- Computers & electronics
- Computer components
- Interface components
- Serial converters/repeaters/isolators
- User manual
advertisement
Retrofit Instructions
P/N 3-9000-786, Rev A
April 2015
Daniel
™
Gas Ultrasonic 3410 Series Electronics
Retrofit Instructions
Daniel customer service
Location
North America/Latin America
Daniel Customer Service
USA (toll free)
Asia Pacific (Republic of Singapore)
Telephone number
+1.713.467.6000
+1.713.827.6314
+1.888.356.9001
+65.6777.8211
Europe (Stirling Scotland, UK)
Middle East Africa (Dubai, UAE)
+44 (0)1786.433400
+971 4 8118100
Daniel Measurement and Control, Inc. (Headquarters)
11100 Brittmoore Park Drive
Houston, TX 77041 USA
http://www.daniel.com
Fax number
+1.713.827.4805
+1.713.827.6312
+1.713.827.3380
+65.6777.0947.0743
+44 (0)1786.433401
+971 4 8865465
•
•
•
•
Customer Service: [email protected]
Customer Support: [email protected]
Asia-Pacific: [email protected]
Europe: [email protected]
Return Material Authorization (RMA)
A Return Material Authorization (RMA) number must be obtained prior to returning any equipment for any reason. Download the
RMA form from the Support Services web page by selecting the link below.
http://www2.emersonprocess.com/EN-US/BRANDS/DANIEL/SUPPORT-SERVICES/Pages/Support-Services.aspx
Signal words and symbols
Pay special attention to the following signal words, safety alert symbols and statements:
Safety alert symbol
This is a safety alert symbol. It is used to alert you to potential physical injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER!
Danger indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING!
Warning indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION!
Caution indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Notice is used to address safety messages or practices not related to personal injury.
Important
Important is a statement the user needs to know and consider.
Tip
Tip provides information or suggestions for improved efficiency or best results.
Note
Note is “general by-the-way” content not essential to the main flow of information.
Important safety instructions
Daniel Measurement and Control, Inc. (Daniel) designs, manufactures and tests products to function within specific conditions.
Because these products are sophisticated technical instruments, it is important that the owner and operation personnel must strictly adhere both to the information printed on the product and to all instructions provided in this manual prior to installation, operation, and maintenance.
Daniel also urges you to integrate this manual into your training and safety program.
BE SURE ALL PERSONNEL READ AND FOLLOW THE INSTRUCTIONS IN THIS MANUAL AND ALL NOTICES AND PRODUCT WARNINGS.
WARNING!
Failure to follow the installation, operation or maintenance instructions for a Daniel product could lead to serious injury or death from explosion or exposure to dangerous substances.
To reduce the risk:
•
•
•
Comply with all information on the product, in this manual, and in any local and national codes that apply to this product.
Do not allow untrained personnel to work with this product.
Use Daniel parts and work procedures specified in this manual.
Product owners (Purchasers):
•
•
•
•
•
•
•
•
Use the correct product for the environment and pressures present. See technical data or product specifications for limitations. If you are unsure, discuss your needs with your Daniel representative.
Inform and train all personnel in the proper installation, operation, and maintenance of this product.
To ensure safe and proper performance, only informed and trained personnel should install, operate, repair and maintain this product.
Verify that this is the correct instruction manual for your Daniel product. If this is not the correct documentation, contact
Daniel at 1-713-827-6314. You may also download the correct manual from:
http://www.Daniel.com
.
Save this instruction manual for future reference.
If you resell or transfer this product, it is your responsibility to forward this instruction manual along with the product to the new owner or transferee.
ALWAYS READ AND FOLLOW THE INSTALLATION, OPERATIONS, MAINTENANCE AND TROUBLESHOOTING MANUAL(S) AND
ALL PRODUCT WARNINGS AND INSTRUCTIONS.
Do not use this equipment for any purpose other than its intended service. This may result in property damage and/or serious personal injury or death.
Product operation (Personnel):
•
•
•
•
•
•
•
•
•
•
•
To prevent personal injury, personnel must follow all instructions of this manual prior to and during operation of the product.
Follow all warnings, cautions, and notices marked on, and supplied with, this product.
Verify that this is the correct instruction manual for your Daniel product. If this is not the correct documentation, contact
Daniel at 1-713-827-6314. You may also download the correct manual from:
http://www.daniel.com
.
Read and understand all instructions and operating procedures for this product.
If you do not understand an instruction, or do not feel comfortable following the instructions, contact your Daniel representative for clarification or assistance.
Install this product as specified in the INSTALLATION section of this manual per applicable local and national codes.
Follow all instructions during the installation, operation, and maintenance of this product.
Connect the product to the appropriate pressure and electrical sources when and where applicable.
Ensure that all connections to pressure and electrical sources are secure prior to and during equipment operation.
Use only replacement parts specified by Daniel. Unauthorized parts and procedures can affect this product's performance, safety, and invalidate the warranty. “Look-a-like” substitutions may result in deadly fire, explosion, release of toxic substances or improper operation.
Save this instruction manual for future reference.
Notice
THE CONTENTS OF THIS PUBLICATION ARE PRESENTED FOR INFORMATIONAL PURPOSES ONLY, AND WHILE EVERY EFFORT HAS
BEEN MADE TO ENSURE THEIR ACCURACY, THEY ARE NOT TO BE CONSTRUED AS WARRANTIES OR GUARANTEES, EXPRESSED OR
IMPLIED, REGARDING THE PRODUCTS OR SERVICES DESCRIBED HEREIN OR THEIR USE OR APPLICABILITY. ALL SALES ARE GOVERNED
BY DANIEL'S TERMS AND CONDITIONS, WHICH ARE AVAILABLE UPON REQUEST. WE RESERVE THE RIGHT TO MODIFY OR IMPROVE
THE DESIGNS OR SPECIFICATIONS OF SUCH PRODUCTS AT ANY TIME.
DANIEL DOES NOT ASSUME RESPONSIBILITY FOR THE SELECTION, USE OR MAINTENANCE OF ANY PRODUCT. RESPONSIBILITY FOR
PROPER SELECTION, USE AND MAINTENANCE OF ANY DANIEL PRODUCT REMAINS SOLELY WITH THE PURCHASER AND END-USER.
TO THE BEST OF DANIEL'S KNOWLEDGE THE INFORMATION HEREIN IS COMPLETE AND ACCURATE. DANIEL MAKES NO
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE WITH RESPECT TO THIS MANUAL AND, IN NO EVENT, SHALL DANIEL BE LIABLE FOR ANY INCIDENTAL,
PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF PRODUCTION, LOSS OF PROFITS,
LOSS OF REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS
OF THIRD PARTIES.
PRODUCT NAMES USED HEREIN ARE FOR MANUFACTURER OR SUPPLIER IDENTIFICATION ONLY AND MAY BE TRADEMARKS/
REGISTERED TRADEMARKS OF THESE COMPANIES.
Warranty and Limitations
1. LIMITED WARRANTY: Subject to the limitations contained in Section 2 herein, Daniel Measurement & Control, Inc. (“Daniel”) warrants that the licensed firmware embodied in the Goods will execute the programming instructions provided by Daniel, and that the Goods manufactured by Daniel will be free from defects in materials or workmanship under normal use and care and Services will be performed by trained personnel using proper equipment and instrumentation for the particular Service provided. The foregoing warranties will apply until the expiration of the applicable warranty period. Goods are warranted for twelve (12) months from the date of initial installation or eighteen (18) months from the date of shipment by Daniel, whichever period expires first.
