D
1
, D
1
+1 are shifted left and the most significant digit of D
1
+1 is lost.
2.
The first ten bits of D
2
indicate key input. When one of the keys on the keypad (0 to 9) is being pressed, the corresponding bit of D
2
(00 to 09) is turned
ON.
Note 1. While one key is being pressed, input from other keys will not be accepted.
2. If more than eight digits are input, digits will be deleted beginning with the leftmost digit.
3. Input bits not used here can be used as ordinary input bits.
This instruction inputs 8 digits in BCD from a 10-key keypad and uses 10 input points. Prepare a 10-key keypad, and connect it so that the switches for numeric keys 0 through 9 are input to points 0 through 9 as shown in the following diagram. The inputs on a DC Input Unit with 16 or more input points can be used.
ID212
0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
COM
COM
0 V
9
10-key
DC Input Unit
311
Advanced I/O Instructions
Using the Instruction
Section 5-28
If the input word for connecting the 10-key keypad is specified for IW, then operation will proceed as shown below when the program is executed.
D
2
IW
00
01
02 to
09
00
01
02 to
09
10
(1) (2) (3) (4)
Input from 10-key
Turn ON flags corresponding to 10-key inputs (The flags remain ON until the next input.)
ON if a key is pressed.
Before execution
D
1
+1 D
1
0 0 0 0 0 0 0 0
(1)
(2)
(3)
(4)
0 0 0 0 0 0 0 1
“1” key input
0 0 0 0 0 0 1 0
“0” key input
0 0 0 0 0 1 0 2
“2” key input
0 0 0 0 1 0 2 9
“9” key input
Flags
Example
ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
D
1
and D
1
+1 are not in the same data area.
In this example, a program for inputting numbers from the 10-key is shown. Assume that the 10-key is connected to IR 000.
25313 (Always ON)
00015
TKY(––)
000
DM1000
DM1002
@XFER(70)
#0002
DM1000
DM 0000
The 10-key information input to IR 000 using TKY(––) is converted to BCD and stored in DM 1000 and DM 1001. Key information is stored in DM 1002.
IR 00015 is used as an “ENTER key”, and when IR 00015 turns ON, the data stored in DM 1000 and DM 1001 will be transferred to DM 0000 and DM 0001.
312
Advanced I/O Instructions
5-28-5 MATRIX INPUT – MTR(––)
Ladder Symbols
MTR(––)
IW
OW
D
Section 5-28
Operand Data Areas
IW: Input word
IR, SR, AR, HR, LR
OW: Output word
IR, SR, AR, HR, LR
D: First destination word
IR, SR, AR, DM, HR, LR
Limitations
Overview
OW bits 00 to 07
(for Output Unit outputs 00 to 07)
Bit 08 is turned ON to indicate that the entire matrix has been read.
D and D+3 must be in the same data area.
When the execution condition is OFF, MTR(––) is not executed. When the execution condition is ON, MTR(––) inputs data from an 8 × 8 matrix and records that data in D to D+3. Data for all 64 points in the matrix will be recorded even when fewer than 64 keys are connected.
04
05
06
07
08
00
01
02
03
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23
24 25 26 27 28 29 30 31
32 33 34 35 36 37 38 39
40 41 42 43 44 45 46 47
48 49 50 51 52 53 54 55
56 57 58 59 60 61 62 63
00 01 02 03 04 05 06 07
IW bits 00 to 07
(for Input Unit inputs 00 to 07)
Key input data is written to D through D+3 (see table below).
A selection signal is output to OW bits 00 to 07 consecutively for 3 cycles. Only one output bit will be turned on at a time. Bit 08 of OW is turned ON for 3 cycles after 07 to indicate when each round of reading the matrix has been completed.
When one of the 64 keys is pressed, an input will be received at one of the input bits. The key that was pressed is identified by comparing the output bit to which the signal was output and input bit at which it was received.
When an key input is detected, the corresponding bit in D through D+3 is turned
ON. The following table shows the correspondence between keys and bits in D through D+3.
Word
D
D+1
D+2
D+3
Bits
00 to 15
00 to15
00 to 15
00 to 15
Corresponding Keys
0 to 15
16 to 31
32 to 47
48 to 63
313
Advanced I/O Instructions
Hardware
Section 5-28
This instruction inputs up to 64 signals from an 8 x 8 matrix using 8 input points and 8 output points. Any 8 x 8 matrix can be used. The inputs must be connected through a DC Input Unit with 8 or more points and the outputs must be connected through a Transistor Output Unit with 8 or more points. The basic wiring and timing diagrams for MTR(––) are shown below.
Wiring
8th row
Precautions
7th row
A8 A7 A6 A5 A4 A3 A2 A1 A0
B9 B8 B7 B6 B5 B4 B3 B2 B1 B0
1st row
Timing Diagram
04
05
06
07
00
01
02
03
00
32
64
00
32
64
06
Each round completed in 24 executions
A9 A8 A7 A6 A5 A4 A3 A2 A1 A0
ID 211 I/O Unit
Matrix select signal
Matrix status
Bits indicating input status
One-round Flag (bit
08 of output word)
The 64 keys can be divided into 8 rows (including a row for OW bit 08) which are scanned consecutively. Since each row is scanned for 3 cycles, a delay of up to
25 cycles can occur before a given row of keys is scanned for inputs.
I/O refreshing must be performed for all I/O points used by MTR(––) each time it is executed to ensure effective operation. The I/O REFRESH instruction must thus be used with MTR(––) whenever MTR(––) is used in a subroutine to ensure that the I/O points are refreshed each execution.
MTR(––) will be executed from the first cycle whenever program execution is started, including restarts made after power interruptions.
SR 25403, which is turned on while MTR(––) is being executed, is reset in an interlocked program section and MTR(––) is not executed in an interlocked program section.
Do not use MTR(––) more than once in the program.
MTR(––) cannot be used for I/O Units mounted to Slave Racks.
314
Advanced I/O Instructions
Example
Section 5-28
The following examples shows programming MTR(––) in a scheduled subroutine, where IORF(97) is programmed to ensure that the I/O words used by
MTR(––) are refreshed each time MTR(––) is executed.
INT(89)
001
004
# 0002
INT(89)
000
004
# 0002
SBN(92)
MTR(––)
99
S
D1
D2
IORF(97)
D1
D2
RET(93)
END(01)
Flags ER: Indirectly addressed DM word is non-existent. (Content of : DM word is not BCD, or the DM area boundary has been exceeded.)
25403: SR 25403 is ON while MTR(––) is being executed.
315
SECTION 6
Program Execution Timing
The timing of various operations must be considered both when writing and debugging a program. The time required to execute the program and perform other CPU operations is important, as is the timing of each signal coming into and leaving the
PC in order to achieve the desired control action at the right time. This section explains the cycle and shows how to calculate the cycle time and I/O response times.
6-1 Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Calculating Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-1 PC with I/O Units Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-2 PC with Link Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Instruction Execution Times
6-4 I/O Response Time
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-1 Basic Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-2 Remote I/O Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-3 Host Link Systems
6-4-4 PC Link Systems
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-5 One-to-one Link I/O Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-6 Interrupt Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
318
322
322
323
324
333
333
334
336
337
339
341
317
Cycle Time
6-1 Cycle Time
Section 6-1
To aid in PC operation, the average, maximum, and minimum cycle times can be displayed on the Programming Console or any other Programming Device and the maximum cycle time and current cycle time values are held in AR 26 and
AR 27. Understanding the operations that occur during the cycle and the elements that affect cycle time is, however, essential to effective programming and
PC operations.
The major factors in determining program timing are the cycle time and the I/O response time. One run through all required CPU operations is called a cycle; the time required for each cycle is called the cycle time.
The overall flow of the CPU operation is as shown in the following flowchart.
318
Cycle Time
Flowchart of CPU Operation
Power application
Clears IR area and resets all timers
Checks I/O Unit connections
Resets watchdog timer
Checks hardware and
Program Memory
NO
Check OK?
YES
Resets watchdog timer and program address counter Sets error flags and turns
ON or flashes indicator
ALARM/ERROR
ERROR
(Solid ON)
Executes user program
ALARM
(Flashing)
End of program?
NO
Note A minimum cycle time can be set either in DM 6619 of the PC Setup
YES
Minimum cycle time?
NO or by executing
SCAN(18).
YES
Resets watchdog timer and waits until the set cycle time has elapsed
Calculates cycle time
Resets watchdog timer
Refreshes input bits and output signals
Services RS-232C port
Services Host Link
Services Peripheral Devices
Services SYSMAC LINK and
SYSMAC NET Link Units
Section 6-1
Initialization on power-up
Overseeing processes
Program execution
Cycle time calculation
PC cycle time
I/O refreshing
RS-232C port servicing
Host Link Unit servicing
Peripheral device servicing
SYSMAC LINK and SYSMAC
NET Link Unit servicing
319
Cycle Time Section 6-1
The first three operations immediately after power application are performed only once each time the PC is turned on. The rest of the operations are performed in cyclic fashion. The cycle time is the time that is required for the CPU to complete one of these cycles. This cycle includes basically eight types of operation.
Operation
1. Overseeing
2. Program execution
3. Cycle time calculation
4. I/O refreshing
5. Host Link Unit servicing
6. RS-232C port servicing
(except CPU01-E/03-E)
7. Peripheral device servicing
8. SYSMAC NET/
SYSMAC LINK servicing
(CPU31-E/33-E only)
1, 2, 3...
1. Overseeing
2. Program execution
3. Cycle time calculation
4. I/O refreshing
5. Host Link Unit servicing
6. RS-232C port servicing
7. Peripheral Device servicing
8. SYSMAC NET/SYSMAC LINK servicing.
The cycle time is the total time required for the PC to perform all of the above operations. The time required for operation 3, cycle time calculation, is negligible and can be ignored in actual calculations
0.7 ms
Time required Function
Watchdog timer set. I/O Bus, Program
Memory checked. Clock refreshed.
Program executed.
Total execution time for all instructions varies with program size, the instructions used, and execution conditions. Refer to 6-3 Instruction
Execution Times for details.
Negligible, but a wait can be generated to bring the cycle time up to the minimum setting if one has been made.
Total of following times:
20
µ s per input byte (8 points). 20
µ s per output byte. (12-point Output Units calculated as 16 points.)
PC Link Unit I/O refresh time.
Special I/O Unit refresh time.
1.1 ms per Remote I/O Master Unit +
0.17 ms per I/O word used on Slave Racks.
Group-2 (High-density) I/O Unit refresh time.
Refer to the tables below for details on PC
Link, Special I/O Unit, and Group-2 Highdensity I/O Unit refresh times.
6 ms per Unit max.
Cycle time calculated. When the CYCLE
TIME instruction (SCAN(18)) is executed, waits until the set time has elapsed and then resets the watchdog timer.
Input bits set according to status of input signals. Output signals sent according to status of output bits in memory.
Inputs and Outputs in Remote I/O Systems refreshed.
Special I/O Units serviced.
Group-2 High-density I/O Units serviced.
0 ms when no device is connected.
T x 0.05, where T is the cycle time calculated in operation 3
0 ms when no device is connected.
0.26 ms minimum or T x 0.05, where T is the cycle time calculated in operation 3
0 ms when no Communications Unit is mounted.
0.8 ms + 10 ms max. per Unit.
Commands from computers connected through Rack-mounting Host Link Units processed.
Communications with devices connected to RS-232C port processed.
Commands from Programming Devices
(computers, Programming Consoles, etc.) processed.
Commands from computers and other devices connected to SYSMAC NET/SYS-
MAC LINK Units processed.
320
Cycle Time
PC Link Unit I/O Refresh
Special I/O Unit Refresh
Group-2 High-density I/O
Unit Refresh
Section 6-1
512
256
128
64
I/O pts to refresh
7.4
4.1
Time required
(ms)
2.7
1.7
Unit
C200H-ID501/215
C200H-OD501/215
C200H-MD501/215
C200H-CT001-V1/CT002
C200H-NC111/NC112
C200H-NC211
C200H-AD001
C200H-DA001
C200H-TS001/TS101
C200H-ASC02
C200H-IDS01-V1/IDS21
C200H-OV001
C200H-FZ001
C200H-TC001/002/003/
101/102/103
C200H-CP114
C200H-AD002
C200H-PID jj
Time required per Unit
0.6 ms
0.6 ms when set for 32 I/O pts.
1.6 ms when set for dynamic I/O
2.6 ms
2.5 ms
5.0 ms
1.3 ms
1.0 ms
1.2 ms
1.9 ms normally, 5.0 ms for @ format
2.0 ms normally, 5.5 ms for command transfer
4.1 ms
2.0 ms
3.0 ms
2.5 ms
1.4 ms
3.0 ms
Unit
C200H-ID216
C200H-OD218
C200H-ID217
C200H-OD219
0.18 ms
0.14 ms
0.31 ms
0.23 ms
Time required per Unit
NT Links If the PC is connected to a Programmable Terminal (PT) via a C200H Interface
Unit, the times shown in the following table will be required to refresh I/O for the
PT.
I/O refresh time Number of table entries for PT
Minimum setting:
Character string table: 0
Numeral table: 0
Maximum setting:
Character string table: 32
Numeral table: 128
2.5 ms
5.4 ms
Watchdog Timer and Long
Cycle Times
Within the PC, the watchdog timer measures the cycle time and compares it to a set value. If the cycle time exceeds the set value of the watchdog timer, a FALS
9F error is generated and the CPU stops. WDT(94) can be used to extend the set value for the watchdog timer.
321
Calculating Cycle Time Section 6-2
Even if the cycle time does not exceed the set value of the watchdog timer, a long cycle time can adversely affect the accuracy of system operations as shown in the following table.
Cycle time (ms)
10 or greater
20 or greater
100 or greater
Possible adverse affects
TIMH(15) inaccurate when TC 016 through TC 511 are used.
(Accuracy when using TC 000 through TC 0015 not affected.)
0.02-second clock pulse (SR 25401) not accurately readable.
0.1-second clock pulse (SR 25500) not accurately readable and
Cycle Time Error Flag (SR 25309) turns ON.
200 or greater 0.2-second clock pulse (SR 25501) not accurately readable.
6,500 or greater FALS code 9F generated regardless of watchdog timer setting and the system stops.
Online Editing When online editing is executed from a Programming Device, operation will be interrupted for a maximum of 260 ms and interrupts will be masked to rewrite the user program. No warnings will be given for long cycle times during this interval.
Check the effects on I/O response time before editing the program online.
!
Caution Editing the program online can cause delays in I/O responses with no warnings being given from the system for the long cycle time produced by editing online. Before editing online, make sure that delays in I/O responses will not create a dangerous situation in the controlled system.
6-2 Calculating Cycle Time
The PC configuration, the program, and program execution conditions must be taken into consideration when calculating the cycle time. This means taking into account such things as the number of I/O points, the programming instructions used, and whether or not peripheral devices are employed. This section shows some basic cycle time calculation examples. To simplify the examples, the instructions used in the programs have been assumed to be all either LD or OUT.
The average execution time for the instructions is thus 0.47
µ s. (Execution times are given in the table in 6-3 Instruction Execution Times.)
6-2-1 PC with I/O Units Only
Here, we’ll compute the cycle time for a simple PC. The CPU controls only I/O
Units, eight on the CPU Rack and five on a 5-slot Expansion I/O Rack. The PC configuration for this would be as shown below. It is assumed that the program contains 5,000 instructions requiring an average of 0.47 µ s each to execute.
8-point Input Units 8-point Output Units
CPU Rack
16-point Input Units 12-point Output Units
8-point Output Unit
Expansion I/O Rack
322
Calculating Cycle Time Section 6-2
Calculations The equation for the cycle time from above is as follows:
Cycle time = Overseeing time + Program execution time + I/O refresh time +
Peripheral device servicing time
Process Calculation With Peripheral
Device
0.7 ms
2.35 ms
Without
Peripheral Device
0.7 ms
2.35 ms
Overseeing Fixed
Program execution 0.47 µ s/instruction
× 5,000 instructions
I/O refresh See below.
Minimum time Peripheral device servicing
Cycle time Total of above
0.34 ms
0.26 ms
3.65 ms
0.34 ms
0.0 ms
3.39 ms
The I/O refresh time would be as follows for two16-point Input Units, four 8-point
Input Units, two 12-point Output Units (12-point Units are treated as 16-point
Units), and five 8-point Output Units controlled by the PC:
(16 pts x 2) + (8 pts x 4)
8 pts x 20 µ s +
(16 pts x 2) + (8 pts x 5) x 20 µ s = 0.34 ms
8 pts
6-2-2 PC with Link Units
Here, the cycle time is computed for a PC with a CPU21-E or CPU23-E CPU that has a Memory Unit with a clock function installed. The PC configuration for this could be as shown below.
The CPU controls three 8-point Input Units, three 8-point Output Units, a Host
Link Unit, and a Remote I/O Master Unit connected to a Remote I/O Slave Rack containing four 16-point Input Units and four 12-point Output Units.
It is assumed that the program contains 5,000 instructions requiring an average of 0.47
µ s each to execute, and that nothing is connected to the RS-232C port and no SYSMAC NET/SYSMAC LINK Unit is mounted.
Host Link Unit
Remote I/O
Master Unit
8-point
Input Units
8-point
Output Units
CPU Rack
Computer
Slave Rack
16-point
Input Units
12-point
Output Units
323
Instruction Execution Times Section 6-3
Calculations The equation for the cycle time is as follows:
Cycle time = Overseeing time + Program execution time
+ I/O refreshing time + Host Link Unit servicing time
+ Peripheral device servicing time
Process Calculation
Overseeing Fixed
Program execution 0.47
µ s/instruction
×
5,000 instructions
I/O refresh See below.
Host Link servicing Fixed
Peripheral device servicing
0.7 + 2.35 + 2.58 +
6 = 11.63
Cycle time
11.63 x 0.05 = 0.58
Total of above
With Peripheral
Device
0.7 ms
2.35 ms
2.58 ms
6.0 ms
0.58 ms
Without
Peripheral Device
0.7 ms
2.35 ms
2.58 ms
6.0 ms
0.0 ms
12.21 ms 11.63 ms
The I/O refreshing time would be as follows for three 8-point Input Units and three 8-point Output Units mounted in the CPU Rack, and eight Units mounted in a Slave Rack.
(8 pts x 3) + (8 pts x 3)
8 pts x 20 µ s + 1.1 ms + 8 Units x 0.17 ms = 2.58 ms
6-3 Instruction Execution Times
The following table lists the execution times for all instructions that are available for the C200HS. The maximum and minimum execution times and the conditions which cause them are given where relevant. When “word” is referred to in the Conditions column, it implies the content of any word except for indirectly addressed DM words. Indirectly addressed DM words, which create longer execution times when used, are indicated by “ : DM”.
Execution times for most instructions depend on whether they are executed with an ON or an OFF execution condition. Exceptions are the ladder diagram instructions OUT and OUT NOT, which require the same time regardless of the execution condition. The OFF execution time for an instruction can also vary depending on the circumstances, i.e., whether it is in an interlocked program section and the execution condition for IL is OFF, whether it is between JMP(04) 00 and JME(05) 00 and the execution condition for JMP(04) 00 is OFF, or whether it is reset by an OFF execution condition. “R”, “IL”, and “JMP” are used to indicate these three times.
All execution times are given in microseconds unless otherwise noted.
LD
Instruction
LD NOT
AND
AND NOT
OR
OR NOT
Conditions
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
ON execution time (
µ s) OFF execution time (
µ s)
0.375
0.375
0.75
0.375
0.375
0.75
0.375
0.75
0.375
0.75
0.375
0.75
0.375
0.75
0.375
0.375
0.375
0.375
0.375
0.375
0.375
0.375
0.375
0.375
324
Instruction Execution Times
Instruction
AND LD
OR LD
OUT
OUT NOT
TIM
Conditions
---
---
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
Constant for SV
: DM for SV
For designated words 256 to 511
CNT Constant for SV
: DM for SV
For designated words 256 to 511
SET
RSET
NOP(00)
END(01)
IL(02)
ILC(03)
JMP(04)
---
---
JME(05) ---
FAL(06) 01 to 99 ---
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
---
---
---
FAL(06) 00
FALS(07)
STEP(08)
---
---
---
SNXT(09) ---
Section 6-3
ON execution time (
µ s)
0.375
0.375
0.563
0.938
0.563
0.938
1.125
1.125
0.563
0.938
0.563
0.938
0.375
34.20
11.44
12.60
12.32
12.28
93.76
77.56
4.28 ms
50.60 (with operand)
24.56 (without operand)
13.96
OFF execution time (
µ s)
0.375
0.375
0.563
0.563
0.563
0.563
R: 1.125
IL: 1.125
JMP: 1.125
R: 39.0875
IL: 1.125
JMP: 1.125
R: 22.2875
IL: 1.125
JMP: 1.125
R: 1.125
IL: 1.125
JMP: 1.125
R: 39.0875
IL: 1.125
JMP: 1.125
R: 22.0875
IL: 1.125
JMP: 1.125
0.563
0.563
0.563
0.563
---
---
14.00
12.64
14.56
12.28
0.375
0.375
0.375
2.25
2.25
325
Instruction Execution Times
Instruction
SFT(10)
KEEP(11)
CNTR(12)
DIFU(13)
DIFD(14)
TIMH(15)
WSFT(16)
CMP(20)
MOV(21)
MVN(22)
Conditions
With 1-word shift register
With 100-word shift register
With 250-word shift register
For IR and SR 23600 to SR 25515
For SR 25600 to SR 51115
Constant for SV
: DM for SV
---
---
Interrupt Constant for SV
Normal cycle
Interrupt : DM for SV
Normal cycle
When shifting 1 word
When shifting 6,144 words using
:
DM
When comparing a constant to a word
When comparing two words
When comparing two : DM
When transferring a constant to a word
When comparing two words
When transferring : DM to : DM
When transferring a constant to a word
When comparing two words
When transferring : DM to : DM
Section 6-3
36.90
11.27 ms
24.20
26.40
61.80
19.00
21.20
57.20
20.20
22.40
57.20
ON execution time (
µ s)
47.06
340.00
800.00
OFF execution time (
µ s)
R: 35.80
IL: 15.70
JMP: 15.60
R: 256.80
IL: 15.72
JMP: 15.68
R: 590.80
IL: 15.60
JMP: 15.66
0.563
0.563
0.938
38.20
53.20
20.60
20.40
32.20
29.40
29.80
27.40
R: 27.90
IL: 20.30
JMP: 20.30
R: 28.00
IL: 20.30
JMP: 20.30
Normal: 20.60
IL: 20.40
JMP: 18.00
Normal: 20.40
IL: 20.20
JMP: 17.80
R: 40.40
IL: 39.20
JMP: 24.90
R: 36.30
IL: 35.20
JMP: 20.80
R: 59.80
IL: 58.60
JMP: 24.90
R: 56.00
IL: 54.60
JMP: 20.80
3
1.125
1.125
1.125
326
Instruction
BIN(23)
BCD(24)
ASL(25)
ASR(26)
ROL(27)
ROR(28)
COM(29)
ADD(30)
Instruction Execution Times
SUB(31)
MUL(32)
DIV(33)
ANDW(34)
ORW(35)
XORW(36)
XNRW(37)
INC(38)
DEC(39)
STC(40)
CLC(41)
TRSM(45)
MSG(46)
Conditions
When converting a word to a word
When converting
:
DM to
:
DM
When converting a word to a word
When converting : DM to : DM
When shifting a word
When shifting : DM
When shifting a word
When shifting : DM
When rotating a word
When rotating : DM
When rotating a word
When rotating : DM
When inverting a word
When inverting : DM
Constant + word
→
word
Word + word → word
: DM + : DM → : DM
Constant – word
→
word
Word – word → word
: DM – : DM → : DM
Constant x word → word
Word x word → word
: DM x : DM → : DM
Word
÷
constant
→
word
Word
÷
word → word
: DM
÷ : DM → : DM
Constant AND word
→
word
Word AND word → word
: DM AND : DM → : DM
Constant OR word
→
word
Word OR word → word
: DM OR : DM → : DM
Constant XOR word → word
Word XOR word → word
: DM XOR : DM → : DM
Constant XNOR word → word
Word XNOR word
→
word
: DM XNOR : DM → : DM
When incrementing a word
When incrementing
:
DM
When decrementing a word
When decrementing : DM
---
---
---
Designated as DM
Designated as : DM
Section 6-3
59.10
110.70
36.70
88.30
34.30
36.90
88.50
23.70
34.10
37.10
88.70
34.10
36.70
88.30
34.10
41.10
24.30
41.70
12.20
12.30
27.70
23.20
40.80
ON execution time (
µ s)
40.40
40.10
42.50
94.10
40.10
42.50
94.10
56.90
59.30
110.90
56.90
21.80
39.00
21.80
39.00
21.90
39.30
74.80
38.40
72.80
21.20
38.20
21.20
38.20
OFF execution time (
µ s)
1.125
1.125
0.75
0.75
0.75
0.75
0.75
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.75
0.75
0.375
0.375
27.70
0.75
327
Instruction Execution Times
Instruction
ADB(50)
SBB(51)
MLB(52)
DVB(53)
ADDL(54)
SUBL(55)
MULL(56)
DIVL(57)
BINL(58)
BCDL(59)
XFER(70)
BSET(71)
ROOT(72)
XCHG(73)
SLD(74)
SRD(75)
MLPX(76)
Section 6-3
Conditions
Constant + word → word
Word + word → word
: DM + : DM → : DM
Constant – word → word
Word – word → word
: DM – : DM → : DM
Constant x word → word
Word x word → word
: DM x : DM → : DM
Word
÷
constant → word
Word
÷
word → word
: DM
÷ : DM → : DM
Word + word → word
: DM + : DM → : DM
Word – word → word
: DM – : DM → : DM
Word x word → word
: DM x : DM → : DM
Word
÷
word → word
: DM
÷ : DM → : DM
When converting words to words
When converting : DM to : DM
When converting words to words
When converting : DM to : DM
When transferring 1 word
When transferring 1,024 words using
: DM
When transferring 6,143 words using
: DM
When setting a constant to 1 word
When setting
:
DM ms to 1,024 words using : DM
When setting : DM ms to 6,144 words using : DM
When taking root of word and placing in a word
When taking root of 99,999,999 in : DM and placing in : DM
Between words
Between
:
DM
When shifting 1 word
When shifting 1,024 DM words using
:
DM
When shifting 6,144 DM words using
:
DM
When shifting 1 word
When shifting 1,024 DM words using
:
DM
When shifting 6,144 DM words using
:
DM
When decoding word to word
When decoding : DM to : DM
13.99 ms
37.70
26.20
95.80
68.60
137.80
33.50
68.50
34.00
4.35 ms
25.93 ms
34.00
4.35 ms
26.01 ms
86.80
178.20
39.30
90.80
45.50
99.00
45.50
99.00
155.90
209.50
166.10
219.70
58.70
93.50
47.30
82.20
54.80
2.40 ms
ON execution time (
µ s)
43.20
45.80
97.40
43.20
45.80
97.40
36.00
38.50
91.10
36.70
OFF execution time (
µ s)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.125
1.125
1.5
1.5
1.125
1.125
1.125
1.125
1.5
328
Instruction Execution Times Section 6-3
Instruction
DMPX(77)
SDEC(78)
FDIV(79)
DIST(80)
COLL(81)
MOVB (82)
Conditions
When encoding a word to a word
When encoding
:
DM to
:
DM
When decoding a word to a word
When decoding 2 digits : DM to : DM
When decoding 4 digits
:
DM to
:
DM
Word
÷
word → word (equals 0)
Word
÷
word → word (doesn’t equal 0)
: DM
÷ : DM → : DM
Constant → (word + (word))
: DM → ( : DM + ( : DM))
(Word + (word)) → word
( : DM + ( : DM)) → : DM
When transferring a constant to a word
ON execution time (
µ s)
48.90
185.90
53.20
113.60
126.00
118.20
357.20
409.20
49.00
106.70
52.90
113.50
38.60
MOVD(83)
SFTR(84)
TCMP(85)
ASC(86)
SEND(90)
When transferring word to a word
When transferring : DM to : DM
When transferring a constant to a word
45.30
97.60
34.00
When transferring word to a word 41.00
When transferring : DM to : DM
When shifting 1 word
97.60
48.40
When shifting 1,024 : DM using : DM
When shifting 6,144 : DM using : DM
1.92 ms
11.8 ms
Comparing to words in a designated table 69.10
Comparing to words in a designated table 71.50
Comparing
:
DM
→ :
DM-designated table 123.50
56.90
Between words
Between : DM
1-word transmit
133.50
563
1000-word transmit
---
752
37.6
SBS(91)
SBN(92)
RET(93)
WDT(94)
IORF(97)
RECV(98)
---
---
---
1-word refresh
30-word refresh
1-word refresh
1000-word refresh
MCRO(99) Designating a word parameter
Designating a : DM parameter
ASFT(––) When resetting 1 word
Default code: (17) When shifting 1 word using
:
DM
When shifting 10 word using : DM
SCAN(––) Constant for SV
Default code: (18)
:
DM for SV
MCMP(––) Comparing 2 words, result word
Default code: (19) Comparing 2 : DM, result : DM
LMSG(––) Word for SV
Default code: (47) : DM for SV
---
45.6
17.60
130.70
2.27 ms
559
764
91.00
125.80
43.60
50.30
68.80
31.80
51.20
104.30
159.30
104.30
159.30
OFF execution time (
µ s)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
3.75
2.25
---
13.7
0.75
1.125
3.75
1.5
1.5
1.5
1.5
1.5
329
Instruction Execution Times Section 6-3
Instruction
TERM(––)
Default code: (48)
---
Conditions
CMPL(––) When comparing words to words
Default code: (60) When comparing : DM to : DM
MPRF(––) 1 Unit
Default code: (61) 10 Units
XFRB(––) Sending 1 bit from word to word
Default code: (62) Sending FF bits from : DM to : DM
LINE(––)
Default code: (63)
When transferring from words to a constant
COLM(––)
Default code: (64)
When transferring from words to a word
When transferring : DM to : DM
When transferring from a constant to words
When transferring from a word to words
When transferring : DM to : DM
SEC(––) DM to DM
Default code: (65) : DM to : DM
HMS(––) DM to DM
Default code: (66) : DM to : DM
BCNT(––) Constant for SV
Default code: (67) : DM for SV
BCMP(––)
Default code: (68)
Comparing constant to word-designated table
To a word after comparing with a word
Comparing
:
DM
→ :
DM-designated table
APR(––) SIN designation
Default code: (69) : DM for SV
TTIM(––)
Default code: (87)
Setting to a constant
ON execution time (
µ s)
16.40
51.40
85.90
33.70
74.20
45.50
241.90
102.90
106.40
293.80
115.20
118.70
303.10
78.50
112.90
80.00
114.50
69.56
37.52 ms
105.00
107.40
166.50
43.90
740.70
43.50
OFF execution time (
µ s)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Setting to : DM 81.70
Constant input OFF: 36.9
R: 38.4
IL: 36.8
JPM: 36.8
Constant input OFF: 75.1
R: 76.6
IL: 75.0
JPM: 75.1
1.5
ZCP(––)
Default code: (88)
Comparing a constant to a word
Comparing a word to a word
Comparing : DM to a : DM
INT(––) Word for SV
Default code: (89) : DM for SV
TKY(––) Input to DM
Input to : DM
RXD(––)
TXD(––)
7SEG(––)
When designating a word
When designating : DM
When designating a word
When designating : DM
Word-designated 4 digits
35.40
38.00
89.70
21.70 to 47.40
21.70 to 64.60
63.10
97.90
76.50
128.50
65.30
125.30
49.10 to 55.40
1.5
1.5
1.5
1.5
21.70
330
Instruction Execution Times
Instruction
FPD(––)
SRCH(––)
MAX(––)
MIN(––)
SUM(––)
FCS(––)
HEX(––)
AVG(––)
PID(––)
XDMR(––)
MTR(––)
ADBL(––)
SBBL(––)
MBS(––)
DBS(––)
MBSL(––)
DBSL(––)
CPS(––)
CPSL(––)
Conditions
: DM-designated 4 digits
Word-designated 8 digits
: DM-designated 8 digits
Word designation, code output
: DM designation, message output
Constant for SV
:
DM for SV
: DM for SV
DM search
: DM search
DM search
: DM search
DM add
: DM add
Add a word
→
word
Add 999 words → : DM
DM conversion
: DM conversion
Average of an operation
Average of 64 operations
When designating a word
When designating : DM
Constant for SV
Word for SV
: DM for SV
Input to DM
Input to : DM
DM + DM → DM
: DM + : DM → : DM
DM – DM → DM
:
DM –
:
DM
→ :
DM
Constant x word → word
DM x DM → DM
: DM x : DM → : DM
Constant ÷ word → word
DM ÷ DM → DM
: DM ÷ : DM → : DM
DM x DM → DM
:
DM x
:
DM
→ :
DM
DM ÷ DM → DM
: DM ÷ : DM → : DM
When comparing two constants
When comparing DM to DM
When comparing DM to : DM
When comparing two DM
When comparing two : DM
Section 6-3
ON execution time (
µ s)
66.60 to 72.80
52.80
104.30
51.20
53.70
106.20
81.90
133.50
90.70
143.70
34.20
29.70
64.80
50.90
86.10
66.70
169.90
61.40
223.70
83.00
138.00
74.20
2.32 ms
6.89 ms
54.60 to 63.60
72.00 to 81.20
72.20
123.30
71.70
123.30
50.20
56.70 to 64.80
74.20 to 82.30
121.00 to 147.50
170.50 to 228.80
78.50
2.11 ms
12.10 ms
57.20
2.05 ms
57.20
2.05 ms
60.10
1.80 ms
52.90
1.41 ms
OFF execution time (
µ s)
17.30
1.5
1.5
1.5
1.5
1.5
1.5
19.7
1.5
1.5
21.7
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
331
Instruction Execution Times
Instruction
NEG(––)
NEGL(––)
ZCPL(––)
SCL(––)
HKY(––)
DSW(––)
Conditions
When converting a constant to a word
When converting a word to a word
When converting : DM to : DM
When converting a word to a word
When converting : DM to : DM
When comparing two words
When comparing two : DM
Word for SV
:
DM for SV
When designating a word
When designating
:
DM
DM CS output
DM RD output
DM data retrieval
: DM CS output
: DM RD output
: DM data retrieval
Section 6-3
ON execution time (
µ s)
34.90
37.50
72.10
47.00
81.90
71.90
123.10
98.20
150.00
55.7
72.9
60.20
61.00
78.80
77.70
78.40
94.20
OFF execution time (
µ s)
1.5
1.5
1.5
1.5
21.7
21.1
332
I/O Response Time Section 6-4
6-4 I/O Response Time
The I/O response time is the time it takes for the PC to output a control signal after it has received an input signal. The time it takes to respond depends on the cycle time and when the CPU receives the input signal relative to the input refresh period.
The minimum and maximum I/O response time calculations described below are for where IR 00000 is the input bit that receives the signal and IR 00200 is the output bit corresponding to the desired output point.
00000
00200
6-4-1 Basic Systems
Minimum I/O Response
Time
The PC responds most quickly when it receives an input signal just prior to the
I/O refresh period in the cycle. Once the input bit corresponding to the signal has been turned ON, the program will have to be executed once to turn ON the output bit for the desired output signal and then the I/O refresh operation would have to be repeated to refresh the output bit. The I/O response time in this case is thus found by adding the input ON-delay time, the cycle time, and the output
ON-delay time. This situation is illustrated below.
Cycle
Cycle time
Instruction execution
I/O refresh
Cycle time
Instruction execution
Instruction execution
Input signal
Input
ON delay
CPU reads input signal
Output ON delay
Output signal
I/O response time
Minimum I/O response time =
Input ON delay + Cycle time + I/O refresh time + Output ON delay
333
I/O Response Time
Maximum I/O Response
Time
Section 6-4
The PC takes longest to respond when it receives the input signal just after the
I/O refresh phase of the cycle. In this case the CPU does not recognize the input signal until the end of the next cycle. The maximum response time is thus one cycle longer than the minimum I/O response time, except that the I/O refresh time would not need to be added in because the input comes just after it rather than before it.
Cycle
Cycle time
Instruction execution
I/O refresh
Cycle time
Instruction execution
Cycle time
Instruction execution
Input signal
Input
ON delay
CPU reads input signal
Output
ON delay
Output signal
I/O response time
Calculation Example
Maximum I/O response time =
Input ON delay + (Cycle time x 2) + Output ON delay
The data in the following table would produce the minimum and maximum cycle times shown calculated below.
Item
Input ON-delay
Output ON-delay
Cycle time
Time
1.5 ms
15 ms
20 ms
Minimum I/O response time = 1.5 + 20 + 15 = 36.5 ms
Maximum I/O response time = 1.5 + (20 x 2) +15 = 56.5 ms
Note In this example the I/O refresh time is negligible has not been included in the minimum I/O response time.
6-4-2 Remote I/O Systems
With C200HS Remote I/O Systems, only the cycle time of the PC needs to be considered in computing the I/O response times as long as the remote I/O transmission time is negligible and smaller than the cycle time. The cycle time, however, is increased by the presence of the Remote I/O System.
The processing that determines and the methods for calculating maximum and minimum response times from input to output are provided in this section. Calculations assume that both the input and the output are located on Slave Racks in a
Remote I/O System, but the calculations are the same for I/O points on Optical
I/O Units, I/O Link Units, I/O Terminals, etc.
Input on
Slave Rack
Output on
Slave Rack
X
Although more precise equations are possible if required, equations used for the following calculations do not consider fractions of a scan.
334
I/O Response Time Section 6-4
In looking at the following timing charts, it is important to remember the sequence in which processing occurs during the PC scan, particular that inputs will not produce programmed actions until the program has been executed.
When calculating the response times involving inputs and outputs from another
CPU connected by an I/O Link Unit, the cycle time of the controlling CPU and the cycle time of the PC to which the I/O Link Unit is mounted must both be considered.
!
Caution Noise may increase I/O delays.
Remote I/O Transmission
Times
Minimum I/O Response
Time
C200HS
CPU
Master
The remote I/O transmission time is computed as follows:
T
RM
= Total Slave transmission time for one Master
= Σ T
RT
+ T
TT
T
RT
= Transmission time for each Slave
= 1.4 ms + (0.2 ms x n)
Where n = number of I/O words on the Slave Rack
T
TT
= Optical I/O Unit/I/O Terminal transmission time
= 2 ms x m
Where m = number of Optical I/O Units/I/O Terminals
The minimum response time occurs when all signals are processed as soon as they are received. Here, three scans are required so that the program is executed, as shown in the following diagram.
Time = Input ON delay + cycle time x 3 + output ON delay
Cycle time
Program execution
Transfer to CPU
Transfer to Master
Slave
Slave I/O refresh
Input
Output
Maximum I/O Response
Time
The maximum response time occurs when the input just misses the program execution portion of the scan, meaning that processing must wait for the next transmission and then the next (i.e., the fourth) scan.
Time = Input ON delay + cycle time x 4 + output ON delay
Note Use the maximum cycle time output to AR 26 in computing the maximum I/O response time.
Cycle time
C200HS
CPU
Master
Transfer to CPU
Program execution
Slave I/O refresh Transfer to Master
Slave
Input
Output
335
I/O Response Time Section 6-4
Example Calculations Calculations would be as shown below for an input ON delay of 1.5 ms, an output ON delay of 15 ms, and a cycle time of 20 ms.
Minimum I/O Response Time
Time = 1.5 ms + (20 ms x 3) + 15 ms = 76.5 ms
Maximum I/O Response Time
Time = 1.5 ms + (20 ms x 4) + 15 ms = 96.5 ms
Note 1. The cycle time may be less than or equal to the remote I/O transmission time when there are Special I/O Units on Slave Racks. If this is the case, there may be cycles when I/O is not refreshed between the Master and the
C200HS CPU.
2. Refreshing is performed for Masters only once per cycle, and then only after confirming completion of the remote cycle.
3. The short duration of ON/OFF status produced by differentiated instructions can cause inaccurate signals when dealing with Remote I/O Systems unless appropriate programming steps are taken.
6-4-3 Host Link Systems
The following diagram illustrates the processing that takes place when an input on one PC is transferred through the Host Link System to turn ON an output on another PC. Refer to Host Link System documentation for further details.
Input on #0 Output on #32
X
Host computer
Buffer for Host
Link Unit # 0
CPU reads input signal
Command/response for Unit # 0
Command
Command/response for Unit # 31
Command
Response
Host computer processing time
Response
Cycle time
PC for Host
Link Unit # 0
I/O refresh
Buffer for Host
Link Unit # 31
Host link service
CPU writes output signal
Cycle time
PC for Host
Link Unit # 31
Input signal
Output signal
Input ON delay
Host link service I/O refresh
Output ON delay
Minimum response time =
I/O response time
The equations used to calculate the minimum and maximum cycle times are given below. The number of cycles required for each PC depends on the amount of data being read/written.
Input ON delay + Command transmission time + (Cycle time of PC for Unit #0 x 3) + Response transmission time + Host computer processing time + Command transmission time + (Cycle time of PC for Unit #31 x 3) + Output ON delay
Maximum response time = Input ON delay + Command transmission time + (Cycle time of PC for Unit #0 x 10) + Response transmission time + Host computer processing time + Command transmission time + (Cycle time of PC for Unit #31 x 10) + Output ON delay
336
I/O Response Time Section 6-4
6-4-4 PC Link Systems
The processing that determines and the methods for calculating maximum and minimum response times from input to output are provided in this subsection.
The following System and I/O program steps will be used in all examples below.
This System contains eight PC Link Units.
In looking at the following timing charts, it is important to remember the sequence processing occurs during the PC scan, particular that inputs will not produce programmed-actions until the program has been execution.
Unit 0
PC Link Unit
PC
Input
Input on PC of Unit 0
LR bit
Output on PC of Unit 7
X
PC Link Unit
PC
X
Output
Unit 7
Input LR XXXX LR XXXX Output
X
!
Caution Noise may increase I/O delays.
PC Link Conditions
Minimum Response Time
Cycle time
The PC Link System used in this example consists of the following:
• No. of PCs linked: 8
•
No. of LR points linked: 128 per PC
•
Maximum PC:
•
LR points used:
8
1,024
The following illustrates the data flow that will produce the minimum response time, i.e., the time that results when all signals and data transmissions are processed as soon as they occur.
Program executed.
I/O refresh
PC with
Unit 0
Buffer in Unit 0 Minimum transmission time
PC Link Unit transmissions
Buffer in Unit 7
PC with
Unit 7
Program executed.
I/O refresh
Cycle time
Input
Output
The equation for minimum I/O response time is thus as follows:
Response time = Input ON delay + Cycle time of PC of Unit 0 + Minimum transmission time + (Cycle time of PC of Unit 7 x 2) + Output ON delay
337
I/O Response Time
Maximum Response Time
Section 6-4
Inserting the following values into this equation produces a minimum I/O response time of 149.3 ms.
Input ON delay:
Output ON delay:
Cycle time for PC of Unit 0:
Cycle time for PC of Unit 7:
1.5 ms
15 ms
20 ms
50 ms
The following diagram illustrates the data flow that will produce the maximum response time. Delays occur because signals or data is received just after they would be processed or because data is sent during processing. In either case, processing must wait until the next scan/polling cycle.
First output to the buffer in the polling unit is delayed by the setting of the number of LR bits to be refreshed each scan. A similar delay is present when the LR data reaches Unit 7. The polling delay is the result of the LR data in its PC being updated immediately after the previous was sent to the buffer in the PC Link Unit, cause a delay until the next polling cycle. One more polling cycle is then required before the data reaches the buffer in PC Link Unit 7.
I/O refresh
PC with
Unit 0
Buffer in Unit 0
Cycle time
PC Link Unit transmissions
Buffer in Unit 7
PC with
Unit 7
Polling delay
PC Link polling time
Maximum transmission time
Induction sequence processing time
Cycle time
Input
Output
The equation for maximum I/O response time is thus as follows:
Response time = Input ON delay + [Cycle time of PC of Unit 0 x (Number of LR transfer bits ÷ I/O refresh bits)] + α + (PC Link polling time +
Induction sequence processing time) + {Cycle time of PC of
Unit 7 x [(Number of LR transfer bits ÷ I/O refresh bits) x 2 + 1]}
+ β + Output ON delay
If cycle time of PC of Unit 0 > PC Link polling time,
α
= cycle time of PC of Unit 0. If cycle time of PC of Unit 0 < PC Link polling time,
α
= PC Link polling time.
If cycle time of PC of Unit 7 > PC Link polling time,
β
= cycle time of PC of Unit 7. If cycle time of PC of Unit 7 < PC Link polling time,
β
= PC Link polling time.
Inserting the following values into this equation produces a maximum I/O response time of 661.3 ms.
Input ON delay: 1.5 ms
Output ON delay:
Cycle time for PC of Unit 0:
15 ms
20 ms
Cycle time for PC of Unit 7:
PC Link polling time:
50 ms
2.8 ms x 8 PCs + 10 ms = 32.4 ms
338
I/O Response Time Section 6-4
Reducing Response Time
Induction sequence processing: 15 ms x (8 PCs – 8 PCs) = 0 ms
I/O refresh bits for Unit 0 256
I/O refresh bits for Unit 7 256
IORF(97) can be used in programming to shorten the I/O response time greater than is possible by setting a high number of refresh bits. (Remember, increasing the number of refresh bits set on the back-panel LED shortens response time, but increases the cycle time of the PC.)
The following calculations for the maximum cycle time use the same example
System configuration as that used in 5–2 Response Times. In programming the
PCs for PC Link Units #0 and #7, IORF(97) is executed during every PC scan for the PC Link Units. The basic equation for the maximum I/O response time is as follows:
Response time = Input ON delay + [Cycle time of PC of Unit 0 x (Number of LR transfer bits
÷
Number of I/O refresh bits
÷
2)] +
α
+ PC Link polling time + Induction sequence processing time + {Cycle time of PC of Unit 7 x [(Number of LR transfer bits
÷
Number of
I/O refresh bits
÷
2) x 2 + 1]} +
β
+ Output ON delay
If cycle time of PC of Unit 0 > PC Link polling time,
α
= cycle time of PC of Unit 0. If cycle time of PC of Unit 0 < PC Link polling time,
α
= PC Link polling time.
If cycle time of PC of Unit 7 > PC Link polling time,
β
= cycle time of PC of Unit 7. If cycle time of PC of Unit 7 < PC Link polling time,
β
= PC Link polling time.
The required data from the example System configuration is as follows:
Input ON delay
Output ON delay
Cycle time of PC of Unit 0
1.5 ms
15 ms
Cycle time of PC of Unit 7
Number of PC Link Units
Number of LR bits
20 ms + 5.7 ms = 25.7
(5.7 ms required for IORF execution)
50 ms + 5.7 ms = 55.7
(5.7 ms required for IORF execution)
8
1,024
256 Number of refresh bits for Unit 0
Number of refresh bits for Unit 7
PC Link polling time
256
2.8 ms x 8 PCs + 10 ms = 32.4 ms
Induction sequence processing time 15 ms x (8 PCs – 8 PCs) = 0 ms
Placing these values into the equation produces a maximum I/O response time of 466.9 ms, approximately 200 ms shorter than when IORF is not used.
6-4-5 One-to-one Link I/O Response Time
When two C200HSs are linked one-to-one, the I/O response time is the time required for an input executed at one of the C200HSs to be output to the other
C200HS by means of one-to-one link communications.
One-to-one link communications are carried out reciprocally between the master and the slave. The respective transmission times are as shown below, depending on the number of LR words used.
Number of words used
64 words (LR 00 to LR 63)
32 words (LR 00 to LR 31)
16 words (LR 00 to LR 15)
39 ms
20 ms
10 ms
Transmission time
339
I/O Response Time
Input
Section 6-4
The minimum and maximum I/O response times are shown here, using as an example the following instructions executed at the master and the slave. In this example, communications proceed from the master to the slave.
Output (LR) Input
(LR)
Output
The following conditions are taken as examples for calculating the I/O response times.
Input ON delay:
Master cycle time:
8 ms
10 ms
Slave cycle time:
Output ON delay:
14 ms
10 ms
Number of LR words: 64 words
Minimum I/O Response Time The C200HS responds most quickly under the following circumstances:
1, 2, 3...
1. The C200HS receives an input signal just prior to the input refresh phase of the cycle.
2. The master to slave transmission begins immediately.
3. The slave executes communications servicing immediately after completion of communications.
Master
Input point
Input bit
CPU processing
Input ON delay
I/O refresh
Overseeing, communications, etc.
Instruction execution
Cycle time
Instruction execution
One-to-one link communications
Master to
Slave
CPU processing
Slave
Instruction execution
Instruction execution
Output ON delay
Output point
The minimum I/O response time is as follows:
+
Input ON delay:
Master cycle time:
Transmission time:
Slave cycle time:
8 ms
10 ms
39 ms
15 ms
Output ON delay: 10 ms
Minimum I/O response time: 82 ms
Maximum I/O Response Time The C200HS takes the longest to respond under the following circumstances:
1, 2, 3...
1. The C200HS receives an input signal just after the input refresh phase of the cycle.
2. The master to slave transmission does not begin immediately.
340
I/O Response Time
Input point
Master Input bit
CPU processing
Input ON delay
Instruction execution
Section 6-4
3. Communications are completed just after the slave executes communications servicing.
Instruction execution
I/O refresh
Overseeing, communications, etc.
Cycle time
Instruction execution
One-to-one link communications
Master to
Slave
Slave to
Master
Master to
Slave
Slave
CPU processing
Instruction execution
Instruction execution
Instruction execution
Output ON delay
Output point
The maximum I/O response time is as follows:
+
Input ON delay:
Master cycle time:
Transmission time:
Slave cycle time:
8 ms
10 ms
39 ms
15 ms
2
3
2
Output ON delay: 10 ms
Maximum I/O response time: 185 ms
6-4-6 Interrupt Response Times
The response time from the time an interrupt input is received until the interrupt subroutine execution has been completed is described next.
Input Interrupts
External interrupt input signal
Internal interrupt signal t1 t2
Interrupt subroutine execution t1 = ON delay of Interrupt Input Unit t2 = Software interrupt response time
Total interrupt response time = t1 + t2
The ON delay of Interrupt Input Unit is 0.2 ms or less.
The software interrupt response time depends on the interrupt response parameter setting in DM 6620 of the PC Setup. If the DM 6620 is set for the C200Hcompatible mode (0000), the software interrupt response time is less than
10 ms. If the DM 6620 is set for the C200HS mode (1xxx), the software interrupt response time is less than 1 ms. The total interrupt response time is thus as shown in the following table.
Interrupt response setting
C200H-compatible mode
C200HS mode
Total interrupt response time
0.2 ms + (Total of following: Special I/O processing time, Remote I/O processing time,
Host Link servicing time, instruction execution)
1.2 ms or less
341
I/O Response Time
Scheduled Interrupts
Section 6-4
Scheduled interrupt interval
Hardware time clock
Scheduled interrupt subroutine execution t3 t3 t3 t3 t3 = Software interrupt response time
Total interrupt response time = t3 (software interrupt response time)
The software interrupt response time depends on the interrupt response parameter setting in DM 6620 of the PC Setup. If the DM 6620 is set for the C200Hcompatible mode (0000), the software interrupt response time is less than
10 ms. If the DM 6620 is set for the C200HS mode (1xxx), the software interrupt response time is less than 1 ms. The total interrupt response time is thus as shown in the following table.
Interrupt response setting
C200H-compatible mode
C200HS mode
Total interrupt response time
Total of following: Special I/O processing time,
Remote I/O processing time, Host Link servicing time, instruction execution
1.0 ms or less
Note 1. If there is any instruction in the program that requires longer than 10 ms to execute when using the C200H-compatible mode, the total interrupt response time will be equal to the execution time of the instruction requiring longer than 10 ms.
2. The above calculations assume that only one interrupt requires executed at any one time. If multiple interrupts are generated at the same time, execution of all but the first interrupt will go on standby, increasing the response times given above.
3. If SYSMAC NET/SYSMAC LINK Units are being serviced when an interrupt occurs, the interrupt will not be processed until SYSMAC NET/SYSMAC
LINK Unit servicing has been completed. The response times in this case will be as shown in the following table and will not be affected by the interrupt response setting.
Interrupt Total interrupt response time
Input interrupt 10.2 ms max.
Scheduled interrupt 10 ms max.
Interrupt Processing Time The processing time from receiving an interrupt input, through program execution, and until a return is made to the original program location is described next.
The limit of the count frequency resulting from using the scheduled interrupt period or input interrupts as the count input is determined by the interrupt processing time.
Interrupt processing time =
Total interrupt response time + Interrupt program execution time +
Interrupt return time
The interrupt program execution time is determined by the content of the interrupt subroutine. This time is negligible f only SBN(92) and RET(93) are executed.
The interrupt return time is 0.04 ms.
342
I/O Response Time Section 6-4
Note 1. If there are several elements that can cause interrupts or if the interrupt period is shorted than the average interrupt processing time, the interrupt subroutine will be executed and the main program will not be executed. This will cause the cycle monitoring time to be exceeded and an FALS 9F error will be generated, stopping PC operation.
2. The maximum interrupt program execution time is contained in SR 262 and
SR 263.
Interrupt Input Pulse Width The pulse width input to Interrupt Input Units must be set to within the conditions shown in the following diagram.
ON time:
OFF time:
0.2 ms min.
0.5 ms min.
0.2 ms min.
0.5 ms min.
343
SECTION 7
Program Monitoring and Execution
This section provides the procedures for monitoring and controlling the PC through a Programming Console. Refer to the LSS
Operation Manual for LSS procedures if you are using a computer running LSS.
7-1 Monitoring Operation and Modifying Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-1 Bit/Word Monitor
7-1-2 Forced Set/Reset
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-3 Forced Set/Reset Cancel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-4 Hexadecimal/BCD Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-5 Hex/ASCII Display Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-6 4-digit Hex/Decimal Display Change
7-1-7 8-digit Hex/Decimal Display Change
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-8 Differentiation Monitor
7-1-9 3-word Monitor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-10 3-word Data Modification
7-1-11 Binary Monitor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-12 Binary Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-13 Changing Timer/Counter SV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-14 Expansion Instruction Function Code Assignments
7-1-15 UM Area Allocation
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-16 Reading and Setting the Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-17 Expansion Keyboard Mapping
7-1-18 Keyboard Mapping
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
354
355
356
357
358
358
359
346
346
349
351
352
361
362
365
366
367
367
368
345
Monitoring Operation and Modifying Data Section 7-1
7-1 Monitoring Operation and Modifying Data
The simplest form of operation monitoring is to display the address whose operand bit status is to be monitored using the Program Read or one of the search operations. As long as the operation is performed in RUN or MONITOR mode, the status of any bit displayed will be indicated.
This section provides other procedures for monitoring data as well as procedures for modifying data that already exists in a data area. Data that can be modified includes the PV (present value) and SV (set value) for any timer or counter.
All monitor operations in this section can be performed in RUN, MONITOR, or
PROGRAM mode and can be cancelled by pressing CLR.
All data modification operations except for timer/counter SV changes are performed after first performing one of the monitor operations. Data modification is possible in either MONITOR or PROGRAM mode, but cannot be performed in
RUN mode.
7-1-1 Bit/Word Monitor
The status of any bit or word in any data area can be monitored using the following operation. Although the operation is possible in any mode, ON/OFF status displays will be provided for bits in MONITOR or RUN mode only.
The Bit/Digit Monitor operation can be entered either from a cleared display by designating the first bit or word to be monitored or it can be entered from any address in the program by displaying the bit or word address whose status is to be monitored and pressing MONTR.
When a bit is monitored, it’s ON/OFF status will be displayed (in MONITOR or
RUN mode); when a word address is designated other than a timer or counter, the digit contents of the word will be displayed; and when a timer or counter number is designated, the PV of the timer will be displayed and a small box will appear if the completion flag of a timer or counter is ON. When multiple words are monitored, a caret will appear under the leftmost digit of the address designation to help distinguish between different addresses. The status of TR bits and SR flags (e.g., the arithmetic flags), cleared when END(01) is executed, cannot be monitored.
Up to six memory addresses, either bits, words, or a combination of both, can be monitored at once, although only three of these are displayed at any one time. To monitor more than one address, return to the start of the procedure and continue designating addresses. Monitoring of all designated addresses will be maintained unless more than six addresses are designated. If more than six addresses are designated, the leftmost address of those being monitored will be cancelled.
To display addresses that are being monitored but are not presently on the Programming Console display, press MONTR without designating another address. The addresses being monitored will be shifted to the right. As MONTR is pressed, the addresses being monitored will continue shifting to the right until the rightmost address is shifted back onto the display from the left.
During a monitor operation the up and down keys can be pressed to increment and decrement the leftmost address on the display and CLR can be pressed to cancel monitoring the leftmost address on the display. If the last address is cancelled, the monitor operation will be cancelled. The monitor operation can also be cancelled regardless of the number of addresses being monitored by pressing SHIFT and then CLR.
LD and OUT can be used only to designate the first address to be displayed; they cannot be used when an address is already being monitored.
346
Monitoring Operation and Modifying Data
Key Sequence
Section 7-1
Clears leftmost address
Cancels monitor operation
Examples
Program Read then Monitor
The following examples show various applications of this monitor operation.
00100
00100READ
TIM 000
T000
1234
T001 o0000
Indicates Completion flag is ON
00100
TIM 001
Monitor operation is cancelled
347
Monitoring Operation and Modifying Data
Bit Monitor
Section 7-1
00000
00000
LD 00001
00001
^ ON
00000
CONT 00001
Note The status of TR bits SR flags SR 25503 to 25507 (e.g., the arithmetic flags), cleared when END(01) is executed, cannot be monitored.
Word Monitor
00000
00000
CHANNEL 000
00000
CHANNEL LR 01
cL01
FFFF
cL00
0000
348
Monitoring Operation and Modifying Data
+Multiple Address Monitoring
Section 7-1
00000
00000
TIM 000
T000
0100
00000 T000
0100
00001 T000
0100
00001 T000
OFF 0100
D000000001 T000
^OFF 0100
D000000001 T000
10FF^ OFF 0100
T000D000000001
0100 10FF^ OFF
D000000001
10FF^ OFF
00001
^ OFF
00000
CONT 00001
00000
CHANNEL DM 0000
Cancels monitoring of leftmost address
Monitor operation is cancelled
0000000001
S ONR OFF
Indicates Force Reset in operation.
Indicates Force Set in operation.
7-1-2 Forced Set/Reset
When the Bit/Digit Monitor operation is being performed and a bit, timer, or counter address is leftmost on the display, PLAY/SET can be pressed to turn ON the bit, start the timer, or increment the counter and REC/RESET can be pressed to turn OFF the bit or reset the timer or counter. Timers will not operate in PRO-
GRAM mode. SR bits cannot be turned ON and OFF with this operation.
349
Monitoring Operation and Modifying Data Section 7-1
Bit status will remain ON or OFF only as long as the key is held down; the original status will return as soon as the key is released. If a timer is started, the completion flag for it will be turned ON when SV has been reached.
SHIFT and PLAY/SET or SHIFT and REC/RESET can be pressed to maintain the status of the bit after the key is released. The bit will not return to its original status until the NOT key is pressed, or one of the following conditions is met.
1, 2, 3...
1. The Force Status Clear operation is performed.
2. The PC mode is changed. (See note.)
3. Operation stops due to a fatal error or power interruption.
4. The I/O Table Registration operation is performed.
This operation can be used in MONITOR mode to check wiring of outputs from the PC prior to actual program execution. This operation cannot be used in RUN mode.
Note The forced set/reset bit status will be maintained when switching from PRO-
GRAM to MONITOR mode if the Force Status Hold Bit is ON and DM 6601 of the
PC Setup has been set maintain the bit’s status. Refer to 3-6-4 PC Setup for details.
Key Sequence
Example The following example shows how either bits or timers can be controlled with the
Force Set/Reset operation. The displays shown below are for the following program section.
00100
TIM 000
#0123
012.3 s
TIM 000
00500
Address Instruction
00200 LD
00201 TIM
00202
00203
LD
OUT
#
TIM
Data
00100
000
0123
000
00500
350
Monitoring Operation and Modifying Data Section 7-1
The following displays show what happens when TIM 000 is set with 00100 OFF
(i.e., 00500 is turned ON) and what happens when TIM 000 is reset with 00100
ON (i.e., timer starts operation, turning OFF 00500, which is turned back ON when the timer has finished counting down the SV).
(This example is performed in MONITOR mode.)
0010000500
^ OFF^ OFF
Monitoring 00100 and 00500.
0010000500
= ON^ OFF
Force set bit status.
Indicates that force set/reset is in progress.
0010000500
= OFF^ OFF
T0000010000500
^ OFF^ OFF
T0000010000500
0123^ OFF^ OFF
T0000010000500
= 0000^ OFF^ ON
T0000010000500
0123^ OFF^ OFF
T0000010000500 o0000^ ON^ ON
T0000010000500
= 0123^ ON^ OFF
T0000010000500
0122^ ON^ OFF
T0000010000500 o0000^ ON^ ON
Reset the force-set bit.
Monitoring TIM 000.
Force setting TIM 000 turns ON 00500.
TIM 000 returns to its original status when PLAY/SET is released.
Display with 0010 originally ON.
Timer starts timing, turning
00500 OFF.*
When the time is up, 00500 goes ON again.
Indicates that the time is up.
*Timing not done in PROGRAM mode.
7-1-3 Forced Set/Reset Cancel
This operation restores the status of all bits in the I/O, IR, TIM, CNT, HR, AR, or
LR areas which have been force set or reset. It can be performed in PROGRAM or MONITOR mode.
Key Sequence
When the PLAY/SET and REC/RESET keys are pressed, a beeper will sound. If you mistakenly press the wrong key, then press CLR and start again from the beginning.
351
Monitoring Operation and Modifying Data
Example
Section 7-1
The following example shows the displays that appear when Restore Status is carried out normally.
00000
00000
00000FORCE RELE?
00000FORCE RELE
END
7-1-4 Hexadecimal/BCD Data Modification
When the Bit/Digit Monitor operation is being performed and a BCD or hexadecimal value is leftmost on the display, CHG can be input to change the value. SR words cannot be changed.
If a timer or counter is leftmost on the display, the PV will be displayed and will be the value changed. See 7-1-13 Changing Timer/Counter SV for the procedure to change SV. PV can be changed in MONITOR mode only when the timer or counter is operating.
To change contents of the leftmost word address, press CHG, input the desired value, and press WRITE
Key Sequence
Word currently monitored on left of display.
[ Data ]
352
Monitoring Operation and Modifying Data
Example
Section 7-1
The following example shows the effects of changing the PV of a timer.
This example is in MONITOR mode
00000
00000
TIM 000
T000
0122
Monitor status of timer PV that will be changed.
Timing
PRES VAL?
T000 0119 ????
PV decrementing
Timing
PRES VAL?
T000 0100 0200
T000
0199
Timing
PV changed. Timer/counter PVs can be changed even when the timer/counter is operating.
Timing
353
Monitoring Operation and Modifying Data Section 7-1
7-1-5 Hex/ASCII Display Change
This operation converts DM data displays from 4-digit hexadecimal data to AS-
CII and vice versa.
Key Sequence
Word currently displayed.
Example 00000
00000
CH DM 0000
D0000
4412
D0000
"AB"
D0000
4142
Monitor the desired DM word.
Press TR to change the display to ASCII code.
Press TR again to return the display to hexadecimal.
354
Monitoring Operation and Modifying Data Section 7-1
7-1-6 4-digit Hex/Decimal Display Change
This operation converts data displays from normal or signed 4-digit hexadecimal data to decimal and vice versa.
Decimal values from 0 to 65,535 are valid when inputting normal 4-digit hexadecimal data, and decimal values from –32,768 to +32,767 are valid when inputting signed 4-digit hexadecimal data.
Key Sequence
Single word or
3-word monitor currently displayed.
TR
(NOT switches between normal and signed data.)
[New data]
Clear new input data.
Specifies positive signed data.
Specifies negative signed data.
TR
Example
TR
TR
cL01D000000001
CFC7 1234R OFF
cL01
-12345
cL01
53191
cL01
-12345
PRES VAL?
cL01-12345
PRES VAL?
cL01+12345
PRES VAL?
cL01+32767
cL01
+32767
cL01D000000001
7FFF 1234R OFF
Monitor the desired word.
(Leftmost word in 3-word monitor.)
Press SHIFT and TR to change the display to signed decimal.
Press NOT to switch back and forth between signed and normal data.
Press CHG to change the content of the displayed word.
Press PLAY/SET to specify positive signed data.
Input the new value.
Press WRITE to enter the new data to memory.
Press SHIFT and TR to change the display back to hexadecimal.
355
Monitoring Operation and Modifying Data Section 7-1
7-1-7 8-digit Hex/Decimal Display Change
This operation converts data displays from normal or signed, 4 or 8-digit hexadecimal data to decimal and vice versa.
Decimal values from 0 to 4,294,967,295 are valid when inputting normal 8-digit hexadecimal data, and decimal values from –2,147,483,648 to +2,147,483,647 are valid when inputting signed 8-digit hexadecimal data.
Key Sequence
3-word monitor currently displayed.
TR
[New data]
TR
(NOT switches between normal and signed data.)
Clear new input data.
Specifies positive signed data.
Specifies negative signed data.
Example
TR
TR
cL01D000000001
8000 1234R OFF
cL01
-32768
cL02 cL01
-0000098304
cL02 cL01
4294868992
cL02 cL01
-0000098304
PRES VAL?
cL02-0000098304
PRES VAL?
cL02+0000098304
[New data]
PRES VAL?
cL02+1234567890
cL02 cL01
+1234567890
cL01D000000001
02D2 1234R OFF
Rightmost four digits
Monitor the first of the desired words.
(Leftmost word in 3-word monitor.)
Press SHIFT and TR to change the display to signed decimal.
Press EXT to change the display to
8-digit signed decimal.
(In this case, LR 02 contains FFFE.)
Press NOT to switch back and forth between signed and normal data.
Press CHG to change the contents of the displayed words.
Press PLAY/SET to specify positive signed data.
Input the new value.
(1234567890 in this case.)
Press WRITE to enter the new data to memory.
Press SHIFT and TR to change the display back to hexadecimal.
356
Monitoring Operation and Modifying Data Section 7-1
7-1-8 Differentiation Monitor
This operation can be used to monitor the up or down differentiation status of bits in the IR, SR, AR, LR, HR, and TC areas. To monitor up or down differentiation status, display the desired bit leftmost on the bit monitor display, and then press
SHIFT and the Up or Down Arrow Key.
A CLR entry changes the Differentiation Monitor operation back to a normal bit monitor display.
Key Sequence
Bit monitor in progress
Example
L000000108H2315
OFF OFF ON
L000000108H2315
U@OFF OFF ON
L000000108H2315
OFF OFF ON
D0002
0123
Monitor the desired bit so that it is leftmost on the screen.
Press SHIFT and Up Arrow to specify up differentiation (U@).
(Press SHIFT and Down Arrow to specify down differentiation (D@).
The buzzer will sound when up
(U@) or down (D@) differentiation is detected.
The original bit monitor display will return when differentiation monitoring is completed.
Press CLR to cancel differentiation monitoring and return to the original bit monitor display.
357
Monitoring Operation and Modifying Data Section 7-1
7-1-9 3-word Monitor
To monitor three consecutive words together, specify the lowest numbered word, press MONTR, and then press EXT to display the data contents of the specified word and the two words that follow it.
A CLR entry changes the Three-word Monitor operation to a single-word display.
Key Sequence
Single-word monitor in progress
Example 00000
00000
CHANNEL DM 0000
D0000
89AB
D0002D0001D0000
0123 4567 89AB
D0003D0002D0001
ABCD 0123 4567
D0004D0003D0002
EF00 ABCD 0123
D0005D0004D0003
1111 EF00 ABCD
D0004D0003D0002
EF00 ABCD 0123
D0002
0123
Specify the first of the 3 words you want to monitor.
Press the Up and Down Arrow keys to change word addresses.
7-1-10 3-word Data Modification
This operation changes the contents of a word during the 3-Word Monitor operation. The blinking square indicates where the data can be changed. After the new data value is keyed in, pressing WRITE causes the original data to be overwritten with the new data. If CLR is pressed before WRITE, the change operation will be cancelled and the previous 3-word Monitor operation will resume.
This operation cannot be used to change SR 253 through SR 255. Only those words displayed on the 3-word Monitor display can be changed.
Key Sequence
3 words currently displayed
[ Data ]
358
Monitoring Operation and Modifying Data
Example
D0002D0001D0000
0123 4567 89AB
D0002 3CH CHG?
= 0123 4567 89AB
D0002 3CH CHG?
0001 4567 89AB
D0002 3CH CHG?
0001 = 4567 89AB
D0002 3CH CHG?
0001 = 2345 89AB
D0002D0001D0000
0001 2345 89AB
D0002D0001D0000
0001 4567 89AB
3-word Monitor in progress.
Stops in the middle of monitoring.
Input new data.
Resumes previous monitoring.
Section 7-1
7-1-11 Binary Monitor
You can specify that the contents of a monitored word be displayed in binary by pressing SHIFT and MONTR after the word address has been input. Words can be successively monitored by using the up and down keys to increment and decrement the displayed word address. To clear the binary display, press CLR.
Key Sequence
[Word]
Binary monitor clear
All monitor clear
359
Monitoring Operation and Modifying Data
Example 00000
00000
CHANNEL 000
c000 MONTR
0000000000001111
c001 MONTR
0000010101010100
00000
CHANNEL 001
00000
00000
CHANNEL DM 0000
D0000
FFFF
D0000 MONTR
1111111111111111
D0000
FFFF
00000
CHANNEL DM 0000
0000S0100R0110SR
Section 7-1
Indicates Force Reset in effect
Indicates Force Set in effect
360
Monitoring Operation and Modifying Data Section 7-1
7-1-12 Binary Data Modification
This operation assigns a new 16-digit binary value to an IR, HR, AR, LR, or DM word.
The cursor, which can be shifted to the left with the up key and to the right with the down key, indicates the position of the bit that can be changed. After positioning to the desired bit, a 0 or a 1 can then be entered as the new bit value. The bit can also be Force Set or Force Reset by pressing SHIFT and either PLAY/SET or
REC/RESET. An S or R will then appear at that bit position. Pressing the NOT key will clear the force status, S will change to 1, and R to o. After a bit value has been changed, the blinking square will appear at the next position to the right of the changed bit.
Key Sequence
Word currently displayed in binary.
(Force Status Clear)
361
Monitoring Operation and Modifying Data
Example
Section 7-1
00000
CHANNEL 000
00000
CHANNEL 001
c001 MONTR
0000010101010101
c001 CHG?
= 000010101010101
c001 CHG?
1 = 00010101010101
c001 CHG?
10 = 0010101010101
c001 CHG?
100 = 010101010101
c001 CHG?
100S = 10101010101
c001 CHG?
100 = 010101010101
c001 CHG?
10 = S010101010101
c001 CHG?
1 = RS010101010101
c001 MONTR
10RS010101010101
IR bit 00115 IR bit 00100
7-1-13 Changing Timer/Counter SV
There are two ways to change the SV of a timer or counter. It can be done either by inputting a new value; or by incrementing or decrementing the current SV.
Either method can be used only in MONITOR or PROGRAM mode. In MONI-
TOR mode, the SV can be changed while the program is being executed. Incrementing and decrementing the SV is possible only when the SV has been entered as a constant.
To use either method, first display the address of the timer or counter whose SV is to be changed, presses the down key, and then press CHG. The new value can then be input numerically and WRITE pressed to change the SV or EXT can be pressed followed by the up and down keys to increment and decrement the current SV. When the SV is incremented and/or decremented, CLR can be pressed once to change the SV to the incremented or decremented value but remaining in the display that appeared when EXT was pressed or CLR can be pressed twice to return to the original display with the new SV.
This operation can be used to change a SV from designation as a constant to a word address designation and visa verse.
362
00000
Monitoring Operation and Modifying Data
Key Sequence
Section 7-1
Example
Inputting New SV and
Changing to Word
Designation
The following examples show inputting a new constant, changing from a constant to an address, and incrementing to a new constant.
00000
00000
TIM 000
00201SRCH
TIM 000
00201 TIM DATA
#0123
00201 TIM DATA
T000 #0123 #????
00201 TIM DATA
T000 #0123 #0124
00201 TIM DATA
#0124
00201 DATA?
T000 #0123 c???
00201 DATA?
T000 #0123 c010
00201 TIM DATA
010
363
Monitoring Operation and Modifying Data
Incrementing and
Decrementing
00000
Section 7-1
00000
TIM 000
00201SRCH
TIM 000
00201 TIM DATA
#0123
00201 TIM DATA
T000 #0123 #????
00201DATA ? U/D
T000 #0123 #0123
Current SV (during change operation)
SV before the change
00201DATA ?
T000 #0123 #0122
00201DATA ?
T000 #0123 #0123
00201DATA ?
T000 #0123 #0124
00201DATA ?
T000 #0124 #????
00201 TIM DATA
#0124
Returns to original display with new SV
364
Monitoring Operation and Modifying Data Section 7-1
7-1-14 Expansion Instruction Function Code Assignments
This operation is used to read or change the function codes assigned to expansion instructions. There are 18 function codes that can be assigned to expansion instructions: 17, 18, 19, 47, 48, 60 to 69, and 87 to 89. More than one function code can be assigned to an expansion instruction.
Note Function Code Assignments can be read in any mode, but can be changed in
PROGRAM mode only.
Key Sequence
Example 00000
INST TBL READ
FUN17:ASFT
INST TBL READ
FUN18:SRCH
INST TBL READ
FUN17:ASFT
INST TBL READ
FUN18:SRCH
INST TBL CHG?
FUN18:SRCH → ????
INST TBL CHG?
FUN18:SRCH → MCMP
INST TBL CHG?
FUN18:SRCH → PID
INST TBL READ
FUN18:PID
D0002
0123
Press CLR to bring up the initial display.
Press EXT to begin displaying function code assignments.
Press the Up and Down Arrow keys to scroll through the function code assignments.
The Up Arrow key displays function codes in ascending order:
17, 18, ... , 89, 17, 18, ...
The Down Arrow key displays function codes in descending order:
17, 89, 88, ... 17, 89, ...
Press CHG to change the displayed function code assignment.
Press the Up and Down Arrow keys to scroll through the instructions.
Press WRITE to enter the change into memory.
Press CLR to return to the initial display.
365
Monitoring Operation and Modifying Data Section 7-1
7-1-15 UM Area Allocation
This operation is used to allocate part of the UM Area for use as expansion DM. It can be performed in PROGRAM mode only. Memory allocated to expansion DM is deducted from the ladder program area.
The amount of memory available for the ladder program depends on the amount of RAM in the CPU. About 15.2 KW of memory is available with the16-KW RAM and about 31.2 KW is available with the 32-KW RAM.
This operation cannot be used to allocate UM to the I/O comment area. UM can be allocated to the I/O comment area only with a host computer equipped with
LSS (V6 or higher).
Key Sequence
Clear memory when changing allocation
FUN VER CHG [New data]
PLAY
SET
9 7
B
1
D
3
WRITE CLR
Example
00000
VER
DM CM LAD
00 00 15.2
UMAREA CHG?
INI DM SIZ:00KW
UMAREA CHG?
INI DM SIZ:02KW
UMAREA SET: CHG
????
UMAREA SET: CHG
9713
DM CM LAD
02 00 13.2
00000
Clear memory completely if the UM Area allocation will be changed.
The current UM Area allocation will be displayed.
“??” will be displayed if the allocation information has been lost.
Press CHG to change the UM Area allocation.
Expansion DM can be set to 00, 01, 02, or 03 KW.
Enter the password by pressing PLAY/SET and
9713.
The new UM Area allocation will be displayed. UM allocated to expansion DM is deducted from the ladder program.
Press CLR to return to the initial display.
366
Monitoring Operation and Modifying Data Section 7-1
7-1-16 Reading and Setting the Clock
This operation is used to read or set the CPU’s clock. The clock can be read in any mode, but it can be set in MONITOR or PROGRAM mode only.
The CPU will reject entries outside of the acceptable range, i.e., 01 to 12 for the month, 01 to 31 for the day of the month, 00 to 06 for the day of the week, or 00 to
60 for the seconds, but it will not recognize non-existent dates, such as 2/31.
Example
FUN
00000
TIM 93- 01- 06
14:25:57 FRI(5)
TIM CHG?93-01-06
14:25:58 FRI(5)
TIM CHG?93-01-06
14:25:59 FRI(5)
TIM CHG?93-01-06
14:26:00 FRI(5)
TIM CHG?93-01-06
14:26:01 FRI(5)
00000
Press CLR to bring up the initial display.
The display will monitor the current date and time.
Press CHG to change the date and/or time. The “9” in “93” will blink, indicating that it can be changed.
Press the Up and Down Arrow keys to move the cursor through the data and time settings. Input new values to change settings if necessary.
In this case, a “0” was input to replace the “8”.
Press CLR to return to the initial display.
7-1-17 Expansion Keyboard Mapping
This operation is used to control the ON/OFF status of bits SR 27700 through
SR 27909 by pressing keys on the Programming Console’s keyboard. The
C200HS also supports the C200H’s Keyboard Mapping operation, which controls the status of bits in AR 22. These operations can be performed in any PC mode, but the Programming Console must be in TERMINAL or expansion TER-
MINAL mode.
To enable expansion keyboard mapping, pin 6 of the CPU’s DIP switch and
AR 0709 must be ON and AR 0708 must be OFF.
Bits turned ON with this operation can be turned OFF by toggling AR 0708. Turn
AR 0709 OFF to stop expansion keyboard mapping and switch the Programming Console from Expansion TERMINAL mode to CONSOLE mode.
TERMINAL Mode The Programming Console can be put into TERMINAL mode by pressing CHG or executing TERM(48) in the program. Pin 6 of the CPU’s DIP switch must be
OFF.
PROGRAM BZ
CONSOLE mode
<MESSAGE>
NO MESSAGE
PROGRAM BZ
Switch the Programming Console to TERMINAL mode by pressing CHG or executing TERM(48).
Press CHG again to return to CONSOLE mode.
367
Monitoring Operation and Modifying Data Section 7-1
Expansion TERMINAL Mode The Programming Console can be put into Expansion TERMINAL mode by turning ON AR 0709. Pin 6 of the CPU’s DIP switch must be ON.
PROGRAM BZ
CONSOLE mode
<MESSAGE>
NO MESSAGE
PROGRAM BZ
Switch the Programming Console to Expansion
TERMINAL mode by turning AR 0709 ON.
Turn AR 0709 OFF to return to CONSOLE mode.
7-1-18 Keyboard Mapping
The C200HS supports the expansion keyboard mapping as well as normal keyboard mapping. Expansion keyboard mapping controls the status of the 41 bits
SR 27700 through SR 27909, while normal keyboard mapping controls only the
16 bits in AR 22. The status of these bits can be controlled by pressing the corresponding Programming Console keys when the Programming Console is in
TERMINAL mode or expansion TERMINAL mode.
The following diagram shows how to switch the Programming Console between
CONSOLE mode (normal operating mode) and TERMINAL or expansion TER-
MINAL mode.
Press the CHG Key or execute TERM(48).
Turn ON AR 0709.
TERMINAL mode
(DIP switch pin 6 OFF)
Press the CHG key.
CONSOLE mode
Turn OFF AR 0709 or turn OFF DIF switch pin 6.
Expansion TERMINAL mode
(DIP switch pin 6 ON)
TERMINAL Mode The Programming Console can be put into TERMINAL mode by pressing CHG or executing TERM(48) in the program. Pin 6 of the CPU’s DIP switch must be
OFF.
Press the CHG key again to return to CONSOLE mode.
When the Programming Console is in TERMINAL mode it can perform normal keyboard mapping and display messages output by MSG(46) or LMSG(47).
With keyboard mapping, bits 00 to 15 of AR 22 will be turned ON when keys 0 to
F are pressed on the Programming Console’s keyboard. A bit will remain ON after the Programming Console’s key is released.
All bits in AR 22 will be turned OFF when AR 0708 is turned ON. Keyboard mapping inputs are disabled when AR 0708 is ON.
In addition to the keyboard mapping function, TERMINAL mode allows messages output by MSG(46) and LMSG(47) to be displayed on the Programming
Console. These messages will be erased if the Programming Console is switch back to CONSOLE mode.
Expansion TERMINAL Mode The Programming Console can be put into Expansion TERMINAL mode by turning ON AR 0709. Pin 6 of the CPU’s DIP switch must be ON.
Turn off AR 0709 or pin 6 of the CPU’s DIP switch to return to CONSOLE mode.
When the Programming Console is in TERMINAL mode it can perform expansion keyboard mapping and display messages output by MSG(46) or
LMSG(47). With expansion keyboard mapping, bits SR 27700 through
SR 27909 will be turned ON when the corresponding key is pressed on the Programming Console’s keyboard. A bit will remain ON after the Programming Console’s key is released.
368
Monitoring Operation and Modifying Data Section 7-1
All bits from SR 27700 through SR 27909 will be turned OFF when AR 0708 is turned ON. Expansion keyboard mapping inputs are disabled when AR 0708 is
ON.
In addition to the keyboard mapping function, expansion TERMINAL mode allows messages output by MSG(46) and LMSG(47) to be displayed on the Programming Console. These messages will be erased if the Programming Console is switch back to CONSOLE mode.
The following diagram shows the correspondence between the position of Programming Console keys and bits in the SR Area. Each key corresponds 1 to 1 with a bit. Shifted inputs are not recognized. Keys 0 to 15 correspond to bits
SR 27700 to SR 27715, keys 16 to 31 correspond to bits SR 27800 to SR 27815, and keys 32 to 41 correspond to bits SR 27900 to SR 27909.
FUN key 0
6
1
7
2
8
3
9
4 5
10 11
12 13 14 15 16 17
18 19 20 21 22 23
24 25 26 27 28 29
30 31 32 33 34 35
36 37 38 39 40 41
The following table shows the correspondence between the actual Programming Console keys and bits SR 27700 to SR 27909.
277
SR word
00
Bit Corresponding key(s)
FUN
01
06
07
08
09
10
02
03
04
05
11
*1
*2
369
Monitoring Operation and Modifying Data
277
SR word
12
Bit
13
278
279
10
11
08
09
12
13
14
01
02
15
00
03
04
01
02
14
15
00
05
06
07
370
Section 7-1
Corresponding key(s)
Monitoring Operation and Modifying Data
279
SR word
03
04
Bit
05
06
07
08
09
Section 7-1
Corresponding key(s)
*3
VER
371
SECTION 8
Communications
This section provides an overview of the communications features provided by the C200HS.
8-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Parameters for Host Link and RS-232C Communications . . . . . . . . . . . . . . . . . . . . . . . . .
8-2-1 Standard Communications Parameters
8-2-2 Specific Communications Parameters
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2-3 Wiring Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2-4 Host Link Communications
8-2-5 RS-232C Communications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2-6 One-to-one Link Communications
8-2-7 NT Links
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
374
374
375
376
377
377
379
382
384
373
Parameters for Host Link and RS-232C Communications
Section 8-2
8-1 Introduction
The C200HS supports the following types of communications.
•
Communications with Programming Devices (e.g., Programming Console,
LSS, or SSS.)
•
Host Link communications with personal computers and other external devices.
•
RS-232C (no-protocol) communications with personal computers and other external devices.
•
One-to-one link communications with another C200HS CPU or a CQM1 CPU.
• NT link communications with Programmable Terminals (PTs) equipped with an
NT link interface.
This section describes the connection methods and application of all of these different types of communications except for communications with Programming Devices, which is described elsewhere in this manual.
Note 1. One-to-one link communications are possible only with CPUs that have an
RS-232C port. They are not possible with the C200HS-CPU01-E/03-E
2. Refer to documentation on the NT-series Interface Units for details on NT link communications.
3. One-to-one link communications and NT link communications are not possible through the peripheral port.
8-2 Parameters for Host Link and RS-232C Communications
The parameters in the PC Setup described in this section are used both by Host
Link communications and RS-232C (no-protocol) communications. These parameters must be set in advance to enable communications.
Note 1. PC Setup parameters in DM 6645 to DM 6654 can be set under the PC Setup item on the Utility Menu.
2. The parameters set in the PC Setup will be ignored and the following communications settings will be used if pin 5 on the C200HS CPU’s DIP switch is turned ON.
Item
Communications mode Host Link
Setting
Unit no.
Start bits
00
1
Data length
Stop bits
Parity
Baud rate
Transmission delay
7
2
Even
9,600 bps
None
Note The above settings apply to CPUs manufactured from July 1995 (lot number
**75 for July 1995). For CPUs manufactured before July 1995 (lot number **65 for June 1995), only 1 stop bit will be set and the baud rate will be 2,400 bps.
374
Parameters for Host Link and RS-232C Communications
Section 8-2
8-2-1 Standard Communications Parameters
The settings in DM 6645 and DM 6650 determine the main communications parameters, as shown in the following diagram.
The settings in bits 00 through 07 and bits 12 through 15 are valid only when pin
5 on the CPU’s DIP switch is OFF. Bits 08 though 11 are valid only in a PC set as the master for a 1:1 link.
Bit 15 0
DM 6645: RS-232C port
DM 6650: Peripheral port
Communications mode
0: Host link
1: RS-232C
2: One-to-one link slave
3: One-to-one link master
4: NT link
Link words for one-to-one link
0: LR 00 to LR 63
1: LR 00 to LR 31
2: LR 00 to LR 16
Port settings
00: Standard communication parameters
01: According to setting in DM 6646 and DM 6651 (
(defaults: standard communications parameter and
Host Link mode)
The standard communications parameters are as shown in the following table.
Item
Start bits
Data length
Stop bits
Parity
Baud rate
Setting
1
7
2
Even
9,600 bps
Be sure to set the proper communications mode.
If the above parameters are acceptable, set the rightmost two digits (port settings) to 00. To change the parameters, use the setting described next.
375
Parameters for Host Link and RS-232C Communications
Section 8-2
8-2-2 Specific Communications Parameters
The following settings are valid only when pin 5 on the CPU’s DIP switch is turned OFF and DM 6645 and DM 6655 are set to specify using the settings in words DM 6646 and DM 6656.
Be sure to set the communications parameters to the same settings for both ends of the communications.
Bit 15
DM 6646: RS-232C port
DM 6651: Peripheral port
Transmission Frame Format (See table below.)
Baud rate (See table below.)
0
Transmission Frame
Format
Baud Rate
00
01
02
03
04
05
06
07
08
00
01
02
03
04
09
10
11
Setting
1
1
1
1
1
1
1
1
1
1
1
1
Stop bits
8
8
7
8
7
7
7
7
7
8
8
8
Data length
1
1
2
1
1
2
1
1
2
2
2
2
Stop bits
None
Even
Odd
None
Even
Odd
None
Even
Odd
Parity
None
Even
Odd
Setting Baud rate
1,200 bps
2,400 bps
4,800 bps
9,600 bps
19,200 bps
Transmission Delay Time Depending on the devices connected to the RS-232C port, it may be necessary to allow time for transmission. When that is the case, set the transmission delay to regulate the amount of time allowed.
Bit 15
DM 6647: RS-232C port
DM 6652: Peripheral port
Transmission delay (4 digits BCD; unit: 10 ms)
Set to 0000 to 9999 (i.e., 0 to 99.9 s)
Default: No delay
0
376
Parameters for Host Link and RS-232C Communications
Section 8-2
8-2-3 Wiring Ports
Use the wiring diagram shown below as a guide in wiring the port to the external device. Refer to documentation provided with the computer or other external device for wire details for it.
The connections between the C200HS and a personal computer are illustrated below as an example.
FG
SD
RD
RS
CS
–
–
–
SG
C200HS
Signal
4
5
2
3
Pin
No.
1
8
9
6
7
Personal computer
Pin
No.
1
6
7
8
4
5
2
3
Signal
–
RD
SD
DTR
SG
DSR
RS
CS
–
Shielded cable
Applicable Connectors
The following connectors are applicable. One plug and one hood are included with the CPU.
Plug: XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0901 (OMRON) or equivalent
Note Ground the FG terminal on the C200HS and at the computer to 100
Ω
or less.
Refer to the C200HS Installation Manual and to the documentation for your computer for details.
8-2-4 Host Link Communications
This section describes the PC Setup parameters and communications procedure for the Host Link communications mode.
Host link communications were developed by OMRON to connect PCs and one or more host computers by RS-232C cable, and to control PCs through communications from the host computer. Normally the host computer issues a command to a PC, and the PC automatically sends back a response. Thus the communications are carried out without the PCs being actively involved. The PCs also have the ability to initiate data transmissions when direct involvement is necessary.
In general, there are two means for implementing host link communications.
One is based on C-mode commands, and the other on FINS (CV-mode) commands. The C200HS supports C-mode commands only. For details on host link communications, refer to Section 11 Host Link Commands.
The C200HS supports Host Link communications either through the peripheral or RS-232C port, or though Host Link Units (#0 and #1) mounted to the PC. The
Host Link Units include the C200H-LD201-V1, C200H-LD202-V1, and C200H-
LK101-PV1.
Note The leftmost two digits of DM 6645 and/or DM 6650 must be set to 00 to enable the Host Link Mode. Also, set the rightmost two digits of DM 6645 and DM 6655 and all digits of DM 6646 and DM 6656 to the required communications parameters before attempting to use Host Link communications.
377
Parameters for Host Link and RS-232C Communications
PC Setup
Section 8-2
The following parameter in the PC Setup is used only when the Host Link communications mode is being used.
Host Link Node Number
A node number must be set for host link communications to differentiate between nodes when multiple nodes are participating in communications.
Set the node number to 00 unless multiple nodes are connected in a network.
DM 6648: RS-232C port
DM 6653: Peripheral port
Bit 15
0 0
0
Node number
(2 digits BCD): 00 to 31
Default: 00
Communications Procedure This section explains how to use the host link to execute data transmissions from the C200HS. Using this method enables automatic data transmission from the
C200HS when data is changed, and thus simplifies the communications process by eliminating the need for constant monitoring by the computer.
1, 2, 3...
1. Check to see that SR 26405 (RS-232C Port Transmit Ready Flag) or
SR 26413 (Peripheral Port Transmit Ready Flag) is ON. If using Host Link
Units, check SR 26705 for Unit #0 and SR 26713 for Unit #1.
2. Use the TXD(––) instruction to transmit the data.
(@)TXD
S
C
N
S: Address of first word of transmission data
C: Control data
0000:
1000:
2000:
3000:
RS-232C port
Peripheral port
Host Link Unit #0
Host Link Unit #1
N: Number of bytes of data to be sent (4 digits BCD)
0000 to 0061
3. From the time this instruction is executed until the data transmission is complete, SR 26405, SR 26413, SR 26705, or SR 26713 will remain OFF. The bits for the RS-232C or peripheral port will turn ON again upon completion of the data transmission. The bits for the Host Link Units will turn ON again when the data transmission has been passed to the Host Link Unit.
4. The TXD(––) instruction does not provide for a response, so in order to receive confirmation that the computer has received the data, the computer’s program must be written so that it gives notification when data is written from the C200HS.
Note 1. The transmission data frame is as shown below for data transmitted in the
Host Link mode by means of the TXD(––) instruction.
@ x 10 1 x 10 0
E X
: ↵
Node
No.
Header code
(Must be “EX”)
Data (up to 122 characters) FCS Terminator
2. To reset the RS-232C port (i.e., to restore the initial status), turn ON
SR 25209. To reset the peripheral port, turn ON SR 25208. These bits will turn OFF automatically after the reset. Host Link Unit #0 is reset using
SR 25213 and Host Link Unit #1 is reset using SR 25207.
3. If the TXD(––) instruction is executed while the C200HS is in the middle of responding to a command from the computer, the response transmission will first be completed before the transmission is executed according to the
378
Parameters for Host Link and RS-232C Communications
Application Example
Section 8-2
TXD(––) instruction. In all other cases, data transmission based on a
TXD(––) instruction will be given first priority.
This example shows a program for using the RS-232C port in the Host Link mode to transmit 10 bytes of data (DM 0000 to DM 0004) to a computer. From
DM 0000 to DM 0004, “1234” is stored in every word.
The default values are assumed for all of the PC Setup (i.e., the RS-232C port is used in Host Link mode, the node number is 00, and the standard communications parameters are used.)
00100 SR 26405
@TXD
DM 0000
#0000
#0010
If SR 26405 (the Transmit Ready Flag) is ON when IR 00100 turns ON, the ten bytes of data (DM 0000 to DM 0004) will be transmitted.
The following type of program must be prepared in the host computer to receive the data. This program allows the computer to read and display the data received from the PC while a host link read command is being executed to read data from the PC.
10 ’C200HS SAMPLE PROGRAM FOR EXCEPTION
20 CLOSE 1
30 CLS
40 OPEN “COM:E73” AS #1
50
:
KEYIN
60 INPUT “DATA ––––––––”,S$
70 IF S$=” ” THEN GOTO 190
80 PRINT “SEND DATA = ”;S$
90 ST$=S$
100 INPUT “SEND OK? Y or N?=”,B$
110 IF B$=”Y” THEN GOTO 130 ELSE GOTO
:
KEYIN
120 S$=ST$
130 PRINT #1,S$
140 INPUT #1,R$
’ Sends command to PC
’ Receives response from PC
150 PRINT “RECV DATA = ”;R$
160 IF MID$(R$,4,2)=”EX” THEN GOTO 210 ’ Identifies command from PC
170 IF RIGHT$(R$,1)<>”
:
” THEN S$=” ”:GOTO 130
180 GOTO
:
KEYIN
190 CLOSE 1
200 END
210 PRINT “EXCEPTION!! DATA”
220 GOTO 140
The data received by the computer will be as shown below. The FCS is “59.”
“@00EX1234123412341234123459
:
CR”
8-2-5 RS-232C Communications
This section explains RS-232C communications. By using RS-232C communications, the data can be printed out by a printer or read by a bar code reader.
Handshaking is not supported for RS-232C communications.
Note The leftmost two digits of DM 6645 and/or DM 6650 must be set to 10 to enable the RS-232C communications. Also, set the rightmost two digits of DM 6645 and
DM 6655 and all digits of DM 6646 and DM 6656 to the required communications parameters before attempting to use Host Link communications.
379
Parameters for Host Link and RS-232C Communications
PC Setup
Section 8-2
Start and end codes or the amount of data to be received can be set as shown in the following diagrams if required for RS-232C communications. This setting is required only for RS-232C communications.
The following settings are valid only with pin 5 on the CPU’s DIP switch is turned
OFF.
Enabling Start and End Codes
DM 6648: RS-232C port
DM 6653: Peripheral port
Bit 15
0 0
0
End code usage
0: Not set (Amount of reception data specified.)
1: Set (End code specified.)
2: CR/LF
Start code usage
0: Not set
1: Set (Start code specified.)
Defaults: No start code; data reception complete at 256 bytes.
Specify whether or not a start code is to be set at the beginning of the data, and whether or not an end code is to be set at the end. Instead of setting the end code, it is possible to specify the number of bytes to be received before the reception operation is completed. Both the codes and the number of bytes of data to be received are set in DM 6649 or DM 6654.
Setting the Start Code, End Code, and Amount of Reception Data
Bit 15 0
DM 6649: RS-232C port
DM 6654: Peripheral port
End code or number of bytes to be received
For end code: (00 to FF)
For amount of reception data: 2 digits hexadecimal, 00 to FF (00: 256 bytes)
Start code 00 to FF
Defaults: No start code; data reception complete at 256 bytes.
Communications Procedure
Transmissions
1, 2, 3...
1. Check to see that SR 26413 (Peripheral Port Transmit Ready Flag) or
SR 26405 (RS-232C Port Transmit Ready Flag) is ON.
2. Use the TXD(––) instruction to transmit the data.
(@)TXD
S
C
N
S: Address of first word of data to be transmitted
C: Control data
Bits 00 to 03
0: Leftmost bytes first
1: Rightmost bytes first
Bits 12 to 15
0: RS-232C port
1: Peripheral port
N: Number of bytes to be transmitted (4 digits BCD),
0000 to 0256
3. From the time this instruction is executed until the data transmission is complete, SR 26405 (or SR 25413 for the peripheral port) will remain OFF. It will turn ON again upon completion of the data transmission.
380
Parameters for Host Link and RS-232C Communications
Section 8-2
Start and end codes are not included when the number of bytes to be transmitted is specified. The largest transmission that can be sent with or without start and end codes in 256 bytes, i.e., N will be between 254 and 256 depending on the designations for start and end codes. If the number of bytes to be sent is set to
0000, only the start and end codes will be sent.
256 bytes max.
Start code Data End code
To reset the RS-232C port (i.e., to restore the initial status), turn on SR 25209. To reset the peripheral port, turn on SR 25208. These bits will turn OFF automatically after the reset.
Receptions
1, 2, 3...
1. Check to see that SR 26414 (Peripheral Port Reception Ready Flag) or
SR 26406 (RS-232C Port Reception Ready Flag) is ON.
2. Use the RXD(––) instruction to receive the data.
(@)RXD
D
C
N
D: Leading word no. for storing reception data
C: Control data
Bits 00 to 03
0: Leftmost bytes first
1: Rightmost bytes first
Bits 12 to 15
0: RS-232C port
1: Peripheral port
N: Number of bytes stored (4 digits BCD), 0000 to 0256
(including start and end bits)
3. The status resulting from reading the data received will be stored in the SR
Area. Check to see that the operation was successfully completed. The contents of these bits will be reset each time RXD(––) is executed.
RS-232C
SR 26400 to
SR 26403
SR 26404
SR 26407
SR 265
Peripheral
SR 26408 to
SR 2641
SR 26412
SR 26415
SR 266
Error
Communications port error code (1 digit BCD)
0: Normal completion
1: Parity error
2: Framing error
3: Overrun error
Communications error
Reception Overrun Flag (After reception was completed, the subsequent data was received before the data was read by means of the RXD instruction.)
Number of bytes received (not including start and end bits)
Note The contents of SR 265 and SR 266 may not be zero when power is turned on or when the communications cable is attached. Execute a dummy RXD(––) or reset the communications port to reset these words to zero.
To reset the RS-232C port (i.e., to restore the initial status), turn ON SR 25209.
To reset the peripheral port, turn ON SR 25208. These bits will turn OFF automatically after the reset.
Note Always program the Transmit Ready Flag in a NO condition on the instruction line to TXD(––) to ensure that this Flag is ON before the transmission can be executed.
381
Parameters for Host Link and RS-232C Communications
Section 8-2
Application Example This example shows a program for using the RS-232C port in the RS-232C mode to transmit 10 bytes of data (DM 0100 to DM 0104) to the computer, and to store the data received from the computer in the DM area beginning with
DM 0200. Before executing the program, the following PC Setup setting must be made.
DM 6645: 1000 (RS-232C port in RS-232C mode; standard communications conditions)
DM 6648: 2000 (No start code; end code CR/LF)
The default values are assumed for all other PC Setup settings. From DM 0100 to DM 0104, 3132 is stored in every word. From the computer, execute a program to receive C200HS data with the standard communications conditions.
00100
DIFU(13) 00101
00101 SR 26405
@TXD
DM 0100
#0000
#0010
If SR 26405 (the Transmit Ready Flag) is ON when IR 00100 turns ON, the ten bytes of data
(DM 0100 to DM 0104) will be transmitted, leftmost bytes first.
SR 26406
@RXD
DM 0200
#0000
265
When SR 26406 (Reception Completed Flag) goes ON, the number of bytes of data specified in
SR 265 will be read from the C200HS’s reception buffer and stored in memory starting at DM 0200, leftmost bytes first.
8-2-6 One-to-one Link Communications
If two C200HSs or one C200HS and one CQM1 are linked one-to-one by connecting them together through their RS-232C ports, they can share common LR areas. When two PCs are linked one-to-one, one of them will serve as the master and the other as the slave.
Note The peripheral port cannot be used for 1:1 links.
One-to-one Links
The data will be as follows:
“31323132313231323132CR LF”
A one-to-one link allows two C200HSs (or a CQM1) to share common data in their LR areas. As shown in the diagram below, when data is written into a word the LR area of one of the linked Units, it will automatically be written identically into the same word of the other Unit. Each PC has specified words to which it can write and specified words that are written to by the other PC. Each can read, but cannot write, the words written by the other PC.
Master Slave
Master area Write “1” 1 Master area
Written automatically.
Slave area 1 1 Write Slave area
Wiring
The word used by each PC will be as shown in the following table, according to the settings for the master, slave, and link words.
DM 6645 setting
Master words
Slave words
LR 00 to LR 63
LR00 to LR31
LR32 to LR63
LR 00 to LR 31
LR00 to LR15
LR16 to LR31
LR 00 to LR 15
LR00 to LR07
LR08 to LR15
Wire the cable as shown in the diagram below using the connector listed.
Applicable Connectors
The following connectors are applicable. One plug and one hood are included with the CPU.
382
Parameters for Host Link and RS-232C Communications
Plug: XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0901 (OMRON) or equivalent
FG
SD
RD
RS
CS
–
Signal
Abb.
C200HS
Pin
No.
–
–
SG
4
5
6
1
2
3
7
8
9
Section 8-2
4
5
6
7
8
1
2
3
Pin
No.
C200HS
Signal
Abb.
–
–
SG
FG
SD
RD
RS
CS
–
PC Setup
Note Ground the FG terminals the C200HS to a resistance of 100 Ω or less.
To use a 1:1 link, the only settings necessary are the communications mode and the link words. Set the communications mode for one of the PCs to the 1:1 master and the other to the 1:1 slave, and then set the link words in the PC designated as the master. Bits 08 to 11 are valid only for the master for link one-to-one.
Bit 15 0
DM 6645: RS-232C port
Communications mode
2: One-to-one link slave
3: One-to-one link master
Link words for one-to-one link
0: LR 00 to LR 63
1: LR 00 to LR 31
2: LR 00 to LR 16
Port settings
00: Standard communication parameters
Communications Procedure If the settings for the master and the slave are made correctly, then the one-toone link will be automatically started up simply by turning on the power supply to both the C200HSs and operation will be independent of the C200HS operating modes.
Application Example This example shows a program for verifying the conditions for executing a oneto-one link using the RS-232C ports. Before executing the program, set the following PC Setup parameters.
Master: DM 6645: 3200 (one-to-one link master; Area used: LR 00 to LR 15)
Slave: DM 6645: 2000 (one-to-one link slave)
The defaults are assumed for all other PC Setup parameters. The words used for the one-to-one link are as shown below.
LR00
LR07
LR08
LR15
Master
Area for writing
Area for reading
Slave
Area for reading
Area for writing
LR00
LR07
LR08
LR15
383
Parameters for Host Link and RS-232C Communications
Section 8-2
When the program is executed at both the master and the slave, the status of
IR 001 of each Unit will be reflected in IR 100 of the other Unit. IR 001 is an input word and IR 100 is an output word.
In the Master
25313 (Always ON)
MOV(21)
001
LR00
MOV(21)
LR08
100
In the Slave
25313 (Always ON)
MOV(21)
001
LR08
MOV(21)
LR00
100
8-2-7 NT Links
NT Links
PC Setup
Application
NT links can be established by connecting the RS-232C port of the C200HS to the NT Link Interface Unit of a Programmable Terminal.
Note The peripheral port cannot be used for NT links.
NT link allow high-speed communications with a Programmable Terminal through direct access of PC memory.
Only the following setting is necessary.
DM 6645: RS-232C port
Bit 15
4 0 0 0
0
Communications mode
4: NT link
Refer to documentation provided for the NT Link Interface Unit for details on actual application of an NT link.
384
SECTION 9
Memory Cassette Operations
This section describes how to manage both UM Area and IOM data via Memory Cassettes. mounted in the CPU.
9-1 Memory Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2 Memory Cassette Settings and Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 UM Area Data
9-4 IOM Area Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
386
386
387
388
385
Memory Cassette Settings and Flags Section 9-2
9-1 Memory Cassettes
The C200HS comes equipped with a built-in RAM for the user’s program so programs can be created even without installing a Memory Cassette. An optional
Memory Cassette, however, can provide flexibility in handling program data, PC
Setup data, DM data, I/O comment data, and other IOM Area data. Memory Cassettes can be used for the following purposes.
•
Saving, retrieving, and comparing data in the UM Area. This UM Area data can include the user program, fixed DM data such as the PC Setup, expansion DM data, I/O comment data, I/O table data, and UM Area allocation data.
• Automatically loading Memory Cassette data on PC startup.
•
Saving and retrieving IOM Area data. IOM data includes IR 000 to IR 231, the two work areas, the two SR Areas, the LR Area, the HR Area, the AR Area, the
TC Area, and DM 0000 to DM 6143.
There are two types of Memory Cassette available, each with a capacity of 16K words. For instructions on installing Memory Cassettes, refer to the C200HS
Installation Guide.
The following table shows the Memory Cassettes used with C200HS PCs.
Memory Capacity Model number Features
EEPROM 16K words C200HS-ME16K Can be written to while mounted in the C200HS.
Can be used for both UM Area data and IOM Area data.
A memory backup battery is not required.
EPROM 16K words C200HS-MP16K Can be written with a commercially available PROM writer.
Can be used for only UM Area data.
Note 1. Memory Cassettes for the C200HS cannot be used with the C200H, and
Memory Units for the C200H cannot be used with the C200HS.
2. EEPROM can be written up to 50,000 times. Data may be corrupted if this limit is exceeded.
3. EPROM chips are sold separately.
!
Caution The C200HS will not operate properly unless the data for it is created on LSS version 3 or later. The
C200HS is not supported by earlier versions of the LSS.
!
Caution Do not mount or remove a Memory Cassette without turning off the power supply to the C200HS
CPU.
9-2 Memory Cassette Settings and Flags
The following settings and flags are available for Memory Cassettes in the SR
Area. Bits/words used in the procedures to manipulate Memory Cassettes are described in the remainder of this section. Refer to page 46 for other details on
SR Area operation.
Word
SR 269
Bit(s)
00 to 07
08 to 10
11 to 13
14
15
Function
Memory Cassette Contents 00: Nothing; 01: UM; 02: IOM (03: HIS)
Memory Cassette Capacity 0: 0 KW (no board); 3: 16 KW
Reserved by system (not accessible by user)
EEPROM Memory Cassette Protected or EPROM Memory Cassette Mounted Flag
Memory Cassette Flag
386
UM Area Data
Word
SR 270
SR 271
SR 272
SR273
Section 9-3
00
Bit(s)
01
02
03
04 to 11
12
13
14
15
00 to 07
13
14
15
00
08 to 15
00 to 10
11
12
01
02 to 11
12
13
14
Save UM to Cassette Bit
Function
Data transferred to Memory Cassette when Bit is turned
Load UM from Cassette Bit An error will be produced if turned ON in any other mode.
Collation Execution Flag
Collation NG Flag
Reserved by system (not accessible by user)
Data will not be transferred from UM to the Memory Transfer Error Flag: Not
PROGRAM mode
Transfer Error Flag: Read Only
Transfer Error Flag: Insufficient
Capacity or No UM
Transfer Error Flag: Board
Checksum Error
E ) D t il d i f ti h k
SR 272 because the information is not needed. Repeat
Ladder program size stored in Memory Cassette
Ladder-only File: 04: 4 KW; 08: 8 KW; 12: 12 KW; ... (64: 64 KW)
00: No Ladder program or no file
Data updated at data transfer from CPU at startup. The file must begin in segment 0.
Ladder program size and type in CPU (Specifications are the same as for bits 00 to 07.)
Reserved by system (not accessible by user)
Memory Error Flag: PC Setup Checksum Error
Memory Error Flag: Ladder Checksum Error
Memory Error Flag: Instruction Change Vector Area Checksum Error
Memory Error Flag: Memory Cassette Online Disconnection
Memory Error Flag: Autoboot Error
Save IOM to Cassette Bit Data transferred to Memory Cassette when Bit is turned
Load IOM from Cassette Bit An error will be produced if turned ON in any other mode.
Reserved by system (not accessible by user)
Transfer Error Flag: Not
PROGRAM mode
Data will not be transferred from IOM to the Memory
Transfer Error Flag: Read Only
Transfer Error Flag: Insufficient
Capacity or No IOM
9-3 UM Area Data
The following procedures can be used to read UM Area data from, write UM Area data to, and compare UM Area data on an EEPROM Memory Cassette mounted to a C200HS CPU. This UM Area data can include the user program, fixed DM data such as the PC Setup, expansion DM data, I/O comment data, I/O table data, and UM Area allocation data. The procedures cannot be used to write to
EPROM Memory Cassettes, which require a PROM writer. Refer to the LSS operation manuals for PROM writer procedures.
Note The data inside the Memory Cassette should be protected by turning on the write-protect switch whenever you are not planning to write to the Cassette.
Writing Data The following procedure is used to write UM Area data from the C200HS CPU to a Memory Cassette mounted in the CPU.
1, 2, 3...
1. Turn off the write-protect switch on the Memory Cassette to write-enable it.
2. Make sure that power to the C200HS CPU is turned OFF.
3. Mount the Memory Cassette to the CPU.
387
IOM Area Data Section 9-4
Reading Data
Comparing Data
4. Turn on the CPU.
5. If the desired program or UM Area data is not already in the CPU, write the data or transfer it to the CPU.
6. Switch the C200HS to PROGRAM mode.
7. Turn ON SR 27000 from the LSS or a Programming Console. The UM Area data will be written to the Memory Card and SR 27000 will be turned OFF automatically.
The following procedures are used to read UM Area data from a Memory Cassette mounted in the C200HS CPU to the CPU. This can be achieved either automatically when the C200HS is turned on or manually from a Programming Device.
Automatic Reading at Startup
1, 2, 3...
1. Turn ON pin 2 on the CPU’s DIP switch to enable reading at startup.
2. Make sure that power to the C200HS CPU is turned OFF.
3. Mount the Memory Cassette containing the data to be read to the CPU.
4. Turn on the CPU. The data in the Memory Cassette will be read to the CPU.
Manual Reading
1, 2, 3...
1. Make sure that power to the C200HS CPU is turned OFF.
2. Mount the Memory Cassette containing the data to be read to the CPU.
3. Turn on the CPU.
4. Switch the C200HS to PROGRAM mode.
5. Turn ON SR 27001 from the LSS or a Programming Console. The data in the
Memory Cassette will be read to the CPU and SR 27001 will be turned OFF automatically.
The following procedure is used to compare the UM Area data in a Memory Cassette to the UM Area data in the CPU.
1, 2, 3...
1. Make sure that power to the C200HS CPU is turned OFF.
2. Mount the Memory Cassette containing the data to be compared.
3. Turn on the CPU.
4. Switch the C200HS to PROGRAM mode.
5. Turn ON SR 27002 from the LSS or a Programming Console. The data in the
Memory Cassette will be compared to the data in CPU and SR 27002 will be turned OFF automatically.
6. Read the status of SR 27003 to determine the results of the comparison. If
SR 27003 is OFF, the data in the Memory Cassette is the same as that in the
CPU. If SR 27003 is ON, either the data is different or the C200HS was not in
PROGRAM mode when the operation was performed.
Note 1. SR 27003 is used only to show the results of comparisons and cannot be manipulated by the user.
2. If the comparison operation is executed in any but PROGRAM mode, SR
27002 will turn ON, as will SR 27003. In this case, the status of SR 27003 will be meaningless.
3. SR 273003 will turn ON if the comparison operation is used without a
Memory Cassette mounted to the CPU.
9-4 IOM Area Data
The following procedures can be used to read IOM data from and write IOM data to an EEPROM Memory Cassette mounted to a C200HS CPU. IOM data includes IR 000 to IR 231, the two work areas, the two SR Areas, the LR Area, the
HR Area, the AR Area, the TC Area, and DM 0000 to DM 6143. This procedure cannot be used to write to EPROM Memory Cassettes, which require a PROM writer. Refer to the LSS operation manuals for PROM writer procedures.
388
IOM Area Data
Writing Data
Reading Data
Section 9-4
Note The data inside the Memory Cassette should be protected by turning on the write-protect switch whenever you are not planning to write to the Cassette.
The following procedure is used to write IOM data from the C200HS CPU to a
Memory Cassette mounted in the CPU.
1, 2, 3...
1. Turn off the write-protect switch on the Memory Cassette to write-enable it.
2. Make sure that power to the C200HS CPU is turned OFF.
3. Mount the Memory Cassette to the CPU.
4. Turn on the CPU.
5. Switch the C200HS to PROGRAM mode.
6. Turn ON SR 27300 from the LSS or a Programming Console. The IOM data will be written to the Memory Card and SR 27300 will be turned OFF automatically.
The following procedures are used to read IOM data from a Memory Cassette mounted in the C200HS CPU to the CPU. This data cannot be read out automatically at startup and must be read manually. Also, the error log in DM 6000 to DM
6030 cannot be read with this procedure.
1, 2, 3...
1. Make sure that power to the C200HS CPU is turned OFF.
2. Mount a Memory Cassette to the CPU.
3. Turn on the CPU.
4. Switch the C200HS to PROGRAM mode.
5. Turn ON SR 27301 from the LSS or a Programming Console. The IOM data in the Memory Cassette will be read to the CPU and SR 27301 will be turned
OFF automatically.
389
SECTION 10
Troubleshooting
The C200HS provides self-diagnostic functions to identify many types of abnormal system conditions. These functions minimize downtime and enable quick, smooth error correction.
This section provides information on hardware and software errors that occur during PC operation. Program input errors are described in 4-7 Inputting, Modifying, and Checking the Program. Although described in Section 3 Memory Areas, flags and other error information provided in SR and AR areas are listed in 10-5 Error Flags.
10-1 Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-2 Programmed Alarms and Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-3 Reading and Clearing Errors and Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-4 Error Messages
10-5 Error Flags
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-6 Host Link Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
392
392
392
392
397
399
391
Error Messages Section 10-4
10-1 Alarm Indicators
The ALM/ERR indicator on the front of the CPU provides visual indication of an abnormality in the PC. When the indicator is ON (ERROR), a fatal error (i.e., ones that will stop PC operation) has occurred; when the indicator is flashing
(ALARM), a nonfatal error has occurred. This indicator is shown in 2-1-1 CPU
Indicators.
!
Caution The PC will turn ON the ALM/ERR indicator, stop program execution, and turn OFF all outputs from the PC for most hardware errors, for certain fatal software errors, or when FALS(07) is executed in the program (see tables on following pages). PC operation will continue for all other errors. It is the user’s responsibility to take adequate measures to ensure that a hazardous situation will not result from automatic system shutdown for fatal errors and to ensure that proper actions are taken for errors for which the system is not automatically shut down. System flags and other system and/or user-programmed error indications can be used to program proper actions.
10-2 Programmed Alarms and Error Messages
FAL(06), FALS(07), and MSG(46) can be used in the program to provide user-programmed information on error conditions. With these three instructions, the user can tailor error diagnosis to aid in troubleshooting.
FAL(06) is used with a FAL number other than 00, which is output to the SR area when FAL(06) is executed. Executing FAL(06) will not stop PC operation or directly affect any outputs from the PC.
FALS(07) is also used with a FAL number, which is output to the same location in the SR area when FALS(07) is executed. Executing FALS(07) will stop PC operation and will cause all outputs from the PC to be turned OFF.
When FAL(06) is executed with a function number of 00, the current FAL number contained in the SR area is cleared and replaced by another, if more have been stored in memory by the system.
When MSG(46) is used a message containing specified data area words is displayed onto the Programming Console or another Programming Device.
The use of these instructions is described in detail in Section 5 Instruction Set.
10-3 Reading and Clearing Errors and Messages
System error messages can be displayed onto the Programming Console or other Programming Device.
On the Programming Console, press the CLR, FUN, and MONTR keys. If there are multiple error messages stored by the system, the MONTR key can be pressed again to access the next message. If the system is in PROGRAM mode, pressing the MONTR key will clear the error message, so be sure to write down all message errors as you read them. (It is not possible to clear an error or a message while in RUN or MONITOR mode; the PC must be in PROGRAM mode.)
When all messages have been cleared, “ERR CHK OK” will be displayed.
Details on accessing error messages from the Programming Console are provided in 7-1 Monitoring Operation and Modifying Data. Procedures for the LSS are provided in the LSS Operation Manual.
10-4 Error Messages
There are basically three types of errors for which messages are displayed: initialization errors, non-fatal operating errors, and fatal operating errors. Most of these are also indicated by FAL number being transferred to the FAL area of the
SR area.
