Allen-Bradley 1352C User Manual
PDF
Dokument
Annonce
Annonce
EE
M eo EE Et
=
fe
ALLEN-BRADLEY
HE
ete
ea
3 System
о
ANETO +: AE RR A TONO mun
SE
aintenance Manual
13526
NR EE LES
2. E ome
on and M
ati
Bullet
Install
RES
ee
He ADA
Important User Information
Repair or Repair/Exchange
Procedure
Because of the variety of uses for this equipment and because of the
differences between this solid state equipment and electromechanical
equipment, the user of and those responsible for applying this equipment must
satisfy themselves as to the acceptability of each application and use of the
equipment. In no event will Allen-Bradley Company be responsible or liable
for indirect or consequential damages resulting from the use or application of
this equipment.
The illustrations shown in this manual are intended solely to illustrate the text
of this manual. Because of the many variables and requirements associated
with any particular installation, the Allen-Bradley Company cannot assume
responsibility or liability for actual use based upon the illustrative uses and
applications. |
No patent liability is assumed by Allen-Bradley Company with respect to use
of information, circuits, equipment or software described in this text.
Reproduction of the content of this manual, in whole or in part, without
written permission of the Allen-Bradley Company is prohibited.
Warnings tell readers where people may be hurt if procedures are
not followed properly.
A Cautions tell readers where machinery may be damaged or
economic loss can occur if procedures are not followed properly.
Both of these:
e Identify a possible trouble spot.
e Tell what causes the trouble.
e Give the result of improper action.
e Tell the reader how to avoid trouble.
For your convenience, the Allen-Bradley Company Motion Control Division,
and the Allen-Bradley Area Support Division (ABSD), provide an efficient
and convenient method of returning equipment eligible for repair or
repair/exchange.
A Product Service Report (P.S.R.) number is required to return any equipment
for repair. This may be obtained from your area Allen-Bradley Distributor,
Sales Office or Area Support Division.
Return any equipment to be repaired to the Area Support Division nearest you.
Be sure to reference the P.S.R. number on the carton and packing slip. Include
your company name and address, your repair purchase order number, and a
brief description of the problem. This will facilitate quick return of your
equipment.
A complete listing of Area Support Divisions may be obtained by calling your
area Allen-Bradley Distributor or Sales Office.
cas ="
TABLE OF CONTENTS
\
EX El El EXE DRED EE
TITLE
Section 1: General Information
Section 2: Installation & Startup
Section 3: Hardware Description
Section 4: Line Generating Unit
Section 5: Troubleshooting
Section 6: Preventative Maintenance
Section 7: Reference Documents
Section 8: Glossary
CT
TABLE OF CONTENTS
1. General Information
1-1. Purpose of Manual 1
1-2. Documentation
—
1-3. Description of Equipment
1-4. Safety
1-4.1. introduction
1-4.2. Operation
E A 2d ea N
1-4.3. Maintenance Work
Section
1
BULLETIN 1352 GENERAL INFORMATION
1-1
Purpose Of Manual
This manual is intended for use by personnel familiar with the functions of
solid-state drive equipment. Included in this manual are reference materials
Documentation
which will allow the reader to operate, maintain, troubleshoot and perform
basic adjustments to the Bulletin 1352 AC Drive System.
The 1352 drive hardware can be packaged in several different configurations
with the major distinction being common DC bus types or individual drive
packages. The inverter hardware of the drive, which controls the AC motor,
remains functionally the same in all configurations. This manual provides
detailed information for installation and start-up of the system. In addition,
basic troubleshooting information is provided. Only brief descriptions of the
operation and general hardware configurations are furnished.
1-2
The Inverter Unit of the Bulletin 1352 Drive can be operated as a Vector
controlled drive, a Scalar controlled drive or a Line Generating Unit (LGU)
with only software and minor board differences. This manual is designed to
be applicable to the general hardware and software of the LGU. For detailed
descriptions of the software and hardware associated with other control types,
refer to the Programming and Operations manual associated with the specific
drive type.
This manual also covers the hardware associated with Common DC bus
applications. For information pertaining to individual drives, refer to the
1352 - 5.0 Installation & Maintenance Manual.
Documentation for Bulletin 1352 applications is summarized in Table 1-1.
Table 1-1. Documentation Summary
Installation & Maint.
1352-5.01 1352 Pre-installation & Provides a detailed description of reccomended wiring practices as well as standard
Maintenance Manual drive dimensions, suggested conduit Entrance/Exit locations and standard cable lug
sizes.
1352 - 5.0 1352 Installation and General hardware and software information aimed at troubleshooting and
Maintenance Manual maintenance of basic equipment whether Vector or Scalar Control.
1352 - 5.1 1352 Vector Control Provides a detailed functional description of the specific hardware and software
Programming and used with the 1352 Vector controlled drive. In addition, advanced troubleshooting
Operations Manual and diagnostic techniques are discussed.
1352-5.2 1352 Scalar Control Provides a detailed functional description of the specific hardware and software
Programming and used with the 1352 Scalar controlled drive. in addition advanced trou bleshooting
Operations Manual and diagnostic techniques are discussed.
1352-53 1352 System Manual Provides a detailed description of the hardware associated with common DC bus
configurations. In addition, a detailed description of regeneration and power
dissipation from a common DC bus is described.
1352 - 5.4 1352 Hardware Options Provides information for Startup & Maintenance of several common hardware
options.
Page 1-2
Bulletin 1352 5.3 System
1-3
Description of Equipment
Bulletin 1352 Drive Systems can be designed in several configurations,
depending on the application requirements. Three common system
arrangements are shown in Figure 1-1. The reference section is shown below
each unit. In the basic configuration (1A) which is most common, a diode
bridge in a Line Converter Unit (LCU) provides a constant DC bus voltage for
the Drive Inverters (INU). In addition to the LCU, a Contactor Unit (CTU) 1s
required to isolate the bridge from the input line. A Capacitor Bank Unit
(CBU) is also required to filter the pulsating DC bus voltage from the LCU. A
disconnect device and fuses are provided for isolation of the INU units from
the DC bus voltage. The disconnect also allows maintenance to be performed
on the inverter without shutting down the complete line.
Occasionally, power is fed back to the DC bus from the load through the INU.
This power is capable of being used by other inverter units connected to the
same bus. Unfortunately, some systems cannot always use all of the
regenerated power that is available, such as when a complete line is being
stopped by means of regenerative braking. When this occurs, a method of
dealing with the unused regenerated energy must be provided.
The Bulletin 1352 AC Drive, employs two alternative methods of handling
this excess regenerated power. The first method (Figure 1B) utilizes a
braking chopper and controlled resistors to dissipate the excess energy. This
is generally employed when the regenerated energy exists infrequently in
comparison to the running time of the system. If excess regenerated energy is
available more often or even on a continuous basis, a Line Generating Unit
(LGU) shown in Figure 1C would be used. This unit provides the capability of
regenerating the power back to the AC supply line. The LGU is capable of
controlling the power factor of the regenerated power such that the power
factor is lagging, unity or even leading, similar to the operation of a
synchronous generator. The LGU is also capable of automatic restart after
either a brief power loss or a dip in the supply line voltage. Each of these types
of common DC bus systems is further explained in this manual.
Section 2 details the installation and startup of the Drive System. Section 3
explains the function of the various modules used in a common DC bus system
except for the LGU which is discussed in Section 4. Section 5 provides
assistance in troubleshooting the Drive System with particular emphasis on
the Line Generating Unit and preventive maintenance requirements. Section
6 consists of the reference documents for all units discussed in this manual.
IMPORTANT: In order to minimize the size of this manual it is assumed
that the reader has previous knowledge of the Bulletin 1352 Inverter as a
stand-alone drive and the manner in which parameters are used. The
Bulletin 1352 - 5.0 Installation and Maintenance Manual should be
reviewed prior to working with this System Manual.
Page 1-3
Bulletin 1352 5.3 System
1AB i
|
©
Lan
|
J
|
|
|
|
|
À
|
|
|
|
|
|
т 1
|
|
|
|
|
|
LL
MAM
um
р
O
n
Nu
ay
| &
raking
I
|
|
-
as
T
|
I
I
|
|
i
!
|
!
I
и
Но ее тт = Em ее ее == == == = =
—
CTT TTT TTA]
a ME ED SED MLD NR mn em mmm ees wes wy
Contactor Line ~ Capacitor Inverter Inverter Braking
Unit Converter Bank Unit Unit Chopper
Unit Unit
Reference
Section 3-2 3-3 3-4 3-5 3-5
1C Line Regenerative System
|
L_ STU _ y LEU 4) _CBU__ y сом оо BRC_ JRESISTOR |
:
"== [Осло === === м == ет ее = =]
Braking
Resistor
PO == e чево тв ен = == = — = STE AED GED ани Gy РН WMG GER EEE EE НЫ "ро = = = = = =
| | | | DCBUS | | i
| | | [ 1 i ? +
| J | | | | $ | | |
| | | | I J | J |
| Ш у | | |
| | | | | l |
| | | | | | |
| | | l | | | |
| | | | | | |
| | | | | | |
| | | ! | i | |
| i | | | l
| | - | | | | |
T LFU L CBU IN
| _ СО рН кб BY aN NU,
Contactor Line Line Capacitor Inverter Inverter
Unit Filter Unit Generator Bank Unit Unit
Unit Unit
Reference
Section 3-2 3-6 4-0 3-4 3-5 3-5
Figure 1-1. System Configurations
Page 1-4
Bulletin 1352 5.3 System
1-4
Safety
1-4.1
1-4.2
1-4.3
Introduction
1352- AC Drive and its associated machinery should plan or
implement the installation, start up and subsequent maintenance
of the Drive. Failure to comply may result in personal injury
and/or equipment damage.
A WARNING: Only qualified personnel familiar with the Bulletin
The Drive is designed to provide circuit protection not only to circuits
connected to it but also to the integral circuits. Therefore, circuit protection
parameters must not be altered. Failure to observe this instruction may
compromise the effectiveness and invalidate any warantees.
Recognized safety regulations must be observed in the installation, start-up
and maintenance procedures. Refer to NFPA 70E, Electrical Safety
Requirement for Employee Workplaces, for installation safety requirements
and general requirements for electrical installation.
Operation - The operation of the Drive should be the responsibility of
personnel familiar with its basic functions. The operator should be informed
of the significance of the Numeric Displays on the Control Panel. In case of a
panel alarm indication, possibly followed by tripping, the operator must be
able to decide whether the Drive should be removed from operation or whether
it should be restarted after resetting the alarm.
Maintenance Work - All maintenance of the Drive must be performed by a-
experienced electrician, familiar with both the drive and solid state
electronics.
work is performed on the Drive to guard against possible injury
that can result from accidental contact with live parts or improper
procedures.
A WARNING: The following points must be observed before any
A. Ifthe Drive is equipped with bypass equipment, a portion of the supply
voltage may also be fed back to the drive cabinet through the output
terminals.
bypass circuitry in a separate bay is required while running in the
A WARNING: A shock hazard exists if maintenance on a drive with
bypass mode. The following must be followed:
1) With all power off, disconnect the power cables between the
drive and its output contactor. This provides against voltage
feedback by potentially welded contacts.
2) Take careful note of all power cables and control wiring which
may be live when the Bypass Mode is in operation.
3) Proceed with Extreme Caution!
maintenance on the drive should only take place if both drive and
A WARNING: If the bypass circuitry is in the same bay as the drive,
bypass are deenergized.
Page 1-5
Bulletin 1352 5.3 System
be checked while in the bypass mode. If adjustment is necessary,
the input cables should be reconnected in the appropriate pattern.
DO NOT make correction by adjusting leads at the motor or output
of the inverter.
A CAUTION: To avoid damage to equipment, motor rotation should
Since all semiconductors exhibit leakage current, the circuits of the Drive
should be regarded as live. Do Not touch any components until the Drive
has been isolated from the supply voltage(s) by disconnects or isolating
switches and it has been verified that there are no voltages present.
. The large capacitors in the Intermediate DC Circuit together with their
resistor discharge circuits are designed to discharge to less than 50V DC
within one minute per NEMA Standard, but these circuits should never
be assumed to be functioning properly. Always measure this voltage prior
to performing any work on the equipment to ensure proper results.
voltage charge is potentially lethal. Therefore, the properly sized
and engineered discharge circuit incorporated in the Drive should
never be modified.
A CAUTION: A power capacitor with even a small remaining
the capacitors causes a considerable discharge current and is
A WARNING: Discharging a voltage as low as 20V DC by shorting
potentially lethal.
. To verify that no voltage is present, a measurement must be taken at the
Intermediate DC bus . The measurement should be made starting with
the 1000V DC range of a multimeter, then switching to lower voltage
ranges as voltage levels permit to prevent over-range indications.
Many voltage testers are unsuitable for checking the Intermediate DC
Circuit voltage, since they do not respond to voltages below approximately
100V DC.
Fatal Voltage is present between the circuit cards and the chassis!
Servicing energized industrial control equipment can be
hazardous. Severe injury or death can result from electrical shock,
burn or unintended actuation of controlled equipment.
Recommended practice is to disconnect and lock-out control
equipment from power sources and confirm discharge of stored
energy in capacitors, if present. If it is necessary to work in the
vicinity of energized equipment, only qualified personnel should be
permitted to perform such work, using all applicable safety
practices and protective equipment.
Do not needlessly remove the aluminum and plastic protection
panels during fault tracing. This is usually unnecessary and can
expose personnel to potential hazards from voltage sources present
in the unit. If any protective panel was removed, always replace
the panel before operating the unit.
A WARNING: When Voltage is supplied to the system a potentially
DE
TABLE OF CONTENTS
2. Installation & Start Up
2-1. Pre-Installation 1
2-1.1. Safety & Codes 1
2-1.2. Unpacking & Inspection 1
2-1.3. Storage 1
2-2. Transportation & Handling 1
2-3. Installation Site 2
2-4. Mounting 2
2-5. Wiring 2
2-5.1. Grounding Practices 2
2-5.2. Power Connections 3
2-5.3. Control & Signal Connections 4
2-5.4. interference Suppression 4
2-6. Losses and Ventilation / Air Conditioning Requirements 5
2-7. Start Up Equipment Required 5
2-8. Preparation For Start Up 6
2-9. Non-Regenerative System Start Up 8
2-10. Controlled Braking Set Up 8
2-11. Line Regenerative System 8
2-12. LGU Adjustments 9
2-12.1. Current And Voltage Tuning 10
2-13. Saving Changes 11
2-14. RAM Memory Battery Back Up 11
Page 2-7
Bulletin 1352 - 5.3 System
PREPARATION FOR START-UP
Cooling
Air
Supply &
Motor Wires
Feeder
Wires
START-UP
~
Supply I Motor Phase
Sequence voltage
a EEE; .
Voltage Current
Adjust . Adjust
Process With Out
Check Motor
Figure 2-2. Start-Up Sequence
Page 2-8
Bulletin 1352 - 5.3 System
2.9
Non-Regenerative System
Startup
2-10
Controlled Braking Setup
2-11
Line Regenerative System
IMPORTANT: The following section is for Non - Regenerating Systems
only (Line Converter Units). For Regenerative Systems, go to section 2-11
(Line Generating Units).
The following procedure should be followed when starting up the Line
Converter Unit for the first time. A Line Converter Unit can be identified by
the semiconductors which are diodes rather than GTO's, and the LCU does not
have an AC Line Filter Unit. Refer to Figure 1-1 for a graphic comparison of
the two systems.
1. Check that the input power is still off (main disconnect open), inverter
DC disconnects are open and the motors are disconnected.
2. Measure the resistance of the DC bus at the diode bridge of the LCU and
the resistance of each inverter DC bus. A good measuring pointis at the
disconnect terminals. Refer to the connection diagram for the equipment
supplied for specific wire numbers. The resistance should be
approximately 3000 ohms.
3. Close the main CTU disconnect, which will apply power to the DC bus.
No further startup procedure is required for the basic LCU. Continue
with section 2-10 if optional Controlled Braking is included.
4. Refer to the Installation and Maintenance Manual 1352 - 5.0 prior to
closing the inverter DC disconnect.
The braking resistors are normally sized for 10% current for 20 seconds with a
20% duty cycle. Care must be taken to insure that this intermittent duty
rating is not exceeded during startup and testing.
Jumper S1 on the Braking Chopper Control Card 3500-BCC should be
checked to insure that it is connected for the proper AC voltage rating. The
Bulletin 810 Current Relay is adjusted for correct current and time prior to
shipping from the factory. If adjustment of the current or time is required,
refer to Allen-Bradley Publication 810-5.0.
WARNING: The Red LED located on the Chopper Control Card
(3500 - BCC) indicates when the Bus is charged and the Chopper
Control Card has its operating voltages. This LED must not be
considered a safety indicator for servicing the braking system. The
LED does not accurately indicate when all voltages have been
removed from the circuit. Only a DC voltmeter should be used to
test for absence of voltages before servicing any part of the system.
IMPORTANT: The following procedure is only used for systems that
provide for regeneration to the AC line using a Line Generating Unit.
2-1
Pre-Installation
2-1.1
2-1.2
2-1.3
2-2
Transportation & Handling
Section
2
BULLETIN 1352 INSTALLATION & STARTUP
Safety & Codes -
outline provisions for safely installing electrical equipment.
Installation MUST comply with specifications regarding wire
type, conductor sizes, branch circuit protection and disconnect
devices. Failure to do so may result in personal injury and/or
equipment damage.
A WARNING: The National Electrical Code (NEC) or local codes
Unpacking & Inspection - After unpacking the equipment, check the
item(s) received against the bill of lading to assure that the nameplate
description of each item agrees with the material ordered. Inspect the
Bulletin 1352 AC Drive and the other equipment for physical damage, as
stated in the Allen-Bradley / Stromberg Terms and Conditions of Sale.
Important: All claims for breakage and damage whether concealed or
obvious must be made to the carrier by the Customer as soon as possible after
receipt of the shipment. The Allen-Bradley Co. will be glad to render
reasonable assistance in the securing of adjustment for such damage claims.
Remove all packing material, wedges, or braces from within the drive
controller. Operate the contactors and relays manually to assure that they
operate freely.
Storage - If any part of the equipment will not be installed when it is
unpacked, it should be stored in a clean, dry place. The storage temperature
must be between OC (32F) and 60C (140F) with a maximum humidity of 90%,
non-condensing to guard against damage to temperature sensitive
components of the controller. The storage environment must be free of
chemical and other corrosive contaminants (ie. conductive dust, sulfides,
animal matter, etc.). Space heaters may be installed in the enclosure to
prevent condensation.
void warranty.
A CAUTION: Non - Compliance with Storage requirements may
The Bulletin 1352 AC Drive system is shipped in sections, generally 5 feet to
20 feet in length. A lifting beam is provided across the top of the lineup for
overhead lifting . Detailed lifting instructions are provided in a separate
envelope attached to the lifting beam. Round rollers can be used to assist in
moving the Drive to the installation site. Once at the final site, the pipe
rolling technique can be used to place the cabinet in the desired position.
pipe rolling technique . Always exercise care and stabilize the
A WARNING: Care must be exercised when using a crane or the
Drive to guard against tipping and possible injury to personnel.
Page 2-2
Bulletin 1352 - 5.3 System
2-3
Installation Site
2-4
Mounting
2-5
Wiring
2-5.1
When choosing the installation site, the following conditions should be
considered:
A.The operating ambient temperature must be between 0C (32F) and 40C
(104F) for NEMA Type 1 enclosures. For NEMA Type 12 enclosures
(which includes a closed loop air conditioning system), the operating
ambient temperature must be between 0C (32F) and 50C (122F).
B. The relative humidity must not exceed 95% non-condensing. Excessive
humidity can cause corrosion or excessive dirt build-up leading to
possible electrical problems.
C. The equipment should be kept clean. Dust build-up inside the enclosure
inhibits proper cooling and decreases the system reliability. If the
environment is excessively dusty, it may require an optional fan & filter
kit modification. Contact the local Allen - Bradley Sales Office for more
details.
D. Only persons familiar with the function of the Drive must have access to
the equipment.
E. The losses in the Drive produce a definite heat dissipation depending on
unit size that tends to warm the air in the room. Attention must be given
to the room ventilation and cooling requirements to ensure the proper
environmental conditions are met. See section 2-6 for more details.
F. Operational altitude is 3300 ft. (1km) maximum without derating.
component damage or a reduction in product life. Wiring or
application errors, such as, undersizing the motor, incorrect or
inadequate AC supply, or ambient temperatures above or below
specified temperature range may result in malfunction of the
Drive.
A CAUTION: Anincorrectly applied or installed drive can result in
Standard Drive Cabinet drawings and equipment installation instructions
are provided in Publication 1352 - 5.01. Refer to this document for sizing and
layout of equipment cabinets and correct mounting procedures. On custom
jobs certified dimension drawings are available, contact the local
Allen - Bradley Sales office.
Grounding Practices - The purpose of grounding is to limit dangerous
voltages on exposed parts to ground, to facilitate proper overcurrent device
operation under ground fault conditions and to help provide electrical
interference suppression.
To ensure a zero voltage reference is available for each element in the system,
two ground networks are provided (Figure 2-1.). Each of these is a copper bus
running the length of the cabinet.
Ground Bus - PE - This is the safety ground required by code. The Ground
Bus can be connected to qualified adjacent building steel ( ie.girder, joist)
or a floor ground loop. Multiple connections are permitted. The ground
bus requires a maximum of 1 ohm to ground.
Signal Bus - TE - Isa separate signal ground. It should be Cadwelded to
the Ground Grid on a dedicated Ground Rod. Do Not ground the TE at the
same place as the PE. The minimum distance from the PE to the TE
ground connection is 10 feet.
Page 2-3
Bulletin 1352 - 5.3 System
IMPORTANT! Generally, grounding should be in accordance with the
National Electrical Code (NEC) and local codes. See NEC article 250 for
ground wire sizing information. Ground wires must be insulated.
Each power feeder from the substation transformer to the drive must be
provided with properly sized ground cables. Simply utilizing the conduit or
cable armor as a ground is not adequate. The conduit or cable armor and
ground wires should be bonded to ground at both ends. Each transformer
enclosure and/or frame must be bonded to ground at a minimum of two
locations.
Each AC motor frame must be bonded to grounded building steel within 20
ft. of its location and tied to the drives PE via ground wires within the power
cables and/or conduit. The conduit or cable armor should be bonded to ground
at both ends.
The Remote Operator’s Control panel must be bonded to grounded
building steel within 30 ft. of its location and tied to the Drives PE via ground
wires within the cable conduit and/or cable tray. Bond conduit or cable armor
at both ends. Cable shield, if required, should be connected to TE at the drive
end only.
Optional Tachometer connections IF required must be routed in grounded
steel conduit. The conduit must be grounded at both ends. Connect the cable
shield to the drive TE Signal bus at the drive end only.
Refer to the instruction manual for each auxiliary device connected to the
drive for any special grounding recommendations.
Bulletin 1352
Transformer
Substation
Control
Electronics
Remote
Operator
Station
Inverter
PE
Minimu
10 Feet
PLCI
Module
Motor
Figure 2-1. System Grounding Practices
2-52 Power Connections - The 1352 Drive requires a three-phase supply and an
equipment grounding conductor to earth ground. A neutral conductor of the
three-phase supply is not necessary and is usually not routed to the Drive.
Three-phase wiring and a grounding conductor connects the Drive to the
motor.
Page 2-4
Bulletin 1352 -5.3 System
2-5.3
2+5.3.1
2-5.3.2
2-5.4
The wire sizes must be selected individually, observing all applicable safety
and N.E.C. regulations. The minimum permissible wire size does not
necessarily result in the best operating economy. The minimum
recommended size for the wires between the Drive and the motor is the same
as that used if a main voltage source connection to the motor was used. The
distance between the drive and motor may affect the size of the conductors
used. Consult the wiring diagrams and appropriate NEC regulations to
determine correct power wiring. If assistance is needed, contact your local
Allen-Bradley sales office.
IMPORTANT: The National Electrical Code (NEC) requires that branch
circuit protection of the AC line input power to the drive be provided by
circuit breaker or fusible disconnect switch. The standard Bulletin 1352
Drive does provide this requirement.
The National Electrical Code requires that motor overload protection be
provided in the motor branch circuit. The standard Bulletin 1352 Drive does
not provide this requirement. See Section 6-3 in 1352-5.0 Manual.
motor rotation should be checked while in the bypass mode. If
adjustment is necessary, the input cables should be reconnected as
appropriate. Do Not make correction by adjusting leads at the
motor or output of the drive.
A CAUTION: Ifbypass contactors are supplied with the drive,
Control & Signal Connections - There are several basic configurations of the
1352 control depending on the type of application and what specific VO cards
are used. This section will describe the basic interconnections to external
wiring for the two most common configurations. The general descriptions and
diagrams are based on commonly used wiring schemes. Refer to the
schematics and interconnection drawings supplied with your equipment to
verify the information for your application.
Control & Signal Wires - A shielded type wire is recommended in the control
circuits for protection against interference . A shielded wire is required for
all signal wires and 24VDC wiring. The shield should be grounded at the
drive TE bus only. Both ends should not be grounded. The recommended
conductor cross-sections should be a minimum of 18 AWG (.05082 in). The
best interference suppression is obtained with a cable having an individual
shield for every pair of wires.
IMPORTANT: The Control & Signal wires should be oriented a distance of
at least six (6) inches (150mm) from power cables. Additional noise
suppression practices (including separate steel conduits for signal leads, etc.)
are recommended. See cable/conduit spacing recommendations provided as
part of both the job schematics and in Publication 1352 - 5.01,
Pre -Installation Instructions. We also recommend that 24 VDC Logic
wiring not exceed 50 feet from the drive.
Control & Signal Interconnections Information - For Control & Signal
Interconnection information see Section 2 in Publication 1352 -5.0
Installation & Maintenance Manual.
Interference Suppression - Harmonic and noise voltage disturbances are
present in the supply and output cables of the Bulletin 1352. The interference
caused by the resulting currents can be reduced utilizing the following
methods:
A. Use of cables with a concentric shielded ground conductor.
B. Use of twisted pair shielded wires for control signals.
Page 2-5
Bulletin 1352 - 5.3 System
C. Route the control cables as far away from the power cables as possible,
and avoid long parallel runs of control and power cables.
For detailed information on recommended wiring types, sizes and practices.
refer to the External Wiring Classification Sheets supplied with your
equipment.
2-5.5 Optional Controlled Braking - The Chopper Control Braking Unit is
supplied with the drive, mounted and wired. The braking resistors are
supplied loose for customer mounting. The resistor bank should be mounted
within 50 feet (15 meters) of the drive enclosure. The cables to the resistor
bank should be in a single conduit with the positive and negative conductors
tied closely together, but not twisted. The positive conductor is connected to
the “+” side of the DC bus and the negative conductor is connected through
the thermal overload to the “-” side of the DC bus.
2-6
Losses and Ventilation/ The power losses experienced in the Drive are nominally less than 2 percent
Air Conditioning of the rated power. The Drive is air-cooled with air circulation provided by a
Requirements cooling fan. Since there is more than one INU on a common DC bus system,
the losses can be estimated by using 2% of each INU rating and adding them
together. This would be a worst case situation if all units were operated at full
load continuously. The 90 inch tall NEMA Type 1 enclosure requires no
clearance side to side, but does require a minimum of three feet in front of the
cabinet. The optional Fan and Filter kit requires an additional 14 inches of
height. A NEMA Type 12 cabinet requires a minimum of six inches of
clearance for the air conditioner to provide proper air circulation.
The ambient temperature of the installation site must be between 0C and 40C
(32F to 105F). In cases where restricted air flow or high temperatures are
present, an air conditioned unit or air conditioning of the installation site may
be required ( see Table 2-1). Contact the Allen-Bradley Drives Division for
assistance in determining the air conditioning requirements. The Bulletin
1352 is offered with an air-conditioned NEMA Type 12 cabinet as an option.
TABLE 2-1. Minimum air flow requirements @ 25° C Ambient and 3300 ft. altitude
2-7
Startup Equipment
75- 115 KVA 190
180 KVA 360
290 KVA 635
460 KVA 1165
730 KVA 1525
Required The following equipment should be available during the startup of the system:
A.
Meter(s) capable of measuring DC voltages from 5 VDC to 1000 VDC,
AC voltages from 115 VAC to 600 VAC, and resistances from 1 ohm to
100K ohms.
Megger with up to 1000 volts potential to check the insulation of the
power wiring,
Hand tools as required.
Page 2-6
Bulletin 1352 -5.3 System
2-8
Preparation For Startup Prior to applying power for the first time the following should be checked. See
Figure 2-2 for a graphic flowchart.
1.
O 4 GS Un
Visually check that power cables are of the correct size and type and the
fuses are correctly sized to protect the wires from overloads and short
circuits.
. Check that shielded cables have been used for DC control circuits as
shown on the interconnection diagram.
. Check that control cables have been routed at least six inches from power
wires and that control and power cables do not have long parallel runs
and are run in separate conduit.
. Check that the power and signal grounds are properly connected. Refer
to section 2-5.1.
. Check that all packing material has been removed from the enclosures.
. Check that all contactors and relays operate freely.
. Check that cooling air is not restricted for each of the enclosure sections.
. Before connecting the power cables, check the cable insulation between
phases and from each phase to ground using a megger at 1000 volts for
the tests. Resistance must be greater than 1 megohm. Connect the
cables to the correct terminals per the connection diagram.
A CAUTION: DO NOT megger the drive, as damage may result!
9. Check that all terminal connections are correct and tight.
10.
11.
Check that there are no loose wires in the enclosure.
Measure the incoming supply voltage at terminals L1,L2 and L3.
Voltage must be at nominal rated voltage plus or minus 10% and each
phase voltage must be within + 5% of the other two phases.
Page 2-9
Bulletin 1352 - 5.3 System
The following procedure should be used to start up a Line Generating Unit
(LGU). (Refer to Figure 2-3)
LGU DC
Disconnect
With the input power removed (main disconnect open), the LGU DC
disconnect closed, motors disconnected and all inverter (INU) DC
disconnects open check that the DC bus is at zero potential then check
the DC bus resistance of the LGU and each INU bus. A good measuring
point is at the disconnect terminals. The resistance should be
approximately 3000 ohms at each location.
The Line Generating Unit is equipped with a battery to backup critical
parameters including the fault queue and trend buffers. Because the
battery will only maintain the backup for approximately four days, the
battery is disconnected for shipment and must be reconnected prior to
startup. Jumper S3 on the 3500-CO3 Control Card must be switched to
position A-B to enable the battery backup. If battery is discharged it
may take as long as 20 hours to recharge.
Check that the DC bus disconnect is closed and the control power is on by
checking that the LED on the Power Supply Card is lit. Turn the “CTU
ON-OFF” selector switch (2S) to OFF. Close the CTU main disconnect
applying power to the AC bus. Press the “STOP” pushbutton on the LGU
control panel. Turn switch 28 to the ON position. Within 10 seconds the
main contactor will close. The LGU will not run. (This sequence verifies
the CTU logic).
If the main contactor closed (the desired result), press the “START”
pushbutton for the LGU. The LGU should run.
Refer to the Installation and Maintenance Manual 1352 - 5.0 for the
inverter for instructions to be followed prior to starting the inverter for
the first time. Closing the DC disconnect for the inverter applies DC
voltage to the bridge. An auxiliary contact on the disconnect supplies
AC power from the 215 volt bus.
INU DC
Disconnect
о
MN
uo
Cc
un
y
1.
2.
3.
4.
5.
| | |
| | |
| Main | |
| AC | |
| Disconnekt |
| | |
| | |
| Main | |
! Contactor
| | |
| |
| t
| |
mu y EU y
Contactor Line
Unit Filter Unit
—
= — — — — — Liu NY__ 1 __ NU__
Line Capacitor Inverter Inverter
Generator Bank Unit Unit
Unit Unit
В - = — = yA
Figure 2-3. System Configurations
Page 2-10
Bulletin 1352 - 5.3 System
2-12
LGU Adjustments Ina Line Generating Unit (LGU) there are many adjustment parameters as
well as four different modes of operation. All the parameters and modes of
operation are factory set for the specific application requirements. The
remainder of this section discusses the initial factory setup procedure to aid in
possible fine tuning during startup. For more details on the internal
operation of the LGU as well as an understanding of its various modes of
operation see section 4 of this manual,
The parameters used in the initial tuning of the LGU are detailed in
Table 2-2.
