YASKAWA Varispeed SI-P1 PROFIBUS-DP Communications Interface Card USER'S MANUAL
Below you will find brief information for PROFIBUS-DP Communications Interface Card Varispeed SI-P1. The Varispeed SI-P1 card is an interface card that allows you to connect your Varispeed series inverter to a PROFIBUS-DP network. This enables you to monitor the inverter's operational status, such as running or stopping, and to read or change settings of the inverter constants.
Advertisement
Advertisement
YASKAWA
Varispeed SERIES OPTION CARD
PROFIBUS-DP COMMUNICATIONS INTERFACE CARD
USER'S MANUAL
Model: SI-P1
YASKAWA
MANUAL NO. SIBZ-C736-70.9B
INTRODUCTION
This User's Manual describes the operations and specifications of the PROFIBUS Communications
Interface Card (hereafter called the SI-P1 card). The SI-P1 card transfers the data between the Varispeed series Inverters and the PROFIBUS-DP open-field network (hereafter called the PROFIBUS-DP). Read this manual carefully and be sure you understand the information provided before attempting any operations.
For the operation of the Inverter, refer to the instructions of the Varispeed Series Inverters.
General Precautions
・ Some drawings in this manual are shown with the protective cover or shields removed, in order to describe the detail with more clarity. Make sure all covers and shields are replaced before operating this product, and operate it in accordance with the instructions in this manual.
・ This manual may be modified when necessary because of improvement of the product, modification, or changes in specifications.
・ A new version of the manual will be released under a reviced manual number when any changes are made.
・ Contact your Yaskawa representative or a Yaskawa office listed on the back of this manual to order a new manual if this manual is damaged or lost. Please provide the document number listed on the front cover of this manual when ordering.
・ Yaskawa cannot guarantee the quality of any products which have been modified. Yaskawa assumes no responsibility for any injury or damage caused by a modified product.
1
Safety Information
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the
PROFIBUS Communications Interface Card SI-P1. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” and “CAUTION.”
WARNING
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury to personnel and damage to equipment.
follow these important notes.
Receiving
CAUTION
・ Do not use any option card which is damaged or has missing parts.
Failure to observe this caution may result in injury.
Installation and Wiring
WARNING
・ Never touch the inside of the Inverter.
Failure to observe this warning may result in electric shock.
・ Disconnect all power before mounting or removing the option card or wiring. Then wait at least the specified time (specified on the front cover) after the power supply is disconnected and all LEDs and CHARGE LED are extinguished.
Failure to observe this warning may result in electric shock.
・ Do not damage or apply excessive stress to the cables. Do not place heavy objects on the cables or place the cables between other objects.
Failure to observe this warning may result in electric shock, malfunction or damage of the equipment.
CAUTION
・ Do not touch the elements of the option card with bare hands.
Failure to observe this caution may result in equipment damage caused by static electricity.
・ Insert the connectors firmly.
Failure to observe this caution may result in malfunction or damage of the equipment.
2
Setting
CAUTION
・ Be careful when changing Inverter settings. The Inverter is factory set to suitable settings.
Failure to observe this caution may result in damage of the equipment.
3
CONTENTS
1. OUTLINE............................................................................................................... 5
2. RECEIVING .......................................................................................................... 6
3. NOMENCLATURE AND SETTING........................................................................ 7
3.1 Components ............................................................................................................................................... 7
3.2 Terminal Block ............................................................................................................................................ 7
3.3 LEDs........................................................................................................................................................... 8
3.4 Address Switch........................................................................................................................................... 9
3.5 Termination Resistor Selector Switches...................................................................................................... 9
3.6 Transmission Speed Settings ..................................................................................................................... 9
4. INSTALLATION AND WIRING............................................................................. 10
4.1 Installing the SI-P1 Card........................................................................................................................... 10
4.2 Wiring of the Communications Cable.........................................................................................................11
5. FUNCTIONS ....................................................................................................... 14
5.1 Initial Settings ........................................................................................................................................... 14
5.1.1 Inverter Settings ............................................................................................................................... 14
5.1.2 How to Get GSD Files...................................................................................................................... 14
5.2 PROFIBUS-DP Data and I/O Map ............................................................................................................ 15
5.3 High-speed I/O Data ................................................................................................................................. 18
5.4 MEMOBUS Message Area ....................................................................................................................... 19
5.4.1 Configuration of MEMOBUS Command Message ........................................................................... 19
5.4.2 Configuration of MEMOBUS Response Messages .......................................................................... 19
5.4.3 Constant Settings Using MEMOBUS Commands ............................................................................ 19
5.4.4 Handshaking Register...................................................................................................................... 19
5.4.5 Example of Handshaking ................................................................................................................. 19
5.4.6 Flow Chart........................................................................................................................................ 19
6. TROUBLESHOOTING ........................................................................................ 19
6.1 Inverter Errors........................................................................................................................................... 19
6.2 Faults of PROFIBUS-DP Communications LED ....................................................................................... 19
7. SPECIFICATIONS............................................................................................... 19
8. APPENDIX .......................................................................................................... 19
8.1 List of MEMOBUS Registers .................................................................................................................... 19
8.1.1 Command Data (Read and Write).................................................................................................... 19
8.1.2 Status Data (Read Only) .................................................................................................................. 19
8.1.3 Monitor Data (Read Only) ................................................................................................................ 19
8.1.4 Enter Command (Write Only) ........................................................................................................... 19
8.1.5 Inverter Constants (Read and Write)................................................................................................ 19
8.1.6 Error Code ....................................................................................................................................... 19
4
1. OUTLINE
The SI-P1 card is an interface card to achieve data communications with the PROFIBUS-DP master for connecting the Varispeed series Inverters to the PROFIBUS-DP open field network.
Mounting the SI-P1 card on the Varispeed series Inverter can monitor operation status including running or stopping; or change or read the settings of the Inverter constants from the PROFIBUS-DP master, which can be utilised for various types of applications.
The following are the Inverter series on which the SI-P1 card can be mounted.
5
2. RECEIVING
Check the following items as soon as the product is delivered.
Item
Has the correct model of the
SI-P1 card been delivered?
Is the SI-P1 card damaged in any way?
Method
Compare the model number on your order to the number printed in the lower right corner of the SI-P1 card.
(Refer to 3.1.)
Inspect the entire exterior of the SI-P1 card to see if there are any scratches or any other damage resulting from shipping.
A GSD file is needed for using the SI-P1 card as a PROFIBUS-DP slave. Use the GSD file to register the
SI-P1 card as a slave to a PROFIBUS-DP master. Contact your Yaskawa representative for more information how to get a GSD file.
If you find any irregularities, contact the agency from which you purchased the Inverter or your Yaskawa representative immediately.
6
3. NOMENCLATURE AND SETTING
3.1 Components
The names of components on the SI-P1 card are shown in Fig. 1.
Connector with Inverter
Control Board (JP1)
Status Display LED
PROFIBUS-DP Bus
Connection Terminal
(JP3)
Termination Resistor
Selector Switch
Address Switch 2 (×10)
Address Switch 1 (×1)
Ground Lead Wire
Spacer
Mounting
Hole
SI-P1
73600-C0331
Model and Code No.
Fig. 1 PROFIBUS-DP Communication Interface Card SI-P1
3.2 Terminal Block
This terminal block connects the SI-P1 card to the PROFIBUS-DP communications line.
Terminal
No.
1
2
3
Name
+5V BUS
GND BUS
A-Line
Meaning
Not available
Not available
Minus RxD/TxD according to RS-485 specifications
4
5
6
B-Line
Shield
RTS
Plus RxD/TxD according to RS-485 specifications
Shielded connection terminal of bus cable
Not available
1 2 3 4 5 6
Terminal
Block
Termination
Resistor
Selector Switch
7
3.3 LEDs
These LED indicator lamps indicate the status of the PROFIBUS-DP or the SI-P1 card.
PWR LED
COMM LED
WD LED ERR LED
LED Display
Name Color Status
PWR
COMM
ERR
WD
Green
-
Green
-
Red
-
Green
Red
-
Operation
Status
Meaning
Lit Power supply ON Power is supplied to the SI-P1 card from the Inverter.
Not lit Power supply OFF • Power is not being supplied to the Inverter.
• Incorrect connection of the SI-P1 card does not supply power to the SI-P1 card.
Lit During communi cations connected
Normal communications are being carried out between the SI-P1 card and the PROFIBUS-DP master.
Not lit
Lit
Communications error/ power supply OFF
Communications error
• Normal communications are not being carried out between the
SI-P1 card and the PROFIBUS-DP master.
• Power is not being supplied.
An error occurred which disabled PROPFIBUS-DP communications.
Not lit During communications connected/ power
• An SI-P1 card address No. is overlapped.
• The address No. specified by the SI-P1 card is not the same as that specified by the PROFIBUS-DP master.
• Normal communications are being carried out between the SI-P1 card and the PROFIBUS-DP master.
• Power is not supplied.
Lit
Blinking
Lit supply OFF
During CPU run
During CPU run
SI-P1 card is being initialized.
SI-P1 card is operating normally.
Blinking
CPU error
CPU error
An error occurred in the SI-P1 card.
An error occurred in the Inverter.
Not lit Power supply OFF Power is not being supplied to the SI-P1 card. The SI-P1 card’s
CPU is not operating normally.
8
3.4 Address Switch
Rotary address switches to set the slave address on the PROFIBUS-DP are provided.
Use setting address switches 1 and 2 on the SI-P1 card to set the Inverter address on the PROFIBUS-DP.
Address = (address switch 2 setting) × 10 + (address switch 1 setting) × 1
Example) Set the address 15 in using the following procedure.
Set Address switch 2 to 1.
Set Address switch 1 to 5.
Address switch 2 Address switch 1
8
9
67
01 2
345 8
9
67
012
345
Set to 1.
Set to 5.
3.5 Termination Resistor Selector Switches
Attach a termination resistor on the final stage of the transmission line to reduce the reflection of the signal and stabilise the communications. When the SI-P1 card is connected as the last unit for the communications line, turn ON the termination resistor selector switch of the SI-P1 card to connect the termination resistor. No termination resistor has to be attached externally.
ON
Provided
( Switch is ON)
ON
1
Not provided
( Switch is OFF)
3.6 Transmission Speed Settings
Setting the transmission speed on the PROFIBUS-DP master automatically sets the same transmission speed on the SI-P1 card.
9
4. INSTALLATION AND WIRING
4.1 Installing the SI-P1 Card
Install the SI-P1 card is where the digital operator and the front cover of the Inverter are removed.
Use the following procedure to install the SI-P1 card.
(1) Turn off the main-circuit power supply.
(2) Wait at least the specified time (specified on the front cover) before removing the front cover of the
Inverter. Check to be sure that the CHARGE indicator is OFF.
