Regin OPA281D-4 Controller Manual
Advertisement
Advertisement
WE TAKE BUILDING
AUTOMATION PERSONALLY
en
MANUAL
OPTIGO
ARDO
THANK YOU FOR CHOOSING REGIN!
Ever since Regin was established in 1947, we have developed and marketed products and systems that create good levels of indoor comfort. Today, we are an important player with one of the market's broadest ranges for building automation.
Our goal is to make real estates in the world more energy efficient. Regin is an international group and our products sells in over 90 countries. Thanks to our global presence with strong local representation, we are well aware of the requirements of the market, as well as of how our products and systems function under the most variable conditions.
Every year, Regin makes substantial investments in the development of our systems and HVAC-products.
DISCLAIMER
The information in this manual has been carefully checked and is believed to be correct. Regin makes no warranties about the contents of this manual and users are requested to report errors and discrepancies to Regin, so that corrections may be made in future editions. The information in this document is subject to change without prior notification.
Some product names mentioned in this document are used for identification purposes only and may be the registered trademarks of their respective companies.
© AB Regin. All rights reserved.
Rev. A, 2022-02-09
Table of Contents
Table of Contents
1 Introduction
1.1 About this manual
This manual covers all the models in the Optigo Ardo series.
The manual has the following main chapters:
✓ Information for the end user
All the information needed by the end user. How to handle the controller, including how to navigate in the menus, LED:s and indications, how to change setpoints and handle alarms etc.
✓ Information for the specialist
A comprehensive guide to all the functions of the controller.
✓ Information for the installer
Everything related to the installation of the hardware, such as wiring examples and commissioning.
✓ Appendix
Technical data, model overview, input and output lists, alarm list, terminal lists.
Special text formats used in the manual:
This box is used to show formulas and mathematical calculations
This box is used to represent the display window on the controller
1.2 More information
More information about the controller is available in:
✓ Product sheet for Optigo Ardo
✓ Instruction for Optigo Ardo
✓ List of predefined configurations for Optigo Ardo
All the above documents are available for download from Regin’s website, www.regincontrols.com
1.3 Display
There is a text display in the Optigo Ardo
The display is used to e.g. change values, set timers and monitor alarms.
Optigo Ardo manual, Rev. A 5 (76)
1.4 Upgrade and backup of Optigo
Ardo
There is an online tool available for Optigo Ardo . The tool is used to upgrade the controller and for backup and to restore the settings.
A LAN/Ethernet communication cable is required in order to connect to the controller, and the controller must also be powered up.
6 (76) Optigo Ardo manual, Rev. A
2 Information for the end user
The Optigo Ardo is a 24 V pre configured ventilation controller with display for use in ventilation applications.
2.1 LED:s and buttons
The controller has an internal text display and features 7 buttons.
2.1.1
Display
The display has 4 rows of 20 characters each. It has background illumination. The illumination is normally off, but is activated as soon as a button is pressed. The illumination will be turned off again after a period of inactivity.
2.1.2
LED:s
The controller has two LEDs in the front marked with the symbols (alarm) and (change).
Symbol Colour
Flashing red
Fixed red
Flashing yellow
Fixed yellow
Function
There are one or more unacknowledged alarms.
There are one or more remaining acknowledged alarms.
You are in a dialog box where it is possible to switch to change mode.
A quick blinking (2 times/s) indicates that the parameter can be changed using the current access level.
A slower blinking (1 time/s) indicates that a higher access level is required to change the parameter.
You are in change mode.
Status indication
Status indication LEDs can be found in the upper left corner of the Optigo Ardo .
Designation
TCP/IP
P/B (Power / Battery)
Colour
Yellow/Green
Green/Red
Description
Green: Connected to other network equipment
Blinking green: Network traffic
Blinking yellow: For identifying
Power on / Battery error
Optigo Ardo manual, Rev. A 7 (76)
2.1.3
Summary of the function of the buttons
Optigo Ardo (7 buttons)
[▲][▼][►][◄]
[OK]
Functions
Navigation buttons:
▲ Navigate upwards.
▼ Navigate downwards.
► Navigate to the right.
◄ Navigate to the left.
In change mode:
◄ Move cursor to the left.
► Move cursor to the right.
▲ Increase the value by 1.
▼ Decrease the value by 1.
▲and ▼ Scroll among the texts when there are several alternatives.
✓ Enter change mode.
✓ Confirm a new value in change mode.
An input must be confirmed with this button in order to change the value in the controller.
When a value has been confirmed, the cursor will move to the next editable value in the current box.
Function in Alarm Mode
▲ Navigate up in the alarm stack.
▼ Navigate down in the alarm stack.
◄ Exit alarm display mode.
✓ A menu with all actions that are available for the current alarm is displayed.
[C] ✓ Enter change mode and erase the value in the display.
✓ Erase the sign at the cursor.
✓ When the current value is completely empty, the edit mode is cancelled and the cursor will move to the next value that will also be erased in the window.
✓ Undo (erase) the input
✓ Closes the menu containing available alarm actions without changing the state of the alarm point.
[ALARM] ✓ Enter alarm display mode.
✓ Browse among alarms in alarm display mode.
2.2 Navigating the menus
The appearance of the start display may vary since there are several different start displays to choose from during configuration.
Optigo Ardo 1.0
2021-06-09 14:29
System: Normal run
Sp: 22.0 Act: 22.5°C
Sp and Act stand for Setpoint and Actual value.
Actual value = the current measured temperature
Setpoint = the desired configured temperature
You can navigate through the menu choices at this level by pressing the [ ▼ ] and [ ▲ ] buttons.
8 (76) Optigo Ardo manual, Rev. A
Which menu items that are shown depends on the access level of the user and the configured inputs/outputs and functions.
Below, all possible menu entries are shown.
✓ Ventilation
✓ Alarm events
✓ Time settings
✓ Inputs/Outputs
✓ Configuration
✓ Alarm status
✓ Access rights
To enter a higher menu level, press the [ ► ] button when the display marker is located at the menu item you wish to enter. At each level there may be several new menus through which you may browse using the [ ▲ ] and [ ▼ ] buttons.
When there are further submenus linked to a menu or menu item, it is indicated by an arrow symbol at the right-hand edge of the display. To choose one, press the [ ► ] button again. To return to a lower menu level, press the [ ◄ ] button.
2.3 Changing values
When you are at a position where it is possible to change one or more values, and your access level is high enough, you can edit the existing value, or enter a new one. After changing the value, you confirm the input with the [OK] button, or undo the change by pressing the [C] / [ ▼► ] buttons for a short while until the original value reappears in the window and change mode is exited. These actions are described in detail in the following sections.
2.3.1
Editing an existing value
1. Press the [OK] button to go to change mode. A flashing cursor appears. If there are multiple editable values in one menu, press the [OK] button until the value you want to change flashes.
2. Move the cursor to the right and to the left with the navigation buttons [ ► ] and [ ◄ ] .
3. The value at the cursor can now be changed in the following ways:
✓ Erase the current digit or character with the [C] / [ ▼► ] buttons.
✓ Use the [ ▲ ] and [ ▼ ] buttons to increase or decrease the value at the cursor. Editable texts can also be changed with this method.
✓ If the character at the cursor is a decimal point, you cannot browse with the [ ▲ ] and [ ▼ ] buttons.
You can however erase the decimal point with the [C] / [ ▼► ] buttons.
✓ If the cursor is placed to the right of the value, i.e. the character at the cursor is a space, you can add a decimal point with the [ ▼ ] button, or the figure 0 with the [ ▲ ] button.
✓ If you require a negative number, move the cursor to the leftmost position and press the [ ▼ ] button to get a minus sign. Then edit the following digits to the required value.
✓ Scroll up [ ▲ ] and down [ ▼ ] to browse through texts when there are several texts to choose from instead of numerical values.
Optigo Ardo manual, Rev. A 9 (76)
2.3.2
Enter a completely new value
✓ Press the [C] / [ ▼► ] buttons to go to change mode. The value is erased in the window, and you have to enter a completely new value.
✓ If you require a negative number, move the cursor to the leftmost position and press the [ ▼ ] button to get a minus sign. Then edit the following digits to the required value.
✓ Press [ ▲ ] to begin the input with the digit 0, then browse to the required digit or character with [ ▲ ] and [ ▼ ] .
✓ Press [ ▼ ] to get a decimal point. When the cursor is placed at a decimal point, you cannot browse with the [ ▲ ] and [ ▼ ] buttons.
2.3.3
Confirm the change
Press [OK] to confirm the change when the required value has been entered. Then the value you see in the window will be updated in the installation.
After the value has been confirmed, the cursor will move to the next editable value in the current menu.
installation.
2.3.4
Undo an initiated change
pressing the [[C ▼ ]] buttons for a short while until the original value reappears in the window and change mode is exited.
2.4 Logging on and off
The controller has four different access levels. The choice of access level determines which menus are shown, as well as which parameters can be changed in the displayed menus.
✓ Guest level does not require logging on, and only permits changes in running mode and gives read-only access to a limited number of menus.
✓ Operator level gives the same access as Guestl level, and in addition, access to change setpoints.
✓ Service level gives the same access as Operator level, and in addition, access to change controller settings and manual mode.
✓ Admin level gives full read/write access to all settings and parameters in all menus.
2.4.1
Log on
1. Browse to Access Rights in the main menu and press [ ► ] .
Log on
Log off
Change password
10 (76) Optigo Ardo manual, Rev. A
2. Select Log on and press [ ► ] .
Log on
Enter password:****
Actual level:
None
3. Press [OK] to make a cursor marker appear at the first digit position.
4. Enter the password (4-digit code) by pressing [ ▲ ] until the correct digit is displayed. Press the [ ► ] to move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to confirm.
2.4.2
Log off
1. Go to Access Rights in the main menu and press [ ► ] .
2. Select Log off and press [ ► ] .
Log off?
No
Actual level:
Admin
3. Select Yes and press [OK] .
2.4.3
Change password
1. Go to Access Rights in the main menu and press [ ► ] .
2. Select Change password and press [ ► ] .
Change password for level:Operator
New password: ****
3. Select Yes and press [OK]
4. Press [OK] to enter change mode.
5. Use the [ ▲ ] and [ ▼ ] buttons to browse and select the access level to change the password for, and press
[OK] to confirm.
Optigo Ardo manual, Rev. A 11 (76)
6. Enter the new password (4-digit code) by pressing [ ▲ ] until the correct digit is displayed. Press the [ ► ] to move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to confirm.
The following passwords are the default for the different access levels:
Access level
Admin
Service
Operator
Guest
Password
1111
2222
3333
5555
You can only change the password for access levels lower or equal to the presently active level, i.e. if you are logged in as Admin you can change all passwords, but as Operator you can only change the
Operator and Guest passwords. There is no point in changing the Guest password since access to that level is granted automatically to all users.
would prevent access to the higher of these two access levels. This is especially important for word can be obtained from Regin. This code is date dependent and valid for one day only.
