OMRON MX2 Series 3G3AX-MX2-ECT EtherCAT Communication Unit User's Manual
تبلیغات
تبلیغات
Inverter
MX2 Series
EtherCAT Communication Unit
User’s Manual
3G3AX-MX2-ECT
EtherCAT Communication Unit
I574-E1-02
© OMRON, 2011
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Introduction
Introduction
Thank you for choosing the EtherCAT Communication Unit 3G3AX-MX2-ECT. This User's Manual
(hereinafter called this manual) describes the parameter setting methods required for installation/wiring and operation of the 3G3AX-MX2-ECT, as well as troubleshooting and inspection methods.
This manual should be delivered to the actual end user of the product.
After reading this manual, keep it handy for future reference.
This manual describes the specifications and functions of the product as well as the relations between them. You should assume that anything not described in this manual is not possible with the product.
Intended Readers
This manual is intended for those with knowledge of the workings of electricity (qualified electric engineers or the equivalent), and also in charge of:
• Introducing the control equipment
• Designing the control system
• Installing and/or connecting the control equipment
• Field management
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1
Read and Understand this Manual
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING
NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED
USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS
OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER
SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE
PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION,
ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Read and Understand this Manual
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY
WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE
WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of
Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3
Safety Precautions
Safety Precautions
Indications and Meanings of Safety Information
In this manual, the following precautions and signal words are used to provide information to ensure the safe use of the EtherCAT Communication Unit 3G3AX-MX2-ECT.
The information provided here is vital to safety. Strictly observe the precautions provided.
The precautions and symbols are as follows.
Meanings of Signal Words
WARNING
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage.
Caution
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or in property damage.
Precautions for Safe Use
Indicates precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Indicates precautions on what to do and what not to do to ensure that the product does not become inoperative, malfunction, or disrupt functionality and performance.
Additional Information
Additional information to increase understanding or make operation easier.
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Safety Precautions
Example of Symbols
This symbol indicates a prohibited item (an item you must not do).
The specific instruction is indicated using an illustration or text inside or near .
The symbol shown to the left indicates "disassembly prohibited".
This symbol indicates danger and caution.
The specific instruction is indicated using an illustration or text inside or near .
The symbol shown to the left indicates "beware of electric shock".
This symbol indicates a compulsory item (an item that must be done).
The specific instruction is indicated using an illustration or text inside or near .
The symbol shown to the left indicates "typical compulsory items".
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5
Safety Precautions
WARNING
Do not remove the terminal block cover or the EtherCAT Communication Unit while the power is being supplied, and within 10 minutes after the power is turned off.
Caution
The inverter has high voltage parts inside which, if short-circuited, might cause damage to itself or other property. Place covers on the openings or take other precautions to make sure that no metal objects such as cutting bits or lead wire scraps go inside when installing and wiring.
Do not disassemble, repair, or modify the inverter. Failure to follow this guideline may result in injury.
6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Precautions for Safe Use
Precautions for Safe Use
Installation and Storage
Do not store or use the product in the following places.
• Locations subject to direct sunlight.
• Locations subject to ambient temperature exceeding the specifications.
• Locations subject to relative humidity exceeding the specifications.
• Locations subject to condensation due to severe temperature fluctuations.
• Locations subject to corrosive or flammable gases.
• Locations subject to exposure to combustibles.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to direct vibration or shock.
Transportation, Installation, and Wiring
• Do not drop or apply strong impact on the product. Doing so may result in damaged parts or malfunction.
• If you are transporting the product installed to the inverter, be sure to carry it by holding an inverter radiation fin.
• Do not remove the cover of the EtherCAT Communication Unit. Also, make sure that the unit fastening screws are tightened to the specified torque.
• Install a stop motion device to ensure safety. In particular, when it is set to continue operation when a communications error occurs, the inverter may not stop and damage to the equipment.
• Take sufficient shielding measures when using the product in the following locations. Not doing so may result in damage to the product.
Locations subject to static electricity or other forms of noise.
Locations subject to strong magnetic fields.
Locations close to power lines.
Operation and Adjustment
• Be sure to confirm the permissible range of motors and machines before operation because the inverter speed can be changed easily from low to high.
Maintenance and Inspection
• Be sure to confirm safety before conducting maintenance, inspection or parts replacement.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
7
Precautions for Correct Use
Precautions for Correct Use
Installation
Follow the inverter mounting direction restrictions.
Modbus-RTU communication
If this EtherCAT Communication Unit is installed, the inverter Modbus-RTU communication becomes disabled.
Product Disposal
Comply with the local ordinance and regulations when disposing of the product.
Warning Label Location
• After installing this EtherCAT Communication Unit to the inverter, warning labels are pasted on the product as shown in the following illustration.
• Be sure to follow the instructions.
(Notes) The overall appearance varies depending on the inverter capacity.
200V
3PHASE
RUN
STOP
RESET
RUN PWR
Hz
A
ALM
PRG
8
Warning Description
The warning description is written in English when it is shipped from the factory.
Affix the Japanese warning label included with the product if necessary.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Precautions for Correct Use
Inverter Version
This EtherCAT Communication Unit can be used with the inverter of unit version 1.1 or higher.
Make sure that the unit version of the inverter is 1.1 or higher.
The unit version of the inverter can be checked on the nameplate of the inverter.
(The unit version can not be checked on the CX-Drive.)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
9
Applicable Standards
Applicable Standards
EC Directives
EC Directives
EMC Directive
Applicable Standard
EN61800-3
Low Voltage Directive EN61800-5-1
Wiring Conforming to EMC Directives".
UL/cUL Standards
Standards
UL/cUL UL508c
Applicable Standard
Functional Safety
When the EtherCAT Communication Unit is mounted on the inverter unit, inverter’s conformance to the
Machinery Directive becomes invalid.
EtherCAT Conformance Test
This product is conformance tested.
10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Trademarks
Trademarks
• EtherCAT is a registered trademark of Beckhoff Automation GmbH (Germany). EtherCAT technology is protected by patents.
EtherCAT
is a registered trademark and patented technology, licensed by Beckhoff Automation
GmbH, Germany.
• Windows, Windows 98, Windows XP, Windows Vista and Windows 7 are registered trademarks of
Microsoft Corporation in the USA and other countries.
• Sysmac is a FA product of OMRON and a trademark or registered trademark of OMRON in Japan and other countries.
• CX-One is a registered trademark of OMRON's FA Integrated Tool Package.
• Other system names and product names that appear in this manual are the trademarks or registered trademarks of the relevant companies.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
11
Checking Before Unpacking
Checking Before Unpacking
Checking the Product
On delivery, be sure to check that the delivered product is the EtherCAT Communication Unit
3G3AX-MX2-ECT model that you ordered. Should you find any problems with the product, immediately contact your nearest local sales representative or OMRON sales office.
Checking the Nameplate
The nameplate is affixed to the back side of the product.
****** ********
Checking the Model
3 G 3 A X - M X 2 - E C T
EtherCAT Communications Unit
For 3G3MX2 series only
Checking the Accessories
Note that the Instruction manual and the Japanese warning label accessories are included with the
EtherCAT Communication Unit 3G3AX-MX2-ECT.
12
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Revision History
Revision History
A manual revision code appears as a suffix to the catalog number located at the top left of the front and lower right of the back covers.
Man.No.
I574-E1-02
01
02
Revision code Revision date
August 2010
July 2011
Revised symbols
Changes and revision pages
First printing
Added information on Machine Automation Controller NJ501-1x00 series.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
13
Related Manuals
Related Manuals
When operating this product, it is necessary to have information about the device you are connecting.
Please see the manuals below for related product information.
Model/Name
Multi-function Compact Inverter SYSDRIVE MX2 SERIES USER’S MANUAL
* Refer to the user’s manual of the Inverter for information on Inverter operation.
Manual number
I570
EtherCAT Master manual
Model/Name
Position Control Units CJ1W-NC281/NC481/NC881/NCF81/NC482/NC882 OPERATION MANUAL
Manual number
W487
NJ-series CPU Unit Software User's Manual
W501
* When using the Master Unit other than as specified above, refer to the manual (operation manual) for that Master
Unit.
14
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
About This Manual
About This Manual
This User's Manual consists of chapters listed below.
Understanding the following configuration ensures more effective use of the product.
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Appendix
Overview
This chapter explains the overview, features and specifications of the
EtherCAT Communication Unit.
This chapter explains information such as the mounting, wiring and setting methods for the EtherCAT Communication Unit.
This chapter explains the common slave specifications during EtherCAT communication, and about the ESIs, PDOs and SDOs.
This chapter describes the profiles that are used to control inverters.
This chapter explains about the CiA402 drive profile.
This chapter explains how to handle any errors that occur in the
EtherCAT Communication Unit.
The appendix provides a list of objects.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
15
CONTENTS
CONTENTS
Section 1 EtherCAT Network
Section 2 Starting a Sample System
16
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
CONTENTS
2-7 Communication Starting and Operation Checking with CJ1W-NCx82 Master ................ 2-20
2-8 Communication Starting and Operation Checking with NJ501-1x00 Master................... 2-22
Section 3 Common Slave Specifications
Section 4 Inverter Control
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
17
CONTENTS
Section 5 CiA402 Drive Profile
Section 6 Handling of Errors and Maintenance
Appendices
18
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
CONTENTS
Index
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
19
CONTENTS
20
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
EtherCAT Network
This chapter explains the overview and features of the EtherCAT Communication Unit and the EtherCAT network.
1-1 Overview of the EtherCAT Communication Unit . . . . . . . . . . . . . . . . . . . . . 1-2
1
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 - 1
1 EtherCAT Network
1-1 Overview of the EtherCAT
Communication Unit
The EtherCAT Communication Unit is an interface unit. When installed to a SYSDRIVE MX2-series multi-function compact inverter, it provides support for 100-Mbps EtherCAT.
Support for EtherCAT enables operating and stopping with high-speed communication, monitoring the operation status, and changing the various set values, and provides support for a wide range of applications.
1-1-1 Features of the EtherCAT Communication Unit
The EtherCAT Communication Unit has the features shown below.
Optimal functionality and ease of operation by standardizing specifications
As a Sysmac Device, you can use the MX2 Series EtherCAT Communication Unit together with the
NJ-series Machine Automation Controller and the Sysmac Studio Automation Software to achieve optimum functionality and ease of operation.
* Sysmac Device is a generic term for OMRON control devices such as an EtherCAT Slave, designed with unified communications specifications and user interface specifications.
Communication function as easy as I/O control
When the CJ1W-NCx82 Master Unit, or Machine Automation Contoroller NJ501-1x00 series is used, the basic control function, frequency setting function and output frequency monitor function are assigned to the process data. This means that the inverter can be controlled as easily as normal I/O control.
Supports the Velocity mode of CiA402
The Velocity mode of the CANopen drive profile (CiA402) enables common control that does not vary with the manufacturer.
PDO free format
When a communication master that supports the process data mapping is used, user can assign the inverter parameters to the process data.
This product can be used when the communication master is a Machine Automation Controller
NJ501-1x00 series.
Using together with slaves
EtherCAT supports connection with Servo Drives and digital I/O slaves,as well as Inverters,allowing flexible network building.
1 - 2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 EtherCAT Network
1-2 Overview of EtherCAT
Ethernet Control Automation Technology (EtherCAT) is a high-performance industrial network system based on Ethernet system and can realize faster and more efficient communications.
Each node achieves a short cycle time by transmitting Ethernet frames at high speed.
In addition, even though EtherCAT has its own communication protocol, it uses standard Ethernet technology in its physical layer. This provides a universal design feature because commercially available Ethernet cables can be used. Its effectiveness can be fully utilized not only in large control systems where high processing speed and system integration are required, but also in small to medium-sized systems.
1
1-2-1 Features of EtherCAT
EtherCAT has the features shown below.
Ultra high-speed communication of 100 Mbps
The I/O response time from the generation of the input signal to the transmission of the output signal is greatly reduced. The optimized Ethernet frame band is fully utilized and transfer is performed with the high-speed repeat method, which enables the highly efficient transmission of various types of data.
Use of standard Ethernet technology
EtherCAT is a global open network that uses standard Ethernet technology in its physical layer. This means that universally available parts can be used, such as commercially available Ethernet cables, connectors and tools.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 - 3
1 EtherCAT Network
1-2-2 EtherCAT System
In EtherCAT, data is not sent to each node in the network, but the Ethernet frame is made to pass through each node.
As the frame passes through, data is read and written at each node in the node's own area inside the frame in several nanoseconds.
The Ethernet frame that was sent by the EtherCAT master passes through all the EtherCAT slaves without stopping midway. Then, the frame is sent back by the final slave, and passes through all the slaves again before returning to the EtherCAT master.
This system ensures high-speed data transmission and realtime performance.
EtherCAT master
Slave
Data
OUT IN
Slave
Slave
• Reading of output data addressed to self
• Writing of input data
Ethernet frame
The periodic data exchange between the EtherCAT master and EtherCAT slaves is performed with the
"EtherCAT telegrams" that are stored directly inside the Ethernet frame.
Each "EtherCAT telegram" consists of an address, data and working counter (check bit) for one or more slaves.
If we compare an Ethernet frame to a train, EtherCAT telegrams can be considered as the carriages.
Ethernet frame
Ethernet header
Ethernet data (Max. of 1,498 bytes)
CRC
1 - 4
EtherCAT header
1st EtherCAT telegram
2nd EtherCAT telegram
1…n EtherCAT telegram
. . . . .
Datagram header
Data
Ethernet frame n th EtherCAT telegram
WKC
WKC: Working counter
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 EtherCAT Network
1-2-3 EtherCAT Communication Types
EtherCAT provides the following two types of communication functions.
Process data communications functions (PDO communications)
This is cyclic (I/O) communication.
The EtherCAT Master Unit maps logical process data space (cyclic data space) to each slave node, and realizes cyclic (I/O) communications with Slave Units.
EtherCAT master
Slave
Slave Slave
Slave
1
Ethernet frame
Ethernet header
EtherCAT header
1st EtherCAT telegram
2nd EtherCAT telegram
3rd EtherCAT telegram
Logic process data
• • •
CRC
Data a
Data b
Data c
Mailbox communication function (SDO communications)
This is message communication.
The EtherCAT Master Unit transmits commands to Slave Units, and the sSave Units return responses to the EtherCAT Master Unit.
The data below is sent and received.
• Read and write process data
• Slave settings
• Monitor slave state
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 - 5
1 EtherCAT Network
1-3 EtherCAT System Configuration
1-3-1 System Configuration
A typical system configuration is shown below.
CX-One FA Integrated
Tool Package
Programmable
Controller
SYSMAC CJ2 or
Position Control
Unit
CJ1W-NCx82 or
Sysmac Studio
Machine Automation Controller
NJ501-1x00 series
Communications cable
SYSDRIVE
3G3MX2 series
EtherCAT
Communication Unit
3G3AX-MX2-ECT
Other slaves
Servo Drive
Digital I/O
Analog I/O
Pulse input, etc
1 - 6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 EtherCAT Network
1-3-2 Overview of Component Equipment
The overview of each structural device is as follows.
EtherCAT master
Manages the EtherCAT network, and performs slave status monitoring and data exchange with the slaves.
EtherCAT slave
Receives data from the Master Unit and sends data to the Master Unit across the EtherCAT network. The sent and received data can be output externally, input from an external source, or used to perform various types of control for slave equipment.
The EtherCAT slave types shown below are available.
• Field network slaves
Slave devices that perform sequence control.
Examples: Digital I/O slaves, analog I/O slaves
• Motion network slaves
Slave devices that perform motion control.
Examples: Servo Units, Inverter Units
When this 3G3AX-MX2-ECT EtherCAT Communication Unit is installed on an inverter, it can be operated as a motion network slave inverter.
Configuration tool
Computer software for setting the EtherCAT network and each slave.
Communications cable
The communications cable that connects the Master Unit with the Slave Units, and the Slave Units to each other.
In an EtherCAT network, use an STP double-shield cable of Ethernet category 5 or higher.
EtherCAT Slave Information (ESI) file
A file in XML format that contains the information unique to the EtherCAT slave.
When this ESI file is loaded into the tool, it makes it easy to perform the various settings, such as the mapping of the EtherCAT slave's I/O memory.
If OMRON's Configuration Tool is used, the ESI file is used together with the Configuration Tool, so you need not worry about installing this file.
If a master by other manufacturer is connected, the ESI file must be loaded into a Configuration Tool supporting that master.
1
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
1 - 7
1 EtherCAT Network
1 - 8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Starting a Sample System
This chapter explains information such as the mounting, wiring and setting methods for the EtherCAT Communication Unit.
2
2-1 Part Names and Settings for the EtherCAT Communication Unit . . . . . . . 2-2
2-1-6 Connection between Communications Cables and Connectors . . . . . . . . . . . . 2-7
2-2 Basic Usage Procedures and Configuration Example . . . . . . . . . . . . . . . . 2-8
2-5 Mounting and Wiring for the EtherCAT Communication Unit . . . . . . . . . 2-13
2-5-4 Node Address Settings for the EtherCAT Communication Unit . . . . . . . . . . . 2-18
2-7 Communication Starting and Operation Checking with CJ1W-NCx82 Master 2-20
2-7-4 Checking the Inverter and EtherCAT Communication Unit . . . . . . . . . . . . . . . 2-21
2-8 Communication Starting and Operation Checking with NJ501-1x00 Master . . 2-22
2-8-4 Checking the Inverter and EtherCAT Communication Unit . . . . . . . . . . . . . . . 2-26
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 1
2 Starting a Sample System
2-1 Part Names and Settings for the
EtherCAT Communication Unit
2-1-1 Part Names
Status indicator
(L/A IN, L/A OUT,
RUN, ERR)
Rotary switches for node address setting (× 10, × 1)
Communications connector
(IN, OUT)
FG cable
2 - 2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-1-2 Status Indicator Names
The following table shows the EtherCAT status indicators and their meanings.
L/A IN
Name
L/A OUT
RUN
ERR
Color
Green
Green
Green
Red
State
OFF
ON
Flickering
OFF
ON
Flickering
OFF
Blinking
Single flash
ON
OFF
Blinking
Single flash
Double flash
Flickering
ON
Meaning
Link not established in physical layer
Link established in physical layer
In operation after establishing link
Link not established in physical layer
Link established in physical layer
In operation after establishing link
Init state
Pre-operational state
Safe-operational state
Operational state
No error
Communications setting error
Synchronization error or communications data error
Application WDT timeout
Boot error
PDI WDT timeout
Additional Information
The timing of each flashing state of indicator is as follows.
on
50 ms
Flickering off
Blinking on off
200 ms
200 ms
Single flash on off
200 ms
1000 ms
200 ms
Double flash on off
200 ms
200 ms
200 ms
1000 ms
2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 3
2 Starting a Sample System
2-1-3 Rotary Switches for Node Address Setting
These switches are used to set the node addresses of slaves in the EtherCAT network (decimal).
The 10s digit is set on the left rotary switch and the 1s digit is set on the right rotary switch.
The setting range is 00 to 99.
Node address setting
(× 1)
Node address setting
(× 10)
Note that the node address settings vary as shown below when the Host Controller is made by OMRON and when it is made by other manufacturers.
Set value for rotary switch
00
01 to 99
Set value for node address
OMRON Host Controller
Host Controller from another manufacturer
The Host Controller set value is used as the node address.
The rotary switch set value is used as the node address.
The Host Controller set value is used regardless of the rotary switch set value.
Precautions for Correct Use
• The set node address is read only once when the inverter power supply is turned ON.
If the setting is changed after the power supply is turned ON, the new setting will not be used until the next time that the power is turned ON.
• Do not change the setting on the rotary switches after the power supply has been turned ON.
• If node addresses overlap, an error occurs and the operation stops.
2 - 4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2-1-4 Communications Connector
An Ethernet twisted-pair cable is connected to this connector.
Communications connector (IN)
Communications connector (OUT)
2 Starting a Sample System
2
8
1
The EtherCAT connector specifications are shown below.
• Electrical characteristics : Conform to IEEE 802.3.
• Connector structure
• Terminal arrangement :
: RJ45 8-pin modular connector (conforms to ISO 8877)
Pin No.
1
2
3
6
7
4
5
8
Hood
Signal
Send data +
Send data
Receive data +
Not used
Not used
Receive data
Not used
Not used
Frame ground
Abbreviation
TD +
TD
RD+
RD
FG
Function
Send data +
Send data
Receive data +
Receive data
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 5
2 Starting a Sample System
2-1-5 Recommended Products
Connection cables and RJ45 connectors
For the communications cable, use a category 5 or higher straight type cable that is double-shielded with aluminum tape and braided shielding. Use a shielded connector of category 5 or higher.
Precautions for Correct Use
• The maximum cable length between nodes is 100 m. However, some cables are specified for less than 100 m. Generally, transmission performance of twisted wire condactor is lower than that of solid wire. Confirm the details with the cable manufacturer.
• Use the shielded-type RJ45 connectors. When selecting a connector, confirm if it can be used with the recommended cable. Confirm the following items: conductor size, conductor type
(solid wire or twisted wire), number of twisted pairs (2 or 4), outer diameter, etc.
Additional Information
If an Ethernet cable of category 5 or higher is used, communications will be possible even if the cable is not shielded. However, we recommend a cable with double, aluminum tape and braided shielding to ensure sufficient noise immunity.
2 - 6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-1-6 Connection between Communications Cables and Connectors
Connect the communications cable and the connector by wiring them straight as shown below.
Pin No.
1
2
3
Wire color
White-Green
Green
4
White-Orange
Blue
5 White-Blue
6
Orange
7
White-Brown
8
Brown
Connector hood
Shielded cable*
* Connect both ends of cable shielded wires to the connector hoods.
Wire color
White-Green
Green
White-Orange
Blue
White-Blue
Orange
White-Brown
Brown
Shielded cable*
Pin No.
1
2
3
4
5
6
7
8
Connector hood
Additional Information
There are 2 types of wiring standards for Ethernet cables: "T568A" and "T568B."
The figure above shows a wiring method conforming to the standard "T568A," but a wiring method conforming to the standard "T568B" can also be used.
2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 7
2 Starting a Sample System
2-2 Basic Usage Procedures and
Configuration Example
2-2-1 Basic Usage Procedures
The basic usage procedures are shown below. For details on settings and connections, refer to the manual for each Master Unit, and the slave manuals.
1 Master Unit setting
Master Unit setting
ESI file setting
CJ1W-NCx82
Master
Ref section 2-3-1.
NJ501-1x00
Master
Ref section 2-4-1.
Ref section 2-3-2.
Ref section 2-4-2.
2
Mounting and wiring of EtherCAT Communications Unit
Mounting of EtherCAT Communications Unit
Ref section 2-5-1.
Wiring of EtherCAT Communications Unit
Ref section 2-5-2.
Setting the node address of the EtherCAT
Communications Unit
Ref section 2-5-3.
3
Setting SYSDRIVE MX2 series
Setting RUN command
Setting frequency reference
Setting reset selection
Ref section 2-6-1.
Ref section 2-6-2.
Ref section 2-6-3.
4 Checking communication start/operation
Starting system
Checking operation
Ref section 2-7-1.
Ref section 2-8-1.
Network setup
Checking Master Unit
Ref section 2-7-2.
Ref section 2-8-2.
Checking Inverter and EtherCAT Communications Unit
Ref section 2-7-3.
Ref section 2-8-3.
Ref section 2-7-4.
Ref section 2-8-4.
Ref section 2-7-5.
Ref section 2-8-5.
2 - 8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-2-2 System Configuration Example
This chapter describes the usage procedures using the system configuration example shown below.
When configuring your actual system, select the units that are required for your system.
CJ1W-NCx82 Master
Master Unit : CJ2-series PLC + CJ1W-NCx82
Slave Unit (
2) : 3G3MX2-A2001 + 3G3AX-MX2-ECT ( 2 sets)
(Notes) This Communication Unit can be used with all the capacities in the SYSDRIVE MX2 series.
Used for data setting and monitoring
• Monitoring status
• File management, etc
PC
CX-Programmer
Power
Supply Unit
CJ2 series
CPU Unit
Master Unit Position Control Unit
(CJ1W-NCx82)
2
RS-232C port connection
Peripheral (USB) port connection
Slave Unit
First unit inverter
Node address 17
Slave Unit
2nd unit inverter
Node address 22
Communications cable 1
Length: 5 m
Communications cable 2
Length: 1 m
Refer to 2-3 CJ1W-NCx82 Master Setting on page 2-11 for details on Unit installation and setting
method.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 9
2 Starting a Sample System
NJ501-1x00 Master
Master Unit : Machine Automation Controller NJ501-1x00 series
Slave Unit (
2) : 3G3MX2-A2001 + 3G3AX-MX2-ECT ( 2 sets)
(Notes) This Communication Unit can be used with all the capacities in the SYSDRIVE MX2 series.
Used for data setting and monitoring
• Monitoring status
• File management, etc
PC
Sysmac Studio
Power
Supply Unit
Master Unit
Machine Automation Controller
NJ501-1x00 series
Peripheral (USB) port connection
Built-in EtherCAT port
Slave Unit
First unit inverter
Node address 1
Slave Unit
2nd unit inverter
Node address 2
Communications cable 1
Length: 5 m
Communications cable 2
Length: 1 m
Refer to 2-4 NJ501-1x00 Master Setting on page 2-12 for details on Unit installation and setting
method.
2 - 10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-3 CJ1W-NCx82 Master Setting
2-3-1 Mounting the CJ1W-NCx82
Connect the SYSMAC CJ2-series PLC and the CJ1W-NCx82 Master Unit by fitting their connectors together. For specific details on mounting onto the SYSMAC Unit and the control panel of the SYSMAC
Unit, refer to the User Manual for the SYSMAC CJ2 series.
2-3-2 CJ1W-NCx82 Setting
Perform the settings for the CJ1W-NCx82 Master Unit. For the setting method of each component, refer to the manual for the Master Unit.
For the setting tool, use CX-Programmer Ver. 9.2 or later.
2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 11
2 Starting a Sample System
2-4 NJ501-1x00 Master Setting
2-4-1 Mounting the NJ501-1x00
Perform configuration of the NJ501-1x00 Master rack. For the specific configuration method, refer to
NJ-series CPU Unit Software User’s Manual (Cat No.W501).
2-4-2 NJ501-1x00 Setting
Set the NJ501-1x00 Master. For the setting method for each part, refer to NJ-series CPU Unit Software
User’s Manual (Cat No.W501).
2 - 12
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-5 Mounting and Wiring for the
EtherCAT Communication Unit
Mount the EtherCAT Communication Unit onto the inverter. Before performing this procedure, turn OFF the main power supply of the inverter. Wait at least 10 minutes after the inverter's LED indicator lamp and charge indicator have turned OFF, and then start the procedure.
This Communication Unit can be used with the inverter of unit version 1.1 or higher.
Make sure that the unit version of the inverter is 1.1 or higher.
The unit version of the inverter can be checked on the nameplate of the inverter.
(The unit version can not be checked on the CX-Drive.)
2
2-5-1 Mounting the EtherCAT Communication Unit
Removing the optional board cover from the inverter front panel
1
Loosen the mounting screw (
1) from the optional board cover of the inverter front
panel.
2
Remove the optional board cover.
3G3M
X2
RUN
IVE
STOP
RESET
RUN
Hz
ALM
A
PWR
PRG
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 13
2 Starting a Sample System
Mounting the EtherCAT Communication Unit onto the inverter
1
Mount the EtherCAT Communication Unit onto the location where the inverter optional board cover that you removed was attached. Check that the connector is firmly connected.
3G3MX2
RUN
ER
STOP
RESET
RUN
PWR
Hz
A
ALM
PRG
(Notes) When the EtherCAT Communication Unit is mounted, the main circuit and control circuit terminals of the inverter are hidden. For this reason, be sure to wire the main circuit and control circuit terminals before mounting the EtherCAT Communication Unit.
2
Tighten the mounting screw of the EtherCAT Communication Unit.
Tighten the bottom right screw of the EtherCAT Communication Unit with the specified torque
(46 N•cm, 4.7 kgf•cm).
2 - 14
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
Connecting the ground cable of the EtherCAT Communication Unit
1
Ground the FG cable of the EtherCAT Communication Unit.
Cut the ground wire of the unit's FG cable to an appropriate length and ground it to the closest possible ground location. Also refer to the inverter manual.
3G3MX2
RUN
IVE
STOP
RESE
T
RUN
PWR
Hz
A
ALM
PRG
2
2-5-2 Wiring the EtherCAT Communication Unit
Perform the wiring for the communications cables.
Preparing the communications cables
Determine the number and length of communications cables that are appropriate for your system configuration.
Each communications cable between the nodes (and between the master and the nodes) must be no longer than 100 m.
In the system configuration example used in this chapter, a cable of 5 m is prepared for communications cable 1, and a cable of 1 m is prepared for communications cable 2.Connect an RJ45 connector to both ends of the communications cable by wiring them straight. Connect both ends of the shielded wires of the cable to the hoods.
For details on preparing the cables, refer to 2-1-6 Connection between Communications Cables and
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 15
2 Starting a Sample System
Wiring the communications cables
FG cable
2 - 16
Master Unit side
Slave Unit side
Securely connect the EtherCAT communication cable connector to the EtherCAT Communication Unit by inserting the connector all the way until it clicks.
Connect the communication cable from the EtherCAT master side to the communication connector IN of the Communication Unit.
Connect the communication connector OUT to the communication connector IN of the next EtherCAT slave.
Do not connect the communication connector OUT of the last EtherCAT slave.
