Panel Meters
Series S
Panel meter 72x36mm
Model S40-T
Pt100/RTD
Thermocouples
Panel meter for Pt100/RTD (2 and 3 wires), and thermocouples J, K, T, E, S, R, N, C,
L and X with temperature display in degrees celsius (ºC) or fahrenheit (ºF). Selectable
Pt100/RTD resolution at 1º or 0.1º, and manual offset available. Thermocouple measure with internal CJC selectable (enabled or disabled). Selectable behavior in case of sensor break (‘to_high’ or ‘to_low’). Reduced size 72x36mm. Reading with 4 digits. Maximum and minimum display memory, steps, alarms with single or double setpoints, 5 levels of brightness, ... Universal AC and DC power modules and up to 2 modules for signal retransmission and control (relay outputs, analogue outputs, ...).
USER’S MANUAL
(2264R05)
User’s Manual S40-T
1. Meter S40-T
Panel meter 72x36mm size for Pt100/RTD and Thermocouples
Panel meter for temperature signals, accepts Pt100/RTD with
2 and 3 wires, and thermocouples J, K, T, E, S, R, N, C, L and
X. Temperature display in degrees celsius (ºC) or fahrenheit
(ºF). Thermocouple cold junction compensation selectable.
Manual offset selectable. Selectable behavior for alarms in case of sensor break (‘to_high’ or ‘to_low’).
Power options with universal AC and DC ranges, and space for 2 additional control and/or signal retransmission modules.
Standard IP54 front protection. Optional green led.
Connections via plug-in screw terminals and configuration via three front push-buttons. For application on industrial environments.
Instrument with reduced 72x36mm size. Resolution 4 digits with negative sign (“9999”/“-1999”).
Management for up to 2 alarms with 1 or 2 setpoints each alarm, with hysteresis and delays. Provides memory for maximum and minimum, display on selectable steps, password and selectable levels of brightness.
1.1 Order reference
S40 -
Model
T -
Power
H
-H
(85-265 Vac/dc)
-L
(11-60 Vdc and 24/48 Vac)
-
Option1
---
-R1
(1 relay)
-AO
(Analogue Output)
-
(empty)
-
Option2
---
-R1
(1 relay)
-AO
(Analogue Output)
-
(empty)
-
Others
---
-G
(green led)
-
(empty)
Index
1. Meter S40-T . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Order reference . . . . . . . . . . . . . . . . . . . 2
1.2 Front View . . . . . . . . . . . . . . . . . . . . . 3
1.3 Rear View. . . . . . . . . . . . . . . . . . . . . . 3
1.4 Power Connections . . . . . . . . . . . . . . . . . 3
1.5 Signal connections - Pt100 / RTD . . . . . . . . . 3
1.6 Signal connections - Thermocouples . . . . . . . . 3
1.7 Technical data. . . . . . . . . . . . . . . . . . . . 4
1.7 Technical data (cont.) . . . . . . . . . . . . . . . . 4
1.8 Mechanical dimensions (mm). . . . . . . . . . . . 5
1.9 Operating the menus . . . . . . . . . . . . . . . . 6
1.10 Configuration menu . . . . . . . . . . . . . . . . 6
1.10 Configuration menu (cont.) . . . . . . . . . . . . 7
1.10.1 Input menu . . . . . . . . . . . . . . . . . . . 8
1.10.2 Temperature configuration . . . . . . . . . . . 8
1.10.3 Alarms . . . . . . . . . . . . . . . . . . . . . 8
1.10.4 Display . . . . . . . . . . . . . . . . . . . . . 8
1.10.5 Tools . . . . . . . . . . . . . . . . . . . . . . 8
1.10.6 Menu OptX - Options. . . . . . . . . . . . . . 9
1.11 Default factory configuration. . . . . . . . . . . . 9
1.12 Messages and errors . . . . . . . . . . . . . . . 9
1.13 Information menu . . . . . . . . . . . . . . . . 10
1.13.1 Information menu . . . . . . . . . . . . . . 10
1.14 Accessing the instrument . . . . . . . . . . . . 10
1.15Warranty . . . . . . . . . . . . . . . . . . . . . 11
1.16 Installation precautions . . . . . . . . . . . . . 11
1.17 CE declaration of conformity . . . . . . . . . . 11
2. Output and control modules . . . . . . . . . . . . . 12
2.1 Module R1 . . . . . . . . . . . . . . . . . . . . 12
2.2 Module AO . . . . . . . . . . . . . . . . . . . . 12
2.3 Modules R2, R4. . . . . . . . . . . . . . . . . . 13
3. More options and accessories . . . . . . . . . . . . 14
3.1 Option G . . . . . . . . . . . . . . . . . . . . . 14
FEMA ELECTRÓNICA - Page 2
User’s Manual S40-T
1.2 Front View
Logo
Alarms
User’s Manual S40-T
1.5 Signal connections - Pt100 / RTD
Measure can be selected for 2 or 3 wire systems.