Consumables and Services are warranted for a period of 90 days from the date of shipment or completion of the Services. Products purchased by Daniel from a third party for resale to Buyer (“Resale Products”) shall carry only the warranty extended by the original manufacturer. Buyer agrees that Daniel has no liability for Resale Products beyond making a reasonable commercial effort to arrange for procurement and shipping of the Resale Products. If Buyer discovers any warranty defects and notifies Daniel thereof in writing during the applicable warranty period, Daniel shall, at its option, correct any errors that are found by Daniel in the firmware or Services or repair or replace F.O.B. point of manufacture that portion of the Goods or firmware found by Daniel to be defective, or refund the purchase price of the defective portion of the Goods/Services. All replacements or repairs necessitated by inadequate maintenance, normal wear and usage, unsuitable power sources or environmental conditions, accident, misuse, improper installation, modification, repair, use of unauthorized replacement parts, storage or handling, or any other cause not the fault of
Daniel are not covered by this limited warranty, and shall be at Buyer's expense. Daniel shall not be obligated to pay any costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by Daniel. All costs of dismantling, reinstallation and freight and the time and expenses of Daniel's personnel and representatives for site travel and diagnosis under this warranty clause shall be borne by Buyer unless accepted in writing by Daniel. Goods repaired and parts replaced by Daniel during the warranty period shall be in warranty for the remainder of the original warranty period or ninety (90) days, whichever is longer. This limited warranty is the only warranty made by Daniel and can be amended only in a writing signed by Daniel. THE
WARRANTIES AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE. THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY
KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPECT
TO ANY OF THE GOODS OR SERVICES. Buyer acknowledges and agrees that corrosion or erosion of materials is not covered by this warranty.
2. LIMITATION OF REMEDY AND LIABILITY: Daniel shall not be liable for damages caused by delay in performance. The remedies of
Buyer set forth in this agreement are exclusive. In no event, regardless of the form of the claim or cause of action (whether based in contract, infringement, negligence, strict liability, other tort or otherwise), shall Daniel's liability to Buyer and/or its customers exceed the price to Buyer of the specific goods manufactured or services provided by Daniel giving rise to the claim or cause of action. Buyer agrees that in no event shall Daniel's liability to Buyer and/or its customers extend to include incidental, consequential or punitive damages. The term “consequential damages” shall include, but not be limited to, loss of anticipated profits, revenue or use and costs incurred including without limitation for capital, fuel and power, and claims of Buyer's customers.
Contents
Contents
Part I Plan
Part II Install
Part III Operate
Appendices and reference
Daniel ™ Gas Ultrasonic 3410 Series Electronics
i
Contents
ii
Retrofit Instructions
Part I
Plan
Chapters covered in this part:
•
Introduction
•
Before you begin
•
Before removing the Electronics
•
Removing Mark III Electronics
Plan
Daniel ™ Gas Ultrasonic 3410 Series Electronics
1
Plan
2
Retrofit Instructions
1
1.1
Introduction
Introduction
General
Welcome to the Daniel 3410 Series Ultrasonic Retrofit Instruction Manual.
This manual has been designed to provide you with a step-by-step set of instructions for retrofitting a meter with Mark III electronics to the new 3410 Series electronics.
NOTICE
Please read the “Before You Begin” section to make sure you have all the components necessary to perform the retrofit before taking the meter out of service.
Important
If retrofitting from Mark II electronics to 3410 Series electronics complete Sections 3 and 4 in the
Daniel Ultrasonic Mark III Upgrade Kit Instructions P/N 3-9000-746 to determine the communications and output settings of the Mark II electronics. Use those settings and the instructions in this manual to configure the Series electronics.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
3
Introduction
4
Retrofit Instructions
2
2.1
Before you begin
Before you begin
This section shows all of the parts and tools required to perform the upgrade. Ensure that all of these items are available before taking the meter out of service.
Tools required
Figure 2-1: Required tools
E.
F.
G.
A.
B.
C.
D.
1/8" flat-blade screw driver
¼ " flat-blade screw driver
3/8" drive ratchet wrench
3/8" drive - extension - at least 3.5" long
3/8" drive - 7/16" socket
Allen wrench - size 6mm Daniel P/N 2-4-9200-501(included in Retrofit kit)
Crescent wrench for cable glands and electrical conduit
Daniel ™ Gas Ultrasonic 3410 Series Electronics
5
Before you begin
Daniel MeterLink
™
is required to communicate with the meter electronics, access information and collect the configuration in the meter and then convert and download the configuration into the new 3410 Series electronics. Always use the latest version of Daniel
MeterLink
™
. Upgrades to the latest version are available at:
http://www2.emersonprocess.com/en-US/brands/daniel/Flow/ultrasonics/Pages/
MeterLink.aspx
6
Retrofit Instructions
3
3.1
Before removing the Electronics
Before removing the Electronics
Procedure before removing the Mark III
Electronics
1.
Before removing power from the meter being retrofitted, use the Daniel MeterLink
™ software to connect to the meter.
2.
Use the Edit/Compare Configuration screen in Daniel MeterLink
™
to read the configuration from the meter and save it to a file on your computer. An example for a file name might be "“Meter Name, MkIII Final Config, 3-4-2013 10-15-02 AM.cfg”.
Daniel MeterLink
™
will be used later in this procedure (see
) to convert the
configuration and download it to the 3410 Series electronics. See
.
CAUTION!
LOSS OF SET-UP DATA
The current meter configuration file must be saved before beginning the 3410 Series electronics retrofit.
Failure to save the current configuration file can result in the loss of important set-up data.
9
provide more detailed instructions on obtaining the required information with respect to the communications set-up of the electronics, however, if these settings are already known, these steps can be skipped.
Step 9
is for
Frequency and Diagnostic outputs. For reference, the known values should be
entered in the Summary Table of Communication/Output Settings in
This information will be required in the setup of the Series electronics. For any setting which is not known, the applicable step(s) for obtaining that information can be used.
3.
Use the
File|Meter Directory
menu path, then select the <meter name> you want to retrofit.
a. Click the
Direct
button on the lower left corner of the Meter Directory dialog box.
b. The
Direct Connection Properties For
dialog appears.
c. Obtain the Modbus ID (same as Comms Address).
Daniel ™ Gas Ultrasonic 3410 Series Electronics
7
Before removing the Electronics
Figure 3-1: Accessing Modbus ID for Ports A and B
8
4.
Based on the information contained in the connection properties window, enter the values for the following parameters in the Summary Table of Communication/
Output Settings in
:
Port A and B: Modbus ID = _____(enter Comms Address).
5.
Exit Daniel MeterLink
™
and disconnect your PC from the meter electronics. The remaining information required before doing the retrofit upgrade, is based on the wiring terminations and the settings of various switches on the boards that comprise the electronics.
6.
Power down the electronics.
CAUTION!
EQUIPMENT DAMAGE
Remove power from the meter electronics.
Failure to remove power from the meter electronics may result in damage to the equipment.
7.
Remove the end caps from the upper electronics housing of the meter to access the electronic circuit boards. See
for board layout of the 3400 stacks. See
for the 3410 Series electronics for board layout.
