Swegon REACT Ma Instructions for use
Swegon REACT Ma gives you the ability to measure the supply and extract air flow in ventilation ducts. It is a valuable tool for anyone who wants to optimize the performance of their ventilation system. It is important to install the device correctly, following the instructions provided in the manual. This will ensure that the device is functioning properly and providing you with accurate readings. The device is equipped with an actual value signal output, which can be used to connect the device to a controller or other device for further processing of the data. The device is also equipped with a Modbus interface, which allows you to communicate with the device using a computer or other device. This can be useful for monitoring the device's status, changing its settings, or retrieving data.
广告
广告
REACT
Ma
Instructions for Use
Symbol key
Symbols on the machine.
This product complies with applicable EU directives
Symbols in this user manual
Warning/Caution!
Application area
The product is a measurement unit designed for comfort ventilation indoors. The product is used to measure supply and extract air flow in ventilation ducts.
The product may not be used for anything other than its intended use.
General
Read through the entire instructions for use before you install/use the product and save the instructions for future reference. It is not permissible to make changes or modify this product other than those specified in this document.
The packaging contains the following items:
1 x REACT M
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment for the work in question, in the form of gloves, respirators and protective glasses during handling, installation, cleaning and service/maintenance.
Electrical safety
Permitted voltage, see “Electrical data”. It is not permissible to insert foreign objects into the product’s contactor connections or the electronics's ventilation openings; risk for short circuiting.
24 V isolation transformer to be connected should comply with the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product and the power supply source.
Disconnect the power supply when working on products that are not required to run in production.
Always follow the local/national rules for who shall be permitted to carry out this type of electrical installation.
20201117
Art. 1546067
Handling
• Always use appropriate transport and lifting devices when the product is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring tube.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry regulations.
• Install the product so that it is not accessible by unauthorized persons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection hatch must be located so that the product is accessible for inspection.
• If the product is mounted so that it is possible to gain access to the inside of the product, it must be supplemented with appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product must be insulated on the outside against condensation.
• For installation, the accessory FSR is recommended.
• The product can be installed position-independent.
• It is recommended to mount the product so that the product’s display is visible.
• The product must be laid down prior to installation so that it cannot fall over.
• Check to make sure that the product does not have any visible defects.
• Check that the product is properly secured after it has been installed.
• Use the product’s eyes to secure the cables with cable ties.
• Check that all cables are properly secured in place after installation.
• Check that the actuator/controller is properly mounted in place.
The document was originally written in Swedish
REACT M
Installation, torque, dimensions and weights
Circular design
Flow range
Min.
Max=Vnom *) 1.
100 220 50 200 0.8
5
125 220 50 225 0.9
9
18
32
90 324
147 529
160 220 50 260 1.1
16 58 254 914
200 220 50 300 1.2
25 90 404 1454
250 220 50 350 1.4
40 144 658 2369
315 220 50 415 1.7
63 227 1054 3794
400 220 50 500 2.1
102 367 1732 6235
500 230 50 600 2.5
164 590 2670 9612
630 230 50 730 3.0 300 1080 4174 15026
*) Vnom at 250 Pa in pressure reading.
* Installed according to the instructions
Installation – all designs
• The product’s air flow measurement requires a straight duct section as per the installation figures.
• In unfavourable conditions before or with disruption, the product’s tolerances cannot be guaranteed.
• Instructions for Use are supplied with the product on delivery, but can also be downloaded from www.swegon.com.
Installation – circular version
• Installation is position dependent.
• Can be installed horizontally or vertically.
5
8
13
20
32
2
3
2
2
A
1. REACT M
2. FSR Clamp
3. Sound attenuator
2.
3 * .
4.
5.
6.
A
210
Figure 1. Requires a straight duct section of 3 x Ø for sound attenuators with baffle or centre body.
210
1
1. REACT M
2. FSR Clamp
Figure 3. Straight duct section requirements, circular ducts, quantity Ø before the product:
Figures 1-5 require no straight duct section (figure 3 * illustrates the T piece with cleaning hatch).
Figure 6 requires a straight duct section before the product equivalent to 4 x the diameter of the duct.
80
100
65
36
0°
30
C
Ød
B B
210
Figure 2. Installation in the duct system. The ducts must be firmly fixed to the frame of the building on each side of REACT M.
