The TSX AEM 160x high level analog input module has recently been added to the range of TSX AEM 411, TSX AEM 412, TSX AEM 413, TSX AEM 811 and TSX AEM 821 modules.
The AEM 160x module is compatible with TSX V3 (TSX 47.30/67.20/87.30) and
TSX/PMX model 40 (TSX or PMX 47.40/67.40/87.40/107.40) PLCs.
The following comparative tables give the main characteristics of the two versions of the module for the user who is already familiar with the TSX AEM 811 and TSX /AEM 821 modules. It is, however, still advisable to read the whole of this document.
Hardware characteristics
_________________________________________________________________________________________
TSX AEM 821 TSX AEM 811 TSX AEM 160x
Input range 1 range for all 8 channels
±
10V 0-10V
0-20mA 4-20mA
1 range per channel 1 range per channel
±
10V
±
5V 0-10V AEM 1601 :
±
10 V
2-10 V
±
5 V 1-5 V
0-20mA 4-20mA AEM 1602 : 0-20 mA
Resolution for
±
10 V range
Accuracy at 25
Acquisition time
°
C
5mV (4000 points)
0.23 % full scale
2 to 2.5ms/channel
Isolation between chs not isolated
Recalibration solid state
1.5s
automatic
0.3mV
(65 000 points)
0.1%
100ms/channel
500 V DC
500 V AC relay
10s recommended
2.5 mV
(8 000 points)
0.2 % full scale
15 ms/channel not isolated
1500 V AC solid state
1s by the user via special software
_____________________________________________________________________
1
_____________________________________________________________________
Software and operating characteristics
__________________________________________________________________________________________
TSX AEM 821
Measurement acquisition 2 groups x 4 registers
(group selected on demand) message mode, ext.
TSX AEM 811 multiplexing on
4 register words message mode
TSX AEM 160x message mode extended register mode (V4)
Sampling time :
. normal mode
Scaling calculation
Associated processing
6ms + 2.5ms x no. of chs periodic : defined by the user
(800ms to 3200s)
6ms + 2 ms x no. of chs 100ms x no. of chs function of no. of chs
3 types of scaling
< 400ms
3 types of scaling
. square root square root normal mode :
240 ms filtered mode :
50 Hz 1.28 s
60 Hz 1.066 s
< 240 ms standard square root
Threshold detection
Generation of interrrupt
Measurement tests
. 2 thresholds per ch.
. interrupts on rising or
2 thresholds per ch.
YES
. sensor break
4-20 mA
. passband overshoot
. input range
NO
. sensor continuity
. input range
overshoot no thresholds
NO
(no thresholds) sensor break voltage ranges and 4-20 mA input range overshoot
IMPORTANT
The information given in sections 3.1 to 3.5 is for the "traditional" method of setting up
TSX AEM 160x modules, the only method available for TSX V3 (TSX P 47.30/67.20/
87.30) PLCs.
Although it is possible to use this method with TSX/PMX model 40 PLCs, it is strongly recommended that the TXT LPL7 PCL V43 or the TXT LPL7 PMS V43 software package is used for setting up modules. These packages have all the tools required for entering configuration parameters in conversational form, and automatically transferring these parameters from the PLC memory to the module memory. Section 3.6 reviews the main features of these software packages.
_____________________________________________________________________
2
X
_________________________________________________________________________________________
General introduction
Page
5
6
7
________________________________________________________________________________________
Operation 11
12
13
15
21
24
________________________________________________________________________________________
Configuration 27
28
30
32
33
35
37
________________________________________________________________________________________
Operation 39
40
42
44
49
_________________________________________________________________________________________
Application example 51
52
55
67
_____________________________________________________________________
3
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
Hardware installation
Page
79
80
80
81
83
84
_________________________________________________________________________________________
Specifications 85
86
86
88
________________________________________________________________________________________
Appendix 89
90
_____________________________________________________________________
4
X
General introduction
1
General introduction
Section 1
Page
1.1
Intelligent modules 6
1.1-1 Introduction
1.1-2 Use
_________________________________________________________________________________________
1.2
TSX AEM 1601 and 1602 modules 7
6
6
1.2-1 Description
1.2-2 External appearance
7
9
_______________________________________________________________________
5
_______________________________________________________________________
1.1
Intelligent modules
1.1-1 Introduction
Intelligent modules are preprogrammed processor modules designed by Telemecanique for distributed processing applications.
The modules are designed as follows :
Structure of an intelligent I/O module
PLC bus
Inputs from the application
Bus interface
Shared memory
Processing unit
Specific interface
Outputs to the application
They comprise :
• An interface bus using standard communication modes between the PLC processor and the intelligent module :
- Discrete interface
- Register interface
- Message interface
• A shared memory in which data is stored, accessible to both the intelligent module and the PLC processor
• A processing unit comprising a processor and operating software
• Inputs/outputs specific to the module
__________________________________________________________________________
1.1-2 Use
Intelligent modules simplify the user program by the employment of a processor with preprogrammed functions.
As these functions are configured by the user, use of the intelligent modules requires a knowledge of PL7-3 software. It may be necessary to refer to appropriate manuals for additional information.
_______________________________________________________________________
6
General introduction
1
1.2
TSX AEM 1601 and 1602 analog input modules
1.2-1 Description
General
The TSX AEM 1601 and 1602 are analog input modules with 16 high level channels.
Used together with sensors or voltage transmitters (for the TSX AEM 1601), or current transmitters (for the TSX AEM 1602), they can be used for monitoring functions, analog measurement or controlling continuous processes.
Functions
In addition to analog/digital conversion, these modules provide the following functions :
• A choice of input ranges (select from the range by channel)
• Monitoring overshoots of input values in relation to limits for selected range
• Scaling of measurements to a standard range
• Extraction of the square root of the measurement
• Detection of sensor break for the range
±
10 V,
±
5 V, 1-5 V and 4-20 mA.
Inputs/Outputs
Application
Analog electrical values
➤
Ch. 0
Ch. 1
Ch. 2
Ch. 3
Ch. 4
Ch. 5
Ch. 6
Ch. 7
Ch. 8
Ch. 9
Ch. 10
Ch. 11
Ch. 12
Ch. 13
Ch. 14
Ch. 15
MODULE
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
TSX AEM
PLC processor
➤
Digital measurements for the 16 channels
Configuration
= adapting the module to the application
Data received from the application :
The module receives the analog electrical values from sensors or transmitters.
_______________________________________________________________________
7
_______________________________________________________________________
Data transmitted to the PLC :
• Measurements : analog input values converted to digital values
• Status words : report on module operation and the monitoring of the sensors
Data received from the PLC :
• Configuration : declared by the user before the measurements can be acquired, fixes the operating characteristics of the module
Characteristics
The main characteristics of the modules are :
______________________________________________________________________
TSX AEM 1601 TSX AEM 1602
Isolation
16 channels with one common
±
10 V
±
5 V, 1-5 V
±
10 V
0-20 mA 4-20 mA
0-20 mA
±
10.2 V
10 V/4 000 pts = 2.5 mV
- 0.4 + 20.4 mA
20 mA : 4000 = 5
µ
A
U :
≥
10 Mohms I :
≅
90
Ω
Between bus and channel : (1500V AC)
Channels not isolated from each other (common
Sampling time
Specific measurement
16 channels (not possible to disable channels)
Normal mode : 15 ms/ch. or 240 ms
Filtered mode : 50 Hz : 80 ms/ch. or 1.28 s
Square root
Software defined
_______________________________________________________________________
8
General introduction
1
Safety
The inputs are protected against industrial interference and are electronically isolated from each other and from the internal PLC voltages. A grounding circuit uncouples the common reference for the channels.
Ease of use
The analog module requires no external power supply. Since the configuration is entirely defined by software and the functions are preprogrammed, the module is particularly easy to use.
Operating convenience
The modules and the terminal blocks can be inserted and removed while equipment is switched on. The PLC processor is continuously informed of the operating status of the module, and the user program can access all data for processing, if required.
______________________________________________________________________
1.2-2 External appearance
The TSX AEM 1601 and 1602 modules are of single height format. They should be inserted into racks equipped with a complete I/O bus.
The modules comprise :
➀
A metal case which protects the electronic circuits and provides protection against radiated interference.
2
OK
ERR
3
➁
A front panel.
4
➂
A connector for a terminal block.
➃
A removable terminal block with 32 screw terminals.
1
_______________________________________________________________________
9
_______________________________________________________________________
The front panel comprises :
➄
2 indicator lamps which show the operating status of the module.
➅
1 indicator lamp which shows an application fault on any of the channels.
5
6
OK
ERR
TSX AEM
F
OK
ERR
➆
A transparent label holder and an identification label.
7
The rear panel of the module is fitted with coded locating devices :
• The standard factory coded locating devices prevent the risk of error when inserting or changing a module.
• An optional user-coded locating device.
_______________________________________________________________________
1 0
X
Operation 2
Section 2
2.1
Hardware structure 12
_________________________________________________________________________________________
2.2
Software structure 13
2.2-1 General
2.2-2 Data exchanges with the PLC processor
2.2-3 Measurement processing
2.2-4 Measurement sampling
13
13
14
14
________________________________________________________________________________________
2.3
Types of processing available 15
2.3-1 Monitoring for range overshoot
2.3-2 Calculating the square root (for flow rate measurements)
2.3-3 Measurement scaling
2.3-4 Sensor break test
15
18
19
20
_______________________________________________________________________________________
2.4
Dialogue with the PLC 21
2.4-1 General
2.4-2 Discrete interface
2.4-3 Register interface
2.4-4 Message interface
2.4-5 Extended register interface
21
21
22
23
23
________________________________________________________________________________________
2.5
Module operating modes 24
2.5-1 Description
2.5-2 Controlling the operating modes
2.5-3 Behaviour of the module in the event of a power break
2.5-4 Effect of faults on the operating modes
24
25
25
25
______________________________________________________________________
11
______________________________________________________________________
2.1
Hardware structure
The following diagram shows the hardware structure of TSX AEM 160x modules :
V0
V1
➤
➤
Prot.
+
Filter
V15 ➤
➤
Multiplexer
➤
MUX
➤
Amplification A/D C
// to serial converter
A
Processing
Data exchange
A/D
➤ ➤
REF
➤
Serial
Link
Management
➤
Micro
➤ controller
EEPROM
Serial to // converter
Isolation barrier
Power supply
➤
➤
Bus
Interface
➤
➤
B
U
S
Input stage : This comprises an overvoltage protection circuit and a filter on each channel to eliminate high frequency noise. The TSX AEM 1602 module has built-in current reading resistors.
Multiplexer : The solid state multiplexer sequentially switches the channels to be converted. The number of operations is unlimited.
Amplifier : Amplifies the input voltages for the two ranges :
±
10V and
±
5 V on the
TSX AEM 1601, and the 0-20 mA range of the TSX AEM 1602.
The 1-5 V and 4-20 mA ranges are derived from the
±
5 V and 0-20 mA ranges respectively.
Analog/digital converter : This double ramp converter converts the analog signal to digital values.
Isolated serial connection : The complete analog measurement circuit is at the input reference voltage and is isolated from the PLC bus. The module micro-controller manages the serial link via a serial interface circuit. The serial link is isolated by photocouplers. In the conversion section, a parallel to serial converter circuit transmits the code converted by the A/D converter, and a serial to parallel converter circuit controls the amplifier gain changes and the changes of multiplexer channel.
Processing : The micro-controller also manages the interface with the PLC, and corrects the analog measurements, based on coefficients stored in an EEPROM, as well as performing square root calculations and tests.
The bus interface carries data exchanges with the PLC processor : transmission of analog measurements, reception of the configuration, etc.
______________________________________________________________________
12
App
.Co
.Ca
.Pr
S
Operation 2
______________________________________________________________________
2.2
Software structure
2.2-1 General
The software structure of the TSX AEM 160x modules is in two parts :
• A common part, identical on all intelligent modules, which manages the data exchanges with the PLC processor
• A specific part which manages sampling (sequencing, conversion, correction of analog measurements, processing of measurements) and specific self-tests
Initial common self test
Initial specific self test
Request interpreter
Message
Standard data exchanges
Discrete register
Application processing :
.Conversion
.Calibration
.Proc. measurements
Specific software Software common to intelligent modules
_______________________________________________________________________
2.2-2 Data exchanges with the PLC processor
The software manages the standard interfaces :
• Discrete interface for transmitting fault data
• Register interface for transmitting status data
• Message interface for writing the configuration, reading the analog measurements, reading the fault bit strings, etc.
Used with TSX/PMX model 40 PLCs, the TSX AEM 16 module also has an extended register interface for transmitting analog measurements.
______________________________________________________________________
13
______________________________________________________________________
2.2-3 Measurement processing
The micro-controller performs the following processes :
• Scales the raw conversion value
• Tests for range overshoot and limits the value, if exceeded
• Tests for sensor break (except for the 0-20 mA range)
Correction coeffs.
for selected range in the EEPROM
Digital values after analog/
→
digital conversion
Scaling raw value to standard scale
±10 V
→
±10 000
±5 V
0-20 mA
1-5 V
→
0/10 000
4-20 mA
Processing sensor break
±5 V ±10 V ranges
Processing
• Test for range overshoot
• Test for sensor break limited if exceeded
±10 V
±5 V
→
±10 200
0-20 mA
1-5 V → -200
4-20 mA +10 200
Processing square root
Measurements transmitted
______________________________________________________________________________________________________
2.2-4 Measurement sampling
The cycle time of the module depends on its operating mode, defined during configuration :
- Normal mode : The duration of the conversion cycle is as follows :
T cycle
= 15 ms x 16 channels, that is 240 ms
The converter resolution is 10 bits + sign
- Filtered mode : Depending on the filtering frequency, the duration of the conversion cycle is :
T cycle
= 80 ms x 16 channels, that is 1.28 s, for filtering at 50 Hz
T cycle
= 67 ms x 16 channels, that is 1.072 s, for filtering at 60 Hz
The advantage of this mode is that the fundamental frequency and the PLC supply voltage harmonics (50 or 60 Hz) are suppressed.