2.4.4
Automatic logoff
When logged in as Operator , Service or Admin , the user will automatically be logged off to Guest after a settable time of inactivity (the default is 60 seconds). It is possible to disable the automatic logoff.
Change password to remove automatic logoff
If you want to remove the automatic logoff, change the password of the desired level to 0000. This can be very useful in certain cases if the unit is intended to be used by trained personnel or, for instance, during commissioning.
ously given that a certain level has been activated.
2.5 Menu structure
The display is used to select predefined configurations for the system, and to change some settings.
Start menu:
Ventilation
Alarm events
Time settings
Inputs/Outputs
Configuration
Alarm status
Access rights
12 (76) Optigo Ardo manual, Rev. A
2.5.1
Ventilation
Ventilation has up to seven submenus:
Actual/Setpoint
Temperature control
Fan control
Demand control
PID controllers
Manual/Auto
Status
Actual/Setpoint
In this submenu, you can read all the actual values of the configured inputs of the circuit. For more information, see
Temperature control
In this submenu, you can read and set all the setpoints for the selected circuit. You need Operator or higher access level to be able to change setpoints. For more information see
.
Fan control
In this submenu, settings of the fan can be read and set. It is only visible for access level Operator and higher, and only editable for access level Service and higher. For more information, see
Demand control
In this submenu, settings for Demand control can be read and set. It is only visible for access level Operator and higher, and only editable for access level Service and higher. For more information, see
PID control
In this submenu, the control parameters can be read and set. It is only visible for access level Operator and higher, and only editable for access level Service and higher. For more information, see
Manual/Auto
In this submenu, the ventilation unit can be set to manual mode. It is only visible for access level Operator and higher, and only editable for access level Service and higher.
For more information, see
.
Status
In this submenu, the status of the ventilation unit can be read.
Each function also has different sub-statuses. For more information, see
Optigo Ardo manual, Rev. A 13 (76)
2.5.2
Time settings
Optigo Ardo has a year-based clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over.
It has individual schedules for each weekday plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules take precedence over other schedules.
Each day has up to four individual running periods. There are daily individual schedules for low speed, normal speed and high speed of the fan, each with up to four running periods.
One output can be used as a timer controlled output, with individual week-schedules with four activation periods per day. This output can be used to control lighting, door locks etc.
The Time settings menu contains the submenus Time schedule , Holiday schedule and Time/Date .
Time schedule
Holiday schedule
Time/Date
Time settings
Fan low speed
Fan normal speed
Fan high speed
Extra time channel
In the time schedules, four periods are available for each day of the week. Also, four periods are available for days that are configured as holidays in the holiday schedule. During the periods the assigned circuit is working with the corresponding setpoint. Outside of a period the system is off.
On On
Off
B2
Figure 2-1 Time schedule
E2
Off
B1 E1
Off
Begin/End
The above figure shows an example of period states. It is not possible for periods to overlap each other.
Timer Low speed, Normal speed, High speed
There are sixteen separate settings menus for each timer channel, two for each weekday and two extra for holidays. Holiday schedules take precedence over other schedules.
14 (76) Optigo Ardo manual, Rev. A
For 24 hour running, set a period to 00:00 - 24:00.
To inactivate a period, set the time to 00:00 - 00:00. If all periods of a day are set to 00:00 - 00:00, the unit will not run that day.
Normal speed
Monday Per3-4 >
Per 1: 00:00 - 24:00
Per 2: 00:00 - 00:00
Normal speed
Monday
Per 3: 00:00 - 00:00
Per 4: 00:00 - 00:00
If you want to run the unit from one day to another, e.g. from Monday 22:00 to Tuesday 09:00, the desired running time for both must be entered.
Normal speed
Monday
Per 1: 22:00 - 24:00
Per 2: 00:00 - 00:00
Normal speed
Tuesday
Per 1: 00:00 - 09:00
Per 2: 00:00 - 00:00
Should periods for the different speeds overlap, high speed takes precedence over normal speed, and normal speed takes precedence over low speed.
Extra time channel
One digital output can be used as a timer controlled output with individual week-schedules and four activation periods per day. The output has sixteen separate setting menus; two for each weekday and two extra for holidays. Holiday schedules take precedence over other schedules.
Extra time channel1
Wednesday Per3-4 >
Per 1: 00:00 - 00:00
Per 2: 00:00 - 00:00
Extra time channel1
Wednesday
Per 3: 00:00 - 00:00
Per 4: 00:00 - 00:00
Parameters (Fan normal speed)
Name
Monday Per.1 Start
Monday Per.1 End
Monday Per.2 Start
Monday Per.2 End
Monday Per.3 Start
Monday Per.3 End
Monday Per.4 Start
Monday Per.4 End
...
Unit Min hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00
Max
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
Default Description
00:00 Start of period 1 Mondays.
24:00
00:00
00:00
00:00
00:00
00:00
00:00
End of period1 Mondays.
Start of period 2 Mondays.
End of period 2 Mondays.
Start of period 3 Mondays.
End of period 3 Mondays.
Start of period 4 Mondays.
End of period 4 Mondays.
Optigo Ardo manual, Rev. A 15 (76)
Name
Holiday Per.1 Start
Holiday Per.1 End
Holiday Per.2 Start
Holiday Per.2 End
Holiday Per.3 Start
Holiday Per.3 End
Holiday Per.4 Start
Holiday Per.4 End
Unit Min hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00
Max
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
Default Description
00:00 Start of period 1 holidays.
00:00 End of period 1 holidays.
00:00
00:00
00:00
00:00
00:00
00:00
Start of period 2 holidays.
End of period 2 holidays.
Start of period 3 holidays.
End of period 3 holidays.
Start of period 4 holidays.
End of period 4 holidays.
Parameters (Fan low and high speed, Extra time channel)
Name
Monday Per.1 Start
Monday Per.1 End
Monday Per.2 Start
Monday Per.2 End
Monday Per.3 Start
Monday Per.3 End
Monday Per.4 Start
Monday Per.4 End
...
Holiday Per.1 Start
Holiday Per.1 End
Holiday Per.2 Start
Holiday Per.2 End
Holiday Per.3 Start
Holiday Per.3 End
Holiday Per.4 Start
Holiday Per.4 End
Unit Min hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
Max
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Default Description
00:00 Start of period 1 Mondays.
00:00
00:00
00:00
End of period 1 Mondays.
Start of period 2 Mondays.
End of period 2 Mondays.
00:00
00:00
00:00
00:00
Start of period 3 Mondays.
End of period 3 Mondays.
Start of period 4 Mondays.
End of period 4 Mondays.
Start of period 1 holidays.
End of period 1 holidays.
Start of period 2 holidays.
End of period 2 holidays.
Start of period 3 holidays.
End of period 3 holidays.
Start of period 4 holidays.
End of period 4 holidays.
Holiday schedule
The system operator can define specific periods of operation or non-operation throughout the year. During these defined periods, the settings in the week schedule do not apply. The holiday schedule provides 24 periods. All holiday periods are working with a special day plan with a maximum of 4 periods.
A holiday period can be any number of consecutive days from 1…365. The dates are in the format: MM:DD.
When the present date falls within a holiday period, the scheduler will use the settings for the weekday
Holiday .
Parameters
Name
Holiday Per.1 Start
Holiday Per.1 End
...
Unit Min
MM:DD 01:01
MM:DD 01:01
Max
12:31
12:31
Default Description
01:01 The start date of holiday period 1.
01:01 The end date of holiday period 1.
16 (76) Optigo Ardo manual, Rev. A
Name
Holiday Per.24 Start
Holiday Per.24 End
Unit Min
MM:DD 01:01
MM:DD 01:01
Max
12:31
12:31
Default Description
01:01 The start date of holiday period 24.
01:01 The end date of holiday period 24.
Time/Date
This menu displays time, date and weekday, and it permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD.
2.5.3
Inputs/Outputs
In the sub menu Inputs/Outputs you can find raw values and analog and digital inputs and outputs. For more information see
Raw values
Analog inputs
Digital inputs
Analog outputs
Digital outputs
2.5.4
Mode switch
In addition to the items in the main menu, there is also an extra menu called Mode switch , that is reached by pressing [ ► ] in the main menu. The mode switch changes the operation of the system.
Mode switch position
0 — Off
1 — Auto
2 — Low speed
3 — Normal speed
4 — High speed
Manual mode Off. System is switched off. No control function.
Automatic mode. Control function depending on timer and settings.
Manual mode. System is forced to low speed of the fans.
Manual mode. System is forced to normal speed of the fans.
Manual mode. System is forced to high speed of the fans.
2.6 Alarm handling
Alarms are indicated by the red alarm LED on the front of the unit. If an alarm condition occurs, an alarm is logged in an alarm list. The list shows the type of alarm, the alarm date and time and the alarm priority (A, B or C alarm).
2.6.1
Alarm priorities
Alarms can be given different priority levels: A alarm , B alarm , C alarm or not active . There is one digital output that can be used as alarm output: Sum alarm .
✓ A and B alarms activate the sum alarm output, if it has been configured.
✓ Class C alarms are removed from the alarm list when the alarm input resets even if the alarm has not been acknowledged.
Optigo Ardo manual, Rev. A 17 (76)
2.6.2
Inspect alarms
✓ Press the alarm buttons [ALARM] / [ ◄▲ ] to display the alarms.
✓ If there is more than one alarm at the same time, this is indicated by up/down arrow symbols at the right-hand edge of the display. You can browse among them in two ways:
1. By using the navigation buttons [ ▼ ] and [ ▲ ] .
2. By pressing the alarm buttons [ALARM] / [ ◄▲ ] several times.
✓ Press [ ◄ ] to exit alarm handling and return to the previous menu.
2.6.3
Acknowledge, block and unblock alarms
✓ Press the [OK] button to get a menu with the available alarm actions for the currently displayed alarm.
✓ Select the required alarm action with the buttons [ ▼ ] and [ ▲ ] .
✓ Press the [OK] button to execute the action.
At the left end of the bottom display line the alarm status is shown. For active, unacknowledged alarms the space is blank. Alarms that have been reset are indicated by the text Acknowledged . Active or blocked alarms are indicated by the text Acknowledged or Blocked .
Acknowledged alarms will remain on the alarm list until the alarm input signal resets.
Blocked alarms remain on the alarm list until the alarm has been reset and the block has been removed. New alarms of the same type will not be activated as long as the block remains.
to block alarms.
