Regin VCV203DWM-2 Controller Manual
Regin VCV203DWM-2 is a versatile room controller for heating and ventilation applications that enables you to create a comfortable indoor climate. The controller is equipped with two analog inputs for sensors or other signals, two digital inputs for external control and two relay outputs for controlling fans or dampers. The control functions are easily set up via the LCD display and the user-friendly menu structure. With its compact size and DIN rail mounting, the controller is easy to install in electrical cabinets or other confined spaces.
Advertisement
Advertisement
WE TAKE BUILDING
AUTOMATION PERSONALLY
en
MANUAL
CORRIGO
THANK YOU FOR CHOOSING REGIN!
Ever since Regin was established in 1947, we have developed and marketed products and systems that create good levels of indoor comfort. Today, we are an important player with one of the market's broadest ranges for building automation.
Our goal is to make real estates in the world more energy efficient. Regin is an international group and our products sells in over 90 countries. Thanks to our global presence with strong local representation, we are well aware of the requirements of the market, as well as of how our products and systems function under the most variable conditions.
Every year, Regin makes substantial investments in the development of our systems and HVAC-products.
DISCLAIMER
The information in this manual has been carefully checked and is believed to be correct. Regin makes no warranties about the contents of this manual and users are requested to report errors and discrepancies to Regin, so that corrections may be made in future editions. The information in this document is subject to change without prior notification.
Some product names mentioned in this document are used for identification purposes only and may be the registered trademarks of their respective companies.
© AB Regin. All rights reserved.
Rev. D, 2021-12-14
Table of Contents
Table of Contents
Settings and configuration in Application tool for pump control ...............................82
Table of Contents
Table of Contents
1 About this manual
This manual covers all the models in the Corrigo series used with the ventilation application. This revision covers software revisions from 5.0.
The manual has the following main chapters:
✓ Information for the end user
All the information needed by the end user. How to handle the controller, including how to navigate in the menus, LED:s and indications, how to change setpoints and handle alarms etc.
✓ Information for the specialist
A comprehensive guide to all the functions of the controller.
✓ Information for the installer
Everything related to the installation of the hardware, such as wiring examples and commissioning.
✓ Appendix
Technical data, model overview, input and output lists, alarm list, terminal lists.
Special text formats used in the manual:
This box is used to show formulas and mathematical calculations
This box is used to represent the display window on the controller
1.1 More information
More information about the product can be found in:
✓ Product sheets for Corrigo Ardo and Corrigo Vido
✓ Instructions for Corrigo Ardo and Corrigo Vido
✓ Variable lists
All the above documents are available for download from Regin’s website, http://www.regincontrols.com
.
Corrigo manual, Rev. D 7 (196)
2 Introduction to Corrigo
The Corrigo series of controllers are used for ventilation control. They can be used as a stand-alone controller or integrated in a SCADA system.
There are two versions of the Corrigo with different hardware platforms: The 24 VCorrigo Ardo and the 230
V Corrigo Vido (see more in:
chapter 3.1 Display, LED:s and buttons
)
Corrigo has between 15, 20 and 28 I/O:s depending on hardware and model.
2.1 Display
The Corrigo Ardo is available with or without display. The Corrigo Vido is only available with display.
An external display can be connected to the controller to make it possible to monitor and work with the controller from another location.
The display or the external display is used to e.g. change values, set timers and monitor alarms.
2.2 Application tool and Configuration of Corrigo
Application tool is a PC-based, free configuration software tool, available at Regin's website www.
regincontrols.com
. The tool is used to configure and commission the controller .
The controller doesn't need to be connected to the computer while configuring. All settings are made in the tool and then uploaded to the controller.
An infinite number of configurations can be stored in the computer memory for later use.
A communication cable is required in order to upload the configuration to the controller. The controller must also be powered up and the application selected in order for it to be configured.
Predefined configurations can be downloaded as atf-files from Regin’s website, www.regincontrols.com
.
These atf-files can be opened in the tool and synchronized to the controller.
More information about configuration is available in:
chapter 5.3 Configuration - System
2.3 Internal web interface
When the Corrigo is connected to an external display or computer with a browser and a connection to the internet, an internal web interface will be shown. The web interface can be used to change setpoints, configure and monitor the controller.
8 (196) Corrigo manual, Rev. D
Figure 2-1 Start screen for the web interface
2.4 Comparison between the user interfaces
There are different user interfaces that can be connected to the Corrigo.
The text-displays and the touch screen ED-T43L-V are designed as an end-user interface to show current values, adjust setpoints and timer settings and to adjust settings like limits of control functions and the PIDsettings.
The complete configuration can only be done via Application tool or the web-interface.
Table 2-1 User interfaces for Corrigo
Text display
Internal/External
Actual values /Setpoint ✓
Time channels
Selected settings
Complete settings
Manual control AHU
Manual control components
Configuration of ports ✓
Complete configuration
ED-T43L-V
(external touch display)
Web interface Application tool
Corrigo manual, Rev. D 9 (196)
3 Information for the end user
3.1 Display, LED:s and buttons
The controllers are available in two different hardware platforms:
✓ The 230 V Corrigo Vido which features 5 buttons.
Figure 3-1 Corrigo Vido
✓ The 24 V Corrigo Ardo which features 7 buttons.
10 (196)
Figure 3-2
Corrigo manual, Rev. D
3.1.1
Display
The display has 4 rows of 20 characters each. It has background illumination. The illumination is normally off, but is activated as soon as a button is pressed. The illumination will be turned off again after a period of inactivity.
3.1.2
LED:s
On the Corrigo Ardo models, there are two LEDs on the front, marked with the symbols (alarm) and
(change). For controllers with display, the alarm indication and change mode LEDs are located in the keypad area.
Symbol Colour
Flashing red
Fixed red
Flashing yellow
Fixed yellow
Function
There are one or more unacknowledged alarms.
There are one or more remaining acknowledged alarms.
You are in a dialog box where it is possible to switch to change mode.
A quick blinking (2 times/s) indicates that the parameter can be changed using the current access level.
A slower blinking (1 time/s) indicates that a higher access level is required to change the parameter.
You are in change mode.
Status indication
Status indication LEDs can be found in the upper left corner of the Corrigo Ardo models.
Designation
P1 RxTx
P2 RxTx
TCP/IP (…W models)
P/B (Power / Battery)
Colour
Yellow/Green
Yellow/Green
Yellow/Green
Green/Red
Description
Port 1, receiving/transmitting
Port 2, receiving/transmitting
Green: Connected to other network equipment
Blinking green: Network traffic
Blinking yellow: For identifying (for example when marking the unit in Application tool)
Power on / Battery error
Corrigo manual, Rev. D 11 (196)
3.1.3
Summary of the function of the buttons
Corrigo Ardo (7 buttons)
[▲][▼][►][◄]
[OK]
[C]
[ALARM]
Corrigo Vido (5 buttons)
[▲][▼][►][◄]
[OK]
[C]
Press both buttons simultaneously
[ALARM]
Functions Function in Alarm Mode
Navigation buttons:
▲ Navigate upwards.
▼ Navigate downwards.
► Navigate to the right.
◄ Navigate to the left.
In change mode:
◄ Move cursor to the left.
► Move cursor to the right.
▲ Increase the value by 1.
▼ Decrease the value by 1.
▲and ▼ Scroll among the texts when there are several alternatives.
▲ Navigate up in the alarm stack.
▼ Navigate down in the alarm stack.
◄ Exit alarm display mode.
✓ Enter change mode.
✓ Confirm a new value in change mode. An input must be confirmed with this button in order to change the value in the controller.
When a value has been confirmed, the cursor will move to the next editable value in the current box.
✓ A menu with all actions that are available for the current alarm is displayed.
✓ Enter change mode and erase the value in the display.
✓ Erase the sign at the cursor.
✓ When the current value is completely empty, the edit mode is cancelled and the cursor will move to the next value that will also be erased in the window.
✓ Undo (erase) the input
✓ Closes the menu containing available alarm actions without changing the state of the alarm point.
✓ Enter alarm display mode.
✓ Browse among alarms in alarm display mode.
Press both buttons simultaneously
3.2 Navigating the menus
The appearance of the start display may vary since there are several different start displays to choose from during configuration.
Vent controller 5.0
2017-01-08 14:29
System: Normal run
Sp: 22.0 Act: 22.5°C
Sp and Act stand for Setpoint and Actual value.
Actual value = the current measured temperature
12 (196) Corrigo manual, Rev. D
Setpoint = the desired configured temperature
You can navigate through the menu choices at this level by pressing the [ ▼ ] and [ ▲ ] buttons.
Which menu items that are shown depends on the access level of the user and the configured inputs/outputs and functions.
Below, all possible menu entries are shown.
✓ Ventilation
✓ Additional function
✓ Time settings
✓ Alarm events
✓ Configuration
✓ Access rights
To enter a higher menu level, press the [ ► ] button when the display marker is located at the menu item you wish to enter. At each level there may be several new menus through which you may browse using the [ ▲ ] and [ ▼ ] buttons.
When there are further submenus linked to a menu or menu item, it is indicated by an arrow symbol at the right-hand edge of the display. To choose one, press the [ ► ] button again. To return to a lower menu level, press the [ ◄ ] button.
3.3 Changing values
When you are at a position where it is possible to change one or more values, and your access level is high enough, you can edit the existing value, or enter a new one. After changing the value, you confirm the input with the [OK] button, or undo the change by pressing the [C] / [ ▼► ] buttons for a short while until the original value reappears in the window and change mode is exited. These actions are described in detail in the following sections.
3.3.1
Editing an existing value
1. Press the [OK] button to go to change mode. A flashing cursor appears. If there are multiple editable values in one menu, press the [OK] button until the value you want to change flashes.
2. Move the cursor to the right and to the left with the navigation buttons [ ► ] and [ ◄ ] .
3. The value at the cursor can now be changed in the following ways:
✓ Erase the current digit or character with the [C] / [ ▼► ] buttons.
✓ Use the [ ▲ ] and [ ▼ ] buttons to increase or decrease the value at the cursor. Editable texts can also be changed with this method.
✓ If the character at the cursor is a decimal point, you cannot browse with the [ ▲ ] and [ ▼ ] buttons.
You can however erase the decimal point with the [C] / [ ▼► ] buttons.
✓ If the cursor is placed to the right of the value, i.e. the character at the cursor is a space, you can add a decimal point with the [ ▼ ] button, or the figure 0 with the [ ▲ ] button.
✓ If you require a negative number, move the cursor to the leftmost position and press the [ ▼ ] button to get a minus sign. Then edit the following digits to the required value.
✓ Scroll up [ ▲ ] and down [ ▼ ] to browse through texts when there are several texts to choose from instead of numerical values.
Corrigo manual, Rev. D 13 (196)
3.3.2
Enter a completely new value
✓ Press the [C] / [ ▼► ] buttons to go to change mode. The value is erased in the window, and you have to enter a completely new value.
✓ If you require a negative number, move the cursor to the leftmost position and press the [ ▼ ] button to get a minus sign. Then edit the following digits to the required value.
✓ Press [ ▲ ] to begin the input with the digit 0, then browse to the required digit or character with [ ▲ ] and [ ▼ ] .
✓ Press [ ▼ ] to get a decimal point. When the cursor is placed at a decimal point, you cannot browse with the [ ▲ ] and [ ▼ ] buttons.
3.3.3
Confirm the change
Press [OK] to confirm the change when the required value has been entered. Then the value you see in the window will be updated in the installation.
After the value has been confirmed, the cursor will move to the next editable value in the current menu.
installation.
3.3.4
Undo an initiated change
pressing the [[C ▼ ]] buttons for a short while until the original value reappears in the window and change mode is exited.
3.4 Logging on and off
The controller has four different access levels. The choice of access level determines which menus are shown, as well as which parameters can be changed in the displayed menus.
✓ Guest level does not require logging on, and only permits changes in running mode and gives read-only access to a limited number of menus.
✓ Operator level gives the same access as Guestl level, and in addition, access to change setpoints.
✓ Service level gives the same access as Operator level, and in addition, access to change controller settings and manual mode.
✓ Admin level gives full read/write access to all settings and parameters in all menus.
3.4.1
Log on
1. Browse to Access Rights in the main menu and press [ ► ] .
Log on
Log off
Change password
14 (196) Corrigo manual, Rev. D
2. Select Log on and press [ ► ] .
Log on
Enter password:****
Actual level:
None
3. Press [OK] to make a cursor marker appear at the first digit position.
4. Enter the password (4-digit code) by pressing [ ▲ ] until the correct digit is displayed. Press the [ ► ] to move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to confirm.
3.4.2
Log off
1. Go to Access Rights in the main menu and press [ ► ] .
2. Select Log off and press [ ► ] .
Log off?
No
Actual level:
Admin
3. Select Yes and press [OK] .
3.4.3
Change password
1. Go to Access Rights in the main menu and press [ ► ] .
2. Select Change password and press [ ► ] .
Change password for level:Operator
New password: ****
3. Select Yes and press [OK]
4. Press [OK] to enter change mode.
5. Use the [ ▲ ] and [ ▼ ] buttons to browse and select the access level to change the password for, and press
[OK] to confirm.
Corrigo manual, Rev. D 15 (196)
6. Enter the new password (4-digit code) by pressing [ ▲ ] until the correct digit is displayed. Press the [ ► ] to move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to confirm.
The following passwords are the default for the different access levels:
Access level
Admin
Service
Operator
Guest
Password
1111
2222
3333
5555
You can only change the password for access levels lower or equal to the presently active level, i.e. if you are logged in as Admin you can change all passwords, but as Operator you can only change the
Operator and Guest passwords. There is no point in changing the Guest password since access to that level is granted automatically to all users.
would prevent access to the higher of these two access levels. This is especially important for word can be obtained from Regin. This code is date dependent and valid for one day only.
3.4.4
Automatic logoff
When logged in as Operator , Service or Admin , the user will automatically be logged off to Guest after a settable time of inactivity (the default is 60 seconds). It is possible to disable the automatic logoff in
Application tool.
Change password to remove automatic logoff
If you want to remove the automatic logoff, change the password of the desired level to 0000. This can be very useful in certain cases if the unit is intended to be used by trained personnel or, for instance, during commissioning.
ously given that a certain level has been activated.
3.5 Menu structure and features
The display is not designed to do a complete configuration of the system. It provides access on to Operator level and partly access to Service settings.
The configuration of the system needs to be done by using Application tool or the web interface.
Start menu:
Ventilation
Additional function
Time settings
Alarm events
Inputs/Outputs
Configuration
Access rights
16 (196) Corrigo manual, Rev. D
3.5.1
Ventilation
Ventilation has up to six submenus:
Actual/Setpoint
Temperature control
Fan control
PID controller
Manual/Auto
Status
Actual/Setpoint
In this submenu, you can read all the actual values of the configured inputs of the circuit. For more information, see
chapter 5 Information for the specialist - Configuration
.
Temperature control
In this submenu, you can read and set all the setpoints for the selected circuit. You need Operator or higher access level to be able to change setpoints.
Fan control
In this submenu, settings of the fan can be read and set. It is only visible for access level Operator and higher, and only editable for access level Service and higher. For more information, see
chapter 5 Information for the specialist - Configuration
PID control
In this submenu, the control parameters can be read and set. It is only visible for access level Operator and higher, and only editable for access level Service and higher. For more information, see
chapter 5 Information for the specialist - Configuration
Manual/Auto
In this submenu, the ventilation unit can be set to manual mode. It is only visible for access level Operator and higher, and only editable for access level Service and higher.
For more information, see
chapter 5 Information for the specialist - Configuration .
Status
In this submenu, the status of the ventilation unit can be read.
Each function also has different sub-statuses. For more information, see
chapter 5 Information for the specialist
.
3.5.2
Additional function (extra controller)
In this submenu, you can read the actual value and read/write the setpoint of a configured extra controller.
For more information, see
chapter 5 Information for the specialist - Configuration .
Corrigo manual, Rev. D 17 (196)
3.5.3
Time settings
Corrigo has a year-based clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over.
It has individual schedules for each weekday plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules take precedence over other schedules.
Each day has up to four individual running periods. There are daily individual schedules for low speed, normal speed and high speed of the fan, each with up to four running periods.
Up to 4 digital outputs can be used as timer controlled outputs. Each with individual week-schedules with four activation periods per day. These outputs can be used to control lighting, door locks etc.
The Time settings menu contains the submenus Time schedule , Holiday schedule and Time/Date .
Time schedule
Holiday schedule
Time/Date
Time settings
Fan low speed
Fan normal speed
Fan high speed
Extra time channel1
Extra time channel2
Extra time channel3
Extra time channel4
In the time schedules, four periods are available for each day of the week. Also, four periods are available for days that are configured as holidays in the holiday schedule. During the periods the assigned circuit is working with the corresponding setpoint. Outside of a period the system is off.
On On
Off
B2
Figure 3-3 Time schedule
E2
Off
B1 E1
Off
Begin/End
The above figure shows an example of period states. It is not possible for periods to overlap each other.
18 (196) Corrigo manual, Rev. D
Timer Low speed, Normal speed, High speed
There are sixteen separate settings menus for each timer channel, two for each weekday and two extra for holidays. Holiday schedules take precedence over other schedules.
For 24 hour running, set a period to 00:00 - 24:00.
To inactivate a period, set the time to 00:00 - 00:00. If both periods of a day are set to 00:00 - 00:00, the unit will not run at 1/1-speed that day.
Normal speed
Monday Per3-4 >
Per 1: 00:00 - 24:00
Per 2: 00:00 - 00:00
Normal speed
Monday
Per 3: 00:00 - 00:00
Per 4: 00:00 - 00:00
If you want to run the unit from one day to another, e.g. from Monday 22:00 to Tuesday 09:00, the desired running time for both must be entered.
Normal speed
Monday
Per 1: 22:00 - 24:00
Per 2: 00:00 - 00:00
Normal speed
Tuesday
Per 1: 00:00 - 09:00
Per 2: 00:00 - 00:00
Should periods for the different speeds overlap, high speed takes precedence over normal speed, and normal speed takes precedence over low speed.
Extra time channels
Up to four digital outputs can be used as timer controlled outputs. Each with individual week-schedules with two activation periods per day. Each output has sixteen separate setting menus; two for each weekday and two extra for holidays. Holiday schedules take precedence over other schedules.
Only the time channels which have been configured, i.e. have been wired to a digital output, will be shown.
Extra time channel2
Wednesday Per3-4 >
Per 1: 00:00 - 00:00
Per 2: 00:00 - 00:00
Extra time channel2
Wednesday
Per 3: 00:00 - 00:00
Per 4: 00:00 - 00:00
Extra time channel 4 can be used to control start/stop of the functions:
✓ Extra fan motor control
✓ Recirculation
Corrigo manual, Rev. D 19 (196)
Parameters (Fan normal speed)
Name
Monday Per.1 Start
Monday Per.1 End
Monday Per.2 Start
Monday Per.2 End
Monday Per.3 Start
Monday Per.3 End
Monday Per.4 Start
Monday Per.4 End
...
Holiday Per.1 Start
Holiday Per.1 End
Holiday Per.2 Start
Holiday Per.2 End
Holiday Per.3 Start
Holiday Per.3 End
Holiday Per.4 Start
Holiday Per.4 End
Unit Min hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00
Max
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
Default Description
00:00 Start of period 1 Mondays.
24:00
00:00
00:00
End of period1 Mondays.
Start of period 2 Mondays.
End of period 2 Mondays.
00:00
00:00
00:00
00:00
Start of period 3 Mondays.
End of period 3 Mondays.
Start of period 4 Mondays.
End of period 4 Mondays.
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Start of period 1 holidays.
End of period 1 holidays.
Start of period 2 holidays.
End of period 2 holidays.
Start of period 3 holidays.
End of period 3 holidays.
Start of period 4 holidays.
End of period 4 holidays.
Parameters (Fan low and high speed, Extra time channels)
Name
Monday Per.1 Start
Monday Per.1 End
Monday Per.2 Start
Monday Per.2 End
Monday Per.3 Start
Monday Per.3 End
Monday Per.4 Start
Monday Per.4 End
...
Holiday Per.1 Start
Holiday Per.1 End
Holiday Per.2 Start
Holiday Per.2 End
Holiday Per.3 Start
Holiday Per.3 End
Holiday Per.4 Start
Holiday Per.4 End
Unit Min hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00 hh:mm 00:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
Max
24:00
24:00
24:00
24:00
24:00
24:00
24:00
24:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Default Description
00:00 Start of period 1 Mondays.
00:00
00:00
00:00
End of period 1 Mondays.
Start of period 2 Mondays.
End of period 2 Mondays.
00:00
00:00
00:00
00:00
Start of period 3 Mondays.
End of period 3 Mondays.
Start of period 4 Mondays.
End of period 4 Mondays.
Start of period 1 holidays.
End of period 1 holidays.
Start of period 2 holidays.
End of period 2 holidays.
Start of period 3 holidays.
End of period 3 holidays.
Start of period 4 holidays.
End of period 4 holidays.
Holiday schedule
The system operator can define specific periods of operation or non-operation throughout the year. During these defined periods, the settings in the week schedule do not apply. The holiday schedule provides 24 periods. All holiday periods are working with a special day plan with a maximum of 4 periods.
20 (196) Corrigo manual, Rev. D
A holiday period can be any number of consecutive days from 1…365. The dates are in the format: MM:DD.
When the present date falls within a holiday period, the scheduler will use the settings for the weekday
Holiday .
Parameters
Name
Holiday Per.1 Start
Holiday Per.1 End
...
Holiday Per.24 Start
Holiday Per.24 End
Unit Min
MM:DD 01.01
MM:DD 01.01
Max
31.12
31.12
Default Description
00.00
The start date of holiday period 1.
00.00
The end date of holiday period 1.
MM:DD 01.01
MM:DD 01.01
31.12
31.12
00.00
00.00
The start date of holiday period 24.
The end date of holiday period 24.
Time/Date
This menu displays time, date and weekday, and it permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD.
3.5.4
Inputs/Outputs
In the sub menu Inputs/Outputs you can find and modify raw values and analog and digital inputs and outputs. For more information see
chapter 5.6 Configuration - Inputs and Outputs
and
Raw values
Analog inputs
Digital inputs
Analog outputs
Digital outputs
3.5.5
Mode switch
In addition to the items in the main menu, there is also an extra menu called Mode switch , that is reached by pressing [ ► ] in the main menu. The mode switch changes the operation of the system.
Mode switch position
0 — Off
1 — Auto
2 — Low speed
3 — Normal speed
4 — High speed
Manual mode Off. System is switched off. No control function.
Automatic mode. Control function depending on timer and settings.
Manual mode. System is forced to low speed of the fans.
Manual mode. System is forced to normal speed of the fans.
Manual mode. System is forced to high speed of the fans.
3.6 Alarm events and alarm handling
If an alarm condition occurs, an alarm is logged in an alarm list. The list shows the type of alarm, the alarm date and time and the alarm priority (A, B or C alarm).
Corrigo manual, Rev. D 21 (196)
3.6.1
Alarm priorities
Alarms can be given different priority levels: A alarm , B alarm , C alarm or not active . There are three digital outputs that can be used as alarm outputs: Sum alarm , Sum alarm A and Sum Alarm B/C .
✓ A, B and C alarms all activate the sum alarm output, if it has been configured.
✓ Class A alarms also activate sum alarm A, and class B/C alarms activate sum alarm B/C.
✓ Class C alarms are removed from the alarm list when the alarm input resets even if the alarm has not been acknowledged.
3.6.2
Inspect alarms
✓ Press the alarm buttons [ALARM] / [ ◄▲ ] to display the alarms.
✓ If there is more than one alarm at the same time, this is indicated by up/down arrow symbols at the right-hand edge of the display. You can browse among them in two ways:
1. By using the navigation buttons [ ▼ ] and [ ▲ ] .
2. By pressing the alarm buttons [ALARM] / [ ◄▲ ] several times.
✓ Press [ ◄ ] to exit alarm handling and return to the previous menu.
3.6.3
Acknowledge, block and unblock alarms
✓ Press the [OK] button to get a menu with the available alarm actions for the currently displayed alarm.
✓ Select the required alarm action with the buttons [ ▼ ] and [ ▲ ] .
✓ Press the [OK] button to execute the action.
At the left end of the bottom display line the alarm status is shown. For active, unacknowledged alarms the space is blank. Alarms that have been reset are indicated by the text Acknowledged . Active or blocked alarms are indicated by the text Acknowledged or Blocked .
Acknowledged alarms will remain on the alarm list until the alarm input signal resets.
Blocked alarms remain on the alarm list until the alarm has been reset and the block has been removed. New alarms of the same type will not be activated as long as the block remains.
to block alarms.
Alarm events
In the Alarm Events menu, there is an alarm log which contains the 40 latest alarm events. The latest event is shown at the top of the list. The alarm log is only used to view alarm history, which may simplify troubleshooting of the installation.
3.7 Internal web interface
When you connect the controller to a computer or an external display with a browser, you reach the controller´s web interface. In the web interface you can monitor the installation and change setpoints etc.
22 (196) Corrigo manual, Rev. D
3.7.1
Overview picture
Figure 3-4 Start screen, web interface
In the overview picture you can monitor the actual values in the system:
✓ Outdoor temperature
✓ Supply air temperature
✓ Extract air temperature
✓ Main setpoint
✓ Fan speed
✓ Heating/cooling recovery
✓ CO
2 level
✓ Humidity
✓ Fan signals
The up and down arrows can be used to adjust the current setpoint for e.g. room temperature or extract air depending on the configured type of temperature control.
In the example above ( 3-4 Start screen, web interface ) the values are:
✓ Outdoor temperature = 13,6 °C
✓ Supply air temperature = 17,8 °C
✓ Extract air temperature = 20,7 °C
✓ Main setpoint = 18°C
✓ Fan speed = Normal speed
✓ Heating/cooling recovery = 100 %
✓ CO
2 level = 485 ppm
✓ Humidity = 59 %
✓ Supply air fan speed 50 % (bottom left)
Corrigo manual, Rev. D 23 (196)
✓ Extract air fan speed 50 % (bottom right)
3.7.2
Log in
Figure 3-5 Log in to the web interface
1. Press the login symbol in the upper right corner to open the login window.
2. Select the user level and use the correct pin code, see table below:
User level
Admin
Service
Operator
Normal
Pin code
1111
2222
3333
5555
3.7.3
Homescreen
The homescreen can be customized to show either a Simple view of the temperature, alarm and time settings
(see
below) or a Technical view with a graphical picture of the system (see
below).
To customize the home screen: go to Menu ► Account settings ► Homescreen settings .
24 (196) Corrigo manual, Rev. D
Simple view
Figure 3-6 Home screen, Simple View
Table 3-1 Symbol explanations, Simple view
Symbol Description
✓ Green: No alarm
✓ Red: Active alarm
✓ Yellow: Returned or acknowledged alarm
✓ Green: Running in Automatic mode
✓ Blue: Forced to a Manual mode (Extended run, Boost or Stop run)
✓ Yellow hand: Any output is in Manual mode
Technical view
In the technical view it is possible to name sensors etc. by pressing the [Edit ] button, see
below.
Corrigo manual, Rev. D 25 (196)
Figure 3-7 Customize technical view
Figure 3-8 Home screen, Technical view
26 (196) Corrigo manual, Rev. D
3.7.4
Change timer settings
Figure 3-9 Time schedule overview
1. Log in with Operator or higher user level
2. Press the [Schedule] button in the top menu bar and the schedule overview will open.
Figure 3-10 Period time settings
3.7.5
Setpoints
It is possible to read and change setpoints in the web interface as well.
1. Log in as Operator or higher.
Corrigo manual, Rev. D 27 (196)
2. Press the [Menu] button in the top menu bar
3. Select Ventilation ► Actual/Setpoint
4. Select Temperature or Fan to change setpoints
Figure 3-11 Setpoints in web interface
3.7.6
Signal analyzer (trend)
With the signal analyzer it's easy to follow up and look at the history of the analog and digital signals ( Menu
► Signal analyzer (trend) ► Trend configuration ).
In the Trend configuration, you select which signals you want to follow up, see
below. Up to 8 analog signal and 8 digital signals can be logged. Configured inputs and outputs can be selected as well as the output signals of the PID-controllers.
Different modes of operation are available at Trend configuration ► Settings .
The signal analyzer can run in three different ways:
1. Continuous run
2. Signal triggered
3. Time triggered
Type
Continuous run
Signal triggered
Time triggered
Description
Continuous logging
Triggered by a configured digital signal it is possible to select which change on the selected signal will trigger the logging:
✓ falling edge
✓ rising edge
✓ any edge ( Trigger signal edge )
The logging will stop after a defined time ( Stop after time ).
Triggered by time and date
The logging will stop after a defined time ( Stop after time ).
28 (196) Corrigo manual, Rev. D
The parameter Type of calculation is used to calculate the stored values of the analog signals of the last day and last week:
✓ Single sample: The current value of the signal is stored.
✓ Average: The average of the signal since the last storage is logged.
Figure 3-12 Configuration of signal analyzer
The signal analyzer curve shows how the signal varies over time.
For the analog signal it's possible to change the limits on the left and right axis. In the example below (
), the left axis is temperature in °C and the right axis is pressure in Pa.
The signal analyzer stores the historical information in different resolution:
✓ Last hour – 10 second interval
✓ Last day – 15 minutes interval
✓ Last week – 1 hour interval
It's possible to switch between the different resolutions in the chart by pressing the green buttons in the middle below the chart (10 s, 15 m or 1 h). In the examples below, 10 s are selected.
The green arrows on the left side and right side are used to scroll through the timeline.
The information in the diagram will be updated once a minute or can be manually done by pressing the
[refresh] button.
The [trash] button is used to delete all historical data and start from the beginning.
Corrigo manual, Rev. D 29 (196)
Figure 3-13 Signal analyzer, analog signal
Figure 3-14 Signal analyzer, digital signal
30 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
4 Information for the specialist - Function descriptions
4.1 Function overview
A number of different control functions as well as analogue and digital in- and output functions can be found in this controller. Certain functions are necessary, while others can be considered optional. The choice of which functions are to be used is free. The only restriction is the physical number of inputs and outputs of the different models. Information about configuration for the different functions is found in
5 Information for the specialist - Configuration
.
The program for an air handling unit contains, apart from other things, the following functions:
Different temperature control modes
✓ Supply air temperature control, with or without outdoor temperature compensation
✓ Room temperature control (cascade control)
✓ Extract air control (cascade control)
✓ Seasonal switching between supply air temperature control and room/extract air temperature control
✓ Outdoor compensated room/extract air control
✓ Extract air depending supply air temperature
With control of:
✓ Heat exchangers (liquid connected, plate or rotating)
✓ Mixing dampers
✓ Heating coil (water with or without frost protection, electric with high temperature limit switch, DX or combi coil)
✓ Cooling (water, DX with or without exchanger control)
✓ Circulation pumps
Fan control
✓ 1-, 2- or 3-speed supply air and extract air fans
✓ Frequency controlled supply and extract air fans with pressure or flow control, manual control or external control from a VAV system
✓ Pressure controlled supply air fan with slave connected extract air fan (output dependent or flow dependent) or opposite function (pressure controlled extract air fan with slave connected supply air fan, output dependent or flow dependent)
Humidity control
It is possible to use either humidification or dehumidification, or to use combined humidification and dehumidification.
Timer control
For starting and stopping the unit, annual clock function. Up to 4 timer outputs for control of external functions such as lighting, door locks etc.
Demand controlled ventilation
In buildings with strongly varying occupancy, the fan speeds or mixing dampers can be controlled by the air quality measured by a CO
2 sensor.
Support control
When using the control function room control or extract air temperature control, it is possible to utilise support-heating and/or support-cooling.
Corrigo manual, Rev. D 31 (196)
Information for the specialist - Function descriptions
Free cooling
When this function has been activated, it is used during the summer to cool the building during the night using cool outdoor air, thereby reducing the need to run chillers during the day.
Free heating
If the outdoor temperature is higher than the indoor temperature and there is a heating demand, the recovery damper will not open for recovery but instead open fully for outdoor air. This may occur during low night-time outdoor temperatures, when the room has been cooled considerably and the outside heat is rising faster than indoors. This function is activated at the same time as Free cooling .
Enthalpy control
Measures and compares the energy content (enthalpy) of the outdoor air and the extract air (temperature and air humidity). When this function is active, the mixing damper signal will be overridden to recirculation if the enthalpy is higher outdoors than indoors.
Pretreatment
Damper and pump control for preheating or precooling of the outdoor air via an underground intake channel.
Cooling recovery
If the extract air is colder than the outdoor air and cooling is required, the heat exchanger control is reversed in order to return the cool extract air.
Recirculation control
Recirculation of air using a supply air fan and (optionally) extract air fan and a recirculation damper with or without temperature control. Used as a recovery function or during heating with support control during the night. Recirculation control is available as an analogue or a digital function.
Step controllers heating/cooling
There are 2 equal step controllers. Both controllers will have 4 steps and can be configured as sequential control or binary control.
Change-over
In 2-pipe systems where a combination heater/cooler is operating together with a heat pump, change-over is a function that enables using the same pipe for both heating and cooling, depending on which is currently required.
32 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
4.2 Temperature control
4.2.1
General
Corrigo has a choice of the following control modes:
1. Supply air
2. Supply air outdoor compensated
3. Room cascade
4. Extract air cascade
5. Room (summer) else outdoor compensated supply air
6. Extract air (summer) else outdoor compensated supply air
7. Room outdoor compensated
8. Extract air outdoor compensated
9. Extract air dependent supply air
The supply air temperature controller is reverse acting, i e. the output will increase for decreasing temperature. The controller is a PID-controller with settable P-band, I-time and D-time.
Figure 4-1 Application tool menu path to temperature control
In the first mode, the temperature at the supply air sensor will be constantly kept at the user setpoint value.
In the second mode, the supply air temperature setpoint is adjusted depending on the outdoor temperature.
In modes three and four the supply air is controlled as part of a cascade controller together with the room/ extract temperature controller. The room/extract temperature offset will dictate the supply air temperature setpoint.
Mode five and six vary according to the outdoor temperature: Outdoor temperature compensated supply air control, as in mode two, in winter and cascaded room control or cascaded extract air control in summer, as in modes three or four. The switch-over temperature is settable.
A neutral zone can be set around the setpoint value.
Example: If the setpoint is 18 °C and the neutral zone is 2 K, the cooling setpoint will be 19 °C and the heating setpoint will be 17 °C (FS=0 K). If the supply air temperature is in the neutral zone, the heating and cooling will be blocked. If the supply air temperature decreases below the setpoint –NZ/2 the heating signal will be active until setpoint is fulfilled. If the supply air temperature increases above the setpoint +NZ/2 the cooling signal will be active until setpoint is fulfilled.
Corrigo manual, Rev. D 33 (196)
Information for the specialist - Function descriptions
Alarms which are activated when the supply air temperature is too high or too low are active.
Alarm for control offset of the supply air temperature is active.
4.2.2
Control modes
Read more about configuration of the control modes in chapter 5.6,
Supply air control
The supply air temperature is kept at the setpoint value by controlling the output signals for sequences A to
J. A single PI control loop is used.
The actual setpoint for the supply air temperature will be limited to a settable minimum and maximum.
Settings and configuration for Supply air control
Table 4-1 Path to configuration and settings for Supply air control
Feature
Supply air control
Sequence configuration
Starting order heating/cooling
Add supply air temperature sensor
Configure input
Sensor type selection
Controller output
Neutral zone setting
Min / Max limit supply air
Setpoint supply air
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence A to J
Temperature control type
Configuration ► Functions ►
Sequence heating and
Sequence cooling
Configuration ► Functions ►
Temperature control
Configuration ► Analog inputs
► Supply air temperature
Configuration ► Analog inputs
► Supply air temperature
Ventilation ► Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Supply air controller
Supply air temperature sensor
(Yes/ No) (
Sensor type
Controller output (%)
Neutral zone (C°)
Min / Max limit supply air (C°)
Setpoint supply air
Note
Selection of temperature control
Required inputs for Supply air control
Inputs and outputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs Supply air temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
34 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Supply air outdoor compensated
The supply air temperature setpoint is temperature compensated using a control curve with 8 node points, see
Figure 4-2 Temperature compensation curve
below.
Figure 4-2 Temperature compensation curve
The default settings for the 8 node points are shown in
below:
Table 4-2 Default settings for compensation curve
Outdoor temperature (°C)
5
10
15
- 20
-15
-10
-5
0
Setpoint supply temperature
25
24
23
23
22
20
18
18
The supply air temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
A single PI control loop is used.
Alarms which are activated when the supply air temperature is too high or too low are active.