Table 2-2. Parameters to be Setup
UCREFG (26) DC Voltage Reference 1071 4-2.9.1
IQREFG (27) Reactive Current Reference 0 4-292
UCUSCAL (81) Voltage Ratio 2-13
USMSCAL (83) DC Voltage Scaling 2-13
UMSCAL (84) AC Voltage Scaling 2-13
RARMAXTIME (87) Time Limit for Rapid Restart 625 4-2.5
RARMAXCOUNT — (88) (87) Times no. of Rapid Restarts 3125 4-2.5
DARMAXCOUNT (89) Delay Time for Delay Restart 1 4-2.5
ARFLAG (96) Select Rapid Restart 4-2.5
IUOFFSET (298) U Phase Current Adjustment 2-13
IVOFFSET (299) V Phase Current Adjustment 2-13
2-12.1 Current and Voltage Tuning - The current and voltage measurement
system has a number of adjustable parameters. Several of these adjustments
are actually carried out automatically by the drive system once the proper
flags have been set in the sequence detailed below.
The current measurement loop has two memory locations IUOFFSET
298EE and IVOFFSET 299EE whose contents may need adjusting to
acheive a proper current measurement. The initial value of each parameter is
16460. The adjustment is semi-automatic and takes place as follows:
1) Deenergize the LGU output by opening the main contactor (Turn
ON/OFF switch 2S to OFF).
2) Set parameter IOFFCONT 297EE to any nonzero value.
3) Wait a minimum of two minutes. Parameter 297EE will automatically
reset to zero when the adjustment cycle is complete.
4) After the adjustment is complete, the contents of the memory locations
should be written to EEPROM by opening the write protection lock
(EEROMLOCK 8 equal to any nonzero number, see 2-13).
The voltage measurement system has three adjustable parameters:
UCMSCAL 83EE scaling factor of the DC voltage measurement
UMSCAL 84EE scaling factor of the AC supply voltage measurement
UCUSCAL 81EE ratio of DC voltage and AC supply voltage.
The AC and DC scaling factors UCMSCAL 83EE and UMSCAL S4EE
should both be adjusted so that the control panel voltage display and the
readout of a voltmeter are the same. Any required change should be minor. If
the panel display is too high, the respective parameter should be increased.
UCUSCAL 81EE is semiautomatically adjusted when the LGU is running.
Page 2-11
Bulletin 1352 -5.3 System
2-13
Saving Changes
2-14
RAM Memory Battery Backup
UCUCONT 296 is set to any nonzero number by using the following
procedure:
Reactive current controller is ON (48EE not zero)
Reactive current reference value (IQREFG 27EE = 0)
Reactive current limit KQ 28EE set to 850 or greater to avoid limiting
the reactive current controller output.
DC voltage reference UCREFG 26EE is set over 1000 to prevent
reactive current consumption from AC line.
The adjustment takes approximately two minutes. When UCUCONT (296)b
1s automatically reset to zero the adjustment is properly completed. If
UCUCONT is still set to 1 the adjustment is still being executed. If the value
1s anything else, the LGU has discovered a problem. Codes are as follows:
BIT DEC MEANING
1 2 Reactive Current Controller is NOT On.
2 4 IQREF (219) is not equal to zero.
3 8 Reactive Current Controller is limited
4 16 Modulator has reached the high limit
5 32 STOP routine has been executed
When adjustments are completed, the contents of memory locations should be
written to EEPROM so they are saved when the power is shut down. Open the
write protection lock EEROMLOCK 8 by setting it to any nonzero number
(see 2-13). It is also recommended that the changed parameters be written
down on paper, a form is provided for this in Section 7.
After completing the adjustments and selections, this information must be
stored in the permanent memory. To do this, set parameter 8 to 1 and wait for
control panel CP1 to finish displaying “SA51” (Control Panel CP2 “Stored to
Backup”). Parameter 8 must be reset to zero. To further ensure no loss of
memory, and/or unauthorized tampering with adjustments, it is
recommended the CP1 lock input be jumpered “ON” by jumpering terminals
16& 8 on the 3500-T74 Card and switch S4 be set to A-C on the Inverter Unit
A2 - Control Card (3500 - CO3, 103 - CON).
CP1 Lock allows parameter viewing via the Control Panel, but prevents any
adjustment. Switch S4 disables writing to EEPROM when in position A-C.
This also prevents possible memory loss.
after power is turned off, and the unit has been verified as
A WARNING: These jumper changes should be made only
Voltage Free.
In addition to being able to save the software program and all drive tuning
adjustments to EEPROM, the drive is equipped with a battery (Ni CAD)
backup for the following items in RAM Memory:
Fault Words
Fault Buffers
Fault Messages
Trend Buffers
12 Programmable Values
To engage the battery backup, Jumper $3 on the INU Control Card (A2)
(3500 - CO3, 103 - CON) should be position A-B.
Page 2-12
Bulletin 1352 - 5.3 System
If the battery backup is not properly engaged or the battery is dead ,the
control panel will intermittently display SA56. Turning power OFF then ON
again is required to reset this message.
off while the jumper S3 is in position A-B. The jumper must be in
position A-C for storage, or the battery will drain in four days.
Battery will recharge when power is applied for approximately 20
hours.
A CAUTION: DO NOT store spare boards or the drive with power
This completes the LGU startup procedure, proceed to the INU Startup in the
respective manual.
J
TABLE OF CONTENTS
3. Hardware Description
3-1. Introduction 1
3-2. Contactor Unit (CTU) 1
3-3. Line Converter Unit (LCU) 4
3-4. Capacitor Bank Unit (CBU) 4
3-5. Inverter Unit (INU) 6
3-6. Line Filter Unit (LFU) 7
3-7. Line Generating Unit (LGU) 8
3-8. Optional Controlled Braking 8
3-9. CP1 Control panel 9
3-9.1. General 9
3-9.2. Operating The Drive 10
3-9.3. Display Operation 10
3-9.4. Fault Diagnostics Displays 10
3-9.5. Parameter Mode 11
3-10. CP2 Control Panel 12
3-10.1. Description 12
3-10.2. Pushbuttons | 12
3-10.3. Displays 13
3-10.4. Setting Parameters 15
3-10.5. Scaling The Displays 15
3-10.6. Installation 15
3-11. Control Card 17
3-12. GTO Pulse Amplifier Card 19
3-13. GTO Chopper Control Card 21
3-14. GTO Power Supply Card 22
3-15. Auxiliary Power Card 23
3-16. Input/Qutput Connection Card 24
3-17. CBU Supervision Card 26
3-18. Matching Card 27
Section
3
BULLETIN 1352 HARDWARE DESCRIPTION
3-1
Introduction
Information provided in section 3 of this Installation and Maintenance
manual is intended to provide maintenance personnel with an understanding
of the major hardware components associated with the 1352 drive.
The 1352 drive consists of the major hardware units in various configurations
as described in section 1-4. In this section, each of these general blocks will be
further detailed . A summary of the units and their abbreviations is provided
in Table 3-1 for reference. Refer to the specific hardware schematics provided
for your particular drive application and Section 1-4 to determine which
hardware configurations you have been supplied.
Table 3-1. Unit Abbreviations
Contactor Unit CTU 3-2
Line Converter Unit LCU 3-3
‘Capacitor Bank Unit CBU 3-4
Inverter Unit INU 3-5
Line Filter Unit LFU 3-6
Line Generator Unit LGU 3-7
Optional Controlled Braking BRC 3-8
CP1 Control Panel : CPi 3-9
CP2 Control Panel CP2 3-10
3-2
Contactor Unit (CTU)
The CTU performs the function of controlling the application of the 3 phase
input line power to the 1352 drive. The CTU is sized based on the total power
requirements of the application. The CTU consists of a main disconnect
switch, fuses, contactors and relays as shown in Figure 3-1. There are
basically two relay functions performed by the CTU relay logic. The main
contactor (K4) controls the application of three phase power directly thru the
CTU. This power is then applied to the LCU. A precharge relay allows power
to flow from two of the three phases on initial energization of the drive system
in order to precharge the capacitors located in the CBU.
When main disconnect S2 is closed, the Phase Loss relay K1 is energized and
power is supplied to the control transformer T2. The Phase Loss relay is
connected to the three phase supply immediately after the fuses and on a
phase different than the control transformer. This means that if one phase is
open, either K1 or T2 will be de-energized and the drive will shut down.
Transformer T2 provided 115 volt AC for the control circuit and 215 volt AC to
the Bus for control power to the other units in the lineup. If there are no faults
when power is applied, relays K2, K6 and K6A are energized and relay K5 is
deenergized. With K2 energized, bus pre-charge timer TR1 and contactor K3
are energized. Contacts from K3, supply single phase AC thru resistors R1 to
the line Converter Unit (LCU) which charges the DC bus Capacitor Bank
Unit (CBU). When TR1 times out it opens K3 and energizes the main
contactor K4 which applies full three phase line voltage to the LCU. The
setting for TR1 should not be reduced below 0.5 seconds to allow sufficient
time for the DC bus to charge. If the bus does not charge to a high enough
level, fuses F1,F2 and F3 may open when the main contactor K4 is energized.
Page 3-2
Bulletin 1352 5.3 System
Ifa CBU voltage imbalance occurs, relay K6 and K6A would energize which
would in turn energize relay K5 (CBU Fault) which seals in, de-energizing K2
and K4, thus shutting down the drive. The fault relay is reset by cycling the
E-STOP pushbutton or by opening the main disconnect S2.
AC Line
E ES O dd il 4 ss A 7 EE O EEE OY Ge OU о U MS ENS 6 OS vy Em FP IEE FY am | EE E ES O O ET @ - a
a =]
N
a CTU 460 KVA al 283 .
- |
25 a
52
Е-5тоР | |
AN . .
. FIN Fr
i i
КТ F4
119] K4 K6A ко T2 —{ —— |
> 20 | | F Ye ? Fa phase loss :
| | F
Door | — || CBI FAULT T | HI IT
Interíock — KS K6 K6A A 115 F6 |
1 |
| || ve ? aa VAC xa] : E NO; ET .
rs A
CBU OVERVOLTAGE Ä 215 у i | |
Ÿ vac KALI KA
| CBU, LCU ® = ! X) —9 <a
| Overtemp | Lg R1.1 R12
| Kl Ks K2 LI Y
+ GP HH FE © |
>]
. FAULT a
O Te A !
TRI - $Р K3 и
L: y pea e
‚ TRI
16 + ba O 9
. On - Off ToLCU
| TR1 Control
117)
i K3
. р
1 Bus Pre-Charge
K3 K4
Main Contactor
Fault Contact Rating
K2 120V, 6Amp
240V, 3Amp
Ba» e mh ше в вез с e e E E A E шыв с ше в шин а a e uN e ее ©
Main
Contactor
ка :
A A : Overvoltage
Main | —~ N
Contactar | herein kr rn i
Ka
12 19
E E OA & 4 YT ES 0 GS O OS © Gé GEE J Spl O AEs 4 ES NN um = | |
To < — —»> 215
3500 - T74 XS 4 — VACBUS
Figure 3-1. Contactor Unit For Basic System
Page 3-3
Bulletin 1352 5.3 System
§ FI " — © HER 4 IER = VE 5 JE 4 mE BD IEF ER fF EEE = us = EEN Sf ET © GS 6 eu € GEA à TOE 4 Gls = оны 6 EEE ans - a
The control circuit for the regenerative system is the same as the basic system
except that it has relays providing information from the Line Generating Unit
(LGU) as shown in Figure 3-3. Relay 2K indicates CTU ready and Relay 1K
indicates contactor enable. The two contacts are in series and must be closed
for precharge to occur (TR1 and K3 energizing). If either 2K or 1K open while
K4 is closed, TR1 will open which will open K4 and shut down the drive.
= =]
N CTU 460 KVA .
24 I
S2 ]
E -STOP .
— 07
I FIM F28 F3 I
| Ка K6A K3 < = | |
He de p T2 — ——{_T— .
> ES | | | | | F8 | phase loss FS |
Door | CBU FAULT — II d--- о 1 TT ‘
Interlock | <> (6 KA A 115 F6 |
| | 50 EZ VAC a] 460 .
CBU OVERVOLTAGE IN \ VAC [
№ 215 LL _ _ я
ка — — KA
\ VAC - =
— X1 —e | “a
CBU, LFU + | | Г 1 Rp
Overtemp KI K5 K2 [ nes me у |
| mo
Не |
FAULT |
— K2 Е |
. TRI - SP кз .
H Fo fs > E dit = ED vy EE 4 D mies = =p a aw is = JL) =
1K и TRI Г.
Г | N ) ,
19 On - Off | To LCU
| TRI Control |
bh , ‘
7 р - = een Am ыы ны om = “1
| | Bus Pre-Charge | | |
‘ TERMINAL |
5 ка Г]
ДН > ‘ J mock |
Main Contactor | CARD |
of, . . Г] 4 3500-T74
nro ° | i in LGU |
| | |
Hh — Contact Rating 2K |
t .
> 120V, 6Amp | — >] 2 |
i
240V, 3Amp . CTU [
| READY
El . 5 |
Fault i ! |
a) KZ mette een . | |
CBU |
r Overvoltage K6 . 2
Gh Main | | |
1K
" Contactor - |
> : i ENABLE
Main : . a TE de ae Eas aE À
T Contactor ee dar rr br rsa ara i — N |
ка .
: 6 Ed AEE e EE во ams EE ES 4 ml = ENE à SEE 0 SE EF Sy fF EE uo] рн оо Ш | | 3 | |
To 215
3500 - T74 x5 —» VAC BUS
Ty
Figure 3-3. Contactor Unit For Regenerative System
Page 3-4
Bulletin 1352 5.3 System
3-3
Line Converter Unit (LCU)
Figure 3-4 illustrates the hardware contained in the LCU. The LCU uses a 6
pulse diode bridge to convert the incoming 3 phase AC power to DC. The LCU
is equipped with a fan for cooling and a thermal switch to guard against
overtemperature. On 290KVA and larger units, the fan and thermal switch
have a manual switch (F51) in their circuits that is open when the unit is
shipped. This switch must be closed before the unit is started up to provide
power to the fan from the 215 volt AC bus and allow K2 in the CTU to close.
The DC choke is provided to filter the ripple from the diode bridge and along
with the CBU provide a smooth DC voltage to the inverters.
The RC snubber circuit in parallel with the diode bridge guards against
temporary overvoltages or voltage spikes by limiting the rate of change of DC
voltage. The bi-polar design reduces losses in the resistors during normal
Ul o
operation.
4 L+
LA %
| ~~ C1
‚|
W10
Ground TL = = "5
215 VAC
О 5
3 FS a
4 13 © A
FAN
3-4
Capacitor Bank Unit (CBU)
Figure 3-4. Line Converter Unit (LCU)
The CBU (Figure 3-5) consists of electrolytic capacitors to both filter the DC
ripple from the diode bridge and provide a source for reactive current.
On units larger than 300 KVA, each of the capacitors is fused for protection.
These CBU's also have thermal switches for protection against
overtemperature wired into the K2 Fault circuit and a fan or fans for cooling.
The power for fans is provided from the 215 volt AC bus. Discharge resistors
R5, R6 and R7 are provided to balance the voltage across the capacitors and
discharge the resistors when power is removed. The resistors are sized to
discharge the DC bus to below 50 volts in one minute per NEMA standards,
but the voltage should always be checked before allowing anyone to work on
the unit.
capacitors causes a considerable discharge current and is
A WARNING: Discharging a voltage as low as 20V by shorting the
potentially lethal.
Page 3-5
Bulletin 1352 5.3 System
- DC BUS + DC BUS
|
x Ï
CBU 730 KVA 1) He HI ТТ
—) 4 H—+3 Hs
x6 xa e x: O
не M1 Fan |" = Ф — — ¿
VAC Bus | M?Fan
3500 -CBS
— | А] 132 - CBS
Xi la 1 xa ON г x3 14 xa
Y y "Y! Y Y
THERMAL SWITCH | |
; |
| | [I +
To CTU K2 Fault Circuit To CTU K6 Fault Circuit
Figure 3-5. Typical Capacitor Bank Unit
A capacitor bank supervision card 3500 - CBS is provided on units 290 KUA
and larger to monitor the voltage balance on the capacitors. This signal is
used in the CTU K6 relay circuit to indicate an overvoltage. LED's are
provided to indicate if any section is below the minimum voltage, which would
then create a higher voltage across the other sections.
IMPORTANT: The LED's are not sensitive enough to assume that the DC
bus is discharged just because the LED’s are not lit. ALWAYS use a
voltmeter across the “+” and “-” terminals to check the bus level before
allowing anyone to work on the unit.
Page 3-6
Bulletin 1352 5.3 System
3-5
inverter Unit (INU) The INU converts the DC voltage from the DC bus output of the CBU to a
voltage and frequency controlled Pulse Width Modulated (PWM) waveform
which is then applied to the AC motor. Figure 3-6 provides an overview of the
major hardware components associated with the INU.
The Inverter Unit is described in detail in separate manuals. The Bulletin
1352 Installation and Maintenance Manual (1352 - 5.0) provides a basic
description and installation instructions. For a more complete description
‘and programming information refer to either Bulletin 1352 Vector
Programming and Operation Manual (1352 - 5.1) or the Bulletin 1352 Scalar
Programming and Operation Manual (1352 - 5.2) depending on the type of
inverters used in the system.
The one major difference with the inverters used as a part of the system is
they have a DC disconnect and fuses for isolation from the DC bus. The AC
control power is provided from the 215 volt AC bus and is controlled through
an auxiliary contact on the DC disconnect so that when the disconnect is
closed, AC power is supplied to the inverter.
Communication
Link
Discrete 1/O
Reference
Control
I/O CARDS
Galvanic
isn soos nes oer via Fiber Optic Link
TER TB E A AT A ATA TENA
E Ell te ee eee ea ele ne Tena e TT EE AAN er AE TAE DAR eee eee np
ehh
mea Tee
CD TAO NOE Sat Ta tema
ос ee - -;--
SOURCE from ROWER :]Î
CBU or я ee ii i
Common Bus SE jé se 3 : 5 RE rs
WARNING SHOCK HAZARD!
All shaded boards are at 600V
potential. Do not Touch !
3 phase Output to motor
Digital Tach (If Used)
(Required for Vector Control)
Figure 3-6. Inverter (INU) Block Diagram
Page 3-7
Bulletin 1352 5.3 System
3-6
Line Filter Unit (LFU) — The Line Filter Unit (LFU)is required on all systems that use a Line
Regenerative "front end”. The LFU provides the proper impedance which
makes controlled regeneration to the line possible, and also provides filtering
for the regenerated energy. The voltage feedback signal for the Line
Generating Unit is provided from the LFU through manual switch F71 (refer
to Figure 3-7). If these wires are ever removed it is important that they are
replaced on the same terminals since this signal is used to determine the
phase rotation information for the LGU as well as the AC voltage level. A
thermal switch is connected into the circuit of K2 in the CTU which will shut
down the system if an overtemperature condition exists. The LFU is force
ventilated with fans connected through a manual switch (F72) to the 215 volt
AC bus. The switch is also in the thermal switch circuit to shut down the
system if F72 is not closed. The switch is shipped in the open position and
must be closed prior to startup to allow K2 in the CTU to close.
To CTU K2 To CTU
Circuit «+ | | |
4 | x72 U1 Vi W1
F72 THERMAL SWITCH
TT
uu
A
+— 1 О LFU
215 VAC FAN 460 KVA
BUS
2 FAN
F71
2 a
«HO! 0-
Te À,
PE [12] y a
| oko |
Figure 3-7. Line Filter Unit
Page 3-8
Bulletin 1352 5.3 System
3-7
Line Generating Unit (LGU)
3-8
Optional Controlled Braking
+DC — LL y 2500 - aC —_—T rs
- DC
The line Generating Unit (LGU) is best thought of as an INU that can be
operated as a generator supplying power to the line rather than to the motor.
The LGU must synchronize to the existing line voltage and return the power
from the motor back to the AC line. The LGU is described in detail in Section
4 of this manual.
With the 1352 Drive there may be an optional chopper controlled braking unit
(see Figure 3-8). The braking unit consists of a control card (3500 - BCC),
GTO, diode and thermal switch. The control card monitors the DC bus voltage
and provides the logic signals to control the GTO (V1). A voltage selection
jumper Sl is provided on the card to select the proper resistor to match the
voltage level. An LED V22 is provided to indicate that the bus is charged.
The card receives its power through resistor R3 from the DC bus. The GTO
controls the power to the braking resistors. When V1 is conducting, the DC
bus voltage is applied across the braking resistor BRR connected to terminals
R + and R-. During turn off, the inductive current from the resistor circuit is
returned to the DC bus via diode V2. The thermal switch F11 monitors the
temperature for protection and will shut down the system if an
overtemperature occurs. The braking resistors are protected against
overcurrent with a thermal overload in series with the resistors and shuts
down the system if an overload occurs.
V22
| DO 660 X1.10
О © 575 BRR
135 - BRC
si R3
О © 500
О © 460
О © 415
О © 380 Л va
-UDC XK XG
OL1
vi R- I
Figure 3-8. Controlled Braking
(3500-BCC) indicates when the Bus is charged and the Chopper
Control Card has its operating voltages. It must not be considered
a safety indicator for servicing the braking system. The LED does
not indicate that all voltages have been removed from the circuit.
To guard against accidental contact with hazardous voltages,only
a DC voltmeter should be used to test for absence of voltages
before servicing any part of the drive or braking system.
A WARNING: The Red LED located on the Chopper Control Card
Page 3-9
Bulletin 1352 5.3 System
3-9
CP1 Control Panel
3-9.1
Figu
The CP1 Control Panel has several modes of operation, it can be used to:
1). Control Drive Operation
2). Alter Drive Parameters
3). Display Operating Values (output amps, frequency etc.)
4). Display other “test point” values from within the drive
5). Display fault diagnostic codes
General - The CP1 panel (Figure 3-9) is installed in the door of the cabinet
and 1s connected to the terminal block card by a 20 pole flat cable. The panel
contains 9 pushbuttons and a digital display. The CP1 panel cannot be used
for remote control. All set-up, operation and troubleshooting of the drive can
be carried out thru the control panel.
Display Code Letter 12 “Remote Indicator” 1
| TRIP
IL,
E ELA E UA ERE AAA E AAA am ay nn EE BE aaa a EA ARDER AAA e pi ee,
Tale AAA AA a AA NA A
Ta denia
ENT
NN CE a maar
ena A D erm me en le Le Ee at
AAA A ma Ta Tab yt PE ee Ee
ANA a a a aaa ale
RA LE aa aa ea Tm a ee ua AAA ee ee eta eal eT aaa Lea a Te a Te au a ta tata
NO. |
Six Digit Display (Parameter Numbers, Fault Codes)
Display Selection: Frequency, Current Voltage or Parameter.
Drive Start
Drive Stop
Increase Frequency Reference, Increment Parameter Numbers
Decrease Frequency Reference, Decrement Parameter Numbers
Parameter Number Selection
Selection of Local or Remote Control
Fault Reset and Parameter Value Storage
Programmabie Key (Reversing)
Remote Indicator Light
el al =
Sn 1Z 13 |© Ne Me win
Display Code Letter
Page 3-10
Bulletin 1352 5.3 System
3-9.2
3-9.3
3-9.4
Operating The Drive - Controlling Drive Operation is simplified by self
explanatory Display Buttons.
START & STOP are momentary pushbuttons to the drive.
LOC/ REM toggles between the local or remote frequency reference. Note the
“Remote” indicator light in the display which indicates if the drive is
— following the remote reference. Initial power up of the drive will be in the
local mode unless it is adjusted such as with Auto Restart.
REV Reverses the direction of rotation of the motor. This button is normally
defeated in software when shipped.
RESET is used to reset any fault. It also has another function when it is used
in the parameter mode (refer to section 3-9.4)
PARAM - Refer to section 3-9.4
DISPLAY - Refer to section 3-9.3
+ /- adjusts the local reference when in the operating (Normal) mode .
Depressing the “ +” button will increase the reference, “-” decrease it.
Response may appear slow since the adjustment initially is made to the
hundreth digit (0.01). Keeping the button depressed will speed up the change
as the adjustment digit will move to the tenth (0.10) and then to the “unit”
(1.00) digit. As you approach the desired value release then repress the button
to slow 1ts rate of change, See parameter mode (section 3-9.4) for additional
uses.
Display Operation - In the normal operating mode, pushing the display
button (Figure 3-9) will provide readings on:
- Drive Frequency References
- Output Frequency
- Motor Current
- Output Voltage
Pushing the display button will change from one display to the next.
The readings are identified by programmable code letters that appear after
the readout on the display .
Fifteen (15) programmable code letters are available for customer use. Five
(5) of the codes have been preset at the factory to indicate the following
readouts: (For additional information, see Publication 1352 - 5.2 Scalar
Programming and Operation).
E Control Panel 1 Local Frequency Reference
| REMOTE Frequency Reference
Output Frequency (Hertz)
Motor Load Current
E 1
Output Voltage
Fault Diagnostic Displays - If a fault occurs, a diagnostic code (Figure 3-10)
corresponding to one of the following faults will be displayed:
- Overcurrent
- Undervoltage
- Overvoltage
- Overtemperature
|
Page 3-11
Bulletin 1352 5.3 System
3-9.5
Semiconductor Fault or Malfunction
Processor Fault or Malfunction
Line Supply Unit (LSU) Malfunction
External Interlock
For detailed explanations on Diagnostic codes and their probable causes see
Section 5 Troubleshooting.
a De Ae EEE ETC
LE EN DLE LANE CO a a ee de at
O ELE TN NN CA ОН
a Wn we
= LA
BA Ls CANON аль К
я
ENE FET EEE
La
vy
Li -
> > Ea
2 ue К: i A Е: = a
: Ea
a М КИЗ “я и 5 A, a oy - LC, и вм р я e a ny
RL ban as
лы ~ =
: ВЕ
3 E AD
ST RE
: E xa
ma , EEN
Re : #8
E TNT TEE,
AA DC DT AL END DADA
Figure 3-10. Control Panel Fault Code Display.
Parameter Mode - The control panel is used for drive tuning and
troubleshooting. Parameters are effectively equivalent to the potentiometers
and test points in analog drives. Some of these values may need changing,
while others need to be viewed only. Viewing and changing parameters is
accomplished by following these steps:
1)
2)
3)
4)
Press the PARAM button.
The Display will read P__ 0001. Press “+” or “-” to reach the desired
parameter. Note the + and - buttons will change the value at an
accelerated rate similar to the description under Normal Operation.
Press DISPLAY to examine the value of that parameter.
To change the value, press “ +” or “=” to reach the desired value. Press
RESET to enter the new value into the parameter. The display will
automatically return to the normal mode if value is not changed.
Otherwise, pressing RESET will return the display to the normal mode
or PARAM to select another parameter for viewing.
IMPORTANT: For final parameter changes to be acknowledged and
stored in EEPROM, it is necessary to set parameter 008 (EEPROMLOCK)
to 1 before deenergizing the drive. When writing new values to EEPROM
memory, DO NOT interrupt power until the display acknowledges all
values are stored by the message SA51 disappearing from the display.
Many of the parameters have preset minimum and maximum values. Ifan
attempt is made to enter a value that is outside the range, SA53 will be
displayed on the panel. Entering a number that is within the parameter
range is necessary to clear the fault code. If an attempt is made to change a
parameter that cannot be changed, SA55 will be displayed then automatically
reset.
If you are unable to clear the fault in this manner, it may be necessary to cycle
power with the main disconnect switch.
Page 3-12
Bulletin 1352 5.3 System
3-10
CP-2 Control Panel
3-10.1
3-10.2
Description - The CP-2 Control Panel (Figure 3-11) is an optional panel used
for both DC and AC drives. It is used either on the drive cabinet, or remotely
mounted (Max. 300 feet). From the CP2 panel the drive can be controlled,
parameters set, faults and parameters displayed and functions programmed.
The panel contains 12 pushbuttons and a 16 character alpha-numeric display.
It also may contain 4 digital inputs (24 VDC or 115VAC) 4 digital outputs
(24VDC solid state) and one analog input. CP2 can be either flush mounted or
surface mounted. Refer to Figure 3-12 and 3-13 for dimension and cable entry
locations. All connections are made using the 48 pin terminal block X2 on the
Terminal Block Card at the bottom of the enclosure.
The panel is connected from serial channel 2 of the drive to serial channel 2 of
the CP2 panel. External power (24V, .5 amp) is needed for both transmission
and reception. The communication rate is set by means of jumper S2 on the
Terminal Block Card using pins 7 & 8 for 4800 Baud. The terminal points for
the VO circuits are shown in Figure 3-14.
+808 +280
Figure 3-11. CP2 Control Panel
Pushbuttons - The pushbutton functions are:
START Drive starts and accelerates to speed reference.
STOP Drive is stopped.
+ Increase frequency reference in increments of 1,
- Decrease frequency reference in increments of 1
+/- Increases the rate of change of the frequency to increments of 10
if pressed after the + or — key and increments of 100 if pressed at
the same time as the + or — key.
CRAWL Drive starts and accelerates to preset frequency set in parameter
160 if pressed with the + key or preset frequency set in parmeter
161 if pressed with the — key.
RESET Resets the fault display and sends a reset command to the drive.
PARAM Switches the control panel to select parameters.
VALUE Allows changing parameter values if pressed after the PARAM
key is pressed.
Page 3-13
Bulletin 1352 5.3 System
F1&F2 Programmable keys not used in the standard configuration.
Check your system drawing to verify if these keys have been
programmed for a function.
F3
BOTTOM VIEW
Changes the number system of the panel between unsigned
decimal, signed decimal and hexidecimal.
151
138
FRONT VIEW
e
Ze)
-
ООО |
OOO
O OO
OO O
e
ia
|
A
144
MOUNTING CUTOUT
NSS
‘ A \
N 281 N
‘
\ \
\ \
SN SN
` `
SN 139 \
>
2
NND
Figure 3-12. CP2 Flush Mount
288
Page 3-14
Bulletin 1352 5.3 System
BOTTOM VIEW FRONT VIEW
——————] O Ool--:
A - N A
6 *)
=
me
288 O O O
281 О О О 296
O OO
OOO
J
Y e —
НН =
I
87.5 »
120
ВО END VIEW
A NT
4
E
144 138
ÓN LA.
i
Lu
- |< —
151 11
Figure 3-13. CP2 Surface Mount
Page 3-15
Bulletin 1352 5.3 System
Use Jumpers
X2
46 9
47 ©
|
| +2av | ;
44 ©
45 O—
110/220
VAC o
ovDE © 10
110/220
+ 24VDC
VAC"
o 8
ov o
110/220
VAC"
24VDC
E
—
—
—
ov o
110/220
VAC"
——
24VDC
| 2
wv
ЧР
w
-
ov O
IN - for -5V,
ебу ОМУ © 43
‚©
Jumper for
-5V € 5V.. 41
oO
4
e ‚oo 20
Jumper for
4-20mA 39
‚о
Jumper tor
1-5mA “-. 38
O
SUN
N. OZ
For internal
157-CPT 24VDC Power
Connection
+5V DIGITAL QUTPUTS Remove
— (200 mA Max) X2 sumpers
28 For External
27 > 24VDC Suppiy
—
DIGITAL INPUTS Ours Y 6 26 os
2 _
т:
——
— no 23 >
mes —
Out 1 Y—- ; 22 0.
21
Y > + Го ©
In 1
1. 19
Qut 2 —
—— 18 ot
17 i
Y FS
— In 2 15 >
—
ows Y 5 FED
1
Y | st
— In3 SERIAL
COMMUNICATION
CHANNEL
36,
ANALOG INPUTS — <y ©
-— RECEIVE 35 0.
