Schneider Electric TSXSCG1131/1161 Modbus protocol module User Guide
ಜಾಹಿರಾತು
ಜಾಹಿರಾತು
________________________________________________________
Contents
___________________________________________________________________________
1 Modbus ® Protocol
Page
3
1.2 Description of the Modbus Protocol
1.3 Principle of the Modbus ® Exchanges
______________________________________________________________________________________
Management of the Protocol
2.1 Images of Modbus Data Objects
7
______________________________________________________________________________________
Hardware Implementation 21
______________________________________________________________________________________
Programming the Module as a Slave 25
______________________________________________________________________________________
Programming the Module as a Master 37
___________________________________________________________________________
1
________________________________________________________
Contents
___________________________________________________________________________
Discrete Bits and Registers
Page
53
______________________________________________________________________________________
Additional Programming Information 59
______________________________________________________________________________________
Programming Examples 61
______________________________________________________________________________________
Appendix 69
___________________________________________________________________________
2
________________________________________________________
Modbus ® Protocol Section 1
___________________________________________________________________________
1.1
Definition of a Protocol
Page
4
4
4 1.1-2 The Modbus Frame
_______________________________________________________________________________________
1.2
Description of the Modbus ® Protocol 5
5
_______________________________________________________________________________________
1.3
Principle of the Modbus ® Exchanges 6
6
___________________________________________________________________________
3
_______________________________________________________________________________________
1.1
Definition of a Protocol
1.1-1 General
Data must be exchanged in a common language between computer systems, programmable logic controllers (PLC) and other intelligent systems. This language must be as simple as possible and understood by each subscriber; nonetheless each exchange must be checked to ensure the transfer is correct. The exchanged variables are enclosed in a frame generally structured as follows:
Header ":" Address Request Data Check End
Each protocol defines the presence, format and contents of the different groups of variables enclosing the data zone.
This structure permits the definition of the start of the message, the message length, the system to which the data is being sent (if required), the type of function requested, the variables, a check parameter and an end of message code that validates the entire message.
However, the contents and structure of the frame are different for each type of protocol.
____________________________________________________________________
1.1-2 The Modbus ® Frame
In the Remote Terminal Unit (RTU) mode, the frame of the Modbus ® protocol has no header nor end of message code, it is therefore composed as follows :
Address Request Data CRC 16
CRC 16 : Cyclic Redundancy Check.
In the ASCII mode, the frame of the Modbus ® protocol is complete and is composed as follows :
Header ":" Address Request
LRC : Longitudinal Redundancy Check,
CR : Carriage Return,
LF : Line Feed.
Data LRC End "CR LF"
___________________________________________________________________________
4
Modbus ® Protocol 1
_______________________________________________________________________________________
1.2
Description of the Modbus
®
Protocol
1.2-1 Principle
The Modbus ® protocol creates a hierarchical system of dialogue between ONE master and several slaves.
The Modbus ® protocol allows the master to poll one or more intelligent slaves connected by a common multipoint link.
Two types of dialogue are possible between the master and the slaves:
. The master interrogates a slave and waits for its reply,
. The master broadcasts information to all the slaves and does not wait for a reply.
The exchange of data is initiated and controlled by the master, which interrogates each slave in turn to see if it has data to transmit. If the slave does not respond within a specific time, the master considers that the slave is absent and goes on to interrogate the next slave. Only one device can transmit data on the line at a time, and the slaves cannot transmit without being invited to do so by the master.
Master
Slave i Slave j Slave k
The principle of the master/slave dialogue can therefore be schematized as a series of point-to-point links, with the master turning an imaginary selector switch to the number of each slave in succession, as shown below.
Master
Slave i Slave k Slave l
Slave-to-slave communication is therefore not possible unless the application software in the master is designed to allow the reception of data from one slave and its transmission to another slave.
___________________________________________________________________________
5
_______________________________________________________________________________________
1.3
Principle of the Modbus
®
Exchanges
1.3-1 Principle
The Modbus ® protocol permits and controls the exchange of data, in the form of bits and words, between the master and the slaves.
Bit memory zones and word memory zones must therefore be defined in each slave so that they can be read or written by the master.
Since the Modbus ® protocol is already defined, it is simply necessary to assign a
Modbus ® address to each data object (bit or word) so that they can be exchanged.
An input object (bit or word) can be read but not written.
An output object (bit or word) can be read or written.
Slave i
MASTER
Slave j
Input bits
Transmission table
P
U
R
S
O
E
G
R
R
A
M
Reception table
Output bits
Input words
Output words
Slave k
___________________________________________________________________________
6
________________________________________________________
Management of the Protocol Section 2
___________________________________________________________________________
2.1
Images of Modbus ® Data Objects
Page
8
_______________________________________________________________________________________
2.2
Master/Slave Exchanges 9
9
9
10
_______________________________________________________________________________________
2.3
Processor/Slave Exchanges 11
12
13
_______________________________________________________________________________________
2.4
Processor/Master Exchanges 13
14
14
_______________________________________________________________________________________
2.5
Functions performed by the Module 15
_______________________________________________________________________________________
2.6
Description of the Main Functions 16
16
16
_______________________________________________________________________________________
2.7
Description of the Complementary Functions 17
___________________________________________________________________________
7
_______________________________________________________________________________________
2.1
Images of Modbus
®
_____________________________________________________________________________________________________
Definition
The Modbus ® protocol defines four types of accessible data objects as follows:
●
●
●
●
Input bits,
Output bits,
Input words,
Output words.
Each slave device connected to a Modbus ® line has a number of objects of each type.
Within a given entity, all data objects are identified by consecutive addresses.
A TSX SCG 11 slave module converts the Modbus ® address into a memory address in the processor of the slave PLC.
The table of correspondence is established during the configuration of the slave module.
All the data objects that are accessible via Modbus ® are located in the internal word (Wi) zone of the slave PLC.
Bit Objects
For the bit objects, the slave module knows the address i of the internal word Wi containing the first bit, defined in position 0 (the bit concerned therefore has the image
Wi,0), and its corresponding Modbus ® address.
The Modbus ® address of the first bit configured must therefore correspond to the first bit (bit 0) of an internal word. The other bits follow in consecutive order.
Example : Input bits
Modbus ® addresses
0100
0101
...
0115
0116
Processor addresses
50
50
...
50
51
Processor objects
W50,0
W50,1
...
W50,F
W51,0
Physical objects
TXT1,D
T2,R
...
M3,S
I10,4
Word Objects
For the word objects, the slave module knows the address j of the first internal word Wj and its corresponding Modbus ® address. All the word o bjects are located in the internal word zone of the slave PLC.
Example : Input words
Modbus ® addresses
Processor addresses
Processor objects
Physical objects
8000
8001
8002
. . .
200
201
202
. . .
W200
W201
W202
. . .
IW2,1
TXT2,V
W202
. . .
___________________________________________________________________________
8
Management of the Protocol 2
_______________________________________________________________________________________
2.2
Master/Slave Exchanges
2.2-1 Principle and Checking of Exchanges
The master or supervision device initiates the exchanges. It interrogates a slave by transmitting a message containing four types of information :
●
●
●
●
The address of the slave,
The function requested,
The data zone (which varies according to the function requested),
The error check.
The master waits for the reply from the slave before sending the next message, thus avoiding any conflict of access to the line. This procedure therefore authorizes halfduplex operation.
The control of transfers between two entities dialoguing via an asynchronous serial link must obviously include exception responses when transfer faults occur. Incoherent replies may be received by the slave module, in which case the slave informs the master that it has not understood the message. The master then decides whether or not to repeat the message.
The error checking procedure is transparent to the user program of the slave, which is not informed of the errors detected and processed by its SCM module.
______________________________________________________________________
2.2-2 Monitoring of the slave
Master
Slave
The master can obtain access to certain information in the slave module by using special function codes, such as diagnostic mode and event counter read, that are restricted to exchanges between the master, TSX SCG 11 and slave.
___________________________________________________________________________
9
_______________________________________________________________________________________
The slave module uses counters to handle its exchanges with the master. The following number of messages are memorized:
●
●
●
●
●
Received on the line,
Received by the slave module with checksum error,
Transmitted by the module with an exception response code,
Received by the slave module,
Transmitted by the module to its processor without receiving a reply.
All these variables can be accessed by the master in a manner that is totally transparent to the user of the slave.
However, the user program of a slave PLC can also read these counters if required.
______________________________________________________________________
2.2-3 Monitoring of the master
Master
Slave
The counters of the master module can monitor :
. The exchanges between the master module and its processor,
. The exchanges between the master and the slaves.
These counters can be read by the user program of the master PLC by using the message mode (text function blocks).
The counters memorize the following information :
●
●
The number of processor requests received,
The number of processor requests refused.
The master module examines the processor request and transmits a refusal in the following cases :
- Slave address incorrect,
- Function number unknown,
- Function illegal in general broadcast mode,
- Number of objects to be accessed too high,
- Implicit length of the processor request incorrect.
●
●
●
The number of slave responses correctly received,
The number of slave responses received with an exception code,
The number of messages without reply from the slave (within the time delay),
●
The number of slave responses received with a checksum error,
●
The number of incoherent slave responses received.