Alarm for control offset of the supply air temperature is active.
Settings and configuration for Supply air outdoor compensated control
Table 4-3 Path to configuration and settings for Supply air outdoor compensated
Feature
Supply air outdoor compensated control
Sequence configuration
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence A to J
Temperature control type
Note
Selection of temperature control
Corrigo manual, Rev. D 35 (196)
Information for the specialist - Function descriptions
Table 4-3 Path to configuration and settings for Supply air outdoor compensated (continued)
Feature
Starting order heating/cooling
Add supply air temperature sensor
Configure input
Sensor type selection
Controller output
Setpoint outdoor curve (X, Y)
Neutral zone setting
Min / Max limit supply air
Menu path in Application tool Variable
Configuration ► Functions ►
Starting order heating and
Starting order cooling
Supply air temperature sensor
(Yes/ No)
Configuration ► Functions ►
Temperature control
Configuration ► Analog inputs
► Supply air temperature
Configuration ► Analog inputs
► Supply air temperature
Ventilation ►Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Supply air controller
Sensor type
Controller output (%)
Neutral zone (C°)
Min / Max limit supply air (C°)
Note
Required inputs for Supply air outdoor compensated
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs ✓ Supply air temperature
✓ Outdoor temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Room cascade
Cascade control of room temperature and supply air temperature to achieve a constant, settable room temperature. The room controller output signal (0-100%) generates the supply air controller’s setpoint value between min and max supply setpoint.
Up to 16 room sensors can be connected. A final value will be calculated from the values of the configured room sensors. Different types of calculation are available, such as:
✓ select the lowest value
✓ select the highest value
✓ calculated the average
✓ calculate the average with the lowest and the highest value
✓ calculate the middle value (median)
The room temperature is kept at the setpoint value by controlling the output signals for A to J. Two PI loops are used.
36 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Settings and configuration for Room cascade control
Table 4-4 Path to configuration and settings for Room cascade
Feature
Room cascade control
Sequence configuration
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence A to J
Temperature control type
Starting order heating/cooling Configuration ► Functions ►
Starting order heating and
Starting order cooling
Add room temperature sensor Configuration ► Functions ►
Temperature control
Select the type of average calculation
Setting of P-band and I-time
Configuration ► Functions ►
Temperature control
Setpoint room temperature
Setpoint adjustment
Room temperature sensor
Room temperature average
Ventilation ► PID controllers ►
Room
Ventilation ► Actual / Setpoint
► Room controller
Ventilation ► Actual / Setpoint
► Room controller
Setpoint room temperature
Setpoint adjustment
Note
Selection of temperature control
0…16
Type of average calculation
Required inputs for Room cascade
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs ✓ Room temperature 1…16
✓ Supply air temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Extract air cascade
Cascade control of extract air temperature and supply air temperature to achieve a constant, settable room temperature. The extract air controller output signal (0-100%) generates the supply air controller’s setpoint value between min and max supply setpoint.
The extract air temperature is kept at the setpoint value by controlling the output signals for A to J. Two PI loops are used.
Settings and configuration for Extract air cascade control
Table 4-5 Path to configuration and settings for Extract air cascade
Feature
Extract air cascade control
Sequence configuration
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence A to J
Temperature control type
Starting order heating/cooling Configuration ► Functions ►
Starting order heating and
Starting order cooling
Add extract air temperature sensor
Configuration ► Functions ►
Temperature control
Extract air temperature sensor
Note
Selection of temperature control
Yes / No
Corrigo manual, Rev. D 37 (196)
Information for the specialist - Function descriptions
Table 4-5 Path to configuration and settings for Extract air cascade (continued)
Feature
Configure Input
Menu path in Application tool Variable
Configuration ► Analog inputs
► Extract air temperature
Setting of P-band and I-time Ventilation ► PID controllers ►
Extract air
Setpoint extract air temperature Ventilation ► Actual / Setpoint
► Extract air controller
Setpoint adjustment Ventilation ► Actual / Setpoint
► Extract air controller
Setpoint extract air
Setpoint adjustment
Required inputs for Extract air cascade
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs ✓ Extract air temperature
✓ Supply air temperature
Note
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Room (summer) else supply air outdoor compensated
Summer mode dependent switching between outdoor compensated supply air temperature control and room cascade control.
When the summer mode function is off, outdoor temperature compensated supply air temperature control will be active. In summer mode it will be cascaded room temperature control that is active. The summer mode function is used for switching control mode.
Settings and configuration for Room (summer) else supply air
Table 4-6 Path to configuration and settings for Room (summer) else supply air
Feature
Room (summer) else supply air control
Sequence configuration
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence A to J
Temperature control type
Starting order heating/cooling Configuration ► Functions ►
Starting order heating and
Starting order cooling
Summer mode settings
Add supply air temperature/ room temperature sensor
Configuration ► Functions ►
Temperature control
Configuration ► Functions ►
Temperature control
Activate summer mode
Supply air temperature sensor
(Yes/ No / Room temperature sensor (1…16))
Configure Input
Sensor type selection
Setting of P-band and I-time
Setpoint room temperature
Configuration ► Analog inputs
► Supply air temperature
Configuration ► Analog inputs
► Supply air temperature
Ventilation ► PID controllers ►
Room
Ventilation ► Actual / Setpoint
► Room controller
Setpoint room temperature
Note
Selection of temperature control
38 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Required inputs for Room (summer) else supply air
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs
✓ Supply air temperature
✓ Room temperature 1…16
✓ Outdoor temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Extract air (summer) else supply air outdoor compensated
Summer mode dependent switching between outdoor compensated supply air temperature control and extract air cascade.
When the summer mode function is off, outdoor temperature compensated supply air temperature control will be active, otherwise cascaded extract temperature control as in control mode 4. Summer mode function is used for switching control mode.
Settings and configuration for Extract air (summer) else supply air
Table 4-7 Path to configuration and settings for Extract air (summer) else supply air outdoor compensated
Feature
Extract air (summer) else supply air control
Sequence configuration
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Temperature control type
Configuration ► Functions ►
Sequence A to J
Starting order heating/cooling Configuration ► Functions ►
Starting order heating and
Starting order cooling
Summer mode settings Configuration ► Functions ►
Temperature control
Add extract air temperature sensor
Configuration ►Functions
►Temperature control
Activate summer mode
Supply air temperature sensor
(Yes/ No / Room temperature sensor (1…16)
Configure Input
Sensor type selection
Configuration ► Analog inputs
► Extract air temperature
Configuration ► Analog inputs► Supply air temperature
Setting of P-band and I-time Ventilation ► PID controllers ►
Extract air
Setpoint extract air temperature Ventilation ► Actual / Setpoint
► Extract air controller
Setpoint extract air
Note
Selection of temperature control
Required inputs for Extract air cascade (summer) else supply air
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs
✓ Extract air temperature
✓ Supply air temperature
✓ Outdoor temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Corrigo manual, Rev. D 39 (196)
Information for the specialist - Function descriptions
Room outdoor compensated
Cascade control of the room temperature and supply air temperature to achieve an outdoor compensated room temperature.
The room temperature setpoint is temperature compensated using a control curve with 8 node points, see the curve below in
Figure 4-3 Temperature compensation curve .
The default settings for the 8 node points are shown in table
below:
Figure 4-3 Temperature compensation curve
Table 4-8 Default settings for compensation curve
Outdoor temperature (°C)
5
10
15
- 20
-15
-10
-5
0
Setpoint supply temperature
25
24
23
23
22
20
18
18
Settings and configuration for Room outdoor compensated control
Table 4-9 Path to configuration and settings for Room outdoor compensated
Feature
Room outdoor compensated
Sequence configuration
Starting order heating/cooling
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence A to J
Temperature control type
Configuration ► Functions ►
Starting order heating and
Starting order cooling
Note
Selection of temperature control
40 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-9 Path to configuration and settings for Room outdoor compensated (continued)
Feature
Add room temperature sensor
Menu path in Application tool Variable
Configuration ► Functions ►
Temperature control
Room temperature sensor
Configure input Configuration ► Analog inputs
► Outdoor temperature
Setting of P-band and I-time
Setpoint adjustment
Ventilation ► PID controllers ►
Room
Ventilation ► Actual / Setpoint
► Room controller
Setpoint outdoor curve ( X, Y ) Ventilation ► Actual / Setpoint
► Room controller
Setpoint adjustment
✓ Setpoint outdoor curve X
(1…4)
✓ Setpoint outdoor curve Y
(1…4)
Note
0…16
Required inputs for Room outdoor compensated
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs ✓ Outdoor temperature
✓ Room temperature 1…16
✓ Supply air temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Extract air outdoor compensated
Cascade control of the extract air temperature and supply air temperature to achieve an outdoor compensated extract air temperature.
The supply air temperature setpoint is temperature compensated using a control curve with 8 node points, see the curve below in
Figure 4-4 Temperature compensation curve
.
Figure 4-4 Temperature compensation curve
Corrigo manual, Rev. D 41 (196)
Information for the specialist - Function descriptions
The default settings for the 8 node points are shown in table
Table 4-8 Default settings for compensation curve
below:
Table 4-10 Default settings for compensation curve
Outdoor temperature (°C)
0
5
10
15
- 20
-15
-10
-5
Setpoint supply temperature
22
20
18
18
25
24
23
23
Settings and configuration for Extract air outdoor compensated control
Table 4-11 Path to configuration and settings for Extract air outdoor compensated
Feature
Extract air outdoor compensated
Sequence configuration
Starting order heating/cooling
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Temperature control type
Configuration ► Functions ►
Sequence A to J
Configuration ► Functions ►
Starting order heating and
Starting order cooling
Note
Selection of temperature control
Add extract air temperature sensor
Configure input
Configuration ► Functions ►
Temperature control
Configuration ► Analog inputs
► Extract air temperature
Extract air temperature sensor
Setpoint outdoor curve ( X, Y ) Ventilation ► Actual / Setpoint
► Extract air controller
✓ Setpoint outdoor curve X
(1…4)
✓ Setpoint outdoor curve Y
(1…4)
Setting of P-band and I-time Ventilation ► PID controllers ►
Extract air
Setpoint extract air temperature Ventilation ► Actual / Setpoint
► Extract air controller
Setpoint adjustment Ventilation ► Actual / Setpoint
► Extract air controller
Setpoint extract air
Setpoint adjustment
0…16
Required inputs for Extract air outdoor compensated
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs ✓ Extract air temperature
✓ Outdoor temperature
✓ Supply air temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
42 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Extract air dependent supply air
A difference between extract air temperature and supply air temperature can be configured to maintain the supply air temperature setpoint to follow extract air temperature with this difference (+10°C to -10°C).
Supply air temperature setpoint = extract air temperature + difference .
Settings and configuration for Extract air dependent supply air
Table 4-12 Path to configuration and settings for Extract air dependent supply air
Feature
Extract air dependent supply air Configuration ► Functions ►
Sequence configuration
Menu path in Application tool Variable
Temperature control type
Function activation
Configuration ► Functions ►
Sequence A to J
Starting order heating/cooling Configuration ► Functions ►
Starting order heating and
Starting order cooling
Add extract air / supply air temperature sensor
Configuration ► Functions ►
Temperature control
✓ Extract air temperature sensor
✓ Supply air temperature sensor
Configure input Configuration► Analog input ►
Extract air temperature/Supply air temperature
Setting of P-band and I-time Ventilation ► PID controllers ►
Extract air
Setpoint extract air temperature Ventilation ► Actual/Setpoint ►
Extract air controller
Setpoint extract air
Setpoint adjustment Ventilation ► Actual/Setpoint►
Extract air controller
Setpoint adjustment
Setpoint temperature difference Ventilation ► Actual/Setpoint ►
Supply air controller
Setpoint delta T extract air supply air (°C)
Note
Selection of temperature control
0…16
Required inputs for Extract air dependent supply air
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs
✓ Extract air temperature
✓ Supply air temperature
Settings
✓ Terminal
✓ Name
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Corrigo manual, Rev. D 43 (196)
Information for the specialist - Function descriptions
4.3 Temperature sequences
Figure 4-5 Configuration - Functions - Sequences
The supply air controller output is either a heating demand or a cooling demand depending on if the supply temperature is over or under the setpoint. This demand is then divided into up to 10 sequences A to J. Each sequence can be configured as Heating , Cooling , Exchanger , Damper , Fan setpoint compensation or Not used .
(See
for more information about configuration).
Figure 4-6 Sequence types
Each sequence has it own PID-settings that can be set in the Ventilation section of Application tool.
Each of these output sequences can be bound to either an analogue output, to two digital 3-position increase/decrease outputs, to one pulse-width modulated (PWM) digital output with a settable period time, or to a start/stop digital output with configurable start and stop limits.
44 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
4.3.1
Heater (Sequence A)
Sequence A is set to Heater as default, but can be changed
Heater types
Figure 4-7 Path to selection of heater types
Water heating
Control
If a sequence is configured as water heating, it’s possible to select if the sequence should be controlled with freeze protection and which freeze protection sensor (1…3) that should be used. The sequence is controlled by the corresponding sequence analogue output or by two digital outputs: 3-position actuator; increase and decrease.
Table 4-13 Settings and configuration for water heater
Feature
Water heater
Menu path in Application tool Variable
Configuration ► Functions ►
Heater (Sequence A) or other sequence configured as heater
Type of heater
Type of freeze protection Freeze protection Configuration ► Functions ►
Heater (Sequence A) or other sequence configured as heater
Select freeze protection temperature sensor
Configuration ► Functions ►
Heater (Sequence A) or other sequence configured as heater
Freeze protection temperature sensor (1, 2 or 3)
Sequence start order Configuration ► Functions ►
Starting order heating
Freeze protection temperature Configuration ► Analog inputs
► Freeze protection temperature 1…3
✓
✓
✓
Sensor type
Filter factor
Compensation
✓ Mode
✓ Manual
✓ Actual value
Note
Corrigo manual, Rev. D 45 (196)
Information for the specialist - Function descriptions
Table 4-13 Settings and configuration for water heater (continued)
Feature
Analogue output
Digital outputs
Menu path in Application tool Variable
Configuration ► Analog output
► Heater (Sequence A) or other sequence configured as heater
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Configuration ► Digital outputs
► Sequence A increase /
Sequence A decrease
✓ NC (Normally closed)
✓ NO (Normally open)
Note
Table 4-14 Required outputs for water heater
Outputs
AO
DO
Menu path in Application tool Name Settings
Configuration ► Analog output Heater (Sequence A) or other sequence configured as heater
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Configuration ► Digital outputs Sequence A increase/Sequence
A decrease
✓ NC (Normally closed)
✓ NO (Normally open)
Freeze protection
The heater return water temperature is measured using the analog input Freeze protection temperature 1…3 or the digital input Freeze protection guard , depending on the selection of freeze protection ( Configuration ►
Heater (Sequence A) ► Type of freeze protection ). Low temperatures will generate an internal, proportional signal that is used to force the heating valve open, thereby preventing freeze-up of the heater.
The internal signal will begin to rise as the frost protection temperature falls below the Alarm limitation running mode + P-band running mode in order to reach 100 % output when the signal has fallen to Alarm level .
When the internal signal reaches 100 % or the digital input Freeze protection guard is activated, the unit is shut down, the heating output is set to completely open mode and an alarm is activated. .
protection sensor has risen above Alarm limitation running mode + P-band running mode .
Freeze protection control is available on all sequences A to J.
46 (196) Corrigo manual, Rev. D
Internal signal
100 %
Information for the specialist - Function descriptions
Prop. band
0 %
Alarm level Freeze protection sensor
Figure 4-8 Freeze protection
Table 4-15 Settings and configuration for freeze protection
Feature
Water heater
Menu path in Application tool Variable
Configuration ► Functions ►
Heater (Sequence A) (or other sequence configured as heater)
Type of heater
Note
✓ Inactive
✓ Water
✓ Electric
✓ DX
✓ Combi coil
✓ Temperature sensor
✓ Freeze guard
✓ Sensor + Guard
Freeze protection
Freeze protection temperature sensor
Configuration of freeze protection temperature,
Freeze protection setpoints
PID-settings
Configuration ► Functions ►
Heater (Sequence A) (or other sequence configured as heater)
Type of freeze protection
Configuration ► Functions ►
Heater (Sequence A) (or other sequence configured as heater)
1…3
Configuration ► Analog inputs
► Freeze protection temperature 1…3
Ventilation ► Temperature control ► Freeze protection 1…
3
✓ Alarm limitation running mode
✓ P-band running mode
✓ Setpoint standby mode
Ventilation ► PID-controllers ►
Freeze protection 1…3
✓ Sensor type
✓ Filter factor
✓ Compensation
✓ Mode
✓ Manual
✓ Actual value (read only)
Table 4-16 Required inputs for freeze protection
Inputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs Freeze protection temperature
1…3
Settings
✓ Sensor type
✓ Filter factor
✓ Compensation
✓ Mode
✓ Manual
✓ Actual value (read only)
Corrigo manual, Rev. D 47 (196)
Information for the specialist - Function descriptions
N Freeze protection guard and an activated. The heating sequence output is set to completely open, the remaining control outputs are set to zero.
Standby mode
If frost protection is activated the controller will go into Standby mode when the running mode switches to
Off . The controller will then control the heating output to maintain a constant temperature at the frost protection sensor. The setpoint for the standby mode is found in Ventilation ► Temperature control ► Freeze protection 1…3
Electric heating
Electric heating is controlled using the analogue output sequence A to J. On activation of the digital input
Overheated electric heater the unit will be shut down, either according to the stop sequence described in section
5.13 Starting and stopping the Corrigo
or as an emergency shutdown. The unit will restart after the alarm has been acknowledged and Overheated electric heater has reset. Note that activation of the input signal
Flow guard will also stop the unit.
Control voltage
Relay electric heating
High limit thermostat
Corrigo
Control voltage
Auxiliary relay
Figure 4-9 Wiring example, high temp limit. Contactors are drawn inactivated.
the heater to ensure that the heating is shut down when the thermostat is activated even if the
Corrigo should be faulty.
Table 4-17 Settings and configuration for electric heating
Feature
Electric heater
Overheating
Flow guard
Alarm
Menu path in Application tool Variable
Configuration ► Functions ►
Heater (Sequence A) (or other sequence configured as heater)
Type of heater
Configuration ► Digital inputs
► Overheated electric heater
Configuration ► Digital inputs
► Flow guard
Alarm status
Note
48 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-18 Required inputs for electric heating
Inputs
DI
Menu path in Application tool Name
Configuration ► Digital input ✓ Overheated electric heater
✓ Flow guard
Settings
Fast stop on overheating
Fast stop is an option in Alarm 63 - Electric heating is overheated . The function means that the fans will be immediately stopped when there is an overheating alarm, regardless of the set cool-down time. It is set in
Alarm status ► 63 Electric heating is overheated ► Edit ► Alarm action.
DX Heater
A DX heater is used together with DX cooler in case of controlling a reversible heat pump.
The heat pump can be switched between heating and cooling. The type of heater sequence needs to be set to
DX and the type of cooler sequence to either DX or DX with exchanger control .
Both sequences are combined with a change-over function.
Inputs and outputs used for controlling the reversible heat pump:
Table 4-19 Required inputs and outputs for controlling the reversible heat pump
Inputs and outputs
DI
AO
DO
Menu path in Application tool Name
Configuration ► Digital inputs ✓ Feedback cooling sequence
✓ Lock PID controller supply
Configuration ► Analog outputs
Change-over 1/2
Configuration ► Digital outputs ✓ Change-over 1/2
✓ Cooling sequence
Note
Inputs and outputs for heater types
Water heating
AI
Electric heating
DI
AO
DO
DI
DI
AO
DO
DX heating
AO
DO
Freeze protection sensor 1…3
(optional)
Freeze protection thermostat
1…3 water heater (optional)
Overheated electric heater
Flow switch (optional)
Sequence x
✓ Sequence x start
✓ Sequence x PWM
✓ Sequence x increase
✓ Sequence x decrease
✓ Sequence x pump
Corrigo manual, Rev. D 49 (196)
Information for the specialist - Function descriptions
4.3.2
Exchanger (Sequence B)
Sequence B is set to Exchanger by default but can be changed.
The heat exchanger unit can be set to one of the following alternatives:
Figure 4-10 Exchanger alternatives
Rotating exchanger
Control
Rotational speed is controlled by the analogue signal Sequence A to J. A rotation guard can be connected to the digital input Rotary exchanger alarm (Alarm 67 Rotary changer alarm in the Alarm status). An alarm is generated if this input is not activated at the same time as the analogue output signal is higher than 1.0 V.
Freeze protection
A defrosting sensor or an exhaust air temperature sensor can be used as a prevention sensor. It is possible to set a starting temperature in Ventilation ► Temperature control ► Exchanger ► Defrosting setpoint min limit and
Min time . This represents both the minimum time that the function should be active, the supply air fan
(SAF) and extract air fan (EAF) compensation, as well as the minimum time before the next prevention cycle should begin. While the cycle is active, Defrosting mode is shown in the display.
Outdoor temperature control of exchanger
Instead of using Sequence A to J for analogue control of the heat exchanger it can be set to run on-off against outdoor temperature. The function controls a digital output Outdoor controlled exchanger , which is activated when the outdoor temperature falls below a set value.
50 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Settings and configuration for rotating exchanger
Table 4-20 Rotating exchanger, settings and configuration
Feature
Rotating exchanger
Temperature setpoints
Note
Analog output signal
Defrosting
Configuration ► Analog outputs
► Sequence A to J
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Configuration ► Functions ►
Temperature control
Defrosting exchanger
Defrosting temperature sensor Configuration ► Functions ►
Temperature control
Defrosting temperature sensor Defrosting sensor
Exhaust air temperature
Outdoor control
Menu path in Application tool Variable
Configuration ► Functions ►
Exchanger (Sequence B) (or other sequence configured as exchanger)
Type of exchanger
Configuration ► Digtal outputs
► Outdoor controlled exchanger
Ventilation ► Temperature control ► Exchanger
Hysteresis setpoints Ventilation ► Temperature control ► Exchanger
Outdoor start/stop exchanger temperature
Defrosting setpoint min limit
Stop supply air fan if outdoor temp <
Hysteresis
Hysteresis to stop defrosting
Delay setpoints Ventilation ► Temperature control ► Exchanger
Start delay exchanger
Start delay with 100 % exchanger
Start alarm delay
Plate exchanger
Control
The airflow through the exchanger is controlled by a shut-off damper and a by-pass damper. Both dampers are controlled by the same analogue output Sequence A to J or by two types of digital outputs: Sequence A to J PWM or 3-position actuator; increase and decrease ( Sequence A to J increase/decrease )and are wired so that one opens as the other closes.
Defrosting
Defrosting is activated either when the digital signal Defrosting is activated in Application tool or when the value of the analogue input Defrosting temperature falls below the de-icing limit (-3°C), or when the analogue signal Pressure extract air rises above the set value for the current pressure.
It is deactivated when the digital signal is reset, or alternatively when the analogue signal rises above the limit value plus a settable differential ( Ventilation ► Temperature control ► Exchanger ► Hysteresis to stop defrosting ).
It’s also possible to use Exhaust air temperature instead of Defrosting temperature for the defrosting function
( Configuration ► Functions ► Temperature control ► Defrosting temperature sensor ).
A PI-controller compares the defrosting setpoint with the signal Defrosting guard exchanger . The lesser of the output signal from this controller and the output from the ordinary controller is used as output to the bypass dampers.
If the digital input signal Defrosting guard exchanger is activated the exchanger is blocked, it will stay blocked as long as the digital input signal is active.
Corrigo manual, Rev. D 51 (196)
Information for the specialist - Function descriptions
Freeze protection
A defrosting sensor or an exhaust air temperature sensor can be used as a prevention sensor. It is possible to set a starting temperature in Ventilation ► Temperature control ► Exchanger ► Defrosting setpoint min limit and
Min time . This represents both the minimum time that the function should be active, the supply air fan
(SAF) and extract air fan (EAF) compensation, as well as the minimum time before the next prevention cycle should begin. While the cycle is active, Defrosting mode is shown in the display.
Table 4-21 Configuration and settings for Plate exchanger
Feature
Plate exchanger
Damper control, Analog Output Configuration ► Analog output
► Sequence B (exchanger) or other sequence configured as exchanger
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
3-position increase / decrease outputs
Configuration ► Digital outputs
► Sequence A to J increase / decrease
PWM with settable period time Configuration ► Digital outputs
► Sequence A to J PWM
✓ NC (Normally closed )
✓ NO (Normally open)
✓ NC (Normally closed )
✓ NO (Normally open)
PWM period time Period time for PWM signal
Defrosting
Configuration ► Functions ►
Sequence A to J
Configuration ► Functions ►
Exchanger (Sequence B or other sequence configured as exchanger
Defrosting mode
Defrosting sensor
Defrosting exchanger
Defrosting temperature
Menu path in Application tool Variable
Configuration ► Functions ►
Sequence B (exchanger) or other sequence configured as exchanger
Type of exchanger
Configuration ► Functions ►
Temperature control
Configuration ► Functions ►
Temperature control
Configuration ► Analog inputs
► Defrosting temperature
Defrosting temperature sensor
Defrosting exchanger
Extract air fan speed when defrosting
Configuration ► Functions ►
Temperature control
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
✓ Actual value (°C)
Extract air fan speed when defrosting with stopped supply air
Note
Yes / No
✓ Auto
✓ Low
✓ Normal
✓ High
Pressure extract air
Exhaust air temperature
Configuration ► Analog inputs
► Pressure extract air
Configuration ► Analog inputs
► Exhaust air temperature
Temperature setpoints Ventilation ► Temperature control ► Exchanger
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
✓ Actual value (°C)
✓ Outdoor start / stop exchanger temperature (°C)
✓ Defrosting setpoint limit (°C)
✓ Stop supply air time if outdoor temp < (°C)
52 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-21 Configuration and settings for Plate exchanger (continued)
Feature
Hysteresis setpoints
Delay setpoints
Menu path in Application tool Variable
Ventilation ► Temperature control ► Exchanger
✓ Hysteresis (°C)
✓ Hysteresis to stop defrosting
(°C)
Note
Ventilation ► Temperature control ► Exchanger
✓ Start delay exchanger (s)
✓ Start delay with 100 % exchanger (s)
✓ Start alarm delay (s)
Liquid exchanger
Control
A mixing valve in the exchanger circulation system is controlled by the analog signal sequence A to J or by two types of digital outputs: Sequence A to J PWM or 3-position actuator; increase and decrease ( Sequence A to J increase/decrease ).
The circulation pump is started as soon as the actuator control signal exceeds 0.1 V and is stopped when the valve has been closed for more than 5 minutes. ( Ventilation ► Temperature control ► Sequence X ► Pump stop delay )
Defrosting
Defrosting is activated either when the digital input signal Defrosting guard exchanger is activated or when the value of the analog input Defrosting temperature falls below the deicing limit (-3°C). It is deactivated when the digital input is reset, or the analog input rises above the limit value plus a settable differential.
( Ventilation ► Temperature control ► Exchanger ► Hysteresis to stop defrosting )
On defrosting:
A PI-controller compares the defrosting setpoint with the signal from the Defrosting temperature sensor or
Exhaust air temperature sensor ( Configuration ► Functions ► Temperature control ). The lesser of the output signal from this controller and the output from the ordinary controller is used as output to the actuator.
If the digital input signal Defrosting guard exchanger is activated the exchanger is blocked, it will stay blocked as long as the digital input signal is active.
Function to prevent the heat exchanger from freezing:
A defrosting sensor or an exhaust air temperature sensor can be used as a prevention sensor. It is possible to set a starting temperature in Ventilation ► Temperature control ► Exchanger ► Defrosting setpoint min limit and
Min time . This represents both the minimum time that the function should be active, the supply air fan
(SAF) and extract air fan (EAF) compensation, as well as the minimum time before the next prevention cycle should begin. While the cycle is active, Defrosting mode is shown in the display.
Outdoor temperature control of exchanger
Instead of using Sequence A to J for analogue control of the heat exchanger it can be set to run on-off against outdoor temperature. This function is activated when you configure the digital output Outdoor controlled exchanger . The digital output is available if the Outdoor temperature sensor in Configuration ► Functions ►
Temperature control is set to anything else than No .
The digital output is activated when the outdoor temperature falls below a set value. The temperature setpoint is set in the Analog input Outdoor temperature or Intake air temperature , depending on the configuration.
Corrigo manual, Rev. D 53 (196)
Information for the specialist - Function descriptions
Configuration and settings for Liquid exchanger
Table 4-22 Configuration and settings for Liquid exchanger
Feature
Liquid exchanger
Menu path in Application tool Variable
Configuration ► Functions ►
Sequence B (exchanger) or other sequence configured as exchanger
Type of exchanger
Damper control, Analog Output Configuration ► Analog output
► Sequence B (exchanger) or other sequence configured as exchanger
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
3-position increase / decrease outputs
Configuration ► Digital outputs
► Sequence A to J increase / decrease
PWM with settable period time Configuration ► Digital outputs
► Sequence A to J PWM
✓ NC (Normally closed )
✓ NO (Normally open)
✓ NC (Normally closed )
✓ NO (Normally open)
PWM period time Period time for PWM signal
Defrosting
Configuration ► Functions ►
Sequence A to J
Configuration ► Functions ►
Sequence B (exchanger) or other sequence configured as exchanger
Defrosting mode
Defrosting sensor
Defrosting exchanger
Defrosting temperature
Configuration ► Functions ►
Temperature control
Configuration ► Functions ►
Temperature control
Configuration ► Analog inputs
► Defrosting temperature
Defrosting temperature sensor
Defrosting exchanger
Extract air fan speed when defrosting
Configuration ► Functions ►
Temperature control
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
✓ Actual value (°C)
Extract air fan speed when defrosting with stopped supply air
Note
Yes / No
✓ Auto
✓ Low
✓ Normal
✓ High
Outdoor controlled exchanger Configuration ► Digital outputs
► Outdoor controlled exchanger
✓ NC (Normally closed )
✓ NO (Normally open)
Exhaust air temperature Configuration ► Analog inputs
► Exhaust air temperature
✓ Sensor type
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
✓ Actual value (°C)
Temperature setpoints Ventilation ► Temperature control ► Exchanger
✓ Outdoor start / stop exchanger temperature (°C)
✓ Defrosting setpoint limit (°C)
✓ Stop supply air fan if outdoor temp < (°C)
Hysteresis setpoints Ventilation ► Temperature control ► Exchanger
✓
✓
Hysteresis (°C)
Hysteresis to stop defrosting
(°C)
Delay setpoints Ventilation ► Temperature control ► Exchanger
✓
✓
Start delay exchanger (s)
Start delay with 100 % exchanger (s)
✓ Start alarm delay (s)
54 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Exchanger and damper sequence
If both an exchanger sequence and a damper sequence is configured, the exchanger sequence will stop when the damper sequence reaches 100 %.
Inputs and outputs for exchanger types
Rotating
AI
DI
Plate
AI
DI
DI
DI
AO 1
DO 1
AO 1
DO 1
Liquid
AI
DI
DI
AO 1
DO 1
DO 1
Description
Defrosting temperature
Feedback sequence x
Defrosting guard exchanger
Rotary exchanger alarm
Sequence x analog output
✓ Sequence x PWM
✓ Sequence x increase/ decrease
✓ Sequence x start
Sequence x pump
1. Depending on type of sequence output
4.3.3
Cooler (Sequence C)
Sequence C is set to Cooling as default, but it can be changed to any sequence.
Water cooling
Control
If a sequence is configured as water cooling, it’s controlled by the corresponding sequence analog output or by two digital outputs; 3-position actuator; increase and decrease.
Table 4-23 Settings and configuration for water cooling
Feature
Water cooling
Analogue output
Digital output
PID settings
Sequence start order
Menu path in Application tool Variable
Configuration ► Functions ►
Cooler (Sequence C) or other sequence configured as cooler
Type of cooler
Configuration ► Analog outputs
► Cooler (Sequence C) or other sequence configured as cooler
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Configuration ► Digital outputs
► Sequence C increase / decrease
Ventilation ► PID controllers ►
Cooler (sequence C)
✓ NC (Normally closed)
✓ NO (Normally open)
Configuration ► Functions ►
Sequence cooling
Description
DX cooling with room or extract air control
If DX cooling is used in conjunction with room temperature control or extract air temperature control, there are two configuration alternatives, DX cooling or DX cooling with exchanger control.
Corrigo manual, Rev. D 55 (196)
Information for the specialist - Function descriptions
DX cooling
When running cascade control, the supply air controller setpoint is normally controlled by the room/extract air controller output signal.
When DX cooling is activated, the supply air controller setpoint is lowered to five degrees (adjustable) below the setpoint given by the room/extract air controller. This prevents the DX cooling from being activated/deactivated too often.
Table 4-24 Settings and configuration for DX cooling
Feature
DX cooling
Supply air controller setpoint for
DX
Setpoint Room / Extract air
Menu path in Application tool Variable
Configuration ► Functions ►
Cooler (Sequence C) or other sequence configured as cooler
Type of cooler
Ventilation ► Actual / Setpoint
► Supply air controller
Ventilation ► Actual / Setpoint
► Room controller/ Extract air controller
Reduction of min limit supply air if active DX-cooling (°C)
✓
✓
✓
Setpoint adjustment
Setpoint room / extract air
Actual setpoint
✓ Controller output
Note
DX cooling with exchanger control
When running cascade control, the supply air controller setpoint is normally controlled by the room/extract air controller output signal.
When DX cooling is activated, the supply air controller setpoint is lowered to five degrees (adjustable) below the setpoint given by the room/extract air controller. This prevents the DX cooling from being activated/deactivated too often.
If the supply air temperature falls below the setpoint given by the room/extract air controller, the heat exchanger output will be activated in order to try to maintain the supply air setpoint given by the room/ extract air controller. The output uses P-control with a P-band of half the setpoint lowering (adjustable, 2.5°
C as default). The setpoint given by the room/extract air controller cannot drop below the set min limit.
When there is no longer a cooling demand, the supply air controller setpoint will return to the value given by the room/extract air controller.
Example:
The room controller gives a supply air setpoint of 16°C. If there is a cooling demand, the supply air controller setpoint is lowered to 11°C (16 – 5) and DX cooling is activated. Should the supply air temperature fall below 16°C, the exchanger output will be activated and reach 100 % output when the supply air temperature has fallen to 13.5°C (16 - 2.5).
Table 4-25 Settings and configuration for DX cooling with exchanger control
Feature
DX cooling
Menu path in Application tool Variable
Configuration ► Functions ►
Cooler (Sequence C) or other sequence configured as cooler
Type of cooler
Supply air controller setpoint for
DX
Ventilation ► Actual / Setpoint
► Supply air controller
Reduction of min limit supply air if active DX-cooling (°C)
Note
56 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-25 Settings and configuration for DX cooling with exchanger control (continued)
Feature
Setpoint Room / Extract air
Heat exchanger output
P-band
Menu path in Application tool Variable
Ventilation ► Actual / Setpoint
► Room controller/ Extract air controller
✓ Setpoint adjustment
✓ Setpoint room / extract air
✓ Actual setpoint
✓ Controller output
Configuration ► Analog outputs
► Exchanger (Sequence B)
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Ventilation ► PID controllers ►
Exchanger (Sequence B) /
Cooler (Sequence C)
Note
Blocking of DX cooling at low outdoor temperature
DX cooling can be blocked when the outdoor temperature is low. It is possible to block the four cooling steps individually or to block all DX cooling. The temperature limits are adjustable (+13°C default) and have a fixed one degree hysteresis.
When two DX cooling steps are used with binary function, the cooling effect is divided into three steps. The desired blocking level can be set individually for each of these steps.
When three DX cooling steps are used with binary function, the cooling effect is divided into seven steps.
However, the controller still only has four blocking level settings. Therefore, Blocking step 1 will apply to binary steps 1 and 2, Blocking step 2 to binary steps 3 and 4, Blocking step 3 to binary steps 5, 6 and Blocking step 4 to binary steps 7.
When four DX cooling steps are used with binary function, the cooling effect is divided into fifteen steps.
However, the controller still only has four blocking level settings. Therefore, Blocking step 1 will apply to binary steps 1-4, Blocking step 2 to binary steps 5-8, Blocking step 3 to binary steps 9-12 and Blocking step 4 to binary steps 13-15.
Table 4-26 Settings and configuration for blocking DX cooling at low outdoor temperature
Feature
Block DX cooling
Hysteresis
Menu path in Application tool Variable
Ventilation ► Temperature control ► Step Controller 1/2
Block step x if outdoor temperature < (°C)
Note
Ventilation ► Temperature control ► Step Controller 1/2
Block DX-cooling if outdoor temperature < (°C)
Blocking of DX cooling at low supply air fan speed
When DX cooling is used in conjunction with pressure controlled or flow controlled fans it is possible to block DX cooling if the supply air fan control signal falls below a preset values. For sequential control, the blocking level is individually settable for each DX cooling step.
