Omron NT31 Series Setup Manual
PDF
Document
Advertisement
Advertisement
Cat. No. V062-E1-03 NT31 and NT31C Programmable Terminals SETUP MANUAL NT31and NT31C Programmable Terminals Setup Manual Revised June 2004 iv Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property. DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage. ! OMRON Product References All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product. The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense. Visual Aids The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc. OMRON, 2000 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication. v vi TABLE OF CONTENTS PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-2 1-3 1-4 1-5 1-6 Role and Operation of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Functions of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications with the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications Using Memory Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Before Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 2 Preparing for Connection . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2-2 Method for Connection to the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Names and Functions of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 3 Hardware Settings and Connections . . . . . . . . . . . . . . . . 3-1 3-2 3-3 3-4 3-5 3-6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting to the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting a Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting a Bar Code Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using a Memory Unit (-V Versions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using a Memory Unit (Versions without the -V Suffix) . . . . . . . . . . . . . . . . . . . . . . . . SECTION 4 Connecting to the Host from the RS-232C Port . . . . . . . 4-1 Connecting to the RS-232C Port at the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 5 Connecting to the Host from the RS-422A/485 Port . . . . 5-1 5-2 Connecting to the Host’s RS-232C Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting to the Host’s RS-422A/485 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 6 System Menu Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10 6-11 6-12 6-13 6-14 System Menu Operation Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starting the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation Modes and the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Memory Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operations in the System Installer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transmitting the Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Conditions for Communications with Host by Using Memory Switches . . . . . . . Starting Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Bar Code Reader Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Console Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Device Monitor Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Version Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi xii xii xii 1 2 4 15 16 19 21 23 24 27 29 30 33 34 35 37 45 51 52 83 84 98 129 131 132 133 138 148 153 155 166 166 186 189 219 225 228 vii TABLE OF CONTENTS SECTION 7 Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . 7-1 7-2 7-3 7-4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Responding to Displayed Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229 230 233 239 243 Appendices A B C D E F G H I J K Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using an RS-232C/RS-422A Convertor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transporting and Storing the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Making the Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Making the Cable for Connecting a PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Making the Cable for Connection to a Bar Code Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . Making the Cable for Connection to a Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relationship between System Program and Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Option List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii 247 255 259 265 267 269 271 273 275 279 285 289 293 About this Manual: This manual describes connecting the NT-series NT31 and NT31C Programmable Terminals to a PLC (Programmable Controller) or other host and peripheral devices and the settings required for communications and applications. It includes the sections described below. Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the Programmable Terminal. Section 1 provides fundamental information about the functions and features of the PTs, types of connection, communication methods, etc. This information will enable you to understand the applications of the PTs. Section 2 describes the connection methods that are possible with the PTs, and the functions of the parts of PTs, as the required knowledge before connecting to the host and to the peripheral devices. Section 3 describes the settings of the PTs and methods for connection to peripheral devices. Section 4 describes the method for connecting to the host using the RS-232C port of the PT. Section 5 describes the method for connecting to the host using the RS-422A/485 port of the PT. Section 6 describes the operation of the System Menu, focusing on the procedure to start the PT. Functions that are convenient when using the PT and those that are useful for system maintenance are also explained here. Section 7 describes the action to take when errors occur in the PT, and how to carry out maintenance and inspection to prevent the occurrence of errors. The Appendices provide specifications, dimensions, procedures for using an RS-232C/RS-422A Convertor Unit, procedures for transporting and storing the PT, information on cable preparation, information on the relationship between the system program and hardware, and product lists. ! WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given. ix Related Manuals: Related manuals are listed below. The symbol at the end of the catalog number is the revision number. Connecting and Setting Up the Programmable Terminal NT31 and NT31C PT Setup Manual (V062-E1-, this manual) This manual describes connecting the Programmable Terminals to a host and peripheral devices and settings required for communications and applications. The functions and actual operating methods for the NT31 and NT31C PTs are provided in the Reference Manual (V064-E1-). Programmable Terminal Functions and Operation NT31/31C/631/631C PT Reference Manual (V064-E1-) This manual is used for any of the following PTs: NT31, NT31C, NT631, and NT631C. It describes screen configurations, part functions, host control methods, and other application information. PT connection and setup procedures are described in the NT31 and NT31C PT Setup Manual (V062-E1-). Creating and Transferring Screen Data, and Installing the System Program NT-series Support Tool for Windows Ver. 4.1 Operation Manual (V061-E1-) The screens displayed on the NT31 and NT31C PTs are created with the Support Tool and transferred to the PT. This manual describes how to create and transfer screen data. It also describes how to download a system program to a PT using the System Installer. The NT-series Support Tool for Windows is normally referred to as merely the Support Tool. Connecting to Controllers Not Made by OMRON PLC Connection Manual (V042-E1-) The NT31 and NT31C PTs can be connected to controllers in the following series: Mitsubishi A Series and FX Series. This manual describes the connection and setup methods for these controllers. The NT-series Support Tool for Windows Version 4.1 is required to connect the NT31 and NT31C PTs to these controllers. NT31/NT631 Multi Vendor Connection Manual (V060-E1-) The NT31 and NT31C PTs can be connected to controllers in the following series: Allen-Bradley SLC 500 Series, GE Fanuc 90-20 and 90-30 Series, and Siemens S7-300 and S7-400 Series. This manual describes the connection and setup methods for these controllers. x PRECAUTIONS This section provides general precautions for using the Programmable Terminal. The information contained in this section is important for the safe and reliable application of the Programmable Terminal. You must read this section and understand the information contained before attempting to set up or operate a Programmable Terminal. 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xi 3 Safety Precautions 1 Intended Audience This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent). • Personnel in charge of introducing FA systems into production facilities. • Personnel in charge of designing FA systems. • Personnel in charge of installing and connecting FA systems. • Personnel in charge of managing FA systems and facilities. 2 General Precautions The user must operate the product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative. Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms. This manual provides information for using the Programmable Terminal. Be sure to read this manual before attempting to use the software and keep this manual close at hand for reference during operation. ! WARNING It is extremely important that Programmable Terminals and related devices be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying Programmable Terminals to the above-mentioned applications. ! WARNING Do not use input functions such as PT touch switches for applications where danger to human life or serious damage is possible, or for emergency switch applications. 3 Safety Precautions Read these safety precautions carefully and make sure you understand them before using the Programmable Terminal so that you can use it safely and correctly. Safety Conventions andtheir Meanings This operation manual uses the following conventions and symbols to indicate cautions, warnings, and dangers in order to ensure safe use of the NT31/31C. The cautions, warnings, and dangers shown here contain important information related to safety. The instructions in these cautions, warnings, and dangers must be observed. ! WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage. xii 3 Safety Precautions WARNING Do not attempt to take the unit apart and do not touch any internal parts while the power is being supplied. Doing either of these may result in electrical shock. WARNING Switch OFF the NT31/NT31C power before replacing the backlight. Otherwise you could sustain an electric shock. CAUTION Do not touch the backlight immediately after switching OFF the power supply. Otherwise burn injuries may result due to the high temperatures. xiii SECTION 1 General This section provides fundamental information about the functions and features of the PTs, types of connection, communication methods, etc. This information will enable you to understand the applications of the PTs. 1-1 1-2 1-3 1-4 1-5 1-6 Role and Operation of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-1 Operation of an NT31/NT31C at an FA Production Site . . . . . . . . . . . . . . . . . . . . 1-1-2 Operations of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Functions of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-2 Comparison between NT31 and NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-3 Additional Functions of the V2 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-4 Comparison between NT30/NT30C and NT31/NT31C . . . . . . . . . . . . . . . . . . . . 1-2-5 Principal Functions of NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-6 Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-1 Peripheral Devices That Can Be Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-2 Connecting to the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications with the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-1 Direct Connection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-2 Host Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-3 NT Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-4 Connecting to other Companies’ PLCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications Using Memory Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5-1 Memory Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5-2 Comparison between Direct Connection and Memory Link . . . . . . . . . . . . . . . . . 1-5-3 Memory Link Online Transfer Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Before Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 3 4 4 5 5 6 8 10 15 15 16 16 16 17 17 19 19 19 20 20 21 1 Section Role and Operation of the NT31/NT31C 1-1 1-1 Role and Operation of the NT31/NT31C The NT31/NT31C is a sophisticated display unit (programmable terminal) which automatically displays information and can also be used for operations when necessary. The following gives a general description of the role and operation of the NT31/NT31C for those using a programmable terminal (PT) for the first time. 1-1-1 Operation of an NT31/NT31C at an FA Production Site Production Line Status Monitoring The NT31/NT31C displays real-time information about the system and equipment operating status, etc. Its power of expression is enhanced by graphs and other visuals, making the displays easy to understand. Production Control (3) Product Today’s target Current production Number defective Number repaired 560 305 2 7 441 275 8 15 % achieved Directions to Workers on the Shop Floor The NT31/NT31C warns of system or equipment failures and prompts the appropriate remedial action. Alarm Assembly line B Positioning pin is defective. Line stopped. Check the following. 1. Defective pin L3 2. Position of dog M2 3. Mounting of photosensor P5 Panel Switch Functions Setting touch switches on the NT31/NT31C allows workers to use the NT31/NT31C as an operating panel; the results of the operations are transmitted to the host. Electroplating control Transport Electr. head Wash. head Corr. prv. head Electrolyte Wash Corr. prv.fluid Clamp Unclamp Adv. Int. stop Rev. 2 Section Role and Operation of the NT31/NT31C 1-1 1-1-2 Operations of the NT31/NT31C Displays Screens The information to be displayed (screen data) can be created on a computer using the Support Tool and stored in the NT31/NT31C. The screen data can be displayed on the NT31/NT31C in response to instructions from the host or touch switch operation. Host The screen data designated by instructions from the host or touch switch operation is displayed. Receives Data from a Host The NT31/NT31C can be connected to the host by a host link or NT link and receive necessary data from the host. Host link, NT link Sends Data to a Host Host Data input using the touch panel (switch ON/OFF statuses, numeric values, character strings) can be transmitted to the host. Host Touch panel ON/OFF information, numeric data, etc. Screen Data The screen data to be displayed on the NT31/NT31C can be created on a personal computer using the Support Tool. Connect the NT31/NT31C to the personal computer with an RS-232C cable and transmit the screen data to the NT31/NT31C. Create screen data. RS-232C Personal computer (Support Tool) Screen data When the host is connected at serial port A, the personal computer is only connected when communicating screen data between the NT31/NT31C and Support Tool. 3 Section Functions of the NT31/NT31C 1-2 1-2 Functions of the NT31/NT31C The NT31/NT31C has the following features. 1-2-1 Features Downsized Body • Slim body (50 mm or less in the panel*). • The communication cable connectors are housed in the unit so that they do not protrude from the unit. * When mounted in a panel of the recommended thickness (page 30). Construction Best Suited to the FA Environment • The panel is an STN monochrome LCD type with backlight for the NT31 and an STN color LCD type with backlight for the NT31C. • The backlight unit and battery can be replaced at the operation site. • Waterproofed equivalent to the NEMA4 standard and to IP65F*. * The panel may not be usable in environments where it is exposed to oil for long periods. 320 dots POWER RUN 240 dots Wide angle of visibility Touch Switch Operation Compatibility with Other PTs Contrast and brightness are adjustable by touch switch operations. • There is upward compatibility between the NT31/NT31C and the following models for screen data and user programs: NT11S, NT20S, NT30, NT30C, NT600S, NT610G, NT610C, NT620S, NT620C, NT625C, NT631, NT631. (After being read to the Support Tool, screens must be modified in accordance with the screen size. Depending on the function used, partial modification of programs may also be necessary. For details on the compatibility of screen data, refer to the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual and the NT-series Support Tool Operation Manual. • The dimensions of the panel cut-out to accommodate the NT31/NT31C are the same as for the NT30/NT30C. Two Ports Featured as Standard: Port A for Common Use by Support Tool/Host and Port B for Exclusive Use by the Host • Communication with the host is possible via another port while connected to the Support Tool. • Reading bar code data from a bar code reader is possible via another port while communicating with the host. Rapid System Program & Screen Data Changes Possible Using a Memory Unit • Installing a memory unit (type NT-MF261) on the rear of the NT31/NT31C makes it easy to write screen data into the NT31/NT31C on site. This enables a rapid response to setup changes. • NT31/NT31C can store a system program into a memory unit. This enables the system to handle more flexible setups. 4 Section Functions of the NT31/NT31C 1-2 Screen Data Check Function Screen data can be checked simply by operations at the NT31/NT31C system menu, without connecting up to the Support Tool. Increased Screen Data Capacity The data capacity of 1 MB is twice that of the NT30/NT30C, enabling storage of a larger quantity of screen data. Large Increase in Maximum Number of Registered Elements The number of elements that can be registered on one screen has been considerably increased, making it possible to create more expressive screens. For details, refer to Display Restrictions in Appendix A Specifications of the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual. Binary Data can be Read to/Written from the Host It is now possible to write binary data stored in words at the host directly to the NT31/NT31C. This makes data conversion by a program at the host unnecessary, reducing the load on the host. Character Display Using High Definition Fonts Any quadrupled characters are displayed with a 32 dot high-definition font. Simple Version Upgrades By using the system installer supplied with the Support Tool (Type NTZJCAT1-EV4), the system program at the NT31/NT31C can be changed easily from a personal computer. Complies with International Standards The NT31/NT31C meets UL/CSA standards and EC directives. Compatible with Other Vendors’ Devices Compatible with Sequencers in the following series: Mitsubishi A-series (Calculator Link) and FX-series (Programming Console), Allen-Bradley SLC 500 Series, GE Fanuc 90-20 and 90-30 Series, and Siemens S7-300 and S7-400 Series. Specialized system programs can be installed that allow the NT31/NT31C to be controlled from other companies’ Sequencers. Multiple Windows Up to 3 windows can be displayed simultaneously in the normal screen. A 9-word window control area has been allocated to the host; the contents of these 9 words can be changed from the Host to open, close, and move windows. 1-2-2 Comparison between NT31 and NT31C Two NT31 models — the NT31, which is capable of versatile graphic displays, and the NT31C, which is also capable of color display — are available. The differences between the NT31 and NT31C are tabled below: Function NT31 NT31C Type NT31-ST121-EV2 (Beige) NT31-ST121B-EV2 (Black) NT31-ST122-EV2 (Beige) NT31-ST122B-EV2 (Black) NT31C-ST141-EV2 (Beige) NT31C-ST141B-EV2 (Black) NT31C-ST142-EV2 (Beige) NT31C-ST142B-EV2 (Black) Display panel STN monochrome LCD display type (with white backlight) STN color LCD type (with white backlight) Beige and black are the front panel colors of each NT31/NT31C types. 1-2-3 Additional Functions of the V2 Versions The V2 versions of NT31/NT31C are supplemented and enhanced by the following functions. High-speed 1:N NT Link The V2 versions are compatible with the high-speed 1:N NT Link as well as the earlier standard 1:N NT Link. Additional Mathematical Functions Operands (values referenced by formula) can be registered to allow the PT to perform calculations automatically and write the results of those calculations to numeral memory tables or words in the host. Device Monitor Function The new device monitor function can be used to change the PLC’s operating mode or display/change values in the PLC’s memory areas. The present values (PVs) of several words can be listed with the device monitor. 5 Section Functions of the NT31/NT31C 1-2 Interlock Function PT operations and inputs can be disabled from the PLC if interlock bits have been allocated in the PLC for the corresponding PT touch switches, numeric inputs, or string inputs. Improved Lamp/Touch Switch Labels The following displays can be performed with lamp or touch switch labels: • Display several lines of labels. • Switch the display between different labels when OFF and ON. • Display the numeral memory table contents as labels. • Display the string memory table contents as labels. NT30/NT30C and NT620S/NT620C/NT625C Emulation The word configuration of the PT status control area and PT status notify area can be set to emulate those of the NT30/NT30C or NT620S/NT620C/NT625C; this mode is called NT30/620 compatible mode. When the PT is operating in NT30/620 compatible mode, it will be equivalent to an NT30/NT30C or NT620S/NT620C/NT625C in the functions listed below. The PT retains full V2 functionality in all functions other than the ones listed below. Refer to Appendix C in the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual for more details. • Word configuration and functions of the PT status control area and PT status notify area • Image/library codes • Insertion of image/library data into character strings Additional CS-series Data Areas Accessible Data areas in CS-series PLCs that were previously inaccessible can be accessed. The data areas listed below can be accessed (read/written). All banks in the EM area, timer completion flags (TU), counter completion flags (CU), Work areas (WR), Task flags (TK), and the HR area. Recipe Function You can set the data (numeric values) for multiple words in record units using the tabular elements on the PT screen, and write these settings in a single operation to words on the host (i.e., PLC or PT memory) using a touch switch operation on the PT Unit. Also, multiple words of numeric data can be read from the host in one operation. In this way, groups of parameter settings can be edited at the PT Unit, and written to or read from the host. Adjusting Contrast and Brightness During PT Operation You can display the brightness and contrast adjustment screen using either the touch switch or commands from the host, even while the PT is in operation. 1-2-4 Comparison between NT30/NT30C and NT31/NT31C Item NT30/NT30C NT31/NT31C Support Tool used NT-ZJCAT1-EV4 or NT-ZA3AT-EV2 NT-ZJCAT1-EV4 DIP switches On rear of unit None (software settings) Use of B7A unit Possible Not possible Use of memory unit Not possible Possible RS-232C interface Connector (9-pin) also used as port for screen data transfer. - Serial port A connector (also used for screen data transfer, 9-pin) - Serial port B connector (for host communications only, 25-pin) RS-422A/485 interface Terminal block Serial port B (25-pin D-SUB connector) Backlight color White/red (selectable) White only Replacement backlight NT30-CFL01/NT30C-CFL01 NT31C-CFL01 (NT31-ST121-EV2/NT31C-ST141EV2 (same for both models). The backlight for the NT31-ST122-EV2/NT31C-ST142EV2 cannot be replaced by the user.) 6 Section Functions of the NT31/NT31C Item NT30/NT30C 1-2 NT31/NT31C NT31/NT31C system program data NT-ZS3AT-EV1 (including system installer) The system installer and system program data are supplied with the Support Tool. High-speed 1:N NT Link Not possible Possible*1 Memory y Link System program Exclusive use by Memory Link Same as OMRON connection Screen data Shared with OMRON connection Exclusive use by Memory Link LCD contrast adjustment By a control on the rear of the unit By touch panel operation Backlight brightness adjustment Not possible By touch panel operation Number of user-registered screens Maximum of 2000 Maximum of 3999 Screen data capacity*2 512 KB 1 MB Numeral string data Maximum of 1000 Maximum of 2000 Character string data Maximum of 1000 Maximum of 2000 Bit data 256 Maximum of 1000 Mathematical tables None 256 max. Calculations can be executed automatically in the PT.*1 Image data Maximum of 224 Maximum of 4095*3 Library data Maximum of 896 Maximum of 12288*3 Method for storing numeric values (numeral memory data and PT status control area) Fixed as BCD (binary coded decimal) Selectable from BCD (binary coded decimal) or binary PT status control area size 4 words 5 words (partial change of contents)*3 PT status notify area size 3 words 2 words (partial change of contents)*3 Window control area size None 9 CH*2 Registering continuous screen Possible Not possible (Use a screen switchover as a substitute.) Lamp/Touch switch labels Fixed display (1 line only) - Interlock function None Operations can be disabled from the PLC by allocating interlock bits to the corresponding touch switch, numeral input, or character string input.*1 Device monitor function Not possible Possible*1 Recipe function None Possible Accessible CS-series PLC data areas --- The data areas listed below can be accessed in addition to the data areas accessible with the NT30/NT30C.*5 - EM banks (EM_0 to EM_C) - Timer completion flags (TU) - Counter completion flags (CU) - Work areas (WR) - Task flags (TK) - HR area (User program memory) Multiple lines can be displayed*1 ON/OFF switching is possible*1 Numeral display is possible*1 Character string display is possible*1 *1: These functions are available only in V2 versions of the NT31/NT31C. *2: This is the capacity of the flash memory that stores screen data. *3: The values are the same as the NT30/NT30C when the PT is in NT30/620 compatible mode. *4: The window control area can be used only in the V versions of the NT31/NT31C. For differences in programming, refer to Appendix B in the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual. 7 Functions of the NT31/NT31C Section 1-2-5 Principal Functions of NT31/NT31C The following are the principal functions of the NT31/NT31C. Functions relating to data display Character display Characters of various sizes can be displayed. Characters can be flashed and displayed in reverse video. High grade fonts are available for the characters with their size enlarged. Graphic display Polylines, rectangles, polygons, circles, circular arcs, and sector shapes can be displayed. They can also be tiled with various patterns, flashed, or displayed in reverse video. Memory data display The contents of character string memory tables and numeral memory tables can be displayed. The contents of memory tables can be changed from the host. Graph display Not only bar graphs but also broken line graphs, trend graphs, and analogue meter graphs can be displayed using numeral memory tables Lamp display Lamps can be turned on and flashed under the control of the host. It is also possible to display different graphics in the ON and OFF states. Alarm list/history display Warning messages are automatically displayed in a list in response to the state of a host bit. The time and the number of times of the messages appeared can also be displayed. Functions relating to data output Buzzer A built-in buzzer can be sounded. Screen printing A hard copy of the currently displayed screen can be printed at the printer connected to the NT31/NT31C. 8 1-2 Section Functions relating to data input Input by touch switches Data can be input by simply touching touch switches displayed on the screen. The possible functions of touch switches include sending data to the host and changing the screen display. Inputs can be enabled and disabled from the host when interlock bits have been allocated. Pop-up window function A window overlaying the currently displayed screen can be alternately opened and closed by pressing a touch switch. In addition to fixed character and graphic displays, control keys and character keys created as touch switches can also be set inside the window. A maximum of three windows can be displayed simultaneously. Since the window need only be opened when input is required, the screen can be used efficiently. Numeral/character string setting function Numeric keys and character keys can be assigned to touch switches so that numeric values and character strings can be input at the operation site. The input data is written to numeral/character string memory tables and also sent to the host. It is also possible to disable input by control from the host. Recipe function Several words of numeric data can be edited at the PT Unit, and written to or read from the host in one operation. Input from a bar code reader Data read with a bar code reader can be input to a character string input field. Functions relating to communication Communications with the host The NT31/NT31C can communicate with the host by four methods: host link, 1:1 NT Link, 1:N NT link (standard or high-speed), and Memory link. Data can be read from the host, and data input by means of touch switches and numeral/character string settings can be sent to the host. It is also possible to connect with other model PLCs. Functions relating to the system System menu System settings and maintenance can be performed by selecting from system menus displayed on the screen. Creation of screen data Screen data created using the Support Tool at a personal computer can be transferred and stored in the built-in screen data memory. Resume function The status and memory table contents of the NT31/NT31C immediately before its operation is stopped can be stored while operation is stopped, or while the power is off, and then displayed on the screen again when operation is restarted. Screen saver function This function serves to extend the service life of the backlight and prevent the formation of an afterimage on the screen. Clock function The time can be displayed in accordance with the internal clock data. Programming Console function The PT can perform the same operations as a C200H-PR027-E Programming Console when the PT is connected to a CPM1, CPM2A, CPM2C, CQM1, CQM1H, C200HX/HG/HE-(Z)E, or SRM1 PLC in a 1:1 NT Link connection, or a CS1G/CS1H PLC in a 1:N NT Link connection. Device Monitor function When the PT is connected to a PLC in a 1:1 NT Link or 1:N NT Link, the PT can be used for operations such as changing the PLC’s operating mode, displaying or changing the PVs of words, or reading the error log. System program install function The system program of the NT31/NT31C can be changed by using the system installer supplied with the Support Tool (NTZJ3AT1/ZJCAT-EV2). It can also be installed by using a memory unit (NT-MF261). Screen display history function/alarm history function The screen display history function records the time at which specific screens are displayed and the number of times they are displayed. The alarm history function records the time at which specific bits at the host are turned ON and the number of times they are turned ON. Trend graph logging function and background function Changes in the contents of numeral memory tables displayed in trend graphs can be recorded (logging function). Also, the record can be maintained even when the trend graph is not displayed (background function). Mathematical function This function allows calculations to be executed continuously during PT operation when mathematical table has been set in screen data. Arithmetic operations, bit operations, logic operations, and comparison operations can be performed. Operations with up to 5 terms are possible. 9 Section 1-2-6 Displays The NT31/NT31C can display various kinds of elements such as characters, numeric values, graphs, lamps, and touch switches, on a screen. The screen data displayed by the NT31/NT31C are created by using the Support Tool at a personal computer. Characters (fixed display) Line 1 Status Stop Characters (character string display) Machine name: NT31C-ST141 Production qty.: 137 units Bar graph 25% 0% Stage 1 Fixed Displays Check 1 50% Stage 2 Touch switches Restart 100% Numeric values (numeral display) Check 2 Lamps Characters and various graphics (circles, circular arcs, sectors, polylines, polygons and rectangles) whose display does not have to be changed, and mark data, image data, and library data that has already been registered, can be written directly onto the screen. Circle Arc Sector Polyline Polygon Rectangle * A continuous straight line with up to 256 points can be drawn. * A polygon with up to 255 vertices can be drawn. Marks are graphics comprising 16 by 16 dots that can be used as characters. They can be used as custom characters within character strings. Image data are graphics comprising any required area of dots. They are registered in advance and as many as required can be displayed at any position on the screen. Windows bit map (BMP) data can be used for images. There is a two-color mode, in which the display color and background color of the image are specified when it is registered in a screen, and an eight-color mode in which colors are assigned to the image in advance. Since image data is composed of dots, it requires a large data size but offers great powers of expression. 10 Section Library data are combinations of fixed display graphics registered as a single graphic. They are registered in advance and as many as required can be displayed at any position on the screen. Since it is generated by combining graphics, library data has a small data size. Mark Image data Lamps Library data These are graphics whose display status changes in accordance with the states of bits at the host. Squares, circles, sectors and polygons can be used for lamps (normal (standard) lamps). In accordance with the status of the host bit, they can be lit (displayed in reverse video) or flashed (repeated alternation between normal and reverse video display states). Lamps can also display different image/library data for the ON and OFF states of the host bit (such lamps are called image/library lamps). There are four standard lamp labels: fixed display character strings, ON/OFF switching character strings, numeral displays, and character string displays. When fixed display character strings or ON/OFF switching character strings are used, several lines of labels can be displayed. Normal (Standard) Lamps ON ON Host Unlit state Lit state Image Library Lamps ON Unlit state Touch Switches Host Lit state These switches can be set at any location on the screen. Pressing a touch switch on the screen where a touch switch has been set can have the following effects: • Notification to a host bit (input notification function) • Changing the displayed screen (screen switching function) • Input of a numeric value or character string (input key function) • Copying of a numeric value or character string (copy key function) • Shifting to another numeric value or character string input field (cursor moving key function) • Obtaining a hard copy of the screen (screen print function) • Opening / Closing a window • Moving a window 11 Section Touch switches can be made to light or flash in accordance with the status of a host bit in the same way as lamps. The following 8 types of display graphic can be used for touch switches: Standard, shadow, 3-dimension, no display frame, rectangle, circle, polygon, sector When rectangle, circle, polygon, or sector is selected as the shape, the area within which pressing of the touch switch is sensed (the touch switch area) can be set independently of the position where the display graphic is set. When this position is pressed... Touch switch area Shown in reverse video Display frame Function executed There are four touch-switch labels: fixed display character strings, ON/OFF switching character strings, numeral displays, and character string displays. When fixed display character strings or ON/OFF switching character strings are used, several lines of labels can be displayed. Numeral Displays Numeric values stored in the numeral memory tables are displayed. The displayed numerals can be changed by changing the data stored in the numeral memory tables. Hexadecimal values can also be displayed. When decimal values are displayed, the number of digits for the integral part and fractional part of displayed values can be specified in advance. String Displays Character strings stored in the character string memory tables are displayed. The displayed character strings can be changed by changing the data stored in the character string memory tables. Numeral Inputs Numeric values can be input at the PT by using touch switches. The input numeric values can also be stored in a numeral memory table and notified to the host. Numeral inputs can be enabled and disabled from the host when an interlock bit has been allocated. 12345678 789 456 123 0. " Input Window String Inputs Character strings can be input at the PT by using touch switches, bar code readers, etc. The input character strings can also be stored in a character string memory table and notified to the host. String inputs can be enabled and disabled from the host when an interlock bit has been allocated. Character string setting input field Display NT31C Input NT31C 12 NT31 NT631C Section Thumbwheel Switches Numeric values can be input by incrementing or decrementing each digit with the corresponding touch switch (+, –). The input numeric values can also be stored in a numeral memory table and notified to the host. Thumbwheel switch inputs can be enabled and disabled from the host when an interlock bit has been allocated. Graphs These are graphics whose display changes in accordance with the numeric values stored in numeral memory tables. There are the following four types. Bar Graphs Bar graphs display the present value in a numeral memory table converted to a percentage within the range –100% to +100% of a preset value. 60% Analog Meters Analogue meters display, using a quarter, half, or full circle shape, the present value in a numeral memory table converted to a percentage within the range –100% to +100% of the preset value. Users can choose from moving pointer type and filling area type displays. Users can also add graduation to the graph. 60% Broken Line Graphs Broken line graphs display, in an easy-to-read form, a sequence of numeral memory table values converted to a percentage within the range –100% to +100% of a preset value. 100% 0% –100% Example showing a series of 11 numeral memory table values (with a check mark set for the display sign) Trend Graphs Trend graphs display chronological changes in the value in a numeral memory table, converting the value to a percentage within the range –100% to +100% of a preset value. The trend graph shifts position with the passage of time. Past data can also be recorded, and the numeral memory table can be read (sampled) even while the trend graph is not being displayed. The user can choose to stop sampling, restart sampling, or display past data, by pressing touch switches. 13 Section Alarm List/History The alarm list/history function displays messages in list form, or graphics (image/library data), in accordance with changes in bit memory table statuses. For the alarm list, a series of bit memory tables are monitored, and messages (contents of character string memory tables) set for bit memory tables that come ON are displayed. For the alarm history, bit memory tables for which the history property is set are continually monitored, and the time when they come ON and number of times they come ON are recorded and displayed together with the message (character string) set for the bit memory table. The NT31/NT31C allows selection of the display order as the newest record first or the oldest record first by memory switch setting. The alarm list function is used to determine which bits are ON at the present time. The alarm history function is used to determine the times at which alarms occurred in the past and how many times alarms have occurred. Alarm List Message (character string table No. 32) set for bit memory table No. 14 Character string table No. 32 Image/library data 113C No.13 Bit Character string table No. 32 Image/library data 113C No.14 Character string table No. 54 Image/library data 1125 No.15 0 1 0 Character string table No. 50 Image/library data 1002 HOST A000000 L001003 D010015 1(ON) When the message displayed is pressed, the image/library data (113C) set for bit memory table No. 14 is displayed. Alarm History Message (character string table No. 13) set for bit memory table No. 24 Recorded data Character string table No. 13 Character string table No. 11 Image/library data 005F No. 22 Bit memory table No. 24 97/12/04 11:19:20 Character string table No. 12 Image/library data 102A No. 23 Bit memory table No. 23 97/12/04 11:25:12 Character string table No. 12 Image/library data 102B Character string table No. 13 Image/library data 102B No. 24 When the upper message displayed is pressed, the image/library data (102B) set for bit memory table No. 13 is displayed. Recipe 14 You can set several words of numeric data at the PT in tabular format, and write it to the host. You can also read several words of numeric data from the host and display it on the PT screen. Section System Configuration 1-3 1-3 System Configuration This section shows the configuration of a system that uses an NT31/NT31C. For details on product models, refer to Appendix J Model List (page 279). 1-3-1 Peripheral Devices That Can Be Connected The following peripheral devices can be connected to an NT31/NT31C. Host Controls the NT31/NT31C as required while controlling machines and monitoring the production line. Host Link: C series, CVM1/CV series PLC, SRM1 Bar code reader Can be connected to CPU units, host link units, and SRM1. However, connection Bar codes can be read as character strings. is not possible to some models of CPU unit and SRM1 (pages 52 and 99). NT Link: CS1G/CS1H, CPM1, CQM1, C200HS, C200HX/HG/HE(-ZE), Printer RS-232C cable (max. 15 m) or RS-422A/485 cable (max. 500 m) CVM1/CV series PLCs, SRM1 Can be connected to CPU units and SRM1. However, connection is notpossible to some models (pages 65, 70, 109 and 111). Memory Link: Can be connected to a personal computer, FA computer, etc. Other companies’ PLCs can also be connected. For printing out the currently displayed NT31/NT31C screen. Personal computer Running Windows 95/98/NT Support Tool Used to create screens for the NT31/NT31C at the personal computer and transmit them to the NT31/NT31C, and to make NT31/NT31C settings. System installer Used to change the system program of the NT31/NT31C. Memory unit Can store screen data and system program to be read out automatically at startup. NT31/NT31C Displays production line monitoring and instructions to the operation site, and notifies the switch ON/OFF status and numeric value inputs to the host. When a 1:N NT Link is being used, up to 8 PTs can be connected to a single PLC. • Bar code reader (page 35) • Recommended printers (page 34) It is also possible to use printers that can emulate an NEC PC-PR201H (using the NEC PC-PR201PL control protocol), and printers that comply with one of the following EPSON control standards: ESC/P 24-J83C (color), or ESC/P 24-J82 (monochrome). • Memory unit (pages 37 and 45) NT-MF261 (made by OMRON) • Support Tool (page 33) NT-series Support Tool Version 4.0 for Windows (Made by OMRON) • NT-ZJCAT1-EV4 (CD-ROM version) • System installer (page 33) System installer (made by OMRON) The system installer is supplied as a standard accessory with the Support Tool (NTZJCAT1-EV4). 15 Communications with the Host Section 1-4 Reference: The following optional devices are available. All of them can be used either with NT31 or NT31C. Replacement backlight NT31C-CFL01 (NT31-ST121-EV2/NT31C-ST141-EV2 (same for both models.) The backlight for the NT31-ST122 -EV2/NT31C-ST142 -EV2 cannot be replaced by the user.) Reflection-suppressing protective sheet NT30-KBA04 Chemical-resistant cover NT30-KBA01 Replacement battery 3G2A9-BAT08 1-3-2 Connecting to the Host The NT31/NT31C has the following two communication ports. • Serial port A: D-SUB 9-pin connector For RS-232C use only (The Support Tool and bar code readers can be connected here.) • Serial port B: D-SUB 25-pin connector For RS-232C or RS-422A/485 (Selectable by memory switch) (The Support Tool and bar code readers cannot be connected here.) The host can be connected at either of these two ports. The connection methods for each communication method at the PT and host sides are indicated below. Make the settings in accordance with the communication method that can be used with the PLC to be connected and the conditions at the operation site. Reference: When using an RS-232C/422A convertor unit (NT-AL001) with the host link or NT link (1:1) communication method, RS-485 cannot be used. The connection must be made with RS-232C or RS-422A. 1-4 Communications with the Host The NT31/NT31C is connected to the host by one of the following communication methods. The following communications can be used to connect an OMRON PLC: • Host link • 1:1 NT Link • 1:N NT Link (standard or high-speed) The following communications can be used to connect another companies’ PLC or FA computer: • Communications protocol supported by the other company’s PLC • Memory link In all of these communication methods that can be used with NT31/NT31C, data communication with host is by direct connection (Memory link is, however, a quasi-direct connection). In the following, the host link and NT link that carry out the direct connection will be discussed. Memory links will be explained in 1-5 Communications Using Memory Links. 1-4-1 Direct Connection Function With the NT31/NT31C, the bits and words referring to data required for display, and those for storing input data, can be allocated to any part of the PLC memory area. 16 Section Communications with the Host 1-4 The NT31/NT31C can directly write to and read from such allocated bits and words to change the display status of the elements on the PT screen, control the PT operating status, and notify statuses to the host. This function, which directly reads and writes the statuses of words and bits without using a PLC program is called the direct connection function. The words and bits allocated for direct connection are called the allocated words and allocated bits. The direct connection function allows the data to be displayed at the NT31/NT31C to be read from the memory area in the PLC and written to memory tables in the NT31/NT31C. Also, the data input at the NT31/NT31C can be written to the memory area in the PLC. The NT31/NT31C screen can be changed in accordance with statuses in the PLC memory area, and the NT31/NT31C’s status data can be written to the PLC’s memory area. NT31/NT31C PLC DM area I/O relay area Auxiliary relay area Timers/counters Features of the Direct Connection Function The direct connection function has the following features. • The bits and words referring to operating status and work instruction information and those for storing input data can be freely allocated to almost any area of the PLC memory. • Since the NT31/NT31C can directly refer to PLC bit and word data without using the program at the PLC, it can be connected to the PLC without changing the PLC program which controls the currently running production line. • The area to control and notify the NT31/NT31C statuses, including display screens, display/no display status, and buzzer output, can be freely allocated to any part of the PLC data area. This means that the PLC status can be read and controlled just by reading this area at the PLC side, without preparing a special communication program. The direct connection function allows the NT31/NT31C to directly read and write almost all bits and words in the PLC and to automatically change the NT31/NT31C screen display. This function can reduce the load on the PLC so that its program development efficiency is improved. 1-4-2 Host Link The host is connected to a PT in a 1:1 connection, and the words and bits of the host are read and displayed by host link communication. This method can be used for connection to the majority of PLC types. 1-4-3 NT Link NT link is a method for high-speed communication with a PLC using the direct connection function. The PLCs that can be connected with the NT link are as follows. • When using the built-in host link function of a CPU unit or SRM1: CPM1, CPM2A, CPM2C, CQM1, CQM1H, C200HS, C200HX/HG/HE(-Z)E, CS1G/CS1H-E(V1), CVM1/CV-series PLC (-EV1 or later version), SRM1 Besides the 1:1 NT Link method, in which one PLC is connected to one PT, the NT31/NT31C can also use the 1:N connection NT Link method, which allows a maximum of eight PTs to be connected to one PLC port. 17 Communications with the Host Section 1-4 PLCs that can be connected with the 1:N connection NT Link method are as follows: CQM1H, C200HX/HG/HE (-Z)E, CS1G/CS1H-E(V1). The NT31/NT31C also supports OMRON’s high-speed 1:N NT Link that provides faster 1:N communications. The only PLCs that support the high-speed 1:N NT Link are the -EV1 and higher versions of the CS1G/CS1H PLCs. In the following sections, the term NT Link is used to refer to the NT Link communication method in general, the term 1:1 NT Link is used to refer specifically to NT Links with a 1:1 connection, and the term 1:N NT Link is used to refer to both standard and high speed NT Links with 1:N connections. When necessary, the standard 1:N NT Link is distinguished from the high-speed 1:N NT Link. Features of the NT Link The NT link has the following features. • High-speed communications with specific types of PLCs can be executed. The NT31/NT31C also supports OMRON’s high-speed 1:N NT Link. • Writing in units of bits to the PLC memory area is possible. This enables the other bits of words to which a touch switch has been allocated to be allocated for other purposes (e.g. a lamp). However, since data is written to the DM area in word units, the other bits of words allocated to touch switches in this area cannot be used for other purposes. • The NT link can be used even when the PLC is in the RUN mode. (When the host link method is used, the NT31/NT31C switches to the monitor mode when the PLC is in the RUN mode.) • In the case of PTs that support the standard 1:N NT Link (NT20S, NT31, NT31C, NT600S, NT620S, NT620C, NT625C, NT631, NT631C) up to 8 PTs can be connected to one port of the PLC and used at the same time. Up to 8 PTs (NT31, NT31C, NT631, and NT631C) can also be connected simultaneously when the high-speed 1:N NT Link is being used. All of the PTs connected to a PLC port must use either the standard or highspeed 1:N NT Link; the two communications systems cannot share a single port. • When using a C200HX/HG/HE-(Z)E PLC and standard 1:N NT Links, up to three 1:N NT Link systems (i.e., 24 PTs) can be connected by installing a communication board in the option slot of the CPU. (Only the standard 1:N NT Link can be used.) For details on the Communications Board, refer to the SYSMAC Communications Board Operation Manual (W304-E1-). • When using a CQM1H PLC and standard 1:N NT Links, multiple 1:N NT Link systems can be connected by installing Serial Communications Boards in the Inner Board slots. For details on the Serial Communications Board, refer to the CQM1H Serial Communications Board Operation Manual (W365-E1-). • When using CS1G or CS1H PLC, multiple 1:N NT Link systems (standard or high-speed) can be connected by installing a Serial Communications Board in the INNER Board slot or installing a Serial Communications Unit in the Backplane. For details on the communication board/communication unit, refer to the CS/CJ-series Serial Communications Board/Unit Operation Manual (W336-E1-). • If the PLC used supports the Programming Console function, the NT31/NT31C can be used as a Programming Console. • If the PLC being used supports the Device Monitor function, the NT31/NT31C can be used to change the PLC’s operating mode and read/change data in the PLC’s memory areas. The NT link is compatible with the host link. The NT31/NT31C screen data and PLC programs used with the host link direct connection method can be used with the NT link method as they are. 18 Section Communications Using Memory Links 1-5 1-4-4 Connecting to other Companies’ PLCs Installing a system program for multi-venders by using a specific system installer enables the NT31/NT31C to be connected to the PLCs of other models in direct connection. This system installer is supplied with the Support Tool (NTZJCAT1-EV4). Compatible PLC 1-5 The NT31/NT31C can be connected to the following model PLCs. • Mitsubishi A series programmable controller (computer link module) • Mitsubishi FX series programmable controller • SLC 500 Series by Allen-Bradley • 90-20 and 90-30 Series by GE Fanuc • S7-300 and S7-400 Series by Siemens For details on the procedure for connecting to other model PLCs, refer to the PLC Connection Manual or NT31/631 Multi Vendor Connection Manual. Communications Using Memory Links In this section, a communication method other than the direct connection, called the memory link, is discussed. 1-5-1 Memory Link Memory link is a method to send and receive data between a personal computer or a FA computer and the NT31/NT31C by using RS-232C/422A communication. In memory link, there is an area called PT Memory, as shown below, inside the NT31/NT31C, and this area is treated as a virtual area on the PLC. This allows PT memory and the display elements of the NT31/NT31C to make a quasi-direct connection. By sending a command for the memory link, the host can make the NT31/NT31C execute processes through PT memory. Frequently used commands are kept handy for read and write tasks of the numeral memory table, character-string memory table, and bit memory table. NT31/NT31C PT PLC PT memory Numeral memory table Lamp Direct connection RS-232C/422A communication In the memory link method, the only difference is that the NT31/NT31C finds its communication target inside instead of outside. In the memory link method, therefore, change of the target is all that is needed to be capable of using the exact screen data that is acquired by the direct connection. (With the NT31/NT31C, the Support Tool must be used to convert the data to screen data for the memory link.) When compared to the direct connection of the host link or NT link methods, the memory link method has some restrictions regarding the use of some functions, as described below. • The Programming Console and Device Monitor functions cannot be used. • The following strobes of PT status notify bits does not turn on (page 7 to 27). 