Lennox ML193UHE Gas Furnace Installation Instructions

Add to My manuals
55 Pages

advertisement

Lennox ML193UHE Gas Furnace Installation Instructions | Manualzz

© 2022 Lennox Industries Inc.

Dallas, Texas USA

INSTALLATION

INSTRUCTIONS

ML193UHE

MERIT ® SERIES GAS FURNACE

UPFLOW / HORIZONTAL AIR DISCHARGE

507863-02

03/2022

Supersedes 10/2021

THIS MANUAL MUST BE LEFT WITH THE

HOMEOWNER FOR FUTURE REFERENCE

This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

CAUTION

As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer (or equivalent), service agency, or the gas supplier.

Contents

Unit Dimensions - inches (mm) ......................................2

ML193UHEGas Furnace ................................................3

Shipping and Packing List ..............................................3

Safety .............................................................................3

Use of Furnace as a Construction Heater ......................4

General ...........................................................................5

Combustion, Dilution, Ventilation Air...............................5

Setting Equipment ..........................................................8

Filters ............................................................................13

Duct System .................................................................13

Pipe Fittings Specifications ...........................................14

Joint Cementing Procedure ..........................................15

Venting Practices ..........................................................16

Gas Piping ....................................................................33

Electrical .......................................................................36

Integrated Control .........................................................39

Unit Start-Up .................................................................41

Gas Pressure Measurement.........................................42

Proper Combustion.......................................................43

High Altitude .................................................................43

Testing For Combustion Air Non-Direct Vents ..............44

Other Unit Adjustments.................................................45

Service..........................................................................46

Repair Parts List ...........................................................46

Start Up Checklist .........................................................48

Blower Data ..................................................................52

Page 1

Unit Dimensions - inches (mm)

1 NOTE - 60C size units that require air volumes over

1800 cfm must have one of the following:

1. Single side return air and Optional Return Air Base

with transition that must accommodate required

20 x 25 x 1 inch (508 x 635 x 25 mm) air filter to

maintain proper velocity.

2. Bottom return air.

3. Return air from both sides.

4. Bottom and one side return air.

See Blower Performance Tables for additional information.

2 Optional Side Return Air Filter Kit is not for use with the Optional Return Air Base.

2 (51)

D

COMBUSTION

AIR INTAKE

Flue Condensate Trap Assembly

Furnished for external field installation on either side of unit.

(See installation instructions for additional information.)

7

(178)

2

OPTIONAL

SIDE RETURN

AIR FILTER KIT

(Either Side)

3-3/8

(86)

2-7/8

(73)

EXHAUST AIR

OUTLET

SUPPLY AIR

OPENING

23-3/4

(603)

25

(635)

TOP VIEW

3/4

(19)

Model No.

030XE36B

045XE36B

070XE36B

090XE36C

090XE48C

110XE48C

110XE60C

A

B

AIR FLOW

C

1

Bottom Return

Air Opening

FRONT VIEW

1 (25)

Front Panel

9/16 (14)

2 OPTIONAL

SIDE RETURN

AIR FILTER KIT

(Either Side)

33

(838)

6-9/16 (167)

Left

9 (229)

Right

12-5/8 (321)

(Either Side)

ELECTRICAL

INLET

(Either Side)

14-3/4

(375)

16

(406)

3/4

(19)

5/8

(16) 3-1/4

(83)

A in - mm

17-1/2 - 446

B in - mm

16-3/8 - 416

21 - 533 19-7/8 - 505

27-3/4

(705)

19-7/16

(494)

2 (51)

(Either Side)

GAS PIPING INLET

(Either Side)

CONDENSATE

TRAP CONNECTION

(Either Side)

6-1/2 (165)

(Either Side)

23

(584)

1 Side Return

Air Opening

(Either Side)

14

(356)

1-15/16 (49)

23-1/2

(597)

1

Bottom Return

Air Opening

SIDE VIEW

9/16

(14)

1-1/2

(38)

C in - mm

16 - 406

D in - mm

7-5/8 - 194

19-1/2 - 495 9-3/8 - 238

Page 2

ML193UHE Gas Furnace

The ML193UHE Category IV gas furnace is shipped ready for installation in the upflow or horizontal position. The fur nace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in horizontal or upflow applications with bottom return air.

or a Non-Direct Vent gas central furnace.

The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.

NOTE - In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In

Non-Direct Vent installations, combustion air is taken from indoors or ventilated attic or crawlspace and flue gases

are discharged outdoors. See FIGURE 1 and FIGURE 2

for applications involving roof termination.

DIRECT VENT INSTALLATION

EXHAUST OUTLET

COMBUSTION

AIR INTAKE OUTSIDE

OF HOUSE

NON-DIRECT VENT

INSTALLATION

EXHAUST

OUTLET

COMBUSTION

AIR INTAKE

INSIDE

OF HOUSE

Shipping and Packing List

Package 1 of 1 contains

1 - Assembled ML193UHE unit

1 - Bag assembly containing the following:

1 - Snap bushing

1 - Snap plug

1 - Wire tie

1 - Condensate trap

1 - Condensate trap cap

1 - Condensate trap clamp

1 - 2” diameter debris screen

1 - 3/4” Threaded street elbow

Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.

The following items may also be ordered separately:

1 - Thermostat

1 - Propane/LP changeover kit

1 - Return air base kit

1 - Horizontal suspension kit

Safety Information

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer (or equivalent), service agency, or the gas supplier.

FIGURE 1

NON-DIRECT VENT

INSTALLATION

EXHAUST

OUTLET

NON-DIRECT VENT

INSTALLATION

EXHAUST

OUTLET

COMBUSTION

AIR INTAKE INSIDE

VENTILATED

ATTIC SPACE

COMBUSTION

AIR INTAKE INSIDE

VENTILATED

CRAWL SPACE

Danger of explosion.

DANGER

There are circumstances in which odorant used with LP/ propane gas can lose its scent. In case of a leak, LP/ propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.

Use only the type of gas approved for use with this furnace.

Refer to unit nameplate.

ML193UHE units are CSA International certified to ANSI

Z21.47 and CSA 2.3 standards.

Building Codes

In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel

Gas Code (ANSI-Z223.1/NFPA 54).

FIGURE 2

Page 3

The National Fuel Gas Code is available from the following address:

American National Standards Institute, Inc.

11 West 42nd Street

New York, NY 10036

In Canada, installation must conform with current National

Standard of Canada CSA-B149 Natural Gas and Propane

Installation Codes, local plumbing or waste water codes and other applicable local codes.

In order to ensure proper unit operation in non-direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas

Code or CSA-B149 standard.

Installation Locations

This furnace is CSA International certified for installation clearances to combustible material as listed on the unit

nameplate and in the table in FIGURE 12. Accessibility

and service clearances must take precedence over fire protection clearances.

NOTE - For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.

For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed ac cording to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.

NOTE - Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Fail ure to do so may cause erratic limit operation and prema ture heat exchanger failure.

This ML193UHE furnace must be installed so that its electrical components are protected from water.

Installed in Combination with a Cooling Coil

When this furnace is used with cooling coils (FIGURE 3),

it shall be installed in parallel with, or on the upstream side of, cooling coils to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper

(or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.

When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code

(ANSI/NFPA No. 70) is available from the following address:

National Fire Protection Association

1 Battery March Park

Quincy, MA 02269

In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.

Heating Unit Installed Parallell to Air Handler Unit

Dampers

(open during heating operation only)

Gas Unit

Air Handler Unit

Dampers

(open during cooling operation only)

Heating Unit Installed Upstream of Cooling Unit

Gas Unit

Evaporator

FIGURE 3

NOTE - This furnace is designed for a minimum continu ous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.

The ML193UHE furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and utility rooms in the upflow or horizontal position. This furnace design has not been CSA certified for installation in mobile homes, recreational vehicles, or outdoors.

Use of Furnace as Construction Heater

Units may be used for heating of buildings or structures under construction, if the following conditions are met to ensure proper operation:

DO NOT USE THE UNIT FOR CONSTRUCTION HEAT

UNLESS ALL OF THE FOLLOWING CRITERIA ARE

MET :

• Furnace must be in its final location. The vent system must be permanently installed per these installation instructions.

• Furnace must be installed as a two pipe system and one hundred percent (100%) outdoor air must be provided for combustion air requirements during construction.

• A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is prohibited.

• The input rate and temperature rise must be set per the furnace rating plate.

• Supply and Return air ducts must be provided and sealed to the furnace. Return air must be terminated outside of the space where furnace is installed.

Page 4

• Return air temperature range between 60°F (16°C) and

80°F (27°C) must be maintained.

• MERV 11 or greater air filters must be installed in the system and must be regularly inspected and maintained

(e.g., regular static checks and replaced at end of life) during construction.

• Blower and vestibule access panels must be in place on the furnace at all times.

• The furnace heat exchanger, components, duct system, and evaporator coils must be thoroughly cleaned following final construction clean−up.

• Air filters must be replaced upon construction comple tion.

• All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified in accordance with these installation instructions.

EQUIPMENT MAY EXPERIENCE PREMATURE COM-

PONENT FAILURE AS A RESULT OF FAILURE TO FOL-

LOW THE ABOVE INSTALLATION INSTRUCTIONS.

FAILURE TO FOLLOW THE ABOVE INSTALLATION IN-

STRUCTIONS VOIDS THE MANUFACTURER’S EQUIP-

MENT LIMITED WARRANTY. LENNOX DISCLAIMS

ALL LIABILITY IN CONNECTION WITH INSTALLER’S

FAILURE TO FOLLOW THE ABOVE INSTALLATION IN-

STRUCTIONS .

NOTWITHSTANDING THE FOREGOING, INSTALLER

IS RESPONSIBLE FOR CONFIRMING THAT THE USE

OF CONSTRUCTION HEAT IS CONSISTENT WITH THE

POLICIES AND CODES OF ALL REGULATING ENTI-

TIES. ALL SUCH POLICIES AND CODES MUST BE AD-

HERED TO.

General

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.

In addition to the requirements outlined previously, the following general recommendations must be considered when installing a ML193UHE furnace:

• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.

• When the furnace is installed in non-direct vent applications, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.

• When the furnace is installed in non-direct vent applications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.

• When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.

• When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.

• Please consult the manufacturer of your evaporator coil for their recommendations on distance required between the heat exchanger and their drain pan. Adequate space must be provided between the drain pan and the furnace heat exchanger.

Page 5

CAUTION

ML193UHE unit should not be installed in areas normally subject to freezing temperatures.

WARNING

Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine base swimming pool chemicals

Water softening chemicals

De-icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Cements and glues

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

Combustion, Dilution & Ventilation Air

If the ML193UHE is installed as a Non-Direct Vent Furnace, follow the guidelines in this section.

NOTE - In Non-Direct Vent installations, combustion air is taken from indoors or ventilated attic or crawlspace and flue gases are discharged out-doors.

In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.

In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this section to install ML193UHE furnaces to ensure effi cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (AN-

SIZ223.1/ NFPA 54).

This reprinted material is not the complete and official po sition of the ANSI on the referenced subject, which is represented only by the standard in its entirety.

In Canada, refer to the CSA B149 installation codes.

CAUTION

Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.

All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When fireplac es, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insuffi cient air causes incomplete combustion which can result in carbon monoxide.

In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.

The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.

This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the Air from Outside section.

Confined Space

A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room.

Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas-fired equipment in the confined space. Each opening must be at least 100 square inches

(64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12

inches (305 mm) of the bottom. See FIGURE 4.

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE

ROOF TERMINATED

EXHAUST PIPE

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

OPENINGS

(To Adjacent

Unconfined

Space)

NOTE - Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm 2 per .29kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches

(64516mm.

2).

FIGURE 4

Page 6

Air from Outside

If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two perma nent openings. One opening shall be within 12” (305mm) of the top of the enclosure and one within 12” (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rating of all equipment in the enclosure (See

FIGURE 5). It is also permissible to bring in air for combustion from a ventilated attic (FIGURE 6) or ventilated crawl space (FIGURE 7.

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(Inlet Air from Crawl Space and Outlet Air to Outside)

VENTILATION LOUVERS

(Each end of attic)

ROOF TERMINATED

EXHAUST PIPE

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

FURNACE

INLET

AIR

OUTLET

AIR

FIGURE 5

*Intake Debris

Screen

(Provided)

Furnace

LOUVERS

(For unheated crawl space)

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

EQUIPMENT IN CONFINED SPACE

(Inlet Air from Ventilated Attic and Outlet Air to Outside)

Roof Terminated

Exhaust Pipe

Ventilation Louvers

Inlet Air

(Minimum

12 in.(305mm) Above attic floor)

EQUIPMENT IN CONFINED SPACE

(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)

Roof Terminated

Exhaust Pipe

Ventilation

Louvers

(Crawl space)

Furnace

Inlet Air

(Minimum

12 in.(305mm)

Above crawl space floor)

Coupling or

3 in. to 2 in.

Transition

(Field Provided)

*Intake Debris Screen Provided)

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 7

If air from outside is brought in for combustion and ventilation, the confined space must have two permanent open ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches

(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces

(crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of

all equipment in the enclosure. See FIGURE 5 and FIG-

URE 8. When communicating with the outdoors through

horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See

FIGURE 9.

When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have

20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 6

Page 7

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(All Air Through Ventilated Attic)

flexible mounting leg). See FIGURE 10.

The bolt and washer must be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing.

Units with 1/2 or 3/4 HP Blower Motor

ROOF TERMINATED

EXHAUST PIPE

VENTILATION LOUVERS

(Each end of attic)

OUTLET

AIR

RIGID LEG remove shipping bolt and washe

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

FURNACE

INLET AIR

(Ends 12” above bottom)

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 8

EQUIPMENT IN CONFINED SPACE -

ALL AIR FROM OUTSIDE

ROOF TERMINATED

EXHAUST PIPE

OUTLET AIR

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

FURNACE

INLET AIR

NOTE-Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm 2 per .59kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all other equipment in the enclosure.

FIGURE 9

Shipping Bolt Removal

Units with 1/2 and 3/4 hp blower motor are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic wash er (rather than the rubber mounting grommet used with a

FIGURE 10

Installation - Setting Equipment

WARNING

Do not connect the return air duct to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.

WARNING

Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.

Upflow Applications

The ML193UHE gas furnace can be installed as shipped in the upflow position. Refer to figure 12 for clearances.

Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front].

The unit must be level from side to side. Unit may be positioned from level to 1/2” toward the front to aid in

draining. See FIGURE 11.

Allow for clearances to combustible materials as indicated on the unit nameplate.

Page 8

SETTING EQUIPMENT

UPFLOW APPLICATION

Place level on the front blower deck to check side to side

Place level on blower deck screws to check forward tilt

UNIT

FRONT

AIR FLOW

1/2” max.

SIDE VIEW

HORIZONTAL APPLICATION

UNIT

FRONT

AIR FLOW 1/2” max.

FRONT VIEW

END VIEW

Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.

FIGURE 11

Page 9

WARNING

Improper installation of the furnace can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum.

A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.

Installation Clearances

Top

Return Air Guidelines

Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.

Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.

Refer to Engineering Handbook for additional information.

ML193UHE applications which include side return air and a condensate trap installed on the same side of the cabinet (trap can be installed remotely within 5 ft.) require either a return air base or field-fabricated transition to accommodate an optional IAQ accessory taller than 14.5”. See figure 13.

Side Return Air

(with transition and filter)

Left Side Right Side

20” X 25” X 1”

(508mmX635mmX 25mm)

Air Filter

Bottom (Floor)

Top/Plenum

*Front

Back

Sides

1 in. (25 mm)

0

0

0

Vent

Floor 0

0

*Front clearance in alcove installation must be 24 in. (610 mm).

Maintain a minimum of 24 in. (610 mm) for front service access.

Allow proper clearances to accommodate condensate trap.

For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 12

Transition

FIGURE 13

Return

Air

Plenum

Page 10

CONDENSATE

TRAP

FURNACE

FRONT

Optional Return Air Base

(Upflow Applications Only)

AIR FLOW

INDOOR AIR

QUALITY

CABINET

(PCO, Filter

Cabinet, etc.)

IF BASE

IS USED

WITHOUT

IAQ CABINET,

A SINGLE

RETURN AIR

PLENUM

MUST

COVER BOTH

UNIT AND

RETURN

AIR BASE

OPENINGS

3−1/4

(83)

7−1/4

(184)

1 23 (584)

Overall

(Maximum)

1 Unit side return air

Opening

1 Minimum

11 (279)

2 Maximum

14 (356)

5−5/8

(143)

SIDE RETURN

AIR OPENINGS

(Either Side)

1 22−7/16

(570)

Overall

(Maximum)

17−1/2 (446) B Width (50W98)

21 (533) C Width (50W99)

24−1/2 (622) D Width (51W00)

FRONT VIEW

OPTIONAL

RETURN

AIR BASE

23

(584)

26−7/8

(683)

SIDE VIEW

3/4

(19)

NOTE- Optional side return air filter kits are not for use with return air base.

1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.

Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).

2

The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.

Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.

To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.

Removing the Bottom Panel

FIGURE 14

Removing the Bottom Panel

Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall

the bottom cap. See FIGURE 15.

Horizontal Applications

WARNING

Do not install the furnace on its front or back. See

FIGURE 16.

See figure 4.

Screw

Bottom Panel

FIGURE 15

Bottom Cap

Front

FIGURE 16

Back

Page 11

The ML193UHE furnace can be installed in horizontal ap plications with either right- or left-hand air discharge.

Refer to FIGURE 17 for clearances in horizontal applica

tions.

Horizontal Application

Installation Clearances

Right-Hand Discharge

L e f t E n d R i g h t E n d

AIR FLOW

Air

Flow

Air

Flow

Bottom (Floor)**

Left-Hand Discharge

Top

L e f t E n d R i g h t E n d

AIR FLOW

Bottom (Floor)**

Top

Front*

Back

Ends

0

0

0

0

Vent

Floor 0

0

*Front clearance in alcove installation must be 24 in. (610 mm).

Maintain a minimum of 24 in. (610 mm) for front service access.

**An 8” service clearance must be maintained below the unit to provide for servicing of the condensate trap.

For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 17

Suspended Installation of Horizontal Unit

This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or

floor joists, as shown in FIGURE 18, or install the furnace

on a platform, as shown in FIGURE 19. A horizontal sus

pension kit (51W10) may be ordered from Lennox or use equivalent

NOTE - Heavy-gauge sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust piping installation.

Cooling coils and supply and return air plenums must be supported separately.

HORIZONTAL SUSPENSION KIT

Metal Strap

(typical)

Internal Brace

(provided with kit)

Bracket

(typical)

Air

Flow

FIGURE 18

NOTE - When the furnace is installed on a platform or with the horizontal suspension kit in a crawlspace, it must be elevated enough to avoid water damage, accommodate drain trap and to allow the evaporator coil to drain.

Platform Installation of Horizontal Unit

1 - Select location for unit keeping in mind service and

other necessary clearances. See FIGURE 17.

2 - Construct a raised wooden frame and cover frame with a plywood sheet. If unit is installed above finished space, fabricate an auxiliary drain pan to be installed under unit. Set unit in drain pan as shown

in FIGURE 19. Leave 8 inches for service clearance

below unit for condensate trap.

3 - Provide a service platform in front of unit. When installing the unit in a crawl space, a proper support platform may be created using cement blocks.

4 - Route auxiliary drain line so that water draining from this outlet will be easily noticed by the homeowner.

5 - If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.

6 - Continue with exhaust, condensate and intake piping installation according to instructions.

Page 12

INTAKE PIPE

EXHAUST PIPE

*Gas connector may be used for Canadian able by local authority having jurisdiction.

*GAS CONNECTION

Duct System

Use industry-approved standards to size and install the supply and return air duct system. Refer to ACCA Manual

D. This will result in a quiet and low-static system that has

uniform air distribution. See FIGURE 20 for proper duct

installation.

SUPPLY

AIR

SERVICE PLATFORM

RAISED

PLATFORM

FIGURE 19

Return Air -- Horizontal Applications

Return air may be brought in only through the end of a furnace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate in-

stallation. See FIGURE 15.

Filters

This unit is not equipped with a filter or rack. A field-pro vided high velocity rated filter is required for the unit to

operate properly. TABLE 1 lists recommended filter sizes.

A filter must be in place whenever the unit is operating.

WARNING

If a high efficiency filter is being installed as part of this system to ensure better indoor air quality, the filter must be properly sized. High efficiency filters have a higher static pressure drop than standard efficiency glass/foam filters. If the pressure drop is too great, system capacity and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls.

Before using any filter with this system, check the specifications provided by the filter manufacturer against the data given in the appropriate Lennox Product

Specifications bulletin. Additional information is provided in Service and Application Note ACC002 (August 2000).

Furnace

Cabinet Width

17-1/2”

21”

TABLE 1

Side Return

Filter Size

Bottom Return

16 X 25 X 1 (1)

16 X 25 X 1 (1)

16 X 25 X 1 (1)

20 X 25 X 1 (1)

Install self tapping screws to seal any potential air leaks

SUPPLY

AIR

UPFLOW UNIT

HORIZONTAL UNIT

FIGURE 20

NOTE - This furnace is not certified for operation in heat ing mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks. For horizontal units, in stall self tapping screws in the three evaporator coil screw holes made for horizontal applications to seal the top cap to the vestibule panel.

Return Air Plenum

NOTE - Return air must not be drawn from a room where this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood fireplace) is installed.

When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room.

This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas.

This raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system.

Return air can be brought in through the bottom or either side of the furnace (return air brought into either side furnace allowed in upflow applications only). If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely.

Use fiberglass sealing strips, caulking, or equivalent seal ing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.

Page 13

Pipe & Fittings Specifications

All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring.

Refer to the TABLE 2 below for approved piping and fitting

materials

TABLE 2

PIPING AND FITTINGS SPECIFICATIONS

Schedule 40 PVC (Pipe) D1785

Schedule 40 PVC (Cellular Core Pipe)

Schedule 40 PVC (Fittings)

Schedule 40 CPVC (Pipe)

Schedule 40 CPVC (Fittings)

SDR-21 PVC or SDR-26 PVC (Pipe)

SDR-21 CPVC or SDR-26 CPVC (Pipe)

Schedule 40 ABS Cellular Core DWV

(Pipe)

Schedule 40 ABS (Pipe)

Schedule 40 ABS (Fittings)

ABS-DWV (Drain Waste & Vent) (Pipe &

Fittings)

PVC-DWV (Drain Waste & Vent) Pipe &

Fittings)

F891

D2466

F441

F438

D2241

F442

F628

D1527

D2468

D2661

D2665

PRIMER & SOLVENT CEMENT

PVC & CPVC Primer

PVC Solvent Cement

CPVC Solvent Cement

ABS Solvent Cement

PVC/CPVC/ABS All Purpose Cement

For Fittings & Pipe of the same material

ABS to PVC or CPVC Transition Solvent

Cement

CANADA PIPE & FITTING & SOLVENT

CEMENT

PVC & CPVC Pipe and Fittings

PVC & CPVC Solvent Cement

ABS to PVC or CPVC Transition

Cement

POLYPROPYLENE VENTING SYSTEM

PolyPro® by Duravent

ASTM

SPECIFICATION

F656

D2564

F493

D2235

D2564, D2235,

F493

D3188

MARKING

ULCS636

InnoFlue® by Centrotherm

UL 1738 CERTIFIED GAS VENTING SYSTEM

PEX System1738 Schedule 40 PVC

Pipes and Fittings

IPEX System1738 PVC FGV Cement &

Primer

UL1738

CAUTION

Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of ignition.

Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.

IMPORTANT

ML193UHE exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the

PVC fittings in the unit.

Use PVC primer and solvent cement or ABS solvent ce-

ment meeting ASTM specifications, refer to TABLE 2.

As an alternate, use all purpose cement, to bond ABS,

PVC, or CPVC pipe when using fittings and pipe made of the same materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.

Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.

Canadian Applications Only - Pipe, fittings, primer and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a single manu facturer as part of an approved vent (exhaust) system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.

Page 14

Input Size

030,

045

070

090

110

Vent Pipe

Dia. in.

6 1-1/2

2

2-1/2

3

6 1-1/2

2

2-1/2

3

2

2-1/2

3

2

2-1/2

3

Flush

Mount Kit

51W11

(US)

51W12

(CA)

3

3

3

3

3

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

YES

YES

YES

YES

YES

YES

YES

YES

TABLE 3

OUTDOOR TERMINATION USAGE*

STANDARD

Wall Kit

3 inch 2 inch

22G44

(US)

4 30G28

(CA)

44J40 (US)

4 81J20

(CA)

Field

Fabricated

YES

YES

YES

YES

YES

YES

YES

YES

1

1

1

1

1

1

1

1

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

5

5

5

5

5

5

5

5

5

5

YES

YES

YES

YES

YES

YES

YES

YES

5 YES

5 YES

YES

YES

5 YES

5 YES

1-1.2 inch

4

71M80

44W92

2

2

2

2

2

2

2

2

(US)

(CA)

YES

YES

YES

YES

YES

YES

YES

YES

CONCENTRIC

4

2 inch

69M29

(US)

44W92

(CA)

YES

YES

YES

YES

YES

YES

4

3 inch

60L46 (US)

44W93

(CA)

YES

YES

YES

YES

YES

YES

NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See vent length tables.

* Kits must be properly installed according to kit instructions.

1Requires field-provided outdoor 1-1/2” exhaust accelerator.

2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when uses with 030, 045 and 070 input models. When using 1-1/2 inch vent pipe, transistion to 2” pipe before installing concentric kit.

3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 030, 045, 070 and 090 input models.When using 1-1/2” vent pipe, transition to 2” pipe before installing flushmount kit.

4 Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.

5 See table 8 for vent accelerator requirements.

6 Requires field provided 2” to 1-1/2” reducer.

Joint Cementing Procedure

All cementing of joints should be done according to the specifications outlined in ASTM D 2855.

NOTE - A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.

DANGER

DANGER OF EXPLOSION!

Fumes from PVC glue may ignite during system check.

Allow fumes to dissipate for at least 5 minutes before placing unit into operation..

1 - Measure and cut vent pipe to desired length.

2 - Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.

3 - Clean and dry surfaces to be joined.

4 - Test fit joint and mark depth of fitting on outside of pipe.

5 - Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.

NOTE - Time is critical at this stage. Do not allow primer to dry before applying cement.

6 - Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.

Page 15

7 - Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe

1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn

ABS or cellular core pipe.

NOTE - Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe.

8 - After assembly, wipe excess cement from pipe at end of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent.

9 - Handle joints carefully until completely set.

Venting Practices

Piping Suspension Guidelines

SCHEDULE 40

PVC - 5' all other pipe* - 3'

Exhaust Piping (FIGURE 25 and FIGURE 26)

Route piping to outside of structure. Continue with installation following instructions given in piping termination section.

REPLACING FURNACE THAT WAS PART OF A

COMMON VENT SYSTEM

CHIMNEY

OR GAS

VENT

(Check sizing for water heater only)

FURNACE

(Replaced)

WATER

HEATER

OPENINGS

(To Adjacent

Room)

* See Piping and Fittings Specifications table

NOTE - Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.

i n s i d

Wall Thickness Guidelines

24” maximum

3/4” minimum e

Wall o u t s i d e

FIGURE 21

1 - In areas where piping penetrates joists or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.

2 - When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.

If replacing a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.

FIGURE 22

CAUTION

Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.

CAUTION

The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.

Vent Piping Guidelines

NOTE - Lennox has approved the use of DuraVent® and

Centrotherm manufactured vent pipe and terminations as an option to PVC. When using the PolyPro ® by Du raVent or InnoFlue® by Centrotherm venting system the vent pipe requirements stated in the unit installation in struction – minimum & maximum vent lengths, termination clearances, etc. – apply and must be followed. Follow the instructions provided with PoyPro by DuraVent and Inno -

Flue by Centrotherm venting system for assembly or if re quirements are more restrictive. The PolyPro by Duravent and InnoFlue by Centrotherm venting system must also follow the uninsulated and unconditioned space criteria

listed in TABLE 7.

Page 16

The ML193UHE can be installed as either a Non-Direct

Vent or a Direct Vent gas central furnace.

NOTE - In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out doors. In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing - Size pipe according to

TABLE 4 and TABLE 5. Count all elbows inside and outside

the home. TABLE 4 lists the minimum vent pipe lengths

permitted. TABLE 5 lists the maximum pipe lengths per-

mitted. Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Ex haust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the

exhaust gas as it exits the termination. Refer to TABLE 8.

In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications.

NOTE - The exhaust collar on all models is sized to ac commodate 2” Schedule 40 vent pipe. In horizontal ap plications, any transition to exhaust pipe larger than 2” must be made in vertical runs of the pipe. Therefore a 2” elbow must be added before the pipe is transitioned to any size larger than 2”. This elbow must be added to the elbow count used to determine acceptable vent lengths.

Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.

Horizontal Installation Offset Requirements

Exhaust Pipe

12” Max.

12” Min.

Horizontal

Gas Furnace

NOTE ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm) of horizontal run is mandatory for drainage.

NOTE - Exhaust pipe MUST be glued to furnace exhaust fitting, unless the optional glueless vent adapter kit 17H92 is used..

NOTE - Exhaust piping should be checked carefully to make sure there are no sags or low spots.

FIGURE 23

NOTE - Lennox offers a glueless vent adapter kit 17H92 as an option for exhaust exiting at the furnace top cap coupling. If the kit is not used then the exhaust pipe MUST be glued to the furnace exhaust fitting.

Piping Size Process

1

What is the furnace capacity?

2

Which style termination being used?

Standard or concentric?.

3

Which needs most elbows?

Intake or exhaust?

4

How many elbows?

Count all elbows inside and outside house.

5

Desired pipe size?

6

What is the altitude of the furnace installation?

7

Find max intake or exhaust pipe length.

Includes all vent pipe and elbows inside and outside the house.

FIGURE 24

IMPORTANT

Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations.

TABLE 4

MINIMUM VENT PIPE LENGTHS

ML193UHE Model

030, 045, -070, -090, 110

MIN. VENT LENGTH*

15 ft. or 5 ft. plus 2 elbows or 10 ft. plus 1 elbow

*Any approved termination may be added to the minimum length listed. Two 45 degree elbows are the equivalent to one

90 degree elbow.

Page 17

Number

Of 90°

Elbows

Used

6

7

4

5

1

2

3

8

9

10

Number

Of 90°

Elbows

Usedl

5

6

7

8

9

10

3

4

1

2

TABLE 5

Maximum Allowable Intake or Exhaust Vent Length in Feet

NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size .

NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.

030/

045

25

20

15

10 n/a

030/

045

20

15

10 n/a

1-1/2” Pipe

Model

070

Standard Termination at Elevation 0 - 10,000

2” Pipe

Model

2-1/2” Pipe

Model

090 110 030/ 070 090 110

030/

045

070 090

20 81 66 44 24 115 100 68

15

10 n/a n/a

56

51

46

41

76

71

66

61

41

36

31

26

61

56

51

46

39

34

29

24

19

14 n/a

19

14 n/a

90

85

80

75

110

105

100

95

75

70

65

60

95

90

85

80

43

38

33

28

63

58

53

48

36 21 70 55 23

1-1/2” Pipe

Model

070

Concentric Termination Elevation 0 - 10,000

2” Pipe

Model

2-1/2” Pipe

Model

090 110 030/ 070 090 110

030/

045

070 090

15 73 58 42 22 105 90 64

10 68 53 37 17 100 85 59

12 n/a n/a n/a

63

58

53

48

43

38

33

28

48

43

38

33

28

23

18

13

32

27

22

17

12 n/a n/a

95

90

85

80

75

70

65

60

80

75

70

65

60

55

50

45

54

49

44

39

34

29

24

19

110

28

23

18

13

43

38

33 n/a

110

39

34

29

24

19

14 n/a

030/

045

137

112

107

102

97

92

132

127

122

117

030/

045

121

116

111

106

101

96

91

86

81

76

3” Pipe

Model

070 090 110

101

96

91

86

121

116

111

106

81

76

137

132

127

122

117

112

107

102

97

92

3” Pipe

Model

94

89

84

79

114

109

104

99

74

69

118

113

108

103

98

93

88

83

78

73

94

89

84

79

114

109

104

99

74

69

118

113

108

103

98

93

88

83

78

73

070 090 110

TABLE 6

VENT LENGTHS (EXHAUST) - VENTILATED ATTIC OR CRAWLSPACE INTAKE AIR - FEET

STANDARD TERMINATION AT ELEVATION 0 - 10,000 ft.

Pipe Size

1 20

1-1/2 in.

070 090 110 030/

045

070

2 in.

090 110 030/

045

2-1/2 in.

070 090 110 030/

045

070

3 in.

090 110

15 N/A N/A 71 56 34 14 100 100 78 43 118 117 98 98

No. of

90 ELL

2

3

4

5

6

7

8

9

10

15 10 N/A N/A 66 51 29 9 95 95 73 38 113 112 93 93

10 N/A N/A N/A 61 46 24 4 90 90 68 33 108 107 88 88

N/A N/A N/A N/A 56 41 19 N/A 85 85 63 28 103 102 83 83

N/A N/A N/A N/A 51 36 14 N/A 80 80 58 23 98 97 78 78

N/A N/A N/A N/A 46 31 9 N/A 85 75 63 18 93 92 73 73

N/A N/A N/A N/A 41 26 4 N/A 70 70 48 13 88 87 68 68

N/A N/A N/A N/A 36 21 N/A N/A 65 65 43 8 83 82 63 63

N/A N/A N/A N/A 31 16 N/A N/A 60 60 38 3 78 77 58 58

N/A N/A N/A N/A 26 11 N/A N/A 55 55 33 N/A 73 72 53 53

NOTES - Additional vent pipe and elbows used to terminate vent pipe outside the structure must be included in the total vent length calculation.

Page 18

Exhaust

DO NOT transition from larger to smaller pipe in horizontal runs of exhaust pipe.

TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW

DIRECT OR NON-DIRECT VENT APPLICATIONS

EXHAUST INTAKE EXHAUST INTAKE

2”

2”

2” or

2”

2” 3” 3”

Exhaust

DO NOT transition from smaller to larger pipe in horizontal runs of exhaust pipe.

2”

030/045/070 Only

1−1/2”

TRANSITION

2” 6” Min

Exhaust

* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.

NOTE − Exhaust pipe and intake pipe must be the same diameter.

FIGURE 25

TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR

NON-DIRECT VENT APPLICATIONS (RIGHT HAND DISCHARGE SHOWN)

12” max.

45°

MAX

EXHAUST

2” or 2”

Exhaust

2”

2”

INTAKE

2”

2”

2” or

2”

2”

2”

DO NOT transition from smaller to larger pipe in horizontal runs of exhaust pipe.

SIDE VIEW

45°

MAX

3”

Exhaust

EXHAUST

*2”

*2”

3”

*2”

DO NOT transition from larger to smaller pipe in horizontal runs of exhaust pipe.

030/045/070 Only

1−1/2”

TRANSITION

*2”

INTAKE

*2”

Exhaust

* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.

NOTE − Exhaust pipe and intake pipe must be the same diameter.

*2”

FIGURE 26

Page 19

Intake Piping

The ML193UHE furnace may be installed in either direct vent or non-direct vent applications. In non-direct vent applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.

Follow the next two steps when installing the unit in Direct

Vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors.

The provided air intake screen must not be used in direct vent applications (outdoors).

1 - Use transition solvent cement or a sheet metal screw to secure the intake pipe to the inlet air connector.

2 - Route piping to outside of structure. Continue with installation following instructions given in general guide lines for piping terminations and intake and exhaust piping terminations for direct vent sections.

Refer to TABLE 5 for pipe sizes.

TYPICAL AIR INTAKE PIPE CONNECTIONS

UPFLOW NON−DIRECT

VENT APPLICATIONS

INTAKE

DEBRIS

SCREEN

(Provided)

Min 2”

NOTE - Debris screen and elbow may be rotated, so that screen may be positioned to face forward or to either side.

FIGURE 27

TYPICAL AIR INTAKE PIPE CONNECTIONS

HORIZONTAL NON−DIRECT VENT APPLICATIONS

(Horizontal Right−Hand Air Discharge Application Shown)

PVC pipe coupling

Min 2”

OR

INTAKE

DEBRIS

SCREEN

(Provided)

NOTE - Debris screen may be positioned straight out

(preferred) or with an elbow rotated to face down.

FIGURE 28

Follow the next two steps when installing the unit in Non-

Direct Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors.

1 - Use field-provided materials and the factoryprovided air intake screen to route the intake piping

as shown in FIGURE 27 or FIGURE 28. Maintain

a minimum clearance of 3” (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed forward or to either side in the upflow position, and either straight out or downward in the horizontal position.

The air intake piping must not terminate too close to the flooring or a platform. Ensure that the intake air inlet will not be obstructed by loose insulation or other items that may clog the debris screen.

2 - If intake air is drawn from a ventilated attic (FIGURE

29) or ventilated crawlspace (FIGURE 30) the exhaust

vent length must not exceed those listed in TABLE 7.

If 3” diameter pipe is used, reduce to 2” diameter pipe at the termination point to accommodate the debris screen. Use a sheet metal screw to secure the intake pipe to the connector, if desired.

3 - Use a sheet metal screw to secure the intake pipe to the connector, if desired.

Page 20

CAUTION

If this unit is being installed in an application with combustion air coming in from a space serviced by an exhaust fan, power exhaust fan, or other device which may create a negative pressure in the space, take care when sizing the inlet air opening. The inlet air opening must be sized to accommodate the maximum volume of exhausted air as well as the maximum volume of combustion air required for all gas appliances serviced by this space.

EQUIPMENT IN CONFINED SPACE

(Inlet Air from Ventilated Attic and Outlet Air to Outside)

Roof Terminated

Exhaust Pipe

Ventilation Louvers

Inlet Air

(Minimum

12 in.(305mm) Above attic floor)

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 29

EQUIPMENT IN CONFINED SPACE

(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)

Roof Terminated

Exhaust Pipe

Ventilation

Louvers

(Crawl space)

Furnace

*Intake Debris

Screen

(Provided)

Furnace

Inlet Air

(Minimum

12 in.(305mm)

Above crawl space floor)

Coupling or

3 in. to 2 in.

Transition

(Field Provided)

*Intake Debris Screen Provided)

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 30

General Guidelines for Vent Terminations

In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the out doors. The ML193UHE is then classified as a non-direct vent, Category IV gas furnace.

In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the out doors. The ML193UHE is then classified as a direct vent,

Category IV gas furnace.

In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel

Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current

CSA-B149 Natural Gas and Propane Installation Codes in

Canada for details.

Position termination according to location given in FIG-

URE 32 or FIGURE 33. In addition, position termination so

it is free from any obstructions and 12” above the average snow accumulation.

At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings).

It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of an outdoor AC unit because the condensate can damage the painted coating.

