advertisement
Trinity Tft
Model Numbers: Tft60 - 399
Version Date: 2015-06-24
INSTALLATION AND OPERATION INSTRUCTIONS FOR
TRINITY Tft BOILER
TABLE OF CONTENTS
1.0
INTRODUCTION ................................................................................................................ 3
2.0
SPECIFICATIONS .............................................................................................................. 6
3.0
BOILER LOCATION .......................................................................................................... 7
4.0
GENERAL VENTING ....................................................................................................... 10
5.0
VENT/AIR-INLET TERMINATION CLEARANCES ..................................................... 24
6.0
CONDENSATE DRAIN .................................................................................................... 26
7.0
INSTALLING GAS PIPING .............................................................................................. 28
8.0
LIGHTING THE BOILER ................................................................................................. 30
9.0
GAS VALVE AND BURNER SET-UP ............................................................................ 32
10.0
BOILER AND HEATING SYSTEM PIPING ................................................................... 35
11.0
LEAD LAG INSTRUCTIONS ........................................................................................... 46
12.0
FIELD WIRING ................................................................................................................. 49
13.0
WIRING SCHEMATICS ................................................................................................... 54
14.0
INSTALLATION CHECKLIST ........................................................................................ 56
15.0
ANNUAL MAINTENANCE AND INSPECTION ........................................................... 57
16.0
TROUBLESHOOTING ..................................................................................................... 59
17.0
PARTS LIST ...................................................................................................................... 81
H
HAZARD SYMBOLS AND DEFINITIONS
Danger Sign: Indicates a hazardous situation which, if not avoided, will result in serious injury or death.
Warning Sign: Indicates a hazardous situation which, if not avoided, could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous situation which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if not avoided, could result in property damage.
This Boiler must be installed by a licensed and trained Heating
Technician or the Warranty is Void. Failure to properly install this unit may result in property damage, serious injury to occupants, or possibly death.
Visit us online
NTI # 84535
Trinity
│
Installation and Operation Instructions Tft Series
Read Before Proceeding
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING _
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to turn the gas “shutoff” valve. Never use tools. If the handle will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the
boiler and to replace any part of the
control system and any gas control which has been under water.
OPERATING INSTRUCTIONS _
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service technician or gas supplier.
TO TURN OFF GAS TO THE BOILER _
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler.
3. Turn the manual gas valve to the OFF position.
Crystalline Silica - Certain components confined in the combustion chamber may contain this potential carcinogen. Improper installation, adjustment, alteration, service or maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Section 14.0 for information on handling instructions and recommended personal protective equipment.
Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the supplied instructions before installing, servicing, or removing this boiler. This boiler contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Void Warranty - This Boiler must have water flowing through it whenever the burner is on or it will damage the unit and void the warranty. Failure to follow these instructions may result in serious injury or death.
2
Tft Series Installation and Operation Instructions
│
Trinity
1.0 INTRODUCTION
General Installation Requirements
The installation of your NTI Trinity Tft gas boiler must conform to the requirements of this manual, your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for
Automatically Fired Boilers ANSI/ASME CSD-1.
This document pertains to the correct installation and operation of NTI Trinity boiler model Tft. The instructions detailed in this document supersede any and all previous instructions provided by NTI, written or otherwise.
Each unit is provided with the following:
1. Installation and Operating Instructions,
2. Appendix A – Controller and Touchscreen Display Instructions,
3. Trinity Users Manual, and
4. Natural Gas to LP Conversion Kit*
* The conversion kit is required to convert the boiler so it will safely operate with Propane Gas.
Read and understand this entire document prior to proceeding with the installation of the
Trinity Tft. Failure to follow the instructions outlined in this document will result in property damage, serious injury or death.
Energy Saving Feature - This boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE
OF THE FOLLOWING CONDITIONS IS TRUE :
An external energy management system is installed that reduces the boiler water temperature as the heating load decreases.
This boiler is not used for any space heating.
This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
This boiler is equipped with a tankless coil.
User Responsibilities
This boiler must be installed and serviced by a qualified installer or service technician. This boiler must be serviced and inspected annually when operating in normal residential applications. Demanding applications or extreme conditions (i.e. commercial) may require more frequent service and inspection. As the User/Owner of this equipment, you are responsible for ensuring the maintenance is performed at the required intervals (see
Section 14 – Annual Maintenance and Inspection).
Failure to have the boiler properly serviced and inspected on a regular basis by a qualified service technician may result in property damage, serious injury or death.
Failure to keep the Vent and Combustion Air Intake clear of ice, snow, and other debris may result in property damage, serious injury, or death.
Installer Responsibilities
As the installing technician it is your responsibility to ensure the installation is performed in accordance with this instruction manual as well as any applicable local or National installation codes. It is also your responsibility to inform the User/Owner of their obligation with respect to the above description under “User Responsibilities”.
Failure to follow this warning could result in fire, serious injury, or death.
3
Trinity
│
Installation and Operation Instructions Tft Series
Failure to use the appropriate Natural to LP Conversion Kit and Orifice when operating the Trinity Tft with Propane will result in extremely dangerous burner operation leading to property damage, serious injury or death. Refer to section titled ATTENTION:
LIQUEFIED PETROLEUM (LP) PROPANE for applicable conversion kit and LP orifice numbers.
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
The Trinity Tft is factory set to operate with Natural Gas. BEFORE OPERATING WITH PROPANE, the specified LP Conversion Kit and Orifice must be installed to convert the boiler so it will operate safely with
LP Propane. The correct kit and LP orifice is listed below (Each kit comes with conversion instructions).
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your Trinity Tft boiler is not installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require boilers fueled with LP gas be provided with an approved means of removing unburned gases from the room. Check your local codes for this requirement.
Model Number
Natural to LP Propane Conversion Kit
_
Kit Number
Tft60-85
Tft110
82650-1
82650-1
Tft155-250
Tft300-399
82650-1
84471-1
LP Orifice
415 (4.15mm)
52 (5.2mm)
62 (6.2mm)
74 (7.4mm)
Boiler Vent / Air-Inlet Piping
The Trinity Tft is certified as a “Category IV” boiler, and requires a “Special Venting
System” designed for pressurized venting. The exhaust gases must be piped directly to the outdoors using the vent materials and rules outlined in these instructions. Failure to follow these instructions will result in serious injury or death.
4
Tft Series Installation and Operation Instructions
│
Trinity
IN THE STATE OF MASSACHUSETTS ONLY
(a) For all horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed and on each additional level of the dwelling, building or structure served by the equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors. a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 30 days to comply with the above requirements; provided, however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating boiler or equipment. The sign shall read, in print size no less than onehalf (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”
(plate included with boiler).
4. INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED: When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED:
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting system” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts list for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
5
Trinity
│
Installation and Operation Instructions Tft Series
2.0 SPECIFICATIONS
Table 2-1 Trinity Tft Specifications
DESCRIPTION Tft60 Tft85 Tft110 Tft155 Tft175 Tft200 Tft250 Tft300 Tft399
CSA Input Modulation
1,4
[MBH]
DOE Heating Capacity
1,2
[MBH]
17-60
56
17-85 21.6-108
78 99
31-155
144
31-175
163
31-200
185
31-250
230
79.8-299 79.8-399
278 380
Net I=B=R Rating
1,2
[MBH]
48 68 86 125 141 160 199 239 330
DOE AFUE
2
[%] 95 95 95 95 95 95 95 94 95.4
Water Connections – NPT
[in.]
Gas Connection - NPT, in.
Vent/Air-inlet Pipe Diameter
[in.]
3
1 (Male)
2 or 3
Dimensions H x W x D [in.]
33-3/8 x 19-3/4 x 14-1/2
Approx. Boiler Weight with Water [lbs]
Approx. Boiler Water
Content [Gallons]
Electrical Rating
110
3.2
½ (Male)
1-1/4 (Male)
3
33-3/8 x 19-3/4 x 18-1/2
180
4.9
120V/1Ph/60Hz/less than12A
1-1/2 (Male)
¾ (Male)
4
36-3/8 x 25-1/4 x 20
250
6.4
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at an altitude of 0-2000ft. Numbers will be lower with longer venting and/or altitudes greater then 2000ft.
2
Ratings based on standard test procedures prescribed by the U.S. Department of Energy; certified by AHRI. Tft399 efficiency represents Thermal Efficiency (AFUE is not applicable).
3
Trinity Tft requires a special venting system, use only vent materials and methods detailed in these instructions.
4
When operating with Propane models Tft60, Tft85 and Tft110 have min/max Input Modulation rates of 17/65, 17.6/88 and 22.6/113 MBH respectfully.
Wall mounting of unit requires two people to lift the boiler into place. Failure to follow these instructions may result in property damage or personal injury.
High Altitude Operation
The Trinity Tft is designed to operate at its maximum listed capacity in installations located at 0-2000ft above
Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity should be derated for elevations above 2000 ft [610 m] in accordance with Table 2-2.
Table 2-2 De-rate % for High Altitudes
2001 ft [610 m] 3000 ft [914 m] 4000 ft [1219 m] 4500 ft [1372 m] 5000 ft [1524 m] Elevations
In Canada
1
In USA
2 de-rate by 10%
- de-rate by 10% de-rate by 12% de-rate by 10% de-rate by 16% de-rate by 10% de-rate % may vary de-rate by 18% de-rate by 20%
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 10%. Consult local authorities for de-rating capacities for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m], if altitude is above 2000 ft [610 m].
Combustion – At elevations above 2000 feet, the combustion of the boiler must be checked with a calibrated combustion analyzer to ensure safe and reliable operation. It is
the Installers responsibility to check the combustion and to adjust the combustion in
accordance with Section 9.0. Failure to follow these instructions may result in property damage, serious injury, or death.
6
Tft Series Installation and Operation Instructions
│
Trinity
3.0 BOILER LOCATION
In all cases, the Trinity Tft must be installed indoors in a dry location where the ambient temperature must be maintained above freezing and below 100
F [38
C]. All boiler components must be protected from dripping, spraying water, or rain during operation and servicing. Consider the proximity of system piping, gas and electrical supply, condensate disposal drain, and proximity to vent termination when determining the best boiler location.
Water or flood damaged components must be replaced immediately with new factoryapproved components as failure to do so may result in fire, serious injury, or death.
Boiler Area Ventilation Air Openings
Direct Vent – If boiler area clearances are less than the recommended clearances specified in Table 3-1, the
3 boiler area must be ventilated (Exception: if the boiler area/room has a volume of 150 ft or greater, ventilation of the boiler room is not required). Each ventilation air opening must meet the minimum requirements of 1 in
2
per 1000 Btu/hr, but not less than 100 in
2
. The lower ventilation opening must be located within 6” of the floor while the upper opening must be located 6” from the top of the space.
If the "Boiler Area" does not meet the recommended clearances listed in Table 3-1, and if the boiler area has a volume less than 150 ft
3
, it is considered a Closet or Alcove. PVC vent pipe and fittings shall not be used within the closet or alcove; only approved CPVC,
Polypropylene or Stainless Steel vent pipe and fittings can be used. See Table 4-4 for a list of approved materials. Under all circumstances, the minimum clearances listed in
Table 3-1 must be provided.
Indoor Combustion Air – When using Indoor Combustion Air in lieu of Direct Vent air-inlet piping, provisions for combustion and ventilation air, in accordance with section “Air for Combustion and Ventilation,” of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 (U.S.), or Clause 8.2, 8.3 or 8.4 of Natural Gas and Propane
Installation Code, CAN/CSA B149.1 (Canada), or applicable provisions of the local building codes, must be adhered to.
Closet Installations
For closet installations it is necessary to provide two ventilation air openings as shown in Figure 3-1, each providing a minimum area equal to 1 in
2
per 1000 Btu/hr, but not less then 100 in
2
and within 6” of the top and bottom of the closet door. See Table 3-1 for minimum clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be completely open to the room at a distance no greater then 18” [457 mm] from the front of the boiler and the room is at least three (3) times the size of the alcove. Provided these conditions are met, the boiler requires no extra ventilation air openings to the space. See Table 3-1for minimum clearances.
Residential Garage Installations
When installed in a residential garage, mount the boiler a minimum of 18” [457 mm] above the floor. Locate or protect the boiler so it cannot be damaged by a moving vehicle. Check with your local authorities for other possible regulations pertaining to the installation of a boiler in a garage.
Wall Mounting Installations
The Tft is provided with integrated wall mounting brackets. Refer to Figure 3-2 for instructions and illustrations on wall mounting.
7
Trinity
│
Installation and Operation Instructions Tft Series
Table 3-1 Minimum Clearances for Installation and Service
Model No. Clearances
Minimum
Front Top
24 [610]
1
12 [305]
Dimensions - inches [mm]
Sides Back
4 [102] 0
Bottom
9 [229]
Flue Pipe
1 [25]
Trinity Tft
Recommended 36 [914] 24 [610] 12 [305] 0 24 [610] 1 [25]
Notes:
1
6” if surface is removable allowing a minimum of 24” [610 mm] clearance (i.e. closet installation). See Ventilation Air
Opening dimensions in Figure 3-1.
Closet/alcove installations in US and Canada require approved CPVC, Polypropylene or
Stainless Steel vent and air-inlet pipe and fittings (see Table 4-4); PVC is not permitted.
Failure to follow these instructions may result in damage or serious injury.
Figure 3-1 Closet Installation, Minimum Clearances
(Model Tft60-110 Shown)
Min. 1” clearance for hot water and
vent pipes
Top ventilation opening
M ax. 6” below ceiling / top
Top = 12”
Bottom = 9”
Front = 6”
(if removable)
Ventilation air opening
1in
2
per 1000 Btu/hr, min. 100in
2
Removable surface / closet door
Ventilation air opening
1in
2
per 1000 Btu/hr, min. 100in
2
Bottom ventilation opening
Max. 6” above floor / bottom
Sides = 4”
Ventilation Air Openings are not required if the boiler area meets the
Recommended Clearances listed in Table 3-1.
8
Tft Series Installation and Operation Instructions
│
Trinity
Figure 3-2 Wall Mounting Instructions
While leaving the Upper bracket (A) intact, remove the Wall-mount bracket (B) attached to the bottom-back of the appliance. Save the mounting hardware for Step 4.
Secure the Wall-mount bracket (B), removed from the bottom of the boiler in Step 1, to a solid wall using field supplied lag screws
(anchors when mounting to a concrete wall) that are adequate to support the weight of the appliance (refer to Table 2-1 Specifications).
Ensure the Wall-mount bracket is mounted level and flush to the wall with mounting holes on the bottom, flange pointed upward and angled away from the wall.
Mount the appliance to the wall by aligning the
Upper bracket (A) with the Wall-mount
bracket (B). Slide the Upper bracket down over the wall mount bracket until it hooks.
Once the appliance is resting securely on the
Upper bracket, secure the Bottom bracket (C) to the underside of the appliance using the mounting hardware removed in Step 1; then, anchor the bottom bracket to the wall as shown using field supplied hardware.
Upper bracket (A)
Wall-mount bracket (B)
Failure to follow instructions may result in fire, serious injury, or death.
This unit requires two people to lift it or damage and injury may result.
Wall Boiler
(A)
Wall-mount bracket (B)
(B)
Ensure bracket
(A) fully inserts into bracket (B)
Bottom bracket (C) shipped with boiler package
9
Trinity
│
Installation and Operation Instructions
4.0 GENERAL VENTING
Tft Series
The Trinity Tft is certified as a “Category IV” boiler requiring a “Special Venting System” designed for pressurized venting. The Exhaust Vent must be piped to the outdoors, using the vent materials and rules outlined in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and utilizes the approved venting material and rules described in this section.
Vent and Air-inlet are to be piped separately. The Trinity Tft cannot share a common vent or air-inlet with multiple boilers; unless the common venting system has been certified by
NTI (Contact NTI for details).
Failure to comply will result in serious injury or death.
Removing an Existing Boiler from Common Venting System
Do not install the Trinity Tft into a common venting system with any other boiler. Failure to comply with this warning will cause flue gas spillage and leech carbon monoxide emissions into the surrounding air resulting in serious injury or death.
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the remaining boilers connected to it. Instructions have been provided on how to remove the existing boiler and how to resize the remaining venting system. Failure to follow these instructions may result in property damage, serious injury or death.
Upon removal of an existing boiler, the following steps shall be followed for each boiler remaining in the common venting system; prior to commencing this procedure, shutdown all boilers remaining in the common venting system.
Steps to Removing an Existing Boiler:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Verify that there is no blockage, restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close fireplace dampers, all building doors and windows and all doors between the space in which the boilers remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any boiler not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
4. Place in operation the boiler being inspected. Follow the applicable lighting instructions. Adjust thermostat so boiler will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each boiler remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning boiler to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code.
10
Tft Series Installation and Operation Instructions
│
Trinity
Direct Vent Installation
When installed as a Direct Vent boiler the combustion air-inlet must also be piped directly to the outdoors using the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
Indoor Combustion Air (non-Direct Vent)
When the installation uses Indoor Combustion Air (i.e. piping is not directly connecting the appliance air-inlet fitting to the outdoors), provisions for combustion and ventilation air, in accordance with section “Air for
Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (U.S.), or Clause 8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1 (Canada), or applicable provisions of the local building codes, must be adhered to.
The boiler shall be located so as not to interfere with proper circulation of combustion, ventilation, and dilution air.
Make up air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air requirements. Failure to ensure adequate make up air to all appliances may result in personal injury or death.
Combustion Air-inlet Contamination
Be careful not to locate the air-inlet termination in an area where contaminants can be drawn in and used for combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature failure, fire, serious injury, or death. See Table 4-1 for a list of areas to avoid when terminating air-inlet piping:
Table 4-1 Corrosive Products and Contaminant Sources
Products to Avoid Contaminated Sources to Avoid
Antistatic fabric softeners, bleaches, detergents, cleaners
Perchloroethylene (PCE), hydrocarbon based cleaners
Chemical fertilizer, herbicides/pesticides, dust, methane gas
Paint or varnish removers, cements or glues, sawdust
Water chlorination chemicals (chloride, fluoride)
Solvents, cutting oils, fiberglass, cleaning solvents
Refrigerant charge with CFC or HCFC
Permanent wave solutions
Laundry facilities
Dry cleaning facilities
Farms or areas with livestock and manure
Wood working or furniture refinishing shops
Swimming pools, hot tubs
Auto body or metal working shops
Refrigerant repair shops
Beauty shops
Fixer, hydrochloric acid (muriatic acid), bromide, iodine Photo labs, chemical / plastics processing plants
Cement powder, crack fill dust, cellulose, fiber based insulation Concrete plant or construction site
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other boiler. Failure to follow instructions may result in serious injury or death.
It is BEST PRACTICE to pipe the combustion air-inlet directly to the outdoors (Direct
Vent installation) to avoid contamination often contained in indoor air.
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-inlet prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly assembled piping assembly should be allowed to cure for a minimum of 8 hours before applying power to the gas fired boiler. Refer to Mandatory Pre-commissioning Procedure for Plastic Venting in this section.
Flammable Cements and Primers – It is the installers’ responsibility to familiarize themselves with the hazards associated with explosive solvents and to take all precautions to reduce these risks. Failure to follow these instructions can cause explosions, property damage, injury or death.
11
Trinity
│
Installation and Operation Instructions Tft Series
Mandatory Pre-commissioning Procedure for Plastic Venting (PVC or CPVC)
Do not apply power to the boiler prior to Step 4 in the Mandatory Pre-commissioning
Procedure for Plastic Venting.
1) Working with the power turned off to the boiler, completely install the vent and air intake system, securely cementing joints together. If possible, allow primers/cements to cure for 8 hours before firing the burner. If curing time is less than 8 hours, proceed with Steps 2 through 6.
2) Maintain the boiler gas supply shut-off valve in the off position.
3) Remove the cable from the Spark Ignition Transformer.
Spark Ignition Circuit - Maintain a safe distance (2 inches minimum) from the spark ignition circuit to avoid injury from electrical shock.
4) Turn power on to the boiler and apply a heat demand.
5) Allow for 3 complete trials for ignition, consisting of pre and post purge of the combustion blower, until an ignition lockout occurs. Repeat the process two more times (i.e. 9 complete ignition sequences in total).
6) Turn power off and reconnect the cable to the Spark Ignition Transformer.
Near Boiler Vent/Air-inlet Piping
Each Trinity Tft is equipped with a short piece of approved CPVC vent pipe which is to be used when venting with PVC. Insert one end into the boiler flue outlet adapter and cement the other to the field venting (see Table 4-
4 for approved venting material). The CPVC vent pipe should extend fully into the boiler flue outlet adapter (see
Table 4-2). Ensure that the venting system does not apply a load or strain on the boiler flue outlet adapter. The manufacturer recommends using two elbows to create a “swing joint” to reduce potential strain on vent piping and cemented joints. See Figures 4-2 through 4-4 for illustrations.
Gasket Seating - Improper seating can cause leakage and eventual failure of the sealing gasket. Ensure the vent pipe is adequately beveled prior to inserting into the boiler flue adapter. Failure to follow these instructions may result in serious injury or death.
PVC Exhaust Venting – DO NOT insert PVC pipe directly into the appliance exhaust adapter, as it can deform from the clamping force of the gear clamp. Failure to follow these instructions may result in gasket failure and/or the dislodging of the exhaust pipe from the appliance adapter, resulting in property damage, serious injury or death.
Polypropylene or Stainless Steel Venting – When using Polypropylene or Stainless Steel piping, the appropriate appliance adapters must be used to transition the appliance vent connections to accept the respective Polypropylene or Stainless Steel venting. See Table
4-3 for a list of approved adapters. Failure to use the correct adapter will result in flue gas leakage resulting in property damage, serious injury or death.
12
Tft Series Installation and Operation Instructions
│
Trinity
Figure 4-2(a) Trinity Tft60-110 & 300-399
Near Boiler Venting (CPVC)
Swing Joint
to attain slope in horizontal runs
CPVC Exhaust
Vent
Flue Outlet
Adapter (factory supplied)
Air-inlet
Pipe *
Air Inlet
Adapter
(factory supplied)
Figure 4-2(b) Trinity Tft60-110 & 300-399
Near Boiler Venting (PVC)
Swing Joint
to attain slope in horizontal runs
PVC Exhaust Vent -
(check local codes and Table 4-3)
PVC Coupling
CPVC Transition
Pipe -
minimum 5” long (factory supplied)
Air-inlet
Pipe *
Air Inlet
Adapter
(factory supplied)
Flue Outlet
Adapter (factory supplied)
Mandatory Vent Pipe
Transition Pipe
See Table 4-2.
