Schneider Electric PL7OSI, MMS Module User Guide
إعلان
إعلان
General A
___________________________________________________________________________
Set-Up and Methodology B
OSI-LOADER C
PL7-OSI
PL7-MMS
MMS OFBs
D
E
F
General Appendix G
Application Example H
___________________________________________________________________________
A
___________________________________________________________________________
________________________________________________________
General A
___________________________________________________________________________
A
MMS Presentation
1.1
Introduction to MMS
1.2
MMS Services
1.3
Client-Server Model
1.4
Confirmed and Unconfirmed Services
1.5
The MMS Functional Model
1.5-1 Virtual Manufacturing Device (VMD)
1.5-2 MMS Objects
__________________________________________________________________________________________________
MMS and TSX Series 7 PLCs
2.1
Presentation
2.1-1 Client Function
2.1-2 Server Function
2.2
Communication Profile
2.3
MMS Client Function
2.3-1 MMS Services Supported
2.3-2 MMS Variables Supported
2.4
MMS Server Function
2.4-1 MMS Services Supported
2.4-2 MMS Objects Supported
2/3
2/4
2/5
2/5
2/6
2/1
2/1
2/1
2/2
2/3
Page
1/1
1/1
1/2
1/2
1/2
1/2
1/3
__________________________________________________________________________________________________
TSX Series 7 PLC MMS Modelization
3.1
The VMD
3.1-1 The VMD Object Description
3.1-2 MMS Services Supported
3/1
3/1
3/4
3.2
The Domain
3.2-1 Domain Object Description
3.2-2 MMS Services Supported
3.3
The Program
3.3-1 PI (Program Invocation) Object Description
3.3-2 MMS Services Supported
3/5
3/5
3/6
3/7
3/7
3/8
___________________________________________________________________________
A / 1
________________________________________________________
___________________________________________________________________________
3.4
The Variables
3.4-1 Objects Assigned to the PLC Station
3.4-2 Objects Assigned to the Station Application
3.4-3 Unnamed Variable Object Description
3.4-4 Named Variable Object Description
3.4-5 Supported MMS Services
Page
3/9
3/10
3/11
3/12
3/13
3/15
__________________________________________________________________________________________________
Conventions
4.1
"Argument" Parameter
4.2
"Result(+)" Parameter
4.3
"Result(-)" Parameter
4.4
Procedure
4/1
4/1
4/1
4/1
__________________________________________________________________________________________________
Context Management
5.1
Initiate Service
5.1-1 MMS Calling Mode
5.1-2 MMS Called Mode
5.2
Conclude Service
5.2-1 MMS Calling Mode
5.2-2 MMS Called Mode
5/1
5/1
5/3
5/5
5/5
5/5
5.3
Abort Service
5.3-1 MMS Calling Mode
5.3-2 MMS Called Mode
5.4
Reject Service
5.4-1 MMS Client Mode
5.4-2 MMS Server Mode
5/6
5/6
5/6
5/7
5/7
5/8
___________________________________________________________________________
A / 2
________________________________________________________
General A
___________________________________________________________________________
A
6
6.1
Status Service
6.1-1 MMS Client Mode
6.1-2 MMS Server Mode
6.2
Unsolicited Status Service
6.2-1 MMS Client Mode
6.2-2 MMS Server Mode
6.3
Identify Service
6.4
GetNameList Service
_______________________________________________________________________________________________________________________________________________________________________________________________
Domain Management Services
7.1
InitiateDownLoadSequence Service
7.2
DownLoadSegment Service
7.3
TerminateDownLoadSequence Service
7.4
InitiateUpLoadSequence Service
7.5
UpLoadSegment Service
7.6
TerminateUpLoadSequence Service
7.7
DeleteDomain Service
7.8
GetDomainAttributes Service
7/1
7/3
7/4
7/6
7/7
7/9
7/10
7/12
Page
6/1
6/1
6/2
6/3
6/3
6/3
6/4
6/5
_______________________________________________________________________________________________________________________________________________________________________________________________
Program Invocation Management Services
8.1
CreateProgramInvocation Service
8.2
DeleteProgramInvocation Service
8.3
Start Service
8.4
Stop Service
8.5
Resume Service
8.6
Reset Service
8.7
GetProgramInvocationAttributes Service
8/1
8/3
8/5
8/6
8/7
8/8
8/9
___________________________________________________________________________
A / 3
________________________________________________________
___________________________________________________________________________
Variable Access Services
9.1
Variable Access Specification Parameters
9.2
Access Result Parameters
9.2-1 Parameters
9.2-2 Error Codes
9.3
Read Service
9.3-1 MMS Client Mode
9.3-2 MMS Server Mode
9.4
Write Service
9.4-1 MMS Client Mode
9.4-2 MMS Server Mode
9.5
InformationReport Service
9.5-1 MMS Client Mode
9.5-2 MMS Server Mode
9.6
GetVariableAccessAttributes Service
_______________________________________________________________________________________________________________________________________________________________________________________________
Appendix
10/1
Page
9/1
9/3
9/3
9/4
9/6
9/6
9/7
9/9
9/9
9/10
9/11
9/11
9/12
9/12
___________________________________________________________________________
A / 4
MMS Presentation 1
__________________________________________________________________________________________
This Section is intended for users that wish to familiarize themselves with the general concepts of MMS.
The intention is not to provide a description of the MMS standard, but simply to review the key points.
Important
The description of status graphs for MMS objects and the detailed description of
MMS service execution procedures are not described in this manual. For these, refer to the MMS standard.
A
If the user feels familiar with these concepts, they can proceed directly to Divider A,
Section 2, where MMS support by TSX Series 7 PLCs is described.
1.1
Introduction to MMS
MMS (Message Manufacturing Specification) defines the services (ISO 9506-1) and the protocol (ISO 9506-2) for the Application layer of the MAP 3.0 communication profile that ensures inter-operability of factory devices.
MMS uses the services and protocols of the network used by MAP3.0 for device interconnection.
MMS is designed to meet the requirements of exchanges between devices used in industrial manufacturing applications (PLCs, numerical controllers, robots, etc.) and the systems used for production management (computers, supervisory systems, etc.).
MMS defines a functional model that meets the various requirements for operation, exchange types and elements to manage.
__________________________________________________________________________________________
1 / 1
A
__________________________________________________________________________________________
1.2
MMS Services
The MMS standard defines 86 services combined into functional sub-groups.
These include:
• Environment and general management services,
• VMD support services,
• Domain management services,
• Program Invocation management services,
• Variable access services,
• Event management services,
• Semaphore management services,
• File management services,
• Operator communication services,
• Journal management services.
1.3
Client-Server Model
__________________________________________________________________________________________
MMS uses the Client-Server model, where the Client device sends requests for services and where the Server device executes the requested service and replies to the Client device.
A device may support only the Server mode (responding to requests for services), or only the Client mode (sending requests for services), or both, in which case it is a Client and a Server.
Most MMS services are confirmed ones.
__________________________________________________________________________________________
1.4
Confirmed and Unconfirmed Services
__________________________________________________________________________________________
A service is confirmed when the exchange (or transaction) requires confirmation from the receiver.
An unconfirmed service is processed without confirmation from the receiver device.
__________________________________________________________________________________________
1 / 2
MMS Presentation 1
__________________________________________________________________________________________
1.5
The MMS Functional Model
1.5-1 Virtual Manufacturing Device (VMD)
MMS defines a Virtual Manufacturing Device (VMD) to represent a variety of manufacturing devices.
A VMD is a model of the Server device (PLC, numerical controller, etc.).
Services assigned to the VMD are those in the "device management" family.
The VMD contains a number of other MMS objects, as described in this Sub-section.
A
1.5-2 MMS Objects
MMS objects in the VMD are defined by their characteristics and by the operations that
MMS services can perform on them.
These objects represent the operation of the VMD to the MMS services.
There are the following MMS objects:
• Domains,
• Programs,
• Variables,
• Events,
• Semaphores,
• Files,
• Operator stations,
• Journals.
__________________________________________________________________________________________
1 / 3
A
__________________________________________________________________________________________
__________________________________________________________________________________________
1 / 4
MMS and TSX Series 7 PLCs 2
__________________________________________________________________________________________
2.1
Presentation
This section describes the MMS features supported by OSI interface modules for integrating TSX Series 7 PLCs into a heterogeneous MMS network layout.
These features are provided by the STACK OSI 3.0 program that must be uploaded into the OSI interface modules (refer to Divider C in this manual).
The PLC acts as an MMS Client and Server device. It can communicate with any MMS device connected to the network.
A
2.1-1 Client Function
The services implemented in MMS Client mode support the following operations:
• Read and write remote application variables,
• Receive unsolicited variables,
• Read the status of a remote device,
• Receive the unsolicited status of a remote device.
For the user, support for these services in MMS Client mode is provided by OFBs programmed in the PL7-3 application (refer to Divider F, Section 3).
2.1-2 Server Function
The services implemented in MMS Server mode support the following operations:
• Identifying the PLC (model, version),
• Monitoring the PLC operating state,
• Uploading and saving the PLC station application,
• Checking the execution of the PL7-3 sequential program,
• Reading and writing PLC application variables.
For the user, support for these MMS services requires no additional programming in the application. The PLC operates as an auto-answering MMS device.
In addition, in MMS Server mode, the PL7-3 program can initiate the following services:
• Sending unsolicited variables,
• Sending TSX Series 7 station operating status.
__________________________________________________________________________________________
2 / 1
A
__________________________________________________________________________________________
These services are triggered by OFBs programmed in the PL7-3 application PL7-3 (refer to Divider F, Section 3).
In addition, all MMS services are supported simultaneously with Telemecanique X-WAY services (UNI-TE message system, common words, NETDIAG network management, bridge functions, etc.) described in the OSI interface module User's Manuals.
2.2
Communication Profile
The communication services and protocols supported are those defined for MAP3.0.
LAYERS
Application
Presentation
Session
Transport
Network
Data Link
MAC
Physical
STANDARDS
MMS IS
MMS DIS
ACSE
Kernel
ASN1
BCS
TP4
IP
ES/IS
LLC1
Token Bus
CSMA-CD
CSMA-CD
SERVICES
ISO 9506/1
ISO 8649
ISO 8822
ISO 8824
ISO 8825
ISO 8326
ISO 8072
ISO 8348
ISO 8802.2
ISO 8802.4
ISO 8802.3
PROTOCOLS
ISO 9506/2
ISO 8650
ISO 8823
ISO 8327
ISO 8073
ISO 8473
ISO 9542
ISO 8802.2
ISO 8802.4
ISO 8802.3
BaseBand (10 Mb/s)
The communication profile parameters can be set so that the OSI module can be adapted to various types of configuration (refer to Divider D).
__________________________________________________________________________________________
2 / 2
MMS and TSX Series 7 PLCs 2
__________________________________________________________________________________________
2.3
MMS Client Function
This function lets the PL7-3/MMS application in the TSX Series 7 station initiate MMS exchanges destined for any remote device on the network.
These MMS exchanges are supported by an MMS association, DIS or IS versions, dynamically negotiated when the association is opened.
MMS associations can be opened by the TSX Series 7 station or by the remote device.
A
2.3-1 MMS Services Supported
Environment and General Management Services:
• Initiate
• Conclude
• Abort
• Reject
VMD Support Services:
• Status
• Unsolicited status
Variables Access Services:
• Read
• Write
• Information Report
__________________________________________________________________________________________
2 / 3
A
__________________________________________________________________________________________
2.3-2 MMS Variables Supported
The table below shows the characteristics of MMS variables accessed by the MMS
Client PL7-3 program:
SCOPE
VMD/DOMAIN/AA
MMS TYPE
SIMPLE TYPE:
Boolean,
Integer16, Integer32
Unsigned16, Unsigned32
FloatingPoint (simple precision),
VisibleString2N (N =1..2048),
OctetString2N (N = 1..2048)
BitStringN (N = 1..2048)
ARRAY [1..1024] :
Boolean
Integer16, Integer32
Unsigned16, Unsigned32
FloatingPoint (simple precision),
VisibleString2,
OctetString2,
BitString1
BitString16
Structure (simple type) (*)
STRUCTURE [1..16] :
Simple type
Array (simple type) (*)
The programming of these services is explained in Divider F on MMS OFBs.
(*): String type restricted to VisibleString2, OctetString2, BitString1 and BitString16.
__________________________________________________________________________________________
2 / 4
MMS and TSX Series 7 PLCs 2
__________________________________________________________________________________________
2.4
MMS Server Function
This function lets the TSX Series 7 station be seen as an MMS auto-answering device for any remote device on the network.
Cases of unsolicited transmission of variables and TSX Series 7 station status data
(InformationReport, UnsolicitedStatus), must be programmed by the MMS OFBs in the
PL7-3/MMS application.
These MMS exchanges are supported by an MMS association MMS, DIS or IS version, dynamically negotiated when the association is opened.
MMS associations can be opened by the station, the remote device or by the
TSX Series 7 PLC.
A
2.4-1 MMS Services Supported
Environment and General Management Services:
• Initiate
• Conclude
• Abort
• Reject
VMD Support Services:
• Status
• Unsolicited Status
• GetNameList
• Identify
Domain Management Services:
• InitiateDownLoadSequence
• DownLoadSegment
• TerminateDownLoadSequence
• InitiateUpLoadSequence
• UpLoadSequence
• TerminateUpLoadSequence
• GetDomainAttributes
• DeleteDomain
Program Invocation (PI) Management Services:
• CreateProgramInvocation
• DeleteProgramInvocation
• GetProgramInvocationAttributes
• Start
• Stop
• Resume
• Reset
__________________________________________________________________________________________
2 / 5
A
__________________________________________________________________________________________
Variable Access Services:
• Read
• Write
• Information Report
• GetVariableAccessAttributes
2.4-2 MMS Objects Supported
The table below shows the MMS objects supported and the PLC correspondence for each type of object.
MMS Object
VMD
TSX Series 7 Description
TSX Series 7 PLC station
DOMAIN (.APP) The station application
.APP (comprising all of the PLC application componants for a V4 level application).
.APP with additional PLC application componants for V5 level applications.
PROGRAM (PI)
VARIABLE
VMD/AA scope
VARIABLE
VMD/DOMAIN/AA scope
The PL7-3 program
(sequential command function)
System Bits (SYi)
Real-time Clock
System Words (SWi)
Internal Bits (Bi), Words (Wi) and Double Words (DWi)
Bit of an Internal Word (Wij)
Constant Words (CWi) and Double
Constant Words (CDWi)
Strings of Words (Wi), Double Words (DWi)
Constant Words (CWi) and Double
Constant Words (CDWi)
Internal Bits (Bi)
__________________________________________________________________________________________
2 / 6
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
3.1
The VMD
VMD represents the TSX Series 7 PLC station that supports the OSI module.
A
3.1-1 The VMD Object Description
This description is taken from the MMS standard.
Executive function
Enables the interface between the MMS model and the PLC station for access to real objects.
It corresponds to the MMS Server.
Vendor Name = TELEMECANIQUE
This attribute defines the device vendor's name.
The value of this attribute is supplied as a response to the MMS Identify service.
Model Name = TSX/PMX 47.420/425 to 107.420/455 for V5 level PLCs
TSX/PMX 47.400 to 107.420 for V4 level PLCs
This attribute defines the model of VMD device.
The value of this attribute is supplied as a response to the MMS Identify service.
Revision = TSX7 Processor version
This attribute defines the version of VMD device.
The value of this attribute is supplied as a response to the MMS Identify service.
List of Abstract Syntaxes Supported
Not used.
Logical Status = STATE_CHANGES_ALLOWED or SUPPORT_SERVICES_ALLOWED
This attribute defines the services accessible in the PLC station (logical operating mode).
The value of this attribute is supplied as a response to the MMS Status service.
__________________________________________________________________________________________
3 / 1
A
__________________________________________________________________________________________
* STATE_CHANGES_ALLOWED
All MMS services supported by the VMD can be executed.
* SUPPORT_SERVICES_ALLOWED
This case corresponds to a PLC memory that cannot be executed (no application in the
PLC memory).
All MMS services supported by the VMD can be executed except for Program Invocation
Management Services.
The services used to access variables are restricted (no access to DOMAIN scope variables, no access to named variables).
List of Capabilities
Not used.
Physical Status = OPERATIONAL or NEEDS-COMMISSIONING or PARTIALLY OPERATIONAL
This attribute defines the PLC station operational status (hardware operating mode).
The value of this attribute is supplied as a response to the MMS Status service.
OPERATIONAL
The PLC station is fully operational if:
• The memory is executable,
• There are no software errors,
• There are no I/O errors.
NEEDS-COMMISSIONING
The PLC station status requires operator intervention (assistance) if:
• The memory cannot be executed,
• The memory cartridge is not present.
PARTIALLY-OPERATIONAL
All other error conditions correspond to this state.
Local Detail
This (16-bit) attribute is divided into two fields (2*8 bits) and enables a more precise specification of the PLC station status.
Each bit is assigned to data that is true when the bit is set to 1.
The value of this attribute is supplied as a response to the MMS Status service.
__________________________________________________________________________________________
3 / 2
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
* PHYSICAL LOCAL DETAIL (8-bits LSB) b0 : b1 :
Non-executable memory
Cartridge absent b2 : b3 :
Software failure
I/O Error
* LOGICAL LOCAL DETAIL (8-bits MSB) b8 : Table of MMS symbols present in the OSI module b9 : OSI directory present in the OSI module
List of Program Invocations (PI) = PL7-3 Program
This attribute contains the list of VMD programs (tasks).
In the present version, there is only one program, i.e. PL7-3.
The PI name is defined in Sub-section 3.3-1.
The value of the "List Of PI" attribute is a response to the MMS GetNameList service.
List of Domains = The PLC station application
This attribute contains the list of VMD domains.
In the present version, there is only one domain, i.e. the PLC station application station
(.APP). The domain name is defined in Sub-section 3.2-1.
The value of the "List Of Domains" attribute is supplied as a response to the MMS
GetNameList service.
List of Transaction Objects
This attribute contains the list of current Transaction objects. A Transaction object is created on reception of any indication primitive for a confirmed service.
This attribute is processed locally in the MMS Server.
List of Upload State Machines (ULSM)
This attribute contains the list of ULSM objects created on reception of an indication from the Domain upload initialization service.
This attribute is processed locally in the MMS Server.
List of Other VMD Specific Objects
This attribute contains the list of other VMD objects.
These are PLC station variables (VMD) that are visible by MMS and defined in Subsection 3.4-1.
Additional details
Not used.
__________________________________________________________________________________________
3 / 3
A
A
__________________________________________________________________________________________
3.1-2 MMS Services Supported
The table below shows the MMS services assigned to the TSX Series 7 station VMD object.
MMS Services
TSX Series 7 station VMD identification
(MMS Identify service)
Read the status of the TSX Series 7 station VMD
(MMS Status service)
Access to the list of names for a class of objects (domain, PI, variable) assigned to the VMD or to a domain of the VMD or to an AA scope
(MMS GetNameList service)
Unsolicited transmission of the state of the TSX Series 7 PLC VMD
(MMS UnsolicitedStatus service) (1)
(1):
The programming of this service in the PL7-3 application is described in the appropriate
OFB Sub-section in Divider F, Section 3.
__________________________________________________________________________________________
3 / 4
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
3.2
The Domain
The domain is the PLC station application (.APP).
A
3.2-1 Domain Object Description
This description is taken from the MMS standard.
Domain Name = MMS or PU_MEM (default name)
This attribute clearly identifies the Domain object in the VMD.
List of Capabilities
Not used.
State
This attribute specifies the domain state.
Five states are defined by the MMS standard (LOADING, COMPLETE, UNCOMPLETE,
READY, IN_USE).
These states are processed locally in the MMS Server.
Assigned Application Association
This attribute designates the MMS assignments used to create the domain (uploading).
This attribute is processed locally in the MMS Server.
MMS Deletable = TRUE
This attribute specifies that the Domain is deletable by the MMS DeleteDomain service.
The value of this attribute is provided on response from the MMS GetDomainAttributes service.
Sharable = FALSE
This attribute indicates that the domain is only used by the PL7-3 program in the
TSX Series 7 PLC MMS model.
Domain Content
Not used.
__________________________________________________________________________________________
3 / 5
A
__________________________________________________________________________________________
List of Subordinate Objects
This attribute contains a list of references to MMS objects that are part of the Domain.
This list contains the station application (Domain) variables that can be accessed by
MMS as defined in Divider A, Sub-section 3.4-2.
List of Program Invocation References
This attribute contains a list of references to programs (tasks) that use the Domain. This list comprises the PI corresponding to the name of the PL7-3 program defined in
Divider A, Sub-section 3.3-1.
Upload In Progress
This attribute specifies the number of domain uploads (saves) in progress.
It is processed locally in the MMS Server.
Additional Detail
Not used.
3.2-2 MMS Services Supported
The table below shows the MMS services assigned to the PLC station Domain application.
MMS Services
Upload the station Domain application
MMS services: InitiateUploadSequence
UploadSegment
TerminateUploadSequence)
Delete the station Domain application
MMS services: DeleteDomain
Download the station Domain application
MMS services: InitiateDownloadSequence
DownloadSegment
TerminateDownloadSequence)
Access to the characteristics of station Domain application
MMS services: GetDomainAttributes
__________________________________________________________________________________________
3 / 6
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
3.3
The Program
The program represents the sequential control function, i.e. the PL7-3 program.
A
3.3-1 PI (Program Invocation) Object Description
This description is taken from the MMS standard.
PI Name = MMS or PI_PL73 (default name)
This attribute unambiguously identifies the PI object
State
This attribute specifies the state of the PI object
Nine states are defined by the MMS standard (IDLE, STARTING, RUNNING, STOPPED,
RESUMING, RESETTING, UNRUNNABLE, NON EXISTENT and STOPPING).
These states are processed locally in the MMS Server.
List of Domains Reference = MMS or PU_MEM
This attribute contains the list of references of the domains assigned to PI.
The domain assigned to PI. PL7-3 is the PLC station application.
MMS Deletable = TRUE
This attribute indicates that the program is deletable by the MMS DeleteProgramInvocation service.
The value of this attribute is supplied on response from the MMS
GetProgramInvocationAttributes service.
Reusable = TRUE
This attribute indicates that the program is executed permanently, without needing to be restarted.
Monitor = FALSE
This attribute indicates that execution of PI will not be tested by the event management mechanisms when it exits the RUNNING state.
__________________________________________________________________________________________
3 / 7
A
__________________________________________________________________________________________
Start Arguments
Not used.
Additional Detail
Not used.
3.3-2 MMS Services Supported
The table below shows the MMS services assigned to the PL7-3 program PI object.
Create PL7-3 PI
MMS service:
Delete PL7-3 PI
MMS service:
Start PL7-3 PI execution
MMS service:
Stop PL7-3 PI execution
MMS service:
Resume PL7-3 PI execution
MMS service:
Reset to the start of PL7-3 PI
MMS service:
Access to PL7-3 PI characteristics
MMS service:
MMS Services
CreateProgramInvocation
DeleteProgramInvocation
Start
Stop
Resume
Reset
GetPIAttributes
__________________________________________________________________________________________
3 / 8
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
3.4
The Variables
These represent the device objects that can be accessed in read/write modes.
The variables supported by the MMS Server are:
MMS Object
NamedVariable
Access
By the variable name
A
UnnamedVariable By the variable address
A named variable is assigned to a scope.
The MMS Server supports the following scopes:
MMS Scope
VMD_specific
DOMAIN_specific
AA_specific
TSX7 Objects
Variables assigned to the
TSX7 PLC station
Variables assigned to the station application .APP
Variables assigned to an
MMS association/application
The rules for storing MMS variables in the PLC memory are described in the table in
Divider F, Sub-section 3.2-2. They are identical to the rules that apply to storing remote
MMS variables in PL7-3 objects.
Named variables are assigned an "Automatic/Programmed" attribute.
Programmed variable
A programmed variable supports the Coherence and Sequencing Management Services:
• The Coherence Service ensures coherent access to MMS/PL7-3 variables via the
MMS Server Read or Write services, regardless of the length of the variable.
• The Sequencing Service ensures synchronization between an access to an MMS/
PL7-3 variable by the MMS Server Read or Write services and its use in PL7-3.
Access to a "programmed" variable requires programming an MSEMA OFB in the PL7-3 application.
__________________________________________________________________________________________
3 / 9
A
__________________________________________________________________________________________
"Automatic" variables
An "Automatic" variable does not support the Sequencing Management Service, and supports Coherence Management only if the number of PL7-3 objects that compose the
MMS variable does not exceed the values given in the table below:
Objects Maximum number of PL7-3 objects composing the variable
System bit
Internal bit - word
System word
Real-time clock
Double words
Constant double words
Words
Constant words
Bits
1
30
60
496
Access to an "Automatic" variable does not require programming a MSEMA OFB in the
PL7-3 application.
3.4-1 Objects Assigned to the PLC Station
The following objects, not present in the PL7-3 Configuration mode, are assigned to the
PLC station (VMD scope):
PL7-3 Objects PLC Variables
Date_time
System_bit
SY50 to SY57
SY0 to SY128
The scope of system bits can be changed in the AA scope, using PL7-MMS (refer to
Divider E, Sub-section 3.3).
__________________________________________________________________________________________
3 / 1 0
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
3.4-2 Objects Assigned to the Station Application
The following objects, that can be configured in PL7-3 Configuration mode, are assigned to the station application (DOMAIN scope):
Objects PLC Variable
Internal_Bit
Internal_Word
Internal_Double_Word
Constant_Word
Constant_Double_Word
System_Word
Internal_Word_Bit
String of Internal_Words
(2048 words max.)
String of Constant_Words
(2048 words max.)
String of Internal_Double_Words
(1024 double_words max.)
String of Constant_Double_Words
(1024 double_words max.)
String of Internal_Bits
(2048 bits max.)
B0 to B3935 (1)
W0 to W32596
DW0 to DW32595
CW0 to CW26206
CDW0 to CDW26205
SW0 to SW127
Wi,j (j: 0 to F)
W0 to W32596
W0 to W26206
DW0 to DW32595
CDW0 to CDW26205
B0 to B3935
A
(1) The upper limit of object indexes depends on the configuration established in PL7-3
Configuration mode.
The scope of system bits can be changed in the VMD and AA scopes, using PL7-MMS
(refer to Divider E, Sub-section 3.3).
__________________________________________________________________________________________
3 / 1 1
A
__________________________________________________________________________________________
3.4-3 Unnamed Variable Object Description
An unnamed variable is designated in the PLC by a "PLC Variable" (e.g.: W10, B7, etc.).
This reference is used to designate the MMS unnamed variable. It is the symbolic address of the MMS variable.
The description below is taken from the MMS standard.
Address = PLC variable
This attribute designates the location of the actual variable in the device.
MMS Deletable = FALSE
This attribute indicates that an unnamed variable cannot be deleted.
Access Method = PUBLIC
This attribute indicates that an unnamed variable is always allowed public access.
Type Description
This attribute designates the type of unnamed variable for its MMS access.
The MMS types that correspond to the accessed objects are listed below:
Unnamed Variable
SYi
Bi
Wi,j
Wi
DWi
CWi
CDWi
SWi
MMS Type
Boolean
Boolean
Boolean
Integer16
Integer32
Integer16
Integer32
Integer16
__________________________________________________________________________________________
3 / 1 2
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
3.4-4 Named Variable Object Description
A named variable is designated in the PLC by a symbol. The symbol is defined in the
PLC application and managed in the station symbol data base under XTEL. The table of application symbols is built by PL7-MMS (refer to Divider E).
The description below is taken from the MMS standard.
Variable Name =
This attribute designates the named variable.
MMS Deletable = FALSE
This attribute indicates that the named variable cannot be deleted.
Type Description
This attribute designates the type of named variable by its MMS access.
The MMS types corresponding to the accessed objects are shown opposite:
A
__________________________________________________________________________________________
3 / 1 3
A
__________________________________________________________________________________________
Named Variable Type MMS Type
System_Bit
Internal_Bit
Internal_Bit_Word
Internal_Word
Internal_Double_Word
Constant_Word
Constant_Double_Word
System_Word
Date_Time
String of Internal_Words
String of Constant_Words
(2048 Words max.)
String of Internal_Double_Words
String of Constant_Double_Words
(1024 Double_Words max.)
String of Internal_Bits
(2048 bits max.)
Boolean (default)
BitString1
Boolean (default)
BitString1
Boolean (default)
BitString1
Integer16 (default)
Unsigned16,
BitString16,
OctetString2,
VisibleString2
Integer32(default)
Unsigned32,
FloatingPoint
Integer16 (default)
Unsigned16,
BitString16,
OctetString2,
VisibleString2
Integer32 (default)
Unsigned32,
FloatingPoint
Integer16 (default)
Unsigned16,
BitString16,
OctetString2,
VisibleString2
Generalized_time (1)
OctetString2N (N=1 to 2048),
VisibleString2N (N=1 to 2048),
ARRAY [1..1024]:
Integer16,
Unsigned16,
BitString16,
VisibleString2
OctetString2,
STRUCTURE [1..16]:
Type simple,
Array (simple type) (*)
ARRAY [1..1024]:
Integer32(default)
Unsigned32,
FloatingPoint
BitStringN (N=1..2048),
ARRAY [1..1024]:
Boolean,
BitString1
__________________________________________________________________________________________
3 / 1 4
TSX Series 7 PLC MMS Modelization 3
__________________________________________________________________________________________
(1) The Generalized_time type follows MMS recommendations MMS. The named variable takes the predefined name M_DAYTIM.
(*) Type string limited to VisibleString2, OctetString2, BitString1 and BitString16.
A
Access Method = PUBLIC
This attribute specifies that a named variable is always available for public access.
3.4-5 Supported MMS Services
The table below lists the MMS services assigned to Variable objects.
MMS Server Services
Read one or more variables (16 max.)
MMS Service:
Write one or more variables (16 max.)
MMS Service:
Read
Write
Access to the attributes of one or more variables (16 max.)
MMS Service: GetVariableAccessAttributes
Unsolicited transmission of one or more variables
MMS Service: InformationReport (1)
(1): The programming of this service in the PL7-3 application is described in Divider F,
Sub-section 3.8.
__________________________________________________________________________________________
3 / 1 5
A
__________________________________________________________________________________________
__________________________________________________________________________________________
3 / 1 6
Conventions 4
__________________________________________________________________________________________
4.
Conventions
The following sections will describe the following elements for each service:
• Service parameters,
• The service processing procedure used by the OSI module and the PLC.
A
4.1
"Argument" Parameter
Defines the parameters of the request (REQ) and the indication (IND) for the service.
The values described are those sent by the MMS Client TSX Series 7 PLC (REQ) and expected (or possible) received by the MMS Server TSX Series 7 PLC.
For services with requests (REQ) that can be initiated by the MMS Server (Abort, Reject,
DownloadSegment, TerminateSequence, UnsolicitedStatus, InformationReport) the values described are those provided by the MMS Server to the remote MMS user.
4.2
"Result(+)" Parameter
Defines the response (RSP) and confirm (CNF) parameters that apply when the requested service is successful.
The values described are those sent by the MMS Client TSX Series 7 PLC (REQ) and expected (or possible) received by the MMS Server TSX Series 7 PLC.
4.3
"Result(-)" Parameter
Defines the error causes and codes assigned to a negative response to a service request.
Only additional error codes specific to this implementation are described.
For other error conditions, refer to the MMS standard.
4.2
Procedure
Each service uses execution functions in the MMS Server resulting in actions performed by the OSI interface module and the TSX Series 7 PLC.
This description informs the user of the responses to expect from the MMS Server to the
PLC for each MMS service (in nominal operation).
The procedures that apply to PL7-3/MMS when using MMS OFBs are described in
Divider F, Section 3.
__________________________________________________________________________________________
4 / 1
A
__________________________________________________________________________________________
__________________________________________________________________________________________
4 / 2
Context Management 5
__________________________________________________________________________________________
5.
Context Management
MMS communication is performed in three phases:
• The connection opening phase (association)
• The message exchange phase
• The connection closure phase
The context management services apply to the first and the last of these phases.
A
5.1
Initiate Service
The Initiate service lets a calling MMS user to build an environment for communication with the MMS Server depending on the respective resources and availability.
This service must be completed successfully before the calling MMS user can invoke or process MMS services in this environment.
5.1-1 MMS Calling Mode
This service lets the PL7-3/MMS application open an association with a remote MMS application.
a. Argument
Local Detail Calling = 7168
The maximum size in bytes proposed for MMS PDUs (Protocol Data Units).
Proposed Max Serv Outstanding Calling = 2 (M between 2 and 5)
The maximum number of transactions per association that the local application can manage in Server mode after receiving indication of confirmed services.
Proposed Max Serv Outstanding Called = 2 (M between 2 and 5)
The maximum number of transactions per association that the local application proposes to have managed by the remote MMS Server on receiving indication of confirmed services.
The value of M depends on the number of associations configured in PL7-OSI (refer to
PICS Appendix G, Sub-section 1.4).
__________________________________________________________________________________________
5 / 1
A
__________________________________________________________________________________________
Proposed Data Structure Nesting Level = 2
Maximum nesting levels when defining all types of data:
• Simple type data (Nest=0),
• Tables of simple type data elements (Nest=1),
• Simple data field arrays (Nest=1),
• Tables of data field arrays (Nest=2),
• Tables of simple data elements (Nest=2).
Proposed Version Number = 1 (IS)
MMS protocol version level.
Proposed Parameter CBB = VNAM-STR1-STR2
Set of conformity blocks negotiated for the supported variables.
VNAM corresponds to support for named variables,
STR1 corresponds to support for tables,
STR2 corresponds to support for structures.
Services Supported Calling = Services supported by the local MMS application.
Set of services that the local MMS application supports for this association. An MMS service is "supported" by an MMS application if it can receive the primitive (IND) and generate a response (RSP) when using a confirmed service.
This parameter is represented by a string of bits (85) where each bit represents a service.
The services "supported" by the local MMS application are defined in Divider A, Subsection 2.4.
b. Result(+)
The RESULT(+) parameter is not described in this specific case as all parameters are negotiated, therefore there are no restrictions other than the need to respect MMS standard negotiation rules.
c. Result(-)
Refer to the MMS standard.
All types of error are returned to the PL7-3/MMS application.
__________________________________________________________________________________________
5 / 2
Context Management 5
__________________________________________________________________________________________
5.1-2 MMS Called Mode
This service lets an MMS user open an MMS association with the TSX Series 7 PLC.
A a. Argument
The ARGUMENT parameter is not described in this specific case, as all parameters are negotiated, therefore there are no specific restrictions.
b. Result(+)
The calling MMS user proposes their operating values as the argument for the INITIATE
INDICATION service.
The table below shows the values of the parameters negotiated by the MMS Server and sent in INITIATE RESPONSE(+) after receiving the connection request from the MMS
Server.
Local Detail Called = Minimum (7168, Proposed Max Segment Size)
Negotiated size of MMS PDUs (Protocol Data Units).
If the Local Detail Calling parameter is not present in the connection request, the value returned is 7168 (bytes).
Negotiated Max Serv Outstanding Calling = Proposed Max Serv Outstanding
Calling
The maximum number of transactions that the calling MMS user can manage at any time on this association following the reception of confirmed service indications.
Negotiated Max Serv Outstanding Called = Minimum (M, Proposed Max Serv
Outstanding Called)
The maximum number of transactions that the local application proposes to have managed by the remote MMS Server on receiving indication of confirmed services.
The value of M depends on the number of associations configured in PL7-OSI (refer to
PICS Appendix G, Sub-section 1.4).
Negotiated Data Structure Nesting Level = Minimum (2, Proposed Data
Structure Nesting Level)
__________________________________________________________________________________________
5 / 3
A
__________________________________________________________________________________________
Maximum nesting levels when defining all types of data:
• Simple type data (Nest=0),
• Tables of simple type data elements (Nest=1),
• Simple data field arrays (Nest=1),
• Tables of data field arrays (Nest=2),
• Tables of simple data elements (Nest=2).
Negotiated Version Number = Minimum (0,1) (DIS,IS)
MMS protocol version.
Negotiated Parameter CBB = Intersection (VNAM-VADR-STR1-STR2-VALT,
Proposed Parameter CBB)
Set of conformity blocks negotiated for the supported variables.
VNAM corresponds to support for named variables,
STR1 corresponds to support for tables,
STR2 corresponds to support for structures.
VALT corresponds to alternate access for variables STR1 and STR2.
Services Supported Called = Services supported by the local application
Set of services that the local MMS Server supports for this association. An MMS service is "supported" by an MMS application if it can receive the primitive (IND) and generate a response (RSP) when using a confirmed service.
This parameter is represented by a string of bits (86) where each bit represents a service.
The services "supported" by the local MMS application are defined in Divider A, Subsection 2.4.
c. Result(-)
Refer to the MMS standard.
d. Procedure
Processing of this service is entirely local in the MMS Server of the OSI interface module.
__________________________________________________________________________________________
5 / 4
Context Management 5
__________________________________________________________________________________________
5.2
Conclude Service
The Conclude service performed negotiated deletion of the MMS communication environment, between the MMS caller and the MMS Server (called). This service ensures that there are not losses of data during transmission when the environment is closed.
Once this service is performed successfully, no new MMS service can be invoked on this association.
A
5.2-1 MMS Calling Mode
This service lets the PL7-3/MMS application close an MMS association opened with a remote MMS application.
a. Argument
None.
b. Result(+)
None.
c. Result(-)
Refer to the MMS standard.
All types of error are returned to the PL7-3/MMS application.
5.2-2 MMS Called Mode
This service lets the MMS user close an MMS association opened on a TSX Series 7
PLC.
a. Argument
None.
b. Result(+)
None.
c. Result(-)
Refer to the MMS standard.
d. Procedure
Processing of this service is entirely local in the MMS Server of the OSI interface module.
__________________________________________________________________________________________
5 / 5
A
__________________________________________________________________________________________
5.3
Abort Service
The Abort service immediately interrupts exchanges without any negotiation on the
MMS communication environment, between the MMS user and MMS Server. This service may cause information to be lost during transmission.
This service is not confirmed.
Once invoked successfully, no new MMS service can be invoked using this association.
5.3-1 MMS Calling Mode
This service lets the PL7-3/MMS application immediately interrupt any MMS association opened with a remote MMS application.
a. Argument
Locally Generated = TRUE or FALSE
This parameter indicates whether the Abort request is local (TRUE), i.e. generated by the TSX Series 7 PLC or remote (FALSE), i.e. generated by the remote application.
5.3-2 MMS Called Mode
This service lets the MMS user close an MMS association opened on a TSX Series 7
PLC.
a. Argument
Locally Generated = TRUE or FALSE
This parameter indicates whether the Abort request is local (TRUE), i.e. generated by the TSX Series 7 PLC or remote (FALSE), i.e. generated by the remote application.
When the MMS Server invokes the service, the value of the parameter received by the
MMS user for ABORT INDICATION will be FALSE.
b. Procedure
Processing of this service is entirely local in the MMS Server of the OSI interface module.
__________________________________________________________________________________________
5 / 6
Context Management 5
__________________________________________________________________________________________
5.4
Reject Service
The Reject service is invoked by the MMS service provider that notifies an MMS user of a protocol error detected by the communication protocol.
This service is not confirmed.
A
5.4-1 MMS Client Mode a. Argument
Detected Here = TRUE or FALSE
This parameter indicates that the protocol error was detected by the local system
(TRUE) or remote system (FALSE).
Original Invoke ID
This parameter indicated (where possible) the invocation number of the PDU (Protocol
Data Unit) found in error.
Reject PDU Type
Specifies the type of PDU found in error.
This value is returned to the PL7-3/MMS application.
Refer to the MMS standard.
Reject Code
Reason for rejection by the PDU depending in its type.
This value is returned to the PL7-3/MMS application.
Refer to the MMS standard.
__________________________________________________________________________________________
5 / 7
A
__________________________________________________________________________________________
5.4-2 MMS Server Mode a. Argument
Detected Here = TRUE or FALSE
This parameter indicates that the protocol error was detected by the local TSX Series 7 system (TRUE) or the remote MMS application (FALSE).
Original Invoke ID
This parameter indicates (where possible) the invocation number of the PDU (Protocol
Data Unit) in error.
Reject PDU Type
Specifies the type of PDU found in error.
Refer to the MMS standard.
Reject Code
Reason for rejection by the PDU depending on its type.
Refer to the MMS standard.
b. Procedure
Processing of this service is entirely local in the MMS Server of the OSI interface module.
__________________________________________________________________________________________
5 / 8
VMD Support Services 6
__________________________________________________________________________________________
6.
