Introduction
V1.00
KBR multimess 1D4
Introduction .............................................................................................................. 5
User manual ...............................................................................................................5
Intended use ..............................................................................................................5
Explanation of safety relevant symbols ......................................................... 6
Safety notes ................................................................................................................7
Product liability ........................................................................................................ 8
Disposal ...................................................................................................................... 8
Range of functions ..................................................................................................9
multimess 1D4-BS with multimess 1F96-DS ..................................................9
multimess 1D4-BS with multisio 6D6 and multisio 6F96-DS ....................................................................................................10
multimess 1D4-BS with multisys 3D2-ESBS ..................................................10
Device overview ....................................................................................................11
Installation ................................................................................................................14
Device assembly ....................................................................................................14
Connections .............................................................................................................15
Start-up ......................................................................................................................16
Start-up of the multimess 1D4 with multimess 1F96-DS display.................................................................................16
Start-up of the multimess 1D4 at the multisio 6D6 with multisio 6F96-DS ...............................................................19
Start-up of the multimess 1D4 with multisys 3D2-ESBS .................................................................................................20
System operation ..................................................................................................20
Configuration of system parameters in the Extras menu ................................................................................................20
Commi function .....................................................................................................22
Para function .......................................................................................................... 22
Consumption monitoring ..................................................................................22
Menu overview ...................................................................................................... 24
Technical data of the measuring module ..................................................... 28
Measuring accuracy ..............................................................................................28
Measuring principle ............................................................................................. 28
Device memory ......................................................................................................29
Power supply ..........................................................................................................29
Hardware inputs and outputs ............................................................................29
Inputs ..........................................................................................................................29
Outputs .................................................................................................................... 29
Electrical connection.............................................................................................30
Mechanical data ......................................................................................................30
3
KBR multimess 1D4
Standards and miscellaneous ............................................................................31
Technical data of the measuring module ..................................................... 32
Power supply ..........................................................................................................32
Hardware inputs and outputs ............................................................................32
Electrical connection.............................................................................................32
Mechanical data ......................................................................................................32
Standards and miscellaneous ........................................................................... 33
Protective measures ..............................................................................................33
Overvoltage and lightning protection ...........................................................33
Index .......................................................................................................................... 34
4 V1.00
Introduction
1 Introduction
KBR multimess 1D4
Thank you for choosing this KBR quality product. In order to familiarize yourself with the operation and configuration of the device, we recommend that you read this manual thoroughly, so that you are able to make use of the entire range of functions of this high-quality product.
1.1 User manual
The individual chapters serve to explain the technical details of the device and show how to avoid damage by means of proper installation and commissioning.
This user manual describes the multimess 1D4 device version with multimess 1F96-DS display. For other device versions, e.g. for multimess 1D4 on multisio 6D6 with multisio 6F96-DS or
multimess 1D4 with multisys 3D2-ESBS, please read the respective device manual.
This user manual is included in the scope of delivery of the device and must be accessible for the user at all times (e.g. in the switchgear cabinet). Even when the device is resold to third parties, the manual remains part of the device.
1.2 Intended use
Although we used the utmost care in assembling this user manual, we would like to thank you in advance for notifying us about any errors or ambiguous descriptions you might notice.
This device is intended for measuring electrical parameters via external transformers in the low-voltage network (400VAC Ph-Ph).
V1.00
5
6
KBR multimess 1D4 Introduction
1.3 Explanation of safety relevant symbols
This user manual contains notes that must be observed for your personal safety and to avoid damage to equipment.
These notes are identified by an i
or information symbol, depending on the degree of hazard they represent.
j
Warning
"Warning" means that death, major injuries or damage may occur in case the appropriate safety measures are not taken.
h
Caution
"Caution" means that minor injuries or damage may occur in case the appropriate safety measures are not taken.
i
Note
"Note" is an important information on the product, its operation or the respective part of the user manual to which special reference is made.
Disclaimer
The content of this user manual has been carefully reviewed in terms of the hardware and software described. Certain deviations, however, cannot be excluded, and the manufacturer is not liable for complete conformity. The specifications made in this user manual are checked on a regular basis, necessary corrections will be included in the next revision.
V1.00
Introduction KBR multimess 1D4
1.4 Safety notes
In order to prevent operating errors, operation of this device is kept as simple as possible. This way, you will be able to quickly start working with the device.
