Auto Sentry® CPT
Central Payment Terminal
Installation Guide - Version 1.0
Information in this manual is subject to change without notice. The example companies, organizations, products, domain names, email addresses logos, people, places and events depicted herein are fictitious. No association with any real company, organization, product, domain name, email address, logo, person, place or event is intended or should be inferred unless otherwise noted. No part of this manual may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose without the express written permission of Innovative Control Systems, Inc.
ICS and its product trademarks in this manual are trademarks of Innovative Control Systems,
Inc. All other marks are property of their respective owners.
© Copyright 2017 Innovative Control Systems, Inc. | All rights reserved.
Innovative Control Systems, Inc.
1349 Jacobsburg Road
Wind Gap, PA 18091
Phone: 610-881-8000
Contents
Auto Sentry® CPT (Side View) Brick Thickness . . . . . . . . . . . . . . . . . . . . . . . 15
Recommended and Accepted Grounding Methods . . . . . . . . . . . . . . . . . 19
Auto Sentry® CPT - Installation Guide 3 3 Table of Contents
Interior Components Upper-Right Chamber (without tray) . . . . . . . . . . . . . . . . . . . . .31
Auto Sentry® CPT Installation Guide 4 Table of Contents
List of Figures
Figure 16. Upper-right Chamber with Vibration Detector mounted on Center Security Wall. . . . . .32
List of Figures Auto Sentry® CPT Installation Guide 5
Auto Sentry® CPT Installation Guide 6 List of Figures
List of Tables
Auto Sentry® CPT Installation Guide 7 List of Tables
Auto Sentry® CPT Installation Guide 8 List of Tables
CHAPTER 1: Introduction
This document was written for installation technicians and electricians. A thorough understanding of electrical wiring, installation, local regulations, and safety protocols is required.
No prior experience with the Auto Sentry® CPT is required.
Purpose
This guide is provided to assist you during installation of the Auto Sentry® CPT. This guide should be supplied to the electrician prior to the installation of cable and wiring to ensure the Auto
Sentry® CPT system is installed properly. Please read the entire manual before you begin.
Faulty installations are the major cause of system malfunctions. The Auto Sentry® CPT system must be installed exactly as described in this manual to ensure its reliability and proper operation.
WARNING:
Failure to properly install the Auto Sentry® CPT system will void the warranty and could result in serious injury or death.
Many of the features you will find in the Auto Sentry® CPT system were integrated at the request of current car wash operators. We welcome your feedback and want to assure you that ICS will always remain the best in the industry in car wash controller and management systems.
By reading the information and performing the procedures in this manual you should be able to:
Install the Auto Sentry® CPT system level wiring
Install the Auto Sentry® CPT communications wiring
Related Documents
The
Auto Sentry® CPT User Manual is available for further reference.
Rules for Installation
WARNING:
Imminent danger exists of electrical shock if the terminal is not installed by a certified electrical contractor.
Auto Sentry® CPT Installation Guide 9 Introduction
ALL wiring must meet local regulations.
Wiring can be contained in rigid PVC conduit or metal conduit.
High-voltage (AC) and low-voltage (DC) must not be combined in a common conduit, junction box, or wire trough.
Power for the Auto Sentry® CPT and any peripherals must come from the ICS Power
Distribution Box or dedicated UPS, as supplied by ICS.
Power for the Auto Sentry® CPT unit is conditioned from the ICS Power Distribution Box. The heat exchanger power is not conditioned.
Examine all boxes and cartons before disposing of them for manuals, cables, connectors, and other miscellaneous parts.
Training and Support
Contact ICS for additional training and support.
Warning Markings
The symbol below (on equipment and hardware) indicates you should consult accompanying documentation before proceeding.
!
WARNING:
Consult accompanying documentation before proceeding.
Inspection and Cleaning
Wipe exterior of unit with damp cloth to clean. Do not use chemicals or cleaning agents.
Preventative maintenance involves an inspection of the Auto Sentry® CPT unit daily for loose connections or damage by untrained or skilled operator.
Introduction Auto Sentry® CPT Installation Guide 10
CHAPTER 2: Site Planning
Careful planning for the layout of the site will help eliminate possible problems with the start-up of your system and will ensure continued, reliable system operation.
All wiring must be installed and used in accordance with local regulations.
Location
The Auto Sentry® CPT unit has been designed to operate in an outdoor environment.