VMD Support Services
The VMD support services let the MMS user:
• Know the status (solicited and unsolicited) of the TSX Series 7 station,
• Know the identity and the characteristics of the TSX Series 7 PLC,
• Acquire the list of names of the various MMS objects in the TSX Series 7 PLC.
In MMS Client mode, the PL7-3/MMS application can:
• Request the status of a remote device,
• Receive the unsolicited status of a remote device.
A
6.1
Status Service
6.1-1 MMS Client Mode
The Status service lets the PL7-3/MMS application know the status of a remote device.
a. Argument
Extended Derivation = FALSE
A simple type approach is used when addressing the remote MMS application to determine the status of the device (no extended tests, such as self-test types requested).
b. Result(+)
VMD Logical Status
VMD Physical Status
The values expected for these parameters are those defined as possible by the MMS standard.
These values are returned to the PL7-3/MMS application.
Local Detail
The value of this string of 128 bits depends on the implementation of the remote device.
This value is returned to the PL7-3/MMS application.
c. Result (-)
Refer to the MMS standard.
All error types are returned to the PL7-3/MMS application.
__________________________________________________________________________________________
6 / 1
A
__________________________________________________________________________________________
6.1-2 MMS Server Mode
The Status Service lets the calling MMS user know the status of the TSX Series 7 PLC station.
a. Argument
Extended Derivation
Not used.
b. Result(+)
VMD Logical Status
VMD Physical Status
These paramters are described in Divider A, Sub-section 3.1.
Local Detail
This paramter is described in Divider A, Sub-section 3.1.
c. Result(-)
Refer to the MMS standard.
d. Procedure
The MMS Server sends a UNI-TE READ_CPU request to the PLC to find out the status of the TSX Series 7 PLC station.
__________________________________________________________________________________________
6 / 2
VMD Support Services 6
__________________________________________________________________________________________
6.2
Unsolicited Status Service
6.2-1 MMS Client Mode
The Unsolicited Status service lets the PL7-3/MMS application receive unsolicited status information from a remote device.
This service is not confirmed.
a. Argument
VMD Logical Status
VMD Physical Status
The values expected for these parameters are those defined as possible in the MMS standard.
These values are returned to the PL7-3/MMS application.
Local Detail
The value of this string of 128 bits depends on the implementation of the remote device.
This value is returned to the PL7-3/MMS application.
A
6.2-2 MMS Server Mode
The Unsolicited Status service lets the MMS Server send the unsolicited status of the
TSX Series 7 PLC station.
This service is not confirmed.
a. Argument
VMD Logical Status
VMD Physical Status
These parameters are described in Divider A, Sub-section 3.1.
Local Detail
This parameter is described in Divider A, Sub-section 3.1.
__________________________________________________________________________________________
6 / 3
A
__________________________________________________________________________________________
6.3
Identify Service
The Identify service lets a calling MMS user acquire data on the identity and characteristics of the TSX Series 7 PLC station.
This service is only supported in MMS Server mode.
a. Arguments
None.
b. Result(+)
Vendor Name
Model Name
Revision
These parameters are described in Divider A, Sub-section 3.1-1.
List of Abstract Syntaxes
Not used.
c. Result(-)
Refer to the MMS standard.
d. Procedure
The MMS Server sends a UNI-TE READ_CPU request to the PLC to find out the identity of the TSX Series 7 PLC station.
__________________________________________________________________________________________
6 / 4
VMD Support Services 6
__________________________________________________________________________________________
6.4
GetNameList Service
The GetNameList service lets the MMS user that invokes the service gain access to all or part of the list of MMS object names defined in the TSX Series 7 PLC station.
This service is only supported in MMS Server mode.
a. Argument
Extended Object Class = Object-Class
This parameter defines the "extended" class of object names that should be sent back by the MMS SERVER. The expected value designates the "MMS 9506 Standard" class.
Object Class = Named Variable or Domain or Program Invocation
Specifies the class of object names that should be returned by the MMS Server.
These objects are described in Divider A, Section 3.
CS Object Class
Not used.
A
Object Scope = VMD-specific or DOMAIN-specific or AA-specific
The scope of the objects whose names are returned.
The scope of PLC objects is described in Divider, Sub-section 3.4.
Domain Name
Domain name when Object Scope equals DOMAIN-specific.
The domain name is specified in Divider A, Sub-section 3.2-1.
Continue After
Designates the name of the object after which the names in the list should be sent back.
b. Result(+)
List of Identifier
__________________________________________________________________________________________
6 / 5
A
__________________________________________________________________________________________
This parameter contains the list of object name of the class and scope specified by the
Object Class and Object Scope parameters, within the limits defined by the Continue
After parameter.
If no object exists, the list will be blank.
More Follows = TRUE or FALSE
This parameter indicates whether it is necessary (TRUE) to perform new requests using the GetNameList service to obtain the full list of names required.
c. Result(-)
Error Class = VMD-STATE
Error Code = VMD-STATE-CONFLICT
Additional Code
TEMPORARILY_UNAVAILABLE (1)
Loading table of symbols
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
INVALID_DOMAIN_NAME (1)
Domain name does not designate a domain that exists.
Error Code = OBJECT_ACCESS_UNSUPPORTED
Additional Code
INVALID_EXTENDED_OBJECT_CLASS (1)
Value of the "Extended Object Class" parameter is incorrect
INVALID_OBJECT_CLASS (2)
Value of the "ObjectClass" parameter is incorrect
INVALID_OBJECT_SCOPE (3)
Value of the "Object Scope" parameter is incorrect
Error Class = SERVICE
Error Code = CONTINUATION-INVALID
The "Continue After" parameter does not designate a known object.
d. Procedure
This service is processed locally in the OSI interface module.
__________________________________________________________________________________________
6 / 6
Domain Management Services 7
__________________________________________________________________________________________
7.
Domain Management Services
The domain management services let the MMS user gain access to the PLC station
(.APP), i.e.:
• Download the station application to the TSX Series 7 PLC
• Archive the station application from the TSX Series 7 PLC
• Acquire the characteristics of the station application
• Delete the station application
A
7.1
InitiateDownLoadSequence Service
This service is invoked by the calling MMS user to request that the MMS Server create the named domain and start the download sequence.
This service is only supported in MMS Server mode a. Argument
Domain Name
This parameter is described in Sub-section 3.2-1.
List of Capabilities
Not used.
Sharable = FALSE
Refer to the description of the DOMAIN object in Divider A, Sub-section 3.2-1.
b. Result(+)
None.
__________________________________________________________________________________________
7 / 1
A
__________________________________________________________________________________________ c. Result(-)
Error Class = DEFINITION
Error Code = OBJECT_EXIST
Additional Code
DOMAIN_ALREADY_EXIST (1)
The station application cannot be downloaded (the PLC is in RUN)
Error Code = OBJECT-UNDEFINED
Additional Code
INVALID_DOMAIN_NAME (1)
Incorrect domain name
Error Class = OTHERS
Error Code = INITIATE_DOWNLOAD_SEQUENCE (2)
Additional Code INVALID_SHARABLE_ATTRIBUTE
(2)
The "Sharable" parameter should be set to FALSE
Error Class = SERVICE
Error Code = OBJECT_STATE CONFILICT
Additional Code = INVALID_DOMAIN_STATE (2)
The domain state is incorrect
Error Class = VMD_STATE
Error Code = DOMAIN_TRANSFER_PROBLEM
Additional Code = DOWNLOAD_IMPOSSIBLE (6)
Remote downloading refused by the PLC d. Procedure
The OSI module MMS Server processes this service using the following operations:
• PLC reservation (UNI-TE RESERVE request),
• Acquisition of the station application status (UNI-TE IDENTIFICATION_OBJECT request (appli_station)),
• Initialize downloading to the PLC (UNI-TE OPEN_DOWNLOAD_SEQUENCE.req
request)
__________________________________________________________________________________________
7 / 2
Domain Management Services 7
__________________________________________________________________________________________
7.2
DownLoadSegment Service
This service is invoked by the MMS Server so that the calling MMS user can transfer a segment of station application (.APP) data to it for downloading.
This service is only supported in MMS Server mode.
a. Argument
Domain Name
This parameter is described in Divider A, Sub-section 3.2-1.
b. Result(+)
Load Data
Data (byte string) to load.
More Follows = TRUE or FALSE
This parameter indicates that there is more (TRUE) or no more (FALSE) data to download.
c. Result(-)
Refer to the MMS standard.
d. Procedure
The OSI module MMS Server processes this service using the following operations:
• Sending a DOWNLOAD_SEGMENT.req until a DOWNLOAD_SEGMENT.cnf is received with the parameter More Follows - FALSE,
• Segmenting data received with DownLoadSegment.Cnf into
N UNI-TE WRITE_DOWNLOAD_SEGMENT requests that are then sent to the PLC.
A
__________________________________________________________________________________________
7 / 3
A
__________________________________________________________________________________________
7.3
TerminateDownLoadSequence Service
This service is invoked by the MMS Server to indicate to the calling MMS user that the download sequence is complete.
This service is only supported in MMS Server mode.
a. Argument
Domain Name
This parameter is described in Divider A, Sub-section 3.2-1.
Discard = TRUE or FALSE (DIS) or SERVICE ERROR (IS)
The DIS version of this parameter indicates that a problem was (TRUE) or was not
(FALSE) detected during a domain download action.
If the value is TRUE, the station application is not validated.
The IS version of this parameter is a Service Error typr.
Error Class = VMD_STATE
Error Code = DOMAIN_TRANSFER_PROBLEM
Additional Code = INCONSISTENT_DATA (2)
The downloaded data is incoherent because:
• Their length is null,
• The PLC declared them incoherent during downloading,
• The PLC declared then invalid at the end of the download procedure.
Additional Code = WRITE_SEG_IMPOSSIBLE (4)
The PLC cannot write the downloaded data.
Additional Code = READ_SEG_IMPOSSIBLE (5)
The PLC cannot read the data.
Error Code = VMD_STATE_CONFLICT
No Additional Code, the PLC has lost the reservation.
Error Class = OTHERS
Error Code = DATE_CODED (1)
Downloaded data in coded format is not supported.
__________________________________________________________________________________________
7 / 4
Domain Management Services 7
__________________________________________________________________________________________ b. Result(+)
None.
c. Result(-)
Refer to the MMS standard.
d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• On receiving DownLoadSegment.Cnf with the "More Follows = FALSE" parameter, t he sy st em s ends t he PLC a close download seq uenc e (UNI-TE
CLOSE_DOWNLOAD_SEQUENCE request),
• Releases PLC reservation (UNI-TE RELEASE request),
• Sends a TERMINATE_DOWNLOAD_SEQUENCE.req request,
• Receives TERMINATE_DOWNLOAD_SEQUENCE.cnf
A
__________________________________________________________________________________________
7 / 5
A
__________________________________________________________________________________________
7.4
InitiateUpLoadSequence Service
This service is invoked by the calling MMS user to request that the MMS Server initiate the upload sequence on the station application (.APP).
This service is only supported in MMS Server mode.
a. Argument
Domain Name
This parameter is described in Divider A, Sub-section 3.2-1.
b. Result(+)
ULSM ID
Identifies the Upload State Machine object. The MMS Server only supports a single upload at one time.
List of Capabilities
Not used.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
DOMAIN_NON_EXISTENT (2)
Incorrect domain name or invalid station application.
__________________________________________________________________________________________
7 / 6
Domain Management Services 7
__________________________________________________________________________________________
Error Class = SERVICE
Error Code = PRIMITIVES_OUT_OF_SEQUENCE
Error Code = OBJECT_STATE_CONFLICT
Additional Code
UPLOAD_IMPOSSIBLE (6)
"Protected" station application
Error Code = PRIMITIVES_OUT_OF_SEQUENCE
A save action is already in progress
A d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• PLC reservation (UNI-TE RESERVE request),
• Acquisition of the station application status (UNI-TE IDENTIFICATION_OBJECT request (appli_station)),
• Initialization of the PLC upload sequence (UNI-TE OPEN_UPLOAD_SEQUENCE.req
request).
7.5
UpLoadSegment Service
This service is invoked by the calling MMS user to request that the MMS Server transfer a data segment from the station application (.APP) to be saved.
This service is only supported in MMS Server mode.
a. Argument
ULSM
Identifies the number of the save in progress.
__________________________________________________________________________________________
7 / 7
A
__________________________________________________________________________________________ b. Result(+)
Load Data
Data (byte string) to save.
More Follows = TRUE or FALSE
This parameter indicates that the remains (TRUE) or not (FALSE) data to save.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
USLM_NON_EXISTENT (5)
The designated USLM does not exist
Error Class = SERVICE
Error Code = PRIMITIVE_OUT_OF_SEQUENCE
Save is completed or Uploadsegment.cnf was received previously
Error Class = VMD_STATE
Error Code = DOMAIN_TRANSFER_PROBLEM
Additional Code = READ_DATA_SEGMENT_IMPOSSIBLE (5)
The PLC cannot read the data.
d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Stringing the data received from the PLC in response to the N
UNI-TE READ_UPLOAD_SEGMENT requests (up to the maximum size of the MMS
PDU) and sending UploadSegment.Rsp to the remote MMS system.
__________________________________________________________________________________________
7 / 8
Domain Management Services 7
__________________________________________________________________________________________
7.6
TerminateUpLoadSequence Service
This service is invoked by the calling MMS user to indicate to the MMS SERVER, the end of the upload sequence.
This service is only supported in MMS Server mode.
A a. Argument
ULSM ID
Identifies the number of the save to complete.
b. Result(+)
None c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
USLM_NON_EXISTENT (5)
The designated USLM does not exist
Error Class = VMD_STATE
Error Code = DOMAIN_TRANSFER_PROBLEM
Additional Code
UPLOAD_NON_FINISHED (3)
The finished indication precedes the end of the upload
__________________________________________________________________________________________
7 / 9
A
__________________________________________________________________________________________ d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• On reception of TerminateUploadSegment.Ind, send the end of upload message to the PLC (UNI-TE CLOSE_UPLOAD_SEQUENCE request),
• Release PLC reservation (UNI-TE RELEASE request).
7.7
DeleteDomain Service
This service lets the calling MMS user to request that the MMS Server delete the station application (.APP).
This service is only supported in MMS Server mode.
a. Argument
Domain name
This parameter is described in Divider A, Sub-section 3.2-1.
b. Result(+)
None c. Result(-)
Error Class = DEFINITION
Error Code = OBJECT_UNDEFINED
Additional Code
DOMAIN_UNDEFINED (2)
The designated domain does not exist
__________________________________________________________________________________________
7 / 1 0
Domain Management Services 7
__________________________________________________________________________________________
Error Class = SERVICE
Error Code = OBJECT_STATE_CONFLICT
Additional Code
DOMAIN_NOT_DELETABLE (1)
The domain cannot be deleted
INVALID_DOMAIN_STATE (2)
The domain state does not allow deletion
UPLOAD_IN_PROGRESS (5)
Domain upload in progress
A d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Reserving the PLC (UNI-TE RESERVE request),
• Acq ui ring th e st ation ap pl i cation (DOMAIN) st at e, usi ng t he
UNI-TE IDENTIFICATION_OBJECT(appli_Station) request sent to the PLC,
• Acquiring the program (PI) state, using the UNI-TE STATUS request sent to the PLC,
• Invalidating the station application (UNI-TE INVALID_APPLI (appli_station) request,
• Physically deleting the station descriptor (UNI-TE OPEN_DOWNLOAD request followed by the UNI-TE WRITE DOWNLOAD request from 64 bytes to 0,
• Releasing PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
7 / 1 1
A
__________________________________________________________________________________________
7.8
GetDomainAttributes Service
This service lets the MMS user request that the MMS Server provide the value of all attributes in the specified domain.
This service is only supported in MMS Server mode.
a. Arguments
Domain Name
This parameter is described in Divider A, Sub-section 3.2-1.
b. Result(+)
List of Capabilities
Not used.
State
MMS Deletable
Sharable
List of PIs
Upload In Progress
These parameters are described in Sub-section 3.2-1.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
DOMAIN_NON_EXISTENT (2)
Incorrect domain name d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Acquisition of the state of the station application using the
UNI-TE IDENTIFICATION_OBJECT(appli_station) request sent to the PLC and the program (UNI-TE STATUS request),
• Acquisition of the state of the application using the UNI-TE STATE request sent to the
PLC.
__________________________________________________________________________________________
7 / 1 2
Program Invocation Management Services 8
__________________________________________________________________________________________
8.
Program Invocation Management Services
The program invocation management services let the MMS user access the PL7-3 sequential control program, i.e. to:
• Create and delete the PL7-3 program,
• Start and stop the PL7-3 program,
• Acquire PL7-3 program characteristics.
A
8.1
CreateProgramInvocation Service
This service lets the calling MMS user create a PI in the MMS Server. This service is only supported in MMS Server mode.
a. Argument
Program Invocation Name
List of Domain Names
Reusable
This parameter is described in Divider A, Sub-section 3.3-1.
Monitor
Not used.
b. Result(+)
None.
__________________________________________________________________________________________
8 / 1
A
__________________________________________________________________________________________ b. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
DOMAIN_NON_EXISTENT (2)
Incorrect domain name assigned
Error Class = DEFINITION
Error Code = OBJECT_EXIST
Additional Code
PI_ALREADY_EXISTS (2)
The designated PI already exists
Error Code = OBJECT_UNDEFINED
Additional Code
INVALID_PI_NAME (4)
The assigned PI name is incorrect
Error Class = SERVICE
Error Code = OBJECT_STATE_CONFLICT
Additional Code
INVALID_DOMAIN_STATE (2)
Incorrect assigned domain state
Error Class = OTHERS
Error Code = CREATE_PROGRAM_INVOCATION
Additional Code
INVALID_REUSABLE_ATTRIBUTE (3)
The value of this parameter must be TRUE
Error Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
No Additional Code
The PI cannot be created in the PLC
__________________________________________________________________________________________
8 / 2
Program Invocation Management Services 8
__________________________________________________________________________________________ d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• PLC reservation (UNI-TE RESERVE request),
• Acquisition of the station application (UNI-TE IDENTIFI-CATION_OBJET(appli_station) request) and pr ogram (UNI-TE STATUS request) state,
• Validating the PL7-3 program (UNI-TE VALID_APPLI(appli_PL7) request),
• Releasing PLC reservation (UNI-TE RELEASE request).
A
8.2
DeleteProgramInvocation Service
This service lets the MMS delete a PI that exists in the MMS Server.
This service is only supported in MMS Server mode.
a. Argument
PI Name
This parameter is described in Divider A, Sub-section 3.3-1.
b. Result(+)
None.
__________________________________________________________________________________________
8 / 3
A
__________________________________________________________________________________________ c. Result(-)
Error Class = DEFINITION
Error Code = OBJECT_UNDEFINED
Additional Code
PI_UNDEFINED (2)
PI does not exist
Error Class = SERVICE
Error Code = OBJECT_STATE_CONFLICT
Additional
Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
No Additional Code
PI cannot be deleted from the PLC d. Procedure
The OSI module MMS Server processes the service using the following operations:
5 PLC reservation (UNI-TE RESERVE request),
5 Acquisition of the program status (UNI-TE STATUS request),
• Invalidating the PL7-3 program (UNI-TE INVALID_APPLI(appli_PL7) request),
• Releasing the PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
8 / 4
Program Invocation Management Services 8
__________________________________________________________________________________________
8.3
Start Service
This service lets the MMS user start the PL7-3 program. PI goes from IDLE to RUNNING state.
This service is only supported in MMS Server mode.
a. Argument
PI Name
This parameter is described in Divider A, Sub-section 3.3-1.
Execution Argument
Not used.
b. Result(+)
None.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_ACCESS_UNSUPPORTED
Additional Code = EXEC_ARGUMENT_UNSUPPORTED (9)
The argument execution parameter is not supported
Error Code = OBJECT_NON_EXISTENT
Additional Code
PI_NON_EXISTENT (3)
The designated PI does not exist
Error Class = OTHERS
Service Specific Information = (PI status)
Incorrect PI status
Error Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
Sans Additionnal Code
The PLC will not change to RUNNING state d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Reservation of the PLC (UNI-TE RESERVE request),
• Acquisition of the PL7-3 program status (UNI-TE STATUS request),
• Transmission to the PLC of the UNI-TE RUN request,
• Release the PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
8 / 5
A
A
__________________________________________________________________________________________
8.4
Stop Service
This service lets the MMS user stop the PL7-3 program. PI goes from RUNNING to
STOPPED state.
This service is only supported in MMS Server mode.
a. Argument
PI Name
This parameter is described in Divider A, Sub-section 3.3-1.
b. Result(+)
None.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
PI_NON_EXISTENT (3)
Designated PI does not exist
Error Class = OTHERS
Service Specific Information = (PI status)
Incorrect PI status
Error Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
No Additionnal Code
The PLC will not go to STOPPED d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Reservation of the PLC (UNI-TE RESERVE request),
• Acquisition of the PL7-3 program status (UNI-TE STATUS request),
• Transmission to the PLC of the UNI-TE RUN request,
• Release the PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
8 / 6
Program Invocation Management Services 8
__________________________________________________________________________________________
8.5
Resume Service
This service lets the MMS user resume the PL7-3 program when it is stopped. PI goes from STOPPED to RUNNING state.
This service is only supported in MMS Server mode.
a. Argument
PI Name
This parameter is described in Divider A, Sub-section 3.3-1.
Execution Argument
Not used.
b. Result(+)
None.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_ACCESS_UNSUPPORTED
Additional Code = EXEC_ARGUMENT_UNSUPPORTED (9)
The argument execution parameter is not supported
Error Code = OBJECT_NON_EXISTENT
Additional Code
PI_NON_EXISTENT (2)
Designated PI does not exist
Error Class = OTHERS
Service Specific Information = (PI status)
Incorrect PI status
Error Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
No Additionnal Code
The PLC will not go to RUNNING state d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Reservation of the PLC (UNI-TE RESERVE request),
• Acquisition of the PL7-3 program status (UNI-TE STATUS request),
• Transmission to the PLC of the UNI-TE RUN request,
• Release the PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
8 / 7
A
A
__________________________________________________________________________________________
8.6
Reset Service
This service lets the MMS user re-initialize the PL7-3 program after stopping it. PI goes from STOPPED to IDLE state.
This service is only supported in MMS Server mode.
a. Argument
PI Name
This parameter is described in Divider A, Sub-section 3.3-1.
b. Result(+)
None.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
PI_NON_EXISTENT (3)
Designated PI does not exisst
Error Class = OTHERS
Service Specific Information = (PI status)
Incorrect PI status
Error Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
No Additionnal Code
The PLC will not go to IDLE state d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Reservation of the PLC (UNI-TE RESERVE request),
• Acquisition of the PL7-3 program status (UNI-TE STATUS request),
• Invalidation of the PL7-3 program (UNI-TE INVALID_APPLI(appli_PL7) request,
• Validation of the PL7-3 program (UNI-TE VALID_APPLI(appli_PL7) request,
• Release the PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
8 / 8
Program Invocation Management Services 8
__________________________________________________________________________________________
8.7
GetProgramInvocationAttributes Service
This service lets the MMS user request that the MMS Server supply the value of all of the attributes of the specified program.
This service is only supported in MMS Server mode.
a. Argument
PI Name
This parameter is described in Divider A, Sub-section 3.3-1.
b. Result(+)
State
List of Domain Names
MMS Deletable
Reusable
This parameter is described in Divider A, Sub-section 3.3-1.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_NON_EXISTENT
Additional Code
PI_NON_EXISTENT (3)
Designated PI does not exist
A d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Reservation of the PLC (UNI-TE RESERVE request),
• Acquisition of the PL7-3 program status (UNI-TE STATUS request),
• Release the PLC reservation (UNI-TE RELEASE request).
__________________________________________________________________________________________
8 / 9
A
__________________________________________________________________________________________
__________________________________________________________________________________________
8 / 1 0
Variable Access Services 9
__________________________________________________________________________________________
9.
Variable Access Services
The variable access services let the MMS user access PLC application variables, i.e.
to:
• Read or write one or more PL7-3 program variables,
• Acquire the characteristics of one or more PL7-3 program variables,
• Receive unsolicited variables from the PL7-3/MMS program.
In MMS Client mode, the PL7-3/MMS application can:
• Read and write remote MMS application variables,
• Receive unsolicited variables from the remote MMS application MMS.
A
9.1
Variable Access Specification Parameters
The table below shows the possible values for the Variable Access Specification parameter in the READ, WRITE and INFORMATION REPORT requests.
Variable Access Specification
Kind of Access = List of Variable
This parameter indicates access to a list of variables.
Kind of Access = List of Variable
Variable Specification
Kind of Variable = NAMED or ADDRESS
In MMS Client mode, the type of variable is always NAME.
In the MMS Server mode, the ADDRESS variable type is restricted to simple type variable READ/WRITE services.
Kind of Variable = NAMED
Name Scope = VMD-Specific or DOMAIN-Specific or AA-Specific
Scope of the named variable.
The scope of PLC variables is described in Divider A, Sub-section 3.4.
Notes:
Select access is only possible in MMS Server mode for READ and WRITE services.
Select access to a "Programmed" variable requires programming a MSEMA OFB in the PL7-3 application.
__________________________________________________________________________________________
9 / 1
A
__________________________________________________________________________________________
Domain Identifer
Domain name when DOMAIN-Specific.
The domain name is described in Divider A, Sub-section 3.2-1.
Item Identifer
Name of the variable.
The named variable is described in Divider A, Sub-section 3.4-4.
Kind of Variable = ADDRESS
Kind of Address = SYMBOLIC-ADDRESS
The unnamed variable uses a symbolic address.
Symbolic Address
Unnamed objects and the symbolic addressing they support are described in
Divider A, Sub-section 3.4-3.
Kind of Access = List of Variable
Alternate Access
Component Name
Not used.
Kind of selection = Select Alternate Access or Select Access
This parameter indicates whether the specification allows for:
• Select Access,
• Select Alternate Access for Nesting Levels greater than 1.
Access Selection = Component or Index or Index Range (low, size)
Indicates the select access choice made:
• Fields in a structure
• Index in a table
• Field of indexes in a table (low index, size of range).
__________________________________________________________________________________________
9 / 2
Variable Access Services 9
__________________________________________________________________________________________
9.2
Access Result Parameters
The table below describes the possible values of the "Access Result" parameter for the
READ, WRITE and INFORMATION REPORT services.
Access Result
Success = TRUE or FALSE
This parameter indicates that access to each variable was made correctly.
Data Access Error
If Success = FALSE, this parameter indicates the reason for the failure to access each variable.
The various possible values are given in Sub-section 9.2-2.
Data
Kind of Data = SIMPLE or ARRAY or STRUCTURE
If Success = TRUE, this parameter gives the result of access to each variable.
Kind of Data = Simple
Class Size
Octet_string
Boolean
Integer
Unsigned
Bit-string
Floating-point
Visible-string
Generalized_time
4096 bytes max.
16, 32 bits
16, 32 bits
2048 bits max.
32 bits
4096 bytes max.
Simple type variable.
Kind of Data = ARRAY
List of Data
Table type variable. The table elements can be simple or structure type variables (refer to Divider A, Sub-section 2.3-2, for information on the types supported in MMS Client and
Server modes).
__________________________________________________________________________________________
9 / 3
A
A
__________________________________________________________________________________________
Kind of Data = STRUCTURE
List of Data
Structure type variable. The structure fields can be simple or table type fields (refer to
Divider A, Sub-section 2.3-2, for information on the types supported in MMS Client and
Server modes).
9.2-2 Error Codes
The "Data Access Error" codes for the "Access Result" parameter may be returned in response to the Read or Write services when a problem occurs that inhibits execution of access to one or more variables.
Description Values
Data Access Error
2
5
6
7
Table of symbols not loaded or currently being downloaded to the module.
Access to the programmed variable interrupted after a reset of the
MSEMA OFB.
Format of the symbolic address of a variable (VADR) not supported or not present in the PL7-3 configuration.
MMS type data not supported.
Incoherence between the definition of the variable in the table of server symbols and the definition of data or of alternate access in the
Write request:
- The type of variable is different from the that of the data,
- For a table or structure type variable, the number of elements or fields of the variable is different from that of the data,
- The number of alternative accesses to the variable is incoherent in relation to the data description.
__________________________________________________________________________________________
9 / 4
Variable Access Services 9
__________________________________________________________________________________________
Valeurs
Data Access Error
8
Meaning
Incoherence between the definition of the variable in the table of server symbols and the definition of data or of alternate access in the
Read or Write request:
- Alternate access to a variable that is not a table or structure type,
- Alternate access by index or index range that exceeds the limits of a table defined in the table of symbols,
- Alternate access to structure field name that does not exist in the definition of the variable in the table of symbols,
- Alternate access by index or index range, to a variable defined as a structure in the table of symbols,
- Alternate access by component to a variable defined as a table in the table of symbols.
Problems when elaborating the Information_Report.req primitive
(memory, etc.). Contact Telemecanique technical support.
9
10
Attribute used for defining the variable in the Read or Write requests not supported (values not supported in "Kind of Access", "Scope",
"Kind of Address"),
- Write access not supported for PL7-3 CWi, CDWi and Wi,j objects,
- Alternate access in write is not supported for Boolean table or
Bitstring1 type variables,
- Alternate access to variables by address (VADR) not supported.
Access to a named variable not defined in the table of server symbols.
The name of the domaine assigned to a named variable of domain scope is invalid.
A
__________________________________________________________________________________________
9 / 5
A
__________________________________________________________________________________________
9.3
Read Service
9.3-1 MMS Client Mode
This service lets the PL7-3/MMS application read one or more variables from a remote
MMS application.
a. Argument
Specification with Result = FALSE
This parameter indicates that the "Variable Access Specification" parameter must not be a part of the Result(+) response.
Variable Access Specification
This parameter is described in Divider A, Sub-section 9.1-1.
a. Result(+)
Variable Access Specification
This parameter must not be present.
List of Access Result
Contains the list of requested variable values (at most the value of 4 variables).
c. Result(-)
Refer to the MMS specification.
All types of errors are returned to the PL7-3/MMS application.
__________________________________________________________________________________________
9 / 6
Variable Access Services 9
__________________________________________________________________________________________
9.3-2 MMS Server Mode
This service is used by an MMS user to request that the MMS Server return the value of one or more variables assigned to the VMD (the TSX Series 7 PLC station) or to the
DOMAIN (the station application .APP) or association AA.
a. Argument
Specification with Result = TRUE or FALSE
This parameter indicates that the "Variable Access Specification" parameter must
(TRUE) or not (FALSE) be a part of the response Result(+).
Variable Access Specification
This parameter is described in Divider A, Sub-section 9.1-1.
b. Result(+)
Variable Access Specification
This parameter is present if the value of the "Specification with Result" argument is
TRUE.
List of Access Result
Contains the list of requested variable values (at most, the value of 16 variables).
A c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_ACCESS_UNSUPPORTED
Additional Code
INVALID_KIND_OF ACCESS (5)
Incorrect "Kind of Access" parameter
INVALID_KIND_OF_VARIABLE (8)
Incorrect "Kind of Variable" parameter
__________________________________________________________________________________________
9 / 7
A
__________________________________________________________________________________________
Error Class = APPLICATION_REFERENCE
Error Code = CONTEXT_UNSUPPORTED
One of the CBB parameters used in the Read_Response (STR1, STR2, VALT, ...) parameter was not negociated when the association was first opened
Additional Code = (local error returned by MMS provider)
MM_041_MAX_NEST_EXCEEDED (41)
MM_042_VNAM_CBB_VIOL (42)
MM_043_VADR_CBB_VIOL (43)
MM_046_VALT_CBB_VIOL (46)
MM_049_STR1_CBB_VIOL (49)
MM_050_STR2_CBB_VIOL (50) d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Access in the OSI module to the named variables table of symbols,
• Tr ans missi on of t he UNI-TE R EAD _SYSTEM _BI T (for s yst em bits),
READ_SYSTEM_WORD (for system words) or READ_OBJECTS (for all other objects) to the PLC.
For "Programmed" variables, the UNI-TE request is only sent if an access authorization has been sent previously by an MSEMA OFB. If this is not the case, the MMS service will await execution. Communication on this association is then interrupted until the access authorization is received.
__________________________________________________________________________________________
9 / 8
Variable Access Services 9
__________________________________________________________________________________________
9.4
Write Service
9.4-1 MMS Client Mode
This service is used by the PL7-3/MMS application to modify one or more remote MMS application variables.
a. Argument
Variable Access Specification
This parameter is described in Divider A, Sub-section 9.1-1.
List of Data
This parameter contains the list of values to write (up to 4 values of variables).
b. Result(+)
List of Write Result
For each variable, this parameter indicates that the write was successful or the cause of failure.
Success = TRUE or FALSE
Data Access Error (if Success = FALSE)
Refer to the MMS standard for the error codes used.
A c. Result(-)
Refer to the MMS standard.
All error types are returned to the PL7-3/MMS application.
__________________________________________________________________________________________
9 / 9
A
__________________________________________________________________________________________
9.4-2 MMS Server Mode
This service is used by an MMS user to request that the MMS Server modify the values of one or more variables assigned to the VMD (the TSX Series 7 station), the DOMAIN
(the .APP station application) or to the AA association.
a. Argument
Variable Access Specification
This parameter is described in Divider A, Sub-section 9.1-1.
List of Data
This parameter contains the list of values to write (up to 16 values of variables).
b. Result(+)
List of Write Result
For each variable, this parameter indicates that the write was successful or the cause of failure.
Success = TRUE or FALSE
Data Access Error (if Success = FALSE)
Refer to the MMS standard for the error codes used.
c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_ACCESS_UNSUPPORTED
__________________________________________________________________________________________
9 / 1 0
Variable Access Services 9
__________________________________________________________________________________________
Additional Code
INVALID_KIND_OF ACCESS (5)
Incorrect "Kind of Access" parameter
Error Class = OTHERS
Error Code = WRITE
Additional Code
DATA_VAR_SPEC_MISMATCH (1)
The number of variables does not correspond to the nbr. of data objects to write
A d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• Access in the OSI module to the named variables table of symbols,
• Transmis sion of th e UNI- TE W RITE_SYSTEM _BIT ( for sy stem bits),
WRITE_SYSTEM_WORD (for system words) or WRITE_OBJECTS (for all other objects) to the PLC.
For "Programmed" variables, the UNI-TE request is only sent if an access authorization has been sent previously by an MSEMA OFB. If this is not the case, the MMS service will await execution. Communication on this association is then interrupted until the access authorization is received.
9.5
InformationReport Service
9.5-1 MMS Client Mode
This service is used by the PL7-3/MMS application to receive an unsolicited variable from a remote MMS application.
This service is not confirmed.
a. Argument
Variable Access Specification
This parameter is described in Divider A, Sub-section 9.1.
List of Access Result
Contains the list of values for the expected variable.
__________________________________________________________________________________________
9 / 1 1
A
__________________________________________________________________________________________
9.5-2 MMS Server Mode
This service lets the MMS Server send one or more unsolicited variables to a remote
MMS application.
This service is not confirmed.
a. Argument
Variable Access Specification
This parameter is described in Divider A, Sub-section 9.1-1.
List of Access Result
Contains the list of values for the expected variable.
9.6
GetVariableAccessAttributes Service
This service is used by an MMS user to request that the MMS Server return the attributes of a variable.
This service is only supported in MMS Server mode.
a. Argument
Kind of Variable = NAMED or UNNAMED
This parameter indicates whether a named or unnamed variable is selected.
Name
Address
These parameters are described in Divider A, Sub-section 9.1-1.
__________________________________________________________________________________________
9 / 1 2
Variable Access Services 9
__________________________________________________________________________________________ b. Result(+)
MMS Deletable = FALSE
These variables cannot be deleted.
Address
Specifies the address of the PUBLIC variable.
Type Specification
Describes type of variable, for a description of types refer to Sub-section 3.4-4.
A c. Result(-)
Error Class = ACCESS
Error Code = OBJECT_ACCESS_UNSUPPORTED
Additional Code
INVALID_OBJECT_SCOPE (3)
Incorrect "Name Scope" parameter
INVALID_ADDRESS (7)
Incorrect "ADDRESS" parameter
Error Code = OBJECT_NON_EXISTENT
Additional Code
DOMAIN_NON_EXISTENT (2)
Designated domain does not exist
VARIABLE_NON_EXISTENT (4)
Designated variable does not exist
Error Class = VMD_STATE
Error Code = VMD_STATE_CONFLICT
Additional Code
TEMPORARILY_UNAVAILABLE (1)
Cannot access table of symbols
__________________________________________________________________________________________
9 / 1 3
A
__________________________________________________________________________________________ d. Procedure
The OSI module MMS Server uses the following operations to process the service:
• For a named variable, access in the OSI module to the named variables table of symbols.
__________________________________________________________________________________________
9 / 1 4
Appendix 10
__________________________________________________________________________________________
10.1 Error Codes
General error codes
These error may be received with negative responses to a number of different services:
Error_Class = SERVICE_PREEMPT
Error_Code = TIMEOUT
The PLC does not answer.
Error_Class = RESOURCE
Error_Code = MEMORY_UNAVAILABLE
Insufficient memory resources available to process the message.
Error_Class = VMD_STATE
• Error_Code = VMD_OPERATIONAL_PROBLEM
The PLC has refused a message (internal message system problem).
• Error_Code = VMD_STATE_CONFLICT
- Additional_Code = TEMPORARILY_NON_EXECUTABLE (2)
The PLC state will not allow the service to be executed immediately (PLC already reserved, table of symbols being downloaded, etc.)
- No Additional_Code
The service cannot be executed as the PLC status will not allow it (reservation lost, inability to access PLC status, etc.).
Specific error codes
These error codes may be received in specific cases (on rece ption of
Download_Segment.ind or Terminate_Download_Sequence.ind, that are not supported in Client mode).
Error_Class = APPLICATION_REFERENCE
Error_Code = CONTEXT_UNSUPPORTED
Additional_Code = CLIENT_DOWNLOAD_UNSUPPORTED (256)
Downloading is not supported in MMS Client mode.
A
__________________________________________________________________________________________
1 0 / 1
A
__________________________________________________________________________________________
Codes
Error_Class = VMD_STATE
• Error_Code = VMD_STATE_CONFLICT
TEMPORARILY_UNAVAILABLE
TEMPORARILY_NON_EXECUTABLE
• Error_Code = VMD_OPERATIONAL_PROBLEM 2
• Error_Code = DOMAIN_TRANSFER_PROBLEM 3
INCONSISTENT_DATA
UPLOAD_NON_FINISHED
2
3
WRITE_SEG_IMPOSSIBLE
READ_DATA_SEGMENT_IMPOSSIBLE
DOWNLOAD_IMPOSSIBLE
Value Description
0
1
1
2
Access to variables is impossible as the table of symbols is being downloaded.
The service is temporaily non executable.
4
5
6
Incoherent downloaded data.
Upload interrupted prior to completion.
Cannot write data to the PLC.
Cannot read data from the
PLC.
Download operation refused by the PLC.
Error_Class = APPLICATION_REFERENCE
• Error_Code = CONTEXT_UNSUPPORTED
MM_041_MAX_NEST_EXCEEDED
MM_042_VNAM_CBB_VIOL
MM_043_VADR_CBB_VIOL
MM_046_VALT_CBB_VIOL
MM_049_STR1_CBB_VIOL
MM_050_STR2_CBB_VIOL
CLIENT_DOWNLOAD_UNSUPPORTED
1
4
41
42
43
46
49
50
256
Contents of Read_Response incompatible with the parameters negociated when the association was opened.
Downloading not supported in Client mode.
Error_Class = DEFINITION
• Error_Code = OBJECT_UNDEFINED
INVALID_DOMAIN_NAME
DOMAIN_UNDEFINED
PI_UNDEFINED
INVALID_PI_NAME
• Error_Code = OBJECT_EXISTS
DOMAIN_ALREADY_EXIST
PI_ALREADY_EXIST
2
1
1
2
3
4
5
1
2
Incorrect domain name.
Domain does not exist.
PI does not exist.
Incorrect PI name.
The domain already exists.
The PI already exists.
__________________________________________________________________________________________
1 0 / 2
Appendix 10
__________________________________________________________________________________________
Codes
Error_Class = RESOURCE
• Error_Code = MEMORY_UNAVAILABLE
Value
3
1
Description
Not enough memory available to execute the service.
Error_Class = SERVICE 4
• Error_Code = PRIMITIVES_OUT_OF_SEQUENCE 1 Incorrect sequencing of archive storage primatives.