In your own interest, however, you should read the following safety notes carefully. During assembly, the applicable DIN / VDE regulations must be observed!
Power supply connection, setup and operation of the device must be performed by qualified personnel only. Qualified personnel in accordance with the safety notes in this user manual are persons authorized to set up, ground and mark devices, systems and circuits in accordance with the applicable standards and regulations.
To avoid fire and electrical shock, the device must not be exposed to rain or humidity!
Before connecting the device to the power supply, check whether the local power supply conditions comply with the specifications on the nameplate.
A faulty connection can lead to the destruction of the device!
When connecting the device, observe the connection chart (see chapter “Connection chart”) and make sure that no voltage is applied to the connection lines. Only use proper wiring material and observe the correct polarity when wiring!
In order to ensure proper and safe operation of the product, it must be transported, stored, installed and assembled in accordance with the specifications and operated and maintained carefully.
A visibly damaged device must generally be considered unfit for use and disconnected from the power supply!
Error detection, repair and maintenance work may only be carried out in our facilities or after contacting the service team.
Unauthorized opening of the device voids any warranty. Correct operation can no longer be guaranteed!
Opening the device may expose live parts. Capacitors in the device may still be loaded, even if the device has been disconnected from all voltage sources. It is generally not allowed to operate an open device!
V1.00
7
KBR multimess 1D4 Introduction
In systems susceptible to lightning, lightning protection must be provided for all input and output lines (for recommendations, see chapter “Protective measures”)!
1.5 Product liability
You have acquired a high quality product. In its manufacture, only components of the highest reliability and quality were used. Each device is subject to long-term testing before it is delivered. Regarding product liability, we refer to our general terms and conditions for electronic equipment, which you can find at www.kbr.de . The warranted characteristics of the device only apply for operation in accordance with its intended use!
1.6 Disposal
Defective, outdated or no longer used devices must be properly disposed of. At your request, we will dispose of the devices for you.
8 V1.00
Insert battery KBR multimess 1D4
2 Range of functions
multimess 1D4 is a multimeter for busbar mounting. On the output side, it can measure all typical alternating and direct current parameters of consumers.
The following device expansion stages are possible, featuring different ranges of function:
“multimess 1D4-BS with multimess 1F96-DS” on page 9
“multimess 1D4-BS with multisio 6D6 and multisio 6F96-DS” on page 10
“multimess 1D4-BS with multisys 3D2-ESBS” on page 10
2.1 multimess 1D4-BS with multimess 1F96-DS
Connection of the optional multimess 1F96-DS display can be established with a ready-made RJ12 cable. For operation of the display, an additional power supply unit is needed, e. g. the multisys
1D4-PS-24V. This way, no complicated wiring of voltage and current paths from the converter to the switchgear cabinet door is necessary.
Up to 10 measuring modules can be read out and displayed.
Connection between the modules is also established via ready-made
RJ12 cables.
Power supply of the measuring device is provided by the measuring voltage. A separate control voltage is not necessary.
i
Note
multimess 1D4-BS with multimess 1F96-DS is the version described in this user manual.
V1.00
9
KBR multimess 1D4
2.2 multimess 1D4-BS with multisio 6D6 and multisio 6F96-DS
If the multimess 1D4 is connected to the multisio 6D6 instead of to the display, the multisio 6D6 creates a load profile memory (P+ P-/ Q+
Q-) and an eBus interface. Five measuring modules can be connected to each central storage module Connection between the modules is established via ready-made RJ12 cables.
2.3 multimess 1D4-BS with multisys 3D2-ESBS
For direct connection of the multimess 1D4 to the KBR eBus, the
multisys 3D2-ESBS gateway is required, which also provides the supply voltage for the module bus interface via ready-made RJ12 cables. A maximum of 15 measuring modules can be connected
(power consumption of the measuring module interface approx. 0.3
W, power output of the multisys 3D2-ESBS gateway approx. 5 W at 24
VDC). For a larger number of measuring modules, the multisys 1D4-PS-
24V power supply unit is required (power output 24 VDC, 10 W).
3 Device overview multimess 1D4 measuring module
For busbar assembly (7.5 mm rail)
Connection to measuring voltage Ph-N 230 VAC
Measuring current connection via transformer x/1A or x/5A
Plug terminal connection 2.5 mm 2
RJ12 display connection
RJ12 module bus connection for supply voltage of the bus interface / connection of additional measuring modules.
