FTX 117 ADJUST
Adjustment Terminal
Instruction for use
2
Description of FTX 117 ADJUST terminal
The FTX 117 ADJUST terminal is an adjustment tool for TSX Nano, TSX Micro and
TSX Premium PLCs (TSX 07, TSX 37 and TSX 57).
The power supply of the FTX 117 ADJUST terminal is provided by the PLC via connection cable T FTX CB1 020 (length 2m) or cable T FTX CB1 050
(length 5m).
The FTX 117 ADJUST terminal can only be connected to the PLC terminal port.
WARNING:
!
It is not advisable to connect the FTX 117 ADJUST terminal to a TSX P ACC 01 junction box powered by a TSX Nano since this may cause the PLC to malfunction.
The following SRAM type PCMCIA memory cards should be used to back up object lists and for remote loading (programs and data) :
• T FTX RSM 3216
• T FTX RSM 12816
• TSX MRP 032
• TSX MRP 064
• TSX MRP 0128
WARNING: The space available on the PCMCIA memory cards is less than the capacity shown :
• 32k16 cards : 28K16 available
• 64k16 cards :
• 128k16 cards :
59K16 available
123K16 available
Communication
The FTX 117 ADJUST terminal is a UNI-TELWAY slave with address 1.
If another terminal is connected to the auxiliary terminal port, the configuration of this terminal must be modified by setting the BASE parameter to a value • 2 (if there is no other device at this address) so that the two terminals may communicate simultaneously.
When the terminal is connected, the "Connection" screen appears. Refer to this section.
Operating modes of the FTX 117 ADJUST terminal
Editor selection
0
Information
Inf
ADJUST 117 V2.0
App: STATION
TSX 3722
1TSX 2Dat 3Dti
< Main screen Edit <
1
TSX
2
Dat
3
Dti
PLC Data Object list
0 Information 0 Information 0 Information
1
Real-time clock
1
Conversion
1
Conversion
2
Run
3 Stop
4 Init
2
Bit value
2
Bit value
3 Transfer
4 Clear
4
Frc
5
FTX
6
Adr
7
Trf
Forcing Terminal Changing Remote
0 Information connection loading
1
Language
2
Preferences
Selection principles
Main screen
/
*
=
+
Selects a line in a screen or field
0
7 to or
*
+ r
Selects an element in the line or the value of a parameter followed by the sign (multiple choice)
Editor screen
Edit r
Esc
Confirms the selection
Cancels the last modification
Abandons an operation
Menu
0
7 to or
*
+ r
Shift
Shift
Menu
/
=
Goes to start of object list
Goes to end of object list
Function screen
Goes to menu. Warning: while the menu is displayed, screen animation is frozen.
Entering and modifying an object or list of objects
%M Access type of variable mentioned on keyboard (eg: %M=Boolean)
Var r
Access all variables using a selection list or by directly entering the code of the variable
Shift Select the upper part of the key
Ins Insert a blank line above the object indicated by the cursor
Esc Abandon entry or abandon insert mode
Del Delete the last figure entered in numerical entry
Values are entered using alphanumeric keys 0 to F and confirm with r
.
3
Information Editor Inf
Displays information relating to the ADJUST software version of the FTX117 terminal.
PLC Editor
Displays the PLC type and status:
TSX
• type of PLC connected
(example : TSX 07 20-10)
• RUN or STOP, ERR, default
I/O
• name of application, presence of forced bits: f
• diagnostics module connected (TSX07 only)
• PLC version (TSX37, TSX 57 only)
TSX 07 20-10
RUN E RR I/O
APP: Exec f
Mod0=OK
Menu
Menu
0
1
Inf:displays information on PLC status
Clk: updates clock and date/time and cause of last stop
(if PLC has realtime clock) (Context-specific selection)
Menu
Menu
Menu
2
3
4
Run: sets PLC to RUN (Context-specific selection)
Stp: sets PLC to STOP (Context-specific selection)
Ini: initializes PLC application (Context-specific selection)
Modifying date and time in the PLC
/ =
Access selection of various elements to be adjusted:
- day of the week,
- day,
- month,
- year,
- time
* +
Fr 10 Mar1996
17:26:48
STP= 2 Jan 1996
2 17:07:23
Select value of element indicated by the cursor.
The number of the day, year and time is entered using the numerical keyboard.
r
Confirm modifications
Meaning of the last stop code
The last two lines of the screen display the date and time of the last PLC stop. A code indicates the reason for the stop :
• 1= terminal changed from RUN to STOP,
• 2= stop due to software fault (PLC task overrun),
• 4= power failure,
• 5= stop due to hardware fault,
• 6= stop due to HALT instruction (TSX37 and TSX57 only).
4
Data Editor Dat
Accesses all PLC variables in order to display, modify or force their value.
Pressing the key corresponding to the type of object required displays the list of these objects starting from the position specified.
Eg: %KWi key and
1 0 ∅
displays %KW10 to %KWn (according to the number declared during configuration).
Menu
Menu
0
1
Menu
2
Menu
3
Menu
4
Inf: displays information on PLC status
Cnv: modifies the display base of non-Boolean variables: decimal, hexadecimal, binary, ASCII (contextual selection)
Bit or S/R: modifying the value of the Boolean variable indicated by the cursor: set, reset, force to 0, force to 1, unforce, unforce module
(contextual selection)
G7 : when a GRAFCET step is indicated by the cursor, this menu :
- Activates/Deactivates the step indicated,
- Initializes the chart,
- Resets the steps of the chart,
- Freezes/Unfreezes the chart.
Sts: indicates the number of active steps and the number of active transitions (this menu is only available if the editor displays GRAFCET steps)
Dgn: displays the status of the chart (this menu is only available if the editor displays GRAFCET steps)
Displaying and modifying a Boolean object (eg: system bit and output bit)
Edit
2
Accesses data editor %S0 0
%S
0
Selects Boolean %S0 (internal bit) r
Menu
2
Confirms. Displays variable
S/R: changes bit %S0 to 1
%S1 0
%S2 0
%S3 0
Edit
%Q r
2
0
Menu
2
.
0
Accesses data editor
Selects output 0 of module 0
Confirms. Displays variable
Set r
Bit: modifies output:
• Set set to 1
• Force 0 forcing to 0
• Force 1 forcing to 1
• Unforce module global unforcing
of I/O module
%Q0.0 = 0.
0000001010
......f...
f : forced state
! : channel faulty
s : channel not exchanged
5
For an object bit of a module, to display or modify a channel in the module, move the cursor under the object to be displayed or modified:
+ *
Shift
Shift
*
+
Moves cursor from one channel to another
Moves cursor in 8-channel steps
Note:
The following display may appear on the screen in the case of a module fault:
Err = 00000010
The significance of these bits is as follows:
• Bit 0: Internal fault (hardware failure)
• Bit 1: Functional fault (no power supply, etc)
• Bit 2: Terminal block fault
• Bit 3: Self-test
• Bit 4: -
• Bit 5: Configuration fault
• Bit 6: Module missing or not powered up
• Bit 7: Down fault
Displaying and modifying a numerical variable (eg: Internal word)
Edit
%MW
2
0
Accesses data editor
Selects internal word %MW0 r
Confirms. Displays variable
Indicate the variable to be modified using the
/ and
= arrows, enter the value and confirm with r
%MW0 0
%MW1 256
%MW2 12
%MW3 0
Modifying the display base of objects (eg: hexadecimal)
Menu
1
Cnv Access selection of base:
• Hex
• Dec
• Bin
• Ascii
Indicate the required base using the
/ and
= keys, confirm with r
%MW0 16#0000
%MW1 16#0100
%MW2 16#000C
%MW3 16#0000
6
Displaying an object associated to an I/O channel
For complex objects or those not known to the keyboard, it is possible to enter the variable using a guided access. Eg: input channel word
Var r
Access selection of object type
4
3
Select objects associated with I/O
Select input word type %IW
Enter the number of the module, channel and position and confirm with r
. The position is optional: 0 if not known.
%IW0.0 0
%IW0.1 0
%IW1.0 200
%IW1.1 0
Displaying and modifying a GRAFCET step
Grafcet steps are accessed by pressing the %X key followed by the number of the step to be displayed.
%Xn: Displays the number of the step to which the cursor is pointing. Example %X0 for step 0.
T: Activity time of the step to which the cursor is pointing. Example T=0 indicates that step
%X0 is not activated. The time is indicated in 100ms.
%X0 T=0
0123456789
0. _ n
1.
0. : Tens digit for the step number.
0123456789: Units digit for the step number.
state : n step active nothing step inactive
The step display screen is in the form of a table where the rows indicate the number of tens of the step number and the columns the units.
The state of the step concerned is displayed at the point at which the tens row and the units column cross. In the example above, step 3 is active.
/ =
+ *
Used to change the display of the tens for the step number (within the limits of the PLC configuration).
Used to select the unit for the step number within the tens display selected.
7
Object list editor
!
Dti
Displays or modifies the values of a list of 16 variables.
Menu
Menu
0
1
Inf: displays information on the PLC status
Cnv: modifies the display base of non-Boolean variables
(decimal, hexadecimal, binary, ASCII)
Menu
2
Bit or S/R: modifies the value of the Boolean variable indicated by the cursor (set, reset, force to 0, force to 1, unforce, unforce module)
G7: activates or deactivates the GRAFCET object indicated by the cursor
Menu
Menu
3
4
Trf: transfer function: stores or retrieves a list
Clr: deletes current object list
Del Deletes list object indicated by the cursor
The method of entering and modifying objects and their value is the same as for the data editor.
Storing/Retrieving a list of objects
This function requires a PCMCIA memory card in the terminal. It is possible to store up to 63 different lists on the same card.
Formatting
Menu
3
Accesses type of transfer
Selects the option Format Card using the
+ *
keys to format a blank PCMCIA card.
Confirm with r
This formatting is specific to storing lists of objects.
Transfer list
Format Card
ADJ(max 62):
Storage
Menu
3
Accesses type of transfer
Selects the FTX -> Card transfer using the
+ *
keys to execute storage on the PCMCIA.
Enter the storage number between 0 and 62, confirm with r
Retrieval
Menu
3
Accesses type of transfer
Transfer list
FTX -> Card
ADJ(max 62):
Selects the Card -> FTX transfer using the
+ *
keys to retrieve to the terminal.
Enter the storage number between 0 and 62, confirm with r
Transfer list
Card -> FTX
ADJ(max 62):
If the storage number is omitted, a list of stored files is displayed and one of these should be selected. The letter 'd' next to a file indicates that this file already contains a list which corresponds to the type of processor connected. An asterisk '*' indicates that the list contained in the file does not correspond to the type of processor connected.
8
A message "Card Error" followed by a code, may appear in the following situations:
Code
2
6
7
3
4
53
54
Cause
The type of card is not recognized
Card not formatted
The card is not compatible
The card inserted is not a TELEMECANIQUE card
Recharge the battery
Card not formatted
Processing error
Find forced bit editor " Frc
Searches for and displays forced bits. The search is governed by the forced bits present in the PLC.
Edit
4
Accesses find editor
%Q: Selects output bit type %Q r
Confirms. Displays result of search
%Q0.0 1f
End of list
The / = keys start searching on the previous or next module.
The Shift / and Shift = keys start:
• Discrete modules: start searching on the previous or next channels
• Non-discrete modules: start searching on the previous or next positions
Terminal editor
#
FTX
Sets the parameters of the FTX117 terminal.
0
1
2
Inf: displays the software version
FTX117
ADJUST 117 V2.0
Lan: selects the working language of the terminal from 5 languages: French, English,
German, Italian and Spanish
(C) 1996-97 SA
0Inf 1Lan 2Prf
Prf: selects:
• Sound audible response or not when keys pressed
• Back light controls the length of time the screen remains lit following the last time a key was pressed. This time will be between 5 and 60 minutes.
3
The value 0 deactivates this function.
Selections are made using the
+ * keys
Tst: starts terminal self-tests (Reserved for Schneider Automation)
Connection
$
Adr
Changes the PLC address in order to be able to adjust a slave PLC on UNI-TELWAY.
/ =
Selects the Master or Slave option
Master option: Confirm with r
Slave option: Enter the number of the slave between 1 and 98, confirm with
Esc Cancels modification r
CONNECTION
Master
Slave
Number: ..
9
Remote loading Editor
%
This is used to load programs and %MW data remotely from the PLC to the terminal and vice versa.
/ =
Used to select the type of remote loading or management of the PCMCIA card.
These selections are context-specific.
Program: Loads a program remotely.
%MW data: Loads %MW data remotely.
REMOTE LOADING
PROGRAM
%MW DATA
CARD MANAGEMENT
Card management: Manages the PCMCIA card.
r
Confirms the selection
Remote loading of a program
/ =
Used to select the direction for remote loading or comparison of the program.
TSX->FTX: Downloads the program from the PLC and stores it on a PCMCIA card.
FTX->TSX: Uploads the program from the
PCMCIA card to the PLC.
PROGRAM
TSX -> FTX
FTX -> TSX
COMPARISON
Comparison: Compares the PLC program with that on the
PCMCIA card.
r
Confirms the selection
Program TSX->FTX
This screen displays:
- The name of the application, which is the name of the file stored on the PCMCIA card.
- The date and time of the PLC realtime clock, which will be the attributes of the file stored on
PROG: TSX -> FTX
App: STATION
16.12.96 09:33
Y:ENTER N:ESC the PCMCIA card.
* +
Modifies the date and time.
r
Confirms the program download
Notes:
• The program on the PCMCIA card cannot be executed in the PLC when the card is inserted into the processor (special format).
• The PCMCIA card can only contain a single program file.
Program FTX->TSX
This screen displays the name of the file found on the PCMCIA card as well as the date and time of this file.
r
Confirms the program upload
PROG: FTX -> TSX
STATION.PRG
16.12.96 09:33
Y:ENTER N:ESC
For TSX Nano, the user has the option of protecting the transferred program.
10
Program FTX->TSX (continued)
For TSX Nano and TSX Micro, if the transferred program is executed in the PLC internal RAM, the user is prompted to save it in the PLC internal FLASH at the end of the transfer if its size is <15Kb.
Note: this operation overwrites the values of any internal words saved in the Flash memory of the TSX Micro (if the %MW->FLASH function described on page 12 is used).
If the message "Appli. and TSX incompatible" appears, the transfer will not be performed. Possible causes of errors are:
• Type of TSX configured differs from and is incompatible with the connected PLC.
• Size of RAM configured is greater than the size of RAM of the connected PLC.
• Size of cartridge configured is greater than the size of cartridge of the connected
PLC.
• Cartridge configured but missing in the connected PLC.
• Cartridge not configured but present in the connected PLC.
• Application level higher than that of the connected PLC.
Comparison
This screen displays the name of the application in the PLC as well as the name of the file found on the
PCMCIA card.
r
Confirms the comparison which may result in:
• IDENTITY: the 2 applications are identical
• DIFFERENCE: the 2 applications are different
COMPARISON
APP: STATION
STATION.PRG
Y:ENTER N:ESC
Remote loading of %MW data
/ =
Used to select the direction for the remote loading of %MW data.
TSX->FTX: Downloads %MW data from the PLC and stores it on a PCMCIA card.
FTX->TSX: Uploads data from the PCMCIA card to the PLC.
%MW->FLASH: Transfers %MW data from the
PLC to the internal Flash of the PLC.
r
Confirms the selection
%MW DATA
TSX -> FTX
FTX -> TSX
%MW -> FLASH
%MW data TSX->FTX
This screen displays the limits of the %MW data to be saved as well as the date and time of the PLC realtime clock which will be the attributes of the file stored on the PCMCIA card.
It is possible to save up to 10 files of %MW data for a single application on the PCMCIA card.
%MW: TSX->FTX 0
0 - 2000
16.12.96 09:33
Y:ENTER N:ESC
The number at the top right of the screen indicates the number of the data file.
* + / =
Move to limits, date and time fields to modify them.
r
Confirms saving of data
11
%MW data FTX->TSX
This screen displays the limits of the %MW data saved in the first data file found on the PCMCIA card as well as the date and time of this file.
The number at the top right of the screen indicates the number of the data file.
The + sign at the bottom right indicates that there are
%MW: FTX->TSX 0
0 - 2000
16.12.96 09:33
Y:ENTER N:ESC + several data files on the card.
/ =
Used to access the previous/next file stored on the PCMCIA card.
r
Confirms file selection
After confirmation of the transfer of the selected file, a screen is used to select the transfer modes:
Reset %MW: Initialization of the whole internal
%MW data zone of the PLC before transferring the new data.
%MW: FTX -> TSX
Reset %MW: N
%MW -> FLASH: N
%MW->FLASH: Memorization of the new data in the internal FLASH memory of the PLC. Possible for %MW0 to %MW999.
Warning: This selection is context-specific. The %MW->FLASH transfer is only available on a TSX Micro PLC version • 2.0. Moreover, the program contained in the
RAM memory is also transferred to the FLASH memory.
/ =
Used to change from one mode to the other.
* +
Used to change the choice of mode selected (Y or N).
Note: The message "TSX comm.error" may appear during loading if an attempt is made to transfer %MW not configured in the PLC.
%MW data ->FLASH
Memorizes the %MW data from %MW0 to %MW999 (or maximum configured %MW if <999) in the internal FLASH memory of the PLC. The program contained in the RAM memory is also transferred to the FLASH memory.
Card management
This screen displays the names of the files found on the PCMCIA card.
/ =
Used to display the names of the previous
Menu
0 or next files.
Inf: displays additional information
Menu
Menu
STATION.PRG
STATION.DT0
STATION.DT1
on the selected file.
1
Del: deletes the selected file.
STATION.DT2
2
For: formats the PCMCIA card (specific to remote loading).
A PCMCIA card dedicated to remote loading can contain a single and unique program file and up to 10 data files associated with this program (including station name). This card cannot contain object list backup files.
Note: *.TMP files may appear if a problem is encountered when loading a program or data remotely.
12
List of accessible Boolean objects
Type Syntax TSX TSX TSX Keys
07 37 57
Internal bit %Mi
System bit %Si
128 256 4096 %M or
max Var 1 1
128 128 128 %S or
Var 1 2
Word extract bit <word>:Xj j=0to15
List of accessible word objects
Type Syntax
Internal word %MWi
%MWi:Xj
TSX TSX TSX Keys
07 37 57
256 32768 32768 %MW or
Constant word
System word
Common word on network 0
Common word on other network
Internal double word
%KWi
%SWi
%NW{j}k
j=station no.
k=word no.
%NW{i.j}k
i=network no.
j=station no.
k=word no.
%MDi
Constant double word %KDi
64
max max Var 2 1
32768 32768 %KW or
max max Var 2 2
128 128 128 %SW or
Var 2 3
%NW or
32 32 Var 2 4
4 4
%NW or
256 256 Var 2 4
32 32
4 4
32768 23768 %MD or
max max Var 2 5
32768 32768 %KD or
System double word
32-bit floating point
%SDi
%MFi
max max Var 2 6
128 128 %SD or
Var 2 7
32768 32768 %MF or
max max Var 2 8
Floating point constant %KFi
1 No bit forcing on TSX07
2 Some system bits and words can be written
32768 32768 Var 2 9
max max
Principle of addressing in-rack module
TSX TSX TSX
07 37 57
In-rack module main secondary
Module module-rack
0 to 4 0 to 10 0 to 10
1 to 7
0 to 10
R, W
R
R, W 2
R, W
R
Actions
R, W, F 1
R, W 2
R
Actions
R, W
R, W
R, W 2
R, W
R, W
13
Principle of addressing module on bus
TSX07 (Nanet) \4.0\m.c
TSX 07 TSX 37 m: 1 to 4 c: 0 to 13
module address: m=I/O module c=I/O channel
TSX 57
List of objects associated with an I/O channel
Type Syntax TSX TSX TSX Keys
07 37 57
I/O logic channel object
Periodic inputs %I
Channel fault bit
%CH<@mod>.<channel>
%I<@mod>.<channel>.ERR 1 Var4 7
Input bit
Input word
%I<@mod>.<channel> 1
%I<@mod>.<channel>.<pos.>
%IW<@mod>.<channel>
%IW<@mod>.<channel>.<pos.>
Input double word %ID<@mod>.<channel>
%ID<@mod>.<channel>.<pos.>
Input floating point %IF<@mod>.<channel>.<pos.>
Periodic outputs %Q
Output bit %Q<@mod>.<channel> 1
14
2
32
32
32
64
256 256 Var4 1/12
64
256 256 Var4 3/14
64
%I or
%IW or
%ID or
256 256 Var4 8
10 32 64 %Q or
Output word
%Q<@mod>.<channel>.<pos.>
%QW<@mod>.<channel>
%QW<@mod>.<channel>.<pos.>
Output double word %QD<@mod>.<channel>
%QD<@mod>.<channel>.<pos.>
2
Actions inacces
-sible
R
R, W, F
R, W
R, W
R, W, F
256 256 Var4 2/13
32 64 %QW or R, W
256 256 Var4 3/15
32 64 %QD or R, W
256 256 Var4 9
Output floating point %QF<@mod>.<channel>.<pos.>
Aperiodic elements %MW
Word %MW<@mod>.<channel>
%MW<@mod>.<channel>.<pos.>
Double word %MD<@mod>.<channel>
%MD<@mod>.<channel>.<pos.>
Floating point %MF<@mod>.<channel>.<pos.>
Constant elements %KW
Word %KW<@mod>.<channel>
32
32
64
64
%MW or
256 256 Var4 5
%MD or
256 256 Var4 10
R
R
Double word
Floating point
%KW<@mod>.<channel>.<pos.>
%KD<@mod>.<channel>
%KD<@mod>.<channel>.<pos.>
%KF<@mod>.<channel>.<pos.>
32 64 %KW or R
256 256 Var4 6
32 64 %KD or
256 256 Var4 11
R
Character string
%KB<@mod>.<channel>.<pos.>:
L<position>even
<@mod> =module address <channel> =channel no. (0 to 127)
<position> =position number (0 to 255). 0 is proposed if the position is not entered.
1 Object only available on discrete modules
14
List of objects associated with an I/O module
Type Syntax TSX TSX TSX Keys
07 37 57
Module channel object
Periodic inputs %I
%CH<@mod>.MOD
Module fault bit %I<@mod>.MOD.ERR
%I or
Var6 5
Input bit
Input word
%I<@mod>.MOD.<position>
%IW<@mod>.MOD
%IW<@mod>.MOD.<position>
Input double word %ID<@mod>.MOD.<position>
Input floating point %IF<@mod>.MOD.<position>
Periodic outputs %Q
Output bit %Q<@mod>.MOD.<position>
%IW or
256 256 Var6 1
Actions inacces
-sible
R
R, W
Output word %QW<@mod>.MOD
%QW<@mod>.MOD.<position>
Output double word %QD<@mod>.MOD.<position>
Output floating point %QF<@mod>.MOD.<position>
Aperiodic elements %MW
Word
Double word
Floating point
%MW<@mod>.MOD
%MW<@mod>.MOD.<position>
%MD<@mod>.MOD.<position>
%MF<@mod>.MOD.<position>
%QW or
256 256 Var6 2
%MW or
256 256 Var6 3
R, W
R
Constant elements %KW
Word %KW<@mod>.MOD
Double word
Floating point
%KW<@mod>.MOD.<position>
%KD<@mod>.MOD.<position>
%KF<@mod>.MOD.<position>
Type Syntax
%KW or
256 256 Var6 4
Character string
%KB<@mod>.MOD.<position>:
L<position>even
<@mod> =module address
List of function block objects
<position> =position number (0 to 255).
R
Actions TSX TSX TSX Keys
07 37 57
64 256 %T or Var3 5 PL7_3 timer current value preset
%Ti
%Ti,V
%Ti,P 1-9999 1-9999 output done output running
Timer current value
%Ti,D
%Ti,R
%TMi
%TMi,V
32 64 256
0/9999 0/9999 0/9999
%TM or Var3 1
R
R
R
R, W 1 preset output running
%TMi,P
%TMi,Q
0/9999 0/9999 0/9999
1 if the adjust option was selected during configuration
R, W
R, W 1
R
15
List of function block objects (continued)
Type Syntax TSX TSX TSX Keys
07 37 57
8 256 %MN or Var3 6 Monostable current value preset output running
%MNi
%MNi,V
%MNi,P
%MNi,D
1/9999 1/9999
16 32 256 %C or Var3 2
0/9999 0/9999 0/9999
Up/Down Counter current value preset output empty output done output full
Register input word
%Ci
%Ci,V
%Ci,P
%Ci,E
%Ci,D
%Ci,F
%Ri
%Ri,I
0/9999 0/9999 0/9999
4 4 256
-32768 -32768
%R or Var3 3
32767 32767 output word output full output empty
Drum output full
%Ri,O
%Ri,F
%Ri,E
%DRi
%DRi,F not running activity time
%DRi,S
%DRi,V
Pulse width modulator %PWM preset %PWM,P percentage %PWM,R
Pulse generator preset number of pulses output running output done
Fast counter threshold 0 threshold 1 current value
%PLS
%PLS,P
%PLS,N
%PLS,Q
%PLS,D
%FC
%FC,S0
%FC,S1
%FC,V
4
1
1/32767
0/100
1
1/32767
0/32767
1
0/65535
0/65535
8 256 preset output full
%FC,P
%FC,F output overrun S0 %FC,TH0 output overrun S1 %FC,TH1
0/65535
1 if the adjust option was selected during configuration
%DR or Var3 4
Var3 7
Var3 6
Var3 5
Actions
R
R
R
R
R
R
R
R, W 1
R
R
R
R, W
R, W 1
R
R, W
R
R,W
R,W 1
R, W
R
R
R, W
R, W
R
R
R
R, W
R
16
List of function block objects (continued)
Type Syntax TSX TSX TSX Keys
07 37 57
1 Var310 Message block output link error output available
Shift register
%MSG
%MSG,E
%MSG,D
%SBRi 8 Var38 register bit
Step to step i = 0 to 7
%SBRi,j j = 0 to 15
%SCi i = 0 to 7
Step to step bit number %SCi,j j = 0 to 255
16
8
256
Var39
List of Grafcet objects
Type
Step status
Step activation time
Syntax
%Xi
%Xi,T
Actions
R
R
R
R
TSX TSX TSX Keys
07 37 57
62 96/
128
128 %X or Var5 1
Actions
R, W 1
96/ 128 indirect
128 access
Macro-step status
1 except TSX07: read only
%XMj
17
18
W913294100802A-03
Schneider Automation Inc.
One High Street
North Andover, MA 01845
Tel.: (1) 508 794 0800 - Fax: (1) 508 975 9010
Schneider Automation S.A.
245, route des Lucioles - BP 147
F-06903 Sophia Antipolis
Tel.: (33) (0)4 92 96 20 00 - Fax: (33) (0)4 93 65 37
Schneider Automation GmbH
Steinheimer Straße 117
D-63500 Seligenstadt
Tel.: (49) 6182 81 2584 - Fax: (49) 6182 81 2860
Printed in July 2005
Download
Advertisement