14047000 Rev A

SAFETY WARNINGS IMPORTANT SAFETY INFORMATION

Disconnect power before installation.

DANGER- RISQUE DE CHOC- COUPER L’ALIMENTATION AVANT L’INSTALLATION

LED Retrofit Kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Product must be installed in accordance with NEC or your local electrical code. If you are not familiar with these codes and requirements, contact a qualified electrician.

ATTENTION- Risque d’incendie ou de choc électrique. L’installation du kit upgrade

LED exige Ia connaissance des systèmes électriques pour luminaires. Si non qualifié, ne tentez pas d’installation. Ce produit doit être installé conformément à NEC ou votre code électrique local. Si vous n’êtes pas familier avec ces codes et ces exigences, veuillez contacter un électricien qualifié.

To prevent wiring damage or abrasion, do not expose wires to the edge of sheet metal or any other sharp objects.

ATTENTION- Pour éviter les dégâts de câblage par l’abrasion, ne pas mettre en contact les fils électriques avec des bords de tôle ou d’autres objets pointus.

Check the existing wiring for damage before Installing upgrade kit. Do not install if existing wires are damaged.

ATTENTION- Risque d’incendie ou de choc électrique. Vérifier si le câblage existant n’est pas endommagé avant l’installation du kit upgrade LED. Ne pas installer si des fils sont endommagés.

Luminaire wiring and electrical parts may be damaged when drilling for installation of the LED upgrade kit. Check for enclosed wiring and components.

ATTENTION- Risque d’incendie ou de choc électrique. Câblage électriques peuvent

être endommagés Iors du perçage pour l’installation du kit upgrade LED. Vérifier les fils et composants.

UNPACKING THE KIT

Install this kit only in luminaires that have the construction features and dimensions shown in the photographs and/ or drawings.

ATTENTION- Risque d’incendie ou de choc électrique. lnstallez ce kit seulement dans les luminaires qui ont les caractéristiques de construction et les dimensions dans les photographies ou les dessins de Ia page suivante.

Seulement les trous indiqués dans les photographies ou les dessins peuvent être faits ou altérés pour l’installation du kit upgrade LED. Ne laissez aucun trou ouvert dans le compartiment électrique.

Pour utilisation dans luminaires fluorescent surface sans lentille de 2 pi par 4 pi, avec une dimension minimum du compartiment de câblage de 13/4” par 3” par 4 pi, suspendu par un minimum de 12 pouces du plafond, convient aux endroits humides et convient à une température ambiante max. de 40 ° C.

(3) Universal Douglas LED Modules/Light Bars

(1) Universal Douglas Driver

(3) Screws supplied per 4’ Light Bar

(6) Connectors (Orange 3-Position)

(1) Relamp Label www.universaldouglas.com

Rev. 3/114/22

Page 1 Universal Lighting Technologies

INSTALLATION

: Disconnect power from the fixture.

: Remove existing linear fluorescent lamps as shown in regulations.

. Dispose of lamps per local

: Remove wiring compartment cover to access existing ballast and set aside. (See , ) www.universaldouglas.com

Rev. 3/114/22

Page 2

14047000 Rev A

: Cut the leads from the ballast to the socket housing on both ends of the fixture as shown in

.

: Cut the leads from the input power to the ballast.

See .

NOTE: Cut leads at the ballast leaving as much length as possible to facilitate installation of the driver. Strip wires as necessary.

: Remove the ballast by removing the ballast mounting screw(s) from the fixture and dispose of properly per local regulations. See .

Universal Lighting Technologies

INSTALLATION

www.universaldouglas.com

Rev. 3/114/22

: Mount the driver into the fixture wiring compartment on a flat surface. The driver mounting surface must be set flush to the fixture for proper thermal management. Install the driver where possible using existing crow’s feet or mounting holes and the provided two drill point screws with serrated heads. Ensure the driver is properly grounded. See

.

: Position the light bars approximately centerline between the existing lamp sockets of the outer four reflectors as shown in . Secure each light bar to the reflector with the (6) provided self-tapping screws shown in .

: Connect red leads from both light bars to the red lead wire of the LED driver with the supplied orange 3-position connector by pushing into the open slot. Repeat for blue leads. See .

Page 3

14047000 Rev A

: Connect the input power lead wires of the LED driver to the branch circuit power conductors as indicated on the wiring diagram shown on the LED driver label. See .

NOTE: Optional 0-10Vdc Analog Dimming interface

Use Violet (+) and Gray (-) for connection to 0-

10Vdc.

Capping Violet and Gray leads separately provides

100% light output.

Wiring Violet and Gray leads together provides minimum light output.

The dimming control connections on the LED driver are for Class 2 wiring methods only. Separate the dimming control field wiring from the branch circuit field wiring in the wiring compartment in accordance with the National Electrical Code.

: Replace wiring compartment cover. Take care not to pinch the red and blue leads between the cover and the fixture. See .

: Place the re-lamp label at a visible location in the fixture.

LED MODULE

SERRATED HEAD SCREW

GROUNDS DRIVER TO HOUSING

LED MODULE

WHITE

BLACK

LED DRIVER

RED

BLUE

VIOLET

GREY

0-10V

DIMMING

CONTROL

LED MODULE

Universal Lighting Technologies

advertisement

Key Features

  • Easy to install
  • Suitable for surface-mount fluorescent luminaires
  • Suitable for damp locations
  • Includes all necessary components
  • Connects easily to existing wiring

Related manuals

Frequently Answers and Questions

What is the dimension requirement for the fixture's wiring compartment?
The wiring compartment should have a minimum dimension of 1-3/4” by 3” by 4 ft.
Can I use this kit with any fluorescent luminaire?
No, this kit is specifically designed for surface-mount fluorescent luminaires measuring 2 ft by 4 ft.
Can I install this kit myself?
Yes, you can install this kit yourself if you have the necessary electrical knowledge and skills. However, if you are not comfortable working with electrical systems, it is recommended that you hire a qualified electrician.