Invt BG 12-40KW Operation Manual

Add to My manuals
68 Pages

advertisement

Invt BG 12-40KW Operation Manual | Manualzz

Operation Manual iMars

INVT Solar Technology (Shenzhen) Co., Ltd.

Preface

The manual is intended to provide detailed information of product information, installation, application, trouble shooting, precautions and maintenance of iMars series grid-tied solar inverters.

The manual does not contain all the information of the photovoltaic system. Please read this manual carefully and follow all safety precautions seriously before any moving, installation, operation and maintenance to ensure correct use and high performance of operation on the inverter.

The use of the iMars series grid-tied solar inverters must comply with local laws and regulations on grid-tied power generation.

The manual needs to be kept well and be available at all times.

All rights reserved. The contents in this document are subject to change without notice.

There may be data deviation because of product improving. Detailed information is in accordant with the final product.

1

iMars grid-tied solar inverters Content

Contents

Preface ................................................................................................................................................ 1

Contents ............................................................................................................................................. 2

1 Safety precautions ......................................................................................................................... 5

1.1 Icons ........................................................................................................................................ 6

1.2 Safety guidelines ..................................................................................................................... 6

1.2.1 Delivery and installation ...............................................................................................................7

1.2.2 Grid-tied operation .........................................................................................................................8

1.2.3 Maintenance and inspection ........................................................................................................8

1.2.4 What to do after scrapping ...........................................................................................................9

2 Product overview ......................................................................................................................... 10

2.1 Solar grid-tied power generation system .............................................................................. 11

2.1.1 Supported grid connection structure ...................................................................................... 11

2.2 Products appearance ............................................................................................................ 12

2.2.1 Three-phase inverter .................................................................................................................. 12

2.3 Name plate ............................................................................................................................ 14

2.4 DRM instruction ..................................................................................................................... 15

2.5 Models ................................................................................................................................... 16

2.6 Dimensions and weight ......................................................................................................... 17

3 Storage ........................................................................................................................................... 18

4 Installation ..................................................................................................................................... 19

4.1 Unpacking inspection ............................................................................................................ 20

4.2 Before installation .................................................................................................................. 21

4.2.1 Installation tools ........................................................................................................................... 21

4.2.2 Installation place............................................................................................................................. 22

2

iMars grid-tied solar inverters Content

4.2.3 Connection cables........................................................................................................................... 24

4.2.4 Miniature circuit breakers.............................................................................................................. 24

4.3 Mechanical installation .......................................................................................................... 25

4.3.1 Installation of three-phase inverter .............................................................................................. 25

4.4 Electrical installation.............................................................................................................. 28

4.4.1 Connection of solar modules ......................................................................................................... 29

4.4.2 AC connection of 12kW / 15kW / 17kW / 20kW / 25kW / 30kW inverter ................................. 30

5 Operation ......................................................................................................................................... 33

5.1 Inspection before operation .................................................................................................. 34

5.2 Grid-tied operation ................................................................................................................ 34

5.3 Stopping................................................................................................................................. 35

5.4 Daily maintenance ................................................................................................................. 35

5.4.1 Regular maintenance ..................................................................................................................... 35

5.4.2 Maintenance guide ......................................................................................................................... 36

6 Display panel .................................................................................................................................... 39

6.1 LED indicators ....................................................................................................................... 40

6.2 Operation panel ..................................................................................................................... 41

6.3 LCD screen............................................................................................................................ 41

6.4 Functions operation ............................................................................................................... 42

6.4.1 Monitoring parameters .................................................................................................................. 42

6.4.2 History ............................................................................................................................................. 43

6.4.3 Statistics .......................................................................................................................................... 44

6.4.4 Parameter settings ......................................................................................................................... 44

6.4.5 System Information ........................................................................................................................ 51

6.4.6 Faults ............................................................................................................................................... 51

3

iMars grid-tied solar inverters Content

6.4.7 Inverter control ............................................................................................................................... 51

6.4.8 Mode settings ................................................................................................................................. 52

6.5 Grid Certification Choice ....................................................................................................... 53

7 Monitoring communication............................................................................................................... 55

7.1 Standard communication ...................................................................................................... 56

7.2 Optional communication ....................................................................................................... 57

7.3 RS485-DRM ports ................................................................................................................. 58

8 Troubleshooting ............................................................................................................................... 59

9 Contact us......................................................................................................................................... 63

10 Technical parameters ...................................................................................................................... 64

4

iMars grid-tied solar inverters Safety precautions

1 Safety precautions

iMars series grid-tied solar inverters are designed and tested strictly in accordance with relevant international safety standards. As an electrical and electronic device, all relevant safety regulations must be strictly complied during installation, operation, and maintenance. Incorrect use or misuse may result in ˖ z Injury to the life and personal safety of the operator or other people. z Damage to the inverter or other property belonging to the operator or other people.

In order to avoid personal injury, damage to the inverter or other devices, please strictly observe the following safety precautions.

This chapter mainly describes various warning symbols in operation manual and provides safety instructions for the installation, operation, maintenance and use of the iMars series grid-tied solar inverters.

5

iMars grid-tied solar inverters Safety precautions

1.1 Icons

This manual provides relevant information with icons to highlight the physical and property safety of the user to avoid device damage and physical injury.

The icons used in this manual are listed below:

Icons Name Instruction Abbreviation

Danger

Warning

Do not

Hot sides

Note

Danger

Warning

Do not

Serious physical injury or even death may occur if not follow the relative requirements

Physical injury or damage to the devices may occur if not follow the relative requirements

Damage may occur if not follow the relative requirements

Hot sides

Sides of the device may become hot. Do not touch.

Note

Physical hurt may occur if not follow the relative requirements

Note

1.2 Safety guidelines

z The first thing after receiving is to check for any visible damage to the package or to the inverter. If there is something suspected, contact the shipping company and local dealer before installing. z Only qualified electricians are allowed to operate on the inverter. z Do not carry out any wiring and inspection or changing components when the power supply is applied. Hazardous voltages may still be present in the inverter even if the AC and DC main switches are switched off. Wait at least 5 minutes after switching off the inverter. This ensures that the capacitors are electrically discharged. z This product can cause a residual current in the external protective earth conductor. Where a residual current-operated protective (RCD) or monitoring

(RCM) device is strongly recommend to used for protection in a case of direct or indirect contact, only an RCD or RCM of Type B is allowed on the supply side of this product.

6

iMars grid-tied solar inverters Safety precautions z Ensure that there is no electromagnetic interference from other electrical and electronic equipments on the installation site. z Do not refit the inverter unauthorized. z All the electric installation needs to be compliance with the national or local laws and standards. z The temperature of individual parts or the enclosure of the inverter

– especially the heat sink may become hot in normal operation. There is a danger of burning.

Do not touch. z Do not open the cover of inverters unauthorizedly. The electrical parts and components inside the inverter are electrostatic. Take measurements to avoid electrostatic discharge during relevant operation. z The inverter must be reliably grounded.

z Ensure that DC and AC side circuit breakers have been disconnected and wait at least 5 minutes before wiring and checking.

Note: Technical personnel who can perform installation, wiring, commissioning, maintenance, troubleshooting and replacement of the iMars series grid-tied solar inverters must meet the following requirements: z Operators need professional training. z Operators must read this manual completely and master the related safety precautions. z Operators need to be familiar with the relevant safety regulations for electrical systems. z Operators need to be fully familiar with the composition and operating principle of the entire grid-tied photovoltaic power generation system and related standards of the countries/regions in which the project is located. z Operators must wear personal protective equipment.

1.2.1

Delivery and installation

z Keep the package and unit complete, dry and clean during storage and delivery. z Please remove and install the inverter with two or more people, because of the inverter is heavy. z Remove and install the inverter with appropriate tools to ensure safe and normal operation and avoid physical injury or death. The people also need mechanical

7

iMars grid-tied solar inverters Safety precautions protective measures, such as protective shoes and work clothes. z Only qualified electricians are allowed to install the inverter. z Do not put and install the inverter on or close to combustible materials. z Keep the installation site away from children and other public places. z

Remove the metal jewelry such as ring and bracelet before installation and electrical connection to avoid electric shock. z Do cover solar modules with light-tight materials. Exposed to sunlight, solar modules will output dangerous voltage. z The inverter input voltage does not exceed the maximum input voltage; otherwise inverter damage may occur. z The positive and negative pole of solar modules can not be grounded, otherwise irrecoverable damage may occur. z Ensure the proper grounding of the inverter, otherwise, improper connection or no grounding may cause stop of the inverter. z

Ensure reliable installation and electrical connection. z When the photovoltaic generator cells are exposed to light (even if it is dim), the generator supplies DC voltage to the inverter.

Note: iMars grid-tied solar inverters are only for crystalline silicon solar modules.

1.2.2 Grid-tied operation

z Only qualified electricians are allowed to operate the inverter under the permission of local power departments. z All electrical connections must meet the electrical standards of the countries/regions in which the project is located. z Ensure reliable installation and electrical connection before operation. z Do not open the cover of inverter during operation or voltage is present.

1.2.3 Maintenance and inspection

z Only qualified electricians are allowed to perform the maintenance, inspection, and components replacement of the inverter. z Contact with the local dealer or supplier for maintenance. z In order to avoid irrelevant personnel from entering the maintenance area during

8

iMars grid-tied solar inverters Safety precautions maintenance, temporary warning labels must be placed to warn non-professionals to enter or use fence for isolation. z Firstly disconnect all power supplies of the grid to the inverter before any maintenance, and then disconnect the breakers and wait for at least 5 minutes until the inverter is discharged before maintenance. z Please follow electrostatic protection norms and take correct protective measures because of the electrostatic sensitive circuits and devices in the inverter. z Do not use parts and components not provided by our company during maintenance.

DŽ z Restart the inverter after settling the fault and problem which may affect the safety and performance of the inverter. z Do not get close to or touch any metal conductive part of the grid or inverter, otherwise electric shock, physical injury or death and fire may occur. Please do not ignore the warning icons and instructions with

“ electric shock

.

1.2.4 What to do after scrapping

z Do not dispose of the inverter together with household waste. The user has the responsibility and obligation to send it to the designated organization for recycling and disposal.

9

iMars grid-tied solar inverters Product overview

2 Product overview

This chapter mainly describes the appearance, packaging accessories, name plate, technical parameters and other information of iMars grid-tied solar inverters.

10

iMars grid-tied solar inverters Product overview

2.1 Solar grid-tied power generation system

The photovoltaic grid-tied power generation system consists of solar modules, grid-tied inverter, metering devices and public grid.

Figure 2.1 Application of iMars grid-tied solar inverters

Grid-tied solar inverter is the core of photovoltaic power generation system. The solar energy can be converted into DC electric energy through solar modules and then be changed into sinusoidal

AC energy which has the same frequency and phase with the public grid by grid-tied solar inverters, and then be fed to the grid.

iMars grid-tied solar inverters are only applied in solar grid-tied power generation system and its

DC input are only composed of crystalline silicon solar modules whose negative and positive poles are not grounded. z The recommended solar modules need to comply with IEC61730 Class A rating.

z iMars grid-tied solar inverters are only for crystalline silicon solar modules.

2.1.1 Supported grid connection structure

iMars series grid-tied solar inverters support TN-S, TN-C, TN-C-S , TT and IT grid connection.

When applied to the TT connection, the N-to-PE voltage should be less than 30V.

11

iMars grid-tied solar inverters Product overview

Figure 2.2 Type of grid

2.2 Products appearance

2.2.1 Three-phase inverter

Figure 2.3 Products appearance of 12~17kW

12

iMars grid-tied solar inverters Product overview

11

12

13

14

15

7

8

9

10

Figure 2.4 Products appearance of 20~30kW

Table 2-1 Parts instruction of Three-phase grid-tied solar inverter

No. Name Instruction

1

2

Cover

Operational panel LED indicators, LCD screen and buttons

5

6

3

4

Communication port

DC input port

Communication port

AC terminal

DRM communication port

For the connection of solar modules

RS485 and EXT communication port

For the connection of AC output

Installation hanger

Fan mounting plate

Concave handle

Safety precautions

Name plate

External grounding hole

Air duct

Screw holes

Cooling chamber

For the connection of inverter and installation bracket

Air inlet, and for fans fixing

For removing and carrying

For rated parameters of the inverter

For ventilation

To fasten the inverter on the installation bracket

Protect the radiator and fan

13

iMars grid-tied solar inverters Product overview

2.3 Name plate

After receiving, please check the information of name plates are the ordered one. If not, please contact with the supplier as soon as possible.

Figure 2.5

Name plate

˄ 1 ˅ Trademark and product type

˄ 2 ˅ Model and important technical parameters

˄ 3 ˅ Certification system of the inverter confirming

˄ 4 ˅ Serial number, company name and country of origin

14

iMars grid-tied solar inverters Product overview

Icons Instruction z TUV certification mark. The inverter is certified by TUV. z CE certification mark. The inverter complies with the CE directive. z CQC certification mark. The inverter is certified by CQC. z EU WEEE mark. Cannot dispose of the inverter as household waste.

2.4 DRM instruction

Figure 2.6 DRM label

Table 2-2 DRMs instruction

No. Mode Requirement

1 DRM0 Operate the disconnection devise

2 DRM1 Do not consume power

3 DRM2 Do not consume at more than 50% of rated power

4 DRM3

Do not consume at more than 75% of rated power AND Source reactive power if capable

5 DRM4 Increase power consumption(subject to constraints from other active DRMs)

6 DRM5 Do not generate power

7 DRM6 Do not generate at more than 50% of rated power

8 DRM7

Do not generate at more than 75% of rated power AND Sink reactive power if capable

9 DRM8 Increase power generation(subject to constraints from other active DRMs)

Note: Our product only realize the DRM0 function

15

iMars grid-tied solar inverters Product overview

2.5 Models

Table 2-3 Models of iMars grid-tied solar inverter

Product name Model

Three-phase (L1, L2, L3, N, PE)

Three-phase grid-tied solar inverter

Three-phase grid-tied solar inverter

Three-phase grid-tied solar inverter

Three-phase grid-tied solar inverter

Three-phase grid-tied solar inverter

Rated output power

Three-phase grid-tied solar inverter

Note: Refer to the product specifications in chapter 10 for detailed information.

16

iMars grid-tied solar inverters Product overview

2.6 Dimensions and weight

Figure 2.7 Inverter dimensions

Table 2-4 Inverter dimension and net weight

Model

12kW / 15kW/ 17kW

H

(mm)

610

W

(mm)

480

20kW / 25kW / 30kW 660 520

D

(mm)

230

250

Net weight

(kg)

36

53

D

H

W

Figure 2.8

Paper packages dimension

Table 2-5 Packages dimension and gross weight

Model

H

(mm)

W

(mm)

D

(mm)

Gross weight

(kg)

12kW / 15kW/ 17kW 788 622 396 43

20kW / 25kW / 30kW 850 665 410 62

Packaging

Material

Paper

Paper

17

iMars grid-tied solar inverters Storage

3 Storage

If the inverter is not put into use immediately, the storage of inverter should meet the following requirements: z Do not remove the outer packing. z The inverter needs to be stored in a clean and dry place, and prevent the erosion of dust and water vapor. z The storage temperature should be kept at -40°C~+70°C, and the relative humidity should be kept at 5%RH~95%RH. z The stacking of inverters is recommended to be placed according to the number of stacking layers in the original shipment. Place the inverter carefully during stacking to avoid personal injury or equipment damage caused by the falling of equipment. z Keep away from chemically corrosive substances that may corrode the inverter. z Periodic inspections are required. If damages are found by worms and rats, or packaging are found to be damaged, the packaging materials must be replaced in time.

After long-term storage, inverters need to be inspected and tested by qualified personnel before put into use.

18

iMars grid-tied solar inverters Installation

4 Installation

This chapter describes how to install the inverter and connect it to the grid-tied solar system

(including the connection between solar modules, public grid and inverter).

Read this chapter carefully and ensure all installation requirements are met before installation.