Figure 4. Dimensions (mm), REACT M circular. The damper can be installed at an optional angle.
2
Swegon reserves the right to alter specifications. 20201117
REACT M
Rectangular design
Min
Flow range
Max=Vnom *) l/s m 3 /h l/s m 3 /h
200 x 200
300 x 200
400 x 200
500 x 200
1000 x 400
1200 x 400
1400 x 400
1600 x 400
500 x 500
600 x 500
700 x 500
800 x 500
1000 x 500
1200 x 500
1400 x 500
1600 x 500
600 x 600
700 x 600
800 x 600
1000 x 600
600 x 200
700 x 200
800 x 200
1000 x 200
300 x 300
400 x 300
500 x 300
600 x 300
700 x 300
800 x 300
1000 x 300
400 x 400
500 x 400
600 x 400
700 x 400
800 x 400
1200 x 600
1400 x 600
1600 x 600
700 x 700
800 x 700
1000 x 700
1200 x 700
1400 x 700
*) Vnom at 250 Pa in pressure reading.
* Installed according to the instructions
6.4
7.0
7.4
8.5
7.7
8.7
9.7
10.7
5.3
5.7
6.3
6.7
7.3
8.3
9.2
10.2
7.9
8.9
9.9
11.0
9.5
10.5
11.6
7.4
4.9
5.3
5.9
6.4
5.1
5.7
6.6
4.4
3.4
3.8
4.3
4.8
4.3
4.8
5.3
6.2
2.5
3.0
3.4
3.9
857
1028
1200
1371
618
722
825
1031
429
514
600
686
682
819
955
1092
1237
1443
1649
844
964
1205
1446
1688
341
409
478
546
355
406
508
273
152
203
254
305
200
233
267
333
67
100
133
167
3085
3702
4319
4936
2227
2598
2969
3711
2457
2948
3439
3931
1543
1851
2160
2468
4453
5195
5937
3038
3472
4339
5207
6075
1279
1462
1827
983
1228
1474
1720
1965
720
840
960
1200
548
731
914
1096
240
360
480
600
1897
2845
3793
4742
24391
29269
34147
39025
17602
20536
23470
29337
19421
23306
27190
31074
12195
14634
17073
19513
35204
41072
46939
24014
27445
34306
41168
48029
10113
11557
14447
7769
9711
11653
13595
15537
5690
6638
7586
9483
4334
5779
7223
8668
527
790
1054
1317
6775
8130
9485
10840
4890
5704
6519
8149
5395
6474
7553
8632
3388
4065
4743
5420
9779
11409
13039
6671
7624
9530
11435
13341
2809
3210
4013
2158
2697
3237
3776
4316
1581
1844
2107
2634
1204
1605
2006
2408
77
90
103
129
107
129
150
171
54
64
75
86
85
102
119
136
121
151
181
211
155
180
206
105
43
51
60
68
44
51
63
34
19
25
32
38
25
29
33
42
8
12
17
21
Installation – rectangular design
Dimension B in the figure and table below is found in the table “Rectangular design” to the left.
• Installation is position dependent.
• Can be installed horizontally or vertically.
Straight section before REACT M in rectangular ducts
Type of disruption
One 90° bend
T piece
E (m
2
=5%)
E = 3 x B
E = 3 x B
E (m
2
=10%)
E = 2 x B
E = 2 x B
1
1xB
1. Controller/Actuator always on the side of the rectangular damper.
E = Straight section.
W = Width, duct.
H = Height, duct.
Figure 5. Straight section requirements, rectangular ducts.
Straight duct section before/after REACT M – sound attenuator with baffle
3
2
1
20
H
20
250
1xB
1xB
1. = Rectangular REACT M
2. = Straight duct ≥ 3xB.
3. = Sound attenuator with baffle.
Figure 6. Straight duct section requirements, rectangular REACT
M and sound attenuator with baffle. Installation with a straight duct section applies to both the supply air and the extract air.
20 B 65
65
Figure 7. Dimensions, REACT M rectangular.
20201117 Swegon reserves the right to alter specifications.
3
REACT M
Connections
1-2 – Supply voltage
1-4 – Actual value signal (U)
A-B – Modbus
For further calculations of U see the formulas page 7.