19 Communications Using Memory Links Section 1-5 Screen switching strobe Numerals input strobe Character-string input strobe • The usable area for allocation is the PT memory only. 1-5-2 Comparison between Direct Connection and Memory Link The major differences between the direct connection and the memory link are as follows: • In the memory link method, the communication with the host should be carried out by using commands. Compared to the ordinal direct connection, which can be used requiring almost no programs, the memory link method requires a program that is necessary for interchange of commands. This, however, gives advantages to the memory link method by using a large variety of functions available in the direct connections from major models such as a personal computer and a FA computer equipped with RS-232C/RS-422A communication means, allowing the PT to be suited for larger usage. • Actual PLCs have many kinds of areas, where as PT memory is a single area with only one kind. When creating screen data by using the memory link methods, it is always necessary to allocate display parts in the PT memory. For communication between the host and the PT by the memory link method and for handling screen display elements, refer to the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual. 1-5-3 Memory Link Online Transfer Function When memory link communications are being used, the NT31/NT31C can be switched to Transmit mode from the host even if the NT31/NT31C is operating and screen data can be written. (The NT31/NT31C can be returned to RUN mode after the screen data is written.) The memory link online transfer function can be used to replace screen data at a fixed time each day or replace screen data with maintenance screen data for maintenance. For more details on the memory link online transfer function, refer to information on the memory link online transfer function in the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual. 20 Section Before Operating 1-6 1-6 Before Operating Follow the procedure given below to start the system of the NT31/NT31C. Host Support Tool NT31/NT31C Set the host settings. Install the PT in the operation panel. • For the host link, refer to pages 52 and 99, and the manuals for the host link unit and peripheral tools. • For the NT link (1:1), refer to pages 65 and 109. • For the NT link (1:N), refer to pages 70 and 111. • For the high-speed NT link (1:N), refer to pages 74 and 113. • For the Memory link, refer to pages 70 and 114 Install the Support Tool at the computer. (refer to the manual for the Support Tool) (page 30) Connect the power supply. (page 31) Install the system program.*1 (refer to page 149 and the Support Tool manual) Make the settings in the system installer mode.*2 (page 149) Transmit the screen data. Create the screens. (Refer to the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual and the Support Tool Operation Manual.) (page 153) Set the memory switches. (page 155) Connect to the host. Connect to the NT31/NT31C. When RS-232C used at the PT: refer to section 4 When RS-422A/485 used at the PT: refer to section 5 Create the host program. Confirm the settings and check communication. Start operation. *1: System program installation is only done in special circumstances, for example when changing the system program, or to recover the original status of the installed program. This operation is not normally necessary. When using other PLC models (sequencers), however, it is necessary to install specific system programs. *2: Display of the system menu, and all change operations, can be inhibited. This enables you to prevent the accidental deletion or alteration of screens and settings. Reference: For the system program, use the NT31/NT31C system program supplied as an accessory with the NT-series Support Tool (NT-ZJCAT1-EV4). For the Support Tool, use NT-series Support Tool for Windows (Ver. 4.1). Refer to the following manuals for the devices and software. Device or Software Manual Title Manual Number NT31/NT31C, NT631/NT631C Reference Manual V064-E1-1 System Installer NT-series Support Tool for Windows (Ver. 4.1) Operation Manual V061-E1- Support Tool NT-series Support Tool for Windows (Ver. 4.1) Operation Manual V061-E1- 21 Section Before Operating Device or Software PLC Manual Title 1-6 Manual Number SYSMAC CPM1 Operation Manual W262-E1- SYSMAC CPM1A Operation Manual W317-E1- SYSMAC CPM2A Operation Manual W352-E1- SYSMAC CPM2C Operation Manual W356-E1- SYSMAC C200H Operation Manual (for CPU01/03/11) (programming) W130-E1- SYSMAC C200H Operation Manual (for CPU21/23/31) (programming) W217-E1- SYSMAC C200HS Installation Guide W236-E1- SYSMAC C200HS Operation Manual (programming) W235-E1- SYSMAC C200HX/HG/HE-Z Installation Guide W302-E1- SYSMAC C200HX/HG/HE Programming Manual W303-E1- SYSMAC C200HX/HG/HE-Z Programming Manual W322-E1- SYSMAC C1000H/C2000H Operation Manual (programming) W140-E1- SYSMAC CQM1 Programming Manual W228-E1- SYSMAC CQM1H Operation Manual W363-E1- SYSMAC CVM1/CV500/CV1000/CV2000 Operation Manual: Ladder Diagrams W202-E1- CS-series CS1G/H-CPU -E Programmable Controllers Operation Manual W339-E1- CS/CJ-series Serial Communication Boards/Units Operation Manual W336-E1- SYSMAC CQM1H Series Serial Communications Board Operation Manual W365-E1- CompoBus Master Control Unit SRM1 Operation Manual W318-E1- Programming g g Devices SYSMAC Support Software Operation Manual: C-series PLCs W248-E1- SYSMAC Support Software Operation Manual: CVM1 PLCs W249-E1- SYSMAC CPT User Manual and Quick Start Guide W332-E1- W333-E1- CX-Programmer Operation Manual (Ver. 3.1) W414-E1- CX-Programmer Operation Manual (Ver. 4.0) W425-E1- SYSMAC C-series Host Link Unit Operation Manual W143-E1- SYSMAC CVM1/CV-series Host Link Operation Manual W205-E1- Host Link Unit/ S i l Communications Serial C i i Board SYSMAC C200HW-COM01 C200HW-COM02-V1 to C200HW-COM06-EV1 W304-E1- Serial Communications Board Operation Manual 22 SECTION 2 Preparing for Connection This section describes the connection methods that are possible with the PTs, and the functions of the parts of PTs, as the required knowledge before connecting to the host and to the peripheral devices. 2-1 2-2 Method for Connection to the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Names and Functions of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 27 23 Section Method for Connection to the Host 2-1 2-1 Method for Connection to the Host This section describes the methods for connection to the host used with the NT31/NT31C, and the relationship between the connection method and the communication method. NT31/NT31C Communication Ports and Communication Methods The NT31/NT31C has two communication ports. Their uses are indicated in the table below. Communication Port Usable Communication Methods Serial port A Host link NT link (1:1) NT link (1:N)* Memory link (Support Tool connection) (bar code reader input function) RS-232C Serial port B Host link NT link (1:1) NT link (1:N)* Memory link RS-232C RS-422A/485 (select between RS-232C and RS-422A/485) Communication Type * There are two NT Link (1:N) communications rates: standard and high-speed. Communication Methods That Can Be Used with the Host The following communication methods can be used with the hosts that can be connected to the NT31/NT31C. • RS-232C • RS-422A • RS-485 The communication types that are actually supported differ depending on the host unit. For details, refer to Section 4 Connecting to the Host from the RS-232C Port and Section 5 Connecting to the Host from the RS-422A/485 Port. Converting the Communication Type with an RS-232C/RS-422A Convertor Unit The following communication type conversions are possible by using an RS-232C/RS-422A convertor unit (NT-AL001-E, made by OMRON). • RS-232C ⇔ RS-422A • RS-232C ⇔ RS-485 24 Section Method for Connection to the Host 2-1 Combinations of Communication Method and Connection Method The connection methods that can be used depending on the communication method used and the communication type for communication between the NT31/NT31C and the host are indicated in the table below. Communica Communication Type at PT Usable Communication Method Communica Communication Type at Host Usable Connection Method Details Host link NT Link (1:1) NT Link (1:N) Memory link 77 86 Direct 1:1 connection PT RS-232C Host RS-232C RS-232C (max. 15 m) 1:1 connection via a convertor unit PT Convertor unit (NT-AL001) Host RS-232C (max. 2 m) RS-422A (max. 500 m) 1:N connection via a convertor unit RS-232C PT Host Convertor unit (NT-AL001) RS-422A (total length 500 m) RS-232C (max. 2 m) 90 RS-422A Direct 1:1 connection PT Host 115 RS-422A (max. 500 m) 1:N connection RS-422A PT Host RS-422A (total length 500 m) : Connection possible 120 : Connection not possible 25 Section Method for Connection to the Host Communica Communication Type at PT 2-1 Usable Communication Method Communica Communication Type at Host Usable Connection Method Host link NT Link (1:1) NT Link (1:N) Memory link Details 1:1 connection via a convertor unit PT Convertor unit (NT-AL001) RS-485 (max. 500 m) Host 86 90 119 123 RS-232C (max. 2 m) 1:N connection via a convertor unit RS-232C PT Host Convertor unit (NT-AL001) RS-485 RS232C (total length 500 m) (max. 2 m) RS 485 RS-485 Direct 1:1 connection PT Host RS-485 (max. 500 m) 1:N connection RS-485 PT Host RS-485 (total length 500 m) : Connection possible : Connection not possible • The RS-232C/RS-422A convertor unit (NT-AL001) requires +5 V, 150 mA at pin 6 of the RS-232C connector. Check the signals of the RS-232C connector at the host. • +5 V is not output from serial port B of the NT31/NT31C. When connecting an NT-AL001 at serial port B, a separate power supply is required for the NTAL001. • The cable of an NT-AL001 cannot be connected or disconnected while the power is ON. Always connect or disconnect the cable while the power supply from the RS-232C cable is OFF (while the host power supply is OFF). • NT link (1:N) connection is possible even when RS-232C is used at the NT31/NT31C side for communication with the host, but in this case one NTAL001 unit is required for each NT31/NT31C. In this case, it is convenient to use serial port A of the NT31/NT31C. +5 V is not output from serial port B. 26 Section Names and Functions of Parts 2-2 2-2 Names and Functions of Parts Before starting operation, the names and functions of the parts of the NT31/NT31C are described here as a confirmation. A method of hardware settings is also described. Front View POWER LED Lit in green when the power is supplied. POWER RUN Display RUN LED • Lit in green while the unit The NT31 has a monochrome LCD screen with a backlight, and the NT31C is in the RUN mode. • Lit in orange or red when has an STN color LCD screen with a the battery is low (orange backlight. in the RUN mode, red in The whole area of the screen is a touch panel which works as an input device. other modes). Reference: The NT31/NT31C comes in two body colors. NT31 NT31C Body Color NT31-ST121-EV2 NT31-ST122-EV2 NT31C-ST141-EV2 NT31C-ST142-EV2 Beige NT31-ST121B-EV2 NT31-ST122B-EV2 NT31C-ST141B-EV2 NT31C-ST142B-EV2 Black 27 Section Names and Functions of Parts 2-2 Rear View Battery cover The battery is secured underneath this cover. Reset switch (inside the cover) Used to initializes all the statuses of the NT31/NT31C. However, registered data such as screen data, and memory switch settings, retain their statuses before initialization. GR terminal Grounding terminal to prevent malfunction due to noise. Expansion interface connector (under the label) When using an expansion interface unit such as a memory unit, peel off the label and connect it here. 24V DC PRINTER Power input terminals Connect the power to the NT31/NT31C at these terminals. PORT B PORT A Warning label Backlight unit (inside the cover) Open the cover to reveal the backlight. The backlight is off while the cover is removed. Tighten the cover screw securely. Serial port A connector Connect the cable for connection to the host or Support Tool here. A bar code reader can also be connected here. This is a 9-pin connector for RS-232C use only. Serial port B connector Connect the cable for connection to the host here. Depending on the setting made at the NT31/NT31C system menu, either RS-232C or RS-422A/485 may be used. This is a 25-pin connector. It is not possible to use RS-232C and RS-422A/485 at the same time. Printer connector Connect the printer cable here. Output conforms to Centronics specifications. Note Confirm system safety before turning the power ON/OFF or resetting. 28 SECTION 3 Hardware Settings and Connections This section describes the settings of the PTs and methods for connection to peripheral devices. For details on connecting to the host, refer Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port. 3-1 3-2 3-3 3-4 3-5 3-6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-1 Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-2 Installation in the Operation Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-3 Power Supply Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-4 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting to the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting a Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-1 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting a Bar Code Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-1 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-2 Setting a Bar Code Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-3 Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using a Memory Unit (-V Versions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5-1 Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5-2 Method of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using a Memory Unit (Versions without the -V Suffix) . . . . . . . . . . . . . . . . . . . . . . . . . 3-6-1 Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6-2 Method of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 30 30 31 32 33 34 34 35 35 35 36 37 38 38 45 46 46 29 Section Installation 3-1 Note On unpacking the NT31/NT31C and peripheral devices, check their external appearance and confirm that there is no damage. Also confirm that there is no abnormal noise on shaking the unit lightly. 3-1 Installation Install the NT31/NT31C in the operation panel and connect the power to the NT31/NT31C as described below. 3-1-1 Installation Environment Observe the following points when installing the PT in an operation panel. Note 1. Do not install the unit at sites subject to the following conditions. • Severe temperature variations • Temperatures or humidities outside the ranges stated in the specifications • High humidity, condensation • Splashing chemical agents • Severe oil splashing • Corrosive or flammable gases • Strong vibrations or shocks • Direct exposure to wind and rain (outdoor sites) • Strong ultra-violet irradiation 2. Take adequate measures to ensure shielding if the unit is used at a location subject to any of the following conditions. • Static electricity, or noise from other equipment • Strong electromagnetic fields • Nearby power cables • Potential exposure to radioactivity 3-1-2 Installation in the Operation Panel The NT31/NT31C is mounted in an operation panel by embedding it in the panel. Use the panel fittings and tool (Philips screwdriver) included in the product package and follow the procedure below. 1, 2, 3... 1. Open a hole of the dimensions shown below in the panel and install the NT31/NT31C from the front side of the panel. 131 184 + 0.5 mm 0 mm + 0.5 mm 0 mm 2. Attach the panel fittings at the four positions at top and bottom and two positions at right and left, shown below, from the rear of the NT31/NT31C. Fit the hook of the fitting in the square hole in the body and tighten the screw with the Philips head screwdriver while lightly pulling the fitting. 24V DC PRINTER 30 PORT B PORT A Section Installation Note 3-1 1. During work at the panel, take care to ensure that no metal scraps enter the unit. 2. The thickness of applicable operation panel is 1.6 mm to 4.8 mm. All fittings must be tightened uniformly to a torque of 0.5 to 0.6 N⋅m in order to ensure water- and dust-resistance. Front sheet of NT31/NT31C may be warped if the tightening is too strong or not uniformity. The panel must not be soiled or warped, and must be able to support an installation that will remain secure and strong. 3-1-3 Power Supply Connection Connect a 24 VDC power supply to the power input terminals. Note 1. Depending on how the power is switched ON/OFF, the entire system may stop. Follow the correct procedure when switching the power ON/OFF. 2. Carefully check the wiring before switching ON the power. 3. Do not connect AC power to the DC terminals. 4. Use DC power supplies with low voltage fluctuation. 5. Do not perform a dielectric strength test. 6. If complying with EC directives (low voltage directives), use a power supply with reinforced insulation (compliance with EC directives is planned for June 1998). 24 VDC Breaker 24 VDC power supply Power Supply The applicable power supply specifications are as follows. Item Value Power supply 24 VDC Allowable power supply voltage fluctuation range Power supply voltage capacity 20.4 VDC to 26.4 VDC (24 VDC –15%, +10%) 15 W or more Parts Used for Connection Note For the connection to the power supply terminal block, twisted wires of 2 mm2 or greater cross sectional area and M3.5 size crimp terminals must be used. Tighten the screws on the terminal block to a torque of 0.8 N⋅m. Fork type 7 mm or less Round type 7 mm or less Recommended Terminals Type (fork type) Type (round type) Japan Solderless Terminal MFG 2-YS3A 2-3.5 Fuji Terminal 2-YAS3.5 V2-S3.5 Nichifu Terminal 2Y-3.5 2-3.5 Maker Applicable Wire (stranded wire) 2.0 to 2.63 mm2 31 Section Installation 3-1 Note When surge noise occurs in the DC power supply, connect a Transistor Voltage Suppressor (TVS) between the 24-V and 0-V DC terminals. Recommended TVS model: 1.5KE33CA Manufacturers: Vishay Intertechnology Inc, ST Microelectronics 3-1-4 Grounding The NT31/NT31C has a functional ground terminal ( Carry out wiring under the following conditions. 1, 2, 3... ). 1. In cases where there is a potential difference between the grounds of the NT31/NT31C and the host, ground as shown in the following figure. If there is some distance between the NT31/NT31C and host and grounding at a single point is difficult, do not connect the functional ground terminal ( ) of the NT31/NT31C. 2. If the NT31/NT31C is installed in the same panel as equipment that generates noise, such as a motor or inverter, do not ground the functional ground terminal ( ) of the NT31/NT31C. NT31/ NT31C Host Grounding at a single point Note Carry out grounding correctly in order to prevent operating errors due to noise. 32 Section Connecting to the Support Tool 3-2 3-2 Connecting to the Support Tool In order to install the system program in the NT31/NT31C, or to transmit screen data created with the Support Tool to the NT31/NT31C, the NT31/NT31C must be connected to a personal computer with an RS-232C cable. The NT31/NT31C connects the RS-232C cable from a personal computer at serial port A. When the host is connected at serial port B, the connection with the host can be maintained as it is while the NT31/NT31C is connected to the RS-232C cable from a personal computer. However, when a bar code reader is being used, it must be disconnected, so that the RS-232C cable can be connected, since they both use serial port A. PRINTER PORT B PORT A Serial port A (RS-232C, 9-pin) Communication Conditions The communication conditions are automatically set when the system installer and Support Tool are started. Recommended Connector Cable Use the cable indicated below. • CV500-CN228 (length: 2 m), made by OMRON (D-SUB 9-pin, male ⇔ D-SUB 25-pin, male) • XW2Z-S001 (conversion cable), made by OMRON (D-SUB 25-pin, female ⇔ half pitch 14-pin, male) • XW2Z-S002 (length: 2 m), made by OMRON (D-SUB 9-pin, male ⇔ D-SUB 9-pin, female) For details on making a connector cable, refer to Appendix F Making the Cable for Connecting a PLC (page 269). 33 Section Connecting a Printer 3-3 3-3 Connecting a Printer Connecting a printer to the NT31/NT31C enables printing of hard copies of the currently displayed screen (printing of screen images), and, by system menu operations, printing of the screen display history and alarm history. The following types of data can be printed, depending on the printer connected to the NT31/NT31C. For details, refer to the pages cited. • Hard copies of the screen (Refer to information on printing data and checking the printer status in the NT31/NT31C/NT631/NT631C Programmable Terminal Reference Manual.) • Screen display history record data (page 196) • Alarm history record data (page 198) 3-3-1 Connection Method Connect the printer to the NT31/NT31C with a Centronics cable, as shown below. The length of the cable should not exceed 1.5 m. Reference: If the connector cable is connected or disconnected while the power to the printer is on, the NT31/NT31C may malfunction. Always turn off the power to the printer before connecting or disconnecting the cable. 24V DCPRINTER PORT B PORT A Recommended Connector Cable The following connection cables are recommended. • NT-CNT121 (1.5 m, 20-pin to 36-pin), made by OMRON Recommended Printers When using a printer, use one that can emulate an NEC PC-PR201H (using the NEC PC-PR201PL control protocol) or complies with one of the following EPSON control standards: ESC/P 24-J83C (color), or ESC/P 24-J82 (monochrome). When using a monochrome printer with an NT31C, set Tone printing with the NT31C memory switches (page 172). 34 Section Connecting a Bar Code Reader 3-4 3-4 Connecting a Bar Code Reader Connecting a bar code reader to the NT31/NT31C enables bar code data to read as character strings into character string input fields, and set in character string memory tables. In order to use a bar code reader, the Comm. A Method memory switch must be set to Bar-Code Reader. For details on the method for inputting character strings with a bar code reader, refer to 3-7 Input of Numeric Values and Character Strings in the NT31/NT31C/ NT631/NT631C Programmable Terminal Reference Manual. Note Make sure that the power supply to the bar code reader and the power supply to the PT are both OFF before connecting or disconnecting the cable. 3-4-1 Connection Method Connect the bar code reader to serial port A of the NT31/NT31C, as shown in the figure below. NT31/NT31C PRINTER PORT B Bar code reader PORT A Serial port A (RS-232C, 9-pin) 9-pin connector Connector cable Bar code reader cable Bar code reader must match the communication setting (3-4-2 Setting a Bar Code Reader, page 35) and data format (3-4-3 Data Format, page 36) in order to connect to the NT31/NT31C. Please confirm the specification of the bar code reader before using. For details on making a connector cable, refer to Appendix G Making the Cable for Connection to a Bar Code Reader (page 271). Reference: The bar code reader must be connected to serial port A. This means that it cannot be connected at the same time as the Support Tool. Note also that when a bar code reader is used, the host must be connected at serial port B. 3-4-2 Setting a Bar Code Reader After connecting a bar code reader, set the communication conditions and other settings for it by selection from the system menu. Settings at the NT31/NT31C At the NT31/NT31C, set the communication conditions for communication with the bar code reader by using the memory switches, selecting from the options indicated in the table below. For more detailed information on the actual system menu operations, refer to 6-10 Setting the Bar Code Reader Input Function (page 186). Item Possible Settings Default Setting Data bits 7 or 8 bits 7 bits Stop bit(s) 1 or 2 bits 2 bits Parity None, odd, even Even Communications speed 4800, 9600, 19200 bps 9600 bps Input Method Manual Manual, Auto 35 Section Connecting a Bar Code Reader Settings at the Bar Code Reader 3-4 Make the settings shown in the table below at the bar code reader. Make sure that the communications speed, parity, stop bit, and data bit settings match the communication settings made at the NT31/NT31C. For details on the setting method, refer to the instruction manual for the bar code reader used. Item Possible Settings Communications speed 4800, 9600, 19200 bps Parity EVEN, ODD, NONE Stop bits 1 or 2 bits Data bits 7 or 8 bits Preamble STX Postamble ETX RS/CS control Available Communication protocol No-protocol mode Transmission of number of bar code label digits Transmission prohibited Transmission of ID characters Transmission prohibited Bar code types Multi-reading (all types can be read) Trigger switch setting Automatic reading mode About RS/CS Control During bar code reading, the NT31/NT31C performs RS/CS control. When the Input Method setting of the NT31/NT31C is set to Auto, the RS signal is turned OFF, prohibiting the next input, until the read data has been notified to the host. Because of this, when the Auto setting is made, the next input is not possible until the data has been notified to the host. However, when the setting is Auto and the RS/CS signals of the cable are shorted, RS/CS control is ineffective. Consequently, data input from the bar code reader to the NT31/NT31C is updated regardless of whether or not the data is notified to the host. For details, refer to the instruction manual for the bar code reader used. 3-4-3 Data Format The data format for communication when using the bar code input function of the NT31/NT31C is shown below. STX (02H) Data Data Data ETX (03H) The characters which are effective as data are hexadecimal codes from 20 to 7FH, and the maximum data length is 40 bytes. Data which does not follow the data format described above is invalidated and discarded. 36 Section Using a Memory Unit (-Vj Versions) 3-5 3-5 Using a Memory Unit (-V Versions) This section discusses the use of a memory unit with a V1 or V2 version of an NT31/NT31C PT (NT31-ST121/122-EV or NT31C-ST141/142-EV). Reference: Depending on the PT model and the system program which is installed, the function and using method of memory unit varies as follows. PT Model Without V suffix With V suf suffix System Program Earlier than Ver. 2 Ver. 2 or later Earlier than Ver. 2 Ver. 2 or later Function of Memory Unit Conventional memory unit function. (Refer to 56.) (System programs can not be transmitted using memory unit.) New memory unit function. (System programs can be transmitted using memory unit.) The memory unit functions are determined by the model of PT being used, regardless of the version of the system program installed in the PT. By installing a memory unit (NT-MF261) on the NT31/NT31C, the screen data in the NT31/NT31C can be recorded (backed up) in the memory unit. In addition, the screen data in the memory unit can be automatically read into the NT31/NT31C when it starts up. This means that system program and screen data can be changed easily at the operation site without connecting to the Support Tool. The data in the memory unit is retained without backup by a battery or other means. In systems where there are frequent setup changes, by preparing a number of memory units in advance and recording screen data in them in accordance with the control performed in each case, the NT31/NT31C screen data can be changed simply by installing the memory unit, without connecting to the Support Tool. In addition, even if NT31/NT31C is replaced, the previous status can be maintained simply by installing the memory unit that retains the system program and screen data of the previous NT31/NT31C. By using the following combinations, data can be stored (backed up) to a memory unit. • Screen data for two PTs. • System program for two PTs. • System program and screen data for one PT. One memory unit can store the screen data for two PTs. Note 1. Make sure that the power supply to the PT is OFF before connecting or disconnecting a memory unit. After mounting a memory unit, be sure to tighten its two screws. 2. During data transmission, do not turn off the power supply to the NT31/NT31C or reset it. 3. Do not touch the PCB (printed circuit board) with bare hands. 37 Section Using a Memory Unit (-Vj Versions) Reference: 3-5 When a memory unit is mounted, the NT31/NT31C cannot be set to the operating status. On completion of data transmission with a memory unit, always disconnect the memory unit from the NT31/NT31C before starting NT31/NT31C operation. Memory units (NT-MF261) can be used in common for the following PT models: NT31, NT31C, NT631, and NT631C (with or without the V suffix). One memory unit can store screen data for up to two PTs of different models. However, since the data compatibility is not complete between NT31/NT31C and NT631/NT631C, an error may occur if an attempt is made to read NT631C data with an NT31C. (The data must be converted using the Support Tool.) Note also that although there is data compatibility between the NT31 and NT31C, and between the NT631 and NT631C, the display may not be correct since these models have different numbers of colors. One memory unit can store a system program for up to two PTs of different models. In order to transmit a system program from the memory unit to the NT31/NT31C, the system program must be compatible to the target PT model. The statuses of memory switch settings and system settings can be recorded to the memory unit besides screen data. When the data in the memory unit is written into the NT31/NT31C, make sure that these settings can be adapted to the NT31/NT31C used before transmission. 3-5-1 Installation Method Install the memory unit (NT-MF261) at the expansion interface connector at the rear of the NT31/NT31C as shown in the figure below (the expansion interface connector is located underneath the note label.). Mounting screws 3-5-2 Method of Use As shown in the figure below, a memory unit has two sets of four DIP switches, and the operation is determined by the DIP switches that are set at startup. 1 2 3 4 1 2 3 4 Factory setting is turned all to off. OFF OFF SW1 Note 38 SW2 1. Always confirm that the power to the NT31/NT31C is off before setting the DIP switches. 2. Do not touch the PCB (printed circuit board) directly with bare hands. Section Using a Memory Unit (-Vj Versions) DIP Switch Functions 3-5 The functions of the DIP switches on the memory unit are indicated in the table below. • SW1 Switch Function SW1 1 SW1-1 Automatic transmission (writing from the memory unit to the PT) OFF: Not executed SW1 2 SW1-2 Automatic transmission (writing from the PT to the memory unit) OFF: Not executed SW1 3 SW1-3 Manual transmission (Direction of transmission and bank used selected at the PT touch panel) OFF: Not executed SW1-4 Data type to transfer ON : Executed ON : Executed ON : Executed OFF: Screen data ON : System program • SW2 Switch Function SW2 1 SW2-1 Disable/enable writing to PT SW2 2 SW2-2 Disable/enable writing to the memory unit SW2 3 SW2-3 Area (bank) selection of automatic transmission. transmission * SW2 4 SW2-4 System/Screen simultaneous transmission OFF: Disable ON : Enable OFF: Disable ON : Enable OFF: Bank 0 ON : Bank 1 OFF: Disable ON : Enable * The memory unit stores system program or screen data for one PT in each of areas (bank 0, bank 1). (The total data storage is for two PTs.) SW2-3 sets which of these two banks is used for automatic transmission. Reference: The DIP switch function of the memory unit is supplemented to NT31/NT31C with the V suffix. In the following cases, a mode setting error occurs. • More than one of the SW1-1 to SW1-3 switches are set to ON. • None of the SW1-1 to SW1-3 switches are set to ON. In the following case, a protect setting error occurs. Transmitting to the write destination has been disabled by the setting for SW2-1 or SW2-2. In the following cases, a data transmission error occurs. • An attempt is made to transmit data other than the system program to PT system program area. • An attempt is made to transmit the system program to PT screen data area. For details on mode setting errors and protect setting errors, refer to Errors When Using a Memory Unit (page 43). 39 Section Using a Memory Unit (-Vj Versions) Writing Screen Data to a Memory Unit Using Automatic Transmission (PT to Memory Unit) 3-5 In this mode, system program or the screen data in the NT31/NT31C is forcibly written to the memory unit irrespective of the setting status of the NT31/NT31C. This mode is convenient if the touch panel is broken and touch switch operation is not possible, or if someone unfamiliar with touch switch operation at the operation site is using the system. Reference: When screen data is written to the memory unit, the data that has been stored in the specified area up until that point is lost (if the data is written into only one Bank, the other Bank will not be affected). Method of Execution Use the following procedure to write the screen data in the NT31/NT31C to the memory unit by automatic transmission. 1, 2, 3... 1. Check that the power supply to the NT31/NT31C is OFF, then set the DIP switches of the memory unit as follows after installing memory unit to NT31/NT31C. SW1 SW2 SW2-4 ON: System/Screen transmitted simultaneously OFF: System/Screen not transmitted simultaneously SW2-3 ON: Bank 1 OFF: Bank 0 SW1-4 ON: System program OFF: Screen data It is not strictly necessary to set SW2-1 to OFF (to disable writing to the PT), but it is recommended to do so to avoid loss of data in the event of operating errors. Reference: Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW1-4. Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW2-3, writes the system program into bank 0, and the screen data into bank 1 at all times. 2. Switch the NT31/NT31C power ON. The screen data is automatically written into the memory unit. The screen data in the NT31/NT31C is preserved. The messages Preparing, Transmitting, Verifying, and Finished are displayed on the screen in accordance with the progress of data writing. At the same time, the progress of the data writing status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte). RUN LED operates as follows according to the processing status. Preparing Transmitting Verifying Finished : flashes at intervals of 1 second : flashes at intervals of 0.5 second : flashes at intervals of 0.5 second : lights up 3. Switch the NT31/NT31C power OFF, remove the memory unit. To operate NT31/NT31C continuously, switch the NT31/NT31C power back ON. 40 Section Using a Memory Unit (-Vj Versions) Writing Screen Data to the PT Using Automatic Transmission (Memory Unit to PT) 3-5 In this mode, the system program or screen data in the memory unit is forcibly written to NT31/NT31C irrespective of the setting status of the NT31/NT31C. Since data transmission by this method is faster than when the Support Tool or system installer is used, it can save a lot of time. When transmitting the same system program or screen data to multiple NT31/NT31C, this mode becomes convenient. Reference: When data is written to the NT31/NT31C, the data that has been stored up until that point is lost. When the system program is changed, the operation of NT31/NT31C also changes. Method of Execution Use the following procedure to write the screen data in the memory unit to the NT31/NT31C by automatic transmission. 1, 2, 3... 1. Check that the NT31/NT31C power is OFF, then set the DIP switches on the memory unit as follows after installing memory unit to NT31/NT31C. SW1 SW2 SW2-4 ON: System/Screen transmitted simultaneously OFF: System/Screen not transmitted simultaneously SW2-3 ON: Bank 1 OFF: Bank 0 SW1-4 ON: System program OFF: Screen data It is not strictly necessary to set SW2-2 to OFF (to disable writing to the memory unit), but it is recommended to do so to avoid loss of data in the event of operating errors. Reference: Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW1-4. Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW2-3. In this case, the data transmission becomes possible only if the data inside memory unit is in either of following combinations. Bank 0: system program, Bank 1: other than system program Bank 0: other than system program, Bank 1: system program If the combination is not as listed above, a data transmitting error occurs. When writing the system program into the NT31/NT31C, the type of system program inside memory unit and the type of PT unit must be corresponding. 2. Switch the NT31/NT31C power ON. The screen data is automatically written into the PT. The messages Preparing, Transmitting, Verifying and Finished are displayed on the screen in accordance with the progress of data writing. At the same time, the progress of data writing status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte). The RUN LED operates as follows according to the processing status. Preparing : flashes at intervals of 1 second Transmitting : flashes at intervals of 0.5 second Verifying : flashes at intervals of 0.5 second Finished : lights up 3. Switch the NT31/NT31C power OFF, remove the memory unit. To operate NT31/NT31C continuously, switch the NT31/NT31C power back ON. 41 Section Using a Memory Unit (-Vj Versions) Reading and Writing Data by Manual Transmission 3-5 In this method, the direction of transmission and area of the memory unit used are set by touch switch operations at the NT31/NT31C. Transmission can be executed while checking the settings. Reference: When data is written to the NT31/NT31C or memory unit, the data that has been stored up until that point is lost. Method of Execution Use the following procedure to write screen data using manual transmission. 1, 2, 3... 1. Check that the NT31/NT31C power is OFF, then set the DIP switches on the memory unit as follows. SW1 SW2 Setting of SW2-4 not relevant Setting of SW2-3 not relevant Setting of SW1-4 not relevant In order to avoid loss of data in the event of operating errors, it is advisable to set SW2-1 and SW2-2 so as to disable writing to the unit from which the data is to be read. 2. Switch the NT31/NT31C power ON. Display language select screen appears. 3. Press the Japanese or English touch switches to select the display language. The following descriptions are for when English is selected. The screen shown below is displayed. Current PT Screen Data, System The first line: Compatible PT type for the system program inside PT. The second line: System program name and Version for the system program inside PT. 42 Section Using a Memory Unit (-Vj Versions) 3-5 (The second line may not be displayed in the kind of system program.) Current PT Screen Data, Screen The comment for the screen data in the NT31/NT31C is displayed here. Current Memory Unit Screen Data • In the case of system program: The first line: Compatible PT type for the system program inside the memory unit. The second line: System program name and Version for the system program inside the memory unit. (The second line may not be displayed in the system program for some models.) • In the case of screen data: The comment for the screen data in the NT31/NT31C is displayed here. The available transmitting destinations are altered depending on the settings of the origin of transmitting as described in the table below. Source [PT]screen Destination [[Memory y unit]] Bank 0 [[Memory y unit]] Bank 1 [PT]system [PT]system/screen [Memory unit] Bank 0/1 (fixed) [Memory unit] Bank 0 If system program is selected [PT]system y ((fixed)) If screen data is selected [PT]screen (fixed) [Memory unit] Bank 1 [Memory unit] Bank 0/1 Reference: [PT]system/screen (fixed) When transmitting the system program and screen data simultaneously from the PT to the memory unit, the setting of banks is Bank 0: system program, Bank 1: screen data, and when transmitting them from the memory unit to the PT, either of the following combinations must be used. Bank 0: system program, Bank 1: other than system program Bank 0: other than system program, Bank 1: system program When writing the system program into the NT31/NT31C, the type of system program inside memory unit and the type of PT unit must be corresponding. 4. Press Execute. The data is transmitted. The messages Preparing, Transmitting, Verifying, and Finished are displayed in accordance with the progress of data transmission. At the same time, the progress of data transmitting status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte). When the data transmission is operated manually, RUN LED remains OFF. 5. Switch the NT31/NT31C power OFF, remove the memory unit, then switch the NT31/NT31C power back ON. Errors When Using a Memory Unit If an error occurs when using the memory unit, the NT31/NT31C operates as follows. • The details of the error and remedial action are displayed on the screen. Each screen has touch switches to change the display language from one to the other. When the manual data transmission is operating, the content of error and remedial action are shown with selected language. When the automatic transmission is operating, it is displayed in Japanese. 43 Section Using a Memory Unit (-Vj Versions) 3-5 • The continuous buzzer sounds. • The RUN LED flashes. If a protect setting error occurs when executing manual transmission, it is possible to return to the memory unit manual transmission screen by pressing the OK touch switch, but in the case of other errors, the status described above remains in effect until the NT31/NT31C power is turned OFF or reset. When an error occurs, take remedial action by referring to the table below. Error 44 Probable Cause Remedial Action Mode setting error DIP switches SW1-1 to SW1-3 are all OFF, or more than one is ON. Turn the NT31/NT31C power OFF, set the memory unit DIP switches correctly, then turn the NT31/NT31C power back ON. Protect setting error (automatic transmission) Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-2. Turn the NT31/NT31C power OFF, set the memory unit DIP switches correctly, then turn the NT31/NT31C power back ON. Protect setting error (manual transmission) Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-2. Perform either of the following procedures. Press the OK touch switch to return to the memory unit manual transmission screen, make the correct settings, then try again. Turn the NT31/NT31C power OFF, correct the DIP switches settings of the memory unit, then turn the power back ON. Flash memory error An error occurred during initialization of the NT31/NT31C or memory unit flash memory, or during write processing. Turn the NT31/NT31C power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the unit. Verify error An error occurred during verification processing at the flash memory of the NT31/NT31C or the memory unit. Turn the NT31/NT31C power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the unit. Transmitting data error (The automatic transmission only) An attempt is made to transmit data other than a system program or the system program of a different PLC model into the NT31/NT31C as the system program. An attempt is made to write a system program into the NT31/NT31C as screen data. Perform either of the following procedures. Turn the NT31/NT31C power OFF, correct the DIP switch settings of the memory unit, and then turn the power back ON. Turn the NT31/NT31C power OFF, set the DIP switch settings to the manual transmission, and then check the data inside the memory unit. Using a Memory Unit (Versions without the -Vj Suffix) 3-6 Section 3-6 Using a Memory Unit (Versions without the -V Suffix) This section discusses the use of a memory unit with the basic versions of the NT31/NT31C PTs (NT31-ST121-E or NT31C-ST141-E). Reference: In this case, the function and use of the memory unit are the same as ones for the NT31/NT31C without the V suffix. (The system program transmission by using a memory unit cannot be processed.) By installing a memory unit (NT-MF261) on the NT31/NT31C, the screen data in the NT31/NT31C can be recorded (backed up) in the memory unit. In addition, the screen data in the memory unit can be automatically read into the NT31/NT31C when it starts up. This means that screen data can be changed easily at the operation site without connecting to the Support Tool. The data in the memory unit is retained without backup by a battery or other means. In systems where there are frequent setup changes, by preparing a number of memory units in advance and recording screen data in them in accordance with the control performed in each case, the NT31/NT31C screen data can be changed simply by changing the memory unit, without connecting to the Support Tool. One memory unit can store the screen data for two PTs. Note 1. Make sure that the power supply to the PT is OFF before connecting or disconnecting a memory unit. After mounting a memory unit, be sure to tighten its two screws. 2. During data transmission, do not turn off the power supply to the NT31/NT31C or reset it. 3. Do not touch the PCB (printed circuit board) with bare hands. Reference: When a memory unit is mounted, the NT31/NT31C cannot be set to the operating status. On completion of data transmission with a memory unit, always disconnect the memory unit from the NT31/NT31C before starting NT31/NT31C operation. Memory units (NT-MF261) can be used in common for the following PT models: NT31, NT31C, NT631, NT631C (with or without the V suffix). One memory unit can store screen data for up to two PTs of different models. However, since the data compatibility is not complete between NT31/NT31C and NT631/NT631C, the data of NT631 cannot be used in NT31C without putting it through a conversion (the data must be converted using the Support Tool). Note also that although there is data compatibility between the NT31 and NT31C, and between the NT631 and NT631C, the display may not be correct since these models have different numbers of colors. The screen data for NT31/NT31C PTs with system program Ver. 2 or later cannot be used with PTs with system program earlier than Ver. 2. The statuses of memory switch settings and system settings can be recorded to the memory unit besides screen data. When the data in the memory unit is written into the NT31/NT31C, make sure that these settings can be adapted to the NT31/NT31C used before transmission. 45 Section Using a Memory Unit (Versions without the -Vj Suffix) 3-6 3-6-1 Installation Method Install the memory unit (NT-MF261) at the expansion interface connector at the rear of the NT31/NT31C as shown in the figure below. (The expansion interface connector is located underneath the note label.) Mounting screws 3-6-2 Method of Use As shown in the figure below, a memory unit has two sets of four DIP switches, and the operation is determined by the DIP switches that are set at startup. 1 2 3 4 1 2 3 4 Factory setting is turned all to off. OFF OFF SW1 Note DIP Switch Functions SW2 1. Always confirm that the power to the NT31/NT31C is off before setting the DIP switches. 2. Do not touch the PCB (printed circuit board) directly with bare hands. The functions of the DIP switches on the memory unit are indicated in the table below. • SW1 Switch Function SW1 1 SW1-1 Automatic transmission (writing from the memory unit to the PT) OFF: Not executed SW1 2 SW1-2 Automatic transmission (writing from the PT to the memory unit) OFF: Not executed SW1 3 SW1-3 Manual transmission (Direction of transmission and bank used selected at the PT touch panel) OFF: Not executed SW1-4 Reserved for system use (must be set to OFF) ON : Executed ON : Executed ON : Executed • SW2 Switch 46 Function SW2 1 SW2-1 Disable/enable writing to PT SW2 2 SW2-2 Disable/enable writing to the memory unit SW2 3 SW2-3 Area (bank) selection of automatic transmission. transmission SW2-4 Reserved for system use (must be set to OFF) OFF: Disable ON : Enable OFF: Disable ON : Enable OFF: Bank 0 ON : Bank 1 Section Using a Memory Unit (Versions without the -Vj Suffix) 3-6 * The memory unit stores screen data for one PT in each area (bank 0, bank 1). (The total data storage is for two PTs.) SW2-3 sets which of these two banks is used for automatic transmission. Reference: In the following cases, a mode setting error occurs. • More than one of the SW1 switches are set to ON. • None of the SW1 switches are set to ON. In the following case, a protect setting error occurs. • Writing to the write destination has been disabled by the setting for SW2-1 or SW2-2. For details on mode setting errors and protect setting errors, refer to Errors When Using a Memory Unit (page 3 to 25). Writing Screen Data to a Memory Unit Using Automatic Transmission (PT to Memory Unit) In this mode, the screen data in the NT31/NT31C is forcibly written to the memory unit irrespective of the setting status of the NT31/NT31C. This mode is convenient if the touch panel is broken and touch switch operation is not possible, or if someone unfamiliar with touch switch operation at the operation site is using the system. Reference: When screen data is written to the memory unit, the data that has been stored in the specified area up until that point is lost (there is no effect on the other area). Method of Execution Use the following procedure to write the screen data in the NT31/NT31C to the memory unit by automatic transmission. 1, 2, 3... 1. Check that the power supply to the NT31/NT31C is OFF, then set the DIP switches of the memory unit as follows after installing the memory unit in NT31/NT31C. 1 2 3 4 1 2 3 4 OFF OFF SW1 SW2 SW2-3 ON: Bank 1 OFF: Bank 0 It is not strictly necessary to set SW 2-1 to OFF (to disable writing to the memory unit), but it is recommended to do so to avoid loss of data in the event of operating errors. 2. Switch the NT31/NT31C power ON. The screen data is automatically written into the memory unit. The screen data in the NT31/NT31C is preserved. The messages Preparing, Transmitting, Verifying, and Finished are displayed on the screen in accordance with the progress of data writing. When messages Preparing, Transmitting, and Verifying are displayed, the RUN LED flashes, and when the message Finished is displayed, the RUN LED lights. 3. Switch the NT31/NT31C power OFF, remove the memory unit. To operate NT31/NT31C continuously, switch the NT31/NT31C power back ON. Writing Screen Data to the PT Using Automatic Transmission (Memory Unit to PT) In this mode, screen data is forcibly written from the memory unit to the NT31/NT31C irrespective of the setting status of the NT31/NT31C. Since data transmission by this method is faster than when the Support Tool is used, it can save a lot of time. When transmitting the same system program or screen data to multiple NT31/NT31C, this mode becomes convenient. 47 Section Using a Memory Unit (Versions without the -Vj Suffix) 3-6 Reference: When data is written to the NT31/NT31C, the data that has been stored up until that point is lost. Method of Execution Use the following procedure to write the screen data in the memory unit to the NT31/NT31C by automatic transmission. 1, 2, 3... 1. Check that the NT31/NT31C power is OFF, then set the DIP switches on the memory unit as follows after installing the memory unit in NT31/NT31C. 1 2 3 4 1 2 3 4 OFF OFF SW2 SW1 SW2-3 ON: Bank 1 OFF: Bank 0 It is not strictly necessary to set SW2-2 to OFF (to disable writing to the memory unit), but it is recommended to do so to avoid loss of data in the event of operating errors. 2. Switch the NT31/NT31C power ON. The screen data is automatically written into the PT. The messages Preparing, Transmitting, Verifying and Finished are displayed on the screen in accordance with the progress of data writing. When messages Preparing, Transmitting, and Verifying are displayed, the RUN LED flashes, and when the message Finished is displayed, the RUN LED lights. 3. Switch the NT31/NT31C power OFF, and remove the memory unit. To operate NT31/NT31C continuously, switch the NT31/NT31C power back ON. Reading and Writing Data by Manual Transmission In this method, the direction of transmission and area of the memory unit used are set by touch switch operations at the NT31/NT31C. Transmission can be executed while checking the settings. Reference: When data is written to the NT31/NT31C or memory unit, the data that has been stored up until that point is lost. Method of Execution Use the following procedure to read and write screen data using manual transmission. 1, 2, 3... 1. Check that the NT31/NT31C power is OFF, then set the DIP switches on the memory unit as follows. 1 2 3 4 1 2 3 4 OFF OFF SW1 SW2 Setting of SW2-3 not relevant In order to avoid loss of data in the event of operating errors, it is advisable to set SW2-1 and SW2-2 so as to disable writing to the unit from which the data is to be read. 48 Using a Memory Unit (Versions without the -Vj Suffix) Section 3-6 2. Switch the NT31/NT31C power ON. The screen shown below is displayed. (Example) Current PT Screen Data The comment for the screen data in the NT31/NT31C is displayed here. Current Memory Unit Screen Data The comments for the screen data in each area are displayed here. Pressing the Trans. Direction Change and Bank Change touch switches changes the selections for the direction of transmission and the area of the memory unit used. 3. Press Execute. The data is transmitted. The messages Preparing, Transmitting, Verifying, and Finished are displayed in accordance with the progress of data transmission. 