The unit itself contains three hinged-panel doors. The unit must be located with enough clearance for the doors to open easily without interfering with access.
The unit must be located so that conduit connections can be easily made and the internal components can be accessed.
Your wash and vacuum layout may be different from the drawings included in this installation guide.
Auto Sentry® CPT Installation Guide 11 Site Planning
Cable Plan
THIS DRAWING IS ONLY INTENDED TO SHOW THE CONDUITS NECESSARY, AS A MINIMUM, TO
COMPLETE THE INSTALLATION OF THE ICS EQUIPMENT PURCHASED. THIS DRAWING IS NOT TO
SCALE.
-- ADDITIONAL CONDUITS MUST BE INSTALLED FOR ALL OTHER NON-ICS EQUIPMENT SUCH AS
LIGHTS, MENU SIGNS, CAMERAS, INTERCOMS, AND THE LIKE.
-- ONLY WIRING FOR ICS EQUIPMENT MAY BE RUN IN THE CONDUITS INSTALLED FOR ICS
EQUIPMENT.
ICS POWER
DISTRIBUTION BOX
MAIN SERVICE
ELECTRICAL PANEL
&21'8,7
AUTO SENTRY
CPT
LOW VOLTAGE
CONDUIT
HIGH VOLTAGE POWER CONDUIT
LOW VOLTAGE CONDUIT
JUNCTION BOX
Figure 1. Cable Plan
Auto Sentry® CPT Installation Guide 12 Site Planning
Auto Sentry® CPT Measurements (Front View)
Auto Sentry CPT
31 1/2”
Block Wall
21”
31 1/2”
57”
10 1/2”
16 1/2” 15”
33”
Pavement
Figure 2. Auto Sentry® CPT Measurements (Front View)
Auto Sentry® CPT Installation
The Auto Sentry® CPT was designed to be installed securely in an existing block wall, where on the other side of the wall, you can access the Auto Sentry® CPT from a room with a locked door. The
hole needs be cut using the measurements in Figure 3.
Auto Sentry® CPT Installation Guide 13 Site Planning
1
Cut the hole in the block wall according to the rough opening measurements in Figure 3.
32 1/2”
22”
Cut Hole
17”
11”
15 1/2”
32 1/2”
1.875 Thick
43 1/2”
32 1/2”
Figure 3. Cut Hole Measurements in block wall for Auto Sentry® CPT
2 Snugly place the Auto Sentry® CPT unit in the hole in the wall.
3 From the back of the Auto Sentry® CPT, bolt the Auto Sentry® CPT to the block wall.
4 Cut the face of several blocks at 1.875” thickness. These blocks will be used as a veneer to cover the base of the Auto Sentry® CPT and cover the CPT around the Note Dispenser so it appears to have been built in the block wall.
See Figure 4, “Auto Sentry® CPT Brick Thickness”.
5 A mason can set these blocks all around the bill dispenser return drawer on the base of the
Auto Sentry® CPT.
6 Install the front plastic cover on the front of the Auto Sentry® CPT.
For more information on wiring your Auto Sentry® CPT:
Auto Sentry® CPT Installation Guide 14 Site Planning
See Figure 3, “System Wiring,” on page 21.
See Figure 4, “Communications Wiring,” on page 25.
Auto Sentry® CPT (Side View) Brick Thickness
Front of the
Auto Sentry® CPT
This drawing is the
Side View of the
Auto Sentry DCPT with open doors in the rear.
Figure 4. Auto Sentry® CPT Brick Thickness
1.875” Brick Thickness
Auto Sentry® CPT Installation Guide 15 Site Planning
Auto Sentry® CPT Swing Door Clearance (Top View)
FP
³;´%$6(:,7+'2256
&/
2)23(1
63$&(
Figure 5. Swing Door Clearance (Top View)
&/
2)$872
6(175<&37
%/2&.:$//
Auto Sentry® CPT Installation Guide 16 Site Planning
Auto Sentry® CPT Power Requirements
Electrician must provide a dedicated 120 V AC, 20 Amp circuit to the ICS Power Distribution
Box. This dedicated circuit must supply the UPS, and then provide conditioned power to the
Auto Sentry® CPT.
Electrician must provide a separate dedicated 120 V AC, 15 Amp circuit to the Auto Sentry®
CPT to power the heat exchangers.