___________________________________________________________________________
10
Management of the Protocol 2
_______________________________________________________________________________________
The master module examines the message received from the slave and declares it incoherent when :
- The message received is inconsistent with the request transmitted to the slave (the slave address, function number or number of objects is different),
- The implicit length of the message received is incorrect.
●
The master module reiterates the message to the slave in the following cases :
The message has not been replied to (within the configured delay),
The message has been received with a checksum error,
The message received is incoherent,
The message contains a reception fault.
●
●
●
The master module stops reiterating the message,
The permitted response time is exceeded during reception,
The replies from the slave are received with a reception fault.
_____________________________________________________________________
2.3
Processor/Slave Exchanges
Master
Slave
Asynchronous link
The processor of the slave PLC sets the TSX SCG 11 asynchronous link module to the reception mode for a message on the line. When a message is received from the master, the slave module analyzes the message and transmits it to the processor of the slave
PLC in the form of a request.
The user program of the slave PLC then performs the required operation (writing of tables, transfer of tables, etc.) and requests the transfer of the data to the coupler and its resetting to the reception mode after the data has been transmitted.
___________________________________________________________________________
11
_______________________________________________________________________________________
The slave module then replies asynchronously to the master by sending the following four types of information :
●
The number of the slave,
●
●
●
The type of function,
The data zone,
The error check.
The slave module is then reset to the reception mode and awaits a message from the master, so that the exchange cycle described above can be repeated.
_____________________________________________________________________
2.3-1 Method of exchange
Exchanges between the user program and the TSX SCG 11 module are made by means of a message mode (16 bit word table). The exchanges are programmed using text blocks. Four access codes, or requests, are required. The TSX SCG 11 module does not use the register interface.
PLC processor
TSX SCG module
Modbus line
®
Physical objects
User program
Accessible objects
User program
Standard interface
Modbus ® access processing
___________________________________________________________________________
12
Management of the Protocol 2
_______________________________________________________________________________________
2.3-2 Processing by the Slave Module and Processor
Slave Module
The module performs the following operations :
●
Reception and analysis of the messages from the master,
●
Conversion of the messages so the processor can understand:
The TSX SCG 11 module processes the Modbus ® data for access by transcribing the
Modbus ® addresses of the objects being accessed in the PLC internal addresses.
●
Conversion of the processor reply and addition of the check code.
●
Transmission of the message to the master.
Processor
The user program must therefore be designed to permit :
●
Reception of the requests received by the module via the message interface,
●
Access to the required data in the table of accessible objects,
●
If required, transfers between the table of accessible objects and the associated physical objects (counter values, time-outs, I/O modules, etc.).
________________________________________________________________________
2.4
Processor/Master Exchanges
Master
Slave
The processor of the master PLC has the initiative. It transmits a request to Channel 0 of the TSX SCG 11 module, which then transmits a message to the slave concerned.
This message contains the following four types of information :
●
The number of the slave,
●
●
●
The type of function requested,
The data zone,
The error check.
___________________________________________________________________________
13
_______________________________________________________________________________________
After receiving a reply from the slave, the master transmits to its processor :
●
●
A report of execution of the request,
The converted data received from the slave.
This ends the exchange cycle between the processor and the master module. The master module is then ready to process another request from its processor.
_________________________________________________________________________
2.4-1 Method of Exchange
The dialogue between the processor and the module takes place through the message interface. The request code is the same as the Modbus ® function code.
The data are exchanged between the processor and the module by means of transmission and reception tables associated with the text block.
_____________________________________________________________________
2.4-2 Processing by the Master Module and Processor
Master Module
The master module performs the following operations :
●
Checking of the validity of the processor request,
●
●
●
Conversion of the message to be transmitted to the slave,
Transmission of the message to the slave and reiteration if necessary,
Conversion of the slave’s reply for transmission to the processor.
Processor
The user program must therefore be designed to handle :
●
The information necessary for the exchange :
- The number of the slave,
- The Modbus ® function code,
- The Modbus ® addresses of the objects accessed,
- The values of the objects to be transferred.
●
●
The transmission of requests to access the module, by the transmission of text blocks,
The processing of the reply to the request.
___________________________________________________________________________
14
07
08
11
12
15
16
17
01
02
03
04
05
06
Management of the Protocol 2
_______________________________________________________________________________________
2.5
Functions performed by the Module
The TSX SCG 11 module performs the Modbus ® functions listed below. These are the only Modbus ® functions performed by the module and they are all detailed herein. Any other function that is requested will be rejected as "function code incorrect".
However, when the TSX SCG 11 module is used as a master, the request "Transparent
Modbus ® " permits the generation of any function number from 1 to 255. In this case, the user program sends to the module the whole of the message to be transmitted, except for the error code which is added by the module.
The Modbus ® functions comprise :
●
The main functions, which permit the exchange of a Modbus ® object,
●
The complementary functions, which are used by the master to obtain information about its slaves and to monitor the exchanges.
The TSX SCG 11 module can only be installed in a TSX 17-20 PLC. This results in a limitation due to the exchanges by text blocks (which in the case of a TSX 17-20 is limited to 30 bytes).
The maximum number of bits or words that can be exchanged is therefore given below.
The functions below (read, write, etc.) are seen from the master side.
The functions marked "B" can be broadcast to all the slaves.
Code Function Broadcast Maximum number
TSX 17-20
208
208
14
14
Read N output bits
Read N input bits
Read N output words
Read N input words
Write an output bit
Write an output word
Read exception status register
Diagnostics
Read events counter
Read events log
Write N output bits
Write N output words
Read slave identification
B
B
B
B
144
10
___________________________________________________________________________
15
_______________________________________________________________________________________
2.6
Description of the Main Functions
2.6-1 Read
Read N Output Bits
Code : 01
This function allows the master to read the status of the output bits in the memory of the slave. The bits can be read or written.
Read N Input Bits
Code : 02
Identical to the previous function and with the same limits, this function processes the input bits. These bits can only be read by the master.
Read N Output Words
Code : 03
This function allows the master to read the output words in the memory of the slave. The words can be read or written.
Read N Input Words
Code : 04
Identical to the previous function and with the same limits, this function processes the input words. The words can only be read by the master.
_____________________________________________________________________
2.6-2 Write
Write an Output Bit
Code : 05
This function allows the master to set an output bit to 0 or 1 in the memory of the slave.
The bits can only be written.
Write an Output Word
Code : 06
This function allows the master to write a word of 16 output bits in the memory of the slave. The bits can only be written.
Write N Output bits
Code : 15
This function allows the master to write the output bits in the memory of the slave. The bits can be read or written.
Write N Output words
Code : 16
This function allows the master to write the output words in the memory of the slave. The words can be read or written.
___________________________________________________________________________
16
Management of the Protocol 2
_______________________________________________________________________________________
2.7
Description of the Complementary Functions
Read Exception Status Register
Code : 07
This function allows the master to read 8 status bits containing the record of certain events which have occurred in the slave.
If the slave is a TSX PLC, the exception status contains the high order bits of the output register word OWx,3. The assignment of these bits is defined by the user.
Echo Check
Code : 08/00
This function returns to the master, for checking purposes, the full message received by the slave.
Restart Communication
Code : 08/01
This function reinitializes the communication channel. Any messages in progress on the channel are cancelled, but the configuration of the channel is preserved.
Read Diagnostic Register
Code : 08/02
This function allows the master to read a 16-bit word containing information concerning the status of the slave. If the slave is a TSX PLC, the structure of the status word is as follows :
●
●
Bit 0 = Slave in PWF (Power Failure) mode,
Bit 1 = not significant,
●
●
Bit 2 = Slave in LOM (Listen Only) mode.
The other bits are not significant.
Change ASCII Separator
Code : 08/03
In the ASCII mode, each byte is replaced by two ASCII characters coded in hexadecimal.
The successive messages are delimited by a separator character initially set to H’0A’
(Line Feed). This function (08/03) allows the separator to be changed to any other character.
This function is not available in the master module.
Force to Listen Only Mode (LOM)
Code : 08/04
This function forces the slave to the Listen Only Mode (LOM).
In this mode, the slave receives all the messages that are addressed to it, but cannot reply.
If the slave is a TSX PLC, the change to the Listen Only Mode is indicated to the processor by bit 2 of the register IWx,1.
Reset Counters
Code : 08/0A
This function resets all the slave’s communication monitoring counters to zero, and also the diagnostic register.
However, if the slave is a TSX PLC, the diagnostic word is not reset to zero.
___________________________________________________________________________
17
_______________________________________________________________________________________
Read Line Message Counter
Code : 08/0B
This function allows the master to read the contents of a 16-bit counter (incremented from 0 to FFFF) which totalizes the number of messages the slave has received on the line and processed.
Read Checksum Error Counter
Code : 08/0C
This function allows the master to read the contents of a 16-bit counter which totalizes the number of messages the slave has received on the line with a checksum error.
Read Exception Error Counter
Code : 08/0D
This function allows the master to read the contents of a 16-bit counter which totalizes the number of replies containing an exception error code that the slave has sent to the master (after reception of a message with incorrect contents).
Read Slave’s Message Counter
Code : 08/0E
This function allows the master to read the contents of a 16-bit counter which totalizes the number of messages that have been addressed to the slave (irrespective of the type of message).
Read Slave’s No Reply Counter
Code : 08/0F
This function allows the master to read the contents of a 16-bit counter which totalizes the number of times the processor of the slave has failed to reply to a request.
Read Event Counter
Code : 11
This function allows the master to read :
●
● a 16-bit status word a 16-bit event counter.
If the slave is a TSX PLC, the status is always set to zero, whereas the event counter is incremented for every message (form and contents) that is correctly received by the slave, excluding exception responses and read counter requests.
Read Event Log
Code : 12
This function allows the master to read :
●
The status word and event counter (identical to Code 11 above) of the slave,
●
●
The number of messages received on the line and processed by the slave (identical to Code 08/0B above),
The contents of the trace buffer (30 bytes maximum).
If the slave is a TSX PLC, the trace buffer is a LIFO stack containing a maximum of 30 bytes (or the number of updated bytes). The bytes are entered in chronological order.
The last byte received is the first to be transmitted (i.e. LIFO : Last In First Out).
___________________________________________________________________________
18
Management of the Protocol 2
_______________________________________________________________________________________
The trace buffer bytes may be of four types :
●
Slave receive, the byte is updated when a message is received by the slave and before it is processed :
7 6 5 4 3 2 1 0
1 x x 0 0 0 x 0
Bit 1 = 1 if communication error,
Bit 5 = 1 if in listen only mode (LOM),
Bit 6 = 1 if the message is being broadcast.
●
Slave send, the byte is updated at the end of transmission of a response, or at the end of processing in the case of a listen only or broadcast message :
7 6 5 4 3 2 1 0
0 1 x 0 0 0 x x
Bit 1 = 1 if exception code 1, 2 or 3,
Bit 5 = 1 if exception code 4,
Bit 6 = 1 if in listen only mode (LOM).
●
Entered Listen Only Mode (Hexadecimal value = H’20').
●
Communication restart (Hexadecimal value = H’xx’).
Read Slave Identification
Code : 17
This function allows the master to obtain the following information from a slave :
●
●
● the identity of the slave, its operating status, the list of information concerning the status and configuration of the slave.
If the slave is a TSX PLC, the reply includes :
●
The type of the TSX PLC connected :
- Value H’17' for a TSX 17-20.
●
The operating status of the PLC :
- Value H’00' for PWF,
- Otherwise value H’FF’.
●
The list of Modbus ® objects configured, i.e. 8 words as follows :
- Number of output bits,
- Modbus ® address of the first output bit,
- Number of input bits,
- Modbus ® address of the first input bit,
- Number of output words,
- Modbus ® address of the first output word,
- Number of input words,
- Modbus ® address of the first input word.
___________________________________________________________________________
19
_______________________________________________________________________________________
___________________________________________________________________________
20
________________________________________________________
Hardware Implementation Section 3
___________________________________________________________________________
3.1
Hardware Description
Page
22
_______________________________________________________________________________________
3.2
Installation of the Module 22
_______________________________________________________________________________________
3.3
Connection 23
23
23
___________________________________________________________________________
21
_______________________________________________________________________________________
3.1
Hardware Description
The TSX SCG 1131 and TSX SCG 1161 Modules comprise the following elements:
1
A grounding terminal,
2 A 15-pin connector for connection to the Modbus ®
3 Two LEDs:
link,
● a green RUN LED (module power is on and module is operating),
● a red I/O LED (I/O bus fault),
The NET and ADR LEDs are not used for the Modbus ® protocol.
4 A cable and a 9-pin connector for connecting to the preceding module
(TSX 17 bus),
5
A 9-pin connector for connecting to the next module (TSX 17 bus).
Module configuration code: 63.
1
2
3
5
4
____________________________________________________________________
3.2
Installation of the Module
The TSX SCG 11 module can only be used with a TSX 17-20 PLC, fitted with a
TSX P 17 20 FC cartridge (without time/date clock) or FTX P17 20 FD (with time/date clock).
The TSX SCG 11 module is connected to the basic PLC or to the preceding extension block (connection to the bus) by the module's integral cable. This means that the m odule is always on the right-hand side of these items.
The module may be installed in the first, second or third extension slot.
0
1 2 3
No more than two modules (TSX SCG 1131 or TSX SCG 1161) can be installed in a given TSX 17-20 PLC.
The last block or extension module in a configuration must be equipped with a line adaptor on its connector for connecting to the next module. This adaptor
(TSX 17 ACC10) is supplied separately.
___________________________________________________________________________
22
Hardware Implementation 3
_______________________________________________________________________________________
3.3
Connection
3.3-1 Connection of the TSX SCG 1131
The module permits connection in accordance with the RS 232C standard, extended for operation with a modem (9 signals).
The module is connected by a 15-pin female connector located on the top part of the module. The connector pin-out is as follows:
RXD : Receive data (3)
TXD : Transmit data (2)
RTS : Ready to send (4)
CTS : Clear to send (5)
RI : Ring indicator (10)
DTR : Data terminal ready (9)
DSR : Data set ready (6)
RLSD : Carrier detection (8)
DSRS : Data signal rate selection (11)
TXD
RXD
RTS
CTS
DSR
GND
RLSD
4
5
6
7
8
1
2
3
9
10
11
12
13
14
15
DTR
RI
DSRS
Refer to the TSX SCG 113 Manual (Asynchronous Link, Sub-section 5.2) for further details.
____________________________________________________________________
3.3-2 Connection of the TSX SCG 1161
The module permits connection to a multipoint RS 485 link. It has a transmission circuit and a reception circuit for differential signals.
The pin-out of the 15-pin female connector, located on the top part of the module, is shown opposite:
GND
D (A)
0V
4
5
6
7
8
1
2
3
9
10
11
12
13
14
15
D (B)
0V
___________________________________________________________________________
23
_______________________________________________________________________________________
___________________________________________________________________________
24
________________________________________________________
Programming the Module as a Slave Section 4
___________________________________________________________________________
4.1
Configuring the Module
Page
26
26
27
_______________________________________________________________________________________
4.2
Slave Module/PLC Exchanges 28
28
29
30
30
30
31
_______________________________________________________________________________________
4.3
Request Codes Available 32
_______________________________________________________________________________________
4.4
Module Operating Modes 34
34
35
___________________________________________________________________________
25
_______________________________________________________________________________________
4.1
Configuring the Module
All the module configuration data is sent from the processor to the module by means of a text function block.
As the module has no back-up memory, its configuration is lost whenever the power is cut off; therefore, the configuration write request must be sent on each power restart
(SYO, SY1, IWx,1,F).
____________________________________________________________________
4.1-1 Definition of the Configuration Table
This table is sent to the module. It is composed of 15 words (30 bytes) which can be written in the word zone (W) or constant word zone (CW) of the PLC.
The first three words defined in the configuration table are coded in BCD (Binary Coded
Decimal).
All the others are binary values with 16 significant bits.
F C B
Type of function: 2
Reserved
8 7 4
Number of bits Parity
Transmission speed (baud rate)
Number of the station
3
Physical address of the first word of the output bit zone
Number of output bits
Modbus ® address corresponding to the first bit
Physical address of the first word of the input bit zone
Number of input bits
Modbus ® address corresponding to the first bit
Stop bits
0
Physical address of the first output word
Number of output words
Modbus ® address corresponding to the first word
Physical address of the first input word
Number of input words
Modbus ® address corresponding to the first word
___________________________________________________________________________
26
Programming the Module as a Slave 4
_______________________________________________________________________________________
4.1-2 Definition of the Configuration Parameters
Type of function
Defines the mode of operation of the channel. Only the configuration for Modbus ® protocol (master and slave) is defined in this manual.
1 = Full duplex character string
2 = Modbus ® slave protocol
Number of bits
Defines the format of the characters exchanged on the line.
Parity
Indicates whether an even or odd parity check bit has been added or not.
7 = ASCII transmission
8 = RTU transmission
0 = no parity
1 = odd parity
2 = even parity
Number of stop bits
Defines the number of stop bits that are used to delimit a character.
Important Note :
1 = one stop bit
2 = two stop bits
The three parameters described above define the transmission format, which is determined by the functional possibilities of the TSX SCG module UART. Only the eight possibilities listed below can be used, to the exclusion of all others. The length of the data field (7 or 8 bits) implicitly defines the ASCII mode or the RTU (Remote
Terminal Unit) mode.
ASCII mode
. 7 bits + even parity + 1 stop bit
. 7 bits + even parity + 2 stop bits
. 7 bits + odd parity + 1 stop bit
. 7 bits + odd parity + 2 stop bits
Transmission speed (baud)
The transmission speed is expressed in four figures coded in BCD, except for the speed of 19200 baud which is coded :
H’1920'.