Channel 1
34
Ot
—
Y =, SEND o.
_ 325 +
tiff
| * RECEIVE Mo.
Channel 2
30 © +
—— |
YF, SEND 29 6
* 110/220 VAC only available on cards
with a “D” in their Code
Figure 3-14.
NOTE: If 130-CPT Card Is Used, + 24V Is Terminals
45 and 47,0V Is Terminals 44 And 48.
10 Connections
Page 3-16
Bulletin 1352 5.3 System
3-10.3
3-10.4
3-10.5
Displays - The normal display on the CP2 control panel (Figure 3-11) has
three sections that are programmable. The default settings are:
Frequency Reference - Left Display
Frequency Feedback - Middle Display
Drive Status - Right Display
When a fault occurs the display is changed to display the fault message which
is a 16 character message describing the fault. For the list of faults refer to
Section 5.
Setting Parameters - Drive parameters can be displayed and changed from
the Control Panel. Pressing the PARAM key changes the display from the
default to displaying parameter addresses. In the parameter mode the CP2
will display the parameter address in the left portion of the display and the
parameter value in the right hand portion. To change the parameter
displayed, the follwing keys must be used:
+ or - Increments the parameter address by 1.
+ or —, then +/- Increments the parameter by 10
+ or —~ with +/- Increments the parameter by 100
To change parameter values, simply select the parameter to be changed, then
press the PARAM and VALUE keys simultaneously while depressing the +/-
and + or - keys to adjust the value. In this mode, pressing the +/- key
simultaneously with either the + or — key will increment the value in units of
1000 instead of 100. Parameters that cannot be changed will display
“ILLEGAL PARAM” when an attempt to alter them is made. Changing back
to the original displayed address will reset the message. If a parameter has a
value greater or less than the limits, the display will indicate “BAD PARAM
VALUE” and the limit will be entered into the parameter.
Scaling the Displays - The values shown in a standard display may be
scaled as desired. There are three parameters for scaling each display:
coefficient, divider and decimal point. The coefficient is the multiplier that is
used with the variable while the divider, as the name implies, is the divisor in
the formula. This combination determines the numbers displayed and the
decimal point is determined by the decimal parameter. The following is a list
of the display parameters:
PARAMETER FUNCTION
100 Speed Coefficient
101 Speed Divider
102 Speed Decimal Point
104 Current Coefficient
105 Current Divider
106 Current Decimal Point
The decimal point parameter with a value of 2 indicates that a decimal point
will appear to the left of the second least significant digit. As an example, to
scale a frequency parameter (.01 Hz. increments) to display in feet per minute
where 60Hz. equals 150FPM, the parameters could be set to the following
values:
PARAMETER VALUE
100 = 1 (coefficient)
101 = 4 (divider)
102 = 1 (decimal)
The frequency parameter would be 6000 (60.00Hz.) when the speed was
150 FPM. Multiplying by parameter 100 (1) gives 6000 and dividing by
parameter 101 (4) gives 1500. The value of parameter 101 determines that
there will be one decimal place and the display will show “150.0”.
Page 3-17
Bulletin 1352 5.3 System
3-10.6
3-11
Control Card
Installation - Normally installation of the CP2 panel is accomplished when
the drive is wired per the interconnection diagram provided with the drive. If
there is a desire to modify the installation, the connections for each of the
functions is described in this section.
Figure 3-14 details the pin numbers for each of the functions and the typical
connections that could be made.
Figure 3-15 illustrates the general layout of the Control Card. The basic
hardware on the control card (with the exception of software chips related to
LGU,Scalar or Vector control) remain the same on all drive applications.
Galvanic isolation of signals coming into the drive from external devices is
accomplished thru the use of a fiber optic serial communication link between
the Control Card and the I/O Cards. Devices V1 thru V6 provide for
connection of several fiber optic links. Only a few of the fiber optic
communication devices may be used depending on the specific application.
Power supply inputs come thru 20 lines of the 40 pin ribbon cable connected to'
connector X1. The other 20 lines of this connector are used for the gate pulse
signal output from the Control Card to the Pulse Amplifier (s) (and the GTO
Chopper Control card when used). Connector X2 is a 40 pin ribbon cable
connector which provides interface between the Control Card and the
Matching Card.
Connectors X3 thru X5 are used for current feedback information coming
from the Hall - Effect transducers. In the GTR units, only X3 and X4 are used.
In the GTO units, all three connectors are used.
Connector X6 provides for analog output signals from 4 Digital to Analog
(D/A) converters located on the Control Card. Because the Control Card is at
the DC Bus potential, the analog output signals are also at DC Bus potential.
Therefore, in order to use the analog outputs, an optional hardware
conversion unit, which provides isolation from the DC Bus potential, must be
used. |
The microprocessor (D8) carries out all functions on the Control Card with the
exception of fault tripping, which is a hardware function. EPROM chips (D17
and D18) contain the main operating program, and will be different
depending on the specific type of control being used (Vector ,Scalar or LGU)
and the firmware revision provided. In addition to the parameter information
stored in RAM (Random Access Memory), there are several parameters which
are related to set-up and configuration of the drive which need to be retained
in the event of a power loss. This type of memory is called EEPROM and is
contained in D16. If the power is lost, all critical drive set-up parameters will
be retained in this memory. In addition to the EEPROM backup, there is a
battery on the control card which maintains some of the RAM memory if
power is lost.
Jumper switch SI is used to set the baud rate for serial communication.
Position a- b corresponds to 9600 baud and a- ¢ corresponds to 4800 baud.
Switch $1 should always be in the a- € position. Jumper switch S3 is used to
disconnect the battery backup when the control card is in long term storage.
When S3 is in the a - b position, the battery back-up is operational; when in
the a - € position battery backup is disabled. During normal operation, S3
should be in the a - b position, and for long term storage, in the a - € position.
D4 controls the write-enable function of the EEPROM backup. When S4 is in
the a - b position, writing to EEPROM is enabled, when in the a - c position,
writing is disabled. If EEPROM writing has been enabled by S4, backup of
the drive set-up parameters is controlled in software.
Page 3-18
Bulletin 1352 5.3 System
INVERTER
A2 3500 - СОЗ
_ ol 103 = CON
eee e—— Power Supply Inputs
== |x
|
mu... о >" Gate Pulse Signal Qutputs
У ON OFF No Power ,Not Ready or Running (GTR Only)
AH <— Status Indication LED Ts Power & Ready
rex FLASHING RAM Fault Detected
al
rooms | “— Matching
ma 2U —> Card Battery
ee Backup
na witc
©.
ОУ м Feedback
ol folro Signals From $3
Hall Effect = b
X x x Transducers 9 а ON
| 4 | 5 e c OFF
=== Lo] Lol lo)
= [0]
Fosse -—» D-A Converters TT
eo | (Optional) : G4
еее 6 Firmware
== lol $200 TT Ew
— ha
| | DB Write
[OOO] $1-€— Enable
Microprocessor Switch
b-a Enable
a - c Disable
To
Connection |__ Fiber Optic
Card | Connectors
Baud
| Rate —» ba
N Always A-C $1
NOTE! The control card is normally supplied and stored without the Firmware
Chips D17 and D18. They must be transferred from the board being replaced.
Software Chip D16 is normally shipped empty. You MUST transfer your software
by transferring the D16 chip from the board being replaced or by
reprogramming the drive.
Figure 3-15. Bulletin 1352 Control Card
Page 3-19
Bulletin 1352 5.3 System
4 3-
12.
GTO Pulse Amplifier Card
The GTO units require three Pulse Amplifer cards. Figure 3-16 shows the
Pulse Amplifier Card with the amplifier circuits for the two GTO's associated
with one phase of the output. A shared logic circuit produces gate control
signals for both GTO’s and ensures that the two devices associated with a
single output phase are not gated on simultaneously.
The gate control signals are sent to individual pulse amplifier circuits for each
GTO. Signals between the logic and the amplifiers are optically isolated. The
amplifier circuits then produce the gate signals for each GTO. In addition to
the gate signal, each amplifier circuit provides the short circuit monitoring of
the output of the inverter and protection of the amplifier circuit for each GTO
in the event of a shorted device.
In the event of a short circuit on the output, all GTOs are turned off. In the
event of a shorted device, the fuse associated with the individual device will
open protecting the amplifier circuit. The logic on the card also detects a
shorted GTO and prevents firing of the other GTO controlled by the card.
Feedback information pertaining to the actual state of each GTO is returned
to the control card and is indicated by an LED associated with each GTO.
During normal operation all LEDs should be lit, if a fault occurs the LED
associated with the affected GTO will not be lit.
Inverter A4, PP} . Rg ee 25, 26 EEE ENE AA o Er EE EERE EEE EE EEE EEE See Table 3-2
5e HHH HHH помо
fc] xT2 | хтз | =]
XA | x ) XA2
|
To T2 + cap xa | || [44 + LE To
Gros _| [XK XK?) |_6Tos
vin | | via
V12 | VIS
V13 | | V16
XG2
XG1 — | COMMON | — =,
\ | LOGIC |
| |
H1 | | H2
X A — |
I
\
Pulse Channel
F1
Positive Branch
| =
1 42V/80kHz
X3
Negative Branch
- œ
ae and”
AUXILIARY VOLTAGE SUPPLY
Ti
F2
NOTE: Fuse and LED locations shown are for 180KVA 460V, INU. Actual location of fuses and LEDs for larger units will vary slightly, but
will be located in the regions designated Upper and Lower Branch Pulse Channel and will have the same numeric designations as above.
Figure 3-16. Bulletin 1352 GTO Pulse Amplifier Card
Page 3-20
Bulletin 1352 5.3 System
X1* 40 Pin Control signals from Control Card and feedback signals back
Ribbon to Control Card
X2* 40 Pin Control signals from Control Card and feedback signals back
Ribbon to Control Card
ХЗ 4 Pin 42V 80Khz square wave from Power Supply used in each
Plug amplifier circuit to produce DC power.
XA1 1 Pin Tab Anode connection to GTO in positive leq of bridge
XG1 1 Pin Tab Gate connection to GTO in positive leg of bridge.
XK1 1 Pin Tab Cathode connection to GTO in negative leg of bridge
XA2 1 Pin Tab Anode connection to GTO in negative leg of bridge
XG2 1 Pin Tab Gate connection to GTO in negative leg of bridge
XK2 1 Pin Tab Cathode conection to GTO in negative leg of bridge
* NOTE: Signals flowing thru cables connected to X1 and X2 are daisy chained from one card
to the next, so that control signals leaving the Control Card directly enter only the first Pulse
amplifier card thru connector X1. Signals are then transferred from one card to the next
going out thru connector X2 and entering thru connector X1.
Table 3-3. GTO Pulse Amplifier Card Fuses and Indications
H2
Fuse associated with GTO in positive leg of bridge
Fuse associated with GTO in negative leg of bridge
Status indication of GTO in positive leg of bridge
Status indication of GTO in negative leg of bridge
Table 3-4. GTO Pulse Amplifier Card Fuses and Indications
180 3500 - A20 120 - PAC
460 3500 - А22 122 - РАС
730 3500 - А23 123 - РАС
140 3500 - А20 120 - РАС
210 3500 - А20 120 - РАС
273 340 3500 - A21 121 - РАС
540 3500 - А22 122 - РАС
$ 870 3500 - А23 123 - РАС
Page 3-21
Bulletin 1352 5.3 System
3-13
GTO Chopper Control Card
INVERTER A-7
To GTO V17
E" EEE EEE EEE E E EE
1 и
EE EAE EAE ER ENEE
EEE EEE EEE
EET TT EET]
Trt ETE
“BEE TET hak
The Chopper Control Card (Figure 3-17) controls the gating of the chopper
GTO. Energy from the commutation of the GTO's in the main inverter bridge
is fed back to the DC bus thru GTO V17. The amount of energy transferred is
determined by the duty cycle of V17.
Control logic on the Chopper Control Card receives a clamping capacitor
voltage reference signal from the Control Card which has been derived from
the Matching Card. This value is compared to the actual measured value of
the capacitor voltage by means of DC bus voltage and GTO terminal voltage
feedbacks. The error between the reference and feedback determine the duty
cycle of the chopper GTO and is used to produce a gate signal for the GTO
which is then amplified.
The amplifier circuitry is very similar to that used in the GTO Pulse
Amplifier cards. In addition to the gate signal, the amplifier circuit provides
for monitoring of the power supply and protection of the amplifier circuit in
the event of a shorted device. In the event of a shorted device, fuse F1 will
open protecting the amplifier circuit.
Daisy Chain from Power 3500 - CH5 (460V)
Supply & Pulse Amp Control Card 3500 - CH7 (575V)
42V /80kHz Temperature Monitoring
Ня И GENTE
x1 Ц 125 - CHC (360V)
X2 | Y / x3 | 127-CHC(575V)
u“
MT 6 ПГ |
C11
LED ON = Aux Voltage OK
V42 |
Feedback
Voltages
T1
From D.C. Bus.
F1
Protection for
Amplifier Circuit
Figure 3-17. GTO Chopper Control Card
Page 3-22
Bulletin 1352 5.3 System
3-14
GTO Power Supply Card The Power Supply illustrated in Figure 3-18 is used to supply voltages to both
INVERTER
A-3
Bh Bo. fet RR
RE CR
в E 4 Fx x
Ь: a
1er e
я
the Control Card and the Pulse Amplifier Cards. The DC voltages used for
control are derived directly from a +300 VDC input from the Auxilliary
Power Card which is taken directly from the DC bus. DC voltages produced
are +/- 14VDC, and +5VDC. In addition to DC voltages, the Power Supply
produces a 42V 80 kHz square wave which is used in the Pulse Amplifier
cards and by the Auxilliary Power Card. The Power Supply also provides
feedback information on the status of the DC bus to the Control Card.
+ 300 VDC Power input from SEE TABLE 3-5 FOR
Aux Power Card IDENTIFICATION NUMBERS
NT FUN НН ПО TTT Er TTT TTT
| ог"
+
X3 X2 | XI y
To Control Card & Pulse Amp Power Supply Status
42V 80KHz + 14VDC, 5VDC DC Bus Status “ON” = OK
+ Square Wave
Output To
Pulse
F1 +300v0C Amp Cards & F4 F3 F2
Chopper Card o
- 14 VDE +5 VDC 14 VDC
Т I T T
1 1 t 4
® 1; BD 1 ®
i 1
à DO
1 I I i
t 1 I |
ı 1 o
| | | 1
| | | |
| | I
ФФ 1 OD O
| 1 }
Figure 3-18. GTO Power Supply
Table 3-5. Identification Numbers
460 180 - 460 3500-P10 110 - POW
460 730 3500 - P11 111 - РОМУ
575 140 - 540 3500 - P12 112 - POW
575 870 3500-P13 113 - POW
Page 3-23
Bulletin 1352 5.3 System
3-15
Auxiliary Power Card The Auxiliary Power Card (Figure 3-19) is used to provide + 300 VDC power
to the Power Supply Card. The +300 VDC is normally derived directly from
the DC bus. Upon initial power up, or if the DC bus voltage drops
momentarily, a secondary source of power provided to the Auxiliary Power
Card in the form of 220 VAC from the INU control transformer is rectified to
+300 VDC and supplied to the Power Supply. A 20 VAC input from the INU
control transformer is rectified to produce auxiliary + 24VDC. The 42V 80
kHz square wave from the Power Supply is used to produce an auxiliary
+/-14 VDC.
INVERTER A-9 3500 - AP2
167 - APC
C1
X2
42V 80 KHz Sq Wave
Input Power
Bus Voltage
215 VAC
20 VAC
to Pulse Amp Cards
X1
A
T1
K1
X3
=
+ 14824VDC
to IOC Cards
Figure 3-19. Auxiliary Power Card
Page 3-24
Bulletin 1352 5.3 System
3-16
Input/Output Connection
Card
The Input/Output Connection card (Figure 3-20) is used to provide
interface between the control and external devices including discrete logic
control devices and analog signals in addition to serial communication and is
typically used for single drive applications. In addition, the card is also
capable of accepting tachometer feedback signals.
Jumper switches on the card are used to scale hardware on the card for the
rated voltage of the tachometer. S1 is used to select the power supply voltage
for the tach where a - bis +24VDC and a - с is + 13VDC. Switches S2 and
53 are used to scale the feedback circuit for the tach voltage used. Position
a - b for both S2 and S3 is used for + 13VDC tachs and a - ¢ is used for
+24VDC tachs. Jumper switch S6 is used to determine the type of signal
used for the discrete analog input coming into the card on X3 terminals 18
and 19. Position a- b scales the circuitry for current signals either 0 - 20 mA
or 4-20 mA and position a - ¢ scales the circuitry for voltage signalsof 0- +5
VDC.
Table 3-6. Input/Output Card Jumper Switches
51 Tachometer supply voltage selection
b +24 VDC
С + 13 VDC
52,53 Tachometer feedback voltage scaling
b + 13VDC
с + 24 VDC
54 Not Used
55 Not Used
se Scaling of analog input
b 0-20 mA, 4-20 mA
с 0- +5VDC
Page 3-25
Bulletin 1352 5.3 System
INVERTER A1
To 1/0 Option
Cards
To 1/0 Option Fees
Cards
fee EEE
(pj
3500 - AIO
Control Card 164 - AIO
3500 - СОЗ
m 103 - CON
Ol | Val N
VITACHA «<——— S
i I vaz
xa | | V2:TACH B <———|[i EH S
. V13
! 1
V3iChannel Е 5 Fiber Optic Connectors to
O Vig : Control Card
NL] V4!'Channel 1 ———»l: : R
| i
Г: - Vaz
i i
© V5Channel2 —Ë F S
! ! vas
I I + 3
. V6.Channei 2 ЧЕ R
x6|| l 1
/
! i
O| |O
Control Panel 1
deidades
To Terminal «
x
Un
|]
O] 10
Block Card FE тн
174-TBC
| |
X1
©.
Control Power Voltages
From Power Supply or
Aux Power Supply
24, + 13,0 VDC
X8
bac
xui[Te ] s [066] [©00]s3
bac
хи. ТЕ ] s2[000] [OOO] s6
bac
24 VDC
Figure 3-20. Input/Output Connection Card
Page 3-26
Bulletin 1352 5.3 System
3-17
CBU Supervision Card ~~ On Capacitor Bank Units of 290 KVA and larger, the voltage across each
individual segment of the capacitor bank is monitored for overvoltage
conditions. Monitoring is performed using the CBU Supervision Card. LEDs
on the card indicate the condition of the voltage level accross each capacitor
segment. Either 3 (460V) or 4 (575 V) LEDs will be used depending on
whether 3 or 4 capacitor bank segments are connected in series. Under
normal operation, there should be one LED lit for each capacitor bank
segment. If the voltage on a particular capacitor bank segment goes below the
limit value, the LED associated with the segment will not be lit, and a relay
circuit in the CTU is alerted to the fault.
CBU A1 3500 - CBS
132- CBS X 1
с
V30 Status of C1 | |
Je Capacitor
Segment | |
| | X2
Status of C2
v23 Capacitor >
( ) Segment | ||
To CTU Fault Connections
Monitoring | | to
Cult Kb \/28 Status of C3 Capacitor
® N Capacitor X3 Bank
Qe X seamen 4 | ser
DO | |
400V AC Line | |
Maximum
a 500V Voltage
d © Switch | |
660V X4
51
Г |->
V27 Status of ca
Je! Capacitor | |
Segment
X5
UT EEE EEE EEE EEE EEE EEE EEE
"ENEE EE EEE NN
E LE E EEE EE EEE EEE EEE
TE LE E E E E E EEE
TEE р,
E EEE
TEE
EEE
e" "e" vd" e Ja "do "EEE EEE EEE EEE E EE
rd Etre tir Err EEE EEE E EEE ETE
"ей а а ана Ен па оон а о А о ее ао, ее а Р.Р.
LE ENEE TET YT ET eT Во,
e ETT
EEE
E EEE EEE
"EEE EEE EEN NENE ae ua me vie vil alo та;
EA EEE EAT EEN EEE
"EA EE EEE EEE EEE EEN EA
ENE
TEE
Figure 3-21. CBU Supervision Card
Page 3-27
Bulletin 1352 5.3 System
3-18
Matching Card
The Matching Card (Fig. 3-22) is mounted on the A2 Control Card and 3500-
CO3 provides a matching circuit for the DC bus voltage and inverter phase
currents based on the KVA rating of the LGU and the rated voltage. Near the
center of the board are two selection jumpers S1 and S2 that set the rated AC
voltage. Unless otherwise specified, the jumpers are set to 460 volt.
Figure 3-22. Matching Card
ae RE.
TABLE OF CONTENTS
4. Line Generating Unit
4-0. General
4-1. Theory
4-2. Operation
4-2.1. General
4-2.2. Main Contactor
4-2.3. Starting
4-2.4. Stopping
4-2-5. Automatic Restart
4-3. Firmware
4-3-1. Reading Software And Firmware Diagrams
4-3.2. Overview
4-3-3. DC Voltage Reference
4-3.4. DC Voltage Controller
4-3-5. Frequency Controller
4-3.6. Reactive Current Controller
4-3.7. AC Voltage Controller
4-3.8. Current Limit
4-4. Modes Of Operation 10
4-4.1. PUCMODE 162EE (Parallel LGU's Oniy) 10
4-4.2. UCREFMODE 160EE (DC Volts A Function Of AC Volts) 12
4-4.3. DBMODE 90EE (LGU Operates in Regen Only) 12
4-4.4. QUCMODE 161EE (Maintain Power Factor Via DC Volts) 13
4-4.5. IQCONT 48EE (Select Power Factor Control) 13
4-5. Start Up “Sector” Adjustment 14
4-6. Operator Interface 17
4-6.1. CP1 Control Panel 17
4-6.2. Serial Communications Software 20
Chapter
4
BULLETIN 1352 LINE GENERATING UNIT
4-0
General
4-1
Theory
The Line Generator Unit (LGU) is used to supply power to the DC Bus feeding
the inverter units as well as regenerate excess power from the motors to the
AC line. The LGU hardware is the same as a Bulletin 1352 Inverter Unit
(INU) with the exception that it contains different firmware chips, matching
card, control card and IOC card. A Line Filter Unit (LFU) is always provided
with the LGU to provide reactance in the system.
WARNING: When voltage is supplied to the LGU a potentially
fatal voltage is present between the cards and the chassis. The
control card is at full DC Bus potential, and the leads running to the
matching card are at full line potential. Only qualified service
personnel familiar with the Bulletin 1352 should attempt to service
the drive or make measurements on the cards.
Due to the greater capabilities of the LGU in comparison to other regenerative
drives it may appear complex, but in reality it utilizes a less complex control
scheme than an INU. There are three functions of the LGU control scheme
when regenerating:
1) Controlling the active current
2) Controlling the reactive current
3) Maintaining synchronization with the line.
This is accomplished rather simply first when the regenerated power from the
motors increases, the frequency of the LGU attempts to increase. This
increases the phase angle between the LGU and the line thus producing more
active power to the line. The reactive power is determined by controlling the
voltage drop across the reactor in the (LFU).
The frequency of the LGU (Active Current Controller) is controlled according
to the voltage level of the DC bus. When a motor is driven by the load it
produces a higher voltage which is rectified by the inverter to DC and forces
the DC bus level higher. The LGU control maintains a fixed DC bus level by
increasing the frequency reference to the LGU as the DC voltage increases.
Since the output of the LGU is tied to the AC line, the frequency doesn’t
actually change, but the phase angle between the LGU and line changes.
Consider the phase angle as an adjustable valve, allowing more or less current
to be returned to the line to maintain the DC voltage at a constant level.
The reactive current controller is also relatively simple, in that it compares
the line voltage and the voltage from the LGU to maintain a fixed voltage drop
across the reactor in the LFU. Since the impedance of the reactor is almost
entirely reactive, the voltage drop across the reactor determines the reactive
current. Normally the LGU is adjusted to maintain zero reactive current, but
it can also supply reactive current to the line in the same manner as a
synchronous generator when it is overexcited.
Synchronizing the LGU to the line is accomplished by using the voltage
measurements and controlling the LGU starting point based on when the line
voltage crosses zero. The zero crossing point is then corrected for the time the
control takes for measurement, to accomplish a perfectly smooth start.
Page 4-2
Bulletin 1352 5.3 System
4-2
Operation
4-2.1
4-2.2
4-2.3
4-2.4
4-2.5
Besides Start and Stop, the LGU operation is virtually automatic and requires
little operator input.
General - Closing the DC disconnect and then the main CTU disconnect in
that order, connects power to the control card in the LGU. The microprocessor
on the control card then initializes and illuminates a red LED on the card.
The CP1 panel displays a status message after initilization is successfully
completed. Since the main contactor is open, there is an internal DC
undervoltage fault in the LGU as well as a chopper undervoltage fault. After
the contactor closes, the LGU attempts to reset these faults. The LGU does
not report that it is ready until these faults have been removed. With the first
START command, the firmware again executes a RESET command.
Main Contactor - The main contactor is interlocked with the LGU so that it
cannot be closed until the LGU indicates that it is ready. The main contactor
is controlled with an "ON - OFF” selector switch on the CTU enclosure door.
When the main contactor closes, it sends an interlock signal back to the LGU
to indicate that it is closed and starts the LGU.
Starting - The START command can be given from any of the control devices
used with the drive (CP1,CP2,PLC,DRC etc.). Normally the “ON-OFF”
switch on the enclosure is used for the start command. This command is sent
to the LGU control as well as closing the main contactors. When multiple
control devices are used it is important to use only one at a time since the
commands to the LGU can be overwritten if control is attempted from more
than one location.
IMPORTANT: Ifthe diode bridge mode is selected, the LGU may not start
immediately but will begin to monitor the DC voltage for start-up in the event
regenerative braking to the line is required. (Refer to Section 4-4.3)
Stopping - The STOP command can be given from any of the control devices
used with the drive. The "ON-Off” switch on the enclosure is normally used
for the stop command.
The EMERGENCY STOP pushbutton is a maintained position pushbutton
with a red mushroom head located on the CTU enclosure. This button will
open the main contactor in the CTU and remove power to the CTU control
circuit. An interlock between the LGU and the contactor shuts down the
LGU.
Automatic Restart - When the LGU stops due to undervoltage, overvoltage
or overcurrent the LGU is usually programmed to reset the fault and attempt
to restart. This operation is termed Rapid Automatic Restart (RAR). [f the
fault occurs again within 16ms of this first restart attempt, the LGU will
make a second attempt after a preset delay. This delayed restart is termed
Delayed Automatic Restart (DAR). If a third fault occurs within 16 ms of the
DAR, a third attempt is not made, instead the LGU is stopped and the fault is
reported on the control panel.
If the second (or third) fault occurs more than 16 ms after the previous fault,
the LGU makes a new RAR attempt. In order to eliminate excessively
frequent restart attempts, the LGU supervises the restart function by
limiting the number of RAR’s in a given period of time. Both the number of
restarts and the time period are adjustable. When an RAR or DAR is
successful, a diagnostic message will appear on the control panel indicating
the cause of the fault and if it was an RAR or DAR.
Page 4-3
Bulletin 1352 5.3 System
ACVOLTAGE
(4-3.7)
4-3
Firmware
4-3.1
UACT
223
The microprocessor for the LGU comes with a built-in program for controlling
the LGU. This section will describe this program starting with a general
overview of the functions and then explaining how the functions are
developed. The Firmware Overview Diagram in Section 7 of this manual
shows the complete detailed diagram.
Reading Software and Firmware Diagrams - The software and firmware
diagrams for the INU and LGU follow similar arrangements. Each signal
reference and control section is labeled with a reference to the section of the
manual describing that portion of the diagram. Each section is composed of
various function blocks. The inputs to a function block are shown on the left,
outputs on the right. Other parameters affecting the function block are shown
above or below the block. Two examples are detailed in Figure 4-1.
UCMAX DC Voltage
«ED Reference
UREF (4-33)
DUREF
222
SUM 221
UCREFG
MIN
UCMIN
Figure 4-1. Function Block 1/0 Parameter Example
Parameters UACT (223) and DUREF (222) are summed to form parameter
UREF (221) which is part of the AC Voltage Controller and is described in
section 4-3.7. All three of these parameters are provided as test points.
The other function block shown in Figure 4-1 is a limiting function. UCREFG
(26) is an adjustable reference input which is limited between the maximum
value UCMAX (154) and the minimum UCMIN (153) This block is a part of
the DC Voltage Reference circuit and is described in section 4-3.3.
Page 4-4
Bulletin 1352 5.3 System
4-3.2 Overview - The control circuit for gating the GTO’s of the LGU has three
basic functions as described in Section 4-1. The DC Voltage Controller
which modifies the frequency of the LGU; the Reactive Current Controller
that modifies the AC voltage and the Synchronization Control which is
actually a measurement function that inputs to the DC Voltage Controller.
An overall block diagram of the control is shown in Figure 4-2. The Reactive
Current Controller and the AC Voltage Controller are the two sections that
form the AC Voltage Reference (UREF). The Frequency Reference (FREF) is
formed by the DC Voltage Controller and reference functions being added to
the line frequency. The DC Voltage Reference Optional Functions are
separated since they may or may not be included in the system provided. The
numbers in each block indicate the sections in this manual that describe the
function.
DUREF UREF
222 221
IQREFG Reactive o AC Voltage Q
| Current Controller
Controller
4-3.6 | 4-37
225
DC Voltage UACT
Reference
Optional |
Functions UCREF ———]
4-4 218 FREF MODULATOR
220
UCREFG DC Voltage | — DC Voltage SUM
Reference | Controller
4-33 4-3.4 a )
4-3.5
224
UCACT
Frequency
FNET
Controller
86
4-3.5
Figure 4-2. Firmware Overview
Page 4-5
Bulletin 1352 5.3 System
DC Voltage
Reference
4-3.3
DC Voltage Reference - The primary flow of the voltage reference (Fig. 4-3)
starts with UCREFG (26) through the MAX/MIN block and SELECT block to
the SUM block. The MAX/MIN block limits the value of UCREFG between
UCMAX (154) and UCMIN (153). The SELECT block is used to select either
the optional functions or UCREFG for the DC voltage reference. The Reactive
Current Trim is also an optional function. The optional functions are
presented in section 4-4 of this manual. The Active Current Limit Trim is
added to UCREFH (240). The operation of the Active Current Limit Trim is
discussed in Section 4-3.8. The sum of these signals is again limited in a
MAX/MIN block with the same limits as UCREFG. The voltage reference is
then sent to a RAMP block that limits the rate of change of the reference to
UCSTEP (155) so that the controller does not receive large step changes in the
reference. The values of UCMIN, UCMAX and UCSTEP are all in units of
.1% of rated (1000 = rated). UCMIN default setting is 900 (90%), UCMAX
default setting is 1200 (120%) and UCSTEP default setting is 10 (1% in a 4
ms. increment). The output of the ramp block then goes to the DC Voltage
Controller.
DC VOLTAGE REFERENCE
Optional
Features
4-4
UCREFG
UCMAX
>
MAX
MIN
SELECT 1 Ucrern
240
SUM
MAX
RAMP |
90 | DC Voltage
DBEMODE a Controller
UCREFMODE NU
Reactive A | UCSTEP
Current Trim
153
UCMIN
QUCMODE
4-4
ACTIVE
CURRENT
LIMIT
TRIM
4-3.8
Figure 4-3. DC Voltage Reference
Page 4-6
Bulletin 1352 5.3 System
4-3.4
4-3.5
DC Voltage Controller - The DC voltage Controller (Figure 4-4) compares
the DC voltage reference UCREF (218) with the DC voltage feedback signal
UCACT (224) and this difference or DELTA is fed to the three controllers.
The “PD” controller is the primary controller. The parameters used for
computation are complex and are calculated by the LGU from the inductance
of the LFU (LLGU 65) and the capacitance of the CBU (CLGU 66). The
computational parameters are KDLLL (55) and KFLL (57) which have the
values of 98 and 1600 respectively. |
The “D” controller is only active during large changes in the DC voltage. If
the difference between UCREF and UCACT exceeds 10% of the rated DC
voltage, the “D” controller is active. The 10% values are determined by
UCDIFMIN (60) and UCDIFMAX (59). Again the gains are determined by
the inductance and capacitance of the system as well as KAA (71) and KII (72)
which are factory set at 600 and 180 respectively.