When two DX cooling steps are used with binary function, the cooling effect is divided into three steps. The desired blocking level can be set individually for each of these steps.
When three DX cooling steps are used with binary function, the cooling effect is divided into seven steps.
However, the controller still only has four blocking level settings. Therefore, Blocking step 1 will apply to binary steps 1 and 2, Blocking step 2 to binary steps 3 and 4, Blocking step 3 to binary steps 5, 6 and Blocking step 4 to binary steps 7.
When four DX cooling steps are used with binary function, the cooling effect is divided into fifteen steps.
However, the controller still only has four blocking level settings. Therefore, Blocking step 1 will apply to
Corrigo manual, Rev. D 57 (196)
Information for the specialist - Function descriptions
binary steps 1-4, Blocking step 2 to binary steps 5-8, Blocking step 3 to binary steps 9-12 and Blocking step 4 to binary steps 13-15.
Table 4-27 Settings and configuration for blocking DX cooling at low supply air fan speed
Feature
Block DX cooling
Menu path in Application tool Variable
Ventilation ► Temperature control ► Step Controller 1/2
Block step x if supply air fan output signal < (%)
Note
Blocking of DX cooling on cooling pump alarm
Corrigo can be configured to block DX cooling on cooling pump alarm. The setting is found in Configuration
► Functions ► Step controller 1/2 ► Block output if sequence feedback alarm .
Inputs and outputs, Cooling and Heating / Cooling Change-Over
Table 4-28 Inputs and outputs
Water
DI
AO 1
DO 1
DX
DI
AO 1
DO 1
DX with exchanger control
DI
AO 1
DO 1
DO 1
1. Depending on type of sequence output
Description
Feedback sequence x
Sequence x analog output
✓ Sequence x PWM
✓ Sequence x increase/ decrease
✓ Sequence x start
Sequence x pump
4.3.4
Damper sequence
Mixing dampers
Control
The analog output signal sequence A to J, or the digital output signals Sequence A to J PWM or 3-position; increase and decrease ( Sequence A to J increase/decrease ), control two dampers for gradual mixing of outdoor air and recirculated air. In this mode the output signal decreases with increasing heat demand.
Table 4-29 Settings and configuration for Mixing dampers
Feature
Select damper control
Analog output
Digital output, PWM
Digital output, 3 position actuator
Menu path in Application tool Variable
Configuration ► Functions ►
Any sequence
Type of sequence
Configuration ► Analog outputs
► Selected sequence
Configuration ► Digital outputs
► Selected sequence
Sequence x PWM
Configuration ► Digital outputs
► Selected sequence
✓ Sequence x increase
✓ Sequence x decrease
Description
58 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
CO
2
If demand controlled ventilation is activated in combination with mixing dampers, CO
2
-control is activated for the sequence, and the CO
2
-value rises above the setpoint value, the dampers will let in more outdoor air.
The function is controlled by a PI-controller.
Table 4-30 Settings and configuration for CO
2 and mixing dampers
Feature
Select damper control
CO
2 control activation
Menu path in Application tool Variable
Configuration ► Functions ►
Any sequence
Type of sequence
Configuration ► Functions ►
Function activation
CO2 control
Note
✓ No
✓ Fan start / stop function
✓ Mixing damper function
✓ Fan start / stop + Mixing damper
CO
2 setpoint
PI settings
Ventilation ► Demand control
► CO2
✓ Setpoint mixing damper
(ppm)
✓ Start limit fan start / stop
(ppm)
✓ Stop hysteresis fan start / stop (ppm)
✓ Demand control
✓ Min time for CO2 control
(min)
Ventilation ► PID controllers ►
CO2
Minimum limit
An outdoor air minimum limit for the amount of fresh air can be set in Application tool or in the web interface. The limit value is settable between 0 and 100 %. (Application tool ► Configuration ► Functions ►
Sequence x ► Sequence output min limit (%) and Sequence output max limit (%)
Damper control and exchanger sequence
If both an exchanger sequence and a damper sequence is configured, the exchanger sequence will stop when the damper sequence reaches 100 %.
Inputs and outputs, Damper
Table 4-31 Inputs and outputs Dampers
Dampers
AI 1
DI
AO 2
✓ Humidity room/extract
✓ Humidity outdoor
✓ CO2 room/extract
Feedback sequence x
Sequence x analog output
DO 2
✓ Sequence x PWM
✓ Sequence x increase/decrease
✓ Sequence x start
1. Depending on control mode
2. Depending on type of sequence output
Damper via Modbus
There is support for the following damper via Modbus communication:
Corrigo manual, Rev. D 59 (196)
Information for the specialist - Function descriptions
✓ Belimo
✓ Siemens
4.3.5
Sequence Fan setpoint compensation
The fan setpoint compensation is used to integrate the fans into the temperature control sequence for heating or cooling. The speed of the fans can be increased or decreased depending on the signal of the temperature control loop. ( Application tool ► Configuration ► Functions ► Sequence x ► Type of setpoint compensation ). The output signal of the sequence acts directly on the calculated setpoint of the fans but can also be output additionally via configured outputs. The maximum compensation is adjustable via a parameter ( Ventilation ► Temperature control ► Selected sequence ► Max fan compensation (% )).
Table 4-32 Settings and configuration for fan setpoint compensation
Feature
Select fan setpoint compensation
Type of compensation
Max compensation
Menu path in Application tool Variable
Configuration ► Functions ►
Sequence x
Type of sequence
Configuration ► Functions ►
Selected sequence
Ventilation ► Temperature control ► Selected sequence
Type of setpoint compensation
Max fan compensation (%)
Note
✓ Decrease
✓ Increase
Fan setpoint compensation
DI
AO 1
DO 1
Feedback sequence x
Sequence x analog output
✓ Sequence x PWM
✓ Sequence x increase/decrease
✓ Sequence x start
1. Depending on type of sequence output
4.3.6
Change-over
Change-over is a function for installations with 2-pipe systems. It makes it possible to use the same pipe for both heating and cooling, depending on whether heating or cooling is required.
Change-over functions can be used for control of reversible heat pumps or external change-over coils.
There are two different change-over functions with two different analog output signals Change-over 1 and
Change-over 2 , that is used for change-over control.
Switching between heating and cooling can be done in two ways. Open contact gives heating control and closed contact gives cooling control.
If the input has not been configured, change-over is handled by the internal controller signal. The output signal will follow the two sequence output signals Change-over sequence for heating and Change-over sequence for cooling .
If frost protection sensor has been configured, it will function in the usual way when heating is active.
However, when cooling is active, it will only be used for indicating temperature.
60 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-33 Path to configuration and settings for Change-over
Feature Menu path in Application tool Variable
Select change-over sequence Configuration ► Functions ►
Change-over 1/ 2
Digital inputs Change-over Configuration ► Digital inputs►
Cooling / (Heating) Changeover…
✓ NC (Normally closed)
✓ NO (Normally open)
✓ Manual / Auto
✓ Actual value
Note
4.3.7
Step controller
Step controller heating / cooling
As an alternative or complement to analog control, heating and cooling can be activated in steps. The internal signal is then used to activate digital outputs for control of the heaters/coolers. Two step controllers with up to four step outputs can be configured in Application tool.There are two possible modes; Sequential control and Binary control .
Sequential control
Each output step has individually settable on and off values in percent of the control signal. The number of steps is equal to the number of heater/cooler groups. Minimum on and off times can be set, i.e. the minimum time the step has to be inactive or active for a change to occur. An analog output signal can also be used to fill out between the steps. The signal will go 0…100 % between the activation of each step
Binary control
The heater power outputs should be binary weighted (1:2:4:8 same for heating and cooling). The number of steps to be controlled is set in Configuration ► Functions ► Step controller 1/2 ► Number of steps . After that, the program will automatically calculate the individual activation levels. Switching differential and minimum on/off times can be set in Ventilation ► Temperature control ► Step controller 1/2 ► Min switch time, Step x start point, Step x stop point . The number of heating/cooling steps will be: 2 no. of groups -1. In binary mode, the analog output signal ( Step controller 1 / 2 ) may also be used to fill out between the steps. The signal will go 0…100
% between the activation of each step. The load connected to the analog signal should have the same size as the smallest of the binary groups. In the example below there are 4 heater groups (1:1:2:4) and the total number of heating/cooling steps is eight.
Y1 = 1
1
2
1
1
4
2
1
Figure 4-11 Step controller example: 4 heater groups, 8 steps (1:1:2:4)
Corrigo manual, Rev. D 61 (196)
Information for the specialist - Function descriptions
Table 4-34 Settings and configuration of Step controllers
Feature
Select step control
Digital outputs
Analog output
Actual binary step
Min switch time
Start / Stop point steps
Menu path in Application tool Variable
Configuration ► Functions ►
Step controller 1 or 2
✓ Step controller sequence
(Sequence A to J or changeover 1 or 2))
✓ Step control type (Sequential or binary)
✓ Number of steps (1…4)
✓ Block output if sequence feedback alarm (Yes / No)
Description
Configuration ► Digital outputs
► Step controller 1(2) step 1...4
✓ NC (Normally closed)
✓ NO (Normally open)
Configuration ► Analog outputs
► Step controller 1 (2)
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Ventilation ►Actual / Setpoint
► Step controller 1 or 2
Min switch time (s) Ventilation ►Temperature control►Step controller 1 or 2
Ventilation ► Temperature control ► Step controller 1 or 2
Step X start point (%)
Step X stop point (%)
Block DX-cooling
Block step X if supply air fan output signal <
Ventilation ► Temperature control ► Step controller 1 or 2
Ventilation ► Temperature control ► Step controller 1 or 2
Block step X if outdoor temperature <
Ventilation ► Temperature control ►Step controller 1 or 2
Block DX-cooling if outdoor temperature < (°C)
Block step X if supply air fan output signal < (°C)
Block step ture < (°C)
X if outdoor tempera-
Step controllers and Change-over
By selecting a sequence that is configured as change-over sequence 1 or 2, the digital output signals step 1…4 will be controlled by both the heating sequence and the cooling sequence that is configured in the changeover function.
4.3.8
Support control
Support control is normally used when room temperature control or extract air control has been configured.
Extract air control
When extract air control is configured a room sensor must be installed.
Support control Heating or Support control Cooling will run if support control is configured, the running mode is in Off-state (timer control OFF and not in extended running) and if conditions call for support control (see below). Minimum run time is settable 0 to 720 minutes (FS= 20 minutes) ( Ventilation ► Demand control ► Support control ► Min time for support control ).
Supply air temperature control
Support control can also be configured when supply air temperature control is used, if a room sensor is installed. The controller uses the configured min. (FS=15°C) and max. (FS=30°C) limitation values as support control setpoints ( Ventilation ► Demand control ► Support control ). The values can be changed in
Ventilation ► Actual/Setpoint ► Supply air controller ► Min limit supply air, Max limit supply air.
Start with supply air fan
62 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Support control can also be configured to start only with the supply air fan. In this mode, the extract air fan is not active. This requires a digital output to be configured, which controls the recirculation damper to open completely so the supply air fan can circulate the air to and from the room. The digital output is called
Recirculation air damper ( Configuration ► Digital Outputs ).
Active support control for sequence
It’s also possible to configure the output value when support control is active (same settings as for recirculation) for each sequence. The sequence output can be configured to 0%, 100% or Auto (modulating
0-100%).
Table 4-35 Settings and configuration for Support control
Feature
Select support control
Extract fan running during support control
Minimum time for support control
Setpoints to start/stop heating room
Setpoint heating
Setpoints to start/stop cooling room
Setpoint cooling
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Support control
Support control (Yes/No)
Extract fan running during support control (Yes/No)
Ventilation ► Demand control
► Support control
Ventilation ► Demand control
► Support control
Min time for support control
(min)
✓ Start heating room temperature (°C)
✓ Stop heating room temperature (°C)
Setpoint heating (°C) Ventilation ► Demand control
► Support control
Ventilation ► Demand control
► Support control
Ventilation ► Demand control
► Support control
✓ Start cooling room temperature (°C)
✓ Stop cooling room temperature (°C)
Setpoint cooling (°C)
Description
Support control heating
Demand for support control heating is when the room temperature is lower than the start value which is settable 0 to 30°C ( Ventilation ► Demand control ► Support control ). The fans will run at the preset speed, the heater and the heat exchanger are controlled by the supply air temperature controller with the configured max limitation for the supply air (FS=30°C) as setpoint and the cooling is shut off (0%). Support control heating stops when the room temperature rises to the stop value and the minimum run time has been exceeded or the running mode changes to On .
For each sequence it’s also possible to configure the output value when support control heating is active. The sequence output can be configured to 0%, 100% or Auto (modulating 0-100%) (See section
for more details).
Support control cooling
Demand for support control cooling is when the room temperature is higher than the start value which is settable 20 to 50°C ( Ventilation ► Demand control ► Support control ). The fans will run at the preset speed, the heater and the heat exchanger (cool recovery is active) are shut down (0 %) and the cooling is controlled by the supply air temperature controller with the configured minimum limitation (FS=12°C) as setpoint.
Support control cooling stops when the temperature falls below the stop value and the minimum run time has been exceeded or the running mode changes to On .
For each sequence It’s also possible to configure the output value when support control cooling is active. The sequence output can be configured to 0%, 100% or Auto (modulating 0-100%) (See section
for more details).
Corrigo manual, Rev. D 63 (196)
Information for the specialist - Function descriptions
4.3.9
Free cooling
This function is used during the summer to cool the building night-time using cool outdoor air, thereby reducing the need for cooling during the day and saving energy.
Free cooling requires an outdoor sensor or an intake temperature sensor and either a room sensor or an extract air sensor. If both outdoor sensor and intake sensor is configured it uses the outdoor sensor for the function.
Free cooling is only activated when all the start conditions below are fulfilled:
✓ Less than four days have passed since the unit was last in running mode.
✓ The outdoor temperature during the previous running period exceeded a set limit (22°C).
✓ It is between 00:00 and 07:00 in the day (settable).
✓ The timer outputs for Normal speed , Extended running, Normal and External switch are Off .
✓ A timer channel will be On sometime during the next 24 hours.
✓ The outdoor temperature is a settable difference (FS=2°C) lower than the room/extract temperature
( Ventilation ► Demand control ► Free cooling ► Start when extract-outdoor > (°C) ).
If an intake sensor is used and/or an extract air sensor is selected and ALL the start conditions are fulfilled, free cooling is activated and will run for 3 minutes (settable) to ensure that the temperature measurement when using an extract air sensor reflects the corresponding room temperature, and that the intake temperature sensor senses the outdoor temperature even if it is placed in the fresh air inlet duct. If an outdoor sensor and a room sensor is selected, the unit will not start free cooling as long as all the temperatures are not within the start and stop temperature intervals.
After three minutes (settable), the stop conditions will be controlled.
Stop conditions:
✓ Outdoor temp above the set max. value (18°C) or below the set min. value (condensation risk, 10°C).
✓ The room temp/extract air temp. is below the set stop value (18°C).
✓ Difference between extract/room and outdoor temperature rises above the settable difference (FS=2°
C) - a hysteresis of 0.5 °C.
✓ The timer outputs for Normal speed , Extended running, Normal or External switch are On .
✓ It is past 07:00 in the day.
If any stop condition is fulfilled after three minutes, the unit will stop again. Otherwise, operation will continue until a stop condition is fulfilled.
If the unit is stopped due to outdoor temperature is outside the temperature intervals the unit will start again after 60 min (settable), it will not start again if room/extract air temp has reached below the stop value.
When free cooling is active, the fans run at normal speed or the set value for pressure/flow control. An offset can also be entered for the fan setpoints during free cooling. The digital output Free cooling indication is active. All sequence A to J outputs are shut down. After free cooling has been active, the heating output is blocked at start up for 60 minutes (configurable time).
Table 4-36 Settings and configuration for Free cooling
Feature
Select free cooling
Select sensors
Pretreatment during free cooling
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Temperature control
Free cooling (Yes/No)
Configuration ► Functions ►
Pretreatment
Pretreatment during free cooling (Yes/No)
Note
64 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-36 Settings and configuration for Free cooling (continued)
Feature
Free cooling indication (DO)
Running and stopping depending on outdoor temperature
Stop depending on room temperature
Free cooling start time
Time to block heat output after free cooling
Fan-kick temperature check
Fan-kick interval time
Menu path in Application tool Variable
Configuration ► Digital outputs
► Free cooling indication
✓
✓
NC (Normally closed)
NO (Normally open)
Ventilation ► Demand control
► Free cooling
✓ Running when day outdoor temperature > (°C)
✓ Stop when night outdoor temperature > (°C)
✓ Stop when night outdoor temperature <(°C)
Ventilation ► Demand control
► Free cooling
Ventilation ► Demand control
► Free cooling
Stop when room temperature <
(°C)
Ventilation ► Demand control
► Free cooling
✓ Free cooling start hour (h)
✓ Free cooling stop hour (h)
Time to block heat output after free cooling (min)
Fan-kick temperature check (s) Ventilation ► Demand control
► Free cooling
Ventilation ► Demand control
► Free cooling
Fan-kick interval time (min)
Note
Table 4-37 Inputs and outputs for free cooling
Inputs and outputs
AI
AI
DO
Outdoor temperature sensor or Intake temperature
Room sensor or Extract air sensor
Free cooling operation
4.3.10 Cooling recovery
If the cooling recovery has been configured, there is a cooling requirement and the extract air temperature is a settable amount lower than the outdoor temperature, cooling recovery can be activated. When cooling recovery is activated the heat exchanger and damper sequence output signal will be activated in the cooling demand.
Table 4-38 Settings and configuration for Cooling recovery
Feature
Select cooling recovery
Menu path in Application tool Variable
Configuration ► Functions ►
Temperature control
Cooling recovery mode (On /
Off)
Note
Table 4-39 Inputs and outputs for cooling recovery
Inputs and outputs
AI
AI
Outdoor temperature sensor/Intake temperature sensor
Extract air sensor/Room temperature sensor
4.3.11 Enthalpy control
Calculating the enthalpy means to calculate the energy content of the air, taking into consideration both the temperature and the air humidity. The value is given in energy per kilogram air (kJ/kg). If enthalpy control is configured, enthalpy is calculated both outdoors and for the extract air. Enthalpy control is turned on in the configuration of a sequence ( Configuration ► Functions ► Sequence x ► Enable enthalpy control ). If the enthalpy
Corrigo manual, Rev. D 65 (196)
Information for the specialist - Function descriptions
is higher outdoors than in the extract air, the recirculation damper function (if enthalpy control is configured for the sequence) will be overridden to increase the recirculation. The function is not active when using free cooling, in which case outdoor air is used for cooling the room instead.
If both outdoor sensor and intake sensor are configured it uses the intake sensor. In order for the enthalpy calculation to be made the functions Enable enthalpy control (Configuration ► Functions ► Sequence) and
Cooling recovery mode must be active, and four sensors are required:
Table 4-40 Settings and configuration for Enthalpy control
Feature
Select enthalpy control
Menu path in Application tool Variable
Configuration ► Functions ►
Sequence X
Enable enthalpy control
Select cooling recovery mode Configuration ► Functions ►
Temperature control
Cooling recovery mode (On /
Off)
Note
Table 4-41 Inputs and outputs for enthalpy control
Inputs and outputs
AI
AI
AI
AI
Outdoor temperature sensor / Intake temperature sensor
Outdoor humidity sensor
Room / Extract air temperature sensor
Room humidity sensor
4.3.12 Heat exchanger efficiency monitoring
The function calculates the heat exchanger temperature efficiency in percent when the output signal to the first exchanger sequence is higher than 5 % (settable) and the extract air/efficiency temperature is 2°C
(settable) higher than the outdoor temperature ( Configuration ► Functions ► Temperature control ► Min temperature difference to show efficiency and Min output exchanger to show efficiency ).
When the control signal is lower than 5 % or the outdoor temperature is higher than 10°C the display will show 0 %.
If an intake sensor is configured it will use that for the outdoor temperature.
The heat exchanger efficiency is calculated using the following formula:
Option 1: Efficiency = (Efficiency temp - Outdoor temp ) / (Extract air temp - Outdoor temp ) * 100
Option 2: Efficiency = (Extract air temp - Exhaust air temp) / (Extract air temp - Outdor temp ) * 100
Alarm
An alarm is activated if the efficiency falls below the set alarm level (50 %). The alarm limit (trigger value) can be changed in Alarm status ► 65 Low efficiency exchanger ► Edit ► Alarm trigger value .
heater. It will then replace the exhaust air temperature sensor.
66 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-42 Settings and configuration for Heat exchanger efficiency monitoring
Feature
Actual efficiency value
Analog input
Menu path in Application tool Variable
Ventilation ► Actual / Setpoint
► Exchanger
Configuration ► Analog inputs
► Efficiency temperature exchanger
✓
✓
✓
Sensor type
Min/Max input (V)
Min/Max signal (°C)
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Efficiency presentation (Yes/No) Select efficiency presentation Configuration ► Functions ►
Temperature control
Minimum temperature difference to show efficiency
Configuration ► Functions ►
Temperature control
Min temperature difference to show efficiency (°C)
Note
Table 4-43 Inputs and outputs for heat exchanger efficiency monitoring
Inputs and outputs
AI
AI
AI
AI
Outdoor temperature sensor / Intake temperature sensor
Extract air sensor
Exhaust air sensor
Efficiency temperature sensor
4.3.13 External setpoint
An external setpoint device, e.g. Regin's TBI-PT1000 or TG-R4/PT1000 can be connected. The unit is connected to the analog input signal External setpoint temperature .
Table 4-44
Feature
Select external setpoint device
Menu path in Application tool Variable
Configuration ► Functions ►
Temperature control
External setpoint device
Analog input Configuration ► Analog inputs
► External setpoint temperature
Note
Table 4-45 Inputs and outputs for External setpoint
Inputs and outputs
AI External setpoint temperature
4.3.14 Recirculation
Recirculation is a function for distributing the air in the room using the supply air fan. The function can be used even when there is no heating or cooling demand. When using recirculation control, the extract air fan stops (but can also be set to run) and a recirculation damper opens which allows the air to circulate through the unit.
Recirculation is activated either via a digital input signal or by connecting it to Extra time channel 4
(Application tool ► Time control). If a timer output for Low/Normal/High speed is activated during recirculation via Extra time channel 4 , Low/Normal/High speed gets priority. If a timer output for Low/
Normal/High speed is activated during recirculation activated by a digital input, recirculation gets priority.
Corrigo manual, Rev. D 67 (196)
Information for the specialist - Function descriptions
Either a digital output ( Recirculation damper ) or an analog output sequence A to J can be used as an on/off output signal.
Recirculation control can be configured as either air circulation ( temperature control inactive ) or air circulation with temperature control. (Only heating, only cooling or both heating and cooling). Recirculation control has its own setpoint. However, the other settings are the same as for normal operation, i. e. if normal operation has been configured as room control, room control will also be used during recirculation.
The recirculation setpoint can be configured as constant or offset. Constant means that the recirculation setpoint will be used. Offset is based on an offset from the supply air setpoint.
To lower the temperature, it is possible to configure free cooling to be used during recirculation, if the conditions for free cooling are fulfilled, see
. Then, when the recirculation damper closes, the supply and extract air dampers open and the extract air fan starts. The supply air fan also starts, if it is not already running. If the free cooling function is not configured for recirculation control and you want to cool down the supply air via a low recirculation setpoint, the cooling battery will be used.
A max. room temperature can be configured for recirculation control under Ventilation ► Demand control ►
Recirculation . If the room temperature rises above the set value, recirculation will be stopped. When the room temperature has fallen 1 K below the set max limit, recirculation will start again if the start conditions are still fulfilled.
When running frequency controlled fans and using recirculation control you can, depending on the type of fan control, configure a special pressure/flow offset for the setpoint or a manual output signal for the supply air fan ( Ventilation ► Fan control ► Fans ► Offset ... fan when recirculation) .
It’s also possible to configure the output value when recirculation is active for each sequence. The sequence output can be configured to 0%, 100% or modulating 0-100%.
Table 4-46 Settings and configuration for recirculation
Feature
Select recirculation
Select sequence output when recirculation
Setpoint recirculation temperature
Temperature for change to outdoor air
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Sequence X
Ventilation ► Demand control
► Recirculation
Ventilation ► Demand control
► Recirculation
Recirculation (Yes/No)
Sequence output when recirculation/support (Auto, 0%, 100%)
Setpoint recirculation (°C)
Change to outdoor air when room air > (°C)
Recirculation air damper control Configuration ► Digital outputs
► Recirculation air damper
✓ NC (Normally closed)
✓ NO (Normally open)
Note
4.3.15 Extra temperature sensor
The input signals Extra sensor 1 , Extra sensor 2 , ..., Extra sensor 5 , can be used to add extra temperature sensors for supervision of temperatures that are not related to any control functions. Each sensor has three alarms tied to it: High temperature, Low temperature and Sensor error.
68 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-47 Settings and configuration for extra temperature sensor
Feature Menu path in Application tool Variable
Select extra sensors and inputs Configuration ► Functions ►
Extra sensors & inputs
✓
✓
Alarm acknowledgement
Extra sensors
✓ Extra alarm
Analog inputs Configuration ► Analog inputs
► Extra sensor X
✓ Sensor type
✓ Filter factor
✓ Compensation
✓ Mode
✓ Manual
Title extra sensor X Change name of extra sensor Configuration ► Analog inputs
► Extra sensor
Extra alarm Configuration ► Digital inputs
► Extra alarm X
✓
✓
NC (Normally closed)
NO ( Normally open)
Manual / Auto (On, Off, Auto)
Note
Corrigo manual, Rev. D 69 (196)
Information for the specialist - Function descriptions
4.4 Fan control
4.4.1
General
The variable speed of the fan is controlled via a frequency converter.
Variable speed control uses an analog output per fan or Modbus communication for controlling a frequency converter. There is one setpoint for each fan for normal, low and high speed. Pressure or air flow control can be used, the offset is in the configured unit (pressure/flow/percent).
Variable speed fans can also be configured to be run with fixed output values (0-100%).
Timer outputs
The fans are normally controlled by the timer channels for slow, normal and high speed but can also be started via a digital input or communication.
Slow, normal and high speed
The units will always start directly with the desired speed.
The extract air fan and the supply air fan have individual start and stop delays which are normally set so that the extract air fan is started before the supply air fan. If there are not enough digital outputs for individual control, both fans will have to be started using the signal for the supply air fan, and the delay will be created using an external time relay.
Speed limits
For both supply air and extract air fans the max and min speed limit will be applied to the output. If the user sets the speed value manually or if the ventilation system stops, this will override the set fan speed limits.
Fan control types
There are different types of fan control. The control type is selected in Application tool ► Configuration ►
Functions ► Function activation ► Fan control type. See
below for a description of the different types.
Table 4-48 Fan control types
Pressure
Flow
Control of the fan speed using pressure transmitters.
Instead of giving a pressure setpoint value, it is possible to use an airflow volume value in m 3 /h. The value from the pressure transmitter is recalculated to a volume flow and the fans will be controlled to give a constant flow.
Manual
External
Use the manual setting if you want to manually set the speed of the fan
Use the external setting if you have an external device that controls the fan speed, e.g. 0…10 V device.
Supply air pressure and extract air fan slave The speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan does not have a pressure transmitter, instead you let the output for the extract air fan follow the control signal for the supply air fan. A scaling factor can be added if the characteristics of the extract air fan are not the same as the characteristics of the supply air fan. (Only pressure control of the supply air fan is possible using this function.)
Supply air pressure with extract air flow slave The speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan is controlled by the supply air flow, in order to achieve a balanced ventilation. A pressure transmitter which is placed in the supply air fan cone ("SAF flow") gives a measured value of the present supply air flow. A corresponding pressure transmitter is placed in the extract air fan cone and gives a measured value of the extract air flow.
The supply air flow is the setpoint used for control of the extract air fan. A scaling factor can be added if the extract air fan does not have the same characteristics as the supply air fan.
70 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-48 Fan control types (continued)
Extract air pressure with supply air fan slave The speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan has no pressure transmitter.
Instead, the supply air fan output is made to follow the extract air fan control signal. A scaling factor can be added if the supply air fan characteristics are not the same as the characteristics of the extract air fan (only pressure control of the extract air fan is possible using this function).
Extract air fan pressure with supply air flow slave
The speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan is controlled by the extract air duct flow in order to achieve a balanced ventilation. A pressure transmitter placed in the extract air fan cone (“EAF flow”) provides a measurement of the current extract air flow. A corresponding pressure transmitter is placed in the supply air fan cone, providing a measurement of the supply air flow.
The supply air fan is controlled using the extract air flow as a setpoint. A scaling factor can be added if the supply air fan does not have the same characteristics as the extract air fan.
Frequency converters
There is support for the following frequency converters and/or EC controllers:
✓ Vacon NXL
✓ Lenze
✓ Omron V1000
✓ Emerson Commander
✓ LS
✓ EBM
✓ Danfoss FC 101
✓ ABB ACS
✓ EC Blue
Read more about the frequency converters in
Appendix F Frequency converters and EC controllers for heat exchangers
Compensation curve
When running pressure/flow control or manual frequency control, it is possible to for the pressure/flow or output to be compensated. By using compensation, the fan can be run at low speed more of the time. The fan speed will increase only when necessary, thus saving energy.
This compensation can be made depending on any analog input such as supply air, extract air, room, outdoor temperature, humidity, CO
2 etc. There are three equal compensation functions.
It is possible to compensate either one or both fans at the same time. It is possible to set which fan that should be compensated, the supply or extract air fan.
There are three compensation functions called Fan compensation curve 1…3 which can be used to set a compensation based on the configured analog input signal (temperature, pressure, flow humidity, CO
2
). The curve has three parameter pairs which correspond to the value of the compensation at three different temperatures.
The compensation can be selected to apply to both fans or one fan, to low, normal, high or all speeds or only when defrosting.
When configuring in Application tool, you select the following settings for the compensation curve:
Corrigo manual, Rev. D 71 (196)
Information for the specialist - Function descriptions
Table 4-49 Settings and configuration for fan compensation curve 1, 2, 3
Feature Menu path inApplication tool Options
Fan level, compensation curve Configuration ► Functions ►
Fan compensation curve 1/2/3
► Fan level
✓ All levels
✓ Low speed
✓ Normal speed
✓ High speed
✓ Low + Normal speed
✓ Normal + High speed
Compensation mode Configuration ► Functions ►
Fan compensation curve 1/2/3
✓ Inactive
✓ In all modes
✓ When defrosting
Fan type to compensate Configuration ► Functions ►
Fan compensation curve 1/2/3
Sensor used in compensation Configuration ► Functions ►
Fan compensation curve 1/2/3
✓ Supply air fan + extract air fan
✓ Supply air fan
✓ Extract air fan
✓ Outdoor temperature
✓ Intake air temperature
✓ Supply air temperature
✓ Exhaust air temperature
✓ Extract air temperature
✓ Room temperature 1…10
✓ etc.
Note
Setpoints for fan compensation
The setpoints for the compensation curves are in the Ventilation section in Application tool.
In
Figure 4-12 Example of fan compensation curve
below is an example of how to compensate the fan depending on the outdoor temperature. The speed of the fan increases at low and high outdoor temperatures. The output of the compensation curve is added to the setpoint of the fan ( Ventilation ► Fan control ► Supply air fan/Extract air fan ► Actual setpoint compensation ).
Outdoor temperature
Figure 4-12 Example of fan compensation curve
Feature
Select fan speed compensated temperature setpoint
Lower/Middle/Higher point X
Lower/Middle/Higher point Y
Menu path in Application tool Variable
Configuration ► Functions ►
Temperature control
Fan speed compensated temperature setpoint
Description
✓ None
✓ Low
✓ High
✓ Low + High
Points on the X-axis Ventilation ► Fan control ►
Fan compensation curve 1/2/3
Ventilation ► Fan control ►
Fan compensation curve 1/2/3
Lower/Middle/Higher point X
Lower/Middle/Higher point Y The Y-axis can be in Pa, % or m 3 /h depending on the fan control type.
72 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Timer outputs
The fans are normally controlled by the timer channels for low, normal and high speed but can also be started via digital input or communication. (Application tool ► Time control)
Fan levels
A frequency controlled fan is the only type of fan that works with the Corrigo. The fan can be set to Low,
Normal or High speed. The selection of the fan speed defines which IOs and time channels will be active in the application.
The fans will always start directly with the desired speed.
There are four different fan speed levels to choose from in Application tool:
✓ Normal
✓ Low - Normal
✓ Normal - High
✓ Low - Normal - High
Variable speed control uses an analogue output per fan or Modbus communication for controlling a frequency converter.
For more information about frequency converters, see
Appendix F Frequency converters and EC controllers for heat exchangers
The fans are normally controlled by the timer channels for slow, normal and high speed but can also be started via digital input or communication.
The extract air fan and the supply air fan have individual start and stop delays which are normally set so that the extract air fan is started before the supply air fan. If there are not enough digital outputs for individual control, both fans will have to be started using the signal for the supply air fan, and the delay will be created using an external time relay.
Application tool menu path for fan control
Feature
Fan control type
Fan levels
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Function activation
Fan control type
Fan levels
Select fan
Select flow presentation
Fan indication
Extract air fan slaved by exchanger supply air flow
Note
✓ Normal
✓ Low-Normal
✓ Normal-High
✓ Low-Normal-High
Configuration ► Functions ►
Fan control
Configuration ► Functions ►
Fan control
Configuration ► Functions ►
Fan control
✓ Supply air + Extract air
✓ Supply air
✓ Extract air
Flow presentation
Supply/ Extract air fan indication
Configuration ► Functions ►
Fan control
Extract air fan slaved by exchanger supply air flow (Yes/
No)
✓ Yes
✓ No
✓ None
✓ Alarm
✓ Run indication
Corrigo manual, Rev. D 73 (196)
Information for the specialist - Function descriptions
Feature
K-factor
X-factor
Setpoint, external flow
Analog inputs flow supply air
Analog inputs flow extract air
Menu path in Application tool Variable
Configuration ► Functions ►
Fan control
✓ Flow calculation supply air Kfactor
✓ Flow calculation extract air
K-factor
✓ Flow calculation exchanger supply air K-factor
✓ Flow calculation exchanger extract air K-factor
Note
Configuration ► Functions ►
Fan control
✓ Flow calculation supply air Xfactor
✓ Flow calculation extract air
X-factor
✓ Flow calculation exchanger supply air X-factor
✓ Flow calculation exchanger extract air X-factor
External flow setpoint (Yes/No) Configuration ► Functions ►
Fan control
Configuration ► Analog inputs
► Flow supply air
✓ Sensor type
✓ Min/Max input (V)
✓ Min/Max signal (m 3 /h)
✓ Filter factor
✓ Compensation (m 3 /h)
✓ Mode
✓ Manual (m 3 /h)
Configuration ► Analog inputs
► Flow extract air
✓ Sensor type
✓ Min/Max input (V)
✓ Min/Max signal (m 3 /h)
✓ Filter factor
✓ Compensation (m 3 /h)
✓ Mode
✓ Manual (m 3 /h)
Analog inputs flow exchanger supply air
Configuration ► Analog inputs
► Flow exchanger supply air
✓ Sensor type
✓ Min/Max input (V)
✓ Min/Max signal (m 3 /h)
✓ Filter factor
✓ Compensation (m 3 /h)
✓ Mode
✓ Manual (m 3 /h)
Feedback Supply/Extract air fan Configuration ► Digital inputs
► Feedback supply/extract air fan
✓ NC (Normally closed)
✓ NO (Normally Open
Mode (On/Off/Auto)
Analog output Supply / Extract fan
Configuration ► Analog outputs
► Supply / Extract air fan
Range output:
✓ 0-10V
✓ 2-10 V
✓ 10-2 V
✓ 10-0 V
Actual values Supply/Extract air fan
Ventilation ► Actual/Setpoint ►
Supply air fan / Extract air fan
✓ Pressure supply / extract air
✓ Flow supply / extract air
✓ Actual setpoint compensation
✓ Actual setpoint
✓ Output signal
✓ Bus values SAF 1…5
Frequency (from frequency converter)
✓ Current (from frequency converter)
✓ Power (from frequency converter)
✓ Error (from frequency converter)
74 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Feature
Setpoints for fans
Menu path in Application tool Variable
Ventilation ► Fan control ►
Fans
✓ Setpoint low/normal/high speed supply air fan (%, Pa, m 3 /h)
✓ Setpoint low/normal/high speed extract air fan (%, Pa, m 3 /h)
✓ Flow supply/extract air (m 3 /h)
✓ Slave factor
✓ Offset supply/extract air when free cooling (%, Pa, m 3 /h)
✓ Offset supply/extract air when recirculation (%, Pa, m 3 /h)
Note
Setpoint supply/extract air fan Ventilation ► Fan control ►
Supply air fan/Extract air fan
✓ Start/stop delay
✓ Outdoor air damper stop delay
✓ Min pressure for supply/ extract air fan indication
✓ Min flow for supply/extract air fan indication
✓ SAF speed min/max limit (%)
✓ EAF speed min/max limit (%)
4.4.2
Fan control types
Pressure
During pressure control, two separate analog output signals are used for supply and extract air and two separate analogue input signals for supply and extract air for pressure transmitters. The fan speeds are controlled via frequency converters, thereby maintaining constant pressure. The pressure transmitter inputs are scalable using Min input (V) and Max input (V).
