Omron NS - REV 04, NS5-TQ11*-V2, NS8-TV02*-V2 Operation Manual
Anuncio
Anuncio
Cat. No. V098-E1-04
Programmable Terminals
OPERATION MANUAL
Introduction
This manual describes the configuration and settings required for communicating with the host devices used by NS-series Programmable Terminals for Host Link communications.
First familiarize yourself with the contents of the manuals related to NS-series
Programmable Terminals (the NS-series Setup Manual, NS-series Programming Manual , and the CX-Designer online help), and then use this manual for Host Link communications.
1
1-1 Overview
This section provides an overview of connecting an NS-V1/V2 PT to an OMRON
Programmable Controller that supports Host Link communications.
The NS-V1/V2 PT is connected 1:1 to the CPU Unit or a Host Link Unit of an OMRON PLC.
Host Link communications are used to read and display or write the words and settings in the host PLC.
NS-V1/V2 PT serial ports A and B can both be connected to a host by means of the Host Link protocol.
Reference
When an NS-V1/V2 PT and a PLC are connected by
Host Link, it is not possible to change to RUN Mode.
If the PLC is set for RUN Mode, it is automatically switched to Monitor Mode. For example, if a compatible Programming Console is connected to the PLC and the PLC operating mode is switched to
RUN mode, the password display for the Monitor
Mode will be displayed at the Programming Console.
2
1-2 Connection Configuration
This section describes the system configuration required for connecting to the host by Host
Link communications.
1-2-1 NS-V1/V2 Configuration Required for Connection
NS-V1/V2 Models
One of the following NS-V1/V2 PTs is required to connect with the host by Host Link communications.
NS12-TS0 @ (B)-V1/-V2
Model
NS10-TV0 @ (B)-V1/-V2
NS8-TV0 @ (B)-V1/-V2
NS8-TV1 @ (B)-V1
NS5-SQ @@ (B)-V1/-V2
NS5-TQ @@ (B)-V2
NS5-MQ @@ (B)-V2
Reference
NS-series PTs without the -V1 or -V2 suffix do not support Host Link communications. One of the above
NS-V1/V2 models must be used.
NS-V1/V2 System Program
To connect to the host by means of Host Link communications, system program version 6 or later must be installed in the NS-V1/V2 PT.
System program
Ver. 6 or later
3
Communications Ports
Communications port
Serial port A
Serial port B
Applicable communications method
Host Link
1:1 NT link
1:N NT link
Memory link
(Bar-code reader input)
(Temperature controller connection)
(CX-Designer connection)
Host Link
1:1 NT link
1:N NT link
Memory link
(Bar-code reader input)
(Temperature controller connection)
(CX-Designer connection)
The following table shows the communications methods that can be used in combination when serial ports A and B are used at the same time.
Serial port B
Host Link
1:1 NT link
YES YES YES YES YES YES YES
YES YES YES YES YES YES YES
1:N NT Link
Memory link
Bar-code reader
Temperature controller
YES YES YES YES YES YES YES
YES YES YES No YES YES YES
YES YES YES YES No YES YES
YES YES YES YES YES YES YES
CX-Designer connection YES YES YES YES YES YES No
4
Communications Setup
The following table shows the communications settings required at the NS-V1/V2 PT and the host to connect to the host by means of Host Link communications.
Setup location
Settings (See note 2.)
NS-V1/V2 PT Baud rate: 9,600 or 19,200 bps (See note 1.)
Host Start bits: 1 bit
Data: 7 bits
Stop bits: 2 bits
Parity: Even
Host Link unit number: 0
Baud rate: 9,600 or 19,200 bps (See note 1.)
Note 1: The baud rate settings must be the same for both the NS-V1/V2 PT and the host.
2: Use the 1:N protocol setting.
1-2-2 Applicable PLCs
The OMRON PLCs listed below can be connected as hosts using Host Link communications.
The connection can be made either directly to the built-in serial port on the CPU Unit or to a
Host Link Unit mounted to the PLC.
C Series
C200HS, C200HX/HG/HE(-Z), CQM1, CQM1H, CPM2A/CPM2C, CPM1/CPM1A, C500,
C1000H, C2000H
CV Series
CV500, CV1000, CV2000, CVM1
CS/CJ Series
CS1G/CS1H, CS1G-H/CS1H-H, CJ1G, CJ1G-H/CJ1H-H, CJ1M, CP1H/CP1L, CJ2H
5
1-3 Connecting to the Host
The types of host that can be connected to a PT by using the serial ports on the NS-series PT and connecting to an RS-232C port at the host are described here.
1-3-1 Connecting to an RS-232C Port at the Host
Compatible Host Units
Some models and series of OMRON PLCs have the host link function built in.
In the CS-series or CQM1H PLCs, the host link method can be used by installing a Serial
Communications Board. In addition, some C200HX/HG/HE(-Z)E have an integral CPU Unit that can be connected in the host link method by installing a Communications Board.
Check the model and series of the PLC, the type of installed Serial Communications Board or
Serial Communications Unit before making a connection.
The PLC Units/Boards that can be connected to an NS-series PT through a Host Link connection using RS-232C ports on both the PLC Unit/Board and PT are listed in the following table.