1 2 3 4 5
Select input Pt100 2Wires in the menu. Terminal 2 can be left unconnected.
RTD/Pt100
2 wires
Units
1 2 3 4 5
Button LE
Button UP
Access to
“Information Menu”
Button SQ
Access to
“Configuration Menu”
Select input Pt100 3Wires in the menu
RTD/Pt100
3 wires
1.3 Rear View
Option1 Option2
1.6 Signal connections - Thermocouples
To configure, select the appropriate thermocouple type in the configuration menu.
1 2 3 4 5
+
-
Thermocouple
Signal
1.4 Power Connections
6 7 8 9 0
Power
~ +
~
-
Earth connection - Although a terminal is offered for earth connection, the connection is optional. The instrument does not need this connection for correct functioning nor for compliance with the security regulations.
Fuse - To comply with security regulation 61010-1, add to the power line a protection fuse acting as disconnection element, easily accessible to the operator and identified as a protection device.
Power “H” fuse 250mA time-lag
Power “L” fuse 400mA time-lag
FEMA ELECTRÓNICA - Page 3
User’s Manual S40-T
1.7 Technical data
Digits 4
Type
Height
Display maximum
Display minimum
Decimal point
Overrange
Underrange
7 segments, red
14 mm
9999
-1999 selectable 8.8.8.8.
9999 flashing
-1999 flashing
1.7 Technical data (cont.)
Power
Power “H”
Power “L”
85 to 265 Vac/dc
11 to 60 Vdc and 24/48Vac
Consumption <4W
Isolation 3500Veff for power “H”
2000Veff for power “L” all levels tested for 60 seconds
Signals accepted
Temperature scale
Display units
Thermocouple data
Thermocouples accepted J, K, T, E, S, R, N, C, L, X
(Thermocouple X is a linear 10uV/ºC signal)
Resolution 1º
Ranges
Max. error at 25ºC
Offset drift
Span drift*
CJC
CJC accuracy
CJC thermal drift
On sensor break
Acquisitions
Pt100/RTD and Thermocouples
ITS90
ºC or ºF, selectable see table 3 see table 3 see table 3 see table 3
*Note - span drift includes also the offset drift
automatic (“On”/“Off” selectable)
<1.0ºC
<0.04º/ºC
“to_high” or “to_low”, selectable
3 acquisitions / second
Configuration
Functions available
Steps
Memory of maximum
Memory of minimum
Password
Double setpoints
Brightness control
3 frontal push buttons yes, configurable yes yes yes, configurable yes yes, 5 levels
Options maximum 2
Mechanical
Mounting panel
Connections
Weight
Housing materials
Front size
Panel cut-out
Deep from panel plug-in screw terminals
<150 grams
ABS, polycarbonate, vergaflex
72x36mm
69x32.5mm
98mm (including terminal)
Pt100/RTD data
Sensors accepted
Resolution
Ranges
Alpha
Max. error at 25ºC
Offset drift
Span drift *
2 or 3 wire, selectable
1º or 0.1º, selectable
see table 3
Alpha385 or Alpha390, selectable see table 3 see table 3 see table 3
*Note - span drift includes also the offset drift
Cable compensation up to 14 Ohm
Compensation accuracy <0.02ºC / Ohm
Acquisitions 4 acquisitions / second
Front protection IP54
Temperature Operation 0 to 50ºC
Temperature Storage –20 to +70ºC
Warm-up 15 minutes
Type Range ºC
Pt100/RTD
800 / -200 ºC
Thermocouple J
1200 / -200 ºC
Thermocouple K
1372 / -200 ºC
Thermocouple T
400 / -200 ºC
Thermocouple E
1000 / -200 ºC
Thermocouple S
1768 / -50 ºC
Thermocouple R
1600 / -50 ºC
Max. error at 25ºC*
<0.2ºC
<2ºC
<2ºC
<2ºC
<2ºC
<4ºC
<4ºC
Range ºF
1562 / -328 ºF
2192 / -328 ºF