Alarm events
In the Alarm Events menu, there is an alarm log which contains the 100 latest alarm events. The latest event is shown at the top of the list. The alarm log is only used to view alarm history, which may simplify troubleshooting of the installation.
18 (76) Optigo Ardo manual, Rev. A
Information for the specialist
3 Information for the specialist
3.1 Function overview
The selected control modes and activated functions depends on the selected configuration. Find more information about the available configurations in the document Optigo Ardo 1.0 - Predefined configurations, which is available on Regin's homepage www.regincontrols.com
. A description about the activation of a configuration will be found in chapter
4.1 Predefined configurations in Optigo Ardo .
The program for an air handling unit contains, apart from other things, the following functions:
Different temperature control modes
✓ Supply air temperature control
✓ Room temperature control (cascade control)
✓ Extract air control (cascade control)
With control of:
✓ Heat exchangers (plate)
✓ Mixing dampers
✓ Heating coil (water with or without frost protection, electric with high temperature limit switch)
✓ Cooling (water)
✓ Circulation pumps
Fan control
✓ 1- or 2-speed supply air and extract air fans
✓ Manual control of fans
Timer control
For starting and stopping the unit, annual clock function. One output for control of external functions such as lighting, door locks etc.
Demand controlled ventilation
In buildings with strongly varying occupancy, the fan speeds or mixing dampers can be controlled by the air quality measured by a CO
2 sensor.
Support control
When using the control function room control or extract air temperature control, it is possible to utilise support-heating and/or support-cooling.
Free cooling
When this function has been activated, it is used during the summer to cool the building during the night using cool outdoor air, thereby reducing the need to run chillers during the day.
Free heating
If the outdoor temperature is higher than the indoor temperature and there is a heating demand, the recovery damper will not open for recovery but instead open fully for outdoor air. This may occur during low night-time outdoor temperatures, when the room has been cooled considerably and the outside heat is rising faster than indoors. This function is activated at the same time as Free cooling .
Cooling recovery
If the cooling recovery has been configured, there is a cooling requirement and the extract air or room temperature is a settable amount lower than the outdoor temperature, thus cooling recovery can be
Optigo Ardo manual, Rev. A 19 (76)
Information for the specialist
activated. When cooling recovery is activated the heat exchanger and damper sequence output signal will be activated in the cooling demand. The function also activates the heating function Free heating : if heating is required and the outdoor temperature is higher than the extract air or room temperature, outdoor air will primarily be used.
Change-over
In 2-pipe systems where a combination heater/cooler is operating together with a heat pump, change-over is a function that enables using the same pipe for both heating and cooling, depending on which is currently required.
20 (76) Optigo Ardo manual, Rev. A
Information for the specialist
3.2 Temperature control
3.2.1
General
Optigo Ardo has a choice of the following control modes:
1. Supply air
2. Room cascade
3. Extract air cascade
The supply air temperature controller is reverse acting, i e. the output will increase for decreasing temperature. The temperature at the supply air sensor will be constantly kept at the user setpoint value. The controller is a PID-controller with settable P-band, I-time and D-time.
In the Room cascade and Extract air cascade modes the supply air is controlled as part of a cascade controller together with the room/extract temperature controller. The room/extract temperature offset will dictate the supply air temperature setpoint.
3.2.2
Control modes
Read more about configuration of the control modes in
Supply air control
The supply air temperature is kept at the setpoint value by controlling the output signals for the sequences.
A single PI control loop is used.
The actual setpoint for the supply air temperature will be limited to a settable minimum and maximum.
Settings and configuration for Supply air control
Table 3-1 Path to configuration and settings for Supply air control
Feature
Configure input 1
Menu path in display
Configuration ►Inputs/Outputs►Analog inputs►Supply air temperature
Sensor type selection
Controller output
Neutral zone setting
2 Configuration ►Inputs/Outputs►Analog inputs►Supply air temperature
Ventilation►Actual/Setpoint►-
Supply air controller
Ventilation ►Actual/Setpoint►-
Supply air controller
Min / Max limit supply air Ventilation ►Actual/Setpoint►-
Supply air controller
Setpoint supply air Ventilation ►Actual/Setpoint►-
Supply air controller
1. Configured according to config-file, but can be changed.
2. Configured according to config-file, but can be changed.
Variable
Sensor type
Controller output (%)
Neutral zone (C°)
Min / Max limit supply air (C°)
Setpoint supply air
Note
Room cascade
Cascade control of room temperature and supply air temperature to achieve a constant, settable room temperature. The room controller output signal (0-100%) generates the supply air controller’s setpoint value between min and max supply setpoint.
Optigo Ardo manual, Rev. A 21 (76)
Information for the specialist
The room temperature is kept at the setpoint value by controlling the output signals for the sequences. Two
PI loops are used.
Settings and configuration for Room cascade control
Table 3-2 Path to configuration and settings for Room cascade
Feature Menu path in display Variable
Configure input 1 Configuration ►Inputs/Outputs►Analog inputs►Room air temperature
Setting of P-band and I-time
Setpoint room temperature
Ventilation ►PID►Room air controller
Ventilation ►Actual/Setpoint►-
Room air controller
Setpoint room temperature
Setpoint adjustment Ventilation ►Actual/Setpoint►-
Room air controller
1. Configured according to config-file, but can be changed.
Setpoint adjustment
Note
Extract air cascade
Cascade control of extract air temperature and supply air temperature to achieve a constant, settable room temperature. The extract air controller output signal (0-100%) generates the supply air controller’s setpoint value between min and max supply setpoint.
The extract air temperature is kept at the setpoint value by controlling the output signals for the sequences.
Two PI loops are used.
Settings and configuration for Extract air cascade control
Table 3-3 Path to configuration and settings for Extract air cascade
Feature
Configure input 1
Menu path in display
Configuration ►Inputs/Outputs►Analog inputs►Extract air temperature
Setting of P-band and I-time Ventilation ►PID► Extract air controller
Setpoint extract air temperature Ventilation ►Actual/Setpoint►Extract air controller
Setpoint adjustment Ventilation ►Actual/Setpoint►Extract air controller
1. Configured according to config-file, but can be changed.
Variable
Setpoint extract air
Setpoint adjustment
Note
3.3 Temperature sequences
The supply air controller output is either a heating demand or a cooling demand depending on if the supply temperature is over or under the setpoint. This demand is then divided into up to 4 sequences A to D. Each sequence is configured as Heating , Cooling , Exchanger , Damper , or Not used depending on the selected configuration.
Each sequence has it own PID-settings that can be set in the Ventilation menu in the display.
Each of these output sequences can be bound to either an analog output, to one pulse-width modulated
(PWM) digital output with a settable period time, or to a start/stop digital output.
22 (76) Optigo Ardo manual, Rev. A
Information for the specialist
3.3.1
Heater
Heater types
Water heating
Control
If a sequence is configured as water heating, it’s possible to select if the sequence should be controlled with freeze protection. The sequence is controlled by the corresponding sequence analog output.
Table 3-4 Settings and configuration for water heater
Feature Menu path in display
Freeze protection temperature Configuration►Inputs/Outputs►Analog inputs►
Freeze protection temperature
Analog output Configuration►Inputs/Outputs►Analog outputs►
Heater
Variable
✓ Sensor type
✓ Filter factor
✓ Compensation
✓ Actual value
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Note
Freeze protection
The heater return water temperature is measured using the analog input Freeze protection temperature . Low temperatures will generate an internal, proportional signal that is used to force the heating valve open, thereby preventing freeze-up of the heater.
The internal signal will begin to rise as the frost protection temperature falls below the Alarm limitation running mode + P-band running mode in order to reach 100 % output when the signal has fallen to Alarm level .
When the internal signal reaches 100 %, the unit is shut down, the heating output is set to completely open mode and an alarm is activated. .
protection sensor has risen above Alarm limitation running mode + P-band running mode .
Optigo Ardo manual, Rev. A 23 (76)
Information for the specialist
Internal signal
100 %
Prop. band
0 %
Alarm level Freeze protection sensor
Figure 3-1 Freeze protection
Table 3-5 Settings and configuration for freeze protection
Feature
Configuration of freeze protection temperature,
Freeze protection setpoints
PID-settings
Menu path in display
Configuration ►Inputs/Outputs►Analog inputs ► Freeze protection temperature
Variable
✓ Sensor type
✓ Filter factor
✓ Compensation
✓ Actual value (read only)
Ventilation ► Temperature control ► Freeze protection
✓ Alarm limitation running mode
✓ P-band running mode
✓ Setpoint standby mode
Ventilation ► Temperature control ► Freeze protection
Note
Standby mode
If frost protection is activated the controller will go into Standby mode when the running mode switches to
Off . The controller will then control the heating output to maintain a constant temperature at the frost protection sensor. The setpoint for the standby mode is found in Ventilation ► Temperature control ► Freeze protection
Electric heating
Electric heating is controlled using the analog output sequence. On activation of the digital input Overheated electric heater the unit will be shut down, either according to the stop sequence or as an emergency shutdown. The unit will restart after the alarm has been acknowledged and Overheated electric heater has reset. Note that activation of the input signal Flow guard will also stop the unit.
24 (76) Optigo Ardo manual, Rev. A
Information for the specialist
Control voltage
Relay electric heating
High limit thermostat
Optigo
Control voltage
Auxiliary relay
Figure 3-2 Wiring example, high temp. limit. Contactors are drawn inactivated.
the heater to ensure that the heating is shut down when the thermostat is activated even if the Optigo Ardo should be faulty.
Table 3-6 Settings and configuration for electric heating
Feature
Overheating
Flow guard
Alarm
Menu path in display
Configuration ►Inputs/
Outputs► Digital inputs ►
Overheated electric heater
Configuration ►Inputs/
Outputs► Digital inputs ► Flow guard
Alarm status
Variable Note
Fast stop on overheating
Fast stop is an option in Alarm - Electric heating is overheated . The function means that the fans will be immediately stopped when there is an overheating alarm, regardless of the set cool-down time. It is set in
Alarm status ► Electric heating is overheated ► Edit ► Alarm action.
Optigo Ardo manual, Rev. A 25 (76)
Information for the specialist
3.3.2
Exchanger
Control
The airflow through the exchanger is controlled by a shut-off damper and a bypass damper. Both dampers are controlled by the same analog output.
Defrosting
Defrosting is activated when the value of the analog input Defrosting temperature falls below the de-icing limit (-3°C).
It is deactivated when the analog signal rises above the limit value plus a settable differential ( Ventilation ►
Temperature control ► Exchanger ► Hysteresis ).
A PI-controller compares the defrosting setpoint with the signal Defrosting guard exchanger . The lesser of the output signal from this controller and the output from the ordinary controller is used as output to the bypass dampers.