• Error_Code = OBJECT_STATE_CONFLICT
DOMAIN_NOT_DELETABLE
INVALID_DOMAIN_STATE
INVALID_PI_STATE
PI_NOT_DELETABLE
UPLOAD_IN_PROGRESS
UPLOAD_IMPOSSIBLE
• Error_Code = CONTINUATION_INVALID
4
5
2
3
6
2
1
4
The "Deletable" attribute in the domain takes the value
FALSE.
The state of the domain does not allow service execution.
The state of PI does not allow service execution.
The "Deletable" attribute in the PI takes the value FALSE.
The uploading in progress inhibits service execution.
Uploading is impossible as the PLC application is protected.
The "Continue After" parameter is GetNameList.req is invalid.
Error_Class = SERVICE_PREEMPT
• Error_Code = TIMEOUT
5
1 The PLC does not respond to the requests sent to it.
Error_Class = ACCESS 7
• Error_Code = OBJECT_ACCESS_UNSUPPORTED 1
INVALID_EXTENDED_OBJECT_CLASS 1
INVALID_OBJECT_CLASS 2
3
"Extended_Object_Class" or "Object_Class" parameters in
GetNameList.req are invalid as they are not supported.
INVALID_OBJECT_SCOPE 3 The "Scope" parameter in
GetNameList.req or in
GetVarAccessAttributes.req
is invalid as it is not supported.
__________________________________________________________________________________________
1 0 / 3
A
A
__________________________________________________________________________________________
Codes
INVALID_KIND_OF_ACCESS
INVALID_ADDRESS
INVALID_KIND_OF_VARIABLE
EXEC_ARGUMENT_UNSUPPORTED
Value Description
5
7
8
9
The value of the "Kind of Access" parameter in a
Read.req or a Write.req is not supported.
The value of the "Address" parameter in Get Var Access
Attributes is not supported.
The value of the "Kind of
Variable" parameter in Get
Var Access Attributes is not supported.
The "Exec Argument" parameter in a Start.req or a
Resume.req is not supported.
• Error_Code = OBJECT_NON_EXISTENT
INVALID_DOMAIN_NAME
DOMAIN_NON_EXISTENT
PI_NON_EXISTENT
VARIABLE_NON_EXISTENT
USLM_NON_EXISTENT
2
1
2
3
4
5
Incorrect domain name.
Domain does not exist.
PI does not exist.
Variable does not exist in the table of symbols.
Machine to upload to does not exist.
Error_Class = CONCLUDE
• Error_Code = FURTHER_COMMUNICATION_
REQUIRED
9
1 Association cannot be closed by Conclude as communication is still in progress.
Error_Class = Others
• Error_Code = DATA_CODED
12
1 The downloaded data is in coded format.
• Error Code = WRITE_CLASS
DATA_VAR_SPEC_MISMATCH
2
1 The number of variables is different from the number of data objects in the Write request.
• Error_Code = INITIATE DOWNLOAD_SEQ
INVALID_SHARABLE_ATTRIBUTE
3
2 The "Sharable" attribute in the domain has the value
True.
These error codes given as a • Service Specific Information =
<Program Invocation State> response to program management requests take the value of the PI state defined in the MMS standard.
__________________________________________________________________________________________
1 0 / 4
________________________________________________________
Set-Up and Methodology B
___________________________________________________________________________
Page B
Presentation and Set-Up
1.1
General
1.1-1 Features Supported by PL7-OSI 3.0
1.2
Configuration Required for PL7-OSI 3.0
1.3
Checking the Hardware
1.4
Connection
1.5
Installing the Software
1.5-1 Initial Preparations
1.5-2 Installation Procedure
1.6
Rules for Access
__________________________________________________________________________________________________
Methodology
2.1
Methodology Proposal for Setting-up an Application 2/1
2.1-1 Device Addresses
2.1-2 Communication Layout
2.1-3 List of MMS Variables
2.1-4 List of MMS Services Used for Each Association
2.1-5 General Methodology
2.1-6 PL7-OSI Application Design Methodology
2.1-7 PL7-MMS Application Design Methodology
2.1-8 PL7-3 Application Design Methodology
2/2
2/3
2/3
2/4
2/5
2/6
2/7
2/8
1/1
1/1
1/2
1/2
1/3
1/4
1/4
1/4
1/6
___________________________________________________________________________
B / 1
B
___________________________________________________________________________
___________________________________________________________________________
B / 2
Presentation and Set-Up 1
__________________________________________________________________________________________
1.1
General
This manual describes the set-up and operation of the PL7-OSI 3.0 software
(ref. TXT L SSP30 V5E) on a terminal with OS/2 (version 1.2 minimum) and the X-TEL
Software Workshop installed. These terminals can be:
• FTX 507,
• IBM PS/2 or Compatible microcomputer with a 80386 or better microprocessor.
This program is used to design and operate applications that require the use of
TSX ETH 200 OSI interface modules.
B
1.1-1 Features Supported by PL7-OSI 3.0
Setting-up PLCs to use an OSI network requires:
• Selecting a communication profile common to all devices (the OSI stack) and uploading this profile to the communication modules,
• Selecting the network operating parameters and loading the corresponding configuration into the interface modules,
• Selecting MMS variables available to the network from the variables available to a device.
These features are supported in PL7-OSI 3.0 by five software sub-sets:
• PL7-OSI supports, for each station:
- Assistance with configuration parameter entry, via menus and on-line help and documentation features,
- Assistance with debugging,
- Configuration transfer between the PLC memory, the module memory and disk storage,
- Configuration documentation,
- Configuration storage to disk,
- Configuration information print-out.
• PL7-MMS supports, for each station:
- Entry of MMS symbols visible to client stations on the network,
- Transfer of selected symbols between the PLC memory and the disk,
- Documentation of the MMS symbol data base,
- Database storage to disk,
- Database print-out.
__________________________________________________________________________________________
1 / 1
B
__________________________________________________________________________________________
• OSI-LOADER supports configuration and execution of the communication profile uploading, via the programming port, to TSX ETH 200 modules connected to an 802.3
standard netwok.
• OFB MMSLD, a PLC operating system extension, automatically loads OSI parameters and the table of MMS symbols into the network interface module each time this is required.
• MMS OFB library, a set of OFBs that perform MMS services (Read/Write Variables,
Device control, etc.) for PLC stations connected to the network.
1.2
Configuration Required for PL7-OSI 3.0
The PL7-OSI 3.0 program is designed to run on FTX 507 terminals or IBM PS/2 or compatible PCs with the following systems installed:
• OS/2 (version 1.2 minimum) Operating System,
• X-TEL Software Workshop (ref. TXT L BASE V5),
• PL7-NET (ref. TXT L PL7 NET V5E), to build a network layout and use the
OSI-LOADER function of PL7-OSI 3.0 from the X-TEL Software Workshop,
• PL7-3 software for programming the application for each network station.
This means that the system requires at least 4 Mbytes of RAM memory installed and
40 Mbytes of hard disk space available).
Important
Telemecanique cannot guarantee correct operation of this software on all microcomputers or compatible PCs on the market with the above-mentioned characteristics.
1.3
Checking the Hardware
The TXT L SSP 30 V5 software package comprises:
• A 3 1/2" diskette, ref. TXT LF SSP V5,
• A 3 1/2" diskette, ref. TXT LF MMS V5,
• A 3 1/2" diskette, ref. TXT LF STK V5,
• A 3 1/2" diskette, ref. TXT LF FB SSP V5,
• A software protection key module,
• A program license contract,
• This documentation set, ref. TXT DM SSP V5E.
__________________________________________________________________________________________
1 / 2
Presentation and Set-Up 1
__________________________________________________________________________________________
To use the PL7-OSI 3.0 software, the user requires the following hardware:
• An FTX 507 terminal or an IBM PS/2 or compatible PC (refer to the required configuration described in Sub-section 1.2),
• A terminal/PLC connection cable when an FTX 507 terminal is used,
• If an IBM PS/2 or compatible PC is used, a TSX TAC 03) terminal/PLC connection kit is required, comprising:
- An RS-232C/ Current Loop converter,
- A Converter/PC connection cable with a 9-pin connector,
- A Converter/PC connection cable with a 25-pin connector,
• If an IBM PS/2 or compatible PC is TSX SCC 02 key module holder.
Only a V4.4 level or higher TSX 47, 67, 87 or 107-40 PLC must be used.
B
1.4
Connection
The connections that are specific to the terminal (monitor, keyboard, mouse, printer, key module holder, etc.) are assumed to have already been made according to the documentation supplied by the terminal manufacturer. This sub-section only describes the fitting of the software key module.
To do this, insert the software key into the vacant slot in the software key module holder.
This operation must always be performed with the terminal powered-down.
Note:
The software key module contains the right of use required to run the PL7-PMS program. The Key
Manager supplied with the X-TEL Software Workshop lets the user transfer this right of use to the
Work Key Module so that only a single key is required (work key) once again releasing a slot in the key module holder.
For more information on the use of the Key Manager, refer to the X-TEL Software Workshop documentation (ref. TXT DM XTEL V5E), Divider C Section 9.
__________________________________________________________________________________________
1 / 3
B
__________________________________________________________________________________________
1.5
Installing the Software
1.5-1 Initial Preparations
Before installing the PL7-OSI 3.0 program on the hard disk, always:
• Read the licence and guarantee certificates that give the conditions of use and detail the restrictions that apply to copying and installing this program,
• Make a copy of the diskettes required for installation and only use this copy to avoid accidental damage to the original diskette.
Important
The PL7-OSI 3.0 program diskettes are supplied write protected. Do not change the position of the write protect tab on these diskettes.
1.5-2 Installation Procedure
The following operations should be performed before installing the PL7-OSI 3.0
program:
• Check that the X-TEL Software Workshop is already installed:
• If so, install PL7-OSI 3.0 following the installation procedure described below,
• Otherwise, first install the X-TEL Software Workshop (refer to the X-TEL documentation (TXT DM XTEL V5E) Divider B Sub-section 5.
• Close all work sessions in progress.
PL7-OSI 3.0 Program Installation
1 Open an OS/2 full screen session,
2 Insert the PL7-OSI 3.0 diskette, TXT LF SSP V5 into the diskette drive,
3 Type the drive identification letter (a: or b:) where the diskette is located and press
<Enter> to confirm,
4 Follow the prompts displayed on-screen,
5
Once the installation procedure is completed, remove the program diskette and insert the next diskette, TXT LF MMS V5 into the diskette drive,
__________________________________________________________________________________________
1 / 4
Presentation and Set-Up 1
__________________________________________________________________________________________
6 Type Install again, then press <Enter> to confirm,
7 Follow the procedure displayed on-screen,
8 Repeat the above procedure to install diskettes TXT LF STK 30 V5 and
TXT LF FB SSP V5,
9 Once the installation procedure for these four diskettes is completed and this is the last installation to perform, run the configuration check. Press <Enter> to confirm,
& Remove the diskette from the drive and return to the X-TEL Software Workshop by pressing <Ctrl><Esc>.
B
__________________________________________________________________________________________
1 / 5
B
__________________________________________________________________________________________
1.6
Rules for Access
PL7-MMS and PL7-OSI programs are accessed by opening the "Tools" window for the
Station where data will be modified. To do this:
1 Select the Telemecanique item from the desktop and double click on it to confirm the selection,
2
Open the user window by double clicking on the XTEL item,
3 Enter the user identification information r equired (user's name and password), then select <Enter> to confirm. The Volumes window will be displayed,
4 Open a Volume by double clicking on the icon for the required volume in the application,
5 Open a Project by double clicking on the icon for the required project in the application,
6 Open a Station by double clicking on the icon for the station where variables will be configured,
7 Follow the procedure displayed on-screen,
8
Open the window for the required function: PL7-MMS or PL7-OSI by double clicking on its icon. If the icon is not present in the Functions secondary window even if the program was previously installed, then the function was not defined for this station.
If so, proceed as follows:
• Pull-down the Define menu and select New,
• Click on MMS or OSI in the list of functions available and confirm the selection made,
9 For improved ease of use, enlarge the PL7-MMS or PL7-OSI window by clicking on the Maximize arrow in the top right of the screen.
__________________________________________________________________________________________
1 / 6
Methodology 2
__________________________________________________________________________________________
2.1
Methodology Proposal for Setting-up an Application on a TSX/PMX PLC Connected to an OSI Network
The methodology proposal described here is designed to assist the user during the generation, debug, storage and documentation phases of application development. As this is a methodology example only, the various operations are described without detailing the operating modes required. For more information, refer to Divider H.
Important: The user must load the OSI Stack into the TSX ETH 200 modules using
OSI-LOADER. This operation is only performed once, the OSI Stack is then stored in the interface module memory.
The failure LED will blink until the stack is loaded (refer to the TSX ETH 200 Interface
Module User's Manual).
B
FTX 507
ETHERNET
APRIL R6S0
APRIL 7000
TSX 7
R6S1
TSX 7
__________________________________________________________________________________________
2 / 1
__________________________________________________________________________________________
2.1-1 Device Addresses
B
Device XWAY Network/ MMS Address
Station Address
R6S0 06/00 R6S0_MMS
00000001
0001
0001
Application name
PSEL
SSEL
TSEL
4954454C454D4543412E060001 NSAP
_______________________________________________________________________________________
R6S1 06/01 R6S1_MMS
00000001
0001
Application name
PSEL
SSEL
0001 TSEL
4954454C454D4543412E060101 NSAP
_______________________________________________________________________________________
APRIL APRIL_S1C
00000001
0000
0101
Application name
PSEL
SSEL
TSEL
4954454C454D4543412E060101 NSAP
_______________________________________________________________________________________
APRIL APRIL_S1S
00000002
0000
Application name
PSEL
SSEL
0101 TSEL
4954454C454D4543412E060101 NSAP
_______________________________________________________________________________________
__________________________________________________________________________________________
2 / 2
Methodology 2
__________________________________________________________________________________________
2.1-2 Communication Layout
R6S0
C0
C1
R6S1
C2
C3
APRIL B
C0 = association open by R6S0 to R6S1
C1 = association open by R6S1 to R6S0
C0 = association open by R6S1 to APRIL
C0 = association open by APRIL to R6S1
2.1-3 List of MMS Variables
Refer to the detailed description in the example in the Appendix.
R6S0_MMS
MT5_W50
MD_W120
MABIT_50
MADW_200
R6S1_MMS
MT5_W50
MBIT_B10
MMOT_W100
MT250_DW1000
MT_500W
MUMOT_W15
US_X900
VOITURE
VSTRING
APRIL_S1C
RUN_API
__________________________________________________________________________________________
2 / 3
__________________________________________________________________________________________
2.1-4 List of MMS Services Used for Each Association
R6S1 APRIL
B
Association
C0
C1
C2
C3
MMS Service
INITIATE
WRITE
READ (2 times)
INFO REPORT (2 fois)
STATUS
UNSOL.STATUS
CONCLUDE/ABORT
R6S0
INITIATE
WRITE
READ (2 times)
CONCLUDE/ABORT
INITIATE
INFO REPORT
READ
CONCLUDE/ABORT
INITIATE
READ
IDENTIFICATION
WRITE
READ
CONCLUDE/ABORT
__________________________________________________________________________________________
2 / 4
Methodology 2
__________________________________________________________________________________________
2.1-5 General Methodology
▲
Program Installation
XTEL-CONF
TSX/PMX V5 Stations
Define the I/O
Parameter the Application
TSX/PMX V4 Stations
Build the Application
Layout
XTEL-MEM
B
PL7-OSI
PL7-MMS
Enter the Addresses of Applications in the Layout:
Create the OSI Directory see note 1 see note 2
Enter MMS Variables for
Applications in the Layout:
Create the MMS Directory
OFF-LINE
Application
Design
PL7-OSI
Application
Design
PL7-MMS
Application
Design
PL7-3+OFB MMS
TSX/PMX V5 Stations TSX/PMX V4 Stations
Build the PLC
Application
XTEL-MEM
▼
▲ > see
Note 3
Transfer to PLC
PL7-3
Debug Mode
Debug the
Application
Update
Application File
Documentation File
Debug the
OSI Modules
Update
Application File
Documentation File
PL7-OSI
ON-LINE
▼
__________________________________________________________________________________________
2 / 5
B
__________________________________________________________________________________________
Note 1:
Refer to the OSI-PRJ directory entry function, Divider D, Sub-section 3.1-2.
In the example, the OSI-PRJ directory contains the names of the R6S0_MMS, R6S1_MMS,
APRIL_S1C applications with the corresponding addresses.
Refer to the device address tables.
These entries are performed once for all of the stations in the project.
Note 2:
Refer to the MMS directory editing function, Divider E, Sub-section 3.1.
In the example, the MMS directory contains the names of the MMS variables with their detailed characteristics (scope, type, length).
Refer to the list of MMS variables table.
These entries are performed once for all of the stations in the project.
Note 3:
All of these operations must be performed for each station.
_______________________________________________________________________________________
2.1-6 PL7-OSI Application Design Methodology
OSI
Directory
Configure the
OSI Paramèters (1)
Define the
Local Application (1)
Select the
Remote Applications (1)
Generate the
OSI Configuration (2)
Design the
PL7-OSI
Application
Download to the
Modules and PLC (3)
Document
OSI Modules (4)
(1) Div. D S-Sect. 3.2
(2) Div. D S-Sect. 3.3
(3) Div. D S-Sect. 4.1 and 4.3
(4) Div. D Sect. 5
TSX/PMX V5 Stations TSX/PMX V4 Stations
Integrate .BIN into the Application file
Possible update of other applications if the OSI-PRJ directory is modified
Note 4:
In the example, device R6S0 has R5S0_MMS as its local application and R6S1_MMS as its remote application. Device R6S1 has R6S1_MMS as its local application and R6S0_MMS and
APRIL_S1C as its remote applications.
__________________________________________________________________________________________
2 / 6
Methodology 2
__________________________________________________________________________________________
2.1-7 PL7-MMS Application Design Methodology
OSI
Directory
Define Remote
MMS Varaibles
Define Local
MMS Variables (1)
Generate the
MMS Configuration (2)
Design
PL7-MMS
Application
Download the
PLC Memory (3)
Document the
Application (4)
(1) Div. E S-Sect. 3.2/3.3
see Note 5
(2) Div. E S-Sect. 3.4
(3) Div. E S-Sect. 4.1
(4) Div. E Sect. 5
(5) Div. E S-Sect. 3.2
TSX/PMX V5 Stations TSX/PMX V4 Stations
Integrate .BIN into the Application File (5)
Possible update of other Applications if the MMS-PRJ
Directory is Modified
Note 5:
In the example, the MMS MBIT_BIO variable is a local variable for the R6S1_MMS application and a remote variable for the R6S0-MMS application.
B
__________________________________________________________________________________________
2 / 7
B
__________________________________________________________________________________________
2.1-8 PL7-3 Application Design Methodology
Integrate the MMSLD
OFB in PL7-3
PL7-3
Configuration Mode
Program the
Application
PL7-3
Programming Mode
Conception
Application
PL7-3
PL7-3 .BIN Files
Document the
Application
STATION .DOC File
TSX/PMX V5 Stations
Store and
Integrate the Application
File (STORE)
TSX/PMX V4 Stations
Integrate .BIN
into the
Application
STATION .BIN
and
STATION .APP Files
__________________________________________________________________________________________
2 / 8
________________________________________________________
OSI-LOADER C
___________________________________________________________________________
General
1.1
Program Functions
Page
1/1
__________________________________________________________________________________________________
OSI-LOADER
2.5-1 Selecting an Operating File
2.5-2 Editing an Operating File
2/1
2/1
2/1
2/2
2/3
2/4
2/5
2/9
2/10
2/11
2/12
C
___________________________________________________________________________
C / 1
A
___________________________________________________________________________
C
___________________________________________________________________________
C / 2
General 1
__________________________________________________________________________________________
1.1
Program Functions
To connect a TSX Series 7 PLC to an OSI/MMS network, the communication interface module installed in the PLC must comprise OSI/MMS software.
This program is loaded in the TSX ETH 200 modules by OSI-LOADER, a project level tool in the X-TEL Software Workshop.
C
__________________________________________________________________________________________
1 / 1
C
__________________________________________________________________________________________
__________________________________________________________________________________________
1 / 2
OSI-LOADER 2
__________________________________________________________________________________________
2.1
Program Presentation
OSI-LOADER is a project level tool, a part of the PL7-OSI 3.0 software package
(ref. TXT L SSP30 V5).
This program lets the user configure and execute an upload to the TSX ETH 200 modules of the OSI-MMS executable program.
It is only used in an 802.3 (ETHERNET) type network environment.
The configuration procedure covers generating an xxx.EXP operating file containing the description of the stations to load. The actual upload procedure transfers the OSI-MMS program to the stations defined in the operating file (xxx.EXP).
C
2.2
Requirements for Running OSI-LOADER
OSI-LOADER in the X-TEL Software Workshop environment requires that PL7-NET be installed and that the ETHERNET network that OSI-LOADER will load to be defined.
For more information on PL7-NET operation, refer to the specific User's Manual for this tool.
2.3
Program Functions
The main OSI-LOADER functions are:
Operating file configuration
Creation and modification of an xxx.EXP operating file that defines the stations that
OSI/MMS is uploaded to.
Loading stations
Uploading to the stations defined in the xxx.EXP operating file.
Deleting files
Deleting previously generated xxx.EXP operating files.
__________________________________________________________________________________________
2 / 1
C
__________________________________________________________________________________________
2.4
Selecting the OSI-LOADER Program
The OSI-LOADER program is run by opening the OSI-LOADER window under the project in which the stations will be loaded. To do this:
1 Open the Desktop Manager window by double clicking on its icon and select the
Telemecanique option by double clicking on its icon,
2 Open the user window by double clicking on XTEL or use the XTEL Browser,
3 Enter the appropriate user parameters (user name and password) and validate so that the Volumes window is displayed,
4
Open a Volume by double clicking on the icon of the appropriate application volume,
5 Open a Project by double clicking on the icon of the project in the application or use the XTEL Browser,
6 Open the OSI-LOADER window by double clicking on its function icon. If the icon is not displayed in the Project Tools secondary window, even after the program has been installed, then the function has not yet been defined in the project. To define the function:
• Pull down the Define menu and select New,
• Click on OSI-LOADER, in the list of functions available, then validate the selection made,
7
For greater visual comfort, select a full screen OSI-LOADER session by clicking on the Maximize icon in the top right corner of the window.
Primary Window
__________________________________________________________________________________________
2 / 2
OSI-LOADER 2
__________________________________________________________________________________________
Diagram
Configuration Load Utilities Exit Help
Generate… Load… View…
Delete...
Operating File [EXP]…
Configuration
Load
Create and modify an xxx.EXP file
Transfer the OSI-MMS program to the stations configured in an operating file
C
Utilities
Exit
Help
View and delete an operating file
Quit OSI-LOADER
Calls-up on-line help
2.5
Generating an Operating File - Configuration Menu
The Configuration menu lets the user create or modify an operating file (xxx.EXP). The operating file downloads the OSI Stack to the stations.
Depending on whether the xxx.EXP filename specified when the function was selected, corresponds to an existing file or a new file, this file will be created or modified.
The sequence of actions to perform to create or modify an xxx.EXP file is shown below:
1 Specify the name of an operating file,
2 Enter (or modify) a list of stations to upload. Each station in the list is defined in a structured approach by:
• The network it is connected to,
• Its station name, taken from the list of stations previously defined for the selected network,
• The location of the TSX ETH 200 module in the station PLC rack,
• The type of OSI-MMS profile to use.
3 Save the operating file (xxx.EXP).
__________________________________________________________________________________________
2 / 3
__________________________________________________________________________________________
2.5-1 Selecting an Operating File
After selecting Configuration, then Generate, the dialog box shown below is displayed:
C
This screen displays:
• A File Name field that displays the operating file name with an .EXP extension, that will be created or modified when a Save is performed.
• A list of known operating files (items) available to for project.
• OK, Cancel and Help buttons.
The filename can be entered by:
• Clicking on the data entry field and typing the file name directly from the keyboard.
• Selecting a file from the list of operating files available for the project, using the following procedure:
- Double clicking on the file to select,
- Highlighting the file to select using the Cursor Keys and pressing <Enter> to confirm the selection made.
A filename will always be displayed by default in the window, according to the following rules:
- If there is no operating file, the default filename is the project name followed by an
.EXP extension,
- Otherwise, the name of the first file in the list is displayed in this field.
OK
Cancel
Help
Calls-up a screen allowing the user to edit the contents of the operating file.
Cancels the configuration action.
Displays on-line help on generating operating files.
__________________________________________________________________________________________
2 / 4
OSI-LOADER 2
__________________________________________________________________________________________
2.5-2 Editing an Operating File
Once a filename selection is confirmed, the following screen is selected:
This screen will list the various stations defined in the previously selected operating file.
The Edit functions are selected using the buttons located at the bottom of the screen.
There are two possible cases:
• If the filename does not correspond to an existing filename and the list displays no existing station; then Create is selected,
• Otherwise, the list will display all of the stations already defined for this file; then Modify is selected. Each station in the list is identified by three components: the network name, the station name and the OSI-MMS profile designation.
Add
Delete
OK
Cancel
Exit
Starts the definition procedure for a new station, calling-up a sequence of four dialog boxes.
These dialog boxes allow the user to select, in sequence, the network name, station name on the network, the module location and finally the OSI-MMS profile designation.
Deletes a station from the list.
Saves the modifications made (generates the operating file).
Cancels the Edit function and returns the user to the previous screen.
Exit the operating file configuration function and returns the user to the OSI-LOADER action bar.
__________________________________________________________________________________________
2 / 5
C
C
__________________________________________________________________________________________
Adding a station to the list
Preliminary remark:
Establishing an upload configuration is equivalent to making a list of stations to load, that are known to a previously defined 802.3 network. Therefore to use OSI-LOADER, it is essential to first define the network layout.
To do this, PL7-NET must be installed and the network must have been defined in the
Networks secondary window within the currently developed Project.
Given these requirements, one of the error messages listed below may be displayed when the user confirms the modifications made by selecting Add:
Message:
Description:
Message:
Description:
"No valid network defined for this project"
No network is defined, or the network defined is not an 802.3 type.
"No valid station defined for this network"
A valid network has been defined, but no station is "connected" in the network layout definition.
If the definition of the network layout is correct, it is possible to add a station to the list.
As described above, the station is described by the network name, the station name, the interface module location (or module number) and the OSI-MMS profile to load. These four parameters are selected successively, via four dialog boxes.
The procedure is the same for each of the four dialog boxes, make a selection from a list displayed and confirm the selection made. Once this is done a dialog box is displayed. This procedure is repeated until the profile selection is complete. Confirming the last selection, returns the user to the configuration screen. The newly defined station is displayed at the end of the list.
__________________________________________________________________________________________
2 / 6
OSI-LOADER 2
__________________________________________________________________________________________
The four dialog boxes comprise the same four buttons:
OK Confirms the selection made and opens the next window (except when the Profiles window is opened, as this is the last screen and confirming the selections made in the profiles window returns the user to the Configuration screen).
Cancel
Exit
Cancels the action and returns the user to the previous screen.
Exits the configuration function and returns the user to the
OSI-LOADER action bar.
Help Displays a help screen for the current selection (network, station, module or profile).
The four screens are illustrated below:
C
__________________________________________________________________________________________
2 / 7
C
__________________________________________________________________________________________
Remarks on the profile selection dialog box:
• This dialog box summarizes the three previous selections (network, station and module).
• In the current version, only one OSI-MMS profile is available: The MMS-IS profile.
__________________________________________________________________________________________
2 / 8
OSI-LOADER 2
__________________________________________________________________________________________
2.6
Loading Stations Defined in an Operating File
To load a set of stations, simply select the previously configured operating file, from the open dialog box and confirm the selection made.
OK Loads the stations defined in the file specified in the File Name field, once the user has confirmed the request.
C
__________________________________________________________________________________________
2 / 9
__________________________________________________________________________________________
2.7
Viewing Operating Files
C
To view an operating file, simply select the file name from the list of files displayed in the dialog box shown below and confirm the selection:
OK
Cancel
Displays the .EXP file view screen.
Cancels the action, no file is displayed and the user is returned to the primary window.
The operating file is viewed in its original format. The user can scroll its contents using the vertical scroll bars. The Cancel button lets the user exit the View mode and return to the OSI-LOADER primary window.
__________________________________________________________________________________________
2 / 1 0
OSI-LOADER 2
__________________________________________________________________________________________
2.8
Deleting Operating Files
To delete an operating file, simply select the file name from the list of files displayed in the dialog box shown below and confirm the selection:
C
OK
Cancel
Deletes the file whose name is shown in the "File Name to Delete" field, once the user has confirmed the request.
If the filename is invalid, the message
"No file selected, or filename entered does not exist!" is displayed.
Cancels the action, no files are deleted.
__________________________________________________________________________________________
2 / 1 1
__________________________________________________________________________________________
2.9
Help
C
The Help item in the pulldown menu lets the user access the OSI-LOADER help screens from the root directory.
The About... item in the pulldown menu displays:
__________________________________________________________________________________________
2 / 1 2
________________________________________________________
PL7-OSI D
___________________________________________________________________________
Section Page
__________________________________________________________________________________________________
General
1.1
Presentation
1.2
PL7-OSI Objectives
1.3
PL7-OSI Functions
1.4
Accessing PL7-OSI
1/1
1/1
1/2
1/3
__________________________________________________________________________________________________
Selecting the Working Memory - Memory Menu
2/1
__________________________________________________________________________________________________
Configuring the Station - Configuration Menu
3.1-1 Project Directory Description
3.1-2 OSI_PRJ Directory Entry Function
3.1-3 OSI_PRJ Directory Restore Function
3.1-4 OSI_PRJ Directory Save Function
3/1
3/2
3/4
3/6
3/7
3.2-1 Selecting and Generating the Module File (xxx.CPL)
3.2-2 Setting OSI Layer Parameters
3.2-3 Defining the Local Application
3.2-4 Selecting Remote Applications
3.3-1 Creating an OSI.BIN File
3.3-2 Modifying and Viewing an OSI.BIN File
3/8
3/8
3/11
3/12
3/14
3/16
3/17
3/19
D
__________________________________________________________________________________________________
Transferring Binary and Module Files - Transfer Menu
4/1
4/3
4/4
4/6
___________________________________________________________________________
D / 1
A
D
___________________________________________________________________________
Page
Documenting and Printing
5.1
Generating Documentation
5.2
View
5.3
5.4
Enter Information
5.5
Documenting a Module
Deleting Files - Configuration Set-Up - Help
6/1
6/2
6.3 Restoring/Saving the OSI.BIN File 6/4
_______________________________________________________________________________
6.3-1 Restore
6.3-2 Save
6/4
6/5
6.4
Help 6/6
5/1
5/2
5/2
5/3
5/6
Appendix
Directory File Format 7/1
___________________________________________________________________________
D / 2
General 1
__________________________________________________________________________________________
1.1
Presentation
PL7-OSI is a Station level function tool, a sub-set of the PL7-OSI 3.0 program. It is run in the X-TEL Software Workshop environment.
Program functions are shared between two components:
• The network interface module configuration and documentation program, designed to run on an FTX 507 station with the X-TEL Software Workshop,
• The PL7-3 Optional Function Blocks (OFBs) that are run on TSX and PMX Series 7
PLCs.
The following sections describe the functions and operating modes of the network configuration program.
The OFB program is described separately in Divider F.
1.2
PL7-OSI Objectives
PL7-OSI lets the user design and load an OSI configuration for every TSX ETH 200 network interface module in a station.
The configuration of an OSI interface module requires the definition of three sub-sets of data:
• The OSI layer parameters,
• The definition of the single local application corresponding to the PL7-3/MMS application implemented on the station,
• The list of remote applications that the application must identify.
The list of remote applications is established by selecting from the list of all applications available to the project stored in the OSI Project directory. Therefore, PL7-OSI also supports creation and modification of the OSI Project directory, in addition to setting network interface module parameters.
PL7-OSI lets the user describe the OSI configuration of the modules in the station. It also supports up/downloading of configuration files for each of the interface modules. Like all other Software Workshop tools, PL7-OSI also generates the files required for documenting the application.
D
__________________________________________________________________________________________
1 / 1
D
__________________________________________________________________________________________
1.3
PL7-OSI Functions
PL7-OSI supports the following functions:
Configuring the OSI_PRJ project level applications directory
Create, modify or view an OSIPRJ.REP directory file containing the MMS applications for the project. This file can be saved (Save function) and restored (Restore function), allowing back-up copies to be made.
Configuring a module file
Create, modify or view a module (coupler) type file (xxx.CPL) for use with TSX ETH 200 network interface modules.
This type of file comprises:
• The OSI layer parameters,
• The definition of the local application that the module is assigned to operate with in
MMS Client mode,
• The list of remote applications that are visible to the local application, if it is to operate in MMS Client mode.
This file (xxx.CPL) can be loaded directly into the module.
Configuring the OSI.BIN file
Create, modify or view an OSI.BIN binary file. This file comprises 1 to 4 interface module partitions and can be up/downloaded to and from the dedicated OSI field in the PLC memory.
Uploading a module (.CPL) file
Uploading a module xxx.CPL file to the memory in a TSX ETH 200 module from the workstation.
Uploading an OSI.BIN file
Uploading an OSI.BIN binary file to the dedicated OSI field in the PLC memory from the workstation.
Downloading an OSI.BIN file
Downloading (saving) the contents of the dedicated OSI field from the PLC memory to the workstation.
__________________________________________________________________________________________
1 / 2
General 1
__________________________________________________________________________________________
Comparison
Comparing the OSI.BIN file in the local workstation memory with the contents of the dedicated OSI memory field in a target PLC.
Station documentation
Creating documentation on a binary (.BIN) file.
Module documentation
Creating a module configuration documentation file.
Deleting a file
Deleting a configuration or documentation type file.
Setting-up the dedicated OSI field in the PLC memory
Modify or view the configuration parameters of the dedicated OSI memory field in a PLC.
The access to these functions depends on the selection, made by the designer, of the working memory. There are three possible selections:
• Local memory (the workstation disk),
• PLC memory,
• Module memory.
D
1.4
Accessing PL7-OSI
PL7-OSI is accessed by opening the OSI window in the station where network interface module are to be configured.
Primary window
__________________________________________________________________________________________
1 / 3
__________________________________________________________________________________________
Diagram
Memory
Local
PLC
Module
Configuration (2/3) Transfer
OSI Directory ➙ Disk ➙ PLC
Module ➙
PLC (3)
Documentation (3) Utilities (3) Exit
Generate
PLC ➙ Disk (3) View
Disk ➙ Module (2) Print
Delete ➙
Debug(1)
Restore
Resume
Compare (3) Enter Data ➙ Save
Documentation
(1) Options that cannot be selected when Local Memory is selected
(2) Options that cannot be selected when PLC Memory is selected
(3) Options that cannot be selected when Module Memory is selected
D
Memory
Configuration
Selects the working memory.
Enter, Save/Restore the project level application directory file
(OSIPRJ.REP). Configures the OSI modules and generates xxx.CPL
or xxx.BIN files.
Transfer Up/Download and Compare xxx.BIN files in the PLC memory OSI field.
Upload xxx.CPL files to a module (depending on the working memory).
Documentation Generates and prints a documentation text file on the xxx.BIN file generated by the tool.
Utilities • Deletes xxx.BIN, xxx.CPL, xxx.OSI, xxx.CRT, xxx.TIT, xxx.DOC files from the workstation disk,
• Save/Restore OSI.BIN files,
• Interactive debugging of the configuration parameters of a module in the PLC memory dedicated OSI field (BIN).
Exit Exits PL7-OSI.
__________________________________________________________________________________________
1 / 4
Selecting the Working Memory - Memory Menu 2
__________________________________________________________________________________________
2.1
Memory Menu
The PL7-OSI main menu lets the user select the working memory.
The functions that can be accessed depend on the selections made.
• Selecting Local memory lets the user access all functions except for the Debug function. It is possible to define module configurations and generate the OSI.BIN file without the need to establish connection with the PLC.
The application directory file can only be accessed when the Local memory option is selected.
• Selecting PLC memory requires connection to the PLC processor. The Up/Download,
Documentation and Debug functions are accessible (and this is the only way to access the Debug function), in the PLC working memory environment.
D
__________________________________________________________________________________________
2 / 1
D
__________________________________________________________________________________________
The table below summarizes the functions that can be accessed using the three types of working memory.
FUNCTIONS
Operations on the OSI directory
Configuration\Module\TSX ETH 200
Configuration\PLC
Transfer\Disk ➙ PLC
Transfer\PLC ➙ Disk
Transfer\Disk ➙ PLC
Transfer\Compare
Documentation\Station
Documentation\Module
Utilities\Delete
Utilities\Debug
Restore/Save OSI.BIN
Yes
Yes
Yes
Yes
Yes
Yes
WORKING MEMORY
Local
Yes
Yes
Yes
PLC
No
No
No
Module
No
Yes
No
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
No
No
No
No
No
No
No
No
Yes
For V5 level stations, an additional restriction applies:
The Configuration\Module and Configuration\PLC and Restore (OSI.BIN) functions cannot be accessed if the user has not first used XTEL-CONF to define the location of the network interface module.
__________________________________________________________________________________________
2 / 2
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
3.
Configuring the Station - Configuration Menu
The Configuration menu lets the user:
• Create, Modify and View the OSI_PRJ directory for all of the MMS applications in the project.
• Define or Modify the parameters of the TSX ETH 200 OSI module, Define the local
MMS application and the remote MMS applications. Once these definitions are made, a Module (xxx.CPL) type file will be generated.
• Generate the OSI.BIN binary file that contains the configuration of all of the PLC's interface modules. The OSI binary file is intended to be uploaded to the dedicated OSI field in the PLC memory.
D
3.1
OSI_PRJ Directory
This function is used to create, modify and view the Directory of remote MMS applications for the project.
The directory is shared by all of the stations in the project. The OSI Directory function is the station level access point. It is important to check data coherence when the directory is modified.
__________________________________________________________________________________________
3 / 1
D
__________________________________________________________________________________________
3.1-1 Describing the Project Directory
The OSI_PRJ Project Directory
• Comprises the description of each MMS application in the project,
• Is described by the OSIPRJ.REP file and is located at project level in the X-TEL Software
Workshop file structure and is unique to each project,
• It can be accessed by all TSXV4/V5 type stations in the project (TSXV4, TSXV5,
PMXV4, PMXV5),
• It can comprise up to 1024 OSI remote applications,
• Supports the OK, Cancel and Help buttons.
The OSIPRJ.REP file is an ASCII file that contains a succession of descriptions of MMS remote applications. It is sorted in rising alphabetical order.
Each of the applications is described by the following parameters (some parameters are optional).
APPLICATION NAME: Identifies an application.
Value = 32 alphanumeric characters.
AP TITLE (optional):
AE QUALIFIER (optional):
Application Process identifier.
Value = 8 x 4 bytes max. in hexadecimal notation.
Application Entity identifier.
Value = 4 bytes max. in hexadecimal notation.
PSEL (Presentation SELector): Access to presentation layer services.
Value = 16 bytes max. in hexadecimal notation.
SSEL (Session SELector): Access to session layer services.
Value = 16 bytes max. in hexadecimal notation.
TSEL (Transport SELector): Access to transport layer services.
Value = 32 bytes max. in hexadecimal notation.
NSAP: Access to network layer services.
(Network Service Access Point) Value = 20 bytes max. in hexadecimal notation.
__________________________________________________________________________________________
3 / 2
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
Reminders on addressing rules:
To establish an MMS assignment, system addressing is performed from the physical layer level (the Medium Access Control (MAC) data link sub-level) to the program task level (application level).
Addressing a Local Module:
• APPLICATION NAME:
Logical name that identifies an OSI application.
• AP TITLE and AE QUALIFIER:
The parameters are optional.
• Presentation Address:
The presentation address PSAP (Presentation Service Access Point) is a concatenated character string combining the presentation selector (PSEL) and the previous session address (SSAP). It is a character string of 1 to 16 bytes with a default value of 00 00 00 01.
• Session Address:
The session address SSAP (Session Service Access Point) is a concatenated character string combining the session selector (SSEL) and the previous transport address (TSAP). It is a character string of 1 to 16 bytes with a default value of 00 01.
• Transport Address:
The transport address TSAP (Transport Service Access) is a concatenated character string combining the transport selector (TSEL) and the previous network address
(NSAP). It is a character string of 1 to 16 bytes with a default value of 00 01.