NOTE -

See TABLE 7 for maximum allowed exhaust pipe

length without insulation in unconditioned space during winter design temperatures below 32°F (0°C). If required exhaust pipe should be insulated with 1/2” (13mm) Ar maflex or equivalent. In extreme cold climate areas, 3/4”

(19mm) Armaflex or equivalent may be necessary. Insu lation must be protected from deterioration. Armaflex with

UV protection is permissable. Basements or other en closed areas that are not exposed to the outdoor ambient temperature and are above 32 degrees F (0°C) are to be considered conditioned spaces.

IMPORTANT

Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze-ups and may block the terminations.

IMPORTANT

For Canadian Installations Only:

In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).

Page 21

Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For

Winter Design Temperatures Single - Stage High Efficiency Furnace

Winter Design

Temperatures1 °F

(°C)

Vent Pipe

Diameter 030

TABLE 7

045

Unit Input Size

070 090 110

PVC 2 PP PVC 2 PP PVC 2 PP PVC 2 PP PVC 2 PP

32 to 21

(0 to -6)

20 to 1

(-7 to -17)

1-1/2”

2 in

2-1/2 in

3 in

1-1/2”

2 in

2-1/2 in

3 in

1-1/2”

N/A N/A

25

18

13

9

15

9

5

1

10

N/A

16

N/A

9

N/A

8

N/A

1

N/A

20

31

24

18

20

18

13

8

15

N/A

28

N/A

18

N/A

16

N/A

8

N/A

N/A

50

42

35

N/A

32

24

19

N/A

N/A

48

N/A

35

N/A

29

N/A

19

N/A

N/A

30

56

47

N/A

30

34

26

N/A

0 to -20

(-18 to -29)

2 in

2-1/2 in

5

1

3

N/A

12

7

10

N/A

22

15

19

N/A

30

22

27

N/A

3 in N/A N/A 2 2 10 10 16 16

1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.

2 Poly-Propylene vent pipe (PP) by Duravent and Centrotherm.

NOTE - Concentric terminations are the equivalent of 5’ and should be considered when measuring pipe length.

NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.

N/A

30

N/A

47

N/A

30

N/A

26

N/A

NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See FIGURE 31.

Conditioned

Space

Conditioned

Space

Pipe Insulation

Unconditioned

Space

FIGURE 31

Page 22

Exhaust

Pipe

Intake

Pipe

VENT TERMINATION CLEARANCES

FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA

INSIDE CORNER

DETAIL

G

A

H

D

E

B

L

F

C

Fixed

Closed

Operable

B

Operable

B

Fixed

Closed

I

M

B

A

J

K

B

A =

VENT TERMINAL

Clearance above grade, veranda, porch, deck or balcony

AIR SUPPLY INLET

US Installations 1

12 inches (305mm) or 12 in. (305mm) above average snow accumulation.

AREA WHERE TERMINAL

IS NOT PERMITTED

Canadian Installations 2

12 inches (305mm) or 12 in. (305mm) above average snow accumulation.

B = Clearance to window or door that may be opened

4 feet (1.2 m) below or to side of opening;

1 foot (30cm) above opening

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

* 12” C = Clearance to permanently closed window

* 12”

D =

E =

F =

G =

Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (610 mm) from the center line of the terminal

Clearance to unventilated soffit

Clearance to outside corner

Clearance to inside corner

* Equal to or greater than soffit depth.

* Equal to or greater than soffit depth.

* No minimum to outside corner

*

* Equal to or greater than soffit depth.

* Equal to or greater than soffit depth.

* No minimum to outside corner

*

H =

I = tended above meter / regulator assembly

Clearance to service regulator vent outlet

Clearance to non-mechanical air

* 3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

* 3 feet (.9m)

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

3 feet (.9m)

J = pliance

4 feet (1.2 m) below or to side of opening;

1 foot (30 cm) above opening

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

6 feet (1.8m) K =

L = ply inlet

Clearance above paved sidewalk or paved driveway located on public property

3 feet (.9m) above if within 10 feet

(3m) horizontally

7 feet (2.1m)† 7 feet (2.1m)†

M = Clearance under veranda, porch, deck or balcony

*12 inches (305mm)‡

1

In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code

2

In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.

12 inches (305mm)‡

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA

B149.1, clearance will be in accordance with local installation codes and the requirements of the lation instructions.”

FIGURE 32

Page 23

VENT TERMINATION CLEARANCES

FOR DIRECT VENT INSTALLATIONS IN THE US AND CANADA

INSIDE CORNER

DETAIL

G

A

H

D

E

B

L

F

C

Fixed

Closed

Operable

B

Operable

B

Fixed

Closed

I

M

B

J

K

A

B

A =

B =

VENT TERMINAL

Clearance above grade, veranda, porch, deck or balcony

Clearance to window or door that may be opened

AIR SUPPLY INLET

US Installations 1

12 inches (305mm) or 12 in. (305mm) above average snow accumulation.

AREA WHERE TERMINAL

IS NOT PERMITTED

Canadian Installations 2

12 inches (305mm) or 12 in. (305mm) above average snow accumulation.

6 inches (152mm) for appliances <10,000 pliances > 10,000 Btuh (3kw) and <50,000 pliances > 50,000 Btuh (15kw)

* 12”

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

* 12” C = Clearance to permanently closed window

D =

E =

F =

G =

H =

Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (610mm) from the center line of the terminal

Clearance to unventilated soffit

Clearance to outside corner

Clearance to inside corner

* Equal to or greater than soffit depth

* Equal to or greater than soffit depth

* No minimum to outside corner

*

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

* Equal to or greater than soffit depth

* No minimum to outside corner

*

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

3 feet (.9m) I = tended above meter / regulator assembly

Clearance to service regulator vent outlet

Clearance to non-mechanical air

* 3 feet (.9m)

J = 6 inches (152mm) for appliances <10,000

K =

L =

M = pliances > 10,000 Btuh (3kw) and <50,000 pliance ply inlet

Clearance above paved sidewalk or paved driveway located on public property

Clearance under veranda, porch, deck or balcony pliances > 50,000 Btuh (15kw)

3 feet (.9m) above if within 10 feet

(3m) horizontally

* 7 feet (2.1m)

*12 inches (305mm)‡

1

In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code

2

In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

6 feet (1.8m)

7 feet (2.1m)†

12 inches (305mm)‡

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA

B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions.”

FIGURE 33

Page 24

Details of Intake and Exhaust Piping Terminations for

Direct Vent Installations

NOTE - In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.

NOTE - Flue gas may be slightly acidic and may adverse ly affect some building materials. If any vent termination is used and the flue gases may impinge on the building material, a corrosion-resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommend ed. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an

appropriate sealant. See FIGURE 41.

Intake and exhaust pipes may be routed either horizontal ly through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the

roof is preferred. FIGURE 34 through FIGURE 42 show

typical terminations.

1 - Intake and exhaust terminations are not required to be in the same pressure zone. You may exit the intake on one side of the structure and the exhaust

on another side (FIGURE 35). You may exit the

exhaust out the roof and the intake out the side of

the structure (FIGURE 36).

NOTE - When venting in different pressure zones, maximum separation of intake and exhaust pipe DO

NOT apply.

2 - Intake and exhaust pipes should be placed as close together as possible at termination end (refer to illustrations). Maximum separation is 3” (76mm) on roof terminations and 6” (152mm) on side wall terminations.

NOTE - When venting in different pressure zones, the maximum separation requirement of intake and exhaust pipe DOES NOT apply.

3 - terminate straight down using two 90° elbows (See

FIGURE 34).

4 - Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake

piping. See TABLE 8.

5 - On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches

(305mm) for 2” PVC and 20 inches (508mm) for 3”

(76mm) PVC beyond the outside wall. Intake piping should be as short as possible.

6 - On field supplied terminations, a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8” and a minimum distance of 6” with a termination elbow.

NOTE - Care must be taken to avoid recirculation of exhaust back into intake pipe.

TABLE 8

Exhaust Pipe Termination Size Reduction

ML193UHE Model Termination Pipe Size

1-1/2” (38mm) *030, *045, *070

*090

110

2” (51mm)

*Use the provided 1-1/2” accelerator if matched with the flushmount termination.

Inches(mm)

3”(76mm) MAX.

UNCONDITIONED

ATTIC SPACE

8” (203mm) MIN

12” (305mm) ABOVE

AVERAGE SNOW

ACCUMULATION

Exhaust

Pipe

3” (76mm) OR

2” (51mm) PVC

PROVIDE SUPPORT

FOR INTAKE AND

EXHAUST LINES

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 34

Exiting Exhaust and Intake Vent

(different pressure zone)

Furnace

Inlet Air

(Minimum 12 in.

305 MM) above grade or snow accumulation

FIGURE 35

Exiting Exhaust and Intake Vent

(different pressure zone)

Roof Terminated

Exhaust Pipe

Furnace

Inlet Air

(Minimum 12 in.

305 MM) above grade or snow accumulation

FIGURE 36

Page 25

7 - If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported. At least one bracket must be used within 6” from the top of the elbow and then every 24” (610mm) as shown

in FIGURE 41, to prevent any movement in any

direction. When exhaust and intake piping must be run up an outside wall, the exhaust piping must be

terminated with pipe sized per TABLE 8.The intake

piping may be equipped with a 90° elbow turndown.

Using turn-down will add 5 feet (1.5m) to the equivalent length of the pipe.

8 - A multiple furnace installation may use a group of up to four terminations assembled together horizontally,

as shown in FIGURE 39.

12” (305mm)

Minimum

Above Average

Snow

Accumulation

Accelerator not required for

3” concentric

INTAKE

FLASHING

(Not Furnished)

CLAMP

SHEET METAL STRAP

(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)

FIELD-PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT DIFFERENT VENT

PIPE SIZE TO TERMINATION

DIRECT VENT CONCENTRIC ROOFTOP TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

FIGURE 37

EXHAUST

VENT

INTAKE

AIR

5”

(127mm)

(305mm)

5-1/2”

(140mm)

12”

Inches (mm)

18” MAX.

(457mm)

EXHAUST VENT

Front View

INTAKE

AIR

12” (305mm) Min.

above grade or cumulation.

optional intake elbow

Side View

OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT

INSTALLATION OF DIRECT VENT WALL TERMINATION KIT

(30G28 or 81J20)

FIGURE 39

2” EXTENSION FOR 2” PVC

PIPE1” EXTENSION FOR 3”

PVC PIPE

4''

FURNACE

EXHAUST

PIPE

FURNACE

INTAKE

PIPE

GLUE EXHAUST

END FLUSH INTO

TERMINATION

FLAT

SIDE 1-1/2” ACCELERATOR

FLUSH-MOUNT SIDE WALL TERMINATION KIT

51W11 (US) or 51W12 (Canada)

FIGURE 40

FIELD-PROVIDED

REDUCER MAY BE

REQUIRED TO ADAPT

DIFFERENT VENT PIPE

SIZE TO TERMINATION

OUTSIDE

WALL

EXHAUST

AIR

Accelerator not required for 3” concentric

EXHAUST

AIR

INTAKE

AIR

CLAMP

(Not Furnished)

12” (305mm) Min.

above grade or average snow ac cumulation.

GRADE

DIRECT VENT CONCENTRIC WALL TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

FIGURE 38

Page 26

* WALL

SUPPORT

C1

NOTE − FIELD−PROVIDED

REDUCER MAY BE

REQUIRED TO ADAPT

LARGER VENT PIPE SIZE

TO TERMINATION

C1

E

A

D

B

A

FIELD FABRICATED WALL TERMINATION

Intake

Elbow

C2

D

B

2” (51mm)

Vent Pipe

A − Minimum clearance above grade or average snow accumulation

B − Maximum horizontal

separation between

intake and exhaust

C1 -

Minimum from end of exhaust to inlet of intake

12” (305 mm)

6” (152 mm)

8” (203 mm)

STRAIGHT

APPPLICATION

A

C2 -

Minimum from end of exhaust to inlet of intake

6” (152 mm)

D

B

EXTENDED

APPLICATION

C2

E

A

B

D

3” (76mm)

Vent Pipe

12” (305 mm)

6” (152 mm)

8” (203 mm)

6” (152 mm)

D − Maximum exhaust pipe length

E − Maximum wall support distance from top of each pipe (intake/exhaust)

12” (305 mm)

6” (152 mm)

20” (508 mm)

6” (152 mm)

See maximum allowable venting tables for venting lengths with this arrangement.

* Use wall support every 24” (610 mm). Use two wall supports if extension is greater than

24” (610 mm) but less than 48” (1219 mm).

NOTE − One wall support must be within 6” (152 mm) from top of each pipe (intake and exhaust) to prevent movement in any direction.

2

2

B

B

A

E

C

C

ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)

D

1

Intake

Elbow

B

A

C

D

3

1

A

- Clearance above

Grade or average snow accumulation

B

- Horizontal separation between intake and exhaust

2” (51mm)

Vent Pipe

6” (152mm)min

24” (610mm )Max

C

- Minimum from end of exhaust to inlet of intake

D

- Exhaust pipe length

9” (227mm)

12” (305mm)min

16” (405mm )Max

E

- Wall support distance from top of each pipe

(intake/exhaust)

6” (152mm) Max

3” (76mm)

Vent Pipe

12” (305 mm) Min 12” (305 mm) Min

6” (152mm)min

24” (610mm )Max

9” (227mm)

12” (305mm)min

16” (405mm )Max

6” (152mm) Max

D

E

D

Exhaust

D

1

B

E

B

Front View of

Intake and Exhaust

12”

C

12” 2

A

A

C

Intake

Exhaust

A

1 The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration. In horizontal tee applications there must be be a minimum of 3 ft away from covered patios or any living ares and cannot be within 3 ft of a window. Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.