The converter resolution is 12 bits + sign.
______________________________________________________________________
14
Operation 2
______________________________________________________________________
Measurement cycle
➤ Period of 240 ms (1)
C0 C1 C2 C3 C4 C5 C6 C7 C8 C9
➤
C15 C0 C1 C2 C3 C4 C5 C6 C7 C8 C9 C10
C = channel
Access to measurements from the user program
The user receives the measurements via the message interface channels and the extended register interface (only available on model 40 processors).
All the measurements provided to the user are made during the same sampling cycle
(time coherence of measurements in relation to each other).
______________________________________________________________________
2.3
Types of processing available
2.3-1 Monitoring for range overshoot
The input range defines the normal limits of operation for the sensor connected to the input.
The declaration of the input range has two principal functions :
• The setting of the error detection limits, which detect range overshoots
• Calculations for scaling
The following table gives the range numbers (to be entered during configuration) and the corresponding normal usage scales, as well as the lower range overshoot limit LL and the higher range overshoot limit HL.
_________________________________________________________________________________________
Range n
°
Scale Lower limit LL Higher limit HL
1601 0
1
±
10 V
±
5 V
1/5 V
- 10.2 V
- 5.1 V
+ 0.92
+ 10.2 V
+ 5.1 V
+ 5.08 V
1602 0 4 / 20 mA
0/20 mA
+ 3.68 mA
- 0.4 mA
+ 20.32 mA
20.4 mA
__________
(1) In normal mode
(*) This range can be used as a 4-20 mA range by placing a 250
Ω
(0.1 %) resistor in the terminal block.
The 1/5 V range is derived, by internal calculation, from the
±
5 V range. In the same way, the
4-20 mA range is derived, by calculation, from the 0-20 mA range.
______________________________________________________________________
15
______________________________________________________________________
Example : Declared range 0/20 mA
Scaled value
+ 10200
+ 10000
Normal value
- 0.4 mA
200 20 mA 20.4 mA
➤
Input current
LL
HL
3 2 1 2 4
➀
The measured value is within the declared full scale input range :
LL = 0 The module supplies the exact value between 0 and + 10 000
HL = 0
➁
The measured value is within the extended full scale range which solves problems of sensor dispersion :
LL = 0 The module supplies the exact value between -200 and 0
HL = 0 or between 10 000 and 10 200
➂
The measured value is below the LL limit (- 0.4 mA), an overshoot fault is detected and a fault data bit is transmitted to the user program :
LL = 1 The module supplies a value limited to -200
HL = 0
➃
The measured value is above the HL limit (+20.4 mA), an overshoot fault is detected and a fault data bit is transmitted to the user program :
LL = 0
HL = 1
The module supplies a value limited to +10 200
______________________________________________________________________
16
Operation 2
______________________________________________________________________
Fault detection limits
The module sets the fault detection limits according to the declared input range.
When the value of an input signal exceeds these limits, the converter saturates and the corresponding fault bits for the higher limit HL or the lower limit LL are set to 1 (section
4.3, fault bit string BDEF).
______________________________________________________________________
17
______________________________________________________________________
2.3-2 Calculating the square root (for flow rate measurements)
TSX AEM 1601/1602 modules perform square root extraction on request, using the following conventions :
• If the measured value is positive :
Square root of «Measured value» = - 100 x
• If the measured value is negative :
Square root of «Measured value» = - 100 x
The square root is extracted after standardizing the measurement.
Example of an application : flow rate measurement
Narrowing of a pipe creates a difference in pressure dp = p2-p1 related to the flow rate Q by the equation :
Q = K x 2 dp/I where K is a constant that is a function of the shape of the pipe, and l the volume of liquid.
P1
The square root extraction function thus provides a measurement proportional to a flow rate from a differential pressure sensor.
P2
______________________________________________________________________
18
Operation 2
______________________________________________________________________
2.3-3 Measurement scaling
TSX AEM 1601/1602 modules have only one measurement scaling mode : the "standard range" scaling mode.
The "standard range" scaling mode provides the user program with the measurement values expressed as a percentage of the full scale range using the following conventions :
• Unipolar range :
The measurements provided by the module are between :
0 and 10 000, that is 0 % and 100.00 % of the full scale range (0 to High Val.).
The overshoots permitted between the error detection limits HL and LL enable the digital values in the extended zone to be obtained.
Extended zone :
- 200 and + 10 200 without square root
- 1 414 (- 200 x 100) and + 10 099
( 10200 x 100) with square root.
Measurement value
%
102.00
100.00
LL
0
-2.00
Analog input value
High
Val.
HL
➤
• Bipolar range :
The measurements provided by the module are between :
- 10 000 and + 10 000, that is - 100.00 % of the negative input range and
+ 100.00 % of the positive input range
(Low val./ High val.).
Extended zone :
- 10 200 + 10 200
(without square root)
- 10 099 + 10 099
(with square root)
Measurement value
%
102.00
100.00
LL
Low
Val.
Analog input value
High
Val.
HL
➤
- 100.00
- 102.00
_____________
(*) The curves represented by lighter lines show the square root function.
______________________________________________________________________
19
______________________________________________________________________
2.3-4 Sensor break test
This test is designed to check the continuity of the external circuit. In other words to check the sensor and the connection between it and the input terminals.
If the wiring (line broken) or the sensor is defective, the module detects a fault.
Conditions for performing the test
TSX AEM 1602 module :
For the 4-20 mA input range, if the current measured at an input is 0 mA +/- 80 mA, the module declares a sensor break on this input.
The sensor break test is not available on the 0-20 mA ranges.
The test is continuously performed on all the configured inputs in the 4-20 mA range.
TSX AEM 1601 module :
On the
±
5 V and
±
10 V ranges, a device measures the impedance of the channel sensor
(i + 8) while it samples the channel (i).
The impedance of the connected sensor must be
≤
1 K
Ω
. A sensor break is detected if the sensor impedance is > 100 K
Ω
.
The test is optional for the
±
5 V and
±
10 V ranges. It is only performed if the 4-bit byte
RUP (i) in the configuration table is set to 1 (cf. § 3.2.2).
The test is continuously performed on all the configured inputs in the 1-5 V range.
When a fault is detected, the module :
• Sets the "sensor break fault" bit (fault bit string BDEF) for the corresponding channel to 1.
• Sets the "application fault" bit in the complementary status register word to 1.
• Illuminates the ERR indicator lamp on the front panel of the module.
• Sets the "channel fault" bit for the corresponding channel to 1.
Using the "channel fault" bit prevents measurements being validated when a fault is detected.
The 1-5 V range
The actions mentioned above are inhibited. If the voltage measured is 0
±
20 mV, the sensor break bit is set to 1.
______________________________________________________________________
20
Operation 2
______________________________________________________________________
2.4
Dialogue with the PLC
2.4-1 General
There are 4 types of data exchange with the PLC processor via the complete I/O bus :
• Discrete interface, with address Ixy,i
• Register interface, with address I/OWxy,i
• Message interface
• Extended register interface x = rack number y = slot number in the rack i = see later in this document
For each of these data exchanges there are corresponding data objects which can be utilized by the user program. The extended register interface is only available on model 40 processors.
_____________________________________________________________________
2.4-2 Discrete interface
TSX AEM 160x modules have a 16 input discrete interface.
The user can access 16 bit objects as well as the fault bit via the program.
Data exchanges are systematically performed during each task cycle in which the module is configured.
The interface indicates the fault status for each channel. Status 1 indicates that the corresponding channel has an application type fault (sensor breaks, range overshoot) and that the application program should ignore the measurement.
Ixy,i
F C 8 4 O
➛
Fault channel 0
➛ Fault channel 15
______________________________________________________________________
21
______________________________________________________________________
2.4-3 Register interface
TSX AEM 1601-1602 modules have eight input word registers and eight output word registers. Data exchanges are performed systematically during each PLC cycle.
8 input register words :
Standard status word IWxy,0
IWxy,1
IWxy,2
IWxy,3
IWxy,4
IWxy,5
IWxy,6
IWxy,7
Complementary status word
2 registers are used : IWxy,0 and IWxy,2. They provide 2 status words which give the operating status (operating modes, module fault, etc).
8 output register words :
OWxy,0
OWxy,1
OWxy,2
OWxy,3
OWxy,4
OWxy,5
OWxy,6
OWxy,7
Standard control word
.
1 single register is used : OWxy,0 which is the module control word (controls RUN/STOP, etc).
______________________________________________________________________
22
Operation 2
______________________________________________________________________
2.4-4 Message interface
The message interface is used to transfer data tables between the module and the PLC processor. The transfer is programmed via a CPL text block and is initiated by the user program.
This type of dialogue is used for writing and re-reading the configuration, and for reading measurements and associated faults.
Data specific to each transfer is organized into internal words (Wi) or constant words,
CWi, (for transmission only).
A more detailed description of programming using the message interface is given in the sections relating to each exchange :
• Configuration (section 3)
• Reading measurements (section 4.1)
• Processing faults (section 4.3)
• Additional requests (section 4.3)
______________________________________________________________________
2.4-5 Extended register interface
The extended register interface is used to transfer the 16 module measurements to the
PLC processor. The transfer is initiated by the user program by executing the READEXT instruction.
Same as discrete interface Ixy,0..F
Wi
Wi + 1
Wi + 2
Wi + 3
Wi + 4
Wi + 5
Wi + 6
Wi + 7
Wi + 8
Wi + 9
Wi + 10
Wi + 11
Wi + 12
Wi + 13
Wi + 14
Wi + 15
Wi + 16
Status of channels
Measurement channel 0
Measurement channel 1
Measurement channel 2
Measurement channel 3
Measurement channel 4
Measurement channel 5
Measurement channel 6
Measurement channel 7
Measurement channel 8
Measurement channel 9
Measurement channel 10
Measurement channel 11
Measurement channel 12
Measurement channel 13
Measurement channel 14
Measurement channel 15
Note
23
______________________________________________________________________
2.5
Module operating modes
2.5-1 Description
The following flow chart illustrates the operating modes of TSX AEM 160x modules
Initial self-test
1
6
➤ RUN module
2
STOP module
5
Awaiting configuration
4
➤ 3
The module runs an initial self-test procedure 1 on power up, initialization request or following a power break.
If no fault is detected during this procedure, the module then operates in RUN or STOP mode (depending on the value of the standard control word) in the default configuration.
To use the module for an application, it must be configured. To do this the user must program the following :
• Place the module in STOP mode ➂ , if it is not already in this mode
• Transmit the configuration via the message interface ➄
• Set the module to RUN mode ➅ .
If the configuration received is faulty or incomplete the module waits until a valid configuration is received ➄ .
The use of the configuration loading function blocks in the TXT L PL7 PCL and
TXT L PL7 PMS programs (which can only run on V4 generation processors) simplifies the programmming of loading operations for the user.
Once configured and running (RUN module and RUN channel), the module is ready to sample measurements.
Standard discrete data, register data and extended register data are exchanged during each task cycle in which the module is configured.
______________________________________________________________________
24
Operation 2
______________________________________________________________________
2.5-2 Controlling the operating modes
The user has access to a control register word which is used to force the module into the required operating mode.
The status register words give information on the operating mode of the module :
• Initial self-test
• RUN/STOP module
• Awaiting configuration ➃
• Operating in default configuration
_____________________________________________________________________
2.5-3 Behaviour of the module in the event of a power break
The TSX AEM 1601/1602 modules do not have a protected memory. All data is lost
(including the configuration and the threshold values), when they are disconnected from the power supply provided by the PLC.
The module must therefore be reconfigured and the threshold values reprogrammed in the event of:
• A cold restart (SY0 = 1),
• A hot restart, when the power supply reserve has been exhausted
• When the module is installed in the PLC.
All these types of restart are described in the PL7-3, TXT DR PL7-3 V4E and
TSX D 22 002E reference manuals.
Complementary status word bit (IWxy,2,D) indicates when the module is operating in the default configuration. This bit can thus be used to detect the loss of the configuration, and to request that the configuration specific to the application is transferred again (see example in section 3).
_____________________________________________________________________
2.5-4 Effect of faults on the operating modes
When an acquisition or conversion fault is detected on the module, it changes to STOP mode, and remains in this mode until the fault disappears.
When an application (sensor or wiring) fault is detected, the module continues to operate in RUN mode.
______________________________________________________________________
25
______________________________________________________________________
______________________________________________________________________
26
X
Configuration 3
Section 3
Page
3.1
Principle
3.1-1 General
3.1-2 Configuration data
3.1-3 Default configuration
3.1-4 Transmission of configuration data
3.1-5 Bits associated with configuration
________________________________________________________________________________________
3.2
Parameters 30
3.2-1 Operating mode
3.2-2 Configuring the channels
3.2-3 Example
30
30
31
________________________________________________________________________________________
3.3
Default configuration 32
28
28
28
28
29
29
________________________________________________________________________________________
3.4
Loading the configuration 33
3.4-1 Entering data
3.4-2 Transferring the configuration to the module
3.4-3 Checking the configuration
33
33
34
________________________________________________________________________________________
3.5
Configuration example 35
3.5-1 Coding
3.5-2 Programming (TSX 47-30/67/87)
35
35
_________________________________________________________________________________________
3.6
Setup software 37
___________________________________________________________________________
27
___________________________________________________________________________
3.1
Principle
3.1-1 General
TSX 160x modules require configuration data to adapt them to a given application. This data defines the operating mode of the module and of each of its channels. Selection of the most suitable configuration simplifies the programming required to make use of the measurements provided by the module.