Load on output 4: max. 0.5 mA
24 V AC/DC
0..10/(2..10) V
Handling
T est
1
2
Mode
Test
24
3
I/s
Test
I/s
Test m /h
1 2 4 A B
BK RD OG PK GY
+
U CA CB
+
N L
24 V AC/DC
A + B
Modbus
Figure 8. Wiring diagram.
5 Nm
3 W 5 VA
100s (90°) 95°
250 Pa max. 100 kPa
1 2 4 A B
+
U
0..10 V DC
(2..10 V DC)
3
Test
I/s m /h
Figure 9. REACT interface.
1 – Select the required function by turning the “Function wheel”.
2 – Set the value or select submenus by turning the “Edit” wheel.
3 – The value flashes twice when a new value is accepted.
I/s
Test m /h
Menus
TTest
Flow
I/s
Test
• Switch between l/s and m 3 /h via the edit wheel.
es t
• A “Lit” square on the display indicates the selected unit.
Vmin
I/s
Test m /h
• Select new value for Vmin via the edit wheel.
Te st
I/s
• Vmin should be less than Vmax.
• Vmin is equal to 0/2 V actual value signal.
VnomVnom
ModeMode
AdrAdr
Vmax
I/s
TTestes
VmaxVmax
VminVmi
FlowFlo
Test m /h
• Select new value for Vmax via the edit wheel.
• Vmax should be greater than Vmin.
• Vmax is equal to 10 V actual value signal.
Vmax Vmax
T Testes
Test
I/s
Test
• Turn the edit wheel to choose between the
Mode m /h following modes:
Vnom Vnom
Vmin Vmi n oFF – Test mode switched off, the controller regulates
Flow Flo
123 – Shows the current software version
3 m /h
Test
I/s m /h
Flow Flo
Vnom Vnom
Vmin Vmi
Vmax Vmax
Flo Flow w n
Vmin Vmi
Adr Adr
Mode Mode
Vmax Vmax
Vnom Vnom
T Testes
Adr Adr Vnom
Mode Mode
Mode
Te st m /h
I/s est
Vmax Vmax
Vmin Vmin
Flow Flow
Mode Mode
T Testes
Mode
I/s
Test
• Shows the selected actual value signal
• Switch between 0-10 and 2-10 V via the edit wheel
Adr Adr
Vnom Vnom
Addr
I/s
Test
• Used for Modbus. for particulars on how to use
Modbus, see next page.
Vnom
I/s
Test
• Used for factory configuration.
4
Swegon reserves the right to alter specifications. 20201117
REACT M
How to use Modbus
Modbus tables are available in a separate document (REACT-Modbus-m)
Function
Addr
Description
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It is possible to set the address from 1 till 247. If you turn the value selector to end stop "+", the display will show a "2". This makes it possible to select the second level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Flow Return to previous level
V min
V max
Test
Mode
Addr.
Not used.
Not used.
Not used.
Shows the angle of the rotation (0…255 digital 0....100%)
Used for selecting communication settings for Modbus. See table below.
V nom
Used for setting response delay for the Modbus communication (see separate documents)
18
19 3
20
21
22
23
24
14 4
15
16
17
10
11
12
13
Display number
1 3
6
7
4
5
8
9
2 3
3 3
3 Limited data length per reading of max. 8 addresses
4 Default setting
21
22
23
17
18
19
20
13
14
15
16
9
10
11
12
EEPROM value
0
7
8
5
6
3
4
1
2
Communication rate
1200
1200
1200
2400
2400
2400
4800
4800
4800
38400
1200
2400
4800
9600
19200
38400
9600
9600
9600
19200
19200
19200
38400
38400
Odd
None
None
None
None
None
None
None
Even
Odd
None
Even
Odd
None
Even
Parity
None
Even
Odd
None
Even
Odd
None
Even
Odd
1
1
1
1
1
1
1
2
1
1
1
1
2
2
1
Stop bits
2
1
1
1
2
2
1
1
1
20201117 Swegon reserves the right to alter specifications.
5
REACT M
Trouble shooting
The product does not communicate over Modbus
• Make sure that the product is energized.
• Check the product's Modbus connection.
• Check the product's communication settings.
• Check that the product has the right and unique
Modbus address.
The product shows the incorrect/no air flow
• Make sure that the product is energized.
• Check that the product’s set size corresponds with the physical size.
• Make sure that the product is installed according to the recommended distance to disruptions, see “Installation”.
• Check that there is an air flow.
• Make sure that the product is correctly oriented in terms of air direction. The air flow must follow the instructions on the product.
• Check that the measuring tube is mounted correctly, plus to plus (red), minus to minus (blue).
• Check that the measuring tubes are undamaged and not creased.
• Check with the help of the k-factor and pressure difference between the red and blue measuring tubes that the flow is within the product’s measurement range.
Cleaning
Ideally, the product should be cleaned in connection with the cleaning of the rest of the ventilation system.
Cleaning of electrical components
• If needed, use a dry cloth to clean the components.
• Never use water, detergent and cleaning solvent or a vacuum cleaner.
External cleaning
• If necessary use tepid water and a well-wrung cloth.
• Never use detergent and cleaning solvent or a vacuum cleaner.
Internal cleaning
• When cleaning the ventilation system, the product must be dismantled if there are no cleaning hatches close to the product.
• Cleaning equipment such as whisks and the like must not be fed through the product.
• If necessary remove dust and other particles that can be present in the product.
• Never use detergent and cleaning solvent or a vacuum cleaner.
Service/maintenance
• The product does not require any maintenance, except for any cleaning when necessary.
• In connection with a service, mandatory ventilation inspection or cleaning of the ventilation system, check that the general condition of the product appears to be good. Pay particular attention to the suspension, cables and that they sit firmly in place.
• It is not permissible to open or repair electrical components.
• If you suspect that the product or a component is defective, please contact Swegon.
• A defective product or component must be replaced by an original spare part from Swegon.
Materials and surface treatment
All sheet-metal parts are galvanized sheet steel (Z275).
Disposal
Waste must be handled according to local regulations.
Product warranty
The product warranty or service agreement will not be valid/will not be extended if: (1) the product is repaired, modified or changed, unless such repair, modification or change has been approved by Swegon AB; or (2) the serial number on the product has been made illegible or is missing.
6
Swegon reserves the right to alter specifications. 20201117
Performance checks
4,00 V
V DC
1 2
U CA CB
4 A B
Figure 10. Shows how to connect a voltmeter for checking the actual value.
Formulas for calculating air flow
The following applies for analogue control.
Control signal 0..10 V DC give the following formulas:
• Calculation of the current actual value (U) when you know the value of the current flow (V act
):
U = 10 V DC
V act
– V min
V max
• Calculation of the current actual value (U) when you know the value of the current flow (V act
):
U = 2 V DC + 8 V DC
V act
– V min
V max
Key to formulas above:
U = actual value signal in [V] DC
V act
= current air flow in [l/s, m 3 /h]
V min
= set min. flow in [l/s, m 3 /h]
V max
= set max. flow in [l/s, m 3 /h]
REACT M
20201117 Swegon reserves the right to alter specifications.
7
REACT M
Technical data
IP class:
Corrosivity class:
Leakage classes according to SS-EN 1751
- Leakage class, casing:
Ambient temperature
Operation:
Storage:
RH:
CE marking:
IP42
C3
C
0 – +50 °C
-20 – +50°C
10 - 95%
(non-condensing)
2014/35/EU (LVD)
2014/30/EU (EMC)
2011/65/EU (RoHS2)
Electrical data
Power supply:
Fixed connection cable,
1000 mm with cable size.
24 V AC/DC ±20% 50 - 60 Hz
3 x 0.75 mm 2
2 x 0.38 mm 2
Power consumption, for transformer rating:
REACT M 0.6 W 1.3 VA
Declaration of Conformity
Swegon AB hereby declares that:
REACT M complies with the essential characteristic demands and relevant regulations specified in the directives, 2014/35/
EU (LVD), 2014/30/EU (EMC) and 2011/65/EU (RoHS2):
The following standards have been observed:
EN 60730-1:2011
EN 61000-6-2:2007
EN 61000-6-3:2007
Automatic electrical controls for household and similar use - Part 1 Generic standards
Electromagnetic compatibility (EMC). Generic standards. Immunity for industrial environments
Electromagnetic compatibility (EMC). Generic standards. Emission standard for residential, commercial and light-industrial environments
Person responsible for this declaration:
Name: Freddie Hansson, R&D Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 200601
This declaration is applicable only if the product has been installed according to the instructions in this document and if no modifications or changes have been made on this product.
References
www.swegon.com
Building Materials Declaration
REACT M Product Data Sheet
REACT Description of functions & Wiring diagram
REACT Modbus
8