• Network Address:
The network address conforms to the hierarchical layout defined in the ISO 8348/AD2 standard and supports all of its formats. The maximum size supported by the NSAP
(Network Service Access Point) is 20 bytes. The NASP address default value is the local NASP format, described as follows:
49: identifies the local NASP format,
54 45 4C 45 4D 45 43 41 2E: ASCII character string abbreviation for
Telemecanique,
00FE: with 00 the default network number and FE the default station number
(from 0 to 63),
01: NSEL identifying a terminal system.
The NSAP network address must be unique to each system and it identifies a single system connected to the network.
The OSI-MMS profile supports a single local MMS application, defined by the parameters:
APPLICATION NAME, AP TITLE (Application Process Title), AE QUALIFIER (Application Entity Qualifier), PSAP, LSAP (Link Service Access), MAC Address (Medium
Access Control).
__________________________________________________________________________________________
3 / 3
D
__________________________________________________________________________________________
Remote System Addressing
The same local addressing parameters are used, i.e. NSAP, TSEL, SSEL, PSEL, AE
QUALIFIER, AP TITLE and APPLICATION NAME.
The OSI Project Directory is created by the PL7-OSI designer, locally from the station.
To do this the Entry function is used, allowing access to the OSIPRJ.REP file at project level. This lets the user describe the remote applications using specific data entry fields.
3.1-2 OSI_PRJ Directory Edit Function
D
Once this function is selected, the following data entry screen is displayed:
This screen displays the OSI_PRJ Directory information, listing the names of the remote applications stored in the OSIPRJ.REP file.
The fields below this display the values of each of the addressing parameters of the remote application selected in the top box.
__________________________________________________________________________________________
3 / 4
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
This field is arranged in three columns that, from left to right, give the:
• Designation of the parameter in column 1,
• Value taken by the parameter in column 2, displayed in a field that can be edited,
• Limit values (number of characters or number of bytes) and the format (character or hexadecimal) of the value entered.
The functions available at Application level are mentioned in the top right part of the screen, these comprise:
• Adding a new remote application,
• Modifying a previously entered application,
• Deleting a previously created application.
These three functions are only effective locally. They do not change the OSIPRJ.REP
file. Only the user confirmation by selecting OK will modify the file.
The functions available at all levels are shown across the bottom of the screen. They are:
• OK: Confirm data entry,
• Cancel,
• Help.
Add Lets the user create a new remote application. Procedure:
• Enter a new application name in the Application Name field, the other fields are cleared,
• Fill-in the other fields,
• Click on Add once the entries are made.
The formats of the various parameters are checked. If an error is found, a message is displayed an the cursor is placed on the field where the error was found.
If no errors are found, the data entered is saved and the application is added to the list in the OSI_PRJ Directory field.
Modify Lets the user modify a remote application that was previously defined in the
OSI_PRJ directory. Procedure:
• Select an application from the list in the OSI_PRJ Directory field, by double clicking on it. The various fields will display the values for the selected application.
• Make the required modifications to the various fields.
• Click on Modify, the values entered are checked as described for Add.
D
__________________________________________________________________________________________
3 / 5
__________________________________________________________________________________________
Delete Lets the user delete a remote application from the OSI directory. Procedure:
• Select the application to delete from the list in the OSI_PRJ Directory field.
• Click on Delete. The selected application will be deleted.
OK This function saves the remote application data as entered, in the OSIPRJ.REP
file in the OSI_PRJ directory.
Note that this action overwrites the existing OSIPRJ.REP file stored at project level.
If a Modify or Delete action was performed, a message informs the user that there may be incoherent data in the stations. The user is then returned to the
PL7-OSI main menu.
Cancel By clicking on this button, the user is returned to the PL7-OSI main menu and
any modifications made will be lost.
3.1-3 OSI_PRJ Directory Restore Function
D
This function lets the user import an ASCII file that meets the OSIPRJ.REP file format requirements, from a diskette or hard disk. When this action is performed, it overwrites the existing OSIPRJ.REP file.
__________________________________________________________________________________________
3 / 6
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
Selecting Restore displays the following window:
Simply type the complete name (file name and access path) of the file to import, in the entry line and select the OK button to confirm.
The user will be prompted to confirm creation of the OSIPRJ.REP file. Once confirmed, any previous OSIPRJ.REP file will be overwritten with the newly imported one.
A message informs the user of the progress of the function. If a syntax error is found in the source file, the error is displayed along with the program line where it occurred.
Selecting the Cancel button lets the user abort the function without creating a new file.
D
3.1-4 OSI_PRJ Directory Save Function
This function lets the user copy the OSIPRJ.REP file to a file on diskette or hard disk with a user specified name. This function is the reverse of the Restore function.
This function is selected in the same way as the Restore function. Enter the full name
(file name and access path) of the target file, in the entry line and confirm the entry made.
A message informs the user of the progress of the function.
__________________________________________________________________________________________
3 / 7
__________________________________________________________________________________________
3.2
Configuring a TSX ETH 200 Module
This function lets the user create, modify or view an xxx.CPL file.
This file comprises the configuration of a TSX ETH 200 module. It is intended to be uploaded to the module. The xxx.CPL file is also used when the station PLC is configured, when the OSI.BIN file is generated (refer to Sub-section 3.3).
The module configuration data comprises three sub-sets:
• OSI layer parameters,
• Definition of the local MMS application,
• List of remote applications that the module defines an association with.
The data is defined using data entry screens that are specific to each set of data. A first screen lets the user select the name of the module file. These screens are defined below.
D
3.2-1 Selecting and Generating the Module File (xxx.CPL)
Once the \Configuration\Module\ETH200 selection is made from the PL7-OSI main menu, the following screen is displayed:
__________________________________________________________________________________________
3 / 8
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
This screen comprises three parts:
• Select File. At left, this section comprises a first field that displays the name of the module file (xxx.CPL) that will be created or modified and a frame that comprises the list of xxx.CPL files available.
It is up to the user to enter the file name, either directly from the keyboard, or by selecting a file from the list of those available.
When there are no xxx.CPL files listed, the default file name that is displayed is a name made up from the station name (Stattion_Name.CPL). If there are already files available, the default display will be the first file in the list of files.
• Select modification. At right, this section comprises three items:
• OSI layer parameters,
• Local application definition,
• Remote application selection.
This part lets the user pre-select the sets of parameters that require definition or modification, simply click on the corresponding items.
• Modify default configuration. At lower right, this section comprises two fields:
Revert to the standard configuration and Save new configuration.
- The Revert to standard configuration option lets the user return to the default module configuration and use the standard parameter values defined by Telemecanique.
This option is useful if a previous modification was made to the standard configuration using the Save new configuration option.
- The Save new configuration option lets the user modify the standard default configuration defined by Telemecanique and use the configuration corresponding to the selected xxx.CPL file.
The configuration saved using this option only affects the parametering of the OSI layers and the definition of the local application.
The Save new configuration option can only be accessed after selecting one of the
Select modification items.
Creating the Module (.CPL) File
When creating the file (the file name selected is not the same as an existing file) and if no modification selections have been made, selecting OK will immediately create the designated file with a default configuration. The OSI layer parameters are initialized with default values and the local application is also defined with default parameters. No remote applications are assigned to the module. The default configuration only allows operation in MMS Server mode.
D
__________________________________________________________________________________________
3 / 9
__________________________________________________________________________________________
Modifying a Module (.CPL) File
If the file name selected is the same as an existing file, the user must select the modifications to make in the appropriate display box. Otherwise an error message will be displayed when the user selects OK.
If the OSI_PRJ remote applications directory for the project was modified since the last time the module file was generated, and it comprises a list of remote applications, the following warning is displayed when the user selects OK.
D Yes
No
Generates the .CPL file when the default configuration is selected (as described previously).
Starts the configuration screen display sequence, according to the modification selections made.
Aborts the module configuration action and returns the user to the PL7-OSI main menu.
__________________________________________________________________________________________
3 / 1 0
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
3.2-2 Setting OSI Layer Parameters
If any modification to OSI layer parameters was specified in the previous screen, selecting OK will display the screen shown below:
This screen comprises:
• The parameter edit field. This field is divided into groups of parameters for each OSI profile layer,
• The control buttons.
Editing parameters
The parameter editing field comprises four columns, arranged from left to right:
• Column 1:
• Column 2:
OSI parameter name,
Numerical value of the parameter to edit,
• Column 3:
• Column 4:
Value measurement unit,
Value numerical base symbol (D for Decimal, H for Hex).
A value is edited by clicking first on the field to modify, in Column 2, then typing in the new value from the keyboard. The column widths shown on screen are constant, but the entry field is restricted to the maximum number of digits allowed for each entry. If the field will accept more digits than the column width will display, it is possible to shift the display
(horizontal scroll) to the left or to the right, using the left and right cursor keys.
A check is performed on the value of the parameters, when the user exits the screen.
It is impossible to exit the screen when an error is found and an error message is displayed. The "Syntax Error" message means that there is at least one syntax error in one of the values. The error message "Values out of bounds" is self-explicit.
D
__________________________________________________________________________________________
3 / 1 1
D
__________________________________________________________________________________________
Button actions
Modify
Cancel
Saves the parameter values, then calls-up the next data entry field, if other modifications were selected in the first screen, or generates the .CPL file once all selected modifications have been made. In this case, the user is returned to the PL7-OSI main menu as soon as generation is complete.
Aborts the set parameter action. The user is returned to the previous screen. The modification selections made previously are lost.
3.2-3 Defining the Local Application
If "Define Local Applications" was selected, the following screen is displayed:
This screen displays the application parameters APPLIC. NAME (Application Name),
AP_TITLE, AE QUALIFIER, PSEL, SSEL, TSEL and NSAP across the top of the screen, in the usual three column layout. If the .CPL file being configured has not yet been generated, the APPLIC. NAME and PSEL fields take the default values.
The screen comprises three parts:
• The top part shows the parameters that define the application, using the standard three column layout,
An "OSI_PRJ Directory" button lets the user access the OSI_PRJ directory by selecting an application that will become the local MMS application.
• The lower part that is reserved for the definition of the number of MMS assignments that the local application can open or accept,
• The control buttons.
__________________________________________________________________________________________
3 / 1 2
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
Define Local Application (upper part)
The parameters required to define the application are APPLIC. NAME, PSEL, SSEL,
TSEL and NSAP. The values of the AP TITLE and AE QUALIFIER parameters are optional.
When a .CPL file is created, these required parameters take the current default values.
The "OSI_PRJ Directory" button lets the user select an application from those defined in the OSI_PRJ directory. To do this, click on the "OSI_PRJ Directory" button. The upper part of the OSI_PRJ screen displays the list of applications present in the directory.
To display the parameters of an application, click on its name in the list. The lower
"Complete Address" field on-screen will display these parameters. Click on the Select button to validate the selection made.
An alternative method for selecting an application requires double-clicking on the selected application. The parameters of the selected application will then be displayed in the Local Application definition window.
It is also possible to enter parameter values that do not correspond to to an application in the OSI_PRJ directory. These values are entered directly into the Local Application definition fields.
Defining the number of assignments
The user must declare the number of assignments that can be open between the local application and the remote applications, defining the number of assignments opened on the initiative of the local application and those accepted by the local application. The total number of assignments is restricted to 322.
The value of Max Serv Outstanding Calling/Called depends on the total number of assignments configured in PL7-OSI (number of assignments opened at the initiative of the local application plus the number of assignments accepted by the local application).
3
2
1
M = max (Negotiated Max Serv Outstanding Called) = proposed Max Serv Outstanding Calling
5
4
D
4 8 12 16 21 24 28 32 Total number of assignments configured in PL7-OSI
OK Saves the parameter values, then calls-up the next data entry screen, if other modifications were selected in the first screen, or generates the
.CPL file once all selected modifications have been made. In this case, the user is returned to the PL7-OSI main menu as soon as generation
Cancel is complete.
Aborts the parametering action. The user is returned to the previous screen. The modification selections made previously are lost.
__________________________________________________________________________________________
3 / 1 3
__________________________________________________________________________________________
3.2-4 Selecting Remote Applications
If "Select Remote Applications" was selected, the following screen is displayed:
D
The screen comprises three parts:
• The "OSI_PRJ Directory" frame that displays a list of remote applications in the OSI directory,
• The "List of Selected Applications" frame that shows a list of remote applications that the local application can establish assignments with. This frame also includes the Add and Delete buttons,
• The "Complete Address" frame listing the parameter values for an application.
The purpose of this screen is to select from the "OSI_PRJ Directory" frame, the remote applications that will be selected for the specific module.
Adding a Remote Application
There are two ways to proceed:
First procedure:
• Click in the "OSI_PRJ Directory" frame and select the appropriate application. Once it is selected, its parameters are displayed in the "Complete Address" frame.
• Click on Add in the "List of Selected Applications" frame, the name of the application will be displayed in the frame and, at the same time, the "Complete Address" field will be cleared.
Second procedure:
• Double click on the application to select in the "OSI_PRJ Directory" frame. The name of the selected application is immediately displayed in the "List of Selected Applications" frame.
__________________________________________________________________________________________
3 / 1 4
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
Deleting a Selected Application
• Click on the application to delete in select in the "List of Selected Applications" frame,
• Click on the Delete button.
Remark
From this screen, it is not possible to delete or modify a Remote Application in the
OSI_PRJ directory ("OSI_PRJ Directory" and "Complete Address" frames). To make these modifications, the user must exit module configuration and return to the
PL7-OSI main menu and select Configure\OSI Directory, then Data Entry.
To complete the Remote Applications selection procedure, use the buttons located at the bottom of the screen.
Button action
OK
Cancel
Generates the xxx.CPL file and returns the user to the PL7-OSI main menu as soon as generation is complete.
Aborts the remote application selection action. The user is returned to the first "Configuring a TSX ETH 200 Module" screen.
The selections made previously are lost.
D
__________________________________________________________________________________________
3 / 1 5
__________________________________________________________________________________________
3.3
Configuring the PLC
D
This function lets the user:
• Create the structure of an OSI.BIN file from one or more Module (xxx.CPL) type files,
• Modify the communication parameters of modules in the OSI partition of an existing
OSI.BIN file,
• View the OSI partition of an existing OSI.BIN file.
This function is a Create action when the OSI.BIN file does not exist. It is a Modify or
View action once the file exists.
The OSI.BIN file that is generated, is used to save the directory and configurations for the interface modules in a station, when it is loaded into the dedicated OSI field in the
PLC memory of the station.
An OSI.BIN file comprises a header, directory or module configurations and memory partitions that each comprise a module configuration.
The number of possible partitions depends on the type of target station:
• TSX 47-420/47-455, PMX 47-420/47-455 stations will only support a single OSI module,
• TSX 67-40, PMX 67-40 stations will support one or two OSI modules,
• TSX 87-40, PMX 87-40, TSX 107-40 and PMX 107-40 stations will support up to four
OSI modules.
These are maximum values that apply to the various models, given that other network interface modules such as FIPWAY, ETHWAY, MAPWAY, etc. must be taken into account when determining the maximum number of connections supported by a station.
__________________________________________________________________________________________
3 / 1 6
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
The sequence of actions to perform to Create, Modify or View an OSI.BIN file is described below:
1.1 Create - Assign one or more module files to one or more slot numbers in the target PLC rack (Create OSI.BIN File screen),
1.2 Modify or View - Modify or View the communication parameters of one or more modules from the configuration stored in the OSI.BIN binary file displayed on-
2 screen (Modify OSI.BIN File screen),
Generate or Regenerate the OSI.BIN file as required, if any modifications were made to an existing configuration.
3.2-1 Creating an OSI.BIN File
The PLC configuration function is a create action when the OSI.BIN file does not yet exist. The following screen is displayed:
D
This screen lets the user assign a slot number in the rack to a previously created module file.
Simply click on a module file name in the "Select File" frame., then click on the slot number in the "Select Slot Number" frame, to assign the file to the module location.
The assignment is shown on-screen by the newly selected file name being displayed in the appropriate column.
Note that if an OSI.BIN file containing .CPL files is displayed, the filename.CPL is replaced by TSX ETH 200, corresponding to the type of module.
For a V5 level station, the slots in the rack that can be accessed are determined by the
3 / 1 7
__________________________________________________________________________________________
Deleting a Module-Slot assignment
To undo an assignment made, click on the appropriate slot number and the following screen is displayed:
D
Click on the DELETE Module option, then on OK and the user will be returned to the previous screen. The file name will have been deleted from the slot.
Note: The Modify option in the module configuration is not available when first creating the OSI.BIN file.
To exit the "Create OSI.BIN File" screen, click on the OK or Cancel buttons at the bottom of the screen.
OK
Cancel
Generates the OSI.BIN file. A message indicates that the file will be created and saved and requests user confirmation before proceeding.
Select Enter to exit this screen.
Aborts the configuration action. This selection must be confirmed by the user.
Help Calls-up the help screens on module assignment.
__________________________________________________________________________________________
3 / 1 8
Configuring the Station - Configuration Menu 3
__________________________________________________________________________________________
3.3-2 Modifying and Viewing an OSI.BIN File
When the selected OSI.BIN file already exists, the Configuration\PLC option calls-up the following screen:
This screen is almost identical to the "Create the OSI.BIN File" screen. The screen title is different and the slots assigned are marked with the type of module and not the module file name as used previously.
The Modify function provides the user with the same features as the Create OSI.BIN file function described above. In addition, it lets the user access the module configuration screens described in Sub-section 3.2.
To modify a module configuration, click on the slot number assigned to it, then click on the Modify option in the newly displayed screen.
Once confirmed by selecting OK, this window is replaced by the "Modify Module File" window.
D
__________________________________________________________________________________________
3 / 1 9
__________________________________________________________________________________________
D
This screen lets the user select the type of modifications to make. The procedure used is the same as that described in Sub-section 3.2 for configuring a module.
If modifications are made to the configuration, the corresponding module file is regenerated, once the action is confirmed by the user. At the end of the PLC configuration session, the user is also prompted to accept OSI.BIN file regeneration.
Remark
It is only possible to modify the configuration of a module from the PLC configuration function, if the module was already declared in the OSI.BIN partition during a prior session.
OK
Cancel
Regenerates the OSI.BIN file. A message warns the user that the file will be regenerated and requests user confirmation before proceeding, as described for creating an OSI.BIN file.
Aborts the configuration action. This action must be confirmed by the user from the dialog box that is displayed.
__________________________________________________________________________________________
3 / 2 0
Transfefring Binary and Module Files - Transfer Menu 4
__________________________________________________________________________________________
4.
Transferring Binary and Module Files - Transfer Menu
This function lets the user transfer an OSI.BIN or Module (.CPL) file, generated by the
Configuration function, from the terminal hard disk to the PLC or module memory. It can also be used to transfer the contents of the dedicated OSI field in the PLC memory to an OSI.BIN file in the workstation.
This function also supports comparisons between an OSI.BIN file on disk and the contents of the dedicated OSI field in the PLC memory.
4.1
Uploading to the PLC
This function lets the user transfer the OSI.BIN file to the PLC memory.
Remark
An upload can only be performed if the dedicated OSI field was assigned previously in the PLC memory. To perform the assignment, use the following tools:
• For a V4 level station
XTEL-MEM will generate an application file for configuring the memory (xxx.APP
file). This configuration must include a dedicated OSI field.
XTEL-TRANSFER can then be used to upload to the PLC memory, the newly generated xxx.APP file.
• For a V5 level station
XTEL-CONF is used to create the memory structure for the application file. This tool is used to reserve the necessary PLC memory for the OSI.BIN file.
XTEL-TRANSFER can then be used to upload to the PLC memory, the memory structure and its associated application files (such as OSI.BIN), if they exist.
D
__________________________________________________________________________________________
4 / 1
__________________________________________________________________________________________
To perform the upload, the workstation must be connected to the PLC.
Once the Disk->PLC action is selected from the pulldown menu, for:
• V4 level stations, the following dialog box is displayed:
D
Yes Starts the transfer. A message is displayed to inform the user that the operation is complete and that it was performed correctly.
If the message "PLC not mapped for this application" is displayed, use
XTEL-MEM and XTEL-TRANSFER to change the memory mapping for the application in the PLC memory.
As a rule, if the transfer could not be executed, the action is completed with the message "File OSI.BIN could not be uploaded correctly to PLC memory" and the user is returned to the main menu.
No Aborts the upload action and returns the user to the PL7-OSI main menu.
• For a V5 level station, The XTEL-TRANSFER screen is displayed with its dialog box:
The OSI function is automatically selected, select Transfer to start the transfer action.
As described previously, for the transfer to be successful, XTEL-TRANSFER must first have been used to transfer the memory structure for the application that was developed using XTEL-CONF.
__________________________________________________________________________________________
4 / 2
Transfefring Binary and Module Files - Transfer Menu 4
__________________________________________________________________________________________
4.2
Downloading from the PLC
This function transfers the contents of the dedicated OSI field from the PLC memory to the OSI.BIN file on the workstation hard disk.
To perform the download, the workstation must be connected to the PLC.
• For a V4 level station, once the PLC ➙ Disk option is selected from the pulldown menu, the Transfer File dialog box is displayed. The sequence of actions is the same as for an Upload.
• For a V5 level station, the XTEL-Transfer screen is displayed with the OSI function selected. Confirmation of the transfer warns the user that the OSI.BIN file present in the workstation will be replaced with the contents of the PLC's OSI memory field.
D
__________________________________________________________________________________________
4 / 3
__________________________________________________________________________________________
4.3
Uploading to a Module
D
This function transfers a module (.CPL) type file, describing the configuration, to the module memory.
Selecting a file to upload
After selecting the Disk->Module option from the pulldown menu, the File Selection dialog box is displayed.
The user can specify the name of the module (.CPL) file to transfer to the module memory.
To do so, click on the name of the file to upload, in the list of files displayed. The selected file name is displayed in the "Files Selected" field. The user can also use the cursor keys to move the selection bar in the list of files and then press <Enter> to confirm the selection made.
__________________________________________________________________________________________
4 / 4
Transfefring Binary and Module Files - Transfer Menu 4
__________________________________________________________________________________________
OK Proceeds to the next phase: selecting the rack location to upload to, once the user has confirmed the action.
Cancel Cancels file selection, the user is returned to the PL7-OSI main menu.
Selecting the module location
After confirming the module (.CPL) file, the following screen is displayed:
This screen lets the user select the slot in the PLC rack where the target interface module is located. The selection is made by clicking on the slot number. Once the selection is made the slot column changes color. Once the target module location has been selected, the transfer can be made.
D
For V5 level stations, the slots that can be selected are those defined in the I/O configuration established using XTEL-CONF.
OK Starts the transfer once the slot number is selected.
If the transfer fails, the cause of failure is displayed and the user is returned to the Select File window after acknowledging the error message.
Cancel Cancels the operation, the user is returned to the File Selection window and no transfer is made.
Warning:
The configuration loaded in the module is automatically overwritten with the configuration loaded in the PLC if the MMSLD OFB is configured in the PL7-3 application.
__________________________________________________________________________________________
4 / 5
__________________________________________________________________________________________
4.4
Comparing the PLC Memory with the OSI .BIN File
D
This function compares the dedicated OSI field in the PLC memory with the OSI.BIN file stored on disk in the workstation.
To perform the comparison, the workstation must be connected to the PLC.
After selecting Compare from the pulldown menu, the following dialog box is displayed.
Click on Yes, comparison is completed when one of two messages is displayed:
"The OSI.BIN file and the binary file in the PLC are identical" or
"The OSI.BIN binary file and the binary file in the PLC are different".
__________________________________________________________________________________________
4 / 6
Documenting and Printing 5
__________________________________________________________________________________________
5.
Documenting and Printing
The following procedure applies for creating documentation on the configuration of OSI modules in the station:
• Prepare the documentation title page (create an OSI.TIT file),
• Prepare the documentation footer (create an OSI.CRT file),
• Create the application documentation (for storage in an OSI.DOC file), from the
OSI.TIT and OSI.CRT files created previously and the OSI.BIN file that contains the configuration,
• View the finished documentation on-screen or print it out.
The first two steps are performed in the Documentation function (first option in the pulldown menu), the third in the Print function.
5.1
Generating Documentation
Selecting the Generate option starts creation of the documentation for the station OSI application.
It requires that the user first create the title page and footer, described respectively in the OSI.TIT and OSI.CRT files.
The documentation uses the information contained in the OSI.BIN file.
D
__________________________________________________________________________________________
5 / 1
__________________________________________________________________________________________
5.2
View
Selecting this function lets the user immediatly view on-screen, the newly generated documentation.
The user can scroll the documentation vertically and horizontally. The format displayed corresponds to what can be printed-out.
D
5.3
When this function is selected, it first displays the list of printer that can be used for printing out the station documentation file.
The user then free to select from the list of printers connected to the workstation, the one to use for printing out the documentation file. Simply click on the <OK> button to confirm the selection and start printing.
The <Cancel> button lets the user cancel the printing in progress.
Remark
The station documentation file generated by PL7-OSI (the OSI.DOC file) can be printed out separately and it can also be integrated into the complete documentation file for a V4 or V5 level station.
The integration is performed by XTEL-DOC and it is transparent to PL7-OSI.
__________________________________________________________________________________________
5 / 2
Documenting and Printing 5
__________________________________________________________________________________________
5.4
Enter Information
Entering the title page
When this menu is selected, its data entry fields display the contents of the OSI.TIT file, if it already exists. Else all fields are blank.
Access to a predefined field is by mouse or keyboard and Tab key. Within a field, the user can move between columns and lines using the mouse or the cursor keys.
Various entries are possible:
• Title
• Company
• Department
• Manager
• REV.
• DATE
• REVISION
• DESIGNER
• EXECUTED by
: Application title (64 chars. max.),
: Company name (16 chars. max.),
: Department name in the Company (16 chars. max.),
: Manager's name (16 car. max.),
: File revision level (3 chars. max.),
: File creation or modification date (8 chars. max.)
: Comments on the revision made (32 chars. max.),
: Designer's name (12 chars. max.),
: User's name (12 chars. max.),
D
__________________________________________________________________________________________
5 / 3
D
__________________________________________________________________________________________
The OSI.TIT file generated is an editable ASCII file.
OK Saves the contents of the screen to the OSI.TIT file and exits the screen.
Cancel
Write
Exits the screen without saving the OSI.TIT file.
Writes the contents of the screen to the yyy.TIT file specified in a dialog box (the default name is OSI.TIT). This command does not exit the screen.
Read Reads a yyy.TIT file stored during a previous session. The file name is specified in a dialog box (the default name is OSI.TIT).
Entering the custom footer
This screen lets the user customize the footer that appears at the bottom of every documentation file page. Two strings of characters can be filled-in by the user:
• A string of 25 characters at the top of the footer,
• A string of 45 characters at the bottom of the footer.
The fields are filled-in with the contents of the OSI.CRT file, if it already exists.
The documentation footer provides the following information:
• Application name,
• Printed item name,
• Document version number,
• Print-out date,
• Relative page numbering by item,
• Absolute page numbering.
__________________________________________________________________________________________
5 / 4
Documenting and Printing 5
__________________________________________________________________________________________
OK Saves the contents of the screen to the OSI.CRT file and exits the screen.
Cancel Exits the screen without saving the OSI.CRT file.
Write
Read
Writes the contents of the screen to a yyy.CRT file specified in a dialog box (the default file name is OSI.CRT). This command does not exit the screen.
Reads a yyy.CRT file saved during a previous session. Its name is specified in a dialog box (the default file name is OSI.CRT).
D
__________________________________________________________________________________________
5 / 5
__________________________________________________________________________________________
5.5
Documenting a Module
Documenting a module comprises presenting in a printable ASCII format, the contents of an xxx.CPL configuration file. The file generated will retain the name of the xxx.CPL
file and take the "OSI" extension.
D
As usual with a "Select File" dialog box, the user can select a file from the list of module
(.CPL) type files known to the station by:
• Double clicking on the file to select,
• Using the cursor keys to select the required file and pressing <Enter>.
If there are no .CPL files available, the Select File box is replaced by the message "No files to select!".
OK
Cancel
Formats an xxx.OSI ASCII file from the selected xxx.CPL file.
Cancels the action. No xxx.OSI file is generated.
__________________________________________________________________________________________
5 / 6
Deleting Files - Configuration Set-Up - Help 6
__________________________________________________________________________________________
6.1
Utilities - Deleting Files
The Delete utility lets the user delete all of the files generated by PL7-OSI.
Once this option is selected, simply click on the type of file to delete. Regardless of the file type (except for OSI.BIN files), the procedure is the same:
Select the file from the dialog box that opens and confirm the selection.
Once the file is deleted, control returns to the updated dialog box. This operation can be repeated as many times as there are files to delete.
For the OSI.BIN file, which is a special case as there is only one such file, the file selection step is of course unnecessary.
If no file can be deleted in the selected type, the selection is dimmed and cannot be accessed.
For example, the screen that is displayed after selecting Module File... (.CPL) is shown below:
D
__________________________________________________________________________________________
6 / 1
__________________________________________________________________________________________
OK Deletes the file listed in the "Files selected" field, after requesting user confirmation.
Cancel Cancels the action. No files are deleted.
6.2
Utilities - Debugging an OSI Configuration
D
This option allows the user to modify, for debug purposes, the OSI parameters of a module, previously loaded into the dedicated OSI field of the PLC memory.
Once confirmed, the new configurations are automatically transferred by OFB into the appropriate modules.
Remark
These configurations are not saved locally in the xxx.CPL files.
This function displays an on-screen representation of a PLC rack and uses the procedure for modifying a PLC configuration (PLC Configuration function for OSI.BIN
files, as described in Sub-section 3.3-2).
__________________________________________________________________________________________
6 / 2
Deleting Files - Configuration Set-Up - Help 6
__________________________________________________________________________________________
Click on the PLC slot number where the module, whose parameters require modification is located, to access the module parameter setup screens.
D
OK
Cancel
Help
Calls-up the screen shown above.
No modifications are made.
Select the module configuration action to access the modification screen. Refer to Subsection 3.3-2.
__________________________________________________________________________________________
6 / 3
__________________________________________________________________________________________
6.3
Utilities - Restoring/Saving an OSI.BIN File
The Restore function allows the user to import an OSI.BIN binary file from a diskette or hard disk, into the station memory field. The newly imported file replaces the existing
OSI.BIN file.
The Save function allows the user to copy the OSI.BIN file from the station to another directory on the hard disk or diskette.
D
6.3-1 Restore
If the Restore option is selected, type the source file name in the field displayed by the dialog box:
OK Copies the selected file to the OSI.BIN file, once the action is confirmed by the user when prompted by the following message:
"This action will overwrite the existing OSI.BIN file. Please confirm the operation."
Cancel Cancels the action and returns the user to the PL7-OSI main menu.
For V5 level stations, if the I/O configuration was not previously defined using
XTEL-CONF, it is not possible to restore the OSI.BIN file. In addition, a coherence check is performed to ensure that the module locations defined in the restored file do indeed correspond to the I/O configuration.
__________________________________________________________________________________________
6 / 4
Deleting Files - Configuration Set-Up - Help 6
__________________________________________________________________________________________
6.3-2 Save
If the Save option is selected, type the target file name in the field displayed by the dialog box and validate it:
If the file already exists, the user will be warned by a message and a request to confirm.
D
__________________________________________________________________________________________
6 / 5
D
__________________________________________________________________________________________
6.4
Help
The Help option in the pulldown menu lets the user access to root directory of PL7-OSI help screens.
The About... option displays information on the current version of the installed software.
__________________________________________________________________________________________
6 / 6
Appendix 7
__________________________________________________________________________________________
7.
Appendix
Directory File Format
The OSIPRJ.REP file can be created using a standard text editor. The file can then be added to the X-TEL data base using the Restore function (refer to Divider D, Sub-section
3.1-3).
To be used with the X-TEL Software Workshop, the directory file must comply with certain rules:
• The file comprises lines that describe remote applications,
• An application is described by a string of variables within a / character as prefix and suffix,
• The values are those of the parameters that define an application and they must be placed in the line in the following sequence: Application_Name, Ap_Title, Ae_Qualifier,
Psel, Ssel, Tsel, Nsap,
• The values of any optional parameters can be omitted, however the / separator characters must be retained,
D
• A # character placed at the start of the line indicates that the line is a comment.
Exemple:
#OSI_PRJ Directory
#
#Format:
#/APPLICATION_NAME/AP_TITLE/AE_QUALIFIER/PSEL/SSEL/TSEL/NSAP/
#
/APPLICATION1///00000004/0003/0001/39840F454E45000000010001410901/
/APPLICATION2///00000003/0001/0001/39840F544E45000000010001010101/
/APPLICATION3/123//00000004/0001/0001/39840F544E45000000010003000601/
<EOF>
__________________________________________________________________________________________
7 / 1
D
__________________________________________________________________________________________
__________________________________________________________________________________________
7 / 2
________________________________________________________
PL7-MMS E
___________________________________________________________________________
Section
1 General
1.1
PL7-MMS Presentation
1.2
PL7-MMS Function
1.2-1 Creating the Project Level Directory of Variables
1.2-2 Creating, Viewing, Uploading and Documenting
Station Variables at Project Level
1.2-3 Converting an Application
1.3
Accessing PL7-MMS
Page
1/1
1/1
1/1
1/2
1/3
1/5
2 Selecting the Working Memory - Memory Menu
2.1
Memory Menu 2/1
3 Configuring Variables
3.1
Editing the MMS Directory at Project Level
3.1-1 Defining Remote Variables
3.1-2 Defining Structures Associated with Remote Variables
3.2
Configuring Remote Variables
3.3
Configuring Local Variables
3.3-1 Defining Local Variables
3.3-2 Defining Structures Associated with Local Variables
3.4
Generating an MMS.BIN Binary File
3/1
3/2
3/6
3/11
3/14
3/14
3/18
3/20
E
4 Transferring Binary Files
4.1
Uploading to the PLC
4.2
Downloading from the PLC
4.3
Comparing the PLC Memory with a Binary File
4/1
4/2
4/3
___________________________________________________________________________
E / 1
________________________________________________________
A
___________________________________________________________________________
Section
5 Documenting and Printing
5.1
Generating the Documentation
5.2
View
5.3
5.4
Entering Information
Page
5/1
5/2
5/2
5/3
E
6 Viewing MMS Binary Files - Deleting Files - Help
6.1
Viewing MMS Binary Files
6.1-1 Viewing a Binary File on the Workstation
Disk
6.1-2 Viewing the Bianry File Stored in the PLC
6.2
Deleting Files
6.3
Saving/Retrieving MMS Binary Files
6.4
Help
7 Appendix
Project Directory File Format 7/1
6/1
6/1
6/3
6/3
6/4
6/5
___________________________________________________________________________
E / 2
General 1
__________________________________________________________________________________________
1.1
PL7-MMS Presentation
PL7-MMS is a Station level function tool, a sub-set of PL7-OSI 3.0.
PL7-MMS lets the user define all of the MMS variables at project level, in the XTEL context, that are visible to all stations. It also supports the selection, for a given station, of "client" variables, i.e. remote variables that are visible to the station. In addition, it also lets the user define, for a given station, "server" symbols, i.e. local symbols (in the selected station) that are visible to other stations.
The MMS variable management function is provided by two software sub-sets:
• PL7-MMS variable definition software, implemented on an FTX 507 station running the XTEL Software Workshop,
• PL7-3 (OFB) Optional Function Block software implemented on the TSX and PMX
Series 7 PLCs.
The following Sub-sections describe the functions and operating modes of PL7-MMS software.
The OFB software is described separately in Divider F.
1.2
PL7-MMS Functions
1.2-1 Creating the Project Level Directory of Variables
Configuring an MMS project directory
Creation or modification of the MMS project directory. This directory is a single ASCII file for all of the stations in the same project. This file is saved at project level in the XTEL file structure.
This file can also be created by other tools such as text editors, word processors, etc.
In this case, the file must be restored to the XTEL base using the "Restore" command.
E
__________________________________________________________________________________________
1 / 1
E
__________________________________________________________________________________________
1.2-2 Creating, Viewing, Uploading and Documenting Station Variables at Project Level
Configuring an MMS binary file
Creating or modifying the MMS binary file (MMS.BIN) with the configuration of station symbole, visible to the other stations and/or remote symbols. The MMS.BIN file can be loaded into the station PLC.
Uploading an MMS binary file
Loading the MMS.BIN file into the dedicated MMS field in the PLC memory, from the workstation disk (using XTEL-TRANSFER for V5 level stations).
Downloading an MMS binary file
Downloading (backing-up) an MMS.BIN file from the dedicated MMS field in the PLC memory to the workstation disk (using XTEL-TRANSFER for V5 level stations).
Comparing files
Comparing the MMS.BIN file with the dedicated MMS field in the PLC memory to check that they are identical.
Viewing an MMS binary file
On-screen viewing of the contents of an MMS.BIN file stored on the workstation hard disk or of the dedicated MMS field in the PLC memory.
Documenting the station
Creating the documentation for an MMS.BIN file.
Creating the MMS. DOC file and the option to create MMS.TIT and MMS.CRT ASCII files.
Deleting a file
Deleting configuration or documentation files.
__________________________________________________________________________________________
1 / 2
General 1
__________________________________________________________________________________________
1.2-3 Converting an Application
This function is used to convert all or part of the files that make up a V43 or V5 level MMS application for migration to V52 level.
This function can be invoked in a number of cases:
• When the program is first started, the presence of an MMS Server base with a version level prior to V52 is detected. A message prompts the user to perform the conversion.
If the MMS function detects a binary file with a version level prior to V52, it will be converted automatically. The conversion also comprises files related to the current application.
The presence of an MMS Server base with a version level prior to V52 inhibits all MMS program functions except the Exit and Conversion functions.
• While MMS is being used, if the program detects the presence of a binary file with a version level prior to V52. The user will be prompted to perform a conversion but this does not inhibit the other functions of PL7-MMS.
As appropriate, the conversion will be performed on the station MMS Server base, the station MMS.BIN binary file or on the documentation file. There are six possible cases:
• First time PL7-MMS V52 is run on the current station
The program detects an MMS Server base and/or an MMS.BIN file with a version level prior to V52.
Action:
Result:
Select the Utilities/Conversion function, then invoke Conversion.
The MMS Server base will be updated along with its binary file, if this is necessary.
• Using the PL7-MMS V52 Documentation/Generate function
This function detects a V52 level base but the MMS.BIN binary file present in the station has a version level prior to V52.
Action:
Result:
Select the Utilities/Conversion function, then invoke the Conversion and
Documentation/Generate actions.
The MMS.BIN file is updated to V52 level and the documentation is generated.
• Using the PL7-MMS V52 Transfer/Disk --> PLC function
This function detects a V52 level base but the MMS.BIN binary file present in the station has a version level prior to V52.
Action:
Result:
Select the Utilities/Conversion function, then invoke the Conversion and
Transfer/Disk --> PLC actions.
The MMS.BIN file is updated to V52 level and the transfer is performed.
__________________________________________________________________________________________
1 / 3
E
E
__________________________________________________________________________________________
• Using the PL7-MMS V52 Transfer/PLC --> Disk function
This function detects a V52 level local base and MMS.BIN binary file, but the MMS.BIN
file present in the PLC has a version level prior to V52.
Action: Save the local binary file, if necessary, prior to invoking
Transfer/PLC -> Disk.
Result: The local V52 level MMS.BIN file is replaced by the MMS.BIN binary file with a version level prior to V52, taken from the PLC.
• Using the PL7-MMS V52 Utilities/View function in local memory
This function detects a V52 level base but the MMS.BIN binary file present in the station has a version level prior to V52.
Action : Select the Utilities/Conversion function, then invoke the Conversion and
Utilities/View actions.
Result : The MMS.BIN file is updated to V52 level and viewing of the file is allowed.
• Selecting the PL7-MMS V52 Utilities/View function in PLC memory
This function detects a V52 level base but the MMS.BIN binary file present in the PLC has a version level prior to V52.
Action : Save the local binary file, if necessary, prior to invoking
Transfer/PLC -> Disk. Then invoke the Utilities/Conversion and
Utilities/View (in local memory) or Transfer/Disk --> PLC (in PLC memory) actions.
Result: The MMS.BIN file is updated to V52 level and viewing of the file is allowed.
__________________________________________________________________________________________
1 / 4
General 1
__________________________________________________________________________________________
1.3
Accessing PL7-MMS
The user can access the MMS variable configuration software by opening the MMS window corresponding to the station for which MMS variable should be defined.
Primary window
Ecran principal PL7 MMS
Remark
To define variables for the entire project or to define variables for a station, the user must use the PL7-MMS program corresponding to a station in the project.
