FloAire Indirect Fired Bent Tube Module Installation Manual

Add to My manuals
84 Pages

advertisement

FloAire Indirect Fired Bent Tube Module Installation Manual | Manualzz

Modular Indirect Fired Heaters and Inserts

Installation, Operation, and Maintenance Manual

Modular Indirect Fired Heater Indirect Fired Module

FOR YOUR SAFETY

If you smell gas:

1. Open windows.

2. Don’t touch electrical switches.

3. Extinguish any open flames.

4. Immediately call your gas supplier.

Indirect Fired Furnace

FOR YOUR SAFETY

The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.

RECEIVING AND INSPECTION

Upon receiving unit, check for any interior and exterior damage. If damage is found, report it immediately to the carrier. Also check that all accessory items are accounted for and are damage free. Turn the blower wheel by hand to verify free rotation and check the damper (if supplied) for free operation.

WARNING!!

Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. ALWAYS disconnect power and gas prior to working on heater.

Save these instructions . This document is the property of the owner of this equipment and is required for future maintenance. Leave this document with the owner when installation or service is complete.

A0016988

March 2021 Rev. 39

2

TABLE OF CONTENTS

WARRANTY ..................................................................................................................................................................................................................... 4

Furnace Warranty ....................................................................................................................................................................................................... 4

CERTIFICATIONS AND PATENTS .................................................................................................................................................................................. 4

Listing ......................................................................................................................................................................................................................... 4

Patents ....................................................................................................................................................................................................................... 4

INSTALLATION ................................................................................................................................................................................................................ 4

Mechanical ................................................................................................................................................................................................................. 5

Site Preparation .................................................................................................................................................................................................... 5

Assembly .............................................................................................................................................................................................................. 5

Curb and Ductwork ............................................................................................................................................................................................... 6

Roof Mount Installation ......................................................................................................................................................................................... 7

Installation with Exhaust Fan ................................................................................................................................................................................ 7

Indirect Fired Module Installation .......................................................................................................................................................................... 8

Indoor (INLINE) Installation .................................................................................................................................................................................. 8

Condensation Drain .............................................................................................................................................................................................. 9

Indoor Flue Venting ............................................................................................................................................................................................ 10

Gas ........................................................................................................................................................................................................................... 13

LP Conversion Kit ............................................................................................................................................................................................... 14

Electrical ................................................................................................................................................................................................................... 16

Input AC Power .................................................................................................................................................................................................. 17

Fan to Building Wiring Connection ...................................................................................................................................................................... 17

COMPONENTS .............................................................................................................................................................................................................. 18

Part Identification ...................................................................................................................................................................................................... 18

Motor Speed Control Options ................................................................................................................................................................................... 21

Variable Frequency Drive Speed Control (Installation Instructions) .......................................................................................................................... 22

ACTECH SMV VFD .................................................................................................................................................................................................. 23

Optional Components ............................................................................................................................................................................................... 24

OPERATION .................................................................................................................................................................................................................. 24

HMI Configuration ..................................................................................................................................................................................................... 24

HMI Options Screen ........................................................................................................................................................................................... 25

HMI Menu Description .............................................................................................................................................................................................. 25

HMI Menu Tree ......................................................................................................................................................................................................... 30

Start Up .................................................................................................................................................................................................................... 38

Tools Required ................................................................................................................................................................................................... 38

Start Up Procedure ............................................................................................................................................................................................. 38

Gas Pressure Adjustment ................................................................................................................................................................................... 39

Furnace Start-Up (Summary) ............................................................................................................................................................................. 40

Furnace Startup .................................................................................................................................................................................................. 41

Final Start-Up Procedure .......................................................................................................................................................................................... 43

Pulley Adjustment ............................................................................................................................................................................................... 43

Pulley Alignment/Proper Belt Tension ................................................................................................................................................................ 44

Pulley Combination Chart ................................................................................................................................................................................... 45

High Altitude Orifice Sizing ................................................................................................................................................................................. 46

Sequence of Operation (Summary) .......................................................................................................................................................................... 47

Sequence of Operation (Detailed) ............................................................................................................................................................................ 47

Re-Circulating Control Options ................................................................................................................................................................................. 50

Manual Positioning Control ................................................................................................................................................................................. 50

Two Position Control .......................................................................................................................................................................................... 50

Outdoor Air % ..................................................................................................................................................................................................... 50

Static Pressure Control (Photohelic) ................................................................................................................................................................... 51

A306 Outdoor Sensor ......................................................................................................................................................................................... 52

Building Signal Damper Control .......................................................................................................................................................................... 52

Schedule Control ................................................................................................................................................................................................ 52

Network .................................................................................................................................................................................................................... 53

BACNET ............................................................................................................................................................................................................. 53

LonWorks ........................................................................................................................................................................................................... 56

SERVICE INFORMATION .............................................................................................................................................................................................. 57

Troubleshooting Flow-charts .................................................................................................................................................................................... 57

Fault Codes ........................................................................................................................................................................................................ 58

Airflow Troubleshooting Chart ............................................................................................................................................................................ 60

Furnace Troubleshooting Chart .......................................................................................................................................................................... 61

VFD Fault List ..................................................................................................................................................................................................... 62

Component Testing ............................................................................................................................................................................................ 63

MAINTENANCE ............................................................................................................................................................................................................. 67

General Maintenance ............................................................................................................................................................................................... 68

2 weeks after startup ................................................................................................................................................................................................ 69

Every 3 months ......................................................................................................................................................................................................... 69

Yearly ....................................................................................................................................................................................................................... 70

Heat Exchanger Inspection ....................................................................................................................................................................................... 71

Appendix A – IBT Board Electrical Connections ............................................................................................................................................................. 72

Appendix B – IBT DDC Points ........................................................................................................................................................................................ 76

IBT DDC Fault Codes ............................................................................................................................................................................................... 80

Start-Up and Maintenance Documentation ..................................................................................................................................................................... 84

Job Information ......................................................................................................................................................................................................... 84

Heater Information .................................................................................................................................................................................................... 84

Maintenance Record ................................................................................................................................................................................................ 84

3

WARRANTY

This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 2-years from date of shipment. This warranty shall not apply if:

1. The equipment is not installed by a qualified installer per the MANUFACTURER’S installation instructions shipped with the product.

2. The equipment is not installed in accordance with Federal, State, and Local codes and regulations.

3. The equipment is misuse d or neglected, or not maintained per the MANUFACTURER’S maintenance instructions.

4. The equipment is not operated within its published capacity.

5. The invoice is not paid within the terms of the sales agreement.

The MANUFACTURER shall not be liable for incidental and consequential losses and damages potentially attributable to malfunctioning equipment. Should any part of the equipment prove to be defective in material or workmanship within the 2-year warranty period, upon examination by the MANUFACTURER, such part will be repaired or replaced by MANUFACTURER at no charge. The BUYER shall pay all labor costs incurred in connection with such repair or replacement. Equipment shall not be returned without

MANUFACTURER’S prior authorization and all returned equipment shall be shipped by the BUYER, freight prepaid to a destination determined by the MANUFACTURER.

Furnace Warranty

Subject to all terms stated herein, the MANUFACTURER warrants to BUYER the stainless-steel heat exchanger to be free from defects in material and workmanship under normal use and service for 25-years from the date of manufacture, and warranty is limited to replacement of the heat exchanger only.

CERTIFICATIONS AND PATENTS

Listing

This unit is ETL-listed to standard American National Standard/CSA Standard for Gas Unit Heaters And

Gas-Fired Duct Furnaces ANSI Z83.8-2016, CSA 2.6-2016.

Patents

The Indirect Bent Tube Heater is covered under the following patent: Heated Make-Up Air: United States

Patent No. 8777119 B2.

INSTALLATION

It is imperative that this unit is installed and operated with the designed airflow, gas, and electrical supply in accordance with this manual. If there are any questions about any items, please call the service department at 1-866-784-6900 for warranty and technical support issues.

4

Mechanical

WARNING: DO NOT RAISE VENTILATOR BY THE INTAKE HOOD, BLOWER OR MOTOR SHAFT, OR

BEARINGS – USE ALL LIFTING LUGS PROVIDED WITH A SPREADER BAR OR SLINGS UNDER THE

UNIT

CLEARANCES

The top, back, and front surfaces of this heater may not be installed less than 6” from combustible materials. The heater base may be installed on combustible surfaces. Allow 24” minimum service clearance on both sides of this heater.

Site Preparation

1. Provide clearance around installation site to safely rig and lift equipment into its final position. Supports must adequately support equipment. Refer to manufacturer’s estimated weights.

2. Consider general service and installation space when locating unit.

3. Locate unit close to the space it will serve to reduce long, twisted duct runs.

4. Do not allow air intake to face prevailing winds. Support unit above ground or at roof level high enough to prevent precipitation from being drawn into its inlet. The inlet must also be located at least 10 feet away from any exhaust vents.

The heater inlet shall be located in accordance with the applicable building code provisions for ventilation air.

IMPORTANT

Figure 1 – Spreader Bar

To prevent premature heat exchanger failure, do not locate any gas fired unit in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere.

Assembly

Intakes and curbs are shipped unassembled to heater module. Upon unit arrival, use the following procedure to assemble the intake to the heater.

1. Apply silicone or weather-proof gasket on the back side of the flanges of the intake hood or v-bank intake.

2. Screw the flanges of the intake hood or v-bank to the unit with the supplied sheet metal screws. Place caulk on the outside of the screws to prevent water leaks. If the unit is a modular unit with a v-bank or evaporative cooler section, the v-bank or evaporative cooler will bolt to the heater with the bolts provided.

Figure 2- Intake and Curb Assembly

INDIRECT FIRED MODULE

CURB

BLOWER

RAIL

INTAKE HOOD

FILTERS

5

Curb and Ductwork

This fan was specified for a specific CFM and static pressure. The ductwork attached to this unit will significantly affect the airflow performance. When using rectangular ductwork, elbows must be radius throat, radius back with turning vanes. Flexible ductwork and square throat/square back elbows should not be used. Any transitions and/or turns in the ductwork near the fan outlet will cause system effect.

System effect will drastically increase the static pressure and reduce airflow.

Table 1

shows the minimum fan outlet duct sizes and straight lengths recommended for optimal fan

Table 1 - Recommended Supply Ductwork performance.

Follow SMACNA standards and manufacturer’s requirements for the duct runs. Fans designed for rooftop installation should be installed on a

Blower

Size

(Inches)

10

Discharge

Side

Duct Size

(Inches)

14 x 14

Straight Duct

Length

(Inches)

48

Down prefabricated or factory built roof curb. Follow curb manufacturer’s instructions for proper curb installation.

15D,

16Z, 18Z

Side

Down

20 x 20

14 x 14

72

48

Do not use unit to support ductwork in any way.

Side

This may cause damage to the unit. 12 16 x 16 54

Down

The unit should be installed on a curb and/or rail that meets local code height requirements.

15

Side

20 x 20 72

Make sure duct connection and fan outlet are

Down properly aligned and sealed.

20D,

20Z, 22Z

Side

Down

26 x 26

20 x 20

108

72 •

Secure fan to curb through vertical portion of the ventilator base assembly flange using a minimum of eight (8) lug screws, anchor bolts, or other suitable fasteners (not furnished). Shims may be required depending upon curb installation and roofing material.

18

24D, 25Z

Side

Down

Side

24 x 24

30 x 30

86

108

Down 24 x 24 86

Check all fasteners for tightness. Figure 3 through

Figure 6 show different mechanical installation

configurations.

20

30D, 28Z

Side

Down

Side

26 x 26

32 x 32

108

168

Down 26 x 26 108

25

Side

Down

32 x 32 168

36D

Side

Down

36 x 36

32 x 32

189

168

WARNING!!

Failure to properly size ductwork may cause system effects and reduce the performance of the equipment.

6

Roof Mount Installation

Figure 3

CURB OUTER

WALL

INDIRECT MODULE

DISCHARGE

OPENING

AIRFLOW

FLEX CONDUIT FOR

FIELD WIRING

SLOPED FILTER

INTAKE

POWER VENT RAIN CAP

INDIRECT FIRED MODULE

LIFTING LUG

4 PLACES

SERVICE DISCONNECT

SWITCH

BLOWER/

MOTOR

ACCESS

DOOR

GAS

CONNECTION

Installation with Exhaust Fan

Figure 4

POWER VENT RAIN CAP

LIFTING LUG

4 PLACES

20 IN HIGH

EQUIPMENT RAIL

AND CURB

INDIRECT FIRED MODULE

SERVICE DISCONNECT

SWITCH

BLOWER/

MOTOR

ACCESS

DOOR

GAS

CONNECTION

20 IN HIGH

EQUIPMENT RAIL

AND CURB

7

Indirect Fired Module Installation

Figure 5

Ø5" TYPE B GAS

VENT FLUE CONNECTIONS

INDIRECT MODULE

AIRFLOW

INDIRECT FIRED MODULE

LIFTING LUG

4 PLACES

SERVICE

DISCONNECT

SWITCH

FLEX CONDUIT FOR

FIELD WIRING

Ø5" TYPE B GAS

VENT FLUE CONNECTIONS

GAS

CONNECTION

2 1/4 in

FLEX CONDUIT

FOR FIELD WIRING

OPTIONAL UNI-STRUT BASE

FOR HANGING

2 PLACES

Indoor (INLINE) Installation

Figure 6

INDIRECT MODULE

DISCHARGE

OPENING

AIRFLOW

FLEX CONDUIT FOR

FIELD WIRING

V-BANK

FILTER

MODULE

UNI-STRUT BASE

FOR HANGING

4 PLACES

Ø5" TYPE B GAS

VENT FLUE CONNECTIONS

INDIRECT FIRED MODULE

LIFTING LUG

4 PLACES

SERVICE DISCONNECT

SWITCH

BLOWER/

MOTOR

ACCESS

DOOR

FILTER/

CONTROL

ACCESS

DOOR

GAS

CONNECTION

8

Condensation Drain

In some applications, condensation can form in the flue collection box, primarily when furnaces are located downstream of cooling coils. If condensation occurs in the flue collection boxes, there are barbed fittings in the bottom of the flue collection boxes to drain condensation out of the boxes. Each burner in the unit is provided with a burner drain pan or a condensation drain assembly located underneath this fitting for the condensation to collect. If the drain assembly is installed on the heater, it w ill have ¼” quick seals located below the front access door for field piping or drainage onto the roof. Consult your local code as to the proper drainage regulations of the condensation.

The internal drain piping is heated to prevent freezing. If drains are field piped, ensure that the field piping is installed to avoid the condensation from freezing. Do not plug the holes under any circumstance, as it will cause the burners to overflow.

In the event the IBT does not have condensation drains and condensation exceeds the pan capacity, IBT condensation drain kits can be ordered for installation in the field.

The part names for the kits are:

“IBT Condensation Kit-1” Single Furnace IBT

“IBT Condensation Kit-2” Double Furnace IBT

“IBT Condensation Kit-3” Triple Furnace IBT

“IBT Condensation Kit-4” Quadruple Furnace IBT

Condensate Drain Trap Installation

Figure 7 – ¼” NPT Condensation Drain

Figure 8 – IBT Condensation Drain

Assembly Connections

When a drain trap is required, refer to Figure 9

for trap details. If you do not install the trap as described, drainage system failures will occur.

1. The trap depth must be 1/2 x the trap height. For example, if the trap height is 6”, the trap depth must be 3”.

2. All joints must be water tight.

3. After the exit from the trap, the drain must be pitched down from the unit connection at least 1” for every 10 feet of horizontal run to promote proper drainage. Check local installation code, if allowed, the drain can be routed to a wastewater system.

4. When the trap can experience freezing temperatures, drain the system or use a heating device. This will prevent water from freezing and damaging the trap.

5. The trap must be primed before the unit is put into operation and properly maintained on a regular schedule.

6. To prime the trap, remove the cleanout cap. Fill the trap with water. Put the cleanout cap back onto the drainage system. Make sure the trap is

operating properly. Refer to Figure 10 .

Figure 9

Figure 10 – Trap Water Flow

Water

Flow

– Trap Dimensions

Trap Height

Cleanout with Cap

1/2 x Trap Height =

Trap Depth

Water

Flow

9

Indoor Flue Venting

This appliance requires a Category III venting system. Refer to appliance manufacturer’s installation instructions for proper vent installation. Indoor gas fired heating equipment must be vented. Do not operate un-vented . Gas fired heating equipment which has been improperly vented, or which experiences a blocked vent condition may emit flue gases into heated spaces.

IMPORTANT

Furnace Only Modules must be installed in a positive pressure airstream. Do not install in a duct on the suction side of a fan. Use only venting materials and components that are UL listed and approved for Category III venting systems. Do not mix pipe, fittings, or joining methods from different manufacturers.

General Venting Guidelines

1. Installation of venting must conform to local building codes, or in the absence of local codes, follow the National Fuel Gas Code.

2. On Units with multiple furnaces, each furnace must be ducted to the outside using its own isolated duct run. Ducts used on each single furnace MUST NOT be connected together in any fashion. Failure to adhere to this may result in a build-up of Carbon-Monoxide in the space when the furnace is operating with less than all of its furnaces powered.

3. Do not use a vent pipe smaller than the size of the outlet on the heater.

4. Install with a minimum upward slope from unit of ¼ inch per foot and suspend from overhead structure at points no greater than 3 feet apart. For best venting, put as much vertical vent as close to the unit as possible.

5. Fasten individual lengths of vent together with at least three corrosion resistant sheet metal screws.

6. Vent pipes should be fitted with a tee with a drip leg and clean out tap at the low point in the vent run. This should be inspected and cleaned out periodically during the heating season.

7. Do NOT use dampers or other devices in the vent or combustion air pipes.

8. Use a vent terminal to reduce downdrafts and moisture in the vent line.

9. A vent system that terminates vertically but has a horizontal run that exceeds 75% of the vertical rise is considered horizontal.

10. Pressures in Category III venting systems are positive, and therefore care must be taken to prevent flue products from entering the heated space.

11. Vent pipes must all be sealed and gastight.

Vertically Vented Furnaces

1. Use single wall or double wall (Type B) vent pipe of a diameter listed in the following table for the appropriate model.

2. Maximize the height of the vertical run of vent pipe. A minimum of five (5) feet (1.5m) of vertical pipe is required. The top of the vent pipe must extend at least two (2) feet (0.61m) above the highest point on the roof. Use Listed Type B vent for external runs. An approved weatherproof vent cap must be installed on the vent termination.

3. Horizontal runs should be pitched upward ¼ in. per foot (21mm/m) and should be supported at three (3) foot (1m) maximum intervals.

4. Design vent pipe runs to minimize the use of elbows. Each 90 ⁰ elbow is equivalent to five (5) feet

(1.5m) of straight vent pipe.

5. Vent pipe should not be run through unheated spaces. If such runs cannot be avoided, insulate the vent pipe to prevent condensation. Insulation should be a minimum of ½ in. (12.7mm) thick foil faced fiberglass minimum of 1½ # density.

6. Dampers must not be used in vent piping runs, as spillage of flue gases into the occupied space could result.

7. Vent connectors serving Category 1 heaters must not be connected into any portion of a mechanical draft system operating under positive pressure.

National Fuel Gas Code Venting Pipe requirement

75,000-149,999 Use 5-inch pipe

150,000-400,000 Use 6-inch pipe

10

Figure 11 - Vertical Venting

Horizontally Vented Furnaces – Category III

Horizontal vent systems terminate horizontally (sideways)

WARNING: Do not use Type B vent within a building on horizontally vented units.

1. All vent pipe joints must be sealed to prevent leakage. Follow the instructions provided with the approved venting materials.

2. The total equivalent length of vent pipe must not exceed 50 ft. (15.25m). Equivalent length is the total length of straight sections, plus 5 ft. (1.52m) for each 90⁰ elbow and 2.5 ft. (0.76m) for each 45° elbow.

3. The vent system must also be installed to prevent collection of condensates. Horizontal runs should be pitched upward ¼ in. per foot (21mm/m) and should be supported at three (3) foot (1m) maximum intervals.

4. Insulate vent pipe exposed to cold air or routed through unheated areas. Insulate vent pipe runs longer than 10 ft. (3m). Insulation should be a minimum of ½ in. (12mm) thick foil faced fiberglass of 1

½ # density. Maintain 6 in. (152mm) clearance between vent pipe and combustible materials.

5. An approved Breidert Type L, Field Starkap or equivalent vent cap must be provided. Vent cap inlet diameter must be the same as the vent pipe diameter.

6. The vent terminal must be at least 12 in. (305mm) from the exterior wall that it passes through to prevent degradation of building material by flue gases.

7. The vent terminal must be located at least 12 in. (305mm) above grade, or in snow areas, at least 3 ft. (1m) above snow line to prevent blockage.

8. The vent terminal must be installed with a minimum horizontal clearance of 4 ft. (1.2m) from electric meters, gas meters, regulators, or relief equipment.