392
Error Messages Section 10-4
The type of error can be quickly determined from the indicators on the CPU, as described below for the three types of errors. If the status of an indicator is not mentioned in the description, it makes no difference whether it is lit or not.
After eliminating the cause of an error, clear the error message from memory before resuming operation.
Asterisks in the error messages in the following tables indicate variable numeric data. An actual number would appear on the display.
Initialization Errors
Error and message
Waiting for Special I/O or Interrupt Input Units
CPU WAIT G
Waiting for Remote I/O
CPU WAIT G
The following error messages appear before program execution has been started. The POWER indicator will be lit and the RUN indicator will not be lit for either of these. The RUN output will be OFF for each of these errors.
FAL no.
None
None
Probable cause
A Special I/O Unit or
Interrupt Input Unit has not initialized.
Power to Remote I/O Unit is off or terminator cannot be found.
Possible correction
Perform the I/O Table Read operation to check unit numbers. Replace Unit if it is indicated by “$” only in the I/O table.
(High-density I/O Units will not appear on I/O Table
Read display for all peripheral devices.)
Check power supply to
Remote I/O Units, connections between
Remote I/O Units, and terminator setting.
Non-fatal Operating Errors The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will continue after one or more of these errors have occurred. For each of these errors, the
POWER and RUN indicators will be lit and the ALM/ERR indicator will be flashing. The RUN output will be ON.
Error and message
FAL error
SYS FAIL FAL**
FAL no.
01 to 99
Probable cause
FAL(06) has been executed in program. Check the FAL number to determine conditions that would cause execution (set by user).
Possible correction
Correct according to cause indicated by FAL number
(set by user).
Interrupt Input Unit error
SYS FAIL FAL8A
Interrupt subroutine error
SYS FAIL FAL8B
8A
8B
An error occurred in data transfer between the
Interrupt Input Unit and the
CPU.
Replace the Interrupt Input
Unit.
Interrupt subroutine containing Special I/O Unit refresh was too long.
Cyclic Special I/O Unit refreshing was not disabled for interrupt subroutine refresh.
Check the interrupt subroutine and PC Setup.
393
Error Messages
Error and message
High-density I/O Unit error
SYS FAIL FAL9A
PC Setup error
SYS FAIL FAL9B
Memory Cassette Transfer error
SYS FAIL FAL9D
Cycle time overrun
CYCLE TIME OVER
I/O table verification error
I/O VER ERR
Remote I/O error
REMOTE ERR
Remote I/O
Master Unit number
*
Special I/O Unit error
SIOU ERR
Group-2 High-density I/O error
SYS FAIL FAL 9A
Battery error
BATT LOW
FAL no.
9A
Probable cause
An error occurred in data transfer between a
High-density I/O Unit and the CPU.
Section 10-4
Possible correction
Check AR 0205 to AR 0214 to identify the Unit with a problem, replace the Unit, and restart the PC.
9B
9D
F8
An error has been detected in the PC Setup. This error will be generated when the setting is read or used for the first time.
Check an correct PC Setup settings.
An error has occurred during data transmission between UM and a Memory
Cassette because:
Not in PROGRAM Mode.
UM or Memory Cassette is read-only.
Insufficient capacity in UM or Memory Cassette.
A checksum error occurred in the Memory Cassette
Watchdog timer has exceeded 100 ms.
Make sure that the PC is in
PROGRAM mode.
Make sure that the Memory
Cassette is not write-protected.
Make sure that the UM and
Memory Cassette capacity is sufficient.
Make sure that SYSMAC
NET data links are not active during the transfer.
Transfer the data again.
Program cycle time is longer than recommended.
Reduce cycle time if possible.
E7
B0 or B1
D0
9A
F7
Unit has been removed or replaced by a different kind of Unit, making I/O table incorrect.
Error occurred in transmissions between
Remote I/O Units.
Use I/O Table Verify
Operation to check I/O table and either connect dummy
Units or register the I/O table again.
Check transmission line between PC and Master and between Remote I/O
Units.
Error has occurred in PC
Link Unit, Remote I/O
Master Unit, between a
Host Link, SYSMAC LINK, or SYSMAC NET Link Unit and the CPU, or in refresh between Special I/O Unit and the CPU.
An error has occurred during data transmission between the CPU and a
Group-2 High-density I/O
Unit.
Determine the unit number of the Unit which caused the error (AR 00), correct the error, and toggle the appropriate Restart Bit in
AR 01, SR 250, or SR 252.
If the Unit does not restart, replace it.
Determine the unit number of the Unit which caused the error (AR 02), replace the
Unit, and try to power-up again.
Backup battery is missing or its voltage has dropped.
Check battery, and replace if necessary.
394
Error Messages Section 10-4
Fatal Operating Errors
Error and message
Power interruption
No message.
The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of the following errors occur. No
CPU indicators will be lit for the power interruption error. For all other fatal operating errors, the POWER and ALM/ERR indicators will be lit. The RUN output will be OFF.
FAL no.
None
Probable cause
Power has been interrupted for at least
10 ms.
Possible correction
Check power supply voltage and power lines. Try to power-up again.
CPU error
No message.
Memory error
MEMORY ERR
No END(01) instruction
NO END INST
None
F1
F0
Watchdog timer has exceeded maximum setting (default setting:
130 ms).
SR 27211 ON:
A checksum error has occurred in the PC
Setup (DM 6600 to
DM 6655).
SR 27212 ON:
A checksum error has occurred in the program, indicating an incorrect instruction.
SR 27213 ON
A checksum error has occurred in an expansion instruction change.
SR 27214 ON:
Memory Cassette was installed or removed with the power on.
SR 27215 ON:
Autoboot error.
END(01) is not written anywhere in program.
Restart system in PROGRAM mode and check program.
Reduce cycle time or reset watchdog timer if longer time required. (Consider effects of longer cycle time before resetting.)
Check the PC Setup.
Check the program.
Install the Memory Cassette correctly.
Check whether the CPU memory is protected or a checksum error occurred in the
Memory Cassette.
Write END(01) at the final address of the program.
I/O bus error
I/O BUS ERR
C0 to C2 Error has occurred in the bus line between the
CPU and I/O Units.
The rightmost digit of the FAL number will indicate the number of the Rack where the error was detected. Check cable connections between the
Racks.
395
Error Messages Section 10-4
Error and message
Too many Units
I/O UNIT OVER
Input-output I/O table error
I/O SET ERROR
FALS error
SYS FAIL FAL**
Communications Errors
Other Error Messages
FAL no.
E1
E0
01 to 99 or 9F
Probable cause
Two or more Special I/O
Units are set to the same unit number
Two or more Group-2
High-density I/O Units are set to the same I/O number or I/O word.
The I/O number of a
64-pt Group-2
High-density I/O Unit is set to 9.
Two SYSMAC NET Link or SYSMAC LINK Units share the same operating level.
Two or more Interrupt
Input Units are mounted.
Input and output word designations registered in I/O table do no agree with input/output words required by Units actually mounted.
FALS has been executed by the program. Check the FAL number to determine conditions that would cause execution (Set by user or by system).
Possible correction
Perform the I/O Table Read operation to check unit numbers, and eliminate duplications. (High-density I/O
Units other than Group-2 are
Special I/O Units, too.)
Set unit numbers of 64-pt
Group-2 High-density I/O Units to numbers other than 9.
Check the SYSMAC NET Link and SYSMAC LINK Unit operating levels and eliminate duplications.
Mount only one Interrupt Input
Unit.
Check the I/O table with I/O
Table Verification operation and check all Units to see that they are in correct configuration.
When the system has been confirmed, register the I/O table again.
Correct according to cause indicated by FAL number. If FAL number is 9F, check watchdog timer and cycle time, which may be to long. 9F will be output when FALS(07) is executed and the cycle time is between 120 and 130 ms.
If errors occur in communications, the indicator for the peripheral port (COMM/
COMM1 when using RS-232C Programming Console cable) or the RS-232C port (COMM2) will not light. Check the connection, programming on both ends
(C200HS and peripheral), and then reset the port using the reset bits (peripheral port: SR 25208; RS-232C port: SR 25209).
A number of other error messages are detailed within this manual. Errors in program input and debugging can be examined in Section 4 Writing and Inputting the Program.
396
Error Flags
10-5 Error Flags
Section 10-5
The following table lists the flags and other information provided in the SR and
AR areas that can be used in troubleshooting. Details are provided in 3-4 SR
Area and 3-5 AR Area.
SR Area
Address(es) Function
23600 to 23615 Node loop status for SYSMAC NET Link system
23700 to 23715 Completion/error code output area for SEND(90)/RECV(98) in SYSMAC LINK/SYSMAC NET Link
System
25310
25311
25312
25411
25413
25414
25415
24700 to 25015 PC Link Unit Run and Error Flags
25100 to 25115 Remote I/O Error Flags
25200
25203
SYSMAC LINK/SYSMAC NET Link Level 0 SEND(90)/RECV(98) Error Flag
SYSMAC LINK/SYSMAC NET Link Level 1 SEND(90)/RECV(98) Error Flag
25206 Rack-mounting Host Link Unit Level 1 Error Flag
25300 to 25307 FAL number output area.
25308
25309
Low Battery Flag
Cycle Time Error Flag
I/O Verification Error Flag
Rack-mounting Host Link Unit Level 0 Error Flag
Remote I/O Error Flag
Interrupt Input Unit Error Flag
Interrupt Programming Error Flag
Group-2 High-density I/O Unit Error Flag
Special Unit Error Flag (Special I/O, PC Link, Host Link, Remote I/O Master, SYSMAC NET Link, or
SYSMAC Link Unit Error Flag)
27215
27312
27313
27314
27315
27500
27501
27502
25503 Instruction Execution Error (ER) Flag
26400 to 26403 RS-232C Port Error Code
26404 RS-232C Port Communications Error
26408 to 26411 Peripheral Port Error Code (except Peripheral Mode)
26412
27011
27012
27013
Peripheral Port Communications Error Flag (except Peripheral Mode)
UM Transfer Error Flag: SYSMAC NET data link active during data link table transfer.
UM Transfer Error Flag: Not PROGRAM mode
UM Transfer Error Flag: Read Only
27014
27015
27211
27212
27213
27214
UM Transfer Error Flag: Insufficient capacity or no UM
UM Transfer Error Flag: Board Checksum Error
Memory Error Flag: PC Setup Checksum Error
Memory Error Flag: UM or Ladder Checksum Error
Memory Error Flag: Expansion Instruction Code Change Area Checksum Error
Memory Error Flag: Memory Cassette Online Disconnection
Memory Error Flag: Autoboot Error
IOM Transfer Error Flag: Not PROGRAM mode
IOM Transfer Error Flag: Read Only
IOM Transfer Error Flag: Insufficient capacity
IOM Transfer Error Flag: Checksum Error
PC Setup Error (DM 6600 to DM 6614)
PC Setup Error (DM 6615 to DM 6644)
PC Setup Error (DM 6645 to DM 6655)
397
Error Flags Section 10-5
AR Area
Address(es)
0000 to 0009
0010
0011
0012
0013
0014
0015
0200 to 0204
0205 to 0215
0215
0300 to 0315
0400 to 0415
0500 to 0515
0600 to 0615
0710 to 0712
0713 to 0715
1114
1115
1514
1515
Function
Special I/O or PC Link Unit Error Flags
SYSMAC LINK/SYSMAC NET Link Level 1 System Error Flags
SYSMAC LINK/SYSMAC NET Link Level 0 System Error Flags
Rack-mounting Host Link Unit Level 1 Error Flag
Rack-mounting Host Link Unit Level 0 Error Flag
Remote I/O Master Unit 1 Error Flag
Remote I/O Master Unit 0 Error Flag
Error Flags for Slave Racks 0 to 4
Group-2 High-density I/O Unit Error Flags (AR 0205 to AR 0214 correspond to I/O numbers 0 to 9.)
Group-2 High-density I/O Unit was not recognized.
Optical I/O Units (0 to 7) Error Flags
Optical I/O Units (8 to 15) Error Flags
Optical I/O Units (16 to 23) Error Flags
Optical I/O Units (24 to 31) Error Flags
Error Flags for Slave Racks 5 to 7
Error History Bits
Communications Controller Error Flag Level 0
EEPROM Error Flag for operating level 0
Communications Controller Error Flag Level 1
EEPROM Error Flag for operating level 1
398
Host Link Errors Section 10-6
10-6 Host Link Errors
These error codes are received as the response code (end code) when a command received by the C200HS from a host computer cannot be processed. The error code format is as shown below.
@ X X X X X X X X
: ↵
Node no.
Header code
End code FCS Terminator
The header code will vary according to the command and can contain a subcode
(for composite commands).
End code
00
01
02
0B
13
14
15
16
18
19
Contents Probable cause Corrective measures
Normal completion
Not executable in RUN mode
Not executable in MONITOR mode The command that was sent cannot be executed when the PC is in
MONITOR mode.
Not executable in PROGRAM mode
The command that was sent cannot be executed when the PC is in
PROGRAM mode.
FCS error
---
The command that was sent cannot be executed when the PC is in
RUN mode.
Format error
The FCS is wrong. Either the FCS calculation is mistaken or there is adverse influence from noise.
The command format is wrong.
Entry number data error
Command not supported
Frame length error
Not executable
---
Check the relation between the command and the PC mode.
This code is not presently being used.
The areas for reading and writing are wrong.
The specified command does not exist.
The maximum frame length was exceeded.
Items to read not registered for composite command (QQ).
Check the FCS calculation method.
If there was influence from noise, transfer the command again.
Check the format and transfer the command again.
Correct the areas and transfer the command again.
Check the command code.
Divide the command into multiple frames.
Execute QQ to register items to read before attempting batch read.
Pin 1 on C200HS DIP switch is ON. Turn OFF pin 1 to execute.
The error was generated while a Check the command data and try
23
A3
A4
A5
User memory write-protected
Aborted due to FCS error in transmit data
Aborted due to format error in transmit data
Aborted due to entry number data error in transmit data
A8 Aborted due to frame length error in transmit data
Other --ted.
f b i
N t Th d h i h already been written to the ap-
Influence from noise was received.
Transfer the command again.
Power Interruptions The following responses may be received from the C200HS if a power interruption occurs, including momentary interruptions. If any of these responses are received during or after a power interruption, repeat the command.
Undefined Command Response
@00IC4A*
↵
No Response
If no response is received, abort the last command and resend.
399
SECTION 11
Host Link Commands
This section explains the methods and procedures for using host link commands, which can be used for host link communications via the C200HS ports.
11-1 Communications Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-2 Command and Response Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-2-1 Commands from the Host Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-2-2 Commands from the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3 Host Link Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-1 IR/SR AREA READ –– RR
11-3-2 LR AREA READ –– RL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-3 HR AREA READ –– RH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-4 PV READ –– RC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-5 TC STATUS READ –– RG
11-3-6 DM AREA READ –– RD
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-7 AR AREA READ –– RJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-8 IR/SR AREA WRITE –– WR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-9 LR AREA WRITE –– WL
11-3-10 HR AREA WRITE –– WH
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-11 PV WRITE –– WC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-12 TC STATUS WRITE –– WG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-13 DM AREA WRITE –– WD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-14 AR AREA WRITE –– WJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-15 SV READ 1 –– R# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-16 SV READ 2 –– R$ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-17 SV READ 3 –– R% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-18 SV CHANGE 1 –– W# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-19 SV CHANGE 2 –– W$ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-20 SV CHANGE 3 –– W% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-21 STATUS READ –– MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-22 STATUS WRITE –– SC
11-3-23 ERROR READ –– MF
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-24 FORCED SET –– KS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-25 FORCED RESET –– KR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-26 MULTIPLE FORCED SET/RESET –– FK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-27 FORCED SET/RESET CANCEL –– KC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-28 PC MODEL READ –– MM
11-3-29 TEST–– TS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-30 PROGRAM READ –– RP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-31 PROGRAM WRITE –– WP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-32 I/O TABLE GENERATE –– MI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-33 COMPOUND COMMAND –– QQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-34 ABORT –– XZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-35 INITIALIZE ––
::
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-36 Undefined Command –– IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4 Host Link Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
417
418
419
420
421
422
423
412
412
413
413
414
415
416
417
408
408
409
409
410
410
411
411
402
404
404
406
407
407
407
424
425
425
426
426
427
427
427
429
430
430
431
401
Communications Procedure Section 11-1
11-1 Communications Procedure
Command Chart
Header code
KS
KR
FK
KC
MM
TS
RP
WP
MI
XZ
::
IC
R$
R%
W#
W$
W%
MS
SC
MF
WL
WH
WC
WG
WD
WJ
R#
RR
RL
RH
RC
RG
RD
RJ
WR
The commands listed in the chart below can be used for host link communications with the C200HS. These commands are all sent from the host computer to the PC.
RUN
Valid
Valid
Valid
Valid
Valid
Valid
PC mode
MON
Valid
Valid
Valid
Valid
Valid
Valid
Valid Valid
Not valid Valid
Not valid
Not valid
Not valid
Not valid
Valid
Valid
Valid
Valid
Not valid Valid
Not valid Valid
Valid Valid
Valid
Valid
Not valid
Not valid
Valid
Valid
Valid
Valid
Not valid Valid
Valid Valid
Valid
Valid
Valid
Valid
Not valid
Not valid
Not valid
Not valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid Valid Valid
Not valid Not valid Valid
Not valid Not valid Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
PRG
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
---
Valid
Valid
Valid
---
Valid
Valid
Valid
---
Name
IR/SR AREA READ
LR AREA READ
HR AREA READ
PV READ
TC STATUS READ
DM AREA READ
AR AREA READ
IR/SR AREA WRITE
LR AREA WRITE
HR AREA WRITE
PV WRITE
TC STATUS WRITE
DM AREA WRITE
AR AREA WRITE
SV READ 1
SV READ 2
SV READ 3
SV CHANGE 1
SV CHANGE 2
SV CHANGE 3
STATUS READ
STATUS WRITE
ERROR READ
FORCED SET
FORCED RESET
MULTIPLE FORCED SET/RESET
FORCED SET/RESET CANCEL
PC MODEL READ
TEST
PROGRAM READ
PROGRAM WRITE
I/O TABLE GENERATE
COMPOUND COMMAND
ABORT (command only)
INITIALIZE (command only)
Undefined command (response only)
422
423
424
425
425
426
426
427
427
415
416
417
417
418
419
420
421
427
429
430
430
411
411
412
412
413
413
414
407
407
408
408
409
409
410
410
402
Communications Procedure Section 11-1
Host link communications are executed by means an exchange of commands and responses between the host computer and the PC. With the C200HS, there are two communications methods that can be used. One is the normal method, in which commands are issued from the host computer to the PC. The other method allows commands to be issued from the PC to the host computer.
Frame Transmission and Reception
Commands and responses are exchanged in the order shown in the illustration below. The block of data transferred in a single transmission is called a “frame”.
A single frame is configured of a maximum of 131 characters of data.
The right to send a frame is called the “transmission right”. The Unit that has the transmission right is the one that can send a frame at any given time. The transmission right is traded back and forth between the host computer and the PC each time a frame is transmitted. The transmission right is passed from the transmitting Unit to the receiving Unit when either a terminator (the code that marks the end of a command or response) or a delimiter (the code that sets frames apart) is received.
Commands from Host In host link communications, the host computer ordinarily has the transmission right first and initiates the communications. The PC then automatically sends a response.
Host computer
Frame (command)
Unit no.
Header code
Text
FCS
Terminator
Next frame transmission enabled (i.e., transmission right transferred)
Frame (command)
Unit no.
Header code
Text
FCS
Terminator
PC
Unit no.
Header code
End code
Text
FCS
Terminator
Frame (response)
Unit no.
Header code
End code
Text
FCS
Terminator
Frame (response)
Commands from PC It is also possible in host link communications for the PC to send commands to the host computer. In this case it is the PC that has the transmission right and initiates the communications.
Host computer
No response
PC
Unit no.
Header code
Text
FCS
Terminator
403
Command and Response Formats
Section 11-2
When commands are issued to the host computer, the data is transmitted in one direction from the PC to the host computer. If a response to a command is required use a host link communications command to write the response from the host computer to the PC.
11-2 Command and Response Formats
This section explains the formats for the commands and responses that are exchanged in host link communications.
11-2-1 Commands from the Host Computer
When a command is issued from the host computer, the command and response formats are as shown below.
Command Format When transmitting a command from the host computer, prepare the command data in the format shown below.
@ x 10 1 x 10 0
Response Format
Node no.
: ↵
Header code
Text FCS Terminator
@
An “@” symbol must be placed at the beginning.
Node No.
Identifies the PC communicating with the host computer.
Specify the node number set for the PC in the PC Setup (DM 6648, DM 6653).
Header Code
Set the 2-character command code.
Text
Set the command parameters.
FCS
Set a 2-character Frame Check Sequence code. See page 405.
Terminator
Set two characters, “ : ” and the carriage return (CHR$(13)) to indicate the end of the command.
The response from the PC is returned in the format shown below. Prepare a program so that the response data can be interpreted and processed.
@ x 10 1 x 10 0 x 16 1 x 16 0 : ↵
Node no.
Header code
End code Text FCS Terminator
@, Node No., Header Code
Contents identical to those of the command are returned.
End Code
The completion status of the command (e.g., whether or not an error has occurred) is returned.
Text
Text is returned only when there is data such as read data.
FCS, Terminator
Refer to the corresponding explanations under “Command Format”.
404
Command and Response Formats
Long Transmissions
Section 11-2
The largest block of data that can be transmitted as a single frame is 131 characters. A command or response of 132 characters or more must therefore be divided into more than one frame before transmission. When a transmission is split, the ends of the first and intermediate frames are marked by a delimiter instead of a terminator.
As each frame is transmitted, the receiving node waits for the delimiter to be transmitted. After the delimiter has been transmitted, the next frame will then be sent. This procedure is repeated until the entire command or response has been transmitted. The following diagram shows an example of host link communications addressed to a PC.
Frame2 (command) Frame3 (command)
Host computer
Frame1 (command)
Unit no.
Header code
Text
FCS
Delimiter
Text
FCS
Delimiter
Text
FCS
Terminator
PC
Frame 1
@ 0 0 W D
Delimiter Delimiter Unit no.
Header code
End code
Text
FCS
Terminator
Frame (response)
Precautions for Long Transmissions
When dividing commands such as WR, WL, WC, or WD that execute write operations, be careful not to divide into separate frames data that is to be written into a single word. As shown in the illustration below, be sure to divide frames so that they coincide with the divisions between words.
Data
Node no.
Header code
↵
One word of data FCS Delimiter
Data from the same word is not divided.
Frame 3
Data
FCS
: ↵
Terminator One word of data
Data from the same word is not divided.
FCS (Frame Check Sequence) When a frame is transmitted, an FCS is placed just before the delimiter or terminator in order to check whether any data error has been generated. The FCS is
8-bit data converted into two ASCII characters. The 8-bit data is the result of an
EXCLUSIVE OR performed on the data from the beginning of the frame until the end of the text in that frame (i.e., just before the FCS). Calculating the FCS each
405
Command and Response Formats
Section 11-2 time a frame is received and checking the result against the FCS that is included in the frame makes it possible to check for data errors in the frame.
@ 1 0 R R 0 0 0 1 4
FCS
2 : ↵
Terminator Node no.
Header code
FCS calculation range
Text
0
R
@
1
ASCII code
40
31
30
52
0100
EOR
0011
EOR
0011
EOR
0101
0000
0001
0000
0010
1
Calculation result
31 0011
0100
↓
4
0001
0010
↓
2
Converted to hexadecimal.
Handled as ASCII characters.
Example Program for FCS This example shows a BASIC subroutine program for executing an FCS check on a frame received by the host computer.
400 *FCSCHECK
410 L=LEN(RESPONSE$) ’ . . . . . . . . . . .
420 Q=0:FCSCK$=“ ”
430 A$=RIGHT$(RESPONSE$,1)
Data transmitted and received
440 PRINT RESPONSE$,AS,L
450 IF A$=”*” THEN LENGS=LEN(RESPONSE$)-3
ELSE LENGS=LEN(RESPONSE$)-2
460 FCSP$=MID$(RESPONSE$,LENGS+1,2) ’
470 FOR I=1 TO LENGS ’ . . . . . . . . . . .
. . . . FCS data received
Number of characters in FCS
480 Q=ASC(MID$(RESPONSE$,I,1)) XOR Q
490 NEXT I
500 FCSD$=HEX$(Q)
510 IF LEN(FCSD$)=1 THEN FCSD$=”0”+FCSD$ ’ FCS result
520 IF FCSD$<>FCSP$ THEN FCSCK$=”ERR”
530 PRINT“FCSD$=”;FCSD$,“FCSP$=”;FCSP$,“FCSCK$=”;FCSCK$
540 RETURN
Note 1. Normal reception data includes the FCS, delimiter or terminator, and so on.
When an error occurs in transmission, however the FCS or some other data may not be included. Be sure to program the system to cover this possibility.
2. In this program example, the CR code (CHR$(13)) is not entered for RE-
SPONSE$. When including the CR code, make the changes in lines 430 and 450.
11-2-2 Commands from the PC
In host link communications, commands are ordinarily sent from the host computer to the PC, but it is also possible for commands to be sent from the PC to the host computer. In Host Link Mode, any data can be transmitted from the PC to the host computer. To send a command to the host computer, use the TRANS-
MIT instruction (TXD(--)) in the PC program in Host Link Mode.
TXD(––) outputs data from the specified port (the RS-232C port or the peripheral port). Refer to page 299 for details on using TXD(––).
406
Host Link Commands
Reception Format
Section 11-3
When TXD(––) is executed, the data stored in the words beginning with the first send word is converted to ASCII and output to the host computer as a host link command in the format shown below. The “@” symbol, node number, header code, FCS, and delimiter are all added automatically when the transmission is sent. At the host computer, it is necessary to prepare in advance a program for interpreting and processing this format.
@ E X 122 characters max.
: ↵
Node no.
Header code
(Must be “EX”)
Text FCS Terminator
One byte of data (2 digits hexadecimal) is converted to two characters in ASCII for transmission, the amount of data in the transmission is twice the amount of words specified for TXD(––). The maximum number of characters for transmission is 122 and the maximum number of bytes that can be designated for
TXD(––) is one half of that, or 61.
11-3 Host Link Commands
This section explains the commands that can be issued from the host computer to the PC.
11-3-1 IR/SR AREA READ –– RR
Reads the contents of the specified number of IR and SR words, starting from the specified word.
Command Format
@ x 10 1 x 10 0
R R x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0511)
No. of words
(0000 to 0512)
FCS Terminator
Response Format
@ x 10 1 x 10 0 R R x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Terminator Node no.
Header code
End code Read data (1 word)
Read data (for number of words read)
FCS
Parameters Read Data (Response)
The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
11-3-2 LR AREA READ –– RL
Reads the contents of the specified number of LR words, starting from the specified word.
Command Format
@ x 10 1 x 10 0
R L x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0063)
No. of words
(0001 to 0064)
FCS Terminator
407
Host Link Commands
Section 11-3
Response Format
@ x 10 1 x 10 0
R L x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Node no.
Header code
End code Read data (1 word)
Read data (for number of words read)
FCS Terminator
Parameters Read Data (Response)
The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
11-3-3 HR AREA READ –– RH
Reads the contents of the specified number of HR words, starting from the specified word.
Command Format
@ x 10 1 x 10 0
R H x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Header code
Response Format
@ x 10 1 x 10 0
R
Beginning word
(0000 to 0099)
No. of words
(0001 to 0100)
H x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0
FCS Terminator
: ↵
Terminator Node no.
Header code
End code Read data (1 word)
Read data (for number of words read)
FCS
Parameters Read Data (Response)
The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
11-3-4 PV READ –– RC
Reads the contents of the specified number of timer/counter PVs (present values), starting from the specified timer/counter.
Command Format
@ x 10
1 x 10
0
R C x 10
3 x 10
2 x 10
1 x 10
0 x 10
3 x 10
2 x 10
1 x 10
0 : ↵
FCS Terminator Node no.
Header code
Beginning timer/counter
(0000 to 0511)
No. of timers/counters
(0001 to 0512)
Response Format
@ x 10 1 x 10 0
R C x 16 1 x 16 0 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
End code Read data (1 word)
Read data (for number of words read)
FCS
: ↵
Terminator
Parameters Read Data (Response)
The number of present values specified by the command is returned in hexade-
408
Host Link Commands
Section 11-3 cimal as a response. The PVs are returned in order, starting with the specified beginning timer/counter.
11-3-5 TC STATUS READ –– RG
Reads the status of the Completion Flags of the specified number of timers/ counters, starting from the specified timer/counter.
Command Format
@ x 10 1 x 10 0
R G x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Header code
Beginning timer/counter
(0000 to 0511)
No. of timers/counters
(0001 to 0512)
FCS Terminator
Response Format
@ x 10 1 x 10 0
R
Node no.
G x 16 1 x 16 0
ON/
OFF
Header code
End code FCS
Read data
(1 timer/counter)
Read data
(for number of TC read)
: ↵
Terminator
Parameters Read Data (Response)
The status of the number of Completion Flags specified by the command is returned as a response. “1” indicates that the Completion Flag is ON.
11-3-6 DM AREA READ –– RD
Reads the contents of the specified number of DM words, starting from the specified word.
Command Format
@ x 10 1 x 10 0
R D x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Header code
Beginning word
(0000 to 9999)
No. of words
(0001 to 10000)
(see note)
FCS
Node no.
Header code
End code Read data (1 word)
Read data (for number of words read)
FCS
Terminator
Note 1. If 10,000 words have to be read, specify the number of words to be read as
0000.
2. DM 6656 to DM 6999 do not exist. An error will not, however, result if you try to read these words. Instead, “0000” will be returned as a response.
Response Format
@ x 10 1 x 10 0
R D x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Terminator
Parameters Read Data (Response)
The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
409
Host Link Commands
Section 11-3
11-3-7 AR AREA READ –– RJ
Reads the contents of the specified number of AR words, starting from the specified word.
Command Format
@ x 10 1 x 10 0
R J x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0027)
No. of words
(0001 to 0028)
FCS Terminator
Response Format
@ x 10 1 x 10 0
R J x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0
Node no.
Header code
End code Read data (1 word )
Read data
(for number of words read)
FCS
: ↵
Terminator
Parameters Read Data (Response)
The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
11-3-8 IR/SR AREA WRITE –– WR
Writes data to the IR and SR areas, starting from the specified word. Writing is done word by word.
Command Format
@ x 10 1 x 10 0
W R x 10 3 x 10 2 x 10 1 x 10 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0511)
Write data (1 word)
Write data
(for number of words to write)
FCS Terminator
Note Data cannot be written to words 253 to 255. If there is an attempt to write to these words, no error will result, but nothing will be written to these words.
Response Format
@ x 10 1 x 10 0
W R x 16 1 x 16 0
Node no.
Header code
End code FCS
: ↵
Terminator
Parameters Write Data (Command)
Specify in order the contents of the number of words to be written to the IR or SR area in hexadecimal, starting with the specified beginning word.
Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 511 is specified as the beginning word for writing,and two words of data are specified, then 0512 will become the last word for writing data, and the command will not be executed because SR 512 is beyond the writeable range.
410
Host Link Commands
Section 11-3
11-3-9 LR AREA WRITE –– WL
Writes data to the LR area, starting from the specified word. Writing is done word by word.
Command Format
@ x 10 1 x 10 0
W L x 10 3 x 10 2 x 10 1 x 10 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0063)
Write data (1 word)
Write data
(for number of words to write )
FCS Terminator
Response Format
@ x 10 1 x 10 0
W L x 16 1 x 16 0 : ↵
Node no.
FCS Terminator
Parameters Write Data (Command)
Specify in order the contents of the number of words to be written to the LR area in hexadecimal, starting with the specified beginning word.
Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 60 is specified as the beginning word for writing and five words of data are specified, then 64 will become the last word for writing data, and the command will not be executed because LR 64 is beyond area boundary.
11-3-10 HR AREA WRITE –– WH
Writes data to the HR area, starting from the specified word. Writing is done word by word.
Command Format x 10 1 x 10 0
W H x 10 3 x 10 2 x 10 1 x 10 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0099)
Write data (1 word)
Write data
(for no. of words to write)
FCS Terminator
Response Format
Header code
End code
@ x 10 1 x 10 0
W H x 16 1 x 16 0 : ↵
Parameters
Node no.
Header code
End code FCS Terminator
Write Data (Command)
Specify in order the contents of the number of words to be written to the HR area in hexadecimal, starting with the specified beginning word.
Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 98 is specified as the beginning word for writing, and three words of data are specified, then 100 will become the last word for writing data, and the command will not be executed because HR 100 is beyond area boundary.
411
Host Link Commands
Section 11-3
11-3-11 PV WRITE –– WC
Writes the PVs (present values) of timers/counters starting from the specified timer/counter.
Command Format
@ x 10 1 x 10 0
W C x 10 3 x 10 2 x 10 1 x 10 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
FCS Terminator Node no.
Header code
Beginning timer/counter
(0000 to 0511)
Write data (1 timer/counter)
Write data
(for no. of PV to write)
Response Format
@ x 10 1 x 10 0
W C x 16 1 x 16 0 : ↵
FCS Terminator
Parameters Write Data (Command)
Specify in decimal numbers (BCD) the present values for the number of timers/ counters that are to be written, starting from the beginning timer/counter.
Note 1. When this command is used to write data to the PV area, the Completion
Flags for the timers/counters that are written will be turned OFF.
2. If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 510 is specified as the beginning word for writing, and three words of data are specified, then 512 will become the last word for writing data, and the command will not be executed because TC 512 is beyond area boundary.
11-3-12 TC STATUS WRITE –– WG
Writes the status of the Completion Flags for timers and counters in the TC area, starting from the specified timer/counter (number). Writing is done number by number.
Command Format
@ x 10 1 x 10 0
W G x 10 3 x 10 2 x 10 1 x 10 0
ON/
OFF
: ↵
Terminator Node no.
Header code
Beginning timer/counter
(0000 to 0511)
FCS
Write data
(1 timer/counter)
Write data
(for number of TC to write)
Response Format
Node no.
Header code
End code
@ x 10 1 x 10 0 W G x 16 1 x 16 0 : ↵
Parameters
Node no.
Header code
End code FCS Terminator
Write Data (Command)
Specify the status of the Completion Flags, for the number of timers/counters to be written, in order (from the beginning word) as ON (i.e., “1”) or OFF (i.e., “0”).
When a Completion Flag is ON, it indicates that the time or count is up.
412
Host Link Commands
Section 11-3
Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 510 is specified as the beginning word for writing, and three words of data are specified, then 512 will become the last word for writing data, and the command will not be executed because TC 512 is beyond area boundary.
11-3-13 DM AREA WRITE –– WD
Writes data to the DM area, starting from the specified word. Writing is done word by word.
Command Format x 10 1 x 10 0
W D x 10 3 x 10 2 x 10 1 x 10 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Node no.
Header code
Beginning word
(0000 to 9999)
Write data (1 word)
Write data
(for number of words to write)
FCS Terminator
Note DM 6656 to DM 6999 do not exist. An error will not, however, result if you try to write to these words.
Response Format
@ x 10 1 x 10 0
W D x 16 1 x 16 0 : ↵
Node no.
Header code
End code FCS Terminator
Parameters Write Data (Command)
Specify in order the contents of the number of words to be written to the DM area in hexadecimal, starting with the specified beginning word.
Note 1. If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 9998 is specified as the beginning word for writing, and three words of data are specified, then 10000 will become the last word for writing data, and the command will not be executed because DM 10000 is beyond the writeable range.
2. Be careful about the configuration of the DM area, as it varies depending on the CPU model.
11-3-14 AR AREA WRITE –– WJ
Writes data to the AR area, starting from the specified word. Writing is done word by word.
Command Format x 10 1 x 10 0
W J x 10 3 x 10 2 x 10 1 x 10 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Node no.
Header code
Beginning word
(0000 to 0027)
Write data (1 word)
Write data
(for the number of words to write)
FCS Terminator
Response Format
@ x 10 1 x 10 0
W J x 16 1 x 16 0
Node no.
Header code
End code FCS
: ↵
Terminator
413
Host Link Commands
Parameters
Section 11-3
Write Data (Command)
Specify in order the contents of the number of words to be written to the AR area in hexadecimal, starting with the specified beginning word.
Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 26 is specified as the beginning word for writing, and three words of data are specified, then 28 will become the last word for writing data, and the command will not be executed because AR 28 is beyond the writeable range.
11-3-15 SV READ 1 –– R#
Searches for the first instance of a TIM, TIMH(15), CNT, CNTR(12), or TTIM(87) instruction with the specified TC number in the user’s program and reads the PV, which assumed to be set as a constant. The SV that is read is a 4-digit decimal number (BCD). The program is searched from the beginning, and it may therefore take approximately 10 seconds to produce a response.
Command Format x 10 1 x 10 0
R # OP 1 OP 2 OP 3 OP 4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
Name TC number
(0000 to 0511)
FCS
: ↵
Terminator
Response Format
@ x 10 1 x 10 0
R # x 16 1 x 16 0 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
End code SV FCS
: ↵
Terminator
Parameters Name, TC Number (Command)
Specify the instruction for reading the SV in “Name”. Make this setting in 4 characters. In “TC number”, specify the timer/counter number used for the instruction.
T
T
C
C
T
OP1
I
N
N
T
Instruction name
OP2
I M
OP3
I
T
M
T
OP4
(S)
H
(S)
R
M
(S): Space
SV (Response)
The constant SV is returned.
Classification
TIMER
HIGH-SPEED TIMER
COUNTER
REVERSIBLE COUNTER
TOTALIZING TIMER
TC number range
0000 to 0511
Note 1. The instruction specified under “Name” must be in four characters. Fill any gaps with spaces to make a total of four characters.
2. If the same instruction is used more than once in a program, only the first one will be read.
3. Use this command only when it is definite that a constant SV has been set.
414
Host Link Commands
Section 11-3
11-3-16 SV READ 2 –– R$
Reads the constant SV or the word address where the SV is stored. The SV that is read is a 4-digit decimal number (BCD) written as the second operand for the
TIM, TIMH(15), CNT, CNTR(12), or TTIM(87) instruction at the specified program address in the user’s program. This can only be done with a program of less than 10K.
Command Format
@ x 10 1 x 10 0
R $ x 10 3 x 10 2 x 10 1 x 10 0 OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
Program address
Name Timer/counter
(0000 to 0511)
: ↵
FCS Terminator
Response Format
@ x 10 1 x 10 0
R $ x 16 1 x 16 0 OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
End code Operand SV
: ↵
FCS Terminator
Parameters Name, TC Number (Command)
Specify the name of the instruction for reading the SV in “Name”. Make this setting in 4 characters. In “TC number”, specify the timer/counter number used by the instruction.
H
A
D
D
C
C
OP1
L
T
T
C
C
T
OP1
Instruction name
I
I
N
N
T
OP2
I
T
M
OP3
M
T
OP4
(S)
H
(S)
R
M
Classification
TIMER
HIGH-SPEED TIMER
COUNTER
REVERSIBLE COUNTER
TOTALIZING TIMER
TC number range
0000 to 0511
(S): Space
Operand, SV (Response)
The name that indicates the SV classification is returned to “Operand”, and either the word address where the SV is stored or the constant SV is returned to
“SV”.