A digital output signal is normally used for each fan ( Supply air fan start/step 1 and Extract air fan start/step 1 ) for sending a start signal to the frequency converters. The start signal is activated as long as the fan is expected to be running and the control signal is > 0%.
For the supply and extract air fans, there is one individually settable value for normal speed, for low and high speed. Changing between the speed setpoint values is done using the timer channels or using digital input signals ( Extended Operation low/normal/high speed ).
Settings and configuration for Pressure control
Feature
Select pressure control
Fan levels
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Function activation
Fan control type
Fan levels
Note
✓ Normal
✓ Low-Normal
✓ Normal-High
✓ Low-Normal-High
Select fan
Analog inputs pressure supply air
Configuration ► Functions ►
Fan control
Configuration ► Analog inputs
► Pressure supply air
✓ Supply air + Extract air
✓ Supply air
✓ Extract air
✓ Sensor type
✓ Min/Max input (V)
✓ Min/Max signal (Pa)
✓ Filter factor
✓ Compensation (Pa)
✓ Mode
✓ Manual (Pa)
Corrigo manual, Rev. D 75 (196)
Information for the specialist - Function descriptions
Feature
Analog inputs pressure extract air
Menu path in Application tool Variable
Configuration ► Analog inputs
► Pressure extract air
✓
✓
Sensor type
Min/Max input (V)
✓ Min/Max signal (Pa)
✓ Filter factor
✓ Compensation (Pa)
✓ Mode
✓ Manual (Pa)
Feedback Supply/Extract air fan Configuration ► Digital inputs
► Feedback supply/extract air fan
✓ NC (Normally closed)
✓ NO (Normally Open
Mode (On/Off/Auto)
Analog output Supply / Extract fan
Configuration ► Analog outputs
► Supply / Extract air fan
Range output:
✓ 0-10V
✓ 2-10 V
✓ 10-2 V
✓ 10-0 V
Actual values Supply/Extract air fan
Ventilation ► Actual/Setpoint ►
Supply air fan / Extract air fan
✓ Pressure supply / extract air
✓ Flow supply / extract air
✓ Actual setpoint compensation
✓ Output signal
✓ Bus values SAF 1…5
Frequency (from frequency converter)
✓ Current (from frequency converter)
✓ Power (from frequency converter)
✓ Error (from frequency converter)
Setpoints for fans Ventilation ► Fan control ►
Fans
Note
✓ Setpoint low/normal/high speed supply air fan (%, Pa, m 3 /h)
✓ Setpoint low/normal/high speed extract air fan (%, Pa, m 3 /h)
✓ Flow supply/extract air (m 3 /h)
✓ Slave factor
✓ Offset supply/extract air when free cooling (%, Pa, m 3 /h)
✓ Offset supply/extract air when recirculation (%, Pa, m 3 /h)
Setpoint supply/extract air fan Ventilation ► Fan control ►
Supply air fan / Extract air fan
✓ Start/stop delay
✓ Outdoor air damper stop delay
✓ Min pressure for supply/ extract air fan indication
✓ Min flow for supply/extract air fan indication
Flow
Instead of giving a pressure setpoint value, it is possible to use an airflow volume value in m 3 /h. The value from the pressure transmitter is recalculated to a volume flow using the formula below and the fans will be controlled to give a constant flow.
Flow = K * ΔP X
K and X are settable constants depending on the fan size.
Δ P is the differential pressure over the fan in Pa.
Each fan has its own set of parameters.
X is normally 0.5 indicating that the flow is proportional to the square root of the differential pressure.
76 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-50 Settings for K- and X-factor
Feature
K-factor
X-factor
Menu path in Application tool Variable
Configuration ► Functions ►
Fan control
✓ Flow calculation supply air Kfactor
✓ Flow calculation extract air
K-factor
✓ Flow calculation exchanger supply air K-factor
✓ Flow calculation exchanger extract air K-factor
Description
Configuration ► Functions ►
Fan control
✓ Flow calculation supply air Xfactor
✓ Flow calculation extract air
X-factor
✓ Flow calculation exchanger supply air X-factor
✓ Flow calculation exchanger extract air X-factor
Manual
Manual control of the fan is set in Ventilation ► Manual/Auto .
Frequency controlled fans can be controlled at a fixed rotational speed. The rotational speed is selected by setting a fixed output signal (0 – 100%). There is one individual setpoint value for normal speed, for low speed and high speed.
Fans that are run with a fixed output signal can also be compensated (see the section above). In this mode, pressure sensors are not needed.
External
This signal can be used to control the SAF and EAF flow setpoints from an external VAV system if the
”Frequency control external” fan type is used.
If this signal is configured as an analog input signal, the flow setpoint for the SAF and EAF will be controlled in normal speed.
The signal can be configured by using scaling: Min volt input (Vmin)/Min flow and Max volt input (Vmax)/
Max flow. The configuration is done in Configuration ► Analog inputs ► External control supply air fan and
External control extract air fan
Supply air pressure and extract air fan slave
The rotational speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan does not have a pressure transmitter, instead you let the output for the extract air fan follow the control signal for the supply air fan. A scaling factor can be added if the characteristics of the extract air fan are not the same as the characteristics of the supply air fan.
The extract air fan will start directly at 50% after the start delay. Then the heating of the exchanger will work for this operating mode as well. When the supply air fan starts, the extract air fan will be slave controlled by the supply air flow.
Corrigo manual, Rev. D 77 (196)
Information for the specialist - Function descriptions
Supply air pressure with extract air flow slave
The rotational speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan is controlled by the supply air flow, in order to achieve a balanced ventilation. A pressure transmitter which is placed in the supply air fan cone ( SAF flow ) gives a measured value of the present supply air flow. A corresponding pressure transmitter is placed in the extract air fan cone and gives a measured value of the extract air flow.
The supply air flow is the setpoint used for control of the extract air fan. A scaling factor can be added if the extract air fan does not have the same characteristics as the supply air fan. The scaling factor is found in
Ventilation ► Fan control ► Slave factor
Extract air pressure with supply air fan slave
The rotational speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan has no pressure transmitter. Instead, the supply air fan output is made to follow the extract air fan control signal. A scaling factor can be added if the supply air fan characteristics are not the same as the characteristics of the extract air fan (only pressure control of the extract air fan is possible using this function). The scaling factor is found in Ventilation ► Fan control ► Slave factor .
Extract air fan pressure with supply air flow slave
The rotational speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan is controlled by the extract air duct flow in order to achieve a balanced ventilation. A pressure transmitter placed in the extract air fan cone ( EAF flow ) provides a measurement of the current extract air flow. A corresponding pressure transmitter is placed in the supply air fan cone, providing a measurement of the supply air flow.
The supply air fan is controlled using the extract air flow as a setpoint. A scaling factor can be added if the supply air fan does not have the same characteristics as the extract air fan. The scaling factor is found in
Ventilation ► Fan control ► Slave factor
Step controlled fans
It is possible to control the speed of the fans via digital outputs if the type of fan control is set to Manual or
External ( Configuration ► Functions ► Function activation ► Fan control type ).
Fans with up to 3 speeds can be controlled by this function ( Configuration ► Functions ► Fan control ► Step control of fans) . The function converts the control signal of the fan to start/stop signals for the step outputs.
Switch points and hysteresis are settable parameters ( Configuration ► Functions ► Fan control ► Switch point step 1-2 SAF / 2-3 SAF / 1-2 EAF / 2-3 EAF (%), Hysteresis (% )). The switch between the steps of the fans is delayed by a timer Speed change delay (s) (FS = 10s) ( Ventilation ► Fan control ► Supply air fan/Extract air fan ). When increasing the speed, the fan must run at the lower speed for the set delay time before the next higher speed is activated. If the speed is reduced, the output of the higher stage is switched off and the lower stage is switched on after the delay time has expired. Only the output of the selected speed is active.
Table 4-51 Settings and configuration for step control of fans
Feature
Select Fan control type
Step control of fans
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Fan control type
Configuration ► Functions ►
Fan control
Step control of fans
Note
✓ Manual
✓ External
✓ No
✓ 1 step
✓ 2 steps
✓ 3 steps
Switch points Configuration ► Functions ►
Fan control
Switch point x
78 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-51 Settings and configuration for step control of fans (continued)
Feature
Hysteresis
Digital outputs
Delay time
Delay time
Menu path in Application tool Variable
Configuration ► Functions ►
Fan control
Hysteresis
Configuration ► Digital outputs ✓ Supply air fan start/step1
✓ Supply air fan step 2
✓ Supply air fan step 3
✓ Extract air fan start/step 1
✓ Extract air fan step 2
✓ Extract air fan step 3
Speed change delay Ventilation ► Fan control ►
Supply air fan
Ventilation ► Fan control ►
Extract air fan
Speed change delay
Note
Kitchen function
Kitchen function is an additional function for external controlled fans; Fan control type = External . The function will stop the unit if the external control signal is lower than a settable limit. A potentiometer which is connected to an analog input can start and stop the air handling unit in addition to control the speed of the fans.
The following settings need to be done to get the function activated:
✓ Fan control type = External ( Configuration ► Functions ► Function activation ► Fan control type )
✓ Kitchen function = Yes ( Configuration ► Functions ► Fan control ► Kitchen function )
✓ Analog input: External control supply air fan and External control extract fan ( Configuration ► Analog inputs ) configured to the same physical input
Different speeds of the fans can be achieved by differently adjusted curves for the two analog inputs. ( Configuration ► Analog inputs ► External control xxx fan ► Min/Max input (V), Min/Max signal(%) ).
The unit will stop if the voltage at the input External control supply air fan falls below the Min input (V). It starts again if the signal rises above the Min input (V) + a fix hysteresis of 0,1V.
Table 4-52 Settings and configuration for kitchen function
Feature
Select Fan control type
Kitchen function
Analog inputs
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Fan control
Fan control type
Kitchen function
Configuration ► Analog inputs ✓ External control supply air fan
✓ External control extract air fan
Note
External
✓ No
✓ Yes
4.4.3
Demand controlled ventilation
In applications with varying occupancy the fan speeds or mixing dampers can be controlled by the air quality as measured by a CO
2 sensor.
With the CO
2 function it’s possible to start and stop the fans, compensate the fan speed and in combination with mixing damper let in more outdoor air depending on the CO
2 value.
When the function is activated with start/stop function and the CO
2 value rises above a settable start value
(default: 800 ppm) the fans will start at configured speed (default: normal speed), if they are not already running. Should the CO
2 value continue to rise, the fan speed can increase if compensation with CO
2 value
Corrigo manual, Rev. D 79 (196)
Information for the specialist - Function descriptions
is configured (See function Fan compensation curve 1 in Application tool ). The fans will stop when the CO
2 value falls a settable hysteresis (default: 160 ppm) below the start value.
If demand controlled ventilation is activated in combination with mixing dampers and the CO
2
-value rises above the setpoint value, the dampers controlled by a sequence with CO
2 function will be overtaken by the
CO
2 controller and let in more outdoor air. The function is controlled by a PI-controller.
The function has a settable minimum running time.
Application tool menu paths for Demand control
Table 4-53 Settings and configuration for Demand control
Feature
Select type of CO
2
CO
CO
2
2 control control in sequence control mode
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
CO2 control:
✓ No
✓ Fan start/stop function
✓ Mixing damper function
✓ Fan start/stop + Mixing damper
Configuration ► Functions ►
Sequence X
Configuration ► Functions ►
Sequence X
CO2 control (No/CO2
Sequence 1, 2)
CO2 control mode (Increasing/
Decreasing)
Analog input CO2 room/Extract air
Setpoints CO
PID settings
2 control
Configuration ► Analog inputs
► CO2 room/extract air
✓ Sensor type
✓ Min/Max input (V)
✓ Min/Max signal (ppm)
✓ Filter factor
✓ Compensation (ppm)
✓ Mode
✓ Manual (ppm)
Ventilation ► Demand control
► CO2
✓ Setpoint mixing damper
(ppm)
✓ Start limit fan start/stop
(ppm)
✓ Stop hysteresis fan start/stop
(ppm)
✓ Min time for CO2 control
(min)
Ventilation ► PID controllers ►
CO2
✓ P-band (ppm)
✓ I-time (s)
✓ D-time (s)
Note
Inputs and outputs for Demand control
Inputs and Outputs
AI CO
2 sensors
4.4.4
Extra fan motor control
External control of two external fan motors can be configured. The fans are started via either a digital input, extra time channel 4 or when the unit is started.
A digital output activates the fan motor. A digital input is available for run indication / motor protection.
80 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-54 Settings and configuration for Extra fan motor control
Feature Menu path inApplication tool Variable
Select Extra fan motor control Configuration ► Functions ►
Function activation
Extra fan motor control (No, 1,
2)
Feedback and start/stop of extra fan motor
Configuration ► Functions ►
Extra fan motor control
✓ Type of feedback fan motor
1, 2 (None, Alarm, Run
Indication)
✓ Start/stop function fan motor
1, 2 (Digital input, Unit running, Extra time channel
4)
Note
Digital input Start/Stop extra fan motor
Digital input Feedback extra fan motor 1, 2
Configuration ► Digital inputs
► Start/(Stop) extra fan motor
1, 2
Configuration ► Digital inputs
► Feedback extra fan motor 1,
2
Digital output extra fan motor 1,
2 start
Configuration ► Digital outputs
► Extra fan motor 1, 2 start
✓ NC (Normally closed)
✓ NO (Normally open)
Manual / Auto
✓ NC (Normally closed)
✓ NO (Normally open)
Manual / Auto
✓ NC (Normally closed)
✓ NO (Normally open)
Extra time channel 4 Time control ►Extra time channel 4
Table 4-55 Inputs and outputs extra fan motor control
Motor control 1
DI
DI
DO
Motor control 2
DI
DI
DO
Start/(Stop) extra fan motor
Feedback extra fan motor
Extra fan motor start
4.5 Pump control
Digital inputs and outputs can be configured for pump control.
All the pumps can use run indication with malfunction alarm, or an alarm input connected to a motor protection or similar.
4.5.1
Heating circuit, water heating
The circulation pump for the heating sequence will always run when the outdoor temperature is lower than a settable value (FS +10°C) ( Ventilation ► Temperature control ► Sequence x ► Pump running when temperature
< (°C) ). At higher outdoor temperatures the pump will run when the sequence output signal is larger than 0
V.
If no outdoor temperature sensor has been configured, the stop temperature can be set to 0°C. Then the pump will only run on heat demand.
The pump has a settable stop delay.
The pump will be exercised once daily at a settable time (FS: 15:00 / 3 p.m.) for one minute or the set shortest running time, whichever is the longest.
4.5.2
Exchanger circuit, liquid connected exchangers
The circulation pump for the exchanger sequence will run when the sequence output signal is larger than 0
V.
Corrigo manual, Rev. D 81 (196)
Information for the specialist - Function descriptions
The pump has a settable, shortest running time.
The pump will be exercised once daily at a settable time (FS: 15:00 / 3 p.m.) for 1 minute, or the set stop delay, whichever is the longest.
4.5.3
Cooling circuit
The circulation pump for the cooling sequence will run when the sequence output signal is larger than 0 V.
The pump has a settable, shortest running time.
The pump will be exercised once daily at a settable time (FS: 3 p.m.) for 1 minute, or the set stop delay, whichever is the longest.
4.5.4
Settings and configuration in Application tool for pump control
Table 4-56 Settings and configuration for pump control
Feature
Select pump control
Pump stop mode
Type of pump indication
Digital output
Setpoints pump
Menu path in Application tool Variable
Configuration ► Functions ►
Sequence A to J
Configuration ► Functions ►
Sequence A to J
Pump control (Yes / No)
Pump stop mode (Auto / Always running)
Note
Configuration ► Functions ►
Sequence A to J
Type of pump indication (None /
Alarm / Run indication)
Configuration ► Digital outputs
► Sequence A to J pump
✓ NC (Normally closed)
✓ NO (Normally open)
Ventilation ► Temperature control ► Sequence A to J
✓ Pump stop delay (min)
✓ Pump-kick hour (h)
✓ Pump running when outdoor temperature < (°C)
✓ Hysteresis to allow pump stop (°C)
4.5.5
Inputs and outputs for pump control
Table 4-57 Inputs and outputs for pump control
Heating
AI
DO
DI
Exchanger
-
DO
DI
Cooling
-
DO
DI
Outdoor temperature sensor
Start / Stop circulation pump
Run indication / alarm, circulation pump
4.6 Damper control
4.6.1
Close-off dampers
The outdoor air and exhaust air ducts close-off dampers can be controlled by digital outputs or be hardwired to the supply air fan relays for normal, low and high speed so that the damper is open when the supply air fan is running. When using pressure controlled fans the digital activation signal is activated as soon as the fan has start conditions. This signal can be used to open the close-off damper.
Select damper type in Configuration ► Functions ► Function activation .
82 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
When the unit is stopped it’s possible to configure a delay time before the Outdoor air damper and Exhaust air damper is closing.
✓ Outdoor air damper close delay: 0-300 seconds (Default: 0 s) ( Ventilation ► Fan control ► Supply air fan ► Outdoor air damper stop delay (s) .)
✓ Exhaust air damper close delay: 0-300 seconds (Default: 0 s)( Ventilation ► Fan control ► Extract air fan
► Exhaust air damper stop delay (s) .)
Table 4-58 Settings and configuration of Close-off dampers
Feature
Select damper type
Digital output outdoor air damper
Digital output exhaust air damper
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Damper:
✓ None
✓ Outdoor
✓ Outdoor + Exhaust
✓ Exhaust
Configuration ► Digital outputs
► Outdoor air damper
✓
✓
NC (Normally closed)
NO (Normally open)
Configuration ► Digital outputs
► Exhaust air damper
✓ NC (Normally closed)
✓ NO (Normally open)
Note
4.6.2
Fire/smoke dampers
Fire dampers are normally configured to open on fire alarm but can be configured to be normally open instead.
Fire damper exercising
Fire damper exercising can be configured. The exercise interval is settable. To be able to use this function, all the dampers must have end-position switches.
The digital input Feedback fire damper should be wired to all the fire damper end position switches
( Configuration ► Digital inputs ► Feedback fire damper ).
90° i
...
3
2
1
E
Figure 4-13 Dampers
When the test cycle is initiated, the digital output Fire damper will be activated and the dampers will begin to move. Within the set time (90 s) the signal Feedback fire damper change to indicate that the dampers have left their normal positions. If not, an alarm will be triggered.
Then, within the set time, Feedback fire damper must change again to indicate that all the dampers have reached the other end position. If not, an alarm will be triggered.
Corrigo manual, Rev. D 83 (196)
Information for the specialist - Function descriptions
When all dampers have reached the end position the output Fire damper will be reset to drive the dampers back to normal position. Again, within the set time (90 s) the signal on the digital input Feedback fire damper must change to indicate that the dampers have left the end positions. If not an alarm will be triggered.
Then, within the set time, Feedback fire damper must change again to indicate that all the dampers are back to their normal positions. If not an alarm will be triggered.
The controller can be configured to stop the air handling unit during the damper testing at Configuration ►
Functions ► Fire/Smoke ► Fire damper test , where it's possible to select if the test will be when the unit is running or stopped.
All dampers must be wired to the same output in order to get correct results.
The fire alarm input can be configured as normally closed or normally open ( Configuration ► Digital inputs ►
Fire Alarm ).
Table 4-59 Settings and configuration of fire and/or smoke dampers
Feature
Select fire and/or smoke
Select operation mode when fire/smoke alarm
Supply air fan setpoint type when fire/smoke alarm
Manual setpoint supply air
Manual output supply air
Extract air fan setpoint type when fire/smoke alarm
Manual setpoint extract air
Manual output extract air
Outdoor air damper function when fire/smoke alarm
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Fire/Smoke
Configuration ► Functions ►
Fire/Smoke
Fire / Smoke:
✓ No
✓ Fire
✓ Smoke
✓ Fire + Smoke
Operation mode when fire/ smoke alarm:
✓ Stopped
✓ Continuous run
✓ Running via normal start/ stop conditions
✓ Supply air fan run
✓ Extract air fan run
Supply air fan setpoint type when fire/smoke alarm:
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Configuration ► Functions ►
Fire/Smoke
Configuration ► Functions ►
Fire/Smoke
Configuration ► Functions ►
Fire/Smoke
Manual setpoint (Pa, m
Manual output (%)
3 /h, %)
Supply air fan setpoint type when fire/smoke alarm:
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Manual setpoint (Pa, m 3 /h, %) Configuration ► Functions ►
Fire/Smoke
Configuration ► Functions ►
Fire/Smoke
Configuration ► Functions ►
Fire/Smoke
Manual output (%)
Outdoor air damper function when fire/smoke alarm:
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Note
84 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Table 4-59 Settings and configuration of fire and/or smoke dampers (continued)
Feature
Exhaust air damper function when fire/smoke alarm
Fire damper mode
Fire damper test
Digital input Feedback fire damper
Menu path in Application tool Variable
Configuration ► Functions ►
Fire/Smoke
Exhaust air damper function when fire/smoke alarm:
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Configuration ► Functions ►
Fire/Smoke
Configuration ► Functions ►
Fire/Smoke
Fire damper mode
✓ Not active
✓ Dampers normally closed
✓ Dampers normally opened
Fire damper test
✓ No test
✓ Test when unit running
✓ Test when unit stopped
Configuration ► Digital inputs
► Feedback fire damper
✓
✓
NC (Normally closed)
NO (Normally open)
Digital input Fire/Smoke alarm Configuration ► Digital inputs
► Fire/Smoke alarm
✓
✓
NC (Normally closed)
NO (Normally open)
Digital output fire damper
Sequence output when fire / smoke mode
Setpoints fire damper
Configuration ► Digital outputs
► Fire damper
✓ NC (Normally closed)
✓ NO (Normally open)
Configuration ► Functions ►
Sequence A to J
Ventilation ► Fire/Smoke ►
Fire/Smoke
Sequence output when fire / smoke mode
✓ Run time fire damper (s)
✓ Test interval fire damper (d)
✓ Test hour fire damper (h)
Note
4.6.3
Inputs and outputs for dampers
Inputs and Outputs
DO
DO
DO
DI
DI
DI
Outdoor air damper
Exhaust air damper
Fire damper
Fire alarm
Smoke alarm
Feedback fire alarm
4.7 Pretreatment
Control of dampers and pump for preheated or pre-cooled outdoor air via an underground intake channel.
The digital output Pretreatment is set to preheating when the unit is started and the outdoor temperature is below the set heating start limit (default 8°C) or to precooling when the outdoor temperature is above the set cooling start limit (default 19°C).
If the outdoor temperature exceeds the set heating start limit by more than 1°C, preheating will be stopped, as well as if the outdoor temperature falls below the cooling start limit by 1°C.
If a sensor is configured in the intake duct this temperature will be compared with the outdoor temperature.
If the temperature in the intake duct does not exceed the outdoor temperature by more than 1°C
(adjustable) 5 minutes (adjustable) after start-up when using preheating, preheating will be stopped. The same conditions apply to precooling, i.e. if the intake temperature is not more than 1°C (adjustable) cooler than the outdoor temperature, precooling will be stopped.
Corrigo manual, Rev. D 85 (196)
Information for the specialist - Function descriptions
Pretreatment always starts at start-up of the unit, if the outdoor temperature so permits. If pretreatment is stopped due to a small difference between the intake temperature and the outdoor temperature, pretreatment will be blocked for 6 hours. Then pretreatment will start (if the outdoor temperature so permits) and run for at least 5 minutes (adjustable)
Feature
Select pretreatment
Select if pretreatment activated during free cooling
Intake sensor configuration
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Pretreatment
Pretreatment (Yes/No)
Pretreatment activated during free cooling (Yes / No)
Digital output: Pretreatment start
Configuration ► Analog inputs
► Intake air temperature
Sensor type
Configuration ► Digital outputs
► Pretreatment start
✓ NC (Normally closed
✓ NO (Normally open)
Setpoints pretreatment Ventilation ► Temperature control ► Pretreatment
✓ Activate preheater when outdoor temperature < (°C)
✓ Activate precooler when outdoor temperature > (°C)
✓ Hysteresis (°C)
✓ Min difference between outdoor and intake air temperature (°C)
✓ Pretreatment block time if difference below min (h)
✓ Min run time (min)
Note
4.8 Humidity control
Humidity control can be configured as Humidification, Dehumidification or both Humidification and
Dehumidification.
Two humidity sensors can be connected, a room sensor for control and an optional duct sensor for maximum limiting. The limit sensor can be omitted.
The humidity control is handled by a PI-controller.
The humidity sensors must give 0…10 V DC for 0…100 % RH.
4.8.1
Humidification
An analog output is used to control a humidifier. The output will increase on decreasing humidity. A digital output can also be used to start a humidifier.
Maximum limitation function using duct humidity sensor:
If the maximum limitation is 80 % RH and the hysteresis is 20 % RH, the controller output signal will begin decreasing at 60 % RH. When halfway to 80 % RH (i.e. when at 70 % RH), half the output signal will be damped. If the humidity in the duct still reaches 80 % RH, the entire output signal will be damped.
4.8.2
Dehumidification
An analogue output ( Humidity control ) is used to control a dehumidifier. The output will increase on increasing humidity. A digital output can also be used to start a dehumidifier.
86 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
4.8.3
Humidification / Dehumidification
An analogue output ( Humidity control ) is used to control a humidifier. The output will increase on decreasing humidity.
For dehumidification it’s configurable which sequence that should be activated for dehumidification through condensation. The parameter for configuration is at Configuration ► Functions ► Humidity control ► Select sequence for dehumidify . The output will increase on increasing humidity. This signal overrides the cooling signal from the temperature controller so the output can be activated for dehumidification even if the temperature controller demand is zero.
cooler is placed first in the air stream so that the exchanger and heater can be used to reheat the air after dehumidification.
4.8.4
Digital humidity signal
A digital output signal, Humidity control start , can be used for on/off control of humidifiers/dehumidifiers.
The output signal has an activation value and a deactivation value which are connected to the humidity controller output. The signal is activated when the humidity controller output rises above the set activation value and is deactivated when the humidity controller output drops below the set deactivation value.
Setpoints are found in Ventilation ► Humidity control
If a start signal is needed for a cooling unit or a magnetic valve for DX dehumidification, the digital output signal for the configured sequence Sequence x pump should be used. In this case, the pump stop delay should be set to 0 s ( Ventilation ► Temperature control ► Sequence x ► Pump stop delay ).
4.8.5
Settings and configuration for Humidity control
Feature
Select Humidity control type
Select Sensor
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Temperature control
✓
✓
No
Humidification
✓ Dehumidification
✓ Humidification +
Dehumidification
Room temperature sensor (1…
16) etc.
Note
Select sequence for dehumidify Configuration ► Functions ►
Humidity control
Select type of output Configuration ► Functions ►
Humidity control
Select sequence for dehumidify
Select type of output
✓ Analog
✓ Step
✓ Analog + Step
Analog inputs: Humidity room/ extract air / Supply air / Outdoor
Configuration ► Analog inputs
► Humidity room/extract air /
Supply air / Outdoor
✓ Sensor type
✓ Min / max input (V)
✓ Min / max signal (%RH)
✓ Compensation (%RH)
✓ Mode
✓ Manual (%RH)
Analog output: Humidity control Configuration ► Analog outputs
► Humidity control
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Digital output: Humidity control start
Configuration ► Digital outputs► Humidity control start
✓
✓
NC (Normally closed
NO (Normally open)
Dehumidification /
Humidification
Corrigo manual, Rev. D 87 (196)
Information for the specialist - Function descriptions
Feature
Setpoints Humidity control
PID settings
Menu path in Application tool Variable
Ventilation ► Humidity control
► Humidity control
✓ Setpoint humidity room/ extract (%RH)
✓ Max limit humidity supply air
(%RH)
✓ Neutral zone between humidification and dehumidification
✓ Max deviation room/extract air humidity (%RH)
✓ Digital output start/stop point
(%RH)
✓ Hysteresis for max limit humidity supply air (%RH)
Note
Ventilation ► PID controllers ►
Humidity
✓ P-band (%RH)
✓ I-time (s)
✓ D-time (s)
✓ Max deviation room/extract air humidity (%RH)
✓ Digital output start/stop point
(%RH)
✓ Hysteresis for max limit humidity supply air (% RH)
P-band
4.8.6
Required inputs and outputs for humidity control
Inputs and outputs
AI
AI
AI
AO
DO
Room humidity sensor
Duct humidity sensor
Outdoor humidity sensor
Humidity control output
Humidity control start
4.9 Filter monitoring
Turn on filter monitoring in Configuration ► Functions ► Function activation .
Analog filter guards may be made air flow dependent. This means that a higher pressure drop is permitted across a filter at a higher air flow. For this purpose, X and Y coordinates are used to set the linear function that should be followed at a pressure drop alarm. They can also be accessed through the alarm settings in the display. FS = X1:0 m 3 /h, Y1:10 Pa : X2:2000 m 3 /h, Y2:150 Pa.
If a constant pressure drop alarm level is wanted, Y1 and Y2 should be set to the same value. In cases where flow control is not used, the first pressure value applies to pressure drop alarms (Y1).
4.9.1
Settings and configuration for filter monitoring
Feature
Activate filter monitoring
Type of filter monitoring
Filter placement
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Filter monitoring
Filter monitoring (yes/no)
✓ Sensor
✓ Guard
✓ Sensor + Guard
Configuration ► Functions ►
Filter monitoring
✓ Supply air
✓ Extract air
✓ Supply air + Extract air
Note
88 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Note Feature
Filter alarm reset
Filter alarm time (month)
Filter alarm supply air limit X1/
X2 (m 3 /h)
Filter alarm supply air limit Y1/
Y2 (Pa)
Filter alarm extract air limit X1/
X2 (m 3 /h)
Filter alarm extract air limit Y1/
Y2 (Pa)
Menu path in Application tool Variable
Configuration ► Functions ►
Filter monitoring
Yes/No
1…12 Configuration ► Functions ►
Filter monitoring
Configuration ► Functions ►
Filter monitoring
Configuration ► Functions ►
Filter monitoring
Configuration ► Functions ►
Filter monitoring
Configuration ► Functions ►
Filter monitoring
Factory settings (FS):
✓ X1 = 0
✓ X2 = 2000
Factory settings (FS):
✓ Y1 = 10
✓ Y2 = 150
Factory settings (FS):
✓ X1 = 0
✓ X2 = 2000
Factory settings (FS):
✓ Y1 = 10
✓ Y2 = 150
Required inputs and outputs for filter monitoring
Inputs and outputs
AI
Menu path in Application tool Name
Configuration ► Analog inputs ✓ Pressure filter supply air
✓ Pressure filter extract air
Settings
✓ Device
✓ Terminal
✓ Name
✓ Sensor type
✓ Min input (V)
✓ Max input (V)
✓ Min signal (Pa)
✓ Max signal (Pa)
✓ Filter factor
✓ Mode
✓ Manual (°C)
4.10 Extended operation and External stop
The digital inputs for extended running can be used to force the unit to start in low, normal or high speed although the timer says the operation mode should be Off.
This digital input has always higher priority than running via time schedule.
The unit will run for the set time. If the running time is set to 0 the unit will only run as long as the digital input is closed.
The signal External stop will stop the unit, even if the timer or one of the signals Extended operation low speed ,
Extended operation normal speed or Extended operation high speed says it should stay in running mode.
Table 4-60 Settings and configuration for extended operation and external stop
Feature
Select extended operation
Select external stop
Select extended operation speed
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Extended operation
Extended operation (Yes/No)
External stop (Yes/No)
Extended operation low/normal/ high speed (Yes/No)
Note
Corrigo manual, Rev. D 89 (196)
Information for the specialist - Function descriptions
Table 4-60 Settings and configuration for extended operation and external stop (continued)
Note Feature
Digital inputs: Extended operation low/normal/high speed
Digital input: External stop
Menu path in Application tool Variable
Configuration ► Digital inputs
► Extended operation low/ normal/high speed
Configuration ►Digital inputs
✓
✓
✓
NC (Normally closed)
NO (Normally open)
NC (Normally closed)
✓ NO (Normally open)
Table 4-61 Inputs and outputs Extended operation and external stop
Inputs and Outputs
DI
DI
DI
DI
Extended operation low speed
Extended operation normal speed
Extended operation high speed
External stop
4.11 Time-switch outputs
Up to four digital time-switch outputs can be configured. Each time channel has a separate scheduler with four periods per week-day.
Extra time channel 4 can be used to control the function Recirculation , see
Table 4-62 Settings and configuration for time-switch outputs
Feature
Select extra time channel
Settings Time schedule
Menu path in Application tool Variable
Configuration ► Functions ►
Extra indications & functions
Time control ► Extra time channel 1…4
Extra time channel (0…4)
Note
Table 4-63 Inputs and outputs Time-switch outputs
Inputs and Outputs
DO
Name
Extra time channel 1
DO
DO
DO
Extra time channel 2
Extra time channel 3
Extra time channel 4
Settings
✓ Controller/Expansion unit
✓ Terminal
✓ Name
✓ NC (Normally closed)/NO
(Normally open)
✓ Controller/Expansion unit
✓ Terminal
✓ Name
✓ NC (Normally closed)/NO
(Normally open)
✓ Controller/Expansion unit
✓ Terminal
✓ Name
✓ NC (Normally closed)/NO
(Normally open)
✓ Controller/Expansion unit
✓ Terminal
✓ Name
✓ NC (Normally closed)/NO
(Normally open)
Menu path in Application tool
Configuration ► Digital outputs
Configuration ► Digital outputs
Configuration ► Digital outputs
Configuration ► Digital outputs
90 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
4.12 SFP, Specific Fan Power
When the frequency controlled fans are connected via Modbus and also supply information on motor output, the Corrigo is capable of calculating SFP using the following formula:
SFP = Total effect from all fans / Supply air fan flow (in m 3 /s)
If both SAF and EAF flow transmitters are connected the controller uses the highest value. If only the SAF flow is connected that is used. If no flow sensor is connected it uses the highest calculated flow from the SAF pressure transmitter or EAF pressure transmitter.
Power loss as a percentage of the frequency converter can be added for calculating the total output. If, for instance, power loss is 5 %, the total output will be as follows:
Total output = (Supply air fan output + Extract air fan output) x 1.05
A daily and a monthly average (always 30 days) are also computed and presented. SFP for the average values is calculated only when the unit is running
The SFP values are displayed in Ventilation ► Energy consumption ► SFP
4.13 Extra controller
An independent temperature control circuit for control of for example a separate zone. The circuit can be configured to heating or cooling. It has an analog input signal for temperature sensors and an analog output signal 0…10 V. There is also a digital output signal which is activated when the analog output signal is above
1 V and deactivated when the analog signal is below 0.1 V. The circuit can be configured to be active all the time or to be active only when the unit is running or when defrosting.
An alarm will be triggered if Extra controller is in manual position or if a sensor error occurs.
The extra controller can also be controlled by freeze protection.
Type of freeze protection: Freeze protection temp 1-3.