Through-the-wall vents shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard. Provide vent termination clearances to building or structure features as follows:

11

Structure Minimum

Door, Window or gravity inlet

Forced air inlet within 10 ft. (3m)

Adjoining building or parapet

Adjacent public walkways

Clearance

4 ft. (1.2 m) below

4 ft. (1.2 m) horizontally

1 ft. (305 mm) above

3 ft. (.91 m) above

6 ft. (1.8 m)

7 ft. (2.1 m) above grade

Figure 12 - Horizontal Venting

EACH APPLIANCE MUST HAVE ITS OWN INDIVIDUAL VENT PIPE AND TERMINAL.

Do not connect vent system from horizontally vented units to other vent systems or a chimney

12

Gas

Installation of gas piping must conform with local building codes, or in the absence of local codes, to the

National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.

WARNING: INLET GAS PRESSURE MUST NOT

EXCEED 14 IN. W.C. SEE UNIT RATING PLATE FOR

PROPER GAS SUPPLY PRESSURE AND GAS TYPE.

1. Always disconnect power before working on or near a heater. Lock and tag the disconnect switch or breaker to prevent accidental power up.

2. Piping to the unit should conform to local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to the Gas

Engineer ’s Handbook for gas line capacities.

3. The incoming pipe near the heater should be sized to match the connection on the outside of the unit. Unit inlet sizes are shown in

Table 2 . Avoid multiple taps in the gas

supply so the unit always has a steady supply of gas .

4. Install a ground joint union with brass seat and a manual shut-off valve external to the unit casing, as shown in

Figure 13 , adjacent to the unit for emergency shut-off and

easy servicing of controls.

5. Provide a sediment trap, as shown below, before each unit and where low spots in the pipe line cannot be avoided.

6. Blow out the gas line to remove debris before making connections. Purge line to remove air before attempting to start unit. Purging of air from gas lines should be performed as described in ANSI Z223.1-latest edition

“National Fuel Gas Code”, or in Canada in CAN/CGA-B149.

7. All field gas piping must be pressure/leak tested prior to unit operation. Use a non-corrosive bubble forming solution or equivalent for leak testing. The heater and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi. The heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi.

8. This unit requires a constant 7 in. w.c. minimum natural gas supply, (LP should be 11 in. w.c. minimum) when the unit is operating at maximum gas flow. If the gas supply exceeds 14 in. w.c.

it will damage the internal valve components, and if it is below 7 in. w.c., the heater may not perform to specifications.

Table 2 – Gas Sizing Reference

Table 3 - Gas Pressure

Gas Pressure Type

Inlet Pressure - Natural Gas

Inlet Pressure - Propane

Max. Manifold Pressure -

Natural Gas

Max. Manifold Pressure -

Propane

Min. Manifold Pressure -

Natural Gas

Min. Manifold Pressure -

Propane

Gas Pressure

7 in. w.c. – 14 in. w.c.

11 in. w.c.

– 14 in. w.c.

3.5 in. w.c. maximum

10 in. w.c. maximum

0.15 in. w.c. minimum

0.75 in. w.c. minimum

Figure 13 – Gas Connection Diagram

NOTICE

Refer to the heater rating plate for determining the minimum gas supply pressure for obtaining the maximum gas capacity for which this heater is specified.

13

LP Conversion Kit

LP/Natural gas conversion kits are used to convert from one gas type to another in the field. This kit is used on all units and the part numbers below should be used on furnace sizes listed. Kits contain:

Main Safety Gas Valve Regulator Spring

Furnace orifices clearly indicated with orifice size

This unit is configured for the gas type listed on the nameplate. To convert gases, you must replace the following parts listed in the table below. The size specific parts include the orifice conversion parts and the combination gas valve spring(s). These parts are available by contacting the phone number in this manual. All field gas piping must be pressure/leak tested prior to unit operation. Use a non-corrosive bubble forming solution or equivalent for leak testing. The equipment and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi. The equipment must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi. This must be performed on an annual basis.

Table 4 - Gas Conversion Kit Part Numbers

Gas

Type

Modulating

Valve Part

Number

E50

150

Furnace Size (MBH)

200 250 300 400

Natural

LP E50

NAT-

HMG150

LP-

HMG150

NAT-

HMG200

LP-

HMG200

NAT-

HMG250

LP-

HMG250

NAT-

HMG300

LP-

HMG300

NAT-

HMG400

LP-

HMG400

Pre-Conversion Unit Check-Out

The following procedure is intended as a guide to aid in determining that the appliance is properly installed and is in a safe condition for continuing use. It should be recognized that generalized test procedures cannot anticipate all situations. Accordingly, in some cases, deviation from this procedure may be necessary to determine safe operation of the equipment:

▪ This procedure should be performed prior to any attempt at modification of the appliance or the installation.

▪ If it is determined there is a condition that could result in unsafe operation, the appliance should be shut off and the owner advised of the unsafe condition.

The following steps should be followed in making the safety inspection:

1. Conduct a gas leakage test of the appliance piping and control system downstream of the shut-off valve in the supply line to the appliance.

2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restrictions, leakage or corrosion, or other deficiencies which could cause an unsafe condition.

3. Shut off all gas to the appliance and shut off any other fuel-burning appliance within the same room. Use the shut-off valve in the supply line to each appliance.

4. Inspect burners and crossovers for blockage and corrosion.

5. Inspect heat exchangers for cracks, openings, or excessive corrosion.

6. Insofar as is practical, close all windows and all doors between the space in which the appliance is located and other spaces of the building. Turn on any exhaust fans, so they will operate at maximum speed. After completing steps 6 through 10, it is believed sufficient combustion air is not available, refer to the section covering air for combustion, venting and ventilation of Natural

Gas and Propane Installation Code , CSA B149.1, or National Fuel Gas Code , ANSI

Z223.1/NFPA 54, for guidance.

7. Place the appliance in operation following the lighting instructions. Adjust thermostat so the appliance will operate continuously. Other fuel-burning appliances shall be placed in operation.

14

8. Determine that the pilot is burning properly and that the main burner ignition is satisfactory by interrupting and re-establishing the electrical supply to the appliance in any convenient manner; a. Visually determine that main burner gas is burning properly, i.e. no floating, lifting, or flashback. Adjust the primary air shutter(s) as required. b. If the appliance is equipped with high- and low-flame control, or flame modulation, check for proper main burner operation at low flame.

9. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use a draft gauge, the flame of a match, or candle.

10. Return doors, windows, exhaust fans, and all other fuel-burning appliances to their previous conditions of use.

11. Check both limit control and fan control for proper operation. Limit control operation can be checked by temporarily disconnecting the electrical supply to the blower motor and determining that the limit control acts to shut off the main burner gas.

15

Electrical

WARNING!!

Disconnect power before installing or servicing fan. High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician.

Before connecting power to the heater, read and understand this entire section of this document. As-built wiring diagrams are furnished with each fan by the factory and are attached to the door of the unit.

Electrical wiring and connections should be made in accordance with local ordinances and the National

Electric Code, ANSI/NFPA70. Be sure the voltage and phase of the power supply and the wire amperage capacity are in accordance with the motor nameplate. For additional safety information, refer to AMCA publication 410-96, Recommended Safety Practices for Users and Installers of Industrial and Commercial

Fans.

1. Always disconnect power before working on or near Table 5 - Copper Wire Ampacity a heater. Lock and tag the disconnect switch or breaker to prevent accidental power up.

Wire Size AWG Maximum Amps

14 15

2. An electrical drop containing the motor power wiring is shipped with every fan. The electrical drop should be

12 20

10 30 brought through one of the conduit openings located in the base of the unit, run through the curb, and connect to a junction box inside the building.

8

6

50

65

3. A dedicated branch circuit should supply the motor

4 85 circuit with short circuit protection according to the

National Electric Code. This dedicated branch should be run to the junction box and connected as shown in

Figure 15 .

Figure 14 – Electrical Drops

4. Make certain that the power source is compatible with the requirements of your equipment. The heater nameplate identifies the proper phase and voltage of the motor.

5. Units shipped with an optional remote HMI panel have separate wiring requirements. It is important to route the main electrical wires (high voltage) in a separate conduit from the remote HMI Cat 5 wiring

(low voltage). Maximum distance on any low voltage wire is 1000 feet.

6. Before connecting the heater to the building ’s power source, verify that the power line wiring is de-energized.

7. Secure the power cables to prevent contact with sharp objects.

8. Do not kink power cable and never allow the cable to come in contact with oil, grease, hot surfaces or chemicals.

9. Before powering up the heater, check fan wheel for free rotation and make sure that the interior of the heater is free of loose debris or shipping materials.

10. If any of the original wire supplied with the heater must be replaced, it must be replaced with type TW wire or equivalent.

INDIRECT FIRED MODULE

20 IN HIGH

EQUIPMENT RAIL

AND CURB

Motor Drop

SERVICE DISCONNECT

SWITCH

BLOWER/

MOTOR

ACCESS

DOOR

Control Drop

16

Input AC Power

1. Circuit breakers feeding the VFDs are recommended to be thermal-magnetic and fast acting.

They should be sized based on the VFD amperage and according to Table 6 . Refer to the

installation schematic for exact breaker sizing.

2. Each VFD should be fed by its own breaker. If multiple VFDs are to be combined on the same breaker, each drive should have its own protection measure (fuses or miniature circuit breaker) downstream from the breaker.

3. Input AC line wires should be run in conduit from the breaker panel to the drives. AC input power to multiple VFDs can be run in a single conduit if needed. Do not combine input and output power cables in the same conduit.

4. The VFD should be grounded on the terminal marked PE. A separate insulated ground wire must be provided to each VFD from the electrical panel. This will reduce the noise being radiated in other equipment.

5. Motors should be grounded to the VFD ground terminal only. Do not connect the motor ground to the heater ground terminal.

Fan to Building Wiring Connection

120V 1 PH.

Gal-flex conduit

(in unit)

Figure 15

208-240V 1 PH.

Gal-flex conduit

(in unit)

208-240/460/600V 3 PH.

Gal-flex conduit

(in unit)

120V 1 PH.

Standing

Power

Disconnect

Switch

Factory wiring 120V 1 PH.

Standing

Power

Disconnect

Switch

Factory wiring

208-240

1 PH.

120V 1 PH.

Standing

Power

Disconnect

Switch

Factory wiring

3 PH.

BK WH GR

Customer supplied wiring from building power or pre wired control panel

BK WH BK BK GR

Customer supplied wiring from building power or pre wired control panel

BK WH BK BK BK GR

Customer supplied wiring from building power or pre wired control panel

17

COMPONENTS

Part Identification

The following image and list identify typical indirect fired heater components and their functions.

Figure 16 – Typical Main Cabinet

# Name

1. Exhaust Flue Pipe

2. Flame Roll-Out Switch

3. Flame Sensor

4. Contactor

5. 750VA Transformer

6. Control Transformer

7. Control Transformer

8. Terminal Strip

9. Circuit Breaker

10. Dirty Filter Airflow Switch

(Optional)

11. Main Airflow Switch

Description

Ventilates combustion between the power-vent exhaust discharge and top of the unit.

Normally closed temperature activated switch. Mounted on bracket at inlet of the upper-most firing tube. Senses flame roll-out in the event of a blocked tube, low airflow, or low gas pressure. If flame-rollout is present, the switch de-energizes heater circuit on individual furnace. Must be manually reset by pressing small red button on back.

Continuously senses for the presence of flame in heating mode after ignition has commenced. Wired to Flame Safety

Control.

Contactor with overload protection to start and protect motor.

The transformer is designed to change one voltage to another by magnetic induction.

120V primary; 24V secondary control transformer.

120V primary; 24V secondary control transformer.

Central location to terminate control wiring. Should be used for troubleshooting.

Protects electrical components from high current spikes.

Senses whether the filters at the intake to the main blower are free of dirt and contaminant.

Senses that there is main airflow across the Heat-exchanger of the furnace. Adjustable set-point. Heater circuit will not energize unless proven.

18

# Name

12. Power-vent Airflow Switch

13. Flame Safety Control

14. IBT Board

*2 required if heat stages > 2

15. Cabinet Heater (Optional)

16. Modulating Valve Control

Transformer

17. HMI

Description

Normally open, non-adjustable airflow switch. Senses whether the power-vent blower is running and allows furnace to spark when airflow is proven.

Initiates and monitors flame. Equipped with non-adjustable time settings for pre-purge, inter-purge, and post-post of the exhaust flue and control cabinet.

Controls the 0-10V DC signal to the modulating gas valve(s), speed controller(s) and 24V AC signals to staged furnace controls. Speed controllers are built into the board. Main board DIP switches should all be set to off. When a slave board is used, the slave board DIP switch 1 should be set to on. Slave board DIP switches 2, 3 and 4 should remain off.

Use a Cat-5 cable from J5 of main board to J1 or J2 of slave board.

Recommended for winter design temperatures of 0°F or below.

120V primary; 24V secondary control transformer. Provides standing 24V power to Modulating Gas Valve.

IBT Board interface. The 4 buttons are used to navigate through the menus. (There can be up to 4 additional HMIs added. These can be used for interface or as a part of space tempering)

19

Figure 17 – Typical Burner Cabinet

# Name

1. Power-vent Motor

Description

Induces airflow through heat exchanger and flue of furnaces

A) Modulating furnace variable speed blower motor.

B) Non-modulating furnace constant speed blower motor.

Power Vent Motor Orifice Size

Furnace BTU (x1000/hr) Dia. (in.)

400 2.625

300

200

150

2.25

2.375

1.875

2. Main Disconnect Switch

3. Fan Motor Speed Control Options:

PSC Motor Speed Control

(Not Shown)

ECM Speed Control

(Not Shown)

Controls all electrical power to entire unit.

Manual knob split capacitor fan motor speed control.

Electronic motor speed control

Variable Frequency Drive (Shown) Used in place of motor starter to protect main blower motor and to control the speed of the main blower to vary main airflow across unit.

4. High pressure gas switch

5. Manifold Gas Pressure Gauge

6. Flame Roll-Out Switch

Monitors pressure and cuts off the electrical control circuit when pressure rises above the desired set point. (Optional)

Indicates manifold gas pressure on individual furnace.

Normally closed temperature activated switch. Mounted on bracket at inlet of the upper-most firing tube. Senses flame roll-out in the event of a blocked tube, low airflow, or low gas pressure. If flame-rollout is present, the switch de-energizes heater circuit on individual furnace. Must be manually reset by pressing small red button on back.

20

# Name

7. On/Off Gas Valve

8. Modulating Gas Valve

9. Low pressure gas switch

10. Main Inlet Gas Pressure Gauge

Not Shown:

- High Limit Switch

- Spark Ignitor

- Discharge Sensor

- Intake Air Sensor (not shown)

Description

On/off gas valve with built in regulator and manual shut off switch. One used on each furnace gas train.

Controls the amount of gas to the furnace to meet desired discharge/Space temperature. (Modulating units only)

Monitors pressure and cuts off the electrical control circuit when pressure drops below the desired set point. (Optional)

Indicates inlet gas pressure to unit.

Normally closed high temperature switch. De-energizes heater circuit on individual furnace if temperature exceeds mechanical set-point. Automatic recycling. 200°F set-point.

Powered by Flame safety control to initiate light-off.

10k Thermistor. Controls the discharge to which the heating module heats to and constantly tries to maintain. Freezestat and discharge Firestat functionality is built into this sensor if the options are enabled.

10k Thermistor. Reports intake temperature to the IBT board.

Heating/cooling will activate based off the set points on the

IBT Board. Does not control the temperature to which the unit heats the discharge. Located in the supply fan,

Motor Speed Control Options

ECM (Electronically Controlled Motor) Speed Control

EC motors and control allows accurate manual adjustment of fan speed. The benefit of EC motors is exceptional efficiency, performance, and motor life.

When using an EC motor, the blower control should be set to ECM. This menu item is located under factory settings > unit options > blower configuration. Once this is set, there is a PWM rate setting under user settings. This will be used to control the speed of the EC motor. The PWM signal will be sent directly to the ECM via J13-(2) PWM + and J13-(9) PWM ( –) pins.

NOTE: A Variable Frequency Drive (VFD) is required to adjust the speed control of a nonelectrically commutated 3 phase direct drive motor.

External PWM Signal

The fan unit will be shipped with power wiring and communication wiring fed to an internal junction box.

The fan is shipped with Shielded Twisted Pair (STP) wire which is used to wire to a remote PWM signal.

Red wire is used to go to the positive PWM signal and black wire is used to go to the negative PWM signal. Reference schematics for all wiring connections. STP is connected to the communication wiring of the motor using wire nuts in the junction box. If a preset length of STP is provided, it will be connected to the junction box from the factory. Run the STP through any available knockout in the fan base.

21

Variable Frequency Drive Speed Control (Installation Instructions)

ATTENTION! DO NOT CONNECT INCOMING AC POWER TO OUTPUT TERMINALS U, V, W.

SEVERE DAMAGE TO THE DRIVE WILL RESULT. INPUT POWER MUST ALWAYS BE WIRED TO

THE INPUT L TERMINAL CONNECTIONS (L1, L2, L3)

VFD Output Power

1. Motor wires from each VFD to its respective motor MUST be run in a separate steel conduit away from control wiring and incoming AC power wiring to avoid noise and crosstalk between drives. An insulated ground must be run from each VFD to its respective motor. Do not run different fan output power cables in the same conduit.

2. VFD mounted in ECP: If the distance between VFD and the motor is greater than the distances specified below, a load reactor should be used between VFD and motor. The load reactor should be sized accordingly and installed within 10 feet of the output of the VFD.

208/230V – Load reactor should be used when distance exceeds 250 feet.

460/480V – Load reactor should be used when distance exceeds 50 feet.

575/600V – Load reactor should be used when distance exceeds 25 feet.

3. VFD mounted in fan: The load reactor should be sized accordingly when VFD is mounted in the fan.

208/230V – Load reactor is optional but recommended for 15 HP and above motors.

460/480V – Load reactor is optional but recommended for 7.5 HP and above motors.

575V/600V – Load reactors are required for all HP motors.

4. If the distance between VFD and the motor is extremely long, up to 1000 FT, a dV/dT filter should be used. The VFD should be increased by 1 HP or to the next size VFD. The dV/dT filter should be sized accordingly and installed within 10 feet of the output of the VFD.

208/230V – dV/dT filter should be used when distance exceeds 400 feet.

460/480V – dV/dT filter should be used when distance exceeds 250 feet.

575/600V – dV/dT filter should be used when distance exceeds 150 feet.

5. No contactor should be installed between the drive and the motor. Operating such a device while the drive is running can potentially cause damage to the power components of the drive.

6. When a disconnect switch is installed between the drive and motor, the disconnect switch should only be operated when the drive is in a STOP state.

VFD Programming

1. The Drive should be programmed for the proper motor voltage. P107 is set to 0 (Low) if motor voltage is 120V AC, 208V AC or 400V AC. P107 is set to 1 (High) if motor voltage is 230V AC, 480V AC or

575V AC.

2. The Drive should be programmed for the proper motor overload value. P108 is calculated as Motor

FLA x 100 / Drive Output Rating (available in table below).

To enter the PROGRAM mode to access the parameters:

1. Press the Mode (M) button. This will activate the password prompt (PASS).

2. Use the Up and Down buttons to scroll to the password value (the factory default password is “0225”) and press the Mode (M) button. Once the correct password is entered, the display will read “P100”, which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu.

3. Use the Up and Down buttons to scroll to the desired parameter number.

4. Once the desired parameter is found, press the Mode (M) button to display the present parameter setting. The parameter value will begin blinking, indicating that the present parameter setting is being displayed. The value of the parameter can be changed by using the Up and Down buttons.

5. Pressing the Mode (M) button will store the new setting and also exit the PROGRAM mode. To change another parameter, press the Mode (M) button again to re-enter the PROGRAM mode. If the

Mode button is pressed within 1 minute of exiting the PROGRAM mode, the password is not required to access the parameters. After one minute, the password must be re-entered in order to access the parameters again.

P500 parameter provides a history of the last 8 faults on the drive. It can be accessed without getting into

PROGRAM mode.