Menu levels
Memory Configuration (1)
Local
Transfer Documentation (1) Utilities
Conversion
MMS Project Directory Disk ➙ PLC Generate
PLC Remote Variables PLC ➙ Disk View
View
Delete (1)
Local Variables Compare Print Restore (1)
PLC Conf.
Enter Information Save (1)
(1) Options that cannot be selected when PLC memory is selected
Memory Selects the working memory.
Configuration Configures MMS variables, calls-up XTEL-SDBASE, generates the MMS.BIN file.
Transfer Uploads, downloads and compares MMS. BIN files between the dedicated MMS field and the PLC memory and vice versa. These actions are performed via XTEL-TRANSFER for V5 level stations and via PL7-MMS functions for V4 level stations.
__________________________________________________________________________________________
1 / 5
E
E
__________________________________________________________________________________________
Documentation Creates customized documentation for the MMS application and allows the user to view and print this documentation.
Utilities • Displays a binary file:
- Present on-disk, if the working memory is the local memory,
- Present in the PLC, if the working memory is the PLC memory.
• Deletes the MMS.BIN, MMS.SCY, MMS.CST, MMS.CRT,
MMS.TIT, MMS.DOC and MMS.STR files from the workstation disk.
• Saves and Restores MMS.BIN files.
Exit
Help
Quits PL7-MMS.
Calls-up on-line help screens.
__________________________________________________________________________________________
1 / 6
Selecting the Working Memory - Memory Menu 2
__________________________________________________________________________________________
2.1
Memory Menu
The PL7-MMS main menu lets the user select one of two working environments: Local memory, where the workstation disk is used or PLC memory.
When Local memory is selected, all functions can be accessed. The configuration of local or remote MMS symbols, project level directory configuration and the documentation can be defined without requiring connection to a PLC.
When PLC memory is selected, MMS variable configuration and file delete, save and restore actions cannot be performed. Naturally workstation connection to the PLC must be established in local mode via the PLC programming port, or in remote mode via station connection to a network.
Inhibited functions are dimmed in the main menu.
The table below summarizes the functions available in the various environments.
FUNCTIONS
MMS Variable Configuration
Transfer\Disk ➙ PLC
Transfer\PLC ➙ Disk
Transfer\Compare
Documentation
Utilities\View
Utilities\Delete
Utilities\Restore
Utilities\Save
Utilities\Conversion
WORKING MEMORY
Yes
Yes
Yes
Yes
Yes
Local
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
PLC
No
Yes
Yes
Yes
No
E
__________________________________________________________________________________________
2 / 1
__________________________________________________________________________________________
E
__________________________________________________________________________________________
2 / 2
Configuring Variables 3
__________________________________________________________________________________________
3.
Configuring Variables
The purpose of this function is to establish the list of variables for the entire project, i.e.
for all stations in the XTEL project. Then for each station, the user will need to establish a list of remote variables that are visible to the station along with a list of local variables that are visible to other stations.
The remote or local variables can be simple or structured types. When they are structured, the structure format must be described.
The Configuration action also allows the user to generate an MMS.BIN binary file that can be loaded into the PLC.
3.1
Editing the MMS Directory at Project Level
Selecting Configuration\MMS Project Directory will display the following menu:
E
This function lets the user establish a list of simple or structured variables for the entire project.
The Define Remote Variables sub-menu lets the user define a list of project variables.
The Define Structures sub-menu lets the user describe the format of structures assigned to STRUCT type variables.
__________________________________________________________________________________________
3 / 1
__________________________________________________________________________________________
3.1-1 Defining Remote Variables
Selecting Define Remote Variables will display the following menu.
Selecting Enter, displays the Variable Editor with the following screen
E
The records, where they exist, are shown as a list in alphabetical order.
The various fields in a record can be filled-in and comprise:
Application Name
This field identifies the MMS application that the variable belongs to. An application name comprises alphanumeric characters and is restricted to a maximum length of 32 characters.
Variable Name
This field identifies the MMS variable. A variable name comprises the following characters: A to Z, a to z, 0 to 9 and $, _
A variable name cannot begin with a number and is restricted to a maximum length of
32 characters.
Scope
This field defines the scope of the MMS variable. The values allowed are VMD, DOMAIN and AA.
__________________________________________________________________________________________
3 / 2
Configuring Variables 3
__________________________________________________________________________________________
Dom/Appli Name
If the scope of the variable is defined as DOMAIN, this field must be filled-in to indicate the name of the domain. A domain name comprises the following characters: A to Z, a to z, 0 to 9 and $, _
A domain name cannot begin with a number and is restricted to a maximum length of
32 characters.
If the scope of the variable is defined as AA this field must be filled-in to indicate the name of the application that has the right to access the variable.
Type
This field defines the type of MMS variable.
Type Inf
For some types, additional information is required. This is the purpose of the Type_Inf field. E.g. when using a Table type variable, the Type_Inf field indicates the number of elements in the table.
Type of MMS Variables - Simple Type
BOOL
INT16
INT32
UINT16
UINT32
BSTR
VSTR
OSTR
STRUCT
FLOAT
: Boolean
: 16-bit signed integer
: 32-bit signed integer
: 16-bit unsigned integer
: 32-bit unsigned integer
: BitString
: VisibleString (character string)
: OctetString (byte string)
: Structure
: Floating point simple precision
Type_Inf
1...2048
2...4096-even
2...4096-even
E
Type of MMS Variables - Table Type
AR-BOOL
AR-INT16
AR-INT32
AR-UINT16
AR-UINT32
AR-BSTR1
: Boolean table
: 16-bit signed integer table
: 32-bit signed integer table
: 16-bit unsigned integer table
: 32-bit unsigned integer table
: BitString1 table
AR-VSTR2
AR-OSTR2
: VisibleString (character string) table
: OctetString (byte string) table
AR-STRUCT : Structure table
AR-FLOAT : Floating point simple precision table
Type_Inf
Number of table elements up to a maximum
MAX = 1024
__________________________________________________________________________________________
3 / 3
E
__________________________________________________________________________________________
Once all record fields are filled-in, the user can select the following actions:
Add
To add the new MMS variable to the existing list.
Modify
To replace the selected record with the newly entered one.
Delete
To delete the record selected from the list.
A single click on a record in the list will select it. A double click will select it and allow the user to fill-in the data entry fields. This operation provides the user with an easy way of changing a field in the record.
The list can display up to 512 MMS variables. The Next and Return buttons are used to view all of the variables, when their total number exceeds 512. The maximum number of variables is restricted to 2048.
Once data entry is complete, the following functions can be selected:
OK
To validate all of the modifications made. Selecting OK will generate the project file. This file is an ASCII file that contains all of the records.
Once generation is complete, a message indicates that the MMS Project directory has been generated and a new screen displayed.
Cancel
To Quit the editor without making any changes. This action must be confirmed.
__________________________________________________________________________________________
3 / 4
Configuring Variables 3
__________________________________________________________________________________________
Selecting Retrieve will display the following window so that the user can designate a file by its name and access path.
This function lets the user import variables defined in a generic file stored in Telemecanique format. A Retrieve action will overwrite any existing MMS_PRJ.REP project directory.
E
__________________________________________________________________________________________
3 / 5
__________________________________________________________________________________________
In the same way, a project directory can be saved for reuse from another station, for example.
Enter the directory path and name:
E
3.1-2 Defining Structures Associated with Remote Variables
Selecting Define Structures will display the following menu.
Selecting Enter, displays the structured variables format entry screen:
__________________________________________________________________________________________
3 / 6
Configuring Variables 3
__________________________________________________________________________________________
The screen will then display two lists:
• A list of structures: To add or modify a structure name, to delete or select a structure,
• A list of elements in the structure to describe the format of the structure selected from the list of structures.
Important:
The user must define a structure for each structured type variable (STRUCT) in the project directory. The name of the structure built must be the same as the name of the
MMS variable defined in the project directory.
The principle is to create a list of structure names and then, for each structure, configure a list of elements that compose the structure.
To prepare the list of structures, the following actions are allowed:
Add
Modify
Delete
Adds a new structure name to the list.
Modifies the name of the structure selected from the list.
Deletes the name of the structure from the list.
After entering a structure name, the user must describe the elements that form the structure by filling-in the various fields:
Element Name This field lets the user give each element in the structure a different name. An element name comprises alphanumeric characters and is restricted to a maximum length of 32 characters.
Type
Type Info
This field defines the type of element in the structure.
For some types, additional information is required. This is the purpose of the Type_Inf field.
E.g. when using a Table type variable, the Type_Inf field indicates the number of elements in the table.
E
__________________________________________________________________________________________
3 / 7
__________________________________________________________________________________________
Type of MMS Structure Elements - Simple Type Type_Inf
BOOL
INT16
INT32
UINT16
UINT32
BSTR
VSTR
OSTR
STRUCT
FLOAT
: Boolean
: 16-bit signed integer
: 32-bit signed integer
: 16-bit unsigned integer
: 32-bit unsigned integer
: BitString
: VisibleString (character string)
: OctetString (byte string)
: Structure
: Floating point simple precision
1...2048
2...4096-even
2...4096-even
E
Type of MMS Structure Elements - Table Type
AR-BOOL
AR-INT16
AR-INT32
AR-UINT16
AR-UINT32
AR-BSTR1
: Boolean table
: 16-bit signed integer table
: 32-bit signed integer table
: 16-bit unsigned integer table
: 32-bit unsigned integer table
: BitString1 table
AR-BSTR16 : BitString16 table
AR-VSTR2 : VisibleString (character string) table
AR-OSTR2 : OctetString (byte string) table
AR-STRUCT : Structure table
AR-FLOAT : Floating point simple precision table
Type_Inf
Number of table elements up to a maximum
MAX = 1024
MAX = 1024
Once all record fields for an element selected from the list are filled-in, the user can select the following actions:
Modify To replace the element selected from the list with the element described in the various data entry screens.
Delete
Insert before
To delete the element selected from the list.
To add the new element to the list before the element selected in the list.
Insert after To add the new element to the list after the element selected in the list.
The user can declare all elements forming each structure and their types in the same way.
__________________________________________________________________________________________
3 / 8
Configuring Variables 3
__________________________________________________________________________________________
Warning
A structured MMS variable comprises a series of simple type elements. To program reading or writing of a structured variable using the MREAD or MWRIT OFBs (refer to Divider F), ensure that a string of Wi words is reserved for them and respect the memory organization conventions are follows:
Each element in a structured variable is aligned with the start of a Wi word, regardless of the actual space required to store the field value.
Warning
If the MMS variable type is AR_STRUCT (and not STRUCT), the description of the structured variable as entered after selecting the Define Structures action from the menu, must not comprise AR_x type elements. The Type_Inf field in the description of the variable after selecting Define Remote Variables from the menu must contain the number of elements from the AR_STRUCT table (the number of structures).
This number is restricted to 16 elements, given that the maximum size of a
STRUCTURE or an AR_STRUCTURE can never exceed 4 Kbytes.
Example:
ALARM_TEMPERATURE
{ Number
Status
: Integer16
: BitString18
Location
Identification
: OctetString6
: Array of 3 Boolean }
If the MMS variable: ALARM_TEMPERATURE is assigned to the PL7-3 variable W0 the result is:
Number
Status
Location
Identification
Placed in word W0.
Placed in words W1 and W2 using bits W1,0...W1,15 and W2,0...W2,1.
Placed in words W3, W4 and W5.
Placed in word W6 using bits W6,0...W6,2.
E
Once data entry is complete for the list of structures and their elements, the following functions can be selected:
OK
To validate all of the modifications made. Selecting OK will generate the project file. This file is an ASCII file that contains all of the structures and their formats.
Once generation is complete, a message indicates that the MMS Project directory has been generated and a new screen displayed.
Cancel
To Quit the editor without making any changes. This action must be confirmed.
__________________________________________________________________________________________
3 / 9
__________________________________________________________________________________________
Selecting Retrieve will display the following window so that the user can designate a file by its name and access path.
This function lets the user import structures defined in a generic file stored in
Telemecanique format. A Retrieve action will overwrite any existing structures file present at project level.
E
In the same way, a structures file can be saved for reuse from another station, for example.
__________________________________________________________________________________________
3 / 1 0
Configuring Variables 3
__________________________________________________________________________________________
Enter the directory path and name:
3.2
Configuring Remote Variables
Selecting Configuration - Remote Variables will call-up an XTEL-SDBASE screen to allow the user to modify data base symbols.
This function lets the user declare, for the currently selected station, a list of remote MMS variables to be read or written. These variables will be taken from the variables available in the project directory.
Remote variables all also referred to as "Client" variables.
To configure a remote variable, simply associate a project directory variable to a symbol designating a CWi object in the data base. This symbol is called a PL7-3 Alias. The Alias is used by PL7-3 OFBs to access MMS variables.
E
__________________________________________________________________________________________
3 / 1 1
__________________________________________________________________________________________
The configuration procedure is as follows:
1. Create a PL7-3 Alias in the PL7-3 window. To do this, enter a CWi in the Variable column and an associated symbol in the Symbol column. The variable entered can have a comment of up to 24 characters.
2. The newly defined symbol is then repeated in the Symbol data entry field in the top
MMS screen, once the user has confirmed the previous data entry made. There are two possible cases:
• The symbol is already assigned to an MMS variable in the MMS project directory and this variable and its characteristics will be displayed in the MMS window,
• The symbol is not assigned to an MMS variable so that the user can select the
Application Name field, and then press <Spacebar> followed by <Enter> to display a window with a list of all of the variables in the project directory. At this point simply select a variable from the list so that it will be automatically assigned to the newly entered symbol.
The symbol can be selected faster if the user knows the name of the application where the variable is located.
From the window that displays the list of variables, the user can enter the
Application Name in a dedicated field and confirm the entry.
The list will then start its display from the first variable belonging to this application.
Warning
A PL7-3 Alias is always a symbol assigned to a CW object.
E
PL7-MMS creates the constant source file MMS.CST, in a fully user-transparent manner. This file contains the PL7-3 Aliases with as the value of each Alias, the position in the table of remote symbols of the MMS variable that it is assigned to.
__________________________________________________________________________________________
3 / 1 2
Configuring Variables 3
__________________________________________________________________________________________
MMS.CST file example:
Alarm
LED
Pressure
= 0
= 1
= 2
The MMS.CST file must be read by the READ function accessed via 3 - CONSTANT in
PL7-3.
To ensure that each Alias generated in PL7-MMS exists in the PL7-3 base, the tool automatically generates an MMS.SCY file that contains each Alias and its corresponding CWi.
MMS.SCY file example:
CW10 = Alarm
CW11 = Led
CW12 = Pressure
The constant words used are not necessarily consecutive in memory.
The MMS.SCY file can be merged with the other symbols in XTEL-SDBASE in the Local station, if the user has any doubt whether all symbols are valid. Therefore, to program a read action, simply designate the variable with the XTEL-SDBASE Alias that represents it in PL7-3. Programming exchange OFBs is simplified in this way and is performed using symbolic programming. The Alias is entered as an input parameter for the MREAD, MWRITE and MURCV OFBs.
Important
The maximum number of remote variables is set to 512 per station.
E
Warning
Any modification to the Project Directory, variables or structures can create incoherences between the files of station variables or structures. No automatic check is performed to ensure coherence between project files and station files. The user must always ensure coherence.
In the same way, the user must ensure data coherence in constant word (CST/SCY) files and the structure definition files. For this reason, it is recommended that all files be saved each time a Save action is performed.
__________________________________________________________________________________________
3 / 1 3
__________________________________________________________________________________________
3.3
Configuring Local Variables
Selecting Configuration - Local Variables will display the following menu.
E
3.3-1 Defining Local Variables
Selecting Define Local Variables will call-up an XTEL-SDBASE screen so that the user can manage data base symbols.
This function is designed to allow the user to declare, for the station being programmed, the list of local MMS variables that are visible to, and accessible by other stations in the project. These variables can be read or written by other stations, including stations outside of the XTEL project.
The local variables are also referred to as Servers.
To configure a local variable, simply assign a symbol designating an MMS variable to a symbol designating a PL7-3 object in the data base.
The configuration procedure is described below:
1. Enter the values for the VALUE, SYMBOL and COMMENT in the PL7-3 view:
VALUE: The name of a PL7-3 object (Wi, CWi, etc.) in 21 alphanumeric characters,
SYMBOL: An MMS variable alias for use by XTEL-SDBASE in 8 alphanumeric characters,
COMMENT: Lets the user assign a comment of up to 32 alphanumeric characters to the MMS variable.
2. Once the symbol is defined, it is automatically copied to the symbol window in the
MMS view.
• If this symbol is already assigned to an MMS variable, then the MMS variable and its characteristics are displayed in the MMS view,
• If this symbol is not assigned to an MMS variable, then the Variable Name,
Scope, Type, Type_Inf and Application Name fields are blank and must be filledin.
__________________________________________________________________________________________
3 / 1 4
Configuring Variables 3
__________________________________________________________________________________________
The various fields in an MMS variable record comprise:
Variable Name
This field identifies the MMS variable. A variable name comprises the following characters: A to Z, a to z, 0 to 9 and $, _
A variable name cannot begin with a number and is restricted to a maximum length of
32 characters.
Scope
This field defines the scope of the MMS variable. The values allowed are VMD, DOMAIN and AA. When an AA (Association) scope is selected, the user must give an application name in the appropriate field. In this case only the designated application can access the variable. The scope of a designated variable is filled-in implicitly with default values selected according to the PL7-3 object.
PL7-3 Object
SYi
Bi, Wi,j
Wi, SWi, CWi
DWi, CDWi
Array of Bi
Array of Wi, CWi
Array of DWi, CDWi
Default MMS Scope
VMD
DOMAIN
DOMAIN
DOMAIN
DOMAIN
DOMAIN
DOMAIN
Type
This field lets the user define the type of MMS variable. The type field is filled-in implicitly with default values selected according to the PL7-3 view Value field. This field can be modified to select table type variables or to enter other valid types.
• Valid simple types are:
BOOL, INT16, INT32, UINT16, UINT32,
BSTR, VSTR, OSTR, STRUCT, FLOAT.
• Valid table types are:
AR-BOOL, AR-INT16, AR-INT32, AR-UINT16, AR-UINT32,
AR-BSTR1, AR-BSTR16, AR-VSTR2, AR-OSTR2, AR-STRUCT, AR-FLOAT.
Access Mode
This field identifies the access mode selected for a local variable in the MMS application defined in the PLC. Its value is AUTO (the default value to ensure that the Server
Automatic level as defined for V51 is provided) or PROG.
E
__________________________________________________________________________________________
3 / 1 5
__________________________________________________________________________________________
Type Inf
For some types, additional information is required. This is the purpose of the Type_Inf field.
E.g. when using a Table type variable, the Type_Inf field indicates the number of elements in the table.
PL7-3 Object
SYi
Bi, Wi,j
Wi, SWi, CWi
DWi, CDWi
Array of Bi
Array of Wi, CWi
Array of DWi, CDWi
Default MMS Type
Boolean
Boolean
Integer16
Integer32
Array of Boolean
Array of Integer16
Array of Integer32
MMS Default Type
Boolean
Integer16
E
Integer32
Array of Boolean
Array of Integer16
Array of Integer32
Valid Corresponding Types
BitString1
Unsigned16, BitString16
OctetString2, VisibleString2
Unsigned32
Floating Point Simple Precision
Array of BitString1, BitStringN
Array of Unsigned16
Array of BitString16
Array of VisibleString2
Array of OctetString2
OctetString2N, VisibleString2N
Array of Unsigned32
Array of Floating Point
__________________________________________________________________________________________
3 / 1 6
Configuring Variables 3
__________________________________________________________________________________________
MMS Type
BitString
OctetString
VisibleString
Array of OctetString2
Array of VisibleString2
Array of Boolean
Arrary of BitString1
Array of Integer16
Array of Unsigned16
Array of BitString16
Array of Integer 32
Array of Unsigned32
Array of Float
Max. Number of Elements
1...2048
2...4096 - Even
2...1024 - Even
1024
1024
1024
Application Name
This field identifies the remote application that is attempting to access the variable. This field must be filled-in when a variable is assigned an AA (Association) scope. Only an application name designated in this way can access this variable. An application name comprises alphanumeric characters and is restricted to a maximum length of 32 characters.
E
__________________________________________________________________________________________
3 / 1 7
__________________________________________________________________________________________
3.3-2 Defining Structures Associated with Local Variables
Selecting Define Structures displays the structured variables format entry screen:
E
The procedure for entering structures associated with local variables is the same as that described for remote variables (refer to Sub-section 3.1-2).
The screen displays two lists:
• A list of structures: To add or modify a structure name, to delete or select a structure,
• A list of elements in the structure to describe the format of the structure selected from the list of structures.
Warning
The user must define a structure for each structured type variable (STRUCT) in the project directory. The name of the structure built must be the same as the name
of the MMS variable defined in the project directory.
The principle is to create a list of structure names and then, for each structure, configure a list of elements that compose the structure.
To prepare the list of structures, the following actions are allowed:
Add Adds a new structure name to the list.
Modify Modifies the name of the structure selected from the list.
Delete Deletes the name of the structure from the list.
__________________________________________________________________________________________
3 / 1 8
Configuring Variables 3
__________________________________________________________________________________________
After entering a structure name, the user must describe the elements that form the structure by filling-in the various fields:
Element Name This field lets the user give each element in the structure a different name. An element name comprises alphanumeric characters and is restricted to a maximum length of 32 characters.
Type
Type Inf
This field defines the type of element in the structure.
For some types, additional information is required. This is the purpose of the Type_Inf field.
E.g. when using a Table type variable, the Type_Inf field indicates the number of elements in the table.
The list of valid types is the same as that described in Sub-section 3.1-2 for remote variables.
Once all record fields for an element selected from the list are filled-in, the user can select the following actions:
Modify To replace the element selected from the list with the element described in the various data entry screens.
Delete To delete the element selected from the list.
Insert before To add the new element to the list before the element selected in the list.
Insert after To add the new element to the list after the element selected in the list.
The user can declare all elements forming each structure and their types in the same way.
Warning
A structured MMS variable comprises a series of simple type elements. To program reading or writing of a structured variable using the MREAD or MWRIT OFBs (refer to Divider F), ensure that a string of Wi words is reserved for them and respect the memory organization conventions as described in Sub-section 3.1-2 for remote variables.
Warning
If the MMS variable type is AR_STRUCT (and not STRUCT), the description of the structured variable as entered after selecting the Define Structures action from the menu, must not comprise AR_xxx type elements. The Type_Inf field in the description of the variable after selecting Define Remote Variables from the menu must contain the number of elements from the AR_STRUCT table (the number of structures, refer to Sub-section 3.1-2).
E
__________________________________________________________________________________________
3 / 1 9
__________________________________________________________________________________________
Once data entry is complete for the list of structures and their elements, the following functions can be selected:
OK
To validate all of the modifications made. Selecting OK will generate the project file. This file is an ASCII file that contains all of the records.
Once generation is complete, a message indicates that the MMS Project directory has been generated and a new screen displayed.
Cancel
To Quit the editor without making any changes. This action must be confirmed.
3.4
Generating an MMS.BIN Binary File
After editing the variables and executing the exit procedure from the editor, the following prompt is displayed:
E
No
Yes
No file will be generated and the user will return to the main menu,
Generates the binary file once the validity of the variables has been checked.
If they are correct, the binary file is generated and a message displayed.
If the validity check fails, a message is displayed telling the user the cause of the failure.
For example when creating a (remote or local) structured variable, STRUCT and the format of the structure has not been defined, the following message is displayed:
"At least one structured variable is incorrect and was not generated in the binary file".
Once confirmed by the operator, the message:
"Binary file generated correctly" indicates that the binary file was generated correctly and the faulty variable put aside.
__________________________________________________________________________________________
3 / 2 0
Transferring Binary Files 4
__________________________________________________________________________________________
4.
Transferring Binary Files
This function lets the user transfer a binary file, generated by the Configuration function, from the terminal hard disk to the PLC or module memory. It can also be used to transfer the contents of the dedicated MMS field in the PLC memory to an MMS.BIN file in the workstation.
This function also supports comparisons between an MMS.BIN binary file on disk and the contents of the dedicated MMS field in the PLC memory.
4.1
Uploading to the PLC
This function lets the user transfer the MMS.BIN binary file to the PLC memory.
Remark
An upload can only be performed if the dedicated OSI field was assigned previously in the PLC memory. To perform the assignment, use the following tools:
• For a V4 level station
XTEL-MEM will generate an application file for configuring the memory (xxx.APP
file). This configuration must include a dedicated OSI field.
XTEL-TRANSFER can then be used to upload to the PLC memory, the newly generated xxx.APP file.
• For a V5 level station
XTEL-CONF is used to create the memory structure for the application file. This tool is used to reserve the necessary PLC memory for the OSI.BIN file.
XTEL-TRANSFER can then be used to upload to the PLC memory, the memory structure and its associated application files (such as OSI.BIN), if they exist.
To perform the upload, the workstation must be connected to the PLC.
E
__________________________________________________________________________________________
4 / 1
__________________________________________________________________________________________
Once the Disk->PLC action is selected from the pulldown menu, the following dialog box is displayed:
Yes Starts the transfer. The message "Transferring..." is displayed to inform the user that the operation is being performed and once it is complete, the message "Binary file transferred correctly" is displayed.
No Aborts the upload action and returns the user to the PL7-MMS main menu.
When execution is complete, the message "Binary file correctly uploaded to the PLC" is displayed.
E
4.2
Downloading from the PLC
This function transfers the contents of the dedicated MMS field from the PLC memory to the MMS.BIN file on the workstation hard disk.
To perform the download, the workstation must be connected to the PLC.
Once the PLC ➙ Disk option is selected from the pulldown menu, the PLC ➙ Disk
Transfer dialog box is displayed. The sequence of actions is the same as for an Upload.
__________________________________________________________________________________________
4 / 2
Transferring Binary Files 4
__________________________________________________________________________________________
4.3
Comparing the PLC Memory with a Binary File
This function compares the dedicated MMS field in the PLC memory with the MMS.BIN
file stored on disk in the workstation.
To perform the comparison, the workstation must be connected to the PLC.
The procedure is the same as Uploading or Downloading the PLC.
After selecting Compare from the pulldown menu, the comparison is completed when one of two messages is displayed:
"The MMS.BIN file and the binary file in the PLC are identical" or
"The MMS.BIN binary file and the binary file in the PLC are different".
E
__________________________________________________________________________________________
4 / 3
__________________________________________________________________________________________
E
__________________________________________________________________________________________
4 / 4
Documenting and Printing 5
__________________________________________________________________________________________
5.
Documenting and Printing
The following procedure applies for creating documentation on the configuration of
MMS variables in the station:
• Prepare the documentation title page (create an MMS.TIT file),
• Prepare the documentation footer (create an MMS.CRT file),
• Create the application documentation (for storage in an MMS.DOC file), from the
MMS.TIT and MMS.CRT files created previously and the MMS.BIN file that contains the local/remote I/O descriptions and the MMS.CST, MMS.SCY and MMS.STR files,
• View the finished documentation on-screen or print it out.
5.1
Generating the Documentation
Selecting the Generate option starts creation of the documentation for the station MMS application.
It requires that the user first create the title page and footer, described respectively in the MMS.TIT and MMS.CRT files.
The documentation uses the information contained in the MMS.BIN file that contains the list of variables defined for the station.
The documentation displays the list of MMS variables in two parts, local variables and remote variables (either of these two parts may be absent).
Each variable is described with all of its MMS characteristics, its attributes and links with the PL7-3 application (aliases and variables)
This information is taken from the MMS.CST and MMS.SCY files and from the
MMS.STR file when structured variables are used.
E
__________________________________________________________________________________________
5 / 1
__________________________________________________________________________________________
5.2
View
Selecting this function lets the user immediatly view on-screen, the newly generated documentation.
The user can scroll the documentation vertically and horizontally. The format displayed corresponds to what can be printed-out.
E
5.3
When this function is selected, it first displays the list of printers that can be used for printing out the station documentation file.
The user then free to select from the list of printers connected to the workstation, the one to use for printing out the documentation file. Simply click on the <OK> button to confirm the selection and start printing.
The <Cancel> button lets the user cancel the printing in progress.
Remark
The station documentation file generated by the station MMS function (the
MMS.DOC file) can be printed out separately and it can also be integrated into the complete documentation file for a V4 or V5 level station.
The integration is performed by XTEL-DOC and it is transparent to PL7-MMS.
__________________________________________________________________________________________
5 / 2
Documenting and Printing 5
__________________________________________________________________________________________
5.4
Entering Information
Entering the title page
When this menu is selected, its data entry fields display the contents of the MMS.TIT file, if it already exists. Else all fields are blank.
Access to a predefined field is by mouse or keyboard and Tab key. Within a field, the user can move between columns and lines using the mouse or the cursor keys.
Various entries are possible:
• Title
• Company
• Department
• Manager
• REV.
• DATE
• REVISION
• DESIGNER
• EXECUTED by
: Application title (64 chars. max.),
: Company name (16 chars. max.),
: Department name in the Company (16 chars. max.),
: Manager's name (16 car. max.),
: File revision level (3 chars. max.),
: File creation or modification date (8 chars. max.)
: Comments on the revision made (32 chars. max.),
: Designer's name (12 chars. max.),
: User's name (12 chars. max.),
The MMS.TIT file generated is an editable ASCII file.
OK Saves the contents of the screen to the MMS.TIT file and exits the screen.
Cancel Exits the screen without saving the MMS.TIT file.
E
__________________________________________________________________________________________
5 / 3
__________________________________________________________________________________________
Entering the custom footer
This screen lets the user customize the footer that appears at the bottom of every documentation file page. Two strings of characters can be filled-in by the user:
• A string of 25 characters at the top of the footer,
• A string of 45 characters at the bottom of the footer.
The fields are filled-in with the contents of the MMS.CRT file, if it already exists.
The documentation footer provides the following information:
• Application name,
• Printed item name,
• Document version number,
• Print-out date,
• Relative page numbering by item,
• Absolute page numbering.
E
OK
Cancel
Saves the contents of the screen to the MMS.CRT file and exits the screen.
Exits the screen without saving the MMS.CRT file.
__________________________________________________________________________________________
5 / 4
Viewing MMS Binary Files - Deleting Files - Help 6
__________________________________________________________________________________________
6.1
Viewing MMS Binary Files
The View utility lets the user view variables in an MMS binary file.
If the working environment is the local memory, the binary file viewed is the MMS.BIN
file on disk. If the working environment is the PLC memory, this function will view the contents of the dedicated MMS field in the PLC memory.
6.1-1 Viewing a Binary File on the Workstation Disk
The selected working memory is the local memory (Memory option in the main menu).
Viewing local variables
Once the View option is selected from the pulldown menu, a window is displayed showing a list of local MMS variables.
E
__________________________________________________________________________________________
6 / 1
__________________________________________________________________________________________
This screen displays the list of local variables stored in the MMS.BIN file. Each line in the list displays the following information:
<PL7_3Object>/<MMSVar>/<Scope>/<Name>/<Type>/<TypeInf>/<Access>/
For example:
W1/Index_01/DOMAIN/MMS/INT16//AUTO/
In the case of structured variables, the structure format is also given and the memory organization that applies to each element, for example:
W10/Product/VMD//STRUCT//AUTO/
{
+0/BOOL/Valid
+1/VSTR 12/Name
+7/INT16/Number
}
E
Viewing remote variables
Simply selecting Remote Variables will display a list of remote variables. This screen displays the list of remote variables stored in the MMS.BIN file. Each line in the list displays the following information:
<PL7_3Object>/<Alias>/<MMSVar>/<Scope>/<Name>/<Type>/<TypeInf>/
For example:
W1/Index_01/Num_File/DOMAIN/Public/INT16//
In the case of structured variables, the structure format is also given and the memory organization that applies to each element, for example:
W2/Index_02/File/DOMAIN/Public/STRUCT//
{
+0/INT16
+1/BSTR 18
+6/AR-BOOL 3
}
__________________________________________________________________________________________
6 / 2
Viewing MMS Binary Files - Deleting Files - Help 6
__________________________________________________________________________________________
6.1-2 Viewing a Binary File Stored in the PLC
To view the MMS contents of the PLC, select MMS memory as the working memory, then click on the View option in the Utilities menu.
The function will read the PLC memory contents and display the view screen.
6.2
Deleting Files
The Delete utility lets the user delete all of the files generated by PL7-MMS.
Once this option is selected, simply click on the type of file to delete. Regardless of the file type, the procedure is the same: select the file from the dialog box that opens and confirm the selection. Once the file is deleted, control returns to the updated dialog box.
This operation can be repeated as many times as there are files to delete.
When there are no more files of a given type to delete, the corresponding option is deleted.
E
__________________________________________________________________________________________
6 / 3
E
__________________________________________________________________________________________
6.3
Saving/Retrieving MMS.BIN Files
Selecting the Retrieve action displays a sub-menu that allows the user to designate the type of file to retrieve.
After selecting the action, simply click on the required type of file. The procedure is the same for all file types. The user must always give the access path and the name of the file to copy to the MMS field.
__________________________________________________________________________________________
6 / 4
Viewing MMS Binary Files - Deleting Files - Help 6
__________________________________________________________________________________________
In the same way, MMS .BIN, .SCY, .CST or .STR files (for local structures) can be saved for use with another station for example.
Regardless of the type of file used, the procedure is always the same. The user must enter the full path name and target file name.
6.4
Help
The Help option in the pulldown menu lets the user access to root directory of PL7-MMS help screens.
The About... option displays information on the current version of the installed software.
E
__________________________________________________________________________________________
6 / 5
__________________________________________________________________________________________
E
__________________________________________________________________________________________
6 / 6
Appendix 7
__________________________________________________________________________________________
7.
Appendix
Project Directory File Format
Variables File Format
The MMS_PRJ.REP file can also be created or modified using a standard text editor.
In this case, it must correspond to the preset Telemecanique format.
Compatibility rules:
• Records must be stored in alphabetical order based on application name, followed by the MMS variable name,
• A record contains all of the fields required to describe the variable. Each field is separated by a / ,
• // indicates an omission,
• # at the start of a line indicates a comment,
• The end of each record is indicated by the <Carriage Return> <Line Feed> characters.
Format:
/<AppName>/<MMSName>/<Scope>/<DomainName or AppName>/<Type>/
<TypeInf>/<CR><LF>
Structures File Format
The MMS_PRJ.STR file can also be created or modified using a standard text editor. In this case, it must correspond to the preset Telemecanique format.
Compatibility rules:
• Structures must be stored in alphabetical order based on the structure name,
• A structure element contains its name, type and where necessary the TypeInf field.
The various fields that describe the structure elements are separated by a / ,
• // indicates an omission,
• The end of each record is indicated by the <Carriage Return> <Line Feed> characters.
Format:
TEMP_ALARM
{
Number/INT16//
States/BSTR/18/
Location/OSTR/6/
Identification/AR-BOOL/3/
}
E
__________________________________________________________________________________________
7 / 1
__________________________________________________________________________________________
E
__________________________________________________________________________________________
7 / 2
________________________________________________________
MMS OFBs F
___________________________________________________________________________
Section
1 General
1.1
PL7-OSI 3.0 OFB Presentation
1.2
Installing OFBs
1.3
Configuring OFBs
1.4
Using OFBs
Page
1/1
1/2
1/2
1/4
2 MMSLD OFB
2.1
Using the MMSLD OFB
2.1-1 Application Modification
2.1-2 Module Memory Loss
3 MMS Services OFBs
3.1
Reminders on MMS Application Design
3.2
Programming MMS OFBs
3.2-1 Characteristics Common to all MMS OFBs
3.2-2 Implementation Principles
3.3
MCNCT OFB: Association Management
3.3-1 Function
3.3-2 PL7-3 Interface
3.3-3 Using the MCNCT OFB
3.3-4 Programming the MCNCT OFB
3.4
MREAD OFB: Read MMS Client Variables
3.4-1 Function
3.4-2 PL7-3 Interface
3.4-3 Using the MREAD OFB
3.4-4 Programming the MREAD OFB
3.5
MWRIT OFB: Write MMS Client Variables
3.5-1 Function
3.5-2 PL7-3 Interface
3.5-3 Using the MWRIT OFB
3.5-4 Programming the MWRIT OFB
2/1
2/1
2/1
___________________________________________________________________________
F / 1
3/11
3/11
3/11
3/15
3/15
3/1
3/2
3/2
3/4
3/21
3/21
3/21
3/26
3/26
3/28
3/28
3/28
3/32
3/32
F
________________________________________________________
___________________________________________________________________________
Section
3.6
MURCV OFB: Unsolicited Data (Client Mode)
3.6-1 Function
3.6-2 PL7-3 Interface
3.6-3 Using the MURCV OFB
3.6-4 Programming the MURCV OFB
3.7
MRSTA OFB: Device Status (Client Mode)
3.7-1 Function
3.7-2 PL7-3 Interface
3.7-3 Using the MRSTA OFB
3.7-4 Programming the MRSTA OFB
3.8
MUSND OFB: Sending Unsolicited Data (Server Mode)
3.8-1 Function
3.8-2 PL7-3 Interface
3.8-3 Using the MUSND OFB
3.8-4 Programming the MUSND OFB
3.9
MSSTA OFB: Sending Device Status (Server Mode)
3.9-1 Function
3.9-2 PL7-3 Interface
3.9-3 Using the MSSTA OFB
3.9-4 Programming the MSSTA OFB
F
4 MSEMA OFB: Synchronizing Access to an MMS Server
Variable
4.1
Function
4.2
PL7-3 Interface
4.3
Using the MSEMA OFB
4.4
Programming the MSEMA OFB
Page
3/34
3/34
3/34
3/38
3/38
3/40
3/40
3/40
3/42
3/42
3/44
3/44
3/44
3/48
3/48
3/50
3/50
3/50
3/53
3/53
4/1
4/2
4/6
4/6
5 Appendix
5.1
Error Handling
5.2
MMS Service Execution Error Indications (IND)
5.3
Error Codes Returned to Status by MMSLD V2.0
5.4
Adding an MMS Variable to an Existing Project
5/1
5/3
5/5
5/6
___________________________________________________________________________
F / 2
General 1
__________________________________________________________________________________________
1.1
PL7-OSI 3.0 OFB Presentation
The PL7-OSI 3.0 V2 OFB library comprises the MMSLD OFB and MMS service OFBs.
The MMSLD OFB is an executable PLC program that automatically monitors uploads the OSI configuration and the table of MMS local variables to the OSI modules
(TSX ETH 200). Uploading is performed from the dedicated OSI and MMS fields in the
PLC memory.
The MMS Service OFBs are an extension of PL7-3 language. They implement the Client functions and some Server functions for TSX ETH 200 modules.
The MCNCT, MREAD, MWRIT, MURCV, MRSTA OFBs are dedicated to MMS Client functions while MUSND and MSSTA OFBs are dedicated to MMS Server unsolicited services.
The MMS Client services that can be programmed in a PL7-3 application via the
TSX ETH 200 module Client function are:
Initiate, Conclude, Abort
Using the MCNCT OFB that allows the PL7-3 application to open, close or interrupt an assignment to a remote MMS Server application, it also enables the user to identify an assignment opened by a remote application.
Read, Write
Using the MREAD and MWRIT OFBs that allow the PL7-3 client application to read or write 1 to 4 variables to a remote device.
Status, UnsolicitedStatus
Using the MRSTA OFB that allows the user to acquire the status of remote device, as an explicit or unsolicited request.
Receiving unsolicited data: InformationReport
Using the MURCV OFB.
The MMS Server services that can be programmed into a PL7-3 application are:
Send unsolicited data: InformationReport, UnsolicitedStatus
Using the MUSND and MSSTA OFBs that when executed send data or status information to a remote MMS client device via the Server functions of OSI/MMS V2 interface modules.
The functions and programming modes for each OFB is described in the remaining sections of this divider.
MMS OFBs are supplied with the PL7-OSI 3.0 software on a separate diskette using the same rights of access. They are part of the MMS family.
F
__________________________________________________________________________________________
1 / 1
__________________________________________________________________________________________
1.2
Installing OFBs
The MMS OFBs must be installed on the workstation hard disk in order to be used. The installation procedure is described in Divider B, Section 1.
F
1.3
Configuring OFBs
Before using an OFB in an application program, it must first be configured. This operation is performed using PL7-3.
Configuration comprises:
• Declaring the type of OFB so that the executable code can be loaded into the OFB program field in memory,
• Defining the number of OFBs used in order to define the OFB constants and data fields in memory.
To perform these actions:
• Select PL7-3 and select 1 - Configuration from the main menu,
• From the Configuration Mode selection screen, select 5 - Optional Function Blocks.