Retrofit Instructions
Before removing the Electronics
Figure 3-2: Remove end caps from the upper electronics enclosure
Figure 3-3: 3400 Electronics Assembly board layout
Daniel ™ Gas Ultrasonic 3410 Series Electronics
9
Before removing the Electronics
Figure 3-4: 3410 Retrofit electronics assembly
10
A. End cap and security screw
B. O-ring
C. Desiccant packet
D. CPU Module
E. Optional RS-232 I/O Module
F. Optional RS-485 I/O Module
G. Blanking cover
H. Guide plate
I. M20 reducer
J. Ground lug - external
K. Transmitter electronics enclosure
L. Power supply
M. I.S. Barrier board
N. Standoffs
O. Backplane board
P. O-ring
Q. End cap and security screw
R. O-ring
S. Acquisition cable and roll pin
T. Acquisition Module assembly
U. Base enclosure
V. Cable glands
W. Gasket, base enclosure
X. Acquisition cable clamp
Y. Acquisition Module
Retrofit Instructions
Before removing the Electronics
8.
Remove the Mark III electronics CPU board, the HART Option Board, and the Field
Termination Board from the enclosure. Fill out the Summary Table of
Communication/Output Settings in
based on the Field Connection Board
wire terminations and/or switch settings of the CPU board and Option Board, if installed. This information will be used to configure the new 3410 Series electronics later in this procedure.
Figure 3-5: Mark III CPU Board showing switch settings
Daniel ™ Gas Ultrasonic 3410 Series Electronics
11
Before removing the Electronics
Figure 3-6: Mark III CPU Board with I.S. Barrier Board piggy-backed on CPU
Board
12
Retrofit Instructions
4
4.1
Removing Mark III Electronics
Removing Mark III Electronics
Procedure to remove the Mark III Electronics
1.
Having obtained all the information related to the set-up of the 3400 Series electronics configuration and communications, all the components related to the electronics can now be physically removed from the meter. Unscrew all wiring from the Field Termination Board. It may be helpful to label the wires to make it easier to connect the 3410 Series electronics.
2.
Remove any conduit and wiring attached to all six conduit ports.
3.
Remove any ground wire attached to the ground lug on the outside of the upper electronics housing. At this point there should be no wires connected to the upper electronics housing.
Figure 4-1: Ground wire removed
4.
Use the 6mm Allen wrench (supplied with upgraderetrofit kit) to remove the two bolts holding the base enclosure.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
13
Removing Mark III Electronics
Figure 4-2: Remove bolts from base enclosure cover
5.
Remove the upper electronics housing from the base enclosure.
a. Remove the Acquisition cable, which comes down from the upper electronics to the Acquisition module in the base enclosure.
NOTICE
shows the Acquisition module for the 3400 Series electronics.
b. Loosen the two screws on the ends of the Acquisition cable connector, and disconnect it from the Acquisition module.
c. Set the upper electronics housing aside once the housing is removed.
Figure 4-3: Remove the Acquisition cable
14
Retrofit Instructions
Removing Mark III Electronics
6.
Remove all the screws that hold the transducer wires in the terminal blocks that attach the transducers to the Acquisition module.
a. Remove the screws from the ends of the two connectors.
b. Disconnect the connectors and remove each of the transducer wires from the connector.
7.
Loosen the cable glands on the base enclosure and pull all of the transducer cables out of the base enclosure.
8.
Unscrew the three screws holding the Acquisition module in the base enclosure and remove the Acquisition module.
The four mounting bolts holding the enclosure cover to the meter body are sealed with an RTV silicone adhesive/sealant.
9.
Remove the RTV with a flat blade screwdriver or utility knife around the perimeter of the recessed opening and the RTV eases the removal of the sealant.
a. Use the 7/16" socket wrench to remove the four mounting bolts.
Figure 4-4: Remove old RTV
10.
Remove the base enclosure from the meter body.
11.
If RTV silicone adhesive/sealant was used to seal the base enclosure to the meter body, remove the adhesive/sealant so the 3410 base enclosure will have a clean mounting surface.
The 3400 Series electronics should be completely removed from the meter body at this time.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
15
Removing Mark III Electronics
16
Retrofit Instructions
Part II
Install
Install
Daniel ™ Gas Ultrasonic 3410 Series Electronics
17
Install
18
Retrofit Instructions
5
5.1
Installing the Series Electronics
Installing the Series Electronics
Procedure to install the 3410 Series Electronics
1.
Remove the 3410 components from the packaging.
a. Use the 6 mm Allen wrench to remove the two screws from the base enclosure cover.
Figure 5-1: Remove bolts from Base enclosure cover
2.
Lift the upper electronics housing from the base enclosure. The acquisition cable connector from the upper electronics is attached to the acquisition module with two screws. The cable is also secured by a cable clamp to a mounting bolt.
a. Remove the screw securing the cable clamp and then loosen the two screws on the acquisition cable connector and disconnect the acquisition cable connector from the acquisition module.
Figure 5-2: Remove acquisition cable and module
Daniel ™ Gas Ultrasonic 3410 Series Electronics
19
Installing the Series Electronics
3.
Unscrew the remaining two mounting screws from the acquisition module in the base enclosure and remove the acquisition board.
4.
Place an insulating gasket on the meter body where the electronics will be mounted
5.
Place the base enclosure on top of the meter body on top of the insulating gasket.
Note that the transducer port openings on the base enclosure are labeled with transducer locations (i.e., A1, A2, B1, B2, C1, C2, D1, D2).
a. Orient the base so that the A1 transducer port is closest to the A1 transducer location on the meter body. The meter body has the transducer location labels embossed in the body next to each transducer boss. The ports on the base enclosure must be oriented outward (towards the sides of the meter body, perpendicular to meter axis).
Figure 5-3: Base enclosure orientation
6.
Use the four ¼ " bolts with stainless steel washers and nylon shoulder washers to secure the base enclosure to the meter body.
a. Use a nut driver to tighten the bolts to a torque of 55 to 65 inch-lbs.
Figure 5-4: Insert 1/4" bolts
20
7.
Fill up the base enclosure wells with RTV adhesive/sealant around and over the four
¼ " bolts.
Retrofit Instructions
Installing the Series Electronics
This will ensure a water-tight seal. Any excess sealant can be removed by using a scraper to leave the sealant flush with the top of the well. Excess sealant will adhere to the acquisition board when it is installed, and make future removal of the board difficult.
Figure 5-5: Apply RTV sealant around bolts
8.
Insert the Acquisition board in the base enclosure and secure it with the two screws as shown for now.
Figure 5-6: Acquisition Module attachment screws
Daniel ™ Gas Ultrasonic 3410 Series Electronics
21
Installing the Series Electronics
Figure 5-7: Acquisition Module wiring
9.
Route the transducer cables through the cable glands with the correct label number
(i.e. A1) which matches the label on the transducer cable.
Figure 5-8: Base enclosure cable glands installation
22
10.
Judge the proper length and cut off the excess.
11.
Strip the outer insulation, outer shield, and inner insulation using a utility knife, refer to
for proper lengths. Verify that insulation of individual wires was not cut
while removing outer layers. Strip each wire 0.28".
Retrofit Instructions
Figure 5-9: Transducer Cable Cut Instructions
Installing the Series Electronics
12.
Insert tubing over wires, inner insulation and under shield approximately 1.5" of shield should overlap.
13.
Insert and secure transducer cables through cable glands verify Line Mark is as referenced in
Figure 5-10: Line mark
14.
Using a torque screwdriver set to 34 ±2 oz. in., secure the wires to the terminal plugs of the Acquisition Module.
15.
Verify the cable lengths are still an appropriate length and if necessary, cut the transducer cables to the correct length with allowance for the wiring terminations and connector placement.