Table 4-64 Settings and configuration for Extra controller
Feature
Select extra controller
Configuration Extra controller
Menu path in Application tool Variable
Configuration ► Functions ►
Function activation
Configuration ► Functions ►
Extra controller
Extra controller Yes / No
✓ Start/Stop function
✓ Control mode
✓ Type of freeze protection
✓ Pump control
✓ Pump running mode
✓ Type of feedback
✓ Digital start output
✓ Extra contr. output when recirculation/support
✓ Sequence output min/max limit (%)
Analog inputs temperature extra controller
Configuration ► Analog inputs
► Extra controller temperature
✓ Sensor type
✓ Min/max input (V)
✓ Min/Max signal (°C)
✓ Filter factor
✓ Compensation (°C)
✓ Mode
✓ Manual (°C)
Note
Corrigo manual, Rev. D 91 (196)
Information for the specialist - Function descriptions
Table 4-64 Settings and configuration for Extra controller (continued)
Feature
Digital inputs
Analog outputs
Digital outputs Extra controller start / Extra controller pump
Setpoint extra controller
Temperature control
PID settings
Manual / Auto
Menu path in Application tool Variable
Configuration ► Digital inputs
► Feedback extra controller
Configuration ► Analog outputs► Extra controller
✓ NC (Normally closed)
✓ NO (Normally open)
Manual / Auto
Range output:
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Configuration ► Digital outputs
► Extra controller start / Extra controller pump
✓ NC (Normally closed)
✓ NO (Normally open)
Setpoint extra controller (°C) Additional function ► Extra controller ► Actual/Setpoint
Additional function ► Extra controller ► Temperature control
✓
✓
Digital start output start/stop point (%)
Pump stop delay (min)
✓ Pump-kick hour (h)
✓ Pump running when outdoor temperature < (°C)
✓ Hysteresis to allow pump stop (°C)
Note
Additional function ► Extra controller ► PID controller
✓
✓
P-band (°C)
I-time (s)
✓ D-time (s)
Additional function ► Extra controller ► Manual / Auto
✓ Controller mode
✓ Manual set (%)
✓ Controller output (%)
✓ Extra controller start mode
✓ Start
✓ Extra controller pump mode
✓ Start
4.14 Room unit
A room unit, ED-RUx, can be configured in the Functions menu inApplication tool.
Room units are available with or without display, or as a touch display (see instructions and product sheets for ED-RU... and ED-RUD-2).
Different functions are available depending on the selected room unit, such as:
✓ Setpoint adjustment
✓ Show temperature
✓ Extended operation
✓ Select the speed of the fan
92 (196) Corrigo manual, Rev. D
Information for the specialist - Function descriptions
Feature
Temperature to show in ED-
RUx
Function on/off button
Fan speed extended run
Extended operation
Max negative setpoint adjustment
Max positive setpoint adjustment
Menu path in Application tool Variable
Configuration ► Functions ►
Room unit
Temperature to show in ED-
RUx:
✓ Room temperature of the display
✓ Room temperature from sensor connected to controller
✓ Outdoor temperature
✓ Supply air temperature
✓ Extract air temperature
Configuration ► Functions ►
Room unit
Configuration ► Functions ►
Room unit
Function on/off button:
✓ No function
✓ On/Off function
✓ On/Off/Extended operation function
Fan speed extended run:
✓ Low speed extended run
✓ Normal speed extended run
✓ High speed extended run
Configuration ► Functions ►
Room unit
Configuration ► Functions ►
Room unit
Configuration ► Functions ►
Room unit
Note minutes
4.15 Energy consumption
If the fans are controlled with Modbus communication, it is possible to follow up the energy consumption in
Application tool and in the web interface..
In the menu Ventilation ► Energy consumption you find the following information:
✓ SFP (Specific Fan Power)
✓ Power usage fans - the sum of power for all configured fans (SAF or EAF)
✓ Today and last 7 days - total accumulated power usage for today and the last seven days.
✓ This year - total accumulated power usage for the current year and for each month separately.
✓ Last year - total accumulated power usage for the previous year and for each month separately.
Corrigo manual, Rev. D 93 (196)
Information for the specialist - Configuration
5 Information for the specialist - Configuration
5.1 Configuration of the Corrigo
The configuration of the Corrigo is made in Application tool, a free PC-based software available on www.regincontrols.com
The controller doesn't need to be connected to the computer while configuring. All settings are made in the tool and then uploaded to the controller.
An infinite number of configurations can be stored in the computer memory for later use.
A communication cable is required in order to upload the configuration to the controller. The controller must also be powered up and the application selected in order for it to be configured.
5.1.1
Predefined configurations for Corrigo
There are predefined configurations available for easy configuration. They can be selected in the internal text display, in the web interface or can be downloaded as atf-files on Regin's webpage. The atf-files can be used in Application tool for further offline modification and adaption.
The predefined configurations are a part of Regin's Ready-Steady-Go concept which makes it much easier and faster to configure the controller.
Predefined configurations in internal text display
Use the internal text display in the Corrigo to select a predefined configuration.
1. Start from the start menu.
Vent controller 5.0
2020-01-08 14:29
System: Normal run
Sp:22.0 Act: 22.5°C
2. Press the right button [ ► ] 7 times until you reach the menu to select the configuration.
Choose Config File
None
3. Select the configuration you want. Available configurations depend on the number of IOs in the hardware.
94 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
4. Select add-ons. Available add-ons depends on the used hardware and selected configuration.
CO2 fan add-on
No
CO2 damper add-on
No
Extended run add-on
No
Fire alarm add-on
No
Free cooling add-on
No
5. Activate the configuration
Load configuration
No
Predefined configurations in web interface
Figure 5-1 Predefined configuration in web interface
Predefined configurations as atf-files
Predefined configurations can be downloaded as atf-files from Regin’s website ( www.regincontrols.com
).
The atf-files can be opened in Application tool and synchronized to the controller.
5.1.2
Application tool
Application tool is used both to configure, monitor and make changes in the application. The start screen gives an overview about what functions are available. For a description of the functions, see table
below.
For configuration and ventilation settings see
chapter 5.5 Configuration - Functions
and
Corrigo manual, Rev. D 95 (196)
Information for the specialist - Configuration
Figure 5-2 Application tool start screen
Table 5-1 Application tool: Menu items
Overview
Ventilation
Additional function
Inputs/Outputs
Configuration
Time control
Alarm status
An overview of the functions and values in the application
Configure setpoints, temperatures etc. Monitoring of ventilation unit.
Configuration of an extra controller.
Read values from all inputs and outputs.
Configuration of the BAS (Building Automation System). Switch on and off functions, define sequences etc.
Configure when the system should be working. Also possible in the display and in the web interface.
Check and acknowledge the alarms in the application.
96 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.2 Work flow for configuration and commissioning the Corrigo
1. Start by configuring the controller in Application tool or in the web interface. Both user-interfaces can be used to configure the controller in the same way. All following information is based on Application tool, but also applies to the web interface. Go through all the steps under the Configuration menu, see table
below.
function/application you choose to set up. Therefore, not all menu items are available for all applications.
Table 5-2 Configuration menu in Application tool
Configuration menu item
System
Device list
Functions
Analog inputs
Digital inputs
Analog outputs
Digital outputs
Raw values
Description
General settings, Communication settings, Unit settings, Save and restore settings
Activation of the different devices in the BAS (Building Automation System)
Activation of functions in the BAS. Configuration of sequences A to J
Configuration of Analog inputs
Configuration of Digital inputs
Configuration of Analog outputs
Configuration of Digital outputs
Read raw values from the controller and expansion units
2. Go to Ventilation menu in Application tool after the configuration is done. In the Ventilation menu you will set values and parameters for the application, see table below.
Table 5-3 Ventilation menu in Application tool
Ventilation menu item
Actual/Setpoint
Temperature control
Fan control
Demand control
Fire/Smoke
Humidity control
PID controllers
Energy consumption
Manual/Auto
Status
Description
Read the actual values and setpoints from the controller. Change setpoints.
Setting of parameters and values for Sequence A to J, Step controllers, Freeze protection, Exchanger, Pretreatment and Summer mode
Setting of values for fans and compensation curves
Setting of values for CO
2
, Recirculation, Free cooling and Support control
Setting of values for Fire and Smoke dampers and alarms
Setting of values for humidity control
Setting of P, I and D- values for Room, Extract air, Sequence A to J, Supply air fan,
Extract air fan, CO
2
, Freeze protection, Defrosting and Humidity
Read information about SFP, power usage for fans and accumulated power usage for today, last 7 days, current and previous year.
Setting of Manual or Auto control of units, functions and sequences.
Read status for the Ventilation unit and Sequences A to J
3. Load the application into the controller and commission. The application can be loaded from the web interfaceor Application tool.
In Application tool, go to the Tools menu at the top and select Load program .
Corrigo manual, Rev. D 97 (196)
Information for the specialist - Configuration
5.3 Configuration - System
Start with configuration of the system which contains the configuration of:
✓ General settings
✓ Communication settings
✓ Serial Ports
✓ BACnet
✓ TCP/IP
✓ Display port
✓ Unit settings
✓ CLOUDigo
✓ Save and restore
Figure 5-3 System configuration in Application tool
5.3.1
General settings
Under General is information about the controller, and some general settings can be made.
Change language
The display language can be changed either by the front display, in the web interface or in Application tool.
Front display menu:
Choose language
English
Web interface: pressing the [[ ► ]] button four times when the start display is shown.
98 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Account settings ► Language
Application tool:
Configuration ► System ► General ► Language
Start screen
There are several different start screens to choose from. The start screen can be changed in Application tool at: Configuration ► System ► General
Type 1, Show headline, date/time, vent. mode, supply temp / setp.
Vent controller 5.0
2019-08-01 11:28
System: Normal speed
Sp: 32.8°C Act:33.1°C
Second line: Date and time
Third line: Status of the unit
Fourth line: Supply temperature and setpoint
Type 2, Show headline, vent. mode, supply temp / setp, sequence A to C
Vent controller 5.0
System: Normal speed
Sp: 32.8°C Act:33.1°C
A 100 B 100 C 100
Second line: Status of the unit
Third line: Supply temperature and setpoint
Fourth line: Output signal of the sequences A to C
Type 3, Show headline, vent. mode, supply temp / setp, SAF / EAF pressure
Vent controller 5.0
System: Normal speed
Sp: 32.8°C Act:33.1°C
SAF: 2000 EAF: 2000
Second line: Status of the unit
Third line: Supply temperature and setpoint
Fourth line: SAF- and EAF- pressure
Type 4, Show headline, date/time, vent. mode
Vent controller 5.0
2019-08-01 11:28
System: Normal speed
Second line: Date and time
Third line: Status of the unit
Corrigo manual, Rev. D 99 (196)
Information for the specialist - Configuration
Type 5, Show headline, date/time
Vent controller 5.0
2019-08-01 11:28
Second line: Date and time
Automatic switch between summer and winter time adjustment
The internal clock is normally configured for automatic summer / winter time adjustment. When enabled, the clock will be set forward one hour at 02:00 am on the last Sunday of March and adjusted back one hour at 03:00 am on the last Sunday of October.
The function can be disabled in Application tool: Configuration ► System ► General
Automatic logoff
If the access level is set to Operator or Admin , the user will automatically be logged off after a set time of inactivity. The time is settable in units of 5 seconds in Application tool. The default is 60 units = 5 minutes
The automatic log off can be disabled in Application tool: Configuration ► System ► General ► Time before automatic logoff in display (unit 5s) (min)
5.3.2
Port 1 and Port 2
The controller can have one or two serial ports. In a controller with two serial ports, both ports have the same functions. However, they can not both be configured to have the same function at the same time, except that both can be slaves.
Table 5-4 Available settings for Port configuration
Types of communication
✓ EXOline slave (Default)
✓ EXOline master
✓ Modbus slave
✓ Modbus master
✓ BACnet MSTP slave
✓ EFX master
Available formats
✓ 8N1 – 8 bit, no parity, 1 stop bit
✓ 8E1 – 8 bit, even parity, 1 stop bit
✓ 8O1 – 8 bit, odd parity, 1 stop bit
(Default)
✓ 8N2 – 8 bit, no parity, 2 stop bit
✓ 8E2 – 8 bit, even parity, 2 stop bit
✓ 8O2 – 8 bit, odd parity, 2 stop bit
Available Baud rates
✓ 9600 (Default)
✓ 14400
✓ 19200
✓ 28800
✓ 38400
✓ 57600
✓ 76800
✓ 115200
The default settings of the ports is EXOline slave:
Function port1
EXOline slave
Format 8O1
Baud 9k6
Table 5-5 Port 1 and 2: Function default values
Function
EXOline slave
EXOline master
Modbus slave
Connection to
Application tool or SCADA system
Pressure transmitters, Expansion units or Room units
SCADA system via Modbus or master controller
Format
8O1
8O1
8N1
Baud
9600
9600
9600
100 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-5 Port 1 and 2: Function default values (continued)
Function
Modbus master
BACnet MS/TP slave
Connection to
Fans, Rotary exchanger, Pressure transmitters, Damper actuators and Wireless receivers
BACnet SCADA or BACnet master controller
Format
8N1
8O1
Baud
9600
9600
5.3.3
Modbus slave
Set the Modbus address for the Modbus slave.
5.3.4
BACnet
The controller is capable of communication via the BACnet -protocol, using either IP or MS/TP data link formats.
In order to connect a controller to a BAS (Building Automation System) via BACnet/IP, a controller with a
TCP/IP port is required. To connect to a BAS via BACnet MS/TP, a controller with an RS485 communication port is required.
function/application you choose to set up. Therefore, not all menu items are available for all applications.
Figure 5-4 All BACnet settings
Table 5-6 BACnet settings
Variable
BACnet/IP
BACnet device name
BACnet device ID
BACnet/IP UDP port number
Function
On/Off
Description
The BACnet/IP protocol is disabled as default. Choose On to enable the protocol.
Name of the controller Editable
The ID of a device, used to identify it on the
BACnet network
The ID number must be unique, and can not be duplicated anywhere on the BACnet network. Editable.
47808
Corrigo manual, Rev. D 101 (196)
Information for the specialist - Configuration
Table 5-6 BACnet settings (continued)
Variable
BBMD address
BACnet MS/TP highest master address
BACnet MS/TP MAC
Function Description
The address is entered as host:port , where host can be the host’s name if DNS is configured. If DNS is not configured, the host address should be entered in the format xxx.xxx.xxx.xxx
, followed by the port number (default setting 47808).
Example: mybbmd: 47808 (with DNS configured) or 10.100.50.99:47808
The BBMD address (BACnet/IP Broadcast
Management Device) is used for discovering devices that are attached to different
BACnet/IP subnets and separated by an
IP-router. Editable.
127
0
The max master address is the MAC address of the highest master device on the BACnet MS/TP network segment.
Setting this number above the highest
MAC address will decrease network performance. Editable.
The MAC address of the device. This needs to be unique only to the subnet to which the device is attached. Editable.
5.3.5
CLOUDigo
The Corrigo can be connected to Regin's cloud server CLOUDigo for access to the controller from any computer.
Set Active to On to be able to connect to CLOUDigo.
Read more about CLOUDigo at Regin's webpage, www.regincontrols.com.
5.3.6
Display port
Two different external displays can be used with the Corrigo.
controller from power and connect it again.
Display
E3-DSP
ED-T43L-V
Description
External text display with menu buttons.
External touch display. 4.3 inch.
Both displays can be found on www.regincontrols.com
5.3.7
Unit settings
Choose units for the system.
Function
Temperature
Flow
Pressure
Unit
°C or °F m 3 /h, CFM, m 3 /s or l/s
Pa or in.wg
102 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.3.8
Save and restore
It is possible to save all settings in a separate memory area of the controller and restore it afterwards. Two different settings can be stored; local settings and factory settings. The saved settings are available after a reset of the application, see
chapter 6.3 Loading the application .
Varible
Save settings local
Restore settings to local
Save factory settings
Total restore to factory settings
Function
Yes/No
Yes/No
Yes/No
Yes/No
5.3.9
Controller address (PLA : ELA)
Description
Saving of the current configuration as local
“user” settings
Restore the saved settings.
Saving the current configuration as factory settings
Go back to the factory settings the controller was delivered with.
Figure 5-5 Changing the controller address and IP settings
The controller uses PLA:ELA addresses when connecting to Application tool and when multiple controllers are connected in a network. Application tool normally uses the addresses PLA = 254 and ELA = 254, so if an address is changed, the new address must also be entered in Application tool. If several controllers are connected in a network, all the units must have the same PLA address, but each unit must have a unique
ELA address.
The address can be changed in the Application tool in the menu Tools ► Change controller address, see
Figure 5-5 Changing the controller address and IP settings
above.
Corrigo manual, Rev. D 103 (196)
Information for the specialist - Configuration
5.3.10 IP-configuration
IP configuration can be made both in Application tool or in the built-in display.
The Dynamic Host Configuration Protocol (DHCP) is a network protocol used on Internet Protocol (IP) networks for dynamic distribution of network configuration parameters, such as IP addresses, DNS servers and other services.
The controller can be configured to either obtain an IP address from a DHCP server (dynamic) or the address can be set manually (static).
Three additional functions can be activated on the network interface:
✓ BACnet IP communication
✓ Connection to the Cloud-server
✓ Modbus TCP
If you wish to set a static IP address for the controller, enter the IP address you wish to use along with the subnet mask, gateway address and DNS server address. In Application tool you go to the Tools menu and choose Change IP settings, see figure
Figure 5-5 Changing the controller address and IP settings
above.
In the display you do as follows below:
TCP/IP
DHCP: Yes
Set static IP
Running IP
-
IP
192.168.001.234
Subnet mask
255.255.255.000
Running subnet mask
-
Running gateway
-
Running DNS1
192.168.001.001
Running DNS2
192.168.001.001
5.4 Configuration - Device list
Different kind of devices can be connected to the Corrigo, i.e. transmitters, fans/frequency converters and expansion units.
It is possible to change the name of the Device in the Name field
104 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Figure 5-6 Device list
5.4.1
Fan (Modbus)
The Corrigo only supports frequency controlled fans with Modbus communication. The fan can be set to three different speeds: Low, Normal and High .
Table 5-7 Fan models and configuration
Model
✓ Vacon
✓ Lenze
✓ Yaskawa/Omron
✓ Emerson
✓ LS iG5A
✓ LS iS7
✓ EBM - PAPST
✓ DANFOSS FC101
✓ ABB ACSxxx
✓ Ziehl blue
Function
✓ Disabled
✓ Supply air fan
✓ Extract air fan
Name
Optional: name the fan
5.4.2
Rotary exchanger (Modbus)
A rotary heat exchanger can be connected to the controller. Three different models can be used.
Table 5-8 Rotary exchanger models and configuration
Model
✓ RHC 200 (Reflex- Winkelmann)
✓ VariMax25M (IBC control)
✓ OJ DHRX
Function
Sequence A to J
Name
Optional: Name the rotary exchanger
Corrigo manual, Rev. D 105 (196)
Information for the specialist - Configuration
5.4.3
Pressure transmitter (Modbus / EXOline)
Regin's differential pressure transmitter Presigo can be connected to the controller. Two generations of
Presigo are available (PDT... and PTDX) and they are available with one or two pressure sensors. Presigo can be configured as expansion unit (1…10) (under Configuration ► Device list ► Device x ► Function) and will expand the number of available I/O:s.
Presigo model
PDT...C
PDT...C-2
PDT...C
PDT...C-2
PDTX...
PDTX...-2
Generation
1
1
2
1
1
2
Pressure sensors
1
2
1
1
2
2
Communication
Modbus
Modbus
EXOline
EXOline
Modbus
Modbus
Expansion with I/O:s
2 x UI
2 x UI
2 x UI
2 x UI
2 x UI, 2 x UO
2 x UI, 2 x UO
5.4.4
Damper actuator
The controller supports two different kinds of damper actuators
Table 5-9 Damper models and configuration
Model
✓ Belimo Brand
✓ Siemens
Function
✓ Sequence A to Sequence J
✓ Recirculation air damper
✓ Outdoor air damper
✓ Exhaust air damper
✓ Fire damper
Name
Optional: Name the damper actuator
5.4.5
Expansion unit (EXOline)
In order to connect additional inputs and outputs to the controller, a communication device needs to be configured. It is possible to connect two expansion units, giving a maximum number of 28*3 = 84 inputs/ outputs. I/O-expansion units or controllers configured as expansion units can be connected.
Expansion unit
IO-A15MIXW-3-BEM
IO-A28MIXW-3-BEM
IO-V19MIXW-1-BEM
Number of I/O:s
15 I/O:s
28 I/O:s
19 I/O:s
5.4.6
Wireless receiver (Modbus)
To be able to use wireless transmitters and sensors in the installation, a wireless receiver must be connected to the Corrigo. There are two receivers available, with different numbers of sensors that can be connected.
Wireless Receiver
RCW-M
RCW-M32
Number of sensors
16
32
No further settings are necessary to communicate with the wireless receiver.
106 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.4.7
Room unit (EXOline/Modbus)
The temperature, fan speed and CO
2
-level in a room can be controlled via a room unit connected to the
Corrigo. There are nine different room units to choose from with different features (see table below).
The room units communicate via EXOline and are connected to the serial ports or display port.
In Application tool, they are configured as expansion units 1…10.
Article
ED-RU
ED-RU-O
ED-RU-F
ED-RU-FO
ED-RU-DO
-
ED-RU-DFO ✓
Occupancy button
-
ED-RU-DOS ✓
ED-RU-H -
ED-RU-
DOCS
ED-RUD-2
-
-
-
-
-
3-step fan control
-
-
-
-
-
-
-
-
Built-in CO
2 sensor
-
-
-
-
-
-
Setpoint knob
-
-
-
-
-
-
-
-
-
Multi-function button
Hidden setpoint
-
-
-
-
-
-
-
-
-
Display
-
-
-
-
-
EXOline (E)/
Modbus (M)
E
E
E
E
E
E
E
E
E
M
5.5 Configuration - Functions
This is where you activate the functions that will be used in the BAS (Building Automation System). It is also where you set up sequence A to J. All functions are more thoroughly described in chapter
4 Information for the specialist - Function descriptions
.
tion you choose to set up. Therefore, not all menu items are available for all applications.
5.5.1
Function activation
In this section you choose control types and turn on or off functions in the BAS (Building Automation
System).
Corrigo manual, Rev. D 107 (196)
Information for the specialist - Configuration
Temperature control type
Figure 5-7 Temperature control type
Table 5-10 Temperature control types
Application
Supply air
Supply air outdoor compensated
Room cascade
Extract air cascade
Room (summer) else supply air
Description More information
The supply air controller output is either a heating demand or a cooling demand depending on if the supply temperature is over or under the setpoint. This demand is then divided into up to 10 sequences, A to
J. Each sequence can be configured as heat, cool, exchanger, damper, compensation or not used and each sequence has it own PID-settings.
Function description:
Sequences:
chapter 4.3 Temperature sequences
Function description:
chapter Supply air outdoor compensated
Sequences:
chapter 4.3 Temperature sequences
The supply air temperature setpoint is temperature compensated using a control curve. The temperature for compensation is configurable between all temperature sensors.
The supply air temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
Cascade control of room temperature and supply air temperature to achieve a constant, settable room temperature.
The room temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
Function description:
Sequences:
Cascade control of extract air temperature and supply air temperature to achieve a constant, settable room temperature.
The extract air temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
Function description:
Sequences:
chapter 4.3 Temperature sequences
Summer mode dependent switching between supply air temperature control and room temperature control.
When the summer mode function is off, temperature compensated supply air temperature control will be active, otherwise (in summer) cascaded room temperature control. Summer mode function is used for switching control mode.
Function description:
(summer) else supply air outdoor compensated
108 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-10 Temperature control types (continued)
Application
Extract air (summer) else supply air
Room outdoor compensated
Extract air outdoor compensated
Extract air dependent supply air
Description More information
Summer mode dependent switching between supply air temperature control and extract air temperature control
When the summer mode function is off, temperature compensated supply air temperature control will be active, otherwise (in summer) cascaded extract temperature control. Summer mode function is used for switching control mode.
Function description:
(summer) else supply air outdoor compensated
The extract air temperature can be compensated when the outdoor temperature increases.
A difference between extract air temperature and supply air temperature can be configured to maintain that the supply air temperature setpoint follows the extract air temperature.
Function description:
chapter Room outdoor compensated
Function description:
chapter Extract air outdoor compensated
A difference between extract air temperature and supply air temperature can be configured to maintain the supply air temperature setpoint to follow extract air temperature.
Function description:
chapter Extract air dependent supply air
Read more about the temperature control functions in
Fan control type
Table 5-11 Fan control types
Application
Pressure
Flow
Manual
External
Supply air pressure and extract air fan slave
Description
Control of the fan speed using pressure transmitters.
Instead of giving a pressure setpoint value, it is possible to use an airflow volume value in m 3 /h.
The value from the pressure transmitter is recalculated to a volume flow and the fans will be controlled to give a constant flow.
Use the manual setting if you want to manually set the speed of the fan
More information
Function description:
Function description:
Function description:
Use the external setting if you have an external device that controls the fan speed, e.g. a 0…10 V device.
Function description:
The speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan does not have a pressure transmitter, instead you let the output for the extract air fan follow the control signal for the supply air fan. A scaling factor can be added if the characteristics of the extract air fan are not the same as the characteristics of the supply air fan.
(Only pressure control of the supply air fan is possible using this function.)
Function description:
chapter Supply air pressure and extract air fan slave
Corrigo manual, Rev. D 109 (196)
Information for the specialist - Configuration
Table 5-11 Fan control types (continued)
Application
Supply air pressure with extract air flow slave
Extract air pressure with supply air fan slave
Description More information
The speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan is controlled by the supply air flow, in order to achieve a balanced ventilation. A pressure transmitter which is placed in the supply air fan cone (SAF flow) gives a measured value of the present supply air flow. A corresponding pressure transmitter is placed in the extract air fan cone and gives a measured value of the extract air flow.
The supply air flow is the setpoint used for control of the extract air fan. A scaling factor can be added if the extract air fan does not have the same characteristics as the supply air fan.
Function description:
chapter Supply air pressure with extract air flow slave
The speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan has no pressure transmitter. Instead, the supply air fan output is made to follow the extract air fan control signal. A scaling factor can be added if the supply air fan characteristics are not the same as the characteristics of the extract air fan (only pressure control of the extract air fan is possible using this function).
Function description:
chapter Extract air pressure with supply air fan slave
Extract air fan pressure with supply air flow slave
The speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan is controlled by the extract air duct flow in order to achieve a balanced ventilation. A pressure transmitter placed in the extract air fan cone (EAF flow) provides a measurement of the current extract air flow. A corresponding pressure transmitter is placed in the supply air fan cone, providing a measurement of the supply air flow.
The supply air fan is controlled using the extract air flow as a setpoint. A scaling factor can be added if the supply air fan does not have the same characteristics as the extract air fan.
Function description:
chapter Extract air fan pressure with supply air flow slave
Read more about fan control types in
Fan levels
A frequency controlled fan is the only type of fan that works with the Corrigo. The fan can be set to Low,
Normal or High speed. The selection of the fan speed defines which IOs and time channels will be active in the application.
The fans will always start directly with the desired speed.
There are four different fan speed levels to choose from in Application tool:
✓ Normal
✓ Low - Normal
✓ Normal - High
✓ Low - Normal- High
Variable speed control uses an analogue output per fan or Modbus communication for controlling a frequency converter.
For more information about frequency converters, see
Appendix F Frequency converters and EC controllers for heat exchangers
110 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
The fans are normally controlled by the timer channels for slow, normal and high speed but can also be started via digital input or communication.
The extract air fan and the supply air fan have individual start and stop delays which are normally set so that the extract air fan is started before the supply air fan. If there are not enough digital outputs for individual control, both fans will have to be started using the signal for the supply air fan, and the delay will be created using an external time relay.
Fan compensation
When running pressure/flow control or manual frequency control, it is also possible to for the pressure/flow or output to be temperature compensated.
This compensation can be made depending on any analogue input such as supply air, extract air, room, outdoor temperature, humidity, CO
2 and so on. There are three equal compensation functions available.
It is possible to compensate either one or both of the fans at the same time and it is possible to set which fan should then be compensated, the supply fan or the extract air fan.
Read more about fan compensation in
Support control
Support control is normally used when room temperature control or extract air control has been configured.
When extract air control is configured a room sensor must be installed.
Support control can also be configured to start only with the supply air fan. In this mode, the extract air fan is not active. This requires a digital output to be configured, which controls the recirculation damper to open completely so the supply air fan can circulate the air to and from the room.
Read more about support control in
CO
2
control
In applications with varying occupancy the fan speeds or mixing dampers can be controlled by the air quality as measured by a CO
2 sensor.
With the CO
2 function it’s possible to start and stop the fans, compensate the fan speed and in combination with mixing damper let in more outdoor air depending on the CO
2 value. This can be configured with the
CO
2 control settings, see
Read more about the CO
2
function in 4.4.3 Demand controlled ventilation
.
Table 5-12 CO
2 control settings
Fan stop/start function
Mixing damper function
Fan start/stop + mixing damper
When the function is activated with start/stop function and the CO
2 value rises above settable start value the fans will start at configured speed (default: normal speed), if they are not already running.
If demand controlled ventilation is activated in combination with mixing dampers, and the
CO
2
-value rises above the setpoint value the dampers controlled by a sequence with CO
2 function will be overtaken by the CO
2 controller and let in more outdoor air. The function is controlled by a PI-controller.
If demand controlled ventilation is activated in combination with mixing dampers, and the
CO
2
-value rises above the setpoint value the dampers controlled by a sequence with CO
2 function will be overtaken by the CO
2 controlled by a PI-controller.
controller and let in more outdoor air. The function is
Inputs and outputs
AI CO
2
-sensors
Corrigo manual, Rev. D 111 (196)
Information for the specialist - Configuration
Free cooling
This function is used during the summer to cool the building night-time using cool outdoor air, thereby reducing the need for cooling during the day and saving energy.
Free cooling requires an outdoor sensor or an intake temperature sensor and either a room sensor or an extract air sensor. If both an outdoor sensor and an intake sensor is configured it uses the outdoor sensor for the function.
Free cooling is only activated when all the start conditions below are fulfilled.
✓ Less than four days have passed since the unit was last in running mode.
✓ The outdoor temperature during the previous running period exceeded a set limit (22°C).
✓ It is between 00:00 and 07:00:00 in the day (settable).
✓ The timer outputs for Normal speed, Extended running, Normal and External switch are Off .
✓ A timer channel will be On sometime during the next 24 hours.
If an intake sensor is used and/or an extract air sensor is selected and ALL the start conditions are fulfilled, free cooling is activated and will run for 3 minutes (settable) to ensure that the temperature measurement when using an extract air sensor reflects the corresponding room temperature and that the intake temperature sensor senses the outdoor temperature even if it is placed in the fresh air inlet duct. If an outdoor sensor and a room sensor is selected, the unit will not start free cooling as long as all the temperatures are not within the start and stop temperature intervals.
Read more about free cooling in
Inputs and outputs
AI
AI
DO
Outdoor temperature sensor or Intake temperature
Room sensor or Extract air sensor
Free cooling operation
Recirculation
Recirculation is a function for distributing the air in the room using the supply air fan. The function can be used even when there is no heating or cooling demand. When using recirculation control, the extract air fan stops (but can also be set to run) and a recirculation damper opens which allows the air to circulate through the unit.
Recirculation is activated either via a digital input signal or by connecting it to Extra time channel 4 (
Application tool - Time control). If timer output for Low/Normal/High speed is activated during recirculation via Extra time channel 4 , Low/Normal/High speed gets priority. If timer output for Low/Normal/
High speed is activated during recirculation activated by a digital input, recirculation gets priority.
Either a digital output (Recirculation damper) or an analogue output sequence (A toJ) can be used as an on/ off output signal.
Recirculation control can be configured as either air circulation (temperature control inactive) or air circulation with temperature control. (Only heating, only cooling or both heating and cooling). Recirculation control has its own setpoint. However, the other settings are the same as for normal operation, i. e. if normal operation has been configured as room control, room control will also be used during recirculation.
Read more about Recirculation in
Pretreatment
Control of dampers and pump for preheated or pre-cooled outdoor air via an underground intake channel.
112 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
The digital output Pretreatment is set to preheating when the unit is started and the outdoor temperature is below the set heating start limit or to precooling when the outdoor temperature is above the set cooling start limit. If the outdoor temperature exceeds the set heating start limit by more than 1°C, preheating will be aborted, as well as if the outdoor temperature falls below the cooling start limit by 1°C.
Read more about pretreatment in
Extra controller
An extra controller can be used as an independent temperature control circuit for control of for example separate zones. The circuit can be configured to heating or cooling. It has an analog input signal for temperature sensors and an analogue output signal (0…10 V). There is also a digital output signal which is activated when the analogue output signal is above 1 V and deactivated when the analogue signal is below
0.1 V. The circuit can be configured to be active all the time or to be active only when the unit is running or when defrosting.
Read more about the extra controller in
Fire / Smoke
Fire dampers are normally configured to open on fire alarm but can be configured to be normally open instead. It is possible to configure which speed the fans should have when in fire mode – however, this is not possible when the fire function has been set to Running via normal start/stop conditions . Setting the fan speed to -1 % will deactivate the fan speed selection. Read more about the fire/smoke function in
Inputs and outputs
DO
DO
DO
DI
DI
Outdoor air damper
Exhaust air damper
Fire damper
Fire alarm
Fire damper end switch monitoring
Humidity control
Humidity control can be configured as Humidification, Dehumidification or both Humidification and
Dehumidification.
Two humidity sensors can be connected, a room sensor for control and an optional duct sensor for maximum limiting. The limit sensor can be omitted.
The humidity control is handled by a PI-controller.
The humidity sensors must give 0…10 V DC for 0…100 % RH.
Read more about Humidity control in
Humidification
Dehumidification
An analogue output is used to control a humidifier. The output will increase on decreasing humidity. A digital output can also be used to start a humidifier.
An analogue output ( Humidity ) is used to control a dehumidifier. The output will increase on increasing humidity. A digital output can also be used to start a dehumidifier.
Humidification + Dehumidification An analogue output ( Humidity ) is used to control a humidifier. The output will increase on decreasing humidity.
For dehumidification it’s configurable which sequence that should be activated for dehumidification through condensation. The output will increase on increasing humidity. This signal overrides the cooling signal from the temperature controller so the output can be activated for dehumidification even if the temperature controller demand is zero.
Corrigo manual, Rev. D 113 (196)
Information for the specialist - Configuration
Filter monitoring
Turn on filter monitoring to monitor the flow through the filter. Analog filter guards may be made air flow dependent. This means that a higher pressure drop is permitted across a filter at a higher air flow. For this purpose, X and Y coordinates are used to set the linear function that should be followed at a pressure drop alarm.
Read more about filter monitoring in
Extended operation
The digital inputs for extended running can be used to force the unit to start in reduced, normal or high speed although the timer says the running mode should be Off . This digital input has always higher priority than running via time schedule.
The unit will run for the set time. If the running time is set to 0 the unit will only run as long as the digital input is closed.
Read more about extended operation in
chapter 4.10 Extended operation and External stop
External stop
The signal External switch will stop the unit, even if the timer or one of the signals Extended Operation, Low ,
Extended Operation, Normal or Extended Operation, High says it should stay in running mode.
Read more about external stop in
chapter 4.10 Extended operation and External stop
Extra fan motor control
External control of an external fan motor can be configured. The fan is started via either a digital input, time channel 4 or when the unit is started.
Read more about extra fan motor control in
1
2
Control mode
0
Start / Stop
Only on DI
When unit is running
Time channel 4
A digital output activates the fan motor. A digital input is available for run time indication/motor protection.
Damper
The outdoor air and exhaust air ducts close-off dampers can be controlled by digital outputs or be hardwired to the supply air fan relays for normal, reduced and high speed in such a fashion that the damper is open when the supply air fan is running. When using pressure controlled fans the digital activation signal is activated as soon as the fan has start conditions. This signal can be used to open the close-off damper.
Damper location to choose from:
✓ Outdoor
✓ Outdoor + Exhaust
✓ Exhaust
Read more about dampers in
114 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Automatic restart after power on
This function makes it possible to block automatic restart of the unit at power-up. At power-up, the B-alarm
Restart blocked after power on is generated. Once this alarm has been acknowledged, the unit will start. See more about alarms in
5.5.2
Sequences
Figure 5-8 Application Tool - Configuration - Functions
There are ten sequences (A to J) that can be configured in the Corrigo. Each sequence will have their own
PID-settings and a PWM digital output signal (Pulse Width Modulation).
The sequence types that can be configured are:
✓ Not used
✓ Heating
✓ Cooling
✓ Exchanger
✓ Damper
✓ Fan setpoint compensation
The default settings are:
✓ A = Heating
✓ B = Exchanger
✓ C = Cooler
✓ D to J = Not used tions you make in other menus.
Read more about sequences in
chapter 4.3 Temperature sequences
Corrigo manual, Rev. D 115 (196)
Information for the specialist - Configuration
Heater sequence
The table below shows the possible settings for a Heater sequence. Not all settings are visible for any type of heater.