22

1

1.5

2

3

5

7.5

10

15

20

0.5

1

1.5

2

3

5

7.5

1

2

3

5

7.5

10

15

20

25

30

10

15

20

25

ACTECH SMV VFD

HP

0.33

0.5

Part Number

ESV251N01SXB571

ESV371N01SXB571

Volts

120/240V

Table 6 – Cross-Reference Table

Input

Input

Input Amps 1Ø

120V AC

Input Amps 1Ø 240V

AC

X -

-

6.8 3.4

120/240V X 9.2 4.6

-

1 ESV751N01SXB571 120/240V X 16.6 8.3

-

1.5

HP

ESV112N01SXB571

Part Number

120/240V

Volts

X

Input

Input

20

Input Amps 1Ø

10

Input Amps 3Ø

ESV371N02YXB571

ESV751N02YXB571

ESV112N02YXB571

ESV152N02YXB571

ESV222N02YXB571

ESV402N02TXB571

ESV552N02TXB571

ESV752N02TXB571

ESV113N02TXB571

ESV153N02TXB571

ESV751N04TXB571

ESV112N04TXB571

ESV152N04TXB571

ESV222N04TXB571

ESV402N04TXB571

ESV552N04TXB571

ESV752N04TXB571

ESV113N04TXB571

ESV153N04TXB571

ESV183N04TXB571

ESV223N04TXB571

ESV751N06TXB571

ESV152N06TXB571

ESV222N06TXB571

ESV402N06TXB571

ESV552N06TXB571

ESV752N06TXB571

ESV113N06TXB571

ESV153N06TXB571

ESV183N06TXB571

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

X

-

-

-

-

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

240V

240V

240V

480V

480V

480V

480V

480V

480V

240V

240V

240V

240V

240V

240V

240V

600V

600V

600V

600V

600V

480V

480V

480V

480V

480V

600V

600V

600V

600V

2.5

3.6

4.1

5.4

9.3

12.4

33

48

59

2.9

5

6.9

8.1

10.8

18.6

26

2

3.2

4.4

6.8

10.2

15.8

24

31

38

45

12.4

19.7

25

31

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

17.1

-

-

-

-

5.1

8.8

12

13.3

30 ESV223N06TXB571 600V X 36

1.7

2.7

3.9

6.1

9

14

21

27

34

40

11

17

22

27

2.1

3

3.5

4.8

8.2

11

29

42

54

2.4

4.2

6

7

9.6

16.5

23

Output

Amps

1.7

2.4

4.2

6

Output

Amps

32

Breaker 1Ø

120V AC

15

15

25

30

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Breaker 1Ø

15

15

20

25

30

-

-

-

-

Breaker 1Ø

240V AC

15

15

15

20

15

15

15

15

15

20

50

80

90

Breaker 3Ø

15

15

15

15

20

30

40

15

15

15

15

20

25

40

50

70

80

20

30

40

50

60

23

Optional Components

Electric Cabinet Heater

Units can be shipped with an optional 120V electric cabinet heater powered from the IBT board. There is a temperature sensor built onto the IBT Board that will regulate when the cabinet heater activates.

Motorized Intake Damper

On units shipped with the optional motorized intake damper, a power transformer is supplied with the unit if the main incoming voltage is greater than 120V. The damper motor is energized whenever the blower gets a call to run. No external wiring to the damper motor is required .

AC Interlock

On units equipped with an optional AC interlock, 24V AC power from Y1 in the condensing unit or rooftop unit should be field wired to screw terminal J11-(5) on the IBT board. 24V AC common from C in the condensing unit or rooftop unit should be field wired to terminal block J11-(8) on the IBT board. When these terminals are powered, heat will be locked out on the IBT.

Remote (HMI) Control Panel

On units shipped with a space HMI, a Cat 5 cable will need to be run from J3 on the main IBT Board to J2 on the HMI. If additional space

HMIs have been added, they can be daisy chained from the first HMI.

In the event there is a slave IBT board, HMIs can also be powered from

J1 or J2 of the slave board. An end of line resistor should be added to the last HMI in the chain.

OPERATION

Figure 18 – Space HMI

HMI Configuration

General Overview

The HMI allows the user to change parameters, and options. You can use the HMI to view operating Information regarding sensors, temperatures, pressures, and fault history.

There are four buttons to navigate through the HMI screens.

Note: Buttons change functions during certain options, and tests.

Verify the screen, and buttons throughout the menu display.

The user can access the HMI configuration screen by pressing the top two buttons simultaneously. To exit this screen, simply press the BACK button. When setting certain options or functions, pressing the BACK button multiple times will bring up the reboot screen. The user may select

‘YES’ to save the changes or select ‘NO’ to return to factory settings, or select ‘CANCEL’. When selecting ‘CANCEL’, any changes made will not be saved, and the screen will return to the top menu.

The HMI menu system allows full access to every configurable parameter in the HMI. The parameters are factory configured to the specific application. Parameters may need to be modified to fine tune automatic operation after the original setup.

Figure 19 – Idle Screen

Figure 20 – Warning Screen

24

HMI Options Screen

To set the HMI number or to adjust the screen contrast, press the bottom two buttons simultaneously on the HMI faceplate. Use the UP and Down buttons to select the parameter that will be adjusted. Press

Enter to select the highlighted parameter.

Setting the HMI number configures the Modbus address for that HMI.

To change the contrast, select “Advanced Options”. The user may adjust the setting from 0 to 10. Setting the contrast to 0 is the lowest setting available and 10 is the highest contrast setting available. The factory default contrast setting is 5.

HMI Notification Letters

The HMI will display notification letters when the unit is in a specific status.

Figure 21 – Notification Letters

• When the blower is in a delay, a “B” will be displayed.

When the condensers are in a Min ON or Min OFF time, a

“T” will be displayed.

HMI Menu Description

USER SETTINGS

(Any changes within this menu do not require a reboot to take effect)

Temp Set Points – Some of these may not be available based on settings. If scheduling is enabled there will be both occupied and unoccupied values for each set point.

Scheduling – This menu will only show when scheduling option has been turned on. Each day contains the option for two occupied time periods. If the time is scrolled past 11:59pm it will display UNOCC.

Copy Schedule – This will allow the user to copy an existing schedule from one day of the week to individual days in the week, to Week Days, or ALL.

Fan Speed - Enabled when blower control is set to VFD Manual. The range of this menu is limited by the min and max frequency set points under factory settings. When occupied scheduling is set to on, occupied and unoccupied settings are available.

HMI Dimming Timer - Configurable menu time until dim, 10 seconds - 60 seconds.

PWM Rate - Enabled when blower control is set to ECM. This will be used to control the speed of the ECM motor. The PWM signal will be sent directly to the ECM motor. When occupied scheduling is set to on, occupied and unoccupied settings are available.

Mixing Box Voltage - Enabled when ‘Mixing Box Config’ is set to ‘Manual’. Voltage output to air box damper.

Outdoor Air % - Enabled when ‘Mixing Box Config’ is set to ‘Schedule’, or ‘Outdoor Air %’.

Limited by min and max outdoor air percentages in factory settings. When occupied scheduling is set to on, occupied and unoccupied settings are available.

Active Faults – Contains the current faults on the board

Fault History - Will show time stamped history of the last 20 faults, most recent fault showing first.

Reset Fault Lockout – Resets lock out faults.

25

FACTORY SETTINGS

( Password = 1111 )

(These will be set job specific from the plant. Any changes within this menu require a reboot to take effect. Upon exiting factory settings, if anything has been altered, the board will reboot itself.

Password = 1111. There is a 5 minute timer before having to re-enter password.)

Temperature Control - If scheduling is enabled there will be both occupied and unoccupied values for each set point.

▪ Tempering Mode Heat – Discharge, Space, Analog Control, DDC, None.

▪ Tempering Mode Cool – Intake, Space, Analog Control, DDC, None.

▪ Activate Based On – Intake, Space, Both, Either, Stat. Default is Either.

Heating Config

▪ # Of Heat Stages – 0, 1, 2, 3, 4 heat stages.

▪ Intake Heat Hysteresis (Hyst) – Intake sensor must go this amount of degrees above the set point before heating will turn off.

▪ Space Heat Hysteresis (Hyst) – Space sensor must go this amount of degrees above the set point before heating will turn off.

▪ Heater Firing Order – Standard, alternate. Standard firing order is furnace 1, 2, 3, 4.

Alternate firing order is furnace 2, 1, 3, 4. This option has no effect for single furnace units.

▪ Input Source – 0-10V DC, 2-10V DC, 0-20 mA, 4-20 mA. This lets the board know what signal to expect from an Analog Control system.

▪ Cabinet Diff – This is the differential for the cabinet heater. The outdoor air temp must fall this many degrees below the activation set point to turn off.

▪ Freezestat Timer – The discharge temp must stay below the freezestat set point for this amount of time before the unit will lock out on freeze stat.

▪ ROT Delay – This is the time after a furnace loses a call for heat before the furnace shuts down.

▪ RCT Delays – If the heat stage value is greater than 1,

RCT Delay Defaults (in Seconds) the user may adjust Relay Close Time (RCT) delay for stages 2, 3, 4. Range settings is 30-600 seconds.

Cooling Config

▪ Cooling Type – None, DX, Evap, Both. If “None” is

RCT Stage 2 Stage 3 Stage 4

1

2

3

4

0

120 s

0

0

0

90 s

120 s

0

0

90 s

90 s

120 s selected all cooling options under user settings are hidden.

▪ Min Cool OA Temp – When the space temperature is calling for cooling, and the outdoor air temperature is below the set point, the unit will shut the condensers off, and start the blower to use outdoor air to cool the space. Default is 55°F. Range setting is 40-90°F.

▪ Condenser Staging – 0, 1, 2, or 3 condensers. Within the 2 and 3 condenser selection, there is another submenu which allows for 2 or 3 stages. For 2 condenser units, 3 stages should only be selected when the condensers are of unequal tonnages.

▪ Intake Cool Hysteresis (Hyst) – Intake sensor must fall this many degrees below the set point for the stage to turn off.

▪ Space Cool Hysteresis (Hyst) – Space sensor must fall this many degrees below the set point for the stage to turn off.

▪ Cond Min Time On – Minimum time each condensing stage must remain on after becoming activated. This is to prevent stage cycling. A “T” will be present in the lower left corner of the home screen when any of the condensers are in a MIN ON/OFF TIME.

▪ Cond Min Time Off – Minimum time each condensing stage must remain off after being deactivated. This is to prevent stage cycling. A “T” will be present in the lower left corner of the home screen when any of the condensers are in a MIN ON/OFF TIME.

▪ Evap Config (continued) o Spray Time On – Time the evaporative cooler will spray in the cycle. o Spray Time Off – Time the evaporative cooler will be idle in the cycle. o Evap Drain – On/Off. Default is Off. o Evap Drain SP - This setting will monitor outside air so that the water does not freeze within the evaporator module. Default setting is 40°F. Range setting is 35-50°F.

26

FACTORY SETTINGS

( Password = 1111 )

▪ Evap Config (continued) o Drain Differential – Temperature differential setting before the drain shuts off. Default setting is 2°F. Range setting is 1-5°F. o Evap Differential – Temperature differential before the evap cooling shuts off. Default setting is 3°F. Range setting is 1-10°F.

Occupied Scheduling – This menu is where the scheduling can be turned On or Off. Default is

Off.

Occupancy Override – This menu is where the occupancy override can be turned On or Off.

Default is On.

Unit Options

▪ Board Config o IBT Address – Modbus address of the IBT board.

o Startup Timer – Time upon power up where the board will sit idle. o Celsius/Fahrenheit – Celsius, Fahrenheit. Changing between the two will reset all set points. o # of HMIs – Number of HMIs connected to the IBT board. Must always be at least one. o HMI Averaging – If there are multiple space HMIs connected, this menu allows you to select which will be included in the space averaging. If a thermistor is connected into the ST screw terminals, it will automatically be averaged into any HMIs included. o HMI Dimming – This is an On/Off menu. Default is set to Off. If set to On, a ‘HMI

Dimming Timer’ option will be available under ‘User Settings’. o Screensaver - This is an On/Off menu. Default is set to On. If set to Off, the home screen will not time out to the screensaver.

▪ Blower Config o Blower Control – 120V Contactor, VFD Manual, VFD Jog, VFD 0-10V, ECM, ECM 0-

10V.

➢ 120V Contactor – 120V output on the IBT board to drive the coil of a contactor. This option should be selected when the IBT is used in conjunction with a DCV package.

➢ VFD Manual – HMI selectable VFD frequency.

VFD Jog – For use with VFD using photohelic control. Uses the aux pins to control the VFD. Powering aux 1 will speed the fan up, powering aux 2 will slow the fan down. When aux

1 or aux 2 are not powered, the VFD will hold current speed.

➢ VFD 0-10V – For use when an external 0-10V signal is being provided to control the speed of the VFD. The VFD output from this input will be based on the VFD min and max freq set under protected params in factory settings. 0 Volts will equal VFD min,

10V will equal VFD max, and all voltages in between will be scaled linearly. This option will utilize 0-10V J14-(6) and 0-10V common J14-(7) screw terminals and will o require field wiring.

➢ Electronically Controlled Motor (ECM) - HMI selectable PWM rate.

ECM 0-10V For use when an external 0-10V signal is being provided to modulate the ECM supply output between min and max speed.

Blower Mode – If the Occupied Scheduling is set to ON, the menu screen for the blower mode will allow you to choose ON/AUTO/OFF for Occupied or Unoccupied. If the

Occupied Scheduling is set to OFF, the menu screen for the blower mode will allow you to choose MANUAL/AUTO/OFF. In blower auto mode, the blower will only run when it gets a call for heating/cooling. In blower manual mode, the blower will run as long as the fan button is enabled regardless of whether the unit is heating/cooling. In blower off mode, powering the unit interlock pin will cause the blower to run. This setting should be used when an IBT is covered by a prewire package.

27

FACTORY SETTINGS

( Password = 1111 ) o Blower Start Delay – On, Off. Enabling this menu will run the furnace before starting the blower. A “B” will be present in the lower-left corner when the unit is in a blower

START/STOP DELAY.

o Blower Stop Delay – On, Off. Enabling this menu

Table 7 – Fan Speed Presets will stop the furnace and allow the blower to run until timer expires.

A “B” will be present in the lower-left corner when the unit is in a blower

PRESET AUX 1 AUX 2 AUX 3

Speed 1

Speed 2

X

X

Speed 3 X X START/STOP DELAY.

o Blower Delay Time – This sets the time that the furnace will run before the blower starts. o Blower Preset Speed – This allows the user to

Speed 4

Speed 5

Speed 6

Speed 7

X

X

X

X

X

X

X

X set blower preset option On or Off. o VFD Direction – Sends a command to the VFD to run in forward or reverse. o

Fan Speed Presets - Uses aux pins to control supply fan VFD, see Table 7 .

o Occ Fan Presets – Occupied scheduled presets 1-7. o Unocc Fan Presets – Unoccupied scheduled presets 1-7.

▪ Purge Config o Purge Button – On, Off. This function will be active when the mixing box is enabled.

When the purge button is pressed, the mixing box dampers will open to max outdoor air and turn on the exhaust contactor.

o Purge Time –This is setting is adjustable from 1 – 120 minutes, default is 15 minutes.

This is the amount of time that the unit will run the purge process, if the user does not stop the purge manually. o VFD Purge Speed – Adjustable between VFD Min and Max frequency. This is the speed the blower will run during the purge cycle. Default is 60 Hz. o ECM Purge Speed – This is the speed the blower will run during the purge cycle. This is adjustable between PWM Min and Max frequency.

▪ Monitoring Sensors – These are On/Off menus. Default is Off.

Smoke Detector, Filter Monitor, Intake Firestat, Discharge Firestat, Freezestat, Low Gas Switch,

High Gas Switch.

▪ Mixing Box Config o Mixing Box – None, Manual, 2 Position, Schedule, Table 8 – Damper Presets

Outdoor Air %, 100% OA, Analog Control. o Mixing Box Deadband – If the temperature difference

PRESET AUX 1 AUX 2 AUX 3

Position 1 X between the outdoor and return sensor is less than or

Position 2 X equal to this set point, the IBT board will not attempt Position 3 X X to adjust the output voltage until it matches the outdoor air percentage set point. This setting only

Position 4

Position 5 X

X

X

Position 6 X X takes effect when either outdoor air % or schedule is

Position 7 X X selected. o Return As Space – On, Off. Setting this to on will not require a space sensor or HMI. It

X will use the return air thermistor (RT) in place of the space sensor. o Min Outdoor Air % - Minimum allowed outdoor air percentage. User can set occupied and unoccupied percentage range. o Max Outdoor Air % - Maximum allowed outdoor air percentage. User can set occupied and unoccupied percentage range. o Off Position – Allows user to select how the dampers will be positioned when the supply fan is off. Standard (default), Max Outdoor Air %, or Min Outdoor Air %. o Damper Presets – This allows the user to set damper preset option On or Off. o Preset Volts

– Uses aux pins to control damper actuator, see Table 8 .

28

(Password = 1111)

FACTORY SETTINGS

▪ Intake Damper – On, Off.

▪ Room Override – On, Off option. This setting will only have an effect when the heat tempering mode is set to Discharge and “Activate Based On” is set to “Either” (intake or space temperature). When the space is calling for heat it will use the Room Override SP instead of

Discharge SP to heat the space.

▪ Exhaust Cntctr (Contactor) – Off, before airflow, after airflow. If scheduling is enabled there will be both occupied and unoccupied values for each set point.

▪ Exhaust On Smoke – Off, On. Input that when enabled, if it receives a 120V signal from a fire system, will shut down the supply fan and enable the exhaust contactor.

▪ Cabinet Heater – On, Off.

▪ Drain Heater – On, Off.

Occupied Override (Occpd Ovrd) Duration – Length of override timer. If override is active it can be manually stopped by pressing the end override button on the HMI. The default setting is 1 hour but can be adjusted up to 16 hours.

Limit Set Point (SP) Adjust - This allows the user to change the current temperature set point from the home screen. The range adjustment is 0-100 degrees. The default is 5 degrees. When the setpoint is set to 0°F/C the adjustment buttons (+/-) will not be visible.

Protected Params – VFD Min and Max Frequency can be adjusted here. PID values within this menu should not be changed

SERVICE SETTINGS

(Password = 1234)

Temperatures – Menu to view all of the temperature sensors.

Discharge Disp Offset – Display offset for discharge temp. This can be used if actual discharge temperature is measured differently on site.

Space Disp Offset – Display offset for space temp. This can be used if actual space temperature is measured differently on site.

Inputs

▪ Open/Closed Status – Menu to view the open/closed status of all inputs.

▪ Voltages – Voltage Inputs. Analog Control, Air quality, Mixing Box Damper, Indoor RH and

Outdoor RH.

▪ VFD Status – Live parameter feedback from the VFD.

Outputs – Board output equipment status.

Test Menu – To stop any test, hit the abort button on the HMI.

▪ Test Fans – All, Supply, Exhaust.

▪ Test Heating – Contains high and low fire tests for stages. If “Heating Config” is set to 0, then

“No Heat Stage Set” will display.

▪ Test Cooling Evap/DX – All, 1, 2, 3, Evap. If “Cooling Config” is set to none, then "No Cooling

Type Set" will display.

▪ Test Analog Control – This test will simulate a voltage input from an analog control system.

The test will begin at 0 volts. The up and down buttons allow for modulation of input.

▪ Test Options.

o Cabinet Heater – Beginning this test will turn the cabinet heater on. o Drain Heater – Beginning this test will turn the drain heater on. o Mixing Box – Beginning this test will create an output to the mixing box. The test will begin at 0 volts. The up and down buttons allow for modulation of the output.

Clear Fault History – Will clear the entire fault history. If there is an active fault when cleared, that fault will show up until it is fixed.

Factory Reset – Will reset board to factory commissioned settings.

Update Factory Defaults – This allows the original factory default settings to be overridden.

When confirming the updated settings, these settings will now be used when “Factory Reset” is needed.

29

HMI Menu Tree

The top menu of the IBT Board contains 3 main categories. These categories are user settings, factory settings, and service.

