BEA ULTIMO User Guide
BEA Ultimo is an advanced automatic door activation and safety sensor that combines microwave doppler radar and active infrared (AIR) technology with background analysis to provide reliable and efficient door operation. With a detection speed of 2 inches per second and a response time of less than 200 milliseconds, it ensures precise and timely door activation. The sensor features three adjustable AIR curtains with up to 32 spots per curtain, allowing for customized detection zones. Its versatile mounting options and adjustable detection field make it suitable for a wide range of applications.
বিজ্ঞাপন
বিজ্ঞাপন
Visit website for available languages of this document.
75.0034.06 ULTIMO 20230401
ULTIMO
ACTIVATION AND SAFETY SENSOR FOR
AUTOMATIC, SLIDING DOORS
Software version 2.5 / Configuration version 7.0
(refer to Admin menu for product software vesion)
Page 1 of 20
DESCRIPTION
1
2
3
4
1. cover
2. light pipe
3. radar antenna
4. AIR receiver
5. AIR emitter
6. LCD
7. [for internal use only]
8. LED
9. AIR curtain angle adjustment knob
10. main adjustment knob
11. main connector
12. [for future development]
5
6
11
12
7 8
9
10
Page 2 of 20 75.0034.06 ULTIMO 20230401
TECHNICAL SPECIFICATIONS
Mounting height
Detection mode
Technology
Radar detection speed (min)
AIR response time (typ.)
Radar transmitter frequency radiated power power density lobe angles
AIR spots size number of spots number of curtains curtain angles
Relay output 1 max. contact current max. contact voltage adjustable hold time
Optofet output 2 max. contact current max. contact voltage hold time
Test/Monitoring input sensitivity response time on request
Supply voltage
Power consumption
Temperature range
Cable length/gauge
Degree of protection
Compliance
6’6” – 11’6” typical: 7'2" motion and presence microwave doppler radar and active infrared (AIR) with background analysis
2 in/s
< 200 ms (max. 500 ms)
24.150 GHz
< 20 dBm EIRP
< 5 mW/cm 2
0 – 45° (typical adjustment), default 25°
2” × 2” (typ.) max. 32 per curtain
3
-3 – 11°, default 0° electromechanical relay (potential- and polarity-free)
1 A
30 VDC
0.5 – 9 seconds solid-state relay (potential- and polarity-free)
400 mA
42 VAC/VDC
0.3 – 1 second low: < 1 V high: > 10 V (max. 30V)
<5 ms (typ.)
12 – 24 VAC ±10%,
12 – 30 VDC ±10%
< 3.2 W
DO NOT EXCEED 26.4 VAC
-13 – 131 °F *
0 – 95% relative humidity, non-condensing
LCD screen is operational from 14 – 131 °F. The sensor may still be programmed in colder temperatures, but with the remote control.
10' / 26 AWG
IP54
R&TTE 1999/5/EC; MD 2006/42/EC; LVD 2006/95/EC; ROHS 2 2011/65/EU
Specifications are subject to change without prior notice.
All values measured in specific conditions.
75.0034.06 ULTIMO 20230401 Page 3 of 20
READ BEFORE BEGINNING INSTALLATION/PROGRAMMING/SETUP
LED SIGNALS
COLORS
(green)
Motion detection
(red)
Presence detection
(white)
IR synchronization
BEHAVIORS
LED flashes
LED flashes quickly x
LED flashes x times
LED flashes red-green
LED is off
INSTALLATION
The sensor should be mounted securely to avoid extreme vibrations.
Do not cover the sensor.
Avoid moving objects and light sources in the detection field.
Avoid highly reflective objects in the infrared field.
This device can be expected to comply with Part 15 of the FCC Rules, provided it is assembled in exact accordance with the instructions provided with this kit. Operation is subject to the following conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
MAINTENANCE
It is recommended to clean the optical parts at least once a year or more if required due to environmental conditions.
Do not use aggressive products to clean the optical parts.
SAFETY
The door control unit and the header cover profile must be correctly grounded.
Only trained and qualified personnel are recommended for installation and setup of the sensor.
Following installation, always test for proper operation
(according to ANSI 156.10) before leaving the premises.
The warranty is invalid if unauthorized repairs are made or attempted by unauthorized personnel.
Page 4 of 20 75.0034.06 ULTIMO 20230401
1
MOUNTING & WIRING
MOUNTING
1. Using the provided mounting template, mount the sensor centered over the clear opening*, ensuring that the bottom of the sensor is no higher than 5 inches from the bottom of the door header.
CAUTION
DOOR
AUTOMATIC
AUTOMATIC
DOOR
AUTOMATIC DOOR - STAND CLEAR
AUTOMATIC DOOR - STAND CLEAR
AUTOMATIC
CAUTION
CAUTION
DOOR
AUTOMATIC DOOR - STAND CLEAR
AUTOMATIC DOOR - STAND CLEAR
AUTOMATIC
CAUTION
DOOR CAUTION
DOOR
AUTOMATIC DOOR - STAND CLEAR
AUTOMATIC DOOR - STAND CLEAR
DUAL SLIDER SINGLE SLIDER
* Extreme left or right mounting is an option for single-sliders when using IR:Width settings 4 or 5 (see page 12). Be sure that the edge of the sensor is aligned with edge of the door header max. 5 in
AUTOMATIC
CAUTION
DOOR
AUTOMATIC
CAUTION
DOOR
2. Route the harness (20.5349) using the wire stay as shown.
• Sensor connectivity (power and relays) must utilize only the supplied harness.
• Sensor is intended to be monitored for proper operation by the door operator or system.
• Harness shall be routed separated from any Mains or non-Class 2 voltage cable for correct operation or shall be rated for the Mains voltage, and suitable protection and routing means shall be used according to
National and Local Codes to prevent damage to the harness and/or sensor.
75.0034.06 ULTIMO 20230401 Page 5 of 20
1
MOUNTING & WIRING
WIRING
RED
BLACK
BROWN
BLUE
WHITE (COM)
YELLOW (N.C.)
GREEN (N.O.)
PURPLE
PURPLE
POWER SUPPLY 1
POWER SUPPLY 1
SAFETY INPUT
SAFETY INPUT
OPENING INPUT
OPENING INPUT 2
OPENING INPUT 2
TEST OUTPUT 3,4
TEST OUTPUT 3,4
1. Voltage: 12 – 24 VAC, 50/60 Hz; 12 – 30 VDC; < 3.2 W (max)
DO NOT EXCEED 26.4 VAC
If a power supply is needed, BEA recommends using only the 12V transformer (1012VAC).
2. Use either yellow or green, not both.
3. Test monitoring input: low = < 1 V, high = > 10 V (30 V max.); response time: typ. < 5 ms
4. The sensor LED will briefly flash RED and the LCD will display a monitoring notification during monitoring communication with the door control. This indicates that external monitoring is functional. Sensor monitoring functionality is automatic by default. Ensure purple wires are properly connected to the door controller and monitoring is enabled. Sensor monitoring logic is defaulted to ActiveLow. ActiveHigh monitoring logic is selectable via InTestLogic on menu 3. To turn sensor monitoring OFF, navigate to menu 3 on the LCD and set InTestMode to OFF.
Page 6 of 20 75.0034.06 ULTIMO 20230401
READ BEFORE BEGINNING PROGRAMMING/SET-UP
HOW TO USE THE LCD
DISPLAY DURING NORMAL FUNCTION motion AIR negative display = active output To adjust contrast, push and turn the gray button simultaneously.
During normal function only.
FACTORY VALUE VS. SAVED VALUE displayed value
=
factory value displayed value
=
saved value
NAVIGATING IN MENUS
1) Push to enter the LCD menu.
2) Enter password, if necessary.
3) Select language before entering the first LCD menu.
Password
X X X X
Not during the first minute after power-on of the sensor.
= scroll = select
Select Back to return to previous menu or display.
Select More to go to next level:
- IR menu
- Radar menu
- Outputs & Diagnostics menu
VALUE CHECK WITH REMOTE CONTROL
Pressing a parameter symbol on your remote control displays the saved value directly on the LCD screen. Do not unlock first.
75.0034.06 ULTIMO 20230401 Page 7 of 20
READ BEFORE BEGINNING PROGRAMMING/SETUP
HOW TO USE THE REMOTE CONTROL
UNDERSTANDING LED ACTIVITY
After unlocking, the red LED flashes and the sensor can be adjusted by remote control.
If the red LED flashes quickly after unlocking, you need to enter an access code from 1 to 4 digits.
If you do not know the access code, cycle the power .
During 1 minute, you can access the sensor without introducing any access code.
To end an adjustment session, always lock the sensor.
ACCESS CODES
It is recommended to use a different access code for each sensor in order to avoid changing settings on both sensors at the same time.
SAVING AN ACCESS CODE
The access code is recommended for sensors installed close to each other.
DELETING AN ACCESS CODE
Enter the existing code
DELETING AN UNKNOWN ACCESS CODE
CYCLE
POWER
ADJUSTING ONE OR MORE PARAMETERS
CHECKING A VALUE
x
x = number of flashes = corresponds to the remote control button assignment for the current setting (see page 16 for parameter assignments)
Example: For a sensor still programmed to factory default, the value check for AIR Presence Time will result in 2 green LED blinks.
RESTORING TO FACTORY VALUES
Page 8 of 20 full reset partial reset full reset = restores to factory defaults partial reset = restores all settings except monitoring and outputs
75.0034.06 ULTIMO 20230401
2
RADAR FIELD
The size of the detection field varies according to the mounting height and parameter settings of the sensor.
ANGLE
Tilt the antenna up to adjust the depth outward and down to adjust inward from the doorway.
Graphics are representations, not default settings.
SHAPE
Navigate to menu 2 of the LCD to choose the desired width shape – wide lobe or narrow lobe.
If using remote control, you can also press the minus sign ( ) to select Narrow shape.
and the plus sign (
To check the existing radar field size/shape, use the following sequence:
x
x = number of flashes
= corresponds to the field size
1x = narrow
2x = wide
75.0034.06 ULTIMO 20230401
) to select Wide shape or
Page 9 of 20
3
ACTIVE INFRARED SAFETY FIELD
NUMBER OF CURTAINS / POSITION OF CURTAINS
(IR:CURTAINS, MENU 1)
Choose the number of and position of the AIR curtains based on your application.
NOTE: The sensor is defaulted to Non-Threshold setting (3). If threshold is desired, you may choose Threshold setting 1, 2, 4, or 5; be sure that the curtain placement matches the LCD screen.
If necessary, use visible spots and red adjustment knob to position properly (see page 11).
DEFAULT
UNDERSTANDING THE LCD "CURTAINS" GRAPHICS
GENERAL SETTINGS the number of squares on a line indicates the curtain number (i.e. C1, C2, or C3) the rectangles on each side of the setting number represent sliding door panels
THRESHOLD SETTINGS (1, 2, 4, 5) a dotted line indicates that curtain C1 is active at full open and inactive during door closing cycle (settings 2 and 5) a solid line indicates that curtain C1 is active at full open and partially active during door closing cycle (settings 1 and 4)
Page 10 of 20 75.0034.06 ULTIMO 20230401
3
ACTIVE INFRARED SAFETY FIELD
ANGLE
1. Activate the four visible spots (press gray knob twice) to verify the position of the AIR curtains.
Visibility depends on external conditions. When spots are not visible, use the Spotfinder to locate the curtains.
THRESHOLD
OR
NON-THRESHOLD
C1
C2
C3
C1
C2
C3
2. If necessary, adjust the AIR curtain angles using the red adjustment knob (see below) and then select the corresponding IR:Curtains setting on menu 1 of the LCD (see right).
NOTE: Be sure that setting shown on the LCD matches the AIR curtain position.
THRESHOLD
NON-THRESHOLD
default
3. When in Threshold mode, verify correct positioning of the threshold curtain:
First, turn on the red spots, and then verify that either C1 is at least in line with the moving door panel (see image below, left) or *preferred* through the door opening (see image below, right).
Next, ensure that C2 is within 3 inches of face of door for the width of the door opening.
C1
C2
C3
C1
C2
C3
75.0034.06 ULTIMO 20230401
PREFERRED
Page 11 of 20
3
ACTIVE INFRARED SAFETY FIELD
WIDTH
1. If desired, adjust the field width using the LCD menu or remote control buttons (see page 16,
IR:Width menu).
WIDE STANDARD NARROW
LEFT, ANGLED RIGHT, ANGLED
The size of the detection field varies according to the mounting height and the settings of the sensor.
Widths specified above correlate to standard mounting height (7'2").
Settings 4 and 5 are only optional in single-slider applications.
2. Always verify the actual AIR detection field by walk-testing according to ANSI 156.10.
Do not use a SPOTFINDER to verify the AIR detection field.
Page 12 of 20
Additional adjustments are possible by LCD or remote control (see OVERVIEW OF SETTINGS).
75.0034.06 ULTIMO 20230401
3
ACTIVE INFRARED SAFETY FIELD
ULTI-SYNC: AUTOMATIC SAFETY FIELD SYNCHRONIZATION
ULTI-SYNC is used to eliminate AIR crosstalk when safety fields are overlapping in the threshold of the door or when safety fields are overlapping side-to-side.
If installed with another sliding door sensor (BEA or otherwise), see the ULTI-SYNC
CROSSTALK Application Note (78.6038)
The LED will flash white, confirming the synchronization is detected. If an overlapping safety field is found in the threshold of the door, ULTIMO will remain synchronized for 2 minutes while the door is closed. If activation does not occur for 2 minutes, the white LED will flash, confirming synchronization is lost. The fields will be synchronized again upon the next activation and will be confirmed by a flash of the white LED.
To check the synchronization status, navigate to menu 3, IR:Synch.
75.0034.06 ULTIMO 20230401 Page 13 of 20
4
SETUP
Ensure that the infrared field is clear of any obstructions.
The sensor can be set up using either the push button or the remote control:
PUSH BUTTON:
Press and hold the gray knob for 2 seconds.
2 sec
REMOTE CONTROL:
Use the following remote control button sequence:
During setup, the LCD will display the camera icon and the LED will slowly flash red/green and then turn off.
+ slow flash
Test the proper operation of the system installation before leaving the premises!
Page 14 of 20 75.0034.06 ULTIMO 20230401
75.0034.06 ULTIMO 20230401 Page 15 of 20
Page 16 of 20 75.0034.06 ULTIMO 20230401
75.0034.06 ULTIMO 20230401 Page 17 of 20
TROUBLESHOOTING
RED LED
RED LED flashes quickly after a setup
The sensor sees the door during setup.
Move the AIR curtains away from the door.
Ensure that the bottom of the sensor is mounted within 5” of the bottom of the door header.
Launch a new assisted setup.
?
RED LED illuminates sporadically
RED LED flashes quickly when unlocking
The sensor vibrates.
The sensor sees the door in a non-threshold application.
The sensor is disturbed by external conditions.
The sensor is protected by a password.
RED Visible External
Monitoring (Test
Indication LED) does not flash
Monitoring installation/setup error.
Check if the sensor is secure. Ensure that the header cover screws and mounting screws are tight.
Check position of cable and sensor cover.
Turn on the visible red spots and adjust the angle of the AIR curtains.
Change the AIR immunity filter and AIR frequency.
Enter the correct password. If you forgot the code, cut and restore the power supply to access the sensor without entering a password during 1 minute.
Verify door control is capable of monitoring and the sensor monitoring wires are properly connected to the door control.
Verify monitoring (TEST) is ON in the sensor settings.
Replace the sensor.
Sensor malfunction.
RED Visible External
Monitoring (Test
Indication LED) flashes continuously
LT1 - Assisted Setup
Error
LT2 - Assisted Setup
Error
LT3 - Assisted Setup
Error
N1 - Assisted Setup
Error
N2 - Assisted Setup
Error
Wiring issue.
Door control not set correctly.
IR:Curtain set to 1, 2, 4, or 5,
C2 and/or C3 interfering with door during closing cycle
IR:Curtain set to 1, 2, 4, or 5,
C2 and/or C3 interfering with door during opening cycle
IR:Curtain set to 1, 2, 4, or 5,
C1 not on door threshold
IR:Curtain set to 3, 6, or 7, C2 and/or C3 interfering with door during closing cycle
IR:Curtain set to 3, 6, or 7, C2 and/or C3 interfering with door during opening cycle
Verify wiring.
Verify door control monitoring set to correct test logic according to the door control.
Increase tilt angle of the interfering curtain to move the curtain away from the threshold
(see pages 10 – 11).
Increase tilt angle of the interfering curtain to move the curtain away from the threshold
(see pages 10 – 11).
Decrease tilt angle of the interfering curtain to place the curtain on the threshold (see pages 10 – 11).
Increase tilt angle of the interfering curtain to move the curtain away from the threshold
(see pages 10 – 11).
Increase tilt angle of the interfering curtain to move the curtain away from the threshold
(see pages 10 – 11).
Page 18 of 20 troubleshooting continues on the next page
75.0034.06 ULTIMO 20230401
TROUBLESHOOTING
ORANGE LED
1
E1 - orange LED flashes once
2
E2 - orange LED flashes twice
The sensor signals an internal fault.
Replace sensor.
The power supply voltage is too low/high.
Check power supply voltage in Diagnostics menu (menu 3) of the LCD.
Check wiring.
Radar communication error Check the connection at the radar.
3
E3 - orange LED flashes 3 times
4
E4 - orange LED flashes 4 times
5
E5 - orange LED flashes 5 times
The sensor does not receive enough AIR energy.
Ensure proper mounting height.
Turn on the visible red spots and adjust the angle of the AIR curtains.
Deactivate curtain #3 (C3, outer curtain).
The sensor receives too much
AIR energy.
Ensure proper mounting height.
The sensor is disturbed by external elements.
AIR power emitter is faulty.
Turn on the visible red spots and adjust the angle of the AIR curtains.
Eliminate the cause of disturbance (lamps, rain cover, etc).
Replace sensor.
8
E8 - orange LED flashes 8 times
ORANGE LED is on The sensor encounters a memory problem.
Cut and restore power supply. If ORANGE
LED illuminates again, replace the sensor.
GREEN LED
GREEN LED illuminates sporadically
The sensor is disturbed by rain and/or leaves.
Ghosting created by door movement.
The sensor vibrates.
Increase radar immunity filter and adjust the radar field angle.
Change radar field angle.
Check if the sensor and door header is secure.
Check position of cable and sensor cover.
The sensor sees the door or other unwanted moving objects.
Remove the objects if possible.
Change radar field size, angle, or immunity.
75.0034.06 ULTIMO 20230401 troubleshooting continues on the next page
Page 19 of 20
TROUBLESHOOTING
OTHER
The LED and the LCD displays are off
No power to sensor.
Check wiring.
Check for correct power supply.
Door cycles open and remains open
Door control monitoring set to
Active High.
Safety output is set incorrectly.
The reaction of the door does not correspond with the
LED signal
The LCD or remote control does not react
Incorrect output configuration / wiring.
Batteries dead.
Set test logic to Active High.
Set the safety output required for the door control.
Ensure that the sensor output configuration matches what the door control is expecting.
Check sensor wiring.
Replace batteries.
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
BEA, Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA, Inc. does not guarantee any use of the sensor/device outside of its intended purpose.
BEA, Inc. strongly recommends that installation and service technicians be AAADM-certifi ed for pedestrian doors, IDA-certifi ed for doors/ gates, and factory-trained for the type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system performance is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer’s recommendations and/or per AAADM/ANSI/DASMA guidelines (where applicable) for best industry practices. Safety inspections must be performed during each service call – examples of these safety inspections can be found on an AAADM safety information label (e.g.
ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code).
Verify that all appropriate industry signage, warning labels, and placards are in place.
Page 20 of 20
Tech Support & Customer Service: 1-800-523-2462
General Tech Questions: [email protected] | Tech Docs: www.BEAsensors.com
75.0034.06 ULTIMO 20230401
ডাউনলোড
বিজ্ঞাপন