2372 / -328 ºF
752 / -328 ºF
1832 / -328 ºF
2282 / -58 ºF
2912 / -58 ºF
Thermocouple N
1300 / -200 ºC
Thermocouple C
2320 / 0 ºC
Thermocouple L
900 / -200 ºC
Thermocouple X
4000 / -200 ºC
<2ºC
<2ºC
<2ºC
<2ºC
2372 / -328 ºF
4192 / 32 ºF
1652 / -328 ºF
7232 / -328 ºF
Table 3 - Thermocouple and PT100/RTD specifications
Offset drift
0.05º/ºC
0.05º/ºC
0.05º/ºC
0.02º/ºC
0.05º/ºC
0.20º/ºC
0.20º/ºC
0.05º/ºC
0.02º/ºC
0.05º/ºC
0.02º/ºC
Span drift*
*includes offset drift
0.10º/ºC
0.20º/ºC
0.20º/ºC
0.02º/ºC
0.20º/ºC
0.20º/ºC
0.20º/ºC
0.20º/ºC
0.02º/ºC
0.20º/ºC
0.02º/ºC
FEMA ELECTRÓNICA - Page 4
User’s Manual S40-T User’s Manual S40-T
1.8 Mechanical dimensions (mm)
36
72
32,5
Panel cut-out
69
18
80
8
T h i s
s e c t i o n b l a n k
FEMA ELECTRÓNICA - Page 5
User’s Manual S40-T
1.9 Operating the menus
The instrument has two menus accessible to the user :
“Configuration Menu” (key SQ)
“Information Menu” (key UP)
The “Configuration Menu” allows to change the configuration of the instrument. Access to the “Configuration Menu” can be password protected with the function “PASSWORD”. During operation with the “Configuration Menu” the alarms are kept
“on-hold”. When leaving the “Configuration Menu” the instrument performs a restart, and new configuration is applied. On restart of the instrument, also the control output modules are restarted (relays, analogue outputs, ...).
1.10 Configuration menu
Input
Press SQ button to enter Configuration Menu
Pt100/RTD 2 wires
Pt100/RTD 3 wires
Thermocouple J
Thermocouple K
Thermocouple T
Thermocouple E
Thermocouple S
The “Information Menu” is for information only, and it does not accept changes on the displayed information. To enter the “In-
formation Menu” press the “UP” button. It is not affected by the “PASSWORD” function. Leaving the “Information Menu” returns to the measuring state of the instrument, without restart of the unit.
Thermocouple R
Thermocouple N
Thermocouple C
Thermocouple L
Rollback - After 30 seconds without interaction from the operator, the instrument leaves the menu and returns to the previous working mode. In case of configuration menu, all changes are discarded.
Thermocouple X
Button SQ - Selects the menu entry currently displayed.
When entering a numeric value (for example a setpoint value) validates the value on display.
Temp. Config,
Button UP - Moves vertically on the menu entries. When entering a numeric value (for example a setpoint value) modifies the current digit by increasing its value up from 0 to
1, 2, 3, 4, 5, 6, 7, 8, 9.
Button LE - Leaves the current menu. Pressing LE several times will leave all menus. When leaving all menus in the configuration menu, changes will be saved . When entering a numeric value (for example a setpoint value) it moves from one digit to the next. Each digit value can then be modified with the UP button.
Degrees
Pt100/RTD res..
Offset
Celsius
Fahrenheit
1º Resolution
0.1º Resolution
Offset counts to add
Thermoc. CJC
On break
Reading to high
Reading to low
Alpha
FEMA ELECTRÓNICA - Page 6
User’s Manual S40-T User’s Manual S40-T
1.10 Configuration menu (cont.)
Alarms
Alarm1
Active
Al. active
Al. inactive
Tools
Password
Factory configuration
Alarm type
Alarm as max.
Alarm as min.