Data will not be communicated correctly if the input/output are connected in reverse.
In the system configuration example used in this chapter, the connectors below are connected with the communications cables.
Communications cable 1
Communications cable 2
Connecting from
Master Unit
1st inverter OUT
(Notes) Do not connect anything to 2nd inverter OUT.
1st inverter IN
2nd inverter IN
Connecting to
If a slave other than this product is used in your system configuration, set the unit in the same way by referring to its User Manual.
Precautions when constructing the network
• When constructing an EtherCAT network, take sufficient safety measures according to the standards.
We recommend that specialized constructors familiar with the safety measures and standards be requested to perform the construction.
• Do not install EtherCAT network devices near devices generating noise.
If there is no choice but to install them down in an environment with a high level of noise, be sure to take measures against the noise, such as covering each device in metal cases.
Precautions when installing communications cables
• To connect a cable to the communications connector of a device, insert it securely until the connector of the communications cable is locked.
• Install and wire the communications cables separately from high-voltage electrical power lines.
• Do not install the cables near devices generating noise.
• Do not install the cables in high-temperature and high-humidity environments.
• Use the cables in locations without powder dust or oil mist.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-5-3 Wiring Conforming to EMC Directives
To conform to the EMC directives (EN61800-3), conduct the wiring work for the EtherCAT
Communication Unit, so that it meets the wiring conditions described in this section. These conditions are for conformance of products to the EMC directives when an EtherCAT Communication Unit is installed on a SYSDRIVE MX2-series inverter. The installation and wiring conditions, however, may be affected by the devices that are connected and wiring of the system where the EtherCAT
Communication Unit is installed. It is necessary to conform to the EMC directives as an overall system.
This section describes only the parts related to the addition of the EtherCAT Communication Unit.
Follow the instructions in the inverter manual for the inverter installation conditions, such as the power supply line wiring, filter installation, and motor wiring clamps.
2
Wiring the communications cables
Install the 3 clamp cores shown below near the communications connectors of the communications cables that are connected to the communications connector (IN) and the communications connector
(OUT). (If the communications cable on the OUT side is not connected, install them for the IN side only.)
Symbol
FC1, FC2, FC3 Clamp core
Name Manufacturer
NEC TOKIN
Model
ESD-SR-160
Wiring the FG cable
Install the FG cable with the shortest possible wiring.
200V
3PHASE
RUN
STOP
RESET
RUN PWR
Hz
A
ALM
PRG
FC1
FC3
FC2
FC1
FC2
FC3
FG cable
Communications cable
(IN)
Communications cable
(OUT)
(Notes) The overall mounting appearance varies depending on the inverter capacity. Do not squeeze the FG cable into the EtherCAT Communication Unit.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 17
2 Starting a Sample System
2-5-4 Node Address Settings for the EtherCAT Communication Unit
Node address settings
Set the rotary switches of the EtherCAT Communication Unit to determine the node address.
In the system configuration example used in this chapter, the settings are as follows.
1st unit
2nd unit
Inverter
Node address
Rotary switch x 10
Rotary switch x 1
Node address
Rotary switch x 10
Rotary switch x 1
CJ1W-NCx82 Master
17
Set to the 1 position.
Set to the 7 position.
22
Set to the 2 position.
Set to the 2 position.
NJ501-1x00 Master
1
Set to the 0 position.
Set to the 1 position.
2
Set to the 0 position.
Set to the 2 position.
Notes on setting are provided below for each Master Unit.
<CJ1W-NCx82 Master>
1 The EtherCAT Communication Unit uses input and output areas for 5 node addresses.
For this reason, when using the inverter with a fixed allocation, set 5 or larger number to the node address of the next unit.
2 Node addresses can be set in a range of 17 to 80. Make sure the node addresses set for the Unit do not overlap with other slave.
3 For the restrictions related to CJ1W-NCx82 Master, refer to Position Control Units
CJ1W-NC281/NC481/NC881/NCF81/NC482/NC882 OPERATION MANUAL (Cat No.W487).
<NJ501-1x00 Master>
1 Node addresses can be set in a range of 1 to 99. Make sure the node addresses set for the Unit do not overlap with other slave.
2 Unlike with the CJ1W-NCx82 master, the node address of the next unit can be set without intervals.
3 For the restrictions related to your NJ501-1x00, refer to NJ-series CPU Unit Software User’s Manual
(Cat No.W501).
(Notes) If a slave other than this product is also connected to the same network, set the unit by referring to its User Manual. In such cases, check that the node addresses do not overlap with other units.
2 - 18
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-6 SYSDRIVE MX2 Series Settings
To perform control from the Communication Unit, the parameter settings must be changed from the front panel digital operator of the inverter.
In this procedure, the inverter power supply must be turned ON. When the power supply is turned ON, the inverter may operate in unintended way. Check the condition of the wiring and system carefully before starting the procedure.
Refer to the User Manual (Cat No.I570) for the SYSDRIVE MX2-series inverter for details on operating the inverter parameter settings and for the meaning of the parameter values.
2
2-6-1 RUN Command Setting
Change the control method for the RUN command.
Parameter No.
A002
Function name
RUN Command Selection 1
Data
04 (Optional boad)
Default value
02 (Digital Operator)
2-6-2 Frequency Reference Setting
Change the control method for the frequency reference.
Parameter No.
A001
Function name Data
Frequency Reference Selection 1 04 (Optional boad)
Default value
02 (Digital Operator)
2-6-3 Reset Selection Setting
Set the operation of the reset signal.
Parameter No.
C102
Function name
Reset Selection
Data
03 (Trip reset only)
* If parameter C102 is not displayed, first set parameter b037 to 01.
Default value
00 (Trip reset at power-ON)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 19
2 Starting a Sample System
2-7 Communication Starting and Operation
Checking with CJ1W-NCx82 Master
After completing the settings and wiring, turn ON the power and check that the communication starts.
The inverter power supply must be turned ON to set the inverter. When the power supply is turned ON, the inverter may operate in unintended way. Check the condition of the wiring and system carefully before starting the operation.
2-7-1 Starting the System
Check the condition of the wiring and system carefully, and then turn ON the power supply for all the inverters and PLC. It does not matter whether the inverter or PLC power supply is turned ON first.
However, an error occurs unless the power supply for all the inverters is turned ON within a certain time
(All Registered Slave Participation Standby Time parameter of CJ1W-NCx82, default value is 10 seconds) after turning ON the PLC power supply.
2-7-2 Network Setup
Firstly,enter the network settings. Until the settings are performed, the indicators show "Initial processing status" in the table below for both the Master Unit and the EtherCAT Communication Unit.
Start CX-Programmer, and double-click the target CJ1W-NCx82 in the I/O table to start the support tool. When the support tool starts, the Network Auto Setup dialog box is displayed. Perform the network setup in accordance with the dialog box instructions. If the Network Auto Setup dialog box is not displayed automatically, start the dialog box by selecting Network Auto Setup from Network in the support tool menu.
For details on network setting, refer to Position Control Units
CJ1W-NC281/NC481/NC881/NCF81/NC482/NC882 OPERATION MANUAL (Cat No.W487).
2-7-3 Checking the Master Unit
Check that the Master Unit has transitioned to normal operation from initial processing.
The indicators of the CJ1W-NCx82 make it easy to check the changes in status.
Initial processing
Normal operation
7-segment display
Flashing
“00”
RUN
ON
ON
ERC
OFF
OFF
ERH
OFF
OFF
ECAT
RUN
OFF
ON
ECAT
ERR
OFF
OFF
L/A
ON
Flashing
For details, refer to Position Control Units CJ1W-NC281/NC481/NC881/NCF81/NC482/NC882
OPERATION MANUAL (Cat No.W487).
2 - 20
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2-7-4 Checking the Inverter and EtherCAT Communication Unit
Check the POWER indicator and other indications of the inverter to confirm that power is being supplied to the inverter.
Check the status indicators of the EtherCAT Communication Unit to see that the status has changed to normal operation from initial processing.
1st unit
Initial processing
Normal operation
L/A IN
ON
Flashing
L/A OUT
ON
Flashing
RUN
OFF
ON
ERR
OFF
OFF
2
2nd unit
Initial processing
Normal operation
L/A IN
ON
Flashing
L/A OUT
OFF
OFF
RUN
OFF
ON
ERR
OFF
OFF
* If three or more units are connected, the status LEDs behave in the same way as the LEDs on the first unit, except for the last unit.
L/A OUT on the last unit is always unlit.
2-7-5 Checking the Operation
Execute the PLC control program and check that the operation is normal.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 21
2 Starting a Sample System
2-8 Communication Starting and Operation
Checking with NJ501-1x00 Master
After completing the settings and wiring, turn ON the power and check that the communication starts.
The inverter power supply must be turned ON to set the inverter. When the power supply is turned ON, the inverter may operate in unintended way. Check the condition of the wiring and system carefully before starting the operation.
2-8-1 Starting the System
Check the condition of the wiring and system carefully, and then turn ON the power supply for all the inverters and NJ501-1x00 Master. It does not matter whether the inverter or NJ501-1x00 Master power supply is turned ON first. However, an error occurs unless the power supply for all the inverters is turned ON within a certain time (Wait time for slave startup parameter of NJ501-1x00, default value is
30 seconds) after turning ON the NJ501-1x00 power supply.
2-8-2 Network Setup
Firstly, enter the network settings. How to set the network is explained below by taking the "MX2-ECT sample" project as an example.
1
Starting the Sysmac Studio
<Project Window>
Click the New Project Button, enter MX2-ECT sample under the Project name, and then click the Create Button.
2 - 22
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
2
Registering an EtherCAT slave
<Controller Configurations and Setup Pane>
Right-click EtherCAT under the Configurations and Setup menu on the left side of the pane, and open the Edit Pane.
When a group of items that can be registered as an EtherCAT slave appears on the right side of the pane, select Frequency Inverter.
From the slave list on the right side of the pane, drag and drop 3G3AX-MX2-ECT onto Master at the center of the pane, and the Unit will be registered as an EtherCAT slave.
2
drug & drop
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 23
2 Starting a Sample System
<Pane when 2 inverters are registered>
The pane after 2 inverters are registered is shown below.
3
Registering an IO map
Right-click I/O Map under the Configurations and Setup menu on the left side of the pane, and open the Edit Pane.
With the NJ501-1x00 Master, data used in the control algorithms is treated as a set of variables.
If you want to assign a variable to each object that controls the inverter and use the assigned variables in the control algorithms, define the variables on this pane.
<I/O Map Pane>
2 - 24
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 Starting a Sample System
4
Building a program
Build the project program you created, so as to convert it to the format supported by the
NJ501-1x00 Master.
Select Build Controller from the Project Menu.
Confirm that the program that is built is with no errors.
5
Synchronizing with the CPU Unit
Transfer the program and settings created in Sysmac Studio to the NJ501-1x00 Master.
Go online and select Synchronization from the Controller Menu.
Click Transfer To Controller to transfer the program data.
When the transfer is completed successfully, the RUN LED indicator on the inverter turns ON.
The inverter is now ready.
<Synchronization Pane>
2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2 - 25
2 Starting a Sample System
2-8-3 Checking the NJ501-1x00 Master
Check that the NJ501-1x00 Master is operating normally in the RUN Mode.
Front LED indicators
Status of NJ501-1x00 Master
PWR (Green)
RUN (Green)
ERROR (Red)
Operating normally
User program is running User program is stopped
ON
ON
OFF
ON
OFF
OFF
2-8-4 Checking the Inverter and EtherCAT Communication Unit
Check the POWER indicator and other indications of the inverter to confirm that power is being supplied to the inverter.
Check the status indicators of the EtherCAT Communication Unit to see that the status has changed to normal operation from initial processing.
1st unit
Initial processing
Normal operation
L/A IN
ON
Flashing
L/A OUT
ON
Flashing
RUN
OFF
ON
ERR
OFF
OFF
2nd unit
Initial processing
Normal operation
L/A IN
ON
Flashing
L/A OUT
OFF
OFF
RUN
OFF
ON
ERR
OFF
OFF
* If three or more units are connected, the status LEDs behave in the same way as the LEDs on the first unit, except for the last unit.
L/A OUT on the last unit is always unlit.
2-8-5 Checking the Operation
Execute the NJ501-1x00 Master control program and check that the operation is normal.
2 - 26
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Common Slave Specifications
This chapter explains the common slave specifications during EtherCAT communication, and about the PDOs and SDOs.
3-1 Structure of CANopen over EtherCAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 - 1
3 Common Slave Specifications
3-1 Structure of CANopen over EtherCAT
The figure below shows the structure of CANopen over EtherCAT (CoE).
Inverter
Application layer
Communications status transitions
Inverter application
SDO
(Mailbox)
Object dictionary
PDO mapping
PDO (Cyclic)
Register Mailbox
SyncManager
EtherCAT data link layer
EtherCAT physical layer
Process data
FMMU
Normally, multiple protocols can be transmitted using EtherCAT. In the EtherCAT Communication Unit for MX2 inverters, the CANopen communication profile (CiA 301) that is popular in Europe, and the drive profile (CiA 402) are used.
The object dictionary in the application layer contains parameters and application data as well as information on the PDO mapping between the process data and inverter application.
The process data object (PDO) consists of objects in the object dictionary that can be mapped to the
PDO. The contents of the process data are defined by the PDO mapping.
Process data communications cyclically reads and writes the PDO. Mailbox communications (SDO) uses asynchronous message communications where all objects in the object dictionary can be read and written.
3 - 2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 Common Slave Specifications
3-2 Communications Status Transitions
The EtherCAT State Machine (ESM) of the EtherCAT slave is controlled by the EtherCAT Master.
Initialization
Pre-operational
Safe-operational
Operational
State
SDO communications
Initialization (Init) Not supported
Pre-Operational
(Pre-Op)
Safe-Operational
(Safe-Op)
Operational (Op)
Supported
Supported
Supported
PDO reception
PDO transmission
Details
Not supported Not supported Communications are being initialized.
Communications are not possible.
Not supported Not supported Only mailbox communications are possible in this state. This state is entered after initialization has been completed. It is used to initialize network settings.
Not supported Supported In this state, PDO transmissions are possible in addition to mailbox communications. Cyclic communications can be used to send information such as status from the inverter.
Supported Supported This is a normal operating state. Cyclic communications can be used to control the motor.
3
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 - 3
3 Common Slave Specifications
3-3 Process Data Objects (PDO)
3-3-1 Outline
The process data objects (PDOs) are used to transfer data during cyclic communications in realtime.
There are two types of PDOs: reception PDOs (RxPDOs) which receive data from the controller, and transmission PDOs (TxPDOs) which send statuses from the inverter to the Host Controller.
RxPDO
Operation command, target value, etc
Host
Controller
Inverter
TxPDO
Operation status, present value, etc
The EtherCAT application layer can hold multiple objects to enable the transferring of inverter process data. The contents of the process data are described in the PDO mapping object and the Sync
Manager PDO assignment object.
3-3-2 PDO Mapping Settings
The PDO mapping indicates the mapping for application objects (realtime process data) between the object dictionary and PDO.
The number of mapped objects is described in sub-index 00 hex of the mapping table. In this mapping table, 1600 to 17FF hex are for RxPDOs and 1A00 to 1BFF hex are for TxPDOs.
The following table is an example of PDO mapping.
Object dictionary
Index Sub
1ZZZ hex
1ZZZ hex
1ZZZ hex
01 hex
02 hex
03 hex
Object contents
6TTT hex TT hex
6UUU hex UU hex
YYYY hex YY hex
8
8
16
PDO length: 32 bits
PDO_1
Object A Object B Object D
6TTT hex
6UUU hex
6VVV hex
6YYY hex
6ZZZ hex
TT hex
UU hex
VV hex
YY hex
ZZ hex
Object A
Object B
Object C
Object D
Object E
3 - 4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 Common Slave Specifications
3-3-3 Sync Manager PDO Assignment Settings
A Sync Manager channel consists of several PDOs. The Sync Manager PDO assignment objects describe how these PDOs are related to the Sync Manager.
The number of PDOs is given in sub-index 00 hex of the Sync Manager PDO assignment table. In this table, index 1C12 hex is for RxPDOs and 1C13 hex is for TxPDOs.
The following table is an example of Sync Manager PDO mapping.
Object dictionary
Index
1C1Z hex
Sub
1 hex
1C1Z hex
1C1Z hex
2 hex
3 hex
Object contents
1A00 hex
1A01 hex
1A03 hex
Sync Manager entity Z
PDO A PDO B PDO D
3
1A00 hex
1A01 hex
1A02 hex
1A03 hex
1A04 hex
1A05 hex
1A06 hex
PDO A
PDO B
PDO C
PDO D
PDO E
PDO F
PDO G
3-3-4 Fixed PDO Mapping
This section describes the contents of fixed PDO mapping for MX2 inverters. The contents of fixed
PDOs cannot be changed.
PDO mapping for speed control (independent profile)
RxPDO
(1701 hex)
TxPDO
(1B01 hex)
5000 hex Command
5010 hex Frequency reference
5100 hex Status
5110 hex Output frequency monitor
PDO mapping for speed control (CiA402 profile)
RxPDO
(1700 hex)
TxPDO
(1B00 hex)
6040 hex Controlword
6042 hex vl target velocity
6041 hex Statusword
6043 hex vl velocity demand
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 - 5
3 Common Slave Specifications
3-4 Service Data Objects (SDO)
3-4-1 Outline
The EtherCAT Communication Unit for MX2 inverters supports SDO communications as message communications. SDO communications are used for setting objects and monitoring the status of MX2 inverters. Objects can be set and the status monitored by reading and writing data to the entries in the object dictionary of the Host Controller.
3-4-2 Abort Codes
The following table lists the abort codes for when an SDO communications error occurs.
Value
05030000 hex
05040000 hex
05040001 hex
05040005 hex
06010000 hex
06010001 hex
06010002 hex
06020000 hex
06040041 hex
06040042 hex
06040043 hex
06040047 hex
06060000 hex
06070010 hex
06070012 hex
06070013 hex
06090011 hex
06090030 hex
06090031 hex
06090032 hex
06090036 hex
08000000 hex
08000020 hex
08000021 hex
08000022 hex
08000023 hex
Meaning
Toggle bit not changed
SDO protocol timeout
Client/Server command specifier not valid or unknown
Out of memory
Unsupported access to an object
Attempt to read a write only object
Attempt to write to a read only object
The object does not exist in the object directory
The object can not be mapped into the PDO.
The number and length of the objects to be mapped would exceed the
PDO length.
General parameter incompatibility reason
General internal incompatibility in the device
Access failed due to a hardware error
Data type does not match, length of service parameter does not match
Data type does not match, length of service parameter too high
Data type does not match, length of service parameter too low
Subindex does not exist
Value range of parameter exceeded (only for write access)
Value of parameter written too high
Value of parameter written too low
Maximum value is less than minimum value
General error
Data cannot be transferred or stored to the application
Data cannot be transferred or stored to the application because of local control
Data cannot be transferred or stored to the application because of the present device state
Object dictionary dynamic generation fails or no object dictionary is present
3 - 6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 Common Slave Specifications
3-5 Emergency Messages
3-5-1 Outline
When an error or warning occurs in an MX2 inverter, an emergency message is sent to the master using mailbox communications. An emergency message is not sent for a communications error.
You can select whether to send emergency messages by setting Diagnosis history (10F3 hex).
The default setting is to send emergency messages. (10F3 hex, sub-index: 05 hex (Flags) = 1)
Set the sub-index 05 hex (Flags) in object 10F3 hex to 0 every time the power is turned ON to disable the sending of emergency messages.
Emergency messages consist of 8 bytes of data.
Byte
Meaning
0
Error code
1 2
Error register
(Object 1001 hex)
3 4 5 6 7
Manufacturer specific error field
(reserved)
3
3-5-2 Error Code List
Error code
5300 hex
Meaning
Error in the option and inverter connection
6341 hex
6331 hex
FF00 hex
FF01 hex
PDO setting error
EEPROM data error
A warning occurred for the inverter
A trip occurred for the inverter
Possible correction
• Check that the Communication Unit is mounted correctly onto the inverter.
• The Communication Unit is faulty. Replace the
Communication Unit.
• If a trip reset was performed with the inverter, set the inverter C102 to 3: Trip reset only, and turn the power supply OFF and ON again.
• If an initialization mode change was performed with the inverter, turn the inverter power supply OFF and ON again.
A set value in PDO mapping is invalid. Check the value of object 5200 and the AL Status code, and then review the PDO assignment settings.
• An error was detected in data inside EEPROM when the power supply was turned ON. Replace the Communication
Unit.
• The Diagnosis history cannot be saved because the
EEPROM has reached the end of its service life. There is no effect on operations, but if you want to use the Diagnosis history, replace the unit.
Eliminate the cause and turn on the bit 7: Fault reset of 5000 hex (Command) or 6040 hex (Controlword).
Eliminate the cause and turn on the bit 7: Fault reset of 5000 hex (Command) or 6040 hex (Controlword).
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 - 7
3 Common Slave Specifications
3-6 Sysmac Device Functions
The control device products designed according to the unified communication specifications and user interface specifications applicable to OMRON's control devices are called Sysmac devices.
In addition, the functions of these devices are called Sysmac device functions.
The following explains the functions available when this product is combined with the Machine
Automation Controller including NJ Series or automation software.
The EtherCAT Communication Unit 3G3AX-MX2-ECT is a Sysmac device that, if the unit version is 1.1 or later, supports Sysmac device functions.
Sysmac error status
Errors generated by slaves are systematically defined in Sysmac devices. When Sysmac Studio is used, error messages and remedial actions can be checked by following common operating procedures.
Errors are notified by 2002 hex-01 hex: Sysmac Error status. If errors detected by the EtherCAT
Communication Unit are to be displayed in Sysmac Studio, 2002 hex-01 hex: Sysmac Error status must be mapped to the PDO. By default, Sysmac Studio automatically maps 2002 hex-01 hex: Sysmac Error status to the PDO by allocation of 1BFF hex : 512th transmit PDO Mapping.
Additional Information
• For the Sysmac error status, refer to 5-6-1 Manufacturer Specific Objects on page 5-16.
• For the errors displayed in Sysmac Studio, refer to A-5 Sysmac Error Status Codes on page
Saving the node address settings
When the node address switch is set to 00, it means that the system is in the software setting mode and the node address values set by Sysmac Studio become effective.
In the software setting mode, execute Write Slave Node Address on the EtherCAT Edit Screen of
Sysmac Studio to save the set values to the nonvolatile memory on the EtherCAT Communication Unit side.
3 - 8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 Common Slave Specifications
Software setting
The value saved in the non-volatile memory on the slave side as SII (Slave Information Interface) information becomes the node address.
EtherCAT Master
(4)
(5)
EtherCAT
Slave Controller
(2)
Nonvolatile memory
SII
Register: 0010 hex
Register: 0012 hex
(3)
(1)
Node address switch
EtherCAT Slave
(EtherCAT Communication Unit)
(1) While the power is off, set the node address
switches to 00.
(2) Write the set value of node address to SII on
the slave, from the master side.
(3) When the slave power is turned on, the set
value of node address is reflected in the register
address 0012 hex by the software.
(4) The EtherCAT master reads the set value at
the register address 0012 hex.
(5) The EtherCAT master writes the value at the
address 0012 hex to the address 0010 hex as
the node address.
Node address switch setting
The value set by the node address switches on the slave becomes the node address.
EtherCAT Master
3
(3) (4)
EtherCAT
Slave Controller
Nonvolatile memory
SII
Register: 0010 hex
Register: 0012 hex
(2)
(1)
Node address switch
EtherCAT Slave
(EtherCAT Communication Unit)
(1) While the power is off, set the node address
switches.
(2) When the slave power is turned on, the value
set by the node address switches is reflected
in the register address 0012 hex.
(3) The EtherCAT master reads the set value at
the register address 0012 hex.
(4) The EtherCAT master writes the value at the
address 0012 hex to the address 0010 hex as
the node address.
Displaying the serial number
The serial number saved in the nonvolatile memory on the Servo Drive side is displayed under 1018 hex-04 hex: Serial number. With controllers conforming to the Sysmac device functions, the network configuration can be checked using this serial number.
To check the network configuration, set Setting = Actual device under Serial Number Check Method on the EtherCAT Edit Screen of Sysmac Studio.
If the specified criteria cannot be met, a Network Configuration Verification Error will occur.
Additional Information
Since replacement of slave device can be detected, all slave parameters will be set without fail.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3 - 9
3 Common Slave Specifications
Conforming to the ESI Specification (ETG.2000 S (R) V1.0.1)
The ESI Specification is a specification document defining the items described in the EtherCAT Slave
Information (ESI) file.
With controllers conforming to the Sysmac device functions, optional functions defined in the ESI
Specification can be used to specify backup parameters on the slave side.
Specified backup parameters on the slave side can be backed up and restored by Sysmac Studio.
SII data check
SII (Slave Information Interface) represents configuration information specific to each EtherCAT slave, which is written to the nonvolatile memory in the EtherCAT slave.
With Sysmac device EtherCAT slaves, SII information is checked on the slave side.
If the slave cannot operated based on the SII information written, a SII verification error will occur. If the error still occurs after turning the power OFF and then ON again, contact your OMRON sales representative.
Precautions for Correct Use
Do not modify the SII information using a setting tool by other manufacturer.
3 - 10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Inverter Control
This chapter describes the profiles that are used to control inverters.
4-6 Trial operation via EtherCAT Communication Unit . . . . . . . . . . . . . . . . . . 4-17
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 1
4 Inverter Control
4-1 Outline
This section describes how to use the EtherCAT Communication Unit to control the inverter.
4-1-1 Function Selection
Inverter control is performed by allocating a function object to a PDO.
These functions are limited depending on the combination with the used Master Unit.
Type
Allocation when using CJ1W-NCx82
Independent profile
CiA402 drive profile
PDO free format
Details
The fixed allocation when connected with OMRON's CJ1W-NCx82.
OMRON's independently-developed function object.
Enables easy control of the inverter.
A function object that conforms to the CiA402 drive profile.
Objects can be freely allocated, including the above objects.
*1 When using a Master Unit from another manufacturer, check yourself whether it supports the above functions.
*2 If you are using your NJ501-1x00 as the master, refer to the explanation on allocation in PDO free format.
4-1-2 Object Mapping
Allocate the object that you want to use to a PDO with the procedure below.
1
Allocate the object to a PDO.
2
Assign the PDO to Sync Manager.
Use the tool of the Master Unit for allocation.
4 - 2
PDO Mapping
This unit uses the PDOs below to allocate the objects.
RxPDO (master to slave)
PDO
1600 hex to 1604 hex
(1st receive PDO Mapping to
5th receive PDO Mapping)
1700 hex
(257th receive PDO Mapping)
1701 hex
(258th receive PDO Mapping)
Details
Objects can be freely allocated. Up to 2 objects (maximum size of 4 bytes) can be allocated to each PDO.
The fixed allocation that conforms to the CiA402 drive profile.
The fixed allocation of the independent profile.
TxPDO (slave to master)
PDO
1A00 to 1A04 hex
(1st transmit PDO Mapping to
5th transmit PDO Mapping)
1B00 hex
(257th transmit PDO Mapping)
1B01 hex
(258th transmit PDO Mapping)
1BFF hex
(512th transmit PDO Mapping)
Details
Objects can be freely allocated. Up to 2 objects (maximum size of 4 bytes) can be allocated to each PDO.
The fixed allocation that conforms to the CiA402 drive profile.
The fixed allocation of the independent profile.
By default, Sysmac Studio assigns 2002 hex: Sysmac error status.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Sync ManagerAssignment
In this unit, specify the PDOs that you want to use as follows.
Sync Manager
Sync Manager PDO assignment
1C12 hex
1C13 hex
Allocate RxPDO (master to slave).
Up to 5 RxPDOs can be allocated.
Allocate TxPDO (slave to master).
Up to 5 TxPDOs can be allocated.
Details
4 Inverter Control
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 3
4 Inverter Control
4-2 Control with the Position Control Unit
This section describes how to connect the OMRON CJ1W-NCx82 and the EtherCAT Communication
Unit to control the inverter.
4-2-1 Inverter Setting
Set the inverter parameters as follows.
Parameter
A001 Frequency Reference Selection 1
A002 RUN Command Selection 1
C102 Reset Selection
P012 Simple Position Control Selection
Description
04: Optional board
04: Optional board
03: Trip reset only
00: Simple position control disabled
02: Simple position control enabled
* Select speed control or Simple position control by setting inverter parameter P012: Simple Position Control
Selection.
To use the Simple position control function, set the required parameters in accordance with the inverter manual.
* If parameter C102 is not displayed, set b037 to 01.
* Do not use motor 2 control of the inverter. The motor 1 control only can be used.
4-2-2 Object Mapping
The object that will be used is allocated with the fixed settings below.
PDO mapping
1701 hex
1600 hex
1601 hex
1B01 hex
1A00 hex
1A01 hex
PDO Description
5000 (Command)
5010 (Frequency reference)
4016.6B (P060 Multi-step position command 0)
301F.40 (Multi-function input (Modbus communication register 1F01 hex coil data 0))
5100 (Status)
5110 (Output frequency monitor)
4010.59 (d030 Current position monitor)
3010.29 (d006 Multi-function output monitor)
Sync Manager assignment
Sync Manager PDO assignment
1C12 hex
1C13 hex
Description
1701 (Fixed allocation of the independent profile)
1600 (Setting as above)
1601 (Setting as above)
1B00 (Fixed allocation of the independent profile)
1A00 (Setting as above)
1A01 (Setting as above)
4 - 4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 Inverter Control
4-2-3 Control Method
Control the inverter by operating the fixed mapping PDOs.