Table 5-13 Sequence alternatives
Application tool
Name
Type of sequence
Type of heater
Setting alternatives
Free choice
Heating
✓ Inactive
✓ Water
✓ Electric
✓ DX (Direct exchanger)
Type of freeze protection
Freeze protection temperature sensor
✓ None
✓ Temperature sensor
✓ Freeze guard
✓ Sensor + Guard
✓ None
✓ 1
✓ 2
✓ 3
Yes / No Pump control
Pump stop mode
Type of pump indication
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Sequence output when recirculation/ support
✓ Always running
✓ Auto
✓ None
✓ Alarm
✓ Run Indication
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Sequence output min limit (%)
Sequence output max limit (%)
Sequence output when the unit is stopped
(%)
Sequence output when fire mode
Sequence output when smoke mode
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Writable
0, 1, Auto
0, 1, Auto
Note
Cooler sequence
The table below shows the possible settings for a Cooler sequence. Not all settings are visible for any type of cooler.
Table 5-14 Sequence alternatives
Application tool
Name
Type of sequence
Type of cooler
Setting alternatives
Free choice
Cooling
✓ Inactive
✓ Water
✓ DX (Direct exchanger)
✓ DX with exchanger control
Note
116 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-14 Sequence alternatives (continued)
Application tool
Pump control
Pump stop mode
Setting alternatives
Yes / No
Type of pump indication
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Sequence output when recirculation/ support
✓ Always running
✓ Auto
✓ None
✓ Alarm
✓ Run Indication
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Sequence output min limit (%)
Sequence output max limit (%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Sequence output when the unit is stopped
(%)
Writable
Note
Exchanger sequence
The table below shows the possible settings for an Exchanger sequence. Not all settings are visible for any type of heater.
Table 5-15 Sequence alternatives
Application tool
Name
Type of sequence
Type of exchanger
Setting alternatives
Free choice
Exchanger
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Exchanger alarm
Defrosting mode
✓ Inactive
✓ Rotating
✓ Plate
✓ Liquid
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Yes / No
✓ No defrosting
✓ Defrosting temperature monitoring
Yes / No Freeze prevention rotation exchanger
Sequence output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Sequence output when the unit is stopped
(%)
Writable
Note
Corrigo manual, Rev. D 117 (196)
Information for the specialist - Configuration
Damper sequence
The table below shows the possible settings for a Damper sequence. Not all settings are visible for any type of heater.
Table 5-16 Sequence alternatives
Application tool
Name
Type of sequence
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Exchanger alarm
Enable enthalpy control
CO2 control
Setting alternatives
Free choice
Damper
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Yes / No
Yes / No
✓ No
✓ CO2 sequence 1
✓ CO2 sequence 2
CO2 control mode ✓ Decreasing
✓ Increasing
Sequence output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
Sequence output when the unit is stopped
(%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Writable
Note
Fan setpoint compensation sequence
The table below shows the possible settings for a Fan setpoint compensation sequence. Not all settings are visible for any type of heater.
Table 5-17 Sequence alternatives
Application tool
Name
Type of sequence
Type of setpoint compensation
Setting alternatives
Free choice
Fan setpoint compensation
✓ Inactive
✓ Decrease
✓ Increase
Yes / No Digital start output
Sequence output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
Sequence output when the unit is stopped
(%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Writable
Note
118 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Starting order heating/cooling
Setting of the order of the sequences is made in Configuration ► Functions ► Sequence heating/cooling.
It is possible to define a specific start order for the different sequences for heating and cooling demand.
The selectable number, 1…10, defines the start order of the sequences. If two sequences have the same start order they will work in parallel.
Start order heating shows only sequences which can work as a heating sequence, such as:
✓ Heater
✓ Exchanger
✓ Damper
✓ Fan setpoint compensation
Start order cooling shows only sequences which can work as a cooling sequence, such as:
✓ Cooler
✓ Exchanger
✓ Damper
✓ Fan setpoint compensation
The following picture (
5-9 ) shows the default settings of the configured sequences A=Heater, B=Exchanger
and C=Cooler, where the Exchanger (SEQ. B) starts first in heating mode followed by the Heater (SEQ. A).
In cooling mode, the Exchanger (SEQ. B) starts first followed by the Cooler (SEQ. C).
Output (%)
100% = 10 V
Sequence order 2 1 1 2
SEQ. C SEQ. B SEQ. B SEQ. A
Sequence capacity (%)
Sequence output (%)
Figure 5-9 Sequence order
0-100% 0-100% 0-100% 0-100%
Sequence settings
These settings are used the define the start of the sequences when the unit starts. There are two different modes to start the unit:
✓ Normal start up
✓ Warm (Heat) start up
Normal start up:
The sequence control starts at 100% for the heating sequence which is selected at the parameter At start up begin temperature control at 100% in . The default setting is Heating 1 , which means it starts at 100% for heating sequence 1 which is the exchanger in the default configuration.
Corrigo manual, Rev. D 119 (196)
Information for the specialist - Configuration
Warm start up:
If the outdoor temperature is lower than the settable limit Warm start up if outdoor temperature < (°C) the unit will start in the warm start mode. A second sequence will start at 100% in this mode if the unit starts. The default setting is Heating 2 , which means it starts at 100% for the heating sequence 2 which is the heater in the default configuration
Table 5-18 Sequence settings
Application tool
At start up begin temperature control at
100 % in
Setting alternatives
✓ Heating 1 0%
✓ Heating 1…10
Writable Warm start up if outdoor temperature < (°
C)
If warm start up begin temperature control at 100 % in
✓ Heating 1 0%
✓ Heating 1…10
Note
Temperature control
Table 5-19 Temperature control
Application tool
Room temperature sensor
Room temperature average
Setting alternatives
None / 1…16
Outdoor temperature sensor
✓ No
✓ Minimum
✓ Maximum
✓ Average
✓ Average remove min / max
✓ Median
✓ No
✓ Intake air
✓ Outdoor
✓ Outdoor + intake air
Yes / No
Yes / No
Yes / No
Extract air temperature sensor
Supply air temperature sensor
Exhaust air temperature sensor
Activate summer mode ✓ No summer setpoint
✓ Switch with calendar
✓ Switch with change-over
✓ Switch with digital output
✓ Switch with outdoor temp
External setpoint device
Efficiency presentation
Min temperature difference to show efficiency (°C)
✓ No
✓ TG - R4
✓ TBI - PT1000
Yes / No
Writable (Default 2)
Min outdoor temperature to show efficiency
(°C)
Writable (Default -100)
Cooling recovery mode On / Off
Temperature difference to start cooling recovery (°C)
Fan speed compensated temperature setpoint
Writable (Default 0)
Defrosting exchanger
✓ None
✓ Low
✓ High
✓ Low & High
Yes / No
120 (196)
Note
How to display the room temperature value.
Which temperature the outdoor sensor measures
Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-19 Temperature control (continued)
Application tool
Defrosting temperature sensor
Setting alternatives
✓ Defrosting sensor
✓ Exhaust air temperature
Extract air fan speed when Defrosting with stopped supply air
✓ Auto
✓ Low
✓ Normal
✓ High
Note
Change-over 1 and 2
Select the change-over sequence for heating and/or cooling.
Read more about change-over in
Step controller 1 and 2
Application tool
Step controller sequence
Setting alternatives
Off
Sequence A…J
Change-over
Step control
Number of steps
Sequential / Binary
1…4
Block output if sequence feedback alarm Yes / No
Read more about step control in
5.5.3
Fan control
Read more about fan control in
Application tool
Fan
Setting alternatives
Kitchen function
Flow presentation
✓ Supply air + Extract air
✓ Supply air
✓ Extract air
Yes / No
Yes / No
Supply air fan indication ✓ None
✓ Alarm
✓ Run indication
Extract air fan indication
Extract air fan slaved by exchanger supply air flow
Flow calculation supply air K-factor
✓ None
✓ Alarm
✓ Run indication
Yes / No
Writable
Flow calculation supply air X-factor
Flow calculation extract air K-factor
Flow calculation extract air X-factor
Flow calculation exchanger supply air Kfactor
Flow calculation exchanger supply air Xfactor
Writable
Writable
Writable
Writable
Writable
Note
Note
The K-factor is usually printed on the fan
The K-factor is usually printed on the fan
The K-factor is usually printed on the fan
Corrigo manual, Rev. D 121 (196)
Information for the specialist - Configuration
Application tool
Flow calculation exchanger extract air Kfactor
Flow calculation exchanger extract air Xfactor
External flow setpoint
Step control of fans
Setting alternatives
Writable
Writable
Switch point step 1-2 SAF (%)
Switch point step 2-3 SAF (%)
Switch point step 1-2 EAF (%)
Switch point step 2-3 EAF (%)
Hysteresis (%)
Yes / No
✓ No
✓ 1 step
✓ 2 step
✓ 3 step
Writable
Writable
Writable
Writable
Writable. Default 5
Note
The K-factor is usually printed on the fan
Fan compensation curve 1, 2 and 3
Read more about the fan compensation curve in
Application tool
Fan level
Mode
Fan
Sensor
Setting alternatives
✓ All levels
✓ Low speed
✓ Normal speed
✓ High speed
✓ Low + Normal speed
✓ Normal + High speed
✓ Inactive
✓ In all modes
✓ When defrosting
✓ Supply air fan + extract air fan
✓ Supply air fan
✓ Extract air fan
✓ Outdoor temperature
✓ Intake air temperature
✓ Supply air temperature
✓ Exhaust air temperature
✓ Extract air temperature
✓ Room temperature 1…10
✓ Pressure supply air
✓ etc.
Description
External flow setpoint
Application tool
Operation mode
Setting alternatives
✓ SAF
✓ EAF
✓ SAF and EAF
Writable (default 1) Factor EAF SAF
Read more about External flow setpoint in
Note
The factor is used if there is a difference between the SAF and EAF flow properties.
122 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Support control
Set if the extract fan will be running or not during support control.
Support control is normally used when room temperature control or extract air control has been configured.
When extract air control is configured a room sensor must be installed.
Support control can also be configured to start only with the supply air fan. In this mode, the extract air fan is not active. This requires a digital output to be configured, which controls the recirculation damper to open completely so the supply air fan can circulate the air to and from the room.
Read more about support control in
Fire / Smoke
Read more about fire and smoke control in
Application tool Setting alternatives
Operation mode when fire alarm ✓ Stopped
✓ Continuous run
✓ Running via normal start/stop conditions
✓ Supply air fan run
✓ Extract air fan run
Supply air fan setpoint type when fire alarm
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Manual setpoint (Pa), (m 3 /h), (%)
Manual output (%)
Writable
Writable
Extract air fan setpoint type when fire alarm ✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Outdoor air damper function when fire alarm
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Exhaust air damper function when fire alarm
✓
✓
Normal function (follow the fan)
Always open
✓ Always closed
Fire damper mode
✓ Not active
✓ Dampers normally closed
✓ Dampers normally opened
Fire damper test
✓ No test
✓ Test when unit running
✓ Test when unit stopped
Operation mode when smoke alarm ✓ Stopped
✓ Continuous run
✓ Running via normal start/stop conditions
✓ Supply air fan run
✓ Extract air fan run
Supply air fan setpoint when smoke alarm ✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Note
Corrigo manual, Rev. D 123 (196)
Information for the specialist - Configuration
Application tool
Extract air fan setpoint when smoke alarm
Setting alternatives
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Outdoor air damper function when smoke alarm
✓
✓
Normal function (follow the fan)
Always open
✓ Always closed
Exhaust air damper function when smoke alarm
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Note
CO
2
control
Setting of the fan speed for CO
2 control on the supply and extract fan.
Read more about CO
2 control in
chapter 4.4.3 Demand controlled ventilation
Application tool Setting alternatives
Setpoint supply air fan when CO2 control ✓ Low speed
✓ Normal speed
✓ High speed
Setpoint extract air fan when CO2 control ✓ Low speed
✓ Normal speed
✓ High speed
Note
5.5.4
Recirculation
Recirculation of air using a supply air fan and (optionally) extract air fan and a recirculation damper with or without temperature control. Used as a recovery function or during heating with support control during the night. Recirculation control is available as an analog or a digital function.
Read more about recirculation in
Application tool
Enable supply air temperature control when recirculation
Setting alternatives
✓ No temperature control
✓ Heating + cooling
✓ Heating
✓ Cooling
Enable the night cooling function when recirculation
Use extra time channel 4 to start recirculation
Run extract air fan during recirculation
Yes / No
Yes / No
Yes / No
Fixed setpoint or setpoint offset when circulation run
✓ Fixed setpoint
✓ Setpoint offset
Note
5.5.5
Humidity control
It is possible to use either humidification or dehumidification, or to use combined humidification and dehumidification.
Read more about humidity control in
124 (196) Corrigo manual, Rev. D
Application tool
Select sequence for dehumidify
Type of output
Setting alternatives
Sequence A to J
✓ None
✓ Analog
✓ Step
✓ Analog + step
Information for the specialist - Configuration
Note
5.5.6
Filter monitoring
Read more about filter monitoring in
Application tool
Type
Filter placement
Filter alarm reset
Filter alarm time (month)
Filter alarm supply air limit X1 (m 3 /h)
Filter alarm supply air limit X2 (m 3 /h)
Filter alarm supply air limit Y1 (Pa)
Filter alarm supply air limit Y2 (Pa)
Filter alarm extract air limit X1 (m 3 /h)
Filter alarm extract air limit X2 (m 3 /h)
Filter alarm extract air limit Y1 (Pa)
Filter alarm extract air limit Y2 (Pa)
Setting alternatives
✓ Sensor
✓ Guard
✓ Sensor + guard
✓ Supply air
✓ Extract air
✓ Supply air + Extract air
Yes/No
Writable
Writable (Default 0)
Writable (Default 2000)
Writable (Default 10)
Writable (Default 150)
Writable (Default 0)
Writable (Default 2000)
Writable (Default 10)
Writable (Default 150)
Note
5.5.7
Extended operation
The digital inputs for extended running can be used to force the unit to start in low, normal or high speed although the timer says the running mode should be Off . This digital input has always higher priority than running via time schedule
The unit will run for the set time. If the running time is set to 0 the unit will only run as long as the digital input is closed.
Read more about extended operation in
chapter 4.10 Extended operation and External stop
Application tool
Extended operation low speed
Extended operation normal speed
Extended operation high speed
Extended operation stop delay (min)
Setting alternatives
Yes/No
Yes/No
Yes/No
Writable
Note
5.5.8
Pretreatment
Damper and pump control for preheating or precooling of the outdoor air via an underground intake channel.
Select if pretreatment should be activated during free cooling.
Corrigo manual, Rev. D 125 (196)
Information for the specialist - Configuration
Read more about pretreatment in
and about free cooling in
.
5.5.9
Extra controller
Read more about extra controller in
Application tool
Start / Stop function
Control mode
Type of freeze protection
Pump control
Pump running mode
Type of feedback
Digital start output
Extra contr. output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
Setting Alternatives
✓ Always running
✓ Unit running
✓ When defrosting
✓ Extra time channel 1…3
✓ Heating
✓ Cooling
Freeze protection temperature 1…3
Yes / No
✓ Always running
✓ Auto
✓ None
✓ Alarm
✓ Run indication
Yes / No
✓ 0
✓ 1
✓ Auto
Writable (Default 0)
Writable (Default 100)
Note
5.5.10 Extra fan motor control
Read more about extra fan motor control in
chapter 4.4.4 Extra fan motor control
Application tool
Type of feedback fan motor 1 (2)
Start/stop function fan motor 1(2)
Setting Alternatives
✓ None
✓ Alarm
✓ Run indication
✓ Digital input
✓ Unit running
✓ Extra time channel 4
Note
5.5.11 Extra indications & outputs
Application tool
Extra time channel
Run indication
Sum alarm outputs
Free cooling running
Setting alternatives
✓ No
✓ 1…4
Yes / No
✓ None
✓ A / B alarm
✓ A - alarm + B - alarm
✓ A - alarm + B / C - alarm
Yes / No
Note
126 (196) Corrigo manual, Rev. D
Application tool
Analog signal output
Information for the specialist - Configuration
Note Setting alternatives
✓ None
✓ Outdoor temperature
✓ Intake air temperature
✓ Supply air temperature
✓ Exhaust air temperature
✓ Extract air temperature
✓ Room temperature 1…16
✓ Defrosting temperature
✓ etc.
Writable (Default -50)
Writable (Default 150)
Writable (Default 0)
Temperature at Vmin (°C)
Temperature at Vmax (°C)
Alarm output
Alarm name
5.5.12 Extra sensors & inputs
Application tool
Alarm acknowledgements
Extra sensors
Extra alarm
Setting Alternatives
Yes / No
✓ No
✓ 1…5
✓ Off
✓ 1…10
Note
5.5.13 Room unit
A room unit, ED-RUx, can be configured via Application tool.
Application tool
Temperature to show in ED-RUx
Function on/off button
Fan speed extended run
Extended operation (min)
Minimum setpoint adjustment (°C)
Maximum setpoint adjustment (°C)
Setting alternatives
✓ Room temperature of the display
✓ Room temperature from sensor connected to controller
✓ Outdoor temperature
✓ Supply air temperature
✓ Extract air temperature
✓ No function
✓ Not used
✓ On / Off function
✓ On/Off/Extended operation function
✓ Low speed extended run
✓ Normal speed extended run
✓ High speed extended run
Writable (Default: 60)
Writable (Default -3)
Writable (Default 3)
Note
5.5.14 Alarms
Set the Alarm delay time at start up. Default: 60 s.
Read more about alarms in
chapter 3.6 Alarm events and alarm handling
and
Corrigo manual, Rev. D 127 (196)
Information for the specialist - Configuration
5.6 Configuration - Inputs and Outputs
Any control signal can be bound to any in- and output, the only restriction being that digital signals cannot be bound to analog inputs and vice versa. It is up to the user doing the binding to make sure that activated functions are bound to appropriate in- and outputs.
iour of the controller. Alarm 194 - Internal alarm will then become active i.
5.6.1
Analog inputs, AI
All analogue inputs are for Pt1000, Ni1000LG, Ni1000 or 0…10 V.
Input signals can be compensated e.g. for wiring resistance.
The raw value will show the actual, uncompensated input value.
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
N Mode to Off or Manual . In this case it's not necessary to configure a physical input, the application will work with the manual value instead.
The settings that can be selected / configured are:
Table 5-20 Analog inputs
Variable
Device
Settings
Terminal
Name
Signal type
Sensor type
Min input (V)
Max input (V)
Min signal (°C)
Max signal (°C)
Filter factor
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ AI 1…32
✓ UAI 1…4, 27, 28
✓ UI 1, 2
✓ Temperature
Writable
Read only
✓ Pt1000
✓ Ni1000LG
✓ Ni1000
✓ 0…10 V
Writable (Default 0)
Writable (Default 10)
Writable (Default 0)
Writable (Default 100)
Writable (Default 0,2)
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
The filter factor is the damping you want the program to work with in order to reduce the influence of potential signal fluctuations on the sensor input.
A new value is calculated using the following formula:
New value = old value * filter factor + raw value * (1 - filter factor)
Compensation (°C) Writable (Default 0)
128 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-20 Analog inputs (continued)
Variable
Mode
Manual (°C)
Actual value (°C)
Settings
✓ Off
✓ Manual
✓ Auto
Writable (Default 0)
Read only
Note
5.6.2
Digital inputs, DI
To simplify adaptation to external functions, all digital inputs can be configured to be either normally open,
NO, or normally closed, NC. The inputs are as default normally open, i. e. if the input is closed, the function connected to the input in Corrigo is activated.
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
configured to either NO or NC themselves. For example, you can choose if the fire alarm input should be activated when it is closed or opened. Therefore, there is a risk that the signal is changed twice and the result is the opposite of the desired.
The settings that can be selected / configured are:
Table 5-21 Digital inputs
Variable
Device
Terminal
Name
NC / NO
Mode
Actual value (°C)
Settings
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ DI 1…8
✓ UDI 1…4
✓ UI 1, 2
Writable
✓ NO
✓ NC
✓ Off
✓ Manual
✓ Auto
Read only
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
✓ NC (Normally closed )
✓ NO (Normally open)
5.6.3
Analog outputs, AO
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
iour of the controller. Alarm 194 - Internal alarm will then become active i.
Corrigo manual, Rev. D 129 (196)
Information for the specialist - Configuration
Table 5-22 Analog outputs
Variable
Device
Terminal
Name
Range output
Settings
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ AO 1…5
Writable
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
5.6.4
Digital outputs, DO
Digital outputs can be NC (Normally Closed) or NO (Normally Opened).
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
iour of the controller.
Alarm 194 - Internal alarm will then become active.
Table 5-23 Digital outputs
Variable
Device
Terminal
Name
NC / NO
Settings
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ DO 1…7
Writable
✓ NO
✓ NC
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
✓ NC (Normally closed )
✓ NO (Normally open)
5.7 Configuration - Raw values
Read the raw values from all I/Os for the controller and/or expansion unit.
5.8 Ventilation
tion you choose to set up. Therefore, not all menu items are available for all applications.
5.8.1
Actual / Setpoint
[Application tool ► Ventilation ► Actual/Setpoint]
Read and adjust setpoints for:
✓ Temperature
✓ Room controller
130 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
✓ Extract air controller
✓ Supply air controller
✓ Humidity
✓ CO
2
✓ Supply air fan
✓ Extract air fan
✓ Step controller
✓ Freeze protection
✓ Exchanger
Temperature
Table 5-24 Setpoints for temperature control
Variable
Actual control type
Outdoor temperature (°C)
Intake air temperature (°C)
Supply air temperature (°C)
Average room temperature (°C)
Extract air temperature (°C)
Exhaust air temperature (°C)
Setpoint adjustment (°C)
Actual setpoint supply air (°C)
Setpoint supply air (°C)
Actual setpoint room (°C)
Setpoint room air (°C)
Actual setpoint extract air (°C)
Setpoint extract air (°C)
R
R
R
R
W
R
W
R
W
R
W
R
R
Read/Write Default value
R
0
18
21
21
Min/Max Note
-20/150
-20/150
-20/150
Room controller
Table 5-25 Setpoints for room control
Variable
Room temperature (°C)
Setpoint adjustment (°C)
Setpoint offset low speed (°C)
Setpoint offset high speed (°C)
Setpoint room air (°C)
Setpoint summer room (°C)
Actual setpoint room (°C) R
Outdoor temperature limit cascade/ supply air (°C)
W
Setpoint outdoor curve X1 (°C) W
W
W
W
W
W
Read/Write Default value
R
0
0
0
21
24
13
-20
Min/Max Note
-20/150
-20/150
-20/40
-40/40
Corrigo manual, Rev. D 131 (196)
Information for the specialist - Configuration
Table 5-25 Setpoints for room control (continued)
Variable
Setpoint outdoor curve Y1 (°C)
Setpoint outdoor curve X2 (°C)
Setpoint outdoor curve Y2 (°C)
Setpoint outdoor curve X3 (°C)
Setpoint outdoor curve Y3 (°C)
Setpoint outdoor curve X4 (°C)
Setpoint outdoor curve Y4(°C)
Controller output (%)
W
W
W
W
R
Read/Write Default value
W 22
W
W
5
20
20
20
30
22
Min/Max
10/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
Note
Extract air controller
Table 5-26 Setpoints for extract air control
Variable
Extract air temperature (°C)
Setpoint adjustment (°C)
Setpoint offset low speed (°C)
Setpoint offset high speed (°C)
Setpoint extract air (°C)
Setpoint summer Extract air (°C)
Actual setpoint extract air (°C) R
Outdoor temperature limit cascade/ supply air (°C)
W
Setpoint outdoor curve X1 (°C)
Setpoint outdoor curve Y1 (°C)
W
W
Setpoint outdoor curve X2 (°C)
Setpoint outdoor curve Y2 (°C)
Setpoint outdoor curve X3 (°C)
Setpoint outdoor curve Y3 (°C)
Setpoint outdoor curve X4 (°C)
Setpoint outdoor curve Y4(°C)
Controller output (%) R
W
W
W
W
W
W
W
W
W
W
W
Read/Write Default value
R
0
0
0
21
24
13
-20
22
5
20
20
20
30
22
Min/Max Note
-10/10
-50/50
-50/50
-20/150
-20/150
-40/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
Supply air controller
Table 5-27 Setpoints for supply air control
Variable
Supply air temperature (°C)
Setpoint adjustment (°C)
Setpoint offset low speed (°C)
Setpoint offset high speed (°C)
Setpoint supply air (°C)
Read/Write Default value
R
W
W
0
0
W
W
0
18
Min/Max Note
-10/10
-50/50
-50/50
-20/150
132 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-27 Setpoints for supply air control (continued)
Variable
Setpoint summer supply air (°C)
Neutral zone (°C)
Min limit supply air
Max limit supply air
Reduction of min limit supply air if active DX-cooling (°C)
Actual setpoint supply air (°C)
Setpoint delta T extract air-supply air (°C)
Setpoint outdoor curve X1 (°C)
Setpoint outdoor curve Y1 (°C)
Setpoint outdoor curve X2 (°C)
Setpoint outdoor curve Y2 (°C)
Setpoint outdoor curve X3 (°C)
Setpoint outdoor curve Y3 (°C)
Setpoint outdoor curve X4 (°C)
Setpoint outdoor curve Y4(°C)
Controller output (%)
W
W
W
W
W
W
W
W
R
Read/Write Default value
W 24
W
W
0
12
W
W
30
5
R
W -2
-20
22
5
20
20
20
30
22
Min/Max
-20/150
0/10
10/150
10/150
0/30
-40/150
-40/40
10/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
Note
Humidity
Table 5-28 Setpoints for humidity control
Variable
Humidity outdoor (%rH)
Humidity room/extract air (%rH)
Humidity supply air (%rH)
Setpoint humidity room/extract air
(%rH)
Humidity control signal (%)
R
R
Read/Write Default value
R
W 50
R
Min/Max Note
0/100
CO
2
Table 5-29 Setpoints for CO
2 control
Variable
CO2 room/extract air (ppm)
Setpoint mixing damper (ppm)
Read/Write Default value
R
W 1000
Min/Max Note
0/2000
Corrigo manual, Rev. D 133 (196)
Information for the specialist - Configuration
Fans
Table 5-30 Setpoints for fans
Variable
Setpoint low speed supply air fan
(%)
Setpoint low speed extract air fan
(%)
Setpoint normal speed supply air fan (%)
Setpoint normal speed extract air fan (%)
Setpoint high speed supply air fan
(%)
Setpoint high speed extract air fan
(%)
Setpoint low speed supply air fan
(Pa)
Setpoint low speed extract air fan
(Pa)
Setpoint normal speed supply air fan (Pa)
Setpoint normal speed extract air fan (Pa)
Setpoint high speed supply air fan
(Pa)
Setpoint high speed extract air fan
(Pa)
Setpoint low speed supply air fan
(m 3 /h)
Setpoint low speed extract air fan
(m 3 /h)
Setpoint normal speed supply air fan (m 3 /h)
Setpoint normal speed extract air fan (m 3 /h)
Setpoint high speed supply air fan
(m 3 /h)
Setpoint high speed extract air fan
(m 3 /h)
Read/Write Default value
W 25
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
25
50
50
75
75
250
250
500
500
750
750
1000
1000
2000
2000
3000
3000
0/10000
0/10000
0/10000
0/10000
0/10000
0/10000
0/60000
0/60000
0/60000
Min/Max
0/100
0/100
0/100
0/100
0/100
0/100
0/60000
0/60000
0/60000
Note
Supply air fan
Table 5-31 Setpoints for supply air fan
Variable
Actual level
Pressure supply air (Pa)
Flow supply air (m 3 /h)
Actual setpoint compensation (Pa, m 3 /h, %)
Actual setpoint (Pa, m 3 /h, %)
Output signal (%)
R
R
R
R
Read/Write Default value
R
R
Min/Max Note
134 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-31 Setpoints for supply air fan (continued)
Variable
Bus values SAF-1…5 Frequency
(from frequency converter)
Current (from frequency converter)
(A)
Power (from frequency converter)
(W)
Error (from frequency converter)
R
R
R
Read/Write Default value
R
Min/Max Note
Extract air fan
Table 5-32 Setpoints for extract air fan
Variable
Actual level
Pressure extract air (Pa)
Flow extract air (m 3 /h)
Actual setpoint compensation (Pa, m 3 /h, %)
Actual setpoint (Pa, m 3 /h, %)
Output signal (%)
Bus values EAF-1…5 Frequency
(from frequency converter)
Current (from frequency converter)
(A)
Power (from frequency converter)
(W)
Error (from frequency converter)
R
R
R
R
R
R
R
R
Read/Write Default value
R
R
Min/Max Note
Step controller 1 and 2
Table 5-33 Setpoints for stepcontroller 1 and 2
Variable
Actual binary step
Read/Write Default value
R
Min/Max Note
Freeze protection
Table 5-34 Setpoints for freeze protection
Variable Read/Write Default value
Freeze protection temperature 1…3
(°C)
R
Min/Max Note
Corrigo manual, Rev. D 135 (196)
Information for the specialist - Configuration
Exchanger
Table 5-35 Setpoints for exchanger
Variable
Defrosting temperature (°C)
Efficiency exchanger (%)
Read/Write Default value
R
R
Min/Max Note
5.8.2
Temperature control
[Application tool ► Ventilation ► Temperature control]
Read more about temperature control in
chapter 4.2 Temperature control
Sequences
Read more about sequences in
chapter 4.3 Temperature sequences .
Table 5-36 Setpoints for sequence A to J
Variable
Digital start output start point (%)
Digital start output stop point (%)
Pump stop delay (min)
Pump-kick hour (h)
Pump running when outdoor temperature < (°C)
Hysteresis to allow pump stop (°C) W
Max fan compensation (%) W
Read/Write Default value
W 10
W
W
1
5
W
W
15
10
1
100
Min/Max
0/100
0/100
0/600
0/23
-40/100
0/100
0/100
Note
Step controller 1 and 2
Read more about step control in
.
Table 5-37 Setpoints for step controller 1 and 2
Variable
Min switch time (s)
Step 1 start point (%)
Step 1 stop point (%)
Step 2 start point (%)
Step 2 stop point (%)
Step 3 start point (%)
Step 3 stop point (%)
Step 4 start point (%)
Step 4 stop point (%) W
Block DX-cooling if outdoor temperature < (°C)
W
W
W
W
W
Read/Write Default value
W 60
W
W
W
10
5
45
40
70
65
95
90
1
Min/Max
0/300
0/100
0/100
0/100
0/100
0/100
0/100
0/100
0/100
-40/150
Note
136 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-37 Setpoints for step controller 1 and 2 (continued)
Min/Max Variable
Block step 1 if supply air fan output signal < (%)
Block step 2 if supply air fan output signal < (%)
Block step 3 if supply air fan output signal < (%)
W
W
Block step 4 if supply air fan output signal < (%)
Block step 1 if outdoor temperature
< (°C)
W
W
Read/Write Default value
W 0
0
0
0
13
Block step 2 if outdoor temperature
< (°C)
W
Block step 3 if outdoor temperature
< (°C)
W
13
13
13 Block step 4 if outdoor temperature
< (°C)
W
Block all step if outdoor temperature
< (°C)
W
Hysteresis for decreased output (%) W
0
0,5
0/100
0/100
0/100
0/100
-40/150
-40/150
-40/150
-40/150
-40/150
0/100
Note
Freeze protection 1, 2 and 3
Read more about freeze protection in
.
Table 5-38 Setpoints for freeze protection 1, 2 and 3
Variable Read/Write Default value
Alarm limitation running mode (°C) W 7
P-band running mode (°C)
Setpoint standby mode (°C)
W
W
5
25
Min/Max
-40/150
0/100
-40/150
Note
Exchanger
Read more about exchangers in
chapter 4.3.2 Exchanger (Sequence B) .
Table 5-39 Setpoints for exchanger
Variable
Start delay exchanger (s)
Start delay with 100 % exchanger
(s)
Start alarm delay (s)
Outdoor start/stop exchanger temperature (°C)
Hysteresis (°C)
Defrosting setpoint min limit (°C)
Min time deicing (min)
W
W
W
W
W
Read/Write Default value
W 0
W 2
60
10
0,2
-3
5
Min/Max
0/3600
0/3600
0/3600
-40/150
0/10
-40/150
0/60
Note
Corrigo manual, Rev. D 137 (196)
Information for the specialist - Configuration
Table 5-39 Setpoints for exchanger (continued)
Variable Read/Write Default value
W -100 Stop supply air fan if outdoor temp
< (°C)
Hysteresis to stop defrosting (°C) W 4
Min/Max
-100/150
0/10
Note
Pretreatment
Read more about pretreatment in
Table 5-40 Setpoints for Pretreatment
Variable
Pretreatment output
Activate preheater when outdoor temperature < (°C)
Activate precooler when outdoor temperature >(°C)
Hysteresis (°C)
W
W
Min difference between outdoor and intake air temperature
W
Pretreatment block time if difference below min (h)
W
Min run time (min) W
Read/Write Default value
R
W 8
19
1
1
6
5
Min/Max
-40/150
-40/150
0/10
0/20
0/24
0/600
Note
Summer mode
Read more about summer mode in
chapter Room (summer) else supply air outdoor compensated
and
Extract air (summer) else supply air outdoor compensated
.
Table 5-41 Setpoints for Summer mode
Variable
Date for start of summer period
Month for start of summer period
Date for end of summer period
Month for end of summer period
Outdoor temp for switch between summer / winter (°C)
Outdoor temp hysteresis for switch between summer / winter (°C)
Read/Write Default value
W 1
W
W
4
1
W
W
10
13
W 0,5
Min/Max
1/31
1/12
1/31
1/12
0/99
0/99
Note
5.8.3
Fan control
[Application tool ► Ventilation ► Fan control]
138 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Fans
Table 5-42 Setpoints for fans
Variable
Actual level supply air fan
Actual level extract fan
Setpoint low speed supply/extract air fan (%)
Setpoint normal speed supply/ extract air fan (%)
Setpoint high speed supply/extract air fan (%)
Setpoint low speed supply/extract air fan (Pa)
Setpoint normal speed supply/ extract air fan (Pa)
Setpoint high speed supply/extract air fan (Pa)
Setpoint low speed supply/extract air fan (m 3 /h)
W
W
W
W
W
W
Setpoint normal speed supply/ extract air fan (m 3 /h)
Setpoint high speed supply/extract air fan (m 3 /h)
W
W
Flow supply air (m 3 /h)
Flow extract air (m 3 /h)
Slave factor
Offset supply air fan when free cooling (Pa, m 3 /h, %)
Offset extract air fan when free cooling (Pa, m 3 /h, %)
W
Offset supply air fan when recirculation (Pa, m 3 /h, %)
W
Offset extract air fan when recirculation (Pa, m 3 /h, %)
W
R
R
W
W
Read/Write Default value
R
R
W 25
50
75
250
500
750
1000
2000
3000
1
0
0
0
0
Min/Max Note
0/100
0/100
0/100
0/10000
0/10000
0/10000
0/60000
0/60000
0/60000
0/1
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
Supply air fan
Table 5-43 Setpoints for supply air fan
Variable
Start delay (s)
Stop delay (s)
Speed during stop delay (%)
Speed change delay (s)
W
W
W
Outdoor air damper stop delay (s) W
Read/Write Default value
W 60
180
50
10
0
25 Min pressure for supply air fan indication (Pa)
W
Min flow for supply air fan indication
(m 3 /h)
W 500
Actual setpoint compensation (Pa) R
Min/Max
0/3600
0/3600
0/100
0/60
0/3600
0/10000
0/60000
Note
Corrigo manual, Rev. D 139 (196)
Information for the specialist - Configuration
Table 5-43 Setpoints for supply air fan (continued)
Variable
Actual setpoint compensation (m 3 / h)
Actual setpoint compensation (%) R
SAF speed min limit (%) W
SAF speed max limit (%) W
Read/Write Default value
R
0
100
Min/Max Note
Extract air fan
Table 5-44 Setpoints for extract air fan
Variable
Start delay (s)
Stop delay (s)
Speed during stop delay (%)
Speed change delay (s) W
Exhaust air damper stop delay (s) W
Min pressure for extract air fan indication (Pa)
W
Min flow for extract air fan indication
(m 3 /h)
W
Actual setpoint compensation (Pa) R
Actual setpoint compensation (m h)
3 / R
Actual setpoint compensation (%) R
EAF speed min limit (%) W
EAF speed max limit (%) W
Read/Write Default value
W 0
W
W
30
0
10
0
25
500
0
100
Min/Max
0/3600
0/3600
0/100
0/60
0/3600
0/10000
0/60000
Note
Fan compensation curve 1, 2 and 3
Read more about fan compensation in
Table 5-45 Setpoints for fan compensation curve 1, 2 and 3
Variable Min/Max
Lower point X
Read/Write Default value
W 15
Lower point Y (Pa, m 3 /h, %)
Middle point X
Middle point Y (Pa, m 3 /h, %)
Higher point X
Higher point Y (Pa, m 3 /h, %)
W
W
W
W
W
0
20
0
25
0
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
Note
140 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.8.4
Demand control
[Application tool ► Ventilation ► Demand control]
CO2
Read more about demand control and CO
2 in
chapter 4.4.3 Demand controlled ventilation
Table 5-46 Setpoints for CO2
Variable
Start limit fan start/stop (ppm)
Stop hysteresis fan start/stop (ppm) W
Demand control
Min time for CO2 control (min)
R
W
Read/Write Default value
W 800
160
20
Min/Max
0/2000
0/2000
0/600
Note
Recirculation
Read more about recirculation in
Table 5-47 Setpoints for recirculation
Variable
Setpoint recirculation (°C)
Setpoint offset recirculation (°C)
Change to outdoor air when room air > (°C)
Outdoor air damper opened
Read/Write Default value
W 18
W
W
0
25
R
Min/Max
-20/150
0/50
10/50
Note
Free cooling
Read more about free cooling in
.