4. Switch the NT31/NT31C power OFF, remove the memory unit, then switch the NT31/NT31C power back ON. Errors When Using a Memory Unit If an error occurs when using the memory unit, the NT31/NT31C operates as follows. • The details of the error and remedial action are displayed on the screen. • The continuous buzzer sounds. • The RUN LED flashes. If a protect setting error occurs when executing manual transmission, it is possible to return to the memory unit manual transmission screen by pressing the OK touch switch, but in the case of other errors, the status described above remains in effect until the NT31/NT31C power is turned OFF or reset. When an error occurs, take remedial action by referring to the table below. Error Probable Cause Remedial Action Mode setting error DIP switches SW1-1 to SW1-3 are all OFF, or more than one is ON. Turn the NT31/NT31C power OFF, set the memory unit DIP switches correctly, then turn the NT31/NT31C power back ON. Protect setting error (automatic transmission) Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-2. Turn the NT31/NT31C power OFF, set the memory unit DIP switches correctly, then turn the NT31/NT31C power back ON. Protect setting error (manual transmission) Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-2. Perform either of the following procedures. Press the OK touch switch to return to the memory unit manual transmission screen, make the correct settings, then try again. Turn the NT31/NT31C power OFF, correct the DIP switches settings of the memory unit, then turn the power back ON. 49 Using a Memory Unit (Versions without the -Vj Suffix) 50 Section 3-6 Error Probable Cause Remedial Action Flash memory error An error occurred during initialization of the NT31/NT31C or memory unit flash memory, or during write processing. Turn the NT31/NT31C power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the unit. Verify error An error occurred during verification processing at the flash memory of the NT31/NT31C or the memory unit. Turn the NT31/NT31C power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the unit. SECTION 4 Connecting to the Host from the RS-232C Port This section describes the method for connecting to the host using the RS-232C port of the PT. 4-1 Connecting to the RS-232C Port at the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-1 Host Types and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-2 Connecting Directly between RS-232C Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 52 77 51 Section Connecting to the RS-232C Port at the Host 4-1 4-1 Connecting to the RS-232C Port at the Host The method for connecting between the RS-232C port of the PT and the RS-232C port of the host is as follows. The following discussion is focused on the connection method to OMRON PLCs (By using the memory link method, a connection can be made to any arbitrary RS-232 unit). When making a connection to a host other than OMRON PLCs, refer to the PLC Connection Manual (V042-E1-) or NT31/631 Multi Vendor Connection Manual (V060-E1-). Direct Connection Between The RS-232C Ports Using an RS-232C Cable (Page 109) This is the easiest connection method. Depending on the host to which the connection is to be made, it may be possible to use OMRON cables with connectors. NT31/NT31C Host RS-232C cable (max. 15 m) Reference: The CS-series CPU cannot be connected with the 1:1 connection NT link method. Use the 1:N connection NT link method instead to make the 1:1 connection. For details, refer to Using the NT Link (1:N) Method (page 70) or Using the Highspeed NT Link (1:N) Method (page 73). 4-1-1 Host Types and Settings The types of host that can be connected to a PT by using the RS-232C ports of both units, and the settings to be made at the host, are described here. When Using the Host Link Method Compatible Host Units 52 Some models and series of OMRON PLCs have the host link function built in. In the CS-series or CQM1H PLCs, the host link method can be used by installing a Serial Communication Board. In addition, some C200HX/HG/HE(-Z)E have an integral CPU that can be connected in the host link method by installing a Communication Board. Check the model and series of the PLC, the type of installed Serial Communication Board, Serial Communication Unit, or Host Link Unit before making a connection. Section Connecting to the RS-232C Port at the Host 4-1 The host units that can be connected to the NT31/NT31C by the host link method using the RS-232C ports of both units are indicated in the table below. PLC Series CS Series Units with Built-in Host Link Function CS1G-CPU42/43/44/45-EV1 CS1H-CPU63/64/65/66/67-EV1 CS1G-CPU42/43/44/45-EV1 CS1H-CPU63/64/65/66/67-EV1 --- C1000H-CPU01-EV1 C2000H-CPU01-EV1 C200HS-CPU01/03/21/23/31/33-E C200HE-CPU11/32/42-E C200HE-CPU11/32/42-ZE C200HG-CPU33/43/53/63-E C200HG-CPU33/43/53/63-ZE C200HX-CPU34/44/54/64-E C200HX-CPU34/44/54/64/65/85-ZE --- C Series CPUs Connectable with Host Link Units or Expansion Communication Board C200HS-CPU21/23/31/33-E --- C200HE-CPU42-E C20HE-CPU42-ZE C200HG-CPU43/63-E C200HG-CPU43/63-ZE C200HX-CPU44/64-E C200HX-CPU44/64/65/85-ZE C200HE-CPU32/42-E C200HE-CPU32/42-ZE C200HG-CPU33/43/53/63-E C200HG-CPU33/43/53/63-ZE C200HX-CPU34/44/54/64-E C200HX-CPU34/44/54/64/65/85-ZE C1000H-CPU01-EV1 C2000H-CPU01-EV1 C1000H-CPU01-EV1 C1000HF-CPU01-EV1 C2000H-CPU01-EV1 ----- Host Link Unit/ Communication Board CS1W-SCU21 CS1W-SCB21 CS1W-SCB41 C120-LK201-EV1 C200H-LK201-EV1 --- C200HW-COM02/04/ 05/06 EV1 05/06-EV1 C500-LK201-EV1 C500-LK203 Connectable to CS1G CS1H C1000H C2000H C200HS C200HE C200HE-Z C200HG C200HG-Z C200HX C200HX-Z C200HS C200HE C200HE-Z C200HG C200HG-Z C200HX C200HX-Z C1000H C2000H C1000H (F) C2000H CPM1-10/20/30CDR- +CPM1-CIF01 CPM1A-10/20/30/40CD- +CPM1-CIF01 CPM2A-30/40/60CD- +CPM1-CIF01 (Peripheral port connection) CPM2C-10/20- (*1) CQM1-CPU21-E CQM1-CPU41/42/43/44-EV1 CQM1H-CPU11/21/51/61 (*2) --- --- --- --- --- --- CPM2A --- --- CPM2C --- --- CQM1 CQM1H-CPU51/61 CQM1H-SCB41 CQM1H CPM1 CV500-CPU01-EV1 CV500-CPU01-EV1 Se CV Series (*3) CV1000-CPU01-EV1 CV1000-CPU01-EV1 CV500 CV2000-CPU01-EV1 CV2000-CPU01-EV1 CVM1 Series (*3) CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 CV500-LK201 CVM1 CompoBus/S master control unit SRM1-C02-V1 --- --- SRM1 CV500-LK201 CV500 LK201 CV1000 CV2000 *1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect. *2: The CQM1H-CPU11 does not have a built-in RS-232C port, so connect to the peripheral port to the PT with a CS1W-CN118 Connecting Cable. *3: CPUs of CVM1/CV-series PLCs without the suffix -EV cannot be connected. 53 Section Connecting to the RS-232C Port at the Host Settings at the Host 4-1 When using the host link method, the settings shown below must be made at the host (depending on the unit, some of these settings may not be necessary, or settings not shown here may be necessary). Item Switch Setting I/O port RS-232C Communications speed Set the same speed as for the NT31/NT31C. (*1) Transfer code ASCII, 7 data bits, 2 stop bits Parity Even 1-to-1/1-to-N 1-to-N(*2) Instruction level Level 1, 2, 3 Unit # 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 158). *2 The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT31/NT31C in a single host link. The setting methods for each type of unit are described in the following. Connecting to a C-series Host Link Unit C200H/C200HS/C200HE/HG/HX (-Z)E Backplane mounted type: C200H-LK201-V1 Setting the Front Switches Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following. LK201 XMT RUN RCV ERROR @ Unit # (SW1, SW2) Set these switches to 0. SW2 SW1 0 0 5 2 SW3 @ Instruction level, parity, and transfer code (SW4) Set this switch to 2. SW4 @ Communications speed (SW3) Set this switch to 5 to select 9600 bps. Set this switch to 6 to select 19200 bps. Setting the Rear Switches ON CTS selector switch External 0V (ON) 54 1 2 3 4 @ 1-to-1/1-to-N selection (DIP switch) Set #3 to ON. @ CTS selection (selector switch) Set this always to 0V (ON). Section Connecting to the RS-232C Port at the Host 4-1 C1000H(F)/C2000H Backplane mounted type: 3G2A5-LK201-EV1 Setting the Front Switches Local Host Mode control (key switch) Set this to host link. Setting the Rear Switches @ I/O port selection (selector switch) Set this to RS-232C. I/O port @ Unit # (DIP SW1) Set SW1-1 to SW1-5 to OFF (0). 8 RS-422A RS-232C 7 6 5 4 Synchronization SW1 3 Internal External 2 1 ON Terminator @ Synchronization (selector switch) Set this to Internal. 8 OFF ON 7 6 5 4 CTS 3 0V External 2 1 ON SW2 @ Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19,200 bps. Set these switches to 1010 to select 9,600 bps. (0: OFF 1: ON) @ 1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N). @ Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.) @ CTS selection (selector switch) Set this always to 0V (ON). 55 Section Connecting to the RS-232C Port at the Host 4-1 C1000H/C2000H Backplane mounted type: C500-LK203 Setting the Rear Switches @ I/O port selection (selector switch) Set this to RS-232C. 5V supply ON OFF @ Unit #, parity, and transfer code (DIP SW1-1 to SW1-7) Set SW1-1 to SW1-7 to OFF (0). 8 7 I/O port 6 RS-422A RS-232C 5 4 SW1 3 2 Synchronization Internal External 1 ON Terminator @ Synchronization (selector switch) Set this to Internal. 8 OFF ON 7 6 5 4 CTS 3 0V External 2 1 ON SW2 @ Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19,200 bps. Set these switches to 1010 to select 9,600 bps. (0: OFF 1: ON) @ 1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N). @ Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.) @ CTS selection (selector switch) Set this always to 0V (ON). 56 Section Connecting to the RS-232C Port at the Host 4-1 C200H/C1000H/C2000H CPU mounting type: 3G2A6-LK201-EV1 Setting the Rear Switches @ Unit #, parity, and transfer code (DIP SW1-1 to SW1-5) Set SW1-1 to SW1-5 to OFF (0). * Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits. @ Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19,200 bps. Set these switches to 1010 to select 9,600 bps. (0: OFF 1: ON) SW1 SW2 @ 1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N). SW3 @ Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.) @ CTS selection (DIP SW3-1 and SW3-2) Set SW3-1 to ON (1), and SW3-2 to OFF (0). (Set this always to 0V.) @ Synchronization (DIP SW3-3 to SW3-6) Set SW3-3, and SW3-5 to ON (1), and SW3-4, and SW3-6 to OFF (0). (Set these to Internal.) Connecting to a CVM1/CV Series Host Link Unit CVM1/CV series backplane mounted type: CV500-LK201 A CVM1/CV series host link unit (CV500-LK201) has two connectors (communication ports 1 and 2). Either of these ports can be used for connection to an NT31/NT31C by the RS-232C method. However, since the connectors at these ports are of different types, a cable that matches the connector must be prepared. • Communication port 1 Communication port 1 is a 25-pin connector for RS-232C use only. • Communication port 2 Communication port 2 is a 9-pin connector which allows selection of the RS-232C or RS-422A method. When this port is used with the RS-232C method, the I/O port selector switch on the front of the unit must be set to RS-232C (the upper position). CPU Bus Unit Settings When connecting to a CVM1/CV series host link unit, set the following communication conditions for the CPU bus unit settings. Item Setting at Host Communications speed Set the same speed as set at the NT31/NT31C(*1) Transfer code ASCII, 7 data bits, 2 stop bits Parity Even 1-to-1, 1-to-N 1-to-N(*2) Instruction level Level 1, 2, 3 *1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page158). 57 Section Connecting to the RS-232C Port at the Host 4-1 *2 The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT31/NT31C in a single host link. Set the CPU bus unit settings directly from a Programming Device (e.g. SYSMAC support software). For details on the CPU bus unit settings, refer to the SYSMAC CVM1/CV-series Host Link Unit Operation Manual (W205-E1-). Setting the Front Switches @ Unit # (SW3, SW4) When using communication port 2, set these switches to 0. Communications port 1 (RS-232C) @ I/O port selection (selector switch) Set this to RS-232C. Communications port 2 (RS-232C/RS-422A) @ CTS selection (DIP SW2 and SW3) Set SW2 or SW3 to ON. (Set this always to 0V.) To use communication port 1, set SW2. To use communication port 2, set SW3. I/O port selector switch RS-232C RS-422A @ Communication condition setting (DIP SW1) Set this switch to OFF. Communication is executed in accordance with the CPU bus unit system settings made at the PLC. The initial values for the system settings are as follows. - Communications speed: 9600 bps - Parity: Even - Xon/Xoff control: Not executed - Communication method: Full duplex - Stop bits: 2 stop bits - Data length: 7 bits Connecting to a CS-series Serial Communication Unit CS-series Backplane mounted type: CS1W-SCU21 Setting the Front Switches Set the unit number of the serial communication unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following. SCU21 RDY ERH SD2 RD2 RUN ERC SD1 RD1 UNIT No. 10 58 FE C Set the unit number to 0 through F so that it will not overlap with the numbers used in other units. Section Connecting to the RS-232C Port at the Host 4-1 Allocation DM Area Settings for CPU Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU. After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. In the following, the channel numbers of the allocation DM area and the settings are shown. m=DM30000+100×unit # (CH) Allocation DM area (CH) Port 1 Port 2 m m+10 m+1 m+11 m+2 m+6 Writing Value Settings 8000 host link mode, 2 stop bits, even parity, data length 7 bits 0000 Communication speed 9600 bps. 0007 Communication speed 19200 bps. m+12 0000 Transmit delay time 0 ms. m+16 0000 No CTS control Unit No.0 for host link Connecting to a CPU Unit CV-series and CVM1/CV-series (-EV) CPU Units • CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1 • CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2 PLC Setup When connecting to a CVM1/CV series CPU, set the following communication conditions for the PLC Setup. Item Setting at Host Communications speed Set the same speed as set at the NT31/NT31C(*1) Stop bit 2 stop bits Parity Even Data length ASCII 7 bits Unit # 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 158). Either set PLC Setup directly from a Programming Device (e.g. SYSMAC support software), or transmit the PLC Setup made at a Programming Device to the CPU. For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/1000/2000 Operation Manual: Ladder Diagrams (W202-E1-). 59 Section Connecting to the RS-232C Port at the Host 4-1 Setting the Front Switches @ I/O port selection (selector switch) Set this to RS-232C. I/O port selector switch RS-232C RS-422A @ System setting (DIP SW4) To effect the existing DIP switch settings, set SW4 to ON. To effect the existing PLC Setup, set SW4 to OFF. Note For CPUs manufactured before or during June 1995 (lot No. 65), the existing DIP switch settings differ from the existing PLC Setup as follows. - DIP switch settings: 2,400 bps, 1 stop bit, even parity, 7 bit data length - PLC Setup: 9,600 bps, 2 stop bits, even parity, 7 bit data length For CPUs manufactured from July 1995 onward (lot No. 75), the stipulated values in the DIP switch settings also are 9,600 bps and 2 stop bits. C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, CQM1H CPUs, SRM1 The connection method depends upon the model of PLC being used, as shown in the following table. PLC model Connection method C200HS, CQM1 Connect to the CPU Unit’s built-in RS-232C port. C200HX/HG/HE(-Z)E • Connect to the CPU Unit’s built-in RS-232C port. • Connect to one of the RS-232C ports (port A or port B) on a Serial Communications Board. CQM1H • Connect to the CPU Unit’s built-in RS-232C port. • Connect to the peripheral port through a CS1W-CN118 Connecting Cable. • Connect to the RS-232C port (port 1) on a Serial Communications Board. CPM1 Connect to the peripheral port through a CPM1-CIF01 RS-232C Adapter. • Connect to the CPU Unit’s built-in RS-232C port. • Connect to the peripheral port through a CPM1-CIF01 RS-232C Adapter. CPM2A, SRM1 CPM2C Connect to the CPU Unit’s RS-232C port or the peripheral port through a Connecting Cable (CPM2C-CN111, CS1W-CN118, or CS1W-CN114). (The CPM2C-CN111 splits the Unit’s Communication Port into a RS-232C port and a peripheral port. A CPM1-CIF01 RS-232C Adapter is also required to connect to this peripheral port.) 60 Section Connecting to the RS-232C Port at the Host 4-1 PLC Setup Area Settings When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, or CQM1H CPU, or SRM1, set the following communication conditions for the PLC Setup area. Item Setting at Host Communication mode Host link mode Communications speed Set the same speed as set at the NT31/NT31C(*1) Stop bit 2 stop bits Parity Even Data length ASCII 7 bits Unit # 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT31/NT31C. For details, refer to Settings the Host Link Method (page158). Set the PLC Setup area settings directly from a Programming Device (e.g. the CX-Programmer support software). For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used. The PLC Setup area word numbers and settings to be made depending on the unit and port to which the connection is made are shown below. CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection Word # Writing Value Settings DM6650 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6651 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6653 C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than the CPU11), or SRM1: Built-in RS-232C port connection Word # Writing Value Settings DM6645 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6646 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6648 C200HX/HG/HE(-Z)E: Serial Communications Board port A CQM1H: Serial Communications Board port 1 Word # Writing Value Settings DM6555 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6556 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6558 61 Section Connecting to the RS-232C Port at the Host 4-1 C200HX/HG/HE(-Z)E: Serial Communications Board port B Word # Writing Value Settings DM6550 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6551 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6553 CPM1: Peripheral port connection through a CPM1-CIF01 RS-232C Adapter Word # Writing Value Settings DM6650 0001 Host link mode Communication conditions set by the contents of DM DM6651 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6653 Connecting to a CPM2C The CPM2C PLCs do not have the same kind of port connectors found on CSseries PLCs. The CPM2C’s communication port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details. Port connecting to PT PLC Setup RS-232C port (D-Sub 9-pin) of CPM2C-CN111 Built-in RS-232C port settings Peripheral port of CPM2C-CN111 Peripheral port settings RS-232C port (D-Sub 9-pin) of CS1W-CN118 Built-in RS-232C port settings Peripheral port of CS1W-CN114 Peripheral port settings Peripheral port CPM2C-CN111 RS-232C port (D-Sub 9-pin, female) CPM2C CS1W-CN118 CPM2C RS-232C port (D-Sub 9-pin, female) CS1W-CN114 CPM2C Peripheral port Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1, or CQM1H When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup area (data memory) effective. C200HX/HG/HE(-Z)E CQM1 CQM1H RS-232C port communication condition setting Set DIP SW5 to OFF to make the settings made in PLC Setup effective. 62 Section Connecting to the RS-232C Port at the Host 4-1 When using the CQM1H’s built-in peripheral port, turn ON SW7. Setting the Switches of a CPM2A When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective. Set the Communications switch to OFF (down position). Setting the Switches of a CPM2C When using a CPM2C, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective. The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS-232C port. Connecting PT to peripheral port Connecting PT to built-in RS-232C port (A device that requires non-standard communications settings is connected to the peripheral port.) SW1: OFF SW2: ON Connecting PT to built-in RS-232C port (A Programming Console is connected to the peripheral port.) SW1: OFF SW2: OFF Setting the Switches on an RS-232C Adapter When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown in the following diagram. CPM1CIF01 CPM1 Set the mode setting switch to HOST (upper position). 63 Section Connecting to the RS-232C Port at the Host 4-1 CS-series CPU type : CS1G/H-CPU-E (-V1) Connect to the built-in RS-232C port of the CPU, or the RS-232C port of the communication board. Note that the connection to a peripheral port must be made via an RS-232C adapter (CS1W-CN118) specially designed for connecting to a peripheral port. PLC Setup When connecting to a CS-series CPU, set the following communication conditions for the PLC Setup area. Since the settings shown below are the PLC default settings for the CPU, no change to the PLC Setup is necessary as long as the communication speed is maintained at 9600 bps. Item Setting at Host Communication speed Set the same speed as set at the NT31/NT31C(*1) Stop bits 2 stop bits Parity Even Data length ASCII 7 bits Unit No. for the host link 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT31/NT31C. For details, refer to Settings the Host Link Method (page 158). When the communication speed is set to 19200 bps, the PLC Setup of the CPU need to be changed. Either set the PLC Setup directly from a Programming Device (Programming Console), or transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU. For details on PLC Setup, refer to the SYSMAC CS-series Operation Manual (W339-E1-). When using the built-in RS-232C port of CS1G/H Word # 160 161 166 Writing Value Settings 8000 Host link mode, data length 7 bits, 2 stop bits, even parity 0000 Communication speed: 9600 bps. 0007 Communication speed: 19200 bps. 0000 Unit #00 When using the peripheral port of CS1G/H Word # 144 145 150 64 Writing Value Settings 8000 Host link mode, data length 7 bits, 2 stop bits, even parity 0000 Communication speed: 9600 bps. 0007 Communication speed: 19200 bps. 0000 Unit #00 Section Connecting to the RS-232C Port at the Host 4-1 Setting the Front Switches Set the CPU DIP switches to 4 or 5 in accordance with the port NT31/NT31C is connected to. RUN ERR/ALM INH PRPHL/COMM SYSMAC CS1G PROGRAMMABLE CONTROLLER CPU42 Peripheral port DIP switches (inside the battery storage) OPEN This is used mainly for connection to the Programming Device. (This also supports the RS-232C unit connection.) MCPWR BUSY OPEN • Set SW4 to ON (establishing communication in accordance with PLC Setup) when connecting the NT31/NT31C to the peripheral port. • Set SW5 to OFF (establishing communication in accordance with PLC Setup) when connecting the NT31/NT31C to the RS-232C port. PERIPHERAL RS-232 port This is used mainly for connection to the RS-232C unit. (This also supports the CX-Programmer.) PORT Connecting to CS-series Serial Communications Board Serial Communications Board equipped with a RS-232C port for CS-series CPU Units: CS1W-SCB41/21 Allocation DM Area Settings for CPU Unit Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU. After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. In the following, the channel numbers of the allocation DM area and the settings are shown. Allocation DM area (CH) Port 1 Port 2 DM32000 DM32010 DM32001 DM32011 DM32002 DM32006 Writing Value Settings 8000 Host link mode, 2 stop bits, even parity, data length 7 bits 0000 Communication speed 9600 bps. 0007 Communication speed 19200 bps. DM32012 0000 Transmit delay time 0 ms. DM32016 0000 No CTS control Unit No.0 for host link When Using the NT Link (1:1) Method Compatible Host Units Some models and series of OMRON PLCs have the NT link (1:1) function built in. With CQM1H PLCs, a Serial Communications Board can be added to provide 1:1 NT Link communications. Some C200HX/HG/HE(-Z)E CPUs can be connected by the NT link (1:1) method by installing a Communication Board. Check the model and series of the PLC against the type of CPU before making the connections. 65 Section Connecting to the RS-232C Port at the Host 4-1 The host units that can be connected to the NT31/NT31C by the NT link (1:1) method using the RS-232C ports of both units are indicated in the table below. PLC Series CPUs with Built-in NT Link Function C200HS-CPU21-E, -EC C200HS-CPU23-E C200HS-CPU31-E C200HS-CPU33-E CPUs Connectable with Expansion Communication Board(*1) Connectable to --C200HS C200HE-CPU42-(Z)E C200HE-CPU32-(Z)E C200HE-CPU42-(Z)E C200HE (-Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HG-CPU33-(Z)E C200HG-CPU43-(Z)E C200HG-CPU53-(Z)E C200HG-CPU63-(Z)E C200HG (-Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E X200HX-CPU65-ZE C200HX-CPU85-ZE C200HX-CPU34-(Z)E C200HX-CPU44-(Z)E C200HX-CPU54-(Z)E C200HX-CPU64-(Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE C200HX (-Z)E CPM1-10CDR- (*2) CPM1-20CDR- (*2) CPM1-30CDR- (*2) CPM1A-10CD- (*2) CPM1A-20CD- (*2) CPM1A-30CD- (*2) CPM1A-40CD- (*2) --- CPM2A-30CD- CPM2A-40CD- CPM2A-60CD- --- CPM2C-10- (*3) CPM2C-20- (*3) --- CQM1-CPU41-EV1 CQM1-CPU42-EV1 CQM1-CPU43-EV1 CQM1-CPU44-EV1 CQM1-CPU45-EV1 --- CQM1H-CPU21-E CQM1H-CPU51-E CQM1H-CPU61-E CQM1H-CPU51 (*4) CQM1H-CPU61 (*4) CQM1H CV500-CPU01-EV1 --- CV500 CV1000-CPU01-EV1 --- CV1000 CV2000-CPU01-EV1 --- CV2000 --- (*5) CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 CompoBus/S master control unit SRM1-C02-V1 C series CV series (*5) CVM1 series CPM1 CPM2A CPM2C CQM1 CVM1 --SRM1 *1 One of the following communication boards is required: C200HW-COM02/COM04/COM05/COM06-EV1. *2 A CPM1-CIF01 adapter is required. *3 Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect. *4 A CQM1H-SCB41 Serial Communications Board is required. *5 CPUs of CVM1/CV series PLCs without the suffix -EV cannot be connected. Reference: CS-series CPU cannot be connected with the 1:1 connection NT link method. Use the 1:N connection NT link method (standard or high-speed) instead to make the 1:1 connection. For details, refer to Using the NT Link (1:N) Method (page 70) or Using the High-speed NT Link (1:N) Method (page 73). 66 Section Connecting to the RS-232C Port at the Host 4-1 Settings at The Host The setting methods for each unit are as follows: Connecting to a C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, CQM1H, or SRM1 PLC Setup Area Settings Write the PLC Setup area (data memory) settings directly from a Programming Device (e.g. SYSMAC support software) in accordance with the host model and port. Host Model Word # RS-232C port of C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H, SRM1 Port A of C200HX/HG/HE(-Z)E (*1) Port 1 of CQM1H (*2) Writing Value Setting DM6645 4000 DM6555 Port B of C200HX/HG/HE(-Z)E (*1) DM6550 CPM1 DM6650 Use NT link (1:1) *1 RS-232C port of the Communication Board *2 RS-232C port of the Serial Communications Board For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used. Connecting to a CPM2C The CPM2C PLCs do not have the same kind of port connectors found on CSseries PLCs. The CPM2C’s communication port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details. Port connecting to PT PLC Setup RS-232C port (D-Sub 9-pin) of CPM2C-CN111 Built-in RS-232C port settings Peripheral port of CPM2C-CN111 Peripheral port settings RS-232C port (D-Sub 9-pin) of CS1W-CN118 Built-in RS-232C port settings Peripheral port of CS1W-CN114 Peripheral port settings Peripheral port CPM2C-CN111 RS-232C port (D-Sub 9-pin, female) CPM2C CS1W-CN118 CPM2C RS-232C port (D-Sub 9-pin, female) CS1W-CN114 CPM2C Peripheral port Setting the DIP Switches on the Front of a C200HX/HG/HE(-Z)E, CQM1, CQM1H When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on 67 Section Connecting to the RS-232C Port at the Host 4-1 the front panel must be set as shown below in order to make the settings in the PLC Setup area (data memory) effective. C200HX/HG/HE(-Z)E CQM1 CQM1H RS-232C port communication condition setting Set DIP SW5 to OFF to make the settings made in PLC Setup effective. Setting the Switches of a CPM2A When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective. Set the Communications switch to OFF (down position). Setting the Switches of a CPM2C When using a CPM2C, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective. The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS-232C port. Connecting PT to peripheral port Connecting PT to built-in RS-232C port (A device that requires non-standard communications settings is connected to the peripheral port.) SW1: OFF SW2: ON Connecting PT to built-in RS-232C port (A Programming Console is connected to the peripheral port.) SW1: OFF SW2: OFF Setting the Switches on an RS-232C Adapter When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown in the following diagram. CPM1CIF01 Set the mode setting switch to NT (lower position). 68 Section Connecting to the RS-232C Port at the Host 4-1 Connecting to CVM1/CV Series (-EV) Set the DIP switches on the front panel as follows. I/O port selection (selector switch) Set this to RS-232C. DIP switch setting (SW3) 6 5 4 3 2 1 OFF Set SW3 to use NT link (ON, right side). ON ON When using the CVM1/CV series, CPU execution processing (execution control 2) in the PLC Setup must be set to Simultaneous processing. 69 Section Connecting to the RS-232C Port at the Host 4-1 Using the NT Link (1:N) Method Compatible Host Units The OMRON PLCs that can be connected using the NT link (1:N) method are the CS-series CS1G/H and the C-series C200HX/HG/HE(-Z)E, CQM1H, and SRM1 only. With the CS-series PLCs, it is possible to connect a 1:N NT Link using a CS1W-SCU21 Serial Communications Unit. Check the model and series of the PLC as well as the model of Serial Communications Board or Unit being used before making the connections. The host units that can be connected to the NT31/NT31C by the NT link (1:N) method using the RS-232C ports of both units are indicated in the table below. CPUs with Built-in NT Link Function PLC Series CS series C series CompoBus/S Master Control Unit CPUs Connectable with Communications Board or Unit(*1) Connectable to CS1G-CPU42/43/44/ CS1G-CPU42/43/44/ CS1G 45-EV1 45-EV1 CS1H CS1H-CPU63/64/65/ CS1H-CPU63/64/65/ 66/67-EV1 66/67-EV1 C200HE-CPU42-(Z)E C200HE-CPU32-(Z)E(*2) C200HE-CPU42-(Z)E(*2) C200HE (-Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HG-CPU33-(Z)E(*2) C200HG-CPU43-(Z)E(*2) C200HG-CPU53-(Z)E(*2) C200HG-CPU63-(Z)E(*2) C200HG (-Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE C200HX-CPU34-(Z)E(*2) C200HX-CPU44-(Z)E(*2) C200HX-CPU54-(Z)E(*2) C200HX-CPU64-(Z)E(*2) C200HX-CPU65-ZE(*2) C200HX-CPU85-ZE(*2) C200HX (-Z)E --- CQM1H-CPU51(*3) CQM1H-CPU61(*3) CQM1H SRM1-C02-V2 --- SRM1 *1 A CS1W-SCB21 or CS1W-SCB41 Serial Communication Board or CS1W-SCU21 Serial Communications Unit is required. *2 One of the following Communication Boards is required: C200HW-COM02/COM04/COM05/COM06 (-EV1) *3 A CQM1H-SCB41 Serial Communication Board is required. Reference: The -V1 versions of CS-series PLCs support the high-speed 1:N NT Link as well as the standard 1:N NT Link. Furthermore, the high-speed 1:N NT Link can be used in earlier versions of CS-series PLCs by installing a new version of Serial Communications Board or Unit. For details, refer to Using the High-speed NT Link (1:N) Method (page 73). Settings at the Host The Settings required for each Unit are described below. • Connecting a C-series C200HX/HG/HE(-Z)E, CQM1H, or SRM1 PLC Setup Area Settings Write the PLC Setup area (data memory) settings directly from a Programming 70 Section Connecting to the RS-232C Port at the Host 4-1 Device (e.g. SYSMAC support software) in accordance with the host model and port. Connection to Word # C200HX/HG/HE(-Z)E, SRM1 Writing Value Setting DM6645 Built-in RS-232C port Use NT link (1:N) = highest unit number of the connected PTs (1 to 7) C200HX/HG/HE(-Z)E Communication Board port A*1 DM6555 500 CQM1H port 1*2 ((*3)) C200HX/HG/HE(-Z)E Communication Board port B*1 DM6550 *1 RS-232C port on the Communications Board *2 RS-232C port on the Serial Communications Board *3 When using a C200HE (-Z)E, the maximum PT unit number is 3. Refer to the PLC’s operation manual for details on changing PLC Setup settings. Setting the DIP Switches of a C200HX/HG/HE(-Z)E When using a C200HX/HG/HE(-Z)E, the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup area (data memory) effective. RS-232C port communication condition setting Set DIP SW5 to OFF to make the settings made in PLC Setup effective. Connecting to CS-series CPU Units CS-series CPU Unit: CS1G/H-CPU-E(V1) The PT is connected to the built-in RS-232C port on the CPU Unit or an RS-232C port on a Communications Board. It can also be connected to the peripheral port on the CPU Unit, but a CS1W-CN118 Peripheral Port Connecting Cable must be used. Connect to the built-in RS-232C port on the CPU Unit or to an RS-232C port on a Communications Board. A special Peripheral Port Connecting Cable (CS1WCN118) can be used to connect to the peripheral port. PLC Setup When connecting to a CS-series CPU, set the following communication conditions for the PLC Setup area, in accordance with the communication port to be used. When using the built-in RS-232C port of CS1G/H Word # 160 Writing Value 8200 161 0000 to 0009 166 000 Settings NT link (1:N) mode (*1) Communications baud rate (standard) = The largest model number of the connected PT (0 – 7) *1 Set any value between 0000 and 0009 Hex for the communications baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex. 71 Section Connecting to the RS-232C Port at the Host 4-1 When using the peripheral port of CS1G/H Word # 144 Writing Value 8200 Settings NT link (1:N) mode 145 0000 to 0009 150 000 (*1) Communications baud rate (standard) = The largest model number of the connected PT (0 – 7) *1 Set any value between 0000 and 0009 Hex for the communications baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex. When connecting PT with its model number 0, 2-5 to the built-in RS-232C port, for example, set the value 8200 Hex to 160 CH, and 0005 Hex to 166CH. Either set PLC Setup directly from a Programming Device (Programming Console), or transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU. For details on PLC Setup, refer to the SYSMAC CS-series Operation Manual (W339-E1-). Setting the Front Switches Set the CPU DIP switch to 4 or 5 in accordance with the port NT31/NT31C is connected to. RUN ERR/ALM INH PRPHL/COMM SYSMAC CS1G PROGRAMMABLE CONTROLLER CPU42 DIP switches (inside the battery storage) Peripheral port OPEN This is used mainly for connection to the Programming Device. (This also supports the RS-232C unit connection.) RS-232 port MCPWR OPEN BUSY • Set SW4 to ON (establishing communication in accordance with PLC Setup) when connecting the NT31/NT31C to the peripheral port. • Set SW5 to OFF (establishing communication in accordance with PLC Setup) when connecting the NT31/NT31C to the RS-232C port. PERIPHERAL This is used mainly for connection to the RS-232C unit. (This also supports the CX-Programmer.) PORT Connecting to CS-series Serial Communications Board Serial Communications Board equipped with a RS-232C port for CS-series CPU Units: CS1W-SCB41/21 CPU Allocation DM Area Settings Setting is written from the Programming Device (a Programming Console or CXProgrammer) directly into the allocation DM area (system setting area) of the CPU. After the setting is written, it becomes effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. 72 Section Connecting to the RS-232C Port at the Host 4-1 In the following, the channel numbers of the allocation DM area and settings are shown. Allocation DM area (CH) Port 1 Port 2 DM32000 DM32010 Writing Value 8200 DM32001 DM32011 0000 to 0009 DM32006 DM32016 000 Settings NT link (1:N) mode (*1) Communications baud rate (standard) = The largest model number of the connected PT (0 – 7) *1 Set any value between 0000 and 0009 Hex for the communications baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex. When connecting PTs with model numbers 3 to 6 to port 1, for example, set the value 8200 Hex to DM32000, 0000 Hex to DM32001, and 0006 Hex to DM32006. Connecting to CS Series Serial Communication Unit A CS series backplane mounted type : CS1W-SCU21 Setting the Front Switches Set the unit number of the serial communication unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following. SCU21 RDY ERH SD2 RD2 RUN ERC SD1 RD1 UNIT No. 32410 FE D C 567 9AB 8 Set the unit number to 0 through F so that it will not overlap with the numbers used in other units. Allocation DM Area Settings for CPU Setting is written from the Programming Device (a Programming Console or CXProgrammer) directly into the allocation DM area (system setting area) of the CPU. After the setting is written, it becomes effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. In the following, the channel numbers of the allocation DM area and settings are shown. m=DM30000+100*unit number (CH) Allocation DM area (CH) Port 1 m Port 2 m+10 Writing Value 8200 m+1 m+11 0000 to 0009 m+6 m+16 000 Settings NT link (1:N) mode (*1) Communications baud rate (standard) = The largest model number of the connected PT (0 - 7) *1 Set any value between 0000 and 0009 Hex for the communications baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex. Using the High-speed NT Link (1:N) Method Compatible Host Units Only the -V1 versions of OMRON’s CS1H and CS1G PLCs support the highspeed 1:N NT Link directly. Other CS-series PLCs can use the high-speed 1:N NT Link indirectly through a CS1W-SCU21 Serial Communications Unit. (If a Serial Communications Unit is used, even CS-series Units without the “-V1” suffix can be connected via high-speed 1:N NT Link.) 73 Section Connecting to the RS-232C Port at the Host 4-1 Be sure to check the model number of the PLC and Serial Communications Board/Unit before trying to establish the high-speed 1:N NT Link. The following table shows which CS-series PLCs can be connected to an NT31/NT31C with the high-speed 1:N NT Link. CPU Units with Built-in NT Link Function CPUs Connectable only through a Serial Communication Board or Unit CS1G-CPU42/43/44/45-EV1 (*1) CS1H-CPU63/64/65/66/67-EV1 (*1) CS1G-CPU42/43/44/45-E(V1) (*2) CS1H-CPU63/64/65/66/67-E(V1) (*2) *1 The high-speed 1:N NT Link is not supported in a direct connection to the CPU Unit of a CS-series PLC without the -V1 suffix. *2 A CS1W-SCB21 or CS1W-SCB41 Serial Communication Board or CS1W-SCU21 Serial Communications Unit is required. Settings at the Host The Settings required for each Unit are described below. • Connecting CS-series CPU Units CS series CPU type : CS1G/H-CPU-EV1 Connect to the built-in RS-232C port on the CPU Unit or to an RS-232C port on a Communications Board. A special Peripheral Port Connecting Cable (CS1WCN118) can be used to connect to the peripheral port. PLC Setup When connecting to a CS series CPU, set the following communication conditions for the PLC Setup area, in accordance with the communication port to be used. When using the built-in RS-232C port of CS1G/H Word # Writing Value Settings 160 8200 NT link (1:N) mode 161 000A Communications baud rate (high-speed) 166 000 = The largest model number of the connected PT (0 – 7) When using the peripheral port of CS1G/H Word # Writing Value Settings 144 8200 NT link (1:N) mode 145 000A Communications baud rate (high-speed) 150 000 = The largest model number of the connected PT (0 – 7) When connecting PTs with model numbers 0, 2, 3, 4, and 5 to the built-in RS-232C port, for example, set the value 8200 Hex to word 160, 000A Hex to word 161, and 0005 Hex to word 166. Either set PLC Setup directly from a Programming Device (Programming Console), or transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU. For details on PLC Setup, refer to the SYSMAC CS-series Operation Manual (W339-E1-). Reference: When using the CX-Programmer to set the high-speed 1:N NT Link, set the communications baud rate to 115,200 bps. 74 Section Connecting to the RS-232C Port at the Host 4-1 Setting the Front Switches Set the CPU DIP switch to 4 or 5 in accordance with the port NT31/NT31C is connected to. RUN ERR/ALM INH PRPHL/COMM SYSMAC CS1G PROGRAMMABLE CONTROLLER CPU42 DIP switches (inside the battery storage) Peripheral port OPEN This is used mainly for connection to the Programming Device. (This also supports connection of RS-232C devices.) MCPWR BUSY OPEN • Set SW4 to ON (establishing communication in accordance with PLC Setup) when connecting the NT31/NT31C to the peripheral port. • Set SW5 to OFF (establishing communication in accordance with PLC Setup) when connecting the NT31/NT31C to the RS-232C port. PERIPHERAL RS-232 port This is used mainly for connection of RS-232C devices. (This also supports the connection of CX-Programmer.) PORT Connecting to a CS-series Serial Communications Board Serial Communications Board equipped with a RS-232C port for CS-series CPU Units: CS1W-SCB41/21 Reference: Serial Communications Boards and Serial Communications Units with lot number 991220 (12/20/99) and later support the high-speed 1:N NT Link. Boards and Units with earlier lot numbers cannot be used. CPU Allocation DM Area Settings Setting is written from the Programming Device (a Programming Console or CXProgrammer) directly into the allocation DM area (system setting area) of the CPU. After the setting is written, it becomes effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. In the following, the channel numbers of the allocation DM area and settings are shown. Allocation DM area (CH) Writing Value Settings Port 1 Port 2 DM32000 DM32010 8200 NT link (1:N) mode DM32001 DM32011 000A Communications baud rate (high-speed) DM32006 DM32016 000 = The largest model number of the connected PT (0 – 7) For example, when connecting PTs with model numbers 3, 4, 5, and 6 to port 1, set the value 8200 Hex to DM32000, 000A Hex to DM32001, and 0006 Hex to DM32006. Connecting to a CS-series Serial Communication Unit A CS-series backplane mounted type : CS1W-SCU21 Reference: Serial Communications Boards and Serial Communications Units with lot number 991220 (12/20/99) and later support the high-speed 1:N NT Link. Boards and Units with earlier lot numbers cannot be used. 75 Section Connecting to the RS-232C Port at the Host 4-1 Setting the Front Switches Set the unit number of the serial communication unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following. SCU21 RDY ERH SD2 RD2 RUN ERC SD1 RD1 UNIT No. 32410 FE D C 567 9AB 8 Set the unit number to 0 through F so that it will not overlap with the numbers used in other units. Allocation DM Area Settings for CPU Setting is written from the Programming Device (a Programming Console or CXProgrammer) directly into the allocation DM area (system setting area) of the CPU. After the setting is written, it becomes effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. In the following, the channel numbers of the allocation DM area and settings are shown. Word m = DM30000 + (100 × unit number) Allocation DM area (CH) Port 1 When Using the Memory Link Method Port 2 Writing Value Settings m m+10 8200 NT link (1:N) mode m+1 m+11 000A Communications baud rate (high-speed) m+6 m+16 000 = The largest model number of the connected PT (0 - 7) In the memory link method, the connection can be made to a personal computer with RS-232 and an FA computer, etc. When connecting to the host in the memory link method, it is necessary to create a program for the memory link at the host side. The following are the communication conditions that can be used in the memory link method. For the host (a personal computer, an FA computer, etc.), its setting should be compatible to one of the communication conditions listed in the following table. Set the same communication conditions at the NT31/NT31C by the memory switch. (page 163). Item 76 Settings at the host Input/Output port RS-232C Communication speed 1200, 2400, 4800, 9600, 19200, 38400 bps. Data bits length 7 bits, 8 bits Stop bits length 1 bits, 2 bits Parity None, even, odd Flow control None, RS/CS, XON/XOFF Section Connecting to the RS-232C Port at the Host 4-1 4-1-2 Connecting Directly between RS-232C Ports The method for connection between the RS-232C ports of the NT31/NT31C and the host is described here. Host link unit/CPU NT31/NT31C SYSMAC CS-series PLC C-series PLC, CVM1/CV-series PLC, SRM1 9-pin connector or 25-pin connector Serial port A (RS-232C, 9-pin type) Serial port B (RS-232C, 25-pin type) 9-pin connector Cable with RS-232C connectors Recommended Connector Cable When making the connector cable, as far as possible use the recommended connectors, connector hoods, and cables indicated in the table below. Some units come supplied with one connector and one connector hood. Check the required components and prepare them in advance. Name Model Remarks Delivered with CS-series CS1G/CS1H XM2A-0901 9-pin Made by OMRON C-series CQM1, C200HS, C200HX/HG/HE(-Z)E, CVM1/CV-series CPUs CV500-LK201 Connector XM24-2501 25-pin Made by OMRON C500-LK203 CV500-LK201 C200H-LK201-EV1 DB-25P 25-pin Made by JAE 3G2A5-LK201-EV1 3G2A6-LK201-EV1 C-series CQM1, C200HS, XM2S-0911 9-pin Made by OMRON C200HX/HG/HE-(Z)E, CVM1/CV-series CPUs CV500-LK201 Connector hood Cable XM2S-0913 9-pin Made by OMRON XM2S-0911-E 9-pin Made by OMRON XM2S-2511 25-pin Made by OMRON C500-LK203 CV500-LK201 C200H-LK201-EV1 DB-C2-J9 25-pin Made by JAE 3G2A5-LK201-EV1 3G2A6-LK201-EV1 AWG28 5P IFVV-SB Multi-core shielded cable Made by Fujikura, Ltd. CO-MA-VV-SB 5P 28AWG Multi-core shielded cable Made by Hitachi Cable, Ltd. CS-series CS1G/CS1H Note After connecting a communication cable, always secure it with the screws. 77 Section Connecting to the RS-232C Port at the Host 4-1 OMRON Cables with Connectors When a connection is made at serial port A in other than the memory link method, OMRON cables with connectors shown below are available. Model Cable Length XW2Z-200S 2m XW2Z-500S 5m XW2Z-200T 2m XW2Z-500T 5m Connector Specification 9 pin ⇔ 25 pin 9-pin 9 pin ⇔ 9-pin 9-pin 9 pin When a connection is made to a personal computer at serial port A in the memory link method, OMRON cable with connectors shown below are available. Model Cable Length Connector Specification CV500-CN228 2m 9-pin ⇔ 25 pin XW2Z-S002 2m 9-pin ⇔ 9 pin When a connection is made at serial port B in other than the memory link method, OMRON cables with connectors shown are available. Model Cable Length XW2Z-200P 2m XW2Z-500P 5m XW2Z-200S 2m XW2Z-500S 5m Connector Specification 25 pin ⇔ 25 pin 25-pin 25 pin ⇔ 9-pin 9 pin 25-pin Note The cable’s tensile load is 30 N. Do not subject it to loads greater than this. Wiring for a Host Link Unit (25-pin) Connection 78 Applicable units: C200H-LK201-EV1 3G2A5-LK201-EV1 C500-LK203 3G2A6-LK201-EV1 CV500-LK201 (communication port 1) Cables with connectors that can be used at serial port A: XW2Z-200S (9-pin ⇔ 25-pin, 2 m) XW2Z-500S (9-pin ⇔ 25-pin, 5 m) Cables with connectors that can be used at serial port B: XW2Z-200P (25-pin ⇔ 25-pin, 2 m) XW2Z-500P (25-pin ⇔ 25-pin, 5 m) CVM1/CV-series host link units (CV500-LK201) have two types of connector; a 25-pin connector (communication port 1), and a 9-pin connector (communication port 2). When using communication port 2, refer to Wiring for Other Connections (Other Than the Memory Link Method) (page79). Section Connecting to the RS-232C Port at the Host 4-1 Serial Port A 1 6 NT31/NT31C Abbreviation FG RS-232C interface Pin number Connector hood 9 Shielding wire Pin number Abbreviation 1 FG 1 2 SD SD 2 3 RD RD 3 4 RS RS 4 5 CS CS 5 +5V 6 5G 5 PLC (host link unit) * 6 – 7 5G 7 8 – 8 – – 9 – – (9-pin type) – – – ER 1 14 13 25 RS-232C interface (25-pin type) * For units that have a CTS setting selector switch, RS and CS do not have to be shorted if this switch is set to 0V. Serial Port B NT31/NT31C Abbreviation FG 1 14 RS-232C/ 422A/485 interface Pin number Connector hood PLC (host link unit) Shielding wire Pin number Abbreviation 1 FG – 1 2 SD SD 2 3 RD RD 3 4 RS RS 4 5 CS CS 5 – * 6 – 6 7 SG SG 7 8 – – 8 – – TRM – – RDB (+) 9 10 – – SDB (+) 11 – – – 12 20 ER – 13 – 14 SDA (–) 15 RDA (–) 16 1 14 13 25 RS-232C interface (25-pin type) – 13 25 – – RSB (+) 23 RSA (–) – 24 25 (25-pin type) * For units that have a CTS setting selector switch, RS and CS do not have to be shorted if this switch is set to 0V. Wiring for Other Connections Applicable units : CV500-LK201 (communication port 2) CS1W-SCU21 CPM1-10CDR- CPM1-20CDR- CPM1A-10CD- CPM1A-20CD- CPM1A-30CD- CPM1A-40CD- CPM2A-30CD- CPM2A-40CD- CPM2A-60CD- CPM2C-10- CPM2C-20- CQM1-CPU21-E CQM1-CPU41-EV1 CQM1-CPU42-EV1 CQM1-CPU43-EV1 CQM1-CPU44-EV1 CQM1H-CPU11 CQM1H-CPU21 CQM1H-CPU51 CQM1H-CPU61 CS1G-CPU42-E(V1) CS1G-CPU43-E(V1) 79 Section Connecting to the RS-232C Port at the Host 4-1 CS1G-CPU44-E(V1) CS1G-CPU45-E(V1) CS1H-CPU63-E(V1) CS1H-CPU64-E(V1) CS1H-CPU65-E(V1) CS1H-CPU66-E(V1) CS1H-CUP67-E(V1) C200HS-CPU21-E, -EC C200HS-CPU23-E C200HS-CPU31-E C200HS-CPU33-E C200HE-CPU32-(Z)E C200HE-CPU42-(Z)E C200HG-CPU33-(Z)E C200HG-CPU43-(Z)E C200HG-CPU53-(Z)E C200HG-CPU63-(Z)E C200HX-CPU34-(Z)E C200HX-CPU44-(Z)E C200HX-CPU54-(Z)E C200HX-CPU64-(Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE CV500-CPU01-EV1 CV1000-CPU01-EV1 CV2000-CPU01-EV1 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 SRM1-C02-V2 Cables with connectors that can be used at serial port A: XW2Z-200T (9-pin ⇔ 9-pin, 2 m) XW2Z-500T (9-pin ⇔ 9-pin, 5 m) Cables with connectors that can be used at serial port B: XW2Z-200S (25-pin ⇔ 9-pin, 2 m) XW2Z-500S (25-pin ⇔ 9-pin, 5 m) CPUs of CVM1/CV-series PLCs without the suffix -EV cannot be connected by any connection method. When connecting to the peripheral port of a CS-series CPU Unit, a CS1WCN118 Connecting Cable is required in addition to the above cables. Serial Port A 1 6 NT31/NT31C Pin Abbreviation number Connector FG hood RS-232C interface 5 80 9 PLC (Host link unit) Shielding wire Pin number Abbreviation 1 FG – 1 2 SD SD 2 3 RD RD 3 4 RS RS 4 CS 5 +5V – 5 CS 6 +5V 6 7 7 8 DSR ER – 8 9 SG 9 (9-pin type) * 1 6 5 9 RS-232C interface SG (9-pin type) Section Connecting to the RS-232C Port at the Host 4-1 Serial Port B NT31/NT31C 1 13 14 25 PLC (Host link unit) Shielding wire Abbreviation FG FG – 1 1 – SD 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS – 6 6 – SG 7 7 – – 8 8 – TRM 9 SG RDB (+) 9 10 SDB (+) 11 – 12 – 13 – 14 SDA (–) 15 RDA (–) 16 * 1 6 5 9 (9-pin type) – – – RSB (+) 23 RSA (–) – 24 25 (25-pin type) * In case 0V is set for those unit which has CTS setting selector, it is not necessary to shorten between RS and CS. Wiring for a Memory Link Connection Cables with connectors that can be used at serial port A: CV500-CN228 (9-pin⇔25-pin, 2 m) XW2Z-S002 (9-pin⇔9-pin, 2 m) Serial Port A Prepare the adapter cable while referring to the following diagram. NT31/NT31C 1 6 Abbreviation Pin number RS-232C connector 5 9 PLC (Host link unit) Shielding wire Abbreviation Connector hood FG Connector hood − 1 SD SD 2 RD RD 3 RS RS 4 CS CS 5 SG +5V 6 − 7 − 8 SG 9 RS-232C connector (9-pin type) 81 Section Connecting to the RS-232C Port at the Host Serial Port B Prepare the adapter cable while referring to the following diagram. NT31/NT31C 1 Abbreviation Pin number 14 25 Connector hood Connector hood – 1 SD SD 2 RD RS-232C /422A/485 RD 3 RS connector RS 4 CS CS 5 SG – 6 SG 7 – 8 TRM 9 10 SDB (+) 11 – 12 – 13 – 14 SDA (–) 15 RDA (–) 16 – – – RSB (+) 23 RSA (–) – 24 25 (25-pin type) 82 Abbreviation FG RDB (+) 13 PLC (Host link unit) Shielding wire RS-232C connector 4-1 SECTION 5 Connecting to the Host from the RS-422A/485 Port This section describes the method for connecting to the host using the RS-422A/485 port of the PT. 5-1 5-2 Connecting to the Host’s RS-232C Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-1 The Type of Host and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-2 1:1 Connection between RS-422A/485 at the PT and RS-232C at the Host . . . . . 5-1-3 1:N Connection between RS-422A/485 at the PT and RS-232C at the Host . . . . 5-1-4 Recommended Connectors, Cables, and Crimp Terminals . . . . . . . . . . . . . . . . . . 5-1-5 Setting the Terminal Resistance for RS-422A/485 Communications . . . . . . . . . . Connecting to the Host’s RS-422A/485 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2-1 Host Types and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2-2 Direct Connection between RS-422A Ports at Both Units . . . . . . . . . . . . . . . . . . 5-2-3 Direct Connection between RS-485 Ports at Both Units . . . . . . . . . . . . . . . . . . . . 5-2-4 1:N Connection among RS-422A Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2-5 1:N Connection among RS-485 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2-6 Recommended Connectors, Cables and Crimp Terminals . . . . . . . . . . . . . . . . . . 5-2-7 Setting the Terminal Resistance for RS-422A/485 Communications . . . . . . . . . . 5-2-8 Handling the Shield on RS-422A/485 Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 85 86 90 95 97 98 99 115 119 120 123 125 126 127 83 Section Connecting to the Host’s RS-232C Port 5-1 5-1 Connecting to the Host’s RS-232C Port The methods for connecting the RS-422A/485 port of the NT31/NT31C and the RS-232C port of the host are described here. There are the following methods. The following discussion is focused on the connection method to OMRON PLCs (By using the memory link method, a connection can be made to any arbitrary RS-232 unit). When making a connection to a host other than OMRON PLCs, refer to the PLC Connection Manual (V042-E1-) or NT31/631 Multi Vendor Connection Manual (V060-E1-). • Method in which the RS-422A port of the NT31/NT31C and the RS-232C port of the host are connected in a 1:1 connection via an RS-232C/RS-422A convertor unit (page 86). When this method is used, the cable length can be extended up to 500 m. PT RS-232C/RS-422A convertor unit RS-422A cable (max. 500 m) Host RS-232C cable (max. 2 m) • Method in which the RS-485 port of the NT31/NT31C and the RS-232C port of the host are connected in a 1:1 connection via an RS-232C/RS-422A convertor unit (page 86). When this method is used, the cable length can be extended up to 500 m. This connection method can be used only with the NT link (1:N) method of type RS-485. PT RS-232C/RS-422A convertor unit RS-485 cable (max. 500 m) Host RS-232C cable (max. 2 m) • Method in which the RS-422A ports of multiple NT31/NT31Cs and the RS-232C port of the host are connected in a 1:N connection via an RS-232C/RS-422A convertor unit (page 90). This connection method is used with the RS-422A type NT link (1:N) method. PT RS-232C/RS422A convertor unit RS-422A cable (max. total length 500 m) Host RS-232C cable (max. 2 m) • Method in which the RS-485 ports of multiple NT31/NT31Cs and the RS-232C port of the host are connected in a 1:N connection via an RS-232C/RS-422A convertor unit (page 90). This connection method is used with the RS-485 type NT link (1:N) method (standard or high-speed). PT RS-232C/RS422A convertor unit RS-485 cable (max. total length 500 m) 84 RS-232C cable (max. 2 m) Host Section Connecting to the Host’s RS-232C Port 5-1 Note One end of the wire must always be connected to the host (PLC), and there must be no branching. Branching will cause problems such as transmission delays and communication failures. PLC PLC (At termination) PLC Relay terminal block Relay terminal block Max. 2 m NT31C NT31 NT31 (Not at (Not at termination) termination) (Not at termination) NT31 NT31 NT31C NT31 NT31 NT31C NT31 (At termination) Example of Good Connection Examples of Bad Connections Reference: CS-series CPUs cannot be connected with the 1:1 connection NT link method. Use the 1:N connection NT Link method (standard or high-speed) instead to make the 1:1 connection. For details, refer to Using the NT link (1:N) method (page 70) or Using the High-speed NT link (1:N) method (page 73). 