Yaskawa A1000 Closed Loop Operation Motor drive Cheat Sheet
Oglas
Oglas
The following procedure is a supplement to other documentation supplied with this equipment and will guide the user in properly wiring the
A1000, motor and encoder. It will also show the user how to configure the
A1000 in closed loop mode operation using a
PG-X3 card for a dedicated applications.
Danger: Improper wiring can and
will cause bodily harm as well as damage to the equipment.
When installing the system, be sure to follow good wiring practices and all applicable codes.
Ensure that the mounting of components is secure and that the environment, such as extreme dampness, poor ventilation, etc. will not cause system degradation.
Step
1
A1000 Model
Identification and Mounting
To make sure you received the correct model, it is essential to verify the A1000 nameplate with your order and make sure the A1000 has the correct rating so it can be used with your motor. Please check the nameplate information as shown in the example below.
Drive Spec Number
Drive Model
Number
Input Power
Rating
Output
Power
Rating
Weight
Serial
Number
UL File
Number
Normal /
Heavy Duty
Amps
Software
Version
· Check that the available power will meet the input
power requirements.
· Ensure that the output power from the A1000 is compatible with the motor requirements.
· In the case of systems with more than one A1000, follow the above procedure for each A1000 and motor.
Mounting the A1000
The mounting of the A1000 is extremely important regarding environment and accessibility. Depending on your system, there are various models available and the mounting dimensions (footprint) may be different. Because the mounting procedure is fairly extensive, it is beyond the scope of this document; the user is referred to the A1000 User
Manual (Document No. SIEP C710606 21A) received with the A1000, Section 2.2 Mechanical Installation. Match the model that you received and follow the procedure described in the manual to ensure a safe and functional installation. In cases where the system has more than one A1000, refer to the proper clearances required for adequate ventilation.
Please pay particular attention to:
· The clearances to be maintained around the enclosure for adequate ventilation.
· The environmental specifications such as avoiding excessive dampness, extreme temperatures, chemical exposure, corrosive areas, etc. to avoid damage to the equipment and to maintain safety.
Removing and Attaching the Terminal Cover
Improper removal of the A1000 terminal cover as well as front cover can cause extensive damage to the A1000. To avoid damage to these items, please pay particular attention to the A1000 User Manual, Document No. SIEP C710606
21A, Section 3.5, Removing and Attaching the Terminal
Cover.
Please read this cheat sheet and other documentation provided with the
A1000 thoroughly before attempting any installation.
NEMA 1
Open Chassis
A1000 Cheat Sheet (Closed Loop Operation)
Step
2
Connect Motor and
Line Power
Fig.1 & 2 below show the electrical connections for the input power and motor terminals for various A1000 models.
Select the proper diagram for the model you are installing
(see Step 1). WITH POWER OFF make the appropriate connections.
Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is grounded properly as shown in fig. 1
!
DANGER; LETHAL VOLTAGES ARE PRESENT- Before applying power to the A1000, ensure that the terminal cover is fastened and all wiring connections are secure.
After the power has been turned OFF, wait at least five minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components.
WARNING DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
B1 B2
-
+1 +2 +3
DC Bus terminals location varies by model.
Page 1 of 3
Step
3
Install PG-X3 Feedback Card and wire encoder feedback
In this step the PG-X3 encoder feedback card is installed. WITH POWER OFF install the PG-X3 card as shown below. Make sure to follow good wiring practices and all applicable codes. Ensure that the feedback card is grounded properly as shown in fig. 3 item H.
This option card can be inserted into either the CN5-B or CN5-C connectors located on the drive’s control board. If only one option card is connected to the drive, use the CN5-C connector. If two option cards are connected, use both CN5-B and CN5-C.
See the A1000 User Manual, Document No. SIEP C710606 21A, Section 3.5, for directions on removing the front cover.
