GE AZ65H07DQC Zoneline® Heat Pump Unit, 230/208 Volt Guide


Add to my manuals
4 Pages

advertisement

GE AZ65H07DQC Zoneline® Heat Pump Unit, 230/208 Volt Guide | Manualzz

INTRODUCING

ZONELINE® PTAC

with

IEQ

PRODUCT AND ACCESSORIES GUIDE

Zoneline PTAC featuring

I

ndoor

E

nvironmental

Q

uality (

IEQ

), improves indoor air quality for comfort and peace of mind

1

ZONELINE® PTAC

with

IEQ

THE REASONS WHY

FEATURES AND BENEFITS

UV-C LIGHT TECHNOLOGY

Customized for the PTAC application. Designed to apply UV-C light to the air as it passes through the unit.

FOCUSED UV-C DIRECTION ON FAN

Powerful UV-C lights focus on the PTAC fan blade, where air movement occurs.

HIGH POWERED LED ARRAY

High-powered LED array treats air passing through the PTAC.

UL® CLASSIFIED

Representative samples of this product have been evaluated by UL and meet applicable safety standards.

2

PTAC IEQ FACT:

RETROFIT CAPABLE

Optimized for Zoneline Packaged Terminal Air Conditioners

(AZ45/65 W5 and beyond)

*GE Appliances tested a Phi-X174 bacteriophage virus, nebulized in a sealed test chamber (10´x 10´x 10´(1000 ft 3)) with an average temperature of 68° F and relative humidity of 50.3%. Air sampling was taken every 30 minutes with the Zoneline

PTAC on high speed with a new UVC kit active over 3 hours & compared to natural decay results. Testing was conducted at a nationally accredited laboratory.

ZONELINE® PTAC

with

IEQ

SPECIFICATIONS

AZ65 SERIES

with

IEQ

• Digital LED display

• UV-C Light Technology

• Cross-flow blower

• Two DC fan motors

• Smart fan cooling

• Heat and Freeze Sentinel

• Remote thermostat capability

• Electronic temperature limiting

• Works with central desk

control and through wall fans

AZ65 SERIES 230/208V

ZONELINE AZ65 SERIES MAKEUP AIR w/IEQ

230/208V Models

Cooling BTUH

EER (BTU/Watt)

AZ65H07DQM AZ65H09DQM AZ65H12DQM AZ65H15DQM

7,000/7,000

12.5/12.5

9,200/9,100

11.3/11.3

11,500/11,400 14,000/13,800

11.2/11.2

10.1/10.1

Dehumidification (Pts/Hr)

CFM, Indoor fan high

Power factor

Vent CFM (module airflow)

Sensible heat ratio

@ 230 volts

Cooling watts

(230/208 V)

Total Cooling AMPERES

(230/208 V)

LR Amperes

Reverse cycle heat BTUH

0.9

360

96%

25-50

89%

560/560

3.7/3.9

13.5

6,200/6,100

1.9

420

97%

25-50

80%

810/805

4.9/5.2

21.0

8,000/7,900

2.9

410

97%

25-50

73%

1,025/1,015

5.8/6.2

4.3

400

97%

25-50

66%

1,370/1,350

6.2/6.6

29.5

31.5

10,200/10,000 13,200/13,000

Coefficient of Performance

(COP)

Heat Pump watts

Heat Pump total amps

Weight (Net/Ship)

4.0/4.0

450/440

3.3/3.4

117/127

3.3/3.3

705/695

4.7/4.8

123/133

3.5/3.5

850/835

5.0/5.2

123/133

3.2/3.2

1,200/1,180

5.4/5.7

126/136

ZONELINE AZ65 SERIES CORROSION PROTECTION w/IEQ

230/208V Models

Cooling BTUH

AZ65H07DQC AZ65H09DQC AZ65H12DQC AZ65H15DQC

7,100/7,000 9,600/9,500 11,800/11,600 14,400/14,200

EER (BTU/Watt)

Dehumidification (Pts/Hr)

CFM, Indoor fan high

CFM, Indoor fan low

Power factor

Sensible heat ratio

@ 230 volts

13.0/13.0

1.6

360

205

96%

73%

12.2/12.2

2.6

420

300

98%

68%

11.8/11.8

3.7

410

300

98%

62%

10.4/10.4

4.8

400

290

97%

60%

Cooling watts

(230/208 V)

Total Cooling AMPERES

(230/208 V)

LR Amperes

Reverse cycle heat BTUH

Coefficient of Performance

(COP)

Heat Pump watts

Heat Pump total amps

Weight (Net/Ship)

545/535

2.5/2.7

13.5

6,200/6,100

4.0/4.0

450/445

2.1/2.2

98/108

795/785

3.6/3.9

21.0

8,100/8,000

3.7/3.7

645/630

2.9/3.1

106/116

995/975

4.5/4.9

1,365/1,365

6.2/6.7

29.5

31.5

10,300/10,200 13,200/13,000

3.6/3.6

835/815

3.8/4.0

104/114

3.2/3.2

1,205/1,180

5.5/5.8

108/118

Listed by

Underwriters

Laboratories

Specifications subject to change. Total watts and total amps include electric heat and fan motor(s). RAK515P, RAK520P and RAK530P are only to be used with a sub-base.

*30 AMP heater wattage will be reduced

in low fan operation.

**RAK4002D junction box (sold separately) required when using the direct connect kit.

Each line cord kit has an integral Leakage

Current Detection and Interruption (LCDI) device as required by National Electrical Code

(NEC) and Underwriters Laboratories (UL) for units manufactured after August 1, 2004.

Currently available for sale or distribution in all states except Hawaii.

GE ZONELINE SPECIFICATIONS —RESISTANCE HEATER WATTAGE

BTUh size

230/208-Volt Line-Cord Connected (P) and Direct Connected Units (D)

RAK315P &

7,000/9,000

RAK320P & RAK330P & RAK315P &

12,000/15,000

RAK320P & RAK330P &

Power connection kit

Total watts

Heater watts

Heater BTUh

Total amps

MCA

RAK315D**

2,410/1,990

2,400/1,960

8,100/6,600

10.5/9.6

15

RAK320D**

3,420/2,830

RAK330D**

4,830/3,990*

3,400/2,780 4,800/3,930*

11,600/9,400 16,300/13,400*

14.9/13.6

20

21.0/19.2

25

RAK315D**

2,430/2,020

2,400/1,960

8,100/6,600

10.6/9.7

15

RAK320D**

3,450/2,860

RAK330D**

4,860/4,020*

3,400/2,780 4,800/3,930*

11,600/9,400 16,300/13,400*

15.1/13.8

20

21.2/19.3

25

Recommended

protective device

(MOCP)

15 amp time-delay fuse or breaker

265-Volt

30 amp time-delay fuse or breaker

BTUh size

Power connection kit

Total watts

Heater watts

Heater BTUh

Total amps

MCA

Recommended

protective device

(MOCP)

RAK515P &

RAK515D

2,440

2,400

8,100

9.1

15

15 amp time-delay fuse or breaker

20 amp time-delay fuse or breaker

30 amp time-delay fuse or breaker

15 amp time-delay fuse or breaker

20 amp time-delay fuse or breaker

Permanent (P, Cord Set) and Direct-Connected Units (D)

7,000/9,000

RAK520P & RAK530P & RAK515P &

12,000/15,000

RAK520P &

RAK520D

3,450

3,400

11,600

12.9

20

20 amp time-delay fuse or breaker

RAK530D

4,850*

4,800*

16,300*

18.1

25

25 amp time-delay fuse or breaker

RAK515D

2,460

2,400

8,100

9.3

15

15 amp time-delay fuse or breaker

RAK520D

3,470

3,400

11,600

13.1

20

20 amp time-delay fuse or breaker

RAK530P &

RAK530D

4,870*

4,800*

16,300*

18.4

25

25 amp time-delay fuse or breaker

NOTE: Resistance heater wattage and amperage dependent on power connection kit.

3

HOW TO ORDER

It’s easy to order Zoneline, and Zoneline Parts & Accessories

Call or go online to get the products, parts and accessories you need from GE Appliances.

ZONELINE.COM

| GEAPPLIANCES.COM

| GEAPPLIANCEPARTS.COM

| 844.GE4.PTAC – GE FACTORY SERVICE

ORDER GE APPLIANCES PARTS DIRECT

When you order GE Appliances Parts direct, you’ll be backed by quality and support you can count on:

• Original genuine parts

• Limited 1-year warranty

• Discounts and promotions

• Access to illustrated parts catalog

• Check status and availability

YOUR PRODUCT INFORMATION:

Locate your Zoneline’s serial number:

• Remove cover

• Find the base pan, located at the bottom of the unit

• Serial number will be printed on the base pan

MY ACCOUNT NUMBER

Apply for credit, speak to a GE Appliances Parts

Specialist or buy genuine GE Appliances Parts at:

GECUSTOMERNET.COM

|

800.851.6200

MY SALES MANAGER

NOMENCLATURE

A Z 6 5 H 0 7 D Q M

Zoneline

Chassis series

65= heat pump

Nominal cooling capacity

07=7,000 BTUh cooling

09=9,000 BTUh cooling

12=12,000 BTUh cooling

15=15,000 BTUh cooling

Q = IEQ with UV-C system factory installed

Unit type

H= heat pump with electric resistance heat backup

Voltage/Phase/Frequency

D= 230/208 Volt, single phase, 60 Hz

Special features

C

M

= Corrosion Protection

=Makeup Air

Questions? Contact us at: [email protected]

Visit Zoneline.com for more information.

Listed by

Underwriters

Laboratories

WARRANTY

1

5

2-5

From Date Of Original Purchase Any part of the air conditioner which fails due to a defect in materials or workmanship. During this limited one-year warranty , GE will provide, free of charge, all labor and related service costs to replace the defective part.

From Date Of Original Purchase Sealed Refrigerating System – if any part of the Sealed Refrigerating System (the compressor, condenser, evaportor, and all connecting tubing, including the makeup air system) should fail due to a defect in materials or workmanship. During this limited five-year warranty , GE will provide, free of charge, all labor and related service costs to replace the defective part.

From Date Of Original Purchase Fan Motors, Switches, Heater, Heater Protectors, Compressor Overload, Solenoids, Circuit Boards, Auxiliary Controls,

Thermistors, Freeze Sentinel, Frost Controls, Pump, Capacitors, Varistors and Indoor Blower Bearing, if any of these parts should fail due to a defect in materials or workmanship. During this additional four-year limited warranty , GE will provide the replacement part free of charge.

The customer will be responsible for any labor and related service costs.

4

GE is a trademark of the General Electric Company. Manufactured under trademark license.

GE Appliances has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice.

Appliance Park Louisville, KY 40225 geappliances.com

Pub. No 20-S0426-22 OTGEA22260

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement