Swegon REACT ALS, REACT Parasol Zenith, REACT M, REACT P, REACT P-X, REACT V Description of Wiring Diagram
Annons
Annons
REACT
Description of functions & wiring diagrams
20221025
Document version: 3
Content
Air flow control with temperature and CO
Air flow control with temperature, CO
Air flow control with temperature and CO
function via external occupancy detector ................................................. 9
Air flow control with temperature and CO
controller for demand control .................................................................. 13
Parallel controlled air flow control with temperature and CO
function ....................................................................... 21
Parallel controlled air flow control with temperature, CO
and occupancy function ..................................................... 22
Parallel controlled air flow control with temperature and CO
function via external occupancy detector ...................... 23
Balanced air flow control with temperature and CO
function .................................................................................... 31
Balanced air flow control with temperature, CO
and occupancy function .................................................................. 32
Balanced air flow control with temperature and CO
function via external occupancy detector .................................... 33
REACT Description of functions & wiring diagrams
2 Swegon reserves the right to alter specifications. 20221025
Description of products
REACT
ALS
Commissioning box with variable flow regulation for air diffusers.
REACT Description of functions & wiring diagrams
REACT
Parasol Zenith
Comfort module with integrated, pressure-independent
VAV control.
REACT
M
Stand-alone measurement unit for measuring air flow.
REACT
V
(-SR spring return)
Damper for variable or constant flow regulation.
REACT
P
Damper for pressure regulation.
REACT
P-X
(-SR spring return)
Damper for pressure regulation.
Room accessories
DETECT
IAQ
Carbon dioxide and temperature controller.
DETECT
IAQ OCS
Carbon dioxide and temperature controller that also detects occupancy.
DETECT
IAQ D
Carbon dioxide and temperature controller for duct installation.
DETECT
Occupancy
Electronic occupancy detector.
LUNA
RC
Room controller for temperature control with display.
LUNA
RC CO
2
Room controller for temperature control with
CO
2
sensor and display.
LUNA
RE
Room controller for temperature regulation.
20221025 Swegon reserves the right to alter specifications.
3
REACT Description of functions & wiring diagrams
Constant flow regulation
Air flow measurement and damper regulation to maintain the set air flow.
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Constant flow
Vmax : 0 l/s
Indicates “Test” on the display.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Notes
4 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the control signal.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
5
REACT Description of functions & wiring diagrams
Two-flow control with occupancy detector
Air flow measurement and regulating damper that controls the air flow on the set position. The damper switches via occupancy detection between two fixed flows.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Unoccupied flow
Vmax : Occupancy flow
The damper will indicate “Test” on the display when boosting (occupancy) to show it is manually boosted.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Notes
6 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control with temperature and CO
2
function
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT IAQ, DETECT IAQ D
(Temperature and CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
5
Y4
Out Modbus
6
A
(+)
B
(-)
Notes
20221025 Swegon reserves the right to alter specifications.
7
REACT Description of functions & wiring diagrams
Air flow control with temperature, CO
2
and occupancy function
Air flow measurement and regulating damper that variably controls the air flow between the minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. Occupancy is detected via occupancy detectors. The damper is regulated to minimum flow rate in no-occupancy mode.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT IAQ OCS
(Temperature and CO
2
with occupancy function)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
5
Y4
Out Modbus
6
A
(+)
B
(-)
Notes
8 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control with temperature and CO
2
external occupancy detector
function via
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. Occupancy is detected in the room via the occupancy detector. The damper is regulated to minimum flow rate in no-occupancy mode.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Settings for the on and off delay are made on the occupancy detector.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
DETECT IAQ, DETECT IAQ D
(Temperature and CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
Y4
Out
Modbus
5 6
A
(+)
B
(-)
Notes
20221025 Swegon reserves the right to alter specifications.
9
REACT Description of functions & wiring diagrams
Air flow control with temperature regulator for demand control
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function) depending on the temperature set point. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
LUNA RE
(Temperature regulator)
Cool
G0
24V Heat
G G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
RTCT
Notes
10 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control with temperature controller for demand control
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function). Control of thermo-actuators for cooling/heating.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Potential to connect condensation sensor.