Version
Setpoint
Hysteresis
Delay
Setpoint2
Counts
Seconds
Brightness
Menu for Alarm2
Second setpoint
Menu for optional module at Opt1
Option1
Option2
Menu for optional module at Opt2
Select password
Apply
Firmware version
Minimum
Standard
Maximum
Display
Steps
Memory of maximum
Memory of minimum
Counts for step
Value
Reset
Value
Reset
FEMA ELECTRÓNICA - Page 7
User’s Manual S40-T
1.10.1 Input menu
The input menu selects the input signal range. Options available are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T,
E, S, R, N, C, L and X.
Note - Thermocouple X is a linear signal at 10uV/ºC.
1.10.2 Temperature configuration
The temperature configuration menu sets the function parameters for Pt100/RTD and thermocouple sensors.
Degrees (DEG) - Value “ºC/ºF”. Select the temperature to be displayed in celsius or fahrenheit degrees.
Pt100/RTD resolution (P.RES) - Value “1º/0.1º”. Resolution for the Pt100/RTD. Select to display with degree or tenth of degree resolution.
Offset (OFFS) - Value from “-9999” to “9999” counts. Offset to be added to the reading. Both for Pt100/RTD and thermocouples.
Thermocouple Cold Junction Compensation (T.CJC) -
Value “On/Off”. Select “On” for automatic CJC compensation in the instrument. Select “Off” to disable the CJC compensation.
On break (ON.BK) - Value “to_h/to_l”. Select “To L” to make the reading go to minimum, in case of probe broken. Select
“To H” to make the reading go to maximum in case of probe broken.
Alpha (ALPH) - Value “385/390”. Select “385” or “390” according to your Pt100/RTD sensor.
Delay (DEL) - Value from “0.0” to “99.9” seconds. Delay to be applied to the relay activation and deactivation. Relays are activated and deactivated X seconds after the activation / deactivation of the alarm. The delay affects only to the relays.
The delay does not affect to the front leds.
Setpoint2 (SET2) - Value from “-1999” to “9999”. Second setpoint. The second setpoint allows for the creation of activation windows. If the alarm is configured as maximum with setpoint 1000 and setpoint2 is configured at 1500, the alarm will be activated between 1000 and 1500 and the alarm will be deactivated when display is <1000 and >1500. Setpoint2 is affected on the same way as the setpoint with hysteresis and delays.
1.10.4 Display
Functions on this menu allow for configuration of the visualization.
Steps (STEP) - Display changes on predefined steps. Values are 1, 2, 5, 10, 20 and 50. The display is made in steps of X counts. For example, select a step of 20 will make the display to change in steps of 20 (1420, 1440, 1460, ...).
Maximum (MAX) - Memory of maximum display. Indicates the maximum value of display since the last reset of the memory. Memory is reset on the following cases : manual reset from the Configuration Menu (Maximum), change on the input signal (Input), modification on the scaling (Scaling), change on the decimal point (dP), modification of the linearization segments, or instrument power-down.
Minimum (MIN) - Memory of minimum display. Indicates the minimum value of display since the last reset of the memory.
Memory is reset on the following cases : manual reset from the Configuration Menu (minimum), change on the input signal (Input), modification on the scaling (Scaling), change on the decimal point (dP), modification of the linearization segments, or instrument power-down.
1.10.3 Alarms
The instrument can manage up to 2 alarms. These alarms control optional relays R1 (see section 2.1) which can be installed at slots Opt1 and Opt2. More alarms can be achieved by installing special control modules R2 and R4. Configuration menus for special modules are not listed in this document.
Active (ACT) - Value “ON/OFF”. Defines if the instrument has to manage this alarm or not. Select “OFF” for alarm not managed.
Type (TYPE) - Value “MAX/MIN”. Defines the behavior of the alarm as maximum or minimum alarm. The alarms configured as maximum are activated when the display value is equal or higher than the setpoint. The alarms configured as maximum are deactivated when the display is lower than the setpoint.
The alarms configured as minimum have the inverse behavior.
Setpoint (SET) - Value from “9999” to “-1999”. Alarm set point.
Hysteresis (HYST) - Value from “0” to “9999”. Points of hysteresis. The hysteresis applies on the deactivation of the alarm.
1.10.5 Tools
Password (PASS) - Select a number to act as password. This password will be requested when entering the Configuration
Menu. To deactivate the password select “Off”.
Factory Settings (FACT) - Factory default configuration.
Select “yES” to activate the factory default configuration.
Version (VER) - Firmware version installed.
Light (LIGH) - Luminosity. Select between 5 predefined levels of luminosity.
FEMA ELECTRÓNICA - Page 8
User’s Manual S40-T User’s Manual S40-T
1.10.6 Menu OptX - Options
Menu options OPT1 and OPT2 give access to the configuration menus of the options installed at slots Opt1, Opt2 and
Opt3. This menu depends on the installed option. If there is no option installed the instrument shows “NONE”. Control modules R1 are controlled from the standard alarm menu
(see section 1.12.7).
1.11 Default factory configuration
Sensor Pt100 2Wire
Degrees ºC
Resolution 0.1º
Offset 0
On Break To high
Alpha 385
Alarms 1 and 2
Active
Type
Setpoint
Hysteresis
Delay
Setpoint2
Display
Off (not managed) maximum
1000
0 counts
0.0 seconds
Off
Steps Off
Memory of maximum -1999
Memory of minimum 9999
Tools
Password
Brightness
Off
3
1.12 Messages and errors
When the instrument detects that the displayed value does not correspond to the input value, the display will flash and alternate with a message.
“ h.udr” Hardware underrange. The thermocouple signal is lower than minimum readable signal (-30mV).
“ h.oVr” Hardware overrange. The thermocouple signal is higher than maximum readable signal (80mV).
“ d.udr” Display underrange. The Pt100/RTD is shortcircuited.
“ hoLd” The instrument is showing the value present when the hold function was activated. Hold function is active.
“ Min” The instrument displays the minimum displayed value in memory. The minimum visualization is active.
“ MAX” The instrument displays the maximum displayed value in memory. The maximum visualization is active.
“ brk” The instrument displays “brk” with either “9999” or
“-1999” when : 1) resistance measured is higher than 390
Ohms (higher than 850ºC for PT100/RTD measure), or 2) in case the third wire ohm is higher than 15 Ohm, or 3) thermocouple measure is open circuit.
“ Err.1” Password incorrect.
“ Err.2” The instrument has detected an installed option but was unable to communicate.
“ E.101” Option is installed but the type can not be recognized.
FEMA ELECTRÓNICA - Page 9
1.13 Information menu
Press UP button to enter Information Menu
Configuration
Maximum
Minimum
Alarm1
Sensor type
ºC or ºF
Hysteresis
Delay
Setpoint2
Memory of maximum
Memory of minimum
“On / Off”
“Max” / “Min”
Setpoint
User’s Manual S40-T
Counts
Seconds
Second setpoint
1.13.1 Information menu
Configuration (Conf) - Information on the configured input sensor and the degrees selected.
Maximum (MAX) - Value of the maximum display.
Minimum (MIn) - Value of the minimum display.
AlarmX (ALX) - Configuration of alarm X. The sequence of information shows if the alarm is being managed (“On/Off”), the alarm type (“Max/Min”), the setpoint, the hysteresis value, the activation delay and the value of setpoint2 (“Off” or the setpoint2 value).
OptionX (OptX) - Type of module installed. If there is no module shows “nonE”.
1.14 Accessing the instrument
You may need to access the inside of the instrument to insert additional modules. Use a flat screwdriver to unlock the upper clips marked with “A”. Then unlock the lower clips marked with “B” and move out the front filter. Let the inside of the instrument slide out of the housing.
To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module. Place all the set into the housing, assuring that the modules correctly fit into the internal guiding slides of the housing. Once introduced, place again the front filter by clipping first the upper clips “A” and then the lower clips “B”.
Option1
Option2
See menu for Alarm1
Option installed
Option installed
A
B
Risk of electric shock. Removing the front cover will grant access to the internal circuits. Disconnect the input signal to prevent electric shock to the operator.
Operation must be performed by qualified personnel only.
FEMA ELECTRÓNICA - Page 10
User’s Manual S40-T User’s Manual S40-T
1.15Warranty
All instruments are warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date.
This warranty does not apply in case of misuse, accident or manipulation by non-authorized personnel. In case of malfunction get in contact with your local provider to arrange for repair. Within the warranty period and after examination by the manufacturer, the unit will be repaired or substituted when found to be defective. The scope of this warranty is limited to the repair cost of the instrument, not being the manufacturer eligible for responsibility on additional damages or costs. .