Freeze protection
A defrosting sensor can be used as a prevention sensor. It is possible to set a starting temperature in
Ventilation ► Temperature control ► Exchanger ► Defrosting setpoint and Min time . This represents both the minimum time that the function should be active, the supply air fan (SAF) and extract air fan (EAF) compensation, as well as the minimum time before the next prevention cycle should begin. While the cycle is active, Defrosting mode is shown in the display.
Table 3-7 Configuration and settings for Plate exchanger
Feature
Exchanger control, Analog
Output
Defrosting exchanger
Defrosting temperature
Extract air fan speed when defrosting
Temperature setpoints
Hysteresis setpoints
Delay setpoints
Menu path in display
Configuration ► Analog inputs
► Defrosting temperature
Variable
Configuration ► Analog output Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Configuration ► Function config.► Temperature control
Defrosting exchanger
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Actual value (°C)
Configuration ► Function config.► Temperature control
Extract air fan speed when defrosting with stopped supply air
Note
Yes / No
✓ Auto
✓ Low
✓ Normal
✓ High
Ventilation ► Temperature control ► Exchanger
Ventilation ► Temperature control ► Exchanger
✓ Outdoor start / stop exchanger temperature (°C)
✓ Defrosting setpoint limit (°C)
✓ Stop supply air time if outdoor temp < (°C)
✓ Hysteresis (°C)
✓ Hysteresis to stop defrosting
(°C)
Ventilation ► Temperature control ► Exchanger
✓
✓
Start delay exchanger (s)
Start delay with 100 % exchanger (s)
✓ Start alarm delay (s)
26 (76) Optigo Ardo manual, Rev. A
Information for the specialist
3.3.3
Cooler
Control
If a cooler is configured, it’s controlled by the corresponding sequence analog output.
Table 3-8 Settings and configuration for water cooling
Feature
Analog output
PID settings
Menu path in display Variable
Configuration ► Analog outputs
► Cooler
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Ventilation ► PID controllers ►
Cooler
Description
3.3.4
Mixing damper
Control
The analog output signal controls two dampers for gradual mixing of outdoor air and recirculated air. In this mode the output signal decreases with decreasing heat demand.
CO
2
If demand controlled ventilation is activated in combination with mixing dampers, CO
2
-control is activated for the sequence, and the CO
2
-value rises above the setpoint value, the dampers will let in more outdoor air.
The function is controlled by a PI-controller.
Table 3-9 Settings and configuration for CO
2 and mixing dampers
Feature
CO
2 setpoint
Menu path in display
Ventilation ► Demand control
► CO2
Variable
✓ Setpoint mixing damper
(ppm)
✓ Start limit fan start / stop
(ppm)
✓ Stop hysteresis fan start / stop (ppm)
✓ Demand control
✓ Min time for CO2 control
(min)
PI settings Ventilation ► PID controllers ►
CO2
Note
Minimum limit
An outdoor air minimum limit for the amount of fresh air can be set. The limit value is settable between 0 and 100 %. For example: to reach a minimum of 20 % fresh air you need to set the max limit of the sequence to 80 %. (Configuration ► Function config.
► Sequence x ► Sequence output min limit (%) and Sequence output max limit (%)
Optigo Ardo manual, Rev. A 27 (76)
Information for the specialist
3.4 Fan control
3.4.1
Fan levels
Frequency controlled fans, EC-fans or fans with 2-step control work with the Optigo Ardo . The fan can be set to Low, Normal or High speed. The selection of the fan speed defines which time channel will be active in the application.
The fans will always start directly with the desired speed.
The extract air fan and the supply air fan have individual start and stop delays which are normally set so that the extract air fan is started before the supply air fan. If there are not enough digital outputs for individual control, both fans will have to be started using the signal for the supply air fan, and the delay will be created using an external time relay.
3.5 CO
2
control
In applications with varying occupancy the fan speeds or mixing dampers can be controlled by the air quality as measured by a CO
2 sensor.
With the CO
2 function it’s possible to start and stop the fans, compensate the fan speed and in combination with mixing damper let in more outdoor air depending on the CO
2 value. This can be configured with the
CO
2 control settings.
Table 3-10 CO
2 control settings
Fan stop/start function
Mixing damper function
Fan start/stop + mixing damper
When the function is activated with start/stop function and the CO
2 value rises above settable start value the fans will start at configured speed (default: normal speed), if they are not already running.
If demand controlled ventilation is activated in combination with mixing dampers, and the
CO
2
-value rises above the setpoint value the dampers controlled by a sequence with CO
2 function will be overtaken by the CO
2 controller and let in more outdoor air. The function is controlled by a PI-controller.
If demand controlled ventilation is activated in combination with mixing dampers, and the
CO
2
-value rises above the setpoint value the dampers controlled by a sequence with CO
2 function will be overtaken by the CO
2 controller and let in more outdoor air. The function is controlled by a PI-controller.
3.6 Free cooling
This function is used during the summer to cool the building night-time using cool outdoor air, thereby reducing the need for cooling during the day and saving energy.
Free cooling requires an outdoor sensor and either a room sensor or an extract air sensor.
Free cooling is only activated when all the start conditions below are fulfilled.
✓ It is between 00:00 and 07:00 in the day (settable).
✓ The timer outputs for Normal speed, Extended running, Normal and External switch are Off .
✓ A timer channel will be On sometime during the next 24 hours.
If an extract air sensor is selected and ALL the start conditions are fulfilled, free cooling is activated and will run for 3 minutes (settable) to ensure that the temperature measurement when using an extract air sensor reflects the corresponding room temperature.
If a room sensor is selected, the unit will not start free cooling as long as all the temperatures are not within the start and stop temperature intervals.
28 (76) Optigo Ardo manual, Rev. A
Information for the specialist
3.7 Support control
Support control is normally used when room temperature control or extract air control has been configured.
When extract air control is configured a room sensor must be installed.
Support control can also be configured to start only with the supply air fan. In this mode, the extract air fan is not active. This requires a digital output to be configured, which controls the recirculation damper to open completely so the supply air fan can circulate the air to and from the room.
3.8 Fire
It is possible to configure the controller operating mode when there is a fire alarm. The following options are available: Stopped , Continuous run , Run via normal start/stop conditions , Only extract air fan , Only supply air fan .
It is possible to configure which speed the fan should have when in fire mode.
It’s also possible to configure if outdoor air damper and exhaust air damper should have Normal function or be Always open or Always closed . Normal function means that the damper open and close depending on if the corresponding fan is running or not.
3.9 Filter monitoring
Turn on filter monitoring to monitor the flow through the filter. Digital inputs can be used to connect a pressure switch to monitor the status of the filter and create an alarm if the signal of the pressure switch turns on.
3.10 Dampers
The outdoor air and exhaust air ducts close-off dampers can be controlled by a digital output or be hardwired to the supply air fan relays for normal, reduced and high speed in such a fashion that the damper is open when the supply air fan is running.
3.11 Changing the battery
The controller has an internal battery to ensure the operation of the memory and real-time clock in the event of a power failure. When the alarm Internal Battery is activated and the battery LED lights up red, the battery has become too weak and needs to be changed. Nonetheless, due to a backup capacitor, the controller will function at least 10 minutes without power supply.
proper ESD protection. Therefore, this should be handled by skilled service personnel.
An earthed wristband must be used during this procedure.
Optigo Ardo manual, Rev. A 29 (76)
Information for the specialist
1. Remove the cover by pressing down the locking torques at the edge of the cover using a small screwdriver, and at the same time pulling the cover outwards.
2. Grip the battery firmly with your fingers and lift it upwards until it rises from its holder.
3. Press the new battery firmly down into place.
type CR2032.
30 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
4 Information for the specialist - Configuration
4.1 Predefined configurations in Optigo
Ardo
To configure the controller, predefined configurations are used. The configuration is selected in the text display.
The predefined configurations are different combinations of components that are activated in the air handling system. The configuration number corresponds to the components that are active, see the schematic below in
.
Optigo Ardo manual, Rev. A 31 (76)
Information for the specialist - Configuration
Figure 4-1 Predefined configurations
Read more about predefined configurations in the document Optigo Ardo 1.0 Predefined configurations which is available on Regin's homepage www.regincontrols.com.
32 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
4.1.1
How to use the predefined configurations
Select a predefined configuration in the display.
1. Start from the start menu.
Optigo Ardo 1.0
2020-01-08 14:29
System: Normal run
Sp:22.0 Act: 22.5°C
2. Press the right button [ ► ] 7 times until you reach the menu to select the configuration.
Choose Config File
None
3. Select the configuration you want. Available configurations depend on the number of IOs in the hardware.
4. Select add-ons. Available add-ons depends on the used hardware and selected configuration.
a. For Optigo Ardo with 15 I/Os
CO2/FreeCool add-on
Ext.run/Fire add-on b. For Optigo Ardo with 28 I/Os
CO2 fan add-on
No
CO2 damper add-on
Yes/No
Extended run add-on
Yes/No
Fire alarm add-on
Yes/No
Free cooling add-on
Yes/No
5. Activate the configuration
Load configuration
Yes/No
4.2 Adjust settings in Optigo
Ardo
There is a possibility to adjust the predefined settings in the controller. The work flow for this is:
1. Select the predefined configuration in the text display
2. Go to the Configuration menu and adjust settings
3. Go to the Ventilaton menu and adjust setpoint settings for e.g. fan control and temperature control.
4. Go to the Time settings menu to adjust the settings of the timer channels and the holiday plan if needed
Optigo Ardo manual, Rev. A 33 (76)
Information for the specialist - Configuration
4.3 Configuration of Optigo
Ardo
4.3.1
System
Configuration
System
General
Unit settings
To configure the system there are two configurations that can be made:
✓ General settings
✓ Unit settings
General settings
Under General is information about the controller, and some general settings can be made.
General
Choose Language
Choose Start Screen
Automatic
Summer/Winter Time
Change-Over
Time Before User
Automatically is
Logged Off
Change language
The display language can be changed in the menu
Dsplay menu:
Choose language
English pressing the [[ ► ]] button four times when the start display is shown.
Start screen
There are several different start screens to choose from.
34 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Show headline, date/time, vent. mode, supply temp / setp.
Optigo Ardo 1.0
2019-08-01 11:28
System: Normal speed
Sp: 32.8°C Act:33.1°C
Second line: Date and time
Third line: Status of the unit
Fourth line: Supply temperature and setpoint
Show headline, vent. mode, supply temp / setp, sequence A to C
Optigo Ardo 1.0
System: Normal speed
Sp: 32.8°C Act:33.1°C
A 100 B 100 C 100
Second line: Status of the unit
Third line: Supply temperature and setpoint
Fourth line: Output signal of the sequences A to C
Show headline, date/time, vent. mode
Optigo Ardo 1.0
2019-08-01 11:28
System: Normal speed
Second line: Date and time
Third line: Status of the unit
Show headline, date/time
Optigo Ardo 1.0
2019-08-01 11:28
Second line: Date and time
Automatic switch between summer and winter time adjustment
The internal clock is normally configured for automatic summer / winter time adjustment. When enabled, the clock will be set forward one hour at 02:00 am on the last Sunday of March and adjusted back one hour at 03:00 am on the last Sunday of October.