Control information (master to slave) n n + 1 n + 2 n + 3 n + 4
Word
Control command
Frequency reference
Multi-step position command 0 (LSW)
Multi-step position command 0 (MSW)
Multi-function input
Meaning
(Notes) n: Start address of the remote I/O output relay area that is assigned to the unit.
Status information (slave to master)
Word Meaning
m m + 1 m + 2 m + 3 m + 4
Status
Output frequency monitor
Current position monitor (LSW)
Current position monitor (MSW)
Multi-function output monitor
(Notes) m: Start address of the remote I/O input relay area that is assigned to the unit.
Bit and data information
Command
The bit data for the command is shown below.
7
1 0
Bit
0
1
Name
Forward/stop *1
Reverse/stop *1
0: Stop
1: Forward command
0: Stop
1: Reverse command
Meaning
7
-
Fault reset
(Reserved)
: Resets an error or trip for the unit or inverter.
The reserved area. Set 0.
*1 Operates as a start bit when Simple position control is enabled.
Frequency reference
Name
Frequency reference
Meaning
Specify the reference frequency in increments of 0.01 Hz. When a value is set that exceeds the maximum frequency, operation is performed at the maximum frequency.
Setting range: 0 to maximum frequency
Multi-step Position command 0
Name
Multi-step position command 0
Meaning
Specify the value of inverter parameter P060: Multi-step position command 0. Values outside the range are not applied and operation is performed with the previous value.
Setting range: Position range setting (reverse side) to position range setting (forward side)
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 5
4 Inverter Control
4 - 6
Multi-function input
The bit data for the multi-function input information is shown below.
13 12 11 10 9 8 7
10
11
12
13
Bit
7
8
9
Name
Multi-function input 1
Multi-function input 2
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 7
(Reserved)
0: OFF
1: ON
The reserved area. Set 0.
Meaning
* Use by assigning a function to the multi-function input with the inverter parameters.
Status
The bit data for the status information is shown below.
15
12
9
7
3
1 0
Bit
0
1
3
7
9
12
15
Forward operation in progress
Reverse operation in progress
Fault
Warning
Remote
Name
Frequency matching
Connection error between the
Optional Unit and inverter
(Reserved)
Meaning
0: Stopped/during reverse operation
1: During forward operation
0: Stopped/during forward operation
1: During reverse operation
0: No error or trip occurred for the unit or inverter
1: Error or trip occurred for the unit or inverter
0: No warning occurred for the unit or inverter
1: Warning occurred for the unit or inverter
0: Local (Operations from EtherCAT are disabled)
1: Remote (Operations from EtherCAT are enabled)
0: During acceleration/deceleration
1: Frequency matched
0: Normal
1: Error (Cannot update data for the inverter. To restore, turn the power OFF and then ON again.)
The reserved area. Set 0.
Output frequency monitor
Name
Output frequency monitor
Meaning
Displays the output frequency in increments of 0.01 Hz.
Current position monitor
Name
Current position monitor
Meaning
Displays the value of inverter parameter d030: Current position monitor.
Multi-function output monitor
The bit data for the multi-function output monitor information is shown below.
6
1
Bit
0
1
6
Name
Multi-function output P1/EDM 0: OFF
Multi-function output P2
1: ON
Multi-function relay output
(Reserved) The reserved area. Set 0.
Meaning
* Use by assigning a function to the multi-function output with the inverter parameters.
0
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 Inverter Control
4-2-4 Sample Program
Configuration
This section explains a configuration that uses CJ1W-NCx82 as the master, and one MX2 inverter on which an EtherCAT Communication Unit (node address: 17) is mounted as the slave.
Parameter settings
The shared parameter settings of CJ1W-NCx82 are as follows.
Parameter name
Remote I/O Output Memory Area Selection
First word of remote I/O Output memory area
Remote I/O Input Memory Area Selection
First word of remote I/O Input memory area
CIO area
3800
CIO area
3900
Set value
The control information and status information of the EtherCAT Communication Unit is allocated to the addresses below.
• Control information (master to slave) n n + 1
Word Address
CIO 3800
CIO 3801
Meaning
Command
Bit 0: Forward/stop
Bit 1: Reverse/stop
Bit 7: Fault reset
Frequency reference (increments of 0.01 Hz)
• Status information (slave to master) m
Word Address
CIO 3900 m + 1 CIO 3901
Meaning
Command
Bit 0: During forward operation
Bit 1: During reverse operation
Bit 3: Fault
Output frequency monitor (increments of 0.01 Hz)
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 7
4 Inverter Control
Ladder program example
0.00
Frequency setting
3900.03
Fault
0.03
Fault reset
30.00
Fault occurred
0.01
0.02
Forward
0.02
Reverse
Reverse
3900.01
30.00
During reverse operation
Fault occurred
3900.00
30.00
0.01
Forward
During forward operation
Fault occurred
0.03
Fault reset
3900.03
Fault
3900.15
Option - Inverter connection fault
3900.15
Option - Inverter connection fault
Time chart
Frequency setting (0.00)
Forward (0.01)
Reverse (0.02)
During forward operation (word m bit 0)
During reverse operation (word m bit 1)
Frequency reference (word n + 1)
Fault occurred (30.00)
Fault reset (0.03)
The frequency reference data in D00000 is forwarded to word n + 1.
(1) (2) (3) (4) (5) (6) (7)
MOV
(021)
D0000
3801
30.00
Frequency reference
Fault occurred
3800.00
Forward/stop
(word n bit 0)
3800.01
Reverse/stop
(word n bit 1)
3800.07
Fault reset
(word n bit 7)
END
(001)
4 - 8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 Inverter Control
Explanation of operations
(1) When the "Frequency setting" contact is turned ON, the frequency reference data that is set in
D00000 is forwarded to the remote I/O output relay area (word n + 1).
(2) When the "Forward" contact is turned ON, "Forward/stop (word n bit 0)" of the remote I/O output relay area turns ON and forward operation starts. During forward operation, "During forward operation (word m bit 0)" of the remote I/O input relay area turns ON.
(3) When the "Forward" contact is turned OFF and after decelerating and stopping, "During forward operation (word m bit 1)" of the remote I/O input relay area turns OFF.
(4) When the "Reverse" contact is turned ON, "Reverse/stop (word n bit 1)" of the remote I/O output relay area turns ON and reverse operation starts. During reverse operation, "During reverse operation (word m bit 1)" of the remote I/O input relay area turns ON.
(5) When the "Reverse" contact is turned OFF and after decelerating and stopping, "During reverse operation (word m bit 1)" of the remote I/O input relay area turns OFF.
(6) When "Fault (word m bit 3)" of the remote I/O input relay area turns ON, "Fault occurred" turns ON.
(7) When the "Fault reset" contact is turned ON, "Fault reset (word n bit 7)" of the remote I/O output relay area turns ON and the fault is cancelled.
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 9
4 Inverter Control
4-3 Control with the Independent Profile
This section describes how to use the OMRON profile to control the inverter.
4-3-1 Inverter Setting
The inverter parameters must be set to match the profile.
With the independent profile, set as follows.
Parameter
A001 Frequency Reference Selection 1
A002 RUN Command Selection 1
C102 Reset Selection
04: Optional boad
04: Optional boad
03: Trip reset only
* If parameter C102 is not displayed, set b037 to 01.
Description
4-3-2 Profile Allocation
Assign the PDOs of the independent profile to Sync Manager.
Sync Manager PDO assignment
1C12 hex
1C13 hex
Description
1701 hex (Fixed allocation of the independent profile)
1B01 hex (Fixed allocation of the independent profile)
The values below are the fixed mapping for the PDOs.
PDO
1701 hex
1B01 hex
5000 hex (Command)
5010 hex (Frequency reference)
5100 hex (Status)
5110 hex (Output frequency monitor)
Description
4-3-3 Control Method
Control the inverter by operating the PDOs that allocate the profile.
IO format
Control information (master to slave)
Word
n n + 1
Command
Frequency reference
Status information (slave to master)
Word
m m + 1
Status
Output frequency monitor
Meaning
Meaning
4 - 10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 Inverter Control
Bit and data information
Command
Bit
0 Forward/stop
Name
1 Reverse/stop
7
-
Fault reset
Reserved
Frequency reference
7
Meaning
0: Stop
1: Forward command
0: Stop
1: Reverse command
: Resets an error or trip for the unit or inverter.
Set 0.
1 0
Name
Frequency reference
Meaning
Specify the frequency reference in increments of 0.01 Hz. When a value is set that exceeds the maximum frequency, operation is performed at the maximum frequency.
Setting range: 0 to maximum frequency
Status
The 16-bit data is as shown below.
15
12
9
7
3
1 0
Bit
0
1
3
7
9
12
15
Name
During forward operation
During reverse operation
Fault
Warning
Remote
Frequency matching
Connection error between the
Optional Unit and inverter
Reserved
Output frequency monitor
Meaning
0: Stopped/during reverse operation
1: During forward operation
0: Stopped/during forward operation
1: During reverse operation
0: No error or trip occurred for the unit or inverter
1: No error or trip occurred for the unit or inverter
0: No warning occurred for the unit or inverter
1: Warning occurred for the unit or inverter
0: Local (Operations from EtherCAT are disabled)
1: Remote (Operations from EtherCAT are enabled)
0: During acceleration/deceleration or stopped
1: Frequency matched
0: Normal
1: Error (Cannot update data for the inverter. To restore, turn the power supply OFF and then ON again.)
Set 0.
Name
Output frequency monitor
Meaning
Displays the output frequency in increments of 0.01 Hz.
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 11
4 Inverter Control
4-4 Control with the CiA402 Profile
This section describes how to use the Velocity mode of the CiA402 drive profile to control the inverter.
4-4-1 Inverter Setting
The inverter parameters must be set to match the profile.
With the CiA402 profile, set as follows.
Parameter
A001 Frequency Reference Selection 1
A002 RUN Command Selection 1
H004 Motor Pole Number 1
C102 Reset Selection
Description
04: Optional boad
04: Optional boad
2/4/6/8/10(Set to match the system.)
03 (Trip reset only)
* After changing H004, turn the inverter power supply OFF and ON again.
* If parameter C102 is not displayed, set b037 to 01.
* Do not use motor 2 control of the inverter. The motor 1 control only can be used.
4-4-2 Profile Allocation
Assign the PDOs of the CiA402 profile to Sync Manager.
Sync Manager PDO assignment
1C12 hex
1C13 hex
Description
1700 hex (Fixed allocation conforming to the CiA402 drive profile)
1B00 hex (Fixed allocation conforming to the CiA402 drive profile)
The values below are the fixed mapping for the PDOs.
PDO
1700 hex
1B00 hex
6040 hex (Controlword)
6042 hex (vl target velocity)
6041 hex (Statusword)
6043 hex (vl velocity demand)
Description
4-4-3 Control Method
Control the inverter by operating the PDOs that allocate the profile.
IO format
Control information (master to slave)
Word
n n + 1
Controlword vl target velocity
Status information (slave to master)
Word
m m + 1
Statusword vl velocity demand
Meaning
Meaning
4 - 12
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 Inverter Control
Bit and data information
Controlword
The 16-bit data is as shown below.
7
3 2 1
Bit
0
1
2
3
7
Name
Switch on
Enable voltage
Quick stop
Enable operation
Fault reset
Reserved
Meaning
The state is controlled by these bits.
For details, refer to 5-1-3 Command Coding on page 5-3.
Faults and warnings are cleared when this bit turns ON.
Set 0.
* When Quick stop is set to 0 during operation, deceleration stop is made. After completely stopping, the next operation is accepted.
0
vl target velocity vl target velocity
Name
Statusword
The 16-bit data is as shown below.
Meaning
Specify the command speed in rpm.
Setting range:
maximum speed to +maximum speed
Specify the operation direction with a symbol (
/+). When a value is set that exceeds the maximum frequency, operation is performed at the maximum frequency.
9
7 6 5 4 3 2 1 0
5
6
3
4
7
Bit
0
1
2
Name
Ready to switch on
Switched on
Operation enabled
Fault
Voltage enabled
Quick stop
Switch on disabled
Warning
Meaning
These bits indicate the state.
For details, refer to 5-1-4 State Coding on page 5-3.
9 Remote
Reserved
vl velocity demand
0: No warning occurred for the unit or inverter.
1: Warning occurred for the unit or inverter.
0: Control from Controlword is disabled.
1: Control from Controlword is enabled.
Not used.
Name
vl velocity demand
Meaning
Displays the operation speed in rpm.
The operation direction is expressed with a symbol (
/+).
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 13
4 Inverter Control
4-5 Control with the PDO Free Format
Objects can be freely allocated to PDOs to create an independent profile.
If you use in combination with the OMRON independent profile or the CiA402 drive profile, you can perform advanced control and monitoring.
To use your OMRON NJ501-1x00 as the master, allocate desired objects by referring to this section.
4-5-1 Inverter Setting
When using the OMRON independent profile, set A001, A002 and C102.
When using the CiA402 drive profile, set A001, A002, H004 and C102.
For details, refer to the previous sections.
4-5-2 Object Mapping
Allocate the objects that you want to use to PDOs.
Setting example
Set as follows to allocate the acceleration time and deceleration time to RxPDO and the current monitor to TxPDO, based on the OMRON independent profile.
PDO mapping
PDO
1600 hex
(1st receive PDO Mapping)
1601 hex
(2nd receive PDO Mapping)
1A00 hex
(1st transmit PDO Mapping)
Description
4011.26 (F002 Acceleration time setting 1)
4011.28 (F003 Deceleration time setting 1)
3010.24 (d002 Output current monitor)
Sync Manager assignment
Sync Manager PDO assignment
1C12 hex
1C13 hex
Description
1701 hex (Fixed allocation of the independent profile)
1600 hex (Setting as above)
1601 hex (Setting as above)
1B01 hex (Fixed allocation of the independent profile)
1A00 hex (Setting as above)
Following from the above allocations, the IO format is as follows.
Control information (master to slave)
Word
n n + 1 n + 2 n + 3 n + 4 n + 5
Command
Frequency reference
Acceleration time setting 1 (LSW)
Acceleration time setting 1 (MSW)
Deceleration time setting 1 (LSW)
Deceleration time setting 1 (MSW)
Meaning
4 - 14
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Status information (slave to master)
Word
m m + 1 m + 2
Status
Output frequency monitor
Output current monitor
Meaning
4-5-3 Objects Allocation in Sysmac Studio
In Sysmac Studio, you can edit the PDO map settings for each slave.
4 Inverter Control
Click Edit PDO Map Settings in the Configurations and Setup of the EtherCAT slave to open the Edit
PDO Map Settings pane.
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 15
4 Inverter Control
To allocate an object to a PDO in Sysmac Studio, select Output (or Input) for one of 1st receive PDO
Mapping to 5th receive PDO Mapping (or 1st transmit PDO Mapping to 5th transmit PDO Mapping), right-click Add PDO Entry on the right side of the screen, and then select a desired object from the list.
When Output (or Input) is selected, the applicable PDO among 1st receive PDO Mapping to 5th
receive PDO Mapping (or 1st transmit PDO Mapping to 5th transmit PDO Mapping) will be allocated to
Sync Manager.
Note that up to 5 PDOs can be selected each for the target of Output (or Input).
Add PDO Entry
In the example shown below, Jogging Frequency (Index: 3012.5Dh) and Manual Torque Boost
Frequency 1 (Index: 3012.62h) are allocated to 1st receive PDO Mapping.
4-5-4 Restrictions
The PDO free format has the restrictions that are described below.
• Up to 2 objects can be allocated to each PDO from 1600 to 1604 hex and 1A00 to 1A04 hex. Keep the total size of the allocated objects to within 4 bytes.
• Up to 5 PDOs each can be allocated to 1C12 and 1C13.
• An object from 5000 to 5999 cannot be allocated to RxPDO (master to slave) together with an object from 6000 to 6999.
• An RxPDO that combines an object from 5000 to 5999 with an object from 6000 to 6999 cannot be allocated to 1C12 hex of Sync Manager.
• The inverter parameters (objects 3000 to 3999 and 4000 to 4999) that can be allocated to RxPDO
(master to slave) are limited to those that can be changed during operation.
• It is not possible to allocate only the LSW or only the MSW to RxPDO or TxPDO.
• The greater the number of RxPDOs or TxPDOs is, the longer the data updating cycle becomes.
Normally the data is updated every 4 ms, but it can increase to every 6 ms depending on the number.
4 - 16
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 Inverter Control
4-6 Trial operation via EtherCAT
Communication Unit
You can use the "Test Operation" function of your parameter setting tool (CX-Drive, etc.) to operate the inverter on a trial basis.
Before performing trial operation of the inverter via the EtherCAT Communication Unit, make sure
EtherCAT network communications have been established properly. The main purpose of trial operation is to confirm that the system operates correctly from the electrical viewpoint. Perform trial operation after confirming safety around the devices.
If an error occurs during trial operation, remove the error by referring to Chapter 6, Handling of Errors
and Maintenance or the User's Manual for MX2 Series, and resume operation after conforming safety.
How to perform trial operation using a parameter setting tool
1
Start your parameter setting tool and make online connection via EtherCAT.
2
Select the Test Operation function.
3
Set a desired frequency, acceleration time and deceleration time, and then select
Forward or Reverse and run the motor.
The motor will keep running until Stop is selected.
4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4 - 17
4 Inverter Control
4 - 18
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
CiA402 Drive Profile
This chapter explains about the CiA402 drive profile.
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 1
5 CiA402 Drive Profile
5-1 Inverter State Control
The state of the MX2 inverter is controlled by using the Controlword (6040 hex). Control state is given in the Statusword (6041 hex).
5-1-1 State Machine
The state of the MX2 inverter changes as shown below.
Each box indicates a state, while numbers 2 to 10 and 15 indicate the state control commands.
Power turned OFF or reset
Start
0: After the main power supply is turned on
Not ready to switch on
1: After initialization is completed
15: Fault reset
Switch on disabled
Fault
Shutdown: 2 7: Disable Voltage
Ready to switch on
Switch on: 3
6: Shutdown
Disable Voltage: 10
Switched on
Enable operation: 4
14: Error
response
operation
completed
Fault reaction active
5: Disable
operation
Operation enabled
8: Shut down
13: Error occurs
9: Disable Voltage
(Notes) The Quick stop active state is not supported. If Quick stop is enabled in the Operation enable state, transition 9 is executed.
5 - 2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
5-1-2 State Descriptions
Not ready to switch on
State
Switch on disabled
Ready to switch on
Switched on
Operation enabled
Fault reaction active
Fault
Details
The power supply is turned ON and initialization is being executed.
Initialization has been completed.
Parameters can be set.
Parameters can be set.
Parameters can be set.
Inverter can be controlled.
Parameters can be set.
There was an error in the inverter and the cause is being determined.
Parameters can be set.
There is an error in the inverter.
Parameters can be set.
5-1-3 Command Coding
The state is controlled by combining the bits in Controlword (6040 hex), as shown in the following table.
Command
Shutdown
Switch on
Switch on + enable operation
Disable voltage
Quick stop
Disable operation
Enable operation
Fault reset
Bit 7 fr
-
-
-
-
-
-
-
0
1
*2*3
Bit 3 eo
-
0
1
0
1
-
-
-
Controlword bit
Bit 2 qs
1
1
1
1
1
-
0
-
Bit 1 ev
1
1
1
1
1
0
1
-
Bit 0 so
0
1
1
1
1
-
-
-
2, 6, 8
3
3 + 4
*1
5
4
7, 9, 10
7, 9, 10
15
Transition
(Notes) fr = Fault reset, eo = Enable operation, qs = Quick stop, ev = Enable voltage, so = Switch on
*1 The state automatically transitions to the Enable operation state after the Switch on state.
*2 Operation when bit 7: Fault reset turns ON.
Fault state : Fault are cleared and the state transitions to Switch on disabled.
: If there are any warnings (6401 hex: Statusword bit 7), they are reset.
State other than Fault : If there are any warnings (6041 hex: Statusword bit 7), they are reset.
: The state will change according to command bits 0 to 3.
*3 When Fault reset is executed with bit 7, set the bit back to 0 before giving the next command.
5
5-1-4 State Coding
The state is indicated by the combination of bits in Statusword (6041 hex), as shown in the following table.
State
Not ready to switch on
Switch on disabled
Ready to switch on
Switched on
Operation enabled
Fault reaction active
Fault
0
0
0
0
0
Bit 6 sod
0
1
1
1
1
1
1
Bit 5 qs
0
1
1
-
-
1
-
Bit 4 ve
-
-
0
1
0
0
1
Bit 3 f
0
0
1
1
0
0
0
Bit 2 oe
0
0
1
1
0
1
0
Bit 1 so
0
0
(Notes) sod = Switch on disabled, qs = Quick stop, ve = Voltage enabled, f = Fault, oe = Operation enabled, so = Switched on, rtso = Ready to switch on
1
1
1
1
0
Bit 0 rtso
0
0
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 3
5 CiA402 Drive Profile
5-2 Modes of Operation
The operation mode indicated below is supported.
* vl: Velocity mode
The operation mode is set in Modes of operation (6060 hex). In addition, the operation mode is given in
Modes of operation display (6061 hex).
The operation modes supported by the inverter can be checked in Supported drive modes (6502 hex).
5 - 4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
5-3 Velocity Mode
In this operation mode, the output speed of the inverter can be controlled.
vl target velocity (6042 hex) vl velocity min/max amount (6046 hex) vl velocity acceleration (6048 hex) vl velocity deceleration (6049 hex)
Velocity limit function
Ramp function vl velocity demand (6043 hex)
Velocity control function vl velocity actual value (6044 hex)
• Related objects
Index
6040 hex
6042 hex
6046 hex
Name
Controlword vl target velocity vl velocity min max amount
6048 hex
6049 hex
6041 hex
6043 hex
6044 hex vl velocity acceleration vl velocity deceleration
Statusword vl velocity demand vl velocity actual value
Details
Gives commands to the inverter.
Gives speed commands to the inverter.
Sets the maximum speed and minimum speed that can be output.
Sets the acceleration time.
Sets the deceleration time.
Sets the status of the inverter.
Gives the command speed.
Gives the output speed.
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 5
5 CiA402 Drive Profile
5-4 Object Dictionary
5-4-1 Object Dictionary Area
CANopen over EtherCAT (CoE) protocol uses the CANopen object dictionary as its base. All objects are assigned four-digit hexadecimal numbers in the areas shown in the following table.
Index
0000 to 0FFF hex
1000 to 1FFF hex
2000 to 2FFF hex
3000 to 5FFF hex
6000 to 9FFF hex
A000 to FFFF hex
Area
Data Type area
CoE Communications area
Manufacturer Specific area 1
Manufacturer Specific area 2
Device Profile area
Reserved area
Meaning
Definitions of data types.
Definitions of variables that can be used by all servers for designated communications.
Variables with common definitions for all OMRON products.
Variables with definitions for this unit. (Inverter parameters, independent profile)
Variables defined in the inverter's CiA402 drive profile.
Area reserved for future use.
5-4-2 Data Types
The data types shown in the following table are used in this profile.
Data type
Boolean
Unsigned8
Unsigned16
Unsigned32
Integer8
Integer16
Integer32
Visible string
BOOL
U8
U16
U32
INT8
INT16
INT32
VS
Code
1 bit
1 byte
2 bytes
4 bytes
1 byte
2 bytes
4 bytes
Size Range
0 to 1
0 to 255
0 to 65,535
0 to 4,294,967,295
128 to 127
32,768 to 327,671
2,147,483,648 to 2,147,483,647
5-4-3 Object Description Format
In this manual, objects are described in the following format.
• Object description format
<Index> <Object name>
Setting range: <Setting range>
Size: <Size>
Operating Mode
Unit: <Unit>
Access: <Access>
Default setting: <Default setting>
PDO map: <Possible/Not possible>
• Object description format when there is a sub-index
<Index> <Object name>
Sub-index 0
Setting range: <Setting range>
Size: <Size>
•
•
•
Sub-index N
Setting range: <Setting range>
Size: <Size>
Operating Mode
Unit: <Unit>
Access: <Access>
Default setting: <Default setting>
PDO map: <Possible/Not possible>
Unit: <Unit>
Access: <Access>
Default setting: <Default setting>
PDO map: <Possible/Not possible>
5 - 6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
• Index
• Object name
: Object index given by a four-digit hexadecimal number.
: The object name.
• Operating mode : Related operating modes.
• Setting range : The possible range of settings.
• Unit : Physical units.
• Default setting : The default value set before shipment.
• Size
• Access
: The object size is given in bytes.
: Indicates whether the object is read only, or read and write.
• PDO map
RO: Read only.
WO: Write only.
RW: Read and write.
: Indicates the PDO mapping attribute.
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 7
5 CiA402 Drive Profile
5-5 CoE Communications Area
5-5-1 Communication Objects
1000 hex Device type
Setting range:
Size: 4 bytes (U32)
Unit:
Access: RO
• Gives the CoE device profile number.
• Explanation of set values
0 to 15
16 to 23
25 to 31
Bit Name
Device profile number
Type
Mode
All
Default setting: 00010192 hex
PDO map: Not possible
Meaning
402 (192 hex): Drive profile
01: Inverter
0: Manufacturer specific
1001 hex
Setting range:
Size: 1 byte (U8)
Error register
Unit:
Access: RO
• Gives the error type that occurred.
• Explanation of set values
Bit
0
1
2
3
Generic error
(Reserved)
(Reserved)
(Reserved)
Details
Default setting: 0
Bit
4
5
6
7
All
PDO map: Not possible
Details
Communication error
Device profile specific error
(Reserved)
Manufacturer specific error
1008 hex
Setting range:
Size: 20 bytes (VS)
Manufacturer device name
Unit:
Access: RO
• Gives the model.
All
Default setting: 3G3AX-MX2-ECT
PDO map: Not possible
1009 hex
Setting range:
Manufacturer hardware version
Unit:
Default setting:
*1
All
Size: 20 bytes (VS) Access: RO PDO map: Not possible
*1 "V*.**" which shows the hardwave version is saved.
• Gives the Manufacturer hardware version of the EtherCAT Communication Unit.
100A hex
Setting range:
Manufacturer software version
Unit:
Default setting:
*1
All
Size: 20 bytes (VS) Access: RO PDO map: Not possible
*1 The version number is saved in “v*.**”.
• Gives the Manufacturer software version of the EtherCAT Communication Unit.
5 - 8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
1010 hex Store parameters
All
Sub-index 0: Number of entries
Setting range:
Size: 1 byte (U8)
Sub-index 1: Save all parameters
Setting range:
Size: 4 bytes (U32)
Unit:
Access: RO
Unit:
Access: RW
Default setting: 01 hex
PDO map: Not possible
Default setting: 00000001 hex
PDO map: Not possible
• All savable parameters are saved in the Inverter EEPROM.
• Saving is executed only when a specific value is written to sub-index 1. This prevents parameter values from being accidentally overwritten.
• The specific value means “save”.
MSB LSB e v a s
65 hex 76 hex 61 hex 73 hex
• A value of 00000001 hex (command valid) is given when reading.
• Parameters cannot be saved to the EEPROM during inverter operation.
• In the following cases, an ABORT code is returned.
• Writing with CompleteAccess.
• Writing a value other than 65766173 hex.
• Writing to the EEPROM may take up to 1 second. (This is when all objects are changed.)
• There is a limit to the number of times you can write to the EEPROM.
1011 hex Restore default parameters
Sub-index 0: Number of entries
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Sub-index 1: Restore all default parameters
Setting range:
Unit:
Size: 4 bytes (U32) Access: RW
Default setting: 01 hex
PDO map: Not possible
Default setting: 00000001 hex
PDO map: Not possible
• Inverter parameters are reset to their default settings.
• A restoration operation is executed only when a specific value is written to sub-index 1. This prevents parameter values from being accidentally overwritten.
• The specific value means “load.”
All
MSB d a
64 hex 61 hex o
6f hex
LSB l
6c hex
• A value of 00000001 hex (command valid) is given when reading.
• In the following cases, an ABORT code is returned.
• Writing with CompleteAccess.
• Writing a value other than 64616F6C hex.
• Writing to the EEPROM may take up to 3 seconds. (This is when all objects are changed.)
• There is a limit to the number of times you can write to the EEPROM.
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 9
5 CiA402 Drive Profile
1018 hex Identity object
All
Sub-index 0: Number of entries
Setting range:
Size: 1 byte (U8)
Sub-index 1: Vendor ID
Setting range:
Size: 4 bytes (U32)
Sub-index 2: Product code
Setting range:
Size: 4 bytes (U32)
Sub-index 3: Revision number
Setting range:
Size: 4 bytes (U32)
Sub-index 4: Serial number
Setting range:
Size: 4 bytes (U32)
Unit:
Unit:
Unit:
Unit:
Unit:
Access: RO
Access: RO
Access: RO
Access: RO
Access: RO
Default setting: 04 hex
PDO map: Not possible
Default setting: 00000083 hex
PDO map: Not possible
Default setting: 00000053 hex
PDO map: Not possible
Default setting: Refer to the table.
PDO map: Not possible
Default setting: 00000000 hex
PDO map: Not possible
• This object contains device information.
• Sub-index 1 (Vendor ID) gives the manufacturer identifier.
• Sub-index 2 (Product code) gives the product's identifier.
• Sub-index 3 (Revision number) gives the device revision number.
• Explanation of set values
Bit
0 to 15
16 to 31
Device's minor revision number
Device's major revision number
Details
• Sub-index 4 (Revision number) gives the serial number for each product. (This is not used by MX2 inverters.)
10F3 hex Diagnosis history All
Sub-index 0: Number of entries
Setting range:
Size: 1 byte (U8)
Sub-index 1: Maximum messages
Unit:
Access: RO
Setting range: 00 to 08 hex
Size: 1 byte (U8)
Sub-index 2: Newest message
Setting range: 06 to 0D hex
Unit:
Access: RO
Unit:
Size: 1 byte (U8)
Sub-index 5: Flags
Access: RO
Setting range: 0000 to 0001 hex
Size: 2 bytes (U16)
Unit:
Sub-indexes 6 to 13: Diagnosis messages 1 to 8
Setting range:
Unit:
Size: 23 bytes (VS)
Access: RW
Access: RO
Default setting: 0D hex
Default setting: 00 hex
Default setting: 06 hex
Default setting: 0001 hex
Default setting:
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
• This object gives up to 8 diagnosis history items. It also enables or disables emergency messages.
• Sub-index 1 (Maximum messages) gives the number of error messages.
• Sub-index 2 (Newest message) gives the sub index where the latest diagnosis message is saved.
• Sub-index 5 (Flags) sets whether or not to give notification of the diagnosis history as an emergency message. It is set to Emergency Message Enabled (0001 hex) when the power supply is turned ON.
• Sub-indexes 6 to 13 (Diagnosis messages 1 to 8) give the diagnosis history. The diagnosis history is saved in Diagnosis messages 1 to 8 in ascending order. When the 9th error is reached, it is saved as
Diagnosis message 1 and the sequence starts again.
• The diagnosis history is retained even when the power supply is turned OFF.
5 - 10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
Diagnosis history details
Meaning
Error code
Size
4 bytes (U32)
Error flag
(Reserved)
2 bytes (U16)
17 bytes
Details
The upper byte is the error code that is defined with CiA301 and CiA402. The lower 2 bytes are the code type and are fixed at E800 hex.
Gives the error type.
Bit 1: Warning
Bit 2: Error
Other bits: Reserved
The reserved area.
5-5-2 PDO Mapping Objects
Indexes 1600 to 17FF hex are used for receive PDO mapping and indexes 1A00 to 1BFF hex are used for transmit PDO mapping. Sub-indexes after sub-index 1 provide information about the application object being mapped.
31
MSB
Index
16 15
Sub-index
8 7 0
Bit length
LSB
Bit 0 to 7 : Bit length of the mapped object. (For example, for 32 bits, 20 hex is given.)
Bit 8 to 5 : Sub-index of the mapped object.
Bit 16 to 31 : Index of the mapped object.
1600 to 1604 hex 1st to 5th receive PDO mapping All
Sub-index 0: Number of objects
Setting range: -
Setting range: -
Size: 4 bytes (U32)
Unit: -
Size: 1 byte (U8)
Sub-index 1: 1st Output Object to be mapped
Unit: -
Access: RW
Access: RW
Sub-index 2: 2nd Output Object to be mapped
Setting range: Unit: -
Size: 4 bytes (U32) Access: RW
Default setting: 0
PDO map: Not possible
Default setting: 00000000 hex
PDO map: Not possible
Default setting: 00000000 hex
PDO map: Not possible
• The PDO mapping when freely allocated objects are used.
• Objects can be allocated up to a total bit length of 32 bits.
5
1700 hex 257th fixed receive PDO mapping All
Sub-index 0: Number of objects
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Sub-index 1: 1st Output Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Sub-index 2: 2nd Output Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Default setting: 2
PDO map: Not possible
Default setting: 60400010 hex
PDO map: Not possible
Default setting: 60420010 hex
PDO map: Not possible
• The PDO mapping when Velocity mode is used.
• The following objects are mapped.
• Controlword (6040 hex), vl target velocity (6042 hex)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 11
5 CiA402 Drive Profile
1701 hex 258th fixed receive PDO mapping
All
Sub-index 0: Number of objects
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Sub-index 1: 1st Output Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Sub-index 2: 2nd Output Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Default setting: 2
PDO map: Not possible
Default setting: 50000010 hex
PDO map: Not possible
Default setting: 50100010 hex
PDO map: Not possible
• The PDO mapping when a fixed profile is used.
• The following objects are mapped.
• Command (5000 hex), Frequency reference (5010 hex)
1A00 to 1A04 hex 1st to 5th transmit PDO mapping
All
Sub-index 0: Number of objects
Setting range:
Size: 1 byte (U8)
Unit:
Access: RW
Sub-index 1: 1st Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RW
Sub-index 2: 2nd Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RW
Default setting: 2
PDO map: Not possible
Default setting: 00000000 hex
PDO map: Not possible
Default setting: 00000000 hex
PDO map: Not possible
• The PDO mapping when freely allocated objects are used.
• Objects can be allocated up to a total bit length of 32 bits.
1B00 hex 257th fixed transmit PDO mapping All
Sub-index 0: Number of objects
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Sub-index 1: 1st Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Sub-index 2: 2nd Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Default setting: 2
PDO map: Not possible
Default setting: 60410010 hex
PDO map: Not possible
Default setting: 60430010 hex
PDO map: Not possible
• The PDO mapping when Velocity mode is used.
• The following objects are mapped.
• Statusword (6041 hex), vl velocity demand (6043 hex)
5 - 12
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
1B01 hex 258th fixed transmit PDO mapping
All
Sub-index 0: Number of objects
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Sub-index 1: 1st Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Sub-index 2: 2nd Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Default setting: 2
PDO map: Not possible
Default setting: 51000010 hex
PDO map: Not possible
Default setting: 51100010 hex
PDO map: Not possible
• The PDO allocation when a fixed profile is used.
• The following objects are mapped.
• Status information (5100 hex), Output frequency monitor (5110 hex)
1BFF hex 512th transmit PDO mapping All
Sub-index 0: Number of objects in this PDO
Setting range:
Unit:
Size: 1 byte (U8) Access: RO
Sub-index 1: 1st Input Object to be mapped
Setting range:
Unit:
Size: 4 bytes (U32) Access: RO
Default setting: 01 hex
PDO map: Not possible
Default setting: 20020108 hex
PDO map: Not possible
• This is a mapping object to notify that the EtherCAT Communication Unit has detected an error.
• 2002 hex-01 hex: Sysmac Error Status has been mapped.
• When the Machine Automation Controller NJ501-1x00 series is connected, assign this object to
1C13 hex: Sync manager 3 PDO assignment.
• By default, Sysmac Studio assigns this object automatically.
5-5-3 Sync Manager Communication Objects
Objects 1C00 to 1C33 hex set how to use the EtherCAT communications memory.
1C00 hex Sync Manager communication type
Sub-index 0: Number of used SM channels
Setting range:
Unit:
Size: 1 byte (U8) Access: RO
Sub-index 1: Communication Type SM0
Setting range:
Size: 4 bytes (U8)
Unit:
Access: RO
Sub-index 2: Communication type SM1
Setting range:
Size: 4 bytes (U8)
Sub-index 3: Communication type SM2
Setting range:
Size: 4 bytes (U8)
Sub-index 4: Communication type SM3
Setting range:
Size: 4 bytes (U8)
Unit:
Unit:
Unit:
Access: RO
Access: RO
Access: RO
Default setting: 04 hex
Default setting: 01 hex
Default setting: 02 hex
Default setting: 03 hex
Default setting: 04 hex
• The Sync Manager has the following settings.
• SM0 : Mailbox reception (master to slave)
• SM1 : Mailbox send (slave to master)
• SM2 : Process data output (master to slave)
• SM3 : Process data input (slave to master)
All
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 13
5 CiA402 Drive Profile
1C10 hex Sync Manager 0 PDO assignment
All
Sub-index 0: Number of assigned RxPDOs
Setting range:
Unit:
Size: 1 byte (U8) Access: RO
Default setting: 00 hex
PDO map: Not possible
• The PDO mapping used by this Sync Manager is given. Mailbox reception Sync Manager does not have PDOs.
1C11 hex Sync Manager 1 PDO assignment
All
Sub-index 0: Number of assigned PDOs
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Default setting: 00 hex
PDO map: Not possible
• The PDO mapping used by this Sync Manager is given. Mailbox send Sync Manager does not have
PDOs.
1C12 hex Sync Manager 2 PDO assignment All
Sub-index 0: Number of assigned RxPDOs
Setting range:
Unit:
Size: 1 byte (U8) Access: RW
Sub-index 1: 1st PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 2: 2nd PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 3: 3rd PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 4: 4th PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 5: 5th PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Default setting: 00 hex
Default setting: 1701 hex
Default setting: 0000 hex
Default setting: 0000 hex
Default setting: 0000 hex
Default setting: 0000 hex
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
• The receive PDOs used by this Sync Manager are given.
• Up to 5 PDOs can be assigned.
• An object from 5000 to 5999 cannot be allocated at the same time as an object from 6000 to 6999.
5 - 14
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
1C13 hex Sync Manager 3 PDO assignment
Sub-index 0: Number of assigned TxPDOs
Setting range:
Unit:
Size: 1 byte (U8) Access: RW
Sub-index 1: 1st PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 2: 2nd PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 3: 3rd PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 4: 4th PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Sub-index 5: 5th PDO Mapping object index of assigned PDO
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Default setting: 00 hex
Default setting: 1B01 hex
Default setting: 0000 hex
Default setting: 0000 hex
Default setting: 0000 hex
Default setting: 0000 hex
• The transmit PDOs used by this Sync Manager are given.
• Up to 5 PDOs can be assigned.
All
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
1C32 hex SM 2 synchronization
All
Sub-index 0: Number of synchronization parameters
Setting range:
Unit:
Size: 1 byte (U8) Access: RO
Sub-index 1: Synchronization type
Setting range:
Size: 2 bytes (U16)
Unit:
Access: RW
Sub-index 4: Synchronization types supported
Setting range:
Unit:
Size: 2 bytes (U16) Access: RO
Default setting: 20 hex
Default setting: 0000 hex
Default setting: 0001 hex
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
• Synchronization type (1C32 to 01 hex) indicates the Synchronization mode of Sync Manager 2.
• 0000 hex: Free Run mode
• Synchronization types supported (1C32 to 04 hex) indicates the types of synchronization supported.
• 0001 hex: Free Run mode
1C33 hex SM 3 synchronization
All
Sub-index 0: Number of synchronization parameters
Setting range:
Unit:
Size: 1 byte (U8) Access: RO
Sub-index 1: Synchronization type
Setting range:
Size: 2 bytes (U16)
Unit:
Access: RW
Sub-index 4: Synchronization types supported
Setting range:
Unit:
Size: 2 bytes (U16) Access: RO
Default setting: 20 hex
Default setting: 0000 hex
Default setting: 0001 hex
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
• Synchronization type (1C33 to 01 hex) indicates the Synchronization mode of Sync Manager 2.
• 0000 hex: Free Run mode
• Synchronization types supported (1C33 to 04 hex) indicates the types of synchronization supported.
• 0001 hex: Free Run mode
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 15
5 CiA402 Drive Profile
5-6 Manufacturer Specific Area
5-6-1 Manufacturer Specific Objects
2002 hex Sysmac Error
All
Sub-index 0: Number of entries
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Default setting: 02 hex
PDO map: Not possible
Sub-index 1: Sysmac Error Status
Setting range:
Size: 1 byte (U8)
Sub-index 2: Sysmac Error Status Clear
Setting range:
Size: 1 byte (U8)
Unit:
Unit:
Access: RO
Access: RW
• Notify and clear the Sysmac Error Status.
• Sub-index 1: Sysmac Error Status
Default setting: 00 hex
Default setting: 00 hex
PDO map: Possible
PDO map: Not possible
• This object is used to notify that the EtherCAT Communication Unit has detected an error.
• When the Machine Automation Controller NJ501-1x00 series, etc., is connected, this object is mapped to the PDO.
• Sub-index 2: Sysmac Error Status Clear
• This object is used to allow the Sysmac product controller to reset the error present in the
EtherCAT Communication Unit.
Additional Information
By default, Sysmac Studio automatically maps sub-index 01 hex: Sysmac Error status to the
PDO by allocation of 1BFF hex: 512th transmit PDO Mapping.
2100 hex Error history clear All
Setting range: 6C636C65 hex
Size: 4 bytes (U32)
Unit:
Access: RW
Default setting: 00000000 hex
PDO map: Not possible
• This object clears the contents of Diagnosis history (10F3 hex).
• This function can be executed by writing 6C636C65 hex using SDO mailbox communications.
• In the following cases, an abort code is returned.
• Writing with CompleteAccess
• Writing a value other than 6C636C65 hex
5 - 16
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
5-6-2 Inverter Parameter Objects
Inverter parameters are allocated to objects 3000 to 3102 hex and 4000 to 4102 hex.
3000 to 3102 hex are 16-bit parameters and 4000 to 4102 hex are 32-bit parameters.
Index and sub-index calculation method
Index: 3000 hex + (N/254), Sub-index: 1 + (N%254)
Index: 4000 hex + (N/254), Sub-index: 1 + (N%254)
N: Inverter register number
(N/254): Integer part after N is divided by 254
(N%254): Remainder after N is divided by 254
3000 hex Inverter parameter object 1 (16-bit access)
All
Sub-index 0: Number of assigned
Setting range:
Size: 1 byte (U8)
Sub-index 1: Inverter register 0000 hex
Setting range:
Size: 2 bytes (U16)
Unit:
Unit:
Access: RO
Default setting: FE hex
Default setting:
PDO map: Not possible
Access: RW
PDO map:
*
Sub-index 2: Inverter register 0001 hex
Setting range:
Size: 2 bytes (U16)
Unit:
Default setting:
Access: RW
PDO map:
*
•
•
•
Sub-index 253 hex: Inverter register 00FC hex
Setting range:
Unit:
Size: 2 bytes (U16) Access: RW
Default setting:
PDO map:
*
* PDO mapping can only be performed for parameters that exist in the inverter. Only parameters that can be set during operation can be mapped to RxPDO.
5
3001 to 3101 hex Inverter parameter objects 2 to 258 (16-bit access)
Same format as 3000 hex, inverter registers 00FD to FFFB hex
All
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 17
5 CiA402 Drive Profile
3102 hex Inverter parameter object 259 (16-bit access)
All
Sub-index 0: Number of assigned
Setting range:
Size: 1 byte (U8)
Sub-index 1: Inverter register FFFC hex
Setting range:
Size: 2 bytes (U16)
Unit:
Unit:
Access: RO
Default setting: 04 hex
Default setting:
PDO map: Not possible
Access: RW
PDO map:
*
Sub-index 2: Inverter register FFFD hex
Setting range:
Size: 2 bytes (U16)
Unit:
Default setting:
Access: RW
PDO map:
*
Sub-index 3: Inverter register FFFE hex
Setting range:
Size: 2 bytes (U16)
Unit:
Access: RW
Default setting:
PDO map:
*
Sub-index 4: Inverter register FFFF hex
Setting range:
Size: 2 bytes (U16)
Unit:
Access: RW
Default setting:
PDO map:
*
* PDO mapping can only be performed for parameters that exist in the inverter. Only parameters that can be set during operation can be mapped to RxPDO.
4000 hex Inverter parameter object 1 (32-bit access) All
Sub-index 0: Number of assigned
Setting range:
Size: 1 byte (U8)
Sub-index 1: Inverter register 0000 hex
Setting range:
Size: 2 bytes (U32)
Unit:
Access: RO
Unit:
Access: RW
Sub-index 2: Inverter register 0001 hex
Setting range:
Size: 2 bytes (U32)
Unit:
Access: RW
• • •
Sub-index 253 hex: Inverter register 00FC hex
Setting range:
Unit:
Size: 2 bytes (U32) Access: RW
Default setting: FE hex
Default setting:
Default setting:
Default setting:
PDO map: Not possible
PDO map:
*
PDO map:
*
PDO map:
*
* PDO mapping can only be performed for parameters that exist in the inverter. Only parameters that can be set during operation can be mapped to RxPDO.
4001 to 4101 hex Inverter parameter objects 2 to 258 (32-bit access)
Same format as 3000 hex, inverter registers 00FD to FFFB hex
All
5 - 18
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
4102 hex Inverter parameter object 259 (32-bit access)
All
Sub-index 0: Number of assigned
Setting range:
Size: 1 byte (U8)
Sub-index 1: Inverter register FFFC hex
Setting range:
Size: 2 bytes (U32)
Unit:
Unit:
Access: RO
Default setting: 04 hex
Default setting:
PDO map: Not possible
Access: RW
PDO map:
*
Sub-index 2: Inverter register FFFD hex
Setting range:
Size: 2 bytes (U32)
Unit:
Default setting:
Access: RW
PDO map:
*
Sub-index 3: Inverter register FFFE hex
Setting range:
Size: 2 bytes (U32)
Unit:
Access: RW
Default setting:
PDO map:
*
Sub-index 4: Inverter register FFFF hex
Setting range:
Size: 2 bytes (U32)
Unit:
Access: RW
Default setting:
PDO map:
*
* PDO mapping can only be performed for parameters that exist in the inverter. Only parameters that can be set during operation can be mapped to RxPDO.
5-6-3 Independent Profile Objects
This section explains about OMRON's independent profile objects.
5000 hex Command
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit:
Access: RW
Default setting: 0000 hex
• This object gives an operation command to the inverter.
• Bit descriptions
PDO map: Possible
All
Bit
0
1
2 to 6
7
8 to 15
Meaning
Forward/stop
Reverse/stop
Reserved
Fault reset
Reserved
Details
0: Stop 1: Forward
0: Stop 1: Reverse
Not used. Always keep at 0.
Faults and warnings are cleared when this bit turns ON.
Not used. Always keep at 0.
5
5010 hex Frequency reference All
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit: 0.01 Hz (0.1 Hz)
Access: RW
Default setting: 0000 hex
PDO map: Possible
• This object gives an output frequency command to the inverter.
• The value in parenthesis indicates the unit when the inverter mode selection is High frequency mode.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 19
5 CiA402 Drive Profile
5100 hex Status
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit:
Access: RO
Default setting: 0000 hex
• This object gives the present state of the unit.
• Bit descriptions
PDO map: Possible
All
Bit
0
1
2
3
4 to 6
7
9
10 to 11
12
13 to 14
15
During forward operation
During reverse operation
Reserved
Fault
Reserved
Warning
Remote
Meaning
Reserved
Frequency matching
Reserved
Connection error between the
Optional Unit and inverter
Details
0: Stop/reverse 1: During Forward operation
0: Stop/forward 1: During Reverse operation
Not used.
1: A fault (inverter trip) occurred.
Not used.
1: A warning occurred.
0: Commands other than those from the EtherCAT Communication Unit are enabled.
1: Commands from the EtherCAT Communication Unit are enabled.
Not used.
0: During Acceleration/deceleration or stopped 1: Frequency matching
Not used.
1: Error (Cannot update data for the inverter. To reset the error, turn the power supply OFF and then ON again.)
5110 hex Output frequency monitor All
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit: 0.01 Hz (0.1 Hz)
Access: RO
Default setting: 0000 hex
PDO map: Possible
• This object gives the output frequency of the inverter.
• The value in parenthesis indicates the unit when the inverter mode selection is High frequency mode.
5200 hex PDO mapping error history
All
Sub-index 0: Number of entries
Setting range:
Size: 1 byte (U8)
Unit:
Access: RO
Sub-index 1: Newest PDO mapping error cause
Setting range:
Unit:
Size: 2 bytes (U16) Access: RO
Sub-index 4: Number of error message
Setting range:
Size: 2 bytes (U16)
Unit:
Access: RO
Sub-indexes 5 to A: PDO mapping error message 1 to 6
Unit:
Unit:
Size: 2 bytes (U16) Access: RO
Default setting: 0A hex
Default setting: 0000 hex
Default setting: 00 hex
Default setting: 0000 hex
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
PDO map: Not possible
• Gives the cause of not being able to transit to Op when PDOs are freely mapped.
• Gives up to 6 PDO mapping error messages.
• Sub-index 1 (error cause) gives the latest cause code.
• Sub-index 4 (number of error messages) gives the number of error messages that are registered.
• Sub-indexes 5 to 10 (PDO mapping error message 1 to 6) give the cause codes when errors occur in
PDO mapping. Messages are saved in sequence from 1 to 6, and no more are saved. The history is cleared when the power supply is turned OFF or the state transitions from initialization (Init) to pre-operational (Pre-Op) is made.
5 - 20
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
Cause code list
0047 hex
0048 hex
004F hex
0050 hex
0060 hex
0061 hex
0070 hex
00E0 hex
00E1 hex
00E2 hex
00E3 hex
00E4 hex
00E5 hex
00E6 hex
00E7 hex
00E8 hex
8000 hex
8001 hex
8002 hex
0001 hex
Cause code
0002 hex
0003 hex
0020 hex
0021 hex
0022 hex
0023 hex
0024 hex
0040 hex
0041 hex
0042 hex
0043 hex
0044 hex
0045 hex
0046 hex
Meaning
Busy
Device busy
Unexpectedly received data
Sync Manager assignment exceeded
PDO map number is invalid (outside the range, does not exist)
RxPDO map overlap
Object specified for RxPDO mapping is invalid
Total number of assignment exceeded
RxPDO object overlap
Number of PDO mapping exceeded
PDO map size exceeded (more than 32 bits)
Incorrect object specification (sub-index 0 is mapped)
Object not supported
5000 to 5999 and 6000 to 6999 objects mixed
Object specified for PDO map is invalid
Incorrect data size for specified object
PDO mapping exists but size is 0
Specified access method not supported
Specified object mapping is invalid
RxPDO object overlap (MX2 registers are overlapping)
Unsupported data type is specified
Unsupported mode (mode other than FreeRun is specified)
Start address of the Refresh area is 1000 hex or lower, or an odd number
Specified size of the Refresh area exceeds the range
Start address of the Refresh area is different from the value in pre-operational (Pre-Op)
Sync Manager buffer overlap
Map size and Sync Manager size are different
Sync Manager operation invalid
Sync Manager size is 0
Incorrect direction setting
Buffer mode is incorrect
Resource depletion
Internal inconsistency
Other error
FFFF hex No error
For details, refer to Chapter 6 Handling of Errors and Maintenance.
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 21
5 CiA402 Drive Profile
5-7 Device Profile area
5-7-1 Drive Profile Objects
This chapter explains about the supported CiA402 drive profile.
603F hex Error code
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit:
Access: RO
Default setting: 0000 hex
PDO map: Possible
• This object gives the latest error code or warning code that occurred in the unit.
All
Index
603F hex
Name
Error code U16
Data type Specifications
0000 hex: No error
5300 hex: No response from the inverter
6331 hex: EEPROM data error
6341 hex: PDO setting error
FF00 hex: Warning occurred for the inverter
FF01 hex: Trip occurred for the inverter
6040 hex Controlword
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit:
Access: RW
Default setting: 0000 hex
• This object controls the state transitions of the unit.
• Bit descriptions
PDO map: Possible
All
Bit
0
1
2
3
4 to 6
7
8 to 15
Name
Switch on
Enable voltage
Quick stop
Enable operation
Reserved
Fault reset
Reserved
Details
The state is controlled by these bits.
Quick stop is not supported. Even when the bit 2 is set to 0, it is ignored.
For details, refer to 5-1-3 Command Coding on page 5-3.
Not used. Always keep at 0.
Faults and warnings are cleared when this bit turns ON.
Not used. Always keep at 0.
6041 hex Statusword
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit:
Access: RO
Default setting: 0000 hex
• This object gives the present state of the unit.
• Bit descriptions
PDO map: Possible
All
5
6
3
4
7
Bit
0
1
2
Name
Ready to switch on
Switched on
Operation enabled
Fault
Voltage enabled
Quick stop
Switch on disabled
Warning
Details
These bits give the state.
For details, refer to 5-1-4 State Coding on page 5-3.
8
9
10 to 15
Reserved
Remote
Reserved
0: No warning occurred for the unit or inverter.
1: Warning occurred for the unit or inverter.
Not used.
0: Control from Controlword is disabled.
1: Indicates that control is being performed by Controlword.
Not used.
5 - 22
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
6042 hex vl target velocity vl
Setting range: 8000 to 7FFF hex
Size: 2 bytes (INT16)
Unit: rpm
Access: RW
Default setting: 0000 hex
PDO map: Possible
• This object gives a command speed and rotation direction command to the inverter.
6043 hex vl velocity demand
Setting range: 8000 to 7FFF hex
Size: 2 bytes (INT16)
Unit: rpm
Access: RO
Default setting: 0000 hex
• This object gives the operating speed that is sent to the inverter.
PDO map: Possible vl
6044 hex vl velocity actual value
Setting range: 8000 to 7FFF hex
Size: 2 bytes (INT16)
Unit: rpm
Access: RO
Default setting: 0000 hex
• This object gives the output speed of the inverter.
PDO map: Possible vl
6046 hex vl velocity min max amount vl
Sub-index 0: Number of entries
Setting range:
Unit: Command unit
Access: RO
Default setting: 02 hex
Size: 1 byte (U8)
Sub-index 1: vl velocity min amount
Setting range: 00000000 to FFFFFFFF hex
Size: 4 bytes (U32)
Sub-index 2: vl velocity max amount
Setting range: 00000000 to FFFFFFFF hex
Size: 4 bytes (U32)
Unit: rpm
Access: RW
Unit: rpm
Access: RW
PDO map: Not possible
Default setting: 0000000F hex
PDO map: Not possible
Default setting: 00000708 hex
PDO map: Not possible
• This object sets the maximum speed and minimum speed.
• To read and write the minimum speed, read or write the inverter parameter b082: Starting Frequency.
• To read and write the maximum speed, read or write the inverter parameter A004: Maximum
Frequency.
5
6048 hex vl velocity acceleration vl
Sub-index 0: Number of entries
Setting range:
Unit: Command unit
Access: RO Size: 1 byte (U8)
Sub-index 1: Delta speed
Setting range: 00000000 to FFFFFFFF hex
Size: 4 bytes (U32)
Sub-index 2: Delta time
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Unit: rpm
Access: RO
Unit: s
Access: RW
• This object sets the acceleration time.
Default setting: 02 hex
Default setting: 00000708 hex
PDO map: Not possible
Default setting: 000A hex
PDO map: Not possible
PDO map: Not possible
• To read the Speed (6048 to 01 hex), read the inverter parameter A004: Maximum Frequency.
• To read and write the Time (6048 to 02 hex), read and write the inverter parameter F002:
Acceleration Time Setting.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 23
5 CiA402 Drive Profile
6049 hex vl velocity deceleration vl
Sub-index 0: Number of entries
Setting range:
Unit: Command unit
Access: RO
Default setting: 02 hex
Size: 1 byte (U8)
Sub-index 1: Delta speed
Setting range: 00000000 to FFFFFFFF hex Unit: rpm
PDO map: Not possible
Default setting: 00000708 hex
Size: 4 bytes (U32)
Sub-index 2: Delta time
Setting range: 0000 to FFFF hex
Size: 2 bytes (U16)
Access: RO
Unit: s
Access: RW
Default setting: 000A hex
PDO map: Not possible
PDO map: Not possible
• This object sets the deceleration time.
• To read the Speed (6049 to 01 hex), read the inverter parameter A004: Maximum Frequency.
• To read and write the Time (6049 to 02 hex), read and write the inverter parameter F003:
Deceleration Time Setting.
605B hex Shutdown option code
Setting range: 1 Unit:
Default setting: 1
Size: 2 bytes (Int16) Access: RW PDO map: Not possible
• This object sets the behavior during Shutdown (Operation enable
Ready to switch on) .
• Explanation of set values
All
Set value
1 Deceleration stop
Stop method
605C hex Disable operation option code
All
Setting range: 1 Unit:
Size: 2 bytes (Int16) Access: RW PDO map: Not possible
• This object sets the behavior during Disable operation (Operation enable
Switched on).
• Explanation of set values
Default setting: 1
Set value
1 Deceleration stop
Stop method
605E hex
Setting range 1:
Size: 2 bytes (Int16)
Fault reaction option code
Unit:
Access: RW
Default setting: 1
• This object sets the behavior when an error occurs.
• Explanation of set values
Set value
1 Deceleration stop
All
PDO map: Not possible
Stop method
5 - 24
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 CiA402 Drive Profile
6060 hex Modes of operation
Setting range: 2
Size: 1 byte (Int8)
Unit:
Access: RW
• This object sets the operation mode.
• Explanation of set values
Value
1 Velocity mode
Default setting: 02 hex
PDO map: Possible
All
Details
6061 hex
Setting range: 0 to 10
Modes of operation display
Unit:
Size: 1 byte (Int8) Access: RO
Default setting: 02 hex
PDO map: Possible
• This object gives the present operation mode.
• The value definitions are the same as for Modes of operation (6060 hex).
All
6502 hex Supported drive modes
All
Setting range:
Size: 4 bytes (U32)
Unit:
Access: RO
Default setting: 00000002 hex
PDO map: Not possible
• This object indicates the supported operation modes.
• Bit descriptions
5
6
3
4
Bit
0
1
2
7
8
9
10 to 31
Supported mode
pp (Profile Position mode) vl (Velocity mode) pv (Profile Velocity mode) t q (Profile Torque mode)
Reserved hm (Homing mode) ip (Interpolated Position mode) csp (Cyclic Sync Position mode) csv (Cyclic Sync Velocity mode) cst (Cyclic Sync Torque mode)
Reserved
Definition
0: Not supported
1: Supported
0: Not supported
0: Not supported
0
0: Not supported
0: Not supported
0: Not supported
0: Not supported
0: Not supported
0
5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5 - 25
5 CiA402 Drive Profile
5 - 26
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Handling of Errors and
Maintenance
This chapter explains how to handle errors that occur in the EtherCAT Communication
Unit.
6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 - 1
6 Handling of Errors and Maintenance
6-1 Communication Line Errors
6-1-1 Status IndicatorExplanations and Error Handling
The 7 types of indicator lighting status are shown below.
B
SF
D
Abbreviation
ON
OFF
F
Name and status
ON
OFF
Flickering ON (50 ms) and OFF (50 ms)
Blinking ON (200 ms) and OFF (200 ms)
Single flash ON (200 ms) and OFF (1,000 ms)
Double flash ON (200 ms), OFF (200 ms), ON (200 ms) and OFF (1,000 ms)
Undefined
RUN
ON
ERR
OFF
OFF
OFF
OFF
ON
F
B
L/A IN
L/A OUT
ON
F
OFF
OFF
Meaning Remarks
During
EtherCAT communications
Link established in physical layer
Link not established in physical layer
Power supply error
Hardware error
EtherCAT communications are being executed.
The operation waiting status after the link is established in the physical layer.
The link is not established in the physical layer (cannot participate in the network).
Power is not supplied correctly to the
Communication Unit.
A hardware error has occurred.
The status is normal if either process data communications, message communications, or both are being executed.
• There was a status transition instruction from the host system during operation, and a transition was made to a status other than Operational. Check that the Master
Unit is operating correctly.Refer to the manual for the Master Unit.
• Check that the communications cable is connected correctly to the connector.
• Check that the communications cable is wired correctly.
• Check that the Master Unit is operating correctly. If using an OMRON Master Unit, check the Master Unit mode and the node address-setting rotary switches of the
Communication Unit.
• If using a Master Unit from another manufacturer, refer to the user's manual for that master.
• If there are devices that generate noise, take necessary measures against the noise to protect the Master Unit,
Communication Unit and communications cables.
• Check that power is supplied correctly to the inverter (for example, check whether the wiring of the inverter main power supply is correct, the power supply voltage has dropped, and the inverter is operating normally).
• Check that the Communication Unit is mounted correctly onto the inverter.
• Eliminate the cause of the error, and then turn the inverter power supply OFF and
ON again.
• Check that the Communication Unit is mounted correctly onto the inverter.
• Replace the Communication Unit.
6 - 2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 Handling of Errors and Maintenance
RUN
B
ERR
SF
B
OFF
D
L/A IN
L/A OUT
Invalid node address setting
EEPROM data error
Sync Manager setting error
Process data communications timeout
Safe-operational state
Pre-operational state
Init state
Meaning Remarks
The setting of the node address-setting rotary switches is invalid.
This is an EEPROM data error.
The Sync Manager setting is invalid.
An error occurred in communications.
• Check the setting of the node address-setting rotary switches, turn OFF the power supply of the inverter, and then restart it.
Use the tool to restore the default data, and restart.
Change to a correct setting.
Check the items below, turn OFF the power supply of the inverter, and then restart it.
• Is the cable length OK?
(Max. 100 m)
• Is the cable disconnected or loosen?
• Is there too much noise?
If it was generated during system operation, check the status of the host master.
An instruction to transition to safe-operational state was generated by the master.
An instruction to transition to pre-operational state was generated by the master.
An instruction to transition to init state was generated by the master.
6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 - 3
6 Handling of Errors and Maintenance
6-1-2 Troubleshooting
Errors related to the EtherCAT Communication Unit
Problem
Both the RUN and ERR indicators are
OFF
ERR indicator is lit red
ERR indicator is flashing red
RUN indicator remains flashing green and status does not change
Cause and possible corrections
Power is not supplied correctly to the Communication Unit. Check that the
Communication Unit is mounted correctly onto the inverter, and that the inverter power supply is wired correctly.Eliminate the cause of the power supply interruption, turn the inverter power supply OFF, and then restart it.
• Check that the Communication Unit is mounted correctly onto the inverter.
• The Communication Unit is faulty. Replace the Communication Unit.
• The setting of the rotary switches for node address setting is invalid. Check the setting of the rotary switches for node address setting, turn OFF the power supply of the inverter, and then restart it.
• There is an error in the Slave Unit's EEPROM memory data. Use the tool to initialize the settings.
• The Sync Manager setting is invalid. Change to a correct setting.
• An error occurred in communications. Check the connection of the communications cables and the length of the cables.
If the ERR indicator remains flashing even after checking the above items, replace the slave.
There was a status transition instruction from the host system during operation, and a transition was made to a status other than Operational. Refer to the Master Unit's manual, and check that the host Master Unit is operating correctly.
Errors related to the network
Problem
L/A IN and L/A OUT indicators remain
OFF
L/A IN and L/A OUT indicators remain flashing green
Cause and possible corrections
Slaves are not connected to the network.
• Check that the Master Unit is operating correctly. If using an OMRON Master Unit, check the Master Unit mode and the slave node addresses.
• If using a Master Unit from another manufacturer, refer to the user's manual for that master.
• Check that the communications cable is wired correctly.
• Check that the Communication Unit is mounted correctly onto the inverter, and that the power supply is wired correctly. Eliminate the cause of the power supply interruption, turn the inverter power supply OFF, and then restart it.
• Check the connector wiring to make sure that the communications cables are not disconnected.
• If the L/A IN and L/A OUT indicators of a certain slave remain OFF, replace the corresponding slave.
• If there are devices that generate noise, take necessary measures against the noise to protect the Master Unit, Communication Unit and communications cables.
• The slave status has not transitioned to Operational. Refer to the Master Unit's manual, and check that the Master Unit is operating correctly.
• If the L/A IN and L/A OUT indicators of a certain slave remain flashing, replace the corresponding slave.
6 - 4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 Handling of Errors and Maintenance
6-2 Message Errors
The abort codes for when an SDO communications error occurs are shown below.
Value
05030000 hex Toggle bit not changed
Meaning
05040000 hex SDO protocol timeout
05040001 hex Client/Server command specifier not valid or unknown
05040005 hex Out of memory
06010000 hex Unsupported access to an object
06010001 hex Attempt to read a write only object
06010002 hex Attempt to write to a read only object
06020000 hex The object does not exist in the object directory
06040041 hex The object can not be mapped into the PDO.
06040042 hex The number and length of the objects to be mapped would exceed the PDO length.
06040043 hex General parameter incompatibility reason
06040047 hex General internal incompatibility in the device
06060000 hex Access failed due to a hardware error
06070010 hex Data type does not match, length of service parameter does not match
06070012 hex Data type does not match, length of service parameter too high
06070013 hex Data type does not match, length of service parameter too low
06090011 hex Subindex does not exist
06090030 hex Value range of parameter exceeded (only for write access)
06090031 hex Value of parameter written too high
06090032 hex Value of parameter written too low
06090036 hex Maximum value is less than minimum value
08000000 hex General error
08000020 hex Data cannot be transferred or stored to the application
08000021 hex Data cannot be transferred or stored to the application because of local control
08000022 hex Data cannot be transferred or stored to the application because of the present device state
08000023 hex Object dictionary dynamic generation fails or no object dictionary is present
6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 - 5
6 Handling of Errors and Maintenance
6-3 Application Errors
6-3-1 Error Statuses
The statuses change as follows when an error is detected in the unit or inverter.
Status display
Function
Error code display
Diagnosis history
Status when error occurs
An error is notified with bit 3: Fault or bit 7: Warning of the Status object (5100 hex) and bit 3: Fault or bit 7: Warning of the Statusword object (6041 hex).
When a trip occurs for the inverter, Fault bit it turned ON, and when a warning occurs for the inverter, Warning bit is turned ON.
To cancel the error, eliminate the cause and set bit 7: Fault reset of 5000 hex
Command or bit 7: Fault reset of 6040 hex Controlword to ON.
The error codes are notified to the object 603F hex. Read with the SDO.
To check the error that occurred for the inverter, check the inverter front panel, or read object 3000 hex sub-index 13 hex with the SDO.
Errors that were detected in the unit and inverter are stored in the Diagnosis history object (10F3 hex) (up to 8 errors).
If a trip occurred for the inverter, check the trip history of the inverter.
6-3-2 Error Code List
Error code
5300 hex
6341 hex
6331 hex
FF00 hex
FF01 hex
Meaning
Error in the communication unit and inverter connection
PDO setting error
EEPROM data error
A warning occurred for the inverter
A trip occurred for the inverter
Possible correction
• Check that the Communication Unit is mounted correctly onto the inverter.
• The Communication Unit is faulty. Replace the
Communication Unit.
• A connection error occurred because a trip reset was performed with the inverter. Set the inverter C102 to 3: Trip reset only, and turn the power supply OFF and ON again.
• A connection error occurred because an initialization or mode change was performed with the inverter. Turn the inverter power supply OFF and ON again.
A set value in PDO mapping is invalid. Check the value of object 5200 and the AL Status code, and then review the PDO mapping settings.
• An error was detected in data inside EEPROM when the power supply was turned ON. Replace the Communication
Unit.
• The Diagnosis history cannot be saved because the
EEPROM has reached the end of its service life. There is no effect on operations, but if you want to use the Diagnosis history, replace the unit.
Eliminate the cause and set bit 7: Fault reset of Command
(5000 hex) or bit 7: Fault reset of Controlword (6040 hex) to
ON.
Eliminate the cause and set bit 7: Fault reset of Command
(5000 hex) or bit 7: Fault reset of Controlword (6040 hex) to
ON.
6 - 6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 Handling of Errors and Maintenance
6-3-3 List of Cause Codes for PDO Mapping Errors
Cause code
0000 hex
0001 hex
0002 hex
0003 hex
0020 hex
0021 hex
0022 hex
0023 hex
0024 hex
0040 hex
0041 hex
0042 hex
0043 hex
0044 hex
0045 hex
0046 hex
0047 hex
0048 hex
004F hex
0050 hex
0060 hex
Busy exceeded exist) exceeded
Meaning
No registered error
Device busy
Unexpectedly received data
Sync Manager assignment
PDO map number is invalid
(outside the range, does not
RxPDO map overlap
Object specified for RxPDO mapping is invalid
Total number of assignment
RxPDO object overlap
Number of PDO mapping exceeded
PDO map size exceeded
(more than 32 bits)
Incorrect object specification
(sub-index 0 is mapped)
Object not supported
5000 to 5999 and 6000 to
6999 objects mixed
Cause and possible corrections
Cannot accept the PDO allocation because the internal status is busy.
Transition again to safe-operational.
Cannot accept the PDO allocation because the internal status is busy.
Transition again to safe-operational.
Wrote to sub-index 0 of the PDO mapping in a size other than 1 byte.
Write in a 1-byte data size.
Wrote to sub-index 0 of Sync Manager in a size other than 1 byte.
Write in a 1-byte data size.
Wrote to sub-indexes 1 to 5 of Sync Manager in a size other than 2 bytes. Write in a 2-byte data size.
Allocated more than 5 PDOs to Sync Manager. Allocate 5 PDOs or less to Sync Manager.
An object was assigned that cannot be assigned to Sync Manager.
Assign within the ranges below.
Sync Manager 2PDO assignment (1C12 hex): 1600 to 1604 hex, 1700 to 1701 hex
Sync Manager 3PDO assignment (1C13 hex): 1A00 to 1A04 hex,
1B00 to 1B01 hex
The same PDO is assigned more than once to Sync Manager 2PDO assignment (1C12 hex). Correct the assignment.
An object was allocated that cannot be allocated to RxPDO. Correct the RxPDO mapping.
The total size of the objects specified with the Sync Manager PDO mapping exceeds 20 bytes. Correct the PDO mapping.
The same object is mapped more than once to RxPDO. Change the
RxPDO mapping.
3 or more objects are allocated to a single PDO. Allocate a maximum of 2 objects to a PDO.
The total size of the objects mapped to a single PDO exceeds 4 bytes.
Keep the total object size that is mapped to a PDO to within 4 bytes.
An object of sub-index 0 (number of entries, etc.) that cannot be allocated to a PDO was mapped. Remove the corresponding object from the mapping.
An object that does not exist was mapped. Correct the PDO mapping.
A sub-index of an object that does not exist was mapped. Correct the
PDO mapping.
An object from 5000 to 5999 was allocated to RxPDO mapping at the same time as an object from 6000 to 6999.Objects from 5000 to 5999 and 6000 to 6999 cannot be mixed in RxPDO, so change the mapping to only one of the ranges.
When a PDO was assigned to Sync Manager 2PDO assignment
(1C12 hex), objects from 5000 to 5999 and 6000 to 6999 were mixed in the assignment. Correct the assignment so that they are not mixed.
An object that cannot be allocated to a PDO was mapped. Correct the
PDO mapping.
The specified object data size is incorrect. Change to a correct size.
Object specified for PDO map is invalid
Incorrect data size for specified object
PDO mapping exists but size is 0
Specified access method not supported
Specified object mapping is invalid
RxPDO object overlap (MX2 registers are overlapping)
Cannot assign to Sync Manager because the PDO mapping is invalid.
Correct the PDO mapping.
PDO mapping writing was performed with complete access which is not supported. Write with single access.
There was an error in the values written with complete access. Correct the values and perform the writing.
An object that does not exist was allocated to a PDO. Correct the PDO mapping.
An object that cannot be mapped was mapped to a PDO. Correct the
PDO mapping.
The objects allocated to RxPDO are different, but the same function, such as a start command or speed reference, is allocated more than once. Change the PDO mapping.
6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 - 7
6 Handling of Errors and Maintenance
Cause code
0061 hex
0070 hex
00E0 hex
00E1 hex
00E2 hex
00E3 hex
00E4 hex
00E5 hex
00E6 hex
00E7 hex
00E8 hex
8000 to 8002 hex
FFFF hex
Meaning
Unsupported data type is specified
Unsupported mode (mode other than FreeRun is specified)
Start address of the Refresh area is 1000 hex or lower, or an odd number
Cause and possible corrections
The data type of the allocated object is invalid. Change to a correct data type.
An operation mode other than FreeRun is set. Set FreeRun mode.
Specified size of the Refresh area exceeds the range
Start address of the Refresh area is different from the value in pre-operational
(Pre-Op)
Incorrect direction setting
Buffer mode is incorrect
Other error
No error
The start address of Sync Manager is set to a value lower than 1000 hex. Change the start address to 1000 hex or higher.
The start address of Sync Manager is set to an odd number. Change the start address to an even number.
The used area of Sync Manager exceeds 2FFF hex. Change the start address.
The start address of Sync Manager is different from the value set during pre-operational. Transition again from pre-operational to safe-operational.
Sync Manager buffer overlap Sync Manager areas are overlapping. Correct the start address.
Map size and Sync Manager size are different
The assignment size and Sync Manager area size do not match.
Match the sizes.
The mapping size is set to 0.Correct the mapping.
Sync Manager operation invalid
Sync Manager size is 0
Cannot operate Sync Manager because the PDO mapping is invalid.
Correct the PDO mapping.
The size assigned to Sync Manager was set to 0 because the PDO mapping is invalid. Correct the PDO mapping.
The access direction (read/write) setting of Sync Manager is incorrect.
Change the setting.
The Butter mode setting of Sync Manager is incorrect. Change the setting.
An error other than those above occurred. Turn the power supply OFF and ON again. If the problem persists, replace the unit.
6 - 8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 Handling of Errors and Maintenance
6-3-4 AL Status Code List
Code
0011 hex
0012 hex
0014 hex
0016 hex
001B hex
001D hex
001E hex
001F hex
0024 hex
0025 hex
0028 hex
Meaning
Invalid status transition request received
Error status transition received
SII verification error
Mailbox setting error
Process data WDT error
RxPDO setting error
Cause and possible corrections
An impossible status transition request was received. Perform the status transition again.
A transition request to an unknown status was received. Perform the status transition again.
The data written in SII and the data inside the unit do not match.
Rewrite the SII data to the correct values. If the problem persists, replace the unit.
A mailbox setting is invalid. Set to the correct value.
In the operational state, the data set with RxPDO was not received for a certain time. Check that the network is connected correctly. Check that RxPDO is being refreshed on the master.
An RxPDO (Sync Manager) setting error was detected. Correct the
RxPDO mapping setting. For the detailed cause, check the contents of object 5200 hex.
TxPDO setting error
PDO WDT setting error
TxPDO mapping error
A TxPDO (Sync Manager) setting error was detected. Correct the
TxPDO mapping setting. For the detailed cause, check the contents of object 5200 hex.
The WDT setting of a PDO is invalid. Set a correct value.
An invalid TxPDO is set. Correct the TxPDO mapping setting. For the detailed cause, check the contents of object 5200 hex.
RxPDO mapping error An invalid RxPDO is set. Correct the RxPDO mapping setting. For the detailed cause, check the contents of object 5200 hex.
SM event mode setting error Set to an unsupported SM event mode. Set a correct value.
6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6 - 9
6 Handling of Errors and Maintenance
6-4 Inverter Errors
The trips that occur for inverters when using an optional board are as follows.
Name
Option error
Option timeout
Meaning
When an unrecoverable error is detected in the optional board, a trip is generated for the inverter.
Error code
E60.
@
A trip occurs when a timeout is generated in communication between the inverter and optional PCB.
E69.
@
Check point and remedy
The inverter unit version is old.
Check that the unit version of the inverters is 1.1 or higher
(1.0 or lower do not operate).Replace the inverter.
Generated when a trip reset was performed with the inverter.
Set C102 to 3: Trip reset only, and turn the power supply
OFF and ON again.
Generated when an initialization or mode change was performed with the inverter.
Turn the power supply OFF and ON again.
The optional board is disconnected.
Check that the optional board case and inverter are fitted together correctly, and check for looseness in the fastening screw.
The inverter or optional board is faulty.
If they are fitted together correctly, the inverter or optional
PCB may be faulty. Replace the inverter or optional board.
The optional board is disconnected.
Check that the optional board case and inverter are fitted together correctly, and check for looseness in the fastening screw.
The optional board is faulty.
If they are fitted together correctly, the optional PCB may be faulty. Replace the optional board.
6 - 10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
pp
Appendices
This chapter explains the specifications of the EtherCAT Communication Unit as well as objects and inverter parameters handled by/set in the EtherCAT Communication Unit.
A-2 Communications Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-1
Appendices
A-1 Specifications
A-1-1 Appearance and Dimensions
Status Indicator
67.6
Rotary switches for node address setting
44.9
28.6
FG cable
Communications connector (IN)
10.3 10.3
Communications connector (OUT)
26.4mm*1
53.1
D*1
FG cable
*1 After the EtherCAT Communication Unit is installed, dimension D of the inverter increases by 26.4 mm.
(Dimension D of the inverter varies depending on the capacity. Refer to the manual for the inverter.)
A-1-2 Common Specifications
Item
Model
Power supply
Protective structure
Temperature
Storage temperature
Humidity
Vibration
Application environment
Weight
Specifications
3G3AX-MX2-ECT
Supplied from the inverter
Open type (IP20)
10 to 50C
20 to 65C
20% to 90% RH (with no condensation)
5.9 m/s
2
(0.6 G), 10 to 55 Hz
At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust)
100 g max.
A-2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
A-1-3 EtherCAT Communications Specifications
Item
Communications standard
Physical layer
Connector
Communications media
Communications distance
Process data
Mailbox (CoE)
Distributed clock
LED display
CiA402 drive profile
Specifications
IEC 61158 Type12, IEC 61800-7 CiA 402 drive profile
100BASE-TX (IEEE802.3)
RJ45
2 (shielded type)
ECAT IN: EtherCAT input
ECAT OUT: EtherCAT output
Category 5 or higher (cable with double, aluminum tape and braided shielding) is recommended.
Distance between nodes: 100 m max.
Fixed PDO mapping
PDO mapping
Emergency messages, SDO requests, SDO responses, and SDO information
FreeRun mode (asynchronous)
L/A IN (Link/Activity IN)
1
L/A OUT (Link/Activity OUT)
1
RUN
1
ERR
1
Velocity mode
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-3
Appendices
A-2 Communications Response Time
The table below lists the communications response time.
CJ1W-NCx82 Master
Starting time
Data transmitting time
Meaning
Write
Read
Performance
Approx. 10 to 14 ms
Approx. 27 ms/pc
Approx. 24 ms/pc
Conditions
Time after the inverter is started from the PLC until the motor produces output *
CJ1W-NCx82 When the communication cycle is 250
s
Time needed to write/read inverter parameters from the PLC
CJ1W-NCx82 When the communication cycle is 250
s
Varies depending on the number of allocated PDOs IO data updating cycle 4 ms or 6 ms
* Due to the characteristics of EtherCAT, the result will become the same with any node as long as the communication cycle is the same.
NJ501-1x00 Master
Starting time
Data transmitting time
Meaning
Write
Read
Performance
Approx. 6 to 10 ms
Approx. 7 ms/pc
Approx. 6 ms/pc
Conditions
Time after the inverter is started from the PLC until the motor produces output *
NJ501-1x00 When the communication cycle is 500
s
Time needed to write/read inverter parameters from the PLC
NJ501-1x00 When the communication cycle is 500
s
Varies depending on the number of allocated PDOs IO data updating cycle 4 ms or 6 ms
* Due to the characteristics of EtherCAT, the result will become the same with any node as long as the communication cycle is the same.
A-4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
A-3 Object List
A-3-1 Object List
Index
Subindex
1000 hex 0
Object name
Device type
1001 hex 0 Error register
1008 hex 0
1009 hex 0
100A hex 0
1010 hex
1011 hex
1018 hex
10F3 hex
2
3
0
1
4
0
1
Manufacturer device name
Manufacturer hardware version
Manufacturer software version
Store parameters
Number of entries
Save all parameters
Restore default parameters
Number of entries
Restore all default parameters
Identity object
Number of entries
Vendor ID
Product code
Revision number
Serial number
Diagnosis history
Number of entries
Maximum messages
2
5
Newest message
Flags
1600 to
1604 hex
0
6 to 13 Diagnosis message 1 to 8
1st to 5th receive PDO mapping
Number of objects
06 to 0D hex
0000 to
0001 hex
1 1st object
(1st Output Object to be mapped)
2 2nd object
(2nd Output Object to be mapped)
*1 "V*.**" which shows the hardware version is saved.
Setting range
00 to 08 hex
Unit
Default setting Size
00010192 hex 4 bytes (U32)
0 1 byte (U8)
00000000 hex
00 hex
00 hex
06 hex
0001 hex
0
00000000 hex
00000000 hex
3G3AX-MX2-ECT 20 bytes (VS)
*1 20 bytes (VS)
*1
01 hex
00000001 hex
01 hex
20 bytes (VS)
1 byte (U8)
4 bytes (U32)
1 byte (U8)
00000001 hex
04 hex
00000083 hex
00000053 hex
XXXXXXXX hex
4 bytes (U32)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
1 byte (U8)
1 byte (U8)
2 bytes (U16)
23 bytes (VS)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
RO
RO
RW
RO
RO
RO
RO
RW
RW
RO
Access
RO
RO
RO
RO
RO
RO
RO
RO
RO
RW
RW
RW
PDO map
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
A-5
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
1700 hex
Subindex
0
Object name
257th fixed receive PDO mapping
Number of objects
Setting range
1701 hex
1A00 to
1A04 hex
0
1B00 hex
1B01 hex
1BFF hex
1C00 hex
1C10 hex
1C11 hex
1
2
0
1
2
1
2
0
1
2
0
1
2
0
1
0
1
2
3
4
0
0
1st object
(1st Output Object to be mapped)
2nd object
(2nd Output Object to be mapped)
258th fixed receive PDO mapping
Number of objects
1st object
(1st Output Object to be mapped)
2nd object
(2nd Output Object to be mapped)
1st to 5th transmit PDO mapping
Number of objects
1st object
(1st Input Object to be mapped)
2nd object
(2nd Input Object to be mapped)
257th fixed transmit PDO mapping
Number of objects
1st object
(1st Input Object to be mapped)
2nd object
(2nd Input Object to be mapped)
258th fixed transmit PDO mapping
Number of objects
1st object
(1st Input Object to be mapped)
2nd object
(2nd Input Object to be mapped)
512th transmit PDO Mapping
Number of objects in this PDO
1st Input Object to be mapped
Communication type SM0
Sync manager communication type
Number of used SM channels
Communication type SM1
Communication type SM2
Communication type SM3
Sync Manager 0 PDO assignment
Number of assigned PDOs
Sync Manager 1 PDO assignment
Number of assigned PDOs
Default setting Size
2
1 byte (U8)
02 hex
03 hex
04 hex
00 hex
00 hex
51000010 hex
51100010 hex
01 hex
20020108 hex
04 hex
01 hex
60400010 hex
60420010 hex
2
50000010 hex
50100010 hex
2
00000000 hex
00000000 hex
2
60410010 hex
60430010 hex
2
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
4 bytes (U8)
1 byte (U8)
4 bytes (U8)
4 bytes (U8)
4 bytes (U8)
4 bytes (U8)
1 byte (U8)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
Unit
RO
RO
RO
RO
RO
RO
RO
RO
RW
RW
RO
RO
RO
RO
RO
Access
RO
RO
RO
RW
RO
RO
RO
RO
RO
PDO map
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
A-6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
1C12 hex
Subindex
0
Object name
Sync manager 2 PDO assignment
Number of assigned RxPDOs
Setting range
1C13 hex
1C32 hex
1C33 hex
2002 hex
1
2
3
4
5
0
1
2
3
4
5
0
1
4
0
1
4
0
1
2
2100 hex 0
5000 hex 0
5010 hex 0
5100 hex 0
Unit
Default setting Size
01 hex
1 byte (U8)
Assigned PDO 1
(1st PDO Mapping object index of assigned PDO)
Assigned PDO 2
(2nd PDO Mapping object index of assigned PDO)
Assigned PDO 3
(3rd PDO Mapping object index of assigned PDO)
Assigned PDO 4
(4th PDO Mapping object index of assigned PDO)
Number of assigned TxPDOs
Assigned PDO 5
(5th PDO Mapping object index of assigned PDO)
Sync Manager 3 PDO assignment
Assigned PDO 1
(1st PDO Mapping object index of assigned PDO)
Assigned PDO 2
(2nd PDO Mapping object index of assigned PDO)
Assigned PDO 3
(3rd PDO Mapping object index of assigned PDO)
Assigned PDO 4
(4th PDO Mapping object index of assigned PDO)
Assigned PDO 5
(5th PDO Mapping object index of assigned PDO)
SM2 synchronization
Number of synchronization parameter
Synchronization type
Synchronization types supported
SM3 synchronization
Number of synchronization parameter
Synchronization type
Synchronization types supported
Sysmac Error
Number of entries
Sysmac Error Status
Sysmac Error Status Clear
Error history clear
Command
Frequency reference
Status
1701 hex
0000 hex
0000 hex
0000 hex
0000 hex
01 hex
1B01 hex
0000 hex
0000 hex
0000 hex
0000 hex
20 hex
0000 hex
0001 hex
20 hex
0000 hex
0001 hex
02 hex
00 hex
00 hex
6C636C65 hex
0000 to
FFFF hex
0000 to
FFFF hex
0000 to
FFFF hex
00000000 hex
0000 hex
0.01 Hz
(0.1 Hz)
0000 hex
0000 hex
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
1 byte (U8)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
1 byte (U8)
2 bytes (U16)
2 bytes (U16)
1 byte (U8)
2 bytes (U16)
2 bytes (U16)
1 byte (U8)
1 byte (U8)
1 byte (U8)
4 bytes (U32)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
RW
RW
Access
RW
RW
PDO map
Not possible
Not possible
RW Not possible
RW
RW
RW
RW
RW
RW
RW
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Possible
(TxPDO)
Not possible
Not possible
Possible
Not possible
Not possible
Not possible
Not possible
Possible
Possible
(TxPDO)
Not possible
Not possible
Not possible
Not possible
Not possible
RO
RW
RW
RW
RW
RO
RO
RW
RO
RO
RW
RO
RO
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-7
Appendices
Index
Subindex
5110 hex 0
5200 hex
0
1
Object name
Output frequency monitor
PDO mapping error history
Number of entries
Newest PDO mapping error code
Setting range
0000 to
FFFF hex
Unit Default setting Size
2 bytes (U16) Unit:
0.01 Hz
(0.1 Hz)
0000 hex
0A hex
FFFF hex
1 byte (U8)
2 bytes (U16)
603F hex
6040 hex
6041 hex
6042 hex
6043 hex
6044 hex
6046 hex
6048 hex
6049 hex
605B hex
605C hex
4
5 to A
0
0
0
0
0
0
0
1
2
0
1
2
0
1
2
0
0
Number of error messages
PDO mapping error message 1 to
6
Error code
Controlword
Statusword vl target velocity vl velocity demand vl velocity actual value vl velocity min max amount
Number of entries
0000 to
FFFF hex
0000 to
FFFF hex
0000 to
FFFF hex
8000 to
7FFF hex
8000 to
7FFF hex
8000 to
7FFF hex vl velocity min amount vl velocity max amount vl velocity acceleration
Number of entries
Delta speed
Delta time vl velocity deceleration
Number of entries
Delta speed
0000 hex
0000 hex
0000 hex
0000 hex
0000 hex
0000 hex
0000 hex
00000000 to
FFFFFFFF hex
00000000 to
FFFFFFFF hex rpm
Command unit
02 hex rpm 0000000F hex
00000708 hex
Command unit
02 hex rpm 00000708 hex 00000000 to
FFFFFFFF hex
0000 to
FFFF hex
rpm rpm rpm s
Command unit rpm
000A hex
02 hex
00000708 hex
Delta time
Shutdown option code
00000000 to
FFFFFFFF hex
0000 to
FFFF hex
1 s
000A hex
1
Disable operation option code
1
00 hex
1
605E hex
6060 hex
6061 hex
6502 hex
0
0
0
0
Fault reaction option code
Modes of operation
Modes of operation display
Supported drive modes
1
2
0 to 10
1
02 hex
02 hex
00000002 hex
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (U16)
2 bytes (INT16)
2 bytes (INT16)
2 bytes (INT16)
1 byte (U8)
4 bytes (U32)
4 bytes (U32)
1 byte (U8)
4 bytes (U32)
2 bytes (U16)
1 byte (U8)
4 bytes (U32)
2 bytes (U16)
2 bytes (INT16)
2 bytes (INT16)
2 bytes (INT16)
1 byte (INT8)
1 byte (INT8)
4 bytes (U32)
Access
RO
RO
RO
RO
RO
RO
RW
PDO map
Possible
(TxPDO)
Not possible
Not possible
Not possible
Not possible
Possible
(TxPDO)
Possible
Possible
(TxPDO)
Possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Not possible
Possible
(TxPDO)
Possible
(TxPDO)
Not possible
Not possible
Not possible
Not possible
Not possible
Possible
Possible
(TxPDO)
Not possible
RO
RW
RO
RW
RW
RO
RO
RW
RO
RO
RO
RO
RW
RW
RW
RW
RW
RO
RO
A-8
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
A-4 Inverter Parameter List
Inverter parameters are allocated to objects 3000 to 3102 hex and 4000 to 4102 hex.
3000 to 3102 hex are 16-bit parameters and 4000 to 4102 hex are 32-bit parameters.
Index and sub-index calculation method
Index: 3000 hex + (N/254), Sub-index: 1 + (N%254)
Index: 4000 hex + (N/254), Sub-index: 1 + (N%254)
N: Inverter register number
(N/254): Integer part after N is divided by 254
(N%254): Remainder after N is divided by 254
Holding register number list (frequency reference and fault monitor)
Index
4000 hex
3000 hex
3000 hex
3000 hex
3000 hex
3000 hex
3000 hex
4000 hex
3000 hex
3000 hex
4000 hex
4000 hex
07 hex
12 hex
13 hex
15 hex
17 hex
18 hex
19 hex
1B hex
Subindex
02 hex
05 hex
06 hex
14 hex
Register
No.
0004 hex
0005 hex
0006 hex
0011 hex
0012 hex
0013 hex
Function name
0001 hex Output Frequency
Setting
Inverter Status B
Inverter Status C
PID Feedback
Fault Counter
Fault Monitor 1
Cause
Fault Monitor 1
Inverter Status
0014 hex Fault Monitor 1
Frequency
0016 hex Fault Monitor 1
Current
0017 hex Fault Monitor 1 Voltage
0018 hex Fault Monitor 1
001A hex
RUN Time
Fault Monitor 1
ON Time
Parameter
No.
F001
R/W
RW
d080 d081
RO
RO
RO
RO
RO
Monitor and setting items
0 to maximum frequency (enabled when A001 = 03)
0: Stopped
1: During operation
2: During trip
0:
1: Stop
2: Deceleration
3: Constant speed
4: Acceleration
5: Forward
6: Reverse
7: Forward to reverse
8: Reverse to forward
9: Forward run start
10: Reverse run start
0 to 10000
Data resolution
0.01 [Hz]
0.01 [%]
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0 to 65530 1 [time]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Refer to Inverter Fault Factor List in the operation manual for the MX2 inverter.
Refer to Inverter Fault Factor List in the operation manual for the MX2 inverter.
0 to 100000
0.01 [Hz]
Possible
(TxPDO)
Output current value at the time of tripping
DC input voltage at the time of tripping
Total RUN time at the time of tripping
Power ON time at the time of tripping
0.01 [A]
0.1 [V]
1 [h]
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
A-9
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
4000 hex
4000 hex
3000 hex
3000 hex
3000 hex
4000 hex
3000 hex
3000 hex
4000 hex
3000 hex
3000 hex
4000 hex
4000 hex
3000 hex
4000 hex
4000 hex
3000 hex
3000 hex
3000 hex
4000 hex
3000 hex
3000 hex
3000 hex
4000 hex
4000 hex
3000 hex
3000 hex
4000 hex
40 hex
41 hex
43 hex
3B hex
3C hex
3D hex
3F hex
35 hex
36 hex
37 hex
39 hex
2F hex
31 hex
32 hex
33 hex
29 hex
2B hex
2C hex
2D hex
23 hex
25 hex
27 hex
28 hex
Subindex
1D hex
1E hex
1F hex
21 hex
22 hex
Register
No.
001C hex
Function name
Fault Monitor 2
Cause
001D hex
001E hex
Fault Monitor 2
Inverter Status
Fault Monitor 2
Frequency
0020 hex Fault Monitor 2
Current
0021 hex Fault Monitor 2 Voltage
Parameter
No.
d082
0022 hex Fault Monitor 2
RUN Time
0024 hex Fault Monitor 2
ON Time
0026 hex Fault Monitor 3
Cause
0027 hex Fault Monitor 3
Inverter Status
0028 hex Fault Monitor 3
Frequency
002A hex
Fault Monitor 3
Current
Fault Monitor 3 Voltage 002B hex
002C hex
Fault Monitor 3
RUN Time d083
002E hex
Fault Monitor 3
ON Time
0030 hex Fault Monitor 4
Cause
0031 hex Fault Monitor 4
Inverter Status
0032 hex Fault Monitor 4
Frequency
0034 hex Fault Monitor 4
Current
0035 hex Fault Monitor 4 Voltage d084
0036 hex Fault Monitor 4
RUN Time
0038 hex Fault Monitor 4
ON Time
003A hex
003B hex
Fault Monitor 5
Cause
Fault Monitor 5
Inverter Status
003C hex
003E hex
Fault Monitor 5
Frequency
Fault Monitor 5
Current
003F hex Fault Monitor 5 Voltage d085
0040 hex Fault Monitor 5
RUN Time
0042 hex Fault Monitor 5
ON Time
R/W
RO
RO
RO
RO
Monitor and setting items
Refer to Inverter fault factor list on page A-12.
Refer to Inverter fault factor list on page A-12.
0 to 100000
Output current value at the time of tripping
DC input voltage at the time of tripping
Total RUN time at the time of tripping
Power ON time at the time of tripping
Refer to Inverter fault factor list on page A-12.
Refer to Inverter fault factor list on page A-12.
0 to 100000
Output current value at the time of tripping
DC input voltage at the time of tripping
Total RUN time at the time of tripping
Power ON time at the time of tripping
Refer to Inverter fault factor list on page A-12.
Refer to Inverter fault factor list on page A-12.
0 to 100000
Output current value at the time of tripping
DC input voltage at the time of tripping
Total RUN time at the time of tripping
Power ON time at the time of tripping
Refer to Inverter fault factor list on page A-12.
Refer to Inverter fault factor list on page A-12.
0 to 100000
Output current value at the time of tripping
DC input voltage at the time of tripping
Total RUN time at the time of tripping
Power ON time at the time of tripping
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [A]
0.1 [V]
Possible
(TxPDO)
Possible
(TxPDO)
1 [h]
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [A] Possible
(TxPDO)
0.1 [V]
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [A]
0.1 [V]
Possible
(TxPDO)
Possible
(TxPDO)
1 [h]
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [A] Possible
(TxPDO)
0.1 [V]
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
1 [h] Possible
(TxPDO)
A-10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3000 hex
3000 hex
4000 hex
4000 hex
3000 hex
3000 hex
4000 hex
3000 hex
3009 hex
3009 hex
Subindex
45 hex
46 hex
47 hex
49 hex
4A hex
4B hex
4D hex
4F hex
13 hex
Register
No.
Function name
0044 hex Fault Monitor 6
Cause
0045 hex Fault Monitor 6
Inverter Status
0046 hex Fault Monitor 6
Frequency
0048 hex Fault Monitor 6
Current
0049 hex Fault Monitor 6 Voltage
004A hex
004C hex
Fault Monitor 6
RUN Time
Fault Monitor 6
ON Time
004E hex
Warning Monitor
0900 hex EEPROM Write
Parameter
No.
d086 d090
R/W
RO
RO
WO
15 hex
0902 hex EEPROM Write Mode
Selection
WO
Monitor and setting items
Refer to Inverter fault factor list on page A-12.
Refer to Inverter fault factor list on page A-12.
0 to 100000
Output current value at the time of tripping
DC input voltage at the time of tripping
Total RUN time at the time of tripping
Power ON time at the time of tripping
Warning code
0: Motor parameter recalculation
1: Set value storage in EEPROM
Other: Motor parameter recalculation and EEPROM
0: Write disabled
1: Write enabled
Data resolution
PDO map
Possible
(TxPDO)
0.01 [Hz]
0.01 [A]
0.1 [V]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
1 [h]
1 [h]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Not possible
Not possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-11
Appendices
Inverter fault factor list
Trip factor high-order (factor)
Name Code
No trip factor
Overcurrent protection during constant speed
Overcurrent protection during deceleration
2
3 Overcurrent protection during acceleration
Overcurrent protection during stop
Overload protection
0
1
Braking resistor overload protection
Overvoltage protection
EEPROM error
Undervoltage protection
6
7
4
5
Current detector error
CPU error
External trip
USP error
8
9
10
11
Grounding protection
Incoming overvoltage protection
Abnormal temperature
Main circuit error
12
13
14
15
Driver error
Thermistor error
Brake error
Emergency shutoff
21
25
30
35
36
37
Overload protection in a low speed range
Digital operator connection error
38
40
Modbus communication (Modbus-RTU) error
41
Internal data error 43 to 45
50 to 69
Encoder disconnection
Overspeed
Position control range trip
80
81
83
Trip factor low-order (Inverter status)
Name Code
During reset
During stop
0
1
During deceleration
At a constant speed
2
3
During acceleration
Operates at frequency = 0
During startup 6
DB active (DC injection braking active) 7
During overload limit
4
5
8
A-12
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Holding register number list (monitor)
4010 hex
3010 hex
3010 hex
Index
4010 hex
3010 hex
3010 hex
4010 hex
3010 hex
3010 hex
3010 hex
4010 hex
4010 hex
3010 hex
3010 hex
4010 hex
4010 hex
3010 hex
3010 hex
4010 hex
4010 hex
3010 hex
3010 hex
3010 hex
3010 hex
31 hex
32 hex
33 hex
34 hex
2C hex
2E hex
2F hex
36 hex
38 hex
3A hex
3E hex
57 hex
59 hex
78 hex
47 hex
48 hex
49 hex
26 hex
28 hex
29 hex
Subindex
22 hex
24 hex
25 hex
Register
No.
1001 hex Output Frequency
1003 hex
Function name
Monitor
Output current monitor
1004 hex Rotation Direction
Monitor
Parameter
No
d001 d002 d003
R/W
RO
RO
RO
2A hex
1005 hex PID Feedback Value
Monitor
1007 hex Multi-function Input
Monitor
1008 hex Multi-function output monitor d004 d005 d006
RO
RO
RO
RO
Monitor and setting items
0 to 40000 (100000)
0 to 65530
0: Stop
1: Forward
2: Reverse
0 to 1000000
2
0
2
1
2
0
: Terminals S1
to 2
6
: Terminals S7/EB
: Terminals P1/EDM to 2
1
: Terminal P2
2
6
: Relay output terminal
0 to 4000000 (10000000) 1009 hex Output Frequency
Monitor (after conversion)
100B hex
Real Frequency
Monitor d007 d008
100D hex
100E hex
Torque Reference
Monitor
Torque Bias Monitor d009 d010
1010 hex Output Torque Monitor d012
RO
RO
RO
RO
1011 hex
1012 hex
Output Voltage
Monitor
Input Power Monitor
1013 hex Integrated Power
Monitor
1015 hex Total RUN Time
Monitor
1017 hex Power ON Time
Monitor
1019 hex Fin Temperature
Monitor
101D hex
1026 hex
Life Assessment
Monitor
DC Voltage Monitor
1027 hex Regenerative Braking
Load Rate Monitor
1028 hex Electronic Thermal
Load Rate Monitor
1036 hex Position Reference
Monitor
1038 hex Current position monitor d013 d014 d015 d016 d017 d018 d022 d102 d103 d104 d029 d030
1057 hex Inverter Mode Monitor d060
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
Data resolution
0.01 [Hz]
0.01 [A]
0.1
Bit
Bit
0.01
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
100000 to +100000
200 to +200
200 to +200
200 to +200
0 to 6000
0 to 9999
0 to 9999000
0 to 999000
0 to 999000
200 to 1500
2
0
: Capacitor on main circuit board
2
1
: Cooling fan
0 to 10000
Bit
0.1 [V]
0 to 1000
0 to 1000
268435455 to 268435455
268435455 to 268435455
0: I-C (IM heavy load)
1: I-V (IM light load)
2: H-I (IM power supply harmonics)
0.01 [Hz]
1 [%]
1 [%]
1 [%]
0.1 [V]
0.1 [kW]
1 [h]
1 [h]
0.1 [
1
1
C]
0.1 [%]
0.1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-13
Appendices
Holding register number list (F group)
Index
4011 hex
4011 hex
3011 hex
Subindex
26 hex
28 hex
2A hex
Register
No.
Function name
1103 hex Acceleration Time
Setting 1
1105 hex Deceleration Time
Setting 1
1107 hex RUN Direction
Selection
Parameter
No.
F002
R/W
RW
Monitor and setting items
1 to 360000
F003
F004
RW 1 to 360000
RW 0: Forward
1: Reverse
Holding register number list (A, b, C, H, P group)
Data resolution
PDO map
0.01 [s] Possible
Possible 0.01 [s]
Possible
(TxPDO)
Index
3012 hex
3012 hex
Subindex
26 hex
27 hex
Register
No.
1201 hex
1202 hex
Function name
Frequency Reference
Selection 1
RUN Command
Selection 1*
Parameter
No.
A001
A002
R/W
RW
RW
Monitor and setting items
00: Volume
01: Control circuit terminal block
02: Digital operator
03: Modbus communication
(Modbus-RTU)
04: Optional board
06: Pulse train frequency
07: Do not set.
10: Operation function output
01: Control circuit terminal block
02: Digital operator
03: Modbus communication
(Modbus-RTU)
04: Optional board
300 to Maximum Frequency 1
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
3012 hex
3012 hex
3012 hex
28 hex
29 hex
2A hex
1203 hex
1204 hex
Base Frequency 1
Maximum Frequency 1
A003
A004
RW
RW 300 to 4000 (10000)
0.1 [Hz]
0.1 [Hz]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
3012 hex
3012 hex
3012 hex
4012 hex
4012 hex
3012 hex
3012 hex
36 hex
37 hex
3A hex
30 hex
32 hex
34 hex
35 hex
1205 hex FV/FI Selection
120B hex
120D hex
FV Start Frequency
FV End Frequency
120F hex FV Start Ratio
A005 RW 00: Switch between FV/FI
02: Switch between FV/volume
03: Switch between FI/volume
0 to 40000 (100000)
4012 hex
3B hex
1210 hex
1211 hex
1212 hex
1215 hex
1216 hex
FV End Ratio
FV Start Selection
FV, FI sampling
Multi-step Speed
Selection
Multi-step Speed 1
Reference 0
A011
A012
A013
A014
A015
A016
A019
A020
RW
RW
RW
RW
RW
RW
RW
RW
0 to 40000 (100000)
0 to 100
0 to 100
00: Start frequency
01: 0 Hz
1 to 30/31 (with 500 ms filter
0.1
Hz hysteresis)
00: Binary 16-step selection with 4 terminals
01: Bit 8-step selection with 7 terminals
0
Starting Frequency to Maximum
Frequency 1
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
1
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
* After changing the RUN Command Selection 1, provide an interval of at least 40 ms before the RUN command is actually executed.
A-14
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
4012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
Subindex
3D hex
Register
No.
Function name
1218 hex Multi-step Speed
Reference 1
3F hex
41 hex
43 hex
45 hex
47 hex
49 hex
4B hex
4D hex
4F hex
51 hex
53 hex
55 hex
57 hex
59 hex
5D hex
5E hex
60 hex
61 hex
62 hex
63 hex
64 hex
121A hex
121C hex
121E hex
1220 hex
1222 hex
1224 hex
1226 hex
1228 hex
122A hex
122C hex
122E hex
1230 hex
1232 hex
1234 hex
1238 hex
1239 hex
123B hex
123C hex
123D hex
123E hex
123F hex
Multi-step Speed
Reference 2
Multi-step Speed
Reference 3
Multi-step Speed
Reference 4
Multi-step Speed
Reference 5
Multi-step Speed
Reference 6
Multi-step Speed
Reference 7
Multi-step Speed
Reference 8
Multi-step Speed
Reference 9
Multi-step Speed
Reference 10
Multi-step Speed
Reference 11
Multi-step Speed
Reference 12
Multi-step Speed
Reference 13
Multi-step Speed
Reference 14
Multi-step Speed
Reference 15
Jogging Frequency
Jogging Stop
Selection
Torque Boost
Selection 1
Manual Torque Boost
Voltage 1
Manual Torque Boost
Frequency 1
Control Method 1
A041
A042
A043
A044
Output Voltage Gain 1
Parameter
No.
A021
R/W
RW
A022
A023
A024
A025
A026
A027
A028
A029
A030
A031
A032
A033
A034
A035
A038
A039
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
0
Starting Frequency to nth Maximum
Frequency
Starting Frequency to 999 (10000)
Data resolution
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
PDO map
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
00: Free run on jogging stop/Disabled in operation
01: Deceleration stop on jogging stop/Disabled in operation
02: DC injection braking on jogging stop/Disabled in operation
03: Free run on jogging stop/Enabled in operation
04: Deceleration stop on jogging stop/Enabled in operation
05: DC injection braking on jogging stop/Enabled in operation
00: Manual torque boost
01: Automatic torque boost
0 to 200
0.1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
A045
RW
RW
RW
0 to 500
00: Constant torque characteristics
01: Reduced torque characteristics
02: Free V/f setting
03: Sensorless vector control
20 to 100
0.1 [%]
1 [%]
Possible
Possible
(TxPDO)
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-15
Appendices
A-16
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
4012 hex
4012 hex
4012 hex
3012 hex
4012 hex
3012 hex
4012
Index
3012 hex
3012 hex
3012 hex
4012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
85 hex
86 hex
87 hex
88 hex
89 hex
7D hex
7E hex
80 hex
81 hex
78 hex
7A hex
7B hex
83 hex
84 hex
6E hex
6F hex
70 hex
71 hex
6B hex
6C hex
6D hex
72 hex
74 hex
Subindex
65 hex
66 hex
6A hex
Register
No.
Function name
1240 hex Automatic Torque
Boost Voltage
Compensation Gain 1
1241 hex Automatic Torque
Boost Slip
Compensation Gain 1
1245 hex Internal DC Injection
Braking Selection
Parameter
No.
A046
A047
A051
R/W
RW
RW
RW
RW
Monitor and setting items
0 to 255
0 to 255
00: Disabled
01: Enabled during stop
02: Output frequency (at A052)
0 to 6000 1246 hex Internal DC Injection
Braking Frequency
1247 hex DC Injection Braking
Delay Time
1248 hex DC Injection Braking
Power
1249 hex DC Injection Braking
Time
124A hex
DC Injection Braking
Edge/Level Selection
124B hex
124C hex
Startup DC Injection
Braking Power
Startup Internal DC
Injection Braking Time
124D hex
DC Injection Braking
Carrier Frequency
124F hex Frequency Upper
Limit 1
A052
A053
A054
A055
A056
A057
A058
A059
A061
RW
RW
RW
RW
RW
RW
RW
RW
0 to 50
0 to 100
0 to 600
00: Edge operation
01: Level operation
0 to 100
0 to 600
20 to 150
76 hex
1251 hex
1253 hex
Frequency Lower
Limit 1
Jump Frequency 1
A062
A063
RW
RW
0
Frequency Lower Limit 1 to
Maximum Frequency 1
0
Starting Frequency to Frequency
Upper Limit 1
0 to 40000 (100000)
1255 hex
1256 hex
1258 hex
1259 hex
125B hex
125C hex
125E hex
Jump Frequency
Width 3
Acceleration Stop
Frequency
Acceleration Stop
Time
125F hex PID Selection
1260 hex
Jump Frequency
Width 1
Jump Frequency 2
Jump Frequency
Width 2
Jump Frequency 3
PID P Gain
A064
A065
A066
A067
A068
A069
A070
A071
A072
RW
RW
RW
RW
RW
RW
RW
RW
RW
0 to 1000 (10000)
0 to 40000 (100000)
0 to 1000 (10000)
0 to 40000 (100000)
0 to 1000 (10000)
0 to 40000
0 to 600
00: Disabled
01: Enabled
02: Reverse output enabled
2 to 2500
1261 hex
1262 hex
1263 hex
1264 hex
PID I Gain
PID D Gain
PID Scale
PID Feedback
Selection
A073
A074
A075
A076
RW
RW
RW
0 to 36000
0 to 10000
1 to 9999
8A hex
8B hex
1265 hex PID Deviation Reverse
Output
1266 hex PID Variable Range
Limit
A077
A078
R/W
RW
RW
00: Current (FI)
01: Voltage (FV)
02: Modbus communication
(Modbus-RTU)
03: Pulse train frequency
10: Operation function output
00: Disabled
01: Enabled
0 to 1000
Data resolution
1 [%]
PDO map
Possible
1 [%]
0.1 [%]
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.1 [s]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
0.1 [s]
1 [%]
0.1 [s]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.1 [kHz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.1 [s]
Possible
(TxPDO)
Possible
(TxPDO)
0.01
0.1 [s]
0.01 [s]
0.01
Possible
Possible
Possible
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
4012 hex
4012 hex
3012 hex
99 hex
9B hex
9D hex
4012 hex
4012 hex
3012 hex
9E hex
A0 hex
A2 hex
3012 hex
3012 hex
3012 hex
3012 hex
3012 hex
4012 hex
4012 hex
3012 hex
3012 hex
90 hex
91 hex
92 hex
93 hex
A3 hex
AC hex
CA hex
CB hex
D4 hex
A6 hex
A8 hex
AA hex
AB hex
Subindex
8C hex
8E hex
8F hex
Register
No.
Function name
1267 hex PID Feedforward
Selection
1269 hex
126A hex
AVR Selection 1
Motor Incoming
Voltage Selection 1
126B hex
126C hex
126D hex
AVR Filter Time
Parameter
AVR Deceleration
Voltage Gain
RUN Mode Selection
126E hex
Energy-saving
Response/Accuracy
Adjustment
1274 hex 1st Acceleration Time
2
1276 hex 1st Deceleration Time
2
1278 hex 2-step
Acceleration/Decelerat ion Selection 1
A083
A084
A085
A086
A092
A093
A094
1279 hex 2-step Acceleration
Frequency 1
127B hex
2-step Deceleration
Frequency 1
127D hex
Acceleration Pattern
Selection
Parameter
No.
A079
R/W
RW
A081
A082
RW
RW
RW
Monitor and setting items
00: Disabled
01: Voltage (FV)
02: Current (FI)
00: Always ON
01: Always OFF
02: OFF during deceleration
200-V class: 00 (200)
01 (215)
02 (220)
03 (230)
04 (240)
400-V class: 05 (380)
06 (400)
07 (415)
0 to 1000
A095
A096
A097
RW
RW
RW
RW
RW
RW
RW
RW
RW
50 to 200
00: Normal operation
01: Energy-saving operation
0 to 1000
1 to 360000
1 to 360000
00: Switched via word 2 terminal
01: Switched by setting
02: Switched only when switching forward/reverse
0 to 40000 (100000)
0 to 40000 (100000)
127E hex
1281 hex
1283 hex
1285 hex
1286 hex
1287 hex
12A5 hex
12A6 hex
12AF hex
Deceleration Pattern
Selection
FI Start Frequency
FI End Frequency
FI Start Ratio
FI End Ratio
FI Start Selection
Acceleration Curve
Parameter
Deceleration Curve
Parameter
Operation Frequency
Selection 1
A098
A101
A102
A103
A104
A105
A131
A132
A141
RW
RW
RW
RW
RW
RW
RW
RW
RW
00: Linear
01: S shape curve
02: U shape curve
03: Inverted U shape curve
04: EL-S shape curve
00: Linear
01: S shape curve
02: U shape curve
03: Inverted U shape curve
04: EL-S shape curve
0 to 40000 (100000)
0 to 40000 (100000)
0 to 100
0 to 100
00: Start frequency
01: 0 Hz
01 (small curve) to
10 (large curve)
01 (small curve) to
10 (large curve)
00: Digital Operator
01: Volume
02: Voltage (FV) input
03: Current (FI) input
04: Modbus communication
(Modbus-RTU)
05: Do not set.
07: Pulse train frequency
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [s]
1 [%]
0.1 [%]
0.01 [s]
0.01 [s]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
Possible
Possible
(TxPDO)
0.01 [Hz]
0.01 [Hz]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz]
0.01 [Hz]
1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-17
Appendices
A-18
4012 hex
3012 hex
3012 hex
3012 hex
Index
3012 hex
3012 hex
3012 hex
3012 hex
4012 hex
4012 hex
3012 hex
3012 hex
4012 hex
3012 hex
4012 hex
3012 hex
3012 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
4013 hex
3013 hex
D8 hex
DA hex
DE hex
29 hex
2A hex
2B hex
EB hex
ED hex
EF hex
F0 hex
E2 hex
E4 hex
E5 hex
E7 hex
F1 hex
28 hex
Subindex
D5 hex
Register
No.
12B0 hex
Function name
Operation Frequency
Selection 2
Parameter
No.
A142
R/W
RW
D6 hex
12B1 hex
Operation Function
Operator Selection
A143
A145
RW
RW
Monitor and setting items
00: Digital Operator
01: Volume
02: Voltage (FV) input
03: Current (FI) input
04: Modbus communication
(Modbus-RTU)
05: Do not set.
07: Pulse train frequency
00: Addition (A141 + A142)
01: Subtraction (A141
A142)
02: Multiplication (A141
A142)
0 to 40000 (100000)
DF hex
E0 hex
E1 hex
12B3 hex
12B5 hex
12B9 hex
12BA hex
Frequency Addition
Amount Setting
Frequency Addition
Sign Selection
EL-S Shape
Acceleration
Curve Ratio 1
EL-S Shape
Acceleration
Curve Ratio 2
12BB hex
12BC hex
12C6 hex
12C8 hex
12CA hex
12CB hex
12BD hex
12BF hex
12C0 hex
12C2 hex
EL-S Shape
Deceleration
Curve Ratio 1
EL-S Shape
Deceleration
Curve Ratio 2
Deceleration Stop
Frequency
Deceleration Stop
Time
PID Sleep Function
Operation Level
PID Sleep Operation
Delay Time
VR Start Frequency
VR End Frequency
VR Start Ratio
VR End Ratio
12CC hex
VR Start Selection
1301 hex Retry Selection
A146
A150
A151
A152
A153
A154
A155
A156
A157
A161
A162
A163
A164
A165 b001
1302 hex Allowable Momentary
Power Interruption Time b002
1303 hex Restart Standby Time b003
RW
RW
RW
RW
RW
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
00: Frequency reference + A145
01: Frequency reference
0 to 50
0 to 50
0 to 50
0 to 50
0 to 40000 (100000)
0 to 600
0 to 40000 (100000)
0 to 255
0 to 40000 (100000)
0 to 40000 (100000)
0 to VR End Ratio
VR Start Ratio to 100
00: Start Frequency A161
01: 0 Hz
00: Trip
01: 0 Hz restart
02: Frequency matching restart
03: Trip after frequency matching deceleration stop
04: Frequency pull-in restart
3 to 250
3 to 1000
A145
2C hex
2E hex
30 hex
1304 hex Momentary Power
Interruption/Undervolt age Trip During Stop
Selection
1305 hex Restart During
Momentary Power
Interruption Selection
1307 hex Frequency Matching
Lower Limit Frequency
Setting
1309 hex Overvoltage/Overcurrent
Restart Selection b004 b005 b007 b008
RW
RW
RW
00: Disabled
01: Enabled
02: Disabled during stop and deceleration stop
00: 16 times
01: No limit
0 to 40000 (100000)
00: Trip
01: 0 Hz restart
02: Frequency matching restart
03: Trip after frequency matching deceleration stop
04: Frequency pull-in restart
Data resolution
PDO map
Possible
(TxPDO)
0.1 [s]
0.1 [s]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
Possible
(TxPDO)
1 [%] Possible
(TxPDO)
1 [%] Possible
(TxPDO)
1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.1 [s] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.1 [s] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3A hex
3B hex
3C hex
3D hex
3E hex
3F hex
40 hex
37 hex
38 hex
39 hex
Subindex
32 hex
33 hex
34 hex
35 hex
Register
No.
130B hex
130C hex
130D hex
130E hex
Function name
Parameter
No.
b010 Overvoltage/Overcurrent
Restart Count Selection
Overvoltage/Overcurrent
Restart Standby Time b011
Electronic Thermal
Level 1
Electronic Thermal
Characteristics
Selection 1 b012 b013
1310 hex Free-electronic
Thermal Frequency 1
1311 hex Free-electronic
Thermal Current 1
1312 hex Free-electronic
Thermal Frequency 2 b015 b016 b017
R/W
RW
RW
RW
RW
RW
RW
RW
41 hex
42 hex
43 hex
44 hex
45 hex
46 hex
47 hex
49 hex
1313 hex Free-electronic
1317 hex
1318 hex
1319 hex
131A hex
131B hex
131C hex
131D hex
131E hex
Frequency Pull-in
Restart Parameter
131F hex Starting Frequency at
Frequency Pull-in
Restart Selection
1320 hex Soft Lock Selection
1322 hex
Thermal Current 2
1314 hex Free-electronic
Thermal Frequency 3
1315 hex Free-electronic
Thermal Current 3
1316 hex Overload Limit 1
Selection
Overload Limit 1 Level
Overload Limit 1
Parameter
Overload Limit 1
Selection 2
Overload Limit 1
Level 2
Overload Limit 1
Parameter 2
Overcurrent
Suppression Selection
Frequency Pull-in
Restart Level
Motor Cable Length
Code Selection b018 b019 b020 b021 b022 b023 b024 b025 b026 b027 b028 b029 b030 b031 b033
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
1 to 3
3 to 1000
200 to 1000
00: Reduced torque characteristics
01: Constant torque characteristics
02: Free setting
0 to Free-electronic Thermal
Frequency 2
0.00 to rated current
1 [Hz]
0.01 [%]
Free-electronic Thermal Frequency
1 to Free Setting, Electric Thermal
Frequency 3
0.00 to rated current
Free-electronic Thermal Frequency
2 to 400 (1000)
0.00 to rated current
Data resolution
1 [time]
0.1 [s]
0.1 [%]
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
1 [Hz]
0.01 [%]
1 [Hz]
0.01 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
00: Disabled
01: Enabled during acceleration/constant speed
02: Enabled during constant speed
03: Enabled during acceleration/constant speed
(accelerated during regeneration)
200 to 2000
0.01 [%]
1 to 30000 0.1 [s]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
00: Disabled
01: Enabled during acceleration/constant speed
02: Enabled during constant speed
03: Enabled during acceleration/constant speed
(accelerated during regeneration)
200 to 2000
0.01 [%]
1 to 30000
00: Disabled
01: Enabled
200 to 2000
1 to 30000
0.1 [s]
0.01 [%]
0.1 [s]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
00: Frequency at interruption
01: Max. frequency
02: Set frequency
00: Data other than b031 cannot be changed when terminal SFT is
ON.
01: Data other than b031 and the set frequency cannot be changed when terminal SFT is
ON.
02: Data other than b031 cannot be changed.
03: Data other than b031 and the set frequency cannot be changed.
10: Data can be changed during
RUN.
5 to 20
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-19
Appendices
A-20
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
Index
4013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
4013 hex
3013 hex
3013 hex
67 hex
68 hex
69 hex
6A hex
5D hex
5E hex
60 hex
66 hex
Subindex
4A hex
4C hex
Register
No.
Function name
1323 hex RUN Time/Power ON
Time Level
1325 hex Rotation Direction
Limit Selection
Parameter
No.
b034 b035
R/W
RW
RW
4D hex
4E hex
4F hex
50 hex
51 hex
52 hex
1326 hex
1327 hex
1328 hex
1329 hex
132A hex
Reduced Voltage
Startup Selection
Display Selection
Initial Screen Selection
User Parameter
Automatic Setting
Function b036 b037 b038 b039
Torque Limit Selection b040
RW
RW
RW
RW
RW
RW
Monitor and setting items
0 to 65535
00: No direction limit
01: Only Forward is enabled.
(Reverse is limited.)
02: Only Reverse is enabled.
(Forward is limited.)
0 (Reduced voltage startup time: small) to 255 (Reduced voltage startup time: large)
00: Complete display
01: Individual display of functions
02: User setting, this setting
03: Data comparison display
04: Basic display
05: Monitor display only
00: Screen on which the Entry was last pressed
001 to 060: (d001 to d060)
201: F001
00: Disabled
01: Enabled
Data resolution
10 [h]
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
00: Four-quadrant separate setting
01: Terminal switching
02: Analog voltage input
03: Do not set.
0 to 200/255 (no)
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
53 hex
54 hex
55 hex
56 hex
57 hex
5A hex
5B hex
5C hex
132B hex
132C hex
132D hex
Torque Limit 1 (fourquadrant mode forward power running)
Torque Limit 2 (fourquadrant mode reverse regeneration)
Torque Limit 3 (fourquadrant mode reverse power running)
132E hex
Torque Limit 4 (fourquadrant mode forward regeneration)
132F hex Torque LADSTOP
Selection
1330 hex Reverse Rotation
Prevention Selection
1333 hex Heavy Load/Light
Load Selection
1334 hex Controlled
Deceleration on Power
Loss b041 b042 b043 b044 b045 b046 b049 b050
RW
RW
RW
RW
RW
RW
RW
RW
0 to 200/255 (no)
0 to 200/255 (no)
0 to 200/255 (no)
00: Disabled
01: Enabled
00: Disabled
01: Enabled
00: Heavy load mode
01: Light load mode
00: Disabled
01: Deceleration stop
02: Constant voltage (without recovery)
03: Constant voltage (with recovery)
0 to 10000
1 [%]
1 [%]
1 [%]
0.1 [V]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
1335 hex DC Bus Voltage
Trigger Level of Ctrl.
Decel
1336 hex Deceleration Hold
Level of Ctrl. Decel
1337 hex Deceleration Time of
Ctrl. Decel
1339 hex Freq. Drop to start Ctrl.
Decel
133F hex Window Comparator
FV Upper Limit Level
1340 hex Window Comparator
FV Lower Limit Level
1341 hex Window Comparator
FV Hysteresis Width
1342 hex Window Comparator
FI Upper Limit Level
1343 hex Window Comparator
FI Lower Limit Level b051 b052 b053 b054 b060 b061 b062 b063 b064
RW
RW
RW
RW
RW
RW
RW
RW
0 to 10000
1 to 360000
0 to 1000
0. to 100.
(Lower limit: b061 + b062
0. to 100.
0. to 100.
(Upper limit: b063
2)
(Upper limit: b060 - b062
2)
0. to 10. (Upper limit:
(b060
b061) / 2)
0. to 100.
(Lower limit: b064 + b065
2)
b065 2
0.1 [V]
0.01 [s]
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
1 [%] Possible
1 [%]
1 [%]
1 [%]
1 [%]
Possible
Possible
Possible
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
7F hex
80 hex
81 hex
7C hex
7D hex
7E hex
75 hex
78 hex
79 hex
Subindex
6B hex
70 hex
71 hex
Register
No.
Function name
1344 hex Window Comparator
FI Hysteresis Width
1349 hex Analog Operation Level at FV Disconnection
Parameter
No.
b065 b070
134A hex
Analog Operation
Level at FI
Disconnection
Ambient Temperature b071
134E hex b075
1351 hex Integrated Power Clear b078
1352 hex
1355 hex
1356 hex
1357 hex
Integrated Power
Display Scale
Starting Frequency
Carrier Frequency
Initialization Selection b079 b082 b083 b084
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
1358 hex Initialization Data
Selection
1359 hex Frequency Conversion
Coefficient
135A hex
STOP Key Selection b085 b086 b087
RW
RW
RW
Monitor and setting items
0. to 10.
(Upper limit: (b063
b064) / 2)
0 to 100/255 (no)
0 to 100/255 (no)
10 to 50
Data resolution
1 [%]
1 [%]
1 [%]
00: Disabled
01: Clear (Return to 00 after clear)
1 to 1000 1
10 to 999 (10000)
20 to 150
00: Initialization disabled
01: Clear fault monitor
02: Initialize data
03: Clear fault monitor + initialize data
04: Do not set.
00: Do not change.
1 [
C]
0.01 [Hz]
0.1 [kHz]
PDO map
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
(TxPDO)
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
82 hex
83 hex
84 hex
85 hex
86 hex
87 hex
88 hex
89 hex
8A hex
8E hex
8F hex
90 hex
91 hex
135B hex
135C hex
135D hex
135E hex b088 b089 b090 b091
135F hex Cooling Fan Operation b092
1360 hex Cooling Fan Total
1361 hex Initialization Target
1362 hex
1363 hex Regenerative Braking
1367 hex
1368 hex
1369 hex
136A hex
Free-run Stop
Selection
Automatic Carrier
Reduction
Usage Rate of
Regenerative Braking
Stop Selection
Operating Time Clear
Selection
Regenerative Braking
Selection
ON Level
Free V/f Frequency 1
Free V/f Voltage 1
Free V/f Frequency 2
Free V/f Voltage 2 b093 b094 b095 b096 b100 b101 b102 b103
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
1 to 9999 0.01
00: Enabled
01: Disabled
02: Only reset is enabled
00: 0 Hz restart
01: Frequency matching restart
02: Frequency pull-in restart
00: Disabled
01: Enabled, depends on the current
02: Enabled, depends on the fin temperature
0 to 1000
0.1 [%]
00: Deceleration stop
01: Free-run stop
00: Always
01: Only during operation
(Including 5 minutes after the power is turned on and also after the inverter stops)
02: Depends on the fin temperature
00: Operating time count
01: Clear (Return to 00 after clear)
00: All data
01: Data other than terminal/communications
02: U*** registration function only
03: Other than U*** registration function
00: Disabled
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
330 to 380/660 to 760
1 [V]
0 to Free V/f Frequency 2
0 to 8000
0 to Free V/f Frequency 3
0 to 8000
1 [Hz]
0.1 [V]
1 [Hz]
0.1 [V]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-21
Appendices
A-22
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
Index
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
3013 hex
CB hex
CD hex
CE hex
BB hex
C0 hex
CA hex
A2 hex
A3 hex
A4 hex
A5 hex
98 hex
99 hex
9A hex
9B hex
A6 hex
A7 hex
A8 hex
A9 hex
AC hex
94 hex
95 hex
96 hex
97 hex
Subindex
92 hex
93 hex
Register
No.
136B hex
136C hex
Function name
Free V/f Frequency 3
Free V/f Voltage 3
136D hex
136E hex
Free V/f Frequency 4
Free V/f Voltage 4
136F hex Free V/f Frequency 5
1370 hex Free V/f Voltage 5
1371 hex Free V/f Frequency 6
1372 hex Free V/f Voltage 6
1373 hex Free V/f Frequency 7
1374 hex Free V/f Voltage 7
1382 hex Break ON Frequency
Parameter
No.
b104 b105 b106 b107 b108 b109 b110 b111 b112 b113
137B hex
137C hex
137D hex
137E hex
Brake Control
Function Selection
Brake Release Wait
Time
Acceleration Wait
Time
Stop Wait Time b120 b121 b122 b123
137F hex Brake Wait Time for
Confirmation
1380 hex Brake Release
Frequency b124 b125
1381 hex Brake Release Current b126 b127
AD hex
AE hex
AF hex
B0 hex
1385 hex Overvoltage
Suppression Function
Selection During
Deceleration
1386 hex Overvoltage
Suppression Level
During Deceleration
1387 hex Overvoltage
Suppression Parameter
1388 hex Overvoltage
Suppression
Proportional Gain
Setting b130 b131 b132 b133
1389 hex Overvoltage
Suppression Integral
Time Setting
1394 hex GS Input Operation
Selection b134 b145
1399 hex Main Panel Display
Selection
13A3 hex b150 d050 Monitor Target 1 b160 d050 Monitor Target 2 b161 13A4 hex
13A6 hex
13A7 hex d001/d007 Frequency
Setting Mode Selection
Initial Screen
Automatic Switching
Function b163 b164
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
0 to Free V/f Frequency 4
0 to 8000
0 to Free V/f Frequency 5
0 to 8000
0 to Free V/f Frequency 6
0 to 8000
0 to Free V/f Frequency 7
0 to 8000
0 to 400 (1000) (Hz)
0 to 8000
00: Disabled
01: Enabled
0 to 500
0 to 500
0 to 500
0 to 500
0 to 40000
0 to 20000
0 to 40000
00: Disabled
01: DC voltage kept constant
02: Acceleration enabled
200-V class: 330 to 390
400-V class: 660 to 780
10 to 3000
0 to 500
0 to 1500
00: No tripping
01: Tripping
0 to 60 hex (BCD) (d001 to d060)
0 to 30 hex (BCD) (d001 to d030)
0 to 30 hex (BCD) (d001 to d030)
00: Disabled
01: Enabled
00: Disabled
01: Enabled
1 [V]
0.1 [s]
Data resolution
1 [Hz]
0.1 [V]
1 [Hz]
0.1 [V]
1 [Hz]
0.1 [V]
1 [Hz]
0.1 [V]
1 [Hz]
0.1 [V]
0.01 [s]
0.01 [s]
0.01 [s]
0.01 [s] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [%] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [s]
0.01
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
Possible
(TxPDO)
Possible
Possible
Possible
Possible
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3013 hex
3013 hex
3013 hex
Subindex
CF hex
Register
No.
13A8 hex
Function name
Selection of Operating
Level on Digital
Operator
Disconnection
Parameter
No.
b165
R/W
RW
D5 hex
DE hex
13AE hex
13B7 hex
Inverter Mode
Selection
Perform Initialization/
Mode Selection
Execution b171 b180
RW
RW
Monitor and setting items
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
00: Selection disabled
01: Induction motor
02: High frequency induction motor
00: Function disabled
01: Initialization/Mode Selection
Execution
Data resolution
PDO map
Possible
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-23
Appendices
Index
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
Subindex
2A hex
Register
No.
Function name
1401 hex Multi-function Input 1
Selection
2B hex
2C hex
2D hex
2E hex
2F hex
30 hex
1402 hex
1403 hex
1404 hex
1405 hex
1406 hex
1407 hex
Multi-function Input 2
Selection
Multi-function Input 3
Selection
Multi-function Input 4
Selection
Multi-function Input 5
Selection
Multi-function Input 6
Selection
Multi-function Input 7
Selection
Parameter
No.
C001
R/W
RW
C002
C003
C004
C005
C006
C007
RW
RW
RW
RW
RW
RW
Monitor and setting items
00: FW (Forward)
01: RV (Reverse)
02: CF1 (Multi-step speed 1)
03: CF2 (Multi-step speed 2)
04: CF3 (Multi-step speed 3)
05: CF4 (Multi-step speed 4)
06: JG (Jogging)
07: DB (External DC injection braking)
08: SET (Motor 2 control)
09: 2CH (2-step acceleration/ deceleration)
11: FRS (Free-run stop)
12: EXT (External trip)
13: USP (USP function)
14: CS (Commercial switch)
15: SFT (Soft lock)
16: FV/FI (Analog input switch)
18: RS (Reset)
19: TH (PTC thermistor thermal protection)
20: STA (3-wire start)
21: STP (3-wire stop)
22: F/R (3-wire forward/reverse)
23: PID (PID disabled)
24: PIDC (PID integral reset)
27: UP (UP/DWN function accelerated)
28: DWN (UP/DWN function decelerated)
29: UDC (UP/DWN function data clear)
31: OPE (Forced operator)
32: SF1 (Multi-step speed bit 1)
33: SF2 (Multi-step speed bit 2)
34: SF3 (Multi-step speed bit 3)
35: SF4 (Multi-step speed bit 4)
36: SF5 (Multi-step speed bit 5)
37: SF6 (Multi-step speed bit 6)
38: SF7 (Multi-step speed bit 7)
39: OLR (Overload limit switching)
40: TL (Torque limit enabled/disabled)
41: TRQ1 (Torque limit switching 1)
42: TRQ2 (Torque limit switching 2)
44: BOK (Brake confirmation)
46: LAC (LAD cancel)
47: PCLR (Position deviation clear)
50: ADD (Frequency addition)
51: F-TM (Forced terminal block)
52: ATR (Torque reference input permission)
53: KHC (Integrated power clear)
56: Reserved.
57: Reserved.
58: Reserved.
59: Reserved.
60: Reserved.
61: Reserved.
62: Reserved.
65: AHD (Analog command held)
66: CP1 (Position command selection 1)
67: CP2 (Position command selection 2)
68: CP3 (Position command selection 3)
69: ORL (Zero return limit signal)
70: ORG (Zero return startup signal)
73: SPD (Speed/position switching)
77: GS1 (GS1 input (C003 only))
78: GS2 (GS2 input (C004 only))
81: 485 (Start co-inverter communication)
82: Reserved.
83: HLD (Retain output frequency)
84: ROK (Permission of RUN command)
85: EB (Rotation direction detection (C007 only))
86: DISP (Display fixed) no: NO (Not assigned)
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
A-24
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
36 hex
37 hex
38 hex
39 hex
3A hex
Subindex
34 hex
35 hex
3E hex
Register
No.
140B hex
140C hex
140D hex
140E hex
Function name
Multi-function Input Terminal 1
Operation Selection
Multi-function Input Terminal 2
Operation Selection
Multi-function Input Terminal 3
Operation Selection
Multi-function Input Terminal 4
Operation Selection
140F hex Multi-function Input Terminal 5
Operation Selection
1410 hex Multi-function Input Terminal 6
Operation Selection
1411 hex Multi-function Input
Terminal 7 Operation
Selection
1415 hex Multi-function Output
Terminal P1/EDM
Selection
Parameter
No.
C011
C012
C013
C014
C015
C016
C017
C021
R/W
RW
RW
RW
RW
RW
RW
RW
RW
3F hex
1416 hex Multi-function Output
Terminal P2 Selection
C022 RW
Monitor and setting items
00: NO (NO contact)
01: NC (NC contact)
00: RUN (During RUN)
01: FA1 (Constant speed reached)
02: FA2 (Set frequency min. reached)
03: OL (Overload warning)
04: OD (PID excessive deviation)
05: AL (Alarm output)
06: FA3 (Meet designated frequency during accel./decel.)
07: OTQ (Overtorque/Undertorque)
09: UV (Signal during undervoltage)
10: TRQ (During torque limit)
11: RNT (RUN time over)
12: ONT (Power on time over)
13: THM (Thermal warning)
19: BRK (Brake release)
20: BER (Brake error)
21: ZS (0Hz)
22: DSE (Excessive speed deviation)
23: POK (Position ready)
24: FA4 (Set frequency exceeded 2)
25: FA5 (Meet designated frequency
2 during accel./decel.)
26: OL2 (Overload warning 2)
27: FVdc (Analog FV disconnection detection)
28: FIdc (Analog FI disconnection detection)
31: FBV (PID FB status output)
32: NDc (Communication disconnection detection)
33: LOG1 (Logic operation output 1)
34: LOG2 (Logic operation output 2)
35: LOG3 (Logic operation output 3)
39: WAC (Capacitor life warning)
40: WAF (Cooling fan life warning signal)
41: FR (Starting contact signal)
42: OHF (Fin overheat warning)
43: LOC (Low current signal)
44: Reserved.
45: Reserved.
46: Reserved.
50: IRDY (Operation ready)
51: FWR (During forward operation)
52: RVR (During reverse operation)
53: MJA (Fatal fault signal)
54: WCFV (Window comparator FV)
55: WCFI (Window comparator FI)
58: FREF (Frequency command source)
59: REF (RUN command source)
60: SETM (Motor 2 selection)
62: EDM (Safety device monitor)
63: Reserved.
no: NO (Not assigned)
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-25
Appendices
A-26
Index
3014 hex
Subindex
43 hex
Register
No.
141A hex
Function name
Multi-function Relay
Output (MA, MB)
Function Selection
3014 hex
3014 hex
44 hex
45 hex
141B hex
141C hex
MP Selection
AM Selection
Parameter
No.
C026
R/W
RW
C027
C028
RW
RW
Monitor and setting items
00: RUN (During RUN)
01: FA1 (Constant speed reached)
02: FA2 (Set frequency min. reached)
03: OL (Overload warning)
04: OD (PID excessive deviation)
05: AL (Alarm output)
06: FA3 (Meet designated frequency during accel./decel.)
07: OTQ (Overtorque/Undertorque)
09: UV (Signal during undervoltage)
10: TRQ (During torque limit)
11: RNT (RUN time over)
12: ONT (Power on time over)
13: THM (Thermal warning)
19: BRK (Brake release)
20: BER (Brake error)
21: ZS (0Hz)
22: DSE (Excessive speed deviation)
23: POK (Position ready)
24: FA4 (Set frequency exceeded 2)
25: FA5 (Meet designated frequency
2 during accel./decel.)
26: OL2 (Overload warning 2)
27: FVdc (Analog FV disconnection detection)
28: FIdc (Analog FI disconnection detection)
31: FBV (PID FB status output)
32: NDc (Communication disconnection detection)
33: LOG1 (Logic operation output 1)
34: LOG2 (Logic operation output 2)
35: LOG3 (Logic operation output 3)
39: WAC (Capacitor life warning)
40: WAF (Cooling fan life warning signal)
41: FR (Starting contact signal)
42: OHF (Fin overheat warning)
43: LOC (Low current signal)
44: Reserved.
45: Reserved.
46: Reserved.
50: IRDY (Operation ready)
51: FWR (During forward operation)
52: RVR (During reverse operation)
53: MJA (Fatal fault signal)
54: WCFV (Window comparator FV)
55: WCFI (Window comparator FI)
58: FREF (Frequency command source)
59: REF (RUN command source)
60: SETM (Motor 2 selection)
62: EDM (Safety device monitor)
63: Reserved.
no: NO (Not assigned)
00: Output frequency
01: Output current
02: Output torque
03: Digital output frequency
04: Output voltage
05: Input power
06: Electronic thermal load rate
07: LAD frequency
08: Digital current monitor
10: Cooling fin temperature
12: Do not set.
15: Pulse train input monitor
16: Do not set.
00: Output frequency
01: Output current
02: Output torque
04: Output voltage
05: Input power
06: Electronic thermal load rate
07: LAD frequency
10: Cooling fin temperature
11: Output torque (signed)
13: Do not set.
16: Do not set.
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
3014 hex
3014 hex
3014 hex
3014 hex
57 hex
58 hex
5A hex
5C hex
52 hex
53 hex
55 hex
61 hex
62 hex
63 hex
64 hex
3014 hex
4014 hex
4014 hex
3014 hex
4014 hex
4014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
Index
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
Subindex
47 hex
48 hex
49 hex
4D hex
4F hex
Register
No.
Function name
141E hex
Digital Current Monitor
Reference Value
141F hex Multi-function Output
P1/EDM Contact
Selection
1420 hex Multi-function Output
P2 Contact Selection
1424 hex Multi-function Relay
Output (MA, MB)
Contact Selection
1426 hex Low Current Signal
Output Mode Selection
Parameter
No.
C030
C031
C032
C036
C038
R/W
RW
RW
RW
RW
RW
RW
Monitor and setting items
2000 to 20000
00: NO (NO contact)
01: NC (NC contact)
00: NO (NO contact)
01: NC (NC contact)
00: NO (NO contact)
01: NC (NC contact)
00: During acceleration/deceleration/ constant speed
01: Only during constant speed
0 to 20000 3014 hex
3014 hex
50 hex
51 hex
1427 hex Low Current Detection
Level
1428 hex Overload Warning
Signal Output Mode
Selection
C039
C040 RW
RW
00: During acceleration/deceleration/ constant speed
01: Only during constant speed
0 to 20000
3014 hex
3014 hex
3014 hex
3014 hex
65 hex
66 hex
67 hex
68 hex
1429 hex Overload Warning
Level 1
142A hex
142C hex
Arrival Frequency
During Acceleration
Arrival Frequency
During Deceleration
142E hex
PID Deviation
Excessive Level
142F hex Arrival Frequency
During Acceleration 2
1431 hex Arrival Frequency
During Deceleration 2
1433 hex Pulse Train Output
Coefficient
1438 hex Feedback Comparison
Signal Off Level
1439 hex Feedback Comparison
Signal On Level
143A hex
143B hex
Overtorque/Undertorq ue Selection
Overtorque Level
(Forward Power
Running)
143C hex
143D hex
Overtorque Level
(Reverse
Regeneration)
Overtorque Level
(Reverse Power
Running)
143E hex
Overtorque Level
(Forward
Regeneration)
143F hex Overtorque/Undertorq ue Signal Output
Mode Selection
C041
C042
C043
C044
C045
C046
C047
C052
C053
C054
C055
C056
C057
C058
C059
C061
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
0 to 40000 (100000)
0 to 40000 (100000)
0 to 1000
0 to 40000 (100000)
0 to 40000 (100000)
0001 to 9999
0 to 1000
0 to 1000
00: Overtorque
01: Undertorque
0 to 200
0 to 200
0 to 200
0 to 200
00: During acceleration/deceleration/ constant speed
01: Only during constant speed
0 to 100 6A hex
6C hex
6D hex
74 hex
1441 hex Electronic Thermal
Warning Level
1443 hex 0 Hz Detection Level
1444 hex Cooling Fin Overheat
144B hex
Warning Level
Communication Speed
Selection
C063
C064
C071
RW
RW
RW
0 to 10000
0 to 110
03 (2,400 bps)
04 (4,800 bps)
05 (9,600 bps)
06 (19.2 kbps)
07 (38.4 kbps)
08 (57.6 kbps)
09 (76.8 kbps)
10 (115.2 kbps)
1 [%]
0.01 [Hz]
1 [
C]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Data resolution
0.01 [%]
PDO map
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [%]
Possible
Possible
(TxPDO)
0.01 [%] Possible
0.01 [Hz]
0.01 [Hz]
0.1 [%]
0.01 [Hz]
0.01 [Hz]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
0.1 [%]
0.1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
1 [%]
1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-27
Appendices
A-28
AF hex
B0 hex
B1 hex
B2 hex
96 hex
97 hex
9A hex
9C hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
Index
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
82 hex
88 hex
8D hex
7A hex
7B hex
7E hex
7F hex
Subindex
75 hex
77 hex
Register
No.
144C hex
144E hex
Function name
Communication
Station No. Selection
Communication Parity
Selection
Parameter
No.
C072
C074
R/W
RW
RW
78 hex
79 hex
8F hex
90 hex
91 hex
92 hex
93 hex
94 hex
95 hex
144F hex Communication Stop
1451 hex
1452 hex
1456 hex
1459 hex
145F hex
1464 hex
146B hex
146C hex
Bit Selection
1450 hex Operation Selection on
Communication Error
Communication Error
Timeout Period
Communication Wait
Time
1455 hex FV Adjustment
FI Adjustment
Thermistor Adjustment
Debug Mode Selection
Communication
Selection
1466 hex Co-inverter
Communication
Starting Station
Number
1467 hex Co-inverter
Communication
Ending Station
Number
1468 hex Co-inverter
Communication
Starting Selection
1469 hex UP/DWN Storage
Selection
146A hex
Reset selection
Reset Restart Selection
UP/DWN Clear
Terminal Mode
C075
C076
C077
C078
C081
C082
C085
C091
C096
C098
C099
C100
C101
C102
C103
C104
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
1 to 247
00: Disabled
01: Even
02: Odd
1: 1 bit
2: 2 bits
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
0: Timeout disabled
1 to 9999
0 to 1000
0 to 2000
0 to 2000
0 to 2000
00: Do not store frequency data
01: Store frequency data
00: Trip reset at power-ON
01: Trip reset at power-OFF
02: Enabled only during trip (Reset when the power is ON.)
03: Trip reset only
00: 0 Hz restart
01: Frequency matching restart
02: Frequency pull-in restart
00: 0 Hz
01: EEPROM data at power ON
Data resolution
0.01 [s]
1 [ms]
0.1 [%]
0.1 [%]
0.1 [%]
For factory adjustment (Do not change.)
00: Modbus communication
(Modbus-RTU)
01: Communication between inverters
02: Communication between inverters (management)
1 to 8
1 to 8
00: 485 terminals start
01: Always started
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
Possible
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
(TxPDO)
Possible
(TxPDO)
146D hex
146E hex
MP Gain Setting
AM Gain Setting
1471 hex AM Bias Setting
C105
C106
C109
1473 hex Overload 1 Warning
Signal Level 2
1486 hex Output P1/EDM ON
Delay Time
1487 hex Output P1/EDM OFF
Delay Time
1488 hex Output P2 ON Delay
Time
1489 hex Output P2 OFF Delay
Time
C111
C130
C131
C132
C133
RW
RW
RW
RW
RW
RW
RW
RW
50 to 200
50 to 200
0 to 100
0 to 20000
0 to 1000
0 to 1000
0 to 1000
0 to 1000
1 [%]
1 [%]
1 [%]
0.01 [%]
0.1 [s]
0.1 [s]
0.1 [s]
0.1 [s]
Possible
Possible
Possible
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3014 hex
3015 hex
3015 hex
3015 hex
3015 hex
3015 hex
BE hex
BF hex
C0 hex
C1 hex
C2 hex
C3 hex
D0 hex
D1 hex
D2 hex
D3 hex
D6 hex
CD hex
CE hex
CF hex
BB hex
BC hex
BD hex
Subindex
B9 hex
BA hex
Register
No.
Function name
1490 hex Output RY ON Delay
Time
1491 hex Output RY OFF Delay
Time
1492 hex Logic Output Signal 1
Selection 1
1493 hex Logic Output Signal 1
Selection 2
1494 hex Logic Output Signal 1
Operator Selection
Parameter
No.