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
LUNA RC/ LUNA RC CO
2
(Room regulator)
24V
AC/DC
0
Vac
0-10V
VAV
0-10V
Fan
G0
Day/ night
Cool Cool
0-10V
Heat Heat
0-10V
CO
2 ext sp
G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1
A
(+)
Modbus
B
(-)
C
Sensor
NTC10
DI2 G0
Notes
20221025 Swegon reserves the right to alter specifications.
11
REACT Description of functions & wiring diagrams
Air flow control with temperature controller for demand control
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function). Control of thermo-actuators for cooling/heating.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Potential to connect condensation sensor.
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT Parasol Zenith
~
(-) (+)
Y
1 2 3
U
5
Bus
C1
Bus
C2
6 7
U
Y
24 V AC/DC
Modbus
LUNA RC
(Room regulator)
24V
AC/DC
0
Vac
0-10V
VAV
0-10V
Fan
G0
Day/ night
Cool Cool
0-10V
Heat Heat
0-10V
CO
2 ext sp
G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1
A
(+)
Modbus
B
(-)
C
Sensor
NTC10
DI2 G0
Notes
12 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control with temperature and CO
2
demand control
controller for
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function). Control of thermo-actuators for cooling/heating.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Potential to connect condensation sensor.
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT Parasol Zenith
~
(-) (+)
Y
1 2 3
U
5
Bus
C1
Bus
C2
6 7
U
Y
24 V AC/DC
Modbus
LUNA RC CO
2
(Room regulator)
24V
AC/DC
0
Vac
0-10V
VAV
0-10V
Fan
G0
Day/ night
Cool Cool
0-10V
Heat Heat
0-10V
CO
2 ext sp
G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1
A
(+)
Modbus
B
(-)
C
Sensor
NTC10
DI2 G0
Notes
20221025 Swegon reserves the right to alter specifications.
13
REACT Description of functions & wiring diagrams
Air flow control with controller for demand control
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the control signal.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y
3
U
4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Controller for demand control
(Room controller/DUC)
Y
~
(-) (+) Modbus
A
(-)
B
(+)
Notes
14 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control with temperature regulator for demand control and occupancy function
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function) depending on the temperature set point in occupancy mode. The room is regulated to minimum flow rate in no-occupancy mode. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
RTCT
Notes
20221025 Swegon reserves the right to alter specifications.
15
REACT Description of functions & wiring diagrams
Air flow control with controller for demand control and occupancy function
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the control signal in occupancy mode. The room is regulated to minimum flow rate in no-occupancy mode.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Settings for the on and off delay are made on the occupancy detector.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Controller for demand control
(Room controller/DUC)
Y
~
(-) (+) Modbus
A
(-)
B
(+)
Notes
16 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow control with temperature controller for demand control and absence control
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function) depending on the temperature set point in occupancy mode. The room is set to absence temperature set point in no-occupancy mode. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Notes
20221025 Swegon reserves the right to alter specifications.
17
REACT Description of functions & wiring diagrams
Air flow control with demand control via Modbus communication
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate.
Demand control via Modbus communication.
Possibility of Modbus control/communication only or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Modbus
Set point function (Address 122) : 1 or 2
Set point (Address 0) : 0 = 0%, 10,000 = 100%
For further information, see the Modbus document for REACT.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Communication for demand control
Modbus
A
(-)
B
(+)
Notes
18 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Parallel controlled air flow control
Air flow measurement and regulating damper that variably controls the air flow in parallel between minimum and maximum flow rate depending on the control signal.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
(-)
1
~
(+)
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
19
REACT Description of functions & wiring diagrams
Parallel controlled two-flow control with occupancy detector
Air flow measurement and regulating damper that controls the air flow on the set position. The dampers switch via occupancy detection between two fixed flows.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Unoccupied flow
Vmax : Occupancy flow
The dampers will indicate “Test” on the display when boosting (occupancy) to show they are manually boosted.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Notes
20 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with temperature and
CO
2
function
Air flow measurement and regulating damper that variably control the air flow in parallel between minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
Y
DETECT IAQ, DETECT IAQ D
(Temperature and CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
5
Y4
Out
Modbus
6
A
(+)
B
(-)
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
21
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with temperature, CO
2
and occupancy function
Air flow measurement and regulating damper that variably control the air flow in parallel between minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. Occupancy is detected in the room via the occupancy detector. The damper is regulated to minimum flow rate in no-occupancy mode.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Settings for the on and off delay are made on the occupancy detector.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
DETECT IAQ OCS
(Temperature and CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
5
Y4
Out
Modbus
6
A
(+)
B
(-)
24 V AC/DC
Modbus
Notes
22 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with temperature and
CO
2
function via external occupancy detector
Air flow measurement and regulating damper that variably control the air flow in parallel between the minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. Occupancy is detected in the room via the occupancy detector. The damper is regulated to minimum flow rate in no-occupancy mode.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Settings for the on and off delay are made on the occupancy detector.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
DETECT IAQ, DETECT IAQ D
(Temperature and CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
Y4
Out
5 6
Modbus
A
(+)
B
(-)