R
R
M
M
O
I
R
OP2
Operand
O
OP3
(S)
(S)
(S)
(S)
:
N
OP4
(S)
(S)
(S)
(S)
(S)
(S)
(S)
Classification
IR or SR
LR
HR
AR
DM
DM (indirect)
Constant
Constant or
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 6655
0000 to 6655
0000 to 9999
Note The instruction name specified under “Name” must be in four characters. Fill any gaps with spaces to make a total of four characters.
415
Host Link Commands
Section 11-3
11-3-17 SV READ 3 –– R%
Reads the constant SV or the word address where the SV is stored. The SV that is read is a 4-digit decimal number (BCD) written in the second word of the TIM,
TIMH(15), CNT, CNTR(12), or TTIM(87) instruction at the specified program address in the user’s program. With this command, program addresses can be specified for a program of 10K or more.
Command Format
@ x 10 1 x 10 0
R % x 10 5 x 10 4 x 10 3 x 10 2 x 10 1 x 10 0 OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
Must be “0”
Program address
Name Timer/counter
(0000 to 0511)
: ↵
FCS Terminator
Response Format
@ x 10 1 x 10 0
R % x 16 1 x 16 0 OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Parameters
Node no.
Header code
End code Operand SV FCS Terminator
Name, TC Number (Command)
Specify the name of the instruction for reading the SV in “Name”. Make this setting in 4 characters. In “TC number”, specify the timer/counter number used by the instruction.
A
D
D
C
C
OP1
L
H
I
N
N
T
Instruction name
OP2
I M
OP3
I
T
M
T
OP4
(S)
H
(S)
R
M
Classification TC number range
T
T
C
C
T
OP1
TIMER
HIGH-SPEED TIMER
COUNTER
REVERSIBLE COUNTER
TOTALIZING TIMER
0000 to 0511
(S): Space
Operand, SV (Response)
The name that indicates the SV classification is returned to “Operand”, and either the word address where the SV is stored or the constant SV is returned to
“SV”.
R
R
R
M
I
Operand
OP2
O
OP3
M
O
(S)
(S)
(S)
(S)
:
N
(S)
(S)
(S)
(S)
OP4
(S)
(S)
(S)
Classification
IR or SR
LR
HR
AR
DM
DM (indirect)
Constant
Constant or
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 6655
0000 to 6655
0000 to 9999
Note The instruction name specified under “Name” must be in four characters. Fill any gaps with spaces to make a total of four characters.
416
Host Link Commands
Section 11-3
11-3-18 SV CHANGE 1 –– W#
Searches for the first instance of the specified TIM, TIMH(15), CNT, CNTR(12), or TTIM(87) instruction in the user’s program and changes the SV to new constant SV specified in the second word of the instruction. The program is searched from the beginning, and it may therefore take approximately 10 seconds to produce a response.
Command Format
@ x 10 1 x 10 0 W # OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0 x 10 3 x 10 2 x 10 1 x 10 0 : ↵
Node no.
Response Format
Header code
Name Timer/counter
(0000 to 0511)
SV (0000 to 9999) FCS Terminator
@ x 10 1 x 10 0
W # x 16 1 x 16 0 : ↵
Node no.
Header code
End code FCS Terminator
Parameters Name, TC Number (Command)
In “Name”, specify the name of the instruction, in four characters, for changing the SV. In “TC number”, specify the timer/counter number used for the instruction.
Classification TC number range
T
T
C
C
T
OP1
(S): Space
Instruction name
I
I
N
N
T
OP2
I
T
M
OP3
M
T
OP4
(S)
H
(S)
R
M
TIMER
HIGH-SPEED TIMER
COUNTER
REVERSIBLE COUNTER
TOTALIZING TIMER
0000 to 0511
11-3-19 SV CHANGE 2 –– W$
Changes the contents of the second word of the TIM, TIMH(15), CNT,
CNTR(12), or TTIM(87) at the specified program address in the user’s program.
This can only be done with a program of less than 10K.
Command Format
@ x 10 1 x 10 0
W $ x 10 3 x 10 2 x 10 1 x 10 0 OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
Program address
Name Timer/counter
(0000 to 0511)
OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Operand SV
: ↵
FCS Terminator
Response Format
@ x 10 1 x 10 0
W $ x 16 1 x 16 0
Node no.
Header code
End code
: ↵
FCS Terminator
417
Host Link Commands
Section 11-3
Parameters Name, TC Number (Command)
In “Name”, specify the name of the instruction, in four characters, for changing the SV. In “TC number”, specify the timer/counter number used for the instruction.
T
T
C
C
T
OP1
N
N
T
I
I
Instruction name
OP2
M
M
OP3
T
I
T
OP4
(S)
H
(S)
R
M
Classification
TIMER
HIGH-SPEED TIMER
COUNTER
REVERSIBLE COUNTER
TOTALIZING TIMER
TC number range
0000 to 0511
(S): Space
Operand, SV (Response)
In “Operand”, specify the name that indicates the SV classification. Specify the name in four characters. In “SV”, specify either the word address where the SV is stored or the constant SV.
H
A
D
D
C
C
OP1
L
M
M
O
R
R
R
I
Operand
OP2
O
OP3
(S)
(S)
(S)
(S)
:
N
(S): Space
OP4
(S)
(S)
(S)
(S)
(S)
(S)
(S)
Classification
IR or SR
LR
HR
AR
DM
DM (indirect)
Constant
Constant or
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 6655
0000 to 6655
0000 to 9999
11-3-20 SV CHANGE 3 –– W%
Changes the contents of the second word of the TIM, TIMH(15), CNT,
CNTR(12), or TTIM(87) at the specified program address in the user’s program.
With this command, program address can be specified for a program of more than 10K.
Command Format
@ x 10 1 x 10 0 W % x 10 5 x 10 4 x 10 3 x 10 2 x 10 1 x 10 0 OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
Must be “0”
Program address
Name
OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Timer/counter
(0000 to 0511)
: ↵
Operand SV FCS Terminator
Response Format
@ x 10 1 x 10 0 W % x 16 1 x 16 0
Node no.
Header code
End code
: ↵
FCS Terminator
418
Host Link Commands
Parameters
Section 11-3
Name, TC Number (Command)
In “Name”, specify the name of the instruction, in four characters, for changing the SV. In “TC number”, specify the timer/counter number used for the instruction.
T
T
C
C
T
OP1
I
N
N
T
Instruction name
OP2
I M
OP3
I
T
M
T
OP4
(S)
H
(S)
R
M
Classification
TIMER
HIGH-SPEED TIMER
COUNTER
REVERSIBLE COUNTER
TOTALIZING TIMER
TC number range
0000 to 0511
(S): Space
Operand, New SV (Response)
In “Operand”, specify the name that indicates the SV classification. Specify the name in four characters. In “SV”, specify either the word address where the SV is stored or the constant SV.
A
D
D
C
C
OP1
L
H
R
R
R
M
I
Operand
OP2
O
OP3
M
O
(S)
(S)
(S)
(S)
:
N
(S): Space
Classification
(S)
(S)
(S)
(S)
OP4
(S)
(S)
(S)
IR or SR
LR
HR
AR
DM
DM (indirect)
Constant
Constant or
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 6655
0000 to 6655
0000 to 9999
11-3-21 STATUS READ –– MS
Reads the PC operating conditions.
Command Format
@ x 10 1 x 10 0
M S
Node no.
Header code
: ↵
FCS Terminator
Response Format
@ x 10 1 x 10 0 M S x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0 16 characters
Node no.
Header code
End code Status data Message
: ↵
FCS Terminator
419
Host Link Commands
Parameters
Section 11-3
Status Data, Message (Response)
“Status data” consists of four digits (two bytes) hexadecimal. The leftmost byte indicates CPU operation mode, and the rightmost byte indicates the size of the program area.
x 16 3 x 16 2
Bit 15 14 13 12 11 10 9 8
0 0 0
1: Remote I/O waiting for power application
1: Fatal error generated
1: FALS generated
Bit
9 8
0 0
1 0
1 1
Operation mode
PROGRAM mode
RUN mode
MONITOR mode
This area is different from that of
STATUS WRITE.
“Message” indicates the FAL/FALS number generated at the point when the command is executed. When there is no message, this is omitted.
11-3-22 STATUS WRITE –– SC
Changes the PC operating mode.
Command Format
@ x 10 1 x 10 0 S C x 16 1 x 16 0 : ↵
Node no.
Header code
Mode data FCS Terminator
Response Format
Bit x 16 1 x 16 0
7 6 5 4 3 2 1 0
1 0 0 0
Bit
6 5
1 0
4
0
Program area
32 Kbytes
Program area write enable
0: Disabled (DIP switch pin 1 is ON)
1: Enabled (DIP switch pin 1 is OFF)
@ x 10 1 x 10 0
S C x 16 1 x 16 0
Node no.
Header code
End code
: ↵
FCS Terminator
420
Host Link Commands
Parameters
Section 11-3
Mode Data (Command)
“Mode data” consists of two digits (one byte) hexadecimal. With the leftmost two bits, specify the PC operating mode. Set all of the remaining bits to “0”.
x 16 1 x 16 0
Bit 7 6 5 4 3 2 1 0
0 0 0 0 0 0
Bit
1 0
0 0
1 0
1 1
Operation mode
PROGRAM mode
MONITOR mode
RUN mode
This area is different from that of STATUS
READ.
11-3-23 ERROR READ –– MF
Reads and clears errors in the PC. Also checks whether previous errors have been cleared.
Command Format
@ x 10 1 x 10 0
M F x 10 1 x 10 0 : ↵
Node no.
Header code
Error clear FCS Terminator
Response Format
@ x 10 1 x 10 0
M F x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0 x 16 3 x 16 2 x 16 1 x 16 0 : ↵
Parameters
Node no.
Header code
End code Error information
(1st word)
Error information
(2nd word)
FCS Terminator
Error Clear (Command)
Specify 01 to clear errors and 00 to not clear errors (BCD). Fatal errors can be cleared only when the PC is in PROGRAM mode.
421
Host Link Commands
Error Information (Response)
The error information comes in two words.
1st word x 16 3 x 16 2
Bit 15 14 13 12 11 10 9 8
0 0 x 16 1
7 6 5 4 x 16 0
3 2 1 0
(Data from I/O bus)
0 1: Group 2 (data bus failure)
0 0 0: CPU Rack
0 0 1: Expansion I/O Rack 1
0 1 0: Expansion I/O Rack 2
0 1 1: Expansion I/O Rack 3
ON: Battery error (Error code F7)
ON: Special I/O Unit error
ON: System error (FAL)
ON: Memory error (Error code F1)
ON: I/O bus error (Error code C0)
ON: PC link error
ON: Host Link Unit transmission error
ON: No end instruction error (FALS)
ON: System error (FALS)
2nd word x 16 3 x 16 2
Bit 15 14 13 12 11 10 9 8
0 0 0 x 16 1
7 6 5 4 x 16 0
3 2 1 0
Section 11-3
Node no.
Header code
Response Format
Name
FAL, FALS No. (B CD00 to 99)
ON: I/O verify error (Error code F7)
ON: Cycle time overrun (Error code F8)
ON: I/O Unit overflow (Error code E1)
ON: I/O setting error (Error code E0)
ON: Remote I/O error (Error codes B0 to B3)
11-3-24 FORCED SET –– KS
Force sets a bit in the IR, SR, LR, HR, AR, or TC area. Once a bit has been forced set or reset, that status will be retained until FORCED SET/RESET CANCEL
(KC) is transmitted.
Command Format
@ x 10 1 x 10 0
K S OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0 x 10 1 x 10 0 : ↵
Word address
Bit FCS Terminator
@ x 10 1 x 10 0
K S x 16 1 x 16 0
Node no.
Header code
End code
: ↵
FCS Terminator
422
Host Link Commands
Section 11-3
Parameters Name, Word address, Bit (Command)
In “Name”, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced set. Specify the name in four characters. In “Word address”, specify the address of the word, and in “Bit” the number of the bit that is to be forced set.
T
T
C
L
H
A
C
C
T
Name
OP1 OP2 OP3 OP4
I
I
I
R
R
R
N
N
T I
O
(S)
(S)
(S)
M
M
T
T
(S)
(S)
(S)
(S)
(S)
H
(S)
R
M
Classification range
Bit
IR or SR
LR
HR
AR
Completion Flag (timer)
Completion Flag (high-speed timer)
Completion Flag (counter)
Completion Flag (reversible counter)
Completion Flag (totalizing timer)
(S): Space
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 0511
Note 1. The area specified under “Name” must be in four characters. Fill any gaps with spaces to make a total of four characters.
2. Words 253 to 255 cannot be set when the CIO Area is specified.
11-3-25 FORCED RESET –– KR
Force resets a bit in an IR, SR, LR, HR, AR, or TC area. Once a bit has been forced set or reset, that status will be retained until FORCED SET/RESET CAN-
CEL (KC) is transmitted.
Command Format
@ x 10 1 x 10 0
K R OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0 x 10 1 x 10 0 : ↵
Node no.
Header code
Response Format
Name Word address
Bit FCS Terminator
@ x 10 1 x 10 0
K R x 16 1 x 16 0 : ↵
Node no.
Header code
End code FCS Terminator
Parameters
T
T
H
A
C
C
T
Name
OP1 OP2 OP3 OP4
C I O (S)
L R (S) (S)
I
I
R
R
N
N
T
T
I
T
(S)
(S)
M
M
(S)
(S)
(S)
H
(S)
R
M
Name, Word address, Bit (Command)
In “Name”, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced reset. Specify the name in four characters. In “Word address”, specify the address of the word, and in “Bit” the number of the bit that is to be forced reset.
Classification Bit range
IR or SR
LR
HR
AR
Completion Flag (timer)
Completion Flag (high-speed timer)
Completion Flag (counter)
Completion Flag (reversible counter)
Completion Flag (totalizing timer)
(S): Space
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 0511
423
Host Link Commands
Section 11-3
Note 1. The area specified under “Name” must be in four characters. Fill any gaps with spaces to make a total of four characters.
2. Words 253 to 255 cannot be set when the CIO Area is specified.
11-3-26 MULTIPLE FORCED SET/RESET –– FK
Force sets, force resets, or cancels the status of the bits in one word in the IR,
SR, LR, HR, AR, or TC area.
Command Format
@ x 10 1 x 10 0
F K OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0
Node no.
Header code
Name Word address x 16 0 x 16 0
Forced set/reset/cancel data x 16 0 x 16 0 x 16 0 x 16 0 x 16 0 x 16 0
Bit 15 14 13 12 11 10 1 0
: ↵
FCS Terminator
Response Format
@ x 10 1 x 10 0
F K x 16 1 x 16 0
Node no.
Header code
End code
: ↵
FCS Terminator
Parameters Name, Word address (Command)
In “Name”, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced set or reset. Specify the name in four characters. In “Word address”, specify the address of the word that is to be forced set or reset.
Bit
T
T
H
A
C
C
T
Name
OP1 OP2 OP3 OP4
C I O (S)
L R (S) (S)
I
I
R
R
N
N
T
T
I
T
(S)
(S)
M
M
(S)
(S)
(S)
H
(S)
R
M
Classification
IR or SR
LR
HR
AR
Completion Flag (timer)
Completion Flag (high-speed timer)
Completion Flag (counter)
Completion Flag (reversible counter)
Completion Flag (totalizing timer)
(S): Space range
0000 to 0511
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 0511
Note Words 253 to 255 cannot be set when the CIO Area is specified.
424
Host Link Commands
Section 11-3
04
05
08
00
02
03
Forced set/reset/cancel Data (Command)
A separate hexadecimal digit is used to specify the desired process for each bit in the specified word, bits 00 to bit 5. The bits that are merely set or reset may change status the next time the program is executed, but bits that are force-set or force-reset will maintain the forced status until it is cleared. If the item specified under “Name” is a timer or counter, the status of the Completion Flag can be force-set or force-reset using bit 15, and all other bits will be ignored. Only forcesetting and force-resetting are possible for timers/counters.
Bits 00 to 15 Setting
Bit status not changed
Reset
Set
Forced-reset
Forced-set
Forced set/reset status cancel
Note The item specified under “Name” must be in four characters. Fill any gaps with spaces to make a total of four characters.
11-3-27 FORCED SET/RESET CANCEL –– KC
Cancels all forced set and forced reset bits (including those set by FORCED
SET, FORCED RESET, and MULTIPLE FORCED SET/RESET). If multiple bits are set, the forced status will be cancelled for all of them. It is not possible to cancel bits one by one using KC.
Command Format
@ x 10 1 x 10 0
K C
: ↵
Node no.
Header code
FCS Terminator
Response Format
@ x 10 1 x 10 0
K C x 16 1 x 16 0 : ↵
Node no.
Header code
End code
11-3-28 PC MODEL READ –– MM
Reads the model type of the PC.
Command Format
@ x 10 1 x 10 0
M M
Node no.
Header code
FCS Terminator
: ↵
FCS Terminator
Response Format
@ x 10 1 x 10 0
M M x 16 1 x 16 0 x 16 1 x 16 0
Node no.
Header code
End code Model code
FCS
: ↵
Terminator
425
Host Link Commands
Parameters
Section 11-3
01
02
03
0E
10
11
12
20
21
22
40
41
Model Code
“Model code” indicates the PC model in two digits hexadecimal.
Model code Model
C250
C500
C120
C2000
C1000H
C2000H/CQM1
C20H/C28H/C40H/C200H/C200HS
CV500
CV1000
CV2000
CVM1-CPU01-E
CVM1-CPU11-E
11-3-29 TEST–– TS
Returns, unaltered, one block of data transmitted from the host computer.
Command Format
@ x 10 1 x 10 0
T S 122 characters max.
: ↵
Node no.
Header code
Characters FCS Terminator
Response Format
@ x 10 1 x 10 0
T S 122 characters max.
: ↵
Node no.
Header code
Characters FCS Terminator
Parameters Characters (Command, Response)
For the command, this setting specifies any characters other than the carriage return (CHR$(13)). For the response, the same characters as specified by the command will be returned unaltered if the test is successful.
11-3-30 PROGRAM READ –– RP
Reads the contents of the PC user’s program area in machine language (object code). The contents are read as a block, from the beginning to the end.
Command Format
@ x 10 1 x 10 0
R P
: ↵
Node no.
Header code
FCS Terminator
Response Format
@ x 10 1 x 10 0
R P x 16 1 x 16 0 x 16 1 x 16 0 : ↵
Node no.
Header code
End code 1 byte
Program (for entire UM area)
FCS Terminator
426
Host Link Commands
Parameters
Section 11-3
Program (Response)
The program is read from the entire program area.
Note To stop this operation in progress, execute the ABORT (XZ) command.
11-3-31 PROGRAM WRITE –– WP
Writes to the PC user’s program area the machine language (object code) program transmitted from the host computer. The contents are written as a block, from the beginning.
Command Format
@ x 10 1 x 10 0 W P x 16 1 x 16 0 : ↵
Node no.
Header code
1 byte FCS Terminator
Program (Up to maximum memory size)
Response Format
Parameters Program ((Command)
Program data up to the maximum memory size.
11-3-32 I/O TABLE GENERATE –– MI
Corrects the registered I/O table to match the actual I/O table.
Command Format
@ x 10 1 x 10 0 M I
: ↵
Node no.
Header code
FCS Terminator
Response Format
@ x 10
1 x 10
0
W P x 16
1 x 16
0
Node no.
Header code
End code
: ↵
FCS Terminator
@ x 10 1 x 10 0 M I x 16 1 x 16 0
Node no.
Header code
End code
: ↵
FCS Terminator
11-3-33 COMPOUND COMMAND –– QQ
Registers at the PC all of the bits, words, and timers/counters that are to be read, and reads the status of all of them as a batch.
Registering Read Information
Register the information on all of the bits, words, and timers/counters that are to be read.
427
Host Link Commands
Command Format
Section 11-3
@ x 10 1 x 10 0 Q Q M R OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0 OP1 OP2
,
Node no.
Header code
Sub-header code
Read area Read word address
Single read information
Total read information (128 max.)
Data format
Data break
,
OP1 OP2 OP3 OP4 x 10 3 x 10 2 x 10 1 x 10 0 OP1 OP2
: ↵
Data break Read area Read word address
Single read information
Total read information (128 max.)
Data format
FCS Terminator
Response Format
@ x 10 1 x 10 0
Q Q M R x 16 1 x 16 0
Node no.
Header code
Sub-header code
End code
: ↵
FCS Terminator
Parameters
Area classification
IR or SR
LR
HR
AR
Timer
Counter
Reversible counter
DM
Read data
Bit
Word
Bit
Word
Bit
Word
Bit
Bit
Completion Flag
PV
Completion Flag
PV
Completion Flag
PV
Completion Flag
PV
Completion Flag
PV
Word
(S): Space
Read Area (Command)
Specify in four-character code the area that is to be read. The codes that can be specified are listed in the following table.
Read Word address, Data Format (Command)
Depending on the area and type of data that are to be read, the information to be read is as shown in the following table. The “read data” is specified in four digits
BCD, and the data format is specified in two digits BCD.
Read area
T I M H
C N T R
T T I M
D M (S) (S)
Read word
0000 to 0255
0000 to 0063
0000 to 0099
0000 to 0027
0000 to 0511
0000 to 0511
0000 to 0511
0000 to 0511
0000 to 0511
0000 to 6655
Data format
00 to 15 (decimal)
“CH”
00 to 15 (decimal)
“CH”
00 to 15 (decimal)
“CH”
00 to 15 (decimal)
“CH”
2 characters other than “CH”
“CH”
2 characters other than “CH”
“CH”
2 characters other than “CH”
“CH”
2 characters other than “CH”
“CH”
2 characters other than “CH”
“CH”
Any 2 characters
428
Host Link Commands
Section 11-3
Data Break (Command)
The read information is specified one item at a time separated by a break code
(,). The maximum number of items that can be specified is 128. (When the PV of a timer/counter is specified, however, the status of the Completion Flag is also returned, and must therefore be counted as two items.)
Batch Reading
The bit, word, and timer/counter status is read as a batch according to the read information that was registered with QQ.
Command Format
@ x 10 1 x 10 0
Q Q I R
: ↵
Node no.
Header code
Sub-header code
FCS Terminator
Response Format
@ x 10 1 x 10 0
Q Q
Node no.
Header code
I R x 16 1 x 16 0
ON/
OFF x 10 3 x 10 2 x 10 1 x 10 0
,
Sub-header code
End code Timer/Counter
If PV is specified the status of the Completion Flag is also returned.
Data break
,
ON/
OFF
,
Bit data
ON/OFF
, x 16 3 x 16 2 x 16 1 x 16 0 : ↵
FCS Terminator Word data
IR, SR, LR, HR,
AR, DM
Parameters Read Data (Response)
Read data is returned according to the data format and the order in which read information was registered using QQ. If “Completion Flag” has been specified, then bit data (ON or OFF) is returned. If “Word” has been specified, then word data is returned. If “PV” has been specified for timers/counters, however, then the PV is returned following the Completion Flag.
Data Break (Response)
The break code (, ) is returned between sections that are read.
11-3-34 ABORT –– XZ
Aborts the Host Link operation that is currently being processed, and then enables reception of the next command. The ABORT command does not receive a response.
Command Format
@ x 10 1 x 10 0 X Z
: ↵
Node no.
Header code
FCS Terminator
429
Host Link Commands
Section 11-3
11-3-35 INITIALIZE ––
::
Initializes the transmission control procedure of all the PCs connected to the host computer. The INITIALIZE command does not use node numbers or FCS, and does not receive a response.
Command Format
@
: : ↵
11-3-36 Undefined Command –– IC
This response is returned if the header code of a command cannot be decoded.
Check the header code.
Response Format
@ x 10 1 x 10 0
I C
: ↵
Node no.
Header code
FCS Terminator
430
Host Link Errors
Section 11-4
11-4 Host Link Errors
These error codes are received as the response code (end code) when a command received by the C200HS from a host computer cannot be processed. The error code format is as shown below.
@ X X X X X X X X
: ↵
Header code
End code FCS Terminator
The header code will vary according to the command and can contain a subcode
(for composite commands).
End code
00
01
02
0B
13
14
15
16
18
19
Contents ted.
f
Probable cause b i
N t Th d t t th t i t h already been written to the ap-
Corrective measures
Normal completion ---
Not executable in RUN mode The command that was sent cannot be executed when the PC is in
RUN mode.
Not executable in MONITOR mode The command that was sent cannot be executed when the PC is in
MONITOR mode.
Not executable in PROGRAM mode
FCS error
The command that was sent cannot be executed when the PC is in
PROGRAM mode.
The FCS is wrong. Either the FCS calculation is mistaken or there is adverse influence from noise.
Format error The command format is wrong.
Entry number data error
Command not supported
Frame length error
Not executable
---
Check the relation between the command and the PC mode.
This code is not presently being used.
Check the FCS calculation method.
If there was influence from noise, transfer the command again.
Check the format and transfer the command again.
Correct the areas and transfer the command again.
The areas for reading and writing are wrong.
The specified command does not exist.
The maximum frame length was exceeded.
Check the command code.
Divide the command into multiple frames.
Items to read not registered for composite command (QQ).
Execute QQ to register items to read before attempting batch read.
Pin 1 on C200HS DIP switch is ON. Turn OFF pin 1 to execute.
The error was generated while a Check the command data and try
23
A3
A4
User memory write-protected
Aborted due to FCS error in transmit data
Aborted due to format error in transmit data
A5
A8
Aborted due to entry number data error in transmit data
Aborted due to frame length error in transmit data
Other --Influence from noise was received.
Transfer the command again.
Power Interruptions
Node no.
The following responses may be received from the C200HS if a power interruption occurs, including momentary interruptions. If any of these responses are received during or after a power interruption, repeat the command.
Undefined Command Response
@00IC4A*
↵
No Response
If no response is received, abort the last command and resend.
431
Appendix A
Standard Models
C200HS Racks
I/O R k
Slave
R k
Name
CPU Rack CPU
Memory Cassette l
Remote I/O Slave
Specifications
10 slots
8 slots
5 slots
3 slots
100 to 120/200 to 240 VAC w/built-in power supply
–––
Conforms to EC directives (see note)
Model number
C200H-BC101-V2
C200H-BC081-V2
C200H-BC051-V2
C200H-BC031-V2
C200HS-CPU01-E
C200HS-CPU01-EC
24 VDC w/built-in power supply
RS-232C port
RS-232C port and conforms to EC directives
RS-232C port and
SYSMAC NET/
SYSMAC LINK supported
Conforms to EC directives (see note)
RS-232C port
RS-232C port and
SYSMAC NET/
SYSMAC LINK supported
C200HS-CPU21-E
C200HS-CPU21-EC
C200HS-CPU31-E
C200HS-CPU03-E
C200HS-CPU23-E
C200HS-CPU33-E
EPROM Chip; 27256; 150 ns ROM-JD-B
EPROM Chip; 27512; 150 ns
EEPROM; 16K words
EPROM; 16K words
100 to 120/200 to 240 VAC (switchable)
Conforms to EC directives
24 VDC Conforms to EC directives (see note)
30 cm
70 cm
2 m
5 m
10 m
100 to 120/200 to 240 VAC (switchable)
24 VDC
100 to 120/200 to 240 VAC (switchable)
Conforms to EC directives
24 VDC
ROM-KD-B
C200HS-ME16K
C200HS-MP16K
C200H-PS221
C200H-PS221-C
C200H-PS211
C200H-CN311
C200H-CN711
C200H-CN221
C200H-CN521
APF/
C200H-CN131
C200H-RT001-P
C200H-RT002-P
Wired C200H-RT201
C200H-RT201-C
C200H-RT202
Note: Units with lot numbers jj
Z5 (Dec. 1995) or later.
433
Standard Models Appendix A
C200H Standard I/O Units
Input Units
Output Units
Name
AC Input Unit
DC Input Unit
AC/DC Input Unit
Interrupt Input Unit
Relay Output Unit
Triac Output Unit
Analog Timer Unit
1
8 pts
16 pts
8 pts
16 pts
8 pts
8 pts
8 pts
16 pts
8 pts
16 pts
8 pts
8 pts
12 pts
16 pts
5 pts
8 pts
12 pts
16 pts
8 pts
8 pts
8 pts
8 pts
12 pts
12 pts
8 pts
12 pts
16 pts
8 pts
8 pts
8 pts
12 pts
16 pts
4 timers
Specifications
100 to 120 VAC
100 to 120 VAC
200 to 240 VAC
200 to 240 VAC
No-voltage contact; NPN
No-voltage contact; PNP
12 to 24 VDC
24 VDC
12 to 24 VAC/DC
24 VAC/DC
12 to 24 VDC
2 A, 250 VAC/24 VDC (For resistive loads)
2 A, 250 VAC/24 VDC (For resistive loads)
2 A, 250 VAC/24 VAC (For resistive loads)
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
2 A, 250 VAC/24 VDC (For resistive loads)
2 A, 250 VAC/24 VDC (For resistive loads)
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
1 A, 120 VAC
1.2 A, 120 VAC
1 A, 200 VAC
0.3 A, 250 VAC
0.5 A, 250 VAC
1 A, 12 to 48 VDC
0.3 A, 24 VDC
0.3 A, 24 VDC
2.1 A, 24 VDC
0.8 A, 24 VDC; source type (PNP); with load short protection
5 to 24 VDC; source type (PNP)
5 to 24 VDC; source type (PNP)
1.0 A, 24 VDC; source type (PNP); with load short protection
0.1 to 1 s/1 to 10 s/10 to 60 s/1 min to 10 min
(switchable)
Model number
C200H-IA121
C200H-IA122/122V
C200H-IA221
C200H-IA222/222V
C200H-ID001
C200H-ID002
C200H-ID211
C200H-ID212
C200H-IM211
C200H-IM212
C200HS-INT01
C200H-OC221
C200H-OC222
C200H-OC225
2, 3
C200H-OC223
C200H-OC224
C200H-OC222V
C200H-OC226
C200H-OC224V
C200H-OA121-E
C200H-OA122-E
C200H-OA221
C200H-OA222V
C200H-OA224
C200H-OD411
C200H-OD211
C200H-OD212 2
C200H-OD213
C200H-OD214
C200H-OD216
C200H-OD217
C200H-OD21A
C200H-TM001
Variable Resistor
Connector
Standard B7A Interface Units
Connector w/lead wire (2 m) for 1 external resistor C4K-CN223
16 input pts
16 output pts
Connects to B7A Link Terminals.
C200H-B7AI1
C200H-B7AO1
Note 1. If the Interrupt Input Unit is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Interrupt Input Unit will be treated as an ordinary 8-point Input Unit. Moreover, Interrupt Input Units cannot be used on
Slave Racks. In addition, Interrupt Input Units require that a version 2 (i.e., model numbers with a “-V2” suffix) Backplane be used at the CPU Rack. If an earlier version Backplane is mounted, the interrupt function cannot be used.
2. Transistor Output Unit C200H-OD212 and Contact Output Unit C200H-OC225 must be mounted to either a C200H-
BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2, or C200H-BC101-V1/V2 Backplane.
3. The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously.
434
Standard Models
C200H Group-2 High-density I/O Units
Name Specifications
24 VDC
24 VDC
Transistor Output Unit p
64 pts.
16 mA 4.5 VDC to 100 mA 26.4 VDC
0.5 A (5A/Unit) 24 VDC
16 mA 4.5 VDC to 100 mA 26.4 VDC
C200H Group-2 B7A Interface Units
Name
Group-2 B7A Interface Units 32 input pts
Specifications
Connects to B7A Link
T i l
32 output pts
16 input pts and 16 output points
32 input pts and 32 output points
Appendix A
Model number
C200H-ID216
C200H-ID218
C200H-ID217
C200H-ID219
C200H-OD218
C200H-OD21B
C200H-OD219
Model number
C200H-B7A12
C200H-B7A02
C200H-B7A21
C200H-B7A22
C200H Special I/O Units
All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit.
i I/O
Name
DC Input Unit 32 pts
32 pts
Transistor
Output Unit
32 pts
32 pts
DC Input/
Transistor
Output Unit
Analog
Output Unit
Temperature Sensor Unit
Specifications
5 VDC (TTL inputs); with high-speed input function
24 VDC; with high-speed inputs
0.1 A, 24 VDC (usable as 128-point dynamic output unit)
16 input/
16 output pts
16 input/
16 output pts
35 mA, 5 VDC (TTL outputs) (usable as 128-point dynamic output unit)
12-VDC inputs; with high-speed input function
0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit)
24-VDC inputs; with high-speed input function
0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit)
16 input/
16 output pts
5 VDC (TTL inputs); with high speed input function 35 mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)
4 to 20 mA, 1 to 5/0 to 10 V (switchable); 4 inputs
4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V (switchable); 8 inputs
4 to 20 mA, 1 to 5/0 to 10 V (switchable); 2 outputs
Model number
C200H-ID501
C200H-ID215
C200H-OD215
C200H-OD501
C200H-MD115
C200H-MD215
C200H-MD501
C200H-AD001
C200H-AD002
C200H-DA001
Temperature Control Unit
Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs
Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs
Platinum resistance thermometer (JPt) (switchable), DIN standards;
4 inputs
Platinum resistance thermometer (Pt) (switchable); 4 inputs
ThermocouTransistor output
Pt resis-
Voltage output
Current output
Transistor output
C200H-TS001
C200H-TS002
C200H-TS101
C200H-TS102
C200H-TC001
C200H-TC002
C200H-TC003
C200H-TC101 mometer Voltage output
Current output
C200H-TC102
C200H-TC103
435
Standard Models Appendix A
Name
Heat/Cool Temperature
Control Unit
Thermocou-
Specifications
Transistor output
Model number
C200H-TV001
PID Control Unit
Position Control Unit
Cam Positioner Unit
High-speed Counter Unit
ASCII Unit
I/D Sensor Unit
Read/Write
H d
Data Carrier
( )
Voice Unit
Connecting
Cable
Fuzzy Logic Unit
Fuzzy
Support
Software
Pt resis-
Voltage output
Current output
Transistor output mometer
Voltage output
Current output
Transistor output
Voltage output
Current output
1 axis
1 axis
Pulse output; speeds: 1 to 99,990 pps
Directly connectable to servomotor driver; compatible with line driver; speeds: 1 to 250,000 pps
2 axis 1 to 250000. pps. 53 pts per axis
Detects angles of rotation by means of a resolver and provides ON and
OFF outputs at specified angles. A maximum of 48 cam outputs (16 external outputs and 32 internal outputs) maximum are available.
1 axis Pulse input; counting speed: 50 kcps;
5 VDC/12 VDC/24 VDC
1 axis Pulse input; counting speed: 75 kcps;
RS-422 line driver
EEPROM
Local application, electromagnetic coupling
Remote application, microwave transmissions
Electromagnetic type
Microwave type
SRAM type for V600-H series.
EEPROM type for V600-H series.
60 messages max.; message length: 32, 48, or 64 s (switchable)
RS-232C
Up to 8 inputs and 4 outputs. (I/O to and from specified data area words)
Available on either 3.5” or 5.25” floppy disks.
C200H-TV002
C200H-TV003
C200H-TV101
C200H-TV102
C200H-TV103
C200H-PID01
C200H-PID02
C200H-PID03
C200H-NC111
C200H-NC112
C200H-NC211
C200H-CP114
C200H-CT001-V1
C200H-CT002
C200H-ASC02
C200H-IDS01-V1
C200H-IDS21
V600-H series
V620-H series
V600-D jj R jj
V600-D jj P jj
C200H-OV001
C200H-CN224
C200H-FZ001
C500-SU981-E
Note For Read/Write Head and Data Carrier combinations, refer to the V600 FA ID System R/W Heads and EE-
PROM Data Carriers Operation Manual and Supplement or V600 FA ID System R/W Heads and SRAM
Data Carriers Operation Manual and Supplement.
C200H Link Units
Name
Host Link Unit Rack-mounting
Specifications
C200H only
PC Link Unit
Remote I/O Master Unit
Multilevel
Up to two per PC; connectable to up to 5
Slaves per PC total
APF/PCF
RS-422
RS-232C
RS-485
APF/PCF
Wired
Model number
C200H-LK101-PV1
C200H-LK202-V1
C200H-LK201-V1
C200H-LK401
C200H-RM001-PV1
C200H-RM201
436
Standard Models Appendix A
SYSMAC LINK Unit/SYSMAC NET Link Unit
The SYSMAC LINK Units and SYSMAC NET Link Unit can only be used with the C200HS-CPU31-E and C200HS-
CPU33-E CPUs.
Name
SYSMAC LINK Unit
Specifications
Wired via coaxial cable.
Bus Connection Unit required separately. One
C1000H-CE001 F Adapter included.
Wired via optical fiber cable.
Bus Connection Unit required separately. An Optical Fiber
Cable Bracket must be used to support an optical cable connected to the SYSMAC LINK Unit.
One required for each node at ends of System
Model number
C200HS-SLK22
C200HS-SLK12
Terminator
Attachment Stirrup
F Adapter
F Adapter Cover
Communications
Provided with SYSMAC LINK Unit
---
---
Coaxial cables Manufactured by Hitachi
C1000H-TER01
C200H-TL001
C1000H-CE001
C1000H-COV01
ECXF5C-2V
Auxiliary Power Supply Unit
SYSMAC NET Link Unit er
Power Cable
Bus Connection Unit
Manufactured by Fujigura
Supplies backup power to either one or two SYSMAC LINK
Units. One C200H-CN111 Power Connecting Cable included.
5C-2V
C200H-APS03
Bus Connection Unit required separately. An Optical Fiber
Cable Bracket must be used to support an optical cable connected to the SYSMAC NET Link Unit.
p q
S l pp y g p For 1 Unit
C200HS-SNT32
C200H-APS01
For 2 Units C200H-APS02
For 1 Unit C200H-CN111
For 2 Units C200H-CN211
Connects SYSMAC LINK Unit or SYSMAC
NET Li k U i C200HS CPU31 E/CPU33 E
For 1 Unit
For 2 Units
C200H-CE001
C200H-CE002
Optional Products
Name
I/O Unit Cover
Terminal Block Cover
Connector Cover
Space Unit
Battery Set
Relay
Specifications
Cover for 10-pin terminal block
Short protection for 10-pin terminal block
Short protection for 19-pin terminal block
Protective cover for unused I/O Connecting Cable connectors
Used for vacant slots
For C200H RAM Memory Unit only
24 VDC
Backplane Insulation Plate For 10-slot Backplane
For 8-slot Backplane
For 5-slot Backplane
Model number
C200H-COV11
C200H-COV02
C200H-COV03
C500-COV02
C200H-SP001
C200H-BAT09
G6B-1174P-FD-US DC24
C200H-ATTA1
C200H-ATT81
C200H-ATT51
I/O Bracket
For 3-slot Backplane
For 10-slot Backplane
For 8-slot Backplane
For 5-slot Backplane
For 3-slot Backplane
C200H-ATT31
C200H-ATTA3
C200H-ATT83
C200H-ATT53
C200H-ATT33
Note 1. When ordering, specify the model name (any component of which is not sold separately).
2. Order the press-fit tool from the manufacturer.
437
Standard Models
Mounting Rails and Accessories
Name Specifications
DIN Track Mounting Bracket 1 set (2 included)
DIN Track Length: 50 cm; height: 7.3 mm
End Plate
Spacer
Length: 1 m; height: 7.3 mm
Length: 1 m; height: 16 mm
---
---
Appendix A
Model number
C200H-DIN01
PFP-50N
PFP-100N
PFP-100N2
PFP-M
PFP-S
Link Adapters
Name
Link Adapter
Specifications Model number
3 RS-422 connectors
3 optical connectors (APF/PCF)
3 optical connectors (PCF)
1 connector each for APF/PCF, RS-422, and RS-232C
1 connector each for PCF, RS-422, and RS-232C
3G2A9-AL001
3G2A9-AL002-PE
3G2A9-AL002-E
3G2A9-AL004-PE
3G2A9-AL004-E
1 connector each for APF/PCF and APF
1 connector each for PCF and AGF
1 connector for APF/PCF; 2 for AGF
3G2A9-AL005-PE
3G2A9-AL005-E
3G2A9-AL006-PE
1 connector for PCF; 2 for AGF 3G2A9-AL006-E
O/E converter; 1 connector for RS-485, 1 connector each for APF/PCF B500-AL007-PE
Used for on-line removal of SYSMAC NET Link Units from the SYSMAC
NET Link System, SYSMAC NET Optical Link Adapter 3 connectors for
APF/PCF.
B700-AL001
SYSMAC BUS/SYSMAC WAY Optical Fiber Products
Plastic Clad Optical Fiber Cable/All Plastic Optical Fiber Cable
Name
Plastic Clad Optical Fiber Cable
All Plastic Optical Fiber Cable
Optical Connectors A
Optical Connectors B
Specifications
0.1 m, w/connectors
1 m, w/connectors
2 m, w/connectors
3 m, w/connectors
5 m, w/connectors
Ambient temp:
–10 ° to 70 ° C
10 m, w/connectors
20 m, w/connectors
30 m, w/connectors
40 m, w/connectors
50 m, w/connectors
Cable only; order desired length between 1 and 200 m in increments of 1 m.
Cable only; order desired length in 5 m increments between
5 and 100 m, or in increments of 200 m or 500 m.
Two optical connectors (brown) for APF (10 m max.)
Two optical connectors (black) for APF (8 to 20 m)
Model number
3G5A2-OF011
3G5A2-OF101
3G5A2-OF201
3G5A2-OF301
3G5A2-OF501
3G5A2-OF111
3G5A2-OF211
3G5A2-OF311
3G5A2-OF411
3G5A2-OF511
B500-OF002
B500-PF002
3G5A2-CO001
3G5A2-CO002
438
Standard Models Appendix A
Name Specifications
All Plastic Optical Fiber Cable Set 1-m cable with an Optical Connector A connected to each end
Optical Fiber Processing Kit Accessory: 125-mm nipper (Muromoto Tekko’s 550M) for
APF
Model number
3G5A2-PF101
3G2A9-TL101
H-PCF
Name
Optical Fiber Cable
Optical Fiber Cable Connector
Specifications
10 m, black
50 m, black
100 m, black
500 m, black
1000 m, black
10 m, orange
50 m, orange
100 m, orange
500 m, orange
1000 m, orange
10 m, black
50 m, black
100 m, black
500 m, black
1000 m, black
SYSMAC BUS:
C200H-RM001-PV1
C200H-RT001/RT002-P
C500-RM001-(P)V1
C500-RT001/RT002-(P)V1
B500jjj (-P)
Two-core cable
Two-core cable
Half-lock connector for Remote I/O Master, Remote I/O
Slave, Host Link
Unit, and Link
Adapter
Model number
S3200-HCCB101
S3200-HCCB501
S3200-HCCB102
S3200-HCCB502
S3200-HCCB103
S3200-HCCO101
S3200-HCCO501
S3200-HCCO102
S3200-HCCO502
S3200-HCCO103
S3200-HBCB101
S3200-HBCB501
S3200-HBCB102
S3200-HBCB502
S3200-HBCB103
S3200-COCH82
Note 1. Optical fiber cables must be prepared and connected by specialists.
2. If the user prepares and connects optical fiber cables, the user must take a seminar held under the auspices of Sumitomo Electric Industries, Ltd. and obtain a proper certificate.
3. The Optical Power Tester, Head Unit, Master Fiber Set, and Optical Fiber Assembling Tool are required to connect optical fiber cables.
Optical Fiber Assembling Tool
Name
Optical Fiber Assembling Tool
Specifications
Used to connect H-PCF and crimp-cut connectors for optical transmission systems such as the SYSMAC C- and
CV-series SYSMAC BUS, SYSMAC LINK and SYSMAC
NET.
Model number
S3200-CAK1062
Note 1. Optical fiber cables must be prepared and connected by specialists.
2. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables.
439
Standard Models Appendix A
Optical Power Tester
Name
Optical Power Tester (see note)
(provided with a connector adapter, light source unit, small single-head plug, hard case, and AC adapter)
Specifications
SYSMAC BUS:
C200H-RM001-PV1
C200H-RT001/RT002-P
C500-RM001-(P)V1
C500-RT001/RT002-(P)V1
Head Unit
S3200-CAT2822
(provided with the
Tester)
Model number
S3200-CAT2820
Note: There is no difference between the light source unit and connector adapter for the Head Unit and those for the Optical Power Tester.
Head Unit
Name
Head Unit (a set consisting of light source unit and connector adapter)
(see note)
Specifications
SYSMAC BUS:
C200H-RM001-PV1
C200H-RT001/RT002-P
SYSMAC NET:
S3200-LSU03-V1/LSU03-01E
C500-SNT31-V4
3G8FX-TM111
3G8SX-TM111
Model number
S3200-CAT2822
S3200-CAT3202
Note: Use a proper Head Unit model for the optical module to be used. If two types of optical modules (unit type and board type) are used, order an Optical Power Tester plus a proper Head Unit model.
Master Fiber Set
Name
Master Fiber Set (1 m)
Specifications
S3200-CAT3202 (SYSMAC NET, NSB, NSU, Bridge)
S3200-CAT2002/CAT2702 (SYSMAC NET, SYSMAC
LINK)
S3200-CAT2822 (SYSMAC BUS)
Model number
S3200-CAT3201
S3200-CAT2001H
S3200-CAT2821
Note 1. The Master Fiber Set is used in combination with the Optical Power Tester to check the optical levels of optical fiber cables connected to optical fiber cable connectors.
2. Optical fiber cables must be prepared and connected by specialists.
3. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables.
SYSMAC LINK/SYSMAC NET Link Optical Fiber Products
Optical Fiber Cables for SYSMAC LINK and SYSMAC NET Link Systems
Use hard-plastic-clad quartz optical fiber (H-PCF) cables for SYSMAC LINK and SYSMAC NET Link Systems.
H-PCF cables are available with connectors already attached, or cables and connectors can be purchased separately and assembled by the user. Refer to the System Manual for the SYSMAC LINK or SYSMAC NET Link Systems for assembly procedures. Models numbers for H-PCF cables with connecters attached are provided in the following illustration.
Model Numbers for H-PCF Cables with Connectors
S3200-CN jjj
jj
jj
Cable length
201:
501:
102:
2 m
5 m
10 m
152:
202:
15 m
20 m
Blank: Over 20 m
(Specify.)
Connectors
20-25: Full-lock connector on one end, half-lock connector on other end.
25-25: Half-lock connectors on both ends.
440
Standard Models Appendix A
An Optical Fiber Cable Bracket must be used to support an optical fiber cable connected to the C200HS-SNT32
SYSMAC NET Link Unit or C200HS-SLK12 SYSMAC LINK Unit.
User optical fiber cables with both tension members and power supply lines.
The following half-lock connector is used and connects to the C200HS SYSMAC LINK and SYSMAC NET Link
Units: S3200-COCF2511.
The following full-lock connector is used and connects to the CV500 SYSMAC LINK and SYSMAC NET Link Units and the C1000H SYSMAC LINK Unit: S3200-COCF2011. This full-lock connector cannot be connected to the
C200HS SYSMAC LINK and SYSMAC NET Link Units.
The above connectors cannot be used for the C500 SYSMAC NET Link Unit, cable relays, and the SYSMAC NET
Link Network Service Board. Refer to the SYSMAC NET Link System Manual for further information.
Programming Devices
Name
Programming Console
Specifications
Hand-held, w/backlight; requires the C200H-CN222 or
C200H-CN422, see below
2-m Connecting Cable attached.
Model number
C200H-PR027-E
CQM1-PRO01-E
Used to attach Hand-held Programming Console to a panel.
C200H-ATT01 Programming Console
Mounting Bracket ti C bl
Data Setting Console
Data Setting Console
Connecting Cable
Ladder Support Software (LSS)
Name
Ladder Support Software (for
C20, C
C jj jj
C
P, C jj
C
K, C120,
H, C200H, C200HS, C500,
C1000H, C2000H, and CQM1)
For Hand-held Programming Console 2 m
4 m
Used for data input and process value display for the
C200H-TC jjj , C200H-TV jjj , C200H-CP114, and
C200H-PID0 j .
For C200H-DSC01 2 m
4 m
Used to connect an IBM PC/AT or compatible to the C200HS.
3.3 m
Specifications
5.25”, 2D for IBM PC/AT compatible
3.5”, 2HD for IBM PC/AT compatible
C200H-CN222
C200H-CN422
C200H-DSC01
C200H-CN225
C200H-CN425
CQM1-CIF02
Model number
C500-SF711-EV3
C500-SF312-EV3
SYSMAC Support Software (SSS)
Product
SYSMAC Support Software
Description
3.5”, 2HD for IBM PC/AT compatible
Model no.
C500-ZL3AT1-E
Training Materials
Name
SYSMAC Training System
Fuzzy Training System
Specifications
Includes text book, cassette tape, and input switch board.
Includes a Fuzzy Training System Manual, a Main Unit, a C200H-MR831 Memory Unit, a C200H-PRO27-E
Programming Console, a C200H-CN222 Cable for the
Programming Console, C500-SU381-E Fuzzy Training
Software, an RS-232C Cable, and a carrying belt.
Model number
C200H-ETL01-E
C200H-ETL13-E
441
Appendix B
Programming Instructions
A PC instruction is input either by pressing the corresponding Programming Console key(s) (e.g., LD, AND, OR,
NOT) or by using function codes. To input an instruction with its function code, press FUN, the function code, and then WRITE. Refer to the pages listed programming and instruction details.
—
Code Mnemonic
AND
—
—
—
—
—
—
—
—
—
—
—
—
—
00
01
02
AND
AND LD AND LOAD
AND NOT AND NOT
CNT
LD
LD NOT
OR
OR LD
OR NOT
OUT
COUNTER
LOAD
OUTPUT
OUT NOT OUTPUT NOT
RSET
SET
TIM
NOP
END
IL
RESET
SET
Name
LOAD NOT
OR
OR LOAD
OR NOT
TIMER
NO OPERATION
END
INTERLOCK
Function
Logically ANDs status of designated bit with execution condition.
Logically ANDs results of preceding blocks.
Logically ANDs inverse of designated bit with execution condition.
A decrementing counter.
Used to start instruction line with the status of the designated bit or to define a logic block for use with AND LD and OR LD.
Page
129
130
129
145
129
Used to start instruction line with inverse of designated bit.
129
Logically ORs status of designated bit with execution condition.
Logically ORs results of preceding blocks.
129
130
Logically ORs inverse of designated bit with execution condition.
Turns ON operand bit for ON execution condition; turns
OFF operand bit for OFF execution condition.
Turns operand bit OFF for ON execution condition; turns operand bit ON for OFF execution condition (i.e., inverts operation).
129
130
130
133 Turns the operand bit OFF when the execution condition is
ON, and does not affect the status of the operand bit when the execution condition is OFF.
Turns the operand bit ON when the execution condition is
ON, and does not affect the status of the operand bit when the execution condition is OFF.
ON-delay (decrementing) timer operation.
Nothing is executed and program moves to next instruction.
Required at the end of the program.
If interlock condition is OFF, all outputs are turned OFF
133
139
138
138
135
03
04
05
(@)06
07
08
09
10
11
12
ILC
JMP
JME
FAL
FALS
STEP
SNXT
SFT
KEEP
CNTR
INTERLOCK CLEAR
JUMP
JUMP END
FAILURE ALARM
AND RESET
SEVERE FAILURE
ALARM
STEP DEFINE
STEP START
SHIFT REGISTER
KEEP
REVERSIBLE
COUNTER
ILC(03). Other instructions are treated as NOP; counter
PVs are maintained.
135 di JME(05) i d
137
137
275 Generates a non-fatal error and outputs the designated
FAL number to the Programming Console.
Generates a fatal error and outputs the designated FALS number to the Programming Console.
When used with a control bit, defines the start of a new step and resets the previous step. When used without N, defines the end of step execution.
275
266
Used with a control bit to indicate the end of the step, reset the step, and start the next step.
Creates a bit shift register.
266
150
Defines a bit as a latch controlled by set and reset inputs.
133
Increases or decreases PV by one whenever the increment input or decrement input signals, respectively, go from OFF to ON.
148
443
Programming Instructions Appendix B
13
14
15
Code
(@)16
Mnemonic
DIFU
DIFD
TIMH
WSFT
Name Function
DIFFERENTIATE UP Turns ON the designated bit for one cycle on the rising edge of the input signal.
DIFFERENTIATE
DOWN
Turns ON the bit for one cycle on the trailing edge.
HIGH-SPEED TIMER A high-speed, ON-delay (decrementing) timer.
WORD SHIFT Shifts data between starting and ending words in word units, writing zeros into starting word.
17 to 19 For expansion instructions.
20 CMP COMPARE
(@)21
(@)22
(@)23
(@)24
MOV
MVN
BIN
BCD
MOVE
MOVE NOT
BCD TO BINARY
BINARY TO BCD
Page
131
131
143
157
Compares the contents of two words and outputs result to
GR, EQ, and LE Flags.
170
Copies source data (word or constant) to destination word.
159
159 Inverts source data (word or constant) and then copies it to destination word.
Converts four-digit, BCD data in source word into 16-bit binary data, and outputs converted data to result word.
Converts binary data in source word into BCD, and outputs converted data to result word.
180
181
(@)25 ASL Shifts each bit in single word of data one bit to left, with CY.
154
(@)26
(@)27
(@)28
(@)29
(@)30
(@)31
(@)32
(@)33
(@)34
(@)35
ASR
ROL
ROR
COM
ADD
SUB
MUL
DIV
ANDW
ORW
ARITHMETIC SHIFT
LEFT
ARITHMETIC SHIFT
RIGHT
ROTATE LEFT
ROTATE RIGHT
COMPLEMENT
BCD ADD
BCD SUBTRACT
BCD MULTIPLY
BCD DIVIDE
LOGICAL AND
LOGICAL OR
Shifts each bit in single word of data one bit to right, with
CY.
Rotates bits in single word of data one bit to left, with CY.
154
Adds two four-digit BCD values and content of CY, and outputs result to specified result word.
155
Rotates bits in single word of data one bit to right, with CY.
155
Inverts bit status of one word of data.
249
205
Subtracts a four-digit BCD value and CY from another four-digit BCD value and outputs result to the result word.
Multiplies two four-digit BCD values and outputs result to specified result words.
Divides four-digit BCD dividend by four-digit BCD divisor and outputs result to specified result words.
Logically ANDs two 16-bit input words and sets corresponding bit in result word if corresponding bits in input words are both ON.
Logically ORs two 16-bit input words and sets corresponding bit in result word if one or both of corresponding bits in input data are ON.
207
211
212
250
251
(@)36
(@)37
XORW
XNRW
INC
DEC
STC
EXCLUSIVE OR
EXCLUSIVE NOR
BCD INCREMENT
BCD DECREMENT
SET CARRY
Exclusively ORs two 16-bit input words and sets bit in result word when corresponding bits in input words differ in status.
Exclusively NORs two 16-bit input words and sets bit in result word when corresponding bits in input words are same in status.
Increments four-digit BCD word by one.
(@)38
(@)39
(@)40
Decrements four-digit BCD word by one.
Sets carry flag (i.e., turns CY ON).
(@)41
45
CLC
TRSM
CLEAR CARRY
TRACE MEMORY
SAMPLE
MESSAGE
Clears carry flag (i.e, turns CY OFF).
Initiates data tracing.
(@)46 MSG Displays a 16-character message on the Programming
Console display.
47 & 48 For expansion instructions.
(@)50
(@)51
ADB
SBB
BINARY ADD Adds two four-digit hexadecimal values and content of CY, and outputs result to specified result word.
BINARY SUBTRACT Subtracts a four-digit hexadecimal value and CY from another four-digit hexadecimal value and outputs result to the result word.
252
253
204
204
205
205
277
278
219
221
444
Programming Instructions Appendix B
Code
(@)52
(@)53
(@)54
(@)55
(@)56
(@)57
(@)58
(@)59
Mnemonic
MLB
DVB
ADDL
SUBL
MULL
DIVL
BINL
BCDL
Name
BINARY MULTIPLY
BINARY DIVIDE
DOUBLE BCD ADD
DOUBLE BCD
SUBTRACT
DOUBLE BCD
MULTIPLY
DOUBLE BCD
DIVIDE
DOUBLE BCD TO
DOUBLE BINARY
DOUBLE BINARY TO
DOUBLE BCD
Function
Multiplies two four-digit hexadecimal values and outputs result to specified result words.
Divides four-digit hexadecimal dividend by four-digit hexadecimal divisor and outputs result to specified result words.
Adds two eight-digit values (2 words each) and content of
CY, and outputs result to specified result words.
Subtracts an eight-digit BCD value and CY from another eight-digit BCD value and outputs result to the result words.
Multiplies two eight-digit BCD values and outputs result to specified result words.
Divides eight-digit BCD dividend by eight-digit BCD divisor and outputs result to specified result words.
Converts BCD value in two consecutive source words into binary and outputs converted data to two consecutive result words.
Converts binary value in two consecutive source words into BCD and outputs converted data to two consecutive result words.
60 to 69 For expansion instructions.
(@)70
(@)71
(@)72
(@)73
(@)74
(@)75
(@)76
(@)77
(@)78
(@)79
(@)80
(@)81
(@)82
(@)83
(@)84
(@)85
XFER
BSET
ROOT
XCHG
SLD
SRD
MLPX
DMPX
SDEC
FDIV
DIST
COLL
MOVB
MOVD
SFTR
TCMP
BLOCK TRANSFER
BLOCK SET
SQUARE ROOT
Moves content of several consecutive source words to consecutive destination words.
Copies content of one word or constant to several consecutive words.
Computes square root of eight-digit BCD value and outputs truncated four-digit integer result to specified result word.
DATA EXCHANGE
ONE DIGIT SHIFT
LEFT
ONE DIGIT SHIFT
RIGHT
Right shifts data between starting and ending words by one digit (four bits).
8-TO-256 DECODER Converts up to four hexadecimal digits in source word into decimal values from 0 to 15 and turns ON, in result word(s), bit(s) whose position corresponds to converted value.
Can also convert up to eight hexadecimal digits and turn
ON corresponding bits in result words R to R+15.
256-TO-8 ENCODER Determines position of highest ON bit in source word(s) and writes the ON bit’s position (0 to F) to digit(s) in R.
Can also determine the position of the highest ON bit in one or two groups of 16 words (S to S+15, S+16 to S+31) and writes the ON bit’s position (00 to FF) to byte(s) in R.
7-SEGMENT
DECODER
FLOATING POINT
DIVIDE
SINGLE WORD
DISTRIBUTE
DATA COLLECT
MOVE BIT
MOVE DIGIT
Exchanges contents of two different words.
Left shifts data between starting and ending words by one digit (four bits).
Converts hexadecimal values from source word to data for seven-segment display.
Divides one floating point value (Dd+1, Dd) by another
(Dr+1, Dr) and outputs the result to R+1 and R.
Moves one word of source data to destination word whose address is given by destination base word plus offset.
Extracts data from source word and writes it to destination word.
Transfers designated bit of source word or constant to designated bit of destination word.
Moves hexadecimal content of specified four-bit source digit(s) to specified destination digit(s) for up to four digits.
REVERSIBLE SHIFT
REGISTER
TABLE COMPARE
Shifts data in specified word or series of words to either left or right.
Compares four-digit hexadecimal value with values in table consisting of 16 words.
Page
224
224
206
209
212
213
181
182
161
160
217
162
156
156
185
188
191
214
162
164
166
167
152
175
445
Programming Instructions Appendix B
Code
(@)86
Mnemonic
ASC
Name
ASCII CONVERT
Function
Converts hexadecimal values from the source word to eight-bit ASCII code starting at leftmost or rightmost half of starting destination word.
Page
194
87 to 89 For expansion instructions.
(@)90
(@)91
92
93
(@)94
(@)97
(@)98
(@)99
SEND
SBS
SBN
RET
WDT
IORF
RECV
MCRO
NETWORK SEND Used for communications with other PCs linked through the SYSMAC NET Link System or SYSMAC LINK System.
(CPU31-E/33-E only)
291
SUBROUTINE
ENTRY
SUBROUTINE
DEFINE
RETURN
Calls and executes subroutine N.
Marks start of subroutine N.
257
259
Marks the end of a subroutine and returns control to main program.
Increases the watchdog timer PV by 0 to 6300 ms.
259
WATCHDOG TIMER
REFRESH
I/O REFRESH
281
NETWORK RECEIVE
Refreshes all I/O words between the start and end words.
281
Used for communications with other PCs linked through the SYSMAC NET Link System or SYSMAC LINK System.
(CPU31-E/33-E only)
293
MACRO Calls and executes a subroutine replacing I/O words.
260
Expansion Instructions
The following table shows the instructions that can be treated as expansion instructions. The default function codes are given for instructions that have codes assigned by default.
65
66
67
17
18
19
Code Mnemonic
(@)ASFT
Name
ASYNCHRONOUS SHIFT
REGISTER
Function
Creates a shift register that exchanges the contents of adjacent words when one of the words is zero and the other is not.
(@)SCAN CYCLE TIME Sets the minimum cycle time (0 to 999.0 s).
(@)MCMP MULTI-WORD COMPARE Compares a block of 16 consecutive words to another block of 16 consecutive words.
47
48
(@)LMSG 32-CHARACTER MES-
SAGE
(@)TERM TERMINAL MODE
Outputs a 32-character message to the Programming
Console.
Switches the Programming Console to TERMINAL mode for the normal keyboard mapping operation.
60
61
62
63
64
CMPL DOUBLE COMPARE
(@)MPRF GROUP-2 HIGH-DEN-
SITY I/O REFRESH
(@)XFRB TRANSFER BITS
(@)LINE
(@)COLM
COLUMN TO LINE
LINE TO COLUMN
Compares two eight-digit hexadecimal values.
Refreshes I/O words allocated to Group-2 High-density
I/O Units.
Copies the status of up to 255 specified source bits to the specified destination bits.
Copies a bit column from 16 consecutive words to the specified word.
Copies the 16 bits from the specified word to a bit column of 16 consecutive words.
68
69
87
88
(@)SEC
(@)HMS
HOURS TO SECONDS
SECONDS TO HOURS
(@)BCNT BIT COUNTER
(@)BCMP
(@)APR
TTIM
ZCP
BLOCK COMPARE
Converts hour and minute data to second data.
Converts second data to hour and minute data.
Counts the total number of bits that are ON in the specified block of words.
Judges whether the value of a word is within 16 ranges
(defined by lower and upper limits).
ARITHMETIC PROCESS Performs sine, cosine, or linear approximation calculations.
TOTALIZING TIMER Creates a totalizing timer.
AREA RANGE COMPARE Compares a word to a range defined by lower and upper limits and outputs the result to the GR, EQ, and
LE flags.
Page
157
276
169
279
280
172
282
168
200
201
183
184
283
174
239
144
176
446
Programming Instructions Appendix B
---
---
---
89
Code
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Mnemonic
(@)INT
7SEG 7-SEGMENT DISPLAY
OUTPUT
(@)ADBL DOUBLE BINARY ADD
AVG
Name
INTERRUPT CONTROL
AVERAGE VALUE
Function
Performs interrupt control, such as masking and unmasking the interrupt bits for I/O interrupts.
Converts 4- or 8-digit BCD data to 7-segment display format and then outputs the converted data.
Adds two 8-digit binary values (normal or signed data) and outputs the result to R and R+1.
Adds the specified number of hexadecimal words and computes the mean value. Rounds off to 4 digits past the decimal point.
Compares two 16-bit (4-digit) signed binary values and outputs the result to the GR, EQ, and LE flags.
Page
262
301
225
235
CPS SIGNED BINARY
COMPARE
178
CPSL
(@)DBS
DOUBLE SIGNED
BINARY COMPARE
Compares two 32-bit (8-digit) signed binary values and outputs the result to the GR, EQ, and LE flags.
SIGNED BINARY DIVIDE Divides one 16-bit signed binary value by another and outputs the 32-bit signed binary result to R+1 and R.
(@)DBSL DOUBLE SIGNED
BINARY DIVIDE
DSW
(@)FCS
DIGITAL SWITCH INPUT
FCS CALCULATE
Divides one 32-bit signed binary value by another and outputs the 64-bit signed binary result to R+3 to R.
Inputs 4- or 8-digit BCD data from a digital switch.
Checks for errors in data transmitted by a Host Link command.
179
231
232
304
283
FPD
(@)HEX
(@)MAX
(@)MBS
FAILURE POINT DETECT Finds errors within an instruction block.
ASCII-TO-HEXADECIMAL Converts ASCII data to hexadecimal data.
FIND MAXIMUM
SIGNED BINARY
MULTIPLY
(@)MBSL DOUBLE SIGNED
BINARY MULTIPLY
(@)MIN
MTR
FIND MINIMUM
MATRIX INPUT
Finds the maximum value in specified data area and outputs that value to another word.
Multiplies the signed binary content of two words and outputs the 8-digit signed binary result to R+1 and R.
Multiplies two 32-bit (8-digit) signed binary values and outputs the 16-digit signed binary result to R+3 through R.
Finds the minimum value in specified data area and outputs that value to another word.
Inputs data from an 8 input point × 8 output point matrix and records that data in D to D+3.
(@)NEG 2’S COMPLEMENT
(@)NEGL
(@)PID
(@)RXD
DOUBLE 2’S
COMPLEMENT
PID CONTROL
RECEIVE
(@)SBBL DOUBLE BINARY
SUBTRACT
Converts the four-digit hexadecimal content of the source word to its 2’s complement and outputs the result to R.
Converts the eight-digit hexadecimal content of the source words to its 2’s complement and outputs the result to R and R+1.
PID control is performed according to the operand and
PID parameters that are preset.
Receives data via a communications port.
Subtracts an 8-digit binary value (normal or signed data) from another and outputs the result to R and
R+1.
(@)SCL SCALING
(@)SRCH DATA SEARCH
(@)SUM
(@)TKY
(@)TXD
SUM CALCULATE
TEN KEY INPUT
TRANSMIT
285
195
233
229
230
234
313
202
203
242
297
227
Performs a scaling conversion on the calculated value.
198
Searches the specified range of memory for the specified data. Outputs the word address(es) of words in the range that contain the data.
289
Computes the sum of the contents of the words in the specified range of memory.
237
Inputs 8 digits of BCD data from a 10-key keypad.
Sends data via a communications port.
311
299
447
Programming Instructions Appendix B
---
Code
---
Mnemonic
(@)XDMR
ZCPL
Name
EXPANSION DM READ
DOUBLE AREA RANGE
COMPARE
Function
The contents of the designated number of words of the fixed expansion DM data are read and output to the destination word on the PC side.
Compares an 8-digit value to a range defined by lower and upper limits and outputs the result to the GR, EQ, and LE flags.
Page
290
177
448
Appendix C
Error and Arithmetic Flag Operation
The following table shows the instructions that affect the ER, CY, GR, LE and EQ flags. In general, ER indicates that operand data is not within requirements. CY indicates arithmetic or data shift results. GT indicates that a compared value is larger than some standard, LT that it is smaller, and EQ, that it is the same. EQ also indicates a result of zero for arithmetic operations. Refer to Section 5 Instruction Set for details.
Vertical arrows in the table indicate the flags that are turned ON and OFF according to the result of the instruction.
Although ladder diagram instructions,TIM, and CNT are executed when ER is ON, other instructions with a vertical arrow under the ER column are not executed if ER is ON. All of the other flags in the following table will also not operate when ER is ON.
Instructions not shown do not affect any of the flags in the table. Although only the non-differentiated form of each instruction is shown, differentiated instructions affect flags in exactly the same way.
The ER, CY, GR, LE and EQ Flags are turned OFF when END(01) is executed, so their status cannot be monitored with a Programming Console.
25503 (ER) 25504 (CY)
Unaffected
25505 (GR)
Unaffected
25506 (EQ)
Unaffected
25507 (LE)
Unaffected
Instructions
TIM
COM(29)
ADD(30)
SUB(31)
MUL(32)
DIV(33)
ANDW(34)
ORW(35)
XORW(36)
XNRW(37)
INC(38)
DEC(39)
STC(40)
CLC(41)
MSG(46)
ADB(50) 1
SBB(51) 1
CNT
END(01) 1
STEP(08)
SNXT(09)
CNTR(12)
TIMH(15)
WSFT(16)
CMP(20)
MOV(21)
MVN(22)
BIN(23)
BCD(24)
ASL(25)
ASR(26)
ROL(27)
ROR(28)
OFF
Unaffected
Unaffected
Unaffected
OFF
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
ON
OFF
Unaffected
OFF
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
OFF
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
OFF
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Page
139
145
252
253
204
204
205
205
278
219
221
249
205
207
211
212
250
251
159
159
180
181
154
154
155
155
138
266
266
148
143
157
170
449
Error and Arithmetic Flag Operation Appendix C
Instructions
MLB(52)
25503 (ER)
Unaffected
25504 (CY) 25505 (GR)
Unaffected
25506 (EQ)
Unaffected
25507 (LE) Page
224
DMPX(77)
SDEC(78)
FDIV(79)
DIST(80)
COLL(81)
MOVB(82)
MOVD(83)
SFTR(84)
TCMP(85)
ASC(86)
SEND(90)
SBS(91)
RECV(98)
MCRO(99)
DVB(53)
ADDL(54)
SUBL(55)
MULL(56)
DIVL(57)
BINL(58)
BCDL(59)
XFER(70)
BSET(71)
ROOT(72)
XCHG(73)
SLD(74)
SRD(75)
MLPX(76)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Note END(01), ADB(50), and SBB(51) also affect the signed binary arithmetic flags. Refer to page 451 for details.
175
194
291
257
293
260
188
191
214
162
164
166
167
152
161
160
217
162
156
156
185
224
206
209
212
213
181
182
Expansion Instructions
Instructions
7SEG(––)
2
ADBL(––)
2
APR(69)
ASFT(17)
AVG(––)
BCMP(68)
BCNT(67)
CMPL(60)
COLM(64)
CPS(––)
CPSL(––)
DBS(––)
DBSL(––)
DSW(––) 3
FCS(––)
25503 (ER) 25504 (CY)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
25505 (GR)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
25506 (EQ)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
25507 (LE)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
174
283
172
201
178
179
231
232
304
283
Page
301
225
239
157
235
450
SCAN(18)
SCL(––)
SEC(65)
SRCH(––)
SUM(––)
TKY(––)
TTIM(87)
TXD(––)
XFRB(62)
XDMR(––)
ZCP(88)
ZCPL(––)
Instructions
FPD(––)
HEX(––)
HMS(66)
INT(89)
LINE(63)
LMSG(47)
MAX(––)
MBS(––)
MBSL(––)
MCMP(19)
MIN(––)
MTR(––) 4
NEG(––) 2
NEGL(––)
2
PID(––)
RXD(––)
SBBL(––) 2
Error and Arithmetic Flag Operation Appendix C
25503 (ER) 25504 (CY)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
25505 (GR)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
25506 (EQ)
Unaffected
Unaffected
Unaffected
Unaffected
25507 (LE)
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
279
233
229
230
169
234
313
Page
285
195
184
262
200
202
203
242
297
227
276
198
183
289
237
311
144
299
168
290
176
177
Note 1. SR 25409 will be ON when 7SEG(––) is being executed.
2. ADBL(––), NEG(––), NEGL(––), and SBBL(––) also affect the signed binary arithmetic flags. Refer to page 451 for details.
3. SR 25410 will be ON when DSW(––) is being executed.
4. SR 25408 will be ON when MTR(––) is being executed.
Signed Binary Arithmetic Flags
The following table shows the instructions that affect the OF and UF flags. In general, OF indicates that the result of a 16-bit calculation is greater than 32,767 (7FFF) or the result of a 32-bit calculation is greater than 2,147,483,647
(7FFF FFFF). UF indicates that the result of a 16-bit calculation is less than –32,768 (8000) or the result of a 32-bit calculation is less than –2,147,483,648 (8000 0000). Refer to Section 5 Instruction Set for details.
Vertical arrows in the table indicate the flags that are turned ON and OFF according to the result of the instruction.
Instructions not shown do not affect any of the flags in the table.
The OF and UF Flags are turned OFF when END(01) is executed, so their status cannot be monitored with a Programming Console.
451
Error and Arithmetic Flag Operation Appendix C
Instructions
END(01)
ADB(50)
SBB(51)
ADBL(––)
SBBL(––)
NEG(––)
NEGL(––)
OFF
SR 25404 (OF )
Unaffected
OFF
SR 25405 (UF) Page
138
219
221
225
227
202
203
These instructions also affect the ER, CY, and EQ Flags. Refer to the previous tables in this appendix for details.
452
Appendix D
Memory Areas
Overview
The following table shows the data areas in PC memory.
Area
I/O Area
Group-2 High-density
I/O Unit Area
480 bits
320 bits
Size Range
IR 000 to IR 029
IR 030 to IR 049
Comments
Can be used as ordinary I/O or, if not used for real I/O, can be used as work bits.
SYSMAC BUS Area
Special I/O Unit Area
Optical I/O Unit Area
Work Area 1
800 bits
1,600 bits
512 bits
64 bits
IR 050 to IR 099
IR 100 to IR 199
IR 200 to IR 231
IR 232 to IR 235
”
”
Can be used as work bits if not used for real I/O.
Special Relay Area 1
Special Relay Area 2
Macro Area
320 bits
704 bits
64 bits
64 bits
3,424 bits Work Area 2
Temporary Relay Area 8 bits
Holding Relay Area 1,600 bits
Auxiliary Relay Area
Link Relay Area
Timer/Counter Area
SR 236 to SR 255
SR 256 to SR 299
SR 290 to SR 293
SR 294 to SR 297
IR 298 to IR 511
Inputs
Outputs
448 buts
1,024 bits
512 counters/ timers
TR 00 to TR 07
HR 00 to HR 99
AR 00 to AR 27
LR 00 to LR 63
TC 000 to TC 511 TIM 000 through TIM 015 can be refreshed via interrupt processing as high-speed timers.
6,144 words DM 0000 to DM 6143 Read/Write
1,000 words DM 0000 to DM 1999 Special I/O Unit Area (see note)
31 words DM 6000 to DM 6030 History Log
Expansion DM Area
I/O Comment Area
Ladder Program Area
(44 words)
512 words
456 words
56 words
DM 6100 to DM 6143
DM 6144 to DM 6655
DM 6144 to DM 6599
DM 6600 to DM 6655
Link test area (reserved)
Fixed DM Area (read only)
(SYSMAC NET Area)
PC Setup
3,000 words max.
DM 7000 to DM 9999 Read only
All UM Area max.
---
All UM Area max.
---
Stores I/O comments in the user program. Must be set using LSS.
Stores the user program executed by the CPU.
The program is retained even after the power supply is turned off.
Note The PC Setup can be set to use DM 7000 through DM 7999 as the Special I/O Area.
453
Memory Areas
SR Area
Appendix D
Word(s)
236
237
238 and 241
Bit(s)
00 to 07
08 to 15
00 to 07
08 to 15
00 to 15
242 and 245 00 to 15 Data link status output area for operating level 1 of SYSMAC LINK or SYSMAC NET Link
System
Reserved by system 246
247 and 248
00 to 15
00 to 07
08 to 15
249 and 250 00 to 07
08 to 15
251
PC Link Unit Run Flags for Units 16 through 31 or data link status for operating level 1
PC Link Unit Error Flags for Units 16 through 31 or data link status for operating level 1
PC Link Unit Run Flags for Units 00 through 15 or data link status for operating level 0
PC Link Unit Error Flags for Units 00 through 15 or data link status for operating level 0
00 Remote I/O Error Read Bit
01 and 02 Not used
03 Remote I/O Error Flag
252
04 to 06
07
08 to 15
00
Unit number of Remote I/O Unit or Optical I/O Unit with error
Not used
Word allocated to Remote I/O Unit or Optical I/O Unit with error
SEND(90)/RECV(98) Error Flag for operating level 0 of SYSMAC LINK or SYSMAC NET
Link System
01
Function
Node loop status output area for operating level 0 of SYSMAC NET Link System
Node loop status output area for operating level 1 of SYSMAC NET Link System
Completion code output area for operating level 0 following execution of
SEND(90)/RECV(98) SYSMAC LINK/SYSMAC NET Link System
Completion code output area for operating level 1 following execution of
SEND(90)/RECV(98) SYSMAC LINK/SYSMAC NET Link System
Data link status output area for operating level 0 of SYSMAC LINK or SYSMAC NET Link
System
253
02
03
04
05
06
07
08
09
10
11
12
13
14
15
00 to 07
08
09
10
11
12
13
14
15
SEND(90)/RECV(98) Enable Flag for operating level 0 of SYSMAC LINK or SYSMAC NET
Link System
Operating Level 0 Data Link Operating Flag
SEND(90)/RECV(98) Error Flag for operating level 1 of SYSMAC LINK or SYSMAC NET
Link System
SEND(90)/RECV(98) Enable Flag for operating level 1 of SYSMAC LINK or SYSMAC NET
Link System
Operating Level 1 Data Link Operating Flag
Rack-mounting Host Link Unit Level 1 Communications Error Flag
Rack-mounting Host Link Unit Level 1 Restart Bit
Peripheral Port Restart Bit
RS-232C Port Restart Bit
PC Setup Clear Bit
Forced Status Hold Bit
Data Retention Control Bit
Rack-mounting Host Link Unit Level 0 Restart Bit
Not used.