The transmission speeds available are shown opposite:
RTU mode
8 bits + even parity + 1 stop bit
8 bits + odd parity + 1 stop bit
8 bits + 1 stop bit
8 bits + 2 stop bits
19200 - 9600 - 4800 - 2400 - 1200
600 - 300 - 150.
___________________________________________________________________________
27
_______________________________________________________________________________________
Number of the Modbus ® station
This number enables the module to recognize the messages that are addressed to it.The address, expressed by three figures coded in BCD, can have a value from 1 to
247: H'001' to H'247'.
The address 0 corresponds to messages that are broadcast by the master to all the slaves.
Tables of correspondence
PLC addresses - Modbus ® addresses
Four tables of correspondence are defined for the following four types of accessible data objects :
●
Output bits,
●
●
●
Input bits,
Output words,
Input words.
Each table of correspondence is composed of three parameters, each of which is coded on a word. These parameters define :
●
The physical address of the first data object in the memory of the PLC, which must be located in the internal word memory zone.
Example : The address W125 is represented by the binary value 125.
●
The total number of data objects used,
●
The Modbus ® address corresponding to the first data object. This address must correspond to the address transmitted on the line by the master to access the first object in the memory of the PLC (physical address).
_______________________________________________________________________________________
4.2
Slave Module/PLC Exchanges
4.2-1 Method of exchange
Data is transferred between the module and the PLC memory in the form of messages that are transmitted and received by means of text blocks.
At the start of the exchanges, the user program sends a request to the module by using a «Transmission/Reception» type Text block. This allows the slave module to receive the messages transmitted by the master on the line.
___________________________________________________________________________
28
Programming the Module as a Slave 4
_______________________________________________________________________________________
The exchange cycle between the slave module and its processor proceeds in four steps as follows :
Step 1
On reception of a Modbus ® message, the module checks and analyzes it and (if it is correct) interprets the function requested by the master. It then transfers to the user program, in the reception table of the Text block, the access code and the information to be processed by the processor.
Four access codes are possible :
●
Read N words : Access code 01 (Modbus ® functions 03 and 04),
●
●
●
Write N words : Access code 02 (Modbus ® functions 06 and 16),
Read N bits : Access code 03 (Modbus ® functions 01 and 02),
Write N bits : Access code 04 (Modbus ® functions 05 and 15).
These codes must be considered as read or write requests as seen from the master.
Step 2
The user program accepts the message and accesses the data requested by the slave module.
Step 3
The user program then transmits a Transmission/Reception type text block with the following parameters :
●
For a read request : the values requested by the master in the form of a Modbus ® read
● request code (TXTi,C = H’80'),
For a write request : the Modbus ® “end of writing” request code (TXTi,C = H’81') without any data.
Step 4
The slave module then processes the request received from the user program and transmits the reply to the master.
The text block is then reset to the reception mode by the module so that it can receive a new Modbus ® message.
_______________________________________________________________________________________
4.2-2 Reading of N Words
Reception table
Access code = 1
Address of first word to be read
Number of words to be read
Transmission table
Value of the first word addressed
Value of the second word addressed
Etc.
Variables
Request code sent to the module : TXTi,C = H’80'
Length of the transmission table : TXTi,L = 2 x (number of words to be read).
___________________________________________________________________________
29
_______________________________________________________________________________________
4.2-3 Writing of N Words
Reception table
Access code = 2
Address of first word to be written
Number of words to be written
Value of the first word
Value of the second word
Value of the third word
Transmission table empty
Variables
Request code sent to the module : TXTi,C = H’81' (end of writing)
Length of the transmission table : TXTi,L = 0.
_______________________________________________________________________________________
4.2-4 Reading of N Bits
Reception table
Access code = 3
Address of first word to be read
Number of words to be read
Transmission table
Value of the first word addressed
Value of the second word addressed
Etc.
Variables
Request code sent to the module : TXTi,C = H’80'
Length of the transmission table : TXTi,L = 2 x (number of words to be read).
_______________________________________________________________________________________
4.2-5 Writing of N bits
Reception table
Access code = 4
Address of first word to be written
Number of words to be written
Mask of the first word = MSK1
Mask of the last word = MSK2
Value of the first word
Value of the second word
Etc.
Transmission table empty
Variables
Request code sent to the module : TXTi,C = H’81'
30
Programming the Module as a Slave 4
_______________________________________________________________________________________
The bit string that the master wants to write is located in a series of words, the first of which (which contains the first bits) is defined by its address.
Before being written, the bit string must first be reset to zero, then a logical OR operation must be effected between the old and new tables.
Two masks MSK1 and MSK2 are defined at the beginning and end of the word table so as to delimit the accessed zone of the bit string.
Wj Wj-1 Wi+1 Wi
Bit string to be written
MSK1 and MSK2 are used with a logical AND to reset the bit string to zero.
MSK1 = L ' 0 0 0 0 ... 0 111 ' bits accessed in the first word (Wi),
MSK2 = L ' 1 1 1 ... 1 0 ... 0 0 ' bits accessed in the last word (Wj).
_______________________________________________________________________________________
4.2-6 Examples
Reading of words W28 to W30
Reception table
Wi = 1
Wi + 1 = 28
Wi + 2 = 3
Transmission table
Wj = W28
Wj + 1 = W29
Wj + 2 = W30
Writing of word W00 to the value 125 and word W01 to the value -79
Reception table
Wi = 2
Wi + 1 = 00
Wi + 2 = 2
Wi + 3 = 125
Wi + 4 = -79
Reading of bits W10,A to W11,2
Reception table Transmission table
Wi = 3
Wi + 1 = 10
Wj = W10
Wj + 1 = W11
Wi + 2 = 2
___________________________________________________________________________
31
_______________________________________________________________________________________
Writing of bits W50,B to W51,4 to L’11010 00101'
Reception table
Wi = 4
Wi + 1 = 50
Wi + 2 = 2
Wi + 3 = H’07FF’ = L’0000 0111 1111 1111'
Wi + 4 = H’FFE0' = L’1111 1111 1110 0000'
Wi + 5 = H’2800' = L’0010 1000 0000 0000'
Wi + 6 = H’001A’ = L’0000 0000 0001 1010'
User program processing
W50 AND Wi+3 —> W50 (resetting to zero of the accessed bits),
W51 AND Wi+4 —> W51 (resetting to zero of the accessed bits),
W50 OR Wi+5 —> W50 (loading of the new values),
W51 OR Wi+6 —> W51 (loading of the new values).
_______________________________________________________________________________________
4.3
Request Codes Available
Write Configuration
Request code
Positive report
TXTi,C = H’40'
TXTi,R = H’FE’
Negative report TXTi,R = H’FD’
This request permits the transmission of the configuration.
Read Configuration
Request code
Positive report
Negative report
TXTi,C = H’41'
TXTi,R = H’71'
TXTi,R = H’FD’
This request permits the reading of the configuration sent to the channel.
The text block used must have a reception table length of at least 30 bytes in order to contain the configuration parameters.
Read Counters
Request code
Positive report
Negative report
TXTi,C = H’70'
TXTi,R = H’A0'
TXTi,R = H’FD’
___________________________________________________________________________
32
Programming the Module as a Slave 4
_______________________________________________________________________________________
This request enables the processor to read the exchange monitoring counters. The reception buffer contains the following seven words :
●
Wi = number of messages received on the line,
●
●
●
●
●
●
Wi+1 = number of messages received by the module with a checksum error,
Wi+2 = number of messages transmitted with an exception code,
Wi+3 = number of messages received by the module,
Wi+4 = number of messages transmitted to the processor without response,
Wi+5 = number of events,
Wi+6 = diagnostic register.
Read Modbus ®
Request code
Positive report
Negative report
TXTi,C = H’80'
TXTi,R = H’B0'
TXTi,R = H’FD’
This request has two uses :
●
If the channel is stopped, it allows the channel to be set to RUN and the module to be set on standby for a message on the line, providing the RUN channel command is present, (OWx1,1 = 1).
The negative report appears if this request is sent when the RUN channel command is absent.
●
If the channel is running, this request constitutes the reply to a request from the master to read N bits or N words.
End of Write Modbus ®
Request code
Positive report
TXTi,C = H’81'
TXTi,V = H’B0'
This is the reply to a request from the master to write N bits or N words.
___________________________________________________________________________
33
_______________________________________________________________________________________
4.4
Module Operating Modes
4.4-1 Status Chart
The status chart below represents the operation of the TSX SCG 11 module after it has been configured for the Modbus ® slave protocol.
Important :
The Modbus ® messages cannot be processed until the "RUN channel" command
(bit OWx,1,1) and the "Read Modbus ® " request have been sent. The RUN bit associated with the channel is then set to 1 (bit IWx,1,1).
STOP command
STOP command
Init
Channel OK
Channel not configured
Configuration OK
Channel configured
RUN command and Modbus ® read request
Channel running awaiting request
Reception of Modbus ® message
Analysis of the message
Message OK
CPU transfer
Awaiting CPU reply
Message OK
CPU reply
Conversion of reply
Transmission of reply
___________________________________________________________________________
34
Programming the Module as a Slave 4
_______________________________________________________________________________________
4.4-2 Effect of Power Failures and Power Restarts on the Module
As the TSX SCG 11 module has no back-up memory, it loses its configuration when it is no longer powered by the PLC.