16.
Ensure that the contacts clamp on the bare wires and not on the wire insulation when the wires are being terminated on the connector.
a. Leave the connector plugged into the Acquisition board while terminating the individual wires.
b. Tighten the connector screws on the either end of the connector after terminating all the wires on the applicable connector.
c. Repeat this procedure for the transducer cables on the other side of the meter.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
23
Installing the Series Electronics
Figure 5-11: Install cable and secure wires
24
17.
Use the cable ties to dress the transducer cables. They should be dressed in groups of two: A1 and C1, D1 and B1, A2 and C2, D2 and B2. Install one cable tie at three inches from the base enclosure and another about the point where the cables start to bend and separate out to their respective port.
Retrofit Instructions
Figure 5-12: Re-oriented and secured transducer cables
Installing the Series Electronics
18.
Reconnect the acquisition cable connector to the acquisition module and secure the cable connector by tightening the two screws.
19.
Install the cable clamp on the Acquisition cable and secure it with the final mounting screw for the Acquisition module.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
25
Installing the Series Electronics
Figure 5-13: Installing the Acquisition Module cable clamp
26
A. Acquisition cable connector
B. Acquisition cable
C. Cable clamp and screw
20.
Wrap the excess cable around the Acquisition Module and place the electronics housing into position on the base enclosure.
21.
Ensure the O-ring on the base of the upper enclosure is properly seated. Position the upper enclosure housing so that it is in the desired orientation for reattaching the electrical conduit.
22.
Install the 3410 meter upper enclosure on the base enclosure once the transducers are wired correctly.
23.
Install the two screws with the 6 mm Allen wrench to secure the upper enclosure to the base enclosure.
Retrofit Instructions
Figure 5-14: Bolt the upper enclosure to base enclosure
Installing the Series Electronics
24.
Remove the end cap next to the conduit entries from the upper enclosure.
shows the layout of the electronics.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
27
Installing the Series Electronics
Figure 5-15: 3410 Series electronics layout
28
A. End cap and security screw
B. O-ring
C. Desiccant packet
D. CPU Module
E. Optional RS-232 I/O Module
F. Optional RS-485 I/O Module
G. Blanking cover
H. Guide plate
I. M20 reducer
J. Ground lug - external
K. Transmitter electronics enclosure
L. Power supply
M. I.S. Barrier board
N. Standoffs
O. Backplane board
P. O-ring
Q. End cap and security screw
R. O-ring
S. Acquisition cable and roll pin
T. Acquisition Module assembly
U. Base enclosure
V. Cable glands
W. Gasket, base enclosure
X. Acquisition cable clamp
Y. Acquisition Module
The following table shows the default communications and output settings for the
3410 electronics and configuration.
Retrofit Instructions
Installing the Series Electronics
Table 5-1: 3410 Series default communications and output settings
Communication/Output
Type
Serial Port A
Frequency/Digital Output 1
Frequency/Digital Output 2
Frequency/Digital Output 3
Default Setting
Modbus ID = 32
Configured to output Frequency 1A
Configured to output Frequency 2A
Configured to output Digital
Output 1A
Default Setting
Baud Rate = 19200
Drive Mode=Open
Collector
Drive Mode=Open collector
Drive Mode=Open
Collector
Note
Port B and Port C are available if Optional RS-232 and
RS- 485 I/O Modules are installed.
Frequency Output 1A is configured for Uncorrected forward flow
Frequency Output 2A is configured for Uncorrected forward flow
Digital Output 1A is configured for Validity status
If the settings above are not consistent with those used in your meter, then these parameters can be changed using Daniel MeterLink
™
software to reconfigure the
communication ports and output ports later in this procedure.
of this document contains additional details with respect to the wiring related to the communications and discrete output signals.
NOTICE
Daniel MeterLink
™
cannot communicate with 3410 meters over a half-duplex serial connection. As a result, for Daniel MeterLink to communicate via a serial connection, that port on the 3410 electronics must be set for RS-232-Full Duplex, or RS-485-Full
Duplex (requires 4 conductor cables).
25.
Check the CPU Module switches on the to ensure they are set properly.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
29
Installing the Series Electronics
Figure 5-16: CPU switch settings
30
A. WRITE PROT. switch
B. DHCP switch
C. Port A (override)
The DHCP switch enables or disables the DHCP server for Ethernet communication.
The WRITE PROT. switch enables or disables “write protection” of the meter configuration.
Set the DHCP switch to the
ON
position to enable Ethernet communication via the
DHCP server. Set the WRITE PROT. switch to the
OFF
position to allow configuration parameters to be written to the meter. Only enable the DHCP server if the meter is not connected to a network that may have a DHCP server already running. The
DHCP server is designed for use when a PC connects directly to the meter and requires the meter to assign the PC an IP address.
26.
Wire all of the electrical connections.
Retrofit Instructions
Installing the Series Electronics
Figure 5-17: Install wiring terminal block connectors to the CPU Module
(shown with Optional I/O Modules)
A. CPU lower terminal block
B. CPU upper terminal block and switches
C. CPU Module
D. 24 VDC loop power
E. Optional RS-232 I/O Module
F. 10.4 - 36 VDC power
G. Fuse
H. Optional RS-485 I/O Module
I. Ethernet terminal block
J. Chassis ground
Daniel ™ Gas Ultrasonic 3410 Series Electronics
31
Installing the Series Electronics
Figure 5-18: Install wiring terminal block connectors to the CPU Module
(shown without Optional I/O Modules)
32
A. CPU lower terminal block
B. CPU upper terminal block and switches
C. CPU Module
D. 24 VDC loop power
E. 10.4 - 36 VDC power
F. Guide plate blanking cover
G. Fuse
H. Guide plate blanking cover
I. Guide plate blanking cover
All of the terminations removed from the modules in the 3410 Series electronics are made with quick disconnect terminal block connectors. This makes it easier to
terminate the wires prior to plugging them into the modules.
document also includes wiring tables and illustrations for each of the connectors in
the electronics. Refer to the System Wiring Drawing in
Retrofit Instructions
Installing the Series Electronics
27.
Install a ground wire to the ground lug on the side of the upper enclosure.
Figure 5-19: Transmitter electronics enclosure ground wire
28.
Attach flex conduit to the conduit ports on the transmitter electronics enclosure.
Before applying power to the meter, ensure the atmosphere is proven safe using an intrinsically safe gas detector.
WARNING!
EXPLOSION HAZARD
Do not apply power to the meter with the end caps removed unless you are in a nonhazardous or explosive-free environment.
Failure to comply could result in death, serious injury and possible equipment damage.
29.
Apply the sealing compound to the conduit seal fittings and allow to set in accordance with manufacturer specifications.
30.
Apply electrical power to the system and verify the field connections are working correctly.
31.
Do not install end caps until you configure the meter.
This completes the installation of the hardware associated with the 3410 Series
Electronics meter retrofit procedure.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
33
Installing the Series Electronics
34
Retrofit Instructions
Part III
Operate
Operate
Daniel ™ Gas Ultrasonic 3410 Series Electronics
35
Operate
36
Retrofit Instructions
Configure the 3410 Series Electronics
6
6.1
6.1.1
6.1.2
Configure the 3410 Series Electronics
Topics covered in this chapter:
•
Initial communication connection using Ethernet
•
Initial communication connection using RS-232 Serial
•
Write the converted configuration file to the meter
•
Configure the meter using the Field Setup Wizard
1.