PLC Series
CS Series
CPU Units with Built-in Host Link
Function
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
CPU Units Connectable with Host
Link Units or Expansion
Communications Board
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
Host Link Unit/
Communications
Board
CS1W-SCU21-V1
CS1W-SCB21-V1
CS1W-SCB41-V1
CJ Series
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1H-CPU65H/66H/67H-R
CJ2H-CPU64/65/66/67/68-EIP
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1H-CPU65H/66H/67H-R
CJ2H-CPU64/65/66/67/68-EIP
CJ1M-CPU11/12/13/21/22/23 CJ1M-CPU11/12/13/21/22/23
CP1H-XA40DR-A/XA40DT-D/XA40D
T1-D/X40DR-A/X40DT-D/X40DT1-D/
Y20DT-D
CP1W-CIF01
CP1L-L14DR-A/L14DR-D/L14DT-D/L
14DT1-D/L20DR-A/L20DR-D/L20DT-
D/L20DT1-D/M30DR-A/M30DR-D/M3
0DT-D/M30DT1-D/M40DR-A/M40DR-
D/M40DT-D/M40DT1-D
C Series
C2000H-CPU01-EV1
C200HS-CPU01/03/21/23/31/33-E
C200HE-CPU11/32/42-E
C200HE-CPU11/32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-CPU34/44/54/64/65/85-ZE
C200HS-CPU21/22/31/33-E
C200HE-CPU42-E
C200HE-CPU42-ZE
C200HG-CPU43/63-E
C200HG-CPU43/63-ZE
C200HX-CPU44/64-E
C200HX-CPU44/64/65/85-ZE
C200HE-CPU32/42-E
C200HE-CPU32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-CPU34/44/54/64/65/85-ZE
C200H-LK201-EV1
C200HW-COM02/04/
05/06-EV1
6
PLC Series
C Series
CPU Units with Built-in Host Link
Function
CPU Units Connectable with Host
Link Units or Expansion
Communications Board
C2000H-CPU01-EV1
Host Link Unit/
Communications
Board
CPM1-10/20/30CDR@ +CPM1-CIF01
CPM1A-10/20/30/40CD
CIF01
@ @ +CPM1-
C1000HF-CPUA1-EV1
C2000H-CPU01-EV1
CPM2A-30/40/60CD @@ @ +CPM1-
CIF01 (Peripheral port connection)
CPM2C-10/20 @@@@@@ @
(See note 1.)
CQM1-CPU21-E
CQM1-CPU41/42/43/44-EV1
CQM1H-CPU11/21/51/61 (See note 2.) CQM1H-CPU51/61 CQM1H-SCB41
CV Series
(See note 3.)
CVM1 Series
(See note 3.)
CV1000-CPU01-EV1 CV1000-CPU01-EV1
CV2000-CPU01-EV1 CV2000-CPU01-EV1
CV500-LK201 CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
SRM1-C02-V2 CompoBus/S master control unit
Note 1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01
RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
2: The CQM1H-CPU11 does not have a built-in RS-232C port, so connect to the peripheral port to the PT with a CS1W-CN118 Connecting Cable.
3: CPU Units of CVM1/CV-series PLCs without the suffix –EV @ cannot be connected.
Settings at the Host
When using the host link method, the settings shown below must be made at the host
(depending on the unit, some of these settings may not be necessary, or settings not shown here may be necessary).
I/O port
Communications speed
RS-232C
Set the same baud rate as set at the NS-series PT (See note 1.)
Transfer code ASCII, 7 data bits, 2 stop bits
Parity Even
1-to-1/1-to-N
Command level
1-to-N (See note 2.)
Level 1, 2, 3
Unit # 00
Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
2: The 1-to-N setting enables using a BCC (Block Check Character). It is not actually possible to connect more than one NS-series PT in a single Host Link.
The setting methods for each type of unit are described in the following.
7
Connecting to a C-series Host Link Unit
C200H/C200HS/C200HE(-Z)E/C200HG(-Z)E/C200HX(-Z)E Rack-mounted type: C200H-LK201-V1
Setting the Front Switches
Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
•
Unit # (SW1, SW2)
Set these switches to 0.
•
Command level, parity, and transfer code (SW4)
Set this switch to 2.
•
Communications speed (SW3)
Set this switch to 5 to select 9600 bps.
Set this switch to 6 to select 19200 bps.
Setting the Rear Switches
•
1-to-1/1-to-N selection (DIP switch)
Set #3 to ON.
CTS selector switch
External
0 V (ON)
•
CTS selection (selector switch)
Set this always to 0 V (ON).
C1000H/C2000H Rack-mounted type: C500-LK201-EV1
Setting the Front Switches
•
Mode control (key switch)
Set this to host link.
8
Setting the Rear Switches
I/O port
•
I/O port selection (selector switch)
Set this to RS-232C.
•
Unit # (DIP SW1)
Set SW1-1 to SW1-5 to OFF (0).
Synchronization
Terminator
0 V
•
Synchronization (selector switch)
Set this to Internal.
• Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
CTS selection (selector switch)
Set this always to 0 V (ON).
C1000H(F)/C2000H Rack-mounted type: C500-LK203
Setting the Rear Switches
•
I/O port selection (selector switch)
Set this to RS-232C.
5V supply
I/O port
•
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to OFF (0).
Synchronization
Terminator
0 V
•
Synchronization (selector switch)
Set this to Internal.
•
Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
CTS selection (selector switch)
Set this always to 0 V (ON).
9
C200H/C1000H/C2000H CPU Unit-mounted Type: C120-LK201-EV
Setting the Rear Switches
•
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to OFF (0).
* Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits.
•
Communications speed (DIP SW2-1 to SW2-4)
Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(0: OFF 1: ON)
• 1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
CTS selection (DIP SW3-1 and SW3-2)
Set SW3-1 to ON (1), and SW3-2 to OFF (0).
(Set this always to 0V.)