PG-X3 Option Card
D
E
F
G
A
B
C
– Terminal block TB1
– Ground terminal (installation hole)
– Jumper for PG power supply voltage (CN3)
– Terminal block TB2
– Model number
– Installation hole
– Connector (CN5)
Option Card Installation
Insert the PG-X3 card (connector CN5) into the matching CN5 connector on the A1000 control card. Next use the screws to fasten the card into place. Connect one of the ground lead lines to the ground terminal with one of the screws. Two separate ground lead lines have been included with the option card. Use the longer one when the option card is plugged into connector CN5-C on the
A1000 control card side and use the shorter one if the PG-X3 card is plugged into connector CN5-B.
(R/L1)
(S/L2)
Connect to chassis ground
Input
Protection
(Fuse or Circuit
Breaker)
To change direction of motor rotation swap any two of the three motor leads
(See Step 2)
L1 L2 L3
Connect frame to ground
Use L1, L2 for
*
Use L1, L2, L3 for
3Ø Induction
1Ø Input Power 3Ø Input Power motor
Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 2_0004 - 2_0056, 4_0002 - 4_0044 and 5_0003 - 50011
NOT USED
(R/L1)
Input
Protection
(Fuse or Circuit
Breaker)
(T/L3)
(S/L2)
(T/L3)
Connect to chassis ground
(U/T1)
(U/T1)
(V/T2)
(W/T3)
BUS TERMINALS:
DO NOT CONNECT TO GROUND
(W/T3)
(V/T2)
To change direction of motor rotation swap any two of the
three motor leads
(See Step 2)
L1 L2 L3
Connect frame to ground
Use L1, L2 for
1Ø Input Power *
Use L1, L2, L3 for
3Ø Induction
3Ø Input Power motor
Fig. 2 Input Power and Output Motor Electrical Connections for
*
Models: 2_0110 & Larger and 4_0058 & Larger
Make sure the A1000 has been properly sized for single phase input power. For best performance, the drive input supply voltage must be at least equal to or greater than the motor rated voltage.
Fig. 3
Ground Lead
D
E
F
G
H
A
B
C
K
L
I
J
– Connector CN5-C
– Connector CN5-B
– Connector CN5-A
– Drive grounding terminal (FE)
– Insert connector CN5 here
– Option card
– Mounting screw
– Lead line Ground
– Use wire cutters to create an opening for cable lines
– Front cover
– Digital Operator
– Terminal cover
Encoder Power Supply
(Max. 200mA)
Select Encoder Power Supply
(IP + IG TB2) with Jumper CN3.
!
Default
IMPORTANT: Verify Encoder
Power Supply Rating
Encoder
Power
Encoder Connection
A single channel encoder can only be used in V/f + PG control mode (A1-02 = 1). It is required to use a quadrature encoder in Flux Vector control mode (A1-02 = 3).
Connect Encoder (PG) signals to TB1 terminals of the PG-X3 card as shown below.
Connect power supply from the PG-X3 card (TB1 – Terminals IP and IG) to the Encoder (PG).
TB2 PG-X3 Terminals TB2 PG-X3 Terminals
+
IP IG
-
SG a+ ab+ b- z+ z+
TB1
A+ AB+ BZ+ Z-
PG
Encoder
Signals
SD FE
Encoder
Power
+
IP IG
-
SG a+ ab+ b- z+ z+
TB1
A+ AB+ BZ+ Z-
PG
SD FE
Encoder Signals
Single Channel Feedback (A Only)
Set F1-37 = 0 (default)
Suitable only for
V/f with Feedback.
Quadrature / Dual Channel Feedback (A & B)
Set F1-37 = 1
(Required for FLUX Vector Operation)
Suitable for V/f or Flux Vector with Feedback.
PG-X3 Encoder Wiring
Step
4
Check Motor Rotation in Open Loop
(Motor uncoupled from Load)
In this step the motor is checked for proper direction and operation.
This test is to be performed solely from the digital operator. Apply power to the A1000 after all the electrical connections have been made and protective covers have been re-attached. At this point,
DO NOT RUN THE MOTOR , the Digital Operator should display as shown in Fig. 3.
Press
Green LED turns on.
Motor Rotation Test
First Digit
Flashing
Fig. 3
Digital Operator
Next, press to move the cursor one position to the right and to increase the frequency reference (d1-01) to 10.00 Hz.
Press to save frequency reference.