Check all settings and wiring carefully.
2.
Set up the Meter Directory, and start initial communication with the 3410 Series electronics.
The basic instructions for setting up the directory and initializing communications are contained in the following text. Refer to the 3410 Series Gas Ultrasonic Flow Meter
Installation Manual (P/N 3-9000-759, Section 4) for more detailed instructions. Use Daniel
MeterLink v1.10 or later to make a connection to the meter.
Initial communication connection using
Ethernet
Ethernet initial connection material checklist
The following materials and information are required:
•
•
•
3410 Ethernet adapter cable (Daniel P/N 1-360-01-596)
Personal computer (PC) configured as follows:
Daniel MeterLink software installed (version 1.10 or later)
Ethernet LAN adapter
Configured to automatically obtain IP address (via DHCP)
Desired 3410 Series meter(s) communication configuration parameters:
IP address
Serial communication parameters such as baud rate and Modbus ID (if desired)
Ethernet initial connection steps
1.
Power up the 3410 Series meter and wait two minutes for the meter to startup.
2.
Ensure that the Ethernet DHCP server is enabled on the 3410 CPU Module by setting
DHCP switch to the
ON
position.
3.
Plug the Ethernet adapter cable (P/N 1-360-01-596) into the meter CPU Module and connect the RJ45 end into the PC Ethernet connector.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
37
Configure the 3410 Series Electronics
6.2
6.2.1
4.
Verify the Ethernet connection status by the 3410 CPU Module
LINK
LED which should be solid green.
5.
Start Daniel MeterLink
™
on the PC. The
Connect to Meter
dialog displays.
a. Click the Edit Meter Directory button.
b. Click the
Add
button (below the
Meter Directory
file operations field). Daniel
MeterLink inserts the
New Meter
record in the last field in the
Meter Directory
table.
6.
Create a new meter directory record with the following parameters: a. Enter a name for the meter.
b. Select Meter Type as Gas or Liquid as appropriate.
c. Check the Ethernet box and uncheck the Direct and Modem boxes.
d. Set the Ethernet IP address to 192.168.135.100.
e. Close the Meter Directory window.
7.
Use the
Meter|Connect
menu path and click the
Ethernet connection for the meter record established in the previous step. Daniel MeterLink meter using the user-specified Ethernet settings.
™
will now connect to the
Initial communication connection using RS-232
Serial
Communications settings and Field Setup Wizard
RS-232 Serial initial connection material checklist
The following materials and information are required:
•
•
Ultrasonic serial cable (Daniel P/N 3-2500-401).
Personal computer (PC) with Daniel MeterLink
™
software version 1.10 (or later)
• Desired 3410 meter(s) communication configuration parameters:
IP address (if desired)
Serial communication parameters such as baud rate and Modbus ID
RS-232 Serial initial connection steps
1.
Power up the 3410 meter and PC.
2.
Plug the DB-9 end of the cable directly into the PC running Daniel MeterLink. The three wires on the other end of the cable connect to RX, TX, and COM terminals on the CPU Module. The Digital Out wire goes to RX, the Digital In wire goes to TX, and the COMMON wire goes to COM.
38
Retrofit Instructions
Figure 6-1: CPU RS-232 serial connection
Configure the 3410 Series Electronics
Table 6-1: CPU RS-232/RS-485 wire colors
CPU
R X
T X
C O M
Wire colors
Red
White
Black
3.
Start Daniel MeterLink
™ following parameters:
on the PC and create a new Meter Directory record with the
Daniel ™ Gas Ultrasonic 3410 Series Electronics
39
Configure the 3410 Series Electronics
40 a. Enter a name.
b. Select
Meter Type
as Gas or Liquid as appropriate.
c. Check the
Direct
box and uncheck the Modem and Ethernet boxes.
d. Set the Direct connection properties for Baud Rate of 19200 and Comms Address
(Modbus ID) of 32.
Retrofit Instructions
Configure the 3410 Series Electronics
4.
Use the
Meter|Connect
menu path and click
Direct
connection for the meter record established above. Daniel MeterLink
™
will now connect to the meter using the userspecified serial communication settings.
Follow the instructions in
to write the converted configuration file to the meter.
Meter Communications Settings
1.
Use the Meter|Communications Settings menu path to access the Communications dialog.
This dialog displays the communications parameters for the 3410 Series electronics and is used to adjust the Baud Rate and Comms Address (i.e. Modbus ID) for the serial ports.
Figure 6-2: Communications Settings dialog
Daniel ™ Gas Ultrasonic 3410 Series Electronics
41
Configure the 3410 Series Electronics
2.
Use the
Driver selection
pull-down menu if communication settings require RS-485
Figure 6-3: Change driver selection for RS-485 half duplex or full duplex communication
6.3
6.3.1
42
Write the converted configuration file to the meter
Write the converted configuration file to the meter
1.
With communication to the meter established, use the Tools|Edit/Compare Configuration menu path to access the Edit/Compare Configuration dialog.
2.
Click Open and the Open Configuration File dialog displays.
Retrofit Instructions
Figure 6-4: Edit/Compare configuration dialog
Configure the 3410 Series Electronics a. Select the final configuration file created in
(i.e., “Meter Name, MKIII Final Config, 3-4-2005 10-15-02 AM.cfg”).
b. Click Open . The file opens and you returned to the Edit/Compare Configuration dialog.
Figure 6-5: Open configuration file dialog
c. Click Convert
). Daniel MeterLink
™
reads the 3410 configuration from the meter and modifies it with the 3400 configuration.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
43
Configure the 3410 Series Electronics
Figure 6-6: Edit/Compare configuration dialog with active Convert button
If the meter supports HART, check the 2nd variable parameter setting using the
Field Setup Wizard|Current Outputs dialog. A reminder dialog prompts you to set this parameter.
Figure 6-7: Hart parameter settings
44
For Gas ultrasonic meters, the HART Secondary Variable options are:
• Uncorrected flow rate
• Corrected flow rate
• Average flow velocity
• Average sound velocity
• Energy flow rate
• Mass flow rate
All data points shown in yellow have been modified from the 3400 configuration.
Retrofit Instructions
Configure the 3410 Series Electronics
Figure 6-8: Converted configuration with highlighted changes
d. Click
Write Checked
to write the converted configuration to the meter (see
). If an error occurs, Daniel MeterLink
™
will display a message indicating the nature of the problem. Manually edit the parameter(s) with errors to successfully complete the download.
e. Click
Write Checked
again after modifying the parameter(s). Repeat this until the write occurs with no errors.
f.
Save the 3400 Series electronics configuration file to your PC.
g. With the converted configuration still displayed, from the Edit/Compare
Configuration dialog, click the
Meter
radio button, located next to the
Compare
button (see
h. Compare the file to verify that this saved configuration matches the meter configuration. If an error occurs, go back to the beginning of the
RS-232 Serial initial connection steps
and try again until no errors are reported.
3.
Use the Meter|Monitor menu path to display the Monitor window and verify that the meter is operating correctly.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
45
Configure the 3410 Series Electronics
Figure 6-9: Meter monitor dialog
6.4
6.4.1
Configure the meter using the Field Setup
Wizard
Configure the meter using the Field Setup Wizard
1.
Use the
Meter|Field Setup Wizard
menu path to access the
Field Setup Wizard Startup dialog.
a. Verify that all settings (options) are correct (e.g., temperature, pressure, meter connections and meter outputs).
b. In the Meter name field insert a name for the meter (this name displays on Daniel
MeterLink
™
main window and the Maintenance logs and Reports files).
c. Ensure the 3410 Series Electronics digital outputs are configured appropriately.