Configuring a module comprises :
• Defining the operating characteristics of the module
• Coding these characteristics, in hexadecimal codes or decimal values
• Transferring the codes and values to the module via a program
Reminder
The "traditional" method of setting up TSX AEM 160 x modules, the only means of set up available for V3 PLCs (TSX P43-30/67-20/87-30), is covered in sub-sections
3.1 to 3.5
The recommended set up method for model 40 PLCs and TXT L PL7 PCL/PMS software is given in sub-section 3.6.
_____________________________________________________________________________
3.1-2 Configuration data
Configuration data comprises :
• The operating mode
• The type of processing for each channel :
- Square root processing
- Range
- Sensor break processing
(on TSX AEM 1601 module only)
Zone 1
Zone 2
Zone 3
Zone i + 2
Zone 17
Operating mode
Configuration channel 0
Configuration channel 1
Configuration channel i
Configuration channel 15
Configuration data should be coded in a word table located in the W (internal words) zone via a program or in the CW (constant words) zone.
______________________________________________________________________
3.1-3 Default configuration
TSX AEM 1601/1602 modules have a default configuration which enables them to operate immediately they are switched on.
The main function of the default configuration is to test the wiring. It is described in detail in section 3.3.
The default configuration is replaced by the user configuration as soon as it is transmitted by the user program.
___________________________________________________________________________
28
Configuration 3
___________________________________________________________________________
3.1-4 Transmission of configuration data
Once the configuration data has been coded and stored, it must be transmitted to the module.
The configuration data is transmitted from the PLC memory to the module memory via a program (using a CPL text block).
The following procedure must be used to transmit the configuration :
• Set the module to «STOP» mode,
• Wait until the module has stopped,
• Send the configuration via a CPL text block,
• Set the module to «RUN» mode.
Module power up
RUN module with default configuration
STOP module
If module is stopped send user configuration
Note : The configuration may be lost if there is a power break or if the module is removed from its slot. If this happens, the configuration must be sent again.
Set module to RUN mode
_____________________________________________________________________
3.1-5 Bits associated with configuration
Two bits, in the standard and complementary status words (and which can be accessed via a program) are associated with module configuration :
IWxy,0,B : At state 1 this bit indicates that the module is awaiting configuration (in the event of an invalid configuration being received).
IWxy,2,D : At state 1 this bit indicates that the module is operating with the default configuration.
___________________________________________________________________________
29
___________________________________________________________________________
3.2
Parameters
3.2-1 Operating mode
The operating mode is coded in a word
(zone 1) :
The third 4-bit group indicates the measurement sampling rate :
• Code 0 : Normal mode - 15 ms/channel with a resolution of 10 bits + sign.
Zone 1
Zone 2
Zone 3
Zone i
Zone 17
0 ACQ A
• Code 1 : Filtered mode at 50 Hz - 80 ms/channel with a resolution of 12 bits + sign.
sampling rate normal/filtered (0/1-2)
• Code 2 : Filtered mode at 60 Hz - 67 ms/channel with a resolution of 12 bits + sign.
_____________________________________________________________________
3.2-2 Configuring the channels
The configuration of a channel (zone 2 to zone 17) is coded in a word comprising :
• The channel number (hexadecimal code)
• Confirmation of sensor break processing (TSX AEM 1601 only)
• The selected range
• Confirmation of square root processing
Channel number
This number from 0 to F identifies the channel to which the configuration applies.
X
Sensor break processing
Sensor break processing is coded in the 2 nd 4 bits, and only applies to the TSX AEM 1601 module when the selected range is
±
10 V or
±
5 V.
X
`
If the selected range is 1-5 V this 4-bit group is ignored.
This 4-bit group must be set to 0 for the TSX AEM 1602.
sensor break processing (0/1)
• 0 no sensor break processing on the
±
10 V and
±
5 V ranges
• 1 sensor break processing
___________________________________________________________________________
30
Configuration 3
___________________________________________________________________________
Input range
The input range is coded on the third 4-bit group :
0
1
2
TSX AEM 1601 TSX AEM 1602
±
10 V
±
5 V
1-5 V
4-20 mA
0-20 mA prohibited
X
Input range number (0 to 2)
Square root processing
Square root processing is coded on the fourth 4-bit group :
• 0 = no square root
• 1 = square root
(See section 2.3-2)
X
Square root processing (0/1)
______________________________________________________________________
3.2-3 Example
To configure a TSX AEM 1601 module as follows :
• Filtered sampling speed at 50 Hz
• Channels 0 to 6 in
±
10V range with sensor break test
• Square root processing on channels 2 and 3
• Channels 7 to 11 in
±
5 V range with no sensor break test
• Channels 12 and 13 in 1-5 V range
• Channels 14 and 15 not used
The coding is :
CW 0 = H'01A0'
CW 1 = H'0010'
CW 2 = H'0011'
CW 3 = H'1012'
CW 4 = H'1013'
CW 5 = H'0014'
CW 6 = H'0015'
CW 7 = H'0016'
CW 8 = H'0107'
CW 9 = H'0108'
CW 10 = H'0109'
CW 11 = H'010A'
CW 12 = H'010B'
CW 13 = H'020C'
CW 14 = H'020D'
CW 15 = H'000E'
CW 16 = H'000F'
___________________________________________________________________________
31
___________________________________________________________________________
3.3
Default configuration
The module has a default configuration which is mainly used to check for correct operation and correct connection.
The default configuration is operational as soon as the module is powered up.
Complementary status word bit IWxy,2,D indicates whether the module is operating with this configuration :
Zone 1 0 0 A 0
IWxy,2,D = 1
→
default configuration
Zone 2 0 0 0 0
• Zone 1, operating mode :
0 : Normal sampling mode
15 ms/channel
Zone 3
Zone 4
Zone 5
0
0
0
0
0
0
0
0
0
1
2
3
• Zones 2 to 17 : Each channel is
• configured identically :
±
10 V range for the TSX AEM 1601
4-20 mA for the TSX AEM 1602
• No sensor break processing
• No square root processing
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
0
0
0
0
0
0
0
0
0
0
0
0
A
B
8
9
6
7
4
5
C
D
E
F
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
If there is a power break or the module has been removed and replaced, the configuration is lost and is replaced by the default configuration.
If the default configuration is acceptable for a channel, there is no need to retransmit the configuration.
___________________________________________________________________________
32
Configuration 3
___________________________________________________________________________
3.4
Loading the configuration
3.4-1 Entering data
When the module configuration data has been defined and the corresponding codes determined, the codes must be stored in the PLC memory before they can be transferred to the module.
This can be performed in the W zone, but it is preferable to use the CW zone.
This screen shows an example of a configuration.
Hexadecimal codes are preceded by the letter H.
2/ 5/ 86 0 :0 CNST
CW NB CONFIGURED : 128
SURVEILLANCE CUVES
CONSTANT VALUE
CW0 = H'01A0'
MNEMONIC
CW1
CW2
CW3
CW4
CW5
CW6
CW7
CW8
CW9
CW10
CW11
CW12
CW13
CW14
CW15
CW16
= H'0010'
= H'0011'
= H'1012'
= H'1013'
= H'0014'
= H'0015'
= H'0016'
= H'0107'
= H'0108'
= H'0109'
= H'010A'
= H'010B'
= H'020C'
= H'020D'
= H'000E'
= H'000F'
CONSTANT VALUE
DISPLAY CONSTANTS
MNEMONIC
CW16 = H'000F'
CWi BOT MODIF CDW EVEN CDW 0DD
______________________________________________________________________
3.4-2 Transferring the configuration to the module
When the configuration data has been stored in the PLC memory, it must be transferred to the module memory. For this, the user must program a transmission reception text block.
Module configuration in PLC processor memory
TxT
CPL
Module memory
Characteristics of a text block
TXT0
R D
S
O
I
CPL
T,M : 0000H
LOCAL
T,C : 0
T,V : 0
CW0
0
T,L : 34
T,S : ?
E
Wi
Wi + 1
Wi + 2
0 0 A 0
0 0 0 C
0 0 1 1
Wi + 16
Transmission table
33
___________________________________________________________________________
• TXTi,M : H’ . . 63' The configuration concerns the module system
Slot N
°
Rack N
°
• TXTi,C : H’0040'
• TXTi,L :
Request code indicating to the module that configuration data is to be sent.
Length of the transmission table. This corresponds to the number of bytes in the table containing the configuration data : 34 bytes.
The confirmation report, TXTi,V, sent back by the module can be used after the data exchange to check that the data has been transmitted correctly. It is H’FE’ if the data exchange is correct, and H’FD’ if not.
Programming the transfer
The transfer should be programmed in the following way :
• Set the module to «STOP» by setting control register bit OWxy,0,C to 0.
• Check that the module has stopped by testing that status word bit IWxy,0,C is at 0.
• Then transfer the configuration. To do this, generate a rising edge on the S input of the text block.
• To check that the transfer has been successful :
- Check that TXTi,E is at 0,
- Check that TXTi,V is H’FE’.
• If the configuration has been successfully received, reset the module to RUN mode by setting the control register word bit
OWxy,0,C to 1.
Bit IWxy,0,C should then change to 1.
1
2
3
Module stopped
Module running
STOP module
Transfer configuration
Configuration received
RUN module
_____________________________________________________________________________
3.4-3 Checking the configuration
The configuration is not accepted by the module if :
• The length of the configuration is incorrect (L
≠
34).
• The syntax is incorrect (code not defined).
• The selections made in the configuration are incompatible.
• The module is in RUN mode.
___________________________________________________________________________
34
Configuration 3
___________________________________________________________________________
Transmission of an incorrect configuration
Transmission of an incorrect configuration causes the status word bit IWxy,0,B «awaiting configuration» to change to 1. The module then awaits a new configuration and the previous correct configuration remains in its memory.
_____________________________________________________________________
3.5
Configuration example
A user wishes to configure a TSX AEM 1601 module following the example given in section 3.2-3.
______________________________________________________________________
3.5-1 Coding
The configuration table is given in section 3.2-3.
Storing the data : Select configuration mode on the terminal and enter the codes one by one into the constant words, CW.
______________________________________________________________________
3.5-2 Programming
The following program is written in Ladder Language. It could also be written in Literal
Language.
The CPL text block is configured first.
2/ 5/ 86 0 :0 CONF
NUMBER OF TEXT BLOCS N/MAX : 2 /64
TELEMECANIQUE
Local : The module is located in the PLC which contains the program.
N0NET/LOCAL TYPE
0
1
LOCAL
LOCAL
CPL
CPL
ADDRESSING MODES ADDR
BUFFER
RECEPTION
LENGTH (byte)
DIRECT CW0 0
INDIRECT W20
Direct,CW : Data is contained in the constant words, CW.
Number of bytes in the reception table : 0.
The program comprises :
• The transfer of the parameters required for the text block (1st contact network) :
- H’563' : The module is located in slot 5 of rack 0 for the basic configuration.
- H’40' : Transmission of the configuration.
- 34 : 34 bytes must be transmitted (17 configuration words).
• The transfer of the configuration once the following conditions have been checked :
___________________________________________________________________________
35
___________________________________________________________________________
Programming the text block characteristics
IW5,0,9
SY0
(*)
H'563'
H'40'
→
TXT0,M
→
TXT0,C
34
→
TXT0,L
B10
Transferring the configuration
B11
B10 IW5,0,B IW5,0,C
IW5,2,D
R TXT0 D
S
O
I
CPL
T,M
LOCAL
T,C
T,V
CW0
0
T,L
T,S
E
IW5,0,B IW5,1,D
B30
TXT0,V = H'FE'
TXT0,V = H'FD'
B20
B30
OW5,0,C
B11
B10 = 1 : The text block parameters have been programmed.
IW5,0,B = 1 or IW5,2,D =1 : The module is either awaiting configuration, or operating with the default configuration.
IW5,0,C = 0 : The module is stopped.
When the configuration has been correctly received by the module (confirmation report
TXT,V = H'FE'), the module is returned to "RUN" mode and the measurements can be used. If there is a transmission or configuration error, the text block is reinitialized (B11).
(*) SYO : Cold restart.
___________________________________________________________________________
36
Configuration 3
___________________________________________________________________________
3.6
Setup software
Setting up TSX AEM 160x modules is simple using PL7-PCL or PL7-PMS (1) software, which provide :
• An operator guide program which enables the user to enter module configuration parameters from an X-TEL workstation (sampling mode and period, input ranges, type of sampling, etc).
For this, it presents all the parameters in the form of a table with the type, limits and definition of each parameter.
This program also provides for :
- Transfers of the parameters between the module, PLC, disk or diskette.
- Print-outs of the parameters.
- Display of parameter changes (measurement of each channel, operating modes, faults, etc).
It uses the dedicated zone technique of model 40 PLCs.
• Two optional function blocks (OFB) specific to the processing of analog measurements which have been added to the other PL7-3 function blocks :
- ANALD (2) for loading the module configuration following a power break or when a module has been replaced.
- ANADG (2) used to monitor for faults which may occur on modules while operating
(for example terminal block fault) or on applications controlled by these modules (for example sensor break). Faults detected in this way are formatted for use by the
APPLIDIAG program (under the Software Workshop) or the DIAG program (under
MINI MONITOR 37).
Restrictions
PL7-PCL software can only by used on model 40 processors, version 4.3 or above.
PL7-PMS software can only be used on PMX type processors.
(1) References
TXT L PL7 PCL, V42x, version
≥
4.6
TXT L PL7 PMS V42x, version
≥
4.6
(2) ANALD for PL7-PCL, AEMLD for PL7-PMS
ANADG for PL7-PCL, AEMDG for PL7-PMS
___________________________________________________________________________
37
___________________________________________________________________________
___________________________________________________________________________
38
X
Operation
_______________________________________________________________________
4
Section 4
4.1
Using the measurements in message mode
4.1-1 Accessing the measurements
4.1-2 Example
Page
40
40
41
__________________________________________________________________________________________
4.2
Using the measurements in extended register mode 42
4.2-1 Accessing the measurements
4.2-2 Conditions for measurements to be valid
42
43
_________________________________________________________________________________________
4.3
Additional programming information 44
4.3-1 Fault processing
4.3-2 Additional requests
4.3-3 Re-reading the configuration
44
48
48
_________________________________________________________________________________________
4.4
Summary - Setting up a configuration on a TSX PLC
49
______________________________________________________________________
3 9
______________________________________________________________________
4.1
Using the measurements in message mode
This operating mode is only available to V3 TSX PLCs (TSX P47-30/67-20/87-30).
____________________________________________________________________
4.1-1 Accessing the measurements
In message mode the measurements are transmitted in 16 internal words (Wi) in response to the request «Read measurements».
This request is programmed using a CPL type text block in transmit/receive mode, with the following characteristics :
• Request code : TXTi,C = 1
• Address : TXTi,M = H’xy00’ (where x = Rack n
°
and y = Slot n
°
)
• Reception table : Wi[16] table of 16 words (32 bytes) containing the 16 measurements
(where Wi = channel 0 measurement, Wi+ 1 = channel 1 measurement, and so on, to Wi+ 15 = channel 15 measurement).
• It is not necessary to define a transmission table.
Confirmation reports : TXTi,V = H’81' if exchange correct, or H’FD’ if incorrect.
TXTi,S = 32 bytes if exchange correct (TXTi,E = 0).
Note :
If the module is in STOP mode, the measurements transmitted are not actual measurements, but the last measurements acquired before the module was stopped.
Conditions for validity and the digital-analog correspondence of the measurements are identical to those for accessing measurements in extended register mode (see section 4.2).
______________________________________________________________________
4 0
Operation
4
______________________________________________________________________
4.1-2 Example
In this example, a CPL type text block with direct addressing is used.
2/ 5/ 86 0 :0 CONF
NUMBER OF TEXT BLOCS N/MAX : 2 /64
N0NET/LOCAL TYPE
0
1
LOCAL
LOCAL
CPL
CPL
TELEMECANIQUE
ADDRESSING MODES ADDR
BUFFER
RECEPTION
LENGTH (byte)
DIRECT W100 0
INDIRECT W20
The measurement reception table W100[16] is defined in PL7-3 CONFIGURATION mode.
Measurements are transferred each time input I14,A changes from state 0 to state 1.
Transferring measurements in message mode
I14,A
1
H'500'
TXT0,C
TXT0,M
B0
B0
O
I
S
TXT0
CPL
______________________________________________________________________
4 1
______________________________________________________________________
4.2
Using the measurements in extended register mode
__________________________________________________________________________________________
4.2.1 Accessing the measurements
This new rapid data exchange mode is only available on model 40 processors version 4.3 and upwards. In this mode, measurements are transmitted by immediate reading of 17 internal words (Wi) :
Wi
Wi + 1
Wi + 2
Channel status
Measurement channel ø
Measurement channel 1
Wi + 15
Wi + 16
Measurement channel 14
Measurement channel 15
This data exchange mode is programmed in PL7-3, using the immediate instruction
READEXT (Ixy; Wi; Wj), where :
• Ixy
• Wi
• Wj= 17
Geographical address of the AEM module
Start of the table
Length of the table in number of words
Note
The extended register data exchange mode is only active if the module is in RUN mode. If the module is in STOP mode, the measurements transmitted are the last measurements acquired before the module was stopped.
______________________________________________________________________
4 2
Operation
4
______________________________________________________________________
4.2-2 Conditions for measurements to be valid
The digital values effectively represent the measurements expected from the analog measurements, provided the following conditions are met :
_________________________________________________________________________________________
Status Consequences
Module in «RUN» mode IWxy,0,C = 1 If the module is in STOP mode, the values read are the last values received before the
Module configured IWxy,2,D = 0 If not configured, the module takes the default configuration. The measurements
Input values are within the limits of the extended zone, with correct sensor and wiring
Wi, k = 0
(k = 0 at H'10')
Wi = destination address of the
Module operating correctly Ixy,S = 0
If the channel is faulty the measurement read is incorrect.
When this bit is at 1, the module changes to STOP.
Example :
The actual measurement for channel 1 is only used if the module is OK, configured, and if no channel fault is detected.
The module is in slot 5 in the rack. The measurement is stored in W11.
IW5,0,C
IW5,2,D W50,1 I 5,S
17
→
W1
READEXT (I5;W50;W1)
W52
→
W11
______________________________________________________________________
4 3
______________________________________________________________________
4.3
Additional programming information
The information in this section relates to the "traditional" method of setting up
TSX AEM 160x modules, which is the only method available for TSX V3 PLCs
(TSX 47-30/67-20/87-30). It is given for information only, as its use is optional.
Using TSX or PMX model 40 PLCs with PL7-PCL and PL7- PMS software means that the traditional method can be done away with completely as they provide the user with equivalent services.
The table on page 49 summarizes the differences between setting up using PL7-3 (with
TSX V3 PLCs) and that using PL7-PCL/PMS (with model 40 PLCs).
______________________________________________________________________
4.3-1 Fault processing (optional)
The user can utilize a program to accurately identify faults occurring on a TSX AEM
1601/1602 module or its external environment.
Types of faults
Faults which occur on a TSX AEM 1601/1602 module can be classified into three categories, according to their degree of gravity and their effect on the operation of the module :
• Blocking faults :
These are failures in the module processor or the interface to the bus. The module processor is halted, and no data exchange on the bus is possible.
• Module acquisition and conversion faults :
These are faults which occur on the measurement acquisition and conversion circuits in the module. The measurements are no longer valid and the module is forced to stop.
• Application faults :
These are caused by factors outside the module (range overshoot, sensor breaks, etc). They may occur on one channel only, while the other channels continue to operate correctly. The faulty channel is indicated to the user.
______________________________________________________________________
4 4
Operation
4
______________________________________________________________________
Fault detection
There are a number of methods of fault identification available to the user :
• Indicator lamps
• Fault bits
• Status words
• Fault bit string (BDEF).
Indicator lamps
Lamp
F
OK
ERR
State
On
On
Off
On
Fault
Blocking fault
No fault
Module fault or terminal block fault
Application fault on a channel
TSX AEM 1601
F
OK
ERR
Change module
Module OK
Application fault
Fault bits
__________________________________________________________________________________________
Access State Fault
Ixy,S (*) By program 1 . Module fault (blocking or acquisition
and conversion)
. Exchange fault with the PLC
. Declared code is different from code 62 or
650/651, in the I/O configuration
(*) This bit informs the PLC (I/O indicator lamp on the processor) that there is a fault on the module.
It changes to 1 as soon as a fault appears and returns to 0 when it disappears.
Status words
_________________________________________________________________________________________
Fault
General fault or its memorization. Combines IWxy,0,6 and IWxy,0,7.
Acquisition and conversion fault or its memorization.
Application fault (sensors and wiring) or its memorization.
Locking fault, module absent or incorrect code.
Terminal block fault : terminal block not locked, or absent.
______________________________________________________________________
4 5
______________________________________________________________________
Fault bit string (BDEF)
This string of 96 bits in the module can be accessed via the message interface. (Request code H'47').
________________________________________________________________________________________
Fault
Reserved bits
Terminal block fault
Analog/digital converter fault
Reserved bits
32,36,40,44,48,52,56,60 Overshoot of lower limit LL channel 0,1,2,3,4,5,6,7... 15,
33,37,41,45,49,53,57,61 Overshoot of higher limit HL channel 0,1,2,3,4,5,6,7... 15,
34,38,42,46,50,54,58,62 Sensor break fault channel 0,1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
35,39,43,47,51,55,59,63 Reserved bits
Programming without reading the fault bit string
When a fault disappears, bits IWxy,0,4 and IWxy,0,i (i = 6 or 7) remain at 1.
The fault is permanently memorized until the module is re-initialized.
Fault
IWxy,0,i
IWxy,0,4
However, the indicator lamps and the fault bit Ixy,S change state as soon as the fault disappears.
Ixy,S module indicator lamp
For this reason, bits IW,xy,0,i (i = 6 or 7) should not be used in programming.
______________________________________________________________________
4 6
Operation
4
______________________________________________________________________
Reading the fault bit string
The fault bit string is read via the text block. It is optional and its main purpose is the accurate location of faults.
The content of the bit string is described on the preceding pages.
The action of reading the fault bit string
(BDEF) acknowledges a fault detected by bits IWxy,0,4, and IWxy,0,i (i = 6 or 7), after it has disappeared, whether the reading takes place before or after the disappearance of the fault.
IWxy,0, bit 4,6 and 7 change to zero :
• When the fault disappears, if they have been acknowledged by reading the fault bits.
• When the fault bits are read after the fault has disappeared.
The message read after detection of fault n
°
1 will not contain fault n
°
2.
Fault
IWxy,0,i
IWxy,0,4
Read
BDEF
Fault 1
Fault 2
IWxy,0,i
IWxy,0,4
Read
BDEF
The user will not be informed of the second fault IWxy,0,4 and IWxy,0,i = 1, (i = 6 or 7) until the first fault has disappeared. Thus fault n
°
2 can only be acknowledged after a new reading of the fault bit string.
It is therefore necessary to sample the fault bit string continuously to detect the appearance or disappearance of new faults.
Fault 1
Fault 1
IWxy,0,i
IWxy,0,4
Read
BDEF
How the received bit string is used depends on the requirements of the user. He may simply wish to keep the bits in internal words and read them in ADJUST or DATA mode on the TSX T507 terminal. Or he may wish to store them in word tables so that the development of faults can be displayed.
______________________________________________________________________
4 7
______________________________________________________________________
4.3-2 Additional requests
In addition to loading the configuration, the PLC processor can exchange various data with the module, using the CPL text function block.
List of request codes
________________________________________________________________________________________
Request function TXTi,C TXTi,M
(hex) (hex)
TXTi,V No. of
(hex) bytes
No. of Module bytes status read
Read fault bit string
40
41
47 xy63 xy63 xy63
FE/FD
71/FD
77/FD
34
0
0
0 STOP
34 RUN/STOP
12 RUN
49
4A
F xy63 xy63 xy63
FE/FD 1 to 20
7A/FD 0
3F/FD 0
0 RUN/STOP
1 to 20 RUN/STOP
27 RUN/STOP
______________________________________________________________________
4.3-3 Re-reading the configuration
Re-reading the configuration consists of transferring the configuration data from the module memory to the PLC memory. The configuration is read as a whole.
For this, the user must program a transmit/receive text block.
Characteristics of the text block (TSX 47-30/47-40/67/87/107)
The text block should have the following characteristics :
• CPL type : to enable exchange between the user program and the module.
• Request code : TXTi,C = H’41'
• Address and channel number :
TXTi,M = H’xy63'
• It is not necessary to define a transmission table.
TXTi,L = 0
• The reception table length must be 34 bytes to be able to receive the whole configuration.
______________________________________________________________________
4 8
4.4
Summary - Setting up a configuration on TSX V3 PLCs as compared with TSX-PMX model 40 PLCs
_______________________________________________________________________________________________________________________________
Design / operation stage Compulsory V3 Configuration V4 configuration with PL7-PCL/PMS
Create configuration C PL7-3 CONSTANT mode
PL7 - PCL CONFIGURATION mode
PMS
Load configuration
Write application name
Read measurements
C
O
C
C
TXT block Request code H'40'
Channel n
Set bit OWxy,0,C to 1
°
Discrete interface Ixy,i
H'63'
TXT block Request code H'49'
Channel n
°
H'63'
TXT block Request code 1
Channel n
°
0
❵
OFB ANALD (PL7/PCL software)
AEMLD (PL7-PMS software)
READEXT instruction
C
O
PL7- PCL CONFIGURATION mode
PMS
Executed by the ANALD or AEMLD OFB
Read fault string
Read configuration
Read application name
O
O
TXT block Request code H'47'
Channel n
°
H'63'
TXT block Request code H'41'
Channel n
°
H'63'
TXT block Request code H'4A'
Channel n
°
PL7- PCL DEBUG mode
PMS
PL7- PCL CONFIGURATION mode
PMS
PL7- PCL CONFIGURATION mode
PMS
Identify the module O TXT block Request code H'0F'
Channel n
°
PL7- PCL all modes
PMS
Debug PL7-3 DATA mode
PL7- PCL DEBUG mode
PMS
______________________________________________________________________
______________________________________________________________________
5 0
X
Application example
Application example 5
Section 5
5.1
Description
Page
52
_______________________________________________________________________________________
5.2
Implementation using a V3 PLC 55
_________________________________________________________________________________________
5.3
Implementation using a V4 PLC 67
______________________________________________________________________
51
______________________________________________________________________
5.1
Description
To establish a central measurement acquisition station for :
• 16 measurements from 4-20 mA sensors
• 16 measurements from 0-10 V sensors
The following processing is necessary :
Acquisition will be at the normal rate for TSX AEM 160x modules, that is 240 ms. After checking for validity (no sensor break, measurement within valid period) the measurements are smoothed using a 1st order filter before being transferred to an external device (display unit / recording unit).
Acquisition
Validity check
Filtering
Storage
Note
This example will only deal with the processing of measurements via the programming of
TSX AEM 16 modules. The assumption is made that the module is connected on a UNI-TELWAY bus, and thus can be accessed via UNI-TE protocol requests.
32 measurements
Acquisition
➩
Checking
➩
Filtering
➩ Transfer to processing device
Measurements are obtained using 2 modules :
• A TSX AEM 1601 for the 16 0-10 V measurements.
• A TSX AEM 1602 for the 16 4-20 mA measurements.
The modules provide the CPU with both the measurement values and the data for checking their validity.
Checks are performed by the CPU using this data. If a measurement is invalid, it is replaced by the value - 2000.
______________________________________________________________________
52
Application example 5
Implementation
Hardware configuration
The hardware configuration is as follows :
Proc
7
0
2
S
U
P
1
6
0
1
A
E
M
1
6
0
2
A
E
M
3
2
9
2
D
S
T
2
1
S
C
M
Slave n° 1
Display
/
Record
UNI-TELWAY bus
➤
Configuration of the TSX AEM 160x modules
• TSX AEM 1601 : NORMAL mode
All 16 channels are configured in the same way :
- Without square root
- Range -10/+10V (of which only the 0-10 V part is used)
- Sensor break test activated
• TSX AEM 1602 : NORMAL mode
All 16 channels are set up for 4-20 mA (NB : the sensor break test is implicit in this measurement range).
It is assumed that the first 8 channels are assigned to flow rate measurements, for which the special "square root extraction" function is required.
______________________________________________________________________
53
1
6
0
2
A
E
M
1
6
0
1
A
E
M
______________________________________________________________________
Analysis
The acquisition speed is 240 ms for 16 channels, and it is usual to adopt an identical time period for processing.
Task AUX0 will be used to read measurements, and perform the checking and filtering processes as well as managing the modules.
Auxiliary task Ø period 240 ms
BUFFER
TXT
➤
➤
Checking
Subroutine
SR Ø
Filtering
Filtering is performed by a subroutine, giving improved program legibility. The storage buffer is located in W200 (32 words). The contents of the buffer will be transferred to the processing device via a text block TXT (or a function block if the processor used is a model 40).
______________________________________________________________________
54
Application example 5
5.2
Implementation using a V3 PLC
The AEM module configuration parameters are entered using PL7-3 in CONFIGURATION mode.
The PLC memory is transferred to the module memory via a text block using request code H'40".
The measurements are read using text blocks (request code 1).
Processed measurements are transferred to the device which will use them using a text block (programming for this part of the processing is provided without being explicitly stated).
Selecting the processor
Since there is a small number of modules (< 4) and little processing to be performed, a
TSX 47-30 PLC will be suitable for this type of application.
Configuring the periodic tasks (PL7-3 CONFIGURATION mode)
74F00501.TIF
______________________________________________________________________
55
______________________________________________________________________
Entering the I/O configuration for the application
1. Enter the codes for the modules used.
74F00502.TIF
2. Assign the AEM 16 modules to task AUX0.
Entering the configuration of the TSX AEM modules
This is entered using PL7-3 in CONSTANT mode. 17 words, starting from CW100, are entered for the AEM 1601 and 17 words, starting from CW200, for the AEM 1602.
74F00503.TIF
______________________________________________________________________
56
Application example 5
74F00504.TIF
Assigning the text blocks
TXT0 is assigned to loading the AEM 1601 module configuration
TXT1 is assigned to loading the AEM 1602 module configuration
TXT2 is assigned to reading measurements from the AEM 1601 module
TXT3 is assigned to reading measurements from the AEM 1602 module
TXT4 is assigned to transferring the measurement buffer to the device which will use it
74F00505.TIF
Assigning the PL7-3 variables
W100 [16] : read buffer for raw measurements from the AEM 1601 module
W120 [16] : read buffer for raw measurements from the AEM 1602 module
W200 [32] : storage buffer for processed measurements
W300 [ 7] : variables used by the filtering subroutine SR0
W250 [32] : buffer used by the filtering subroutine
CWO [32] : filtering coefficient (0 < CWi < 100)
______________________________________________________________________
57
______________________________________________________________________
B0 : validation of the acquisition
B2 : 1st acquisition indicator AEM 1601 module
B3 : 1st acquisition indicator AEM 1602 module
B4 :
B5 :
Programming the master task
<MANAGE COLD RESTART
! IF SY0 THEN SET B1
<ENABLE TASK AUX 0
! IF NOT CTRL4,R THEN START CTRL4
Programming task AUX0
<WRITE TSX AEM 1601 MODULE CONFIGURATION
!
IF NOT IW4,0,3
THEN RESET OW4,0,C
!
IF IW4,0,3.IW4,2,D
THEN H’463'->TXT0,M;H’40'->TXT0,C;34->TXT0,L;
EXCHG TXT0
!
IF NOT IW4,2,D.(B4+B1)
THEN SET OW4,0,C
!
IW4,2,D->B4
<WRITE TSX AEM 1602 MODULE CONFIGURATION
!
IF NOT IW5,0,3
THEN RESET OW5,0,C
!
IF IW5,0,3.IW5,2,D
THEN H’563'->TXT1,M;H’40'->TXT1,C;34->TXT1,L;
EXCHG TXT1
!
!
IF NOT IW5,2,D.(B5+B1)
THEN SET OW5,0,C
IW5,2,D->B5
<MEASUREMENT PROCESSING
!
<ACQUISITION REQUESTED
!
IF NOT B0
THEN RESET B2;RESET B3;JUMP L150
______________________________________________________________________
58
Application example 5
<CHECK STATUS OF TSX AEM 1601 MODULE
!
IF NOT B2+I4,S
THEN-1->O6,0[16];-2000->W200[16];JUMP L119
ELSE 0->O6,0[16]
<CHECK CHANNEL 0
!L100 :IF I4,0
THEN -2000->W200;SET O6,0;JUMP L101
<FILTER CHANNEL 0
!
IF O6,0
THEN W100->W200;0->W250;RESET O6,0
ELSE W100->DW300;W200->DW302;W250->W304;
CW0->W306;CALL SR0;W304->W250;W305->W200
<CHECK CHANNEL 1
!L101 :IF I4,1
THEN -2000->W201;SET O6,1;JUMP L102
<FILTER CHANNEL 1
!
IF O6,1
THEN W101->W201;0->W251;RESET O6,1
ELSE W101->DW300;W201->DW302;W251->W304;
CW1->W306;CALL SR0;W304->W251;W305->W201
<CHECK CHANNEL 2
!L102 :IF I4,2
THEN -2000->W202;SET O6,2;JUMP L103
<FILTER CHANNEL 2
!
IF O6,2
THEN W102->W202;0->W252;RESET O6,2
ELSE W102->DW300;W202->DW302;W252->W304;
CW2->W306;CALL SR0;W304->W252;W305->W202
<CHECK CHANNEL 3
!L103 :IF I4,3
THEN -2000->W203;SET O6,3;JUMP L104
<FILTER CHANNEL 3
!
IF O6,3
THEN W103->W203;0->W253;RESET O6,3
ELSE W103->DW300;W203->DW302;W253->W304;
CW3->W306;CALL SR0;W304->W253;W305->W203
<CHECK CHANNEL 4
!L104 :IF I4,4
THEN -2000->W204;SET O6,4;JUMP L105
______________________________________________________________________
59
______________________________________________________________________
<FILTER CHANNEL 4
!
IF O6,4
THEN W104->W204;0->W254;RESET O6,4
ELSE W104->DW300;W204->DW302;W254->W304;
CW4->W306;CALL SR0;W304->W254;W305->W204
<CHECK CHANNEL 5
!L105 :IF I4,5
THEN -2000->W205;SET O6,5;JUMP L106
<FILTER CHANNEL 5
!
IF O6,5
THEN W105->W205;0->W255;RESET O6,5
ELSE W105->DW300;W205->DW302;W255->W304;
CW5->W306;CALL SR0;W304->W255;W305->W205
<CHECK CHANNEL 6
!L106 :IF I4,6
THEN -2000->W206;SET O6,6;JUMP L107
<FILTER CHANNEL 6
!
IF O6,6
THEN W106->W206;0->W256;RESET O6,6
ELSE W106->DW300;W206->DW302;W256->W304;
CW6->W306;CALL SR0;W304->W256;W305->W206
<CHECK CHANNEL 7
!L107 :IF I4,7
THEN -2000->W207;SET O6,7;JUMP L108
<FILTER CHANNEL 7
!
IF O6,7
THEN W107->W207;0->W257;RESET O6,7
ELSE W107->DW300;W207->DW302;W257->W304;
CW7->W306;CALL SR0;W304->W257;W305->W207
<CHECK CHANNEL 8
!L108 :IF I4,8
THEN -2000->W208;SET O6,8;JUMP L109
<FILTER CHANNEL 8
!
IF O6,8
THEN W108->W208;0->W258;RESET O6,8
ELSE W108->DW300;W208->DW302;W258->W304;
CW8->W306;CALL SR0;W304->W258;W305->W208
<CHECK CHANNEL 9
!L109 :IF I4,9
THEN -2000->W209;SET O6,9;JUMP L110
______________________________________________________________________
60
Application example 5
<FILTER CHANNEL 9
!
IF O6,9
THEN W109->W209;0->W259;RESET O6,9
ELSE W109->DW300;W209->DW302;W259->W304;
CW9->W306;CALL SR0;W304->W259;W305->W209
<CHECK CHANNEL 10
!L110 :IF I4,A THEN -2000->W210;SET O6,A;JUMP L111
<FILTER CHANNEL 10
!
IF O6,A
THEN W110->W210;0->W260;RESET O6,A
ELSE W110->DW300;W210->DW302;W210->W304;
CW10->W306;CALL SR0;W304->W260;W305->W210
<CHECK CHANNEL 11
!L111 :IF I4,B
THEN -2000->W211;SET O6,B;JUMP L112
<FILTER CHANNEL 11
!
IF O6,B
THEN W111->W211;0->W261;RESET O6,B
ELSE W111->DW300;W211->DW302;W211->W304;
CW11->W306;CALL SR0;W304->W261;W305->W211
<CHECK CHANNEL 12
!L112 :IF I4,C THEN -2000->W212;SET O6,C;JUMP L113
<FILTER CHANNEL 12
!
IF O6,C
THEN W112->W212;0->W262;RESET O6,C
ELSE W112->DW300;W212->DW302;W212->W304;
CW12->W306;CALL SR0;W304->W262;W305->W212
<CHECK CHANNEL 13
!L113 :IF I4,D
THEN -2000->W213;SET O6,D;JUMP L114
<FILTER CHANNEL 13
!
IF O6,D
THEN W113->W213;0->W263;RESET O6,D
ELSE W113->DW300;W213->DW302;W213->W304;
CW13->W306;CALL SR0;W304->W263;W305->W213
<CHECK CHANNEL 14
!L114 :IF I4,E
THEN -2000->W214;SET O6,E;JUMP L115
<FILTER CHANNEL 14
!
IF O6,E
THEN W114->W214;0->W264;RESET O6,E
ELSE W114->DW300;W214->DW302;W214->W304;
CW14->W306;CALL SR0;W304->W264;W305->W214
______________________________________________________________________
61
______________________________________________________________________
<CHECK CHANNEL 15
!L115 :IF I4,F
THEN -2000->W215;SET O6,F;JUMP L119
<FILTER CHANNEL 15
!
IF O6,F
THEN W115->W215;0->W265;RESET O6,F
ELSE W115->DW300;W215->DW302;W215->W304;
CW15->W306;CALL SR0;W304->W265;W305->W215
<==============================================================
!
<CHECK STATUS OF TSX AEM 1602 MODULE
!L119 :IF NOT IW5,0,C+I5,S
THEN H’FFFF’->O16,0[16];-2000->W216[16];JUMP L139
ELSE 0->O16,0[16]
<PROCESS CHANNEL 0
!L120 :
<CHECK
!
IF I5,0 THEN -2000->W216;SET O16,0;JUMP L121
<FILTER CHANNEL 0
!
IF O16,0
THEN W120->W216;0->W266;RESET O16,0
ELSE W120->DW300;W216->DW302;W266->W304;
CW16->W306;CALL SR0;W304->W266;W305->W216
<CHECK CHANNEL 1
!L121 :IF I5,1
THEN -2000->W217;SET O16,1;JUMP L122
<FILTER CHANNEL 1
!
IF O16,1
THEN W121->W217;0->W267;RESET O16,1
ELSE W121->DW300;W217->DW302;W267->W304;
CW17->W306;CALL SR0;W304->W267;W305->W217
<CHECK CHANNEL 2
!L122 :IF I5,2
THEN -2000->W218;SET O16,2;JUMP L123
<FILTER CHANNEL 2
!
IF O16,2
THEN W122->W218;0->W268;RESET O16,2
ELSE W122->DW300;W218->DW302;W268->W304;
CW18->W306;CALL SR0;W304->W268;W305->W218
<CHECK CHANNEL 3
!L123 :IF I5,3
THEN -2000->W219;SET O16,3;JUMP L124
______________________________________________________________________
62
Application example 5
<FILTER CHANNEL 3
!
IF O16,3
THEN W123->W219;0->W269;RESET O16,3
ELSE W123->DW300;W219->DW302;W269->W304;
CW19->W306;CALL SR0;W304->W269;W305->W219
<CHECK CHANNEL 4
!L124 :IF I5,4
THEN -2000->W220;SET O16,4;JUMP L125
<FILTER CHANNEL 4
!
IF O16,4
THEN W124->W220;0->W270;RESET O16,4
ELSE W124->DW300;W220->DW302;W270->W304;
CW20->W306;CALL SR0;W304->W270;W305->W220
<CHECK CHANNEL 5
!L125 :IF I5,5
THEN -2000->W221;SET O16,5;JUMP L126
<FILTER CHANNEL 5
!
IF O16,5
THEN W125->W221;0->W271;RESET O16,5
ELSE W125->DW300;W221->DW302;W271->W304;
CW21->W306;CALL SR0;W304->W271;W305->W221
<CHECK CHANNEL 6
!L126 :IF I5,6
THEN -2000->W222;SET O16,6;JUMP L127
<FILTER CHANNEL 6
!
IF O16,6
THEN W126->W222;0->W272;RESET O16,6
ELSE W126->DW300;W222->DW302;W272->W304;
CW22->W306;CALL SR0;W304->W272;W305->W222
<CHECK CHANNEL 7
!L127 :IF I5,7
THEN -2000->W223;SET O16,7;JUMP L128
<FILTER CHANNEL 7
!
IF O16,7
THEN W127->W223;0->W273;RESET O16,7
ELSE W127->DW300;W223->DW302;W273->W304;
CW23->W306;CALL SR0;W304->W273;W305->W223
<CHECK CHANNEL 8
!L128 :IF I5,8
THEN -2000->W224;SET O16,8;JUMP L129
______________________________________________________________________
63
______________________________________________________________________
<FILTER CHANNEL 8
!
IF O16,8
THEN W128->W224;0->W274;RESET O16,8
ELSE W128->DW300;W224->DW302;W274->W304;
CW24->W306;CALL SR0;W304->W274;W305->W224
<CHECK CHANNEL 9
!L129 :IF I5,9
THEN -2000->W225;SET O16,9;JUMP L130
<FILTER CHANNEL 9
!
IF O16,9
THEN W129->W225;0->W275;RESET O16,9
ELSE W129->DW300;W225->DW302;W275->W304;
CW25->W306;CALL SR0;W304->W275;W305->W225
<CHECK CHANNEL 10
!L130 :IF I5,A
THEN -2000->W226;SET O16,A;JUMP L131
<FILTER CHANNEL 10
!
IF O16,A
THEN W130->W226;0->W276;RESET O16,A
ELSE W130->DW300;W226->DW302;W276->W304;
CW26->W306;CALL SR0;W304->W276;W305->W226
<CHECK CHANNEL 11
!L131 :IF I5,B
THEN -2000->W227;SET O16,B;JUMP L132
<FILTER CHANNEL 11
!
IF O16,B
THEN W131->W227;0->W277;RESET O16,B
ELSE W131->DW300;W227->DW302;W277->W304;
CW27->W306;CALL SR0;W304->W277;W305->W227
<CHECK CHANNEL 12
!L132 :IF I5,C
THEN -2000->W228;SET O16,C;JUMP L133
<FILTER CHANNEL 12
!
IF O16,C
THEN W132->W228;0->W278;RESET O16,C
ELSE W132->DW300;W228->DW302;W278->W304;
CW28->W306;CALL SR0;W304->W278;W305->W228
<CHECK CHANNEL 13
!L133 :IF I5,D
THEN -2000->W229;SET O16,D;JUMP L134
______________________________________________________________________
64
Application example 5
<FILTER CHANNEL 13
!
IF O16,C
THEN W133->W229;0->W279;RESET O16,C
ELSE W133->DW300;W229->DW302;W278->W304;
CW29->W306;CALL SR0;W304->W279;W305->W229
<CHECK CHANNEL 14
!L134 :IF I5,E
THEN -2000->W230;SET O16,E;JUMP L135
<FILTER CHANNEL 14
!
IF O16,E
THEN W134->W230;0->W280;RESET O16,E
ELSE W134->DW300;W230->DW302;W279->W304;
CW30->W306;CALL SR0;W304->W280;W305->W230
<CHECK CHANNEL 15
!L135 :IF I5,F
THEN -2000->W231;SET O16,F;JUMP L139
<FILTER CHANNEL 15
!
IF O16,F
THEN W135->W231;0->W281;RESET O16,F
ELSE W135->DW300;W231->DW302;W281->W304;
CW31->W306;CALL SR0;W304->W281;W305->W231
<TRANSFER PROCESSED MEASUREMENTS AND DATE/TIME TO DEVICE WHICH
WILL USE THEM
!L139 :SW51->W232;SW52->W233;SW53->W234;SW54->W235;SW55->W236
!
H’765'->TXT4,M;H’7FC’->TXT4,C;74->TXT4,L;OUTPUT TXT4
<REQUEST FOR ACQUISITION OF MEASUREMENTS FROM NEXT CYCLE
!
!L140 :IF IW4,0,C.TXT2,D
THEN H’400'->TXT2,M;1->TXT2,C;EXCHG TXT2;SET B2
ELSE RESET B2
!
IF IW5,0,C.TXT3,D
THEN H’500'->TXT3,M;1->TXT3,C;EXCHG TXT3;SET B3
ELSE RESET B3
<END OF PROCESSING
!L150 :RESET B1
______________________________________________________________________
65
______________________________________________________________________
Programming SR0 in task AUX0
<FIRST ORDER FILTERING S(N)->ALPHA*S(n-1)+(1-ALPHA)*E(N)
!
<DW300 :E(N)=CURRENT RAW MEASUREMENT
!
<DW302 :S(N-1)=PREVIOUS FILTERED MEASUREMENT
!
<W304 :REMAINDER OF PREVIOUS CALCULATION
!
<W305 :S(N)=CURRENT FILTERED MEASUREMENT
!
<W306 :ALPHA FILTERING COEFFICIENT MULTIPLIED BY 100
!
<CALCULATION OF THE FILTERED MEASUREMENT
! W306*DW302+W304+DW300*(100-CW0)->DW305
! DW305 REM 100->W304;DW305/100->W305
______________________________________________________________________
66
Application example 5
5.3
Implementation using a V4 PLC
Introduction
Model 40 PLCs can be programmed using the method described in sub-section 5.2. In fact it is the only method for PLCs which are version 4.3 and below. However, from version
4.3 onwards, it is preferable to use methods specific to Model 40 PLCs in order to make use of their new features and the features of the PL7-PCL and PL7-PMS installation software :
• Division of the PLC memory into dedicated zones
• Function blocks
Differences as compared with implementation using a V3 PLC
• AEM module configuration parameters are entered using PL7-PCL or PL7-PMS installation software in CONFIGURATION mode.
• These parameters are transferred from the PLC memory to the module memory using an Optional Function Block (ANALD or AEMLD).
• The measurements are read via the Extended Register interface (READEXT instruction).
• The processed measurements are transferred to the device which will use them using an OFB (COMUW) (programming for this part of the processing is provided without being explicitly stated).
Selecting the processor
A TSX P47-420 is selected for the same reasons that a TSX P47-30 was chosen in sub-section 5.2. The built-in UNI-TELWAY port removes the necessity for the
TSX SCM 21 module.
Configuring the synchronous tasks
Identical method to that described in paragraph 5.2 :
74F00506.TIF
______________________________________________________________________
67
______________________________________________________________________
Entering the I/O configuration for the application
1. Enter the codes for the modules used.
74F00507.TIF
2. Assign the TSX AEM 16 modules to task AUX0.
Entering the configuration parameters
These are entered using the PL7-PCL or PL7-PMS set up software, in CONFIGURATION mode (refer to the TSX DM PL7 PCL V4E or TXT DM PL7 PMS V4E manuals).
Assigning the function blocks
The text blocks in paragraph 5.2 are replaced by function blocks. If the installation is performed using the PL7-PCL software :
• The ANALD0 function block is reserved for the TSX AEM 1601 module
• The ANALD1 function block is reserved for the TSX AEM 1602 module
In the same way, assuming that the UNI-TELWAY processor port is implemented using the PL7-COM (1) program, function block COMUW0 is reserved for the exchange of data with the user device.
Note
To complete the comparison with the assignment of text blocks in sub-section 5.2, it should be noted that no function block is necessary for accessing measurements provided by the modules.
(1) Communication software - complete reference : TXT L PL7 CMM V42 E.
______________________________________________________________________
68
Application example 5
Assigning the PL7-3 variables
This is similar to the process described in sub-section 5.2, but :
• The read buffer for raw measurements from the AEM 1601 module is in W99 [17].
• The read buffer for raw measurements from the AEM 1602 is in W119 [17].
This is so that the measurements occupy the same positions in the memory (W100 to W115 and W120 to W135).
The channel status word occupies positions W99 and W119.
Programming the master task
<MEMORY HOT OR COLD RESTART
!
IF SY0
THEN SET B1
<ENABLE TASK AUX 0
!
IF NOT CTRL4,R THEN START CTRL4
Programming task AUX0
<WRITE TSX AEM 1601 MODULE CONFIGURATION
!
!
IF IW4,0,3.(IW4,2,D+B1)
THEN EXEC ANALD0(0;0=>)
OPTIONAL FUNCTION BLOCKS: I/O PARAMETERS
ANALD0
0 AEM : word
0 APPLI : word
______________________________________________________________________
69
______________________________________________________________________
<WRITE TSX AEM 1602 MODULE CONFIGURATION
!
!
IF IW5,0,3.(IW5,2,D+B1)
THEN EXEC ANALD1(1;0=>)
OPTIONAL FUNCTION BLOCKS: I/O PARAMETERS
ANALD1
1 AEM : word
0 APPLI : word
<ACQUIRE MEASUREMENTS
!
IF NOT B0
THEN JUMP L150
ELSE 17->W10
!
!
IF ANALD0,READY.IW4,0,C
THEN READEXT(I4;W99;W10)
IF ANALD1,READY.IW5,0,C
THEN READEXT(I5;W199;W10)
<MEASUREMENT PROCESSING
!
<CHECK STATUS OF TSX AEM 1601 MODULE
!
IF NOT IW4,0,C+I4,S
THEN -1->O6,0[16];-2000->W200[16];JUMP L119
ELSE 0->O6,0[16]
<CHECK CHANNEL 0
!L100 :IF W99,0
THEN -2000->W200;SET O6,0;JUMP L101
<FILTER CHANNEL 0
!
IF O6,0
THEN W100->W200;0->W250;RESET O6,0
ELSE W100->DW300;W200->DW302;W250->W304;
CW0->W306;CALL SR0;W304->W250;W305->W200
<CHECK CHANNEL 1
!L101 :IF W99,1
THEN -2000->W201;SET O6,1;JUMP L102
<FILTER CHANNEL 1
!
IF O6,1
THEN W101->W201;0->W251;RESET O6,1
ELSE W101->DW300;W201->DW302;W251->W304;
CW1->W306;CALL SR0;W304->W251;W305->W201
______________________________________________________________________
70
Application example 5
<CHECK CHANNEL 2
!L102 :IF W99,2
THEN -2000->W202;SET O6,2;JUMP L103
<FILTER CHANNEL 2
!
IF O6,2
THEN W102->W202;0->W252;RESET O6,2
ELSE W102->DW300;W202->DW302;W252->W304;
CW2->W306;CALL SR0;W304->W252;W305->W202
<CHECK CHANNEL 3
!L103 :IF W99,3
THEN -2000->W203;SET O6,3;JUMP L104
<FILTER CHANNEL 3
!
IF O6,3
THEN W103->W203;0->W253;RESET O6,3
ELSE W103->DW300;W203->DW302;W253->W304;
CW3->W306;CALL SR0;W304->W253;W305->W203
<CHECK CHANNEL 4
!L104 :IF W99,4
THEN -2000->W204;SET O6,4;JUMP L105
<FILTER CHANNEL 4
!
IF O6,4
THEN W104->W204;0->W254;RESET O6,4
ELSE W104->DW300;W204->DW302;W254->W304;
CW4->W306;CALL SR0;W304->W254;W305->W204
<CHECK CHANNEL 5
!L105 :IF W99,5
THEN -2000->W205;SET O6,5;JUMP L106
<FILTER CHANNEL 5
!
IF O6,5
THEN W105->W205;0->W255;RESET O6,5
ELSE W105->DW300;W205->DW302;W255->W304;
CW5->W306;CALL SR0;W304->W255;W305->W205
<CHECK CHANNEL 6
!L106 :IF W99,6
THEN -2000->W206;SET O6,6;JUMP L107
<FILTER CHANNEL 6
!
IF O6,6
THEN W106->W206;0->W256;RESET O6,6
ELSE W106->DW300;W206->DW302;W256->W304;
CW6->W306;CALL SR0;W304->W256;W305->W206
______________________________________________________________________
71
______________________________________________________________________
<CHECK CHANNEL 7
!L107 :IF W99,7
THEN -2000->W207;SET O6,7;JUMP L108
<FILTER CHANNEL 7
!
IF O6,7
THEN W107->W207;0->W257;RESET O6,7
ELSE W107->DW300;W207->DW302;W257->W304;
CW7->W306;CALL SR0;W304->W257;W305->W207
<CHECK CHANNEL 8
!L108 :IF W99,8
THEN -2000->W208;SET O6,8;JUMP L109
<FILTER CHANNEL 8
!
IF O6,8
THEN W108->W208;0->W258;RESET O6,8
ELSE W108->DW300;W208->DW302;W258->W304;
CW8->W306;CALL SR0;W304->W258;W305->W208
<CHECK CHANNEL 9
!L109 :IF W99,9
THEN -2000->W209;SET O6,9;JUMP L110
<FILTER CHANNEL 9
!
IF O6,9
THEN W109->W209;0->W259;RESET O6,9
ELSE W109->DW300;W209->DW302;W259->W304;
CW9->W306;CALL SR0;W304->W259;W305->W209
<CHECK CHANNEL 10
!L110 :IF W99,A
THEN -2000->W210;SET O6,A;JUMP L111
<FILTER CHANNEL 10
!
IF O6,A
THEN W110->W210;0->W260;RESET O6,A
ELSE W110->DW300;W210->DW302;W210->W304;
CW10->W306;CALL SR0;W304->W260;W305->W210
<CHECK CHANNEL 11
!L111 :IF W99,B
THEN -2000->W211;SET O6,B;JUMP L112
<FILTER CHANNEL 11
!
IF O6,B
THEN W111->W211;0->W261;RESET O6,B
ELSE W111->DW300;W211->DW302;W211->W304;
CW11->W306;CALL SR0;W304->W261;W305->W211
<CHECK CHANNEL 12
!L112 :IF W99,C
THEN -2000->W212;SET O6,C;JUMP L113
______________________________________________________________________
72
Application example 5
<FILTER CHANNEL 12
!
IF O6,C
THEN W112->W212;0->W262;RESET O6,C
ELSE W112->DW300;W212->DW302;W212->W304;
CW12->W306;CALL SR0;W304->W262;W305->W212
<CHECK CHANNEL 13
!L113 :IF W99,D
THEN -2000->W213;SET O6,D;JUMP L114
<FILTER CHANNEL 13
!
IF O6,D
THEN W113->W213;0->W263;RESET O6,D
ELSE W113->DW300;W213->DW302;W213->W304;
CW13->W306;CALL SR0;W304->W263;W305->W213
<CHECK CHANNEL 14
!L114 :IF W99,E
THEN -2000->W214;SET O6,E;JUMP L115
<FILTER CHANNEL 14
!
IF O6,E
THEN W114->W214;0->W264;RESET O6,E
ELSE W114->DW300;W214->DW302;W214->W304;
CW14->W306;CALL SR0;W304->W264;W305->W214
<CHECK CHANNEL 15
!L115 :IF W99,F
THEN -2000->W215;SET O6,F;JUMP L119
<FILTER CHANNEL 15
!
IF O6,F
THEN W115->W215;0->W265;RESET O6,F
ELSE W115->DW300;W215->DW302;W215->W304;
CW15->W306;CALL SR0;W304->W265;W305->W215
<===============================================================
!
<CHECK STATUS OF TSX AEM 1602 MODULE
!L119 :IF NOT IW5,0,C+I5,S
THEN -1->O16,0[16];-2000->W216[16];JUMP L139
ELSE 0->O16,0[16]
<PROCESS CHANNEL 0
!L120 :
<CHECK
!
IF W199,0
THEN -2000->W216;SET O16,0;JUMP L121
______________________________________________________________________
73
______________________________________________________________________
<FILTER CHANNEL 0
!
IF O16,0
THEN W120->W216;0->W266;RESET O16,0
ELSE W120->DW300;W216->DW302;W266->W304;
CW16->W306;CALL SR0;W304->W266;W305->W216
<CHECK CHANNEL 1
!L121 :IF W199,1
THEN -2000->W217;SET O16,1;JUMP L122
<FILTER CHANNEL 1
!
IF O16,1
THEN W121->W217;0->W267;RESET O16,1
ELSE W121->DW300;W217->DW302;W267->W304;
CW17->W306;CALL SR0;W304->W267;W305->W217
<CHECK CHANNEL 2
!L122 :IF W199,2
THEN -2000->W218;SET O16,2;JUMP L123
<FILTER CHANNEL 2
!
IF O16,2
THEN W122->W218;0->W268;RESET O16,2
ELSE W122->DW300;W218->DW302;W268->W304;
CW18->W306;CALL SR0;W304->W268;W305->W218
<CHECK CHANNEL 3
!L123 :IF W199,3
THEN -2000->W219;SET O16,3;JUMP L124
<FILTER CHANNEL 3
!
IF O16,3
THEN W123->W219;0->W269;RESET O16,3
ELSE W123->DW300;W219->DW302;W269->W304;
CW19->W306;CALL SR0;W304->W269;W305->W219
<CHECK CHANNEL 4
!L124 :IF W199,4
THEN -2000->W220;SET O16,4;JUMP L125
<FILTER CHANNEL 4
!
IF O16,4
THEN W124->W220;0->W270;RESET O16,4
ELSE W124->DW300;W220->DW302;W270->W304;
CW20->W306;CALL SR0;W304->W270;W305->W220
<CHECK CHANNEL 5
!L125 :IF W199,5
THEN -2000->W221;SET O16,5;JUMP L126
______________________________________________________________________
74
Application example 5
<FILTER CHANNEL 5
!
IF O16,5
THEN W125->W221;0->W271;RESET O16,5
ELSE W125->DW300;W221->DW302;W271->W304;
CW21->W306;CALL SR0;W304->W271;W305->W221
<CHECK CHANNEL 6
!L126 :IF W199,6 THEN -2000->W222;SET O16,6;JUMP L127
<FILTER CHANNEL 6
!
IF O16,6
THEN W126->W222;0->W272;RESET O16,6
ELSE W126->DW300;W222->DW302;W272->W304;
CW22->W306;CALL SR0;W304->W272;W305->W222
<CHECK CHANNEL 7
!L127 :IF W199,7
THEN -2000->W223;SET O16,7;JUMP L128
<FILTER CHANNEL 7
!
IF O16,7
THEN W127->W223;0->W273;RESET O16,7
ELSE W127->DW300;W223->DW302;W273->W304;
CW23->W306;CALL SR0;W304->W273;W305->W223
<CHECK CHANNEL 8
!L128 :IF W199,8
THEN -2000->W224;SET O16,8;JUMP L129
<FILTER CHANNEL 8
!
IF O16,8
THEN W128->W224;0->W274;RESET O16,8
ELSE W128->DW300;W224->DW302;W274->W304;
CW24->W306;CALL SR0;W304->W274;W305->W224
<CHECK CHANNEL 9
!L129 :IF W199,9
THEN -2000->W225;SET O16,9;JUMP L130
<FILTER CHANNEL 9
!
IF O16,9
THEN W129->W225;0->W275;RESET O16,9
ELSE W129->DW300;W225->DW302;W275->W304;
CW25->W306;CALL SR0;W304->W275;W305->W225
<CHECK CHANNEL 10
!L130 :IF W199,A THEN -2000->W226;SET O16,A;JUMP L131
<FILTER CHANNEL 10
!
IF O16,A
THEN W130->W226;0->W276;RESET O16,A
ELSE W130->DW300;W226->DW302;W276->W304;
CW26->W306;CALL SR0;W304->W276;W305->W226
______________________________________________________________________
75
______________________________________________________________________
<CHECK CHANNEL 11
!L131 :IF W199,B
THEN -2000->W227;SET O16,B;JUMP L132
<FILTER CHANNEL 11
!
IF O16,B
THEN W131->W227;0->W277;RESET O16,B
ELSE W131->DW300;W227->DW302;W277->W304;
CW27->W306;CALL SR0;W304->W277;W305->W227
<CHECK CHANNEL 12
!L132 :IF W199,C
THEN -2000->W228;SET O16,C;JUMP L133
<FILTER CHANNEL 12
!
IF O16,C
THEN W132->W228;0->W278;RESET O16,C
ELSE W132->DW300;W228->DW302;W278->W304;
CW28->W306;CALL SR0;W304->W278;W305->W228
<CHECK CHANNEL 13
!L133 :IF W199,D
THEN -2000->W229;SET O16,D;JUMP L134
<FILTER CHANNEL 13
!
IF O16,C
THEN W133->W229;0->W279;RESET O16,C
ELSE W133->DW300;W229->DW302;W278->W304;
CW29->W306;CALL SR0;W304->W279;W305->W229
<CHECK CHANNEL 14
!L134 :IF W199,E
THEN -2000->W230;SET O16,E;JUMP L135
<FILTER CHANNEL 14
!
IF O16,E
THEN W134->W230;0->W280;RESET O16,E
ELSE W134->DW300;W230->DW302;W279->W304;
CW30->W306;CALL SR0;W304->W280;W305->W230
<CHECK CHANNEL 15
!L135 :IF W199,F
THEN -2000->W231;SET O16,F;JUMP L139
<FILTER CHANNEL 15
!
IF O16,F
THEN W135->W231;0->W281;RESET O16,F
ELSE W135->DW300;W231->DW302;W281->W304;
CW31->W306;CALL SR0;W304->W281;W305->W231
______________________________________________________________________
76
Application example 5
<TRANSFER PROCESSED MEASUREMENTS AND DATE/TIME TO DEVICE WHICH
WILL USE THEM
!L139 :SW51->W232;SW52->W233;SW53->W234;SW54->W235;SW55->W236
! 74->W0;1->COMUW0,SLAVE;EXEC COMUW0(;0;;;;;;;;;;;;;;;;;=>)
OPTIONAL FUNCTION BLOCKS: I/O PARAMETERS
0
RESET
COM
:
COMUW0 bit
: word
FORMAT : pt_w
P0
P1
:
: pt_w pt_w
P2
P3
: pt_w
: pt_w
P4
P5
P6
P7
P8
P9
:
:
:
:
:
: pt_w pt_w pt_w pt_w pt_w pt_w
P10
P11
P12
P13
P14
P15
: pt_w
: pt_w
: pt_w
: pt_w
: pt_w
: pt_w
<END OF PROCESSING
!L150 :RESET B1
Note
For further information on the operation of ANALDi function blocks, refer to manual
TXT DM PL7-PCL V4E.
For further information on the operation of COMUWi function blocks, refer to manual
TXT DM PL7-CMM V4E (II/IE
≥
02A02).
______________________________________________________________________
77
______________________________________________________________________
Programming SR0 in task AUX0
<FIRST ORDER FILTERING S(N)->ALPHA*S(n-1)+(1-ALPHA)*E(N)
!
<DW300 :E(N)=CURRENT RAW MEASUREMENT
!
<DW302 :S(N-1)=PREVIOUS FILTERED MEASUREMENT
!
<W304 :REMAINDER OF PREVIOUS CALCULATION
!
<W305 :S(N)=CURRENT FILTERED MEASUREMENT
!
<W306 :ALPHA FILTERING COEFFICIENT MULTIPLIED BY 100
!
<CALCULATION OF THE FILTERED MEASUREMENT
!
W306*DW302+W304+DW300*(100-CW0)->DW305
!
DW305 REM 100->W304;DW305/100->W305
______________________________________________________________________
78
X
Hardware installation
________________________________________________________________________________________
6
Section 6
6.1
Locating devices
Page
80
_________________________________________________________________________________________
6.2
Identification 80
_________________________________________________________________________________________
6.3
Connection 81
6.3-1 Description
6.3-2 Connection principle
6.3-3 Referencing the channel inputs and sensors
81
81
82
_________________________________________________________________________________________
6.4
Description of the installation sheet 83
__________________________________________________________________________________________
6.5
Recalibration 84
_____________________________________________________________________
79
_____________________________________________________________________
6.1
Locating devices
_________________________________________________________________________________________
Mechanical
3 digit decimal code defined by
3 female locating devices
TSX AEM 1601 : 650
TSX AEM 1602 : 651
Software
Entered when configuring the I/O TSX AEM 1601 : 650
TSX AEM 1602 : 651
Reminder
TSX AEM 160x modules can only be installed in racks with a complete bus
(TSX RKN...) and are only compatible with V3 (TSX P47-30/67-20/87-30) or model 40 processors.
________________________________________________________________________________________
6.2
Identification
➀
Snap-on characters
Used to identify the location of the module and the terminal block.
➁
Module label
Used to identify :
• The module type
• Assignment of the indicator lamps
• The type of input conditioner
➂
User label
Identifies :
• The module type
• The default configuration
• The internal words in the PLC
memory in which the measurement
results will be stored.
➃
Wiring label
Attached to the inside of the
TSX BLK 4 terminal block cover.
Identifies the terminal connections.
1
OK
OK
3
2
1
4
_____________________________________________________________________
80
Hardware installation
6
_____________________________________________________________________
6.3
Connection
6.3-1 Description
TSX AEM 1601/1602 modules use a TSX BLK4 terminal block. This removable terminal block has 32 screw terminals.
Analog input
Channel 0
Analog input
Channel 1
Analog input
Channel 2
Analog input
Channel 3
Analog input
Channel 4
Analog input
Channel 5
Analog input
Channel 6
Analog input
Channel 7
Signals
Ch 0
Ch 1
Ch 2
Ch 3
Ch 4
Ch 5
Ch 6
Ch 7
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
B8
B7
B6
B5
B4
B3
B2
B1
A8
A7
A6
A5
A4
A3
A2
A1
TSX BLK 4 terminal block
(label)
D1
D2
D3
D4
D5
D6
D7
D8
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
C5
C6
C7
C8
C1
C2
C3
C4
Ch 8
Ch 9
Ch 10
Ch 11
Ch 12
Ch 13
Ch 14
Ch 15
Signals
Analog input
Channel 8
Analog input
Channel 9
Analog input
Channel 10
Analog input
Channel 11
Analog input
Channel 12
Analog input
Channel 13
Analog input
Channel 14
Analog input
Channel 15
_____________________________________________________________________
6.3-2 Connection principle
It is advisable to take the following precautions to protect the signal from induced outside noise in serial mode and from common mode noise :
Type of cable
Use screened twisted pairs, with a minimum cross-section of 0.22 mm 2 .
_____________________________________________________________________
81
_____________________________________________________________________
Cable screening
Since there are a large number of channels, a cable with a minimum of 16 twisted pairs and general screening (external ø 15 mm max.) should be used for connecting the BLK 4 terminal block and the intermediate terminal block. Twisted pair cables with separate screening should be used for connecting the intermediate terminal block and the sensors.
The cable screening should be connected to the PLC earth (ground) through a
TSX RAC 20 grounding strip which must be fitted to the PLC rack.
Routing the cables :
• The measurement cables must be kept away from the discrete I/O cables (especially the relay outputs) and the power cables.
• Parallel routing must be avoided (a minimum distance of 20cm must be maintained between cables) and wires should be crossed at right angles.
_____________________________________________________________________
6.3-3 Referencing the channel inputs and sensors
TSX AEM 1601/1602 modules have 16 inputs which have a common point but are isolated from the PLC bus.
For safety reasons, the module has an RC network (4.7 nF/20 MOhms) for earthing
(grounding) the channel reference voltage.
TSX BLK4
It is preferable to use "floating" sensors
(not referenced to ground).
Example to the right : wiring of four "floating" sensors.
+
-
+
-
+
A8
A7
A6
A5
A4
C1
C2
C3
C4
C5
-
+
-
A3
A2
A1
C6
C7
C8
B8 D1 internal module network
_____________________________________________________________________
82
Hardware installation
6
_____________________________________________________________________
6.4
Description of the installation sheet
All the data required for installing TSX AEM modules is grouped together on this sheet.
It is divided into three parts :
• Configuration of the module (sampling the channels)
• Configuration of the channels
• Wiring
An example of the installation sheet is shown at the send of section 7 (and may be photocopied).
Example
Module configuration
1
X
A
B
C
Ch.
0
1
TSX AEM INSTALLATION SHEET
Channel configuration
Range Proc.
Scaling Test Coding Name
N
N
N
N
Temperature sensor with conditioner
Pressure transmitter
2
3
4
2
Updated
3
O
N
4 5
By
N
N
N
Flow rate measurement
PH transmitter
6
Date
7
Design
Cascade flow rate control input
8
Diagram
P
100
Ω
∆ P
100
Ω
PH
Circuit
Wiring
TSX BLK 4
C
B4
B3
B2
B1
B8
B7
B6
B5
A4
A3
A2
A1
A8
A7
A6
A5
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
D6
D7
D8
Date
Circuit
R
9
Telemecanique
Number
➀
Module configuration
➁
Channel number
➂
Input range
➃
Square root extraction
➄
Not used
➅
Sensor break
➆
Coding of the configuration.
➇
Name and/or reference of devices wired
➈
Wiring diagrams
_____________________________________________________________________
83
_____________________________________________________________________
6.5
Recalibration
TSX AEM 1601 and TSX AEM 1602 modules are factory preset and checked before delivery.
The high quality of the components used means that any error developing over time will be within the stated limits. However, to enable the user to compensate for any drift which may occur, or for those used to performing regular adjustments, the modules may be recalibrated provided that the correct version of AEM module set up software is available, that is :
• TXT L PL7 PCL V42 version
≥
4.6
• TXT L PL7 PMS V42 version
≥
4.6
As these software packages are only compatible with model 40 PLCs, version 4.3 and above, it is not possible to recalibrate TSX V3 PLCs.
The recalibration procedure is described in the user manuals supplied with the above set up software packages.
_____________________________________________________________________
84
X
Specifications 7
Section 7
________________________________________________________________________________________
7.1
Consumption
Page
86
________________________________________________________________________________________
7.2
Input characteristics 86
7.2-1 TSX AEM 1601
7.2-2 TSX AEM 1602
86
87
_________________________________________________________________________________________
7.3
Installation sheet 88
______________________________________________________________________
8 5
______________________________________________________________________
7.1
Consumption
Power supply for the modules is provided by the PLC.
________________________________________________________________________________________
Maximum consumption Typically
5 V 650 mA
15 mA
520 mA
11 mA
_____________________________________________________________________
7.2
Input characteristics
7.2-1 TSX AEM 1601 input characteristics
The TSX AEM 1601 has 16 analog inputs with the following characteristics :
_________________________________________________________________________________________
±
10.2 V
±
30 V
> 10 MOhms
10 V/4000 = 2.5 mV
Measurement error (filtered mode) as % of full scale • at 25
°
C
• at 60
°
C
Minimum sampling rate for
0.2 %
0.55 % (drift of 1/2 class per 10
°
C)
≤
1 LSB
> 50 dB (filtered mode)
120
µ s
> 70 dB
≤
1 LSB
240 ms
RC grounding network
≤
1 LSB
R : 20 MOhms
4.7 nF
Isolation between channels and ground 500 V DC
Dielectric strength between channels and bus 1500 V 50 Hz / 1 mn
______________________________________________________________________
86
Specifications 7
______________________________________________________________________
7.2-2 TSX AEM 1602 input characteristics
The TSX AEM 1602 has 16 analog inputs with the following characteristics :
_________________________________________________________________________________________
±
20.4 mA
±
30 V (only 1 input overloaded at any time)
Approximately 90
Ω
20 mA/4000 = 5
µ
A
0-20 mA 4-20 mA Measurement error (filtered mode) as % of full scale • at 25
°
C
• at 60
°
C
0.2 %
0.55 %
≤
1 LSB
0.2 %
0.55 %
Minimum sampling rate for
> 50 dB (filtered mode)
60
µ s
> 70 dB
≤
1 LSB
240 ms
RC grounding network
≤
1 LSB
R : 20 MOhms
4.7 nf
Isolation between channels and ground 500 V DC
Dielectric strength between channels and bus 1500 V 50 Hz / 1 mn
______________________________________________________________________
8 7
______________________________________________________________________
______________________________________________________________________
88
X
8.1
Index
Appendix 8
Section 8
Page
90
_____________________________________________________________________
89
_____________________________________________________________________
8.1
Index
A
Access via extended register
Accessing measurements
Acquisition of measurements
Additional requests
B
Bits associated with configuration
C fault
Configuration channels
default
re-reading
Connection
D
Data exchange module-PLC
Detection of faults
L
Limits error detection
higher and lower
Locating devices
M
Measurement processing
sampling
scaling
Measurement sampling
Measurement scaling
Mode filtered
normal
operating
P
Processing faults
measurements
sensor break
F R
Fault bit string (BDEF)
Faults
blocking
detection
effect on operating modes
module acquisition and conversion
Range overshoot
Re-reading the
S
configuration
Recalibration
Resolution
I
Identification
Indicator lamps
Interface discrete
extended register
message
register
Safety
Sensor break test
Square root
Standard range
Structure
W hardware software
Words register
status
_____________________________________________________________________
90
___________________________________________________________________________
Indicator lamps
TSX AEM 1601
F
OK
ERR
Red lamp "module off"
Green lamp" module on and operating correctly"
Red lamp "channel fault" indicates an application fault on a channel (signal outside limits, or sensor break or calculation overflow).
General characteristics
• V3 PLCs : TSX 47-30/67-20/87-30
Model 40 PLCs : TSX or PMX 47-40/67-40/87-40/107-40
• Mechanical and software locating code : 650 for the TSX AEM 1601
651 for the TSX AEM 1602
• Behaviour at power break (for a period greater than the PLC power supply reserve) and at power return :
- Loss of configuration
- Restart with default configuration
• Consumption at 5 V : 520 mA and 12 VL : 11 mA.
Connections
Signals
TSX BLK 4 terminal block
(label)
Signals
Analog input
Channel 0
Analog input
Channel 1
Analog input
Channel 2
Analog input
Channel 3
Ch 0
Ch 1
Ch 2
Ch 3
+
-
+
-
+
-
+
-
A8
A7
A6
A5
A4
A3
A2
A1
C1
C2
C3
C4
C5
C6
C7
C8
+
-
+
-
+
-
+
-
Ch 8
Ch 9
Ch 10
Ch 11
Analog input
Channel 8
Analog input
Channel 9
Analog input
Channel 10
Analog input
Channel 11
Analog input
Channel 4
Analog input
Channel 5
Ch 4
Ch 5
+
-
+
-
+
-
B8
B7
B6
B5
D1
D2
D3
D4
+
-
+
-
+
-
Ch 12
Ch 13
Analog input
Channel 12
Analog input
Channel 13
Analog input
Channel 6
Ch 6
B4
B3
D5
D6
Ch 14
Analog input
Channel 14
Analog input
Channel 7
Ch 7
+
-
B2
B1
D7
D8
+
-
Ch 15
Analog input
Channel 15
___________________________________________________________________________
2
Quick reference
___________________________________________________________________________
Sensors with isolated voltage supply
POWER
SUPPLY
+
-
TSX BLK 4 terminal block
+
V
-
In0 (+)
In0 (-)
+
V
-
In1 (+)
In1 (-)
TSX RAC 20
Sensors with isolated current supply (4-20 mA, 2 wire)
POWER
SUPPLY
+
mA
+
mA
+
-
TSX BLK 4 terminal block
In0 (+)
In0 (-)
In1 (+)
In1 (-)
- +
Control panel indicator/recorder
___________________________________________________________________________
3
___________________________________________________________________________
Exchange block diagram
TSX AEM 1601/1602 module
➤ ➤
PLC processor
Ixy,i
Fault detection
8 words OW
OW
Channel 0 ➤
Channel 1 ➤
Channel 2 ➤
Channel 3 ➤
Channel 4 ➤
Channel 5 ➤
Channel 6 ➤
Channel 7 ➤
Channel 8 ➤
Channel 9 ➤
Channel 10 ➤
Channel 11 ➤
Channel 12 ➤
Channel 13 ➤
Channel 14 ➤
Channel 15 ➤
➤
CAN
Processing
➤
8 words
17 words
IW
READEXT
MSG
IW
Wi
WI+16
TXT
CONFIGURATION
➤
➤
➤
Request interpreter
Message
Common requests
_________________________________________________________________________________________
Purpose of request TXTi,C Ch. n
°
TXTi,V N
°
of N
°
of Module
(hex) (hex) (hex) bytes bytes status read
49
4A
0F
01
40
41
47
63
63
63
0
63
63
63
FE(FD)
71(FD)
77
FE/FD
7A(FD)
3F(FD)
81(FD)
20
0
0
0
34
0
0
0
20
27
32
0
34
12
STOP
STOP/RUN
STOP/RUN
STOP/RUN
STOP/RUN
STOP/RUN
RUN
Transfer characteristics
●
●
●
●
●
CPL type transmit/receive text block
TXTi,M = H’xy..' where x = Rack n
°
, y = slot, .. = channel n
°
00 or 63
TXTi,C = request code
TXTi,V = confirmation sent by module, FD = incorrect transfer
TXTi,S = number of bytes received per transfer (if transfer OK)
___________________________________________________________________________
4
Quick reference
___________________________________________________________________________
Addressing
Discrete bits
Input : read by
PLC processor
I x y , i
Word N°
Slot N°
Rack N°
Register words
IW or OW x y, i
Input : read by
PLC processor
Output : written
by PLC processor
Word N°
Slot N°
Rack N°
Discrete bits
F E D C B A 9 8 7 6 5 4 3 2 1 0
Ixy,8 fault channel 8
Ixy,9 fault channel 9
Ixy,A fault channel 10
Ixy,B fault channel 11
Ixy,C fault channel 12
Ixy,D fault channel 13
Ixy,E fault channel 14
Ixy,F fault channel 15
Ixy,0 fault channel 0
Ixy,1 fault channel 1
Ixy,2 fault channel 2
Ixy,3 fault channel 3
Ixy,4 fault channel 4
Ixy,5 fault channel 5
Ixy,6 fault channel 6
Ixy,7 fault channel 7
8 input register words
(words read by PLC processor)
Standard status word IWxy,0
F
IWxy,1
F
IWxy,2
F
IWxy,3
Complementary status word
0
0
0
IWxy,4
IWxy,5
IWxy,6
IWxy,7
8 output register words
(words written by PLC processor)
Standard control word OWxy,0
F
OWxy,1
F
OWxy,2
F
OWxy,3
F
OWxy,4
F
OWxy,5
OWxy,6
OWxy,7
0
0
0
0
0
___________________________________________________________________________
5
___________________________________________________________________________
Input register words : Transmitted by the module and read by the PLC processor
IWxy,0 standard status word IWxy,2 complementary status word n
°
2
F E D C B A 9 8 7 6 5 4 3 2 1 0 F E D C B A 9 8 7 6 5 4 3 2 1 0
2 1 = RESET m essage system (text block)
3 1 = module available (self-test completed)
4 1 = module or fault memorization fault
6 1 = acquisition, conversion or fault memorization fault
7 1 = application or fault memorization fault
8 1 = module off (blocking fault)
9 1 = initial self-test running
A 1 = terminal block not locked
B 1 = awaiting configuration
0 = module configured
C 1 = module in RUN mode
0 = module in STOP mode
D 1 = default configuration
Output register words : Transmitted by the PLC processor and read by the module
OWxy,0 standard control word
F E D C B A 9 8 7 6 5 4 3 2 1 0
2 1 = set message system to zero
(text block)
C RUN/STOP module control
1 = RUN 0 = STOP
Extended register interface
Acquisition mode only available on model 40 processors version 4.3 and above.
Syntax
! READEXT (Ixy; Wi; Wj)
Ixy : geographical address of the module
Wi : start of the reception table
Wj : number of words to read (17 for TSX AEM 160x modules)
Content of the reception table
Wi
Wi + 1
Wi + 2
Wi + 3
Wi + 4
Wi + 5
Wi + 6
Wi + 7
Wi + 8
Wi + 9
Wi + 10
Wi + 11
Wi + 12
Wi + 13
Wi + 14
Channel status
Measurement channel 0
Measurement channel 1
Measurement channel 2
Measurement channel 3
Measurement channel 4
Measurement channel 5
Measurement channel 6
Measurement channel 7
Measurement channel 8
Measurement channel 9
Measurement channel 10
Measurement channel 11
Measurement channel 12
Measurement channel 13 same as discrete bit Ixy,0…F
Wi + 15 Measurement channel 14
Wi + 16 Measurement channel 15
___________________________________________________________________________
6
Quick reference
___________________________________________________________________________
Configuration = table of 17 words
Common to 16 channels : 1 word
0 • A 0
➤
Acquisition
0 Normal mode
1 50 Hz filtered mode
2 60 HZ filtered mode
For each channel
• • • • ➤ Channel N°
0 to F
Sensor break
0 no test
1 sensor break test
on range
±10 V ±5 V
Processing
0 no sqare root
1 square root
TSX AEM range
1601 1602
0 ± 10 V
1 ± 5 V
2 1-5 V
4-20 mA
0-20 mA
Default configuration
. Normal mode : ±10 V or 4-20 mA
. Configuration of each channel :
- no square root extraction
- no sensor break test
in ±10V range
Transfer characteristics
●
CPL type transmit/receive text block
●
TXTi,M = H'xy63' where x = Rack N
°
and y = slot
●
TXTi,C = H'40'.
●
Length of transmission table : 34 bytes
●
TXTi,V = confirmation sent by module
FE = if transfer correct, FD = if transfer incorrect
●
TXTi,S = number of bytes received per transfer (if transfer OK)
●
Once configured the "Default configuration" bit IWxy,2,D changes to 0
●
If configuration is incorrect, the "Awaiting configuration" bit IWxy,0,B remains at 1
___________________________________________________________________________