C140
C141
C142
C143
C144
R/W
RW
RW
RW
RW
RW
2C hex
2D hex
2E hex
2F hex
31 hex
1495 hex Logic Output Signal 2
Selection 1
1496 hex Logic Output Signal 2
Selection 2
1497 hex Logic Output Signal 2
Operator Selection
1498 hex Logic Output Signal 3
Selection 1
1499 hex Logic Output Signal 3
Selection 2
149A hex
14A4 hex
14A5 hex
14A6 hex
14A7 hex
14A8 hex
14A9 hex
14AA hex
1502 hex
1503 hex
1504 hex
1506 hex
Logic Output Signal 3
Operator Selection
Input Terminal 1
Response Time
Input Terminal 2
Response Time
Input Terminal 3
Response Time
Input Terminal 4
Response Time
Input Terminal 5
Response Time
Input Terminal 6
Response Time
Input Terminal 7
Response Time
14AD hex
Multi-step
Speed/Position
Determination Time
1501 hex Auto-tuning Selection
Motor Parameter 1
Motor Capacity 1
Motor Pole Number 1
Speed Response
C145
C146
C147
C148
C149
C150
C160
C161
C162
C163
C164
C165
C166
C169
H001
H002
H003
H004
H005
RW
RW
RW
RW
RW
RW
RW
RW
RW
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
0 to 1000
0 to 1000
Same as C021 and C022 (excluding
LOG1 to LOG3)
Same as C021 and C022 (excluding
LOG1 to LOG3)
00: AND
01: OR
02: XOR
Same as C021 and C022 (excluding
LOG1 to LOG3)
Same as C021 and C022 (excluding
LOG1 to LOG3)
00: AND
01: OR
02: XOR
Same as C021 to C022 (excluding
LOG1 to LOG3)
Same as C021 to C022 (excluding
LOG1 to LOG3)
00: AND
01: OR
02: XOR
0 to 200
1
Data resolution
0.1 [s]
0.1 [s]
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
1
1
1
1
1
1
1
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
00: Disabled
01: Enabled (motor does not rotate)
02: Enabled (motor rotates)
00: Standard motor parameter
02: Auto-tuning data
00: 0.1
01: 0.2
02: 0.4
03: 0.55
04: 0.75
05: 1.1
06: 1.5
07: 2.2
08: 3.0
09: 3.7
10: 4.0
11: 5.5
12: 7.5
13: 11.0
14: 15.0
15: 18.5
00: 2P
01: 4P
02: 6P
03: 8P
04: 10P
0 to 1000
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-29
Appendices
A-30
3016 hex
3016 hex
3016 hex
3016 hex
Index
3015 hex
3015 hex
3015 hex
3015 hex
4015 hex
3015 hex
3015 hex
3015 hex
3015 hex
3015 hex
4015 hex
3015 hex
3015 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
31 hex
38 hex
39 hex
3C hex
47 hex
48 hex
4C hex
50 hex
52 hex
54 hex
56 hex
57 hex
43 hex
45 hex
47 hex
48 hex
Subindex
32 hex
41 hex
68 hex
69 hex
30 hex
Register
No.
Function name
Parameter
No.
1507 hex Stabilization
Parameter 1
H006
1516 hex Motor 1 Parameter R1 H020
1518 hex Motor 1 Parameter R2 H021
151A hex
151C hex
151D hex
Motor 1 Parameter L
Motor 1 Parameter Io
Motor 1 Parameter J
1525 hex Motor 1 Parameter R1
(Auto-tuning Data)
1527 hex Motor 1 Parameter R2
(Auto-tuning Data)
1529 hex Motor 1 Parameter L
(Auto-tuning Data)
152B hex
152C hex
Motor 1 Parameter Io
(Auto-tuning Data)
Motor 1 Parameter J
(Auto-tuning Data)
H022
H023
H024
H030
H031
H032
H033
H034
153D hex
153E hex
V/f Control With Speed
Feedback Slip
Compensation
Proportional Gain
V/f Control With Speed
Feedback Slip
Compensation Integral
Gain
1603 hex Pulse Train Input
Terminal RP Selection
H050
H051
P003
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
0 to 255
1 to 65530
1 to 65530
1 to 65530
1 to 65530
1 to 9999000
1 to 65530
1 to 65530
1 to 65530
1 to 65530
1 to 9999000
0 to 1000
0 to 1000
4E hex
4F hex
51 hex
52 hex
53 hex
1604 hex
160B hex
160C hex
161A hex
161B hex
161F hex Acceleration/
Deceleration Time
1621 hex
1622 hex
1624 hex
1625 hex
1626 hex
Feedback Pulse Train
Input Type Selection
Number of Encoder
Pulses
Simple Position
Control Selection
160F hex Creep Speed Setting
Overspeed Error
Detection Level
Speed Deviation Error
Detection Level
Input Type
Torque Reference
Input Selection
Torque Reference
Setting
Torque Bias Mode
Torque Bias Value
Torque Bias Polarity
Selection
P004
P011
P012
P015
P026
P027
P031
P033
P034
P036
P037
P038
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
0.1 [%] Possible
00: Frequency setting (including
PID)
01: Feedback pulse
(Enabled only when motor 1 control is selected)
02: Do not set.
00: Single-phase pulse input
01: 2-phase pulse 1
02: 2-phase pulse 2
03: Single-phase pulse train + direction
32 to 1024
Possible
(TxPDO)
Possible
(TxPDO)
00: Simple position control disabled
02: Simple position control enabled
Starting frequency to 1000
0 to 1500
0 to 12000
00: Digital Operator
03: Do not set.
1
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.1 [%] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
Possible
(TxPDO)
00: Terminal FV
01: Terminal FI
03: Digital Operator
06: Do not set.
0 to 200
Possible
(TxPDO)
Possible
00: Disabled
01: Digital Operator
05: Do not set.
200 to +200
1 [%]
Possible
(TxPDO)
Possible
00: As per sign
01: Depends on the RUN direction
1 [%]
Possible
(TxPDO)
Data resolution
1
PDO map
Possible
0.001 [
]
Possible
(TxPDO)
0.001 [
]
Possible
(TxPDO)
0.01 [mH] Possible
(TxPDO)
0.01 [A] Possible
(TxPDO)
0.01
[kgm
2
]
Possible
(TxPDO)
0.001 [
]
Possible
(TxPDO)
0.001 [
]
Possible
(TxPDO)
0.01 [mH] Possible
(TxPDO)
0.01 [A]
0.01
[kgm
2
]
0.1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
4016 hex
4016 hex
4016 hex
4016 hex
4016 hex
4016 hex
4016 hex
4016 hex
3016 hex
3016 hex
3016 hex
3016 hex
4016 hex
4016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
6D hex
6F hex
71 hex
73 hex
75 hex
77 hex
79 hex
7E hex
7F hex
81 hex
7B hex
7C hex
7D hex
84 hex
86 hex
BB hex
Subindex
55 hex
67 hex
68 hex
69 hex
6B hex
57 hex
58 hex
66 hex
Register
No.
Function name
1628 hex Speed Limit Value in
Torque Control
(Forward)
162A hex
Speed Limit Value in
Torque Control (Reverse)
162B hex
Speed/Torque Control
Switching Time
1639 hex Pulse Train Frequency
Scale
163A hex
163B hex
Pulse Train Frequency
Filter Time Constant
Pulse Train Bias
Amount
163C hex
163E hex
Pulse Train Limit
Multi-step Position
Command 0
Parameter
No.
P039
P040
P041
P055
P056
P057
P058
P060
R/W
RW
RW
RW
RW
RW
RW
RW
RW
BC hex
BD hex
BE hex
1640 hex
1642 hex
1644 hex
1646 hex
1648 hex
164A hex
164C hex
164E hex
Multi-step Position
Command 1
Multi-step Position
Command 2
Multi-step Position
Command 3
Multi-step Position
Command 4
Multi-step Position
Command 5
Multi-step Position
Command 6
Multi-step Position
Command 7
Zero Return Mode
164F hex Zero Return Direction
Selection
1650 hex Zero Return Mode 1
Frequency
P061
P062
P063
P064
P065
P066
P067
P068
P069
P070
1651 hex Zero Return Mode 2
Frequency
1652 hex Position Range setting
(Forward side)
P071
P072
1654 hex Position Range setting
(Reverse side)
P073
1657 hex Positioning Mode Selection P075
1659 hex Encoder Disconnection
Detection Time
168E hex
Number of Send Data of
All Stations in Co-inverter
Communication
168F hex Recipient Station Number of All Stations in Co-inverter
Communication 1
1690 hex Recipient Register of All
Stations in Co-inverter
Communication 1
1691 hex Sender Register of All
Stations in Co-inverter
Communication 1
P077
P140
P141
P142
P143
RW
RW
RW
RW
RW
RW
RW
RW
RW
Monitor and setting items
0 to 12000
0 to 4000
0 to 268435455
268435455 to 0
00: Limit
01: Do not limit
0 to 100
1 to 5
1 to 247
0000 to FFFF hex
0000 to FFFF hex
Data resolution
0.01 [Hz]
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
0 to 12000
0 to 1000
10 to 320 *Input frequency at maximum frequency
1 to 200
-100 to +100
0 to 100
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
Position range setting (reverse) to position range v (forward) (Displays
MSB 4 digits including "
")
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
Position range setting (reverse) to position range setting (forward)
(Displays MSB 4 digits including "
")
00: Zero return mode 1
01: Zero return mode 2
00: Forward
01: Reverse
0 to 1000
1
1
1
1
1
1
1
1
0.01 [Hz]
0.01 [Hz]
1 [ms]
0.1 [kHz]
0.01 [s]
1 [%]
1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
0.01 [Hz] Possible
1
1
0.1 [s]
PDO map
Possible
(TxPDO)
Possible
Possible
Possible
(TxPDO)
Possible
Possible
Possible
Possible
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-31
Appendices
Index
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
3016 hex
301E hex
301E hex
301E hex
301E hex
301E hex
301F hex
Subindex
BF hex
C0 hex
C1 hex
C2 hex
C3 hex
C4 hex
C5 hex
C6 hex
C7 hex
C8 hex
C9 hex
CA hex
3E hex
3F hex
40 hex
41 hex
42 hex
40 hex
Register
No.
Function name
1692 hex Recipient Station Number of All Stations in Co-inverter
Communication 2
1693 hex Recipient Register of All
Stations in Co-inverter
Communication 2
1694 hex Sender Register of All
Stations in Co-inverter
Communication 2
1695 hex Recipient Station Number of All Stations in Co-inverter
Communication 3
1696 hex Recipient Register of All
Stations in Co-inverter
Communication 3
1697 hex Sender Register of All
Stations in Co-inverter
Communication 3
1698 hex Recipient Station Number of All Stations in Co-inverter
Communication 4
1699 hex Recipient Register of All
Stations in Co-inverter
Communication 4
169A hex
Sender Register of All
Stations in Co-inverter
Communication 4
169B hex
Recipient Station Number of All Stations in Co-inverter
Communication 5
169C hex
169D hex
1E01 hex
Recipient Register of All
Stations in Co-inverter
Communication 5
Sender Register of All
Stations in Co-inverter
Communication 5
Coil Data 1
*
Parameter
No.
P144
P145
P146
P147
P148
P149
P150
P151
P152
P153
P154
P155
1E02 hex
Coil Data 2
*
1E03 hex
Coil Data 3
*
1E04 hex
Coil Data 4
*
1E05 hex
1F01 hex
Coil Data 5
Coil Data 0
*
*
R/W
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RO
RO
RO
RO
RO
RW
Monitor and setting items
1 to 247
0000 to FFFF hex
0000 to FFFF hex
1 to 247
0000 to FFFF hex
0000 to FFFF hex
1 to 247
0000 to FFFF hex
0000 to FFFF hex
1 to 247
0000 to FFFF hex
0000 to FFFF hex
2
0
: Coil No. 0010 hex to
2
15
: Coil No. 001F hex
2
0
: Coil No. 0020 hex to
2
15
: Coil No. 002F hex
2
0
: Coil No. 0030 hex to
2
15
: Coil No. 003F hex
2
0
: Coil No. 0040 hex to
2
15
: Coil No. 004F hex
2
0
: Coil No. 0050 hex to
2
8
: Coil No. 0058 hex
2
1
: Coil No. 0001 hex to
2
15
: Coil No. 000F hex
Data resolution
PDO map
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
* Each of the above holding registers (Coil Data 0 to 5) consists of 16 sets of coil data. Since coils are not supported in communication between inverters (only holding registers are supported), use the above holding registers if you want to access the coil.
A-32
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Holding register number list (2nd setting F group)
Index
4021 hex
4021 hex
Subindex
46 hex
48 hex
Register
No.
Function name
2103 hex Acceleration Time 2
Setting
2105 hex Deceleration Time 2
Setting
Parameter
No.
F202
R/W
RW
Monitor and setting items
1 to 360000
F203 RW 1 to 360000
Data resolution
0.01 [s]
PDO map
Possible
0.01 [s] Possible
Holding register number list (2nd setting, Group A, b, C, H, and P)
Index
3022 hex
3022 hex
Subindex
46 hex
47 hex
Register
No.
2201 hex
2202 hex
Function name
Frequency Reference
Selection 2
RUN Command
Selection 2*
Parameter
No.
A201
A202
Torque Boost
Selection 2
Manual Torque Boost
Voltage 2
Manual Torque Boost
Frequency 2
A241
A242
A243
R/W
RW
RW
Monitor and setting items
00: Volume
01: Control circuit terminal block
02: Digital Operator
03: Modbus communication
(Modbus-RTU)
04: Optional boad
06: Pulse train frequency
07: Do not set.
10: Operation function output
01: Control circuit terminal block
02: Digital operator
03: Modbus communication
(Modbus-RTU)
04: Optional boad
300 to Maximum Frequency 2 3022 hex
3022 hex
3022 hex
3022 hex
3022 hex
48 hex
49 hex
80 hex
81 hex
82 hex
2203 hex
2204 hex
223B hex
223C hex
223D hex
Base Frequency 2
Maximum Frequency 2
A203
A204
RW
RW
RW
RW
RW
300 to 4000 (10000)
00: Manual torque boost
01: Automatic torque boost
0 to 200
0 to 500
* If the RUN Command 2 Selection has been changed, wait for at least 40 ms before an actual RUN command is issued.
Data resolution
PDO map
Possible
(TxPDO)
0.1 [Hz]
0.1 [Hz]
0.1 [%]
0.1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible
Possible
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-33
Appendices
Index
3022 hex
3022 hex
3022 hex
3022 hex
4022 hex
4022 hex
3022 hex
3022 hex
4022 hex
4022 hex
3022 hex
4022 hex
4022 hex
3023 hex
3023 hex
3023 hex
3023 hex
3023 hex
3024 hex
3025 hex
B9 hex
BB hex
53 hex
54 hex
5D hex
5E hex
5F hex
72 hex
4D hex
B4 hex
B6 hex
B8 hex
Subindex
83 hex
Register
No.
223E hex
223F hex
Function name
Control Method 2
Output Voltage Gain 2
Parameter
No.
A244
R/W
RW
A245 RW
Monitor and setting items
00: Constant torque characteristics
01: Reduced torque characteristics
02: Free V/f setting
03: Sensorless vector control
20 to 100
Data resolution
1 [%]
PDO map
Possible
(TxPDO)
Possible 84 hex
85 hex
RW 0 to 255 1 [%] Possible
86 hex
94 hex
2240 hex Automatic Torque
Boost Voltage
Compensation Gain 2
2241 hex Automatic Torque
Boost Slip
Compensation Gain 2
224F hex Frequency Upper
Limit 2
A246
A247
A261
RW
RW
0 to 255 1 [%]
0.01 [Hz]
Possible
Possible
(TxPDO)
96 hex
AE hex
AF hex
2251 hex
2269 hex
226A hex
Frequency Lower
Limit 2
AVR Selection 2
Motor Incoming
Voltage Selection 2
A262
A281
A282
RW
RW
RW
RW
0
Frequency Lower Limit 2 to
Maximum Frequency 2
0
Starting Frequency to Frequency
Upper Limit 2
00: Always ON
01: Always OFF
02: OFF during deceleration
200-V class: 00 (200)
01 (215)
02 (220)
03 (230)
04 (240)
400-V class: 05 (380)
06 (400)
07 (415)
1 to 360000
0.01 [Hz]
0.01 [s]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
(TxPDO)
Possible 226F hex 2nd Acceleration Time
2
A292
2271 hex 2nd Deceleration Time
2
2273 hex 2-step
Acceleration/Decelerat ion Selection 2
A293
A294
RW
RW
1 to 360000 0.01 [s] Possible
2274 hex 2-step Acceleration
Frequency 2
2276 hex 2-step Deceleration
Frequency 2
230C hex
230D hex
2317 hex
2318 hex
2429 hex
Electronic Thermal
Level 2
Electronic Thermal
Characteristics
Selection 2
2316 hex Overload Limit 2
Selection
Overload Limit Level 2
Overload Limit 2
Parameter
Overload Warning
Level 2
2502 hex Motor Parameter 2
A295
A296 b212 b213 b221 b222 b223
C241
H202
RW
RW
RW
RW
RW
RW
RW
RW
RW
00: Switched by 2 word terminal
01: Switched by setting
02: Switched only when switching forward/reverse
0 to 40000 (100000)
Possible
(TxPDO)
0 to 40000 (100000)
2000 to 10000
00: Reduced torque characteristics
01: Constant torque characteristics
02: Free setting
00: Disabled
01: Enabled during acceleration/constant speed
02: Enabled during constant speed
03: Enabled during acceleration/constant speed
(accelerated during regeneration)
100 to 2000
0.01 [Hz] Possible
(TxPDO)
0.01 [Hz] Possible
(TxPDO)
0.01 [%]
Possible
(TxPDO)
Possible
(TxPDO)
0.1 [%]
Possible
(TxPDO)
1 to 30000
0 to 2000
0.1 [s]
0.1 [%]
Possible
(TxPDO)
Possible
(TxPDO)
Possible
00: Standard motor parameter
02: Auto-tuning data
Possible
(TxPDO)
A-34
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Index
3025 hex
3025 hex
3025 hex
3025 hex
3025 hex
4025 hex
3025 hex
3025 hex
3025 hex
3025 hex
3025 hex
3025 hex
3025 hex
4025 hex
63 hex
65 hex
67 hex
68 hex
51 hex
52 hex
61 hex
70 hex
72 hex
74 hex
76 hex
77 hex
Subindex
4E hex
4F hex
Register
No.
2503 hex
Function name
Motor Capacity 2
2504 hex Motor Pole Number 2
2506 hex Speed Response 2
Parameter
No.
H203
R/W
RW
H204
H205
RW
RW
Monitor and setting items
00: 0.1
01: 0.2
02: 0.4
03: 0.55
04: 0.75
05: 1.1
06: 1.5
07: 2.2
08: 3.0
09: 3.7
10: 4.0
11: 5.5
00: 2P
01: 4P
02: 6P
03: 8P
04: 10P
1 to 1000
2507 hex Stabilization
2516 hex Motor 2 Parameter R1 H220
2518 hex
251A hex
251C hex
251D hex
Parameter 2
Motor 2 Parameter R2
Motor 2 Parameter L
Motor 2 Parameter Io
Motor 2 Parameter J
H206
H221
H222
H223
H224
2525 hex Motor 2 Parameter R1
(Auto-tuning Data)
H230
2527 hex Motor 2 Parameter R2
(Auto-tuning Data)
H231
H232 2529 hex Motor 2 Parameter L
(Auto-tuning Data)
252B hex
Motor 2 Parameter Io
(Auto-tuning Data)
252C hex
Motor 2 Parameter J
(Auto-tuning Data)
H233
H234
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
0 to 255
1 to 65530
1 to 65530
1 to 65530
1 to 65530
1 to 9999000
1 to 65530
1 to 65530
1 to 65530
1 to 65530
1 to 9999000
-
Data resolution
PDO map
Possible
(TxPDO)
Possible
(TxPDO)
1 [%] Possible
1 Possible
0.001 [
]
Possible
(TxPDO)
0.001 [
]
Possible
(TxPDO)
0.01 [mH] Possible
(TxPDO)
0.01 [A]
0.01
Possible
(TxPDO)
Possible
(TxPDO)
0.001 [
]
0.001 [
]
Possible
(TxPDO)
Possible
(TxPDO)
0.01 [mH] Possible
(TxPDO)
0.01 [A] Possible
(TxPDO)
0.01
Possible
(TxPDO)
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-35
Appendices
A-5 Sysmac Error Status Codes
A list and descriptions of the error event codes that display in Sysmac Studio are provided.
A-5-1 Error Table
The errors that may occur for this Unit are listed below. Event levels are given in the table as follows:
Abbreviation
Maj
Prt
Min
Obs
Info
Name
Major fault level
Partial fault level
Minor fault level
Observation
Information
Event code Event name Meaning Assumed cause
04A10000 hex Non-volatile
Memory
Hardware
Error
04BA0000 hex
04BB0000 hex
04BC0000 hex
Connection
Error between
Inverter and
Communications Unit
Inverter
Warning
Inverter Trip
34F00000 hex PDO Setting
Error
An error occurred in non-volatile memory.
• Non-volatile memory failure
An error occurred in the connection between the
Inverter and the
EtherCAT Communications Unit for the Inverter.
An Inverter warning was detected.
An Inverter trip was detected.
There is an illegal setting value in the
PDO mapping.
• Contact failure between the
Inverter and the EtherCAT
Communications Unit for the
Inverter.
• Inverter trip was reset.
• The Inverter was initialized or the mode was changed.
• The EtherCAT Communications
Unit for the Inverter failed.
• An Inverter warning was detected.
• An Inverter trip was detected.
• The PDO mapping or Sync-
Manager settings are incorrect.
Level
Maj Prt Min Obs Info
Reference
A-36
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
A-5-2 Error Descriptions
Controller Error Descriptions
The items that are used to describe individual errors (events) are described in the following copy of an error table.
Event name
Meaning
Source
Gives the name of the error.
Gives a short description of the error.
Gives the source of the error.
Event code
Gives the code of the error.
Error attributes
Effects
Indicators
System-defined variables
Cause and correction
Level
Tells the level of influence on control.
*1
Source details
Recovery
Gives details on the source of the error.
Gives the recovery method.
*2
Detection timing
Log category
Tells when the error is detected.
Tells which log the error is saved in.
*3
User program
Tells what will happen to execution of the user program.*4
Operation
Provides special information on the operation that results from the error.
Gives the status of the built-in EtherNet/IP port and built-in EtherCAT port indicators. Indicator status is given only for errors in the EtherCAT Master Function Module and the EtherNet/IP Function Module.
Variable Data type Name
Lists the variable names, data types, and meanings for system-defined variables that provide direct error notification, that are directly affected by the error, or that contain settings that cause the error.
Assumed cause Correction
Lists the possible causes, corrections, and preventive measures for the error.
Prevention
Attached information
Precautions/
Remarks
This is the attached information that is displayed by the Sysmac Studio or an NS-series PT.
Provides precautions, restrictions, and supplemental information.
*1 One of the following:
Major fault: Major fault level
Partial fault: Partial fault level
Minor fault: Minor fault level
Observation
Information
*2 One of the following:
Automatic recovery: Normal status is restored automatically when the cause of the error is removed.
Error reset: Normal status is restored when the error is reset after the cause of the error is removed.
Cycle the power supply: Normal status is restored when the power supply to the Controller is turned OFF and then back
ON after the cause of the error is removed.
Controller reset: Normal status is restored when the Controller is reset after the cause of the error is removed.
Depends on cause: The recovery method depends on the cause of the error.
*3 One of the following:
System: System event log
Access: Access event log
*4 One of the following:
Continues: Execution of the user program will continue.
Stops: Execution of the user program stops.
Starts: Execution of the user program starts.
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-37
Appendices
Error Descriptions
Event name
Meaning
Source
Error attributes
Effects
Indicators
Non-volatile Memory Hardware Error
An error occurred in non-volatile memory.
EtherCAT Master Function Module
Source details
Level
User program
Minor fault
Continues.
EtherCAT NET RUN
Event code
04A10000 hex
Slave
Detection timing
Recovery
Error reset (after cycling slave power)
Log category
Operation
Non-volatile memory cannot be written.
EtherCAT NET ERR EtherCAT LINK/ACT
When establishing communications after turning
ON power to the slave
System
System-defined variables
Cause and correction
---
Variable
None
Assumed cause
Non-volatile memory failure
---
Data type
---
Correction
Replace the EtherCAT Communications Unit or the EtherCAT slave.
---
Name
---
Prevention
None
Attached information
Precautions/
Remarks
None
This error is not recorded in the error log of the slave.
Event name
Meaning
Source
Connection Error between Inverter and Communications
Unit
Event code
04BA0000 hex
An error occurred in the connection between the Inverter and the EtherCAT Communications Unit for the Inverter.
EtherCAT Master Function Module
Source details
Slave
Detection timing
Continuously
Error attributes Level
Minor fault
Recovery
Error reset (after cycling slave power)
Log category
System
Effects
Indicators
System-defined variables
User program
EtherCAT NET RUN
---
Variable
Continues.
Operation
---
Data type
Inverter communications will not operate.
EtherCAT NET ERR EtherCAT LINK/ACT
---
Name
Cause and correction
None
Assumed cause
Contact failure between the Inverter and the EtherCAT Communications
Unit for the Inverter.
---
Correction
Securely install the EtherCAT Communications Unit for the Inverter.
---
Prevention
Securely install the EtherCAT Communications Unit for the Inverter.
Inverter trip was reset.
The Inverter was initialized or the mode was changed.
The EtherCAT Communications Unit for the Inverter failed.
None
Turn ON the Inverter’s power supply again.
Replace the EtherCAT Communications Unit for the Inverter.
None
None
Attached information
Precautions/
Remarks
None
A-38
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Appendices
Event name
Meaning
Source
Inverter Warning
An Inverter warning was detected.
EtherCAT Master Function Module
Error attributes Level
Minor fault
Effects
Indicators
System-defined variables
Cause and correction
User program
Continues.
EtherCAT NET RUN
---
Variable
None
Assumed cause
An Inverter warning was detected.
Event code
04BB0000 hex
Source details
Slave
Recovery
Error reset (after resetting slave errors)
Operation
Not affected.
EtherCAT NET ERR
---
Data type
---
Correction
Read the value in slave object 3000 hex sub-index 4F hex and check the warning details. Remove the cause of the warning accordingly. Then execute an error reset with slave object
5000 hex or a fault reset with 6040 hex.
Detection timing
Log category
Continuously
System
EtherCAT LINK/ACT
---
Name
---
Prevention
Depends on the nature of the error.
Attached information
Precautions/
Remarks
None
None
Event name
Meaning
Source
Inverter Trip
An Inverter trip was detected.
EtherCAT Master Function Module
Error attributes Level
Minor fault
Effects
Indicators
System-defined variables
Cause and correction
User program
Continues.
EtherCAT NET RUN
---
Variable
None
Assumed cause
An Inverter trip was detected.
Event code
04BC0000 hex
Source details
Slave
Recovery
Error reset (after resetting slave errors)
Operation
Motor stops.
EtherCAT NET ERR
---
Data type
---
Correction
Read slave object 3000 hex sub-index
13 hex (cause) and 3000 hex subindex 14 hex (inverter status) values and check the details. Remove the cause of the trip accordingly. Then execute an error reset with slave object 5000 hex or a fault reset with
6040 hex.
Detection timing
Log category
Continuously
System
EtherCAT LINK/ACT
---
Name
---
Prevention
Depends on the nature of the error.
Attached information
Precautions/
Remarks
None
None
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-39
Appendices
Event name
Meaning
Source
Error attributes
Effects
Indicators
PDO Setting Error
There is an illegal setting value in the PDO mapping.
EtherCAT Master Function Module
Source details
Level
User program
Minor fault
Continues.
EtherCAT NET RUN
Event code
34F00000 hex
Slave
Detection timing
At transfer of
EtherCAT Configuration Setup
System
Recovery
Error reset (after resetting slave errors)
Log category
Operation
The slave can enter the Pre-operational state.
EtherCAT NET ERR EtherCAT LINK/ACT
System-defined variables
Cause and correction
---
Variable
None
Assumed cause
The PDO mapping or SyncManager settings are incorrect.
---
Data type
---
Correction
Read and check the ALStatus code and the value in 5200 hex. Correct the settings.
---
Name
---
Prevention
Check that there are no mistakes in settings for the PDO mapping and
SyncManager.
Attached information
Precautions/
Remarks
None
None
A-40
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Index
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Index-1
I
Index
Index
A
.................................................................. 3-6
C
.................................................................. 2-6
....................................................................... 3-2
............................................................ 5-21
.............................................................. 4-12
........................................... 5-8
.................................................. 1-7
.......................................... 2-5
.......................................................... 1-7
D
...................................................... 5-22
E
............................................3-7, 3-8
.............................................................. 6-6
........................................................................... 1-7
............................................................... 1-4
........................................................... 1-7
.............................................................. 1-7
........................................................ 1-4
F
...................................................... 3-5
I
...................................................... 4-10
........................................ 5-19
......................................... 5-17
M
..................................... 5-16
N
................................................................ 2-4
O
........................................................... 5-6
.....................................................................A-5
P
................................................................A-9
............................................................................... 3-4
.................................................4-14, 4-17
................................................................ 3-4
................................................. 5-11
...................................................... 4-4
..................................................... 3-4
R
.......................................................................... 4-2
S
............................................................................... 3-6
...................................................... 3-6
................................................................A-2
.....................................................2-3, 6-2
............................................................... 4-3
.................................................. 3-5
Sync Manager Communication Objects
T
........................................................................... 4-2
V
.......................................................4-12, 5-5
W
........................................................... 2-7
Index-2
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
OMRON Corporation
Industrial Automation Company
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Authorized Distributor:
© OMRON Corporation 2010 All Rights Reserved.
In the interest of product improvement, specifications are subject to change without notice.
Cat. No. I574-E1-02
1107