Yaskawa E7 E7 Drive Cheat Sheet
Pubblicità
Pubblicità
The following procedure is a supplement to other documentation supplied with this equipment and will guide the user in properly wiring the E7 and motor.
It will also show the user how to configure the E7 for Hand and Auto operation.
Danger:
Improper wiring can and will
cause bodily harm as well as damage to the equipment.
Step
1
E7 Model Identification and
Mounting
To make sure you received the correct model, it is essential to verify the E7 nameplate with your order and make sure that the E7 has the correct rating so it can be used with your motor. Please check the nameplate information as shown in the example below.
Drive Model
Number
Input Power
Rating
Output Power
Rating
Serial
Number
UL File
Number
CIMR-E7U2011
Drive Spec
Number
Weight
Check that the available power meets the input power requirements.
Ensure that the output power from the VFD is compatible with the motor requirements.
In the case of systems with multiple VFDs follow the above procedure for each VFD and the motor it will control.
When installing the system, be sure to follow good wiring practices and all applicable codes.
Ensure that the mounting of the various components are secure and that the environment, such as extreme dampness, poor ventilation etc. will not cause system degradation.
Mounting the E7
The mounting of the E7 is extremely important regarding environment and accessibility. Depending on your system, there are various models available and the mounting dimensions (footprint) may be different. Because the mounting procedure is fairly extensive, it is beyond the scope of this document, the user is referred to the E7 User Manual
(Document No. TM.E7.01) received with the E7, Section 1
Physical Installation. Match the model that you received and follow the procedure described in the manual to ensure a safe and functional installation. In cases where the system has more than one E7, refer to the proper clearances required for adequate ventilation. Please pay particular
attention to:
The clearances to be maintained around the enclosure for adequate ventilation.
The environmental specifications such as avoiding excessive dampness, extreme temperatures, chemical exposure, corrosive areas etc. to avoid damage to the equipment and to maintain safety.
Removing and Attaching the Terminal Cover
Improper removal of the E7 terminal cover as well as front cover can cause extensive damage to the E7. To avoid damage to these items, please pay particular attention to the
E7 User Manual, Document No. TM.E7.01, Section 1.7,
Removing and Attaching the Terminal Cover.
Please read this cheat sheet and the E7 User
Manual (TM.E7.01) provided with the E7 thoroughly before attempting any installation.
NEMA 1
YEA Document Number: TM.E7.03 01/15 /20 10
Open Chassis
Step
2
E7 Cheat Sheet
E7 Motor and
Line Power
Fig.1 & 2 below show the electrical connections for the input power and motor terminals for various E7 models.
Select the proper diagram for the model you are installing
(see Step 1). WITH POWER OFF make the appropriate connections.
Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is grounded properly as shown.
!
DANGER, LETHAL VOLTAGES ARE PRESENT- Before applying power to the E7, ensure that the terminal cover is fastened and all wiring connections are
secure. After the power has been turned OFF, wait at least five minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components.
WARNING DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
B1 B2 + +1 +2
Step
3
E7 Control Wiring
Page 1 of 2
This step shows how to connect control wiring to the E7. Before making any control connections MAKE SURE POWER
TO THE E7 IS TURNED OFF!
Next remove the terminal cover to gain access to the control terminals (See Step 1).
SELECT SPEED COMMAND METHOD b1-01
The E7 is DEFAULT SETUP FOR SPEED COMMAND SIGNAL FROM TERMINALS. Please refer to the diagram below for wiring an external speed command signal. Program b1-01 to 0 to set speed command from the digital operator.