Output OFF Bit
FAL number output area (see error information provided elsewhere)
Low Battery Flag
Cycle Time Error Flag
I/O Verification Error Flag
Rack-mounting Host Link Unit Level 0 Communications Error Flag
Remote I/O Error Flag
Always ON Flag
Always OFF Flag
First Cycle Flag
454
Memory Areas Appendix D
Word(s)
254
255
256 to 261
262
263
264
265
266
00 to 03
04
05
06
07
08 to 11
12
13
14
00
01
02
03
13
14
15
04
05
06
07
08 to 15
00 to 15
00 to 15
00 to 15
09
10
11
12
05
06
07
08
00
01
Bit(s) Function
1-minute clock pulse bit
0.02-second clock pulse bit
02 and 03 Reserved for function expansion. Do not use.
04 Overflow Flag (for signed binary calculations)
Underflow Flag (for signed binary calculations)
Differential Monitor End Flag
Step Flag
MTR Execution Flag
7SEG Execution Flag
DSW Execution Flag
Interrupt Input Unit Error Flag
Reserved by system
Interrupt Programming Error Flag
Group-2 High-density I/O Unit Error Flag
Special Unit Error Flag (Special I/O, PC Link, Host Link, Remote I/O Master)
0.1-second clock pulse bit
0.2-second clock pulse bit
1.0-second clock pulse bit
Instruction Execution Error (ER) Flag
Carry (CY) Flag
Greater Than (GR) Flag
Equals (EQ) Flag
Less Than (LE) Flag
Reserved by system (used for TR bits)
Reserved by system
Longest interrupt subroutine (action) execution time (0.1 ms)
Number of interrupt subroutine (action) with longest execution time.
15
00 to 15
00 to 15
(8000 to 8512) 8000 to 8007, 8099
Bit 15: Interrupt Flag
RS-232C Port Error Code
0: No error 1: Parity error
2: Framing error
RS-232C Port Communications Error
RS-232C Port Send Ready Flag
3: Overrun error
RS-232C Port Reception Completed Flag
RS-232C Port Reception Overflow Flag
Peripheral Port Error Code in General I/O Mode
0: No error 1: Parity error
2: Framing error
F: When in Peripheral Bus Mode
3: Overrun error
Peripheral Port Communications Error in General I/O Mode
Peripheral Port Send Ready Flag in General I/O Mode
Peripheral Port Reception Completed Flag in General I/O Mode
Peripheral Port Reception Overflow Flag in General I/O Mode
RS-232C Port Reception Counter in General I/O Mode
Peripheral Reception Counter in General I/O Mode (BCD)
455
271
272
Memory Areas
Word(s)
267
268
269
270
456
Appendix D
Memory Areas Appendix D
Word(s)
273
274
275
276
277 to 279
280 to 289
290 to 293
294 to 297
298 to 299
00
Bit(s)
01
02 to 11
12
13
14
15
00
01
02
03
04
05
06
07
08
09
10 to 15
00
01
02
03 to 15
00 to 07
08 to 15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 15
Save IOM to Cassette Bit
Function
Data transferred to Memory Cassette when Bit is turned
Load IOM from Cassette Bit An error will be produced if turned ON in any other mode.
Reserved by system (not accessible by user)
Transfer Error Flag: Not
PROGRAM mode
Data will not be transferred from IOM to the Memory
Transfer Error Flag: Read Only
Transfer Error Flag: Insufficient
Capacity or No IOM
Transfer Error Flag: Checksum
Error
Special I/O Unit #0 Restart Flag g
Special I/O Unit #1 Restart Flag fl ill ON f U i
Special I/O Unit #2 Restart Flag
Special I/O Unit #3 Restart Flag
Special I/O Unit #4 Restart Flag
Special I/O Unit #5 Restart Flag
Special I/O Unit #6 Restart Flag
Special I/O Unit #7 Restart Flag p
Special I/O Unit #8 Restart Flag
Special I/O Unit #9 Restart Flag
Reserved by system (not accessible by user)
PC Setup Startup Error (DM 6600 to DM 6614)
PC Setup RUN Error (DM 6615 to DM 6644)
PC Setup Communications/Error Setting/Misc. Error (DM 6645 to DM 6655)
Reserved by system (not accessible by user)
Sl
Minutes (00 to 59)
Hours (00 to 23)
Used for time increments.
Used for keyboard mapping. See page 368.
Reserved by system (not accessible by user)
Macro Area inputs.
Macro Area outputs.
Reserved by system (not accessible by user) g
R k
457
Memory Areas
AR Area
Appendix D
03
04
05
06
07
08 to 11
12 to 15
16
17
18
Writeable
19
Writeable
20
Writeable
21
00
Word(s)
01
02
22
10
11
12, 13
14
15
00 to 04
05 to 14
15
00 to 15
Bit(s)
00 to 09
10
11
12
13
14
15
00 to 09
Host Computer to Rack-mounting Host Link Unit Level 0 Error Flag
Remote I/O Master Unit 1 Error Flag
Remote I/O Master Unit 0 Error Flag
Restart Bits for Special I/O Units 0 to 9 (also function as Restart Bits for PC Link Units)
Restart Bit for operating level 1 of SYSMAC LINK or SYSMAC NET Link System
Restart Bit for operating level 0 of SYSMAC LINK or SYSMAC NET Link System
Not used.
Remote I/O Master Unit 1 Restart Flag.
Remote I/O Master Unit 0 Restart Flag.
Slave Rack Error Flags (#0 to #4)
Group-2 High-density I/O Unit Error Flags
Group-2 High-density I/O Unit Error Flag
Error Flags for Optical I/O Units 0 to 7
Function
Error Flags for Special I/O Units 0 to 9 (also function as Error Flags for PC Link Units)
Error Flag for operating level 1 of SYSMAC LINK or SYSMAC NET Link System
Error Flag for operating level 0 of SYSMAC LINK or SYSMAC NET Link System
Host Computer to Rack-mounting Host Link Unit Level 1 Error Flag
00 to 15
00 to 15
00 to 15
00 to 03
Error Flags for Optical I/O Units 8 to 15
Error Flags for Optical I/O Units 16 to 23
Error Flags for Optical I/O Units 24 to 31
Data Link setting for operating level 0 of SYSMAC LINK System
04 to 07
08
Data Link setting for operating level 1 of SYSMAC LINK System
Normal TERMINAL Mode/Expansion TERMINAL Mode Input Cancel Bit
09 Expansion TERMINAL Mode Changeover Flag
10 and 11 Reserved by system.
12 Terminal Mode Flag
ON: Expansion; OFF: Normal (Same as status of pin 6 on CPU’s DIP switch)
13
14
15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 07
Error History Overwrite Bit
Error History Reset Bit
Error History Enable Bit
Active Node Flags for SYSMAC LINK System nodes of operating level 0
Active Node Flags for SYSMAC LINK System nodes of operating level 1
SYSMAC LINK/SYSMAC NET Link System operating level 0 service time per cycle
SYSMAC LINK/SYSMAC NET Link System operating level 1 service time per cycle
Seconds: 00 to 99
08 to 15
00 to 07
08 to 15
Minutes: 00 to 59
Hours: 00 to 23 (24-hour system)
Day of Month: 01 to 31 (adjusted by month and for leap year)
00 to 07
08 to 15
00 to 07
08 to 12
13
14
15
00 to 15
Month: 1 to 12
Year: 00 to 99 (Rightmost two digits of year)
Day of Week: 00 to 06 (00: Sunday; 01: Monday; 02: Tuesday; 03: Wednesday; 04:
Thursday; 05: Friday; 06: Saturday)
Not used.
30-second Compensation Bit
Clock Stop Bit
Clock Set Bit
Keyboard Mapping
458
Memory Areas Appendix D
23
24
Word(s)
25
26
27
05
06
07
Bit(s)
00 to 15
00 to 04
Function
Power Off Counter (BCD)
Reserved by system.
Cycle Time Flag
SYSMAC LINK System Network Parameter Flag for operating level 1
SYSMAC LINK System Network Parameter Flag for operating level 0
08
09
SYSMAC/SYSMAC NET Link Unit Level 1 Mounted Flag
SYSMAC/SYSMAC NET Link Unit Level 0 Mounted Flag
10 Reserved by system.
11 and 12 PC Link Level
13
14
Rack-mounting Host Link Unit Level 1 Mounted Flag
Rack-mounting Host Link Unit Level 0 Mounted Flag
15
00 to 11
CPU-mounting Device Mounted Flag
Reserved by system.
12
13
14
15
00 to 15
00 to 15
Trace End Flag
Tracing Flag
Trace Trigger Bit (writeable)
Trace Start Bit (writeable)
Maximum Cycle Time (0.1 ms)
Present Cycle Time (0.1 ms)
DM Area (Error Log)
Word
DM 6000
DM 6001 to
DM 6030
Function
Error Pointer (Incremented by 1 for each error (0000 to 000A)
Error Records (3 words per error for 10 errors, 30 words total)
See following table for structure of individual records.
First
Word
Second
Third
Bit Content
00 to 07 Error code (see error information provided elsewhere)
08 to 15 00 (non-fatal) or 80 (fatal)
00 to 07
08 to 15
Seconds
Minutes
Clock data read from AR
18 d AR 19
00 to 07 Hours
08 to 15 Day of month
459
Appendix E
PC Setup
Word(s) Bit(s)
Startup Processing (DM 6600 to DM 6614)
DM 6601
Function
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600 00 to 07 Startup mode (effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR 02: RUN
08 to 15 Startup mode designation
00: Programming Console switch
01: Continue operating mode last used before power was turned off
02: Setting in 00 to 07
00 to 07 Reserved
DM 6602
08 to 11 IOM Hold Bit (SR 25212) Status
0: Reset; 1: Maintain
12 to 15 Forced Status Hold Bit (SR 25211) Status
0: Reset; 1: Maintain
00 to 07 Reserved
08 to 15 Special I/O Unit Area
00: Use DM 1000 to DM 1999
01: Transfer DM 7000 through DM 7999 to DM 1000 through DM 1999 at startup and use DM 1000 to DM 1999.
DM 6603 to
DM 6614
00 to 15
02: Use DM 7000 to DM 7999
Reserved
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615
DM 6616
DM 6617
00 to 15 Reserved
00 to 07 (Servicing time for RS-232C port (effective when bits 08 to 15 are set to 01))
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port.
Minimum: 0.256 ms; maximum 65.536 ms
08 to 15 (RS-232C port servicing setting enable)
00: Do not set service time
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped.
00 to 07 Servicing time for peripheral port (effective when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
DM 6618
DM 6619
Minimum: 0.256 ms; maximum 65.536 ms
08 to 15 Peripheral port servicing setting enable
00: Do not set service time
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped.
00 to 07 Cycle monitor time (effective when bits 08 to 15 are set to 01, 02, or 03)
00 to 99 (BCD): Setting (see 08 to 15)
08 to 15 Cycle monitor enable (Setting in 00 to 07 x unit; 99 s max.)
00: 120 ms (setting in bits 00 to 07 disabled)
01: Setting unit: 10 ms
02: Setting unit: 100 ms
03: Setting unit: 1 s
00 to 15 Cycle time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum time in ms
Default
PROGRAM
Programming
Console switch
---
Reset
---
DM 1000 to
DM 1999
---
---
No setting (00)
No setting (00)
00
00: 120 ms
Variable
461
PC Setup Appendix E
Word(s) Bit(s)
Interrupt/Refresh Processing (DM 6620 to DM 6622)
Function
The following settings are effective after transfer to the PC the next time operation is started.
DM 6620 00 to 09 Special I/O Unit cyclic refresh (Bit number corresponds to unit number, PC
Link Units included)
0: Enable cyclic refresh and I/O REFRESH (IORF(97)) from main program
1: Disable (refresh only for I/O REFRESH from interrupt programs)
DM 6621
DM 6622
DM 6646
Disable not valid for normal (C200H) interrupt response or on Slave Racks.
10 to 11 Reserved
12 to 15 Interrupt response
0: Normal (C200H compatible)
1: High-speed (C200HS)
00 to 07 Reserved
08 to 15 Special I/O Unit refresh (PC Link Units included)
00: Enable refresh for all Special I/O Units
01: Disable refresh for all Special I/O Units (but, not valid on Slave Racks)
00 to 07 Scheduled interrupt time unit
00: 10 ms
01: 1 ms
08 to 15 Scheduled interrupt time unit enable
00: Disable (10 ms)
01: Enable
00 to 15 Reserved DM 6623 to
DM 6644
RS-232C Port Settings (DM 6645 to DM 6649)
The following settings are effective after transfer to the PC.
DM 6645 00 to 07 Port settings
00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
01: Settings in DM 6646
08 to 11 Words linked for 1:1 link
0: LR 00 to LR 63; 1: LR 00 to LR 31; 2: LR 00 to LR 15
12 to 15 Communications mode
0: Host link; 1: RS-232C; 2: 1-to-1 link slave; 3: 1-to-1 link master;
4: NT (PT) link
00 to 07 Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
DM 6647
08 to 15 Frame format
00:
01:
02:
11:
Start
1 bit
1 bit
1 bit
03: 1 bit
04: 1 bit
05: 1 bit
06: 1 bit
07: 1 bit
08: 1 bit
09: 1 bit
10: 1 bit
1 bit
Length
7 bits
7 bits
7 bits
7 bits
7 bits
7 bits
8 bits
8 bits
8 bits
8 bits
8 bits
8 bits
00 to 15 Transmission delay
0000 to 9999: BCD in ms.
Stop
1 bit
1 bit
1 bit
2 bit
2 bit
2 bit
1 bit
1 bit
1 bit
2 bit
2 bit
2 bit
Parity
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
Default
Enable
---
Normal
---
Enable
10 ms
---
Standard
LR 00 to LR 63
Host Link
1.2 K
1 start bit, 7-bit data, 1 stop bit, even parity
0 ms
462
PC Setup
Word(s)
DM 6648
DM 6649
Bit(s)
00 to 07 Node number (Host link)
00 to 31 (BCD)
08 to 11 Start code enable (RS-232C)
0: Disable; 1: Set
Function
12 to 15 End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
00 to 07 Start code (RS-232C)
00 to FF (binary)
08 to 15 12 to 15 of DM 6648 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6648 set to 1:
End code (RS-232C)
00 to FF (binary)
Peripheral Port Settings (DM 6650 to DM 6654)
The following settings are effective after transfer to the PC.
DM 6650 00 to 07 Port settings
00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
01: Settings in DM 6651
08 to 11 Reserved
12 to 15 Communications mode
0: Host link; 1: RS-232C
DM 6651
DM 6652
00 to 07 Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
08 to 15 Frame format
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
10:
11:
Start
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
Length
7 bits
7 bits
7 bits
7 bits
7 bits
7 bits
8 bits
8 bits
8 bits
8 bits
8 bits
8 bits
00 to 15 Transmission delay (Host Link)
0000 to 9999: In ms.
Stop
1 bit
1 bit
1 bit
2 bit
2 bit
2 bit
1 bit
1 bit
1 bit
2 bit
2 bit
2 bit
Parity
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
DM 6653 00 to 07 Node number (Host link)
00 to 31 (BCD)
08 to 11 Start code enable (RS-232C)
0: Disable; 1: Set
12 to 15 End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
Appendix E
Default
0
Disabled
Disabled
Not used
Standard
---
Host Link
1.2 K
1 start bit, 7-bit data, 1 stop bit, even parity
0 ms
0
Disable
Disable
463
PC Setup
Word(s)
DM 6654
Bit(s)
00 to 07 Start code (RS-232C)
00 to FF (binary)
08 to 15 12 to 15 of DM 6653 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6653 set to 1:
End code (RS-232C)
00 to FF (binary)
Function
Error Settings (DM 6655)
The following settings are effective after transfer to the PC.
DM 6655 00 to 03 Interrupt programming error enable
0: Detect interrupt programming errors
1: Do not detect
04 to 07 (Multiple action execution error enable
0: Detect multiple action execution
1: Do not detect )
08 to 11 Cycle time monitor enable
0: Detect long cycles as non-fatal errors
1: Do not detect long cycles
12 to 15 Low battery error enable
0: Detect low battery voltage as non-fatal error
1: Do not detect low batter voltage
Appendix E
Default
0000
Detect
Detect
Detect
Detect
464
Appendix F
Word Assignment Recording Sheets
This appendix contains sheets that can be copied by the programmer to record I/O bit allocations and terminal assignments, as well as details of work bits, data storage areas, timers, and counters.
465
10
11
12
13
06
07
08
09
14
15
Word:
Bit
00
01
02
03
04
05
Programmer:
13
14
15
09
10
11
12
Word:
Bit
00
01
02
03
04
05
06
07
08
Field device
Unit:
Program:
Notes
Field device
Unit:
Notes
I/O Bits
10
11
12
13
06
07
08
09
14
15
Word:
Bit
00
01
02
03
04
05
13
14
15
09
10
11
12
Word:
Bit
00
01
02
03
04
05
06
07
08
Date:
Field device
Unit:
Field device
Unit:
Notes
Page:
Notes
466
10
11
12
13
06
07
08
09
14
15
Area:
Bit
00
01
02
03
04
05
Programmer:
13
14
15
09
10
11
12
Area:
Bit
00
01
02
03
04
05
06
07
08
Usage
Usage
Word:
Program:
Notes
Word:
Notes
Work Bits
10
11
12
13
06
07
08
09
14
15
Area:
Bit
00
01
02
03
04
05
13
14
15
09
10
11
12
Area:
Bit
00
01
02
03
04
05
06
07
08
Date:
Usage
Usage
Word:
Word:
Notes
Page:
Notes
467
Programmer:
Word Contents
Program:
Notes
Data Storage
Word
Date:
Contents
Page:
Notes
468
Programmer:
TC address T or C Set value
Timers and Counters
Program:
Notes
Date:
TC address T or C Set value
Page:
Notes
469
Appendix G
Program Coding Sheet
The following page can be copied for use in coding ladder diagram programs. It is designed for flexibility, allowing the user to input all required addresses and instructions.
When coding programs, be sure to specify all function codes for instructions and data areas (or # for constant) for operands. These will be necessary when inputting programs though a Programming Console or other Peripheral
Device.
471
Program Coding Sheet
Programmer:
Address Instruction Operand(s)
Program:
Address Instruction
Date:
Operand(s) Address Instruction
Page:
Operand(s)
472
Appendix H
Data Conversion Tables
Normal Data
25
26
27
28
22
23
24
29
30
31
32
18
19
20
21
14
15
16
17
10
11
12
13
07
08
09
03
04
05
06
00
01
02
Decimal
16
17
18
19
1A
1B
1C
1D
1E
1F
20
12
13
14
15
0E
0F
10
11
07
08
09
0A
0B
0C
0D
03
04
05
06
00
01
02
Hex
00010100
00010101
00010110
00010111
00011000
00011001
00100000
00100001
00100010
00100011
00100100
00100101
00100110
00100111
00101000
00101001
00110000
00110001
00110010
BCD
00000000
00000001
00000010
00000011
00000100
00000101
00000110
00000111
00001000
00001001
00010000
00010001
00010010
00010011
00001110
00001111
00010000
00010001
00010010
00010011
00010100
00010101
00010110
00010111
00011000
00011001
00011010
00011011
00011100
00011101
00011110
00011111
00100000
Binary
00000000
00000001
00000010
00000011
00000100
00000101
00000110
00000111
00001000
00001001
00001010
00001011
00001100
00001101
473
Data Conversion Tables
Signed Binary Data
Decimal
2147483647
2147483646
.
32768
.
.
32767
32766
.
.
.
2
1
0
5
4
3
–5
.
.
.
–32767
–32768
–32769
–2147483647
.
.
.
–2147483648
–1
–2
–3
–4
16-bit Hex
0005
0004
0003
0002
0001
0000
FFFF
FFFE
FFFD
FFFC
FFFB
8001
.
.
.
8000
–––
.
.
.
–––
–––
–––
–––
.
–––
.
.
7FFF
7FFE
.
.
.
32-bit Hex
7FFFFFFF
7FFFFFFE
00008000
.
.
.
00007FFF
00007FFE
.
.
.
00000005
00000004
00000003
00000002
00000001
00000000
FFFFFFFF
FFFFFFFE
FFFFFFFD
FFFFFFFC
FFFFFFFB
.
.
.
FFFF8001
FFFF8000
FFFF7FFF
80000001
.
.
.
80000000
Appendix H
474
Appendix I
Extended ASCII
Programming Console Displays
Bits 0 to 3
BIN
HEX
0000 0
0001 1
0010 2
0011 3
0100 4
0101 5
0110 6
0111 7
1000 8
1001 9
1010 A
1011 B
1100 C
1101 D
1110 E
1111 F
Bits 4 to 7
0000 0001 0010 0011 0100 0101 0110 0111 1010 1011 1100 1101 1110 1111
0 1 2
NUL DLE Space
0
SOH DC
1
!
1
STX
ETX
DC
DC
2
3
"
#
2
3
EOT DC
4
$
ENQ NAK
%
ACK SYN &
4
5
6
BEL ETB '
BS CAN (
HT
LF
EM )
SUB *
VT
FF
CR
S0
S1
ESC +
FS ,
GS -
RS .
US /
=
>
;
<
?
:
9
7
8
3
M
N
K
L
O
I
J
G
H
D
E
F
B
C
@
A
4
]
^
\
[
_
Y
Z
W
X
T
U
V
R
S
P
Q
5 j i f
` l a b c d e g h k m n o
6 t r
}
|
{ p q s u v w x y z
«
~
7
!
"
*
)
(
'
,
.
/
#
$
%
&
+
A
:
;
0
1
2
3
4
5
6
7
8
9
<
=
>
?
B
M
N
K
L
O
I
J
G
H
D
E
F
B
C
@
A
C
]
^
\
[
_
Y
Z
W
X
T
U
V
R
S
P
Q
D
|
{
} y z w x t u v r s p q
~
F m n l k o j i g h f d e b c
` a
E
475
address allocation
AND
APF
AR area arithmetic shift
ASCII
ASCII Unit
Backplane
BCD
BCD calculation binary binary calculation binary-coded decimal bit bit address
Glossary
The location in memory where data is stored. For data areas, an address consists of a two-letter data area designation and a number that designates the word and/or bit location. For the UM area, an address designates the instruction location (UM area). In the FM area, the address designates the block location, etc.
The process by which the PC assigns certain bits or words in memory for various functions. This includes pairing I/O bits to I/O points on Units.
A logic operation whereby the result is true if and only if both premises are true.
In ladder-diagram programming the premises are usually ON/OFF states of bits or the logical combination of such states called execution conditions.
Acronym for all plastic fiber-optic cable.
A PC data area allocated to flags, control bits, and work bits.
A shift operation wherein the carry flag is included in the shift.
Short for American Standard Code for Information Interchange. ASCII is used to code characters for output to printers and other external devices.
An Intelligent I/O Unit used to program in BASIC. When connected to an NSU on a Net Link System, commands can be sent to other nodes.
A base onto which Units are mounted to form a Rack. Backplanes provide a series of connectors for these Units along with wiring to connect them to the CPU.
Backplanes also provide connectors used to connect them to other Backplanes.
In some Systems, different Backplanes are used for different Racks; in other
Systems, Racks differ only according to the Units mounted to them.
Short for binary-coded decimal.
An arithmetic calculation that uses numbers expressed in binary-coded decimal.
A number system where all numbers are expressed to the base 2, i.e., any number can be written using only 1’s or 2’s. Each group of four binary bits is equivalent to one hexadecimal digit.
An arithmetic calculation that uses numbers expressed in binary.
A system used to represent numbers so that each group of four binary bits is numerically equivalent to one decimal digit.
A binary digit; hence a unit of data in binary notation. The smallest unit of information that can be electronically stored in a PC. The status of a bit is either ON or
OFF. Different bits at particular addresses are allocated to special purposes, such as holding the status input from external devices, while other bits are available for general use in programming.
The location in memory where a bit of data is stored. A bit address must specify
(sometimes by default) the data area and word that is being addressed, as well as the number of the bit.
477
bit designator bit number buffer building-block PC bus bar call carry flag clock pulse clock pulse bit common data condition constant control bit
Control System controlled system control signal counter
478
Glossary
An operand that is used to designate the bit or bits of a word to be used by an instruction.
A number that indicates the location of a bit within a word. Bit 00 is the rightmost
(least-significant) bit; bit 15 is the leftmost (most-significant) bit.
A temporary storage space for data in a computerized device.
A PC that is constructed from individual components, or “building blocks”. With building-block PCs, there is no one Unit that is independently identifiable as a
PC. The PC is rather a functional assembly of components.
The line leading down the left and sometimes right side of a ladder diagram. Instruction execution proceeds down the bus bar, which is the starting point for all instruction lines.
A process by which instruction execution shifts from the main program to a subroutine. The subroutine may be called by an instruction or by an interrupt.
A flag that is used with arithmetic operations to hold a carry from an addition or multiplication operation, or to indicate that the result is negative in a subtraction operation. The carry flag is also used with certain types of shift operations.
A pulse available at a certain bit in memory for use in timing operations. Various clock pulses are available with different pulse widths.
A bit in memory that supplies a pulse that can be used to time operations. Various clock pulse bits are available with different pulse widths, and therefore different frequencies.
Data that is stored in the LR Area of a PC and which is shared by other PCs in the same the same system. Each PC has a specified section of the LR Area allocated to it. This allocation is the same in each LR Area of each PC.
An message placed in an instruction line to direct the way in which the terminal instructions, on the right side, are to be executed. Each condition is assigned to a bit in memory that determines its status. The status of the bit assigned to each condition determines, in turn, the execution condition for each instruction up to a terminal instruction on the right side of the ladder diagram.
An operand for which the actual numeric value is specified by the user, and which is then stored in a particular address in the data memory.
A bit in a memory area that is set either through the program or via a Programming Device to achieve a specific purpose, e.g., a Restart bit is turned ON and
OFF to restart a Unit.
All of the hardware and software components used to control other devices. A
Control System includes the PC System, the PC programs, and all I/O devices that are used to control or obtain feedback from the controlled system.
The devices that are being controlled by a PC System.
A signal sent from the PC to effect the operation of the controlled system.
A dedicated group of digits or words in memory used to count the number of times a specific process has occurred, or a location in memory accessed
CPU
CPU Backplane
CPU Rack
CTS cycle cycle time data area data area boundary data sharing debug decimal decrement default definer delay destination
Glossary through a TC bit and used to count the number of times the status of a bit or an execution condition has changed from OFF to ON.
An acronym for central processing unit. In a PC System, the CPU executes the program, processes I/O signals, communicates with external devices, etc.
A Backplane which is used to create a CPU Rack.
Part of a building-block PC, the CPU Rack contains the CPU, a power supply, and other Units. With most PCs, the CPU Rack is the only Rack that provides linkable slots.
An acronym for clear-to-send, a signal used in communications between electronic devices to indicate that the receiver is ready to accept incoming data.
The process used to execute a ladder-diagram program. The program is examined sequentially from start to finish and each instruction is executed in turn based on execution conditions.
The time required for a single cycle of the ladder-diagram program.
An area in the PC’s memory that is designed to hold a specific type of data, e.g., the LR area is designed to hold common data in a PC Link System. Memory areas that hold programs are not considered data areas.
The highest address available within a data area. When designating an operand that requires multiple words, it is necessary to ensure that the highest address in the data area is not exceeded.
An aspect of PC Link Systems and of Data Links in Net Link Systems in which common data areas or common data words are created between two or more
PCs.
A process by which a draft program is corrected until it operates as intended.
Debugging includes both the removal of syntax errors, as well as the fine-tuning of timing and coordination of control operations.
A number system where all numbers are expressed to the base 10. In a PC all data is ultimately stored in binary form, four binary bits are often used to represent one decimal digit, via a system called binary-coded decimal.
Decreasing a numeric value.
A value automatically set by the PC when the user omits to set a specific value.
Many devices will assume such default conditions upon the application of power.
A number used as an operand for an instruction but that serves to define the instruction itself, rather that the data on which the instruction is to operate. Definers include jump numbers, subroutine numbers, etc.
In tracing, a value that specifies where tracing is to begin in relationship to the trigger. A delay can be either positive or negative, i.e., can designate an offset on either side of the trigger.
The location where an instruction is to place the data on which it is operating, as opposed to the location from which data is taken for use in the instruction. The location from which data is taken is called the source.
479
differentiated instruction differentiation instruction digit digit designator distributed control
DM area download electrical noise error code exclusive OR exclusive NOR exection condition execution time
Expansion I/O Backplane
Expansion I/O Rack extended counter
Glossary
An instruction that is executed only once each time its execution condition goes from OFF to ON. Nondifferentiated instructions are executed each cycle as long as the execution condition stays ON.
An instruction used to ensure that the operand bit is never turned ON for more than one cycle after the execution condition goes either from OFF to ON for a
Differentiate Up instruction or from ON to OFF for a Differentiate Down instruction.
A unit of storage in memory that consists of four bits.
An operand that is used to designate the digit or digits of a word to be used by an instruction.
An automation concept in which control of each portion of an automated system is located near the devices actually being controlled, i.e., control is decentralized and ‘distributed’ over the system. Distributed control is one of the fundamental concepts of PC Systems.
A data area used to hold only word data. Words in the DM area cannot be accessed bit by bit.
The process of transferring a program or data from a higher-level computer to a lower-level computer or PC.
Random variations of one or more electrical characteristics such as voltage, current, and data, which might interfere with the normal operation of a device.
A numeric code generated to indicate that an error exists, and something about the nature of the error. Some error codes are generated by the system; others are defined in the program by the operator.
A logic operation whereby the result is true if one, and only one, of the premises is true. In ladder-diagram programming the premises are usually the ON/OFF states of bits, or the logical combination of such states, called execution conditions.
A logic operation whereby the result is true if both of the premises are true or both of the premises are false. In ladder-diagram programming the premises are usually the ON/OFF states of bits, or the logical combination of such states, called execution conditions.
The ON or OFF status under which an instruction is executed. The execution condition is determined by the logical combination of conditions on the same instruction line and up to the instruction currently being executed.
The time required for the CPU to execute either an individual instruction or an entire program.
A Backplane which is used to create an Expansion I/O Rack.
Part of a building-block PC, an Expansion I/O Rack is connected to either a CPU
Rack or another Expansion I/O Rack to increase the number of slots available for mounting Units.
A counter created in a program by using two or more count instructions in succession. Such a counter is capable of counting higher than any of the standard counters provided by the individual instructions.
480
Glossary extended timer A timer created in a program by using two or more timers in succession. Such a timer is capable of timing longer than any of the standard timers provided by the individual instructions.
Factory Intelligent Terminal A programming device provided with advanced programming and debugging capabilities to facilitate PC operation. The Factory Intelligent Terminal also provides various interfaces for external devices, such as floppy disk drives.
fatal error
FIT flag flicker bit floating point decimal
Floppy Disk Interface Unit
An error that stops PC operation and requires correction before operation can continue.
Abbreviation for Factory Intelligent Terminal.
A dedicated bit in memory that is set by the system to indicate some type of operating status. Some flags, such as the carry flag, can also be set by the operator or via the program.
A bit that is programmed to turn ON and OFF at a specific frequency.
A decimal number expressed as a number between 0 and 1 (the mantissa) multiplied by a power of 10, e.g., 0.538 x 10 -5 .
A Unit used to interface a floppy disk drive to a PC so that programs and/or data can be stored on floppy disks.
force reset force set function code hardware error hexadecimal
Host Link System
Host Link Unit host computer
HR area increment indirect address
The process of forcibly turning OFF a bit via a programming device. Bits are usually turned OFF as a result of program execution.
The process of forcibly turning ON a bit via a programming device. Bits are usually turned ON as a result of program execution.
A two-digit number used to input an instruction into the PC.
An error originating in the hardware structure (electronic components) of the PC, as opposed to a software error, which originates in software (i.e., programs).
A number system where all numbers are expressed to the base 16. In a PC all data is ultimately stored in binary form, however, displays and inputs on Programming Devices are often expressed in hexadecimal to simplify operation.
Each group of four binary bits is numerically equivalent to one hexadecimal digit.
A system with one or more host computers connected to one or more PCs via
Host Link Units so that the host computer can be used to transfer data to and from the PC(s). Host Link Systems enable centralized management and control of PC Systems.
An interface used to connect a PC to a host computer in a Host Link System.
A computer that is used to transfer data or programs to from a PC in a Host Link
System. The host computer is used for data management and overall system control. Host computers are generally personal or business computers.
A data area used to store and manipulate data, and to preserve data when power to the PC is turned OFF.
Increasing a numeric value.
An address whose contents indicates another address. The contents of the second address will be used as the operand. Indirect addressing is possible in the
DM area only.
481
Glossary initialization error initialize input
An error that occurs either in hardware or software during the PC System startup, i.e., during initialization.
Part of the startup process whereby some memory areas are cleared, system setup is checked, and default values are set.
The signal coming from an external device into the PC. The term input is often used abstractly or collectively to refer to incoming signals.
A bit in the IR area that is allocated to hold the status of an input.
An external device that sends signals into the PC System.
input bit input device input point input signal instruction instruction block
I/O capacity
The point at which an input enters the PC System. Input points correspond physically to terminals or connector pins.
A change in the status of a connection entering the PC. Generally an input signal is said to exist when, for example, a connection point goes from low to high voltage or from a nonconductive to a conductive state.
A direction given in the program that tells the PC of an action to be carried out, and which data is to be used in carrying out the action. Instructions can be used to simply turn a bit ON or OFF, or they can perform much more complex actions, such as converting and/or transferring large blocks of data.
A group of instructions that is logically related in a ladder-diagram program. Although any logically related group of instructions could be called an instruction block, the term is generally used to refer to blocks of instructions called logic blocks that require logic block instructions to relate them to other instructions or logic blocks.
instruction execution time The time required to execute an instruction. The execution time for any one instruction can vary with the execution conditions for the instruction and the operands used within it.
instruction line A group of conditions that lie together on the same horizontal line of a ladder diagram. Instruction lines can branch apart or join together to form instruction blocks.
interface interlock
An interface is the conceptual boundary between systems or devices and usually involves changes in the way the communicated data is represented. Interface devices such as NSBs perform operations like changing the coding, format, or speed of the data.
A programming method used to treat a number of instructions as a group so that the entire group can be reset together when individual execution is not required.
An interlocked program section is executed normally for an ON execution condition and partially reset for an OFF execution condition.
interrupt (signal)
Interrupt Input Unit inverse condition
A signal that stops normal program execution and causes a subroutine to be run.
A Rack-mounting Unit used to input external interrupts into a PC System.
A condition that produces an ON execution condition when the bit assigned to it is OFF, and an OFF execution condition when the bit assigned to it is ON.
The number of inputs and outputs that a PC is able to handle. This number ranges from around one hundred for smaller PCs to two thousand for the largest ones.
482
I/O Control Unit
I/O devices
I/O Interface Unit
I/O Link
I/O Link Unit
I/O point
I/O response time
I/O table
I/O Unit
I/O word
IR area
JIS jump jump number ladder diagram (program) ladder diagram symbol ladder instruction
Glossary
A Unit mounted to the CPU Rack in certain PCs to monitor and control I/O points on Expansion I/O Units.
The devices to which terminals on I/O Units, Special I/O Units, or Intelligent I/O
Units are connected. I/O devices may be either part of the Control System, if they function to help control other devices, or they may be part of the controlled system.
A Unit mounted to an Expansion I/O Rack in certain PCs to interface the Expansion I/O Rack to the CPU Rack.
Created in an Optical Remote I/O System to enable input/output of one or two IR words directly between PCs. The words are input/output between the PC controlling the Master and a PC connected to the Remote I/O System through an I/O
Link Unit or an I/O Link Rack.
A Unit used with certain PCs to create an I/O Link in an Optical Remote I/O System.
The place at which an input signal enters the PC System, or at which an output signal leaves the PC System. In physical terms, I/O points correspond to terminals or connector pins on a Unit; in terms of programming, an I/O points correspond to I/O bits in the IR area.
The time required for an output signal to be sent from the PC in response to an input signal received from an external device.
A table created within the memory of the PC that lists the IR area words allocated to each Unit in the PC System. The I/O table can be created by, or modified from, a Programming Device.
The most basic type of Unit mounted to a backplane to create a Rack. I/O Units include Input Units and Output Units, each of which is available in a range of specifications. I/O Units do not include Special I/O Units, Link Units, etc.
A word in the IR area that is allocated to a Unit in the PC System.
A data area whose principal function is to hold the status of inputs coming into the system and that of outputs that are to be set out of the system. Bits and words in the IR that are used this way are called I/O bits and I/O words. The remaining bits in the IR area are work bits.
Acronym for Japanese Industrial Standards.
A type of programming where execution moves directly from one point in a program to another, without sequentially executing any instructions inbetween.
Jumps are usually conditional on an execution condition.
A definer used with a jump that defines the points from and to which a jump is to be made.
A form of program arising out of relay-based control systems that uses circuit-type diagrams to represent the logic flow of programming instructions. The appearance of the program is similar to a ladder, and thus the name.
A symbol used in a ladder-diagram program.
An instruction that represents the ‘rung’ portion of a ladder-diagram program.
The other instructions in a ladder diagram fall along the right side of the diagram and are called terminal instructions.
483
Ladder Support Software
LAN leftmost (bit/word)
Link Adapter link linkable slot
Link System
Link Unit load local area network logic block logic block instruction logic instruction loop
LR area
Glossary
A software package that provides most of the functions of the Factory Intelligent
Terminal on an IBM AT, IBM XT, or compatible computer.
An acronym for local area network.
The highest numbered bits of a group of bits, generally of an entire word, or the highest numbered words of a group of words. These bits/words are often called most-significant bits/words.
A Unit used to connect communications lines, either to branch the lines or to convert between different types of cable. There are two types of Link Adapter:
Branching Link Adapters and Converting Link Adapters.
A hardware or software connection formed between two Units. “Link” can refer either to a part of the physical connection between two Units (e.g., optical links in
Wired Remote I/O Systems) or a software connection created to data existing at another location (Network Data Links).
A slot on either a CPU or Expansion I/O Backplane to which a Link Unit can be mounted. Backplanes differ in the slots to which Link Units can be mounted.
A system that includes one or more of the following systems: Remote I/O System, PC Link System, Host Link System, or Net Link System.
Any of the Units used to connect a PC to a Link System. These are Remote I/O
Units, I/O Link Units, PC Link Units, Host Link Units, and Net Link Units.
The processes of copying data either from an external device or from a storage area to an active portion of the system such as a display buffer. Also, an output device connected to the PC is called a load.
A network consisting of nodes or positions in a loop arrangement. Each node can be any one of a number of devices, which can transfer data to and from each other.
A group of instructions that is logically related in a ladder-diagram program and that requires logic block instructions to relate it to other instructions or logic blocks.
An instruction used to locally combine the execution condition resulting from a logic block with a current execution condition. The current execution condition could be the result of a single condition, or of another logic block. AND Load and
OR Load are the two logic block instructions.
Instructions used to logically combine the content of two words and output the logical results to a specified result word. The logic instructions combine all the same-numbered bits in the two words and output the result to the bit of the same number in the specified result word.
A group of instructions that can be executed more than once in succession (i.e., repeated) depending on an execution condition or bit status.