The 3410 Series Electronics also supports, and may be configured for, the AGA8
Detailed Method.
46
Retrofit Instructions
Figure 6-10: Field Setup Wizard Startup dialog
Configure the 3410 Series Electronics
2.
Setup the Frequency and Digital Output Sources parameters from the Field Setup
Wizard Frequency/Digital Outputs Sources Page.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
47
Configure the 3410 Series Electronics
Figure 6-11: Field Setup Wizard Frequency and Digital Output Sources page
48
The meter has user-configurable selections for either a frequency output or digital status (FODO). Use the pull-down menus to edit these parameters.
(3) Frequency/Digital Outputs:
• FODO1 (four possible output configurations)
• FODO2(eight possible output configurations)
• FODO3(eight possible output configurations)
Frequency or Digital Outputs (FODO 1) source selections:
• FO1A, DO1A, FO1B, DO1B
Frequency or Digital Outputs (FODO 2) source selections:
• FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B
Frequency or Digital Outputs (FODO 3) source selections:
• FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B
Mode options:
• Open Collector (requires external excitation supply voltage and pull-up resistor)
• TTL (internally powered by the meter 0-5 VDC signal)
Channel B Phase options:
Retrofit Instructions
Configure the 3410 Series Electronics
• Lag forward, Lead reverse (Phase B lags Phase A while reporting forward flow, leads Phase A while reporting reverse flow)
• Lead forward, Lag reverse (Phase B leads Phase A while reporting forward flow, lags Phase A while reporting reverse flow)
Phase A and Phase B output (based on flow direction):
• Reverse flow - output only reports flow in the reverse direction. For frequency outputs, Phase B of the output is 90 degrees out of phase with Phase A.
• Forward flow - output only reports flow in the forward direction. For frequency outputs, Phase B of the output is 90 degrees out of phase with Phase A.
• Absolute - output reports flow in both directions. For frequency outputs, Phase B of the output is 90 degrees out of phase with Phase A.
• Bidirectional - output reports flow on Phase A only in the forward direction and on Phase B only in the reverse direction.
Maximum frequency for the frequency outputs:
• 1000 Hz
• 5000Hz
3.
If changes were made in the
Field Setup Wizard
, choose to save the configuration when Daniel MeterLink
™
prompts you after the changes are written to the meter.
Click
Finish
in the
Field Setup Wizard
dialog to write any changes to the meter.
4.
You have successfully completed upgrading your3400 electronics to 3410 Series electronics.
5.
Save your configuration file for the meter's parameters you just set as the “As Left
Settings”.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
49
Configure the 3410 Series Electronics
50
Retrofit Instructions
Mark III RS-232 and RS-485 Serial communications setup
Appendix A
Mark III RS-232 and RS-485 Serial communications setup
Topics covered in this appendix:
•
Mark III RS-232 Full Duplex
•
Mark III RS-485 Half Duplex
•
Mark III Discrete output switch settings
•
Mark III RS-232 Full Duplex
•
Mark III RS-485 Half Duplex
•
Mark III Series 100 option board (if installed)
•
Mark III RS-232 Full Duplex
•
Mark III RS-485 Half Duplex
•
Mark III Series 100 plus HART option board (if installed)
A.1
Mark III RS-232 Full Duplex
Figure A-1: Port A settings
Daniel ™ Gas Ultrasonic 3410 Series Electronics
51
Mark III RS-232 and RS-485 Serial communications setup
Figure A-2: Port B settings
A.2
Mark III RS-485 Half Duplex
Figure A-3: Port A settings (Factory default switch settings for Port A)
Figure A-4: Port B settings
52
Retrofit Instructions
A.3
Mark III RS-232 and RS-485 Serial communications setup
Mark III Discrete output switch settings
Figure A-5: Group 1 Frequency and digital outputs
Figure A-6: Group 2 Frequency and digital outputs
Daniel ™ Gas Ultrasonic 3410 Series Electronics
53
Mark III RS-232 and RS-485 Serial communications setup
Figure A-7: Series 100 option board (if installed)
A.4
Mark III RS-232 Full Duplex
Figure A-8: Port C settings
54
Retrofit Instructions
A.5
Mark III RS-232 and RS-485 Serial communications setup
Mark III RS-485 Half Duplex
Figure A-9: Port C settings
A.6
Mark III Series 100 option board (if installed)
Figure A-10: Analog output 1
Figure A-11: Analog input 1 (Temperature)
Daniel ™ Gas Ultrasonic 3410 Series Electronics
55
Mark III RS-232 and RS-485 Serial communications setup
Figure A-12: Analog input 2 (Pressure)
Figure A-13: Series 100 Plus HART option board (if installed)
56
Retrofit Instructions
A.7
Mark III RS-232 and RS-485 Serial communications setup
Mark III RS-232 Full Duplex
Figure A-14: Port C settings
A.8
Mark III RS-485 Half Duplex
Figure A-15: Port C settings
A.9
Mark III Series 100 plus HART option board (if installed)
Figure A-16: Analog output 1
Daniel ™ Gas Ultrasonic 3410 Series Electronics
57
Mark III RS-232 and RS-485 Serial communications setup
Figure A-17: Analog output 2 (HART capable)
Figure A-18: Analog input 1 (Temperature)
Figure A-19: Analog input 2 (Pressure)
58
Retrofit Instructions
Summary table of communications/output settings
Appendix B
Summary table of communications/output settings
Based on switch position on the 3400 CPU board and Option board if installed, indicate the appropriate configuration for each communication/output parameters on the 3400 electronics. Use these parameters to configure the 3410 Series electronics.
Table B-1: Communications/output settings summary table
Output Type
Serial Port A
Serial Port B
Serial Port C
Digital Output 1A
Digital Output 1B
Frequency Output 1A
Digital Output 2A
Digital Output 2B
Not Used (if
J4-1 not used)
Not Used (if
J4-1 not used)
Not Used (if
J5-2 not used)
Not Used (if
J5-2 not used)
(Check electronics switch settings and circle appropriate box for each output)
Not Used (if
J6 not used)
RS-232 (if S3 is set to
RS232)
RS-485 Half
Duplex (if S3 is set to
RS-485 and
S5-1 is set to
Half
RS-485 Full
Duplex (if S3 is set to
RS-485 and
S5-1 is set to
Full
Not Used (if
J7 not used)
RS-232 (if S4 is set to
RS232)
RS-485 Half
Duplex (if S4 is set to
RS482 and
S5-2 is set to
Half)
RS-485 Full
Duplex (if S4 is set to
RS-485 and
S5-2 is set to
Full)
Not Used (if
J16 not used)
Not Used (if
J4-2 not used)
RS-232 (if
S10 is set to
RS232)
TTL (if S8-1 is set to TTL)
RS-485 Half
Duplex (if
S10 is set to
RS-485)
Open Collector (if S8-1 is set to OC)
TTL (if S8-2 is set to TTL)
TTL (if S8-3 is set to TTL)
TTL (if S9-1 is set to TTL)
TTL (if S9-2 is set to TTL)
Open Collector (if S8-2 is set to OC)
Open Collector (if S8-3 is set to OC)
Open Collector (if S8-1 is set to OC)
Open Collector (if S9-2 is set to OC)
Daniel ™ Gas Ultrasonic 3410 Series Electronics
59
Summary table of communications/output settings
60
Table B-1: Communications/output settings summary table
(continued)
Output Type
Frequency Output 1B
Frequency Output 2A
Frequency Output 2B
Analog Input 1
Analog Input 2
Analog Output 1
Analog Output 2 (HART Capable)
(Check electronics switch settings and circle appropriate box for each output)
Not Used (if
J5-1 not used)
Not Used (if
J5-6 not used)
Not Used (if
J5-5 not used)
TTL (if S8-4 is set to TTL)
TTL (if S9-3 is set to TTL)
TTL (If S9-4 is set to TTL)
Open Collector (if S8-4 is set to OC)
Open Collector (if S9-3 is set to OC)
Open Collector (if S9-4 is set to OC)
Not used (if
J12-1 not used)
Not Used (if
J12-3 not used)
Not Used (if
J11 not used)
Not Used (if
J10 not used)
Source (if
S12 is set to
SRC)
Source (if
S13 is set to
SRC)
Source (if
S14 is set to
SRC)
Source (if
S15 is set to
SRC)
Sink (if S12 is set to SINK)
Sink (if S13 is set to SINK)
Sink (if S14 is set to SINK)
Sink (if S15 is set to SINK)
Enter the results of the 3400 Summary Table of Communications/output settings in the table below as a quick reference to setup the 3410 Series meter configuration parameters.
