Swegon REACT ALSa Instructions for use
Reklama
Reklama
REACT
ALSa
Instructions for Use
Key to symbols
Symbols on the machine
This product complies with applicable EU directives
Symbols in these Instructions for Use
04/01/2023
Art. 1546102
Other risk
When the product is voltage fed, the damper cone will either open or close. This can entail a certain risk for pinch injuries, for example, to the fingers if these are placed within the damper cone.
Warning/Caution!
Risk of crushing
Application area
The product is a commissioning box with variable flow regulation or constant flow regulation, designed for comfort ventilation indoors. The product is used to regulate the supply air flow in ventilation ducts.
The product may not be used for anything other than its intended use.
General
Read through the entire instructions for use before you install/use the product and save the instructions for future reference. It’s not permissible to make changes or modify this product other than those specified in this document.
The packaging contains the following items
1 x REACT ALS
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment for the work in question, in the form of gloves, respirators and protective glasses during handling, installation, cleaning and service/maintenance.
Electrical safety
Permitted voltage, see “Electrical data”. It is not permissible to insert foreign objects into the product’s contactor connections or the electronics's ventilation openings; risk for short circuiting.
24 V isolation transformer to be connected should comply with the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product and the power supply source.
Disconnect the power supply when working on the product and it is not required to be running.
Always follow the local/national rules for who shall be permitted to carry out this type of electrical installation.
Handling
• Always use appropriate transport and lifting devices when the product is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring tubes.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry regulations.
• Install the product so that it is not accessible by unauthorized persons, for example in a suspended ceiling.
• Install the product for easy access during service/maintenance.
• If the product is mounted in a fixed ceiling, the inspection hatch must be located so that the product is accessible for inspection.
• If the product is mounted in cold areas, the whole product must be insulated on the outside against condensation.
• The product must be installed horizontally.
• The product must be laid down prior to installation so that it cannot fall over.
• Check to make sure that the product doesn’t have any visible defects.
• Check that the product is properly secured after it has been installed.
• Check that all cables are properly secured in place after installation.
• If the product is mounted so that it is possible to gain access to the inside of the product, it must be supplemented with appropriate protection, for example, a ventilation unit.
• It is recommended to mount the product so that the associated diffuser face can be opened.
The document was originally written in Swedish
REACT ALS
Installation, dimensions and weights
Size
Min.
Max = Vnom *) l/s m 3 /h l/ s m 3 /h
160-250 7 25
250-315 20 72
110
330
396
1188
*) Vnom at 100 Pa in pressure reading.
* Installed according to the instructions
Tolerance Q* ±5% with at least ±x l/s
2
3
Installation
• The product’s air flow measurement requires a straight duct section as per the installation figures.
• In unfavourable conditions before or with disruption, the product’s tolerances cannot be guaranteed.
• Instructions for Use are supplied with the product on delivery, but can also be downloaded from www.
swegon.com.
1.
Size B
160-250 504
250-315 622
C
332
388
ØD
159
249
Ød
250
315
Weight (kg)
4.9
7.8
Size
160-250
250-315
E
199
300
F
239
340
G
140
190
H
445
575
K
100
140
2.
3.
*
Figure 1. Dimensions (mm).
4.
5.
Figure 2. Straight section requirements, circular ducts.
1-4: Quantity Ø before the product: 0 x Ø.
5: Quantity Ø before the product: 4 x Ø.
*Cleaning hatch
2
Swegon reserves the right to alter specifications. 04/01/2023
REACT ALS
Connection
1-2 – Supply voltage
1-3 – Control signal (Y)
1-4 – Actual value signal (U)
A-B – Modbus
24 V AC/DC
0..10/(2..10) V
0..10/(2..10) V
For further calculations of Y and U see the formulas on page 7.