•
Synchronization (DIP SW3-3 to SW3-6)
Set SW3-3 and SW3-5 to ON (1), and
SW3-4 and SW3-6 to OFF (0). (Set these to Internal.)
Connecting to a CVM1/CV Series Host Link Unit
CVM1/CV-series Rack-mounted type: CV500-LK201
A CVM1/CV series host link unit (CV500-LK201) has two connectors (communications ports 1 and 2). Either of these ports can be used for connection to an NS-series PT by the RS-232C method. However, since the connectors at these ports are of different types, a cable that matches the connector must be prepared.
• Communications port 1
Communications port 1 is a 25-pin connector for RS-232C use only.
•
Communications port 2
Communications port 2 is a 9-pin connector which allows selection of the RS-232C or
RS-422A method. When this port is used with the RS-232C method, the I/O port selector switch on the front of the unit must be set to RS-232C (the upper position).
CPU Bus Unit Settings
When connecting to a CVM1/CV series host link unit, set the following communications conditions for the CPU Bus Unit settings.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note 1.)
Transfer code ASCII, 7 data bits, 2 stop bits
Parity Even
1-to-1, 1-to-N
Command level
1-to-N (See note 2.)
Level 1, 2, 3
Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
2: The 1-to-N setting enables using a BCC (Block Check Character). It is not actually possible to connect more than one NS-series PT in a single Host Link.
10
Set the CPU Bus Unit settings directly from a Programming Device (e.g. CX-Programmer).
For details on the CPU Bus Unit settings, refer to the SYSMAC CVM1/CV-series Host Link
Unit Operation Manual (W205-E1@ ).
Setting The Front Switches
•
Unit # (SW3, SW4)
When using communication port 2, set these switches to 0.
•
I/O port selection (selector switch)
Set this to RS-232C.
•
CTS selection (DIP SW2 and SW3)
Set SW2 or SW3 to ON. (Set this always to 0V.)
To use communication port 1, set SW2. To use communication port 2, set SW3.
•
Communication condition setting (DIP SW1)
Set this switch to OFF.
Communication is executed in accordance with the
CPU bus unit system settings made at the PLC. The initial values for the system settings are as follows.
- Communications speed: 9600 bps
- Parity: Even
- Xon/Xoff control: Not executed
- Communication method: Full duplex
- Stop bits: 2 stop bits
- Data length: 7 bits
Connecting to a CS-series Serial Communications Unit
CS-series Rack-mounted type: CS1W-SCU21(-V1)
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
Set the unit number to 0 through F so that it will not overlap with the numbers used in other units.
Allocation DM Area Settings in CPU Unit
Settings are written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit.
After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communications port, or execution of the STUP command.
In the following, the words allocated in the DM area and the settings are shown.
11
m = DM 30000 + 100
× unit number (word address) m
Allocation DM area word
Port 1 Port 2 m+10
Writing
Value
Settings
8000 Host link mode, 2 stop bits, even parity, data length
7 bits m+1 m+11 0000 Communications speed 9600 bps. m+2 m+3 m+12 m+13
0007 Communications speed 19200 bps.
0000 Transmit delay time 0 ms.
0000 No CTS control Unit No.0 for host link
Connecting to a CJ-series Serial Communications Unit
CJ-series Rack-mounted Type: CJ1W-SCU21/41-V1
Setting the Front Switches
Set the unit number for the Serial Communications Unit using the rotary switch on the front of the Unit. Follow the procedure below use a flat-head screwdriver ( − ) to set the number and sign in the setting display window.
Port 2 on the CJ1W-SCU41-V1 is an RS-232C port.
CJ1W-SCU21-V1 CJ1W-SCU41-V1
• Unit Number Setting
Set a number from 0 to
F that does not overlap another unit.
• Port 1
RS-232C
• Unit Number Setting
Set a number from 0 to
F that does not overlap another unit.
• Port 2
RS-232C
• Port 2
RS-232C
Setting CPU Unit Allocation DM Area Words
Settings can be directly written to the Allocation DM Area (System Setup Area) by using a
Programming Device, such as a Programming Console or the CX-Programmer. After the settings are written, the settings will become valid by performing any of the following: turning on the power supply again, restarting the Unit, restarting the communications port, or executing a STUP instruction.
12
The following table shows words allocated in the DM Area and setting details. m = D30000 + 100
×
unit number (word address)
Writing Value Setting details m
Allocation DM area word
Port 1 Port 2 m+10 8000 Host link mode, 2 stop bits, even parity,
7-bit data length
Baud rate: 9,600 bps m+2 m+3 m+12 m+13
0007
0000
0000
Baud rate: 19,200 bps
Transmission delay time: 0 ms
No CTS control, Unit number 0 for host link
Connecting to a CPU Unit
CV-series and CVM1/CV-series (-EV @ ) CPU Units
CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1
CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2
PLC Setup
When connecting to a CVM1/CV series CPU Unit, set the following communications conditions for the PLC Setup.
Item
Communications speed
Setting at Host
Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
Either set PLC Setup directly from a Programming Device (e.g. CX-Programmer), or transmit the PLC Setup made at a Programming Device to the CPU UNIT.
For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/1000/2000 Operation
Manual: Ladder Diagrams (W202-E1@ ).
13
Setting the Front Switches
•
I/O port selection (selector switch)
Set this to RS-232C.
I/O port selector switch
•
System setting (DIP SW4)
To effect the existing DIP switch settings, set SW4 to ON.
To effect the existing PC Setup, set
SW4 to OFF.
Note
For CPUs manufactured before or during June 1995 (lot No. @@ 65), the existing DIP switch settings differ from the existing PC Setup as follows.
- DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7 bit data length
- PC Setup:
9,600 bps, 2 stop bits, even parity, 7 bit data length
For CPUs manufactured from July 1995 onward (lot No. @@ 75), the stipulated values in the DIP switch settings also are 9,600 bps and 2 stop bits.
C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, CQM1H CPU Units, SRM1
The connection method depends upon the model of PLC being used, as shown in the following table.
PLC model
C200HS, CQM1
C200HX/HG/HE(-Z)E
CQM1H
CPM1
CPM2A, SRM1
CPM2C
Connection method
Connect to the CPU Unit’s built-in RS-232C port.
•
Connect to the CPU Unit’s built-in RS-232C port.
•
Connect to one of the RS-232C ports (port A or port B) on a Serial
Communications Board.
•
Connect to the CPU Unit’s built-in RS-232C port.
•
Connect to the peripheral port through a CS1W-CN118
Connecting Cable.
•
Connect to the RS-232C port (port 1) on a Serial Communications
Board.
Connect to the peripheral port through a CPM1-CIF01
RS-232C Adapter.
•
Connect to the CPU Unit’s built-in RS-232C port.
•
Connect to the peripheral port through a CPM1-CIF01 RS-232C
Adapter.
Connect to the CPU Unit’s RS-232C port or the peripheral port through a Connecting Cable (CPM2C-CN111, CS1W-CN118, or CS1W-CN114).
(The CPM2C-CN111 splits the Unit’s communications port into an RS-232C port and a peripheral port. A CPM1-CIF01
RS-232C Adapter is also required to connect to this peripheral port.)
PLC Setup Area Settings
When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, or
CQM1H CPU Unit, or SRM1, set the following communications conditions for the PLC Setup area.
Item
Communications mode
Communications speed
Stop bit
Setting at Host
Host link mode
Set the same baud rate as set at the NS-series PT (See note.)
2 stop bits
14
Item Setting at Host
Parity Even
Data length
Unit #
ASCII 7 bits
00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer).
For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.
The PLC Setup area word numbers and settings to be made depending on the unit and port to which the connection is made are shown below.
CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection
Word
DM6650
DM6651
Writing Value
0001
0303
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00 DM6653 0000
C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than the CPU11), or SRM1: Built-in RS-232C port connection
Word
DM6645
Writing Value
0001
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM
DM6646 0303
0304
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00 DM6648 0000
C200HX/HG/HE(-Z)E: Serial Communications Board port A, CQM1H: Serial Communications
Board port 1
Word
DM6555
DM6556
DM6558
Writing Value
0001
0303
0304
0000
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM area
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00
15
C200HX/HG/HE(-Z)E: Board Port B Connection
DM6550
DM6551
0001
0303
0304
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00 DM6553
CPM1 Connection
Word
DM6650
0000
Writing Value
0001
DM6651
DM6653
0303
0304
0000
Settings
Host link mode, communications conditions set by the contents of DM area
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS-series PLCs.
The CPM2C’s communications port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select
RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details.
Port connecting to PT
RS-232C port (D-Sub 9-pin) of CPM2C-CN111
Peripheral port of CPM2C-CN111
RS-232C port (D-Sub 9-pin) of CS1W-CN118
Peripheral port of CS1W-CN114
Peripheral port
PLC Setup
Built-in RS-232C port settings
Peripheral port settings
Built-in RS-232C port settings
Peripheral port settings
RS-232C port
(D-Sub 9-pin, female)
Peripheral port
RS-232C port
(D-Sub 9-pin, female)
Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1 or CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup area (data memory) effective.
16
RS-232C port communication condition setting
Set DIP SW5 to OFF to make the settings made in
PC Setup effective.
When using the CQM1H’s built-in peripheral port, turn ON SW7.
Setting the Switches of a CPM2A
When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
Set the Communications switch to OFF (down position).
Setting the Switches of a CPM2C
When using a CPM2C, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS-232C port.
•
Connecting PT to peripheral port
•
Connecting PT to built-in RS-232C port
(A device that requires non-standard communications settings is connected to the peripheral port.)
• Connecting PT to built-in RS-232C port
(A Programming Console is connected to the peripheral port.)
Setting the Switches on a RS-232C Adapter
When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown in the following diagram.
Set the mode setting switch to HOST (upper position).
17
CS-series CPU Unit type: CS1G/H-CPU-EV1, CS1G/H-H
Connect to the built-in RS-232C port of the CPU Unit, or the RS-232C port of the
Communications Board. Note that the connection to a peripheral port must be made via an
RS-232C adapter (CS1W-CN118) specially designed for connecting to a peripheral port.
PLC Setup
When connecting to a CS-series CPU Unit, set the following communications conditions for the PLC Setup area. Since the settings shown below are the PLC default settings for the CPU
Unit, no change to the PLC Setup is necessary as long as the communications speed is maintained at 9600 bps.
Item
Communications speed
Setting at Host
Set the same baud rate as set at the NS-series PT (See note.)
Stop bits 2 stop bits
Parity Even
Data length
Unit No. for the host link
ASCII 7 bits
00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
When the communications speed is set to 19200 bps., the PLC Setup of the CPU Unit need to be changed.
Either set the PLC Setup directly from a Programming Device (Programming Console), or transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU Unit.
For details on PLC Setup, refer to the SYSMAC CS series Operation Manual (W339-E1@ ).
When using the built-in RS-232C port of CS1G/H
Word #
160
161
Writing Value
8000
0000
0007
166 0000
When using the peripheral port of CS1G/H
Settings
Host link mode, data length 7 bits, 2 stop bits, even parity
Communications speed: 9600 bps.
