Schneider Electric Quantum EIO - Remote I/O Modules Configuration Guide
إعلان
إعلان
Quantum EIO
Remote I/O Modules
Installation and Configuration Guide
Original instructions
S1A48978.14
02/2022 www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
As part of a group of responsible, inclusive companies, we are updating our communications that contain non-inclusive terminology. Until we complete this process, however, our content may still contain standardized industry terms that may be deemed inappropriate by our customers.
Remote I/O Modules
Table of Contents
S1A48978.14
Safety Information
.......................................................................................7
Operation and Adjustments .........................................................................9
About the Book
..........................................................................................10
Characteristics of Ethernet Remote I/O Modules
.................................12
Quantum EIO 140CRP31200 Head Module Description ..............................12
Quantum EIO Adapter Module Descriptions................................................14
Installation
..................................................................................................21
Installing Quantum EIO Modules................................................................21
Installing the Quantum Controller .........................................................21
Mounting a Quantum EIO-Compatible Module on the Backplane ............22
Quantum EIO-Compatible Module Installation Considerations................23
Remote I/O Network Cable Installation .................................................24
Installing the Communications Adapter on the Remote Drop ........................26
Installing a Quantum EIO Adapter Module ............................................26
Installing Ethernet Remote I/O Drops on a Remote Rack .......................27
Setting the Location of the Ethernet Remote I/O Drop ............................28
Remote I/O Infrastructure Cables...............................................................29
Duplicate IP Address Checking ............................................................30
Loss of I/O Connection ........................................................................31
Configuration and Programming with Control Expert
Creating a Control Expert Project...............................................................32
Configuring the Local Rack ..................................................................32
Configuring the Ethernet Remote I/O Drop............................................34
Available Control Expert Configuration Tabs .........................................35
NTP Configuration in Control Expert.....................................................36
Control Expert Configuration for Remote I/O Ethernet Modules ....................37
IP Configuration..................................................................................38
RSTP Bridge Configuration..................................................................39
SNMP Agent Configuration ..................................................................39
Service Port Configuration ...................................................................41
Control Expert Configuration for Ethernet Remote I/O Drops........................42
Configuring the Size and Location of Data ............................................43
Configuring the Parameters .................................................................43
Device DDT Parameters......................................................................46
Time Stamping ...................................................................................47
Device DDT Names for the Quantum EIO Remote I/O Head
Device DDT Names for Quantum EIO Remote I/O Adapter
Elementary Functions (EFs) and Function Blocks (EFBs) ............................55
Using Quantum Function Blocks in M580 Systems ................................55
3
Remote I/O Modules
4
Downloading the Application to the PLC ...............................................56
Explicit Messaging
....................................................................................58
EtherNet/IP Explicit Messaging Using MBP_MSTR .....................................58
Supported MBP_MSTR Function Codes...............................................58
EtherNet/IP Explicit Messaging Services ..............................................58
Configuring the CONTROL and DATABUF Parameters..........................60
Explicit Messaging via the Control Expert GUI ............................................61
Sending Explicit Messages to EtherNet/IP Devices................................61
Immediate I/O Access (IU_ERIO) ..............................................................63
Implicit Messaging
....................................................................................66
The MAST Task in Implicit Exchanges........................................................66
Diagnostics
................................................................................................67
LED Indicators on the 140 CRP 312 00 Module .....................................67
LED Indicators on the Quantum EIO Adapter Module ............................68
Service Port Management .........................................................................70
Service Port Configuration ...................................................................70
Service Port Configuration for Adapter Modules ....................................70
Diagnostics Available through the CPU ......................................................71
System Diagnostics ............................................................................71
Device Data Types for the Remote I/O Modules ....................................73
Diagnostics Available through Modbus/TCP ...............................................73
Modbus Diagnostic Codes ...................................................................73
Diagnostics Available through EtherNet/IP CIP Objects ...............................81
About CIP Objects ..............................................................................81
Assembly Object.................................................................................83
Connection Manager Object ................................................................84
Quality Of Service (QoS) Object...........................................................86
TCP/IP Interface Object.......................................................................87
Ethernet Link Object............................................................................88
EtherNet/IP Interface Diagnostics Object ..............................................91
EtherNet/IP IO Scanner Diagnostics Object ..........................................93
IO Connection Diagnostics Object ........................................................94
EtherNet/IP Explicit Connection Diagnostics Object...............................96
EtherNet/IP Explicit Connection Diagnostics List Object.........................97
RSTP Diagnostics Object ....................................................................98
Service Port Control Object ............................................................... 100
Diagnostics Available through Control Expert............................................ 102
Device Services................................................................................ 102
EtherNet/IP Objects .......................................................................... 103
Service Port Management (Online Action) .......................................... 103
Pinging the 140CRP31200 Module..................................................... 104
Displaying I/O Memory Consumption.................................................. 105
Logging DTM Events to a Control Expert Logging Screen .................... 106
Firmware Upgrade
.................................................................................. 108
Firmware Update with Automation Device Maintenance ............................ 108
140CRP31200 Firmware Upgrade with OS Loader ................................... 108
S1A48978.14
Remote I/O Modules
Adapter Firmware Upgrade with Unity Loader ........................................... 110
Glossary
Index
S1A48978.14
5
Safety Information
Remote I/O Modules
Important Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
!
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
Before You Begin
Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine.
S1A48978.14
7
8
Remote I/O Modules
WARNING
UNGUARDED EQUIPMENT
• Do not use this software and related automation equipment on equipment which does not have point-of-operation protection.
• Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes. The type or model of automation equipment suitable for each application will vary depending on factors such as the control function required, degree of protection required, production methods, unusual conditions, government regulations, etc. In some applications, more than one processor may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and factors present during setup, operation, and maintenance of the machine and, therefore, can determine the automation equipment and the related safeties and interlocks which can be properly used. When selecting automation and control equipment and related software for a particular application, you should refer to the applicable local and national standards and regulations. The National
Safety Council's Accident Prevention Manual (nationally recognized in the United
States of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as point-of-operation guarding must be provided. This is necessary if the operator's hands and other parts of the body are free to enter the pinch points or other hazardous areas and serious injury can occur. Software products alone cannot protect an operator from injury. For this reason the software cannot be substituted for or take the place of point-of-operation protection.
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have been installed and are operational before placing the equipment into service. All interlocks and safeties related to point-ofoperation protection must be coordinated with the related automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for pointof-operation protection is outside the scope of the Function Block Library,
System User Guide, or other implementation referenced in this documentation.
Start-up and Test
Before using electrical control and automation equipment for regular operation after installation, the system should be given a start-up test by qualified personnel to verify correct operation of the equipment. It is important that arrangements for such a check are made and that enough time is allowed to perform complete and satisfactory testing.
WARNING
EQUIPMENT OPERATION HAZARD
• Verify that all installation and set up procedures have been completed.
• Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.
• Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
S1A48978.14
Remote I/O Modules
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not installed according to local regulations (according to the
National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
• Remove tools, meters, and debris from equipment.
• Close the equipment enclosure door.
• Remove all temporary grounds from incoming power lines.
• Perform all start-up tests recommended by the manufacturer.
Operation and Adjustments
The following precautions are from the NEMA Standards Publication ICS 7.1-1995
(English version prevails):
• Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is improperly operated.
• It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments. Personnel who have access to these adjustments should be familiar with the equipment manufacturer’s instructions and the machinery used with the electrical equipment.
• Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
S1A48978.14
9
Remote I/O Modules
About the Book
Document Scope
PlantStruxure is a Schneider Electric program designed to address the key challenges of many different types of users, including plant managers, operations managers, engineers, maintenance teams, and operators, by delivering a system that is scalable, flexible, integrated, and collaborative.
This document presents one of the PlantStruxure features, using Ethernet as the backbone around the Quantum PLC offer and connecting a Quantum local rack to
Quantum and Modicon X80 remote I/O drops and distributed I/O devices. This feature is known as Quantum Ethernet I/O or Quantum EIO. ( NOTE: Modicon X80 is the generic name given to the M340 I/O modules when they are connected remotely to a Quantum controller or module in a PlantStruxure architecture. The
M340 I/O name is still used when the module is connected to a M340 controller.
The product references remains unchanged; only the range name changes.
)
This guide describes these modules and their roles in a Quantum EIO system:
• 140CRP31200: remote I/O head module on a Quantum local rack in a remote
I/O main ring
• 140CRA31200: remote I/O adapter module in a Quantum remote I/O drop
• BMXCRA312•0: remote I/O adapter module in a Modicon X80 remote I/O drop
NOTE: The specific configuration settings contained in this guide are for instructional purposes only. The settings required for your specific application can be different from the examples presented in this guide.
NOTE: The architectures described in this document have been tested and validated in various scenarios. If you intend to use architectures different than the ones described in this document, test and validate them thoroughly before implementing.
Validity Note
This document is valid for the Quantum EIO system when used with
EcoStruxure ™ Control Expert 15.0 or later.
The technical characteristics of the devices described in the present document also appear online. To access the information online, go to the Schneider Electric home page www.se.com/ww/en/download/ .
The characteristics that are described in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.
Related Documents
Title of Documentation
Quantum EIO, System Planning Guide
Quantum EIO, Distributed Network, Installation and Configuration Guide
Quantum EIO, Control Network, Installation and
Configuration Guide
Reference Number
S1A48959 (English), S1A48961 (French),
S1A48962 (German), S1A48964 (Italian),
S1A48965 (Spanish), S1A48966 (Chinese)
S1A48986 (English), S1A48987 (French),
S1A48988 (German), S1A48990 (Italian),
S1A48991 (Spanish), S1A48992 (Chinese)
S1A48993 (English), S1A48994 (French),
S1A48995 (German), S1A48997 (Italian),
S1A48998 (Spanish), S1A48999 (Chinese)
10 S1A48978.14
Remote I/O Modules
Title of Documentation
Quantum using EcoStruxure ™ Control Expert,
Change Configuration On The Fly, User Guide
Quantum using EcoStruxure
Modicon X80, Analog Input/Output Modules,
User Manual
Modicon X80, Discrete Input/Output Modules,
User Manual
Modicon X80, BMXNOM0200 Serial Link
Module, User Manual
Modicon X80, BMXEHC0200 Counting Module,
User Manual
Modicon X80, BMXERT1604T Time Stamp
Module, User Guide
™ Control Expert,
Hot Standby System, User Manual
Modicon X80, BMXNRP0200/0201 Fiber
Converter Modules, User Guide
Reference Number
S1A48967 (English), S1A48968 (French),
S1A48969 (German), S1A48970 (Italian),
S1A48972 (Spanish), S1A48976 (Chinese)
35010533 (English), 35010534 (French),
35010535 (German), 35013993 (Italian),
35010536 (Spanish), 35012188 (Chinese)
EIO0000001108 (English), EIO0000001109
(French), EIO0000001110 (German),
EIO0000001111 (Spanish), EIO0000001112
(Italian), EIO0000001113 (Chinese)
35011978 (English), 35011979 (German),
35011980 (French), 35011981 (Spanish),
35011982 (Italian), 35011983 (Chinese)
35012474 (English), 35012475 (German),
35012476 (French), 35012477 (Spanish),
35012478 (Italian), 35012479 (Chinese)
EIO0000002696 (English), EIO0000002697
(French), EIO0000002698 (German),
EIO0000002699 (Italian), EIO0000002700
(Spanish), EIO0000002701 (Chinese)
35013355 (English), 35013356 (German),
35013357 (French), 35013358 (Spanish),
35013359 (Italian), 35013360 (Chinese)
EIO0000001121 (English), EIO0000001122
(French), EIO0000001123 (German),
EIO0000001125 (Italian), EIO0000001124
(Spanish), EIO0000001126 (Chinese)
EcoStruxure
Languages and Structure, Reference Manual
EcoStruxure
™
™
Control Expert, Program
Control Expert, System Bits and
Words, Reference Manual
35006144 (English), 35006145 (French),
35006146 (German), 35013361 (Italian),
35006147 (Spanish), 35013362 (Chinese)
EIO0000002135 (English), EIO0000002136
(French), EIO0000002137 (German),
EIO0000002138 (Italian), EIO0000002139
(Spanish), EIO0000002140 (Chinese)
EcoStruxure ™ Control Expert, Operating Modes 33003101 (English), 33003102 (French),
33003103 (German), 33003104 (Spanish),
33003696 (Italian), 33003697 (Chinese)
Quantum using EcoStruxure ™ Control Expert,
Hardware Reference Manual
35010529 (English), 35010530 (French),
35010531 (German), 35013975 (Italian),
35010532 (Spanish), 35012184 (Chinese)
EcoStruxure ™ Control Expert, Installation
Manual
35014792 (English), 35014793 (French),
35014794 (German), 35014795 (Spanish),
35014796 (Italian), 35012191 (Chinese)
You can download these technical publications and other technical information from our website at www.se.com/ww/en/download/ .
S1A48978.14
11
Remote I/O Modules
Characteristics of Ethernet Remote I/O Modules
Characteristics of Ethernet Remote I/O Modules
Introduction
This chapter describes the head and adapter modules for Ethernet remote I/O communications in a Quantum EIO system. Specifically, those modules are:
• 140CRP31200: head module on a local Quantum rack
• 140CRA31200: adapter module on a Quantum remote I/O drop
• BMXCRA312•0: adapter module on a Modicon X80 remote I/O drop
This chapter includes physical characteristics, port descriptions, and agency specifications for these modules.
Quantum EIO 140CRP31200 Head Module Description
Introduction
The Quantum 140CRP31200 module is the remote I/O head module on the local rack of Quantum EIO installations. This module allows the PLC to connect to an
Ethernet network and control remote I/O devices.
Functionality
The main purpose of the 140CRP31200 module is to provide I/O scanning services of remote I/O devices on either a remote I/O network or a device network, which contains remote I/O and distributed I/O devices. The module is directly connected to the remote I/O network main ring, and it manages the remote I/O network through a daisy chain loop topology. This module also provides various
Ethernet services, such as configuration for remote I/O devices and diagnostics.
You can use these function blocks with the 140CRP31200 module:
•
• DROP
• XDROP
Only one 140CRP31200 module can be configured on the local rack. This module has interfaces for communicating with Ethernet remote I/O devices on the network.
The 140CRP31200 module allows the PLC to connect to an Ethernet network and to have a deterministic I/O exchange with modules in the Ethernet remote I/O drops.
The 140CRP31200 module is dedicated to the management of remote I/O devices only. Other services of the 140CRP31200 module:
• The module uses RSTP to enable all remote I/O devices on the main ring to recover from a communication disruption within 50 ms.
• The module can configure IP parameters and the configurations for I/O modules on the drops for up to 31 remote I/O devices.
• The module provides a communication path (through an interlink) to allow distributed I/O and control network traffic to participate on the remote I/O network.
• The module supports Hot Standby functionality. The primary 140CRP31200 module and the standby 140CRP31200 module do not swap their IP addresses when a switchover occurs.
12 S1A48978.14
Characteristics of Ethernet Remote I/O Modules
External Features
140CRP31200:
Remote I/O Modules
1 LED display
2 SERVICE port (ETH 1)
3 INTERLINK port (ETH 2)
4 DEVICE NETWORK port (ETH 3)
5 DEVICE NETWORK port (ETH 4)
NOTE: To help prevent dust from entering the unused Ethernet ports on this module, cover the port with the stopper:
External Ports
The 140CRP31200 module monitors the functionality of network links depending on which links are connected to the network. The module has 4 external ports (but a single IP address):
S1A48978.14
13
Remote I/O Modules
Characteristics of Ethernet Remote I/O Modules
Port
SERVICE
INTERLINK
DEVICE
NETWORK
Quantity
1
1
2
Description
The SERVICE port allows the diagnosis of Ethernet ports and provides access to external tools and devices (Control Expert,
ConneXium Network Manager, HMI, etc.). The port supports these modes:
• access port (default): This mode supports Ethernet communications.
• port mirroring: In this mode, data traffic from one or more of the other 3 ports is copied to this port. This allows a connected tool to monitor and analyze the port traffic.
• disabled
NOTE:
• You can configure the SERVICE port either on line or off line.
• In port mirroring mode, the SERVICE port acts like a read-only port. That is, you cannot access devices (ping, connection to Control Expert, etc.) through the SERVICE port.
NOTE: The maximum load the network can process from distributed I/O devices is:
• 5 Mbps per dual-ring switch (DRS) port or service port
• 20 Mbps for distributed I/O traffic on the main ring
Refer to the
Service Port Configuration topic , page 41
.
The INTERLINK port provides connectivity to other Quantum EIO modules.
These 2 copper ports provide:
• connections for remote I/O communications
• cable redundancy via the daisy chain loop architecture
NOTE: Do not connect a device with a speed in excess of 100 Mbps to any port. If the device is configured for a speed that exceeds 100 Mbps, the
Ethernet link may not be established between the device and the module through the port.
Quantum EIO Adapter Module Descriptions
Introduction
These adapter modules are used on Ethernet remote I/O drops in 31 Quantum
EIO installations:
• 140CRA31200
• BMXCRA312•0
A remote I/O drop can be connected directly to either the main ring or a remote I/O sub-ring.
NOTE: If you use a low-end CPU (140 CPU 6• 1••) (2 Mb or less), you can only install a maximum of 31 remote I/O drops. Of those 31 drops, you can only install a maximum of sixteen BMXCRA312•0 remote I/O drops. If you use a high-end CPU (140 CPU 6•• ••) (4 Mb or more), you can install a maximum of thirty-one BMXCRA312•0 or 140CRA31200 remote I/O drops.
Functionality
Adapter modules exchange data with the 140CRP31200 remote I/O head module on the local rack:
• The 140CRA31200 module is an adapter module on a Quantum remote I/O drop.
• The BMXCRA31200 and BMXCRA31210 modules are adapter modules on
Modicon X80 remote I/O drops.
Features:
14 S1A48978.14
Characteristics of Ethernet Remote I/O Modules
Remote I/O Modules
• The input data from the Ethernet remote I/O drop is collected and published to the remote I/O scanner.
• The output modules are updated with the data received from the remote I/O scanner.
• The protocol used for exchange is EtherNet/IP.
• The remote I/O scanner views the 140CRA31200 or BMXCRA312•0 module as a remote I/O adapter.
• The exchanges are deterministic, which means that the time it takes to resolve a remote I/O logic scan is predictable.
CAUTION
UNEXPECTED BEHAVIOR OF THE APPLICATION.
If you use your BMXCRA in a Quantum Ethernet IO architecture, take care to update the Quantum CPU and the 140CRP31200 to the following minimum versions:
• CPU: V3.1
• CRP: V1.56
Failure to follow these instructions can result in injury or equipment damage.
External Features
These adapter modules have the same dimensions and installation constraints as other modules in their respective product lines (Quantum or Modicon X80):
S1A48978.14
1 LED display
2 rotary switches
3 SERVICE port (ETH 1)
4 DEVICE NETWORK port (ETH 2)
5 DEVICE NETWORK port (ETH 3)
15
Remote I/O Modules
Characteristics of Ethernet Remote I/O Modules
NOTE: To help prevent dust from entering the unused Ethernet ports on these adapter modules, cover the ports with the stopper:
External Ports
Two of the Ethernet ports allow implicit I/O exchanges with a remote I/O scanner adapter. (An implicit I/O exchange has a maximum frame size of 1400 bytes.) The ports can be implemented alone or in redundant mode.
You can use a maximum of 31 adapters in a single Ethernet remote I/O network.
For network topology planning, refer to the Quantum Ethernet I/O System
Planning Guide .
These modules have up to three 10/100 Base-T Ethernet ports:
Port
SERVICE
DEVICE
NETWORK
Description
The SERVICE port allows the diagnosis of Ethernet ports and provides access to external tools and devices (Control Expert, ConneXium Network Manager, HMI, etc.). The port supports these modes:
• access port (default): This mode supports Ethernet communications.
• port mirroring: In this mode, data traffic from one of the other 3 ports is copied to this port. This allows a connected management tool to monitor and analyze the port traffic.
• disabled
NOTE:
• You can configure the SERVICE port either on line or off line.
• In port mirroring mode, the SERVICE port acts like a read-only port. That is, you cannot access devices (ping, connection to Control Expert, etc.) through the SERVICE port.
• There is no SERVICE port on the BMXCRA31200 adapter module.
Refer to
Service Port Configuration , page 41
.
The DEVICE NETWORK copper port provides:
• connections for remote I/O communications
• cable redundancy
NOTE: Do not connect a device with a speed in excess of 100 Mbps to any port. If the device is configured for a speed that exceeds 100 Mbps, the
Ethernet link may not be established between the device and the module through the port.
Cable Redundancy
Use a daisy chain network configuration that implements the RSTP service to establish redundant communications between the adapter module and a remote I/
O scanner. The adapter operates normally when at least one of the 2 physical paths to the 140CRP31200 is valid. (For network topology planning, refer to the
Quantum Ethernet I/O System Planning Guide .)
Module Specifications
Product Certification
The Quantum EIO head/adapter modules meet these standards:
16 S1A48978.14
Characteristics of Ethernet Remote I/O Modules
Remote I/O Modules
Environmental Requirements
Parameter protection protection class over voltage class operating temperature storage temperature sinusoidal vibration
Reference
EN 61131-2
IEC 60527
EN 61131-2
EN 61131-2
IEC 60068-2-1
Ab&Ad (cold)
IEC 60068-2-2
Bb&Bd (cold)
IEC 60068-2-1
Ab&Ad (cold)
IEC 60068-2-2
Bb&Bd (cold)
IEC 60068-2-6fC
EN 61131-2
IEC 60068-2-27Ea operating shock altitude free fall, random
(packaged)
UL (UL508)
CSA (CSA22.2 no. 142)
C-tick
Hazardous locations (Cl1 div 2)
IEC61000-4-16
EMI EN 55011
CE
EN 61131-1
IEC 61131-2 (zone B and zone C, except surges on AC: zone B only)
Quantum EIO modules conform to these product certification and marine classification authorities:
Key
ABS
BV
DNV
GOST
GL
LR
RINA
Certification Body
American Bureau of Shipping
Bureau Veritas
Det Norske Veritas
Gosudarstvennyy Standart
Germanischer Lloyd
Lloyd's Register
Registro Italiano Navale
Country
United States
France
Norway
Russia
Germany
United Kingdom
Italy
The electrical isolation within a Quantum EIO system modules complies with the
1500 Vac/2250 Vdc 60s from IEEE 802.3 2008.
EN 61131-2
IEC 60068-2-32
Specification
IP20 protection class 1 category II
0 ... 60° C
-40 ... 85° C
• .5 ... 8.4 Hz at 3.5 mm constant amplitude
• 8.4 ... 150 Hz at 1g constant acceleration
• 10 cycles at sweep rate of 1 oct/min
30 g peak, 11 ms, half-sine wave, 3 shocks in each direction (+ and -) for each of the 3 principle axes
0 ... 5000 m maximum during operation. For altitudes > 2000 m, reduce the operating temperature by 6° C for each additional 1000 m.
5 random drops from 1 m onto flat surfaces
S1A48978.14
17
Remote I/O Modules
Parameter free fall, flat drop
(unpackaged) free fall, angled
(unpackaged) relative humidity
(operating) relative humidity
(nonoperating)
Characteristics of Ethernet Remote I/O Modules
Reference test ed., method 1
EN 61131-2
IEC 60068-2-32 test ed., method 1
EN 61131-2
IEC 60068-2-31
IEC 60068-2-78Ca
IEC 60068
Specification
• 2 random drops from 1 m onto flat surfaces
• 5 drops from 0.1 m onto flat surfaces
5 drops from 0.1 m onto each corner
93% (+/- 2%, noncondensing) at 60° C for conformally coated modules 140CRA31200C and 140CRP31200C
93% (+/- 2%, noncondensing) at 60° C for conformally coated modules 140CRA31200C and 140CRP31200C
NOTE: The BMXCRA31210 is also available in a coated version.
I/O Devices
Introduction
This topic lists the Quantum and Modicon X80 I/O devices that can be connected to an Ethernet remote I/O network.
To add I/O modules to an Ethernet remote I/O drop in Control Expert offline mode, click and drag the modules from the Hardware Catalog to the remote I/O drop in the bus editor. You can also double-click the rack slot in which you want to insert the I/O module and select from the New Device dialog box. The available I/O modules are listed in the following tables.
Quantum Analog and Digital Modules
These analog and digital I/O modules are supported in Quantum Ethernet remote
I/O drops:
Input
Analog I/O Modules :
140 ACI 030 00
140 ACI 040 00
140 AII 330 00
140 AII 330 10
140 ARI 030 10
140 ATI 030 00
140 AVI 030 00
Digital I/O Modules :
140 DDI 153 10
140 DDI 353 00
140 DDI 353 10
140 DDI 364 00
140 DDI 673 00
140 DDI 841 00
140 DDI 853 00
140 DAI 340 00
140 DAI 353 00
140 DAI 440 00
Output
140 ACO 020 00
140 ACO 130 00
140 AIO 330 00
140 AVO 020 00
140 DDO 153 10
140 DDO 353 00
140 DDO 353 01
140 DDO 353 10
140 DDO 364 00
140 DDO 843 00
140 DDO 885 00
140 DAO 840 00
140 DAO 840 10
140 DAO 842 10
Input/Output
140 AMM 090 00
140 DDM 390 00
140 DDM 690 00
140 DAM 590 00
18 S1A48978.14
Characteristics of Ethernet Remote I/O Modules
Input
140 DAI 453 00
140 DAI 540 00
140 DAI 543 00
140 DAI 553 00
140 DAI 740 00
140 DAI 753 00
140 DII 330 00
140 DSI 353 00
Output
140 DAO 842 20
140 DAO 853 00
140 DRA 840 00
140 DRC 830 00
140 DVO 853 00
140 DIO 330 00
Remote I/O Modules
Input/Output
Modicon X80 Analog and Digital Modules
These analog and digital I/O modules are supported in Modicon X80 Ethernet remote I/O drops:
Input
Analog I/O Modules :
BMX ART 0414
BMX ART 0814
BMX AMI 0410
BMX AMI 0800
BMX AMI 0810
Digital I/O Modules :
BMX DDI 1602
BMX DDI 1603
BMX DDI 1604
BMX DAI 0805
BMX DAI 0814
BMX DAI 1602
BMX DAI 1603
BMX DAI 1604
BMX DAI 1614
BMX DAI 1615
BMX DDI 3202K
BMX DDI 6402K
Output
BMX AMO 0210
BMX AMO 0410
BMX AMO 0802
BMX DDO 3202K
BMX DDO 6402K
BMX DDO 1602
BMX DDO 1612
BMX DAO 1605
BMX DAO 1615
BMX DRA 0804
BMX DRA 0805
BMX DRA 0815
BMX DRA 1605
BMX DRC 0805
Input/Output
BMX AMM 0600
BMX DDM 16022
BMX DDM 16025
BMX DDM 3202K
NOTE: Schneider Electric recommends that you upgrade the module with the latest available software version. However, a BMX ART 0414 module, V2.1 or later, can work properly behind a Modicon X80 remote I/O adapter module.
Intelligent and Special Purpose Modules
These intelligent/special purpose modules are supported in Quantum and
Modicon X80 Ethernet remote I/O drops:
Type expert
Quantum Module Modicon X80 Module
BMX CRA 312 00
—
BMX CRA 312 10
BMX ERT 1604T 140 ERT 854 10
140 ERT 854 20
140 ESI 062 10
S1A48978.14
19
Remote I/O Modules
Characteristics of Ethernet Remote I/O Modules
Type counting communication
Quantum Module
140 EHC 105 00
140 EHC 202 00
140 XBE 100 00
140 NRP 312 00/01
Modicon X80 Module
BMX CRA 312 00
—
—
—
BMX CRA 312 10
BMX EHC 0200
BMX EHC 0800
BMX NOM 0200.
Restrictions are described in chapter BMXNOM0200
Limitation and
Implementation Rules (see
Modicon X80,
BMXNOM0200 Serial Link
Module, User Manual).
BMX EIA 100 (max of 1 per drop; may be combined with one BMX NOM 0200 module)
BMX NRP 0200/01 fiber cable conversion
NOTE: Schneider Electric recommends that you upgrade the module with the latest available software version. However, a BMX NOM 0200 module, V1.4 or later, can work properly behind a Modicon X80 remote I/O adapter module.
Modicon X80 Analog and Digital Module Versions
When the following modules are used in an EIO drop with a BMX CRA 312 10 adapter module, they require these versions (or later):
Module
BMX AMI 0410
BMX AMM 0600
BMX AMO 0210
BMX ART 0414
BMX ART 0814
BMX EHC 0200
BMX EHC 0800
Product Version
PV5
PV5 (PV6)
PV7 (PV8)
PV5 (PV6)
PV7
PV3 (PV4)
PV5 (PV6)
PV3
PV3
Hardware Release Level
RL5
RL5 (RL6)
RL7 (RL8)
RL5 (RL6)
RL7
RL3 (RL4)
RL5 (RL6)
RL3
RL3
Software Version
SV1.1
SV1.2
SV1.1
SV2.0
SV2.1
SV2.0
SV2.1
SV1.1
SV1.1
20 S1A48978.14
Installation
Overview
Remote I/O Modules
This chapter describes the hardware installation of a Quantum EIO system. It includes the installation of modules in the local rack and the Ethernet remote I/O drop to which it is connected. Other discussions include the interconnections between rack-mounted modules and the hardware considerations for different
PLC platforms.
Installing Quantum EIO Modules
Introduction
This section describes the installation of these Quantum EIO modules:
• 140CRP31200 remote I/O head module (on the local rack)
• 140CRA31200 remote I/O adapter module (on a Quantum remote I/O drop)
• 140CRA31908 remote I/O adapter module (for S908 applications)
• BMXCRA312•0 remote I/O adapter module (on a Modicon X80 remote I/O drop)
Installing the Quantum Controller
Introduction
For any Quantum EIO system, install a Quantum controller on the local rack. Only processors with firmware version 3.0 or later (version 3.10 for BMXCRA312•0 support) are compatible with Quantum EIO installations.
Compatible Processors
Compatible processors:
Processor Type standalone
Hot Standby
Part
140 CPU 651 50
140 CPU 651 60
140 CPU 652 60
140 CPU 658 60
140 CPU 671 60
140 CPU 672 60
140 CPU 672 61
140 CPU 678 61
NOTE: Low-end Quantum processors (140 CPU 434 12U, 140 CPU 534 14U,
140 CPU 311 10) and Quantum safety processors (140 CPU 651 60S, 140
CPU 671 60S) are not compatible with Quantum EIO systems.
Selecting a Power Supply
When installing a Quantum controller, add a power supply module that is capable of supplying power to all modules on the rack.
S1A48978.14
21
Remote I/O Modules
Mounting a Quantum EIO-Compatible Module on the Backplane
Introduction
Use these instructions to install Quantum and Modicon X80 modules that operate in a Quantum EIO system:
• 140CRP31200 remote I/O head module (on the local rack)
• remote I/O adapter module:
◦ 140CRA31200 remote I/O adapter module (on a Quantum remote I/O drop)
◦ BMXCRA312•0 adapter module (on a Modicon X80 remote I/O drop)
◦ 140CRA31908 adapter module facilitates the use of S908 hardware and applications in M580 Ethernet I/O architectures.
• 140NOC78000 distributed I/O head module (on the local rack)
• 140NOC78100 control head module (on the local rack)
Grounding Considerations
Do not apply power to a Quantum rack until connections are made at both ends of the Ethernet cable. For example, connect the cable to both the 140CRP31200 and another device (adapter module) or ConneXium dual-ring switch DRS before you turn on the power.
Refer to the Quantum EIO System Planning Guide for details on dual-ring switches (DRSs).
DANGER
ELECTRICAL SHOCK HAZARD
• Switch off the power supply to the automation controller stations at both ends of the connection before inserting or removing an Ethernet cable.
• Use suitable insulation equipment when inserting or removing all or part of this equipment.
Failure to follow these instructions will result in death or serious injury.
Use fiber-optic cable to establish a communications link when it is not possible to master potential between distant grounds.
22 S1A48978.14
Remote I/O Modules
Mounting a Module
Step Action
1
Hold the module at an angle and mount it on the 2 hooks near the top of the backplane.
The figure shows the correct way to hold the module:
2
3
Swing the module down so the connector engages the backplane connector.
Use a Phillips-head screw driver to tighten the screw at the bottom of the module from 2 to
4 in-lbs or from .22 through .45 N•m of torque.
NOTE: The figure above shows a Quantum module being mounted from top to bottom. Modicon X80 modules mount from bottom to top.
Replacing a Module
You can replace a Quantum EIO module at any time using another module with compatible firmware. The replacement module obtains its operating parameters over the backplane connection from the CPU. The transfer occurs immediately at the next cycle to the device.
The operating parameters that the CPU sends to a replacement module do not include any parameter values that were edited in the original module using explicit messaging SET commands.
Quantum EIO-Compatible Module Installation Considerations
Introduction
Observe the following guidelines when you install these Quantum and Modicon
X80 modules in a Quantum EIO system:
• 140CRP31200 remote I/O head module (on the local rack)
• remote I/O adapter module (on the remote I/O drop)
◦ 140CRA31200 module on a Quantum drop
◦ 140CRA31908 adapter module on a Quantum drop
◦ BMXCRA312•0 module on a Modicon X80 drop
• 140NOC78000 distributed I/O head module (on the local rack)
• 140NOC78100 control network head module (on the local rack)
S1A48978.14
23
Remote I/O Modules
Grounding Considerations
DANGER
ELECTRICAL SHOCK HAZARD
• Switch off the power supply to the automation controller stations at both ends of the connection before inserting or removing an Ethernet cable.
• Use suitable insulation equipment when inserting or removing all or part of this equipment.
Failure to follow these instructions will result in death or serious injury.
Use fiber-optic cable to establish a communications link when it is not possible to master potential between distant grounds.
NOTE: Refer to the ground connections information in Electrical installation guide .
Installation
You can apply power to the Quantum EIO controller rack after the 140CRP31200 head module or adapter module is inserted:
• Successful installation:
◦ Initialization is finished.
◦ Interconnections to other modules are validated (drop adapter module only).
• Unsuccessful installation:
◦ Initialization does not finish.
◦ Interconnections to other modules are not validated (adapter modules only).
You can see the status of the installation on the LED display.
NOTE: Because all modules on the local rack are initialized when power is applied, the 140CRP31200 remote I/O head module can only validate the interconnections with 140NOC78000 and 140NOC78100 head modules after these modules have been initialized. Therefore, the adapter module waits until its queries about the interconnected port information are answered.
NOTE: These guidelines pertain to the installation of a single head module or adapter module, not the entire network. For network power-up guidelines, refer to Quantum EIO, System Planning Guide .
Remote I/O Network Cable Installation
Introduction
Your application can include:
• communications with a simple remote I/O daisy chain loop
• communications with a mix of remote I/O and distributed I/O networks
The cable connections to the 140CRP31200 remote I/O head module on the local rack are different in these scenarios. They are discussed below.
Each device network port on the 140CRP31200 module is connected to the main ring of the daisy chain. Likewise, each device network port on a 140CRA31200 or
BMXCRA312•0 adapter module is connected to an Ethernet I/O device. The
140CRP31200 module and the •••CRA312•0 adapter modules do not have fiber optic ports.
The Ethernet ports
on the 140CRP31200 module and the •••CRA312•0 adapter modules.
24 S1A48978.14
Remote I/O Modules
Remote I/O Simple Daisy Chain Loop
The 140CRP31200 module supports communications with Ethernet remote I/O drops in daisy chain loops:
1 local rack with a 140CRP31200 remote I/O head module
2 Modicon X80 remote I/O drop with a BMXCRA312•0 adapter module
3 Quantum remote I/O drop with a 140CRA31200 adapter module
When you support only remote I/O, you do not have to link the 140CRP31200 module to other communication modules on the local rack.
Mix of Remote I/O Drops, Distributed I/O Devices, and Clouds
The Quantum EIO architecture allows distributed I/O devices to participate directly on the remote I/O network. This can be useful if, for example, you want to integrate a SCADA or HMI panel or other non-Quantum device into the remote I/O network.
S1A48978.14
25
Remote I/O Modules
Distributed I/O devices cannot be connected directly to the main ring of the remote
I/O network, but they can be connected via a DRS. Most DRS preconfigurations enable some switch ports to support distributed I/O clouds:
1 main ring
2 140CRP31200 interlinked to 140 NO• 7•• module on the local rack
3 dual-ring switch (DRS)
4 dual-ring switch (DRS) connection to distributed I/O sub-ring
5 dual-ring switch (DRS) connection to distributed I/O cloud
Some dual-ring switch (DRS) preconfigurations support the connection of distributed I/O devices connected directly to a sub-ring. In these configurations, the distributed I/O devices have the advantage of cable redundancy provided by the sub-ring loop. In order for a distributed I/O device to operate on a sub-ring, use a device with 2 Ethernet ports that support RSTP.
The above figure shows two STB islands used as distributed I/O devices on a subring. The network interface module installed in each island is an STB NIP 2311
NIM, which has dual Ethernet ports and the RSTP service.
Installing the Communications Adapter on the Remote Drop
Introduction
This section describes the installation of the 140CRA31200 or BMXCRA312•0 adapter module in an Ethernet remote I/O drop.
Installing a Quantum EIO Adapter Module
Locate a Backplane Slot
Install the 140CRA31200 adapter module in any slot in the remote I/O drop. Insert the BMXCRA312•0 adapter module in slot 0 only in the remote I/O drop.
Refer to the directions for
installing a module on the backplane, page 22
.
26 S1A48978.14
Remote I/O Modules
Power Consumption
Power consumption is 1.2 A on a 5 Vdc power rail on the backplane (6 W). The adapter module supports modules on 2 racks. (Power consumption has no relation to the number of installed rack modules.)
Select a Power Supply
When configuring the PLC station, use a power supply module that can supply power to all rack modules.
NOTE: You can place a power supply module in any slot on Quantum
Ethernet remote I/O drop. In Modicon X80 Ethernet remote I/O drops, you can insert the power supply only in the double-wide slot to the left of slot 0.
Select a power module that suits your unique system requirements. These modules (and their conformally coated versions) are supported:
Power Supply Type standalone summable
Quantum Module
• 140 CPS 21 00 (C)
• 140 CPS 511 00 (C)
• 140 CPS 111 00 (C)
Modicon X80 Module
–
• BMX CPS 2010
• BMX CPS 3020
• BMX CPS 2000
• BMX CPS 3500
• BMX CPS 3540
• BMX CPS 4002 redundant
• 140 CPS 214 00 (C)
• 140 CPS 414 00 (C)
• 140 CPS 114 20 (C)
• 140 CPS 224 00 (C)
• 140 CPS 424 00 (C)
• 140 CPS 524 00 (C)
• 140 CPS 124 20 (C)
• ABL 8RED 24400
• ABL 8REM 24030
• ABL 8RPS 24030
Installing Ethernet Remote I/O Drops on a Remote Rack
Introduction
These guidelines apply to Ethernet remote I/O drops on remote racks.
Racks and Extensions
An Ethernet remote I/O drop can include 2 racks. In a 2-rack drop, the racks are linked with these bus extender modules and cables:
Remote Drop Type
Quantum
Modicon X80
Bus Extender Module
140 XBE 100 00
BMX XBE 1000
Cable
140 XCA 717 0• (1 to 3 m)
BMX XBC •••K (0.8 to 12 m)
Maximum Configuration
Quantum remote I/O drops can include two 16-slot racks for a maxiumum of 32 slots. Modicon X80 remote I/O drops with a BMXCRA312•0 adapter module can support two racks for a maximum of 24 slots.
NOTE: If you use a low-end CPU (140 CPU 6• 1••) (2 Mb or less), you can only install a maximum of 31 remote I/O drops. Of those 31 drops, you can only install a maximum of sixteen BMXCRA312•0 remote I/O drops. If you use a high-end CPU (140 CPU 6•• ••) (4 Mb or more), you can install a maximum of thirty-one BMXCRA312•0 or 140CRA31200 remote I/O drops.
S1A48978.14
27
Remote I/O Modules
The table shows the maximum number of modules of each type in remote drops:
Module Type Quantum 140CRA31200 remote I/O adapter (note 1) power supply (note 2) bus extension (note 3)
I/O
1
2
2
27
2
2
Modicon X80
BMXCRA312•0
1
23
• NOTE 1:
◦ 140CRA31200: This adapter module consumes 1 slot in the main (first) rack in Quantum remote drops. The extended (second) rack in a Quantum remote I/O drop does not require an adapter.
◦ BMXCRA312•0: This adapter module supports a Modicon X80 remote I/O drop with 2 racks when a bus extender module is in both the main and extended racks.
• NOTE 2: A power supply consumes 1 dedicated slot in each rack in Quantum and Modicon X80 remote I/O drops.
• NOTE 3: A bus extender module is required for each rack in remote I/O drops. In Quantum remote I/O drops, the bus extender consumes 1 rack slot.
In Modicon X80 remote I/O drops, the bus extender attaches to the end of the rack and does not consume a rack slot.
Refer to the
list of modules that remote I/O installations support, page 18
.
Setting the Location of the Ethernet Remote I/O Drop
Setting Rotary Switches
Set the location of the Ethernet remote I/O drop on the network with the rotary switches on the front of the 140CRA31200 or BMXCRA312•0 adapter module before you apply power to the module and before you download the application:
28
The values you set are applied during a power cycle. If you change the switch settings after the module has powered up, the Mod Status LED is activated and a mismatch message is logged in the module diagnostic.
Because new values on the rotary switches are implemented only at the next power cycle, we recommend that you set the value before starting the module.
(Valid values: 00 ... 159)
The values on the rotary switches combine with the device prefix (for example,
140CRA_ xxx or BMXCRA_ xxx ) to create the device name (where xxx represents the value of the rotary switches). The preceding figure shows the Tens switch set to 0 and the Ones switch set to 01, for a device name of 140CRA_001.
NOTE:
• The rotary switches can be manipulated with a small flat-tipped screwdriver.
• No software is required to configure or enable the rotary switches.
• Do not use the Stored and Clear IP settings on the Ones rotary switch. (The functionality of these settings does not apply to remote I/O installations.)
S1A48978.14
Remote I/O Infrastructure Cables
Cable Installation
Remote I/O Modules
Introduction
Observe these guidelines when making cable connections between remote I/O devices on a Quantum EIO installation. (Remote I/O devices include local racks, remote I/O drops, or DRSs.)
A copper cable connection between 2 consecutive remote I/O devices cannot exceed 100 m. A fiber cable connection between 2 consecutive remote I/O devices cannot exceed 15 km (single mode) or 2.5 km (multi-mode).
Connections Between Devices
This figure shows the distances between remote I/O devices in Quantum EIO installations:
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module
3 140NOC78100 control head module
4 DRS (with copper and fiber ports): This DRS extends the distance between devices using fiber cable (up to 15 km).
5 distributed I/O sub-ring connected to the main ring via (4)
6 fiber cable portion of the main ring used to separate the DRSs beyond 15 km
7 copper cable (twisted pair) portion of the main ring
8 remote I/O drop
9 DRS (with copper ports only): This DRS extends the distance between devices.
10 control network
NOTE: It is required to use shielded twisted pair CAT5e (10/100 Mbps) cables, ideally ConneXium 490NTC•000•• cables.
S1A48978.14
29
Remote I/O Modules
NOTICE
COMMUNICATION FAULTS
Use shielded twisted pair CAT5e (10/100 Mbps) cables to prevent communication faults.
Failure to follow these instructions can result in equipment damage.
Interlink
To support distributed I/O sub-rings in Quantum EIO installations, establish an interlink between an Ethernet communication module on the local rack and the
140CRP31200 remote I/O head module:
1 local rack, including a 140 NOC 780 00 distributed I/O head module that is interlinked with a 140CRP31200 remote I/O head module
2 DRS connected to the main ring and a distributed I/O sub-ring
3 distributed I/O sub-ring
NOTE: For the interlink connection, it is required to use shielded twisted pair
CAT5e (10/100 Mbps) cables.
NOTICE
COMMUNICATION FAULTS
For the interlink connection, use shielded twisted pair CAT5e (10/100 Mbps) cables to prevent communication faults.
Failure to follow these instructions can result in equipment damage.
Duplicate IP Address Checking
Introduction
Each Quantum EIO module has a single IP address. Therefore, the address conflict detection algorithm (also called duplicate IP checking) is performed based on the status (link up, link down) of the ports.
Link Down
These conditions apply when links are lost:
30 S1A48978.14
Remote I/O Modules
Link Status
A transition has occurred from 1 connected link to all links down.
There is 1 link down and at least 1 connected link.
Description
When no module ports are connected to a cable (all links are down), all services are reset. For example, I/O connections, Modbus connections, and explicit EtherNet/IP connections close, but low-level network services (like RSTP or switches) are not affected. The updated Net Status LED indicates the status.
There is no impact on services that are running in the module.
Link Up
These conditions apply when links are added:
Link Status
A transition has occurred from no connected links to
1 connected link.
A transition has occurred from at least 1 connected link to an additional connected link.
Description
A duplicate IP check is performed:
• no duplicate : All services start.
• duplicate : I/O services stop. The 140CRA31200 or
BMXCRA312•0 adapter module gets new configuration and downloads the IP configuration again. The system goes to default IP and I/O modules are set to fallback mode.
A duplicate IP check is performed:
• no duplicated: All services continue.
• duplicate: All services stop.
NOTE: The updated Net Status LED indicates the status.
Loss of I/O Connection
Conditions
An I/O connection can be lost under these conditions:
Condition CPU 140CRP31200
X
X
Adapter Module
(140CRA31200 or
BMXCRA312•0)
X
• Perform a hot swap.
• Replace a module of the same type.
X X
There is no remote I/O cable connection.
X
The I/O connection is closed.*
*Hot swap of the CPU results in an explicit close (lost I/O connection).
Remote Adapter Fallback
In some instances, the 140CRA31200 or BMXCRA312•0 adapter module on the remote I/O drop can lose I/O connections for a period longer than the configured hold up time. During the hold up, the adapter tries to get IP and configuration parameters from the 140CRP31200. If the adapter does not obtain those parameters, it gets these results:
• inputs : retain last known values
• outputs : set to fallback
NOTE: Configure the hold up time on the
Control Expert Parameter tab, page
.
S1A48978.14
31
Remote I/O Modules
Configuration and Programming with Control Expert
Configuration and Programming with Control Expert
Introduction
Use Control Expert to configure your local rack and remote drops for Ethernet communications.
Creating a Control Expert Project
Introduction
Use the instructions in this section to create a Control Expert project that allows communication between a local rack and an Ethernet remote I/O drop. Here are the basic stages of the Control Expert configuration:
1. Select a high-end Quantum processor to create a new Control Expert configuration.
2. Add a power supply to the local rack.
3. Add an Ethernet remote I/O head module (140 CRP 312 00) to the local rack.
4. Configure a rack assembly for the Ethernet remote I/O drop.
NOTE: These instructions assume that you have a working knowledge of
Control Expert.
Configuring the Local Rack
Assemble a Local Rack
In Control Expert, assemble a Quantum rack:
Step
1
2
3
4
5
6
7
8
Action
In Control Expert, create a project.
Add a PLC from the New Project window.
In the Project Browser , doubleclick Local Bus .
Add a power supply to the Local
Bus .
Add a 140 CRP 312 00 remote I/O head module to an available slot in the local rack.
Use the same method to add a 140
NOC 780 00 distributed I/O head module to the Local Bus .
Double-click any empty slot to add modules to the Local Bus .
Save the file.
Comment
Click File > New .
Result : The New Project window appears.)