Figure 4-2(c) Trinity Tft155-250
Near Boiler Venting (CPVC)
Air-inlet Pipe *
Air Inlet Adapter
(factory supplied)
Swing Joint
to attain slope in horizontal runs
CPVC Exhaust
Vent
Flue Outlet
Adapter (factory supplied)
Air-inlet
Pipe *
Air Inlet
Adapter
(factory supplied)
Figure 4-2(d) Trinity Tft155-250
Near Boiler Venting (PVC)
Swing Joint to attain slope in horizontal runs
PVC Exhaust Vent -
(check local codes and Table 4-3)
PVC Coupling
CPVC Transition
Pipe - mini mum 5” long (factory supplied)
Flue Outlet
Adapter (factory supplied)
Mandatory Vent Pipe
Transition Pipe
See Table 4-2.
Air-inlet - check with applicable local codes for acceptable pipe material.
Exhaust venting must be supported to reduce strain on piping joints. Failure to follow these instructions may result in result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
13
Trinity
│
Installation and Operation Instructions
Figure 4-2(e) Trinity Tft60-110 & 300-399
Near Boiler Venting (Stainless Steel)
SS Air-inlet Pipe
Tft Series
Figure 4-2(f) Trinity Tft60-110 & 300-399
Near Boiler Venting (Polypropylene)
PPS Elbow
w/ offset angle to account for slope
PPS Air-inlet Pipe*
Swing Joint
to attain slope in horizontal runs
SS Exhaust
Vent
Flue Outlet
Adapter (factory supplied)
SS Appliance Adapter
(see Table 4-3)
PPS Exhaust Vent
Air Inlet Adapter
(factory supplied)
PPS Appliance Adapter
(see Table 4-3)
Flue Outlet Adapter
(factory supplied)
Air-inlet Adapter
(factory supplied)
Figure 4-2(g) Trinity Tft155-250 Figure 4-2(h) Trinity Tft155-250
Near Boiler Venting (Stainless Steel)
SS Air-inlet Pipe
FasNSeal Appliance
Adapter (see Table 4-3)
Air Inlet Adapter
(factory supplied)
Swing Joint
to attain slope in horizontal runs
SS Exhaust
Vent
Flue Outlet
Adapter (factory supplied)
Near Boiler Venting (Polypropylene)
PPS Air-inlet Pipe*
Air Inlet Adapter
(factory supplied)
PPS Elbow
w/offset angle to account for slope
PPS Exhaust Vent
PPS Appliance Adapter
(see Table 4-3)
Flue Outlet Adapter
(factory supplied)
Air-Inlet - check with applicable local codes for acceptable pipe material.
Exhaust venting must be supported to reduce strain on piping joints. Failure to follow these instructions may result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
14
Tft Series Installation and Operation Instructions
│
Trinity
Table 4-2 CPVC Vent Pipe Transition Piece (used when venting with PVC)
Model No.
Tft60-110
Tft155-250
Tft300-399
Vent Pipe Size
3”
3”
4”
CPVC Transition Vent Pipe Length
Minimum 5” [127 mm]
Minimum 5” [127 mm]
Minimum 5” [127 mm]
Table 4-3 Appliance Adapters for Polypropylene and Stainless Steel Venting
Model No. Vent Material Venting Brand
Tft60-250
Polypropylene
DuraVent – PolyPro
Centrotherm - InnoFlue
Stainless Steel DuraVent – FasNSeal
DuraVent – PolyPro
Polypropylene
Tft300-399 Centrotherm - InnoFlue
Full Insertion Depth
2-7/8” [73 mm]
2-5/8” [67 mm]
2-5/8” [67 mm]
Adapter Part No.
1,2
300150
ISAA0303
300715
300151
ISAA0404
Stainless Steel DuraVent – FasNSeal 303631
Notes:
1
Listed appliance adapters are only approved for use with the respective venting brand; i.e. a PolyPro appliance adapter shall not be used with InnoFlue venting.
2
PolyPro and FasNSeal appliance adapters are available from DuraVent (1-800-835-4429 or www.duravent.com
);
InnoFlue appliance adapters are available from Centrotherm Eco Systems (1-877-434-3432 or www.centrotherm.us.com).
Vent/Air-inlet Pipe Material
Table 4-4 Acceptable Vent and Air-Inlet Pipe Material
Items
1
Vent Piping and Fittings
Pipe Cement
Materials
2, 3
PVC - DWV
PVC Schedule 40
PVC
CPVC
Venting System Standards
United States
Canada
4
ANSI/ASTM D2265
ANSI/ASTM D1785
CPVC Schedule 40 ANSI/ASTM F441
Stainless Steel (SS) UL-1738
Polypropylene (PP) -
ANSI/ASTM D2564
ANSI/ASTM F493
All venting material in
Canada must be
ULC S636 approved.
See Note 4 below for appropriate temperature applications.
All Vent and Air-Inlet materials installed on gas fired appliances in CAN/US must meet the Standards listed in this Table. Failure to comply could result in fire, serious injury or death.
Primers
PVC / CPVC ANSI/ASTM F656
Notes:
1
2
Refer to Table 4-5 for Allowable Vent and Air-Inlet Pipe Sizes and Lengths.
PVC venting (exhaust and air-inlet) is not permitted within the Closet/alcove of a Closet/alcove installation.
3
The Air-inlet does not require high temperature pipe material. Check applicable local codes for acceptable materials.
4
ULC S636 PVC is approved for flue gas temperatures up to 149 o
F (65 o
C) and must only be used for low temperature applications. High temperature applications requiring boiler supply water temperatures greater than 140 o
F (60 o
C) must use ULC S636 CPVC, PP or SS.
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
(polyphenolsulfone) in the exhaust venting system is prohibited. Failure to follow these instructions may result in property damage, personal injury or death.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Failure to follow these instructions may result in property damage, personal injury or death.
15
Trinity
│
Installation and Operation Instructions
Vent/Air-inlet Pipe Length Determination
Tft Series
Use Table 4-5 to determine the maximum pipe length that can be used. The table calculates 90º elbows, and 45º elbows at 5 equivalent feet each.
Example: When using 3” pipe, a Tft60-110 can be installed with 150 equivalent feet of air-inlet piping and 150 equivalent feet of exhaust-vent piping. See Table 4-5 for more details.
Models Tft60-110 require a minimum equivalent exhaust vent length of 15’. When operating on Propane, models Tft60-110 require a minimum air-inlet length of 6’ and 11’ for 2” and 3” venting respectfully.
Table 4-5 Allowable Vent and Air-inlet Pipe Size and Lengths
Model No.
Pipe
Size
Gas
Length
(ft)
1
Number of Elbows (90’s or 45’s) and Equivalent Feet
2 3 4 5 6 7 8 9
Tft60-110 NG 100 95 90 85 80 75 70 65 60 55
Tft60-85 2”
1
LP
35 30 25 20 15 10 5 - - -
Tft110
25 20 15 10 5 - - - - -
Tft60-110 150 145 140 135 130 125 120 115 110 105
3”
Tft155-250 NG/LP 100 95 90 85 80 75 70 65 60 55
Tft300-399
4”
100 95 90 85 80 75 70 65 60 55
Note:
1
See WARNING below.
PVC Exhaust Venting – When using 2” PVC venting with models Tft60-110, the first seven (7) equivalent feet of exhaust venting must be approved 2” CPVC or 3” PVC; see exceptions in Table 4-4 and Figures 4-2b and 4-2d.
Termination Options
– Direct Vent Installation
The venting system of the Tft may be terminated using field supplied piping to construct a “Two-Pipe” termination, see Figures 4-3a, 4-4a, 4-4d, 4-5a, 4-6a and 4-6d; alternatively the venting may be terminated using a factory kit selected from Table 4-6. The “IPEX Low Profile” kit (see Figures 4-3b and 4-5c) and “M&G
DuraVent Concentric (Wall)” kit (see Figures 4-3d and 4-5d) can be used for Sidewall terminations, while the
“M&G DuraVent Concentric (Roof)” kit (see Figures 4-4c and 4-6c) can be used for Rooftop terminations; the
“IPEX Concentric” kit (see Figures 4-3c, 4-4b, 4-5b and 4-6b) can be used for either Sidewall or Rooftop terminations.
Sidewall Termination - Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may not be the preferred venting option. Refer to Figures 4-4 and
4-6 for roof top venting options.
The vent for this appliance shall not terminate over public walkways; or near soffit vents or crawl space vents or other area where condensate of vapor could create a nuisance or hazard or cause property damage; or where condensate or vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
Extra precaution must be taken to adequately support the weight of the Vent/Air-inlet piping in applications using roof-top terminations. Failure to follow these instructions may result in venting or boiler component failure resulting in flue gas spillage leading to property damage, serious injury or death.
Optional Termination Kits
– Direct Vent Installation
Kits certified with the Trinity Tft are listed in Table 4-6 and available from IPEX, DuraVent and/or NTI. For more information on System 636 Vent Kits or wholesaler locations contact IPEX directly USA: 1-800-463-9572 or www.IPEXamerica.com
│
CAN: 1-866-473-9462 or www.ipexinc.com
. For more information on PolyPro
Vent Kits or wholesaler locations contact DuraVent directly 1-800-835-4429 or www.duravent.com. For more information on InnoFlue Vent Kits or wholesaler locations contact Centrotherm directly at 1-877-434-3432 or www.centrotherm.us.com.
16
Tft Series Installation and Operation Instructions
│
Trinity
Table 4-6 Optional Vent Termination Kits
Description
Vent
Size
Supplier P/N
IPEX Low Profile
(Flush Mount)
7
2”
3”
4”
2”
196984 (NTI P/N 85062)
196985 (NTI P/N 84357)
196986 (NTI P/N 84358)
196125
IPEX Concentric
(Wall/Roof)
5,6,7,8
3”
4”
196116 (NTI P/N 82666)
197117
196021 (NTI P/N 84355)
197021
DuraVent - PolyPro
Concentric (Wall)
DuraVent - PolyPro
Concentric (Roof)
Centrotherm – InnoFlue
(Flush Mount)
2”
3”
4”
2”
3”
4”
2”
3”
2”
2PPS-HK
3PPS-HK
4PPS-HK
2PPS-VK
3PPS-VK
4PPS-VK
ISLPT0202
ISLPT0303
ICWS2413 & ICTC0224
Figure
4-3(b), 4-5(c)
4-3(c), 4-4(b),
4-5(b), 4-6(b)
Vent Material
Compatibility
PVC/CPVC
7
PVC/CPVC
7
4-3(d), 4-5(d) PVC/CPVC/PP
4-4(c), 4-6(c) PVC/CPVC/PP
PVC/CPVC/PP
Vent Option
Roof Wall
Centrotherm – InnoFlue
Concentric (Wall)
9
Centrotherm – InnoFlue
Concentric (Roof)
9
3”
4”
2”
3”
4”
ICWS3513 & ICTC0335
ICWT352 & ICTC0335
ICWS4639 & ICTC0446
ICRT2439 & ICTC0224
ICRT3539 & ICTC0335
ICRT4679 & ICTC0446
4-3(d), 4-5(d) PVC/CPVC/PP
4-4(c), 4-6(c) PVC/CPVC/PP
Notes:
1
2
Instructions included with termination kits contain detailed assembly and installation instructions.
3
All factory termination kits are ULC S636 approved.
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
4
Piping MUST be secured to the vent terminal during installation.
5
IPEX Concentric Terminal MUST be cemented together and to the vent pipes during installation.
6
Vent Screens provided with boiler may be used with the IPEX Concentric Vent Kits; otherwise use IPEX vent screens
(2” vent screen P/N 196050; 3" vent screen P/N 196051; 4" vent screen P/N 196052 – each sold separately).
7
IPEX Low Profile and Concentric kits (excluding P/N’s 197117 & 197021) are constructed out of ULC S636 approved
PVC; check with your local authority for the acceptance of PVC as a venting material prior to use.
8
IPEX Concentric kits can be shortened to fit the requirements of the installation; see instructions included with the kit for more details.
9
Centrotherm Concentric termination kits must use the applicable “Twin pipe to concentric adapter,” part number
ICTC0224, ICTC0335 or ICTC0446.
10
2” Vent Termination Kits may only be used with models Tft60-110; see Table 4-5.
11
3” Vent Termination Kits may only be used with models Tft60-250; see Table 4-5.
12
4” Vent Termination Kits may only be used with models Tft300-399; see Table 4-5.
PVC In Canada - Authorities in some jurisdictions may not allow the use of any PVC venting materials with condensing boilers; check with the local safety inspector to verify compliance prior to installing a PVC Concentric Vent Kit with a Trinity Tft.
17
Trinity
│
Installation and Operation Instructions
Sidewall Venting Options
– Direct Vent Installation
Figure 4-3(a)
Two-pipe Termination (Sidewall)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Figure 4-3(b)
Low Profile Termination (Sidewall)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Inlet
Tft Series
Exhaust
Exhaust
Inlet
Figure 4-3(c)
IPEX Concentric Termination (Sidewall)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Inlet
Exhaust
Figure 4-3(d)
PolyPro / InnoFlue Concentric Termination (Sidewall)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Inlet
Exhaust
18
Tft Series Installation and Operation Instructions
│
Trinity
Roof Venting Options
– Direct Vent Installation
Figure 4-4(a)
Two-pipe Termination (Roof)
Figure 4-4(b)
IPEX Concentric Termination (Roof)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Inlet
Inlet
Exhaust
Exhaust
Figure 4-4(c)
PolyPro / InnoFlue Concentric Termination (Roof)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Figure 4-4(d)
Two-pipe Termination (Roof-exhaust / Sidewall-inlet)
Location of exhaust and air-inlet connections vary between models, see Figure 4-2.
(model Tft60-110 shown)
Exhaust
Inlet
Exhaust
Inlet
19
Trinity
│
Installation and Operation Instructions Tft Series
Sidewall Termination Details
– Direct Vent Installation
Figure 4-5(a)
Exhaust
Two-Pipe Termination (Sidewall)
Horizontal
4-
12” or greater than 36”
Figure 4-5(b)
IPEX Concentric Termination (Sidewall)
Refer to documentation included with termination kit for complete installation instructions.
Exhaust
Exhaust
Air-inlet
Vertical
Min. 18”
Air-inlet
Gas Vent Directly Below
Keep Free of Obstructions
Air-inlet
Air-inlet around perimeter (1-
2” from wall)
Exhaust through center
Vent Screen
Vent Screen
Min. 12” above grade or snow level Vent pipe piece to retain vent screen
Min. 12” above grade or snow level
Vent pipe piece to retain vent screen
Figure 4-5(c)
IPEX Low Profile Termination
Refer to documentation included with termination kit for complete installation instructions.
Exhaust
Air-inlet
Figure 4-5(d)
DuraVent PolyPro Wall Termination
Refer to documentation included with termination kit for complete installation instructions.
Exhaust
Air-inlet
Air-inlet around perimeter
Exhaust
Gas Vent Directly Below
Keep Free of Obstructions
Air-inlet bottom
Exhaust center
Min. 12” above grade or snow level
Min. 12” above grade or snow level
20
Tft Series Installation and Operation Instructions
│
Trinity
Roof Termination Details
– Direct Vent Installation
Figure 4-6(a)
Two-Pipe Termination (Roof)
Figure 4-6(b)
IPEX Concentric Termination (Roof)
Exhaust
Vent Screen
Vent pipe piece to retain vent screen
Refer to documentation included with termination kit for complete installation instructions.
Vent pipe piece to retain vent screen
Air-inlet
Exhaust center
Vent Screen
Vertical
Min. 18”
Min. 12” above grade or snow level
Air-inlet around perimeter
Min. 12” above grade or snow level
Flashing
Horizontal
4-
12” or greater than 36”
Figure 4-6(c)
DuraVent PolyPro Roof Termination
Refer to documentation included with termination kit for complete installation instructions.
Exhaust
Air-inlet
Flashing
Figure 4-6(d)
Exhaust only Roof Termination
Figure illustrates two options for exhaust termination only; neither vent pipe illustrated is for combustion air-inlet.
Vent pipe piece to retain vent screen
Exhaust
Option 1
Vent Screen
Min. 12” above grade or snow level
Min. 12” above grade or snow level
Exhaust
Option 2
Flashing
Flashing
21
Trinity
│
Installation and Operation Instructions Tft Series
Venting Rules and Guidelines
1.
Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
2.
Combustion Air-inlet Contamination: Air for combustion must be drawn from an area free of dust and contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust and debris will cause corrosion damage of the heat exchanger voiding your NTI warranty. Refer to Table 4-
1 for a list of corrosive products and contaminants sources to avoid.
3.
Vertical Separation: The exhaust must be a minimum of 18” [457 mm] above the air inlet, and the air inlet must always be a minimum of 12” [305 mm] plus snow allowance above any surface that will support snow.
(Two feet plus snow allowance is highly recommended). Consult your weather office for the maximum typical snowfall for your region.
Example: New Brunswick Canada - typical maximum snowfall is 19”, thus the inlet must be (12”+19”)
=
31” above grade and exhaust must be (31”+18”)
=
49” above grade.
4.
Horizontal Separation: The horizontal distance between the inlet and exhaust must be a minimum of 4”
[102 mm] center to center.
5.
Wall Flashing: Under normal operating conditions this boiler will produce a plume of white gases, and should be taken into consideration when selecting an adequate location. A 36” [915 mm] diameter stainless, plastic, or vinyl shield can be used to flash the exterior of the residence.
6.
Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people and pets or damage nearby shrubs and plants.
7.
Elbow Extensions: Elbows on outside of wall must be no more than ½” [13 mm] away from the wall.
8.
Vent Sloping: All indoor exhaust piping must be on a slope back to the boiler a minimum of ¼” per linear foot of vent [6.25 mm per linear 305 mm]. For applications where excessive condensation is possible ½” per linear foot [13 mm per linear 305 mm] is recommended.
9.
Vent Supports: Where required Vent and Air-inlet piping shall be secured to the wall for more rigidity. All interior vent pipe shall be supported a minimum of every 36” [915 mm].
10. Roof Exhaust: In all roof applications the discharge must point away from the pitch of the roof.
11. Roof Flashing: Install adequate flashing where the pipe enters the roof, to prevent water leakage.
12. Rain Cap: Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
13. Venting Below Grade: For installations that exit the wall below grade refer to Figure 4-7.
14. Vent Screens: Install factory supplied vent screens on the outside of the last elbow for both the inlet and exhaust vent terminal elbows. Install the screen into the female opening of the elbow, and then cut a small piece of pipe to sandwich the screen into the elbow. NOTE: ensure the small piece of pipe cut, does not extend past the end of the elbow. Two screens are provided in the package. See Figures 4-5 and 4-6.
15. Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate could drip and freeze resulting in a slip hazard or damage to vehicles and machinery.
16. Warning Plate: For Sidewall Venting, install the warning plate “Gas Vent Directly Below”, directly above
(within 4 ft [1.22 m] vertically) the location of the air-inlet pipe, so it is visible from at least 8 ft [2.4 m] away. See Figure 4-5.
17. Wall Thickness: Direct vent terminations are designed to work with any standard wall thickness.
Installation guidelines for min/max wall thickness are as follows: Min.= 1” [25mm], Max.= 60” [1.52 m].
18. Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may not be the preferred venting option. Refer to Figures 4-4 and 4-6 for roof top venting options.
22
Tft Series Installation and Operation Instructions
│
Trinity
Figure 4-7 Venting Below Grade
For installations that exit the wall below grade:
1. Excavate site to a point below where the pipes are to exit as shown.
2. Ensure the wall is fully sealed where the pipes penetrate.
3. The Vent/Air-inlet piping MUST be secured to the side of the building above grade, as shown, to provide rigidity.
4. Optional mounting bracket PN. 82075 for securing the exhaust pipes (only applicable for
3” PVC/CPVC venting).
12” [305 mm] plus snow allowance above grade
5. Ensure that the Vent/Air-inlet clearances are maintained, see Section 5.0 for details.
Supports every
24” [610 mm]
Air-Inlet
Figure 4-8 Outdoor Venting
Vent piping outside the building is permitted under the following conditions:
1. The maximum length outside the building is 20 feet [6.1 m]. Note that outdoor length must be included in the overall vent length calculation.
2. All normal termination clearances are maintained.
3. The pipe is supported every 24” [610 mm].
4. The exhaust and air-inlet are sloped back to the boiler ½” elevation for every linear foot [13 mm for every linear 305 mm].
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust
Vent
Maximum of 20 ft
[6.1 m] is permitted for piping outside a building.
Figure 4-9 Existing Chimney Chase Way
It is permissible to use an existing chimney as a chase way to run the Vent/Air-inlet piping as long as:
1. The chimney is not being used by any other boiler.
2. Flue gases don’t enter the vacant chimney.
3. Only Trinity certified venting materials are used, see Section 4.0.
4. Vent lengths are within the maximums specified.
5. The top of the chimney is capped and the
Vent/Air-inlet pipes are flashed to prevent leakage into the vacant chimney.
Chimney
Cap
Existing
Chimney
(used as a chase way)
Exhaust Vent
Air-Inlet
Exhaust Vent Min.
18” [457 mm] above air-inlet
Air-Inlet
Min. 12” [305 mm] above roof and snow level
Under no circumstances may an existing chimney or chase-way be used to vent or provide combustion air to a Trinity Tft. Failure to follow these instructions will result in fire, property damage, serious injury or death.
23
Trinity
│
Installation and Operation Instructions
5.0 VENT/AIR-INLET TERMINATION CLEARANCES
Tft Series
The quick reference table below is to be read in conjunction with the numbered notes as indicated, Figures 5-1 and 5-2, and the Venting Rules and Guidelines in Section 4.0. The instructions detailed in this section are a combination of Trinity Tft specific and National Gas Code restrictions.