TEMP SET

POINTS

HEATING

COOLING

OPTIONS

INTAKE HEAT

SPACE HEAT

DISCHARGE

HEAT

MIN DISCHARGE

HEAT

MAX DISCHARGE

HEAT

INTAKE COOL

STAGE 1

SPACE COOL

INTAKE COOL

DIFFERENTIAL

SPACE STAGE

DIFFERENTIAL

EVAP COOL

ROOM

OVERRIDE

INTAKE

FIRESTAT

DISCHARGE

FIRESTAT

FREEZESTAT

CABINET HEAT

DRAIN HEAT

EVAP DRAIN

DRAIN

DIFFERENTIAL

EVAP

DIFFERENTIAL

RANGE

35-110 °F / 2-43°C

RANGE

35-110 °F / 2-43°C

RANGE

40-150 °F / 4-66°C

RANGE

40-150 °F / 4-66°C

RANGE

40-150 °F / 4-66°C

RANGE

55-120 °F / 13-50°C

RANGE

50-120 °F / 10-32°C

RANGE

0-20 °F / 1-13°C

RANGE

0-20 °F / 1-13°C

RANGE

55-100 °F / 13-38°C

RANGE

40-150 °F / 4-66°C

RANGE

100-300 °F

38-149 °C

RANGE

100-300 °F

38-149 °C

RANGE

(-40)-75 °F

(-40)-24 °C

RANGE

0-40 °F / (-18)-4°C

RANGE

35-45 °F / 2-7°C

RANGE

35-50 °F / 2-10°C

RANGE

1-5 °F / 1-3°C

RANGE

1-10 °F / 1-6°C

DEFAULT

240 °F / 116°C

DEFAULT

35 °F / 2°C

DEFAULT

0 °F / -18°C

DEFAULT

35 °F / 2°C

DEFAULT

40 °F / 4°C

DEFAULT

2 °F / 1°C

DEFAULT

3 °F / 2°C

DEFAULT

60 °F / 16°C

DEFAULT

70 °F / 21°C

DEFAULT

80 °F / 21°C

DEFAULT

80 °F / 10°C

DEFAULT

120 °F / 66°C

DEFAULT

75 °F / 29°C

DEFAULT

74 °F / 23°C

DEFAULT

10 °F / 6°C

DEFAULT

2 °F / 2°C

DEFAULT

85 °F / 29°C

DEFAULT

90 °F / 31°C

DEFAULT

135 °F / 57°C

30

SCHEDULING

COPY SCHEDULE

FAN SPEED

HMI DIMMING TIMER

PWM RATE

MIXING BOX VOLTAGE

OUTDOOR AIR %

ACTIVE FAULTS

FAULT HISTORY

RESET LOCKOUTS

START TIME A

END TIME A

START TIME B

END TIME B

COPY FROM: (DAY)

COPY TO: (DAY, WEEK DAYS, ALL)

RANGE - MIN TO MAX VFD

FREQUENCY

RANGE

10-60 SECONDS

RANGE

0-100%

RANGE

0-10V

RANGE

MIN TO MAX

OUTDOOR AIR %

DISPLAYS ACTIVE FAULTS

SHOWS MOST RECENT

FAULTS IN SYSTEM

RESETS FAULTS THAT

LOCKOUT THE SYSTEM

MON/FRI 8AM

SAT/SUN UNOCC

MON/FRI 6PM

SAT/SUN UNOCC

DEFAULT

UNOCC

DEFAULT

UNOCC

DEFAULT

60 HZ

DEFAULT

60 SECONDS

DEFAULT

100%

DEFAULT

0.00 V

DEFAULT

100%

31

ENTER

PASSWORD

1111

TEMPERATURE

CONTROL

HEATING

CONFIG

DISCHARGE

HEAT

TEMPERING

MODE

COOL

TEMPERING

MODE

SPACE

ANALOG

CONTROL

DDC

NONE

INTAKE

SPACE

ANALOG

CONTROL

DDC

NONE

INTAKE

SPACE

ACTIVATE

BASED ON

# OF HEAT

STAGES

SPACE HEAT

HYST

INTAKE HEAT

HYST

HEATER FIRING

ORDER

INPUT SOURCE

CABINET DIFF

FREEZESTAT

TIMER

ROT DELAY

RCT DELAYS

2/3/4

BOTH

EITHER

STAT

0-4

RANGE

0-3 °F / 0-10°C

RANGE

0-5 °F / 0-3°C

STANDARD

DEFAULT

DEFAULT

1

DEFAULT

3

0

°F / 1°C

°F / 2°C

ALTERNATE

0-10V

2-10V

0-20mA

4-20mA

RANGE

1-4 °F / 1-20°C

RANGE

0-20 MINUTES

RANGE

30-240

SECONDS

RANGE

30-600

SECONDS

DEFAULT

1 °F / 5°C

DEFAULT

20 MINUTES

DEFAULT

45 SECONDS

DEFAULT

VARIES PER STAGE

32

COOLING

CONFIG

OCCUPIED

SCHEDULING

OCCUPANCY

OVERRIDE

COOLING TYPE

MIN COOL

OA TEMP

CONDENSER

STAGING

INTAKE COOL

HYST

SPACE COOL

HYST

COND MIN ON

TIME

COND MIN OFF

TIME

EVAP CONFIG

ON/OFF

ON/OFF

NONE

DX

EVAP

BOTH

RANGE

40-90 °F / 4-32°C

NONE

1 CONDENSER

1 STAGE

2 COND

2 STAGES

2 COND

3 STAGES

3 COND

2 STAGES

3 COND

3 STAGES

RANGE

0-5 °F / 0-10°C

RANGE

0-3 °F / 0-10°C

RANGE

1-5 MINUTES

RANGE

1-5 MINUTES

SPRAY TIME ON

SPRAY TIME OFF

EVAP DRAIN

EVAP DRAIN SP

DRAIN

DIFFERENTIAL

EVAP

DIFFERETIAL

DEFAULT

OFF

DEFAULT

ON

DEFAULT

55 °F / 13°C

DEFAULT

3 °F / 2°C

DEFAULT

1 °F / 1°C

DEFAULT

2 MINUTES

DEFAULT

2 MINUTES

RANGE

0-60 SECONDS

RANGE

0-500 SECONDS

ON/OFF

RANGE

35-50 °F / 2-10°C

RANGE

1-5 °F / 1-3°C

RANGE

1-10 °F / 1-6°C

DEFAULT

SET BY PLANT

DEFAULT

SET BY PLANT

DEFAULT

OFF

DEFAULT

40 °F / 4°C

DEFAULT

2 °F / 2°C

DEFAULT

3 °F / 2°C

33

UNIT OPTIONS

BOARD CONFIG

BLOWER CONFIG

IBT ADDRESS

STARTUP TIMER

CELSIUS /

FAHRENHEIT

# OF HMIS

HMI DIMMING

SCREENSAVER

HMI AVERAGING

BLOWER CONTROL

RANGE

1-247

RANGE

5 SECONDS -

4 MINUTES

CELSIUS /

FAHRENHEIT

RANGE 1-5

ON/OFF

ON/OFF

HMI: 2-5

AVERAGE SENSOR:

ON/OFF

120V CONTACTOR

VFD MANUAL

VFD JOG

VFD 0-10V

ECM

ECM 0-10V

BLOWER MODE

BLOWER START

DELAY

BLOWER STOP

DELAY

BLOWER DELAY

TIME

BLOWER PRESET

SPEED

VFD DIRECTION

FAN SPEED

PRESETS

ON/AUTO/

MANUAL/OFF

ON/OFF

ON/OFF

RANGE

0-120 SECONDS

ON/OFF

FORWARD/REVERSE

PRESET

1-7

DEFAULT

AUTO

DEFAULT

OFF

DEFAULT

OFF

DEFAULT

90 SECONDS

DEFAULT

OFF

DEFAULT

FORWARD

DEFAULT

PRESET 1: 30 HZ

DEFAULT

71

DEFAULT

00:05

DEFAULT

FAHRENHEIT

DEFAULT

1

DEFAULT

OFF

DEFAULT

ON

DEFAULT

2

OFF

34

UNIT OPTIONS

PURGE CONFIG

MONITORING

SENSORS

MIXING BOX

CONFIG

INTAKE DAMPER

ROOM OVERRIDE

PURGE BUTTON

PURGE TIME

VFD PURGE

SPEED

ECM PURGE

SPEED

SMOKE

DETECTOR

FILTER MONITOR

INTAKE FIRESTAT

DISCHARGE

FIRESTAT

FREEZESTAT

LOW GAS SWITCH

HIGH GAS

SWITCH

MIXING BOX

MIXING BOX

DEADBAND

MIN OUTDOOR

AIR %

MAX OUTDOOR

AIR %

RETURN AS

SPACE

DAMPER

PRESETS

PRESET VOLTS

OFF POSITION

ON/OFF

ON/OFF

ON/OFF

RANGE

1-120 MINUTES

RANGE

30-60 HZ

RANGE

PWM MIN-MAX

DEFAULT

OFF

DEFAULT

15 MINUTES

DEFAULT

60 HZ

VARIES BASED ON

DESIGN

ON/OFF

DEFAULT

OFF

ON/OFF

ON/OFF

ON/OFF

ON/OFF

ON/OFF

ON/OFF

DEFAULT

OFF

DEFAULT

OFF

DEFAULT

OFF

DEFAULT

OFF

DEFAULT

OFF

DEFAULT

OFF

OFF

MANUAL

2 POSITION

SCHEDULE

OUTDOOR AIR %

ANALOG CONTROL

DEFAULT

MANUAL

0-10 °F / 0-6°C

0-100%

0-100%

ON/OFF

DEFAULT

5 °F / 3°C

DEFAULT

0

DEFAULT

100

DEFAULT

OFF

ON/OFF

RANGE

PRESET 1-7

STANDARD

MAX OUTDOOR AIR %

MIN OUTDDOR AIR %

DEFAULT

OFF

DEFAULT

PRESET 1: 0V

DEFAULT

STANDARD

DEFAULT

ON

DEFAULT

OFF

35

UNIT OPTIONS

OCCPD OVRD

DURATION

LIMIT SP ADJUST

PROTECTED

PARAMS

ENTER

PASSWORD

1234

EXHAUST

CNTCTR

EXHAUST ON

SMOKE

CABINET HEATER

DRAIN HEATER

RANGE

1-16 HOURS

RANGE

0-100 °F / 0-55°C

DO NOT ADJUST

THESE

PARAMETERS

NONE

BEFORE AIRFLOW

AFTER AIRFLOW

ON/OFF

ON/OFF

ON/OFF

DEFAULT

1 HOUR

DEFAULT

5 °F / 3°C

TEMPERATURES

SENSOR OFFSET

INPUTS

DEFAULT

NONE

DEFAULT

OFF

DEFAULT

OFF

DEFAULT

OFF

INTAKE

DISCHARGE

RETURN

OUTSIDE

SPACE (ST THERMISTOR)

CABINET

SPACE AVG

HMI2 (SPACE HMI1)

HMI3 (SPACE HMI2)

HMI4 (SPACE HMI3)

HMI5 (SPACE HMI4)

DISCHARGE DISP

OFFSET

SPACE DISP

OFFSET

OPEN/CLOSED

STATUS

VOLTAGES

VFD STATUS

RANGE

+/- 20 °

RANGE

+/- 5 °

CURRENT

STATUS OF

INPUTS

BOARD

INPUT/OUTPUT

VOLTAGE

READINGS

REAL TIME VFD

FEEDBACK

DEFAULT

0 °

DEFAULT

0 °

36

OUTPUTS

TEST MENU

CLEAR FAULT HISTORY

SET CLOCK

FACTORY RESET

UPDATE FACTORY

DFLTS

OPEN/CLOSED STATUS

CURRENT STATUS OF

INPUTS/OUTPUTS

VARIABLE VALUES

OUTPUT SOURCE

TEST FANS

TEST HEATING

TEST COOLING

EVAP/DX

TEST ANALOG

CONTROL

TEST OPTIONS

ENTER TO CONFIRM

BACK TO EXIT

MONTH DAY YEAR

TIME

ENTER TO CONFIRM

CANCEL TO EXIT

ENTER TO CONFIRM

CANCEL TO EXIT

MOD VALVES

POWER VENT 1

POWER VENT 2

MIXING BOX

PWM RATE

SOFTWARE/HMI

ALL/SUPPLY/EXHAUST

RUN HIGH FIRE TEST

RUN LOW FIRE TEST

ALL/1/2/3/EVAP

0-10V INPUT

SIMULATION

CABINET HEATER

DRAIN HEATER

MIXING BOX

ON/OFF STATUS

ADJUST PARAMETER

TO TEST

ADJUST PARAMETER

TO TEST

ADJUST PARAMETER

TO TEST

ADJUST PARAMETER

TO TEST

ALL/1/2/3/4

ALL/1/2

ON/OFF

ON/OFF

0-10V OUTPUT

SIMULATION

37

Start Up

Prior to starting up or operating the heater, check all fasteners for tightness. In particular, check the set screw in the wheel hub, bearings, and the fan sheaves (pulleys). With power and gas to the heater OFF or prior to connecting ventilator to power, turn the fan wheel by hand to be sure it is not striking the inlet or any obstacles. Re-center, if necessary.

Tools Required

AC Voltage Meter

Tachometer

Standard hand Tools

Amperage Meter

Manometer

Thermometer

Start Up Procedure

1. Check all electrical connections for tightness and continuity.

2. Check pulley alignment and belt tension as shown in Pulley Alignment/Proper Belt Tension (page

44).

3. Inspect the condition of the intake damper and damper linkage, if provided.

4. Inspect the air-stream for obstructions and install intake filters if missing.

5. Compare the supplied motor voltage with the fan’s nameplate motor voltage. If this does not match, correct the problem.

6. Start the fan up by turning the external disconnect to the ON position, and shut it OFF immediately.

Check rotation of the wheel with the directional arrow on the blower scroll. Reversed rotation will result in poor air performance, motor overloading and possible burnout. For units equipped with a single-phase motor check the motor wiring diagram to change rotation. For 3-phase motors, any two power leads can be interchanged to reverse motor direction.

7. When the fan is started up, observe the operation and check for any unusual noises.

38

Gas Pressure Adjustment

Table 9 - Reference Information (Natural Gas)

1st Furnace

(Modulating)

2nd Furnace

(On/Off or

Modulating)

1 Furnace

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

N/A

# of Furnaces in Unit

2 Furnaces

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

3 Furnaces

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

3rd Furnace

(On/Off)

4th Furnace

(On/Off)

N/A

N/A

N/A

N/A

3.5" w.c.

N/A

FURNACE

# 1

(MODULATING)

FURNACE

# 2

(MODULATING)

Figure 22 – Typical Furnace Layout

FURNACE

# 3

(ON/OFF)

FURNACE

# 4

(ON/OFF)

4 Furnaces

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

On/Off Valve Fully

Open Maxitrol

Modulating Valve @

3.5" w.c.

3.5" w.c.

3.5" w.c.

INDIRECT FIRED MODULE INDIRECT FIRED MODULE

BLOWER MODULE

39

Furnace Start-Up (Summary)

Setting Incoming Pressure

Pressure must be measured at the first “T” in the supply gas line before the first gas valve.

Adjusting On/Off Stages

Remove the pressure regulator adjustment cover screw on the On/Off valve and using a screwdriver. Refer to

Table 9 for proper adjustment settings based on # of

furnaces in the unit. Turn the inner adjustment screw clockwise to increase the gas flow and counter-clockwise to decrease the gas flow. Replace the pressure regulator adjustment screw cover.

Adjusting the High Fire (modulating stage)

Set pressure according to Table 9 .

Press and hold button

#1 down on the modulating gas valve until the LED light is solid red. This will drive the valve into its fully open position. Adjust high fire. Press or hold button #1 to increase gas flow. Press or hold button #2 to decrease gas flow. Hold down both buttons to save the high fire setting.

Adjusting the low fire (modulating stage)

Low fire manifold pressure

:

The desired pressure reading for natural gas is

0.15” . If this cannot be obtained, set the low fire pressure as low as possible.

The pressure reading for propane gas should be

0.75” .

Press and hold button #2 down on the modulating gas valve until the LED blinks red. This will drive the valve into its minimum flow position. Adjust low fire. Press or hold button #1 to increase gas flow. Press or hold button

#2 to decrease gas flow. Hold down both buttons to save the low fire settings. Replace cover.

40

Furnace Startup

1. Open the field installed manual gas shut-off valve, and ensure the On/Off gas control valve knob is set to ‘On’.

2. Check the inlets to all of the firing tubes on the furnace and ensure that they are all clear of foreign debris. Verify that the tubes line up properly with each nozzle of the gas manifold.

3. Start the unit and check the gas supply pressure at the inlet gas gauge, this gauge is upstream of all electronic gas valves.

The inlet pressure should be 7 in. - 14 in. w.c. on natural gas or 11 in. – 14 in. w.c. on propane gas . If the inlet pressure is too high, install an additional pressure regulator external to the unit.

4. Verify DIP switches are set correctly on the modulating valve.

Factory settings are all DIP switches ‘OFF’.

5. A final gas leak check shall be performed to verify the gastightness of the heater’s components and piping under normal operating conditions.

6. At any point during high/low fire burner adjustment, check the characteristics of the flames in every firing tube of the furnace.

Non-existence of flame or a lazy flame can be caused by low gas pressure, a dirty nozzle orifice, or clogged section of exhaust flue.

7. When testing is complete, replace all caps and covers removed during the adjustment procedure.

Table 10 – DIP Switch Position

High Fire Burner Adjustment

1. Set the unit into high fire mode. This is achieved by configuring

high fire by going into the HMI Configuration menu (page 24).

Service>test menu>test heating>run high fire test>stages: all .

2. After it has been verified that the furnace(s) are lighting off properly, the manifold gas pressure should be adjusted to jobsite conditions. The gas pressure regulator (integral to the

On/Off gas control valve) is adjusted at the factory for average gas conditions. It is important that the gas supplied to the furnace is in accordance with the input rating on the rating plate.

Figure 23 – ON/Off Gas Valve

See “Gas Pressure Adjustment Reference Information” (page

39) for an overview of proper pressure settings of all furnaces

and for a visual representation of the layout of the furnaces.

Once the gas pressure is verified, exit the high fire test.

Once the gas pressure is verified, continue to step 3.

Figure 24 – Modulating

Valve

3. If the unit is set up for analog control, continue with high fire using the method above or send the unit a constant 10V DC or 20mA signal.

See Table 10 .

o Remove the cover on the modulating valve. Read the manifold gas pressure gauge (0-10 in. w.c.) located directly on the gas manifold. The pressure should read

3.5 in. w.c. for natural gas / 10 in. w.c.

for propane.

If the pressure is incorrect, adjust the pressure.

41

o To adjust the pressure, press button #1 until the LED lights solid red. Release the button. The valve is now in high fire setting mode. o Buttons #1 and #2 are used to set desired high fire setting. Press once to step or hold to auto step.

➢ Button #1 = increases flow

➢ Button #2 = decreases flow

To save the high fire setting, simultaneously hold buttons

#1 and #2 until the LED turns off.

4. If the proper ( in. w.c

.) gas pressure cannot be achieved by adjusting the modulating gas valve, and it has been verified that the inlet gas pressure is within the acceptable range of 7 in. - 14 in. w.c. on natural gas and 11 in. – 14 in. w.c. on propane gas , adjust the regulator on the On/Off gas control valve.

Figure 25 – Modulating Valve Electric

Controls

Low-Fire Burner Adjustment

1. Lock the unit into low fire mode. This is achieved by

configuring low fire by going into the HMI Configuration menu (page 24).

Service>test menu>test heating>run low fire test . See

Table 9

for an overview of proper pressure settings.

2. Press and hold button #2 on the modulating valve until the

LED light blinks red. Release the button. The valve is now in low fire setting mode.

3. Press button #1 to increase flow or press button #2 to decrease flow.

The desired pressure reading for natural gas is

0.15 in. w.c.

If this cannot be obtained, set the low fire pressure as low as possible.

The pressure reading for propane gas should be

0.75 in. w.c.

4. Save the low fire setting by simultaneously holding down buttons #1 and #2 until the blinking LED turns off. Press the abort button on the HMI to exit low fire mode.

Figure 26 – On/Off Gas Valve Regulator

42

Final Start-Up Procedure

1. With the air and burner systems in full operation and all ducts attached, measure the system airflow.

The motor sheave (pulley) is variable pitch, and allows for an increase or decrease of the fan RPM.

See below Pulley Adjustment section if airflow needs to be adjusted. Refer to Table 11

and

Table

13

for adjustment specifications.

2. Once the proper airflow is achieved, measure and record the fan speed with a reliable tachometer.

Caution - Excessive speed will result in motor overloading or bearing failure. Do not set fan

RPMs higher than specified in the maximum RPM chart. See the troubleshooting guide for more information.

3. Measure and record the voltage and amperage to the motor and compare with the motor nameplate to determine if the motor is operating under safe load condition.

4. Once the rpm of the ventilator has been properly set, disconnect power and recheck belt tension

and pulley alignment as shown in Pulley Alignment/Proper Belt Tension (page 44).

Table 11 – Maximum RPM and HP Chart

Belt Drive

Blower Size Maximum RPM Maximum HP

10” 1800 2

12”

15”

1500

1400

3

5

18”

20”

1200

1000

5

10

25” 900 20

Direct Drive

Blower Size Maximum RPM Maximum HP

15D 1800 2

20D

24D

30D

36D

16Z

1500

1400

1200

1000

2400

3

5

5

10

4

18Z

20Z

22Z

25Z

28Z

3200

2300

1900

1800

1400

5

5

5

8

7

Pulley Adjustment

The adjustable motor pulley is factory set for the RPM specified.

Speed can be increased by closing or decreased by opening the adjustable motor sheave. Two groove variable pitch pulleys must be adjusted an equal number of turns or closed. Any increase in speed represents a substantial increase in horsepower required by the unit. Motor amperage should always be checked to avoid serious damage to the motor when the speed is varied. Always

torque setscrews according to Table 12

torque specifications.