The “I” controller output is slight when compared to the output of the other
controller and its function is to bring the DC voltage error to zero. The gain of
the “I” controller is PUI (53) and is set at 500. The sum of these three
controllers is then limited to the range from -10000 to + 10000 which equates
to + or - 12.5 Hz. in the frequency control.
Frequency Controller - The output from the DC voltage controller is
summed with FNETWORK (204) to obtain the final frequency reference
FREF (220). FNETWORK is obtained from the AC line frequency FNET (86)
that has been limited to the range between FNETMIN (165) and FNETMAX
(166) with the rate of change controlled by FNETSTEP (167) in the ramp
block. The frequency values are scaled so that 48000 equals 60 Hz. FREF can
also be considered as the “active current” reference since the frequency
reference to the modulator is what determines the phase angle between the
LGU and the line voltage and thus controls the power returned to the line.
Page 4-7
Bulletin 1352 5.3 System
eee rea nacos EEE ESS SES EEE TETE
DC VOLTAGE CONTROLLER : FREQUENCY CONTROLLER
|
UCREF |
218
В —Ú | ENETMAX ER
DC Voltage SUM : (167)
Reference: + )
:
: - ! FNETWORK
| RAMP
224 PD ; NE :
UCACT E И | EREF
|; 220
_Y_ —
i E Tr T—T— ©
(65) LLGU Y SUM |:
(57) KFLL ‘ :
165 - > :
(66) CLGU | ENETMIN : Modulator
| :
- :
i
|
haa 1
UCDIFMAX
(59 > 1
> ;
!
MAX
TA I
E SUM LIMIT |i
i
D > od ra
= A I
J
(65) LLGU
— !
MIN (66) CLGU +10000 |;
— (71) KAA 10000 |;
Co (72)K11 !
UCDIFMIN
Danrnenenericaeo ro anencene caca a roo EreTAVEveCraCreaC Creta neto tara ooerdrecaeariroreenrenaareorvorvecmmaca !
Ais sd ded dada era rrr wry avr nl
Figure 4-4. DC Voltage And Frequency Controller
Page 4-8
Bulletin 1352 5.3 System
IQREFG
MAX
4-3.6
Reactive Current Controller - The Reactive Current Reference (Fig. 4-5)
can be used or bypassed as desired. If IQCONT (48) is set to zero, the Reactive
Current Reference is bypassed and DUSET (54) is used as the input to the AC
Voltage Controller. Both DUSET or the external reactive current reference,
IQREFG (27)are normally set to zero. IQREFG is clamped between the limits
IQMIN (156) and IQMAX (157) and its rate of change is limited in the RAMP
block by IQSTEP (158). The reactive current parameters are in .1% of rated
current (1000 = rated). The output of the ramp block is IQREF (219) which is
compared to the reactive current feedback IIMC (228). The difference between
the two goes to a “PI” controller. DUREFO (82) is the initial value for the
output and is automatically set to zero when UCUSCAL is calibrated as
described in section 2-8. The gain of the proportional part of the controller is
determined by PUQ (52) and is set at the factory to 4. PUQI (53) is the gain of
the integral part of the controller and is set to 400.
IQSTEP
RAMP
REACTIVE CURRENT CONTROLLER
IQREF
219
T
и
Figure 4-5. Reactive Current Controller
228
IMC
—
2
PI
Lc
SELECT
(82) DUREFO
(51) PUQI
(52) PUQ
DUSET
O
1
0
IQCONT
OT
AC
Voltage
Controller
Page 4-9
Bulletin 1352 5.3 System
4-3.7
Reactive
Current
Controller
4-3.8
AC Voltage Controller - The AC Voltage Controller (Figure 4-6) includes
part of the current limit function as decribed in Section 4-3.8. If the current
tries to exceed the limit, the output of the Reactive Current Controller is
reduced towards zero. After the LIMIT block, DUREF (222) is added to the AC
voltage feedback UACT (223) in the sum block and becomes the AC voltage
reference UREF (221) to the modulator.
To
Modulator
ULGU
(68) ILGU
(65) LLGU
Figure 4-6. AC Voltage Controller
Current Limit - The current limit for the LGU is accomplished in two steps.
Figure 4-3 shows the active current limit, and Figure 4-6 shows the reactive
current limit. The reactive current limit uses the active current feedback
IREC (227) and the total current limit KQ (28) to determine the reactive
current allowed. The reactive current allowed is determined by taking the
square root of the difference between the square of KQ and the square of
IREC.
Reactive Current allowed < V KQ2-iREC2 = V (P28)2 - (P227)2
If this value is exceeded, DUREF is clamped at zero. When not in current
limit, DUREF limit is calculated by the program using the rated voltage
(ULGU67), the rated current (ILGU 68) and inductance (LLGU 65).
The active current limit (Figure 4-3) is more direct using the active current
feedback IRE (231) and the active current limit setting KI (29). For this two
part current limit to operate properly, KQ (reactive current limit) must be set
to a lower value than KI (active current limit). In this way, the control will
reduce the reactive current to zero before having any effect on the active
current. Only if the current continues to rise after the reactive current is
eliminated, will the active current be reduced. When in current limit, active
current limit affects VCREF in such a way as to limit active current.
QUCMODE is not in effect and cannot increase the DC voltage to maintain a
set reactive current as described in section 4-4.4.
Page 4-10
Bulletin 1352 5.3 System
IREC1
IREC2
IREC3
IREC4
IRECS
IREC6
4-4
Modes of Operation
As seen in Figures 4-3, 4-6 and 4-7, there are five different optional features
that affect the way the LGU functions. They are factory set for the application
and require changing only during troubleshooting if it is desired to isolate a
portion of the firmware. Table 4-1 gives the default settings. A description of
the modes is provided in this section.
Table 4-1. Modes of Operation
MODE PRIMARY USE VALUE SECTION
PUCMODE (162) Parallel LGU's 0 4-41
UCREFMODE (160) DC Volts a function of 0 4-4 2
AC volts
DBMODE (90) LGU runs only for 0 4-4.3
regeneration
QUCMODE (161) Maintain power factor 0 4-4.4
setting via DC volts
IQCONT (48) Set power factor 1 4-4.5
4-41 PUCMODE 162EE (Parallel LGU's Only) - When PUCMODE is set to any
non-zero number it modifies the DC voltage reference according to the active
current feedback IREC227 (see Figure 4-7) This mode of operation is only
used when there is more than one LGU on the DC bus. The purpose of
PUCMODE is to let the DC bus voltage reference droop for this LGU when it
is providing more than its share of the power, thus keeping the load shared
between LGU's.
REC UACTDISP
UCREEFBIAS ferina | 203
227 | FUNCTION SUM
SELECT SUM |
| Du | O1 | — DC Voltage
| > Reference
© UCREFOFF O
C272) GD UCREFOFF1 о! —
1
i
' 244
G&D | | ОСВЕРОРР2 UCREFOFFSET
GD UCREFOFF3
«С»
UCREFOFF4 PUCMODE
UCREFOFFS
UCREFOFF6
Figure 4-7. DC Voltage Reference Optional Functions
Page 4-11
Bulletin 1352 5.3 System
This load sharing is accomplished by comparing the active current feedback
signal IREC to several preset limits. The output is determined via a
programmable function block that defines five points on the curve.
The preset limits and the corresponding output are identified as:
INPUT OUTPUT
PARAMETER DEFAULT PARAMETER DEFAULT
IREC1 272EE -1000 IUCREFOFF1 130
IREC2 274EE -850 [UCREFOFF2 111
IREC3 276EE -500 IUCREFOFF3 190
IREC4 278EE + 500 IUCREFOFF4 50
IREC5 280EE + 850 IUCREFOFF5 29
IREC6 282EE + 1000 IUCREFOFF6 10
The function block provides the curve as shown in Figure 4-8. Asan example,
if IREC is zero which is midway between IREC3 and IREC4 the output will be
midway between [IUCREFOFF3 and IUCREFOFF4 which is 70. The output is
proportional to the input within a given range. This would be similar to the
control being able to select points from the graph.
The output of this function block is then summed with the DC voltage
reference bias UCREFBIAS 284EE to form UCREFOFFSET 244 which goes
into the DC voltage reference circuit. For UCREFOFFSET to have any effect
either DBMODE 90EE or UCREFMODE 160EE described below must also be
selected as shown in Figure 4-3. If PUCMODE is not selected,
UCREFOFFSET is determined by UCREFOFF93.
OUTPUT
IUCREFOFF1
IUCREFOFF2
IUCREFOFF3
IUCREFOFF4 } ~— 1 --bH-d--4--L-d--4--E----4--E7
IUCREFOFFS (F-<0-L}--F-0--1--H-4--+4--F54--1--4- 00-04-8002
IUCREFOFF6 FF ~1-TT--r~1--1--"r-r-t1--r-—4+-14--t~=fF-q4~-~¢==p-de-qd- =
+1000 1-800 600 1-400 -200 0 200 400 ! 600 300! 1000
{ !
! |
1 | IREC | o
| | { | ‘ 1
IRECT IREC2 IREC3 IRECA IRECS IREC6
Figure 4-8. PUCMODE FUNCTION BLOCK
Page 4-12
Bulletin 1352 5.3 System
UCACT
224
4-4.2
4-4.3
IREFF
235
LIMIT
UCREFMODE 160EE (DC VOLTS A FUNCTION OF AC VOLTS) -
UCREFMODE adjusts the DC voltage reference to AC line voltage changes
as well as allowing the voltage droop from PUCMODE as shown in Figure 4-3.
When UCREFMODE is set to any non-zero number it selects the sum of
UCREFOFFSET as described above and UACTDISP 203, which is the filtered
AC voltage feedback, as the intermediate DC voltage reference UCREFH 240.
When UCREFMODE is zero, UCREFG 26EE is used for UCREFH.
DBMODE 30EE (LGU OPERATES IN REGEN ONLY) - When DBMODE
is set to a non-zero number it will also select the DC voltage reference in the
same manner as described previously in UCREFMODE. DBMODE is selected
when the LGU operation is only desired while power is being regenerated
back to the AC line (Figure 4-9). This mode is used when an LCU is used in
parallel with the LGU. With an LCU in parallel and DBMODE not selected, a
circulating current of less than ten percent is flowing between the LGU and
the LCU when the power flow is from the AC line to the DC bus. With
DBMODE selected the LGU only operates when the power flow is from the
DC bus to the AC line, thus eliminating this circulating current. In
DBMODE the LGU is ready to run and monitors the DC bus level. When the
DC level exceeds UCDBMSTART 238 or the rate of rise of the DC bus voltage
is greater than DUCDBMSTART 239, the LGU will start and regenerate the
power back to the AC line. The LGU will stop operation when the filtered
active current feedback IREFF 235 is greater than DBMIRESTOP 79EE for
the time set in DBMCNTR 80EE (4ms increments).
238 UCDBMSTART
239 DUCDBMSTART
LIMIT
21 | SELECT
From AC Voltage O 01
Controller =
MODULATOR
FREF i
220
From Frequency os:
Controller — o.
À
S-R FLIP - FLOP
S
SELECT
— R O1
0 >
A
90
DBMODE
73 DBMIRESTOP
80 DBMCNTR
Figure 4-9. DBMODE OPERATION
Page 4-13
Bulletin 1352 5.3 System
4-4.4
4-4.5
QUCMODE 161EE (Maintain Power Factor via DC Volts) - The fourth
mode of operation is QUCMODE which will adjust the DC voltage reference to
maintain a reactive current setting (Figure 4-3). The reactive current is
determined by the voltage drop across the LFU reactor. During regeneration,
if the DC voltage is too low, then the LGU AC voltage will also be low and the
voltage drop across the reactor will be low (or negative) thus taking reactive
power from the AC line. When QUCMODE is set to any non-zero number, the
DC voltage reference is incremented up or down as a function of the reactive
current. Reactive current control must also be selected (IQCONT 48 not zero)
for QUCMODE to have any effect.
IQCONT 48EE (Select Power Factor Control) - IQCONT (48) is described
in section 4-3.6 and selects the Reactive Current Controller. This mode is
turned on by setting IQCONT to any non-zero number. When this mode is
inactive (IQCONT = 0), the reference offset to the AC Voltage Controller is
set to zero via DUSET (54).
Page 4-14
Bulletin 1352 5.3 System
4-5
START-UP “SECTOR” The start-up angle is adjusted only after all the measurement adjustments
ADJUSTMENT have been executed and only if over or undervoltage trips occur during
LGU startup.
The AC supply voltage period of 360° is divided into 60° sectors. (See Figure
4-10) Each sector begins at the instant one of the phase voltages crosses zero.
When the LGU is requested to start, it waits for one of these zero Crossings
before initializing.
U V W
port pr ga
—.——É —— ——ÚrÉnZ——
U-V-W — > > > > >
U-W-V = < «— че —
SECTOR
Figure 4-10. Start-up Sectors
When the LGU begins a start-up routine, it checks the level of the line voltage
and the direction of rotation. If the line voltage is not present or too low, a
failure is displayed. If the level of line voltage is sufficient, the LGU defines
the next allowed start-up sector in which a start-up takes place. In defining a
start-up sector the LGU takes into account filtering delay of the AC supply
voltage measuring (approx. 18°) as well as a processing delay caused by the
synchronization routine. This delay time is stored to the memory location
FILTDELAY 92EE. Parameter 92EE scaling is 256 corresponding to the
angle of 60°. An adequate value is the initial value of 240. Changing this
value is generally not required.
The line synchronization is determined by measurement of two phase voltages
and comparing this to the calculated value. A comparison takes place after
performing each measurement. If the latest measured voltage is WV phase
voltage, the start-up mode is 1. When the UV phase voltage is measured, the
start-up mode is 2. The above ratios should be of a slightly different value
depending on the mode of start-up. The startup mode is recorded in
Parameter STARTMODE 342. The startup sector is recorded in Parameter
STARTSECT 341.
Start-up can be enabled or disabled for each sector and mode of start-up
separately. This is done by using memory locations 361EE, 364EE, 367EE,
370EE, 373EE and 376EE in the U-W-V case. The value of the first location is
sector 0 and so forth. Ifthe valueis 0, start-up in this sector is prohibited.
When the value is 1 only mode 1 is enabled, if the value is 2, only mode 2 is
enabled, and if equal to 3, both modes 1 and 2 are enabled.
Page 4-15
Bulletin 1352 5.3 System
The direction of AC supply voltage rotation is observed in the memory
locations DIREC 237 and UVWDIR 340. DIREC 237 is determined by the
direction of rotation when the LGU is not running and UVWDIR 340 when
the LGU is running. Both are automatically set. The 0 value corresponds to
the U-V-W direction and any non-zero corresponds to the U-W-V direction.
For U-W-V voltage rotation, contents of memory locations 36 1EE to 378EE
should be used. Rotation UVW uses 343EE to 360EE. The contents of the
memory locations correspond to each other in direct numeric sequence. (i.e.
343EE would be replaced with 361EE) Refer to Table 4-2.
Table 4-2. Start-Up Angle Parameters
DIREC 237 Phase rotation not running, 0 = U-V-W
UVWDIR 340 Phase rotation at start-up, 0 = U-V-W
STARTSECT 341 Start-up sector number
STARTMODE 342 -Start-up mode type
ROTATION U-V-W ROTATION U-W-V
VSECTO 343EE MSECTO 361EE Start-up permission for sector 0.
VOFFSOT 344EE MOFFSOT 362EE Sector 0, mode 1 fine tuning.
VOFFSO2 345EE MOFFSO2 363EE Sector 0, mode 2 fine tuning.
VSECT1 346EE MSECT1 364EE Start-up permission for sector 1..
VOFFS11 347EE MOFFS11 365EE Sector 1, mode 1 fine tuning.
VOFFS12 348EE MOFFS12 366EE Sector 1, mode 2 fine tuning.
VSECT2 349EE MSECT2 367EE Start-up permission for sector 2.
VOFFS21 350EE MOFFS21 368EE Sector 2, mode 1 fine tuning.
VOFFS22 351EE MOFFS22 369EE Sector 2, mode 2 fine tuning.
VSECT3 352EE MSECT3 370EE Start-up permission for sector 3.
VOFFS31 353EE MOFFS31 371EE Sector 3, mode 1 fine tuning.
VOFFS32 354EE MOFFS32 372EE Sector 3, mode 2 fine tuning.
VSECT4 355EE MSECT4 373EE Start-up permission for sector 4.
VOFFS41 356EE MOFFS41 374EE Sector 4, mode 1 fine tuning.
VOFFS42 357EE MOFFS42 375EE Sector 4, mode 2 fine tuning.
VSECTS 358EE MSECTS 376EE Start-up permission for sector 5.
VOFFS51 359EE MOFFS51 377EE Sector 5, mode 1 fine tuning.
VOFFS52 360EE MOFFS52 378EE Sector 5, mode 2 fine tuning.
When 343EE = 3 sector 0 start-up enable is set to 3 and start-up in any other
sector is disabled, i.e. 346EE = 349EE = = 376EE =0. A START command is
then given. If a start-up takes place too late, the content of memory locations
344EE and 345EE have to be changed to lower values. Refer to Table 4-3. A
good practice is to change content of both memory locations to the same extent
(e.g. decrease by 2). The total change should not be more than 10.
Table 4-3. Sector Phase Adjustment
PHASE SEQUENCE UVW UWV
DCBUS Overvoltage Lower Value of Raise Value of
Parameter 344 - 345 Parameter362 - 363
DCBUS Undervoltage Raise Value of Lower Value of
Parameter344 - 345 Parameter362 - 363
Page 4-16
Bulletin 13525.3 System
Unless DBMODE is being used, only one sector must be set up. When
DBMODE is used, all sectors should be set up since the DC voltage is
increasing and the startup should be immediate and not waiting for the next
cycle. When start-up of section 0 is adjusted (two start-ups are successful) the
content of memory location 343EE is set to 0 and the adjustment of sector 1 is
performed setting 346EE to 3. In order to perform fine adjustment, memory
locations 347EE and 348EE are used. The procedure is the same as above.
When adjustment of sector 1 is accomplished, an adjustment of sector 2 is
performed by setting 346EE to 0 and 349EE to 3 and so on. When sector 5 has
been adjusted, all sectors are turned on by setting the content of memory
locations 343EE, 346EE,..., 358EE to 3. After that, several start-ups should
be performed. If one start-up causes voltage trips, the start-up sector which
requires tuning can be obtained from location (341) and the mode of start-up
from location (342).
When the U-V-W rotation is properly adjusted, the adjustment of U-W-V
arrangement can be performed by changing two of the incoming lines to the
Line Contactor Unit (on the mains side!). The adjustments are performed the
same as above with the exception that different memory locations are used,
and if a start-up takes place too late (DC voltage increases), fine adjustment
parameters should be increased.
When the AC supply phase arrangement is known an adjustment for the
opposite phase rotation can be omitted. The start-up enable values of the
adjusted sectors are set to a final value of 3 and others to 0. The phase
arrangement should be determined at the installation site and checked that
the start-up enable values of the opposite arrangement are set to 0. The
parameters obtained should be stored in EEPROM memory by unlocking
EEROMLOCKS (8 =0) per section 2-13.
Page 4-17
Bulletin 1352 5.3 System
4-6
Operator Interface
4-6.1
The Bulletin 1352 Drive System is often connected to a master control such as
a Digital Reference Control, a PLC, a CP1 or CP2 control panel or the Drive
Maintenance System.
CP1 Control Panel - The CP1 control panel is mounted on the drive
enclosure and is used as the local control forthe drive. The description of the
CP1 is located in section 3-9 of this manual. The pushbutton status is sent
from the CP1 panel to the control via serial communications channel 1 using
Parameter CP1IBUTTONS 19. This packed word is the input to the function
block CPIBUTTONS which takes the packed word and provides a logical
output at the parameter addresses shown in Figure 4-11A. These addresses
are then used as the input for other function blocks that then go to the
SCALAR block. Serial channel 1 is always used for the CP1 panel.
The displays for the CP1 panel for the LGU are preset at the factory but can be
modified as required, the default displays are:
LETTER DISPLAY # DESCRIPTION
A DISPLAYO LINE CURRENT
r DISPLAY1 DC VOLTAGE REFERENCE
U DISPLAY 2 LINE VOLTAGE
с DISPLAY3 DC VOLTAGE
A DISPLAY4 LINE CURRENT
The display blocks are shown in Figures 4-11 (B) and (C). DISPLAYO block is
used to display the Line Current as a default. Parameter OUTO 1574 is the
value of the parameter before any display scaling. Parameters MIN 1682 and
MAX 1683 are the minimum and maximum values allowed for OUTO.
The other parameters are common to each of the display blocks. SP 1577
determines the rate of change of the display as follows:
SP = 0 only the parameter display functions appear
SP = 1 very fast change
SP = 2 fastchange
SP = 3 normal change
SP = 4 slow change
Page 4-18
Bulletin 1352 5.3 System
DISMARK is the parameter that determines the code letter used to indicate
the display that is shown. Display characters and the numbers used to select
that character are shown below:
CHARACTER VALUE
L 0
r 1
[] 2
с 3
d 4
A 5
C 6
F 7
H 8
L 9
P 10
U 11
u 12
b 13
h 14
Parameters MUL, DIV and POINT are additional scaling factors for the
displays. MUL and DIV are the multiplier and divisor that are used to
convert the parameter value to a meaningful display.
DISPLAY to DISPLAY4 use D_ SOURCE as the address of the displayed
parameter rather than OUTO as is used for DISPLAYO. OUTO can be used as
the input to other function blocks, whereas D_ SOURCE cannot.
D__ SOURCE can however display any parameter from the drive.
SPECIALDISPLAY is used to display faults 25 and 26 as well as the
remote/local dot. For all three of these displays, any non-zero input will cause
the predetermined message to display, see Figure 4-11 (D). The fourth input
to this block is CP1LOCK which will disable parameter changing if 1356 is
any non-zero value.
Page 4-19
Bulletin 1352 5.3 System
A) B)
_ EP BUTTONS LINE CURRENT
STOP 111344 OUTO [1574]
+ El3as 1677 5 E DISMARKO
- Wize 1577 1 | SPEED
PAR Lf3a7 1682 0 F MIN
LOC/REM F-11348 1683 3000 E MAX
RESET 11349 1555 579 — MULO
REV 11350 1556 100 DIVO
DISP 11351 1557 1 — POINTO
C) C) C)
1570] 240H] D1SOURCE D2SOURCE 1572] 201H b3source
1678 1 ~ DISMARK1 1679 11 — DISMARK2 1680 3 7 DISMARK3
1977 1 — SPEED 1577 1 — SPEED 1577 1 — SPEED
1558 1 — MULTI 1561 460 |p MUL?2 1564 621 — MUL3
1559 1 — DIV 1562 100 EH DIV2 1565 100 | DIV3
1560 1 — POINT? 1563 1 — POINT2 1566 1 - POINT3
С) D)
—
un
~J
un
—
mm
~J
Ww
DASOURCE
1681 5 — DISMARK4
—
un
=}
On
REMIND
1577 1 — SPEED
CP1LOCK
—
La
un
с
1567 579 FE MULA
1559 100 F DIVA 1577 | SP
1560 1 — POINT4
Figure 4-11. CP1 Blocks
Page 4-20
Bulletin 1352 5.3 System
4-6.2
4-6.2.1
4-6.2.2
Serial Communications Software - The serial communications uses many
parameters to define the data to be sent, how often and if the data was
transferred correctly. For connection to other communications devices the
communications specifications are:
Asynchronous serial data communications
Full duplex
Baud rate of 4800
Each word is 10 characters
Even parity
1 start bit
7 data bits
1 stop bit
The following are some of the communications parameters.
[МАГ and IX Parameters - A series of parameters from 114EE to
151EE are used to define the data to be transmitted on the serial channels and
the intervals at which the transmissions are made. There is room for up to
eight parameters (IXO to IX7) to be sent on channel 1 and eight more (IX0-2 to
[X7-2) on channel 2. The frequency of the transmissions is determined by the
intervals set in IVALO to IVAL7 for channel 1 and IVALO-2 to IVAL7-2 for
channel 2. The intervals are supervised to ensure that the intervals specified
will not overload either channel. Each transmission takes approximately 21
ms so that the more parameters to be transmitted, the longer the interval
required between updates of a given parameter.
Âs an example, consider the situation for channel 1 where parameter 247 is
sent every 210 ms, 248 every 189 ms, and 211 every 168 ms. The values in
each parameter are :
PARAMETER VALUE MEANING
114EE IVALO 10 210ms.
115EE IX0 247 Digital Output DIG__ OUTPUTS
116EE IVALI 9 189 ms.
117EE IX1 248 Analog output ANAOUTO
118EE IVAL2 9 . 189 ms.
119EE 1X2 249 Analog output ANAOUT1
120EE IVAL3 8 168 ms.
121EE IX3 211 FAULTWORDI
TBCTRANSMITI1 9EE and TBCTRANSMIT?2 10EE - The 3500 - IOC card
can be programmed to transmit input signals using a transmisssion buffer
with nine fields. Eight of these fields can be programmed with hexadecimal
code numbers, the first four fields are defined in parameter 9EE and the
second four are defined in parameter 10EE. The codes are as follows:
0 = No transmission
1 = Send analog input 0
2 = Send analog input 1
3 = Send analog input 2
4 = Send digital inputs
5 = Send CP1 push button signals
For example, assume that the analog input 0 should be sent every other time
and the other inputs are sent evenly. The transmission buffer would be 1-2-1-
3-1-4-1-5. Parameter 9EE would be set to 1213H and parameter 10EE would
be set to 1415H defining the last four codes. To enable the transmission,
parameters 9EE and 10EE would then be selected for transmission using one
of the communications parameters from 114EE to 129EE for channel 1 or
Page 4-21
Bulletin 1352 5.3 System
4-6.2.3
4-6.2.4
134EE to 151EE for channel 2. If the communications were set as shown in
section 4-6.2.1 the addition of 9EE and 10EE would start at 122EE as follows:
PARAMETER VALUE MEANING
122EE IVAL4 100 2.10 sec.
123EE IX4 9 TBCTRANSMIT1 9EE
124EE [VALS 100 2.10 sec.
125EE 1X5 10 TBCTRANSMIT2 10EE
REQUESTMSGE 112EE and ANSWERMSGE 113EE - Parameters
112EE and 113EE are best considered as windows where data is passed from
the drive program to the external control device such as a control panel, DMS,
PLC or computer. For ease of explanation. assume a CP1 control panel is used
to change a parameter value. When the CP1 requests a parameter it sends the
parameter number to parameter address 112EE. The program then retreives
the value of the requested parameter and places that value into parameter
113EE to be sent to the control panel. If the operator changes the value of the
parameter at the panel and enters it into the program, then address 113EE is
sent to parameter 112EE which tells the programs to send the new value to
the last address requested. Parameters 112EE and 113EE are used by both
serial channels.
COMMUNICATIONS DIAGNOSTICS - The serial communications
channels are supervised and parameters are provided to store the information
necessary to check on the accuracy of the communications. The following isa
listing of the diagnostic parameters and a brief description of what they mean:
COMM __ TIMEOUTZ2 169EE Defines the maximum time between
messages before a channel 2
communications loss is detected.
CH2 BAUDRATE 170EE Determines the rate of data transmission
and must remain at 4800 Baud.
SELMACONT 171EE Determines the program action after
communications loss using the following
codes:
0 = No action
1 = Send message to Panel
2 = Send message plus ramp to stop
3 = Send message plus coast to stop
COMM__ TIMEOUT 172EE Defines the maximum time between
messages before a Channel 1
communications loss is detected.
OKMSGES1 182 À count of the completed messages on
channel 1.
FAULTMSGES1 183 À count of the lost messages on channel
1.
OKMSGES2 184 A count of the completed messages on
channel 2.
FAULTMSGES2 185 À count of the lost messages on channel
2.
HWFAULTS1 266 A count of the parity errors on channel 1.
HWFAULTS2 267 À count of the parity errors on channel 2.
Page 4-22
Bulletin 1352 5.3 System
BCCERRORSI
BCCERRORS2
FORMATERRORS1
FORMATERRORS2
SAMIDATA
SAMIADDR
SAMIDATA1
SAMIADDR1
SAMIDATA2
SAMIADDR2
SAMIDATAS
SAMIADDR3
268
269
270
271
303
304
305
306
307
308
309
310
A count of the checksum errors on
channel 1.
A count of the checksum errors on
channel 2.
A count of the unknown character errors
on channel 1.
A count of the unknown character errors
on channel 2.
The last data received on channel 1.
The address of the last data received on
channel 1.
The last data received and accepted on
channel 1.
Address of the last data received and
accepted on channel 1.
The last data received on channel 2.
Address of the last data received on
channel 2.
The last data received and accepted on
channel 2.
Address of the last data received and
accepted on channel 2.
A B C D E
F
G H J I J K L M N 0 Р
{
1 {
1 1
REACTIVE CURRENT CONTROLLER AC VOLTAGE CONTROLLER
IQMAX :
IQSTEP
IQREF | ' ;
MAX : 219 '
DUR 3
IQRE FG RAMP 9 т Pl SELECT] | 25
- | 1
> — | / —© | LIMIT о SUM URL UREF 4
{L34) — DUSE T e ! га SELECT MODULATOR
(82 )DUREFO вес ya + ! о о о — о 5
MIN 228 (51 )PUOI ' : REC (6301-972 : © ° 20"
[IMC (52 )PUQ 227 FREF 6
e A] 25 220 |
Cas) ‘ua UACT UCACT 9 0 —0 7
[QCONT | 224 (P22) бог о ;
ies | 7 !
me ‘ CE ' o LIMIT S-R FLIP-FLOP \
€ ! (G31) À R SELECT
> ‘ 9
DC VOLTAGE REFERENCE OPTIONAL FUNCTIONS OA = 68 )1LOU ' A с И
: PTT TT TT TITI TT AT TT TT TTT TT TUTO TT TT TT OT TT TT TT TT TT TOO TT TOUT TTTT TT OUT 70077) 238 UCOBMSTART 10
| DC V ‘ | 057
REC Learns [ETT UACTOISP OLTAGE REFERENCE DC VOLTAGE CONTROLLER 1 ¡REFf 229 UCIBMSTART о — © | га
: 235
FUNCTION SELECT 2 SUM SELECT] Sah
(33) AN > o (F30) — o о SUM LIMIT : 12
{ t
UOREFOFF |g +O e > o e ı ' ya ED
Ô UCMAX DBMODE 13
IRECI UCREFOFFI > ВНЕ UCMAX | PESTE (SEE 617) В
UCREFOFFSET y о! ' )
IREC2 UCREFOFF2 MAX Là ' UCREF Eno ooo ooo EEE
y ET... MT 1S
ED | ' |
IREC3 |( 276 )|( 277 )| UCREFOFF3 PUCMODE * ES RED о МАХ $ 218 ' FREQUENCY CONTROLLER
‘ ED RAMP i о SUM 1 | 16
1 : 1 ‘
IREC4 UCREFOFF4 Rh > — ı Ne —e— FNETMAX 17
/ ‘1631-0 (166) F
| MIN 1 1 NETSTEP 1
IRECS UCREFOFFS ! | о 53 )РО! : 18
193 MÍN 1 | 224 \ MAX L FNETWORK |
IREC6 |( 282 )|( 283 )| UCREFOFF6 ' UCMIN SELECT N 155 1 UCACT PD RAMP 204 ! те
‘ REACTIVE| |! 55 UCSTEP = — | fr,
CURRENT ——O UCMIN (86. J '
жен он = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = ! TRIM o ! (55 )KOLLL 1 ! 20
as ‘ lo ~~ > |
VOLTAGE FEEDBACK | TS: ' Com | MIN | =
' | 1 (57 )KFLL | X 1 FREF
‘ ' 7 t
QUC MODE ; ! (66 )CLGU SUM 220 22
CD) — FNETMIN ©
IRE UCDIFMAX NEUE 705 | (07)
| 23
231 L
1 1 у !