Compliance alone doesn’t insure a satisfactory installation as good common sense must also be applied. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Table 5-1 Termination Clearances Quick Reference Table (See Figures 5-1 and 5-2)
Canada
1
USA
2
Clearances to Air-Inlet Termination
Min. Distance Min. Distance
A Above grade/roofline and snow level
8
B Above roof line - Concentric Vent
6, 11, 13
12 in. 305 mm 12 in. 305 mm
24 in. 610 mm 24 in. 610 mm
C To exhaust vent from any other boiler
Clearances to Exhaust Vent Termination
A Above grade/roofline and snow level
8
D Minimum vertical separation above air inlet
9
E Minimum horizontal separation from air inlet
3
F Window or door that may be opened, or other building opening
G To combustion air inlet of any other appliance
H Non-mechanical air supply inlet to building
I Mechanical air supply inlet to building
4
J Soffit, overhang, eave or parapet
K Soffit vent or vent opening in an overhang, eave or parapet
L Outside corner
10
36 in. 915 mm 12 in. 305 mm
Min. Distance Min. Distance
12 in. 305 mm 12 in. 305 mm
18 in. 457 mm 18 in. 457 mm
4 in. 102 mm 4 in. 102 mm
36 in. 915 mm 12 in. 305 mm
36 in. 915 mm 12 in. 305 mm
36 in. 915 mm 12 in. 305 mm
6 ft. 1.83 m 3 ft. 915 mm
24 in. 610 mm 24 in. 610 mm
6 ft. 1.83 m
-
-
6 ft. 1.83 m
- -
M Inside corner of an L-shaped structure (including walls and fences)
U Above, under or near exterior stairs
V Into a canopy or carport
36 in. 915 mm 36 in. 915 mm
N Service regulator / vent outlet 36 in. 915 mm 36 in. 915 mm
P Each side of center line above or below meter / regulator assembly
5
36 in. 915 mm 36 in. 915 mm
Q Above a paved sidewalk, driveway, or parking lot on public property if adjacent
12
7 ft. 2.13 m 7 ft. 2.13 m
X X X X
R Above a public walkway
S Above a sidewalk or paved driveway that is located between two single family dwellings and services both dwellings
T Under a concrete veranda, porch, deck, or balcony
7
X
24 in.
X X X
610 mm 24 in. 610 mm
X
X
X
X
X
X
X
X
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local building codes.
2 - US installations must comply with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code and local building codes.
3 - Horizontal separation center-to-center (c.c.) 4”-12” (102-305 mm).
4 - For US installations, an exhaust vent must be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally.
5 Horizontal clearance must be observed up to a height of 15 ft. [4.6 m] above/below the meter, regulator, or relief devices
.
6 - Concentric Vent must protrude from the roof precisely 24” [610 mm] measuring from the terminal end-cap vanes.
7 - Permitted if veranda, porch, deck, or balcony is made of concrete and a minimum of two sides are fully open beneath.
8 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice
(i.e. for roof venting clearances - roofline and snow level). If living in a snowfall region, consult your local weather office for the maximum typical snowfall for your area.
9 - Note that the vent must maintain a minimum vertical distance above the air-inlet. Example: Vent height = 18” (457 mm) above air inlet + 12” (305 mm) for air inlet above grade/roof line and snow level = 30” (762 mm) above grade and snow level.
10 Clearances to an outside corner to be in accordance with local installation codes.
11 In Canada, concentric vent materials are subject to approval by local inspectors. See Termination Kits in Section 4.0.
12 Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard.
13 Contact the manufacturer for special exemptions relating to multiple boiler installations using concentric vents.
_
X
-
Not permitted by National gas code(s) and/or recommended by boiler manufacturer.
24
Tft Series Installation and Operation Instructions
│
Trinity
Figure 5-1 Termination Clearance Quick Reference Diagram (See Table 5-1)
Illustrations of Termination Clearances
Figure 5-2 Sidewall Termination (See Table 5-1)
Clearances “F” and “G”
Canada
– Minimum 3 ft. [915 mm]
The US
– Minimum 1 ft. [305 mm]
Two-Pipe
Termination
F
Clearance “Q”
Adjacent to Public
Walkway or Driveway
Minimum 7ft. [2.13 m]
Q
G
Concentric Vent
Termination
G
– Letter represents a specific Termination Position. Refer to Table 5-1 for corresponding termination clearances.
25
Trinity
│
Installation and Operation Instructions
6.0 CONDENSATE DRAIN
Tft Series
This unit produces liquid condensate in the heat exchanger and venting system as a product of combustion.
Steps must be taken to ensure condensate does not collect in the venting system; therefore, all exhaust piping must slope back to the boiler a minimum 1/4” per linear foot of vent. Condensate must be drained from the unit into a household drain.
Check with your municipality, or local gas company to determine if the disposal of combustion condensate is permitted in your area (e.g. in the State of Massachusetts the condensate must be neutralized prior to entering a drain).
The following are important notes that must be taken into consideration when constructing the condensate drain system (See Condensate Trap Installation Instructions for further details):
DO NOT install condensate lines outside. A frozen or blocked drain will cause the condensate to back-up and leak. This may result in damage to boiler components resulting in a no heat condition; property damage may also occur.
NEVER use copper, steel, or galvanized piping in the construction of the condensate system (condensate is very corrosive and will corrode most metals).
When a condensate pump is used or required, select a pump that is designed for residential furnaces.
All tubing, drains and surfaces that come in contact with condensate draining from the boiler, must be constructed out of corrosion resistant material; copper, steel and galvanized are not acceptable materials for draining condensate. Failure to abide by this caution will result in property damage.
Condensate Trap Installation Instructions (see Figure 6-1)
(Note: the Condensate Trap is factory supplied with the boiler and must be field installed)
1. Inspect Condensate Trap Assembly – Inspect the Condensate Trap to ensure all parts were shipped with the assembly (see Figure 6-1). The Condensate Trap must be periodically disassembled and cleaned as part of a regular maintenance plan.
2. Attach to Boiler Condensate Drain – Insert the inlet fitting of the Condensate Trap into the boiler condensate drain; secure with the factory supplied gear clamp (see Figure 6-1). Pull down on the Condensate
Trap and ensure that it remains securely fastened.
3. Outlet to Drain – Direct condensate from the outlet of the Condensate Trap to a household drain, condensate pump or neutralizer (check with your local authority regarding the disposal of condensate). If necessary connect suitable ¾” tubing to the bottom of the Condensate Trap and route it to drain, being careful NOT to route it higher than the Condensate Trap outlet (see Figure 6-1).
The Condensate Trap must be periodically disassembled and cleaned as part of a regular maintenance plan. Failure to clean the trap regularly can cause condensate drain blockage leading to boiler malfunction, property damage and even personal injury.
Carefully follow the above instructions and the accompanying figure – check to ensure the condensate trap is secure to the bottom of the boiler and that no strain is placed on it.
Failure to install the condensate trap properly will result in flue gas spillage and leeching of carbon monoxide emissions into the surroundings resulting in serious injury or death.
26
Tft Series Installation and Operation Instructions
│
Trinity
Figure 6-1 Condensate Drain Piping
Inspect Condensate
Trap assembly
Boiler Condensate Drain
Gear Clamp
(factory supplied)
Condensate Trap
(factory supplied)
Attach to Boiler Condensate Drain
Tighten gear clamps and pull down on Condensate Trap to test secureness
Pipe Outlet to Drain
Direct condensate to a vented drain; ensure no strain is applied to the Condensate Trap and Boiler Condensate
Drain. If n ecessary, add a piece of ¾” tubing to the bottom of the Condensate Trap as illustrated.
27
Trinity
│
Installation and Operation Instructions Tft Series
7.0 INSTALLING GAS PIPING
The Trinity Tft is factory equipped to operate with Natural Gas, the installation of a conversion kit is required prior to operating with Propane Gas. The Natural to LP
Conversion Kit (see Table 7-1) must be installed prior to installing the gas piping to the boiler. Failure to properly convert the unit to operate with Propane may result in property damage, serious injury or death.
Liquefied Petroleum (LP) propane gas is heavier than air. Do not install the boiler in a pit or similar location that will permit heavier than air gas to collect. Check with Local
Codes as they may require boilers fueled with LP gas to be provided with an approved means of removing unburned gases from the room. Failure to follow these instructions may result in serious injury or death.
Table 7-1 Natural to LP Propane Conversion Kit
Model Kit Number Orifice Number
Tft60-85
Tft110
Tft155-250
82650-1
82650-1
82650-1
415 (4.15mm)
52 (5.2mm)
62 (6.2mm)
Tft300-399
Installation
84471-1 74 (7.4mm)
Refer to the current National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation codes, and local codes for gas piping requirements and sizing. Pipe size running to the unit depends on:
Length of pipe.
Number of fittings.
Type of gas.
Maximum input requirement of all gas boilers in the residence.
Ensure that:
The gas line connection to the boiler does not apply any weight to the gas valve. NTI recommends using approved flexible gas piping (if acceptable by local codes) to connect the boiler to the gas supply (See
Figure 7-1 for details).
You plan the installation so the piping does not interfere with the vent pipe, or the removal of the valve, burner, and serviceable components.
The Boiler is installed such that the gas ignition system components are protected from water (dripping, spraying, rain etc.) during installation and servicing.
The gas piping is large enough for all the gas appliances in the home. No appreciable drop in line pressure should occur when any unit (or combination of units) lights or runs. Use common gas-line sizing practices.
Always use a pipe-threading compound that is resistant to Propane (LP) gas solvent action. Apply sparingly to all male threads, starting at two threads from the end. Over doping or applying dope to the female end, can result in a blocked gas line.
DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the valve or blower motor can occur.
Install a manual “Equipment Shut-Off Valve” as shown in Figure 7-1. Valve must be listed by a nationally recognized testing laboratory.
The gas line piping can safely be removed from the boiler for servicing, by strategically placing the gas line shutoff and union; see example in Figure 7-1.
All gas piping, including gas components in the boiler, are checked for leaks using a “Bubble Test”, prior to operating the boiler.
Strain on the gas valve and fittings may result in vibration, premature component failure and leakage and may result in a fire, explosion, property damage, serious injury or death.
Do not use an open flame to test for gas leaks. Failure to follow these instructions may result in fire, property damage, serious injury or death.
When performing a pressure test on the gas line piping, be sure the boiler is disconnected or isolated if the test pressure is expected to exceed 1/2 PSI (14” w.c.), as damage to the gas valve could occur resulting in fire, property damage, serious injury or death.
28
Tft Series Installation and Operation Instructions
│
Trinity
Figure 7-1 Gas Line Connection (Typical)
Manual Gas Shutoff Valve
Should overheating occur or the gas supply fail to shutoff, close the
Manual Gas Shutoff Valve to the boiler.
Union
Flexible Gas Line Piping
Recommended to eliminate strain on the boiler gas components (only use if acceptable by local codes).
Drip Leg / Optional Gas Supply Location
When used as the Gas Supply Location, remove cap and install on the top fitting; drip leg must be field constructed external to the boiler.
Test all gas piping, internal and external to the boiler, for leaks. Failure to follow these instructions may result in fire, property damage, serious injury or death.
29
Trinity
│
Installation and Operation Instructions Tft Series
8.0 LIGHTING THE BOILER
Before Start-up refer to Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.
Failure to follow these instructions can result in explosions, injury or death.
Prior to turning the gas supply on and lighting the boiler, ensure all aspects of the installation are complete and in conformance with the instructions provided in this manual, including the Vent/Air-Inlet, Condensate Drain, and System Water Piping. Failure to precisely follow these instructions will cause a fire or explosion resulting in property damage, serious injury or death.
Do not store or use gasoline or other flammable vapors & liquids in the vicinity of this or any other boiler. Failure to follow instructions could result in explosion causing property damage, serious injury or death.
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, serious injury or death.
Should overheating occur or the gas supply fail to shutoff, close the Manual Gas Shutoff
Valve to the boiler. Failure to follow instructions could result in explosion causing property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING _
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to turn the gas “shutoff” valve. Never use tools. If the handle will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the
boiler and to replace any part of the
control system and any gas control which has been under water.
OPERATING INSTRUCTIONS _
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service technician or gas supplier.
TO TURN OFF GAS TO THE BOILER _
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler
3. Turn the manual gas valve to the OFF position
30
Tft Series Installation and Operation Instructions
│
Trinity
The initial lighting of the boiler must be performed by a licensed Gas Technician.
Failure to follow instructions may result in property damage, serious injury or death.
Ensure the boiler is wired in accordance with this manual.
Ensure the gas shutoff valve is turned on, and that the gas system has been fully tested for leaks.
Ensure the system is completely filled with water, and that ALL the air is purged out.
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8 hours, first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for
Plastic Venting in Section 4.0.
Failure to follow these instructions can result in explosion, serious injury or death.
Initial Start-Up
1. Turn on power to the Trinity Tft and turn-up the Thermostat(s). The boiler should run through a purge, and combustion should occur. (The control system has a built-in ignition retry, allowing the system to try at least three times, before locking-out.)
2. With the unit operating at full capacity, verify that the gas line pressure is 4-10.5 inches w.c. for Natural gas, and 9-13 inches w.c. for Propane (See Section 9.0 for details).
3. Using an appropriate Oxygen (O
2
) or Carbon Dioxide (CO
2
) analyzer, take a sample of the flue gas. The sample must fall within the acceptable ranges for CO
2
, which is 8.7% - 9.7% for Natural Gas, and 10.5%-
11.5% for Propane (See Section 9.0 for details).
4. Perform at least three lights in succession to ensure proper operation.
5. After the three successive lights, unplug the flame probe, and allow the unit to cycle again. The flame safety system will allow the unit to go through 4 ignition cycles before going to “Hold 110 – Ignition failure occurred”. Once you have confirmed this behavior, replace the wire on the flame sensor, recycle power and reconfirm proper lighting.
The flame probe is located in the burner plate; it has a single white/semi-transparent wire connected to it. DO NOT remove the orange spark cable from the ignition electrode
(also located in the burner plate); this device is used for spark ignition and produces 14,000 volts potential which would result in an EXTREME ELECTRICAL SHOCK possibly causing serious injury or death.
If the unit fails to light consistently and smoothly, contact NTI for technical assistance at
1-800-688-2575. Never allow the boiler to operate if the ignition or operation of the burner is rough or erratic. Failure to follow these instructions may result in serious injury or death.
Re-lighting Unit
1. Stop and read these instructions very carefully.
2. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device that automatically lights the burner.
Do not try to light the burner by hand.
4. Turn the gas shutoff valve to the off position, and then remove the front cover.
5. Wait five (5) minutes to clear out any gas. Then check for gas, including near the floor. If you smell gas
“Stop” and follow “B” above (see FOR YOUR SAFETY, READ BEFORE OPERATING). If you don’t detect any gas proceed to the next step.
6. Turn the gas shutoff valve to the on position, wait an addition five (5) minutes and check for gas.
7. Replace the front cover.
8. Set the thermostat to the highest setting, and then turn on all power to the boiler.
9. Ignition sequence is automatic, combustion will occur after a brief fan purge. Ignition will retry 3 times.
10. If ignition does not occur, “Turn off the gas and electricity to the boiler” and contact a qualified service technician, or gas supplier.
Turning Off the Boiler
1. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
2. Turn the gas shutoff valve to the off position.
31
Trinity
│
Installation and Operation Instructions
9.0 GAS VALVE AND BURNER SET-UP
Tft Series
Gas Line Pressure
Set-up of the Trinity Tft gas valve must be performed by a licensed Gas Technician.
Failure to perform the set-up correctly may result in incorrect operation, component failure, property damage, serious injury or death.
The boiler gas valve is equipped with a line pressure test port; see Figures 9-1 and 9-2. Use the following procedure to measure the gas line pressure to the boiler to ensure it falls within the range given in Table 9-1:
1. Turn the supply of gas to the boiler off.
2. Open the bleed screw of the line pressure test port approximately 1-1/2 turns. This port is directly connected to the gas line feeding the boiler. See Figures 9-1 and 9-2.
3. Force 1/4
ID tubing over the housing of the line pressure test port; install the other end of the tubing to an appropriate line pressure test gauge or manometer. Ensure both ends of the tubing make a tight connection.
4. Open the supply of gas to the boiler and check for gas leaks.
5. Observe the line pressure under static conditions and compare it to Table 9-1. The pressure will be greatest under static conditions.
6. With all other gas appliances in the application running, operate the burner to the maximum firing rate (See
Table 9-2) and compare the observed line pressure with Table 9-1. The pressure will be lowest during the maximum flow of gas.
7. Adjust the gas line pressure to ensure the parameters in Table 9-1 are attained under all conditions. If possible adjust the line pressure to the "Nominal/Desired" value listed in Table 9-1, while the unit is operating at the maximum modulation rate, see Table 9-2.
8. Continue observing the gas line pressure until the completion of the combustion analyses, in case adjustments need to be made.
9. Complete pressure testing, and then return the bleed screw of the Line Pressure Test Port to the closed position.
The line pressure is a function of the gas supply and is affected solely by field provided parameters such as line size and regulator settings. Under no circumstances can the boiler gas valve influence or be used to adjust the gas line pressure.
Failure to close the bleed screw of the Line Pressure Test Port will cause a severe leakage of gas, resulting in a fire or explosion causing property damage, serious injury or death.
Table 9-1 Line Pressure and Combustion Parameters
Line Pressure (inches wc) CO
2
(%)*
Gas
Nominal/Desired Min. Max. Min. Max.
CO (ppm)
Max.*
175
175
Natural
7 4 10.5 8.7 9.9
Propane
11 8 13 10 11.5
*Note: Observe the combustion products with the burner operating at the maximum modulation rate.
Table 9-2 Minimum and Maximum Modulation Rates
Model Min. Modulation Rate (RPM) Max. Modulation Rate (RPM)
Tft60
Tft85
1525
1525
4650
6300
Tft110
Tft155
Tft175
Tft200
Tft250
Tft300
Tft399
1625
900
900
900
900
1500
1500
7000
3700
4100
4650
5900
5000
6900
32
Tft Series Installation and Operation Instructions
│
Trinity
Carbon Monoxide - Never leave the unit operating while producing Carbon Monoxide
(CO) concentrations in excess of 175ppm. Failure to follow this warning may result in serious injury or death.
Manifold Pressure - DO NOT adjust or measure the Manifold Pressure of the boiler.
Correct manifold pressure is factory set. Field adjustment could result in improper burner operation resulting in fire, explosion, property damage or death.
Adjustments to the Throttle / Input Screw may only be made by a qualified gas technician, while using a calibrated combustion analyzer capable of measuring CO
2
and
CO. Adjustments may only be performed if the gas line pressure is maintained above
Decrease gas
Turn Clockwise minimum levels throughout the duration of the test, see Table 9-1. Failure to follow these instructions may result in serious injury or death.
Throttle/Input Adjustment Screw
Increase gas
Turn Counter Clockwise
Adjustment
Throttle / Input Screw Adjustments - The boiler is equipped with a Throttle/Input Adjustment Screw, located on the Gas Valve and Venturi Assembly. It is used to adjust the flow of gas leaving the gas valve entering the
Venturi and then the combustion air stream. Turn the adjustment screw in (clockwise) to reduce the flow of gas, make combustion leaner, and reduce the concentration of CO
2
in the flue gases. To increase the CO
2
level and flow of gas in the combustion air stream, adjust the Throttle screw out (counterclockwise).
Tft60-250 Adjustments - The throttle screw for models Tft60-250 is a multiple turn valve. Typical adjustment required for Natural Gas is 0-1 full turns in or out from the factory setting. Typical adjustment for LP Gas is
0-3 full turns in or out from the factory setting upon inserting the LP orifice as per the applicable Propane conversion instructions. See Figure 9-1 for throttle screw location.
Tft300-399 Adjustments - The throttle screw for the Tft300-399 is a geared valve with a 4:1 ratio. Adjusting the throttle screw 4 complete turns will return the valve to the original location, 2 turns from fully open will completely close the valve. Typical adjustment required is 0-1/4 turn in or out from the factory setting. See
Figure 9-2 for throttle screw location.
Combustion Calibration - To calibrate burner operation, perform the following procedure using a calibrated combustion analyzer capable of measuring CO
2
and CO from Natural and Propane Gas burning boilers:
1. Operate the unit at the maximum modulation rate, see Table 9-2.
2. Ensure the gas line pressure is maintained within tolerance, see Table 9-1.
3. While at the maximum modulation rate, measure the CO
2
and CO; adjust as necessary, using the Throttle
Screw, to be within the limits listed in Table 9-1.
4. Operate the unit at the minimum modulation rate (Table 9-2). Ensure the combustion remains smooth and
CO
2
and CO remain within the limits (Table 9-1). If not, do not adjust further, contact NTI for assistance.
Flue Gas Analysis and Adjustment
Each Trinity Tft is factory set to operate with Natural Gas, for boilers field converted to operate with Propane
Gas, a flue gas analysis and adjustment is mandatory. See Table 7-1 and Propane conversion instructions.
Failure to perform the flue gas analysis and adjustment detailed in this section may result in erratic and unreliable burner operation, leading to reduced efficiency, increased fuel consumption, reduced component life, heat exchanger combustion deposits, and general unsafe operation. Failure to follow these instructions may result in serious injury or death.
Analysis – Perform flue gas analysis, and adjust throttle/input screw as required until CO
2
and CO levels are within acceptable limits.
33
Trinity
│
Installation and Operation Instructions
Figure 9-1 Tft60-250 Gas Valve and Venturi Assembly
(model Tft60-110 shown)
Gas Valve
Tft Series
DO NOT Remove
Cap
Manifold Pressure
Test Port
Venturi
Line Pressure
Test Port
Throttle / Input
Adjustment Screw
Figure 9-2 Tft300-399 Gas Valve and Venturi Assembly
Manifold Pressure
Test Port
Throttle / Input
Adjustment Screw
Line Pressure
Test Port
Gas Valve
DO NOT
Remove Cap
Venturi
34
Tft Series Installation and Operation Instructions
│
Trinity
10.0 BOILER AND HEATING SYSTEM PIPING
The fire tube design of the Trinity Tft heat exchanger results in minimal head loss, however it must be considered when sizing system piping and circulators. Furthermore, the low mass of the Tft heat exchanger requires a minimum flow rate anytime the burner is operating. To maintain the efficient and reliable operation of the heat exchanger, and to avoid heat exchanger failure, it is critical to ensure the rules and guidelines in this section are followed.
Failure to follow the instructions provided in this section will void the NTI warranty and may result in property damage, fire, serious injury or death.
Boiler System Preparation
Prior to connecting plumbing to the boiler, flush the entire system to ensure it is free of sediment, flux, solder, scale, debris or other impurities that may be harmful to the system and boiler. During the assembly of the heating system, it is important to keep the inside of the piping free of any debris including construction and copper dust, sand and dirt.
For retrofits, all system piping, including radiators, must be cleansed of build-up including sludge and scale. All systems, old and new, must be cleansed to remove flux, grease and carbon residue; NTI recommends cleaning the boiler system with “Fernox F3 Cleaner”. For retrofit applications with heavy limescale and sludge deposits, a heavier duty cleaner may be required; NTI recommends the use of “Fernox DS-40 System Cleaner”. For information on performing the cleaning, follow the instructions included with the applicable Fernox Cleaner. See
Table 10-1 for a list of recommended boiler system cleaning and treatment products.
Failure to rid the heating system of the contaminants listed above will void your NTI warranty and may result in premature heat exchanger failure and property damage.
Table 10-1 Boiler System Cleansers and Corrosion Inhibitors
Application
Fernox Product NTI Part # Description
Boiler Water Treatment F1 Protector
Cleanser for new and old systems F3 Cleaner
83448
83449
DS-40 System Cleaner 83450 Cleanser for Retrofits
Boiler Water
Corrosion inhibitor.
Removes flux, grease and carbon residue.
Removes heavy limescale and sludge deposits.
Pressure - Trinity boilers are intended solely for use in pressurized closed-loop heating systems operating with a minimum pressure of 15 PSI at the boiler outlet. To obtain the minimum system design pressure, follow the piping diagrams illustrated in this section.
Oxygen Elimination - This boiler may only be installed in a pressurized closed-loop heating system, free of air and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the system during commissioning via strategically placed, adequately sized air-removal devices; located throughout the heating system. See figures in this section detailing the location of the primary air-removal device required for the boiler. Immediately repair any leaks in the system plumbing to avoid the addition of make-up water; make-up water provides a source of oxygen and minerals that may lead to heat exchanger failure. Failure to follow these instructions will result in poor performance, unnecessary wear of system components and premature failure.
The Trinity Tft is not approved for operation in an “open system”, thus it cannot be used for direct potable water heating or process heating of any kind.
Water Chemistry – The installer of the Trinity Tft boiler must consider the condition of the water in the heating system. Ensure the condition of the boiler water falls within the following parameters:
PH – between 6.6 and 8.5.
Chloride – less than 125mg/l.
Iron – less than 0.5mg/l.
Copper – less than 0.1mg/l.
Conductivity – less than 400µS/cm (at 25ºC); [TDS < 200ppm or Total Hardness < 11.6grains/USgal.]
35
Trinity
│
Installation and Operation Instructions Tft Series
Treatment - Boiler water that falls outside of the conditions listed above must be treated with a corrosion inhibitor. For information on performing the treatment, follow the instructions included with the corrosion inhibitor. See Table 10-1 for a list of recommended boiler system cleaners and corrosion inhibitors.
To maintain protection, the level of corrosion inhibitor must be monitored periodically for the correct concentration.
Anti-freeze - For systems requiring freeze protection, use only inhibited propylene glycol, specially formulated for hydronic heating systems; use of other types of antifreeze may be harmful to the system and will void the warranty. Note: the use of glycol may reduce the usable output capacity of the boiler, thus requiring the unit to be “down-fired” by limiting the maximum operating capacity and/or the maximum water temperature.
NTI recommends against exceeding 35% concentration of glycol.
DO NOT use inhibited glycol with non-compatible boiler inhibitors. Non-compatible inhibitors may counteract each other rendering them ineffective.
Near Boiler Plumbing
Pressure Relief Valve - A Pressure Relief Valve is factory supplied with each unit. Trinity Tft boilers have a maximum allowable operating pressure of 30PSI (80PSI for models Tft155-399). The pressure relief valve must be installed at the boiler outlet and in the vertical position, as shown in Figures 10-1 through 10-3, with the drain pipe outlet exiting the side of the pressure relief valve horizontally and elbowing downward.
If installed in the incorrect orientation (horizontally with drain pipe out the bottom) the relief valve may not function properly resulting in property damage or personal injury.
Ensure the discharge of the pressure relief is piped to a location where the steam or water will not cause property damage or serious injury.
Pressure Gauge – Trinity Tft units come with a factory supplied Pressure Gauge. The pressure gauge must be installed at the boiler outlet prior to any circulators. See Figures 10-1 through 10-3.
Auto Air Vent – Install the factory supplied auto air vent directly above the outlet fitting on the top of the unit; see Figures 10-1 through 10-3 illustrating the correct location. Failure to install the auto air vent as illustrated may result in occasional malfunctioning of the incorporated LWCO.
Low Water Cutoff (LWCO) – Trinity Tft boilers are provided with a factory installed LWCO switch which incorporates a Test Button and Power and Low Water indicator lights. Perform the following Operational
Test Procedure before placing the boiler in service, and ensure Maintenance is carried out with the following schedule.
Do not run the boiler unattended until the following procedure is completed. Failure to follow procedure may lead to unsafe boiler operation resulting in fire, property damage and loss of life.
Operational Test Procedure (LWCO)
1. Before introducing water to the boiler, turn the power on; both the green “POWER” LED and amber “LOW
WATER” LED should illuminate. Generate a burner demand; the burner should not fire and “Lockout 67
ILK OFF” should appear on the screen. Contact NTI for assistance if this does not happen.
2. Fill the boiler with water; the “LOW WATER” LED should turn off. Clear the Lockout from the display board; burner should fire.
3. With the burner firing, press the TEST button to simulate a low water condition; the amber “LOW WATER”
LED should illuminate and the burner should turn off.
Maintenance (LWCO)
Every Year – perform Step 3 from the Operational Test Procedure.
Every 5-years – Remove the LWCO and clean all surfaces in contact with water.
36
Tft Series Installation and Operation Instructions
│
Trinity
Near Boiler Piping (Tft60-110)
Figure 10-1(a)
Supply/Return Bottom (Tft60-110)
Figure 10-1(b)
Supply/Return Top (Tft60-110)
Auto Air-Vent
Auto Air-Vent
Pressure Relief
Valve
Inlet
Pressure Relief
Valve
Outlet
Pressure Gauge
Pressure Gauge
Outlet
Inlet
Pressure Relief
Valve (alternate location)
Pressure Relief
Valve (alternate location)
Figure 10-1(c)
Supply Top / Return Bottom (Tft60-110)
Auto Air-Vent
Pressure Relief
Valve
Inlet
Figure 10-1(d)
Supply Bottom / Return Top (Tft60-110)
Auto Air-Vent
Pressure Relief
Valve
Outlet
Pressure Gauge
Pressure Relief
Valve (alternate location)
Pressure Relief
Valve (alternate location)
Pressure Gauge
Outlet
I nlet
37
Trinity
│
Installation and Operation Instructions
Near Boiler Piping (Tft155-250)
Figure 10-2(a)
Supply/Return Bottom (Tft155-250)
Auto Air-Vent
Pressure Relief
Valve
Tft Series
Figure 10-2(b)
Supply/Return Top (Tft155-250)
Inlet
Auto Air-Vent
Pressure Relief
Valve
Pressure Gauge
Outlet
Inlet
Pressure Relief
Valve (alternate location)
Pressure Gauge
Outlet
Pressure Relief
Valve (alternate location)
Figure 10-2(c)
Supply Top / Return Bottom (Tft155-250)
Auto Air-Vent
Pressure Relief Valve
Pressure Gauge
Outlet
Figure 10-2(d)
Supply Bottom / Return Top (Tft155-250)
Inlet
Auto Air-Vent
Pressure Relief Valve
Inlet
Pressure Relief
Valve (alternate location)
Pressure Relief Valve
(alternate location)
Pressure Gauge
Outlet
38
Tft Series Installation and Operation Instructions
│
Trinity
Near Boiler Piping (Tft300-399)
Figure 10-3(a)
Supply/Return Bottom (Tft300-399)
Figure 10-3(b)
Supply/Return Top (Tft300-399)
Auto Air-Vent
Auto Air-Vent
Inlet
Pressure Relief
Valve
Pressure Relief
Valve
Pressure Gauge
Outlet
Inlet
Outlet
Pressure Gauge
Pressure Relief
Valve (alternate location)
Figure 10-3(c)
Supply Top / Return Bottom (Tft300-399)
Auto Air-Vent
Pressure Relief Valve
Pressure Gauge
Pressure Relief
Valve (alternate location)
Figure 10-3(d)
Supply Bottom / Return Top (Tft300-399)
Inlet
Auto Air-Vent
Pressure Relief
Valve
Outlet
Pressure Relief
Valve (alternate location)
Inlet
Pressure Gauge
Outlet
Pressure Relief
Valve (alternate location)
39
Trinity
│
Installation and Operation Instructions
Boiler System Plumbing
Tft Series
The Trinity Tft boiler uses a low mass heat exchanger that requires a minimum rate of forced water circulation any time the burner is operating (See Table 10-2 for minimum flow rate requirements). To ensure the minimum flow rate is attained, NTI strongly recommends installing the boiler in a “Primary/Secondary” plumbing configuration utilizing “Closely Spaced Tees” or a “Low Loss Header” to de-couple the Boiler-Primary loop from the System-Secondary loop(s). See the examples of Primary/Secondary Loop configurations in Figures 10-
5 and 10-6.
Table 10-2 Minimum Flow Rate Requirements
Model Flow (US gpm) Model Flow (US gpm)
Tft60 3 Tft155-250 7.5
Tft85-110 3.5 Tft300-399 12
System Components – As a minimum, a properly installed system will include the following major components identified in Table 10-3.
Table 10-3 System Major Component Checklist
Factory Supplied Field Supplied Components
Pressure Gauge
Auto Air Vent
Boiler Loop Circulator (Pump B in Figure 10-5 or Pump C in Figure 10-6)
DHW Loop Circulator (Pump A in Figure 10-5 and Figure 10-6, for applications utilizing and Indirect Fired Water Heater)
(CH Circulator - Pump C in Figure 10-5; Zone Circulators in Figure 10-6)
Central Air Removal Devices (i.e. Micro Bubbler or Air-Scoop)
Pressure Regulating “Fill Valve”
Backflow Preventer
Expansion Tank
Circulating Pumps – Trinity Tft boilers are equipped with three 120VAC pump outputs:
1. PUMP A
“DHW Pump” - operates during a Domestic Hot Water demand (DHW).
2. PUMP B
“Boiler Pump” - operates during any demand.
3. PUMP C
“CH Pump”
- operates during a Central Heat/Thermostat demand (THERMOSTAT).
Ensure pumps are oriented as per the manufacturers’ instructions. Wiring of these circulators will depend on the system configuration selected; see Figures 10-5 and 10-6. For further wiring details see Section 12.0.
Circulators responsible for forcing the water flow through the boiler must be sized according to Table 10-4. Pump recommendations are based on a Primary/Secondary plumbing configuration (see Figures 10-5 and 10-6) using the listed pipe size in the
Boiler-Primary Loop, with up to 50 equivalent feet of pipe length. The installer is responsible for sizing the boiler circulator(s) and piping for applications using non
Primary/Secondary plumbing; Figure 10-4 provides Head Loss curves for this purpose.
Failure to ensure the minimum water flow rate through the boiler when the burner is operating will result in “short-cycling”, reduced performance and operating efficiency, and may also cause overheating and premature failure which will void the warranty.
Failure to follow instructions may result in fire, property damage, serious injury or death.
40
Tft Series Installation and Operation Instructions
│
Trinity
Table 10-4 Circulator and Pipe Size Requirements
Model
Temp.
Rise (ºF)
Boiler Flow
Rate (GPM)
Boiler Head
Loss (ft)
Tft60
Tft85
Tft110
20
25
35
20
25
35
20
25
35
6
4
3
8
6
4
10
8
6
2.7
1.6
1.0
3.4
2.7
1.6
3.9
3.4
2.7
Minimum
Pipe Size
1”
¾”
¾”
1”
1”
¾”
1”
2
1”
1”
Tft155
20
25
35
14
11
8
5.3
3.9
3.1
Minimum Primary Loop Pump Size
(1)
B&G
NRF-9
NRF-22
NRF-22
NRF-22
Grundfos
NRF-22 UPS15-58 (2)
NRF-22 UPS15-58 (1)
UPS15-58 (1)
UPS15-58 (2)
UPS15-58 (2)
UPS15-58 (2)
1-1/4” NRF-25 (3) UPS26-99 (2)
1-1/4”
1”
NRF-22 UPS15-58 (3)
NRF-22 UPS15-58 (2)
Taco
005
005
005
007
NRF-22 UPS15-58 (2) 005
NRF-22 UPS15-58 (1) 005
NRF-22
(2)
UPS15-58 (3) 007
2
007
005
0011
007
007
Armstrong
Astro 30 (2)
Astro 30 (2)
Astro 30 (1)
Astro 30 (3)
Astro 30 (2)
Astro 30 (2)
Astro 30 (3)
(2)
Astro 30 (3)
Astro 30 (2)
E7
Astro 30 (3)
Astro 30 (3)
Tft175
Tft200
20
25
35
20
25
35
16
13
9
18
15
11
6.6
4.7
3.4
7.5
5.8
3.9
1-1/2” NRF-36 (2) UPS26-99 (2)
1-1/4” NRF-25 (3) UPS26-99 (2)
1”
NRF-22 UPS15-58 (3)
1-1/2” NRF-36 (2) UPS26-99 (2)
1-1/4” NRF-36 (2) UPS26-99 (2)
1-1/4” NRF-22 UPS15-58 (3)
0011
0010
007
0011
0011
007
E7
E7
Astro 30 (3)
E7
E7
Astro 30 (3)
Tft250
20
25
23
18
11.3
7.5
1-1/2” NRF-36 (3) UPS26-99 (3)
1-1/2” NRF-36 (2) UPS26-99 (2)
0013
0011
E8
E7
35
20
13
28
4.7
5.4
1-1/4” NRF-25 (3) UPS26-99 (2)
2”
NRF-36 (3) UPS26-99 (3)
1-1/2” NRF-36 (2) UPS26-99 (3)
0010
0012
E7
E8
Tft300
Tft399
25
35
20
25
22
16
37
29
4
3.1
8.2
5.7
0011
1-1/2” NRF-25 (3) UPS26-99 (2)
2”
2”
PL55
NRF-36 (3)
UPS26-150 (3) 2400-30
UPS26-99 (3)
0010
0012
E7
E7
E11
E8
35 21 3.9 1-1/2” NRF-36 (2) UPS26-99 (2) 0011 E7
Notes:
1
Pump sizing based on Primary/Secondary plumbing configuration with specified minimum pipe diameter with up to 50’ equivalent length.
2
Upsize piping to 1-1/4” if using Taco 007, Armstrong Astro 30 or B&G NRF-22; alternatively upsize circulator to 0010,
Astro 50 or NRF-25.
41
14
12
10
8
6
4
2
0
Trinity
│
Installation and Operation Instructions
Figure 10-4(a) Tft60-110 Head Loss Curve
6
3
2
1
0
5
4
2 4 6 8
Flow Rate (US gpm)
Figure 10-4(b) Tft155-250 Head Loss Curve
6 8 10 12 14 16
Flow Rate (US gpm)
18
Figure 10-4(c) Tft300-399 Head Loss Curve
10
8
10
20 22
12
Tft Series
24
42
2
0
6
4
10 12 14 16 18 20 22 24 26
Flow Rate (US gpm)
28 30 32 34 36 38
Tft Series Installation and Operation Instructions
│
Trinity
Air Removal – The boiler and system plumbing layout must be configured to promote the removal of air from the water. Air vents and bleeders must be strategically placed throughout the system to aid in purging the air from the system during commissioning of the boiler. The system must also employ the use of a strategically located air removal device, such as an air scoop or micro-bubbler, designed to remove the air from the water as it flows through the system.
Follow the installation instructions included with the air removal device when placing it in the system; air removal devices generally work better when placed higher in the system. Always locate air removal devices in areas of the system that have a guaranteed positive pressure, e.g., in close proximity to the water fill and expansion tank.
Trinity boilers are supplied with an automatic air removal device to aid in the purging of air from the boiler during the initial fill. Place this devise in the location indicated in
Figures 10-1 through 10-3.
Expansion Tank – The expansion tank must be sized in accordance with the water volume of the system as well as the firing rate of the appliance. It is important to locate the expansion tank, and make-up water fill, on the inlet side of any circulator in the system, as doing so will guarantee the lowest pressure in the system will be at least equal to the tank and make-up water pressure. See examples in Figures 10-5 and 10-6.
Ensure the expansion tank cannot become isolated from the boiler anytime the system is operating. Failure to follow these instructions may result in discharge of the Pressure
Relief Valve may result in property damage or personal injury.
The installation of flow checks, motorized valves or other shutoff devices (other than for the purpose of servicing) are not permitted between the location of the "Closely Spaced
Tees" and the expansion tank; see Figures 10-5 and 10-6.
Indirect Fired Water Heater – When installed as per Figure 10-6, the indirect fired water heater is in series with the boiler during a demand for DHW. Therefore, its head loss, along with the head loss of the boiler and associated piping, must be considered when sizing the circulator.
Figure 10-5: Single System Circulator Configuration - Often used in applications zoned with “Zone Valves”.
During a demand for central heat, the boiler energizes the System Circulator via the Central Heating (CH) pump output (PUMP C). The System Circulator must be sized to provide adequate circulation throughout the heating system. During a Domestic Hot Water (DHW) demand, the boiler de-energizes the System
Circulator (PUMP C) and energizes the DHW Circulator (Pump A). With this configuration the Boiler
Circulator is the only pump that causes flow through the boiler and it is powered during any demand via the boiler pump output (PUMP B). This circulator must be sized according to Table 10-4.
The piping configuration described above requires the Central Heating system and DHW system to be de-coupled from the “Primary Loop” via closely spaced tees (Figure 10-5).
Figure 10-6: Multiple System Circulator Configuration - Often used in applications with “Zone Circulators”.
This configuration requires the installation of a check valve located at each circulator. During a central heating demand the boiler energizes the Central Heat Circulator via the Central Heat pump output (PUMP C).
During a Domestic Hot Water (DHW) demand, the boiler de-energizes PUMP C and energizes the DHW
Circulator (Pump A). Both Pump A and C, used in this configuration, are responsible for water flow through the boiler and must be sized according to Table 10-4. Pump output, PUMP B is not used in this configuration.
Figures 10-5 and 10-6 illustrate typical piping systems. These piping schematics do not illustrate all of the required concepts and components required to have a proper installation. Concepts not shown include: prevention of thermal-siphoning (heat traps), isolation valves, drain and purge valves, etc. It is the responsibility of the installing contractor and system designer to determine which system best meets the need of the installation and to consider all aspects of a proper system design. Contractor modifications to these instructions may be required, based upon existing piping and system design.
43
Trinity
│
Installation and Operation Instructions
Figure 10-5 Primary/Secondary Plumbing
(Single System Circulator Configuration)
Water connection locations will vary between boiler models; refer to Figures 10-1 to 10-3.
Tft Series
44
Tft Series Installation and Operation Instructions
│
Trinity
Figure 10-6 Primary/Secondary Plumbing
(Multiple System Circulator Configuration)
Water connection locations will vary between boiler models; refer to Figures 10-1 to 10-3.
45
Trinity
│
Installation and Operation Instructions
11.0 LEAD LAG INSTRUCTIONS
Tft Series
Multiple Boiler Applications
The Tft controller has the internal capacity to stage or Lead-Lag up to 8 boilers configured in a cascade. This
Lead-Lag capability allows a designated “Master” boiler to communicate with and effectively control each boiler in a multiple boiler system. This function is accomplished by “Daisy Chaining” a 3-wire cable between each of the boilers and enabling the Master parameter in the boiler of your choice. The boiler with the Master parameter enabled becomes the single point of contact for Central Heating, Domestic Hot Water and Outdoor
Reset settings and control wiring. Use the instructions detailed in this section to set-up and install the cascade boiler system; reference Appendix A – Controller and Touchscreen Display Instructions for details on more advanced settings and for assistance with navigating the touchscreen display.
Figure 11-1 Multiple Boiler Lead-Lag Plumbing Configuration
Water connection locations will vary between boiler models; refer to Figures 10-1 to 10-3.
Master Boiler
Tft399 Models Illustrated
46
Tft Series Installation and Operation Instructions
│
Trinity
Lead Lag Instructions - Common
Plumbing – install as many as 8 Tft boilers in parallel in a primary/secondary plumbing configuration as illustrated in Figure 11-1. Size common piping as per Table 11-1.
Boiler Pump – each boiler must have its own circulator (see Figure 11-1) which is controlled by its PUMP B output; see Field Wiring Figure 12-1 and Table 12-1. The Boiler Pump must be sized according to Table 10-4.
Communication Wiring – using 3-wire cable, daisy-chain terminals DATA +, DATA – and DATA COM of each boiler in parallel; see Field Wiring Table 12-2a and Figure 12-2.
System Sensor (Optional) – install a system sensor (NTI P/N: 84010) on the outlet (supply) pipe feeding the heating system, see Figure 11-1. Wire the system sensor to SENSOR COM and SYSTEM of the Master
Boiler; see Field Wiring Table 12-2a and Figure 12-2. The system sensor automatically becomes the modulation sensor for the boiler system, i.e. the control attempts to achieve setpoint temperature at the location of the sensor. If a system sensor is NOT used, at the Master boiler set the applicable sensor input to
Unconfigured as follows:
Configure
– Sensor Configuration – S10 (J10-7) sensor
Outdoor Sensor (Optional) – wire the outdoor sensor to SENSOR COM and OUTDOOR of any one of the boilers in the cascade; see Field Wiring Table 12-2a and Figure 12-2. Note: only one outdoor sensor is needed for the multiple boiler system.
Modbus Address – assign a unique MB2 Modbus Address to each boiler in the cascade. Access the MB2
Modbus Address setting via the System Identification & Access menu as follows:
Configure
– System Identification & Access – MB2 Modbus Address
Master Enable – choose one (and only one) boiler in the cascade to be the Master, this boiler will receive all control wiring and will be used for setting control parameters (see steps below). On this one boiler, set
Master enable equal to Enabled via the Lead Lag Master Configuration menu, accessed as follows:
Configure
– Lead Lag Master Configuration – Master enable
Table 11-1 Minimum Pipe Sizes for Multiple Boiler Applications
# of
Units
2
3
4
5
6
7
8
Tft60 Tft85 Tft110 Tft155 Tft175 Tft200 Tft250 Tft300 Tft399
Pipe Size Pipe Size Pipe Size Pipe Size Pipe Size Pipe Size Pipe Size Pipe Size Pipe Size
1”
1-1/4”
1-1/2”
1-1/2”
2”
2”
2”
1-1/4”
1-1/2”
2”
2”
2”
2-1/2”
2-1/2”
1-1/2”
2”
2”
2-1/2”
2-1/2”
2-1/2”
3”
1-1/2”
2”
2-1/2”
2-1/2”
3”
3”
3”
2”
2”
2-1/2”
3”
3”
4”
4”
2”
2-1/2”
2-1/2”
3”
4”
4”
4”
2”
2-1/2”
3”
4”
4”
4”
4”
2-1/2”
3”
3”
4”
4”
4”
5”
2-1/2”
3”
3”
4”
5”
5”
5”
Note: Minimum pipe size based on assumed temperature rise of 25ºF at maximum firing rate.
47
Trinity
│
Installation and Operation Instructions
Lead Lag Instructions
– Central Heating
Tft Series
Central Heat Demand Switch (Room Thermostat) – connect to R (24VAC) and CH2 (LL) of the Master
Boiler; see Field Wiring Table 12-2b and Figure 12-2. Switch must be an isolated end switch (dry contact).