Table 5-48 Setpoints for free cooling
Variable
Free cooling mode
Running when day outdoor temperature > (°C)
Read/Write Default value
R
W 22
W 18 Stop when night outdoor temperature > (°C)
Stop when night outdoor temperature < (°C)
W 10
Stop when room temperature < (°C) W
Free cooling start hour (h) W
Free cooling stop hour (h)
Time to block heat output after free cooling (min)
W
W
18
0
7
60
Fan-kick temperature check (s) W 180
Min/Max
10/40
10/40
10/40
10/40
0/23
1/24
0/600
0/3600
Note
Corrigo manual, Rev. D 141 (196)
Information for the specialist - Configuration
Table 5-48 Setpoints for free cooling (continued)
Variable
Fan-kick interval time (min)
Read/Write Default value
W
Start when extract - outdoor > (°C) W
60
2
Min/Max
0/600
1/5
Note
Support control
Read more about support control in
.
Table 5-49 Setpoints for support control
Variable
Support control mode
Min time for support control (min) W
Start heating room temperature (°C) W
Read/Write Default value
R
20
15
Stop heating room temperature (°C) W
Setpoint heating (°C) W
Start cooling room temperature (°C) W
Stop cooling room temperature (°C) W
Setpoint cooling (°C) W
21
30
30
28
12
Min/Max
0/600
10/40
10/40
-20/150
10/40
10/40
-20/150
Note
5.8.5
Fire / Smoke
[Application tool ► Ventilation ► Fire/Smoke]
Read more about fire and smoke control in
chapter 4.6.2 Fire/smoke dampers
.
Table 5-50 Setpoints for Fire/Smoke
Variable
Run fire damper (s)
Test interval fire damper (d)
Test hour fire damper (h)
Feedback fire damper
Fire damper
Status fire damper
Fire alarm
Smoke alarm
R
R
R
R
R
Read/Write Default value
W 90
W
W
1
0
Min/Max
0/300
0/7
0/24
Note d = day
5.8.6
Humidity control
[Application tool ► Ventilation ► Humidity control]
Read more about humidity control in
.
142 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-51 Setpoints for humidity control
Variable Read/Write Default value
Max limit humidity supply air (%rH) W 80
Neutral zone between humidification and dehumidification
Max deviation room/extract air humidity (%rH)
W
W
20
10
Digital output start point (%rH)
Digital output stop point (%rH)
Hysteresis for max limit humidity supply air (%rH)
W
W
W
15
5
20
Min/Max
0/100
0/100
0/100
0/100
0/100
0/100
Note
5.8.7
PID controllers
[Application tool ► Ventilation ► PID controllers]
Table 5-52 Setpoints for PID-control
Variable
Room controller
Extract air
Sequence A to J
Supply air fan
Read/Write
W
W
W
W
Extract air fan
CO2
Freeze protection 1, 2 and 3
Defrosting
Humidity
W
W
W
W
W
Default value Pband
Default value Itime (s)
100 °C
100 °C
10 °C
300
300
100
60 ✓ 500 Pa
✓ 1000 m 3 /h
(flow)
60 ✓ 500 Pa
✓ 1000 m 3 /h
(flow)
100 ppm
100 °C
16 °C
100 %rH
100
100
240
300
Default value D-time (s)
0
0
0
0
-
-
0
0
5.8.8
Energy consumption
[Application tool ► Ventilation ► Energy consumption]
SFP (Specific fan power)
Table 5-53 Setpoints for SFP
Variable
SFP (kW/m 3 /s)
SFP day average
SFP month average
Frequency converter loss
R
R
Read/Write Default value
R
R
Min/Max Note
Corrigo manual, Rev. D 143 (196)
Information for the specialist - Configuration
Power usage fans
The sum of power for all configured fans (SAF or EAF).
Table 5-54 Setpoints for power usage fans
Variable
Power usage fans (kW)
Read/Write Default value
R
Min/Max Note
Today and last 7 days
Total accumulated power usage for today and the last seven days.
Table 5-55 Setpoints for Today and last 7 days
Variable
Today (kWh)
Yesterday (kWh) R
1...6 days before yesterday (kWh) R
Read/Write Default value
R
Min/Max Note
This year
Total accumulated power usage for each month and total for the current year.
Table 5-56 Setpoints for This year
Variable
January (kWh)
February (kWh)
March (kWh) etc...
Total (kWh)
R
R
R
R
Read/Write Default value
R
Min/Max Note
Last year
Total accumulated power usage for each month and total for the previous year.
Table 5-57 Setpoints for This year
Variable
January (kWh)
February (kWh)
March (kWh) etc...
Total (kWh)
R
R
R
R
Read/Write Default value
R
Min/Max Note
144 (196) Corrigo manual, Rev. D
5.8.9
Manual / Auto
[Application tool ► Ventilation ► Manual/Auto]
Ventilation unit
Table 5-58 Settings for ventilation unit
Variable
Unit operation
Manual setpoint
Service stop
Standby mode
BMS override
Alternatives
✓ Off
✓ Manual
✓ Auto
✓ Low speed
✓ Normal speed
✓ High speed
✓ Stop
✓ Starting up
✓ Low/Normal/High speed
✓ Support heating
✓ Support cooling
✓ CO2 mode
✓ Free cooling
✓ Cool down mode
✓ Fire mode
✓ Smoke mode
✓ Recirculation mode
✓ Defrosting mode
✓ Inactive
✓ Active
✓ On
✓ Off
✓ Off
✓ Low
✓ Normal
✓ High
✓ Stop
✓ Stop with support control
✓ Free cooling
✓ Recirculation
Fan controls
Table 5-59 Settings for fan controls
Variable
Supply air fan
Alternatives
✓ Off
✓ Manual output
✓ Auto
✓ Manual setpoint
✓ Low speed
✓ Normal speed
✓ High speed
Manual setpoint (Pa, m3/ h, %)
Writable
Manual output (%)
Extract air fan
Writable
✓ Off
✓ Manual output
✓ Auto
✓ Manual setpoint
✓ Low speed
✓ Normal speed
✓ High speed
Corrigo manual, Rev. D
Information for the specialist - Configuration
Note
Note
145 (196)
Information for the specialist - Configuration
Table 5-59 Settings for fan controls (continued)
Variable Alternatives
Manual setpoint (Pa, m3/ h, %)
Writable
Manual output (%) Writable
Sequence A to J
Table 5-60 Settings for sequence A to J
Variable
Mode
Manual (%)
Actual value (%)
Alternatives
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Sequence A to J analog
Table 5-61 Settings for sequence A to J analog
Variable
Mode
Manual set (%)
Controller output (%)
Alternatives
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Note
Note
Note
Change-over 1 and 2, Supply air fan, Extract air fan, Humidity control, Step controller
1 and 2, Temperature output
Table 5-62 Settings for change-over, Supply air fan, Extract air fan, Humidity control, Step controller, Temperature output
Variable
Mode
Manual set (%)
Controller output (%)
Alternatives
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Note
Sequence A to J start, Sequence A to J pump
Table 5-63 Settings for sequence A to J start and pump
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
146 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Supply and Extract air fan start/step 1, Supply and extract air fan step 2 and 3
Table 5-64 Settings for supply and extract air fan start/Step 1, step 2 and 3
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Dampers
✓ Recirculation air damper
✓ Outdoor air damper
✓ Exhaust air damper
✓ Fire damper
Table 5-65 Settings for dampers
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Alarms
✓ Sum alarm 1
✓ Sum alarm 2
✓ Alarm output
Table 5-66 Settings for alarms
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Extra time channels 1…4
Table 5-67 Settings for extra time channels 1…4
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Note
Note
Corrigo manual, Rev. D 147 (196)
Information for the specialist - Configuration
Free cooling indication
Table 5-68 Settings for free cooling indication
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Pretreatment start
Table 5-69 Settings for Pretreatment start
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Running indication
Table 5-70 Settings for running indication
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Note
Note
Humidity control start
Table 5-71 Settings for humidity control start
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Change-over 1 and 2 (Change-over 1 and 2 start)
Table 5-72 Settings for change-over start
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
148 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Outdoor controlled exchanger
Table 5-73 Settings for outdoor controlled exchanger
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
5.8.10 Status
Status for the ventilation unit and sequences A to J.
Ventilation unit
Sequence A to J
✓ Actual mode
✓ Schedule mode
✓ External stop
✓ Extended operation
✓ Extended operation time left (min)
✓ Manual mode HMI
✓ Manual mode HMI time left (s)
✓ Free cooling mode
✓ Support control mode
✓ Night operation active last night
✓ Summer mode
✓ Fire alarm input
✓ Smoke alarm input
✓ Frost risk
✓ Internal alarm (alarm 194)
✓ Duplicated AO
✓ Duplicated DO
✓ Current configuration file
✓ Analog output (%)
✓ Start
✓ Pump
5.9 Additional function
[Application tool ► Additional function]
5.9.1
Extra controller
An extra controller (independent temperature control circuit) can be added to the Corrigo to control e.g. a separate zone. The controller can be configured to heating or cooling. All the setpoints for the extra controller are in this menu.
Read more about the extra controller in
Setpoints extra controller
Table 5-74 Actual/Setpoint
Variable
Temperature extra controller (°C)
Setpoint extra controller (°C)
Controller output (%)
Read/Write Default value
R
W
R
18
Min/Max Note
-20/150
Corrigo manual, Rev. D 149 (196)
Information for the specialist - Configuration
Table 5-75 Temperature control
Variable
Digital start output start point (%)
Digital start output stop point (%)
Pump stop delay (min)
Pump-kick hour (h)
Pump running when outdoor temperature < (°C)
W
W
W
W
Hysteresis to allow pump stop (°C) W
Read/Write Default value
W 10
1
5
15
10
1
Table 5-76 PID controller
Variable
P-band (°C)
I-time (s)
D-time (s)
Table 5-77 Manual/Auto
Variable
Controller mode
Alternatives
Manual set (%)
✓ Off
✓ Manual
✓ Auto
Writable
Writable Controller output (%)
Extra controller start mode
✓ Off
✓ Manual
✓ Auto
Read only Start
Extra controller pump mode
Start
✓ Off
✓ Manual
✓ Auto
Read only
Read/Write Default value
W 33
W 100
W 0
Min/Max
0/100
0/100
0/600
0/23
-20/150
0/10
Note
Min/Max
0/1000
0/9999
0/9999
Description
Note
5.9.2
Motor control 1 and 2
Table 5-78 Control
Variable
Stop delay motor control (min)
Read/Write Default value
W 0
Table 5-79 Manual/Auto
Variable
Mode
Alternatives
Motor
✓ Off
✓ Manual
✓ Auto
Read only
Min/Max
0/600
Note
Note
150 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.10 Inputs / Outputs
[Application tool ► Inputs/Outputs]
In this section, the values for all used Inputs and outputs are displayed.
For wireless sensors, the low battery indication and signal strength (RSSI) are displayed.
5.11 Time control
Corrigo has a year-based clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over.
It has individual schedules for each weekday plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules take precedence over other schedules.
This menu displays time, date and weekday, and it permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD.
Figure 5-10 Time channels
Each day has up to four individual running periods. For three-speed fans and pressure controlled fans there are daily individual schedules for low speed, normal speed and high speed, each with up to four running periods.
Up to 4 digital outputs can be used as timer controlled outputs . Each with individual week-schedules with two activation periods per day. These outputs can be used to control lighting, door locks etc.( Configuration ►
Digital outputs ► Extra time channel 1…4 )
Corrigo manual, Rev. D 151 (196)
Information for the specialist - Configuration
In the time schedules, four periods are available for each day of the week. Also, four periods are available for days that are configured as holidays in the holiday schedule. During the periods the assigned circuit is working with the corresponding setpoint. Outside of a period the system is off.
On On
Off
B2
Figure 5-11 Time schedule
E2
Off
B1 E1
Off
Begin/End
The above figure shows an example of period states. It is not possible for periods to overlap each other.
Holiday schedules take precedence over other schedules.
✓ For 24 hour running, set a period to 00:00 - 24:00.
✓ To inactivate a period, set the time to 00:00 - 00:00. If all periods of a day are set to 00:00 - 00:00, the unit will not run that day.
✓ If you want to run the unit from one day to another, e.g. from Monday 22:00 to Tuesday 09:00, the desired running time for both must be entered.
speed, and normal speed takes precedence over low speed.
See more about Time control in
5.11.1 Extra time channels
Up to four digital outputs can be used as timer controlled outputs. Each with individual week-schedules with four activation periods per day.
Only the time channels which have been configured, i.e. have been wired to a digital output or an additional function, will be shown.
( Configuration ► Digital outputs ► Extra time channel 1…4 )
5.11.2 Holiday calendar
The system operator can define specific periods of operation or non-operation throughout the year. During these defined periods, the settings in the week schedule do not apply. The holiday calendar includes 24 periods. All holiday periods are working with a special day plan with a maximum of 4 periods.
A holiday period can be any number of consecutive days from 1…365. The dates are in the format: MM:DD.
152 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.11.3 Time settings in display and web interface
The times can also be set using the built-in display and the web interface, see
5.12 Alarm status
5.12.1 Alarm handling
Alarms are indicated by the red alarm LED on the front of the unit or on the external display (E3-DSP or
ED-T43L-V).
All alarms can be monitored, acknowledged and blocked using the display and buttons, via an external display (E3-DSP, ED-T43L-V ), via Application tool or via the web interface. There is also a digital input for acknowledging all alarms.
The alarm settings can be changed in Application tool or in the web interface.
Table 5-80 Inputs and outputs
Inputs and outputs
DI Alarm acknowledgement
5.12.2 Alarm configuration
The alarm configuration menu permits configuration of the priority for all alarms. A complete alarm list with default settings and actions, can be found in
Appendix D Alarm list . It contains all the default alarm texts and
priorities.
Priority
Alarms can be given different priority levels A-alarm , B-alarm and C-alarm or Not active . Digital outputs can be bound to act as alarm outputs for A-alarms or B/C-alarms or both A- and B/C-alarms. The digital outputs can be inverted, so that an inoperative alarm gives a high output and vice versa. A- and B- alarms must be acknowledged to reset. C- alarms automatically reset as soon as there is no longer a cause for alarm.
The alarm priority that is shown in the display in the event of an alarm can only be changed using
Application tool.
Alarm text
The alarm text that is shown in the display in the event of an alarm can be changed using Application tool or the web interface.
Stop function
Each alarm offers the possibility to choose whether an activated alarm should stop the controller or not. The controller can also be set to run at reduced speed during alarms. The latter option can only be configured using Application tool. Automatic restart will take place when the alarm has been acknowledged.
For some alarm types such as electric heating high temperature limit and water heating frost protection it would be dangerous to not stop the unit on alarm. Therefore, for such alarm types, the program will always reset the stop function to Active even if the operator should choose Inactive .
Corrigo manual, Rev. D 153 (196)
Information for the specialist - Configuration
Unfortunately it is not possible to remove the display text concerning the stop function for these alarm types. This is because the available program space demands that all alarms are treated in the same way in the display.
ttiivvee, or unexpected malfunctions may occur.
Sum alarm
There are two sum alarm functions with two digital outputs:
Inputs and outputs
DO
DO
Sum alarm 1
Sum alarm 2
The function of the outputs can be individually configured in Configuration ► Functions ► Extra indications & outputs .
Sum alarm outputs
None
A/B-alarm
A-alarm + B-alarm
A-alarm + B/C-alarm
DO Sum alarm 1
Not available
Active on A/B-alarm
Active on A-alarm
Active on A-alarm
DO Sum alarm 2
Not available
Not available
Active on B-alarm
Active on B/C-alarm
Alarm output
There is one alarm output function with configurable alarm connected to one digital output:
Inputs and outputs
DO Alarm output
External alarms
There are 11 possible external alarms. One digital input called External alarm and 10 digital inputs called
Extra alarm .
5.13 Starting and stopping the Corrigo
5.13.1 Start and stop conditions in priority
The unit will start and stop depending on the following conditions in this priority:
1. Service stop (only via display with admin authority)
2. Run in fire mode
3. Stop in fire mode
4. Run in smoke mode
5. Stop in smoke mode
6. Stop due to alarm
7. External stop (DI)
154 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
8. Low/normal/high speed due to alarm
9. Start high speed (DI)
10.Start normal speed (DI)
11.Start low speed (DI)
12.Start recirculation (DI)
13.External start/stop (via communication), support control (heat / cool / CO
2
) is enabled if external stop with support control is selected
14.Start recirculation (via communication)
15.Start free cooling (via communication)
16.Start/stop in manual mode (off, low, normal, high), manual mode, only one variable used in display,
Modbus, BACnet etc.
17.Start high speed via time channel
18.Start normal speed via time channel
19.Start low speed via time channel
20.Start support control (heat / cool / CO
2
) via normal start condition
21.Start recirculation via time channel
22.Start free cooling via normal start condition
Possibility to block automatic restart at power - on
The function Automatic restart at power-on makes it possible to block automatic restart of the unit at powerup. At power-up, the B-alarm Restart blocked after power on is generated.
Once this alarm has been acknowledged, the unit will start. ( Configuration ► Functions ► Function activation )
5.13.2 Start sequence
Start of the unit will run according to the following sequence:
1. If the controller is configured for water heating and has an outdoor temperature sensor and the outdoor temperature is below a configurable temperature (Full heat at start when outdoor temp is below, default: +3 ºC) the heating valve is opened and the heating circulation pump is started (sequence for heat start is configurable). ( Configuration ► Functions ► Sequence settings )
2. Signals for outdoor air and exhaust air dampers are activated.
3. If the controller is configured with a heat exchanger the heat exchanger will be run at 100% capacity
(sequence for normal start is configurable) for a pre-set time (Start delay with 100% exchanger, default
2 s). ( Ventilation ► Temperature control ► Exchanger )
4. The extract air fan or the pressure control of the extract air fan will be started after a preset time
(Extract air fan start delay, default 0 s).( Ventilation ► Fan control ► Extract air fan ► Start delay (s) )
5. The supply air fan or the control of the supply air pressure will be started after a preset time (Supply air fan start delay, default 60 s).( Ventilation ► Fan control ► Supply air fan ► Start delay (s) )
6. Thereafter temperature control according to the configured control mode is started. Electric heating, if configured, is not started until a run signal from the supply air fan or flow switch has been received.
And not yet activated pumps will be started.
7. When all fans and pumps is running and exchanger has run for a pre-set time a pre-set delay (Start alarm delay, default 60s) will be activated before the alarm handling system is activated and the unit is in normal running mode. ( Configuration ► Functions ► Alarms )
Corrigo manual, Rev. D 155 (196)
Information for the specialist - Configuration
5.13.3 Stop sequence
Stopping of the unit will run according to the following sequence:
1. Deactivation of the alarm handling system.
2. Electric heating, if configured, is shut down.
3. After individually set delay times the fans are stopped; Supply air fan stop delay (Default 180 s),
Extract air fan stop delay (Default 30 s) ( Ventilation ► Fan control ► Extract/Supply air fan ► Stop delay
(s) )
4. Outdoor air and exhaust air dampers are shut down. Outdoor air damper close delay: 0-300 seconds
(Default: 0 s), Exhaust air damper close delay: 0-300 seconds (Default: 0 s)( Ventilation ► Fan control ►
Extract/Supply air fan ► Stop delay (s) )
5. Actuator signals are set to zero and the pumps are stopped.
6. If shutdown mode (Frost protection when stopped) is configured, it will be activated.
exchanger will continue to run during the stop sequence until everything else is stopped
5.14 Changing the battery
The controller has an internal battery to ensure the operation of the memory and real-time clock in the event of a power failure. When the alarm Internal Battery is activated and the battery LED lights up red (24 V models), the battery has become too weak and needs to be changed. Nonetheless, due to a backup capacitor, the controller will function at least 10 minutes without power supply.
proper ESD protection. Therefore, this should be handled by qualified personnel.
An earthed wristband must be used during this procedure.
5.14.1 24 V models (Corrigo Ardo)
1. Remove the cover by pressing down the locking torques at the edge of the cover using a small screwdriver, and at the same time pulling the cover outwards.
156 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
2. Grip the battery firmly with your fingers and lift it upwards until it rises from its holder.
3. Press the new battery firmly down into place.
type CR2032.
5.14.2 230 V models (Corrigo Vido)
The 230 V models should not be opened by the user. Please contact Regin if you need to change the battery.
Corrigo manual, Rev. D 157 (196)
6 Information for the installer
6.1 Installation
6.1.1
Corrigo Ardo (24 V)
The controller can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet or, using a suitable front-mounting kit, in a cabinet door or other control panel.
Figure 6-1 Corrigo Ardo voltage.
instructions given in this manual.
Wiring examples Corrigo Ardo
For a complete list of terminals, see
The pictures below show examples for 24 V Corrigo Ardo
158 (196) Corrigo manual, Rev. D
Figure 6-2 Wiring example
Inputs and outputs 24 V Corrigo Ardo
There is a list of input and outputs in
Appendix C Input and output lists
that can be used to help you keep track of which inputs and outputs you need to configure.
Analog inputs
Analogue inputs must refer to an Agnd terminal.
Analogue inputs can, depending on the configuration, be used for either PT1000 / Ni1000 temperature sensors or for 0…10 V DC analogue input signals, for example from a pressure transmitter.
Digital inputs
Digital inputs must refer to +C on terminal 4. Digital inputs may only be wired to voltage-free contacts. Any external voltage applied to a digital input may harm the unit.
Universal inputs
A universal input can be configured to act as either an analogue input or as a digital input.
A universal input configured as an analogue input can, depending on the configuration, be used for either
PT1000 / Ni1000 temperature sensors or for 0…10 V DC analogue input signals, for example from a pressure transmitter.
Universal inputs configured as an analogue input must refer to an Agnd terminal.
A universal input configured as a digital input must, just like other digital inputs refer to C+ on terminal 4. It may only be wired to voltage-free contacts.
Corrigo manual, Rev. D 159 (196)
Analog outputs
Analogue outputs must refer to a Agnd terminal.
All analogue outputs can be individually set to any one of the following output signals:
✓ 0…10 V DC
✓ 2…10 V DC
✓ 10…0 V DC
✓ 10…2 V DC the same transformer pole is used as reference for all the equipment. The equipment may otherwise not function as intended and may also suffer damages.
Digital outputs
Digital outputs should normally refer to G
DO on terminal 10.
G
DO is internally connected to G on terminal 1 and supplies 24 V AC or DC depending on the choice of supply voltage.
All the digital outputs are controlled by MOSFET transistors. The outputs are internally connected with G
0 and can deliver max 2 A per output. However, the total power for all the DOs must not exceed 8 A.
A number of different wiring alternatives are possible depending on the type of supply voltage to the controller and the relay type.
Figure 6-3 24 V AC supply and 24 V AC relays
Figure 6-4 24 V DC supply and 24 V DC relays
160 (196) Corrigo manual, Rev. D
Figure 6-5 24 V AC supply and 24 V DC relays
Figure 6-6 24 V DC supply and 24 V AC relays
6.1.2
Corrigo Vido (230 V)
The controller can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet or, using a suitable front-mounting kit, in a cabinet door or other control panel. The 230 V ( Corrigo Vido) models can also be mounted directly on a wall.
Corrigo manual, Rev. D 161 (196)
8x Pt1000 / Ni1000
UI3
UI4
DI1
DI2
AO1
AI1
AI2
AI3
AI4
UI1
UI2
17
18
19
20
21
22
23
24
25
26
27 0..10V In/Out
AO2
Gnd
AO3
28
29
30
0..10V In/Out
0..10V Out / PWM*
31 B
MBUS*
32 A
N
N
L
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
DO7
DO6
DO5
DO4
DO3
DO2
DO1
TCP/IP E N
P1
A B ext.
Display
Figure 6-7 Corrigo Vido
* Depending on model voltage.
instructions given in this manual.
Inputs and outputs 230 V Corrigo Vido models
There is a list of input and outputs in Appendix C Input and output lists
that can be used to help you keep track of which inputs and outputs you need to configure.
Analog inputs
Analog inputs must refer to a ground, Gnd, terminal.
Analog inputs are intended for use with PT1000 / Ni1000 sensors as a temperature sensor.
Digital inputs
Digital inputs must refer to a ground, Gnd, terminal.
Universal inputs
A universal input can be configured to act as either an analogue input or as a digital input.
162 (196) Corrigo manual, Rev. D
A universal input configured as an analogue input can be used with PT1000 / Ni1000 temperature sensors.
A universal input configured as an analogue input must refer to a ground, Gnd, terminal.
A universal input configured as a digital input must refer to a ground, Gnd, terminal.
Universal analog
Universal analog I/O:s can be configured as either analog inputs or analog outputs.
Analog outputs must refer to a ground, Gnd, terminal. The outputs can be individually set to any one of the following output signals:
✓ 0…10 V DC
✓ 2…10 V DC
✓ 10…0 V DC
✓ 10…2 V DC
Digital outputs
The relays are voltage-free and must receive power from a single pole for each relay.
Figure 6-8
6.1.3
Expansion units EXOline
The communication between master and expansion units takes place via EXOline. The slave units will be assigned the address 241:1 and 241:2 during initialisation (PLA:ELA).
Corrigo manual, Rev. D 163 (196)
Figure 6-9 Expansion units EXOline
6.2 Commissioning
Before the controller can be used, inputs and outputs as well as a number of parameters must be configured.
All configuring must be done in Application tool that can be downloaded from http://www.regincontrols.
com or in the web interface.
6.2.1
Configuration using Application tool
Application tool is a PC-based, free configuration software tool, available at Regin's website www.
regincontrols.com
The tool is used to configure and commission the controller .
The controller doesn't need to be connected to the computer while configuring. All settings are made in the tool and then uploaded to the controller.
An infinite number of configurations can be stored in the computer memory for later use.
A communication cable is required in order to upload the configuration to the controller. The controller must also be powered up and the application selected in order for it to be configured.
Predefined configurations can be downloaded as atf-files from Regin’s website, www.regincontrols.com
.
These atf-files can be opened in the tool and synchronized to the controller.
6.2.2
Configuration in the web interface
When the Corrigo is connected to an external display or computer with a browser and a connection to the internet, an internal web interface will be shown. The web interface can be used to configure, change setpoints, and monitor the controller.
164 (196) Corrigo manual, Rev. D
Figure 6-10 Start screen for the web interface
6.3 Loading the application
Reset the controller by pressing the reset button, using for example a paper clip.
Figure 6-11 Resetting the controller
Corrigo manual, Rev. D 165 (196)
Load the application into the controller and commission. The application is loaded from Application tool.
In Application tool, go to the Tools menu at the top and select Reload controller .
166 (196) Corrigo manual, Rev. D
Appendix A Technical data
A.1 Corrigo Ardo
A.1.1
General data
Supply voltage
Power consumption
Ambient temperature
Ambient humidity
Storage temperature
24 V AC (21…27 V AC 50…60 Hz / 20…36 V DC
See
Table B-2 in Appendix B Model overview
0…50 °C
Max. 95 % RH
-20…70 °C
Protection class
Connection
Memory backup
Display
Mounting
Casing
Dimensions (WxHxD)
Battery type
Battery life
Operating system
IP20
Disconnectable terminal strips, 4 mm 2
Built-in long life battery gives long backup time of all settings incl. real time
Backlit LCD, 4 rows of 20 characters
DIN-rail or cabinet
Standard Euronorm (8.5 modules wide)
149 x 121 x 60 mm incl. terminals
CR2032 replaceable Lithium cell
Min. 5 years
EXOrealC
A.1.2
Communication ports
TCP/IP
RS485
EXOline, Modbus, BACnet/IP, CLOUDigo
EXOline, Modbus, BACnet MS/TP
A.1.3
Inputs & Outputs
Analog inputs (AI)
Digital inputs (DI)
Universal inputs (UI)
Analog outputs (AO)
Digital outputs (DO)
For PT1000, Ni1000, Ni1000LG sensors (accuracy ± 0.4 °C) or 0…10 V DC (accuracy ± 0.15 % of full output signal). 12 bit resolution in the A/D conversion.
For potential-free contacts
Can be set to act as either analog input or digital input with specifications as above
0…10 V DC, 1 mA, short-circuit protected
Mosfet outputs, 24 V AC or DC, 2 A continuous. Max. 8 A in total.
Corrigo manual, Rev. D 167 (196)
A.2 Corrigo Vido
A.2.1
General data
Supply voltage
Power consumption
Ambient temperature
Ambient humidity
Storage temperature
Protection class
Memory backup
Display
Mounting
Dimensions (WxHxD)
Battery type
Battery life
Operating system
85…265 V AC, 50/60 Hz
See
in
0…50 °C
Max. 95 % RH
-20…70 °C
IP20, IP40 when mounted in cabinet
Built-in long life battery gives long backup time of all settings incl. real time
Backlit LCD, 4 rows of 20 characters
DIN-rail, cabinet or on wall
146.7 x 97.6 x 76.0 mm incl. terminals
CR2032 replaceable Lithium cell
Min. 8 years
EXOrealC
A.2.2
Communication ports
TCP/IP
RS485
EXOline, Modbus, BACnet/IP, CLOUDigo
EXOline, Modbus, BACnet MS/TP
A.2.3
Inputs & Outputs
Analog inputs (AI)
Digital inputs (DI)
Universal inputs (UI)
Analog inputs/outputs (UA)
Digital outputs (DO)
For PT1000, Ni1000, Ni1000LG sensors. 12 bit resolution in the A/D conversion.
For potential-free contacts
Can be set to act as either analogue inpue or digital input with specifications as above
Configurable as output (0…10 V DC, 2…10 V DC, 10…0 V DC or 10…2 V DC, 8 bit D/A (shortcircuit protected) or input (0…10 V DC)
7x relay, 230 V AC, 1 A load per relay, max 7 A total
168 (196) Corrigo manual, Rev. D
Appendix B Model overview
B.1 Corrigo Ardo - Model overview
Table B-1 Corrigo Ardo and Expansion units (24 V)
Name
VCA152DW-4
VCA152W-4
VCA283DW-4
VCA283W-4
IO-A15MIXW-3-BEM
IO-A19MIXW-1-BEM
IO-A28MIXW-3-BEM
Voltage
24 V
24 V
24 V
Description
Ardo Controller with one RS485 port and one TCP/IP port
Ardo Controller with two RS485 ports and one TCP/IP port
Ardo Expansion unit with one RS485 port
Table B-2 Corrigo Ardo inputs, outputs, ports, display, power consumption
Name AI
VCA152DW-4
VCA152W-4
VCA283DW-4
VCA283W-4
IO-A15MIXW-3-BEM 4
IO-AV19MIXW-1-BEM 4
IO-A28MIXW-3-BEM 4
4
4
4
4
DI
8
8
4
4
4
2
8
UI*
4
4
-
-
-
4
4
AO
5
5
3
3
3
2**
5
DO
7
7
4
4
4
7
7
2
2
1
1
1
1
1
RS485 ports
1
1
1
1
1
1
1
TCP/IP ports
-
-
-
-
-
-
-
M-Bus ports
Display
-
-
-
-
-
Power consumption (VA)
9
5
5
9
5
7.5
5
* Universal inputs can be configured to function as either analog or digital outputs.
** Universal analog that can be configured to function as either analog inputs or analog outputs (0…10 V
DC).
B.2 Corrigo Vido - Model overview
Table B-3 Corrigo Vido and expansion unit (230 V)
Name
VCV203DW-2
IO-A15MiXW-3-BEM
IO-V19MIXW-1-BEM
IO-A28MIXW-3-BEM
Voltage
230 V
230 V
Description
Vido Controller with one RS485 port and one TCP/IP port
Vido Expansion unit with one RS485 port
Table B-4 Corrigo Vido inputs, outputs, ports, display, power consumption
Name AI DI UI* AO DO RS485 ports
TCP/IP ports
M-Bus ports
VCV203DW-2 4
IO-A15MiXW-3-BEM 4
IO-V19MIXW-1-BEM 4
IO-A28MIXW-3-BEM 4
2
4
2
8
4
4
4
-
2**
3
2**
5
7
7
7
4
1
1
1
1
1
1
1
1
-
-
-
-
* Universal inputs can be configured to function as either analogue or digital outputs.
-
-
-
Display Power consumption (VA)
11
5
7.5
5
Corrigo manual, Rev. D 169 (196)
** Universal analogue that can be configured to function as either analogue inputs or analogue outputs (0…
10 V DC).
170 (196) Corrigo manual, Rev. D
Appendix C Input and output lists
The lists below are intended to be used as a memory aid during configuration, in order to help keep track of the desired input and output functions.
The left column contains the name of the in-/output signal, the middle column displays the name of the corresponding signal in Application tool and the right column shows the text displayed in the controller.
C.1 Analog inputs
Name
Outdoor temperature sensor
Intake air temperature sensor
Supply air temperature sensor
Exhaust air temperature sensor
Extract air temperature sensor
Room temperature sensor 1
Room temperature sensor 2
Room temperature sensor 3
Room temperature sensor 4
Room temperature sensor 5
Room temperature sensor 6
Room temperature sensor 7
Room temperature sensor 8
Room temperature sensor 9
Room temperature sensor 10
Room temperature sensor 11
Room temperature sensor 12
Room temperature sensor 13
Room temperature sensor 14
Room temperature sensor 15
Room temperature sensor 16
Pressure transmitter supply air
Pressure transmitter extract air
Flow transmitter supply air
Flow transmitter extract air
Flow transmitter exchanger supply air
Exchanger EAF pressure transmitter
De-icing temperature heat exchanger
Frost protection temperature sensor 1
Frost protection temperature sensor 2
Frost protection temperature sensor 3
CO2/VOC sensor
Room humidity transmitter (% RH)
Supply air humidity transmitter (% RH)
Outdoor air humidity transmitter (% RH)
Temperature extra controller
Corrigo manual, Rev. D
Name in Application tool
Outdoor temperature
Intake air temperature
Supply air temperature
Exhaust air temperature
Extract air temperature
Room temperature 1
Room temperature 2
Room temperature 3
Room temperature 4
Room temperature 5
Room temperature 6
Room temperature 7
Room temperature 8
Room temperature 9
Room temperature 10
Room temperature 11
Room temperature 12
Room temperature 13
Room temperature 14
Room temperature 15
Room temperature 16
Pressure supply air
Pressure extract air
Flow supply air
Flow extract air
Flow exchanger supply air
Pressure exchanger extract air
Defrosting temperature
Freeze protection temperature 1
Freeze protection temperature 2
Freeze protection temperature 3
CO2 room/extract air
Humidity room/extract air
Humidity supply air
Humidity outdoor
Extra controller temperature
Description
171 (196)
Name
External control signal SAF (%)
External control signal EAF (%)
Extra sensor 1
Extra sensor 2
Extra sensor 3
Extra sensor 4
Extra sensor 5
External supply setpoint (PT1000)
External Setpoint airflow (m3/h)
Filter supply pressure transmitter
Filter extract pressure transmitter
Efficiency temperature sensor exchanger
Name in Application tool
External control supply air fan
External control extract air fan
Extra sensor 1
Extra sensor 2
Extra sensor 3
Extra sensor 4
Extra sensor 5
External setpoint temperature
External setpoint flow
Pressure filter supply air
Pressure filter extract air
Efficiency temperature exchanger
Description
C.2 Digital inputs
Name
Supply air fan motor protection/run indication
Extract air fan motor protection/run indication
Extended operation low speed
Extended operation normal speed
Extended operation high speed
Fire alarm
Smoke alarm
External alarm
Fire damper end-switch monitoring
Feedback/Indication Sequence A
Feedback/Indication Sequence B
Feedback/Indication Sequence C
Feedback/Indication Sequence D
Feedback/Indication Sequence E
Feedback/Indication Sequence F
Feedback/Indication Sequence G
Feedback/Indication Sequence H
Feedback/Indication Sequence I
Feedback/Indication Sequence J
Electric heating is overheated
External stop
Acknowledge all alarms
Flow switch
De-icing exchanger
Rotation exchanger
Frost protection thermostat
Start Recirculation Run
Change over signal 1, switches between heating=0 and cooling=1 on the output signal
Name in Application tool
Feedback supply air fan
Feedback extract air fan
Extended operation low speed
Extended operation normal speed
Extended operation high speed
Fire alarm
Smoke alarm
External alarm
Feedback fire damper
Feedback sequence A
Feedback sequence B
Feedback sequence C
Feedback sequence D
Feedback sequence E
Feedback sequence F
Feedback sequence G
Feedback sequence H
Feedback sequence I
Feedback sequence J
Overheated electric heater
External stop
Alarm acknowledgement
Flow guard
Defrosting guard exchanger
Rotary exchanger alarm
Freeze protection guard
Start/(Stop) recirculation
Cooling/(heating) Change-over 1
Description
172 (196) Corrigo manual, Rev. D
Name
Change over signal 2, switches between heating=0 and cooling=1 on the output signal
Filter guard 1 supply air
Filter guard 2 extract air
Motor control 1 start
Motor control 2 start
Motor control 1 protection/run indication
Motor control 2 protection/run indication
Extra alarm 1
Extra alarm 2
Extra alarm 3
Extra alarm 4
Extra alarm 5
Extra alarm 6
Extra alarm 7
Extra alarm 8
Extra alarm 9
Extra alarm 10
Freeze supply PID
Summer mode
Feedback/Indication extra controller
Name in Application tool
Cooling/(Heating) Change-over 2
Description
Filter guard supply air
Filter guard extract air
Start/(Stop) extra fan motor 1
Start/(Stop) extra fan motor 2
Feedback extra fan motor 1
Feedback extra fan motor 2
Extra alarm 1
Extra alarm 2
Extra alarm 3
Extra alarm 4
Extra alarm 5
Extra alarm 6
Extra alarm 7
Extra alarm 8
Extra alarm 9
Extra alarm 10
Lock PID controller supply
Summer/(Winter) mode
Feedback extra controller
C.3 Universal inputs
Universal inputs on the controller can be individually configured as either analog inputs, using any of the analog input signals above, or as digital inputs, using any of the digital inputs above.