Recording of momentary current and voltage values.
Continuous energy meter for active and reactive energy
10 V1.00
multimess 1F96-DS
KBR multimess 1D4
Display illumination (Dot Matrix 128x96)
Brightness and contrast adjustable
Display dimming time adjustable
(energy saving function)
Operation via sensor buttons
Mounting depth 40 mm
Door assembly cut-out 92x92 mm
Module bus connection RJ12 for measuring modules and supply voltage
Display of momentary current and voltage values
Continuous energy meter for active and reactive energy
Management of up to 10 measuring modules
Assignment of station names to the measuring modules
Display language selectable
German ("deut") / English ("engl")
V1.00
11
KBR multimess 1D4
3.1 Operating structure
Instantaneous value display
The following overview gives you an idea of the multimess
1D4 operating structure with the
1F96-DS display. For a detailed description, please refer to
“Menu overview” on page 24.
U PH-N measuring module 1
Module name
Voltage channel 1
Voltage channel 2
Voltage channel 3
U PH-PH measuring module 1
Module name
Voltage channel 1
Voltage channel 2
Voltage channel 3
Apparent current meas. module 1
Module name
Apparent current channel 1
Apparent current channel 2
Apparent current channel 3
Total power
Module name
Apparent power
Active power
Reactive power
Apparent power meas. module 1
Module name
Apparent power channel 1
Apparent power channel 2
Apparent power channel 3
Additional measuring modules
Additional measuring modules
Additional measuring modules
Additional measuring modules
Additional measuring modules
12 V1.00
KBR multimess 1D4
Active power meas. module 1
Module name
Active power channel 1
Active power channel 2
Active power channel 3
Reactive power meas. module 1
Module name
Reactive power channel 1
Reactive power channel 2
Reactive power channel 3
Cosine Phi measuring module 1
Module name
Cosine Phi channel 1
Cosine Phi channel 2
Cosine Phi channel 3
Frequency
Module name
Network frequency
Energy meter:
Continuous counter
active energy
Continuous counter
reactive energy
Extras (Settings)
Display firmware version
Commissioning
Configuration
Additional measuring modules
Additional measuring modules
Additional measuring modules
Additional measuring modules
Additional measuring modules
Commissioning
Password
Module name
Scan / remove module
Reset display
Single-phase / 3-phase measurement
Transformer I 1 / 2
Transformer U 1 / 2
Configuration
Display firmware module
Measuring module selection
LCD contrast
LCD brightness
LCD dimmer brightness
Dimmer delay
Display test
Language selection
V1.00
13
KBR multimess 1D4
4 Installation
In this chapter, you will find a description of:
“Device assembly” on page 14
“Connections” on page 15
“Commissioning” on page 16
4.1 Device assembly
During installation, the applicable DIN / VDE regulations must be observed! Before connecting the device to the power supply, check whether the local power supply conditions comply with the specifications on the nameplate. A faulty connection may destroy the system! The device must be connected in accordance with the connection chart. For energy and synchronous pulse input, polarity must be observed (contact your energy supplier).
In systems susceptible to lightning, lightning protection must be provided for the control voltage, bus line and pulse lines (e.g. energy supplier pulse lines from the transformer station to the location of the energy control system).
14 V1.00
L1
L2
L3
N
V1.00
KBR multimess 1D4
4.2 Connections
Terminals 10 - 13
(L1, L2, L3, N)
Terminals 20 (k1) and 21 (l1), 22 (k2) and
23(l2), 24 (k3) and 25 (l3)
Measuring voltage. The power supply of the device is also provided by the measuring voltage. For technical data, please refer to the nameplate.
Measuring inputs for current. The measuring inputs for current must be connected via current transformers x/1A AC or x/5A AC. When connecting transformers, pay attention to the energy flow direction and the correct assignment of measuring voltage inputs to the current transformers.
13 12 11 10
N L3 L2
Measuring voltage
Messspannung
L1
Modul Modul k1
Measuring current l1
Messstrom k2 l2 k3 l3
20 21 22 23 24 25
Stromflussrichtung / current direction
15
Erstellung
Index Änderung
Maßstab: 1 : 1
Bezeichnung:
Artikelnr.:
Geprüft Datum
02.05.2011
EDV Bezeichnung:
Anschlussplan multimess 1D4-BS
02.05.11
Strasser
Datum Name
DTDASP0042_1811-1_multimess 1D4-BS.ai
A4
GmbH
Am Kiefernschlag 7
91126 Schwabach
Blatt
1 / 1
KBR multimess 1D4
4.3 Start-up
The following section describes the start-up procedure for the different device versions.