Notes
20221025 Swegon reserves the right to alter specifications.
23
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with temperature regulator for demand control
Air flow measurement and regulating damper that variably controls the air flow in parallel between the set minimum and maximum flow rate (cooling function) depending on the temperature set point. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
RTCT
Notes
24 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with controller for demand control
Air flow measurement and regulating damper that variably controls the air flow in parallel between minimum and maximum flow rate depending on the control signal.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Controller for demand control
(Room controller/DUC)
Y
~
(-) (+) Modbus
A
(-)
B
(+)
Notes
20221025 Swegon reserves the right to alter specifications.
25
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with temperature regulator for demand control and occupancy function
Air flow measurement and regulating damper that variably controls the air flow in parallel between the set minimum and maximum flow rate (cooling function) depending on the temperature set point in occupancy mode. The room is regulated to minimum flow rate in no-occupancy mode. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
RTCT
Notes
26 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with controller for demand control and occupancy function
Air flow measurement and regulating damper that variably controls the air flow in parallel between minimum and maximum flow rate depending on the control signal in occupancy mode. The room is regulated to minimum flow rate in no-occupancy mode.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Settings for the on and off delay are made on the occupancy detector.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Controller for demand control
(Room controller/DUC)
Y
~
(-) (+) Modbus
A
(-)
B
(+)
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
27
REACT Description of functions & wiring diagrams
Parallel controlled air flow control with temperature controller for demand control and absence control
Air flow measurement and regulating damper that variably controls the air flow in parallel between the set minimum and maximum flow rate (cooling function) depending on the temperature set point in occupancy mode. The room is set to absence temperature set point in no-occupancy mode. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
Y
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
24 V AC/DC
Modbus
Notes
28 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Balanced air flow control
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the control signal. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
29
REACT Description of functions & wiring diagrams
Balanced two-flow control with occupancy detector
Air flow measurement and regulating damper that controls the air flow on the set position. The damper switches via occupancy detection between two fixed flows. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Notes
30 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Balanced air flow control with temperature and CO
2
function
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
DETECT IAQ, DETECT IAQ D
(Temperatur och CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
Y4
Out
Modbus
5 6
A
(+)
B
(-)
Notes
20221025 Swegon reserves the right to alter specifications.
31
REACT Description of functions & wiring diagrams
Balanced air flow control with temperature, CO
2
occupancy function
and
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. Occupancy is detected in the room via the occupancy detector. The damper is regulated to minimum flow rate in no-occupancy mode. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U Modbus
3 4
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
DETECT IAQ OCS
(Temperature and CO
²
with occupancy function)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
5
Y4
Out
Modbus
6
A
(+)
B
(-)
Notes
32 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Balanced air flow control with temperature and CO
2
via external occupancy detector
function
Air flow measurement and regulating damper that variably controls the air flow between the minimum and maximum flow rate depending on the current temperature and the CO
2
content in the room. Occupancy is detected in the room via the occupancy detector. The damper is regulated to minimum flow rate in no-occupancy mode. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
DETECT IAQ, DETECT IAQ D
(Temperature and CO
2
)
+/ ~
G+ G0
Y1
CO 2
Y2
ºC
1 2 3 4
Y3
Y4
Out
Modbus
5 6
A
(+)
B
(-)
Notes
20221025 Swegon reserves the right to alter specifications.
33
REACT Description of functions & wiring diagrams
Balanced air flow control with temperature controller for demand control
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function) depending on the temperature set point. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room. The wiring diagram also shows the alternative with
RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
RTCT
Notes
34 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Balanced air flow control with controller for demand control
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the control signal. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
Controller for demand control
(Room controller/DUC)
Y
~
(-) (+) Modbus
A
(-)
B
(+)
Notes
20221025 Swegon reserves the right to alter specifications.
35
REACT Description of functions & wiring diagrams
Balanced air flow control with temperature regulator for demand control and occupancy function
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function) depending on the temperature set point in occupancy mode. The room is regulated to minimum flow rate in no-occupancy mode. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
LUNA RE
(Temperature regulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
RTCT
Notes
36 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Balanced air flow control with controller for demand control and occupancy function
Air flow measurement and regulating damper that variably controls the air flow between minimum and maximum flow rate depending on the control signal in occupancy mode. The room is regulated to minimum flow rate in no-occupancy mode. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room.