C.4 Analog outputs
Name
Sequence A output in (%)
Sequence B output in (%)
Sequence C output in (%)
Sequence D output in (%)
Sequence E output in (%)
Sequence F output in (%)
Sequence G output in (%)
Sequence H output in (%)
Sequence I output in (%)
Sequence J output in (%)
Change over 1 (%)
Change over 2 (%)
Control signal Supply air fan in (%)
Control signal Extract air fan in (%)
Name in Application tool
Sequence A
Sequence B
Sequence C
Sequence D
Sequence E
Sequence F
Sequence G
Sequence H
Sequence I
Sequence J
Change-over 1
Change-over 2
Supply air fan
Extract air fan
Description
Corrigo manual, Rev. D 173 (196)
Name
Control valve Humidity (%)
Step Controller 1 (%)
Step Controller 2 (%)
Extra controller (%)
AI Signal output (%)
C.5 Digital outputs
Name
Sequence A Start
Sequence B Start
Sequence C Start
Sequence D Start
Sequence E Start
Sequence F Start
Sequence G Start
Sequence H Start
Sequence I Start
Sequence J Start
Sequence A Pump Start
Sequence B Pump Start
Sequence C Pump Start
Sequence D Pump Start
Sequence E Pump Start
Sequence F Pump Start
Sequence G Pump Start
Sequence H Pump Start
Sequence I Pump Start
Sequence J Pump Start
Sequence A PWM
Sequence B PWM
Sequence C PWM
Sequence D PWM
Sequence E PWM
Sequence F PWM
Sequence G PWM
Sequence H PWM
Sequence I PWM
Sequence J PWM
Sequence A actuator increase
Sequence B actuator increase
Sequence C actuator increase
Sequence D actuator increase
174 (196)
Name in Application tool
Humidity control
Step controller 1
Step controller 2
Extra controller
Temperature output
Description
Name in Application tool
Sequence A start
Sequence B start
Sequence C start
Sequence D start
Sequence E start
Sequence F start
Sequence G start
Sequence H start
Sequence I start
Sequence J start
Sequence A pump
Sequence B pump
Sequence C pump
Sequence D pump
Sequence E pump
Sequence F pump
Sequence G pump
Sequence H pump
Sequence I pump
Sequence J pump
Sequence A PWM
Sequence B PWM
Sequence C PWM
Sequence D PWM
Sequence E PWM
Sequence F PWM
Sequence G PWM
Sequence H PWM
Sequence I PWM
Sequence J PWM
Sequence A increase
Sequence B increase
Sequence C increase
Sequence D increase
Description
Corrigo manual, Rev. D
Name
Sequence E actuator increase
Sequence F actuator increase
Sequence G actuator increase
Sequence H actuator increase
Sequence I actuator increase
Sequence J actuator increase
Sequence A actuator decrease
Sequence B actuator decrease
Sequence C actuator decrease
Sequence D actuator decrease
Sequence E actuator decrease
Sequence F actuator decrease
Sequence G actuator decrease
Sequence H actuator decrease
Sequence I actuator decrease
Sequence J actuator decrease
Start supply air fan/Start step 1 supply air fan
Start step 2 supply air fan
Start step 3 supply air fan
Start extract air fan/ Start step 1 extract air fan
Start step 2 extract air fan
Start step 3 extract air fan
Recirculation air close-off damper
Outdoor air close-off damper
Exhaust air close-off damper open/close fire dampers
Sum alarm 1
Sum alarm 2
Alarm output
Start motor control 1
Start motor control 2
Time Channel 1
Time Channel 2
Time Channel 3
Time Channel 4
Free Cool Run
Pretreatment
Run indication
Step Controller 1 output step 1
Step Controller 1 output step 2
Step Controller 1 output step 3
Step Controller 1 output step 4
Step Controller 2 output step 1
Step Controller 2 output step 2
Step Controller 2 output step 3
Name in Application tool
Sequence E increase
Sequence F increase
Sequence G increase
Sequence H increase
Sequence I increase
Sequence J increase
Sequence A decrease
Sequence B decrease
Sequence C decrease
Sequence D decrease
Sequence E decrease
Sequence F decrease
Sequence G decrease
Sequence H decrease
Sequence I decrease
Sequence J decrease
Supply air fan start/step 1
Supply air fan step 2
Supply air fan step 3
Extract air fan start/step 1
Extract air fan step 2
Extract air fan step 3
Recirculation air damper
Outdoor air damper
Exhaust air damper
Fire damper
Sum alarm 1
Sum alarm 2
Alarm output
Extra fan motor 1 start
Extra fan motor 2 start
Extra time channel 1
Extra time channel 2
Extra time channel 3
Extra time channel 4
Free cooling indication
Pretreatment start
Running indication
Step controller 1 step 1
Step controller 1 step 2
Step controller 1 step 3
Step controller 1 step 4
Step controller 2 step 1
Step controller 2 step 2
Step controller 2 step 3
Corrigo manual, Rev. D
Description
175 (196)
Name
Step Controller 2 output step 4
Start Dehumidifier/Humidifier
Start Change over 1
Start Change over 2
Outdoor temperature controlled Exchanger
Start Extra control unit
Extra controller pump start
Name in Application tool
Step controller 2 step 4
Humidify control start
Change-over 1 (Change-over 1 start)
Change-over 2 (Change-over 2 start)
Outdoor controlled exchanger
Extra controller start
Extra controller pump
Description
176 (196) Corrigo manual, Rev. D
Appendix D Alarm list
The alarm text, priority and delay columns show the factory set values.
19
20
17
18
15
16
13
14
21
22
23
D.1
No
1
4
5
2
3
6
7
8
9
10
11
Alarm text
Malfunction supply air fan 1
Malfunction supply air fan 2
Malfunction supply air fan 3
Malfunction supply air fan 4
Malfunction supply air fan 5
Malfunction extract air fan 1
Malfunction extract air fan 2
Malfunction extract air fan 3
Malfunction extract air fan 4
Malfunction extract air fan 5
Alarm supply air fan 1
12 Alarm supply air fan 2
B
B
B
B
B
A
B
B
B
B
Prio
B
A
Alarm supply air fan 3
Alarm supply air fan 4
Alarm supply air fan 5
Alarm extract air fan 1
Alarm extract air fan 2
Alarm extract air fan 3
Alarm extract air fan 4
Alarm extract air fan 5
Warning supply air fan 1
Warning supply air fan 2
Warning supply air fan 3
A
A
A
A
A
A
A
A
C
C
C
Delay
120 s
120 s
120 s
120 s
120 s
120 s
120 s
120 s
120 s
120 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
Limit Default action Description
Malfunction supply air fan 1
Malfunction supply air fan 2
Malfunction supply air fan 3
Malfunction supply air fan 4
Malfunction supply air fan 5
Malfunction extract air fan 1
Malfunction extract air fan 2
Malfunction extract air fan 3
Malfunction extract air fan 4
Malfunction extract air fan 5
Alarm from frequency converter
SAF via Modbus communication
Alarm from frequency converter
SAF 2 via Modbus communication
Alarm from frequency converter
SAF 3 via Modbus communication
Alarm from frequency converter
SAF 4 via Modbus communication
Alarm from frequency converter
SAF 5 via Modbus communication
Alarm from frequency converter
EAF 1 via Modbus communication
Alarm from frequency converter
EAF 2 via Modbus communication
Alarm from frequency converter
EAF 3 via Modbus communication
Alarm from frequency converter
EAF 4 via Modbus communication
Alarm from frequency converter
EAF 5 via Modbus communication
Warning from frequency converter SAF 1 via Modbus communication
Warning from frequency converter SAF 2 via Modbus communication
Warning from frequency converter SAF 3 via Modbus communication
Corrigo manual, Rev. D 177 (196)
Alarm text
Warning supply air fan 4
Warning supply air fan 5
Warning extract air fan 1
Warning extract air fan 2
Warning extract air fan 3
Warning extract air fan 4
Warning extract air fan 5
External operation supply air fan
External operation extract air fan
Extra fan motor 1 running
C
C
-
Extra fan motor 2 running -
Malfunction pump heater
Malfunction pump cooler
Malfunction pump exchanger B
B
B
Malfunction fire damper
Malfunction damper
Malfunction extra fan motor 1 -
Malfunction extra fan motor 2 -
Testing fire damper C
Malfunction sequence A
Malfunction sequence B
Malfunction sequence C
Malfunction sequence D
Malfunction sequence E
Malfunction sequence F
Malfunction sequence G
Malfunction sequence H
Malfunction sequence I
Malfunction sequence J
B
B
-
-
-
-
-
-
-
-
-
-
C
C
C
C
C
C
Prio
C
29
30
40
41
42
43
44
49
50
51
52
45
46
47
48
33
34
35
36
37
38
39
31
32
27
28
No
24
25
26
0 s
0 s
0 s
0 s
0 s
0 s
120 s
120 s
120 s
120 s
5 s
5 s
20 s
5 s
90 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
120 s
120 s
0 s
Delay
0 s
Limit Default action Description
Warning from frequency converter SAF 4 via Modbus communication
Warning from frequency converter SAF 5 via Modbus communication
Warning from frequency converter EAF 1 via Modbus communication
Warning from frequency converter EAF 2 via Modbus communication
Warning from frequency converter EAF 3 via Modbus communication
Warning from frequency converter EAF 4 via Modbus communication
Warning from frequency converter EAF 5 via Modbus communication
SAF run-signal received when unit is stopped
EAF run-signal received when unit is stopped
External operation of motor control 1
External operation of motor control 2
Malfunction pump, heating circuit
Malfunction pump, cooling circuit
Malfunction pump, liquid connected exchanger
Fire damper exercise test failed
Normal stop
Malfunction damper (via
Modbus)
Malfunction in extra fan motor control 1
Malfunction in extra fan motor control 2
The unit is stopped due to exercise on fire damper.
Malfunction sequence A
Malfunction sequence B
Malfunction sequence C
Malfunction sequence D
Malfunction sequence E
Malfunction sequence F
Malfunction sequence G
Malfunction sequence H
Malfunction sequence I
Malfunction sequence J
178 (196) Corrigo manual, Rev. D
No
53
Alarm text
Filter alarm supply air
54 Filter alarm extract air
Alarm low air flow
Freeze protection guard
Defrosting guard exchanger
Fire alarm
Smoke alarm
External stop
External alarm
Service stop
C
Electric heating is overheated A
B
B
A
A
Warning freeze protection B
B
A
-
Low efficiency exchanger
Defrosting alarm
Rotary exchanger alarm
Extra alarm 1
Extra alarm 2
Extra alarm 3
Extra alarm 4
Extra alarm 5
Extra alarm 6
Extra alarm 7
Extra alarm 8
Extra alarm 9
Extra alarm 10
Internal battery error A
Alarm service interval C
Restart blocked after power on B
-
-
-
-
-
B
-
-
-
-
-
B
-
Deviation alarm supply air temp.
B
Deviation alarm supply air fan -
Deviation alarm extract air fan -
Deviation alarm humidity control
-
Deviation alarm extra controller -
81
82
83
84
85
65
66
71
72
73
74
67
68
69
70
75
76
77
78
79
80
58
59
60
61
62
63
64
55
56
57
Prio
B
B
0 s
0 s
0 s
0 s
0 s
0 s
0 s
5 s
0 s
0 s
Delay
180 s
180 s
30 min
2 s
0 s
0 s
0 s
0 s
20 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
30 min
30 min
30 min
30 min
30 min
Limit
CURVE
CURVE
50 %
10 °C
50 Pa
50 Pa
10 %
10 °C
Default action Description
Filter alarm supply air pressure switch or analogue filter switch activated. The analogue filter switch may be flow dependent.
Normal stop
Fast stop
Filter alarm extract air pressure switch or analogue filter switch activated. The analogue filter switch may be flow dependent.
Flow switch activated
Fast stop
Fast stop
Normal stop
External frost protection thermostat activated
Exchanger deicing pressure switch activated
Fire alarm activated
Smoke detector activated
"External stop" activated
Normal stop
Normal stop
External alarm activated
Service stop activated
Heater high temperature limit switch activated
Frost protection function is overriding the control of the heater output
Heat exchanger efficiency below limit value
Exchanger deicing activated by deicing sensor
Exchanger rotation guard alarm
Extra alarm 1 on digital input
Extra alarm 2 on digital input
Extra alarm 3 on digital input
Extra alarm 4 on digital input
Extra alarm 5 on digital input
Extra alarm 6 on digital input
Extra alarm 7 on digital input
Extra alarm 8 on digital input
Extra alarm 9 on digital input
Fast stop
Extra alarm 10 on digital input
Internal battery needs replacing
Time for service
Restart blocked due to earlier power failure
Supply air temp deviates too much from the setpoint
Supply air pressure deviates too much from the setpoint
Extract air pressure deviates too much from the setpoint
The room humidity deviates too much from the setpoint
Extra unit temp deviates too much from the setpoint
Corrigo manual, Rev. D 179 (196)
89
90
No
86
87
88
91
107
108
109
110
101
102
103
104
105
106
111
112
113
114
97
98
99
100
92
93
94
95
96
115
Alarm text
High supply air temperature
Low supply air temperature
Supply air temperature max limit
Supply air temperature min limit
High room temperature B
B
-
Prio
B
-
Low room temperature B
High extract air temperature B
Low extract air temperature B
High outdoor air temperature -
Low outdoor air temperature -
Freeze protection alarm 1 A
Freeze protection alarm 2 A
Freeze protection alarm 3 A
High temperature extra sensor
1
Low temperature extra sensor
1
High temperature extra sensor
2
Low temperature extra sensor
2
High temperature extra sensor
3
Low temperature extra sensor
3
High temperature extra sensor
4
Low temperature extra sensor
4
High temperature extra sensor
5
Low temperature extra sensor
5
High temperature selected sensor 1
Low temperature selected sensor 1
High temperature selected sensor 2
Low temperature selected sensor 2
Manual operation air handling unit
Manual operation supply air
-
-
-
-
-
-
-
-
-
-
-
-
-
-
C
C
Manual operation supply air fan C
Delay
5 s
5 s
0 s
0 s
30 min
30 min
0 s
0 s
0 s
0 min
0 min
0 min
0 min
0 min
0 min
0 min
0 min
0 min
0 min
0 min
0 min
0 s
0 s
0 min
0 min
30 min
30 min
0 min
0 min
0 s
30 °C
10 °C
0 °C
0 °C
0 °C
0 °C
30 °C
10 °C
30 °C
10 °C
30 °C
10 °C
30 °C
10 °C
Limit
30 °C
10 °C
30 °C
10 °C
30 °C
10 °C
40 °C
-30 °C
Default action Description
Supply air temp too high
Supply air temp too low
Fast stop
Fast stop
Fast stop
Maximum limiting of supply air temp active
Minimum limiting of supply air temp active
Room temp too high during room temp control
Room temp too low during room temp control
High extract air temp during extract air control
Low extract air temp during extract air control
Outdoor temperature is too high
Outdoor temperature is too low
Frost protection temperature 1 below frost limit value
Frost protection temperature 2 below frost limit value
Frost protection temperature 3 below frost limit value
High temperature extra sensor 1
Low temperature extra sensor 1
High temperature extra sensor 2
Low temperature extra sensor 2
High temperature extra sensor 3
Low temperature extra sensor 3
High temperature extra sensor 4
Low temperature extra sensor 4
High temperature extra sensor 5
Low temperature extra sensor 5
High temperature 1 on selected sensor
Low temperature 1 on selected sensor
High temperature 2 on selected sensor
Low temperature 2 on selected sensor
The unit is in manual mode
Supply air temp controller in manual control
Supply air fan in manual control
180 (196) Corrigo manual, Rev. D
145
146
147
148
149
139
140
141
142
143
144
123
124
125
126
131
132
133
134
127
128
129
130
135
136
137
138
119
120
121
122
No
116
117
118
Alarm text
Manual operation extract air fan
Manual operation heater
Manual operation exchanger
C
C
Prio
C
Manual operation cooler
Manual operation damper
Manual operation pump heater C
C
C
Manual operation pump exchanger
C
Manual operation pump cooler C
Manual operation damper recirc.
Manual operation damper outdoor air
C
C
Manual operation damper exhaust air
C
Manual operation fire damper C
Manual control sequence A -
Manual control sequence B -
Manual control sequence C -
Manual control sequence D -
Manual control sequence E -
Manual control sequence F -
Manual control sequence G -
Manual control sequence H -
Manual control sequence I -
Manual control sequence J -
Output in manual operation C
Input in manual operation C
Manual operation extra controller
Manual operation ext. fan motor 1
C
C
Manual operation ext. fan motor 2
C
Manual operation pretreatment C
Sensor error outdoor air temperature
B
Sensor error intake air temperature
Sensor error supply air temperature
Sensor error exhaust air temperature
Sensor error extract air temperature
B
B
B
B
Sensor error room temperature
1
B
Corrigo manual, Rev. D
5 s
5 s
5 s
5 s
5 s
0 s
0 s
0 s
0 s
0 s
5 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
Delay
0 s
0 s
0 s
Limit Default action Description
Extract air fan in manual control
The heater is in manual mode
Heat exchanger output in manual control
Cooling output in manual control
Damper output in manual control
Heating circulation pump in manual control
Exchanger circulation pump in manual control
Cooling circulation pump in manual control
Recirculation air damper in manual control
Fresh air damper in manual control
Exhaust air damper in manual control
Fire dampers in manual control
Manual control of sequence A
Manual control of sequence B
Manual control of sequence C
Manual control of sequence D
Manual control of sequence E
Manual control of sequence F
Manual control of sequence G
Manual control of sequence H
Manual control of sequence I
Manual control of sequence J
Analogue or digital output in manual mode
Analogue or digital input in manual mode
Extra controller in manual mode
Motor control 1 in manual mode
Motor control 2 in manual mode
Pretreatment in manual mode
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
181 (196)
172
173
174
175
176
177
178
179
159
160
161
162
155
156
157
158
163
164
No
150
151
152
153
152
165
166
167
168
169
170
171
Alarm text Prio
Sensor error room temperature
2
B
Sensor error room temperature
3
B
Sensor error room temperature
4
B
Sensor error room temperature
5
B
Sensor error room temperature
6
B
Sensor error room temperature
7
B
Sensor error room temperature
8
B
Sensor error room temperature
9
B
Sensor error room temperature
10
B
Sensor error room temperature
11
B
Sensor error room temperature
12
B
Sensor error room temperature
13
B
Sensor error room temperature
14
B
Sensor error room temperature
15
B
Sensor error room temperature
16
B
B Sensor error pressure supply air
Sensor error pressure extract air
Sensor error flow supply air
B
B
Sensor error flow extract air
Sensor error flow exch. supply air
Sensor error press. exch. extr.
air
Sensor error defrosting temperature
B
B
B
B
B Sensor error freeze protect.
temp. 1
Sensor error freeze protect.
temp. 2
B
Sensor error freeze protect.
temp. 3
B
Sensor error CO2 room/extract air
B
Sensor error humidity room/ extr. air
Sensor error humidity supply air
B
B
Sensor error humidity outdoor B
Sensor error extra controller B
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
Delay
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
Limit Default action Description
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
182 (196) Corrigo manual, Rev. D
188
189
190
191
192
193
194
No
180
181
182
183
184
185
186
187
Alarm text
Signal error external control
SAF
Signal error external control
EAF
Sensor error extra sensor 1
Sensor error extra sensor 2
Sensor error extra sensor 3
Sensor error extra sensor 4
Sensor error extra sensor 5
Sensor error external temp.
setpoint
Signal error external flow setpoint
Sensor error press. filter supp.
air
Sensor error press. filter extr.
air
Sensor error efficiency temp.
exch.
Communication fault device
Malfunction extra controller
Internal error
B
B
B
B
B
C
C
C
B
B
B
B
B
B
Prio
B
5 s
5 s
5 s
5 s
0 s
5 s
60 s
Delay
5 s
5 s
5 s
5 s
5 s
5 s
5 s
5 s
Limit Default action Description
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Malfunction in connected sensor
Communication error to a device
Malfunction in connected sensor
Internal error
Corrigo manual, Rev. D 183 (196)
Appendix E Terminal lists
E.1 Corrigo Ardo (24 V models)
Terminal
12
13
14
15
16
17
30
10
11
3
4
31
32
33
1
2
41
42
43
34
35
40
44
45
50
51
52
53
I/O
Power supply G+
Power supply G0-
Earth
DI common +C
DO common GDO
DO1
DO2
DO3
DO4
DO5
DO6
DO7
Analogue ground
AI1
AI2
Analogue ground
AI3
AI4
Analogue ground
UAI1
UAI2
Analogue ground
UAI3
UAI4
Port 1 B
Port 1 A
Port 1 N
Port 1 E
184 (196)
Hardware model
A15 A28
-
-
-
-
-
-
-
✓ *
✓ *
✓ *
✓ *
✓ *
✓ *
✓ *
✓ *
Notes
Corrigo manual, Rev. D
77
78
90
72
73
74
75
76
60
61
62
63
71
91
92
93
94
95
* Depending on the model
AO1
AO2
AO3
AO4
AO5
Port 2 B
Port 2 A
Port 2 N
Port 2 E
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Analogue ground
✓ *
✓ *
✓ *
✓ *
-
-
-
-
-
-
E.2 Corrigo Vido (230 V models)
✓ *
✓ *
✓ *
✓ *
8x Pt1000 / Ni1000
AI1
AI2
AI3
AI4
UI1
UI2
UI3
UI4
DI1
DI2
AO1
AO2
Gnd
17
18
19
20
21
22
23
24
25
26
27
28
29
0..10V In/Out
0..10V In/Out
AO3 30
0..10V Out / PWM*
31 B
MBUS*
32 A
N
N
L
12
11
10
9
8
16
15
14
13
7
6
5
4
3
2
1
DO7
DO6
DO5
DO4
DO3
DO2
DO1
TCP/IP E N
P1
A B ext.
Display
* Depending on the model
Corrigo manual, Rev. D 185 (196)
Terminal I/O
16
25
26
27
22
23
24
28
29
17
18
19
20
21
30
31
32
8
9
10
11
12
13
14
15
6
7
4
5
1
2
3
* Depending on the model
DO1
Common DO1/DO2
DO2
-
DO3
Common DO3/DO4
DO4
-
DO5
Common DO5/DO6
DO6
-
DO7
Common DO7
Power supply L
Power supply N
AI1
AI2
AI3
AI4
UAI1
UAI2
UAI3
UAI4
DI1
DI2
UA1
UA2
Analogue ground
AO3
MBUS A
MBUS B
Hardware model
V19
-
-
-
-
✓ *
✓ *
V20
-
-
-
Note
186 (196) Corrigo manual, Rev. D
Frequency converters and EC controllers for heat exchangers
Appendix F Frequency converters and EC controllers for heat exchangers
There is support for the following frequency converters and/or EC controllers:
✓ Vacon NXL
✓ Lenze
✓ Omron V1000
✓ Emerson Commander
✓ LS
✓ EBM-PAPST
✓ Danfoss FC 101
✓ ABB ACS
✓ EC Blue
For Heat exchangers via Modbus:
✓ Eltwin A/S EC controller, RHC 200
✓ VariMax25
✓ OJ DHRX
When communicating via frequency converters through Modbus, it is sometimes necessary to change certain settings in the frequency converter.
2103
2105
2106
2107
1501
2110
2111
2101
F.1 Vacon NXL
No settings necessary. Vacon NXL frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read:
The following signals can be read/written from/to the frequency converter:
Address
2003
2001
11
80
Modbus register
32003, 42003
32001, 42001
30011, 40011
30080, 40080
32103, 42103
32105, 42105
32106, 42106
32107, 42107
31501, 41501
32110, 42110
32111, 42111
32101, 42101
Name Scaling
FB speed reference (SP) 1000
FB status word -
Acc.. motor output
Number of decimals for acc. motor output
FB motor speed
1
1
Motor speed
Current
Torque
Output
100
1
100
Voltage DC
Alarm
FB status word
1
-
-
10
1000
Type
%
Binary kW kWh
%
± Rpm
A
± % (of nominal) kW
V
Error code
Binary
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
Corrigo manual, Rev. D 187 (196)
Frequency converters and EC controllers for heat exchangers
✓ Current (A)
✓ Accumulated power (kWh)
F.2 Lenze
No settings necessary. Lenze frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
528
509
511
506
30
27
49
50
45
2
512
Modbus register
32049, 42049
32050, 42050
30045, 40045
30002, 40002
32512, 42512
32528, 42528
32509, 42509
32511, 42511
31506, 41506
32110, 42110
32027, 42027
Name Scaling
Password
Parameter version
-
-
FB speed reference (SP) 50
FB status word
Acc. motor output
Motor frequency
Current
-
1
10
1
Output
Voltage DC
Alarm
FB status word
1000
1
-
-
Type
-
-
%
Binary kW
Hz
A kW
V
Error code
Binary
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
F.3 Omron V1000
Connection via RS485:
Omron V1000
R+
R-
R+ / S+
R- / Sconnected to connected to connected to connected to
Corrigo
S+
S-
B on Port 1 or Port 2
A on Port 1 or Port 2
F.3.1
Parameters
The following parameters must be set from the display of the frequency converter:
Parameter
H5-01 (0 x 425)
H5-07 (0 x 42B)
Description
Slave address
RTS control
Set to value
1
2
1 (enabled)
Value
Supply air fan
Exhaust air fan
Activation of RS485
188 (196) Corrigo manual, Rev. D
Frequency converters and EC controllers for heat exchangers
Parameter o1-03 (0 x 502)
H5-03 (0 x 427)
Description
Frequency reference units
Parity
Set to value
1
0
Value
0 - 100 %
No parity
Default values should be used for remaining parameters. The following values may not be changed:
Parameter
H5-02 (0 x 426)
H5-04 (0 x 428)
H5-11 (0 x 43C)
H5-12 (0 x 43D) b1-01 (0 x 180)
Description
Communication speed
Set to
3 (default)
Stopping method after communication error
3 (default)
Communication Enter function 1 (default)
Run command 0 (default)
Value
9600
No stop
Enter command not necessary bit 0 = forward start/stop, bit 1 = reverse start/stop
Via Modbus b2-01 (0 x 181)
Frequency reference selection
1
Run command selection 1
2 (default)
2 (default) Via Modbus
Omron frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
38
33
34
63
39
40
Address
3
2
36
93
Modbus register
30003, 40003
30002, 40002
30036, 40036
30063, 40063
30039, 40039
30040, 40040
30038, 40038
30033, 40033
30034, 40034
30093, 40093
Name Scaling
FB Speed reference (SP) 10
Password
Motor frequency
-
100
Motor speed
Current
Output
DC voltage
Status change
Alarm
1
10
10
10
-
-
Acc. Motor output 1
Type
%
-
Hz
± Rpm
A kW
V
Binary
Binary kW
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
F.4 Emerson Commander
Connection between RS485 and RJ45:
RJ45
2 (orange)
7 (white/brown) connected to
B on Port 1 or Port 2
A on Port 1 or Port 2
Corrigo manual, Rev. D 189 (196)
Frequency converters and EC controllers for heat exchangers
F.4.1
Termination resistor
✓ If using a termination resistor, it should be connected between RJ45:1 (white/orange) and RJ45:8
(brown).
resistor and try again.
F.4.2
Terminals
Terminal
B4
B5
Description
Drive enabled
Forward
Corrigo
B2 (+ 24 V)
B2 (+ 24 V)
F.4.3
Parameters
The following parameters must be set from the display of the frequency converter:
Parameter
44
43
Description
Slave address
Baud rate
Set to value
1 (default)
2
9.6 (Default is 19.2)
Value
Supply air fan
Exhaust air fan
Address
114
18
1038
615
501
2
504
402
503
505
1040
F.4.4
Changing parameters
1. Deactivate the unit by opening terminal B4. The display should read "iH 0.0".
2. Set parameter 10 to L3 . All parameters up to and including 95 can then be altered.
3. Set parameter 43 to 9.6
(9600 Baud)
Emerson frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
Modbus register
30114, 40114
30018, 40018
31038, 41038
30615, 40615
30501, 40501
30002, 40002
30504, 40504
30402, 40402
30503, 40503
30505, 40505
31040 41040
Name
Speed selection
Scaling
-
FB speed reference (SP) 10
FB status word
Control switch
-
-
Motor frequency
Max speed
10
10
Motor speed
Current
Output
Voltage DC
Status change
1
10
10
1
-
Type
-
%
-
Binary
Hz
Hz
+/- Rpm
A kW
V
Binary
190 (196) Corrigo manual, Rev. D
Frequency converters and EC controllers for heat exchangers
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
F.5 LS
LS frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
F.5.1
LS iG5A
The following signals can be read/written from/to the frequency converter:
Address
5
6
10
31
21
9
13
12
14
15
29
Modbus register
30005,40005
30006,40006
30010,40010
30031,40031
30029,40029
30009,40009
30013,40013
30012,40012
30014,40014
30015,40015
30029,40029
Name Scaling
FB speed reference (SP) 10
FB status word
Motor frequency 100
100 Torque
RPM
Motor current
Output
Voltage
1
10
10
10
Status change
Alarm
Alarm 2
-
-
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
F.5.2
LS iS7
The following signals can be read/written from/to the frequency converter:
791
786
784
790
Address
5
6
10
Modbus register
30005,40005
30006,40006
30010,40010
30791,40791
30786,40786
30784,40784
30790,40790
Name Scaling
FB speed reference (SP) 10
FB status word
Motor frequency
-
100
Torque
RPM
Motor current
Output
100
1
10
10
Type
%
Binary
Hz
%
Rpm
A kW
V
Binary
Binary
Binary
Type
%
Binary
Hz
%
Rpm
A kW
Corrigo manual, Rev. D 191 (196)
Frequency converters and EC controllers for heat exchangers
Address
789
14
816
817
Modbus register
30789,40789
30014,40014
30816,40816
30817,40817
Name
Voltage
Status change
Alarm
Alarm 2
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
-
-
Scaling
10
-
Type
V
Binary
Binary
Binary
F.6 EBM-PAPST
EBM frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
53250
53249
53265
53266
53267
53268
53269
Modbus register
30250,40250
30249,40249
30265,40265
30226,40266
30267,40267
30268,40268
30269,40269
Name Scaling
FB speed reference (SP) 640
FB control word -
RPM
FB status word -
Status change
DC voltage
Motor current
Type
%
Rpm
Binary
Binary
V
A
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
F.7 EC Blue
ECBlue frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
3
5
15
16
Modbus register
30003,40003
30005,40005
30015,40015
30016,40016
Name Scaling
FB speed reference (SP) 1
FB control word -
RPM
Current 100
Type
%
0 = off
3 = on
Rpm
A
192 (196) Corrigo manual, Rev. D
Frequency converters and EC controllers for heat exchangers
Address
34
21
13
Modbus register
30034,40034
30021,40021
30013,40013
Name
Output
DC voltage
Alarm
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
1
-
Scaling
1
Type kW
V
Error code
F.8 Danfoss FC 101
Danfoss frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
3100
50000
16130
16140
16100
16300
16030
Modbus register
33100,43100
350000,450000
316130,416130
316140,416140
316100,416100
316300,416300
316030,416030
Name Scaling
FB speed reference (SP) 100
FB control word -
Motor frequency 10
Current
Output
DC voltage
Status change
1
-
100
1000
Type
%
Hz
A kW
V
The variables presented in the display of the Corrigo are:
✓ Frequency (Hz)
✓ Output (kW)
✓ Current (A)
✓ Accumulated power (kWh)
2
3
F.9 Eltwin A/S EC controller (for heat exchangers), RHC 200
Communication takes place using address 7, 9600 bps, 8 bits, no parity and 1 stop bit.
Version 1.01, 2015-04-03
Address
1
Modbus register
30001
30002
30003
Name
Running mode
Speed
Supply voltage
1
-
Scaling
-
Type
Bit 0 = Operation0:
Stop1: Run
Bit 3 = Reset1: Reset
0…100.0 %
V(RMS)
Corrigo manual, Rev. D 193 (196)
9
10
11
12
13
14
15
5
6
7
8
Frequency converters and EC controllers for heat exchangers
Address
4
Modbus register
30004
Name
Error code
Scaling
1
30005
30006
30007
30008
30009
30010
30011
30012
30013
30014
30015
Speed output
Voltage output
Motor current, DC link
Motor output
Supplied power
Running time
Max. speed
Min. speed
Program version
Hardware version
Application version
1
1
1
10
1
1
1
1
1
1
1
RPM
RPM
ID
ID
ID mA
W
W h
Type
Bit 0: Excess current/
Ground fault
Bit 1: Excess current from DC link 265V~
Bit 2: Undervoltage from
DC link 170V~
Bit 3: Hardware error
Bit 4: External error, input
Bit 5: Overload
Bit 6: Overheating, stop
Bit 7: Overheating, reduced
Bit 8: Rotor cover error
Bit 9: Rotor cover input
Bit 10: DIP 1
Bit 11: DIP 2
Bit 12: DIP 3
Bit 13: DIP 4
Bit 14: Not used
Bit 15: Communication error
RPM
Volt
F.10 VariMax25M
Communication takes place using address 16, 9600 bps, 8 bits, no parity and 1 stop bit.
1
1
Address
1
Modbus register
40001
30001
10001
Name
Program version
Scaling
100
Setpoint
Alarm acknowledgement
10
Type
0…100.0 %
1
194 (196) Corrigo manual, Rev. D
Corrigo manual, Rev. D 195 (196)
last page
HEAD OFFICE AB Regin, Box 116, SE-428 22 Kållered • Visiting address: Bangårdsvägen 35, SE-428 36 Kållered
Phone: +46 (0)31 720 02 00 • Fax: +46 (0)31 720 02 50 • [email protected] • www.regincontrols.com
Download
Advertisement
Key features
Control heating and ventilation for a comfortable indoor climate
Two analog inputs for sensors or other signals
Two digital inputs for external control
Two relay outputs for controlling fans or dampers
LCD display and user-friendly menu structure for easy setup
Compact size and DIN rail mounting for easy installation
Frequently asked questions
The control functions are easily set up via the LCD display and the user-friendly menu structure.
The controller is compact and DIN rail mounted.
The controller can be installed in electrical cabinets or other confined spaces.