4.3.1 Start-up of the multimess 1D4 with multimess 1F96-DS display
For starting up the multimess 1D4 with multimess 1F96-DS display, please proceed as follows:
1. Connect the measuring module to the multimess 1F96-DS display via the module bus interface.
2. With the "Module out" connector, connect the measuring module to the multisys 1D4-PS-24V power supply unit via the second module bus interface.
3. At the multisys 1D4 power supply unit, connect the supply voltage
(refer to nameplate). The operation LED on the device is illuminated green.
4. At the terminals 10 (L1), 11 (L2), 12 (L3) and 13 (N), connect the measuring voltage (the operating voltage of the measuring module).
5. At the display, select the menu Extras > Commissioning to scan measuring modules connected.
6. Displayed are modules already existing, as well as the menu items
"scan" and "rem." (for removing measuring modules from the module bus list).
7. After selection of the menu item "scan", the scan mode is activated and the function LED at the measuring modules flashes slowly.
16 V1.00
KBR multimess 1D4
8. At the measuring module, the scan sensor button (close to the status LED, flashing green) is unlocked.
9. To set the measuring module into scan mode, touch the scan sensor button for about 4 seconds (the green status LED flashes more quickly)
10. The multimess display recognizes the measuring module and adds it to the list of modules connected.
11. You can now scan further modules, which are automatically added to the module list or, by touching the stop button, end the scanning process. The display can manage a maximum number of ten modules.
Set-up diagram for operation of the multimess 1D4 with multimess 1D4-DS (example):
LCD
V1.00
Measuring module 1 to 10 (maximum)
Modul in
Modul out
multisys 1D4-PS24V
+ _
101 102
L N PE
1 2 PE
24V DC
85 - 260V AC
Netz / Power multisys
1D4-PS-24V power supply unit
17
KBR multimess 1D4
Configuration
Extras menu
18
Display of the firmware version and release of the display
DS display
01.00 version
005 release
Previous menu
Display of measuring module version,
Display configuration
Start commissioning
Next menu
Display of the firmware version and release of the measuring module at the module bus
Measuring module designation
BS type module bus device
01.00 version
001 release
Selection of next measuring module
Selection of previous measuring module
Next menu
V1.00
KBR multimess 1D4
4.3.2 Start-up of the multimess 1D4 at the multisio 6D6 with multisio 6F96-DS
For starting up the multimess 1D4 at the multisio 6D6, please proceed as follows:
1. Connect the measuring module to the multisio 6D6 via the module bus interface.
2. At the terminals 10 (L1), 11 (L2), 12 (L3) and 13 (N), connect the measuring voltage (the operating voltage of the measuring module).
3. On the display, select the menu Settings > Module management.
4. Displayed are the multisio basic module as well as modules already existing and the menu item "scan".
5. After selecting this menu item with the cursor buttons, the scan mode can be started with the scan button and the scan display begins to flash. This way, the scan button at the measuring module
(close to the status LED, flashing green) is unlocked.
6. By pressing the scan sensor button for approx. 4 seconds, set the measuring module into scan mode (the green status LED flashes more quickly).
The multisio basic module now recognizes the measuring module and adds it to the list of modules connected.
You can now scan further modules, which are automatically added to the module list or, by touching the stop button, end the scanning process. The multisio 6D6 can manage a maximum number of ten modules.
You can now read out and process the data.
V1.00
19
KBR multimess 1D4
4.3.3 Start-up of the multimess 1D4 with multisys 3D2-ESBS
For starting up the multimess 1D4 at the KBR eBus via the multisys
3D2-ESBS gateway, please proceed as follows:
1. Connect the measuring module to the multisys 3D2 gateway via the module bus interface.
2. At the terminals 10 (L1), 11 (L2), 12 (L3) and 13 (N), connect the measuring voltage (the operating voltage of the measuring module).
3. Connect the multisys 3D2 gateway to the KBR eBus using terminals
90, 91 and 92.
A command, triggered by the visual energy computer software, unlocks the scan button at the measuring module (close to the status LED, flashing green).