For this example, double-click the 140 CPU
651 50 module. ( New Project > Quantum >
140 CPU 651 50 ).
Click Tools
>
Project Browser
>
Configuration > Local Bus .
Result : The Local Bus window opens, and the rack includes the processor you selected.)
Drag the module to slot 1. ( Tools catalog
> Hardware
> Local Quantum Drop > Supply >
140 CPS 114 X0 )
Drag the module to slot 4. ( Tools catalog
> Hardware
> Local Quantum Drop >
Communication > 140 CRP 312 00 )
Drag the module to slot 5. ( Tools catalog
> Hardware
> Local Quantum Drop >
Communication > 140 NOC 780 00 )
This step is optional, but you can provide
Ethernet transparency between the device network and the control network by adding a
140 NOC 781 00 control head module to the local rack.
Click File > Save .
32 S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
The local rack in your Control Expert configuration should look like this:
S1A48978.14
Note that the Local Bus contains these modules:
• power supply (140 CPS 114 •0)
• CPU (140 CPU 651 50)
• remote I/O head module (140 CRP 312 00)
• distributed I/O head module (140 NOC 780 00)
• control head module (140 NOC 781 00)
Rack Parameters
Double-click the 140 CRP 312 00 module in the Local Bus window to access these configuration parameters for the local rack:
•
•
•
•
•
•
NOTE: You can accept the automatically assigned IP address or change the
IP address in the Control Expert IP Config tab.
Rack Considerations
Remember:
• The copy/cut/paste commands are not available for the 140CRP31200 module.
• You can cut or copy other devices in the local rack or the drop and paste them in any rack of the same type. You can perform these actions (cut, copy, paste) only in the same device editor. You cannot move objects from the local rack to the drop or vice-versa.
• The number of the first slot in a rack is 1. Therefore, a 4-slot rack has slot numbers 1, 2, 3, 4.
NOTE: If you use a low-end CPU (140 CPU 6• 1••) (2 Mb or less), you can only install a maximum of 31 remote I/O drops. Of those 31 drops, you can only install a maximum of sixteen BMXCRA312•0 remote I/O drops. If you use a high-end CPU (140 CPU 6•• ••) (4 Mb or more), you can install a maximum of thirty-one BMXCRA312•0 or 140CRA31200 remote I/O drops.
33
Remote I/O Modules
Configuration and Programming with Control Expert
Configuring the Ethernet Remote I/O Drop
Instructions
In the previous topic, you
added a 140CRP31200 module to the local rack in a
Control Expert project, page 32
. The 140CRP31200 remote I/O head module supports communication with an Ethernet remote I/O rack.
When you insert a 140CRP31200 module in the local rack, Control Expert automatically creates an EIO Bus , which has the same capabilities as an existing
S908 legacy remote I/O bus.
In the EIO Bus , you can select a Quantum drop or an Modicon X80 drop.
Within an Modicon X80 drop, the BMXCRA31200 adapter module is inserted by default. This module supports only standard digital and analog modules. Insert a
BMXCRA31210 module from the Drop end communicator field if you require more functionality, such as the following:
•
• expert modules
•
• CCOTF
NOTE: If you use a low-end CPU (140 CPU 6• 1••) (2 Mb or less), you can only install a maximum of 31 remote I/O drops. Of those 31 drops, you can only install a maximum of sixteen BMXCRA312•0 remote I/O drops. If you use a high-end CPU (140 CPU 6•• ••) (4 Mb or more), you can install a maximum of thirty-one BMXCRA312•0 or 140CRA31200 remote I/O drops.
Use these instructions to configure a remote rack ( EIO Bus ) that includes a
140CRA31200 or BMXCRA312•0 adapter module in slot 1:
Step
1
2
3
4
5
Action
In the Project Browser , double-click EIO
Bus to see the (empty) drop.
Comment
( Tools view
> Project Browser > Structural
>
Project
>
Configuration
>
EIO
Bus )
In the EIO Bus window, double-click the square link connector to access the available racks.
Select a rack for a Quantum Ethernet I/O drop or a Modicon X80 Ethernet I/O drop.
NOTE: If you select a Modicon X80 drop, also choose a BMXCRA31200 or BMXCRA31210 adapter module in the Drop end communicator field of the New Device window.
Double-click any empty slot to add modules to the EIO Bus .
Save the file.
The New Device window appears.
This example uses the 4-slot 140 XBP
004 00 rack: New Device
Number
Click File > Save .
> Part
> EIO Quantum Drop > Rack
> 140 XBP 004 00 . Select the device and press OK .
For this example, this step is optional.
34 S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
The Control Expert configuration now includes the remote rack window ( EIO Bus ). Because the Ethernet remote
I/O drop requires a module for communication with the local rack, Control Expert automatically adds an adapter module in slot 1.
Rack Parameters
The adapter module is now installed as the communications adapter module of your Ethernet remote I/O drop. Double-click the adapter to see its configuration tabs:
•
•
•
Rack Considerations
Remember these points:
• You can insert 2 racks on a Modicon X80 Ethernet remote I/O drop with a
BMXCRA31210. You can only insert 1 rack with a 140CRA31200 module.
• Control Expert automatically inserts BMXCRA312•0 adapter modules in slot
0. You cannot delete or move these modules.
• The number of the first slot in a Quantum rack is 1. The number of the first slot in a Modicon X80 rack is 0. Therefore, a 4-slot Quantum rack includes slot numbers 1, 2, 3, 4, and a 4-slot Modicon X80 rack includes slot numbers
0, 1, 2, 3.
• You can cut or copy other devices in the remote drop and paste them in any rack of the same type. You can perform these actions (cut, copy, paste) only in the same device editor. You cannot move objects from the local rack to the drop or vice-versa.
Available Control Expert Configuration Tabs
About the Parameters
The Control Expert configuration tabs are available after you have configured these:
•
local rack (including a 140CRP31200 remote I/O head module), page 32
•
Ethernet remote I/O drop (including a 140CRA31200 or BMXCRA312•0 remote I/O adapter module), page 34
S1A48978.14
35
Remote I/O Modules
Configuration and Programming with Control Expert
Control Expert Configuration Tabs
This table indicates the available Control Expert configuration tabs for the local rack’s 140 CRP 312 00 head module and the remote I/O drop’s adapter module:
Control Expert Tab 140CRP31200 Head Module
(Local Rack)
X
X
X
X
X
X
•••CRA312•0 Adapter Module
(Remote I/O Drop)
(See note.)
X
X
X
X
X (BMXCRA31210 only)
NOTE: The adapter module (140CRA31200 or BMXCRA312•0) automatically receives an IP address. To maintain unique addressing on the network, keeping and using the auto-assigned
IP addresses is generally considered a good practice.
NTP Configuration in Control Expert
Introduction
This topic describes the Control Expert NTP (time stamp) parameters for the
BMXCRA31210 module. To access these parameters on the Control Expert NTP tab,
double-click the communication module in the local rack, page 32 .
Access the NTP Tab
To access the NTP tab, open the Bus Editor , double click on the CRP module and then select the NTP tab:
Field
NTP server configuration for adapter modules
Parameter
IP address of Primary NTP Server
IP address of Secondary NTP Server
Polling period
—
Value a.b.c.d (0.0.0.0)
1, 120 (5)
—
Comment entered value online behavior disabled in connected mode
NOTE: For time zones that support daylight saving time (DST), the default value is enabled (checked). It is disabled (unchecked) for all time zones that don't support DST.
Valid IP addresses for NTP servers:
• 1.0.0.0 ... 126.255.255.255
• 128.0.0.0 ... 223.255.255.255
For any other IP address, a detected error is reported. Addresses 224.0.0.0 and higher are experimental multicast addresses. Addresses starting at 127 are loopback addresses.
36 S1A48978.14
Configuration and Programming with Control Expert
Setting the Time Zone
Set the time zone in the Project Settings window:
Remote I/O Modules
Set the time zone:
Step
1
2
3
4
Action
In Control Expert, select Tools > Project Settings .
Expand the General menu in the Projects Settings window, and select the Time setting.
Select the appropriate values for each time zone property.
Click Apply to save changes, or click OK to save changes and close window.
Control Expert Configuration for Remote I/O Ethernet Modules
Overview
This section describes the module configuration tabs in Control Expert. Use the parameters on these tabs to configure services for the 140CRP31200 module in the local rack and the adapter module (140CRA31200 or BMXCRA312•0) in
Ethernet remote I/O drops.
S1A48978.14
37
Remote I/O Modules
IP Configuration
Configuration and Programming with Control Expert
Access the IP Config Tab
The Control Expert IP configuration parameters apply to the 140CRP31200 head module in the local rack. To access the IP Config tab,
:
38
IP Config Parameters
Configure the IP parameters for the 140CRP31200 head module in the IP address configuration field on the IP Config tab:
Parameter
IP address A
IP address B
Subnetwork mask
Gateway address
Description
The address corresponds to the 140CRP31200 module.
This address is used for Hot Standby configurations.
NOTE: If you change IP address A, the system may recalculate all IP addresses (including those of the drops) to keep all devices in the same subnet.
This bit mask identifies or determines the IP address bits that correspond to the network address and the subnet portion of the address. (The value can be changed to any valid value in the subnetwork.)
This is the IP address of the default gateway to which messages for other networks are transmitted.
Default Value
192.168.10.1
IP address A + 1
255.255.0.0
0.0.0.0 (when not used)
Configure the IP parameters for the adapter module (in the remote drop) in the
CRA IP address configuration field on the IP Config tab:
Parameter
Drop No.
Device Name
IP Address
Description drop number device name (140CRA31200 or BMXCRA312•0 adapter)
When an Ethernet remote I/O drop is added, the adapter module is automatically assigned an IP address. (You can change this IP address in the IP Address column, but we recommend that you accept the automatically assigned IP address.)
Default Value
—
—
—
S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
RSTP Bridge Configuration
About RSTP
Use RSTP to design a network with redundant cabling so that remote I/O communications automatically find an alternate path if a communication disruption occurs (for example, a cable breaks or a device becomes inoperable). This method does not require you to manually enable or disable communication paths.
Changing these parameters can affect sub-ring diagnostics, I/O determinism, and network recovery times.
Access the RSTP Tab
You can access the RSTP parameters in Control Expert by double-clicking these modules in the Control Expert rack view:
• head module on the local rack (140CRP31200)
• adapter module on the remote drop (140CRA31200 or BMXCRA312•0)
The RSTP tab appears:
Parameters
This table shows the Bridge priority parameters for the RSTP Operational State on the Control Expert RSTP tab:
Bridge Priority
Root
Backup Root
Value
0
4096
140CRP31200 default for Hot Standby
(automatic)
Adapter Module
—
—
Participant 32768 — default
NOTE: In Hot Standby systems, the RSTP bridge priority is applied to the 140CRP31200 module in rack A.
SNMP Agent Configuration
About SNMP
Use the SNMP tab in Control Expert to configure SNMP parameters for these
Quantum Ethernet I/O modules:
• head module on the local rack (140CRP31200)
• adapter module on the remote drop (140CRA31200 or BMXCRA312•0)
An SNMP v1 agent is a software component of the SNMP service that runs on these modules to allow access to diagnostic and management information for the modules. You can use SNMP browsers, network management software, and other tools to access this data. In addition, the SNMP agent can be configured with the
IP addresses of 1 or 2 devices (typically PCs that run network management
S1A48978.14
39
Remote I/O Modules
Configuration and Programming with Control Expert
software) to be the targets of event-driven trap messages. Such messages inform the management device of events like cold starts and the inability of the software to authenticate a device.
Access the SNMP Tab
Double-click these modules in the Control Expert configuration to access their
SNMP tabs:
• 140CRP31200 head module (local rack)
• 140CRA31200 or BMXCRA312•0 adapter module (remote drop)
The SNMP tab appears:
Field
IP Address managers
Agent
Use the SNMP tab to configure the SNMP agents for the communication modules in the local rack and remote drop. The SNMP agent can connect to and communicate with 1 or 2 SNMP managers as part of an SNMP service. The
SNMP service includes:
• authentication checking, by the Ethernet communication module, of any
SNMP manager that sends SNMP requests
• management of events or traps
SNMP Parameters
These parameters are found on the Control Expert SNMP tab:
Parameter
IP Address manager 1
IP Address manager 2
Location (SysLocation)
Contact (SysContact)
Enable SNMP manager
Description
The address of the first SNMP manager to which the SNMP agent sends notices of traps.
The address of the second SNMP manager to which the SNMP agent sends notices of traps.
device location description of the person to contact for device maintenance unchecked (default): You can edit the
Location and Contact parameters.
checked: You cannot edit the Location and Contact parameters.
Value
0.0.0.0 ... 255.255.255.255
31 characters (maximum) checked/unchecked
40 S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
Field
Community names
Security
Parameter
Set
Get
Trap
Enable “Authentication failure” trap
Description password that the SNMP agent requires to read commands from an SNMP manager
(default = Public ) unchecked (default): not enabled.
checked (enabled): The SNMP agent sends a trap notice to the SNMP manager if an unauthorized manager sends a Get or Set command to the agent.
Value
15 characters (maximum) checked/unchecked
Online Behavior
Tests are done to verify that the IP addresses of the managers are not:
• multicast
• loopback
• broadcast
Service Port Configuration
Access the Service Port Tab
Double-click these modules in the Control Expert rack view to access the Control
Expert Service Port tab:
• head module on the local rack (140CRP31200)
• adapter module on the remote drop (140CRA31200 or BMXCRA31210)
The Service Port tab appears:
Field
Service Port
Parameter
Enabled
Disabled
Service Port Parameters
These parameters are on the Control Expert Service Port tab:
Value
—
—
Comment
Enable port and edit port parameters.
Disable port parameters.
S1A48978.14
41
Remote I/O Modules
Field
Service Port
Mode
Parameter
Access (default)
Mirroring
Value
—
—
Access Port
Configuration
Port Mirroring
Configuration
Service Port
Number
Source Port(s)
ETH1
Internal Port
ETH2
ETH3
ETH4
Configuration and Programming with Control Expert
Comment
This mode supports Ethernet communications.
In port mirroring mode, data traffic from one or more of the other ports is copied to this port. A connected tool can monitor and analyze port traffic.
NOTE: In this mode, the SERVICE port acts like a read-only port.
That is, you cannot access devices (ping, connection to Control
Expert, etc.) through the SERVICE port.
You cannot edit the value in the Service Port Number field.
all Ethernet traffic for the module
140CRP31200: all INTERLINK port traffic adapter modules: Ethernet traffic through the first remote I/O port
140CRP31200: Ethernet traffic through the first remote I/O port adapter modules: Ethernet traffic through the second remote I/O port adapter modules: Ethernet traffic through the second remote I/O port
(140CRP31200 only)
On Line Behavior
The Service Port parameters are stored in the application, but you can reconfigure (change) the parameters in connected mode. Values that you reconfigure in connected mode are sent to the remote drop’s adapter module or
140CRP31200 head module in explicit messages. (The changed values are not stored, so a mismatch can exist between the parameters that are being used and those that are in the stored application.) If the module does not respond to the explicit messages, a message appears.
Limitations
The SERVICE port on the 140CRP31200 head module and the adapter modules have the same limitations as the cloud port of the dual-ring switch (DRS).
Therefore, the module's cloud port and the DRS's cloud port can be connected to the same equipment.
The maximum load the module can process from distributed I/O devices:
• 5 Mbps: per SERVICE port
• 20 Mbps: total distributed I/O traffic on the main ring
For more information about considerations that apply to the use of the distributed
I/O cloud port and the service port on the DRS, refer to the Predefined
Configuration Files topic in the Quantum Ethernet I/O System Planning Guide .
Control Expert Configuration for Ethernet Remote I/O Drops
Introduction
This section discusses the use of Control Expert to configure the Ethernet remote
I/O drop and its adapter module. It includes descriptions of the parameters on the
Configuration , Parameter , and Device DDT tabs in Control Expert.
NOTE: These instructions assume that you have already
added a remote I/O drop to your Control Expert project, page 27
.
42 S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
Configuring the Size and Location of Data
Introduction
Use the Control Expert Configuration tab to configure the size and location of data for an Ethernet remote I/O drop that includes a 140CRA31200 or
BMXCRA312•0 remote I/O adapter module.
NOTE: These instructions assume that you have already
Control Expert project, page 34 .
Access the Configuration Tab
Access the Configuration parameters in Control Expert:
Step
1
2
3
Action
Expand (+) the EIO Bus in the Control
Expert Project Browser .
Double-click the Quantum EIO drop.
Select the Configuration tab.
Comment
( Project Browser > EIO Bus > EIO
Quantum Drop / EIO Modicon X80 Drop )
The EIO drop window appears. It contains the parameter tabs from the Ethernet remote I/O drop.
The Configuration tab is available for the
Quantum EIO drop only.
The Configuration tab shows the Parameter Name and the corresponding
Value :
Configuration Parameters
On the Control Expert Configuration tab, configure these parameters for the
Ethernet remote I/O Quantum drop:
Parameter Name
Starting address status table
Ending address status table
In Bytes
Out Bytes
Value the first register in the status table (configured) the starting address + the maximum number of addresses for the configured rack size the total number of bytes for input modules in the remote I/O drop the total number of bytes for output modules in the remote I/O drop
NOTE: These parameters do not apply to Modicon X80 drops.
Configuring the Parameters
Parameter Tab (Remote I/O Drop)
This topic describes the Control Expert Parameter tab for an Ethernet remote I/O drop that includes a 140CRA31200 or BMXCRA312•0 adapter module.
NOTE: These instructions assume that you have already
Control Expert project, page 34 .
S1A48978.14
43
Remote I/O Modules
The Parameter tab appears:
Configuration and Programming with Control Expert
Access the Parameter Tab
Access the Parameter tab in Control Expert:
Step
1
2
3
Action
Expand (+) EIO Bus in the Control
Expert Project Browser .
Double-click the EIO drop
(Quantum or Modicon X80.
Select the Parameter tab.
Comment
Path: Project Browser > EIO Bus > EIO
Quantum Drop / EIO Modicon X80 Drop
The EIO drop window appears. It contains the parameter tabs for the remote I/O drop.
44
Parameter Descriptions
Use the Control Expert Parameter tab to configure the following parameters for the Ethernet remote I/O drop.
Address information parameters:
Parameter Comment
Device Name The device name of the device includes a fixed device prefix and a number provided by the rotary switch. Valid device names conform to this structure:
• 140CRA_ xxx
• BMXCRA_ xxx
Remember that xxx equals the 3-digit value selected on the rotary switches, so the device name includes the device prefix ( 140CRA or BMXCRA ) plus that value.
When the device is placed on the Ethernet remote I/O drop, the number is set to the device number. The device number does not change when the device moves to a new location.
Valid device numbers are unique within the application. A message like this appears when analysis reveals redundant device numbers:
IP Address
Sub Network
{EIO Bus (2) 140 CRA 312 00}: Device name is not unique
NOTE: The device number does not change if you move the drop, but you can modify the number. However, if you modify the number, the link breaks between the device name and the drop number. Schneider Electric recommends that you allow the drop number to equal the device name, even if it can be modified.
You cannot edit the IP address and Sub network (mask) fields. The IP address is editable only in the
of the 140CRP31200 module.
The value for Sub network is deduced from the 140CRP31200 sub network mask.
Hold up time parameter:
S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
Parameter
Hold up time
Comment
The hold up time represents the time (ms) that device outputs are maintained in their current states after a communication disruption and before taking their fallback values:
• default value : 1000 ms
• valid value range : 50...65,530 ms
The minimum holdup time differs for standalone and Hot Standby systems. If you assign a holdup time value that is less than the recommended minimum value, you can send an I/O module to the fallback state. When communications are restored, the I/O module restarts and may not operate as anticipated.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not configure a holdup time value that is less than the recommended minimum value for standalone or Hot Standby systems:
REQUIRES CLEANUP standalone systems:
• periodic application: 4.4 x PLC scan time
• cyclic application: configured watchdog value
REQUIRES CLEANUP
Hot Standby systems: configured watchdog value + PLC scan time
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Connection parameters :
Parameter
Custom RPI
CRA->CRP
RPI
CRP->CRA
RPI
Comment
Check this box to configure the CRA->CRP RPI value.
NOTE: The minimum CRA->CRP RPI value is 5 ms.
NOTE: Only change the CRA->CRP RPI value if you are using the
IU_ERIO function block, page 63
.
Inputs: The RPI is the input refresh rate at which the adapter module sends inputs to the 140CRP31200 module. The RPI is set in the subscribe field for the adapter on the remote I/O drop.
• periodic mode : default value = 1/2 MAST period
• cyclic mode : default value = 1/4 MAST watchdog timeout period
• valid values : 5...1500 (ms)
You can configure this value when Custom RPI is checked.
Outputs: Outputs are passed from the 140CRP31200 module to the adapter. Set the output refresh rate with the Application Trigger value ( CRP->CRA RPI ) at the end of the CPU MAST task:
• periodic mode : default value = 1.1 * MAST period. The value output is sent at the end of the actual MAST period.
• cyclic mode : default value = 1/4 * watchdog timeout period. The value output is sent at the end of the actual MAST period.
NOTE: The default value for the watchdog timer is 250 ms. If the MAST task does not finish within the watchdog period, the process times out. If the watchdog is greater than 4 times the MAST period, the drops could switch to fallback while the CPU is running. For example, MAST period = 20 ms, logic execution = 90 ms, watchdog time = 100 ms.
You cannot edit this value. All outputs are published synchronously or at the execution of the MAST task:
• synchronously: immediately at the end of the MAST task
• execution of IU_ERIO: You can only generate outputs when you
ERIO function block, page 63 . (See the note below.)
S1A48978.14
45
Remote I/O Modules
Configuration and Programming with Control Expert
NOTE:
• When the Periodic mode is selected for the MAST task, the Period value allows the complete execution of the logic. (The MAST can overrun when its execution time exceeds this value.) Valid values: 1...255 ms
(increment: 1 ms).
• When Cyclic mode is selected for the MAST task, the outputs are sent upon the completion of the task. The Watch Dog value (10 ... 1500 ms, default = 250) should be greater than the execution time. Valid values:
10...1500 ms (increment: 10 ms, default = 250 ms).
Device DDT Parameters
Device DDT Parameters (Remote I/O Drop)
This topic describes the Control Expert Device DDT tab for an Ethernet remote I/
O drop that includes a 140CRA31200 or BMXCRA312•0 adapter module. A derived data type (DDT) is a set of elements with the same type ( ARRAY ) or with different types (structure).
The device DDT instance name can be defined manually but, when adding a module, a default device DDT instance name (see EcoStruxure ™ Control Expert,
Program Languages and Structure, Reference Manual) is defined by Control
Expert
NOTE:
• These instructions assume that you have already
Control Expert project, page 34
.
• Refer to the
Derived Data Types chapter, page 48
to create, update, and view derived data types.
Access the Device DDT Tab
Access the Device DDT parameters in Control Expert:
Step
1
2
Action
Expand (+) EIO Bus in the Control
Expert Project Browser
Double-click on the EIO drop (Quantum or Modicon X80.
Comment
Path: Project Browser
>
EIO Bus
>
EIO
Quantum Drop / EIO Modicon X80 Drop
The EIO drop window appears. It contains the parameter tabs for the remote I/O drop.
Example of the Implicit device DDT area which contains a name and a type.
46
Parameters
Use the Control Expert Device DDT tab to configure these parameters for the adapter on the remote I/O rack:
S1A48978.14
Configuration and Programming with Control Expert
Parameter
Implicit device DDT Name
Goto details
Type
Remote I/O Modules
Description
A default device DDT instance name (see EcoStruxure ™
Control Expert, Program Languages and Structure,
Reference Manual) is defined by Control Expert.
NOTE:
• There are 2 device DDT types for Ethernet remote
I/O drops in a Quantum system:
◦ 140CRA31200 adapter: T_U_DROP_STD_IN
◦ BMXCRA312•0 adapter: T_M_DROP_EXT_IN
• There is 1 device DDT type for a Quantum
Ethernet remote I/O drop in an M580 system:
◦ 140CRA31200 adapter: T_Q_DROP_EXT_IN module type (uneditable) link to the DDT data editor screen
Time Stamping
Time Stamp Module
Use these modules on an Ethernet remote I/O drop:
• Modicon X80 BMXCRA31210 adapter module with a BMX ERT 1604 time stamp module
• Quantum 140CRA31200 adapter module with a 140 ERT 1604 module
This sample rack configuration in Control Expert shows an X80 EIO drop with the required BMX ERT 1604 module:
Configuration
Double-click the BMX ERT 1604 in the remote rack to see the time stamp Configuration tab.
S1A48978.14
47
Remote I/O Modules
Configuration and Programming with Control Expert
NOTE: For more information about time stamping with the BMXCRA31210 modules, refer to the Modicon X80, BMXERT0604T Time Stamp Module,
User Guide .
Derived Data Types
Overview
This chapter describes how to complete your Control Expert project by creating, updating, and viewing derived data type (DDT) variables.
Device DDT Names for the Quantum EIO Remote I/O Head Module
Introduction
This topic describes the Control Expert Device DDT tab for a Quantum local rack that includes a 140CRP31200 remote I/O head module. A derived data type
(DDT) is a set of elements with the same type ( ARRAY ) or with different types
(structure).
The device DDT instance name can be defined manually but, when adding a module, a default device DDT instance name (see EcoStruxure ™ Control Expert,
Program Languages and Structure, Reference Manual) is defined by Control
Expert
Modifying a Device DDT name
In Control Expert a Device DDT name can be easily modified:
Step
1
2
3
4
5
Action
Open Data Editor in the Control
Expert Project Browser .
Right click on the device DDT and use the Copy/Paste .
Expand Local Bus in the Control
Expert Project Browser .
Double-click the 140CRP31200 module.
Select the Device DDT tab.
Comment
Path: Tools > Data Editor
A new default name is proposed by default.
Path: Tools > Project Browser > Project >
Configuration > Local Bus
The parameter tabs appear.
select the new DDT name (eg : My_CRP312) as the name of Device DDT.
The Implicit device DDT field contains a default name and type.
Access the Device DDT Tab
In Control Expert:
Step
1
2
3
Action
Expand Local Bus in the Control Expert
Project Browser .
Double-click the 140CRP31200 module.
Select the Device DDT tab.
Comment
Path: Tools > Project Browser > Project
>
Configuration
>
Local Bus
The parameter tabs appear.
48 S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
Example of the Implicit device DDT area which contains a name and a type.
S1A48978.14
Parameters
Use the Control Expert Device DDT tab to configure parameters for the
140CRP31200 module on the local rack:
Parameter
Implicit device
DDT
Goto details
Name
Type
Description a default device DDT instance name (see EcoStruxure ™ Control
Expert, Program Languages and Structure, Reference Manual) is defined by Control Expert.
module type (uneditable) link to the DDT data editor screen
Implicit Device DDT Types
The 140CRP31200 module implements the implicit device DDT type in accordance with the CPU configuration:
• T_U_CRP_HSBY_IN: Hot Standby configurations
• T_U_CRP_STD_IN: standalone configurations
Hot Standby Configurations
This table describes the fields in the T_U_CRP_HSBY_IN implicit device DDT type that is used with the 140CRP31200 module in Hot Standby configurations:
Field
LOCAL_PLC
REMOTE_PLC
Type
T_U_CRP_STD_IN
T_U_CRP_STD_IN
Access
R
R
Description
140CRP31200 status (local PLC)
140CRP31200 status (remote/peer PLC)
Standalone and Hot Standby Configurations
This table describes the fields in the T_U_CRP_STD_IN implicit device DDT type that is used with the 140CRP31200 module in standalone and Hot Standby configurations.
ETH_STATUS (BYTE):
Name
PORT1_LINK
Type
BOOL
Rank
0
Bit
0
Description
PORT2_LINK BOOL 1 1
0 = Port 1 link is down.
1 = Port 1 link is up.
0 = Port 2 link is down.
1 = Port 2 link is up.
49
Remote I/O Modules
Configuration and Programming with Control Expert
Name
PORT3_LINK
PORT4_LINK
CRP_LINK
REDUNDANCY_
STATUS
SCANNER_OK
GLOBAL_STATUS
Type Rank
2
Bit
2
Description
BOOL
BOOL
BOOL
BOOL
3
4
5
3
4
5
0 = Port 3 link is down.
1 = Port 3 link is up.
0 = Port 4 link is down.
1 = Port 4 link is up.
0 = CRP link is down.
1 = CRP link is up.
0 = Redundant owner is not present.
1 = Redundant owner is present.
NOTE: In Hot Standby systems, if this bit is set to 1 either in the local or remote 140CRP31200 DDT then the main physical ring is OK. If this bit is set to 0 in both the local and remote 140CRP31200 DDTs, the main physical ring is broken.
BOOL 6 6
BOOL 7 7
0 = Scanner is not present.
1 = Scanner is present.
0 = At least 1 service is not operating normally.
1 = All services are operating normally.
NOTE: You can monitor breaks in the remote I/O main ring by diagnosing the
REDUNDANCY_STATUS bits in the 140CRP31200 module DDT. The system detects and reports in this bit a main ring cable break that persists for at least
5 seconds.
Within the REDUNDANCY_STATUS bit:
• 0: The cable is broken or the device is stopped.
• 1: The loop is present and healthy.
In a Hot Standby system, perform a BITWISE OR operation of the
REDUNDANCY_STATUS bit in the DDTs for both the primary and standby
140CRP31200 modules to determine whether a cable break has occurred. As indicated above, a value of 0 indicates a cable break; a value of 1 indicates no cable break.
SERVICE_STATUS (BYTE):
Name Type
RSTP_SERVICE
PORT502_SERVICE
SNMP_SERVICE
IP_ADDRESS_
STATUS
(reserved bits)
BOOL
BOOL
BOOL
BOOL
—
Rank
0
Bit
0
Description
2
3
4
2
3
4
5...7
5...7
0 = RSTP service is not operating normally.
1 = RSTP service is operating normally or disabled.
0 = Port 502 service is not operating normally.
1 = Port 502 service is operating normally or disabled.
0 = SNMP service is not operating normally.
1 = SNMP service is operating normally or disabled.
0 = IP address is a duplicate or unassigned.
1 = Assigned IP address is not a duplicate.
—
ETH_PORT_STATUS:
50 S1A48978.14
Configuration and Programming with Control Expert
Name
These combined 2-bit values indicate the conditions (WORD) port function
RSTP role
Remote I/O Modules
—
—
—
—
Rank
—
—
—
—
—
—
2
3
0
1
2
3
14/15
0
1
Bit
1/0
3/2
5/4
7/6
9/8
11/10
12/13
Description
Ethernet port 1 function
Ethernet port 1 RSTP role
Ethernet port 2 function
Ethernet port 2 RSTP role
Ethernet port 3 function
Ethernet port 3 RSTP role
Ethernet port 4 function
Ethernet port 4 RSTP role disabled access port port mirror remote I/O network port unknown alternate/backup root designated
IN_BYTES:
Type
UINT
Rank
4/5
Bit
—
IN_ERRORS:
Type
UINT
Rank
6/7
Bit
—
OUT_BYTES:
Type
UINT
Rank
8/9
Bit
—
OUT_ERRORS:
Type
UINT
Rank
10/11
Bit
—
Description number of bytes (octets) received on interface
Description number of inbound packets that contain detected errors
Description number of bytes (octets) sent on interface
Description number of outbound packets that contain detected errors
Device DDT Names for Quantum EIO Remote I/O Adapter Modules
Introduction
This topic describes the Control Expert Device DDT tab for an Ethernet remote I/
O drop that includes a •••CRA312•0 adapter module.
The I/O structure type for the Quantum remote I/O drop is T_U_DROP_STD_IN.
The I/O structure type for the Modicon X80 remote I/O drop is T_M_DROP_EXT_
IN. In addition, when a remote I/O drop with a Quantum 140CRA31200 module is placed into an M580 system, the I/O structure type is T_Q_DROP_EXT_IN.
The device DDT instance name can be defined manually but, when adding a module, a default device DDT instance name (see EcoStruxure ™ Control Expert,
S1A48978.14
51
Remote I/O Modules
Configuration and Programming with Control Expert
Program Languages and Structure, Reference Manual) is defined by Control
Expert
NOTE: These instructions assume that you have already
Control Expert project, page 27 .
Access the Device DDT Tab
In Control Expert:
Step
1
2
3
Action
Expand EIO Bus in the Control Expert
Project Browser to display the EIO drop (Quantum
Double-click the EIO drop.
Select the Device DDT tab.
Example of the Implicit device DDT area which contains a name and a type.
Comment
Path: Tools
Project
> Project Browser >
> Configuration > EIO Bus >
EIO Quantum Drop
The EIO drop window appears.
Name
IO_HEALTH_RACK1 only for T_Q_DROP_EXT_IN
IO_HEALTH_RACK2 only for T_Q_DROP_EXT_IN
Drop Parameters
Use the Control Expert Device DDT tab to configure these parameters for the
Ethernet remote I/O drop:
Parameter
Implicit device DDT
Goto details
Name
Type
Description
A default device DDT instance name (see EcoStruxure ™
Control Expert, Program Languages and Structure,
Reference Manual) is defined by Control Expert.
module type (uneditable) link to the DDT data editor screen
Diagnostic Parameters
This table contains the DROP diagnostic parameters for the Ethernet remote I/O drop module:
Type
WORD
Bit
—
Description
Health bits of rack 1: slots 1 to 16
WORD — Health bits of rack 2: slots 1 to 16
52 S1A48978.14
Configuration and Programming with Control Expert
Name
DEVICE_NAME
VERSION
ROTARY_SWITCHES
CRA_STATE
CRA_DIAGNOSTIC [WORD] GLOBAL_IO_HEALTH
CCOTF_IN_PROGRESS
CCOTF_INVALID_CONF
IOPL_MISMATCH
SWITCH_CHANGE
DROP_COM_HEALTH
CYCLE_CURR_TIME
CYCLE_MAX_TIME
CYCLE_MIN_TIME
TIME_STAMP_RECORDS
(Not used for 140CRA31200 applications.)
TS_DIAGNOSTIC_FLAGS
(WORD)
(BMXCRA312•0 only)
TIME_VALID
CLOCK_FAILURE
CLOCK_NOT_SYNC
BUFF_FULL
SOE_UNCERTAIN
TS_BUF_FILLED_PCTAGE
(BMXCRA312•0 only)
TS_EVENTS_STATE
(BMXCRA312•0 only)
ETH_STATUS (BYTE) PORT1_LINK
S1A48978.14
UINT
BOOL
BOOL
—
0
1
BYTE
BYTE
BOOL
BOOL
BOOL
BOOL
2
3
7
—
—
0
Type string[16]
Bit
—
WORD —
BYTE
BYTE
—
—
BOOL
BOOL
BOOL
BOOL
0
1
2
3
BOOL
BOOL
UINT
4
5
—
UINT
UINT
—
—
Remote I/O Modules
Description
device name of the remote I/O drop, page 44
firmware version (Maj, Min) (4 digits coded in BCD) rotary switch value at power up
1: CRA module is idle.
2: CRA module is stopped.
3: CRA module is running.
0: At least one I/O module in the drop reports bad health.
CCOTF is in progress.
CCOTF configuration is not valid.
There is an output data mismatch. The modules in the rack are not the same as the modules configured in the PLC.
The rotary switches settings have changed since the last power up.
This bit shows the drop communication health (set to 1 in remote I/O drop).
This word indicates the execution time of the last CRA cycle.
It has values between [0,65535] with a resolution of 0.01 ms, therefore, the last cycle time is between [0,655] ms.
This word indicates the longest CRA cycle execution time since the last start.
It has values between [0,65535] with a resolution of 0.01 ms, therefore, the longest cycle time is between [0,655] ms.
This word indicates the shortest CRA cycle execution time since the last start.
It has values between [0,65535] with a resolution of 0.01 ms, therefore, the shortest cycle time is between [0,655] ms.
This word contains the number of Time
Stamp records available in the drop local buffer.
The time is valid and synchronized.
The time source of the sending device is not validated. The time stamp value is ignored.
The time source of the sending device is not synchronized with the external UTC time.
The buffer is full.
The SOE (sequence of events) in the buffer is not known. The SOE is reset when the sequence of events is OK.
This byte reports the percentage of the buffer filled (0...100).
The byte reports the main state of TS events.
0 = Port 1 link is down.
1 = Port 1 link is up.
53
Remote I/O Modules
Name
PORT2_LINK
PORT3_LINK
(reserved bit)
RPI_CHANGE
REDUNDANCY_OWNER
GLOBAL_STATUS
SERVICE_STATUS (BYTE) RSTP_SERVICE
NTP_UPDATE (reserved)
MAX_PACKET_INTERVAL
54
SNTP_SERVICE (reserved)
PORT502_SERVICE
SNMP_SERVICE
ETH_PORT_STATUS (BYTE)
(reserved bits)
These combined 2-bit values indicate the conditions port function
RSTP role
Type
BOOL
BOOL
—
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
—
WORD
—
—
UINT
UINT
Configuration and Programming with Control Expert
3
4
6
Bit
1
2
7
8
9
10
11
4...7
1/0
3/2
5/4
7/6
0
1
9/8
11/10
12/13
14/15
2
3
0
1
2
3
—
—
Description
0 = Port 2 link is down.
1 = Port 2 link is up.
0 = Port 3 link is down.
1 = Port 3 link is up.
—
RPI change: EtherNet/IP RPI change is in progress (during CCOTF).
0 = Redundant owner is not present.
1 = Redundant owner is present.
0 = At least 1 service is not operating normally.
1 = All services are operating normally.
0 = RSTP service is not operating normally.
1 = RSTP service is operating normally or disabled.
0 = SNTP service is not operating normally.
1 = SNTP service is operating normally or disabled.
0 = Port 502 service is not operating normally.
1 = Port 502 service is operating normally or disabled.
0 = SNMP service is not operating normally.
1 = SNMP service is operating normally or disabled.
—
Ethernet port 1 function
Ethernet port 1 RSTP role
Ethernet port 2 function
Ethernet port 2 RSTP role
Ethernet port 3 function
Ethernet port 3 RSTP role
Ethernet port 4 function
Ethernet port 4 RSTP role disabled access port port mirror remote I/O network port alternate backup designated root elapsed time (100 ms) since last update from NTP server maximum packet interval (ms) for output packets
S1A48978.14
Configuration and Programming with Control Expert
Name
IN_BYTES
IN_ERRORS
OUT_BYTES
OUT_ERRORS
SOE_UNCERTAIN
Type
UINT
UINT
UINT
UINT
BOOL
—
—
—
Bit
—
—
Remote I/O Modules
Description number of bytes (octets) received on interface number of inbound packets that contain detected errors (In Errors) number of bytes (octets) sent on interface number of outbound packets that contain detected errors (In Errors)
The SOE (sequence of events) in the buffer is not known. The SOE is reset when the sequence of events is OK.
Device DDT Types for I/O Modules
Refer to the following user guides for specific I/O module device DDT types:
I/O Module
Modicon X80 discrete input/output
Modicon X80 analog input/output
BMX EHC 0800
BMX EHC 0200
BMX NOM 0200
BMX ERT 1604T
User Guide Reference
Modicon M340 Using EcoStruxure ™ Control Expert Discrete Input/
Output Modules User Manual
Modicon M340 with EcoStruxure ™ Control Expert Analog Input/Output
Modules User Manual
Modicon M340 with EcoStruxure ™ Control Expert Counting Module
BMX EHC 0800 User Manual
Modicon M340 with EcoStruxure ™ Control Expert Counting Module
BMX EHC 0200 User Manual
Modicon M340 with EcoStruxure ™ Control Expert Serial Link User
Manual
BMX ERT 1604T M340 ERT Module User Manual
Elementary Functions (EFs) and Function Blocks (EFBs)
Introduction
Use the elementary functions (EFs) and elementary function blocks (EFBs) in the following table when you use Quantum RIO drops in M580 systems.
Using Quantum Function Blocks in M580 Systems
Supporting Quantum Configurations
M580 PLCs use these elementary functions (EFs) and elementary function blocks
(EFBs) to support Quantum I/O configurations:
Function Block
ACI030
ACI040
ACO020
ACO130
AII330
AII33010
AIO330
AMM090
Quantum Family
I/O management
I/O management
I/O management
I/O management
I/O management
I/O management
I/O management
I/O management
Description
EFBs: Manage the I/O for Quantum ERIO modules.
S1A48978.14
55
Remote I/O Modules
Function Block
ARI030
ATI030
AVI030
AVO020
ERT_854_10
ERT_854_20
ERT_854_30
I_NORM_WARN
I_PHYS_WARN
I_SCALE_WARN
I_SET
I_RAW
I_RAWSIM
I_NORM
I_PHYS
I_SCALE
I_FILTER
O_NORM_WARN
O_PHYS_WARN
O_SCALE_WARN
O_SET
O_RAW
O_NORM
O_PHYS
O_SCALE
O_FILTER
DROP
XDROP
Quantum Family
I/O management
I/O management
I/O management
I/O management
I/O management
I/O management
I/O management analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling analog I/O scaling
I/O configuration
I/O configuration
Configuration and Programming with Control Expert
Description
EFBs: Scale analog values from Quantum analog modules.
EFs: Scale analog values from Quantum analog modules.
EFBs: Scale analog values from Quantum analog modules.
EFs: Scale analog values from Quantum analog modules.
EFBs: I/O configuration blocks for building data blocks for analog or ERT modules.
Application Download
Downloading the Application to the PLC
Downloading the Application to the PLC
Download the Control Expert application to the PLC through one of its ports or through a connection to an Ethernet communication module:
Method
USB port
Modbus Plus port
Connection
If the PLC and the PC that is running Control Expert both have USB ports, you can download the application to the PLC directly through the
USB ports.
If the PLC and the PC that is running Control Expert both have Modbus
Plus ports, you can download the application to the PLC directly through the Modbus Plus ports.
56 S1A48978.14
Configuration and Programming with Control Expert
Remote I/O Modules
Method serial port
Connection
If the PLC and the PC that is running Control Expert both have serial ports, you can download the application to the PLC directly through the serial ports.
Ethernet port If the PLC and the PC that is running Control Expert both have Ethernet ports, you can download the application to the PLC directly through the
Ethernet ports.
communication module You can download the application to the PLC by connecting Control
Expert to the IP address of the communication module.
NOTE: You cannot download the application to the PLC with the 140CRP31200 module.
S1A48978.14
57
Remote I/O Modules
Explicit Messaging
Overview
EtherNet/IP uses the TCP/IP and UDP/IP protocols to implement both explicit and implicit messaging.
This chapter explains the 140CRP31200 remote I/O head module and its use of explicit messaging for request-and-reply communications for non-real-time information (like configuration and diagnostic data). A network node that receives a TCP/IP-encapsulated explicit message processes the message and generates a response.
NOTE: The 140CRP31200 module can process 16 MBP_MSTR blocks per
MAST cycle.
NOTE: If you receive a detected error message — stating that the
140CRP31200 module does not have a link (has no cable), MSTR functionality may not be available. If this happens, check that your cables are connected properly.
This chapter describes how to use both Control Expert function block logic and the
Control Expert interface to send explicit messages.
EtherNet/IP Explicit Messaging Using MBP_MSTR
Introduction
This section shows you how to configure the MBP_MSTR function block for explicit messages.
NOTE: Use the 140CRP31200 module to send MBP_MSTR commands to diagnose the status of sub-rings. For other operations (get remote statistics, read data, etc.), we recommend that you send an MBP_MSTR command from a 140 NO• 7•• •• module.
Supported MBP_MSTR Function Codes
Function Codes
We recommend using these MBP_MSTR function codes with the 140 CRP 312 00 module to diagnose sub-rings:
MBP_MSTR Control
Code
0x00 0x0E
Description
EIP explicit message (connected)
0x01 0x0E EIP explicit message (unconnected)
140 CRP 312 00
Support
X
NOTE: The 140 CRP 312 00 module supports only 16 MBP_MSTR codes per
CPU cycle.
EtherNet/IP Explicit Messaging Services
Overview
Communication protocols:
• EtherNet/IP : The 140 CRP 312 00 module uses the EtherNet/IP protocol for all exchanges of I/O data.
• Modbus : The 140 CRP 312 00 module uses the Modbus/TCP protocol for reading diagnostics and for MBP_MSTR.
58 S1A48978.14
Remote I/O Modules
Every EtherNet/IP explicit message performs a service. Each service is associated with a service code (or number). You will need to identify the explicit messaging service by its name, decimal number, or hexadecimal number.
You can execute EtherNet/IP explicit messages using either a Control Expert
MBP_MSTR function block or the Control Expert Ethernet Configuration Tool’s
EtherNet/IP Explicit Message Window . (Refer to
Control Expert GUI, page 61 .)
NOTE: Configuration edits made to an Ethernet communication module from the Control Expert Ethernet Configuration Tool’s EtherNet/IP Explicit Message
Window are not saved to the operating parameters stored in the CPU and, therefore, are not sent by the CPU to the module on startup.
You can use Control Expert to construct a request that executes any service supported by the target device that is compliant with the EtherNet/IP protocol.
Services
The services supported by Control Expert include these standard explicit messaging services:
Service Code
Hex Dec
Description
3
4
1
2
5
6
7
8
9
A
D
E
10
3
4
1
2
5
6
7
8
9
10
13
14
16
Get_Attributes_All
Set_Attributes_All
Get_Attribute_List
Set_Attribute_List
Reset
Start
Stop
Create
Delete
Multiple_Service_Packet
Apply_Attributes
Get_Attribute_Single
Set_Attribute_Single
18
19
1A
1B
1C
11
14
15
16
17
17
20
21
22
23
24
25
26
27
28
Find_Next_Object_Instance
Error Response (DeviceNet only)
Restore
Save
No Operation (NOP)
Get_Member
Set_Member
Insert_Member
Remove_Member
GroupSync x (available service)
— (service not available)
X
X
X
X
—
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Available in...
MBP_MSTR block
X
X
X
X
X
—
X
X
X
X
X
X
X
—
X
X
X
X
X
—
Control Expert
GUI
X
X
—
—
S1A48978.14
59
Remote I/O Modules
Configuring the CONTROL and DATABUF Parameters
Overview
The CONTROL and DATABUF output parameters define the operations of the
MBP_MSTR function block. For the EtherNet/IP protocol, the structure of the
CONTROL and DATABUF output parameters remains the same for all explicit messaging services.
Configuring the Control Parameter
Use MSTR operation 14 or 270 to send generic Modbus requests on the network.
(These operation codes are not available on the Modbus Plus port or embedded
Ethernet port on the CPU.)
The CONTROL parameter register contains these consecutive words:
Register
CONTROL[0]
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL [5]
CONTROL [6]
CONTROL[7]
CONTROL[8]
1
1
Function operation detected error status data buffer length response offset routing register
IP address request length response length
Description
• 14 = unconnected
• 270 = connected
Holds the event code (read-only).
Data buffer length, in words
Offset for the beginning of the response in the data buffer, in 16-bit words
Note: To avoid overwriting the request, make the response offset value greater than the request length CONTROL[10] .
Specify a network destination node during data transfer:
• MSB: The most significant byte contains the source node address (for example, the slot number of the 140 NOE 771 •• or 140CRP31200 module).
Exception:
The value of the integrated Ethernet port on the CPU is 254 (FE h) regardless of the CPU slot number.
Note: Only 1 Ethernet 140CRP31200 module can be used.
• LSB: The least significant byte contains the destination node address (for example, MBP on the Ethernet Transporter (MET) mapping index for the 140
NOE 771 •• or the drop number for the 140CRP31200).
Each address contains 1 byte of the 32-bit IP address:
• high byte = byte 4 of the IP address (MSB)
• low byte = byte 3 of the IP address
• high byte = byte 2 of the IP address
• low byte = byte 1 of the IP address (LSB) length of the CIP request, in bytes length of the response received, in bytes read only—set after completion
1. For example, the Control parameter handles the IP address 192.168.1.6 in the following order: Byte 4 = 192, Byte 3 = 168, Byte 2 = 1,
Byte 1 = 6.
Configuring the Data Buffer
The DATABUF varies in size. It consists of contiguous registers that include—in sequence—both the CIP request and the CIP response. To avoid overwriting the request, confirm that the data buffer is large enough to contain both the request and response data.
Data Buffer:
Variable size: set in CONTROL[2]
CIP Request:
Request size: set in CONTROL[7]
60 S1A48978.14
Remote I/O Modules
CIP Response:
Starting position: set in CONTROL[3]
Response size: reported in CONTROL[8]
NOTE: If the response offset is smaller than the request size, response data overwrites part of the request.
The formats of the data buffer’s CIP request and CIP response are described in this table. (Both the request and response are structured in little endian order.)
0
1
Request
Byte offset
2
...
2
3
4
...
0
1
Response
Byte offset
Field
Service
Request_Path_Size
Request_Path
Request_Data
Data Type
Byte
Byte
Padded EPATH
Byte array
Field
Reply Service
Reserved
General Status
Data Type
Byte
Byte
Byte
Size of Additional Status Byte
Additional Status Word array
Response Data Byte array
Description
Service of the explicit message
The number of words in the Request_Path field
This byte array describes the path of the request (including class ID, instance ID, etc.) for this transaction.
Service-specific data in the explicit message request delivery (if none, this field is empty)
Description
Service of the explicit message + 16#80
0
EtherNet/IP General Status
Additional Status array size—in words
Additional status
Response data from request, or additional detected error data if
General Status indicates a detected error
Explicit Messaging via the Control Expert GUI
Sending Explicit Messages to EtherNet/IP Devices
Introduction
The 140 CRP 312 00 module uses explicit messages from Control Expert to obtain diagnostics information from an EtherNet/IP module or device on the network.
Access the EtherNet/IP Explicit Message Window
Step
1
2
Action
Access the 140 CRP 312 00 module for
Online Action.
Double-click the 140 CRP 312 00 module in the Control Expert rack view.
Comment
Refer to the
.
The EtherNet/IP Explicit Message tab appears.
S1A48978.14
61
Remote I/O Modules
The EtherNet/IP Explicit Message Tab
The EtherNet/IP Explicit Message window shows an example of the configuration of an EtherNet/IP explicit message and the response to the message. The explicit message is addressed to a DRS to obtain diagnostic information:
Field
Address
NOTE: Refer to your
EtherNet/IP device user manual for the values in the
Address field.
Service
Data (hex)
Messaging
Send to Device (button)
Parameters
Features of the EtherNet/IP Explicit Message screen:
Parameter (Value)
IP Address
( x.x.x.x
)
Class
(1...65535)
Instance
(0...65535)
Attribute
(0...65535)
Number
(1...127)
Name
Enter Path (hex)
—
Connected
Unconnected
—
Description
The IP address of the target device, used to identify the target of the explicit message. (The IP address in the example above is 192.168.1.6.)
The class identifier of the target device is an integer that is used to construct the message path. (The class in the example above is 4.)
The class instance of the target device is an integer that is used to construct the message path. (The class instance in the above example is
100.)
The specific device attribute (or property) is the target of the explicit message. This integer is used to construct the message path. (The attribute in the above example is 3.)
NOTE: Check this box to enable this optional field.
Number is an integer that is associated with the service that the explicit message performs.
NOTE: If you select Custom Service , type in a service number. This field is read-only for all other services.
Scroll to the name of the service that you want the explicit message to perform. In the example above, Get_Attribute_Single is selected.
Check this box to enable the message path field where you can manually enter the entire path to the target device. (In the example above, the box is not checked.)
The Data field contains the data to be sent to the target device for services that send data. (The field is blank in the example above.)
Select the type of explicit message to send:
• unconnected : An unconnected message requires path information
(addressing) that identifies the destination device and (optionally) device attributes.
• connected : A connected explicit message contains path information and a connection identifier to the target device.
NOTE: The example uses an Unconnected message.
After the explicit message is configured, press Send to Device .
62 S1A48978.14
Field
Response (hex)
Status
Repeat (500ms)
Remote I/O Modules
Parameter (Value)
—
—
—
Description
Response contains the (hexadecimal) data sent to the configuration by the target device when you press Send to Device .
After you press Send to Device , the messages in the Status field indicate the status of the explicit message.
Check this box to send the explicit message every 500 ms. (In this example, leave this blank.)
NOTE: You can use explicit messaging to perform many different services, but every EtherNet/IP device does not support every service.
Immediate I/O Access (IU_ERIO)
Description
Function Description
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not use the IU_ERIO function block in Quantum Hot Standby installations.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
An IU_ERIO function block updates Ethernet remote I/O drop input and output modules with an optimal response time. The Ethernet remote I/O drop inputs and outputs are updated during the MAST task.
Call this function block in a MAST task. It can be called more than once in a task.
NOTE: To maintain system performance, we recommend that you use no more than 10 executions of the IU_ERIO block during a single MAST task.
The input and output modules are physically located on an Ethernet remote I/O drop and declared in the Ethernet configuration.
EN and ENO can be configured as additional parameters.
NOTE: Refer to the Quantum EIO System Planning Guide for calculating the
ART when your application does not use an IU_ERIO function block.
IU_ERIO Mechanism
The Ethernet remote I/O drop input values are read in the 140CRP31200 module with an optimal response time.
The input values read in the 140CRP31200 module represent the latest values sent in an asynchronous way by the adapter module in each drop. The maximum time shift between values read in the 140CRP31200 and actual input values depends on the
adapter’s publishing frequency (subscribe field CRA-> RPI ), page
.
S1A48978.14
63
Remote I/O Modules
The following diagram represents the I/O exchanges between a CPU and the
Ethernet remote I/O drops:
Representation in FBD
Representation:
Representation in LD
Representation:
64
Representation in IL
CAL IU_ERIO(DROP:=>Drop_Number, DIR:=>Input_Output, STATUS=
>Status_Report);
Representation in ST
IU_ERIO(DROP:=>Drop_Number, DIR:=>Input_Output, STATUS=
>Status_Report);
S1A48978.14
Remote I/O Modules
Parameter Description
Input parameters:
Parameter
Drop
Dir
Data type
INT
BOOL
Meaning
Drop number (1...31)
Drop number:
• 1: Drop 1
• 2: Drop 2
• ...
• 31: Drop 31
Data direction:
• 0 = Outputs. The output values are sent immediately to the 140CRP31200 module.
• 1 = Inputs. The input values are read immediately from the 140CRP31200 module.
Output parameter:
Parameter
Status
Data type
WORD
Meaning
Status report from the 140CRP31200 module:
• 0002 hex: Invalid drop number
• 0003 hex: Ethernet remote I/O drop is not configured
• 0004 hex: Ethernet remote I/O drop is not connected
• 0005 hex: Retry number is exceeded
• 0007 hex: An error is detected on the
140CRP31200 module
• 0008 hex: Operation was not completed before time out
• 0009 hex: 140CRP31200 module is not present on the local drop
• 000B hex: Operation OK
NOTE: If no connection is opened with the Ethernet remote I/O drop, a detected communication error (system words %SW172 to %SW173) is returned.
S1A48978.14
65
Remote I/O Modules
Implicit Messaging
The MAST Task in Implicit Exchanges
Task Management
This topic explains implicit messaging and the relationship between the MAST task configuration and the remote I/O implicit exchanges.
Implicit messaging maintains open connections for real-time communications of a predefined nature between consumers and producers. Implicit messages contain control data and a connection identifier.
EtherNet/IP uses the TCP/IP and UDP/IP protocols to implement both explicit and implicit messaging.
Access the MAST Configuration
View the Properties of MAST :
Step
1
2
3
Action
Go to the Properties of MAST dialog box in Control Expert ( Tools
Browser
>
Project
>
Program
>
Tasks
>
MAST ).
>
Project
Right-click Properties .
Configure the parameters.
CIP Definitions
Inputs: The MAST period should be 2 times the RPI of the 140CRA31200 or
BMXCRA312•0 adapter on the remote I/O drop. This provides new input values for every MAST cycle. (For example, an RPI of 25 ms provides data for a MAST period of 50 ms.)
Outputs: The CPU in the local rack of a Quantum Ethernet I/O system produces outputs to Ethernet remote I/O drops and consumes inputs from those drops
(based on the producer/consumer model). A consumer (the remote drop) detects the lack of updated data through a time-out. (Possible time-out values are N x RPI, where N = 4, 8, 16 ....) When a time-out is triggered, the consumer assumes that the producer is absent.
Periodic and Cyclic Modes
The effect that periodic and cyclic modes have on implicit messages is explained in the
description of the connection parameters, page 44 .
Quantum I/O Management for Implicit I/O Exchanges
Assign state RAM addresses:
Drop type
Quantum Ethernet remote
I/O
Modicon X80 Ethernet remote I/O
Instruction
The direct state RAM address manages the Quantum I/O data.
Assign the state RAM addresses for each module. (Default values are proposed by Control Expert in the module configuration windows.)
You can also define symbols on the I/O variables allocated in the state
RAM.
To assign state RAM addresses for Modicon X80 I/O data, refer to the topic
Device DDT Names for Quantum EIO adapters, page 51
66 S1A48978.14
Diagnostics
Overview
Remote I/O Modules
This chapter describes the diagnostics for the Quantum EIO modules. For details on diagnostics at the system level, refer to the systems diagnostics topic in the
Quantum Ethernet I/O System Planning Guide .
LED Indicators
LED Indicators on the 140 CRP 312 00 Module
Display
These LEDs are on the front of the 140CRP31200 module:
Description general power-up sequence
FDR client
EIP scanner
S1A48978.14
Indications
ODVA standard
LED conditions: component not operating invalid configuration not configured configured no/default module MAC no/default port MAC sequence non-ODVA standard no Ethernet connections duplicate IP waiting for IP default IP receive or assign IP invalid configuration no EIP connection or all EIP connections closed
—
—
—
—
—
—
—
Active green
—
—
— on
—
—
5 blink (.25
sec on; .25
sec off)
—
Ready green
Mod Status red on green off off off flash off off blink blink 2 blink 2
6 blink (.25
sec on; .25
sec off)
—
2
— blink 3 blink 4 off flash flash blink (.25
sec on; .25
sec off)
— off off flash on off off
1
— blink (.25
sec on; .25
sec off)
— on blink 5 blink 6 on blink 7 on off off off off flash on on on on off
Net Status red
—
—
— off off off
4
— blink (.25
sec on; .25
sec off)
— on off off off off off green
—
—
— on/flash off off
3
— blink (.25
sec on; .25
sec off)
— off off off flash off flash
67
Remote I/O Modules
Description
one or more connections established one connection timeout
Active green
—
Ready green on
Mod Status red off green on off on
Net Status red off green on
— on flash off
NOTE: In Hot Standby systems, the Net Status LEDs on the 140 CRP 312 00 modules are solid green during normal operations. When power to the 140
CRP 312 00 module in either rack A or B is lost, the Net Status LED on the
140 CRP 312 00 module in the partner rack is unchanged (solid green).
Ethernet Port Indications
These LEDs report the status of the Ethernet port:
Name
LINK
ACT
Color green yellow
— green
—
Status on on off blinking off
Description
100 Mbps link detected
10 Mbps link detected no detected link active Ethernet link (transmit or receive) inactive Ethernet link
LED Indicators on the Quantum EIO Adapter Module
Display
The LEDs are on the front of the adapter module:
140CRA31200:
68 S1A48978.14
BMXCRA312•0:
Remote I/O Modules
Indications
LED conditions:
Description power-up sequence not configured blink (.25 sec on; .25 sec off)
IP address not valid
Run green
1
—
IO red
2
—
Mod Status green red
Green/Red/Green flashing flashing off off
Net Status green red
Green/Red/Off off flashing off off
• valid IP address
• invalid configuration off off configured
I/O data communication established detected error states no external error detected external error detected
STOP
RUN recoverable error nonrecoverable error duplicate IP address flashing flashing flashing on
— off on
(note 1)
(note 2)
— on
—
— on on off off
— off
—
— off off flashing on on
—
— flashing flashing on off off off off
—
—
OS firmware update flashing
— flashing
— off
— on off off on on
NOTE 1 (STOP state):
• on: An input or output is a detected error that originates in a module, or a channel configuration or a channel configuration error has been detected.
• off: Operations are normal.
NOTE 2 (RUN state):
• on: External error is detected.
• off: External error is not detected.
Ethernet Port Indications
S1A48978.14
These LEDs report the status of the Ethernet port:
Name
LINK
Color green yellow
—
Status on on off
Description
100 Mbps link detected
10 Mbps link detected no detected link
69
Remote I/O Modules
Name
ACT
Color green
—
Status blinking off
Description active Ethernet link (transmit or receive) inactive Ethernet link
Service Port Management
Service Port Configuration
Introduction
The 140CRP31200 remote I/O head module and the remote I/O adapter modules
(140CRA31200 and BMXCRA31210) support the configuration of the SERVICE port without requiring you to re-build or download your application.
140CRP31200
The online configuration of the SERVICE port on the 140CRP31200 module is discussed in the section about
diagnostics through Control Expert, page 103
.
Adapter Modules
You can send explicit messages with an EtherNet/IP tool for the configuration of the SERVICE port on the 140CRA31200 or BMXCRA31210 modules. For details, refer to the discussions of
EtherNet/IP CIP objects, page 100
and
SERVICE port configuration for adapter modules, page 70
.
Cycling Power
The online configuration of the SERVICE port is volatile. The following situations can arise when power is cycled to the module while the application is being applied:
• The configuration can be lost.
• The configuration in the application can be applied to the SERVICE port.
Service Port Configuration for Adapter Modules
Configuration
Follow these steps to modify the Service Port configuration of an online
140CRA31200 or BMXCRA312•0 adapter module:
Step
1
2
3
Action
Launch the EtherNet/IP Explicit Message window, page 61
.
Assign these Device Services parameters:
• Address :
◦ IP Address: Enter the IP address of the adapter with the SERVICE port you want to configure.
◦ Class: 0x400
◦ Instance: 1
• Service :
◦ Name: Set_Attribute_Single
Set the Port Control value:
• Attribute : Check this box.
• Attribute (field): Enter 1 (access port).
• Data (hex) (field): Enter a value that is based on the
Port Control attribute definition, page 101 .
70 S1A48978.14
Remote I/O Modules
Step
4
5
Action
NOTE:
• To set the UINT value of 2, set the data field to 02 00 (low byte/high byte).
• If you enter 2 (port mirroring) in Attribute , refer to the next table.
• In port mirroring mode, the SERVICE port acts like a read-only port. That is, you cannot access devices (ping, connection to Control Expert, etc.) through the SERVICE port.
Leave the default values for these parameters:
• Enter Path(hex) : Leave this check box unselected.
• Repeat(500ms) : Leave this check this check box unselected.
• Messaging : Select Unconnected .
Press Send to Device .
Port Mirroring: Use these steps only if you chose 2 (port mirroring) for the Port
Control value (above):
Step
1
2
3
Action
Set the Port Control value:
• Attribute : Check this box.
• Attribute : Enter 2 (port mirroring).
• Data(hex) : Enter a value that is based on the
Port Control attribute definition, page 101
.
Accept the default values for other parameters (as before).
Press Send to Device .
Diagnostics Available through the CPU
System Diagnostics
Introduction
System diagnostics are performed locally on the CPU with system bits (%S) and system words (%SW).
Local Rack Diagnostics
Local rack diagnostics are accessible for the 140CRP31200, 140 NOC 771 ••, and
140 NOE 771 •• modules within the standard system bits (%SW180 to %SW339).
Ethernet Remote I/O Drop Diagnostics
Ethernet remote I/O drop diagnostics are accessible for the entire drop within system bits and words in the PLC (%S, %SW). Each drop is animated with a health bit display of the health bit status for:
• a drop node
• a module in a remote drop
The Quantum PLC on the local rack monitors remote I/O drops and module health. The 140CRA31200 or BMXCRA312•0 adapter module on the remote I/O drop transmits detected errors in drop modules to the Quantum PLC via
implicit exchanges, page 81 . The detected errors are stored in the global diagnostic
buffers of the PLC and in the diagnostic buffer of the individual drop module.
The Quantum PLC or the 140CRP31200 module on the local rack updates the detected error buffers. Health bits are updated in the PLC only if the adapter of the concerned drop communicates with the 140CRP31200 module on the local rack.
If these modules cannot communicate, the concerned health bits are set to 0.
S1A48978.14
71
Remote I/O Modules
System Bits/Words
%S117
%SW101
%SW108
%SW109
%SW152 ... %SW153
%SW172 ... %SW175
%SW176 ... %SW179
%SW180 ... %SW181
%SW182 ... %SW183
%SW641 ... %SW702
72
System Bits and Words
This table describes new or modified system bits and words that represent detected errors:
Symbol
EIOERR
EIO_CCOTF_COUNT
FORCED_DISCRETE_COUNT
FORCED_ANALOG_COUNT
EIO_DROP_ERROR
EIO_CONNECT_STATUS
SDBY_EIO_CONNECT_STATUS
IOHEALTHij
(i = 1 ... 32, j = 1 ... 5)
EIO_MOD_HEALTH
Description detected remote I/O error on the Ethernet I/O network
EIO CCOTF counting status register forced bit counting status register forced bit counting status register detected Ethernet remote I/O drop status
The bit is set to 0 if at least one I/O module in the drop as a detected error.
The bit is set to 1 if all modules are operating properly.
• %SW152.0: drop #1
• %SW152.1: drop #2
• ........
• %SW153.14: drop #31
Ethernet I/O communication health status for drops in standalone and primary systems
Ethernet I/O communication health status for drops in standby systems health bits of the PLC modules (including Hot Standby and
Safety Hot Standby systems)
Ethernet remote I/O module health bit status
NOTE: Refer to Quantum-Specific System Words section (see EcoStruxure ™
Control Expert, System Bits and Words, Reference Manual) for a detailed explanation.
Viewing Diagnostics in Control Expert
The bus editor in Control Expert uses color animation to display the status of each drop, rack, or module on the EIO Bus . The slot number of the drop/rack/module appears in red when a detected error is associated with that slot. For a module, the red display indicates the module is missing, inoperable, or improperly configured.
Drop
140 CRA
Status drop (d) rack (r), drop (d)
Language
Object
%SWi.j
%SWi i j
BMX CRA module (m), rack
(r), drop (d) rack (r), drop (d) module (m), rack
(r), drop (d)
%SWi.j
%SWi
%SWi.j
152 + [(d-1)/16]
641 + [(d-1)*2] +
(r-1)
641 + [(d-1)*2] +
(r-1)
641 + [(d-1)*2] + r
641 + [(d-1)*2] + r
(d-1)/16
16-m
15-m
NOTE: Remember that the 16 slots have different numbering schemes:
• 140CRA31200 drop: slots 1...16
• BMXCRA312•0 drop: slots 0...15
NOTE: Remember that the rack numbering scheme is also different:
• 140CRA31200 drop: 1 or 2
• BMXCRA312•0 drop: 0 or 1
S1A48978.14
Remote I/O Modules
Device Data Types for the Remote I/O Modules
Device Data Types
The DDT structures for these remote I/O modules are described elsewhere:
• 140CRP31200 head module (local rack)
• 140CRA31200 or BMXCRA312•0 adapter (remote drop)
These DDTs are available in the application. Refer to the
Derived Data Types section, page 48 .
The DDT diagnostics data is mapped to default local variables. The data is updated every MAST cycle.
Diagnostics Available through Modbus/TCP
Modbus Diagnostic Codes
Supported Diagnostic Codes
Modbus function code 3 provides access to a variety of diagnostic functions, including basic network diagnostics, Ethernet port diagnostics, and Modbus port
502 diagnostics.
To access the function code 3 diagnostics from the local device, set the unit ID to
100.
The following modules support these Modbus diagnostic codes.
• Quantum remote I/O head module (140CRP31200)
• Quantum distributed I/O head module (140NOC78000)
• Quantum control head module (140NOC78100)
• Quantum remote I/O adapter module (140CRA31200)
• M340 distributed I/O head module (BMXNOC0401)
• M340 remote I/O adapter module (BMXCRA31200)
• Quantum IEC 61850 module (140NOP85000)
• M580 communications module (BMENOC03•1)
• M580 communications module (BMENOP0300)
Modbus Function Code 3: Basic Network Diagnostics
Basic network diagnostics start at address 40001(decimal) as described in the following table.
Starting
Address
(Decimal)
40001
Length
(Words)
2
40003 1
Register Byte Order
MS BYTE LS BYTE
MS Byte
00
Byte 02
MS Byte
Byte 01
40004
40005
40006
40008
1
1
2
2
MS Byte
MS Byte
IP 1
IP 3
SM 1
LS Byte
LS Byte
03
LS Byte
LS Byte
IP 2
IP 4
SM 2
Comments
Basic network diagnostic validity
Communication global status
Supported communication services
Status of communication services
IP address (IP1.IP2.IP3.IP4)
Subnet mask (SM1.SM2.SM3.SM4)
S1A48978.14
73
Remote I/O Modules
74
Starting
Address
(Decimal)
Length
(Words)
Register Byte Order
MS BYTE LS BYTE
40010
40012
40015
2
3
3
SM 3
GW 1
GW 3
MAC 1
MAC 3
MAC 5
MS Byte
00
02
04
SM 4
GW 2
GW 4
MAC 2
MAC 4
MAC 6
01
40018
40020
40022
40023
40024
40026
40028
40030
40038
2
2
1
1
2
2
2
8
2
03
LS Byte
05
C01
C03
C01
C03
LS Byte
LS Byte
C01
C03
C01
C03
C01
C03
Char 2
Char 4
Char 6
Char 8
Char 10
Char 12
Char 14
Char 16
Byte 01
C00
C02
C00
C02
MS Byte
MS Byte
C00
C02
C00
C02
C00
C02
Char 1
Char 3
Char 5
Char 7
Char 9
Char 11
Char 13
Char 15
MS Byte
00
Byte 02 LS Byte
03
Comments
Default gateway (GW1.GW2.GW3.GW4)
MAC address (MAC1:MAC2:MAC3:MAC4:MAC5:
MAC6.
Ether frame format capability / configuration / operational
Ethernet receive frames OK
Ethernet transmit frames OK
Number of open client connections
Number of open server connections
Number of Modbus detected error messages sent
Number of Modbus messages sent
Number of Modbus messages received
Device name
IP assignment mode capability / operational
Example: Reading Basic Network Diagnostics with Modbus Function Code 3
Here is an example of how to read registers 40018 and 40019, the Ethernet receive frames OK count registers. The request contains 7 bytes. The starting address, shown as a hex value in byte 2 below, is calculated as follows:
40018 – 40001 = 17 dec = (11 hex)
The number of registers to be diagnosed (2 hex) is shown in byte 4:
Byte
Number
0
1
Value
Function code = 03 (hex)
Starting Address Hi = 00 (hex)
S1A48978.14
S1A48978.14
Remote I/O Modules
5
6
3
4
Byte
Number
2
Value
Starting Address Low = 11 (hex)
No. of Registers Hi = 00 (hex)
No. of Registers Low = 2 (hex)
CRC high byte (inserted by the Modbus sending application)
CRC low byte (inserted by the Modbus sending application)
The normal response is returned in 8 bytes. In this example, the expected response is 14229 hex; this value is shown in bytes 2 through 5 of the response:
6
7
3
4
5
1
2
Byte Number
0
Value
Function code = 03 (hex)
Byte count = 4 (hex)
1 st register data, high byte = 00 (hex)
1 st register data, low byte = 01 (01 hex)
2 nd register data, high byte = 42 (hex)
2 nd register data, low byte = 29 (hex)
CRC high byte
CRC low byte
1
2
3
Byte Number
0
Value
Original function code + 80 hex (= 83 hex)
Detected error code
CRC high byte
CRC low byte
For more information on Modbus function code 3 and other function codes, refer to the Modicon Modbus Protocol Reference Guide (PI-MBUS-300).
Modbus Function Code 3: Ethernet Internal Port Diagnostic
Data
Internal port diagnostics start at address 40040 (decimal) as described in the following table.
40043
40044
40045
40046
40047
40048
Starting
Address
(Decimal)
40040
40041
40042
1
1
1
1
1
3
1
1
1
Length
(Words)
Register Byte Order Comments
MS
BYTE
LS
BYTE
MS Byte LS Byte
MS Byte LS Byte
MS Byte LS Byte
Internal port Diagnostics Data Validity
Internal port Logical/Physical Port Number
Internal port Ethernet Control Capability
MS Byte LS Byte
MS Byte LS Byte
MS Byte LS Byte
MS Byte LS Byte
MS Byte LS Byte
MAC 1
MAC 3
MAC 2
MAC 4
Internal port Link Speed Capability
Internal port Ethernet Control Configuration
Internal port Link Speed Configuration
Internal port Ethernet Control Operational
Internal port Link Speed Operational
MAC Address (MAC1:MAC2:MAC3:MAC4:MAC5:
MAC6)
75
Remote I/O Modules
76
Starting
Address
(Decimal)
40051
40053
40055
40057
40059
40061
40063
40065
40067
40069
40071
40073
40075
40077
40079
40081
40083
Length
(Words)
Register Byte Order Comments
MS
BYTE
LS
BYTE
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
MSB
C00
C02
MSB
C00
C02
MAC 5
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MAC 6
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
Internal port Media Counters Data Validity
Internal port Num Frames Transmitted OK
Internal port Num Frames Received OK
Internal port Num Ether Collisions
Internal port Carrier Sense Errors detected
Internal port Num Ether Excessive Collisions
Internal port CRC Errors detected
Internal port FCS Errors detected
Internal port Alignment Errors detected
Internal port Num Internal MAC Tx Errors detected
Internal port Late Collisions
Internal port Num Internal MAC Rx Errors detected
Internal port Multiple Collisions
Internal port Single Collisions
Internal port Deferred Transmissions
Internal port Frames Too Long
Internal port Frames Too Short
S1A48978.14
Remote I/O Modules
Starting
Address
(Decimal)
40085
40087
40088
40089
...
40118
40119
40120
40121
40123
40125
40127
40129
401331
40133
40135
40137
40139
40141
1
32
1
2
Length
(Words)
Register Byte Order Comments
MS
BYTE
LS
BYTE
2 Internal port SQE Test Error detected
2
2
2
2
2
2
2
2
2
2
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C02
MSB
C00
C01
C02 LSB C03
MS Byte LS Byte
IL char64 IL char63
IL char62 IL char61
...
...
IL char04 IL char03
IL char02 IL char01
MS Byte LS Byte
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
C01
LSB C03
Internal port Interface Label Length
Internal port Interface Label characters
Internal port Interface Counters Diagnostic Validity
Internal port Num Octets Received
Internal port Num Unicast Packets Received
Internal port Num Non Unicast Packets Received
Internal port Num Inbound Packets Discarded
Internal port Num Inbound Packets Error detected
Internal port Num Inbound Packets Unknown
Internal port Num Octets Sent
Internal port Num Unicast Packets Sent
Internal port Num Non Unicast Packets Sent
Internal port Num Outbound Packets Discarded
Internal port Num Outbound Packets Error detected
S1A48978.14
77
Remote I/O Modules
78
Modbus Function Code 3: Ethernet Port 1 Diagnostic Data
Port 1 diagnostics start at address 40143 (decimal). As described in the following table, port 1 diagnostic data fields are the same as for the internal port, with the appropriate starting address offset.
Starting
Address
Length Register Byte Order
40143
...
40244
1
...
2
MS BYTE LS BYTE
MS Byte LS Byte
...
...
MSB C00 C01
C02 LSB C02
Comments
Port 1 Port Diagnostics Data Validity
...
Port 1 Num Outbound Packets Error detected
Modbus Function Code 3: Ethernet Backplane Port Diagnostic
Data
Backplane port diagnostics start at address 40246 (decimal). As described in the following table, backplane port diagnostic data fields are the same as for the internal port and port 1, with the appropriate starting address offset.
Starting
Address
Length Register Byte Order
40246
...
40347
1
...
2
MS BYTE LS BYTE
MS Byte LS Byte
...
...
MSB C00 C01
C02 LSB C02
Comments
Backplane Port Diagnostics Data Validity
...
Backplane Port Num Outbound Packets Error detected
Modbus Function Code 3: Ethernet Port 3 Diagnostic Data
Port 3 diagnostics start at address 40349 (decimal). As described in the following table, port 3 diagnostic data fields are the same as for the internal port and ports 1 and 2, with the appropriate starting address offset.
Starting
Address
Length Register Byte Order
40349 1
MS BYTE LS BYTE
MS Byte LS Byte
...
40450
...
2
...
...
MSB C00 C01
C02 LSB C03
Comments
Port 3 Port Diagnostics Data Validity
...
Port 3 Num Outbound Packets Error detected
Modbus Function Code 3: Ethernet Port 4 Diagnostic Data
Port 4 diagnostics start at address 40452 (decimal).As described in the following table, port 4 diagnostic data fields are the same as for the internal port and ports
1-3, with the appropriate starting address offset.
Starting
Address
Length Register Byte Order
40452
...
40553
1
...
2
MS BYTE LS BYTE
MS Byte LS Byte
...
...
MSB C00 C01
C02 LSB C03
Comments
Port 4 Port Diagnostics Data Validity
...
Port 4 Num Outbound Packets Error detected
S1A48978.14
S1A48978.14
Remote I/O Modules
Ethernet Port Not Present
If an Ethernet port is not physically present on the device, the relevant Modbus registers will return data = 0.
Modbus Function Code 3: Modbus TCP Port 502 Diagnostic
Data
Modbus TCP port 502 diagnostics start at address 40555 (decimal) as described in the following table.
Starting
Address
40555
40557
40558
40559
40561
40563
1
2
Length
Register Byte Order
2
1
MS BYTE LS BYTE
MS Byte
00
Byte 01
Byte 02
MS Byte
LS Byte
03
LS Byte
2
1
MS Byte
MSB C00
C02
MSB C00
C02
MS Byte
LS Byte
C01
LSB C03
C01
LSB C03
LS Byte
40564
40565
40566
40567
40568
40570
40571
40572
40573
40575
40576
40578
...
40663
40665
40666
40668
1
1
1
1
2
1
1
1
2
1
2
2
...
2
1
2
1
Comments
Modbus TCP/Port 502
Diagnostic Data Validity
Port 502 Status
Num Open Connections
Num MB Messages Sent
Num MB Messages Received
MS Byte
MS Byte
MS Byte
MS Byte
MSB C00
C02
MS Byte
MS Byte
MS Byte
LS Byte
LS Byte
LS Byte
LS Byte
C01
LSB C03
LS Byte
LS Byte
LS Byte
Num MB Open Client
Connections
Num MB Open Server
Connections
Max Num Connections
Max Num Client Connections
Max Num Server Connections
Num MB Detected Error
Messages Sent
MSB - IP1 IP2
IP3 LSB - IP4
MS Byte LS Byte
MSB - IP1 IP2
IP3
MS Byte
LSB - IP4
LS Byte
...
MSB - IP1
IP3
MS Byte
...
IP2
LSB - IP4
LS Byte
Num Attempts to Open
Unauthorized Connection 1
Remote IP Address 2
Num Attempts to Open
Unauthorized Connection 2
...
Remote IP Address 31
MSB - IP1 IP2
IP3 LSB - IP4
MS Byte LS Byte
Num Open Priority Connections
Max Num Priority Connections
Num Entries in Unauthorized
Table
Remote IP Address 1 Connection 1
Num Attempts to Open
Unauthorized Connection 31
Remote IP Address 32
Num Attempts to Open
Unauthorized Connection 32
Connection 2
Connection 31
Connection 32
79
Remote I/O Modules
80
Modbus Function Code 3: Modbus TCP Port 502 Connection
Table Data
Modbus TCP port 502 connection table data starts at address 40669 (decimal) as described in the following table.
Starting
Address
40669
40670
1
1
Length
Register Byte Order
MS BYTE LS BYTE
MS Byte LS Byte
MS Byte LS Byte
40671
40672
40673
40675
1
1
2
1
MS Byte
MS Byte
IP1
IP3
MS Byte
LS Byte
LS Byte
IP2
IP4
LS Byte
Comments
Connection Table Validity
Number of Entries
Starting Entry Index
Connection 1 Index
Connection 1 Remote IP
Address
40676
40677
40678
40679
40680
40681
40683
1
1
1
1
1
2
1
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
IP1
IP3
MS Byte
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
IP2
IP4
LS Byte
Connection 1
Connection 1 Remote Port
Number
Connection 1 Local Port
Number
Num MB Messages Sent on
Connection 1
Num MB Messages Received on Connection 1
Num MB Detected Error
Messages Sent on Connection
1
Connection 2 Index
Connection 2 Remote IP
Address
Connection 2
40684
40685
40686
40687
...
41168
41169
41171
1
1
1
1
...
1
2
1
MS Byte
MS Byte
MS Byte
MS Byte
...
MS Byte
IP1
IP3
MS Byte
LS Byte
LS Byte
LS Byte
LS Byte
...
LS Byte
IP2
IP4
LS Byte
Connection 2 Remote Port
Number
Connection 2 Local Port
Number
Num MB Messages Sent on
Connection 2
Num MB Messages Received on Connection 2
Num MB Detected Error
Messages Sent on Connection
2
...
Connection 63 Index
Connection 63 Remote IP
Address
Connection 63*
41172
41173
41174
41175
41176
41177
1
1
1
1
1
2
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
IP1
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
IP2
Connection 63 Remote Port
Number
Connection 63 Local Port
Number
Num MB Messages Sent on
Connection 63
Num MB Messages Received on Connection 63
Num MB Detected Error
Messages Sent on Connection
63
Connection 64 Index
Connection 64 Remote IP
Address
Connection 64*
S1A48978.14
Remote I/O Modules
Starting
Address
Length
Register Byte Order Comments
MS BYTE LS BYTE
IP3 IP4
MS Byte LS Byte 415179
41180
41181
41182
1
1
1
1
MS Byte
MS Byte
MS Byte
LS Byte
LS Byte
LS Byte
Connection 64 Remote Port
Number
Connection 64 Local Port
Number
Num MB Messages Sent on
Connection 64
Num MB Messages Received on Connection 64
41183 1 MS Byte LS Byte Num MB Detected Error
Messages Sent on Connection
64
*140 CRA 312 10 and BMX CRA 312 •0 RIO adapter modules support a maximum of 8 connections.
Diagnostics Available through EtherNet/IP CIP Objects
Introduction
Quantum Ethernet I/O applications use CIP within a producer/consumer model to provide communication services in an industrial environment. This section describes the available CIP objects for Quantum EIO modules.
About CIP Objects
Overview
The Ethernet communication module can access CIP data and services located in connected devices. The CIP objects and their content depend on the design of each device.
CIP object data and content are exposed—and accessed—hierarchically in the following nested levels:
Identity Object
NOTE: You can use explicit messaging to access these items:
• Access a collection of instance attributes by including only the class and instance values for the object in the explicit message.
• Access a single attribute by adding a specific attribute value to the explicit message with the class and instance values for the object.
This chapter describes the CIP objects that the Ethernet communication module exposes to remote devices.
Overview
The Identity object presents the instances, attributes and services described below.
S1A48978.14
81
Remote I/O Modules
82
Class ID
01
Instance IDs
The Identity object presents two instances:
• 0: class
• 1: instance
Attributes
Identity object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID Description
01
02
X = supported
— = not supported
Revision
Max Instance
GET
X
X
SET
—
—
Instance ID = 1 (instance attributes):
Description Attribute ID hex dec
01
02
01
02
03
04
03
04
05 05
06
07
18
06
07
24
X = supported
— = not supported
Vendor ID
Device Type
Product Code
Revision
Major
Minor
Status bit 2:
0x01=the module is configured bits 4-7:
0x03=no I/O connections established
0x06=at least 1 I/O connection in run mode
0x07=at least 1 I/O connection established, all in IDLE mode
Serial Number
Product Name
Modbus Identity
Type GET
UINT
UINT
UINT
STRUCT
USINT
USINT
Word
X
X
X
X
X
UDINT
STRING
STRUCT
X
X
X
SET
—
—
—
—
—
—
—
—
Services
The Identity object performs the following services upon the listed object types:
S1A48978.14
Service ID hex dec
01 01
Description
Get_Attributes_All
Class Instance
X X
X X
Remote I/O Modules
Notes
Returns:
• all class attributes (instance = 0)
• instance attributes 1 to 7 (instance = 1)
Returns the value of the specified attribute.
0E 14
X = supported
— = not supported
Get_Attribute_Single
Assembly Object
Overview
The Assembly object consists of the attributes and services described below.
NOTE: You can send an explicit message to the Assembly object only when no other connections have been established that read from or write to this object. For example, you can send an explicit message to the Assembly object if a local slave instance is enabled, but no other module is scanning that local slave.
Class ID
04
Instance IDs
The Assembly object presents the following instance identifiers:
• 0: class
• 101, 102, 111, 112, 121, 122: instance
Attributes
The Assembly object consists of the following attributes:
Instance ID = 0 (class attributes):
Attribute ID
01
02
03
X = supported
— = not supported
Description
Revision
Max Instance
Number of Instances
Instance attributes:
GET
X
X
X
SET
—
—
—
S1A48978.14
83
Remote I/O Modules
Instance ID
101
102
111
112
121
122
X = supported
— = not supported
Attribute ID
03
Description
Local slave 1: T->O input data
Local slave 1: O>T
Local slave 2: T->O input data
Local slave 2: O>T
Local slave 3: T->O input data
Local slave 3: O>T
Type
Array of BYTE
Array of BYTE
Array of BYTE
Array of BYTE
Array of BYTE
Array of BYTE
X
X
X
X
X
GET
X
SET
—
X
—
X
—
X
Services
The CIP Assembly object performs these services upon the listed object types:
Service ID hex
0E dec
14
10 16
Description
Get_Attribute_Single
Set_Attribute_Single 1
Class
X
—
Instance
X
X
Notes
Returns the value of the specified attribute
Returns these values:
0E=attribute not settable: assembly is not o->T type
0F=permission denied: assembly is being used by an active connection
13=config too small: the Set_Attribute_Single command contains partial data
15=data too big: the Set_Attribute_Single command contains too much data
X = supported
— = not supported
1. When valid, the size of the data written to the Assembly object using the Set_Attribute_Single service equals the size of the Assembly object as configured in the target module.
Connection Manager Object
Overview
The Connection Manager object presents the instances, attributes and services described below.
Class ID
06
Instance IDs
The Connection Manager object presents two instance values:
• 0: class
• 1: instance
Attributes
Connection Manager object attributes are associated with each instance, as follows:
84 S1A48978.14
S1A48978.14
Remote I/O Modules
Instance ID = 0 (class attributes):
Attribute ID Description
01
02
X = supported
— = not supported
Revision
Max Instance
Instance ID = 1 (instance attributes):
Attribute ID hex dec
01 01
02
03
04
05
06
07
08
02
03
04
05
06
07
08
Description
Open Requests
Open Format
Rejects
Open Resource
Rejects
Open Other Rejects
Close Requests
Close Format
Requests
Close Other
Requests
Connection
Timeouts
Type
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
09
0B
0C
0D
09
11
12
13
X = supported
— = not supported
Connection Entry
List
CPU_Utilization
STRUCT
UINT
UDINT MaxBuffSize
BufSize Remaining UDINT
X
X
X
X
GET
X
X
SET
—
—
GET SET Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
—
—
—
—
Number of Forward Open service requests received
Number of Forward Open service requests that were rejected due to bad format
Number of Forward Open service requests that were rejected due to lack of resources
Number of Forward Open service requests that were rejected for reasons other than bad format or lack of resources
Number of Forward
Close service requests received
Number of Forward
Close service requests that were rejected due to bad format
Number of Forward
Close service requests that were rejected for reasons other than bad format
Total number of connection timeouts that occurred in connections controlled by this connections manager
0 (Unsupported optional item
0 (Unsupported optional item
0 (Unsupported optional item
0 (Unsupported optional item
Services
The Connection Manager object performs the following services on the listed object types:
85
Remote I/O Modules
Service ID hex dec
01 01
0E 14
X = supported
— = not supported
Description
Get_Attributes_All
Get_Attribute_Single
Class Instance Notes
X
X
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
Quality Of Service (QoS) Object
Overview
The QoS object implements Differentiated Services Code Point (DSCP or
DiffServe ) values for the purpose of providing a method of prioritizing Ethernet messages. The QoS object presents the instances, attributes and services described below.
Class ID
48 (hex), 72 (decimal)
Instance IDs
The QoS object presents two instance values:
• 0: class
• 1: instance
Attributes
The QoS object consists of the following attributes:
Instance ID = 0 (class attributes):
Attribute ID
01
02
X = supported
— = not supported
Description
Revision
Max Instance
Instance ID = 1 (instance attributes):
Attribute ID
04
Description
DSCP Urgent
Type
USINT
GET
X
SET
X
05
06
07
DSCP Scheduled
DSCP High
DSCP Low
USINT
USINT
USINT
X
X
X
X
X
X
GET
X
X
SET
—
—
Value
For CIP transport class
0/1 Urgent priority messages, default value
= 55.
For CIP transport class
0/1 Urgent priority messages, default value
= 47.
For CIP transport class
0/1 Urgent priority messages, default value
= 43.
For CIP transport class
0/1 Urgent priority messages, default value
= 31.
86 S1A48978.14
Remote I/O Modules
Attribute ID
08
Description
DSCP Explicit
Type
USINT
GET
X
SET
X
Value
For CIP explicit messages (transport class 2/3 and UCMM), default value = 27.
X = supported
— = not supported
NOTE: A change in the instance attribute value takes effect on device re-start, for configurations made from flash memory.
Services
The QoS object performs the following services upon the listed object types:
Service ID hex dec
0E 14
10 16
X = supported
— = not supported
Description
Get_Attribute_Single
Set_Attribute_Single
Class
X
—
Instance
X
X
TCP/IP Interface Object
Overview
The TCP/IP interface object presents the instances (per network), attributes and services described below.
Class ID
F5 (hex), 245 (decimal)
Instance IDs
The TCP/IP interface object presents 2 instance values:
• 0: class
• 1: instance
Attributes
TCP/IP interface object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID Description
01
02
X = supported
— = not supported
Revision
Max Instance
GET
X
X
SET
—
—
Instance ID = 1 (instance attributes):
S1A48978.14
87
Remote I/O Modules
Attribute ID
01
02
Description
Status
Configuration
Capability
Type
DWORD
DWORD
03
04
Configuration Control DWORD
Physical Link Object STRUCT
Path Size
Path
UINT
Padded
EPATH
Interface Configuration STRUCT 05
IP Address
Network Mask
Gateway Address
06
X = supported
— = not supported
Name Server
Name Server 2
Domain Name
Host Name
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
STRING
GET
X
X
SET
—
—
X X
Value
0x01
0x01 = from BootP
0x11 = from flash
0x00 = other
0x01 = out-of-box default
X —
X
X
X
—
0x00 = out-of-box default
Services
The TCP/IP interface object performs the following services upon the listed object types:
Service ID hex dec
01 01
Description Class Instance Notes
0E
10
14
16
Get_Attributes_All
Get_Attribute_Single
Set_Attribute_Single 1
X
X
—
X
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
Sets the value of the specified attribute.
X = supported
— = not supported
1. The Set_Attribute_Single service can execute only when these preconditions are satisfied:
• Configure the Ethernet communication module to obtain its IP address from flash memory.
• Confirm that the PLC is in stop mode.
Ethernet Link Object
88
Overview
The Ethernet Link object consists of the instances, attributes and services described below.
Class ID
F6 (hex), 246 (decimal)
S1A48978.14
Instance IDs
The Ethernet Link object presents the following instance values:
• 0: class
• 1: port 1
• 2: port 2
• 3: port 3
• 4: port 4
Remote I/O Modules
Attributes
The Ethernet Link object presents the following attributes:
Instance ID = 0 (class attributes):
Attribute ID Description
01
02
03
X = supported
— = not supported
Revision
Max Instance
Number of Instances
Description
Instance ID = 1 (instance attributes):
Type GET SET Value
GET
X
X
X
SET
—
—
—
Attribute ID hex
01 dec
01 Interface Speed UDINT X —
02 02 Interface Flags DWORD X —
Valid values include:
0, 10000000, 100000000
Bit 0: link status
0 = Inactive
1 = Active
Bit 1: duplex mode
0 = half duplex
1 = full duplex
Bits 2—4: negotiation status
3 = successfully negotiated speed and duplex
4 = forced speed and link
Bit 5: manual setting requires reset
0 = automatic
1 = device need reset
Bit 6: local hardware detected error
0 = no event
1 = event detected module MAC address 03
04
03
04
Physical Address
Interface Counters
In octets
In Ucast Packets
In NUcast Packets
ARRAY of 6
USINT
STRUCT
UDINT
UDINT
UDINT
X
X
—
— octets received on the interface unicast packets received on the interface non-unicast packets received on the interface
S1A48978.14
89
Remote I/O Modules
Description Attribute ID hex dec
05 05
In Discards
In Errors
In Unknown Protos
Out Octets
Out Ucast Packets
Out NUcast Packets
Out Discards
Out Errors
Media Counters
Alignment Errors
FCS Errors
Single Collisions
Multiple Collisions
SQE Test Errors
Deferred Transmissions
Late Collisions
06 06
Excessive Collisions
MAC Transmit Errors
Carrier Sense Errors
Frame Too Long
MAC Receive Errors
Interface Control
Control Bits
90
Forced Interface Speed
Type GET SET Value
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
STRUCT
UDINT
UDINT
UDINT
X —
UDINT
UDINT
UDINT
UDINT
UDINT
STRUCT
WORD
UINT
X X inbound packets received on the interface, but discarded inbound packets with detected errors (does not include in discards) inbound packets with unknown protocol octets sent on the interface unicast packets sent on the interface non-unicast packets sent on the interface outbound packets discarded outbound packets with detected errors frames that are not an integral number of octets in length bad CRC — frames received do not pass the
FCS check successfully transmitted frames that experienced exactly 1 collision successfully transmitted frames that experienced more than 1 collision number of times the detected SQE test error is generated frames for which first transmission attempt is delayed because the medium is busy number of times a collision is detected later than 512 bit times into the transmission of a packet frames that do not transmit due to excessive collisions frames that do not transmit due to a detected internal MAC sublayer transmit error times that the carrier sense condition was lost or not asserted when attempting to transmit a frame frames received that exceed the maximum permitted frame size frames not received on an interface due to a detected internal MAC sublayer receive error
API of the connection
Bit 0: Auto-negotiation
0 = disabled
1 = enabled
Note: When auto-negotiation is enabled,
0x0C (object state conflict) is returned when attempting to set either:
• forced interface speed or
• forced duplex mode
Bit 1: forced duplex mode (if auto-negotiation bit = 0)
0 = half duplex
1 = full duplex
Valid values include:
S1A48978.14
Attribute ID hex dec
Description Type GET SET Value
Remote I/O Modules
10 16 Interface Label SHORT_
STRING
X —
10000000, 100000000
Note: Attempting to set any other value returns the detected error 0x09 (invalid attribute value)
A fixed textual string identifying the interface, that should include ‘internal’ for internal interfaces. Maximum number of characters is
64.
X = supported
— = not supported
Services
The Ethernet Link object performs the following services upon the listed object types:
Service ID hex
01
10
0E
4C
X = supported
76
— = not supported dec
01
16
14
Description
Get_Attributes_All
Set_Attribute_Single
Get_Attribute_Single
Get_and_Clear
Class
X
—
X
—
Instance
X
X
X
X
EtherNet/IP Interface Diagnostics Object
Overview
The EtherNet/IP Interface Diagnostics object presents the instances, attributes and services described below.
Class ID
350 (hex), 848 (decimal)
Instance IDs
The EtherNet/IP Interface object presents two instance values:
• 0: class
• 1: instance
Attributes
EtherNet/IP Interface Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
S1A48978.14
91
Remote I/O Modules
Attribute ID Description
01
02
X = supported
— = not supported
Revision
Max Instance
GET
X
X
SET
—
—
Attribute ID
01
02
03
04
Instance ID = 1 (instance attributes):
Description
Protocols Supported
Connection Diagnostics
Max CIP IO Connections opened
Type
UINT
STRUCT
UINT
Current CIP IO Connections UINT
Max CIP Explicit
Connections opened
UINT
Current CIP Explicit
Connections
CIP Connections Opening
Errors
UINT
UINT
CIP Connections Timeout
Errors
Max EIP TCP Connections opened
UINT
UINT
UINT Current EIP TCP
Connections
IO Messaging Diagnostics
IO Production Counter
IO Consumption Counter
STRUCT
UDINT
UDINT
GET
X
X
X
SET
—
—
X
IO Production Send Errors
Counter
IO Consumption Receive
Errors Counter
Explicit Messaging
Diagnostics
Class 3 Msg Send Counter
UINT
UINT
STRUCT
UDINT
X X
Value
Number of Class 1 connections opened since the last reset
Number of Class 1 connections currently opened
Number of Class 3 connections opened since the last reset
Number of Class 3 connections currently opened
Increments each time a Forward Open is not successful (Originator and Target)
Increments when a connection times out (Originator and Target)
Number of TCP connections (used for EIP, as client or server) opened since the last reset
Number of TCP connections (used for EIP, as client or server) currently open
Increments each time a Class 0/1 message is sent
Increments each time a Class 0/1 message is received
Increments each time a Class 0/1 message is not sent
Increments each time a consumption is received with a detected error
X = supported
— = not supported
Class 3 Msg Receive
Counter
UCMM Msg Receive
Counter
UCMM Msg Receive
Counter
UDINT
UDINT
UDINT
Increments each time a Class 3 message is sent
(client and server)
Increments each time a Class 3 message is received
(client and server)
Increments each time a UCMM message is sent
(client and server)
Increments each time a UCMM message is received
(client and server)
Services
The EtherNet/IP Interface Diagnostics object performs the following services upon the listed object types:
92 S1A48978.14
Service ID hex dec
01 01
0E
4C
14
76
X = supported
— = not supported
Description
Get_Attributes_All
Get_Attribute_Single
Get_and_Clear
Class Instance
X
—
—
X
X
X
Remote I/O Modules
Notes
Returns the value of all attributes.
Returns the value of the specified attribute.
Returns and clears the values of all instance attributes.
EtherNet/IP IO Scanner Diagnostics Object
Overview
The EtherNet/IP IO Scanner Diagnostics object presents the instances, attributes and services described below.
Class ID
351 (hex), 849 (decimal)
Instance IDs
The EtherNet/IP IO Scanner Diagnostics object presents two instances:
• 0: class
• 1: instance
Attributes
EtherNet/IP IO Scanner Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
02
X = supported
— = not supported
Description
Revision
Max Instance
GET
X
X
SET
—
—
Instance ID = 1 (instance attributes):
Attribute ID
01
Description
IO Status Table
Size
Status
X = supported
— = not supported
Type
STRUCT
UINT
ARRAY of
UNINT
GET
X
SET
—
Services
The EtherNet/IP IO Scanner Diagnostics object performs the following services upon the listed object types:
S1A48978.14
93
Remote I/O Modules
Service ID hex dec
01 01
0E 14
X = supported
— = not supported
Description
Get_Attributes_All
Get_Attribute_Single
Class Instance
X
X
X
X
Notes
Returns the value of all attributes.
Returns the value of the specified attribute.
IO Connection Diagnostics Object
Overview
The IO Connection Diagnostics object presents the instances, attributes and services described below.
Class ID
352 (hex), 850 (decimal)
Instance IDs
The IO Connection Diagnostics object presents two instance values:
• 0: class
• 1...256: instance (The instance number is the connection number in the configuration.)
Attribute ID
01
Attributes
IO Connection Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
02
X = supported
— = not supported
Description
Revision
Max Instance
GET
X
X
SET
—
—
Instance ID = 1 to 256 (instance attributes):
Description
IO Communication Diagnostics
IO Production Counter
IO Consumption Counter
Type
STRUCT
UDINT
UDINT
IO Production Send Errors Counter UINT
UINT IO Consumption Receive Errors
Counter
CIP Connection Timeout Errors
CIP Connection Opening Errors
UINT
UINT
GET
X
SET
X
CIP Connection State
CIP Last Error General Status
UINT
UINT
Value
Increments at each production
Increments at each consumption
Increments each time a production is not sent
Increments each time a consumption is received with a detected error
Increments when a connection times out
Increments each time a connection is unable to open
State of the Connection Bit
General status of the last error detected on the connection
94 S1A48978.14
Attribute ID
02
Description
CIP Last Error Extended Status
Input Communication Status
Type
UINT
UINT
Output Communication Status UINT
Connection Diagnostics
Production Connection ID
Consumption Connection ID
Production RPI
STRUCT
UDINT
UDINT
UDINT
Production API
Consumption RPI
Consumption Connection
Parameters
Local IP
Local UDP Port
Remote IP
Remote UDP Port
Production Multicast IP
UDINT
UDINT
Consumption API UDINT
Production Connection Parameters UDINT
UDINT
UDINT
UINT
UDINT
UINT
UDINT
Consumption Multicast IP
Protocols Supported
UDINT
UDINT
Remote I/O Modules
GET SET Value
Extended status of the last error detected on the connection
Communication status of the inputs (see table, below)
Communication status of the outputs (see table, below)
X X
Connection ID for production
Connection ID for consumption
RPI for production
API for production
RPI for consumption
API for consumption
Connection parameters for production
Connection parameters for consumption
—
—
—
—
Multicast IP used for production (or 0)
Multicast IP used for consumption (or 0)
Protocol supported on the connection:
1 = EtherNet/IP
X = supported
— = not supported
The following values describe the structure of the instance attributes: CIP
Connection State , Input Communication Status , and Output Communication
Status :
Bit Number
15...3
2
1
0
Description
Reserved
Idle
Consumption inhibited
Production inhibited
Values
0
0 = no idle notification
1 = idle notification
0 = consumption started
1 = no consumption
0 = production started
1 = no production
Service ID hex dec
01 01
0E 14
S1A48978.14
Description
Services
The EtherNet/IP Interface Diagnostics object performs the following services upon the listed object types:
Class Instance Notes
Get_Attributes_All
Get_Attribute_Single
X
—
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
95
Remote I/O Modules
Service ID hex dec
4C 76
X = supported
— = not supported
Description
Get_and_Clear
Class Instance
— X
Notes
Returns and clears the values of all instance attributes.
EtherNet/IP Explicit Connection Diagnostics Object
Overview
The EtherNet/IP Explicit Connection Diagnostics object presents the instances, attributes and services described below.
Class ID
353 (hex), 851 (decimal)
Instance IDs
The EtherNet/IP Explicit Connection Diagnostics object presents two instance values:
• 0: class
• 1...
N : instance ( N = maximum concurrent number of explicit connections)
Attributes
EtherNet/IP Explicit Connection Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID hex
01
02
X = supported
— = not supported
Description
Revision
Max Instance
Value
1
0...N
GET
X
X
SET
—
—
Instance ID = 1 to N (instance attributes):
Description Type Attribute
ID hex
01
GET SET Value
Originator connection ID UDINT X — Originator to target connection
ID
02
03
04
Originator IP
Originator TCP Port
Target connection ID
UINT X
UDINT X
UDINT X
—
—
— Target to originator connection
ID
05
06
07
Target IP
Target TCP Port
Msg Send Counter
UDINT X
UDINT X
UDINT X
—
—
— Incremented each time a Class
3 CIP message is sent on the connection
96 S1A48978.14
Attribute
ID hex
08
Description
Msg Receive counter
Remote I/O Modules
Type GET SET Value
UDINT X — Increments each time a Class 3
CIP message is received on the connection
X = supported
— = not supported
Services
The EtherNet/IP Explicit Connection Diagnostics object performs the following services upon the listed object type:
Service ID hex dec
01 01
Description
Get_Attributes_
All
X = supported
— = not supported
Class Instance Notes
X X Returns the value of all attributes.
EtherNet/IP Explicit Connection Diagnostics List Object
Overview
The EtherNet/IP Explicit Connection Diagnostics List object presents the instances, attributes and services described below.
Class ID
354 (hex), 852 (decimal)
Instance IDs
The EtherNet/IP Explicit Connection Diagnostics List object presents two instance values:
• 0: class
• 1...
N : instance
Attributes
EtherNet/IP Explicit Connection Diagnostics List object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID Description
01
02
X = supported
— = not supported
Revision
Max Instance
GET
X
X
SET
—
—
Instance ID = 1 to N (instance attributes):
S1A48978.14
97
Remote I/O Modules
Attribute ID
01
02
X = supported
— = not supported
Description
Number of connections
Explicit Messaging
Connections Diagnostic List
Originator connection ID
Originator IP
Originator TCP port
Target connection ID
Target IP
Target TCP port
Msg Send counter
Type
UINT
ARRAY of
STRUCT
UDINT
UINT
UDINT
UDINT
UDINT
UDINT
UDINT
Msg Receive counter UDINT
GET
X
X
SET
—
—
Value
Total number of opened explicit connections
O->T connection ID
—
—
T->O connection ID
—
—
Increments each time a Class 3 CIP message is sent on the connection
Increments each time a Class 3 CIP message is received on the connection
Description
Services
The EtherNet/IP Explicit Connection Diagnostics object performs the following services upon the listed object types:
Class Instance Notes
08
09
4B
Service ID hex dec
01 01
08
09
75
X = supported
— = not supported
Get_Attributes_All
Create
Delete
Explicit_Connections_
Diagnostic_Read
X
X
—
—
—
—
X
X
Returns the value of all attributes.
—
—
—
RSTP Diagnostics Object
Overview
The RSTP Diagnostics object presents the instances, attributes and services described below.
Class ID
355 (hex), 853 (decimal)
Instance IDs
The RSTP Diagnostics object presents these instance values:
• 0: class
• 1: instance
98 S1A48978.14
Attribute ID
01
02
Remote I/O Modules
Attributes
RSTP Diagnostics object attributes are associated with each instance.
Instance ID = 0 (class attributes):
Description
Revision: This attribute specifies the current revision of the RSTP Diagnostic
Object. The revision is increased by 1 at each new update of the object.
Max Instance: This attribute specifies the maximum number of instances that may be created for this object on a per device basis (for example, an RSTP
Bridge). There is 1 instance for each RSTP port on a device.
Type
UINT
UINT
GET
X
X
SET
—
—
X = supported
— = not supported
Attribute ID
01
02
Instance ID = 1 to N (instance attributes):
Description
Switch Status
Protocol Specification
Bridge Priority
Time Since Topology
Change
Topology Change Count
Type
STRUCT
UINT
UDINT
UDINT
UDINT
X
X
GET
X
X
X
CLEAR
—
—
—
—
—
Value
—
Refer to RFC-4188 for attribute definitions and value range. In addition, the following value is defined: [4]: the protocol is IEEE 802.1D-2004 and IEEE 802.1W
Refer to RFC-4188 for attribute definitions and value range.
Refer to RFC-4188 for attribute definitions and value range.
Refer to RFC-4188 for attribute definitions and value range.
Designated Root
Root Cost
Root Port
Max Age
Hello Time
Hold Time
Forward Delay
Bridge Max Age
Bridge Hello Time
Bridge Forward Delay
Port Status
Port
Priority
State
Enable
Path Cost
Designated Root
Designated Cost
Designated Bridge
Designated Port
Forward Transitions Count
X
X
X
X
X
X
X
—
—
X
X
X
—
—
—
—
—
—
—
—
X
String
UINT
STRUCT
UDINT
UDINT
UINT
UINT
UDINT
String
UDINT
String
String
UDINT
UDINT
UINT
UINT
UDINT
UINT
UINT
UINT
UDINT
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
—
Refer to RFC-4188 for attribute definitions and value range.
Refer to RFC-4188 for attribute definitions and value range.
Services:
S1A48978.14
99
Remote I/O Modules
Attribute ID Description
03 Port Mode
Port Number
Admin Edge Port
Oper Edge Port
Auto Edge Port
Type
STRUCT
UINT
UINT
UINT
UINT
X
X
GET
X
X
X
CLEAR
—
—
—
—
—
Value
• Get_and_Clear: The current value of this parameter is returned with the response message.
• other services: The current value of this parameter is returned without being cleared.
—
This attribute indicates the port number for a data query. The value range is configuration dependent. For a 4-port Ethernet device, as an instance, the valid range is 1...4.
This attribute indicates if this is a user-configured edge port:
• 1: true
• 2: false
Other values are not valid.
This attribute indicates if this port is currently an edge port:
• 1: true
• 2: false
Other values are not valid.
This attribute indicates if this port is a dynamically determined edge port:
• 1: true
• 2: false
Other values are not valid.
X = supported
— = not supported
Service ID hex
01 dec
01
02
32
02
50
Description
Services
The RSTP Diagnostics object performs these services:
Class Instance Notes
Get_Attributes_All
Get_Attribute_Single
Get_and_Clear
X
X
—
X
X
X
This service returns:
• all attributes of the class
• all attributes of the instance of the object
This service returns:
• the contents of a single attribute of the class
• the contents of the instance of the object as specified
Specify the attribute ID in the request for this service.
This service returns the contents of a single attribute of the instance of the object as specified. Then the relevant counter-like parameter(s) within the specified attribute are cleared. (Specify the attribute ID in the request for this service.)
X = supported
— = not supported
Service Port Control Object
Overview
The Service Port Control object is defined for port control purposes.
100 S1A48978.14
Class ID
400 (hex), 1024 (decimal)
Instance IDs
The Service Port Control object presents these instance Values:
• 0: class
• 1: instance
Remote I/O Modules
Attributes
Service Port Control object attributes are associated with each instance.
Required class attributes (instance 0):
Attribute ID
01
02
X = supported
— = not supported
Description
Revision
Max Instance
Type
UINT
UINT
Get
X
X
Set
—
—
Required instance attributes (instance 1):
Description Type Get Attribute ID hex
01 dec
01 Port Control UINT X
Set
X
Value
02 02 Mirror UINT X X
0 (default): disabled
1: access port
2: port mirroring
3: extended port bit 0 (default): ETH2 port bit 1: ETH3 port bit 2: ETH4 port bit 3: internal port
X = supported
— = not supported
NOTE:
• If the SERVICE/EXTEND port is not configured for port mirroring, the mirror attribute is ignored. If the value of a parameter request is outside the valid range, the service request is ignored.
• In port mirroring mode, the SERVICE/EXTEND port acts like a read-only port. That is, you cannot access devices (ping, connection to Control
Expert, etc.) through the SERVICE/EXTEND port.
Services
The Service Port Control object performs these services for these object types:
S1A48978.14
101
Remote I/O Modules
Service ID hex dec
01 01
Name
Get_Attributes_All
Class
02 02 Set_Attributes_All
X
—
0E
10
14
16
Get_Attribute_
Single
Set_Attribute_
Single
X = supported
— = not supported
X
—
Instance
X
Description
X
X
Get all attributes in a single message.
Set all attributes in a single message.
Get a single specified attribute.
X Set a single specified attribute.
Diagnostics Available through Control Expert
Introduction
The Quantum EIO modules support online actions. Use the online actions to perform these tasks:
• Display EtherNet/IP objects for the head module or a remote EtherNet/IP device.
• View and edit the service/extend port configuration parameters for the head module/
• Ping the head module or a remote EtherNet/IP or Modbus TCP device to confirm it is active on the Ethernet network.
• Connect to a remote device to perform these actions:
◦ View the remote device’s default parameter settings.
◦ View the remote device’s current parameter settings.
◦ Edit and download to the remote device its editable parameter settings.
Device Services
Access the Device Services Tab
The Control Expert IP configuration parameters apply to the 140 CRP 312 00 head module in the local rack. To access the Device Services tab,
double-click on the 140 CRP 312 00 module, page 32
.
Device Services Parameters
These parameters are found on the Control Expert Device Services tab:
Field
Network Card
CRP Diagnostics
(See below.)
Parameter
Card
• Connect
• Disconnect
• Online Action
• EtherNet/IP Explicit Message
Apply
Description
IP address of the PC connection to the 140 CRP
312 00 apply configuration
102 S1A48978.14
Remote I/O Modules
Access Online Action
In the CRP Diagnostics field, select Connect to connect to the PLC and press
Apply to access the configuration tabs for Online Action or EtherNet/IP Explicit
Message :
• Online Action configuration tabs:
◦
◦
◦
•
EtherNet/IP Explicit Message, page 61
EtherNet/IP Objects
View Parameters
Use the EtherNet/IP Objects tab to view available EtherNet/IP parameters:
Step
1
2
3
4
Action
In Control Expert, access the module for
Online Action.
Double-click on the 140 CRP 312 00 module in the Control Expert rack view.
Select the EtherNet/IP Objects tab.
Press Refresh .
Comment
Refer to Online Action, page 103
.
View these parameters:
• Group/Parameters
• Value
• Unit
This action updates the screen with current parameters.
Service Port Management (Online Action)
Introduction
Configure the SERVICE port for the 140CRP31200 module on the Control Expert
Service Port tab.
Access the Service Port Tab
Step
1
2
3
Action
In Control Expert, access the module for Online Action.
.
Double-click the 140CRP31200 module in the Control Expert rack view.
Select the Service Port tab.
Field
Service Port Mode
Access Port
Configuration
Port Mirroring
Configuration
Service Port Parameters
Parameter
Access (default)
Value
ETH1
Mirroring ETH1
Service Port Number ETH1
Source Port(s)
ETH1
Internal Port Yes
No
Comment
You cannot edit the value in the Service Port Number field.
Service Port Mode = Mirroring (see note)
Service Port Mode = any available source port
Ethernet traffic destined for the module
S1A48978.14
103
Remote I/O Modules
Field Parameter Value
ETH2
ETH3
ETH4
Yes
No
Yes
No
Yes
No
—
Comment traffic through the 140CRP31200 INTERLINK port
Ethernet traffic through the first remote I/O port
Ethernet traffic through the second remote I/O port
Description — — description of the source port
NOTE: In port mirroring mode, the SERVICE port acts like a read-only port. That is, you cannot access devices (ping, connection to
Control Expert, etc.) through the SERVICE port.
Buttons on the Service Port tab:
Button
Update
Refresh
Description
After you change Service Port parameters, press this button so that the module can use the new configuration.
This button reads the latest Service Port configuration from the module.
On Line Behavior
The Service Port parameters are stored in the application, but you can reconfigure (change) the parameters in connected mode. Values that you reconfigure in connected mode are sent to the 140CRP31200 module through explicit messages. (The changed values are not stored, so a mismatch can exist between the parameters that are being used and those in the stored application.)
If the module does not respond to the explicit messages, a message appears.
Limitations
The SERVICE port on the 140CRP31200 module has the same limitations as the cloud port of the dual-ring switch (DRS). Therefore, the cloud port on the module and the cloud port on the DRS can be connected to the same equipment.
For more information about considerations that apply to the use of the distributed
I/O cloud port on the DRS, refer to the topic Predefined Configuration Files topic in the Quantum Ethernet I/O System Planning Guide .
Pinging the 140CRP31200 Module
Introduction
Use the Control Expert ping function to send an ICMP echo request to the
140CRP31200 head module. The request determines if the target device is present. If the target device is present, the request determines the time elapsed until an echo response from the target device is received.
Access the Ping Tab
Open the Control Expert Ping tab:
Step
1
2
3
Action
In Control Expert, access the 140CRP31200 head module for
.
Double-click on the 140CRP31200 head module in the Control Expert rack view.
Select the Ping tab.
104 S1A48978.14
Ping Tab
This illustration shows the Ping tab and its parameters:
Remote I/O Modules
Ping parameters:
Field
Address
Ping
Parameter
IP Address
Repeat (100ms)
Stop on Error
Ping (button)
Ping Result
Clear (button)
Value
— checked unchecked checked unchecked
—
—
—
Comment
IP address of the target module.
Ping once.
Ping every 100 ms.
Stop pinging when a detected communication error is displayed.
Continue pinging when a detected communication error is displayed.
Start pinging. (Click again to stop repeated pinging when no detected error is displayed.)
This box reports the response to the ping.
Click this button to clear (empty) Ping Result .
Displaying I/O Memory Consumption
Displaying Memory Consumption
In Control Expert you can monitor the I/O memory consumption by viewing the bus properties. Use one of these methods:
• In the Project Browser , right-click Project > Configuration > EIO Bus >
Properties
• In the Project Browser , right-click Project > Configuration > EIO
[Quantum or Modicon X80] Drop > Properties
• In background of the EIO Bus window, right-click Bus properties .
• In the Edit menu, scroll to Bus properties .
S1A48978.14
105
Remote I/O Modules
The IO-Memory screen looks like this:
Exceeding EIO Limitations
Control Expert displays a detected error in the log window if one of these events occurs:
• The size of the EIO memory exceeds 1400 input bytes or 1400 output bytes.
• The size of the EIO network exceeds 32768 input bytes or 24576 output bytes.
• The size of the EIO network exceeds 80% of the 32768 input bytes or 80% of the 24576 output bytes.
Logging DTM Events to a Control Expert Logging Screen
Description
Control Expert maintains a log of events for:
• the Control Expert embedded FDT container
• each Ethernet communication module DTM
• each EtherNet/IP remote device DTM
Events relating to the Control Expert FDT container are displayed in the FDT log event page of the Output Window .
Events relating to a communication module or remote EtherNet/IP device are displayed:
• in configuration mode: in the Device Editor , by selecting the Logging node in the left pane
• in diagnostic mode: in the Diagnostics window, by selecting the Logging node in the left pane
Logging Attributes
The Logging window displays the result of an operation or function performed by
Control Expert. Each log entry includes the following attributes:
Attribute
Date/Time
Log Level
Description
The time the event occurred, displayed in the format: yyyy-mm–dd hh:mm:ss
The level of event importance. Values include:
Information A successfully completed operation.
Warning An operation that Control Expert completed, but which may lead to a subsequent error.
106 S1A48978.14
Remote I/O Modules
Attribute Description
Error An operation that Control Expert was unable to complete.
Message A brief description of the core meaning of the event.
Detail Message A more detailed description of the event, which may include parameter names, location paths, etc.
Accessing the Logging Screen
In Control Expert:
Step
1
2
3
4
Action
Open a project that includes a BME NOC 03•1 Ethernet communication module.
Clock Tools > DTM Browser to open the DTM Browser .
In the DTM Browser , double-click the BME NOC 03•1 (or right-click Open ) to open the configuration window.
Select Logging in the navigation tree in the left pane of the window.
S1A48978.14
107
Remote I/O Modules
Firmware Upgrade
Introduction
This chapter describes the steps for upgrading the firmware for your
140CRP31200 head module and the 140CRA31200 or BMXCRA312•0 adapter module.
Firmware Update with Automation Device Maintenance
Overview
The EcoStruxure ™ Automation Device Maintenance is a standalone tool that allows and simplifies the firmware update of devices in a plant (single or multiple).
The tool supports the following features:
• Automatic device discovery
• Manual device identification
• Certificate management
• Firmware update for multiple devices simultaneously
NOTE: For a description of the download procedure, refer to the
EcoStruxure ™ Automation Device Maintenance, User Guide .
140CRP31200 Firmware Upgrade with OS Loader
OS
Use the Control Expert OS Loader to upgrade the firmware on the 140CRP31200 module. OS Loader was installed on your PC when you installed Control Expert.
(The minimum required version of OS Loader is V6.0. The compatible version is included with your copy of Control Expert.)
A complete firmware upgrade includes the installation of these discrete files:
• kernel
• exec
The kernel and exec files are installed independently. Therefore, perform the firmware upgrade process two times (once for each file).
The name of the firmware file indicates the upgrade type (kernel or exec).
Examples:
• kernel file name: CCS1_Noc_Kerl_OSLoader.bin
• exec file name: CCS1_Noc_Exec_OSLoader.bin
NOTE: These instructions assume that you are familiar with Control Expert.
For more information about the OS Loader, refer to the chapter OSLoader
Screens (see EcoStruxure ™ Control Expert, OS Loader, User Manual).
Upgrade Procedure
Follow these steps to upgrade either the firmware kernel or the firmware exec.
108 S1A48978.14
Step
1
5
6
2
3
4
7
8
9
Remote I/O Modules
NOTE:
• We recommend that you update the kernel before you upgrade the exec.
Both firmware upgrade files are installed in the same manner. The only difference is the name of the file you select.
• Confirm that there is no interruption to power or communications during the firmware upgrade process. Otherwise, the 140CRP31200 module can be damaged.
• During the firmware upgrade, the I/O communications with the adapter on the remote drop are interrupted. After the
expires, the I/O modules return to their fallback state.
Action
Connect the PC that is running the Control Expert OS
Loader directly to one of the module ports.
Launch OS Loader.
Click Next to continue.
Select the FTP communication driver and press Next to continue.
In the Target Address area, type in the FTP Address of the
140CRP31200 module that is the target of the upgrade.
Click Next to continue. Perform these tasks at the next installation screen:
—
Comment
Available ports:
• SERVICE port:
◦ 140CRP31200 head module
◦ 140CRA31200 adapter (Quantum remote drop)
◦ BMXCRA31210 adapter (Modicon X80 remote drop)
• INTERLINK port (140CRP31200)
• DRS port that is configured for a distributed I/O cloud
Start > Programs > EcoStruxure Control Expert > OS
Loader .
Go directly to the first installation step.
The next screen displays a list of devices discovered by OS
Loader. It also displays the FTP address for each discovered device.
— a b
Select Download OS to device .
Click the Browse button to navigate to and select the desired firmware upgrade file.
— Click Next . Perform these tasks at the next installation screen: a b
Compare the selected firmware File against the firmware already loaded in the
Device .
Confirm that the Hardware ID for both the file and the device are the same
Click Next . On the summary page, click Download .
Click Close .
The OS Loader displays the progress of the FTP session.
The download is complete when it displays the word
SUCCESS .
The firmware download is finished.
The upgrade process takes approximately 2 minutes:
• 1 minute for firmware upgrade
• 1 minute to reboot and reestablish I/O connections
Hot Standby
Use these steps to upgrade the 140CRP31200 firmware in Hot Standby configurations:
S1A48978.14
109
Remote I/O Modules
Step
1
2
3
Action
Use the preceding instructions to upgrade the firmware for the 140CRP31200 in the standby rack.
NOTE: During the firmware upgrade, the I/O communications with the remote drop’s adapter and the 140CRP31200 module in the primary rack are not interrupted. However, the standby I/O communications with the adapter are interrupted.
When the firmware on the 140CRP31200 in the standby rack is upgraded, perform a manual switch-over that gives the newly upgraded standby rack the role of primary rack.
Upgrade the firmware for the adapter in the (new) standby rack to facilitate future Hot
Standby switch-overs.
Adapter Firmware Upgrade with Unity Loader
Overview
Use these procedures to upgrade the firmware for the 140CRA31200 or
BMXCRA312•0 remote I/O adapter:
2
3
Stage
1
4
Description
Download and install Unity Loader software.
Configure and store IP parameters (optional).
Connect your configuration PC to the remote I/O adapter.
Transfer the firmware upgrade to the remote I/O adapter.
The minimum required version of Unity Loader is V2.2. (V2.3 is required for the
BMXCRA312•0 adapter module and I/O modules in a Modicon X80 Ethernet remote I/O drop.)
Downloading and Installing Unity Loader
Download the Unity Loader software to your PC:
2
3
Step
1
4
5
Action
Enter the web address for Schneider Electric (www.se.com) in an Internet browser.
In the Search from input field , enter the phrase Unity Loader and press Enter .
Examine the search results and select the appropriate entry for the Unity Loader software.
NOTE: You can select the Download results.
> Softwares menu command to filter the
Follow the on-screen instructions to download both the Unity Loader installation software and any necessary installation instructions.
Run the Unity Loader setup file and follow the instructions (on the screen and in the downloaded documentation) to install Unity Loader.
Default Address Configurations
If you wish, you can configure and store IP parameters for the remote drop’s communications adapter when these conditions are met:
• The rotary switch setting is Stored .
• You have not configured and stored valid IP parameters
The adapter uses these default address configurations:
110 S1A48978.14
Remote I/O Modules
Parameter
Default IP Address
Description
The default IP address starts with 10.10 and uses the last 2 bytes of the
MAC address. As an example, a device with the MAC address of
00:00:54:10:8A:05 has a default IP address of 10.10.138.5 (0x8A=138,
0x05=5).
The default mask is 255.0.0.0 (a class A mask).
Default Sub-Network
Mask
Default Gateway
Address
The default gateway address is identical to the default IP address.
The default address is based on the adapter’s MAC address. This makes it possible for several Schneider Electric devices to use their default network configurations on the same network.
To use a specific set of IP parameters, store them in the adapter module. Set the rotary switches to the Stored position.
You can send an
EtherNet/IP explicit message, page 58
to the
TCP/IP interface object, page 87
of the module to store the configured IP parameters.
NOTE: The adapter uses the stored IP parameters only after a power cycle.
Connect the Configuration PC to the Remote I/O Adapter
Connect your configuration PC (that is running Unity Loader) directly to the
140CRA31200 or BMXCRA31210 adapter module. These ports are available:
• SERVICE port
• DRS port that is configured for a distributed I/O cloud
NOTE: There is no SERVICE port on the BMXCRA31200 adapter.
Verify that communications are established between the PC and the adapter by issuing a Ping command from the PC:
Step
1
2
3
4
Action
Open a command window on the PC.
In the Run dialog, type in cmd .
Click OK .
At the command prompt, type in the ping command and the device IP address.
Comment
Start > Run .
Example: C:\>ping 192.168.21.38
:
The command window verifies that a connection is established:
Upgrade Procedure
Do not interrupt the firmware download process:
S1A48978.14
111
Remote I/O Modules
Step
1
• Do not allow an interruption to the power or the communications during the firmware upgrade process.
• Do not shut down the Unity Loader software during the upgrade.
If the firmware download process is interrupted, the new firmware is not installed and the adapter continues to use the old firmware. If an interruption occurs, restart the process.
Open Unity Loader on your PC and update the firmware for the remote I/O adapter:
Action
Open Unity Loader on your PC. ( Start > Programs > Schneider Electric > Unity Loader )
Unity Loader opens and displays the Project tabM
112
2
3
4
In the Connection area of the Project page, connect to the module:
• In the Media list, select Ethernet .
• In the Address field, type in the IP address of the adapter, which is either:
◦ configured : The adapter is already communicating on the network and the IP address for the module is
configured in the application, page 38
.
◦ default : The adapter’s rotary switch position is Stored and you did not already store valid IP parameters.
• Click Connect .
After Unity Loader has connected to the module, click the Firmware tab:
In the PC area, click the ellipsis ( ...
) button to open a dialog where you can navigate to and select the firmware file for the network connectivity module. The firmware is contained in a Unity Loader file (.ldx extension).
S1A48978.14
Step
Remote I/O Modules
Action
After you select the firmware file and close the dialog, the selected revision of this firmware is displayed in the list on the left, and the current version of the firmware is displayed in the list on the right.
5
6
When the arrow in the middle of the screen (above) is green, click Transfer .
NOTE: Only click Transfer if the arrow is green. A yellow arrow indicates that the firmware file on your computer is the same version or newer than the file selected for transfer; a red arrow indicates that the firmware on the computer is not compatible with the remote I/O adapter.
Click yes on the 2 dialogs that appear. A third dialog appears (below), which indicates the transfer status with the blue bars at the bottom of the screen. After the transfer is complete, click Close .
7
8
NOTE: If you are upgrading firmware for more than one remote I/O adapter, additional dialogs will appear. Click yes to close each dialog.
In the Unity Loader software, click Disconnect and close the window.
Reboot the module to finalize the firmware update.
The upgrade process takes approximately 2 minutes:
• firmware upgrade (1 minute)
• reboot, reestablish I/O connections (1 minute)
S1A48978.14
113
Remote I/O Modules
During the firmware upgrade, the I/O communications with the adapter module may be interrupted. After the
expires, the I/O modules return to their fallback state.
114 S1A48978.14
Glossary
Remote I/O Modules
A adapter:
The target of real-time I/O data connection requests from scanners. It cannot send or receive real-time I/O data unless it is configured to do so by a scanner, and it does not store or originate the data communications parameters necessary to establish the connection. An adapter accepts explicit message requests
(connected and unconnected) from other devices.
ART:
( application response time ) The time a PLC application takes to react to a given input. ART is measured from the time a physical signal in the PLC turns on and triggers a write command until the remote output turns on to signify that the data has been received.
B broadcast:
A message sent to devices in the subnet.
C
CCOTF:
( change configuration on the fly ) A feature of Control Expert that allows a PLC hardware change in the system configuration while the PLC is operating and not impacting other active drop operations.
CIP ™ :
( common industrial protocol ) A comprehensive suite of messages and services for the collection of manufacturing automation applications (control, safety, synchronization, motion, configuration and information). CIP allows users to integrate these manufacturing applications with enterprise-level Ethernet networks and the internet. CIP is the core protocol of EtherNet/IP.
control network:
An Ethernet-based network containing PLCs, SCADA systems, an NTP server,
PCs, AMS, switches, etc. Two kinds of topologies are supported:
• flat — Devices in this network belong to the same subnet.
• 2 levels — The network is split into an operation network and an intercontroller network. These 2 networks can be physically independent, but are generally linked by a routing device.
D
DDT:
( derived data type ) A set of elements with the same type ( array ) or with different types (structure).
determinism:
For a defined application and architecture, the ability to predict that the delay between an event (change of an input value) and the corresponding change of an output state is a finite time t , smaller than the time required for your process to run correctly.
S1A48978.14
115
Remote I/O Modules
116 device network:
An Ethernet-based network within a remote I/O network that contains both remote
I/O and distributed I/O devices. Devices connected on this network follow specific rules to allow remote I/O determinism.
distributed I/O device:
Any Ethernet device (Schneider Electric device, PC, servers, or third-party devices) that supports I/O exchange with a PLC or other Ethernet communication service.
distributed I/O network:
A network containing distributed I/O devices that integrates a unique standalone
PLC or a unique Hot Standby system. I/O scanning may be performed by a communication module interlinked with a remote I/O head module on the local rack of an Ethernet remote I/O system. Distributed I/O network traffic is delivered after remote I/O traffic, which takes priority in an Ethernet remote I/O network.
DRS:
( dual-ring switch ) A ConneXium extended managed switch with one of several possible predefined configurations downloaded to it so that it can participate in an
Ethernet I/O network. A DRS provides 2 RSTP-enabled ring connections, one for the main ring and one for a sub-ring. It also manages QoS, which provides a predictable level of performance for both remote I/O and distributed I/O traffic on the same I/O network.
DRSs require a firmware version 6.0 or later.
DTM:
( device type manager ) A device driver running on the host PC. It provides a unified structure for accessing device parameters, configuring and operating the devices, and troubleshooting the network. DTMs can range from a simple graphical user interface (GUI) for setting device parameters to a highly sophisticated application capable of performing complex real-time calculations for diagnosis and maintenance purposes. In the context of a DTM, a device can be a communications module or a remote device on the network.
See FDT .
E
EtherNet/IP ™ :
A network communication protocol for industrial automation applications that combines the standard internet transmission protocols of TCP/IP and UDP with the application layer common industrial protocol (CIP) to support both high speed data exchange and industrial control. EtherNet/IP employs electronic data sheets
(EDS) to classify each network device and its functionality.
Ethernet:
A 10 Mb/s, 100 Mb/s, or 1 Gb/s, CSMA/CD, frame-based LAN that can run over copper twisted pair or fiber optic cable, or wireless. The IEEE standard 802.3
defines the rules for configuring a wired Ethernet network; the IEEE standard
802.11 defines the rules for configuring a wireless Ethernet network. Common forms include 10BASE-T, 100BASE-TX, and 1000BASE-T, which can utilize category 5e copper twisted pair cables and RJ45 modular connectors.
explicit messaging:
TCP/IP-based messaging for Modbus TCP and EtherNet/IP. It is used for pointto-point, client/server messages that include both data (typically unscheduled information between a client and a server) and routing information. In EtherNet/
IP, explicit messaging is considered class 3 type messaging, and can be connection-based or connectionless.
S1A48978.14
S1A48978.14
Remote I/O Modules
F
FBD:
( function block diagram ) A graphical programming language that works like a flowchart. By adding simple logical blocks ( AND , OR , etc.), each function or function block in the program is represented in this graphical format. For each block, the inputs are on the left and the outputs on the right. Block outputs can be linked to inputs of other blocks in order to create complex expressions.
FDT:
( field device tool ) The technology that harmonizes communication between field devices and the system host.
G gateway:
A device that interconnects 2 different networks, sometimes with different network protocols. When used to connect networks based on different protocols, a gateway converts a datagram from one protocol stack into the other. When used to connect 2 IP-based networks, a gateway (also called a router) has 2 separate
IP addresses, one on each network.
H
Hot Standby:
A high-availability control system with a second (standby) PLC that maintains upto-date system status. If the primary PLC becomes inoperable, the standby PLC takes control of the system.
I implicit messaging:
UDP/IP-based class 1 connected messaging for EtherNet/IP. Implicit messaging maintains an open connection for the scheduled transfer of control data between a producer and consumer. Because an open connection is maintained, each message contains primarily data, without the overhead of object information, and a connection identifier.
interlink port:
An Ethernet port on Ethernet remote I/O head modules allowing direct connection of distributed I/O modules to the remote I/O network and transparency between a control network and the Ethernet remote I/O network.
I/O scanning:
Continuously polling the I/O modules to collect data and status, event, and diagnostics information. This process monitors inputs and controls outputs.
IP address:
The 32-bit identifier, consisting of both a network address and a host address, assigned to a device connected to a TCP/IP network.
L local rack:
A Quantum rack containing the controller, a power supply, and an Ethernet remote I/O head module. A local rack consists of 1 or 2 racks, the main rack
(containing the remote I/O head module) and an optional extended rack. A
Quantum Ethernet remote I/O network requires 1 local rack on the main ring.
117
Remote I/O Modules
118
M
MAST:
A master processor task that is run through its programming software. The MAST task has 2 sections:
• IN: Inputs are copied to the IN section before execution of the MAST task.
• OUT: Outputs are copied to the OUT section after execution of the MAST task.
multicast:
A special form of broadcast where copies of the packet are delivered to only a specified subset of network destinations. Implicit messaging typically uses multicast format for communications in an EtherNet/IP network.
P
PLC: programmable logic controller . The PLC is the brain of an industrial manufacturing process. It automates a process as opposed to relay control systems. PLCs are computers suited to survive the harsh conditions of the industrial environment.
port mirroring:
In this mode, data traffic that is related to the source port on a network switch is copied to another destination port. This allows a connected management tool to monitor and analyze the traffic.
NOTE: In port mirroring mode, the SERVICE port acts like a read-only port.
That is, you cannot access devices (ping, connection to Control Expert, etc.) through the SERVICE port on the module.
R remote I/O drop:
One of the 3 types of remote I/O devices in an Ethernet remote I/O network. A remote I/O drop is a Quantum or an X80 rack of I/O modules that are connected to an Ethernet remote I/O network and managed by an Ethernet remote adapter module. A drop can be a single rack or a rack with an extension rack.
remote I/O main ring:
The main ring of an Ethernet remote I/O network. The ring contains remote I/O devices and a local rack (containing a controller, a power supply module, and an
Ethernet remote I/O head module).
remote I/O network:
An Ethernet-based network that contains 1 standalone PLC or one Hot Standby system and remote I/O devices. There are 3 types of remote I/O devices: a local rack, a remote I/O drop, and a ConneXium extended dual-ring switch (DRS).
Distributed I/O devices may also participate in a remote I/O network via connection to DRSs.
RPI:
(requested packet interval) The time period between cyclic data transmissions requested by the scanner. EtherNet/IP devices publish data at the rate specified by the RPI assigned to them by the scanner, and they receive message requests from the scanner at each RPI.
RSTP:
( rapid spanning tree protocol ) A protocol that allows a network design to include spare (redundant) links to provide automatic backup paths if an active link stops working, without the need for loops or manual enabling/disabling of backup links.
S1A48978.14
S1A48978.14
Remote I/O Modules
S
S908 legacy remote I/O:
A Quantum remote I/O system using coaxial cabling and terminators.
service port:
A dedicated Ethernet port on the Quantum Ethernet remote I/O modules. The port may support 3 major functions (depending on the module type):
• port mirroring — for diagnostic use
• access — for connecting HMI/Control Expert/ConneXium Network Manager to the PLC
• extended — to extend the device network to another subnet
• disabled — disables the port, no traffic is forwarded in this mode
SNMP:
( simple network management protocol ) Protocol used in network management systems to monitor network-attached devices for events. The protocol is part of the internet protocol suite (IP) as defined by the internet engineering task force
(IETF), which consists of network management guidelines, including an application layer protocol, a database schema, and a set of data objects.
T trap:
An event directed by an SNMP agent that indicates one of the following:
• a change has occurred in the status of an agent
• an unauthorized SNMP manager device has attempted to get data from, or change data on, an SNMP agent
TCP/IP:
Also known as internet protocol suite , TCP/IP is a collection of protocols used to conduct transactions on a network. The suite takes its name from 2 commonly used protocols: transmission control protocol and internet protocol. TCP/IP is a connection-oriented protocol that is used by Modbus TCP and EtherNet/IP for explicit messaging.
U
UDP:
( user datagram protocol ) A transport layer protocol that supports connectionless communications. Applications running on networked nodes can use UDP to send datagrams to one another. UDP does not always deliver datagrams as reliable or ordered as those delivered by TCP. However, by avoiding the overhead required for TCP, UDP is faster. UDP may be the preferred protocol for time-sensitive applications, where dropped datagrams are preferable to delayed datagrams.
UDP is the primary transport for implicit messaging in EtherNet/IP.
119
Index
140 CRA 312 00
Control Expert configuration..................... 34, 37, 42
description.........................................................14
firmware upgrade ............................................. 108
functionality .......................................................14
grounding ..........................................................23
installation ..............................................21–23, 26
Modbus diagnostic codes ...................................73
NTP configuration ..............................................12
ports .................................................................16
rack extension ...................................................27
specifications.....................................................16
140 CRP 312 00
Control Expert configuration.......................... 32, 37
description.........................................................12
explicit messaging..............................................58
external features ................................................13
firmware upgrade ............................................. 108
functionality .......................................................12
grounding ..........................................................23
installation ................................................... 21–23
Modbus diagnostic codes ...................................73
NTP configuration ..............................................36
ports .................................................................13
specifications.....................................................16
sub-ring diagnostics ...........................................73
140 NOC 780 00
grounding ..........................................................23
installation ................................................... 22–23
Modbus diagnostic codes ...................................73
specifications.....................................................16
140 NOC 781 00
grounding ..........................................................23
installation ................................................... 22–23
Modbus diagnostic codes ...................................73
specifications.....................................................16
140 NOP 850 00
Modbus diagnostic codes ...................................73
140CRA31908
installation ................................................... 21–23
A
assembly object ....................................................83
B
BME NOC 03•1
Modbus diagnostic codes ...................................73
BMENOP0300
Modbus diagnostic codes ...................................73
BMX CRA 312 ••
installation .........................................................22
BMX CRA 312 •0
grounding ..........................................................23
installation .........................................................23
BMX CRA 312 00
Control Expert configuration..................... 34, 37, 42
description.........................................................14
external features ................................................15
firmware upgrade ............................................. 108
functionality .......................................................14
installation ................................................... 21, 26
Modbus diagnostic codes ...................................73
NTP configuration ..............................................12
S1A48978.14
Remote I/O Modules
ports .................................................................16
rack extension ...................................................27
specifications.....................................................16
BMX CRA 312 10
Control Expert configuration..................... 34, 37, 42
description.........................................................14
external features ................................................15
firmware upgrade ............................................. 108
functionality .......................................................14
installation ................................................... 21, 26
Modbus diagnostic codes ...................................73
NTP configuration ..............................................36
ports .................................................................16
rack extension ...................................................27
specifications.....................................................16
BMX NOC 0401
Modbus diagnostic codes ...................................73
C
CIP objects ...........................................................81
connection manager object ....................................84
Control Expert
logging ............................................................ 106
Control Expert project
convert from 7.0 to 8.0........................................32
convert Control Expert project
from 7.0 to 8.0 ...................................................32
D
derived data types .................................................48
device DDT
T_Q_DROP_EXT_IN ................................... 47, 51
diagnostics
Modbus codes ...................................................73
system ..............................................................71
E
EF
Quantum drop in M580 system ...........................55
EFB
Quantum drop in M580 system ...........................55
Ethernet link object ................................................88
Ethernet remote I/O
cabling ..............................................................29
Control Expert configuration................................32
diagnostics ........................................................67
EtherNet/IP
explicit messaging..............................................58
implicit messaging..............................................66
EtherNet/IP explicit connection diagnostics
object ........................................................... 96–97
EtherNet/IP interface diagnostics object ..................91
EtherNet/IP IO Scanner Diagnostics object .............93
explicit messaging
EtherNet/IP ................................................. 60–61
EtherNet/IP services ..........................................59
F firmware
firmware upgrade
140 CRP 312 00 .............................................. 108
121
Remote I/O Modules function block
Quantum drop in M580 system ...........................55
function code 3
diagnostics ........................................................73
140 NOC 780 00 ................................................16
140 NOC 781 00 ................................................16
BMX CRA 312 00...............................................16
I
G
grounding .............................................................23
identity object........................................................81
installation ...................................................... 22–23
I/O devices ...........................................................18
intelligent...........................................................19
special purpose .................................................19
IO connection diagnostics object ............................94
T
T_M_DROP_EXT_IN
Modicon X80 remote I/O adapter.........................51
T_Q_DROP_EXT_IN
device DDT .......................................................47
Quantum remote I/O adapter ..............................51
T_U_CRP_HSBY_IN
140 CRP 312 00 Hot Standby) ............................49
T_U_CRP_STD_IN
140 CRP 312 00 standalone ...............................49
T_U_DROP_STD_IN
Quantum remote I/O adapter ..............................51
TCP/IP interface object ..........................................87
L logging
to Control Expert .............................................. 106
U update
firmware .......................................................... 108
upgrade
firmware .......................................................... 108
M
MAST task ............................................................66
MBP_MSTR..........................................................60
Modbus diagnostic codes.......................................73
Modicon X80 I/O devices
analog...............................................................19
digital ................................................................19
mounting ..............................................................23
O online action
ping ................................................................ 104
online diagnostics................................................ 102
P
ping.................................................................... 104
Q
QoS object............................................................86
Quantum drop in M580 system
M580 system .....................................................55
Quantum I/O devices
analog...............................................................18
digital ................................................................18
R
replacing...............................................................23
rotary switches ......................................................28
RSTP diagnostics object ........................................98
S
setting rotary switches ...........................................28
specifications
140 CRA 312 00 ................................................16
140 CRP 312 00 ................................................16
122 S1A48978.14
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00 www.se.com
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2022 Schneider Electric . All rights reserved.
S1A48978.14