Central Heat Setpoint – at the Master boiler only, set the CH setpoint via the Lead Lag Master Configuration menu, accessed as follows:
Configure
– Lead Lag Master Configuration – CH setpoint
Outdoor Reset Settings – at the Master boiler only, set the Outdoor reset parameters via the Lead Lag Master
Configuration menu, accessed as follows:
Configure
– Lead Lag Master Configuration – Advanced Settings – Outdoor reset
CH Pump – one boiler in the cascade can be chosen to operate the Central Heating pump via its PUMP C output; see Field Wiring Figure 12-1 and Table 12-1. From the respective boiler display, check the box next to Use for Lead Lag Master demands for the CH Pump to ensure proper pump behavior. Menu access to the
CH Pump parameters is as follows:
Configure
– Pump Configuration – Central Heat pump – Use for Lead Lag Master demands
Lead Lag Instructions
– Domestic Hot Water
Tank Thermostat – connect to SENSOR COM and DHW of the Master Boiler; see Field Wiring Table 12-2a and Figure 12-2. Switch must be an isolated end switch (dry contact).
DHW Setpoint – at the Master boiler only, set the DHW setpoint via the Lead Lag Master Configuration menu, accessed as follows:
Configure
– Lead Lag Master Configuration – DHW setpoint
DHW switch (Lead Lag) – at the Master boiler only, set DHW switch equal to DHW (S6) sensor shorted via the
Lead Lag Master Configuration menu, accessed as follows:
Configure
– Lead Lag Master Configuration – Advanced Settings – Domestic Hot Water – DHW switch
DHW enable (Local) – at the Master boiler only, set DHW enable equal to Disabled via the Domestic Hot
Water Configuration menu, accessed as follows:
Configure
– Domestic Hot Water Configuration – DHW enable
DHW Pump – one boiler in the cascade can be chosen to operate the DHW pump via its PUMP A output; see
Field Wiring Table 12-2b and Figure 12-2. From the respective boiler display, check the box next to Use for
Lead Lag Master demands for the DHW Pump to ensure proper pump behavior. Menu access to the DHW
Pump parameters is as follows:
Configure
– Pump Configuration – DHW pump – Use for Lead Lag Master demands
Tank Sensor – when operating in a cascade system, the boiler controls do not support the use of a tank sensor; a tank thermostat (switch) must be used.
48
Tft Series Installation and Operation Instructions
│
Trinity
12.0 FIELD WIRING
All wiring must be in accordance with the Canadian Electrical code, CSA C22.2 and any applicable local codes.
Ensure that the wiring complies with this manual. The boiler must be electrically grounded in accordance with the National Electrical Code ANSI/NFPA 70, local codes, and/or the Canadian Electrical Code CSA C22.1.
Avoid Shocks - To Avoid Electrical Shock, turn off electrical power to the boiler prior to opening any electrical box within the unit. Ensure the power remains off while any wiring connections are being made. Failure to follow these instructions may result in component failure, serious injury or death.
Field Wiring - Wire grommets must be used to secure wiring and prevent chafing when passing wiring through the cabinet wall. Failure to follow instructions may damage unit.
Line Voltage Connections
Electrical rating for the Trinity Tft is 120V / 1 Phase / 60 Hz / 12A. All line voltage wiring connections to the
Trinity Tft are made at the junction box in the control panel located at the bottom of the boiler cabinet. The connections are accessed by removing the front door of the boiler, followed by the removal of the control panel cover. Field connections are to be installed in accordance with Figure 12-1 and Table 12-1. Holes are located on the bottom (underside) of the control panel junction box.
Fuses (120VAC) – The Trinity Tft is equipped with two 7 Amp fuses to protect 120VAC system components.
The fast-acting fuses are located on the left side of the control panel and are easily accessed upon removal of the front cover of the boiler cabinet.
Fuse A: Protects the blower, spark generator and PUMP B output circuits.
Fuse B: Protects PUMP A and PUMP C output circuits.
Wire Protection - When passing any wiring through the cabinet of the boiler, the installer must use wire grommets suitable for securing the wiring and preventing chafing.
Failure to follow instructions may result in component failure, serious injury or death.
Power Supply - The Trinity Tft is designed to be powered using a single phase 120VAC power supply that is fused (or protected via a circuit breaker) to allow a maximum of 15
Amps. Failure to follow instructions may result in component failure, serious injury or death.
Labeling - Label all wires prior to disconnecting them when servicing controls. Wiring errors can cause improper and dangerous operation. Failure to follow instructions may result in property damage or personal injury.
Continuity - Before connecting the line voltage wiring, perform a continuity check between all wires and ground to make sure that there are no electrical leaks that could blow a fuse or damage electrical components. Also check the polarity of the line and neutral wires. Line must measure 120VAC to ground; neutral must measure zero.
Failure to follow instructions may damage the unit.
Max Load - Circulator outputs (PUMP A, B, C) are each limited to operating a circulator with a maximum current load of 3 Amps or a maximum 1/6 hp motor. See
Table 12-1.
49
Trinity
│
Installation and Operation Instructions
Figure 12-1 Line Voltage Field Wiring
Tft Series
Table 12-1 Line Voltage Field Connections
Connection Location
L1
(120VAC)
1
Description
Location for connecting line voltage of the power supply. Note; most installation codes require the installation of a service switch to break line voltage to the appliance.
PUMP A 2 120VAC output to the DHW circulator; powered during a demand for DHW.
PUMP B
PUMP C
3
4
120VAC output to the Boiler circulator; powered during all demands; DHW, local Central
Heat (CH1) and Lead-Lag Central Heat [CH2 (LL)]. This output is not used for all plumbing configurations, see Section 10.0.
120VAC output to the Central Heating circulator; powered during a demand for local
Central Heat (CH1) or Lead-Lag Central Heat [CH2 (LL)].
5
L2
(Neutral)
6
Location for connecting neutral of the power supply and all circulators.
7
Ground Location for connecting earth ground and for grounding all of the circulators.
8
50
Tft Series Installation and Operation Instructions
│
Trinity
Low Voltage Connections
Like the line voltage, the low voltage wiring connections to the Trinity Tft are made at the junction box in the control panel located at the bottom of the boiler cabinet. The connections are accessed by removing the front door of the boiler, followed by the removal of the control panel cover. Field connections are to be installed in accordance with Figure 12-2 and Tables 12-2a and 12-2b. Holes are located on the bottom (underside) of the control panel junction box.
Fuse (24VAC) - Trinity Tft models are equipped with a “blade style” 2 Amp fuse to protect the internal transformer located within the control panel box.
Table 12-2a Low Voltage Field Connections (Communication and Sensor I/O)
Connection Location
DATA +
DATA -
DATA COM
1
2
3
Description
Lead-Lag
–
Terminals 1, 2 and 3 can be "daisy-chained" to multiple boilers (up to 8 in total) for the purpose of staging.
For lone boiler applications, these terminals can be alternatively used for communication to an external device (i.e. Building Automation System, BAS)
4-20mA (+)
4-20mA (-)
COM
4
5
6
External Modulation Control – Using a 4-20mA signal connected to terminals 4 and 5, an external control can be used to directly modulate the burner firing rate or adjust the active set point. This can be useful for applications using external staging controls or
Building Automation Systems.
Sensor Common
–
Common port for field inputs SYSTEM, OUTDOOR and DHW.
SYSTEM
OUTDOOR
DHW
7
8
9
System Water Temperature
–
An optional strap-on System Sensor is available from
NTI (P/N 84010). When connected to terminals 6 and 7, the control will indicate a “CH” or “Lead-Lag” temperature. Sensor can be used for direct modulation of system temperature.
Outdoor Temperature Sensor
–
A wall mountable OD Sensor is included with each boiler. When connected to terminals 6 and 8, the control will indicate the outdoor temperature and Outdoor Reset function will be operable.
DHW Tank Demand
–
Input requiring closure of terminals 6 and 9 to initiate a demand for DHW. Switch made via isolated end switch (dry contact) from a thermostat
(aquastat) located in an Indirect Fired Water Heater. Or optional DHW Tank Sensor
(NTI P/N 84632), see Appendix A for details.
Table 12-2b Low Voltage Field Connections (24VAC I/O)
Connection Location
COM
(24VAC)
1
Description
24VAC Common – Neutral for the 24VAC power supply from the boiler. COM can be used in conjunction with terminal R to provide a power source for a digital thermostat.
2
R
(24VAC)
3
24VAC Hot - Power supply for inputs LIM, CH1 and CH2 (LL).
LIM
CH1
CH2 (LL)
4
5
6
External Limit – Input requiring 24VAC from terminal R to permit the burner to operate.
Comes factory equipped with a jumper to the R terminal. For installations requiring the use of an additional safety switch, such as a Flow Switch, or auxiliary temperature limit, remove the factory installed jumper and install the normally open isolated contacts of the additional limit in its place.
Local Central Heat Demand
– Input requiring 24VAC from terminal R to initiate a
“local” CH call. Switch is made using an isolated end switch (dry contact) via thermostat, zone controller or other device. Typically used as the lone heat input or as the high temperature input in dual CH temperature systems.
Lead-Lag Central Heat Demand
–
Input requiring 24VAC from terminal R to initiate a
“lead-lag” CH call. Switch is made using an isolated end switch (dry contact) via thermostat, zone controller or other device. Typically used as a lead-lag input for cascaded boilers or as the low temperature input in dual CH temperature systems.
7
ALARM
8
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm condition. May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
51
Trinity
│
Installation and Operation Instructions Tft Series
Low Voltage Terminals
– “R” terminals 2 and 3 of the 24VAC I/O barrier has 24VAC potential from the internal transformer. Do not connect power from this terminal to any other terminal other than terminals 4, 5 and 6 (LIM, CH1 and CH2 (LL)). Failure to follow these instructions may damage the unit.
The low voltage connections are divided into two separate barrier strips: Communication and Sensor I/O (Input/Output) and 24VAC I/O. DO NOT connect 24VAC (or other power supply) to the Communication and Sensor I/O connections; doing so will cause control failure.
Figure 12-2 Low Voltage Field Wiring
Communication and Sensor I/O
24VAC I/O
52
Tft Series Installation and Operation Instructions
│
Trinity
Modbus Communication Connections
The Trinity Tft uses Modbus for communicating data to and from the boiler controller. Effectively the boiler incorporates three (3) Modbus communication ports:
1. Controller MB1 to Display COM1 – provides communication of all data between the boiler controller and the user interface (touch-screen display). Controller communication port “MB1” is factory wired to communication port “COM1” of the touch-screen display.
2. Controller MB2 to Field Terminals (see Table 12-2a; Locations 1-3) – allows for communication between boilers for the purpose of staging/cascading; as many as 8 boilers can be “daisy-chained” together.
For lone boiler applications, this port can be alternatively used for communication to an external device (i.e.
Building Automation System, BAS). Controller communication port “MB2” is factory wired to Low
Voltage field connections DATA (+), DATA (-), and DATA COM (see Figure 12-2).
3. Display COM2 – the new Tft touch-screen display provides a spare Modbus communication port; the extra port allows for dedicated communication to an external device (i.e. Building Automation System, BAS).
Display communication port “COM2” is accessed from the rear of the touch-screen display, see Figure 12-3 for wiring instructions. See Figure 16-3 for instructions on accessing the rear of the touch-screen display.
Figure 12-3 COM2 Modbus Wiring (Rear of Display)
53
Trinity
│
Installation and Operation Instructions
13.0 WIRING SCHEMATICS
Figure 13-1 Tft Connection Diagram
Tft Series
54
Tft Series Installation and Operation Instructions
│
Trinity
Figure 13-2 Tft Ladder/Logic Diagram
55
Trinity
│
Installation and Operation Instructions Tft Series
14.0 INSTALLATION CHECKLIST
Installation
1. If operating on Propane Gas, convert boiler using appropriate Kit number. See Table 7-1.
2. Locate the boiler in accordance with Section 3.0 of this manual.
3. Install the Vent/Air-inlet piping in accordance with Sections 4.0 and 5.0 of this manual. Ensure all joints are secured and cemented properly. Both the Vent and Air-inlet pipes must terminate outdoors.
Perform the Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.
4. Connect the condensate trap and drain in accordance with Section 6.0 of this manual.
5. Connect the gas supply in accordance with Section 7.0 of this manual.
6. Install the plumbing in accordance with this manual; Flush/cleanse the internals of the heating system.
Treat system water with Fernox F1 Protector when needed.
7. Connect field wiring in accordance with Section 12.0 of this manual.
8. Advise home/building owner of their responsibilities with respect to maintaining the boiler.
The building owner is responsible for keeping the Vent/Air-inlet termination free of snow, ice, or other potential blockages and for scheduling boiler routine maintenance as described in the next section. Failure to properly maintain the boiler may result in serious injury or death.
Start-up
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8 hours, first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for
Plastic Venting in Section 4.0.
Failure to follow these instructions can result in explosion, serious injury or death.
1. Turn gas shut-off valve to the ON position.
2. Turn Power on to the boiler.
3. Set Controller to the desired settings.
4. Turn thermostat up, Ignition will occur.
Operational Checklist
1. System is free of gas leaks.
2. System is free of water leaks.
3. Water pressure is maintained above 15 PSI.
4. All air is purged from the heating system piping.
5. Ensure proper water flow rate; unit must not kettle, bang, hiss or flash the water to steam.
6. Ensure gas line pressure is in accordance with Section 9.0.
7. System is free of combustion leaks.
8. Unit must operate smoothly.
9. Ensure the flue gas combustion readings are within the tolerances listed in Table 9-1.
10. Each ignition must be smooth.
11. Verify that all condensate lines are clean and drain freely.
Before Leaving
1. Remove line pressure gauge from gas valve, tighten bleed screw, test screw for leaks. See Section 9.0.
2. Install plug into the flue gas test port and test for leaks, see Section 9.0.
3. Allow the boiler to complete at least one heating cycle, or to operate for at least 15 minutes.
4. Always verify proper operation after servicing.
Instructions to Installing Contractor
1. Ensure that the customer receives the Warranty Documentation included with the installation manual.
2. Leave the manual with the customer so they know when to call for annual maintenance and inspection.
This boiler must have water flowing through it whenever the burner is firing. Failure to comply may damage the unit, void the warranty, and cause serious injury or death.
Allowing the boiler to operate with a dirty combustion chamber will adversely affect its operation and void the warranty. Failure to clean the heat exchanger on a frequency that matches the need of the application may result in fire, property damage, or death.
56
Tft Series Installation and Operation Instructions
│
Trinity
15.0 ANNUAL MAINTENANCE AND INSPECTION
This unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
1. Lighting is smooth and consistent, and the combustion fan is noise & vibration free.
2. The condensate drain freely flows, and is cleaned of sediment.
3. Relief Valve and air vents are not weeping.
4. Low water cut off is tested (remove and clean a minimum of once every 5 years, see Section 10.0)
5. Examine all venting for evidence of leaks. Ensure vent screens are cleaned and clear of debris.
6. Check the burner plate for signs of leaking.
7. The combustion chamber must be inspected and if necessary cleaned.
8. Keep boiler area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
9. Ensure there is nothing obstructing the flow of combustion and ventilation air.
10. Listen for water flow noises indicating a drop in boiler water flow rate.
Important - The hydronic system may need to be flushed to eliminate hard water scale
(Use Fernox DS-40 Descaler, NTI PN: 83450).
11. Verify proper operation after servicing.
Wiring Labels - Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Cleansers and Potable Water - Boiler system cleansers and corrosion inhibitors must not be used to flush contaminants from water heaters or potable water systems.
Combustion Chamber Cleaning Procedure
NTI recommends having the combustion chamber cleaned after the first year of operation, with subsequent cleanings scheduled based on the condition of the combustion chamber at the time. Units operating with LP Gas or in an industrial environment may require more frequent cleanings.
Crystalline Silica - Read carefully the warnings and handling instructions pertaining to
Refractory Ceramic Fibers before commencing any service work in the combustion chamber. Take all necessary precautions and use recommended personal protective equipment as required.
Cleaning Checklist
1. Remove the demand for heat, allow the post-purge cycle to finish, turn gas and power supply off.
2. Working inside the cabinet, disconnect the cabling to the combustion blower, gas valve, spark igniter and flame sensor, then remove the air-inlet piping and Gas Valve/Venturi assembly (gas line is disconnected at the factory supplied union fitting).
3. Once the combustion chamber has cooled, remove the combustion blower followed by the burner plate – be careful not to damage the insulation disc located underneath the burner plate.
4. Use a vacuum with a high efficiency filter to remove any loose debris or dust.
5. Remove the condensate trap from the bottom of the boiler and place a drain under the boiler condensate drain.
6. Wet the inside of the combustion chamber with warm water (do not use any chemicals). Use a garden hose with a trigger nozzle to direct pressurized water through the heat exchanger tubes; the water will exit via the condensate drain on the bottom. Continue process until the tubes are clear and the water runs clean. Use dry rags or plastic to protect electrical components from being damaged by dripping or spraying water.
7. Disassemble the condensate trap and thoroughly clean it; then reassemble and securely connect it to the boiler condensate drain, see Section 6.0.
8. Remove the burner from the burner plate; clean if necessary using compressed air. Reattach the burner; ensure the gasket is in perfect condition and is reinstalled (replace if necessary).
9. Inspect the insulation disc located on the under-side of the burner plate. Replace if damaged.
10. Re-install the burner plate; be sure the insulation disc is properly aligned. Reinstall remaining components in the opposite order they were removed.
11. Perform the Start-up and Operational Checklist detailed in the previous section.
Replace any gaskets or insulation discs that show any signs of damage and do not re-use.
Failure to follow these instructions may result in fire, property damage or death.
57
Trinity
│
Installation and Operation Instructions Tft Series
Refractory Ceramic Fibers (RFC)
Personal Protective Equipment Recommended - Read the following warnings and handling instructions carefully before commencing any service work in the combustion chamber. The insulating material on the inside of the burner plate contains Refractory
Ceramic Fibers and should not be handled without personal protective equipment.
Potential Carcinogen - Use of Refractory Ceramic Fibers in high temperature applications (above 1000 o
C) can result in the formation of Crystalline Silica
(cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational carcinogen by the following regulatory organizations: International Agency for Research on Cancer (IARC),
Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration
(OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling instructions in Table 15-1 may result in serious injury or death.
Crystalline Silica - Certain components confined in the combustion chamber may contain this potential carcinogen. Improper installation, adjustment, alteration, service or maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Table 15-1 for handling instruction and recommended personal protective equipment. Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the supplied instructions before installing, servicing, or removing this boiler. This boiler contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Table 15-1 Handling Instructions for Refractory Ceramic Fibers (RCF)
Reduce the Risk of Exposure Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes
Wear long-sleeved clothing, gloves, and safety goggles or glasses .
Avoid breathing in silica dust
Avoid transferring contamination
Wear a respirator with an N95-rated filter efficiency or better.
1
Use water to reduce airborne dust levels when cleaning the combustion chamber.
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
When installing or removing RFCs, place the material in a sealable plastic bag.
Remove contaminated clothing after use. Store in sealable container until cleaned.
Wash contaminated clothing separately from other laundry.
First Aid Measures If irritation persists after implementing first aid measures consult a physician.
Skin - Wash with soap and water.
Eyes - Do not rub eyes; flush with water immediately.
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated passage ways.
Notes:
1
R espirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling, and disposal of RCFs.
For more information on Refractory Ceramic Fibers, the risks, recommended handling procedures and acceptable disposal practices contact the organization(s) listed below:
Canada (CCOHS): Telephone directory listing under Government Blue Pages Canada—Health and
Safety—Canadian Centre for Occupational Health and Safety; or website http://www.ccohs.ca.
United States (OSHA): Telephone directory listing under United States Government—Department of
Labor—Occupational Safety and Health
Administration; or website http://www.osha.gov.
58
Tft Series Installation and Operation Instructions
│
Trinity
16.0 TROUBLESHOOTING
Observe the following precautions when servicing the boiler. Failure to comply with
Servicing the Boiler
these may result in fire, property damage, serious injury or death.
Disconnect or shutoff all energy sources to the boiler: 120VAC power, water and gas.
Identify and mark wires before disconnecting or removing them.
Never bypass electrical fuses or limit devices except temporarily for testing.
Use proper personal protective equipment (PPE) i.e. eye protection, safety footwear.
These procedures should only be performed by qualified service personnel, when abnormal operation of the boiler is suspected. The boiler incorporates a sophisticated microprocessor based control which normally responds appropriately to varying conditions. If the boiler operation appears to be incorrect, or it is not responding at all to a demand for heat, the following is suggested to determine and correct the problem.
Before undertaking any troubleshooting procedures it is highly recommended to have available a digital multimeter(s) capable of measuring AC and DC volts, Amperes,
Resistance (Ohms) and Continuity.
Check 120VAC and 24VAC at the Boiler
First, verify the following:
There is 120V being supplied to the boiler: o
The circuit breaker in the electrical panel supplying power to the boiler is not tripped. o
The service switch (if applicable) is in the ON position. o
The boiler service switch located on the front of the boiler is in the ON (1) position
There is a heat call from the thermostat: o
Verify 24VAC to thermostat. o
The thermostat is placed at a sufficiently high setting to create a call for heat to the boiler.
To check for the presence of 120VAC and 24VAC at the boiler follow this procedure:
Remove the boiler front cover (remove screw from bottom, undo side latches, then lift cover up and off0.
120VAC o Remove the control panel cover. Loosen the three #8 hex-head sheet metal screws securing the cover to the control panel (one on the bottom, and one on each side). Lift the cover off and remove it from the unit; this will expose the field wiring barrier strips. o With an AC voltmeter set on the appropriate scale, measure the voltage across the L1 and L2 terminals
(terminals 1 and 5). o If 120VAC is not detected, check the electrical service as suggested above. If the service is verified, inspect the circuit wiring from the panel to the boiler for broken or disconnected conductors. o If 120VAC is detected, turn power off to the boiler at the service switch and check the 120VAC fuse located on the right side of the control panel; refer to Figure 16-1 – replace if necessary.
24VAC (only check if 120VAC supply is verified). o
Remove the control panel cover. Loosen the three #8 hex-head sheet metal screws securing the cover to the control panel (one on the bottom, and one on each side). Lift the cover off and remove it from the unit; this will expose the field wiring barrier strips. o
With an AC voltmeter set on the appropriate scale, measure the voltage between the R and COM terminals (terminals 1 and 2). o
If 24VAC is not detected, check the 24VAC fuse located at the transformer in the control panel; refer to
Figure 16-1 – replace if necessary.
Only replace fuses with identical parts, see Figure 16-1. Failure to follow this warning may result in component failure, fire, property damage, serious injury or death.