1 1 1 24
u ACTIVE : МАХ SUM oe
| «I [CURRENT] — 5 M 25
Hh | OUT
| ‘ 26
DO | (65 )LLGU «10000 |
III 4 MIN 66 )CLGU - 10000 t 27
[71 )KAR |
(_60_) (72 )KII ' ı 26
ис © 201 UCACTDISP ' Oo UCDIF MIN oc
-— O 203 UACTDISP (012) ‘ =ттттттететееляеееттеттежеетттстеетнйееетсоо!
3 UACT (FE) ' CURRENT FEEDBACK ' 30
uv о ! IUOFFSET
UL TIPLEXER-— 4% H—© 224 UCACT (18) (M9) | A 31
SCAL ING SCALING ——) 233 ULV U o LEGEND 32
WY —@234 vw ' © HH A > à CALC | €)202 IACTDISP O - SOFTWARE TEST POINT
33
© 237 DIREC ' М — 227 IREC (ЕВ) (C7) - PROGRAMABLE PARAMETER
—Q 340 UVWDIR ‘ V , о — — © 228 1IMC (BE) ' (CO) - REFERENCE INPUT PARAMETER 34
| O > © © 231 IRE (625) ! 35
Ÿ Y Y :
——
TO ! 1 36
CTU . IVOFFSET |
' 1 37
| THIS PAPER IS OUR PROPERTY. IS CONFIDENTIAL OR
' IS PROVIDED ONLY FOR REFERENCE IN DEALING wi | DJS
ES SIS aw To7-07 ALLEN-BRADLEY |”
. 5 . Y
| nO NI aaa Fon e | oae Solved hi vt Saris 3¢
REPRESENTATIVE SO CERTIF IES ON ITS FACE. ВУ APPO TmEe: LINE GENERATING UNIT -
| TING THIS PAPER YOU AGREE TO THE ABOVE. | DATE SOFTWARE OVERVIEW
‘ ECN NO. REFERENCE DWG. 40
, ECN “O.
, ECK NO. . INDEX NO. ож. = 41
REV. DATE USED ON: ABS-AC.SCH.SW.B | wo. D-5040350-18 |:
\ 5-9-89
LT
TABLE OF CONTENTS
5. Troubleshooting
5-1. General 1
—
5-1.1. Test Instruments and Tools
—
5-1.2. Principle of Fault Tracing
—
5-1.3. Documenting Errors
5-2. Diagnostic Messages
5-2.1. Fault Table
5-3. Testing Methods
5-3.1 Choosing the Right Fault Tracing Instruction
5-3.2. Diagnostics
5-3.3. Fault Queue
5-3.5. Regulator Status
5-3.6. Faultword
ч BB в Бо с" WW N N
5-4. Troubleshooting Guide
5-5. Trends 18
5-5.1. General 18
5-5.2. Use of Trend 18
5-6. Changing Printed Circuit Boards 20
5-6.1. Circuit Board Replacement 20
5-6.2. Control Card (103 CON/3500 C03) Replacement 20
5-7. Checking and Replacement of Power Semiconductors. 21
5-7.1. Power Transistors (GTR) 21
5-7.2. GTO and Free Wheeling Diodes 21
5-7.3. Installation Instructions 22
Chapter
>
BULLETIN 1352 TROUBLESHOOTING
5-1
General The Bulletin 1352 Drive has several advanced diagnostic and troubleshooting
functions available, including trending and the capability of reviewing prior
fault occurances. Troubleshooting procedures should begin by recording
information from the following sources:
Fault messages from the control panel
Faultword0 - Parameter 210 and Faultword 1 - Parameter 211
Status of LED's on the various cards.
DRIVESTATUS - Parameter 214
SCSTATUS - Parameter 215
5-1.1 Test Instruments and Tools - The following test instruments and tools are
required for fault tracing and repair:
A. Multimeter capable of 1000VDC/750VAC, with input resistance of at
least 1 megohm.
B. Testleads
C. Assorted (Phillips and Blade type) screwdrivers
D. Setof metric box-end or open-end wrenches or sockets, sizes 5-1/2, 7,
10, 13, 17, 19 and 24 mm in particular.
E. Soldering iron suitable for use with CMOS circuits ( grounded tip) and
solder.
5-1.2 Principle of Fault Tracing - The fault tracing method presented here is
based on systematic tracing of the fault location and then systematic testing
using spare circuit cards. For most fault conditions, replacement of control
circuit cards will isolate the problem in the shortest period of time. The fault
tracing method assumes that only one fault has occurred at a particular time,
possibly causing further effects such as blown fuses.
5-1.3 Documenting Errors - Any problems should be written down and
documented as to the failure, any indicator or fault messages that are
annunciated as well as the corrective action. This information will assist in
correcting any problem that re-occurs.
Page 5-2
Bulletin 1352 5.3 System
5-2
Diagnostic Messages
5-2.1
Fault Table
+ * * + *
* *
#+
*+
++
**
**
**
The following is a list of all diagnostics messages transmitted to the Control
Panel. Messages with a FL prefix turn the LGU off and disable the contactor
lock signal. Status (SA) messages are warnings and do not shut down the
unit.
CP1
Message
FLO1
FLO2
FLO3
FLO4
FLO5
FLO6
FLO7
FLO9
FL10
FL11
FL12
FL13
FL14
FL15
FL17
FL18
FL19
FL20
FL21
FL22
FL25
FL26
FL40
FL41
FL42
FL43
FL44
SA50
SA51
SA52
SA53
ЗА55
SA56
SA57
SA58
SA59
SA80
SA81
SA82
SA83
SA84
SA85
CP2
Message Text
CHOP UNDERVOLT
CHOP OVERVOLT
AUX UNDERVOLT
OVERTEMPERATURE
OVERCURRENT
DC OVERVOLT
DC UNDERVOLT
Ul FAULT
U2 FAULT
V1 FAULT
V2 FAULT
W1 FAULT
W2 FAULT
SHORT CIRC/EFLT
COMM FAULT
TACHO LOSS
IMEAS FAULT
MOTOR STALLED
MATCH CARD FAULT
PROCESSOR FAULT
DIS25 FAULT
DIS26 FAULT
UNBALANCED LOAD
START TOO LONG
NO SECT AVAIL
NO DIGINP AVAIL
NO AC VOLTAGE
NO BACKUP/NEW EP
STORED TO BACKUP
NO WR TO EEPROM
BAD PARAM VALUE
ILLEGAL PARAM
NO BATT BACKUP
LOW AC/DC VOLT
START INHIBIT
SYSTEM RESTART
RAR - OVERCURRENT
DAR - OVERCURRENT
RAR-UC OVERVOLT
DAR-UC OVERVOLT
Explanation
Chopper Undervoltage
Chopper Overvoltage
Auxiliary power fault
Heatsink overtemp, or fan stopped
AC current too high
DC voltage too high
DC voltage too low
U - phase, positive leg
U - phase, negative leg
V phase, positive leg
V phase, negative leg
W phase, positive leg
W phase, negative leg
AC Short circuit or ground fault
Intervals between incoming messages
too long.
Tach pulses missing
Current measurement fault
Motor current too high for too long.
Matching card malfunction
Processor failure
Programmable fault
Programmable fault
Unbalanced AC current
Good synchronizing places not located
No starting sectors available
No digital inputs available
No Line Voltage
New EEPROM
EEPROM writing enabled
Cannot write to EEPROM
Parameter value out of range
Wrong parameter number
Battery Backup did not work
Contactor Open
Starting is disabled
System Restart
Overcurrent after rapid auto reclose
Overcurrent after delayed auto reclose
UDC - overvoltage after RAR
UDC - overvoltage after DAR
RAR - UC UNDERVOLT UDC - undervoltage after RAR
DAR - UC UNDERVOLT UDC - undervoltage after DAR
Specific for LGU
Refer to Section 4-2.5 for further information on restart function
Page 5-3
Bulletin 1352 5.3 System
5-3
Testing Methods
5-3.1
A
WARNING: Servicing energized industrial control equipment can
be hazardous. Severe injury or death can result from electrical
shock, burn, or unintended actuation of controlled equipment.
Recommended practice is to disconnect and lock out control
equipment from power sources, and confirm discharge of stored
energy in capacitors, if present. Ifitis necessary to work in the
vicinity of energized equipment, the safety related work practices
of NFPA 70E, Electrical Safety Requirements for Employee
Workplaces , must be followed.
Do not remove the aluminum and plastic protection panels
needlessly during fault tracing. This is usually unnecessary and
can expose the personnel to potential hazards from voltage sources
present in the unit. Always replace protective panels before
operating unit.
In order to avoid damage to the CMOS circuits from an accidental discharge of
static electricity, the following rules must be followed when handling the
circuit cards and performing measurement checks on the cards:
A.
Before removing a card from the rack, discharge your own static
Charge by touching an unpainted point such as on the rack. The use of
a properly grounded wrist strap is recommended when performing any
checks or tests on cards.
A
CAUTION: The CMOS circuits utilized on the control eircuit
cards can be destroyed by static charges generated by friction of
materials made of synthetic fibers. Use of faulty circuit cards may
also damage related components.
When configuring jumpers or checking a detached circuit board, it
should preferably be laid on a conductive, grounded surface, taking
care not to short out the battery leads.
Test measurements on the control circuit cards are not permitted.
A
CAUTION: Do not perform measurements to any points on the
card. Such measurements could damage circuit components.
D.
DO NOT connect the common terminal of test instruments operated
from the main supply to the common terminal (M) of the auxiliary
voltage (+ 12V) unless power to the Drive is disconnected.
The probe of the test instrument can be moved from one test point to
another while the Drive is operating, provided that the probe is first
grounded by touching it to the common probe of the meter or scope.
Choosing the Right Fault Tracing Instruction - The following paragraphs
match the fault situations that constitute the starting points for fault tracing.
In some cases, operating personnel will have to reset the fault and then
attempt to restart the unit. The fault tracing procedure should start at the
point corresponding to the original fault indication. Occasionally, the cause of
a malfunction of the unit must be determined without any visible LED fault
indications.
Page 5-4
Bulletin 1352 5.3 System
5-3.2
5-3.3
5-3.4
5-3.5
5-3.6
Diagnostics - There are four sources of diagnostic information available to
the operator. This information is accessable via the local control panel and
can be transmitted via the serial communication link as bit coded words.
The sources are:
1) Fault Words (See Tables 5-1 thru 5-3 for summary and Sect. 5-3 for
details).
2) Fault Queue
3) Drive Status Word
4) Regulator Status Word
Fault Queue - In the event of a fault, the fault that occurs first is stored in a
buffer FLT _ QUEUE 176. This location retains the data until the drive is
reset. After being reset the fault code is moved to Parameter (177) and a
negative 1 is stored in Parameter (176). If power is turned off , this data is
backed up with a battery. If another fault occurs, all the data stored is moved
to the next higher memory location and the new fault number is stored in
Parameter (176).
Assume that the drive has had three fault shutdowns, the first from
overcurrent (05), the second from overtemperature (04) and the third from DC
Undervoltage (07) as the initial causes of shutdown. After each fault, the
drive was reset. The fault queue would contain the following:
PARAMETER FAULT # EXPLANATION
176 -1 RESET
177 7 DC UNDERVOLTAGE
178 -1 RESET
179 4 OVERTEMPERATURE
180 -1 RESET
181 5 OVERCURRENT
Drive Status - The status of the drive is summarized in the Bit Word found at
Parameter 214. The meaning of that word is decoded as follows:
BIT #
NOT RUNNING 0
READY 1
FAULT 2
Regulator Status - The status of the Drives internal regulators are indicated
by the bits in Parameter 215. The bit meanings are:
BIT #
QUIESCENT STATE 0
RIDE THROUGH 1
FLYING START 2
FREQUENCY INTEGRATOR 3
IREHIGH CONTROLLER 4
IRELOW CONTROLLER 5
UCHIGH CONTROLLER (119%) 6
UCHIGH CONTROLLER (116%) 7
IR COMPENSATION 8
IR COMPENSATION 12
TORQUE REGULATION 13
IR COMP AT CURRENT LIMIT 14
Faultword - The FAULTWORD parameters contain the fault codes and
status messages. All 32 codes are packed into the three faultwords as shown
in Tables 5-1 thru 5-3. The faultwords can be sent via serial communications
to the control devices (PLC ,DMS, etc.) A “1” in the bit indicates that the fault
has occurred. If multiple faults are present, the number displayed would be
the total of the decimal values of each fault.
Page 5-5
Bulletin 1352 5.3 System
Table 5-1. FaultwordQ Parameter 210
E
BIT#
Description
CP1 FAULT#
bone A ue 4
Faultword1 Parameter 211
2
Table 5
E
BIT#
ion
Ipt
Descr
CPI FAULTZ
aten
A
Table 5-3. Faultword2 Parameter 212
Bulletin 1352 5.3 System
Page 5-6
E
BIT#
Description
Message#
Нк
кк
taa
+
ize
ive S
Dr
+
atada
LAA
LED Ident
+
EHRT
RC
aaa
pti
+
icators
LED Ind
4
Table 5
on
Card Locat
aT TT
Page 5-7
Bulletin 1352 5.3 System
5-4
Troubleshooting Guide
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
None Drive Dead, A. Main Disconnect S2 Not A. Close Disconnect
Main Contactor Closed.
K4 will not close. B. Maintained Emergency B. Reset Emergency Stop
Stop Depressed.
C. Low or No Voltage at C. Provide correct voltage. Voltage of
Supply to Drive. all three phases must be + 10% of
nameplate rating& within 5% of the
other phases.
D. Blown fuses D. Check or replace LSU fuses F1 thru F8
E. LGU Output Disconnect E. Check LGU Relays 1K & 2K
or DC Fuses open
E. Control Voltages E.Check for 115 VAC between terminals
missing TB1 - 24 and TB1 - 25.
Check for 215 VAC between TB1 - 9 and
TB1-12.
F. Check for Interlock or Jumper
F. Fault interlock Open Continuity at:
Terminals TB1-20 & 21
Terminals TB1-21 & 22
Terminals TB1-22 & 23
Terminals TB1-15& 16
Check that LSU-K1 has picked up
Check that LSU-K2 has picked up
G. 210 KVA units and G. Reset Breaker F51 in LCU
above only. LCU cooling Check fan for free rotation
fan circuit breaker is off or Check heatsink thermostats 551 & 52
tripped. for open circuit.
None CP-1 Panel A. Maintained Emergency A. Reset Emergency Stop
Blank, Drive Stop Depressed.
seems to be B. Blown fuses B. Check or replace LSU fuses F1 thru F8
dead, but C. Control Voltages C. Check for 115 VAC between LSU
cooling fans run.
Missing
D. Main Disconnect Open
Terminals TB1-24 and TB1-25. ‘
Check for 215 VAC between LSU
terminalis TB1-9 and TB1 -12.
Check for 215 VAC between INU
Terminals X1.1, 101 and 102.
D. Check Aux contacts of Main
Disconnect
Page 5-8
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
None CP-1 Panel A.Cooling fan circuit A.Reset breakers.
Blank, Drive breakers are offor F2 in INU (30 -115KVA)
seems to be tripped. F11 in INU (140 - 870 KVA)
dead, cooling F51 in LCU (210-870 KVA)
fans do not run. If breaker trips again, check fans for
free rotation.
If INU fan breaker continues to trip,
temporarily remove jumper on INU X1
(103 - 104). (Run at no load) If breaker
trips replace A3 Power Supply on units
115KVA and smaller.
On larger units replace A9 Auxiliary
Power Supply. If breaker doesn’t trip,
replace the cooling fan.
B. Main Disconnect Open B. Check AUX Contacts of Main
Electronic Noise Disconnect
Any Display Drive stopped Verify that grounding practices listed in
but appears to Sect. 2 have been followed.
be running.
Display Character Displays are Electronic noise has erased Verify grounding per Sect. 2. Replace
[1
strange. Drive EEPROM
doesn’t operate
as programmed.
All memory
appears to be
lost.
D16 Chip with another chip containing
new software or reload your program.
Page 5-9
Bulletin 1352 5.3 System
5-4
Troubleshooting Guide Cont.
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
None Main fuses A. Insufficient Precharge A. Verify precharge timer TR1 isset
blown Time greater than 0.5 sec.
B. Precharge resistor B. Measure precharge resistor values
open. (10 ohms each) replace if necessary.
Check that K3 energizes during
precharge time and de-energizes after
precharge time.
C. Malfunctioning Main C. Open Main Disconnect and verify
Contactor Unit. (K4) contactor operates freely.
D.Malfunctioning diode D. Replace G1,G2 or G3 (30 - 180 KVA ).
rectifier G51,G52 or G53 (210 -340 KVA ). or V51
- V56 on 460 -870 KVA units.
Check/ Replace bad diodes
E. Cap. bank or inverter E. Inspect/Measure Capacitors and Bus
shorted “ + “ to “-”. circuits.
F. Excessive voitage at F. Measure input voltage. Voltage
input to drive terminals. must be within * 10% of nameplate
| rating (460 VAC or 575 VAC) and within
5% of the other phases.
None Main Fuses blow A. Diode rectifier is weak A. Replace G1, G2 or G3 (30-115 KVA
periodically
while running.
and malfunctioning.
B. Capacitor Bank or
Inverter Intermittantly
Shorted “ + “ to "-".
C. Excessive voltage at
input to drive terminals.
D. Intermittent single
phasing of incoming 3
phase power.
E. An intermittent
problem exsists in the
motor circuit.
F. Phase voltage
unbalance greater than
6.5%.
units). G51, G52 or G53 (210 - 340 KVA)
Check/Replace bad Diodes V51 - V56
(460 - 870 KVA)
B. Inspect/Measure Capacitors and Bus
Circuits.
Check for loose wires or material in bus
circuits.
Check for worn or cracked insulation
on main power conductors.
C. Check input voitage. Voltage must
be within + 10% of nameplate rating
(460 VAC or 575 VAC). `
D. Check supply network cables,
terminations and switches.
E. Check motor winding for
intermittent shorts or grounds.
Check motor winding or connection for
an open circuit.
Check motor circuits and wires with
appropriate meters.
Verify reliable terminations and
insulation.
F. Correct cause of voltage imbalance in
supply lines.
Page 5-10
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
None DC Bus fuses A. Capacitor bank or A. Inspect/Measure capacitors and bus
blow while inverter intermittently circuits.
running or shorted “ +" to “-". Check for loose wires or material in bus
starting circuits. |
Inverter. Check for worn or cracked insulation
(140KVA and on main power conductors.
above only) B. Anintermittent B. Check the motor windings for shorts
problem exists in the or grounds.
motor circuit. Check the motor windings or
connections for an open circuit.
Check the motor circuits and wires
with an appropriate meter and verify
integrity of terminations and
insulation.
None DC fuses blow A. Short circuit in the A. Check for short circuit in
when main inverter. semiconductor and replace if
contactor K4 is necessary.
closed. B. Misfiring of GTO B. Check data of fault queue
Thyristors Parameters 176 - 181.
C. Inverter intermittently C. Inspect/Measure capacitors and bus
shorted “ + “ to “-" orto circuits.
chassis. Check for loose wires or material in
main circuits.
Check for worn or cracked insulation
on main power conductors.
FLO1 (CP-1) C9 Capacitor A. Loose connections A. Verify solid connections at chopper
circuit voltage bus bars.
pd UNDERVOLT too low. Reseat connectors on INU A7 Chopper
(140KVA and larger)
B. INU A7 Chopper Control
Card malfunctioning
C. Short circuited
capacitors C9.1 - C9.N
D. V17 Chopper Thyristor
malfunctioning
E. INU A4 Pulse Amp
malfunction
F. Precharge time too
short
Control Card.
Verify connections at thyristor V17.
B. Inspect/Replace fuse F1 on A7
Chopper Control Card.
Replace INU A7 Chopper Control Card
Verify that the INU cooling fan breaker
F11 and Temp. sensor $1 are closed.
C. Disconnect the chopper capacitors
from the circuits at the Bus Bars.
Inspect and measure capacitors for
short circuits.
D. Replace V17 and V28 thyristors.
Check/Replace INU A8 Snubber Card
E. Replace A4 Pulse Amp.
F. Readjust timer TR1 to 0.5 seconds.
Page 5-11
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
FLO2 (CP-1) C9 Capacitor A. Loose connections A. Tighten connections at chopper bus
CHOP OVERVOLT circuit voltage bars.
(CP-2) too high. Reseat connectors on INU A7 Chopper
Control Card.
B. INU A7 Chopper Control 8. Replace INU A7 Chopper Control
Card malfunctioning Card
FLO3 (CP-1) Voltage Supply AA. Voltage Supply to the A. Check incoming supply voltage.
AUX to the Circuit Drive is Too Low. Voltage must be within + 10% of
UNDERVOLT Boards is nameplate rating and each phase
(CP-2) insufficient within 5% of each other.
B. DC Bus voltage (UC) is B. Check condition of DC bus.
low or DC Bus is not
charged.
C. Auxiliary 215 VAC C. Measure 215 VAC supply to INU at
supply to INU is low or Terminals. Replace Auxiliary power
missing. card if necessary.
Verify INU cooling fan breaker F2 or
F11 is closed.
D. Power Supply INU - A3 D. Check fuses on INU-A3 Power Card
or Auxiliary Power Card (INU-A9 on units 140KVA and larger)
INU A9 is malfunctioning Check status of LED on Power Supply
- Card INU A3. Replace card if necessary.
Check status of LED on Auxiliary Power
Supply Card INU A9. Replace card if
necessary.
FLO4 (CP-1) INU Heatsink A. Obstructed coolingair ~~ A. Remove any obstructions from
OVERTEMPERATURE temperature is flow. louvers or heatsinks.
(CP-2) too high. B. Room air temperature B. Cool air temperature to below 40C
too high.
C. INU cooling fan is
malfunctioning or is
stalled.
D. Heatsink thermal switch
has malfunctioned.
E. Overtemperature
circuitry has
malfunctioned.
F. Unbalanced phase
voltage.
(104F)
C. Check Cooling fan circuit breaker.
Check that the fan rotates and remove
any obstructions. Replace fan if
necessary.
D. Check that the thermal switch
located at the top of the INU is not
open, replace if required.
E. Replace the INU- A3 power supply
(115 KVA and smaller drives)
Replace the INU - A7 Chopper Control
(140 KVA and larger drives)
F. Correct cause of unbalanced phase
voltages to within 5%.
Page 5-12
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
FLOS (CP-1) The A. Asudden increase in A. Check the process for unusual load
OVERCURRENT Instantaneous motor load occured or jam.
(CP-2) Peak Currenthas B. À mechanical bind has B. Check for bearing , belt or gear
exceeded 230% caused high currents failure.
of Drive rating C. Problem exists in motor C. A motor winding has shorted or
circuit. grounded.
A motor winding or connection has
an open circuit.
Check motor circuit with appropriate
meter.
D. IR Comp setting D. Check and reset IR compensation
incorrect | Check and reset current limit.
E. Problem with E. Check and reset Accel/Decel rates.
accel/decel rates Try to adjust so that the drive does
not go into current limit, but follows
the ramp instead.
F. Attempted to start F. Increase Parameter 75 Restart Delay
before motor EMF (1000 = 1 Sec.)
decayed
FLO6 (CP-1) The DC Bus (Uc) A. Supply voltage to the A. Maximum permissable supply
DC OVERVOLT Capacitor drive is too high. voltage is 110% of rated.
(CP-2) Voltage has Transformer taps must be changed to
exceeded 130% reduce AC voltage.
of rated. B. The load has overhauled B. The decel ramp is too rapid. Extend
the motor. the decel ramp by increasing
Parameter 66 value,
C. Regen torque limittoo C. Reduce the Regen Torque Limit
high. Parameter 80 value.
Controlled braking may be required.
D. INU A3 Power Supply Uc D.Check that Parameter 207 is
Voltage Measurement between 900 and 1100. if the value is
erroneous beyond these limits, replace INU- A3
Measure the actual DC Bus voltage
with a meter. It should be 621 VDC
(460 V). Verify values with Parameter
207. If the DC Bus voltage is OK,
replace INU- A-13.
*Note: Atno load, DC voltage may
be as high as 716 volts with 460V
input + 10%.
FLOZ7 (CP-1) DC Bus Voltage A. DC Bus not charged A. Check if main contactor is closed
DC UNDERVOLT (Uc) Capacitor B. DC Bus fuse blown B. Replace fuse
(CP-2) Voltage too low. C. INU- A3 Power Supply C. Measure the actual DC Bus Voltage
Uc voltage measurement
erroneous.
with a meter and verify the value with
Parameter 207. If the D.C. Bus voltage
Is within + 10% of 621 VDC replace
INU-A3.
Page 5-13
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display
Symptom
Probable Cause
Recommended Solutions / Comments
FLO9, v11- U1 FAULT
FL10, v14- U2 FAULT
FL11,Vv12-V1 FAULT
FL12, V15 - V2 FAULT
FL13,V13-W1 FAULT
FL14, V16 - W2 FAULT
(GTO Only)
(140- 870 KVA only)
A. Power semiconductor
device or pulse amplifier
malfunction. For
example: V12-V1 FAULT
refers to the power
semiconductor of positive
branch of “V* phase or its
puise amplifier.
A. Reset the fault. Drive will check for
shorted cells, motor leads or ground
faults. Fault 15 will be the
acknowledgement if they are present.
If the fault repeats check that pulse
amp (cards A4,A5 and A6) LED's are lit.
If they aren’t, check power supply
connector X3 and condition of fuses F1
and F2.
Check fuses on Power Supply Card A3
and Aux Power Supply A9.
If the fault cannot be located, it may
actually be a FL 05 Fault.
If itis not possible to reset the fault,
check that the flat cables of control
and pulse amplifier cards are firmly
connected. Check the fuses F2 thru F5
on the Power Supply Card. If a fuse is
blown, check the power
semiconductor device. !f the fault isn't
found, replace the pulse amplifier card
or control card as required.
FLO9, v1 FAULT
FL10, va FAULT
FL11, V2 FAULT
FL12, v5 FAULT
FL13, V3 FAULT
FL14, v6 FAULT
(GTR Only)
(30- 115 KVA only)
A. Power semiconductor
device or pulse amplifier
malfunction. For
example: VS FAULT refers
to the power
semiconductor of positive
branch of “V” phase or its
pulse amplifier.
A. Reset the fault. Start-up the
inverter. If the fault occurs again,
there is a short circuit in the output
connector or phase power semi-
conductor device of the phase
indicated by the fault code or pulse
amplifier malfunction. In the case of
no short circuit in the output
connector, check the condition of the ‘
power semi-conductor device
If itis not possible to reset the fault,
check that the flat cables of control
and pulse amplifier cards are firmly
connected. Check the fuses F2 thru F5
on the Power Supply Card. If a fuse is
blown, check the power
semiconductor device. If the fault isn't
found, replace the pulse amplifier card
or control card as required.
Page 5-14
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display
Symptom
Probable Cause
Recommended Solutions / Comments
FL15 (CP-1) A Low resistance A. Moisture in wire or A. Dry out or replace.
SHORT CIRCUIT / Phase-to Phase motor insulation
GROUND FAULT or Phase - To - B. Cracked or Stripped B. Replace wire or tape.
(CP-2) Ground is wire insulation or
(140KVA and Larger) detected termination tape. |
C. Motor circuitincorrectly C. Verify, inspect, correct and test with
wired or terminated. meggohmeter.
D. ES Limit incorrect D. Parameter 275 should be set to 100
E. Motor winding shorted E. Replace Motor
FL17 (CP-1) Serial Data A. Drive improperly A. See Section 2 for proper grounding
COMMUNICATION Communication grounded. procedures.
FAULT has been В. А1 5ирр\у Сага LED not B. Check that the cables connecting A9
(CP-2) interrupted or Hluminated auxiliary power supply and control
lost card are firmly connected
C. A1 supply card LED is C. Baud rate values are set incorrectly
Huminated. or A110C card is malfunctioning. The
correct baud rate for channel 1 is 4800
Baud which is set correctly when swich
S1 onthe control card is in position a-c.
Replace IOC card if necessary.
D. Fiber Optic cables D. Check connections, and replace
damaged or disconnected. cables if damaged or broken.
FL18 (CP-1) Tach pulses A. Tach Cables faulty or A. Check condition of cables and that
TACH LOSS faulty or non- disconnected. they are installed correctly.
(CP-2) existant, or B. Process overload has B. Check the motor and load for
motor has caused motor to stall. jamming and correct.
stalled.
FL19 (CP-1) A currentsignal A. Current is being A. A bypass or alternate supply
CURRENT issensedwhen backfed from the motor. voltage is present. Isolate the drive
MEASURING FAULT theinverteris output from the motor circuit.
or CURRENT stopped. B. A Hall Effecttransducer B. Aribbon cable connection to the
FEEDBACK ERROR | is giving an erroneous Hall Effect transducers is bad, or the
(CP-2) signal. transducer itself is malfunctioning and
C. The signal conversion to
digital data is incorrect.
D. Current Offset limit
incorrect
must be replaced.
C. Check Parameters 219 and 220 for
excessive value, they should be less
than 1000. (Param 219 monitors
U-Phase Current, and Param 220
monitors V phase Current.)
Check Parameter 219 and 220 as
detailed above and replace control
card if necessary.
D. Check Parameter 190. Value should
be 50.
Page 5-15
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display
Sym ptom
Probable Cause
Recommended Solutions / Comments
FL20 (CP-1) Drive hasbeen A. Stall protection feature A.Refer to the 5.2 manual
MOTOR STALLED incurrentlimit improperly adjusted.
(CP-2) and below stall B. Load is too great for B.Reduce load
frequency too drive or motor
long. C. Stall Time setting istoo C.Correct Stall Time setting at
low. Parameter 83 ( “0” = Infinity)
D. IR Comp level istoolaow D. Readjust IR Comp, see section 3-3.7
FL21 (CP-1) A. Matching Card INU A- A. Check that the matching card is
MATCHING CARD 2.2 Connection is looseor firmly connected and that the
FAULT missing. matching card type corresponds to to
(CP-2) the inverter type.
B. Matching Card is B. Replace Matching Card.
malfunctioning
FL22 (CP-1) Processor EEPROMS D17 and D18 Turn power on and off and wait two
PROCESSOR FAULT information is faulty or Control Card INU- minutes. Try operation again. Replace
(CP-2) erroneous A2 malfunctioning. EPROMS D17 and D18 on control card
if malfunction remains Replace
Control Card INU-A2
FL25 (CP-1) An Interlock ata A. Missing Customer A. Check interlocks and correct.
INTERLOCK or Digital Input is Interlock Reset display by pressing "DISPLAY “
CUSTOMER FAULT detected. twice.
(CP-2)
FL26 (CP-1) Same as FLT 25. Motor running hot. Check for proper cooling air flow thru
INTERLOCK or (Normally used, motor. If motor is operating at below
CUSTOMER FAULT for motor base speed, it may require a separate
(CP-2) overload, RTD cooling fan.
Monitor, Motor
Thermostat etc.
Page 5-16
Bulletin 1352 5.3 System
Troubleshooting Guide Cont.
Diagnostic Display
Symptom
Probable Cause
Recommended Solutions / Comments
FL40 (CP-1) Asymmetrical Peak Phase Currents Check Parameter 78 value (Default is
Line Current inbalance exceeds 3000 which equals 30% rated current).
Parameter 78. Check for incoming supply line fuse
blowing and improperly closed switch
in supply line. |
FLA1 (CP-1) Startup lasts too Synchronization circuit Check incoming line voltage is within
long. cannot find an + 10% of rated and each phase is
appropriate startup point within * 5% of the other two phases.
within 20ms. Correct incoming line problem.
FL42 (CP-1) Prohibited All sector parameters set Check sector parameters (Section 4-5).
Startup sectors to ©, or line voltage Check incoming line for blown fuse or
problem improperly closed switch.