2

3

As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield

(24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material.

All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.

Exhaust pipe 45 ° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.

FIGURE 41

Page 27

DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

STRAIGHT-CUT OR

ANGLE-CUT IN DIRECTION

OF ROOF SLOPE *

8” - 12”

(203mm - 305mm)

Minimum 12” (305MM) above chimney top plate or average snow accumulation

INTAKE PIPE

INSULATION (optional)

SHEET

METAL TOP

PLATE

3” - 8”

(76mm-

203mm)

INSULATE

TO FORM

SEAL

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

ALTERNATE

INTAKE PIPE

3” - 8”

(76mm-

203mm)

EXTERIOR

PORTION OF

CHIMNEY

3 - If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm).

When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.

Distance between exhaust pipe terminations on multiple furnaces must meet local codes.

NON-DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

STRAIGHT-CUT OR

ANGLE-CUT IN DIRECTION

OF ROOF SLOPE

NOTE - Do tical discharge through an existing unused chimney or stack is required, insert piping inside trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 42

Details of Exhaust Piping Terminations for Non-Direct

Vent Applications

Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is

preferred. FIGURE 43 and FIGURE 44 show typical ter-

minations.

1 - Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed

in TABLE 8.The Specified pipe size ensures proper

velocity required to move the exhaust gases away from the building.

2 - On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches

(305mm) for 2” PVC and 20 inches (508mm) for 3”

(76mm) PVC beyond the outside wall.

12” (305mm)

ABOVE AVE.

SNOW

ACCUMULATION

Minimum 12” (305MM) above chimney top plate or average snow accumulation

SHEET

METAL TOP

PLATE

INSULATE

TO FORM

SEAL

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

EXTERIOR

PORTION OF

CHIMNEY

NOTE - Do tical discharge through an existing unused chimney or stack is required, insert piping inside trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 44

Crawl Space and Extended Horizontal Venting

Lennox provides kit 51W18 (USA) kit 15Z70 (Canada) to install 2” or 3” PVC exhaust piping through the floor joists and into the crawl space. See figure below.

This kit can also be used as a supplemental drain for installations with condensate run back in the vent pipe (ie. long horizontal runs, unconditioned spaces, etc.).

Venting In A Crawl Space

3” (76mm) OR

2” (51mm) PVC

PROVIDE SUPPORT

FOR EXHAUST LINES

UNCONDITIONED

ATTIC SPACE

NON-DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 43

Page 28

Basement Floor

KIT 51W18

(USA)

KIT 15Z70

(CANADA)

Condensate Piping

This unit is designed for either right- or left-side exit of condensate piping in upflow applications. In horizontal applications, the condensate trap must extend below the unit. An 8” service clearance is required for the conden-

sate trap. Refer to figures FIGURE 45 and FIGURE 47

for condensate trap locations. FIGURE 53 shows trap as-

sembly using 1/2” PVC or 3/4” PVC.

NOTE - If necessary the condensate trap may be installed up to 5’ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.

1 - Determine which side condensate piping will exit the unit, location of trap, field-provided fittings and length of PVC pipe required to reach available drain.

NOTE - Do not remove the rubber grommet used to seal the cabinet on the side not used when installing the condensate trap.

2 - Use a large flat head screw driver or a 1/2” drive

socket extension and remove plug (FIGURE 45)

from the cold end header box at the appropriate location on the side of the unit. Install provided 3/4

NPT street elbow fitting into cold end header box.

Use Teflon tape or appropriate pipe dope.

NOTE - Cold end header box drain plugs are facto ry installed. Check the unused plug for tightness to prevent leakage.

3 - Install the cap over the clean out opening at the base

of the trap. Secure with clamp. See FIGURE 53.

4 - Install drain trap using appropriate PVC fittings, glue all joints. Glue the provided drain trap as shown

in FIGURE 53. Route the condensate line to an

open drain. Condensate line must maintain a 1/4” downward slope from the furnace to the drain.

CONDENSATE TRAP AND PLUG LOCATIONS

(Unit shown in upflow position)

Trap

(same on right side)

1-1/2 in.

Plug

(same on left side)

NOTE - In upflow applications where side return sate trap, filter rack must be installed beyond condensate trap or trap must be re-located to avoid interference.

FIGURE 45

5 - FIGURE 48 and FIGURE 50 show the furnace and

evaporator coil using a separate drain. If necessary the condensate line from the furnace and evaporator

coil can drain together. See FIGURE 49, FIGURE 51 and FIGURE 52.

Upflow furnace (FIGURE 51)

- In upflow furnace applications the field provided vent must be a mini mum 1” to a maximum 2” length above the conden sate drain outlet connection. Any length above 2” may result in a flooded heat exchanger if the com bined primary drain line were to become restricted.

Horizontal furnace (FIGURE 52)

- In horizontal fur nace applications the field provided vent must be a minimum 4” to a maximum 5” length above the con densate drain outlet connection. Any length above

5” may result in a flooded heat exchanger if the com bined primary drain line were to become restricted.

NOTE - In horizontal applications it is recommended to install a secondary drain pan underneath the unit and trap assembly.

NOTE - Appropriately sized tubing and barbed fit ting may be used for condensate drain. Attach to the

drain on the trap using a hose clamp. See FIGURE

46.

CAUTION

Do not use copper tubing or existing copper condensate lines for drain line.

6 - If unit will be started immediately upon completion of installation, prime trap per procedure outlined in Unit

Start-Up section.

Field Provided Drain Components

Elbow

Tubing

Barbed Fitting

Hose Clamp

FIGURE 46

Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) - kit no. 26K68 and 24 ft.

(7.3m) - kit no. 26K69.

Page 29

CONDENSATE TRAP LOCATIONS

(Unit shown in upflow position with remote trap)

FieldProvidedVent

Min. 1” AboveCondensate

DrainConnection

1” Min.

2” Max.

*5’ max.

PVCPipeOnly

Trap Can Be Installed a

Maximum 5’ From Furnace

To Drain

*Piping from furnace must slope down a minimum 1/4” per ft. toward trap

FIGURE 47

Furnace With Evaporator

Coil Using A Separate Drain

Evaporator drain line required

(Trap at coil is optional)

Field Provided Vent

(1” min. 2” max. above condensate connection)

Condensate

DrainConnection

Condensate Trap With Optional Overflow Switch

From Evaporator Coil

HorizontalFurnace4” Min. to 5” Max.above

condensatedrain connection)

FurnaceCondensate

DrainConnection

Optional

FIGURE 49

FIGURE 48

Page 30

Furnace with Evaporator Coil Using a Separate Drain

(Unit shown in horizontal left-hand discharge position)

Evaporator

Coil

Field Provided Vent

(4” min. to 5” max. above condensate connection)

Condensate

DrainConnection

4”min

5”max

5’ max.

PVC Pipe Only

Drain Pan

(Trap at coil is optional)

Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap

.

Furnace with Evaporator

Coil Using a Common Drain

(Trap at coil is optional)

Evaporator drain line required

FIGURE 50

IMPORTANT

When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in order for the furnace pressure switch to operate properly.

(1” min. to 2” Max.above

condensatedrain connection)

Condensate

DrainConnection

FIGURE 51

Furnace with Evaporator Coil Using a Common Drain

(Unit shown in horizontal left−hand discharge position)

Drain Pan

Evaporator

Coil

Condensate Drain

Connection

4”min

5”max

5’ max.

PVC Pipe Only

(Trap at coil is optional)

Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap

(4” min. to 5” Max.above

condensatedrain connection)

FIGURE 52

Page 31

TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC

Optional Condensate Drain Connection

Adapter 3/4 inch slip X

3/4 inch mpt (not furnished)

90

°

Street Elbow

3/4 inch PVC

(not furnished)

Adapter 3/4 inch slip X

3/4 inch mpt (not furnished)

Condensate Drain

Connection In Unit

1 (25 mm) Min.

2 (50 mm) Max.

Above Top Of

Condensate Drain

Connection In Unit

Vent

5 Feet

Maximum

90

°

Street Elbow

3/4 inch PVC

( furnished) 90 ° Elbow 3/4 inch PVC

(Not Furnished)

To

Trap

Optional DrainPipingFromTrap

Drain Assembly for 1/2 inch Drain Pipe

1/2 inch PVC Pipe

(Not Furnished)

Condensate Drain

Connection In Unit

3/4 inch PVC Pipe

(Not Furnished)

Coupling 3/4 inch slip X slip

(Not Furnished)

1/2 inch PVC Pipe

(Not Furnished)

To

Drain

90 ° Elbow

1/2 inch PVC

(Not Furnished)

Drain Assembly for 3/4 inch Drain Pipe

Drain Trap

Assembly

(Furnished)

Drain Trap

Clean Out

To

Drain

90 ° Elbow

3/4 inch PVC

(Not Furnished)

90 ° Elbow

3/4 inch PVC

(Not Furnished)

To

Drain

Coupling 3/4 inch slip X slip

(Not Furnished)

DrainTrap Assembly

(Furnished)

DrainTrap Assembly with 1/2 inch Piping

1 (25 mm) Min. 2 (50 mm) Max. Above Top

Of Condensate Drain Connection In Unit

Vent

DrainTrap Assembly with 3/4 inch Piping

1 (25 mm) Min. 2 (50 mm) Max. Above Top

Of Condensate Drain Connection In Unit

Vent

3/4 inch

7

(178)

1/2 inch

Condensate Drain

Connection In Unit

Condensate Drain

Connection In Unit

To

Drain

To

Drain

FIGURE 53

Page 32

Gas Piping

CAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

WARNING

Do not over torque (800 in-lbs) or under torque (350 inlbs) when attaching the gas piping to the gas valve.

1 - Gas piping may be routed into the unit through either the left- or right- hand side. Supply piping enters into the gas valve from the side of the valve as shown in

FIGURE 56. Connect the gas supply piping into the

gas valve. The maximum torque is 800 in lbs and minimum torque is 350 in lbs when attaching the gas piping to the gas valve.

IMPORTANT

When converting the ML193 unit from natural gas to LP/ propane install the field provided low pressure switch.

See FIGURE 54.

switch. See figure 55.

LOW INLET PRESSURE SWITCH

(S145) LOCATION

Orange

White

Orange

Yellow

Gas Valve Shown In Off Position

FIGURE 54

2 - When connecting gas supply, factors such as length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop.

TABLE 9 lists recommended pipe sizes for typical

applications.

NOTE - Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.

.

3 - Gas piping must not run in or through air ducts, clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See

FIGURE 56 and FIGURE 57.

4 - Piping should be sloped 1/4 inch per 15 feet (6mm per 5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.

5 - A 1/8” N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection.

See FIGURE 61.

6 - In some localities, codes may require installation of a manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type.

IMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petroleum gases.

Leak Check

After gas piping is completed, carefully check all field-in stalled piping connections for gas leaks. Use a commercially available leak detecting solution specifically manu factured for leak detection. Never use an open flame to test for gas leaks.

The furnace must be isolated from the gas supply sys tem by closing the individual manual shut-off valve during any gas supply system at pressures greater than or equal to ½ psig. (3.48 kPa, 14 inches w.c.). This furnace and its components are designed, manufactured and inde pendently certified to comply with all applicable ANSI/CSA standards. A leak check of the furnace and its components is not required.

CAP

FURNACE

VALVE WILL NOT HOLD

NORMAL TEST PRESSURE

1/8” N.P.T. PLUGGED TAP

FIGURE 55

IMPORTANT

When testing pressure of gas lines, gas valve must be

disconnected and isolated. See FIGURE 55. Gas valves

can be damaged if subjected to pressures greater than

1/2 psig (3.48 kPa).

Page 33

WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection. Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.