A data area that is used in a PC Link System so that data can be transferred between two or more PCs. If a PC Link System is not used, the LR area is available for use as work bits.
Abbreviation for Ladder Support Software.
LSS
484
Glossary main program masking
Master memory area mnemonic code
Network Service Board
Any of the areas in the PC used to hold data or programs.
A form of a ladder-diagram program that consists of a sequential list of the instructions without using a ladder diagram. Mnemonic code is required to input a program into a PC when using a Programming Console.
MONITOR mode most-significant (bit/word) See leftmost (bit/word).
NC input An input that is normally closed, i.e., the input signal is considered to be present when the circuit connected to the input opens.
nest
A mode of PC operation in which normal program execution is possible, and which allows modification of data held in memory. Used for monitoring or debugging the PC.
Net Link System
Programming one loop within another loop, programming a call to a subroutine within another subroutine, or programming an IF-ELSE programming section within another IF-ELSE section.
An optical LAN formed from PCs connected through Net Link Units. A Net Link
System also normally contains nodes interfacing computers and other peripheral devices. PCs in the Net Link System can pass data back and forth, receive commands from any interfaced computer, and share any interfaced peripheral device.
Net Link Unit The Unit used to connect PCs to a Net Link System. The full name is “SYSMAC
Net Link Unit”.
A device with an interface to connect devices other than PCs to a Net Link System.
Network Service Unit
All of a program except for the subroutines.
‘Covering’ an interrupt signal so that the interrupt is not effective until the mask is removed.
Short for Remote I/O Master Unit.
node
NO input noise interference nonfatal error normal condition
A Unit that provides two interfaces to connect peripheral devices to a Net Link
System.
One of the positions in a LAN. Each node incorporates a device that can communicate with the devices at all of the other nodes. The device at a node is identified by the node number. One loop of a Net Link System (OMRON’s LAN) can consist of up to 126 nodes. Each node is occupied by a Net Link Unit mounted to a PC or a device providing an interface to a computer or other peripheral device.
An input that is normally open, i.e., the input signal is considered to be present when the circuit connected to the input closes.
Disturbances in signals caused by electrical noise.
A hardware or software error that produces a warning but does not stop the PC from operating.
A condition that produces an ON execution condition when the bit assigned to it is ON, and an OFF execution condition when the bit assigned to it is OFF.
485
NOT
NSB
NSU
OFF
OFF delay
ON
ON delay one-shot bit on-line removal operand operand bit operand word operating error
Optical I/O Unit
Optical Slave Rack
OR output output bit output device
486
Glossary
A logic operation which inverts the status of the operand. For example, AND
NOT indicates an AND operation with the opposite of the actual status of the operand bit.
An acronym for Network Service Board.
An acronym for Network Service Unit.
The status of an input or output when a signal is said not to be present. The OFF state is generally represented by a low voltage or by non-conductivity, but can be defined as the opposite of either.
The delay between the time when a signal is switched OFF (e.g., by an input device or PC) and the time when the signal reaches a state readable as an OFF signal (i.e., as no signal) by a receiving party (e.g., output device or PC).
The status of an input or output when a signal is said to be present. The ON state is generally represented by a high voltage or by conductivity, but can be defined as the opposite of either.
The delay between the time when an ON signal is initiated (e.g., by an input device or PC) and the time when the signal reaches a state readable as an ON signal by a receiving party (e.g., output device or PC).
A bit that is turned ON or OFF for a specified interval of time which is longer than one cycle.
Removing a Rack-mounted Unit for replacement or maintenance during PC operation.
Bit(s) or word(s) designated as the data to be used for an instruction. An operand can be input as a constant expressing the actual numeric value to be used or as an address to express the location in memory of the data to be used.
A bit designated as an operand for an instruction.
A word designated as an operand for an instruction.
An error that occurs during actual PC operation as opposed to an initialization error, which occurs before actual operations can begin.
A Unit that is connected in an Optical Remote I/O System to provide 8 I/O points.
Optical I/O Units are not mounted to a Rack.
A Slave Rack connected through an Optical Remote I/O Slave Unit.
A logic operation whereby the result is true if either of two premises is true, or if both are true. In ladder-diagram programming the premises are usually ON/OFF states of bits or the logical combination of such states called execution conditions.
The signal sent from the PC to an external device. The term output is often used abstractly or collectively to refer to outgoing signals.
A bit in the IR area that is allocated to hold the status to be sent to an output device.
An external device that receives signals from the PC System.
output point output signal overseeing overwrite parity
PC
PCB
PC configuration
PCF
PC Link System
PC Link Unit
PC System peripheral device port present value printed circuit board
Printer Interface Unit program
Programmable Controller
Glossary
The point at which an output leaves the PC System. Output points correspond physically to terminals or connector pins.
A signal being sent to an external device. Generally an output signal is said to exist when, for example, a connection point goes from low to high voltage or from a nonconductive to a conductive state.
Part of the processing performed by the CPU that includes general tasks required to operate the PC.
Changing the content of a memory location so that the previous content is lost.
Adjustment of the number of ON bits in a word or other unit of data so that the total is always an even number or always an odd number. Parity is generally used to check the accuracy of data after being transmitted by confirming that the number of ON bits is still even or still odd.
An acronym for Programmable Controller.
An acronym for printed circuit board.
The arrangement and interconnections of the Units that are put together to form a functional PC.
Acronym for plastic-clad optical fiber cable.
A system in which PCs are connected through PC Link Units to enable them to share common data areas, i.e., each of the PCs writes to certain words in the LR area and receives the data of the words written by all other PC Link Units connected in series with it.
The Unit used to connect PCs in a PC Link System.
With building-block PCs, all of the Racks and independent Units connected directly to them up to, but not including the I/O devices. The boundaries of a PC
System are the PC and the program in its CPU at the upper end; and the I/O
Units, Special I/O Units, Optical I/O Units, Remote Terminals, etc., at the lower end.
Devices connected to a PC System to aid in system operation. Peripheral devices include printers, programming devices, external storage media, etc.
A connector on a PC or computer that serves as a connection to an external device.
The current value registered in a device at any instant during its operation. Present value is abbreviated as PV.
A board onto which electrical circuits are printed for mounting into a computer or electrical device.
A Unit used to interface a printer so that ladder diagrams and other data can be printed out.
The list of instructions that tells the PC the sequence of control actions to be carried out.
A computerized device that can accept inputs from external devices and generate outputs to external devices according to a program held in memory. Pro-
487
programmed alarm programmed error programmed message
Programming Console
Programming Device
PROGRAM mode
PROM Writer prompt
PV
Rack refresh relay-based control
Remote I/O Master Unit
Remote I/O Slave Unit
Remote I/O System
488
Glossary grammable Controllers are used to automate control of external devices. Although single-component Programmable Controllers are available, building-block Programmable Controllers are constructed from separate components. Such building-block Programmable Controllers are formed only when enough of these separate components are assembled to form a functional assembly, i.e., no one individual Unit is called a PC.
An alarm given as a result of execution of an instruction designed to generate the alarm in the program, as opposed to one generated by the system.
An error arising as a result of the execution of an instruction designed to generate the error in the program, as opposed to one generated by the system.
A message generated as a result of execution of an instruction designed to generate the message in the program, as opposed to one generated by the system.
The simplest form or programming device available for a PC. Programming
Consoles are available both as hand-held models and as CPU-mounting models.
A peripheral device used to input a program into a PC or to alter or monitor a program already held in the PC. There are dedicated programming devices, such as Programming Consoles, and there are non-dedicated devices, such as a host computer.
A mode of operation that allows inputting and debugging of programs to be carried out, but that does not permit normal execution of the program.
A peripheral device used to write programs and other data into a ROM for permanent storage and application.
A message or symbol that appears on a display to request input from the operator.
Acronym for present value.
An assembly of various Units on a Backplane that forms a functional unit in a building-block PC System. Racks include CPU Racks, Expansion I/O Racks, I/O
Racks, and Slave Racks.
The process of updating output status sent to external devices so that it agrees with the status of output bits held in memory and of updating input bits in memory so that they agree with the status of inputs from external devices.
The forerunner of PCs. In relay-based control, groups of relays are interconnected to form control circuits. In a PC, these are replaced by programmable circuits.
The Unit in a Remote I/O System through which signals are sent to all other Remote I/O Units. The Remote I/O Master Unit is mounted either to a CPU Rack or an Expansion I/O Rack connected to the CPU Rack. Remote I/O Master Unit is generally abbreviated to Master.
A Unit mounted to a Backplane to form a Slave Rack. Remote I/O Slave Unit is generally abbreviated to Slave.
A system in which remote I/O points are controlled through a Master mounted to a CPU Rack or an Expansion I/O Rack connected to the CPU Rack.
Remote I/O Unit remote I/O word reset return reversible counter reversible shift register right-hand instruction rightmost (bit/word) rotate register
RUN mode scheduled interrupt self diagnosis self-maintaining bit servicing set set value shift register
Slave
Slave Rack
Glossary
Any of the Units in a Remote I/O System. Remote I/O Units include Masters,
Slaves, Optical I/O Units, I/O Link Units, and Remote Terminals.
An I/O word allocated to a Unit in a Remote I/O System.
The process of turning a bit or signal OFF or of changing the present value of a timer or counter to its set value or to zero.
The process by which instruction execution shifts from a subroutine back to the main program (usually the point from which the subroutine was called).
A counter that can be both incremented and decremented depending on the specified conditions.
A shift register that can shift data in either direction depending on the specified conditions.
Another term for terminal instruction.
The lowest numbered bits of a group of bits, generally of an entire word, or the lowest numbered words of a group of words. These bits/words are often called least-significant bits/words.
A shift register in which the data moved out from one end is placed back into the shift register at the other end.
The operating mode used by the PC for normal control operations.
An interrupt that is automatically generated by the system at a specific time or program location specified by the operator. Scheduled interrupts result in the execution of specific subroutines that can be used for instructions that must be executed repeatedly for a specified period of time.
A process whereby the system checks its own operation and generates a warning or error if an abnormality is discovered.
A bit that is programmed to maintain either an OFF or ON status until set or reset by specified conditions.
The process whereby the PC provides data to or receives data from external devices or remote I/O Units, or otherwise handles data transactions for Link Systems.
The process of turning a bit or signal ON.
The value from which a decrementing counter starts counting down or to which an incrementing counter counts up (i.e., the maximum count), or the time from which or for which a timer starts timing. Set value is abbreviated SV.
One or more words in which data is shifted a specified number of units to the right or left in bit, digit, or word units. In a rotate register, data shifted out one end is shifted back into the other end. In other shift registers, new data (either specified data, zero(s) or one(s)) is shifted into one end and the data shifted out at the other end is lost.
Short for Remote I/O Slave Unit.
A Rack containing a Remote I/O Slave Unit and controlled through a Remote I/O
Master Unit. Slave Racks are generally located away from the CPU Rack.
489
Glossary slot software error software protect source
Special I/O Unit
A position on a Rack (Backplane) to which a Unit can be mounted.
An error that originates in a software program.
A means of protecting data from being changed that uses software as opposed to a physical switch or other hardware setting.
The location from which data is taken for use in an instruction, as opposed to the location to which the result of an instruction is to be written. The latter is called the destination.
A dedicated Unit that is designed for a specific purpose. Special I/O Units include Position Control Units, High-Speed Counter Units, Analog I/O Units, etc.
SR area
SSS subroutine subroutine number system error message
TC area
TC number terminal instruction
A data area in a PC used mainly for flags, control bits, and other information provided about PC operation. The status of only certain SR bits may be controlled by the operator, i.e., most SR bits can only be read.
Abbreviation for SYSMAC Support Software.
A group of instructions placed after the main program and executed only if called from the main program or activated by an interrupt.
A definer used to identify the subroutine that a subroutine call or interrupt activates.
Abbreviation for set value.
The maximum voltage/current that a relay can safely switch on and off.
SV switching capacity syntax error An error in the way in which a program is written. Syntax errors can include
‘spelling’ mistakes (i.e., a function code that does not exist), mistakes in specifying operands within acceptable parameters (e.g., specifying reserved SR bits as a destination), and mistakes in actual application of instructions (e.g., a call to a subroutine that does not exist).
SYSMAC Support Software A software package installed on a IBM PC/AT or compatible computer to function as a Programming Device.
system configuration The arrangement in which Units in a system are connected.
system error An error generated by the system, as opposed to one resulting from execution of an instruction designed to generate an error.
An error message generated by the system, as opposed to one resulting from execution of an instruction designed to generate a message.
A data area that can be used only for timers and counters. Each bit in the TC area serves as the access point for the SV, PV, and Completion flag for the timer or counter defined with that bit.
A definer that corresponds to a bit in the TC area and used to define the bit as either a timer or a counter.
An instruction placed on the right side of a ladder diagram that uses the final execution conditions of an instruction line.
terminator The code comprising an asterisk and a carriage return (* CR) which indicates the end of a block of data, whether it is a single-frame or multi-frame block. Frames within a multi-frame block are separated by delimiters.
490
timer
TM area transmission distance
TR area trace transfer trigger address
UM area
Unit unit number watchdog timer
Wired Slave Rack word word address word multiplier work bit work word
Glossary
A location in memory accessed through a TC bit and used to time down from the timer’s set value. Timers are turned ON and reset according to their execution conditions.
A memory area used to store the results of a trace.
The distance that a signal can be transmitted.
A data area used to store execution conditions so that they can be reloaded later for use with other instructions.
An operation whereby the program is executed and the resulting data is stored in
TM memory to enable step-by-step analysis and debugging.
The process of moving data from one location to another within the PC, or between the PC and external devices. When data is transferred, generally a copy of the data is sent to the destination, i.e., the content of the source of the transfer is not changed.
An address in the program that defines the beginning point for tracing. The actual beginning point can be altered from the trigger by defining either a positive or negative delay.
The memory area used to hold the active program, i.e., the program that is being currently executed.
In OMRON PC terminology, the word Unit is capitalized to indicate any product sold for a PC System. Though most of the names of these products end with the word Unit, not all do, e.g., a Remote Terminal is referred to in a collective sense as a Unit. Context generally makes any limitations of this word clear.
A number assigned to some Link Units and Special I/O Units to facilitate identification when assigning words or other operating parameters to it.
A timer within the system that ensures that the cycle time stays within specified limits. When limits are reached, either warnings are given or PC operation is stopped depending on the particular limit that is reached.
A Slave Rack connected through a Wired Remote I/O Slave Unit.
A unit of data storage in memory that consists of 16 bits. All data areas consists of words. Some data areas can be accessed only by words; others, by either words or bits.
The location in memory where a word of data is stored. A word address must specify (sometimes by default) the data area and the number of the word that is being addressed.
A value between 0 and 3 that is assigned to a Master in a Remote I/O System so that words can be allocated to non-Rack-mounting Units within the System. The word setting made on the Unit is added to 32 times the word multiplier to arrive at the actual word to be allocated.
A bit in a work word.
A word that can be used for data calculation or other manipulation in programming, i.e., a ‘work space’ in memory. A large portion of the IR area is always re-
491
492
Glossary served for work words. Parts of other areas not required for special purposes may also be used as work words, e.g., LR words not used in a PC Link or Net Link
System.
A address tracing. See tracing, data tracing.
addresses, in data area, 27 advanced I/O instructions
7-SEGMENT DISPLAY OUTPUT, 303
DIGITAL SWITCH INPUT, 306 functions, 302
HEXADECIMAL KEY INPUT, 310
MATRIX INPUT, 315
TEN-KEY INPUT, 312 application examples, 339
AR area, 48–54 arithmetic flags, 119 arithmetic operations, flags, 44
ASCII, converting data, 195, 196
B battery, Low Battery Flag, 42
BCD calculations, 205–219 converting, 28 definition, 28 binary calculations, 220 definition, 28 signed binary, 29 unsigned binary, 29 bits controlling, 130 forced set/reset, 349 monitoring, 346–349 buzzer, 81
C
C200H programs, transferring to C200HS, 11 calendar/clock, dedicated bits, 52 canceling, forced set/reset, 351 channel. See word checksum, calculating frame checksum, 284 clock, reading and setting, 367 clock pulse bits, 43 communications host link, 377 node number, 378 link, one-to-one, 382 one-to-one, 383 wiring, 377 constants, operands, 119 control bit definition, 27
Output OFF, 42
Control System, definition, 3
Index
controlled system, definition, 3 counters bits in TC area, 60 changing SV, 362 conditions when reset, 146, 149 creating extended timers, 147 extended, 147 inputting SV, 94
Power OFF, 54 reversible counters, 148
CPU, 16
CPU-mounting Device Mounted Flag, 54 operational flow, 318–319
CPU indicators, 17
CPU Rack, definition, 18 cycle, First Cycle Flag, 43
CYCLE MONITOR TIME, PC Setup, 59
CYCLE TIME, PC Setup, 59 cycle time, 318–322 calculating, 322–324 controlling, 277
Cycle Time Indicators, 54 displaying on Programming Console, 98 error flag, 43 flag for SCAN(18), 54
D data comparison instructions, 169–180 converting, 28, 181–204 decrementing, 205 incrementing, 205 modifying, 358 modifying binary data, 361 modifying hex/BCD, 352 moving, 158–169 data area, definition, 25 data areas, 453 structure, 27
Data Link table, transferring, 90 data memory, fixed, 56 data retention in AR area, 48 in HR area, 60 in IR area, 31 in LR area, 61 in SR area, 33 in TC area, 60 in TR area, 61 data tracing, 278–292 flags and control bits, 54 decimal converting display between 4-digit hex and decimal, 355 converting display between 8-digit hex and decimal, 356 decrementing, 205 definers, definition, 118 delay time, in C500 Remote I/O Systems, 335
493
differentiated instructions, 119 function codes, 118 digit, monitoring, 346 digit numbers, 28
DIP switch, 23 displays converting between 4-digit hex and decimal, 355 converting between 8-digit hex and decimal, 356 converting between hex and ASCII, 354
I/O Unit designations, 88
Programming Console, English/Japanese switch, 80
DM area, allocating UM to expansion DM, 366
E
ER. See flag, Instruction Execution Error error codes, programming, 276 error history, dedicated bits, 51 error messages, programming, 279, 280 errors clearing messages, 85 fatal, 395 history area, 57 initialization, 393
Instruction Execution Error Flag, 44 message tables, 392–396 messages when inputting programs, 96 non-fatal, 393 programming indications, 392 programming messages, 279, 280 reading and clearing messages, 392 resetting, 277
SR and AR area flags, 397 execution condition, definition, 66 execution time, instructions, 324–332 expansion DM, allocating UM to, 366 expansion DM area, allocation, 56
Expansion I/O Rack, definition, 19 expansion instructions, 8, 120, 446 changing function code assignments, 365 reading function code assignments, 365 expansion keyboard mapping, 367
F
FAL area, 42, 276 fatal operating errors, 395 flag
AR and SR area error flags, 397 arithmetic, 44 programming example, 171, 174, 178
CPU-mounting Device Mounted, 54
CY clearing, 206 setting, 206
Cycle Time Error, 43 definition, 27
First Cycle, 43
FPD Trigger Bit, 54
494
Index
I/O Verification Error, 43
Instruction Execution Error, 44
Link Units, 54
Low Battery, 42
Optical I/O Error, 50
Step, 44 flags arithmetic, 119 error and arithmetic, 449 signed binary arithmetic, 451 floating-point decimal, division, 215 forced set/reset, 349 canceling, 351–352
Forced Status Hold Bit, 41
FORCED STATUS, PC Setup, 59
Frame Check Sequence. See frames, FCS frame checksum, calculating with FCS(––), 284 frames dividing
See also host link precautions, 405
FCS, 405 function codes, 118 changing expansion instruction function codes, 365 reading expansion instruction function codes, 365
G
Group-2 High-density I/O Units, 4
Group-2 B7A Interface Units, word allocation, 33
Group-2 High-density I/O Units, word allocation, 33
H hexadecimal, definition, 28
High-density I/O Units. See Group
Units host link command and response formats, 404 communications
See also host link commands methods, 403
PC transmission, 406 procedures, 378, 403 data transfer, 403 dividing frames, 405 frame definition, 403 maximum size, 403 node number, 378 setting parameters, start and end codes, 380 host link commands
**, 430
FK, 424
IC, 430
KC, 425
KR, 423
KS, 422
MF, 421
MI, 427
MM, 425
MS, 419
QQ, 427
R#, 414
R$, 415
R%, 416
RC, 408
RD, 409
RG, 409
RH, 408
RJ, 410
RL, 407
RP, 426
RR, 407
SC, 420
TS, 426
W#, 417
W$, 417
W%, 418
WC, 412
WD, 413
WG, 412
WH, 411
WJ, 413
WL, 411
WP, 427
WR, 410
XZ, 429 host link errors, 431
Host Link Systems, error bits and flags, 40
HR area, 60
I
I/O bit definition, 31 limits, 31
I/O numbers, 33
I/O points, refreshing, 282, 283
I/O response time, one-to-one link communications, 339
I/O response times, 333
I/O status, maintaining, 42
I/O table clearing, 89 reading, 87 registration, 84 verification, 86
Verification Error flag, 43
I/O Units. See Units
I/O word allocation, 31 definition, 31 limits, 31 incrementing, 205 indirect addressing, 119 input bit application, 31 definition, 3 input device, definition, 3 input point, definition, 3 input signal, definition, 3 instruction set, 443
Index
7SEG(––), 302
ADB(50), 220
ADD(30), 206
ADDL(54), 207
AND, 68, 129 combining with OR, 69
AND LD, 71, 130 combining with OR LD, 73 use in logic blocks, 72
AND NOT, 68, 129
ANDW(34), 251
APR(69), 240
ASC(86), 195
ASFT(17), 157
ASL(25), 154
ASR(26), 154
AVG(––), 236
BCD(24), 182
BCDL(59), 183
BCMP(68), 174
BCNT(67), 284
BIN(23), 181
BINL(58), 182
BSET(71), 160
CLC(41), 206
CMP(20), 170
CMPL(60), 173
CNT, 145
CNTR(12), 148
COLL(81), 164
COLM(64), 202
COM(29), 250
CPS(––), 179
CPSL(––), 180
DBS(––), 232
DBSL(––), 233
DEC(39), 205
DIFD(14), 109, 131–132 using in interlocks, 136 using in jumps, 138
DIFU(13), 109, 131–132 using in interlocks, 136 using in jumps, 138
DIST(80), 162
DIV(33), 213
DIVL(57), 214
DMPX(77), 189
DSW(––), 305
DVB(53), 225
END(01), 70, 124, 138 execution times, 324–332
FAL(06), 276
FALS(07), 276
FCS(––), 284
FDIV(79), 215
FPD(––), 286
HEX(––), 196
HKY(––), 309
HMS(66), 185
IL(02), 105, 135–137
ILC(03), 105, 135–137
INC(38), 205
INT(89), 263
IORF(97), 282
JME(05), 137
495
PID(––), 243
RECV(98), 294
RET(93), 260
ROL(27), 155
ROOT(72), 218
ROR(28), 155
RSET, 133
RXD(––), 298
SBB(51), 222
SBN(92), 260
SBS(91), 258
SCAN(18), 277
SCL(––), 199
SDEC(78), 192
SEC(65), 184
SEND(90), 292
SET, 133
SFT(10), 150
SFTR(84), 152
SLD(74), 156
SNXT(09), 267
SRCH(––), 290, 291
SRD(75), 156
STC(40), 206
STEP(08), 267
SUB(31), 208
JMP(04), 137
JMP(04) and JME(05), 107
KEEP(11), 133 in controlling bit status, 109 ladder instructions, 67
LD, 68, 129
LD NOT, 68, 129
LINE(63), 201
LMSG(47), 280
MAX(––), 234
MBS(––), 230
MBSL(––), 231
MCMP(19), 169
MCRO(99), 261
MIN(––), 235
MLB(52), 225
MLPX(76), 186
MOV(21), 159
MOVB(82), 166
MOVD(83), 167
MPRF(61), 283
MSG(46), 279
MTR(––), 314
MUL(32), 212
MULL(56), 213
MVN(22), 159
NOP(00), 138
NOT, 66 operands, 64
OR, 69, 129 combining with AND, 69
OR LD, 72, 130 combining with AND LD, 73 use in logic blocks, 73
OR NOT, 69, 129
ORW(35), 252
OUT, 70, 130
OUT NOT, 70, 130
496
Index
SUBL(55), 210
SUM(––), 238
TCMP(85), 176
TERM(48), 78, 281 terminology, 64
TIM, 139
TIMH(15), 143
TKY(––), 312
TRSM(45), 278
TTIM(87), 144
TXD(––), 300
WDT(94), 282
WSFT(16), 157
XCHG(73), 162
XFER(70), 161
XFRB(62), 168
XNRW(37), 254
XORW(36), 253
ZCP(88), 177
ZCPL(––), 178 instruction sets
ADBL(––), 226
NEG(––), 203
NEGL(––), 204
SBBL(––), 228 instructions advanced I/O, 302 designations when inputting, 94 instruction set lists, 125
IORF(97), 339 mnemonics list, ladder, 125 instructions tables, 8 interlocks, 135–137 using self-maintaining bits, 109 interrupts, 254 control, 263
IOM data, reading/writing Memory Cassette data, 387
IOM HOLD BIT STATUS, PC Setup, 59
IR area, 31–33
J jump numbers, 137 jumps, 137–138
K keyboard mapping, 368 expansion keyboard mapping, 367
L ladder diagram branching, 103
IL(02) and ILC(03), 105 using TR bits, 103 controlling bit status using DIFU(13) and DIFD(14), 109, 131–132 using KEEP(11), 133–139 using OUT and OUT NOT, 70
using SET and RSET, 133 converting to mnemonic code, 66–78 display via LSS, 65 instructions combining, AND LD and OR LD, 73 controlling bit status using KEEP(11), 109 using OUT and OUT NOT, 130 format, 118 notation, 118 structure, 65 using logic blocks, 71 ladder diagram instructions, 129–130
Ladder Support Software. See peripheral devices
LEDs. See CPU indicators leftmost, definition, 27
Link System, flags and control bits, 39–41
Link Units
See also Units flags, 54
PC cycle time, 323 logic block instructions, converting to mnemonic code, 71–77 logic blocks. See ladder diagram logic instructions, 250–254
LR area, 61
LSS. See peripheral devices
Index
O one-to-one link, wiring, 382 one-to-one link communications, I/O response timing, 339 operand bit, 66 operands, 118 allowable designations, 118 requirements, 118 operating modes, 80 operation, preparations, 80–91
Optical I/O Unit, Error flag, 50 output bit application, 31 controlling, via Output OFF bit, 42 controlling ON/OFF time, 131 controlling status, 108, 109 definition, 3 output device, definition, 3 output point, definition, 3 output signal, definition, 3
M mapping, expansion keyboard mapping, 367 memory all clear, 82 memory areas, 453 clearing, 82 definition, 25
Memory Cassette, installing, 21
Memory Cassettes transferring C200H programs, 11
UM Area/IOM data, 386 memory clear, 84 memory partial clear, 83 messages, programming, 279, 280 mnemonic code, converting, 66–78 models, C200HS, 433 modifying data, hex/binary, 352 monitoring binary, 359 differentiation monitoring, 357 monitoring 3 words, 358 mounting Units, location, 19
N nesting, subroutines, 259 non-fatal operating errors, 393 normally closed condition, definition, 66
NOT, definition, 66
P password, entering on Programming Console, 81
PC configuration, 18 definition, 3 flowchart, 319
PC Link Systems error bits and flags, 40–41
LR area application, 61
PC Setup, 58 default, 58
PC SETUP, HEX INPUT, 59 peripheral devices, 5
Ladder Support Software (LSS), 5
Programming Console, 5, 78–80 peripheral port, communications receiving, 381 transmitting, 380 power supply, Power OFF Counter, 54 precautions, general, xiii present value. See PV program execution, 114
Program Memory setting address and reading content, 92–93 structure, 66 programming checks for syntax, 96–98 entering and editing, 93 example, using shift register, 151 inputting, modifying and checking, 92–108 inserting and deleting instructions, 100–102 instructions, 443 jumps, 107 precautions, 112 preparing data in data areas, 160 searching, 99–100 setting and reading from memory address, 92 simplification with differentiated instructions, 132 writing, 64
497
Programming Console, 78–80
See also peripheral devices programs, transferring from C200H, 11
PV accessing via PC area, 60
CNTR(12), 149 timers and counters, 139
R
Racks, types, 18
Remote I/O Systems, error bits and flags, 39 response time calculations, C500 PCs, 337 response times, I/O, 333–343 rightmost, definition, 27
RS-232C communications one-to-one link, 382 procedures, 379 receiving, 381 transmitting, 380 connecting Units, 382
RS-232C connector, 17
RS-232C port, wiring example, 377
RS-232C SETUP, PC Setup, 59
S self-maintaining bits, using KEEP(11), 134 set value. See SV settings communications, host link, 377
PC Setup, 58 seven-segment displays, converting data, 192 shift registers, 150–158 controlling individual bits, 151 signed binary arithmetic flags, 451 signed binary data, 29
Special I/O Unit Default Area, 56
Special I/O Units. See Units
SR area, 33–48 stack operation
COLL(81), 164
DIST(80), 162
STARTUP MODE, PC Setup, 59
STARTUP SETTINGS, PC Setup, 59 status indicators. See CPU indicators step execution, Step flag, 44 step instructions, 267–276 subroutine number, 260 subroutines, 254–266
SV accessing via TC area, 60 changing, 362
CNTR(12), 149 timers and counters, 139
498
Index switches, DIP. See DIP switch
SYSMAC LINK, loop status and completion codes, 37
SYSMAC LINK System
Active Node Flags, 52 instructions, 292 service time, 52
SYSMAC NET, loop status and completion codes, 37
SYSMAC NET Link System
Data Link Table transferring, 90 instructions, 292 service time, 52
T
TC area, 60
TC numbers, 60, 139
TERMINAL mode, 78
Key Bits, 53 time, reading and setting the clock, 367 timers bits in TC area, 60 changing SV, 362 conditions when reset, 140, 144
TTIM(120), 145 example using CMP(20), 171 extended timers, 141 flicker bits, 143 inputting SV, 94
ON/OFF delays, 141 one-shot bits, 142
TR area, 61
TR bits, use in branching, 103 tracing
See also See data tracing and address tracing.
flags and control bits, 54
U
UM Area allocation to expansion DM, 366 reading/writing Memory Cassette data, 386
UM area, 61
Units definition, 3
High-density I/O Units, definition, 4
I/O Units, definition, 3
Link Units, definition, 4
Special I/O Units, definition, 4 unsigned binary data, 29
W watchdog timer, 321 extending, 282 word bit, definition, 27 work word, definition, 27
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W235-E1-05
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Date Revised content Revision code
1
2
January 1994
August 1994
Original production
Host Link Commands have been added as Section 10.
Page 5: Available manuals table undated.
Page 16: Paragraph and table added at top of page.
Page 17: New CPU models and indicators graphics added.
Page 19: New C200H CPU capabilities table added.
Page 20: New C200HS CPU capabilities table added.
Pages 31, 381: Functions redefined for SR 264 and SR 265.
Page 34: New information added to SR Area table.
Page 48: First table under 3-5 AR (Auxiliary Relay) Area replaced. AR Area Flags and Control
Bits table corrected.
Page 51: 3-5-4 SYSMAC LINK System Data Link Settings added.
Page 52: 3-5-6 Active Node Flags added.
Page 52: 3-5-7 SYSMAC LINK/SYSMAC NET Link System Service Time (CPU31-E/33-E) added.
Page 90: 4-6-9 SYSMAC NET Link Table Transfer added.
Page 125: Commands SEND(90) and RECV(98) added to tables.
Page 291: 5-26-1 Network Instructions added.
Page 329: SEND(90) and RECV(98) added to tables.
Page 399: 9-6 Host Link Errors added.
Page 359: New CPU models added.
Page 363: SYSMAC NET Link and SYSMAC LINK models added.
Page 366: SYSMAC NET Link and SYSMAC LINK optical fiber product information added.
Appendix B : Information added to Instructions table.
Appendix C : Information added to Instructions table.
Appendix D : Information added to SR and AR Memory tables.
499
Revision code
2A
Date
April 1995
Revision History
Revised content
The following instructions have been corrected: ASFT(––) to ASFT(17), XFRB(––) to XFRB(62),
MCMP(––) to MCMP(19), CMPL(––) to CMPL(60), BCMP(––) to BCMP(68), ZCP(––) to ZCP(88),
SEC(––) to SEC(65), HMS(––) to HMS(66), LINE(––) to LINE(63), COLM(––) to COLM(64),
APR(––) to APR(69), INT(––) to INT(89), SCAN(––) to SCAN(18), LMSG(––) to LMSG(47),
TERM(––) to TERM(48), MPRF(––) to MPRF(61), and BCNT(––) to BCNT(67).
Page 7: Internal auxiliary relays
Ι
and
ΙΙ
areas renamed and corrected in Increased SR Area.
Page 17: CPU Indicators descriptions corrected.
Page 21: Note added after the table.
Page 23: Functions for pin 5 corrected.
Page 34: Function of bit 09 of word 252 corrected.
Pages 36, 37: Function of bits 08 to 10 of word 269 corrected. Functions of words , 267, 270,
271, 274, and 277 to 279 corrected. Words 298 to 299 added. SYSMAC NET/SYSMAC LINK
System added.
Page 43: RS-232C Port Communications Areas added.
Page 44: “UM” changed to “Ladder Diagram”.
Page 47: Restarting Special I/O Units added.
Page 57: Note added.
Page 83: “PC Unit” corrected to “Main Rack”.
Page 139: Last sentence in Limitations replaced.
Page 154: Note removed.
Page 170: “CB+32” corrected to “CB+31” in the description. The bits for the last five ranges in the description corrected.
Page 179: Note removed.
Page 180: Note removed. Example corrected.
Pages 196, 197: Notes removed.
Page 240: The operation amount when the SV and PV match corrected from 50% to 0%.
Page 235: Note removed.
Page 241: Second graph corrected. “Step response” corrected to “Ramp response” for the bottom graph.
Page 242: “Step response” corrected to “Ramp response” for the top graph. Second graph corrected.
Page 249: “DM 6618” corrected to “DM 6622” in the diagram for Scheduled Interrupts.
Page 250: SYSMAC LINK/SYSMAC NET servicing added to Normal Interrupt Mode (C200H
Compatible). Interrupt response time and Note 1 added to High-speed Interrupt Mode
(C200HS).
Page 271: Resetting Errors rewritten.
Page 275: Third paragraph in the description for 5-25-6 TERMINAL MODE – TERM(––) corrected.
Page 277: Execution time for 5-25-9 GROUP-2 HIGH-DENSITY I/O REFRESH – MPRF(––) corrected.
Page 282: Note c) corrected.
Pages 293 to 295: RS-232C port information added. Control word and flag information corrected.
Page 297: Hardware rewritten.
Page 298: Text added to Timing. Timing chart corrected.
Page 301: Example corrected.
Pages 302, 304: Word names corrected in Using the Instruction.
Pages 302, 304, 306: Charts corrected in Using the Instruction.
Pages 312 to 317: 6-1 Cycle Time and 6-2 Calculating Cycle Time have been rewritten.
Pages 326 and 327: 6-4 I/O Response Time rewritten.
Page 353: AR area corrected to SR area. Table of corresponding keys added.
Page 355: Section 8 Communications added.
Page 364: Text added to possible correction for Memory Cassette Transfer Error.
Page 366: Text added to possible cause and correction for Too many Units. Communications
Errors added after the table.
Page 367: Error flags added to the table.
Pages 403 to 411: Standard models updated.
Page 423: Data for Special Relay Areas 1 and 2 corrected.
Pages 424 to 427: SR Area table updated to reflect SR Area table in Section 3 Memory
Areas.
Page 429: “DM 0000” corrected to “DM 6001” in DM Area (Error Log) table.
Page 432: RS-232C Port Settings added.
500
Revision code
2B
2C
3
4
05
Revision History
Date Revised content
July 1995 The following corrections and additions were made.
Page 6: SYSMAC Support Software added and LSS removed.
Pages 23 and 374: Default communications parameters changed.
Page 26: I/O Terminals and B7A Interface Unit added and macro bits corrected.
Page 31: List of Units that don’t use slot words corrected.
Pages 32, 33, 34, 39, 43, 48, 50: Group-2 B7A Interface Units and I/O Terminals added.
Page 39: Type of data stored in SR 25108 to SR 25115 corrected to BCD.
Page 44: Section added on Special Unit Error Flag
Pages 45, 46: Mode for SR 26408 to SR 26415 changed.
Page 48: Details added to first table.
Page 52: Heading shortened.
Page 120: Caution added.
Pages 215, 216: Limits for operands clarified/corrected.
Page 243: Caution added.
Pages 243, 244: Variable name changed for Y and corrected variable description.
Page 245: Bottom graphic and related description corrected.
Page 274: Explanation in last paragraph clarified.
Page 283: Execution time corrected for IORF(97).
Pages 299 to 301: CPU models specified in control word contents corrected.
Page 314: Graphic corrected.
Page 336: Description of Host Link Systems expanded.
Page 382: Last argument corrected in application example
Page 405: Top graphic corrected and “frame 2” changed to “frame 3” in second graphic.
Page 461: Default added for DM 6610 and DM 6618.
Page 462: Settings for DM 6620 bits 00 to 09 and DM 6621 bit 08 to 15 corrected.
Page 463: Default for DM 6654 bits 00 to 07 changed.
August 1996 The Precautions section was added after About this Manual.
Page 88: Special I/O Unit type “N” corrected from Host Link Unit to Position Control
Unit.
Page 110: Ladder diagram corrected for the self-maintaining bit example.
Page 158: ASFT(17) example changed.
Page 191: “Content of the source words is zero” corrected to “Content of a source word is zero” for the ER Flags.
Page 226: DVB(53) example changed.
Page 280: “SR” added to the first source word of LMSG(47).
Page 395: “Possible correction” for “I/O bus error” corrected.
Page 430: “Command Format” corrected to “Response Format” for 11-3-36 Unde-
fined Command –– IC.
May 1999
April 2001
Page 245: Proportional operation diagram corrected.
Page 283: Note and execution time information in 5-25-8 I/O REFRESH – IORF(97) corrected.
Page 321: C200H-PID jj added to Special I/O Unit Refresh.
Page xv: Minor change made to precautionary information on mounting.
Page 23: Information on pin number 5 changed.
Pages 140, 144, 145: Information on SV settings added.
Pages 433, 434, 435: Information added to tables in several places.
February 2002 Page 177: Ladder symbol removed.
501
OMRON ELECTRONICS LLC
1
Commerce Drive
Schaumburg, IL
60173
847.843.7900
For US technical support or other inquiries: 800.556.6766
OMRON CANADA, INC.
885
Milner Avenue
Toronto, Ontario M
1
B
5
V
8
416.286.6465
OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.omron.com/oei
Canada - http://www.omron.ca
W235-E1-5 1 2 /02 ©2002 OMRON ELECTRONICS LLC Specifications subject to change without notice.
Printed in the U.S.A.