Communications speed: 19200 bps.
Word #
144
145
Writing Value
8000
0000
0007
150 0000
Settings
Host link mode, data length 7 bits, 2 stop bits, even parity
Communications speed: 9600 bps.
Communications speed: 19200 bps.
Setting the Front Switches
Set the CPU Unit DIP switches to 4 or 5 in accordance with the port the NS-Series PT is connected to.
18
DIP switches (inside the battery storage)
•
Set SW4 to ON (establishing communication in accordance with PC Setup) when connecting the NSseries PT to a peripheral port.
•
Set SW5 to OFF (establishing communication in accordance with PC Setup) when connecting the NSseries PT to an RS-232C port.
Peripheral port
This is used mainly for connection to the
Programming Device.
(This also supports the
RS-232C unit connection.)
RS-232 port
This is used mainly for connection to the RS-232C unit.
(This also supports the
CX-Programmer.)
Connecting to CS1 Series Serial Communications Board
Serial Communications Board equipped with an RS-232C port for CS-series CPU Units:
CS1W-SCB41/21-V1
Allocation DM Area Settings in CPU Unit
Settings are written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit.
After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communications port, or execution of the STUP command.
In the following, the words allocated in the DM area and the settings are shown.
Allocation DM area word
Port 1
D32000
Port 2
D32010
Writing Value
8000
Settings
D32001 D32011 0000
D32002
D32003
D32012
D32013
0007
0000
0000
Host link mode, 2 stop bits, even parity, data length 7 bits
Communications speed 9600 bps.
Communications speed 19200 bps.
Transmit delay time 0 ms.
No CTS control, Unit No. 0 for host link
1-3-2 Connecting to an RS-422A/485 Port at the Host
Compatible Host Units
Some models and series of OMRON PLCs have the RS-422A type host link function built in.
With the CS-series and CQM1H, the host link method can be used by installing a serial
Communications Board. In addition, some C200HX/HG/HE(-Z)E devices have an integral
CPU Unit that can be connected in the host link method by installing a Communications
Board.
With the CPM2A and CPM2C, an RS-422A type of 1:1 NT Link can be created through a
CPM1-CIF11 RS-422A Adapter.
19
Check the model and series of the PLC and the type of the installed Board or Unit before making a connection.
The PLC Units that provide an RS-422A Host Link interface and that can be connected to an
NS-series PT port to which an RS-232C/RS422A Link Adaptor (NS-AL002) is connected are listed in the following table.
PLC
Series
Host Link Unit/
Communications Board
CS
Series
CJ
Series
CPU Units with Built-in Host Link
Function
CPU Units Connectable with
Host Link Units or Expansion
Communications Board
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/
67H
CJ1G-CPU44/CPU45
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1H-CPU65H/66H/67H-R
CJ2H-CPU64/65/66/67/68-EIP
CJ1M-CPU11/12/13/21/22/23
CP1H-XA40DR-A/XA40DT-D/XA
40DT1-D/X40DR-A/X40DT-D/X4
0DT1-D/Y20DT-D
CP1L-L14DR-A/L14DR-D/L14DT-
D/L14DT1-D/L20DR-A/L20DR-D/
L20DT-D/L20DT1-D/M30DR-A/M
30DR-D/M30DT-D/M30DT1-D/M
40DR-A/M40DR-D/M40DT-D/M4
0DT1-D
CS1W-SCB41-V1
CJ1W-SCU41-V1
CP1W-CIF11
C
Series
C2000H-CPU01-EV1
C200HS-CPU01/03/21/23/31/33-E
C200HE-CPU11/32/42-E
C200HE-CPU11/32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-
CPU34/44/54/64/65/85-ZE
C200H-LK202-EV1
C200HE-CPU32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-
CPU34/44/54/64/65/85-ZE
C2000H-CPU01-EV1
C1000HF-CPUA1-EV1
C2000H-CPU01-EV1
CPM1-10/20CDR@ +CPM1-CIF11
CPM1A-10/20/30/40CD @ @ +CPM1-CIF11
20
PLC
Series
CPU Units with Built-in Host Link
Function
C
Series
CPM2A-30/40/60CD @@ @ +CPM1-CIF11
(Peripheral port connection)
CPM2C-10/20 @@@@@@ @ (See note 1.)
CPU Units Connectable with
Host Link Units or Expansion
Communications Board
Host Link Unit/
Communications Board
CV
Series
(See note
2.)
CVM1
Series
(See note
2.)
CV1000-CPU01-EV1 CV1000-CPU01-EV1
CV2000-CPU01-EV1 CV2000-CPU01-EV1
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
SRM1 SRM1-C02-V2+CPM1-CIF11
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
CV500-LK201
Note 1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01
RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
2: CPU Units of CVM1/CV-series PLCs without the suffix -EV @ cannot be connected.
The RS-485 interface (2-wire method) provided by NS-series PTs is for connecting to an
OMRON Temperature Controller. Do not connect it to an NS-series PT or PLCs using RS-485.
Settings at the Host
When using the RS-422A type host link method, the settings shown below must be made at the host (depending on the unit, some of these settings may not be necessary, or settings not shown here may be necessary).
Item Setting at Host
I/O port RS-422A
Communications speed Set the same baud rate as set at the NS-series PT (See note 1.)
Transfer code ASCII, 7 data bits, 2 stop bits
Parity Even
1-to-1/1-to-N
Command level
Unit #
1-to-N (See note 2.)
Level 1, 2, 3
00
Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
2: The 1-to-N setting enables using a BCC (Block Check Character). It is not actually possible to connect more than one NS-series PT in a single Host Link.