10.00 Hz
Next, press on the Digital Operator. The motor should now be operating at low speed running in the correct forward (clockwise) direction.
Next, press on the Digital Operator.
If motor rotation is not correct, then either reverse “Phase
Order” using parameter b1-14 or power down the drive, wait five minutes and swap 2 motor leads.
!
DANGER
After the power has been turned OFF, wait at least five minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components.
Digital Operator turned off.
Use precaution, and refer to Fig.1 or 2, swap any two of the three output leads to the motor
(U/T1, V/T2 and W/T3).
After the wiring change, repeat Step 3 and recheck motor direction.
A1000 Cheat Sheet (Closed Loop Operation)
Step
5
Changing Parameters and
Monitoring the A1000
This step shows how to access and modify a A1000 parameter as well as how to monitor A1000 signals such as output frequency and motor current.
Make sure all protective covers have been re-attached and power is turned on. DO NOT RUN THE MOTOR.
Access Parameter Menu and Change Parameter Value
Press two times until the digital operator shows the parameter menu.
2X
Inc./Dec. Selection
2X
Go to Next Digit
Select Digit
Inc./Dec. Selection
Page 2 of 3
Step
6
Rotational Auto-Tuning Closed Loop
(De-couple Motor from Load)
In this step the A1000 is setup for use with the motor in closed loop operation. Make sure the following has been done:
· Encoder (PG) connected correctly to the PG-X3 Card
· All protective covers have been re-attached
· Ensure the motor can spin freely and any connected mechanical brake is released
· Connected machinery should be allowed to rotate the motor
IMPORTANT:
To achieve optimal drive performance use rotational Auto-Tuning with the load decoupled from the motor. If motor and load can not be decoupled, reduce the motor load so that it is no greater than 30% of the rated load. Performing rotational Auto-Tuning with a higher load can result in incorrect motor parameters and may cause irregular motor rotation.
Next apply power to the A1000. DO NOT RUN THE MOTOR.
Select Closed Loop Control Method
Select Closed Loop Control Method A1-02
V/f with PG
Control method suitable for applications that require accurate motor speed regulation (0.02%) but do not require a high speed response.
Go to parameter A1-02,
!
Encoder Direction
Select V/f with PG Method or Closed Loop Vector
Control Method
To adjust control method use / and press .
Closed Loop Vector (Recommended)
Control method suitable for applications that medium to high speed control accuracy, high torque response and full torque at 0 speed.
Check the motor speed monitor U1-05 while turning the motor manually in forward direction (CW). If the sign displayed is negative, power down the drive, wait at least five minutes until the charge indicator extinguishes completely then swap encoder wires A+ with A- on the PG-X3 card. Next power-up the drive and repeat this test. Or reverse the encoder direction with parameter F1-05. For encoders with only A & B outputs, exchange A & B.
Auto-tuning Procedure
Start here
From the main reference press once until the Digital Operator shows the Auto-Tuning menu then press .
T1-03 Rated Voltage (e.g. 230 V, 460 V)
T1-04 Rated current (e.g. 11.0 A, 22.0 A)
T1-05 Rated Frequency (e.g. 60.0 Hz)
T1-06 Number of Poles (e.g. 4 Poles)
For standard AC motors use the default setting for motor base frequency
(60Hz), motor poles (4) and motor rated speed.
T1-07 Rated Speed (e.g. 1750 rpm)
T1-08 Encoder / PG Number of Pulses per Rev. (e.g. 1024)
Switch to Edit Mode Modify Value Save New Value
Monitor Motor Frequency and Motor Current
After setting parameter T1-08 press to select the
Auto-Tuning start command.
A1000 Digital Operator power-up state
Output Frequency and Motor Current can be monitored simultaneously.
To monitor output frequency and motor current or other signals
Press once until the Digital Operator shows parameter
T1-02 Mtr Rated Power then press
Enter Motor Power in kW (Kilowatt) individually, press once, the press
. Next press to select monitor
Use to select monitor signal.
Digits
Flashing
U1-02 Output Frequency
Please refer to the A1000 User Manual, (Document No.
SIEP C710606 21A) on how to access other drive monitors.