Table B-2: Communications/output settings summary table results
Output Type
Serial Port A
Serial Port B
Serial Port C
(1)
Digital Output 1A
Digital Output 1B
Frequency Output 1A
Digital Output 2A
Digital Output 2B
Frequency Output 1B
Frequency Output 2A
Frequency Output 2B
Analog Input 1
Enter communications and output settings
Retrofit Instructions
Summary table of communications/output settings
Table B-2: Communications/output settings summary table results
(continued)
Output Type
Analog Input 2
Analog Output 1
Analog Output 2 (HART Capable)
Enter communications and output settings
(1) Port C is available for 3410 Series electronics with Optional I/O RS-232 and /or RS-485 Modules installed.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
61
Summary table of communications/output settings
62
Retrofit Instructions
3410 Communication and Output settings
Appendix C
3410 Communication and Output settings
Topics covered in this appendix:
•
3410 Wiring and I/O
•
Ethernet cable to PC communication
•
Input and output connections
•
Serial communications
•
Analog input settings
•
Analog output settings
•
Digital Input
•
External power source connection and fuse
C.1
3410 Wiring and I/O
Refer to the Daniel 3410 Series Ultrasonic Gas Flow Meter Installation Manual (P/N
3-9000-759) for more wiring details.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
63
3410 Communication and Output settings
Figure C-1: 3410 Upper electronics with Optional I/O Modules
Figure C-2: CPU Module labeling and LED indicators
64
Retrofit Instructions
3410 Communication and Output settings
Table C-1: CPU Module labeling and LED functions
CPU Module label or LED
WRITE PROT.
DHCP
PORT A
Function
Write-protect mode - with switch in the ON position (default setting) protects configuration and firmware overwrites.
To write configuration changes or download firmware to the meter change the switch to the
OFF position
Dynamic Host Protocol Server enables you to communicate with a Daniel meter that is not connected to a network.
When the CPU Module switch is in the ON position, the meter is enabled to act as a DHCP server for a single DHCP client connected to the Ethernet port using a crossover cable. This should be used for peer to peer connections only.
When the connection is made, select to use the Meter Name in the meter instead of the Meter
Directory Name in order to keep all log files and configurations separate from each meter.
PORT A override - RS-232 serves as an override during meter commissioning to establish communications and in the event the user cannot communicate with the meter due to an inadvertent communication configuration change. The override period is for two minutes. Supports:
• auto-detected ASCII (Start bit 1, Data Bit 7, Parity Odd/
Even, Stop Bit 1)
• RTU (Start Bit 1, Data Bit 8,
Parity none, Stop Bit 1).
• Modbus protocols RS-232
Baud rate=19,200 Modbus
ID=32
Switch position indicator or
LED
Switch position
• ON - (default setting) enables write-protection of the configuration and firmware
• OFF - enables writing configuration changes or downloading firmware
Switch position
•
ON
- the meter is enabled to act as a DHCP server for a single DHCP client
•
OFF
- disables the DHCP server
Switch position
• ON - enables RS-232 PORT
A override
• OFF - (default setting) disables RS-232 PORT A override
Daniel ™ Gas Ultrasonic 3410 Series Electronics
65
3410 Communication and Output settings
Table C-1: CPU Module labeling and LED functions
(continued)
MEAS System color indicates metrology mode Acquisition mode
Measurement mode
LED status
• Red flashing LED
• Solid red the Acquisition
Module is not communicating with the CPU Module
• Green flashing LED
Solid Green PWR
LED 4
LED 5
RX
TX
LINK
3.3V Power Indicator
Not used
Not used
RX signal (Port A for RS485 or
RS232) communication) receiving data
TX signal (Port A for RS485; 2wire or 4-wire) or RS232 communication) transmitting data
ETH1Link user Ethernet connection
Flashing green (when receiving data)
Flashing green (when transmitting data)
Solid green
Optional RS-232 Module wiring
Use the table in
to wire the Optional RS-232 module.
Figure C-3: Optional RS--232 Module wiring
66
Retrofit Instructions
3410 Communication and Output settings
Optional RS-485 Module wiring
Use the table in
to wire the Optional RS-485 module.
Figure C-4: Optional RS-485 Module wiring
C.2
Ethernet cable to PC communication
The Ethernet port IP address, subnet mask, and gateway address are softwareconfigurable. In addition, a meter can be configured to act as a DHCP (Dynamic Host
Configuration Protocol) server to assign an IP address to a PC or laptop running Daniel
MeterLink. The DHCP server facility is not intended to act as a general purpose DHCP server for a wider network. To this end, no user control is provided over the class or range of IP addresses the unit provides. A standard twisted pair (Cat-5) cable should be used for
Ethernet wiring.
It is strongly recommended that the meter be configured using an independent (offnetwork) single host. After configuration of the Daniel 3410 Series Gas Ultrasonic Flow
Meter, the DHCP option must be turned off if used on a LAN/WAN.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
67
3410 Communication and Output settings
NOTICE
RESTRICTED ETHERNET AND SERIAL CONNECTIVITY USAGE
Failure to restrict Ethernet and communication access to the Daniel 3410 Series Gas Ultrasonic
Flow Meter can result in, among other things, unauthorized access, system corruption, and/or data loss.
User is responsible for ensuring that physical access and Ethernet or electronic access to the
Daniel 3410 Series Gas Ultrasonic Flow Meter is appropriately controlled and any necessary security precautions are implemented; such as, establishing a firewall, setting password permissions and/or implementing security levels.
Figure C-5: Ethernet communication
C.3
Use ethernet cable, Daniel P/N 3-3400-079, to connect the PC to the meter.
A DIN 41612 48-pin connector is the interface from the CPU Module to the Backplane
(male end located on the back of the Backplane Board).
Input and output connections
The Daniel 3410 Series Ultrasonic Flow Meter provides the Analog inputs for pressure and temperature, Analog output 2 and frequency and digital outputs on the CPU Module lower terminal block.
68
Retrofit Instructions
3410 Communication and Output settings
Figure C-6: CPU Module lower terminal block I/O connections
I.
J.
E.
F.
G.
H.
A.
B.
C.
D.