The unit must be properly grounded. See “Grounding” on page 19 for more information.
When mounting the unit, minimum clearances must meet local regulations.
Auto Sentry® CPT Wiring Guidelines
When running wires to and from the Auto Sentry® CPT unit, follow these guidelines:
For an existing site, use a hole saw to drill new conduit holes through steel base if necessary.
File and tape edges of new holes before affixing conduit.
Run conduit and wire up through steel base into the unit.
Use wiring ties and wire clamps inside unit to contain wires.
Cable Sizing
Each installation will vary depending on what type of cable is used, the load (Amps), how long is the cable run, what type of building construction, the environment, and how many other cables are installed. Therefore, cable sizing would be decided and calculated to be site installation specific. To determine cable size needed, the electrical contractor will refer to the electrical regulations book and make a decision for the best installation.
Conduit Wiring Guidelines
All conduit must be rigid PVC or metal.
All conduit runs should meet local and national regulations. Conduits shall be properly connected and securely fastened to the boxes with listed conduit hubs, and should be tightened to the torque specs of the manufacturer.
High-voltage (AC) and low-voltage (DC) must not be combined in a common conduit, junction box, or wire trough.
Auto Sentry® CPT Installation Guide 17 Site Planning
Dimensions, Measurements, and Ratings Specifications
Table 1: Dimensions, Measurements, and Ratings Specifications
Dimension
Width
Height
Depth
Weight
Operating Temp.
31 1/2''
31 1/2”
29''
350 lbs.
Amount
—
—
—
—
—
Frequency
Supply Voltage
Max. Amps.
IPX Rating
-20 °F to 140 °F
-29 °C to 60 °C
50/60 Hz
120 - 240 V AC
10 Amps @ 120 V AC
NEMA 4X
—
Notes
Intended for permanently connected supply.
System and Heat Exchanger
Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hosedirected water; and that will be undamaged by the external formation of ice on the enclosure. Including protection against corrosion.
Auto Sentry® CPT Installation Guide 18 Site Planning
Grounding
The Auto Sentry® CPT and peripheral equipment must be properly grounded.
Recommended and Accepted Grounding Methods
Proper system grounding is an extremely important part of the system installation. Grounds for all system devices should be wired to the main service electrical panel ground bus bar which, in turn, should be grounded to a ground rod. A conduit ground does not provide a sufficient ground. It is recommended that the neutral and ground bus bars be bonded together when it is not prohibited by local regulations.
The universal ground symbol identifies the grounding terminal located in the upper-left chamber, bottom left side near terminal blocks. A second ground is marked and located in the base, bottom-left side. This is the dedicated 120 V line for the heat exchanger.
WARNING: Ground wire must be connected to the ground terminals. Failure to properly ground the unit could result in unit failure and/or bodily injury.
IMPORTANT: Improper grounding will void equipment warranty.
Auto Sentry® CPT Installation Guide 19 Site Planning
Wire Gauge and Conduit Size
When planning the orientation of the wiring runs, follow the applicable ICS wiring diagrams and consider the layout of the components at the site.
To determine conduit size needed, see Table 2.
Table 2: Max. Number of Wires (THHN) in a Given Conduit Size
—
AWG 14
13
½
24
¾
39
1 1 ¼
69
1 ½
94 154
2
AWG 12
10 18 29 51 70 114
AWG 10
6 11 18 32 44 73
AWG 8
3 5 9 16 22 36
AWG 6
1 2 6 11 15 26
AWG 4
1 1 4 7 9 16
AWG 3
1 1 3 6 8 13
AWG 2
1 1 3 5 7 11
AWG 1
1 1 1 3 5 8
57
35
29
25
18
—
—
160
79
3
51
37
22
19
2 ½
—
164
104
16
12
Auto Sentry® CPT Installation Guide 20 Site Planning
CHAPTER 3: System Wiring
The Auto Sentry® CPT main power input is wired to the terminal block in the rear, upper-left chamber. The heat exchanger power input is also located in the upper-left chamber.
The CPT has the ability to link with differing types of wash equipment and vacuum, for example,
Wash Bays, Vacuums, and small commercial auto car wash (In-Bay). The wiring diagrams will vary.
See the specific System Installation Guide drawings that you received from your sales representative.
Auto Sentry® CPT Installation Guide 21 System Wiring
Power and Low Voltage Wiring Layout
POWER CABLE PLAN
ICS AUTO SENTRY CPT
with ICS Power Distribution Box
*** THIS DRAWING IS MEANT ONLY TO SHOW THE TYPES OF CABLES THAT MUST BE RUN BETWEEN PIECES OF ICS EQUIPMENT. THIS
DRAWING IS NOT TO SCALE. THE INDIVIDUAL WHO RUNS THE CABLING MUST ENSURE THAT AMPLE CABLE IS AVAILABLE AT EITHER END TO
FACILITATE TERMINATION. THE TERMINATION POINTS OF THE CABLES ARE NOT SHOWN ON THIS DOCUMENT. ***
E
DSL / CABLE MODEM
CONNECTION POINT
DSL /HIGH SPEED
CABLE MODEM
ICS SUPPLIED
UPS CABLES
SITE’S MAIN SERVICE
ELECTRICAL PANEL
UPS 2200 BATTERY
BACKUP
SUPPLIED BY ICS
ICS POWER
DISTRIBUTION BOX
ROUTER
SWITCH
C
SITE SUPPLIED CABLE FROM A 20 AMP
BREAKER IN THE SITE’S MAIN ELECTRICAL
SERVICE PANEL PROVIDING AN INDIVIDUAL
LINE, NEUTRAL, AND GROUND TO THE ICS
POWER DISTRIBUTION BOX.
3 – 12 GA THHN, SITE SUPPLIED, FROM A DEDICATED 15 AMP BREAKER IN THE
SITE’S MAIN ELECTRICAL SERVICE PANEL PROVIDING AN INDIVIDUAL LINE, NEUTRAL,
AND GROUND TO THE AUTO SENTRY CPT FOR THE HEAT EXCHANGERS.
TERMINATIONS MUST BE COMPLETED AS PER THE PROVIDED AUTO SENTRY CPT
POWER TERMINATION DIAGRAM. THE GROUND WIRE MUST BE TERMINATED ON
THE MECHANICAL GROUND LUG IN THE ELECTRICAL PANEL.
+LJK9ROWDJH&RQGXLW
/RZ9ROWDJH&RQGXLW
ICS SUPPLIED
14/3 SHIELDED D
A
ICS SUPPLIED
CAT 6 SHIELDED
F G
AUTO SENTRY CPT
Figure 6. Power Layout
Auto Sentry® CPT Installation Guide 22 System Wiring
32:(5&$%/(6&+('8/(
$8726(175<&37
ZLWK,&63RZHU'LVWULEXWLRQ%R[
*** NOTE: The wiring and terminations are the responsibility of the owner, electrician, and/or supplied contractor. Please have an electrician and/or owner supplied contractor complete all of the site’s wiring installation and terminations prior to the ICS technician coming on site. All permanent site wiring connections must be performed by a licensed electrician that must comply with all local and national codes.***
.(<
$
:,5(7<3( 3529,'('
%<
7(50,1$7,21
/2&$7,216
7(50,1$7('
%<
*$7++1(/(&75,&,$1 )520&37720$,16(59,&((/(&75,&$/3$1(/$03%5($.(59$& (/(&75,&,$1
& 6+,(/'('
'
(
6+,(/'('
6+,(/'('
6+,(/'('
)
*
&$76+,(/'('
&$76+,(/'('
,&6
,&6
)5200$,16(59,&((/(&75,&$/3$1(/727+(,&632:(5
',675,%87,21%2;$03%5($.(59$&
)520&3772,&632:(5',675,%87,21%2;$03%5($.(59$&
(/(&75,&,$1
(/(&75,&,$1
,&6
,&6
)520,&632:(5',675,%87,21%2;72836%$&.83%$77(5<9$&(/(&75,&,$1
)520836%$&.83%$77(5<72,&632:(5',675,%87,21%2;9$&(/(&75,&,$1
,&6
,&6
)5206:,7&+72&371(7:25.3257
)5206:,7&+72&37)25&5(',7&$5'5($'(521/<3257
(/(&75,&,$1
(/(&75,&,$1
127(6 ALL WIRING FOR ICS EQUIPMENT TO BE RUN BY AN ELECTRICIAN AND MUST BE A SINGLE CABLE FROM POINT TO POINT.
SPLICING OF WIRES IS NOT ALLOWED.