The OFB Configuration screen displays a list of OFB types already declared and the number of OFBs per type.
• If the OFB is not present in this list, press the [New OFB] dynamic function key. A new screen lets the user view the list of OFBs available on the hard disk. Use the
[PREV FAM] and [NEXT FAM] dynamic function keys to select the required MMS family and use [INS] to select the type of OFB required for the application.
__________________________________________________________________________________________
1 / 2
General 1
__________________________________________________________________________________________
• After confirming the selections made, the OFB Configuration screen is displayed once again. The [MODIFY] command lets the user define the number of OFBs to use for the declared type. The user should configure an OFB for each network interface module in the station. For example, a station with four interface modules should have four MMSLD OFBs.
For further information refer to the PL7-3 Operating Modes documentation
(TXT DM PL7 3 V5E).
F
__________________________________________________________________________________________
1 / 3
F
__________________________________________________________________________________________
1.4
Using OFBs
To implement an MMS OFB, the user must perform the steps listed below:
1. Configure the module using PL7-OSI. Configure the MMS Client and MMS Server symbol data bases using PL7-MMS.
2. Define the local XTEL-SDBASE symbols used by the application so that the OFB inputs can be symbolically wired.
3. Configure and program the OFB using PL7-3.
Configure the number of times (instances) each OFB must be used.
Initialize the constants assigned to the MMS Client identifiers by executing a PL7-3
Read command on the MMS.CST file.
4. How to program each OFB is described in detail in Divider F, Section 3.
__________________________________________________________________________________________
1 / 4
MMSLD OFB 2
__________________________________________________________________________________________
2.1
Using the MMSLD OFB
The MMSLD OFB operates in implicit execution mode: the application designer does not program it in the PL7-3 application. It will run regardless of PLC state (Run or Stop).
The MMSLD OFB executes its upload function under the following conditions:
• When the OSI/MMS configuration of the application STATION.APP is modified by the designer,
• When the contents of the memory are lost due to a failure or an interface module replacement.
2.1-1 Application Modification
When the dedicated OSI or MMS fields in the PLC memory are modified, this field is automatically uploaded to the assigned interface module memory.
Loading a new application (STATION.APP) or binary file (OSI.BIN or MMS.BIN) modifies either of the dedicated OSI or MMS fields and therefore causes uploading to the module memory.
2.1-2 Module Memory Loss
The MMSLD OFB continually monitors the TSX ETH 200 modules present in the PL7-3 application I/O configuration.
Monitoring the interface comprises detecting loss or alteration to OSI parameters or of the table of symbols in the interface module memory. If the OSI or MMS configuration is lost, the MMSLD OFB automatically loads the interface module memory from the dedicated OSI and MMS fields in the PLC memory.
F
__________________________________________________________________________________________
2 / 1
__________________________________________________________________________________________
F
__________________________________________________________________________________________
2 / 2
MMS Services OFBs 3
__________________________________________________________________________________________
3.1
Reminders on MMS Application Design
A TSX/PMX station that uses MMS services to communicate with other stations, via one or more TSX ETH 200 modules is considered in XTEL as a Local Application that establishes exchanges with Remote Applications. In normal operation, associations are opened between the Local Application and Remote Applications. Each of these associations is a communication channel that is used to exchange data in Client/Server mode. The data exchanges are established with MMS variables identified with symbols common to all of the applications.
MMS application development implies declaration and definition at project level of each
Remote Application and of each MMS variable assigned to each Remote Application.
Once the common data base is established, each station - application - developed, will be configured so that the Remote Applications that are visible to it are designated. In addition, its Local Application characteristics are configured in each OSI module.
PL7-OSI is the tool used to perform the configuration tasks.
In parallel, PL7-MMS lets the user establish, for each station, the link between the MMS name of each MMS variable as seen by the Local Application, and a symbol ("Alias") in the PL7 local data base (in XTEL-SDBASE).
If the variable takes a value that is significant in the Local Application (application PL7-3 object) that will be read or written by a Remote Application, it will be declared for the Local
Application as a local MMS variable and assigned to a PL7-3 variable.
If it is a variable that is significant in a Remote Application, and it will be read or written by the Local Application, it will be declared as a remote MMS variable and its "Alias" in the local data base will be assigned to a CW (Constant Word) variable, the value of which will be a pointer to the table of remote MMS variables.
Before programming the OFBs in PL7-3, it is essential to ensure coherence with the development environment, by loading the MMS.CST file and, if necessary, by merging
MMS.SCY into the station data base.
It is important to note, at MMS application programming level, the following points:
In PL7-3, the fundamental symbol data base is managed by XTEL-SDBASE at station level. This data base ensures the link between the "Alias" (symbol) and the
PL7-3 variable (object).
OFBs are programmed symbolically. The symbols used are the PL7-3 "Aliases".
When an OFB input needs to be wired with an MMS variable, the variable is designated by its "Alias" and not by its MMS symbol.
The system will manage all necessary assignments, on compilation or execution, based on the tables of variables established using PL7-MMS.
F
__________________________________________________________________________________________
3 / 1
__________________________________________________________________________________________
3.2
Programming MMS OFBs
This Sub-section presents some of the characteristics common to all MMS OFBs and the principles that apply to their implementation. The principles that apply to interfacing with PL7-3 data are covered in particular.
Each of the OFBs is described in detail in the following Sub-sections.
F
3.2-1 Characteristics Common to all MMS OFBs
a. Like all communication OFBs, MMS OFBs require more than one PLC cycle to execute.
b. Call not maintained
OFB execution is implicitly maintained by the system, therefore the user need only program execution of the block. When using Literal language, the program line could be:
! IF NOT B0 THEN EXEC OFBi(... =>...); SET B0 giving the following advantages:
* Parameters are sent only once, ensuring a considerable gain in performance.
* Programming is simplified as the programmer does not need to maintain the call to the
OFB while execution is in progress.
However, the output parameters are ignored as the variables that should be wired will not be refreshed. Therefore the outputs are public internal data interprets as results.
Correct programming practice could be:
! IF NOT B0 THEN EXEC OFBi(... => ...); SET B0
!
! <WAIT>
! IF NOT OFBi, READY THEN JUMP L10
Note
The OFBs have a Bit type output parameter, the Error bit that is used for diagnostic purposes. This bit must not be wired. Error must be used as an internal result parameter.
__________________________________________________________________________________________
3 / 2
MMS Services OFBs 3
__________________________________________________________________________________________ c. Diagnostics characteristics
The OFBs can be used by APPLIDIAG. For this reason, they all have a bit type output,
ERROR and an internal public data bit INHIB.
When ERROR is set to 1, it indicates an error found by the function block. The error is indicated in one or more WORD and DWORD type data, STATUS and STATUSn. The number of STATUSi words and the meanings assigned to their states are described in detail in the description of each OFB.
INHIB is a public internal data bit that can be used to inhibit the indication of errors. If an error occurs, the OFB can continue execution as ERROR and STATUS always remain at 0.
d. RESET and READY bits
As the MMS OFBs are executed over a number of PLC cycles, the RESET input parameter can be used to interrupt OFB execution while it awaits the response to a message. In the same manner, OFBs have a public internal data bit READY that indicates execution in progress.
The READY bit
! IF NOT B0.MCNCT0,READY
THEN EXEC MCNCT0(;Initiate;CplMap;ORDO_APP;200=> ...);
SET B0
!
! <WAIT>
! IF NOT MCNCT0, READY THEN JUMP L500
! IF MCNCT0, ERROR THEN JUMP L999
!
! <The association is open. It will be repeated until closed>
! <by ORDO.>
! IF [MCNCT0, STATE=0] THEN MCNCT0,CHANNEL->ORDO
!
! <Program continues...>
The RESET action
The bit type RESET input is used to interrupt execution when the bit is set to 1. Any messages in progress are lost. The READY and ERROR bits are set to 1. STATUS indicates a user requested stoppage. The OFB is ready to be executed again. Writing the RESET input by UNI-TE request is allowed, i.e. using APPLIDIAG or PL7-3 Adjust and Data modes for example, with the PLC running or stopped.
A RESET action on an idle OFB (READY bit at 1) will reset the ERROR and STATUS public internal data to 0 along with any data interpreted as an output.
F
__________________________________________________________________________________________
3 / 3
F
__________________________________________________________________________________________
3.2-2 Implementation Principles
MMS Client/Server communication is implemented in three phases:
• Open a transmission channel that associates the Client to the Server,
• Perform exchanges on this temporary point-to-point data link,
• Close the association.
Remark
Before attempting to close an association, ensure that all exchanges in progress are completed: test the READY bits of the MMS OFBs to ensure that they are at 1.
The functions implied by these three phases are performed by MMS OFBs.
Association identification
• Case 1: The application initiates the call
The MCNCT OFB associates an MMS Client and Server, i.e. the PL7-3 application assigns the TSX/PMX PLC to a remote device, via a TSX ETH 200 module located in the PLC rack.
MCNCT requires as input parameters, the name of the remote MMS application to assign and the number of the interface module slot location in the rack.
Any subsequent exchanges between the two applications are performed via the opened channel (until it is closed). The OFBs that manage the exchange will always refer to this channel, therefore it need only be identified by a simple logical reference.
The MCNCT OFB will assign the logical identifier to the association. The reference is provided in the internal data CHANNEL once the communication channel opening procedure is complete. For simplicity, the reference is the same as the OFB instance number.
To close the association, use the same instance of the OFB.
Note that between the opening and the closing of an association, the MCNCT OFB monitors any change of state in the association caused by the remote device (Abort) or any interface module failure.
To sum up:
The logical number of an association in the calling application is the instance number of the MCNCT OFB that opened it.
An MCNCT OFB manages a single association at a time.
__________________________________________________________________________________________
3 / 4
MMS Services OFBs 3
__________________________________________________________________________________________
• Case 2: The application receives the call
In this case the OFB's ACCEPT parameter is used to retrieve the reference of the communication channel.
To ensure that the correct identifier is used for an association solicited by a remote station, the MCNCT OFBs must be programmed sequentially in Accept mode.
The first Accept must be Ready before starting the execution of the second, and so on, to ensure that the first does indeed receive the association opened by the remote station, and that the second also receives the second association opened by the remote station, and so on.
Remark
Setting SY0 to 1 and resetting the OFBs will cause incoherence between the state of the associations monitored by the OFBs and the true status of the module. Any associations that are opened must therefore be closed first (by conclude or abort) before selecting SY0 = 1.
Remote MMS variables and PL7-3
• Identification of MMS variables
The MMS variables are designated to the OFBs by XTEL-SDBASE symbols (Aliases) assigned to them when the variables are defined using PL7-MMS. These symbols let the OFBs (MREAD, MWRIT and MURCV) that use remote MMS variables to retrieve the complete definition. This is only possible if the MMS.CST file was loaded in PL7-3.
Therefore:
Before programming MMS OFBs always initialize PL7-3 constants using the READ command in PL7-3 to read the MMS.CST file.
• Exchanging the values of remote MMS variables
The MMS variables can be simple type (Boolean, Integer16, etc.) and also simple tables (refer to the table of MMS types).
The OFB input parameters can only be simple bit, word and double word types and not table types. To avoid this problem, the values of MMS variables are sent to the
OFBs according to the following principle:
- A remote MMS variable is defined as an OFB input with three input parameters, one that identifies the variable and the two others that define the size and the address of the buffer where the value of the variable is stored.
In the PL7-3/OFB interface, a remote MMS variable is designated as follows:
F
__________________________________________________________________________________________
3 / 5
__________________________________________________________________________________________
Mxxx word
VARi word
SIZEi
DATAi ptr_word
F i
Where
VARi Wired with the variable identifier (XTEL-SDBASE Alias).
SIZEi Buffer size (reception) or size of the data to send (transmission). Expressed in bytes.
DATAi Start of buffer address, always a word type.
In transmission mode, the buffer can be located in the system word (SWi), constant word (CWi) or internal word (Wi) fields.
In reception mode (write) only the internal word field (Wi) can be used.
In all cases, the fields used for other word type objects are illegal (register words, common words, Grafcet words).
Decimal integer index between 0 and 3: The Client mode OFBs MREAD and
MWRIT can handle up to 4 variables, except for MURCV that can only be assigned to a single variable.
__________________________________________________________________________________________
3 / 6
MMS Services OFBs 3
__________________________________________________________________________________________
Correspondence between PL7-3 Types and MMS remote variables
The table below shows the MMS types supported and the correspondence established between PL7-3 types (Note: the MREAD and MWRIT OFBs used in the examples are described in later sections).
MMS Type PL7-3 Correspondence
Boolean
Buffer
Size
2 LSB of a word
Example:
! EXEC MREAD(;Server;Vbool;2;W0=>)
! W0,0->B0
Unsigned16
Integer16
Unsigned32
Integer32
BitStringN
PL7-3 word objects
Example:
! EXEC MREAD(;Server;Vint16;2;W0=>)
! W0,0->COM0,0
2
Double length word objects
Example:
! EXEC MREAD(;Server;Vint32;4;CDW0=>)
4
Bits from words, where the first bit in the string is stored in the LSB of the first word, the second in the MSB of the first word.
Bit i is stored in the bit of word [j],k where i is the bit number, from 0 to N-1 j = i / 16 k = i mod 16
Example:
! B0->W0,0;B1->W0,1;B2->W0,2;B3->W0,3
! EXEC MWRIT(;Server;Vbool4;2;W0=>)
((N-1)/16
+1)*2 with N>0
OctetStringN Succession of words, where the first byte in the string is stored in the LSB of the first word, the second in the MSB of the first word.
Byte i is stored in the bit of word 256 k of word j where i is the byte number, from 0 to N-1 j = i / 2 k = i mod 2
((N-1)/2
+1)*2 with N>0 or
N/2+
N mod 2
__________________________________________________________________________________________
3 / 7
F
F
__________________________________________________________________________________________
MMS Type
OctetStringN
(Continued)
Array of
BitString16
Array of
Unsigned16
Array of
Integer16
Array of
Unsigned32
Array of
Integer32
PL7-3 Correspondence
Example:
! <Write a byte table>
! <{0,1,2,3) -> Vtab(4)>
! H'0100'->W0;H'0302'->W1
! EXEC MWRIT(;Server;Vtab4;4;W0=>)
!
! <Write a string of 5 chars.>
! <"ABCDE" -> Vstr(5)>
! M'AB'->W0,M'CD'->W1;M'E'->W2
! EXEC MWRIT(;Server;Vstr4;6;W0=>)
Succession of words (stored in the same way as BitStringN)
Example:
! <Read a table of 8 elements>
! EXEC MREAD(;Server;Vtab8;16;W0=>)
Succession of words (stored in the same way as Integer16)
Example:
! <Read a table of 3 elements>
! EXEC MREAD(;Server;Vtab3;6;W0=>)
Succession of double words (stored in the same way as Integer32)
Example:
! <Read a table of 3 elements>
! EXEC MREAD(;Server;Vtab3;12;W0=>)
Buffer
Size
Nbr. of elements x2
Nbr. of elements x2
Nbr. of elements x4
(*) Warning: The sequence in which the listings are saved in the PLC words is not standardized. For dialog with devices from other vendors, it may be necessary to change the order of the bits by changing the application program in one of the devices to ensure coherence.
__________________________________________________________________________________________
3 / 8
MMS Services OFBs 3
__________________________________________________________________________________________
MMS local variables and PL7-3
• Identifying MMS variables
The local MMS variables as seen by a PL7-3 application use XTEL-SDBASE Aliases in the same way as MMS remote variables, but unlike these, the symbols of local variables are assigned to local application PL7-3 objects (bits, words, double words or tables of these elements).
• MMS local variables
MMS local variables correspond to three different types of elements in PL7-3. The
OFBs that MMS local variables are wired to, at present the MUSND OFB, comprising three possible input parameters for variable identification and one parameter per type of element (bit, word, double word) that can correspond to the type of MMS variable.
Naturally it is only possible to wire one of the three inputs to designate a variable.
In addition, to define a table type, another input is dedicated to the number of elements in the variable.
In the PL7-3/OFB interface, an MMS local variable is designated as shown below:
MUSND
VARi_B ptr_bit
SIZEi_W ptr_word
VARi_DW
SIZEi ptr_dword word
F
Where i
VARi_B is wired with the XTEL-SDBASE Alias corresponding to the variable when it corresponds to a bit type element.
VARi_W is wired with the XTEL-SDBASE Alias corresponding to the variable when it corresponds to a word type element.
VARi_DW is wired with the XTEL-SDBASE Alias corresponding to the variable when it corresponds to a double word type element.
SIZEi is the data size, expressed as a number of elements. It equals 1 by default.
a decimal integer from 1 to 3: the MUSND block can handle up to 4 variables at one time.
Important: Only one of the VARi inputs should be wired.
__________________________________________________________________________________________
3 / 9
__________________________________________________________________________________________
Correspondence between PL7-3 types and MMS local variables
PL7-3 Object Assigned MMS
Type
BitString1
Input Used
(VARi_x)
VARi_B System bits (SYn)
Internal bits (Bn)
String of N successive objects of the previous type
System Words (SWn)
Internal Words (Wn)
Constant Words (CWn)
String of N successive objects of the previous type
Internal Double Words (DWn)
Constant Double Words (CDWn)
String of N successive objects of the previous double word type
Array of
BitString1
BitString16
Array of
BitString16
BitString32
Array of
BitString32
VARi_B
VARi_W
VARi_W
VARi_DW
VARi_DW
Size
(SIZEi)
1 or not wired
N
1
N
1 or not wired
N
F
Exclusions: Types of PL7-3 objects that cannot be used as MMS variables:
• Discrete I/O bits (Ixy,n and Oxy,n)
• Bits assigned to Grafcet (Xi; XMj; Xj,1 and Xj,o)
• Module error bits (Ixy,S and Oxy,S)
• Indexed bits
• Register words (IWxy,1)
• Common words (COMi,j and COMxi,j with x = A, B, C or D)
• Words assigned to Grafcet (Xi,V; Xj,i,V; Xj,I,V and Xj,O,V)
• Indexed words
Important
It is not possible to wire a pointer type input to a bit (VARi_B) using a bit taken from a word.
__________________________________________________________________________________________
3 / 1 0
MMS Services OFBs 3
__________________________________________________________________________________________
3.3
MCNCT OFB: Association Management
3.3-1 Function
The MCNCT OFB manages the association between the PL7-3 application and a remote application. It lets the user open connection (MMS Initiate service), identify an association opened by a remote application (Accept command) and close it normally
(Conclude service) or close it urgently (Abort service). Finally it informs the PL7-3 program on the status of the connection: open, closed by the local or remote station.
The ACCEPT command is required to identify an association opened by a remote device when execution of an OFB is required on this association. If the PLC is only a server for the association, this command need not be used.
3.3-2 PL7-3 Interface
RESET bit
COMMAND word
APPLI
MODULE
TIMEOUT ptr_dword word word
MCNCT bit
INHIB STATE bit word
READY CHANNEL bit word
STATUS IND word word
ERROR
F
__________________________________________________________________________________________
3 / 1 1
__________________________________________________________________________________________
Input Parameters
F
RESET
COMMAND
APPLI
Type
Bit
Word
Ptr_Word
Access
R/RW
R/R
R/R
Description
Interrupt OFB execution (READY at 0). Connection remains in critical state (STATE at -1).
Warning: A RESET on an idle OFB (READY at 1) that also indicates an open association (STATE at 0) will place the association in a critical state.
It is recommended that RESET NOT BE USED
WHEN READY=1 AND STATE=0, even to reset the
Type of service to execute, depending on value:
0: Open association (Initiate Service)
1: Identify association (Accept Service)
2: Close association (Conclude Service)
Name of the remote application to reach.
Pointer on a field where the first word contains the size (in bytes) of the field, the next words the characters for the remote association name.
MODULE
TIMEOUT
Word
Word
R/R
R/R
Module position in the main PLC rack (slots 0 to 7).
Timeout for a response from a remote device. Expressed in tenths of a millisecond. This time is used by all confirmed services exchanged.
Allowed values: 0 to 32767,
Default value: 100,
Value 0: Infinate wait state,
Special case of restarts after TimeOut, refer to code ind. =/1002, in the Appendix, Divider F,
Sub-section 5.2.
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
__________________________________________________________________________________________
3 / 1 2
MMS Services OFBs 3
__________________________________________________________________________________________
Public Internal Data
STATUS
READY
INHIB
Type
Word
Bit
Bit
Access
R/R
Description
IF ERROR is at 1. Identifies execution errors. Each
R/R
RW/RW
OFB status:
READY = 1: OFB ready for execution,
Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
CHANNEL Word R/R Logical identifier assigned to the connection by the
OFB after opening.
The identifier is the instance number of the MCNCT
OFB that controls the connection. This reference identifies the association in the exchanges on this channel. It must be provided as an input to other
STATE Word R/R Connection state:
0: Association open
1: Association closed by a local Conclude
2: Association closed by a remote Conclude
3: Association closed by a local Abort
-1: Association does not exist
__________________________________________________________________________________________
IND Word R/R MMS Service execution error indicator (indicated by
STATUS bits 8 to 11). Refer to Appendix, Div. F/5.
F
APPLIDIAG Interface: STATUS bit information
Bit Description Corrective action
Bit 0 Unknown command
The COMMAND code is not 0,1,2 or 3
The COMMAND code is not 0,1,2 or 3
Bit 1 Error reading application name.
An error occurred when reading the application name (size exceeds 32 characters, access error or parameter setting error).
Check the APPLI parameter
Bit 2 Association already open.
An association with an application with the same name as the one set in
APPLI is already open using the same channel number
(OFB instance number).
No corrective action is required (DO
NOT RESET the OFB). Exchanges can continue
__________________________________________________________________________________________
3 / 1 3
F
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS bit information (cont'd)
Corrective Action Bit Description
Bit 3 Association number already used.
The channel number (OFB instance number) already identifies an association between the PLC and a remote application with a different name than the one declared in APPLI.
Bit 4
Bit 5
Association already closed. An attempt to close (using Conclude or Abort services) was made with an instance number (channel number) that is no longer assigned.
Association to identify does not exist.
An identification (Accept service) request was attempted on a connection that was not opened by a remote application.
Bit 7
Bit 8
Bit 9
Association monitoring interrupted by a RESET.
MMS error detected by the local module (Bit 8).
MMS error detected by the remote module (Bit 9).
Bit 10 Error during MMS service execution
(Bit 10).
Bit 11 MMS Service rejected (Bit 11).
Bit 12 Error accessing the module.
The module is missing, unplugged, in error or is not the right type
(TSX ETH 200).
Bit 13 Communication error.
The exchange failed for one of the reasons listed below:
1. No response to the request before timeout. The PLC master task is overloaded.
2. The module rejected the request because it was being configured or does not have a loaded MMS Client configuration.
Close the previous association using a
Conclude or Abort service.
Reset OFB outputs (RESET).
Check the application name provided
(APPLI parameter).
Check the next two bits to identify the type of error.
Analyze the IND parameter to determine the cause of the error.
Check the module and/or the slot number in the rack sent to the OFB
(MODULE input parameter).
Increase the master task cycle time or reduce the PLC load (in case 1).
Check the module configuration (in case 2).
Bit 14 Processing interrupted.
OFB execution was interrupted by setting its RESET input to 1 by SY0, a software error or a power break.
Bit 15 System error.
The OFB does not have the system resources required for execution.
Reduce the number of OFBs configured (of all types).
__________________________________________________________________________________________
3 / 1 4
MMS Services OFBs 3
__________________________________________________________________________________________
3.3-3 Using the MCNCT OFB
To implement the MCNCT OFB, follow the steps described below:
1. Configure the module using PL7-OSI,
2. Define the local application XTEL-SDBASE symbols ready for symbolic assignment of OFB inputs.
Using symbolic programming makes for clearer and easily portable applications.
3. Configure and program the OFB using PL7-3.
Allow for the number of instances, taking into account that an MCNCT instance only manages one association at a time and that the instance number is used as the logical identifier (Channel Number) for the association (communication channel used between the local application and the remote application). All Client and Server OFBs that exchange data on this channel use the channel number as an input.
Initialize the constants assigned to the remote MMS identifiers by executing a PL7-3
READ command on the MMS.CST file.
Programming the MCNCT OFB is described in detail in the next Sub-section.
3.3-4 Programming the MCNCT OFB a. Opening an association
This function uses the MMS Initiate service.
Connection is opened by executing the MCNCT OFB with the COMMAND input set to 0.
The other inputs to set are:
APPLI (name of the application to open the association with),
MODULE (slot number of the communication module),
TIMEOUT
Execution results:
Association opened:
ERROR = 0
CHANNEL = Association Number (OFB instance number),
STATE = 0
Opening failed:
ERROR = 1
STATUS gives the reason for the failure
STATE gives the state of the connection
__________________________________________________________________________________________
3 / 1 5
F
__________________________________________________________________________________________
Note
Any attempt to open an association that is already open will fail (ERROR = 1) except if the value of APPLI is the same on the second attempt as the first. In this case, exchanges remain authorized on the channel. Otherwise the result is the same as failing to close the first connection: all exchanges are impossible. Before being able to reuse the channel, the association must be closed
(using Conclude or Abort services) and identification performed.
F
Programming example
The READY bit
! IF NOT B0.MCNCT0,READY
THEN EXEC MCNCT0(;Initiate;CplMap;ORDO_APP;200=> ...);
SET B0
!
! <WAIT>
! IF NOT MCNCT0, READY THEN JUMP L500
! IF MCNCT0, ERROR THEN JUMP L999
!
! <The association is open. It will be identified until closed>
! <by ORDO.>
! IF [MCNCT0, STATE=0] THEN MCNCT0,CHANNEL->ORDO
!
! <Program continues...>
Data used
Symbol
Initiate
Accept
Conclude
Abort
CplMap
Ordo
Ordo_app
Variable
CW0
CW1
CW2
CW3
CW10
W10
CW11
CW12
Value
2
3
0
1
4
?
4
M'ORDO'
__________________________________________________________________________________________
3 / 1 6
MMS Services OFBs 3
__________________________________________________________________________________________ b. Identifying an association opened by a remote application
The Accept command (non MMS) is used by the local application to identify an association opened by a remote application. Connection is opened by executing the
MCNCT OFB with the COMMAND input set to 1.
The other input to set are:
APPLI (name of the application to open the association with),
MODULE (slot number of the communication module),
TIMEOUT
Execution results:
Association identified:
ERROR = 0
CHANNEL = Association Number (OFB instance number),
STATE = 0
Identification failed:
ERROR = 0
STATUS gives the reason for the failure
STATE gives the state of the connection
Note
Any attempt to identify a previously identified association will always fail (ERROR = 1) except if the value of APPLI is the same on the second attempt as the first. In this case, exchanges remain authorized on the channel. Otherwise the result is the same as failing to close the first connection: all exchanges are impossible. Before being able to reuse the channel, the association must be closed (using Conclude or Abort services) and identification performed.
Programming example
Using number 2 to identify a connection opened by a remote "Supervisor" device. The module used is located in slot 4 of the main PLC rack. The timeout is 2 seconds.
! IF NOT B0.MCNCT2,READY
THEN EXEC MCNCT2(;Accept;CplMap;SUPER_APP;200=> ...);
SET B0
!
! <WAIT>
! IF NOT MCNCT2, READY THEN JUMP L500
! IF MCNCT2, ERROR THEN JUMP L999
!
! <The association is identified. It will be identified until>
! <closed by SUPERVI.>
! IF [MCNCT2, STATE=0] THEN MCNCT2,CHANNEL->SUPER
!
! <Program continues...>
__________________________________________________________________________________________
3 / 1 7
F
__________________________________________________________________________________________
Data used
Symbol
Initiate
Accept
Conclude
CplMap
Super
Super_ap
Variable
CW0
CW1
CW2
CW10
W20
CW20
CW21
Value
2
4
0
1
Channel Num. = 2
11
M'SUPERVISOR'
F c. Closing an association
This function uses the MMS Conclude service.
Connection is closed by executing the MCNCT OFB with the COMMAND input set to 2.
The other inputs are ignored.
Execution results:
Association closed:
ERROR = 0
STATE = 1
Closure failed:
ERROR = 0
STATUS gives the reason for the failure
STATE gives the state of the connection
Generally a failure is caused by:
• Services still being processed on the association,
• Association already closed.
Note
If an open association fails to close, exchanges remain authorized although ERROR and STATUS will indicate an error.
An association closure is not executed immediately. The Conclude service is executed over a number of cycles. During the time between requesting closure and its becoming effective, reception of data (solicited or not) is allowed to complete requests in progress. All new service requests (read or write) are refused. If a write request is in progress when the Conclude request is made, the
Conclude request will be rejected. STATE changes state once execution of the Conclude request is confirmed.
__________________________________________________________________________________________
3 / 1 8
MMS Services OFBs 3
__________________________________________________________________________________________
Programming example
Concluding connection 0.
! IF NOT B1.MCNCT0,READY
THEN EXEC MCNCT0(;Conclude;;;=> );SET B1
!
! <WAIT>
! IF NOT MCNCT0, READY THEN JUMP L500
! IF MCNCT0, ERROR THEN JUMP L999
!
! <The association is closed.>
! IF [MCNCT2, STATE=0] THEN MCNCT2,CHANNEL->SUPER
!
! <Program continues...>
For data used, refer to page 3/16.
d. Emergency shutdown of an association
This function uses the MMS Abort service.
Connection is closed by executing the MCNCT OFB with the COMMAND input set to 3.
The other inputs are ignored.
Execution results:
Association closed:
ERROR = 0
STATE = 2
Closure failed:
ERROR = 1
STATUS gives the reason for the failure
STATE gives the state of the connection
An Abort service is only refused if the association is already closed.
Note
Although the Abort service is executed over a number of cycles, closure is performed urgently. As soon as this request is received, all exchanges (read or write) in progress are cancelled. Any new requests received will be rejected.
F
__________________________________________________________________________________________
3 / 1 9
__________________________________________________________________________________________
Programming example
Aborting connection 0.
! IF NOT B2.MCNCT0,READY
THEN EXEC MCNCT0(;Abort;;;=> ); SET B2
!
! <WAIT>
! IF NOT MCNCT0, READY THEN JUMP L500
! IF MCNCT0, ERROR THEN JUMP L999
!
! <The association is closed.>
For data used, refer to page 3/16.
F e. Monitoring function
This function cannot be programmed. It is implicit when the OFB is executed to open or identify an association and as long as the association remains open.
The OFB monitors the status of the module and the association.
Events detected are:
Module disconnected or failure
Association closed by the remote device
When one of these events occurs, ERROR is set to 1. STATUS will give the cause and
STATE will give the state of the association.
Note
During monitoring, the MCNCTi,READY bit is at 1. This means that the OFB remains accessible to execute Conclude or Abort services.
Remark
When a Reset is performed on an MCNCT block while an association is being monitored, the association will enter a critical state (STATE = -1) and all current transactions on the association will be lost.
__________________________________________________________________________________________
3 / 2 0
MMS Services OFBs 3
__________________________________________________________________________________________
3.4
MREAD OFB: Read MMS Client Variables
3.4-1 Function
The MREAD OFB supports the MMS_READ service. It will read 1 to 4 variables from a remote application.
The variables are MMS Client variables defined with PL7-MMS. At OFB level, the variables are identified by their XTEL-SDBASE symbols (Aliases).
3.4-2 PL7-3 Interface
RESET
CHANNEL bit word
VAR0...3
SIZE0...3
DATA0...3
DATA3 word word ptr_word word word ptr_word
MREAD bit
INHIB RC0...3
bit word
READY RC0...3
bit word
STATUS IND word word
ERROR
F
__________________________________________________________________________________________
3 / 2 1
__________________________________________________________________________________________
Input Parameters
COMMAND
Type
Bit
Word
Word
Word
DATA0..DATA3 Ptr_Word
Access
R/RW
R/R
R/R
R/R
R/R
Description
Interrupts OFB execution or resets STATUS.
Association number (communication channel
XTEL-SDBASE Alias of variables to read.
Size in bytes of the reception buffers.
Pointer to reception buffers.
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
Public Internal Data
STATUS
Type
Word
F
READY Bit
INHIB
RC0...RC3
IND
Bit
Word
Word
Access
R/R
Description
IF ERROR is at 1. Identifies execution errors.
Each bit indicates an error.
R/R
RW/RW
OFB status:
READY = 1: OFB ready for execution,
Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
R/R
R/R
Length of data if read action was correct. Else, cause
MMS Service execution error indicator (indicated by
STATUS bits 8 to 11). Refer to Appendix, Div. F,
Sub-section 5.2.
__________________________________________________________________________________________
3 / 2 2
MMS Services OFBs 3
__________________________________________________________________________________________
Meaning of RCi data on error
-100
-101
-102
-103
-104
-105
-106
-107
-108
-109
-110
-4
-5
-6
-7
-8
>= 0
-1
-2
-3
No errors.
VARi input not set.
VARi is set but a corresponding SIZEi or DATAi input is not set.
Access to a non configured field.
Access to a write protected segment (CW, SW, etc.).
Reception buffer assigned to VARi causes overlap.
Reception buffer assigned to VARi is too small.
VARi input not defined.
VARi type incompatible with its definition in the function field
Object invalidated
Hardware-fault
Temporarily-unavailable
Object-access-denied
Object-undefined
Invalid-address
Type-unsupported
Type-inconsistent
Object-Attribute-inconsistent
Object-access-unsupported
Object-non-existent
F
__________________________________________________________________________________________
3 / 2 3
F
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit Description Corrective Action
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Association not open or being closed.
Association not available for exchanges.
Error accessing the MMS function field.The PL7-MMS function field is not configured or loaded.
Check the CHANNEL parameter or the status of the association
(MCNCTi,STATE and MCNCTi,STATUS variables, i = Association Number).
Configure and/or load an MMS field.
Error accessing the variable description. Error reading the description of variables (invalid descriptor, variable not defined, etc.).
The RCi data indicates the affected input parameter.
Error accessing data. Access protected or illegal, settings, capacity overflow, etc. The RCi data indicate the parameter that caused the error.
Access refused by the server. Error accessing MMS variables (variable not defined, access protected, etc...) The
RCi data indicate the parameter that caused the error.
Allocation error. There is not enough space in the PL7-MMS field to perform memory allocation.
Check the VARi input parameters and/ or the definition of variables using
PL7-MMS. Ensure that the constants file MMS.CST is loaded.)
Check the DATAi parameters.
Check the VARi and DATAi parameters. Check the definition of variables with PL7-MMS (coherence with their definition in the remote station).
Reduce the size of variables to read or reduce the number of OFBs in the application that can perform dynamic memory allocations in the PL7-MMS field.
Bit 6 Request too large.
The variables requested in read cause the request to exceed 4096 bytes.
Reduce the number of variables to read in the request or reduce the size of the data to read.
Bit 8
Bit 9
MMS error detected by the module
(Bit 8).
MMS error detected by the remote module (Bit 9).
Check the next two bits to identify the type of error.
Bit 10 Error during MMS service execution
(Bit 10).
Bit 11 MMS Service rejected (Bit 11).
Analyze the IND parameter to determine the cause of the error.
Bit 12 Error accessing the module.
The module is missing, unplugged, in error or is not the right type
(TSX ETH 200).
Check the module and/or the slot number in the rack sent to the OFB (MOD-
ULE input parameter).
__________________________________________________________________________________________
3 / 2 4
MMS Services OFBs 3
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit Description Corrective Action
Bit 13 Communication error. The exchange failed for one of the reasons listed below:
1. No response to the request before timeout. The PLC master task is overloaded.
2. The module rejected the request because it was being configured or does not have a loaded MMS Client configuration.
Increase the master task cycle time or reduce the PLC load (in case 1).
Check the module configuration (in case
2).
Bit 14 Processing interrupted. OFB execution was interrupted by setting its RE-
SET input to 1 by SY0, a software error or a power break.
Reduce the number of OFBs configured
(of all types).
Bit 15 System error.The OFB does not have the system resources required for execution.
F
__________________________________________________________________________________________
3 / 2 5
__________________________________________________________________________________________
3.4-3 Using the MREAD OFB
To implement the MREAD OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
F
3.4-4 Programming the MREAD OFB
The MREAD OFB reads 1 to 4 MMS Client variables from a remote application. This implies that:
• The local application is aware of these variables, i.e. that they have been defined for the station using PL7-MMS,
• A communication channel is open with the remote application, i.e. that an MCNCT
OFB has already opened an association (Initiate service) or identified an association opened by the remote application (Accept service).
The identification of each MMS variable is passed to the MREAD OFB via an
XTEL-SDBASE symbol (Alias) that links it to the MMS symbol (refer to Sub-section 3.4).
The Alias is taken to the VARi parameter.
Each of the values from the variables to read are stored in a reception buffer that is defined for the OFB by the input parameters:
• DATAi: Address of the first reception buffer word,
• SIZEi: Size, in bytes, of the reception buffer.
(The DATAi and SIZEi parameters correspond to the VARi parameter, where i is between 0 and 3).
The number of the association used by the request is taken to the CHANNEL parameter.
Execution results:
Read performed correctly:
ERROR = 0
RC0..RC3 specify by their values, the size in bytes of the data received
Read failed:
ERROR = 1
RC0..RC3 specify the reason for the failure
__________________________________________________________________________________________
3 / 2 6
MMS Services OFBs 3
__________________________________________________________________________________________
Programming example
Reading two variables "NB-STATION" an integer and "LIST-STATIONS" a table of three bytes. These variables are identified by the symbols STATION and STATIONS. The first variable is stored after W0 (2 byte field). The second after W1 (4 byte field). The exchange used the association designated 1.
! IF NOT B1.MREAD0,READY.[MCNCT1,STATE=0]
THEN EXEC MREAD0(;1;STATION;2;NB_ST;STATIONS;
4;;LST_ST;;;;;;=>); SET B1
!
! <WAIT>
! IF NOT MCNCT0, READY THEN JUMP L500
! IF MCNCT0, ERROR THEN JUMP L999
!
! <The two variables are read.>
! <W0 contains the value of "NB-STATIONS";
! <W1 contains the first two bytes of "LIST_STATIONS";
! <The LSB of W2 contains the third byte.
!
! <Program continues...>
Data used
Symbol
Nb_st
Lst_st
Remote
Station
Stations
Variable
W0
W1
W10
CW100
CW101
Value
?
?
1 (Channel Num. = 1)
From PL7-MMS
From PL7-MMS
F
__________________________________________________________________________________________
3 / 2 7
__________________________________________________________________________________________
3.5
MWRIT OFB: Write MMS Client Variables
3.5-1 Function
The MWRIT OFB supports the MMS_WRITE service. It will write 1 to 4 variables to a remote application.
The variables are MMS Client variables defined with PL7-MMS. At OFB level, the variables are identified by their XTEL-SDBASE symbols (Aliases).
F
3.5-2 PL7-3 Interface
RESET
CHANNEL bit word
VAR0...3
SIZE0...3
DATA0...3
word word ptr_word word word ptr_word
MWRIT bit
INHIB RC0 bit word
READY RC3 bit word
STATUS IND word word
ERROR
__________________________________________________________________________________________
3 / 2 8
MMS Services OFBs 3
__________________________________________________________________________________________
Input Parameters
CHANNEL
SIZE0...SIZE3
Type
Bit
Word
Word
Word
DATA0..DATA3 Ptr_Word
Access
R/RW
R/R
R/R
R/R
R/R
Description
Interrupts OFB execution or resets STATUS.
Association number (communication channel
XTEL-SDBASE Alias of variables to read.
Size in bytes of the data to send. (Optional: If the parameter is not set, the exact size of the variable is used. When this input is used, additional control is
Pointer to transmission buffers.
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
Public Internal Data
STATUS
Type
Word
READY
INHIB
RC0...RC3
IND
Bit
Bit
Word
Word
Access
R/R
Description
IF ERROR is at 1. Identifies execution errors.
Each bit indicates an error.
R/R
RW/RW
OFB status:
READY = 1: OFB ready for execution,
Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
R/R
R/R
Cause of the Write error.
MMS Service execution error indicator (indicated by
STATUS bits 8 to 11). Refer to Appendix, Div. F,
Sub-section 5.2.
F
__________________________________________________________________________________________
3 / 2 9
F
__________________________________________________________________________________________
Meaning of RCi data on error
-100
-101
-102
-103
-104
-105
-106
-107
-108
-109
-110
-4
-5
-6
-7
-8
>= 0
-1
-2
-3
No errors.
VARi input not set.
VARi is set but a corresponding SIZEi or DATAi input is not set.
Access to a non configured field.
Access to a write protected segment (CW, SW, etc.).