Motor HP to kW = HP x 0.746
Example: 10HP = 10 x 0.746 = 7.46 kW
Digit Flashing
Press to select the digit you would like to change and use to adjust value and press to save.
Press to select the next parameter and follow the same procedure described above to adjust its value.
Continue
!
Warning! Sudden movement hazard. The A1000 and motor may start unexpectedly during Auto-Tuning.
Warning! Electric Shock Hazard. High voltage will be supplied to the motor when stationary Auto-Tuning is performed. Do not touch the motor during auto-tuning.
Notice: Auto-Tuning will not function properly when a brake is engaged on the load. Ensure the motor shaft can freely rotate. Never perform an Auto-Tune with motor connected to a load.
Next, press on the Digital Operator. The A1000 will now start the Auto-tuning procedure.
The display will show message “Tune Successful” when the
Auto-Tuning procedure has been successfully completed.
Please refer to the A1000 User Manual or repeat the procedure again if the display shows an error message.
A1000 Cheat Sheet (Closed Loop Operation)
Page 3 of 3
Step
7
Selecting Start/Stop and Speed Reference Sources
This step shows how to setup the run and reference source of the A1000. The run source determines how the A1000 drive receives its start and stop command and the reference source determines how the speed of the motor is controlled. Make sure all protective covers have been re-attached and power is turned on. DO NOT RUN THE MOTOR.
This section may require you to change one or more A1000 parameters. Please refer to Step 5 for a detailed explanation on how to change parameters.
SELECT REFERENCE SOURCE
1.
Adjust motor speed / frequency from the Digital Operator b1-01
Go to parameter b1-01, set value to
To adjust frequency use / and press .
2.
Adjust motor speed / frequency from external terminals (0 - 10V / 4 - 20mA Signal)
Go to parameter b1-01, set value to (Factory Default)
User Terminals
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
Potentiometer
2K Ohm
+
0 ~ 10Vdc
V+ AC V- A1 A2 A3 FM AM AC MP RP AC Located inside the drive on the terminal board
4 ~ 20mA
+
(Factory Default)
Note: 2 nd row of terminal board is shown here.
SELECT RUN SOURCE
1.
Start / Stop Control from Digital Operator b1-02
Go to parameter b1-02, set value to
2.
Start / Stop Control from external terminals (switch or relay contact)
Go to parameter b1-02, set value to
User Terminals
Forward
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
Reverse
Link
User Terminals
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
( Factory Default)
User Terminals
Start
Switch
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
Normally
Open
Reverse
Link
Step
8
Motor Performance Fine Tuning
The following tables show how to fine tune motor operation for V/f with PG and Closed Loop Vector Operation.
Please refer to the A1000 User Manual (Document No. SIEP C710606 21A) for additional information.
V/f Control with encoder feedback (A1-02 = 1)
Problem
· Motor is hunting and oscillation at speeds between 10 and 40Hz.
· Motor noise
· Motor hunting and oscillation at speed up to
40Hz
· Poor torque or speed response
· Motor hunting and oscillation
· Poor motor torque at speeds below 10 Hz
· Motor hunting and oscillation
· Poor motor torque at low speeds
· Motor instability at motor start
· Poor speed precision
Parameter
n1-02 Hunting Prevention Gain
C6-02 Carrier Frequency Selection
C4-02 Torque Compensation Primary Delay Time
C4-01 Torque Compensation Gain
E1-08 Mid Output Voltage A
E1-10 Minimum Output Voltage
C5-01 ASR Proportional Gain 1
C5-02 ASR Integral Time 1 <4>
<3>
Action Default Suggested Setting
· If insufficient motor torque relative to the size of the load causes hunting reduce the setting.
· When motor hunting and oscillation occur with a light load increase setting.
· Lower this setting if hunting occurs when using a motor with a
1.00 0.10 to 2.00 relatively low inductance such as a high-frequency motor or a motor with a larger frame size.
· If the motor noise is too loud increase the carrier frequency.
· When motor hunting and oscillation occur at speeds up to 40 Hz lower the carrier frequency.
· The default setting for the carrier frequency depends on the drive capacity (o2-04) and the Duty Selection (C6-01).