Figure 7. Power Cable Schedule
Auto Sentry® CPT Installation Guide 23 System Wiring
AC Power Terminations
AUTO SENTRY CPT MAIN POWER INPUT
Located in the CPT’s Rear, Upper Left Door
G N L
CABLE FROM 15 AMP CIRCUIT
BREAKER WITHIN THE ICS POWER
DISTRIBUTION BOX TO THE UPS
800 BACKUP BATTERY
10
A
Auto Sentry CPT
Located in the CPT’s Rear
Upper Left Door
ICS SUPPLIED
14/3 SHIELDED
SITE SUPPLIED 3 – 12 GA. THHN CABLE
FROM A 15 AMP BREAKER IN THE SITE’S
MAIN ELECTRICAL SERVICE PANEL
PROVIDING AN INDIVIDUAL LINE,
NEUTRAL, AND GROUND TO THE POWER
TERMINAL BLOCK FOR THE HEAT
EXCHANGERS.
GROUND
NEUTRAL
LINE
Figure 8. AC Power Terminations
AC Power Terminations
AUTO SENTRY CPT
HEAT EXCHANGER POWER INPUT
Located in the CPT’s Rear
Upper Left Door
G N L
10
A
WIRE COLOR KEY
WHITE = NEUTRAL
BLACK = LINE
GREEN/YELLOW = GROUND
Figure 9. AC Power Terminations Photo
Auto Sentry® CPT Installation Guide 24 System Wiring
CHAPTER 4: Communications Wiring
This section describes wiring for RS-422 and RS-485 communications.
Installation Requirements
All peripheral equipment connected to the RS-232 ports must be Listed, have an Electronics
Industrial Association (EIA) standard RS-232 communications protocol and not be installed over a hazardous location.
RS-232 communication must not exceed 100 feet. RS-232 communication wires must be in a separate PVC conduit from any AC wires.
Communications equipment signal wires must also be run in separate rigid PVC or metal conduit, separate from any power conduits.
Low Voltage Layout
%$6(7:$//3/$7(
$76(59(5&20387(5:,7+7+(
$028172)3257672$&&2002'$7(
7+(727$/$028172)1(7:25.:,5(6
&37
%
,&66833/,('
&$76+,(/'('
$
Figure 10. Low Voltage Wire Layout
Auto Sentry® CPT Installation Guide 25 Communications Wiring
1(7:25.&20081,&$7,216$1'&21752/:,5,1*
,'(17,),(5 :,5(7<3( 3529,'('
%<
$
%
&$76+,(/'('
&$76+,(/'('
7(50,1$7,21
/2&$7,216
7(50,1$7('
%<
,&6
,&6
)520%$6(7:$//3/$7(72&37)251(7:25.
(/(&75,&,$1
)520%$6(7:$//3/$7(72&37)25&$5'5($'(5 (/(&75,&,$1
127( ALL WIRING FOR ICS EQUIPMENT TO BE RUN BY A REPRESENTATIVE OF THE CAR WASH AND MUST BE HOME-RUNNED
FROM POINT TO POINT. SPLICING OF WIRES IS NOT ALLOWED.
Figure 11. Low Voltage Wire Schedule
Port Assignments
Device
—
Bill Acceptor
Coin Acceptor
Bill Dispenser
SIO Board
Touch Screen
—
Receipt Printer
Barcode Reader
Coin Hoppers
Table 3: Port Assignments
Port Type and Location
COM Port 1
COM Port 2
COM Port 3
COM Port 4
COM Port 6
USB
USB
USB
USB (Virtual COM Port 5)
SIO Board
Auto Sentry® CPT Installation Guide 26 Communications Wiring
CHAPTER 5: Parts Identification
This chapter provides details on identifying the Auto Sentry® CPT exterior and interior components and locations. Both exterior and interior components, wires, accessories, and the more items are available for purchase or reorder.
The Auto Sentry® CPT also includes plastic panels to fit the exterior of the metal unit. Panels may be purchased separately.
NOTE:
If you cannot find the part in the following diagrams, contact ICS sales for more information: 800-246-3469
Auto Sentry® CPT Installation Guide 27 Parts Identification
Exterior Components Chip and PIN
The Auto Sentry® CPT exterior components for the Chip and PIN are displayed in Figure 12.
Figure 12. Exterior Components Auto Sentry® CPT
1
2
#
4
5
ICS Part Number
AS2TOUCH15Z2
CPMOPINPAD
ASPRHEC
ASSPEAKER
15" touch screen.
PIN pad
Description
3 CPLECARDREADUS Moneris card reader assembly.
USB receipt printer.
Speaker for the Auto Sentry.
# ICS Part Number Description
– BARCODERDR
OPTIONAL (not shown)
Barcode reader. (Optional and additional fees apply.)
– BARCODEHOUSWEDG Barcode wedge. (Optional and additional fees apply.)
– BARCODEHOUSING Barcode housing. (Optional and additional fees apply.)
– CAMERAASSM1 Camera assembly. (Optional and additional fees apply.)
6
7
8
CPMOCONTREADUS MonerisMoneris Contactless reader.
AS2COINACC
AS3BILLACCU
9 AS2COINACC
10 AS2COINFLIP
Coin acceptor.
Bill acceptor, upstacker.
Coin return cup.
Coin return cup with flip door.
11 AS2BILLDISPFLIP Bill return cup with flip door.
Table 4: Exterior Components for the
Auto Sentry® CPT Installation Guide 28 Parts Identification
Interior Components Upper-left Chamber Chip and PIN
Figure 13. Interior Components Upper-left Chamber Chip and PIN
Auto Sentry® CPT Installation Guide 29 Parts Identification
# ICS Part Number
1 AS2TERMB
Description
Terminal blocks. (not shown)
# ICS Part Number
6 AS2PWRC
AS2TERMBRK10
AS2TERMBLOCK-
GND
AS2TERMBLOCKW
10-Amp fuses. US.
(2 or 3) Terminal block, ground.
(2) Terminal block, AC, white.
2 CPMOCONTREADUS Contactless Tap N Go reader.
7
8
AS2COINACC
ASEMIFILTER
9 H/CCONTROLBD
3 CPMOPINPAD
4 AS3BILLACCU
PIN pad.
Bill acceptor, upstacker.
10
11
ASPSSWITCH
ASPUSHBUT
5 CPMOCARDREADUS Card reader assembly with cable.
12
Table 5: Interior Components Upper-left Chamber Chip and PIN
AS3BILLACCU
Description
P ower supply
+5 +12 +24 +36 V DC
Coin acceptor.
EMI filter for AC V.
Heater/cooler control board.
Power switch, illuminated.
Push button for service access.
Bill acceptor, upstacker.
Auto Sentry® CPT Installation Guide 30 Parts Identification
Interior Components Upper-Right Chamber (without tray)
Figure 14. Interior Components Upper-Right Chamber
# ICS Part Number Description # ICS Part Number
1 AS3DISPASSM1
2 AS2TOUCH15ZCNCD
3 ASPRHEC
4 AS3ENCCRDC
5 AS3MB170WN7
Table 6: Interior Components
Secure Heavy Duty Touch
Screen
Touch Controller Card.
Receipt printer.
Coin return cup.
Mother board.
6
7
8
AS3ENCH-
CHAINBKT
AS2CHAIN
ASSPEAKER
9 ASBSIO
10 AS3DRSW
Bracket.
Description
Coin drawer cable chain.
Speaker.
SIO board.
Door Switch (2 pieces)
Auto Sentry® CPT Installation Guide 31 Parts Identification
Interior Components Upper-Right Chamber (with tray)
Figure 15. Upper-right Chamber with Tray
2
Figure 16. Upper-right Chamber with Vibration Detector mounted on Center Security Wall
Auto Sentry® CPT Installation Guide 32 Parts Identification
#
1
ICS Part Number
COIN HOPPERS
ASCOINHOP25
ASCOINHOP01
ASCOINHOP05
ASCOINHOP100
ASCOINHOP25
Description
Coin Hopper for
0.25 denominations.
Coin Hopper for
0.01 denominations.
Coin Hopper for
0.05 denominations.
Coin Hopper for
1.00 denominations.
Coin Hopper for
0.25 denominations.
# ICS Part Number
3 VIBRATIONSEN
VIBRATIONSE-
NASSM
VIBRATIONSE-
NASSM
2 Coin Hopper Tray
Table 7: Upper-right Chamber Coin Hoppers and Vibration Detector
Description
Electronic Vibration Detector
Only
Electronic Vibration Detector
System Kit
Electronic Vibration Detector
System Kit
Auto Sentry® CPT Installation Guide 33 Parts Identification
Rear Door Components
Figure 17. Rear Door Components
# ICS Part Number Description
1
ASDRLOCK
ASDRKEY
Door lock bezel.
Door lock.
Door lock key. (not shown)
2 AS3HEATCOOL-1
Table 8: Rear Door Components
Heat exchanger assembly.
Auto Sentry® CPT Installation Guide 34 Parts Identification
Security Locks
Figure 18. Security Locks in Upper Chambers
# ICS Part Number Description
1
2
AS3ENCCFRMDBLHDL
AS3ENCCFRMSGLHDL
Double security lock frame.
(Top of CPT head)
Single security lock frame.
(Bottom of Right Chamber)
4 AS3ENCBUSHHDL
5 AS3ENCCFRMDBLHDL
Bushing
Bolt
6 AS3ENCHBLKHDL Block (Not Shown. Block is behind the
Table 9: Security Locks in upper chambers
Auto Sentry® CPT Installation Guide 35 Parts Identification
Figure 19. Security Lock Frames, Interior Base
Auto Sentry® CPT Installation Guide 36 Parts Identification
Figure 20. Bushing and Bolt
ICS Part Number Description
1
2
AS3ENCFRMBSDL
AS3ENCBUSHBSDL
Single Lock frame. (Base of CPT)
Bushing.
3 AS3ENCBLTBSDL Bolt.
AS3ENCBLKBSDL Block (Not Show. Block is behind Security
Lock Frame. See #1 in Figure 19.)
Table 10: Locks Figure 19 and Figure 20
Auto Sentry® CPT Installation Guide 37 Parts Identification
Base of CPT
Figure 21. CPT Interior Base
ICS Part Number Description
1 AS3DRSW Door switch. (Includes two pieces for complete switch.)
2
3
ASPUSHBUT
AS3HEATCOOL-1
Service screen button.
Heat exchanger.
4
Security Door Locks. “Security
Table 11: Auto Sentry CPT Interior Base
Auto Sentry® CPT Installation Guide 38 Parts Identification
Base of Auto Sentry CPT
Figure 22. Base of Auto Sentry CPT without bill dispenser
Auto Sentry® CPT Installation Guide 39 Parts Identification
Figure 23. Base with Gen Mega Bill Dispenser
ICS Part Number Description
1
2
PWRSUP24V
AS2CBL61
Power Supply for the Heat Exchangers.
24 Volt (Low Voltage) power cable for the heat exchangers.
3 BDGENMEGADUAL Gen Mega Bill Dispenser Single Only.
Table 12: Base of Auto Sentry® CPT with Bill Dispenser Tray
Auto Sentry® CPT Installation Guide 40 Parts Identification
Figure 24. Gen Mega Single Bill Dispenser Cable Bracket
Auto Sentry® CPT Installation Guide 41 Parts Identification
Plastic Panel Identification
The Auto Sentry® CPT includes plastic panels. The following drawings identify the part numbers for each panel.
Front View
Figure 25. Front View
ICS Part Number
1 AS3FP
2 DECALASCUSTOM
Table 13: Front View
Description
Front panel.
Decals for payment area.
Auto Sentry® CPT Installation Guide 42 Parts Identification
Index
A
AC power terminations
AS2BILLDISPFLIP
AS2CBL61
AS2CHAIN
AS2COINFLIP
AS2TERMBLOCKGND
AS2TERMBLOCKW
AS2TERMBRK6
AS3FP
AS3HEATCOOL
ASDRLOCK
ASPRHEC
ASSPEAKER
B
C
COM cable termination diagram
installation requirements
Conduit sizing
D
Dimensions
E
Electronics industrial association
F
Frequency
G
Gate, auto sentry control box
H
H/CCONTROLBD
I
L
Location
Low voltage wire schedule
O
P
side chamber, empty
upper right chamber with tray
Plastic panel identification
Power requirements
R
S
Server area detail
Site layout
Auto Sentry® CPT Installation Guide 43 Index
Supply voltage
T
W
Warranty voiding
Wiring
Auto Sentry® CPT Installation Guide 44 Index
Document Change History
Table 1: Document Change History
Document
Version
Date
1.0
2/5/2018
Contributor Initials Description
WS, KK, KK, BM, TR First release in US. UK documentation was released first.
45