Reception buffer assigned to VARi causes overlap.
Reception buffer assigned to VARi is too small.
VARi input not defined.
VARi type incompatible with its definition in the function field
Object invalidated
Hardware-fault
Temporarily-unavailable
Object-access-denied
Object-undefined
Invalid-address
Type-unsupported
Type-inconsistent
Object-Attribute-inconsistent
Object-access-unsupported
Object-non-existent
__________________________________________________________________________________________
3 / 3 0
MMS Services OFBs 3
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit Description Corrective Action
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Association not open or being closed.
Association not available for exchanges.
Error accessing the MMS function field.The PL7-MMS function field is not configured or loaded.
Check the CHANNEL parameter or the status of the association
(MCNCTi,STATE and MCNCTi,STATUS variables, i = Association Number).
Configure and/or load an MMS field.
Error accessing the variable description. Error reading the description of variables (invalid descriptor, variable not defined, etc.).
The RCi data indicates the affected input parameter.
Check the VARi input parameters and/ or the definition of variables using
PL7-MMS. Ensure that the constants file MMS.CST is loaded.)
Error accessing data. Access protected or illegal, settings, capacity overflow, etc. The RCi data indicate the parameter that caused the error.
Access refused by the server. Error accessing MMS variables (variable not defined, access protected, etc...) The
RCi data indicate the parameter that caused the error.
Allocation error. There is not enough space in the PL7-MMS field to perform memory allocation.
Check the DATAi parameters.
Check the VARi and DATAi parameters. Check the definition of variables with PL7-MMS (coherence with their definition in the remote station).
Reduce the size of variables to read or reduce the number of OFBs in the application that can perform dynamic memory allocations in the PL7-MMS field.
Bit 8
Bit 9
MMS error detected by the module
(Bit 8).
MMS error detected by the remote module (Bit 9).
Check the next two bits to identify the type of error.
Analyze the IND parameter to determine the cause of the error.
Bit 10 Error during MMS service execution
(Bit 10).
Bit 11 MMS service rejected (Bit 11)
Bit 13 Communication error. The exchange failed for one of the reasons listed below:
1. No response to the request before timeout. The PLC master task is overloaded.
2. The module rejected the request because it was being configured or does not have a loaded MMS Client configuration.
Increase the master task cycle time or reduce the PLC load (in case 1).
Check the module configuration (in case
2).
F
__________________________________________________________________________________________
3 / 3 1
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit Description Corrective Action
Bit 14 Processing interrupted. OFB execution was interrupted by setting its RE-
SET input to 1 by SY0, a software error or a power break.
Bit 15 System error.The OFB does not have the system resources required for execution.
Reduce the number of OFBs configured
(of all types).
3.5-3 Using the MWRIT OFB
To implement the MWRIT OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
F
3.5-4 Programming the MWRIT OFB
The MWRIT OFB reads 1 to 4 MMS Client variables from a remote application. This implies that:
• The local application is aware of these variables, i.e. that they have been defined for the station using PL7-MMS,
• A communication channel is open with the remote application, i.e. that an MCNCT
OFB has already opened an association (Initiate service) or identified an association opened by the remote application (Accept service).
The identification of each MMS variable is passed to the MWRIT OFB via an
XTEL-SDBASE symbol (Alias) that links it to the MMS symbol (refer to Sub-section 3.4).
The Alias is taken to the VARi parameter.
__________________________________________________________________________________________
3 / 3 2
MMS Services OFBs 3
__________________________________________________________________________________________
Each of the values from the variables to read are stored in a reception buffer that is defined for the OFB by the input parameters:
• DATAi: Address of the first transmission buffer word,
• SIZEi: Size, in bytes, of the transmission buffer. This input may not be used. If it is, the
OFB will perform a coherence check on the size of the type of MMS variable defined with PL7-MMS.
(The DATAi and SIZEi parameters correspond to the VARi parameter, where i is between 0 and 3).
The number of the association used by the request is taken to the CHANNEL parameter.
Execution results:
Write performed correctly:
ERROR = 0
RC0..RC3 are at 0
Write failed:
ERROR = 1
RC0..RC3 specify the reason for the failure
Programming example
Writing the variable "ASM-FINI" to 1. A Boolean type, this variable is identified by the symbol ASM_FIN. The transmission buffer (the exchange fields are always word types) is W100 (Aux). The exchange is performed on association 0.
! IF NOT B1.MWRIT0,READY.[MCNCTO,STATE=0] THEN SET AUX,0;
THEN EXEC MWRIT0(;0;ASM_FIN;1; AUX;;;;;;;;;=>); SET B1
!
! <WAIT>
! IF NOT MWRIT0, READY THEN JUMP L500
! IF MWRIT0, ERROR THEN JUMP L999
!
! <The variable "ASM_FIN" is set to 1.
!
! <Program continues...>
Data used
Symbol Variable Value
Aux
Asm_fini
W100
CW102
1 (after SET AUX, 0_
Assigned by PL7-MMS
__________________________________________________________________________________________
3 / 3 3
F
__________________________________________________________________________________________
3.6
MURCV OFB: Unsolicited Data (Client Mode)
3.6-1 Function
The MURCV OFB supports the MMS INFORMATION REPORT service. This lets a
Client application receive unsolicited data sent by a remote Server application. The application is in stand-by with the MURCV OFB.
The variables are MMS Client variables defined with PL7-MMS. At OFB level, the variables are identified by their XTEL-SDBASE symbols (Aliases).
F
3.6-2 PL7-3 Interface
RESET
CHANNEL
VAR
SIZE
BUFFER bit word word word ptr_word
MURCV bit
INHIB RC bit word
READY bit
STATUS IND word word
__________________________________________________________________________________________
3 / 3 4
MMS Services OFBs 3
__________________________________________________________________________________________
Input Parameters
CHANNEL
BUFFER
Type
Bit
Word
Word
Word
Ptr_Word
Access
R/RW
R/R
Description
Interrupts OFB execution or resets STATUS.
Association number (communication channel
R/R
R/R
R/R
XTEL-SDBASE Alias of variables to read.
Size in bytes of the reception field.
Pointer to reception field.
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
Public Internal Data
STATUS
Type
Word
READY
INHIB
RC
IND
Bit
Bit
Word
Word
Access
R/R
Description
IF ERROR is at 1. Identifies execution errors.
Each bit indicates an error.
R/R
RW/RW
OFB status:
READY = 1: OFB ready for execution,
Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
R/R
R/R
Length of data if read action was correct. Else, cause
MMS Service execution error indicator (indicated by
STATUS bits 8 to 11).
Refer to the Appendix, Divider F, Sub-section 5.2.
F
__________________________________________________________________________________________
3 / 3 5
F
__________________________________________________________________________________________
Meaning of RC data on error
-100
-101
-102
-103
-104
-105
-106
-107
-108
-109
-110
When an error occurs that is linked to the description of MMS variables, data access or refusal by the server to allow access, as shown by bits 2, 3 and 4, the RC data specifies the cause of the error.
-4
-5
-6
-7
-8
>= 0
-1
-2
-3
No errors.
VARi input not set.
VARi is set but a corresponding SIZEi or DATAi input is not set.
Access to a non configured field.
Access to a write protected segment (CW, SW, etc.).
Reception buffer assigned to VARi causes overlap.
Reception buffer assigned to VARi is too small.
VARi input not defined.
VARi type incompatible with its definition in the function field
Object invalidated
Hardware-fault
Temporarily-unavailable
Object-access-denied
Object-undefined
Invalid-address
Type-unsupported
Type-inconsistent
Object-Attribute-inconsistent
Object-access-unsupported
Object-non-existent
__________________________________________________________________________________________
3 / 3 6
MMS Services OFBs 3
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit Description Corrective Action
Bit 0
Bit 1
Association not open or being closed.
Association not available for exchanges.
Error accessing the MMS function field.The PL7-MMS function field is not configured or loaded.
Check the CHANNEL parameter or the status of the association
(MCNCTi,STATE and MCNCTi,STATUS variables, i = Association Number).
Configure and/or load an MMS field.
Bit 2
Bit 3
Bit 4
Bit 5
Bit 8
Bit 9
Error accessing the variable description. Error reading the description of variables (invalid descriptor, variable not defined, etc.).
Check the VAR input parameters and/ or the definition of variables using
PL7-MMS. Ensure that the constants file MMS.CST is loaded.)
Error accessing data. Access protected or illegal, settings, capacity overflow, etc.
Check the BUFFER parameter.
Access refused by the server. Error accessing MMS variables (variable not defined, access protected, etc...).
Check the VAR and BUFFER parameters. Check the definition of variables with PL7-MMS (coherence with their definition in the remote station).
Allocation error. There is not enough space in the PL7-MMS field to perform memory allocation.
Reduce the size of variables to read or reduce the number of OFBs in the application that can perform dynamic memory allocations in the PL7-MMS field.
MMS error detected by the module
(Bit 8).
MMS error detected by the remote module (Bit 9).
Check the next two bits to identify the type of error.
Bit 10 Error during MMS service execution
(Bit 10).
Bit 11 MMS Service rejected (Bit 11).
Analyze the IND parameter to determine the cause of the error.
Check the configuration and/or the status of the module.
Bit 13 Communication error. The module rejected the request because it was being configured or has failed.
Bit 14 Processing interrupted. OFB execution was interrupted by setting its RESET input to 1 by SY0, a software error or a power break.
Bit 15 System error.The OFB does not have the system resources required for execution.
Reduce the number of OFBs configured (of all types).
F
__________________________________________________________________________________________
3 / 3 7
__________________________________________________________________________________________
3.6-3 Using the MURCV OFB
To implement the MURCV OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
F
3.6-4 Programming the MURCV OFB
The MURCV OFB lets a Client PL7-3 application stand-by to receive the value of an
M MS v ar ia bl e sen t b y a re mo te Se rv er a ppl i ca tion (MMS Service:
INFORMATION_REPORT). The MMS variable was defined with PL7-MMS as a Client variable.
This OFB operates in the same way as MREAD except that data can be received over a longer length of time. Only one variable can be received each time the OFB is executed.
The identification of each MMS variable is passed to the MURCV OFB via an
XTEL-SDBASE symbol (Alias) that links it to the MMS symbol (refer to Sub-section 3.4).
The Alias is taken to the VARi parameter.
Each of the values from the variables to read are stored in a reception buffer that is defined for the OFB by the input parameters:
• BUFFER: Address of the first reception buffer word,
• SIZE: Size, in bytes, of the reception buffer.
(The DATAi and SIZEi parameters correspond to the VARi parameter, where i is between 0 and 3).
The number of the association used by the request is taken to the CHANNEL parameter.
Execution results:
Read performed correctly:
ERROR = 0
RC specifies the size in bytes of the data received
Read failed:
ERROR = 1
RC specifies the reason for the failure
__________________________________________________________________________________________
3 / 3 8
MMS Services OFBs 3
__________________________________________________________________________________________
Programming example
Waiting to receive a synchronization variable sent by a sequencer. The "START-
PRODUCING" Boolean type variable is followed by the number of parts to produce,
"PARTS". The program sets to OFBs to receive these two variables.
! IF NOT B1.MURCV0,READY.MURCV1,READY.[MCNCT0,STATE=0]
THEN EXEC MURCV0(;ORDO;START;2;AUX0=>);
THEN EXEC MURCV1(;ORDO;START;2;AUX1=>);
SET B1
!
! <WAIT>
! IF NOT MURCV0, READY THEN JUMP L200
! IF MCNCT0, ERROR THEN JUMP L999
!
! <The "START_PRODUCING" was received.
! <If it is true, the program starts producing parts.
! <Else, it will stop waiting for "PARTS".
!
! IF AUX0,F
THEN JMP L10
THEN EXEC MURCV1(1=>); JUMP L200
!
! L10:
! <Start-Producing>
! <Non blocking wait for the "PARTS" variable.
! IF NOT MURCV1, READY THEN JUMP L200
! IF MURCV1, ERROR THEN JUMP L999
! <etc.
!
! <L200:
! <Program continues...>
Data used
Symbol
Aux0
Aux1
Ordo
Start
Parts
Variable
W0
W1
W10
CW103
CW104
Value
?
?
0 (Channel Num. = 0)
From PL7-MMS
From PL7-MMS
F
Remark
When a Reset action on an MURCV OFB is performed while waiting to receive data, the OFB attempts to warn the module that it is no longer waiting, by sending a message without confirm. The RESET action takes about 2 milliseconds to perform.
__________________________________________________________________________________________
3 / 3 9
__________________________________________________________________________________________
3.7
MRSTA OFB: Device Status (Client Mode)
3.7-1 Function
The MRSTA OFB supports the MMS_STATUS service or reception of
UNSOLICITED_STATUS. It lets a Client application read the status of a remote Server device. The Client can either send a request or wait for transmission from the Server.
3.7-2 PL7-3 Interface
RESET
CHANNEL
UNSOL bit word bit
MRSTA bit
ERROR
F
INHIB PHYSIC bit word
READY LOGIC bit word
STATUS LOCDET word bit
IND word
DETAIL
word [8]
Input Parameters
CHANNEL
UNSOL
Type
Bit
Word
Bit
Access
R/RW
R/R
R/R
Description
Interrupts OFB execution or resets STATUS.
Association number (communication channel
At 1, unsolicited read.
At 0, solicited read (default).
__________________________________________________________________________________________
3 / 4 0
MMS Services OFBs 3
__________________________________________________________________________________________
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
Public Internal Data
STATUS
READY
INHIB
PHYSIC
LOGIC
LOCDET
DETAIL
IND
Type
Word
Access
R/R
Description
IF ERROR is at 1. Identifies execution errors.
Each bit indicates an error.
Bit
Bit
Word
Word
Bit
Table of
8 words
Word
R/R
RW/RW
OFB status:
READY = 1: OFB ready for execution,
Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
R/R
R/R
R/R
Physical status of the remote device.
Logical status of the remote device.
R/R
R/R
Indicates that the optional status (local detail) is present (LOCDET at 1) or not.
This optional field receives the additional status information for PHYSIC and LOGIC. This field de-
MMS Service execution error indicator (indicated by
STATUS bits 8 to 11). Refer to Appendix F/5.
F
LOGIC and PHYSIC States
This data indicates the state of the device, as specified by the MMS standard.
__________________________________________________________________________________________
3 / 4 1
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit
Bit 0
Description
Association not open or being closed.
Association used not available for exchanges.
Corrective Action
Check the CHANNEL parameter or the status of the association
(MCNCTi,STATE and MCNCTi,STATUS variables, i = Association Number).
Check the next two bits to identify the type of error.
Bit 8
Bit 9
MMS error detected by the module
(Bit 8)
MMS error detected by the remote module (Bit 9).
Bit 10 Error during MMS service execution
(Bit 10)
Bit 11 MMS Service rejected (Bit 11).
Bit 13 Communication error. The module rejected the request because it was being configured, unplugged or has failed.
Bit 14 Processing interrupted. OFB execution was interrupted by setting its RESET input to 1 by SY0, a software error or a power break.
Bit 15 System error. The OFB does not have the system resources required for execution.
Analyze the IND parameter to determine the cause of the error.
Check the module configuration and/ or status.
Reduce the number of OFBs configured
(of all types).
F
3.7-3 Using the MRSTA OFB
To implement the MRSTA OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
3.7-4 Programming the MRSTA OFB
The MRSTA OFB lets a Client application read the status of a remote Server device, as defined in the MMS standard. The value of the UNSOL input determines the read mode.
At 0 (default mode), reading is explicitly requested (MMS Service: Status). At 1, unsolicited read is supported and the OFB will wait for the Unsolicited Status request.
__________________________________________________________________________________________
3 / 4 2
MMS Services OFBs 3
__________________________________________________________________________________________
The number of the association used by the request is taken to the CHANNEL parameter.
Execution results:
Data received correctly:
ERROR = 0
PHYSIC and LOGIC contain the physical and logical status of the remote device.
If LOCDET = 1, DETAIL contains additional information.
Read failed:
ERROR = 1
STATUS details the cause of failure
Programming example
The PL7-3 application and the MMS Client await remote device change of state from a robot. The event is indicated using the MMS Unsolicited Status service.
! IF NOT B1.MRSTA0,READY.[MCNCT,STATE=0]
THEN EXEC MRSTA0(;Robot;1=>); SET B1
!
! <WAIT>
! IF NOT MRSTA0, READY THEN JUMP L200
! IF MRSTA0, ERROR THEN JUMP L999
!
! <The status data was received.>
! <Analyze status. If incorrect restart the OFB.
!
! IF [MRSTA0,LOGIC=1]
THEN JUMP L200
! L200:
ELSE RESET B1; JUMP L500
! <Program continues...>
Data used
Symbol
Robot
Variable
W12
Value
Channel number = Inst. MCNCT2
F
Remark
When a Reset action on an MRSTA OFB is performed while waiting to receive data, the OFB attempts to warn the module that it is no longer waiting, by sending a message without confirm. The RESET action takes about 2 milliseconds to perform
__________________________________________________________________________________________
3 / 4 3
__________________________________________________________________________________________
3.8
MUSND OFB: Sending Unsolicited Data (Server Mode)
3.8-1 Function
The MUSND OFB supports the MMS INFORMATION REPORT service. This lets an
MMS Server application send unsolicited data to a Client application.
The variables are MMS Server variables defined with PL7-MMS. At OFB level, the variables are identified by their XTEL-SDBASE symbols (Aliases).
F
3.8-2 PL7-3 Interface
MUSND bit
RESET
CHANNEL word ptr_bit
VAR0_B
VAR0_W
VAR0_DW
NBELT0
.
.
.
.
VAR0…3_B
VAR0…3_W ptr_word ptr_dword word
VAR0…3_DW
NBELT3
RC0…3 bit
READY bit
STATUS word bit
RC0…3 word
IND word
ERROR
__________________________________________________________________________________________
3 / 4 4
MMS Services OFBs 3
__________________________________________________________________________________________
Input Parameters
Type
Bit
Word CHANNEL
VAR0_t to 3_t Ptr_Bit
NBELT 0...3
Word
Access
R/RW
R/R
R/R
R/R
Description
Interrupts OFB execution or resets STATUS.
Association number (communication channel
XTEL-SDBASE Alias of variables to send.
(Set by type)
Number of elements to send.
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
Public Internal Data
STATUS
Type
Word
READY
INHIB
RC0 to 3
IND
Bit
Bit
Word
Word
Access
R/R
R/R
Description
IF ERROR is at 1. Identifies execution errors.
Each bit indicates an error.
OFB status:
READY = 1: OFB ready for execution,
RW/RW Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
Length of data if read action was correct. Else, cause R/R
R/R MMS Service execution error indicator (indicated by
STATUS bits 8 to 11). Refer to Appendix, F/5.
F
__________________________________________________________________________________________
3 / 4 5
F
__________________________________________________________________________________________
Meaning of RC data on error
Value
>= 0
-1
-2
-3
-4
-5
-6
Description
No errors.
Not used (no VARi_t input used).
Only one VARi_t input should be used.
PL7-3 object not supported.
Access exceeds limits (overflows configured field).
Memory resource not available (copy bit type object).
Maximum size for table of set objects exceeded
The following limits apply:
• Bit : 1024
• Word : 1024
• DWord : 1024
__________________________________________________________________________________________
3 / 4 6
MMS Services OFBs 3
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit
Bt 0
Description
Association not open or being closed.
Association not available for exchanges.
Corrective Action
Check the CHANNEL parameter or the status of the association
(MCNCTi,STATE & MCNCTi,STATUS variables, i = Association Number).
Check the variables.
Bit 1
Bit 2
Error accessing data. Access protected or illegal, settings, capacity overflow, etc.
The RCi data indicate the parameter that caused the error.
Access refused by the server.
Error accessing MMS variables
( variabl e not defined, access protected, etc...) The RCi data indicate the parameter that caused the error.
Allocation error. There is not enough space in the PL7-MMS field to perform memory allocation.
Check the VARi parameters. Check the definition of variables with PL7-
MMS (coherence with their definition in the module).
Bit 3
Bit 4
Bit 8
Bit 9
Request too large. The maximum request length is 4096 bytes, else the variables requested in read cause the request to exceed 4096 bytes.
MMS error detected by the module
(Bit 8).
MMS error detected by the remote module (Bit 9).
Bit 10 Error during MMS service execution
(Bit 10).
Bit 11 MMS Service rejected (Bit 11).
Bit 13 Communication error. The exchange failed for one of the reasons listed below:
1. No response to the request before timeout. The PLC master task is overloaded.
2. The module rejected the request because it was being configured or does not have a loaded MMS Client configuration.
Reduce the size of variables to read or reduce the number of OFBs in the application that can perform dynamic memory allocations in the PL7-MMS field.
Reduce the number of variables to read in the request or reduce the size of the data to read.
Check the next two bits to identify the type of error.
Analyze the IND parameter to determine the cause of the error.
Increase the master task cycle time or reduce the PLC load (in case 1). Check the module configuration (in case 2).
Bit 14 Processing interrupted. OFB execution was interrupted by setting its RESET input to 1 by SY0, a software error or a power break.
Bit 15 System error. The OFB does not have the system resources required for execution.
Reduce the number of OFBs configured
(of all types).
__________________________________________________________________________________________
3 / 4 7
F
F
__________________________________________________________________________________________
3.8-3 Using the MUSND OFB
To implement the MUSND OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
3.8-4 Programming the MUSND OFB
The MUSND OFB lets a Server PL7-3 application send, at its own initiative, the values of 1 to 4 MMS Server variables to a remote Client application. MUSND corresponds to the MURCV OFB in a PL7-3 Client application.
MMS variables are defined with PL7-MMS in the same way as MMS server variables.
This OFB operates in the same way as MWRIT (in Client mode) except that the setting of Server variables (MUSND) is different from that of Client variables (MWRIT). (Refer to Sub-section 3.4).
The XTEL-SDBASE Alias for the MMS variables to send values for are set to the
VARi_B, VARi_W or VARi_DW inputs depending on the types of variables used (refer to Divider F, Sub-section 3.2). The size of data to send is set to the SIZEi inputs and expressed as a number of elements.
The number of the association used by the request is taken to the CHANNEL parameter.
__________________________________________________________________________________________
3 / 4 8
MMS Services OFBs 3
__________________________________________________________________________________________
Execution results:
Data sent correctly:
ERROR = 0
RCi = 0
Read failed:
ERROR = 1
RCi specifies the reason for the failure
Programming example
Send the "SUPERVISOR" application "FAILURE" variables (bit B100) and "CAUSE", the cause of the failure (word W100). "FAILURE" is a Boolean type with FAIL as its symbol. "CAUSE" is a "1 byte string" identified by CAUSE. Finally the association is identified by the variable SUPER (opened by MCNCT1).
! <If FAIL is at 1, a failure was found; CAUSE gives the cause.
! <The program warns the supervisor.
!
! IF FAIL.NOT B1.MUSNDV0,READY.[MCNCT0,STATE=0]
THEN EXEC MUSND0(;SUPER;FAIL;;;CAUSE=>);
SET B1
!
! <WAIT>
! IF NOT MUSND0, READY THEN JUMP L500
! IF MUSND0, ERROR THEN JUMP L999
!
! <Program continues...>
Data used
Symbol
SUPER
FAIL
CAUSE
Variable
W11
B100
W100
Value
1
1 to trigger send
?
F
__________________________________________________________________________________________
3 / 4 9
__________________________________________________________________________________________
3.9
MSSTA OFB: Sending Device Status (Server Mode)
3.9-1 Function
The MSSTA OFB supports the MMS UNSOLICITED_STATUS service. It lets an MMS
Server application send the status of its device to a Client. Transmission can be cyclic or triggered.
F
3.9-2 PL7-3 Interface
RESET
CHANNEL
TCYCLE bit word word
MSSTA bit
INHIB PHYSIC bit word
READY LOGIC bit word
STATUS IND word word
ERROR
__________________________________________________________________________________________
3 / 5 0
MMS Services OFBs 3
__________________________________________________________________________________________
Input Parameters
CHANNEL
TCYCLE
Type
Bit
Word
Word
Access
R/RW
R/R
R/R
Description
Interrupts OFB execution or resets STATUS.
Association number (communication channel
Sample and change status time (in MAST cycles).
At 0, only one transmission will be made.
Output Parameters
ERROR
Type
Bit
Access
R/R
Description
Execution error detected by the OFB.
Public Internal Data
STATUS
Type
Word
READY
INHIB
PHYSIC
LOGIC
IND
Bit
Bit
Word
Word
Word
Access
R/R
Description
IF ERROR is at 1. Identifies execution errors.
Each bit indicates an error.
R/R
RW/RW
OFB status:
READY = 1: OFB ready for execution,
Inhibits error indication:
ERROR and STATUS remain at 0, OFB execution is
F
R/R
R/R
R/R
Physical status of the remote device.
Logical status of the remote device.
MMS Service execution error indicator (indicated by
STATUS bits 8 to 11). Refer to Appendix F/5.
LOGIC and PHYSIC States
This data indicates the state of the device, as specified by the MMS standard.
__________________________________________________________________________________________
3 / 5 1
F
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit
Bit 0
Signification
Association not open or being closed.
Association not available for exchanges.
Corrective Action
Check the CHANNEL parameter or the status of the association
(MCNCTi,STATE & MCNCTi,STATUS variables, i = Association Number).
Check that the TCYCLE parameter does not exceed 32767.
Bit 1
Bit 8
Bit 9
TCYCLE parameter exceeds limits.
The value of TCYCLE exceeds 32767 cycles.
MMS error detected by the module
(Bit 8).
MMS error detected by the remote module (Bit 9).
Bit 10 Error during MMS service execution
(Bit 10).
Bit 11 MMS Service rejected (Bit 11).
Check the next two bits to identify the type of error.
Analyze the IND parameter to determine the cause of the error.
Bit 13 Communication error.The exchange failed for one of the reasons listed below:
1. No response to the request before timeout. The PLC master task is overloaded.
2. The module rejected the request because it was being configured or does not have a loaded MMS Server configuration.
Increase the master task cycle time or reduce the PLC load (in case 1).
Check the module configuration (in case 2).
Bit 14 Processing interrupted. OFB execution was interrupted by setting its RESET input to 1 by SY0, a software error or a power break.
Bit 15 System error.
The OFB does not have the system resources required for execution.
Reduce the number of OFBs configured
(of all types).
__________________________________________________________________________________________
3 / 5 2
MMS Services OFBs 3
__________________________________________________________________________________________
3.9-3 Using the MSSTA OFB
To implement the MRSTA OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
3.9-4 Programming the MSSTA OFB
The MSSTA OFB lets a PL7-3 MMS Server application send its status to a Client application.
There are two ways to use the OFB:
• The status is sent on change of state. The status is polled per iodically (every TCYCLE cycles of the master task).
The OFB execution command is only sent once.
Periodic transmission of the status information can be stopped by executing the OFB with RESET set to 1.
• The Status is only sent when the OFB is executed. To do so, set TCYCLE to 0.
The number of the association used by the request is taken to the CHANNEL parameter.
Programming example
Sending the status to the SUPERVISOR application on change of state, polled every 50 master task cycles.
F
! IF NOT B1.MSSTA0,READY.[MCNCT1,STATE=0]
THEN EXEC MSSTA0(;SUPER;50=>); SET B1
!
! <WAIT>
! IF NOT B2 THEN EXEC MSSTA(1;;=>); SET B2
!
! IF MSSTA0, ERROR THEN JUMP L999
!
! <Program continues...>
Data used
Symbol
SUPER
Variable
W1!
Value
1 Channel number = Inst. MCNCT1
__________________________________________________________________________________________
3 / 5 3
__________________________________________________________________________________________
F
__________________________________________________________________________________________
3 / 5 4
MSEMA OFB: Synchronizing Access to an MMS Server Variable 4
__________________________________________________________________________________________
4.1
Function
The MSEMA OFB is used to "synchronize" access to a Local (Server) PLC MMS
Variable, by a remote (Client) device and its usage in the local PL7-3 application.
The OFB manages a semaphore that indicates that a Local MMS variable, for which read/write access is expected, is available for use in the application.
The semaphore management is essentially used for writing variables with a size that exceeds 128 bytes: writing these variable by the remote device via the TSX ETH 200 interface requires a number of PLC cycles. The semaphore is therefore used to inhibit any access to the variable while it is being written.
The Local MMS variables that a semaphore must be assigned to are the ones configured in Programmed Mode using PL7-MMS V2.5 .
If, when access to a variable is requested by a remote device, the interface is found to not have an assigned semaphore, the MMS service requested for this variable
(Read/Write) will be put on hold until the MSEMA OFB is executed for this variable.
F
__________________________________________________________________________________________
4 / 1
F
__________________________________________________________________________________________
4.2
PL7-3 Interface
Inputs
RESET
MSEMA
: bit ERROR : bit
CHANNEL : word
VAR_B : ref_bit
VAR_W : ref_word
VAR_DW : ref_dword
Outputs
Internal
Public
Data
INHIB : bit
STATUS : word
READY : bit
STATUS : word
RC
IND
: word
: word
__________________________________________________________________________________________
4 / 2
MSEMA OFB: Synchronizing Access to an MMS Server Variable 4
__________________________________________________________________________________________
Input parameters
Parameters Type
RESET Bit
Access
R/RW (1)
Description
Setting RESET to 1 will interrupt OFB execution (READY bit at 0) or resetting STATUS to zero (READY bit at 1).
By default RESET =0
CHANNEL
VAR_t with t = B,
W or DW
Word ref_t
R (1)
R (2)
R (1)
R (2)
Number of the association open for MMS exchanges.
By default CHANNEL = -1.
MMS Server variable to assign to the semaphore.
By default, these inputs are considered as not being wired.
Output parameters
)
Parameters Type
ERROR Bit
R (2)
Internal public data
Parameters Type
INHIB Bit
Access
R (1)
Access
R/W (1)
R/W (2)
Description
Error detected by the OFB (if INHIB = 0).
STATUS
RC
IND
READY
Word
Word
Word
Bit
R (1)
R (2)
R (1)
R (2)
R (1)
R (2)
R (1)
R (2)
Description
Inhibits error indication.
ERROR and STATUS always stay at zero.
By default INHIB = 0.
Identifies a detected error.
See list of indicated errors on page 4/5
Cause of a protection failure.
(see list of possible causes on page 4/4
Valid only if READY = 1.
Indicates an MMS service failure.
(indicated by STATUS bits 8 to 11).
When READY is at 0, the Server variable has not yet been written or read by the
Client device.
On a rising edge on READY, the variable is written r read and is available; READY stays at 1 until the OFB is next executed.
F
(1): access by program.
(2): access by request.
__________________________________________________________________________________________
4 / 3
__________________________________________________________________________________________
Meaning of RC data on error
Value
>=0
Description
No errors.
-1
-2
-3
-103
The VAR input is not used.
Only one VAR_x input should be used.
PL7-3 object not supported
Object-access-denied:
Access is not allowed to association scope variables.
-108
-110
Object-Attribute-inconsistent:
The variable is not programmed.
Object-non-existent
The variable is not present in the table of symbols.
F
__________________________________________________________________________________________
4 / 4
MSEMA OFB: Synchronizing Access to an MMS Server Variable 4
__________________________________________________________________________________________
APPLIDIAG Interface: STATUS Details
Bit Description
Bit 0=1 The association is not open or being closed.
The association used (CHANNEL parameter) is not available for exchanges.
Bit 1=1 Error accessing data.
The parameter given in the VAR_B,
VAR_W or VAR_DW input is incorrect.
Bit 2=1 Access to the variable refused by the interface.
The variable to associate to the semaphore (VAR_x input) does not exist or is not in program mode.
Corrective action
Check the CHANNEL parameter or the association status (MCNCTi, STATE and MCNCTi, STATUS variables, where i is the association number).
Analyze the value of the RC parameter to determine the cause of the error.
Analyze the value of the RC parameter to determine the cause of the error.
Bits 3 to 7
Non used.
Bit 8=1 MMS error detected by the interface.
Bit 9=1 Error detected by the remote station.
The interface or the remote station detected an error in MMS service processing.
Access the next two bits to determine the type of error.
Bit 10=1 Error during MMS service execution.
Bit 11=1
MMS service execution ended on an error condition.
Analyze the IND parameter to determine the cause of the error.
Bit 12 Not used.
Bit 13=1 Communication error.
Exchange with the interface failed.
Check the configuration and/or the interface status.
Bit 14=1 Processing interrupted.
OFB execution was interrupted during execution by a RESET action, an
SY0, SY1 request, a program error or a power failure.
Bit 15=1 System error.
The OFB lacks the system resources
Reduce the number of OFBs configured (all families combined).
required for execution.
__________________________________________________________________________________________
4 / 5
F
__________________________________________________________________________________________
4.3
Using the MSEMA OFB
To implement the MSEMA OFB, first open (or identify) an association with the remote application by executing an instance of the MCNCT OFB.
Also ensure that the local variable used as a parameter for MSEMA was declared with the "PROG" access mode in PL7-MMS.
F
4.4
Programming the MSEMA OFB
The MSEMA OFB ensures that the PL7-3 application is informed of a read or write request affecting one of its local variables, sent by a remote application.
An instance of the MSEMA OFB can control a single variable. The name of the local
MMS variable is set to one of the VAR_B, VAR_W, VAR_DW inputs depending on the type of the variable (refer to Divider F, Sub-section 3.2).
The number of the association used by the request is taken to the CHANNEL parameter.
Case 1
To guarantee a coherent value for a variable with a size between 120 bytes and 4Kbytes, as it is modified, for the same MMS service request, over a number of PLC cycles
(coherence management).
For each variable that is considered "sensitive", an instance of the MSEMA OFB must be programmed in the PL7-3 application and the value of the READY bit tested. Testing the READY bit will indicate whether access is completed:
• The value has been completely updated by the interface (MMS Write Service), the
PL7-3 program can read and process it,
• The value has been completely returned to the remote station (MMS Read Service), the PL7-3 program can modify it once again.
Case 2
To avoid loosing intermediate values for a variable accessed in "bursts" by a remote station (sequence management).
Program as many instance EXECs for the MSEMA OFB for the same variable deemed to be "sensitive" as there are MMS services likely to cause simultaneous access. Testing the READY bit enables "separating" values that came to the interface in a batch:
The first EXEC of the OFB releases the first value that can be taken into account by the
PL7-3 application (MMS Write Service), by restarting the next EXEC, the interface will release the next value of the same variable that it will have saved because there was no associated EXEC, and so on.
__________________________________________________________________________________________
4 / 6
MSEMA OFB: Synchronizing Access to an MMS Server Variable 4
__________________________________________________________________________________________
Execution results:
• Ready goes to 0:
The designated variable is being accessed by the interface following a read/write request from the remote station.
• Ready goes from 0 to 1:
The variable is no longer being accessed, the PL7-3 application can use it.
Programming example:
Ensuring coherence for a variable of over 128 bytes.
The remote supervisor sends a WRITE that contains a sequence initializing a number of processes (symbolized by the INITSEQ local variable) to a server PLC using an association previously identified by an Accept (symbolized by PLCRCV2).
!
IF NOT B100 THEN
EXEC MSEMA0( ; PLCRCV2 ; ; INITSEQ ; =>) ;
SET B100; !
!< Wait until finished writing INIT values >
!
MSEMA0.READY
→
B200;
!
IF RE(B200) THEN JUMP PROCESS-INITSEQ
!
IF MSEMA0,ERROR THEN JUMP PROCESS-ERROR
Ensuring sequencing for a variable written in bursts.
The remote supervisor sends a number of WRITEs of the same variable (symbolized by
COLOR) with different value, for processing in sequence by a server PLC. They are sent using an association previously identified by an Accept (symbolized by PLCRCV2).
!< RECEIVE COLOR >
!
IF NOT B100 THEN EXEC MSEMA0( ; PLCRCV2 ; ; COLOR ; =>) ;
!
SET B100;
!< Wait end of processing for a color >
!
MSEMA0.READY
→
B200;
!
IF RE(B200) THEN JUMP PROCESS-COLOR
!
IF MSEMA0,ERROR THEN JUMP PROCESS-ERROR
!< PROCESS-COLOR >
! ——— succession of PL7-3 instructions ———
! IF COUNTER=0 THEN JUMP RECEIVE-COLOR
F
__________________________________________________________________________________________
4 / 7
F
__________________________________________________________________________________________
Remarks
• If 2 EXECs of MSEMA are programmed on the same variable and in the same
MAST cycle:
EXEC MSEMA1 (VARIABLE1);
...............
EXEC MSEMA0 (VARIABLE1); regardless of the instance number programmed first in the PL7-3 application, the lowest instance number value will always be executed first. The instances are stored in rising number order in the processor execution queues and executed at the end of the MAST cycle, in that order.
• If 2 EXECs of MSEMA are programmed on two different variables in the same
MAST cycle:
EXEC MSEMA0 (VARIABLE1);
...............
EXEC MSEMA0 (VARIABLE2); it is always the last programmed variable that will be taken into account. The parameters taken into account previously will be overwritten and the execution at the end of the MAST cycle will affect the last values of the stored parameters.
__________________________________________________________________________________________
4 / 8
Appendix 5
__________________________________________________________________________________________
5.1
Error Handling
Status:
Ind:
RCi:
Identifies the type of error (it can be accessed using APPLIDIAG).
There are two possible classes:
• OFB programming errors.
• MMS communication errors.
For the "MMS communication error class" the IND parameter identifies the cause of the MMS error.
If b8 = 1, the values of IND are given by the list of "MMS service execution errors" in Sub-section 4.2.
If b9 = 1, the IND errors are Error class\Error Code (MSB\LSB) from the
MMS standard or from the implementation of the remote service (corresponds to "PDU MMS Error".
Identifies MMS communication errors.
There are two possible classes:
If b8 = 1, error detected by the local module.
If b9 = 1, error detected by the remote module.
Identifies an error that occurred when accessing an MMS variable.
If b4 = 1, RCi contains the error type
(Refer to the list of RCi for each service).
(Corresponds to "Data access failure MMS").
F
__________________________________________________________________________________________
5 / 1
F
__________________________________________________________________________________________
Error analysis diagram
Corrective action First level diagnostics
▼
ERROR Bit =1
YES
NO
Second level diagnostics
NONE
STATUS bits
0,1,2,3,5,6,7,12,
13,14,15=1
YES OFB programming error
See local application
STATUS bit 8 =1
YES
Local error see IND
See local application
STATUS bit 9 =1
YES
Remote error see IND
STATUS bit 4 =1
YES
Remote error accessing a variable see RCI
See remote applications
See
remote applications
__________________________________________________________________________________________
5 / 2
Appendix 5
__________________________________________________________________________________________
5.2
MMS Service Execution Error Indications (IND)
Value
22
27
41
42
49
50
1000
1001
2001
1002
1003
Description
Indicates the services were still being processed when a Conclude was sent. Wait until the end of processing before handling Conclude.
Indicates that the maximum number of services confirmed during processing on this association was exceeded. The maximum number of possible confirmed services depends on the number of associations defined in PL7-OSI (refer to Divider D, Sub-section 3.2-3).
Indicates that the maximum "Nesting_Level" value negotiated when the association was opened was exceeded. Example, a Write.req service used to write a table of structures was sent when the negotiated
"Nesting_Level" was 1.
Indicates that a named variable is being accessed when the VNAM parameter is not supported on the association.
Indicates that an "Array" type is specified when the STR1 parameter is not supported by the association.
Indicates that a "Structure" type is specified when the STR2 parameter is not supported by the association.
Service cannot be processed in the current module state. The service request must be repeated until no error condition occurs.
No module resources for processing the service. This may occur, for example, if the PL7-3 application opens more associations than are configured in the module.
The time-out for an MMS response from the remote device is exceeded
(Time_Out). When this error occurs, close the affected association using
ABORT as the module may be in an incoherent state. Also check that the remote device is still operational then, if necessary, increase the value of the Time_Out parameter in the MCNCT OFB prior to reopening the association.
The module does not have any open association with the references requested (APPLI and/or CHANNEL parameters). This may occur, for example, in one of the following cases:
• Send "Accept.req" without any association opened by the remote device,
• Send "Conclude.req" or "Abort.req" on an association that is not open,
• Send a confirmed service on an association that is not open.
F
__________________________________________________________________________________________
5 / 3
F
__________________________________________________________________________________________
Value Description
1004
1005
1006
1007
1008
1009
1011
1012
2000
The module already has an association open with the requested references (APPLI and CHANNEL parameters). This occurs if the PL7-3 application send two consecutive open association requests with the same MCNCT OFB instance number without first closing the previous instance.
Error code corresponding to a WARNING, the association can be used.
The module already has an association open with the same reference for the CHANNEL parameter and with a different reference for the APPLI parameter. This occurs if the PL7-3 application open an association with
Appli1 then using the same instance of the MCNCT OFB, opens an association with Appli2 without first closing the previous instance.
The association with the requested references (APPLI and CHANNEL parameters) has already been identified in the module. This occurs if the
PL7-3 application sends two consecutive "Accept" requests to Appli1 with the same instance of the MCNCT OFB.
Error code corresponding to a WARNING, the association can be used.
The value of the MCNCT OFB APPLI parameter used to send "Initiate.req" is not recognized by the module. Check the configuration of Remote
Application uploaded to the module.
The PL7-3 application is attempting to perform an "Accept" on an association that it opened and that is illegal.
"Abort.ind" returned by the module (this is not an error, only an indication).
The module is not yet operational for executing a service. Repeat the service request until no error code occurs (repeat execution of the affected
MMS service OFB).
Flow control returned that indicates an unconfirmed service that cannot be processed by the module. Repeat the service request until no error code occurs (repeat execution of the affected MMS service OFB).
Protocol error. Contact Telemecanique technical support.
__________________________________________________________________________________________
5 / 4
Appendix 5
__________________________________________________________________________________________
5.3
Error Codes Returned to Status by MMSLD V2.0
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Description
Gate allocation error in the PLC message system. No message system resources available.
Corrective Action
No message system resources are available in the PLC processor. The
OFB can no longer dialog with the module. This situation can resolve itself after a few seconds.
MMS application failed or non-existent.
OSI application failed or non-existent.
Check that the MMS.BIN application is correctly loaded in the PLC processor an that there is a table of symbols for local variables.
Check that the OSI.BIN application is correctly loaded in the PLC processor.
Module failure.
Check the module terminal block, check that the module is installed in the configured location in the rack.
Interface error during message exchange.
Error loading the OSI configuration in the module.
Error loading the MMS table of symbols in the module.
These errors are caused by an interruption in the dialog between the PLC and the module. If on restart there are no serious errors, the OFB returns to normal operation (uploading the module) without further operator intervention.
Remarks:
• Setting the INHIB input to 1 resets the ERROR bit to 0 and the STATUS word takes the value 0,
• Resetting the INHIB input to 0 allow updating of the ERROR and STATUS outputs in the event of an error.
F
__________________________________________________________________________________________
5 / 5
F
__________________________________________________________________________________________
5.4
Adding an MMS Variable to an Existing Project
1. Adding a local variable to STATION 1:
• Start PL7-PMS on STATION 1
- MENU: C
ONFIGURATION
/L
OCAL
V
ARIABLES
/D
EFINE LOCAL VARIABLES
:
Enter the full characteristics of the variable, refer to Divider E, Sub-section 3.3.
- MENU: Configure/PLC
Generate the .BIN file
- MENU: T
RANSFER
/D
ISK
→
PLC
Transfer the .BIN file to the PLC.
2. Adding a remote variable to STATION 2:
• Start PL7-PMS on STATION 2
- MENU: C
ONFIGURE
/MMS P
ROJECT
D
IRECTORY
/D
EFINE REMOTE VARIABLES
:
Enter the full characteristics of the variable, refer to Divider E, Sub-section 3.1.
- MENU: C
ONFIGURE
/R
EMOTE VARIABLES
:
Refer to Divider E, Sub-section 3.2.
Enter:
. CWi variables,
. The SDBASE "Alias" symbol
From the "D
EFINE
R
EMOTE
MMS V
ARIABLES
" window:
Select the associated MMS variable.
- MENU: C
ONFIGURE
/PLC
Generate the .BIN file
- MENU: T
RANSFER
/D
ISK
→
PLC
Transfer the .BIN file to the PLC.
• Start PL7-3 on STATION 2
- Read the MMS.CST constants file
(READ function in selection: 3-CONSTANTS in PL7-3).
__________________________________________________________________________________________
5 / 6
________________________________________________________
General Appendix G
___________________________________________________________________________
Section
1 PICS
1.1
Information Relative to Implentation (PICS)
1.2
Supported MMS Services (PICS Service CBBs)
1.3
Supported MMS Parameters (Parameter CBBs)
1.4
Characteristics Specific to Implementation
(PICS Local Implementation Values)
Page
1/1
1/3
1/4
1/5
___________________________________________________________________________
G / 1
G
________________________________________________________
___________________________________________________________________________
G
___________________________________________________________________________
G / 2
PICS 1
__________________________________________________________________________________________
1.1
Information Relative to Implementation (PICS)
Implementation's Vendor name
Implementation's Model Name
Implementation's Revision Identifier
Telemecanique
System Dependent
2.0
System Dependent Machine Name(s) and
Version Number(s)
Operating System(s)
MMS abstract syntax
MMS Version Number Supported
System Dependent
ISO/DIS 9506
ISO/IS 9506
0 and 1
Not supported MMS Companion Standard abstract syntaxes
MMS Companion Standard
Version Number Supported
Calling MMS-user
Called MMS-user
Not supported
Yes
Yes
Not Used List of Standardized Names
RequestDomainDownload
RequestDomainUpload
LoadDomainContent
StoreDomainContent
DeleteDomain
GetDomainAttributes
CreateProgramInvocation
DeleteProgramInvocation
Start
Stop
Resume
Reset
Kill
GetProgramInvocationAttributes
Server
Server
Server
Server
Server
Server
Server
Server
Server
DefineEventCondition
DeleteEventCondition
__________________________________________________________________________________________
1 / 1
G
G
__________________________________________________________________________________________
GetEventConditionAttributes
ReportEventConditionstatus
AlterEventConditionMonitoring
TriggerEvent
DefineEventAction
DeleteEventAction
GetEnventActionAttributes
ReportEventActionStatus
DefineEventEnrollement
DeleteEventEnrollement
AlterEventEnrollement
ReportEventEnrollementStatus
GetEventEnrollementAttributes
AcknowledgeEventNotification
AttachToEventCondition
EventNotification
GetAlarmSummary
GetAlarmeEnrollementSummary
ReadJournal
WriteJournal
InitializeJournal
CreateJournal
DeleteJournal
ReportJournalStatus
ObtainFile
__________________________________________________________________________________________
1 / 2
PICS 1
__________________________________________________________________________________________
1.2
Supported MMS Services (PICS Service CBBs)
Service Conformance Building Block
Initiate
Conclude
Cancel
UnsolicitedStatus
Status
GetNameList
Identify
Rename
GetcapabitlityList
Read
Write
InformationReport
GetVariableAccessAttributes
DefineNamedVariable
Server, Client or Both
Both
Both
Both
Both
Server
Server
Both
Both
Both
Server
DefineScatteredAccess
GetScatteredAccessAttributes
DeleteVariableAccess
DefineNamedVariableList
GetNamesVariableList
DeleteNamedVariableList
DefineNameType
GetNamedTypeAttributes
DeleteNamedType
Input
Outpout
TakeControl
RelinquishControl
DefineSemaphore
DeleteSemaphore
ReportSemaphoreStatus
__________________________________________________________________________________________
1 / 3
G
__________________________________________________________________________________________
Supported MMS Services (PICS Service CBB's)
ReportPoolSemaphoreStatus
ReportSemaphoreEntryStatus
AttachToSemaphore
InitiateDownloadSequence
DownloadSegment
TerminateDownloadSequence
InitiateUploadSequence
UploadSegment
TerminateUploadSequence
Server
Server
Server
Server
Server
Server
1.3
Supported MMS Parameters (Parameter CBBs)
G
Parameter Conformance Building Block Server, Client or Both
STR1 (Support for ARRAYs) Yes
STR2 (Support for STRUCTUREs) Yes
NEST (Maximum Data Structure
Nesting Level)
NEST = 2 (1)
VNAM (Support for NAMED variables) Yes
VADR (Support for UNNAMED and
SINGLE variables)
VALT (Support for Alternate Access)
Yes*
Yes*
VSCA (Support for Scarattered Access) No
TPY (Support for a Third Party File
Server
No
REAL (Support for REAL) No
ACKEC (Support of Acknowledgement No
Event Condition Parameter)
CEI (Support forEvaluation Interval
Parameter
NO
* Read/Write Server only: No alternative access for writing a field with a Boolean or BitString1 table element type structure.
(1) Tables of tables and structures that have a structure as a field are not supported.
__________________________________________________________________________________________
1 / 4
PICS 1
__________________________________________________________________________________________
1.4
Characteristics Specific to Implementation (PICS Local
Implementation Values)
Local Implementation Value
Range of values for floating point numbers
Support
IEEE 754 (Single)
Supported values of the floating point exponent width IEEE 754 (Single)
Supported values of the floating point format width
Range of values for signed integer
Range of values for unsigned integer
Maximum length for-BIT STRING in bits
IEEE 754 (Single)
[-2147483648..2147483647]
[0..2147483647]
2048
4096
Symbolic
Maximum length for OCTET STRING in octet
Address formats for VADR horizontal CBB
Maximum Input Time Out in seconds
Level of support for time
Granularity of time in milliseconds
Uninterruptible access to variable
Date and time
10
Length of variable less than 120 bytes
Priority processing for semaphores
Capabilities of VMD
Local Detail
File Name Syntax
Yes refer to Document
Range of Maximum Services Outstanding Calling [0..2] ME[2..5]
Range of Maximum Services Outstanding Called [0..2] ME[2..5]
Execution Argument
Additionnal Code in Error Type Yes refer to Document
Additionnal Detail in Error Type
Method for Extended Derivation of
Status Information
Local Detail Calling/Called
Load Data Format
Maximum number of Upload State machines
[64..7168]
TSX PLC application format
1
G
__________________________________________________________________________________________
1 / 5
__________________________________________________________________________________________
G
__________________________________________________________________________________________
1 / 6
________________________________________________________
Application Example H
___________________________________________________________________________
Section
1 Application Example
1.1
Presentation
1.2
R6S0 Device Application
1.2-1 Hardware Configuration
1.2-2 Master Task Program, Main Program Module:
MAST/MAIN
1.2-3 OSI Addresses, TSX ETH 200 Module
1.2-4 PL7-3 Constants
1.2-5 List of MMS Variables
1.2-6 List of PL7-3 Symbols
1.3
R6S1 Device Application
1.3-1 Hardware Configuration
1.3-2 Master Task Program, Main Program Module:
MAST/MAIN
1.3-3 OSI Addresses, TSX ETH 200 Module
1.3-4 PL7-3 Constants
1.3-5 List of MMS Variables
1.3-6 List of PL7-3 Symbols
Page
1/1
1/1
1/1
1/2
1/8
1/9
1/10
1/12
1/13
1/13
1/13
1/20
1/22
1/22
1/25
___________________________________________________________________________
H / 1
H
________________________________________________________
___________________________________________________________________________
H
___________________________________________________________________________
H / 2
Application Example 1
1.1
Presentation
The example described in this Section is the one presented in the Methodology Section,
Divider B, Sub-section 2.1.
Remider of the OSI network layout
FTX 507
ETHERNET
APRIL R6S0
APRIL 7000
R6S1
TSX 7 TSX 7
1.2
R6S0 Device Application
1.2-1 Hardware Configuration
Rack reference: TSX RKN 82F
_____________________________________________________________________
RACK
0/1
S
U
P
7
0
1
0
7
5
5
/
4
M
A
P
1
0
7
E
T
H
2
0
0
D
S
T
8
3
5
D
S
T
8
3
5
D
E
T
1
6
1
2
PS M 0 1 2 3 4 5 6 7
___________________________________________________________________________
1 / 1
H
1.2-2 Master Task Program, Main Program Module: MAST/MAIN
<initialize variables for MCNCT0 (manage association C0)
! IF SY0+SY1 THEN 2->Mod_cnc0
W1 : Mod_cnc0
<initialize variables for INITIATE C0
! IF RE(I5,0) THEN 0->Com_cnc0
W0 : Com_cnc0
<initialize variables for CONCLUDE C0
! IF RE(I5,2) THEN 2->Com_cnc0
W0 : Com_cnc0
<initialize variables for ABORT C0
! IF RE(I5,3) THEN 3->Com_cnc0
W0 : Com_cnc0
<manage association C0 to R6S1
! IF RE(I5,0)+RE(I5,2)+RE(I5,3)
THEN EXEC MCNCT0(Res_cnc0;Com_cnc0;Mod_cnc0;R6s1;500=>Err_cnc0)
OFB: I/O PARAMETERS
Res_cnc0
Com_cnc0
Mod_cnc0
R6s1
500
MCNCT0
RESET : bit
COMMAND : word
MODULE : word
APPLI : pt_w
TIMEOUT : word
ERROR : bit Err_CNC0
B0
W0
W1
CW0
B3
: Res_cnc0
: Com_cnc0
: Mod_cnc0
: R6s1 remote application (R6S1)
: Err_cnc0
<display status connection C0
! Ste_cnc0->O4,0[4]
MCNCT0,STATE : Ste_cnc0
<if association C0 open, O3,0 blinks
! IF [Ste_cnc0=0] THEN SY6->O3,0
MCNCT0,STATE : Ste_cnc0
H
___________________________________________________________________________
1 / 2
Application Example 1
<display MWRITE0
! MWRIT0,READY.NOT MWRIT0,ERROR->O4,4
<write a W and a bit to R6S1 (C0) and restart soon as ready + count
! IF I5,4.MWRIT0,READY.[MCNCT0,STATE=0]
THEN INC W100;EXEC MWRIT0(B4;MCNCT0,CHANNEL;CW11;;W100;CW10;;W10;;;;;;=>);
INC W3;RESET B4
B4
MCNCT0,CHANNEL
CW11
W100
CW10
W10
OFB: I/O PARAMETERS
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
MWRIT0
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
MCNCT0,STATE
W100
B4
: Ste_cnc0 W100
: Val_w100 value to write to remote w100
: Res_wri0
MCNCT0,CHANNEL : Cha_cnc0
CW11 : Word_w100 remote variable (R6S1)
CW10
W10
: Bit_b10 remote variable (R6S1)
: Val_b10 value to write to R6S1
___________________________________________________________________________
1 / 3
H
<display MREAD0
! MREAD0,READY.NOT MREAD0,ERROR->O3,7
<read W and bit written to R6S1 (C0) by previous OFB and restart ..
! IF I5,4.MREAD0,READY.[MCNCT0,STATE=0]
THEN EXEC MREAD0(B5;MCNCT0,CHANNEL;CW11;2;W110;CW10;2;W11;;;;;;=>);
INC W4;RESET B5
B4
MCNCT0,CHANNEL
CW11
2
W110
CW10
2
W11
OFB: I/O PARAMETERS
MREAD0
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
MCNCT0,STATE
B5
: Ste_cnc0
: Res_rea0
MCNCT0,CHANNEL : Cha_cnc0
CW11 : Word_w100 remote variable (R6S1)
W110 : Res_w100 result read W100 from R6S1
CW10
W11
: Bit_b10 remote variable (R6S1)
: Res_b10 result read from R6S1
H
___________________________________________________________________________
1 / 4
Application Example 1
<display MREAD1 (structure + table)
! MREAD1,READY.NOT MREAD1,ERROR->O3,4
<read structure + a table of 250 DW from R6S1 (C0) + count
! IF I5,A.MREAD1,READY.[Ste_cnc0=0]
THEN EXEC MREAD1(;Cha_cnc0;Voit;14;Res_voit;T250_dw;1000;Res_dw;;;;;;=>);
INC W5
OFB: I/O PARAMETERS
MCNCT0,STATE
MCNCT0,CHANNEL
CW13
W122
CW15
W100
Cha _cnc0
Voit
14
Res voit
T250_dw
1000
Res_dw
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
MREAD1
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
: Ste_cnc0
: Cha_cnc0
: Voit remote variable (R6S1)
: Res_voit result read structure from R6S1
: T250_dw remote variable (R6S1)
: Res_dw result read 250 dw from R6S1
___________________________________________________________________________
1 / 5
H
<display MURCV0
! MURCV0,READY.NOT MURCV0,ERROR->O3,6
<receive unsolicited data (information report) from R6S1 (C0)+ count
! IF I5,6.MURCV0,READY.[Ste_cnc0=0]
THEN EXEC MURCV0(Res_urc0;Cha_cnc0;Umot_w15;2;Res_uw15=>);INC W7
Res_urc0
Cha_cnc0
Umot_w15
2
Res_uw15
OFB: I/O PARAMETERS
RESET : bit
CHANNEL : word
VAR : word
SIZE : word
MURCV0
BUFFER : pt_w
ERROR : bit
MCNCT0,STATE
B6
MCNCT0,CHANNEL
CW12
W20
: Ste_cnc0
: Res_urc0
: Cha_cnc0
: Umot_w15 remote variable (R6S1)
: Res_uw15 result receive info report
<Visu MURCV1
! MURCV1,READY.NOT MURCV1,ERROR->O3,5
<receive unsolicited data (information report) from R6S1 (C0) + count
! IF I5,7.MURCV1,READY.[Ste_cnc0=0]
THEN EXEC MURCV1(Res_urc1;0;Bit_b10;2;Res_b10=>);INC W6
Res_urc1
0
Bit_b10
2
Res_b10
OFB: I/O PARAMETERS
RESET : bit
CHANNEL : word
VAR : word
SIZE : word
BUFFER : pt_w
MURCV1
ERROR : bit
MCNCT0,STATE
B7
CW10
W11
: Ste_cnc0
: Res_urc1
: Bit_b10 remote variable (R6S1)
: Res_b10 result read from R6S1
H
___________________________________________________________________________
1 / 6
Application Example 1
<read STATUS of R6S1 from C0
! IF I5,8.MRSTA0,READY.[Ste_cnc0=0]
THEN EXEC MRSTA0(Res_ssta;Cha_cnc0;=>)
OFB: I/O PARAMETERS
Res_ssta
Cha_cnc0
RESET : bit
CHANNEL : word
UNSOL : bit
MRSTA0
ERROR : bit
MCNCT0,STATE
B8
MCNCT0,CHANNEL
: Ste_cnc0
: Res_ssta
: Cha_cnc0
<receive unsolicited STATUS sent by R6S1 to C0
! IF I5,9.MRSTA1,READY.[Ste_cnc0=0] THEN SET B13;
EXEC MRSTA1(Res_ssta;Cha_cnc0;B13=>)
OFB: I/O PARAMETERS
Res_ssta
Cha_cnc0
B13
RESET : bit
CHANNEL : word
UNSOL : bit
MRSTA1
ERROR : bit
MCNCT0,STATE
B8
MCNCT0,CHANNEL
: Ste_cnc0
: Res_ssta
: Cha_cnc0
<display status (STATUS —>Physic ) remote device
! (MRSTA1,PHYSIC)->Physic;Physic,0->O3,1
W21 : Physical status remote device
<increment W120 for read from R6S1
! INC DW_120
W120 : DW_120 variable read by R6S1
___________________________________________________________________________
1 / 7
H
1.2-3 OSI Adresses, TSX ETH 200 Module
Network layer
_____________________________________________________________________
Values
CONFIGURATION TIMER (S)
NPDU LIFETIME (500 MS)
20
3
4954454C454D4543412E060001
Transport layer
_____________________________________________________________________
Values
RETRY TIMER (MS)
MAX RETRIES
WINDOW INFO TIMER (MS)
MAX CREDIT
2000
3
2000
1
0001
Session layer
_____________________________________________________________________
Values
DISCONNECT TIME OUT (S) 60
0001
Application layer
_____________________________________________________________________
Values
APPLICATION NAME
AP TITLE (H)
AE QUALIFIER (H)
R6S0_MMS
00000001
MMS ASSOCIATIONS OPEN
MMS ASSOCIATIONS ACCEPTED
: 16
: 16
H
___________________________________________________________________________
1 / 8
Application Example 1
Remote applications
_________________________________________________________________
APPLICATION NAME
AP TITLE
AE QUALIFIER
PSEL
SSEL
TSEL
:
:
: R6S1_MMS
: 00000001
: 0001
: 0001
: 4954454C454D4543412E060101
1.2-4 PL7-3 Constants
CW0 -> CW31 Application constant NB CW CONFIG. : 100
_______________________________________________________________
Constant Value
CW0 =8
CW5 =0
CW6 =0
CW7 =0
CW8 =0
CW9 =0
CW10 =0
CW11 =1
CW12 =3
CW13 =4
CW14 =0
CW15 =2
CW16 =0
CW17 =0
CW19 =0
CW20 =0
CW21 =0
CW22 =0
CW23 =0
CW24 =0
CW25 =0
CW26 =0
CW27 =0
CW28 =0
CW29 =0
CW30 =0
CW31 =0
CW1 = R6S1_MMS
___________________________________________________________________________
1 / 9
H
1.2-5 List of MMS Variables
List of Local MMS variables
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: W50
: MT5_W50
: VMD
: AR-INT16 5
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Domain Name
Type
: W120
: MD_W120
: DOMAIN
: MMS
: AR-INT16 500
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Appli_Name
Type
: B50
: MABIT_50
: AA
: R6S1_MMS
: BOOL
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Appli_Name
Type
: DW200
: MADW_200
: AA
: R6S1_MMS
: AR-INT32 5
________________________________________________________________
H
___________________________________________________________________________
1 / 1 0
Application Example 1
List of remote MMS variables
________________________________________________________________
MMS Var
Scope
Type
Alias
PL7_3 Object
MMS Var Rank
: MBIT_B10
: VMD
: BOOL
: Bit_b10
: CW10
: 0
________________________________________________________________
MMS Var
Scope
Type
Alias
PL7_3 Object
MMS Var Rank
: MMOT_W100
: VMD
: INT16
: Mot_w100
: CW11
: 1
________________________________________________________________
MMS Var
Scope
Type
Alias
PL7_3 Object
MMS Var Rank
: MT250_DW1000
: VMD
: AR-UINT32 250
: T250_dw
: CW15
: 2
________________________________________________________________
MMS Var
Scope
Type
Alias
PL7_3 Object
MMS Var Rank
: MUMOT_W15
: VMD
: INT16
: Umot_w15
: CW12
: 3
________________________________________________________________
MMS Var
Scope
: VOITURE
: VMD
Type : STRUCT
Structure Description {
+0 INT16
+1 VSTR 10
+6 BOOL
}
Total size
Alias
PL7_3 Object
MMS Var Rank
: 7
: Voit
: CW13
: 4
________________________________________________________________
___________________________________________________________________________
1 / 1 1
H
1.2-6 List of PL7-3 Symbols
Variable Symbol
B6
B7
B8
B9
B0
B3
B4
B5
B50
CW0
CW10
CW11
CW12
CW13
CW15
DW200
W1
W2
W10
W11
W20
W21
W50
W100
DW1000
MCNCT0,IND
Res_tdw
Ind_cnc0
MCNCT0,CHANNEL Cha_cnc0
MCNCT0,INHIB Inh_cnc0
MCNCT0,READY
MCNCT0,STATE
MCNCT0,STATUS
W0
Rea_cnc0
Ste_cnc0
Sts_cnc0
Com_cnc0
W110
W120
W122
W1000
Mod_cnc0
Tim_cnc0
Val_b10
Res_b10
Res_uw15
Physic
T5_w50
Val_w100
Res_w100
Dmot_120
Res_voit
Res_dw
Res_cnc0
Err_cnc0
Res_wri0
Res_rea0
Res_urc0
Res_urc1
Res_ssta
Seconde
Abit_50
R6s1
Bit_b10
Mot_w100
Umot_w15
Voit
T250_dw
Atdw_200
Display Comment spec. AA variable read by R6S1 remote application (R6S1) remote variable (R6S1) remote variable (R6S1) remote variable (R6S1) remote variable (R6S1) remote variable (R6S1) spec. AA variable read by R6S1 result read from R6S1 value to write to R6S1 result read from R6S1 resultat reception info report physical status of remote device variable written and read by R6S1 value to write to remote w100 result read W100 from R6S1 variable read by R6S1 result read structure from R6S1 result read 250 dw from R6S1
H
___________________________________________________________________________
1 / 1 2
Application Example 1
1.3
R6S1 Device Application
1.3-1 Hardware Configuration
Rack reference: TSX RKN 82F
_____________________________________________________________________
RACK
0/1
S
U
P
7
0
6
7
/
4
5
5
D
E
T
1
6
D
S
T
1
6
E
T
H
2
0
0
1 3
5
PS M 0 1 2 3 4 5 6 7
1.3-2 Master Task Program, Main Program Module: MAST/MAIN
<accept association C0 opened by R6S0
! IF RE(I2,0) THEN EXEC MCNCT0(Res_cnc0;1;7;R6s0;500=>Err_cnc0)
OFB: I/O PARAMETERS
Res_cnc0
1
7
R6s0
500
MCNCT0
RESET : bit
COMMAND : word
MODULE : word
APPLI : pt_w
TIMEOUT : word
ERROR : bit Err_CNC0
B0
CW0
B1
: Res_cnc0 reset ofb
: R6s0 remote application (R6S0)
: Err_cnc0
<if association C0 open, O3,0 blinks
! IF [MCNCT0,STATE=0] THEN SY6->O3,0
<send (info rep.) to R6S0 (C0) word w15 every second (after ACCEPT)
! IF I2,1.MUSND0,READY.SY6.[MCNCT0,STATE=0]
THEN INC W15;EXEC MUSND0(B6;MCNCT0,CHANNEL;;W15;;1;;;;;;;;;;;;=>)
___________________________________________________________________________
1 / 1 3
H
B6
MCNCT0,CHANNEL
W15
1
OFB: I/O PARAMETERS
MUSND0
RESET : bit
CHANNEL : word
VAR0_B : pt_b
VAR0_W : pt_w
VAR0_DW : pt_d
NBELT0 : word
VAR1_B : pt_b
VAR1_W : pt_w
VAR1_DW : pt_d
NBELT1 : word
VAR2_B : pt_b
VAR2_W: pt_W
VAR2_DW : pt_d
NBELT2: word
VAR3_B: pt_b
VAR3_W: pt_w
VAR3_DW: pt_d
NELBELT3: word
ERROR : bit
W15
B6
: Umot_w15 word sent by unsolicited /sec
: Res_snd0 reset ofb
<send (info rep.) to R6S0 (C0) bit B10 every second (after ACCEPT)
! IF I2,2.MUSND1,READY.NOT SY6.[MCNCT0,STATE=0]
THEN SY5->B10;EXEC MUSND1(B6;MCNCT0,CHANNEL;B10;;;1;;;;;;;;;;;;=>)
B6
MCNCT0,CHANNEL
B10
1
OFB: I/O PARAMETERS
MUSND1
RESET : bit
CHANNEL : word
VAR0_B : pt_b
VAR0_W : pt_w
VAR0_DW : pt_d
NBELT0 : word
VAR1_B : pt_b
VAR1_W : pt_w
VAR1_DW : pt_d
NBELT1 : word
VAR2_B : pt_b
VAR2_W: pt_W
VAR2_DW : pt_d
NBELT2: word
VAR3_B: pt_b
VAR3_W: pt_w
VAR3_DW: pt_d
NELBELT3: word
ERROR : bit
H
B10 : Bit_b10
B6 : Res_snd0 reset ofb
___________________________________________________________________________
1 / 1 4
Application Example 1
<send UNSOL. STATUS to R6S0(C0) and monitor /10 cycles (after ACCEPT)
! IF I2,3.MSSTA0,READY.[MCNCT0,STATE=0]
THEN EXEC MSSTA0(Res_sta0;MCNCT0,CHANNEL;10=>)
Res sta0
MCNCT0,CHANNEL
10
OFB: I/O PARAMETERS
RESET : bit
CHANNEL : word
TCYCLE : word
MSSTA0
ERROR : bit
B7 : Res_sta0 reset ofb
<initialize variables to INITIATE association C1
! IF RE(I2,4) THEN 0->Com_cnc1
W1 : Com_cnc1
<initialize variable for CONCLUDE C1
! IF RE(I2,6) THEN 2->Com_cnc1
W1 : Com_cnc1
<initialize variable for ABORT C1
! IF RE(I2,7) THEN 3->Com_cnc1
W1 : Com_cnc1
<manage association C1 to R6S0
! IF RE(I2,4)+RE(I2,6)+RE(I2,7) THEN
EXEC MCNCT1(Res_cnc1;Com_cnc1;7;R6s0;500=>Err_cnc1)
Res_cnc1
Com_cnc1
7
R6s0
500
OFB: I/O PARAMETERS
MCNCT1
RESET : bit
COMMAND : word
MODULE : word
APPLI : pt_w
TIMEOUT : word
ERROR : bit Err_CNC1
B8
W1
CW0
B9
: Res_cnc1 reset ofb
: Com_cnc1
: R6s0 remote application (R6S0)
: Err_cnc1
<display status association C1
! MCNCT1,STATE->O3,C[4]
<if association C1 open o3,1 blinks
! IF [MCNCT1,STATE=0] THEN SY6->O3,1
___________________________________________________________________________
1 / 1 5
H
<display MWRIT0
! MWRIT0,READY.NOT MWRIT0,ERROR->O3,4
<write a table of 5 W in R6S0 (C1) and count
! IF I2,8.MWRIT0,READY.[MCNCT1,STATE=0]
THEN INC Val_w50;EXEC MWRIT0(Res_rea0;MCNCT1,CHANNEL;T5_w50;10;Val_w50;;;;;;;;;=>);
INC W4
OFB: I/O PARAMETERS
Res_read
MCNCT1,CHANNEL
T5_W50
10
VAL_w50
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
MWRIT0
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
W60
B11
CW10
: Val_w50 values to write to R6S0
: Res_rea0 reset ofb
: T5_w50 remote variable (R6S0)
<display MREAD1
! MREAD1,READY.NOT MREAD1,ERROR->O3,8
<read a table of 500 W specific MMS domain in R6S0 (C1) and count
! IF I2,A.MREAD1,READY.[MCNCT1,STATE=0]
THEN EXEC MREAD1(B12;MCNCT1,CHANNEL;Dmot_120;1000;Res_d120;;;;;;;;;=>);
INC W6
H
___________________________________________________________________________
1 / 1 6
Application Example 1
B12
MCNCT1,CHANNEL
Dmot_120
1000
Res_d120
OFB: I/O PARAMETERS
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
MREAD1
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
CW31
W120
: Dmot_120 remote variable (R6S0)
: Res_d120 result read from R6S0
<display MREAD0
! MREAD0,READY.NOT MREAD0,ERROR->O3,7
<read tab 5 W + 1 BIT + tab 5 DW AA spec. from R6S0(C1)and count
! IF I2,9.MREAD0,READY.[MCNCT1,STATE=0]
THEN EXEC MREAD0(B12;MCNCT1,CHANNEL;CW10;10;W70;CW29;2;W110;CW30;20;W30;;;=>);
INC W5
OFB: I/O PARAMETERS
B12
MCNCT1,CHANNEL
CW10
10
W70
CW29
2
W110
CW30
20
W30
MREAD0
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
CW10
W70
CW29
W110
CW30
: T5_w50 remote variable (R6S0)
: Res_w50 result read from R6S0
: Abit_50 remote variable (R6S0)
: Res_ab50 result read from R6S0
: Atdw_200 remote variable (R6S0)
___________________________________________________________________________
1 / 1 7
H
<open association C2 with APRIL
! IF RE(I2,F) THEN EXEC MCNCT2(B12;0;7;April_s;500=>)
B12
0
7
April_s
500
OFB: I/O PARAMETERS
MCNCT2
RESET : bit
COMMAND : word
MODULE : word
APPLI : pt_w
TIMEOUT : word
ERROR : bit
CW20 : April_s remote application (APRIL)
<send (info report) to APRIL (C2) w15 every second
! IF I2,B.MUSND1,READY.SY6.[MCNCT2,STATE=0]
THEN INC W15;EXEC MUSND1(B6;MCNCT2,CHANNEL;;W15;;1;;;;;;;;;;;;=>)
OFB: I/O PARAMETERS
B6
MCNCT0,CHANNEL
W15
1
RESET : bit
CHANNEL : word
VAR0_B : pt_b
VAR0_W : pt_w
VAR0_DW : pt_d
MUSND1
NBELT0 : word
VAR1_B : pt_b
VAR1_W : pt_w
VAR1_DW : pt_d
NBELT1 : word
VAR2_B : pt_b
VAR2_W: pt_W
VAR2_DW : pt_d
NBELT2: word
VAR3_B: pt_b
VAR3_W: pt_w
VAR3_DW: pt_d
NELBELT3: word
ERROR : bit
W15
B6
: Umot_w15 word sent by unsolicited /sec
: Res_snd0 reset ofb
H
___________________________________________________________________________
1 / 1 8
Application Example 1
<accept on association C3 opened by APRIL
! IF RE(I2,E) THEN EXEC MCNCT3(B12;1;7;April_c;500=>B13)
B12
1
7
April_c
500
OFB: I/O PARAMETERS
MCNCT3
RESET : bit
COMMAND : word
MODULE : word
APPLI : pt_w
TIMEOUT : word
ERROR : bit B13
CW40 : April_c remote application (APRIL)
<display MREAD2
! MREAD2,READY.NOT MREAD2,ERROR->O3,5
<read bit %MX28 from APRIL (C3) and count (after ACCEPT)
! IF I2,D.MREAD2,READY.[MCNCT3,STATE=0]
THEN EXEC MREAD2(B12;MCNCT3,CHANNEL;Mx28;2;Res_apri;;;;;;;;;=>);
INC W3
OFB: I/O PARAMETERS
B12
MCNCT3,CHANNEL
Mx28
2
Res_april
MREAD2
RESET : bit
CHANNEL : word
VAR0 : word
SIZE0 : word
DATA0 : pt_w
VAR1 : word
SIZE1 : word
DATA1 : pt_w
VAR2 : word
SIZE2 : word
DATA2 : pt_w
VAR3 : word
SIZE3 : word
DATA3: pt_w
ERROR : bit
CW33
W115
: Mx28 remote variable (APRIL 7000)
: Res_apri result read run bit (APRIL)
<animation variable read by R6S0
! INC W600;INC W1000
<animation variable read by R6S0
! INC Voit
W122 : Voit structure read by R6S0
___________________________________________________________________________
1 / 1 9
H
1.3-3 OSI Addresses, TSX ETH 200 Module
Network layer
____________________________________________________________________
Values
CONFIGURATION TIMER (S)
NPDU LIFETIME (500 MS)
20
3
4954454C454D4543412E060101
Transport layer
___________________________________________________________
Parameters Values
RETRY TIMER (MS)
MAX RETRIES
WINDOW INFO TIMER (MS)
MAX CREDIT
2000
3
2000
1
0001
Session layer
____________________________________________________________________
Values
DISCONNECT TIME OUT (S) 60
0001
Application layer
____________________________________________________________________
Values
APPLICATION NAME
AP TITLE (H)
AE QUALIFIER (H)
MAX CREDIT
R6S1_MMS
2000
1
00000001
MMS ASSOCIATIONS OPEN : 16
MMS ASSOCIATIONS ACCEPTED : 16
H
___________________________________________________________________________
1 / 2 0
Application Example 1
Remote applications
_________________________________________________________________
APPLICATION NAME : R6S0_MMS
AP TITLE :
AE QUALIFIER
PSEL
:
: 00000001
SSEL
TSEL
: 0001
: 0001
: 4954454C454D4543412E060001
APPLICATION NAME : APRIL_S1S
AP TITLE :
AE QUALIFIER
PSEL
:
: 00000002
SSEL
TSEL
: 0000
: 0101
: 49415052494C00000000EDA0011501
APPLICATION NAME : APRIL_S1C
AP TITLE :
AE QUALIFIER
PSEL
:
: 00000001
SSEL
TSEL
: 0000
: 0101
: 49415052494C00000000EDA0011501
___________________________________________________________________________
1 / 2 1
H
1.3-4 PL7-3 Constants
CW0 -> CW49 application constants NB CW CONFIG.: 128
_______________________________________________________________
Constant Value
CW0 =8
CW5 =0
CW6 =0
CW7 =0
CW8 =0
CW9 =0
CW10 =5
CW11 =0
CW12 =0
CW13 =0
CW14 =0
CW15 =0
CW16 =0
CW17 =0
CW18 =0
CW19 =0
CW20 =9
CW27 =0
CW28 =0
CW29 =0
CW30 =1
CW31 =2
CW32 =2
CW33 =4
CW34 =5
CW35 =3
CW36 =0
CW37 =0
CW38 =0
CW39 =0
CW40 =9
CW46 =0
CW47 =0
CW48 =0
CW49 =0
CW1 = R6S0_MMS
CW21 = APRIL_S1S
CW41 = APRIL_S1C
H
1.3-5 List of MMS Variables
List of local MMS variables
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
:
: M DAYTIME
: VND
: GENERALIZED_TIME
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: W50
: MT5_W50
: VMD
: AR-INT16 5
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: B10
: MBIT_B10
: VMD
: BOOL
1 / 2 2
Application Example 1
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: W100
: MMOT_100
: VMD
: INT16
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: DW1000
: MT 250_DW1000
: VMD
: AR-UINT32 250
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: W200
: MT 500W
: VMD
: AR-INT16 500
________________________________________________________________
PL7_3 Object
MMS_Name
: W15
: MUMOT_15
Scope : VMD
Type : INIT16
________________________________________________________________
PL7_3 Object
MMS_Name
Scope
Type
: W900
: VOITURE
: VMD
: STRUCT
Structure description {
+0 INIT16 NB GATE
+1 VSTR 10 COLOR
+6 BOOL RADIO
Total size
}
: 7
________________________________________________________
PL7_3 Object
MMS_Name
: W910
: VSTRING
Scope
Type
: VMD
: VSTR 20
_ ______________________________________________________________
___________________________________________________________________________
1 / 2 3
H
List of remote MMS variables
___________________________________________________
MMS Var : MABIT_50
Appli_Name
Scope
Type
: R6S1_MMS
: AA
: BOOL
Alias
PL7_3
MMS Var Rank
: Abit_50
: CW29
: 0
_________________________________________________________
MMS Var
Appli_Name
: MADW_200
: R6S1_MMS
Scope
Type
Alias
: AA
: AR-INT32 5
: Atdw_200
PL7_3 Object : CW30
MMS Var Rank : 1
_________________________________________________________
MMS Var
Scope
Domain Name
Type
Alias
PL7_3 Object
: MD_W120
: DOMAIN
: MMS
: AR-INT16 500
: Dmot_120
: CW31
MMS Var Rank : 2
_________________________________________________________
MMS Var : MT250_DW1000
Scope
Type
Alias
: VMD
: AR-UINT32 250
: Mtdw1000
PL7_3 Object : CW35
MMS Var Rank : 3
_________________________________________________________
MMS Var
Scope
Type
: RUN_API
: VMD
: BSTR 1
Alias
PL7_3 Object
MMS Var Rank
: Mx28
: CW33
: 4
_________________________________________________________
MMS Var
Scope
: MT5_W50
: VMD
Type
Alias
PL7_3 Object
: AR-INT16 5
: T5_w50
: CW10
MMS Var Rank : 5
___________________________________________________
H
___________________________________________________________________________
1 / 2 4
Application Example 1
1.3-6 List of PL7-3 Symbols
Variable
CW40
DW30
W0
W1
W15
W50
W60
W70
W100
W110
W115
W120
W200
W122
W900
W910
DW1000
CW0
CW10
CW20
CW29
CW30
CW31
CW33
CW35
B0
B1
B6
B7
B8
B9
B10
B11
Symbol
April_c
Res_adw
Com_cnc0
Com_cnc1
Umot_w15
At5_w50
Val_w50
Res_w50
Mot_w100
Res_ab50
Res_apri
Res_d120
T_500w
Voit
Us_w900
Vstring
T250_dw
Res_cnc0
Err_cnc0
Res_snd0
Res_sta0
Res_cnc1
Err_cnc1
Bit_b10
Res_rea0
R6s0
T5_w50
April_s
Abit_50
Atdw_200
Dmot_120
Mx28
Mtdw1000
Display Comment reset ofb reset ofb reset ofb reset ofb reset ofb remote application (R6S0) remote variable (R6S0) remote application (APRIL) remote variable (R6S0) remote variable (R6S0) remote variable (R6S0) remote variable (APRIL 7000) remote variable (R6S0) remote application (APRIL) result read from R6S0 word sent by unsolicited /sec table 5 W written & read by april values to write to R6S0 result read from R6S0 word written and read by R6S0 result read from R6S0 result read run bit (APRIL) result read from R6S0 table of 500 W read by APRIL structure read by R6S0 visible string 20 read by APRIL tab DW1000->DW1250 rd. by R6S0
___________________________________________________________________________
1 / 2 5
H
H
___________________________________________________________________________
1 / 2 6