(3) Remove the option clip to prevent C and D option and from rising. The option clip can be easily removed by holding onto the protruding portion of the clip and pulling it out.
(4) Insert the spacer, which is provided on the Inverter's control board, into the spacer hole of SI-P1 card.
(5) Fit the connector (JP1) on the SI-P1 card precisely to the Option-C connector.
(6) Pass the spacer through the spacer hole on the card. Check to be sure that it is precisely aligned with the 2CN position, and snap it into the proper position. Be sure to press it in firmly until you hear it snap into place.
(7) Insert the option clip to prevent the side with connector from rising.
(8) Connect the ground lead cable of the SI-P1 card to the control circuit terminal 12 on the Inverter control board.
(9) Select the termination resistor, set the address switches 1 and 2 to the correct setting, and connect the card to the peripheral devices.
(10) Reattach the front cover of the Inverter.
2CN
C Option Card
Connector
C Option Card mounting
Spacer
C Oprion Card Option Clip
(To prevent raising of C and D Option
Cards)
Fig. 2 Installing the SI-P1 Card
10
4.2 Wiring of the Communications Cable
Use the following procedure to wire the PROFIBUS-DP master to the terminal block of the SI-P1 card.
Use a shielded twisted-pair cable in conformance with the PROFIBUS specifications for the communications cable.
1) The following table shows the applicable cable sizes for the terminal block (JP3).
Standard wire
Single wire
UL
CSA
[Terminal: MINI COMBICON series, manufactured by Phoenix Contact Co., Ltd.]
[ mm 2 ]
0.14 to 1.5
0.14 to 1.5
-
-
AWG
28 to 16
28 to 16
30 to 14
28 to 16
I VAC
[ A] [ V]
8 160
8
8
160
300
8 300
2) Refer to Fig. 4.2 for the connection cable termination of the bus connection terminal on the SI-P1 card’s side.
3) Use a thin screwdriver that is less than 2.5 mm wide and less than 0.4 mm thick to loosen the terminal screw.
4) Connect the No.3 pin on the bus connection terminal block on the SI-P1 card’s side to the No. 8 pin on the PROFIBUS-DP master D-SUB’s side and connect the No.4 pin on the terminal block on the SI-P1 card’s side to the No. 3 pin on the PROFIBUS-DP master D-SUB’s side. (Refer to Fig. 4.)
5) Insert the wires from under the terminal block.
6) Tighten the terminal screws firmly.
(Tightening torque: 0.22 to 0.25 [N ・ m])
Wire
Stripped wire: approx. 5.5 mm long
Fig. 3 End of Connection Cable
11
Inverter
PROFIBUS-DP Master
3-phase
Power Supply
R
S
T
RxD/TxD-N
8
RxD/TxD-P
3
9-pin
D-SUB
Bus Connection
Terminal Block
(JP3) 1
2
SI-P1 Card
P
3
4
RxD/TxD-N
RxD/TxD-P
5
6
Shield
E
2CN
(60P)
Varispeed
Series
2CN
(60P)
E (G)
U
V
W
Notes: 1 A PROFIBUS cable is recommended for the shielded twisted-pair cable.
2 Separate the communications cables from the main circuit wiring or other power cables.
Fig. 4 Interconnection (when One Inverter Used)
Motor
M
12
PROFIBUS-DP Master
RxD/TxD-N
RxD/TxD-P
8
3
9-pin
D-SUB
P
3-phase
Power
Supply
SI-P1 Card
3
4
1
2
5
6
Bus
Connection
Terminal
Block (JP3)
RxD/TxD-N
RxD/TxD-P
Shield
E
2CN
(60P)
R
S
T
Inverter
Varispeed
Series
U
V
W
2CN
(60P)
E (G)
P
3-phase
Power
Supply
SI-P1 Card
5
6
2
3
4
1
Bus
Connection
Terminal
Block (JP3)
RxD/TxD-N
RxD/TxD-P
Shield
E
Inverter
2CN
(60P)
R
S
T
Varispeed
Series
U
V
W
2CN
(60P)
E (G)
Fig. 5 Interconnection (when Two Inverters Used)
Motor
M
Motor
M
13
5. FUNCTIONS
5.1 Initial Settings
5.1.1 Inverter Settings
Set the following constants, whenever necessary, before starting communications between the Inverter and the PROFIBUS-DP master.
Constant
No.
Name
Display
Reference selection *1 b1-01 b1-02
F6-01
F6-02
F6-03
Reference Source
Operation method selection *1
Run Source
Operation selection after communications error
BUS Fault Sel
Description
Set the inputting method for frequency reference.
0: Digital Operator
1: Control circuit terminals (analog inputs)
2: MEMOBUS communication (using SI-K2)
3: Option Card
4: MEMOBUS communication (for CP-717)
Set the operation method.
0: Digital Operator
1: Control circuit terminals (sequence inputs)
2: MEMOBUS communication (using SI-K2)
3: Option Card
4: MEMOBUS communication (for CP-717)
Set the stopping method for communication errors.
0: Deceleration stop using deceleration time in C1-02
1: Coast to stop
2: Emergency stop using deceleration time in C1-09
3: Continue operation *2
Input level of external fault from
Communications Option Card
0: Always detect
1: Detect during operation
EF0 Detection
Stopping method for external fault from Communications
Option Card
EF0 Fault Action
0: Deceleration stop using deceleration time in C1-02.
1: Coast to stop
2: Emergency stop using deceleration C1-09.
3: Continue operation *2
Torque reference/torque limit selection from optical option
F6-06
0: Torque reference/torque limit from transmission disabled
1: Torque reference/torque limit from transmission enabled.
Torque Ref/Lmt Sel
Factory
Setting
Inverter
F7 G7
1
1
1
0
1
1
○ ○
○ ○
○ ○
○ ○
○ ○
× ○
*1: Set b1-02 to 3 to run/stop through the PROFIBUS-DP communications. Set b1-01 to 3 to specify the frequency.
*2: Selecting "Continue operation" will allow the operation with the Inverter to continue when a fault occurs.
Provide other measures such as an emergency stop switch for safe operation.
*3: Enabled when A1-02 (Control method selection) is set to 3 (Flux vector) or 4 (open loop vector). In this case, the d5-01
(Torque control selection) setting can be used to select the torque reference or the torque limit.
d5-01 = 0 (Speed control): Torque limit setting d5-01 = 1 (Torque control): Torque reference setting
*4: When F1-06 is set to 1 (factory setting), the motor may not turns unless the torque reference or the torque limit is set from the PROFIBUS-DP master.
5.1.2 How to Get GSD Files
A GSD file is needed for using the SI-P1 card as a PROFIBUS-DP slave. Use the GSD file to register the
SI-P1 card as a slave to a PROFIBUS-DP master. Contact your Yaskawa representative for more information how to get a GSD file.
14
5.2 PROFIBUS-DP Data and I/O Map
Input and output data length of SI-P1 card can be chosen from among Extended data 1 (32 bytes),
Extended data 2 (12 bytes) and Basic data (6 bytes). Data length is set by the configuration tool of
PROFIBUS-DP master.
(1) Extended data 1 (data length: 32 bytes) z High-speed I/O data – Bytes 0 to 15
This data is directly transferred to the Inverter or from the Inverter. Using this high-speed I/O can control running or stopping of the Inverter.
z MEMOBUS message – Bytes 16 to 31
This data is transferred to the Inverter using MEMOBUS messages. All the Inverter constants and data can be accessed by this data. Because the data in this area is transferred to the Inverter after the SI-P1 card receives and edits it, time is required to return the data. The master must synchronize the timing of sending and receiving the data by the handshaking.
Also the run command or the frequency reference changes immediately by high-speed I/O even if it is commanded by MEMOBUS messages.
The following memory map shows the I/O data bytes and their designated functions.
15
Byte
25
26
27
28
21
22
23
24
29
30
31
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
0
3
4
1
2
Output Data
PROFIBUS-DP Master ⇒ Inverter
Function
Run Command
Frequency Reference
Torque Reference / Torque Limit
Torque Compensation
Not used
Multi-function Analog Output 1 (Terminal
FM) Output
Multi-function Analog Output 2 (Terminal
AM) Output
Multi-function Output
Function Code (Reference)
Starting Register No.
Number of Data Items
Data 1
Data 2
Data 3
Data 4
Not used
Handshaking Register
Byte
25
26
27
28
21
22
23
24
29
30
31
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
0
3
4
1
2
Input Data
Inverter ⇒ PROFIBUS-DP Master
Function
Inverter Status
Motor Speed
Torque Reference
Speed Detection PG Count Value
Frequency Reference
Output Frequency
Output Current
Main Speed Frequency Reference
(Terminal A2) Input
Function Code (Return)
Starting Register No.
Number of Data Items
Data 1
Data 2
Data 3
Data 4
Not used
Handshaking Register
16
(2) Extended data 2 (data length: 12 bytes) z High-speed I/O data – Bytes 0 to 3 z MEMOBUS Message – Bytes 4 to 11
Byte
8
9
10
11
5
6
3
4
7
0
1
2
Output Data
PROFIBUS-DP Master ⇒ Inverter
Function
Run Command
Frequency Reference
Function Code (Reference)
Starting Register No.
Number of Data Items
Data 1
Not used
Handshaking Register
(3) Basic data (data length: 6 bytes) z High-speed I/O data – Bytes 0 to 5
Byte
0
1
2
3
4
5
Output Data
PROFIBUS-DP Master ⇒ Inverter
Function
Run Command
Frequency Reference
Torque Reference/Torque Limit
Byte
8
9
10
11
5
6
3
4
7
0
1
2
Input Data
Inverter ⇒ PROFIBUS-DP Master
Function
Inverter Status
Motor Speed
Function Code (Return)
Starting Register No.
Number of Data Items
Data 1
Not used
Handshaking Register
Byte
0
1
2
3
4
5
Input Data
Inverter ⇒ PROFIBUS-DP Master
Function
Inverter Status
Motor Speed
Output Current
17
5.3 High-speed I/O Data
The data in this area is directly transferred to the Inverter.
PROFIBUS-DP Master ⇒ Inverter
For Extended data 1:
Byte
6
7
4
5
2
3
0
1
8
9
10
11
12
13
14
15
Not used
Function
Run Command
Frequency reference
Torque reference /Torque limit *1, *2
Torque compensation *1
Multi-function Analog
Output 1 (Terminal FM) *3
Multi-function Analog
Output 2 (Terminal AM) *3
Not used
Multi-function Output *4
Meaning
Run Command
Frequency reference
Upper byte
Lower byte
Upper byte
Lower byte
Torque reference/ Upper byte torque limit value Lower byte
Torque compensation
Upper byte
Lower byte
Set to "00H".
Analog output value
Analog output value
Set to "00H".