Upflow Application

Left Side Piping

(Standard)

MANUAL

MAIN SHUT-OFF

VALVE

GROUND

JOINT

UNION

DRIP LEG

1/2” NPT

FIELD

PROVIDED

AND INSTALLED

NOTE - BLACK IRON PIPE

ONLY

TO BE ROUTED INSIDE OF CABINET

Upflow Application

Right Side Piping

(Alternate)

1/2” NPT

MANUAL

MAIN SHUT-OFF

VALVE

GROUND

JOINT

UNION

DRIP LEG

FIGURE 56

Horizontal Applications

Possible Gas Piping Configurations

MANUAL

MAIN SHUT-OFF

VALVE

Horizontal Application

Left-Side Air Discharge

MANUAL

MAIN SHUT-OFF

VALVE

GROUND

JOINT

UNION

DRIP LEG

GROUND

JOINT

UNION

DRIP LEG

Horizontal Application

Right-Side Air Discharge

FIELD

PROVIDED

AND INSTALLED

NOTE - BLACK IRON PIPE

ONLY

TO BE ROUTED INSIDE OF CABINET

FIGURE 57

MANUAL

MAIN SHUT-OFF

VALVE

GROUND

JOINT

UNION

DRIP LEG

Page 34

Nominal

Iron Pipe

Size Inches

(mm)

1/2

(12.7)

3/4

(19.05)

1

(25.4)

1-1/4

(31.75)

1-1/2

(38.1)

2

(50.8)

2-1/2

(63.5)

3

(76.2)

Internal

Diameter inches

(mm)

.622

(17.799)

.824

(20.930)

1.049

(26.645)

1.380

(35.052)

1.610

(40.894)

2.067

(52.502)

2.469

(67.713)

3.068

(77.927)

10

(3.048)

172

(4.87)

360

(10.19)

678

(19.19)

1350

(38.22)

2090

(59.18)

4020

(113.83)

6400

(181.22)

11300

(319.98)

20

(6.096)

118

(3.34)

247

(7.000)

466

(13.19)

957

(27.09)

1430

(40.49)

2760

(78.15)

4400

(124.59)

7780

(220.30)

TABLE 9

Gas Pipe Capacity - ft3/hr (m3/hr)

Length of Pipe - feet (m)

30

(9,144)

95

(2.69)

199

(5.63)

374

(10.59)

768

(22.25)

1150

(32.56)

2220

(62.86)

3530

(99.95)

6250

(176.98)

40

(12,192)

81

(2.29)

170

(4.81)

320

(9.06)

657

(18.60)

985

(27.89)

1900

(53.80)

3020

(85.51)

5350

(151.49)

50

(15.240)

72

(2.03)

151

(4.23)

284

(8.04)

583

(16.50)

873

(24.72)

1680

(47.57)

2680

(75.88)

4740

(134.22)

60

(18.288)

65

(1.84)

137

(3.87)

257

(7.27)

528

(14.95)

791

(22.39)

1520

(43.04)

2480

(70.22)

4290

(121.47)

70

(21.336)

60

(1.69)

126

(3.56)

237

(6.71)

486

(13.76)

728

(20.61)

1400

(39.64)

2230

(63.14)

3950

(111.85)

80

(24.384)

NOTE Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.

56

(1.58)

117

(3.31)

220

(6.23)

452

(12.79)

677

(19.17)

1300

(36.81)

2080

(58.89)

3670

(103.92)

90

(27.432)

635

(17.98)

1220

(34.55)

1950

(55.22)

3450

(97.69)

52

(1.47)

110

(3.11)

207

(5.86)

424

(12.00)

100

(30,480)

50

(1.42)

104

(2.94)

195

(5.52)

400

(11.33)

600

(17.00)

1160

(32.844)

1840

(52.10)

3260

(92.31)

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section.

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1 - Seal any unused openings in the common venting system.

2 - Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

4 - Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.

5 - After the main burner has operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle.

6 - After determining that each appliance connected to the common venting system is venting properly, (step

3) return all doors, widows, exhaust fans, fireplace dampers, and any other gas-burning appliances to their previous mode of operation.

7 - If a venting problem is found during any of the preceding tests, the common venting system must be modified to correct the problem.

Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.

Page 35

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

CAUTION

Electrostatic discharge can affect electronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.

WARNING

Fire Hazard. Use of aluminum wire with this product may result in a fire, causing property damage, severe injury or death. Use copper wire only with this product.

INTERIOR MAKE-UP BOX INSTALLATION

MAKE-UP

BOX

Right Side

The unit is equipped with a field make-up box. The make up box may be moved to the right side of the furnace to facilitate installation . Secure the excess wire to the existing harness to protect it from damage.

Refer to FIGURE 59 for schematic wiring diagram and

troubleshooting.

The power supply wiring must meet Class I restrictions.

Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.

CAUTION

Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit breaker(s) per Product Specifications bulletin (EHB) and unit rating plate.

NOTE - Unit nameplate states maximum current draw.

Maximum Over-Current Protection allowed is 15 AMP.

Holes are on both sides of the furnace cabinet to facilitate wiring .

Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

Before connecting the thermostat check to make sure the wires will be long enough for servicing at a later date.

Make sure that thermostat wire is long enough to facilitate future removal of blower for service.

Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring shown

in FIGURE 59. Use 18-gauge wire or larger that is suitable

for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in the absence of local codes, according to the current

National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard

C22.1) for Canada. A green ground wire is provided in the field make-up box.

NOTE - The ML193UHE furnace contains electronic com ponents that are polarity sensitive. Make sure that the fur nace is wired correctly and is properly grounded.

FIGURE 58

Page 36

Accessory Terminals See pages 39 and 40 for igntion control illustration.

One line voltage “EAC” 1/4” spade terminal is provided on the furnace integrated control. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.

One line voltage 120V “HUM” 1/4” spade terminal is provided on the furnace integrated control. This terminal is energized in the heating mode when the combustion air inducer is operating. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidifier rated at greater than one amp is connected to this terminal, it is necessary to use an external relay relay

One 24V ”HUM” 1/4” spade terminal is provided on the furnace integrated control. The terminal is energized in the heating mode when the combustion air inducer is operating and the pressure switch is closed. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the ”C” terminal.

Thermostat

Install the room thermostat according to the instructions

provided with the thermostat. See FIGURE 59 for thermo-

stat designations. If the furnace is being matched with a heat pump, refer to the thermostat installation instruction for set up.

Indoor Blower Speeds

1 - When the thermostat is set to “FAN ON,” the indoor blower will run continuously on the (FAN) speed when there is no cooling or heating demand. See table below for for allowable circulation speeds.

2 - When the ML193UHE is running in the heating mode, the indoor blower will run on the heating speed (HEAT).

See table below for allowable heating speeds.

3 - When there is a cooling demand, the indoor blower will run on the cooling speed (COOL).

Generator Use - Voltage Requirements

The following requirements must be kept in mind when specifying a generator for use with this equipment:

• The furnace requires 120 volts + 10% (Range: 108 volts to 132 volts)

• The furnace operates at 60 Hz + 5% (Range: 57

Hz to 63 Hz)

• The furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power

• Generator should have a wave form distortion of less than 5% THD (total harmonic distortion).

ML193UHE

Model Number

-030

-045

-070

-09036C

-09048C

-11048C

-11060C

Red

Allowed

Not Allowed

Allowable Heating Speeds

Yellow Blue

Factory Setting

Allowed

Not Allowed

Allowed

Not Allowed

Allowed

Allowed

Factory Setting

Allowed

Factory Setting

Allowed

Factory Setting

Brown

Allowed

Factory Setting

Allowed

Factory Setting

Allowed

Model Number

All Models

Red

Factory Setting

Allowable Circulation Speeds

Yellow Blue

Not Allowed Not Allowed

Brown

Not Allowed

Black

Not Allowed

Allowed

Not Allowed

Black

Not Allowed

Page 37

FIGURE 59

Page 38

Integrated Control 103217-03

IGNITION CONTROL 103217-03

120V HUM

LINE

XFMR

CIRC

EAC

HUM24

NEUTRALS (5) NEUTRAL

3/16” QUICK CONNECT TERMINALS

COOL COOL SPEED FROM INDOOR BLOWER

MOTOR (24 VAC)

HEAT

FAN

HEAT SPEED FROM INDOOR BLOWER

MOTOR (24 VAC)

CONTINUOUS FAN SPEED FROM

INDOOR BLOWER MOTOR (24 VAC)

PARK (3)

FS

24 COM

TABLE 10

1/4” QUICK CONNECT TERMINALS

POWER FOR HUMIDIFIER (120 VAC

INCOMING POWER LINE (120 VAC)

TRANSFORMER PRIMARY (120 VAC)

INDOOR BLOWER MOTOR (120 VAC)

ELECTRONIC AIR CLEANER (120 VAC)

POWER FOR HUMIDIFIER (24 VAC)

TERMINALS FOR UNUSED MOTOR

SPEED TAPS

FLAME SENSOR ELECTRODE (120 VAC)

COMMON (24 VAC) RED LED RECALL BUTTON

BLOWER OFF DELAY

FIGURE 60

RED LED Flash Code 2

Off

Heartbeat 1

Continuous Rapid Flash

1

2

3

4

7

10

11

8

9

12

13

5

6

Note - 1

Note - 2

Note - 3

Diagnostic Codes / Status

No power to control or board fault detected

Normal Operation - Idle, Continuous Fan, Cool

Call For Heat / Burner Operation

Reverse Line Voltage Polarity

Improper Earth Ground

Burner failed to light, or lost flame during heat demand

Low Flame Signal - check flame sensor

Watchguard - burner failed to light, exceeded maximum number of retries or recycles.

Not Used

Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer than 3 minutes

Rollout Switch Open

Pressure Switch failed to close or opened during heat demand

Watchguard - Pressure Switch opened 5 times during one heat demand

Pressure Switch stuck closed prior to activation of combustion air inducer

Flame Sensed without gas valve energized

Low Line Voltage

Notes

A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating

Error codes are indicated by a “rapid flash” - the LED flashes X times at ½ second on ½ second off, remains off for 3 seconds then repeats.

Last 10 error codes are stored in memory including when power is shut off to the unit. - To recall, press and release button, most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.

Page 39

Integrated Control 107163-01

IGNITION CONTROL 107163-01

PARKS

Push Button

Error Recall

Diagnostic LED

RED LED Flash Code

Off

On

Fast Heartbeat 3

Slow Heartbeat 1

1 Flash 2

2 Flashes 2

3 Flashes 2

4 Flashes 2

5 Flashes 2

6 Flashes 2

7 Flashes 2

8 Flashes 2

9 Flashes 2

10 Flashes 2

11 Flashes 2

12 Flashes 2

13 Flashes 2

Note - 1

Note - 2

Note - 3

Note - 4

Heating Blower Off

Delay Selector Switch

Diagnostic Codes / Status of Furnace Ignition Control 107163-01

No Power to Control or Board Fault Detected

Board Fault Detected

Call for Heat / Burner Operation

Normal Operation – Idle, Continuous Fan, or Cool

Reverse Line Voltage Polarity or Phasing of 120V power

Improper earth ground

Burner failed to light, or lost flame during heat demand

Low flame signal – check flame sensor

Watchguard – burner failed to light, exceeded maximum number of retries/recycles, 1 hour lockout

Not used

Primary or Secondary limit switch open or Watchguard mode – Limit Switch open longer than 3 minutes

Roll-out Switch Open

Pressure Switch failed to close or opened during heat demand, inducer on

Watchguard - Pressure switch opened 5 times during a single heating demand

Pressure switch stuck closed prior to activation of Combustion Air Inducer

Flame sensed without gas valve energized

Low line voltage

Notes

A slow heartbeat is indicated by 1s on / 1s off. It is used for idle, continuous fan and cool modes.

Error codes are indicated by a “rapid flash” - the LED flashes X times at ½ second on ½ second off, remains off for 3 seconds then repeats.

A fast heartbeat is indicated by 0.5s on / 0.5s off. It is only used during a heat call.

Last 10 error codes are stored in memory including when power is shut off to the unit. - To recall, press, and release button, most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.

Page 40

Unit Start-Up

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING

Do not use this furnace if any part has been underwater. A flood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion.

Immediately call a qualified service technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.

WARNING

Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.

CAUTION

Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.

BEFORE LIGHTING the unit, smell all around the furnace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

The gas valve on the ML193UHE is equipped with a gas control switch (lever). Use only your hand to move switch.

Never use tools. If the switch will not move by hand, do not try to repair it. Force or attempted repair may result in a fire or explosion.

Placing the furnace into operation:

ML193UHE units are equipped with an automatic hot surface ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on these units.

Priming Condensate Trap

The condensate trap should be primed with water prior to start-up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:

1 - Follow the lighting instructions to place the unit into operation.

2 - Set the thermostat to initiate a heating demand.

3 - Allow the burners to fire for approximately 3 minutes.

Adjust the thermostat to deactivate the heating demand.

5 - Wait for the combustion air inducer to stop. Set the thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes.

Adjust the thermostat to deactivate the heating demand and wait for the combustion air inducer to stop. At this point, the trap should be primed with sufficient water to ensure proper condensate drain operation.

WARNING

. If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.

Gas Valve Operation (FIGURE 61)

1 - STOP!

Read the safety information at the beginning of this section.

2 - Set the thermostat to the lowest setting.

3 - Turn off all electrical power to the unit.

4 - This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.

5 - Remove the upper access panel.

6 - Move gas valve switch to OFF. See FIGURE 61.

7 - Wait five minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.

8 - Move gas valve switch to ON. See FIGURE 61

MANIFOLD

PRESSURE

ADJUSTMENT

SCREW

MANIFOLD

PRESSURE

OUTLET

PORT

INLET

PRESSURE

PORT GAS VALVE SHOWN IN ON POSITION

FIGURE 61

9 - Replace the upper access panel.

10- Turn on all electrical power to the unit.

11- Set the thermostat to desired setting.

NOTE - When unit is initially started, steps 1 through

11 may need to be repeated to purge air from gas line.

12- If the appliance will not operate, follow the instructions

“Turning Off Gas to Unit”

Turning Off Gas to Unit

1 - Set the thermostat to the lowest setting.

2 - Turn off all electrical power to the unit if service is to be performed.

3 - Remove the upper access panel.

Page 41

4 - Move gas valve switch to OFF.

5 - Replace the upper access panel.

Failure To Operate

If the unit fails to operate, check the following:

1 - Is the thermostat calling for heat?

2 - Are access panels securely in place?

3 - Is the main disconnect switch closed?

4 - Is there a blown fuse or tripped breaker?

5 - Is the filter dirty or plugged? Dirty or plugged filters will cause the limit control to shut the unit off.

6 - Is gas turned on at the meter?

7 - Is the manual main shut-off valve open?

8 - Is the internal manual shut-off valve open?

9 - Is the unit ignition system in lockout? If the unit locks out again, inspect the unit for blockages.

Heating Sequence Of Operation

1 - When thermostat calls for heat, combustion air inducer starts.

Combustion air pressure switch proves blower operation. Switch is factory set and requires no adjustment.

3 - After a 15-second prepurge, the hot surface ignitor energizes.

4 - After a 20-second ignitor warm-up period, the gas valve solenoid opens. A 4-second Trial for Ignition period begins.”

5 - Gas is ignited, flame sensor proves the flame, and the combustion process continues.

6 - If flame is not detected after first ignition trial, the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve

(“WATCHGUARD” flame failure mode). The ignition control will then automatically repeat steps 1 through

6 after 60 minutes. To interrupt the 60-minute

“WATCHGUARD” period, move thermostat from

“Heat” to “OFF” then back to “Heat”. Heating sequence then restarts at step 1.

Gas Pressure Adjustment

Gas Flow (Approximate)

ML193

Unit

-030

-045

-070

-090

-110

TABLE 11

GAS METER CLOCKING CHART

Seconds for One Revolution

120

Natural

1 cu ft

Dial

2 cu ft

Dial

240

1 cu ft

Dial

300

LP

2 cu ft

Dial

600

80

55

160

110

200

136

41

33

82

66

102

82

Natural-1000 btu/cu ft LP-2500 btu/cu ft

400

272

204

164

Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolu tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time

in TABLE 11. If manifold pressure matches TABLE 12 and

rate is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.

NOTE - To obtain accurate reading, shut off all other gas appliances connected to meter.

Supply Pressure Measurement

When testing supply gas pressure, use the 1/8” N.P.T. plugged tap or pressure post located on the gas valve to

facilitate test gauge connection. See FIGURE 61. Check

gas line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High pressure can result in permanent damage to gas valve or overfire.

On multiple unit installations, each unit should be checked separately, with and without units operating. Supply pres-

sure must fall within range listed in TABLE 12.

Manifold Pressure Measurement

1 - Connect the test gauge positive side “+“ to manifold pressure tap on gas valve.

2 - Tee into the gas valve regulator vent hose and connect to test gauge negative “-”.

3 - Start unit and let run for 5 minutes to allow for steady state conditions.

4 - After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in

TABLE 12.

5 - Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

6 - Start unit and perform leak check. Seal leaks if found.

TABLE 12

Supply Line and Manifold Pressure (inches w.c.)

Unit Fuel

Manifold

Pressure

Line Pressure

All

All

Nat. Gas

L.P. Gas

3.5

10.0

4.5 - 10.5

11.0 - 13.0

NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Page 42

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com bustion. Take combustion sample beyond the flue outlet and compare to the table below.

ML193 Unit

030

045

070

090

110

TABLE 13

CO

2

Nat

6.5 - 7.5

7.0 - 9.0

CO

2

LP

7.5 - 8.5

8.0 - 10.0

The maximum carbon monoxide reading should not exceed 100 pm.

High Altitude Information

NOTE - In Canada, certification for installations at eleva tions over 4500 feet (1372 m) is the jurisdiction of local authorities.

Units may be installed at altitudes up to 10,000 ft. above

sea level. See TABLE 14 for de-rate manifold values. Units

installed at altitude of 7501 - 10,000 feet require an orifice change. Units installed at altitude of 4501 - 10,000 feet require a pressure switch change which can be ordered

separately. TABLE 15 lists conversion kit and pressure

switch requirements at varying altitudes.

The combustion air pressure switch is factory-set and requires no adjustment.

NOTE - A natural to LP/propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

TABLE 14

Manifold and Supply Line Pressure 0-10,000ft.

Manifold Pressure in. wg.

ML193

Unit

Gas

0 - 4500 ft 4501 - 5500 ft 5501 - 6500 ft 6501 - 7500 ft 7501 - 10,000 ft

Supply Line Pressure in. w.g.

0 - 10000 ft.

All

Models

Natural

L.P. Propane

3.5

10.0

3.3

9.4

3.2

9.1

3.1

8.9

3.5

10.0

4.5

11.0

13.0

13.0

NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

TABLE 15

Conversion Kit and Pressure Switch Requirements at Varying Altitudes

Natural to LP/

Propane

High Altitude

Natural Burner

Orifice Kit

LP/Propane to

Natural

High Altitude LP/

Propane Burner

Orifice Kit

High Altitude Pressure Switch

ML193 Model

0 - 7500 ft

(0 - 2286m)

17H63

7501 - 10,000 ft

(2286 - 3038m)

14C90

0 - 7500 ft

(0 - 2286m)

N/A

7501 - 10,000 ft

(2286 - 3038m)

17H66

4501 - 7500 ft

(1373 - 2286m)

7501 -10,000 ft

(2286 - 3048m)

-030

-045

-070

-090

-110

*11K49 73W37 *73W81 *11K44

11U65 11U66

* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).

Page 43

Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications

WARNING

. CARBON MONOXIDE POISONING HAZARD!

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.

After the ML193UHE gas furnace has been started, the following test should be conducted to ensure proper venting and sufficient combustion air has been provided to the

ML193UHE as well as to other gas-fired appliances which are separately vented.

If a ML193UHE furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.

The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section.

1 - Seal any unused openings in the venting system.

2 - Visually inspect the venting system for proper size and horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

3 - To the extent that it is practical, close all building doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the building.

4 - Close fireplace dampers.

5 - Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed.

Do not operate a summer exhaust fan.

6 - Follow the lighting instruction to place the appliance being inspected into operation. Adjust thermostat so appliance will operate continuously.

7 - Use the flame of match or candle to test for spillage of flue gases at the draft hood relief opening after 5 minutes of main burner operation.

8 - If improper venting is observed during any of the above tests, the venting system must be corrected or sufficient combustion/make-up air must be provided. The venting system should be re-sized to approach the minimum size as determined by using the appropriate tables in appendix G in the current standards of the National Fuel Gas Code

ANSI-Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and Propane appliances venting sizing tables in the current standard of the

CSA-B149 Natural Gas and Propane Installation

Codes in Canada.

9 - After determining that each appliance remaining connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.

Page 44

Other Unit Adjustments

Primary Limit.

The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment.

Flame Rollout Switches (Two)

These manually reset switches are located on the front of the burner box.

Pressure Switch

The pressure switch is located in the heating compartment on the cold end header box. This switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory-set and must not be adjusted.

Temperature Rise

After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. See ‘Allowable Heating Speeds” table on page 37. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.

Fan Control

Ignition Control 103217-03

The fan on time of 30 seconds is not adjustable. The fan off delay (amount of time that the blower operates after the heat demand has been satisfied) may be adjusted by changing the jumper position across the five pins on the integrated control. The unit is shipped with a factory fan off setting of 120 seconds. The fan off delay affects com fort and is adjustable to satisfy individual applications. Adjust the fan off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de-energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher re-

turn air temperatures. See FIGURE 62.

Ignition Control 107163-01

The heat fan-on time of 30 seconds is not adjustable The heat fan-off delay (amount of time that the blower oper ates after the heat demand has been satisfied) may be adjusted by changing the two position dip switch on the integerated control, to one of four slections. Blower off de lay is factory set at 90 seconds. For other blower off delay settings, please refer to the following chart:

60

90

120

180

Blower Delay Select

SW2-1

OFF

OFF

ON

ON

Factory Setting is 90

SW2-2

ON

OFF

OFF

ON

HEAT FAN ‐ OFF TIME IN SECONDS

NO JUMPER

To adjust fan-off timing, reposition jumper across pins to achieve desired setting.

60 Second off Time

90 Second off Time

120 Second off Time

180 Second off Time

FIGURE 62

Electrical

1 - Check all wiring for loose connections.

2 - Check for the correct voltage at the furnace operating).

Correct voltage is 120VAC + 10%

3 - Check amp-draw on the blower motor with blower access panel in place.

Motor Nameplate__________Actual__________

Blower Speeds

Follow the steps below to change the blower speeds.

1 - Turn off electrical power to furnace.

2 - Remove blower access panel.

3 - Disconnect existing speed tap at integrated control speed terminal.

NOTE - Termination of any unused motor leads must be insulated.

4 - Place unused blower speed tap on integrated control

“PARK” terminal or insulate.

5 - Refer to blower speed selection chart on unit wiring diagram for desired heating or cooling speed.

See Product Specifications bulletin for blower

performance tables. See for allowable heating

speeds.

6 - Connect selected speed tap at integrated control speed terminal.

7 - Resecure blower access panel.

8 - Turn on electrical power to furnace.

9 - Recheck temperature rise.

Page 45

Electronic Ignition

The integrated control has an added feature of an internal

Watchguard control. The feature serves as an automatic reset device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the integrated control to begin the ignition sequence.

Exhaust and Air Intake Pipe

Check exhaust and air intake connections for tightness and to make sure there is no blockage.

2 - Is pressure switch closed? Obstructed exhaust pipe will cause unit to shut off at pressure switch. Check termination for blockages.

3 - Obstructed pipe or termination may cause rollout switches to open. Reset manual flame rollout switches on burner box assembly if necessary.

Service

WARNING

ELECTRICAL SHOCK, FIRE,

OR EXPLOSION HAZARD.

Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage.

Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly.

Verify proper operation after servicing.

WARNING

The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.

Annual Furnace Maintenance

At the beginning of each heating season, and to comply with the Lennox Limited Warranty, your system should be checked as follows:

1 - Check wiring for loose connections, voltage at indoor unit and amperage of indoor motor.

2- Check the condition of the belt and shaft bearings if applicable.

3- Inspect all gas pipe and connections for leaks.

4- Check the cleanliness of filters and change if necessary (monthly).

5- Check the condition and cleanliness of burners and heat exchanger and clean if necessary.

Check the cleanliness of blower assembly and clean the housing, blower wheel and blower motor if necessary .

7- Inspect the condensate drain and trap for leaks and cracks. The drain and trap must also be cleaned and the trap must be primed with water. Inspect the rubber hoses connected to the pressure switches for cracks or loose connections, replace as necessary.

Remove the rubber hoses from the cold end header box and inspect for any blockage, clean as needed.

If strainers are installed in the hoses remember to remove and clean before reinstalling the hoses.

8- Evaluate the heat exchanger integrity by inspecting the heat exchanger per the AHRI heat exchanger inspection procedure. This procedure can be viewed at www.ahrinet.org

9- Ensure sufficient combustion air is available to the furnace. Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) must be properly sized, open and unobstructed to provide combustion air.

10- Inspect the furnace intake and exhaust pipes to make sure they are in place, structurally sound, without holes, blockage or leakage and the exhaust pipe is sloped toward the furnace. Inspect terminations to ensure they are free of obstructions and are structurally sound. Inspect the furnace return air duct connection to ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.

11- Inspect the furnace return air duct connection to ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.

12- Check the condition of the furnace cabinet insulation and repair if necessary.

13- Perform a complete combustion analysis during the furnace inspection to ensure proper combustion and operation. Consult Service Literature for proper combustion values.

Verify operation of CO detectors and replace batteries as required.

Perform a general system test. Turn on the furnace to check operating functions such as the start-up and shutoff operation.

1 - Check the operation of the ignition system, inspect and clean flame sensor. Check microamps before and after. Check controls and safety devices (gas valve, flame sensor, temperature limits). Consult

Service Manual for proper operating range. Thermal

Limits should be checked by restricting airflow and not disconnecting the indoor blower. For additional details, please see Service and Application Note

H049.

2 - Verify that system total static pressure and airflow settings are within specific operating parameters.

3 - Clock gas meter to ensure that the unit is operating at the specified firing rate. Check the supply pressure and the manifold pressure. If manifold pressure adjustment is necessary, consult the Service

Literature for unit specific information on adjusting gas pressure. Not all gas valves are adjustable.

Verify correct temperature rise.

Page 46

Winterizing and Condensate Trap Care

1 - Turn off power to the furnace.

2 - Have a shallow pan ready to empty condensate water.

3 - Remove the clean out cap from the condensate trap and empty water. Inspect the trap then reinstall the clean out cap.

Cleaning the Burner Assembly

1 - Turn off gas and electrical power to the furnace.

Remove heating compartment access panel.

2 - Disconnect the gas supply line from the gas valve.

3 - Disconnect and label wires from gas valve.

4 - Disconnect ignitor wiring at 2 circuit plug.

5 - Disconnect and label wires from rollout switch.

6 - Disconnect and label flame sensor wire.

Disconnect and label ground wire from burner/ manifold assembly.

8 - Remove four screws that secures burner/manifold assembly to vestibule. Remove the assembly and make note not to allow ignitor plate to dislodge from the assembly.

9 - Gently clean the face of the burners using the soft brush attachment on a vacuum cleaner. Visually inspect the inside of the burners and crossovers for any blockage caused by foreign matter. Remove any blockage

10 - Reinstall the burner/manifold assembly using the existing four screws. Burners are self aligning to center of clam shells.

11 - Reconnect ground wire.

12 - Reconnect flame sensor wire.

13 - Reconnect rollout switch wires.

14 - Reconnect ignitor wires.

15 - Reconnect gas valve wires.

16 - Reconnect gas supply line to gas valve.

17 - Refer to instructions on verifying gas and electrical connections when re-establishing supplies

18 - Follow instructions to place furnace in operation.

Run furnace 5 minutes to ensure burners are clean and operating correctly.

19 - Replace heating compartment access panel.

Repair Parts List

The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate -- Example: ML193UH045XE36B-01.

All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.

Cabinet Parts

Upper access panel

Blower access panel

Top Cap

Control Panel Parts

Transformer

Integrated control board

Door interlock switch

Blower Parts

Blower wheel

Motor

Motor mounting frame

Motor capacitor

Blower housing cutoff plate

Heating Parts

Flame Sensor

Heat exchanger assembly

Gas manifold

Combustion air inducer

Gas valve

Main burner cluster

Main burner orifices

Pressure switch

Ignitor

Primary limit control

Flame rollout switches

Page 47

Start-Up & Performance Check List

2

2

UNIT SET UP

(typical)

Furnace:

Model Number_______________

Serial Number_________________

Line Voltage

4

1 GAS SUPPLY

Natural Gas LP Propane Gas

Piping Connections Tight

Leak Tested

Supply Line Pressure “W.C.________

1

Gas Supply Pressure

1

SUPPLY

AIR

3

Flter

RETURN AIR

2 INTAKE / EXHAUST PIPE

All Joints Primed and Glued

Terminations Installed Properly

Horizontal Pipes Sloped (if applicable)

Condensate Trap Primed / Line Sloped

Pipes Supported

Heat Cable Installed and Operable (if applicable)

3

DUCT SYSTEM

SUPPLY AIR DUCT

Sealed

Insulated (if necessary)

RETURN DUCT

Sealed

Filter Installed and Clean

4

Grilles Unobstructed

VOLTAGE CHECK

Supply Voltage _____

Electrical Connections Tight

Page 48

1

HEATING MODE

GAS MANIFOLD PRESSURE “W.C._____

UNIT OPERATION

2 COMBUSTION SAMPLE CO

2

%

______

CO PPM_______

3

INDOOR BLOWER AMPS______

4

5

TEMPERATURE RISE

Supply Duct Temperature ________

Return Duct Temperature _ _____

Temperature Rise = ________

TOTAL EXTERNAL STATIC

Supply External Static _______

Return External Static + ______

Total External Static = _______

6

7

CONDENSATE LINE

Leak Free

VENT PIPE

Leak Free

Combustion CO

2

2

7

SUPPLY

AIR

3

COOLING MODE

INDOOR BLOWER AMPS______

4 TEMPERATURE DROP

Return Duct Temperature _________

Supply Duct Temperature _ _______

Temperature Drop = _________

5

8

TOTAL EXTERNAL STATIC (dry coil)

Supply External Static _______

Return External Static + ______

Total External Static = _______

DRAIN LINE

Leak Free

9 THERMOSTAT

Adjusted and Programmed

Explained Operation to Owner

Thermostat

9

Blower Motor Amps

3

6

8

Gas Manifold Pressure

1

Temperatures

4

Duct Static

High +

5

RETURN AIR

Low -

Contractor's: Name_________________________Telephone_____________Checklist Completed____________________

Job Address_____-________________________________Technician's Name___________________________________

Page 49

Requirements for Commonwealth of Massachusetts

Modifications to NFPA-54, Chapter 10

Revise NFPA-54 section 10.8.3 to add the following requirements:

For all side wall, horizontally vented, gas-fueled equip ment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the finished grade in the area of the venting, in cluding but not limited to decks and porches, the following requirements shall be satisfied:

INSTALLATION OF CARBON MONOXIDE

DETECTORS. At the time of installation of the side wall, horizontally vented, gas-fueled equipment, the installing plumber or gasfitter shall observe that a hard-wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed.

In addition, the installing plumber or gasfitter shall observe that a battery-operated or hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas-fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard-wired carbon monoxide detectors.

a. In the event that the side wall, horizontally vented, gas-fueled equipment is installed in a crawl space or an attic, the hardwired carbon monoxide detector with alarm and battery backup may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery-operated carbon monoxide detector with an alarm shall be installed.

2 - APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3 - SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas-fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS.”4

4 - INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas-fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:

The equipment listed in Chapter 10 entitled

“Equipment Not Required to Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2 - Product Approved side wall, horizontally vented, gasfueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS -

GAS EQUIPMENT VENTING SYSTEM PROVIDED.

When the manufacturer of Product Approved side wall, horizontally vented, gas-fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1 - Detailed instructions for the installation of the venting system design or the venting system components: and

2 - A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS -

GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of Product Approved side wall, horizontally vented, gas-fueled equipment does not pro vide the parts for venting the flue gases, but identifies

“special venting systems,” the following requirements shall be satisfied by the manufacturer:

1 - The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

The “special venting systems” shall be Product

Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product

Approved side wall, horizontally vented, gas-fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Page 50

FOR THE PROVINCE OF ONTARIO, HORIZONTAL

SIDEWALL VENT APPLICATIONS ONLY

For exterior horizontal venting applications, the 2” X 1.5” reducer for 2” venting at the point where the exhaust pipe exits the structure is not required in direct or non-direct vent applications in the Province of Ontario. In these applications, the vent should be oriented such that the exhaust plume is unobjectionable. If the installation requires more separation between the flue gases and the building struc ture, a reducer may be installed on the exhaust pipe to increase the flue gas velocity.

ADDENDUM FOR ALL PROVINCES OF CANADA

See below for venting in all provinces of Canada. Lennox approves the following termination for use in all provinces of Canada.

B

D

C

12”

A

A − Clearance above grade or average snow accumulation

2” (51MM)

Vent Pipe

3” (76MM)

Vent Pipe

12” (305 mm) Min. 12” (305 mm) Min.

B − Horizontal separation between intake and exhaust

6” (152 mm) Min.

24” (610 mm) Max.

6” (152 mm) Min.

24” (610 mm) Max.

C − Exhaust pipe length Per: Saskatchewan Code of Practice

D − Wall support distance from top of each pipe (intake/exhaust)

6” (152 mm) Max.

6” (152 mm) Max.

NOTE − Flue gas may be acidic and may adversely affect some building materials. If flue gases impinge on the building materials, a corrosion−resistant shield should be used to protect the wall surface. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.

Page 51

Blower Data

ML193UH030XE36B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

cfm

High

(Black)

Watts

Air Volume / Watts at Various Blower Speeds

Medium-High cfm

(Brown)

Watts cfm

Medium

(Blue)

Watts

Medium-Low cfm

(Yellow)

Watts

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1435

1400

1360

1325

1300

1265

1235

1200

1160

346

351

358

370

382

387

402

411

420

1170

1130

1085

1055

1020

990

945

910

885

191

199

207

217

227

231

244

253

260

1000

955

905

865

815

785

735

710

660

127

132

137

148

157

161

168

175

183

775

735

680

625

570

515

475

425

355

91

95

104

107

114

62

71

81

84 cfm

705

635

515

445

380

310

265

215

175

Low

(Red)

Watts

61

66

68

72

75

45

48

50

55

ML193UH045XE36B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

cfm

High

(Black)

Watts

Air Volume / Watts at Various Blower Speeds

Medium-High cfm

(Brown)

Watts cfm

Medium

(Blue)

Watts

Medium-Low cfm

(Yellow)

Watts

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1420

1390

1355

1330

1295

1265

1240

1210

1160

343

348

349

368

378

386

402

411

420

1305

1270

1230

1205

1180

1140

1100

1065

1030

264

271

280

291

298

310

316

331

340

1170

1135

1100

1060

1025

995

955

920

880

191

199

207

220

226

233

242

253

262

930

885

850

795

755

720

670

615

580

102

109

119

126

134

140

148

157

160 cfm

780

735

680

625

570

515

475

425

355

Low

(Red)

Watts

91

95

104

107

114

66

71

81

84

Page 52

Blower Data

ML193UH070XE36B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

cfm

High

(Black)

Watts

Air Volume / Watts at Various Blower Speeds

Medium-High cfm

(Brown)

Watts cfm

Medium

(Blue)

Watts

Medium-Low cfm

(Yellow)

Watts

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1430

1395

1365

1340

1305

1270

1250

1210

1185

330

337

344

357

367

377

393

401

412

1300

1270

1245

1215

1180

1145

1110

1080

1045

249

256

269

275

285

296

305

316

325

1170

1145

1100

1080

1040

1005

970

930

885

185

192

199

210

219

230

237

247

255

955

910

865

815

760

720

685

635

600

101

107

115

123

133

139

147

152

158 cfm

750

705

655

600

550

505

455

405

355

Low

(Red)

Watts

93

95

100

109

114

67

71

76

82

ML193UH090XE36C PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

cfm

High

(Black)

Watts

Air Volume / Watts at Various Blower Speeds

Medium-High cfm

(Brown)

Watts cfm

Medium

(Blue)

Watts

Medium-Low cfm

(Yellow)

Watts

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1410

1375

1340

1310

1275

1240

1210

1170

1135

280

289

301

314

326

340

347

362

368

1340

1315

1285

1260

1225

1190

1160

1130

1105

230

239

249

261

269

279

288

299

304

1160

1125

1090

1055

1015

965

920

885

855

160

168

175

180

195

201

211

221

229

835

885

840

780

730

675

620

580

535

90

95

104

112

117

126

133

138

144 cfm

770

730

685

645

590

535

495

455

405

Low

(Red)

Watts

87

91

98

102

107

64

70

74

81

Page 53

Blower Data

ML193UH090XE48C PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

cfm

High

(Black)

Watts

Air Volume / Watts at Various Blower Speeds

Medium-High cfm

(Brown)

Watts cfm

Medium

(Blue)

Watts

Medium-Low cfm

(Yellow)

Watts

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1710

1675

1655

1615

1595

1560

1525

1490

1445

373

381

392

408

416

429

439

453

464

1500

1475

1460

1410

1365

1335

1295

1260

1230

256

263

273

282

295

308

315

325

332

1395

1365

1315

1290

1245

1200

1160

1105

1085

200

206

219

225

236

246

255

268

275

1315

1275

1230

1195

1155

1105

1060

1015

980

164

173

185

192

203

214

221

229

240 cfm

1205

1160

1110

1065

1010

965

915

875

830

Low

(Red)

Watts

129

135

142

151

160

167

176

184

195

ML193UH110XE48C PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

cfm

High

(Black)

Watts

Air Volume / Watts at Various Blower Speeds

Medium-High cfm

(Brown)

Watts cfm

Medium

(Blue)

Watts

Medium-Low cfm

(Yellow)

Watts

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1750

1715

1680

1640

1615

1580

1540

1515

1470

372

380

391

405

418

433

445

450

467

1535

1495

1470

1425

1395

1345

1315

1285

1230

254

262

272

284

296

305

315

325

334

1410

1380

1355

1300

1260

1225

1180

1135

1095

200

208

220

230

239

249

258

268

278

1330

1295

1255

1220

1170

1130

1080

1035

995

169

176

184

194

206

212

223

230

240 cfm

1220

1175

1135

1085

1025

975

935

895

850

Low

(Red)

Watts

128

135

145

154

162

170

179

186

192

Page 54

Blower Data

ML193UH110XE60C PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds

External

Static

Pressure in. w.g.

Bottom Return Air, Side Return Air with Return Air from

Both Sides or Return Air from Bottom and One Side.

Single Side Return Air − Air volumes in bold require

Optional Return Air Base and field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.

High

(Black)

Med-High

(Brown)

Medium

(Blue)

Med-Low

(Yellow)

Low

(Red)

High

(Black)

Med-High

(Brown)

Medium

(Blue)

Med-Low

(Yellow)

Low

(Red) cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

0.00 2150 624 1915 436 1755 345 1650 280 1480 201 2175 607 1930 412 1760 330 1645 271 1475 199

0.10 2120 633 1880 441 1715 353 1605 288 1435 210 2135 614 1885 421 1705 342 1595 280 1415 207

0.20 2085 648 1830 455 1665 362 1560 298 1360 220 2085 628 1830 437 1670 351 1545 293 1370 218

0.30 2040 663 1795 468 1630 374 1515 317 1325 229 2035 647 1790 451 1625 364 1500 308 1315 227

0.40 2005 675 1760 482 1585 386 1470 327 1270 244 1995 657 1755 469 1590 378 1460 319 1275 240

0.50 1965 688 1710 496 1540 399 1425 336 1230 251 1985 674 1725 478 1545 391 1410 329 1225 250

0.60 1935 705 1680 507 1510 408 1390 347 1180 263 1925 687 1675 494 1495 401 1375 343 1170 257

0.70 1885 715 1635 521 1485 425 1345 359 1140 271 1900 698 1635 506 1450 413 1330 351 1125 270

0.80 1855 735 1600 534 1440 426 1305 367 1085 279 1850 711 1605 520 1415 430 1285 363 1075 281

Page 55

advertisement

Related manuals