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0 (2)-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
DETECT O
(Occupancy detector)
NC C NO 24 ~
1 2 3 4 5
Controller for demand control
(Room controller/DUC)
Y
~
(-) (+) Modbus
A
(-)
B
(+)
Notes
20221025 Swegon reserves the right to alter specifications.
37
REACT Description of functions & wiring diagrams
Balanced air flow control with temperature controller for demand control and absence control
Air flow measurement and regulating damper that variably controls the air flow between the set minimum and maximum flow rate (cooling function) depending on the temperature set point in occupancy mode. The room is set to absence set point in no-occupancy mode. The air flow value from the master damper is sent analogously to the slave damper to maintain the balance in the room. The wiring diagram also shows the alternative with RTCT duct temperature sensor and thermo-actuator (heating function).
Demand control via analogue control signal (Y). Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Minimum flow rate
Vmax : Maximum flow rate
Mode : 0-10 V
Slave
Vmin : 0
Vmax : Vnom on Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT V
REACT V-SR
REACT ALS
Master
1
~
2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
LUNA RE
(Temperaturregulator)
Cool
G0
24V
G
Heat
G0
Cool
0-10V
1 2 3 4
~
(+) (-)
5 6
Heat
0-10V
Temp Cond Modbus
7 8 9
10
(+)
11
(-)
Ts
DETECT O
(Närvarogivare)
NC C NO 24 ~
1 2 3 4 5
Notes
38 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Measurement of air flow
Air flow measuring device that variably sends out the air flow value depending on minimum and maximum flow rate.
Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Wiring diagram
U
24 V AC/DC
Modbus
REACT M
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
Notes
20221025 Swegon reserves the right to alter specifications.
39
REACT Description of functions & wiring diagrams
Air flow measurement with slave-controlled air flow control in balance
The air flow value from the measuring unit is sent analogously to the slave damper depending on minimum and maximum flow rate to maintain the balance in the room.
Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Slave
Vmin : Same as Master
Vmax : Same as Master
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT M
Master
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
24 V AC/DC
Modbus
Notes
40 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Air flow measurement with slave-controlled air flow control with offset
The air flow value from the measuring unit is sent analogously to the slave damper depending on minimum and maximum flow rate to maintain the balance with regard to other air flow.
Return of the current air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Slave
Vmin : Same as Master ± offset
Vmax : Same as Master ± offset
Mode : Same as Master
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT M
Master
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
41
REACT Description of functions & wiring diagrams
Constant pressure regulation
Pressure measurement and regulating damper to maintain the set pressure.
Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Pmin : Constant pressure
Pmax : 0 Pa
Indicates “Test” on the display.
Wiring diagram
REACT P
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Notes
42 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Constant pressure regulation with external regulator
Pressure measurement and regulating damper with an external regulator to maintain the set pressure.
Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Pmin : Constant pressure
Pmax : 0 Pa
Indicates “Test” on the display.
Wiring diagram
227C / SR
1 2 3 4
REACT P-X
REACT P-X-SR
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
1 2 3 4
U
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
43
REACT Description of functions & wiring diagrams
Parallel controlled pressure regulation
Pressure measurement and regulating damper that variably regulates the duct pressure in parallel between minimum and maximum pressure depending on the control signal.
Demand control via analogue control signal (Y). Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
Wiring diagram
REACT P
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT P
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
Y
24 V AC/DC
Modbus
Notes
44 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Parallel controlled pressure regulation with external regulator
Pressure measurement and regulating damper with external regulator that variably regulate the duct pressure in parallel between minimum and maximum pressure depending on the control signal.
Demand control via analogue control signal (Y). Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
Wiring diagram
227C / SR
1 2 3 4
REACT P-X
REACT P-X-SR
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
1 2 3 4
U
227C / SR
1 2 3 4
REACT P-X
REACT P-X-SR
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
1 2 3 4
U
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
45
REACT Description of functions & wiring diagrams
Balanced pressure regulation
Pressure measurement and regulating damper that variably regulate the duct pressure between minimum and maximum pressure depending on the control signal. The actual pressure value from the master damper is sent analogously to the slave damper to maintain balance.