Upper byte
Lower byte
Upper byte
Lower byte
Bit 0: Multi-function contact output terminals M1 and
M2
Bit 1: Multi-function output 1 – terminals P1 and PC
Bit 2: Multi-function output 2 terminals P2 and PC
Bit 3 to 7: Set to "0".
Refer to the table5.1.
Remarks
1 = 0.01 Hz (Unit depends on the o1-03 setting.)
Setting range: zero to maximum frequency
1 = 0.1%
Setting range: F448H (-300.0) to 0BB8H (300.0%)
1 = 0.1%
Setting range: F448H (-300.0) to 0BB8H (300.0%)
F9FCH (-11V) to 0604H (11V)
F9FCH (-11V) to 0604H (11V)
0: Open
1: Closed
*1: Can be used when setting A1-02 (Control method selection) to 3 (Flux vector) or 4 (Open loop vector 2) for Varispeed
G7 series.
*2: Can be used when F6-06 (Torque reference/torque limit selection from optical option) is set to 1. In this case, the setting of d5-01 (Torque control selection) can be used to select the torque reference or the torque limit.
d5-01 = 0 (Speed control): torque limit value d5-01 = 1 (Torque control): torque reference value
*3: To select inverter multi-function analog output for communications, set H4-01 [Monitor selection (terminal FM)] and
H4-04 [Monitor selection (terminal AM)] to 31 (Not used).
*4: Inverter multi-function output ON/OFF during communications, set H2-01 [Multi-function input (terminal M1-M2)],
H2-02 [Multi-function output 1 (terminal P1)], and H2-03 [Multi-function output 2 (terminal P2)] to F.
18
Run Command (common to each data length)
Bit No.
0
1
2
Description
FWD run/stop
REV run/stop
Terminal S3 function
Remarks
Enabled when setting b1-02 (Operation method selection) to 3 (Option card).
3
4
5
6
7
8
9
A
B
C
D
E
F
Terminal S4 function
Terminal S5 function
Terminal S6 function
Terminal S7 function
Terminal S8 function *
External fault
Fault reset
Terminal S9 function *
Terminal S10 function *
Terminal S11 function *
Terminal S12 function *
Fault history trace clear
External BB command
Depends on H1-01 (multi-function selection 1: terminal S3 function selection) setting.
Depends on H1-02 (multi-function selection 2: terminal S4 function selection) setting.
Depends on H1-03 (multi-function selection 3: terminal S5 function selection) setting.
Depends on H1-04 (multi-function selection 4: terminal S6 function selection) setting.
Depends on H1-05 (multi-function selection 5: terminal S7 function selection) setting.
Depends on H1-06 (multi-function selection 6: terminal S8 function selection) setting.
1: External fault
1: Fault reset
Depends on H1-07 (multi-function selection 7: terminal S9 function selection) setting.
Depends on H1-08 (multi-function selection 8: terminal S10 function selection) setting.
Depends on H1-09 (multi-function selection 9: terminal S11 function selection) setting.
Depends on H1-10 (multi-function selection 10: terminal S12 function selection) setting.
1: Clears the fault history.
1: External Baseblock
*: Not used with Varispeed F7 series inverters since they do not have terminals S8 to S12.
19
Inverter ⇒ PROFIBUS-DP Master
For Extended data 1:
Byte
6
7
4
5
2
3
0
1
12
13
14
15
8
9
10
11
Function
Inverter status
Motor speed *1
Torque reference *2
Speed Detection PG Count
Value *3
Frequency reference
Output frequency
Output current
Inverter status
Description
16-bit hexadecimal data
16-bit hexadecimal data
16-bit hexadecimal data
16-bit hexadecimal data
16-bit hexadecimal data
16-bit hexadecimal data upper byte lower byte upper byte lower byte upper byte lower byte upper byte lower byte upper byte lower byte upper byte lower byte upper byte lower byte upper byte lower byte
1 = 0.01 A *5
Description
Refer to the table 5.2.
1 = 0.01 Hz *4
1 = 0.1%
1 = 1 pulse
1 = 0.01 Hz *4
1 = 0.01 Hz *4
Main Speed Frequency
Reference (Terminal A2) input
*6
16-bit hexadecimal data
1=0.1%
*1: Cannot be used when setting A1-02 (Control method selection) to 0 (V/f control).
*2: Cannot be used when setting A1-02 (Control method selection) to 0 (V/f control) or 1 (V/f with PG feedback).
*3: Can be used when setting A1-02 (Control method selection) to 1 (V/f with PG feed back) or 3 (Flux vector).
*4: Unit depends on the setting of o1-03 (Frequency units of reference setting and monitor).
*5: 1 is 0.1 A for Inverters with a capacity of more than 11 kW.
*6: Inverter analog input status (terminal A2) can be seen.
Inverter Status (common to each data length)
Bit No.
4
5
6
7
8
9
2
3
0
1
E
F
A
B
C
D
Name
Running
Zero Speed
Reverse Running
Reset Signal Being Input
Frequency (Speed) Agree
Inverter Operation Ready
Minor Fault
Major Fault
OPE Error
Recovery From Momentary Power Loss
Enabled/Disabled
LOCAL/REMOTE Selection
Multi-function Output Selection 1
Terminals M1-M2 Output
Multifunction Output Selection 2
Terminals P1-PC Output
Multifunction Output Selection 3
Terminals P1-PC Output
Motor Selection (1/2)
Zero Servo Completed*
Meaning
1: Running (run command ON or voltage output)
1: Zero speed
1: Reverse running
1: Reset signal being input.
1: Frequency (speed) agreed
1: Inverter operation ready.
1: Displayed at warning
1: Alarm
1: Operation error (constant setting error)
0: No recovery after momentary power loss
1: Running after momentary power loss
1: REMOTE selected
1: Closed
1: Closed
1: Closed
1: Motor 2 selected.
1: Zero servo is completed.
*: Can be used when setting A1-02 (Control method selection) to 3 (Flux vector) for Varispeed G7 Series.
20
5.4 MEMOBUS Message Area
In this area, a MEMOBUS message is transferred to the SI-P1 card, and the constants in the Inverter can be set, read, and monitored. Up to four data items can be written or read at one time.
Because the SI-P1 card edits the MEMOBUS message internally and transfers it to the Inverter after receiving the message, time is required to return it. It is necessary to synchronize sending or receiving of the data between the PROFIBUS-DP master and the SI-P1 card. Use the handshaking register for sychronization. For details on the handshaking register, refer to 5.4.4 "Handshaking Register."
To write a constant to the inverter, be sure to execute an ENTER command. The written data becomes valid by executing the ENTER command. For the details of the ENTER command, refer to 8.1.1 "Enter
Command."
5.4.1 Configuration of MEMOBUS Command Message
The following table shows the configuration of MEMOBUS command messages when the Extended data 1 is selected.
Byte
16 Function code
Name Function
MEMOBUS command code:
03H: Read command (reading Inverter internal data)
10H: Write command (writing data into the inverter)
Other codes: Not supported.
17
18
19
Starting Resistor No.
Number of Data Items
Starting resistor No.
upper byte lower byte
Write: Set doubled number of written data items (2 to 8).
Read: Set doubled number of read data items (2 to 8).
Data word 1 upper byte lower byte
20
21
22
23
24
Data 1*
Data 2* Data word 2
25
26
27
28
29
Data 3*
Data 4*
Data word 3
Data word 4
Not used -
30
31 Handshaking Resistor Refer to 5.4.4 "Handshaking Register."
*: Setting is needed only for the write command. Always select 00H for the read command.
upper byte lower byte upper byte lower byte upper byte lower byte
21
5.4.2 Configuration of MEMOBUS Response Messages
The following table shows the configuration of MEMOBUS response messages when the Extended data 1 is selected.
Byte
16 Function code
Name
17
18
19
Starting resistor No.
Number of data items
20
21
22
23
24
Data 1*
Data 2*
25
26
27
Data 3*
Data 4*
28
29
30
31
Not used
Handshaking register
*: Data is returned only for the read command.
Function
MEMOBUS response codes
00H: Waiting for response from inverter
03H: Response to read operation
10H: Response to write operation
83H: Read command error
90H: Write command error
Other codes: Not supported.
Starting resistor No.
upper byte
Data word 1 lower byte
Write: Set double number of written data items
Read: Set double number of read data items upper byte
Data word 2 lower byte upper byte
Data word 3
Data word 4 lower byte upper byte lower byte upper byte lower byte
Refer to 5.4.4 "Handshaking Register."
22
If an error occurs, the SI-P1 card sets MSB (Most Significant Bit) in the MEMOBUS response code to 1 and returns the error response. The number of data items is set to 02H and the following error codes are set to the lower bytes of Data 1.
Error Name
Function Code Error
Incorrect Register No.
Improper Number of
Data Items
Incorrect Data
Contents
Incrorrect Write-in
Error Code
01H
02H
03H
21H
22H
23H
24H
Description
Something other than 03H or 10H is specified for the function code.
Start register No. is greater than the setting of 600H.
Unused register No. is specified.
The number of data items at write-in or read-out is outside the acceptable range setting of the constant for writing in 2 to 8.
The setting of the constant for writing in is beyond the upper or lower limit of the constant.
Constant is incorrectly set at constant write-in.
A constant is written during running.
ENTER command is written during running.
Read-only data is written.
A constant is written when the Inverter is undervoltage (UV).
ENTER command is written when the Inverter is undervoltage (UV).
A constant is written while data is being stored.
23
5.4.3 Constant Settings Using MEMOBUS Commands
The written or read data of each constant is transferred in a hexadecimal value.
Negative values are expressed as a two's complement.
Example 1) The frequency reference is 30Hz.
30 Hz/0.01 Hz = 3000 → bb8H
Example 2) -5% is assigned as the bias for terminal FM of multi-function analog output 1.
5/0.1 = 50 → 32H
Converted into a two's complement → FFCEH
Example 3) 60.00 Hz is assigned for d1-01 (register No.: 0280H).
60.00Hz/0.01Hz = 6000 → 1770H
Byte Name
26
27
28
21
22
23
24
25
29
30
31
16
17
18
19
20
Function code
Starting Register No.
Number of Data Items
Data 1
Data 2
Data 3
Data 4
Not used
Handshaking Resistor *1
*1: Depends on the status of the previous data.
*2:Depends on the status of the fault.
Upper
Lower
Upper
Lower
Upper
Lower
Upper
Lower
Upper
Lower
Command
Message
10H
02H
80H
02H
17H
70H
00H
00H
00H
00H
00H
00H
00H
00H
00H
01H
Data
Response
Message
10H
02H
80H
02H
00H
00H
00H
00H
00H
00H
00H
00H
00H
00H
00H
01H
Response Message
(at Fault) *2
90H
00H
00H
02H
00H
02H
00H
00H
00H
00H
00H
00H
00H
00H
00H
01H
24
5.4.4 Handshaking Register
Handshaking is used to synchronize the timing of the sending or receiving of MEMOBUS message data between the SI-P1 card and the PROFIBUS-DP master. Use byte 31 in the PROFIBUS-DP master input area (from the SI-P1 card to the PROFIBUS-DP master) and in the output area (from the PROFIBUS-DP master to the SI-P1 card). When the status of byte 31 bit 7 changes, the data set to the output area on the
PROFIBUS master’s side becomes valid on the SI-P1 card. When the status obtained after changing byte
31 bit 7 in the output area coincides with the bit 7 status in the input area, the data in the input area on the
PROFIBUS-DP master’s side must be valid.
Handshaking Output Register
PROFIBUS-DP Master ⇒ SI-P1 Card b7 b0
HS - - - - - - INIT
Bit
7
1 to 6
0
Name
HS
-
INIT
Function
Handshaking bit. Used to synchronize the timing for sending or receiving data.
Changes the status when a new command is transmitted.
Note: Be sure to clear this bit to 0 when turning ON the power supply or setting bit 0 (INIT) to 1 to initialize the handshaking bit for the SI-P1 card.
Not used
Clears the handshaking bit for the SI-P1 card to 0
25
Handshaking Input Register
SI-P1 Card ⇒ PROFIBUS-DP Master b7
HS STATUS WD b0
-
Bit Name Function
7
5 to 6
HS
STATUS *
Handshaking bit. Used to synchronize the timing for sending or receiving data. Changes the status when a new response is transmitted.
Note: This bit is cleared to 0 when the power supply is turned ON or by setting the handshaking initialization bit (INIT) on the output register on the PROFIBUS-DP master’s side) to 1.
Status of the data exchange between the PROFIBUS-DP master and the
Inverter.
00H: Idle
01H: Sends a MEMOBUS command to the Inverter.
10H: Waits for a MEMOBUS command from the Inverter.
11H: Receives a response.
Counter increases every 64 ms.
1 to 4 WD *
0 Not used
* STATUS and WD are information for your reference.
26
5.4.5 Example of Handshaking
Clear the handshaking register HS bit (bit 7) to 0 for the PLC program after turning ON the power supply or re-initialization. The following drawing describes how to perform handshaking. The arrow marks indicate whether the PROFIBUS-DP master or the SI-P1 card has the control for the protocol.
Initial
Setting
PROFIBUS-DP Master SI-P1 Card
Handshaking Output Register Handshaking Input Register
0 0 Initial Setting
⇓
Creation of
Command
0 0
⇓
Command
Valid
1 ⇒ 0 New MEMOBUS Command for SI-P1
Card
⇓
1 0 Processing of Command
⇓
1 ⇐ 1 Response Valid
⇓
Creation of
Command
1 1 Idle
⇓
Command
Valid
0 ⇒ 1 New MEMOBUS Command to SI-P1 Card
⇓
0 1 Processing of Command
⇓
0 ⇐ 0 Response Valid
⇓
Creation of
Command
0 0 Idle
⇓
Command
Valid
1 ⇒ 0 New MEMOBUS Command to SI-P1 Card
⇓ etc.
27
5.4.6 Flow Chart
The following flow chart shows how handshaking works when a MEMOBUS message is used.
SI-P1 Card PROFIBUS-DP DP Master
Power ON or re-initialization START START
Initialization
Clears the handshaking register HS bit to "0".
Clears handshaking register HS bit to "0".
NO
Sends a new message.
YES
Creates a command message.
*: Toggle means to change the HS bit status from 0 to 1 or from 1 to 0.
Toggles handshaking register HS bit.*
Sends to slave.
NO
INDATA HS =
YES
Handles the response.
Receives for the master.
Transfers to dual port RAM.
Command message
Normal
Command executed.
Abnormal
Creates a response message.
Command not executed.
Creates a response message of a fault.
Transfers to dual port RAM.
Toggles hand-haking register HS bit.*
Sends to master.
28
6. TROUBLESHOOTING
6.1 Inverter Errors
The following table outlines the faults displayed in the Inverter’s operator and their causes and corrective actions.
Refer to the Instruction Manuals for any faults displayed in the operator other than those described below.
Display Meaning
OPE05
Sequence
Select
BUS
Option Com
Err
EF0
Opt External
Flt
CPF06
Option Error
Option card selection error
Option
Communications
Error
External fault input from communications option card
Option card connection error
Cause
The Option card was selected as the frequency reference source by setting b1-01 to 3, but an Option card is not connected.
Communications are not established between the PROFIBUS-DP master and the inverter.
External fault is input from the
PROFIBUS-DP master.
The Inverter and the Option card are not connected properly.
CPF20
Option A/D
Error
CPF21
Option CPU down
CPF22
Option Type
Err
CPF23
Option
DPRAM Err
Option card A/D converter error
Communications
Option card self diagnostic error
Communications
Option card model code error
Communications
Option card
DPRAM error
The Inverter and the Option card are not connected properly.
The option card’s A/D converter is faulty.
Option card fault
Corrective Action
Connect the Option card to the 2CN connector on the inverter control board.
Confirm the PROFIBUS-DP communications
LED display.
Turn OFF the external fault input.
Turn OFF the inverter power supply and confirm the Option card and Inverter connection. Then turn ON the power supply again.
Replace the Option card if the fault occurs again.
Turn OFF the inverter power supply and confirm the Option card and Inverter connection. Then turn ON the power supply again.
Replace the Option card if the fault occurs again.
Turn ON the inverter power supply again.
Replace the Option card if the fault occurs again.
29
6.2 Faults of PROFIBUS-DP Communications LED
The following table shows the faults, causes and corrective actions to be displayed in the LED on the SI-P1 card.
●
Green
Green
Green
LED Display
PWR COMM ERR
●
●
●
●
●
Red
Red
WD
●
Red
Red
Red Green
Meaning
Power OFF
CPU error
Inverter error
Communications error
Cause
Power is not supplied to the inverter.
SI-P1 card is not connected properly so that power is not supplied to the SI-P1 card.
SI-P1 card CPU is defective.
Inverter is defective.
An error occurred and disabled communications.
Green reen
Green
Green
Green
Green
Communications error
Red Green
●
Green
CPU Initialization
●
Green
Note: LED Status
: Lights
Normal
An error occurred and disabled communications.
SI-P1 card is being initialized.
Normal communications are enabled.
: Blinks ● : Not lit
Corrective Action
Check the inverter main circuit wiring and turn ON the power supply.
Turn OFF the inverter power supply and check the SI-P1 card and Inverter connection. Then turn ON the power supply again.
Turn ON the inverter power supply again. If the fault occurs again, replace the SI-P1 card.
Turn ON the inverter power supply again. If the fault occurs again, replace the Inverter.
Confirm that the address specified by the PROFIBUS-DP master coincides with the SI-P1 card address.
Confirm that the PROFIBUS-DP master is operating normally.
Confirm that the termination resistor is connected correctly to the communications line.
Confirm that the communications line is connected correctly.
Confirm that the communications line is separated from the main circuit wiring.
Confirm that the same address is not used for other devices in the
PROFIBUS-DP.
30
7. SPECIFICATIONS
Model
Item
PROFIBUS Data
Specifications
SI-P1
Extended data 1
High-speed I/O data (inputs: 16 bytes, outputs: 16 bytes)
MEMOBUS message (inputs: 16 bytes, outputs: 16 bytes)
Extended data 2
High-speed I/O data (inputs: 4 bytes, outputs: 4 bytes)
MEMOBUS message (inputs: 8 bytes, outputs: 8 bytes)
Basic data
High-speed I/O data (inputs: 6 bytes, outputs: 6 bytes)
4.75V to 5.25VDC (supplied from inverter) Operating Power Supply
Ambient Operating
Temperature
-10℃ to +45℃
Ambient Operation Humidity 95%RH max. (no condensation)
Storage Temperature -20℃ to +60℃
Application Site
Altitude
Communications Speed
Indoors (no corrosive gases, dust, or dirt)
1000 m max.
9.6k bps to 12M bps
31
8. APPENDIX
8.1 List of MEMOBUS Registers
8.1.1 Command Data (Read and Write)
Register No.
0000H
0001H
0002H
0003H
0004H
0005H
0006H
0007H
0008H
0009H
Meaning
BIT
Reserved
Run Command
0 Forward run/Stop 1: Forward run 0: Stop
1 Reverse run/Stop 1: Reverse run 0: Stop
2 External fault 1: Fault (EF0)
3 Fault reset 1: Fault reset
4 ComNet
5 ComCtrl
6 Multi-function input reference 3 (terminal S3)
7 Multi-function input reference 4 (terminal S4)
8 Multi-function input reference 5 (terminal S5)
9 Multi-function input reference 6 (terminal S6)
A Multi-function input reference 7 (terminal S7)
B Multi-function input reference 8 (terminal S8)
C Multi-function input reference 9 (terminal S9)
D Multi-function input reference 10 (terminal S10)
E Multi-function input reference 11 (terminal S11)
F Multi-function input reference 12 (terminal S12)
Frequency reference (Unit: set by o1-03)
Not used
Torque reference
Torque compensation
PID aimed value
Analog output 1 setting (-11V/-1540 to 11 V/1540, valid when H4-01 is set to 31)
Analog output 2 setting (-11V/-1540 to 11 V/1540, valid when H4-04 is set to 31)
Multi-function output setting
0 Contact output (terminals M1 and M2) 1: ON 0: OFF
1 PHC1 (terminals P1 and PC) 1: ON 0: OFF
2 PHC2 (terminals P2 and PC) 1: ON 0: OFF
3 PHC3 (terminals P3 and C3) 1: ON 0: OFF
4 PHC4 (terminals P4 and C4) 1: ON 0: OFF
5 Not used
6 Fault contact (terminals MA and MC) depends on the setting of bit 7.
1:ON 0:OFF
7 Fault contact (terminals MA and MC) 1:ON 0:OFF
8-F Not used
○
○
○
○
000AH
-
000EH
Not used ― ―
000FH
Reference selection setting
0 Not used
1 PID aimed value input 1: Valid 0: Invalid
2-B Not used
C 1: Simultaneous data terminal S5 input 1: Valid 0: Invalid
D 1: Simultaneous data terminal S6 input 1: Valid 0: Invalid
E 1: Simultaneous data terminal S7 input 1: Valid 0: Invalid
F 1: Simultaneous data terminal S8 input 1: Valid 0: Invalid
○
○
○
○
○
○
○
×
Note: When writing data into the register, write 0 to the unused bit. Do not write any data to the reserved register.