4. By pressing the scan sensor button for approx. 4 seconds, set the measuring module into scan mode (the green status LED flashes more quickly).
The measuring module is detected and included in the bus list.
You can now read out and process the data.
5 System operation
In this chapter, you will find instructions on how to operate the multimess 1D4 with the multisio 1D4-DS display in daily use.
Furthermore, it contains references to the complete range of functions.
5.1 Configuration of system parameters in the Extras menu
To adapt multimess 1D4 to the system monitored, its parameters have to be configured.
Press the F1 key eleven times, selecting the Extras menu.
Here, measuring modules connected and the firmware version of the display are shown.
You have access to the following functions:
“Commi function” on page 22
“Para function” on page 22
The menu navigation of the multimess 1D4-DS is self-explanatory.
The operator is guided and supported by the device through operating instructions displayed for the respective situation.
20 V1.00
KBR multimess 1D4
The following signs and abbreviations will be used in the display:
Scroll forward (through main menu or submenu)
Scroll backwards (through main menu or submenu)
QS
YS
O
SCAN
Return
Next measuring module
Previous measuring module
Value input
Select next screen
Return for configuration
Perform configuration
Fundamental power factor
Voltage phase / neutral conductor
Network frequency
Active power – total (3-phase)
Active power / reactive power / apparent power – total (3-phase)
Confirmation to save configuration
Discard configuration
Scan mode (search mode) for module search
imw Operating software of the measuring module or display module
1x3p 3-phase measurement
3x1p
single-phase measurement
Measuring voltage transformer 1 / 2
Main current transformer 1 / 2
LC
d
t
LCD parameter (display module)
Password protection
Reset function display
V1.00
21
KBR multimess 1D4
5.1.1 Commi function
With the "commi" start-up function, up to 10 measuring modules connected can be integrated.
This includes: Password protection for configuration
Assigning names to individual measuring modules
Scan menu for reading in measuring modules connected
Removing measuring modules connected
Selection of single-phase or 3-phase measurements
Configuration of current transformer primary / secondary
Configuration of voltage transformer primary / secondary
5.1.3 Para function
With the "para" configuration function, you can display the firmware version of the measuring modules connected, change the LCD settings and choose between English and German as the display language.
5.1.4 Consumption monitoring
In this operating mode, momentary measured values as well as continuous meters for active and reactive energy consumption can be read out directly at the display.
22 V1.00
V1.00
KBR multimess 1D4
The respective module name is included on each screen, depending on the measuring module selected.
The following momentary values can be displayed:
1 st
screen: Voltage Ph-N for phase L1, L2 and L3 individually
2 nd screen: Voltage Ph-Ph for phase L1-2,
L2-3 and L3-1 individually
3 rd screen: Apparent current for phase
L1, L2 and L3 individually
4 th
screen: Total power for apparent, active and reactive power
5 th screen: Apparent power for phase
L1, L2 and L3 individually
6 th
screen: Active power for phase
L1, L2 and L3 individually
7 th
screen: Reactive power for phase
L1, L2 and L3 individually
8 th screen: Cosine Phi for phase
L1, L2 and L3 individually
9 th screen: Power frequency
10 th screen: Continuous energy meter for active energy consumption
Continuous energy meter for reactive energy consumption
11 th screen: Commissioning
(Extras menu)
LCD parameters
23
KBR multimess 1D4
6 Menu overview
In this chapter, you will find a complete overview of all menus and menu items of the multimess.
24
Display of momentary measuring voltage for
Phase L1-N
Phase L2-N
Phase L3-N
Display of momentary measuring voltage for
Phase L1-2
Phase L2-3
Phase L3-1
V1.00
V1.00
KBR multimess 1D4
Display of momentary apparent current for
Phase L1
Phase L2
Phase L3
Display of total values of
Apparent power
Active power
Reactive power
Display of momentary apparent power for
Phase L1
Phase L2
Phase L3
25
KBR multimess 1D4
26
Display of momentary active power for
Phase L1
Phase L2
Phase L3
Display of momentary reactive power for
Phase L1
Phase L2
Phase L3
Display of momentary values of cosine Phi for
Phase L1
Phase L2
Phase L3
V1.00
V1.00
KBR multimess 1D4
Display of momentary network frequency
Display of the continuous energy meter for active energy (total value).
In the submenus
()
, the values of the individual phases can be seen.
Display of the continuous energy meter for reactive energy (total value).
In the submenus
()
, the values of the individual phases can be seen.
27
KBR multimess 1D4
Display of the firmware version of the display.
Furthermore, the Commissioning and
Configuration submenus are included.
7 Technical data
7.1 Technical data of the multimess 1D4 measuring module
7.1.1 Measuring accuracy
Current
Voltage
Apparent power
Active power
Reactive power
Frequency
± 0.5 % / ± 1 digit
± 0.5 % / ± 1 digit
± 1 % / ± 1 digit
± 1 % / ± 1 digit
± 1 % / ± 1 digit
± 0.1 Hz / ± 1 digit
7.1.2 Measuring principle
Reading
A/D converter
Measurement of U and I
Update speed
(complete measuring cycle)
Harmonics calculation
Frequency measurement
128 measured values per period
12 bit simultaneous recording of measured values for U and I;
< 1 sec.
DFT with 128 points over one period
Mode: Voltage measured between phase L1, L2, L3 – N
28 V1.00
KBR multimess 1D4
7.1.3 Device memory
Main and data memory
Program / parameter memory
Energy counter P+, P-, Q+, Q-
Limit violation Time for acquisition
16kB RAM unbuffered
256 kB Flash / 4kB EEP saved in EEP
8 min. for average current value, saved in RAM
7.1.4 Power supply
Measuring module power supply
Module bus power supply
50...230...280 VAC Ph-N, 3,2VA, provided by the measuring voltage ext. 24VDC, 0.3W, via RJ12 module bus connector
7.1.5 Hardware inputs and outputs
7.1.5.1 Inputs
Measuring inputs for voltage
Measuring inputs for current
U
L1-N
; U
L2-N
; U
L3-N
Input impedance
I
L1
; I
L2
; I
L3
Power consumption
7.1.5.2 Outputs
Serial interface
Module bus
Baud rate
Addressing
3 x 50V...230V...280V AC
900 kOhm each (Ph-N)
3 x 0,02A...5A...6A AC
<_ 0.3 VA per input at 6A
RS485 via RJ12 interface
38400
Can be addressed using the display or visual energy (connection via multisio
3D2 ESBS gateway)
V1.00
29
KBR multimess 1D4
7.1.6 Electrical connection
Connection elements
Permissible cross section of the connection lines
Measuring voltage inputs
Fuse protection
Measuring current inputs
Fuse protection
Input control voltage
Module bus connection
Connection material
Plug terminals
2.5 mm
2 max. 6 A
NONE!!! Always short-circuit current transformer terminals k and l prior to opening the circuit!
via measuring voltage ready-made KBR system cable (6 pole modular cable, unshielded), max. length 30m if placed accordingly
7.1.7 Mechanical data
Busbar devices
Housing measurements 90 x 71 x 61 mm (H x W x D)
Mounting type Wall mounting on DIN rail 7.5mm deep, in accordance with DIN EN 50022
Suitable for distribution board mounting
Weight approx. 175g
30 V1.00
KBR multimess 1D4
7.1.8 Standards and miscellaneous
Environmental conditions
Electrical safety
Standards and amendments
DIN EN 60721-3-3/A2: 1997; 3K5+3Z11;
(IEC721-3-3; 3K5+3Z11)
Operating temperature -5°C … +55°C
Humidity 5% … 95% non-condensing
Storage temperature
Standards and amendments
Protection class
Overvoltage category
Degree of protection
Electromagnetic compatibility
-25°C … +70°C
DIN EN 61010: 2001 +B1: 2002; +B2:
2004
II
CAT III: U
PH-PH
up to 400V
IP 20
DIN EN 60529:1991 +A1:2000
DIN EN 61000-6-1: 2007,
DIN EN 61000-6-2: 2005,
DIN EN 61000-6-3: 2007,
DIN EN 61000-6-4: 2007
V1.00
31
KBR multimess 1D4
7.2 Technical data of the multimess 1D4-DS display
7.2.1 Power supply
Power supply ext. 24VDC, 1W, via RJ12 module bus connector
7.2.2 Hardware inputs and outputs
Serial interface
Module bus
Baud rate
RS485 via RJ12 interface
38400
7.2.3 Electrical connection
Module bus connection
Connection material ready-made KBR system cable (6 pole modular cable, unshielded), max. length 30m if placed accordingly
7.2.4 Mechanical data
Flush-mounted device
Housing dimensions
Mounting cutout
Protection type
Weight
96 x 96 x 46 mm (H x W x D)
92 x 92 mm (according to manufacturer’s specifications)
Front IP 51 approx. 175g
32 V1.00
KBR multimess 1D4
7.2.5 Standards and miscellaneous
Environmental conditions
Electrical safety
Standards and subsequent amendments
DIN EN 60721-3-3/A2: 1997; 3K5+3Z11;
(IEC721-3-3; 3K5+3Z11)
Operating temperature -5°C … +55°C
Humidity 5% … 95%, non-condensing
Storage temperature
Standards and subsequent amendments
Protection type
-25°C … +70°C
DIN EN 61010-1/A2: 1996-05;
(IEC1010-1/A2)
Electromagnetic compatibility
IP20 in accordance with DIN EN 40050 part 9: 1993-05
DIN EN 61000-6-3: 2005-06;
(IEC 61000-6-3)
DIN EN 61000-6-2: 2000-03;
(IEC 61000-6-2)
7.3 Protective measures
7.3.0.1 Overvoltage and lightning protection
It is recommended to install overvoltage protection measures to protect our high-quality devices from damage. We also recommend to protect control voltage inputs and pulse lines, if required.