Demand control via analogue control signal (Y). Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
Slave
Pmin : 0
Pmax : 300
Mode : Same as Master
Wiring diagram
REACT P
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT P
Master
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
Notes
46 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Balanced pressure regulation with external regulator
Pressure measurement and regulating damper with external regulator that variably regulate the duct pressure between minimum and maximum pressure depending on the control signal. The actual pressure value from the master damper is sent analogously to the slave damper to maintain the balance.
Demand control via analogue control signal (Y). Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
Slave
Pmin : 0
Pmax : 300
Mode : Same as Master
Wiring diagram
227C / SR
1 2 3 4
REACT P-X
REACT P-X-SR
Slave
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
1 2 3 4
U
227C / SR
1 2 3 4
REACT P-X
REACT P-X-SR
Master
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
1 2 3 4
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
47
REACT Description of functions & wiring diagrams
Constant pressure regulation and air flow measurement with slave-controlled air flow control
REACT P measures and regulates to maintain the set air pressure. The air flow value from REACT M is sent analogously to the slave damper REACT V. Depending on minimum and maximum flow rate the air flow balance is maintained with or without offset.
Return of the current pressure/air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Slave
Vmin : Same as Master ± offset
Vmax : Same as Master ± offset
Mode : Same as Master
Pmin : Constant pressure
Pmax : 0 Pa
Indicates “Test” on the display.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT M
Master
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
REACT P
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
Notes
48 Swegon reserves the right to alter specifications. 20221025
REACT Description of functions & wiring diagrams
Constant pressure regulation with external regulator and air flow measurement with slave-controlled air flow control
REACT P-X measures and regulates with an external regulator to maintain the set pressure. The air flow value from
REACT M is sent analogously to the slave damper REACT V. Depending on minimum and maximum flow rate the air flow balance is maintained with or without offset.
Demand control via analogue control signal (Y). Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Slave
Vmin : Same as Master ± offset
Vmax : Same as Master ± offset
Mode : Same as Master
Pmin : Constant pressure
Pmax : 0 Pa
Indicates “Test” on the display.
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT M
Master
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
REACT P-X
REACT P-X-SR
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
227C / SR
1 2 3 4
1 2 3 4
U
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
49
REACT Description of functions & wiring diagrams
Pressure regulation and air flow measurement with slave- controlled air flow control
REACT P measures and regulates variably between minimum and maximum pressure depending on the control signal.
The air flow value from REACT M is sent analogously to the slave damper REACT V. Depending on minimum and maximum flow rate the air flow balance is maintained with or without offset.
Return of the current pressure/air flow via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Slave
Vmin : Same as Master ± offset
Vmax : Same as Master ± offset
Mode : Same as Master
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
1 2
Y U
3 4
Modbus
A
(-)
B
(+)
U
REACT M
Master
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
REACT P
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
Y
24 V AC/DC
Modbus
Notes
50 Swegon reserves the right to alter specifications. 20221025
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
REACT Description of functions & wiring diagrams
Pressure regulation with external regulator and air flow measurement with slave-controlled air flow control
REACT P-X measures and regulates with an external regulator variably between minimum and maximum pressure depending on the control signal. The air flow value from REACT M is sent analogously to the slave damper REACT V.
Depending on minimum and maximum flow rate the air flow balance is maintained with or without offset.
Demand control via analogue control signal (Y). Return of the current pressure via analogue actual value signal (U).
Possibility of Modbus control/communication or Modbus in combination with analogue signals.
Settings
Master
Vmin : Set value for min. actual value signal (0/2 V)
Vmax : Set value for max. actual value signal (10 V)
Mode : 0 (2)-10 V
Slave
Vmin : Same as Master ± offset
Vmax : Same as Master ± offset
Mode : Same as Master
Pmin : Minimum pressure
Pmax : Maximum pressure
Mode : 0 (2)-10 V
Wiring diagram
REACT V
REACT V-SR
REACT ALS
Slave
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
U
REACT M
Master
~
(-) (+)
1 2
U
4
Modbus
A
(-)
B
(+)
227C / SR
1 2 3 4
REACT P-X
REACT P-X-SR
~
(-) (+)
Y U
1 2 3 4
Modbus
A
(-)
B
(+)
1 2 3 4
U
Y
24 V AC/DC
Modbus
Notes
20221025 Swegon reserves the right to alter specifications.
51