○
○
○
○
○
○
○
○
×
×
―
○
○
○
○
○ ○
○ ○
○ ○
○
○
○
○
○
―
○
○
○
○
○
○
○
Inverter
F7 G7
○ ○
○ ○
○
○
○
○
○
○
○
○
○
○
×
×
×
○
○
○
×
×
○
○
○ ○
○
○
○
○
○
○
― ―
× ○
× ○
○ ○
32
8.1.2 Status Data (Read Only)
Register No.
0010H
0011H
0012H
0013H
0014H
0015H
Meaning
BIT Display
Inverter status
0 1: Running
1 1: Zero speed
2 1: Reverse running
3 1: Reset signal inputting
4 1: Speed agree
5 1: Inverter ready
6 1: Minor fault
7 1: Major fault
8-D Not used
E 1: ComRef status
F 1: ComCtrl status
Operator status
0 1: OPE occurring
1 1: ERR occurring
2 1: PRG mode
3-4 1CN status 00: JVOP-160 01: JVOP-161 11: PC
5-F Not used
OPE No.
Inverter code F7: 2020H G7: 2050H
Fault contents 1
4
5
6
0 PUF Fuse blown
1 UV1 Main circuit undervoltage / main circuit MC operation error
2 UV2 Control power fault
3 UV3 Inrush prevention circuit fault
-
GF
Not used
Ground fault
OC Overcurrent
7
8
OV Main circuit Overvoltage
OH Cooling fan overheat
9 OH1 / Cooling fan stop in inverter
A OL1 Motor overload
B OL2 Inverter overload
C OL3 Overtorque 1
D OL4 Overtorque 2
E RR Internal braking transistor fault
F RH Installed braking resistor overheating
Fault contents 2
0 EF3 External fault (input terminal S3)
5
6
7
3
4
1
2
EF4 External fault (input terminal S4)
EF5 External fault (input terminal S5)
EF6 External fault (input terminal S6)
EF7 External fault (input terminal S7)
EF8 External fault (input terminal S8)
-
OS
Not used
Overspeed
8 DEV Excessive speed deviation
9 PGO PG disconnection detected
A PF Main circuit voltage fault
B LF Output open phase
C OH3 Motor overheat alarm
D OPR Operator connection fault
E ERR EEPROM write error
F OH4 Motor overheating
33
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
-
○
○ ○
○ ○
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
-
○
○
○
○
○
Inverter
F7 G7
○ ○
○
○
○
○
○
○
-
○
○
-
○
○
○
○
○
○
○
○
×
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
Register No.
0016H
0017H
0018H
0019H
Meaning
BIT Display
Fault contents 3
CE MEMOBUS communications error 0
1
2
3
BUS SI-P1 communications error
-
-
Not used
Not used
4
5
6
7
CF Control fault
SVE Zero servo fault
EFO External fault input from communications card
FBL PID control feedback command loss
8 UL3 Undertorque detection 1
9
A
UL4 Undertorque detection 2
OL7 High-slip braking OL
B EF9 External fault (input terminal S9)
C EF10 External fault (input terminal S10)
D EF11 External fault (input terminal S11)
E EF12 External fault (input terminal S12)
9
A
B
7
8
5
6
2
3
4
0
1
C
D
E
F
F CPF Hardware fault
CPF contents 1
0 Not used
1 Not used
2 CPF02 occurring
3 CPF03 occurring
4 CPF04 occurring
5 CPF05 occurring
6 CPF06 occurring
7-F Not used
CPF contents 2
0 CPF20 occurring
1 CPF21 occurring
2 CPF22 occurring
3 CPF23 occurring
4-F Not used
Minor fault contents 1
UV Main circuit undervoltage
OV Main circuit overvoltage
OH Cooling fin overheating
OH2 Inverter overheating pre-alarm
OL3 Overtorque 1
OL4 Overtorque 2
EF FWD/REV run command input together
BB External baseblock
EF3 External fault (input terminal S3)
EF4 External fault (input terminal S4)
EF5 External fault (input terminal S5)
EF6 External fault (input terminal S6)
EF7 External fault (input terminal S7)
EF8 External fault (input terminal S8)
- Not used
OS Overspeed
34
×
×
×
×
○
○
○
○
○
○
-
○
○
○
○
○
-
-
○
○
○
○
○
○
○
-
○
○
○
○
×
-
○
○
○
○
○
-
○
×
○
○
○
○
○
-
Inverter
F7 G7
○ ○
○
○
-
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
-
-
○
○
○
○
○
○
○
-
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
Register No.
001AH
001BH
0020H
Meaning
BIT Display
Minor fault 2
0 DEV Excessive speed deviation
1 PGO PG disconnection
2
3
4
OPR Digital operator connection fault
CE MEMOBUS communications error
BUS SI-P1 communications error
A
B
8
9
5 CALL Waiting for communications
6 OL1 Motor overload
7 OL2 Inverter overload
- Not used
EFO SI-P1 external fault detecting
- Motor switching during running
FBL PID feedback reference lost
C CALL Communications on standby
D UL3 Undertorque 1
E UL4 Undertorque 2
F
Minor fault 3
0
SE Sequence Error
- Not used
4
5
6-F
1
2
3
OH3 Motor overheating alarm
EF9 External fault (input terminal S9)
EF10 External fault (input terminal S10)
EF11 External fault (input terminal S11)
EF12 External fault (input terminal S12)
- Not used
Inverter status
0 1: Running
1 1: Reverse running
2 1: Inverter ready
3 1: Fault
4 1: Data setting error
5 1: Multi-function contact output (M1 and M2) ON
6 1: Multi-function PHC1 output (P1 and PC)
7 1: Multi-function PHC2 output (P2 and PC)
8 1: Multi-function PHC3 output (P3 and C3)
9 1: Multi-function PHC4 output (P4 and C4)
A-F Not used
○
○
○
-
○
○
×
×
×
-
○
×
○
×
×
-
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
Inverter
F7 G7
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
-
○
○
○
○
○
-
○
○
○
35
Register No.
0021H
0022H
0023H
0024H
0025H
0026H
0027H
0028H
0029H
002AH
002BH
Meaning
BIT Display
Fault contents
0 Overcurrent (OC), ground fault (GF)
1 Main circuit overvoltage (OV)
2 Inverter overload (OL2)
3 Radiation fan overheating, inverter internal cooling fan stop [OH (OH1)]
4 Internal braking transistor fault (rr), installed braking resistor overheating (RH)
5 Fuse blown (PUF)
6 PID control feedback command loss (FBL)
7 External fault (EF0, EF3 to EF7)
8 Hardware fault (CPF)
9 Motor overload (OL1), overtorque detection 1 (OL3), overtorque detection 2
(OL4)
A PG disconnection (PGO), Overspeed (OS), excessive speed deviation (DEV)
B Main circuit undervoltage (UV) detecting
C
Main circuit undervoltage, main circuit MC operation fault (UV1), control power fault (UV2), inrush prevention circuit fault (UV3)
D Output open phase (LF)
E MEMOBUS communications error
F Operator connection fault (OPR)
Data Link Status
0 Data writing
1 Not used
2 Not used
3 Upper/lower limit error
4 Data consistency error
5-F Not used
Frequency reference (U1-01)
Output frequency (U1-02)
Output voltage reference (U1-06)
Output current (U1-03)
Output power (U1-08)
Torque reference (U1-09)
Not used
Not used
Sequence input status
0 1: Multi-function contact input terminal S1 ON
1 1: Multi-function contact input terminal S2 ON
2 1: Multi-function contact input terminal S3 ON
3 1: Multi-function contact input terminal S4 ON
4 1: Multi-function contact input terminal S5 ON
5 1: Multi-function contact input terminal S6 ON
6 1: Multi-function contact input terminal S7 ON
7 1: Multi-function contact input terminal S8 ON
8 1: Multi-function contact input terminal S9 ON
9 1: Multi-function contact input terminal S10 ON
A 1: Multi-function contact input terminal S11 ON
B 1: Multi-function contact input terminal S12 ON
C-F Not used
○
○
○
-
-
○
○
○
○
○
○
○
○
○
○
○
-
-
○
○
-
○
○
○
○
○
○
○
×
×
-
○
×
×
×
○
○
○
○
○
○
○
○
Inverter
F7 G7
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
-
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
-
-
○
○
○
○
○
○
○
○
-
○
○
○
○
36
002EH
-0030H
0031H
0032H
0033H
0034H
-0037H
0038H
0039H
003AH
003BH
003CH
Register No.
002CH
002DH
Meaning
BIT Display
Inverter status
0 1: Running
1 1: Zero speed
2 1: Speed agree
3 1: Arbitrary speed agree
4 Frequency detection 1 1: Output frequency ≦ L4-01
5 Frequency detection 2 1: Output frequency ≧ L4-01
6 1: Inverter ready
7 1: Undervoltage detection
8 1: Baseblocking
9 Frequency mode 1: Other than communications 0: Communications
A Run command mode 1: Other than communications 0: Communications
B 1: Overtorque detection
C 1: Frequency reference loss
D 1: Fault retry
E 1: Fault occurring
F 1: MEMOBUS time over
Multi-function output status
0 Multi-function contact output (M1 and M2) ON
1 Multi-function PHC output (P1 and PC) ON
2 Multi-function PHC output (P2 and PC) ON
3 Multi-function PHC output (P3 and C3) ON
4 Multi-function PHC output (P4 and C4) ON
5-F Not used
Not used
003DH
003EH
003FH
Main circuit DC bus voltage
Torque monitor
Output power
Not used
PID control feedback
PID input volume
PID output volume
Software No. (CPU)
Software No. (FLASH)
Communications error contents
0 CRC error
1 Incorrect data length
2 Not used
3 Parity error
4 Overrun error
5 Framing error
6 Time over
7-F Not used kVA setting
Control mode
○
○
○
-
○
○
○
○
○
○
×
-
-
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Inverter
F7 G7
○ ○
○ ○
○
○
○
○
○
○
○
○
○
-
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
-
○
-
○
○
○
○
○
○
-
○
-
○
○
○
○
37
8.1.3 Monitor Data (Read Only)
For details, refer to the Varispeed Instruction Manuals. The units to be monitored are the same as the operator displayed units excluding the units related to frequency and output current.
Status Monitor (U1-XX)
Register No.
0040H
0041H
0042H
0043H
0044H
0045H
0046H
0047H
0048H
0049H
004AH
004BH
004CH
004DH
004EH
004FH
0050H
Constant
Contents
No.