59
Trinity
│
Installation and Operation Instructions
Figure 16-1 Tft Control Panel
Figure 14-1 Tft Model
Fuses “A” and “B” 3AG
7A 250 Fast-Acting
Tft Series
Fuse “C” ATO 2A
32V Auto Blade Type
Control Panel Cover
Control Panel
Fuses
The Trinity Tft is equipped with three (3) fuses. Check these fuses before replacing the controller or any other electrical component; if the fuse is blown, it will prevent the protected device(s) from functioning.
To check, and if necessary replace, the fuses:
Remove all 120VAC power from the appliance. Be careful to check that the unit is not powered from more than one source e.g. a UPS (uninterruptible power supply).
Remove the front cover.
Fuses "A" and "B" are accessible by removing the spring-loaded knurled knob of their respective holders.
Push the knob toward the panel, and twist approximately 1/4 turn counter-clockwise.
Fuse "C" is an auto blade type and is installed in an “inline” fuse holder; gain access by removing the control panel cover.
After inspecting and if necessary replacing fuses, replace the panel cover and front cover. Restore power to the appliance and confirm proper operation.
Only replace fuses with identical parts, see Figure 16-1. Failure to follow this warning may result in component failure, fire, property damage, serious injury or death.
User Interface (Touch-screen Display)
A blank screen does not necessarily indicate a problem; the display may be configured to automatically blank the screen after a pre-set interval. Simply touch the screen to activate it. Confirm that 120VAC is being supplied to the appliance and that the service switch located below the display is turned ON (1). If the screen does not become active, perform the following procedure:
Blank Screen
1. Remove the front cover from the boiler.
2. Remove the control panel cover and check Fuse “C” (Auto Blade Type); if faulty check for shorts in the thermostat wiring, correct, then replace fuse (see Figure 16-1).
3. Ensure the “2 by 2” Molex connector, located behind the display at the top, is connected and that the wires are fully inserted (see Figures 16-2 and 16-3). Verify that 24VAC is present between the Blue and Red wires; if not trace wiring back to 24VAC transformer; correct wiring and/or replace transformer (see Figure
13-1).
4. Remove the display assembly from the control panel and check the 24VAC wiring connection on the back of the display; Blue to terminal 7 [24VAC (COM)], Red to terminal 8 [24VAC] (see Figure 16-3).
60
Tft Series Installation and Operation Instructions
│
Trinity
System Disconnected
If the Touch-screen Display is not blank, but is displaying “System Disconnected!” in the middle of the screen, ensure the 4 by 1 Molex connector, located behind the display at the top, is connected and that the wires are fully inserted (see Figures 16-2 and 16-3). If the connector appears to be fine, check the wiring connections on the back of the touch-screen display (remove display assembly, see Figure 16-3); Green, Red and Black go to terminals 1, 2 and 3 respectfully.
Figure 16-2 Touch-screen Display Electrical Disconnects
Power Supply Connector (2 by 2) Communication Connector (4 by 1)
Black
Blue (White on bottom)
Green
Red
Black
Red
White
Blue
Green
Red
Figure 16-3 Display Electrical Connection Access
Red
Black
Connectors Located
Behind Display at Top
Access the electrical connections in the back of the display by removing the screws securing the display assembly to the control panel.
61
Trinity
│
Installation and Operation Instructions Tft Series
Summary and Diagnostics Display –
The Trinity Tft controller and Touch-screen display provides detailed operational and diagnostic information for aid in troubleshooting. When power is applied to the appliance the initial page displayed is the Summary page. Information presented on the Summary page includes Demand source, Burner state, status of sensors and pumps, and so forth. Any current Alert or Lockout condition is also displayed. Accessible from the Summary page are the Configuration, Diagnostics, Details and History pages.
Refer to Appendix A - Controller and Touchscreen Display Instructions for more information.
Lockout and Alert History – The controller maintains a record of the fifteen (15) most recent events for both
Lockouts and Alerts. To display the logs, touch the History button on the Summary page (refer to Appendix
A - Controller and Touchscreen Display Instructions). In any situation where a malfunction is suspected, always check the Alerts and Lockouts history. Entries recorded in the history provide useful information for determining the cause of the malfunction.
Table 16-1 Troubleshooting Chart
PROBLEM
Display shows “System
Disconnected!” constantly
Burner not operating
Lockout 2 – Waiting for safety data verification
Lockout 9 – Flame bias out of range
POSSIBLE CAUSE CORRECTIVE ACTION
Communication wire disconnected
See, “System Disconnected!” above.
Faulty Sola controller If 24VAC present at Sola controller terminals J8 1
& 2, check Power LED on Sola controller. Verify that connector J8 is securely plugged into the Sola controller. Recycle power to appliance, if Sola controller does not operate, replace the Sola controller.
Heat demand satisfied; no call for heat
Check Demand and Setpoints via Touchscreen.
Check thermostat and DHW aquastat settings (as applicable).
Appliance outlet temperature exceeds “Setpoint - On Hysteresis”
Hold, Delay or Lockout
Burner switch off
Safety parameter(s) has been adjusted
4-20mA input being overdriven.
Control malfunction
Check outlet temperature, setpoint and hysteresis settings via Touchscreen.
Check Summary page on Touchscreen for code.
Check Summary page, if Demand indicates
“Burner switch off” go to diagnostics burner test page and switch on.
Changing settings that are considered safety parameters require “Safety data verification”.
Refer to Appendix A.
If using 4-20mA input, check to ensure current is not greater than 21mA.
Cycle power, if problem returns replace control.
Hold 27 – Flame sensor shorted to ground detected
Hold 61 – Anti short-cycle
Hold 62 – Fan speed not proved
Hold 63 – LCI OFF (Limit control input)
A flame circuit shorted to ground may show up as a flame circuit timeout. Zero-Ohm shorts can display as Hold 27.
Normal operation
Normal Operation (Drive to
Lightoff)
Blown fuse
Wiring defect
- Faulty Sola controller
- Faulty Blower
Incorrect Sola controller.
Check to ensure condensate drain is not blocked.
Check to ensure no external voltage is applied to
R & CH terminals. If using 4-20mA input, check to ensure current is not greater than 21mA.
Allow timer to expire, or reduce Anti short-cycle setting as needed (See Appendix A)
Hold 62 is momentarily displayed prior to burner ignition during the Drive to Lightoff.
Check Fuse
"
A
"
, blown fuse prevents blower from operating.
Inspect blower wiring, ensure connectors at Sola controller and blower are securely attached.
If Hold 62 persists for 15 seconds or more, while the blower is running, check
"
Fan speed
" indicated on display. If
"
LOW RPM
"
,
"
HIGH
RPM
", “0”
or rapidly changing RPM value is displayed, try connecting another Sola controller.
If problem remains, replace blower.
Replace control with correct model (Replacement part number 77777)
62
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Hold 65 – Interrupted Air
Switch OFF
Hold 66 – Interrupted air switch ON
Incorrect Sola controller.
Incorrect Sola controller.
Hold / Lockout 67 – ILK OFF Low Water Condition
External Limit Tripped
Lockout or Hold 79 – Outlet
High Limit
Lockout or Hold 81 – Delta T limit
OR
Appliance making banging or hissing sounds
CH or DHW settings
Replace control with correct model (Replacement part number 77777)
Replace control with correct model (Replacement part number 77777)
Check operation of internal LWCO.
Indication that an external limit (wired to “LIM”) is open. Not a problem with boiler, check external limit.
Check if CH and/or DHW setpoint temperature plus off hysteresis exceed “High limit” setpoint – factory setting = 200°F (93°C).
CH or DHW pump problem
See
"
Inoperative CH or DHW pump
"
below.
Incorrect “Outlet high limit” setting Increase “Outlet high limit” setting; maximum setting = 200°F (93°C).
Incorrect “Outlet high limit response” setting
Insufficient water flow
Unless deemed unacceptable by local installation codes, the “Outlet high limit response” should be set to “recycle and hold” to prevent lockout.
Check Fuse
"B"
Check appliance pump.
Ensure plumbing is correct. Refer to Section
10.0 System Piping. Check that water pressure
Lockout 82 – Stack limit
Lockout or Hold 85 –
Inlet/Outlet Inversion Limit
Dirty heat exchanger
Incorrect “Stack limit setpoint”
Faulty sensor
Pump flowing in the wrong direction
Incorrect factory sensor wiring
Insufficient water flow is at least 15PSI.
Boiler heat transfer surfaces may be fouled with scale or magnetite. Clean with Fernox
DS-40 Descaler and Cleanser. See Table 10-1.
Inspect and if required clean the combustion chamber and/or heat exchanger. Refer to Section
14.0 Annual Maintenance and Inspection and
Section 10.0 Boiler and Heating System Piping.
Unless installed in Canada with PVC exhaust venting, set “Stack limit setpoint” to maximum setting of 220ºF (104ºC). In Canada PVC exhaust venting is limited to 149ºF (65ºC).
Check resistance of sensor and compare to thermistor resistance chart, see Table 16-2.
Ensure water circulation through the boiler is in the correct direction, see Figure 10-1.
Disconnect flue sensor cable; screen should display “Hold 95 – Stack sensor fault”; if not contact NTI.
See Lockout or Hold 81. Lockout or Hold 88 – Outlet
T Rise limit
Hold 91– Inlet sensor fault Sensor disconnected
Faulty sensor
Hold 92 – Outlet sensor fault Sensor disconnected
Faulty sensor
Hold 95 – Stack sensor fault Sensor disconnected
Check sensor connection located on the bottom of the heat exchanger. Check connection on control board.
Check resistance of sensor and compare to thermistor resistance chart, see Table 16-2.
Check sensor connection located on the top of the heat exchanger. Check connection on control board.
Check resistance of sensor and compare to thermistor resistance chart, see Table 16-2. (Note the Outlet sensor incorporates two sensors, check resistance individually.)
Check sensor connection located at the bottom of the flue pipe inside the boiler cabinet. Check connection on control board.
63
Trinity
│
Installation and Operation Instructions
Table 16-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE
Hold 95 – Stack sensor fault Faulty sensor
Lockout 109 or Hold 110 –
Ignition failure occurred
(failure to prove flame after 3 ignition attempts)
Lockout 113 – Flame circuit timeout
Lockout 122 – Lightoff rate proving failed
Alert 128 - Modulation rate was limited due to IAS open
Hold 137 – ILK failed to close
Spark cable disconnected
Blocked venting
Blocked condensate drain.
Insufficient gas line pressure
Flame rod disconnected
No 120VAC to Spark Generator
Faulty Spark Generator
No 24VAC to Gas Valve
Faulty Gas Valve
A flame circuit shorted to ground may show up as a flame circuit timeout. High resistance shorts can display as Lockout 113.
Blower is not turning on
Missing or incorrect blower feedback signal
Blower is always on
Incorrect Sola controller.
See Hold / Lockout 67
Tft Series
CORRECTIVE ACTION
Check resistance of sensor and compare to thermistor resistance chart, see Table 16-2. (Note the Outlet sensor incorporates two sensors, check resistance individually.)
Ensure that the high voltage spark cable is securely connected to the spark generator and the igniter electrode. Check that the green ground wire is securely attached to the ¼” quick connect tab on the igniter electrode.
Check for blockage of the exhaust-vent, air-inlet, combustion blower, gas valve venturi, burner heat exchanger etc.
Clean condensate trap, inspect condensate drain for blockages and build-up – correct accordingly.
Ensure the manual gas shutoff valve is open.
Refer to Section 9.0 GAS VALVE AND
BURNER SETUP.
Verify that the flame rod signal wire is securely attached to the flame rod and the Sola controller.
Check wiring from Sola controller to spark generator. With an AC voltmeter measure voltage across J5-6 and ground (the Sola controller chassis is connected to the 120VAC supply ground) during trial for ignition.
During trial for ignition check for arc on spark electrode via the observation port located next to the spark electrode in the burner door. If the spark generator is receiving 120VAC and no spark is observed, replace the spark generator.
Check the wiring harness for loose or interrupted connections of the gas valve wiring. With an AC voltmeter, measure the voltage between Sola controller terminals J5-2 to J4-10. There should be
24VAC present during trial for ignition, if not replace Sola controller.
The gas valve emits an audible click when it switches on or off. If the Sola controller is providing 24VAC to the gas valve, and the wiring is intact, it should be possible to detect if the valve is responding.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage is applied to R & CH terminals. If using 4-20mA input, check to ensure current is not greater than 21mA.
See “Blower not operating” below.
See Hold 62 above.
See “Blower operating at high speed while burner is off” below.
Replace control with correct model.
64
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE
Lockout 138 – Flame too low Blocked venting
Fowled or faulty flame sensor
Incorrect combustion settings
CORRECTIVE ACTION
Check for blockage of the exhaust-vent, Air-inlet, combustion blower, gas valve venturi, heat exchanger etc.
Inspect flame sensor for cracks of fowling, clean or replace as necessary.
Check combustion settings, correct accordingly.
Lockout 173 - Pilot relay feedback incorrect
Lockout 174 – Safety relay feedback incorrect
Alert 206 – Lead Lag header temperature was invalid
Alert 233 – Lead Lag outdoor temperature was invalid
External Electrical Noise Look for sources of electrical noise, i.e. a large motor or multiple pieces of equipment starting at the same time.
Failing Limit Switch in ILK circuit Check operation of internal LWCO, and/or external limit (i.e. devise connected between “R” and “LIM”); replace as necessary
Hardware failure of Sola controller Reset power, If problem persists replace Sola controller.
System Sensor not connected
See Alert 248
If desired, install System Sensor and wire to
SENSOR input connections “SYSTEM” and
“COM”. Otherwise ignore Alert 206
Alert 248 – CH outdoor temperature was invalid
Outdoor sensor not connected
Alert 448 – Flame too low
Alert 449 – Modulation rate was limited due to flame strength
Inoperative CH and/or DHW pump
Blower operating at high speed while burner is off
Outdoor sensor wiring
Faulty sensor
Blocked venting, dirty heat exchanger, failing flame sensor, poor combustion settings.
Normal operation
Blown fuse
Faulty Sola controller
Faulty pump
Blower signal cable disconnected
No 24VAC to Sola controller
The Trinity Tft is factory set with Outdoor Reset enabled. Connect outdoor sensor or disable
Outdoor Reset.
Check wiring of outdoor sensor. Wires should connect to SENSOR inputs “OUTDOOR” and
“COM”.
Check sensor. Should be free of ice and snow.
Check resistance of sensor and compare to thermistor resistance chart, see Table 16-2.
Indicates that the burner had to shut down due to insufficient flame signal. If Alert persists, refer to
Lockout 138.
Indicates that the minimum permissible modulation rate was temporarily increased due to low flame signal strength. If Alert persists, refer to Lockout 138.
Check Fuse
"
B
"
.
If Fuse “B” not blown, and Sola controller is operating, navigate to pump diagnostic on display.
Manually switch pump on, check for 120VAC at pump connection terminal on line voltage barrier strip. If 120VAC not detected, replace Sola controller.
If 120VAC supplied to pump, and pump does not operate, replace pump.
Verify that the 5-position Molex connector on the wiring harness is securely connected to its mating connector on the blower.
Check that the 4-position Molex connector on wiring harness is securely connected to its mating connector on the Sola controller.
Check Power LED on Sola controller.
Check Fuse "
C
"
.
With an AC voltmeter measure voltage at terminals J8 1 & 2, 24VAC should be present.
65
Trinity
│
Installation and Operation Instructions
Table 16-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE
Blower power disconnected Blower not operating
Blown fuse
Faulty blower
Tft Series
CORRECTIVE ACTION
Verify that the 3-position Molex connector on the wiring harness is securely connected to its mating connector on the blower.
Check Fuse
"
A
"
using the procedure described above. Fuse
"
A
"
protects the blower as well as the ignition spark generator and appliance pump.
Measure voltage across pins 1 & 2 (black and white wires) of 3-position connector on wiring harness. If 120VAC detected, reconnect then and remove 5-position signal connector. Blower should rotate at high speed. If blower does not rotate, replace blower.
Table 16-2 Thermistor Resistance vs. Temperature
Temp °F (°C)
Resistance Ohms (Ω)
Temp °F (°C)
Resistance Ohms (Ω)
-22 (-30)
-4 (-20)
14 (-10)
32 (0)
41 (5)
50 (10)
59 (15)
68 (20)
77 (25)
86 (30)
95 (35)
104 (40)
113 (45)
176,133
96,761
55,218
32,650
25,390
19,900
15,710
12,490
10,000
8,057
6,531
5,327
4,369
122 (50)
131 (55)
140 (60)
149 (65)
158 (70)
167 (75)
176 (80)
185 (85)
194 (90)
203 (95)
212 (100)
230 (110)
-
3,603
2,986
2,488
2,083
1,752
1,481
1,258
1,072
918
789
680
506
-
Table 16-3 Hold and Lockout Codes
Code Description
0
1
2
None
Unconfigured safety data
Waiting for safety data verification
3
4
5
6
7
Internal fault: Hardware fault
Internal fault: Safety Relay key feedback error
Internal fault: Unstable power (DCDC) output
Internal fault: Invalid processor clock
Internal fault: Safety relay drive error
8
9
Internal fault: Zero crossing not detected
Internal fault: Flame bias out of range
10
11
Internal fault: Invalid Burner control state
Internal fault: Invalid Burner control state flag
12
13
14
15
16
17
Internal fault: Safety relay drive cap short
Internal fault: PII shorted to ILK
Internal fault: HFS shorted to LCI
Internal fault: Safety relay test failed due to feedback ON
Internal fault: Safety relay test failed due to safety relay OFF
Internal fault: Safety relay test failed due to safety relay not OFF
66
Note
Hold / No lockout
Lockout
Lockout
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Lockout
Lockout
Hold
Hold / Lockout
Hold / Lockout
Lockout
Lockout
Lockout
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-3 Hold and Lockout Codes
Code Description
18
Internal fault: Safety relay test failed due to feedback not ON
19
20
Internal fault: Safety RAM write
Internal fault: Flame ripple and overflow
21
22
23
24
25
26
27
Internal fault: Flame number of sample mismatch
Internal fault: Flame bias out of range
Internal fault: Bias changed since heating cycle starts
Internal fault: Spark voltage stuck low or high
Internal fault: Spark voltage changed too much during flame sensing time
Internal fault: Static flame ripple
Internal fault: Flame rod shorted to ground detected
28
29
Internal fault: A/D linearity test fails
Internal fault: Flame bias cannot be set in range
30
31
Internal fault: Flame bias shorted to adjacent pin
Internal fault: SLO electronics unknown error
32
33
34
35
36
Internal fault: Safety Key 0
Internal fault: Safety Key 1
Internal fault: Safety Key 2
Internal fault: Safety Key 3
Internal fault: Safety Key 4
37
38
Internal fault: Safety Key 5
Internal fault: Safety Key 6
39
40
41
42
43
44
45
65
66
Internal fault: Safety Key 7
Internal fault: Safety Key 8
Internal fault: Safety Key 9
Internal fault: Safety Key 10
Internal fault: Safety Key 11
Internal fault: Safety Key 12
Internal fault: Safety Key 13
46
47
64
Internal fault: Safety Key 14
Flame rod to ground leakage
48
49
58
59
Static flame (not flickering)
24VAC voltage low/high
50
51
Modulation fault
Pump fault
52
Motor tachometer fault
53
54
AC inputs phase reversed
Safety GVT model ID doesn’t match application’s model ID
55
Application configuration data block CRC errors
56-57
RESERVED
Internal fault: HFS shorted to IAS
Internal fault: Mux pin shorted
60
61
62
63
Internal fault: HFS shorted to LFS
Anti short cycle
Fan speed not proved
LCI OFF
PII OFF
Interrupted Airflow Switch OFF
Interrupted Airflow Switch ON
67
ILK OFF
Note
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Hold
Lockout
Lockout
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Lockout
Hold
Hold
Hold
Hold
Hold
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Hold
Hold
Hold
N/A
Hold
Hold
Hold
67
Trinity
│
Installation and Operation Instructions
Table 16-3 Hold and Lockout Codes
Code Description
68
83
84
ILK ON
69
70
Pilot test hold
Wait for leakage test completion
71
Input power frequency mismatch
72-77
RESERVED
78
Demand lost in run
79
Outlet high limit
80
DHW high limit
81
Delta T limit
82
Stack limit
Delta T exchanger/outlet limit
Delta T inlet/exchanger limit
85
86
87
88
89
90
91
Inlet/Outlet inversion limit (See Table 17-1)
Exchanger/outlet inversion limit
Inlet/exchanger inversion limit
Outlet T-Rise limit (See Table 17-1)
Exchanger T-rise limit
Heat exchanger high limit
Inlet sensor fault
92
93
105
106
Outlet sensor fault
DHW sensor fault
94
95
96
97
98
99
100
Header sensor fault
Stack sensor fault
Outdoor sensor fault
Internal fault: A2D mismatch
Internal fault: Exceeded VSNSR voltage tolerance
Internal fault: Exceeded 28V voltage tolerance
Pressure sensor fault
101
Exchanger sensor fault
102-104
RESERVED
Flame detected out of sequence
Flame lost in MFEP
107
108
121
Flame lost early in run
Flame lost in run
109
110
111
112
113
Ignition failed
Ignition failure occurred
Flame current lower than WEAK threshold
Pilot test flame timeout
Flame circuit timeout
114-115
RESERVED
116
Wait for OK to Run
117
118
119
120
Flap valve condensate fault
Controller interaction system fault
Controller interaction communications fault
Flap valve backflow fault
Flap valve fault
122
123
Light off rate proving failed
Purge rate proving failed
124
High fire switch OFF
68
Tft Series
Note
Lockout
Disabled
Disabled
Hold
Hold
Hold
Hold
Hold
Hold
Lockout
Lockout
Lockout
Hold
Disabled
N/A
Hold
Hold
Lockout
Hold
Hold
Disabled
Hold / Lockout
Lockout
Disabled
Disabled
Hold
Disabled
Disabled
Hold / Lockout
Lockout
Lockout
Lockout
Lockout
Hold
Hold
Lockout
Lockout
Disabled
Disabled
Hold
Hold
Disabled
Disabled
Lockout
Lockout
Hold
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-3 Hold and Lockout Codes
Code Description
125
High fire switch stuck ON
126
127
Low fire switch OFF
Low fire switch stuck ON
128
Fan speed failed during pre-purge
129
Fan speed failed during pre-ignition
130
Fan speed failed during ignition
131
136
Fan movement detected during standby
132
Fan speed failed during run
133-135
RESERVED
Interrupted Airflow Switch failed to close
137
138
ILK failed to close
Flame too low
139-142
RESERVED
143
Internal fault: Flame bias out of range 1
144
145
146
147
148
Internal fault: Flame bias out of range 2
Internal fault: Flame bias out of range 3
Internal fault: Flame bias out of range 4
Internal fault: Flame bias out of range 5
Internal fault: Flame bias out of range 6
149
150
Flame detected
Flame not detected
151
152
153
154
155
156
157
High fire switch ON
Combustion pressure ON
Combustion pressure OFF
Purge fan switch ON
Purge fan switch OFF
Combustion pressure and Flame ON
Combustion pressure and Flame OFF
158
159
Main valve ON
Main valve OFF
160
161
171
172
Ignition ON
Ignition OFF
162
163
Pilot valve ON
Pilot valve OFF
164
169
Block intake ON
165
Block intake OFF
166-168
RESERVED
Safety opto bad in test state
170
Safety relay opto feedback incorrect
Safety relay feedback incorrect in run
Main relay feedback incorrect
173
174
175
176
177
Pilot relay feedback incorrect
Safety relay feedback incorrect
Safety relay open
Main relay ON at safe start check
Pilot relay ON at safe start check
178
Safety relay ON at safe start check
179-180
RESERVED
181
Invalid Blocked condensate enable setting
Note
Hold
Hold
Hold
Hold / Lockout
Hold / Lockout
Hold / Lockout
Hold
Hold
Hold
Hold
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Hold / Lockout
Hold
Hold / Lockout
Hold / Lockout
Hold / Lockout
Hold / Lockout
Hold / Lockout
Hold / Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Disabled
69
Trinity
│
Installation and Operation Instructions
Table 16-3 Hold and Lockout Codes
Code Description
205
206
207
208
209
210
211
212
213
196
197
198
199
200
201
202
203
204
189
190
191
192
193
194
195
182
183
184
185
186
187
188
221
222
223
224
225
226
227
214
215
216
217
218
219
220
228
229
230
Invalid J7-1 configuration, both LFS and Blocked condensate
Invalid J7-2 configuration, both HFS and Flap valve
Invalid BLOWER/HSI output setting
Invalid Delta T limit enable setting
Invalid Delta T limit response setting
Invalid DHW high limit enable setting
Invalid DHW high limit response setting
Invalid Flame sensor type setting
Invalid interrupted air switch enable setting
Invalid interrupted air switch start check enable setting
Invalid Igniter on during setting
Invalid Ignite failure delay setting
Invalid Ignite failure response setting
Invalid Ignite failure retries setting
Invalid Ignition source setting
Invalid Interlock open response setting
Invalid Interlock start check setting
Invalid LCI enable setting
Invalid light off rate setting
Invalid Light off rate proving setting
Invalid Main Flame Establishing Period time setting
Invalid MFEP flame failure response setting
Invalid NTC sensor type setting
Invalid Outlet high limit response setting
Invalid Pilot Flame Establishing Period setting
Invalid PII enable setting
Invalid pilot test hold setting
Invalid Pilot type setting
Invalid Post-purge time setting
Invalid Power up with lockout setting
Invalid Pre-ignition time setting
Invalid Pre-purge rate setting
Invalid Pre-purge time setting
Invalid Purge rate proving setting
Invalid Run flame failure response setting
Invalid Run stabilization time setting
Invalid Stack limit enable setting
Invalid Stack limit response setting
Unconfigured Delta T limit set point setting
Unconfigured DHW high limit set point setting
Unconfigured Outlet high limit set point setting
Unconfigured Stack limit set point setting
Invalid DHW demand source setting
Invalid Flame threshold setting
Invalid Outlet high limit set point setting
Invalid DHW high limit set point setting
Invalid Stack limit set point setting
Invalid Modulation output setting
Invalid CH demand source setting
70
Note
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Disabled
Disabled
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Tft Series
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-3 Hold and Lockout Codes
Code Description
4
5
6
7
1
2
3
8
9
231
232
233
234
235
236
237
Invalid Delta T limit delay setting
Invalid Pressure sensor type setting
Invalid IAS closed response setting
Invalid Outlet high limit enable setting
Invalid Outlet connector type setting
Invalid Inlet connector type setting
Invalid DHW connector type setting
Invalid Stack connector type setting
238
239
240
241
242
243
244
Invalid Header connector type setting
Invalid Outdoor connector type setting
Exchanger sensor not allowed with stack connector setting
Invalid DHW auto detect configuration
Invalid UV with spark interference not compatible with Igniter on throughout
245
246
247
248
249
Invalid Outlet connector type setting for T-rise
4-20mA cannot be used for both modulation and setpoint control
Invalid ILK bounce detection enable
Invalid forced recycle interval
STAT cannot be demand source when Remote Stat is enabled
250
251
Invalid Fan speed error response
Lead drop-stage on error setting does not match drop method configuration
252
253
254
255
256
257
258
Invalid Line frequency setting
Lead Lag modulation sensor not valid with setpoint source
Lead Lag modulation sensor not valid with local setpoint source
Lead Lag modulation sensor not valid with local modulation source
Selected Controller interaction enable setting is not allowed
Controller interaction enable does not match neighbor stack fault setting
Controller ID must be non-zero if controller interaction is enabled
259
260
Modulation output must be fan if controller interaction is enabled
Asymmetrical paired (no flap) is set but flap switch input is energized
261
262
Neighbor burner control blower fault detected
Blower fault detected during flap test
263
264
Invalid DHW demand temperature setting
Invalid preferred outlet high limit setting
265
Invalid preferred lightoff rate setting
266
Invalid preferred stack limit rate setting
Table 16-4 Alert Codes
Code
0
Description
None (No alert)
Alert PCB was restored from factory defaults
Safety configuration parameters were restored from factory defaults
Configuration parameters were restored from factory defaults
Invalid Factory Invisibility PCB was detected
Invalid Factory Range PCB was detected
Invalid range PCB record has been dropped
EEPROM lockout history was initialized
Switched application annunciation data blocks
Switched application configuration data blocks
Note
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
71
Trinity
│
Installation and Operation Instructions
Table 16-4 Alert Codes
Code Description
39
40
41
42
43
35
36
37
38
28
29
30
31
32
33
34
24
25
26
27
19
20
21
22
23
15
16
17
18
10
11
12
13
14
53
54
55
56
57
58
48
49
50
51
52
44
45
46
47
Configuration was restored from factory defaults
Backup configuration settings was restored from active configuration
Annunciation configuration was restored from factory defaults
Annunciation configuration was restored from backup
Safety group verification table was restored from factory defaults
Safety group verification table was updated
Invalid Parameter PCB was detected
Invalid Range PCB was detected
Alarm silence time exceeded maximum
Invalid safety group verification table was detected
Backdoor password could not be determined
Invalid safety group verification table was not accepted
CRC errors were found in application configuration data blocks
Backup Alert PCB was restored from active one
RESERVED
Lead Lag operation switch was turned OFF
Lead Lag operation switch was turned ON
Safety processor was reset
Application processor was reset
Burner switch was turned OFF
Burner switch was turned ON
Program Module (PM) was inserted into socket
Program Module (PM) was removed from socket
Alert PCB was configured
Parameter PCB was configured
Range PCB was configured
Program Module (PM) incompatible with product was inserted into socket
Program Module application parameter revision differs from application processor
Program Module safety parameter revision differs from safety processor
PCB incompatible with product contained in Program Module
Parameter PCB in Program Module is too large for product
Range PCB in Program Module was too large for product
Alert PCB in Program Module was too large for product
IAS start check was forced on due to IAS enabled
Low voltage was detected in safety processor
High line frequency occurred
Low line frequency occurred
Invalid subsystem reset request occurred
Write large enumerated Modbus register value was not allowed
Maximum cycle count was reached
Maximum hours count was reached
Illegal Modbus write was attempted
Modbus write attempt was rejected (NOT ALLOWED)
Illegal Modbus read was attempted
Safety processor brown-out reset occurred
Application processor watchdog reset occurred
Application processor brown-out reset occurred
Safety processor watchdog reset occurred
Alarm was reset by the user at the control
72
Tft Series
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-4 Alert Codes
Code Description
103
104
105
106
107
108
98
99
100
101
102
94
95
96
97
73
74
75
76
68
69
70
71
72
64
65
66
67
59
60
61
62
63
Burner control firing rate was > absolute max rate
Burner control firing rate was < absolute min rate
Burner control firing rate was invalid, % vs. RPM
Burner control was firing with no fan request
Burner control rate (non-firing) was > absolute max rate
Burner control rate (non-firing) was < absolute min rate
Burner control rate (non-firing) was absent
Burner control rate (non-firing) was invalid, % vs. RPM
Fan off cycle rate was invalid, % vs. RPM
Set point was over ridden due to sensor fault
Modulation was over ridden due to sensor fault
No demand source was set due to demand priority conflicts
CH 4-20mA signal was invalid.
Flame strength rate differential was invalid
Flame strength step rate was invalid
Periodic forced recycle
Absolute max fan speed was out of range
Absolute min fan speed was out of range
89
90
91
92
93
85
86
87
88
77
78
79
80
Fan gain down was invalid
Fan gain up was invalid
Fan minimum duty cycle was invalid
Fan pulses per revolution was invalid
81 Fan PWM frequency was invalid
82-83 RESERVED
84 Lead Lag CH 4-20mA water temperature setting was invalid
No Lead Lag add stage error threshold was configured
No Lead Lag add stage detection time was configured
No Lead Lag drop stage error threshold was configured
No Lead Lag drop stage detection time was configured
Lead Lag all boiler off threshold was invalid
Modulation output type was invalid
Firing rate control parameter was invalid
Forced rate was out of range vs. min/max modulation
Forced rate was invalid, % vs. RPM
Slow start ramp value was invalid
Slow start degrees value was invalid
Slow start was ended due to outlet sensor fault
Slow start was end due to reference set point fault
CH max modulation rate was invalid, % vs. RPM
CH max modulation rate was > absolute max rate
CH modulation range (max minus min) was too small (< 4% or 40 RPM)
DHW max modulation rate was invalid, % vs. RPM
DHW max modulation rate was > absolute max rate
DHW modulation range (max minus min) was too small (< 4% or 40 RPM)
Min modulation rate was < absolute min rate
Min modulation rate was invalid, % vs. RPM
Manual rate was invalid, % vs. RPM
Slow start enabled, but forced rate was invalid
Analog output hysteresis was invalid
73
Trinity
│
Installation and Operation Instructions
Table 16-4 Alert Codes
Code Description
131
132
133
134
135
136
137
123
124
125
126
127
128
129
130
116
117
118
119
120
121
122
109
110
111
112
113
114
115
155
157
158
159
160
161
162
163
164
165
166
138
139
140
146
147
148
149
151
152
Analog modulation output type was invalid
IAS open rate differential was invalid
IAS open step rate was invalid
Mix max modulation rate was invalid, % vs. RPM
Mix max modulation rate was > absolute max or < absolute min rates
Mix modulation range (max minus min) was too small (< 4% or 40 RPM)
Fan was limited to its minimum duty cycle
Manual rate was > CH max modulation rate
Manual rate was > DHW max modulation rate
Manual rate was < min modulation rate
Manual rate in Standby was > absolute max rate
Modulation commanded rate was > CH max modulation rate
Modulation commanded rate was > DHW max modulation rate
Modulation commanded rate was < min modulation rate
Modulation rate was limited due to outlet limit
Modulation rate was limited due to Delta-T limit
Modulation rate was limited due to stack limit
Modulation rate was limited due to anti-condensation
Fan Speed out of range in RUN
Modulation rate was limited due to IAS was open
Slow start ramp setting of zero will result in no modulation rate change
No forced rate was configured for slow start ramp
CH demand source was invalid
CH P-gain was invalid
CH I-gain was invalid
CH D-gain was invalid
CH OFF hysteresis was invalid
CH ON hysteresis was invalid
CH sensor type was invalid
CH hysteresis step time was invalid
CH remote control parameter was invalid
CH ODR not allowed with remote control
CH control was suspended due to fault
CH header temperature was invalid
CH outlet temperature was invalid
CH steam pressure was invalid
Minimum water temperature parameter was greater than setpoint
Minimum water temperature parameter was greater than time of day setpoint
CH modulation rate source parameter was invalid
DHW demand source was invalid
DHW P-gain was invalid
DHW I-gain was invalid
DHW D-gain was invalid
DHW OFF hysteresis was invalid
DHW ON hysteresis was invalid
DHW hysteresis step time was invalid
DHW sensor type was invalid
Inlet sensor type was invalid for DHW
Outlet sensor type was invalid for DHW
74
Tft Series
Tft Series Installation and Operation Instructions
│
Trinity
194
195
196
197
198
199
200
185
186
187
188
189
190
191
192
193
178
179
180
181
182
183
184
167
168
169
170
171
172
173
174
175
176
177
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
Table 16-4 Alert Codes
Code Description
DHW storage OFF hysteresis was invalid
DHW storage ON hysteresis was invalid
DHW modulation sensor type was invalid
DHW modulation sensor was not compatible for Auto mode
DHW control was suspended due to fault
DHW temperature was invalid
DHW inlet temperature was invalid
DHW outlet temperature was invalid
DHW high limit must be disabled for Auto mode
DHW sensor type was not compatible for Auto mode
DHW priority source setting was invalid
DHW priority method setting was invalid
CH S5 (J8-11) sensor was invalid
CH Inlet temperature was invalid
CH S10 (J10-7) sensor was invalid
Lead Lag CH setpoint source was invalid
Lead Lag P-gain was invalid
Lead Lag I-gain was invalid
Lead Lag D-gain was invalid
Lead Lag OFF hysteresis was invalid
Lead Lag ON hysteresis was invalid
Lead Lag slave enable was invalid
Lead Lag hysteresis step time was invalid
No Lead Lag Modbus port was assigned
Lead Lag base load common setting was invalid
Lead Lag DHW demand switch setting was invalid
Lead Lag Mix demand switch setting was invalid
Lead Lag modulation sensor setting was invalid
Lead Lag backup modulation sensor setting was invalid
Lead Lag slave mode setting was invalid
Lead Lag rate allocation setting was invalid
Lead selection setting was invalid
Lag selection setting was invalid
Lead Lag slave return setting was invalid
Lead Lag add stage method setting was invalid
STAT may not be a Lead Lag CH demand source when Remote Stat is enabled
Lead Lag base load rate setting was invalid
Lead Lag master was suspended due to fault
Lead Lag slave was suspended due to fault
Lead Lag header temperature was invalid
Lead Lag was suspended due to no enabled Program Module installed
Lead Lag slave session has timed out
Too many Lead Lag slaves were detected
Lead Lag slave was discovered
Incompatible Lead Lag slave was discovered
No base load rate was set for Lead Lag slave
Lead Lag slave unable to fire before demand to fire delay expired
Adding Lead Lag slave aborted due to add requirement change
No Lead Lag slaves available to service demand
75
232
233
234
235
236
237
238
239
240
225
226
227
228
229
230
231
216
217
218
219
220
221
222
223
224
251
252
253
254
255
259
260
261
241
243
244
245
246
247
248
249
250
262
263
264
265
266
267
268
Trinity
│
Installation and Operation Instructions
Table 16-4 Alert Codes
Code Description
No Lead Lag active service was set due to demand priority conflicts
No Lead Lag add stage method was specified
No Lead Lag drop stage method was specified
Using backup Lead Lag header sensor due to sensor failure
Lead Lag frost protection rate was invalid
Lead Lag drop stage method setting was invalid
CH frost protection temperature was invalid
CH frost protection inlet temperature was invalid
DHW frost protection temperature was invalid
No anticondensation setpoint was configured for frost protection
RESERVED
DHW priority override time was not derated due to invalid outdoor temperature
Warm weather shutdown was not checked due to invalid outdoor temperature
Lead Lag slave communication timeout
RESERVED
LL set point was invalid
LL time of day set point was invalid
LL outdoor temperature was invalid
LL ODR time of day set point was invalid
LL ODR time of day set point exceeded normal set point
LL max outdoor set point was invalid
LL min outdoor set point was invalid
LL min water set point was invalid
LL outdoor temperature range was too small (minimum 12 C / 22 F)
LL water temperature range was too small (minimum 12 C / 22 F)
Lead Lag DHW setpoint was invalid
Lead Lag CH demand switch was invalid
Lead Lag ODR min water temperature was invalid
RESERVED
CH set point was invalid
CH time of day set point was invalid
CH outdoor temperature was invalid
CH ODR time of day setpoint was invalid
CH ODR time of day set point exceeds normal set point
CH max outdoor set point was invalid
CH min outdoor setp oint was invalid
CH min water set point was invalid
CH outdoor temperature range was too small (minimum 12 C / 22 F)
CH water temperature range was too small (minimum 12 C / 22 F)
CH ODR min water temperature was invalid
RESERVED
DHW set point was invalid
DHW time of day set point was invalid
DHW storage setpoint was invalid
STAT may not be a DHW demand source when Remote Stat is enabled
No DHW anticondensation setpoint was configured
No CH anticondensation setpoint was configured
STAT may not be a CH demand source when Remote Stat is enabled
CH 4mA water temperature setting was invalid
76
Tft Series
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-4 Alert Codes
Code Description
294
295
296
297
298
299
300
301
287
288
289
290
291
292
293
278
279
280
281
282
283
284
285
286
269
270
271
272
273
274
275
276
277
309
310
311
312
313
314
315
316
317
302
303
304
305
306
307
308
CH 20mA water temperature setting was invalid
Steam 4mA water temperature setting was invalid
Steam 20mA water temperature setting was invalid
Abnormal Recycle: Pressure sensor fault
Abnormal Recycle: Safety relay drive test failed
Abnormal Recycle: Demand off during Pilot Flame Establishing Period
Abnormal Recycle: LCI off during Drive to Purge Rate
Abnormal Recycle: LCI off during Measured Purge Time
Abnormal Recycle: LCI off during Drive to Light off Rate
Abnormal Recycle: LCI off during Pre-Ignition test
Abnormal Recycle: LCI off during Pre-Ignition time
Abnormal Recycle: LCI off during Main Flame Establishing Period
Abnormal Recycle: LCI off during Ignition period
Abnormal Recycle: Demand off during Drive to Purge Rate
Abnormal Recycle: Demand off during Measured Purge Time
Abnormal Recycle: Demand off during Drive to Light off Rate
Abnormal Recycle: Demand off during Pre-Ignition test
Abnormal Recycle: Demand off during Pre-Ignition time
Abnormal Recycle: Flame was on during Safe Start check
Abnormal Recycle: Flame was on during Drive to Purge Rate
Abnormal Recycle: Flame was on during Measured Purge Time
Abnormal Recycle: Flame was on during Drive to Light off Rate
Abnormal Recycle: Flame was not on at end of Ignition period
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
Abnormal Recycle: Flame was lost early in Run
Abnormal Recycle: Flame was lost during Run
Abnormal Recycle: Leakage test failed
Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate
Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time
Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time
Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period
Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
Abnormal Recycle: ILK off during Drive to Purge Rate
Abnormal Recycle: ILK off during Measured Purge Time
Abnormal Recycle: ILK off during Drive to Light off Rate
Abnormal Recycle: ILK off during Pre-Ignition test
Abnormal Recycle: ILK off during Pre-Ignition time
Abnormal Recycle: ILK off during Main Flame Establishing Period
Abnormal Recycle: ILK off during Ignition period
Run was terminated due to ILK was off
Run was terminated due to interrupted air flow switch was off
Stuck reset switch
Run was terminated due to fan failure
Abnormal Recycle: Fan failed during Drive to Purge Rate
Abnormal Recycle: Fan failed during Measured Purge Time
Abnormal Recycle: Fan failed during Drive to Light off Rate
Abnormal Recycle: Fan failed during Pre-Ignition test
77
Trinity
│
Installation and Operation Instructions
Table 16-4 Alert Codes
Code Description
343
344
345
346
347
348
349
350
351
336
337
338
339
340
341
342
327
328
329
330
331
332
333
334
335
318
319
320
321
322
323
324
325
326
361
362
363
364
365
366
352
353
354
355
356
357
358
359
360
Abnormal Recycle: Fan failed during Pre-Ignition time
Abnormal Recycle: Fan failed during Ignition period
Abnormal Recycle: Fan failed during Main Flame Establishing Period
Abnormal Recycle: Main Valve off after 10 seconds of RUN
Abnormal Recycle: Pilot Valve off after 10 seconds of RUN
Abnormal Recycle: Safety Relay off after 10 seconds of RUN
Abnormal Recycle: Hardware flame bias
Abnormal Recycle: Hardware static flame
Abnormal Recycle: Hardware flame current invalid
Abnormal Recycle: Hardware flame rod short
Abnormal Recycle: Hardware invalid power
Abnormal Recycle: Hardware invalid AC line
Abnormal Recycle: Hardware SLO flame ripple
Abnormal Recycle: Hardware SLO flame sample
Abnormal Recycle: Hardware SLO flame bias range
Abnormal Recycle: Hardware SLO flame bias heat
Abnormal Recycle: Hardware SLO spark stuck
Abnormal Recycle: Hardware SLO spark changed
Abnormal Recycle: Hardware SLO static flame
Abnormal Recycle: Hardware SLO rod shorted
Abnormal Recycle: Hardware SLO AD linearity
Abnormal Recycle: Hardware SLO bias not set
Abnormal Recycle: Hardware SLO bias shorted
Abnormal Recycle: Hardware SLO electronics
Abnormal Recycle: Hardware processor clock
Abnormal Recycle: Hardware AC phase
Abnormal Recycle: Hardware A2D mismatch
Abnormal Recycle: Hardware VSNSR A2D
Abnormal Recycle: Hardware 28V A2D
Abnormal Recycle: Hardware HFS IAS shorted
Abnormal Recycle: Hardware PII INTLK shorted
Abnormal Recycle: Hardware HFS LCI shorted
Abnormal Recycle: Hardware HFS LFS shorted
Abnormal Recycle: Invalid zero crossing
Abnormal Recycle: fault stack sensor
Abnormal Recycle: stack limit
Abnormal Recycle: delta T limit
Abnormal Recycle: fault outlet sensor
Abnormal Recycle: outlet high limit
Abnormal Recycle: fault DHW sensor
Abnormal Recycle: DHW high limit
Abnormal Recycle: fault inlet sensor
Abnormal Recycle: Check Parameters Failed
Internal error: No factory parameters were detected in control
Internal error: PID iteration frequency was invalid
Internal error: Demand-Rate interval time was invalid
Internal error: Factory calibration parameter for modulation was invalid
Internal error: CH PID P-scaler was invalid
Internal error: CH PID I-scaler was invalid
78
Tft Series
Tft Series Installation and Operation Instructions
│
Trinity
Table 16-4 Alert Codes
Code Description
457
458
459
460
461
462
463
464
465
448
449
450
451
452
453
454
455
456
466
467
468
469
470
471
472
473
474
475
476
367
368
369
370
371
Internal error: CH PID D-scaler was invalid
Internal error: DHW PID P-scaler was invalid
Internal error: DHW PID I-scaler was invalid
Internal error: DHW PID D-scaler was invalid
Internal error: Lead Lag master PID P-scaler was invalid
372
373
Internal error: Lead Lag master PID I-scaler was invalid
Internal error: Lead Lag master PID D-scaler was invalid
374
375
Abnormal Recycle: Hardware flame bias high
Abnormal Recycle: Hardware flame bias low
376
377
Abnormal Recycle: Hardware flame bias delta high
Abnormal Recycle: Hardware flame bias delta low
378
379
Abnormal Recycle: Hardware flame bias dynamic high
Abnormal Recycle: Hardware flame bias dynamic low
380
381
382
383
Abnormal Recycle: Fan Speed Not Proven
Abnormal Recycle: Fan Speed Range Low
Abnormal Recycle: Fan Speed Range High
Abnormal Recycle: Pre-Ignition test failed, recycle
384-
388 RESERVED
389 Abnormal Recycle: AC power frequency Mismatch
390-447 RESERVED
Flame too low
Modulation rate was limited due to flame strength
RESERVED
Circulator control was invalid
Circulator P-gain was invalid
Circulator I-gain was invalid
Circulator temperature was invalid
Circulator outlet temperature was invalid
Circulator inlet temperature was invalid
Circulator outlet temperature was invalid
Circulator sensor choice was invalid
Circulator PID setpoint was invalid
LCI demand lost in run
Demand lost in run
STAT demand lost in run
Demand lost in run due to no flame
LCI lost in Combustion Pressure Establishing Period
LCI lost in Combustion Pressure Stabilizing Period
RESERVED
Internal error: EEPROM write was attempted before EEPROM was initialized
Internal error: EEPROM cycle count address was invalid
Internal error: EEPROM days count address was invalid
Internal error: EEPROM hours count address was invalid
Internal error: Lockout record EEPROM index was invalid
Internal error: Request to write PM status was invalid
Internal error: PM parameter address was invalid
Internal error: PM safety parameter address was invalid
Internal error: Invalid record in lockout history was removed
Internal error: EEPROM write buffer was full
79
Trinity
│
Installation and Operation Instructions
Table 16-4 Alert Codes
Code Description
553
564
600
601
603
604
605
606
609
495
496
497
498
499
500
550
610
611
612
613
614
615
616
622
623
624
629
486
487
488
489
490
491
492
493
494
477
478
479
480
481
482
483
484
485
Internal error: Data too large was not written to EEPROM
Internal error: Safety key bit 0 was incorrect
Internal error: Safety key bit 1 was incorrect
Internal error: Safety key bit 2 was incorrect
Internal error: Safety key bit 3 was incorrect
Internal error: Safety key bit 4 was incorrect
Internal error: Safety key bit 5 was incorrect
Internal error: Safety key bit 6 was incorrect
Internal error: Safety key bit 7 was incorrect
Internal error: Safety key bit 8 was incorrect
Internal error: Safety key bit 9 was incorrect
Internal error: Safety key bit 10 was incorrect
Internal error: Safety key bit 11 was incorrect
Internal error: Safety key bit 12 was incorrect
Internal error: Safety key bit 13 was incorrect
Internal error: Safety key bit 14 was incorrect
Internal error: Safety key bit 15 was incorrect
Internal error: Safety relay timeout
Internal error: Safety relay commanded off
Internal error: Unknown safety error occurred
Internal error: Safety timer was corrupt
Internal error: Safety timer was expired
Internal error: Safety timings
Internal error: Safety shutdown
Delta T inlet/outlet limit was exceeded
Inlet/outlet inversion occurred
Outlet T-rise limit was exceeded
Delta T inlet temperature was invalid
Delta T outlet temperature was invalid
CH ODR boost max offpoint temperature was invalid
CH ODR boost max offpoint temperature was too low
Lead Lag ODR boost max offpoint temperature was invalid
Lead Lag ODR boost max offpoint temperature was too low
Time to rotate lead boiler to next firing slave
Time to rotate lead boiler to next available slave
Time to rotate lead boiler to first firing slave in order
Time to rotate lead boiler to lowest running slave
Lead boiler was rotated based on new firing sequence order
Lead boiler was rotated based on measured run time
Parameter PCB was switched to backup
Range PCB was switched to backup
Lead Lag modulation sensor was not valid with setpoint source
Lead Lag modulation sensor was not valid with local setpoint source
Lead Lag modulation sensor was not valid with local modulation rate source
Disagreement on number of interacting controls
80
Tft Series
Tft Series Installation and Operation Instructions
│
Trinity
17.0 PARTS LIST
For a list of parts that corresponds to the item numbers in the callouts, refer to Table 17-1. Note that some item numbers may appear more than once in the parts list depending on which model number is being referenced.
Building Owners - Replacement parts are available from your stocking wholesaler. Contact your local Installer or Wholesaler for assistance with parts.
Wholesalers - Contact NY Thermal Inc. directly when ordering replacement parts, 1-506-657-6000.
Installers - Contact NY Thermal Inc. directly if technical assistance required, 1-800-688-2575.
Figure 17-1(a) Tft Heat Engine and Gas Train (Tft60-110 Illustrated)
34
25
36
11
2
10
5
6
12
1
32
4
7
8
9
9
14
105
13
33
26
15
21
17
40
43
15
18
17
16
81
74
37
Trinity
│
Installation and Operation Instructions
Figure 17-1(b) Tft Cabinet, Vent and Air-inlet Parts (Tft60-110 Illustrated)
41
44
33
42
46
75
76
45
73
78
45
80
28
39
20
37
74
77
82
27
48
72
95
55
35
49
Tft Series
57
85
56
68
63
61
58
60
Figure 17-1(c) Tft Control Panel
23
65
67
69
54
70
52
59
62
70
107
82
Tft Series Installation and Operation Instructions
│
Trinity
Figure 17-1(d) Tft Installation Kit
19 108
112
110
109
92
31
93
38
38
113
111
8
8
8
71
30
83
111
79
103
50
119
Natural to LP Conversion Kit
Table 17-1 Trinity Tft Parts List
Item Part #
1 84547
Models
Tft155-250
1
1
2
84552
84541
84548
Tft300-399
Tft60-110
Tft155-250
2
2
4
5
84553
84542
84441
82052
Tft300-399
Tft60-110
Tft60-399
Lx150, M100(V), Tft60-110,
Ti100-150, Ts80
5
5
6
6
7
7
7
7
8
8
8
8
8
Description
Premix Burner, Tft155-250
Premix Burner, Tft300-399
Premix Burner, Tft60-110
Premix Burner Gasket Tft155-250
Premix Burner Gasket Tft300-399
Premix Burner Gasket, Tft60-110
Blower Gasket Tft60-399
EBM Blower RG130
82661 (82661-1) Lx150E, Lx200-300, Tft155-
250, Ti200
82994 (82994-1) Lx400, Tft300-399, Ti400
82054-2 (84299) Lx150-300, M100(V), T150-
200, Tft60-250, Ti100-200,
Ts80, Tx200, Tx200C
83106
81994
Lx400, Tft300-399, Ti400
Lx300, T150-200, Tft155-
250, Tx200, Tx200C
82990
84433
83205
82650
84157
84471
84470
84434
Lx400, Tft300-399, Ti400
Tft110
Ts80, Tft60-85, Ti100
Lx150-200, M100(V), Tft110,
Ti150-200
Lx300, Tft155-250, Tx200,
Tx200C
Tft300-399 (LP)
Tft300-399 (NG)
Tft60-85
EBM Blower Kit RG148/1200-3633 (55667.01970)
EBM Blower Kit RG148/Enhanced (55667.21200)
Venturi Gasket, Cork
O-Ring, Venturi To Blower Lx/Ti400, Tft300-399
Venturi 051
Venturi 45900450-010
Venturi 002
Venturi 003
Gas Valve Orifice 5.2mm, LP
Gas Valve Orifice 6.2mm, LP
Gas Valve Orifice 7.4mm, LP
Gas Valve Orifice 9.6 mm, NG
Gas Valve Orifice 4.15mm, LP
83
Trinity
│
Installation and Operation Instructions Tft Series
Item Part #
9 82054 (83204)
9 82989
10 83870
Models
Lx150
–300, M100(V), T150-
200, Tft60-250, Ti100-200,
Ts80
Lx400, Tft300-399, Ti400
Lx150-500, Tft60-399, Ts80 Ignition Electrode, Dual (Includes P/N: 82774)
11
12 82600 (82600-1) Lx150-300, M100(V), Tft60-
250, Ti100-200, Ts80
13
82774
83194
13 83883
Lx150-800, Tft60-399,
Ti100-400, Ts80
Lx400, Tft300-399, Ti400
M100(V), Lx150-300, Tft60-
250, Ti100-200, Ts80
Description
Gas Valve VK8115V1341B (Valve Only)
Gas Valve VR8615VB 1044B
Igniter Gasket, Graphite (Ignition Electrode / Flame
Rod)
Gas Valve Regulator Vent Upgrade Kit c/w Clamp
(Includes P/N: 83134)
Gas Valve Inlet O-Ring Gasket
Gas Valve Inlet O-Ring Gasket
14 84435
14 84442
15 84039
15 84419
16 84424
17 84464
17 84465
17 84463
Tft300-399
Tft60-250
Tft300-399
Tft60-250
Tft60-399
Tft155-250
Tft300-399
Gas Valve Adapter 3/4" NPT Elbow
Gas Valve Adapter 1/2" NPT Straight
Sensor, Supply & Return Dual Tft300-399
Sensor, Supply & Return Dual Tft60-250
Low Water Cut Off
Pipe Coupling, Groove Joint, 1-1/4" Tft155-250
Pipe Coupling, Groove Joint, 1-1/2" Tft300-399
18
18
18
19
20
21
23
25
26
26
30
31
32
32
84457
84460
84454
84474
83608
21 84458
21 84461
84455
84423
84546
84456
84459
26 84453
27 84505
27 84504
28 84637
30 82913 (83510)
85119
84479
84549
84554
32 84545
33 84551
33 84556
33 84544
34 84550
34 84555
34 84543
Tft60-110 Pipe Coupling, Groove Joint, 1"
Tft60-110
Supply Pipe, SS, 1-1/4" Tft155-250
Tft300-399
Tft60-110
Tft60-399, Tx51-200,
Tx200C
Supply Pipe, SS 1-1/2"
Supply Pipe, SS, 1"
Auto Air Vent, 1/2" NPT
Lx150-400, Tft60-399, Ts80 Flue Sensor, Dual
Tft155-250
Tft300-399
Tft60-110
Tft60-399, Tx51-200,
Tx151C, Tx200C
Return Pipe, SS 1-1/4"
Return Pipe, SS 1-1/2"
Return Pipe, SS 1"
Receptacle, 120VAC
Tft60-399
Tft155-250
Tft300-399
Tft60-110
Tft300-399
Sight Glass Assembly Tft-series
Heat Exchanger ASME Tft155-250
Heat Exchanger ASME Tft300-399
Heat Exchanger ASME Tft60-110
Tube Strap Tft300-399
Tft60-250
Tft60-399
M100(V), Tft60-399, Ti100-
400, Tx51-200, Tx151C,
Tx200C
Tft60-399, VM110, VM110P Condensate Trap (Used on Tft models prior to 15140)
Tft60-399 Elbow, Brass, Street 90, 3/4"
Tft155-250
Tft300-399
Burner Plate Gasket Tft155-250
Burner Plate Gasket Tft300-399
Tft60-110
Tft155-250
Tft300-399
Tft60-110
Tft155-250
Tft300-399
Tft60-110
Tube Strap Tft60-250
Plug, Flue Sensor, Tft-series
Condensate Trap (Used on Tft models prior to 15140)
Burner Plate Gasket Tft60-110
Burner Plate Ceramic Disc Tft155-250
Burner Plate Ceramic Disc Tft300-399
Burner Plate Ceramic Disc Tft60-110
Burner Plate Tft155-250
Burner Plate Tft300-399
Burner Plate Tft60-110
84
Tft Series Installation and Operation Instructions
│
Trinity
Item Part #
35 84214
Models
Ts80, Tft60-399, Tx51-200,
Tx151C, Tx200C
36 82762 (82762-1) Lx150-500, M100(V), Tft60-
399, Ti100-400, Ts80
37 82099
37 83951 (82100)
38 82615
Lx150-300, M100(V), T150-
200, Tft60-250, Ti100-200,
Ts80, Tx200, Tx200C
Lx400, Tft300-399, Ti400
Tft60-110, Tx51-151,
Tx151C
39 84558
39 84559
39 84557
40 83718
41
41
41
84438
84451
84437
42 84450
42 84436
43 85107
44 84497
Tft155-250
Tft300-399
Tft60-110
Description
Grommet, Diaphragm, 1/2"
Flame Rod Lx/Ti/Ts/Tft (60-500) (Includes P/N: 82774)
1-1/2" MJ Coupling
2" MJ Coupling
Round Mesh Vent Screen, 2"
Tft60-399, VM110, VM110P Hose Clamp, 1-1/16 to 1-
1/2”
Tft155-250
Tft300-399
Tft60-110
Tft300-399
Tft60-250
Air Inlet Assembly Tft155-250
Air Inlet Assembly Tft300-399
Air Inlet Assembly Tft60-110
Flue Outlet Adapter SS 3" (304066) Tft155-250
Flue Outlet Adapter SS 4" (304081) Tft300-399
Flue Outlet Adapter SS 3" (304065 D) Tft60-110
Air Inlet Adapter SS 4" Tft300-399
Air Inlet Adapter SS 3" Tft60-250
45
45 84566
46 83505
46
47
47
47
84567
83923
83506
84439
84440
48 TBD
49 85163
50 83955
52 83592-TFT
Tft60-399, VM110, VM110P Condensate Drain Adapter Tube
Tft60-399 Exhaust Test Plug, EPDM Tft60-399
Tft300-399
Tft60-250
Lx150-300, Tft60-250, Ts80,
Tx51-200, Tx151C, Tx200C
Lx400, Tft300-399
Lx150-200, Tft60-110
Tft155-250
Tft300-399
Wall Mount Bracket Top Tft300-399
Wall Mount Bracket Top Tft60-250
Grommet, Vinyl, 7/8” OD, 1/2" IPS (1020T)
Grommet, Vinyl, 3/4" IPS (1020)
Grommet, Vinyl, 1-3/8" OD (1300)
Grommet, Vinyl 1-1/4" IPS (1625) Tft155-250
Grommet, Vinyl 1-1/2" IPS (1875) Tft300-399
52
54
55
55
55
56
57
84653
84420
84582
84583
84581
83707
83724
Tft60-399 Air Switch Bracket
Tft60-399, VM110, VM110P Blocked Condensate Drain / Blocked Vent Switch
Lx300-400, Tft60-399 Wall Mount Bracket Bottom Lx300-400, Tft60-399
Tft60-399 Tft Touchscreen Upgrade Kit
(Models manufactured before 6/1/2012)
Lx150-800, Tft60-399
Tft60-399
Tft155-250
Tft300-399
Tft60-110
Display S7999D, Black Touch Screen (Models manufactured after 6/1/2012)
Terminal, Barrier, 2 Row, 8 Position
Control Panel Support Tft155-250
Control Panel Support Tft300-399
Control Panel Support Tft60-110
Ignition Coil Q652B1006/B Lx150-800, Tft60-399, Tx51-
200, Tx151C, Tx200C
Lx150-800, Tft60-399, Tx51-
200, Tx151C, Tx200C
Spark Igniter Wire 12"
58 82250 Lx150-800, Tft60-399, Ts80 Snap Bushing 1"
59 83592-1 (84015) Lx150-800, Tft60-399 Power Supply, White Touch Screen Only
60 82457 (83190) Lx150-400, M100(V), T150-
200, Tft60-399, Ti100-400,
Ts80
Transformer 24V, 40VA
61 77777
62 84590
63 84584
65 84421
67 83517
Tft60-399
Tft60-399
Tft60-399
Tft60-399
Honeywell Sola Controller R7910B1015/B Tft60-399
Control Panel Cover Tft60-399
Control Panel Tft60-399
Terminal, Barrier, 2 Row, 9 Position
Lx150-400, Tft60-399, Ts80 Fuse, 2A, 32V, Plug Style
85
Trinity
│
Installation and Operation Instructions Tft Series
Item Part #
68
69
70
70
70
70
84192
83837
84586
84588
TBD
TBD
Models Description
Lx150-800, Tft60-399, Ts80 Fuse Holder, Panel Mount, 20A, 250VAC max
Lx150-800, Tft60-399, Ts80 Fuse, 7A, 250VAC, Barrel Style, Fast Blow
Tft60-399 Display Mounting Support, White Touch Screen Tft
(Models manufactured before 6/1/2012)
Tft60-399
Tft60-399
Display Cover, White Touch Screen Tft (Models manufactured before 6/1/2012)
Display Mounting Support, Black Touch Screen Tft
(Models manufactured after 6/1/2012)
Tft60-399 Display Cover, Black Touch Screen Tft (Models manufactured after 6/1/2012)
Outdoor Sensor 10K 71 81027-1 (83604) Lx150-800, M100(V), T150-
200, Tft60-399, Ti100-400,
Ts80, Tx51-200, Tx151C,
Tx200C
72 84578
72 84577
Tft300-399
Tft60-250
Front Cover Tft300-399
Front Cover Tft60-250
73 84571
73 84572
73 84570
74 84574
74 84575
Tft155-250
Tft300-399
Tft60-110
Tft155-250
Tft300-399
Right Side Tft155-250
Right Side Tft300-399
Right Side Tft60-110
Left Side Tft155-250
Left Side Tft300-399
74 84573
75 84564
75 84565
75 84563
76 84561
76 84562
76 84560
77 84569
77
78
78
79
79
80
80
80
TBD
84568
TBD
83962
83206
84576
TBD
TBD
81 84010
82 84579
82
83
84580
83135
85 84585
85 TBD
92 84472
92 84473
92 82869
93 84467
93 84468
93 84466
Tft60-110
Tft155-250
Tft300-399
Tft60-110
Tft155-250
Tft300-399 Top Panel Tft300-399
Tft60-110 Top Panel Tft60-110
Tft60-250, VM110, VM110P Bottom Heat Exchanger Support Tft60-250, VM110,
VM110P
Tft300-399 Bottom Heat Exchanger Support Tft300-399
Tft60-250, VM110, VM110P Top Heat Exchanger Support Tft60-250, VM110,
VM110P
Tft300-399 Top Heat Exchanger Support Set Tft300-399
Lx400, Tft300-399, Ti400
Lx150-300, M100, M100V,
T150-200, Tft60-250, Ti100-
200, Ts80, Tx200, Tx200C
Gas Valve Orifice O-Ring Lx400, Tft300-399
Gas Valve to Venturi Screws & Seal
Tft60-110
Tft155-250
Tft300-399
Lx150-800, Tft60-399
Tft155-250
Back/Bottom Tft60-110
Back Tft155-250
Back Tft300-399
System Sensor, Pipe Sensor Lx/Tft
Bottom Tft155-250
Tft300-399 Bottom Tft300-399
Tft60-399, VM110, VM110P Hose Clamp, 9/16 to 1-
1/16”
Tft60-110 Spark Generator Support Bracket, Tft60-110
Tft155-399
Tft155-250
Tft300-399
Tft60-110
Tft155-250
Tft300-399
Tft60-110
Left Side Tft60-110
Top Panel Access Cover Tft155-250
Top Panel Access Cover Tft300-399
Top Panel Access Cover Tft60-110
Top Panel Tft155-250
Spark Generator Support Bracket, Tft155-399
Brass Bushing, 1-1/4" x 3/4" Tft155-250
Brass Bushing, 1-1/2" x 3/4" Tft300-399
Brass Bushing, 1" x 3/4" Tft60-110
Brass Tee, 1-1/4" x 1/2" x 1-1/4" Tft155-250
Brass Tee, 1-1/2" x 1/2" x 1-1/2" Tft300-399
Brass Tee, 1" x 1/2" x 1" Tft60-110
86
Tft Series Installation and Operation Instructions
│
Trinity
Item Part #
95 84095
105 82064
105 83016
107 84490
108 83991
108 83427
109 13701
110 84090
111 82616
111 83018
112 84492
112 84501
113 82782
113 84483
119 84471-1
Models
Lx500-800, Tft60-399, Ts80,
Tx51-200, Tx151C, Tx200C
Lx150-300, M100(V), T150-
200, Ti100-200, Tft60-250,
Ts80
Lx400, Tft300-399, Ti400
Lx500-800, Tft60-399
Lx150-200, M100(V), Tft60-
250, Ti100-200, Ts80
Lx300-600, Tft300-399
Lx150-400, M100(V), Tft60-
399, Ti100-400, Ts80, Tx51-
200, Tx151C, Tx200C
Lx150-400, M100(V), Tft60-
399, Ti100-400, Ts80, Tx51-
200
Lx150-200, M100(V), T150-
200, Tft60-250, Ti100-200,
Ts80, Tx51-200, Tx151C,
Tx200C
Lx300-600, Tft300-399,
Ti400
Lx150-300, M100(V), Tft60-
250, Ti100-200, Ts80,
Tx200, Tx200C
Tft300-399
Description
Plug, 7/8" Black Dome
Gas Valve Harness
Gas Valve Harness Lx/Ti400, Tft300-399
Switch, On-Off
CPVC Pipe 3", System 636, 5" Long
CPVC Pipe 4", System 636, 5" Long
Pressure Relief Valve, ASME, 3/4" NPT, 30psi
Pressure Gauge, Bottom Stem Mount, 60psi
Round Mesh Vent Screen, 3"
Round Mesh Vent Screen, 4" (300-600)
Natural Gas To LP Conversion Instructions (Included in 82650-1)
Natural Gas To LP Conversion Instructions (Included in 84471-1)
Conversion Decal (Included In 82650-1) Lx150-300, M100(V), Tft60-
250, Ti100-200, Ts80,
Tx200, Tx200C
Tft300-399
Tft300, Tft399
Conversion Decal (Included In 84471-1)
NG to LP Conversion Kit (Tft300-399)
87
Trinity
│
Installation and Operation Instructions
Visit us online
NY Thermal Inc. 30 Stonegate Dr. Saint John, NB E2H 0A4 Canada
Technical Assistance: 1-800-688-2575
Website: www.ntiboilers.com
Fax: 1-506-432-1135
88
Tft Series
advertisement
Related manuals
advertisement