5-1-1 The Type of Host and Settings The using condition is the same as the connecting PT side RS-232C and the host side RS-232C. For the available type and settings of the host, refer to the pages listed below. Method Reference Host link Host Link Method (page 52) NT link (1:1) NT Link (1:1) method (page 65) NT link (1:N) Using the NT Link (1:N) Method (page 70) High-speed NT link (1:N) Using the High-speed NT Link (1:N) Method (page 73) Memory link Memory Link Method (page 76) 85 Section Connecting to the Host’s RS-232C Port Settings at the RS-232C/RS-422A Convertor Unit (NT-AL001) 5-1 When making a connection between RS-232C and RS-422A/485 ports using an RS-232C/RS-422A convertor unit, set the DIP switches on the NT-AL001 as follows. Example: the terminal resistor is active, RS-422A, NT link (1:N). ON 1 2 3 4 5 6 omR on NT-AL001 Built-in terminal resistor setting (DIP SW1-2) If at the end of the RS-422A/485 cable, set this switch to ON (to activate the built-in terminal resistor). If not at the end of the RS-422A/485 cable, set this switch to OFF (to inactivate the built-in terminal resistor). 2-wire type/4-wire type selection (DIP SW1-3, SW1-4) For RS-422A, set both of these switches to OFF (4-wire type). For RS-485, set both of these switches to ON (2-wire type). Selection of RS-422A/485 send mode (DIP SW1-5, SW1-6) For host link or NT link (1:1), set both of these switches to OFF. (Always send) For NT link (1:N), set SW1-5 to OFF and SW1-6 to ON. (Sends when CS is H) Note Read the manual supplied with the NT-AL001 carefully before using the unit. 5-1-2 1:1 Connection between RS-422A/485 at the PT and RS-232C at the Host The connection method in which the RS-422A/485 port of an NT31/NT31C and the RS-232C port of a host are connected via a convertor unit is described here. An RS-232C/RS-422A convertor unit (NT-AL001) is used to convert between the RS-232C and RS-422A communication methods. Host link unit/CPU NT31/NT31C Serial port B (RS-422A/485, 25-pin type) SYSMAC C-series PLC, CVM1/CV-series PLC, SRM1 RS-232C/RS-422A convertor unit (NT-AL001) 25-pin connector RS-422A/485 cable (max. length: 500 m) RS-422A terminal block 9-pin connector or 25-pin connector RS-232C cable with connectors 9-pin connector Reference: When using RS-485 as a port for the NT31/NT31C, only NT link (1:N) method (standard or high-speed) can be used. 86 Section Connecting to the Host’s RS-232C Port 5-1 Connecting an NT31/NT31C and NT-AL001 (RS-422A) NT31/NT31C NT-AL001 Host RS-422A NT31/NT31C side 1 Abbreviation Pin number 14 RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 − 8 Shielding wire 8 7 6 connector 13 5 4 3 2 TRM 9 RDB (+) 10 6 RDA SDB (+) 11 5 RDB − 12 4 SDA − 13 3 SDB − 14 1 Functional ground SDA (−) 15 RDA (−) 16 25 1 NT-AL001 side Pin number Abbreviation RS-422A terminal block − − − RSB (+) 23 RSA (−) 24 − 25 (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Connecting an NT31/NT31C and NT-AL001 (RS-485) NT31/NT31C NT-AL001 Host RS-485 NT31/NT31C side Abbreviation Pin number 1 14 RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 − 8 8 7 6 connector 25 4 3 2 1 NT-AL001 side TRM 9 RDB (+) 10 6 RDA SDB (+) 11 5 RDB − 12 4 SDA − 13 3 SDB − 14 1 Functional ground SDA (−) 15 RDA (−) 16 − 13 5 − − RSB (+) 23 RSA (−) 24 − 25 Pin number Abbreviation RS-422A terminal block Shielding wire (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Reference: When using RS-485 as a port for the NT31/NT31C, only NT link (1:N) method (standard or high-speed) can be used. 87 Section Connecting to the Host’s RS-232C Port 5-1 Connecting an NT-AL001 and Host NT31/NT31C Host NT-AL001 RS-232C Wiring When Connecting a Host Link Unit (25-pin) Applicable units: C200H-LK201-V1 3G2A5-LK201-EV1 C500-LK203 3G2A6-LK201-EV1 CV500-LK201 (communication port 1) CVM1/CV-series host link unit (CV500-LK201) has two types of connector: a 25-pin connector (communication port 1), and a 9-pin connector (communication port 2). When using the communication port, refer to Wiring for Connections other than Memory Link (page 88). PLC (host link unit) side NT-AL001 side 1 Abbreviation Pin number 6 RS-232C connector FG Connector hood 9 Shielding wire Connector hood FG 1 FG − 1 2 SD SD 2 3 RD RD 3 4 RS RS 4 5 CS CS 5 6 − +5V 6 7 SG − 7 8 − − 8 − − SG 9 − − (9-pin type) 5 Abbreviation Pin number 1 14 13 25 RS-232C connector − − − 20 ER (25-pin type) Wiring for Connections Other Than Memory Link Applicable units: CV500-LK201 (communication port 2) CS1W-SCU21 CPM1-10CDR- CPM1A-10CD- CPM1A-30CD- CPM1-20CDR- CPM1A-20CD- CPM1A-40CD- CPM2A-30CD- CPM2A-40CD- CPM2A-60CD- CPM2C-10- CQM1-CPU21-E CQM1-CPU41-EV1 CQM1-CPU43-EV1 CPM2C-20- CQM1H-CPU11 CQM1H-CPU21 CQM1H-CPU51 CQM1H-CPU61 CS1G-CPU42-E(V1) CS1G-CPU43-E(V1) CS1G-CPU44-E(V1) CS1G-CPU45-E(V1) CS1H-CPU63-E(V1) CS1H-CPU64-E(V1) CS1H-CPU65-E(V1) CS1H-CPU66-E(V1) CS1H-CPU67-E(V1) 88 CQM1-CPU42-EV1 CQM1-CPU44-EV1 Section Connecting to the Host’s RS-232C Port C200HS-CPU21-E C200HS-CPU31-E C200HE-CPU32-E C200HG-CPU33-E C200HG-CPU53-E C200HX-CPU34-E C200HX-CPU54-E C200HS-CPU23-E C200HS-CPU33-E C200HE-CPU42-E C200HG-CPU43-E C200HG-CPU63-E C200HX-CPU44-E C200HX-CPU64-E C200HE-CPU32-ZE C200HE-CPU42-ZE C200HG-CPU33-ZE C200HG-CPU43-ZE C200HG-CPU53-ZE C200HG-CPU63-ZE C200HX-CPU34-ZE C200HX-CPU44-ZE C200HX-CPU54-ZE C200HX-CPU65-ZE CV500-CPU01-EV1 CV2000-CPU01-EV1 CVM1-CPU01-EV2 CVM1-CPU21-EV2 SRM1-C02-V2 C200HX-CPU64-ZE C200HX-CPU85-ZE CV1000-CPU01-EV1 5-1 CVM1-CPU11-EV2 Usable Cables with Attached Connectors: • For host link and 1:1 NT Link only (+5 V power wire attached) SJ45007-102 (9-pin to 9-pin, 0.7 m) SSJ45007-202 (9-pin to 9-pin, 2 m) • For host link, 1:1 NT Link, or 1:N NT Link (+5 V power supplied from PLC) XW2Z-070T-1 (9-pin to 9-pin, 0.7 m) XW2Z-200T-1 (9-pin to 9-pin, 2 m) SJ46006-102 (9-pin to 9-pin, 1 m) SSJ46006-202 (9-pin to 9-pin, 2 m) CVM1/CV-series CPUs whose model names do not have the suffix -EV cannot be connected by any connection method. When connecting to the peripheral port of a CS-series CPU Unit, a CS1WCN118 Connecting Cable is required in addition to the above cables. (Supply power to the +5 V output of the NT-AL001 from an external power supply when using this method.) 1 6 NT-AL001 side PLC side RS-232C connector 5 9 FG Connector hood − 1 1 − SD 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS +5V 6 6 (+5V) − 7 7 − − 8 8 − SG 9 9 SG (9-pin type) 1 6 Pin number Abbreviation Connector FG hood Abbreviation Pin number Shielding wire (9-pin type) RS-232C connector When there is no +5 V output at the PLC side 9 5 When using host link or NT link (1:1) When there is +5 V output at the PLC side When using NT link (1:N) • When using the host link or NT link (1:1) method, short the RS and CS terminals at the PLC side with each other (leave the RS and CS terminals at the NTAL001 side open). • When using the NT link (1:N), cross-connect the RS and CS terminals at the NT-AL001 and PLC sides. 89 Section Connecting to the Host’s RS-232C Port 5-1 If there is +5 V output at the PLC side, no external power supply is required for the NT-AL001. Wiring for a Memory Link Connection Prepare the adapter cable while referring to the diagram shown below. Host side NT-AL001 side 6 1 Abbreviation Abbreviation Pin number RS-232C connector FG Connector hood − 1 SD SD 2 RD RD 3 RS RS 4 CS CS 5 (+5V) +5V 6 SG − 7 − 8 SG 9 (9-pin type) Connector hood RS-232C connector Shielding wire 9 5 No +5 V output is at the host side A +5 V output is present at the host side Since it is necessary to input a voltage of +5 V to the number 6 pin of NT-AL001, supplying a voltage of 5 V from the host or an external voltage supply for NTAL001 is required. 5-1-3 1:N Connection between RS-422A/485 at the PT and RS-232C at the Host The connection method in which the RS-422A/485 ports of multiple NT31/NT31Cs are connected to the RS-232C port of one host in a 1:N connection is described here. An RS-232C/RS-422A convertor unit (NT-AL001) is used to convert between the RS-232C and RS-422A/485 communication methods. Host link unit/CPU NT31/NT31C CS1G/H C200HX/HG/HE(-Z)E Serial port B (RS-422A/485, 25-pin type) 25-pin connector RS-232C/RS-422A convertor unit (NT-AL001) 9-pin connector Relay terminal block Max. 2 m RS-232C cable with connectors RS-422A terminal block RS-422A/485 cable (max. total length: 500 m) 90 9-pin connector Section Connecting to the Host’s RS-232C Port 5-1 The relay terminal board is not included in the figure below. Insert a relay terminal board so as to achieve the wiring configuration indicated below. Connecting an NT31/NT31C and NT-AL001 (RS-422A) NT31/NT31C NT-AL001 Host RS-422A 1 14 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 Shielding wire 8 7 6 5 connector 13 25 − 6 SG 7 4 3 2 1 NT-AL001 side − 8 TRM 9 RDB (+) 10 6 RDA RDB (+) 11 5 RDB − 12 4 SDA − 13 3 SDB 1 Functional ground − 14 SDA (−) 15 RDA (−) 16 Pin number Abbreviation RS-422A terminal block − − − RSB (+) 23 RSA (−) 24 − 25 (25-pin type) Next PT For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 91 Section Connecting to the Host’s RS-232C Port 5-1 The relay terminal board is not included in the figure below. Insert a relay terminal board so as to achieve the wiring configuration indicated below. Connecting an NT31/NT31C and NT-AL001 (RS-485) NT31/NT31C NT-AL001 Host RS-485 1 14 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 connector 13 25 FG Connector hood − 1 Shielding wire 8 7 6 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 − 8 TRM 9 RDB (+) 10 6 RDA SDB (+) 11 5 RDB − 12 RS-422A terminal 4 SDA block − 13 3 SDB − 14 1 Functional ground SDA (−) 15 RDA (−) 16 5 4 3 2 1 NT-AL001 side Pin number Abbreviation − − − RSB (+) 23 RSA (−) 24 − 25 (25-pin type) Next PT For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 92 Section Connecting to the Host’s RS-232C Port 5-1 The relay terminal board is not included in the figure below. Insert a relay terminal board so as to achieve the wiring configuration indicated below. Connection between NT31/NT31C Units (RS-422A) NT31/NT31C Host NT-AL001 RS-422A 1 14 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 connector 13 25 Shielding wire Connector hood Connector hood − 1 1 − SD 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS − 6 6 − 7 7 SG 8 − 9 TRM 10 10 RDB (+) 11 11 RDB (+) − 12 12 − − 13 13 − − 14 14 − SDA (−) 15 15 SDA (−) RDA (−) 16 16 RDA (−) − − 8 9 RDB (+) RDB (+) − − − RSB (+) 23 23 RSB (+) RSA (−) 24 24 RSA (−) − 25 25 (25-pin type) 13 25 FG SG − 14 Pin number Abbreviation FG TRM 1 NT31/NT31C side RS-232C/ 422A/485 connector − − (25-pin type) *2 Make the connection between pin numbers 9 and 10 at the terminal NT31/NT31C (marked in the figure above) only. For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 93 Section Connecting to the Host’s RS-232C Port 5-1 The relay terminal board is not included in the figure below. Insert a relay terminal board so as to achieve the wiring configuration indicated below. Connection between NT31/NT31C Units (RS-485) NT31/NT31C Host RS-485 1 14 NT31/NT31C side NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 connector 13 25 Shielding wire FG Connector hood Connector hood − 1 1 − 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS − 6 6 − SG 7 7 SG − 8 8 − TRM 9 9 TRM RDB (+) 10 10 RDB (+) SDB (+) 11 11 SDB (+) − 12 12 − − 13 13 − − 14 14 − SDA (−) 15 15 SDA (−) RDA (−) 16 16 RDA (−) − − − 14 13 25 FG SD 1 Pin number Abbreviation − − RSB (+) 23 23 RSB (+) RSA (−) 24 24 RSA (−) − 25 25 RS-232C/ 422A/485 connector − (25-pin type) − (25-pin type) *2 Make the connection pin numbers 9 and 10 at the terminal NT31/NT31C (marked in the figure above). For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Connecting an NT-AL001 and Host NT31/NT31C Host NT-AL001 RS-232C Wiring when connecting a CS-series CS1G/H Serial Communications Board, CQM1H Serial Communications Board, or C-series C200HX/HG/HE(-Z)E Communications Board. Applicable PLCs: CS1G-CPU42-E(V1) CS1G-CPU44-E(V1) CS1H-CPU63-E(V1) CS1H-CPU65-E(V1) 94 CS1G-CPU43-E(V1) CS1G-CPU45-E(V1) CS1H-CPU64-E(V1) CS1H-CPU66-E(V1) Section Connecting to the Host’s RS-232C Port 5-1 CS1H-CPU67-E(V1) CQM1H-CPU51 C200HE-CPU32-(Z)E C200HG-CPU33-(Z)E C200HG-CPU53-(Z)E C200HX-CPU34-(Z)E C200HX-CPU54-(Z)E C200HX-CPU65-ZE CQM1H-CPU61 C200HE-CPU42-(Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E C200HX-CPU85-ZE Usable Cables with Attached Connectors: • For host link, 1:1 NT Link, or 1:N NT Link (+5 V power supplied from PLC) XW2Z-070T-1 XW2Z-200T-1 SJ46006-102 SSJ46006-202 1 6 NT-AL001 side PLC side Abbreviation Pin number RS-232C connector 5 9 (9-pin to 9-pin, 0.7 m) (9-pin to 9-pin, 2 m) (9-pin to 9-pin, 1 m) (9-pin to 9-pin, 2 m) Shielding wire FG Connector hood Connector hood − 1 1 − SD 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS +5V 6 6 +5V − 7 7 − − 8 8 − SG 9 9 SG (9-pin type) 6 1 Pin number Abbreviation FG RS-232C connector (9-pin type) 9 5 Since the CS1G/H, CQM1H, and C200HX/HG/HE(-Z)E have a +5 V output, no external power supply is required for the NT-AL001. 5-1-4 Recommended Connectors, Cables, and Crimp Terminals Connectors and Cables Recommended for RS-232C When making an RS-232C connecting cable, as far as possible use the recommended parts indicated in the table below. Some units come supplied with one connector and connector hood. Check the required parts and prepare them in advance. Name Model Remarks Delivered with XM2A-0901 9-pin type Made by OMRON CS-series CS1G/H C-series CQM1, C200HS, C200HX/HG/HE(-Z)E CVM1/CV-series CPUs CV500-LK201 XM2A-2501 25-pin type Made by OMRON C500-LK203 3G2A5-LK201-EV1 C200H-LK201-V1 DB-25P 25-pin type Made by JAE 3G2A5-LK201-EV1 3G2A6-LK201-EV1 Connector 95 Section Connecting to the Host’s RS-232C Port Name Connector hood Model Delivered with XM2S-0911 9-pin type Made by OMRON C-series CQM1, C200HS, C200HX/HG/HE(-Z)E CVM1/CV-series CPUs CV500-LK201 XM2S-0913 Made by OMRON 9-pin --- XM2S-0911-E Made by OMRON 9-pin CS series CS1G/CS1H XM2S-2511 25-pin type Made by OMRON C500-LK203 3G2A5-LK201-EV1 C200H-LK201-V1 25-pin type DB-C2-J9 Cable Remarks 5-1 3G2A5-LK201-EV1 3G2A6-LK201-EV1 Made by JAE AWG28 5P IFVV-SB Multi-core shielded cable --Made by Fujikura, Ltd. CO-MA-VV-SB 5P 28AWG Multi-core shielded cable --Made by Hitachi, Ltd. Cables with Connectors Made by OMRON When connecting an NT-AL001 and a PLC, use the OMRON cables with connectors indicated in the table below. Model Cable Length XW2Z-070T-1 0.7 m 2m XW2Z-200T-1 Connector Specification 9-pin ⇔ 9-pin Host link, NT link (1:1), NT link (1:N) +5 V power supplied from PLC (Use when the PLC has a +5 V output.) Note The maximum tensile load of the recommended cable is 30 N. Do not exceed this load. • After connecting a connecting cable, always tighten the connector screws. • Recommended connectors, cables and crimp terminals for RS-422A/485 When making an RS-422A/485 connecting cable, as far as possible use the recommended parts indicated in the table below. Some units come supplied with one connector and connector hood. Check the required parts and prepare them in advance. Name Model Maker XM2A-2501 25-pin type Made by OMRON Delivered with the following units: C500-LK203 DB-25P F-N 25-pin type Made by JAE Delivered with the following units: 3G2A6-LK201-EV1 3G2A5-LK201-EV1 XM2S-2511 25-pin type Made by OMRON Delivered with the following units: C500-LK203 Connector Connector hood DB-C2-J9 Cable 96 Remarks TKVVBS4P-03 25-pin type Made by JAE Tachii Electric Wire Co., Ltd. Delivered with the following units: 3G2A6-LK201-EV1 3G2A5-LK201-EV1 Section Connecting to the Host’s RS-232C Port Name Crimp terminals Model Maker 5-1 Remarks 1.25-N3A (fork type) Japan Solderless Terminal MFG Y1.25-3.5L (fork type) Molex Inc. Recommended cable size: AWG22 to t 18 (0.3 to 0.75 mm2) The terminal screws of the NT-AL001 are M3 specification. When wiring, use crimp terminals for M3 use. Tighten terminal screws with a tightening torque of 0.5 N@m. Note Always use crimp terminals for wiring. Examples of applicable terminals Round type Fork type 6.2 mm or less 6.2 mm or less 5-1-5 Setting the Terminal Resistance for RS-422A/485 Communications The serial port B connector of the NT31/NT31C has a terminal resistance setting terminal (TRM). In RS-422A/485 communications, a terminal resistor must be set at the device at the end of the communication cable, but not at any other device. The NT31/NT31C has a built-in terminal resistor, and whether or not the terminal resistance is applied is set by the wiring at the terminal resistance setting terminals (pins No. 9 and 10 of serial port B). The terminal resistance is 120 Ω. When carrying out RS-422A/485 communications using serial port B, short between terminals No. 9 and 10 at the NT31/NT31C at the end of the RS-422A/485 cable. Leave terminals No. 9 and 10 open at NT31/NT31C units other than the one at the end of the cable. When not using RS-422A/485 communications, the terminal resistance setting is ineffective. In order to set the terminal resistance, wiring work is required at the cable’s connector: carry out the wiring correctly by referring to APPENDIX E Making the Cable, page 267. Abbreviation Pin number FG Connector hood - - TRM 9 RDB (+) 10 SDB (+) 11 - 12 Terminal resistor setting - Pin Nos. 9 and 10 25 Function Terminal resistance is applied. Shorted Short only at the NT31/NT31C connected to the end of an RS-422A/485 cable. Terminal resistance is not applied. Open Leave the terminals open when connecting an NT31/NT31C anywhere other than at the end of the RS-422A/485 cable. Note Before connecting or disconnecting cables between devices, make sure that the power supply to all of the connected devices (NT31/NT31C, PLC, etc.) is OFF. 97 Section Connecting to the Host’s RS-422A/485 Port Reference: 5-2 The internal circuit of the NT31/NT31C is shown below. + − 10 (RDB) 16 (RDA) Terminal resistor (120 Ω) Making a connection here inserts a terminator between + (RDB) and − (RDA). 9 (TRM) For details on setting the terminal resistance of NT-AL001-E, refer to Settings at the RS-232C/RS-422A Convertor Unit (NT-AL001-E) (page 86). 5-2 Connecting to the Host’s RS-422A/485 Port The methods for connecting the RS-422A/485 port of the NT31/NT31C and the RS-422A/485 port of the host are described here. There are the following methods. The following discussion is focused on the connection method to OMRON PLCs (By using the memory link method, a connection can be made to any arbitrary RS-422 unit). When making a connection to a host other than OMRON PLCs, refer to the PLC Connection Manual (V042-E1-) or Multi Vendor Connection Manual (V060-E1-). • Method in which the RS-422A ports of the NT31/NT31C and host are connected directly by an RS-422A cable (page 115). When this method is used, the cable length can be extended up to 500 m. PT Host RS-422A cable (max. 500 m) • Method in which the RS-485 ports of the NT31/NT31C and host are connected by an RS-485 cable (page 119). When this method is used, the cable length can be extended up to 500 m. This connection method can be used only with the NT link (1:N) method (standard or high-speed) of type RS-485. PT Host RS-485 cable (max. 500 m) • Method in which the RS-422A ports of multiple NT31/NT31Cs and the RS-422A port of the host are connected in a 1:N connection (page 120). This connection method is used with the RS-422A type NT link (1:N) method (standard or high-speed). PT Host RS-422A cable (max. total length 500 m) • Method in which the RS-485 ports of multiple NT31/NT31Cs and the RS-485 port of the host are connected in a 1:N connection (page 123). 98 Section Connecting to the Host’s RS-422A/485 Port 5-2 This connection method is used with the RS-485 type NT link (1:N) method (standard or high-speed). PT Host RS-485 cable (max. total length 500 m) Note One end of the wire must always be connected to the host (PLC), and there must be no branching. Branching will cause problems such as transmission delays and communication failures. PLC PLC (At termination) PLC Relay terminal block Relay terminal block Max. 2 m NT31C NT31 NT31 (Not at (Not at termination) termination) (Not at termination) NT31 NT31 NT31C NT31 NT31 NT31C NT31 (At termination) Example of Good Connection Examples of Bad Connections Reference: CS-series CPUs cannot be connected with the 1:1 connection NT link method. Use the 1:N connection NT link method (standard or high-speed) instead to make the 1:1 connection. For details, refer to Using the NT link (1:N) Method (page 111) or Using the High-speed NT link (1:N) Method (page 113). 5-2-1 Host Types and Settings The types of host that have an RS-422A port and can be connected to the RS-422A/485 port of the NT31/NT31C, and the settings to be made at the host, are described here. When Using the Host Link Method Compatible Host Units Some models and series of OMRON PLCs have the RS-422A/485 type host link function built in. With the CS-series and CQM1H, the host link method can be used by installing a serial communication board. In addition, some C200HX/HG/ HE(-Z)E devices have an integral CPU that can be connected in the host link method by installing a communication board. With the CPM2A and CPM2C, an RS-422A type of 1:1 NT Link can be created through a CPM1-CIF11 RS-422A Adapter. Check the model and series of the PLC and the type of the installed Board or Unit before making a connection. 99 Section Connecting to the Host’s RS-422A/485 Port 5-2 The host units featuring the RS-422A/485 type host link function and can be connected to the RS-422A/485 port of the NT31/NT31C are indicated in the table below. Units with Built-in Host Link Function PLC Series CS series Host Link Unit / Communication Board CPUs Connectable with Host Link Units or Expansion Communication Board CPU CS1W-SCB41-E CS1G-CPU42/43/44/45-EV1 CS1H-CPU63/64/65/66/67-EV1 CS1G CS1H 3G2A6-LK202-EV1 C1000H-CPU01-EV1 C2000H-CPU01-EV1 C1000H C2000H C200H-LK202-V1 C200HS-CPU01/03/21/23/31/33-E C200HS-CPU01/21-EC C200HE-CPU11/32/42-E C200HE-CPU11/32/42-ZE C200HG-CPU33/43/53/63-E C200HG-CPU33/43/53/63-ZE C200HX-CPU34/44/54/64-E C200HX-CPU34/44/54/64/65/85-ZE C200HS C200HE C200HE-ZE C200HG C200HG-ZE C200HX C200HX-ZE C200HE-CPU32/42-E C200HE-CPU32/42-ZE C200HE C200HE-ZE C200HG-CPU33/43/53/63-E C200HG-CPU33/43/53/63-ZE C200HG C200HG-ZE C200HX-CPU34/44/54/64-E C200HX-CPU34/44/54/64/65/85-ZE C200HX C200HX-ZE 3G2A5-LK201-EV1 C1000H-CPU01-EV1 C2000H-CPU01-EV1 C1000H C2000H C500-LK203 C1000H-CPU01-EV1 C2000H-CPU01-EV1 C1000H C2000H C200HW-COM03/06-EV1 C series CPM1-10/20/30CDR- +CPM1-CIF11 CPM1 CPM1A-10/20/30/40CD- +CPM1-CIF11 CPM2A-30/40/60CD- +CPM1-CIF11 (Peripheral port connection) CPM2A CPM2C-10/20- (*1) CQM1H-SCB41 CV series i ((*2) 2) CVM1 series (*2) SRM1 Connectable to CV500-LK201 CV500-LK201 CPM2C CQM1H-CPU51/61 CQM1H CV500-CPU01-EV1 CV500-CPU01-EV1 CV500 CV1000-CPU01-EV1 CV1000-CPU01-EV1 CV1000 CV2000-CPU01-EV1 CV2000-CPU01-EV1 CV2000 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 CVM1 SRM1-C02-V1+CPM1-CIF11 SRM1 *1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect. *2: CPUs of CVM1/CV-series PLCs without the suffix -EV cannot be connected. The host link method cannot be used when an NT31/NT31C is connected using RS-485. To use the host link method, connect by RS-422A. Settings at the Host When using the RS-422A type host link method, the settings shown below must be made at the host (depending on the unit, some of these settings may not be necessary, or settings not shown here may be necessary). Item 100 Setting at Host I/O port RS-422A Communications speed Set the same speed as for the NT31/NT31C. (*1) Transfer code ASCII, 7 data bits, 2 stop bits Section Connecting to the Host’s RS-422A/485 Port Item 5-2 Setting at Host Parity Even 1-to-1/1-to-N 1-to-N(*2) Instruction level Level 1, 2, 3 Unit # 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 156). *2 The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT31/NT31C in a single host link. The setting methods for each type of unit are described in the following. Connecting to a C Series Host Link Unit C200H/C200HS/C200HE(-Z)E/C200HG(-Z)E/C200HX(-Z)E Backplane mounting type: C200H-LK201-V1 Setting the Front Switches Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following: LK201 XMT RUN RCV ERROR SW1 @ Unit # (SW1, SW2) Set these switches to 0. SW2 0 0 5 2 SW3 SW4 @ Instruction level, parity, and transfer code (SW4) Set this switch to 2. @ Communications speed (SW3) Set this switch to 5 to select 9600 bps. Set this switch to 6 to select 19200 bps. Setting the Rear Switches @ Terminator setting (selector switch) Set this switch to ON. Terminator ON OFF 1-to-1 (ON) 1-to-N (OFF) @ 1-to-1/1-to-N protocol selection (selector switch) Set this switch to 1-to-N (OFF). 101 Section Connecting to the Host’s RS-422A/485 Port 5-2 C1000H/C2000H rack-mounting type: 3G2A5-LK201-EV1 Setting the Front Switches Mode selector Host Local @ Mode selector (key switch) Set this to Host link. Setting the Rear Switches @ I/O port selection (selector switch) Set this to RS-422A. I/O port 8 RS-422A RS-232C 7 6 5 SW1 4 Synchronization 3 2 Internal External @ Unit # (DIP SW1) Set SW1-1 to SW1-5 to OFF (0). 1 ON Terminator @ Synchronization (selector switch) Set this to Internal. 8 7 OFF ON 6 5 4 CTS 3 0V External 2 1 ON SW2 @ Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19200 bps. Set these switches to 1010 to select 9600 bps. (0: OFF 1: ON) @ 1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N). @ Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.) @ CTS selection (selector switch) Set this always to 0V (ON). @ Terminator setting (selector switch) Set this switch to ON. 102 Section Connecting to the Host’s RS-422A/485 Port 5-2 C1000H/C2000H rack-mounting type: C500-LK203 Setting the Rear Switches @ I/O port selection (selector switch) Set this to RS-422A. 5V supply ON OFF 8 SW1 @ Unit #, parity, and transfer code (DIP SW1-1 to SW1-7) Set SW1-1 to SW1-7 to OFF (0). 7 I/O port 6 RS-422A RS-232C 5 4 3 2 Synchronization Internal External 1 ON Terminator 8 OFF ON 7 6 5 4 CTS 3 0V External 2 1 ON @ Synchronization (selector switch) Set this to Internal. SW2 @ Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19,200 bps. Set these switches to 1010 to select 9,600 bps. (0: OFF 1: ON) @ 1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N). @ Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.) @ CTS selection (selector switch) Set this always to 0V (ON). @ Terminator setting (selector switch) Set this switch to ON. C200H/C1000H/C2000H CPU mounting type: 3G2A6-LK202-EV1 Setting the Rear Switches @ Unit #, parity, and transfer code (DIP SW1-1 to SW1-5) Set SW1-1 to SW1-5 to OFF (0). * Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits. @ Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19,200 bps. Set these switches to 1010 to select 9,600 bps. (0: OFF 1: ON) SW1 SW2 @ 1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N). SW3 @ Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.) @ Terminator setting (DIP SW3-1 to SW3-6) Set SW3-1, SW3-3, and SW3-5 to ON (1). Set SW3-2, SW3-4, and SW3-6 to OFF (0). (Set terminator ON.) 103 Section Connecting to the Host’s RS-422A/485 Port 5-2 Connecting to a CVM1/CV Series Host Link Unit CVM1/CV series rack-mounting type: CV500-LK201 A CVM1/CV series host link unit (CV500-LK201) has two connectors (communication ports 1 and 2). To use the RS-422A type host link method, set communication port 2 to RS-422A. Communication port 2 is a 9-pin connector which allows selection of the RS-232C or RS-422A method. When this port is used with the RS-422A method, the I/O port selector switch on the front of the unit must be set to RS-422A (the lower position). CPU Bus Unit Settings When connecting to a CVM1/CV series host link unit, set the following communication conditions for the CPU bus unit settings. Item Setting at Host Communications speed Set the same speed as for the NT31/NT31C. (*1) Transfer code ASCII, 7 data bits, 2 stop bits Parity Even 1-to-1/1-to-N 1-to-N(*2) Instruction level Level 1, 2, 3 *1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 156). *1 The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT31/NT31C in a single host link. Set the CPU bus unit settings directly from a Programming Device (e.g. SYSMAC support software). For details on the CPU bus unit settings, refer to the SYSMAC CVM1/CV-series Host Link Unit Operation Manual (W205-E1-). 104 Section Connecting to the Host’s RS-422A/485 Port 5-2 Setting the Front Switches @ Unit # (SW3, SW4) Set these switches to 0. Communications port 1 (RS-232C) Communications port 2 (RS-232C/RS-422A) I/O port selector switch @ I/O port selection (selector switch) Set this to RS-422A. RS-232C RS-422A @ Communication condition setting (DIP SW1) Set this switch to OFF. Communication is executed in accordance with the CPU bus unit system settings made at the PLC. The initial values for the system settings are as follows. - Communications speed: 9,600 bps - Parity: Even - Xon/Xoff control: Not executed - Communication method: Full duplex - Stop bits: 2 stop bits - Data length: 7 bits @ Terminator setting (selector switch) Set this to ON. Connecting to a CPU Unit CVM1/CV-series (-EV) CPUs • CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1 • CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2 PLC Setup When connecting to a CVM1/CV series CPU, set the following communication conditions for the PLC Setup. Item Setting at Host Communications speed Set the same speed as for the NT31/NT31C. (*1) Stop bit 2 stop bits Parity Even Data length ASCII 7 bits Unit # 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 156). Either set PLC Setup directly from a Programming Device (e.g. SYSMAC support software), or transmit the PLC Setup made at a Programming Device to the CPU. For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/CV1000/ CV2000 Operation Manual: Ladder Diagrams (W202-E1-). 105 Section Connecting to the Host’s RS-422A/485 Port 5-2 Setting the Front Switches @ Host link communication method selection (selector switch) Set this to RS-422A. @ Communication type setting (DIP SW3) Set SW3 to OFF. (for host link communication) I/O port selector switch RS-232C RS-422A @ Host link default value settings (DIP SW4) To effect the existing DIP switch settings, set SW4 to ON. To effect the values set in the PLC Setup, set SW4 to OFF. Note For CPUs manufactured before or during June 1995 (lot No. 65), the existing DIP switch settings differ from the PLC Setup default values as follows. - Existing DIP switch settings: 2,400 bps, 1 stop bit, even parity, 7 bit data length - PLC Setup default values: 9,600 bps, 2 stop bits, even parity, 7 bit data length For CPUs manufactured from July 1995 onward (lot No. 75), the stipulated values in the DIP switch settings also are 9600 bps and 2 stop bits. @ Terminator setting (DIP SW6) Set this switch to ON. (Set terminator ON.) C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1H, or SRM1 The connection method depends upon the model of PLC being used, as shown in the following table. PLC model Connection method C200HX/HG/HE(-Z)E • Connect to the RS-422A port (port A) on a Communications Board. • Connect to the RS-422A port (port 2) on a Serial Communications Board. • Connect to the peripheral port through a CPM1-CIF11 RS-422A Adapter. • Connect to the peripheral port through a CPM1-CIF11 RS-422A Adapter. • Connect to the peripheral port (on a CPM2C-CN111 or CS1W-CN114 Connecting Cable) through a CPM1-CIF11 RS-422A Adapter. CQM1H CPM1 CPM2A, SRM1 CPM2C (The CPM2C-CN111 splits the Unit’s Communication Port into a RS-232C port and a peripheral port.) Reference: There are no Communication Boards for the C200HX/HG/HE(-Z)E in which port B is the RS-422A port. There are no Serial Communication Boards for the CQM1H in which port 1 is the RS-422A port. PLC Setup Area Settings When connecting to a C200HX/HG/HE(-Z)E or CPM1, CPM2A, CPM2C, 106 Section Connecting to the Host’s RS-422A/485 Port 5-2 CQM1H CPUs or SRM1, set the following communication conditions for the PLC Setup area. Item Setting at Host I/O port RS-422A Communication mode Host link mode Communications speed Set the same speed as for the NT31/NT31C. (*1) Stop bit 2 stop bits Parity Even Data length ASCII 7 bits Unit # 00 *1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 156). Set the PLC Setup area settings directly from a Programming Device (e.g. CXProgrammer). For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used. The PLC Setup area word numbers and settings to be made depending on the unit to which the connection is made are shown below. When using port A of the communication board of C200HX/HG/HE(-Z)E Word # Writing Value Settings DM6555 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6556 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6558 When using a CPM1, CPM2A, CPM2C, SRM1 Word # Writing Value Settings DM6650 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6651 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6653 When using a CQM1H Word # Writing Value Settings DM6550 0001 Host link mode, no CTS control Communication conditions set by the contents of DM DM6551 0303 Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps 0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps 0000 Unit # 00 DM6553 107 Section Connecting to the Host’s RS-422A/485 Port 5-2 Connecting to a CPM2C The CPM2C PLCs do not have the same kind of port connectors found on CSseries PLCs. The CPM2C’s communication port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details. Peripheral port CPM2C-CN111 CPM2C CPM2C CS1W-CN114 Peripheral port RS-232C port (D-Sub 9-pin, female) Setting Switches on a C200HX/HG/HE(-Z)E Communications Board Set the switches on a C200HX/HG/HE(-Z)E communication board as follows. Switch 1: Set to 4 (4-wire type, for RS-422A) Switch 2 : Set to ON for terminator ON (termination resistance applied) Setting Switches on a CQM1H Serial Communications Board Set the switches on a CQM1H Serial Communications Board as follows. Wire selection (WIRE): Set to 4 (4-wire type, for RS-422A) Terminator (TERM): Set to ON for termination ON. Serial Communications Board (Inner Board slot 1) Terminator Switch (TERM) Set to ON (right side). Wire Selection Switch (WIRE) Set to 4 (right side). Setting the Switches on an RS-422A Adapter CPM1CIF11 CPM1 Set the terminator selector switch to ON (upper position). Connecting to a CS-series Serial Communications Board Serial Communications Board with RS-422A/485 port equipped for CS-series CPU Type : CS1W-SCB41 (The port 2 is RS-422A/485 port.) Allocation DM Area Settings for CPU Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU. After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communication port, or executing the STUP command. In the following, the channel numbers of the allocation DM area and the settings are shown. 108 Section Connecting to the Host’s RS-422A/485 Port Allocation DM area (CH) Writing Value 5-2 Settings Port 2 DM32010 8000 Host link mode, 2 stop bits, data length 7 bits, even parity, DM32011 0000 Communication speed 9600 bps. 0007 Communication speed 19200 bps. DM32012 0000 Transmit delay time 0 ms. DM32016 0000 No CTS control Unit No.0 for host link Using the NT Link (1:1) Method Compatible Host Units Some models and series of OMRON PLCs have the RS-422A type NT link (1:1) function built in. • The C200HX/HG/HE(-Z)E CPUs can be connected by the RS-422A type NT link (1:1) method by installing a Communications Board. • The CQM1H CPUs can be connected by the RS-422A type NT link (1:1) method by installing a Serial Communications Board. Check the model and series of the PLC against the type of CPU before making the connections. The host units that can be connected to the RS-422A port of the NT31/NT31C by the RS-422A type NT link (1:1) method are indicated in the table below. PLC Series C series CV series i ((*2) 2) CVM1 series (*2) CPUs with Built-in RS-422A type NT Link (1:1) Function Model Name C200HE-CPU32-(Z)E(*1) C200HE-CPU42-(Z)E(*1) C200HE (-Z)E C200HG-CPU33-(Z)E(*1) C200HG-CPU43-(Z)E(*1) C200HG-CPU53-(Z)E(*1) C200HG-CPU63-(Z)E(*1) C200HG (-Z)E C200HX-CPU34-(Z)E(*1) C200HX-CPU44-(Z)E(*1) C200HX-CPU54-(Z)E(*1) C200HX-CPU64-(Z)E(*1) C200HX-CPU65-ZE(*1) C200HX-CPU85-ZE(*1) C200HX (-Z)E CQM1H-CPU51/61 CQM1H CV500-CPU01-EV1 CV500 CV1000-CPU01-EV1 CV1000 CV2000-CPU01-EV1 CV2000 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 CVM1 *1 One of the following communication boards is required: C200HW-COM03-EV1 or C200HW-COM06-EV1. *1 A CQM1H-SCB41 Serial Communication Board is required. *1 CPUs of CVM1/CV series PLCs without the suffix -EV cannot be connected. The NT link (1:1) method cannot be used using RS-485. To use the NT link (1:1) method, connect by RS-422A. NT link connection using RS-422A/485 is not possible with CPM1. Settings at the Host The setting methods for each type of unit are described in the following. 109 Section Connecting to the Host’s RS-422A/485 Port 5-2 • Connecting to a CVM1/CV-series (-EV) CPUs • CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1 • CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2 PLC Setup When connecting to the CVM1/CV series CPU by the NT link (1:1) method, no particular settings are required at the PLC Setup. Setting the Front Switches @ Host link communication method selection (selector switch) Set this to RS-422A. I/O port selector switch RS-232C @ Communication type setting (DIP SW3) Set this switch to ON. (for communication by NT link) RS-422A @ Terminator setting (DIP SW6) Set this switch to ON. (Set terminator ON.) Connecting to a C-series C200HX/HG/HE(-Z)E or CQM1H PLC Setup Area Settings Write the PLC Setup area (data memory) settings directly from a Programming Device (e.g. CX-Programmer) in accordance with the host model. Word # Writing Value Setting Port A of C200HX/HG/HE(-Z)E*1 Host Model DM6555 4000 Use NT link ((1:1)) Port 2 of CQM1H*2 DM6550 4000 *1 RS-422A port of the communication board *1 RS-422A port of the Serial Communications Board For details on operations relating to the PLC Setup area, refer to the manual for the PLC you are using. Setting the DIP Switches on a C200HX/HG/HE(-Z)E Communication Board Set the switches on a C200HX/HG/HE(-Z)E communication board as follows. Switch 1: Set to 4 (4-wire type, for RS-422A) Switch 2 : Set to ON for terminator ON (termination resistance applied) Setting Switches on a CQM1H Serial Communications Board Set the switches on a CQM1H Serial Communications Board as follows. Wire selection (WIRE): Set to 4 (4-wire type, for RS-422A) 110 Section Connecting to the Host’s RS-422A/485 Port Terminator (TERM): 5-2 Set to ON for termination ON. Serial Communications Board (Inner Board slot 1) Terminator Switch (TERM) Set to ON (right side). Wire Selection Switch (WIRE) Set to 4 (right side). Using the NT Link (1:N) Method Compatible Host Units The OMRON PLCs that can be connected using the RS-422A/485 type NT link (1:N) method are the CS1G/H, C200HX/HG/HE(-Z)E, and CQM1H models only. A Serial Communications Board or a communications board must be installed to make the connection. Check the model and series of the PLC against the type of CPU or communications board before making the connections. The host units that can be connected to the RS-232C port of the NT31/NT31C by the RS-422A type NT link (1:N) function via a convertor are indicated in the table below. PLC Series CPUs with Built-in RS-422A type NT Link (1:N) Function CPU that becomes connectable by installing a communication board Model Name CS1G-CPU42/43/44/45-E(V1) CS series (*1) --- CS1H-CPU63/64/65/66/ 67-E(V1)(*1) CS1G CS1H --- C200HE-CPU32-(Z)E(*2) C200HE-CPU42-(Z)E(*2) C200HE (-Z)E --- C200HG-CPU33-(Z)E(*2) C200HG-CPU43-(Z)E(*2) C200HG-CPU53-(Z)E(*2) C200HG-CPU63-(Z)E(*2) C200HG (-Z)E --- C200HX-CPU34-(Z)E(*2) C200HX-CPU44-(Z)E(*2) C200HX-CPU54-(Z)E(*2) C200HX-CPU64-(Z)E(*2) C200HX-CPU65-ZE(*2) C200HX-CPU85-ZE(*2) C200HX (-Z)E --- CQM1H-CPU51/61(*3) CQM1H C series *1 The serial CS1W-SCB41-E communication board is required. *1 A C200HW-COM03-V1 or C200-COM06-V1 communication board is required. *1 A CQM1H-SCB41 Serial Communication Board is required. Settings at the Host C-series C200HX/HG/HE(-Z)E and CQM1H PLC Setup Area Settings Write the communication conditions directly into the PLC Setup area (data memory) using a Programming Device (e.g. CX-Programmer). Make the setting indicated in the word shown below. 111 Section Connecting to the Host’s RS-422A/485 Port Connection to Word # Writing Value Port A of a C200HX/ HG/HE(-Z)E*1 DM6555 500 Port 2 of a CQM1H*2 DM6550 500 5-2 Setting Use NT link (1:N) = highest g est unit u t number u be of o the t e connected PTs ((1 to 7))*3 *1 The Communications Board’s RS-422A/485 port *1 The Serial Communications Board’s RS-422A/485 port *1 When using C200HE(-Z)E, the maximum PT unit number is 3. For details on setting the PLC Setup area settings, refer to the PLC’s operation manual. Reference: There are no Serial Communication Boards for the C200HX/HG/HE(-Z)E in which port B is the RS-422A/485 port. There are no Serial Communication Boards for the CQM1H in which port 1 is the RS-422A/485 port. Setting the DIP Switches on a C200HX/HG/HE(-Z)E Communication Board Set the switches on a C200HX/HG/HE(-Z)E communication board as follows. Switch 1: Set to 4 (4-wire type, for RS-422A), or Set to 2 (2-wire type, for RS-485) Switch 2 : Set to ON for terminator ON (termination resistance applied) Setting Switches on a CQM1H Serial Communications Board Set the switches on a CQM1H Serial Communications Board as follows. Wire selection (WIRE): Set to 4 (4-wire type, for RS-422A) or Set to 2 (2-wire type, for RS-485) Terminator (TERM): Set to ON for termination ON. Serial Communications Board (Inner Board slot 1) Terminator Switch (TERM) Set to ON (right side) Wire Selection Switch (WIRE) When using RS-422A: Set to 4 (right side) for 4-wire type. When using RS-485: Set to 2 (left side) for 2-wire type. Connecting to CS-series Serial Communication Board Serial Communications Board with RS-422A/485 port equipped for CS-series CPU type : CS1W-SCB41 (The port 2 is RS-422A/485 port.) 112 Section Connecting to the Host’s RS-422A/485 Port 5-2 Setting the Front Switches RDY COMM1 COMM2 Port 1 RS-232C PORT1 Terminal resistance setting switch (TER) Set to ON (Terminal resistance is present.) (right side) OFF 2 Port 2 RS-422A/485 ON TERM 4 WIRE PORT2 (RS422/ RS485) Two wire type/four wire type changeover switch (WIRE) For RS-422A : 4 (4 wire type) (right side) For RS-485 : 2 (2 wire type) (left side) SCB41 Allocation DM Area Settings for CPU Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU. After settings are written, they become effective by turning the power ON, restarting the unit, restarting the communication port, or executing the STUP command. In the following, the channel numbers of the allocation DM area and settings are shown. Allocation DM area (CH) Writing Value Settings Port 2 DM32010 8200 NT link (1:N) mode DM32011 0000 to 0009 (*1) Communications baud rate (standard) DM32016 000 = The largest model number of the connected PT (0 – 7) *1 Set any value between 0000 and 0009 Hex for the communications baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex. For example, when connecting PTs with model numbers 3, 4, 5, and 6 to port 2 in the NT link (1:N), set a value of 8200 Hex for D32010, 0000 Hex for DM32011, and 0006 Hex for D32016. Using the High-speed NT Link (1:N) Method Compatible Host Units Only OMRON’s CS1H and CS1G PLCs support the high-speed 1:N NT Link through RS-422A/RS-485. The high-speed 1:N NT Link must be established through a CS1W-SCB41-E Serial Communications Board. (If a Serial Communications Board is used, even CS-series Units without the “-V1” suffix can be connected via high-speed 1:N NT Link.) Be sure to check the model number of the PLC and Board/Unit before trying to establish the high-speed 1:N NT Link. The following table shows which CS-series PLCs can be connected to an NT31/NT31C with the high-speed 1:N NT Link through RS-422A/RS-485. 113 Section Connecting to the Host’s RS-422A/485 Port 5-2 PLCs supporting direct connection to the CPU Unit PLCs supporting connection through a Serial Communication Board --- CS1G-CPU42/43/44/45-E(V1) (*1) CS1H-CPU63/64/65/66/67-E(V1) (*1) *1 A CS1W-SCB41 Serial Communication Board is required. Settings at the Host Connecting to a CS-series Serial Communications Board Serial Communications Board equipped with an RS-422A/485 port for CS-series CPU Units: CS1W-SCB41 (Port 2 is an RS-422A/485 port.) Reference: Serial Communications Boards and Serial Communications Units with lot number 991220 (12/20/99) and later support the high-speed 1:N NT Link. Boards and Units with earlier lot numbers cannot be used. Setting the Front Switches RDY COMM1 COMM2 Port 1 RS-232C PORT1 Terminator Switch (TERM) Set to ON (right side) OFF 2 ON TERM 4 WIRE PORT2 (RS422/ RS485) Port 2 RS-422A/485 Wire Selection Switch (WIRE) RS-422A: Set to 4 (right side) for 4-wire type. RS-485: Set to 2 (left side) for 2-wire type. SCB41 CPU Allocation DM Area Settings Setting is written from the Programming Device (a Programming Console or CXProgrammer) directly into the allocation DM area (system setting area) of the CPU. After the setting is written, it becomes effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command. In the following table, the relevant word addresses in the allocation DM area and settings are shown. Allocation DM area Port 2 Writing Value Settings DM32010 8200 NT link (1:N) mode DM32011 000A Communications baud rate (high-speed) DM32016 000 = The largest model number of the connected PT (0 – 7) For example, when connecting PTs with model numbers 3, 4, 5, and 6 to port 2, set the value 8200 Hex to DM32010, 000A Hex to DM32011, and 0006 Hex to DM32016. When using the Memory Link Method 114 With the memory link method, the connection can be made to a personal computer and an FA computer with RS-422A. Section Connecting to the Host’s RS-422A/485 Port 5-2 When connecting to the host with the memory link method, it is necessary to create a program for the memory link at the host side. The following are the communication conditions that can be used with the memory link method. For the host (a personal computer, an FA computer, etc.), its setting should be compatible to one of the communication conditions listed in the following table. Set the same communication conditions at the NT31/NT31C by the memory switch. (page 163). Item Setting at Host Input/Output board RS-422A Communication speed 1200, 2400, 4800, 9600, 19200, 38400 bps. Data bits length 7 bits, 8 bits Stop bits length 1 bit, 2 bits Parity None, even, odd Flow control None, XON/XOFF 5-2-2 Direct Connection between RS-422A Ports at Both Units The connection method in which the RS-422A ports of an NT31/NT31C and a host are connected is described here. Host link/CPU/ Communication unit NT31/NT31C SYSMAC CS-series PLC, C-series PLC, CVM1/CV-series PLC, SRM1 25-pin connector 9-pin connector or 25-pin connector Serial port B (RS-422A, 25-pin type) RS-422A cable with connectors (max. length: 500m) Connecting an NT31/NT31C and Host (RS-422A) NT31/NT31C Host RS-422A Wiring When Connecting a C-series Host Link Unit or CPM1 (Host Link) Applicable units: C200H-LK202-V1 3G2A5-LK201-EV1 115 Section Connecting to the Host’s RS-422A/485 Port 5-2 C500-LK203 3G2A6-LK202-EV1 1 14 6 1 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 PLC side − 6 Pin number Abbreviation SG 7 Connector hood FG − 8 1 RDB connector 13 25 TRM 9 2 − RDB (+) 10 3 − SDB (+) 11 4 − − 12 5 SDB − 13 6 RDA FG − 14 7 SDA (−) 15 8 − RDA (−) 16 9 SDA − − − RSB (+) 23 RSA (−) 24 − 25 RS-422A connector 9 5 (9-pin type) Shielding wire (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Wiring When Connecting CPM1, CPM2A, CPM2C, or SRM1 Applicable units: CPM1-10CDR- CPM1A-10CD- CPM1A-30CD- CPM2A-30CD- CPM2A-60CD- CPM2C-10- CPM1-20CDR- CPM1A-20CD- CPM1A-40CD- CPM2A-40CD- CPM2C-20- SRM1-C02-V2 Connect to the PLC through a CPM1-CIF11 RS-422A Adapter. NT31/NT31C side 1 14 Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 FG − 8 SG connector 13 25 PLC side Abbreviation FG SG TRM 9 SDB (+) RS-422A terminal RDB (+) 10 SDA (−) block SDB (+) 11 RDB (+) RDB − 12 RDA (−) RDA − 13 − 14 SDA (−) 15 RDA (−) 16 SDB SDA (9-pin type) − − − RSB (+) 23 RSA (−) 24 − 25 Shielding wire (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 116 Section Connecting to the Host’s RS-422A/485 Port 5-2 Wiring When Connecting a CS-series CS1G/H Serial Communications Board, C series C200HX/HG/HE(-Z)E Communication Board, CQM1H Serial Communications Board, or CVM1/CV-series Host Link Unit Applicable units: CS1G-CPU42-E(V1) CS1G-CPU44-E(V1) CS1H-CPU63-E(V1) CS1H-CPU65-E(V1) CS1H-CPU67-E(V1) C200HE-CPU32-(Z)E C200HG-CPU33-(Z)E C200HG-CPU53-(Z)E C200HX-CPU34-(Z)E C200HX-CPU54-(Z)E C200HX-CPU65-ZE CS1G-CPU43-E(V1) CS1G-CPU45-E(V1) CS1H-CPU64-E(V1) CS1H-CPU66-E(V1) C200HE-CPU42-(Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E C200HX-CPU85-ZE CQM1H-CPU51 CQM1H-CPU61 CV500-LK201 (communication port 2) 1 14 6 1 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 PLC side − 6 Pin number Abbreviation SG 7 Connector hood FG − 8 1 SDA TRM 9 2 SDB RDB (+) 10 3 − SDB (+) 11 4 − − 12 5 − − 13 6 RDA interface 13 25 − 14 7 − SDA (−) 15 8 RDB RDA (−) 16 9 − − − RSB (+) 23 RSA (−) 24 − 25 Shielding wire RS-422A interface 5 9 − (9-pin type) (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Wiring When Connecting a CVM1/CV-series CPU Applicable units: CV500-CPU01-EV1 CV2000-CPU01-EV1 CVM1-CPU01-EV CVM1-CPU21-EV CV1000-CPU01-EV1 CVM1-CPU11-EV 117 Section Connecting to the Host’s RS-422A/485 Port 5-2 CVM1/CV-series CPUs whose model names do not have the suffix -EV cannot be connected by any connection method. 1 14 6 1 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 Pin number Abbreviation SG 7 Connector hood FG − 8 1 SDA TRM 9 2 SDB RDB (+) 10 3 − SDB (+) 11 4 RS − 12 5 CS − 13 6 RDA connector 13 25 PLC (CPU) side − 14 7 − SDA (−) 15 8 RDB RDA (−) 16 − − 23 RSA (−) 24 − 25 9 5 − 9 − RSB (+) RS-422A connector (9-pin type) Shielding wire (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Wiring for a Memory Link Connection Prepare the adapter cable while referring to the following diagram. 1 14 NT31/NT31C side Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 Abbreviation SG 7 Connector hood − 8 SDA TRM 9 SDB RDB (+) 10 RS connector 13 25 Host side SDB (+) 11 CS − 12 ROA − 13 ROB − 14 SDA (−) 15 RDA (−) 16 RS-422A connector − − − RSB (+) 23 RSA (−) 24 − 25 Shielding wire (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 118 Section Connecting to the Host’s RS-422A/485 Port 5-2 5-2-3 Direct Connection between RS-485 Ports at Both Units The connection method in which the RS-485 ports of an NT31/NT31C and a host are connected is described here. NT31/NT31C CPU CS1G/H C200HX/HG/HE(-Z)E CQM1H 25-pin connector Serial port B (RS-485, 25-pin type) 9-pin connector RS-485 cable with connectors (max. length: 500 m) Reference: When RS-485 is used at the PT side, only the NT link (1:N) method (standard or high-speed) can be used. Connecting an NT31/NT31C and Host NT31/NT31C Host RS-485 Wiring When Connecting a CS-series CS1G/H Serial Communications Board and C Series C200HX/HG/HE(-Z)E Communications Board, or CQM1H Serial Communications Board Applicable units: CS1G-CPU42-E(V1) CS1G-CPU44-E(V1) CS1H-CPU63-E(V1) CS1H-CPU65-E(V1) CS1H-CPU67-E(V1) C200HE-CPU32-(Z)E C200HG-CPU33-(Z)E C200HG-CPU53-(Z)E C200HX-CPU34-(Z)E C200HX-CPU54-(Z)E CS1G-CPU43-E(V1) CS1G-CPU45-E(V1) CS1H-CPU64-E(V1) CS1H-CPU66-E(V1) C200HE-CPU42-(Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E 119 Section Connecting to the Host’s RS-422A/485 Port 1 14 C200HX-CPU65-ZE C200HX-CPU85-ZE CQM1H-CPU51 CQM1H-CPU61 6 1 NT31/NT31C side 5-2 Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 − 8 1 SDA (−) TRM 9 2 SDB (+) RDB (+) 10 3 − SDB (+) 11 4 − − 12 5 − − 13 6 RDA (−) connector 13 25 PLC (CPU) side Shielding wire Pin number Abbreviation Connector FG hood − 14 7 − SDA (−) 15 8 RDB (+) RDA (−) 16 9 − RS-422A connector 9 5 − (9-pin type) − − RSB (+) 23 RSA (−) 24 − 25 (25-pin type) For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 5-2-4 1:N Connection among RS-422A Ports The connection method in which the RS-422A ports of multiple NT31/NT31Cs and one host are connected in a 1:N connection is described here. CPU NT31/NT31C Serial port B (RS-422A, 25-pin type) 25-pin connector Relay terminal block Max. 2 m RS-422A cables (max. total length 500 m) 24V DC PRINTER PORT B 120 CS1G/H C200HX/HG/HE(-Z)E CQM1H 9-pin connector Section Connecting to the Host’s RS-422A/485 Port Reference: 5-2 Communication using the RS-422A type standard NT link (1:N) method is possible only when a CS1W-SCB41 Serial Communications Board is installed in a CS-series CS1G/H, a Communications Board is installed in a C200HX/ HG/HE(-Z)E, or a CQM1H-SCB41 Serial Communications Board is installed in a CQM1H. Communication using the RS-422A type high-speed NT link (1:N) method is possible only when a CS1W-SCB41 Serial Communications Board is installed in a CS-series CS1G/H. The relay terminal block is not included in this figure. Insert the relay terminal block so as to achieve the wiring configuration shown below. Connecting between NT31/NT31C Units NT31/NT31C Host RS-422A 1 14 NT31/NT31C side Abbreviation Pin number 13 25 FG Connector hood Shielding wire Connector hood 1 1 − SD 2 2 SD RS-232C/ 422A/485 connector RD 3 3 RD connector RS 4 4 RS CS 5 5 CS − 6 6 − SG 7 7 SG 8 9 RDB (+) RDB (+) 13 25 FG − − 14 Pin number Abbreviation RS-232C/ 422A/485 TRM 1 NT31/NT31C side 8 − 9 TRM 10 10 RDB (+) 11 11 RDB (+) − 12 12 − − 13 13 − − 14 14 − SDA (−) 15 15 SDA (−) RDA (−) 16 16 RDA (−) − − − − − RSB (+) 23 23 RSB (+) RSA (−) 24 24 RSA (−) − 25 25 − (25-pin type) − (25-pin type) *2 Make the connection between pin numbers 9 and 10 at the NT31/NT31C at the end of the RS-422A cable (marked in the figure above) only. For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Connecting an NT31/NT31C and a Host NT31/NT31C Host RS-422A 121 Section Connecting to the Host’s RS-422A/485 Port 5-2 Wiring When Connecting a CS-series CS1G/H Serial Communication Board, C Series C200HX/HG/HE(-Z)E Communication Board, or CQM1H Serial Communications Board Applicable units: 1 14 CS1G-CPU42-E(V1) CS1G-CPU44-E(V1) CS1H-CPU63-E(V1) CS1H-CPU65-E(V1) CS1H-CPU67-E(V1) C200HE-CPU32-(Z)E C200HG-CPU33-(Z)E C200HG-CPU53-(Z)E C200HX-CPU34-(Z)E C200HX-CPU54-(Z)E C200HX-CPU65-ZE CS1G-CPU43-E(V1) CS1G-CPU45-E(V1) CS1H-CPU64-E(V1) CS1H-CPU66-E(V1) CQM1H-CPU51 CQM1H-CPU61 C200HE-CPU42-(Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E C200HX-CPU85-ZE 1 NT31/NT31C side 6 Abbreviation Pin number RS-232C/ 422A/485 FG Connector hood − 1 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 Connector hood FG − 8 1 SDA (−) interface 13 25 PLC side Shielding wire Pin number Abbreviation TRM 9 2 SDB (+) RDB (+) 10 3 − SDB (+) 11 4 − − 12 5 − − 13 6 RDA (−) − 14 7 − SDA (−) 15 8 RDB (+) RDA (−) 16 9 − 5 9 − (9-pin type) − − RSB (+) 23 RSA (−) 24 − 25 (25-pin type) RS-422A interface Next PT For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 122 Section Connecting to the Host’s RS-422A/485 Port 5-2 5-2-5 1:N Connection among RS-485 Ports The connection method in which the RS-485 ports of multiple NT31/NT31Cs and one host are connected in a 1:N connection is described here. CPU NT31/NT31C Serial port B (RS-485, 25-pin type) 25-pin connector CS1G/H C200HX/HG/HE(-Z)E CQM1H 9-pin connector Relay terminal block Max. 2 m RS-485 cables (max. total length 500 m) 24V DC PRINTER PORT B Reference: Communication using the RS-485 type standard NT link (1:N) method is possible only when a CS1W-SCB41 Serial Communications Board is installed in a CS-series CS1G/H, a Communications Board is installed in a C200HX/HG/ HE(-Z)E, or a CQM1H-SCB41 Serial Communications Board is installed in a CQM1H. Communication using the RS-485 type high-speed NT link (1:N) method is possible only when a CS1W-SCB41 Serial Communications Board is installed in a CS-series CS1G/H. 123 Section Connecting to the Host’s RS-422A/485 Port 5-2 Connecting between NT31/NT31C Units NT31/NT31C Host RS-485 NT31/NT31C side NT31/NT31C side 1 14 Abbreviation Pin number RS-232C/ 422A/485 connector 13 25 FG Connector hood Shielding wire Pin number Abbreviation Connector hood − 1 1 − SD 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS − 6 6 − SG 7 7 SG − 8 8 − TRM 9 9 TRM RDB (+) 10 10 RDB (+) SDB (+) 11 11 SDB (+) − 12 12 − − 13 13 − − 14 14 − SDA (−) 15 15 SDA (−) RDA (−) 16 16 RDA (−) − − − − RSB (+) 23 23 RSB (+) RSA (−) 24 24 RSA (−) − 25 25 − 1 14 13 25 FG RS-232C/ 422A/485 connector − − (25-pin type) (25-pin type) Next PT *2 Make the connection between pin numbers 9 and 10 at the NT31/NT31C at the end of the RS-485 cable (marked in the figure above) only. For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. Connecting an NT31/NT31C and a Host The relay terminal block is not included in this figure. Insert the relay terminal block so as to achieve the wiring configuration shown below. NT31/NT31C Host RS-485 Wiring When Connecting a CS-series CS1G/H Serial Communication Board, C Series C200HX/HG/HE(-Z)E Communication Board, or CQM1H Serial Communications Board Applicable units: CS1G-CPU42-E(V1) CS1G-CPU44-E(V1) CS1H-CPU63-E(V1) 124 CS1G-CPU43-E(V1) CS1G-CPU45-E(V1) CS1H-CPU64-E(V1) Section Connecting to the Host’s RS-422A/485 Port 1 14 CS1H-CPU65-E(V1) CS1H-CPU67-E(V1) C200HE-CPU32-(Z)E C200HG-CPU33-(Z)E C200HG-CPU53-(Z)E C200HX-CPU34-(Z)E C200HX-CPU54-(Z)E C200HX-CPU65-ZE CS1H-CPU66-E(V1) CQM1H-CPU51 CQM1H-CPU61 C200HE-CPU42-(Z)E C200HG-CPU43-(Z)E C200HG-CPU63-(Z)E C200HX-CPU44-(Z)E C200HX-CPU64-(Z)E C200HX-CPU85-ZE 6 1 NT31/NT31C side 5-2 Abbreviation Pin number Connector FG hood RS-232C/ 422A/485 connector 13 25 − 1 SD 2 RD 3 RS 4 CS 5 − 6 SG 7 Connector hood FG − 8 1 SDA (−) TRM 9 2 SDB (+) RDB (+) 10 3 − SDB (+) 11 4 − − 12 5 − − 13 6 RDA (−) PLC (CPU) side Shielding wire Pin number Abbreviation − 14 7 − SDA (−) 15 8 RDB (+) RDA (−) 16 9 − RS-422A connector 9 5 − (9-pin type) − − RSB (+) 23 RSA (−) 24 − 25 (25-pin type) Next PT For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-442A/485 Cables on page 127. 5-2-6 Recommended Connectors, Cables and Crimp Terminals Connectors and Cables Recommended for RS-422A/485 When making an RS-422A/485 connecting cable, as far as possible use the recommended parts indicated in the table below. When using the memory link method, however, use a connector that matches with the RS-422A port at the CPU (CP) side. Some units come supplied with one connector and connector hood. Check the required parts and prepare them in advance. Name Model Maker Remarks XM2A-2501 25-pin type Made by OMRON Delivered with the following units: C500-LK203 DB-25P F-N 25-pin type Made by JAE Delivered with the following units: 3G2A6-LK201-EV1 3G2A5-LK201-EV1 Connector 125 Section Connecting to the Host’s RS-422A/485 Port Name Model XM2S-2511 Connector hood DB-C2-J9 Cable Crimp terminals Maker 5-2 Remarks 25-pin type Made by OMRON Delivered with the following units: C500-LK203 Delivered with the following units: 3G2A6-LK201-EV1 3G2A5-LK201-EV1 25-pin type Made by JAE TKVVBS4P-03 Tachii Electric Wire Co., Ltd. 1.25-N3A (fork type) Japan Solderless Terminal MFG Y1.25-3.5L (fork type) Molex Inc. Recommended cable size: AWG22 to t 18 (0.3 to 0.75 mm2) The terminal screws of the RS-422A adaptor (CPM1-CIF11) are M3 specification. When wiring, use crimp terminals for M3 use. Tighten terminal screws with a tightening torque of 0.5 N@m. Use the same specification of the terminal screws which is used in the relay terminal block. Note Always use crimp terminals for wiring. Examples of applicable terminals Round type Fork type 6.2 mm or less 6.2 mm or less 5-2-7 Setting the Terminal Resistance for RS-422A/485 Communications The serial port B connector of the NT31/NT31C has a terminal resistance setting terminal (TRM). In RS-422A/485 communications, a terminal resistor must be set at the device at the end of the communication cable, but not at any other device. The NT31/NT31C has a built-in terminal resistor, and whether or not the terminal resistance is applied is set by the wiring at the terminal resistance setting terminals (pins No. 9 and 10 of serial port B). The terminal resistance is 120 Ω. When carrying out RS-422A/485 communications using serial port B, short between terminals No. 9 and 10 at the NT31/NT31C at the end of the RS-422A/485 cable. Leave terminals No. 9 and 10 open at NT31/NT31C units other than the one at the end of the cable. When not using RS-422A/485 communications, the terminal resistance setting is ineffective. In order to set the terminal resistance, wiring work is required at the cable’s connector: carry out the wiring correctly by referring to APPENDIX E Making the Cable, page 267. Abbreviation Pin number FG Connector hood - - TRM 9 RDB (+) 10 SDB (+) 11 - 12 - 126 25 Terminal resistor setting Section Connecting to the Host’s RS-422A/485 Port Pin Nos. 9 and 10 5-2 Function Terminal resistance is applied. Shorted Short only at the NT31/NT31C connected to the end of an RS-422A/485 cable. Terminal resistance is not applied. Open Leave the terminals open when connecting an NT31/NT31C anywhere other than at the end of the RS-422A/485 cable. Note Before connecting or disconnecting cables between devices, make sure that the power supply to all of the connected devices (NT31/NT31C, PLC, etc.) is OFF. Reference: The internal circuit of the NT31/NT31C is shown below. + − 10 (RDB) 16 (RDA) Terminal resistor (120 Ω) Making a connection here inserts a terminator between + (RDB) and − (RDA). 9 (TRM) For details on setting the terminal resistance of the host unit, refer to setting methods for each type of the communication. 5-2-8 Handling the Shield on RS-422A/485 Cables Perform the following procedures to connect, process the shield, and connect to ground for communications systems using the RS-422A/485. Incorrect connection may result in communications errors with the host. Connecting the Ground Wire The PT has a functional ground terminal (FG: 1, 2, 3... ). 1. Ground according to Figure (a) for normal grounding. • Connect the ground terminal (GR) of the devices to the functional ground (FG: ). Make sure that each signal line is grounded at only one point and ground to 100 Ω max. • Short the LG terminal of the PLC to the ground terminal (GR). • Use a wire gauge of at least 2mm2 for the ground wire. • Refer to the manual for individual Communications Units for details on proper wiring procedures. ) of the PT if it is mounted to the 2. Do not ground the functional ground (FG: same panel as devices that generate noise, such as motors or inverters, as shown in Figure (b). Preparing the Shield of RS-422A/485 Connectors Always prepare RS-422A/485 cable shields properly. Otherwise, communications errors may occur with the host. Ground only one end of the shield when connecting the ground terminal (GR) of ), and grounding each signal line at the devices to the functional ground (FG: only one point and to 100 Ω max, as shown in Figure (a). Ground both ends of the shield when not grounding the functional ground (FG: ) of the PT, as shown in Figure (b). When using a CJ1M-CIF11 alone or combined with an NT-AL001, be sure to connect, process the shield, and connect to ground as shown in Figure (b). 127 Section Connecting to the Host’s RS-422A/485 Port Example of Recommended Wiring Signal line 128 Signal line 5-2 SECTION 6 System Menu Operation This section describes the operation of the System Menu, focusing on the procedure to start the PT. Functions that are convenient when using the PT and those that are useful for system maintenance are also explained here. 6-1 6-2 System Menu Operation Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starting the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-1 Operation at Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 Operation Modes and the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-1 Relationships among Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-2 Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-3 Operations with the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4 Memory Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-1 Clearing Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-2 Initializing Display History Record Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-3 Initializing Alarm History Record Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-4 Initializing the Recipe Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-5 Initializing the Memory Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-6 Initializing the Memory Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5 Operations in the System Installer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-1 Setting the Display Language in the System Installer Mode . . . . . . . . . . . . . . . . . 6-5-2 Clearing/Installing the System Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-3 Changing the System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-4 Clearing Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6 Transmitting the Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 Setting Conditions for Communications with Host by Using Memory Switches . . . . . . . . 6-7-1 About Communication Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7-2 Setting the Host Link Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7-3 Setting the NT Link (1:1) Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7-4 Setting the NT Link (1:N) Method (Standard/High-speed) . . . . . . . . . . . . . . . . . . 6-7-5 Setting the Memory Link Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7-6 Setting the Communication Type for Serial Port B . . . . . . . . . . . . . . . . . . . . . . . . 6-8 Starting Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9 System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-1 Memory Switch Setting Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-2 Setting the Start-up Wait Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-3 Setting the Key Press Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-4 Setting the Buzzer Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-5 Setting the Printer Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-6 Setting the Print Method (NT31C Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-7 Setting Screen Saver Movement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-8 Setting the Screen Saver Start-up Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-9 Setting the History Display Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-10 Setting the Resume Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-11 Setting the Automatic Reset Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-12 Setting the Time-out Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9-13 Setting the Retry Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10 Setting the Bar Code Reader Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 132 132 133 133 135 136 138 138 140 142 143 145 147 148 149 149 151 152 153 155 155 158 160 161 163 165 166 166 166 167 168 169 170 172 173 175 177 179 181 183 184 186 129 Section 6-11 System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11-1 I/O Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11-2 Displaying/Setting the Calendar and Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11-3 Checking the PT Setting Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11-4 Displaying and Printing the Display History Record . . . . . . . . . . . . . . . . . . . . . . 6-11-5 Displaying and Printing the Alarm History Record . . . . . . . . . . . . . . . . . . . . . . . 6-11-6 Checking Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11-7 Device Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11-8 Checking Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12 Programming Console Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12-1 Usable Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12-2 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12-3 Method of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13 Device Monitor Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13-1 Compatible Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13-2 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13-3 Method of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 Version Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14-1 Method of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 189 189 193 195 196 198 200 203 213 219 219 221 222 225 226 226 227 228 228 System Menu Operation Flow 6-1 Section 6-1 System Menu Operation Flow Follow the procedure below when using the NT31/NT31C for the first time or changing the system program. Create the Screen Data Create the data to be displayed on the NT31/NT31C by using the Support Tool. For details on creating screen data, refer to the NT-series Support Tool Ver. 4.1 for Windows Operation Manual (V061-E1-). Start Up the NT31/NT31C (Display the System Menu) (page 132) Turn ON the power to the NT31/NT31C. If no screen data has been registered, an error message is displayed. In this case, press the OK touch switch on the error message screen to display the System Menu. If screen data has been registered and the RUN mode is established, perform the appropriate operations on the touch panel to display the System Menu. Initialize the Memory (page 138) If necessary, initialize the memory of the NT31/NT31C by operation from the System Menu. Transmit the Screen Data (page 153) Connect the Support Tool to the NT31/NT31C and transmit the screen data from the Support Tool to the NT31/NT31C. For details on connecting the Support Tool, refer to 3-2 Connecting to the Support Tool (page 33). Set the Memory Switches (pages 155, 166, 186) Select the System Menu and set the operations of the NT31/NT31C — for example the conditions for communication with the host — using the memory switches. Start Operation (page 166) Connect the NT31/NT31C to the host and start operation. System Maintenance (page 189) If an error occurs during operation, check the I/Os, settings, etc., by referring to this guide. 131 Section Starting the NT31/NT31C 6-2 6-2 Starting the NT31/NT31C After checking that the hardware has been connected correctly, switch on the power to the NT31/NT31C to start it up. This section describes the operation of the NT31/NT31C when it is started up. 6-2-1 Operation at Startup The NT31/NT31C operates as follows when the power is switched ON, or when it is reset. Initial Processing Self diagnosis — including a check on the internal memory of the NT31/NT31C and a system program check — and the internal processing required for startup, are performed. If an error occurs during initial processing, an error screen is displayed. If there is an error in the system program, the system program must be reinstalled. For details on the installation procedure, refer to 6-5 Operations in the System Installer Mode (page 148). Memory Unit Check and Processing Check if a memory unit is installed. If a memory unit is installed, processing (screen data and system program reading/writing) is executed in accordance with its DIP switch settings (pages 37 and 45). If there is an error in the screen data, an error screen is displayed. Pressing the OK touch switch on the error screen will return the display to that immediately before the error occurred. It is also possible to display the System Menu from the error screen by pressing two of the four corners of the touch panel simultaneously. If there is an error in the system program, the main menu of the system installer mode is displayed. If this is the case, reinstall the proper system program. Initialize the memory or change the settings as required. Start of Communication with the Host Communication with the host starts in accordance with the communication method set in the system memory of the NT31/NT31C. During the interval until communication is established, the system initialization screen (screen No. 9000) is displayed. For details, refer to 6-8 Starting Operation (page 166). If the system initialization screen remains on, display the System Menu by pressing two of the four corners of the touch panel simultaneously, and check the settings for the communication conditions for communication with the host. Operation Start The RUN mode is established, and operation starts in accordance with the screen data in the NT31/NT31C. When changing the settings or checking the statuses, perform the appropriate operation by displaying the System Menu. For details on displaying the System Menu, refer to 6-3-3 Operations with the System Menu (page 136). 132 Section Operation Modes and the System Menu 6-3 6-3 Operation Modes and the System Menu The NT31/NT31C operates in four modes: the RUN, Transmit, Maintenance, and Expansion modes. These modes are selected from the System Menu. In addition, the NT31/NT31C also features the System Installer mode which is used specifically for installing the system program. The System Installer mode is selected by operation at the panel when the NT31/NT31C power is switched ON. 6-3-1 Relationships among Modes The relationships among the System Menu, each of the operation modes, and the System Installer mode, are indicated in the figure below. For details on system menu operation, refer to 6-3-3 Operations with the System Menu (page 136). [RUN Mode] [Transmit Mode] This is the mode in which the NT31/NT31C operates. In this mode the NT31/NT31C can be controlled from the host, and various display and I/O operations are possible. In this mode, screen data and other data are transmitted between the Support Tool and the NT31/NT31C. To change system settings or screen data contents When system settings and screen data registration have been completed To change system settings or screen data contents. SYSTEM MENU [Maintenance Mode] In this mode, NT31/NT31C maintenance operations, such as initialization of the memory, checking settings, and the I/O check, are executed. Quit Power ON Transmit Mode Maintenance Mode Expansion Mode If there is no system program, or if the settings for data control are changed... [System Installer Mode] [Expansion Mode] In this mode, the Programming Console function is used, or check the version of system program. In this mode, the system program of the NT31/NT31C is installed, display of the System Menu is enabled or disabled, and screen data changes are enabled and disabled, among other operations. 133 Section Operation Modes and the System Menu Items in the System Menu 6-3 The items displayed in the system menu and their functions are as follows. Menu Item Function Quit Clear the System Menu screen and return to the RUN mode screen. Transmit Mode Display the Transmit Mode screen to allow transmission for screen data between the Support Tool and the NT31/NT31C. For details on transmission of screen data, refer to 6-6 Transmitting the Screen Data (page 153). Maintenance Mode Display the Maintenance Mode menu to allow system maintenance of the NT31/NT31C, and various NT31/NT31C settings. Expansion Mode Functions of the System Installer Mode 134 Display the Expansion Mode menu to allow selection of the expansion functions supported by the NT31/NT31C. The following expansion functions are supported: • Version Display Displays the version of system program, the date it was created, and the PT model. For details, refer to 6-14 Version Display. • Programming Console Function Allows the NT31/NT31C to be used as a Programming Console for a CS1G/CS1H, CPM1, CPM2A, CPM2C, CQM1, CQM1H, C200HX/HG/HE(-Z), or SRM1. For details, refer to 6-12 Programming Console Function. • Device Monitor Function Allows the NT31/NT31C to change the PLC’s operating mode and display/change the contents of words in a CS1G/CS1H, CPM1, CPM2A, CPM2C, CQM1, CQM1H, C200HX/HG/ HE(-Z), or SRM1. For details, refer to 6-13 Device Monitor Function in this manual or 2-16 Device Monitor Function in the Reference Manual. The following functions can be executed in the System Installer mode. • Setting the display language • Clearing and installing system programs • Disabling/enabling display of the System Menu. • Disabling/enabling writing to the screen data memory • Clearing screen data For details on these functions, refer to 6-5 Operations in the System Installer Mode (page 148). Section Operation Modes and the System Menu 6-3 6-3-2 Menu Tree The System Menu allows the various functions of the NT31/NT31C to be executed by using touch switches displayed on the touch panel. The menu tree, starting from the System Menu, is shown below. For details on System Menu operations, refer to 6-3-3 Operations with the System Menu (page 136). The menu tree may differ according to the system program installed in the NT31/NT31C. The menu tree for the system program that is installed in the NT31/NT31C on shipment is shown below. SYSTEM INSTALLER MODE Exit System Installer Download System Program (page 149) Change System Settings (page 151) Erase Screen Data (page 152) SYSTEM MENU MEMORY INIT. MENU Quit Transmit Mode (page 153) Maintenance Mode Expansion Mode Quit Screen Data (page 138) Display History (page 140) Alarm History (page 142) Recipe Table (page 143) Memory Table (page 145) Memory Switch (page 147) MAINTENANCE MODE MENU Quit Memory Init. Memory Switch I/O Settings Calendar Check (page 193) PT Settings (page 195) Display History Alarm History Screen Data Disp. (page 200) I/O Check MEMORY SWITCH MENU Start-up Wait Time (page 167) Key Press Sound (page 168) Buzzer Sound (page 169) Printer Controller (page 170) Print Method (page 172) Screen Saver Movement (page 173) Screen Saver Start up Time (page 175) Hist. Disp. Method (page 177) Resume Function (page 179) Comm. Auto-return (page 181) Time-out Interval (page 183) Retry Counts (page 184) Comm. A Method (page 155) Comm. B Select (page 165) Comm. B Method (page 155) I/O SETTINGS MENU I/O CHECK MENU Quit Contrast Adjust (page 189) Brightness Adjust (page 191) Quit I/F Check Device Check DISPLAY HISTORY MENU EXPANSION MODE MENU Quit Programming Console Function (page 219) Version Display (page 228) Device Monitor Function (page 225) I/F CHECK MENU Quit Tool Comm. (page 213) Comm. Port A (page 215) Comm. Port B (page 215) Printer (page 218) DEVICE CHECK MENU Quit Sort by Occurrence (page 196) Sort by Frequency (page 196) ALARM HISTORY MENU Quit Sort by Occurrence (page 198) Sort by Frequency (page 198) Quit Buzzer Check (page 203) LED Check (page 204) LCD Check (page 206) Backlight Check (page 207) Screen Memory (page 207) Touch Switch (page 210) Battery (page 212) 135 Section Operation Modes and the System Menu 6-3 6-3-3 Operations with the System Menu This section describes how to use the menus, including how to call the System Menu, how to call the System Installer mode, and how to select menu items. Calling the System Menu The System Menu can be displayed by either of the following two methods. • Touching the corners of the touch panel • Pressing a touch switch that displays the System Menu Reference: If display of the System Menu is disabled by the setting made in the System Installer mode, the System Menu cannot be displayed (this does not apply if an error has occurred). At the same as the System Menu is displayed, the operation of the NT31/NT31C stops and the RUN LED goes OFF. Touching The Corners of The Touch Panel When two of the four corners of the touch panel (see the figure below) are touched simultaneously, the System Menu is displayed. RUN mode POWER [SYSTEM MENU] RUN Quit Press any two of the four corners at the same time. Transmit Mode Maintenance Mode Expansion Mode Note that the touch switches used to call the System Menu are not displayed at corners on the screen. If a touch switch displayed in a corner is pressed first, the touch switch will function and the System Menu will not be displayed. In particular, when the touch switch has switch screen function, as a result of screen switch over, it means the corner is not pressed even if it is kept pressing. To successfully call the System Menu, first press a corner where no touch switch is displayed, and then press any other corner regardless of the presence of a touch switch. Reference: With the NT31/NT31C, the System Menu can be displayed even if the screen has touch switches registered at all four corners. Pressing a Touch Switch That Displays The System Menu There is a control key that has the function of displaying the System Menu. By registering the touch switch for System Menu display ([MENU]) on a screen when creating it, the System Menu can be displayed just by pressing this switch. Calling the System Installer Mode If the NT31/NT31C has no system program installed, or if the system program is destroyed, the System Installer mode is automatically established when the power is switched ON. To establish the System Installer mode in order to install a system program or make settings for data management, either turn the power ON, or reset the 136 Section Operation Modes and the System Menu 6-3 NT31/NT31C, while pressing the touch switch at the top left corner of the touch panel (size: 7.2 mm 7.2 mm). Switch the power to the NT31/NT31C ON while pressing this touch switch. POWER RUN Selecting Menu Items The menu items in the System Menu are displayed on the NT31/NT31C screen as touch switches. Menu items can be selected simply by pressing them. Example: Displaying the MAINTENANCE MODE MENU screen by pressing Maintenance Mode in the System Menu. Ver 3.10 Switching from the System Menu to the RUN Mode Press Maintenance Mode. Return to the RUN mode by selecting Quit in the System Menu and other menus. Reference: Unlike previous PT models, the NT31/NT31C does not return to the RUN mode automatically if no operations are performed. 137 Section Memory Initialization 6-4 6-4 Memory Initialization The NT31/NT31C has the following initialization functions. Use them as necessary. • Clearing screen data Page 138 • Initializing memory tables Page 145 • Initializing memory switches Page 147 • Initializing display history record data Page 140 • Initializing alarm history record data Page 142 • Initializing recipe tables Page 143 Reference: If writing to the screen data memory has been disabled by the System Setting setting in the System Installer mode, memory initialization is not possible. 6-4-1 Clearing Screen Data Use this function if the screen data has been corrupted and the NT31/NT31C cannot be started up correctly. This operation clears (initializes) only the screen data and contents of the mathematical tables. The memory switch settings and display history/alarm history record data are retained. Reference: When this function is used, all of the screen data contents registered in the NT31/NT31C up to that point are cleared. Check that the created screens are backed up at the Support Tool before using it. The screen data can be cleared in the System Installer mode too (page 149). The following types of data can be initialized individually. Contents of numeral/character string memory tables (page 142) Memory switch settings (page 145) Display history record data (page 140) Alarm history record data (page 142) 138 Section Memory Initialization 6-4 Clear the screen data by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Init.. Select Screen Data. Select Yes. The screen data is cleared. During clearance, the message Erasing Now... is displayed. If No is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without clearing the screen data. On completion of screen data clearance, the NT31/NT31C returns to the MEMORY INIT. MENU screen. After the screen data has been cleared, if an attempt is made to set the NT31/NT31C to the RUN mode before screen data has been transmitted from the Support Tool or memory unit, an error message will be displayed and the RUN mode will not be established. 139 Section Memory Initialization 6-4 6-4-2 Initializing Display History Record Data The display history record function keeps a record of the order of display of the screens displayed during operation, and the number of times each screen is displayed. These records are kept only for screens for which the History attribute has been set. The maximum number of records is 1024 for sort by occurrence (order of display occurrence) and 255 for sort by frequency (order of the number of times each screen has been displayed). Use the display history record initialization function to clear the history record data to 0, for example when the screen data has been changed, etc. Also, if Alarm (Use Ring Buffer) under History Setting of System in PT Configuration (Tools) has not been checked, no more records will be stored after the maximum number of records has been kept, and therefore the records must be periodically initialized. If Alarm (Use Ring Buffer) is checked, when the maximum number of records is reached the oldest record is deleted and the newest data is recorded. Reference: The NT31/NT31C also allows the display history record data to be initialized by controlling the PT status control area from the host. For details, refer to 2-2-1 PT Status Control Area in the Reference Manual. 140 Section Memory Initialization 6-4 Initialize the display history record data by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Init.. Select Display History. Select Yes. The display history record data is initialized. During initialization, the message Initializing is displayed. If No is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without initializing the display history record data. On completion of display history record data initialization, the message Finished is displayed and the NT31/NT31C returns to the MEMORY INIT. MENU screen. 141 Section Memory Initialization 6-4 6-4-3 Initializing Alarm History Record Data The alarm history record function continually checks the status of host bits that have been designated in advance with a bit memory table, and records the time when any of the bits is set to 1 (comes ON), and the number of times that each bit comes ON. The maximum number of records is 256 for sort by occurrence (order of error occurrence) and 255 for sort by frequency (order of the number of times each error has occurred). Use the alarm history record initialization function to reset the alarm history record data to 0, for example when the screen data has been changed, etc. Also, if Screen (Use Ring Buffer) under History Setting in the PT Environment Settings – System Settings has not been checked, no more records will be stored after the maximum number of records has been kept, and therefore the records must be periodically initialized. If Screen (Use Ring Buffer) is checked, when the maximum number of records is reached the oldest record is deleted and the newest data is recorded. Reference: The NT31/NT31C also allows the alarm history record data to be initialized by controlling the PT status control area from the host. For details, refer to 2-2-1 PT Status Control Area in the Reference Manual. 142 Section Memory Initialization 6-4 Initialize the alarm history record data by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Init.. Select Alarm History. Select Yes. The alarm history record data is initialized. During initialization, the message Initializing is displayed. If No is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without initializing the alarm history record data. On completion of alarm history record data initialization, the message Finished is displayed and the NT31/NT31C returns to the MEMORY INIT. MENU screen. 6-4-4 Initializing the Recipe Tables You can initialize the recipe tables (i.e., all the recipe data) edited in the NT31/NT31C. Here, “initializing” the recipe tables means to restore the battery backup memory (“recipe data memory”) to the values in flash memory at that time. If, after downloading from the Support Tool, you do not upload the data even once, initialization will restore the initial values set using the Support Tool. The values will not be cleared. 143 Section Memory Initialization 6-4 Initialize the recipe tables by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Init.. Select Recipe Table. Select Yes. The recipe tables are initialized. During initialization, the message Initializing is displayed. If No is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without initializing the recipe tables. On completion of memory table initialization, the message Finished is displayed and the NT31/NT31C returns to the MEMORY INIT. MENU screen. 144 Section Memory Initialization 6-4 6-4-5 Initializing the Memory Tables It is possible to initialize the numeral memory tables and character string memory tables in the NT31/NT31C. When these tables are initialized, the values are returned to those set by the Support Tool (they are not cleared). When the memory tables are initialized, they are returned to their initial values regardless of the setting made for the resume function (page 179). If ON is set for the Resume Function memory switch, the initial values set with the Support Tool will not be recorded in the memory tables unless they are initialized. Reference: If OFF is set for the Resume Function memory switch, the memory tables can be initialized just by switching the NT31/NT31C power off and back on again, or by resetting the NT31/NT31C (page 179). The bit memory table merely reflects the statuses of bits at the host and therefore cannot be initialized. 145 Section Memory Initialization 6-4 Initialize the memory tables by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Init.. Select Memory Table. Select Yes. The memory tables are initialized. During initialization, the message Initializing is displayed. If No is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without initializing the memory tables. On completion of memory table initialization, the message Finished is displayed and the NT31/NT31C returns to the MEMORY INIT. MENU screen. 146 Section Memory Initialization 6-4 6-4-6 Initializing the Memory Switches Initialization returns all the memory switches of the NT31/NT31C to their status on shipment. Initialize the memory switches by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Init.. Select Memory Switch. Select Yes. The memory tables are initialized. During initialization, the message Initializing is displayed. If No is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without initializing the memory switches. On completion of memory switch initialization, the message Finished is displayed and the NT31/NT31C returns to the MEMORY INIT. MENU screen. 147 Section Operations in the System Installer Mode 6-5 After initialization, the memory switch statuses are as follows. Memory Switch Status Start-up Wait Time 00 Key Press Sound ON Buzzer Sound OFF Printer Controller ESC/P Print Method Tone (NT31C only) Screen Saver Movement Display erased Screen Saver Start up Time 010 Hist. Disp. Method From New Data Resume Function OFF Comm. Auto-return OFF Time-out Interval 01 Retry Counts 005 Comm. A Method Host Link (communications speed = 9600 bps)* Comm. B Select RS-232C Comm. B Method None * The communication conditions for a bar code reader are initialized as follows: Data bits: 7 bits; stop bit: 1 bit; parity: none; flow control: RS/CS. 6-5 Operations in the System Installer Mode The following functions can be executed in the System Installer mode: • Setting the display language (see below) • Clearing/installing the system program (page 149) • Disabling/enabling display of the System Menu (changing the system settings) (page 151) • Disabling/enabling writing to the screen data memory (changing the system settings) (page 151) • Clearing screen data (page 152) For details on calling the System Installer mode, refer to Calling the System Installer Mode (page 136). The version code displayed beside the System Installer title on the screen indicates the version of the System Installer Mode. For version 2.00 or later, the memory unit is used to transfer the system program. For details, refer to 3-5 Using a Memory Unit (-V Versions) on page 37. 148 Section Operations in the System Installer Mode 6-5 6-5-1 Setting the Display Language in the System Installer Mode The first setting made in the System Installer mode is to select whether the display language is to be English or Japanese. Select English or Japanese. From here on, this manual assumes that English has been selected here. The System Installer mode menu is displayed. If there is no system program or the system program has been corrupted, the message System Program not exist or incorrect. is displayed at the bottom of the screen. 6-5-2 Clearing/Installing the System Program Use this function when the system program of the NT31/NT31C has been corrupted, or when installing a new system program. Reference: In order to install a system program, the system installer must also be installed at the Support Tool. The system installer is an accessory with the Support Tool (NT-ZJCAT1-EV4). When installing the Support Tool in a personal computer, install the system installer also. For details on the method for installing the system installer at the Support Tool side, and the operating procedure, refer to the NT-series Support Tool Ver. 4.1 for Windows Operation Manual (V061-E1-). When the system program is cleared by mistake, it becomes impossible to use the NT31/NT31C at all. Check that the system installer is installed at the Support Tool side before deleting the program. However, note that the registered screen data and memory switch settings are retained. It becomes possible to install the system program inside the memory unit automatically by installing the memory unit at startup. (Refer to 3-5 Using a Memory Unit (-V Versions).) Clear/install the system program by following the menu operation from the System Installer mode menu shown below. 149 Section Operations in the System Installer Mode 6-5 Clearing the System Program Select Download System Program. Select Yes. The system program is cleared. During clearance, the message Erasing ... is displayed. • If Return to Menu is selected, the NT31/NT31C returns to the System Installer mode menu without clearing the system program. • If clearance fails, a screen asking whether you wish to try again is displayed. On completion of system program clearance, the NT31/NT31C enters the standby status for downloading of the system program. Downloading the System Program On normal completion of system program clearance, the standby status for system program downloading is automatically established. When the NT31/NT31C enters this status, transmit the system program from the system installer at the personal computer. During downloading, the progress of transmission is indicated on the screen. Select Run System. If Abort is selected during standby for downloading or during downloading, a screen asking whether you wish to download again is displayed. When the system program is started, the NT31/NT31C starts up normally. If no screen data has been registered, an error message will be displayed indicating that screen data hasn’t been registered. Transfer the screen data and proceed. Reference: If the new system program is not downloaded successfully after deleting a system program, it is not possible to use the NT31/NT31C at all. After deleting the system program, be sure to download a new one. 150 Operations in the System Installer Mode Section 6-5 6-5-3 Changing the System Settings The NT31/NT31C allows the following settings to be made to prevent the screen data and memory switch settings from being changed or deleted by operating errors. Disabling/enabling System Menu Display When System Menu display is disabled by this setting, the System Menu cannot be displayed by touch panel operations or by using the touch switches. However, if a error occurs, the System Menu can be displayed from the error message screen. Disabling/enabling Writing to The Screen Data Memory When writing to the screen data memory is disabled by this setting, it is impossible to use the following System Menu functions. • Switching to the Transmit mode • Displaying the memory switch setting screens • Checking the screen data memory • Displaying the initialization menu • Displaying the calendar/time setting screen (the calendar/time display screen can be displayed) Change the system settings by following the menu operation from the System Installer mode menu shown below. Select Change System Settings. Select Display System Menu or Screen Memory Protect. Each time either of these items is selected, the setting switches from Disabled to Enabled or vice versa. Select OK. The settings are written to the NT31/NT31C while the screen is displayed. • If Cancel is selected, the NT31/NT31C returns to the System Installer mode menu without changing the settings. The settings remain as they were before the operation was started. 151 Operations in the System Installer Mode Section 6-5 • If writing of the settings fails, a screen asking whether you wish to try again is displayed. After the settings have been written, the System Installer mode menu screen is redisplayed. 6-5-4 Clearing Screen Data If the screen data has been corrupted and the NT31/NT31C cannot be started normally, use this function to clear the screen data. Note that only the screen data is cleared (initialized), and the memory switch settings and the display history/alarm history record data are retained. Reference: When this function is used, all of the screen data contents registered in the NT31/NT31C up to that point are cleared. Check that the created screens are backed up at the Support Tool before using it. The screen data can also be cleared from the System Menu (page 138). If the screen data is cleared in the System Installer mode, the message Screen Data Corrupted may be displayed on switching to the RUN mode. If this happens, initialize the screen data again from the MEMORY INIT. MENU screen. Clear the screen data by following the menu operation from the System Installer mode menu shown below. Select Erase Screen Data. Select Yes. The screen data is cleared. During clearance, the message Erasing ... is displayed. • If Return to Menu is selected, the NT31/NT31C returns to the MEMORY INIT. MENU screen without clearing the screen data. • If screen data clearance fails, a screen asking if you wish to try again is displayed. On completion of screen data clearance, the NT31/NT31C returns to the System Installer mode menu screen. After the screen data has been cleared, if an attempt is made to set the NT31/NT31C to the RUN mode before screen data has been transmitted from the Support Tool or memory unit, an error message will be displayed and the RUN mode will not be established. 152 Section Transmitting the Screen Data 6-6 6-6 Transmitting the Screen Data The screen data is created with the Support Tool and then transmitted to the NT31/NT31C. This section explains how to transmit the screen data. For details on how to create the screen data and the operation of the Support Tool, refer to the Reference Manual and the NT-series Support Tool Ver. 4.1 for Windows Operation Manual (V061-E1-). Reference: The screen data can be transmitted also from the memory unit installed in the NT31/NT31C. For details on this method, refer to 3-5 Using a Memory Unit (-V Versions) or 3-6 Using a Memory Unit (Versions without the V Suffix). The screen data can be transmitted at a faster rate by setting High for Baud Rate on the Comms. Setting... window of the Support Tool. If writing to the screen data memory is disabled by the setting made for System Setting in the System Installer mode, screen data transmission is not possible. Screen Data Composition and Transmission Units The screen data comprises the following types of data. • User screen data (screen units) • System memory (memory switch) settings • Direct connection information • Numeral memory table data • Character string memory table data • Bit memory table data • Mathematical table data • Mark information • Image/library data • Recipe table data It is possible to transmit the screen data (data for all the screens) in file units, or to transmit individual data or the data of individual screens in data units. (It is not possible to transmit mathematical table data in data units.) When data is transmitted in file units, all of the screen data in the NT31/NT31C is cleared and then the new data is transmitted. When data is transmitted in data units, first the previous data is invalidated, then the new data is registered as valid data. Since the previous data is not cleared, free memory area in the NT31/NT31C will be insufficient when transmissions in data units are repeated. If this happens, write the screen data again by data transmission in file units. Transmitting Screen Data from the Support Tool To transmit screen data from the Support Tool to the NT31/NT31C, follow the procedure below. Operation 1, 2, 3... 1. Connect the NT31/NT31C to a personal computer in which the Support Tool has been installed and turn the power to the NT31/NT31C ON. 2. Turn ON the power to the personal computer and start up the Support Tool. 153 Section Transmitting the Screen Data 6-6 3. Establish the Transmit mode by following the menu operation from the System Menu shown below at the NT31/NT31C. Ver 3.10 Select Transmit Mode. Select Tool Transmit. 4. Open the screen data to be transmitted at the Support Tool, then select Download (NTST PT) in the Support Tool’s Connect menu and specify the data to be transmitted. 5. During screen data transmission, the transmission status is displayed. 6. On completion of screen data transmission, press the Quit touch switch. The NT31/NT31C returns to the Transmit mode. If the screen data cannot be successfully transmitted from the Support Tool, use the communication check functions of the NT31/NT31C to check if communication between the NT31/NT31C is normal or not (page 213). Precautions to Be Observed When Transmitting Screen Data 154 If any of the following, or a system error, occurs during transmission of screen data, the transmitted screen data will not be registered correctly in the NT31/NT31C. If this happens, the NT31/NT31C may not enter the RUN mode when started up, or there may be unpredictable malfunctions such as failure to display screens during operation. In this case, the screen data must be retransmitted in file units to register it correctly. • The power to the NT31/NT31C is interrupted or the NT31/NT31C is reset. • The power to the personal computer on which the Support Tool is running is interrupted or the computer is reset. • The cable connecting the NT31/NT31C to the personal computer on which the Support Tool is running is disconnected or has a broken wire. • The Quit touch switch on the NT31/NT31C screen is pressed to end screen data transmission. Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 • Screen data transmission is stopped by operation at the Support Tool. Note When transferring the data in units of screens, if there are changes in memory table and/or direct access, transfer such data along with the screen data. 6-7 Setting Conditions for Communications with Host by Using Memory Switches The NT31/NT31C can be connected to the host by the following 7 types of communication methods can be used to communicate with a host. • Host link Memory link method • NT Link (1:1) Mitsubishi A-computer link method • NT Link (1:N) Mitsubishi FX method • High-speed NT Link (1:N) The NT31/NT31C has the following two ports, either of which can be used for communications with the host, depending on the requirements. • Serial port A (exclusively for RS-232C, 9-pin connector) • Serial port B (RS-232C/RS-422A (selectable), 25-pin connector) The method for setting the communication method for communications with the host is described here. For details on setting the communication conditions for a bar code reader, refer to 6-10 Setting the Bar Code Reader Input Function (page 186). Reference: Apart from the host, it is also possible to connect the Support Tool or a bar code reader to serial port A. When a bar code reader is connected at serial port A, the host must be connected at serial port B. When serial port A is being used for communications with the host, the host must be disconnected so that the Support Tool can be connected. There are four memory switch setting screens. The conditions for communications with the host are set on the fourth screen (the screen on which 4/4 is displayed). For details on setting memory switches other than those for setting the conditions for communications with the host, refer to 6-9 System Settings (page 166). When using the Mitsubishi A-computer link method and Mitsubishi FX method, a system program for multi-venders is required. Install the system program to the NT31/31C by the system installer (refer to page 149). For details, refer to PLC Connection Manual (V042-E1-). When using PLCs manufactured by Allen-Bradley, GE Fanuc, or Siemens, refer to NT31/631 Multi Vendor Connection Manual (V060-E1-). 6-7-1 About Communication Conditions Items Set for Communication Conditions The following settings are made for the communication conditions for communication between the NT31/NT31C and the host. 155 Section Setting Conditions for Communications with Host by Using Memory Switches 6-7 Port Communication Method/Communication Type Settings Setting Item Comm. A Method Function Setting Options Page Set the communication method used at serial port A. Depending on the communication method, further communication condition settings may be necessary. A system program for OMRON model. None/Host Link/NT Link (1:1)/ NT Link (1:N) (standard or highspeed)/Bar-Code Reader Memory link Page 158 Page 160 Page 161 Page 163 Comm. B Select Set whether serial port B is to be used for RS-232C or RS-422A communication. RS-232C/RS-422A Page 165 Comm. B Method Set the communication method used at serial port B. Depending on the communication method, further communication condition settings may be necessary. A system program for OMRON model. None/Host Link/NT Link (1:1)/ NT Link (1:N) (standard or highspeed) Memory link Page 158 Page 160 Page 161 Page 163 Communication Condition Settings for The Host Link Method Setting Item Comm. Speed (for host link only) Function Setting Options Sets the communications speed 9600 bps/ for communications with the host. 19200 bps Page Page 158 Communication Condition Settings for The NT link (1:1) Method No further communication conditions need to be set. Communication Conditions Settings for The NT Link (1:N) Method Setting Item Function Setting Options Unit No. (for NT link (1:N) only) Set the unit number of the NT31/NT31C. 0 to 7 Comm. Speed Sets the communications speed Standard or for communications with the host. high-speed Page Page 161 Setting The Conditions for Communications with The Memory Link Method Setting Item Possible Combinations of Communication Method Settings 156 Function Setting Options Data bits Set the data bits length. 7, 8 bits Stop bits Set the stop bits length. 1, 2 bits Parity Set the parity. None, even, odd Comm. Speed Set the communications speed 1200, 2400, for communications with the host. 4800, 9600, 19200, 38400 bps Flow control Set the flow control and its method. None, RS/CS, XON/XOFF Response Set whether the response is carried out for normal process of communication command or not. Yes, No Page Page g 163 The combinations of communication methods that can be set with the NT31/NT31C are indicated in the table below. Combinations other than these listed below cannot be set (when using a system for multi-venders, refer to the PLC Connection Manual (V042-E1-) or NT31/631 Multi Vendor Connection Manual (V060-E1-). Section Setting Conditions for Communications with Host by Using Memory Switches 6-7 Serial port A Serial port B None Host Link NT Link (1:1) NT Link (1:N) Bar-code reader Memory Link None Host Link NT Link (1:1) NT Link (1:N) (Standard or high-speed) Memory Link : Possible combination : Impossible combination Combinations other than those indicated above cannot be set. Reference: When using serial port B for communication with the host, and serial port A for the transmission of screen data from the Support Tool, set the settings of serial port A to None. 157 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 6-7-2 Setting the Host Link Method Set the communication conditions for the host link method at serial port A or serial port B by following the operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Display the fourth memory switch screen by pressing the [↓] (next screen) or [↑] (previous screen) touch switch. Press the touch switch corresponding to the port at which the host link method is to be set (Comm. A Method or Comm. B Method) to display the setting option Host Link. The setting option changes each time the touch switch is pressed. 