BIT
U1-01 Frequency reference *1
U1-02 Output frequency *1
U1-03 Output current (100%/8192) *2
U1-04 Control mode
U1-05 Motor speed *1
U1-06 Output voltage reference
U1-07 Main circuit DC bus voltage
U1-08 Output power
U1-09 Torque reference (internal)
Input terminal status
0 1: Control circuit terminal S1 closed
1 1: Control circuit terminal S2 closed
2 1: Control circuit terminal S3 closed
U1-10
3 1: Control circuit terminal S4 closed
4 1: Control circuit terminal S5 closed
5 1: Control circuit terminal S6 closed
6 1: Control circuit terminal S7 closed
7 1: Control circuit terminal S8 closed
8 1: Control circuit terminal S9 closed
U1-11
9 1: Control circuit terminal S10 closed
A 1: Control circuit terminal S11 closed
B 1: Control circuit terminal S12 closed
C-F Not used
Output terminal status
0 1: Control circuit terminal M1 and M2 closed
1 1: Control circuit terminal P1 closed
2 1: Control circuit terminal P2 closed
3 1: Control circuit terminal P3 closed
4 1: Control circuit terminal P4 closed
5-6 Not used
7 1: Terminal MA/MB and MC closed
U1-12
8-F Not used
Operation status
0 1: Running
1 1: Zero speed
2 1: Reverse running
3 1: Reset signal inputting
4 1: Speed agree
5 1: Inverter ready
6 1: Minor fault
7 1: Major fault
8 Not used
U1-13 Cumulative operation time
U1-14 Software No. (FLASH)
U1-15 Frequency reference terminal A1 input voltage
U1-16 Multi-function analog input terminal A2 input voltage
U1-17 Multi-function analog input terminal A3 input voltage
Inverter
F7 G7
×
-
○
×
×
×
○
○
×
○
○
○
×
×
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
×
○
○
○
-
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
-
○
○
38
Register No.
0051H
0052H
0053H
0054H
0055H
0056H
0057H
0058H
0059H
005AH
005BH
005DH
005EH
005FH
0060H
0061H
0062H
0063H
0064H
0065H
0066H
0067H
0069H
006AH
006BH
006CH
Constant
No.
BIT
Meaning
U1-18 Motor secondary current (Iq)
U1-19 Motor exciting current (Id)
U1-20 Output frequency after soft-start *1
U1-21 Speed control (ASR) input
U1-22 Speed control (ASR) output
Not used
U1-24 PID control feedback
U1-25 DI-16H2 input status
U1-26 Output voltage reference (Vq)
U1-27 Output voltage reference (Vd)
U1-28 Software No. (CPU)
Not used
Not used
U1-32 ACR output of q axis
U1-33 ACR output of d axis
U1-34 OPE fault constant
U1-35 Zero servo movement pulses
U1-36 PID input volume
U1-37 PID output volume
U1-38 PID command
MEMOBUS communications error code
0 1: CRC error
U1-39
1 1: Incorrect data length
2 Not used
3 1: Parity error
4 1: Overrun error
5 1: Framing error
6 1: Time over
7-F Not used
U1-40 Cooling fan operating time
U1-42 Motor magnetic flux calculated value
U1-43 Motor magnetic flux current compensated value
U1-44 Speed control (ASR) output (without filter)
U1-45 Feed-forward control output
*1: The unit of frequency is 0.1 Hz with sign when command code 100FH/200FH bit 0 is set to 0.
The unit of frequency depends on the o1-03 setting without a sign when command code 100FH/200FH bit 0 is set to 1.
*2: Output current is 100%/1892. 100% indicates the inverter rated current.
Inverter
F7 G7
○
○
○
-
○
○
○
○
○
-
○
×
○
○
○
-
○
○
-
○
-
○
○
×
×
×
×
○
○
○
×
○
○
○
○
○
○
-
○
○
○
○
○
-
○
○
○
○
○
-
○
○
-
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
39
Status Monitor (U2-XX)
Register No.
0080H
0081H
0082H
0083H
0084H
0085H
0086H
0087H
0088H
0089H
008AH
008BH
008CH
008DH
Constant
Meaning
No.
BIT
U2-01 Current fault (Refer to the next page for Fault Codes.)
U2-02 Last fault (Refer to the next page for Fault Codes.)
U2-03 Frequency reference at fault
U2-04 Output frequency at fault
U2-05 Output current at fault
U2-06 Motor speed at fault
U2-07 Output voltage reference at fault
U2-08 DC bus voltage at fault
U2-09 Output power at fault
U2-10 Torque reference at fault
Input terminal status at fault
0 1: Control circuit terminal S1 closed
1 1: Control circuit terminal S2 closed
2 1: Control circuit terminal S3 closed
3 1: Control circuit terminal S4 closed
4 1: Control circuit terminal S5 closed
U2-11
U2-12
5 1: Control circuit terminal S6 closed
6 1: Control circuit terminal S7 closed
7 1: Control circuit terminal S8 closed
8 1: Control circuit terminal S9 closed
9 1: Control circuit terminal S10 closed
A 1: Control circuit terminal S11 closed
B 1: Control circuit terminal S12 closed
C-F Not used
Output terminal status at fault
0 1: Control circuit terminals M1 and M2 closed
1 1: Control circuit terminal P1 closed
2 1: Control circuit terminal P2 closed
3 1: Control circuit terminal P3 closed
4 1: Control circuit terminal P4 closed
5-6 Not used
7 1: Terminal MA/MB and MC closed
U2-13
8 Not used
Operation status at fault
0 1: Running
1 1: Zero speed
2 1: Reverse running
3 1: Reset signal inputting
4 1: Speed agree
5 1: Inverter ready
6 1: Minor fault
7 1: Major fault
8 Not used
U2-14 Cumulative operation time at fault
Fault History (U3-XX)
Register No.
0090H
0091H
0092H
0093H
0094H
0095H
0096H
0097H
Constant
No.
Meaning
U3-01 Most recent fault (Refer to the table for Fault Codes.)
U3-02 Second most recent fault (Refer to the table for Fault Codes.)
U3-03 Third most recent fault (Refer to the table for Fault Codes.)
U3-04 Fourth most recent or oldest fault (Refer to the table for Fault Codes.)
U3-05 Cumulative operation time at fault
U3-06 Accumulated time of second fault
U3-07 Accumulated time of third fault
U3-08 Accumulated time of fourth/oldest fault
40
Inverter
F7 G7
×
×
-
○
○
○
○
○
×
×
×
-
○
○
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
-
○
○
○
-
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
-
○
Inverter
F7 G7
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Display
Fault Codes of 0080, 0081, 0090 to 0093
Meaning
PUF Fuse blown
UV1 Main circuit undervoltge
UV2 Control power fault
UV3 Inrush prevention circuit fault
Not used
GF Ground fault
OC Overcurrent
OV Overvoltage
OH
OH1
Cooling fan overheating / inverter internal cooling fan overheating
OL1 Motor overload
OL2 Inverter overload
OL3 Overtorque 1
OL4 Overtorque 2
RR Internal braking transistor fault
RH Installed braking resistor overheating
EF3 External fault (input terminal S3)
EF4 External fault (input terminal S4)
EF5 External fault (input terminal S5)
EF6 External fault (input terminal S6)
EF7 External fault (input terminal S7)
EF8 External fault (input terminal S8)
Not used
OS Overspeed
DEV Excessive speed deviation
PGO PG disconnection detected
PF Main circuit voltage fault
LF Output open-phase
OPR Digital operator connection fault
ERR EEPROM write error
CE MEMOBUS communications error
BUS SI-P1 communications error
-
Not used
Not used
CF Control fault
SVE Zero servo fault
EFO External fault from SI-P1
FBL PID control feedback command loss
UL3 Undertorque 1
UL4 Undertorque 2
OL7 High-slip braking OL
EF9 External fault (input terminal S9)
EF10 External fault (input terminal S10)
EF11 External fault (input terminal S11)
EF12 External fault (input terminal S12)
Not used
VCF DC bus neutral overvoltage
Fault Code
18H
19H
1AH
1BH
1CH
1EH
12H
13H
14H
15H
16H
17H
1FH
21H
22H
23H
24H
25H
26H
08H
09H
0AH
0BH
0CH
0DH
01H
02H
03H
04H
05H
06H
07H
0EH
0FH
10H
11H
27H
28H
29H
2AH
2BH
2CH
2DH
2EH
2FH
30H
31H
×
×
-
×
×
×
×
○
×
×
○
×
○
○
-
-
○
○
○
○
○
○
-
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
Inverter
F7 G7
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
○
○
○
○
-
-
○
○
○
○
○
○
-
○
○
41
8.1.4 Enter Command (Write Only)
Register No.
Name
0900H Enter command
0910H Enter command
Contents
Writes in constant data to non-volatile memory
(EEPROM).
Does not write in constant data to non-volatile memory (EEPROM).
Set Value
0000H
0000H
Enter Command
To write in a constant to the inverter from the PROFIBUS-DP master, be sure to send an Enter command.
The written set value becomes valid when the inverter receives the Enter command. There are two types of Enter commands as described below.
Enter command that writes in a constant to the non-volatile memory
This command is executed by writing "0" to register number 0900H. When this command is executed, the changed set value is written in to the non-volatile memory and becomes valid. The value is stored in the inverter even after the power supply is turned OFF. However, the data can be written in to the inverter's non-volatile memory at most 100,000 times. So do not use this Enter command unnecessarily.
Enter command that does not write in a constant to the non-volatile memory
This command is executed by writing "0" to register number 0910H. When this command is executed, the changed set value is not written in to the non-volatile memory and becomes valid. The value is eliminated and returned to its original value when the power supply is turned OFF. Therefore, use this command when the set value of a constant is to be changed temporarily.
Register numbers 0900H and 0910H are exclusive for writing. If any of these registers is read out,
"Incorrect fault No." (error code 02H) occurs.
42
8.1.5 Inverter Constants (Read and Write)
Register No.
Constant
No.
Name
0100H
0101H
0102H
0103H
0104H
0105H
0106H-0125H
0189H
018AH
018BH
018CH
0191H
0192H
0193H
0195H
01A3H
01A4H
0180H
0181H
0182H
0183H
0184H
0185H
0186H
0187H
01A5H
01A6H
01A7H
01A8H
01A9H
01AAH
01ABH
01ACH
01ADH
01AEH
01AFH
01B0H
01B1H
01B2H
01B3H
01B4H
01B5H
A1-00 Language selection for digital operator display
A1-01 Constant access level
A1-02 Control method selection
A1-03 Initialize
A1-04 Password
A1-05 Password setting
A2-01
to 32
User setting constants b1-01 Reference selection b1-02 Operation method selection b1-03 Stopping method selection b1-04 Prohibition of reverse operation b1-05 Operation selection for setting E1-09 or less b1-06 Read sequence input twice b1-07 Operation selection after switching to remote mode b1-08 Run command selection in programming mode b2-01 Zero speed level (DC injection braking starting frequency) b2-02 DC injection braking current b2-03 DC injection braking time at start b2-04 DC injection braking time at stop b3-01 Speed search selection b3-02 Speed search operating current b3-03 Speed search deceleration time b3-05 Speed search wait time b4-01 Timer function ON-delay time b4-02 Timer function OFF-delay time b5-01 PID control mode selection b5-02 Proportional gain (P) b5-03 Integral (I) time b5-04 Integral (I) limit b5-05 Derivative (D) time b5-06 PID limit b5-07 PID offset adjustment b5-08 PID primary delay time constant b5-09 PID output characteristics selection b5-10 PID output gain b5-11 PID reverse output selection b5-12 Selection of PID feedback command loss detection b5-13 PID feedback command loss detection level b5-14 PID feedback command loss detection time b5-15 PID sleep function operation level b5-16 PID sleep operation delay time b5-17 Acceleration/deceleration time for PID reference
○
○
○
○
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Inverter
○
○
○
F7 G7
○
○
○
○
○
○
○
○
○
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
43
021BH
021CH
021DH
021EH
021FH
0220H
0221H
0222H
0223H
0224H
0225H
0226H
0227H
022DH
020BH
020CH
020DH
020EH
020FH
0210H
0211H
0212H
0213H
0215H
0216H
01B6H
01B7H
01B8H
01B9H
01CAH
01CBH
01CCH
01CDH
01CEH
01CFH
01D0H
01D1H
01DAH
01DBH
0200H
0201H
0202H
0203H
0204H
0205H
0206H
0207H
0208H
0209H
020AH
Register No.
Constant
No.
Name b6-01 Dwell frequency at start b6-02 Dwell time at start b6-03 Dwell frequency at stop b6-04 Dwell time at stop b7-01 Droop control gain b7-02 Droop control delay time b8-01 Energy-saving mode selection b8-02 Energy-saving gain b8-03 Energy-saving filter time constant b8-04 Energy-saving coefficient b8-05 Power detection filter time constant b8-06 Search operation voltage limiter b9-01 Zero-servo gain b9-02 Zero-servo completion width
C1-01 Acceleration time 1
C1-02 Deceleration time 1
C1-03 Acceleration time 2
C1-04 Deceleration time 2
C1-05 Acceleration time 3
C1-06 Deceleration time 3
C1-07 Acceleration time 4
C1-08 Deceleration time 4
C1-09 Emergency stop time
C1-10 Accel/decel time setting unit
C1-11 Accel/decel time switching frequency
C2-01 S-curve characteristic time at acceleration start
C2-02 S-curve characteristic time at acceleration end
C2-03 S-curve characteristic time at deceleration start
C2-04 S-curve characteristic time at deceleration end
C3-01 Slip compensation gain
C3-02 Slip compensation primary delay time
C3-03 Slip compensation limit
C3-04 Slip compensation selection during regeneration
C3-05 Output voltage limit operation selection
C4-01 Torque compensation gain
C4-02 Torque compensation primary delay time constant
C5-01 ASR proportional (P) gain 1
C5-02 ASR integral (I) time 1
C5-03 ASR proportional (P) gain 2
C5-04 ASR integral (I) time 2
C5-05 ASR limit
C5-06 ASR primary delay time
C5-07 ASR switching frequency
C5-08 ASR integral (I) limit
C6-01 CT/VT selection
C6-02 Carrier frequency selection
C6-03 Carrier frequency upper limit
C6-04 Carrier frequency lower limit
C6-05 Carrier frequency proportional gain
C6-11 Carrier frequency selection for open-loop vector control 2
44
Inverter
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
×
×
○
○
○
○
○
○
○
○
○
○
○
×
×
×
○
○
○
○
○
○
×
×
F7 G7
○ ○
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
○
○
○
○
○
0289H
028AH
0293H
0294H
0295H
0296H
0297H
0298H
0299H
029AH
029BH
029CH
029DH
029EH
029FH
02A0H
02A1H
02A2H
02A4H
0280H
0281H
0282H
0283H
0284H
0285H
0286H
0287H
0288H
028BH
028CH
028DH
028EH
028FH
0290H
0291H
0292H
Register No.
Constant
No.
Name d1-01 Frequency reference 1 d1-02 Frequency reference 2 d1-03 Frequency reference 3 d1-04 Frequency reference 4 d1-05 Frequency reference 5 d1-06 Frequency reference 6 d1-07 Frequency reference 7 d1-08 Frequency reference 8 d1-09 Frequency reference 9 d1-10 Frequency reference 10 d1-11 Frequency reference 11 d1-12 Frequency reference 12 d1-13 Frequency reference 13 d1-14 Frequency reference 14 d1-15 Frequency reference 15 d1-16 Frequency reference 16 d1-17 Jog frequency reference d2-01 Frequency reference upper limit d2-02 Frequency reference lower limit d2-03 Master speed reference lower limit d3-01 Jump frequency 1 d3-02 Jump frequency 2 d3-03 Jump frequency 3 d3-04 Jump frequency width d4-01 Frequency reference hold function selection d4-02 + - Speed limits d5-01 Torque control selection d5-02 Torque reference delay time d5-03 Speed limit selection d5-04 Speed limit d5-05 Speed limit bias d5-06 Speed/torque control switching timer d6-01 Field weakening level d6-02 Field frequency d6-03 Field forcing function selection d6-05 AφR time constant
Inverter
○
○
○
○
○
○
○
○
○
×
×
○
○
×
×
×
×
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
F7 G7
○ ○
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
45
030EH
030FH
0310H
0311H
0312H
0313H
0314H
0315H
0316H
0317H
0318H
0300H
0302H
0303H
0304H
0305H
0306H
0307H
0308H
0309H
030AH
030BH
030CH
0321H
0322H
0323H
0324H
0325H
0326H
0327H
0319H
031AH
031BH
031CH
031DH
031EH
031FH
0320H
Register No.
Constant
No.
Name
E1-01 Input voltage setting
E1-03 V/f pattern selection
E1-04 Max. output frequency
E1-05 Max. voltage
E1-06 Base frequency
E1-07 Mid. output frequency
E1-08 Mid. output frequency voltage
E1-09 Min. output frequency
E1-10 Min. output frequency voltage
E1-11 Mid. output frequency 2
E1-12 Mid. output frequency voltage 2
E1-13 Base voltage
E2-01 Motor rated current
E2-02 Motor rated slip
E2-03 Motor no-load current
E2-04 Number of motor poles
E2-05 Motor line-to-line resistance
E2-06 Motor leak inductance
E2-07 Motor iron saturation coefficient 1
E2-08 Motor iron saturation coefficient 2
E2-09 Motor mechanical loss
E2-10 Motor iron loss for torque compensation
E2-11 Motor rated output
E3-01 Motor 2 control method selection
E3-02 Motor 2 max. output frequency
E3-03 Motor 2 max. voltage
E3-04 Motor 2 max. voltage frequency
E3-05 Motor 2 mid. output frequency
E3-06 Motor 2 mid. output frequency voltage
E3-07 Motor 2 min. output frequency
E3-08 Motor 2 min. output frequency voltage
E4-01 Motor 2 rated current
E4-02 Motor 2 rated slip
E4-03 Motor 2 no-load current
E4-04 Motor 2 number of poles
E4-05 Motor 2 line-to-line resistance
E4-06 Motor 2 leak inductance
E4-07 Motor 2 rated capacity
Inverter
○
○
○
○
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
F7 G7
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
46
038FH
0390H
0399H
039AH
039BH
039CH
039DH
039EH
039FH
03A0H
03A1H
0391H
0392H
0393H
0394H
0395H
0396H
0397H
0398H
03A2H
03A3H
03A4H
03A5H
03A7H
0380H
0381H
0382H
0383H
0384H
0385H
0386H
0387H
0388H
0389H
038AH
038BH
038CH
038DH
Register No.
Constant
No.
Name
F1-01 PG constant
F1-02 Operation selection at PG open circuit (PGo)
F1-03 Operation selection at Overspeed (oS)
F1-04 Operation selection at deviation (dEv)
F1-05 PG rotation
F1-06 PG division rate (PG pulse monitor)
F1-07 Integral value during accel/decel enable/disable
F1-08 Overspeed detection level
F1-09 Overspeed detection delay time
F1-10 Excessive speed deviation detection level
F1-11 Excessive speed deviation detection delay time
F1-12 Number of PG gear teeth 1
F1-13 Number of PG gear teeth 2
F1-14 PG open-circuit detection time
F2-01 Bi-polar or uni-polar input selection
F3-01 Digital input option
F4-01 Channel 1 monitor selection
F4-02 Channel 1 gain
F4-03 Channel 2 monitor selection
F4-04 Channel 2 gain
F4-05 Channel 1 output monitor bias
F4-06 Channel 2 output monitor bias
F4-07 Analog output signal level for channel 1
F4-08 Analog output signal level for channel 2
F5-01 Channel 1 output selection
F5-02 Channel 2 output selection
F5-03 Channel 3 output selection
F5-04 Channel 4 output selection
F5-05 Channel 5 output selection
F5-06 Channel 6 output selection
F5-07 Channel 7 output selection
F5-08 Channel 8 output selection
F5-09 DO-08 output mode selection
F6-01 Operation selection after communications error
F6-02 Input level of external fault from Communications Option Card
F6-03 Stopping method for external fault from Communications Option Card
F6-04 Trace sampling from Communications Option Card
F6-06 Torque reference/torque limit selection from optical option
Inverter
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
F7 G7
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
47
041DH
041EH
041FH
0420H
0421H
0422H
0423H
0424H
0425H
0426H
0427H
0428H
0429H
042AH
042BH
042CH
042DH
042EH
042FH
0430H
0431H
0432H
0410H
0411H
0412H
0413H
0414H
0415H
0416H
0417H
0418H
0419H
041AH
041BH
041CH
0400H
0401H
0402H
0403H
0404H
0405H
0406H
0407H
0408H
0409H
040BH
040CH
040DH
040EH
040FH
Register No.
Constant
No.
Name
H1-01 Terminal S3 function selection
H1-02 Terminal S4 function selection
H1-03 Terminal S5 function selection
H1-04 Terminal S6 function selection
H1-05 Terminal S7 function selection
H1-06 Terminal S8 function selection
H1-07 Terminal S9 function selection
H1-08 Terminal S10 function selection
H1-09 Terminal S11 function selection
H1-10 Terminal S12 function selection
H2-01 Terminal M1-M2 function selection (contact)
H2-02 Terminal P1 function selection (open-collector)
H2-03 Terminal P2 function selection (open-collector)
H2-04 Terminal P3 function selection (open-collector)
H2-05 Terminal P4 function selection (open-collector)
H3-01 Signal level selection (terminal A1)
H3-02 Gain (terminal A1)
H3-03 Bias (terminal A)
H3-04 Signal level selection (terminal A3)
H3-05 Multi-function analog input (terminal A3)
H3-06 Gain (terminal A3)
H3-07 Bias (terminal A3)
H3-08 Multi-function analog input terminal A2 function selection
H3-09 Multi-function analog input terminal A2 signal level selection
H3-10 Gain (terminal A2)
H3-11 Bias (terminal A2)
H3-12 Analog input filter time constant
H3-13 Terminal A1/A2 switching
H4-01 Monitor selection (terminal FM)
H4-02 Gain (terminal FM)
H4-03 Bias (terminal FM)
H4-04 Analog output 1 signal level selection
H4-05 Gain (terminal AM)
H4-06 Bias (terminal AM)
H4-07 Analog output 1 signal level selection
H4-08 Analog output 2 signal level selection
H5-01 Station address
H5-02 Communication speed selection
H5-03 Communication parity selection
H5-04 Stopping method after communication error
H5-05 Communication error detection selection
H5-06 Send wait time
H5-07 RTS control ON/OFF
H6-01 Pulse train input function selection
H6-02 Pulse train input scaling
H6-03 Pulse train input gain
H6-04 Pulse train input bias
H6-05 Pulse train input filter time
H6-06 Pulse train monitor selection
H6-07 Pulse train monitor scaling
48
Inverter
×
×
○
○
○
○
○
○
×
×
×
○
○
○
○
○
×
×
×
×
×
○
×
×
F7 G7
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Register No.