The function can be disabled in: Configuration ► System ► General
Automatic logoff
If the access level is set to Operator or Admin , the user will automatically be logged off after a set time of inactivity. The time is settable in units of 5 seconds. The default is 60 units = 5 minutes
The automatic log off can be disabled in: Configuration ► System ► General ► Time before automatic logoff in display (unit 5s) (min)
Optigo Ardo manual, Rev. A 35 (76)
Information for the specialist - Configuration
Unit settings
Select if the temperature should be displayed in Celsius (°C) or Fahrenheit (°F)
4.3.2
Function configuration
Configuration
Function config.
Function activation
Heater
Exch. / Mix. Damper
Cooler
Add. heater
Temperature control
Sequence settings
Fan control
Fan compensation
Support control
Fire
CO2 control
Filter monitoring
Extended operation
Alarms
This is where you activate the functions that will be used in the BAS (Building Automation System). It is also where you set up sequences.
Function activation
This is where you select:
✓ Fan levels (Low-Normal-High)
✓ Support control (Yes/No)
✓ Free cooling (Yes/No)
✓ Auto restart (Yes/No)
36 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
The Auto restart function makes it possible to block automatic restart of the unit at power-up. At power-up, the B-alarm
Restart blocked after power on is generated. Once this alarm has been acknowledged, the unit will start.
Sequences
There are four sequences in the controller, and which sequence or sequences that will be used depends on which predefined configuration that has been chosen in the controller. Each sequence will have their own
PID-settings.
The available settings for the different sequences depends on which predefined configuration you have selected.
The sequence types are:
✓ Not used
✓ Heater
✓ Cooler
✓ Exchanger
✓ Mixed Damper
✓ Additional heater tions you make in other menus.
Setting for sequences
Configuration
Function config.
Heater
Exch. /mix. Damper
Cooler
Add. heater
The table below shows the possible settings for all sequences (Heater, Cooler, Exchanger/Mixed damper,
Additional heater).
Table 4-1 Sequence settings
Menu
Pump stop mode
Period time for PWM-signal (s)
Sequence output min limit (%)
Sequence output max limit (%)
Setting alternatives
✓ Always running
✓ Auto
Writable. Default 60 s
Writable
Writable
Note
Optigo Ardo manual, Rev. A 37 (76)
Information for the specialist - Configuration
Table 4-1 Sequence settings (continued)
Menu
Sequence output when the unit is stopped
(%)
Sequence output when fire mode (%)
Setting alternatives
Writable
Writable
Note
Starting order heating/cooling
The following picture shows the default settings of the configured sequences, where the Exchanger or Mixed damper starts first in heating mode followed by the Heater and the Additional heater. In cooling mode, the
Exchanger or Mixed damper starts first followed by the Cooler.
Figure 4-2 Sequence starting order
Temperature control
Table 4-2 Settings for temperature control
Menu
Activate summer mode
Setting alternatives
Cooling recovery mode
Fan speed temp. setpoint
Defrosting Exchanger
EAF speed when defrosting with stopped
SAF
✓ No summer setpoint
✓ Switch with calendar
✓ Switch with changeover
✓ Switch with digital input
✓ Switch with outdoor temp
On / Off
Low / High
Yes / No
Normal
Note
38 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Sequence settings
These settings are used the define the start of the sequences when the unit starts. There are two different modes to start the unit:
✓ Normal start up
✓ Warm (Heat) start up
Normal start up:
The sequence control starts at 100% for the heating sequence which is selected at the parameter At start up begin temperature control at 100% . The default setting is Heating 1 , which means it starts at 100% for heating sequence 1 which is the exchanger in the default configuration.
Warm start up:
If the outdoor temperature is lower than the settable limit Warm start up if outdoor temperature < (°C) the unit will start in the warm start mode. A second sequence will start at 100% in this mode if the unit starts. The default setting is Heating 2 , which means it starts at 100% for the heating sequence 2 which is the heater in the default configuration
Table 4-3 Sequence settings
Display
Begin temperature control at 100 %
Setting alternatives
✓ Heating X 0%
✓ Heating X
Writable Warm start up if outdoor temperature < (°
C)
If warm start begin temperature control at
100 % in
✓ Heating %
✓ Heating X
Note
Fan control
Settings for fan control.
Table 4-4 Settings for fan control
Menu
Switch point step 1-2
Hysteresis %
Setting alternatives
✓ SAF, Writable%
✓ EAF , Writable %
Writable
Fan compensation
Settings for fan compensation
Note
Optigo Ardo manual, Rev. A 39 (76)
Information for the specialist - Configuration
Table 4-5 Settings for fan compensation
Menu
Fan level
Mode
Fan
Setting alternatives
✓ All levels
✓ Low speed
✓ Normal speed
✓ High speed
✓ Low + Normal speed
✓ Normal + High speed
✓ Inactive
✓ In all modes
✓ When defrosting
✓ SAF+ EAF
✓ SAF
✓ EAF
Support control
Settings for support control
Table 4-6 Settings for support control
Menu
EAF running during support control
Setting alternatives
Yes / No
Fire
Settings for fire.
Table 4-7 Settings for fire
Display
Operation mode (when fire alarm)
SAF setpoint type
EAF setpoint type
Outdoor air damper function
Exhaust air damper function
Note
Note
Setting alternatives
✓ Stopped
✓ Continuous run
✓ Running via normal start/stop conditions
✓ Supply air fan run
✓ Extract air fan run
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Note
40 (76) Optigo Ardo manual, Rev. A
CO
2
control
Settings for CO2 control
Table 4-8 Settings for CO2 control
Display
Setpoint SAF
Setpoint EAF
Setting alternatives
✓ Low speed
✓ Normal speed
✓ High speed
✓ Low speed
✓ Normal speed
✓ High speed
Information for the specialist - Configuration
Note
Filter monitoring
Settings for filter monitoring.
Display
Filter alarm reset
Filter alarm time (month)
Setting alternatives
Yes/No
Writable
Note
Alarms
Set the Alarm delay time at start up. Default: 60 s.
4.3.3
Inputs/Outputs
Configuration
Inputs/Outputs
Analog Inputs
Digital Inputs
Analog Outputs
Digital Outputs
Analog inputs
All analog inputs are for Pt1000, Ni1000LG, Ni1000 or 0…10 V.
Input signals can be compensated e.g. for wiring resistance.
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
The settings that can be selected / configured are:
Optigo Ardo manual, Rev. A 41 (76)
Information for the specialist - Configuration
Table 4-9 Analog inputs
Variable
Terminal
Sensor type
Min input (V)
Max input (V)
Min signal (°C)
Max signal (°C)
Filter factor
Settings
✓ Off
✓ AI 1…4
✓ UAI 1…4
✓ Pt1000
✓ Ni1000LG
✓ Ni1000
✓ 0…10 V
Writable (Default 0)
Writable (Default 10)
Writable (Default 0)
Writable (Default 100)
Writable (Default 0,2)
Note
The number of terminals are depending on Optigo Ardo model
The filter factor is the damping you want the program to work with in order to reduce the influence of potential signal fluctuations on the sensor input.
A new value is calculated using the following formula:
New value = old value * filter factor + raw value * (1 - filter factor)
Compensation (°C) Writable (Default 0)
Digital inputs, DI
To simplify adaptation to external functions, all digital inputs can be configured to be either normally open,
NO, or normally closed, NC. The inputs are as default normally open, i. e. if the input is closed, the function connected to the input in Optigo Ardo is activated.
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
configured to either NO or NC themselves. For example, you can choose if the fire alarm input should be activated when it is closed or opened. Therefore, there is a risk that the signal is changed twice and the result is the opposite of the desired.
The settings that can be selected / configured are:
Table 4-10 Digital inputs
Variable
Terminal
Settings
NC / NO
✓ Off
✓ DI 1…8
✓ NO
✓ NC
Note
The number of terminals are depending on Optigo Ardo model
✓ NC (Normally closed )
✓ NO (Normally open)
Analog outputs, AO
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
42 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Table 4-11 Analog outputs
Variable
Terminal
Range output
Settings
✓ Off
✓ AO 1…5
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Note
The number of terminals are depending on Optigo Ardo model
Digital outputs, DO
Digital outputs can be NC (Normally Closed) or NO (Normally Opened).
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
Table 4-12 Digital outputs
Variable
Terminal
NC / NO
Settings
✓ Off
✓ DO 1…7
✓ NO
✓ NC
Note
The number of terminals are depending on Optigo Ardo model
✓ NC (Normally closed )
✓ NO (Normally open)
4.3.4
Other configuration
Configuration
Communication
TCP/IP
Save and restore
Communication
The controller uses TCP/IP.
In this menu it's possible to turn on and off DHCP and set a static IP-address.
Save and restore
Save and restore:
✓ Local settings
✓ Factory settings
Optigo Ardo manual, Rev. A 43 (76)
Information for the specialist - Configuration
4.4 Ventilation
Ventilation
Actual/Setpoint
Temperature control
Fan control
Demand control
PID controllers
Manual/Auto
Status
4.4.1
Actual / Setpoint
Actual/Setpoint
Temperature
Room air controller
Extract air contr.
Supply air contr.
CO2
Fans
Supply air fan
Extract air fan
Freeze protection
Exchanger
Read and adjust setpoints for:
✓ Temperature
✓ Room air controller
✓ Extract air controller
✓ Supply air controller
✓ CO
2
✓ Fans
44 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
✓ Supply air fan
✓ Extract air fan
✓ Freeze protection
✓ Exchanger
Temperature
Table 4-13 Setpoints for temperature control
Variable
Actual control type
Outdoor temperature (°C)
Supply air temperature (°C)
Room temperature (°C)
Extract air temperature (°C)
Setpoint adjustment (°C)
R
R
W
R
R
Read/Write Default value
R
0
Min/Max Note
-10/10
Room air controller
Table 4-14 Setpoints for room air control
Variable
Actual room air temperature (°C)
Setpoint room (°C)
Actual setpoint room (°C)
W
R
Setpoint adjustment low speed (°C) W
Read/Write Default value
R
21
0
Setpoint adjustment high speed (°
C)
W 0
Summer mode: Room setpoint (°C) W
Controller output (%) R
24
Min/Max Note
-20/150
-50/50
-50/50
-20/150
Extract air controller
Table 4-15 Setpoints for extract air control
Variable
Actual temperature (°C)
Setpoint (°C)
Actual setpoint (°C) R
Setpoint adjustment low speed (°C) W
Setpoint adjustment high speed (°
C)
W
Summer mode: Setpoint (°C)
Controller output (%)
Read/Write Default value
R
W 21
W
R
0
0
24
Min/Max Note
-20/150
-50/50
-50/50
-20/150
Optigo Ardo manual, Rev. A 45 (76)
Information for the specialist - Configuration
Supply air controller
Table 4-16 Setpoints for supply air control
Variable Read/Write Default value
Actual supply air temperature (°C) R
Setpoint adjustment (°C)
Actual setpoint supply air (°C)
W
R
0
Setpoint adjustment low speed (°C) W
Setpoint adjutment high speed (°C) W
W Summer mode: Setpoint supply air
(°C)
Summer mode: Outdoor temperature (°C)
Min limit supply air
W
W
0
0
24
24
12
Max limit supply air
Controller output (%)
W
R
30
Min/Max Note
-10/10
-50/50
-50/50
-20/150
-20/150
10/150
10/150
CO
2
Table 4-17 Setpoints for CO
2 control
Variable
Actual CO2 (ppm)
Setpoint (ppm)
Read/Write Default value
R
W 1000
Min/Max Note
0/2000
Fans
Table 4-18 Setpoints for fans
Variable
Setpoint low speed supply air fan
(%)
Setpoint normal speed supply air fan (%)
Setpoint high speed supply air fan
(%)
Setpoint low speed extract air fan
(%)
Setpoint normal speed extract air fan (%)
Setpoint high speed extract air fan
(%)
Read/Write Default value
W 25
W
W
W
W
W
50
75
25
50
75
Min/Max
0/100
0/100
0/100
0/100
0/100
0/100
Note
46 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Supply air fan
Table 4-19 Setpoints for supply air fan
Variable
Actual level
Output (%)
Actual setpoint compensation (%) R
Read/Write Default value
R
R
Min/Max Note
Extract air fan
Table 4-20 Setpoints for extract air fan
Variable
Actual level
Output signal (%)
Actual setpoint compensation (%) R
Read/Write Default value
R
R
Min/Max Note
Freeze protection
Table 4-21 Setpoints for freeze protection
Variable Read/Write Default value
Freeze protection temperature (°C) R
Min/Max Note
Exchanger
Table 4-22 Setpoints for exchanger
Variable
Deicing temperature (°C)
Read/Write Default value
R
Min/Max Note
4.4.2
Temperature control
Ventilation
Temperature control
Heater
Exch. /Mix. Damper
Cooler
Add. heater
Freeze protection
Exchanger
Optigo Ardo manual, Rev. A 47 (76)
Information for the specialist - Configuration
Summer mode
N Exch. / Mix. Damper refers to the sequence Exch. / Mix. Damper. The menu
Exchanger refers to a physical exchanger.
Sequences A to D
Read more about sequences in
.
The sequences available in the controller are Heater, Exchanger/Mixed damper, Cooler or Additional heater.
The sequence/sequences used depends on the predefined configuration chosen for the controller.
Table 4-23 Settings for sequence A to D
Variable
Pump stop delay (min)
Pump-kick hour (h)
Pump running when outdoor temperature < (°C)
Hysteresis to allow pump stop (°C) W
Read/Write Default value
W 5
W
W
15
10
1
Min/Max
0/600
0/23
-40/100
0/100
Note
Freeze protection
Read more about freeze protection in
.
Table 4-24 Settings for freeze protection
Variable
Setpoint (°C)
P-band (°C)
Setpoint standby mode (°C)
Read/Write Default value
W 7
W
W
5
25
Min/Max
-40/150
0/100
-40/150
Note
Exchanger
Read more about exchangers in
.
Table 4-25 Settings for exchanger
Variable
Start delay exchanger (s)
Start delay exchanger 100 % (s)
Start alarm delay exchanger (s)
Defrosting setpoint (°C)
Defrosting min time (min)
Defrosting hysteresis (°C)
W
W
W
W
Defrosting stop SAF if temp outdoor
< (°C)
W
Read/Write Default value
W 0
W 2
60
5
0,2
-100
Min/Max
0/3600
0/3600
0/3600
Note
0/60
0/10
-100/150
48 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Summer mode
Table 4-26 Settings for Summer mode
Variable
Date for start of summer period
Month for start of summer period
Date for end of summer period
Month for end of summer period
Outdoor temp for switch between summer / winter (°C)
Outdoor temp hysteresis for switch between summer / winter (°C)
Read/Write Default value
W 1
W
W
4
1
W
W
10
13
W 0,5
Min/Max
1/31
1/12
1/31
1/12
0/99
0/99
Note
4.4.3
Fan control
Ventilation
Fan control
Fans
Supply air fan
Extract air fan
Fan comp. curve
Fans
Table 4-27 Settings for fans
Variable
Offset supply air fan when free cooling (%)
Offset extract air fan when free cooling (%)
Read/Write Default value
W 0
W 0
Min/Max
-100/100
-100/100
Note
Supply air fan
Table 4-28 Settings for supply air fan
Variable
Start delay (s)
Stop delay (s)
Outdoor air damper stop delay (s) W
SAF speed min limit (%) W
SAF speed max limit (%) W
Read/Write Default value
W 60
W 180
0
0
100
Min/Max
0/3600
0/3600
0/3600
0/100
0/100
Note
Optigo Ardo manual, Rev. A 49 (76)
Information for the specialist - Configuration
Extract air fan
Table 4-29 Settings for extract air fan
Variable
Start delay (s)
Stop delay (s) W
Outdoor air damper stop delay (s) W
Read/Write Default value
W 0
30
0
EAF speed min limit (%)
EAF speed max limit (%)
W
W
0
100
Min/Max
0/3600
0/3600
0/3600
0/100
0/100
Note
Fan compensation curve
Table 4-30 Settings for fan compensation curve
Variable
Lower point X
Read/Write Default value
W 15
Lower point Y (%)
Middle point X
Middle point Y (%)
Higher point X
W
W
W
W
0
20
0
25
Higher point Y (%) W 0
Min/Max
-30000/
30000
-100/100
-30000/
30000
-100/100
-30000/
30000
-100/100
Note
4.4.4
Demand control
Ventilation
Demand control
CO2
Free cooling
Support control
CO2
Table 4-31 Settings for CO2
Variable
Start limit fan start/stop (ppm)
Read/Write Default value
W
Stop hysteresis fan start/stop (ppm) W
800
160
Demand control
Min time for CO2 control (min)
R
W 20
Min/Max
0/2000
0/2000
Note
0/600
50 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Free cooling
Read more about free cooling in
Table 4-32 Settings for free cooling
Variable
Free cooling mode
Running if day outdoor temperature
> (°C)
W
Stop if night outdoor temperature >
(°C)
W
Read/Write Default value
R
22
18
Stop if night outdoor temperature <
(°C)
Stop if room temperature < (°C)
W
W
10
18
Free cooling start hour (h)
Free cooling stop hour (h)
Time to block heat output after free cooling (min)
Fan-kick temperature check (s)
W
W
W
W
Fan-kick interval time (min) W
Start when extract - outdoor > (°C) W
0
7
60
180
60
2
Min/Max Note
10/40
10/40
10/40
10/40
0/23
1/24
0/600
0/3600
0/600
1/5
Support control
Read more about support control in
Table 4-33 Settings for support control
Variable
Support control mode
Min time for support control (min) W
Start heating room temperature (°C) W
Read/Write Default value
R
20
15
Stop heating room temperature (°C) W 21
Setpoint heating (°C) W
Start cooling room temperature (°C) W
Stop cooling room temperature (°C) W
Setpoint cooling (°C) W
30
30
28
12
Min/Max
0/600
10/40
10/40
-20/150
10/40
10/40
-20/150
Note
4.4.5
PID controllers
Ventilation
PID controllers
Room air controller
Extract air contr.
Optigo Ardo manual, Rev. A 51 (76)
Information for the specialist - Configuration
CO2
Heater
Exch. /Mix. Damper
Cooler
Add. heater
Freeze protection
Defrosting
Room air controller
Table 4-34 Settings for PID-control - Room air control
Variable
P-band
I-time (s)
Read/Write
W
W
Default value
100
300
Min/Max
0/1000
0/9999
Extract air controller
Table 4-35 Settings for PID-control - Extract air control
Variable
P-band
I-time (s)
Read/Write
W
W
Default value
33
100
Min/Max
0/1000
0/9999
CO2
Table 4-36 Settings for PID-control - CO2
Variable
P-band
I-time (s)
D-time (s)
Read/Write
W
W
W
Default value
100
100
0
Min/Max
0/1000
0/9999
0/9999
Sequence A to D
Table 4-37 Settings for PID-control - Sequence A to D
Variable
P-band
I-time (s)
D-time (s)
Read/Write
W
W
W
Default value
10
100
0
Min/Max
0/1000
0/9999
0/9999
Note
Note
Note
Note
52 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Freeze protection
Table 4-38 Settings for PID-control - Freeze protection
Variable
P-band
I-time (s)
D-time (s)
Read/Write
W
W
W
Default value
100
100
0
Min/Max
0/1000
0/9999
0/9999
Note
Defrosting
Table 4-39 Settings for PID-control - Defrosting
Variable
P-band
I-time (s)
D-time (s)
Read/Write
W
W
W
Default value
16
240
0
Min/Max
0/1000
0/9999
0/9999
4.4.6
Manual / Auto
Ventilation
Manual/Auto
Ventilation unit
Fan controls
Heater
Exch. /Mix. Damper
Cooler
Add. heater
Change Over
Supply air fan
Extract air fan
Outdoor Air Damper
Exhaust Air Damper
Sum Alarm
Extra TC
Free cooling indic.