V1.00
33
KBR multimess 1D4
8 Index
A
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
C
Commissioning multimess 1D4 at the multisio 6D6 with multisio 6F96-DS . . . . . 19 multimess 1D4 with display multimess 1F96-DS . . . . . . . . . . . . . 16 multimess 1D4 with multisys 3D2-ESBS . . . . . . . . . . . . . . . . . . . . . 20
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Consumption monitoring . . . . . . . . . . . . . . 22
F
Function
Commi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Para. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
I
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
M
Measuring inputs for current . . . . . . . . . . . 15
Measuring voltage . . . . . . . . . . . . . . . . . . . . . 15
Menu overview. . . . . . . . . . . . . . . . . . . . . . . . . 24
D
Device overview . . . . . . . . . . . . . . . . . . . . . . . 10
Device versions multimess 1D4-BS with multimess 1F96-DS . . . . . . . . . . . . . . . . . . . . . 9 multimess 1D4-BS with multisio 6D6 and multisio 6F96-DS . . . . . 10 multimess 1D4-BS with multisys 3D2-ESBS . . . . . . . . . . . . . . . . . . . . . 10
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E
Explanation of safety relevant symbols . . 6
P
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Product liability . . . . . . . . . . . . . . . . . . . . . . . . . 8
Protective measures . . . . . . . . . . . . . . . . . . . 33
S
Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Set-up diagram multimess 1D4 with multimess 1D4-DS 17
T
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . 28
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
U
User manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
34 V1.00
KBR Kompensationsanlagenbau GmbH
Am Kiefernschlag 7
D-91126 Schwabach,
Germany
Phone +49 9122 6373 - 0
Fax +49 9122 6373 - 83
E-mail [email protected]
www.kbr.de
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 Introduction
- 5 User manual
- 5 Intended use
- 6 Explanation of safety relevant symbols
- 7 Safety notes
- 8 Product liability
- 8 Disposal
- 9 Range of functions
- 9 multimess 1D4-BS with multimess 1F96-DS
- 10 multisio 6F96-DS
- 10 multimess 1D4-BS with multisys 3D2-ESBS
- 11 Device overview
- 14 Installation
- 14 Device assembly
- 15 Connections
- 16 Start-up
- 16 multimess 1F96-DS display
- 19 multisio 6D6 with multisio 6F96-DS
- 20 multisys 3D2-ESBS
- 20 System operation
- 20 in the Extras menu
- 22 Commi function
- 22 Para function
- 22 Consumption monitoring
- 24 Menu overview
- 28 Technical data of the measuring module
- 28 Measuring accuracy
- 28 Measuring principle
- 29 Device memory
- 29 Power supply
- 29 Hardware inputs and outputs
- 29 Inputs
- 29 Outputs
- 30 Electrical connection
- 30 Mechanical data
- 31 Standards and miscellaneous
- 32 Technical data of the measuring module
- 32 Power supply
- 32 Hardware inputs and outputs
- 32 Electrical connection
- 32 Mechanical data
- 33 Standards and miscellaneous
- 33 Protective measures
- 33 Overvoltage and lightning protection
- 34 Index