Figure 27 - Pulley Adjustment Illustration

Decrease Amperage and Blower RPM

Table 12 - Setscrew Torque

Thread Size Torque (IN/LB)

No. 10

1/4”

5/16”

3/8”

7/16”

1/2”

32

72

130

275

384

600

43

Pulley Alignment/Proper Belt Tension

Figure 28 – Alignment Reference

Figure 29 – Belt Tension

44

Pulley Combination Chart

3 to 5 HP

BX BELTS

BLOWER PULLEY

2BK160H

2BK140H

2BK120H

2BK110H

2BK100H

2BK90H

2BK80H

2BK70H

2BK60H

2BK55H

2BK50H

7-1/2 to 10 HP

BX BELTS

BLOWER PULLEY

2BK160H

2BK140H

2BK120H

2BK110H

2BK100H

2BK90H

2BK80H

3 to 5 HP

BX BELTS

Motor RPM

1/3 to 1-1/2 HP

AX BELTS

BLOWER PULLEY

AK114

1/3 to 2 HP

AX BELTS

BLOWER PULLEY

AK114

AK94

AK79

AK66

AK54

AK46

AK39

AK32

BLOWER PULLEY

2B5V278

2B5V250

2B5V234

2B5V200

2B5V184

2B5V160

2B5V154

2B5V136

2B5V124

2B5V110

7-1/2 to 10 HP

BX BELTS

BLOWER PULLEY

2B5V278

2B5V250

2B5V234

2B5V200

2B5V184

2B5V160

2B5V154

2B5V136

2B5V124

2B5V110

DATUM DIAMETER

11

DATUM DIAMETER

11

9

7.5

6.2

5

4.2

3.5

3

DATUM DIAMETER

15.4

13.4

11.4

10.4

9.4

8.4

7.4

6.4

5.4

4.9

4.4

DATUM DIAMETER

15.4

13.4

11.4

10.4

9.4

8.4

7.4

DATUM DIAMETER

27.8

25

23.4

20

18.4

16

15.4

12.6

12.4

11

DATUM DIAMETER

27.8

25

23.4

20

18.4

16

15.4

12.6

12.4

11

1725

MOTOR PULLEY

1VL34

PITCH DIAMETER

11.2

Dd1

1.9

Open

5

308

MOTOR PULLEY

1VL40

PITCH DIAMETER

11.2

9.2

7.7

6.4

5.2

4.4

3.7

3.2

Dd1

2.4

Open

5

400

488

582

701

863

1019

1212

1402

MOTOR PULLEY

2VP42

PITCH DIAMETER

15.7

13.7

11.7

10.7

9.7

8.7

7.7

6.7

5.7

5.2

4.7

Dd1

2.9

Open

6

330

378

442

484

534

595

672

772

908

995

1101

MOTOR PULLEY

2VP60

PITCH DIAMETER

15.7

13.7

11.7

10.7

9.7

8.7

7.7

Dd1

4.3

Open

6

516

592

693

758

836

932

1053

MOTOR PULLEY

2VP42

PITCH DIAMETER

28.1

25.3

23.7

20.3

18.7

16.3

15.7

12.9

12.7

11.3

Dd1

2.9

Open

6

184

205

218

255

277

317

330

401

407

458

MOTOR PULLEY

2VP60

PITCH DIAMETER

28.1

25.3

23.7

20.3

18.7

16.3

15.7

12.9

12.7

11.3

Dd1

4.3

Open

6

289

320

342

399

434

497

516

628

638

717

15 to 20 HP

BX BELTS

MOTOR PULLEY

2VP75

BLOWER PULLEY

2B5V278

2B5V250

2B5V234

2B5V200

DATUM DIAMETER

27.8

25

23.4

20

PITCH DIAMETER

28.1

25.3

23.7

20.3

2B5V184

2B5V160

2B5V154

2B5V136

18.4

16

15.4

12.6

18.7

16.3

15.7

12.9

** 2HP Motors on 20 IN Blowers use 2VP42 Pulleys

Dd1

5.8

Open

6

381

423

451

527

572

656

681

829

Table 13

5

538

617

722

790

871

972

1098

Pd1

3

Pd1

3

5

348

399

467

511

563

628

709

815

958

1050

1162

Pd1

4.7

Pd1

2

4

339

Pd1

2.6

4

431

525

627

755

929

1098

1305

1509

5

301

334

357

416

452

519

538

655

666

748

Pd1

6.2

5

393

436

466

544

590

677

703

856

5

194

216

230

269

292

335

348

423

430

483

Pd1

4.7

4 1/2

549

630

737

806

889

991

1120

Pd2

4

Pd2

4

4 1/2

357

409

479

524

578

644

728

837

984

1078

1193

Pd2

5.9

Pd2

3

3 1/2

354

Pd2

3.6

3 1/2

447

544

650

782

962

1137

1352

1563

4 1/2

307

341

364

425

461

529

549

669

679

763

Pd2

7.4

4 1/2

399

443

473

552

600

688

714

869

4 1/2

200

222

237

276

300

344

357

435

441

496

Pd2

5.9

TURNS ON MOTOR PULLEY

3

370

2 1/2

385

2

400

4

405

450

480

561

609

698

725

883

4

313

348

371

433

470

540

560

682

693

779

4

205

227

243

283

307

353

366

446

453

509

4

366

420

491

537

593

661

747

858

1009

1106

1223

4

560

642

752

822

907

1011

1143

TURNS ON MOTOR PULLEY

3 2 1/2 2

462 477 493

563

672

809

995

1176

1399

1617

581

694

836

1028

1215

1445

1671

600

717

863

1062

1255

1492

1725

1 1/2

416

TURNS ON MOTOR PULLEY

3 1/2 3 2 1/2

375

430

504

551

608

677

765

880

1034

1133

1254

385

441

516

564

622

694

784

901

1059

1161

1285

923

1084

1189

1315

394

451

528

578

637

710

803

TURNS ON MOTOR PULLEY

3 1/2 3 2 1/2

571

655

767

838

925

1031

1165

582

667

781

854

943

1051

1187

593

680

796

871

960

1071

1210

TURNS ON MOTOR PULLEY

3 1/2 3 2 1/2

210

233

249

290

315

362

375

457

464

522

215

239

255

297

323

370

385

468

475

534

394

479

487

547

220

244

261

304

331

379

TURNS ON MOTOR PULLEY

3 1/2 3 2 1/2

319

355

378

442

480

550

571

695

706

794

325

361

386

450

489

561

582

709

720

809

722

733

824

331

368

393

459

498

571

593

TURNS ON MOTOR PULLEY

3 1/2 3 2 1/2

411

457

488

569

618

709

736

896

417

464

495

578

627

720

747

909

424

470

502

586

636

730

758

923

1 1/2

508

619

739

889

1095

1294

1539

1779

5 1/2

527

604

708

774

854

952

1075

Dd2

3.9

Dd2

3.9

5 1/2

339

388

455

497

548

611

691

794

933

1023

1132

Dd2

5.5

Dd2

2.9

4 1/2

323

Dd2

3.4

4 1/2

416

506

605

728

896

1059

1259

1455

5 1/2

295

327

349

408

443

508

527

642

652

733

Dd2

7

5 1/2

387

430

459

535

581

667

692

842

5 1/2

189

210

224

262

284

326

339

412

419

471

Dd2

5.5

1

431

2

430

477

509

595

646

741

769

936

2

338

375

400

467

507

582

604

735

747

840

2

225

250

267

312

338

388

403

490

498

560

1/2

447

Closed

0

462

1

524

638

762

916

1128

1333

1585

1833

1/2

539

656

784

943

1161

1372

1632

1887

Closed

0

554

675

806

970

1194

1411

1678

1941

2

403

462

541

591

652

727

821

944

1110

1216

1346

1 1/2

412

472

553

605

667

744

840

965

1135

1244

1376

1

421

483

565

618

682

760

859

987

1160

1272

1407

2

604

693

811

887

978

1091

1232

1 1/2

615

705

826

903

996

1110

1255

1

626

718

840

919

1014

1130

1277

1 1/2

436

484

517

603

655

751

780

949

1 1/2

344

382

408

476

517

593

615

749

761

855

1 1/2

230

256

273

319

346

397

412

501

509

572

1

442

491

524

612

664

762

791

963

1

350

389

415

484

526

603

626

762

774

870

1

235

261

279

326

354

406

421

513

521

585

1/2

448

498

531

620

673

773

802

976

1/2

430

493

577

631

697

777

877

1008

1185

1299

1438

Closed

0

439

504

590

645

711

793

896

1030

1211

1327

1468

1/2

637

730

855

935

1031

1150

1299

Closed

0

648

743

870

951

1049

1170

1322

1/2

240

267

285

333

361

414

430

524

532

598

Closed

0

246

273

291

340

369

423

439

535

543

611

1/2

356

395

422

493

535

614

637

776

788

885

Closed

0

362

402

429

501

544

624

648

789

801

901

Closed

0

454

505

539

629

683

783

813

990

45

High Altitude Orifice Sizing

The burner orifices should be sized per the table below depending on fuel type, furnace size and altitude.

Standard orifice sizes are for sea level. The unit should either be ordered with the altitude specific orifices or the parts should be ordered through the manufacturer.

Table 14 – High Altitude

Natural Gas High ALT Conversion

High ALT for 400,000BTU

Altitude Input Rate Drill Size

High ALT for 300,000 to 75,000BTU

Input Rate Input Rate Input Rate Drill Size

0 - 1999ft

2000-2999ft

3000-3999ft

4000-4999ft

5000-5999ft

6000-6999ft

7000-7999ft

8000-8999ft

9000-10000ft

400000

384000

368640

353894

339739

326149

313103

300579

288556

#41

#42

2.35mm

2.3mm

#43

2.25mm

#44

#45

#46

300,000

288000

276480

265421

254804

244612

234827

225434

216417

200,000

192000

184320

176947

169869

163075

156552

150290

144278

150,000

144000

138240

132710

127402

122306

117414

112717

108209

#3/32

2.35mm

2.3mm

#43

2.25mm

#44

2.15mm

#46

#47

Size

#41

#42

2.35mm

2.3mm

#43

2.25mm

#44

#45

#46

#47

#3/32

2.15mm

1.45mm

#54

#55

#56

#57

High ALT for 400,000BTU

LP Gas High ALT Conversion

High ALT for 300,000 to 75,000BTU

Altitude

0 - 1999ft

2000-2999ft

3000-3999ft

4000-4999ft

5000-5999ft

6000-6999ft

7000-7999ft

8000-8999ft

9000-10000ft

Input Rate

400000

384000

368640

353894

339739

326149

313103

300579

288556

Drill Size

1.45mm

#54

#54

#54

#54

#55

#55

#55

#56

Input Rate

300,000

288000

276480

265421

254804

244612

234827

225434

Input Rate

200,000

192000

184320

176947

169869

163075

156552

150290

Input Rate

150,000

144000

138240

132710

127402

122306

117414

112717

Drill Size

#54

#54

#55

#55

#55

#55

#56

#56

#57

Orifice Part Numbers

Part#

BG100-41

AX#

A0023045

BG100-42

BG101-19

BG101-05

A0023050

A0023053

A0023051

BG100-43

BG101-20

BG100-44

BG100-45

BG100-46

BG100-47

BG100-3/32

BG101-21

A0023047

A0023054

A0023046

A0028800

A0028801

A0028802

A0023044

A0023055

BG101-16

BG100-54

BG100-55

BG100-56

BG100-57

A0023052

A0023048

A0023049

A0023057

A0028803

216417 144278 108209

Orifice Qty. Per Furnace

Size

150,000 BTU

200,000 BTU

300,000 BTU

400,000 BTU

Qty

6

8

12

15

46

Sequence of Operation (Summary)

▪ Main Blower is turned “On” and the Main Airflow Switch is proven.

▪ Air temperature at the intake of the unit falls below the setting of the Intake Air Set-point initiating a “Call for Heat” to the IBT Board.

▪ FSC-1 sends 24V AC power back to the IBT Board.

▪ IBT BOARD sends a 120V AC signal to Power-vent Blower Motor to initiate 1 min pre-purge at high speed.

▪ 24V AC signal runs through the safety circuit (Power-vent Airflow Switch/High Temperature Limit/Flame

Roll-out Switch) and into FSC-1.

▪ FSC-1 initiates Trial for Ignition by sending signal to Spark Igniter to light furnace and 24V AC power to On/Off Gas Valve and signal to IBT BOARD that it is sparking. This opens On/Off Gas Valve and triggers the start of the 17 seconds of 10V DC from the IBT BOARD to the modulating valve(s) and

120V AC output to the Power-vent Blower Speed Controller(s).

▪ Flame is sensed by FSC1’s Remote Flame Sensor at the upper-most firing tube of furnace.

▪ IBT BOARD’s 17 second high-fire sequence runs out and 0-10V DC modulating signal from IBT BOARD is output to Modulating Gas Valve and modulates the Power-vent Blower Speed Controller along with the modulating gas valves to maintain efficiency.

▪ IBT BOARD continues to modulate the heat output of MAU by adjusting the 0-10V DC signal to

Modulating Gas Valve and turning other modulating furnaces or On/Off Staged Furnaces on and off as required to satisfy the Temperature Selector Dial setting.

Note: If two modulating furnaces are present this sequence occurs with FSC-2 and a second speed controller if the call for heat dictates a need for a second furnace.

Sequence of Operation (Detailed)

The Indirect-fired heater is most easily understood when broken down into smaller individual systems.

There are two main systems; a make-up air fan and a heater. The make-up air fan consists of a heavy-duty blower and motor. The heater may be further broken down into two control systems, the Modulating Gas

System (MGS) and the Flame Safety Control (FSC). The burner mixes air with the gas (Natural or Propane) which burns into a heat exchanger which heats the air. There are between one and four furnaces in each heater depending on the total required heating output capacity for the application. Included in every unit is at least one modulating furnace, located furthest downstream, closest to the discharge of the heating module. The modulating furnace(s) and additional On/Off furnaces (if used) are controlled using verniertype modulation methods resulting in fully linear heating output over the entire gas-firing range.

47

Modulating Gas System

The first system, the Modulating Gas System, consists of an Intake Air Sensor, a Vernier Auto Balancing

Module (IBT Board), a Discharge Air Sensor, a Space Air Sensor (only on space temp control option), and a modulating gas valve(s). The Intake Air Sensor, the space sensor, or a combination of the two can be used to give a call for heat signal to the IBT board. Using a PID loop, the IBT board looks at the difference between the temp sensor readings in order to appropriately modulate the heat. For Kitchen MUA heating applications, Intake Air setpoint should be set at 45°F, whereas the discharge setpoint should be set at

55°F. For all other applications, the setpoint should be set appropriately based on the end-users preferences and on-site conditions.

There are 4 different options for controlling the gas firing output of these units. These include Discharge

Temperature Control, Space Temperature Control, and Building Automation Control, and DDC. Refer to

HMI Menu Description (page 25)

to see where the menu items are located to configure for each type of control:

1. Discharge Control: When used in discharge control, the IBT board receives a call to heat from the intake sensor, the IBT board will modulate the discharge temperature until it hits the desired set point. The user can choose whether discharge heating/cooling is activated based on intake temperature, space temperature, either, or both.

2. Space Control: When the space control option has been selected, there will be an HMI that contains an internal temperature sensor. The user can choose whether the space heating/cooling is activated based on intake temperature, space temperature, either, or both.

3. Analog Control/Direct Digital Control (DDC) :

A 0-10V DC or 0-20mA signal is sent to the IBT board from the building control system to regulate the heating output of the unit. Refer to Appendix B for BACNET/LONWORK DDC points. If Analog

Control is utilized, dipswitch 4 on the IBT board should be set to up (main and slave if 2 IBT boards are present).

In all cases, the IBT board controls the amount of gas to the burner based on the signal from the temperature control components. When the modulating gas valve is all the way open and achieving the maximum BTUs and temperature rise of the unit, it is called “high fire”.

Figure 30 - Temp Sensor

48

Flame Safety Control

The second system to understand is the Flame Safety Control . The FSC is present only to monitor the flame, NOT to control temperature. The FSC uses a sensor mounted at the intake of the upper-most firing tube of the furnace to sense the existence of a flame. The FSC controls the opening of the redundant solenoid gas valves and the operation of the spark igniter to initiate a flame upon start up. When there is a call for heat, the LED on the FSC is energized indicating that the unit has power. Then, there is a one minute prepurge in which the power-vent blower on the furnace runs at full speed to

Figure 31 - Flame Safety

Controller exhaust any gas in the Heat-exchanger/Control Cabinet that may be present prior to trial for ignition. As soon as the pre-purge has initiated, the FSC checks that airflow is sensed by the power-vent airflow switch* and that the

High Limit and Roll-out switches are not tripped.

*NOTE: If, while trouble-shooting the unit, it is necessary to jumper-out this airflow switch, the jumpers must be applied to the contacts immediately after the power-vent motor is turned on and the FSC begins to check for airflow, otherwise the unit will go into lock-out mode.

Upon successful sensing of induced power-vent airflow and continuity of temperature limit and roll-out switches, the FSC initiates a 15 second ignition sequence. During this ignition sequence, the FSC opens the On/Off gas valves and allows gas to pass through to the gas manifold. At the same moment, the spark igniter begins to spark, causing the electrode on the burner to ignite the gas. This results in a flame at the lowest firing tube of the furnace which immediately ignites the flow of gas in each succeeding firing tube moving vertically until the entire furnace is lit. When the sensor detects the flame at the intake of the uppermost firing tube the FSC continues to power the On/Off gas valve until there is a loss of flame presence.

This is the normal operating mode.

Figure 32 – Ignition Sequence

Modulating Stage Sequence

As mentioned in the previous sections, every unit is equipped with a modulating furnace(s) located furthest downstream at the discharge of the heater module. The modulating stage(s) operates differently than the other On/Off staged furnaces in that instea d of being “On” or “Off”, the gas flow to this furnace is modulated up and down to account for varying calls for heat during the unit ’s operating period. In addition, the speed of its power-vent blower is varied as the gas flow changes in order to maintain constant combustion efficiency over the entire firing range.

Modulating furnace power-vent blower(s) are controlled by an onboard speed controller on the IBT that varies the output voltage to the motor. There is one Speed Controller per modulating furnace. (Two speed controllers per board.) The Output voltage (True RMS) to the motor varies non-linearly between 120V AC

@ 10V DC for high fire and 81.6V AC @ 0V DC for low fire.

49

IBT BOARD and High Fire Start

The IBT BOARD translates a difference between two sensor values and the set point or a 0-10V DC or

0-20 mA signal from an Analog Control to the modulating furnace(s). The signal is linearized such that input voltage is directly proportional to amount of gas being delivered to the modulating valve(s). If that signal is greater than a high voltage threshold for a certain interval it will relay 24V to the FSC on the next furnace. This will repeat if the heat capacity is still not enough and more stages will be turned on. If the call for heat is lower than a low voltage threshold for a certain period of time the IBT BOARD will cut power to the last stage that turned on, starting the post purge sequence and repeat the process for subsequent stages if needed. On furnaces that have two modulating burners the linearized signal is sent to one of these burners depending on the need for heat while the furnace not receiving the modulating signal is locked in to high fire, low fire or off.

In order to ensure proper light-off in all conditions, every unit’s IBT BOARD contains software that forces the modulating furnace(s) to light at high fire when that furnace’s main gas valve is first opened. There is a built in timer that allows it to send a constant 10V DC signal to the modulating gas valve(s) and powervent blower speed controller(s) and force the furnace(s) into high fire for a period of 17 seconds after the initial spark is sent by the FSC. After this forced high-fire light-off period has expired, the modulating furna ce’s power-vent blower and modulating gas valve will receive a modulating signal from the IBT BOARD as mentioned above.

NOTE: For in-depth board information, see

Appendix A (page 72)

Re-Circulating Control Options

Manual Positioning Control

The dampers can be controlled from the HMI in the unit or from a space HMI if one is provided to any position from 0% to 100% fresh air. This is a 0-10V setting, which is available under user settings, 100%

Outdoor Air (0 volts), 100% Return Air (10 volts). This will allow manually setting the dampers to match the building ventilation requirements. On a power failure the return air damper will close by spring return.

Two Position Control

The dampers can be controlled by a two position switch (a field supplied switching device) to open the fresh air to 100%. The IBT board sends out a constant voltage. The field supplied switch will cut or allow the signal from the IBT board to the mixing box damper. On opening of the circuit, power failure, or if the unit is shutoff, the return air damper will close by spring return. If the circuit is closed, the IBT board will allow the return air damper to open per the set point.

Outdoor Air %

The dampers can be controlled from the HMI in the unit or from a space HMI if one is provided to any position from 0% to 100% fresh air. There is an outdoor air percentage setting which is available under user settings. This will allow the user to manually set the dampers to match the building ventilation requirements. The IBT board utilizes an internal algorithm to alter its 0-10V output to the mixing box damper in order to maintain an exact outdoor air percentage. When this mixing box option is selected, a mixing box deadband comes into play. This setting checks the delta T between outdoor and return air. If the difference between these two temperatures is less than or equal to the mixing box deadband setting, the IBT board will not alter its output to the mixing box damper (default setting is 5 degrees). On a power failure, or if the unit is turned off, the return air damper will close by spring return.