Note
Optigo Ardo manual, Rev. A 53 (76)
Information for the specialist - Configuration
Running indication
Ventilation unit
Table 4-40 Settings for ventilation unit
Variable
Mode
Alternatives
✓ Off
✓ Auto
✓ Low speed
✓ Normal speed
✓ High speed
Fan controls
Table 4-41 Settings for fan controls
Variable
Supply air fan (SAF) mode
Manual setpoint (%)
Manual output (%)
Extract air fan (EAF)
Manual setpoint (%)
Manual output (%)
Alternatives
✓ Off
✓ Manual output
✓ Auto
✓ Manual setpoint
✓ Low speed
✓ Normal speed
✓ High speed
Writable
Writable
✓ Off
✓ Manual output
✓ Auto
✓ Manual setpoint
✓ Low speed
✓ Normal speed
✓ High speed
Writable
Writable
Read/Write
W
Note
Note
Sequence A to D (Heater, Exchanger/Mixed Damper, Cooler, Additional heater)
Table 4-42 Settings for sequence A to D
Alternatives Variable
Sequence output
Mode
Manual (%)
Actual value (%)
Analog output
Mode
✓ Manual
✓ Auto
Writable
Read only
Manual (%)
Output (%)
Pump
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Note
54 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Table 4-42 Settings for sequence A to D (continued)
Variable
Mode
Start
Alternatives
✓ Manual
✓ Auto
✓ On
✓ Off
Start
Mode
Start
✓ Off
✓ On
✓ Auto
Read only
Supply and Extract air fan
Table 4-44 Settings for supply and extract air fan
Variable
Signal fan
Mode
Alternatives
Manual set (%)
Output
Start fan
Mode
✓ Off
✓ On
✓ Auto
Writable
Read only
Start
✓ Off
✓ Manual
✓ Auto
Read only
Note
Change-over
Table 4-43 Settings for change-over, Supply air fan, Extract air fan
Variable
Mode
Manual set (%)
Controller output (%)
Start
Mode
Alternatives
✓ Off
✓ Manual
Writable
Read only
Start
✓ Off
✓ Manual
✓ Auto
Read only
Note
Note
Dampers
✓ Outdoor air damper
✓ Exhaust air damper
Optigo Ardo manual, Rev. A 55 (76)
Information for the specialist - Configuration
Table 4-45 Settings for dampers
Variable
Mode
Start
Alternatives
✓ Off
✓ On
✓ Auto
Read only
Sum Alarm
Table 4-46 Settings for alarms
Variable
Mode
Start
Alternatives
✓ Off
✓ On
✓ Auto
Read only
Extra time channel
Table 4-47 Settings for extra time channel
Variable
Mode
Start
Alternatives
✓ Off
✓ On
✓ Auto
Read only
Free cooling indication
Table 4-48 Settings for free cooling indication
Variable
Mode
Start
Alternatives
✓ Off
✓ On
✓ Auto
Read only
Running indication
Table 4-49 Settings for running indication
Variable
Mode
Start
Alternatives
✓ Off
✓ On
✓ Auto
Read only
4.4.7
Status
Ventilation
Status
Note
Note
Note
Note
Note
56 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Ventilation Unit
Heater
Exch. /Mix. Damper
Cooler
Add. heater
Timer channel
Status for the ventilation unit, sequences A to D and timer channels.
Ventilation unit
Sequence A to D
Timer channels
✓ Operation mode
✓ Schedule
✓ Manual mode
✓ External stop
✓ Extended operation Mode
✓ Time left
✓ Free cooling mode
✓ Support control mode
✓ Night operation active last night
✓ Summer mode
✓ Fire alarm input
✓ Output (%)
✓ Pump
✓ Start
Timer channel: On/Off
4.5 Alarm events
In the Alarm Events menu, there is an alarm log which contains the 100 latest alarm events. The latest event is shown at the top of the list. The alarm log is only used to view alarm history, which may simplify troubleshooting of the installation.
4.6 Time settings
Time settings
Time schedule
Fan low speed
Fan normal speed
Fan high speed
Extra time channel
Holiday schedule
Holiday calendar
Optigo Ardo manual, Rev. A 57 (76)
Information for the specialist - Configuration
Time/Date
Optigo Ardo has a year-based clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over.
It has individual schedules for each weekday plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules take precedence over other schedules.
This menu displays time, date and weekday, and it permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD.
Each day has up to four individual running periods. For fans there are daily individual schedules for low speed, normal speed and high speed, each with up to four running periods.
One digital output can be used as a timer controlled output with individual week-schedules and four activation periods per day. This output can be used to control lighting, door locks etc.
In the time schedules, four periods are available for each day of the week. Also, four periods are available for days that are configured as holidays in the holiday schedule. During the periods the assigned circuit is working with the corresponding setpoint. Outside of a period the system is off.
On On
Off
B2
Figure 4-3 Time schedule
E2
Off
B1 E1
Off
Begin/End
The above figure shows an example of period states. It is not possible for periods to overlap each other.
Holiday schedules take precedence over other schedules.
✓ For 24 hour running, set a period to 00:00 - 24:00.
✓ To inactivate a period, set the time to 00:00 - 00:00. If all periods of a day are set to 00:00 - 00:00, the unit will not run that day.
✓ If you want to run the unit from one day to another, e.g. from Monday 22:00 to Tuesday 09:00, the desired running time for both must be entered.
speed, and normal speed takes precedence over low speed.
58 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
4.6.1
Extra time channel
One digital output can be used as a timer controlled output with individual week-schedule and four activation periods per day.
4.6.2
Holiday calendar
The system operator can define specific periods of operation or non-operation throughout the year. During these defined periods, the settings in the week schedule do not apply. The holiday calendar includes 24 periods. All holiday periods are working with a special day plan with a maximum of 4 periods.
A holiday period can be any number of consecutive days from 1…365. The dates are in the format: MM:DD.
4.7 Inputs/Outputs
Inputs/Outputs
Raw values
Analog inputs
Digital inputs
Analog outputs
Digital outputs
Analog inputs
Digital inputs
Analog outputs
Digital outputs
In this section, the values for all used Inputs and outputs are displayed.
There are also the raw values for the inputs and outputs ( Inputs/Outputs ► Raw values )
4.8 Alarms status
Alarms status
Alarm configuration
Alarm limits
Alarms are indicated by the red alarm LED on the front of the unit .
All alarms can be monitored, acknowledged and blocked using the display and buttons.
The Alarm configuration menu permits configuration of the priority for all alarms.
Optigo Ardo manual, Rev. A 59 (76)
Information for the specialist - Configuration
4.8.1
Alarm configuration
The alarm configuration menu permits configuration of the priority for all alarms. A complete alarm list with default settings and actions, can be found in
. It contains all the default alarm texts and priorities.
Priority
Alarms can be given different priority levels A-alarm , B-alarm and C-alarm or Not active . The A- and Balarms are connected to the digital output sum alarm . The digital output can be inverted, so that an inoperative alarm gives a high output and vice versa. A- and B- alarms must be acknowledged to reset. Calarms automatically reset as soon as there is no longer a cause for alarm.
Stop function
Each alarm offers the possibility to choose whether an activated alarm should stop the controller or not
( Extra stop function ). The controller can also be set to run at reduced speed during alarms. Automatic restart will take place when the alarm has been acknowledged.
For some alarm types such as Electric heating overheated and Warning freeze protection it would be dangerous to not stop the unit on alarm. Therefore, for such alarm types, the program will always reset the stop function to Active even if the operator should choose Inactive .
Unfortunately it is not possible to remove the display text concerning the stop function for these alarm types. This is because the available program space demands that all alarms are treated in the same way in the display.
ttiivvee, or unexpected malfunctions may occur.
4.8.2
Sum alarm
There is one sum alarm function with one digital output.
✓ A and B alarms all activate the sum alarm output, if it has been configured.
✓ Class C alarms are removed from the alarm list when the alarm input resets even if the alarm has not been acknowledged.
Table 4-50 Sum alarm
Inputs and outputs
DO Sum alarm
4.8.3
Alarm limits
[Alarm status ► Alarm limits]
The only alarm limit that can be set is the Deviation alarm for supply air temperature .
4.9 Access rights
Access rights
60 (76) Optigo Ardo manual, Rev. A
Information for the specialist - Configuration
Log on
Log off
Change password
The controller has four different access levels. The choice of access level determines which menus are shown, as well as which parameters can be changed in the displayed menus.
✓ Guest level does not require logging on, and only permits changes in running mode and gives read-only access to a limited number of menus.
✓ Operator level gives the same access as Guest level, and in addition, access to change setpoints.
✓ Service level gives the same access as Operator level, and in addition, access to change controller settings and manual mode.
✓ Admin level gives full read/write access to all settings and parameters in all menus.
4.9.1
Log on
1. Browse to Access Rights in the main menu and press [ ► ] .
Log on
Log off
Change password
2. Select Log on and press [ ► ] .
Log on
Enter password:****
Actual level:
None
3. Press [OK] to make a cursor marker appear at the first digit position.
4. Enter the password (4-digit code) by pressing [ ▲ ] until the correct digit is displayed. Press the [ ► ] to move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to confirm.
4.9.2
Change password
1. Go to Access Rights in the main menu and press [ ► ] .
2. Select Change password and press [ ► ] .
Change password for level:Operator
New password: ****
3. Select Yes and press [OK]
4. Press [OK] to enter change mode.
5. Use the [ ▲ ] and [ ▼ ] buttons to browse and select the access level to change the password for, and press
[OK] to confirm.
Optigo Ardo manual, Rev. A 61 (76)
Information for the specialist - Configuration
6. Enter the new password (4-digit code) by pressing [ ▲ ] until the correct digit is displayed. Press the [ ► ] to move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to confirm.
The following passwords are the default for the different access levels:
Access level
Admin
Service
Operator
Password
1111
2222
3333
You can only change the password for access levels lower or equal to the presently active level, i.e. if you are logged in as Admin you can change all passwords, but as Operator you can only change the
Operator password.
would prevent access to the higher of these two access levels. This is especially important for word can be obtained from Regin. This code is date dependent and valid for one day only.
62 (76) Optigo Ardo manual, Rev. A
5 Information for the installer
5.1 Installation
5.1.1
Optigo
Ardo
The controller can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet or, using a suitable front-mounting kit, in a cabinet door or other control panel.
Figure 5-1 Optigo Ardo voltage.
instructions given in this manual.
Wiring examples
For a complete list of terminals, see
Optigo Ardo manual, Rev. A 63 (76)
24V AC/DC
+
_
DO1 - 7
+C
Contact
Modular conn.
4P4C
Ext.disp.
230VAC G (24VAC)
G0 (OV)
N L
SM230A-SR
Y
(-) (+)
RVAx-24A
Y
AI1 - 4
DI1 - 8
UI1 - 4
AO1 - 5
TCP/IP
RJ45
+
0V +24V
24VDC
Power supply
N L
Temp sensors
Pt1000
Contact
_
+
CTRTA
0-10 V
+C
CO2 transmitter
0...10 V
G0 (OV)
G (24VAC) 230VAC
Figure 5-2 Wiring
230VAC
Inputs and outputs
There is a list of input and outputs in
Appendix C Input and output lists
that can be used to help you keep track of which inputs and outputs you need to configure.
Analog inputs
Analog inputs must refer to an Agnd terminal.
Analog inputs can, depending on the configuration, be used for either PT1000 / Ni1000 temperature sensors or for 0…10 V DC analog input signals, for example from a pressure transmitter.
Digital inputs
Digital inputs must refer to +C on terminal 4. Digital inputs may only be wired to voltage-free contacts. Any external voltage applied to a digital input may harm the unit.