Frequency/Digital Output 2 (FODO 2)
Frequency/Digital Output 2 (FODO 2) Gnd
Frequency/Digital Output 2 (FODO 2) Gnd
Frequency/Digital Output 3 (FODO 3)
Analog Output 2 + (4-20mA output)
Analog Output 2 - (4-20mA output)
Analog In (Temperature) +
Analog In (Temperature) -
Analog In (Pressure) +
Analog In (Pressure) -
Possible configurations for Frequency and Digital Outputs are shown in the following figure.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
69
3410 Communication and Output settings
Figure C-7: Frequency/Digital Output
Output for FODO1 and Digital Output1 (Group 1 on the CPU Module upper terminal block) share a common ground and have 50V isolation. FODO2 and FODO3 (Group 2 on the CPU
Module lower terminal block) share a common ground and have 50V isolation. This allows an output to be connected to a different flow computer. The outputs are opto-isolated from the CPU Module and have a withstand voltage of at least 500V rms dielectric.
70
Retrofit Instructions
3410 Communication and Output settings
Figure C-8: CPU Module Frequency and Digital shared common ground
C.4
Serial communications
Use a serial cable, Daniel P/N 3-2500-401, to connect to a PC running Daniel MeterLink.
The cable is designed for RS-232 communications which is the serial Port A default configuration (see
Systems Wiring Diagram, Daniel Drawing DMC - 005324).
The DB-9 end of the cable plugs directly into the PC running Daniel MeterLink
™
. The three wires on the other end of the cable connect to the CPU Module RS-485/RS-232 terminals.
The RED wire goes to RX, the WHITE wire goes to TX, and the BLACK wire goes to COM (see
Table 3-5 for Port A wiring).
RS-485, 2-wire connection on Port A, uses TX+ and TX- on the CPU Module and has a ground wire.
When Belden wire No. 9940 or equivalent is used, the maximum cable length for RS-232 communications at 9600 bps is 88.3 meters (250 ft.) and the maximum cable length for
RS-485 communication at 57600 bps is 600 meters (1970 ft.).
Port A supports a special override mode which forces the port to use known communication values (19200 baud, address 32, RS-232). Note that the protocol is autodetected. This mode is expected to be used during meter commissioning (to establish initial communication) and in the event that the user cannot communicate with the meter
(possibly due to an inadvertent communication configuration change). Alternately, when using Daniel MeterLink with an Ethernet port, use Ethernet cable, Daniel P/N 3-3400-079, to connect the PC.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
71
3410 Communication and Output settings
Table C-2: Serial port parameters
Port/Communication
• Port A (Standard)
• RS-232
• RS-485 Half Duplex
• RS-485 ( 2-wire communication on Port A.)
(1)
Description
• Typically used for general communications with a flow computer, RTU (Modbus slave) and radios.
• RS-485 - 2-wire (Half Duplex) connected to TX + and TX -
• Special override mode to force port configuration to known settings.
• Supports RTS/CTS handshaking with software-configurable RTS on/off delay times.
• Factory default is RS-232,
Address 32, 19200 baud.
Ethernet
Common features
• Communications via Daniel
MeterLink using RS-232 or
RS-485 Full Duplex
• Software configurable
Modbus Address (1-247)
• Auto-detects TCP/IP and
ASCII or RTU Protocol
• ASCII Protocol:
Start Bits = 1, Data Bits
= 7
(2)
Parity: odd or even 1,
Stop Bits = 1
(3)
Baud Rates: 1200,
2400, 9600, 19200,
38400, 57600, 115000 bps
-
• RTU Protocol: Start Bits = 1,
Data Bits = 8
(4)
Parity: none, Stop Bits =
1
(5)
Baud Rates: 1200,
2400, 9600, 19200,
38400, 57600, 115000 bps
Modbus TCP/IP, Modbus TCP Preferred port for diagnostic communication via Daniel MeterLink
™
10 Mbps/100 Mbps
(1) RS-485 2-wire connections use TX+ and TX - on the CPU Module
(2) Denotes auto-detected protocols
(3) Denotes auto-detected protocols
(4) Denotes auto-detected protocols
(5) Denotes auto-detected protocols
NOTICE
If not using Ethernet, a full duplex serial connection is necessary for Daniel MeterLink
™
to communicate with a Daniel 3410 Series Ultrasonic Flow Meter.
72
Retrofit Instructions
Figure C-9: PC to meter serial connection wiring
3410 Communication and Output settings
C.5
C.6
C.7
Analog input settings
The Daniel 3410 Series Ultrasonic Flow Meter has the capability to sample analog temperature (Analog Input 1) and pressure (Analog Input 2) with 4-20 mA signals. These analog input signals are configured to sink. The two independent analog input circuits are configured for conventional 4-20 mA service. Also, 24VDC isolated power supply connection is provided for an external power source. Refer to the System Wiring Diagram
Analog output settings
The Daniel 3410 Series Ultrasonic Flow Meter provides two 4-20 mA analog output signals that are software configurable for either sink or source current. Refer to the System Wiring
.
Full HART
®
functionality is provided so that any commercially available HART which meets the specifications of the HART
®
®
transmitter
Communications Foundation can be connected to a Daniel3410 Series Ultrasonic Flow Meter.
Digital Input
The Daniel 3410 Series Ultrasonic Flow Meter provides one digital input that can be used as a general purpose input. The digital input must be configured via the Daniel MeterLink
™
Tools|Edit/Compare Configuration
screen.
Daniel ™ Gas Ultrasonic 3410 Series Electronics
73
3410 Communication and Output settings
C.8
External power source connection and fuse
Located on the CPU Module are connections for a user-provided external power source, a 2
Amp fuse and a 24V loop power connection for ultrasonic meter analog outputs, temperature transmitter or pressure transmitter devices. The current is limited to 88mA.
Figure C-10: CPU Module power source connections
A.
B.
C.
24V Loop power
Power in connector (Main power source)
2 Amp fuse (used for main power input)
74
Retrofit Instructions
3410 Series engineering drawings
Appendix D
3410 Series engineering drawings
DMC-005324 3410 Series Ultrasonic Meter System Wiring Diagram
Daniel ™ Gas Ultrasonic 3410 Series Electronics
75
3410 Series engineering drawings
76
Retrofit Instructions
3410 Series engineering drawings
Daniel ™ Gas Ultrasonic 3410 Series Electronics
77
3410 Series engineering drawings
Daniel ™ Gas Ultrasonic 3410 Series Electronics
77
Daniel Measurement and Control, Inc.
11100 Brittmoore Park Drive
Houston, TX 77041 USA
T +1 713-467-6000
F +1 713-827-4805
USA Toll Free 1 888-356-9001
Daniel Measurement Services, Inc.
T +1 713-827-6314
www.Daniel.com
Europe: Stirling, Scotland, UK
T +44-1786-433400
Middle East Africa: Dubai, UAE
T +971-4-811-8100
Asia Pacific: Singapore
T +65-677-8211
This product is a core component of the PlantWeb digital plant architecture.
©
2015 Daniel Measurement and Control, Inc., All rights reserved.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Daniel Measurement and Control, Inc., and Daniel
Measurement Services, Inc., (Daniel) are Emerson Process
Management business units. The Daniel name and logo are trademarks of Daniel Industries, Inc. The Senior, Junior, Simplex,
MeterLink, SeniorSonic, JuniorSonic, and DanPac are trademarks of
Daniel Industries, Inc. All other trademarks are property of their respective owners.
P/N 3-9000-786
Rev A
2015
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement