Schneider Electric Quantum EIO - Control Network Configuration Guide
विज्ञापन
विज्ञापन
Quantum EIO
S1A48993 10/2019
Quantum EIO
Control Network
Installation and Configuration Guide
10/2019 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this document on any medium whatsoever without permission of Schneider Electric, given in writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.
S1A48993 10/2019
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Characteristics of the 140NOC78100 Module . . . . . . . .
140NOC78100 Module Description. . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Installing the 140NOC78100 Module . . . . . . . . . . . . . . .
Mounting a Quantum EIO-Compatible Module on the Backplane. . . .
Quantum EIO-Compatible Module Installation Considerations . . . . . .
Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Planning and Designing Control Network Interconnectivity
How the Control Network Works within a Quantum EIO System . . . .
Rules for Interconnectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting a Control Network to a Quantum EIO System . . . . . . . . .
Transparency Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Configuring the 140NOC78100 Module . . . . . . . . . . . . .
4.1 Creating a Project in Control Expert . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating a Project in Control Expert . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the Size and Location of Inputs and Outputs . . . . . . . . . .
4.2 The Control Expert FDT/DTM Interface. . . . . . . . . . . . . . . . . . . . . . . .
Ethernet Configuration Tool User Interface . . . . . . . . . . . . . . . . . . . . .
DTM Browser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DTM Browser Menu Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Bus Discovery Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Properties in the Device Editor. . . . . . . . . . . . . . . . . . . . .
Uploading and Downloading DTM-Based Applications . . . . . . . . . . . .
4.3 Hardware Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adding a DTM to the Control Expert Hardware Catalog . . . . . . . . . . .
Add an EDS File to the Control Expert Hardware Catalog . . . . . . . . .
Updating the Control Expert Hardware Catalog . . . . . . . . . . . . . . . . .
Remove an EDS File from the Control Expert Hardware Catalog. . . .
86
92
96
98
76
78
79
83
63
69
70
71
35
36
50
59
100
102
103
104
107
109
23
25
27
28
9
13
19
20
30
32
S1A48993 10/2019
3
4
4.4 Channel Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Channel Properties Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Channel Properties - Ethernet Page . . . . . . . . . . . . . . . . . . . . . . . . . .
Channel Properties - Switch Page . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Channel Properties - TCP/IP Page . . . . . . . . . . . . . . . . . . . . . . . . . . .
Channel Properties - EtherNet/IP Page . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Ethernet Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enabling Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the DHCP and FDR Servers. . . . . . . . . . . . . . . . . . . . . . .
Configuring the SNMP Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Access Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring QoS Ethernet Packet Tagging . . . . . . . . . . . . . . . . . . . . .
Configuring the Rapid Spanning Tree Protocol . . . . . . . . . . . . . . . . . .
Configuring the Service/Extend Port . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the IP Forwarding Service . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Electronic Mail Notification . . . . . . . . . . . . . . . . . . . . . . . .
4.6 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Security Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7 Configuring the 140 NOC 78• 00 Head Module as an EtherNet/IP
Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introducing the Local Slave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring a Local Slave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Slave Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device List Configuration and Connection Summary. . . . . . . . . . . . . .
Configuring Device Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Device IP Address Settings . . . . . . . . . . . . . . . . . . . . . . .
Configuring Modbus TCP Request Settings . . . . . . . . . . . . . . . . . . . .
Adding and Removing Connections. . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring EtherNet/IP Connections . . . . . . . . . . . . . . . . . . . . . . . . .
Checking Remote Device Identity . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Modular Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
163
164
167
172
178
181
183
184
Configuring Communication Module Connection Settings. . . . . . . . . .
EtherNet/IP Connection Information . . . . . . . . . . . . . . . . . . . . . . . . . .
186
188
Chapter 5 Configuring Remote Devices . . . . . . . . . . . . . . . . . . . . . .
191
Displaying Remote Device and DTM Properties . . . . . . . . . . . . . . . . .
192
193
195
197
199
200
126
133
136
138
140
144
147
151
111
112
114
115
117
120
122
123
153
161
161
S1A48993 10/2019
Chapter 6 Online Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Action - EtherNet/IP Object . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Action - Port Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Action - Ping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Viewing and Editing Online Settings for a Remote Device . . . . . . . . .
Get and Set Rack Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Working With Derived Data Types . . . . . . . . . . . . . . . . .
Creating and Updating Derived Data Types . . . . . . . . . . . . . . . . . . . .
Working with Derived Data Type Variables . . . . . . . . . . . . . . . . . . . . .
Effect of Activating and De-activating Devices on I/O %MW Memory
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8 Explicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1 Explicit Messaging Using the MBP_MSTR Block . . . . . . . . . . . . . . . .
Configuring Explicit Messaging Using MBP_MSTR . . . . . . . . . . . . . .
8.2 EtherNet/IP Explicit Messaging Using MBP_MSTR . . . . . . . . . . . . . .
EtherNet/IP Explicit Messaging Services . . . . . . . . . . . . . . . . . . . . . .
Configuring the CONTROL and DATABUF Parameters . . . . . . . . . . .
MBP_MSTR Example: Get_Attributes_Single . . . . . . . . . . . . . . . . . . .
8.3 Modbus TCP Explicit Messaging Using MBP_MSTR . . . . . . . . . . . . .
Modbus TCP Explicit Messaging Function Codes. . . . . . . . . . . . . . . .
Configuring the Control Parameter for Modbus TCP Explicit Messaging
8.4 Explicit Messaging via the Control Expert GUI . . . . . . . . . . . . . . . . . .
Sending Explicit Messages to EtherNet/IP Devices . . . . . . . . . . . . . .
Sending Explicit Messages to Modbus TCP Devices . . . . . . . . . . . . .
Chapter 9 Implicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EtherNet/IP Implicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 10 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LED Indicators on the 140NOC78•00 Module . . . . . . . . . . . . . . . . . . .
10.2 Diagnostics Available through the CPU. . . . . . . . . . . . . . . . . . . . . . . .
System Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3 Diagnostics Available through Modbus/TCP . . . . . . . . . . . . . . . . . . . .
Modbus Diagnostic Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.4 Diagnostics Available through EtherNet/IP CIP Objects . . . . . . . . . . .
About CIP Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identity Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection Manager Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S1A48993 10/2019
259
260
260
263
263
264
264
274
275
276
278
280
240
241
242
250
251
254
257
257
224
227
228
228
230
231
233
235
201
202
204
206
207
209
211
212
214
5
6
Modbus Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quality Of Service (QoS) Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TCP/IP Interface Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ethernet Link Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EtherNet/IP Interface Diagnostics Object. . . . . . . . . . . . . . . . . . . . . . .
EtherNet/IP IO Scanner Diagnostics Object . . . . . . . . . . . . . . . . . . . .
IO Connection Diagnostics Object . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EtherNet/IP Explicit Connection Diagnostics Object . . . . . . . . . . . . . .
EtherNet/IP Explicit Connection Diagnostics List Object . . . . . . . . . . .
RSTP Diagnostics Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Port Control Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Router Diagnostics Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Router Routing Table Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.5 Diagnostics Available through Control Expert . . . . . . . . . . . . . . . . . . .
Using the Diagnostic Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Module Ethernet Diagnostics . . . . . . . . . . . . . . . . . . .
Communication Module Bandwidth Diagnostics . . . . . . . . . . . . . . . . .
Email Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Slave / Connection Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . .
Local Slave or Connection I/O Value Diagnostics . . . . . . . . . . . . . . . .
Logging DTM Events to a Control Expert Logging Screen . . . . . . . . .
10.6 Hot Standby Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hot Standby Synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hot Standby Switchover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 11 Firmware Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
337
140 NOC 78• 00 Firmware Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . .
12.1 Accessing the Embedded Web Server . . . . . . . . . . . . . . . . . . . . . . . .
337
Chapter 12 Embedded Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . .
341
320
322
325
328
329
330
331
336
Introducing the Embedded Web Pages . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the Home Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using and Editing a Username and Passwords. . . . . . . . . . . . . . . . . .
12.2 Monitoring the Control Expert Application . . . . . . . . . . . . . . . . . . . . . .
Using the Monitoring Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Editor (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working With Data Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Editor (Lite) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
342
343
344
346
349
350
351
357
361
303
305
309
311
313
315
316
317
282
284
286
288
292
295
297
301
S1A48993 10/2019
12.3 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Diagnostics Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Processor Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanner Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ethernet Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QoS Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Email Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Time Service Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . .
Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Router Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
387
Appendix A Detected Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .
TCP/IP Ethernet Detected Error Codes. . . . . . . . . . . . . . . . . . . . . . . .
Modbus TCP Explicit Messaging Detected Error Codes . . . . . . . . . . .
EtherNet/IP Implicit or Explicit Messaging Detected Error Codes . . . .
Electronic Mail Notification Service Detected Error Response Codes
389
390
391
392
395
377
379
380
382
385
386
363
364
365
368
369
371
373
375
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
397
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
405
S1A48993 10/2019
7
8
S1A48993 10/2019
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
S1A48993 10/2019
9
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
BEFORE YOU BEGIN
Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine.
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on factors such as the control function required, degree of protection required, production methods, unusual conditions, government regulations, etc. In some applications, more than one processor may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and factors present during setup, operation, and maintenance of the machine and, therefore, can determine the automation equipment and the related safeties and interlocks which can be properly used. When selecting automation and control equipment and related software for a particular application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as pointof-operation guarding must be provided. This is necessary if the operator's hands and other parts of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software cannot be substituted for or take the place of point-of-operation protection.
10
S1A48993 10/2019
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have been installed and are operational before placing the equipment into service. All interlocks and safeties related to point-of-operation protection must be coordinated with the related automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation protection is outside the scope of the Function Block Library, System User Guide, or other implementation referenced in this documentation.
START-UP AND TEST
Before using electrical control and automation equipment for regular operation after installation, the system should be given a start-up test by qualified personnel to verify correct operation of the equipment. It is important that arrangements for such a check be made and that enough time is allowed to perform complete and satisfactory testing.
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not installed according to local regulations (according to the National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
S1A48993 10/2019
11
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
12
S1A48993 10/2019
About the Book
At a Glance
Document Scope
PlantStruxure is a Schneider Electric program designed to address the key challenges of many different types of users, including plant managers, operations managers, engineers, maintenance teams, and operators, by delivering a system that is scalable, flexible, integrated, and collaborative.
This document presents one of the PlantStruxure features, using Ethernet as the backbone around the Quantum PLC offer and connecting a Quantum local rack to Quantum and Modicon X80 remote I/O drops and distributed I/O devices. This feature is known as Quantum Ethernet I/O or
Quantum EIO. ( NOTE: Modicon X80 is the generic name given to the M340 I/O modules when they are connected remotely to a Quantum controller or module in a PlantStruxure architecture.
The M340 I/O name is still used when the module is connected to a M340 controller. The product references remains unchanged; only the range name changes.
)
This guide describes the 140NOC78100 control network head module and its role in a Quantum
EIO system.
NOTE: The specific configuration settings contained in this guide are for instructional purposes only. The settings required for your specific application may differ from the examples presented in this guide.
S1A48993 10/2019
13
Validity Note
This document is valid for the Quantum EIO system when used with
EcoStruxure™ Control Expert 14.1 or later.
The technical characteristics of the devices described in the present document also appear online.
To access the information online:
Step
1
2
3
4
5
6
Action
Go to the Schneider Electric home page www.schneider-electric.com
.
In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks ( * ).
If you entered a reference, go to the Product Datasheets search results and click on the reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the product range that interests you.
If more than one reference appears in the Products search results, click on the reference that interests you.
Depending on the size of your screen, you may need to scroll down to see the datasheet.
To save or print a datasheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.
14
S1A48993 10/2019
Related Documents
Title of Documentation
Quantum EIO System Planning Guide
Quantum EIO Remote I/O Modules Installation and Configuration
Guide
Quantum EIO Distributed I/O Network Installation and Configuration
Guide
Modicon Quantum Change Configuration on the Fly User Guide
Modicon Quantum Hot Standby System User Manual
Modicon M340/X80 BMX NRP 020• Fiber Optic Repeater Module
User Guide
Reference Number
S1A48959 (English),
S1A48961 (French),
S1A48962 (German),
S1A48964 (Italian),
S1A48965 (Spanish),
S1A48966 (Chinese)
S1A48978 (English),
S1A48981 (French),
S1A48982 (German),
S1A48983 (Italian),
S1A48984 (Spanish),
S1A48985 (Chinese)
S1A48986 (English),
S1A48987 (French),
S1A48988 (German),
S1A48990 (Italian),
S1A48991 (Spanish),
S1A48992 (Chinese)
S1A48967 (English),
S1A48968 (French),
S1A48969 (German),
S1A48970 (Italian),
S1A48972 (Spanish),
S1A48976 (Chinese)
35010533 (English),
35010534 (French),
35010535 (German),
35010536 (Spanish),
35013993 (Italian),
35012188 (Chinese)
EIO0000001108 (English),
EIO0000001109 (French),
EIO0000001110 (German),
EIO0000001111 (Spanish),
EIO0000001112 (Italian),
EIO0000001113 (Chinese)
S1A48993 10/2019
15
16
Title of Documentation
Modicon M340/X80 with EcoStruxure™ Control Expert Analog
Input/Output Modules User Manual
Modicon M340/X80 with EcoStruxure™ Control Expert Discrete
Input/Output Modules User Manual
Modicon M340/X80 with EcoStruxure™ Control Expert
BMX EHC 0200 Counting Module User Manual
EcoStruxure™ Control Expert Program Languages and Structure
Reference Manual
EcoStruxure™ Control Expert, System Bits and Words, Reference
Manual
EcoStruxure™ Control Expert Operating Modes
Quantum with EcoStruxure™ Control Expert Hardware Reference
Manual
Reference Number
35011978 (English),
35011979 (German),
35011980 (French),
35011981 (Spanish),
35011982 (Italian),
35011983 (Chinese)
35012474 (English),
35012475 (German),
35012476 (French),
35012477 (Spanish),
35012478 (Italian),
35012479 (Chinese)
35013355 (English),
35013356 (German),
35013357 (French),
35013358 (Spanish),
35013359 (Italian),
35013360 (Chinese)
35006144 (English),
35006145 (French),
35006146 (German),
35006147 (Spanish),
35013361 (Italian),
35013362 (Chinese)
EIO0000002135 (English),
EIO0000002136 (French),
EIO0000002137 (German),
EIO0000002138 (Italian),
EIO0000002139 (Spanish),
EIO0000002140 (Chinese)
33003101 (English),
33003102 (French),
33003103 (German),
33003104 (Spanish),
33003696 (Italian),
33003697 (Chinese)
35010529 (English),
35010530 (French),
35010531 (German),
35010532 (Spanish),
35013975 (Italian),
35012184 (Chinese)
S1A48993 10/2019
Title of Documentation
EcoStruxure™ Control Expert Installation Manual
Reference Number
35014792 (English),
35014793 (French),
35014794 (German),
35014795 (Spanish),
35014796 (Italian),
35012191 (Chinese)
You can download these technical publications and other technical information from our website at https://www.schneider-electric.com/en/download
S1A48993 10/2019
17
18
S1A48993 10/2019
Quantum EIO
140NOC78100 Module Characteristics
S1A48993 10/2019
Characteristics of the 140NOC78100 Module Chapter 1
Characteristics of the 140NOC78100 Module
Introduction
This chapter describes the 140NOC78100 head module for control network communications in a
Quantum EIO system.
This chapter includes physical characteristics, port descriptions, and agency specifications for the
140NOC78100 module.
What Is in This Chapter?
This chapter contains the following topics:
Topic
140NOC78100 Module Description
Module Specifications
Communication Specifications
Page
S1A48993 10/2019
19
140NOC78100 Module Characteristics
140NOC78100 Module Description
Introduction
The 140NOC78100 control head module is installed on the local rack of a Quantum EIO system.
The module provides the interfaces to communicate with a control network and client applications on an Ethernet remote I/O network.
Functionality
The main purpose of the 140NOC78100 head module is to provide transparency between the control network, the device network, and an extended distributed I/O network, while preserving device network determinism. In addition, the 140NOC78100 module also provides services to communicate with PLC applications running on the control network.
Only one 140NOC78100 module, which supports 1 Gbds can be configured on the local rack.
To communicate with remote I/O devices on a remote I/O network, interlink the 140NOC78100 module with the 140CRP31200 remote I/O head module (or a 140NOC78000 distributed I/O head module that is interlinked with the 140CRP31200 module) on the local rack.
To communicate with remote I/O or distributed I/O devices on the device network, interlink the
140NOC78100 module with the 140NOC78000 distributed I/O head module or the 140CRP31200.
To communicate with devices on an extended distributed I/O network, interlink the 140NOC78000 module with the extended port of the 140NOC78100 module.
20
S1A48993 10/2019
External Features
140NOC78100:
140NOC78100 Module Characteristics
1 LED display
2 SERVICE/EXTEND port (ETH 1)
3 INTERLINK port (ETH 2)
4 CTRL NETWORK port (ETH 3)
5 CTRL NETWORK port (ETH 4)
NOTE: To help prevent dust from entering the unused Ethernet ports on this module, cover the port with the stopper:
S1A48993 10/2019
21
140NOC78100 Module Characteristics
External Ports
The 140NOC78100 module monitors the functionality of network links depending on which links are connected to the network. The module has 4 external ports (up to three IP addresses).
Port Quantity
SERVICE/EXTEND 1
INTERLINK
CTRL NETWORK
1
2
Description
The SERVICE/EXTEND port allows the diagnosis of Ethernet ports and provides access to external tools and devices (Control Expert, ConneXium Network
Manager, HMI, etc.). The port supports these modes:
port mirroring: In this mode, data traffic from one or more of the 3 external
ports – plus the internal port – is copied to this port. This allows a connected tool to monitor and analyze the port traffic.
access port (default): In this mode, diagnostic information is provided via
EtherNet/IP or Modbus explicit messages
, or via SNMP
NOTE: In access port mode, the IP address of the port is the same as that of the control network.
extended network: In this mode, an existing distributed I/O network participates in the Ethernet remote I/O network when a 140NOC78000 distributed I/O head module is connected to the SERVICE/EXTEND control head module and also connected to the
140CRP31200 remote I/O head module.
disabled
port of the 140NOC78100
INTERLINK port of the
NOTE:
If the device, which is connected to the SERVICE/EXTEND port, is configured for a speed that exceeds 100 Mbps, the Ethernet link may not be established between the device and the module through the SERVICE/EXTEND port.
In port mirroring mode, the SERVICE/EXTEND port acts like a read-only port.
That is, you cannot access devices (ping, connect to Control Expert, etc.) through the SERVICE/EXTEND port.
To configure this port, refer to the Configuring the Service/Extend Port topic
The INTERLINK port provides connectivity to other Quantum EIO head modules on the local rack.
These 2 copper ports provide:
connections for control network communications
star, loop, or mesh topology
22
S1A48993 10/2019
140NOC78100 Module Characteristics
Module Specifications
Product Certification
The Quantum EIO head/adapter modules meet these standards:
UL (UL508)
CSA (CSA22.2 no. 142)
C-tick
Hazardous locations (Cl1 div 2)
IEC61000-4-16
EMI EN 55011
CE
EN 61131-1
IEC 61131-2 (zone B and zone C, except surges on AC: zone B only)
Quantum EIO modules conform to these product certification and marine classification authorities:
Key
ABS
BV
DNV
GOST
GL
LR
RINA
Certification Body
American Bureau of Shipping
Bureau Veritas
Det Norske Veritas
Gosudarstvennyy Standart
Germanischer Lloyd
Lloyd's Register
Registro Italiano Navale
Country
United States
France
Norway
Russia
Germany
United Kingdom
Italy
The electrical isolation within a Quantum EIO system modules complies with the
1500 Vac/2250 Vdc 60s from IEEE 802.3 2008.
S1A48993 10/2019
23
140NOC78100 Module Characteristics
Environmental Requirements
Parameter protection
Reference
EN 61131-2 protection class over voltage class
IEC 60527
EN 61131-2
EN 61131-2 operating temperature IEC 60068-2-1 storage temperature
Ab&Ad (cold)
IEC 60068-2-2
Bb&Bd (cold)
IEC 60068-2-1
Ab&Ad (cold) sinusoidal vibration
IEC 60068-2-2
Bb&Bd (cold)
IEC 60068-2-6fC
EN 61131-2
Specification
IP20 protection class 1 category II
0 ... 60° C
-40 ... 85° C operating shock altitude free fall, random
(packaged) free fall, flat drop
(unpackaged) free fall, angled
(unpackaged) relative humidity
(operating) relative humidity
(nonoperating)
IEC 60068-2-27Ea
EN 61131-2
IEC 60068-2-32 test ed., method 1
EN 61131-2
IEC 60068-2-32 test ed., method 1
EN 61131-2
IEC 60068-2-31
IEC 60068-2-78Ca
.5 ... 8.4 Hz at 3.5 mm constant amplitude
8.4 ... 150 Hz at 1g constant acceleration
10 cycles at sweep rate of 1 oct/min
30 g peak, 11 ms, half-sine wave, 3 shocks in each direction (+ and -) for each of the 3 principle axes
0 ... 5000 m maximum during operation. For altitudes >
2000 m, reduce the operating temperature by 6° C for each additional 1000 m.
5 random drops from 1 m onto flat surfaces
2 random drops from 1 m onto flat surfaces
5 drops from 0.1 m onto flat surfaces
5 drops from 0.1 m onto each corner
IEC 60068
93% (+/- 2%, noncondensing) at 60° C for conformally coated modules 140CRA31200C and 140CRP31200C
93% (+/- 2%, noncondensing) at 60° C for conformally coated modules 140CRA31200C and 140CRP31200C
NOTE: The BMXCRA31210 is also available in a coated version.
24
S1A48993 10/2019
140NOC78100 Module Characteristics
Communication Specifications
Introduction
The following specifications describe both the I/O communication and the explicit messaging capacities of the 140NOC78100 control head module.
I/O Communication Specifications
The 140NOC78100 module presents the following I/O communication features:
Communication Type Feature
EtherNet/IP
(CIP Implicit
Messaging) scanner maximum number of devices
Capacity
64 devices (61 devices as scanner + 3 devices as adapter) shared with Modbus TCP maximum message size 511 bytes adapter maximum number of instances 3 adapter instances maximum number of connections 2 connections per instance maximum message size inputs outputs
511 bytes including header
505 bytes excluding header
509 bytes excluding header
Modbus TCP
(Modbus Scanner) maximum number of registers read write maximum number of devices maximum message size read write
125 registers
120 registers
64 devices shared with EtherNet/IP
250 bytes (125 words) excluding header
240 bytes (120 words) excluding header
I/O Data Exchange with the CPU
Feature Capacity Comments maximum total input data size maximum total output data size
4 kb
4 kb
4 kb of data includes user configuration data and overhead. The overhead includes module diagnostic data, data object headers, and the number of headers depending on the user configuration. As a result, the user configurable data size is less than 4 kb, but more than 3.5 kb.
4 kb of data includes user configurable data and overhead. The overhead includes module control data, data object headers, and the number of headers depending on the user configuration. As a result, the user configurable data size is less than 4 kb, but more than 3.5 kb.
S1A48993 10/2019
25
140NOC78100 Module Characteristics
Explicit Messaging Specifications
The 140NOC78100 module presents the following explicit messaging features:
Communication Type
EtherNet/IP
(CIP Explicit Messaging)
Modbus TCP (Modbus
Explicit Messaging)
Feature client server maximum number of simultaneous connections maximum number of concurrent requests maximum number of simultaneous connections maximum messaging size client server maximum number of simultaneous connections maximum number of concurrent requests maximum number of requests that can be transferred to the CPU per scan maximum number of simultaneous connections maximum message size read write
Capacity
16 connections
16 requests, shared with
Modbus TCP
32 connections
1023 bytes
16 connections
16 requests, shared with
EtherNet/IP
12 connections
32 connections
250 bytes (125 words) excluding header
240 bytes (120 words) excluding header
26
S1A48993 10/2019
Quantum EIO
Installing the 140NOC78100 Module
S1A48993 10/2019
Installing the 140NOC78100 Module Chapter 2
Installing the 140NOC78100 Module
Introduction
This chapter describes the installation process of the 140NOC78100 module within a Quantum
EIO system.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Mounting a Quantum EIO-Compatible Module on the Backplane
Quantum EIO-Compatible Module Installation Considerations
Cable Installation
Page
S1A48993 10/2019
27
Installing the 140NOC78100 Module
Mounting a Quantum EIO-Compatible Module on the Backplane
Introduction
Use these instructions to install Quantum and Modicon X80 modules that operate in a Quantum
EIO system:
140CRP31200 remote I/O head module (on the local rack) remote I/O adapter module:
140CRA31200 remote I/O adapter module (on a Quantum remote I/O drop)
BMXCRA312•0 adapter module (on a Modicon X80 remote I/O drop)
140CRA31908 adapter module facilitates the use of S908 hardware and applications in
M580 Ethernet I/O architectures.
140NOC78000 distributed I/O head module (on the local rack)
140NOC78100 control head module (on the local rack)
Grounding Considerations
Do not apply power to a Quantum rack until connections are made at both ends of the Ethernet cable. For example, connect the cable to both the 140CRP31200 and another device (adapter module) or ConneXium dual-ring switch DRS before you turn on the power.
Refer to the Quantum EIO System Planning Guide for details on dual-ring switches (DRSs).
DANGER
ELECTRICAL SHOCK HAZARD
Switch off the power supply to the automation controller stations at both ends of the connection before inserting or removing an Ethernet cable.
Use suitable insulation equipment when inserting or removing all or part of this equipment.
Failure to follow these instructions will result in death or serious injury.
Use fiber-optic cable to establish a communications link when it is not possible to master potential between distant grounds.
28
S1A48993 10/2019
Installing the 140NOC78100 Module
Mounting a Module
Step
1
Action
Hold the module at an angle and mount it on the 2 hooks near the top of the backplane. The figure shows the correct way to hold the module:
2
3
Swing the module down so the connector engages the backplane connector.
Use a Phillips-head screw driver to tighten the screw at the bottom of the module from 2 to 4 in-lbs or from .22 through .45 N•m of torque.
NOTE: The figure above shows a Quantum module being mounted from top to bottom.
Modicon X80 modules mount from bottom to top.
Replacing a Module
You can replace a Quantum EIO module at any time using another module with compatible firmware. The replacement module obtains its operating parameters over the backplane connection from the CPU. The transfer occurs immediately at the next cycle to the device.
The operating parameters that the CPU sends to a replacement module do not include any parameter values that were edited in the original module using explicit messaging SET commands.
S1A48993 10/2019
29
Installing the 140NOC78100 Module
Quantum EIO-Compatible Module Installation Considerations
Introduction
Observe the following guidelines when you install these Quantum and Modicon X80 modules in a
Quantum EIO system:
140CRP31200 remote I/O head module (on the local rack) remote I/O adapter module (on the remote I/O drop)
140CRA31200 module on a Quantum drop
140CRA31908 adapter module on a Quantum drop
BMXCRA312•0 module on a Modicon X80 drop
140NOC78000 distributed I/O head module (on the local rack)
140NOC78100 control network head module (on the local rack)
Grounding Considerations
DANGER
ELECTRICAL SHOCK HAZARD
Switch off the power supply to the automation controller stations at both ends of the connection before inserting or removing an Ethernet cable.
Use suitable insulation equipment when inserting or removing all or part of this equipment.
Failure to follow these instructions will result in death or serious injury.
Use fiber-optic cable to establish a communications link when it is not possible to master potential between distant grounds.
NOTE: Refer to the ground connections information in
Electrical installation guide
.
30
S1A48993 10/2019
Installing the 140NOC78100 Module
Installation
You can apply power to the Quantum EIO controller rack after the 140CRP31200 head module or adapter module is inserted:
Successful installation:
Initialization is finished.
Interconnections to other modules are validated (drop adapter module only).
Unsuccessful installation:
Initialization does not finish.
Interconnections to other modules are not validated (adapter modules only).
You can see the status of the installation on the LED display.
NOTE: Because all modules on the local rack are initialized when power is applied, the
140CRP31200 remote I/O head module can only validate the interconnections with 140NOC78000 and 140NOC78100 head modules after these modules have been initialized. Therefore, the adapter module waits until its queries about the interconnected port information are answered.
NOTE: These guidelines pertain to the installation of a single head module or adapter module, not the entire network. For network power-up guidelines, refer to Quantum EIO, System Planning
Guide .
S1A48993 10/2019
31
Installing the 140NOC78100 Module
Cable Installation
Introduction
We recommend the use of shielded twisted 4-pair CAT5e (10/100 Mbps) cables for the following connection types in a Quantum EIO system:
the interlink connection between 140NOC78•00 modules and a 140CRP31200 remote I/O head module on the local rack
the connection between 140NOC78•00 modules and DRSs on the main ring the connection between a 140NOC78000 distributed I/O head module and an isolated or extended distributed I/O network
NOTE: We recommend that copper shielded twisted 2-pair CAT5e (10/100 Mbps) and CAT6
(10/100/1000 Mbps) cables not be used. Rather, we recommend that you use copper shielded twisted 4-pair CAT5e (10/100 Mbps and CAT6 (10/100/1000 Mbps) cables.
NOTE: We recommend the use of CAT6 (10/100/1000 Mbps) copper shielded twisted 4-pair cables for the connection between a 140NOC78100 control head module and a control network.
NOTE: Regarding shielded twisted 4-pair CAT5e (10/100 Mbps) cables, we recommend
ConneXium 490NT•000•• cables.
32
S1A48993 10/2019
Installing the 140NOC78100 Module
Connections Between Devices
This example shows the maximum cable lengths between remote I/O and distributed I/O devices and a control network in a Quantum EIO installation.
NOTE: Use copper cable for distances less than or equal to 100 m. User fiber cable for distances greater than 100 m.
2 3 10
5
4
200
656.17
6
4
8 9 8
7
1 140CRP31200 remote I/O head module to manage remote I/O devices
2 140NOC78000 distributed I/O head module to manage distributed I/O devices
3 140NOC78100 control head module to provide transparency between the device network and the control network (10)
4 DRSs (with copper and fiber ports): These DRSs extend the distance between devices (up to 15 km).
5 Ethernet distributed I/O sub-ring
6 fiber portion of the main ring
7 copper portion of the main ring
8 Ethernet remote I/O drops on the main ring
9 DRS (with copper ports): This DRS serves to extend the distance between other devices.
10 control network
S1A48993 10/2019
33
Installing the 140NOC78100 Module
34
S1A48993 10/2019
Quantum EIO
Planning and Designing Control Network Interconnectivity
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity Chapter 3
Planning and Designing Control Network Interconnectivity
Introduction
In a Quantum EIO system, you can design an architecture that contains both remote I/O and distributed I/O devices operating on the same Ethernet remote I/O network.
Through the use of a control head module installed on the local rack, you can connect a new or existing Ethernet control network to a device network (containing remote I/O and distributed I/O devices).
The control network module is configured with Control Expert and communicates with the following devices in a device network:
PLC
140NOC78000 distributed I/O head module
remote I/O and distributed I/O devices
HMI devices
SCADA programs
NOTE: The architectures described in this document have been tested and validated in various scenarios. If you intend to use architectures different than the ones described in this document, test and validate them thoroughly before implementing.
What Is in This Chapter?
This chapter contains the following topics:
Topic
How the Control Network Works within a Quantum EIO System
Rules for Interconnectivity
Connecting a Control Network to a Quantum EIO System
Transparency Functionality
Page
S1A48993 10/2019
35
Planning and Designing Control Network Interconnectivity
How the Control Network Works within a Quantum EIO System
Introduction
The 140NOC78100 control head module is mainly responsible for providing network transparency between devices located on a device network (including remote I/O and/or distributed I/O devices), an extended distributed I/O network, and a control network, while preserving determinism for remote I/O devices on the device network.
The 140NOC78100 module also:
operates in a redundant network that uses the RSTP protocol
configures IP parameters and device configuration files for I/O devices supports Hot Standby functionality operates with other Quantum EIO head modules (140CRP31200, 140NOC78000) or operates without being interlinked with these head modules on the local rack
36
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
The following graphic shows a control network [10] connected to a Quantum EIO system via interlink of the 140NOC78100 control head module with the 140NOC78000 distributed I/O head module and the 140CRP31200 remote I/O head module on the local rack. The 140NOC78100 module provides network transparency between the control network and the device network.
10
4
3
11
5
9
8
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module interlinked with the 140CRP31200 module
3 140NOC78100 control head module interlinked with the 140NOC78000 module on the local rack
4 distributed I/O sub-ring
5 dual-ring switch (DRS) configured for copper-to-fiber and fiber-to-copper transition on the main ring
(connecting the distributed I/O sub-ring and the distributed I/O cloud to the main ring)
6 distributed I/O cloud
7 remote I/O drop on the main ring
8 remote I/O drops on the remote I/O sub-ring
9 DRS on the main ring (connecting the remote I/O sub-ring to the main ring)
10 control network (connected by the 140NOC78100 module)
11 main ring
S1A48993 10/2019
37
Planning and Designing Control Network Interconnectivity
What Comprises a Network?
IP addresses are within one subnet.
Devices communicate to each other directly.
Target addresses outside of the subnet are directed to a router.
How Does Routing Work Between Networks?
Routers subdivide large networks into smaller networks and subnetworks. The netmask assigns the IP address of the individual devices to a particular subnetwork.
The division into subnetworks with the aid of the netmask is performed in much the same way as the division of the network addresses (net id) into classes A to C.
The bits of the host address (host ID) that represent the mask are set to 1. The remaining bits of the host address in the netmask are set to 0 (see the following examples).
Example of a netmask:
38
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Example of IP address with subnetwork assignment when the above subnet mask is applied:
S1A48993 10/2019
39
Planning and Designing Control Network Interconnectivity
Example of how the network mask is used:
In a large network, it is possible that routers separate the fieldbus network from the extended network. How does addressing work in such a case?
40
A control network
B fieldbus network
C extended network
D router
The control network (A) wants to send data to the extended network (C). A knows C’s IP address and also knows that the router (D) knows the way to C from the fieldbus network (B).
A, therefore, puts its message in an envelope and writes C’s IP address as the destination address.
For the source address, A writes its own IP address on the envelope.
A then places this envelope in a second one with D’s MAC address as the destination and its own
MAC address as the source. This process is comparable to going from layer 3 to layer 2 of the
ISO/OSI base reference model.
Finally, A puts the entire packet into the mailbox. This is comparable to going from layer 2 to layer
1, i.e., to sending the data packet over the Ethernet.
D receives the letter and removes the outer envelope. From the inner envelope, it recognizes that the letter is meant for C. D places the inner envelope in a new outer envelope and searches its address list (the ARP table) for C’s MAC address. D writes C’s MAC address on the outer envelope as the destination address and its own MAC address as the source address. D then places the entire data packet in the mail box.
C receives the letter and removes the outer envelope, and finds the inner envelope with A’s IP address. Opening the inner envelope and reading its contents corresponds to transferring the message to the higher protocol layers of the ISO/OSI layer model.
C would now like to send a reply to A. C places its reply in an envelope with A’s IP address as destination and its own IP address as source. But where does C send the answer because it did not receive A’s MAC address, which was lost when D replaced the outer envelope.
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
In the MIB, C finds D listed under the variable hmNetGateway-IPAddr as a means of communicating with A. C therefore puts the envelope with the IP addresses in a further envelope with D’s MAC destination address.
The letter now travels back to A via D, the same way the first letter traveled from A to C.
The following table details the steps in the Control Expert DTM:
Step
1
Action
Double-click the 140NOC78100 module in the DTM Browser. Select TCP/IP in the Channel
Properties list, and set the 140NOC78100 module’s control network address and control network gateway.
Click Apply to save changes, or click OK to save changes and close the window.
S1A48993 10/2019
41
Planning and Designing Control Network Interconnectivity
Step
2
Action
Select Services to view the Ethernet services that you can enable or disable. In the right pane, select Enabled for the IP Forwarding service.
42
Click Apply to save changes, or click OK to save changes and close the window.
S1A48993 10/2019
Step
3
Planning and Designing Control Network Interconnectivity
Action
Select IP Forwarding in the Services list to access the IP forwarding service parameters. Set the
IP Address and the Sub-Network Mask for the Control Network, the Fieldbus Network, and the
Extended Network.
S1A48993 10/2019
Click Apply to save changes, or click OK to save changes and close the window.
43
Planning and Designing Control Network Interconnectivity
Step
4
Action
Double-click the 140NOC78000 module in the DTM Browser. Select TCP/IP in the Channel
Properties list, and set the 140NOC78000 module’s fieldbus address and gateway address.
5
Click Apply to save changes, or click OK to save changes and close the window.
Confirm that all fieldbus devices are set with the proper gateway address.
NOTE: If they are defined via DHCP from the 140NOC78000 module, cycle power the devices to configure the new gateway address. If they are defined in the device or from an external address server, reconfigure the gateway address as required by the device.
44
Click Apply to save changes, or click OK to save changes and close the window.
S1A48993 10/2019
Step
6
Planning and Designing Control Network Interconnectivity
Action
Double-click the 140CRP31200 module on the local rack. Select the IPConfig tab and confirm that the fieldbus address and gateway address are set. When the system starts, the EIO drops are provided new addresses.
NOTE: If previously configured, cycle power the distributed I/O devices to reconfigure with the new gateway address.
7 Confirm that the PCs on the control network are set with a proper IP address and subnet mask to access the 140NOC78100 module’s IP forwarding service.
S1A48993 10/2019
45
Planning and Designing Control Network Interconnectivity
Step
8
Action
Finally, to access devices on the fieldbus network, add a routing entry in the PC’s routing table to define the 140NOC78100 module as the default gateway to the fieldbus network.
Multiple Ethernet Cards in a PC
A PC Ethernet card connected to a network on the 140NOC78100 module can communicate with devices within that subnet. To communicate with devices on the other two 140NOC78100 networks, set the 140NOC78100 module’s IP address as the Ethernet card’s default gateway.
If you have more than one Ethernet card installed in the PC (each with a configured IP address on a particular subnet and a configured default gateway) and you try to communicate with a device that is not on the 140NOC78100 module network (or any network not assigned to the Ethernet cards in the PC), the application does not know what default gateway on which Ethernet card to use.
To fix this, add a static route to your PC for each of the other 140NOC78100 module networks that you want to access from the 140NOC78100 module network to which you are connected. Use the route -p to create a persistent route across system boots.
Example: c:\Route ADD 192.153.0.0 mask 255.255.0.0 172.16.30.1
c:\Route ADD 192.168.0.0 mask 255.255.0.0 172.16.30.1
Where:
192.153.0.0 is the extended network in our example.
192.168.0.0 is the distributed I/O network in our example.
172.16.30.1 is the IP address of the 140 NOC 781 00 module on the control network.
NOTE: Do not use multiple default routes.
46
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
The following figure shows the IP forwarding service configuration in the 140NOC78100 module for the previous example.
S1A48993 10/2019
47
Planning and Designing Control Network Interconnectivity
How is the 140NOC78100 Module’s Default Gateway Used?
As previously stated, if a datagram is targeted outside of a network, the datagram is sent to the default gateway. In a Quantum EIO system, the default gateway is the 140NOC78100 module. If the datagram is not targeted to a device in one of the 3 networks known by the 140NOC78100 module, the datagram is sent to the 140NOC78100 module’s default gateway. In this example, the default gateway is a router further up in the Ethernet infrastructure.
1
2
3
3
1 extended network (example: 192.153.x.x)
2 distributed I/O network (example: 192.168.x.x)
3 control network (example: 172.16.x.x)
48
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
7
9
1 extended network (example: 192.153.x.x)
2 distributed I/O network (example: 192.168.x.x)
3 control network (example: 172.16.x.x)
4 router to other networks (example: 131.158.x.x)
5 140CRP31200 remote I/O head module
6 140NOC78000 distributed I/O head module
7 140NOC78100 control head module
8 dual-ring switch (DRS) on main ring connected to distributed I/O network and remote I/O sub-ring
9 remote I/O sub-ring
S1A48993 10/2019
49
Planning and Designing Control Network Interconnectivity
Rules for Interconnectivity
Introduction
The local rack within a Quantum EIO system can have different combinations of Ethernet head modules. This topic describes the types of networks created when the 140NOC78100 control head module interconnects with other head modules on the local rack.
NOTE: Refer to the Local Rack Head Module Connectivity topic in the Quantum EIO System
Planning Guide for topology rules regarding installing and interlinking the head modules on the local rack.
NOTE: Refer to the Selecting the Correct Topology topic in the Quantum EIO System Planning
Guide for details about the network types described on the following pages.
NOTE: Enable and configure the IP forwarding service
see page 151
in the 140NOC78100 module to provide network transparency in the network types described on the following pages.
NOTE: Refer to the
see page 69
chapter to configure the 140NOC78100 module for use in the network types described on the following pages.
A local rack contains one 140CRP31200 remote I/O head module and up to 6 communication modules (only one of which can be a 140NOC78100 module). The 140NOC78100 module can be interlinked with other head modules on the local rack for various network combinations:
140NOC78100 Module Interconnectivity the 140NOC78100 module interlinked with the 140CRP31200 module
Network Type
remote I/O network
— and — control network the 140NOC78100 module interlinked with up to three 140NOC78000 modules and the
140CRP31200 module
device network
— and — control network one 140NOC78000 modules interlinked with the
140NOC78100 module
of the
NOTE: If you to install up to three
140NOC78000 modules, please refer to the
Quantum EIO System Planning Guide for bandwidth guidelines.
the 140NOC78100 module interlinked with up to three 140NOC78000 modules
extended distributed I/O network
— and — control network independent distributed I/O network
Description provides network transparency between the control network and the remote I/O network, while preserving network determinism provides network transparency between the control network and the device network, while preserving network determinism provides network transparency between the control network and the extended distributed I/O network provides network transparency between the control network and up to
3 independent distributed I/O networks
50
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Interlinking the 140NOC78100 Module in a Remote I/O Network
To provide network transparency between the control network and the remote I/O network, perform the following steps:
Step
1
2
3
4
5
Action
Install one 140CRP31200 remote I/O head module and one 140NOC78100 control head module on the local rack.
Connect the
interlink port ( see page 22 ) (ETH 2) of the 140NOC78100 module to the
interlink port (ETH 2) of the 140CRP31200 module to provide network transparency between the control network and the Ethernet remote I/O network.
Connect the start of the main ring to the
140CRP31200 module.
device network port (ETH 3 or ETH 4) of the
Connect the end of the main ring to the
140CRP31200 module.
device network port (ETH 3 or ETH 4) of the
Connect the
control network port ( see page 22
140NOC78100 module to the control network.
(ETH 3 or ETH 4) of the
S1A48993 10/2019
51
Planning and Designing Control Network Interconnectivity
5
4
3
4
52
4 4 4
3
1 140CRP31200 remote I/O head module
2 140NOC78100 control head module interlinked with the 140CRP31200 module on the local rack
3 main ring
4 Ethernet remote I/O drops on the main ring
5 control network
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Interlinking the 140NOC78100 Module in a Device Network
To provide network transparency between the control network and a device network, perform the following steps:
Step
1
2
3
4
5
6
7
Action
Install one 140CRP31200 remote I/O head module, up to three 140NOC78000 distributed I/O head modules (that can be interlinked with the 140CRP31200 module), one 140NOC78100 control head module on the local rack, and an additional
140NOC78000 module (that can be interlinked with the 140NOC78100 module).
Connect the interlink port (ETH 2) of the 140NOC78000 module to the
(ETH 2) of the 140CRP31200 module.
interlink port
Connect the interlink port (ETH 2) of the 140NOC78100 module to the device network/interlink port (ETH 3) of the 140NOC78000 module.
Connect the start of the main ring to the
140CRP31200 module.
device network port (ETH 3 or ETH 4) of the
Connect the end of the main ring to the
140CRP31200 module.
device network port (ETH 3 or ETH 4) of the
Connect DRSs to the main ring for distributed I/O sub-rings and/or distributed I/O clouds.
Refer to the Predefined Configuration Files topic in the Quantum EIO System
Planning Guide for details on installing DRSs and distributed I/O devices.
Connect the control network port the control network.
(ETH 3 or ETH 4) of the 140NOC78100 module to
S1A48993 10/2019
53
Planning and Designing Control Network Interconnectivity
10
3
11
9
4
5
8
54
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module (interlinked with the 140CRP31200 module to support the device network)
3 140NOC78100 control head module (interlinked with the 140NOC78000 module to provide network transparency between the control network and the device network)
4 distributed I/O sub-ring
5 DRSs with a predefined configuration file to support copper-to-fiber and fiber-to-copper transitions on the main ring
6 distributed I/O cloud
7 remote I/O drop on the main ring
8 remote I/O drops on a remote I/O sub-ring
9 DRS connecting the remote I/O sub-ring to the main ring
10 control network
11 main ring
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Interlinking the 140NOC78100 Module in an Extended Distributed I/O Network
To provide network transparency between the control network and an extended distributed I/O network, perform the following steps:
Step
1
2
3
4
5
6
7
8
Action
Install one 140CRP31200 remote I/O head module, up to three 140NOC78000 distributed I/O head modules (that can be interlinked with the 140CRP31200 module), one 140NOC78100 control head module on the local rack, and an additional 140NOC78000 (that can be interlinked with the 140NOC78100 module).
Connect the interlink port (ETH 2) of the 140NOC78000 module to the interlink port (ETH 2) of the 140CRP31200 module.
Connect the to the device network/interlink port (ETH 3) of the 140NOC78000 module service/extend port (ETH 1) of the 140NOC78100 module.
Connect the device network port distributed I/O network.
(ETH 4) of the 140NOC78000 to your existing
Connect the control network port module to the control network.
(ETH 3 or ETH 4) of the 140NOC78100
Connect the start of the main ring to the of the 140CRP31200 module.
device network port (ETH 3 or ETH 4)
Connect the end of the main ring to the the 140CRP31200 module.
device network port (ETH 3 or ETH 4) of
Connect DRSs to the main ring for distributed I/O sub-rings and/or distributed I/O clouds.
Refer to the Predefined Configuration Files topic in the Quantum EIO System
Planning Guide for details on installing DRSs and distributed I/O devices.
S1A48993 10/2019
55
Planning and Designing Control Network Interconnectivity
3
11
5
4
56
6
10 8
6
9
7
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module (interlinked with the extend port of the 140NOC78100 module to support the extended distributed I/O network and also interlinked with the 140CRP31200 module to support the device network)
3 140NOC78100 control head module (interlinked with the 140NOC78000 module (2) to provide network transparency between the device network and the control network)
4 extended distributed I/O network
5 distributed I/O sub-ring
6 DRSs with a predefined configuration file to support copper-to-fiber and fiber-to-copper transitions on the main ring
7 distributed I/O cloud
8 remote I/O drop on the main ring
9 remote I/O drops on the remote I/O sub-ring
10 DRS connecting the remote I/O sub-ring to the main ring
11 control network
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Interlinking the 140NOC78100 Module in an Independent Distributed I/O Network
To provide network transparency between the control network and an independent distributed I/O network, perform the following steps:
Step
1
2
3
4
5
6
7
8
Action
Install one 140CRP31200 remote I/O head module, up to three 140NOC78000 distributed I/O head modules (that can be interlinked with the 140CRP31200 module), one 140NOC78100 control head module on the local rack and an additional 140NOC78000 module (that can be interlinked with the
140NOC78100 module).
Connect the interlink port (ETH 2) of the 140CRP31200 module to the interlink port (ETH 2) of the 140NOC78000 module.
Connect the interlink port (ETH 2) of a second 140NOC78000 module to the interlink port (ETH 2) of the 140NOC78100 module.
Connect the device network port distributed I/O network.
(ETH 4) of the 140NOC78000 to your existing
Connect the control network port module to the control network
(ETH 3 or ETH 4) of the 140NOC78100
Connect the start of the main ring to the of the 140CRP31200 module.
device network port (ETH 3 or ETH 4)
Connect the end of the main ring to the the 140CRP31200 module.
device network port (ETH 3 or ETH 4) of
Connect DRSs to the main ring for distributed I/O sub-rings and/or distributed
I/O clouds.
Refer to the Predefined Configuration Files topic in the Quantum EIO System
Planning Guide for details on installing DRSs and distributed I/O devices.
S1A48993 10/2019
57
Planning and Designing Control Network Interconnectivity
12
6
3 4 5
58
7
11 9
7
10
8
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module (interlinked with the 140CRP31200 module
3 140NOC78100 control head module
4 140NOC78000 distributed I/O head module (interlinked with the 140NOC78100 module to provide network transparency between the independent distributed I/O network and the control network)
5 independent distributed I/O network (participates only in the control network portion of a Quantum EIO system)
6 distributed I/O sub-ring
7 DRSs with a predefined configuration file to support copper-to-fiber and fiber-to-copper transitions on the main ring
8 distributed I/O cloud
9 remote I/O drop on the main ring
10 remote I/O drops on the remote I/O sub-ring
11 DRS connecting the remote I/O sub-ring to the main ring
12 control network
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Connecting a Control Network to a Quantum EIO System
Introduction
A 140NOC78100 control head module provides multiple network connectivity options, while preserving network determinism:
non-redundant (single attachment) — provides a single chain connection from the control network port on the 140NOC78100 module installed on the local rack to an Ethernet port on a switch located on the control network.
A single chain connection does not provide redundancy.
Use copper shielded twisted 4-pair CAT6 (10/100/1000 Mbps) cable to connect the
140NOC78100 module to the switch on the control network. The distance to the switch can only be less than or equal to 100 m.
redundant (RSTP) — provides cable redundancy by using a daisy chain loop topology from the control network port on the 140NOC78100 module to a port on an Ethernet managed dual-ring switch (DRS) located on the control network. This DRS is linked to a second DRS, which completes the daisy chain loop by connecting back to the 140NOC78100 module.
Use copper shielded twisted 4-pair CAT6 (10/100/1000 Mbps) cable between the
140NOC78100 module and the 2 DRSs and between the DRSs as well. The distance to the
DRSs and between the DRSs can only be less than or equal to 100 m.
NOTE: We recommend that copper shielded twisted 2-pair CAT5e (10/100 Mbps) and CAT6
(10/100/1000 Mbps) cables not be used. Rather, we recommend that you use copper shielded twisted 4-pair CAT5e (10/100 Mbps and CAT6 (10/100/1000 Mbps) cables.
NOTE: The switch used in a non-redundant control network type does not have to be a managed dual-ring switch (DRSs).
Connecting a Non-redundant Control Network
If your control network does not require redundancy, follow the steps below to provide network transparency between the control network and your desired network(s):
Step
1
2
3
4
Action
Install a 140NOC78100 control head module on the local rack. Install a 140CRP31200 remote
I/O head module and 140NOC78000 distributed I/O head modules (the number of which depends upon your desired network) on the local rack.
Interlink the head modules, based on your desired network(s)
.
NOTE: Use copper shielded twisted 4-pair CAT5e (10/100 Mbps) cable to interlink the head modules on the local rack.
Install an Ethernet switch on the control network a distance equal to or less than 100 m from the
140NOC78100 module on the local rack.
NOTE: The switch does not have to be a managed dual-ring switch (DRS).
Connect the control network port (ETH 3 or ETH 4) of the 140NOC78100 module — using copper shielded CAT6 (10/100/1000 Mbps — to an Ethernet port on the switch located on the control network.
S1A48993 10/2019
59
Planning and Designing Control Network Interconnectivity
The following graphic displays an Ethernet remote I/O network connected to a control network. The
140NOC78100 control head module on the local rack, which is connected to a switch on the control network, provides network transparency between the remote I/O network and the control network.
11
4
3
10
5
9
8
60
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module (interlinked with the 140CRP31200 module to support the device network)
3 140NOC78100 control head module (interlinked with the 140NOC78000 module to provide network transparency between the control network and the device network)
4 distributed I/O sub-ring
5 DRSs with a predefined configuration file to support copper-to-fiber and fiber-to-copper transitions on the main ring
6 distributed I/O cloud
7 remote I/O drop on the main ring
8 remote I/O drops on a remote I/O sub-ring
9 DRS connecting the remote I/O sub-ring to the main ring
10 main ring
11 control network
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Connecting a Redundant Control Network
If your control network requires redundancy, follow the steps below to provide network transparency between the control network and your desired network(s):
Step
1
2
3
4
Action
Install a 140NOC78100 control head module on the local rack. Install a
140CRP31200 remote I/O head module and 140NOC78000 distributed I/O head modules (the number of which depends upon your desired network) on the local rack.
Interlink the head modules, based on your desired network(s)
.
NOTE: Use copper shielded twisted 4-pair CAT5e (10/100/1000 Mbps) cable to interlink the head modules on the local rack.
Install and connect 2 Ethernet managed dual-ring switches (DRSs via copper shielded twisted 4-pair CAT5e (10/100 Mbps) cable on the control network a distance equal to or less than 100 m from each other and from the 140NOC78100 module on the local rack.
Connect one of the control network ports (ETH 3 or ETH 4) of the 140NOC78100 module via copper shielded twisted 4-pair CAT5e (10/100 Mbps) cable to a port on the DRS.
Connect the other control network port (ETH 3 or ETH 4) of the 140NOC78100 module via copper shielded twisted 4-pair CAT5e (10/100 Mbps) cable to another port on the DRS.
NOTE: For DRS installation and configuration details, refer to the topic in the Quantum EIO System Planning Guide .
Predefined Configuration Files
S1A48993 10/2019
61
Planning and Designing Control Network Interconnectivity
The following graphic displays an Ethernet remote I/O network connected to a redundant control network. The 140NOC78100 control head module on the local rack, which is connected to 2 separate DRSs on the control network, provides network transparency between the remote I/O network and the control network.
11
4
3
10
5
9
8
62
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module (interlinked with the 140CRP31200 module to support the device network)
3 140NOC78100 control head module (interlinked with the 140NOC78000 module to provide network transparency between the control network and the device network)
4 distributed I/O sub-ring
5 DRSs with a predefined configuration file to support copper-to-fiber and fiber-to-copper transitions on the main ring
6 distributed I/O cloud
7 remote I/O drop on the main ring
8 remote I/O drops on a remote I/O sub-ring
9 DRS connecting the remote I/O sub-ring to the main ring
10 main ring
11 control network with 2 DRSs that provide redundancy
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
Transparency Functionality
Introduction
The 140NOC78100 control head module uses an IP forwarding service to provide network transparency between networks in a Quantum EIO system.
The IP forwarding service of the 140NOC78100 control head module is the interface between the control network and the other network (i.e., device network, extended distributed I/O network), with which you want to provide network transparency.
Use Control Expert to configure the IP forwarding service (
see page 151
NOTE: In configurations that use the IP forwarding service (the 140NOC78100 control head module bridging the control network to the distributed I/O network via the 140NOC78000 distributed I/O head module), we recommend that you use the 140NOC78100 module’s IP address to download the Control Expert application to the PLC.
If you download the application via the 140NOC78000 module, the 140NOC78100 resets at the end of the download, which resets the connection between Control Expert and the 140NOC78000 module. See the following figure showing the IP forwarding service feature in the 140NOC78100 module used to connect to the 140NOC78000 module.
4
1 2 3
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module
3 140NOC78100 control head module
4 Control Expert
S1A48993 10/2019
63
Planning and Designing Control Network Interconnectivity
How the IP Forwarding Service Manages Transparency between Networks
In order for the 140NOC78100 control I/O head module to manage transparency between networks, interlink the head modules on the local rack.
Connect the
see page 22
) of the 140CRP31200 remote I/O head module (ETH 2) or
the 140NOC78000 distributed I/O head module (ETH 2 or ETH 3) to the the 140NOC78100 module, as shown in this picture: interlink port (ETH 2) of
64
1 140CRP31200 remote I/O head module
2 140NOC78000 distributed I/O head module (interlinked with the 140CRP31200 module to support a device network)
3 140NOC78100 control head module (interlinked with the 140NOC78000 module to provide transparency between the control network and the device network)
IP Forwarding Topology
As an example, suppose you want to provide transparency between the control network and the device network:
On the control network, host A exists with a MAC address of aa-aa-aa-aa-aa-aa and an IP address of A.A.A.0.
On the device network, host B exists with a MAC address of bb-bb-bb-bb-bb-bb and an IP address of B.B.B.0.
In order for host A and B to communicate with each other, you need to connect the control network and device network physically, as well as logically. The IP forwarding service in the 140NOC78100 is the interface for the network connection.
The IP forwarding service gathers 3 types of information:
physical (example: 100BASE-T)
data link (example: MAC address) network (example: IP address)
The IP forwarding service now has and it has interface A with an IP address of A.A.A.1 on the control network, interface B with an IP address of B.B.B.1 on the device network.
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
With this information, the routing table used for IP address forwarding looks like this:
Network
A.A.A.0 (control network)
B.B.B.0 (device network)
Interface
A.A.A.1
B.B.B.1
Now that you have established the IP forwarding service (i.e., gateway), add the IP address forwarding information to hosts A and B, which allows the hosts to send packets beyond their own
IP network.
S1A48993 10/2019
65
Planning and Designing Control Network Interconnectivity
At this point, you can assume that host A is aware of host B and that host A wants to send a packet
(example: Modbus message) to host B. Host A (IP address A.A.A.A sends the message to interface A (IP address A.A.A.1), which then sends it to interface B (IP address B.B.B.1) and finally to host B (IP address B.B.B.B) (as shown in the following graphic:
3 host A control network
IP address: A.A.A.A
11
9
12 host B device network
IP address: B.B.B.B
8
10
4 7
5
6
5
66
1 140CRP31200 remote I/O head module on the local rack
2 140NOC78000 distributed I/O head module (interface B)
3 140NOC78100 control head module (interface A)
4 DRS (with a C2 predefined configuration file loaded) connecting the distributed I/O sub-ring (5) and the distributed I/O cloud (6) to the main ring (8)
5 distributed I/O sub-ring
6 distributed I/O cloud
S1A48993 10/2019
Planning and Designing Control Network Interconnectivity
7 remote I/O drop on the main ring
8 main ring
9 control network (host A)
10 device network (host B)
11 control network (host A) with IP address A.A.A.A sends the message to interface A (140NOC78100 module) with IP address A.A.A.1
12 interface B (140NOC78000 module) sends the message to the device network (host B) with IP address
B.B.B.1
S1A48993 10/2019
67
Planning and Designing Control Network Interconnectivity
68
S1A48993 10/2019
Quantum EIO
Configuring the 140NOC78100 Module
S1A48993 10/2019
Configuring the 140NOC78100 Module Chapter 4
Configuring the 140NOC78100 Module
Introduction
This chapter shows you how to use Control Expert programming software to select and configure the 140NOC78100 head module on the local rack.
NOTE: The instructions presented in this chapter include specific choices made for a sample project. Your Control Expert project may include different choices that are appropriate for your specific configuration.
What Is in This Chapter?
This chapter contains the following sections:
4.4
4.5
4.6
4.7
Section
4.1
4.2
4.3
Topic
Creating a Project in Control Expert
The Control Expert FDT/DTM Interface
Hardware Catalog
Channel Properties
Ethernet Services
Security
Configuring the 140 NOC 78• 00 Head Module as an EtherNet/IP Adapter
Page
S1A48993 10/2019
69
Configuring the 140NOC78100 Module
Creating a Project in Control Expert Section 4.1
Creating a Project in Control Expert
Overview
This section shows you how to add modules, including the 140NOC78100 control head module, to your project, using Control Expert.
What Is in This Section?
This section contains the following topics:
Topic
Creating a Project in Control Expert
Configuring the Size and Location of Inputs and Outputs
Page
70
S1A48993 10/2019
Configuring the 140NOC78100 Module
Creating a Project in Control Expert
Introduction
You may have already created a project in Control Expert and installed a power supply and a
140CRP31200 remote I/O head module. If so, jump to the Adding a 140NOC78100 Control Head
Module... topic
Expert project and add the following components:
see page 73
) If not, the following pages show you how to create a new Control
a CPU a power supply a 140NOC78100 control head module
NOTE: To add the power supply and a 140CRP31200 module to the local rack in Control Expert, refer to the Quantum EIO Remote I/O Modules Installation and Configuration Guide .
Creating and Saving a New Control Expert Project
The following steps describe the creation of a project:
Step
1
2
3
Action
Open Control Expert.
In the Control Expert main menu, select File → New....
The New Project window opens displaying a list of Schneider Electric controller types.
In the New Project window, expand the Quantum node and select a CPU. In this example, select the
140 CPU 651 60 controller:
S1A48993 10/2019
71
Configuring the 140NOC78100 Module
Step
4
Action
Click OK. Control Expert displays the Project Browser, below.
5
6
To save the project, select File → Save. The Save As dialog opens.
In the Save As dialog, type in a File name —which will be the name of your Control Expert project — then click Save. Control Expert saves your project to the specified path location.
NOTE: You can change the default location Control Expert uses to store project files. Before saving your project:
1 Select Tools → Options. The Options Management window opens.
2 In the left pane, navigate to Options → General → Paths.
3 In the right pane, type in a new path location for the Project path. You can also edit the:
Import/Export file path
XVM path
Project settings templates path
4 Click OK to close the window and save your path edits.
Adding a Power Supply to the New Control Expert Project
The next step is to add a power supply to your Control Expert project:
Step
7
Action
In the Project Browser, double click Local Bus. Control Expert displays both the:
Local Bus window with the selected CPU in the second position, and
Hardware catalog displaying the Local Bus tab, below:
72
S1A48993 10/2019
Step
8
Configuring the 140NOC78100 Module
Action
In the Hardware catalog, under the Supply node, use your mouse to select then drag a
140 CPS 111 00 power supply to a position in the rack — in this example, slot 1.
9 In the File menu, select Save, to save your edits.
NOTE: Schneider Electric recommends that you periodically save your changes as you make edits.
Adding a 140NOC78100 Control Head Module to the New Control Expert Project
Next, add a 140NOC78100 control head module to your project:
Step
10
Action
Returning to the Hardware catalog, under the Communication node, use your mouse to select then drag a 140NOC78100 control head module to an open slot in the rack — in this example, slot 5.
When you drop the module into the rack, Control Expert opens the communication module
Properties window.
S1A48993 10/2019
73
Configuring the 140NOC78100 Module
Step
11
Action
In the General tab of the module properties window, Control Expert assigns a the device an alias name — in this example, Q_NOC78100. You can type in a name to change the default alias name.
74
12
When you change the alias name, Control Expert changes the base input and output type and variable names to match the edited alias name.
NOTE:
Schneider Electric recommends that you assign a unique alias name to each communication module. This practice helps you distinguish between modules of the same type.
No other configuration needs to be — or can be — performed in the tabs of this window. All other pages are read-only.
In the File menu, select Save to save your edits.
S1A48993 10/2019
Step
13
Configuring the 140NOC78100 Module
Action
Click OK to close the Properties window. The Local Bus now displays the modules you have added:
14
15
The next step is to configure the located memory space in the CPU for the 140NOC78100 module’s inputs and outputs
.
Open the DTM Browser in Control Expert to configure the DTM parameters of the
140NOC78100 module by clicking Tools → DTM Browser.
S1A48993 10/2019
75
Configuring the 140NOC78100 Module
Configuring the Size and Location of Inputs and Outputs
Overview
Use the Configuration tab of the 140NOC78100 control head module’s Properties window to configure the:
size and starting position of inputs size and starting position of outputs
The following steps present one example of how to configure the size and location of inputs and outputs. Your own project configuration may differ.
Setting Input and Output Memory Addresses and Naming the Module
The Properties window opens when you double-click the left mouse button on the image of the
140NOC78100 module in either the Local Bus window or the Project Browser.
When you select the Configuration tab, it displays the network — or Alias — name. This is the name assigned to the network channel when you added the 140NOC78100 module to the project.
Use the Configuration page to edit the communication module inputs and outputs, as follows:
76
S1A48993 10/2019
Configuring the 140NOC78100 Module
To input the above settings, take the following steps:
Step
1
2
3
Action
In the module’s Properties window, select the Configuration tab.
Type in the size and starting position of the inputs and outputs, as follows:
In the Inputs area:
In the %MW index field, type in a starting address for inputs — in this example: 1.
In the Max size field, type in the maximum number of 16-bit words dedicated to inputs — in this example:16.
In the Outputs area:
In the %MW index field, type in a starting address for outputs — in this example: 17.
In the Max size field, type in the maximum number of 16-bit words dedicated to outputs — in this example: 16.
Notes:
The inputs and outputs can be located at any available address and do not need to be
located in adjacent areas. Confirm that the space allocated to inputs and outputs does not overlap.
Control Expert automatically reserves space for two arrays of 32 bytes, as follows:
for connection health bits, located at the beginning of the space configured for inputs for connection control bits, located at the beginning of the space configured for outputs
The specified %MW range for both inputs and outputs is available in the CPU. For more information, refer to the Processor Configuration Screen topic in the Control Expert help file.
In Control Expert select Edit → Validate (or click the Validate toolbar button) to save the address and size settings for inputs and outputs.
NOTE: After you validate module settings for the first time, you cannot edit the module name.
If you subsequently decide to change the module name, delete the existing module from the configuration, then add and rename a replacement module.
Completing the Ethernet Network Configuration
After configuring settings for inputs and outputs, the next step is to configure the 140NOC78100 module settings — beginning with its Channel Properties remote Ethernet network devices.
see page 111
— and then configure
NOTE: After you input configuration settings for the 140NOC78100 module and remote devices, return to the Configuration tab of the 140NOC78100 module’s Properties window and click the
Update application button. This creates derived data type (DDT) variables
display the following information and commands for your Control Expert project:
connection health bits, that display the status of each connection connection control bits, you can use to toggle each connection on and off the value of input and output items module and device configuration settings free memory space that has been reserved, but not yet allocated
see page 214
S1A48993 10/2019
77
Configuring the 140NOC78100 Module
The Control Expert FDT/DTM Interface Section 4.2
The Control Expert FDT/DTM Interface
Overview
The section describes the use of DTMs within Control Expert.
What Is in This Section?
This section contains the following topics:
Topic
Ethernet Configuration Tool User Interface
DTM Browser
DTM Browser Menu Commands
Field Bus Discovery Service
Device Editor
Configuring Properties in the Device Editor
Uploading and Downloading DTM-Based Applications
Page
78
S1A48993 10/2019
Configuring the 140NOC78100 Module
Ethernet Configuration Tool User Interface
Overview
The Ethernet Configuration Tool presents the following two views:
a Device Editor for configuring Ethernet communication modules, remote devices, and their
common Ethernet connections a Diagnostic window for monitoring the real-time operation of network devices, and diagnosing their condition
Connecting and Disconnecting a Device or Module DTM
A device or module DTM can be either connected to, or disconnected from the physical device or module.
When a device and its DTM are...
Connected
Disconnected
You can use the Ethernet configuration tool to...
Monitor and diagnose the real-time operation of the device or module
Configure a communication module or remote device by editing its properties
NOTE: Be sure to distinguish between:
connecting and disconnecting a DTM and the associated physical device using commands in
the DTM Browser, and placing Control Expert in online or offline operating mode using commands in the Control Expert
PLC menu
You can connect a DTM to, or disconnect a DTM from a device or module using the contextual pop-up menu in the DTM Browser. The DTM Browser indicates the relationship between the DTM and the remote module or device: a connected DTM is displayed in bold text; a disconnected DTM is displayed in normal text.
To connect a DTM to, or disconnect a DTM from its respective module or device, follow these steps:
2
3
Step Action
1 In the DTM Browser select the DTM that you want to connect to, or disconnect from, the physical communication module or remote device.
NOTE: If the module or device name appears in:
bold text, it is connected and only the Disconnect command is enabled normal text, it is disconnected and only the Connect command is enabled
Click the right mouse button. A pop-up menu opens.
Select one of the following commands:
Connect
Disconnect
NOTE: The Connect and Disconnect commands are also available in the Control Expert Edit menu.
S1A48993 10/2019
79
Configuring the 140NOC78100 Module
Device Editor
Use the Device Editor to display and configure device properties. The collection of properties you can view or edit depends upon the device selected in the DTM Browser, and whether Control
Expert is operating in Advanced Mode.
When the communication module and its DTM are...
Connected
Disconnected
The Device Editor opens in this mode...
read / write read-only
The Device Editor looks like this:
80
1 DTM Browser
2 Device Editor
Refer to the Device Editor topic in this help file for information on how to use the editor.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Access the Device Editor from the DTM Browser. If necessary, you may need to first disconnect the Ethernet communication module from its DTM.
Step
1
2
3
Action
(if necessary) In the DTM Browser, select the Ethernet communication module node and click the right mouse button. then select Disconnect in the pop-up menu.
In the DTM Browser, again select the Ethernet communication module node and click the right mouse button. The same pop-up menu opens.
Select Device menu → Configuration in the pop-up menu. The Device Editor opens.
Diagnostic Window
Use the Diagnostic Window to display:
colored LED icons that indicate the operating status of the Ethernet communication module,
remote devices, and their connections diagnostic data for the communication module, local slaves, and Ethernet connections
The Diagnostic Window can be displayed only when the communication module is connected to its DTM.
1 DTM Browser
2 Diagnostic Window
S1A48993 10/2019
81
Configuring the 140NOC78100 Module
Refer to the Diagnostic Window topic in this help file for information on how to use this window.
Access the Diagnostic Window from the DTM Browser. If necessary, you may need to first connect the Ethernet communication module to its DTM.
Step
1
2
3
Action
(if necessary) In the DTM Browser, select the Ethernet communication module node and click the right mouse button, then select Connect in the pop-up menu.
In the DTM Browser, again select the Ethernet communication module node and click the right mouse button. The same pop-up menu opens.
Select Device menu → Diagnostics in the pop-up menu. The Diagnostic Window opens.
82
S1A48993 10/2019
Configuring the 140NOC78100 Module
DTM Browser
Overview
The DTM Browser displays a hierarchical list of DTMs — in the form of nodes on a connectivity tree — that have been added to your Control Expert project. Each DTM node represents an actual module or device in your Ethernet network.
Node Types
There are 3 types of DTM nodes:
communication DTMs:
Any communication DTM can be plugged directly under the root node (Host PC) and is at the
1st level.
A communication DTM can support gateway DTMs or device DTMs as children if their protocols are compatible.
gateway DTMs:
A gateway DTM can support other gateway DTMs or device DTMs as children if their protocols are compatible.
device DTMs:
A device DTM does not support any child DTMs.
S1A48993 10/2019
83
Configuring the 140NOC78100 Module
Node Names
Each DTM has a default name when inserted into the browser. The default name consists of the following elements:
<channel: address> device name
Where:
Element channel address
Description
This is the name of the channel communication media, to which the device is plugged in. This name is read from the DTM and is set by the device vendor.
Example: EtherNet/IP, Modbus
The bus address of the device, which can be:
the connection point on its parent gateway network
the slot number in the modular device parent internal bus
Example: the device IP address device name The default name is determined by the vendor in the device DTM, but can be edited by the user.
Node Status
The DTM Browser displays the status of each DTM node in the connectivity tree, as follows:.
Status
Built / Not-built
Connected / Disconnected
Installed / Not-installed
Description
A blue check mark superimposed on a device icon indicates that node, or one of its sub-nodes, is not built. This means that some property of the node has changed, and the information stored in the physical device is no longer consistent with the local project.
A connected DTM is denoted in bold text. An unconnected
DTM appears in plain text.
NOTE:
Connecting a DTM to its physical device automatically connects all higher level parent nodes up to the root node.
Disconnecting a DTM from its physical device automatically disconnects all its lower level child nodes.
NOTE: Connecting or disconnecting a DTM to or from its device does not also connect or disconnect Control Expert to or from the PLC. DTMs can be connected/disconnected while
Control Expert is either offline or online.
A red superimposed on a device icon indicates the DTM for that device is not installed on the PC.
84
S1A48993 10/2019
Configuring the 140NOC78100 Module
Handling Invalid Nodes
As indicated above, a red superimposed on a node indicates the DTM for that node is not installed on the PC. To resolve this situation, right-click the node to open a pop-up menu with the following 2 commands:
Command
Delete
Properties
Description
Removes the selected node (and its sub-nodes) from the DTM Browser.
Opens the following dialog, which you can use to identify the name of the missing DTM:
NOTE: After you install the DTM, reopen the Control Expert application.
S1A48993 10/2019
85
Configuring the 140NOC78100 Module
DTM Browser Menu Commands
Overview
The DTM Browser includes a pop-up, contextual (right-click) menu that displays commands for the currently selected DTM. The list of available commands consists of:
universal commands, as determined by the selected node level:
host PC node (level 1)
communication module node (level 2) remote device node (level 3)
device-specific commands, as determined by the device DTM
Host PC Node Commands
The Host PC node contextual menu includes the following commands:
Name
Add 1
Check DTM devices 1
Description
Opens the Add dialog — containing a subset of the Hardware Catalog, allowing the selection of a communication module DTM.
Checks the current project for invalid DTMs or DTMs that are not installed in the PC. If the results of the check include invalid or notinstalled DTMs, they are displayed in the User errors tab in the information window and a red is superimposed over their icons in the DTM Browser.
DTM services Displays the communication DTMs selection, as well as the device topology, their respective IP addresses, and connection state. In this dialog, for each device you can connect, disconnect, load from devices, or store to devices. You can also choose to stop communication or continue activity when detected errors occur.
Displays the DTM catalog tab of the Hardware Catalog dialog.
DTM hardware catalog
Expand all 2 Displays every DTM in the project.
Collapse all 2 Displays only the communication DTMs in the project.
1. This command also appears in the Control Expert Edit menu.
2. This command also appears in the Control Expert View menu.
86
S1A48993 10/2019
Configuring the 140NOC78100 Module
Communication Module and Remote Device Node Commands
The DTM Browser’s contextual menu has the following items:
Name
Open 1
Add 1
Description
This opens the Device Editor for the selected communication module.
NOTE: Double-clicking the left mouse button on the DTM in the DTM Browser also opens this window.
This opens the Add dialog, displaying a subset of the Hardware Catalog, allowing the selection of a DTM.
NOTE: Control Expert filters the content of the Add dialog, so that it displays only DTMs that are compatible with the selected DTM selected.
Delete 1
Field Bus
Discovery
Connect 1
Disconnect 1
If the selected DTM allows this function, this deletes the selected DTM and its sub-node
DTMs from the DTM connectivity tree.
Deletion from the DTM connectivity tree does not affect the DTM’s link to the I/O scanning table.
This scans the connected physical devices to create the corresponding field bus topology.
Refer to the Field Bus Discovery Service topic.
This connects the DTM ( see page 90 )
to its physical device on the network. This connection does not depend on the PLC online/offline status of the Control Expert project application.
NOTE: Connecting a gateway or device DTM implicitly connects its parent DTM.
This disconnects the DTM ( see page 90 )
from its physical device. This disconnection depends on the PLC online/offline status of the Control Expert project application.
NOTE: Disconnecting a gateway or device DTM implicitly disconnects its parent DTM.
Load data from device 1
Store data to device
1
Copy
Paste
Device menu
This loads data from the physical device on the network to the DTM.
This loads data from the DTM to the physical device on the network.
This command is disabled.
This command is disabled.
This command opens a sub-menu that contains device-specific commands, as determined by the device vendor.
For details, refer to the Communication Module Commands topic
.
Device menu 2 This command opens a sub-menu that contains device-specific commands, as determined by the device vendor.
For details, refer to the Communication Module Commands topic
.
Properties
1 Opens the Ethernet communication module Properties window.
1. This command also appears in the Control Expert Edit menu.
2. This command also appears in the Control Expert View menu.
S1A48993 10/2019
87
Configuring the 140NOC78100 Module
Name
Print device 1
Description
If this optional function is supported by a DTM, this function displays the device documentation — including configuration settings — in the PC’s default Internet browser, which can then be printed.
NOTE: Device information can be printed:
for only one device DTM at a time, when that DTM is not open for editing in the
Device Editor.
only when the DTM is disconnected from the physical device.
Zoom out 2 This returns to the display of the entire DTM connectivity tree.
Expand all 2 This displays DTMs below the selected DTM.
Collapse all 2 This displays only the selected DTM.
1. This command also appears in the Control Expert Edit menu.
2. This command also appears in the Control Expert View menu.
Communication Module Commands
When you select Device menu in the main contextual menu for the communication module, a submenu with the following commands is displayed:
Name
Offline Parameter
Online Parameter
Compare
Configuration
Observe
Diagnosis
Description
This command is disabled.
This command is disabled.
This compares 2 devices, either online or offline.
This opens the Device Editor for the selected communication module, when the module and its DTM are disconnected.
This command is disabled.
This opens the Diagnosis Window for the selected communication module, when the module and its DTM are connected.
88
S1A48993 10/2019
Configuring the 140NOC78100 Module
Name
Additional functions
Remove EDS from library
Online Action
Description
Add EDS to library Opens the EDS File Wizard, which you can use to add a device EDS file to the Control Expert EDS device library. Control Expert displays the contents of EDS files as DTMs for use in the DTM Browser and
Device Editor.
Opens the EDS Deletion from Device Library window, which you can use to delete an EDS file from the device library.
EtherNet/IP
Explicit Message
Modbus TCP
Explicit Message
Opens the Online Action window. Depending upon the protocol(s) a remote device supports, you can use the Online Action window to:
Ping a remote EtherNet/IP or Modbus TCP device view and write to EtherNet/IP properties in a remote EtherNet/IP
device view and write to port configuration properties in a remote
EtherNet/IP device
Opens the EtherNet/IP Explicit Message
( see page 251 ) window, which
you can use to send explicit messages to EtherNet/IP remote devices.
Opens the Modbus TCP Explicit Message
devices.
window, which you can use to send explicit messages to Modbus TCP remote
About
Advanced Mode Displays or hides expert-level properties that help define Ethernet
connections. See the Enabling Advanced Mode topic
instruction on how to use this feature.
for
When you select Device menu 2 in the main contextual menu for the communication module, a sub-menu with the following commands is displayed:
Name
Configuration
Description
This opens the Device Editor for the selected communication module, when the module and its DTM are disconnected.
Diagnosis
Remove EDS from library
Online Action
This opens the Diagnosis Window for the selected communication module, when the module and its DTM are connected.
Add EDS to library Opens the EDS File Wizard, which you can use to add a device EDS file to the Control
Expert EDS device library. Control Expert displays the contents of EDS files as DTMs for use in the DTM Browser and Device Editor.
Opens the EDS Deletion from Device Library window, which you can use to delete an
EDS file from the device library.
Opens the Online Action window. Depending upon the protocol(s) a remote device supports, you can use the Online Action window to:
Ping a remote EtherNet/IP or Modbus TCP device view and write to EtherNet/IP properties in a remote EtherNet/IP device view and write to port configuration properties in a remote EtherNet/IP device
S1A48993 10/2019
89
Configuring the 140NOC78100 Module
Name
EtherNet/IP
Explicit Message
Modbus TCP
Explicit Message
Description
Opens the EtherNet/IP Explicit Message
send explicit messages to EtherNet/IP remote devices.
) window, which you can use to
Opens the Modbus TCP Explicit Message ( see page 254
send explicit messages to Modbus TCP remote devices.
) window, which you can use to
Advanced Mode Displays or hides expert-level properties that help define Ethernet connections. See the
Enabling Advanced Mode topic ( see page 91 ) for instruction on how to use this feature.
Connecting and Disconnecting a Device or Module DTM
A device or module DTM can be either connected to, or disconnected from, the physical device or module.
When a device and its DTM are... You can use the Ethernet configuration tool to...
Connected Monitor and diagnose the real-time operation of the device or module
Disconnected Configure a communication module or remote device by editing its properties
NOTE: Distinguish between:
connecting and disconnecting a DTM and the associated physical device using commands in
the DTM Browser
— and — placing Control Expert in online or offline operating mode using commands in the Control Expert
PLC menu
You can connect a DTM to, or disconnect a DTM from a device or module using the contextual pop-up menu in the DTM Browser. The DTM Browser indicates the relationship between the DTM and the remote module or device: a connected DTM is displayed in bold text; a disconnected DTM is displayed in normal text.
To connect a DTM to, or disconnect a DTM from its respective module or device, follow these steps:
Step
1
2
Action
In the DTM Browser select the DTM that you want to connect to, or disconnect from, the physical communication module or remote device.
NOTE: If the module or device name appears in:
bold text, it is connected and only the Disconnect command is enabled.
normal text, it is disconnected and only the Connect command is enabled.
Click the right-mouse button.
Result: A pop-up menu opens.
90
S1A48993 10/2019
Configuring the 140NOC78100 Module
Step
3
Action
Select one of the following commands:
Connect
Disconnect
NOTE: The Connect and Disconnect commands are also available in the Control Expert Edit menu.
Enabling Advanced Mode
Use the contextual menu in the DTM Browser to toggle Control Expert in or out of Advanced Mode, thereby displaying or hiding expert-level properties that help define Ethernet connections. These properties are identified by the icon.
NOTE: To maintain system performance, confirm that Advanced Mode properties are configured only by persons with a solid understanding of communication protocols.
To toggle Advanced Mode on and off:
3
4
Step
1
2
Action
Close both the Diagnosis Window and every instance of the Device Editor before attempting to toggle Advanced Mode on or off.
NOTE: If the Device Editor or the Diagnosis Window is open, the Advanced Mode status — on or off — cannot be changed.
In the DTM Browser, right-click the communication module.
Result: A pop-up menu opens.
To toggle ON advanced mode, select Device Menu → Advanced Mode.
To toggle OFF advanced mode, repeat steps 1 through 3, above.
S1A48993 10/2019
91
Configuring the 140NOC78100 Module
Field Bus Discovery Service
Introduction
Use the field bus discovery service to detect — and add to your Control Expert application — control network devices that are situated on a local channel. The field bus discovery service is available only when the Ethernet communication module DTM is connected to its physical device.
Only the first level devices below the communication DTM are detected.
Performing Field Bus Discovery
The results of the scanning process is compared to the registered DTMs in the DTM catalog of the computer. If a match is found in the DTM catalog for a scanned device, the results are accompanied with a matching type that gives the accuracy of the match.
The three available matching types are:
exact match:
All identification attributes are matching. The correct device type was found.
generic match:
At least the Vendor and device Type ID attributes match. The support level of DTM is Generic
Support .
uncertain match:
At least the Vendor and device Type ID attributes match. The support level of DTM is not
Generic Support .
The following procedure explains how to use the field bus discovery service:
Step
1
2
Action
In the DTM browser, select an appropriate DTM.
Right click, and in the pop-up menu select Field bus discovery.
Result: The Field bus discovery dialog opens:
92
3 If necessary, select a channel and a protocol:
if the DTM has more than one channel
if the channel supports more than one protocol
S1A48993 10/2019
Configuring the 140NOC78100 Module
5
6
7
8
Step
4
9
Action
Click OK.
Result:The service starts to detect devices on the selected channel.
NOTE: The field bus discovery service limits its search to only the range of IP addresses that is pre-configured for the selected channel in the Channel Properties page
If at least one matched device has been found, the Field bus discovery dialog displays a list of
Scanned Devices.
Use the controls of the Field bus discovery dialog to select the devices to add to your Control
Expert application.
After you have selected all the devices you want to add in the Field bus discovery dialog, click OK.
If the field bus discovery process has found one or more devices with an IP address that is already in use in the project, you will be asked if you want to continue and replace the existing project deviice(s). Click Yes and proceed to step 9, below, or No to cancel automatic field bus discovery.
The device properties dialog (below) opens, displaying the default name for the first discovered device to be added:
10
11
S1A48993 10/2019
In the General page of the device properties dialog, type the Alias name for the device to be added, then click OK.
Result: The dialog closes, then re-opens if there is another device to be added to the application.
Repeat step 9 for each additional discovered device.
After all devices have been added to the application, configure each device for operation as part of the application. To do this:
Disconnect the Ethernet communication module from its DTM. In the DTM Browser, select the
Ethernet communication module, then select Edit → Disconnect.
Configure the new device properties in the DTMs for both the Ethernet communication module and the newly added remote device.
93
Configuring the 140NOC78100 Module
Field Bus Discovery Dialog
If at least one matched device has been found, the Field bus discovery dialog box is displayed listing the scanned and matched devices. Select the matched devices to be created in the Control
Expert project (which then shows up in the Selected Devices list:
94
This dialog presents 3 lists:
This list...
Scanned Devices
Matched Devices
Selected Devices
Displays...
All the devices (matched and unmatched) found during the scan.
The matched DTMs found in the workstation DTM catalog for the device that you selected in the Scanned Devices list.
Each time a scanned device is selected in the Scanned Devices list, the contents of the Matched Devices list is updated to display the matched device DTMs found for the selected scanned device.
The matching process can yield one or more matched devices for a given scanned device. In this case, only one DTM was discovered for the selected scanned device.
This list displays the device DTMs that have been selected in the Matched Devices list, which will be added to the Control Expert project.
S1A48993 10/2019
Configuring the 140NOC78100 Module
The lists use the following colored icons:
This color...
green yellow red black
Indicates...
The device has been selected.
The device has been matched.
The device has not been matched.
Information about the address of the scanned device:
In the Scanned Devices list, the device has an address identical to one of the DTMs in
the Control Expert project.
In the Matched Devices list, the device will be assigned an address identical to one of the DTMs in the Control Expert project.
NOTE: An icon can consist of 2 colors. For example, a search can discover a device that:
has a matching DTM
— and — has an IP address identical to a device already added to the Control Expert application
In this case, the icon next to the discovered device would be:
half yellow and half black, before it is selected
— and — half green and half black, after it is selected
This dialog has 5 buttons:
Button
Add All
Use this button to...
Automatically add the respective (according to the matching types listed above) device DTM for each found device in the Matched Devices list to the Selected Devices list.
Add One Add the matched device DTM selected in the Matched Devices list.
Remove Remove one or more devices from the Selected Devices list.
OK
Cancel
Insert the device DTMs in the Selected Devices list into the Control Expert project.
If there are one or more devices in the Selected Devices list that have the same address in the
Control Expert project, a message box opens asking if you want to continue.
If you click OK, all devices in the Control Expert project that have identical addresses as the selected devices are deleted and replaced by the DTMs selected in the Selected Devices list.
Cancel the field bus discovery scan and do nothing. All information in the 3 lists is discarded.
S1A48993 10/2019
95
Configuring the 140NOC78100 Module
Device Editor
Description
Use the Device Editor to view and configure Ethernet communication modules and remote devices. The collection of properties you can view or configure depends on:
the node type selected in the DTM Browser:
communication module
remote device
whether Control Expert is operating in Advanced Mode
Displaying Properties of the Ethernet Communication Module
After you open the Ethernet communication module in the DTM Browser, the left pane (1) of the
Device Editor displays a tree control containing configurable property groups for the communication module. Click a node in the tree control to display one or more pages of module properties for the selected group in the right pane (2).
96
S1A48993 10/2019
Configuring the 140NOC78100 Module
Property Types
The Device Editor displays an icon next to many device properties. The following 3 icons are displayed:
This icon...
Indicates the property is...
Read-only
The property value cannot be edited in this page.
Read-write
The property value can be edited in this page.
An expert-level communication protocol property that is displayed only when Advanced Mode is enabled.
Displaying Property Definitions
Many property configuration pages provide an on-screen definition of the property you are editing.
To display a property definition in the Description section of the page, select that property in the property list. The following screen displays a description of the Gateway IP Address property.
NOTE: The preceding displayed page can be accessed by opening an Ethernet communication module in the Device Editor, and then selecting Channel Properties → TCP/IP in the navigation tree.
S1A48993 10/2019
97
Configuring the 140NOC78100 Module
Configuring Properties in the Device Editor
Configuring Properties
The Device Editor can be opened from the DTM Browser.
To open the DTM Browser select Tools → DTM Browser in the Control Expert main menu.
To use the Device Editor:
Step Description
1 Confirm that the DTM you want to use is not connected to the actual communication module or
device. If necessary, disconnect the DTM from the module or device ( see page 90 )
.
2 In the DTM Browser, select the Ethernet network node you want to configure, which can be either:
an Ethernet communication module
— or — a remote device
3 With a node selected in the DTM Browser, do one of the following:
In the Control Expert main menu, select Edit → Open.
— or —
In the DTM Browser click the right mouse button and, in the pop-up menu, select Open.
The Device Editor appears. It displays the configurable properties for the selected module or device:
98
4 Expand the navigation tree and select a node in the left window pane to display its properties in the right pane. The list of configurable properties varies, depending on the node type, communication module or remote device, selected in the DTM Browser.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Step Description
5 While you edit a parameter, Control Expert displays an icon next to the field you are editing and in the navigation tree indicating the parameter value is being edited. Control Expert displays one of the following icons:
This icon...
Indicates the importance of the parameter being edited is...
High: Editing this parameter may limit or deny access to the module or device.
Low: Editing this parameter will not limit or deny access to the module or device.
6 After you finish editing a page, click:
Apply to save your edits and keep the page open.
— or —
OK to save your edits and close the page.
NOTE: Your edits will not take effect until they are successfully downloaded from your PC to the
CPU and from the CPU to the communication modules and network devices.
S1A48993 10/2019
99
Configuring the 140NOC78100 Module
Uploading and Downloading DTM-Based Applications
Introduction
You can use Control Expert to download an application file from your PC to the PLC, and to upload an application file from the PLC to your PC.
To successfully complete an upload, the application file needs to include specific upload-related information as part of the application.
Downloading DTM-Based Applications
Control Expert applications that include DTM files require more memory than traditional Control
Expert applications. The following products employ DTMs for network configuration:
140 NOC 771 01 Ethernet communication module for Quantum
TSX ETC 101 Ethernet communication module for Premium
BMX NOC 0401 Ethernet communication module for M340
140NOC78•00 Ethernet communication module for Quantum
In some cases, the configurations created for these modules and the data associated with them require more memory than is available in the CPU.
If the amount of memory required by an application exceeds the amount of memory that is available in the CPU, Control Expert provides notice of this condition during the build process, before the application is downloaded to the PLC.
When this situation occurs, exclude the additional upload-related information from the application to complete the build and enable the application download. To do this, make the following configuration change in Control Expert:
2
3
Step
1
Action
In the main menu, select Tools → Project Settings... The Project Settings window opens.
In the left pane of the Project Settings window, select General → PLC embedded data.
In the right pane, de-select Upload information:
100
4 Click OK to save your changes and close the Project Settings window.
S1A48993 10/2019
Configuring the 140NOC78100 Module
After the Upload information setting is disabled, you can build the application and download it to the PLC.
NOTE: An application in which the Upload information setting has been disabled cannot later be uploaded from the PLC to the PC.
Uploading DTM-Based Applications
DTM-based applications that were successfully downloaded to Control Expert with the project’s
Upload information setting enabled can later be uploaded from the PLC to the PC if the following pre-conditions exist:
DTM-based applications that were successfully downloaded to Control Expert with the project’s
Upload information setting enabled can later be uploaded from the PLC to the PC if the target PC has the following files installed on it:
a version of Control Expert that is equal to or later than the version used to create the
application the master DTMs for the modules included in the configuration
NOTE: The Ethernet Configuration Tool installation CD contains the Master DTMs for all the
Ethernet communication modules, referenced above.
the device DTMs for all DTM-based devices attached to the network (the DTMs are of the same or higher revision as each device DTM used in the configuration) the device EDS files for any EtherNet/IP device used in the configuration (the EDS files are of the same or higher revision as each device EDS file used in the configuration)
After all the above components have been installed on the target PC, you can upload a DTM-based
Control Expert application from a PLC.
NOTE: All of the above DTM components need to be installed on the target PC the upload.
before attempting
S1A48993 10/2019
101
Configuring the 140NOC78100 Module
Hardware Catalog Section 4.3
Hardware Catalog
Overview
Control Expert includes a collection of modules and devices called the Hardware Catalog that you can add to a Control Expert project. EtherNet/IP and Modbus TCP devices are located in the hardware catalog’s DTM Catalog page. Each device in the catalog is represented by a DTM that defines the parameters of the module or device.
Not all devices in the market today offer device-specific DTMs. Some devices are instead defined by a device-specific EDS file. Control Expert displays each EDS file in the form of a DTM. In this way, you can use Control Expert to configure these Ethernet/IP devices defined by an EDS file in the same way you would configure a DTM-defined device.
Other devices lack both a DTM and an EDS file. You can configure these devices by using a generic DTM that is included in the DTM Catalog page.
This section address the topics:
how to add a DTM to the catalog
how to add an EDS file to the catalog how to update the catalog how to remove an EDS file from the catalog
What Is in This Section?
This section contains the following topics:
Topic
Adding a DTM to the Control Expert Hardware Catalog
Add an EDS File to the Control Expert Hardware Catalog
Updating the Control Expert Hardware Catalog
Remove an EDS File from the Control Expert Hardware Catalog
Page
102
S1A48993 10/2019
Configuring the 140NOC78100 Module
Adding a DTM to the Control Expert Hardware Catalog
A Manufacturer Defined Process
Before a DTM can be used by the Control Expert Hardware Catalog, install the DTM on the host
PC, the same PC that is running Control Expert, by means of an installation process defined by the device manufacturer.
Consult your device documentation, provided by the device manufacturer, for information describing how to install a device DTM on your PC.
NOTE: After a device DTM is successfully installed on your PC, update the Control Expert
Hardware Catalog
see page 107
added to a Control Expert project.
so the new DTM is visible in the catalog and available to be
S1A48993 10/2019
103
Configuring the 140NOC78100 Module
Add an EDS File to the Control Expert Hardware Catalog
Overview
Control Expert includes a wizard you can use to add one or more EDS files to the Control Expert
Hardware Catalog. The wizard presents a series of instruction screens that:
simplify the process of adding EDS files to the catalog provide a redundancy check in case you attempt to add duplicate EDS files to the catalog
NOTE: The Control Expert Hardware Catalog displays a partial collection of DTMs and EDS files registered with the ODVA. This library includes DTMs and EDS files for products not manufactured or sold by Schneider Electric. The non-Schneider Electric EDS files are identified by vendor in the catalog. Please contact the identified device’s manufacturer for inquiries regarding the corresponding non-Schneider Electric EDS files.
Adding EDS Files
To add one or more EDS files to the library:
Step
1
2
3
Action
If the DTM Browser is not already open, in the Control Expert main menu select Tools →
DTM Browser.
In the DTM Browser, select a communication module, then click the right mouse button.
Result: A pop-up menu opens.
In the pop-up menu, select Device menu → Add EDS to library.
Result: The introductory page of the wizard opens.
104
S1A48993 10/2019
Step
4
Action
Click Next.
Result: Page 2 of the wizard opens:
Configuring the 140NOC78100 Module
S1A48993 10/2019
6
7
5
8
In the Select the Location of the EDS File(s) section, select one of the following:
Add File(s), to add one or more EDS files you will individually select
Add all the EDS from the Directory, to add all files from a folder you will select.
Select Look in Subfolders to also add EDS files in subfolders beneath the folder you selected.
Click the Browse button.
Result: The Open dialog opens.
Use the Open dialog to navigate to and select one of the following:
one or more EDS files
a folder containing EDS files
After you have made your selections, click Open.
Result: The dialog closes, and your selection appears in the Directory or File Name field.
105
Configuring the 140NOC78100 Module
Step
9
13
14
15
10
11
12
Action
Choose the naming convention rule for the EDS DTM name creation.
The new naming convention is based on Model Name / Product Name and Revision. A random character is automatically suffixed when Model Name / Product Name and Revision of an EDS file of the library are identical. The new naming convention is irrespective of the order in which
EDS files are added to device library.
By default, the New Naming Convention check box is selected and the new naming rule applies.
NOTE: To keep backward compatibility with Unity Pro/Control Expert versions, unchecked the
New Naming Convention check box and the naming rule is based on Model Name / Product
Name.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
Click Next.
Result: The wizard compares the selected EDS files against existing files in the library.
(Conditional) If one or more selected EDS files is a duplicate, a File Already Exists message opens.
Close the message.
Page 3 of the wizard opens indicating the status of each device you attempted to add:
A green check mark indicates the EDS file can be added.
A blue informational icon indicates a redundant file.
A red exclamation point indicates an invalid EDS file.
(Optional) Select a file in the list, then click View Selected File to open it.
Click Next to add the non-duplicate files.
Result: Page 4 of the wizard opens, indicating the action is complete.
Click Finish to close the wizard.
The next step is to update the Control Expert Hardware Catalog ( see page 107
newly added device is available for inclusion in a Control Expert project.
, so that the
106
S1A48993 10/2019
Configuring the 140NOC78100 Module
Updating the Control Expert Hardware Catalog
Updating Hardware Catalog
After you have followed the manufacturer’s instructions and installed a module or device DTM on your PC, the next step is to update the Control Expert Hardware Catalog. Updating the
Hardware Catalog makes the new Ethernet module or device available for addition to your Control
Expert application.
To update the Hardware Catalog:
Step
1
2
Action
In the Control Expert main menu, select Tools → Hardware Catalog.
Result: The Hardware Catalog window opens.
In the Hardware Catalog window, select the DTM Catalog tab to display a module and device
DTM list. At the time of initial software installation, the catalog displays no devices.
S1A48993 10/2019
107
Configuring the 140NOC78100 Module
Step
3
Action
Click the External Update Tool button.
Result: The FDT/DTM Catalog window opens.
4
5
6
In the FDT/DTM Catalog window, click Update. The window refreshes itself, as indicated by the progress bar in the lower right corner of the window.
After the update has finished, click Close.
Result: The FDT/DTM Catalog window closes, and the Hardware Catalog displays.
In the Hardware Catalog window, click Reload catalog to refresh the DTM list.
108
S1A48993 10/2019
Configuring the 140NOC78100 Module
Remove an EDS File from the Control Expert Hardware Catalog
Overview
You can remove a module or device from the list of available devices in the Control Expert
Hardware Catalog by removing its EDS file. When you remove an EDS file from the library, the device or module is no longer displayed by Control Expert in the DTM Catalog page of the
Hardware Catalog window.
However, removing an EDS file from the library does not delete the file. Instead, the EDS file
remains in its stored location and can again be added to the catalog
time.
see page 104
Removing an EDS File from the Catalog
To remove an EDS file from the catalog:
Step
1
2
3
Action
If the DTM Browser is not already open, select Tools → DTM Browser in the Control Expert main menu.
In the DTM Browser, select a 140NOC78•00 head module, then click the right mouse button.
Result: A pop-up menu opens.
In the pop-up menu, select Device menu → Additional functions → Remove EDS from library.
Result: The following window opens:
S1A48993 10/2019
109
Configuring the 140NOC78100 Module
Step
4
5
6
7
8
9
10
Action
Use the selection lists in the heading of this window to specify how EDS files are displayed:
Display Filters the list of displayed EDS files; select:
All EDS (no filtering)
Only Devices
Only Chassis
Only Modules
Sort by
Displayed Name
Sorts the list of displayed EDS files; select:
File Name
Manufacturer
Category
Device Name
The description displayed for each device; select:
Catalog Name
Product Name
In the Device Library tree control, navigate to and select the EDS file you want to remove.
(Optional) Click the View Selected File button to display the read-only contents of the selected
EDS file.
Click the Delete Selected File button.
Result: A message box opens.
Click Yes to remove the selected EDS file from the list.
When you have finished removing EDS files, click Close.
The next step is to update the Hardware Catalog
110
S1A48993 10/2019
Configuring the 140NOC78100 Module
Channel Properties Section 4.4
Channel Properties
Overview
This section describes how to configure channel properties for the Ethernet network.
What Is in This Section?
This section contains the following topics:
Topic
Channel Properties Page
Channel Properties - Ethernet Page
Channel Properties - Switch Page
Channel Properties - TCP/IP Page
Channel Properties - EtherNet/IP Page
Page
S1A48993 10/2019
111
Configuring the 140NOC78100 Module
Channel Properties Page
Description
Use the Channel Properties page to:
select the IP address to use for:
connecting module or device DTMs to physical devices sending explicit messages to Modbus TCP and EtherNet/IP devices
view your PC’s IP address settings
The Channel Properties page looks like this:
112
To display this page, select the Channel Properties node in the navigation tree located on the left side of the Device Editor.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Properties
This page presents the following properties:
Name
Source Address area:
Source IP
Address (PC):
Description
A list of IP addresses assigned to network interface cards installed on your PC.
Sub-Network Mask: The subnet mask associated with the selected Source IP Address.
EtherNet/IP Network Detection area:
Begin detection range address
End detection range address
The starting IP address of the address range for automatic field bus discovery of
EtherNet/IP devices.
The ending IP address of the address range for automatic field bus discovery of
EtherNet/IP devices.
Modbus TCP Network Detection area:
Begin detection range address
End detection range address
The starting IP address of the address range for automatic field bus discovery of
Modbus TCP devices.
The ending IP address of the address range for automatic field bus discovery of
Modbus TCP devices.
Managing Source IP Address for Multiple PCs
When you connect a PC to a DTM-based Control Expert application, Control Expert requires that you define the IP address of the PC connected to the PLC, which is referred to as the source IP address (PC) . Rather than having to perform a Build in Control Expert each time you connect a PC to the PLC, the source IP address (PC) is selected automatically when you import the Control
Expert application. During application import, the DTM retrieves all available configured NIC addresses of a connected PC and matches the subnet mask of the master with the available NIC list.
If a match between the subnet mask of the master and the NIC list exists, Control Expert automatically selects the matched IP address as the source IP address (PC) in the Channel
Properties page.
If multiple matches exist, Control Expert automatically selects the IP address nearest to the subnet mask.
If no match exists, Control Expert automatically selects the IP address to the nearest available subnet mask.
S1A48993 10/2019
113
Configuring the 140NOC78100 Module
Channel Properties - Ethernet Page
Description
The Ethernet page presents communication settings for Quantum 140 NOC 780 00 and 140 NOC
781 00 Ethernet communication modules. Use this page to:
view and edit the Connection Speed, which includes both the:
transmission speed, and
duplex mode
view the Frame Format
To display this page, select the Channel Properties → Ethernet node in the navigation tree located on the left side of the Device Editor.
NOTE: Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
Properties
The Ethernet page presents the following properties:
Name
Connection Speed
Frame Format
Description
The transmission speed and duplex mode for the network. Values include:
Auto 10/100 Mb (default)
100 Mb Half
100 Mb Full
10 Mb Half
10 Mb Full
NOTE: Schneider Electric recommends the default setting—Auto
10/100 Mb. This setting causes the connected devices to perform auto-negotiation and thereby determine the fastest common transmission rate and duplex mode.
Ethernet II is the only available value (read-only).
114
S1A48993 10/2019
Configuring the 140NOC78100 Module
Channel Properties - Switch Page
Description
Use the Switch tab of the Switch page to:
enable or disable each of the 4 Ethernet ports on the 140NOC78•00 head module
view and edit the Baud Rate for each port, which includes both the:
transmission speed
— and — duplex mode
NOTE: The Ethernet communication module supports only the Ethernet II frame type.
The Switch page looks like this:
To display this page, select the Channel Properties → Switch node in the navigation tree located on the left side of the Device Editor. Then click the Switch tab.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
S1A48993 10/2019
115
Configuring the 140NOC78100 Module
Properties
This page presents the following properties:
Name
Port
Enabled
Baud Rate
Description
(read-only) The Ethernet port number: 1...4.
The active status of the port:
Yes = enabled
No = disabled
The transmission speed and duplex mode for the network. Values include:
Auto 10/100 Mbits/sec (default)
100 Mbits/sec Half duplex
100 Mbits/sec Full duplex
10 Mbits/sec Half duplex
10 Mbits/sec Full duplex
For ETH 3 and ETH 4:
Auto 10/100/1000 Mbits/sec (default)
1000 Mbits/sec Half duplex
1000 Mbits/sec Full duplex
NOTE: Schneider Electric recommends the default setting. This setting causes the connected devices to perform auto-negotiation and thereby determine the fastest common transmission rate and duplex mode.
116
S1A48993 10/2019
Configuring the 140NOC78100 Module
Channel Properties - TCP/IP Page
Description
Use the TCP/IP page to:
select a Configuration mode, which specifies how the communication module obtains its IP
addressing settings
— and — edit the IP addressing settings that will be used if the Configuration mode is set to Static
The TCP/IP page looks like this:
To display this page, select the Channel Properties → TCP/IP node in the navigation tree located on the left side of the Device Editor.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
Selecting a Configuration Mode
Use the Configuration list to specify a configuration mode. The configuration mode setting determines how the communication module obtains its IP address at startup. Choices are:
Configuration Mode
Static
Description
The module uses the scanner IP address, gateway IP address, and sub-network mask configured in this page.
S1A48993 10/2019
117
Configuring the 140NOC78100 Module
Setting the Module Addresses in Static Mode
Configure 3 IP addressing properties for the Ethernet communication module in Static configuration mode:
Property
Scanner IP Address
Sub-Network Mask
Gateway Address
Description
The 32-bit identifier — consisting of both a network address and a host address — assigned to a device connected to a TCP/IP Internet network using the Internet Protocol (IP).
The 32-bit value used to hide (or mask) the network portion of the IP address and thereby reveal the host address of a device on a network using the IP protocol.
The address of a device, if any, that serves as a gateway to the communication module.
Default Address Configurations
The communication module uses a default address configuration when it is not configured or when a duplicate IP address is detected. The default address is based on the MAC address of the module and makes it possible for several Schneider Electric devices to use their default network configuration on the same network.
The module uses the following default address configurations:
No router configured:
Service port (ETH 1) default IP = 10.10.MAC5.MAC6
Interlink port (ETH 2) default IP = 10.10.MAC5.MAC6
Control ports (ETH 3, 4 default IP = 10.10.MAC5.MAC6
Router configured, fieldbus network configured, service port configured for access mode:
Service port (ETH 1) default IP = 169.254.10.MAC6
Interlink port (ETH 2) default IP = 169.254.20.MAC6
Control ports (ETH 3, 4) default IP = 169.254.10.MAC6
Router configured, fieldbus network configured, service port configured for extended network:
Service port (ETH 1) default IP = 169.254.30.MAC6
Interlink port (ETH 2) default IP = 169.254.20.MAC6
Control ports (ETH 3, 4) default IP = 169.254.10.MAC6
118
S1A48993 10/2019
Configuring the 140NOC78100 Module
Duplicate Address Checking
Before going online, the module sends out at least 4 ARP messages with a proposed IP address:
if an answer is returned:
another network device is already using the proposed IP address.
the module will not use the proposed IP address, but will instead use the default IP address.
if an answer is not returned:
the module is assigned the proposed IP address (along with the associated network parameters).
NOTE: When powering up an entire network, some switches may be slow to complete the power up process. This can cause some ARP messages to be dropped. To help avoid this situation,
Schneider Electric recommends that, when powering up an entire network, confirm that all network switches complete their power up cycle before powering up the PLCs.
S1A48993 10/2019
119
Configuring the 140NOC78100 Module
Channel Properties - EtherNet/IP Page
Description
The EtherNet/IP page is displayed only when Control Expert is operating in Advanced Mode
see page 91
. Advanced mode properties are identified by the icon.
Use the EtherNet/IP page to configure the following communication module properties:
properties that determine how the communication module, as a scanner, opens connections for
both implicit and explicit messages the frequency for transmitting produced data over implicit messaging connections the timeout period for explicit messaging connections the behavior of the communication module—as a scanner—when:
the application is stopped, or the communication module receives a reset service request
The EtherNet/IP page looks like this:
120
To display this page, select the Channel Properties → EtherNet/IP node in the navigation tree located on the left side of the Device Editor.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Properties
Note: Users experienced in the configuration of EtherNet/IP networks can edit the following readwrite properties.
Name
Timeout
FW_Open IO Connection Timing
Description
FW_Open EM Connection Timing
EM Connected RPI
EM Request Timeout
The amount of time the communication module waits for the
Forward_Open IO messaging transaction to open an implicit messaging connection. Default = 5000 ms
The amount of time the communication module waits for the
Forward_Open IO messaging transaction to open an explicit messaging connection. Default = 3000 ms
The value used to set the T->O (target to originator) and O->T
(originator to target) requested packet interval (RPI) for explicit message connections. This value is used to calculate the lifetime of a connection. Default = 10000 ms.
The amount of time the communication module waits between a request and reply of an explicit message. Default =10 s.
Output
Allow reset explicit message The behavior of the communication module—as scanner—when it receives a reset service request:
TRUE indicates the module will accept the request and reset itself.
FALSE indicates the module ignores the reset service request and continues uninterrupted operations.
Default = FALSE
Behavior when CPU state is STOP The state of the communication module when the CPU application goes into a STOP state:
TRUE indicates that the module enters STOP state (implicit connections are closed).
FALSE indicates that the module enters IDLE state (implicit connections are not closed).
Default = FALSE
S1A48993 10/2019
121
Configuring the 140NOC78100 Module
Ethernet Services Section 4.5
Ethernet Services
Overview
This section describes how to enable and configure Ethernet services provided by the
140NOC78100 head modules.
What Is in This Section?
This section contains the following topics:
Topic
Enabling Services
Configuring the DHCP and FDR Servers
Configuring the SNMP Agent
Configuring Access Control
Configuring QoS Ethernet Packet Tagging
Configuring the Rapid Spanning Tree Protocol
Configuring the Service/Extend Port
Configuring Time Synchronization
Configuring the IP Forwarding Service
Configuring Electronic Mail Notification
Page
122
S1A48993 10/2019
Configuring the 140NOC78100 Module
Enabling Services
Description
Use the Services page to enable and disable Ethernet services provided by the 140NOC78100 head module.
NOTE: After you enable a service, you can configure its settings. If a service is not configured,
Control Expert applies its default settings.
The Services page looks like this:
NOTE: By default, the Address Server, I/O Communication Control, and Service Port fields are set to Enabled. All other fields are set to Disabled.
S1A48993 10/2019
123
Configuring the 140NOC78100 Module
Enabling/Disabling Ethernet Services
To enable or disable Ethernet services on the Services page:
Step
1
2
3
4
Action
Double-click the 140NOC78100 head module in the DTM browser or right-click the module and click Open.
Click Services in the navigation tree located in the left panel of the Device Editor.
For each feature, change the setting as desired. Address Server, I/O Communication Control, and Service Port are Enabled by default. All other features are Disabled by default.
Click Apply to save changes, or click OK to save changes and close the window.
When you Enable a service, Control Expert displays a node for that service in the navigation tree in the left panel of the Device Editor, beneath the Services parent node. Click a service node to access its settings.
When you Disable a service, Control Expert hides the node for that service.
NOTE: Refer to Configuring Properties in the Device Editor (see Quantum using EcoStruxure™
Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
Ethernet Services Descriptions
The 140NOC78100 head module can be configured to provide the following Ethernet services:
If this service is enabled...
Access Control
Address Server
I/O Communication Control
Network Time Service
The module can...
Deny access to the 140NOC78100 head module by unauthorized network devices
Provide both IP addressing parameters and operating parameters to other
Ethernet devices
Allow the Control Expert application to control the enabling and disabling of individual connections between the head module and remote I/O devices
NOTE:
The application can open and close individual connections using the control bits located at the beginning of the output area.
If this service is disabled, the user — via the application program — cannot toggle on and off connection control bits.
Synchronize computer clocks over the Internet for the purposes of event recording (sequence events), event synchronization (trigger simultaneous events), or alarm and I/O synchronization (time stamp alarms)
124
S1A48993 10/2019
If this service is enabled...
Service Port
IP Forwarding
SNMP
QoS Tagging
RSTP
Configuring the 140NOC78100 Module
The module can...
Supports 3 functions:
Port Mirroring: You can connect to this port via a PC and sniff (using
Ethereal, WireShark, etc.) the traffic that is travelling through the other ports including the Ethernet port — the internal port — that is connected to the CPU.
Access Port: You can connect an Ethernet device (ex: an HMI or a PC with
Control Expert software or a PC with ConneXium Network Manager software) to this port, and communicate with the CPU/PLC, the
140NOC78100 head module itself, or access other devices connected to the network.
Extended Network: An existing distributed I/O network participates in the
Ethernet remote I/O network when a 140NOC78000 distributed I/IO head module is connected to the SERVICE/EXTEND
140NOC78100 control head module and also connected to the
INTERLINK module.
port of the 140CRP31200 remote I/O head
Exchange network transparent data between the control network, the device network, and extended distributed I/O networks, while preserving remote I/O device network determinism
Send email messages that notify you of custom events during application execution. Custom email messages are delivered to a preconfigured destination on demand by your application code.
Serve as an SNMP v1 agent
Provide trap information to up to two devices configured as SNMP managers.
NOTE: The SNMP service is enabled.
Network switches can prioritize the transmission and forwarding of Ethernet packets
NOTE: The QoS service is enabled.
Create a logical network path for Ethernet devices that are part of a topology that includes redundant physical paths. The RSTP-enabled module also automatically restores network communication — by activating redundant links — in the event the network experiences a loss of service.
NOTE: The RSTP service is enabled.
S1A48993 10/2019
125
Configuring the 140NOC78100 Module
Configuring the DHCP and FDR Servers
Introduction
The 140 NOC 78• 00 head module includes both a DHCP and a fast device replacement (FDR) server. The DHCP server provides IP address settings to networked Ethernet devices. The FDR server provides operating parameter settings to replacement Ethernet devices that are equipped with FDR client functionality.
Use the Address Server page to:
enable and disable the 140 NOC 78• 00 head module’s FDR service
view an automatically generated list of all devices included in the 140 NOC 78• 00 head module’s Ethernet configuration, displaying for each device:
IP addressing parameters whether the device’s IP addressing parameters are provided by the 140 NOC 78• 00 head module’s embedded DHCP server
manually add remote devices — that are not part of the 140 NOC 78• 00 head module’s
Ethernet configuration — to the 140 NOC 78• 00 module’s DHCP client list
NOTE: Remote devices added in this way are equipped with DHCP client software, and are configured to subscribe to the 140 NOC 78• 00 head module’s IP addressing service.
The Address Server page looks like this:
126
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring the Address Server
To configure the Address Server:
Step
1
2
3
4
Action
Open the 140 NOC 78• 00 head module in the DTM browser.
Click the Address Server node in the Services navigation tree in the left panel of the Device Editor.
Enable or disable the FDR Server field.
View an automatically generated list of all devices included in the
140 NOC 78• 00 head module’s Ethernet configuration, displaying for each device:
IP addressing parameters whether the device’s IP addressing parameters are provided by the
140 NOC 78• 00 head module’s embedded DHCP server
Manually add remote devices to the DHCP service if necessary.
Click Apply to save changes and leave the window open, or click OK to save changes and close the window.
Enabling the FDR Service
Before enabling the FDR service, enable the FTP/TFTP services (
see page 162
To enable the 140 NOC 78• 00 head module’s FDR service, set the FDR Server field to Enabled.
To disable the service, toggle the same field to Disabled.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to apply edited properties to networked devices.
Any networked Ethernet device equipped with FDR client functionality can subscribe to the
140 NOC 78• 00 head module’s FDR service. The module can store up to 1 MB of FDR client operating parameter files. When this file storage capacity is reached, the module can not store any additional client FDR files.
The 140 NOC 78• 00 head can store FDR client files for up to 128 devices, depending on the size of each stored file. For example, if the size of each FDR client file is small — not more than 8 Kb
— the module could store up to the maximum of 128 parameter files.
S1A48993 10/2019
127
Configuring the 140NOC78100 Module
Manually Adding Remote Devices to the DHCP Service
Remote devices that are part of the 140 NOC 78• 00 head module’s Ethernet configuration — and which have subscribed to the 140 NOC 78• 00 head module’s IP addressing service — automatically appear in the Automatically Added Devices list.
Other remote devices — that are not part of the 140 NOC 78• 00 head module’s configuration — can be manually added to the module’s DHCP IP addressing service.
To manually add networked Ethernet devices — which are not part of the 140 NOC 78• 00 head module’s Ethernet configuration — to the module’s IP addressing service:
Step
1
2
3
Description
In the Address Server page, click the Add button in the Manually Added Devices field. Control
Expert adds an empty row to the list of Manually Added Devices.
In the new row, configure the following parameters for the client device:
IP Address Type in the IP address of the client device.
Identifier Type Select the type of value the client device will use to identify itself to the FDR server:
MAC address device Name
Identifier
Netmask
Depending upon the identifier type, type in the client device setting for the
MAC address or name.
Type in the client device subnet mask.
Gateway Type in the gateway address that remote devices can use to communicate with devices located on other networks. Use 0.0.0.0 if remote devices will not communicate with devices located on other networks.
Refer to the topic Configuring Properties in the Device Editor (see Quantum using EcoStruxure™
Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to apply edited properties to networked devices.
128
S1A48993 10/2019
Configuring the 140NOC78100 Module
Viewing the Auto-Generated DHCP Client List
The list of Automatically Added Devices includes a row for each remote device that is:
part of the 140 NOC 78• 00 head module’s Ethernet configuration
configured to subscribe to the 140 NOC 78• 00 head module’s DHCP addressing service
NOTE: You cannot add devices to this list in this page. Instead, use the configuration pages for the remote device to subscribe to this service.
The list of Automatically Added Devices contains the following information for each networked device:
Property
Device No
IP Address
DHCP
Identifier Type
Identifier
Netmask
Gateway
Description
The number assigned to the device in the Control Expert configuration.
The client device IP address.
TRUE indicates that the device subscribes to the DHCP service.
Indicates the mechanism used by the server to recognize the client
(MAC address or DHCP device name).
The actual MAC address or DHCP device name.
The client device subnet mask.
The IP address a DHCP client device will use to access other devices that are not located on the local subnet. A value of 0.0.0.0 constrains the
DHCP client device by allowing it to communicate only with devices on the local subnet.
S1A48993 10/2019
129
Configuring the 140NOC78100 Module
Subscribing to the DHCP Service for a Device that is Part of the Configuration
An Ethernet device — that is part of the 140 NOC 78• 00 head module’s Ethernet configuration — can subscribe to the module’s IP addressing service. To subscribe to this service, follow these steps:
Step Action
1 In the DTM Browser, select the 140 NOC 78• 00 head module that is connected to the remote device that you want to add to the DHCP service. In the following example, the module with the alias name of Q_NOC78000 is selected:
2
NOTE: The selected module is connected to the STB NIC 2212 network interface device bearing the alias name NIC2212_01, which is the module you want to add to the DHCP service.
With Q_NOC78100 selected in the DTM Browser, right-click and select Open in the pop-up menu.:
130
The Device Editor opens.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Step Action
3 In the navigation tree on the left side of the Device Editor, expand the Device List node and select the device for which you want to enable the DHCP service. In this example, select NIC2212_01:
4
Control Expert displays the properties for the selected remote device in the right pane of the window.
In the right pane of the window, select the Address Setting tab to display the following page:
S1A48993 10/2019
131
Configuring the 140NOC78100 Module
Step Action
5 In the Address Server area of this page, configure the following properties:
DHCP for this device Select Enabled
Identified by The choices are:
MAC Address, or
Device Name
6
Identifier
Netmask
Gateway
Select Device Name.
Control Expert has automatically added the device name
Q_NOC78100. For the purpose of this example, accept this default value.
Control Expert has automatically applied the same netmask used for the 140 NOC 781 00 head module. For the purpose of this example, accept the default value of 255.255.255.0.
For the purpose of this example, accept the default value of
0.0.0.0.
Click Apply to save changes, or click OK to save changes and close the window.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for more information on editing and saving property settings in this window.
132
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring the SNMP Agent
Description
The 140 NOC 78• 00 head module includes an SNMP v1 agent. An SNMP agent is a software component running on the communication module that allows access to the module's diagnostic and management information via the SNMP service.
SNMP browsers, network management software, and other tools typically use SNMP to access this data. In addition, the SNMP agent can be configured with the IP address of up to 2 devices, typically PCs running network management software, to be the target of event driven trap messages. These trap messages inform the management device of events such as cold start and unauthorized access.
Use the SNMP page to configure the SNMP agent in the 140 NOC 78• 00 head module. The
SNMP agent can connect to and communicate with up to 2 SNMP managers as part of an SNMP service. The SNMP service includes:
authentication checking, by the 140 NOC 78• 00 head module, of any SNMP manager that
sends SNMP requests management of event, or trap, reporting by the module
The SNMP page looks like this:
S1A48993 10/2019
133
Configuring the 140NOC78100 Module
To display this page:
3
4
Step
1
2
Description
Click Services in the navigation tree in the left panel of the Device Editor.
Result:The Services page opens.
In the Services page, set the SNMP field to Enabled. Then click Apply.
Result:SNMP appears in the navigation tree.
Select the SNMP in the navigation tree.
Click Apply to save changes and leave the window open, or click OK to save changes and close the window.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
Viewing and Configuring SNMP Properties
NOTE: The sysName SNMP parameter is neither editable nor visible in the Control Expert Ethernet
Configuration Tool software. By default, the sysName is set to the 140 NOC 78• 00 head module part number.
When DHCP is enabled and Device Name is selected as the DHCP identifier for the module, the
SNMP sysName parameter is not set to the module part number, but is instead the device name.
The following properties can be viewed and edited in the SNMP page:
Property
IP Address Managers:
IP Address Manager 1
Description
IP Address Manager 2
The IP address of the first SNMP manager to which the SNMP agent sends notices of traps.
The IP address of the second SNMP manager to which the SNMP agent sends notices of traps.
Agent:
Location
Contact
SNMP Manager
The device location (32 characters maximum)
Information describing the person to contact for device maintenance (32 characters maximum)
Select either:
TRUE: the Location and Contact information are editable in this page
FALSE: Location and Contact settings are not editable in this page
Community Names:
Get
Set
Password required by the SNMP agent before executing read commands from an SNMP manager. Default = Public.
Password required by the SNMP agent before executing write commands from an SNMP manager. Default = Public
134
S1A48993 10/2019
Configuring the 140NOC78100 Module
Property
Trap
Security:
Enable Authentication Failure
Trap
Description
Password an SNMP manager requires from the SNMP agent before the manager will accept trap notices from the agent. Default = Public
TRUE causes the SNMP agent to send a trap notice to the SNMP manager if an unauthorized manager sends a Get or Set command to the agent. Default = FALSE.
S1A48993 10/2019
135
Configuring the 140NOC78100 Module
Configuring Access Control
Description
Use the Access Control page to restrict access to the 140NOC78•00 head module in its role as either a Modbus TCP or EtherNet/IP server. When access control is enabled in the Services page, add the IP addresses of the following devices to the list of Authorized Addresses to permit communication with that device:
the 140NOC78•00 head module itself, so that the module can use EtherNet/IP explicit messaging for any of the following purposes:
obtaining diagnostic data resetting the module changing the IP address
any client device that may send a request to the 140NOC78•00 head module, in its role as either
Modbus TCP or EtherNet/IP server your own maintenance PC, so that you can communicate with the PLC via Control Expert to configure and diagnose your application, and to view the module’s web pages any target device to which the 140NOC78•00 head module may send a Modbus TCP explicit message
NOTE: You do not need to list the IP address of a target device to which the communication module may send an EtherNet/IP explicit message.
The following graphic depicts the Access Control page immediately after a new row has been added to the list of Authorized Addresses, but before the new item has been configured:
136
S1A48993 10/2019
Configuring the 140NOC78100 Module
To display this page:
Step
1
2
3
Description
Select the Services node in the navigation tree located in the left panel of the Device Editor.
Result:The Services page opens.
In the Services page, set the Access Control field to Enabled and click either OK or Apply.
Result:The Access Control node appears in the navigation tree.
Select the Access Control node in the navigation tree.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
Adding and Removing Devices in the Authorized Address List
To add a device to the Authorized Addresses list:
Step
1
2
3
4
5
Description
In the Access Control page, click Add.
A new row appears in the Authorized Addresses list, displaying:
a red exclamation point, indicating editing has begun
a placeholder IP address of 0.0.0.0
Double-click the placeholder IP address.
Result:The IP address field expands and becomes editable.
In the new IP address field, type the IP address of the device that will be able to access the
140NOC78•00 head module, then press Enter.
Repeat steps 1 through 3, above, for each additional device for which you want to grant access to the 140NOC78•00 head module.
Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User
Manual) for instructions on how to save your configuration edits.
To remove a device from the Authorized Addresses list, select its IP address in the list, then click
Remove. The selected IP address is removed.
S1A48993 10/2019
137
Configuring the 140NOC78100 Module
Configuring QoS Ethernet Packet Tagging
Description
The Ethernet communication module can be configured to perform Ethernet packet tagging. The module supports the OSI layer 3 Quality of Service (QoS) standard defined in RFC-2475. When you enable QoS, the module adds a differentiated services code point packet it transmits, thereby indicating the priority of that packet.
(DSCP) tag to each Ethernet
Use the QoS page to:
specify the source of QoS packet priority settings, and
view or edit the five QoS DSCP prioritization values
The QoS page looks like this:
138
To display this page:
Step
1
2
3
Description
Select the Services node in the navigation tree located on the left side of the
Device Editor. The Services page opens.
In the Services page, set the QoS Tagging field to Enabled, then click OK or
Apply. The QoS node appears in the navigation tree.
Select the QoS node in the navigation tree.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Specifying the Source of QoS Settings
The five QoS prioritization values can be set either from the communication module’s flash memory, or in this page. To specify the QoS configuration source, set the Use value from field to either:
Setting
Configuration 1
Description
The communication module uses the settings input in the Type of Traffic section of this page.
Flash 1 The communication module uses the settings saved in the module’s flash memory. The fields in the Type of Traffic section are read-only.
1. Schneider Electric recommends that QoS values be set in the configuration, and not by saving settings to flash memory. Settings saved to flash memory will be lost if the module is replaced.
NOTE: You can also edit QoS configuration settings by using explicit messages to set the attributes of the QoS CIP object
see page 284
.
Type of Traffic Settings
QoS tagging lets you prioritize Ethernet packet streams based on the type of traffic in that stream.
The communication module recognizes the traffic types described below. When the Use value from field is set to Configuration, you can edit the prioritization values in this page. Each traffic type can have a prioritization value from 0... 63.
Traffic Type
DSCP Value for IO Data Urgent Priority Messages (EtherNet/IP)
Default
55
DSCP Value for IO Data Scheduled Priority Messages (EtherNet/IP) 47
DSCP Value for IO Data High Priority Messages (Modbus TCP & EtherNet/IP) 43
DSCP Value for IO Data Low Priority Messages (EtherNet/IP)
DSCP Value for Explicit Message (Modbus TCP & EtherNet/IP)
31
27
To effectively implement QoS settings in your Ethernet network:
Use network switches that support QoS.
Consistently apply DSCP values to network devices and switches that support DSCP.
Confirm that switches apply a consistent set of rules for sorting DSCP tags, when transmitting and receiving Ethernet packets.
NOTE: The QoS settings for Scheduled, High, and Low priority messages also apply to input and output priority messages for a remote device. You can configure these settings for a remote device
(see Quantum using EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual) in the Device Editor by selecting a device connection node, then opening the connection’s General page.
S1A48993 10/2019
139
Configuring the 140NOC78100 Module
Configuring the Rapid Spanning Tree Protocol
Description
Ethernet ports 3 and 4, located on the front of the 140 NOC 78• 00 head module, support the Rapid
Spanning Tree Protocol (RSTP). RSTP is an OSI layer 2 protocol defined by IEEE 802.1D 2004.
RSTP performs 2 services:
It creates a loop-free logical network path for Ethernet devices that are part of a topology that
includes redundant physical paths.
It automatically restores network communication — by activating redundant links — in the event the network experiences a loss of service.
RSTP software, operating simultaneously in all network switches, obtains information from each switch, which enables the software to create a hierarchical logical network topology. RSTP is a flexible protocol that can be implemented on many physical topologies, including ring, mesh, or a combination of ring and mesh.
Use the RSTP → General and the RSTP → Advanced pages to configure RSTP for the embedded
Ethernet switch in the 140 NOC 78• 00 head module.
NOTE: RSTP can be implemented only when all network switches are configured to support RSTP.
The RSTP → General page looks like this:
140
S1A48993 10/2019
The RSTP → Advanced page looks like this:
Configuring the 140NOC78100 Module
NOTE: The Advanced page is available only when you enable advanced mode.
S1A48993 10/2019
141
Configuring the 140NOC78100 Module
To display these pages:
Step
1
2
3
Description
Select the Services node in the navigation tree located on the left side of the Device Editor.
Result:The Services page opens.
In the Services page, set the RSTP field to Enabled, then click OK or Apply.
Result: The RSTP node appears in the navigation tree.
Select the RSTP node in the navigation tree, then click on either the General or Advanced tab to display that page.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
Configuring RSTP Properties
The following properties can be viewed and edited in the RSTP → General page:
Property
RSTP Operational State:
Bridge Priority
Description
Select one of the following values in the drop-down list:
Root (0)
Backup Root (4096)
Participant (32768)
NOTE: Network switches running RSTP software periodically exchange information about themselves using special packets called Bridge
Protocol Data Units (BPDUs), which act as a heartbeat. The Bridge
Priority value is contained in the BPDU and establishes the relative position of the switch in the RSTP hierarchy.
The following properties can be viewed and edited in the RSTP → Advanced page:
Property
Bridge Parameters:
Maximum Age Time
Description
Transmit Hold Count
Hello Time
This value is set to The length of time, from 6 to 40 seconds, that the switch waits for receipt of the next hello message, before initiating a change to the RSTP topology. Default = 40 s.
The maximum number of BPDUs, from 1 to 40, that the switch can transmit per second. Default = 40.
(read-only) The frequency—set at 2 seconds—that the embedded switch sends heartbeat BPDUs.
142
S1A48993 10/2019
Configuring the 140NOC78100 Module
Property
Port Parameters (These properties can be separately configured for ports 3 and 4):
RSTP (read-only) This property is set to Enabled in the Services page.
Priority
Description
Path Cost
The priority assigned to the switch port, an integer from 0 to 240 in increments of 16. Default = 0. This value is used by the RSTP process if it needs to break a tie between two ports on the same switch when identifying a:
root port: the port on a non-root switch that is closest to the root bridge in terms of path cost, or designated port: the port at one end of a network segment through which traffic passes on its way to the root bridge
The method used to determine the path cost through the embedded switch. Values include:
Auto: The RSTP protocol automatically assigns a value to the switch by operation of the RSTP algorithm.
Manual: Input the RSTP cost — an integer from 1 to 200000000 — in the Value field.
Edge Port
Point to Point
(read-only) Set to a fixed value of Auto. The RSTP process automatically determines if the port is an RSTP edge port.
(read-only) Set to a fixed value of Auto. The RSTP process automatically determines if the port is an RSTP point-to-point port.
S1A48993 10/2019
143
Configuring the 140NOC78100 Module
Configuring the Service/Extend Port
Introduction
The 140NOC78100 control head module includes a service/extend port that can be configured to support 3 functions:
Extended Network: If you configure the service port for an extended network, you can extend the device network by adding another distributed I/O network.
Port Mirroring: If you configure the service port for port mirroring, you can connect to this port via a PC and sniff (using Ethereal, WireShark, etc.) the traffic that is traveling through the other ports, including the internal port that is connected to the CPU.
Access Port: If you configure the service port for access, diagnostic information is provided via
EtherNet/IP or Modbus explicit messaging (
see page 227
see page 133
.
NOTE: In access port mode, the IP address of the port is the same as that of the control network.
The Service Port page — when configured as an Extended Network — looks like this:
144
S1A48993 10/2019
Configuring the 140NOC78100 Module
The Service Port page — when configured for Port Mirroring — looks like this:
Displaying the Service Port Page
To display the Service Port page:
Step
1
2
Action
Click Service Port in the navigation tree, and set the Service Port Mode to one of the following:
Extended Network
Port Mirroring
Access Port
Click Apply to save changes and leave the window open, or click OK to save changes and close the window.
S1A48993 10/2019
145
Configuring the 140NOC78100 Module
Service Port Page Properties
The following properties can be viewed and edited in the Service Port → Extended Network page:
Property
Internal Port
ETH 2
ETH 3
ETH 4
Description
These ports are disabled and cannot be edited.
The following properties can be viewed and edited in the Service Port → Port Mirroring page:
Property
Internal Port
ETH 2
ETH 3
ETH 4
Description
These ports are editable:
To enable these ports, click Yes in the Enabled field.
To disable these ports, click No in the Enabled field.
The extended network IP address and sub-network mask in the IP forwarding service are disabled.
146
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring Time Synchronization
Introduction
The network time service (SNTP) synchronizes the clock in the 140NOC78000 distributed I/O head module to that of the time server. The synchronized value is used to update the clock in the PLC.
Typical time service configurations utilize redundant servers and diverse network paths to achieve high accuracy and reliability.
Use the time service for:
event recording (sequence events)
event synchronization (trigger simultaneous events) alarm and I/O synchronization (time stamp alarms)
Time Synchronization Service Features
Some features of the time synchronization service are:
periodic time correction obtained from the reference-standard time server
automatic switch over to a backup time server if a detected problem occurs with the normal time server system controller projects use a function block to read the accurate clock, a feature that allows project events or variables to be time stamped
estimated time stamping accuracy of:
5 msec for 140 CPU 651 •0s and later
10 msec for other CPUs
local time zone is configurable, including daylight savings time
Time Synchronization Process
The 140NOC78•00 control head module contains an SNTP client, which provides time synchronization.
Action
An SNTP client requests a time synchronization signal from an SNTP server.
(The request is sent over an Ethernet network.)
The SNTP client stores the time.
Result
The SNTP server responds with a signal.
The SNTP client sends a message to the controller’s clock system counter. The controller updates its internal clock.
Use the R_NTPC function block in either MAST, FAST, or Interrupt sections to read the clock from the PLC application.
S1A48993 10/2019
147
Configuring the 140NOC78100 Module
On an Ethernet network, all controllers should be synchronized with the same SNTP server.
Power Up
To establish the accurate Ethernet system network time, the system performs the following at power up:
requires the 140NOC78000 head module to boot uses the 140NOC78000 head module to obtain the time from the SNTP server
requires a predefined interval until time is accurate; your configuration determines how long before time is accurate may require several updates to achieve peak accuracy
Once an accurate time is received, the service sets the status in the associated time service register.
The time service clock value starts at 0 until fully updated from the 140NOC78100 head module.
Model
Modicon Quantum with Control Expert
Starting Date
January 1st 1980 00:00:00.00
Stop or Run PLC
Stop and run have no effect on the accuracy of the clock.
Stop and run have no effect on the update of the clock.
A transition from one mode to the other has no effect on the accuracy of the Ethernet system network time.
Download Application
The status clock value associated with the time service register in the CPU is reinitialized after an application is downloaded or after an SNTP server swap.
There will be 2 polling periods before the time is accurate.
148
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring the Time Synchronization Service
To configure the time synchronization service:
Step
1
2
3
4
5
Action
Open the 140NOC78000 head module in the DTM browser.
In the Services page, set the Network Time Service field to Enabled.
Click the Network Time Service node in the Services navigation tree in the left panel.
Enter changes in the appropriate fields on the Network Time Service configuration page. The table below describes the configuration page parameters.
Click Apply to save changes, or click OK to save changes and close the window.
S1A48993 10/2019
149
Configuring the 140NOC78100 Module
Time Synchronization Configuration Parameters
Field Parameter
NTP Server Configuration
Primary NTP Server IP
Address
Secondary NTP Server IP
Address
Polling Period
Action
Enter a valid IP address.
Enter a valid IP address.
The polling period is the time (in seconds) between updates from the
SNTP server. To obtain optimal accuracy (and if your network allows), reduce the polling period to a small value. The default is 5 seconds.
Enter a value:
min = 1 sec
max = 120 sec
Time Zone
Time Zone
Time Zone Offset
Select the desired time zone from the drop-down list. The default value is your current system’s time zone (as found in Windows). You can also select Custom Time Zone.
If you selected Custom Time Zone, enter a value in the range of
(24 hours * 60 minutes - 1) [1-minute step].
Daylight Saving
Automatically adjust clock for daylight saving change
Start Daylight Saving
End Daylight Saving
Disabled: In the Start Daylight Saving and End Daylight Saving fields, enter the month, day of week, and occurrence range from the respective drop-down lists. Disabled is the default.
Enabled: The 140 NOC 78• 00 head module automatically corrects the local time to account for daylight saving time. The Start Daylight Saving and End Daylight Saving fields are disabled because their times are automatically changed in the spring and fall every year.
Month: January to December
Day of Week: Sunday to Saturday
Occurrence: 1 to 5
Month: January to December
Day of Week: Sunday to Saturday
Occurrence: 1 to 5
CPU Time Update
Update CPU time with this module
Select True or False from the drop-down list. False is the default.
150
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring the IP Forwarding Service
Introduction
The 140NOC78100 head module uses an IP forwarding service to provide transparency between networks in a Quantum EIO system. Use Control Expert to configure the IP forwarding service, including configurable parameters for control network, fieldbus network, extended network, or default gateway.
1 Configure ports ETH 3 and ETH 4 (control network ports).
2 Configure port ETH 2 (interlink port).
3 Configure port ETH 1 (service/extend port).
4 Configure the default gateway, which is the IP address of the control network router. This router is not a
Quantum EIO device; rather, it is a customer device that typically connects the control network to other networks higher up in the Ethernet infrastructure.
S1A48993 10/2019
151
Configuring the 140NOC78100 Module
Displaying the IP Forwarding Service Parameters
To display the IP Forwarding page and access the parameters:
Step
1
2
3
4
Action
Click Services in the navigation tree in the left panel of the Device Editor.
Result: The Services page opens.
In the Services page, set the IP Forwarding field to Enabled. Then click Apply.
Result: IP Forwarding appears in the navigation tree.
Click IP Forwarding in the navigation tree.
Click Apply to save changes and leave the window open, or click OK to save changes and close the window.
NOTE: The control network and device network need to have unique IP addresses.
NOTE: To use the service port in Extended Network mode, disable the IP forwarding service feature first
see page 123
) , then select the service port mode as Extended Network. Refer to
Configuring the Service/Extend Port (
see page 144
152
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring Electronic Mail Notification
Introduction
The electronic mail notification service allows controller-based projects to report alarms or events.
The controller monitors the system, and can automatically create an electronic mail message alert with data, alarms, and/or events. Mail recipients can be either local or remote.
Based on predefined events or conditions, messages are created using the MSTR function
block.
The email message is constructed from predefined headers, plus variables and text (a maximum of 238 bytes). This message is sent directly from the automation system to the local email server.
Mail headers contain common predefined items — recipient list, sender name, and subject.
These items can be updated by an authorized administrator.
NOTE: Test the email block before using it in an application. If you improperly configure an email
MSTR block to receive an email when a detected problem occurs, the email may not be sent as expected.
Mail System Types
The simple mail transfer protocol (SMTP) provides 2 mechanisms for transmitting email messages:
direct connection
relay system
Mechanism Condition direct connection
Sender and receiver are connected to the same transport service.
relay system Sender and receiver are not connected to the same transport service.
Result
Email messages are sent to host.
Email messages are relayed from one server to another server.
To relay messages, the SMTP server uses the addresses of the:
destination host destination mailbox
S1A48993 10/2019
153
Configuring the 140NOC78100 Module
Mail Service Client
The 140NOC78100 control head module includes an SMTP client. When the module receives a specific request from the project, it sends an email message to the mail server.
154
S1A48993 10/2019
Configuring the 140NOC78100 Module
Displaying the SMTP Page
To display the SMTP page:
Step
1
2
3
4
Action
Click Services in the navigation tree in the left panel of the Device Editor.
Result: The Services page opens.
In the Services page, set the SMTP field to Enabled. Then click Apply.
Result: SMTP appears in the navigation tree.
Select SMTP in the navigation tree.
Click Apply to save changes and leave the window open, or click OK to save changes and close the window.
S1A48993 10/2019
155
Configuring the 140NOC78100 Module
Configuring the Mail Service
A user-defined event or condition triggers the MSTR block to create a message. Each message uses one of 3 user-defined headers. Each message sent from the controller may contain text and variable information (with a maximum of 238 bytes).
The project selects the appropriate header. Each header contains:
sender’s name
list of recipients subject
The following properties can be viewed and edited in the SMTP page:
Property
SMTP Server IP Address
SMTP Server Port
Password Authentication
Description
Enter the IP address of the mail server.
The default TCP port number for SMTP is 25. Configure the port as specified by your local mail server.
If security is needed, enable Password Authentication by selecting the check box.
Enter values for:
Login
Any printable character allowed
64-character maximum
Password
Any printable character allowed
64-character maximum
NOTE: You can use an optional login (system ID) and password to authenticate the connection to the SMTP mail server. The SMTP-supported authentication method is LOGIN.
156
S1A48993 10/2019
Configuring the 140NOC78100 Module
Property
Email Header
Description
Each header contains:
Sender’s ID in the From field
32-character maximum (no spaces)
List of recipients in the To field
Separate each email address with a comma.
128-character maximum
Fixed part of message in the Subject field 1
32-character maximum
1 The Subject field consists of 2 parts:
1. Fixed (32-character maximum)
2. Dynamic (206-character maximum)
An authorized administrator can define and update the text and variable information.
Define the 3 mail headers to indicate different levels of importance. For example:
Header 1 could be Detected problem reported by PLC 10.
Header 2 could be Notification from substation 10.
Header 3 could be Info message from water system.
Listing different recipients in each of the 3 headers allows the right information to flow quickly to the correct recipients. The project adds pertinent information such as the specific device, process, or location. This pertinent information is added to the body of the mail message. Then, the complete message is sent to an electronic mail server for distribution to recipients. These recipients could be engineers, managers, or process owners.
Using the MBP__MSTR Block for Mail Service
Each operation is designed by a code. To send an email message, use the MBP_MSTR block with function code 13.
S1A48993 10/2019
157
Configuring the 140NOC78100 Module
MBP_MSTR Parameters
The following table describes the MBP_MSTR parameters:
Parameter enable abort active error success control databuf
Data Type none none none none none
INT, UINT
INT, UINT
Description on = enables selected MBP_MSTR operation on = terminates active MBP_MSTR operation on = instruction is active on = MBP_MSTR operation is terminated prior to completion on = operation successful
Control block is the first of several network-dependent, contiguous holding words and the first of 9 contiguous words entered in the top node.
The remaining 8 words are: displayed: identifies one of the MBP_MSTR = 13 first implied displays detected error status (See Mail Service
Detected Error Codes (see Quantum using
EcoStruxure™ Control Expert, Ethernet Network
Modules, User Manual) .) second implied third implied fourth implied fifth implied sixth implied seventh implied eighth implied displays length (number of words transferred) not used high byte: slot address of the 140NOC78100 head module or 0xFE for the 140 CPU 651 •0 low byte: 0 (not used) not used not used not used not used
The databuf parameter is the address of the buffer including the data inserted into the body of the email message. The data should be in ASCII format starting at the second word.
NOTE:
1. The least significant byte of the first word contains a valid (configured) mail header (should be value 1, 2, or 3).
2. The most significant byte of the first word contains the length of the dynamic part of the message’s subject field. The length is between 0 and 238 characters.
158
S1A48993 10/2019
Configuring the 140NOC78100 Module
Databuf Parameter Description
The first word of the databuf parameter contains the following information:
Byte Number
1 (least significant byte)
2 (most significant byte)
Description mail header
Nb n of extra characters in the subject
Value
{1, 2, 3} user-defined (between 0 and
238)
The second and subsequent words (maximum 119) contain the data (ASCII format) that will be copied into the email message. The first n characters are added to the configured email subject.
The remaining characters ( 2* N -2n ) are part of the message body. N represents the number of words transferred.
S1A48993 10/2019
159
Configuring the 140NOC78100 Module
Electronic Mail Notification Service Subtree
The electronic mail delivery service subtree contains the following objects:
Service emailIndex (1) smtpStatus (2) smtpSrvAddr (3) smtpMailSentCnt (4) smtpErrCnt (5) smtpLastErr (6) smtpLastMailElapsedTime (7) smtpLnkSrvStatus (8) smtpSrvChkFailCnt (9)
Description index value in the email service table global status of the SMTP service:
idle (1): no configuration
operational (2): operational and running stopped (3): stopped
IP address of the remote SMTP server total number of emails sent to the network and successfully acknowledged by the server total number of emails:
not sent to the network
sent but not successfully acknowledged by the server
The smtpLastErr (6) object details the detected errors.) last detected error code (See details in the Configuring a
Commuinication Module with TFE {Private MIB topic.) number of seconds elapsed since last successful email sent status of link between communication module and remote
SMTP server:
NOK (1) = SMTP server cannot be reached.
OK (2) = SMTP server can be reached.
number of times link to SMTP server has been detected as down
Operating Modes and Sending Requests
Because the controller program sends the email request, a controller cannot send an email message either while in the stopped mode or while downloading a project. As soon as the controller is in run mode, the function block sends a request during the first project scan.
Diagnostic counters are reset to 0 after either a power-up, a project download, or a reconfiguration of the mail service.
160
S1A48993 10/2019
Configuring the 140NOC78100 Module
Security Section 4.6
Security
Security Features
Security and HTTP, FTP, and TFTP Services
The module uses HTTP services to provide access to its embedded Web pages. The module uses
FTP and TFTP services to support various features including firmware upgrades, FDR services, and Ethernet remote IO.
The module’s HTTP, FTP, and TFTP services can be disabled or enabled using the DTM Browser
Security screen.
HTTP, FTP, and TFTP services are disabled by default in DTM instances created using
PlantStruxure EIO Version 1.5 and Unity Pro 8.0 or later. They are enabled by default in instances created using earlier versions of Unity Pro.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
You can use Control Expert to enable or disable HTTP, FTP, and TFTP services as described in the following procedure.
If the HTTP, FTP, or TFTP services have been enabled with Control Expert, they can also be
enabled or disabled at run time using an MBP_MSTR block with operation code FFF0 (hex)
see page 248
S1A48993 10/2019
161
Configuring the 140NOC78100 Module
Using Control Expert to Enable and Disable Firmware Upgrade & FDR and Web Access Services
Perform the following steps to enable or disable FTP/TFTP or HTTP services on the module.
Step
1
2
3
4
5
6
Action
In the Control Expert main menu, select Tools → DTM Browser to open the DTM Browser.
Confirm that the DTM you want to use is not connected to the actual communication module
or device. If necessary, disconnect the DTM from the module or device ( see page 90 ) .
In the DTM Browser, select the module. Right-click and select Open to open the
Device Editor.
Click the Security node in the navigation tree in the left panel to open the Security screen.
On the Security screen, choose the appropriate setting: (Enabled or Disabled) for the service or services.
Click:
Apply to save the changes and keep the window
- or -
OK to save the changes and close the window
The edits will not take effect until they are successfully downloaded from your PC to the CPU and from the CPU to the communication modules and network devices.
162
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring the 140 NOC 78• 00 Head Module as an EtherNet/IP Adapter Section 4.7
Configuring the 140 NOC 78• 00 Head Module as an
EtherNet/IP Adapter
Introduction
This section describes how to configure the 140 NOC 78• 00 head module to act as an EtherNet/IP adapter, using a functionality called local slaves. local slave . The head module supports up to 3 instances of
In its role as a EtherNet/IP adapter, the module initiates no messages. Instead, it responds to:
implicit messaging requests from a scanner device in the network
explicit messaging requests—directed to the head module’s assembly object from other devices on the network
see page 278
—
NOTE: If no local slave instance is enabled, the head module can respond to explicit messaging requests directed at its CIP objects other than the assembly object.
What Is in This Section?
This section contains the following topics:
Topic
Introducing the Local Slave
Configuring a Local Slave
Local Slave Inputs and Outputs
Device List Configuration and Connection Summary
Configuring Device Properties
Configuring Device IP Address Settings
Configuring Modbus TCP Request Settings
Configuring Communication Module Connection Settings
EtherNet/IP Connection Information
Page
S1A48993 10/2019
163
Configuring the 140NOC78100 Module
Introducing the Local Slave
Local Slave Networking Example
The Ethernet communication module supports up to 3 instances of the local slave functionality. The local slave functionality allows other scanners on the network to read from, and write to, the
Ethernet communication module using implicit messaging. Each local slave instance can accept one exclusive owner connection and one listen only connection. Through a local slave, a remote scanner can access the communication module’s CIP assembly object
see page 278
. The local slave function is especially beneficial for peer-to-peer data exchanges at a repetitive rate.
NOTE:
The Ethernet communication module can provide 3 local slave adapter instances, while
simultaneously performing as a scanner. These roles are not mutually exclusive.
The local slave is exclusively an EtherNet/IP functionality.
164
S1A48993 10/2019
Configuring the 140NOC78100 Module
In the following example, the local slave instance is part of the following topology:
12
1 primary PLC (containing remote I/O, distributed I/O, and control head modules)
2 standby PLC
3 DRS connecting remote I/O and distributed I/O devices to the main ring
4 distributed I/O device (Advantys STB island)
5 third-party PLC
6 PC
7 remote I/O devices
8 main ring
9 Modicon X80 racks — connected to the PLCs via copper cable — containing BMX NRP 020• fiber converter modules to extend the distance between the 2 PLCs beyond 100 m
10 control network (connected to the primary and standby PLCs)
11 CPU-sync link (fiber cable)
12 fiber cable connecting the two BMX NRP 020• modules to extend the distance between the 2 PLCs beyond
100 m
S1A48993 10/2019
165
Configuring the 140NOC78100 Module
This sample configuration includes the following devices:
A primary PLC (1) incorporates the 140NOC78000 head module with one local slave instance
enabled. The PLC scans I/O data from remote devices (4).
A standby PLC (2) listens to the scan of the primary PLC’s local slave by the third-party PLC (5).
DRS (3)
An Advantys STB island (4) includes an STB NIC 2212 EtherNet/IP network interface module plus 8 I/O modules.
A third-party scanner (5) lacks adapter capability and therefore cannot itself be scanned by the primary PLC:
The scanner collects data from sources that are not part of this network.
The scanner writes data to inputs of the primary PLC’s local slave.
The scanner scans the primary PLC’s local slave’s output data through an exclusive owner connection.
A PC (6) runs this software:
Control Expert
the Control Expert configuration tool
Advantys configuration software
NOTE:
Because the third-party scanner (5) and the standby scanner (2) both receive the same data
from the local slave, confirm that the requested packet interval (RPI) settings of the third-party scanner’s exclusive owner connection and the standby scanner’s listen-only connection are the same.
By enabling a local slave on the primary PLC (1):
The PLC (1) allows the third-party PLC (5) to write to it at a repetitive rate, even if the PLC is not capable of acting as an adapter.
The standby PLC (2) is able to scan the primary PLC (1) at a repetitive rate, rather than through application-intensive explicit messaging.
The following topics show you how to use Control Expert software installed in the PC (6) to configure a local slave, and to create input and output items in support of the peer-to-peer data transfers between and among scanners.
166
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring a Local Slave
Description
The Ethernet communication module presents 3 identical Local Slave configuration pages. Use each page to configure a separate local slave instance. Create a local slave instance by:
enabling and naming the local slave specifying the size of local slave input and output assemblies configuring local slave variable names
To display this page, select one of the 3 Local Slave nodes in the navigation tree located on the left side of the Device Editor.
NOTE: Refer to the topic Configuring Properties in the Device Editor (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) for instructions on how to edit properties.
The following steps describe a sample configuration for Local Slave 1. Your configuration may be different.
Configuration Example: Local Slave 1
In the sample network configuration, the application in the third-party PLC produces data, which is available in the PLC’s Ethernet communication module as inputs. In this example, the third-party device produces the following information:
production totals for manufacturing line A
production totals for manufacturing line B the number of production interruption events for line A the number of production interruption events for line B
Any information that needs to be passed to the third-party device — for example, confirmation that data from the third-party device has been received by the PLC — is accessible in the third-party device as input data. In this example, the third-party device is programmed to scan Local Slave 1 for this confirmation.
When configuring inputs and outputs in both the local slave and the third-party PLC, associate inputs and outputs as follows:
Associate these local slave items: outputs (T -> O) — assembly instance 101 inputs (O -> T) — assembly instance 102 with these third-party PLC items: inputs — assembly instance 101 outputs — assembly instance 102
S1A48993 10/2019
167
Configuring the 140NOC78100 Module
The configured Local Slave page looks like this:
168
S1A48993 10/2019
Configuring the 140NOC78100 Module
Enabling and Naming the Local Slave
Use the Properties section of the Local Slave page to enable (or disable) and identify the local slave.
Setting
Number
Active Configuration
Comment
Connection bit
Description
The unique number — or identifier — assigned to the device. By default, Control
Expert assigns:
000 = local slave 1
001 = local slave 2
002 = local slave 3
In this example, accept the default 000.
Enabled activates the local slave.
Disabled de-activates the local slave, but saves the current local slave settings.
In this example, select Enabled.
An optional free text comment field up to 80 characters maximum.
In this example, leave blank.
Auto-generated integer (0...127) indicating the offset of the connection’s:
health bit, located in the module’s input area
control bit, located in the module’s output area
Note: This setting is auto-generated after the local slave settings are input and the network configuration is saved.
Configuring the Size of Local Slave Input and Output Assemblies
Use the Assemblies section of the Local Slave page to configure the size of the local slave inputs and outputs. The assembly numbers are non-editable, and are assigned by Control Expert as follows:
Assembly number
101
102
103
199
111
112
113
200
121
Local slave number
1
1
1
1
2
2
2
2
3
Used for connection
T->O 1
O->T Exclusive Owner
Configuration
O->T Listen Only
T->O
O->T Exclusive Owner
Configuration
O->T Listen Only
T->O
1. In this table:
O indicates the originator — or scanner — device.
T indicates the target — or adapter — device.
S1A48993 10/2019
169
Configuring the 140NOC78100 Module
Assembly number
122
123
Local slave number
3
3
Used for connection
O->T Exclusive Owner
Configuration
201 3 O->T Listen Only
1. In this table:
O indicates the originator — or scanner — device.
T indicates the target — or adapter — device.
The Local Slave assembly settings include:.
Setting
Outputs (T->O)
Outputs (T->O) Size
Inputs (O->T)
Inputs (O->T) Size
Configuration
Configuration Size
Description
A read-only value (see preceding table).
In this example, 101.
The maximum size — in bytes — reserved for local slave outputs.
An integer from 1 to 509.
In this example, only 2 output bytes are used: type in 2.
A read-only value (see table, above).
In this example, 102.
The maximum size — in bytes — reserved for local slave inputs. An integer from 0 to 505.
In this example, only 8 input bytes are used: type in 8.
A read-only value (see table, above).
In this example, 103.
A read-only value set to 0.
NOTE: When using explicit messaging to read the Ethernet communication module’s assembly object, allocate sufficient room for the response, because the size of the response will equal the sum of: the assembly size + Reply service (1 byte) + General Status (1 byte)
170
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring Local Slave I/O Variable Names
Each input and output that Control Expert creates for your application has both a non-editable structure name (used by Control Expert to internally identify input and output items) and an editable variable name.
Use the I/O Structure Name section of the Local Slave page to:
view and edit local slave input and output variable names
view non-editable local slave structure names
The following property settings have been made in this example:
Setting
Input:
Structure Name
Description
Variable Name
The read-only name for input structures. By default, it is the concatenation of:
the prefix T_
the alias device name — in this case Q_NOC78100 the device number — in this case 01 the suffix _IN
In this case, the default would be T_Q_NOC78100_01_IN.
The editable base name for input variables. By default, it is the concatenation of:
the alias device name — in this case Q_NOC78100
the device number — in this case 01 the suffix _IN
In this case, the default would be Q_NOC78100_01_IN.
For this example, accept the default variable name.
Output:
Structure Name
Variable Name
The read-only name for output structures. By default, it is the concatenation of:
the prefix T_
the alias device name — in this case Q_NOC78100 the device number — in this case 01
the suffix _OUT
In this case, the default would be T_Q_NOC78100_01_OUT.
The editable base name for output variables. By default, it is the concatenation of:
the alias device name — in this case Q_NOC78100
the device number — in this case 01 the suffix _OUT
In this case, the default would be Q_NOC78100_01_OUT.
For this example, accept the default variable name.
If you have edited one or more variable names, you can restore the default variable names by clicking the Default Name button.
S1A48993 10/2019
171
Configuring the 140NOC78100 Module
Local Slave Inputs and Outputs
Introduction
The Ethernet communication module serves as an adapter when the Active Configuration field is set to Enabled in the configuration window for one (or more) of the module’s local slave nodes.
When a local slave instance of an Ethernet communication module is enabled, the designated memory location allocated to that instance is exposed to, and can be accessed by, other devices.
The I/O data exchange, between the remote device and the local slave, is configured as part of the remote device’s configuration settings.
Configuring the I/O Items
You can configure input and output items in groups of 1 or more single bits, 8-bit bytes, 16-bit words, 32-bit dwords, or 32-bit IEEE floating values. The number of items you create depends upon the data type and size of each item.
The process for creating and defining I/O items for the local slave is the same as for any adapter class device, and depends upon the type of items you wish to create.
In support of the ongoing configuration example, the following items are required:
4 input word items
1 output word item
NOTE: The items created, below, are designed to hold data received from, or sent to, the thirdparty scanner. In addition to these items, it is necessary to include logic in the application programs in which the Ethernet communication module and the third-party scanner, respectively, are included. Writing this code is beyond the scope of this example.
172
S1A48993 10/2019
Creating Input Word Items
To create input items for local slave 01:
Step Action
1 Select the Input tab to open that page:
Configuring the 140NOC78100 Module
NOTE: In this example, each row represents a byte. Because the items you create will be a 16-bit words, each item consists of 2 rows.
2 In the Default Item Name Root input box type: ProductionTotal_LineA.
3 Starting at the beginning of the table, select the first two rows: 0 and 1:
S1A48993 10/2019
173
Configuring the 140NOC78100 Module
Step Action
4 Click the Define Item(s) button.
Result: The Item Name Definition dialog opens:
5 Select WORD as the New Item(s) Data Type, then click OK.
Result: A new item is created:
174
6 Click Apply to save the new items, and leave the page open.
7 Repeat steps 2 - 6 for each new word item you need to create. In this example, that includes the following items:
Rows 2-3, Default Items Name Root: ProductionTotal_LineB
Rows 4-5: Default Items Name Root: Events_LineA
Rows 6-7: Default Items Name Root: Events_LineB
8 Create output words.
S1A48993 10/2019
Creating Output Word Items
To create output items for local slave 01:
Step
1
Action
Click the Output tab to open the following page:
Configuring the 140NOC78100 Module
2
3
NOTE: In this example, each row represents a byte. Because the only item you will create is a 16bit word, you will select 2 rows.
In the Default Item Name Root input box type: DataReceived.
Starting at the beginning of the table, select the first 2 rows, 0 and 1:
S1A48993 10/2019
175
Configuring the 140NOC78100 Module
Step
4
Action
Click the Define Item(s) button.
Result: The Item Name Definition dialog opens:
5 Select WORD as the New Item(s) Data Type, then click OK.
Result: A new item is created:
176
6
7
Click OK to close the Items window.
Select File → Save to save your edits.
S1A48993 10/2019
Configuring the 140NOC78100 Module
Using Local Slave Inputs and Outputs
The inputs and outputs created, above, are used as follows:
The third-party device updates values of the following variables:
ProductionTotal_LineA
ProductionTotal_LineB
Events_LineA
Events_LineB
The Ethernet communication module updates value of the DataReceived variable in the thirdparty device at the configured RPI.
S1A48993 10/2019
177
Configuring the 140NOC78100 Module
Device List Configuration and Connection Summary
Introduction
The Device List page displays read-only properties that summarize the:
configuration data, including:
input data image
output data image maximum and actual numbers for devices, connections and packets recommended PLC scan times
Modbus requests and EtherNet/IP connection data
To display this page, first select a communication module in the DTM Browser then, in the left pane of the Device Editor, select the Device List node.
Configuration Data
The Device List page displays the following configuration data:
Name
Input
Input Offset
Description Value set by...
Input Reserved Size
Input Current Size
The starting address for inputs (%MW index)
The total number of words configured for inputs
(Max size)
The cumulative number of inputs (Input size) actually used in the application
Configuration page in Control
Expert
Configuration page in Control
Expert
General page in the
Device Editor for a selected remote device and connection
Output
Output Offset The starting address for outputs (%MW index)
Output Reserved Size The total number of words configured for outputs
(Max size)
Output Current Size The cumulative number of outputs (Output size) actually used in the application
Configuration page in Control
Expert
Configuration page in Control
Expert
General page in the
Device Editor for a selected remote device and connection
Note: When configuring an offset and a reserved size for both inputs and outputs, be sure that inputs and outputs do not overlap.
178
S1A48993 10/2019
S1A48993 10/2019
Configuring the 140NOC78100 Module
Name
Configuration Size
Description Value set by...
Maximum Number of
Devices
Current Number of
Devices
Maximum Number of
Connections
The maximum number of devices that can be added to the configuration.
The number of devices currently in the configuration.
The maximum number of connections that can be managed by the module.
predefined network design in the Control
Expert Device Editor predefined
Current Number of
Connections
Maximum Number of
Packets
Current Number of
Packets
The number of connections in the configuration.
network design in the Control
Expert Device Editor
The maximum number of packets per second the module is able to manage.
predefined
The number of packet/s that will be generated by the current configuration.
PLC Scan Time (Quantum PLCs only) network design in the Control
Expert Device Editor predefined Minimum PLC Scan
Time
The estimated cycle time to process inputs and outputs, equal to the sum of estimates for communication over both the backplane and the network.
Module Exchange Time The estimated additional time contributed by the
EtherNet/IP module to perform the I/O management. This value is included in the
"minimum PLC scan time" value.
predefined
Request / Connection Data
The Device List page displays the following request and connection data:
Name
Connection Bit
Device
Type
Address
Rate
Packets / s
Offset In
Description
The offset for both the connection’s health bit and control bit.
The device Number as set in the Properties configuration page for the local slave or remote device.
The target device type:
Ethernet/IP
Local Slave
Modbus TCP
The target device IP Address.
NOTE: Only for remote devices. Not applicable for local slaves.
The RPI (for EtherNet/IP) or the Repetitive Rate (for Modbus TCP), in ms.
The number of Ethernet packets per second generated by this remote device.
The starting %MW address for inputs to this device.
179
Configuring the 140NOC78100 Module
Name
Size In
Offset Out
Size Out
Description
The number of input words configured for this remote device.
The starting %MW address for outputs from this device.
The number of output words configured for this remote device.
180
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring Device Properties
Overview
Use the Properties configuration page to view and configure settings for a remote device. These settings will:
assign a numeric address to the device include or exclude device inputs and outputs in the Control Expert project
specify variable and structure names for device inputs and outputs determine how I/O items will be managed
To display this page, select the device name, which is found under the Device List node in the left pane of the Device Editor, then click the Properties tab.
NOTE: Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
Device Properties
The Properties page includes the following settings:
Setting
In the Properties section:
Number
Description
Active Configuration
The relative position of the device in the list, from 0 to 127.
By default, this number is assigned sequentially to devices in the project, beginning with the number 000 that is assigned to the first local slave.
Enable: adds this device to the Control Expert project configuration
Disable: removes this device from the Control Expert project configuration
NOTE:
Changing this setting also changes the addresses of items in project memory. Selecting Enable adds the device’s inputs and outputs to project memory; selecting Disable removes these inputs and outputs from memory.
Alternatively, if you enable the I/O Communication Control service, you can turn ON and OFF the connection between a communication module and a remote device by toggling the output CONTROL_BIT for that connection.
This leaves unchanged the size of the project’s input and output data images.
In the IO Structure Name section:
S1A48993 10/2019
181
Configuring the 140NOC78100 Module
Setting
Input area:
Instance Variable Name
Description
Structure Name
The editable base name for input variables. By default, it is the concatenation of:
the string DEVICE_ the device number the suffix _IN
The read-only name for input structures. By default, it is the concatenation of:
The prefix T_
the string DEVICE_ the device number the suffix _IN
Output area:
Instance Variable Name The editable base name for output variables. By default, it is the concatenation of:
the string DEVICE_ the device number the suffix _OUT
Structure Name The read-only name for input structures. By default, it is the concatenation of:
The prefix T_
the string DEVICE_ the device number the suffix _OUT
Default Name button Restores the default variable and structure names.
In the Items Management section of the page, edit the following:
Import mode
Reimport Items
Automatic: I/O items are taken from the device DTM and updated if the items list in the device DTM changes. Items cannot be edited in the Device Editor.
Manual: I/O items are added when the device DTM is first added to Control
Expert. Thereafter, all I/O item edits are made manually in the Device Editor.
Changes to the device DTM do not impact the I/O items list.
Imports the I/O items list from the device DTM, overwriting any manual I/O item edits. Enabled only when Import mode is set to Manual.
182
S1A48993 10/2019
Configuring the 140NOC78100 Module
Configuring Device IP Address Settings
Overview
Use the pages of the Device Editor to view and edit IP address settings for a remote device.
To display this page, select a remote device name in the Device List node in the left pane of the
Device Editor, then click on the Address Setting tab.
NOTE: Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
Configuring the Address Setting Page
The Address Setting page includes the following settings:
Setting Description
In the Address Settings page, edit the following:
IP Address By default:
the first three octet values equal the first three octet values
of the Ethernet communication module, the fourth octet value equals this device Number setting
DHCP for this Device
Identified by
Enabled activates the DHCP client in this device. The device obtains its IP address from the DHCP service provided by the Ethernet communication module and appears on the auto-generated DHCP client list.
Disabled (the default) de-activates the DHCP client in this device.
If DHCP for this Device is Enabled, this indicates the device identifier type:
MAC Address, or
Name
Identifier
Mask
Gateway
If DHCP for this Device is Enabled, the specific device MAC
Address or Name value.
NOTE: If you use a device name, confirm that you have typed the same device name in the DTM device. Otherwise, the device will not take its IP address.
The device subnet mask. The default = 255.255.255.0.
The gateway address used to reach this device. The default of
0.0.0.0 indicates this device is located on the same subnet as the Ethernet communication module.
S1A48993 10/2019
183
Configuring the 140NOC78100 Module
Configuring Modbus TCP Request Settings
Overview
Use the Request Setting page to configure scanner connection information for a remote Modbus
TCP device.
To display this page, select a remote Modbus TCP device in the Device List node in the left pane of the Device Editor, then click on the Request Settings tab.
NOTE: Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
Configuring the Request Settings Page
The Request Settings page includes the following settings:
Setting
Connection Bit
Unit ID
Health Timeout
Repetitive Rate
RD Address
RD Length
Last Value
Description
The offset for both this connection’s health bit and control bit.
The number of the device, or module, that is the target of the connection. A value of:
255 (the default) used to access the Ethernet communication module
itself
0...254 identifies the device number of the target device, behind a
Modbus TCP to Modbus gateway
NOTE: When accessing data in the Ethernet communication module itself, use 255. When accessing data in the application running in the PLC, use a value from 0 to 254 (a value of 1 is recommended).
The maximum allowed period, in milliseconds, between device responses, from 0 to 120000 ms, in intervals of 5 ms. When this setting is exceeded, the health timeout bit is set to 1.
Default = 1500 ms
The rate at which data will be scanned, from 0 to 60000 ms, in intervals of
5 ms.
Default = 60 ms
Address—from 0 to 65535—in the remote device of the first word from which the communication module reads data.
The number of words in the remote device, from 0 to 125, that the communication module will read.
The behavior of inputs in the application in the event communication is lost:
Hold Value (the default)
Set To Zero
184
S1A48993 10/2019
Configuring the 140NOC78100 Module
Setting
WR Address
WR Length
Description
Address—from 0 to 65535—in the remote device of the first word to which the communication module writes data.
The number of words in the remote device, from 0 to 120, that the communication module will write.
NOTE: For RD Address and WR Address, take into account the remote device address system and check you read or you write the right information, for instance Modicon Quantum addresses start from 1 whereas Modicon Premium addresses start from 0.
S1A48993 10/2019
185
Configuring the 140NOC78100 Module
Configuring Communication Module Connection Settings
Overview
Control Expert automatically creates a connection between the communication module and a remote device when the remote device is added to the Control Expert project. Properties defining each connection must be configured in the DTMs for both the connection module and the remote
see page 195
Use the Connection Settings page to view and edit connection properties from the perspective of the communication module.
To open this page, in the left pane of the Device Editor expand the navigation tree and, under the
Device List node, select <remote device> → <connection>, where:
<remote device> represents the name of the selected remote device appearing in the
Device List, and
<connection> represents the name of the selected connection, which depends upon the types of connections supported by the remote device and the particular connection type selected in the connection configuration settings for the remote device DTM.
NOTE: The name of the connection displayed in the Device List depends upon the types of connections supported by the remote device and the particular connection type selected in the connection configuration settings for the remote device DTM.
Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties
186
S1A48993 10/2019
Configuring the 140NOC78100 Module
Communication Module Connection Properties
The following connection settings for this sample configuration can be viewed or configured in the
DTM for the communication module:
Setting
Connection Bit
Request Packet Interval
(RPI)
Time-out Multiplier
Description
(Read-only) The system generated number, from 0 to 256, for the health bit for this connection.
NOTE: The first numbered Connection Bit is 0, which maps to:
HEALTH_BITS_IN[0].0: the first bit in the first byte of the zero-based
HEALTH_BITS_IN byte array, and
CONTROL_BITS_OUT[0].0: the first bit in the first byte of the zero-based
CONTROL_BITS_OUT byte array,
The refresh period, from 2 to 65535 ms, for this connection.
Default = 12 ms
NOTE: This parameter can be set in the DTM for the communication module, or in the DTM for the remote device.
This setting, multiplied against the RPI, produces a value that triggers an inactivity timeout. Setting selections include: x4, x8, x16, x32, x64, x128, x256 and x512.
Default = x4
NOTE: To view the Time-out Multiplier parameter, Control Expert must be operating in Advanced Mode.
S1A48993 10/2019
187
Configuring the 140NOC78100 Module
EtherNet/IP Connection Information
Overview
Use this read-only page to view connection properties for the remote device. An EtherNet/IP connection provides a communication link between two or more devices. Properties for a single connection are configured in the DTMs for each of the connected devices—typically a communication module and a remote device. The read-only properties viewable in this page can be configured in the General page of the connection node configuration page for the DTM of the remote device
see page 195
.
To open this page, in the left pane of the Device Editor expand the navigation tree and, under the
Device List node, select <remote device> → <connection>, where:
<remote device> represents the name of the selected remote device appearing in the
Device List, and
<connection> represents the name of the selected connection, which depends upon the types of connections supported by the remote device and the particular connection type selected in the connection configuration settings for the remote device DTM.
Remote Device Connection Properties
A connection to a remote Schneider Electric device can present the following properties:
Setting
RPI
Input size
Input mode
Input type
Input priority
Input trigger
Output size
Output mode
Description
The refresh period for this connection, in milliseconds.
The number of bytes reserved for input data, from 0 to 505.
The transmission type:
Multicast
Point to Point
Ethernet packet type—fixed or variable length—to be transmitted.
NOTE: The Ethernet communication module supports only Fixed length packets.
The transmission priority. The value depends upon the device DTM. Values can include:
Low
High
Scheduled
The transmission trigger. Values can include:
Cyclic
Change of state or application
The number of bytes reserved for output data, from 0 to 509.
The transmission type:
Multicast
Point to Point
188
S1A48993 10/2019
Configuring the 140NOC78100 Module
Setting
Output type
Output priority
Description
Ethernet packet type—fixed or variable length—to be transmitted.
NOTE: The Ethernet communication module supports only Fixed length packets.
The transmission priority. The value depends upon the device DTM. Values can include:
Low
High
Scheduled
S1A48993 10/2019
189
Configuring the 140NOC78100 Module
190
S1A48993 10/2019
Quantum EIO
Configuring Remote Devices
S1A48993 10/2019
Configuring Remote Devices Chapter 5
Configuring Remote Devices
Overview
This chapter describes how to use the Control Expert Device Editor to configure remote device properties, including properties that define:
the connection between the remote device and the communication module the degree to which the actual remote device must match the remote device described in the
Control Expert project configuration other settings required by the remote device manufacturer that are unique to the remote device
NOTE:
Before connecting with remote devices, check whether the module’s FTP/TFTP services are
enabled, and if they are not, enable them (
see page 162
Before you can configure settings for a device, the device DTM must be disconnected from the remote device itself. If necessary, you can disconnect a DTM by selecting its node in the
DTM Browser then selecting Edit → Disconnect.
The DTM for a device determines its configuration template. The topics presented in this chapter described configuration settings that apply to devices manufactured by Schneider
Electric and to non-manufacturer-specific generic devices.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Displaying Remote Device and DTM Properties
Adding and Removing Connections
Configuring EtherNet/IP Connections
Checking Remote Device Identity
Configuration Settings
Configuring Modular Devices
Page
S1A48993 10/2019
191
Configuring Remote Devices
Displaying Remote Device and DTM Properties
Introduction
Use this page to view properties that describe:
the remote device, and
its DTM
To display this page, select a remote device in the DTM Browser to open its DTM. Then, in the left pane of the Device Editor, select the node that displays the assigned device name.
NOTE: When this page is displayed, if this device is capable of supporting an additional
connection, you can use the Add Connection command to create a new connection for this device
see page 193
Properties
The properties displayed in this page are read-only and are determined by the manufacturer of the remote device. The source of the displayed property values is the device DTM. The following list presents an example of the self-explanatory properties you may see displayed for a Schneider
Electric device:
File Name
File:
Description
File Creation Date
File Creation Time
Last Modification Date
Last Modification Time
EDS Revision
Device:
Vendor Name
Device Type
Major Revision
Minor Revision
Product Name
Catalog Number
192
S1A48993 10/2019
Configuring Remote Devices
Adding and Removing Connections
Introduction
Connections are created and configured in the DTM for a remote device.
Use the Device Editor to access the DTM for a remote device, where you can add and remove connections between the remote device and the Ethernet communication module.
Adding a Connection
To add a connection between a remote device and the communication module:
Step
1
2
3
4
5
6
7
Action
In the DTM Browser, double-click a remote device. Its DTM opens in the
Device Editor.
In the left pane of the Device Editor, select the node displaying the name of the remote device.
NOTE:
If the device is capable of supporting additional connections, the
Add Connection button becomes enabled.
If the Add Connection button remains disabled, the device is presently supporting its maximum number of connections. In this case, a new connection can be added only after an existing connection is removed.
Click the Add Connection button. The Select the connection to add dialog opens.
In the Connection to add lit, select a connection type.
NOTE: The types of connections available in the list depends upon the connection types supported by the specific remote device.
Click OK to close the dialog. The new connection appears in the tree control in the left pane.
Click on the following tabbed pages, and configure the properties in each page
(as necessary):
Identity Check
Configuration Settings
Do one of the following:
click Apply to save your edits and leave the window open, or
click OK to save your edits and close the window
S1A48993 10/2019
193
Configuring Remote Devices
Removing a Connection
To remove a connection between a remote device and the communication module:
Step
1
2
3
4
Action
In the DTM Browser, double-click a remote device. Its DTM opens in the
Device Editor.
In the left pane of the Device Editor, beneath the remote device name, select the connection node you wish to remove.
Click the Remove Connection button. The dialog opens. The connection disappears from the tree control.
Do one of the following:
click Apply to save your edits and leave the window open, or
click OK to save your edits and close the window
194
S1A48993 10/2019
Configuring Remote Devices
Configuring EtherNet/IP Connections
Overview
Use this page to configure connection properties that are required by the remote device DTM. An
EtherNet/IP connection provides a communication link between two or more devices. Properties for a single connection must be configured in the DTMs for each of the connected devices (typically a communication module and a remote device).
Open this page:
Step
1
2
3
4
Action
Double-click on the remote device in the DTM Browser to open its DTM in the
Device Editor.
In the navigation tree in the left pane of the Device Editor, select the connection node you want to configure.
In the right pane of the Device Editor, click the General tab.
Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
NOTE: When this page is open, you can use the Remove Connection command to delete the selected connection.
Remote Device Connection Properties
A connection to a remote Schneider Electric device can present these properties:
Property
RPI
Input size
Input mode
Input type
(read only)
Input priority
Input trigger
Description
RPI indicates the refresh period for this connection in milliseconds. (This parameter can also be set in the DTM for the communication module device.)
This is the number of bytes (0 ... 505) that are reserved for input data.
This mode is the input transmission type:
Multicast
Point to Point
This is the Ethernet packet type (fixed or variable length) for transmission.
NOTE: The Ethernet communication module supports only Fixed length packets.
This transmission priority value depends upon the device DTM. These are the available values:
Low
High
Scheduled
These are the available values for the transmission trigger:
Cyclic
Change of state or application
S1A48993 10/2019
195
Configuring Remote Devices
Property
Output size
Output mode
Description
This is the number of bytes (0 ... 509) that are reserved for output data.
This mode is the output transmission type:
Multicast
Point to Point
Output type
(read only)
This is the Ethernet packet type (fixed or variable length) for transmission.
NOTE: The Ethernet communication module supports only Fixed length packets.
Output priority This transmission priority value depends upon the device DTM. These are the available values:
Low
High
Scheduled
196
S1A48993 10/2019
Configuring Remote Devices
Checking Remote Device Identity
Overview
Use this page to specify the degree to which a remote device (detected on the network) conforms to the configuration settings for the same remote device in the Control Expert application project.
Control Expert does not maintain connections to a remote device that does not pass this identity check.
Open this page:
3
4
Step
1
2
Action
Double-click on the remote device in the DTM Browser to open its DTM in the Device Editor.
In the navigation tree in the left pane of the Device Editor select the connection node you want to configure.
In the right pane of the Device Editor, click the Identity Check tab.
Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
NOTE: When this page is open, you can use the Remove Connection command to delete the selected connection.
S1A48993 10/2019
197
Configuring Remote Devices
Remote Device Identity Properties
A connection to a remote Schneider Electric device can present these properties:
Property
Check Identity
Description
This property defines the rule that Control Expert uses to compare the configured versus the actual remote device. These are the available settings:
Must match exactly: The DTM or EDS file exactly matches the remote device.
Disable: The checking function does not run. The identity portion of the connection is
filled with zero values (the default setting).
Must be compatible: When the remote device is not the same as defined by the
DTM/EDS, it emulates the DTM/EDS definitions.
None—no checking occurs; the identity portion of the connection is omitted
Custom: Enable the following parameter settings individually.
When Check identity is set to Custom, complete these fields:
Compatibility
Mode
Minor Version
Major Version
Product Code
Product Type
Product Vendor
True: For each of the following selected tests, the DTM/EDS and remote device are compatible.
False: For each of the following selected tests, the DTM/EDS and remote device match exactly.
For each of these, select a setting:
Compatible: Include the parameter in the test.
Not checked: Do not include the parameter in the test.
198
S1A48993 10/2019
Configuring Remote Devices
Configuration Settings
Introduction
Use the Configuration Settings page to complete the configuration of the connection to this remote device. The information added in this page extends the address path to the remote device.
To open this page:
Step
1
2
3
4
Action
Double-click on the remote device in the DTM Browser to open its DTM in the
Device Editor.
In the navigation tree in the left pane of the Device Editor select the connection node you want to configure.
In the right pane of the Device Editor, click the Configuration Settings tab.
Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
NOTE: When this page is open, you can use the Remove Connection command to delete the selected connection.
Configuration Settings
The content of this page can vary, depending upon the DTM—selected in the Add dialog—that defines this device. Examples of DTM properties that may be configured in this page include:
This DTM type...
Generic Device
Can require this content...
Property
Configuration 1 :
Description
A hexidecimal extension to the addressing path.
Advanced Generic Device Input Instance 1
Output Instance
:
1 :
Configuration Instance 1 :
The device specific assembly number associated with input (T -> O) transmissions.
The device specific assembly number associated with output (O -> T) transmissions.
The device specific assembly number associated with device configuration settings.
A hexidecimal extension to the addressing path.
Configuration 1 :
Device with EDS (The list of properties is defined by, and varies with, each specific DTM.)
1. The value, or range of values, that can be used to configure this property must be obtained from the manufacturer of the specific device and device DTM.
S1A48993 10/2019
199
Configuring Remote Devices
Configuring Modular Devices
Introduction
The Chassis/Modules page applies only to modular devices—i.e., remote devices that combine a network interface module, chassis, and input/output modules. Use the chassis page to configure the chassis by:
selecting a chassis type, and specifying the number of chassis slots inserting one or more modules into the chassis removing a module from the chassis moving a module to a different position in the chassis
You can add any chassis—and any module suitable for a selected chassis—that appears in the
Device Library.
To open this page:
2
3
Step
1
Action
Double-click on the remote device in the DTM Browser to open its DTM in the Device Editor.
In the navigation tree in the left pane of the Device Editor select the Chassis/Modules node.
Refer to the topic Configuring Properties in the Device Editor for instructions on how to edit properties.
Configuring the Chassis
To configure the chassis for a modular device:
Step
1
5
6
2
3
4
Action
Select a chassis type in the Chassis Type Available in the Device Library list.
The selected number of slots appear in the Configured Modules list beneath the selected remote adapter.
Select a module in the Available Modules for the Chassis list.
Click the button to insert the selected module into the first available (i.e., lowest numbered) open slot.
Use the following buttons to move a module within the chassis:
moves the selected module up to the next available slot
moves the selected module down to the next available slot
deletes the selected module from the chassis
Repeat steps 2 through 4 for all modules you want to add to the chassis.
Do one of the following:
Click Apply to save your edits and leave the page open
Click Save to save your edits and close the page
200
S1A48993 10/2019
Quantum EIO
Online Action
S1A48993 10/2019
Online Action Chapter 6
Online Action
Overview
This chapter describes online actions you can undertake in Control Expert. Depending on the type and protocol of the selected communication module or remote device, you can perform these tasks:
Display CIP objects.
View and edit port configuration parameters.
Ping a module or device to confirm that it is active on the Ethernet network.
Connect to a remote device and ...
View device default parameter settings.
View the current parameter settings for the device.
Edit the parameter settings for the device.
NOTE: Before you can perform online actions for a communication module or remote device, connect its DTM to the physical module or device. (That is, select the module or device node in the
DTM Browser and select Edit → Connect.)
What Is in This Chapter?
This chapter contains the following topics:
Topic
Online Action - EtherNet/IP Object
Online Action - Port Configuration
Online Action - Ping
Viewing and Editing Online Settings for a Remote Device
Get and Set Rack Size
Page
S1A48993 10/2019
201
Online Action
Online Action - EtherNet/IP Object
Overview
Use the EtherNet/IP Object page of the Online Action window to perform these tasks:
Retrieve and display the data that describes the current state of CIP objects for the selected
communication module or remote device.
Reset the selected communication module or remote device.
NOTE: Before you can perform online actions for a communication module or remote device, connect its DTM to the physical module or device. (That is, select the module or device node in the
DTM Browser and select Edit → Connect.)
Choose an operating mode in Control Expert to select the CIP object information that this page displays:
Mode
Standard mode
Advanced mode
CIP Objects
Identity object
Identity object
Connection Manager object
TCP/IP Interface object
Ethernet Link object
QoS object
Retrieve and Display EtherNet/IP Object Data
Display CIP object data for a communications module or remote device:
Step
1
2
3
4
5
6
Action
Select a communication module in the DTM Browser.
Open the Online Action window. (Right-click the pop-up menu and scroll to Device menu →
Online Action.)
Select a communication module or device in the left pane of the Online Action window.
In the right pane, click the EtherNet/IP Object tab to open that page.
Observe these requirements for the selected operating mode in Control Expert.
Advanced Mode: Select a CIP object:
Identity
Connection Manager
TCP/IP
Ethernet Link
QoS
Standard Mode: Control Expert displays data only for the CIP Identity object.
Click the Refresh button.
202
S1A48993 10/2019
Online Action
Reset a Communication Module or Remote Device
Reset a communications module or remote device:
Step
1
2
3
4
5
Action
Select a communication module in the DTM Browser.
Open the Online Action window. (Right-click the pop-up menu and scroll to Device menu →
Online Action.)
In the left pane of the Online Action window, select a communications module or device.
In the right pane, click on the EtherNet/IP Object tab to open that page.
Click the Reset Device button.
S1A48993 10/2019
203
Online Action
Online Action - Port Configuration
Overview
Use the Port Configuration page of the Online Action window to view and edit communications port properties for a remote device. Specifically, you can use this page to perform these tasks:
Get port configuration settings from a remote EtherNet/IP device.
Use a Set command to write edited values to the same remote EtherNet/IP device.
Configuration edits transmitted from this page are sent as EtherNet/IP explicit messages and employ the Address and Messaging settings configured in the EtherNet/IP Explicit Messaging window.
NOTE: Before you can perform online actions for a remote device, connect its DTM to the physical device. (That is, select the device node in the DTM Browser and select Edit → Connect.)
Get Port Configuration Settings
To get settings from a remote EtherNet/IP device on the network:
Step
1
2
3
4
5
6
7
8
9
Action
In the DTM Browser, select the communication module upstream of the remote EtherNet/IP device.
Click the right mouse button, and in the pop-up menu select Device menu → EtherNet/IP
Explicit Message. The EtherNet/IP Explicit Message window opens.
In the EtherNet/IP Explicit Messaging page, complete the Address section.
Note: Port configuration explicit messages are sent as unconnected messages.
Return to the DTM Browser and again select the communication module upstream of the remote
EtherNet/IP device.
Click the right mouse button, and in the pop-up menu select Device menu → Online Action. The
Online Action window opens.
In the left pane of the Online Action window, select a remote EtherNet/IP device.
In the right pane, click on the Port Configuration tab to open that page.
If the remote device consists of more than one port, select the port number in the Physical
Interface Instance list.
In the Port Configuration page, click the Get Values from Device button.
The table displays the returned values of the communication properties for the selected remote device and port.
204
S1A48993 10/2019
Online Action
Edit and Set Port Configuration Settings
To edit and set port configuration settings that were retrieved using the above-described Get Port
Configuration Settings process:
Step
1
2
3
4
Action
Double-click the left mouse button in the Value cell for the parameter you want to edit. The cell becomes editable.
Note: The page also displays a Description of the selected parameter.
Type in, or select, the new value.
Repeat the above steps for each parameter you want to edit.
Perform one of these tasks:
Click the Set All Values to Device to write all values to the remote device.
If you edited parameters for only one part or group of the collection of remote device values, perform these steps:
1 In the Set Part of Values area, select one property group.
2 Click the Set Values to Device button.
Control Expert sends the property value edits to the remote device via an EtherNet/IP explicit message, and displays the results in the Description area.
S1A48993 10/2019
205
Online Action
Online Action - Ping
Overview
Use the EtherNet/IP Object page of the Online Action window to send an ICMP echo request to a target communication module or remote device to determine:
if the target device is present, and if so the elapsed time to receive an echo response from the target device
The target device is identified by its IP address setting.
NOTE: Before you can perform online actions, connect the DTM for the communication module or remote device to the module or device itself. To do this, select the module or device node in the
DTM Browser, then select Edit → Connect.
Pinging a Network Device
To ping a network device:
Step
1
2
3
4
5
6
7
8
Action
In the DTM Browser, select a communication module.
Right-click the pop-up menu and select Device menu → Online Action.
Result: The Online Action window opens.
In the left pane of the Online Action window, select a communication module or device.
In the right pane, click the Ping tab to open that page.
NOTE: The read-only IP Address of the selected module or device is preselected.
To send...
a single ping, de-select Repeat.
a series of pings (1 every 100 ms), select Repeat.
(Optional)
Select Stop on Error to stop pinging if an error is detected.
Click Ping once to begin pinging.
The result of the ping is displayed in the Ping Result area. Click Clear to empty the Ping Result contents
Click Ping a second time to stop looped pinging, where no error has been detected.
206
S1A48993 10/2019
Online Action
Viewing and Editing Online Settings for a Remote Device
About Online Parameters
Use the Online Parameters window to perform these tasks:
View the remote device’s default parameter settings.
View the remote device’s current parameter settings.
Edit and download to the remote device its editable parameter settings.
Parameter setting edits that are transmitted from this page are sent as EtherNet/IP explicit messages. These edits employ the Address and Messaging settings configured in the EtherNet/IP
Explicit Messaging window.
NOTE: Before you can view and edit online settings for a remote device, connect its DTM to the physical device. (That is, select the device node in the DTM Browser and select Edit → Connect.)
Online Parameters Window
Open the Online Parameters window:
Step
1
2
3
Action
Select the node for a remote device in the DTM Browser.
Right-click in the pop-up menu and scroll to Device menu → Online Parameters. The
Online Parameters window opens for the selected remote device.
In the left pane of the Online Parameters window, select a connection node. Control Expert displays the parameters relating to the selected connection in the right pane.
NOTE: The list of parameters displayed in the Online Parameters window depends upon the the device that is selected in the DTM Browser and the connection that is selected in the left pane of the Online Parameters window.
Read-only parameters are identified by a locked icon .
Editable parameters are identified by a blue arrowhead .
Displaying Default Parameter Settings
Click the Get Values from EDS button to view the default parameter settings for the remote device.
Control Expert reads the default device values from its EDS file and displays them on-screen.
S1A48993 10/2019
207
Online Action
Displaying Online Parameter Settings
View the current parameter settings for the remote device:
Step
1
2
3
Action
Open the Synchronize Action dialog box. (Click the Synchronize button while a connection is selected in the left pane.)
In the message box, select Read values from the device.
Click OK.
The message box closes. Look at the Online Parameters window:
The Status field displays the results of the read transaction.
The parameter list displays the current values.
Editing Online Parameter Settings
Edit parameter settings for the remote device:
Step
1
2
3
4
5
Action
With a connection selected in the left pane, display one of these settings:
default device settings
current device settings
In the Value column, type in or select a new value for each setting that you want to edit.
NOTE: When you select a parameter, the Description area displays an explanation of the parameter and its available settings.
Open the Synchronize Action dialog box. (Click the Synchronize button.)
In the message box, select Write data to the device.
Click OK.
The message box closes. In the Online Parameters window, the Status field displays the results of the write transaction.
208
S1A48993 10/2019
Online Action
Get and Set Rack Size
Introduction
Use the rack size page to set the chassis (rack) size through a direct online communication from the Control Expert Ethernet Configuration Tool software to the remote device.
NOTE: For some modular remote devices, it is possible for the actual rack size to differ from the configured rack size. In this case, use the controls in this page to synchronize your application program with the device configuration.
Transmissions made in this page are sent as EtherNet/IP explicit messages and employ the
Address and Messaging settings configured in the EtherNet/IP Explicit Messaging window.
NOTE: Before you can get or set rack size data in this page, connect the device DTM to the physical device. (That is, select the device node in the DTM Browser and select Edit → Connect.)
Rack Size Page
Open the Get/Set Rack Size page:
Step
1
2
Action
Select the remote device node in the DTM Browser.
Click the right mouse button, then in the pop-up menu select Device menu → Get/Set Rack Size.
The Get/Set Rack Size window opens.
Get Rack Size
Click the Get Rack Size button to obtain the actual configured rack size from the remote modular device.
The actual rack size is displayed as a read-only value in the text box to the left of the Get/Rack
Size button. The Status field displays the result of the explicit messaging transaction.
Set Rack Size
Write a new rack size setting to the remote modular device:
Step
1
2
Action
In the editable text box to the left of the Set Rack Size button, type in the desired rack size.
Click the Set Rack Size button. The remote modular device is re-configured with the new rack size.
NOTE: The Status field displays the result of the explicit messaging transaction.
S1A48993 10/2019
209
Online Action
210
S1A48993 10/2019
Quantum EIO
Working With Derived Data Types
S1A48993 10/2019
Working With Derived Data Types Chapter 7
Working With Derived Data Types
Overview
This chapter describes how to complete your project by creating, updating, and viewing derived data type (DDT) variables in Control Expert.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Creating and Updating Derived Data Types
Working with Derived Data Type Variables
Effect of Activating and De-activating Devices on I/O %MW Memory Addresses
Page
S1A48993 10/2019
211
Working With Derived Data Types
Creating and Updating Derived Data Types
Creating or Updating Derived Data Types
After you have completed your edits in the Device Editor, the next step is to let Control Expert create the necessary program objects — in the form of derived data types (DDTs) and variables — that will support your network design. To do this, follow these steps:
Step Action
1 In the Project Browser, navigate to and select the communication module.
2 Do one of the following:
Click the right mouse button, and select Open in the pop-up menu
— or —
In the Edit menu, select Open.
Result: The Configuration page of the Ethernet communication module opens:
212
3 Click the Update application button.
NOTE:
Every time you use the Device Editor to make changes to your Control Expert project, return to this screen and click the Update application button to save your edits.
Control Expert refreshes the collection of DDTs and variables — by adding, editing, or deleting previously generated DDTs and variables — each subsequent time you click the Update application button.
S1A48993 10/2019
Working With Derived Data Types
Step Action
4 Click OK.
Result: The Project Browser displays the new or edited derived data types:
S1A48993 10/2019
213
Working With Derived Data Types
Working with Derived Data Type Variables
Derived Data Type Variables
When you click the Update application button, Control Expert creates a collection of derived data types and variables. These are used by Control Expert to support communication and data transfer between the PLC and the various local slaves, remote devices, and their I/O items. You can access these derived data types and variables in the Control Expert Data Editor and add them to a userdefined Animation Table, where you can monitor read-only variables and edit read-write variables.
Use these data types and variables to:
view the status of all connections from the communication module to remote EtherNet/IP and
Modbus TCP devices, where:
the status of all connections is displayed in the form of a HEALTH_BITS array consisting of
32 bytes
each connection is represented by a single bit in the array a bit value of 1 indicates the connection is healthy a bit value of 0 indicates the connection is lost, or the communication module can no longer communicate with the remote device toggle a connection ON (0) or OFF (1) by writing to a selected bit in a 32 byte CONTROL_BITS array
NOTE: Be alert to the distinction between toggling a bit in the CONTROL_BITS array on or off versus enabling or disabling a remote device.
monitor the value of local slave and remote device input and output items you created in the
Control Expert Device Editor
214
S1A48993 10/2019
Working With Derived Data Types
Identifying Derived Variables in the Data Editor
To view your Control Expert application’s derived data type variables:
Step
1
Description
In the Project Browser, navigate to and double-click the left mouse button on
Variables & FB instances → Derived Variables:
S1A48993 10/2019
215
Working With Derived Data Types
Step
2
Description
The Data Editor opens, displaying the Variables page:
NOTE:
A check mark appears in the DDT check box. (If not, select the DDT check boxes to display these
variables.)
The red arrow and lock icons indicate the variable name was auto-generated by Control Expert based on the configuration of the local slave or remote device and cannot be edited.
Displaying the Order of Input and Output Items in PLC Memory
The Data Editor displays the address of each input and output variable. Click the Address column header to sort input and output addresses in ascending order. When you open the first input and output variables, you can see both the connection health bits and the connection control bits:
216
S1A48993 10/2019
Working With Derived Data Types
Notice the order of inputs and outputs in the above example. Recall that the user defines the size and location of inputs and outputs. However, within the reserved area for both inputs and outputs,
Control Expert assigns addresses to variables in the following order:
Inputs
Health bits 1
Order Outputs
1 Control bits 1
Modbus TCP input variables
Local Slave input variables
3
2 2
3
Modbus TCP output variables 2
Local Slave output variables
3
EtherNet/IP output variables
2
EtherNet/IP input variables
2 4
1. Health and control bits are sub-ordered as follows: i. by device type: a. Modbus TCP; b. local slave; c. EtherNet/IP ii. within each device type: a. by device or local slave number b. within a device: by connection number
2. Device variables are sub-ordered as follows: i. by device number ii. within a device: by connection number iii. within a connection: by item offset
3. Local slave variables are sub-ordered as follows: i. by local slave number ii. within each local slave: by item offset
NOTE: When a device is added to or removed from the project, or when the active status of an existing device or a local slave changes, the specific location of inputs and outputs in PLC memory also changes.
S1A48993 10/2019
217
Working With Derived Data Types
Identifying the Connection Health Bits
The Ethernet communication module can support up to 128 connections to remote devices. The health of each connection is represented in a single bit value. A health bit value of:
1 indicates the connection is active
0 indicates the connection is inactive
The health bits are contained in a 32-byte array in the Variables page of the Data Editor. To display offline this byte array, first sort the variables in ascending order of address, then open the first input variable as shown below:
218
S1A48993 10/2019
Working With Derived Data Types
To determine which health bit is mapped to a specific remote device connection, in the
Device Editor for the Ethernet communications
Step Action
1 In the Device Editor for the Ethernet communication module, under the Device List node, navigate to and select:
for Modbus TCP devices: the main device node for EtherNet/IP devices: a connection node
2 For a Modbus TCP device, open the Request Setting page and look for the Connection Bit number:
3
In the above example (which displays the left portion of a truncated Request Setting page), the
Connection Bit value of 0 maps to the first bit in the first byte of the HEALTH_BITS_IN array, which can be represented as HEALTH_BITS_IN[0].0
.
For an EtherNet/IP device, open the Connection Settings page and look for the Connection Bit number:
4
In the above example, the Connection Bit value of 2 maps to the third bit in the first byte of the
HEALTH_BITS_IN array, which can be represented as HEALTH_BITS_IN[0].2
.
For a local slave, open the local slave configuration page and look for the Connection Bit number:
S1A48993 10/2019
219
Working With Derived Data Types
Monitoring Connection Health Bits in an Animation Table
Use an animation table to monitor the status of connection health bits and other variables. To add health bits to an animation table, follow these steps:
2
3
Step
1
Action
In the Project Browser, select the Animation Tables node and click the right mouse button.
Result: A pop-up menu opens.
Select New Animation Table.
In the New Animation Table dialog, type in values for the following fields:
Name Type in a name for the new animation table. In this example, type in
Connection_Health_Bits.
Number of animated characters
Accept the default value of 100.
The completed dialog looks like this:
220
4
5
Click OK.
Result: The dialog closes, and the new Connection_Health_Bits animation table opens.
Double-click the first empty row in the Name column, then click the ellipsis button
Result: The Instance Selection dialog opens.
.
S1A48993 10/2019
Working With Derived Data Types
Step
6
Action
In the Instance Selection dialog, navigate to and select the entire HEALTH_BITS_IN array:
7 Click OK to add the array to the Connection_Health_Bits animation table:
Keep in mind that each row represents a byte, which contains 8 individual connection health bits.
When the DTM for the Ethernet communication module is connected to the physical module, the
Value field displays a value for the entire byte.
S1A48993 10/2019
221
Working With Derived Data Types
Modifying Connection Control Bits in an Animation Table
You can also use an animation table to modify the value of a control bit, toggling it on or off.
NOTE: Using control bits to a connection on or off (as described below) is the preferred way of regulating communication with a remote device. Toggling a connection control bit on and off does not affect the address location of I/O items. In either case — on or off — the I/O items remain a part of the configuration at the same address locations.
By contrast, enabling and disabling the Active Configuration property for a device or local slave either adds I/O items to, or removes I/O items from, the application. This has the rippling effect of changing the addresses not only for the items of the enabled/disabled device, but also for I/O items relating to other devices in the configuration.
The following example shows you how to add connection control bits to the
Connection_Health_Bits animation table that you created, above, and use the animation table’s
Modification function to toggle control bits on or off:
Step
1
2
Action
With the Connection_Health_Bits animation table open, double-click the next empty row in the
Name column, then click the ellipsis button
Result: The Instance Selection dialog opens.
.
In the Instance Selection dialog, navigate to and select the entire CONTROL_BITS_OUT array:
222
S1A48993 10/2019
Working With Derived Data Types
Step
3
Action
Click OK to add the control bit array to the Connection_Health_Bits animation table:
4
5
6
Keep in mind that each row represents a byte, which contains 8 individual connection control bits.
When the DTM for the Ethernet communication module is connected to the physical module, the
Value field displays a value for the entire byte.
With the DTM for the Ethernet communication module connected to the physical module, double click in the Value column for the row (byte) that contains the control bit you want to toggle.
Type a value that toggles the bit (or bits) in the byte you want to change to on or off. For example, suppose the Value field of the control bit displays an initial value of 7. This indicates that the first three (0, 1, and 2) are not established. If you intend to establish the third connection (i.e. connection number 2), modify the corresponding bit to 0 (type a value of 3).
NOTE: When the control bit is 0, the connection is established. When the control bit is 1, the connection is closed.
On your keyboard, press Enter.
Result: The control bit for the third connection (i.e., connection number 2) is toggled off.
S1A48993 10/2019
223
Working With Derived Data Types
Effect of Activating and De-activating Devices on I/O %MW Memory Addresses
Introduction
Control Expert assigns a located address in %MW memory to each input and output variable for a remote device and local slave, when that device or slave is activated.
In addition, Control Expert removes from %MW memory each located variable address whenever the related device or slave is de-activated.
In each case, because of the ordered structure of I/O items in PLC memory, the activation and deactivation of a single device causes a rippling effect on the address locations of other I/O variables throughout the application.
Because activating and de-activating devices can cause substantial changes to located variable addresses, Schneider Electric recommends the following practices:
Activate all the devices and local slaves your application is likely to use, and allow these devices to remain activated.
If it subsequently becomes necessary to disable communications to a device or slave, instead of de-activating it, use the appropriate control bits to toggle off all connections to that slave or device.
When configuring function blocks in Control Expert, instead of directly assigning input and output pins to a specific %MW address, assign specific input and output pins only to the derived data types and variables automatically created by Control Expert.
The Sample Network
The sample network is a part of the same physical network that has been the subject of our continuing configuration example, and includes:
the Ethernet communication module, named Q_NOC78100 an STB NIC 2212 EtherNet/IP network interface module with I/O modules, named NIC2212_01
Note that, when a new network is created, Control Expert presents 3 local slave nodes that can be activated and pre-assigns them device numbers 000, 001, and 002. By default, each local slave is not activated. Therefore, each local slave’s inputs and outputs are not initially assigned a %MW memory address.
The following example describes the effect of activating a local slave function after another remote device has already been configured and added to the network. In this case:
The sample Ethernet network has been configured as follows:
Total network inputs and outputs are set in the Configuration page of the Ethernet communication module in Control Expert:
100 input words are reserved, beginning at %MW01
100 output words are reserved, beginning at %MW101
Connection bits for the project include:
32 input bytes (16 words) for health bits with an instance name of Q_NOC78100_IN
32 output bytes (16 words) for control bits with an instance name of Q_NOC78100_OUT
224
S1A48993 10/2019
Working With Derived Data Types
Local slave inputs and outputs include:
8 input bytes (4 words) are reserved with an instance name of Q_NOC78100_LS1_IN
2 output bytes (1 word) is reserved with an instance name of Q_NOC78100_LS1_OUT
Remote EtherNet/IP device inputs and outputs include:
19 input bytes (10 words) are reserved with an instance name of NIC2212_01_IN
6 output bytes (3 words) are reserved with an instance name of NIC2212_01_OUT
I/O Assignment Without an Activated Local Slave
When you click the Update application button in the Ethernet communication module Configuration page, with the local slave de-activated, Control Expert auto-generates a collection of variables in support of the application’s I/O items at the following instance locations:
Notice the address locations of the remote EtherNet/IP device’s inputs (%MW17) and outputs
(%MW117). As you will see, below, when the local slave is activated, these address locations will change.
S1A48993 10/2019
225
Working With Derived Data Types
I/O Assignment With an Activated Local Slave
The following example displays input and output variables for the same project. However, in this example the Active Configuration setting for the first local slave was set to Enabled in the local slave configuration page, before the input and output variables were created. As a result clicking the Update application button in the Ethernet communication module Configuration page generated the following collection of variables:
Notice how the address locations for the remote EtherNet/IP device have shifted:
inputs (NIC2212_01_IN) have shifted from %MW17 to %MW21
outputs (NIC2212_01_OUT) have shifted from %MW117 to %MW118
This shift of %MW input and output memory address assignments occurs because the local slave was activated, and local slave I/O variables are placed in a located memory address position ahead of remote EtherNet/IP device I/O variables.
A similar shift of addresses would occur — with respect to both local slave and EtherNet/IP device
I/O variable addresses — if a Modbus TCP remote device is activated. This is because Modbus
TCP device I/O variables are places in a located memory address position ahead of both local slave and EtherNet/IP I/O variables.
As stated above, to help prevent this shift of I/O memory addresses, activate all local slaves and remote devices that your project may require, and then allow them to remain active. If you later disable a device, use the appropriate control bits to toggle off all connections to that device.
226
S1A48993 10/2019
Quantum EIO
Explicit Messaging
S1A48993 10/2019
Explicit Messaging Chapter 8
Explicit Messaging
Overview
EtherNet/IP uses the TCP/IP and UDP/IP protocols to implement both explicit and implicit messaging.
This chapter explains the 140 NOC 78• 00 head module and its use of explicit messaging for request-and-reply communications for non-real-time information (like configuration and diagnostic data). A network node that receives a TCP/IP-encapsulated explicit message processes the message and generates a response.
NOTE:
The 140 NOC 78• 00 head module can process 16 MBP_MSTR blocks per MAST cycle.
The 140 NOC 78• 00 head module processes MBP_MSTR blocks to reach data on the control network only.
NOTE: If you receive a detected error message — stating that the 140CRP31200 module does not have a link (has no cable), MSTR functionality may not be available. If this happens, check that your cables are connected properly.
This chapter describes how to use both Control Expert function block logic and the Control Expert interface to send explicit messages.
What Is in This Chapter?
This chapter contains the following sections:
Section
8.1
8.2
8.3
8.4
Topic
Explicit Messaging Using the MBP_MSTR Block
EtherNet/IP Explicit Messaging Using MBP_MSTR
Modbus TCP Explicit Messaging Using MBP_MSTR
Explicit Messaging via the Control Expert GUI
Page
S1A48993 10/2019
227
Explicit Messaging
Explicit Messaging Using the MBP_MSTR Block Section 8.1
Explicit Messaging Using the MBP_MSTR Block
Configuring Explicit Messaging Using MBP_MSTR
Overview
You can use the MBP_MSTR function block to configure both Modbus TCP and EtherNet/IP connected and unconnected explicit messages.
The operation begins when the input to the EN pin is turned ON. The operation ends if the ABORT pin is turned ON, or if the EN pin is turned OFF.
The CONTROL and DATABUF output parameters define the operation.
NOTE: The structure and content of the CONTROL and DATABUF output parameters differ for explicit messages configured using the EtherNet/IP and Modbus TCP protocols. Refer to the topics
Configuring the Control Parameter for EtherNet/IP and Configuring the Control Parameter for
Modbus TCP for instructions on how to configure these parameters for each protocol.
The ACTIVE output turns ON during operation; the ERROR output turns ON if the operation aborts without success; the SUCCESS output turns ON at the successful completion of the operation.
EN and ENO can be configured as additional parameters.
Representation in FBD
228
S1A48993 10/2019
Explicit Messaging
Input Parameters
Parameter
ENABLE
ABORT
Data type
BOOL
BOOL
Description
When ON, the explicit message operation (specified in the first element of the CONTROL pin) is executing.
When ON, the operation is aborted.
Output Parameters
Parameter
ACTIVE
ERROR
SUCCESS
Data type
BOOL
BOOL
BOOL
Description
ON when the operation is active.
OFF at all other times.
ON when the operation is aborted without success.
OFF before operation, during operation, and if operation succeeds.
ON when the operation concludes successfully.
OFF before operation, during operation, and if operation does not conclude successfully.
CONTROL
DATABUF
1
1
WORD
WORD
This parameter contains the control block. The first element contains a code describing the operation to be performed. The content of the control block depends on the operation. The structure of the control block depends on the protocol (EtherNet/IP or Modbus TCP).
Note: Assign this parameter to a located variable.
This parameter contains the data buffer. For operations that:
provide data — e.g., a write operation — this parameter is the data source
receive data — e.g., a read operation — this parameter is the data destination
Note: Assign this parameter to a located variable.
1. Refer to the topics Configuring the Control Block for EtherNet/IP and Configuring the
Control Block for Modbus TCP for instructions on how to configure these parameters for the
EtherNet/IP and Modbus TCP communication protocols.
S1A48993 10/2019
229
Explicit Messaging
EtherNet/IP Explicit Messaging Using MBP_MSTR Section 8.2
EtherNet/IP Explicit Messaging Using MBP_MSTR
Overview
This section shows you how to configure the MBP_MSTR function block for EtherNet/IP explicit messages.
What Is in This Section?
This section contains the following topics:
Topic
EtherNet/IP Explicit Messaging Services
Configuring the CONTROL and DATABUF Parameters
MBP_MSTR Example: Get_Attributes_Single
Page
230
S1A48993 10/2019
Explicit Messaging
EtherNet/IP Explicit Messaging Services
Overview
Every EtherNet/IP explicit message performs a service. Each service is associated with a service code (or number). You will need to identify the explicit messaging service by its name, decimal number, or hexadecimal number.
You can execute EtherNet/IP explicit messages using either a Control Expert MBP_MSTR function block or the Control Expert Ethernet Configuration Tool’s EtherNet/IP Explicit Message Window.
NOTE: Configuration edits made to an Ethernet communication module from the Control Expert
Ethernet Configuration Tool’s EtherNet/IP Explicit Message Window are not saved to the operating parameters stored in the CPU and, therefore, are not sent by the CPU to the module on startup.
You can use Control Expert to construct a request that executes any service supported by the target device that is compliant with the EtherNet/IP protocol.
Services
The services supported by Control Expert include the following standard explicit messaging services:
1
2
5
6
3
4
9
A
7
8
Service Code
Hex Dec
D
E
10
11
1
2
3
4
5
6
7
8
9
10
13
14
16
17
Description
Get_Attributes_All
Set_Attributes_All
Get_Attribute_List
Set_Attribute_List
Reset
Start
Stop
Create
Delete
Multiple_Service_Packet
Apply_Attributes
Get_Attribute_Single
Set_Attribute_Single
Find_Next_Object_Instance
14 20 Detected Error Response
(DeviceNet only)
"X" = the service is available.
"—" = the service is not available.
X
X
X
X
—
X
X
X
X
X
X
X
X
X
X
Available in...
MBP_MSTR block
X
X
X
—
X
X
—
X
X
X
—
X
Control Expert GUI
X
X
—
S1A48993 10/2019
231
Explicit Messaging
Service Code
Hex Dec
15
16
17
18
21
22
23
24
Description
Restore
Save
No Operation (NOP)
Get_Member
19
1A
1B
1C
25
26
27
28
Set_Member
Insert_Member
Remove_Member
GroupSync
"X" = the service is available.
"—" = the service is not available.
X
X
X
X
X
X
X
X
Available in...
MBP_MSTR block
X
X
X
X
Control Expert GUI
X
X
X
—
232
S1A48993 10/2019
Explicit Messaging
Configuring the CONTROL and DATABUF Parameters
Overview
The CONTROL and DATABUF output parameters define the operation performed by the MBP_MSTR function block. For the EtherNet/IP protocol, the structure of the CONTROL and DATABUF output parameters remains the same for every explicit messaging service
see page 231
.
Configuring the Control Parameter
The Control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[0]
CONTROL[1]
CONTROL[2]
CONTROL[3]
Function
Operation
Detected error status
Data buffer length
Response offset
Description
14 = unconnected
270 = connected
Holds the event code
(read-only).
Data buffer length, in words
Offset for the beginning of the response in the data buffer, in 16-bit words
Note: To avoid overwriting the request, confirm that the response offset value is greater than the request length CONTROL[7] .
CONTROL[4]
CONTROL[5]
CONTROL[6]
1
1
Slot
IP address
High byte = slot location on backplane
Low byte = 0 (not used)
High byte = byte 4 of the IP address (MSB)
Low byte = byte 3 of the IP address
High byte = byte 2 of the IP address
Low byte = byte 1 of the IP address (LSB)
Length of the CIP request, in bytes CONTROL[7] Request length
CONTROL[8] Response length Length of the response received, in bytes
Read only—set after completion
1. For example, the Control parameter handles the IP address 192.168.1.6 in the following order: Byte 4 = 192, Byte 3 = 168, Byte 2 = 1, Byte 1 = 6.
S1A48993 10/2019
233
Explicit Messaging
Configuring the Data Buffer
The data buffer varies in size. It consists of contiguous registers that include—in sequence—both the CIP request and the CIP response. To avoid overwriting the request, confirm that the data buffer is large enough to simultaneously contain both the request and response data.
Data Buffer:
Variable size: set in CONTROL[2]
CIP Request:
Request size: set in CONTROL[7]
CIP Response:
Starting position: set in CONTROL[3]
Response size: reported in CONTROL[8]
NOTE: If the response offset is smaller than the request size, the response data overwrites part of the request.
The format of the data buffer’s CIP request and CIP response is described, below.
NOTE: Structure both the request and response in little endian order.
Request:
1
2
Byte offset Field
0 Service
Request_Path_Size
Request_Path
...
Request_Data
Data type
Byte
Byte
Padded
EPATH
Byte array
Description
Service of the explicit message
The number of words in the Request_Path field
This byte array describes the path of the request— including class ID, instance ID, etc.—for this transaction
Service specific data to be delivered in the explicit message request—if none, this field is empty
Response:
1
2
Byte offset Field
0 Reply Service
Reserved
General Status
Data type
Byte
Byte
Byte
Description
Service of the explicit message + 16#80
0
EtherNet/IP General Status (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual)
Additional Status array size—in words 3
4
Size of Additional
Status
Additional Status
Byte
Word array Additional status 1
...
Response Data Byte array Response data from request, or additional detected error data if General Status indicates a detected error
1. Refer to The CIP Networks Library, Volume 1, Common Industrial Protocol at section 3-5.6 Connection
Manager Object Instance Detected Error Codes ;
234
S1A48993 10/2019
Explicit Messaging
MBP_MSTR Example: Get_Attributes_Single
Overview
The following unconnected explicit messaging example shows you how to use the MBP_MSTR function block to retrieve diagnostic information for an STB island from an STB NIC 2212 network interface module, by using the Get_Attributes_Single service.
You can perform the same explicit messaging service using the EtherNet/IP Explicit Message
Window of the Control Expert Ethernet Configuration Tool (
see page 251
Implementing the MBP_MSTR Function Block
To implement the MBP_MSTR function block, you need to create and assign variables, then connect it to an AND block. In the following example, the logic will continuously send an explicit message upon receiving notice of success:
Input Variables
Variables need to be created and assigned to input pins. For the purpose of this example, variables have been created — and named — as described below. (You can use different variable names in your explicit messaging configurations.)
Input Pin
ENABLE
ABORT
Variable
Enable
StopEM
Data Type
BOOL
BOOL
S1A48993 10/2019
235
Explicit Messaging
Output Variables
Variables also need to be created and assigned to output pins. (The names assigned to output variables apply only to this example, and can be changed in your explicit messaging configurations.)
Output Pin
ACTIVE
ERROR
SUCCESS
CONTROL
DATABUF
Variable
EMActive
EMError
EMSuccess
EIP_ControlBuf
EIP_DataBuf
Data Type
BOOL
BOOL
BOOL
Array of 10 WORD s
Array of 100 WORD s
NOTE: To simplify configuration, you can assign the CONTROL and DATABUF output pins to a byte array consisting of located variables. When configured in this manner, you will not need to be aware of the location of data within a word (for example, high versus low byte, and big or little endian format).
Control Array
The control array parameter ( EIP_ControlBuf ) consists of 9 contiguous words. You need to configure only some control words; other control words are read-only and are written to by the operation. In this example, the control array defines the operation as an unconnected explicit message, and identifies the target device:
Register
CONTROL[0]
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
1
Description
Operation:
High byte =
00 (unconnected), or
01 (connected)
Low byte = 0E (CIP explicit message)
Detected error status: read-only (written by operation)
Data buffer length = 100 words
Response offset: offset — in words — for the beginning of the explicit message response in the databuffer
High byte = slot location of the communication module in the backplane
Low byte = 0 (not used)
IP address of the Ethernet communication module:
High byte = byte 4 of the IP address
Low byte = byte 3 of the IP address
Configure Setting (hex)
Yes 16#000E
(unconnected)
No
Yes
Yes
Yes
Yes
16#0000
16#0064
16#0004
16#0400
16#C0A8
236
S1A48993 10/2019
Explicit Messaging
Register
CONTROL[6]
1
CONTROL[7]
CONTROL[8]
Description
IP address of the Ethernet communication module:
High byte = byte 2 of the IP address
Low byte = byte 1 of the IP address
CIP request length (in bytes)
Length of received response (written by operation)
Configure
Yes
Yes
No
Setting (hex)
16#0106
16#0008
16#0000
1. In this example, the control parameter handles the IP address 192.168.1.6 in the following order: Byte 4 =
192, Byte 3 = 168, Byte 2 = 1, Byte 1 - 6.
CIP Request
The CIP request is located at the beginning of the databuffer and is followed by the CIP response.
In this example, the CIP request calls for the return of a single attribute value (diagnostic data), and describes the request path through the target device’s object structure leading to the target attribute:
1
2
Request word
3
High byte
Description
Request path size (in words)
Request path: class assembly object
Request path: instance
Value
(hex)
16#03
16#04
16#64
Low byte
Description Value
(hex)
EM Service: Get_Attributes_Single 16#0E
Request path: logical class segment 16#20
16#24
4 Request path: attribute 16#03
Request path: logical instance segment
Request path: logical attribute segment
16#30
Combining the high and low bytes, above, the CIP request would look like this:
2
3
Request word
1
4
Value
16#030E
16#0420
16#6424
16#0330
S1A48993 10/2019
237
Explicit Messaging
Viewing the Response
Use a Control Expert Animation table to display the EIP_DataBuf variable array. Note that the
EIP_DataBuf variable array consists of the entire data buffer, which includes the:
CIP request (4 words) located in EIP_DataBuf(1-4)
CIP service type (1 word) located in EIP_DataBuf(5)
CIP request status (1 word) located in EIP_DataBuf(6)
CIP response (in this case, 10 words) located in EIP_DataBuf(7-16)
To display the CIP response, follow these steps:
Step
1
2
3
4
Action
In Control Expert, select Tools → Project Browser to open the Project Browser.
In the Project Browser, right-click Animation Tables → New Animation Table.
Result: A new animation table opens.
In the New Animation Table dialog, edit the following values:
Name Type in a table name. For this example: EIP_DataBuf.
Functional Mode
Comment
Accept the default <None>.
Leave blank.
Number of animated characters
Type 100, representing the size of the data buffer in words.
The completed dialog looks like this:
238
Click OK to close the dialog.
S1A48993 10/2019
Explicit Messaging
Step
5
6
Action
In the animation table’s Name column, type in the name of the variable assigned to the databuffer:
EIP_DataBuf and press Enter. The animation table displays the EIP_DataBuf variable.
Expand the EIP_DataBuf variable to display its word array, where you can view the CIP response at words EIP_DataBuf(7-16):
Note: Each word presents 2 bytes of data in little endian format, where the least significant byte is stored in the smallest memory address. For example, ‘0E’ in EIP_DataBuf[0] is the low byte, and
‘03’ is the high byte.
S1A48993 10/2019
239
Explicit Messaging
Modbus TCP Explicit Messaging Using MBP_MSTR Section 8.3
Modbus TCP Explicit Messaging Using MBP_MSTR
Overview
This section shows you how to configure the MBP_MSTR function block to send explicit messages using the Modbus TCP protocol.
What Is in This Section?
This section contains the following topics:
Topic
Modbus TCP Explicit Messaging Function Codes
Configuring the Control Parameter for Modbus TCP Explicit Messaging
Page
240
S1A48993 10/2019
Explicit Messaging
Modbus TCP Explicit Messaging Function Codes
Overview
Every Modbus TCP explicit message performs a function. Each function is associated with a code
(or number). You will need to identify the explicit messaging function by its name, decimal number, or hexadecimal number.
You can execute Modbus TCP explicit messages using either a Control Expert MBP_MSTR function block or the Control Expert Ethernet Configuration Tool’s Modbus Explicit Message Window.
NOTE: Configuration edits made to an Ethernet communication module from the Control Expert
Ethernet Configuration Tool are not saved to the operating parameters stored in the CPU and, therefore, are not sent by the CPU to the module on startup.
Services
The function codes supported by Control Expert include the following standard explicit messaging functions:
Function Code
Hex Dec
Description
7
8
A
17
3
4
1
2
1
2
3
4
7
8
10
23
Write data
Read data
Get local statistics
Clear local statistics
Get remote statistics
Clear remote statistics
Reset module
Read / write data
FFF0 65520 Enable / disable HTTP and
FTP/TFTP services
"X" = the service is available.
"—" = the service is not available.
X
X
X
X
X
X
X
X
X
Available in...
MBP_MSTR block
-
X
X
X
X
X
X
X
X
Control Expert
GUI
S1A48993 10/2019
241
Explicit Messaging
Configuring the Control Parameter for Modbus TCP Explicit Messaging
Overview
The CONTROL and DATABUF output parameters define the operation performed by the
see page 228
) function block. For the Modbus TCP protocol, both the structure and the content of
the CONTROL output parameter vary, depending upon the function code
see page 241
The structure of the CONTROL parameter is described, below, for each supported function code.
Refer to the Quantum Ethernet I/O System Planning Guide sub-ring break.
for an example of an MSTR block created in a Control Expert application to read the ports of a dual-ring switch (DRS) to diagnose a
Control Parameter Routing Register
The CONTROL[5] routing register specifies the source and destination node addresses for network data transfer, and consists of the following 2 bytes:
Most Significant Byte (MSB): contains the source node address, for example, the slot number
of the 140 NOC 78• 00
Least Significant Byte (LSB): contains the destination node address — a value representing either a direct or a bridge address. The LSB is required for devices that are reached through a bridge, for example, an Ethernet to Modbus bridge or an Ethernet to Modbus Plus bridge. The values of the LSB are as follows:
If no bridge is used: LSB is set to zero(0).
If a bridge is used: LSB contains the Modbus Plus on Ethernet Transporter (MET) mapping index value. This value, also known as the Unit ID, indicates the device to which the message is directed.
The CONTROL[5] routing register:
242
When the Ethernet communication module acts as a server, the LSB indicates the destination of a message received by the communication module:
messages with an LSB value from 0 to 254 are forwarded to and processed by the CPU messages with an LSB value of 255 are retained and processed by the Ethernet communication module
NOTE: Unit ID 255 should be used when requesting diagnostic data from the Ethernet communication module.
S1A48993 10/2019
Explicit Messaging
Write Data
The control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Function
Operation
Detected error status
Data buffer length
Starting register
Routing register
Description
1 = write data
Holds the event code
Number of addresses sent to the slave
Start address of the slave to which the data is written, in 16-bit words
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
Byte 4 of the IP address (MSB)
CONTROL[6]
1
CONTROL[7]
1
IP address
Byte 3 of the IP address
CONTROL[8]
1
CONTROL[9]
1
Byte 2 of the IP address
Byte 1 of the IP address (LSB)
1. For example, the control parameter handles the IP address 192.168.1.7 in the following order: Byte 4 =
192, Byte 3 = 168, Byte 2 = 1, Byte 1 = 7.
Read Data
The control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Function
Operation
Detected error status
Data buffer length
Starting register
Routing register
Description
2 = read data
Holds the event code
Number of addresses to be read from the slave
Determines the %MW starting register in the slave from which the data is read. For example: 1 = %MW1,
49 = %MW49)
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
Byte 4 of the IP address (MSB)
CONTROL[6]
1 IP address
CONTROL[7]
1
CONTROL[8]
1
Byte 3 of the IP address
Byte 2 of the IP address
CONTROL[9]
1 Byte 1 of the IP address (LSB)
1. For example, the control parameter handles the IP address 192.168.1.7 in the following order: Byte 4 =
192, Byte 3 = 168, Byte 2 = 1, Byte 1 = 7.
S1A48993 10/2019
243
Explicit Messaging
Get Local Statistics
The control parameter consists of 9 contiguous words, as described below:
Register Function
CONTROL[1] Operation
CONTROL[2] Detected error status
CONTROL[3] Data buffer length
CONTROL[4] Starting register
CONTROL[5] Routing register
Description
3 = read local statistics
Holds the event code ( see page 389 )
(read-only)
Number of addresses to be read from local statistics (0...37)
First address from which the statistics table is read (Reg1=0)
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
— CONTROL[6] (not used)
CONTROL[7]
CONTROL[8]
CONTROL[9]
Module Response: A TCP/IP Ethernet module responds to the Get Local Statistics command with the following information:
Word
00...02
03
Description
MAC Address
Board Status — this word contains the following bits:
Bit 15 0 = Link LED off;
1 = Link LED ON
Bit 3
Bits 14...13
Bit 12
Bits 11...9
Bits 8...4
Reserved
Reserved
0 = 10 Mbit;
1 = 100 Mbit
Reserved
Bit 2
Bit 1
Bit 0
0 = half duplex; 1 = full duplex
0 = not configured; 1 = configured
0 = PLC not running;
1 = PLC or NOC running
Module Type — this bit presents the following values:
0 = NOE 2x1
1 = ENT
2 = M1E
3 = NOE 771 00
4 = ETY
5 = CIP
6 = (reserved)
7 = 140 CPU 651 x0
8 = 140 CRP 312 00
9 = (reserved)
10 = 140 NOE 771 10
11 = 140 NOE 771 01
12 = 140 NOE 771 11
13 = (reserved)
14 = 140 NOC 78• 00
15...16 = (reserved)
17 = M340 CPU
18 = M340 NOE
19 = BMX NOC 0401
20 = TSX ETC 101
21 = 140 NOC 771 01
244
S1A48993 10/2019
Explicit Messaging
Word Description
04 and 05 Number of receiver interrupts
06 and 07 Number of transmitter interrupts
08 and 09 Transmit_timeout detected error count
10 and 11 Collision_detect error count
12 and 13 Missed packets
14 and 15 (reserved)
16 and 17 Number of times driver has restarted
18 and 19 Receive framing detected error
20 and 21 Receiver overflow detected error
22 and 23 Receive CRC detected error
24 and 25 Receive buffer detected error
26 and 27 Transmit buffer detected error
28 and 29 Transmit silo underflow
30 and 31 Late collision
32 and 33 Lost carrier
34 and 35 Number of retries
36 and 37 IP address
Clear Local Statistics
The control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
CONTROL[7]
CONTROL[8]
CONTROL[9]
Function
Operation
Detected error status
(not used)
(not used)
Routing register
(not used)
Description
4 = clear local statistics
Holds the event code ( see page 389 )
(read-only)
—
—
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
—
S1A48993 10/2019
245
Explicit Messaging
Get Remote Statistics
The control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Function
Operation
Detected error status
Data buffer length
Starting register
Routing register
Description
7 = get remote statistics
Holds the event code
Number of addresses to be read from the statistics data field
(0...37)
First address from which the node statistics table is read
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
Byte 4 of the IP address (MSB)
CONTROL[6]
1 IP address
CONTROL[7]
1 Byte 3 of the IP address
CONTROL[8]
1 Byte 2 of the IP address
CONTROL[9]
1 Byte 1 of the IP address (LSB)
1. For example, the control parameter handles the IP address 192.168.1.7 in the following order: Byte 4 =
192, Byte 3 = 168, Byte 2 = 1, Byte 1 = 7.
Clear Remote Statistics
The control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Function
Operation
Detected error status
(not used)
(not used)
Routing register
Description
8 = clear remote statistics
Holds the event code
—
—
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
Byte 4 of the IP address (MSB)
CONTROL[6]
1 IP address
CONTROL[7]
1
CONTROL[8]
1
Byte 3 of the IP address
Byte 2 of the IP address
CONTROL[9]
1 Byte 1 of the IP address (LSB)
1. For example, the control parameter handles the IP address 192.168.1.7 in the following order: Byte 4 =
192, Byte 3 = 168, Byte 2 = 1, Byte 1 = 7.
246
S1A48993 10/2019
Explicit Messaging
Reset Module
The control parameter consists of 9 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
CONTROL[7]
CONTROL[8]
CONTROL[9]
Function
Operation
Detected error status
(not used)
(not used)
Routing register
(not used)
Description
10 = reset module
Holds the event code ( see page 389 )
(read-only)
—
—
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
—
Read/Write Data
The control parameter consists of 11 contiguous words, as described below:
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Function
Operation
Detected error status
Data buffer length
Starting register
Routing register
Description
23 = read / write data
Holds the event code
Number of addresses sent to the slave
Determines the %MW starting register in the slave to which the data will be written. For example: 1 = %MW1, 49 = %MW49)
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index
Byte 4 of the IP address (MSB)
CONTROL[6]
1
CONTROL[7]
1
IP address
Byte 3 of the IP address
CONTROL[8]
1 Byte 2 of the IP address
CONTROL[9]
1 Byte 1 of the IP address (LSB)
CONTROL[10]
CONTROL[11]
Data buffer length
Starting register
Number of addresses to be read from the slave
Determines the %MW starting register in the slave from which the data is read. For example: 1 = %MW1, 49 = %MW49)
1. For example, the control parameter handles the IP address 192.168.1.7 in the following order: Byte 4 =
192, Byte 3 = 168, Byte 2 = 1, Byte 1 = 7.
S1A48993 10/2019
247
Explicit Messaging
Enable/Disable HTTP or FTP/TFTP Services
When HTTP or FTP/TFTP has been enabled using Control Expert configuration tools
see page 161
) , an MSTR block can be used to change the enabled state of the service while the
application is running. The MSTR block cannot change the state of the HTTP or FTP/TFTP services if the service was disabled using one of the configuration tools.
The control parameter consists of 9 contiguous words, as described below:
Register Function
CONTROL[1] Operation
Description
FFF0 (hex) 65520 (dec) = enable / disable HTTP or FTP/TFTP
CONTROL[2] Detected error status Holds the event code (read-only). Codes returned include:
0x000 (Success): MSTR block with operational code 0xFFF0 was called and the enabled state of HTTP or FTP/TFTP was changed.
0x5068 (Busy): MSTR block with operational code 0xFFF0 was called within 2 seconds of the previous call (regardless of return code from previous call).
0x4001 (Same state): MSTR block with operational code 0xFFF0 was called to change the enabled state of HTTP and FTP/TFTP to the states they were already in.
0x2004 (Invalid data): MSTR block with operational code 0xFFF0 was called and the data in the control block did not match the specifications.
0x5069 (Disabled): If the HTTP or FTP/TFTP service was already disabled via the Control Expert interface when the MSTR block with operational code 0xFFF0 was called to change the state of the disabled service.
CONTROL[3] Set this register to 1.
CONTROL[4]
CONTROL[5] Module slot number and destination ID
CONTROL[6]
CONTROL[7]
Request mode
High byte = Module slot number communication module slot
Low byte = Destination ID
Bit 0 (LSB) = 1: Enable FTP/TFTP
Bit 0 (LSB) = 0: Disable FTP/TFTP
Bit 1 = 1: Enable HTTP
Bit 1 = 0: Disable HTTP
Set this register to 0.
CONTROL[8]
CONTROL[9]
HTTP, FTP, and TFTP service state changes made by MSTR with operation code FFF0 (hex) are overridden by the configured value when the module is power-cycled or reset and when a new application is downloaded to the module.
248
S1A48993 10/2019
Explicit Messaging
Here are some examples:
State Configured By
Control Expert
Disabled
Enabled
Action attempted using
MSTR with operation code
FFF0 (hex)
Any
Disable
Enable
Result
MSTR returns detected error code 0x5069 (service was already disabled by configuration)
MSTR returns code 0x000 (success).
Another MSTR block action enables the service
--OR--
The module is reset or power-cycled
--OR--
A new application is downloaded with the service disabled by configuration
MSTR returns detected error code 0x4001 (same state).
No change made.
S1A48993 10/2019
249
Explicit Messaging
Explicit Messaging via the Control Expert GUI Section 8.4
Explicit Messaging via the Control Expert GUI
What Is in This Section?
This section contains the following topics:
Topic
Sending Explicit Messages to EtherNet/IP Devices
Sending Explicit Messages to Modbus TCP Devices
Page
250
S1A48993 10/2019
Explicit Messaging
Sending Explicit Messages to EtherNet/IP Devices
Overview
Use the EtherNet/IP Explicit Message window to send an explicit message from Control Expert to an EtherNet/IP module or device on the network.
An explicit message can be sent as either a connected, or an unconnected message:
an unconnected message requires path — or addressing — information identifying the
destination device and, optionally, device attributes a connected explicit message contains both path information and a connection identifier to the target device
You can use explicit messaging to perform many different services. Not every EtherNet/IP device supports every service.
NOTE: Before you can perform explicit messaging, connect the DTM for the upstream communication module to the module itself. To do this, select the module node in the
DTM Browser, then select Edit → Connect.
The EtherNet/IP Explicit Message window, below, presents an example of both the configuration of an EtherNet/IP explicit message and the response. The explicit message is addressed to a remote STB NIC 2212 network interface module to obtain diagnostic information.
S1A48993 10/2019
251
Explicit Messaging
Sending Explicit Messages
The following steps explain how to execute the EtherNet/IP explicit message, depicted above:
Step
1
2
3
Action
In the DTM Browser, select the communication module that is upstream of the target device.
Click the right mouse button, and in the pop-up menu select Device menu → EtherNet/IP
Explicit Message.
Result: The EtherNet/IP Explicit Message window opens.
Configure the explicit message using the following fields:
IP Address The IP address of the target device, used to identify the target of the explicit message. In the above example: 192.168.1.6.
Class
Instance
The class identifier of the target device, used in the construction of the message path. An integer from 1 to 65535. In this example: 4.
The class instance of the target device, used in the construction of the message path. An integer from 0 to 65535. In this example: 100.
Attribute (Optional) The specific device attribute — or property — that is the target of the explicit message, used in the construction of the message path. An integer from 0 to 65535. In this example: 3
NOTE: Select the check box to enable this field.
NOTE: Refer to your EtherNet/IP device user manual for class, instance and attribute values.
Number The integer associated with the service to be performed by the explicit message. An integer from 1 to 127.
NOTE: If you select Custom Service as the named service, type in a service number. This field is read-only for all other services.
Name
Enter Path
Data
Messaging
Repeat 500 ms
Select the service the explicit message is intended to perform. In this example: Get_Attribute_Single.
(Optional) Select this check box to enable the message path field, where you can manually enter the entire path to the target device. In this example, the path is not manually entered.
NOTE: Displayed only when Advanced Mode is enabled.
The data to be sent to the target device, for services that send data. In this example, leave blank.
Select the type of explicit message to send:
Connected
Unconnected
In this example, select Unconnected.
Select this check box to re-send the explicit message every 500 ms.
In this example, leave this blank.
252
S1A48993 10/2019
Step
4
5
Explicit Messaging
Action
After your explicit message is configured, click Send to Device.
The Response area displays the data sent to the configuration tool by the target device in hexadecimal format.
The Status area displays messages indicating whether or not the explicit message has succeeded.
Click Close to close the window.
S1A48993 10/2019
253
Explicit Messaging
Sending Explicit Messages to Modbus TCP Devices
Overview
Use the Modbus Explicit Message window to send an explicit message from Control Expert to a
Modbus TCP module or device on the network.
You can use explicit messaging to perform many different services. Not all Modbus TCP devices support all services.
NOTE: Before you can perform explicit messaging, connect the DTM for the upstream communication module to the module itself. To do this, select the module node in the
DTM Browser, then select Edit → Connect.
The Modbus TCP Explicit Message window, below, presents an example of both the configuration of a Modbus TCP explicit message, and the response. In this example, the explicit message is used to read 2 registers in the remote STB NIP 2212 network interface module, starting at offset
5391.
254
S1A48993 10/2019
Explicit Messaging
Sending Explicit Messages
To send an explicit message to a target Modbus TCP device:
Step
1
2
3
4
5
Action
In the DTM Browser, select the communication module that is upstream of the target device.
Click the right mouse button, and in the pop-up menu select Device menu → Modbus Explicit
Message.
Result: The Modbus Explicit Message window opens.
Configure the explicit message using the following fields:
IP Address The IP address of the target device, used to identify the target of the explicit message. In this example: 192.168.1.7.
Start Address
Quantity
A component of the addressing path. In this example 5391.
A component of the addressing path. In this example 2.
Read Device
Id Code
Object Id
Refer to your Modbus TCP device user manual for Start Address, Quantity, Read Device Id
Code, and Object Id values.
Unit Id The number of the device, or module, that is the target of the connection.
A value of:
255 (the default) used to access the Ethernet communication module itself
0...254 identifies the device number of the target device, behind a
Modbus TCP to Modbus gateway
Number
(read-only) The service the explicit message is intended to perform. In this example Basic Device Identity. Not used in this example.
(read-only) Specify the object the explicit message is intended to access.
In this example 0. Not used in this example.
Name
(read-only) The integer associated with the service to be performed by the explicit message. An integer from 0...255.
Select the service the explicit message is intended to perform. In this example ReadHoldingRegisters
Repeat 500ms Select this check box to re-send the explicit message every 500 ms. Leave this check box de-selected.
After your explicit message is configured, click Send to Device.
The Response area displays any data sent to the configuration tool by the target device in hexadecimal format.
The Status area displays messages indicating whether or not the explicit message has succeeded.
Click Close to close the window.
S1A48993 10/2019
255
Explicit Messaging
256
S1A48993 10/2019
Quantum EIO
Implicit Messaging
S1A48993 10/2019
Implicit Messaging Chapter 9
Implicit Messaging
EtherNet/IP Implicit Messaging
Introduction
The recommended RPI for EtherNet/IP implicit message connections are 1/2 of MAST cycle time.
If the resulting RPI is less than 25 ms, the implicit message connections may be adversely affected when the diagnostic features of the 140NOC78•00 module are accessed via explicit messaging or
DTM.
In this situation, the following timeout multiplier settings are recommended. Refer to the
Configuring Communication Module Connection Settings (
see page 187
topic to set the timeout multiplier.
RPI (ms) Connection Timeout
2
5
10
20
25
16
8
4
Recommended Timeout
Multiplier
64
32
128
160
160
160
100
NOTE: If you use RPI values lower than recommended, unnecessary bandwidth is consumed on the network, and the module system performance is impacted.
S1A48993 10/2019
257
Implicit Messaging
258
S1A48993 10/2019
Quantum EIO
Diagnostics
S1A48993 10/2019
Diagnostics Chapter 10
Diagnostics
Overview
This chapter describes the diagnostics for the Quantum EIO modules. For details on diagnostics at the system level, refer to the systems diagnostics topic in the Quantum Ethernet I/O System
Planning Guide .
What Is in This Chapter?
This chapter contains the following sections:
Section
10.1
10.2
10.3
10.4
10.5
10.6
Topic
LED Indicators
Diagnostics Available through the CPU
Diagnostics Available through Modbus/TCP
Diagnostics Available through EtherNet/IP CIP Objects
Diagnostics Available through Control Expert
Hot Standby Services
Page
S1A48993 10/2019
259
Diagnostics
LED Indicators Section 10.1
LED Indicators
LED Indicators on the 140NOC78•00 Module
Display
These LEDs are on the front of the 140NOC78•00 module:
260
NOTE: The Net Status 1 and Net Status 2 LEDs are not functional for the 140NOC78000 distributed I/O head module.
S1A48993 10/2019
Diagnostics
Indications
LED conditions:
Description general component not operating invalid configuration not configured configured no/default module MAC no/default port
MAC no link power-up sequence blink (.25 sec on;
.25 sec off)
IP address duplicate IP waiting for IP
I/O data communication default IP address assigned configured IP address assigned invalid configuration no I/O or CIP connections at least one I/O data connection to a remote I/O drop at least one CIP connection
—
—
—
—
—
—
Active Ready Mod Status green green green red
— off off on
—
—
—
5
—
—
—
—
— off off blink off flash on blink 2 off blink 2 off blink 3 —
6 1 blink 4 on blink 5 on blink 6 on on on blink 7 on on on on on on on flash off off flash flash
—
2 off off off off off off off off
Net Status green off off off off off
—
3 off off off flash off flash on off
Net Status 1 red green off off off on/flash off off off
—
4 on off off off off off off off off off on/flash off off off
—
5 off off off flash off flash on flash off red off off off off off
—
6 on off off off off off off
Net Status 2 green off off off on/flash off off off
—
7 off off off flash off flash on flash off red off off off off off
—
8 on off off off off off off flash
NOTE: The 140NOC78100 control head module has the unique functionality of providing multiple
Ethernet network interfaces. The Ready LED indicates the status on any of the configured Ethernet network interfaces. For example, when the interlink cable is disconnected, the Ready LED flashes
5 times, even though the 140NOC78100 module is still connected to the control network.
S1A48993 10/2019
261
Diagnostics
Ethernet Port Indications
These LEDs report the status of the Ethernet port:
Name
LINK (valid for ETH 1 and ETH 2 only)
ACT
Color green yellow
— green green
Status on on off blinking off
Description
100 Mbps link detected
10 Mbps link detected no detected link active Ethernet link (transmit or receive) inactive Ethernet link
262
S1A48993 10/2019
Diagnostics
Diagnostics Available through the CPU Section 10.2
Diagnostics Available through the CPU
System Diagnostics
Introduction
System diagnostics are performed locally on the CPU with system bits (%S) and system words
(%SW).
Local Rack Diagnostics
Local rack diagnostics are accessible for 140 NOC 78• 00, 140 NOC 771 ••, and 140 NOE 771 •• modules within the standard system words (%SW180 to %SW183).
System Bits and Words
This table describes new or modified system bits and words that represent detected errors:
System Bits/Words
%S117
Symbol
EIOERR
%SW101
%SW108
EIO_ CCOTF_COUNT
FORCED_DISCRETE_COUNT
%SW152 ... %SW153 EIO_DROP_ERROR
%SW172 ... %SW175 EIO_CONNECT_STATUS
%SW176 ... %SW179 SDBY_EIO_CONNECT_STATUS
%SW641 ... %SW702 EIO_MOD_HEALTH
Description detected remote I/O error on the Ethernet I/O network
EIO CCOTF counting status register forced bit counting status register detected Ethernet remote I/O drop status
The bit is set to 0 if at least one I/O module in the drop as a detected error.
The bit is set to 1 if all modules are operating properly.
%SW152.0: drop #1
%SW152.1: drop #2
........
%SW153.14: drop #31
Ethernet I/O communication health status for drops in standalone and primary systems
Ethernet I/O communication health status for drops in standby systems
Ethernet remote I/O module health bit status
NOTE: Refer to the EcoStruxure™ Control Expert, System Bits and Words, Reference Manual a detailed explanation of system bits and words.
for
S1A48993 10/2019
263
Diagnostics
Diagnostics Available through Modbus/TCP Section 10.3
Diagnostics Available through Modbus/TCP
Modbus Diagnostic Codes
Supported Diagnostic Codes
Modbus function code 3 provides access to a variety of diagnostic functions, including basic network diagnostics, Ethernet port diagnostics, and Modbus port 502 diagnostics.
To access the function code 3 diagnostics from the local device, set the unit ID to 100.
The following modules support these Modbus diagnostic codes.
Quantum remote I/O head module (140CRP31200)
Quantum distributed I/O head module (140NOC78000)
Quantum control head module (140NOC78100)
Quantum remote I/O adapter module (140CRA31200)
M340 distributed I/O head module (BMXNOC0401)
M340 remote I/O adapter module (BMXCRA31200)
Quantum IEC 61850 module (140NOP85000)
M580 communications module (BMENOC03•1)
M580 communications module (BMENOP0300)
Modbus Function Code 3: Basic Network Diagnostics
Basic network diagnostics start at address 40001(decimal) as described in the following table.
Starting
Address
(Decimal)
40001
Length
(Words)
2
Register Byte Order
MS BYTE LS BYTE
Comments
40003
40004
40005
40006
40008
1
1
1
2
2
MS Byte 00 Byte 01
Byte 02
MS Byte
LS Byte
LS Byte 03
Basic network diagnostic validity
Communication global status
MS Byte
MS Byte
IP 1
IP 3
SM 1
SM 3
LS Byte
LS Byte
IP 2
IP 4
SM 2
SM 4
Supported communication services
Status of communication services
IP address (IP1.IP2.IP3.IP4)
Subnet mask (SM1.SM2.SM3.SM4)
264
S1A48993 10/2019
Diagnostics
Starting
Address
(Decimal)
40010 2
Length
(Words)
Register Byte Order
MS BYTE LS BYTE
40012
40015
40018
40020
40022
40023
40024
40026
40028
40030
40038
3
3
2
2
1
1
2
2
2
8
2
GW 1
GW 3
MAC 1
MAC 3
GW 2
GW 4
MAC 2
MAC 4
MAC 5 MAC 6
MS Byte 00 01
02
04
C00
03
LS Byte 05
C01
C02
C00
C02
MS Byte
MS Byte
C00
C02
C03
C01
C03
LS Byte
LS Byte
C01
C03
C00
C02
C00
C02
Char 1
Char 3
Char 5
Char 7
C01
C03
C01
C03
Char 2
Char 4
Char 6
Char 8
Char 9
Char 11
Char 13
Char 15
Char 10
Char 12
Char 14
Char 16
MS Byte 00 Byte 01
Byte 02 LS Byte 03
Comments
Default gateway (GW1.GW2.GW3.GW4)
MAC address
(MAC1:MAC2:MAC3:MAC4:MAC5:MAC6.
Ether frame format capability / configuration / operational
Ethernet receive frames OK
Ethernet transmit frames OK
Number of open client connections
Number of open server connections
Number of Modbus detected error messages sent
Number of Modbus messages sent
Number of Modbus messages received
Device name
IP assignment mode capability / operational
Example: Reading Basic Network Diagnostics with Modbus Function Code 3
S1A48993 10/2019
265
Diagnostics
Here is an example of how to read registers 40018 and 40019, the
2 below, is calculated as follows:
Ethernet receive frames OK count registers. The request contains 7 bytes. The starting address, shown as a hex value in byte
40018 – 40001 = 17 dec = (11 hex)
The number of registers to be diagnosed (2 hex) is shown in byte 4:
5
6
3
4
1
2
Byte Number
0
Value
Function code = 03 (hex)
Starting Address Hi = 00 (hex)
Starting Address Low = 11 (hex)
No. of Registers Hi = 00 (hex)
No. of Registers Low = 2 (hex)
CRC high byte (inserted by the Modbus sending application)
CRC low byte (inserted by the Modbus sending application)
The normal response is returned in 8 bytes. In this example, the expected response is 14229 hex; this value is shown in bytes 2 through 5 of the response:
3
4
5
6
7
1
2
Byte Number
0
Value
Function code = 03 (hex)
Byte count = 4 (hex)
1 st register data, high byte = 00 (hex)
1 st
register data, low byte = 01 (01 hex)
2 nd
register data, high byte = 42 (hex)
2 nd
register data, low byte = 29 (hex)
CRC high byte
CRC low byte
1
2
Byte Number
0
3
Value
Original function code + 80 hex (= 83 hex)
Detected error code
CRC high byte
CRC low byte
For more information on Modbus function code 3 and other function codes, refer to the Modicon
Modbus Protocol Reference Guide (PI-MBUS-300).
266
S1A48993 10/2019
Diagnostics
Modbus Function Code 3: Ethernet Internal Port Diagnostic Data
Internal port diagnostics start at address 40040 (decimal) as described in the following table.
Starting
Address
(Decimal)
40040
40041
40042
40043
40044
40045
40046
40047
40048
40051
40053
40055
40057
40059
40061
40063
40065
40067
40069
1
1
1
1
3
1
1
1
1
Length
(Words)
2
2
2
2
2
2
2
2
2
2
Register Byte Order
MS BYTE LS BYTE
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
MAC 1
MAC 3
MAC 2
MAC 4
MAC 5 MAC 6
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
Comments
Internal port Diagnostics Data Validity
Internal port Logical/Physical Port Number
Internal port Ethernet Control Capability
Internal port Link Speed Capability
Internal port Ethernet Control Configuration
Internal port Link Speed Configuration
Internal port Ethernet Control Operational
Internal port Link Speed Operational
MAC Address (MAC1:MAC2:MAC3:MAC4:MAC5:MAC6)
Internal port Media Counters Data Validity
Internal port Num Frames Transmitted OK
Internal port Num Frames Received OK
Internal port Num Ether Collisions
Internal port Carrier Sense Errors detected
Internal port Num Ether Excessive Collisions
Internal port CRC Errors detected
Internal port FCS Errors detected
Internal port Alignment Errors detected
Internal port Num Internal MAC Tx Errors detected
S1A48993 10/2019
267
Diagnostics
268
40087
40088
40089
...
40118
40119
40120
40121
Starting
Address
(Decimal)
40071 2
Length
(Words)
Register Byte Order
MS BYTE LS BYTE
40073
40075
40077
40079
40081
40083
40085
40123
40125
40127
40129
2
2
2
2
2
2
2
1
32
1
2
2
2
2
2
Comments
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
Internal port Late Collisions
Internal port Num Internal MAC Rx Errors detected
Internal port Multiple Collisions
Internal port Single Collisions
Internal port Deferred Transmissions
Internal port Frames Too Long
Internal port Frames Too Short
Internal port SQE Test Error detected
MS Byte LS Byte Internal port Interface Label Length
IL char64 IL char63 Internal port Interface Label characters
IL char62 IL char61
...
...
IL char04 IL char03
IL char02 IL char01
MS Byte LS Byte
MSB C00 C01
Internal port Interface Counters Diagnostic Validity
Internal port Num Octets Received
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
Internal port Num Unicast Packets Received
Internal port Num Non Unicast Packets Received
Internal port Num Inbound Packets Discarded
Internal port Num Inbound Packets Error detected
S1A48993 10/2019
Diagnostics
Starting
Address
(Decimal)
401331 2
Length
(Words)
Register Byte Order
MS BYTE LS BYTE
40133
40135
40137
40139
40141
2
2
2
2
2
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
MSB C00 C01
C02 LSB C03
Comments
Internal port Num Inbound Packets Unknown
Internal port Num Octets Sent
Internal port Num Unicast Packets Sent
Internal port Num Non Unicast Packets Sent
Internal port Num Outbound Packets Discarded
Internal port Num Outbound Packets Error detected
Modbus Function Code 3: Ethernet Port 1 Diagnostic Data
Port 1 diagnostics start at address 40143 (decimal). As described in the following table, port 1 diagnostic data fields are the same as for the internal port, with the appropriate starting address offset.
Length Comments Starting
Address
40143
...
40244
1
...
2
Register Byte Order
MS BYTE LS BYTE
MS Byte
...
LS Byte
...
MSB C00
C02
C01
LSB C02
Port 1 Port Diagnostics Data Validity
...
Port 1 Num Outbound Packets Error detected
S1A48993 10/2019
269
Diagnostics
Modbus Function Code 3: Ethernet Backplane Port Diagnostic Data
Backplane port diagnostics start at address 40246 (decimal). As described in the following table, backplane port diagnostic data fields are the same as for the internal port and port 1, with the appropriate starting address offset.
Length Comments Starting
Address
40246
...
40347
1
...
2
Register Byte Order
MS BYTE LS BYTE
MS Byte
...
LS Byte
...
MSB C00
C02
C01
LSB C02
Backplane Port Diagnostics Data Validity
...
Backplane Port Num Outbound Packets Error detected
Modbus Function Code 3: Ethernet Port 3 Diagnostic Data
Port 3 diagnostics start at address 40349 (decimal). As described in the following table, port 3 diagnostic data fields are the same as for the internal port and ports 1 and 2, with the appropriate starting address offset.
Length Comments Starting
Address
40349
...
40450
1
...
2
Register Byte Order
MS BYTE LS BYTE
MS Byte
...
LS Byte
...
MSB C00
C02
C01
LSB C03
Port 3 Port Diagnostics Data Validity
...
Port 3 Num Outbound Packets Error detected
Modbus Function Code 3: Ethernet Port 4 Diagnostic Data
Port 4 diagnostics start at address 40452 (decimal).As described in the following table, port 4 diagnostic data fields are the same as for the internal port and ports 1-3, with the appropriate starting address offset.
Length Comments Starting
Address
40452
...
40553
1
...
2
Register Byte Order
MS BYTE LS BYTE
MS Byte
...
LS Byte
...
MSB C00
C02
C01
LSB C03
Port 4 Port Diagnostics Data Validity
...
Port 4 Num Outbound Packets Error detected
Ethernet Port Not Present
If an Ethernet port is not physically present on the device, the relevant Modbus registers will return data = 0.
270
S1A48993 10/2019
Diagnostics
Modbus Function Code 3: Modbus TCP Port 502 Diagnostic Data
Modbus TCP port 502 diagnostics start at address 40555 (decimal) as described in the following table.
Comments Starting
Address
40555
40557
40558
40559
40561
40563
40564
40565
40566
40567
40568
40570
40571
40572
40573
40575
40576
40578
...
40663
40665
...
2
1
2
1
1
1
1
2
1
1
1
1
1
Length Register Byte Order
MS BYTE LS BYTE
2 MS Byte 00
Byte 02
Byte 01
LS Byte 03
MS Byte
MS Byte
LS Byte
LS Byte
2
2
MSB C00
C02
MSB C00
C02
MS Byte
MS Byte
MS Byte
C01
LSB C03
C01
LSB C03
LS Byte
LS Byte
LS Byte
1
MS Byte
MS Byte
MSB C00
C02
MS Byte
MS Byte
MS Byte
MSB - IP1
IP3
MS Byte
LS Byte
LS Byte
C01
LSB C03
LS Byte
LS Byte
LS Byte
IP2
LSB - IP4
LS Byte
2
2
1
MSB - IP1
IP3
MS Byte
...
MSB - IP1
IP3
MS Byte
IP2
LSB - IP4
LS Byte
...
IP2
LSB - IP4
LS Byte
Modbus TCP/Port 502 Diagnostic
Data Validity
Port 502 Status
Num Open Connections
Num MB Messages Sent
Num MB Messages Received
Num MB Open Client Connections
Num MB Open Server Connections
Max Num Connections
Max Num Client Connections
Max Num Server Connections
Num MB Detected Error Messages
Sent
Num Open Priority Connections
Max Num Priority Connections
Num Entries in Unauthorized Table
Remote IP Address 1 Connection 1
Num Attempts to Open
Unauthorized Connection 1
Remote IP Address 2
Num Attempts to Open
Unauthorized Connection 2
...
Remote IP Address 31
Num Attempts to Open
Unauthorized Connection 31
Connection 2
Connection 31
S1A48993 10/2019
271
Diagnostics
Starting
Address
40666
40668
Length Register Byte Order
MS BYTE LS BYTE
2
1
MSB - IP1
IP3
MS Byte
IP2
LSB - IP4
LS Byte
Comments
Remote IP Address 32
Num Attempts to Open
Unauthorized Connection 32
Connection 32
Modbus Function Code 3: Modbus TCP Port 502 Connection Table Data
Modbus TCP port 502 connection table data starts at address 40669 (decimal) as described in the following table.
Comments Starting
Address
40669
40670
40671
40672
40673
40675
40676
40677
40678
40679
40680
40681
40683
40684
40685
40686
40687
1
1
1
1
2
1
1
1
1
1
2
1
1
Length Register Byte Order
MS BYTE LS BYTE
MS Byte
MS Byte
LS Byte
LS Byte
MS Byte
MS Byte
IP1
IP3
LS Byte
LS Byte
IP2
IP4
MS Byte
MS Byte
MS Byte
LS Byte
LS Byte
LS Byte
1
1
1
1
MS Byte
MS Byte
MS Byte
IP1
IP3
MS Byte
MS Byte
MS Byte
MS Byte
MS Byte
LS Byte
LS Byte
LS Byte
IP2
IP4
LS Byte
LS Byte
LS Byte
LS Byte
LS Byte
Connection Table Validity
Number of Entries
Starting Entry Index
Connection 1 Index
Connection 1 Remote IP Address
Connection 2 Remote Port Number
Connection 2 Local Port Number
Num MB Messages Sent on
Connection 2
Num MB Messages Received on
Connection 2
Num MB Detected Error Messages
Sent on Connection 2
Connection 1
Connection 1 Remote Port Number
Connection 1 Local Port Number
Num MB Messages Sent on
Connection 1
Num MB Messages Received on
Connection 1
Num MB Detected Error Messages
Sent on Connection 1
Connection 2 Index
Connection 2 Remote IP Address
Connection 2
272
S1A48993 10/2019
Diagnostics
Starting
Address
...
41168
41169
...
1
2
Length Register Byte Order
MS BYTE LS BYTE
1
...
MS Byte
IP1
IP3
MS Byte
...
LS Byte
IP2
IP4
LS Byte
Comments
...
Connection 63 Index
Connection 63 Remote IP Address
Connection 63*
41171
41172
41173
41174
41175
1
1
1
1
MS Byte
MS Byte
MS Byte
MS Byte
LS Byte
LS Byte
LS Byte
LS Byte
Connection 63 Remote Port
Number
Connection 63 Local Port Number
Num MB Messages Sent on
Connection 63
Num MB Messages Received on
Connection 63
Num MB Detected Error Messages
Sent on Connection 63
Connection 64 Index
Connection 64 Remote IP Address
41176
41177
1
2
MS Byte
IP1
IP3
LS Byte
IP2
IP4
Connection 64*
415179
41180
41181
41182
1
1
1
1
MS Byte
MS Byte
MS Byte
MS Byte
LS Byte
LS Byte
LS Byte
LS Byte
Connection 64 Remote Port
Number
Connection 64 Local Port Number
Num MB Messages Sent on
Connection 64
Num MB Messages Received on
Connection 64
41183 1 MS Byte LS Byte Num MB Detected Error Messages
Sent on Connection 64
*140 CRA 312 10 and BMX CRA 312 •0 RIO adapter modules support a maximum of 8 connections.
S1A48993 10/2019
273
Diagnostics
Diagnostics Available through EtherNet/IP CIP Objects Section 10.4
Diagnostics Available through EtherNet/IP CIP Objects
Introduction
Quantum Ethernet I/O applications use CIP within a producer/consumer model to provide communication services in an industrial environment. This section describes the available CIP objects for Quantum EIO modules.
What Is in This Section?
This section contains the following topics:
Topic
About CIP Objects
Identity Object
Assembly Object
Connection Manager Object
Modbus Object
Quality Of Service (QoS) Object
TCP/IP Interface Object
Ethernet Link Object
EtherNet/IP Interface Diagnostics Object
EtherNet/IP IO Scanner Diagnostics Object
IO Connection Diagnostics Object
EtherNet/IP Explicit Connection Diagnostics Object
EtherNet/IP Explicit Connection Diagnostics List Object
RSTP Diagnostics Object
Service Port Control Object
Router Diagnostics Object
Router Routing Table Object
Page
274
S1A48993 10/2019
Diagnostics
About CIP Objects
Overview
The Ethernet communication module can access CIP data and services located in connected devices. The CIP objects and their content depend on the design of each device.
CIP object data and content are exposed—and accessed—hierarchically in the following nested levels:
NOTE:
You can use explicit messaging to access these items:
Access a collection of instance attributes by including only the class and instance values for the object in the explicit message.
Access a single attribute by adding a specific attribute value to the explicit message with the class and instance values for the object.
This chapter describes the CIP objects that the Ethernet communication module exposes to remote devices.
S1A48993 10/2019
275
Diagnostics
Identity Object
Overview
The Identity object presents the instances, attributes and services described below.
Class ID
01
Instance IDs
The Identity object presents two instances:
0: class
1: instance
Attributes
Identity object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02
X = supported
— = not supported
Max Instance
GET
X
X
Instance ID = 1 (instance attributes):
Attribute ID hex dec
01
02
01
02
03
04
03
04
Description
Vendor ID
Device Type
Product Code
Revision
Major
Minor
X = supported
— = not supported
Type GET
UINT
UINT
UINT X
STRUCT X
USINT
USINT
X
X
SET
—
—
SET
—
—
—
—
276
S1A48993 10/2019
Diagnostics
Attribute ID hex
05 dec
05
Description Type GET SET
Status bit 2:
0x01=the module is configured bits 4-7:
0x03=no I/O connections established
0x06=at least 1 I/O connection in run mode
0x07=at least 1 I/O connection established, all in IDLE mode
Serial Number
Product Name
Modbus Identity
Word X
UDINT X
STRING X
STRUCT X
—
06
07
18
06
07
24
X = supported
— = not supported
—
—
—
Services
The Identity object performs the following services upon the listed object types:
Description Class Instance Notes Service ID hex dec
01 01 Get_Attributes_All X X
0E 14 Get_Attribute_Single
X = supported
— = not supported
X X
Returns:
all class attributes (instance = 0)
instance attributes 1 to 7 (instance = 1)
Returns the value of the specified attribute.
S1A48993 10/2019
277
Diagnostics
Assembly Object
Overview
The Assembly object consists of the attributes and services described below.
NOTE: You can send an explicit message to the Assembly object only when no other connections have been established that read from or write to this object. For example, you can send an explicit message to the Assembly object if a local slave instance is enabled, but no other module is scanning that local slave.
Class ID
04
Instance IDs
The Assembly object presents the following instance identifiers:
0: class
101, 102, 111, 112, 121, 122: instance
Attributes
The Assembly object consists of the following attributes:
Instance ID = 0 (class attributes):
Attribute ID
01
02
03
X = supported
— = not supported
Description
Revision
Max Instance
Number of Instances
Instance attributes:
Instance ID
101
102
111
112
121
122
X = supported
— = not supported
Attribute ID
03
Description
Local slave 1: T->O input data
Local slave 1: O>T
Local slave 2: T->O input data
Local slave 2: O>T
Local slave 3: T->O input data
Local slave 3: O>T
278
X
X
GET
X
SET
—
—
—
Type
Array of BYTE
Array of BYTE
Array of BYTE
Array of BYTE
Array of BYTE
Array of BYTE
X
X
X
X
X
GET
X
X
—
X
SET
—
X
—
S1A48993 10/2019
Diagnostics
Services
The CIP Assembly object performs these services upon the listed object types:
Service ID hex dec
0E
10
14
16
Description
Get_Attribute_Single
Set_Attribute_Single 1
Class
X
—
Instance
X
X
Notes
Returns the value of the specified attribute
Returns these values:
0E=attribute not settable: assembly is not o->T type
0F=permission denied: assembly is being used by an active connection
13=config too small: the Set_Attribute_Single command contains partial data
15=data too big: the Set_Attribute_Single command contains too much data
X = supported
— = not supported
1. When valid, the size of the data written to the Assembly object using the Set_Attribute_Single service equals the size of the Assembly object as configured in the target module.
S1A48993 10/2019
279
Diagnostics
Connection Manager Object
Overview
The Connection Manager object presents the instances, attributes and services described below.
Class ID
06
Instance IDs
The Connection Manager object presents two instance values:
0: class
1: instance
Attributes
Connection Manager object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
SET
—
—
Instance ID = 1 (instance attributes):
Attribute ID hex dec
01 01
Description
Open Requests
Type
UINT
GET SET Value
02
03
04
02
03
04
Open Format
Rejects
Open Resource
Rejects
Open Other
Rejects
05 05 Close Requests
X = supported
— = not supported
UINT
UINT
UINT
UINT
X
X
X
X
X
X
X
X
X
X
Number of Forward Open service requests received
Number of Forward Open service requests that were rejected due to bad format
Number of Forward Open service requests that were rejected due to lack of resources
Number of Forward Open service requests that were rejected for reasons other than bad format or lack of resources
Number of Forward Close service requests received
280
S1A48993 10/2019
Diagnostics
Attribute ID hex
06 dec
06
07
08
07
08
Description
Close Format
Requests
Close Other
Requests
Connection
Timeouts
Type
UINT
UINT
UINT
GET SET Value
X
X
X
09 09 Connection Entry
List
STRUCT X
0B
0C
0D
11
12
13
CPU_Utilization
MaxBuffSize
UINT
UDINT
BufSize Remaining UDINT
X = supported
— = not supported
X
X
X
X
X
X
—
—
—
—
Number of Forward Close service requests that were rejected due to bad format
Number of Forward Close service requests that were rejected for reasons other than bad format
Total number of connection timeouts that occurred in connections controlled by this connections manager
0 (Unsupported optional item
0 (Unsupported optional item
0 (Unsupported optional item
0 (Unsupported optional item
Services
The Connection Manager object performs the following services on the listed object types:
Class Instance Notes Service ID hex dec
01
0E
01
14
X = supported
— = not supported
Description
Get_Attributes_All
Get_Attribute_Single
X
X
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
S1A48993 10/2019
281
Diagnostics
Modbus Object
Overview
The Modbus object converts EtherNet/IP service requests to Modbus functions, and Modbus exception codes to CIP General Status codes. It presents the instances, attributes and services described below.
Class ID
44 (hex), 68 (decimal)
Instance IDs
The Modbus object presents two instance values:
0: class
1: instance
Attributes
The Modbus object consists of the following attributes:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
Instance ID = 1 (instance attributes):
Attribute ID
—
Description
No instance attributes are supported
Type
—
GET
X
X
SET
—
—
GET
—
SET
—
282
S1A48993 10/2019
Services
The Modbus object performs the following services upon the listed object types:
Class Instance Service ID hex dec
0E
4B
4C
4D
4E
4F
14
75
76
77
78
79
Description
Get_Attribute_Single
Read_Discrete_Inputs
Read_Coils
Read_Input_Registers
Read_Holding_Registers
Write_Coils
50
51
80
81
X = supported
— = not supported
Write_Holding_Registers
Modbus_Passthrough
—
—
—
—
X
—
—
—
X
X
X
X
X
X
X
X
Diagnostics
S1A48993 10/2019
283
Diagnostics
Quality Of Service (QoS) Object
Overview
The QoS object implements Differentiated Services Code Point (DSCP or instances, attributes and services described below.
DiffServe ) values for the purpose of providing a method of prioritizing Ethernet messages. The QoS object presents the
Class ID
48 (hex), 72 (decimal)
Instance IDs
The QoS object presents two instance values:
0: class
1: instance
Attributes
The QoS object consists of the following attributes:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
SET
—
—
284
S1A48993 10/2019
Diagnostics
Instance ID = 1 (instance attributes):
Attribute ID
04
Description
DSCP Urgent
Type
USINT
07
08
05
06
X = supported
— = not supported
DSCP Scheduled USINT
DSCP High USINT
DSCP Low
DSCP Explicit
USINT
USINT
GET SET Value
X X For CIP transport class 0/1 Urgent priority messages, default value = 55.
X X
X X
For CIP transport class 0/1 Urgent priority messages, default value = 47.
For CIP transport class 0/1 Urgent priority messages, default value = 43.
X
X
X
X
For CIP transport class 0/1 Urgent priority messages, default value = 31.
For CIP explicit messages (transport class
2/3 and UCMM), default value = 27.
NOTE: A change in the instance attribute value takes effect on device re-start, for configurations made from flash memory.
Services
The QoS object performs the following services upon the listed object types:
Description Class Instance Service ID hex dec
0E
10
14
16
X = supported
— = not supported
Get_Attribute_Single
Set_Attribute_Single
X
—
X
X
S1A48993 10/2019
285
Diagnostics
TCP/IP Interface Object
Overview
The TCP/IP interface object presents the instances (per network), attributes and services described below.
Class ID
F5 (hex), 245 (decimal)
Instance IDs
The TCP/IP interface object presents 2 instance values:
0: class
1: instance
Attributes
TCP/IP interface object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
SET
—
—
Instance ID = 1 (instance attributes):
Attribute ID
01
02
03
04
Description
Status
Configuration
Capability
Type
DWORD
DWORD
Configuration Control DWORD
Physical Link Object STRUCT
X
X
GET SET Value
X — 0x01
X —
X
—
0x01 = from BootP
0x11 = from flash
0x00 = other
0x01 = out-of-box default
Path Size
Path
UINT
Padded
EPATH
X = supported
— = not supported
286
S1A48993 10/2019
Diagnostics
Attribute ID
05
Description
Interface
Configuration
IP Address
Network Mask
Gateway Address
Name Server
Name Server 2
Domain Name
06 Host Name
X = supported
— = not supported
Type GET
STRUCT X
SET
X
Value
0x00 = out-of-box default
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
STRING X —
Services
The TCP/IP interface object performs the following services upon the listed object types:
Service ID hex dec
01 01
Description Class Instance Notes
Get_Attributes_All X X Returns the value of all attributes.
0E
10
14
16
Get_Attribute_Single
Set_Attribute_Single 1
X
—
X
X
Returns the value of the specified attribute.
Sets the value of the specified attribute.
X = supported
— = not supported
1. The Set_Attribute_Single service can execute only when these preconditions are satisfied:
Configure the Ethernet communication module to obtain its IP address from flash memory.
Confirm that the PLC is in stop mode.
S1A48993 10/2019
287
Diagnostics
Ethernet Link Object
Overview
The Ethernet Link object consists of the instances, attributes and services described below.
Class ID
F6 (hex), 246 (decimal)
Instance IDs
The Ethernet Link object presents the following instance values:
0: class
1: port 1
2: port 2
3: port 3
4: port 4
Attributes
The Ethernet Link object presents the following attributes:
Instance ID = 0 (class attributes):
Attribute ID
01
02
03
X = supported
— = not supported
Description
Revision
Max Instance
Number of Instances
X
X
GET SET
X —
—
—
288
S1A48993 10/2019
Diagnostics
Attribute ID Description hex dec
01 01 Interface Speed
02
Instance ID = 1 (instance attributes):
02 Interface Flags
Type
UDINT
DWORD
03
04
03
04
Physical Address
Interface Counters
In octets
In Ucast Packets
In NUcast Packets
In Discards
In Errors
In Unknown Protos
Out Octets
Out Ucast Packets
Out NUcast Packets
Out Discards
Out Errors
X = supported
— = not supported
S1A48993 10/2019
ARRAY of 6
USINT
STRUCT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
GET SET Value
X
X
X
X
—
—
—
—
Valid values include:
0, 10000000, 100000000
Bit 0: link status
0 = Inactive
1 = Active
Bit 1: duplex mode
0 = half duplex
1 = full duplex
Bits 2—4: negotiation status
3 = successfully negotiated speed and duplex
4 = forced speed and link
Bit 5: manual setting requires reset
0 = automatic
1 = device need reset
Bit 6: local hardware detected error
0 = no event
1 = event detected module MAC address octets received on the interface unicast packets received on the interface non-unicast packets received on the interface inbound packets received on the interface, but discarded inbound packets with detected errors
(does not include in discards) inbound packets with unknown protocol octets sent on the interface unicast packets sent on the interface non-unicast packets sent on the interface outbound packets discarded outbound packets with detected errors
289
Diagnostics
Attribute ID Description hex dec
05 05 Media Counters
Alignment Errors
FCS Errors
Single Collisions
Type
STRUCT
UDINT
UDINT
UDINT
Multiple Collisions
SQE Test Errors
UDINT
UDINT
Deferred Transmissions UDINT
Late Collisions UDINT
Excessive Collisions
MAC Transmit Errors
UDINT
UDINT
Carrier Sense Errors UDINT
Frame Too Long
MAC Receive Errors
UDINT
UDINT
X = supported
— = not supported
GET SET Value
X — frames that are not an integral number of octets in length bad CRC — frames received do not pass the FCS check successfully transmitted frames that experienced exactly 1 collision successfully transmitted frames that experienced more than 1 collision number of times the detected SQE test error is generated frames for which first transmission attempt is delayed because the medium is busy number of times a collision is detected later than 512 bit times into the transmission of a packet frames that do not transmit due to excessive collisions frames that do not transmit due to a detected internal MAC sublayer transmit error times that the carrier sense condition was lost or not asserted when attempting to transmit a frame frames received that exceed the maximum permitted frame size frames not received on an interface due to a detected internal MAC sublayer receive error
290
S1A48993 10/2019
Diagnostics
Attribute ID Description hex dec
06 06 Interface Control
Control Bits
10 16 Interface Label
Type
STRUCT
WORD
Forced Interface Speed UINT
GET SET Value
X
SHORT_STRING X
X
—
API of the connection
Bit 0: Auto-negotiation
0 = disabled
1 = enabled
Note: When auto-negotiation is enabled,
0x0C (object state conflict) is returned when attempting to set either:
forced interface speed or forced duplex mode
Bit 1: forced duplex mode (if autonegotiation bit = 0)
0 = half duplex
1 = full duplex
Valid values include:
10000000, 100000000
Note: Attempting to set any other value returns the detected error 0x09
(invalid attribute value)
A fixed textual string identifying the interface, that should include ‘internal’ for internal interfaces. Maximum number of characters is 64.
X = supported
— = not supported
Services
The Ethernet Link object performs the following services upon the listed object types:
Description Class Instance Service ID hex
01
10
0E
4C dec
01
16
14
76
X = supported
— = not supported
Get_Attributes_All
Set_Attribute_Single
Get_Attribute_Single
Get_and_Clear
X
—
X
—
X
X
X
X
S1A48993 10/2019
291
Diagnostics
EtherNet/IP Interface Diagnostics Object
Overview
The EtherNet/IP Interface Diagnostics object presents the instances, attributes and services described below.
Class ID
350 (hex), 848 (decimal)
Instance IDs
The EtherNet/IP Interface object presents two instance values:
0: class
1: instance
Attributes
EtherNet/IP Interface Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
SET
—
—
292
S1A48993 10/2019
Diagnostics
Instance ID = 1 (instance attributes):
Attribute ID
01
02
03
Description
Protocols Supported
Type
UINT
Connection Diagnostics STRUCT X
Max CIP IO Connections opened
UINT
UINT
GET SET Value
X —
—
Number of Class 1 connections opened since the last reset
Number of Class 1 connections currently opened Current CIP IO
Connections
Max CIP Explicit
Connections opened
UINT
UINT
Number of Class 3 connections opened since the last reset
Number of Class 3 connections currently opened Current CIP Explicit
Connections
CIP Connections
Opening Errors
CIP Connections
Timeout Errors
Max EIP TCP
Connections opened
Current EIP TCP
Connections
IO Messaging
Diagnostics
UINT
UINT
UINT
UINT
STRUCT
IO Production Counter UDINT
X X
Increments each time a Forward Open is not successful (Originator and Target)
Increments when a connection times out
(Originator and Target)
Number of TCP connections (used for EIP, as client or server) opened since the last reset
Number of TCP connections (used for EIP, as client or server) currently open
IO Consumption
Counter
IO Production Send
Errors Counter
IO Consumption
Receive Errors Counter
X = supported
— = not supported
UDINT
UINT
UINT
Increments each time a Class 0/1 message is sent
Increments each time a Class 0/1 message is received
Increments each time a Class 0/1 message is not sent
Increments each time a consumption is received with a detected error
S1A48993 10/2019
293
Diagnostics
Attribute ID
04
Description
Explicit Messaging
Diagnostics
Class 3 Msg Send
Counter
Class 3 Msg Receive
Counter
UCMM Msg Receive
Counter
UCMM Msg Receive
Counter
X = supported
— = not supported
Type GET SET Value
STRUCT X X
UDINT
UDINT
UDINT
UDINT
Increments each time a Class 3 message is sent
(client and server)
Increments each time a Class 3 message is received (client and server)
Increments each time a UCMM message is sent
(client and server)
Increments each time a UCMM message is received (client and server)
Services
The EtherNet/IP Interface Diagnostics object performs the following services upon the listed object types:
Description Class Instance Notes Service ID hex dec
01
0E
4C
01
14
76
Get_Attributes_All
Get_Attribute_Single
Get_and_Clear
X
—
—
X
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
Returns and clears the values of all instance attributes.
X = supported
— = not supported
294
S1A48993 10/2019
Diagnostics
EtherNet/IP IO Scanner Diagnostics Object
Overview
The EtherNet/IP IO Scanner Diagnostics object presents the instances, attributes and services described below.
Class ID
351 (hex), 849 (decimal)
Instance IDs
The EtherNet/IP IO Scanner Diagnostics object presents two instances:
0: class
1: instance
Attributes
EtherNet/IP IO Scanner Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02
X = supported
— = not supported
Max Instance
GET
X
X
SET
—
—
Instance ID = 1 (instance attributes):
Attribute ID
01
Description
IO Status Table
Size
Status
X = supported
— = not supported
Type
STRUCT
UINT
ARRAY of
UNINT
GET
X
SET
—
S1A48993 10/2019
295
Diagnostics
Services
The EtherNet/IP IO Scanner Diagnostics object performs the following services upon the listed object types:
Class Instance Notes Service ID hex dec
01
0E
01
14
Description
Get_Attributes_All
Get_Attribute_Single
X = supported
— = not supported
X
X
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
296
S1A48993 10/2019
Diagnostics
IO Connection Diagnostics Object
Overview
The IO Connection Diagnostics object presents the instances, attributes and services described below.
Class ID
352 (hex), 850 (decimal)
Instance IDs
The IO Connection Diagnostics object presents two instance values:
0: class
1...256: instance (The instance number is the connection number in the configuration.)
Attributes
IO Connection Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
SET
—
—
S1A48993 10/2019
297
Diagnostics
Instance ID = 1 to 256 (instance attributes):
Attribute ID
01
Description
IO Communication
Diagnostics
IO Production Counter
IO Consumption Counter
Type
STRUCT
UDINT
UDINT
UINT IO Production Send Errors
Counter
IO Consumption Receive
Errors Counter
CIP Connection Timeout
Errors
CIP Connection Opening
Errors
UINT
UINT
UINT
CIP Connection State UINT
CIP Last Error General Status UINT
CIP Last Error Extended
Status
UINT
Input Communication Status UINT
Output Communication Status UINT
X = supported
— = not supported
GET SET Value
X X
Increments at each production
Increments at each consumption
Increments each time a production is not sent
Increments each time a consumption is received with a detected error
Increments when a connection times out
Increments each time a connection is unable to open
State of the Connection Bit
General status of the last error detected on the connection
Extended status of the last error detected on the connection
Communication status of the inputs
(see table, below)
Communication status of the outputs
(see table, below)
298
S1A48993 10/2019
Diagnostics
Attribute ID
02
Description
Connection Diagnostics
Production Connection ID
Consumption Connection ID
Production RPI
Production API
Consumption RPI
Consumption API
Production Connection
Parameters
Consumption Connection
Parameters
Local IP
Local UDP Port
Remote IP
Remote UDP Port
Production Multicast IP
Consumption Multicast IP
Protocols Supported
Type
STRUCT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UINT
UDINT
UINT
UDINT
UDINT
UDINT
GET SET Value
X X
Connection ID for production
Connection ID for consumption
RPI for production
API for production
RPI for consumption
API for consumption
Connection parameters for production
Connection parameters for consumption
—
—
—
—
Multicast IP used for production (or 0)
Multicast IP used for consumption (or
0)
Protocol supported on the connection:
1 = EtherNet/IP
X = supported
— = not supported
The following values describe the structure of the instance attributes: CIP Connection State ,
Input Communication Status , and Output Communication Status :
Bit Number
15...3
2
1
0
Description
Reserved
Idle
Consumption inhibited
Production inhibited
Values
0
0 = no idle notification
1 = idle notification
0 = consumption started
1 = no consumption
0 = production started
1 = no production
S1A48993 10/2019
299
Diagnostics
Services
The EtherNet/IP Interface Diagnostics object performs the following services upon the listed object types:
Description Class Instance Notes Service ID hex dec
01
0E
4C
01
14
76
Get_Attributes_All
Get_Attribute_Single
Get_and_Clear
X
—
—
X
X
X
Returns the value of all attributes.
Returns the value of the specified attribute.
Returns and clears the values of all instance attributes.
X = supported
— = not supported
300
S1A48993 10/2019
Diagnostics
EtherNet/IP Explicit Connection Diagnostics Object
Overview
The EtherNet/IP Explicit Connection Diagnostics object presents the instances, attributes and services described below.
Class ID
353 (hex), 851 (decimal)
Instance IDs
The EtherNet/IP Explicit Connection Diagnostics object presents two instance values:
0: class
1...
N : instance ( N = maximum concurrent number of explicit connections)
Attributes
EtherNet/IP Explicit Connection Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID hex
01
02
X = supported
— = not supported
Description
Revision
Max Instance
Value
1
0...N
GET
X
X
SET
—
—
Instance ID = 1 to N (instance attributes):
Attribute ID hex
01
02
03
04
05
06
Description
Originator connection ID
Originator IP
Originator TCP Port
Target connection ID
Target IP
Target TCP Port
X = supported
— = not supported
Type GET SET Value
UDINT X
UINT X
UDINT X
UDINT X
UDINT X
UDINT X
—
—
—
—
—
—
Originator to target connection ID
Target to originator connection ID
S1A48993 10/2019
301
Diagnostics
Attribute ID hex
07
Description
Msg Send Counter
08 Msg Receive counter
Type GET
UDINT X
UDINT X
SET
—
—
Value
Incremented each time a Class 3
CIP message is sent on the connection
Increments each time a Class 3 CIP message is received on the connection
X = supported
— = not supported
Services
The EtherNet/IP Explicit Connection Diagnostics object performs the following services upon the listed object type:
Class Instance Notes Service ID hex dec
01 01
Description
Get_Attributes_All
X = supported
— = not supported
X X Returns the value of all attributes.
302
S1A48993 10/2019
Diagnostics
EtherNet/IP Explicit Connection Diagnostics List Object
Overview
The EtherNet/IP Explicit Connection Diagnostics List object presents the instances, attributes and services described below.
Class ID
354 (hex), 852 (decimal)
Instance IDs
The EtherNet/IP Explicit Connection Diagnostics List object presents two instance values:
0: class
1...
N : instance
Attributes
EtherNet/IP Explicit Connection Diagnostics List object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
SET
—
—
S1A48993 10/2019
303
Diagnostics
Instance ID = 1 to N (instance attributes):
Attribute ID
01
02
Description Type
Number of connections UINT
Explicit Messaging
Connections Diagnostic
List
ID
Originator connection
ARRAY of
STRUCT
UDINT
Originator IP
Originator TCP port
UINT
UDINT
Target connection ID UDINT
Target IP UDINT
Target TCP port
Msg Send counter
UDINT
UDINT
Msg Receive counter UDINT
GET SET Value
X — Total number of opened explicit connections
X —
O->T connection ID
—
—
T->O connection ID
—
—
Increments each time a Class 3 CIP message is sent on the connection
Increments each time a Class 3 CIP message is received on the connection
X = supported
— = not supported
Services
The EtherNet/IP Explicit Connection Diagnostics object performs the following services upon the listed object types:
Class Instance Notes Service ID hex dec
01
08
09
4B
01
08
09
75
X = supported
— = not supported
Description
Get_Attributes_All
Create
Delete
Explicit_Connections_
Diagnostic_Read
X
X
—
—
X
X
—
—
Returns the value of all attributes.
—
—
—
304
S1A48993 10/2019
Diagnostics
RSTP Diagnostics Object
Overview
The RSTP Diagnostics object presents the instances, attributes and services described below.
Class ID
355 (hex), 853 (decimal)
Instance IDs
The RSTP Diagnostics object presents these instance values:
0: class
1: instance
Attributes
RSTP Diagnostics object attributes are associated with each instance.
Instance ID = 0 (class attributes):
Attribute ID
01
Description
Revision: This attribute specifies the current revision of the RSTP
Diagnostic Object. The revision is increased by 1 at each new update of the object.
02
X = supported
— = not supported
Max Instance: This attribute specifies the maximum number of instances that may be created for this object on a per device basis
(for example, an RSTP Bridge). There is 1 instance for each RSTP port on a device.
Type
UINT
UINT
GET
X
X
SET
—
—
S1A48993 10/2019
305
Diagnostics
Instance ID = 1 to N (instance attributes):
Attribute ID Description
01 Switch Status
Protocol Specification
Bridge Priority
Time Since Topology
Change
Designated Root
Root Cost
Type GET CLEAR Value
STRUCT X — —
UINT X —
UDINT
UDINT
Topology Change Count UDINT
String
UDINT
X
X
X
X
X
—
—
—
—
—
Refer to RFC-4188 for attribute definitions and value range. In addition, the following value is defined: [4]: the protocol is IEEE 802.1D-2004 and IEEE 802.1W
Refer to RFC-4188 for attribute definitions and value range.
Refer to RFC-4188 for attribute definitions and value range.
Refer to RFC-4188 for attribute definitions and value range.
Root Port
Max Age
Hello Time
Hold Time
UDINT
UINT
UINT
UDINT
X
X
X
X
—
—
—
—
Forward Delay
Bridge Max Age
Bridge Hello Time
Bridge Forward Delay
X = supported
— = not supported
UINT
UINT
UINT
UINT
X
X
X
X
—
—
—
—
306
S1A48993 10/2019
Attribute ID Description
02 Port Status
Port
Priority
State
Enable
Path Cost
Designated Root
Designated Cost
Designated Bridge
Designated Port
Forward Transitions
Count
03 Port Mode
Port Number
Admin Edge Port
Oper Edge Port
Auto Edge Port
Diagnostics
Type GET CLEAR Value
STRUCT X
UDINT X
X
X
—
Refer to RFC-4188 for attribute definitions and value range.
UDINT
UINT
X
X
X
X
UINT
UDINT
String
UDINT
String
String
UDINT
X
X
X
X
X
X
X
X
X
X
X
X
X
X
STRUCT X
UINT
UINT
X
X
—
—
—
Refer to RFC-4188 for attribute definitions and value range.
Services:
Get_and_Clear: The current value of this
parameter is returned with the response message.
other services: The current value of this parameter is returned without being cleared.
—
This attribute indicates the port number for a data query. The value range is configuration dependent. For a 4-port Ethernet device, as an instance, the valid range is 1...4.
This attribute indicates if this is a user-configured edge port:
1: true
2: false
UINT
UINT
X
X
—
—
Other values are not valid.
This attribute indicates if this port is currently an edge port:
1: true
2: false
Other values are not valid.
This attribute indicates if this port is a dynamically determined edge port:
1: true
2: false
Other values are not valid.
X = supported
— = not supported
S1A48993 10/2019
307
Diagnostics
Services
The RSTP Diagnostics object performs these services:
Description Class Instance Notes Service ID hex dec
01 01 Get_Attributes_All X X
02
32
02
50
Get_Attribute_Single
Get_and_Clear
X
—
X
X
This service returns:
all attributes of the class
all attributes of the instance of the object
This service returns:
the contents of a single attribute of the class
the contents of the instance of the object as specified
Specify the attribute ID in the request for this service.
This service returns the contents of a single attribute of the instance of the object as specified. Then the relevant counter-like parameter(s) within the specified attribute are cleared. (Specify the attribute ID in the request for this service.)
X = supported
— = not supported
308
S1A48993 10/2019
Diagnostics
Service Port Control Object
Overview
The Service Port Control object is defined for port control purposes.
Class ID
400 (hex), 1024 (decimal)
Instance IDs
The Service Port Control object presents these instance Values:
0: class
1: instance
Attributes
Service Port Control object attributes are associated with each instance.
Required class attributes (instance 0):
Attribute ID
01
02
X = supported
— = not supported
Description
Revision
Max Instance
Type
UINT
UINT
Get
X
X
Set
—
—
S1A48993 10/2019
309
Diagnostics
Required instance attributes (instance 1):
Attribute ID hex dec
01 01
Description
Port Control
Type
UINT
Get Set Value
02 02 Mirror UINT
X
X
X
X
0 (default): disabled
1: access port
2: port mirroring
3: extended port bit 0 (default): ETH2 port bit 1: ETH3 port bit 2: ETH4 port bit 3: internal port
X = supported
— = not supported
NOTE:
If the SERVICE/EXTEND port is not configured for port mirroring, the mirror attribute is ignored.
If the value of a parameter request is outside the valid range, the service request is ignored.
In port mirroring mode, the SERVICE/EXTEND port acts like a read-only port. That is, you cannot access devices (ping, connection to Control Expert, etc.) through the
SERVICE/EXTEND port.
Services
The Service Port Control object performs these services for these object types:
Class Instance Description Service ID hex dec
01
02
0E
01
02
14
Name
Get_Attributes_All
Set_Attributes_All
Get_Attribute_Single
10 16 Set_Attribute_Single
X = supported
— = not supported
X
—
X
—
X
X
X
X
Get all attributes in a single message.
Set all attributes in a single message.
Get a single specified attribute.
Set a single specified attribute.
310
S1A48993 10/2019
Diagnostics
Router Diagnostics Object
Overview
The Router Diagnostics object presents the instances, attributes and services described below.
Class ID
402 (hex), 1026 (decimal)
Instance IDs
The Router Diagnostics objects presents 2 instance values:
0: class
1...
N : instance
Attributes
The Router Diagnostic object attributes are associated with each instance.
Instance ID = 0 (class attributes):
Attribute ID
01
02
03
04
05
Description revision: increased by 1 at each new update of the object max instance: the maximum instance number of the object number of instances: the number of object instances currently created at this class level of the device optional attribute list: the number of attributes in the optional attribute list optional list: the number of services in the optional services list
06
07
X = supported
— = not supported maximum ID number of class attributes: the attribute ID number of the last class attribute of the class definition implemented in the device maximum ID number of instance attributes: the attribute ID number of the last instance attribute of the class definition implemented in the device
Type
UINT
UINT
UINT
UINT
UINT
UINT
UINT
GET
X
X
X
X
X
X
X
SET
—
—
—
—
—
—
—
Value current value: 1 default value: 1 current value: 1 current value: 0 current value: 0 current value: 7 default value: 2
S1A48993 10/2019
311
Diagnostics
Instance ID = 1 to N (instance attributes):
Attribute ID
01
02
X = supported
— = not supported
Description forwarding status: whether IP forwarding services are enabled or not current forwarding load: total load, in packets per seconds, handled by the
IP forwarding service
Type
UINT
UINT
GET
X
X
CLEAR
—
—
Value enabled (1): forwarding disabled (0): discarding default: 0 default: 0
Services
The Router Diagnostics object performs these services:
Description Class Instance Service ID hex dec
01 01 Get_Attributes_All X X
0E 14 Get_Attribute_Single X X
Notes
This service returns:
all attributes of the class
all attributes of the object
This service returns:
the contents of a single attribute of the
class the contents of the instance of the object as specified
Specify the attribute ID in the request for this service.
X = supported
— = not supported
312
S1A48993 10/2019
Diagnostics
Router Routing Table Object
Overview
The Router Routing Table object presents the instances, attributes and services described below.
Class ID
403 (hex), 1027 (decimal)
Instance IDs
The Router Routing Table objects presents 2 instance values:
0: class
1...
N : instance
Attributes
The Router Routing Table object attributes are associated with each instance.
Instance ID = 0 (class attributes):
Attribute ID
01
Description revision: increased by 1 at each new update of the object
02
03
X = supported
— = not supported max instance: the maximum instance number of the object number of instances: the number of object instances currently created at this class level of the device
Type
UINT
UINT
UINT
GET
X
X
X
SET
—
—
—
Value current value: 1 current value: 32
S1A48993 10/2019
313
Diagnostics
Instance ID = 1 to N (instance attributes):
Attribute ID
01
X = supported
— = not supported
Description route entry: information about the entry in the routing table, including:
UDINT: route/network destination
UDINT: net mask
UDINT: gateway address
UDINT: IP interface
UINT: cost
UDINT: incoming packets per second
UDINT: outgoing packets per second
Type
Struct
GET
X
CLEAR
—
Services
The Router Routing Table object performs these services:
Description Class Instance Notes Service ID hex dec
01 01 Get_Attributes_All X X
0E 14 Get_Attribute_Single X X
This service returns:
all attributes of the class
all attributes of the object
This service returns:
the contents of a single attribute of the
class the contents of the instance of the object as specified
Specify the attribute ID in the request for this service.
X = supported
— = not supported
314
S1A48993 10/2019
Diagnostics
Diagnostics Available through Control Expert Section 10.5
Diagnostics Available through Control Expert
Introduction
The Quantum EIO modules support online actions. Use the online actions to perform these tasks:
Display EtherNet/IP objects for the head module or a remote EtherNet/IP device.
View and edit the service/extend port configuration parameters for the head module/
Ping the head module or a remote EtherNet/IP or Modbus TCP device to confirm it is active on the Ethernet network.
Connect to a remote device to perform these actions:
View the remote device’s default parameter settings.
View the remote device’s current parameter settings.
Edit and download to the remote device its editable parameter settings.
What Is in This Section?
This section contains the following topics:
Topic
Using the Diagnostic Window
Communication Module Ethernet Diagnostics
Communication Module Bandwidth Diagnostics
Email Diagnostics
Local Slave / Connection Diagnostics
Local Slave or Connection I/O Value Diagnostics
Logging DTM Events to a Control Expert Logging Screen
Page
S1A48993 10/2019
315
Diagnostics
Using the Diagnostic Window
Introduction
Use the Diagnostic window to display:
LED icons (in the left pane of the window) that indicate the operating status of modules, devices
and connections pages (in the right pane of the window) that present diagnostic data for the following:
the communication module local slave nodes activated for the communication module
EtherNet/IP connections between the communication module and a remote EtherNet/IP device
Refer to the following topics for a description of the individual pages that are displayed in the right pane of the Diagnostic window.
NOTE: Before you can open the Diagnostic window, you must first connect the DTM for the target communication module to the physical module itself. To do this, select the module node in the
DTM Browser, then select Edit → Connect.
To open the Diagnostic window:
Step
1
2
Action
In the DTM Browser, select the communication module and click the right mouse button. A popup menu opens.
In the menu, select Device menu → Diagnostic.
Diagnostic LED Icons
During the time that a communication module DTM is connected to the physical communication module, Control Expert sends an explicit message request once per second to detect the state of the communication module and of all the remote devices and EtherNet/IP connections linked to that module.
Control Expert places one of the following status icons over the module, device or connection in the left pane of the Diagnostic window to indicate its current status:
This icon...
Indicates the following state for a...
Communication module Connection to a remote device
Run state
One of the following states:
unknown started stopped not connected
The health bit for every EtherNet/IP connection and Modbus
TCP request, to a remote device or to a sub-device or module, is set to active (1).
The health bit for at least one EtherNet/IP connection or
Modbus TCP request, to a remote device or to a sub-device or module, is set to inactive (0).
316
S1A48993 10/2019
Diagnostics
Communication Module Ethernet Diagnostics
Introduction
Use the Ethernet Diagnostic page to display either dynamically generated or static data for the communication module’s Ethernet port(s). The number of ports on the module determines the number of columns displayed in this page.
Use the Refresh Every 500ms checkbox to display static or dynamic data, as follows:
When the checkbox is...
Selected
De-selected
This page...
Displays data that is dynamically updated every 500 ms, and
Increments the number at the top of the table each time data is refreshed
Displays static data, and
Does not Increment the number at the top of the table, which instead displays a constant value
NOTE: Before you can open the Diagnostic window, you first must connect the DTM for the target communication module to the physical module itself. To do this, select the module node in the
DTM Browser, then select Edit → Connect.
To open this page:
2
3
Step
1
4
Action
In the DTM Browser, select the communication module and click the right mouse button. A pop-up menu opens.
In the menu, select Device menu → Diagnostic.
In the left pane of the Diagnostic window, select the communication module node.
Click on the Ethernet Diagnostic tab to open that page.
S1A48993 10/2019
317
Diagnostics
Ethernet Diagnostic Parameters
The Ethernet Diagnostic page displays the following parameters for each communication module port:
Parameter
General parameters:
Interface Speed
Interface Flags
Duplex Mode
Negotiation Status
Description
Valid values include: 0, 10000000, 100000000 in Mbits/s
Bit 0—Link Status: 0 = Inactive; 1 = Active
Bit 1—Duplex Mode (see below)
Bits 2...4—Negotiation Status (see below)
Bit 5—Manual Setting Requires Reset (see below)
Bit 6—Local Hardware Fault (see below)
0 = half duplex; 1 = full duplex
3 = successfully negotiated speed and duplex
4 = forced speed and link
0 = automatic; 1 = device requires reset Manual Setting Requires
Reset
Local Hardware Fault
Physical Address
Input parameters:
Octets
Unicast Packets
Non-Unicast Packets
Discards
Errors
Unknown Protocols
Output parameters:
Octets
Unicast Packets
Non-Unicast Packets
Discards
Errors
Unknown Protocols
Error counter parameters:
Alignment Errors
FCS Errors
Single Collisions
0 = no event; 1 = event detected
Module MAC Address
Octets received on the interface
Unicast packets received on the interface
Non-unicast packets received on the interface
Inbound packets received on the interface, but discarded
Inbound packets that contain errors (does not include In Discards)
Inbound packets with unknown protocol
Octets received on the interface
Unicast packets received on the interface
Non-unicast packets received on the interface
Inbound packets received on the interface, but discarded
Outbound packets that contain errors (does not include In Discards)
Outbound packets with unknown protocol
Frames that are not an integral number of octets in length
Frames received that do not pass the FCS check
Successfully transmitted frames that experienced exactly one collision
318
S1A48993 10/2019
Diagnostics
Parameter
Multiple Collisions
SQE Test Errors
Deferred Transmissions
Late Collisions
Excessive Collisions
MAC Transmit Errors
Carrier Sense Errors
Frame Too Long
MAC Receive Errors
Description
Successfully transmitted frames that experienced more than one collision
Number of times the SQE test error is generated
Frames for which first transmission attempt is delayed because the medium is busy
Number of times a collision is detected later than 512 bittimes into the transmission of a packet
Frames for which transmission fails due to excessive collisions
Frames for which transmission fails due to internal MAC sublayer transmit error
Times that the carrier sense condition was lost or never asserted when attempting to transmit a frame
Frames received that exceed the maximum permitted frame size
Frames for which reception on an interface fails due to an internal MAC sublayer receive error
S1A48993 10/2019
319
Diagnostics
Communication Module Bandwidth Diagnostics
Introduction
Use the Bandwidth page to display either dynamically generated or static data for the communication module’s bandwidth usage.
Use the Refresh Every 500ms checkbox to display static or dynamic data, as follows:
When the checkbox is...
Selected
De-selected
This page...
Displays data that is dynamically updated every 500 ms, and
Increments the number at the top of the table each time data is refreshed
Displays static data, and
Does not Increment the number at the top of the table, which instead displays a constant value
2
3
4
NOTE: Before you can open the Diagnostic window, you must first connect the DTM for the target communication module to the physical module itself. To do this, select the module node in the
DTM Browser, then select Edit → Connect.
To open this page:
Step
1
Action
In the DTM Browser, select the communication module and click the right mouse button. A pop-up menu opens.
In the menu, select Device menu → Diagnostic.
In the left pane of the Diagnostic window, select the communication module node.
Click on the Bandwidth tab to open that page.
320
S1A48993 10/2019
Diagnostics
Bandwidth Diagnostic Parameters
The Bandwidth Diagnostic page displays the following parameters for the communication module:
Description Parameter
I/O - Scanner:
EtherNet/IP Sent
EtherNet/IP Received
Modbus TCP Requests
Modbus TCP Responses
The number of EtherNet/IP packets the module has sent, since the last reset, in packets/second.
The number of EtherNet/IP packets the module has received, since the last reset, in packets/second.
The number of Modbus TCP requests the module has sent, since the last reset, in packets/second.
The number of Modbus TCP responses the module has received, since the last reset, in packets/second.
I/O - Adapter:
EtherNet/IP Sent
EtherNet/IP Received
The number of EtherNet/IP packets the module has sent—in the role of a local slave—since the last reset, in packets/second.
The number of EtherNet/IP packets the module has received—in the role of a local slave—since the last reset, in packets/second.
I/O - Module
Module Capacity
Module Utilization
The maximum number of packets that the module can process, in packets per second.
The percentage of communication module capacity being used by the application.
Messaging - Client:
EtherNet/IP Activity
Modbus TCP Activity
The number of I/O messages sent by the module—using the EtherNet/IP protocol—since last reset, in packets per second.
The number of I/O messages sent by the module—using the Modbus TCP protocol—since last reset, in packets per second.
Messaging - Server:
EtherNet/IP Activity
Modbus TCP Activity
The number of I/O messages received by the module—using the EtherNet/IP protocol—since last reset, in packets per second.
The number of I/O messages received by the module—using the Modbus
TCP protocol—since last reset, in packets per second.
Module:
Processor Utilization The percent of Ethernet communication module processor capacity used by the present level of communication activity.
S1A48993 10/2019
321
Diagnostics
Email Diagnostics
Diagnosing SMTP Transmissions
Use the Email Diagnostic page to display dynamically generated data describing the communication module’s Email message transmissions.
NOTE: Before you can open the Diagnostic window, connect the DTM for the target communication module to the physical module itself. To do this, select the module node in the
DTM Browser, then select Edit → Connect.
The Email Diagnostic page looks like this:
322
Click the Reset Counter button to reset the counting statistics on this page to 0.
S1A48993 10/2019
Diagnostics
To open this page:
2
3
Step
1
4
Action
In the DTM Browser, select the communication module and click the right mouse button. A pop-up menu opens.
In the menu, select Device menu → Diagnostic. The Diagnostic window opens.
In the left pane of the Diagnostic window, select the communication module node.
Click on the Email Diagnostic tab to open that page.
Email diagnostic Parameters
Email service parameters include the following:
Parameter
Refresh Every 500ms
Email Service
Description
Select this to dynamically update this page every 500ms. The number of times this page has been refreshed appears immediately to the right (in this example, 192.
The status of this service in the Ethernet communication module:
green = operational (OK)
orange = not operational (NOK)
Remote Email Server Status The connection status between Ethernet communication module and the SMTP server:
green = operational (OK) red = not operational (NOK)
SMTP Server IP Address
Sender
Receivers
Subject
Number of Emails Sent
NOTE: Status is checked at start-up and at least every 30 minutes after start-up.
IP address of the SMTP server
The three header fields of the last Email message sent.
Time Since Last Email
Last Error
Time Since Last Email
Total number of emails sent and successfully acknowledged by the
SMTP server.
Counts the number of seconds since the last email was successfully sent.
Hexadecimal code describing the reason for the last unsuccessful
Email transmission (see Premium using EcoStruxure™ Control
Expert, TSX ETC 101 Ethernet Communication Module, User
Manual) . The value “0” indicates no detected transmission errors.
Counts the number of seconds since the last email was successfully sent.
S1A48993 10/2019
323
Diagnostics
Parameter
Number of Errors
Description
Total number of emails that either:
could not be sent
were sent but were not successfully acknowledged by the
SMTP server
Email Service Not Reachable Number of times the SMTP server could not be reached. (Link checked every 30 minutes.)
324
S1A48993 10/2019
Diagnostics
Local Slave / Connection Diagnostics
Introduction
Use the Local Slave Diagnostic page and the Connection Diagnostic page to display I/O status and production/consumption information for selected local slave or connection.
Use the Refresh Every 500ms checkbox to display static or dynamic data, as follows:
When the checkbox is...
Selected
De-selected
This page...
Displays data that is dynamically updated every 500 ms, and
Increments the number at the top of the table each time data is refreshed
Displays static data, and
Does not Increment the number at the top of the table, which instead displays a constant value
NOTE: Before you can open the Diagnostic window, you first must connect the communication module or remote device DTM to the physical module or device. To do this, select the appropriate node in the DTM Browser, then select Edit → Connect.
To open this page:
Step
1
2
3
4
Action
In the DTM Browser, select the communication module and click the right mouse button. A pop-up menu opens.
In the menu, select Device menu → Diagnostic.
In the left pane of the Diagnostic window, click on one of the following:
the communication module node, or
a connection node
Depending upon your selection in step 3, above, click on either the
Local Slave Diagnostic tab or the Connection Diagnostic tab to open that page.
S1A48993 10/2019
325
Diagnostics
Local Slave / Connection Diagnostic Parameters
This page displays the following diagnostic parameters for the selected local slave or connection:
Parameter
Status:
Input
Output
General
Extended
Counter:
Frame Error
Description
An integer representing input status.
An integer representing output status.
An integer representing basic connection status.
An integer representing extended connection status.
Time-Out
Refused
Production
Consumption
Production Byte
Consumption Byte
Increments each time a frame is not sent by missing resources or is impossible to send.
Increments each time a connection times out.
Increments when connection is refused by the remote station.
Increments each time a message is produced.
Increments each time a message is consumed.
Total of produced messages, in bytes, since the communication module was last reset.
Total of consumed messages, in bytes, since the communication module wa last reset.
Packets per second calculated sing current configuration value.
Theoretical Packets per second
Real Packets per second
Diagnostic:
Actual number of packets per second generated by this connection.
CIP Status
Extended Status
An integer representing CIP status.
An integer representing extended CIP status.
Production Connection ID The connection ID.
Consumption Connection
ID
The connection ID.
O -> T API
T -> O API
O -> T RPI
T -> O RPI
Accepted packet interval (API) of the output connection.
Accepted packet interval (API) of the input connection.
Requested packet interval (RPI) of the output connection.
Requested packet interval (RPI) of the input connection.
326
S1A48993 10/2019
Parameter
Socket Diagnostics:
Socket ID
Remote IP Address
Remote Port
Local IP Address
Local Port
Production:
Sequence Number
Max Time
Min Time
RPI
Over Run
Under Run
Consumption:
Sequence Number
Max Time
Min Time
RPI
Over Run
Under Run
Description
Internal Identification of the socket.
IP address of the remote station, for this connection.
Port number of the remote station, for this connection.
IP address of the communication module, for this connection.
Port number of the communication module, for this connection.
The number of the sequence in the production.
Maximum time between two produced messages.
Minimum time between two produced messages.
Current production time.
Increments each time a produced message exceeds RPI.
Increments each time a produced message is less than RPI.
The number of the sequence in the consumption.
Maximum time between two consumptions.
Minimum time between two consumptions.
Current consumption time.
Increments each time a consumed message exceeds RPI.
Increments each time a consumed message is less than RPI.
Diagnostics
S1A48993 10/2019
327
Diagnostics
Local Slave or Connection I/O Value Diagnostics
Introduction
Use the I/O Values page to display both the input data image and output data image for the selected local slave or connection.
Use the Refresh Every 500ms checkbox to display static or dynamic data, as follows:
When the checkbox is...
Selected
De-selected
This page...
Displays data that is dynamically updated every 500 ms, and
Increments the number at the top of the table each time data is refreshed
Displays static data, and
Does not Increment the number at the top of the table, which instead displays a constant value
NOTE: Before you can open the Diagnostic window, you first must connect the communication module or remote device DTM to the physical module or device. To do this, select the appropriate node in the DTM Browser, then select Edit → Connect.
To open this page:
Step
1
2
3
4
Action
In the DTM Browser, select the communication module and click the right mouse button. A pop-up menu opens.
In the menu, select Device menu → Diagnostic.
In the left pane of the Diagnostic window, click on one of the following:
the communication module node, or
a connection node
Click on the I/O Values tab to open that page.
Local Slave / Connection I/O Values
This page displays the following parameters for either a local slave or a remote device connection input and output values:
Parameter
Input/Output data display
Length
Status
Description
A display of the local slave or remote device input or output data image.
The number of bytes in the input or output data image.
The Scanner Diagnostic object’s status, with respect to the read of the input or output data image.
328
S1A48993 10/2019
Diagnostics
Logging DTM Events to a Control Expert Logging Screen
Description
Control Expert maintains a log of events for:
the Control Expert embedded FDT container
each Ethernet communication module DTM each EtherNet/IP remote device DTM
Events relating to the Control Expert FDT container are displayed in the FDT log event page of the
Output Window.
Events relating to a communication module or remote EtherNet/IP device are displayed:
in configuration mode: in the Device Editor, by selecting the Logging node in the left pane
in diagnostic mode: in the Diagnostics window, by selecting the Logging node in the left pane
Logging Attributes
The Logging window displays the result of an operation or function performed by Control Expert.
Each log entry includes the following attributes:
Attribute
Date/Time
Log Level
Message
Detail Message
Description
The time the event occurred, displayed in the format: yyyy-mm--dd hh:mm:ss
The level of event importance. Values include:
Information A successfully completed operation.
Warning An operation that Control Expert completed, but which may lead to a subsequent error.
Error An operation that Control Expert was unable to complete.
A brief description of the core meaning of the event.
A more detailed description of the event, which may include parameter names, location paths, etc.
Accessing the Logging Screen
In Control Expert:
Step
1
2
3
4
Action
Open a project that includes a BME NOC 03•1 Ethernet communication module.
Clock Tools → DTM Browser to open the DTM Browser.
In the DTM Browser, double-click the BME NOC 03•1 (or right-click Open) to open the configuration window.
Select Logging in the navigation tree in the left pane of the window.
S1A48993 10/2019
329
Diagnostics
Hot Standby Services Section 10.6
Hot Standby Services
What Is in This Section?
This section contains the following topics:
Topic
Hot Standby Synchronization
Hot Standby Switchover
Page
330
S1A48993 10/2019
Diagnostics
Hot Standby Synchronization
Introduction
As an example, you have CPU A and CPU B in a Quantum EIO Hot Standby system. CPU A is the primary CPU, and CPU B is the standby CPU. After a switchover, CPU B becomes the primary.
The 140NOC78•00 modules in CPU A synchronize with the 140NOC78•00 modules in CPU B to update CPU B with the data from CPU A.
The 140NOC78•00 standby modules then synchronize with the primary modules every 10 seconds to verify that the data in the standby modules has been updated in the primary modules. If the standby modules unsuccessfully synchronize with the primary modules, they keep polling for the primary modules every 10 seconds.
If the data in the standby and primary modules is different, the synchronization stops and a synchronization error is detected in the standby CPU. The purpose of this process is to check if data has been added to the previous primary module before the polling period expired when the
Hot Standby system switchover occurred.
NOTE: When the 140NOC78•00 standby modules are offline, they do not synchronize.
S1A48993 10/2019
331
Diagnostics
Recovering from a Synchronization Detected Error
If the synchronization between 140NOC78•00 modules does not work properly before the switchover occurs, follow these steps:
Step
1
2
Action
In the DTM Browser window, right-click the 140 NOC 78• 00 module → Connect.
Right-click the 140 NOC 78• 00 module → Device menu → Diagnosis as shown in the following figure:
332
S1A48993 10/2019
Step
3
Action
Click the Hot Standby Diagnostic tab.
Result: The following screen displays:
Diagnostics
S1A48993 10/2019
333
Diagnostics
Step
4
Action
Select the Refresh Every 500ms check box to view the synchronization status.
Click the Copy Files from Standby to Primary bullet in the Force Manual Synchronization field.
Click Send.
Result: The synchronization status is off, and the modules are synchronized as the following screen shows:
334
S1A48993 10/2019
Step
5
Diagnostics
Action
If you select Manual Synchronization, the Force Manual Synchronization field options are disabled.
Result: The synchronization status is on, and the modules are synchronized, as the following screen shows:
S1A48993 10/2019
335
Diagnostics
Hot Standby Switchover
140NOC78•00 IP Address Swap Time
The following table details the 140NOC78•00 module IP address swap time in a Quantum EIO Hot
Standby system:
Maximum swap time
Recommended setting for implicit message
500 ms (IP address swapping) + connection establishment time (3 s)
Set RPI to 1/2 of MAST cycle time (50 ms maximum)
Timeout multiplier setting:
MAST Cycle Time
(ms)
20
50
100
200
255
Recommended RPI
(ms)
10
25
50
50
50
Timeout Multiplier
16
8
4
4
4
Connection
Timeout (ms)
160
200
200
200
200
NOTE: The maximum swap time may increase if the end device does not respond in a timely manner.
NOTE: During the swap, there may be disruption in communication between the 140NOC78•00 module and the end device. Confirm that the application can tolerate this communication disruption.
336
S1A48993 10/2019
Quantum EIO
Firmware Upgrade
S1A48993 10/2019
Firmware Upgrade Chapter 11
Firmware Upgrade
140 NOC 78• 00 Firmware Upgrade
OS
Use the Control Expert OS to upgrade the firmware on the 140 NOC 78• 00 head module.
OS Loader was installed on your PC when you installed Control Expert. (The minimum required version of OS Loader is V7.0. The compatible version is included with your copy of Control Expert.)
A complete firmware upgrade includes the installation of these discrete files:
kernel
exec
The kernel and exec files are installed independently. Therefore, perform the firmware upgrade process two times (once for each file).
The name of the firmware file indicates the upgrade type (kernel or exec). Examples:
kernel file name: CCS1_Noc_Kerl_OSLoader.bin
exec file name: CCS1_Noc_Exec_OSLoader.bin
NOTE: These instructions assume that you are familiar with Control Expert. For more information about the OS Loader, refer to EcoStruxure™ Control Expert, OS Loader, User Manual .
S1A48993 10/2019
337
Firmware Upgrade
Upgrade Procedure
Follow these steps to upgrade either the firmware kernel or the firmware exec.
NOTE:
Before performing the firmware upgrade procedure, check whether the module’s FTP/TFTP
services are enabled, and if they are not, enable them
see page 162
.
We recommend that you update the kernel before you upgrade the exec. Both firmware upgrade files are installed in the same manner. The only difference is the name of the file you select.
Interruption to power or communications during the firmware upgrade process can disrupt the upgrade. If that happens, restart the module.
Step
1
2
3
4
5
6
7
8
9
Action
Connect the PC that is running the Control Expert OS
Loader directly to one of the module ports.
Launch OS Loader.
Click Next to continue.
Select the FTP communication driver and press Next to continue.
Comment
Available ports:
SERVICE port
INTERLINK port
DRS port that is configured for a distributed I/O cloud
Start → Programs → EcoStruxure Control
Expert → OS Loader.
Go directly to the first installation step.
The next screen displays a list of devices discovered by OS Loader. It also displays the FTP address for each discovered device.
— In the Target Address area, type in the FTP Address of the 140 CRP 312 00 module that is the target of the upgrade.
Click Next to continue. Perform these tasks at the next installation screen: a Select Download OS to device.
b Click the Browse button to navigate to and select the desired firmware upgrade file.
Click Next. Perform these tasks at the next installation screen: a Compare the selected firmware File against the firmware already loaded in the Device.
b Confirm that the Hardware ID for both the file and the device are the same
—
—
Click Next. On the summary page, click Download.
The OS Loader displays the progress of the
FTP session. The download is comple when it displays the word SUCCESS.
Click Close.
The firmware download is finished.
338
S1A48993 10/2019
Firmware Upgrade
The upgrade process takes approximately 2 minutes:
1 minute for firmware upgrade
1 minute to reboot and reestablish I/O connections
NOTE: During the firmware upgrade, the I/O communications with the 140 NOC 780 00 head module are interrupted. After the hold up time expires, the I/O modules return to their fallback state.
Hot Standby
Use these steps to upgrade the 140 NOC 78• 00 firmware in Hot Standby configurations:
Step
1
2
Action
Use the preceding instructions to upgrade the firmware for the 140 NOC 78• 00 in the standby rack.
NOTE: During the firmware upgrade, the I/O communications with the 140 NOC 78• 00 module in the primary rack are not interrupted.
When the firmware on the 140 NOC 78• 00 in the standby rack is upgraded, perform a manual switch-over that gives the newly upgraded standby rack the role of primary rack.
S1A48993 10/2019
339
Firmware Upgrade
340
S1A48993 10/2019
Quantum EIO
Embedded Web Pages
S1A48993 10/2019
Embedded Web Pages Chapter 12
Embedded Web Pages
Overview
This chapter describes the embedded web pages for the 140NOC78•00 head module.
The communication module includes a Hypertext Transfer Protocol (HTTP) server. The server transmits web pages for the purpose of monitoring, diagnosing, and controlling remote access to the communication module. The server provides easy access to the communication module from standard internet browsers, including, but not limited to, Internet Explorer.
Before attempting to view the module’s embedded web pages, check whether the module’s HTTP service is enabled, and if not, enable it
see page 162
What Is in This Chapter?
This chapter contains the following sections:
Section
12.1
12.2
12.3
Topic
Accessing the Embedded Web Server
Monitoring the Control Expert Application
Diagnostics
Page
S1A48993 10/2019
341
Embedded Web Pages
Accessing the Embedded Web Server Section 12.1
Accessing the Embedded Web Server
Introduction
This section introduces the 140NOC78•00 head module’s embedded web server, and describes how to access (and to control access to) the web pages.
What Is in This Section?
This section contains the following topics:
Topic
Introducing the Embedded Web Pages
Accessing the Home Page
Using and Editing a Username and Passwords
Page
342
S1A48993 10/2019
Embedded Web Pages
Introducing the Embedded Web Pages
Introduction
Use the 140NOC78•00 head module’s embedded web server pages to:
display real-time diagnostic data for both the module and other networked devices
read the values of and write values to Control Expert application variables manage and control access to the embedded web pages by assigning separate passwords for:
viewing the diagnostic web pages using the data editor to write values to Control Expert application variables
Requirements
The embedded web server presents module data in the form or standard HTML web pages.
Access the embedded web pages using Internet Explorer version 4.0 or later, running the Java
Runtime Environment (JRE) version 1.6 or later.
S1A48993 10/2019
343
Embedded Web Pages
Accessing the Home Page
On First Use
Before you begin to use the 140NOC78100 control head module’s embedded web pages, you need to:
navigate to the web server (see Quantum using EcoStruxure™ Control Expert,
140 NOC 771 01 Ethernet Communication Module, User Manual)
access web page content by inputting the default username and password (see Quantum using
EcoStruxure™ Control Expert, 140 NOC 771 01 Ethernet Communication Module, User
Manual) combination
change passwords (see Quantum using EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual) that are required for:
accessing web pages writing data values using the data editor
Navigating to the Web Server
To access the embedded web server:
Step
1
2
3
Action
Open an Internet browser.
Enter the IP address of the 140NOC78100 module in the format: http://IP address .
Click Enter.
NOTE: If a DNS name has been assigned to the module, the DNS name can be used instead of the IP address.
344
S1A48993 10/2019
Result: The web server opens, displaying the Home page:
Embedded Web Pages
Use the Home page as the point of entry to the 140NOC78100 module’s embedded web server.
From here, you can navigate to every other web page.
S1A48993 10/2019
345
Embedded Web Pages
Using and Editing a Username and Passwords
Inputting the Username and Web Page Access Password
A username and password are required to access web page content and edit application data.
Username and password settings are case sensitive.
The embedded web pages support the use of a single, editable username for both web page access and data editing. The factory-default username setting is USER.
The embedded web pages require 2 different passwords, as follows:
an HTTP access password, which grants read-only access to web page content
a data editor write password, which permits the editing of data values using the Data Editor
Each password can be edited. The factory default setting for each password is USER.
To input a username and password combination
Step
1
2
Description
After navigating to the embedded web server (see Quantum using EcoStruxure™ Control
Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) , select one of the main menu selections (for example, Setup).
Select a page name from the list of pages on the left side of the page (for example, Security).
Result: The following dialog opens.
346
3 Type the required Username and Password combination, then click OK.
NOTE: In the above example, the settings for both the Username and Password are set to the default setting of USER.
S1A48993 10/2019
Embedded Web Pages
Editing the Username and Passwords
The single username and both passwords can be edited in the Security web page. To edit username and passwords, follow these steps:
Step Description
1 Navigate to and open the web server, (see Quantum using EcoStruxure™ Control Expert,
140 NOC 771 01 Ethernet Communication Module, User Manual) using the IP address of the communication module.
Result: The Home page opens.
2 From the Home page, click the Setup main menu item. If required, input the username and web page password (see Quantum using EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual) .
Result: The Setup page opens:
S1A48993 10/2019
347
Embedded Web Pages
Step Description
3 On the left side of the page, click the Security node. (If required, input the Username and web page access Password.)
The Security page opens:
348
4
5
6
7
To change the username and password combination used for web page access, in the HTTP access rights section of the page, enter values for the following fields:
Username:
To change the username: type in a new username
To retain the current username (for example, if you are changing only the password): type in the current username
New password:
To change the password: type in a new password
To keep the current password (for example, if you are changing only the username): type in the current password
Confirm password: Type in the same password entered in the New password field, above.
Click the Save User button.
To change the password used for writing data values in the Data Editor, in the
Data Editor Write Password section of the page, enter values for the following fields:
Data Editor write password:
Type in the current password that is required to write data using the
Data Editor.
New write password:
Confirm write password:
Type in the new Data Editor password.
Type in the same password entered in the New write password field, above.
Click the Change Write Password button.
S1A48993 10/2019
Embedded Web Pages
Monitoring the Control Expert Application Section 12.2
Monitoring the Control Expert Application
Overview
This section describes how to use the 140NOC78•00 head module’s embedded web pages to monitor the Control Expert application.
What Is in This Section?
This section contains the following topics:
Topic
Using the Monitoring Page
Data Editor (Standard)
Working With Data Templates
Data Editor (Lite)
Page
S1A48993 10/2019
349
Embedded Web Pages
Using the Monitoring Page
Monitoring Page
Click the main menu Monitoring command to display the Monitoring page:
To access a monitoring service, click either of the following links:
Data Editor Lite
Data Editor Standard
350
S1A48993 10/2019
Embedded Web Pages
Data Editor (Standard)
Overview
The Data Editor is a Java applet that dynamically displays run-time application data. Use the
Data Editor to create and edit data monitoring tables that provide read/write access to application data and device registers.
NOTE: Write access is password protected.
WARNING
UNINTENDED EQUIPMENT OPERATION
The data editor makes it possible to write to application variables and change application data values.
Use passwords to strictly limit access to write data functionality.
Do not use weak passwords, including the default password and other obvious passwords.
Limit access to trained personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This topic describes the Data Editor user interface.
S1A48993 10/2019
351
Embedded Web Pages
Data Editor
The Data Editor presents the following controls:
1 toolbar
2 data template list
3 data template
4 configuration area
352
S1A48993 10/2019
Embedded Web Pages
Toolbar
The Data Editor toolbar presents the following features:
Command or Field
New
Save
Icon Description
If a node in the data template list is selected, this command opens the New table dialog for the creation of a new data template. The new data template is inserted below the selected node.
If a row in the currently open data template is selected, this command inserts a new row below the selected row.
Saves changes made to both the data template list and each data template.
Copy
Paste
Delete
Change password
Read PLC symbols
Start animation
Stop animation
If a node in the data template list is selected, this command copies the selected data template.
If an item (or row) in the currently open data template is selected, this command to copies the selected item.
If the root, or Empty, node is selected in the data template list, this command pastes a previously copied data template into the list.
If an empty item (or row) in the currently open data template is selected, this command pastes a previously copied item into the data template item at the selected row.
NOTE: When adding a copied item, or row, to a data template, the paste command will overwrite item data in the selected row. To insert a copied row between existing rows, first use the New command to create an empty row, then paste the copied data into the new row.
Deletes the selected data template from the list, or the selected item from the data template.
Opens the Change password dialog, where you can change the Data Editor
Write (see Quantum using EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual) password.
NOTE: The Data Editor Write password can also be changed in the Setup →
Security web page.
Loads the existing Control Expert symbol, or variable, names into the Lookup
Variable dialog. Variables that have been loaded into this dialog can be added to the currently open data template.
Starts the dynamic display of value and status for the items contained in the selected data template.
NOTE: The Start animation icon is visible only when animation is turned
OFF.
Stops the dynamic display of value and status for the items contained in the selected data template.
NOTE: The Stop animation icon is visible only when animation is turned ON.
S1A48993 10/2019
353
Embedded Web Pages
Command or Field
Rate
IP address
Icon Description
— The refresh rate of the dynamic display of data template items, in milliseconds.
— The IP address of the Ethernet communication module and its embedded web server.
Data Template List
The data template list displays a node for each data template that was either:
previously saved
— or — created after the Data Editor was opened, but not yet saved
Select a data template in this list to view or edit its contents.
NOTE: If you create a new data template then navigate away from the Data Editor before clicking the Save button, the new data template will be lost.
Data Template
Use the data template when animation is turned ON to monitor the status and values of items for the template that is currently selected in the data template list.
Each data template item (or row) is defined in the configuration area. A data template item can contain the following fields:
Field
Symbol
Address
Description
Contains the names of Control Expert symbols (variables).
Contains direct addresses and the addresses of Control Expert symbols (variables). Any direct address can be viewed by entering its reference in this field. Valid direct addresses include:
%Mi
%Ii
%IWi same as for 0X coils same as 1x for discreet inputs same as 3x for input registers
%MWi, %MDi, %MFi same as 4x for holding registers
NOTE:
A single bit of any word address (for example, %MWi, %IWi) can be specified by appending
".j" to the address, where "j" is a bit index in the range of 0 (LSB) to 15 (MSB). For example, bit 4 of the value at %MW101 would be specified as %MW101.4.
A direct address can include an index specification that allows it to be treated as an array variable. Indexed addressing can be used with a %Mi, %MWi, %MDi, or %MFi address by appending "[j]" to the address of the beginning of the array, where "j" is an unsigned integer value. For example, the third value of an array of float values starting at %MF201 would be specified as %MF201[2].
354
S1A48993 10/2019
Embedded Web Pages
Field
Data type
Value
Format
Status
Description
Contains the data type of the symbol (variable) or direct address. Symbol (variable) data types appear automatically when the symbol (variable) is located. Select direct address data types from a drop-down list. The following data types are valid:
INT
UINT
DINT
UDINT
REAL
TIME
16-bit signed integer
16-bit unsigned integer
32-bit signed integer
32-bit unsigned integer
32-bit IEEE floating point
32-bit unsigned integer (in ms)
DATE
TOD
BOOL
Date (32-bit BCD)
Time of day (32-bit BCD)
1 bit discrete (Boolean)
When animation has started, this field displays the value of the symbol (variable) or direct address. This field is updated continuously.
Contains the format type for displaying the value of the symbol (variable) or direct address. The following formats are available: bool Boolean dec hex binary
ASCII
Decimal
Hexadecimal
Binary bytes displayed as ASCII characters time date day_hr_min_sec_ms
YYYY-MM-DD or HH:MM:SS
Contains messages describing the status of communication with the direct address: if communication is normal The status message reads OK if communication is interrupted
The status field displays a system message describing the interruption
S1A48993 10/2019
355
Embedded Web Pages
Configuration Area
Open and close the configuration area by double-clicking on a row in the data template. The configuration area will display the configuration settings for the selected row. Use the up and down arrows on your keyboard to move between rows in the data template and display their settings in the configuration area.
Use the configuration area when data template animation is turned OFF to:
create a new data template display the items contained in an existing data template
see page 357
see page 359
see page 359
Use the configuration area when data template animation is turned ON to write data to read/write application variables.
Refer to the topic Working With Data Templates use the controls in the configuration area.
see page 357
for more information on how to
356
S1A48993 10/2019
Embedded Web Pages
Working With Data Templates
Creating a Data Template
To display and access application data, first create a data template.
To create a new data template, follow these steps:
Step
1
2
Description
Confirm that Data Editor animation is OFF. If necessary, click the Stop animation toolbar button.
Click the New table toolbar button.
Result: The New table dialog opens:
3
4
In the Table name field, type in the name of the new data template.
Click Ok.
Result: The new data template appears as a node in the data template list.
NOTE: Save the new data template before performing any other task in the Data Editor. Moving to another page or creating a new data template in the current page before saving your work deletes the new data template.
S1A48993 10/2019
357
Embedded Web Pages
Saving a Data Template
After you save a new data template, you can re-use it to view or modify its contents.
NOTE:
The last saved modification overwrites the pre-existing data template, even if the data template
was originally created by someone other than yourself.
If a data template is open for viewing by someone else, your edits to that data template will be seen only when that person next accesses the Data Editor.
To save a new data template, follow these steps:
Step
1
Description
Click the Save toolbar button.
Result: The Save application dialog opens:
2
3
In the Password field, type in the Web Page (HTTP) Access password.
NOTE: The default password is USER.
Click Ok.
The new data template is saved.
358
S1A48993 10/2019
Embedded Web Pages
Displaying an Existing Data Template
When you open a saved data template, you can use it to:
edit its contents by inserting either a direct address
monitor the value and status of data items write data values to a read/write variables
The data template list, located on the left side of the Data Editor, displays the saved data templates. Select a data template node from the list to display that template’s data items in the spreadsheet on the right:
Inserting a Direct Address Into a Data Template
You can add Control Expert direct address items (also called located registers) into a data template. After a direct address item is added, you can view or modify its value.
To add a direct address item to a data template, follow these steps:
Step
1
2
3
4
Description
In the data template spreadsheet, double-click on an empty row.
Result: The Data Editor configuration area opens.
In the Address field of the configuration area, type the item’s direct address.
In the configuration area, click Apply.
Result: The selected row is updated.
Save your edits.
S1A48993 10/2019
359
Embedded Web Pages
Modifying Data Values Using a Data Template
You can use the Data Editor to write data values to a direct address item, and send the new value to the controller.
For example, suppose that you have programmed a pushbutton object to jog a motor when the button is depressed and to stop jogging when the button is released. If communications are lost while the button is depressed, the motor will continue to jog even when the button is released.
Graphic objects are not designed to be used to control situations like this, unless other interlock methods are installed in the system.
NOTE: You can only modify the value of data items that are defined as read/write in the Control
Expert application.
To use the Data Editor to edit data, follow these steps:
2
3
Step
1
Description
In the data template spreadsheet, double-click on the item you want to write data to.
Result: The Data Editor configuration area opens, displaying the fields for the selected item.
In the Value field, type the desired data value.
Click Apply.
Result: The Enter password dialog opens:
4
5
In the Password field, type the Write Data password.
NOTE: The default password is USER.
Click OK.
Result: The new value is sent to the controller.
360
S1A48993 10/2019
Embedded Web Pages
Data Editor (Lite)
Overview
Data Editor Lite is a version of the Data Editor that is smaller in size and therefore faster to download, especially for use via a dial-up connection.
Data Editor Lite presents the same interface as the Data Editor, with the exception that its toolbar does not include the Read PLC Symbols function:
Variables
Data Editor Lite accepts the following IEC variables:
Address
%MW IEC internal word
%MD IEC double word
%M IEC internal bits
Type
INT
DINT
BOOL
Display
DECIMAL
DECIMAL
BOOLEAN
NOTE: You cannot access the Lookup Variable dialog and insert symbols into a data template using Data Editor Lite. You can insert only direct addresses.
S1A48993 10/2019
361
Embedded Web Pages
Re-Using Data Editor Templates
Data Editor Lite can reuse the same templates created with the Data Editor. However, Data Editor templates can use a wider range of variable types than Data Editor Lite. When Data Editor Lite encounters a variable it cannot manage, it displays Not Supported as the data type. In this case, the variable cannot be edited using Data Editor Lite.
362
S1A48993 10/2019
Embedded Web Pages
Diagnostics Section 12.3
Diagnostics
Overview
This section describes the diagnostic services provided by the 140NOC78•00 head module.
What Is in This Section?
This section contains the following topics:
Topic
Using the Diagnostics Page
Status Summary
Rack Viewer
Processor Load
Scanner Status
Messaging
Ethernet Statistics
QoS Configuration
Redundancy
Email Diagnostics
Network Time Service Diagnostics
Properties
Router Status
Page
S1A48993 10/2019
363
Embedded Web Pages
Using the Diagnostics Page
Diagnostics Page
Click the main menu Diagnostics command to display the Diagnostics page:
364
To access a monitoring service, click one of the following links:
Status Summary
Rack Viewer
Ethernet:
see page 368
Processor Load
Ethernet Statistics
Redundancy
see page 365
see page 373
see page 369
see page 371
see page 380
see page 377
see page 375
see page 379
see page 382
Router Status
Properties
see page 386
see page 385
S1A48993 10/2019
Embedded Web Pages
Status Summary
Introduction
Use the Status Summary page to view the status of:
the LEDs (see Quantum using EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual) located on the front of the 140NOC78•00 head module the Ethernet services
(see Quantum using EcoStruxure™ Control Expert, 140 NOC 771 01
Ethernet Communication Module, User Manual) supported by the 140NOC78•00 module the 140NOC78•00 module in its role as:
scanner
Modbus TCP server
EtherNet/IP messaging server
Status Summary Display
The Status Summary page looks like this:
S1A48993 10/2019
365
Embedded Web Pages
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → Status Summary.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
Status Summary Data
The LEDs section of the page can present the following operational states:
LED
Active
Ready
Module Status
Network Status
Network Status 1
Network Status 2
Color
Green
Red
Green
Red
Green
Red
Green
Red
Green
Gray
Green
Gray
Text Descriptions
Ready for operation
Detected error present
Waiting for address server response
Duplicate IP address
Waiting for served IP configuration
Default IP address in use
Detected configuration error
Ready for operation
Not configured
Fault detected
Recoverable fault detected
Ready for operation
Detected connection error
Duplicate IP address
Ready for operation
Detected connection error
Duplicate IP address
Ready for operation
Detected connection error
Duplicate IP address
366
S1A48993 10/2019
Embedded Web Pages
The Services section of the page can present the following functional conditions:
Function
DHCP Server
FDR Server
Access Control
IP Forwarding
Scanner Status
Color
—
Network Time Service
E-mail Service
Green
Red
Gray
—
—
Text Descriptions
Enabled
Enabled
Disabled
Disabled
Working properly
At least one connection is bad
Not configured
Working properly
At least one connection is bad
S1A48993 10/2019
367
Embedded Web Pages
Rack Viewer
Introduction
Use the Rack Viewer to access web pages that describe the identity, placement, configuration, and operation of modules in the Quantum rack.
To view information describing a specific module, including the 140NOC78•00 head module, click the image of that module in the Rack Viewer.
Rack Display
The Rack Viewer looks like this, when it is first opened:
368
To open this page:
2
3
Step
1
4
5
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Rack Viewer.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
To open a page displaying configuration and operating data for the 140NOC78•00 module, click the module image in the rack.
Result: The Rack Viewer parameter page opens.
To return to the main Rack Viewer page, click the Back arrow.
S1A48993 10/2019
Embedded Web Pages
Processor Load
Introduction
Use the Processor Load web page to display dynamically generated data for the 140NOC78•00 head module’s bandwidth usage.
Processor Load Display
The Processor Load page looks like this:
NOTE: The background color for the Processor Utilization and Module Utilization values varies, depending upon the percentage of utilization. If utilization is:
90% to 100%: background color is RED
80% to 89.99%: background color is YELLOW
0% to 79.99%: background color is GRAY
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → Processor Load.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
369
Embedded Web Pages
Processor Load Parameters
The Processor Load page displays the following parameters for the communication module:
Description Parameter
Module Load:
Processor Utilization The percent of Ethernet communication module processor capacity used by the present level of communication activity. The background color of the value changes, depending on the percentage utilization.
I/O Scanner:
EtherNet/IP Sent (writes)
EtherNet/IP Received
(read)
Modbus TCP Requests
Modbus TCP Responses
The number of EtherNet/IP packets the module has sent, since the last reset, in packets/second.
The number of EtherNet/IP packets the module has received, since the last reset, in packets/second.
The number of Modbus TCP requests the module has sent, since the last reset, in packets/second.
The number of Modbus TCP responses the module has received, since the last reset, in packets/second.
I/O Adapter:
EtherNet/IP Sent (writes)
EtherNet/IP Received
(read)
I/O - Module
Module Capacity
The number of EtherNet/IP packets the module has sent in the role of a local slave since the last reset, in packets/second.
The number of EtherNet/IP packets the module has received in the role of a local slave since the last reset, in packets/second.
Module Utilization
The maximum number of packets that the module can process, in packets per second.
The percentage of communication module capacity being used by the application. The background color of the value changes, depending on the percentage utilization.
Messaging - Client:
EtherNet/IP activity
Modbus TCP activity
The number of I/O messages sent by the module using the EtherNet/IP protocol since last reset, in packets per second.
The number of I/O messages sent by the module using the Modbus TCP protocol since last reset, in packets per second.
Messaging - Server:
EtherNet/IP activity
Modbus TCP activity
The number of I/O messages received by the module using the EtherNet/IP protocol since last reset, in packets per second.
The number of I/O messages received by the module using the Modbus TCP protocol since last reset, in packets per second.
370
S1A48993 10/2019
Embedded Web Pages
Scanner Status
Introduction
The Scanner Status web page displays read-only data describing the current state of the
140NOC78•00 head module in its role as I/O scanner.
Scanner Status Display
The top of the page displays the following general diagnostic information about the scanner:
I/O scanning status
A value of Operational indicates that the values in the Scanner Status grid are reporting the state of scanned devices.
A value of Stopped indicates the local system is not scanning. In this case, any data that appears in the Scanner Status grid is meaningless.
Number of transactions per second
Number of connections
The Scanner Status web page looks like this:
In the Scanner Status grid, the colors that appear in each block indicate the following states for specific remote devices:
GREEN indicates that a device is being scanned
BLACK indicates that I/O scanning of the specific device has been intentionally disabled
GRAY indicates an device that is not configured
RED indicates a suspect device
NOTE: A green Scanner Status indicator in the grid can remain green for a remote scanned device after the Ethernet cable is detached from that device. This situation can occur if the health timeout value for that device is set to 0.
To avoid this result and to help promote the accurate reporting of I/O scanning health, configure an operational health timeout value in the range 1...65535 (in 1 ms increments).
S1A48993 10/2019
371
Embedded Web Pages
The grid also indicates the protocol used to communicate with the remote device:
MB: indicates a Modbus TCP connection
EIP: indicates an EtherNet/IP connection
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → Scanner Status.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
372
S1A48993 10/2019
Embedded Web Pages
Messaging
Introduction
The Messaging page provides current information on the open TCP connections on port 502.
Messaging Display
The top of the page displays the number of messages sent and received by local port 502.
The Messaging page looks like this:
The display grid provides the following information about each active connection:
Conn.: the connection number: 1 to 64
Remote address: the IP address of the remote device
NOTE: If the remote device includes an embedded web server, click the Remote address to open that server and view the remote device’s web pages.
Remote port: the TCP port for the connection on the remote device
Local port: the TCP port for the connection on the Ethernet communication module
Type: the connection type (EtherNet/IP or Modbus TCP)
Mess. Sent: the number of messages transmitted over this connection
Mess. Received: the number of messages received by this connection
Error Sent: the number of events detected on this connection
NOTE:
Following a request to close a connection, the PLC may hold the connection open in its memory
for a few minutes, during which the display will reflect the open connection.
The Number of Messages received is not reset after a port 502 connection is closed. Therefore, the count indicates the total number of messages that have been received since the module was started.
S1A48993 10/2019
373
Embedded Web Pages
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → Messaging.
If necessary, type the HTTP web access password.
NOTE: The default password is USER.
374
S1A48993 10/2019
Embedded Web Pages
Ethernet Statistics
Introduction
The Ethernet Statistics page provides information about the status, transmit and receive statistics, and detected errors for the web server embedded in the 140NOC78•00 head module.
Ethernet Statistics Display
The Ethernet Statistics page looks like this:
Click the Reset counters button to reset the counting statistics to zero.
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → Ethernet Statistics.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
375
Embedded Web Pages
Ethernet Statistics
The Ethernet Statistics page displays the following data for the Ethernet communication module.
Ethernet configuration data:
Hostname
MAC Address
IP Address
Subnet Mask
Gateway Address
The name assigned to the communication module
The factory assigned Media Access Control (MAC) address, consisting of 6 hexidecimal octet values
The Internet Protocol (IP) address (see Quantum using EcoStruxure™ Control
Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) that has been assigned to the communication module
The subnet mask (see Quantum using EcoStruxure™ Control Expert,
140 NOC 771 01 Ethernet Communication Module, User Manual) that has been assigned to the communication module
The IP address of the remote device (see Quantum using EcoStruxure™ Control
Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) , if any, that serves as a gateway to the communication module
Port Statistics:
Speed (Operational) Baud rate: 0, 10 or 100 Mbits/second
Duplex (Operational) Twisted Pair—Full Duplex Link, or Twisted Pair—Half Duplex Link
Frames transmit OK The number of frames that have been successfully transmitted
Frames received OK The number of frames that have been successfully received
Collisions The number of times a collision between two successfully transmitted packets was detected on the link
Excessive collisions The number of times the transmitter has not succeeded after 16 attempts to transmit a frame, due to repeated collisions
Late collisions The number of times a collision was detected after the slot time of the channel had elapsed
CRC errors
Number Bytes
Received
The number of times a CRC (FCS) error was detected on an incoming frame
The number of inbound bytes received on the interface
Number Inbound
Packets Error
Number Inbound
Packets Discard
The number of inbound packets that contain detected errors (not included in discards)
The number of inbound packets received on the interface, but discarded
Number Bytes Sent The number of outbound bytes transmitted on the interface
Number Outbound
Packets Error
Number Outbound
Packets Discard
The number of outbound packets that contain detected errors (not included in discards)
The number of outbound packets discarded while attempting to send them
376
S1A48993 10/2019
Embedded Web Pages
QoS Configuration
Introduction
The 140NOC78•00 head module supports the OSI layer 3 Quality of Service (QoS) standard defined in RFC-2475. When the QoS is enabled, the module adds a differentiated services code point (DSCP) tag to each Ethernet packet it transmits, thereby indicating the priority of that packet.
The QoS Configuration page displays the following:
status of the QoS Ethernet packet tagging service, enabled or disabled
the QoS service configuration settings
NOTE: The QoS service is enabled in the Services page (see Quantum using EcoStruxure™
Control Expert, 140 NOC 771 01 Ethernet Communication Module, User Manual) , and the configuration settings are input in the QoS page
Configuration Tool.
see page 138
, of the Control Expert Ethernet
QoS Configuration Display
The QoS Configuration page looks like this:
This page is read-only.
S1A48993 10/2019
377
Embedded Web Pages
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → QoS Configuration.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
378
S1A48993 10/2019
Embedded Web Pages
Redundancy
Introduction
Use the Redundancy page to enable and disable the Rapid Spanning Tree Protocol (RSTP) for switch ports 3 and 4.
NOTE: Because only switch ports 3 and 4 support RSTP redundancy, use ports 3 and 4 to connect the 140NOC78•00 head module to the network, and ports 1 and 2 for connections to local devices.
The RSTP service creates a loop-free logical network path for Ethernet devices that are part of a topology that includes redundant physical paths, and automatically restores network communication by activating redundant links in the event the network experiences a service interruption.
Redundancy Display
The Redundancy page looks like this:
To open this page:
Step
1
2
3
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → Switch →
Redundancy.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
379
Embedded Web Pages
Email Diagnostics
Diagnosing SMTP Transmissions
Use the SMTP Diagnostics web page to display dynamically generated data describing the
140NOC78•00 head module Email transmissions.
NOTE: The Email service is enabled in the Services page, and the configuration settings are input in the SMTP Configuration page of the module DTM.
The SMTP Diagnostics web page looks like this:
380
Click the Reset Counter button to reset the Email Service Statistics to 0.
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → SMTP Diagnostics.
If necessary, type the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
Embedded Web Pages
Email Diagnostic Parameters
Electronic mail notification service parameters include the following:
Parameter
Email Service:
Status
Description
The status of this service in the Ethernet communication module:
Operational
Service Disabled
Email Server:
Status
NOTE: Status is checked at start-up and at least every 30 minutes after start-up.
IP Address IP address of the SMTP server
Information of Last Email Header Used:
Sender Address: Content of the From field in the last used Email header
Recipient Address:
Subject:
Content of the To field in the last used Email header
Content of the Subject field in the last used Email header
Email Service Statistics:
Number of Emails Sent
Number of Responses from
Email Server
Number of Errors
Total number of Emails sent and successfully acknowledged by the SMTP server.
Total number of responses received from the SMTP server
Total number of Emails that either:
could not be sent
were sent but were not successfully acknowledged by the SMTP server
Last Error
The connection status between Ethernet communication module and the
SMTP server:
check mark = connected no check mark = not connected
Hexadecimal code describing the reason for the last unsuccessful Email transmission (see Modicon M340, BMX NOC 0401
Ethernet Communication Module, User Manual) . The value “0” indicates no unsuccessful transmissions.
Counts the number of seconds since the last Email was successfully sent.
Time elapses since last Email successfully sent (sec)
Number of times link to the server down
Number of times the SMTP server could not be reached. (Link checked every 30 minutes.)
S1A48993 10/2019
381
Embedded Web Pages
Network Time Service Diagnostics
Diagnosing the Network Time Service
Use the Network Time Service Diagnostic web page to display dynamically generated data describing the operation of the network time protocol (NTP) service that you configured in the
Network Time Service page (see Modicon M340, BMX NOC 0401
Ethernet Communication Module, User Manual) in Control Expert.
NOTE: The Network Time Service is enabled in the Services page, and the configuration settings are input in the Network Time Service Configuration page of the module DTM.
The NTP Diagnostics web page looks like t his:
382
Click the Reset Counter button to reset the Network Time Service Statistics to 0.
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Ethernet → NTP Diagnostics.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
Embedded Web Pages
Network Time Service Diagnostic Parameters
Time synchronization service parameters are in the table:
Parameter
Network Time Service:
Status
Description
Operational status of the service in the module:
Operational
Service Disabled
Date and Time Status:
Date:
Time:
DST Status
System date
System time
NOTE: Red text indicates the network time server is not available.
The actual working status of the automatic daylight savings service:
ON = automatic adjustment of daylight savings is enabled and the current date
and time reflect the daylight savings time adjustment
OFF = automatic adjustment of daylight savings is disabled; or automatic adjustment of daylight savings is enabled, but the current date and time may not reflect the daylight savings time adjustment
Time zone plus or minus Universal Time, Coordinated (UTC) Time Zone
NTP Server:
Status
IP Address
Type
Connection status of the NTP server:
check mark = the NTP server is reachable
no check mark = the NTP server is not reachable
The IP address of the NTP server
The NTP server currently active:
Primary
Secondary
Network Time Service Statistics:
Number of Requests: Total number of client requests sent to the NTP server
Number of Responses: Total number of server responses sent from the NTP server
Number of Errors: Total number of unanswered NTP requests
S1A48993 10/2019
383
Embedded Web Pages
Parameter
Last Error
Description
Last detected error code received from the NTP client:
0: good NTP configuration
1: late NTP server response (can be caused by excessive network traffic or server overload)
2: NTP not configured
3: invalid NTP parameter setting
4: NTP component disabled
5: NTP server is not synchronized (NTP server needs to be synchronized so that the NTP accesses behave as defined in the client NTP settings)
7: unrecoverable NTP transmission
9: invalid NTP server IP address
15: invalid syntax in the custom time zone rules file
384
S1A48993 10/2019
Embedded Web Pages
Properties
Introduction
The Properties web page displays read-only data describing the particular 140NOC78•00 head module installed in your system.
Properties Display
The Properties page looks like this:
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Properties.
If necessary, type in the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
385
Embedded Web Pages
Router Status
Introduction
Use the Router Status page to diagnose communication between devices on separate networks that are connected via the 140NOC78100 module’s IP forwarding service.
386
The display grid provides the following information about each active connection:
Forwarding status: enabled or disabled (forwarding/discarding) based on status of IP forwarding
service
Current forward load: the total load in pps (packets per second) of IP forwarding service
Route: the destination network
Network mask: the CIDR scope of route
IP gateway: the gateway IP address
IP address: the interface on destination network
Cost: the cost of route (metric)
To open this page:
2
3
Step
1
Action
Starting at the Home page, click the Diagnostics main menu item.
Result: The Diagnostics page opens.
On the left side of the Diagnostics page, select Router Status.
If necessary, type the HTTP web access password.
NOTE: The default password is USER.
S1A48993 10/2019
Quantum EIO
S1A48993 10/2019
Appendices
S1A48993 10/2019
387
388
S1A48993 10/2019
Quantum EIO
Detected Error Codes
S1A48993 10/2019
Detected Error Codes Appendix A
Detected Error Codes
Overview
This chapter contains a list of codes that describe the status of Ethernet communication module messages.
What Is in This Chapter?
This chapter contains the following topics:
Topic
TCP/IP Ethernet Detected Error Codes
Modbus TCP Explicit Messaging Detected Error Codes
EtherNet/IP Implicit or Explicit Messaging Detected Error Codes
Electronic Mail Notification Service Detected Error Response Codes
Page
S1A48993 10/2019
389
Detected Error Codes
TCP/IP Ethernet Detected Error Codes
TCP/IP Ethernet Detected Error Codes
An event in an MBP_MSTR routine via TCP/IP Ethernet may produce one of the following codes in the MBP_MSTR control block.
TCP/IP Ethernet Hexadecimal Detected Error Codes
TCP/IP Ethernet hexadecimal detected error codes include:
Code (hexadecimal)
16#1001
16#2001
16#2002
16#2003
16#2004
16#2005
16#2006
16#2007
16#2008
16#200E
16#200F
16#3000
16#3001
16#3002
16#3003
16#3005
16#3006
16#3007
16#4001
16#F001
16#F002
Meaning
Abort by user
An operation type that is not supported has been specified in the control block
One or more control block parameters were modified while the MSTR element was active (this only applies to operations which require several cycles for completion).
Control block parameters my only be modified in inactive MSTR components.
Invalid value in the length field of the control block
Invalid value in the offset field of the control block
Invalid value in the length and offset fields of the control block
Unauthorized data field on slave
Invalid slot number in the configuration routing register
Example: 253 for 140 CRP 312 00 slot number
Unauthorized network routing path on slave
The control block is not assigned, or parts of the control block are located outside of the %MW (4x) range.
The space allocated for the CIP response is too small.
Generic Modbus exception response
Slave does not support requested operation
Non-existing slave registers were requested
An unauthorized data value was requested
Slave has accepted a lengthy program command
Function cannot currently be carried out: lengthy command running
Slave has rejected lengthy program command
Inconsistent response by Modbus slave
Module is resetting
Component not fully initialized
390
S1A48993 10/2019
Detected Error Codes
Modbus TCP Explicit Messaging Detected Error Codes
Modbus TCP Detected Error Codes
An event in an MBP_MSTR routine via Modbus TCP may produce one of the following detected error codes in the MBP_MSTR control block.
Modbus TCP Hexadecimal Detected Error Codes
Modbus TCP hexadecimal detected error codes include:
Code (hexadecimal)
16#5101
16#5102
16#5103
16#5104
16#5105
16#5106
16#5107
16#5108
16#5109
16#5301
16#510A
16#510B
Meaning
No resources
Bad IP address
Transaction timed out
Concurrent connections or transactions limit reached
Remote address not allowed
No route to host
Remote host is down
Connection reset by peer
Network is down
No resources available
— or —
Module not ready or initializing
Connection refused
Connection timed out
S1A48993 10/2019
391
Detected Error Codes
EtherNet/IP Implicit or Explicit Messaging Detected Error Codes
Introduction
If an MBP_MSTR function block does not execute an EtherNet/IP explicit message, Control Expert displays a hexadecimal detected error code. This code can describe:
an EtherNet/IP event a TCP/IP Ethernet event
Refer to the topic TCP/IP Ethernet detected error codes
codes.
see page 390
EtherNet/IP Detected Error Codes
EtherNet/IP hexadecimal detected error codes include:
Code
16#800D
16#8015
16#8018
Description
Timeout on the explicit message request
Either:
Nor resources to handle the message, or
Internal event: no buffer available, no link available, impossible to send to the TCP task
Either:
Another explicit message for this device is in progress, or
TCP connection or encapsulation session in progress
16#8030 Timeout on the Forward_Open request
Note: The following 16#81xx events are Forward_Open response detected error codes that originate at the remote target and are received via the CIP connection.
16#8100
16#8103
16#8106
16#8107
Connection in use or duplicate Forward_Open
Transport class and trigger combination not supported
Ownership conflict
Target connection not found
16#8108
16#8109
16#8110
16#8111
16#8113
16#8114
16#8115
16#8116
16#8117
16#8118
Invalid network connection parameter
Invalid connection size
Target for connection not configured
RPI not supported
Out of connections
Vendor ID or product code mismatch
Product type mismatch
Revision mismatch
Invalid produced or consumed application path
Invalid or inconsistent configuration application path
392
S1A48993 10/2019
Code
16#8119
16#811A
16#811B
16#8123
16#8124
16#8125
16#8126
16#8127
16#8131
16#8132
16#8133
16#8134
16#8135
16#8136
16#8141
16#8142
16#8145
16#8146
16#8147
16#8148
16#8149
16#814A
16#814B
16#814C
16#814D
16#814E
16#814F
16#8160
16#8170
16#8171
16#8173
16#81A0
16#81B0
S1A48993 10/2019
Detected Error Codes
Description
Non-Listen Only connection not opened
Target object out of connections
RPI is smaller than the production inhibit time
Connection timed out
Unconnected request timed out
Parameter event in unconnected request and service
Message too large for unconnected_send service
Unconnected acknowledge without reply
No buffer memory available
Network bandwidth not available for data
No consumed connection ID filter available
Not configured to send scheduled priority data
Schedule signature mismatch
Schedule signature validation not possible
Port not available
Link address not valid
Invalid segment in connection path
Event in Forward_Close service connection path
Scheduling not specified
Link address to self invalid
Secondary resources unavailable
Rack connection already established
Module connection already established
Miscellaneous
Redundant connection mismatch
No more user-configurable link consumer resources: the configured number of resources for a producing application has reached the limit
No more user-configurable link consumer resources: there are no consumers configured for a producing application to use
Vendor specific
No target application data available
No originator application data available
Not configured for off-subnet multicast
Event in data assignment
Optional object state event
393
Detected Error Codes
Code Description
16#81C0 Optional device state event
Note: All 16#82xx events are register session response detected error codes.
16#8200
16#8208
16#820F
Target device does not have sufficient resources
Target device does not recognize message encapsulation header
Reserved or unknown event from target
394
S1A48993 10/2019
Detected Error Codes
Electronic Mail Notification Service Detected Error Response Codes
SMTP Codes
The following codes are available only on the Control Expert DTM and web page diagnostic screens for the electronic mail notification service:
Code (hexadecimal)
16#5100
16#5101
16#5102
16#5103
16#5104
16#5105
16#5106
16#5107
16#5108
16#5109
16#510A
16#510B
16#510C
16#510D
16#510E
Description
Internal error detected
SMTP component not operational
Mail header not configured
Invalid mail header value detected (1, 2, or 3)
Cannot connect to SMTP server
Error detected during transmitting content of email body to SMTP server
Closing SMTP connection with the server returned a detected error message
SMTP HELO request unsuccessful
SMTP MAIL request unsuccessful — SMTP server may require authentication
SMTP RCPT request unsuccessful
No recipient accepted by the SMTP server
SMTP DATA request unsuccessful
Send email request contains an invalid length
Authentication unsuccessful
A reset component request was received while the connection was open
S1A48993 10/2019
395
Detected Error Codes
396
S1A48993 10/2019
Quantum EIO
Glossary
S1A48993 10/2019
Glossary
A
adapter
The target of real-time I/O data connection requests from scanners. It cannot send or receive realtime I/O data unless it is configured to do so by a scanner, and it does not store or originate the data communications parameters necessary to establish the connection. An adapter accepts explicit message requests (connected and unconnected) from other devices.
advanced mode
A selection in Control Expert that displays expert-level configuration properties that help define
Ethernet connections. To maintain system performance, confirm that advanced mode properties are configured only by persons with a solid understanding of communication protocols.
ARP
( address resolution protocol ) A request and reply protocol used for resolution of network layer addresses into link layer addresses, a function in multiple-access networks.
C
CIP™
( common industrial protocol ) A comprehensive suite of messages and services for the collection of manufacturing automation applications (control, safety, synchronization, motion, configuration and information). CIP allows users to integrate these manufacturing applications with enterpriselevel Ethernet networks and the internet. CIP is the core protocol of EtherNet/IP.
control network
An Ethernet-based network containing PLCs, SCADA systems, an NTP server, PCs, AMS, switches, etc. Two kinds of topologies are supported:
flat — Devices in this network belong to the same subnet.
2 levels — The network is split into an operation network and an inter-controller network. These
2 networks can be physically independent, but are generally linked by a routing device.
D
DDT
( derived data type ) A set of elements with the same type ( array ) or with different types (structure).
determinism
For a defined application and architecture, the ability to predict that the delay between an event
(change of an input value) and the corresponding change of an output state is a finite time than the time required for your process to run correctly.
t , smaller
S1A48993 10/2019
397
Glossary device network
An Ethernet-based network within a remote I/O network that contains both remote I/O and distributed I/O devices. Devices connected on this network follow specific rules to allow remote I/O determinism.
DHCP
( dynamic host configuration protocol ) An extension of the BOOTP communications protocol that provides for the automatic assignment of IP addressing settings (ncluding IP address, subnet mask, gateway IP address, and DNS server names). DHCP does not require the maintenance of a table identifying each network device. The client identifies itself to the DHCP server using either its MAC address, or a uniquely assigned device identifier. The DHCP service utilizes UDP ports 67 and 68.
distributed I/O cloud
A group of distributed I/O devices connected either to a non-ring port on a DRS or to a distributed
I/O communications module in the local rack. Distributed I/O clouds are single-point connections to the Ethernet I/O network and are not required to support RSTP.
distributed I/O device
Any Ethernet device (Schneider Electric device, PC, servers, or third-party devices) that supports
I/O exchange with a PLC or other Ethernet communication service.
DRS
( dual-ring switch ) A ConneXium extended managed switch with one of several possible predefined configurations downloaded to it so that it can participate in an Ethernet I/O network. A DRS provides 2 RSTP-enabled ring connections, one for the main ring and one for a sub-ring. It also manages QoS, which provides a predictable level of performance for both remote I/O and distributed I/O traffic on the same I/O network.
DRSs require a firmware version 6.0 or later.
DTM
( device type manager ) A device driver running on the host PC. It provides a unified structure for accessing device parameters, configuring and operating the devices, and troubleshooting the network. DTMs can range from a simple graphical user interface (GUI) for setting device parameters to a highly sophisticated application capable of performing complex real-time calculations for diagnosis and maintenance purposes. In the context of a DTM, a device can be a communications module or a remote device on the network.
See FDT .
E
EDS
( electronic data sheet ) Simple text files that describe the configuration capabilities of a device. EDS files are generated and maintained by the manufacturer of the device.
398
S1A48993 10/2019
Glossary
EtherNet/IP™
A network communication protocol for industrial automation applications that combines the standard internet transmission protocols of TCP/IP and UDP with the application layer common industrial protocol (CIP) to support both high speed data exchange and industrial control.
EtherNet/IP employs electronic data sheets (EDS) to classify each network device and its functionality.
explicit messaging
TCP/IP-based messaging for Modbus TCP and EtherNet/IP. It is used for point-to-point, client/server messages that include both data (typically unscheduled information between a client and a server) and routing information. In EtherNet/IP, explicit messaging is considered class 3 type messaging, and can be connection-based or connectionless.
extended distributed I/O network
An Ethernet-based network containing distributed I/O devices located on an existing distributed I/O network that participate in an Ethernet remote I/O network through use of an control network head module.
extended port on a
F
FDR
( fast device replacement ) A service that uses configuration software to replace a device.
FDT
( field device tool system host.
) The technology that harmonizes communication between field devices and the
H
HMI
( human machine interface ) An HMI is a device that displays process data to a human operator, who in turn uses the HMI to control the process.
An HMI is typically connected to a SCADA system to provide diagnostics and management data, such as scheduled maintenance procedures and detailed schematics for a particular machine or sensor.
Hot Standby
A high-availability control system with a second (standby) PLC that maintains up-to-date system status. If the primary PLC becomes inoperable, the standby PLC takes control of the system.
S1A48993 10/2019
399
Glossary
I
implicit messaging
UDP/IP-based class 1 connected messaging for EtherNet/IP. Implicit messaging maintains an open connection for the scheduled transfer of control data between a producer and consumer.
Because an open connection is maintained, each message contains primarily data, without the overhead of object information, and a connection identifier.
independent distributed I/O network
An Ethernet-based network containing distributed I/O devices located on an existing distributed I/O network that participate in the control network only of an Ethernet remote I/O network.
interlink port
An Ethernet port on Ethernet remote I/O head modules allowing direct connection of distributed I/O modules to the remote I/O network and transparency between a control network and the Ethernet remote I/O network.
isolated distributed I/O network
An Ethernet-based network containing distributed I/O devices that do not participate in an Ethernet remote I/O network.
L
local rack
A Quantum rack containing the controller, a power supply, and an Ethernet remote I/O head module. A local rack consists of 1 or 2 racks, the main rack (containing the remote I/O head module) and an optional extended rack. A Quantum Ethernet remote I/O network requires 1 local rack on the main ring.
M
MAST
A master processor task that is run through its programming software. The MAST task has 2 sections:
IN: Inputs are copied to the IN section before execution of the MAST task.
OUT: Outputs are copied to the OUT section after execution of the MAST task.
N
NTP
( network time protocol ) Protocol for synchronizing computer system clocks. The protocol uses a jitter buffer to resist the effects of variable latency.
400
S1A48993 10/2019
Glossary
P
PLC programmable logic controller . The PLC is the brain of an industrial manufacturing process. It automates a process as opposed to relay control systems. PLCs are computers suited to survive the harsh conditions of the industrial environment.
Q
Quantum Ethernet I/O device
These devices in Ethernet I/O systems provide automatic network recovery and deterministic remote I/O performance. The time it takes to resolve a remote I/O logic scan can be calculated, and the system can recover quickly from a communication disruption. Quantum Ethernet I/O devices include:
local rack (with an Ethernet remote I/O head module)
remote I/O drop (with an Ethernet adapter module)
DRS (with a pre-defined configuration downloaded)
R
remote I/O drop
One of the 3 types of remote I/O devices in an Ethernet remote I/O network. A remote I/O drop is a Quantum or an X80 rack of I/O modules that are connected to an Ethernet remote I/O network and managed by an Ethernet remote adapter module. A drop can be a single rack or a rack with an extension rack.
remote I/O network
An Ethernet-based network that contains 1 standalone PLC or one Hot Standby system and remote I/O devices. There are 3 types of remote I/O devices: a local rack, a remote I/O drop, and a ConneXium extended dual-ring switch (DRS). Distributed I/O devices may also participate in a remote I/O network via connection to DRSs.
RPI
(requested packet interval) The time period between cyclic data transmissions requested by the scanner. EtherNet/IP devices publish data at the rate specified by the RPI assigned to them by the scanner, and they receive message requests from the scanner at each RPI.
RSTP
( rapid spanning tree protocol ) A protocol that allows a network design to include spare (redundant) links to provide automatic backup paths if an active link stops working, without the need for loops or manual enabling/disabling of backup links.
S1A48993 10/2019
401
Glossary
S
SCADA
( supervisory control and data acquisition ) SCADA systems are computer systems that control and monitor industrial, infrastructure, or facility-based processes (examples: transmitting electricity, transporting gas and oil in pipelines, and water distribution).
service port
A dedicated Ethernet port on the Quantum Ethernet remote I/O modules. The port may support 3 major functions (depending on the module type):
port mirroring — for diagnostic use
access — for connecting HMI/Control Expert/ConneXium Network Manager to the PLC extended — to extend the device network to another subnet disabled — disables the port, no traffic is forwarded in this mode
SMTP
( simple mail transfer protocol ) An email notification service that allows controller-based projects to report alarms or events. The controller monitors the system and can automatically create an email message alert with data, alarms, and/or events. Mail recipients can be either local or remote.
SNMP
( simple network management protocol ) Protocol used in network management systems to monitor network-attached devices for events. The protocol is part of the internet protocol suite (IP) as defined by the internet engineering task force (IETF), which consists of network management guidelines, including an application layer protocol, a database schema, and a set of data objects.
sub-ring
An Ethernet-based network with a loop attached to the main ring, via a DRS. A sub-ring may contain either remote I/O or distributed I/O devices.
T
TCP/IP
Also known as internet protocol suite , TCP/IP is a collection of protocols used to conduct transactions on a network. The suite takes its name from 2 commonly used protocols: transmission control protocol and internet protocol. TCP/IP is a connection-oriented protocol that is used by
Modbus TCP and EtherNet/IP for explicit messaging.
402
S1A48993 10/2019
Glossary
U
UDP
( user datagram protocol ) A transport layer protocol that supports connectionless communications.
Applications running on networked nodes can use UDP to send datagrams to one another. UDP does not always deliver datagrams as reliable or ordered as those delivered by TCP. However, by avoiding the overhead required for TCP, UDP is faster. UDP may be the preferred protocol for timesensitive applications, where dropped datagrams are preferable to delayed datagrams. UDP is the primary transport for implicit messaging in EtherNet/IP.
S1A48993 10/2019
403
Glossary
404
S1A48993 10/2019
Quantum EIO
Index
S1A48993 10/2019
Index
0-9
140 CRA 312 00 grounding, installation, grounding, installation, grounding, installation,
specifications,
140 CRP 312 00
specifications,
140 NOC 78• 00
firmware upgrade,
140 NOC 780 00 device editor,
DTM browser,
specifications,
140 NOC 781 00 grounding, installation,
specifications,
140 NOP 850 00
140CRA31908 installation,
A
address
advanced mode
DTM browser, assembly object,
S1A48993 10/2019
B
BME NOC 03•1
BMENOP0300
BMX CRA 312 •• installation,
installation,
BMX CRA 312 •0
BMX CRA 312 00
BMX CRA 312 10
BMX NOC 0401
C
cabling
channel properties,
chassis,
CIP objects,
clear local statistics,
control bits,
configuring
connection add,
settings, connection manager object, connection timeout
405
Index
Control Expert
downloading DTM-based application,
logging,
uploading DTM-based application, control network head module description, interlink for device network,
interlink for Ethernet remote I/O,
interlink for extended distributed I/O net work, interlink for independent distributed I/O
non-redundant (single attachment),
redundant (dual homing),
D
data editor creating a data template, direct address,
modify data, displaying a data template,
derived variables, detected error codes
Modbus TCP,
saving a data template, data editor (standard), data template
EtherNet/IP,
TCP/IP, device
I/O request settings,
IP address, properties,
DTM browser, device network control network interconnectivity,
406
add,
,
,
scanner status,
system,
bandwidth, connection,
Ethernet statistics,
Modbus codes, processor load,
redundancy,
diagnostics web page, downloading
DTM-based application,
DTM
uploading application,
configuring properties in device editor,
device editor,
dual attachment control network,
E
EDS file add,
diagnostics,
,
S1A48993 10/2019
Ethernet connection speed,
Ethernet link object,
Ethernet remote I/O cabling, diagnostics, object,
Ethernet remote I/O network control network interconnectivity,
EtherNet/IP
EtherNet/IP detected error codes,
EtherNet/IP explicit connection diagnostics
,
EtherNet/IP interface diagnostics object,
EtherNet/IP IO Scanner Diagnostics object,
EtherNet/IP settings, explicit message
EtherNet/IP,
EtherNet/IP,
Modbus TCP, explicit messaging
EtherNet/IP services,
Get_Attributes_Single,
Modbus TCP,
Modbus TCP function codes, 241
explicit messaging detected error codes,
extended distributed I/O network control network interconnectivity,
F
FDR,
field bus discovery, firmware upgrade
140 NOC 78x 00,
FTP/TFTP services enable/disable, function code 3 diagnostics,
S1A48993 10/2019
G
get remote statistics, grounding,
H
hardware catalog updating,
home web page,
Hot Standby
140NOC78• switchover,
140NOC78• synchronization,
HTTP services
I
I/O
independent distributed I/O network control network interconnectivity, inputs
IO connection diagnostics object,
IP address swap time
IP forwarding service
control network, control network,
IP forwarding topology
L
local slave,
configuring,
Index
407
Index logging
M
MAST cycle time
HSBY switchover (140NOC78•),
,
,
MBP_MSTR detected error codes,
menu commands
DTM browser,
Modbus diagnostic codes,
Modbus TCP detected error codes, monitoring web page,
N
network transparency control network,
non-redundant control network,
NTP diagnostics,
O
online action display CIP object data,
EtherNet/IP object, get port configuration, ping,
set port configuration,
online parameters, outputs
,
P
password data editor write,
408 ping,
Q
,
QoS object,
R
rack size
redundancy, redundant control network, remote device,
connection,
DTM file name, identity check,
remove connection, replacing,
RPI,
RPI (recommended)
RSTP,
RSTP diagnostics object,
S
scanner status, services
single attachment control network,
S1A48993 10/2019
specifications
140 CRA 312 00,
140 CRP 312 00,
BMX CRA 312 00, communication, status summary,
summary
swap time
synchronization in HSBY
T
T_Q_NOC78100_IN control network,
T_Q_NOC78100_OUT control network,
timeout multiplier control network,
TCP/IP detected error codes,
transparency
U
user interface, username,
V
variables
S1A48993 10/2019
W
web pages data editor (standard),
home,
monitoring, password,
redundancy,
scanner status,
Index
409
Index
410
S1A48993 10/2019