For use with 0
– 10V Speed Command Signal
For use with 4
– 20mA Speed Command Signal
E7 User Control Terminals
SN SC SP A1 A2 +V AC AC R+ R-
E7 User Control Terminals
SN SC SP A1 A2 +V AC AC R+ RS1-2 in ON
Position
E(G)
O
F
F2
E(G)
O
F
F
1
2
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG S+ S-
Cable
Shield
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG S+ S-
Cable
Shield
R/L1 S/L2 T/L3 + 1 + 2 B1 B2 U/T1 V/T2 W/T3
NOT USED
(R/L1) (S/L2) (T/L3) (U/T1) (V/T2) (W/T3)
Connect to chassis ground
Input
Protection
(Fuse or Circuit
Breaker)
To change direction of motor rotation swap any
two of the three motor leads (See Step 2)
Connect to chassis ground
L1 L2 L3
Connect frame to ground
Use L1, L2 for
1Ø Input Power *
Use L1, L2, L3 for
3Ø Input Power
3Ø Induction motor
Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 20P4 to 2018 & 40P4 to 4018
+
0 – 10V
-
For use with Potentiometer
E7 User Control Terminals
SN SC SP A1 A2 +V AC AC R+ R-
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG S+ S-
Potentiometer
2K Ohm
O
F
F
+ -
4 – 20mA
For use with 2-Wire, 4 – 20mA Transducer
E7 User Control Terminals
E(G)
SN SC SP A1 A2 +V AC AC R+ R-
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG S+ S-
Black: Output
4 – 20mA (2)
Cable
Shield
Brown or Red: +Power (1)
S1-2 in ON
Position
O
F
F
1
2
Note: Only for use with PI Mode
(Refer to TM.E7.01 section 5-17)
Used also used in Hand Mode when b1-12 set to ‘1’
SELECT RUN COMMAND METHOD b1-02
R1/L11 S1/L21 T1/L31
R/L1 S/L2 T/L3
NOT USED
-
U/T1
+ 1
V/T2 W/T3
+ 2
The E7 is DEFAULT SETUP TO START/STOP FROM TERMINALS. Please refer to the diagram below for wiring an external run command switch or contact. Program b1-02 to 0 to start/stop the E7 from the digital operator using the
AUTO button.
Use for permanent contacts
2-Wire Control
E(G)
(Factory Default)
E7 User Control Terminals
SN SC SP A1 A2 +V AC AC R+ R-
Use for momentary contacts
3-Wire Control
E(G)
E7 User Control Terminals
SN SC SP A1 A2 +V AC AC R+ R-
(R/L1) (S/L2)
Input
Protection
(Fuse or Circuit
Breaker)
(T/L3) (U/T1)
Connect to chassis ground
(W/T3)
(V/T2)
To change direction of motor rotation swap any two of the
three motor leads
(See Step 2)
L1 L2 L3
Connect frame to ground
Use L1, L2 for
1Ø Input Power
*
Use L1, L2, L3 for
3Ø Induction
3Ø Input Power motor
Fig. 2 Input Power and Output Motor Electrical Connections for
Models: 2022 & Larger and 4030 & Larger
* Make sure the drive has been properly sized for single phase input power.
*
Cable
Shield
*
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG
Connect switch or contact to terminal S1 and terminal SN
Use for permanent contacts
2-Wire Control
Factory Supplied
S+ S-
Cable
Shield
*
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG S+ S-
Normally Open
Connect momentary contacts to terminal S1, S2 and SN
Normally Closed
To use 3-Wire
Control, first initialize the E7 using parameter
A1-03 = 3330
(Refer to
TM.E7.01)
©20 10 Yaskawa Electric America, Inc. (800) YASKAWA (927-5292) Fax (847) 887-7310 [email protected] www.yaskawa.com
Step
4
E7 Quick Setup
This step shows how to set up the most important parameters using the E7 Quick Setup function. Apply power to the E7 after all the electrical connections have been made and the terminal cover has been re-attached. At this point DO NOT RUN THE MOTOR . The Digital Operator should be reading as shown in Fig. 3 (See Step 5).
Next, push 2 times on the Digital Operator until the Digital Operator shows the
Quick Setting Menu.
Next press to start the Quick Setup procedure.
E7 Cheat Sheet
Step
5
Check Motor Rotation and Direction
Check the motor for proper direction and operation. This test is to be performed solely from the digital operator. Apply power to the E7 after all the electrical connections have been made and protective covers have been re-attached. At this point DO NOT RUN THE MOTOR . The Digital Operator should display as shown below in Fig. 3.
Page 2 of 2
Step
6
Hand / Auto Mode Operation
HAND MODE
The E7 can be operated in HAND mode when the following actions have been performed:
All parameters are programmed
Motor direction is correct
Hand Mode: Hand Reference source selected in parameter b1-12
FWD LED
ON
01 Flashing
Hand Reference b1-12
The E7 Quick Setup consists of the most important parameters to setup your E7 Drive for use with your motor system.
Press to access a parameter, and use to select the digit and use
Fig. 3 Digital Operator to change the parameter value.
Press Hand Button
Press to Turn Off/Stop System
Press to save the value.
Press to go to the next parameter to continue the Quick Setup programming.
When Quick Setup is completed press to exit the Quick Setting menu and go to operation.
Quick Setup Parameters
b1-03
b5-01
b5-02
b5-03
b5-31
C1-01
C1-02
d2-01
d2-02
E1-01
E2-01
H3-08
Parameter
b1-01
b1-02
H3-09
H3-13
Default
Value
Description Comments
1
1
0
0
2.0
Speed Command Source
Speed Control Method
Run Command Source
Start/Stop Control Method
Stop Method Selection
PI Mode Selection
Proportional Gain Setting
5.0 sec. Integral Time Setting
0 PI Unit Selection
0 = Digital Operator (Adjust Motor Speed from keypad)
1 = Terminals (Speed Pot. / 0 - 10V / 4 - 20mA)
0 = Digital Operator (Start/Stop motor from keypad)
1 = Terminals (Start/Stop using external contact / switch)
0 = Ramp to stop (Motor ramps down at stop command)
1 = Coast to stop (Motor freewheels at stop command)
0 = Disabled, 1 = Enabled, 3 = Fref + PI
Only active when b5-01 is set to value greater than 0
Only active when b5-01 is set to value greater than 0
Predefined Engineering Units, see TM.E7.01
3
3
0.0 sec.
0.0 sec.
Acceleration Time
Deceleration Time
100.0 % Frequency Upper Limit
0.0 % Frequency Lower Limit
*
*
2
2
0
The time it takes to ramp up from 0 to maximum motor speed.
The time it takes to ramp down from maximum motor speed to 0.
Maximum motor speed allowed (e.g. 100 % = Max rpm)
Minimum motor speed allowed (e.g.
Input Voltage Setting
Motor Rated Current
Terminal A2 Signal Level Selection
Auxiliary Terminal Input Selection
Master Freq. Ref. Terminal Selection
Nominal voltage of incoming line
Motor nameplate current
0 = 0 - 10V
2
3
4
= - 20mA
Predefined signals, see TM.E7.01
0 = Main Fref is terminal A1
1 = Main Fref is terminal A2
0 % = Min rpm)
YEA Document Number: TM.E7.03 01/15 /20 10
STOP LED ON
Press then press to change the speed command.
0 Flashing
Next press then .
The motor should now be operating at low speed, e.g. 10.00 Hz, running in the correct forward direction.
Next, press on the Digital Operator.
If motor rotation is not correct, power down the E7 Drive.
!
DANGER
After the power has been turned OFF, wait at least five minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components.
Digital Operator turned off.
Using Safety precaution, and referring to Fig.1 or 2, swap any two of the three output leads to the motor (U/T1, V/T2 and W/T3). After the wiring change, repeat
Step 3 to recheck motor direction.
Hand Frequency Reference Selection: b1-12
0: Use digital operator to enter Speed command (factory default)
1: Use analog input terminal A1 or A2 depending on parameter H3-13 selection
(See Step 3 for wiring instructions).
AUTO MODE
The E7 can be operated in AUTO mode when the following actions have been performed:
All parameters are programmed
Motor direction is correct
Auto Mode: Reference source selected in parameter b1-01 (See Step 3)
Auto Mode: Run source selected in parameter b1-02 (See Step 3)
Press Auto Button
Set Reference (b1-01)
Press to Turn Off/Stop System
Press the AUTO button to put the E7 into AUTO mode.
In AUTO mode the E7 is capable of starting or stopping based on the Run
Command Selection setting parameter b1-02 (See Step 3 Select Run Command
Method).
The Speed Command used in AUTO mode is based on the Speed Command
Selection setting parameter b1-01 (See Step 3 Select Speed Command Method).
©2010 Yaskawa Electric America, Inc. (800) YASKAWA (927-5292) Fax (847) 887-7310 [email protected] www.yaskawa.com