The setting methods for each type of unit are described in the following.
21
Connecting to a C Series Host Link Unit
C200H/C200HS/C200HE(-Z)E/C200HG(-Z)E/C200HX(-Z)E Rack-mounted Type: C200H-LK202-V1
Setting the Front Switches
Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following:
• Unit # (SW1, SW2)
Set these switches to 0.
• Command level, parity, and transfer code (SW4)
Set this switch to 2.
•
Communications speed (SW3)
Set this switch to 5 to select 9600 bps.
Set this switch to 6 to select 19200 bps.
Setting the Rear Switches
•
Terminator setting (selector switch)
Set this switch to ON.
Terminator
• 1-to-1/1-to-N protocol selection (selector switch)
Set this switch to 1-to-N (OFF).
22
C1000H/C2000H Rack-mounted Type: C500-LK201-EV1
Setting the Front Switches
• Mode selector (key switch)
Set this to Host link.
Setting the Rear Switches
• I/O port selection (selector switch)
Set this to RS-422A.
I/O port
Synchronization
Terminator
0 V
•
Unit # (DIP SW1)
Set SW1-1 to SW1-5 to OFF (0).
• Synchronization (selector switch)
Set this to Internal.
• Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19200 bps.
Set these switches to 1010 to select
9600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
• Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
• CTS selection (selector switch)
Set this always to 0 V (ON).
•
Terminator setting (selector switch)
Set this switch to ON.
23
C1000H(F)/C2000H Rack-mounted Type: C500-LK203
Setting the Rear Switches
• I/O port selection (selector switch)
Set this to RS-422A.
5V supply
I/O port • Unit #, parity, and transfer code
(DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to OFF (0).
Synchronization
• Synchronization (selector switch)
Set this to Internal.
Terminator
0 V
• Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
• CTS selection (selector switch)
Set this always to 0 V (ON).
• Terminator setting (selector switch)
Set this switch to ON.
C200H/C1000H/C2000H CPU-mounted Type: C120-LK202-EV1
Setting the Rear Switches
•
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to OFF (0).
* Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits.
• Communications speed (DIP SW2-1 to SW2-4)
Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(0: OFF 1: ON)
• 1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
• Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
• Terminator setting (DIP SW3-1 to SW3-6)
Set SW3-1, SW3-3, and SW3-5 to ON (1).
Set SW3-2, SW3-4, and SW3-6 to OFF (0).
(Set terminator ON.)
24
Connecting to a CVM1/CV Series Host Link Unit
CVM1/CV series Rack-mounted Type: CV500-LK201
A CVM1/CV series host link unit (CV500-LK201) has two connectors (communications ports 1 and 2). To use the RS-422A type host link method, set communications port 2 to RS-422A.
Communications port 2 is a 9-pin connector which allows selection of the RS-232C or
RS-422A method. When this port is used with the RS-422A method, the I/O port selector switch on the front of the unit must be set to RS-422A (the lower position).
CPU Bus Unit Settings
When connecting to a CVM1/CV series host link unit, set the following communications conditions for the CPU Bus Unit settings.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note 1.)
Transfer code ASCII, 7 data bits, 2 stop bits
Parity Even
1-to-1/1-to-N
Command level
1-to-N (See note 2.)
Level 1, 2, 3
Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
2: The 1-to-N setting enables using a BCC (Block Check Character). It is not actually possible to connect more than one NS-series PT in a single Host Link.
Set the CPU Bus Unit settings directly from a Programming Device (e.g., CX-Programmer).
For details on the CPU Bus Unit settings, refer to the SYSMAC CVM1/CV-series Host Link
Unit Operation Manual (W205-E1@ ).
25
Setting the Front Switches
•
Unit # (SW3, SW4)
Set these switches to 0.
Communications port 1
(RS-232C)
Communications port 2
(RS-232C/RS-422A)
I/O port selector switch •
I/O port selection (selector switch)
Set this to RS-422A.
• Communication condition setting (DIP SW1)
Set this switch to OFF.
Communication is executed in accordance with the CPU bus unit system settings made at the PLC. The initial values for the system settings are as follows.
- Communications speed: 9,600 bps
- Parity: Even
- Xon/Xoff control: Not executed
- Communication method: Full duplex
- Stop bits: 2 stop bits
- Data length: 7 bits
• Terminator setting (selector switch)
Set this to ON.
Connecting to a CPU Unit
CVM1/CV-series (-EV @ ) CPU Units
• CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1
•
CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2
PLC Setup
When connecting to a CVM1/CV-series CPU Unit, set the following communications conditions for the PLC Setup.
Item
Communications speed
Setting at Host
Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
Parity Even
Data length
Unit #
ASCII 7 bits
00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
Either set the PLC Setup directly from a Programming Device (e.g. CX-Programmer), or transmit the PLC Setup made at a Programming Device to the CPU Unit.
For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/CV1000/ CV2000
Operation Manual: Ladder Diagrams (W202-E1@ ).
26
Setting the Front Switches
•
I/O port selection (selector switch)
Set this to RS-422A.
• Communication type setting (DIP SW3)
Set SW3 to OFF.
(for host link communication)
I/O port selector switch
• Host link default value settings
(DIP SW4)
To effect the existing DIP switch settings, set SW4 to ON.
To effect the values set in the PC Setup, set SW4 to OFF.
Note
For CPUs manufactured before or during June 1995 (lot No. @@ 65), the existing DIP switch settings differ from the PC Setup default values as follows.