1.16 Installation precautions
Risk of electrical shock. Instrument terminals can be connected to dangerous voltage.
Instrument protected with double isolation. No earth connection required.
Instrument is in conformity with CE rules and regulations. See
“CE Declaration of Conformity” further in this document.
This instrument has been designed and verified according to the 61010-1
CE security regulation, and is designed for applications on industrial environments. See the “CE Declaration of Conformity” further in this document for information on the category of measure and the degree of pollution levels that apply.
Installation of this instrument must be performed by qualified personnel only. This manual contains the appropriate information for the installation.
Using the instrument in ways not specified by the manufacturer may lead to a reduction on the specified protection level. Disconnect the instrument from power before starting any maintenance and / or installation action.
The instrument does not have a general switch and will start operation as soon as power is connected. The instrument does not have protection fuse, the fuse must be added during installation.
The instrument is designed to be panel mounted. An appropriate ventilation of the instrument must be assured. Do not expose the instrument to excess of humidity. Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents, etc.
General recommendations for electrical installations apply, and for proper functionality we recommend : if possible, install the instrument far from electrical noise or magnetic field generators such as power relays, electrical motors, speed variators, ... If possible, do not install along the same conduits power cables (power, motor controllers, electrovalves, ...) together with signal and/or control cables.
Before proceeding to the power connection, verify that the voltage level available matches the power levels indicated in the label on the instrument.
In case of fire, disconnect the instrument from the power line, fire alarm according to local rules, disconnect the air conditioning, attack fire with carbonic snow, never with water.
1.17 CE declaration of conformity
Manufacturer FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 - Barberà del Vallès
BARCELONA - SPAIN www.fema.es - [email protected]
Products S40-T
The manufacturer declares that the instruments indicated comply with the directives and rules indicated below.
Electromagnetic compatibility directive 2004/108/CE
Low voltage directive 2006/95/CE
Security rules EN-61010-1
Instrument Fixed
Permanently connected
Pollution degree 1 and 2 (without condensation)
Isolation Double
Category CAT-II
Electromagnetic compatibility rules EN-61326-1
EM environment Industrial
Immunity levels
EN-61000-4-2 By contact ±4 KV
By air ±8 KV
EN-61000-4-3
EN-61000-4-4 On AC power lines : ±2 KV
On DC power lines : ±2 KV
On signal lines : ±1 KV
Criteria B
Criteria B
Criteria B
EN-61000-4-5 Between AC power lines ±1 KV Criteria B
Between AC power lines and earth ±2 KV Criteria B
Between DC power lines ±1 KV
Between signal lines and earth ±1 KV
Criteria B
Between DC power lines and earth ±2 KV Criteria B
Criteria B
EN-61000-4-6
EN-61000-4-8 30 A/m at 50/60 Hz
EN-61000-4-11 0 % 1 cycle
40 % 10 cycles
70 % 25 cycles
0 % 250 cycles
Emission levels
CISPR 11 Instrument Class A, Group 1
Criteria B
Criteria B
Criteria A
Criteria A
Criteria A
Criteria A
Criteria A
Criteria B
Criteria B
Criteria A
Barberà del Vallès November 2014
Daniel Juncà - Quality Manager
According to directive 2012/19/EU, electronic equipment must be recycled in a selective and controlled way at the end of its useful life.
FEMA ELECTRÓNICA - Page 11
User’s Manual S40-T
2. Output and control modules
2.1 Module R1 2.2 Module AO
Module with 1 relay. Up to a maximum of two R1 modules can be installed in one S Series panel meter. For more relay output needs, check special modules R2 and R4. For more information see document 2657_S40_OPTIONAL_MOD-
ULES at www.fema.es
Relay type
Maximum current
Voltage
Installable at
3 contacts (Common, NC, NO)
8A (resistive load)
250 Vac continuously
Option1 and/or Option2
Module with 1 analogue output. Configurable 4/20mA or
0/10Vdc. Output signal proportional to the reading. Scaling through the frontal keypad. Up to a maximum of two AO modules can be installed in one S Series panel meter. For more information see document 2657_S40_OPTIONAL_
MODULES at www.fema.es
Output
Accuracy
Isolated
Thermal drift
Installable at
4/20mA, 0/10Vdc selectable
0.1% FS yes, 1000Vdc
50 ppm/ºC for Vdc
60 ppm/ºC for mA
Option1 and/or Option2
Opt 1
A B C
Opt 2
A B C
Opt 1
M V A B C
Opt 2
M V A B C
Signal
Terminal A
Terminal B
Terminal C
Power
Common
NO - Normally Open
NC - Normally Closed
Signal
Jumper M
Jumper V
Terminal A
Terminal B
Terminal C
Power
mode mA mode Vdc
Vexc (+13.8Vdc @25mA)
Signal output (mA or Vdc)
GND
FEMA ELECTRÓNICA - Page 12
User’s Manual S40-T User’s Manual S40-T
2.3 Modules R2, R4
Special modules with 2 and 4 relays. Use special modules
R2 or R4 when standard R1 modules do not provide required functionality for your application. Only one special module R2 or R4 can be installed in an S Series panel meter. Special modules R2 and R4 are not compatible with R1 modules.