Only qualified electricians are allowed to install the inverter.

19

iMars grid-tied solar inverters Installation

4.1 Unpacking inspection

I Inspect the information of the order and the name plate to ensure the product are the ordered one and no damage to the package. If any problem, contact the supplier as soon as possible.

Put the inverter into the package if not used and protect it from humidity and dust.

Check as following after unpacking:

(1) Ensure no damage to the inverter unit.

(2) Ensure the operation manual, port and installation accessories in the package.

(3) Ensure no damage or loss to the items in the package.

(4) Ensure the information of the order are the same as that of the name plate.

Below are the detailed lists:

Packing list of 12kW / 15kW/ 17kW inverter:

6

7

4

5

No.

1

2

3

8

9

Figure 4.1 Packing list of 12kW / 15kW/ 17kW inverter

Table 4-1 Detailed delivery list of 12kW / 15kW / 17kW inverter

Name

12kW / 15kW / 17kW inverter

Installation bracket operation manual

Communication connector

DC connector

Expansion bolts M8*60

Hex combination bolt

Screws M6*16

Ring terminal

Quantity

1

1

1

2

2

6

6

2

5

20

iMars grid-tied solar inverters Installation

Packing list of 20kW / 25kW / 30kW inverter:

Figure 4.2 Packing list of 20kW / 25kW / 30kW inverter

Table 4-2 Detailed delivery list of 20kW / 25kW / 30kW inverter

No.

1

2

Name

20kW / 25kW / 30kW inverter

Installation bracket

5

6

3

4

7

8 operation manual

Communication connector

DC connector

Expansion bolts M8*60

Hex combination bolt

Screws M6*16

9 Ring terminal

4.2 Before installation

4.2.1 Installation tools

Table 4-3 Tools list

No. Installation tools

1 Marking pen

2

3

4

Electrodrill

Hammer

Monkey wrench

Instruction

Mark the installation hole

Drill in the bracket or wall

Hammer on the expansion bolts

Fix the installation bracket

21

Quantity

1

1

1

2

2

6

6

2

5

iMars grid-tied solar inverters Installation

No.

5

6

7

8

9

10

Installation tools

Allen driver

Straight screwdriver

Megger

Multimeter

Electric iron

Wire crimper

Instruction

Fasten the screws, remove and install AC wiring box

For AC wiring

Measuring insulation performance and impedance

Check the circuit and AC and DC voltage

Weld communications cable

Crimp DC terminals

11 Hydraulic clamp

4.2.2 Installation place

Crimp ring terminal for AC wiring

Select installation site according to below requirements:

(1) The height of the installation position should ensure that the line of sight is at the same level as the LCD for viewing the parameters inverter conveniently.

Figure 4.3 Optimal mounting height

(2) The installation site must be well ventilated and away from raindrops or direct sunlight.

(3) There must be enough pre-reserved space around the installation site for convenient installation and disassembly of the inverter and air convection, as shown in Fig 4.4.

Fig 4.4 Installation spacing

22

iMars grid-tied solar inverters Installation

When install more than one inverter, it is necessary to reserve a certain space between the inverters. The left and right spacing is shown as Figure 4.5, and the upper and lower sides of the inverter should have sufficient space to ensure good heat dissipation.

Figure 4.5 Side-by-side installation space requirements

(4) The ambient temperature of installation should be -25°C~60°C

(5) The installation site should be away from electronic devices which can generate strong electromagnetic interference

(6) The inverter should be installed on firm and solid surface eg wall surface and metal bracket

(7) The installation surface should be vertical to the horizontal line, as shown in Figure 4.6

Install the inverter vertically or backward İ 15 e to facilitate heat dissipation.

Do not tilt the inverter forward, horizontal, upside down, over- backward, and roll when install the inverter.

Fig 4.6 Installation position of the inverter

23

iMars grid-tied solar inverters Installation

(8) The installation should ensure that the inverter is reliably grounded, and the material of grounded metal conductor should be consistent with the metal material reserved for the grounding of the inverter. z Do not remove any part and component of the inverter unintended; otherwise damage to the device and physical injury may occur.

4.2.3 Connection cables

The user can select connection cable according the table below:

Table 4-4 Cable specifications

DC side

Model

12kW /15kW / 17kW

20kW / 25kW

30kW

Cross-section

(length ≤ 50m)

4

4

4

mm ϡ

Cross-section

(length >50m) mm ϡ

6

6

6

AC side

Mini cross-section mm ϡ

L N/PE

6

8

10

4

4

6

4.2.4 Miniature circuit breakers

It is recommended strongly to install circuit breakers or fus es at the DC input and AC output to ensure safe installation and running. z In order to protect the PCE, user and installer, external DC and AC circuit breaker shall be equipped at the end-use application; z The wiring shall be according local electric code. Choose proper cable for power input and output lines. Input and output cable shall be PV private cables suitable for outdoor use.

Table 4-5 Breakers specifications

Model

12kW

DC input

Recommended DC breakers

(optional for length >100m)

DC1000V, C32A, 2P

15kW

17kW

20kW

DC1000V, C32A, 2P

DC1000V, C32A, 2P

DC1000V, C40A, 2P

25kW

30kW

DC1000V, C40A, 2P

DC1000V, C50A, 2P

AC output

Recommended AC breakers

AC400V, C25A, 4P

AC400V, C32A, 4P

AC400V, C35A, 4P

AC400V, C50A, 4P

AC400V, C63A, 4P

AC400V, C63A, 4P

24

iMars grid-tied solar inverters Installation

4.3 Mechanical installation

Since the installation place can be made by different construction materials, the inverter can be installed by different mounting methods. Take the typical installation environment as the example, the manual describes how to install the inverter on concrete wall. And because of different structure, the three-phase inverter has different instillation modes.

The inverter should be mounted in a vertical position of 90°to the horizontal line as shown in figure

4.7.

4.3.1 Installation of three-phase inverter

Figure 4.7 Installation bracket of 12kW / 15kW/ 17kW/ 20kW / 25kW / 30kW

25

iMars grid-tied solar inverters Installation

Table 4-6 Instruction of installation bracket

Model

A(mm)

Installation hole

B(mm)

12kW / 15kW/ 17kW / 20kW / 25kW / 30kW 400 400

Installation steps of three-phase inverter:

(1) Use the wall hanging plate in the packing box to determine the hole position θ As shown in

Figure 4.8. Level the holes with a level ruler and mark it with a marking pen.

Figure 4.8 Mark the punch position

(2) Drill 6 installation holes on the wall with electric drill. As shown in Figure 4.9.

Figure 4.9 Drilling

(3) Fix the expansion bolts to the 4/6 installation holes with hammer, as shown in Figure 4.10.

26

iMars grid-tied solar inverters Installation

Figure 4.10 Install expansion bolts

(4) Fix the installation bracket onto the expansion bolts and ensure the installation is firm enough(tightening torque is 13N Ь m) . As shown in Figure 4.11.

Figure 4.11 Fix the installation bracket

(5) Hang the inverter onto the installation bracket and ensure the installation is firm enough .

As shown in Figure 4.12.

Figure 4.12 Installation of inverter

27

iMars grid-tied solar inverters Installation

(6) Ensure the inverter is installed properly and tighten the M6X16 bolts into the screw holes on the left and right side of inverter(tightening torque is 4N Ь m). As shown in Figure 4.13.

Figure4.13 Installation of M6X16 bolts

4.4 Electrical installation

This section proposes to describe detailed electrical installation and related safety instructions.

Note

Figure 4.14 Block diagram of the grid-tied solar system z Improper operation during the wiring process can cause fatal injury to operator or unrecoverable damage to the inverter. Only qualified personnel can perform the wiring work. z All electrical installations must be in accordance with local and national electrical codes. z All cables must be firmly attached, undamaged, properly insulated and adequately dimensioned. z It is not allowed to close the AC and DC breakers before the inverter is electrically connected. z Read and follow the instructions provided in this section while observing all safety warnings. z Always note the rated voltage and current defined in this manual. Never exceed the limits.

28

iMars grid-tied solar inverters Installation

4.4.1 Connection of solar modules

2 2

2 2

1 1

3 3

5

4 4

5

Figure 4.15 Connection between DC connector and solar modules

Connection steps:

(1) Lighting, short-circuit and other protection measures which meet the local electrical safety laws and regulations are needed before the AC connection; z Only qualified cables under the local electrical safety laws and regulations are allowed to connect.

(2) Connect the output cables of solar modules to the DC connector as figure 4.15 shows.

Loose the nut of connector and remove the isolation layer of the DC cable for about 15mm.

Insert it into the connector and press until heart the lock sound. Finally fasten the nut to a torque of 2.5-3 Nm. The wiring of negative pole is the same as that of the positive pole.

Ensure the poles of solar modules are well connected with the connectors;

(3) After the DC connector is connected, use a multimeter to measure the voltage of the DC input string, verify the polarity of the DC input cable, and ensure that the voltage of each string is within the allowable range of the inverter, as shown in Figure 4.16.

Figure 4.16 DC input voltage measuring

29

iMars grid-tied solar inverters Installation z The solar modules connected with the inverter needs to be the configured ones other than some connecting devices without authorized. Otherwise, device damage, unstable operation or fire may occur.

(4) Connect the DC connector with the inverter and ensure tightly-fastened;

(5) Insert the screw-driver into the hole of the connector to remove the connector form the inverter.

(6) Unclench the pressed cover with screw-driver to remove the cables from the connector.

4.4.2 AC connection of 12kW / 15kW / 17kW / 20kW / 25kW / 30kW inverter

Table4-7 Port instruction of12kW / 15kW/ 17kW /20kW / 25kW / 30kW AC connector

AC connector Three-phase Remark

L1 L1 (A)

L2

L3

N

L2 (B)

L3 (C)

N neutral wire

PE grounding wire

Connection steps of 12kW / 15kW/ 17kW / 20kW / 25kW / 30kW inverter:

Must be connected

(1)Lighting, short-circuit and other protection measures which meet the local electrical safety laws and regulations are needed before the AC connection; z Only qualified cables under the local electrical safety laws and regulations are allowed to connect. z Only with the permission of the local electric power company can the inverter be connected to the utility grid.

(2) Disassemble the waterproof cover of the three-phase inverter AC junction box, as shown in

Figure 4.17;

Figure 4.17 Unpacking the waterproof cover

30

iMars grid-tied solar inverters Installation

(3) Remove the fixing screws of AC terminal rail, as shown in Figure 4.18.

Figure 4.18 Remove fixing screws of the rail

(4) Pull out the AC terminal rail as shown in Figure 4.19.

Figure 4.19 Pull out the rail

(5) Crimp the five wires(L1 ǃ ǃ ǃ PE) of the three-phase utility grid and the OT terminals firmly to ensure that the conductor of the wire is not exposed, as shown in Figure 4.20;

Figure 4.20 Wire crimp terminal

(6) The connection of AC cable and the connector should be correct and the screws are tightened.

The tightening torque is 2N•m, as shown in Figure 4.21.

31

iMars grid-tied solar inverters Installation

Figure 4.21 Connection of wire and connector

(7) Push the AC terminal rail into the inside of the case and fix the rail with screws. Then lock the waterproof cover of the junction box with the fixing screws. The tightening torque is 1.5 N•m.

Finally, tighten the waterproof connector to complete the waterproofing of the cable, as shown in

Figure 4.22.

Figure 4.22 Fix the waterproof cover of junction box

32

iMars grid-tied solar inverters Operation

5 Operation

This chapter describes detailed operation of the inverter which involves the inspection before operation, grid-tied operation, stopping and daily maintenance of the inverter.

33

iMars grid-tied solar inverters Operation

5.1 Inspection before operation

Check as follows before operation (including but not limited to):

(1) Ensure the installation site meet the requirement mentioned in section 4.2.2 for easy installation, removing, operation and maintenance;

(2) Ensure the mechanical installation meet the requirement mentioned in section 4.3;

(3) Ensure the electrical installation meet the requirement mentioned in section 4.4;

(4) Ensure all switches are “ off ” ;

(5) Ensure the voltage meet the requirement mentioned in chapter 10;

(6) Ensure all electrical safety precautions are clearly-identified on the installation site. z Do check as above before any operation if the system or inverter needs to be installed, refitted and maintained.

5.2 Grid-tied operation

Note z When power on the inverter for the first time, please refer to section 6.5 to complete grid certification choice. z Keep the inverter power on at least 30 minutes to charge for the internal clock battery.

Please start the inverter as follows:

(1) Ensure the requirements mentioned in section 5.1 are met;

(2) Switch on the breakers at the AC side;

(3) Switch on the integrated DC switch;

(4) Switch on the switch on the DC side;

(5) Observe the LED indicators and information displayed on the screen. Refer to chapter 6 for detailed information.

(6)

Run

Green indicator blinks, others off: the inverter is power on and in

(7) self-inspection;

Run Green indicator on, others off: the inverter is in power generation after self-inspection----successful commissioning.

(8) “ Warn ” or “ Fault ” indicators are on or blinking: the inverter is power on, but fault occurs. Please refer to section 6.3 for detailed information, and then stop as the section 5.3 mentioned, finally settle the problems as chapter 8. If all faults are solved, do as chapter 5 mentioned.

(9) Refer t o section 6.4.4 to set the inverter time according to local time.

(10) The default DC input mode is “ independent ” . Please refer to section 6.4.4 for inquiry and detailed setting.

34

iMars grid-tied solar inverters Operation

5.3 Stopping

Stop the inverter as follows it needs maintenance, inspection and troubleshooting:

(1) Switch off the breakers at the AC side;

(2) Switch off the integrated DC switch;

(3) Switch off the switch on the DC side;

(4) Wait at least 5 minutes until the internal parts and components are discharged. And then stop the inverter.

5.4 Daily maintenance

The inverter can perform power generation, start and stop automatically even the day and night shifts and seasons change in one year. In order to prolong the service life, daily maintenance and inspection are needed besides following the instructions mentioned in this manual seriously.

5.4.1 Regular maintenance

Maintenance contents

Store the operation data

Check inverter operation status

Clean the surface

Check electrical connection

Maintenance methods

Maintenance cycle

Use real-time monitoring software to read inverter running data, regularly back up all inverter running data and stats. Check the monitoring software and inverter LCD screen to make sure the parameters are set correctly.

Check to make sure the inverter installation is solid, no damage or deformation. When inverter running, check to make sure the sound and variables are normal. When inverter running, use thermal imager to check whether the case cooling is normal.

Check the ambient humidity and dust around inverter, clean the inverter when necessary.

See Section 5.4.2.

Check the cable connection and inverter terminals, make sure they are connected reliably, not loose, and no damage, insulation reliable.

Once each quarter

Every six months

Every six months

Every six months

35

iMars grid-tied solar inverters Operation

Maintenance contents

Maintenance methods

Maintenance and replace fan

Check the security features

Check the fans of three-phase inverter to make sure out of wind is normal, the sound is normal, the fan blades are no cracks, power lines and control signal lines are not damaged. If necessary, clean the air inlet and outlet; If not running properly, the fan must be replaced, see

Section 5.4.2.

Check the off-on feature of inverter: use monitoring software or LCD and keyboard on the inverter, do "off" and "on" operation, to confirm its off-on feature intact. At the same time, make sure monitoring software can normally communicate with the inverter. Check the warning label on or around the inverter, if necessary replaced.

5.4.2 Maintenance guide

Maintenance cycle

Every six months

Every six months

Clean the inverter

Cleaning procedure is as follows:

(1) Disconnect the input and output switches.

(2) Wait ten minutes.

(3) Use a soft brush or a vacuum cleaner to clean the surface and the inlet and outlet of the inverter.

(4) Repeat Section 5.1 operating content.

(5) Restart the inverter.

Clean the fans

Cleaning procedure is as follows:

(1) Disconnect the input and output switches.

(3) Remove the inverter as the reverse steps of Section 4 content.

(4) Remove the cooling chamber or fan mounting plate, as shown in Figure 5.1 and Figure

5.2.

36

iMars grid-tied solar inverters Operation

Figure 5.1 Remove the cooling chamber

Figure 5.2 Remove the fan mounting plate

(5) Use soft brush or vacuum cleaner to clean the cooling chamber and the fans.

(6) Assembly the cooling chamber or fan mounting plate into inverter.

(7) Re-install the inverter to its original position as Section 4 of the content.

(8) Repeat Section 5.1 operating content.

(9) Restart the inverter.

Fan Replacement

If the inverter reports over-temperature fault, or non-normal fan operation noise, please replace the fan. This operation must be carried out by professionals. z Inverter should be shut down before maintenance work begins, and disconnect all power inputs. z Wait at least 10 minutes, until the inverter internal capacitors discharge before maintenance work. z Fan replacement must be carried out by professionals.

Fan replacement procedure is as follows:

(1) Disconnect the input and output switches.

(2) Make DC switch to the "OFF" position.

(3) Wait ten minutes.

(4) Remove the inverter as the reverse steps of Section 4 content.

37

iMars grid-tied solar inverters Operation

(5) Dismantle the fan mounting plate as shown in Figure 5.2.

(6) Remove the damaged fans, and replace good fans, connect the power lines and control signal lines, as shown in Figure 5.3.

Figure 5.3 Replace fans

(7) Assembly the cooling chamber or fan mounting plate into inverter.

(8) Re-install the inverter to its original position as Section 4 of the content.

(9) Repeat Section 5.1 operating content.

(10) Restart the inverter.

Note z Once the inverter alarms and stops, do not be restarted before all the fault has been ruled out. Checks should be strictly in accordance with Section 5.1 steps.

38

iMars grid-tied solar inverters Display panel

6 Display panel

This chapter describes the panel displaying and how to operate on the panel, which involves the

LCD display, LED indicators and operation panel.

39

iMars grid-tied solar inverters Display panel

The operation state and parameters can be attained from the LED indicators and LCD display. The displayed content and parameters can also be set or modified by the operation panel.

LCD screen p

A l a r m

V - p v 1 : 0 0 0 . 0 V

I - p v 1 : 0 0 0 . 0 A h

V - p v 2 : 0 0 0 . 0 V

0 1 . A 0 0 1 MENU

LED indicator

Operation panel

Figure 6.1 Operation panel

6.1 LED indicators

There are three LED indicators on the panel:

(1) “ Run ” , operation indicator, green;

(2) “ Warn ” recoverable fault indicator, yellow;

(3) “ Fault ” , unrecoverable fault indicator, red.

The inverter state includes 6 states of stand-by, self-inspection, power generation, recoverable fault and unrecoverable fault; LED indicators are on, off and blinking. Please refer to table 5-1 for detailed state of inverter and LED indicators state.

“ ”: LED indicator is off;

“ ” ( green), “ ” ( yellow), “ ” ( red): LED indicator is blinking at every 0.25S or 0.5S;

“ (Green), “ ” ( yellow), “ ” ( red): LED indicator is on.

Table 6-1 Inverter state and LED indicators

Inverter state LED indicators

Stand-by

Self-inspection

Power generation

Run

Warn

Fault

Run

Warn

Fault

Run

Warn

Fault

Run

Warn

Fault

Description

No power on. All indicators off.

Green indicator blinks in every 0.25s, others off.

Power on and ready for self-inspection

Green indicator keeps on, others off.

Grid-tied power generation.

(1) Grid-tied power generation, but clock fault (A007);

(2) Grid-tied power generation, but DC input fault

(A001 or E001);

(3) Grid-tied power generation ˈ but fan fault(E006 or

40

iMars grid-tied solar inverters Display panel

Inverter state LED indicators Description

E012);

Green and yellow indicator keeps on, others off.

Recoverable fault

Unrecoverable fault

Run

Warn

Fault

Run

Warn

Fault

Run

Warn

Fault

Run

Warn

Fault

Inverter stand-by. The public grid fault(A001, A003,

A004, A005or A006);

Yellow indicator blinks in every 0.5s, others off

(2) Inverter stand-by. DC input fault (E001);

Yellow indicator keeps on, others off

Hardware or software fault (E003, E004, E005, E008,

E009, E011, E013 or E015). De-couple the inverter from the system before maintenance.

Red indicator blinks in every 0.5s, others off

Current-leakage or unqualified output power energy of the inverter (E007, E010, E014, E017, E018 or E020).

De-couple the inverter from the system before maintenance.

Red indicator keeps on, others off

Artificial turned off

Run

Warn

Fault

Stop after the communication or panel command. All indicators are on.

Note Please refer to chapter 6 and 8 for detailed fault information and troubleshooting.

6.2 Operation panel

There are 4 buttons on the panel:

(1) “ ESC ” , exit and return ;

(2) “ ” , back to the front page and data increasing;

(3) “ ” ˈ to the next page and data decreasing;

(4) “ ENT ” , enter.

6.3 LCD screen

All information is displayed on the LCD screen. The background illumination of LCD screen will go out to save power if there is not button operation in 15 seconds. But it can be activated by pressing any button. Press “ ENT ” to enter into the main interface if the background illumination is on. All parameters can be viewed and set on the interface.

There are main interface and menu interfaces on the LCD screen, of which the main interface is the default one after power on, while the menu interfaces are used to watch and set parameters or other manual operation, such as viewing the monitoring parameters, history record, system information, statistics and fault information and setting the displayed language, time, communication address, password and factory defaults.

41

iMars grid-tied solar inverters Display panel

Curve Graphic

Display Area

Text Parameter

Display Area

Status Area Fault Code Menu

Figure 6.2 Main interface

The main interface of the LCD screen is shown as the figure above:

(1) The curve displays the power changing at the current day;

(2) The words on the screen display the current key parameters of the inverter. Three lines of words are displayed at a time, but if the inverter is in operation or stand-by state, the words are rolling forward at every 3s. And the user can press “ ” or “ ” to look up the information freely;

(3) 5 states of the inverter are displayed on the screen;

(4) If the inverter is in fault or warning state, up to 8 corresponding fault codes can be displaying on the screen.

6.4 Functions operation

Most of the parameters can be viewed and set through the LCD screen and operation panel.

M a i n M e n u

M o n i t P a r a m S e t u p

H i s t o r y S y s t e m I n f o

S t a t i s t i c s F a u l t I n f o

Figure 6.3 Main interface

6.4.1 Monitoring parameters

Press “ ” and “ ” in the main interface to select “Monit P aram” , and then press “ ENT ” to view the parameters which is shown in figure 6.4. Go the front or next page through “ ” and “ ” and return through “ ESC ” .

C u r r e n t S t a t e

E - t o d : 0 W h

$ - t o d : 噉 0 . 0 0

P - i n : 0 . 0 0 k W

Figure 6.4 Monitoring parameters

Different inverter has different parameters. “ ƽ ” in table 6-2 means the monitoring parameters of the inverter can be displayed on the LCD screen.

42

iMars grid-tied solar inverters Display panel

Table 6-2 Monitoring parameters

Monitoring content

Total power produced this day(E-tod)

Total power saved this day($-tod)

Input power(P-in)

Output power(P-out)

Peak power(PpDay)

Grid voltage U(VoutU)

Grid voltage V (VoutV)

Grid voltage W (VoutW)

Grid current U (IoutU)

Grid current V(IoutV)

Grid current W(IoutW)

Grid frequency(Fgrid)

Power factor(pf)

Input V 1(V-pv1)

Input I1 (I-pv1)

Input V2(V-pv2)

Input I2(I-pv2)

Grounding resistor(Riso)

Leakage current(Ileak)

Temperature 1(Tinv1)

Temperature 2(Tinv2)

Total power consumption(E-tot)

Total time(h-tot)

Current date(Data)

Current time(Time)

First power-on time of today (Power ON)

First running time of today (Run Time)

Peak power time of today (Ppk Time)

Stop running time of today (Today OFF)

Stop running time of yesterday (Last OFF)

12kW / 15kW / 17kW 20kW / 25kW / 30kW

6.4.2 History

Press “ ” and “ ” in the main interface to select “ History ” , and then press “ENT” to view the

43

iMars grid-tied solar inverters Display panel parameters which is shown in figure 6.5.

H i s t o r y

2 0 1 2 / 0 1 / 0 5 1 1 : 3 2 : 1 6

A 0 0 5 : G r i d u n d e r f r e q

0

Figure 6.5 History parameters

There are 32 history records in total. Press “ ” and “ ” to review the history record and press

“ ESC ” to exit. The numbers on the top right is the serial No. of the record and the numbers in the second line display date when faults occur and settled. If the color of the third line illuminates, the fault occurs, if not, the fault is solved.

6.4.3 Statistics

Press “ ” and “ ” in the main interface to select “Statistics” , and then press “ENT” to view the parameters which is shown in figure 6.6.

Figure 6.6 Statistic information

The information in table 6-3 can be viewed in the statistical menu.

Table 6-3 Statistic information

Content Detailed

Lifetime

Total operation time, total power produced, total power saved, total CO

2 reduction in lifetime

Day statistics

Total power produced, total power saved, peak power and total CO

2 reduction in current day

6.4.4 Parameter settings

Press “ ” and “ ” in the main interface to select “ Setup Menu ” , and then press “ENT” to view the parameters which is shown in figure 6.7.

A d d r e s s

S e t u p M e n u

D a t e / T i m e

K e y p a d P W D

C a s h / p r i c e

L a n g u a g e

S e t M o d e l

Figure 6.7 Setting information

Parameters can be set in this interface.

44

iMars grid-tied solar inverters Display panel

LCD menus: p

Alarm h

V - pv 1 : 000 . 0 V

I - pv 1 : 000 . 0 A

V - pv 2 : 000 . 0 V

01 . A 001 MENU

Address

Setup Menu

Date / Time

Keypad PWD Language

Cash / price Country

Main Menu

Monit Param Setup

History

Statistics

System Info

Fault Info

RS 485 Address

001 1

Current State

E - tod : 0 Wh

$ - tod : 噉 0 . 00

P - in : 0 . 00 kW

User Password

0000 0

History

2012 / 01 / 05 11 : 32 : 16

A 005 : Grid under freq

0

Setup Cash

Val / kWh : 00 . 50 噉 / 1 kWh

Setup Date / Time

Time : 12 : 14 : 30

Lifetime

Statistical Menu

Today

Address

Setup Menu

Date / Time

Keypad PWD Language

Cash / price Set Model

System Information

Part No .

Cert . Area

Serial No .

Soft Ver

Run Param

Fault

1 : A 005 Grid under freq

2 : A 001 Input under Volt

3 :

On / Off

Clear

Restart

Control Menu

Factory

Curr. Language : English

English Dutch

Chinese

German

Country

Germany

England

Australia

: Australia

Greece

Denmark

Holland

Setup Model : Independ

Independ

Parallel

45

iMars grid-tied solar inverters Display panel

Table 6-4 Parameters setting

Setting item LCD display

R S 4 8 5 A d d r e s s

RS485

Address

User password

U s e r P a s s w o r d

Instruction

Enter into the interface and edit the data through “ ” or “ ” . And then press

“ ENT ” again to the next bit. After editing the three bits, press

ENT

to save the edition and press “ ESC ” to exit.

Enter into the interface and edit the data through “ ” or “ ” . And then press

“ ENT ” again to the next bit. After editing the four bits, press “ ENT ” to save the edition and press “ ESC ” to exit.

The default password is “ 0000 ” ; the user can enter into the setting interface without password. If the password is not

“ 0000 ” , the user can enter into the setting interface with password.

46

iMars grid-tied solar inverters Display panel

Setting item LCD display

Setup Cash

Setup

Date/Time

Language

Select

Country

Setup mode

S e t u p C a s h

V a l / k W h : 0 0 . 5 0 噉 / 1 k W h

S e t u p D a t e / T i m e

T i m e : 1 2 : 1 4 : 3 0

Curr. Language : English

English Dutch

Chinese

German

Country

Germany

England

Australia

: Australia

Greece

Denmark

Holland

S e t u p M o d e l : I n d e p e n d

I n d e p e n d

P a r a l l e l

Instruction

Enter into the interface and edit the currency type and cash through “ ” or

“ ” . And then press “ ENT ” again to the next line. After editing the four bits, press

“ ENT ” to save the edition and press

“ ESC ” to exit.

The currency types include EUR, POD,

CNY and USD.

Enter into the interface and edit the date and time through “ ” or “ ” . And then press

ENT

again to the next line. After editing the four bits, press “ ENT ” to save the edition and press “ ESC ” to exit.

ˈ

Enter into the interface and edit the language through “ ” or “ ” . And then press “ ENT ” again to save the edition and press “ ESC ” to exit.

The default language is English.

Enter into the interface and select country through “ ” or “ ” . And then press “ ENT ” again to save the edition and press “ ESC ” to exit.

The DC input mode includes

“ independent ” and “ parallel ” :

“ independent mode ” is the independent

MPPT of Track A and Track B; “ parallel mode ” is the parallel MPPT of Track A and Track B.

The default mode is “ independent ” .

The input mode setting is invisible if the inverter is in power generation. It is only available during DC power on and AC power off.

Press “ ” or “ ” to select the setting mode and press “ ENT ” to save the setting or “ ESC ” to return.

If the situation of section 6.4.8 occurs, it is necessary to switch the DC input to

“ parallel ” mode.

47

iMars grid-tied solar inverters Display panel

Setting item Instruction LCD display

Input password

0000

Set power

P-Lmt

Mode

LmtPower

P.Factor

set power

Limit Mode Invalid

Invalid

Auto

Manual

Limit Power

100%

The password is needed when enter into the interface of “Set power”. Get the password from the supplier if necessary.

There are 3 submenus: ķ P-Lmt Mode: invalid (limited power function is invalid),auto (special for single phase) ,manual (set the limit of output value manually); ĸ LmtPower: this function is only valid when the P-Lmt

Mode is manual, the percentage is that of the rated power and the setting range is from 10% to 100%; Ĺ p.Factor: includes normal model (default value

“1”), current advanced mode and current hysteresis mode and the setting rage is

-0.9-0.99.

(the machine of three phase only has the function of Ĺ )

Power Factor

Grid Tied Mode

Normal Mode

Power Factor 1.00

48

iMars grid-tied solar inverters Display panel

Setting item LCD display Instruction

Input password

0000

Run Param

UV Volt

Run Param

OV time

UV time

OV Volt

UF Freq

UF time

184V

ACUV Volt(phase volt)

0.20s

ACUV Time

263V

ACOV Volt(phase volt)

ACOV Time

0.20s

47.6Hz

ACUF Freqency

ACUF Time

0.20s

51.4Hz

ACOF Freqency

0.20s

ACOF Time

Password is required when enter into the interface of “Run Param”. Get the password from the supplier if necessary.

Set ACUV Volt, ACUV time and others under the related submenus, and then press “ ” and “ ” to modify, and finally press “ENT” to confirm.

49

iMars grid-tied solar inverters Display panel

Setting item Instruction LCD display

Input Password

0000

Run Param*

Run Param

UV volt 1 OV time 1

UV time 1

OV volt 1

UF Freq 1

UF time 1

115V

ACUV Volt(phase volt)

ACUV Time

00.04s

309V

ACOV Volt(phase volt)

00.02s

ACOV Time

47.99Hz

ACUF Frequency

ACUF Time

00.12s

50.50hz

ACOF Frequency

00.12s

196V

ACUV Volt(phase volt)

ACUV Time

0.19s

ACOF Time

252V

ACOV Volt(phase volt)

ACOV Time

01.90s

49.49Hz

ACUF Frequency

ACUF Time

595s

50.2Hz

ACOF Frequency

ACOF Time

115s

Run Restart Time

060s

OFF

ON

Island protect:on

There are 2 protections under

G83/G59(UK) and PEA(Thailand) standards, and there is only one protection under other grid tied standard.

Set ACUV Volt, ACUV time and others under the related submenus, and then press “ ” and “ ” to modify, and finally press “ENT” t o confirm.

Generally, it is only necessary to set

ACUV and ACUF value for ACUV and

ACUF protection. And it is necessary to set ACOF1 and ACOF2 together for

ACOF protection.

50

iMars grid-tied solar inverters Display panel

6.4.5 System Information

Press “ ” and “ ” in the main interface to select “ System Information ” , and then press “ENT” to view the parameters which is shown in figure 6.8.

System Information

Part No .

Cert . Area

Serial No .

Run Param

Soft Ver

Figure 6.8 System information

The system information include “ product model ” , “ serial No.

” , “ software version ” and “ certificate version

.

S y s t e m V e r

V e r s i o n 1 : V 1 . 0 5

V e r s i o n 2

M C U V e r s i o n

: V 1 . 0 5

: V 1 . 0 5

Figure 6.9 System version

6.4.6 Faults

Press “ ” and “ ” in the main interface to review the fault history, and then press “ENT” to view the sub-menu which is shown in figure 6.10.

F a u l t

1 : A 0 0 5 G r i d u n d e r f r e q

2 : A 0 0 1 I n p u t u n d e r V o l t

3 :

Figure 6.10 Fault information

There are 8 pieces of fault information in the record which is shown in figure 5.10; otherwise it will display “ No Fault!” Refer to section 6.4.2 for more detailed information.

6.4.7 Inverter control

Press “ ” and “ ” in the control interface, and then press “ENT” to view the sub-menu which is shown in figure 6.11.

O n / O f f

C o n t r o l M e n u

F a c t o r y

C l e a r

R e s t a r t

Figure 6.11 Control interface

Refer to the table below for detailed information.

Table 6-5 Inverter control

51

iMars grid-tied solar inverters Display panel

Control item

On/Off control

Restart

Record clear

Restore to factory

O N

O F F

LCD display

O n / O f f C t r l

R e s t a r t

P r e s s E N T t o e x e c u t e .

P r e s s E S C t o c a n c e l .

C l e a r a l l R e c o r d : S u r e ˛

P r e s s E N T t o e x e c u t e .

P r e s s E S C t o c a n c e l .

R e s t o r e t o F a c t o r y

P r e s s E N T t o e x e c u t e .

P r e s s E S C t o c a n c e l .

Instruction

Control the “O n/Off ” through the panel.

Press “ ” and “ ” in the control interface to select the operation. Press

ENT

to ensure the operation and press

“ ESC ” to return.

Restart the inverter through the panel.

And save the all settings and operation record.

Press “ ENT ” to ensure restarting and the inverter will begin to self-inspect or press

“ ESC ” to return.

Press “ ENT ” to ensure clear all records or press “ ESC ” to return.

Record clear

is to clear all setting parameters through the panel, restore to the factory setting and save all history operation records.

“ Restore to factory ” is to clear all setting parameters and history operation records through the panel, restore to the factory setting. Press “ ENT ” to ensure clear or press “ ESC ” to return.

6.4.8 Mode settings

The default mode of series grid-tied solar inverter is “ independent ” . But if the current of solar modules are joined into the inverter as figure 6.12 shows, it is necessary to switch the mode into

“ parallel ” .

The mode 12kW / 15kW /17kW / 20kW / 25kW / 30kW Please refer to section 6.4.4 for detailed setting.

Note

Figure 6.12 “ Parallel ” input mode z Only where there is more than 100V DC voltage input, LCD display working, and

AC switch off, can query and modify the inverter DC input mode via the LCD screen and keypad.

52

iMars grid-tied solar inverters Display panel

6.5 Grid Certification Choice

Power on the inverter by DC input for the first time or after Restore factory settings, it will appear on the LCD screen prompts as follows:

S O L A R I N V E R T E R

I n i t i a l i n g Ă Ă W a i t i n g

> > > > > > >

Waiting a few seconds later, in the LCD screen will appear a list of countries as follows, requiring the user to choose what country of use.

As shown below:

C o u n t r y : U n s e t

Germany

U K

A u s t r a l i a

G r e e c e

D e n m a r k

H o l l a n d

C o u n t r y :

G r e e c e

D e n m a r k

H o l l a n d

U n s e t

C h i n a

T h a i l a n d

Other

Press the

“ ”

or

“ ”

button to navigate the country, press the ENT button to complete the setting.

After determine the location, please follow the user manual required with the proper use of inverter.

The user can change the location through the following ways:

LCD Screen ˖ MENU ė Main Menu: Setup ė Setup Menu: Country ė Country: p

A l a r m

V - p v 1 : 0 0 0 . 0 V

I - p v 1 : 0 0 0 . 0 A h

V - p v 2 : 0 0 0 . 0 V

0 1 . A 0 0 1 MENU

M a i n M e n u

M o n i t P a r a m S e t u p

H i s t o r y

S t a t i s t i c s

S y s t e m I n f o

F a u l t I n f o

A d d r e s s

S e t u p M e n u

D a t e / T i m e

K e y p a d P W D

C a s h / p r i c e

L a n g u a g e

C o u n t r y

C o u n t r y : C h i n a

Germany

UK

G r e e c e

D e n m a r k

A u s t r a l i a H o l l a n d

The user can query the grid certification which has been set through the following ways:

LCD Screen ˖ MENU → Main Menu: System Info → System Information: Cert. Area → Certificate Area p

A l a r m h

V - p v 1 : 0 0 0 . 0 V

I - p v 1 : 0 0 0 . 0 A

V - p v 2 : 0 0 0 . 0 V

0 1 . A 0 0 1 MENU

M a i n M e n u

M o n i t P a r a m

H i s t o r y

S t a t i s t i c s

S e t u p

S y s t e m I n f o

F a u l t I n f o

S y s t e m I n f o r m a t i o n

P a r t N o .

S e r i a l N o .

S o f t V e r

C e r t . A r e a

R u n P a r a m

C e r t i f i c a t e A r e a

A S 4 7 7 7

Comparison Table: Available Countries and their grid certification

53

iMars grid-tied solar inverters Display panel

16

17

18

19

20

21

22

8

9

10

11

12

13

14

15

4

5

6

7

No.

1

2

3

Country

Germany

UK

Australia

Greece

Denmark

Holland

China

Certification

VDE0126& AR-N4105

G83/G59

AS4777

VDE0126

TF321

C10/C11

CQC

Remark

8 Thailand PEA

9 Other VDE0126

Reference Table: Grid Certification and Grid Voltage and Frequency of Some Countries

Three-phase Grid

No. Country Certification voltage frequency

1 Germany

4

5

2

3

6

7

France

Greece

Turkey

Romania

Slovakia

Portugal

VDE0126& AR-N4105 380~400V 50Hz

Poland

Hungary

Switzerland

Austria

Australia

Singapore

New Zealand

Belgium

Luxembourg

Holland

Denmark

AS4777.2&AS4777.3

AS/NZS3100

C10/C11

TF3.2.1

400~415V

380~400V

380~400V

50Hz

50Hz

50Hz

Italy ENEL 400V 50Hz

54

iMars grid-tied solar inverters Monitoring communication

7 Monitoring communication

This chapter describes the communication connection of inverter and monitoring system

(Industrial master, private computers, smart phones and so on).

55

iMars grid-tied solar inverters Monitoring communication

7.1 Standard communication

The standard communication mode of iMars grid-tied solar inverter is RS485 which includes

RS485

and

EXT

ports. The two ports can both communicate with private computers, smart phones and so on. The system monitoring solution are shown as figure 7.1.

Figure 7.1 Monitoring system of inverter

Table 7-1 Pins on inverter instruction

Pin on inverter Definition

1 +5VDC

4 GND

56

iMars grid-tied solar inverters Monitoring communication

RS485

1 4

2 3

1 4

2 3

EXT

4 3 2 1

Figure 7.2 RS485 pin on inverter Figure 7.3 Communication connector

Connection steps:

(1) Weld communication cables to the RS485 terminals of the inverter as figure 7.4 shows;

Ensure the cable corresponds to the pin as table 6-1 shows and the welding is tight enough.

Figure 7.4 Detailed connection

(2) According to Table 7-1, connect the communication connector pinout and the user's device, make sure the connection is correct;

(3) Please download the monitoring software

“ iMars WinExpert

and its operation instruction on www.invt-solar.com.

7.2 Optional communication

The optional communication modes include Ethernet, WiFi, which also need corresponding communication parts and components. All operation parameters of the inverter are output from port “ RS485/EXT ” , and then to the communication devices, finally after convertering, to the monitoring system of upper PC as standard Ethernet, WiFi signal. See figure 7.1.

Table 7-2 Optional accessories

Optional accessories

Ethernet converter

WiFi converter

GPRS converter

ENET converter

Inverter port

RS485/EXT

RS485/EXT

RS485/EXT

RS485/EXT

57

Port of upper PC

RJ45 plug

WiFi signal

GPRS signal

Ethernet port

iMars grid-tied solar inverters Monitoring communication

Please download the connection instruction, operation manual and commissioning tools on website www.invt-solar.com.

Note: the optional accessories are not standard-configured.

7.3 RS485-DRM ports

Table 7-3 RS485-DRM Pins on inverter instruction

Pin on inverter Colour Definition

Figure 7.5 RS485-DRM pin on inverter Figure 7.6 Connection cable

RS485-DRM connection steps:

(1) Weld communication cables to the RS485-DRM terminals of the inverter as figure 7.6 shows;

Ensure the cable corresponds to the pin as table 7-3 shows and the welding is tight enough.

According to Table 7-3, connect the communication connector pinout and the user's device, make sure the connection is correct.

58

iMars grid-tied solar inverters Troubleshooting

8 Troubleshooting

This chapter describes the fault alarm and fault code for quick troubleshooting.

59

iMars grid-tied solar inverters Troubleshooting

Table 8-1 Fault code

Fault

Message code

A

Instruction Fault analysis

A001

A002

A003

A004

A005

Input UV

Bus UV

Grid UV

Grid OV

Grid UF

Input undervoltage

PV1 undervoltage

PV2 undervoltage

Bus undervoltage DC input

AC undervoltage

AC overvoltage

AC underfrequency

Low voltage of the public grid

High voltage of the public grid

Low frequency of the public grid

A006

A007

A009

A011

Grid OF

Clock Fail

Cmd Shut

Grid Loss

AC overfrequency High frequency of the public grid

Clock alarm

Manual stutdown

The public grid disconnects.

Wrong setting

Stop by the operation panel or upper

PC

Check if inverter AC connection is well

E

E001 Input OV Input overvoltage DC input overvoltage

E003

E004

E005

E006

E007

E008

E009

E010

E011

E012

E013

E014

Bus OV

Boost Fail

Bus overvoltage Internal bus voltage

Voltage-boost fault Voltage-boost fault of the inverter

Grid OC AC overcurrent Internal AC overcurrent

OTP Overtemperature Internal overtemperature

Riso Low

IGBT drv

Low isolation impedance

IGBT drive protection

Low isolation impedance of the external port system

IGBT drive protection of the inverter

Int Comm

ILeek Fail

Internal communication fault

Huge leakage current

Master-slave DSP communication disabled

Error of master-slave DSP check bit

Huge leakage current of the system or inverter

Relay Fault Relay fault Internal relay fault

Fan Fail Fan fault Internal fan fault

Internal memory error

Dc inject High DC injection High DC injection during AC output

60

iMars grid-tied solar inverters Troubleshooting

Fault code

E015

E018

E019

E020

Message

OutputShort

Input OC

Incnst

Instruction

Output short-circuit

Fault analysis

Output short-circuit

Input overcurrent DC input overcurrent

Data consistency fault

Inconsistent grid voltage, frequency, leakage current or AC/DC injection

PowerReversed DC power reversed DC power reversed

61

iMars grid-tied solar inverters Troubleshooting

If any problem, please contact with the supplier and provide following information: z Model of the inverter: ; z

Serial No. of the inverter: ; z System üü version 1: ;

üü version 2: ;

üü MCU software version: ; z Fault code: ; z Fault description .

62

iMars grid-tied solar inverters Contact us

9 Contact us

Shenzhen·China

INVT Solar Technology (Shenzhen) Co., Ltd.

Address: Room 504, No. 7 Building, Gaofa Scientific Industrial Park, Longjing, Nanshan District,

Shenzhen, China

Service hotline: +86 400 700 9997

E-mail: [email protected]

INVT group website: www.invt.com

INVT solar website: www.invt-solar.com

63

iMars grid-tied solar inverters Technical parameters

10 Technical parameters

Table 10-1Technical parameters

Three-phase

Model

BG12KTR BG15KTR BG17KTR BG20KTR

Max. DC voltage (V) 1000 1000 1000 1000

Input(DC)

Output(AC)

System

Others

Starting voltage (V)

MPPT voltage(V)

Operation voltage

(V)

MPPT/strings per

MPPT

Max. DC power (W)

Max. input current

(A)

Isc PV(A)

Max inverter backfeed current to the array

DC switch

Max output power

Voltage(V)/ frequency(Hz)

Max. AC current (A)

Maximum output fault current

AC inrush current

Maximum output overcurrent protection(A)

Power factor

Harmonic distortion

Cooling

Maximum efficiency

European efficiency

MPPT efficiency

Protection degree

200

180~800

350 - 800

12500

19x2

21x2

0A

12000

19.3

38.2

98.20%

97.60%

200

180~800

400 - 800

15600

21x2

23.5x2

0A

47.7

98.30%

97.80%

200

180~800

400 - 800

17500

23×2

25.5×2

0A

54

2/1

Optional

300

280-800

450-800

20800

25X 2

27X 2

0A

BG25KTR

1000

300

280-800

480-800

26000

30 X 2

33 X 2

0A

15000 17000 20000

320~460Vac, 50Hz(47~51.5Hz) / 60Hz(57~61.5Hz)

25000

27.3

32 24.1

250A ˈ 41.6ms

Less than 10 A

63.3

-0.80~+0.80(adjustable)

< 3% (rated power ˅

Air cooling

98.30%

97.80%

98.4%

98.0%

99.9%

IP65

40

472A ˈ 11.04ms

Less than 20 A

79.1

98.4%

98.0%

BG30KTR

1000

300

280-800

480-800

31200

33X 2

36X 2

0A

30000

48

95

98.5%

98.0%

Power consumption

Isolation mode

Protective class

Overvoltage category inverter topology

Pollution degree

Operation temperature

Relative humidity

Max. altitude(m)

< 1W

Transformerless

I

AC:III,PV:II

Non-isolated

3

(-25 ć ~+60 ć ) ˈ derate after 45 ć

4~100%, Condensation

<2000 (derate if the altitude ˚ 2000)

Displaying

Systerm language

LED/ LCD, backlit display

English, Chinese, German, Dutch

RS485 (standard); handheld keypad; WiFi (optional) Communication

DC terminal PV-CF-S / PV-CM-S

<50 Noise dB(A)

Installation mode Wall installation

Grid standard

DIN VDE 0126-1-1 ˖ 2013 ˈ VDE-AR-N 4105 ˖ 2011 ˈ DIN VDE V 0124-100 ˖ 2012 ˈ IEC 61727 ˄ IEC62116 ˅ˈ

AS/NZS 4777.2

˖ 2015 ˈ NB/T32004-2013 ˈ IEC 60068-2-1 ˖ 2007 ˈ IEC 60068-2-2 ˖ 2007 ˈ IEC 60068-2-14 ˖

2009 ˈ IEC 60068-2-30 ˖ 2005 ˈ IEC 61683 ˖ 1999 ˈ C10/11 ˖ 2012

Safe certificate /

EMC category

IEC 62109-1 ˖ 2010 ˈ IEC 62109-2 ˖ 2011 ˈ EN 61000-6-2: 2005 / EN 61000-6-3:2007/A1:2011

Input overvoltage protection, input overcurrent protection, DC isolation monitoring, DC monitoring, grounding fault current monitoring, grid monitoring, island protection, short circuit protection, overheating protection

Protection

64

201807(V1.1)

advertisement

Related manuals