- Existing DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7 bit data length
- PC Setup default values:
9,600 bps, 2 stop bits, even parity, 7 bit data length
For CPUs manufactured from July 1995 onward (lot No. @@ 75), the stipulated values in the DIP switch settings also are 9600 bps and 2 stop bits.
• Terminator setting (DIP SW6)
Set this switch to ON.
(Set terminator ON.)
C-series C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1H, CPU Unit or SRM1
The connection method depends upon the model of PLC being used, as shown in the following table.
PLC model
C200HX/HG/HE(-Z)E
CQM1H
CPM1
CPM2A, SRM1
CPM2C
Connection method
•
Connect to the RS-422A port (port A) on a Communications Board.
• Connect to the RS-422A port (port 2) on a Serial Communications
Board.
•
Connect to the peripheral port through a CPM1-CIF11 RS-422A
Adapter.
•
Connect to the peripheral port through a CPM1-CIF11 RS-422A
Adapter.
•
Connect to the peripheral port (on a CPM2C-CN111 or
CS1W-CN114 Connecting Cable) through a CPM1-CIF11 RS-422A
Adapter.
(The CPM2C-CN111 splits the Unit’s communications port into a
RS-232C port and a peripheral port.)
Reference
• There are no Communications Boards for the
C200HX/HG/HE(-Z)E in which port B is the RS-422A port.
• There are no Serial Communications Boards for the
CQM1H in which port 1 is the RS-422A port.
27
PLC Setup Area Settings
When connecting to a C200HX/HG/HE(-Z)E or CPM1, CPM2A, CPM2C, CQM1H CPU Units or SRM1, set the following communications conditions for the PLC Setup area.
Item
I/O port
Communications mode
Communications speed
Stop bit
Setting at Host
RS-422A
Host link mode
Set the same baud rate as set at the NS-series PT (See note.)
2 stop bits
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link .
Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer).
For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.
The PLC Setup area word numbers and settings to be made depending on the unit to which the connection is made are shown below.
When using port A of the Communications Board of C200HX/HG/HE(-Z)E
Word #
DM6555
DM6556
Writing Value
0001
0303
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM area
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00 DM6558 0000
When using a CPM1, CPM2A, CPM2C, SRM1
Word #
DM6650
DM6651
DM6653
Writing Value
0001
0303
0304
0000
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM area
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00
28
When using a CQM1H
Word #
DM6550
Writing Value
0001
DM6551 0303
0304
Settings
Host link mode, no CTS control, communications conditions set by the contents of DM area
Data length 7 bits, 2 stop bits, even parity, communications speed: 9600 bps
Data length 7 bits, 2 stop bits, even parity, communications speed: 19200 bps
Unit # 00 DM6553 0000
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS-series PLCs.
The CPM2C’s communications port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select
RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details.
Peripheral port
Peripheral port
RS-232C port
(D-Sub 9-pin, female)
Setting Switches on a C200HX/HG/HE(-Z)E Communications Board
Set the switches on a C200HX/HG/HE(-Z)E Communications Board as follows.
Switch 1: Set to 4 (4-wire type, for RS-422A)
Switch 2: Set to ON for terminator ON (termination resistance applied)
Setting Switches on a CQM1H Serial Communications Board
Set the switches on a CQM1H Serial Communications Board as follows.
2-wire/4-wire selection (WIRE): Set to 4 (4-wire type, for RS-422A)
Terminator (TERM): Set to ON for termination ON (termination resistance applied).
Serial Communications Board
(Inner Board slot 1)
Terminator Switch (TERM)
Set to ON (right side).
2-wire/4-wire Selection Switch
(WIRE)
Set to 4 (right side).
29
Setting the Switches on an RS-422A Adapter
Set the terminator selector switch to ON (upper position).
Connecting to a CS-series Serial Communications Board
Serial Communications Board with an RS-422A/485 port equipped for CS-series
CPU Unit Type: CS1W-SCB41(-V1) (The port 2 is an RS-422A/485 port.)
Allocation DM Area Settings in CPU Unit
Settings are written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit.
After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communications port, or executing the STUP command.
In the following, the words allocated in the DM area and the settings are shown.
Allocation DM area word
Port 2
D32010
Writing Value
8000
Settings
D32011
D32012
D32013
0000
0007
0000
0000
Host link mode, 2 stop bits, data length 7 bits, even parity,
Communications speed 9600 bps.
Communications speed 19200 bps.
Transmit delay time 0 ms.
No CTS control, Unit No. 0 for host link
30
Connecting to a CJ-series Serial Communications Unit
CJ-series Rack-mounted Serial Communications Unit: CJ1W-SCU41-V1
(Port 1 is an RS-422A/ 485 port.)
Setting the Front-panel Switches
Set the unit number for the Serial Communications Unit using the rotary switch on the front panel of the Unit. Use a flat-head screwdriver to set the unit number in the setting display window.
Set the terminator switch to ON (right side).
Set the 2-wire/4-wire selection switch to 4 (right side).
• Terminator Switch (TERM)
Set to ON (right side).
• Unit Number Setting
Set a number between 0 and F. Do not set a number used by another Unit.
• 2-wire/4-wire Selection Switch
(WIRE)
Set to 4 (right side).
• Port 1
RS-422A/485
Setting Parameters Allocated in the DM Area in the CPU Unit
Settings can be directly written to the words allocated to the Serial Communications Unit in the DM Area (System Setup Area) by using a Programming Device, such as a Programming
Console or the CX-Programmer. Any changes to the settings can be enabled by cycling the power supply, restarting the Unit, restarting the communications port, or executing a STUP instruction.
The following table lists the words allocated in the DM Area and setting details.
M = D30000 + 100
×
unit number (word address)
Allocation DM Area word
Port 1 Port 2 m M+10
Write value Setting details
M+1 M+11
M+2
M+3
M+12
M+13
0000
0007
0000
0000
7-bit data
Baud rate: 9,600 bps
Baud rate: 19,200 bps
Transmission delay time: 0 s
No CTS control, unit number 0 for Host
Link
31
1-4 Settings for Host Link
This section describes the procedure for making the NS-V1 PT settings for connecting to the host by means of Host Link communications.
Use either serial port A or B. The flow of operations for connecting to the host is as follows:
(1) Design the screen data.
(2) Transfer the screen data.
(3) Set the communications method for serial port A or B
(4) Connect to the host.
1-4-1 Designing the Screen Data
Use the CX-Designer to create the screen data. First, select Communication Setting from the PT Menu to display the Communication Setting Dialog Box.
Select Serial Port A or Serial Port B . Then set the serial port to PLC and the protocol to Host
Link .
1-4-2 Transferring Screen Data
Use the transfer program to transfer the screen data to the NS-V1/V2 PT.
For details on transferring screen data, refer to Transferring Data to the PT in the
CX-Designer online help.
1-4-3 Setting the Communications Method for Serial Port A or B
This procedure is not required if the method has already been set in 1-4-1 Designing the
Screen Data above. At the NS-V1/V2 PT, set Host Link as the communications method for the serial port that is to be used to connect to the host by means of Host Link communications.
Also set the baud rate to same value as the host.
These settings are made from the NS-V1/V2 PT’s System Menu.
32
(1) Press the Comm. Tab in the System Menu to display the Communications Setup Screen.
(For the NS5 PT, press the Comm.
Button in the System Menu to display the screen, and then press the
←
and
→
Screen Switching Buttons to display the screen for page (2/3).
(2) Press the drop-down menu button and set Host Link as the communications method for serial port A or B.
(3) Press the Detail Button to display the Host Link settings, and select Comm. Speed .
(4) Press the Write Button and press the Yes Button on the following dialog boxes to restart the NS-V1/V2.
NS12/NS10/NS8-V1/V2 PT
(The screen is somewhat different for the NS12.)
NS5
33
1-4-4 Connecting to the Host
Connect in the same way as for a 1:1 NT Link, and use the same cables that are used for a
1:1 NT Link connection.
If cables must be prepared, refer to the relevant manuals for the PLC or Host Link Unit, and to the NS Series Setup Manual (Cat. No. V083).
34
1-5 PLC Areas That Can Be Used for Communications
OMRON C-series PLCs
PLC model
C200HS
C200HE/HG/HX(-Z)
00000 to
00511
00000 to
00099 to
00063 to
00031
00000 to
00027
00000 to
00063 to
00031
00000 to
00511 to
00127
00000 to
06655
07000 to
09999
00000 to
00511
-
00000 to
06143
-
C2000H
CQM1
CQM1H to
00255 to
00099 to
00019
00200 to
00255 to
00019 to
00015
CPM2A/CPM2C 00000 00000 to
00049 to
00023
00200 to
00255 to
00027 to
00063
00000 to
00015 to
00511
00000 to
00127
00000 to
00255 to
04095
00000 to
06655
00000 to
06655
00000 to
01023
06144 to
06655
00000 to
02047
06144 to
06655
-
00000 to
06143
-
-
35
CVM1/CV-series PLCs
PLC model
CV500
CVM1-CPU01-V @
CVM1-CPU11-V @
00000 to
02555
00000 to
02555 to
00511 to
00511 to
08191
-
- to
00511 to
01023 to
09999
CV1000 00000 -
CV2000
CVM1-CPU11-V @ to
02555 to
00511 to
01023 to
09999
CVM1-CPU21-V @
Note 1: The HR Area is included in the CIO Area. To use the HR Area, specify the CIO Area.
2: Do not use this area for creating screens. It cannot be used with Host Link communications.
OMRON CS/CJ-series PLCs
PLC model
CS1G/H(-H)
CJ1G/H(-H)
CJ1M
CP1L
CP1H
CJ2H
00000 to
06143
00000 to
00511
00000 to
00959 to
02047 to
09999
00000 to
09999
-
Note 1: The EM Area cannot be specified for the CJ1M.
2: Do not use this area for creating screens. It cannot be used with Host Link communications.
36
1-6 Restrictions
Applicable Project Versions
When connecting to the host by means of Host Link communications, use version 6.0 or later for creating the screen data (project) to be transferred to the NS-V1/V2 PT.
To use a project of version 5.x or earlier, first use CX-Designer to convert the project to version 6.0 or later before transferring it to the NS-V1/V2 PT.
Applicable Serial Ports
Either NS-V1/V2 serial port A or B can be used to connect to the host by means of Host Link communications.
Applicable NS Models
Only NS-series PT models with a -V1/V2 suffix can be used to connect to the host by means of Host Link communications. NS-series PT models without the -V1/V2 suffix cannot be connected.
37
Revision History
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Cat. No.
V098-E1 -04
Revision Code
Revision code
01
02
03
04
Date
July 2004
July 2006
July 2007
June 2008
Revised content
Original production
Revisions made for the release of the CX-Designer.
Pages 6 and 20: CJ-series CPU Unit model numbers added.
Cover: Added models to list of NS-series PT.
Page 3: Added 3 models to end of model table in section 1-2-1.
Page 5: Added CJ2H to list of CS/CJ-series PLCs.
Pages 6 and 19: Added models to CJ-series PLCs in table.
Page 26: Added CJ2H to PLC models listed in table.
38