158 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 Press the Set touch switch to the right of the port at which the setting has been made. In this example, serial port A is used. Press the Comm. Speed touch switch to display the communications speed to be set. The setting option changes each time the touch switch is pressed. In this example, serial port A is used. Press Quit. The communications speed is set. • To quit the communications speed setting screen without setting the communications speed, press the Abort touch switch. The NT31/NT31C returns to the memory switch setting screen (4/4) and the previous communications speed remains in effect. On completion of communications speed setting, the NT31/NT31C returns to the memory switch setting screen (4/4). To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 159 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 6-7-3 Setting the NT Link (1:1) Method Set the communication conditions for the NT link (1:1) method at serial port A or serial port B by following the operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Display the fourth memory switch screen by pressing the [↓] (next screen) or [↑] (previous screen) touch switch. Press the touch switch corresponding to the port at which the NT link (1:1) method is to be set (Comm. A Method or Comm. B Method) to display the setting option NT Link (1:1). The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 160 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 6-7-4 Setting the NT Link (1:N) Method (Standard/High-speed) Set the communication conditions for the NT link (1:N) method at serial port A or serial port B by following the operation from the System Menu shown below. The communications speed determines whether the 1:N NT Link is standard or high-speed. Standard: High-speed: Standard 1:N NT Link High-speed 1:N NT Link Ver 3.10 Select Maintenance Mode. Select Memory Switch. Display the fourth memory switch screen by pressing the [↓] (next screen) or [↑] (previous screen) touch switch. Press the touch switch corresponding to the port at which the NT link (1:N) method (standard or high-speed) is to be set (Comm. A Method or Comm. B Method) to display the setting option NT Link (1:N). The setting option changes each time the touch switch is pressed. In this example, serial port A is used. 161 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 Press the Set touch switch to the right of the port at which the setting has been made. In this example, serial port A is used. Press the Unit No. touch switch to display the unit number to be set. Press the Comm. Speed touch switch to display the communications speed, standard or 115.2-kbps high-speed. (The Comm. Speed setting determines which method of 1:N NT Link is used.) The setting option changes each time the touch switch is pressed. In this example, serial port A is used for a standard 1:N NT Link. Press Quit. The unit number and communications speed are set. • To quit the unit number/communications speed setting screen without confirming the unit number/communications speed settings, press the Abort touch switch. The NT31/NT31C will return to the memory switch setting screen (4/4) with the previous settings still in effect. Reference: Unit numbers are numbers assigned to each PT when multiple PTs are connected to one host, so that the host can identify the individual PTs. The units numbers that can be set differ according to the host model, as follows. C200HE(-ZE): Unit numbers 0 to 3 (maximum of 4 PTs per host port) C200HG(-ZE), C200HX(-ZE): Unit numbers 0 to 7 (maximum of 8 PTs per host port) When making the settings, make sure there is no duplication of unit numbers among PTs. On completion of unit number/communications speed setting a, the NT31/NT31C returns to the memory switch setting screen (4/4). To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 162 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 6-7-5 Setting the Memory Link Method Set the communication conditions for the host link method at serial port A or serial port B by following the operation from the System Menu shown below. Check the communication settings of the host to be used. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Display the fourth memory switch screen by pressing the [↓] (next screen) or [↑] (previous screen) touch switch. Press the touch switch corresponding to the port at which the memory link method is to be set (Comm. A Method or Comm. B Method) to display the setting option Memory Link. The setting option changes each time the touch switch is pressed. In this example, serial port A is used. Press the Set touch switch to the right of the port at which the setting has been made. In this example, serial port A is used. 163 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 Display the data bits to be set (7 bits or 8 bits) by pressing the Data Bit Length touch switch. Display the stop bits to be set (1 bit or 2 bits) by pressing the Stop Bit Length touch switch. Display the parity to be set (None, even, odd) by pressing the Parity Bit touch switch. Display the communication speed to be set (1200, 2400, 4800, 9600, 19200, 38400 bps.) by pressing the Comm. Speed touch switch. Display the condition of the flow control to be set (None, RS/CS, XON/XOFF) by pressing Flow Control touch switch. If the RS-422A is selected for serial port B setting, RS/CS is not displayed. Display presence or absence of the response by pressing the Response touch switch. The setting option changes each time the touch switch is pressed. In this example, serial port A is used. Press the Quit touch switch. • To quit the communications speed setting screen without setting the communications speed, press the Abort touch switch. The NT31/NT31C returns to the memory switch setting screen (4/4) and the previous communications speed remains in effect. On completion of communications speed setting, the NT31/NT31C returns to the memory switch setting screen (4/4). To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 164 Setting Conditions for Communications with Host by Using Memory Switches Section 6-7 6-7-6 Setting the Communication Type for Serial Port B Set the communication type (RS-232C or RS-422A) for serial port B by following the operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Display the fourth memory switch screen by pressing the [↓] (next screen) or [↑] (previous screen) touch switch. Press the Comm. B Select touch switch to display the communication type to be set. The setting option changes each time the touch switch is pressed. Reference: f serial port B is used for RS-485 communications, RS-422A must be set as its communication type. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 165 Section System Settings 6-8 6-9 Starting Operation After completing screen data transmission and setting the communication conditions, connect the NT31/NT31C to the host and start operation. Note Check the operation of all screen data and host programs carefully before using them. If incorrect, the system may operate unpredictably. Switching to the RUN Mode and Starting Operation Press the Quit touch switch on the System Menu screen or other screen. The NT31/NT31C switches to the RUN mode and starts operation. The operation at the start is as follows. Display of The System Initialization Screen When establishing the communication with a host, the System initializing character string is displayed on the screen. If the communication with the host cannot be established, the System initializing screen remains up. If this is the case, check the settings at the host and the PT side, the cables and wiring. In addition, creating screen number 9000 enables the display of a screen other than the System initialization screen. Transmission of The Contents of Memory Tables If the Resume Function memory switch is set to ON, or if the initial values of the memory tables are used, the contents of the numeral/character-string memory tables are copied to the allocated words at the host. ↓ Display of The Startup Screen The startup screen is displayed on reading the contents (screen number of the screen to be displayed) of the first word of the PT status control area. If the contents are not correct for a screen number, or there is no data registered for the set screen number, an error message is displayed. Confirming the Communications between the NT31/NT31C and the Host Execute the host program and confirm that the following operations are performed normally. • Confirm that the NT31/NT31C screens switch in accordance with the host program. If the screens do not switch correctly, check the connection between the host and the NT31/NT31C, and also check if the hardware settings are correct. For details, refer to Section 4 Connecting to the Host from the RS-232C Port, or Section 5 Connecting to the Host from the RS-422A/485 Port. • Confirm that the operation results of touch switch and numeric value/character string input at the NT31/NT31C are sent to the host correctly by displaying the contents of the host words and bits using a Programming Device (e.g. CX-Programmer). If the results of operations at the NT31/NT31C are not sent to the host correctly, check the setting of the display elements. For details on setting display elements, refer to the description of each display element in the Reference Manual. 6-9 System Settings The NT31/NT31C allows a variety of functions which are convenient during operation to be set with memory switches. This section describes the memory switch settings relating to the operation environment. Since the memory switch settings are backed up to the flash memory by the battery in the NT31/NT31C, they are not cleared when the power is switched OFF. 6-9-1 Memory Switch Setting Screens There are four memory switch setting screens. The required screen can be displayed by using the [ ] (next screen) and [ ] (previous screen) touch switches. 166 Section System Settings 6-9 The four memory switch setting screens are shown below. [ ] (next screen) [ ] (previous screen) [ ] (next screen) [ ] (previous screen) [ ] (next screen) [ ] (previous screen) [ ] (next screen) [ ] (previous screen) Memory Switch Settings A list of the memory switch settings is presented below. • Start-up Wait Time page 167 • Key Press Sound page 168 • Buzzer Sound page 169 • Printer Controller page 170 • Print Method page 172 • Screen Saver Movement page 173 • Screen Saver Start up Time page 175 • Hist. Disp. Method page 177 • Resume Function page 179 • Comm. Auto-return page 181 • Time-out Interval page 183 • Retry Counts page 184 • Comm. A Method page 155 (For the bar code reader, refer to page 186.) • Comm. B Select page 165 • Comm. B Method page 155 For details on each setting, refer to the pages indicated. 6-9-2 Setting the Start-up Wait Time The Start-up Wait Time is the time lapse until the NT31/NT31C switches to the RUN mode after its power has been switched ON or after it has been reset. Set this item if it takes some time for the host to start operation. Nothing is displayed during the Start-up Wait Time. The setting range is 0 to 10 seconds. The default (factory) setting is 00sec. 167 Section System Settings 6-9 Set the system start-up wait time by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press Start-up Wait Time to display the required time lapse. The setting option changes each time the touch switch is pressed, according to the following sequence. 01 02 03 .... 09 10 00 01 .... To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 6-9-3 Setting the Key Press Sound It is possible to set whether or not the key sound is sounded when a touch switch on the NT31/NT31C screen is pressed. • ON: When a touch switch is pressed, the key sound sounds for 0.2 seconds. • OFF: The key sound does not sound when touch switches are pressed. The default (factory) setting is ON. 168 Section System Settings 6-9 Set the key press sound by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press Key Press Sound to display ON or OFF. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 6-9-4 Setting the Buzzer Sound The NT31/NT31C has a function for sounding a buzzer in response to an instruction from the host, or when an error occurs. It is possible to set whether or not the buzzer actually sounds with the memory switches. • ON: The buzzer sounds in response to instructions and when an error occurs. • OFF: The buzzer does not sound in response to instructions or when errors occur. • ERROR ON: The buzzer sounds only when an error occurs. The default (factory) setting is OFF. 169 Section System Settings Reference: 6-9 There are other instructions and settings relating to the buzzer, but this memory switch setting has the highest priority. For details on the buzzer, refer to 2-15-5 Buzzer Function in the Reference Manual. Set the buzzer sound by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press Buzzer Sound to display ON, OFF, or ERROR ON. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 6-9-5 Setting the Printer Controller The NT31/NT31C has a function for printing out data at a printer connected to it in response to an instruction from the host or operation at the NT31/NT31C. Three types of printer can be connected to the NT31/NT31C: select the type used with this memory switch setting. • ESC/P: Printers that conform to Epson’s ESC/P 24-J83C (color) printer control specifications or printers that conform to Epson’s ESC/P 24-J82 (monochrome) control specifications. 170 Section System Settings 6-9 • PC-PR201H: Printers that can emulate the PC-PR201H, made by NEC Corp. • PCL 5: Printers that conform to the PCL 5 printer control specifications. Note that the NT31 can only be used with the monochrome Tone setting and does not support color printing. For the NT31, the Print Method is fixed as Tone. The default (factory) setting is ESC/P. Reference: In addition to this setting, NT31C has the Print Method setting (page 172). For details on the print function, refer to 2-15-7 Print Function in the Reference Manual. Set the printer controller setting by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press Printer Controller to display the required printer type. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 171 Section System Settings 6-9 6-9-6 Setting the Print Method (NT31C Only) The NT31/NT31C has a function for printing out data at a printer connected to it in response to an instruction from the host or operation at the NT31/NT31C. When using the NT31C, the currently displayed screen image or other data can be printed out in color. You can select whether screen data is actually printed out in color, or in monochrome tones that represent colors, with this memory switch setting. When PCL 5 is set for Printer Controller, the setting is fixed as Tone. • Color: Color images are printed in color. • Tone: Color images are printed in monochrome tones. The default (factory) setting is Tone. Reference: In addition to this setting, NT31C has the Printer Controller setting (page 170). For details on the print function, refer to 2-15-7 Print Function in the Reference Manual. Set the print method setting by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press Print Method to display the required printing method. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. 172 Section System Settings 6-9 • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 6-9-7 Setting Screen Saver Movement The NT31/NT31C has a function to prevent the formation of an afterimage by turning off the screen display if no operation is performed for a certain period of time, and then displaying character strings at random positions and in random colors (the colors only change for the NT31C). The Screen Saver Movement setting determines whether or not these character strings are displayed while the screen display is off. If Display is selected, the character string stored in character string memory table No. 0 is displayed. If Display erase is selected, the character string is not displayed, and the backlight is also turned off while the screen display is off. The default (factory) setting is Display erased. The screen saver can be canceled, and former screen redisplayed, by any of the following operations. • Touching any part of the touch panel • Screen switching due to PT status control area operations • Screen switching due to bit memory table operations • Execution of any of the following PT status control bit operations: • Changing the backlight mode • Screen printing (change from OFF to ON) • Screen display (change from OFF to ON) Reference: The time before the screen is turned OFF is set by the Screen Saver Start up Time setting. For details, refer to 6-9-8 Setting the Screen Saver Start-up Time (page 175). Even if its operation has been set with the Screen Saver Movement setting, the screen saver function will not be executed if 000 is set for Screen Saver Start up Time. Screen saver function is enabled only through RUN mode of NT31/NT31C. In System Menu or System Installer mode, this function is not started. 173 Section System Settings 6-9 Set the screen saver operation by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the second memory switch setting screen. Press Screen Saver Movement to display Display or Display erased. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 174 Section System Settings 6-9 6-9-8 Setting the Screen Saver Start-up Time The NT31/NT31C has a function to maximize the service life of the backlight and prevent the formation of an afterimage by turning off the screen display and the backlight if no operation is performed for a certain period of time. The Screen Saver Start up Time setting determines the time interval before the screen saver function operates. The setting range is 0 to 255 minutes. The default (factory) setting is 10 minutes. If 000 is set, the screen saver function does not operate. The screen saver can be canceled, and previous screen redisplayed, by any of the following operations. • Touching any part of the touch panel • Screen switching due to PT status control area operations • Screen switching due to bit memory table operations • Execution of any of the following PT status control bit operations: • Changing the backlight mode • Screen printing (change from OFF to ON) • Screen display (change from OFF to ON) Reference: It is possible to display the character string stored in character string memory table No. 0 at random positions and in random colors while the screen display is off. For details, refer to 6-9-7 Setting Screen Saver Movement (page 173). Note however that, when this feature is used, the backlight does not go off. For details on the screen saver function, refer to 2-15-4 Screen Saver Function in the Reference Manual. Screen saver function is enabled only through RUN mode of NT31/NT31C. In System Menu or System Installer mode, this function is not started. 175 Section System Settings 6-9 Set the screen saver start-up time by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the second memory switch setting screen. Set a time in the input field to the right of Screen Saver Start up Time. Each of the digits can be incremented or decremented by pressing the associated + and − keys. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 176 Section System Settings 6-9 6-9-9 Setting the History Display Method The NT31/NT31C features the display history record function, which records the time at which screens are displayed during operation and the number of times they are displayed, and the alarm history record function, which continually monitors bit statuses at the host and records the time when bits come ON and the number of times they come ON. The Hist. Disp. Method setting determines whether — when these record data are displayed in sort by occurrence — the records are displayed in a progression from newest to oldest or from oldest to newest. • From Old Data: The records are displayed in sequence from the oldest to newest. • From New Data: The records are displayed in sequence from the newest to oldest. The default (factory) setting is From New Data. Reference: When the voltage of the NT31/NT31C’s built-in battery becomes low, the history record contents cannot be retained. For details on the display history record function and the alarm history record function, refer to 2-15-1 Display History Record Function and 2-15-2 Alarm History Record Function in the Reference Manual. 177 Section System Settings 6-9 Set the history display method by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the second memory switch setting screen. Press Hist. Disp. Method to display the required display order. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 178 Section System Settings 6-9 6-9-10 Setting the Resume Function The NT31/NT31C has a function to keep the contents of the memory tables even when the power to the NT31/NT31C is OFF and write back them to the host when the power is turned ON. If the resume function is OFF, the memory tables are initialized to these initial values on switching to the RUN mode. If the resume function is ON, these are not initialized and are kept the battery-backed up contents. When the memory table is initialized, its contents are reset to the initial state that is set by the Support Tool. When the system is started up the next time, the screen is displayed using the previous contents of the memory table. • ON: The resume function is used. • OFF: The resume function is not used. The default (factory) setting is OFF. Reference: When the voltage of the NT31/NT31C’s built-in battery becomes low, the memory table contents cannot be retained even if ON is set for the resume function. For details on the resume record function, refer to 2-15-3 Resume Function in the Reference Manual. 179 Section System Settings 6-9 Set the resume function by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the second memory switch setting screen. Press Resume Function to display the required setting. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 180 Section System Settings 6-9 6-9-11 Setting the Automatic Reset Function The NT31/NT31C has a function for ignoring communication errors and automatically returning to the RUN mode when they occur. The Comm. Auto-return setting determines whether the automatic reset function is effective or not. • ON: When a communication error occurs, the NT31/NT31C automatically returns to the RUN mode without displaying an error screen (the System Initializing screen may be displayed). • OFF: When a communication error occurs, an error screen is displayed and operation stops. Pressing OK on the error screen returns the NT31/NT31C to the RUN mode. The default (factory) setting is OFF. Reference: If a communication error occurs when OFF is set for Comm. Auto-return, the NT31/NT31C makes the number of attempts at communication with the host specified by the setting for the Retry Counts touch switch (page 184). If communication cannot be re-established in any of these attempts, an error screen is displayed. For details on communication errors, refer to 7-2-5 Communication Errors and Their Remedies (page 237). 181 Section System Settings 6-9 Set the automatic reset function by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the third memory switch setting screen. Press Comm. Auto-return to display the required setting. The setting option changes each time the touch switch is pressed. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 182 Section System Settings 6-9 6-9-12 Setting the Time-out Interval The NT31/NT31C goes into the time-out error status if no response is received from the host within a fixed time. The Time-out Interval setting specifies the time lapse at which time-out is judged to have occurred. The setting range is 1 to 10 seconds. The default (factory) setting is 1 second. Reference: Whether or not an error screen is displayed when a time-out error occurs is determined by the setting for the Comm. Auto-return memory switch. Set the time-out interval by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the third memory switch setting screen. Press Time-out Interval to display the required time lapse. The setting option changes each time the touch switch is pressed, according to the following sequence. 01 02 03 .... 09 10 01 .... To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. 183 Section System Settings 6-9 • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 6-9-13 Setting the Retry Count The NT31/NT31C does not immediately display an error screen when a communication error occurs, but tries to re-establish communication. The Retry Counts setting specifies the number of attempts to be made to re-establish communication. If communication cannot be recovered within this number of attempts, the following happens depending on the setting made for the Comm. Auto-return memory switch (page 181). • Comm. Auto-return ON: Operation in the RUN mode is continued without displaying an error screen. Regardless of the setting made for Retry Counts, attempts to re-establish communication are repeated until normal communication is achieved. • Comm. Auto-return OFF: The RUN mode is ended and an error screen is displayed. On pressing the OK touch switch on the error screen, the screen displayed immediately before is redisplayed and attempts are made to re-establish communication. The System Menu can be displayed from the error screen by pressing any two of the four corners of the touch panel simultaneously. The setting range is 0 to 255 times. The default (factory) setting is 5 times. Reference: For details on communication errors, refer to 7-2-5 Communication Errors and Their Remedies (page 237). 184 Section System Settings 6-9 Set the retry count by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. Press [↓] (next screen) or [↑] (previous screen) to display the third memory switch setting screen. Set a number of times in the input field to the right of Retry Counts. Each of the digits can be incremented or decremented by pressing the associated + and − keys. To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 185 Section 6-10 Setting the Bar Code Reader Input Function 6-10 Setting the Bar Code Reader Input Function The NT31/NT31C has a bar code reader input function which allows a bar code reader to be connected and bar code data to read as character strings into character string input fields. This section describes the communication conditions for the bar code reader and the setting method for confirming the input data. Reference: For details on bar code reader types and connection methods, refer to 3-4 Connecting a Bar Code Reader in this manual and for details on how to use a bar code reader refer to 3-7 Input of Numeric Values and Character Strings in the Reference Manual. The bar code reader is connected to serial port A. This means that serial port B must be used for communications with the host. Communication Condition Settings for Bar Code Readers Setting Item Function Setting Options Page Data bit length Sets the bit length for the data bits. 7* or 8 bits Page 187 Stop bit length Sets the stop bit length for the data. 1 or 2* bits Page 187 Parity bit Sets the parity bit for the data. None, odd, even* Page 187 Communications speed Sets the communications speed for the bar code reader 4800, 9600*, or 19200 bps Page 187 Input method Sets the method for confirming data when it is input to a character string input field. Manual: The data is confirmed with a touch switch. The data can be corrected and character strings can be added. Auto: The data is automatically confirmed when it is input. Manual*, Auto Page 187 * Default (factory) setting Setting the Communication Conditions and Setting Method Set the bar code reader communication conditions and method of confirmation at input by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Memory Switch. 186 Section 6-10 Setting the Bar Code Reader Input Function Press [↓] (next screen) or [↑] (previous screen) to display the fourth memory switch setting screen. Press Comm. A Method to select Bar-Code Reader. The setting option changes each time the touch switch is pressed. Press the Set touch switch to the right of Comm. A Method. Display the required setting for each item by pressing the touch switches. The setting option changes each time the touch switch is pressed. Press Quit. Pressing Abort on the communication condition/confirmation method setting screen causes the NT31/NT31C to return to the memory switch setting screen (4/4) without executing setting (with the previous settings still effective). On completion of communication condition/confirmation method setting, the NT31/NT31C returns to the memory switch setting screen (4/4). 187 Setting the Bar Code Reader Input Function Section 6-10 To set other memory switches, select the relevant screen using the [ ] (next screen) or [ ] (previous screen) touch switch, then make the setting. • To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. • To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE MODE MENU screen with the previous settings still in effect. 188 Section 6-11 System Maintenance 6-11 System Maintenance The NT31/NT31C has the following maintenance and check functions. Item Function Page I/O Settings Adjustment of display panel contrast and brightness of the backlight. Page 189 Calendar Check Display and setting of the time data of the NT31/NT31C clock function. Page 193 PT Settings Direct connection setting of the screen data in the NT31/NT31C and display of the setting statuses of the serial ports. Page 195 Display history record Display and printing of display history record data. Page 196 Alarm history record Display and printing of alarm history record data. Page 198 Screen data check Display of each screen stored in the NT31/NT31C. Page 200 Device check Checking of the I/O functions of the NT31/NT31C. Page 203 I/F check Page 213 I/O check Checking of the communication functions of the NT31/NT31C. This section describes how to use these functions. 6-11-1 I/O Settings This function is used to adjust the contrast of the display panel and the brightness of the backlight. With the NT31/31C, you can adjust the contrast and brightness settings using either of the following two methods. Setting from the System Menu Adjusting the contrast: Select System Menu/Maintenance Mode/I/O Settings/ Contrast Adjust. Adjusting the brightness: Select System Menu/Maintenance Mode/I/O Settings/ Brightness Adjust. Setting Using Special Screen During PT Operation You can set the brightness and contrast by displaying the screen with the following number, using a touch switch with a switch screen function, or by specifying the display screen in the PT status control area. Screen number 9030: Brightness and contrast adjustment screen. Contrast Adjustment The NT31/NT31C allows the contrast to be adjusted in 100 steps. The CONTRAST ADJUST screen enables you to make the adjustment while actually checking the contrast on the screen. Once the contrast has been set, it remains in effect even if the power is turned OFF or the NT31/NT31C is reset (and even if the voltage of the built-in battery becomes low). 189 Section 6-11 System Maintenance Setting from the System Menu Adjust the contrast of the display panel by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Settings. Select Contrast Adjust. Adjust the contrast with the touch switches in the left half of the screen. [ ]: Increase 10 steps []: Increase 1 step []: [ ]: Decrease 1 step Decrease 10 steps Press Quit. The contrast is set and the NT31/NT31C returns to the I/O SETTINGS MENU screen. 190 Section 6-11 System Maintenance Setting Using Brightness and Contrast Adjustment Screen Display screen number 9030 using either a touch switch with switch screen function, or by specifying the display screen in the PT status control area. Adjust the contrast with the touch switches in the right half of the screen. [ ]: Increase 10 steps []: Increase 1 step []: [ ]: Decrease 1 step Decrease 10 steps Press Quit. The contrast is set, and the NT31/NT31C returns to the previous screen. Backlight Brightness Adjustment The NT31/NT31C allows the brightness of the backlight to be adjusted in 3 steps. The BRIGHTNESS ADJUST screen enables you to make the adjustment while actually checking the brightness on the screen. The length of hours the backlight lasts in a normal temperature are as follows. High contrast: Low, middle contrast: 10,000 hours (NT31-ST121-EV2, NT31C-ST141-EV2) 50,000 hours (NT31-ST122-EV2, NT31C-ST142-EV2) 25,000 hours (NT31-ST121-EV2, NT31C-ST141-EV2) 191 Section 6-11 System Maintenance Setting from the System Menu Adjust the backlight brightness by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Settings. Select Brightness Adjust. Adjust the contrast with the High, Middle, and Low touch switches in the left half of the screen. Press Quit. The contrast is set and the NT31/NT31C returns to the I/O SETTINGS MENU screen. 192 Section 6-11 System Maintenance Setting Using Brightness and Contrast Adjustment Screen Display screen number 9030 using either a touch switch with switch screen function, or by specifying the display screen in the PT status control area. Adjust the brightness with the touch switches (High, Middle, Low) in the left half of the screen. Press Quit. The brightness is set, and the NT31/NT31C returns to the previous screen. 6-11-2 Displaying/Setting the Calendar and Clock The NT31/NT31C has a clock function for setting and displaying the date and time. This section describes how to display and set the clock data by menu operation from the System Menu. Reference: The clock function does not strictly check the date and day of the week settings. When setting the clock data, be sure to set the correct date and day of the week. If a mistake is made — for example entering a value in the range 13 to 19 when entering the month — the buzzer sounds three times. Make sure that the data is correct when the month changes. Numeral memory tables 247 to 255 are reserved for the clock function. Clock data can be displayed and set during operation of the NT31/NT31C by using these numeral memory tables. For details on the clock function, refer to 2-15-6 Clock Function in the Reference Manual. No clock data is set on shipment from the factory. The clock data is backed up by the built-in battery of the NT31/NT31C. If the battery voltage becomes low, the clock data cannot be retained when the power to the NT31/NT31C is turned OFF or the NT31/NT31C is reset and the clock function will not operate correctly. When writing to the screen data memory is disabled by the setting made for System Setting in the System Installer mode, it is not possible to set the date and time. 193 Section 6-11 System Maintenance Display/set clock data by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Calendar Check. Press Set. If you are just checking the display, press Quit at this point; the NT31/NT31C will return to the MAINTENANCE MODE MENU screen. Set the date. Each of the digits of the year, month, date, hour, minute, and second settings, and the day of the week setting, are touch switches: press these touch switches to change the corresponding settings. Press Quit. The clock data is set and the NT31/NT31C returns to the date and time display. • Pressing Abort causes the NT31/NT31C to return to the date and time display without executing setting (with the previous settings still effective). 194 Section 6-11 System Maintenance 6-11-3 Checking the PT Setting Status The direct connection settings of the NT31/NT31C screen data, and the settings for serial port A and serial port B, can be checked. Screen Configuration and Display Contents There are the following three PT setting status screens. [ ] (next screen) [ ] (next screen) [ ] (previous screen) [ ] (previous screen) [ ] (next screen) [ ] (previous screen) Display Contents of The First Screen Item Meaning Screen Data Type The host type set for the screen data PT Control Area Word at the host to which the PT status control area is allocated PT Notification Area Word at the host to which the PT status notify area is allocated Window Control Area Word at the host to which the window control area is allocated Numeric Expression Default for the method of interpretation of the contents of host words to which numeral memory tables are allocated (numeric value storage method). Expansion I/F Type of unit installed at the expansion interface connector Compatibility Sets whether or not to use NT30/620 compatible mode for screen data. (Sets whether to operate as a normal NT31/631 or emulate many key NT30/620 characteristics.) Display Contents of The Second Screen Item Meaning Comm. Port A Communication type set for serial port A (fixed as RS-232C) Comm. Method Communication method set for serial port A Comm. Setting Communication conditions set for serial port A (display contents differ according to the communication method) Display Contents of The Third Screen Item Meaning Comm. Port B Communication type set for serial port B (RS-232C/RS-422A) Comm. Method Communication method set for serial port B Comm. Setting Communication settings set for serial port B (display contents differ according to the communication method) 195 Section 6-11 System Maintenance Display Method Display the PT setting statuses by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select PT Settings. Switch the screen as required by pressing the [↓] (next screen) or [↑] (previous screen) touch switch. Press Quit. The NT31/NT31C returns to the MAINTENANCE MODE MENU screen. 6-11-4 Displaying and Printing the Display History Record The display history record function is a function that records the order of display of each screen during operation, and the number of times each screen is displayed. Only the screens for which the display history screen attribute has been set in advance are processed by this function. The record data can be displayed, and printed out at a printer connected to the NT31/NT31C by operation from the System Menu. This section explains how to display and print out the display history record data recorded in the NT31/NT31C. Note that there are two display methods sort by occurrence (display time order) and sort by frequency (order of number of times displayed). 196 Section 6-11 System Maintenance Reference: With the NT31/NT31C, the record data can also be displayed by calling screen No. 9001 (sort by occurrence) or screen No. 9002 (sort by frequency) during the RUN mode. For details on the display history record function, refer to 2-15-1 Display History Record Function in the Reference Manual. The order of display for sort by occurrence display (from oldest record or from newest record) is set with the Hist. Disp. Method memory switch (page 177). The printing method and other information must be set in advance with the Printer Controller (page 170) and Print Method (page 172) memory switches. Display and print the display history record data by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Display History. Select Sort by Occurrence or Sort by Frequency. If necessary, select the next or previous screen by pressing [↓] (next screen) or [↑] (previous screen). The example screen to the left shows a display for the sort by occurrence method (from oldest record). 197 Section 6-11 System Maintenance If required, press Prt. to print the display history record data. Press Quit. The NT31/NT31C returns to the DISPLAY HISTORY MENU screen. Example Print-out All of the recorded data is printed out in the same order as on the currently displayed screen. Example: Sort by occurrence, from oldest record No. Scrn YY/MM/DD HH:MM Comment 1 1 98/01/12 10:21 Coolant Error 2 2 98/01/12 11:53 Motor Error 3 8 98/01/13 09:35 Compressor Error 4 2000 98/01/13 14:22 Emergency Stop 01/01 6-11-5 Displaying and Printing the Alarm History Record The alarm history record function is a function that continually monitors, during operation, the status of bits at the host designated in advance with a bit memory table, and records the time when these bits come ON, and the number of times they come ON. The record data can be displayed, and printed out at a printer connected to the NT31/NT31C by operation from the System Menu. This section explains how to display and print out the alarm history record data recorded in the NT31/NT31C. Note that there are two display methods sort by occurrence (ON time order) and sort by frequency (order of number of times the bits have come ON). Reference: With the NT31/NT31C, the record data can also be displayed by registering an alarm history display element on the screen. For details on the alarm history record function, refer to 2-15-2 Alarm History Record Function in the Reference Manual. The order of display for sort by occurrence display (from oldest record or from newest record) is set with the Hist. Disp. Method memory switch (page 177). The printing method and other information must be set in advance with the Printer Controller (page 170) and Print Method (page 172) memory switches. 198 Section 6-11 System Maintenance Display and print the alarm history record data by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Alarm History. Select Sort by Occurrence or Sort by Frequency. If necessary, select the next or previous screen by pressing [↓] (next screen) or [↑] (previous screen). The example screen to the left shows a display for the sort by occurrence method (from oldest record). If required, press Prt. to print the display history record data. 199 Section 6-11 System Maintenance Press Quit. The NT31/NT31C returns to the ALARM HISTORY MENU screen. Example Print-out All of the recorded data is printed out in the same order as on the currently displayed screen. Example: Sort by occurrence method, from oldest record No. Comment YY/MM/DD HH:MM 01/01 1 Remote I/O Error 98/02/06 16:02 2 PIC Unit Error 98/02/07 09:21 3 Cycle Time Over 98/02/17 15:44 6-11-6 Checking Screen Data The NT31/NT31C allows the registered screens (Nos. 1 to 3999) to be displayed and checked by operation from the System Menu. Reference: Window screens cannot be displayed by operation from the System Menu. Only the user screens (Nos. 1 to 3999) can be displayed. Screens for system use cannot be displayed. Specifying The Display Method Specify the display method for the screens as indicated in the table below. Setting Item Display of Lamp/ Touch SW No. Function Allows designation of whether the bit number of the lamp bit set for a lamp or touch switch is displayed or not. The display format is as follows L (: area type, : bit number). Setting Options ON, OFF* Display of Memory Allows designation of whether the table numbers of numeral and character string Table No. memory tables are displayed or not. The display format for numeral memory tables is N and the display format for character string memory tables is S. This function is valid for the following display elements. - Numeral displays - Character string displays - Bar graphs - Numeral setting input fields (including thumbwheel type) - Character string input fields ON, OFF* Display of image/ Library No. Allows designation of whether image/library code numbers are displayed or not. ON, OFF* Display of Broken Line Frame Allows designation of whether or not broken line frames are displayed around the display elements for showing the positions registered. ON, OFF* * Default (factory) setting Reference: Each setting of the screen data check is effective only on this menu. Exiting from this screen data check menu resets the settings to the default (all the settings are set to OFF). 200 Section 6-11 System Maintenance Operations On The SCREEN DATA CHECK Screen The function shown below can be set on the SCREEN DATA CHECK screen. Use this function as required when displaying complex screens on which multiple display elements have been registered overlapping each other. a) Equivalent to 2 touch switches (14.4 mm) c) b) Equivalent to 2 touch switches (14.4 mm) a) Display the previous display element on the upper most portion of the screen in the order in which the display elements were registered (excluding fixed display elements). b) Display the next display element on the upper most portion of the screen in the order in which the display elements were registered (excluding fixed display elements). c) Return to the screen on which screens are specified. 201 Section 6-11 System Maintenance Displaying the SCREEN DATA CHECK Screen Display the SCREEN DATA CHECK screen by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select Screen Data Disp. Specify the screen to be displayed in the input field in the middle of the screen. Each of the digits can be incremented or decremented by pressing the associated + and − keys. Press Set. Press the touch switches to specify the display method in each case. The setting option changes each time a touch switch is pressed. 202 Section 6-11 System Maintenance Press Quit to return to the screen number selection screen. Press Disp. BOILER OPERATION T 015003 RUN T 015301 STOP L 020000 L 020005 Start Confirmation Stop Confirmation T 016312 ERROR L 020013 Error Occurrence BOILER OPERATION T 015003 RUN T 015301 STOP L 020000 L 020005 Start Confirmation Stop Confirmation T 016312 ERROR Touching the top or bottom of the screen changes the way the display elements overlap each other in the order in which they are registered. In this example, the bottom portion of the touch switch, which is under the lamp, will be displayed over the lamp. When you have finished checking the screen, press the central part of the screen to return to the screen number selection screen. L 020013 Error Occurrence If you wish to continue by checking another screen, repeat the operation, starting by specifying the screen number. To end the operation, press Quit on the screen number selection screen. The NT31/NT31C returns to the MAINTENANCE MODE MENU screen. 6-11-7 Device Check The NT31/NT31C provides checks on the functions of the following items. • Buzzer Page 203 • LED Page 204 • LCD Page 206 • Backlight Page 207 • Screen data memory Page 207 • Touch switches Page 210 • Battery voltage Page 212 Checking the Buzzer Check if the buzzer sounds correctly. 203 Section 6-11 System Maintenance Reference: The buzzer will sound in this check regardless of the setting made with the Buzzer Sound memory switch. Check the buzzer by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select Buzzer Check. • If the buzzer functions correctly, it will sound continuously. At this time, the Buzzer Check touch switch will be displayed in reverse video. • To stop the buzzer while it is sounding, press the Buzzer Check touch switch again. Checking the RUN LED 204 Check if the RUN LED functions normally. Section 6-11 System Maintenance Check the RUN LED by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select LED Check. • If the RUN LED is functioning normally, it will operate as follows. At this time the LED Check touch switch will be displayed in reverse video. Lit in green OFF lit in red OFF lit in green... • To end the LED check, press the LED Check touch switch on the DEVICE CHECK MENU screen again. 205 Section 6-11 System Maintenance Checking the LCD (Screen Display) Check if the LCD (screen display) functions normally by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select LCD Check. • The check screen displays all the dots on the screen: either press anywhere on the touch panel or wait for three seconds and all the dots will be cleared. With the NT31C, the display and clearance of all the dots on the screen is repeated for each color in turn (red green blue magenta cyan yellow white black). On completion of the display and clearance of all dots, the NT31/NT31C returns to the DEVICE CHECK MENU screen. • To abort the LCD check, press the top right corner of the touch panel. The NT31/NT31C will return to the DEVICE CHECK MENU screen. 206 Section 6-11 System Maintenance Checking the Backlight Check if the backlight functions normally by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select Backlight Check. • If the backlight is normal, it flashes. At this time, the Backlight Check touch switch is displayed in reverse video. • To end the backlight check, press the Backlight Check touch switch again. Screen Data Memory Check Reference: Check if the screen data memory is functioning normally. In the screen data memory check, a write test is performed on the screen data memory. Since all the screen data in the NT31/NT31C is lost in this check, confirm that this data is backed up at the Support Tool or memory unit before executing it. If writing to the screen data memory is disabled by the setting for System Settings in the System Installer mode, it is not possible to execute a screen data check. 207 Section 6-11 System Maintenance Once a screen data check has been started, it cannot be stopped. Check the screen data memory by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select Screen Memory. Press Execute. • During the check, the message Checking Now... is displayed. 208 System Maintenance Section 6-11 • On normal completion of the check, the message Memory Check OK is displayed. • If an error is discovered in the check, the message Memory Check NG is displayed. After confirming the result of the check, press Quit. The NT31/NT31C returns to the DEVICE CHECK MENU screen. 209 Section 6-11 System Maintenance Checking Touch Switches Check whether or not the touch switches function normally by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select Touch Switch. Press the touch switches displayed on the screen. A touch switch is normal if it is displayed in reverse video while pressed. To end the check, press the touch switch at the top right corner (NT31: displayed in reverse video; NT31C: displayed in yellow). The NT31/NT31C will return to the DEVICE CHECK MENU. 210 System Maintenance Reference: Section 6-11 The functions of touch switches pressed during the I/O check are not notified to the host. The check cannot be performed until the touch switch at the top right corner is displayed in reverse video (for NT31) or displayed in yellow (NT31C). Start the check after the status of the touch switch at the top right corner has changed. 211 Section 6-11 System Maintenance Checking the Battery Voltage Check the voltage of the NT31/NT31C’s built-in battery by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select Device Check. Select Battery. The voltage is within the normal range. or The voltage is lowered. is displayed. After confirming the result of the check, press Quit. The NT31/NT31C returns to the DEVICE CHECK MENU screen. 212 Section 6-11 System Maintenance Note When The voltage is lowered is displayed, replace the built-in battery immediately. For details on the replacement method, refer to 7-3-1 Replacing the Battery (page 242). 6-11-8 Checking Interfaces The NT31/NT31C allows the following communication functions to be checked. • Communication with the Support Tool Page 213 • Communication at serial ports Page 215 • Communication with printers Page 218 213 Section 6-11 System Maintenance Checking Communication with the Support Tool Check communication with the Support Tool by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select I/F Check. Select Tool Comm.. The check on communication with the Support Tool starts. • If communication with the Support Tool is normal, data transmitted from the Support Tool is displayed as hexadecimal data when received by the NT31/NT31C. 214 Section 6-11 System Maintenance After confirming the result of the test, press Quit. The NT31/NT31C returns to the I/F CHECK MENU screen. Checking Communication at Serial Ports Check communication at the serial ports (A, B). Check Screen The check screen and check method differ according to the communication method set for the port to be checked. For Host Link Example: Serial port A while using the host link Press Execute to start the check. The data for checking communication is sent to the host, and is displayed as the Sending Data in hexadecimal. • If communication with the host is normal, the reply from the host is displayed at Received Data in hexadecimal. • If a communication error occurs while checking the communication conditions with the host, a communication error screen is displayed. Since this indicates that there is a communication fault, check the communication cables and settings. For NT Link (1:1 or 1:N) Example: Serial port B while using the NT Link (1:N) Press Execute to start the check. The data for checking communication is sent to the host, and is displayed as ∗∗ symbols at Sending Data. • If communication with the host is normal, the reply from the host is displayed at Received Data as ∗∗ symbols. • If a communication error occurs while checking the communication conditions with the host, a communication error screen is displayed. Since this indicates that there is a communication fault, check the communication cables and settings. 215 Section 6-11 System Maintenance For Memory Link Example: Serial port A while using the memory link The check is started as soon as the check screen is displayed. Send the command from the host. • If communication with the host is normal, the data received from the host is displayed in hexadecimal text code at Received Data. • If nothing is displayed at Received Data when the command is sent from the host, there is a communication fault: check the communication cables and settings. For a Bar Code Reader The check starts when the check screen is displayed. Read data with the bar code reader in this status. • If communication with the bar code reader is normal, the read character strings are displayed in hexadecimal text code at Received Data. • If nothing is displayed at Received Data when data is read with the bar code reader, there is a communication fault: check the communication cables and settings. 216 Section 6-11 System Maintenance Check Method Check communication with the serial ports by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select I/F Check. Select Comm. Port A or Comm. Port B. The check screen is displayed (Check screen, page 215). After confirming the result of the check, press Quit. The NT31/NT31C returns to the I/F CHECK MENU screen. 217 System Maintenance Section 6-11 Checking Communication with a Printer Check communication with a printer by following the menu operation from the System Menu shown below. Ver 3.10 Select Maintenance Mode. Select I/O Check. Select I/F Check. Select Printer. Confirm that a printer is connected to the NT31/NT31C, then press Execute: Printer Interface Check will be printed out at the printer. • While data is being sent to the printer, the message Checking Now... is displayed. • When the sending of data to the printer is completed, Finished Normal by Printer Interface Check is displayed. 218 Programming Console Function Section 6-12 • If data does not reach the printer within 60 seconds after sending starts, the message ‘Finished Printer output failed’ is displayed. After confirming the result of the check, press Quit. The NT31/NT31C returns to the I/F CHECK MENU screen. 6-12 Programming Console Function The NT31/NT31C has been equipped with the Programming Console function, which allows it to be used like a C200H-PRO27-E Programming Console for CPM1, CPM2A, CPM2C, CQM1, CQM1H, C200HX/HG/HE (-Z)E, CS-series CS1G/CS1H, or SRM1 PLCs. Except for recording (saving) ladder programs on cassette tape and replaying (reading) them, almost all the functions of a Programming Console can be executed. Note When the programmable controller functions are used, carefully check that the system is safe before carrying out the following operations. • Changing monitor data • Switching the operating mode • Forced set or reset • Changing a present value or set value 6-12-1 Usable Systems The Programming Console function can communicate with the PLC with the communication methods indicated in the following table. 219 Section 6-12 Programming Console Function Communication Method Communication Type NT Link (1:1) RS-232C NT Link (1:N) Applicable PLCs Connected Port C200HE-CPU42-(Z)E(*1) C200HG-CPU43-(Z)E(*1) C200HG-CPU63-(Z)E(*1) C200HX-CPU44-(Z)E(*1) C200HX-CPU64-(Z)E(*1) C200HX-CPU65-ZE(*1) C200HX-CPU85-ZE(*1) CPM2A-30CD-(*1) CPM2A-40CD-(*1) CPM2A-60CD-(*1) CPM2C-10-(*2) CPM2C-20-(*2) CQM1-CPU4-EV1(*1) CQM1H-CPU21(*1) CQM1H-CPU51(*1) CQM1H-CPU61(*1) SRM1-C02-V2 CPU built-in RS-232C port CPM1-10CDR- CPM1-20CDR- CPM1A-10CD- CPM1A-20CD- CPM1A-30CD- CPM1A-40CD- Peripheral port (*3) CS1G-CPU42-E(V1)(*1) CS1G-CPU43-E(V1)(*1) CS1G-CPU44-E(V1)(*1) CS1G-CPU45-E(V1)(*1) CS1H-CPU63-E(V1)(*1) CS1H-CPU64-E(V1)(*1) CS1H-CPU65-E(V1)(*1) CS1H-CPU66-E(V1)(*1) CS1H-CPU67-E(V1)(*1) CPU built-in RS-232C port Peripheral port (*4) *1: The peripheral port Programming Console always has priority. If a Programming Console is connected later, the Programming Console function of the NT31/NT31C is invalidated and operation from the NT31/NT31C becomes impossible. *2: The CPM2C-CN111 Connecting Cable splits the PLC’s Communication Port into a RS-232C port and a peripheral port. *3: An RS-232C cable cannot be connected to the peripheral port. An RS-232C adapter (CPM1-CIF01) is required. *4: The RS-232C cable cannot be directly connected to the peripheral port. An RS-232C converting cable (CS1W-CN118) is required. Reference: Note that the Programming Console function cannot be used with CPM1, CQM1, and C200HX/HG/HE PLCs of the following lot numbers. CPM1: 5, *6 where * is a number in the range 1 to 9 or the letter X or Y. CQM1: 3, 4, 5, *6 where * is a number in the range 1 to 9 or the letter X or Y. C200HX/HG/HE: 5 *6 where * is a number in the range 1 to 9 or the letter X or Y. 220 Programming Console Function Section 6-12 6-12-2 Connection Method CQM1, CQM1H, C200HX/HG/HE(-ZE), or SRM1 The connection method is exactly the same as for the NT Link (1:1). Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. * When using the Programming Console function with a CQM1H, turn ON pin 7 of the DIP switch on the front of the CQM1H’s CPU Unit. CPM1 or CPM2A The connection method is the same as for the NT Link (1:1). With a CPM1, connect the RS-232C cable to the peripheral port via a CPM1-CIF01 RS-232C Adapter or CPM1-CIF11 RS-422A Adapter. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. CPM2C The connection method is the same as for the NT Link (1:1). Connect to the PLC’s communications connector with a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, a CPM1-CIF01 RS-232C Adapter, or a CPM1-CIF11 RS-422A Adapter. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. * When using the Programming Console function with a CPM2C, turn ON pin 2 of the DIP switch on the front of the CPM2C’s CPU Unit. CS1G/CS1H The connection method is exactly the same as for the NT Link (1:N) (standard or high-speed). Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. The standard or high-speed 1:N NT Link can be used. The Programming Console function can be used only when the PT’s unit number is set to 0. Only one unit using the Programming Console function can be connected to each of the PLC’s ports (built-in RS-232C port and peripheral port). When using the Programming Console function, make sure that the maximum unit number for the PT is set to 0 in the PLC Setup of the CS1G/CS1H. With the CS1G/CS1H, the Programming Console function cannot be used simultaneously at both the built-in RS-232C port and peripheral port. Furthermore, the Programming Console function cannot be started at the RS-232C port while a Programming Console is connected to the peripheral port. 221 Section 6-12 Programming Console Function 6-12-3 Method of Use The Programming Console screen is displayed by operating the system menu as described below. Ver 3.10 Select Expansion Mode. Select Programming Console. The Programming Console screen is displayed. Press the Programming Console sheet keys (touch switches) for the operation. Press the Quit touch switch to exit the screen. An error is displayed if a wrong communication protocol is selected or a Programming Console is connected to the peripheral port.(*1) *1: With the CS1G/CS1H, the Programming Console function cannot be used simultaneously at both the built-in RS-232C port and peripheral port. Reference: When an error screen is displayed, the system menu can be displayed by pressing two of the four corners of the touch panel simultaneously. The Check touch switch on the screen can also be used to display the system menu, but it will not work unless the cause of the error has been removed. If the system menu is not displayed when the Check touch switch is pressed, press two of the four corners of the touch panel to return to the system menu. 222 Section 6-12 Programming Console Function Key Operations Mode Selection Keys, Mode Lock Key The display element on the Programming Console screen shown below comprises the mode selection keys, which change the operation mode of the PLC, and the mode lock key, which prevents unintended mode changes. Mode selection keys Mode lock key The RUN, MONITOR, and PROGRAM mode selection key elements are touch switches and pressing them causes the PLC operation mode to change (unlike an actual Programming Console, it is possible to switch directly between the RUN mode and the PROGRAM mode.) When the Programming Console function is started, the PLC operation status is read and reflected at the PLC. The mode lock key element is also a touch switch, and it alternates between the lock ON (with no key displayed) and lock OFF (with key displayed) states when pressed. During the lock ON state, mode selection key operations are ineffective. The mode displays change as indicated in the figures below during the lock ON status and during the lock OFF status. When the Programming Console function starts, the lock ON status is established. If the RUN, MONITOR, or PROGRAM mode selection key is pressed in the lock OFF status, the mode changes and the lock ON status is established. During Lock OFF RUN mode MONITOR mode PROGRAM mode MONITOR mode PROGRAM mode During Lock ON RUN mode Programming Console Keyboard The Programming Console keyboard used on the screen when the Programming Console function is used is comprised entirely of touch switches (shown by the dashed line frames in the figure below). On pressing a touch switch, a key operation is executed. However, since there is a discrepancy between the size of the displayed keys and the size of the touch switches, take care to press as close to the center of the key as possible by referring to the figure below. In addition, if the connected host is the CS1G/CS1H, the Programming Console key sheet for the CS Series is automatically displayed. 223 Programming Console Function Section 6-12 Standard Programming Console Key Sheet Programming Console Key Sheet for CS1 Series Differences with Respect to Programming Consoles • Programs cannot be stored (recorded) or read (replayed). If it is necessary to store or read a program, use a Programming Device. • It is not possible to adjust the volume of the key press sound. Whether or not the key press sound sounds is determined by the setting for the Key Press Sound memory switch of the NT31/NT31C. It sounds when the setting is ON and does not when the setting is OFF (page 168). • If an error occurs when using the Programming Console function, an error screen is displayed. Whether or not the buzzer sounds at this time is determined by the setting for the Buzzer Sound memory switch of the NT31/NT31C (page 169). Reference: A communications error will occur if you use the Programming Console function to change the communications settings (in the PLC Setup) that govern the port to which the NT31/NT31C is connected. In this case, the Programming Console function will be unusable. 224 Section 6-13 Device Monitor Function 6-13 Device Monitor Function The NT31/NT31C has been equipped with the Device Monitor function which can be used to change the PLC’s operating mode, read/change words in the PLC’s data areas, and display the PLC’s error log of a CS1G/CS1H, CPM1, CPM2A, CPM2C, CQM1, CQM1H, C200HX/HG/HE(-Z)E, or SRM1. The Device Monitor can perform the following operations: • Changing the PLC’s operating mode • Displaying/changing the contents of words, displaying/changing the status of bits, force-setting/force-resetting the status of bits (Registration Monitor) • Listing the contents of a range of words (Continuous Monitor) • Displaying the error log and clearing errors (Error Log) This section provides an overview of the Device Monitor function and explains how to connect to the PLC. For more details, refer to 2-16 Device Monitor Function in the Reference Manual. ! Caution Be sure that it is safe to proceed before using the Device Monitor function to perform one of the following operations from the PT. Changing monitored data Switching the PLC’s operating mode Force setting or force resetting bits Changing PVs or SVs Reference: The Device Monitor function can be used with Ver. 3.0 and higher versions of the PT system program only. The Device Monitor functions are almost identical to the functions of the Data Access Console (DAC). The Device Monitor function cannot be used with host link or memory link communications. 225 Section 6-13 Device Monitor Function 6-13-1 Compatible Systems The following table shows the combinations of communications methods and PLCs that can support the PT’s Device Monitor function. Communications method 1:1 NT Link 1:N NT Link PLC model C200HS-CPU21-E C200HS-CPU23-E C200HS-CPU31-E C200HS-CPU33-E C200HE-CPU32 (-Z)E C200HE-CPU42 (-Z)E C200HG-CPU33 (-Z)E C200HG-CPU43 (-Z)E C200HG-CPU53 (-Z)E C200HG-CPU63 (-Z)E C200HX-CPU34 (-Z)E C200HX-CPU44 (-Z)E C200HX-CPU54 (-Z)E C200HX-CPU64 (-Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE CPM1-10CDR-*1 CPM1-20CDR-*1 CPM1A-10CD-*1 CPM1A-20CD-*1 CPM1A-30CD-*1 CPM1A-40CD-*1 CPM2A-30CD- CPM2A-40CD- CPM2A-60CD- CPM2C-10-*2 CPM2C-20-*2 CQM1-CPU4-EV1 CQM1H-CPU21 CQM1H-CPU51 CQM1H-CPU61 SRM1-C02-V2 C200HE-CPU32 (-Z)E C200HE-CPU42 (-Z)E C200HG-CPU33 (-Z)E C200HG-CPU43 (-Z)E C200HG-CPU53 (-Z)E C200HG-CPU63 (-Z)E C200HX-CPU34 (-Z)E C200HX-CPU44 (-Z)E C200HX-CPU54 (-Z)E C200HX-CPU64 (-Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE CQM1H-CPU21 CQM1H-CPU51 CQM1H-CPU61 SRM1-C02-V2 CS1G-CPU42-E(V1) CS1G-CPU43-E(V1) CS1G-CPU44-E(V1) CS1G-CPU45-E(V1) CS1H-CPU63-E(V1) CS1H-CPU64-E(V1) CS1H-CPU65-E(V1) CS1H-CPU66-E(V1) CS1H-CPU67-E(V1) *1: A CPM1-CIF01 RS-232C Adapter is required. *2: Use a Conversion Cable (CPM2C-CN111 or CS1W-CN114/118), CPM1-CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect to the PLC. 6-13-2 Connection Method CQM1H or C200HX/HG/HE(-ZE) The 1:1 NT Link or 1:N NT Link can be used. The connection method is exactly the same as for the 1:1 NT Link or 1:N NT Link. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. CQM1 or C200HS The 1:1 NT Link can be used. The connection method is exactly the same as for the 1:1 NT Link. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. CPM1, CPM2A, or SRM1 The 1:1 NT Link can be used in all CPUs and the 1:N NT Link can also be used in -V2 and higher versions of the SRM1. The connection method is exactly the same as for the 1:1 NT Link or 1:N NT Link. With a CPM1, connect the RS-232C cable to the peripheral port via a CPM1-CIF01 RS-232C Adapter or CPM1-CIF11 RS-422A Adapter. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. CPM2C 226 The 1:1 NT Link can be used. The connection method is the same as for the NT Link (1:1). Connect to the PLC’s communications connector with a CPM2C- Section 6-13 Device Monitor Function CN111 or CS1W-CN114/118 Connecting Cable, a CPM1-CIF01 RS-232C Adapter, or a CPM1-CIF11 RS-422A Adapter. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. CS1G/CS1H The 1:N NT Link (standard or high-speed) can be used. The connection method is exactly the same as for the 1:N NT Link. Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting to the Host from the RS-422A/485 Port for details on connecting to the PLC. 6-13-3 Method of Use The Device Monitor screen is displayed by operating the system menu as described below. Ver 3.10 Select Expansion Mode. Select Device Monitor. An error message will be displayed if the wrong communications protocol is selected. The Device Monitor screen is displayed. Reference: When an error screen is displayed, the system menu can be displayed by pressing two of the four corners of the touch panel simultaneously. The Check touch switch on the screen can also be used to display the system menu, but it will not work unless the cause of the error has been removed. If the system menu is not displayed when the Check touch switch is pressed, press two of the four corners of the touch panel to return to the system menu. For more details on operations of the Device Monitor function, refer to 2-16 Device Monitor Function in the Reference Manual. 227 Section 6-14 Version Display 6-14 Version Display Use the Version Display function to check the version of the NT31/NT31C’s system program. The Version Display screen shows the model, creation date, and version of the system program installed in the NT31/31C. 6-14-1 Method of Use The Version Display screen is displayed by operating the system menu as described below. Ver 3.10 Select Expansion Mode. Select Version Display. The system program’s version information will be displayed as described below. Press the Quit touch switch to exit the Version Display screen and return to the Expansion Mode screen. • • • • PT Model: System program: Version Date PT model number System program name System program version Date program was created. This screen is an example. Actual screens will show the information specific to the PT and system program being used. After checking the version information, press the Quit touch switch to exit the Version Display screen and return to the Expansion Mode screen. Reference: The PT model always shows the model number of the ivory model of the PT. The B suffix will not be displayed, even for black models. The system program’s version number is also displayed in the upper-right corner of the System Menu. The creation date does not always match the file date of the system program installed with the System Installer. 228 SECTION 7 Troubleshooting and Maintenance This section describes the action to take when errors occur in the PT, and how to carry out maintenance and inspection to prevent the occurrence of errors. 7-1 7-2 7-3 7-4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Responding to Displayed Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2-1 Errors Occurring at Start of Operation and Their Remedies . . . . . . . . . . . . . . . . . 7-2-2 Errors Occurring during Operation and Their Remedies . . . . . . . . . . . . . . . . . . . 7-2-3 Errors Occurring on Screen Data Initialization and Transmission . . . . . . . . . . . . 7-2-4 Errors in the System Installer Mode and Their Remedies . . . . . . . . . . . . . . . . . . . 7-2-5 Communication Errors and Their Remedies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance of the NT31/NT31C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3-1 Replacing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 233 233 235 236 237 237 239 242 243 229 Section Troubleshooting 7-1 7-1 Troubleshooting When a fault relating to the operation of the NT31/NT31C occurs, find the symptoms in the table below and respond by following the corresponding Remedy indicated in the table. Note 1. Confirm system safety before turning the power ON/OFF or resetting. 2. Do not disassemble the PT for repair or modification. NT31/NT31C Symptoms Power LED fails to come ON Nothing is displayed on the screen. Cannot communicate with the S Support pp Tool Cannot communicate with the host Cannot switch from the system initializing screen. Communication error message is displayed when communicating to the host. Cause Remedy Power is not being supplied. Check the connections and make sure that power is supplied correctly. (3-1-3 Power Supply Connection, page 31) Power supply fuse has blown. Contact your OMRON service center. Screen No. 0 has been read at the host side. This is not an error. Change the screen number from screen number 0. (Setting the screen number to 0 turns the screen off.) The system startup waiting time has not elapsed yet. This is not an error. The display will appear after the waiting time has elapsed. The Transmit mode has not been established. Display the System Menu and select the Transmit mode. (6-6 Transmitting the Screen Data, page 153) Not connected to the Support Tool. Check the installation of the connector cable. (3-2 Connecting to the Support Tool, page 33) The PT model setting and direct connection setting at the Support Tool do not match the NT31/NT31C. Using the PT Configuration settings of the Support Tool, set the PT model and direct connection settings that match the NT31/NT31C. Memory switch settings do not match. Check the communication setting in the Memory Switch menu of the Maintenance mode, and match the communication protocol settings for the host and NT31/NT31C. (6-7 Setting Conditions for Communications with Host by Using Memory Switches, page 155) NT31/NT31C and host are not correctly connected. Check that the type, length, and installation of the connector cable match the specifications. (Section 4 Connecting to the Host from the RS-232C Port, and Section 5 Connecting to the Host from the RS-422A/485 Port) In an RS-422A/485 connection, the terminator setting is incorrect. Make the NT31/NT31C and PLC termination resistance settings correctly. (Section 4 Connecting to the Host from the RS-232C Port, and Section 5 Connecting to the Host from the RS-422A/485 Port) In an NT Link (1:N) connection, there Make the settings again so that there is no is duplication in the unit numbers. duplication. (6-7-4 Setting the NT Link (1:N) Method (Standard/High-speed), page 161) The buzzer has sounded and the RUN OFF. U LED is O The touch panel does not respond. p The PLC mode has changed to the monitor mode. 230 The power to the NT31/NT31C, NT-AL001 or host is OFF. Check the power supply. Malfunction due to external noise Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. The NT31/NT31 has developed trouble. Contact your OMRON service center. Malfunction due to external noise Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. The touch panel is broken. Test the touch panel with I/O Check in the MAINTENANCE MODE menu. If there is an error, contact your OMRON service center. The NT31/NT31C changes the mode This is an NT31/NT31C specification. When using a when host link communication is PLC that can also be connected using the NT Link used. method, use an NT Link connection (there is no mode change with the NT Link method). Section Troubleshooting NT31/NT31C Symptoms Cause 7-1 Remedy The graph display does not change. One of the percentage display settings — −100%, 0%, or 100% — is incorrect. Set the −100%, 0%, and 100% values in the following relationship: −100% value < 0% value < 100% value The trend graph display does not agree with the actual time axis. The cycle for graph display update processing is longer than the set sampling cycle. Delete other elements on the same screen as the trend graph that are allocated to the host and have a high update frequency. Or lengthen the sampling cycle. The Programming Console function cannot be used. The communication settings are incorrect. Set the communication method as follows when using the Programming Console function. With C-series PLC: 1:1 NT Link With CS1-series PLC: 1:N NT Link (standard or high-speed) A Programming Console is connected. It is not possible to use a Programming Console and the Programming Console function at the same time. Disconnect the Programming Console. The PLC does not support the Programming Console function. Not all PLCs support the Programming Console function. Check the model of PLC you are using. (6-12 Programming Console Function, page 219) The system program for other vendor’s PLCs has been installed. (PLC models other than OMRON.) The Programming Console function can be used only when the system program for OMRON PLCs is installed. Install the correct system program. The communications settings are not correct. Set the communication method as follows when using the Device Monitor function. With C-series PLCs: 1:1 NT Link or 1:N NT Link With CS-series PLCs: 1:N NT Link (standard or high-speed) The PLC does not support the Device Monitor function. Not all PLCs support the Device Monitor function. Check the model of PLC you are using. Refer to 6-13 Device Monitor Function for details. The system program installed in the PT is for a PLC maker other than OMRON. The Device Monitor function can be used only when the PT is connected to a PT with the system program for OMRON PLCs installed. Install a system program that supports the Device Monitor function. Since the memory table is allocated to the host memory, the display is updated in accordance with the contents of the host memory. When the contents of the memory table are set as a fixed value, do not allocate the memory table to the host. The battery voltage has dropped and the data in the memory table has been destroyed. Replace the battery and execute memory table initialization. (7-3-1 Replacing the Battery, page 242, and 6-4-5 Initializing the Memory Tables, page 145) Since ON is set for the resume function, the initial values of the screen data memory are not written to the memory tables. Execute memory table initialization. (6-4-5 Initializing the Memory Tables, page 145) If the resume function does not need to be used, use the NT31/NT31C with the resume function OFF. (6-9-10 Setting the Resume Function, page 179) The numeral memory table is specified as the destination for a mathematical table’s results. Calculations are executed continuously while the PT is operating and the calculation results are automatically written to the memory table. Specify another numeral memory table or a word in the host. The Device Monitor function cannot be used. The memory table display contents differ from the initial value set at the pp Tool. Support 231 Section Troubleshooting NT31/NT31C Symptoms Updating of numeric values and text is d l d delayed. Some of the elements arranged g on a normal di l d screen are not displayed. Cause 7-1 Remedy Malfunction due to external noise Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. There are too many numeral/text displays on the displayed screen. Reduce the number of numeral/text displays on the screen for which updating is delayed. The cycle time is extended due to heavy processing at the host. Shorten the host cycle time. In an RS-422A/485 connection, there is illegal branching or an erroneous terminator setting. Wire correctly by referring to Section 5 Connecting to the Host from the RS-422A/485 Port. The quantity of read data exceeds the stipulated restriction. Check the maximum number of elements by referring A of the g to Display p y Restrictions in Appendix pp R f M l C h screen d i Reference Manual. Create the data again and then transmit all of the screen data in a batch to the NT31/NT31C. The total of the element coefficients for the displayed screen is greater than 1024. On an overlapping screen, Since the data is transmitted from some of the set elements the host in screen units, the number are not displayed. of elements on the overlapping screen has exceeded the maximum permissible without being checked by the Support Tool. Check the maximum number of elements by referring to Display Restrictions in Appendix A of the Reference Manual. Create the screen data again and then send all the screen data in a batch to the NT31/NT31C. The System Menu cannot be called up. Display System Menu under Change System Settings in the System Installer mode is set to Disabled. In the System Installer mode, set Display System Menu to Enabled (page 151). The following System Menu operations are not possible. - Establishing the Transmit mode - Displaying the memory switch setting screens - Screen data memory check - Displaying the initialization menu - Displaying the calendar/time setting screen Screen Memory Protect under Change System Setting in the System Installer mode is set to Disabled. In the System Installer mode, set Screen Memory Protect to Enabled (page 151). Screen Memory Protect has been set to Disabled because the PT power supply was turned OFF during deletion of screen data. Do not turn the PT power OFF during deletion of screen data. In the System Installer mode, first change the setting for Screen Memory Protect to Enabled, then repeat the screen data delete operation (pages 151 and 152) Cannot input numeric values The upper/lower (max./min.) limit check for numeric value input is in effect. Check the screen data’s upper/lower (max./min.) limit check setting for numeric value input, and correct it if necessary. Refer to 2-12 Inputting Numeric Values in the Reference Manual for details. Cannot input numeric values/character strings. Bit 5 of the PT status control area (numeral/character string input) is set to 1 (ON). Set bit 5 to 0 (OFF). Refer to 2-2-1 PT Status Control Area (Host ↔ PT) in the Reference Manual for details. The interlock function is set for the input field and the controlling interlock bit is OFF. Inputs are prohibited in input fields when the corresponding interlock bit is OFF. Check the status of the corresponding interlock bit and turn it ON. Window screen does not open Bit 6 of the PT status control area (PT window opening) is set to 1 (ON). Set bit 6 to 0 (OFF). Refer to 2-2-1 PT Status Control Area (Host ↔ PT) in the Reference Manual for details. Cannot switch screens with touch switches Bit 4 of the PT status control area (PT screen switching) is set to 1 (ON). Set bit 4 to 0 (OFF). Refer to 2-2-1 PT Status Control Area (Host ↔ PT) in the Reference Manual for details. Touch switch does not work. (Buzzer sounds.) The interlock function is set for the touch switch and the controlling interlock bit is OFF. Touch switches are disabled when the corresponding interlock bit is OFF. Check the status of the corresponding interlock bit and turn it ON. 232 Section Responding to Displayed Error Messages NT31/NT31C Symptoms The display is dim. Cause 7-2 Remedy Insufficient contrast or brightness Increase the contrast/brightness (pages 189 and 191). Backlight defective, or its life has expired Replace the backlight (page 240). The display is too faint. The contrast is too high. Reduce the contrast (page 189). The digits in numeral display come out as *. The number of digits of a numeric value in a numeral memory table exceeds the set number. • Confirm the values of the PLC words allocated to the numeral memory table. The numeric value in the numeral memory table exceeds the number of display digits. • Check the values of the PLC words allocated to the numeral memory table entry. ”**” or ”***” is displayed in the numeral display or numeral input field. 7-2 • Allocate one PLC word to each numeral memory table. • Allocate only one word to each numeral memory table entry if the numeral display or numeral input field has 4 digits or less. Responding to Displayed Error Messages When the NT31/NT31C displays an error message, find the corresponding symptoms in the appropriate table below and respond by following the Remedy indicated in the table. For details of the error messages displayed when using memory unit and corrective action to take for them, refer to 3-5 Using a Memory Unit (NT31/NT31C with V) in page 37 or 3-6 Using a Memory Unit (NT31/NT31C without V) in page 45. 7-2-1 Errors Occurring at Start of Operation and Their Remedies The table below shows the errors that can occur when the power to the NT31/NT31C is turned ON and when operation starts, and their remedies. Cause Remedy [No Comm. Protocol] Set the comm. Protocol by MAINTENANCE MODE. Message No communication protocol has been set. Communication protocol and screen data type are mismatched Using the memory switches, set the communication method to be used for communication with the host. (6-7 Setting Conditions for Communications with Host by Using Memory Switches, page 155) [Screen Data Error] Screen Data corrupted. Initialize Screen Memory, and download Screen Data again. - The power was switched OFF during screen data initialization, checking, or transmission. - Transmission of screen data was interrupted. - Illegal data has been written to the screen data memory. Initialize the screen data memory by operation at the System Menu, then re-transmit the screen data. (6-4-1 Clearing Screen Data, page 138) If the problem persists, contact your OMRON service center. [No Screen Data] No Screen Data is saved in Screen Memory. Download Screen Data using by the Support Tool. Then set the PT to the TRANSMIT MODE, and download Screen Data again. No screen data is registered. Transmit screen data from the Support Tool. 233 Section Responding to Displayed Error Messages Message 7-2 Cause Remedy [No Direct Connection Info.] No Direct Connection Information is set in Screen Data. Set Direct Connecting Information in Screen Data using by the Support Tool. Then set the PT to the TRANSMIT MODE and download Screen Data again. Allocated words have not been set for the PT status control area and PT status notify area. Allocate words for the PT status control area and PT status notify area with the Support Tool and then transmit the direct connection information to the NT31/NT31C. [Incorrect Screen Data] Screen Data in Screen Memory do not match with the System Program. Initialize Screen Memory, and download Screen Data again. The type of registered screen data does not match that at the NT31/NT31C. Initialize the screen data memory, then transmit the correct screen data. (6-4-1 Clearing Screen Data, page 138) [No Starting Screen] Specified Starting Screen is not saved. Fix Screen Data using by the Support Tool. Then set the PT to the TRANSMIT MODE and download Screen Data again. No data is registered for either the screen number set in the PT status control area or the Initial Screen set with the Support Tool. Or the screen number which does not exist are registered. Either specify a screen number for which data is registered at the PT status control area, or set the screen as the Initial Screen in the System settings under PT Configuration at the Support Tool. [Touch Panel is disconnected] The touch panel cable (film cable) inside the NT31/NT31C is disconnected. Contact your OMRON service center. [Memory Switch Corrupted] Because Memory Switch setting was last. Initialized Memory Switch setting. Press Confirm to return to the SYSTEM MENU. The memory switches have been initialized due to discovery of an error in the memory switch settings. Set the memory switches again using the System Menu and the System settings under PT Configuration at the Support Tool. (Section 6 System Menu Operation) If the problem recurs, contact your OMRON service center. [Calendar Data Error] Calendar Data is incorrect. Set to the MAINTENANCE MODE and set Calendar Data. There is an error in the date/time values due, for example, to low battery voltage. Check the battery voltage by checking the color of the RUN LED and with the battery check in the System Menu; if the voltage is low, replace the battery with a new one. (Checking the Battery Voltage, page 212, and 7-3-1 Replacing the Battery, page 242) If the battery voltage is confirmed to be normal, set the calendar clock correctly from the System Menu. (6-11-2 Displaying/Setting the Calendar and Clock, page 193) [Backup Data Error] Memory table and History data was initialized by backup failure. It can be caused by lowered voltage of the battery. Initialization has been executed because of an error in the backup data area. Check the battery voltage by checking the color of the RUN LED and with the battery check in the System Menu; if the voltage is low, replace the battery with a new one. (Checking the Battery Voltage, page 212, and 7-3-1 Replacing the Battery, page 242) The re-transmit the memory table data from the Support Tool. If the voltage is normal and the problem recurs, contact your OMRON service center. [With memory switch setting screen] Invalid Comm. Method Protocol settings for serial port A and serial port B are mismatched. Refer to Possible Combinations of Communication Method Settings in page 156 and set the protocol of serial port A and serial port B so that their settings are matched. * Set serial port A to None when connecting the Support Tool and the host at the same time. 234 Section Responding to Displayed Error Messages 7-2 7-2-2 Errors Occurring during Operation and Their Remedies The table below shows the errors that can occur during operation of the NT31/NT31C and their remedies. Message Cause Remedy [Address Setting Error] Addressing Error exists in the Screen. Correct address setting by the Support Tool. The host side allocated words and bits set with the Support Tool are incorrect. Set correct words and bits after checking the area used at the host side by referring to PLC Memory Map in Appendix D of the Reference Manual or the operation manual for the PLC being used. [Memory Table No. Error] Memory table No. is out of limit. Correct the table No. by the Support Tool. The memory table number set with the Support Tool is outside the range for the number of memory tables set in the system memory. Either increase the number of memory tables in the System settings under PT Configuration at the Support Tool, or set the memory table number again within the established range. [Programming Console Error] Setting of Programming Console Function is inadequate. It can be caused by: This PLC does not support Prog g Console Function. gramming Protocol mismatch. Set the PLC to NT Link. “PROGRAMMING CONSOLE” is connected to PLC. The communication settings are incorrect. Set the communication method/communication port as follows when using the Programming Console function. With C-series PLCs:1:1 NT Link With CS-series PLCs: 1:N NT Link (standard or high-speed) The PLC used does not support the Programming Console function. Not all PLCs support the Programming Console function. Check the model of the PLC you are using. (6-12 Programming Console Function, page 219) A Programming Console is connected. It is not possible to use a Programming Console and the Programming Console function at the same time. Disconnect the Programming Console. The connecting cable is defective. Check the cable connection and perform a conductivity test. If there is a fault, replace the cable. Malfunction due to external noise Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. A Programming Console is connected. It is not possible to use a Programming Console and the Programming Console function at the same time. Disconnect the Programming Console. The communication conditions at the PLC have been changed in accordance with the NT31/NT31C Programming Console function. Set the communication conditions at the PLC to match the conditions set in the System Menu. [Programming Consol Error] Programming Console Function does not RUN. It can be caused by: Connecting cable is faulty. “PROGRAMMING PROGRAMMING CONSOLE CONSOLE” is connected to PLC. Protocol mismatch between the PT and PLC. Set the PLC to NT Link. 235 Section Responding to Displayed Error Messages 7-2 7-2-3 Errors Occurring on Screen Data Initialization and Transmission The table below shows the errors that can occur when the NT31/NT31C data is initialized, and during data setting and transmission, and their remedies. Message Cause Remedy [Flash Memory Error] Flash Memory I/O Error. If this happens frequently, Flash Memory may be broken. Press Reset Switch to restart. There is a hardware fault, or the flash memory (memory for storing screen data) has reached the end of its service life. If the same message is displayed even after clearing the screen data or transmitting screen data several times, contact your OMRON service center. [Calendar Data Error] Calendar Data is incorrect. Set to the MAINTENANCE MODE and set Calendar Data. Hardware fault, or system program error Set the calendar clock again from the System Menu. If the problem recurs, delete the program in the System Installer mode, then re-install the program. (6-5-2 Clearing/Installing the System Program, page 149) If this does not solve the problem, contact your OMRON service center. [Tool Transmit Error] ∗∗∗∗ Error detected while downloading by the following case: faulty connecting cable. corrupted data by noise. The connecting cable is defective. Check the cable connection and perform a conductivity test. If there is a fault, replace the cable. (Appendix F Making the Cable for Connecting a PLC, page 269) Malfunction due to external noise Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. [Tool Transmit Error] Check Sum Error occurs while downloading by the following case: corrupted data by noise. Malfunction due to external noise Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. [Tool Transmit Error] Time-out Error occurs while downloading by the following case: faulty connecting cable. The connecting cable is defective. Check the cable connection and perform a conductivity test. If there is a fault, replace the cable. [Tool Transmit Error] Reception was failed by Buffer Over Flow Error. The receive buffer has overflowed. Retransmit the data from the Support Tool. 236 Section Responding to Displayed Error Messages 7-2 7-2-4 Errors in the System Installer Mode and Their Remedies This section describes the errors that may occur in the System Installer mode of the NT31/NT31C, and the remedies for these errors. Message Cause Remedy System Program not exist or incorrect. - The system program has not been installed. - The system program has been deleted due to a hardware fault, or because the flash memory (memory for storing the system program) has reached its life. Select Download System Program and download the system program (6-5-2 Clearing/Installing the System Program, page 149). If this does not solve the problem, contact your OMRON service center. Unable to erase System Program. Hardware fault, or flash memory (memory for storing the system program) has reached its life. If the same message is displayed on repeating selection of Download System Program and attempting to delete the system program several times, contact your OMRON service center (6-5-2 Clearing/Installing the System Program, page 149). Unable to download System Program. - A communication error occurred during downloading of the system program. - Illegal data has been written into the screen data memory. - Hardware fault, or flash memory (memory for storing the system program) has reached its life. Select Download System Program and download the system program again (6-5-2 Clearing/Installing the System Program, page 149). Also refer to 7-2-3 Errors Occurring on Screen Data Initialization and Transmission (page 236), and take the corrective action described for tool transmission errors. If this does not solve the problem, contact your OMRON service center. Unable to write System Settings. Hardware fault, or flash memory (memory for storing the system program) has reached its life. If the same message is displayed on repeating writing of system settings several times, contact your OMRON service center. If writing is normally terminated after the error message was once displayed, the Memory Switch setting for system program may have been altered. In such a case, check and re-set the setting in the Memory Switch menu of the Maintenance mode. Unable to erase Screen Data. Hardware fault, or flash memory (memory for storing the system program) has reached its life. If the same message is displayed on repeating screen data deletion several times, contact your OMRON service center. 7-2-5 Communication Errors and Their Remedies This section describes the errors relating to communication that can occur during operation, and their remedies. Operation When a Communication Error Occurs When a communication error occurs, the error message is displayed at the NT31/NT31C, and the buzzer sounds, provided the setting made for Buzzer Sound in the System Menu is other than OFF. An error message is displayed provided the setting for the Comm. Auto-Return memory switch is not ON (note that some error messages are displayed even if the setting is ON). Operation When Communication Errors Occur When an error message is displayed, remove the cause of the error and then press the OK touch switch displayed on the screen. The NT31/NT31C will return to the screen that was displayed before the error occurred, and operation will restart. Display of Communication Errors For communication errors, the name of the port at which the error occurred, the error classification (send or receive error), the details of the error, the probable cause, and the remedy, are displayed as shown below. 237 Section Responding to Displayed Error Messages 7-2 Example: Parity error at serial port A Receive Errors The following errors can occur when receiving data. • Parity error • Framing error • Overrun error • FCS (sum value) error • Time out error • Data over flow error • PLC unit No. error (host link only) • NAK received (in the case of the host link, the end code is also displayed) • Undefined command error Send Errors The following errors can occur when receiving data. • Time out error • Data over flow error Probable Causes and Remedies Error Details Parity Error Framing Error Over-run Error FCS (Check Sum) Error 238 The remedies to take in accordance with the displayed cause are indicated in the table below. Displayed Probable Cause Remedy Communication parameters/ conditions set incorrectly. Check if the settings at the host for parity bit, frame length, communications speed, stop bit length and flow control agree with those at the NT31/NT31C. The connecting cables are not connected correctly. Check the communication cable connection and perform a conductivity test. If there is a fault, replace the cable. For details on communication cables, refer to Section 4 Connecting to the Host from the RS-232C Port, and Section 5 Connecting to the Host from the RS-422A/485 Port. Noise caused data corruption during communication. Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. Noise caused data corruption during communication. Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. The PLC is transmitting incorrect data. Check the operation at the host side. Section Maintenance of the NT31/NT31C Error Details Time-out Error Displayed Probable Cause 7-3 Remedy The connecting cables are not connected correctly. (Send/Receive) Check the communication cable connection and perform a conductivity test. If there is a fault, replace the cable. For details on communication cables, refer to Section 4 Connecting to the Host from the RS-232C Port, and Section 5 Connecting to the Host from the RS-422A/485 Port. The communication service of the host is stopped. (Send/Receive) Check that the host is capable of communicating with the NT31/NT31C (confirm that the communication settings of the host and NT31/NT31C match). Time-out Interval is too short. (Send) Set a longer value for Time-out Interval at the host side. Time-out Interval is too short. (Receive) Set a longer value for Time-out Interval in the System Menu. (6-9-12 Setting the Time-out Interval, page 183) It may also be possible to solve the problem by shortening the host cycle time. The unit # does not match that set on the PLC. Re-set the unit number at the host side to 0. Noise caused data corruption during communication. Carry out grounding work in accordance with the conditions by referring to 3-1-4 Grounding, page 32. NAK received —— Check the settings for allocated words and bits. If noise is a possible factor, distance the cable from sources of noise and insert a noise filter in the power supply line. If using the equipment in a location subject to a lot of noise, use a cable with a high degree of protection against noise for the transmission route. Also make the cable as short as possible. Undefined Command E Error The host is not supported. Check the PLC model used for the host. Instruction level 3 is not effective. Check that the instruction level setting for the host is level 1, 2, 3. Data Over Flow Error Communication command from the host is too long. (With memory link) Set flow control method in the host. Increase transmission interval. Command transmission to the host is not possible. Check the communication cable. Check the control method at the PT and the host. Increase the communication on speed when it to slow. PLC Unit No. Error 7-3 Maintenance of the NT31/NT31C Carry out maintenance work in order to ensure that the NT31/NT31C is always used in its optimum condition. WARNING Do not attempt to take the unit apart and do not touch any internal parts while the power is being supplied. Doing either of these may result in electrical shock. Spare PT It is advisable to have a spare NT31/NT31C available to minimize system downtime in the event of an NT31/NT31C failure or if the screen display becomes difficult to read due to deterioration of the display unit. Backlight When the backlight in the display is getting dim and the screen cannot be read easily, replace the backlight. The backlight can be replaced at the rear of the 239 Section Maintenance of the NT31/NT31C 7-3 NT31-ST121-EV2/NT31C-ST141-EV2 while it is mounted in an operation panel. The backlight for the NT31-ST122-EV2/NT31C-ST142-EV2 cannot be replaced by the user. Contact your OMRON service center when the backlight needs to be replaced. Replaceable Backlight Model NT31C-CFL01 (for both NT31-ST121-EV2/NT31C-ST141-EV2) Guide to Backlight Replacement Under normal conditions it can be assumed that the backlight will need to be replaced after about 25,000 hours when used at medium brightness (the figure is about 10,000 hours when used at the high brightness setting). However, the life of the backlight does vary, particularly in accordance with the temperature in the environment in which it is used, and it should be replaced when it is getting dim and the screen is getting hard to read. The life expectancy of the backlight for the NT31-ST122-EV2/NT31C-ST142-EV2 at high brightness is 50,000 hours. The backlight cannot be replaced by the user, however. Contact your OMRON service center when the backlight needs to be replaced. Notes on Replacing the Backlight Pay attention to the following points when replacing the backlight. • Carry out the replacement work in a location where there is no danger that dust or foreign bodies will enter the unit, and where no water will drip onto it. Do not touch the printed circuit boards of the NT31-ST121-EV2/NT31C-ST141-EV2 with your bare hands. Also, discharge the static electricity from your body before starting the work. • Do not carry the backlight unit by holding only its cable, or pull on the cable. Do not subject the backlight to excessive force or shock. • Do not disassemble the product to repair or modify it. Replacing the Backlight Use the following procedure to replace the backlight. WARNING Switch OFF the NT31-ST121-EV2/NT31C-ST141-EV2 power before replacing the backlight. Otherwise you could sustain an electric shock. CAUTION Do not touch the backlight immediately after switching OFF the power supply. Otherwise burn injuries may result due to the high temperatures. Replace the backlight by following the procedure given below: Procedure 1, 2, 3... 1. Turn the power supply to the NT31-ST121-EV2/NT31C-ST141-EV2 OFF. 2. Disconnect the terminal block wiring, the communication cable, and the printer cable. If a memory unit or interface unit is mounted, remove that unit also. 240 Section Maintenance of the NT31/NT31C 7-3 3. Open the cover of the CFL unit housing by following the procedure described below. a) Unscrew the screw in the center of the cover. The screw is designed so that it cannot be removed, but if it does come out for some reason and falls inside the PT, it must be extricated without fail. b) Open the cover while pressing the tabs at its left and right inward. c) When the cover has opened far enough, remove it. b b b 4. Remove the CFL unit by following the procedure described below. a) Disengage the connector. b) Sufficiently loosen the screw that secures the CFL unit. The screw is designed so that it cannot be removed, but if it does come out for some reason and falls inside the PT, it must be extricated without fail. c) Shift the CFL unit to the right. d) Pull out the CFL unit. 5. Fit a new CFL unit by following the procedure described below. a) Slot the projection on the left end of the CFL unit into the hole in the fixture inside the PT. b) Engage the CFL unit with the fixture inside the PT. Check that the CFL unit is in contact with the left end of the fixture and is parallel with the fixture during this engagement. c) Tighten the screw of the CFL unit to secure it. The tightening torque is 0.2 N@m. 241 Section Maintenance of the NT31/NT31C 7-3 d) Engage the connector of the CFL unit with the connector of the PT so that the red cable is at the left side. Insert the connector so that it clicks firmly into place. Red cable White cable d b Fixture inside the NT31-ST121-EV2/NT31C-ST 141-EV2 Backlight unit 6. Fit the cover and secure it with the screw. 7. Reconnect the wiring, cables, and units disconnected in 2, and tighten the screws. 8. Before starting normal operation, confirm that the following tests can be executed correctly by using the I/O check in the Maintenance menu. Also perform a communication test with the host. • Touch switch • Backlight 9. On confirming that all the tests in 8 can be executed normally, start operation. 7-3-1 Replacing the Battery The NT31/NT31C uses a lithium battery to back up the memory contents. The battery life is about 5 years if the NT31/NT31C is used in a location where the ambient temperature is 25C. If the temperature at the location of use is higher than this, the battery life will be shorter. Change the battery at suitable intervals in accordance with the operating environment of the NT31/NT31C. It is advisable to keep a spare battery so that the battery can be replaced immediately when replacement becomes necessary. Battery Type 3G2A9-BAT08 (for both NT31 and NT31C) Guide to Replacement Replace the battery in the following cases. The battery must be replaced within 5 days. • When 5 years have passed since the installation of a new battery. • When the RUN LED is lit in orange (during operation) or in red (when stopped). • When the message The voltage is lowered. is displayed on switching on the power or resetting the NT31/NT31C. • When The voltage is lowered is displayed in the Battery check in the battery check menu of the Maintenance mode. Battery Replacement Method Replace the battery by following the procedure given below. To protect the contents of the memory, the battery must be replaced within 5 minutes. Procedure 1, 2, 3... 242 1. Keep the power ON for at least 5 minutes and then turn it OFF. Section Inspection and Cleaning 7-4 Reference: Unless the power is kept ON for at least 5 minutes, the memory contents cannot be retained for more than 5 minutes without a battery. 2. Insert a flat blade screwdriver at the top of the battery cover located at the left of the rear face of the NT31/NT31C and pull it toward you. 3. Remove the battery that is secured under the battery cover, grip the cable, and pull the connector straight out. 4. Insert the connector of the new battery into the connector on the NT31/NT31C and fit the battery under the battery cover. When inserting the battery connector, make sure that the projection on it faces to the left, and press it fully home while keeping it straight. The connector of the new battery must be connected within 5 minutes after disconnecting the old battery’s connector. However, the battery can be replaced while the NT31/NT31C power is on, and in this case there is no time restriction. 5. Close the battery cover, making sure that the cable is not trapped. 7-4 Inspection and Cleaning Clean and inspect the NT31/NT31C regularly to ensure that it is always used in its optimum condition. Cleaning Method If the display is dirty the screen is difficult to see. Clean the screen from time to time as follows. • In daily cleaning, wipe the display with a soft dry cloth. If the soiling is particularly heavy, attempting to remove it by wiping with a dry cloth may damage the front sheet of the unit. In this case, wipe with a damp cloth. • If the soiling cannot be removed with a dry cloth, wet the cloth with diluted neutral detergent (2%), wring it out well and wipe the display with it. 243 Section Inspection and Cleaning 7-4 • If rubber or vinyl products, tape, etc., are left stuck to the display for long periods they will cause staining. If such items are stuck to the display, remove them during cleaning. Note Never use volatile solvents such as benzene or thinners, or chemical dusters. Inspection Method Point Inspected In normal environments, inspect the NT31/NT31C at intervals of between 6 months and a year. In environments that are extremely hot and humid, or very dusty environments, shorten the inspection interval. Items Required for The Inspection Prepare the following items before starting the inspection. • Screwdrivers (Philips, flat head) • Tester (or digital voltmeter) • Industrial alcohol • 100% cotton cloth • Hygrometer (required in some cases) • Thermometer (required in some cases) • Synchroscope (required in some cases) • Pen-writing oscilloscope (required in some cases) Points Inspected Inspect the following points to determine if there is any divergence from the stated criteria. If there is, either improve the surrounding environment so that the values fall within the stated range, or adjust the NT31/NT31C, for example by re-tightening screws. Inspection Details Criterion Power supply voltage Fluctuation in power supply terminal voltage Ambient environmental di i conditions Ambient temperature (temperature in the 0 to 50C operation panel) Thermometer Ambient humidity (humidity in the operation panel) 35% to 85% RH Hygrometer Presence/absence of dust Dust must not be settled Visual inspection Looseness of mounting brackets, etc. To be no looseness Philips screwdriver Connector connections of connecting cable To be fully inserted and locked, with no looseness Philips screwdriver Looseness of screws in external wiring To be no looseness Philips screwdriver Mounting g conditions diti Permissible voltage fluctuation range 20.4 to 26.4 VDC (24 VDC –15%, +10%) Inspection Instrument Conditions of external connecting cables Faults such as incipient disconnection Components with limited lives Brightness of the backlight Note 244 Tester Visual inspection Must be sufficiently bright. Visual inspection Backlight life: NT31-ST121-EV2/NT31C-ST141EV2: Brightness is halved after about 25,000 hours in use at medium brightness, or about 10,000 hours in use at high brightness. NT31-ST122-EV2/NT31C-ST142EV2: Brightness is halved after about 50,000 hours of use at high brightness. 1. Do not disassemble for repairs or modification. 2. The disposal of the unit (including batteries to be disposed and backlight) may be regulated by national or local authorities. Dispose of them in accor- Section Inspection and Cleaning 7-4 dance with the laws and regulations of the relevant country and local authority. Reference: Desire on replacing the NT31/NT31C When replacing the NT31/NT31C after discovering a fault during inspections, note the following points: Be sure to switch the power OFF before starting replacement. After replacement, check that the new NT31/NT31C is not subject to the same error. If a faulty unit is returned for repairs, write as detailed a description of the fault as possible and send this description together with the unit to the OMRON address indicated on the back cover of this book. 245 Appendix A Specifications General Specifications Specification Item Rated power supply voltage NT31-ST121-EV2/NT31C-ST141-EV2 24 VDC NT31-ST122-EV2/NT31C-ST142-EV2 Allowable power supply voltage range Allowable power interruption time Power consumption 20.4 VDC to 26.4 VDC (24 VDC –15% to +10%) Operating ambient temperature Storage ambient temperature Operating ambient humidity 0 to +50C Operating environment No corrosive gases Noise resistance Common mode: 1000 Vp-p (between power supply terminals and panel) No regulation 15 W max. –20 to +60C 35% to 85% (with no condensation) Normal mode: Conforms to IEC61000-4-4 2 kV (power line) 300 Vp-p Pulse width of 100 ns to 1 µs, pulse rise time of 1 ns Vibration resistance (operating) Shock resistance (operating) Dimensions Weight Panel cutout dimensions 10 to 57 Hz with 0.075 mm amplitude 57 to 150 Hz with 1G {9.8 m/s2} acceleration for 30 minutes in each of X, Y, Z directions 147 m/s2 {15G} 3 times in each of X, Y, and Z directions 195 (W) 142 (H) 54 (D) mm (With expansion unit mounted: 195 (W) 142 (H) 74 (D) mm) 1 kg max. 184 +0.5× 131 +0.5 mm 0 0 Circle of panel pressure 1.6 to 4.8 mm Enclosure ratings Front panel: Equivalent to IP65F (NEMA4)* Grounding D-type grounding (Ground to 100 Ω or less) * The NT31/NT31C may not be used at a location where it is exposed to splashing oil for a long period. 247 Appendix A Specifications Performance Specifications Display Specifications Item Specification NT31-ST121-EV2/NT31C-ST141-EV2 Display device Number of dots (resolution) 320 dots horizontally Size of a standard character NT 31-ST121-EV2 : Height 5.76 mm, Width : 2.88 mm NT 31C-ST141-EV2 : Height 5.76 mm, Width : 2.88 mm Effective display area 118.2 mm horizontally NT31: Display panel NT31-ST122-EV2/NT31C-ST142-EV2 NT31: Monochrome STN LCD (with backlight) NT31C: Color STN LCD (with backlight) 240 dots vertically 89.4 mm vertically (5.7 inches) View angle Up: Down: Left/right: NT31C: Up: Down: Left/right: 20 30 "30 45 60 "50 NT31: Up: Down: Left/right: NT31C: Up: Down: Left/right: 20 40 "45 30 50 "50 Display color NT31: Black, white (2 colors) NT31C: 8 colors (and intermediate colors can be displayed with tiling patterns) Life expectancy (until brightness 50,000 hours minimum reduced by half) Backlight g ( hi (white cold cathode tube) Contrast adjustment dj t t Adjustable in 100 levels by operation at the touch panel Life expectancy At low or medium brightness : 25,000 hours minimum At high brightness : 50,000 hours minimum At high brightness : 10,000 hours minimum Replacement Can be replaced from the rear Brightness adjustment Adjustable in 3 levels by touch switch operation at the touch panel Cannot be replaced by the user Automatic turn-off function Can be set to turn off in 1 to 255 minutes, or to remain on POWER (green LED) Lit while power is being supplied Indicators RUN Lit in green : Running normally, Memory unit automatic transmission done Flash in green : Memory unit automatic transmission being executed, memory unit automatic transmission error Lit in orange : Low battery voltage (during operation) Flash in red : Low battery voltage (when NT31/NT31C is stopped) *1: Time taken for brightness to reduce to half at normal temperature and humidity 248 Appendix A Specifications Panel Specifications Item Specification Type : Resistive type Number of switches: 192 (16 horizontally Maximum number that can be registered on one screen: 192 Touch panel Cell size: NT31/NT31C 6.3 Input: Pressure-sensitive type 12 vertically) 6.3 mm Operating force: 1 N minimum Life expectancy: One million operations minimum External Interface Specifications Item Specification Serial port A Conforms to EIA RS-232C D-SUB 9-pin connector (female) +5 V (250 mA max.) output at pin No. 6 Serial port B EIA RS-232C or RS-422A/485 (selectable, by memory switch setting) D-SUB 25-pin connector (female) Serial communication Parallel interface Conforms to Centronics standard, 20-pin half pitch connector Expansion interface Dedicated connector Note Check that the current capacity of the equipment to be supplied is within 250 mA before using the +5 V output of pin No. 6. The +5 V output of the unit delivers +5 V " 5% and 250 mA maximum. Programming Environment Item Specification Programming System Programming support software Programming Tool Programming support software: NT-series Support Tool for Windows (Ver. 4.0), by OMRON Special Features Item Specifications Buzzer Three kinds of buzzer sound (continuous, short intermittent, and long intermittent) ON: On reception of a command from the host, display of a screen with a buzzer setting, or display of an error screen such as for a receive error. OFF: On reception of a command from the host, or display of a screen with no buzzer setting. Setting: Set “ON” for “Buzzer Sound” in the memory switch menu, or set “ERROR ON” for the buzzer to sound only when an error occurs. The buzzer sounds three times in response to prohibited input. Touch switch input sound Touch switches Input sound: Sounding for 0.2 seconds Setting: Set “ON” for “Key Press Sound” in the memory switch menu. Maintenance function - Memory switch setting - Self-test functions, such as for the memory and external interface - Setting condition confirmation function - Communication check function - Initialization of internal memory data - Display of display/alarm history data - Registered data test display function 249 Appendix A Specifications Item Specifications Battery backup - Backup of numeral/character string memory table data in the NT31/NT31C - Backup of display/alarm history data - Backup of calendar and clock setting Battery life: 5 years (at 25C) When voltage becomes low: RUN LED lights in orange or red The communication flag to the PLC (BAT LOW) comes ON (1). Resume function Retains the contents of the numeral/character string memory tables (i.e., they are not initialized) when the power is turned ON, when the NT31/NT31C is reset, and when the operation mode is changed. Setting: Set “ON” for “Resume Function” in the memory switch menu. Screen print function Functions: - Prints a hard copy of the screen display - Prints display/alarm histories Setting: Set the printing protocol (“Print Controller”) and printing type (“Print Method”) in the memory switch menu. “ESC/P”, “Color”: Color printing conforming to ESC/P 24-J83C “PC-PR201H”, “Color”: Color printing conforming to PC-PR201PL “ESC/P”, “Tone”: Monochrome printing in 8 grayscale levels, conforming to ESC/P 24-J82 “PC-PR201H”, “Tone”: Monochrome printing in 8 grayscale levels, conforming to PC-PR201PL “PCL 5”, “Tone”: Monochrome printing in 8 grayscale levels, conforming to PCL 5 However, the NT31 supports monochrome printing only. Calendar and clock function - Displays the current time in accordance with the built-in clock - Displayed and set with “Calendar Check” in the “MAINTENANCE MODE” menu Programming Console function Executes functions equivalent to those of al C200H-PRO27-E Programming Console for CPM1, CPM1A, CPM2A, CPM2C, CQM1 (-EV1 only), CQM1H, C200HX/HG/HE(-Z)E, and SRM1 (C02-V2 only) PLCs. Executes functions as a Programming Console for CS1 series PLC. Device Monitor function The Device Monitor function can be used to change the PLC’s operating mode, read/change words in the PLC’s data areas, and display the PLC’s error log. Compatible PLCs include the CPM1, CPM1A, CPM2A, CPM2C, CQM1, CQM1H, C200HX/HG/HE(-Z)E, SRM1, and CS-series PLCs. Mathematical function Up to 256 calculation expressions can be registered along with the screen data. The calculation function reads the required data from numeral memory tables or host words, executes the registered calculations, and writes the results. Arithmetic operators, logic operators, bit operators, and comparative operators can be used. Transmission functions 250 System program transmission Downloads the system program from the system installer Downloads/Upload the system program with a memory unit. Screen data transmission - Function for downloading screen data to and uploading screen data from the Support Tool - Function for transmitting screen data to and from the memory unit. History data uploading Function for uploading display/alarm history data from PT. Appendix A Specifications Communications Specifications For a Host Link , RS-232C Type Item Specification Communications standard EIA RS-232C Communications settings Start-stop synchronization Communications speed: Data length: Stop bit: Parity: Connector 9-pin D-SUB connector (female) (serial port A) 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 Transmission distance Max. 15 m* 9600, 19200 bps 7 bits 2 bits Even Communications protocol C-series SYSMAC WAY (1:N) * When using an NT-AL001, the specifications are as follows. • RS-232C cable: Max. 2 m • RS-422A cable: Total length 500 m max. For a Host Link , RS-422A Type Item Specification Communications standard EIA RS-422A Communications settings Start-stop synchronization Communications speed: Data length: Stop bit: Parity: Connector 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 Transmission distance Max. 500 m Communications protocol C-series SYSWAY (1:N) 9600, 19200 bps 7 bits 2 bits Even For an NT Link , 1:1, RS-232C Type Item Specification Communications standard EIA RS-232C Connector 9-pin D-SUB connector (female) (serial port A) 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 Transmission distance Max. 15 m* * When using an NT-AL001, the specifications are as follows. • RS-232C cable: Max. 2 m • RS-422A cable: Total length 500 m max. 251 Appendix A Specifications For an NT Link , 1:1, RS-422A Type Item Specification Communications standard EIA RS-422A Connector 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 Transmission distance Max. 500 m For an NT Link , 1:N, RS-232C Type Item Specification Communications standard EIA RS-232C Connector 9-pin D-SUB connector (female) (serial port A) 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 to 8 Transmission distance Max. 15 m* * To connect two or more PTs, NT-AL001 units are required. When using an NT-AL001, the specifications are as follows. • RS-232C cable: Max. 2 m • RS-422A/485 cable: Total length 500 m max. For an NT Link , 1:N, RS-422A/485 Type Item Specification Communications standard EIA RS-422A/485 Connector 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 to 8 Transmission distance Max. 500 m For a High-speed NT Link , 1:N, RS-232C Type Item Specification Communications standard EIA RS-232C Connector 9-pin D-SUB connector (female) (serial port A) 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 to 8 Transmission distance Max. 15 m* * To connect two or more PTs, NT-AL001 units are required. When using an NT-AL001, the specifications are as follows. • RS-232C cable: Max. 2 m • RS-422A/485 cable: Total length 500 m max. For a High-speed NT Link , 1:N, RS-422A/485 Type Item Specification Communications standard EIA RS-422A/485 Connector 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 to 8 Transmission distance Max. 500 m 252 Appendix A Specifications For a Memory Link , RS-232C Type Item Specification Communications standard EIA RS-232C Communications settings Start-stop synchronization Communications speed: Data length: Stop bit: Parity: Flow control: Response: 1200, 2400, 4800, 9600, 19200, 38400 bps 7, 8 bits 1, 2 bits None, even, odd None, RS/CS, XON/XOFF Presence/absence Connector 9-pin D-SUB connector (female) (serial port A) 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 Transmission distance Max. 15 m* Communications protocol Memory link * When using NT-AL001, specification is as follows: • RS-232C: Max. 2 m • RS-422A: Max. total length 500 m For a Memory Link , RS-422A Type Item Specification Communications standard EIA RS-422A Communications settings Start-stop synchronization Communications speed: Data length: Stop bit: Parity: Flow control: Response: Connector 25-pin D-SUB connector (female) (serial port B) Number of units connected 1:1 Transmission distance Max. 500 m* Communications protocol Memory link 1200, 2400, 4800, 9600, 19200, 38400 bps 7, 8 bits 1, 2 bits None, even, odd None, XON/XOFF Presence/absence For a Bar Code Reader Item Specification Communications standard EIA RS-232C Communications settings Start-stop synchronization Communications speed: Data length: Stop bit: Parity: Flow control: Connector 9-pin D-SUB connector (female) (serial port A) Number of units connected 1:1 Transmission distance Max. 15 m Communications protocol Non-protocol mode Data format [STX] 4,800, 9600, 19200 bps 7, 8 bits 1, 2 bits None, even, odd RS/CS Data (0 to 40 bytes) [ETX] 253 Appendix B Dimensions Body 183.5 (7.22) POWER RUN 142 (5.59) 130.5 (5.14) 5 (0.20) 195 (7.68) Units: mm (inch) 54 (2.13) With memory unit installed (NT-MF261) 74 (2.91) 255 Appendix B Dimensions Mounting Dimensions Mounting panel Mounting fixture POWER RUN 25 (0.98) 153 (6.02) 15.5 (0.61) 145 (5.71) 5 (0.2) 34 (1.34) (min.) 38 (1.5) (max.) Units: mm (inch) 206 (8.11) 256 Appendix B Dimensions Cable Connection Dimensions (with NT-MF261) 96 (3.78) 10.2 (0.47) 91 (3.58) 24V DC 26.7 (1.05) PRINTER PORT B PORT A 5 (0.20) 50 (1.97) 60 (2.36) Units: mm (inch) 257 Appendix C Using an RS-232C/RS-422A Convertor Unit This section outlines the external dimensions, procedure for mounting and removal, and specifications of an RS-232C/RS-422A convertor unit (NT-AL001-E). Refer to this information when designing the control panel. For details, refer to the instruction manual supplied with the NT-AL001-E. Dimensions 53.5 (2.11) 110 (4.33) om Ron 4 (0.16) 74.5 (2.93) 100.2 (3.94) 105 (4.13) max. NT–AL001-E (30) (1.18) 45 (1.77) 30 (1.18) Units: mm (inch) 30 (W) 114 (H) 100.2 (D) mm: with the RS-422A terminal block cover closed 30 (W) 114 (H) 119.5 (D) mm: with the RS-422A terminal block cover open Methods for Mounting and Removal The RS-232/RS-422 convertor unit (NT-AL001-E) can be mounted on a DIN rail or in an operation panel. The RS-422A terminal block of the convertor unit can be easily removed. Mounting to a DIN Rail Latch the top part of the rear face of the convertor unit (a in the figure) onto the top edge of the DIN rail, and push the unit in the direction indicated by b in the figure. Now fit end plates at the right and left of the convertor unit to secure it and ensure that it cannot shift laterally. (a) (b) 259 Appendix C Using an RS-232C/RS-422A Convertor Unit Removal from a DIN Rail Remove the end plates at right and left of the convertor unit and, as shown in the figure below, insert a flat blade screwdriver into the rail stopper at the bottom face of the convertor unit and prize it free. Mounting to an Operation Panel Drill two mounting screw holes in an operation panel with a thickness of at least 2 mm (0.08 inch) and secure the convertor unit with screws. 30 (1.18) 100 (3.94) 110 (4.33) 21 (0.83) 2-M4 Units: mm (inch) Note In order to ensure a secure and strong mount, mount the convertor unit in an operation panel with a thickness of at least 2 mm (0.08 inch). 260 Appendix C Using an RS-232C/RS-422A Convertor Unit Specifications The general specifications and communications specifications of the convertor unit are shown below. General Specifications Item Specification Dimensions 30 (W) 30 (W) 114 (H) 114 (H) 100.2 (D) mm: with the RS-422A terminal block cover closed 119.5 (D) mm: with the RS-422A terminal block cover open Weight 200 g max. Operating ambient temperature 0 to 55C Operating ambient humidity 10% to 90% (with no condensation) Rated power supply voltage +5 V " 10% (using pin No. 6 of the RS-232C connector) Rated power supply current 150 mA max. Rush current 0.8 A max. Insulation resistance 20 MΩ or higher, measured between all RS-422A terminal signal lines collectively and functional ground terminal with a 500 VDC megger Dielectric strength 1500 VAC for 1 minute between all RS-422A terminal signal lines collectively and functional ground terminal Leakage current: 10 mA max. Operating environment No corrosive gases Storage ambient temperature −20 to +75C Vibration resistance Conforms to JIS C0911 60 minutes in each of X, Y, and Z directions Shock resistance Conforms to JIS C0912 47m/s2, 3 times in each of X, Y, and Z directions Communications Specifications RS-232C Interface Item Specification Communications speed Max. 115.2k bps Transmission distance Max. 2 m Connector 9-pin D-SUB connector (female) RS-422A/485 Interface Item Specification Communications speed Max. 115.2k bps (depends on the RS-232C communications speed) Transmission distance Max. 500 m Connector 8-terminal detachable terminal block, M3.0 261 Appendix C Using an RS-232C/RS-422A Convertor Unit DIP Switch Settings The convertor unit has 6 digits DIP switch for setting the RS-422A/485 communication conditions. Before connecting the cable to the convertor unit, make the DIP switch settings. (Factory settings) ON 123456 omR on NT–AL001-E [SW1-1] Not used (always ON) [SW1-2] Setting for built-in terminal resistance - OFF Terminator not set - ON Terminator set [SW1-3, 4] Selection of 2-wire type/4-wire type SW1-3 SW1-4 OFF 2-wire type (RS-485) ON SW1-3 SW1-4 OFF 4-wire type (RS-422A) ON [SW1-5, 6] Selection of the RS-422A send mode SW1-5 SW1-6 OFF Continual sending ON SW1-5 OFF ON SW1-6 SW1-5 OFF ON SW1-6 Complies with CS control of RS-232C (Data sent at CS high) Complies with CS control of RS-232C (Data sent at CS low) When using the host link or 1:1 NT Link, set the RS-422A send mode to continual sending (set both SW1-5 and 6 OFF). When using the 1:N NT Link (standard or high-speed), set the RS-422A send mode to complies with CS control of RS-232C (i.e., one of SW1-5 and SW1-6 must be ON). Note 1. Do not set both SW1-5 and SW1-6 ON at the same time. This may damage internal circuits. 2. The power supply to the device supplying +5 V must be turned OFF before starting wiring work. 3. Before connecting the RS-232C cable and turning on the power to an RS-232C device such as a PT (i.e., turning on the power to the convertor unit), check that the cable is wired correctly and that the DIP switch settings are correct. If the power is turned on while there is a wiring fault, the internal circuits of the convertor unit or the RS-232C device may be damaged. 4. When the convertor unit is connected to a C200HX/HG/HE (-ZE), CQM1H, CS1G/H model of OMRON PLC as an RS-422A device, set DIP switches SW1-5 and SW1-6 as indicated below. SW1-5 OFF 5 6 262 SW1-6 ON Appendix C Using an RS-232C/RS-422A Convertor Unit Pin Arrangement The convertor unit has a terminal block for an RS-422A/485 interface connection and a connector for an RS-232C interface connection. The pin arrangements for the RS-422A/485 terminal block and the RS-232C connector are as follows. RS-422A/485 Terminal Block 7 5 3 1 8 6 4 2 Terminal block pin No. Signal name Abbreviation Signal direction (convertor unit ⇔ RS-422 device) CSA → 8 Request to send (−) 7 Request to send (+) CSB → 6 Receive data (−) RDA ← 5 Receive data (+) RDB ← 4 Send data (−) SDA → 3 Send data (+) SDB → 2 Signal ground SG (GND) – 1 Functional ground * The CSB and CSA signals are for specialized applications. – RS-232C Connector Connector pin No. 1 2 3 4 5 Signal name Abbreviation Signal direction (convertor unit ⇔ RS-232C device) 6 1 Not used – – 7 2 Send data SD ← 8 3 Receive data RD → 4 Request to send (shorted to CS internally) RS ← 5 Clear to send (shorted to RS internally) CS → 6 +5 V (150 mA) input for convertor unit +5 V → 7 Data set ready (shorted to ER internally) DR → 8 Data terminal ready (shorted to DR internally) ER ← 9 9 Signal ground SG * The hood is connected to the functional ground terminal of the RS-422A terminal block. – 263 Appendix C Using an RS-232C/RS-422A Convertor Unit Block Diagram A diagram showing the internal blocks of the convertor unit is shown below. Refer to this diagram when making cables yourself, or when connecting devices with special interfaces. RS-232C side D-SUB 9P CASE +5 V SG 6 Fuse R POWER LED DC-DC Convertor L 9 Photocoupler RS-232C Dr/Rec RD SD RS CS DR ER 264 3 2 RS-422A/485 side 8P terminal block RS-422A/485 Dr/Rec R R L REG IS_5 V 1 IS_0 V 2 SG 3 4 SDB SDA R 2-wire type/ 4-wire type SW1-6 SW1-3 R 7 8 SW1-4 SW1-5 4 5 FG Terminator R 5 RDB 6 RDA 7 8 CSB CSA SW1-2 RS-422A Dr Appendix D Transporting and Storing the NT31/NT31C • When transporting the NT31/NT31C, use the packaging intended for it. • When storing the NT31/NT31C, observe the following conditions. Storage ambient temperature: Storage ambient humidity: –20 to +60C 35% to 85% 265 Appendix E Making the Cable The procedure for making up the cable is described below. Also refer to this procedure for making a connecting cable for use with RS-422A/485 type connections. Cable Preparation The preparation of the cable differs according to whether or not the shielding wire is to be connected to the FG. Cable with Shielding Wire Connected to FG 1, 2, 3... 1. Cut the cable to the required length. 2. Remove the external vinyl insulation from the cable with a razor blade. Take care not to damage the shielding underneath. 3. Cut back the shielding wire with scissors. 4. Use wire strippers to strip the insulation from each wire. 5. Fold back the shielding wire. 6. Wrap aluminum foil tape around the folded-back shielding wire. (1) (2) 40 (1.57) (RS-232C) 25 (0.98) (RS-422A) (3) 10 (0.39) (4) 5 (0.19) (5) (6) Units: mm (inch) Aluminum foil tape Cable with Shielding Wire Not Connected to FG 1, 2, 3... 1. Cut the cable to the required length. 2. Remove the external vinyl insulation from the cable with a razor blade. Take care not to damage the shielding underneath. 3. Cut back the shielding wire with scissors. 4. Use wire strippers to strip the insulation from each wire. 267 Appendix E Making the Cable 5. Wrap vinyl tape over the cut off end of the shielding wire. (1) (2) 40 (1.57) (RS-232C) 25 (0.98) (RS-422A) (3) (4) 5 (0.19) (5) Units: mm (inch) Vinyl tape Soldering 1, 2, 3... 1. Slide heat-shrink tube over each wire. 2. Pre-solder each wire and connector terminal. 3. Solder each wire to each connector terminal. 1 mm Soldering iron Heat-shrink tube (F, 1.5 mm dia., ȏ = 10 mm) 4. Push the heat shrink tube over the soldered joint and heat the tube to shrink it in place. Heat-shrink tube Hood Assembly Assemble the connector hood as shown below. Aluminum foil tape End connected to FG 268 End not connected to FG Appendix F Making the Cable for Connecting a PLC Refer to the following when making a cable for connecting the Support Tool. Assembly of Connecting Cables Wiring should be carried out in one of the following ways, depending on the type of RS-232C connector. 25-pin Connector Personal computer SD 2 2 SD RD 3 3 RD RS 4 4 RS CS 5 5 CS SG 7 9 SG FG 1 Connector for peripheral devices on PT Shielding wire Connector hood Connector hood Note Please connect the shielding wire to the connector hood at both the personal computer and the peripheral device connector on the PT. Use the following recommended products when making the connecting cable. Name Model Connector Connector hood Cable Remarks XM2D-2501 25-pin, made by OMRON, for personal computer side XM2A-0901 9-pin, made by OMRON, for PT side XM2S-2511 25-pin, made by OMRON, for personal computer side XM2S-0911 9-pin, made by OMRON, for PT side AWG28 5P IFVV-SB Multi-core shielded cable, made by Fujikura Ltd. CA-MA-VV-SB 5P 28AWG Multi-core shielded cable, made by Hitachi Cable, Ltd. 9-pin Connector Personal computer RD 2 2 SD SD 3 3 RD RS 7 4 RS CS 8 5 CS SG 5 9 SG Connector for peripheral devices on PT Shielding wire Connector hood Connector hood Note Please connect the shielding wire to the connector hood at both the personal computer and the peripheral device connector on the PT. Use the following recommended products when making the connecting cable. Name Connector Connector hood* Cable Model Remarks XM2D-0901 9-pin, made by OMRON, for personal computer XM2A-0901 9-pin, made by OMRON, for PT XM2S-0911 9-pin, mm pitch screw, made by OMRON XM2S-0913 9-pin, inch pitch screw, made by OMRON AWG28 5P IFVV-SB Multi-core shielded cable, made by Fujikura Ltd. CA-MA-VV-SB 5P 28AWG Multi-core shielded cable, made by Hitachi Cable, Ltd. * One XM2S-0911 (for PT) and either one XM2S-0911 or -0913 (for your personal computer) are needed. 269 Appendix G Making the Cable for Connection to a Bar Code Reader Refer to the following when making the cable for connection to a bar code reader. Wiring Method NT31/NT31C side Bar code reader side Abbr. Abbr. RS-232C interface Pin No. 1 SD SD 2 RD RD 3 RS RS 4 CS CS 5 +5 V SG 6 ER 7 SG 8 +5 V 9 When using the +5 V output of the NT31/NT31C, limit the cable length to within 2 m. If a cable longer than 2 m is used, connect an external power supply to the bar code reader. Connector and Related Parts Use the parts which are specified by bar code reader and following recommended products when making the connecting cable. Name Model Remarks Connector XM2A-0901 9-pin type, made by OMRON, PT side Connector hood XM2S-0911 9-pin, made by OMRON Cable AWG28 Multi-core shielded cable, made by Fujikura Ltd. 5P IFVV-SB CA-MA-VV-SB 5P 28AWG Multi-core shielded cable, made by Hitachi Cable, Ltd. 271 Appendix H Making the Cable for Connection to a Printer The following product is recommended as the cable for connecting a printer. NT-CNT121 (made by OMRON, cable length 1.5 m, 20-pin – 36-pin) Refer to the following when making a cable for connection to a printer. • Connector pin arrangement and wiring Connector for a printer on PT side 11 2 0 1 1 0 Printer side Abbr. Pin No. Connector hood Shielding wire Pin No. Connector hood 1 8 3 6 20 0V 1 D7 11 9 N.C. 2 N.C. D6 12 8 D5 3 7 0V 13 21 D4 4 6 N.C 14 N.C. D3 5 5 0V 15 22 0V 6 23 D2 16 4 N.C. 7 N.C. D1 17 3 D0 8 2 0V 18 24 STROB 9 1 N.C. 19 N.C. BUSY 10 11 0V 20 19 1 1 9 273 Appendix I Relationship between System Program and Hardware Here, relationship between system program and hardware is described. NT31/NT31C have following models. NT31-ST121-E Conventional product p NT31C-ST141-E NT31-ST121-EV1 NT31C-ST141-EV1 NT31-ST121-EV2 Version upgrade pg model of the products p above (12/98) Version upgrade pg model of the products p above NT31C-ST141-EV2 NT31-ST122-EV2 NT31C-ST142-EV2 System programs indicated below are installed for the models shown above in the default state. Also, system programs are supplied with the Support Tool as follows. • System programs for NT31-ST121-E/NT31C-ST141-E: System Program Ver. 1.0 (System programs supplied with NT-ZJ3AT1-EV2/ZJCAT1-EV2) • System programs for NT31-ST121-EV1/NT31C-ST141-EV1: System Program Ver. 2.0 or 2.1 (System programs supplied with NT-ZJ3AT1-EV3/ZJCAT1-EV3) • System programs for NT31-ST121/122-EV2 and NT31C-ST141/142-EV2: System Program Ver. 3.0 (System programs supplied with NT-ZJCAT1-EV4) (A system program for the earlier NT30/620 PTs is also included with the NT-ZJCAT1-EV4.) These system programs have mutual compatibility, therefore, they can be installed and used for NT31-ST121-E/ NT31C-ST141-E/NT31-ST121-EV1/NT31C-ST141-EV1/NT31-ST121-EV2/NT31-ST122-EV2/ NT31C-ST141-EV2/NT31C-ST142-EV2 each. However, there will be a limitation on function depending on the combination. Refer to the following table. Limitations of System Program/PT Combinations The following table shows only the relationship between the hardware and system program. For details of the relationship with the screen data created using the Support Tool, refer to NT-series Support Tool for Windows (Ver. 4.1) Operation Manual (V061-E1-). 275 Appendix I Relationship between System Program and Hardware Combining a -V1 Version and Version without a -V Suffix Hardware System program Ver. 1.0 NT31-ST121-E NT31-ST121-EV1 NT31C-ST141-E NT31C-ST141-EV1 The following functions cannot be used The following functions cannot be used Analogue meter Analogue meter High-definition font display High-definition font display Installation of system programs using memory unit Connection to Mitsubishi PLCs Connection to Mitsubishi PLCs Memory link Memory link Window control from the host Window control from the host Multiple display of window screens Multiple display of window screens Moving a window Moving a window Refer to the following table for details on new functions supported by the -V2 versions. Refer to the following table for details on new functions supported by the -V2 versions. System program Ver. 2.0 or Ver. 2.1 * Installation of system programs using memory unit is possible The following functions cannot be used Installation of system programs using memory unit The new functions supported by the -V2 versions cannot be used. Refer to the following table for details. High-definition font display Refer to the following table for details on new functions supported by the -V2 versions. * The system program’s version can be checked from the System Menu. Combining a -V1 Version and -V2 Version Hardware System program Ver. 2.0 or Ver. 2.1 NT31-ST121-EV1 NT31-ST121/122-EV2 NT31C-ST141-EV1 NT31C-ST141/142-EV2 The following functions (new functions supported by the -V2) cannot be used: Additional data areas accessible in CS-series PLCs The CS-series high-speed 1:N NT Link Interlock function that controls touch switches, numeral inputs, and character string inputs Mathematical function Device Monitor function NT30/620 compatible mode Expanded capabilities for label (guide character) displays, including multiple lines of text, ON/OFF switching displays, numeral memory table displays, and character string memory table displays System program Ver. 3.0 All of the functions described in the Setup Manual and Reference Manual can be used. * The system program’s version can be checked from the System Menu. 276 Appendix I Relationship between System Program and Hardware Combining a -V2 Version and Version without a -V Suffix Hardware System program Ver. 1.0 NT31-ST121-E NT31-ST121/122-EV2 NT31C-ST141-E NT31C-ST141/142-EV2 The following functions cannot be used The following functions cannot be used Analogue meter Analogue meter High-definition font display High-definition font display Installation of system programs using memory unit Connection to Mitsubishi PLCs Connection to Mitsubishi PLCs Memory link Memory link Window control from the host Window control from the host Multiple display of window screens Multiple display of window screens Moving a window Moving a window Additional data areas accessible in CS-series PLCs Additional data areas accessible in CS-series PLCs The CS-series high-speed 1:N NT Link The CS-series high-speed 1:N NT Link Interlock function that controls touch switches, numeral inputs, and character string inputs Interlock function that controls touch switches, numeral inputs, and character string inputs Device Monitor function Device Monitor function NT30/620 compatible mode NT30/620 compatible mode Expanded capabilities for label (guide character) displays, including multiple lines of text, ON/OFF switching displays, numeral memory table displays, and character string memory table displays Expanded capabilities for label (guide character) displays, including multiple lines of text, ON/OFF switching displays, numeral memory table displays, and character string memory table displays System program Ver. 3.0 Mathematical function Mathematical function The following functions cannot be used Installation of system programs using memory unit * Installation of system programs using memory unit is possible All of the functions described in the Setup Manual and Reference Manual can be used. High-definition font display * The system program’s version can be checked from the System Menu. 277 Appendix J Model List PTs Model Specification NT31-ST121-EV2 STN monochrome display, beige NT31-ST121B-EV2 STN monochrome display, black NT31-ST122-EV2 STN monochrome display, beige NT31-ST122B-EV2 STN monochrome display, black NT31C-ST141-EV2 STN color display, beige NT31C-ST141B-EV2 STN color display, black NT31C-ST142-EV2 STN color display, beige NT31C-ST142B-EV2 STN color display, black Host Link Units Model Specification 3G2A6-LK201-EV1 CPU-mounted type with RS-232C connector 3G2A6-LK202-EV1 CPU-mounted type with RS-422A connector C200H-LK201-V1 Rack-mounting unit with RS-232C connector for C200H C200H-LK202-V1 Rack-mounting unit with RS-422A connector for C200H 3G2A5-LK201-EV1 Features a selectable RS-232C/RS-422A connector C500-LK203 Rack-mounting unit for C500 CV500-LK201 Features an RS-232C connector and a selectable RS-232C/RS-422A connector Rack-mounting unit for CVM1/CV Applicable PLC C-series C1000H C2000H C-series C200HS C200HX/HG/HE(-Z)E C-series C1000H C2000H CVM1/CV-series CV500 CV1000 CV2000 CVM1 CompoBus/S Master Control Unit Model SRM1-C02-V2 Specification Features an RS-232C port Model Name SRM1 Communications Unit Model CS1W-SCU21 Specification RS-232C (2 ports) Rack-mounting unit Applicable PLC CS-series CS1G/H 279 Appendix J Model List CPU Units for Connection via a Host Link Model Specification PLC Type CPM1-10CDR- CPM1-20CDR- CPM1A-10CD- CPM1A-20CD- CPM1A-30CD- CPM1A-40CD- RS-232C adapter/RS-422A adapter connected to the peripheral port C-series CPM1 CPM2A-30CD- CPM2A-40CD- CPM2A-60CD- Features a 9-pin connector for RS-232C connections C-series CPM2A CPM2C-10- CPM2C-20- The PLC’s communications connector can be split into C-series an RS-232C port and peripheral port with a CPM2C CPM2C-CN111 Connecting Cable. (The CS1W-CN114/118 Connecting Cables convert the connector to a single RS-232C or peripheral port.) CQM1-CPU21-E CQM1-CPU41-EV1 CQM1-CPU42-EV1 CQM1-CPU43-EV1 CQM1-CPU44-EV1 CQM1-CPU45-EV1 Features a 9-pin connector for RS-232C connections C-series CQM1 CQM1H-CPU11 CQM1H-CPU21 CQM1H-CPU51 CQM1H-CPU61 Features a 9-pin connector for RS-232C connections (The CQM1H-CPU11-E has only a peripheral port.) C-series CQM1H C200HS-CPU21-E C200HS-CPU23-E C200HS-CPU31-E C200HS-CPU33-E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HS C200HE-CPU32-(Z)E(*) C200HE-CPU42-(Z)E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HE(-Z)E C200HG-CPU33-(Z)E(*) C200HG-CPU43-(Z)E C200HG-CPU53-(Z)E(*) C200HG-CPU63-(Z)E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HG(-Z)E C200HX-CPU34-(Z)E(*) C200HX-CPU44-(Z)E C200HX-CPU54-(Z)E(*) C200HX-CPU64-(Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE Features a connector for RS-232C connections (selectable/9-pin) C-series C200HX(-Z)E CS1G-CPU42-E(V1) CS1G-CPU43-E(V1) CS1G-CPU44-E(V1) CS1G-CPU45-E(V1) Features a connector for RS-232C connections (9-pin) CS-series CS1G CS1H-CPU63-E(V1) CS1H-CPU64-E(V1) CS1H-CPU65-E(V1) CS1H-CPU66-E(V1) CS1H-CPU67-E(V1) Features a connector for RS-232C connections (9-pin) CS-series CS1H CV500-CPU01-EV1 CV1000-CPU01-EV1 CV2000-CPU01-EV1 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 Features a connector for RS-232C connections (selectable/9-pin) CVM1/CV-series CV500 CV1000 CV2000 CVM1 * Either of the communication boards C200HW-COM02/COM04/COM05/COM06-EV1 is required. 280 Appendix J Model List CPU Units for Connection via a 1:1 NT Link Model Specification PLC Type CPM1-10CDR- CPM1-20CDR- CPM1A-10CD- CPM1A-20CD- CPM1A-30CD- CPM1A-40CD- RS-232C adapter connected to the peripheral port (RS-422A adapter cannot be used) C-series CPM1 CPM2A-30CD- CPM2A-40CD- CPM2A-60CD- Features a 9-pin connector for RS-232C connections C-series CPM2A CPM2C-10- CPM2C-20- Connect to the RS-232C port of a CPM2C-CN111 Connecting Cable. C-series CPM2C CQM1-CPU41-EV1 CQM1-CPU42-EV1 CQM1-CPU43-EV1 CQM1-CPU44-EV1 CQM1-CPU45-EV1 Features a 9-pin connector for RS-232C connections C-series CQM1 CQM1H-CPU21 CQM1H-CPU51 CQM1H-CPU61 Features a 9-pin connector for RS-232C connections C-series CQM1H C200HS-CPU21-E C200HS-CPU23-E C200HS-CPU31-E C200HS-CPU33-E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HS C200HE-CPU32-(Z)E(*) C200HE-CPU42-(Z)E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HE(-Z)E C200HG-CPU33-(Z)E(*) C200HG-CPU43-(Z)E C200HG-CPU53-(Z)E(*) C200HG-CPU63-(Z)E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HG(-Z)E C200HX-CPU34-(Z)E(*) C200HX-CPU44-(Z)E C200HX-CPU54-(Z)E(*) C200HX-CPU64-(Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE Features a connector for RS-232C connections (selectable/9-pin) C-series C200HX(-Z)E CV500-CPU01-EV1 CV1000-CPU01-EV1 CV2000-CPU01-EV1 CVM1-CPU01-EV2 CVM1-CPU11-EV2 CVM1-CPU21-EV2 Features a connector for RS-232C connections (selectable/9-pin) CVM1/CV-series CV500 CV1000 CV2000 CVM1 * Either of the communication boards C200HW-COM02/COM04/COM05/COM06-EV1 is required. CPU Units for Connection via a 1:N NT Link Model Specification PLC Type CQM1H-CPU51(*1) CQM1H-CPU61(*1) Features a 9-pin connector for RS-232C connections C-series CQM1H C200HE-CPU32-(Z)E(*) C200HE-CPU42-(Z)E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HE(-Z)E C200HG-CPU34-(Z)E(*) C200HG-CPU43-(Z)E C200HG-CPU53-(Z)E(*) C200HG-CPU63-(Z)E Features a connector for RS-232C connections (selectable/9-pin) C-series C200HG(-Z)E 281 Appendix J Model List Model Specification C200HX-CPU34-(Z)E(*) C200HX-CPU44-(Z)E C200HX-CPU54-(Z)E(*) C200HX-CPU64-(Z)E C200HX-CPU65-ZE C200HX-CPU85-ZE Features a connector for RS-232C connections (selectable/9-pin) C-series C200HX(-Z)E PLC Type CS1G-CPU42-E(V1) CS1G-CPU43-E(V1) CS1G-CPU44-E(V1) CS1G-CPU45-E(V1) Features a connector for RS-232C connections (9-pin) CS-series CS1G CS1H-CPU63-E(V1) CS1H-CPU64-E(V1) CS1H-CPU65-E(V1) CS1H-CPU66-E(V1) CS1H-CPU67-E(V1) Features a connector for RS-232C connections (9-pin) CS-series CS1H *1: A CQM1H-SCB41 Serial Communications Board is required. *2: Either of the communication boards C200HW-COM02/COM04/COM05/COM06-EV1 is required. CPU Units for Connection via a High-speed NT Link (1:N)) Model Specification PLC Type CS1G-CPU42-E(V1) CS1G-CPU43-E(V1) CS1G-CPU44-E(V1) CS1G-CPU45-E(V1) Features a 9-pin connector for RS-232C connections CS-series CS1G CS1H-CPU63-E(V1) CS1H-CPU64-E(V1) CS1H-CPU65-E(V1) CS1H-CPU66-E(V1) CS1H-CPU67-E(V1) Features a 9-pin connector for RS-232C connections CS-series CS1H Reference: Serial Communications Boards (CS1W-SCB41) and Serial Communications Units (CS1W-SCU21) with lot number 991220 (12/20/99) and later support the high-speed 1:N NT Link. Boards and Units with earlier lot numbers cannot be used to establish a high-speed 1:N NT Link. RS-232C/RS-422A Convertor Unit Model NT-AL001 Specification RS-232C: 9-pin connector RS-422A: 8-pin terminal block RS-232C Adaptor, RS-422A Adaptor Model Specification CPM1-CIF01 Links the RS-232C port of an NT31/NT31C and the peripheral port of a CPM1, CPM2A, CPM2C, SRM1 (compatible with host link, and NT Link (1:1)) CPM1-CIF11 Links the RS-422A port of an NT31/NT31C and the peripheral port of a CPM1, CPM2A, CPM2C, SRM1 (compatible with host link) 282 Appendix J Model List Related Parts and Equipment for PT Name Model Remark Support Tool* Options p NT-ZJCAT1-EV4 Compatible with PC/AT personal computers For Windows 95/98/NT (English version) CD-ROM NT31C-CFL01 Replaceable backlight (common to NT31 and NT31C) NT30-KBA04 Reflection suppressing protective sheet for NT31/NT31C NT30-KBA01 Chemical-resistant cover for NT31/NT31C NT-MF261 Memory unit for NT31/NT31C 3G2A9-BAT08 Spare battery * The Support Tool indicated above includes the system installer and the standard system programs (Ver. 3.0) for the NT31, NT31C, NT631, and NT631C. System programs for the earlier NT30/620 PTs are also included. Cables with Connectors for PT ↔ PLC/NT-AL001-E Model Cable Length XW2Z-200S 2m XW2Z-500S 5m XW2Z-200T 2m XW2Z-500T 5m XW2Z-200P 2m XW2Z-500P 5m XW2Z-200S 2m XW2Z-500S 5m XW2Z-070T-1 0.7 m XW2Z-200T-1 2m Applicable units Communication Method Specification Host link units with a 25-pin p connector Serial p port A host link (RS-232C only) 9 pin ↔ 25-pin 9-pin 25 pin Host link units with a 9-pin p connector t Serial port p A host link,, NT Link (1:1) (RS-232C only) 9 pin ↔ 9-pin 9-pin 9 pin Host link units with a 25-pin p connector Serial p port B host link (RS-232C only) 25 pin ↔ 25-pin 25-pin 25 pin Host link units with a 9-pin p connector Serial port p B host link,, NT Link (1:1) (RS-232C only) 25 pin ↔ 9 25-pin 9-pin pin CPU Units with a 9-pin connector (The PLC((*1)) supplies +5 V for NT-AL001-E connections.) Host Link, 1:1 NT Link, or 1:N NT Link using NT-AL001-E NT AL001 E 9 pin ↔ 9-pin 9 pin 9-pin *1: The following PLCs can supply +5 V: C200HX/HG/HE(-Z)E, CQM1H, CPM2A, CPM2C, and CS1G/H. Cables with Connectors Model Cable Length CV500-CN228 2m XW2Z-S001* 15 cm Specification 25-pin (male) ↔ 9-pin (male) 25-pin (female) ↔ 14-pin (male) XW2Z-S002 2m 9-pin (female) ↔ 9-pin (male) * The XW2Z-S001 is a converting cable. A CV500-CN228 must be purchased separately for connection to a computer. Connection Cable Model AWG28 Specification 5P IFVV-SB CO-MA-VV-SB 5P 28AWG Multicore cable, manufactured by Fujikura, Ltd. Multicore cable, manufactured by Hitachi Cable, Ltd. Applicable Connectors Name Connector Model Specification XM2A-2501 25-pin type (male), made by OMRON XM2D-2501 25-pin type (female), made by OMRON (for personal computers) XM2A-0901 9-pin type (male), made by OMRON XM2D-0901 9-pin type (female), made by OMRON (for personal computers) DB-25P 25-pin type (male), made by JAE 283 Appendix J Model List Connector hood XM2S-2511 25-pin type, mm pitch screw, made by OMRON XM2S-2513 25-pin type, inch pitch screw, made by OMRON XM2S-0911 9-pin type, mm pitch screw, made by OMRON XM2S-0911-E 9-pin type, mm pitch screw, made by OMRON XM2S-0913 9-pin type, inch pitch screw, made by OMRON DB-C2-J9 25-pin type, made by JAE Printer Cable Model NT-CNT121 Specification Printer cable for half pitch (1.5 m), made by OMRON Cable for Peripheral Port of CS-series PLC Model CS1W-CN118 Specification Made by OMRON (CS-series peripheral port ↔ D-Sub, 9-pin, female) Connecting Cable for the CPM2C Communications Connector Model CPM2C-CN111 284 Specification Made by OMRON (CPM2C communications port ↔ D-Sub, 9-pin, female, C-series peripheral port) Appendix K Option List Replaceable Backlight ... NT31C-CFL01 (Used for NT31-ST121-EV2, NT31C-ST141-EV2 Only) This is a backlight (CFL unit) for replacement purposes. Protective Sheet ... NT30-KBA04 (Used for Both NT31/NT31C) Stuck to the display to prevent irregular reflection or contamination. The entire sheet is colorless and transparent. The five sheets make a set. 285 Appendix K Option List Chemical-resistant Cover ... NT30-KBA01 Covers the front panel and protects it from various chemical agents. The entire sheet is milky white and made of silicone rubber. The sheet offers protection against the following chemical agents. Protects against Does not protect against Boric acid Hexane Sulfuric acid Lubricating oil Nitrogen Benzene Ammonia gas Butane Carbonic acid gas Carbonic acid Phenol Chlorinated solvents Glycerin Napthalene Ammonia water Soy bean oil Calcium chloride Toluene Developing fluid (hypo) Acetaldehyde Lard For information on chemical agents not listed in the table above, please inquire whether or not protection is offered (if the chemical agent is one against which silicone rubber is recognized as offering protection, please use this product even if the agent is not listed in the “Protects against” column of the table above). Replacement Battery ... 3G2A9-BAT08 This is a lithium battery used for memory backup. 286 Option List Appendix K Memory Unit ... NT-MF261 This is a dedicated unit for reading/writing the screen data and the system programs in an NT31/NT31C. Data is transmitted by DIP switch setting at the memory unit. 287 Index Numbers Chemical–resistant cover, 286 Cleaning method, 243 1:N connection among RS–422A ports, 120 Clearing screen data, 138, 152 1:N connection among RS–485 ports, 123 Clearing/installing the system program, 149 1:N connection between RS–422A/485 at the NT31/NT31C and RS–232C at the host, 90 Comm. A Method, 156 Comm. B Method, 156 Comm. B Select, 156 A Allowable power supply voltage range, 247 Applicable connectors, 283 Automatic transmission (memory unit), 40, 47 B Communication board, 53, 66, 70, 74, 100 Communication boards, 109 Communication by Using Memory Link, 19 Communication condition, 155 Communication condition settings for bar code readers, 186 Communication condition settings for the host link method, 156 Communication errors and their remedies, 237 Backlight, 239 Communication method for communications with the host, 155 Backlight brightness adjustment, 191 Communication method settings, 156 Backlight unit, 28 Communication methods, 24 Battery cover, 28 Communication port, 24 Before operating, 21 Communication type, 24 Brightness adjustment, 248 Communication Unit, 279 Communications specifications, 251 C Comparison between NT31 and NT31C, 5 Connecting a bar code reader, 35 Cable connection dimensions, 257 Connecting a printer, 34 Cable for peripheral port of CS1–series PLC, 284 Connecting directly between RS–232C ports, 77 Cables with connectors, 283 Connecting to other model PLCs, 19 Calling the System Installer mode, 136 Connecting to the Support Tool, 33 Calling the System Menu, 136 Connection cable, 283 Cell size (Touch panel), 249 Connection method, 24 Changing the system settings, 151 Contrast adjustment, 189 Checking communication at serial ports, 215 CPU, 100 Checking communication with a printer, 218 CPUs, 66, 70, 74, 109, 111 Checking communication with the support tool, 214 CPUs (for connection via a host link), 280 Checking interfaces, 213 CPUs connectable with host link units or expansion communication board, 100 Checking screen data, 200 Checking the backlight, 207 Checking the battery voltage, 212 D Checking the buzzer, 203 Device check, 203 Checking the LCD (screen display), 206 Device Monitor function, 225 Checking the PT setting status, 195 Dimensions, 247 Checking the RUN LED, 204 Direct connection function, 16 Checking touch switches, 210 Disabling/enabling System Menu display, 151 289 Index Disabling/enabling writing to the screen data memory, 151 Installation environment, 30 Display, 27 Installation in the operation panel, 30 Display color, 248 Display device, 248 Display specifications, 248 Displaying and printing the display history record, 196 L–M Life expectancy (backlight), 248 Life expectancy (display panel), 248 Displaying/setting the calendar and clock, 193 Life expectancy (touch panel), 249 Downloading the system program, 150 Maintenance Mode, 134 Making the cable, 267 E Making the cable for connecting a PLC, 269 Making the cable for connection to a bar code reader, 271 Effective display area, 248 Making the cable for connection to a printer, 273 Enclosure ratings, 247 Manual transmission (memory unit), 42, 48 Error messages, 233 Manuals, 21 Errors in the system installer mode and their remedies, 237 Memory initialization, 138 Errors occurring at start of operation, 233 Errors occurring during operation, 235 Errors occurring on screen data initialization and transmission, 236 Errors when using a memory unit, 43, 49 Expansion interface connector, 28 Expansion Mode, 134 External interface specifications, 249 F–H Memory link method, 76, 114 Memory switch, 155 Memory switch setting screen, 166 Memory unit, 287 Menu tree, 135 RUN mode, 133 System Installer Mode, 133 Mounting dimensions, 256 N Noise resistance, 247 Functional ground terminal, 32 NT link, 17 General specifications, 247 NT link (1:1) method, 65 GR terminal, 28 NT link (1:N) method, 70, 111 high-speed, 73, 113 Grounding, 32, 247 Host link, 17 Host link method, 52, 99 NT–AL001, 259 Number of dots, 248 Number of switches (touch panel), 249 Host link unit, 53, 279 I O Operating ambient humidity, 247 I/O settings, 189 Operating ambient temperature, 247 In the panel, 4 Operating environment, 247 Initializing alarm history record data, 142 Initializing display history record data, 140 Initializing the memory switches, 147 Initializing the memory tables, 145 Initializing the recipe tables, 143 Inspection method, 244 290 Operating force, 249 Operation at startup, 132 Operation modes, 133 P Peripheral devices that can be connected, 15 Index Power consumption, 247 Setting “Screen Saver Movement”, 173 Power input terminals, 28 Setting the automatic reset function, 181 POWER LED, 27 Setting the bar code reader input function, 186 Power supply connection, 31 Setting the ”Buzzer Sound”, 169 precautions, xi Setting the communication type for serial port B, 165 Precautions to be observed when transmitting screen data, 154 Principal functions of NT31/NT31C, 8 Setting the conditions for communications with the memory link method, 156 Printer cable, 284 Setting the display language in the System Installer mode, 149 Printer connector, 28 Setting the history display method, 177 Programming console function, 219 Setting the host link method, 158 Programming environment, 249 Setting the “Key Press Sound”, 168 Protective sheet, 285 Setting the Memory Link Method, 163 PT, 279 Setting the NT link (1:1) method, 160 PT Memory, 19 Setting the NT link (1:N) method, 161 Setting the “Print Method”, 172 R Rated power supply voltage, 247 Recipe function, 6 Recommended printers, 34 Setting the “Printer Controller”, 170 Setting the resume function, 179 Setting the retry count, 184 Setting the screen saver start–up time, 175 Relationship between system program and hardware, 275 Setting the ”Start–up Wait Time”, 167 Relationships among modes, 133 Setting the terminal resistance, 97, 126 Replaceable backlight, 285 Setting the time–out interval, 183 Replacement battery, 286 Shock resistance (operating), 247 Replacing the backlight, 240 Special features, 249 Replacing the battery, 242 Starting operation, 166 Reset switch, 28 Starting the NT31/NT31C, 132 RS–232C adaptor, 282 Storage ambient temperature, 247 RS–232C/RS–422A convertor unit, 86, 282 Supplemental functions to V2, 5 RS–422A adaptor, 282 Support Tool, 283 RUN, 133 Switching from the System Menu to the RUN mode, 137 RUN LED, 27 Switching to the RUN mode, 166 System configuration, 15 S System Menu, 133 Screen data composition and transmission units, 153 Screen data memory check, 207 T–U Selecting menu items, 137 Serial communication board, 52, 70, 74, 99, 114 Terminal resistance setting terminal , 97 Serial communication unit, 52 Transmit Mode, 134 Serial port A, 16, 24 Transmitting the screen data, 153 Serial port A connector, 28 Transporting and storing the NT31/NT31C, 265 Serial port B, 16, 24 Usable systems (programming console function), 219 Serial port B connector, 28 Using a Memory Unit(NT31/NT31C with V1), 37 Set, 159 Using an RS–232C/RS–422A convertor unit, 259 291 Index V W Warning label, 28 Vibration resistance (operating), 247 View angle, 248 292 Waterproofed, 4 Weight, 247 Revision History A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. V062-E1-03 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. Revision code Date 1 July 2000 02 January 2003 Revised content Original production Page 73: Description on connections added under Connecting to CS1-series CPU Units. Page 185: Setting range of 0 to 10 seconds corrected to 1 to 10 seconds under Setting the Time-out Interval and “00” deleted from the sequence in the bottom graphic. Page 224: Description on error display under Reference changed. Page 235: One row about the numeral display or numeral input field added to the table. Page 269: Indications inside connector graphics corrected and a note about the use of shielding wire added to each graphic. 03 June 2004 CS1 was changed to CS, and the abbreviation for Programmable Controllers was unified to PLC. The following changes were also made. Page 5: Added new models to table. Page 7: Added information on backlight color. Also added details on battery replacement for new models. Page 17: Added information on backlight replacement for new models. Page 23: Corrected and added information on reference manuals to table. Page 29: Added new models to table. Page 33: Changed information in table on power supply specifications. Page 39: Added new models to introduction. Page 59: Corrected DIP switch setting for SW3–6 from “ON” to “OFF” in graphic. Page 79: Added CS-series PLC to graphic. Page 82: Added information on cables for CS-series CPU Units. Page 90: Removed information on cables with connectors. Page 91: Added information on cables for CS-series CPU Units. Page 150: Added information on System Installer mode versions. Page 193: Added information on backlight brightness. Page 223: Added and corrected information on CS1G/CS1H PLCs. Page 224: Corrected “can” to “cannot” in note. Page 241: Added information on backlight replacement for new models. Page 242: Added information on backlight replacement for new models, and changed model numbers. Page 243: Changed “NT31/NT31C” to “PT” in text and changed model numbers in graphic. Page 246: Changed and added information in table on power supply voltage and backlight brightness. Pages 247 and 248: Changed specifications tables to add information on new models. Pages 275, 276, and 277: Added new models Page 281: Removed information on SJ cables with connectors. Page 283: Changed PT models that support replaceable backlights. 293 OMRON Corporation FA Systems Division H.Q. 66 Matsumoto Mishima-city, Shizuoka 411-8511 Japan Tel: (81)55-977-9181/Fax: (81)55-977-9045 Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 1 East Commerce Drive, Schaumburg, IL 60173 U.S.A. Tel: (1)847-843-7900/Fax: (1)847-843-8568 OMRON ASIA PACIFIC PTE. LTD. 83 Clemenceau Avenue, #11-01, UE Square, Singapore 239920 Tel: (65)6835-3011/Fax: (65)6835-2711 Authorized Distributor: Cat. No. V062-E1-03 Note: Specifications subject to change without notice. This manual is printed on 100% recycled paper. Printed in Japan Cat. No. V062-E1-03 NT31, NT31C Programmable Terminals SETUP MANUAL ">

Download
Just a friendly reminder. You can view the document right here. But most importantly, our AI has already read it. It can explain complex things in simple terms, answer your questions in any language, and help you quickly navigate even the longest or most compilcated documents.
Advertisement