Configuration is done through the OPTx entry of the configuration menu. Functionality for R2 and R4 modules differs from standard R1 modules. For more information see document 2657_S40_OPTIONAL_MODULES at www.fema.es
R2
Opt 1
A B C D E F
Signal
R4
Number of relays
Relay type
Maximum current
Voltage*
Installable at slot
Terminal
2, or 4
3 contacts (Common, NO, NC)
6A (resistive load) (each relay)
250 Vac continuously
Opt.1.
R2 fills OPT1
R4 fills OPT1 and OPT2
Plug-in screw terminals pitch 3.81mm
* Terminals approved for 300V (according to UL1059, groups B and D) and 160V (according to VDE in CAT-III and pollution degree 3).
Terminal A
Terminal B
Terminal C
Terminal D
Terminal E
Terminal F
Terminal G
Terminal H
Terminal I
Terminal J
Terminal K
Terminal L
Opt 2
G H I J K L
Power
Relay1 Common
Relay1 NO - Normally Open
Relay1 NC - Normally Closed
Relay2 Common
Relay2 NO - Normally Open
Relay2 NC - Normally Closed
Relay3 Común
Relay3 NO - Normally Open
Relay3 NC - Normally Closed
Relay4 Common
Relay4 NO - Normally Open
Relay4 NC - Normally Closed
FEMA ELECTRÓNICA - Page 13
User’s Manual S40-T
3. More options and accessories
3.1 Option G
Green led option.
Green led
FEMA ELECTRÓNICA - Page 14
User’s Manual S40-T User’s Manual S40-T
T H
I S
P
A G
E
B L
A N
K
FEMA ELECTRÓNICA - Page 15
other products
Panel Meters
Standard 96x48mm
Panel Meters
Small 72x36mm
Panel Meters
Miniature 48x24mm
Bar Meters Large Displays
60&100mm digit
Signal Converters
& Isolators
www.fema.es
ELECTRONIC INSTRUMENTATION FOR INDUSTRY
FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 Barberà del Vallès
BARCELONA - SPAIN
Tel. (+34) 93.729.6004 - www.fema.es
Fax (+34) 93.729.6003 - [email protected]
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 1. Meter S40-T
- 2 1.1 Order reference
- 3 1.2 Front View
- 3 1.3 Rear View
- 3 1.4 Power Connections
- 3 1.5 Signal connections - Pt100 / RTD
- 3 1.6 Signal connections - Thermocouples
- 4 1.7 Technical data
- 4 1.7 Technical data (cont.)
- 5 1.8 Mechanical dimensions (mm)
- 6 1.9 Operating the menus
- 6 1.10 Configuration menu
- 7 1.10 Configuration menu (cont.)
- 8 1.10.1 Input menu
- 8 1.10.2 Temperature configuration
- 8 1.10.3 Alarms
- 8 1.10.4 Display
- 8 1.10.5 Tools
- 9 1.10.6 Menu OptX - Options
- 9 1.11 Default factory configuration
- 9 1.12 Messages and errors
- 10 1.13 Information menu
- 10 1.13.1 Information menu
- 10 1.14 Accessing the instrument
- 11 1.15Warranty
- 11 1.16 Installation precautions
- 11 1.17 CE declaration of conformity
- 12 2. Output and control modules
- 12 2.1 Module R
- 12 2.2 Module AO
- 13 2.3 Modules R2, R
- 14 3. More options and accessories
- 14 3.1 Option G