Universal inputs
A universal input can be configured to act as either an analog input or as a digital input.
A universal input configured as an analog input can, depending on the configuration, be used for either
PT1000 / Ni1000 temperature sensors or for 0…10 V DC analog input signals, for example from a pressure transmitter.
64 (76) Optigo Ardo manual, Rev. A
Universal inputs configured as an analog input must refer to an Agnd terminal.
A universal input configured as a digital input must, just like other digital inputs refer to C+ on terminal 4. It may only be wired to voltage-free contacts.
Analog outputs
Analog outputs must refer to a Agnd terminal.
All analog outputs can be individually set to any one of the following output signals:
✓ 0…10 V DC
✓ 2…10 V DC
✓ 10…0 V DC
✓ 10…2 V DC the same transformer pole is used as reference for all the equipment. The equipment may otherwise not function as intended and may also suffer damages.
Digital outputs
Digital outputs should normally refer to G
DO on terminal 10.
G
DO is internally connected to G on terminal 1 and supplies 24 V AC or DC depending on the choice of supply voltage.
All the digital outputs are controlled by MOSFET transistors. The outputs are internally connected with G
0 and can deliver max 2 A per output. However, the total power for all the DOs must not exceed 8 A.
A number of different wiring alternatives are possible depending on the type of supply voltage to the controller and the relay type.
Figure 5-3 24 V AC supply and 24 V AC relays
Optigo Ardo manual, Rev. A 65 (76)
Figure 5-4 24 V DC supply and 24 V DC relays
Figure 5-5 24 V AC supply and 24 V DC relays
Figure 5-6 24 V DC supply and 24 V AC relays
66 (76) Optigo Ardo manual, Rev. A
5.2 Commissioning
To commission the controller, start by selecting a configuration suitable for your application.
Some of the parameters in the configuration can be changed, for example temperature setpoints. Change the setpoints if needed.
5.3 Resetting the controller
Reset the controller by pressing the reset button, using for example a paper clip.
Figure 5-7 Resetting the controller
Optigo Ardo manual, Rev. A 67 (76)
Appendix A technical data
A.1 Optigo
Ardo
A.1.1
General data
Supply voltage
Power consumption
24 V AC (21…27 V AC) 50…60 Hz / 20…36 V DC
See
in
Ambient temperature
Ambient humidity
Storage temperature
Protection class
Connection
Memory backup
Display
Mounting
Casing
Dimensions (WxHxD)
Battery type
Battery life
Operating system
0…50 °C
Max. 95 % RH
-20…70 °C
IP20
Disconnectable terminal strips, 4 mm 2
Built-in long life battery gives long backup time of all settings incl. real time
Backlit LCD, 4 rows of 20 characters
DIN-rail or cabinet
Standard Euronorm (8.5 modules wide)
149 x 121 x 60 mm incl. terminals
CR2032 replaceable Lithium cell
Min. 5 years
EXOrealC
A.1.2
Ethernet port data
Port type
Default protocol
Supported protocols
Ethernet
EXOline-TCP
EXOline-TCP
A.1.3
Inputs & outputs
Analog inputs (AI)
Digital inputs (DI)
Universal inputs (UI)
Analog outputs (AO)
Digital outputs (DO)
For PT1000 or Ni1000 sensors (accuracy ± 0.4 °C) or 0…10 V DC (accuracy ± 0.15 % of full output signal). 12 bit resolution in the A/D conversion.
For potential-free contacts
Can be set to act as either analog input or digital input with specifications as above
0…10 V DC, 1 mA, short-circuit protected
Mosfet outputs, 24 V AC or DC, 2 A continuous. Max. 8 A in total.
68 (76) Optigo Ardo manual, Rev. A
Appendix B Model overview
Name
OPA151D-4
OPA281D-4
Supply voltage Description
24 V
24 V
Ardo controller with 15 IOs
Ardo controller with 28 IOs
Table B-1 Optigo Ardo Models
Name AI
OPA151D-4
OPA281D-4
4
4
DI
4
8
UI*
0
4
AO
3
5
DO
4
7
0
0
RS485 ports
1
1
Ethernet ports
Display Power consumption
(VA)
Yes
Yes
9 VA
9 VA
* Universal inputs can be configured to function as either analog or digital inputs.
Optigo Ardo manual, Rev. A 69 (76)
Appendix C Input and output lists
The lists below are intended to be used as a memory aid during configuration, in order to help keep track of the desired input and output functions.
The left column contains a description of the in-/output signal and the right column shows the text displayed in the controller.
C.1 Analog inputs
Description
Outdoor temperature sensor
Supply air temperature sensor
Extract air temperature sensor
Room temperature sensor
De-icing temperature heat exchanger
Frost protection temperature sensor
CO2/VOC sensor
External supply setpoint (PT1000)
Name in display
Outdoor temperature
Supply air temperature
Extract air temperature
Room temperature
Defrosting temperature
Freeze protection temperature
CO2 room/extract air
External setpoint temperature
C.2 Digital inputs
Description
Supply air fan motor protection/run indication
Extract air fan motor protection/run indication
Extended operation low speed
Extended operation normal speed
Extended operation high speed
Fire alarm
Electric heating is overheated
External stop
Flow switch change-over signal, switches between heating=0 and cooling=1 on the output signal
Filter guard 1 supply air
Filter guard 2 extract air
Summer mode
Name in display
Feedback supply air fan
Feedback extract air fan
Extended operation low speed
Extended operation normal speed
Extended operation high speed
Fire alarm
Overheated electric heater
External stop
Flow guard
Cooling/(heating) Change-over
Filter guard supply air
Filter guard extract air
Summer/(Winter) mode
C.3 Universal inputs
Universal inputs on the controller can be individually configured as either analog inputs, using any of the analog inputs in
, or as digital inputs, using any of the digital inputs in
70 (76) Optigo Ardo manual, Rev. A
C.4 Analog outputs
Description
Sequence A output in (%)
Sequence B output in (%)
Sequence C output in (%)
Sequence D output in (%) change-over (%)
Control signal Supply air fan in (%)
Control signal Extract air fan in (%)
C.5 Digital outputs
Description
Sequence A Pump Start
Sequence B Pump Start
Sequence C Pump Start
Sequence D Pump Start
Sequence A PWM
Sequence B PWM
Sequence C PWM
Sequence D PWM
Start supply air fan / Start step 1 supply air fan
Start step 2 supply air fan
Start extract air fan/ Start step 1 extract air fan
Start step 2 extract air fan
Outdoor air close-off damper
Exhaust air close-off damper
Sum alarm
Time Channel 1
Free Cool Run
Run indication
Start change-over
Name in display
Sequence A
Sequence B
Sequence C
Sequence D
Change-over
Supply air fan
Extract air fan
Name in display
Sequence A pump
Sequence B pump
Sequence C pump
Sequence D pump
Sequence A PWM
Sequence B PWM
Sequence C PWM
Sequence D PWM
Supply air fan start / step 1
Supply air fan step 2
Extract air fan start/step 1
Extract air fan step 2
Outdoor air damper
Exhaust air damper
Sum alarm
Extra time channel 1
Free cooling indication
Running indication
Changeover start
Optigo Ardo manual, Rev. A 71 (76)
Appendix D Alarm list
The alarm text, priority and delay columns show the factory set values.
D.1
Alarm text
Malfunction supply air fan
Malfunction extract air fan
Filter alarm supply air
B
Filter alarm extract air
Fire alarm
Electric heating is overheated
Warning freeze protection
B
Defrosting alarm
Internal battery error
-
Restart blocked after power on
Deviation alarm supply air temp.
B
Freeze protection alarm A
A
B
A
A
B
B
Prio
B
Manual operation air handling unit
Manual operation supply air
C
C
Manual operation supply air fan
C
Manual operation extract air fan
C
Manual operation heater C
Manual operation exchanger
C
Manual operation cooler C
Manual operation damper
C
Manual operation pump heater
Manual operation pump cooler
Manual operation damper outdoor air
C
C
C
C Manual operation damper exhaust air
Manual control sequence A
-
Manual control sequence B
Manual control sequence C
-
0s
0s
0s
0s
2s
0s
0s
30min
Delay
120s
120s
180s
180s
0s
0s
0s
0s
0s
0s
0s
0s
0s
0s
0s
0s
0s
0s
0s
Limit
10 °C
Description
Malfunction supply air fan
Malfunction extract air fan
Filter alarm supply air pressure switch
Filter alarm extract air pressure switch
Fire alarm activated
Heater high temperature limit switch activated
Frost protection function is overriding the control of the heater output
Exchanger deicing activated by deicing sensor
Internal battery needs replacing
Restart blocked due to earlier power failure
Supply air temp deviates too much from the setpoint
Frost protection temperature below frost limit value
The unit is in manual mode
Supply air temp controller in manual control
Supply air fan in manual control
Extract air fan in manual control
The heater is in manual mode
Heat exchanger output in manual control
Cooling output in manual control
Damper output in manual control
Heating circulation pump in manual control
Cooling circulation pump in manual control
Fresh air damper in manual control
Exhaust air damper in manual control
Manual control of sequence A
Manual control of sequence B
Manual control of sequence C
72 (76) Optigo Ardo manual, Rev. A
Alarm text
Manual control sequence D
Output in manual operation
C
Sensor error outdoor air temperature
B
Sensor error supply air temperature
B
B Sensor error extract air temperature
Sensor error room temperature
Sensor error defrosting temperature
Sensor error freeze protect. temp.
B
B
B
Sensor error CO2 room/ extract air
B
Sensor error external temp. setpoint
B
Internal error C
Prio
-
5s
5s
5s
60s
5s
5s
5s
Delay
0s
0s
5s
5s
Limit Description
Manual control of sequence D
Analog or digital output in manual mode
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Internal error
Optigo Ardo manual, Rev. A 73 (76)
Appendix E Terminal lists
E.1 Optigo
Ardo
Terminal
14
15
16
17
30
10
11
12
13
3
4
1
2
31
32
33
34
35
40
I/O
Power supply G+
Power supply G0-
Earth
DI common +C
DO common GDO
DO1
DO2
DO3
DO4
DO5
DO6
DO7
Analog ground
AI1
AI2
Analog ground
AI3
AI4
Analog ground
74 (76)
Hardware model
A15 A28
-
-
-
-
-
Notes
Optigo Ardo manual, Rev. A
72
73
74
75
44
45
71
76
77
78
90
41
42
43
91
92
93
94
95
UAI1
UAI2
Analog ground
AO1
AO2
AO3
AO4
AO5
UAI3
UAI4
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Analog ground
-
-
-
-
-
-
-
-
-
-
-
Optigo Ardo manual, Rev. A 75 (76)
last page