Constant no.
048FH
0490H
0491H
0492H
0493H
0494H
0499H
049AH
049BH
049CH
049DH
0480H
0481H
0482H
0483H
0484H
0485H
0486H
0487H
0488H
0489H
048AH
048BH
048CH
049EH
049FH
04A1H
04A2H
04A3H
04A4H
04A5H
04A6H
04A7H
04A8H
04A9H
04AAH
04ADH
04AEH
04AFH
04B1H
04B3H
04B5H
04B6H
04B7H
04B8H
04BBH
04BFH
Name
L1-01 Motor protection selection
L1-02 Motor protection time constant
L1-03 Alarm operation selection during motor overheating
L1-04 Motor overheating operation selection
L1-05 Motor temperature input filter time constant
L2-01 Momentary power loss detection
L2-02 Momentary power loss ridethru
L2-03 Min. baseblock time
L2-04 Voltage recovery time
L2-05 Undervoltage detection level
L2-06 KEB deceleration time
L2-07 Momentary recovery time
L2-08 Frequency reduction at KEB start
L3-01 Stall prevention selection during accel
L3-02 Stall prevention level during accel
L3-03 Stall prevention limit during accel
L3-04 Stall prevention selection during decel
L3-05 Stall prevention selection during running
L3-06 Stall prevention level during running
L4-01 Speed agreement detection level
L4-02 Speed agreement detection width
L4-03 Speed agreement detection level (+/-)
L4-04 Speed agreement detection width (+/-)
L4-05 Operation when frequency reference is missing
L5-01 Number of auto restart attempts
L5-02 Auto restart operation selection
L6-01 Torque detection selection 1
L6-02 Torque detection level 1
L6-03 Torque detection time 1
L6-04 Torque detection selection 2
L6-05 Torque detection level 2
L6-06 Torque detection time 2
L7-01 Forward drive torque limit
L7-02 Reverse drive torque limit
L7-03 Forward regenerative torque limit
L7-04 Reverse regenerative torque limit
L8-01 Protect selection for internal DB resistor (Type ERF)
L8-02 Overheat pre-alarm level
L8-03 Operation selection after overheat pre-alarm
L8-05 Input open-phase protection selection
L8-07 Output open-phase protection selection
L8-09 Ground protection selection
L8-10 Cooling fan control selection
L8-11 Cooling fan control delay time
L8-12 Ambient temperature
L8-15 OL2 characteristics selection at two speeds
L8-18 Soft CLA selection
49
Inverter
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
F7 G7
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
0580H
0581H
0584H
0585H
0586H
0588H
0589H
058AH
058BH
059AH
059BH
05A4H
05A5H
05B0H
05B1H
05B2H
0500H
0501H
0502H
0503H
0504H
0505H
0506H
0507H
0508H
0509H
050AH
050BH
050CH
050EH
0510H
0515H
0516H
0700H
0701H
0702H
0703H
0704H
0705H
0706H
0707H
0708H
Register No.
Consatnt
No.
Name
N1-01 Hunting-prevention function selection
N1-02 Hunting-prevention gain
N2-01 Speed feedback detection control (AFR) gain
N2-02 Speed feedback detection control (AFR) time constant
N2-03 Speed feedback detection control (AFR) time constant 2
N3-01 High-slip braking deceleration frequency width
N3-02 High-slip braking current limit
N3-03 High-slip braking stop dwell time
N3-04 High-slip braking oL time
N4-07 Integral time of speed estimator
N4-08 Proportional gain of speed estimator
N4-17 Torque adjustment gain
N4-18 Feeder resistance adjustment gain
N5-01 Feed forward control selection
N5-02 Motor acceleration time
N5-03 Feed forward proportional gain o1-01 Monitor selection o1-02 Monitor selection after power up o1-03 Frequency units of reference setting and monitor o1-04 Setting unit for frequency constants related to V/f characteristics o1-05 LCD brightness adjustment o2-01 LOCAL/REMOTE key enable/disable o2-02 STOP key during control circuit terminal operation o2-03 User constant initial value o2-04 kVA selection o2-05 Frequency reference setting method selection o2-06 Operation selection when digital operator is disconnected o2-07 Cumulative operation time setting o2-08 Cumulative operation time selection o2-10 Fan operation time setting o2-12 Fault trace/fault history clear function o3-01 Copy function selection o3-02 Read permitted selection
T1-00 Motor 1/2 selection
T1-01 Autotuning mode selection
T1-02 Motor output power
T1-03 Motor rated voltage
T1-04 Motor rated current
T1-05 Motor base frequency
T1-06 Number of motor poles
T1-07 Motor base speed
T1-08 PG pulses per revolution for teaching
Inverter
○
○
○
○
×
○
○
○
○
○
○
○
○
×
×
○
○
○
○
○
○
○
○
○
○
×
×
×
×
×
×
×
×
○
○
○
○
F7 G7
○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
50
8.1.6 Error Code
Error
Code
01H
02H
03H
21H
22H
23H
24H
Contents
Function code error
・ Function code from the master is any other than 03H and 10H.
Incorrect register No.
・ The register number to be accessed has not been registered.
・ Enter command "0900H" or "0910H" was read out although they were write-only registers.
Incorrect number of data items
・ The number of data items at write-in or read-out is not in the range from 2 to 8.
Data setting error
・ A simple upper/lower limit error occurred when writing control data or a constant.
・ A constant setting error occurred when writing a constant.
Write mode error
・ A constant was attempted to be written in from the master during running.
・ An Enter command was attempted to be written in from the master during running.
・ Any constant other than A1-00 to 05, E1-03 or o2-04 was attempted to be written in from the masterwhen"CPF03" occurred.
・ Read-only data was attempted to be written in from the master.
Write mode error during main circuit Undervoltage
・ A constant was attempted to be written in from the master during UV occurrence.
・ An Enter command was attempted to be written in from the master during UV occurrence.
Write mode error during constant processing
・ A constant was attempted to be written in from the master while the data was being stored.
51
Varispeed SERIES OPTION CARD
PROFIBUS-DP COMMUNICATIONS INTERFACE CARD
USER'S MANUAL
IRUMA BUSINESS CENTER
480, Kamifujisawa, Iruma, Saitama 358-8555, Japan
Phone 81-4-2962-5696 Fax 81-4-2962-6138
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone 1-847-887-7000 Fax 1-847-887-7370
MOTOMAN INC. HEADQUARTERS
805 Liberty Lane West Carrollton, OH 45449, U.S.A.
Phone 1-937-847-6200 Fax 1-937-847-6277
YASKAWA ELETRICO DO BRASIL COMERCIO LTD.A.
Avenida Fagundes Filho, 620 Bairro Saude-Sao Paulo-SP, Brazil CEP: 04304-000
Phone 55-11-5071-2552 Fax 55-11-5581-8795
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone 49-6196-569-300 Fax 49-6196-569-312
Motoman Robotics Europe AB
Box 504 S38525 Torsas, Sweden
Phone 46-486-48800 Fax 46-486-41410
Motoman Robotec GmbH
Kammerfeldstra βe 1, 85391 Allershausen, Germany
Phone 49-8166-90-100 Fax 49-8166-90-103
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, United Kingdom
Phone 44-1236-735000 Fax 44-1236-458182
YASKAWA ELECTRIC KOREA CORPORATION
Kfpa Bldg #1201, 35-4 Youido-dong, Yeongdungpo-Ku, Seoul 150-010, Korea
Phone 82-2-784-7844 Fax 82-2-784-8495
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, Singapore
Phone 65-6282-3003 Fax 65-6289-3003
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No.18 Xizang Zhong Road. Room 1805, Harbour Ring Plaza Shanghai 20000, China
Phone 86-21-5385-2200 Fax 86-21-5385-3299
YATEC ENGINEERING CORPORATION
4F., No.49 Wu Kong 6 Rd, Wu-Ku Industrial Park, Taipei, Taiwan
Phone 886-2-2298-3676 Fax 886-2-2298-3677
YASKAWA ELECTRIC (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone 852-2803-2385 Fax 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club, 21
Jianguomenwai Avenue, Beijing 100020, China
Phone 86-10-6532-1850 Fax 86-10-6532-1851
TAIPEI OFFICE
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
SHANGHAI YASKAWA-TONGJI M & E CO., LTD.
27 Hui He Road Shanghai China 200437
Phone 86-21-6553-6060 Fax 86-21-5588-1190
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing P.R. China Post Code: 100083
Phone 86-10-6233-2782 Fax 86-10-6232-1536
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic Technological Investment & Development Area,
Beijing 100076, P.R. China
Phone 86-10-6788-0551 Fax 86-10-6788-2878
YASKAWA ELECTRIC CORPORATION
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
©
2001-2004 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. SIBZ-C736-70.9B
Printed in Japan July 2004 01 8 2
04-1 ⑤
00-71011
Download
Advertisement
Key features
Connects Varispeed inverters to PROFIBUS-DP network
Monitors inverter status (running, stopping, etc.)
Reads and changes inverter constants
Supports high-speed I/O data transfer
Features MEMOBUS message area for advanced control
Includes handshaking functionality for data synchronization
Frequently asked questions
The SI-P1 card is an interface that connects Varispeed series inverters to a PROFIBUS-DP network, enabling communication and control.
The SI-P1 card supports both high-speed I/O data transfer and MEMOBUS messages. High-speed I/O data allows for immediate control of the inverter, while MEMOBUS messages enable access to and modification of the inverter constants.
The SI-P1 card uses a handshaking mechanism to synchronize the sending and receiving of MEMOBUS messages. This ensures that data is exchanged reliably between the inverter and the master.
Possible errors include power supply issues, communication errors, and CPU errors. The LED indicators on the SI-P1 card provide information about the specific error.