SONBEST SD5111B RS485 Network Type Large Screen LCD Wall-Mounted Temperature and Humidity Display User Manual

Add to My manuals
5 Pages

advertisement

SONBEST SD5111B RS485 Network Type Large Screen LCD Wall-Mounted Temperature and Humidity Display User Manual | Manualzz

SD5111B Us er Ma nual http://www.sonbus.com/

SD5111B

RS485 network type large screen LCD wall-mounted temperature and humidity display

User Manual

File Version: V21.2.25

SD5111B using the standard RS485 bus MODBUS-RTU protocol,easy access to PLC , DCS and other instruments or systems for monitoring temperature,humidity state quantities.The internal use of high-precision sensing core and related devices to ensure high r eliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.

Sha nghai Son best Industrial Co., Ltd Page1

SD5111B Us er Ma nual http://www.sonbus.com/

Technical Parameters

Technical parameter

Temperature measuring range

Temperature measuring accuracy

Humidity measuring range

Humidity accuracy

Communication Interface

Default baud rate

Power

Display

Parameter value

-30 ℃ ~80 ℃

± 0.5

℃ @25 ℃

0~100%RH

± 3%RH @25 ℃

RS485

9600 8 n 1

DC9~24V 1A

LCD

Running temperature

Working humidity

-40~80° C

5%RH~90%RH

Wiring instructions

Any incorrect wiring can cause irreversible damage to the product. Please carefully wire the cable as follows in the case of power failure, and then connect the cable to confirm the correctness and then use it again.

ID

1

2

Core color

Red

Green

Identification

V+

V-

Note

Power +

Power -

3

4

Yellow

Blue

A+

B-

RS485 A+

RS485 B-

In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the core color is for reference.

Communication Protocol

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is

9600, 8, n, 1

1. Read Data (Function id 0x03)

Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 02 C4 0B .

Device ID Function id Start Address Data Length CRC16

01 03 00 00 00 02 C4 0B

For the correct query frame, the device will respond with data:01 03 04 00 79 00 7A AA 09 , the response format is parsed as follows:

Device ID Function id Data Length

01 03 04 data 1

00 79 data 2

00 7A

Check Code

AA 09

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21.

Others and so on.

2. Data Address Table

Address Start Address Description Data type Value range

40001 00 01 temperature read 0~65535

Sha nghai Son best Industrial Co., Ltd Page2

SD5111B Us er Ma nual http://www.sonbus.com/

40002

40101

40102

40103

00 02

00 64

00 65

00 66 humidity model code total points

Device ID read read/write read/write read/write

0~65535

0~65535

1~20

1~249

40104

40105

00 67

00 68 baud rate mode read/write read/write

0~6

1~4

40106 00 69 protocol read/write 1~10

3 read and modify device address

(1) Read or query device address

If you don't know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

Device ID

FA

Function id

03

Start Address

00 64

Data Length

00 02

CRC16

90 5F

FA is 250 for the general address. When you don't know the address, you can use 250 to get the real device address, 00 64 is the device model register.

For the correct query command, the device will respond, for example the response data is: 01 03 02

07 12 3A 79, the format of which is as shown in the following table:

Device ID Function id Start Address Model Code

01 03 02 55 3C 00 01

CRC16

3A 79

Response should be in the data, the first byte 01 indicates that the real address of the current device is,

55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes

00 01 Indicates that the device has a status quantity.

(2)Change device address

For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66

00 02 E8 14 .

Device ID

01

Function id

06

Start Address

00 66

Destination

00 02

CRC16

E8 14

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table:

Device ID Function id Start Address Destination CRC16

01 06 00 66 00 02 E8 27

Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.

4 Read and Modify Baud Rate

(1) Read baud rate

The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, read the current device's baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.

Device ID Function id Start Address Data Length CRC16

01 03 00 67 00 01 35 D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600;

4 is 19200; 5 is 38400; 6 is 115200.

For the correct query command, the device will respond, for example the response data is: 01 03 02

Sha nghai Son best Industrial Co., Ltd Page3

SD5111B Us er Ma nual http://www.sonbus.com/

00 03 F8 45, the format of which is as shown in the followin g table:

Device ID Function id Data Length Rate ID CRC16

01 03 02 00 03 F8 45

coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.

(2)Change the baud rate

For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

Device ID Function id Start Address Target Baud Rate CRC16

01 03 00 66 00 01 64 15

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

5 Read Correction Value

(1) Read Correction Value

When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters.

Device ID Function id Start Address Data Length CRC16

01 03 00 6B 00 01 F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02

00 64 B9 AF, the format of which is as shown in the following table:

Device ID

01

Function id

03

Data Length

02

Data value

00 64

CRC16

B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, humidity have this parameter, the light generally does not have this item.

(2)Change correction value

For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .

Device ID

01

Function id

06

Start Address

00 6B

Destination

00 64

CRC16

F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after successful change.

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual proper ty rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use

Sha nghai Son best Industrial Co., Ltd Page4

SD5111B Us er Ma nual http://www.sonbus.com/ of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd

Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China

Web: http://www.sonbest.com

Web: http://www.sonbus.com

SKYPE: soobuu

Email: [email protected]

Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

Sha nghai Son best Industrial Co., Ltd Page5