Load on output 4: max. 0.5 mA
1 2 3 4 A B
5 Nm
3 W 5 VA
1000s (90°) 95°
2550 Pa max. 100 kPa
+
Y U
1 2 3 4
BK RD WH OG PK GY
+
Y U CA CB
+
0..10 V DC
(2..10 V DC) a. b. c. d. e.
N L
24 V AC/DC
-
Modbus
0..10 V DC
(2..10 V DC)
Figure 3. Wiring diagram.
Regulation and forced control via analogue control signal
See connection in the wiring diagram, Figure 3.
a. Open the damper: 24 VAC (L) via diode/rectifier
(positive half-wave) b. Regulate to set max. value: 24 VAC/DC (L) c. Regulate to set min. value: Mode = 0 – 10 V, no control signal d. Close the damper: 24 VAC/DC (N)
• Mode = 0 – 10 V, min. value = 0
• Mode = 2 – 10 V e. Regulate according to control signal 0-10 V / 2-10 V
• Mode = 0 – 10 V
0 V = min. value
10 V = max. value
• Mode = 2 – 10 V
0 V = close the damper
2 V = min. value
10 V = max. value
04/01/2023 Swegon reserves the right to alter specifications.
3
REACT ALS
Use
T est
2
I/s
Test m /h
3
I/s
Test m /h
Vnom Flow
Adr Vmin
Mode
Test
Vmax
1
Figure 4. REACT interface.
1 – Select the required function by turning the “Function wheel”.
2 – Set the value or select submenus by turning the “Edit” wheel.
3 – The value flashes twice when a new value is accepted.
I/s
Test
Menus m /h st
Te
I/s
Flow
I/s
Test
• Switch between l/s and m 3 /h via the edit wheel.
es t
• A “Lit” square on the display indicates the selected unit.
Vmi n
Vmin
I/s
Test m /h
3
Test m /h Test
I/s
3 m /h m /h
Te
I/s
• Vmin should be less than Vmax.
n
Vmin Vmi
VnomVnom
ModeMode
AdrAdr
Vmax
I/s
TTestes
Test
• Select new value for Vmax via the edit wheel.
Flow Flo
• Vmax should be greater than Vmin.
Vnom Vnom
Vmin Vmi
Adr Adr
Flo Flow w
Vmax Vmax
Mode Mode
Vmax Vmax
Vnom Vnom
Mode Mode
Adr Adr
T Testes
Vnom
I/s
Test
• For setting damper size. The set damper size is shown according to the list below.
List of Vnom abbreviations
Display text Physical size
110 ø160
330 ø250 Vmax Vmax
Test
I/s
T Testes
• Disconnects automatically after 10 hours.
Mode Mode
Adr Adr m /h
Test m /h
Vmin Vmi
• Turn the edit wheel to choose between the following modes: n oFF
Flow Flo w – Test mode switched off, the controller regulates normally on – Test mode is on, the damper is locked in its position oP – Opens the damper fully cL – Closes the damper completely
Lo – The damper is regulated to the selected Vmin
Hi – The damper is regulated to the selected Vmax
123 – Shows the current software version
Vmin Vmin
Vmax Vmax
Flow Flow
T Testes
Mode Mode
Vnom Vnom
Adr Adr
Mode
I/s
• Shows the selected control and actual value signal.
Test m /h
• Switch between 0-10 and 2-10 V via the edit wheel.
Adr
I/s
Test
• Used for Modbus. For particulars on how to use
Modbus, see next page.
4
Swegon reserves the right to alter specifications. 04/01/2023
REACT ALS
How to use Modbus
Modbus tables are available in a separate document (REACT – Modbus settings)
Function
Adr
Description
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It is possible to set the address from 1 till 247. If you turn the value selector to end stop "+", the display will show a "2". This makes it possible to select the second level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Flow
V min
V max
Test
Mode
Adr.
V nom
Return to previous level
Not used.
Not used.
Not used.
Shows the angle of the rotation (0…255 digital 0....100%)
Used for selecting communication settings for Modbus. See table below.
Used for setting response delay for the Modbus communication (see separate documentation)
16
17
18
19 3
12
13
14 4
15
20
21
22
23
24
Display number
1 3
2 3
3 3
10
11
8
9
6
7
4
5
3 Limited data length per reading of max. 8 addresses
4 Default setting
15
16
17
18
11
12
13
14
19
20
21
22
23
EEPROM value
0
1
2
9
10
7
8
5
6
3
4
Communication rate
1200
1200
1200
2400
2400
2400
4800
4800
4800
9600
9600
9600
19200
19200
19200
38400
38400
38400
1200
2400
4800
9600
19200
38400
Odd
None
Even
Odd
None
Even
Odd
None
None
None
None
None
None
Parity
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
1
1
2
1
1
1
1
2
1
1
1
1
1
Stop bits
2
1
1
2
1
1
1
1
2
2
1
04/01/2023 Swegon reserves the right to alter specifications.
5
REACT ALS
Trouble shooting
The product does not communicate over Modbus
• Make sure that the product is energized.
• Check the product's Modbus connection.
• Check the product's communication settings.
• Check that the product has the right and unique
Modbus address.
The product shows the incorrect/no air flow
• Make sure that the product is energized.
• Check that the motor’s set size (Vnom) corresponds with the physical size of the product, see “Use”.
• Make sure that the product is installed according to the recommended distance to disruptions, see “Installation”.
• Check that there is an air flow.
• Make sure that the product is correctly oriented in terms of air direction. The air flow must follow the instructions on the product.
• Check that the measuring tubes are mounted correctly, plus to plus (red), minus to minus (blue).
• Check that the measuring tubes are undamaged and not creased.
• Check with the help of the k-factor and pressure difference between the red and blue measuring tubes that the flow is within the product’s measurement range.
The product does not regulate the air flow
• Make sure that the product is energized.
• Check that the damper motor has not become detached from the damper cone.
• Check that the product is connected correctly.
• Check that the product is not force controlled.
The product does not regulate on the desired air flow
• Check that the settings for Vmin and Vmax correspond with the required regulation range.
• Check the electrical connection for the required function, see wiring diagrams in the document “Description of functions & wiring diagram”.
Product does not exit test mode
• Check that the product is connected correctly, check the “Y” signal and polarity on “G” and “G0”. See
“Connections”.
• Check the setpoint settings for Vmin and Vmax. The value for Vmax must be higher than Vmin in order for the product to be in automatic mode.
• If Modbus communication is used for the damper, test mode can be active via the communication. Try disconnecting the Modbus cables and set the motor in automatic mode. See “Use”.
Cleaning
Ideally, the product should be cleaned in connection with the cleaning of the rest of the ventilation system.
Cleaning of electrical components
• If needed, use a dry cloth to clean the components.
• Never use water, detergent and cleaning solvent or a vacuum cleaner.
External cleaning
• If necessary use tepid water and a well-wrung cloth.
• Never use detergent and cleaning solvent or a vacuum cleaner.
Internal cleaning
• The damper insert must be dismantled when cleaning the ventilation system.
• Cleaning equipment such as whisks and the like must not be fed through the product.
• If necessary remove dust and other particles that can be present in the product.
• Never use detergent and cleaning solvent or a vacuum cleaner.
Service/maintenance
• The product does not require any maintenance, except for any cleaning when necessary.
• In connection with a service, mandatory ventilation inspection or cleaning of the ventilation system, check that the general condition of the product appears to be good. Pay particular attention to the suspension, cables and that they sit firmly in place.
• It’s not permissible to open or repair electrical components.
• If you suspect that the product or a component is defective, please contact Swegon.
• A defective product or component must be replaced by an original spare part from Swegon.
Materials and surface treatment
• All sheet-metal parts are galvanized sheet steel (Z275).
• Internal sound-absorbing material is made of PET
(polyethylene terephthalate), fire rating: B-s1, d0.
Disposal
Waste must be handled according to local regulations.
Product warranty
The product warranty or service agreement will not be valid/will not be extended if: (1) the product is repaired, modified or changed, unless such repair, modification or change has been approved by Swegon AB; or (2) the serial number on the product has been made illegible or is missing.
6
Swegon reserves the right to alter specifications. 04/01/2023
Performance checks
4,00 V
V DC
REACT ALS
Dismantling the damper insert
1 2
Y
3
U CA CB
4 A B
Figure 5. Shows how to connect a voltmeter for checking the actual value.
Formulas for calculating air flow
The following applies for analogue control.
Control signal 0..10 V DC give the following formulas:
• Calculation of the current flow (V act value of the control signal (Y):
) when you know the
V act
= V min
+
Y
10 V DC
(V max
– V min
)
• Calculation of the current actual value (U) when you know the value of the current flow (V act
):
U = 10 V DC
V act
V nom
Control signal 2..10 V DC gives the following formulas:
• Calculation of the current flow (V act value of the control signal (Y):
) when you know the
Disconnect the damper motor cable. Fold away the perforated mesh.
Turn the damper insert so that the bayonet fitting releases. Pull out the damper insert.
V act
= V min
+
Y – 2 V DC
8 V DC
(V max
– V min
)
• Calculation of the current actual value (U) when you know the value of the current flow (V act
):
U = 2 V DC + 8 V DC
V act
V nom
Key to formulas:
Y = control signal in [V] DC
U * = actual value signal in [V] DC, always refers to 0-V nom
V act
= current air flow in [l/s, m 3 /h]
.
V min
= set min flow in [l/s, m 3 /h]
V max
= set max flow in [l/s, m 3 /h]
V nom
= nominal flow in [l/s, m 3 /h], see table on page 2.
* Note! Does not indicate damper position.
Figure 6. Dismantling the damper insert. Reassemble, in the reverse order.
04/01/2023 Swegon reserves the right to alter specifications.
7
REACT ALS
Technical data
IP class:
Corrosivity class:
Pressure class:
Leakage classes according to SS-EN 1751
Running times open/closed:
Ambient temperature
Operation:
Storage:
RH:
CE marking:
0 – +50 °C
-20 – +50°C
10 – 95%
(non-condensing)
2006/42/EC (MD)
2014/30/EU (EMC)
2011/65/EU (RoHS2)
IP42
C3
A
C
85 s
Electrical data
Power supply:
Fixed connection cable,
1000 mm med cable size.
24 V AC/DC ±15% 50 - 60 Hz
4 x 0.75 mm 2
2 x 0.38 mm 2
Power consumption, for transformer rating:
REACT ALS 150 N 2.0 W 3.5 VA
Declaration of Conformity
Swegon AB hereby affirms that:
REACT ALS complies with the essential characteristic demands and relevant regulations specified in the directives, 2006/42/EC (MD), 2014/30/EU (EMC) and
2011/65/EU (RoHS2):
The following standards have been observed:
EN ISO 12100:2010
EN 60204-1:2006
EN 60730-1:2011
EN 61000-6-2:2007
EN 61000-6-3:2007
Safety of machinery - General principles for design
- Risk assessment and risk mitigation
Safety of machinery - Electrical equipment of machines -
Part 1: Generic standards
Automatic electrical control and control unit for household use - Part 1: Generic standards
Electromagnetic compatibility (EMC). Generic standards. Immunity for industrial environments
Electromagnetic compatibility (EMC). Generic standards. Emission standard for residential, commercial and light-industrial environments
Person responsible for this declaration:
Name: Freddie Hansson, R&D Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 221116
This declaration is applicable only if the product has been installed according to the instructions in this document and if no modifications or changes have been made on this product.
References
www.swegon.com
Building Materials Declaration
REACT ALS Product sheet
REACT Description of functions & Wiring diagram
REACT Modbus settings
8
Swegon reserves the right to alter specifications. 04/01/2023