The module must therefore be reconfigured whenever:
●
● it undergoes a cold restart (SY0 = 1).
it undergoes a hot restart (SY1 = 1) after the power reserve has been depleted.
Power Restart
On power-up, the PLC sets the bit IWx,0,8 (blocking fault) to 1. After approximately 300 ms, the discrete interfaces, register and message become active in the module. The module then runs its self-tests (IWx,0,8 = 0 and IWx,0,9 = 1), which last for about 1 s.
On completion of the self-tests, the Module Available bit (IWx,0,3) and PWF bit (IWx,1,F) are set to 1 to indicate that the module can be accessed in message mode.
Acknowledgement of the PWF bit is possible but not compulsory.
IWx,0,3
IWx,0,8
IWx,0,9
IWx,0,F
Power-up
(Initialization) Self-tests
Module available
Recommendation:
The module 12V and PLC 5V power supplies may behave differently when power failures occur, causing loss of the configuration without the bits SY0 and SY1 changing state. It is therefore preferable to test not only the bits SY0 and SY1 but also the bit IWx,1,F (PWF).
___________________________________________________________________________
35
_______________________________________________________________________________________
___________________________________________________________________________
36
________________________________________________________
Programming the Module as a Master Section 5
___________________________________________________________________________
5.1
Configuring the Module
Page
39
39
39
_______________________________________________________________________________________
5.2
Master Module/PLC Exchanges: Main Functions 41
5.2-2 Read N output bits
5.2-3 Read N output words
-
-
Read N input bits
Read N input words
42
43
44
44
41
41
42
42
_______________________________________________________________________________________
5.3
Master Module/PLC Exchanges: Complementary Functions 45
47
47
47
47
48
48
45
45
46
46
46
48
49
49
___________________________________________________________________________
37
________________________________________________________
Programming the Module as a Master Section 5
___________________________________________________________________________
5.4
Request Codes Available
Page
50
_______________________________________________________________________________________
5.5
Module Operating Codes 52
52
52
___________________________________________________________________________
38
Programming the Module as a Master 5
_______________________________________________________________________________________
5.1
Configuring the Module
All the module configuration information is transferred from the processor to the module by means of a text function block.
This table is composed of 4 words (8 bytes) which can be written in the word zone (W) or constant word zone (CW) of the PLC.
_______________________________________________________________________________________
5.1-1 Definition of the Configuration Table
Wi
Wi + 1
Wi + 2
Wi + 3
F C B
Type of function
8 7
Number of bits Parity
Transmission speed (baud rate)
4 3
Time envelope
0 0 0
Stop bits
Reiteration
0
The first three words defined in the configuration table are coded in BCD (Binary Coded
Decimal).
_______________________________________________________________________________________
5.1-2 Definition of the Configuration Parameters
Type of function
Defines the mode of operation of the channel. Only the configuration for Modbus ® protocol (master/slave) is dealt with in this manual.
4 = Modbus ® master protocol
Number of bits
Defines the format of the characters exchanged on the line.
7 = ASCII transmission
.
8 = RTU transmission
Parity
Indicates whether an odd or even parity check bit has been added or not.
0 = no parity
1 = odd parity
2 = even parity
Number of stop bits
Defines the number of stop bits that are used to delimit a character.
1 = one stop bit
2 = two stop bits
Important note :
The three parameters described above define the transmission format, which is determined by the functional possibilities of the TSX SCG module UART.
___________________________________________________________________________
39
_______________________________________________________________________________________
Only the eight possibilities listed above can be used, to the exclusion of all others. The length of the data field (7 or 8 bits) implicitly defines the ASCII mode or the RTU (Remote
Terminal Unit) mode :
ASCII mode
●
●
●
●
7 bits + even parity + 1 stop bit
7 bits + even parity + 2 stop bits
7 bits + odd parity + 1 stop bit
7 bits + odd parity + 2 stop bits
RTU mode
●
●
●
●
8 bits + even parity + 1 stop bit
8 bits + odd parity + 1 stop bit
8 bits + 1 stop bit
8 bits + 2 stop bits
Transmission speed (baud)
The transmission speed is expressed in four figures coded in BCD, except for the speed of 19200 baud which is coded :
H’1920'. The transmission speeds available are shown opposite.
Time envelope
This is the time that the TSX SCG 11 module master allows to the slave to reply to a request. If the slave has not replied by the end of this time, the master considers the slave has not received the request.
This time must always be more than the longest response time of all the various slaves connected to the line. The time envelope is coded in BCD on one word and can be fixed between 20ms and 99.99s
(i.e. 1 minute 40 seconds). The values
H’0000', H’0001' and H’0002' fix the response time at 20ms.
Number of reiterations
This parameter defines the number of times the master can reiterate a request to which the slave has not replied, or has replied with an error code. The request is reiterated after the time envelope defined above has elapsed. If the number of reiterations is fixed at zero, the master does not reiterate any of its requests.
19200 - 9600 - 4800 - 4200 -
1200 - 600 - 300 - 150
H'0000' to H'9999' increments of the time base (10ms).
H'0' to H'9'
___________________________________________________________________________
40
Programming the Module as a Master 5
_______________________________________________________________________________________
5.2
Master Module/PLC Exchanges: Main Functions
5.2-1 Method of exchange
Data is transferred between the memory of the PLC and the master module in the form of messages that are transmitted and received by means of text blocks.
The requests sent to the master module are coded in the variable TXTi,C of the text block and have the same number as the Modbus ® function concerned.
The user program positions the parameters associated with each request in the transmission table of the text block. These parameters include :
●
●
●
●
The number of the slave,
The Modbus ® address of the objects to be processed,
The number of objects, etc.
After processing the reply from the slave, the master module completes the reception table of text block with the data necessary for the interpretation of the request by the user program.
Only the main Modbus ® functions that permit the exchange of a Modbus ® object are described below.
_______________________________________________________________________________________
5.2-2 Read N output bits - Read N input bits
Transmission table
Number of the slave
Modbus ® address of the 1st bit
Number of bits to be read
Reception table
Number of words read
Mask of the last word = MSK
Value of the 1st word
Value of the 2nd word
Etc.
Variables
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’01' (Output bits)
H’02' (Input bits)
TXTi,L = 6
The first bit of the string to be read by the master always corresponds to the least significant bit of the first word.
The mask of the last word permits the identification of the last significant bits of the string.
MSK = L ' 1 1 1 1 ... 1 0 ... 0 0 ' bits accessed in the last word
___________________________________________________________________________
41
_______________________________________________________________________________________
5.2-3 Read N output words - Read N input words
Transmission table
Number of the slave
Modbus ® address of the 1st word
Number of words to be read
Reception table
Number of words read
Value of the 1st word
Value of the 2nd word
Etc.
Variables
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’03' (Output words)
H’04' (Input words)
TXTi,L = 6
_______________________________________________________________________________________
5.2-4 Write an output bit
Transmission table
Number of the slave
Modbus ® address of the output bit
Value to be written
The value to be written is equal to :
●
●
H’0000' to write the bit at zero,
H’00FF’ to write the bit at one.
Variables
Request code sent to the module :
Length of the transmission table :
Reception table empty
TXTi,C = H’05'
TXTi,L = 6
_______________________________________________________________________________________
5.2-5 Write an output word
Transmission table
Number of the slave
Modbus ® address of the output word
Value to be written
Reception table empty
Variables
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’06'
TXTi,L = 6
___________________________________________________________________________
42
Programming the Module as a Master 5
_______________________________________________________________________________________
5.2-6 Write N output bits
Transmission table
Number of the slave
Modbus ® address of the 1st bit to be written
Number of words
Mask of the first word = MSK1
Mask of the last word = MSK2
Value of the first word
Value of the second word
Etc.
Reception table empty
The bit string that the master wants to write is located in a series of words, the first of which (which contains the first bits) is defined by its address.
Before being written, the bit string must first be reset to zero, then a logical OR operation must be effected between the old and new tables.
Wj Wj-1 Wi+1 Wi
Bit string to be written
MSK1 = L ' 0 0 0 0 ... 0 111 ' bits accessed in the first word (Wi),
MSK2 = L ' 1 1 1 ... 1 0 ... 0 0 ' bits accessed in the last word (Wj).
MSK1 and MSK2 are used by the module to define the number of bits to be written and to position the bit string to be written on the first bit, defined by its Modbus ® address.
Variables
Request code sent to the module : TXTi,C= H’0F’
Length of the transmission table : TXTi,L = 10 + 2 (number of words to be written)
___________________________________________________________________________
43
_______________________________________________________________________________________
5.2-7 Write N output bits
Transmission table
Number of the slave
Modbus ® address of the 1st word to be written
Number of words to be written
Value of the first word
Value of the second word
Etc.
Reception table empty
Variables
Request code sent to the module : TXTi,C = H’10'
Length of the transmission table : TXTi,L = 6 + 2 (number of words to be written)
_______________________________________________________________________________________
5.2-8 Examples
Reading of the input words with Modbus ® addresses 8100 and 8101 of slave 32.