50

Static Pressure Control (Photohelic)

The dampers can be controlled by a building static pressure control. This controller will sense the difference between pressure inside the building, and pressure outside the building (sensed at the A306 outdoor sensor), and position the dampers to maintain the pressure setting on the controller. The controller has two set points and an indicator. The two set points are a minimum desired static pressure point, and a maximum static pressure point.

The actual building static pressure will be shown by a visual indicator between these two settings. The controller will modulate the dampers to maintain a static pressure between these set points.

When building static pressure is below the minimum setting, the damper motor will proportionally open the fresh air damper and close the return air damper until static increases above the minimum setting.

At this point, the damper motor will stop and hold this proportion.

If the building static continues to climb and goes above maximum setting, the damper motor will reverse proportion, closing the fresh air damper and opening the return air damper until static drops below maximum setting.

During the “OFF” or “Night” cycle of the unit, an internal switching circuit will close the return air damper.

See additional wiring and installation information on the static pressure controller and A306 outdoor sensor.

Figure 33 – Photohelic Gauge

Static Pressure Controller Installation Instructions

Avoid locating the front of the static pressure controller in sunlight or other areas with high ambient light or corrosive levels. Bright light shining on the photocells can cause false actuation of the load relays.

The static pressure controller should be zeroed out before attaching the low and high pressure hoses.

The zero adjustment is located between the minimum and maximum dials.

Use the supplied rubber tubing the high side of the static pressure controller should be plumbed to the inside of the building. The low side of the static pressure controller should be plumbed to the A306 outdoor sensor. See the A306 installation instructions.

Figure 34 – Static Pressure Controller

51

A306 Outdoor Sensor

The A306 senor is used in conjunction with the photohelic. Use the installation instructions shipped with the A306 outdoor sensor.

Figure 35 – Exploded View

Figure 36 – Outdoor Sensor Installed

Building Signal Damper Control

When this option is ordered, the supply and return dampers will modulate based on a 0-10V DC signal from the Building automation system.

Schedule Control

When this option is ordered, the supply and return damper will change based on the schedule. There are separate occupied and unoccupied outdoor air percentage settings located under user settings. The unit will maintain the appropriate outdoor air percentage based on the schedule state. When this mixing box option is selected, a mixing box deadband comes into play. This setting checks the delta T between outdoor and return air. If the difference between these two temperatures is less than or equal to the mixing box deadband setting, the IBT board will not alter its output to the mixing box damper (default setting is 5 degrees).

52

Network

For DDC descriptions, see Appendix B – IBT DDC Points (page

76)

NOTE: The board will reboot when altering factory settings.

BACNET

BACNET IP or BACNET MS/TP compatibility can be implemented with this package through a Protocessor, which is a BTL listed embedded Gateway configured to give a Building Management

System (BMS) access to monitor and/or control a list of BACNET objects. The Protocessor is mounted and factory pre-wired inside the Electrical Control Panel. Field connections to the Building

Management System are shown to the right.

The Protocessor is pre-configured at the factory to use the field protocol of the Building Management System in the specific jobsite.

BACNET objects can only be accessed through the specified port and protocol.

1. Field Ethernet Connection for BACNET IP

2. Field RS485 Connection for BACNET MS/TP

Figure 37 - BACNET Wiring Reference

Figure 38 - BACNET

Connections

53

Changing Device Instance, MAC Address, Baud Rate

Some applications may require that the Protocessor have a specific Device Instance, the default device instance is 50,000. To change the Device Instance, you must access the Web Configurator by connecting a computer to the Ethernet port of the Protocessor. The computer used must be assigned a static IP address of 192.168.1.xxx and a subnet mask of 255.255.255.0.

To access the Web Configurator, type the IP address of the Protocessor in the URL of any web browser.

The default IP address of the Protocessor is 192.168.1.24. Once the landing page has loaded, if required, log in using “admin” for the username and password. If the default “admin” password does not work, the gateway should have a printed password on the module’s Ethernet port.

Go to the main configuration page, select “Configure” from the left-hand menu. Select “Profile

Configuration

,” the window shown in Figure 39

should appear.

The MAC address and Baud Rate, used by BACNET MTSP, are editable. The MAC address default is

127, and the Baud Rate default is 38400.

Figure 39 - Configuration Parameters Page

If any changes are made, click on the submit button for each individual change.

Each individual change will require the system to restart.

54

Changing the IP Address

Some BACNET IP applications may require changing the IP address of the Protocessor. In order to change the IP address, go to the internal server by typing the default IP address of the Protocessor,

192.168.1.24, in the URL field of any web browser. The computer used must have a static IP address of

192.168.1.xxx. The window shown in Figure 40

appears. Click on the “Diagnostics and Debugging” button on the lower right corner.

Click on “Setup” from the left hand side menu and select “Network Settings.” The window shown in

Figure 40

will appear. You can now modify the IP address to whatever is required in the application.

Once the IP address has been modified, click on “Update IP Settings.”

Figure 40 - Network Settings Page

After you have updated the IP settings, you will be prompted to restart the system. You can do so by clicking on the “System Restart” button at the bottom of the screen. Any time after this, you will have to type the new IP address of the Protocessor on the URL to gain access to the Web Configurator.

55

LonWorks

LonWorks compatibility can be implemented on control packages through the ProtoNode, a LonMark certified external Gateway configured to give a Building Management System access to monitor and/or control a list of Network Variables. The ProtoNode is mounted and factory pre-wired inside the Electrical

Control Panel. Field connections to the Building Management System is shown.

Figure 41 – LonWorks Adapter and Wiring Reference

Commissioning on a LonWorks Network

During the commissioning process by the LonWorks administrator (using a LonWorks

Network Management Tool), the user will be prompted to hit the Service Pin in the

ProtoNode. This pin is located in the front face, and it can be pressed by inserting a small screwdriver and tilting it towar ds the LonWorks Port. The location of the “Service

Pin” is shown in Figure 42 .

Figure 42 - Service Pin Location

NOTE: Insert Small Screwdriver. Tilt Toward LonWorks Port To Activate Service

Pin.

If an XIF file is required, it can be obtained by following these steps:

1. Set your computer’s static IP address to 192.168.1.xxx with a subnet mask of

255.255.255.0.

2.

Run a Cat 5 connection from the ProtoNode’s Ethernet port to your computer.

3. On any web browser’s URL field, type 192.168.1.24/fserver.xif

The web browser should automatically download the fserver.xif file or let you save it on your computer. Save it as fserver.xif.

56

SERVICE INFORMATION

Troubleshooting Flow-charts

57

Fault Codes

The following tables list causes and corrective actions for possible problems with indirect heater units.

Review these lists prior to consulting technical support.

Fire

Smoke

Fault

Gas PS High

Gas PS Low

Description

There is an input from the fire detector.

There is an input from the smoke detector.

The board is receiving an input on the gas pressure high terminal.

The board lost input on the

Gas Pressure Low terminal. There should be an input when gas

Possible checks

Check for short circuits in the wire.

Replace fire detector.

Verify the smoke detector is set up properly.

Check for short circuits in the wire.

Replace smoke detector.

Adjust regulator or add regulator.

Repair faulty wiring.

Replace switch.

See High Gas Pressure switch (page 65).

Low Gas pressure switch.

Repair broken or loose wiring connections.

Replace switch.

See Low Gas Pressure switch (page 65).

Exhaust Overload pressure is at the proper level.

Motor overload has tripped.

Supply Overload

Sensor missing

(Return, Outside,

Intake, Discharge)

Sensor broken

(Return, Outside,

Intake, Discharge)

Motor overload has tripped.

Temperature sensor is not connected

Temperature sensor is defective

Check motor for debris or bad bearings.

Check motor wiring connections.

Check overload reset button.

Check wiring to the contactor.

Check overload amperage setting.

Check motor for debris or bad bearings.

Check motor wiring connections.

Check overload reset button.

Check wiring to the contactor.

Check overload amperage setting.

Install, and wire sensor.

Check for faulty wiring.

See temperature sensor (page 64).

Check for faulty wiring.

See temperature sensor (page 64).

HMI Temp Sensor The HMI contains an internal temperature sensor.

RTC 1 Temp Sensor Real Time Clock (RTC) temperature sensor located on IBT board.

Verify there is no damage to the HMI, or wiring to HMI.

If space temperature is being utilized, make sure

HMI Averaging is set to ON for all space HMIs.

Refer to HMI Menu Tree (page 30) Factory

Settings – Unit Options.

Verify there is no damage to the IBT board.

Check wiring to the IBT board.

58

Fault

No supply air proving

(Air flow switch)

FSC1 High Temp

FSC1 Rollout

FSC Vent Proving

Freezestat lockout

Firestat lockout

DX Float detect

Modbus system communication

Master ROM CRC

Clogged filters

Check FPDK

Signal was not received from air switch when supply blower was running.

Description

The Flame Sensor Controller (FSC) continually and safely monitors, analyze, and controls the proper operation of the gas burner and inducer motor.

If flame-rollout is present, the switch de-energizes heater circuit on individual furnace. Must be manually reset by pressing small button on the switch. 325°F setpoint.

The FSC verifies that airflow is sensed by the induced draft air sensor.

The discharge temperature was too low for a long period of time.

Intake or discharge temperatures exceeded the firestat set point.

Input signal from the drain pan float switch

Software mismatch

Possible checks

Make sure the blower runs.

Check air switch wiring.

Check blower rotation.

Check damper operation.

See Air Flow Switch (page 63).

Check connector J7 on the IBT board. Make sure the connection is secure.

High limit switch failed open. There should be continuity.

Check wiring to the switches

Reset the switch.

Rollout switch failed open. There should be continuity.

Check for a blocked tube, low airflow, or low gas pressure.

Kinked/blocked/damaged hose.

Poor venting.

Blockage in vent system.

Clogged condensation drain.

Power vent motor.

Failed switch.

See Vent Proving switch (page 64).

Check gas pressure.

Check for proper burner firing.

Use the HMI to reset.

Use the HMI to reset.

Check for faulty regulators.

Check for faulty modulating valves.

Make sure the pan drain is clear and water is draining.

Check for shorted wires.

Replace float switch.

Contact technical support.

Software mismatch

Input from filter airflow switch.

Freeze Protection Drain Kit is not operating correctly.

HMI “x” Revision Wrong Software mismatch

HMI Config Error HMI is not connected, or HMI is assigned incorrectly

Contact technical support.

Clean or replace filters.

See Clogged Filter Switch (page 63).

Improper installation.

Not Installed.

Contact technical support to flash the appropriate software.

Install HMI or change HMI address using bottom 2 buttons on HMI. See

HMI Options Screen (page 25)

59

Airflow Troubleshooting Chart

Problem

Fan Inoperative

Motor Overload

Insufficient Airflow

Potential Cause

Blown fuse

Open circuit breaker

Corrective Action

Check amperage .

Check fuse, replace if needed

Check circuit breaker .

.

Disconnect switch in “Off” position Turn to “On” position .

Motor wired incorrectly

Check motor wiring. Verify connections with wiring diagram located on fan motor .

Broken fan belt

Motor starter overloaded

HMI set to “Blower Off”

Fan rotating in the wrong direction

Replace belt .

Check amperage .

Reset starter .

Set HMI to “Blower On” .

Verify the fan is rotating in the direction shown on rotation label.

Fan speed is too high

Motor wired incorrectly

Overload in starter set too low

Motor HP too low

Reduce fan RPM.

Check motor wiring. Verify connections with wiring diagram located on fan motor.

Set overload to motor FLA value.

Determine if HP is sufficient for job.

Duct static pressure lower than design

Reduce fan RPM.

Fan rotating in the wrong direction

Poor outlet conditions

Intake damper not fully open

Duct static pressure higher than design

Blower speed too low

Supply grills or registers closed

Dirty/clogged filters

Verify the fan is rotating in the direction shown on rotation label.

There should be a straight clear duct at the outlet.

Inspect damper linkage. If the linkage is damaged, replace damper motor.

Improve ductwork to eliminate or reduce duct losses.

Increase fan RPM. Do not overload motor.

Open and adjust.

Clean filters. Replace filters if they cannot be cleaned or are damaged.

Adjust belt tension.

Reduce fan RPM.

Install filters.

Excessive Airflow design

Excessive Vibration and Noise Misaligned pulleys

Damaged/unbalanced wheel

Fan is operating in the unstable region of the fan curve

Bearings need lubrication

Damaged bearing

Fan speed is too high

Dirty/oily belt

Belts too loose

Worn belt

Belt slippage

Blower speed too high

Filters not installed

Duct static pressure lower than

Reduce fan RPM.

Align pulleys.

Replace wheel.

Refer to performance curve for fan.

Lubricate bearings.

Replace bearings if damaged.

Reduce fan RPM.

Clean belts.

Inspect and replace if needed.

60

Furnace Troubleshooting Chart

Problem

Furnace Does

Not Light/Stay

Lit

Not Enough

Heat

Potential Cause

Main gas is off

Air in gas line

Corrective Action

Open main gas valve.

Purge gas line.

Dirt in burner orifices

Gas pressure out of range

ON/OFF gas valve is off

Spark Igniter Rod out of position

Excessive drafts

Safety device has cut power

Clean orifices with compressed air.

Adjust to proper gas pressure.

Turn ON/OFF gas valve on.

Relocate Spark Igniter Rod to proper area.

Re-direct draft away from unit.

Check limits.

Check Air Flow Switch (page 63)

.

Dirty flame sensor

Thermostat not calling for heat

No spark at igniter

Defective valve

Clean flame sensor.

Change heating set-points to call for heat.

See Flame Safety Control check (page 66).

See Gas valve / Modulating gas valve check (page

67).

Loose valve wiring

Defective flame sensor

Shut off valve closed

See Gas valve / Modulating gas valve check (page

67).

Replace flame sensor.

Open shut off valve.

Defective Flame Safety Controller

See Flame Safety Control check (page 66).

Increase airflow through furnace.

Unit cycling on high limit

Main gas pressure too low

Unit locked into low fire

Check gas pressure.

Increase main gas pressure

– do not exceed

14 in. w.c

. inlet pressure.

Check wiring.

Check Modulating Valve settings.

See High-Fire and Low-Fire Burner Adjustment

Too much airflow

Furnace undersized

Gas controls not wired properly

Thermostat setting too low

(page 41)

Decrease airflow if possible.

Check design conditions.

See Gas valve / Modulating gas valve check (page

67).

Increase thermostat setting.

Thermostat malfunction

Too Much Heat Defective modulating gas valve

Thermostat setting too high

Lifting Flames or Flashback

Yellow Tipping

Flames

Floating Flames or Flame Rollout

Unit locked into high fire

Thermostat wired incorrectly

Too much primary air

Manifold pressure set too high

Dirty orifice

Orifice too large

Insufficient primary air

Misaligned orifice

Insufficient primary air

Orifice too large

Manifold Pressure too high

Blocked Vent

Misaligned orifice

Check thermostat.

Check/replace modulating valve.

Decrease thermostat setting.

Check Modulation Valve Settings, see Table 10

See High-Fire and Low-Fire Burner Adjustment

.

(page 41).

Check thermostat wiring.

Reduce primary air.

Reduce manifold pressure.

Check and clean orifice.

Check orifice size.

Increase primary air.

Check manifold alignment.

Increase primary air.

Check orifice size.

Decrease Manifold Pressure.

Check Venting System.

Check manifold alignment.

61

VFD Fault List

Fault Number

0

1

2

3

4

5

6

7

8

13

14

15

16

9

10

11

12

No Fault

Description

IGBT Temperature Fault

Output Fault

Ground Fault

Temperature Fault

Flying Start Fault

High DC BUS

Low DC BUS

Overload Fault

OEM Fault

Illegal Setup Fault

Dynamic Brake Fault

Phase Lost

External Fault

Control Fault

Start Fault

Incompatible Parameter Set

17

18-27

28

29

EPM Hardware Fault

Internal Fault

Remote Keypad Lost

Assertion Level Fault

30 - 33

34

Internal Fault

Comm. Module Failure

35 - 44 Network Fault

Refer to VFD manufacturer manual for further details.

62

Component Testing

Air flow switch (PS-09)

1. Verify the vent tube is connected to the high side port for standard supply fans. When the supply fan starts, the positive pressure will close the switch and allow the supply fan to run. A fault will occur if the switch does not close.

2. If the “No Supply Air Proving” fault is active: o Check the rotation of the supply fan. o Verify the electrical connections are secure and tight. Verify vent tube is not pinched or damaged. o When the unit is powered ON and the supply fan is running, there should be 24V AC at connector J13 pin 6 and J13 pin

13. If the voltage reading is incorrect at J13 pin 13, check the adjustment of the switch.

Air Flow Switch Field Adjustment

Figure 43 - Air Flow Switch and Wiring Reference

Follow these steps if performing a part replacement, or to calibrate the switch.

Install the switch. Install the vent tube to the correct port. Install the electrical connections.

Power the unit ON. Monitor the HMI screen.

Turn the adjustment screw until a fault appears on the screen, then turn the screw until the fault becomes inactive. Turn the screw two more full turns counterclockwise.

Clogged filter switch (PS-10)

1. The vent tube should be connected to the low side port. A fault will occur when the switch senses a negative pressure.

2. If the “Clogged Filters” fault is active: o Check the filters. If the filters are clogged or damaged, replace as needed. Check for any other obstructions in the unit. o Verify the electrical connections are secure and tight. Verify vent tube is not pinched or damaged. o When the unit is powered ON, there should be 24V AC at connector J13 pin 5 and 0V AC J13 pin 12. If there is voltage at pin 12, check the adjustment of the switch.

Clogged Filter Switch Field Adjustment

Figure 44 - Clogged Filter

Switch and Wiring Reference

Follow these steps if performing a part replacement, or to calibrate the switch.

1. Install the switch. Install the vent tube on the low side port. Install the electrical connections.

2. Use material suitable to block the filter. This will create a clogged filter symptom.

3. Power the unit ON. The switch should now be closed, and the ‘Clogged Filters’ fault should be active. Check for voltage at the following pins:

▪ Common pin to ground. There should be 24-28V AC .

▪ Normally open pin to ground. There should be 24-28V AC .

A. If the voltage reading is correct, remove the material blocking the filter. The fault should clear.

If the fault is present, adjust the switch until set properly.

B. If the voltage reading is incorrect, adjust the switch until the proper voltage is obtained at the pins. Block the filter, and monitor that the switch closes (clogged). Unblock the filter, and monitor that the switch opens (unclogged).

63

Intake (SN-03)/Return (SN-04)/Outdoor (SN-05)/Discharge (SN-06) Temperature sensor

1. Make sure the unit is OFF.

2. Make sure the wires are connected properly.

3. Measure the resistance of the temperature sensor

Figure 45 – Wiring Reference

Table 15 - Sensor

Ohm Reading at the IBT board connector J15.

SN-03 – pin 1 to pin 2

SN-04 – pin 3 to pin 4

SN-05 – pin 5 to pin 6

SN-06 – pin 7 to pin 8

Use the temperature/ohm chart to determine your readings.

A. If there is 0 ohms the sensor or wires are shorted.

B. If there is infinite (OL) ohms the sensor or wires are open.

If the sensor or wiring has failed, replace the sensor.

Vent Proving switch (PS-01)

1. Make sure the wiring is connected properly.

2. Verify the vent tubing is routed correctly, and the tube is not pinched or clogged.

3. Make sure the unit is OFF. Check the switch. Remove the electrical connections. Check for continuity between pins:

• Pin “C” to pin “NO”. There should be no continuity.

▪ If there is continuity, the switch has failed. Replace the switch.

▪ If there is no continuity, re-connect the electrical connections. Continue to the next step.

4. Connect a manometer between the pressure switch, and hose. Power the unit ON, and monitor the manometer. Verify the value ( w.c.

) on the switch is correct.

▪ If the reading is below the set point, there is an issue with the vacuum.

▪ If the reading is above the set point, continue to the next step.

5. With the unit ON. Check for voltage:

Back probe connector J7-pin 14 to ground. There should be 24-28V AC .

Back probe connector J7-pin 10 to ground. There should be 24-28V AC .

▪ If the voltage reading is incorrect, check the wiring for an open or short circuit. If the wiring check is good, the switch has failed. Replace the switch.

▪ If the voltage reading is correct, there may have been an intermittent fault.

Figure 46 - Vent Proving Switch and Wiring Reference

64

Low Gas Pressure switch (PS-05)

1. Power the unit ON. Verify the inlet pressure gauge is reading the correct pressure.

Natural gas - 7 in. w.c. – 14 in. w.c

.

Propane - 11 in. w.c. – 14 in. w.c.

Note: If the reading is incorrect, contact the gas supply company .

2. Reset the lever on the switch. Gas pressure must be higher in the chamber for the reset latch to be set properly.

▪ If the reset did not work, continue with the next step.

3. Remove the cover. Make sure the wiring is set up for Normally Open (N.O.) contact.

4. Check for voltage:

Back probe connector J13-pin 3 to ground. There should be 24-28V AC .

Back probe connector J13-pin 10 to ground. There should be 0V AC .

A. If the voltage reading is incorrect, check the wiring for an open or short circuit. If the wiring is correct, the switch has failed. Replace the switch

B. If the voltage reading is correct, and the switch reset corrected the fault, there may have been an intermittent fault.

Figure 47 - Low Gas Pressure and Wiring Reference

C

NO

High Gas Pressure switch (PS-07) (PS-08)

NC

1. Power the unit ON. Reset the lever on the switch. Gas pressure must be lower in the chamber for the reset latch to be set properly.

2. Remove the cover. Make sure the wiring is set up for Normally Closed (N.C.) contact.

3. Verify the On/Off gas valve, and modulating valve are set properly. See High-Fire and Low-Fire

Burner Adjustment (page 41)

4. Check for voltage:

Back probe connector J13-pin 3 to ground. There should be 24-28V AC .

Back probe connector J13-pin 10 to ground. There should be 24-28V AC .

A. If the voltage reading is incorrect, check the wiring for an open or short circuit. If the wiring is correct, the switch has failed. Replace the switch

B. If the voltage reading is correct, and the switch reset corrected the fault, there may have been an intermittent fault.

Figure 48 - High Gas Pressure and Wiring Reference

C

NO

NC

65

Flame Safety Control (FSC-01)

1. Make sure the wiring is connected properly.

2. Power the unit ON. Use the HMI to set the unit in test mode.

Service > Test Menu > Test Heating > Run Low Fire Test > Stages All

Refer to the operation of sequence, Flame Safety Control (page 49).

Determine the symptom below

:

Symptom

Control does not start

Thermostat ON – no spark

Action

-Check wiring

-Check for a 24V AC transformer failure

-Check circuit breaker

-Check LED light

-Check wiring to thermostat input (TH)

-Faulty thermostat

-Check LED light

-Check wiring

-Check for flame fault

Blower ON – no Trial For

Ignition (TFI) after purge delay

Valve ON

TFI

– no spark during

-Air Flow fault, see Air Flow Switch (page 63).

-Check connection at PSW terminal

-Faulty Control (Check voltage between L1 and IND. There should be

24V AC )

-Check wiring

-Shorted ignitor electrode

-Check cable to ignitor

Spark ON – valve OFF -Check wiring

-Valve coil open

-Check voltage at V1

-Check flame rod position Flame during TFI – no flame sensed after TFI -Check cable to flame rod

-Poor ground connection at burner

-Poor flame

3. Power the unit ON. If the LED is blinking, verify the fault:

Steady ON = Internal controller failure

1 flash = Airflow fault

2 flashes = Flame without call for heat

3 flashes = Ignition lock out

66

Modulating Gas Valve (VA-05) (VA-06)

1. Make sure the wiring is connected properly. Check the wiring using a multi-meter for open or short circuits.

Terminal 1 – Signal ( + ) to J7-pin 6/J8-pin 6

Terminal 2 – Signal ( ) to J7-pin 7/J8-pin 7

Terminal 3 – Power 24V DC ( + ) to H

Terminal 4 – Power ( ) to N

A. If any damaged wiring is found, repair or replace.

B. If any open or short circuits are found, repair or replace.

C. If any wiring is connected incorrectly, correct the wiring.

Note: The wiring connection is polarity sensitive.

1. Make sure the DIP switches are all in the OFF position (factory setting). This will set the valve to receive a 0-10V DC

signal. If the unit is set up for an analog control system, see Table 10 .

2. Make sure the valve has been adjusted properly. See High-fire and Low-fire burner adjustment

(page

41).

3. If the unit has been running, restart the unit. Check for voltage:

Connector J7-pin 6/J8-pin 6 to ground. There should be 10V DC . The voltage reading will drop after the unit has been running.

Check for voltage between H to N on the terminal block. There should be 24-28V AC . This voltage reading will be constant.

A. If the voltage reading is incorrect, check voltage to the IBT control board.

B. If the voltage reading is correct, there may be an issue with the modulating valve.

Figure 49 - Modulating Gas Valve and Wiring Reference

Main (ON/OFF) Gas Valve (VA-01)

1. Make sure the wiring is connected properly.

2. Make sure the gas valve is ON.

3. Power the unit ON. Check for voltage. Check for voltage across the pins on the gas valve. There should be 24-28V AC .

A. If the voltage reading is incorrect, check the wiring for an open or short circuit.

B. If the voltage reading is correct, the gas valve may be faulty.

Figure 50 - Main Gas Valve and Wiring Reference

67

MAINTENANCE

To guarantee trouble free operation of this heater, the manufacturer suggests following these guidelines.

Most problems associated with fan failures are directly related to poor service and maintenance.

Please record any maintenance or service performed on this fan in the documentation section located at the end of this manual.

WARNING: DO NOT ATTEMPT MAINTENANCE ON THE HEATER UNTIL THE

ELECTRICAL SUPPLY HAS BEEN COMPLETELY DISCONNECTED AND THE MAIN

GAS SUPPLY VALVE HAS BEEN TURNED OFF.

General Maintenance

1. Fan inlet and approaches to ventilator should be kept clean and free from any obstruction.

2. Motors are normally permanently lubricated. Check bearings periodically. If they have grease fittings lubricate each season. Use caution when lubricating bearings, wipe the fittings clean, the unit should be rotated by hand while lubricating. Caution: Use care when touching the exterior of an operating motor. Motors normally run hot and may be hot enough to be painful or cause injury.

3. All fasteners should be checked for tightness each time maintenance checks are preformed prior to restarting unit.

4. Blowers require very little attention when moving clean air. Occasionally oil and dust may accumulate causing imbalance. If the fan is installed in a corrosive or dirty atmosphere, periodically inspect and clean the wheel, inlet and other moving parts to ensure smooth and safe operation.

5. Before each heating season, verify that the drain on the bottom of each common flue box of every furnace in the unit is clear.

Re-Setting of the Unit

If the flame safety control is locked out (Spark igniter fails or no gas supply), reset the unit by:

1. Turn OFF Power to the unit.

2. Turn Power to the unit back ON.

Emergency shutdown of unit

To shut down the unit in the event of an emergency do the following:

1. Turn power OFF to the unit from main building disconnect.

2. Turn the external disconnect switch to the OFF position.

3. CLOSE the inlet gas valve located on the heater.

Prolonged shutdown of the unit

For prolonged shutdown the following steps should be done:

1. Turn the external disconnect switch to the OFF position.

2. CLOSE the inlet gas valve located on the heater.

To re-start the unit the following steps should be done:

1. Turn the external disconnect switch to the ON position.

2. OPEN the inlet gas valve located on the heater.

68

2 weeks after startup

1. Belt tension should be checked after the first 2 weeks of fan operation. Belts tend to stretch and settle into pulleys after an initial start-up sequence. Do not tension belts by changing the setting of the motor pulley , this will change the fan speed and may damage the motor. To re-tension belts, turn the power to the fan motor OFF. Loosen the fasteners that hold the blower scroll plate to the blower. Rotate the motor to the left or right to adjust the belt tension. Belt tension should be adjusted to allow 1/64” of deflection per inch of belt span. Exercise extreme care when adjusting

V-belts as not to misalign pulleys. Any misalignment will cause a sharp reduction in belt life and produce squeaky noises. Over-tightening will cause excessive belt and bearing wear as well as noise. Too little tension will cause slippage at startup and uneven wear. Whenever belts are removed or installed, never force belts over pulleys without loosening motor first to relieve belt tension. When replacing belts, use the same type as supplied by the manufacturer. On units shipped with double groove pulleys, matched belts should always be used.

2. All fasteners should be checked for tightness each time maintenance checks are preformed prior to restarting unit.

Every 3 months

1. Belt tension should be checked quarterly. See instructions in the previous maintenance section.

Over-tightening will cause excessive bearing wear and noise. Too little tension will cause slippage at startup and uneven wear.

2. Filters need to be cleaned and/or replaced quarterly, and more often in severe conditions.

Washable filters can be washed in warm soapy water. When re-installing filters, be sure to install with the airflow in the correct direction as indicated on the filter.

Unit Size

1

2

3

4

5

Diagonal Filters

Filter Quantity

4

2

4

4

9

Table 16 - Filter Quantity Chart

Intake

Size 1 Sloped

Size 2 Sloped

Size 3 Sloped

Size 4 Sloped

Size 5 Sloped

Size 1 V-Bank

Size 2 V-Bank

Size 3 V-Bank

Size 4 V-Bank

16” x 20” 20” x 25”

3

6

3

10

8

3

8

15

8

12 Size 5 V-Bank

Table 17 - Optional Mixing Box Filters

Filter Size Unit Size

10 x 16

20 x 25

1

2

15 x 20

18 x 25

14.5 x 19

3

4

5

Vertical Filters

Filter Quantity

1

1

2

2

3

Filter Size

10 x 16

16 x 25

15 x 15

16 x 20

14.5 x 19

69

Yearly

1. Before each heating season, verify that the drain on the bottom of each common flue box of every furnace in the unit is clear.

2. Inspect bearings for wear and deterioration. Replace if necessary.

3. Inspect belt wear and replace torn or worn belts.

4. Inspect bolts and set screws for tightness. Tighten as necessary.

5. Inspect motor for cleanliness. Clean exterior surfaces only. Remove dust and grease from the motor housing to ensure proper motor cooling. Remove dirt and grease from the wheel and housing to prevent imbalance and damage.

6. The heat exchanger should be checked for cracks. The heat exchanger should be replaced immediately if cracks are detected.

7. Inspect the combustion blower motor for cleanliness. Clean exterior surfaces of the combustion blower motor only. Removing excess dust and grease guarantees proper motor cooling.

8. Before each heating season, examine the burner and gas orifices. Inspect burner ports for foreign debris, heat exchanger, and spark igniter for cleanliness.

70

Heat Exchanger Inspection

NOTE: Below is for size 1 and 2 units.

Figure 51 – Size 1 and Size 2 Heat Exchanger

1. To inspect the heat exchanger, remove the access door on backside side of unit.

2. Visually inspect the heat exchanger. Check for splits, cracks or holes in the tubes and joints. If damage is found, replace the heat exchanger.

NOTE: Below is for size 3-5 units.

1. To inspect the heat exchanger, remove the access door on backside side of unit. This will expose the insulated heat exchanger compartment.

2. Use a sharp razor knife to cut the reinforced silver tape around all four outer edges, and down the center of the two halves.

3. Remove the insulation. Silicone is used to adhere the insulation to the panel.

4. Remove the screws from the right side panel first. Then remove the screws from the left panel.

Remove both panels to expose the heat exchanger.

5. Visually inspect the heat exchanger. Check for splits, cracks or holes in the tubes and joints. If damage is found, replace the heat exchanger.

Figure 52 – Size 2 to Size 5 Heat Exchanger

71

Appendix A – IBT Board Electrical Connections

RJ45 Connectors

J1 Auxiliary slave port

J2 Programming port (service only)

J3 connects to HMI

J4 connects to VFD controller

J5 connects to Cat 5 converter for Compressor

Frequency Drive

J6 connects to electronic expansion controller

J7 (FSC-1) and J8 (FSC-2) connectors contain inputs and outputs for Flame Safety Controller

(FSC), furnace, and gas train. J7 comes standard as stage 1 furnace, J8 as stage 2 furnace.

Pin 1 - 24V AC output to Pressure Switch input

(PSW) on FSC

Pin 2 - 24V AC output to Thermostat input (TH/W) on FSC

Pin 3 - detects 24V AC presence from IND on

FSC

Pin 4 - 24V AC output to valve power (V1) on FSC

Pin 5 - 24V AC output to main gas valve

Pin 6 - 0-10V DC (+) to modulating gas valve or

Electric Heater (option)

Pin 7 - 0-10V DC ( –) to modulating gas valve

Pin 8 - modulating gas valve shield

Connector J9 contains 120V AC connections

Pin 9 - ground to main gas valve

Pin 10 - detects 24V AC presence from vent proving switch

Pin 11 - 24V AC output (L1) on FSC

Pin 12 - 24V AC supply power (R) on FSC

Pin 13 - 24V AC out to high limit switch

Pin 14 - 24V AC out to vent proving switch

Pin 15 - detects 24V AC presence from roll out switch

Pin 16 - detects 24V AC presence from high limit switch

Pin 17 - 24V AC out to roll out switch

Pin 18 - valve ground (V2) on FSC

Pin 1 - 120V AC input

Pin 2 - tied to Pin 1 internally to the board

Pin 3 - detects 120V AC presence for fire condition

Pin 4 - 120V AC out to damper

Pin 5 - 120V AC presence from damper end limit

Pin 6 - 120V AC out to drain heater

Pin 7 - 120V AC out to cabinet heater

Pin 8 - 120V AC neutral

72

Connector J10 contains 120V AC connections

Pin 1 - detects 120V AC from evap cooler pressure switch

Pin 2 - detects 120V AC from evap cooler float switch

Pin 3 - 120V AC out to evap cooler water solenoid

Pin 4 - 120V AC out to evap cooler 3 way drain valve

Pin 5 - detects 120V AC from supply overload

Pin 6 - 120V AC out to supply starter coil

Pin 7

-

120V AC out to exhaust starter coil

Pin 8 - 120V AC from exhaust overload

Connector J11 contains low voltage screw terminal connections

Pin 1 - is an auxillary input

Pin 2 - is an auxiliary input

Pin 3 - is an auxiliary input

Pin 4 - Analog Control/DDC heat select input

Connector J12 contains low voltage sensor screw terminal connection

Pin 5 - Analog Control/DDC cool select input

Pin 6 - Analog Control/DDC call for blower input

Pin 7 - Analog Control/DDC occupied override input

Pin 8 - Analog Control/DDC isolated common

Pin 1 - smoke detector 24V AC out

Pin 2 - smoke detector 24V AC out

Pin 3 - smoke detector input

Pin 4 - smoke detector 24V AC common

Connector J13 contains low voltage connections

Pin 5 - air quality 24V AC out

Pin 6 - air quality 0-10V DC input

Pin 7 - air quality 0-10V DC common

Pin 8 - air quality 24V AC common

Pin 1 - 24V DC (+) for 4-20mA current sensor

Pin 2 - PWM (+) out for ECM motor

Pin 3 - 24V AC out for low gas pressure switch

Pin 4 - 24V AC out for high gas pressure switch

Pin 5 - 24V AC out for clogged filter switch

Pin 6 - 24V AC out for air flow switch

Pin 7 - 24V AC for board power

Pin 8 - 24V DC (-) for 4-20mA current sensor

Pin 9 - PWM ( –) out for ECM motor

Pin 10 - detects 24V AC for low gas pressure switch

Pin 11 - detects 24V AC for high gas pressure switch

Pin 12 - detects 24V AC for clogged filter switch

Pin 13 - detects 24V AC for air flow switch

Pin 14 - Ground

73

Connector J14 contains screw terminal connections for relative humidity sensors

Pin 1 - 24V DC (+) to humidity sensor

Pin 2 - 0-10V DC input from humidity sensor

Pin 3 - 0-10V DC common from humidity sensor

Pin 4 - 24V DC common to humidity sensor

Connector J15 contains screw terminal connections for 10k temperature thermistors only

Pin 5 - 24V DC + to humidity sensor

Pin 6 - 0-10V DC input from humidity sensor

Pin 7 - 0-10V DC common from humidity sensor

Pin 8 - 24V DC common to humidity sensor

Pins 1 and 2 - for intake sensor

Pins 3 and 4 - for return sensor

Pins 5 and 6 - for outdoor sensor

Connector J16 contains low voltage screw terminal connections for BAS/DDC/Space

Pins 7 and 8 - for discharge sensor

Pins 9 and 10 - for space temperature sensor

Pin 1 - Analog Control /DDC 0-10V DC input

Pin 2 - Analog Control /DDC 4-20mA input

Pin 3 - Analog Control /DDC analog input common

Pin 4 - Analog Control /DDC shield

Connector J17 triac output for power vent 2

Pin 5 - aux in for unit interlock

Pin 6 - 24V AC out

Pin 7 - 24V AC out

Pin 8 - common

74

Connector J18 contains low voltage connections

Pin 1 - 24V DC (+) spare output

Pin 2 - 0-10V DC (+) for modulating damper

Pin 3 - 0-10V DC (+) spare

Pin 4 - dx float switch output

Pin 5 - 24V AC out spare unit interlock

Pin 6 - unused connection

Pin 7 - unused connection

Connector J19 triac output for second power vent 2

Pin 8 - 24V DC ( –) spare output

Pin 9 - 0-10V DC ( –) for modulating damper

Pin 10 - 0-10V DC ( –) spare

Pin 11 - dx float switch common

Pin 12 - 24V AC common spare unit interlock

Pin 13 - unused connection

Pin 14 - unused connection

Connector J20 triac neutral for second power vent

Connector J21 triac neutral for first power vent

Connector J22 (Y1) contains 24V AC condenser 1 outputs

Pin 1 - 24V AC out

Connector J23 (Y2) contains 24V AC condenser 2 outputs

Connector J24 (Y3) contains 24V AC condenser 3 outputs

Pin 1 - 24V AC out

Connector J25 factory programming only, Zilog

ZDI microcontroller debug/programming interface

Pin 1 - 3.3V DC

Pin 2 - reset

Pin 3 - Gnd

Pin 2 - 24V AC common

Pin 2 - 24V AC common

Pin 4 - DBG input

Pin 5 - Gnd

Pin 6 - NC

75

Appendix B – IBT DDC Points

Full External Control Points:

BACNET OBJECT

NAME

HeatCommand

CoolCommand

BACNET

OBJECT

ID

1

2

BACNET

DATA

TYPE

Binary

Value

Binary

Value

LON SNVT NAME nviHeatCommand nviCoolCommand

SNVT TYPE

SNVT_count

SNVT_count

FUNCTION

Control

Control

DEFAULT

0

0

RANGE

0-1

0-1

DESCRIPTION

OFF(0) / ON(1)

OFF(0) / ON(1)

Binary

FanCommand 3 nviFanCommand SNVT_count Control 0 0-1 OFF(0) / ON(1)

Value

Use only if Heati ng and/or Cooling tempering mode has been set to “DDC” through the unit’s HMI.

• Setting the Heating and Cooling modes to “DDC” disables temperature based activation of these functions . The preferred heating and cooling activation method is to use space and/or intake temperatures along with unit set points.

Heating and Cooling cannot be called for at the same time.

The Fan Control point will only work if the heating or cooling mode is set to DDC.

For factory settings and temperature set points BACNET and LON points are displayed on to the BMS as raw values. The BMS must scale these points when reading and/or writing based on the point description.

For example, temperature sensor values must be divided by 10 after they are read. Likewise, when writing to a set point, the intended value must be multiplied by 10 before being sent to the controller.

Factory Settings:

BACNET OBJECT NAME

NumberofHMIs

BACNET

OBJECT ID

4

BACNET

DATA TYPE

Analog Value

LON SNVT NAME nviNumberofHMIs

SNVT

TYPE

SNVT_ count

FUNCTION

Monitor/Control

DEFAULT

1

RANGE

1-5

DESCRIPTION

HMI1 is always the cabinet HMI

IncludeHMIAvg

SetHeatStages

SetCondenserStages

5

6

7

Analog Value

Analog Value

Analog Value nviIncludeHMIAvg nviSetHeatStages nviSetCondStages

SNVT_ count

SNVT_ count

SNVT_ count

Monitor/Control

Monitor/Control

Monitor/Control

2

0

0

1-31 odd

0-4

0-5

Bitfield, if bit=1 that HMI is read only

One IBT Board can support 2 stages

Distinction between the number of condensers and the number of condenser cooling stages

FreezestatTime 8 Analog Value nviFstatTime

SNVT_ count

Monitor/Control 10 1-10 Time in Minutes

EvapSprayONTime

EvapSprayOFFTime

9

10

Analog Value

Analog Value nviEvSprayONt nviEvSprayOFFt

SNVT_ count

SNVT_ count

Monitor/Control

Monitor/Control

Set By

Plant

Set By

Plant

0-60

0-500

Time in Seconds

Time in Seconds

MinVFDFreqOccupied 11 Analog Value nviMinVFDFreqO

SNVT_ count

Monitor/Control 0 0-MaxVFDFreq Freq(Hz)*10

MaxVFDFreqOccupied

MinOAPercentOccupied

MaxOAPercentOccupied

12

13

14

Analog Value

Analog Value

Analog Value nviMaxVFDFreqO nviMinOAPercentO nviMaxOAPercentO

SNVT_ count

SNVT_ count

SNVT_ count

Monitor/Control

Monitor/Control

Monitor/Control

80

0

100

MinVFDFreq-

800

0-Max Outdoor

Air %

Min Outdoor Air

%-100

Freq(Hz)*10

Minimum Percentage of Outdoor

Air

Maximum Percentage of Outdoor

Air

MinPWMOccupied

MaxPWMOccupied

SchedulingEnable

15

16

17

Analog Value

Analog Value

Binary Value nviMinPWMO nviMaxPWMO nviSchedEnable

SNVT_ count

SNVT_ count

SNVT_ count

Monitor/Control

Monitor/Control

Monitor/Control

0

100

0

0-Max PWM

Min PWM-100

0-1

ECM Minimum Speed

ECM Maximum Speed

Disabled (0) / Enabled (1)

CoolDXLowTempLimit

EvapDrainValveSP

EvapDrainValveSPDiff

EvapCoolingDiff

18

19

20

21

Analog Value

Analog Value

Analog Value

Analog Value nviCoolDLowTLim nviEvapDValveSP nviEvapDVlvSPDif nviEvapCoolDif

SNVT_ count

SNVT_ count

SNVT_ count

SNVT_ count

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

550°F

130°C

400°F

40°C

20°F

20°C

30°F

20°C

400-700°F

40-210°C

350-1100°F

20-100°C

10-50°F

10-30°C

10-100°F

10-60°C

Temperature*10

Temperature*10

Temperature*10

Temperature*10

MinOAPercentUnoccupied

MaxOAPercentUnoccupied

MinVFDFreqUnoccupied

MaxVFDFreqUnoccupied

MinPWMUnoccupied

MaxPWMUnoccupied

22

23

24

25

26

27

Analog Value

Analog Value

Analog Value

Analog Value

Analog Value

Analog Value nviMinOAPercentU nviMaxOAPercentU nviMinVFDFreqU nviMaxVFDFreqU nviMinPWMU nviMaxPWMU

SNVT_ count

SNVT_ count

SNVT_ count

SNVT_ count

SNVT_ count

SNVT_ count

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

0%

100%

30Hz

60Hz

0%

100%

0-Max %

Min-100%

0-VFD Max

VFD Min-800

0-Max PWM

Min PWM - 100

Percentage of outdoor air

Percentage of outdoor air

Freq (Hz) *10

Freq (Hz) *10

Motor speed %

Motor speed %

CoolEvapLowTempLimit 28 Analog Value nviCoolELowTLim SNVT_ Monitor/Control 800°F 60-100°F count

Temperature*10

38°C 16-38°C

Writing to any of these registers will trigger a system reboot. Avoid writing to these on a regular basis.

The Scheduling Enable point tells the unit whether scheduling is allowed or not. It is NOT an occupancy command.

76

Temperature Set Points:

BACNET OBJECT NAME

BACNET

OBJECT

ID

BACNET

DATA

TYPE

LON SNVT NAME SNVT TYPE FUNCTION DEFAULT RANGE DESCRIPTION

InHeatOccSP

SpaceHeatOccSP

MinDischHeatSP

DischHeatOccSP

MaxDischHeatOccSP

InCool1OccSP

IntakeCoolOccStageDiff

SpaceCoolOccStageDiff

SpaceCoolOccSP

EvapCoolOccSP

InHeatUnoccSP

SpaceHeatUnoccSP

MinDischHeatUnoccSP

DischHeatUnoccSP

MaxDischHeatUnoccSP

InCool1UnoccSP

IntakeCoolUnoccStageDiff

SpaceCoolUnoccStageDiff

SpaceCoolUnoccSP

EvapCoolUnoccSP

InFirestatSP

DischFirestatSP

CabinetHeatSP

FreezestatSP

FurnaceDrainHeatSP

RoomOverrideSP

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value

Analog

Value nviInHeatOccSP nviSpaceHOccSP nviMinDischHSP nviDischHOccSP nviMaxDischHOcSP nviInCool1OccSP nviInCOccStgDif nviSpCOccStgDif nviSpaceCOccSP nviEvapCoolOccSP nviInHeatUnoccSP nviSpaceHUnoccSP nviMinDisHUnocSP nviDischHUnoccSP nviMaxDisHUnocSP nviInC1UnoccSP nviInCUnocStgDif nviSpCUnocStgDif nviSpaceCUnoccSP nviEvapCUnoccSP nviInFirestatSP nviDischFstatSP nviCabinetHeatSP nviFreezestatSP nviFurnDrainHSP nviRoomOrideSP

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

450°F

70°C

700°F

210°C

600°F

160°C

600°F

160°C

1200°F

490°C

850°F

290°C

100°F

60°C

30°F

20°C

740°F

230°C

850°F

290°C

450°F

70°C

700°F

210°C

600°F

160°C

600°F

160°C

1200°F

490°C

850°F

290°C

100°F

60°C

30°F

20°C

740°F

230°C

850°F

290°C

1350°F

570°C

2400°F

1160°C

0°F

-180°C

350°F

20°C

350°F

20°C

900°F

310°C

350-1100°F

20-430°C

Intake Heat SP + Intake Heat

Diff < Intake Cool SP

350-1100°F

20-430°C

Space Heat SP + Space Heat

Diff < Space Cool SP

400°F-DischHeatOccSP

40°C-DischHeatOccSP

MinDischHeatSP-

MaxDischHeatOccSP

DischHeatOccSP-1500°F

DischHeatOccSP-660°C

550-1000°F

130-380°C

Intake Cool SP - Intake Cool

Hyst > Intake Heat SP

0-200°F

0-110°C

0-200°F

0-110°C

500-900°F

100-320°C

Space Cool SP - Space Cool

Hyst > Space Heat SP

550-1000°F

130-380°C

350-1100°F

20-430°C

350-1100°F

20-430°C

400°F-DischHeatUnoccSP

40°C-DischHeatUnoccSP

MinDischHeatUnoccSP-

MaxDischHeatUnoccSP

DischHeatUnoccSP-1500°F

DischHeatUnoccSP-660°C

550-1000°F

130-380°C

0-200°F

0-110°C

0-200°F

0-110°C

500-900°F

100-320°C

550-1000°F

130-380°C

1000-3000°F

380-1490°C

1000-3000°F

380-1490°C

0-400°F

(-180)-40°C

(-400)-750°F

(-400)-24°C

350-450°F

20-70°C

600-1200°F

160-490°C

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

Temperature*10

The preferred method for DDC control is through set point manipulation. Use the set points shown above along with the “DDC Occupied Override” point in the Runtime settings section to control the blower and to determine when to heat or cool.

• Temperatures can be in degrees F or degrees C, depending on the “Temp Units” point in the factory settings.

77

Runtime Settings and Indicators:

BACNET OBJECT NAME

VFDFrequencySettingOcc

PWMRateOccupied

MixBoxUnoccOAPercent

MixBoxOccOAPercent

BACNET

OBJECT

ID

55

56

57

58

BACNET

DATA

TYPE

Analog

Value

Analog

Value

Analog

Value

Analog

Value

LON SNVT NAME nviVFDFrequencyO nviPWMRateO nviMBoxUnocOAPer nviMBoxOcOAPer

MixingDamperVolts

DDCOccupiedOverride

FSC1GasON

FSC2GasON

FSC3GasON

FSC4GasON

59

60

61

62

63

64

Analog

Value

Binary

Value

Binary

Input

Binary

Input

Binary

Input

Binary

Input nviMDamperV nviDDCOccupOride nvoFSC1GasON nvoFSC2GasON nvoFSC3GasON nvoFSC4GasON

SNVT TYPE

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

FUNCTION

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor/Control

Monitor

Monitor

Monitor

Monitor

DEFAULT

Set By

Plant

Set By

Plant

0

100

0

0

0

0

0

0

RANGE

VFD Min Freq-VFD Max

Freq

Min PWM-Max PWM

Min Outdoor Air %-

Max Outdoor Air %

Min Outdoor Air %-

Max Outdoor Air %

0-1000

0-1

0-1

0-1

0-1

0-1

DESCRIPTION

Running VFD Frequency

Running PWM Rate

Percentage of Outdoor Air

Unoccupied

Percentage of Outdoor Air

Occupied

Volts*100

Override Off(0)

– Override

On(1)

Off(0)

– On(1)

Off(0)

– On(1)

Off(0)

– On(1)

Off(0)

– On(1)

VFDFrequencySetting

Unoccupied

PWMRateUnoccupied

CoolingOutputY1

CoolingOutputY2

CoolingOutputY3

AirQuality

AnalogHeatControl 0-10V

65

66

67

68

69

70

71

Analog

Value

Analog

Value

Binary

Input

Binary

Input

Binary

Input

Analog

Value

Analog

Value nviVFDFreqU nviPWMRateU nvoCoolOutY1 nvoCoolOutY2 nvoCoolOutY3 nvoAirQuality nviAVHeat0-10V

SNVT_count Monitor/Control

Set By

Plant

VFD Min Freq-VFD Max

Freq

SNVT_count Monitor/Control

Set By

Plant

Min PWM-Max PWM

SNVT_count

SNVT_count

SNVT_count

SVNT_count

SNVT_count

Monitor

Monitor

Monitor

Monitor

Monitor/Control

0

0

0

0

0

0-1

0-1

0-1

0-1000

0-1000

Unoccupied Running

Unoccupied Running

Off(0) – On(1)

Off(0)

– On(1)

Off(0)

– On(1)

Volts*100

Volts*100

• Use the “DDC Occupied Override” point to switch between occupied and unoccupied settings and set points. Make sure that all timeslots in the unit’s internal schedule are set to “Unoccupied” in order to avoid conflicting commands. This can be verified through the unit’s HMI.

• To control the blower through the “DDC Occupied Override” point, set the blower mode to

“ON/AUTO/OFF” during occupied and unoccupied times, depending on the required sequence of operations.

FSC1-4 points can be used as indicators that the unit is attempting to heat. Cooling Outputs Y1-3 points can be used as indicators that the unit is attempting to cool.

• Analog heat control can only be used if the heating tempering mode is set to “DDC”.

78

Sensor Values and Alerts:

BACNET OBJECT NAME

DamperPositionReference

SupplySpeedReference

OATemp

ReturnTemp

DischargeTemp

IntakeTemp

SpaceTemp

RTCTemp

HMI1Temp

HMI2Temp

HMI3Temp

HMI4Temp

HMI5Temp

AlertCode1

AlertCode2

AlertCode3

AlertCode4

AlertCode5

AlertCode6

BACNET

OBJECT

ID

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

BACNET

DATA

TYPE

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

Analog

Input

LON SNVT NAME nvoDamperPos nvoSupSpeedRef nvoOATemp nvoReturnTemp nvoDischargeTemp nvoIntakeTemp nvoSpaceTemp nvoRTCTemp nvoHMI1Temp nvoHMI2Temp nvoHMI3Temp nvoHMI4Temp nvoHMI5Temp nvoAlertCode1 nvoAlertCode2 nvoAlertCode3 nvoAlertCode4 nvoAlertCode5 nvoAlertCode6

SNVT TYPE

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

SNVT_count

FUNCTION

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

DEFAULT

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

RANGE

0-1000

0-1000

(-64)-302°F

(-53)-150°C

(-64)-302°F

(-53)-150°C

(-64)-302°F

(-53)-150°C

(-64)-302°F

(-53)-150°C

(-64)-302°F

(-53)-150°C

(-40)-185°F

(-40)-85°C

(-40)-257°F

(-40)-125°C

(-40)-257°F

(-40)-125°C

(-40)-257°F

(-40)-125°C

(-40)-257°F

(-40)-125°C

(-40)-257°F

(-40)-125°C

0-87

0-87

0-87

0-87

0-87

DESCRIPTION

Volts*100

Volts*100

Temperature*10

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

<Min = Disconnected

>Max = Broken

See fault code table page 80

See fault code table page 80

See fault code table page 80

See fault code table page 80

See fault code table page 80

UnitStatus 91

Analog

Input nvoUnitStatus

SNVT_count

SNVT_count

Monitor

Monitor

-

-

0-87

0-3

See fault code table page 80

0= Idle

1= Heating

2= Cooling

3 = Blower Only

• Temperatures can be in degrees F or degrees C, depending on the “Temp Units” point in the factory settings.

Values should be scaled by the Building Management System (see point description).

Variable Frequency Drive Information (Read-Only):

BACNET OBJECT

NAME

VFDActualFrequency

VFDAmperage

VFDPower

BACNET

OBJECT

ID

92

93

94

BACNET

DATA TYPE

Analog Input

Analog Input

Analog Input

LON SNVT NAME nvoVFDActFreq nvoVFDAmps nvoVFDPower

SNVT TYPE

SNVT_count

SNVT_count

SNVT_count

FUNCTION

Monitor

Monitor

Monitor

DEFAULT

-

-

-

RANGE

0-65535

0-1000

0-65500

DESCRIPTION

Frequency*10

Amperage*10 kiloWatts*100

79

IBT DDC Fault Codes

23

24

25

26

27

28

29

30

15

16

17

18

19

20

21

22

7

8

9

10

11

12

13

14

Code

0

1

2

3

4

5

6

39

40

41

42

43

44

45

46

31

32

33

34

35

36

37

38

47

48

49

50

Description

No Fault

Fire

Smoke

Gas PS High (Master)

Gas PS Low (Master)

IBT to IBT Comm Fail

Gas PS High (Slave)

Gas PS Low (Slave)

Exhaust Overload

Supply Overload

VFD571 IGBT Temp

VFD571 Output

VFD571 Ground

VFD571 Temp

VFD571 Flying Start

VFD571 High DC Bus

VFD571 Low DC Bus

VFD571 Overload

VFD571 OEM

VFD571 Illegal Setup

VFD571 Dynamic Brake

VFD751 Phase Lost

VFD751 External

VFD751 Control

VFD571 Start

VFD571 Incompat Param Set

VFD571 EPM HW

VFD571 Internal 1

VFD571 Internal 2

VFD571 Internal 3

VFD571 Internal 4

VFD571 Internal 5

VFD571 Internal 6

VFD571 Internal 7

VFD571 Internal 8

VFD571 Personality

VFD571 Internal 10

VFD571 Remote Keypad Lost

VFD571 Assertion Level

VFD571 Internal 11

VFD571 Internal 12

VFD571 Internal 13

VFD571 Internal 14

VFD571 Comm Module

VFD571 Network

VFD571 Network 1

VFD571 Network 2

VFD571 Network 3

VFD571 Network 4

VFD571 Network 5

VFD571 Network 6

80

74

75

76

77

78

79

80

81

66

67

68

69

70

71

72

73

Code

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

90

91

92

93

94

82

83

84

85

86

87

88

89

Description

VFD571 Network 7

VFD571 Network 8

VFD571 Network 9

Return Sensor Missing

Return Sensor Broken

Outside Sensor Missing

Outside Sensor Broken

Intake Sensor Missing

Intake Sensor Broken

Discharge Sensor Missing

Discharge Sensor Broken

HMI Temp Sensor

RTC 1 Temp Sensor

RTC 2 Temp Sensor

No Damper End

No Supply Air Proving

FSC1 High Temp

FSC2 High Temp

FSC3 High Temp

FSC4 High Temp

FSC1 Rollout

FSC2 Rollout

FSC3 Rollout

FSC4 Rollout

FSC1 Vent Proving

FSC2 Vent Proving

FSC3 Vent Proving

FSC4 Vent Proving

Freezestat Lockout

Firestat Lockout

Evap Water PS

Evap Float Detect

DX Float Detect

Modbus SysInfo Comm

Master ROM CRC

Slave ROM CRC

Clogged Filters

HMI 1 Version Wrong

HMI 2 Version Wrong

HMI 3 Version Wrong

HMI 4 Version Wrong

HMI 5 Version Wrong

Modbus Supply Vfd Comm

Modbus HMI Comm

Definitions

MVL – Modulating Voltage Low – (.2V for 0-10V input, 2.1V for 2-10V input, .4mA for 0-20mA input, or

4.2mA for a 4-20mA input) - If the voltage stays below this set value for a certain amount of time the current relay will open.

MVH – Modulating Voltage High – (9.60V for either 0-10V or 2-10V, or 19.2mA for either 0-20mA or 4-

20mA) - If the voltage stays above this set value for a certain amount of time the next relay will close.

RCT – Relay Close Time – The amount of time that the input voltage must stay above MVH before the next relay will close.

ROT – Relay Open Time – The amount of time that the input voltage must stay below MVL before the current relay will open.

RTT – Relay Tentative Time – The amount of time after a new relay has closed that the voltage must not drop or else the newly closed relay will open again.

Number of Stages - This will set the number of stages that are on the IBT.

Resolution – The resolution changes how often a sample is take and recorded from the input.

Cycle Time – The cycle time is the amount time that is stored in the history.

The number of samples that is stored in the history is calculated by ( Cycle Time/Resolution) .

Stage Operation

During stage 1 the first burner is modulating the full range of the input, whether it be a 0-10V signal or a

2-10V signal. Once the input voltage has been above MVH for time RCT, a pre-purge cycle starts on the next burner.

If the input voltage still remains high and has not lowered for the entire 1 minute pre-purge, the second burner will then light and go into high-fire for 17 seconds. Stage 2 begins after the 17 seconds. During this stage the input is split into two sets of linearization data. Burner one will modulate from 0-10V from the first half of the input signal. Burner two will modulate from 0-10V from the second half.

For example, if the input is a 0-10V signal and has a value of 7V, burner one will be at max output of 10V and burner two will be around 4V (based on the current set of linearization data). If the input signal is a 2-

10V signal and the value is 6V, burner one will be at 10V and burner two will be at 0V. This is because

6V is the very middle of the 2-10V scale for the input. If the input signal is a 0-10V signal and has a value of 1V, the first burner will have an output around 2V and the second burner will have an output of 0V.

This modulating scheme remains throughout the rest of the stages. If the input remains above MVH for time RCT after the preceding relay has closed, the third burner will begin its 1 minute pre-purge followed by 17 seconds of high fire and Stage 3 will be entered. After this 17 seconds the third burner will remain at high-fire while the first two burners continue to modulate. The fourth burner acts in the same manner as the third. If the input voltage ever remains below MVL for time ROT, then the last relay will be opened and that stage will shut off.

81

Modulation Sequence

Input V < MVL for time ROT

STAGE 1

1 Modulating Burner that is linearized based on the input. Stays in stage 1 for as long as V < MHV

Input V > MVH for time RTT

STAGE 2

2 Modulating Burners with split linearization. Stays in stage 2 for as long as MVL <V < MVH

Input V < MVL for time ROT

Input V < MVL for time ROT

Input V > MVH for time RTT

STAGE 3

2 Modulating Burners with split linearization and 1 Fixed Burner.

Stays in stage 3 for as long as MVL

< V < MVH

Input V > MVH for time RTT

STAGE 4

2 Modulating Burners with split linearization and 2 Fixed Burners.

Stays in stage 4 for as long as MVL

< V

RCT

Stage Total # of stages

1 2 3 4

First 0 0 0 0

Second x 120 90 90

Third x x 120 90

Fourth x x x 120

45

45

45

45

Relay 2 closes

Second Burner -> 1 Minute prepurge followed by 17 second High-

Fire

If input V lowers during

RTT

Input V > MVH for time RCT

60

60

60

60

Input V > MVH for time

RCT

If input V lowers during

RTT

ROT

(Seconds)

Relay 3 closes

Third Burner -> 1 Minute pre-purge followed by 17 second High-Fire

Input V > MVH for time RCT

If input V lowers during

RTT

Relay 4 closes

Fourth Burner -> 1 Minute prepurge followed by 17 second High-

Fire

RTT

(Seconds)

82

83

Start-Up and Maintenance Documentation

START-UP AND MEASUREMENTS SHOULD BE PERFORMED AFTER THE SYSTEM HAS BEEN AIR

BALANCED AND WITH THE HEAT ON (Warranty will be void without completion of this form)

Job Information

Job Name

Address

City

State

Zip

Phone Number

Fax Number

Contact

Purchase Date

Service Company

Address

City

State

Zip

Phone Number

Fax Number

Contact

Start-Up Date

Heater Information

Refer to the start-up procedure in this manual to complete this section.

Name Plate and Unit Information Field Measured Information

Model Number Motor Voltage

Serial Number

Motor Volts

Motor Hertz

Motor Phase

Motor FLA

Motor HP

Blower Pulley

Motor Pulley

Belt Number

Gas Type

Min. Btu/Hr

Max. Btu/Hr

Motor Amperage**

RPM

Gas Type

High Fire Inlet Gas Pressure

Low Fire Manifold Gas Pressure

High Fire Manifold Gas Pressure

Thermostat Set-Point

Temperature Control

Airflow Direction in. w.c. in. w.c. in. w.c.

Discharge

Space

Correct

Incorrect

**

If measured amps exceed the FLA rating on the nameplate, fan RPM must be reduced to decrease the measured amps below the nameplate FLA rating.

Maintenance Record

Date Service Performed

Factory Service Department

Phone: 1-866-784-6900

Fax: 1-919-554-9374

84

advertisement

Related manuals

Download PDF

advertisement