1 (2 kHz) 1 to max. setting
· If motor torque and speed response are too slow, decrease the
setting.
· If motor hunting and oscillation occur, increase the setting.
200 ms <1> 100 to 1000 ms
· If motor torque is insufficient at speeds below 10 Hz, increase the setting.
· if motor hunting and oscillation with a relatively light load, decrease the setting.
· If motor torque is insufficient at speeds below 10 Hz, increase the setting.
· If motor instability occurs at motor start, decrease the setting.
Note: The recommended setting value shown is for 200 V class drives.
Multiply value x 2 for 400V class drives and x 2.875 for 575V class drives.
Adjust the ASR proportional gain 1 (C5-01) and the ASR integral time 1 (C5-02).
1.00
E1-08: 15.0 V
E1-10: 9.0 V
C5-01: 0.20
C5-02: 0.200
<2>
<2>
0.50 to 1.50
Default setting ±5 V
Prop. gain = 0.10 to 1.00
Int. time = 0.100 to 2.000
Closed Loop Vector Control (A1-02 = 3)
Problem Parameter Default Suggested Setting
C5-01 ASR Proportional Gain 1 <4>
C5-03 ASR Proportional Gain 1 <4>
· Poor torque or speed response
· Motor hunting and oscillation
C5-02 ASR Integral Time 1 <4>
C5-04 ASR Integral Time 2 <4>
· Trouble maintaining the ASR proportional gain or the integral time at the low or high end of the speed range
C5-07 ASR Gain Switching Frequency <4>
· Motor hunting and oscillation C5-06 ASR Primary Delay Time Constant <4>
· Motor noise
· Motor hunting and oscillation occurs at speeds below 3 Hz
C6-02 Carrier Frequency Selection
Action
· If motor torque and speed response are too slow, gradually increase the ASR gain setting by 5.
· If motor hunting and oscillation occur, decrease the setting.
· Parameter C5-03 needs to be adjusted only if C5-07 > 0.
· Perform ASR Auto-Tuning if possible
· If motor torque and speed response are too slow, decrease the
setting.
· If motor hunting and oscillation occur, increase the setting.
· Parameter C5-04 needs to be adjusted only if C5-07 > 0.
Have the drive switch between two different ASR proportional gain and integral time settings based on the output frequency.
· If motor torque and speed response are too slow, gradually
decrease the setting by 0.01.
· If the load is less rigid and subject to oscillation, increase this
setting.
· If there is too much motor noise, the carrier frequency is too low.
· If motor hunting and oscillation occur at low speeds, reduce the
carrier frequency.
Note: The default setting for the carrier frequency depends on the drive capacity (o2-04) and Drive Duty Selection (C6-01).
20.00
0.500 s
0.0 Hz
0.004 s
1
10.00 to 50.00
0.300 to 1.000 s
0.0 to max. freq. output
0.004 to 0.020s
2KHz to max. setting
· Overshoot or undershoot when the speed changes with high inertia load
Use S-Curve: C2-01, C2-02, C2-03, C2-04 0 1
<1> Default setting value is dependent on parameter A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03.
<3> ASR in V/f Control with PG only controls the output frequency, and therefore does not allow for high gain settings like in Close Loop Vector control.
<4> Refer to C5: Automatic Speed Regulator (ASR) in the A1000 User Manual (Document No. SIEP C710606 21A) for details on Automatic Speed Regulator (ASR).
Wiring Diagram: 2-Wire Control
Use for maintained contacts
Stop
Switch
Normally
Closed
Note: 3 rd row of terminal board is shown here.
Wiring Diagram: 3-Wire Control
Use for momentary contacts
(Set Parameter A1-03 to 3330)
NOTE: It is beyond the scope of this document to program the A1000 drive for network communication control.
Please refer to the refer to the A1000 User Manual, (Document No. SIEP C710606 21A) for this selection.
Yaskawa America, Inc.
2121 Norman Drive South
Waukegan, IL 60085
(800) YASKAWA (927-5292) Fax (847) 887-7310
[email protected] www.yaskawa.com
Document Number: TM.A1000.02 1/4/2011 © Yaskawa America, Inc.