Transmission table
Wi = 32
Wi+1 = 8100
Wi+2 = 2
Reception table
Wj = 2
Wj+1 = slave object with Modbus ® address 8100
Wj+2 = slave object with Modbus ® address 8101
Writing of the output words with Modbus ® addresses 4105, 4106 and 4107 of slave 45 with the values 38, -342 and 2154 respectively.
Transmission table
Wi =
Wi+1 =
45
4105
Wi+2 =
Wi+3 =
Wi+4 =
Wi+5 =
3
38
-342
2154
Reading of 18 output bits of slave 228, the first of which has the Modbus ® address 202.
Transmission table
Wi = 228
Wi+1 = 202
Wi+2 = 18
Reception table
Wj = 2
Wj+1 = H’FFFC’
Wj+2 = slave bits with Modbus ® addresses 202 to 217
Wj+3 = slave bits with Modbus ® addresses 218 to 233
___________________________________________________________________________
44
Programming the Module as a Master 5
_______________________________________________________________________________________
Writing of 12 output bits of slave 191, the first of which has the Modbus ® address 118.
For the purposes of this example, it is assumed that the 12 bits to be written are bits
W50,E to W51,9 of the processor in the master.
Transmission table
Wi = 191
Wi+1 = 118
Wi+2 = 2
Wi+3 = H’3FFF’ = L’0011111111111111'
Wi+4 = H’FC00' = L’1111110000000000'
Wi+5 = W50
Wi+6 = W51
_______________________________________________________________________________________
5.3
Master Module/PLC Exchanges: Complementary Functions
5.3-1 Read exception status register
Transmission table
Number of the slave
Reception table
Exception status of the slave
Variables
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’07'
TXTi,L = 2
_______________________________________________________________________________________
5.3-2 Echo check
Transmission table
Number of the slave
Diagnostic code = 0
Data
Reception table empty
Variables
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 6
___________________________________________________________________________
45
_______________________________________________________________________________________
5.3-3 Restart communication
Transmission table
Number of the slave
Diagnostic code = 1
Data
Reception table empty
The data can take any of the following two values :
●
H’00FF’ : continue if there is an error.
In this case, the trace buffer which records the connection events will be erased.
●
H’0000' : stop if there is an error.
Variables
Request code sent to the module :
Length of the transmission table :
TXTi,C =
TXTi,L =
H’08'
6
_______________________________________________________________________________________
5.3-4 Read diagnostic register
Transmission table
Number of the slave
Diagnostic code = 2
Reception table
Diagnostic register of the slave
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
_______________________________________________________________________________________
5.3-5 Force to listen only mode (LOM)
Transmission table
Number of the slave
Diagnostic code = 4
Reception table empty
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
___________________________________________________________________________
46
Programming the Module as a Master 5
_______________________________________________________________________________________
5.3-6 Reset counters
Transmission table
Number of the slave
Diagnostic code = 10
Reception table empty
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
_______________________________________________________________________________________
5.3-7 Read line message counter
Transmission table
Number of the slave
Diagnostic code = 11
Reception table
Number of messages received
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
_______________________________________________________________________________________
5.3-8 Read checksum error counter
Transmission table
Number of the slave
Diagnostic code = 12
Reception table
Number of checksum errors
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
_______________________________________________________________________________________
5.3-9 Read exception error counter
Transmission table
Number of the slave
Diagnostic code = 13
Reception table
Number of exception responses
Request code sent to the module :
Length of the transmission table :
TXTi,C =
TXTi,L =
H’08'
4
___________________________________________________________________________
47
_______________________________________________________________________________________
5.3-10 Read slave’s message counter
Transmission table
Number of the slave
Diagnostic code = 14
Reception table
Number of messages sent to the slave
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
_______________________________________________________________________________________
5.3-11 Read slave’s no reply counter
Transmission table
Number of the slave
Diagnostic code = 15
Reception table
Number of no replies from slave proc.
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’08'
TXTi,L = 4
_______________________________________________________________________________________
5.3-12 Read event counter
Transmission table
Number of the slave
Reception table
Status word
Event counter
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’0B’
TXTi,L = 2
___________________________________________________________________________
48
Programming the Module as a Master 5
_______________________________________________________________________________________
5.3-13 Read event log
Transmission table
Number of the slave
Reception table
Status word
Event counter
Line message counter
Nber of messages received on line
Number of bytes in the trace buffer
1st & 2nd bytes of the trace buffer
3rd & 4th bytes of the trace buffer
Etc.
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’0C’
TXTi,L = 2
_______________________________________________________________________________________
5.3-14 Read slave identification
Transmission table
Number of the slave
Reception table
Slave identifier
Operating status of the slave
Number of bytes that follow
1st & 2nd bytes
3rd & 4th bytes
Etc.
Request code sent to the module :
Length of the transmission table :
TXTi,C = H’11'
TXTi,L = 2
___________________________________________________________________________
49
_______________________________________________________________________________________
5.4
Request Codes Available
Write Configuration
Request code
Positive report
Negative report
TXTi,C = H’40'
TXTi,R = H’FE’
TXTi,R = H’FD’
This request permits the transmission of the configuration to the module.
A negative report is returned when :
●
The channel is not stopped, or
●
The parameters of the request are incorrect.
Read Configuration
Request code
Positive report
Negative report
TXTi,C = H’41'
TXTi,R = H’71'
TXTi,R = H’FD’
This request permits the configuration sent to the channel, to be re-read.
A negative report is returned if the channel is not configured.
Read Counters
Request code
Positive report
Negative report
TXTi,C = H’70'
TXTi,R = H’A0'
TXTi,R = H’FD’
This request enables the processor to read the exchange monitoring counters. The reception buffer contains the following 12 words :
●
●
Wi = number of processor requests accepted by the module,
Wi+1 = number of processor requests refused by the module,
●
●
●
●
Wi+2 = number of correct slave replies received,
Wi+3 = number of slave replies received with an exception code,
Wi+4 = number of master messages sent without replies (time envelope elapsed),
Wi+5 = number of slave replies received with a checksum error,
●
●
●
●
●
●
Wi+6 = number of slave replies received that are incoherent,
Wi+7 = number of master messages reiterated,
Wi+8 = number of reiteration procedures abandoned,
Wi+9 = number of time envelopes elapsed during reception,
Wi+10 = number of slave replies received with a reception fault,
Wi+11 = diagnostic register.
Transparent Modbus ®
Request code
Positive report
Negative report
TXTi,C = H’81'
TXTi,R = H’FE’
TXTi,R = H’17'
This request enables the processor to generate a function that is different from the
Modbus ® functions controlled by the module.
___________________________________________________________________________
50
Programming the Module as a Master 5
_______________________________________________________________________________________
The user program prepares the message to be transmitted on the line in the transmission table of the text block, the first byte of which is the number of the destination slave.
The module then checks the number of the slave. If it is not correct, the module returns a negative report. If it is correct, the module calculates the redundancy code and transmits the complete message. If the number of the slave is null (i.e. general broadcast), the module transmits the message on the line and sends a positive report to the processor without waiting for a reply.
Modbus ® functions
Request codes
Positive reports
TXTi,C = number of the Modbus ® function
TXTi,R = H’FE’
TXTi,R = H’19' (re quest addressed to a slave that is in the
Listen Only Mode)
Negative reports can arise from two sources :
●
From the master module, if it has detected an error in the processor request or if it has not received a reply from the slave.
●
From the slave module, if it has detected an error in the request received from the master or if it cannot process the request received from the master.
In this case, the slave returns to the master an exception response comprising :
- The address of the slave,
- The function code received by the slave, to which it adds the value H’80',
- The exception code indicating the type of error,
- The exchange monitoring code.
The master module then transmits to its processor the exception code received from the slave as the negative report to the request, as shown below.
Negative report (TXTi,R)
H’01' (exception response)
H’02' (exception response)
H’03' (exception response)
H’04' (exception response)
H’05' (exception response)
H’06' (exception response)
H’07' (exception response)
H’15'
H’17'
H’18'
H’FD’
Significance
Function number not defined in the slave
Modbus ® address unknown to the slave
Illegal value for the Modbus ® address indicated
Slave processor failed
Acknowledged: the slave processor has accepted and is processing the request from the master
Slave processor busy
Negative acknowledgement
No correct reply from the slave after reiterations
Incorrect request parameters
Channel stopped
Unknown Modbus ® function
___________________________________________________________________________
51
_______________________________________________________________________________________
5.5
Module Operating Modes
5.5-1 Status Chart
The status chart below represents the operation of channel 0 of the TSX SCG 11 module after it has been configured for the Modbus ® master protocol.
Init
STOP command
STOP command
Channel OK
Channel not configured
Configuration OK
Channel configured
RUN command and Modbus ® read request
Channel running exchange with slave
End of Modbus ® exchange
Channel running, awaiting request
Modbus ® request
The channel starts running on receiving the first Modbus ® request accompanied by the
“RUN Channel” request (bit OWx,1,1).
The RUN bit associated with the channel is then set to 1 (bit IWx,1,1).
The channel can be stopped at any time by setting bit OWx,1,1 to zero.
_______________________________________________________________________________________
5.5-2 Effect of Power Failures and Power Restarts on Module
Refer to Section 4.4-2
___________________________________________________________________________
52
________________________________________________________
Discrete Bits and Registers Section 6
___________________________________________________________________________
Page
6.1
Discrete Interface 54
54
54
55
_______________________________________________________________________________________
6.2
Register Interface 56
56
57
___________________________________________________________________________
53
_______________________________________________________________________________________
6.1
Discrete Interface
6.1-1 Description
The discrete interface of the TSX SCG module enables the user program to control the transmission and reception on the channel.
This interface comprises :
●
4 input bits : Ix,0 to Ix3
These bits reflect the states of the input signals of the line adaptors.
●
4 output bits : Ox,0 to Ox,3
These bits set the output signals of the line adaptors to 0 or 1.
Each of these I/O bits has a specific definition according to the module. Certain of these bits are not simply recopied by the module, but also act directly on the operation of the channel. The assignment of these I/O bits and their effect on the operation of the channel are described below.
A logic state of 0 (zero) indicates an active signal.
A logic state of 1 (one) indicates an inactive signal.
___________________________________________________________________________________________
6.1-2 TSX SCG 113 Module
3 2 1 0
Output bits Ox,i DSRS DTR
●
DTR = Data terminal ready
This signal, which is used to control the modem, has no effect on the operation of the channel.
The request to send is controlled by the the Modbus ® protocol and is therefore transparent to the user.
●
DSRS = Data signal rate selection 0 = the channel operates at the configured speed,
1 = the channel operates at the configured speed divided by 2.
If the type of modem used offers this possibility, this signal can be used to operate at reduced speed when repeated errors of transmission are detected.
3 2 1 0
Input bits Ix,i RI CD DSR CTS
●
●
CTS
DSR
= Clear to send
= Data set ready
1 = transmission circuit disabled, no effect on channel operation,
●
CD = Carrier detection 1 = reception circuit disabled,
●
RI = Ring indicator no effect on channel operation.
___________________________________________________________________________
54
Discrete Bits and Registers 6
_______________________________________________________________________________________
Note :
When these signals are not used, they are set to 1 by the adaptor; the transmission and reception circuits are therefore disabled.
___________________________________________________________________________________________
6.1-3 TSX SCG 116 Module
This adaptor does not have any transmission monitoring signals. In the RS-485 mode, the transmitter validation bit that switches the transmitter to the high-impedance state is controlled by the Modbus ® protocol and is transparent to the user.
___________________________________________________________________________
55
_______________________________________________________________________________________
6.2
Register Interface
6.2-1 Input Registers
Input Registers IWx,0 to IWx,7
These read-only registers provide information on the module operation.
Input Register IWx,0
BIT FUNCTION
0 Not assigned
1
2 Resetting in progress
3 Module available
4 General fault
DESCRIPTION
Resetting to zero by the system of the message in progress.
Indicates the end of the common and specific self-tests and consequently that the module is available.
This bit is set to 1 for any type of fault. It performs the logical
OR of bits 7 and 8 of this register.
5 Not assigned
6 Not assigned
7 Application fault
8 Blocking fault
9 Module self-tests
Fault during the execution of a request (error of parity in reception).
No 12V, or module 12V and PLC 5V supplies asynchronous.
Check that these power supplies come on at the same time, then reset this bit to 0 by SY0 or SY1. Fault in the RAM,
REPROM or internal logic of the module. This fault permanently blocks the coupler, which must be replaced. The RUN light is off and the I/O light is on.
On power-up of the PLC, the module runs a series of selftests, indicated by this bit. The module is not available during this phase and cannot be configured or used.
A Not assigned
B Module not configured
C Module running
D Reserved
E Not assigned
F Not assigned
This bit eguals 1 when the module is not configured.
A request is being executed.
___________________________________________________________________________
56
4
5
6
7 to
E
F
Discrete Bits and Registers 6
_______________________________________________________________________________________
Input Register IWx,1
This word contains information concerning the operating status of the module channel.
BIT
0
1
FUNCTION
Not assigned
RUN/STOP
DESCRIPTION
2
3
LOM
Module configured
Adaptor code
0 = Channel stopped
1 = Channel running
0 = Slave Modbus channel is in reception/transmission mode
1 = Slave Modbus channel is in Listen Only Mode (LOM)
0 = Module not configured
1 = Module configured
101 = RS 232-Modem adaptor
100 = RS 485 adaptor
Not assigned
PWF A power return has occurred (state 1). This bit must be reset to zero (by OWx,1,F) to process a new power return.
Input registers IWx,2 to 7
These registers are not used.
___________________________________________________________________________________________
6.2-2 Output Registers
Output Register OWx,0
The bit OWx,0,2 of this word is used to reset the message system of the module to zero.
Output Register OWx,1
This word contains the RUN/STOP control bits
BIT
0
1
FUNCTION
Not assigned
RUN/STOP
DESCRIPTION
0 = Channel stopped
1 = Channel running
2 to
E
Not assigned
F PWF acknowledgement
Setting this bit to 1 acknowledges (not compulsory) a PWF on the PLC (resets IWx,1,F to logic state 0)
___________________________________________________________________________
57
_______________________________________________________________________________________
Note:
The user program is responsible for setting the acknowledgement or zero reset bits to 0.
Output register OWx,2
Not used.
Output register OWx,3 (slave only)
The most significant bits correspond to a status register (see Section 2.7, Read
Exception Error Counter).
Output registers OWx, 4 to OWx,7
Not used.
___________________________________________________________________________
58
________________________________________________________
Additional Programming Information Section 7
___________________________________________________________________________
A
7.1
Fault Bits
Page
60
___________________________________________________________________________
59
_______________________________________________________________________________________
7.1
Fault Bits
Faults are indicated by 48 fault bits (3 words of 16 bits) which can be read in the message mode by the standard request (common to all intelligent modules) : «Read fault bits».
The fault bits are then received in the reception table of the text block concerned :
●
●
●
●
●
Request code
Variable
Transmission table
Reception table
Module address and channel number
TXTi,C = H’47'
TXTi,L = 0
Not used
At least 6 bytes
TXTi,M = 0x63 where x = 1,2 or 3
State of the variables at the end of the exchange :
●
Number of bytes received TXTi,S = 6
●
Report TXTi,R = H’77'
Organization of the Table
●
BDEF fault bits
Fault Bit
0
1
2
3-36
37
38-47
Fault
EPROM checksum fault
RAM fault (internal, external)
12V fault
Not used
Reception parity error
Not used
___________________________________________________________________________
60
________________________________________________________
Programming Examples Section 8
___________________________________________________________________________
8.1
Programming a Slave in the TSX 17-20
Page
62
62
63
64
65
___________________________________________________________________________
61
_______________________________________________________________________________________
8.1
Programming a Slave in the TSX 17-20
8.1-1 Description
In this example, a TSX 17-20 module is linked to a master using Modbus ® protocol.
The station number of the slave is 1.
The program described below ensures the configuration of the module after PLC powerup and the processing of the Modbus ® slave protocol.
For a given application, 4 zones of bits and words (i.e. the accessible Modbus ® objects) must be defined in the slave. The user must of course also define the corresponding physical objects (discrete I/O, etc.) as required, and write the application program linking these physical objects to the accessible Modbus ® objects.
i.e. a zone of 60 words starting at W60 that is defined as follows :
W75 to W89
W105 to W119
W60 to W74
W90 to W104
Table of 240 inputs bits
Table of 15 inputs words
Table of 240 outputs bits
Table of 15 outputs words
The start of each zone corresponds to a Modbus ® master address (values defined for a given master)
Inputs bits
Inputs words
Outputs bits
Outputs words
W75
W90 has the corresponding Modbus ® address 0
W105 has the corresponding Modbus ® address 0
W60 has the corresponding Modbus ® address 0 has the corresponding Modbus ® address 0
___________________________________________________________________________
62
Programming Examples 8
_______________________________________________________________________________________
8.1-2 Organization
The main program organizes the transfer of the configuration on the module channel 0 and then authorizes the processing of the Modbus ® slave protocol on this channel.
Start
Initialization of module
NO
YES
Initialization of the module
End
Configuration request
Transfer of the configuration
___________________________________________________________________________
63
_______________________________________________________________________________________
8.1-3 Definition of the Objects and Constants
TXT0 : configuration of channel 0,
TXT1 : transfer of Modbus ® messages on channel 0,
B0 : authorization of Modbus ® protocol.
CW0 : H’2802'
CW1 : H’9600'
CW2 : 1
CW3 : 60
CW4 : 240
CW5 : 0
CW6 : 75
CW7 : 240
CW8 : 0
CW9 : 90
CW10 : 15
CW11 : 0
CW12 : 105
CW13 : 15
CW14 : 0
:
:
:
:
:
:
:
:
:
:
:
:
:
:
: Modbus ® ,RTU mode, no parity, 2 stop bits speed 9600 baud slave station number 1 output bit zone
240 bits from W60 to W74
Modbus ® address of the 1st output bit : 0 input bit zone
240 bits from W75 to W89
Modbus ® address of the 1st input bit : 0 output word zone
15 words from W90 to W104
Modbus ® address of the 1st output word : 0 input word zone
15 words from W105 to W119
Modbus ® address of the 1st input word : 0
___________________________________________________________________________
64
Programming Examples 8
_______________________________________________________________________________________
8.1-4 Program Listing
** LABEL
SY1
1
R TXT0
CONFIG
D IW2, 1, 3 OW2, 1, 1
OW2, 1, 1 SY1 IW2, 1, 3 S
O
CPL
T ,M:H0200
LOCAL
T , C:H0040
T, R:H
CWO
I
T ,L: 30
T ,S:
E
H'0080'
OPERATE
TXT1, C
0
OPERATE
W50
** LABEL
OW2, 1, 1
2
OW2, 1, 1 BO
R TXT1
MODBUS TR/REC
D COMPAR
W10 = 1
S
O
CPL
T ,M:H0200
LOCAL
T , C:H0080
T, R:H
W10 (30)
I
T ,L: 2
T ,S:
E
COMPAR
W10 = 3
COMPAR
W10 = 2
COMPAR
W10 = 4
** LABEL 3 END
** LABEL
COMPAR
4
W12 > 0
SRO READ WORDS
L4
J
L13
J
W0 (W11)
OPERATE
W25 (W50)
OPERATE
W11 + 1 W11
OPERATE
W12 - 1 W12
OPERATE
W50 + 1 W50
L6
J
L8
J application
MODBUS / ..............................................
Télémécanique-/-TSX
PROG.: MAST rev date
11-15-90 page
7- 1
7
___________________________________________________________________________
65
_______________________________________________________________________________________
** LABEL
COMPAR
5
W12 = 0
** LABEL
COMPAR
6
W12 > 0
SR1 WRITE WORDS
OPERATE
TXT1,L
H'0080'
OPERATE
TXT1,C
L13
J
L4
J
OPERATE
W13 (W50) W0 (W11)
OPERATE
W11 + 1 W11
OPERATE
W50 + 1 W50
OPERATE
W12 - 1 W12
** LABEL
COMPAR
7
W12 = 0 H'0081'
OPERATE
TXT1,C
L13
J
L6
J application
MODBUS / ..............................................
Télémécanique-/-TSX
PROG.: MAST rev date
11-15-90 page
7- 2
8
___________________________________________________________________________
66
Programming Examples 8
_______________________________________________________________________________________
** LABEL
COMPAR
8
W12 < > 0
SR2 WRITE BITS
W0 (W11)
OPERATE
W53
OPERATE
W53 AND W13 W53
OPERATE
W53 OR W15 W0 (.
0:W53 OR W15
** LABEL
COMPAR
9
W12 < > 0
W0 (W11)
MASK 1
** LABEL
COMPAR
10
W12 > 1
** LABEL
COMPAR
101
W12 > 1
INTER. WORDS
W11 [2]
OPERATE
W51 [2]
OPERATE
W11 + 1 W11
OPERATE
W12 - 1 W12
W16 (W0)
OPERATE
W0 (W11)
OPERATE
W12 - 1 W12
OPERATE
W50 + 1 W50
OPERATE
W11 + 1 W11
L10
J application
MODBUS / ..............................................
Télémécanique-/-TSX
PROG.: MAST rev date
11-15-90 page
7- 3
9
___________________________________________________________________________
67
_______________________________________________________________________________________
** LABEL
COMPAR
11
W12 > 0
MASK 2
W0 (W11)
OPERATE
W53
OPERATE
W53 AND W14 W53
OPERATE
W16 (W50) W54
OPERATE:0
W53 OR W54 W (.
0:W53 OR W54
** LABEL
COMPAR
12
W12 > 0
W0 (W11)
0
OPERATE
W12
H'0081'
OPERATE
TXT1,C
** LABEL
TXT1,D
13
COMPAR
W12 = 0
BR END
0
0
OPERATE
W10
OPERATE
W50
B0
END OF PROGRAM application
MODBUS / ..............................................
Télémécanique-/-TSX
PROG.: MAST rev date
11-15-90 page
7- 4
10
___________________________________________________________________________
68
________________________________________________________
Appendix Section 9
___________________________________________________________________________
9.1
Response Time of the Slave
Page
70
_______________________________________________________________________________________
9.2
Response Time of the Master 71
___________________________________________________________________________
69
_______________________________________________________________________________________
9.1
Response Time of the Slave
Calculating the Response Time
It is necessary to calculate the slave response times in order to configure the master (i.e.
to define the time envelope after which the master polls the next slave if there is no reply from the first one), and also in order to evaluate the overall performance of the communication system. The times given below are valid for the most unfavorable cases.
The response time of a slave is the sum of the following transfer times :
●
The time (Trm) to transmit a message to the slave,
●
●
●
●
The time (Tmp) for the module to process the message,
The time (Tpr) for the processor to accept and to reply,
The time (Tmr) for the PLC to process the reply,
The time (Tmt) to transmit the message to the master.
The time to transmit a message of N characters to the slave.
Trm = 1000 x N x (Number of bits per character)/(baud rate)
The time for the module to process the message.
Tmp is the time required by the module to recognize the end of the message (i.e. a minimum delay of 3.5 characters between 2 messages), to analyze the message and to transmit a request to the processor.
This time depends on the master's request.
The time for the processor to accept and to reply.
Tpr = 6 x (PLC scan time) for exchanges by text block.
The time for the PLC to process the reply.
Tmr is the time required by the module to process the processor reply and to prepare the message for transmission to the master.
This time depends on the master's request.
The time to transmit the message of M characters to the master.
Tmt = 1000 x M x (Number of bits per character)/(baud rate).
Example
On a link with a speed of 9600 baud and a character format of 1 start bit, 8 data bits, 1 even parity bit and 1 stop bit (i.e. 11 bits per character), the master requests the reading of 32 bits.
The exchanges are made via the message interface (i.e. by Text block) and the scan time of the PLC is 80 milliseconds.
Trm
Tmp
Tpr
Tmr
Tmt
Total time
= 1000 x 8 x 11 / 9600 =
= (1000 x 3.5 x 11 / 9600) + 4.5 =
= 6 x 80
= 1000 x 8 x 11 / 9600
=
=
=
=
9.2 ms
8.5 ms
480 ms
1.0 ms
9.2 ms
508 ms
The time envelope of the master could therefore be fixed at 520 milliseconds.
___________________________________________________________________________
70
Appendix 9
_______________________________________________________________________________________
9.2
Response Time of the Master
Calculating the Response Time
The response time of the master (i.e. of one complete Modbus ® question-and-answer transaction) is the sum of the following transfer times (the times given below are for the most unfavorable cases) :
●
The time (Trr) to receive a request from the processor,
●
●
The time (Tmp) for the module to process the message,
The time (Ttt) to transmit a message to the slave,
●
●
●
●
The time (Trs) for the slave to prepare its reply,
The time (Tst) for the slave to transmit its reply to the master,
The time (Tpr) for the master to process the slave's reply,
The time (Tsr) for the processor to reply.
The time to receive a request from the processor.
Trr = 2 x (PLC scan time)
The time for the module to process the message.
Tmp is the time required by the module to receive the processor request and to prepare the message for transmission to the slave. This time depends on the request (Modbus function, number of objects, etc.).
The time to transmit a message of N characters to the slave.
Ttt = 1000 x N x (Number of bits per character)/(baud rate).
The time for the slave to prepare its reply.
Trs is the response time of the polled slave, less transmission time.
The time for the slave to transmit its reply of M characters to the master.
Tst = 1000 x M x (Number of bits per character)/(baud rate).
The time for the master to process the slave's reply.
Tpr is the time that the module takes to analyze the Modbus reply from the slave and to convert the reply for transmission to the processor. This time depends on the request
(Modbus function, number of objects, etc.).
The time, for the processor to reply.
Tsr = 2 x (PLC scan time).
Examples
In these examples, the data link has a speed of 9600 baud and a character format of 1 start bit, 8 data bits, 1 even parity bit and 1 stop bit (i.e. 11 bits per character) and the scan time of the PLC is 60 milliseconds.
___________________________________________________________________________
71
_______________________________________________________________________________________
Writing of 16 words :
Trr = 120 ms
Tmp
Ttt = 1000 x 41 x 11 / 9600
Trs : time depends on slave considered
= 8.3 ms
= 47 ms
Tst = 1000 x 8 x 11 / 9600
Tpr
Tsr
= 9.2 ms
= 2.1 ms
= 120 ms
Total time : 307 ms + (slave processing time)
Reading of 256 bits :
Trr = 120 ms
Tmp
Ttt = 1000 x 8 x 11 / 9600
Trs : time depends on slave considered
= 1.8 ms
= 9.2 ms
Tst = 1000 x 37 x 11 / 9600
Tpr
= 42.4 ms
= 8.6 ms
Tsr = 120 ms
Total time = 302 ms + (slave processing time)
___________________________________________________________________________
72