FLA3 (CP-1) No digital inputs Communication error If digital inputs are not being used, set
within 2.8 parameter 173 to O. If digital inputs
seconds are used refer to section 4-6.2 on serial
communications. Check that
grounding is per section 2-5.
FL44 (CP-1) Nolinevoltage Low line voltage orsingle Check incoming line voltage as in
phasing
Fault 41.
Page 5-17
Bulletin 1352 5.3 System
Troubleshooting Information Messages
Diagnostic Display Symptom Probable Cause Recommended Solutions / Comments
SA50 (CP1) There is no information in
NO BACKUP / the EEPROM Memory
NEW EP (CP2)
SA51 (CP1) Writing to EEPROM
STORED TO BACKUP Memory.
SA52 (CP1) Writing to A. Position of $4 switch A. Check switch position
NO WR TO EEPROM EEPROM must be A-B to write.
(CP2) Memory is B. EEPROM D16 is faulty B. Replace D16 EEPROM with known
inhibited good EEPROM.
SA53 (CP1) Drive will set Re-Check value being entered for
PARAMETER QUT of parameter value validity.
LIMITS (CP2) to min/max
allowable
SAS5 (CP1) Parameter
ILLEGAL remainsat
PARAMETER - original value
CHANGE NOT
PERMITTED (CP2)
SA56 (CP1) Insufficient A. Switch S-3 is in A-C A. Change switch position
NO BATT BACKUP voltage from (battery OFF position)
(CP2) NiCad battery B. Battery has B. Allow 20 hours with power on for
malfunctioned or battery to recharge. Cycle power on
discharged. and off to clear fault message. If
message refuses to clear replace
Control Card INU - A2.
SA57 (CP1) Auxiliary Power is low. Check Supply Voltage.
LOW AC/DC Volt ;
SA58 (CP1) Start is inhibited by the A stop signal overrides a start signal.
START INHIBIT processor. Check logic sequencing external to
(CP2) drive. Check Start/Stop buttons.
SA59 (CP1) The processor is initializing
SYSTEM RESTART its operation. This
(CP2) normally occurs when
power is first applied to a
Control Card.
Page 5-18
Bulletin 1352 5.3 System
5-5
Trends
5-5.1 General - The Bulletin 1352 LGU control software contains 8 sampling
buffers each with 100 sample capacity. These Buffers can be used to store
measurement data to aid in troubleshooting.
A sampling interval can be selected which corresponds to time interval
4ms ...262 seconds per sample by adjusting the number in parameter
TRENDIVAL 196. The time interval is the TRENDIVAL times 4ms. Scalar
control uses 3ms intervals rather than 4ms.
Triggering the storage (as explained in Sect. 5-5.2.3) can be done one of three
ways:
On a fault
Based on the value of Trend 1
Manually
5-5.2 Use of Trend
5-5.2.1 Selection of Monitored Addresses - Set a desired parameter number for
the trend control addresses which are going to be used. The default parameter
selected for the LGU is shown in the table below.
Trend Buffer Parameter Trend Storage Param
Buffer # Location Location Monitored Fetch Location
1 191EE 218 DC VOLTAGE REFERENCE 320 200 - 599
2 192EE 219 REACTIVE CURRENT REFERENCE 321 600 - 699
3 193EE 221 ACVOLTAGE REFERENCE 322 700 - 1799
4 194EE 222 REACTIVE CURRENT CONT. OUTPUT 323 800 - 899
5 195EE 223 ACTUAL AC VOLTAGE 324 900 - 3999
6 241EE 224 ACTUAL DC VOLTAGE 325 1000 - 1099
7 242EE 225 ACTUAL AC VOLTAGE-UNFILTERED 326 1100 - 1199
8 243EE 226 PHASE ANGLE 327 1200 - 1299
5-5.2.2 Selection of Sampling Interval - A sampling interval is selected with 4ms
steps at 196EE.
196EE 01 = 4mssampling interval
2 = 8mssampling interval
3 = 12mssampling interval
3-5.2.3 Selection of Triggering Condition -
ÓN FAULT: A trend triggering occurs on an operation fault by setting
Parameter 197EE to -1. In this case trend triggering stores 80 samples before
the fault and 20 samples after.
e.g.: + "., : "e, vn 9
Trigger
Triggering From Fault
Page 5-19
Bulletin 1352 5.3 System
5-5.2.4
5-5.2.5
TREND 1 VALUE CHANGE: A triggering condition can be set using trend
buffer 1 at address 197EE
197EE = 1 Triggers when deviation of two consequent samples of Trend 1
(191) overshoot the number set in parameter 197.
20 — 80 —
Trigger
Triggering From TRENDTRIG (197) or TRENDSAVE (199)
MANUALLY: A Triggering can also be accomplished “Manually” by using
single step mode in the same manner as an oscilloscope by setting 199
(TREND__SAVE) #0. In this case trend triggering is instantaneous and 199
is automatically reset to 0.
Monitoring of the Trend Triggering - The content of the memory location
TRIGCOUNT (200) is increased by one every time a trend triggering occurs.
Trend Content D/A Conversion - An analog signal can be obtained since
each trend buffer has an address which can be used for connecting a D/A
converter to a buffer.
The addresses are:
320EE Trend buffer 1
321EE Trend buffer 2
322EE Trend buffer 3
323EE Trend buffer 4
324EE Trend buffer 5
325EE Trend buffer 6
326EE Trend buffer 7
327EE Trend buffer 8 `
The sample conversion interval is 20ms/sample and the entire buffer content
conversion lasts 2s. This rate is sufficient for plotter operation. Each sample
contains a synchronization mark which serves for identification of trend’s
start point.
sync pulses
e.g.: Y Р.
„=
ER
a.
X
start of trend buffer
end of trend buffer
Page 5-20
Bulletin 1352 5.3 System
5-5.2.6
5-6
Changing Printed Circuit
Boards
3-6.1
5-6.2
Trend Investigation in the Numeric Form - The numeric values of the
trends can be viewed at the following addresses:
500 - 599 Trend buffer 1
600 - 699 Trend buffer 2
700 - 799 Trend buffer 3
800 - 899 Trend buffer 4
900 - 999 Trend buffer 5
1000 - 1099 Trend buffer 6
1100 - 1199 Trend buffer 7
1200 - 1299 Trend buffer 8
Bulletin 1352 Digital A.C. Drives feature printed circuit boards
that require no adjustments as part of the normal troubleshooting and
maintenance. This feature also helps simplify board replacement.
Circuit Board Replacement - The following steps should be followed when
changing the printed circuit boards:
CAUTION: The CMOS circuits utilized on the control circuit
cards can be destroyed by static charges generated by friction of
materials made of synthetic fibers. Use of bad circuit cards may
also damage related components. Observe proper care and
recommended practices when handling circuit cards.
A. Remove power by opening the disconnect switch and verify with a meter
that all circuits are voltage free.
B. Carefully detach all ribbon cables , noting their location and orientation
and whether the connectors were properly seated.
IMPORTANT: A grounded wrist strap should be used when replacing circuit
boards to protect against static discharge damage to the boards!
C. Remove the small metric mounting hardware with a screwdriver taking
care not to drop any of the associated washers into the other circuits of
the drive.
D. Lift out the circuit board in question, and check that the replacement
board is correct before attempting installation. Install the new circuit
board by replacing the mounting hardware and re-inserting the
connectors and switches in their correct location on the new board.
Steps A thru D apply to replacement of all printed circuit boards in the
Bulletin 1352 drive.
Control Card (103 CON/ 3500 C03) Replacement - In addition to the steps
mentioned above, the Control Card of the drive requires the transfer of the
following components when changing cards:.
A. Transfer EPROMS D17 and D18 to the corresponding locations on the
new Control Card using an I.C. removal/ insertion tool for CMOS
Circuits.
B. In order to retain the application software values, it will be necessary to
also transfer EEPROM D16 to the new card.
Page 5-21
Bulletin 1352 5.3 System
IMPORTANT: If the new empty EEPROM is left in the control card, it is
important that you observe item “D” when first reapplying power
C. Transfer the matching card and it’s spacers from the suspect board to the
new control board by removing the four mounting screws from behind
the card and re-installing them in the proper location on the new card.
Be sure to attach the X-2 connector firmly into its socket and latch the
connector tabs.
D. When reapplying power to the Bulletin 1352 after installing a new
control card, you must wait at least 2 minutes after the red LED on the
control card lights before interrupting power or adjusting parameters. If
you choose to use the new EEPROM (D186) which was supplied with the
card, it can take as long as 3 or 4 minutes before the LED lights.
After the LED illuminates, it is permissible to proceed with adjusting the
parameter values and operating the drive
5-7
Checking and Replacement When testing power semiconductors, the measurements must be made with
of Power Semiconductors multimeter that uses a sufficiently high current for resistance measurements.
Always determine the polarity of your instrument leads when performing
resistance measurements.
5-71 Power Transistors (GTR) - If it is suspected that a damaged GTR power
semiconductor device exists, proceed as follows:
® Before proceeding, verify that the drive is voltage free.
e Disconnect motor cables
® Disconnect card terminals of power devices
e
Measure the collector to emitter and collector to base resistances
(positive probe in contact with the collector lead). The resistances
must be different from those in the short circuit state (the resistance
value depends both on the ohmmeter used and the semiconductor
device itself). Generally, this is a resistance greater than 10k Ohm.
e Reapply voltage to the drive.
WARNING: Hazardous voltages will be present in the drive
when performing the following tests!
e Allow sufficient time for the intermediate circuit to charge up to `
measurement voltage. Switch the meter for a voltage measurement
and check the offset voltage of the diodes between base and collector
and emitter and collector (anode in contact with first mentioned lead)
values should be approximately 0.3V to 0.5V.
5-7.2 GTO and Free Wheeling Diodes - If a damaged or malfunctioning GTO
power semiconductor or Free -Wheeling Diode is suspected, proceed as follows:
® Verify that all the Drive is voltage free before proceeding.
® disconnect motor cables
® disconnect card terminals of power devices
e
Measure the collector to cathode, anode to gate, and cathode to gate
resistances (positive probe in contact with the first lead mentioned).
The value must be different from those in the short circuit state (the
resistance value depends both on the ohmmeter used and the
semiconductor device itself). Check the diodes by measuring
resistance between the cathode and anode.
e Reapply voltage to the drive.
Page 5-22
Bulletin 1352 5.3 System
5-7.3
when performing the following tests!
A CAUTION: Hazardous voltages will be present in the drive
Allow sufficient time for the DC Bus circuit to charge up to measurement
voltage. Switch the meter for a voltage measurement and ensure that
diode junctions exist between gate and the cathode (positive on gate).
Offset voltage should be approximately 0.5V. In the voltage range
measure offset voltage of diodes anode to cathode. If a damaged free-
wheeling diode is suspected, both the diode and thyristor will have to be
removed from the heat sink since they are connected in parallel. Remove
the thyristor by opening its clamp, and measure the diode condition.
NOTE: It is impossible to accurately measure the condition of the
thyristor when it is unclamped!
If the short circuit has been located, the semiconductor device must be
replaced.
Remove power from the drive,measure DC bus for 0 volts and remove the
bad semiconductor. If necessary, also detach the conductor busbar
positioned across the semiconductor as well as any associated leads. Note
the direction in which the device was originally installed. This will
ensure correct polarity when a replacement semiconductor is installed.
IMPORTANT: GTO devices must be replaced with the same
manufacturer’s device. Verify the correct type from the vendor part
number printed on the insulator portion of the device. Recheck the
clamping value for the new GTO.
Installation Instructions - Power semiconductors are precision devices. New
semiconductors should be stored in their original packages until required .
NOTE: To avoid confusion with “good” components, always clearly mark
suspected damaged components after removing them from the circuit.
A.
When replacing components, check that the new and old components have
the same type designation or that the new component can replace the old
one. At this stage, review the phases of the replacement procedure and
consider orientation of the heatsink. Care should be taken to assure
proper clearance between heatsink components to reduce possibility of
arc-over when voltage is applied to the Drive.
Preparation of the heatsink and busbar:
If the area is clean, spread out the remaining heatconducting compound
with a rubber spatula to obtain even distribution of compound. If the
area is dirty, wipe the heatsink surface and the busbar clean.
NOTE: Do not clean the surfaces too thoroughly of all grease residue,
since the machined aluminum surface will oxidize in a few seconds
possibly producing a poor heat conductive surface.
C. GTR Installation -
1. Clean the semiconductor contact surfaces with solvent and spread heat
conducting paste on the base of the heat sink.
2. Install the module in the heatsink and secure the clamping screws to the
following torque, tightening the screws alternately 1/8 turn at a time.
Metric Thread DIA Torque
Page 5-23
Bulletin 1352 5.3 System
3. Check the insulator and connections for damage and clean the insulator
and surrounding area with a solvent dampened paper towel. Tighten the
wires and conductor rails to the connector using the following torques:
etric Thread DIA
M
anat
D. GTO Installation -
1. Preparation of the semiconductor: Lightly rub the contact surface
carefully against a piece of No. 400 grit emery paper on a flat even
surface with circular movements. Clean the surfaces with a solvent and
immediately apply a very thin layer of heat-conducting compound
(Penitrox A or equivalent) on the contact surfaces using a rubber
spatula. Resolder the firing leads to the GTO thyristor, if required. The
first (grey) lead connects to the gate which is the electrode protruding
from the side of the thyristor through the insulator. The second (red)
lead connects to the other pin which is connected to the thyristor cathode
(The metal rim on the face of the device).
2. Tightening the press clamp: Place the centering pin in position and
check to be sure that length does not prevent the surface of the
semiconductor from fully contacting the heatsink surface. Place the
semiconductor under the press clamp (Type SLZF) and turn the clamp
plus or minus 90° left and right, leaving it in a position where the
connecting leads are not subjected to any stresses or sharp bends. This
procedure ensures spreading of the heat-conducting compound and
adequate surface contact of the semiconductor. Place the Mounting
Force Indicator (dial indicator) on the spring beam and zero it (Fig. 5-1).
Tighten the press clamp to finger tightness (screws tight but no
deflection of the beam). Check that the beam is parallel with the
heatsink surface. Determine the required compression force from the
semiconductor equipment list and read the correct beam deflection from
the charts in Tables 5-7 and 5-8. If not found on the chart, contact your
Allen-Bradley Representative to confirm the correct mounting force for a
particular semiconductor. Continue tightening the clamp using equal
turns on the clamping bolts until the proper force is reached.
3. Tighten wires and conductor busbar to the connector, maintaining the
following torque requirements: | ‘
Metric Thread DIA
Ear AUT,
eh aaa
№: som
4. Clean the insulator of the semiconductor and its surrounding area with a
disposable wiper moistened with solvent if necessary. Check that the
insulators and the connections are intact.
The following example is included to help clarify the procedure for GTO
identification and clamping force determination:
EXAMPLE: A 290 KVA LGU has a bad V17 GTO which was reported by
FLO1. Inspection of the GTO cell showed a manufacturer’s number of
“S6475KR” from Toshiba. By checking the Cross Reference table 5-7, the Allen-
Bradley Part Number for this GTO is listed as 501665.
Page 5-24
Bulletin 1352 5.3 System
Table 5-7 also lists the clamping force required to properly install the GTO.
Note some of the units can be used with different size clamps. This may cause
a requirement for a different deflection measurement as measured by the
force measuring gauge. The clamp number is determined by measuring the
distance between clamping bolts and selecting the proper deflection from
Table 5-8. When tightening the clamp make certain to alternate between
bolts and turn only 1/4 turn at a time.
Table 5-7. GTO Cross Reference
501667
501668
501669
501665
501666
593356
503355
503359
503354
503357
503358
504062
504063
504064
504065
504066
504067
504068
504069
56425R, 1300V, 880A
S6426R, 1300V, 1400A
SL427R, 1300V, 2220A
S56475R, 1300V, 370A
S6476R, 1300V, 560A
$6425W, 1700V, 840A
S6426W, 1700V, 1330A
FG1000 AL-34-1340,1700V,1330A
56427W, 1700V ,2100A
56475W, 1700V, 340A
56476W, 1700V, 530A
FG1000AL-26-8830, 1300V,880A
FG1000AL-26-1430,1300V,1400A
FG450BL-26, 1300V, 340A
FG600AL -26,1300V, 560A
W66013/2A,1300V, 560A
FG600AL-34-8430, 1700V, 840A
W660017/2B , 1700V, 530A
FG600AL-34-5320, 1700V,530A
Toshiba
Toshiba
Toshiba
Toshiba
Toshiba
Toshiba
Toshiba
Mitsubishi
Toshiba
Toshiba
Toshiba
Mitsubishi
Mitsubishi
Mitsubishi
Mitsubishi
Westcode
Mitsubishi
Westcode
Mitsubishi
89C
117
142
70A
89C
89C
117
117
142
70A
89C
89C
117
70A
89C
89C
89C
89C
89C
0.22 mm
0.112 mm
0.46 mm
0.09 mm
0.135 mm
0.22 mm
0.112 mm
0.08 mm
0.46 mm
0.09 mm
0.135 mm
0.183 mm
0.080 mm
0.09 mm
0.165 mm
0.115 mm
0.165 mm
0.115 mm
0.165 mm
Page 5-25
Bulletin 1352 5.3 System
Force Measuring Gauge
Deflection measured here
Clamp
Figure 5-1. Press Clamp Dial Indicator
Table 5- 8. Clamp Identification
aC TTS
TABLE OF CONTENTS
6. Preventative Maintenance
6-1. Preventative Maintenance Of Drive Equipment 1
6-2. Periodic inspection 1
6-2.1. Contamination 1
6-2.2. Operating Mechanisms 1
6-2.3. Contacts 1
6-2.4. Terminals 2
6-2.5. Coils 2
6-2.6. Solid State Devices 2
6-2.7. Bus Connections 2
6-2.8. Overload Maintenance After A Fault Condition 2
6-2.9. Bus Capacitors 2
6-2.10. "Keep Good Maintenance Records” 2
Section
6
BULLETIN 1352 PREVENTATIVE MAINTENANCE
6-1
Preventative Maintenance
of Drive Equipment
6-2
Periodic Inspection
6-2.1
6-2.2
6-2.3
can be hazardous. Severe injury or death can result from
electrical shock, burn, or unintended actuation of controlled
equipment. Recommended practice is to disconnect and lock out
control equipment from power sources, and allow stored energy
in capacitors to dissipate, if present. If it is necessary to work in
the vicinity of energized equipment, follow the safety related
work practices of NFPA 70E, Electrical Safety Requirements
for Employee Workplaces.
A WARNING: Servicing energized industrial control equipment
Industrial control equipment should be inspected periodically. Inspection
intervals should be based on environmental and operating conditions, and
adjusted as indicated by experience. An initial inspection within 3 to 4
months after installation is suggested. Applicable parts of the following
guidelines should be used:
Contamination - If inspection reveals that dust, dirt, moisture or other
contamination has reached the control equipment, the cause must be
eliminated. This could indicate an incorrect or ineffective enclosure, unsealed
enclosure openings (conduit or other) or incorrect operating procedures.
Dirty, wet or contaminated parts must be replaced unless they can be cleaned
effectively by vacuuming or wiping. DO NOT USE SOLVENTS
Operating Mechanisms - Check for proper functioning and freedom from
sticking or binding. Replace any broken, deformed or badly worn parts or :
assemblies according to individual product renewal parts lists. Check for and
securely re-tighten any loose fasteners. Lubricate only if specified in
individual product instructions.
IMPORTANT: Allen-Bradley magnetic starters, contactors and relays are
designed to operate without lubrication-- do not lubricate these devices since
oil or grease on the pole face (mating surfaces) of the operating magnet may
cause the device to stick in the "ON” mode. Some parts of other devices are
factory lubricated -- if lubrication during use or maintenance of these devices
is needed, it will be specified in their individual instructions. If in doubt,
consult the nearest Allen-Bradley Sales Office for information.
Contacts - Check contacts for both wear and dirt accumulation. Contacts are
not harmed by discoloration and slight pitting. Contacts should never be
filed, as dressing only shortens contact life. Contact spray cleaners should not
be used as their residues on magnet pole faces or in operating mechanisms
may cause sticking, and on contacts can interfere with electrical continuity.
Contacts should only be replaced after silver has become badly worn. Always
replace contacts in complete sets to avoid misalignment and uneven contact
pressure.
Page 6-2
Bulletin 1352 5.3 System
6-2.4
6-2.5
6-2.6
6-2.7
6-2.8
6-2.9
6-2.10
Terminals - Loose connections can cause overheating that can lead to
equipment malfunction. Check the tightness of all terminals and bus Бай
connections and securely tighten any loose connections. Replace any parts or
wiring damaged by overheating.
Coils - If a coil exhibits evidence of overheating (cracked, melted or burned
insulation), it must be replaced. In that event, check for and correct
overvoltage or undervoltage conditions, which can cause coil failure. Be sure
to clean any residue of melted coil insulation from other parts of the device or
replace such parts.
Solid State Devices - Solid state devices require little more than a periodic
visual inspection. Printed circuit boards should be inspected to determine
whether all ribbon cables are properly seated in their connectors. Board
locking tabs should also be in place. Necessary replacements should be made
only at the printed circuit (PC) board or plug-in component level. Solvents
should not be used on PC boards. Where blowers are used, air filters if
supplied should be cleaned or changed periodically depending on the specific
environmental conditions encountered. For additional information see
NEMA Standards Publication No. ICS 1.1-1984 entitled: "Safety Guidelines
for the Application, Installation and Maintenance of Solid State Control”
WARNING: Use of other than factory recommended test
equipment for solid state controls may result in damage to the
control or test equipment or unintended actuation of the
controlled equipment.
Bus Connections - The bolts in the DC bus should be checked for tightness
and any dirt or dust on the bus supports should be removed.
Overload Maintenance After a Fault Condition - See NEMA Standards
Publication No. ICS 2.2 entitled: Maintenance of Motor controllers after a
fault condition (also published as NEMA Standards Publication No. ICS 2,
Part ICS 2-302).
Bus Capacitors - The voltage of each section on the monitoring board (3500 -
CBS) should be checked for even division of voltage. If the voltage is
unbalanced, then the capacitors in the CBU should be checked to make
certain they are not shorted. If fuses are provided, they should be checked for
opens. The capacitors should be visually checked for any signs of expansion or
bulging which could cause the capacitor to fail.
“Keep Good Maintenance Records” - This rule will be most helpful in
locating possible intermittent problems by pointing to a particular area of
recurring trouble within the overall system. Further, good maintenance
records will help reduce major costly shutdowns by demanding the use of
proper test equipment and an appropriate inventory of spare parts. For
additional information see NFPA 70B, RECOMMENDED PRACTICE FOR
ELECTRICAL EQUIPMENT MAINTENANCE, published by the National
Fire Protection Association.
—]———]—— LL. Ú—Ñ——D——;———]LL TE
TABLE OF CONTENTS
7. Reference Documents
7-0. Parameter Tables 1
7-1. Operational Controls 2
7-1.1. Reference Values 3
7-1.2. Display Addresses 4
7-1.3. LGU Control 4
7-1.4. Parameters Of The LGU 6
7-1.5. CP2 Displays Scaling 7
7-1.6. Serial Communications Channel 1 8
7-1.7. Serial Communications Channel 2 9
7-1.8. Parameters 2 Of The LGU 10
7-1.9. Diagnostics 12
7-1.10. Actual Values 13
7-1.11. Logic Data Provided By The LGU 14
7-1.12. Debugger 15
7-1.13. Test Points 16
7-1.14. The Memory Area Reserved For The I/O Of SAFT 163 10C 18
7-1.15. Parameters 3 Of The LGU 18
7-1.16. 21
7-1.17. | 22
7-1.18. 24 | .
7-1.19. Trend Scanning Buffers 25
7-2. Number Systems 26
7-2.1. Decimal System 26
7-2.2. Binary And Hexadecimal Number System 26
7-2.3. Conversion From One Number System To Another 26
7-2.4. Negative Numbers 28
7-2.5. Use Of Hexadecimal (Binary) Numbers 29
7-3. Parameter Values After Start-Up 30
7-4. Rated Values 34
7-5. Rated DC Voltages & Currents 34
7-6. DC Capacitors 34
7-7. LFU's 35
Section
7
BULLETIN 1352 REFERENCE DOCUMENTS
7-0
PARAMETER TABLE
(Numerical Order)
TYP=
H=
H.Lim.=
Low Lim. =
Init=
EXPLANATION =
-Blank-, if the value is saved only in the RAM memory
andis not protected against power breaks.
-EE-, if the value is stored in the EEPROM memory
-M-, if the value has battery backup
Decimal address
Hexadecimal address
Largest Decimal number that can be stored at the given
address. If the number is not provided, the high limit is
+ 32767.
Smallest Decimal number that can be stored at the given
address. If the number is not provided, the low limit is
— 32767.
Initial value which is stored to the EEPROM when it is
empty. The value is equal to O if the initial value is not
given.
Explanation. If not presented Parameter is not used in
the given program version.
Page 7-2
Bulletin 1352 System
7-1
Operational Controls
Type D H H.lim. Low lim. Init Explanation
1 001
2 002 START. Start-up request when =0 (not zero) the
LGU starts up automatically or remains waiting for
braking to the AC network in the diode bridge
mode (90EE = 0)
3 003 STOP. Shutdown request. When the given value is
= 0, LGU shuts down immediately. Zero reset is
done automatically.
6 006 CONTACTOR. The 0 value is set when the main
contactor is open and not 0 when itis closed.
7 007 LOCKPANEL. Control panel is disabled when not 0.
The control is released when 0.
8 008 1 EEROMLOCK. When the parameter is not O saving
to the EEPROM is initiated. Cycle duration is
Independent of the value.
EE 9 009 8993 TBCTRANSMIT1. Control Word which determines
the I/O input transmission of the 3500-T74 terminal
block card.
EE 10 00A 12852 TBCTRANSMIT2. Same as above.
12 00C RESET. Fault acknowledgement. When RESET is +0
the LGU acknowledges a fault. At the same time
the zero set of 13 is performed. The zero set of
RESET is done automatically.
13 00D LGUCONTROL. Concentrated LGU Control Word.
by = RESET, by = START, bg = STOP, (0 = OFF,
1 = ON)
14 00€ CP2_ ANALOG. The analog input data for CP2 is
sent to this address.
17 011 RARCNT. Rapid Auto-Restart Counter. Increments
by 1 after each RAR event.
18 012 DARCNT. Delayed Auto-Restart Counter.
Increments by 1 after each DAR event.
19 013 CP1_BUTTONS. The terminal block card stores
pushbutton signals in the packed byte form to this
address.
20 014 SELMASTOPC. Counts stop signals coming from the
serial communications channel.
Page 7-3
Bulletin 1352 System
7-1
(cont.)
Type D H H.lim. Low lim. Init Explanation
21 015 DRIVESTOPC. Counts stop signals developed by the
LGU itself (eq. fault).
22 016 COAST_STOP. Stop command. The command
functions as STOP 3. Zero reset is automatic.
23 017 BUTTONSWORD. CP?'s push button signals in
packed byte form.
24 018 START1_P. Start-up command. Functions the same
as START 2. Zero reset is automatic.
25 019 START2_P. Start-up command. Functions the same
as START 2. Zero reset is automatic.
7-1.1
Reference Values
Type D H H.lim. Low lim. Init Explanation
EE 26 O01A 1071 UCREFG. DC voltage external reference. 1000
corresponds to the rated value.
EE 27 018 0 IQREFG. Reactive current external reference. 1000
corresponds to the rated value. |
EE 28 01C 850 KQ. Reactive current regulator limiting parameter.
1000 corresponds to the rated current.
EE 29 01D 900 K1. Active current limiting parameter .1000
corresponds to rated current
Page 7-4
Bulletin 1352 System
7-1.2
Display Addresses
Type D H H.lim. Low lim. Init Explanation
32 020 Reserved for the addresses of the display messages
between the control panel and LGU.
33 021 2
34 022 -"-
35 023 -"-
36 024 =".
37 025 -"-
38 026 ="
39 027 „nn
40 028 -”-
41 029 -"-
42 02A “
43 02B 4
44 02C -"-
45 02D *.
7-1.3
LGU Control
Type D H H.lim. Low lim. Init Explanation
EE 48 030 — 1 IQCONT. If IQCONT = 0, the reactive current control
Is disabled. If IQCONT #0, the reactive control is
enabled.
EE 49 031 1 LGUSTATUS. Concentrated Control Word.
EE 51 033 400 PUQI. Gain factor of the integrated part of reactive
current controller.
EE 52 034 4 PUQ. Gain of the reactive current controller.
EE 53 035 500 PUL Gain of the intergrated part of the DC voltage
controller.
EE 54 036 DUSET. If the reactive current controller is not in
use, DUSET is used as a reference for the voltage
across AC line reactor. 8000 corresponds to the
rated AC voltage.
Page 7-5
Bulletin 1352 System
7-1.3
(Cont.)
Type D H H.lim. Low lim. Init Explanation
EE 55 037 98 KDLLL. DC voltage controller parameter.
56 038 7367 KDLUC. DC voltage controller parameter. A
calculation made by the LGU.
EE 57 039 1600 KFLL DC voltage controller parameter.
58 03A 6582 KFUC. DC voltage controller parameter. A
calculation made by the LGU.
EE 59 038 100 UCDIFMAX. Parameter of the FAST DC voitage
controller. The FAST controller functions if actual
voltage differs from the reference by more than
this setting. 1000 corresponds to the rated value.
EE 60 030 — 100 UCDIFMIN. As above, but the FAST controller
functions when the actual voltage has undershot
the reference by more than this setting.
61 03D 846 PUDII. Gain ofthe FAST DC voltage controller. A
calculation made by the LGU.
62 03E 846 PUDAA. -“-
63 03F 254 PUDIA. -“-
64 040 254 PUDAI. -"-
EE 65 041 320 LLGU. The LFU AC reactor inductance in
microhenries per phase.
EE 66 042 1540 CLGU. The CBU capacitance in 10 microfarad units
EE 67 043 460 ULGU. The LGU rated voltage in volts.
EE 68 044 577 ILGU. The LGU rated AC current in amps.
EE 69 045 5225 KLU. Auxiliary quantity for computing of (56).
EE 70 046 4668 KFU. Auxiliary quantity for computing of (58).
EE 71 047 600 KAA. Auxiliary quantity for computing of (61).
EE 72 048 180 KIA. Auxiliary quantity for computing of (63) and
(64).
Page 7-6
Bulletin 1352 System
7-1.4
Parameters of the LGU
Type D H H.lim. Low lim. Init Explanation
EE 78 04E 3000 UNBALCURR. Current unbalance limit within 5 sec
fault occurs (#20). 10000 corresponds to the rated
current,
EE 79 04F -5 DBMIRESTOP. Min. active current limit. If active
current is below this setting for the time set in 80EE
and in diode bridge mode, LGU stops and waits for
another braking requirement. 1000 corresponds to
the rated current.
EE 80 050 2500 DBMCNTR. See above. Time is given in 4ms
Increments.
EE 81 051 62240 UCUSCAL. A scaling factor between DC and AC
voltage measurements calculated by LGU. *
EE 82 052 0 DUREFO. The initial value for reactive current
controller output ie. the AC reactor voltage drop.
3000 corresponds to the rated AC voltage.
EE 83 053 1799 UCMSCAL. DC voltage measurement scaling factor*
EE 84 054 39272 UMSCAL. AC voltage measurement scaling factor. *
85 055 2008 XREL. The relative reactance of the AC reactor.
Computed by the LGU. 1000 corresponds to 100%.
EE 86 056 65535 0 48000 FNET. The rated frequency of the network.
Scaling: 40000 corresponds to 50 Hz (48000 to 60
Hz).
EE 87 057 625 RARMAXTIME. Time limit for rapid automatic
restart. 16ms increments.
EE 88 058 3125 RARMAXCOUNT. The value is equal to 87EE
multiplied by the allowed number of RARs.
EE 89 059 1 DARMAXCOUNT. The de-energized interval of a
DAR. A unit corresponds to 16ms.
EE 90 O5SA 0 DBMODE. If DBMODE = 0 the diode bridge mode is
OFF. If DBMODE = 0 the diode bridge is ON.
EE 91 058 60 UCSTRTOFF. The offset value for start of
regeneration calculation. 1000 corresponds to the
rated DC voltage.
EE 92 05C 280 FILTDELAY. The filtering delay of the AC voltage.
EE 93 05D 48 UCREFOFF. The offset value for DC voltage
reference calculation. 1000 correponds to the rated
DC voltage.
EE 94 05E 48 DUCSTRTOFF. The offset value for 239 calculation.
1000 corresponds to the rated DC voltage.
* Section 2-12.1
Page 7-7
Bulletin 1352 System
7-1.4
(cont.)
Type D H H.lim. Low lim. Init Explanation
EE 95 O05F 100 DUCDBM. When DC voltage is above 239 and
during 4ms rises above 95EE in the diode bridge
mode of operation, the LGU is started up. 1000
corresonds to the rated DC voltage.
96 060 ARFLAG. When ARFLAG = 0 rapid automatic
restartisin operation. Otherwise 0.
97 06! ARFAIL. When ARFAIL = 0 LGU shuts down.
7-1.5
CP2 Displays Scaling
Type D H H.lim. Low lim. Init Explanation
98 062 DSPMODE. If DSPMODE = 0, CP2 normal display is
taking place. When 1, FAULT display is taking
place.
EE 99 063 236 DSPADDR. A memory cell address of the FAULT
display.
EE 100 064 620 UCDISPMUL. DC voitage factor of the CP2 display.
Set equal to the rated voltage.
EE 101 065 1000 UCDISPDIV. DC voltage divider of the CP2 display.
Do not change.
EE 102 066 UCDISPRNT. DC voltage decimal point position of
the CP2 display. Do not change.
0 - no decimal point
1- one decimal digit
2 - two decimal digits, etc.
EE 103 067 577 IDISPMUL. The current factor of the CP2 display.
Set equal to the current rated value.
EE 104 068 1000 IDISPDIV. The current divider of the CP2 display.
Do not change!
EE 105 069 IDISPPNT. Decimal point position of the CP2 current
display. Do not change. |
EE 106 06A 460 UDISPMUL. AC voltage factor of the CP2 display.
Set equal to the AC rated voltage.
EE 107 068 1000 UDISPDIV. The AC voltage divider of the CP2
display. Do not change.
EE 108 06C UDISPPNT. Decimal point psoition of the AC
voltage of the CP2 display. Do not change. Setting
same as 102EE.
Page 7-8
Bulletin 1352 System
7-1.5
(cont.)
Type D H H.lim. Low lim. Init Explanation
EE 109 06D 1 DSPMUL. A factor of the FAULT display. The
quantity multiplied by 109EE and divided by 110EE
appears on the display. Decimal point position
determined by 111EE.
EE 110 06E DSPDIV. FAULT display divider of the CP2 display.
Do not change.
EE 111 06F DSPPNT. The decimal point position of the FAULT
display. Setting same as 102EE.
7.1.6
Serial Communications
Channel 1
Type D H H.lim. Low lim. Init Explanation
112 070 REQUESTMSGE. PLC or control panel sends the
address of requested data here.
113 071 ANSWERMSGE. Data requested in (112) transferred
to this address for transmission.
EE 114 072 19 IVALO. The interval in which the parameter
determined by 115EE issent. Step = 32ms. A
transmission of one message takes up 20ms.
EE 115 073 247 IX0. The address of the value that should be
transmitted with the interval determined by 114EE.
EE 116 074 20 IVAL1. Transmission interval. As 114EE.
EE 117 075 214 IX1. The value to be sent. As 115EE.
EE 118 076 21 IVAL2. Transmission interval. As 114EE.
EE 119 077 210 IX2. The value to be sent. As 115EE.
EE 120 078 23 IVAL3. Transmission interval. As 114EE.
EE 121 079 211 IX3. The value to be sent. As 115EE.
EE 122 07A | 25 IVAL4. Transmission interval. As 114EE.
EE 123 078 201 IX4. The value to be sent. As 115EE.
EE 124 07C 27 IVALS. Transmission interval. As 114EE.
EE 125 07D 202 IX5. The value to be sent. As 115EE.
EE 126 07E IVALO. Transmission interval. As 114EE.
EE 127 07F IX6. The value to be sent. As 115EE.
EE 128 080 IVAL7. Transmission interval. As 114EE.
EE 129 081 ` IX7. The value to be sent. As 115EE.
Page 7-9
Bulletin 1352 System
Serial Communications
Channel 2
Type D H Init Explanation
EE 130 082 10 NORMALMSGE. The transmission interval of the
CP2 normal display message with 128ms. step.
EE 131 083 100 DIAGNMSGE. The transmission interval of the CP2
fault display message with 128ms. step.
EE 134 086 19 IVALO2. The same as 114EE for channel 2.
EE 135 087 247 1X02. The same as 115EE for channel 2.
EE 136 088 20 IVAL12. The same as 114EE for channel 2.
EE 137 089 210 IX12. The same as 115EE for channel 2.
EE 138 08A 21 IVAL22. The same as 114EE for channel 2.
EE 139 088 211 1X22. The same as 115EE for channel 2.
EE 140 08C IVAL32. The same as 114EE for channel 2.
EE 141 08D 1X32. The same as 115EE for channel 2.
EE 142 08E IVAL42. The same as 114EE for channel 2.
EE 143 08F 1X42. The same as 115EE for channel 2.
EE 144 090 IVAL52. The same as 114EE for channel 2.
EE 145 091 IX52. The same as 115EE for channel 2.
EE 146 092 IVAL62. The same as 114EE for channel 2.
EE 147 093 IX62. The same as 115EE for channel 2.
EE 148 094 IXS62. The same as above except that the memory
cell content defined by 147EE is moved using the
address given here.
EE 149 095 IVAL72. Same as 146EE.
EE 150 096 IX72. Same as 147EE
EE 151 097 IXS72. Same as 148EE.
Page 7-10
Bulletin 1352 System
7-1.8
Parameters 2 of the LGU
Type D H H.lim. Low lim. Init Explanation
EE 153 099 1040 770 900 UCMIN. The low limit of DC voltage reference
values 26EE, (240) and (218). Values less than 153EE
are not stored to these memory locations. 1000
corresponds to rated voltage.
EE 154 09A 1300 1060 1200 UCMAX. The high limit for DC voltage reference
values 26EE, (240) and (218). Values greater than
154EE are not stored to these memory locations.
1000 corresponds to rated voltage.
EE 155 098 1 10 UCSTEP. Max. change of integration time of
Integrator between (240) and (218) in 4ms steps.
1000 corresponds to rated voltage.
EE 156 09C — 1000 — 500 IQMIN. The low limit for 27EE and (219) reactive
current reference values. A value less than 156EE is
not stored to these memory cells. 1000 corresponds
to rated current. 156EE has to be < 157EE if both
values are not set =0.
EE 157 09D 1000 500 IQMAX. The high limit for 27EE and (219) reactive
current reference values. A value greater than
157EE is not stored to these memory cells. 1000
corresponds to the rated current. 157EE has to be =
156EE if both values are not set = 0.
EE 158 OYE 1 25 IQSTEP. Max. change of integration time of
integrator between 27EE and (219) in 4ms steps.
1000 corresponds to rated current.
EE 160 ОАО 1 UCREFMODE. If UCREFMODE = 0, the sum of the
contents of addresses (244) and (203) is set as (240)
reference value. If UCREFMODE = 0, not
significant.
EE 161 OA 1 1 QUCMODE. !f QUCMODE = 0, (218) reference value
changed if needed so that the reactive current can
be controlled. If QUCMODE = 0, it does not affect
(218).
EE 162 0A2 | 0 PUCMODE. If PUCMODE = 0, 93EE is moved to the
(244) location. If PUCMODE =0, (244) value is
calculated by using 272EE to 281EE content. Used
only when LGUs are connected in parallel otherwise
=0.
EE 164 0A4 MASTERSLAVE. The mode of operation of the LGU
serial communications channel 2.
0 = normal mode,
2 = debugger
Page 7-11
Bulletin 1352 System
Type
D
H
7-1.8
(cont.)
H.lim. Low lim. Init
Explanation
EE
EE
165
166
0A5
0A6
44000
52000
FNETMIN. The minimum value of the AC network
frequency. Values less than 165EE are not stored in
(204) location. 40000 scaling corresponds to 50Hz
(48000 = 60 Hz.).
FNETMAX. The maximum value of the AC network
frequency. Values greater than 166EE are not
stored in (204) location. 40000 scaling corresponds
to 50 Hz. (48000 = 60 Hz ).
EE
167
168
0A7
0A8
FNETSTEP. The maximum rate of change of 204
identified AC network frequency. The scaling factor
is Hz/sec. If 167EE = 0 or the network voltage does
not exist, the identification is OFF and (204) is set
the same as 86EE.
COMMUNICATIONTYPE
0 = No Acknowledgement
1 = Acknowledge Channel 1
2 = Acknowledge Channel 2
3 = Acknowledge both channels
EE
EE
169
170
0A9
0AA
65535 0
4800
COMM_TIMEOUT2. Monitoring of the serial data
communications channel 2. Time elapsed from the
previous acknowledged message before itis
considered as a communication break. The actions
are determined by 171EE. If the value = 0, the
channel 2 is not monitored. A unit = 16ms.
CH2_BAUDRATE. The Baud Rate of the serial data
communications channel 2. Do not change.
EE
171
OAB
SELMACONT. Operation inthe case of a break in
data communication:
0
1
2
no interference,
activated on the board and by means of (211),
as point 1, butin addition to that LGU
stopped.
# WM
Any other values have the same meaning as 2.
EE
172
0AC
65535 0
COMM_TIMEOUT. Monitoring of the serial data
communications channel 1. Otherwise the same as
169EE.
EE
173
0AD
USEIOWORD. When USEIOWORD =0, the digital
inputs are used for LGU control. When =0, no
digital inputs.
EE
174
ОАЕ
USEIOSTART. When USEIOSTART #0, the inputs are
used for LGU start-up, shut-down and fault
acknowledgement. 173EE should be set = 0 as well.
EE
175
OAF
USEIOCONT. When USEIOCONT +0, the digital
inputs are used to provide the main contactor status
data. 173EE should be set #0 as well.
Page 7-12
Bulletin 1352 System
7-1.9
Diagnostics
Type D H H.lim. Init Explanation
M 176 OBO FLT QUEUE. Fault buffer. The first fault number.
For fault numbers see (210) and (211).
M 177 0B1 Prior first fault/reset number before (176)
M 178 0B2 Prior first fault/reset number before (177)
M 179 083 Prior first fault/reset number before (178)
M 180 0B4 Prior first fault/reset number before (179)
M 181 0B5 Prior first fault/reset number before (180)
182 086 OKMSGES1. Number of acknowledged messages
from channel 1 received by diagnostics. The
number is incremented by 1 on every received
message.
183 0B7 FAULTMSGES1. The number of abandoned
messages in channel 1. The number should be = 0. |
If the number increases constantly, there is a fault
inthe channel 1 communications.
184 0B8 OKMSGES2. The same as (182) for channel 2.
185 0B9 FAULTMSGES2. The same as (183) for channel 2.
EE 186 OBA DATREFADDR. A reference voltage code address
for the D/A converter of channel 1.
EE 187 088 231 DA1ADDR. The address of the quantity monitored
by the D/A converter of channel 1.
EE 188 OBC 8 DATSCALE. A scaling factor of the quantity
| monitored by the D/A converter of channel 1.
EE 189 08D 1 DATMODE. Mode of operation of D/A 1.
EE 190 OBE 1000 CURRENTOFFSET. The current measurement
reference point error in 0.01% of the fundamental
current. If an error is greater than 190EE, the LGU
does not start-up and sends out a current
measurement error message.
NOTE: A current transducer test is performed only
once immediately after current is switched on.
EE 191 OBF 218 TREND1. The address of a monitored variable in
trend buffer 1.
EE 192 OCO 219 TREND2. The address of a monitored variable in
trend buffer 2.
EE 193 OC1 221 TREND3. Trend 3 address.
EE 194 0C2 222 TREND4. Trend 4 address.
EE 195 0C3 223 TRENDS. Trend 5 address.
Page 7-13
Bulletin 1352 System
7-1.9
(cont.)
Type D H H.lim. Low lim. Init Explanation
EE 196 0C4 TRENDIVAL. Trend buffers sampling interval, time
| unit = 3ms.
EE 197 0C5 — 1 TRENDTRIG. Trend triggering condition:
— 1 = no condition, fault trigger only
> 1 = triggering takes place when the difference
between two successive values in 191EE 1 is greater
than 197EE.
198 0C6 TRENDREQ.
199 0C7 TRENDSAVE. Trend save to the scanning buffers. If
set = 0 causes triggering and trend saving. Reset to
0 takes place automatically.
200 0c8 TRIGCOUNT. Counter stores the number of
triggerings.
7-1.10
Actual Values
Type D H H.lim. Low lim. Init Explanation
201 Oca UCACTDISP. A filtered DC voltage actual value for a
panel display. 1000 corresponds to rated DC
voltage.
202 OCA IACTDISP. A filtered AC current effective value for a
panel display. 1000 corresponds to rated value.
203 — OCB UACTDISP. A filtered AC voltage actual value for a
panel display. The value is also used as AC network
voltage value in the calculation of (238), (239) and
(240). 1000 corresponds to rated voltage.
204 0CC FNETWORK. The AC network measured frequency.
The scaling factor 40000 corresponds to 50 Hz
frequency (48000 = 60 Нг.).
Page 7-14
Bulletin 1352 System
7-1.11
Logic data provided by
the LGU
Type D H H.lim. Low lim. — Init Explanation
M 210 0D2 FAULTWORDO. A packed fault logic word
represents the number of the fault in (176) and on
the CP1 display:
No. Bit
1 0= chopper undervolt.
2 1= chopper overvolt.
3 2= auxil. volt. fault
4 3= overheating
5 4 = overioad
6 5= Uc overvoltage
7 6= Uc undervoltage
9 8 = 1U fault
10 9= 2U fault
11 10= 1V fault
12 11= 2V fault
13 12= 1W fault
14 13= 2W fault
M 211 0D3 FAULTWORD1. A packed fault logic word:
No. Bit
19 0= current measurement fault
21 = matching card fault
22 = processor fault
15 4= AC short or ground fault
40 5= Unbalanced AC current
41 6 Start too long
42 7 = No Startup sector available
25 8 = Programmable fault
26 9= Programmable fault
43 10= No Digital Input available
44 11= No AC Line voltage
17 12= communication fault
17 13= communication fault
20 14=
18 15=
Page 7-15
Bulletin 1352 System
7-1.11
(cont.)
Type D H H.lim. Low lim. Init Explanation
M 212 0D4 FAULTWORD2. A packed fault logic word:
No. Bit
50 0 = new EEPROM
51 1= writing to EEPROM
52 2= cannot write to EEPROM
53 3= parameter out of limits
55 4 = wrong parameter number
57 5= low AC voltage
59 6= system restart
58 7= start disabled
80 8= RAR - Overcurrrent
81 9= DAR - Overcurrent
82 10= RAR - DC Overvoltage
83 11= DAR - DC Overvoltage
12=
56 13= no battery backup
84 14= RAR - DC Undervoltage
85 15= DAR - DC Undervoltage
213 0D% IOWORD. Digital inputs and outputs of the CP2.
LGU sets bits (CP2 output):
Bit Output No.
12 0= run
13 1= ready
14 2= fault
| 15 3= locking of the contactor
214 0D6 SAMISTATUS. LGUstatus data:
Bit
0= run
1= ready
2= fault
3= Locking of the main contactor
7-1.12
Debugger
Type D H H.lim. Low lim. Init Explanation
216 0D8 MEMADDR. Debugging address. Only allowed to
be used by software professionals.
(4096 + 2* address).
217 0D9 MEMDATA. Debugging data. As above.
Page 7-16
Bulletin 1352 System
7-1.13
Test Points
Type D H H.lim. Low lim. Init Explanation
218 ODA UCREF. Internal DC voltage reference value to the
DC voltage controller. 1000 corresponds to rated
voltage.
219 ODB IQREF. Internal reactive current reference value to
the reactive current controller. 1000 corresponds to
rated value.
220 ODC FREF. Frequency reference value to the modulator.
40000 corresponds to 50 Hz. (48000 = 60 Hz).
221 ODD UREF. À voltage developed by the modulator .8000
corresponds to rated AC voltage.
NOTE: The LGU output voltage is proportional to
(221) and the instantaneous DC voltage from the
INU's.
222 ODE DUREF. The reactive current controller output or
54EE if the reactive current control is disabled.
Absolute value can be less if reactive current has to
be limited. 8000 corresponds to rated AC network
voltage.
223 ODF UACT. AC network voltage effective value. 1000
corresponds to rated value.
224 0EO UCACT. DCvoltage actual value. 1000 corresponds
to rated voltage.
225 ОЕ! UACTM. The AC network unfiltered voltage value.
1000 corresponds to rated voltage.
226 QE2 ANGLE. Phase angle of the modulator.
227 OE3 IREC. The effective value of the active current.
1000 corresponds to rated value.
228 0E4 IMC. The effective value of the reactive current.
1000 corresponds to rated value.
229 0E5 IU. Measured U phase current.
230 OE6 IV. Measured V phase current.
231 ОЕ7 IRE. The effective value of the unfiltered active
current. 1000 corresponds to rated value.
232 (QE8 HM. The effective value of the unfiltered reactive
current. 1000 corresponds to rated value.
233 0&9 UUV. UV measured phase to phase voltage.
234 0EA UWV. WV measured phase to phase voltage.
235 0EB IREFF. (227) with additional filtering. Scaling factor
is the same.
236 =— OEC DUREFF. (222) with additional filtering. Scaling
factor is the same.
Page 7-17
Bulletin 1352 System
Type
D
7-1.13
(cont.)
H H.lim. Low lim. Init
Explanation
237
OED
DIREC. The AC network vector direction of
rotation. Direction is set when the LGU is not
running. UVW phase arrangement =0, UWV phase
arrangement z 0.
238
OEE
UCDBMSTART. The LGU is modulated when the DC
voltage is above this limit in the diode bridge mode
of operation. 1000 corresponds to rated value.
239
OEF
DUCDBMSTART. The LGU is modulated when the
DC voltage ts above this limit and the voltage is over
95EE during 4ms period. The LGU calculates it as
the sum of (203) and 94EE. 1000 corresponds to
rated DC voltage.
240
OFO
UCREFH. DC voltage reference value. The LGU
calculates it as the sum of the (203) and (244) or
substitutes 26EE depending on the values of 90EE
and 160EE. 1000 corresponds to rated DC voltage.
EE
241
OF 1 224
TREND6. Trend 6 address. See 19EE.
EE
242
OF2 225
TREND7. Trend 7 address.
EE
243
OF3 226
TREND8. Trend 8 address.
244
OF4
UCREFOFFSET. Offset value for 240EE calculation.
The LGU moves 93EE to this location or calculates it
using 272EE to 281EE and (227) memory contents.
Page 7-18
Bulletin 1352 System
7-1.14
The Memory Area Reserved
for the 1/0 of SAFT 163 10C
Type D H H.lim. Low lim. Init Explanation
245 OF5 DIG_INPUTS. The packed bit information about the
state of the digital inputs.
246 OF6 ANAINO. Analog input data.
247 OF7 DIGITAL_OUTPUTS. The Control Word of the
digital outputs.
248 OF8 ANAQUTO. The Control Word of the analog output
0.
249 OF9 ANAOUT1. The Control Word of the analog output
1.
250 OFA ANAINT. Input 1 of the analog fiber optic board.
251 OFB ANAIN2. Input 2 of the analog fiber optic board.
EE 252 OFC DA2REFADDR. Same as 186EE but for channel 2 D/A
converter.
EE 253 OFD 232 DA2ADDR. Same as 187EE but for channel 2.
EE 254 OFE 8 DA2SCALE. Same as 188EE but for channel 2.
EE 255 OFF 1 DA2MODE. Same as 189EE but for channel 2.
7-1.15
Parameters 3 of the LGU
Type D H H.lim. Low lim. — Init Explanation
266 10A HWFAULTS1. Incremented by 1 when a HW fault
(parity, overrun) is observed in the serial data
communications channel 1.
267 10B HWFAULTS2. Same as (266) but for channel 2.
268 10C BCCERRORS1. Incremented by 1 when a
CHECKSUM error is observed in the data
communications channel 1.
269 10D BCCERRORS2. Same as (268) but for channel 2.
Page 7-19
Bulletin 1352 System
7-1.15
(cont.)
Type D H H.lim. Lowlim. Init Explanation
270 10E FORMATERRORS1. Incremented by 1 when an
unspecified character is observed in data
communications channel 1.
271 10F FORMATERRORS2. Same as (270) but for channel 2.
EE 272 110 — 1500 IREC1. Parameter of the function generator. When
162EE is = 0 parameters are in use. The function
output data is transferred to (244).
EE 273 111 110 UCREFOFF1. Output value corresponding to the
contents of 272EE.
EE 274 112 — 850 IREC2. Same as 272EE.
EE 275 113 71 UCREFOFF2. Same as 273EE.
EE 276 114 — 500 IREC3. Same as 272EE.
EE 277 115 50 UCREFOFF3. Same as 273EE.
EE 278 116 500. IREC4. Same as 272EE.
EE 279 117 10 UCREFOFF4. Same as 273EE.
EE 280 118 850 IRECS. Same as 272EE.
EE 281 119 -11 UCREFOFFS. Same as 273EE.
EE 282 11A 15 IREC6. Same as 272EE.
EE 283 118 10 UCREFOFF6. Same as 273EE.
284 11C -50 UCREFBIAS. The contents of memory location (284)
is added to the function generator output data.
293 125 DA1CHANNEL. The data to be transmitted to
channel 1 of the D/A converter can be observed at
this memory location.
294 126 DA2CHANNEL. The data to be transmitted to
channel 2 of the D/A converter can be observed at
this memory location.
Page 7-20
Bulletin 1352 System
7-1.15
(cont.)
Type D H H.lim. Low lim. Init Explanation
296 128 UCUCONT. Adjustment control of UCUSCAL 81EE.*
0 = no adjustment
1 = adjustment is ON
>1 = Error; thekind of error is clarified in the
following bits:
by =0 reactive current regulation is OFF
by=0 reactive current reference value is not = 0,
b3=0 reactive current controller output is
limited
ba=0 modulator is at the high limit state
bs=0 stop routine has been executed
297 129 IOFFCONT. 298EE and 299EE adjustment control.
When IOFFCONT = 0, the adjustment is functioning.
The zero reset takes place automatically after the
adjustment.
EE 298 12A 16460 IUOFFSET. The U phase current measurement
offset.*
EE 299 128 16460 IVOFFSET. The V phase current measurement
offset.* |
303 12F SAMIDATA. The latest received data from the serial
data communications channel 1 which has proper
format.
304 130 SAMIADDR. The address of the above.
305 131 SAMIDATA1. The latest received, checked and
accepted data from the serial data communications
channel 1.
306 132 SAMIADDR1. The address of the above.
307 133 SAMIDATA?. Same as (303) but for channel 2.
308 134 SAMIADDR2. Same as (304) but for channel 2.
309 135 SAMIADDR3. Same as (305) but for channel 2.
310 136 SAMIADDR3. Same as (306) but for channel 2.
* Section 2-12.1
Page 7-21
Bulletin 1352 System
7-1.15
(cont.)
Type D H H.lim. Low lim. Init Explanation
320 140 TREND_FETCH. All 100 samples of trend 1 are
sequentially transferred to this memory location.
The trend can be analyzed by means of the D/A
converter.
321 141 TREND2_FETCH. Same as (320) but for trend 2.
322 142 TREND3_ FETCH. 3 trend.
323 143 TREND4 FETCH. 4 trend.
324 144 TRENDS_FETCH. 5 trend.
325 145 TREND6_FETCH. 6 trend.
326 146 TREND7 FETCH. 7 trend.
327 147 TREND8 FETCH. 8 trend.
7-1.16
Type D H H.lim. Low lim. Init Explanation
330 14A 40 DEVICETYPE. Drive type:
10 = DC
20 = vector control
30 = scalar contro!
40 = LGU
331 14B 304 REVISION. Version number. 204 corresponds to
version 3.04.
332 14C 5601 EPROM - low storage code
333 14D 7861 for D17 circuit.
334 14E 5601 EPROM - high storage code
335 14F 7518 for D18 circuit.
336 150 0 0 PARACOUNT
339 153 EEPROMCOUNT. Incremented by 1 when
parameter is written to the EEPROM.
Page 7-22
Bulletin 1352 System
7-1.17
Type D H H.lim. Low lim. init Explanation
340 154 UVWDIR. At start-up the LGU stores to this location
the direction of network vector rotation. The value
isthe same as (237).
341 155 STARTSECT. At start-up the LGU stores to this
location the start-up sector number.
342 156 STARTMODE. At start-up the LGU stores to this
location the start-up mode type.
EE 343 157 0 VSECTO. Start-up permission for the start-ups in
sector 0 when phase direction is UVW (i.e. when
(340) = 0).
0 = no permission
1= mode 1 permission
2= mode 2 permission
3= modes 1 and 2 permission
EE 344 158 142 VOFFS01. The start-up fine adjustment parameter
for mode 1 when operating in sector 0 and with the
UVW AC network rotation.
EE 345 159 147 VOFFS02. Same as 344EE but for mode 2.
EE 346 15A 0 VSECT1. Same as 343EE but for sector 1.
EE 347 15B 273 VOFFS11. Same as 344EE but for sector 1.
EE 348 15C 271 VOFFS12. Same as 345EE but for sector 1.
EE 349 15D 0 VSECT2. For sector 2.
EE 350 15E 406 VOFFS21. For sector 2.
EE 351 15F 401 VOFFS22. For sector 2.
EE 352 160 0 VSECT3. For sector 3.
EE 353 161 654 VOFFS31. For sector 3.
EE 354 162 659 VOFFS32. For sector 3.
EE 355 163 0 VSECTA4. For sector 4.
EE 356 164 785 VOFFS41. For sector 4.
EE 357 165 783 VOFFS42. For sector 4.
EE 358 166 0 VSECTS. For sector 5.
EE 359 167 918 VOFFS51. For sector 5.
EE 360 168 913 VOFFS52. For sector 5.
EE 361 169 0 MSECTO. Same as 343EE but for the UWV AC
network voltage phase rotation. (i.e. (340) = 0).
For sector 0.
Page 7-23
Bulletin 1352 System
Type D H Init Explanation
EE 362 16A 360 MOFFSO1. Same as 344EE but for the UWV AC
network voltage phase rotation. (i.e. (340) +0).
For sector 0.
EE 363 16B 364 MOFFS02. Same as 345EE but for UWV AC network
voltage phase rotation. For sector 0.
EE 364 16C 0 MSECT1. For sector 1.
EE 365 16D 615 MOFFS11. For sector 1.
EE 366 16E 611 MOFFS12. For sector 1.
EE 367 16F 0 MSECT2. For sector 2.
EE 368 170 747 MOFFS21. For sector 2.
EE 369 171 744 MOFFS22. For sector 2.
EE 370 172 0 MSECT3. For sector 3.
EE 371 173 872 MOFFS31. For sector 3.
EE 372 174 876 MOFFS32. For sector 3.
EF 373 175 0 MSECT4. For sector 4.
EE 374 176 103 MOFFS41. For sector 4.
EE 375 177 99 MOFFS42. For sector 4.
EE 376 178 0 MSECTS. For sector 5.
EE 377 179 235 MOFFS51. For sector 5.
EE 378 17A 232 MOFFS52. For sector 5.
444 1BC DA3CHANNEL. The data transmitted to channel 3
of the D/A converter can be observed at this
memory location.
445 1BD DA4CHANNEL. The data transmitted to channel 4
of the D/A converter can be observed at this
memory location.
Page 7-24
Bulletin 1352 System
Type D H
7-1.18
H.iim.
Low lim.
Init
Explanation
EE 451 1C3
D_SEL. D/A converter selection. When D_SEL = 0
channels 1 and 2 of the previously selected D/A are
in operation. The later selected D/A converter has
only channel 1. When D_SEL = 0 the previously
selected converter is not in operation and the later
has 4 operating channels.
EE 452 1C$
DA3REFADDR. Same as 186EE but for channel 3.
EE 453 105
DA3ADDR. Same as 187EE but for channel 3.
EE 454 1C6
DA3SCALE. Same as 188EE but for channel 3.
EE 455 107
DA3MODE. Same as 189EE but for channel 3.
EE 456 1C8
DA4REFADDR. Same as 186EE but for channel 4.
EE 457 1C9
DAJADDR. Same as 187EE but for channel 4.
EE 458 1CA
DA4SCALE. Same as 188EE but for channel 4.
EE 459 1CB
DA4MODE. Same as 189EE but for channel 4.
Page 7-25
Bulletin 1352 System
Trend Scanning Buffers
Type D H Explanation
M 500 1F4 Trend 1 scanning buffer. When a trend triggering
occurs, the program transfers samples from the
data acquisition buffer to the scanning buffer
where they can be observed. The (500) to (599)
area is used as the scanning buffer of trend 1. The
capacity of the buffer is 100 samples.
M 600 258 Trend 2 scanning buffer.
M 699 2BB
M 700 2BC Trend 3 scanning buffer.
M 799 31F
M 800 320 Trend 4 scanning buffer.
M 899 1383
M 900 384 Trend 5 scanning buffer.
M 999 ЗЕ7
M 1000 3ES8 Trend 6 scanning buffer.
M 1099 a46
M 1100 447 Trend 7 scanning buffer.
М 1199 4AF
M 1200 aB0 Trend 8 scanning buffer.
Page 7-26
Bulletin 1352 System
7-2
NUMBER SYSTEMS
7-2.1
7-2.2
7-2.3
Decimal System - The numbers familiar for a long time are based on the
supposition that the number of available symbols is the same as the number of
fingers on the human hands i.e. 10. This is the concept of decimal number
representation. The available ordered set of digits in the decimal system is:
0123456789
The decimal representation allows us to create unlimited numbers by using
juxtapositional notation. À number magnitude is defined by polynomial
notation in the base 10. Base or radix of the decimal system representation is
10. The number 583 in the decimal system is:
5*102 + 8*10! + 3*100 = 583
If a number has a fractional portion, digits after a decimal point are powers
with negative exponents of the system base 10. E.g. number 437.25 can be
represented in the following polynomial notation:
4*102 + 3*10! + 7*100 + 2*10-1 + 5*10-2 = 437.95
Binary and Hexadecimal Number System - The binary system uses only
digits 0 and 1 for number representation. The base of the binary system is 2
and numerical value are defined by a polynomial of powers of 2. Binary
numbers in written form are notedby a capital letter B at the end of the
number. E.g. binary number 1001B in decimal system is represented as
follows:
1*23 + 0*22 + 0*21 + 1#20 = 9
Every symbol of the binary number is called a bit. The total number of bits in
a binary number is unlimited. In practice binary numbers have 8, 16 or 32
bits (most computers use one of these lengths as a machine word).
Hexadecimal system has a base of 16. Sixteen different symbols are available
for number representation:
0123456789ABCDEF
The capital letters À to F of the English alphabet corresponds to the decimal
numbers 10 to 15. The decimal value is determined as a polynomial of powers
of 16. Hexadecimal numbers in written form are noted by a capital letter H at
the end of thenumber . Hexadecimal number 4A2CH in decimal notation is:
4*163 + 10*162 + 2*161 + 12*160 = 18988.
Conversion from one Number System to Another - Decimal numbers are
normally used in number representation. Microcomputers almost without
exception are based on using hexadecimal numbers. Decimal numbers should
be converted into binary for use in digital electronic circuits. Digital
electronic circuits used in microcomputers can distinguish between onl y two
different stable states which are presented below depending on the
application:
0 or 1
OV or 5V
false or true
reset or set
Page 7-27
Bulletin 1352 System
The natural form of number representation in computer systems is the binary
system. The hexadecimal system has a close connection with the binary
system.
Numbers 12 and 7640 are presented below in the different number systems:
System
Decimal 12 7640
Binary 1100B 1110111011000B
Hexadecimal CH 1DD8H
The most compact way of number representation is the hexadecimal system.
Conversion from binary and hexadecimal systems to the decimal system is
made by adding the powers of the system base as was presented above. A
conversion from the decimal system to one of the other systems is more
cumbersome. In order to convert a number to the desired system it should be.
divided by the base of that system until the quotient is 0. The results of
conversion are partial remainders. E.g. 25 is converted to the binary form as
follows:
Integer Remainder
25 + 2 12 1
12 + 2 6 0
6 + 2 3 0
3 +2 1 1
1 +2 0 1
Result of conversion is 11001B by reading up the list of remainders
Correspondingly conversion from decimal system to hexadecimal is made by
successive division by 16 and writing down partial remainders. The example
of converting number 826 to the hexadecimal form is given below:
Integer Remainder
826 — 16 51 10=A
51 — 16 3 3
3-16 0 3
Result of conversion is 33AH
A conversion from hexadecimal to binary representation is needed more often.
This kind of conversion is easily performed so that each digit of hexadecimal
number can be converted to the binary form and thus a binary juxtapositional
notation 1s made. The opposite conversion is made by breaking up a binary
representation into tetrades (groups of four); convert each tetrade into
hexadecimal form with juxtapositional notation.
Page 7-28
Bulletin 1352 System
7-2.4
Table 7-2. System-To-System Conversion Equivalents:
Binary Hexadecimal Decimal
0000 0 0
0001 1 1
0010 2 2
0011 3 3
0100 4 4
0101 5 5
0110 6 6
0111 7 7
1000 8 8
1001 9 9
1010 A 10
1011 B 11
1100 C 12
1101 D 13
1110 E 14
1111 F 15
The example of converting number 5A7CH to the binary form is given below:
5A7CH 5 A 7 C
0101 1010 0111 1100
0101101001111100B
Negative Numbers - A negative number in the decimal system is obtained
by placing a minus sign in front of the notation. Computer logic recognizes
only binary representation (zero and one) and does not recognize a minus sign.
A negative number is coded by using the same zero and one representation.
The method of negative number representation is so-called two's complement
representation. A negative number always has 1 in the most significant bit
(the leftmost bit), and a positive number always has a zero in the most
significant bit.
A negative number is obtained by inverting all bits and adding one unit to the
inverted number. E.g. 00000101B (=5) is converted to the negative number
as follows:
00000101B - Binary number to be converted
11111010 - Inverse of each bit
+1 - addition of one
11111011B - the negative equivalent (= —5)
Page 7-29
Bulletin 1352 System
7-2.5
Use of Hexadecimal (binary) Numbers - In most cases, a computer
processes 8 or 16 bit long machine words. Even though 1 or 2 bits are
sufficient for data processing, numbers should be expanded to 8 or 16 bit long
words. The value of the number is not changed when extra zeroes (positive
numbers) or ones (negative numbers) are filled in at the left of the data bit
binary places.
Parameter table locations are 16 bits long. This means that a 16 bit word in
binary representation can be saved in the memory. The largest decimal
number is 32767 and the smallest negative number is — 32768. Examples of
numbers suitable for the Parameter Table presented in the different systems
are given in the table below:
Decimal Hexadecimal Binary
+ 32767 7FFF 0111111111111111
— 32768 8000 1000000000000000
0 0000 0000000000000000
+ 3 0003 0000000000000011
+ 16 0010 0000000000010000
— 3 FFFD 1111111111111101
— 16 FFF0 1111111111110000
When an inverter or LGU shuts down due to a fault, the display panel (CP1 or
CP2) will exhibit the first fault even though subsequent faults occur. It is
advisable to analyze the fault words (210, 211 & 212) for other faults. The
following is an example using Faultwordl 211.
Assume for this example the contents of address 211 in decimal form as 20 or
in hexadecimal as 14H. The number should then be converted to binary form:
Decimal Hexadecimal
Integer Remainder
20+ 2 10 0 14H
10-2 5 0 0001 0100
5+2 2 1 00010100B
2-2 1 0 or in 16 bit notation
1-2 0 1 0000000000010100B
10100B
or in 16 bit notation or in 16 bit notation
0000000000010100B 0000000000010100B
This binary number shows that bits by and b4 are 1. Looking at the parameter
table shows that bits by and b4 indicate the faults were processor fault (22)
and programmable fault (25, motor overload).
Page 7-30
Bulletin 1352 System
7-3
PARAMETER VALUES
AFTER START-UP
Type D H Init Name Value
EE 26 01A 1071 UCREFG
EE 27 O1B 0 IQREFG
EE 28 O1C 850 KQ
EE 29 O1D 900 KI
EE 48 030 -1 IQCONT
EE 54 036 0 DUSET
EE 65 041 320 LLGU
EE 66 042 1540 CLGU
EE 67 043 460 ULGU
EE 68 044 577 ILGU
EE 82 052 0 DUREFO
EE 83 053 1799 UCMSCAL
EE 84 054 39272 UMSCAL
EE 86 056 48000 FNET
EE 87 057 625 RARMAXTIME
EE 88 058 3125 RARMAXCOUNT
EE 89 059 1 DARMAXCOUNT
EE 90 ОБА 0 DBMODE
Page 7-31
Bulletin 1352 System
Type D H Init Name Value
EE 100 064 620 UCDISPMUL
EE 103 067 577 IDISPMUL
EE 106 06A 460 UDISPMUL
EE 160 ОА0 1 UCREFMODE
EE 161 0A1 1 QUCMODE
EE 162 0A2 0 PUCMODE
EE 173 0AD 0 USEIOWORD
EE 174 OAE 0 USEIOSTART
EE 175 OAF 0 USEIOCONT
EE 191 OBF 218 TREND1
EE 192 OCO 219 TREND2
EE 193 OC! 221 TREND3
EE 194 0C2 222 TRENDS
EE 195 0C3 223 TRENDS
EE 197 0C5 -1 TRENDTRIG
EE 241 OF1 224 TREND6
EE 242 0F2 225 TREND7
EE 243 ОРЗ 226 TRENDS
EE 343 157 0 VSECTO
EE 344 . 158 142 VOFFSO1
Page 7-32
Bulletin 1352 System
Type D H init Name Value
EE 345 159 147 VOFFSO2
EE 346 15A 0 VSECT1
EE 347 158 273 VOFFS11
EE 348 15C 271 VOFFS12
EE 349 15D 0 VSECT2
EE 350 15E 406 VOFFS21
EE 351 15F 401 VOFFS22
EE 352 160 0 VSECT3
EE 353 161 654 VOFFS31
EE 354 162 659 VOFFS32
EE 355 163 0 VSECT4
EE 356 164 785 VOFFS41
EE 357 165 783 VOFFS42
EE 358 166 0 VSECTS
EE 359 167 918 VOFFS51
EE 360 168 913 VOFFS52
EE 361 169 0 MSECTO
EE 362 16A 360 MOFFSO2
EE 303 168 364 MOFFSO2
EE 364 16C 0 MSECT1
Page 7-33
Bulletin 1352 System
Type D H Init Name Value
EE 365 16D 615 MOFFS11
EE 366 16€ 611 MOFFS12
3: 367 16F 0 MSECT2
EE 368 — 170 747 MOFFS21
EE 369 17 744 MOOFS22
3: 370 172 0 MSECT3
EE 371 173 872 MOFFS31
EE 372 174 876 MOFFS32
EE 373 175 0 MSECTA
EE 374 176 103 MOFFS41
EE 375 177 99 MOFFS42
EE 376 178 0 MSECTS
EE 377 179 235 MOFFSSI
EE 378 17A 232 MOFFS52
Page 7-34
Bulletin 1352 System
7-4
Rated Values
7-5
Rated DC Voltages & Currents
The rated current and voltage values for the available LGU units are listed
below. Rated current should be stored to the locations ILGU 68EE and
IDISPMUL 103EE. Rated AC voltage is stored in parameter ULGU 67EE and
UDISPMUL 106EE and rated DC voltage in UCDISPMUL 100EE.
Rated AC Rated AC Rated DC
Voltage Current Voltage
LGU ULGU67EE [LGUEBEE
UDISPMUL IDISPMUL UCDISPMUL
106EE 103EE 100EE
160 F 415 415 243 560
250 F 415 415 380 560
400 F 415 415 610 560
630 F 415 415 960 560
460 F 460 460 580 621
730 F 460 460 920 621
200 F 500 500 231 675
315 F 500 500 360 675
500 F 500 500 580 675
800 F 500 500 920 675
540 F 575 575 550 777
870 F 575 575 870 777
160 F 660 660 140 891
250 F 660 660 218 891
400 F 660 660 350 891
630 F 660 660 550 891
1000 F 660 660 870 891
7-6
DC Capacitors
The available DC capacitor banks and their capacitance in millifarads are
listed below. The appropriate number should be entered in parameter CLGU
66EE.
IMPORTANT: In the case of parallel connection of several capacitor units
the value set for the CLGU is the sum of all the values used from the table.
Capacitors of the LSU and LRU units are also to be taken into account. The
values of those units are also presented in the following list.
CBU Capacitance mF CLGU 66EE Value
40 F 415 3.30 - 330
63 F 415 4.95 495
100 F 415 6.60 — 660
160 F 415 9.90 990
250 F 415 13.20 1320
400 F 415 23.10 2310
630 F 415 36.30 3630
Page 7-35
Bulletin 1352 System
7-7
LFU's
50 F 500
80 F 500
125 F 500
200 F 500
315 F 500
500 F 500
800 F 500
160 F 660
250 F 660
400 F 660
630 F 660
1000 F 660
2.20
3.30
4.40
6.60
9.90
14.30
20.37
3.30
4.95
7.43
10.73
15.28
220
330
440
660
990
1430
2037
330
495
743
1073
1528
All available Line Filter Units (LFU) and their line choke inductances (uH)
are presented in the following list. The value is to be set in Parameter
location LLGU 65EE for the correct LFU used.
Unit
160 F 415
250 F 415
400 F 415
630 F 415
200 F 500
315 F 500
500 F 500
800 F 500
250 F 660
400 F 660
630 F 660
1000 F 660
[Inductance (UH) and LLGU 65EE
680
440
275
175
780
505
320
200
1110
695
440
280
РНР
TABLE OF CONTENTS
8. Glossa ry
8-1. Glossary 1
BULLETIN 1352 GLOSSARY
GLOSSARY
Analog
Angle, Phase
Asynchronous
Baud
Binary
Bit
Buffer
Byte
CBU
Chopper
Commutation
Constant, Time
Control Word
Converter, A/D
Converter, D/A
CTU
Current, Active
Current, Reactive
Current, Total
DAR
Default
Differential
Digital
Diode
A control system with continuously adjustable voltage or current signal
levels.
The difference between two sine waves measured by comparing the two zero
crossings.
Not synchronized or independently varying.
Rate of transmission of data. Used in serial communication to synchronize
the sender to the receiver.
À numbering system using the base 2, values can be 0 or 1.
One character of data consisting of Oor 1.
Storage location used for data to be transmitted.
A character or number consisting of 16 bits in the 1352 Drive.
Capacitor Bank Unit. A module consisting mainly of capacitors used to filter
and provide storage for the DC voltage.
A circuit that takes DC and converts it to pulsating DC. Used for controlling
the voltage level.
Switching the current from one phase to another.
Time required between repetitive operations used as a measure for the output
of an integrator tochange a certain amount.
The digital commands for control packed together into one 16 bit number
where each bit is analyzed separately.
Device that converts an analog signal to a digital number.
Device that converts a digital number into a current or voltage analog signals.
Contactor unit part of a 1352 Drive that provides control of the incoming line
and control voltage.
Portion of the output current that produces torque.
Portion of the output current that produces motor excitation.
Complete current produced consisting of active and reactive components.
Delayed Automatic Restart, feature of a line generating unit that allows the
unit to restart automatically.
Value provided for a parameter as a part of the program when the drive is
started initially.
An output signal that is proportional to the rate of change of the input.
À control system that uses two specific voltage or current signal levels.
A semiconductor that allows current to flow in only one direction.
Page 2
Bulletin 1352 Glossary
Diode, Freewheeling
DMS
DRC
EE
EEPROM
EPROM
False
Fault
Faultword
Firmware
Flag
Gain
GTO
GTR
Hardware
Hexadecimal
Initialization
Integral
INU
Inverter
IRE
LCU
LFU
LGU
Location, Memory
A name given to a diode when used toprovide an alternate path for current to
flow when another path is abruptly blocked.
Drive Maintenance System. A computer based program that allows analyzing
of the 1352 Drive for maintenance purposes.
Digital Reference Control. A master reference in digital form for controlling
several drives in unison.
An abbreviation that indicates a parameter can be stored in EEPROM (D186).
Electrically Erasable Programmable Read Only Memory. Memory that can
be changed with an electrical signal, but retains the data when power is
removed.
Erasable Programmable Read Only Memory. Memory that can only be
changed with ultraviolet light; permanent memory.
Term that refers to the state of a digital logic signal that is at 0 volts (off).
Malfunction that is monitored and displayed on the control panel.
A group of 16 digital bits each bit indicating a separate fault, packed together
as a unit for rapid transmitting.
The portion of the program that defines the relationship among the
parameters, not normally changed.
A digital bit that is used as an indicator that a function is active.
The coefficient of an amplifier that determines the multiplier for the input to
determine the output.
Gate Turn Off. Semiconductor that can allow current flow or block current
via a low level signal to its gate terminals.
Giant Transistor. A group of transistors packaged together and operating as
one unit.
That portion of a drive that is visible and can be touched.
Number system using the base 16, used extensively in computers and
microprocessors.
The act of resetting parameters to their starting value.
The portion of an amplifier that is proportional to the integral of the input and
determines the rate of change.
Abbreviation for an inverter unit, converts DC voltage to controlled AC
voltage.
Portion of a drive that converts DC voltage to AC voltage, sometimes used to
refer to the complete drive. -
Abbreviation that refers to the REAL current (active current).
Line Converter Unit. Unit that converts the AC line voltage to DC bus
voltage.
Line Filter Unit. Portion of a regenerative drive that contains the AC reactor.
Line Generating Unit. Portion of a Regenerative Drive that converts the
regenerative DC voltage to AC and returns it to the incoming power line.
A place where a value is stored to be used by the program. Parameter.
Page 3
Bulletin 1352 Glossary
Loop, Closed
LRU
LSU
Memory
Microprocessor
Modulator
Offset
Packed Word
Parallel
Parameter
PLC
Precharge
Program
Proportional
RAM
RAR
Rated
Reactor
Rectifier
Regulator
Reset
Ride-Through
ROM
Scalar
Scaling
Serial
À type of control that compares a reference signal to a feedback signal, and
gives an output proportional to.the magnitude and rate of change of their
difference.
Line Rectifier Unit. Combination of a line converter unit and a capacitor
bank unit in one module.
Line Supply Unit. Combination of a line rectifier unit and contactor unit in
one module.
Place where data and instructions are stored for use by the program.
À silicon chip that can be programmed to process data.
À device that is programmed to generate gate pulses to control the voltage and
frequency of the drive.
À constant difference that is set between the input and output of a function
block.
À digital number where each bit represents a logical (true or false) signal up
to 16 signals can be packed in one word.
A type of communications where several bits are sent at the same time.
Opposite of serial.
A memory address that is used to store data for use by the program.
Programmable Logic Controller. A microprocessor based device that controls
the operation of a machine.
Supplying a limited current to capacitors to give them an initial charge prior
to the full charge to reduce inrush current.
Series of insructions to the microprocessor.
Controlling one variable linearly with respect to another variable (constant
multiplier).
Random Access Memory. Memory locations that are most quickly addressed
and can be changed readily. Data is lost when power is removed.
Rapid Automatic Restart. A feature of the LGU that allows restarting
automatically after certain faults.
The normal design value for a unit. Nominal value.
A coil of wire sometimes wrapped around an iron core to limit the rate of
change of current. A choke or inductor.
A device that converts AC voltage to DC voltage.
A device that is used to control another variable. A controller.
A signal used to return a function to its initial state.
The feature where the control is kept operational during short power outages.
Read Only Memory. Memory locations that can not be changed, the values
can only be read.
A type of inverter control that controls the motor frequency to determine
speed without a tachometer.
Changing a variable to a number that is in units that relate to physical units.
A type of communication where data is sent one bit after another. Opposite of
parallel.
Page 4
Bulletin 1352 Glossary
Software
Synchronous
Thyristor
Transducer, Hall Effect
Trends
True
Uc
Value, Actual
Value, Filtered
Value, Average
Value, Initial
Value, Maximum
Value, Minimum
Value, Reference
Vector
That portion of the program that can be altered.
Controlling the timing of a device to match another exactly.
A solid state switch that can control a large amount of power from a signal on
its gate.
A device that is used to accurately measure AC current at low frequency.
Storage of various parameters that allows later retrieval and analysis. Often
used for fault analysis.
A logical expression to indicate that voltage is present.
An expression for the DC voltage level.
A feedback signal that is based on measurement rather than calculation. A
measured value.
A measured signal that has had fast transients removed.
A measured signal that has been changed to indicate the average over a time
interval. |
The value that the program assigns to a parameter upon starting. Default
value.
The maximum value allowed for a parameter.
The minimum value allowed for a parameter.
The number set into a parameter to indicate to the program the desired
output.
Type of control which uses feedback of the actual rotor/stator position to
calculate the voltage and current vectors, thereby permitting the accurate
control of speed and motor torque at all speeds even zero.
Page 9-5
Bulletin 1352C-5.3 Index
T
TBCTRANSMITI 9ÉE and TBCTRANSMIT2 10EE LL... Lea a anna aa 4-20
Terminals .................em0s0cererriooaa an o aeciaaoeeaaoaooaaoraerecoa ooo 6-2
Test Instruments and Tools .................... renedeeceaeneao oa aadecoroiar io 5-1
Test Points .................00.. 00000000 a ae a a ee a aa aa a Aa A a aa 7-16
Testing Methods 21022020 eee eee aa aa a aa a aa aa a aa aa a a aa AA 5-3
The Memory Area Reserved for the 1/0 of SAFT 163 10C .................. e rreroesiaa, 7-18
Transportation & Handling ...... rene aa aa A 2-1
Trend Content D/A Conversion ............ ea aaearaceseara 5-19
Trend Investigation in the NumericForm a a aacero ao, 5-20
Trend Scanning Buffers ...... a aa eee aa da RAA ненееаеоеенеоен 7-25
UC AN 5-18
U
UCREFMODE 160EE (DC VOLTS A FUNCTION OF ACVOLTS) ..........Ñ..0. o 4-12
Unpacking & Inspection .................... ana a aa aa a PS 2-1
Use of Hexadecimal (binary) Numbers .........12LL0L LL a ana aerea o 7-29
Use Of Trend... a eee ea ae aa a Aa ae a aa a a ad aa a A ore oaaocmda 5-18
VW
Page 9-1
Bulletin 1352C-5.3 Index
9.0 INDEX
Subject Page
A
AC Voltage Controller ................... eee eanorecac a ooo anreoerariae 4-9
Actual Values ................0....00000000r earn earecancec cocoa caceaeaeceriaaa 7-13
Automatic Restart Lo aaa anareonecerenenicieoicci, 4-2
Auxiliary Power Card .....................0 200 ereciaaa aaa areoaroredecaó, 3-23
B
Binary and Hexadecimal Number System... reee aedenerereriae 7-26
Bus Capacitors .....222 2000 4e eee see aa ae ae ea a aa a a ea aa aa a 6-2
Bus Connections LL. a aa a ae aa aa aaron enororoniocead ei 6-2
C
Capacitor Bank Unit (CBU) ...... aeoreara a recasrivor cra renamarmoreoenaroreosrarrarecoecoda 3-4
CBU Supervision Card ...............ee.ef00000 0 e ea a a 3-26
Changing Printed Circuit Boards .................. 2.2 aaa aaa LL 5-20
Checking and Replacement of Power Semiconductors .................................... 5-21
Choosing the Right Fault Tracing Instruction ...................2..00 00 LL 5-3
Circuit Board Replacement ........................ i 5-20
€] | RAA вк ооннн вн ена венка анка неко наа нон л сени ион анннеисееооненоооонеочеоновоецы 6-2
Communications Diagnostics ..........20200002000 0 aa ana aa aa AA Aa aa 4-21
Contactor Unit (CTU) oe aaraceaaaaca eo0aaoaaoacoredeada, 3-1
Contacts ...........escerreccorroocrrrererece aa oneocanannoereceneeenonórooneaee, 6-1
Contamination ................o—esreevesrvececee00mecao aa aaaOnoaCeaaacoaaroroniaoeca 6-1
Control 8 Signal Connections ..............._eeesÑr0drd0eo aa aa 2-4
Control & Signal Interconnections Information ................- La at LL 2-4
Control & Signal Wires .... aa aa eee ae aaa rnao 2-4
Control Card 00er ererareacarecarerareecocancaa na aecraaoerdora 3-17
Control Card ( 103 CON/ 3500 C03) Replacement ..............._... a aa LL 5-20
Controlled Braking Setup ...............—.. 2... 0000 ea aaonoaareói, 2-8
Conversion from one Number System to Another .........Ñ...e 2... 000000 eeerereara, 7-26
CP-2 Control Panel arererorceradecacececaanooeaaca ia oooovao 3-12
CP1 Control Panel ............ e eeenaracacooaaaaianeaaa0eaanocecaororedo. 3-9,4-17
CP2 Displays Scaling ..................... ererecrreraaacaa caca aa 7-7
Currentand Voltage Tuning .................e.. eee eee оуууоенееенеее 2-10
Page 9-2
Bulletin 1352C-5.3 Index
D
DBMODE 90EE (LGU Operates INREGEN Only) 211111 LL A A LR 4-12
DE Capacitors aa es aa A aa aa A a a ee ae a a a a a aa a a ae aa aa 7-34
DE Voltage Controller ...................22. RER RER 4-6
DC Voltage Reference .................... 0 aneCiorerCen aa aaarrrereaoodoreneaia, 4-5
Debugger ...........eeeeecvreereceeaeaaea ene aa a a nd a a a a a a AL 7-15
Decimal System .............. iii ee eee eae aaa eae eae. 7-26
Description of Equipment .....................2 0... "._—..— ee AA 1-2
Diagnostic Messages iti a na a sea aa aa a aa a aa aan 5-2
Diagnostics ................e 000000000 Ada aa aa aa Ada aa AAA AAA 5-4, 7-12
N EEE 3-10
Display Addresses 0002. ee aa aneneaaarroaaioooooorecie 7-4
Display Operation ............... 2.0.2 nara eno a aaaaerioeeneora 3-10
Displays naco a AAA a a 3-16
Documenting Errors Lee a eee ea a ea ea ea a a aa a 5-1
Drive Status .............ñ._eecerecrcroceamceirecoceaoonaa aran a a ееееееени 5-4
F
Fault Diagnostic Displays .................... 2.2000 ena a a A A aa LL 3-10
FaultQueue eerericorereaaceaeaaaca0aó enarecÓcecarionoiare ia 5-4
FaultTable ..................000000 00 a ea ae a a a a da a a a a a a aa aa aa a 5-2
FAUT Le a aa da a aa a aa ana aa aa A 5-4
Firmware .............ecceexecraoeaeaaeaeaooaaaoneaaarenacendedanienovororocaaorcarena 4-3
Frequency Controller... eee da aa a ee ee aa a a a aan, aaoenreco 4-6
G
Glossary Lo к ни ен не ванн ннунануе лисе ееееееееоеоооные 8-1
Grounding Practices ................ee...eeseresoaroc 0 da a a aa 2-2
GTO and Free Wheeling Diodes ....................20200. 0 eareciocneccónenec or 5-21
GTO Chopper Control Card ..... RR RER RR 3-21
GTO Power Supply Card ..... oe a A aa a aa a a aan a 3-22
GTO Puise Amplifier Card ............... nea aa a a a 3-19
|
Input/Output Connection Card ..................0. 0.0.0 r0r0edieaaenaraecacecenavece, 3-24
Installation Instructions... o.oo i 00000 ea a aa 5-22
Installation Site ................ e .e00eririerereeereai ea aaaareaoconeneaaaocoreoneco 2-2
Interference Suppression ............... 00.00 aa a aa aa ae ana aa 2-4
Inverter Unit (INU) 1.111200 ee A AE 3-6
IQCONT 48EE (Select Power Factor Control) rn 4-13
Page 9-3
Bulletin 1352C-5.3 Index
K
Keep Good Maintenance Records .............1200anaasa ana aa a aa aa 6-2
L
LFU'S 11111 LL LL L Lee ea AAA AAA Ada de a A A aa aa AA A da AA 7-35
LGU Adjustments LL a aa ee ea a a aa Aa 2-10
LGU Control ........... eee ea a a a a ae a a a a a a a a Aa A AA A0 7-4
Line Converter Unit (LCU) ............... ee a a a AL 3-4
Line Filter Unit (LRU) «oo. ii ee AL 3-7
Line Generating Unit (LGU) 1.112020 Lean ana aa aa aa 3-8
Line Regenerative System ................. 2... aa dde e a aaoereacooóad 2-8
LOC/REM .......u aaaaenanerenacec e reneroooerecooon aria 3-10
Losses and Ventilation/Conditioning Air Reguirements ............... ee 2-5
M
Main Contactor oo e coaoocaii 4-2
Maintenance Work oo. e erenrroecananeca are oororedaaceioaia 1-4
Matching Card ..... eee aaa ee aarracec eerieareaa, 3-27
Modes of Operation .............. ea aa aeno aaa oorareareceioóeeaoo 4-10
Monitoring of the Trend Triggering .................... aan aa nererooeaaaeo 5-19
Mounting .................. ereeeeea eee oonenocaneneneaaao aa aorrrorrececacó. 2-2
N
Negative Numbers .................. RER ana aa a 7-28
Non-Regenerative System Startup .................002.. e aa a eaararearrea 2-8
Number Systems ....................0 a arrerareraaacCenecec orraacocerecioocaciao 7-26
O
Operating Mechanisms .ererecic cen aacos o ecorerereraaco: — 6-1
Operating The Drive oi i ee ee a A 3-10
Operational Controls .................. ir a aa aa a aa aa aa a a 7-2
Operator Interface ........ ee ne aren aaa ea aeaeo a aeneaeaa aaa aoooor.o 4-17
Optional Controlled Braking ......... aa anedeeeeo 2-5, 3-8
Overload Maintenance After a FaultCondition 1111011 6-2
P
PARAM -.............e00eereaaanan area PT 3-10
Parameter Mode 1222211211 eee aa aa a ea aa aa a aa a a a a aa 3-11
Parameter Table ................000000000 00 a aa a a ad a aa 7-1
Parameter Values After Start-Up ...................200000 0 DD dada 7-30
Parameters 20ftheLGU ................. Ce ee eee ieee eee eee 7-10
Parameters 3 ofthe LGU ......._....... a aaa aa A 7-18
Parameters of the LGU ............. aa a a arroreererecoevcóco 7-6
Periodic inspection .....................00 00.000 een ea 6-1
Page 9-4
Bulletin 1352C-5.3 Index
Power CoNNeCtiONS «ooo ea aenenonoreaorreio erica 2-3
Power Transistors (GTR) ...............e_2e22000mro0e0 a eee eid 5-21
Pre-Instaltation .............. 0. eririec ao narereciaaeca,on o aoacorecacira 2-1
Preparation For Startup 2.000 e a 2-6
Preventative Maintenance of Drive Equipment ............ un rerececocecia 6-1
Principle of Fault Tracing .... ooo ee aa aeooaorrereearóae 5-1
PUCMODE 162£E (Parallet LGU's Only) LL... LL LL LL AA 4-10
Pushbuttons .............._.eomeeeerrereca enano aaaa anna a aooreceoeeeecoooeccór 3-12
Q
QUCMODE 161EE (Maintain Power Factor via DC Volts) ........1111111LL 0 4-13
R
RAM Memory Battery Backup .............Ñ........0 0D a anna 2-11
Rated DC Voltages & Currents ......... iio i 7-34
Rated Values oo aaa aarece ad 7-34
Reactive Current Controller ................. eee ee aora aareroeoecoecaconeaa 4-8
Reading Software and Firmware Diagrams ......................... et ea. 4-3
Reference Values .....................00000 0000 ea aa An 7-3
Regulator Status oo aaooaanaaaacaaaaoroenaciecioo 5-4
REQUESTMSGE 112EE and ANSWERMSGE 113EE o.oo id 4-21
RESET .....rverececanrocorerereae ani racer inn a oeeraanereceaaaaroororerececÓcaca ico 3-10
REV ennnnioroorccean ena acer arena oa ea aaoavannanonecaooeanaocacanecoororooroaaaroara 3-10
5 |
Safety ......2 12e eee aa ae eee aa ae ea ae a ea aa a aa ea ae da A aa AAA acceda iaa, 1-4
Safety & Codes .........01L2 2e a aa nana aa nada aa ae aa a ae AN о 2-1
Saving Changes ................000000 0080000000 a a a AAA a aan 2-11
Scaling the Displays .................0.000000 aa ana aa aa a AA 3-16
Selection of Monitored Addresses ........................ errerenenenerenereceri.e, 5-18
Selection of Sampling Interval .................. 2. rana aooaaooooaaeroeadas 5-18
Selection of Triggering Condition ................_.._ a Lea aa LL 5-18
Serial Communications Channel 1... aero rerereneneaaa 7-8
Serial Communications Channel 2 ............... e A 7-9
Serial Communications Software er aa anna aan Cea 4-20
Setting Parameters... ana A na a aa a a 3-16
Solid State Devices .... e ea aa aa a a ae a a aa a aa da a a Aa ar rea errores 6-2
START ESTOP ..................000r00recac aaa enerarencecec erro ocecerecoreriaa 3-10
Start-Up “Sector” Adjustment ......... a aa ao a aarcrreroeaao 4-14
Starting ........... PS Cer ee eee eee ee 4-2
Startup Equipment Required ............. enredar en aaoneceCenacaao acond ooo 2-5
StOpping it RR RER 4-2
CN ALLEN:-BRADLEY
UD” AROCKWELL INTERNATIONAL COMPANY
With offices in major cities worldwide.
WORLD HEADQUARTERS EUROPE/MIDDLE EAST/
Allen-Bradley AFRICA HEADQUARTERS
1201 South Second Street Allen-Bradley Europe B.V.
Milwaukee, WI 53204 USA Amsterdamseweg 15
Tel: (1) 414 382-2000 1422 AC Uithoom
Telex: 4311 016 The Netherlands
Fax: (1) 414 382-4444 Tel: (31) 2975/43500
Telex: (844) 18042
Fax: (31) 2975/60222
Publication 1352C-5.3 — October, 1987
A subsidiary of Rockwell international, one of the world’s largest technology companies, Allen-Bradley
meets today’s automation challenges with over 85 years of practical plant floor experience. More than
12,000 employees throughout the world design, manufacture and apply a wide range of control and
automation products and supporting services to help our customers continuously improve quality,
productivity and time to market. These products and services not only control individual machines, but also
integrate the manufacturing process while providing access to vital plant floor data that can be used to
support decision-making throughout the enterprise.
ASIA/PACIFIC HEADQUARTERS CANADA HEADQUARTERS
Allen-Bradley (Hong Kong) Limited Allen-Bradley Canada Limited
Room 1006, Block B, Sea View Estate — 135 Dundas Street
2-8 Watson Road Cambridge, Ontario N1R 5X1
Hong Kong Canada
Tel: (852) 887-4788 Tel: (1) 519 623-1810
Telex: (780) 64347 Fax: (1) 519 623-8930
Fax: (852) 510-9436
LATIN AMERICA
HEADQUARTERS
Allen-Bradley
1201 South Second Street
Milwaukee, Wi 53204 USA
Tel: (1) 414 382-2000
Telex: 4311 016
Fax: (1) 414 382-2400
P/N 503915
Copyright 1992 Allen-Bradley Company, Inc. Printed in USA
">
/